INSTALLATION MANUAL
System Inverter Air Conditioners
FXNQ20A2VEB
FXNQ25A2VEB
FXNQ32A2VEB
FXNQ40A2VEB
FXNQ50A2VEB
FXNQ63A2VEB
CE - DECLARACION-DE-CONFORMIDAD
CE - DICHIARAZIONE-DI-CONFORMITA
CE - H
CE - ERKLRING OM-SAMSVAR
CE - ILMOITUS-YHDENMUKAISUUDESTA
CE - PROHLEN-O-SHOD
19 ob upotevanju dolob:
20 vastavalt nuetele:
21 :
22 laikantis nuostat, pateikiam:
23 ievrojot prasbas, kas noteiktas:
24 odriavajc ustanovenia:
25 bunun koullarna uygun olarak:
07 **
08 **
09 **
10 **
11 **
12 **
Tetsuya Baba
Managing Director
Pilsen, 1st of April 2015
13 **
14 **
15 **
16 **
17 **
18 **
19 **
20 **
21 **
22 **
23 **
24 **
25 **
0510260101
TUV (NB1856)
DAIKIN.TCF.024G5/02-2015
<C>
<B>
<A>
Machinery 2006/42/EC **
Electromagnetic Compatibility 2004/108/EC *
CE - ATITIKTIES-DEKLARACIJA
CE - ATBILSTBAS-DEKLARCIJA
CE - VYHLSENIE-ZHODY
CE - UYGUNLUK-BEYANI
16 megfelelnek az albbi szabvny(ok)nak vagy egyb irnyad dokumentum(ok)nak, ha azokat elrs szerint hasznljk:
17 speniaj wymogi nastpujcych norm i innych dokumentw normalizacyjnych, pod warunkiem e uywane s zgodnie z naszymi
instrukcjami:
18 sunt n conformitate cu urmtorul (urmtoarele) standard(e) sau alt(e) document(e) normativ(e), cu condiia ca acestea s fie utilizate n
conformitate cu instruciunile noastre:
19 skladni z naslednjimi standardi in drugimi normativi, pod pogojem, da se uporabljajo v skladu z naimi navodili:
20 on vastavuses jrgmis(t)e standardi(te)ga vi teiste normatiivsete dokumentidega, kui neid kasutatakse vastavalt meie juhenditele:
21 , ,
:
22 atitinka emiau nurodytus standartus ir (arba) kitus norminius dokumentus su slyga, kad yra naudojami pagal ms nurodymus:
23 tad, ja lietoti atbilstoi raotja nordjumiem, atbilst sekojoiem standartiem un citiem normatviem dokumentiem:
24 s v zhode s nasledovnou(mi) normou(ami) alebo inm(i) normatvnym(i) dokumentom(ami), za predpokladu, e sa pouvaj v slade
s naim nvodom:
25 rnn, talimatlarmza gre kullanlmas kouluyla aadaki standartlar ve norm belirten belgelerle uyumludur:
01 Directives, as amended.
02 Direktiven, gem nderung.
03 Directives, telles que modifies.
04 Richtlijnen, zoals geamendeerd.
05 Directivas, segn lo enmendado.
06 Direttive, come da modifica.
07 , .
08 Directivas, conforme alterao em.
09 .
08 esto em conformidade com a(s) seguinte(s) norma(s) ou outro(s) documento(s) normativo(s), desde que estes sejam utilizados de
acordo com as nossas instrues:
09 ,
:
10 overholder flgende standard(er) eller andet/andre retningsgivende dokument(er), forudsat at disse anvendes i henhold til vore
instrukser:
11 respektive utrustning r utfrd i verensstmmelse med och fljer fljande standard(er) eller andra normgivande dokument, under
frutsttning att anvndning sker i verensstmmelse med vra instruktioner:
12 respektive utstyr er i overensstemmelse med flgende standard(er) eller andre normgivende dokument(er), under forutssetning av at
disse brukes i henhold til vre instrukser:
13 vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien vaatimuksia edellytten, ett niit kytetn ohjeidemme
mukaisesti:
14 za pedpokladu, e jsou vyuvny v souladu s naimi pokyny, odpovdaj nsledujcm normm nebo normativnm dokumentm:
15 u skladu sa slijedeim standardom(ima) ili drugim normativnim dokumentom(ima), uz uvjet da se oni koriste u skladu s naim uputama:
DICz*** .
A DICz*** est autorizada a compilar a documentao tcnica de fabrico.
DICz*** .
DICz*** er autoriseret til at udarbejde de tekniske konstruktionsdata.
DICz*** r bemyndigade att sammanstlla den tekniska konstruktionsfilen.
DICz*** har tillatelse til kompilere den Tekniske konstruksjonsfilen.
06 Nota *
01 **
02 **
03 **
04 **
05 **
06 **
05 Nota *
04 Bemerk *
03 Remarque *
02 Hinweis *
01 Note *
EN60335-2-40,
01 are in conformity with the following standard(s) or other normative document(s), provided that these are used in accordance with our
instructions:
02 der/den folgenden Norm(en) oder einem anderen Normdokument oder -dokumenten entspricht/entsprechen, unter der Voraussetzung,
da sie gem unseren Anweisungen eingesetzt werden:
03 sont conformes la/aux norme(s) ou autre(s) document(s) normatif(s), pour autant qu'ils soient utiliss conformment nos instructions:
04 conform de volgende norm(en) of n of meer andere bindende documenten zijn, op voorwaarde dat ze worden gebruikt overeenkomstig
onze instructies:
05 estn en conformidad con la(s) siguiente(s) norma(s) u otro(s) documento(s) normativo(s), siempre que sean utilizados de acuerdo con
nuestras instrucciones:
06 sono conformi al(i) seguente(i) standard(s) o altro(i) documento(i) a carattere normativo, a patto che vengano usati in conformit alle
nostre istruzioni:
07 () () () () ,
:
CE - IZJAVA O SKLADNOSTI
CE - VASTAVUSDEKLARATSIOON
CE - --
17 m deklaruje na wasn i wyczn odpowiedzialno, e modele klimatyzatorw, ktrych dotyczy niniejsza deklaracja:
18 r declar pe proprie rspundere c aparatele de aer condiionat la care se refer aceast declaraie:
19 o z vso odgovornostjo izjavlja, da so modeli klimatskih naprav, na katere se izjava nanaa:
20 x kinnitab oma tielikul vastutusel, et kesoleva deklaratsiooni alla kuuluvad kliimaseadmete mudelid:
21 b , , :
22 t visika savo atsakomybe skelbia, kad oro kondicionavimo prietais modeliai, kuriems yra taikoma i deklaracija:
23 v ar pilnu atbildbu apliecina, ka tlk uzskaitto modeu gaisa kondiciontji, uz kuriem attiecas deklarcija:
24 k vyhlasuje na vlastn zodpovednos, e tieto klimatizan modely, na ktor sa vzahuje toto vyhlsenie:
25 w tamamen kendi sorumluluunda olmak zere bu bildirinin ilgili olduu klima modellerinin aadaki gibi olduunu beyan eder:
CE - IZJAVA-O-USKLAENOSTI
CE - MEGFELELSGI-NYILATKOZAT
CE - DEKLARACJA-ZGODNOCI
CE - DECLARAIE-DE-CONFORMITATE
09 u , , , :
10 q erklrer under eneansvar, at klimaanlgmodellerne, som denne deklaration vedrrer:
11 s deklarerar i egenskap av huvudansvarig, att luftkonditioneringsmodellerna som berrs av denna deklaration innebr att:
12 n erklrer et fullstendig ansvar for at de luftkondisjoneringsmodeller som berres av denne deklarasjon, innebrer at:
13 j ilmoittaa yksinomaan omalla vastuullaan, ett tmn ilmoituksen tarkoittamat ilmastointilaitteiden mallit:
14 c prohlauje ve sv pln odpovdnosti, e modely klimatizace, k nim se toto prohlen vztahuje:
15 y izjavljuje pod iskljuivo vlastitom odgovornou da su modeli klima ureaja na koje se ova izjava odnosi:
16 h teljes felelssge tudatban kijelenti, hogy a klmaberendezs modellek, melyekre e nyilatkozat vonatkozik:
CE - DECLARAO-DE-CONFORMIDADE
CE - --
CE - OVERENSSTEMMELSESERKLRING
CE - FRSKRAN-OM-VERENSTMMELSE
01 a declares under its sole responsibility that the air conditioning models to which this declaration relates:
02 d erklrt auf seine alleinige Verantwortung da die Modelle der Klimagerte fr die diese Erklrung bestimmt ist:
03 f dclare sous sa seule responsabilit que les appareils d'air conditionn viss par la prsente dclaration:
04 l verklaart hierbij op eigen exclusieve verantwoordelijkheid dat de airconditioning units waarop deze verklaring betrekking heeft:
05 e declara baja su nica responsabilidad que los modelos de aire acondicionado a los cuales hace referencia la declaracin:
06 i dichiara sotto sua responsabilit che i condizionatori modello a cui riferita questa dichiarazione:
07 g :
08 p declara sob sua exclusiva responsabilidade que os modelos de ar condicionado a que esta declarao se refere:
CE - DECLARATION-OF-CONFORMITY
CE - KONFORMITTSERKLRUNG
CE - DECLARATION-DE-CONFORMITE
CE - CONFORMITEITSVERKLARING
3P323721-8J
Installation manual
CONTENTS
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
SAFETY PRECAUTIONS................................................ 1
BEFORE INSTALLATION................................................ 2
SELECTING INSTALLATION SITE ................................. 3
PREPARATIONS BEFORE INSTALLATION ................... 3
INDOOR UNIT INSTALLATION....................................... 4
OUTDOOR UNIT INSTALLATION................................... 5
REFRIGERANT PIPING WORK ..................................... 5
DRAIN PIPING WORK .................................................... 7
INSTALLING THE DUCT................................................. 8
ELECTRIC WIRING WORK ............................................ 8
WIRING EXAMPLE ......................................................... 9
FIELD SETTING AND TEST RUN .................................11
WIRING DIAGRAM ....................................................... 13
The original instructions are written in English. All other languages are translations of the original instructions.
1.
SAFETY PRECAUTIONS
WARNING
Ask your dealer or qualified personnel to carry out installation
work.
Do not attempt to install the air conditioner yourself. Improper
installation may result in water leakage, electric shocks or
fire.
Install the air conditioner in accordance with the instructions
in this installation manual.
Improper installation may result in water leakage, electric
shocks or fire.
Consult your local dealer regarding what to do in case of
refrigerant leakage. When the air conditioner is to be
installed in a small room, it is necessary to take proper measures so that the amount of any leaked refrigerant does not
exceed the concentration limit in the event of a leakage.
Otherwise, this may lead to an accident due to oxygen depletion.
Be sure to use only the specified accessories and spare
parts for installation work.
Failure to use the specified parts may result in the unit falling,
water leakage, electric shocks or fire.
Install the air conditioner on a foundation strong enough to
withstand the weight of the unit.
English
A foundation of insufficient strength may result in the equipment falling and causing injury.
Carry out the specified installation work after taking into
account strong winds, typhoons or earthquakes.
Failure to do so during installation work may result in the unit
falling and causing accidents.
Make sure that a separate power supply circuit is provided
for this unit and that all electrical work is carried out by qualified personnel according to local laws and regulations and
this installation manual.
An insufficient power supply capacity or improper electrical
construction may lead to electric shocks or fire.
Make sure that all wiring is secured, the specified wires are used,
and that there is no strain on the terminal connections or wires.
Improper connections or securing of wires may result in
abnormal heat build-up or fire.
When wiring the power supply and connecting the remote
controller wiring and transmission wiring, position the wires
so that the control box lid can be securely fastened.
Improper positioning of the control box lid may result in electric shocks, fire or the terminals overheating.
If refrigerant gas leaks during installation, ventilate the area
immediately.
Toxic gas may be produced if the refrigerant comes into contact with fire.
After completing installation, check for refrigerant gas leakage.
Toxic gas may be produced if the refrigerant gas leaks into
the room and comes into contact with a source of fire, such
as a fan heater, stove or cooker.
Be sure to switch off the unit before touching any electrical
parts.
Do not touch the switch with wet fingers.
Touching the switch with wet fingers can cause electric shock.
Be sure to earth the air conditioner.
Do not earth the unit to a utility pipe, lightning conductor or
telephone earth lead.
Imperfect earthing may result in electric shocks or fire.
A high surge current from lightning or other sources may
cause damage to the air conditioner.
Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in electric shocks or fire.
CAUTION
While following the instructions in this installation manual,
install drain piping to ensure proper drainage and insulate
piping to prevent condensation.
Improper drain piping may result in indoor water leakage and
property damage.
Install the indoor and outdoor units, power cord and connecting wires at least 1 meter away from televisions or radios to
prevent picture interference and noise.
(Depending on the incoming signal strength, a distance of
1 meter may not be sufficient to eliminate noise.)
Remote controller (wireless kit) transmitting distance can be
shorter than expected in rooms with electronic fluorescent
lamps (inverter or rapid start types).
Install the indoor unit as far away from fluorescent lamps as
possible.
Sound pressure level is less than 70 dB (A).
Only handle the indoor unit with gloves.
2-2 ACCESSORIES
Check the following accessories are included with your unit.
Name
Metal
clamp (1)
Drain
hose (2)
Insulation
for fitting
Sealing pad
Quantity
1 pc.
1 pc.
1 each
1 each
Large (5)
mid. (6)
Shape
Name
Screws for
duct flanges
(7)
Quantity
1 set
Washer for
hanging
bracket (8)
8 pcs.
BEFORE INSTALLATION
Washer
fixing plate
(11)
1 set
4 pcs.
Large (9)
8 pcs.
Shape
26 pcs.
small (10)
4 pcs.
Name
Sealing
material
(12)
Leveling
screws (14)
Quantity
2 pcs.
1 pc.
1 set
Shape
4x M6
2.
Clamp
BRC1D52/BRC1D61/BRC1E51/
BRC2C51/BRC1E52/BRC3A61
BRC4C62
Items to be checked
2-1 PRECAUTIONS
(Other)
Operation manual
Installation
manual
(this
manual)
Check
English
Check
3.
To avoid contact with the fan, the following precaution action must be
taken:
- Install the unit with ducting and grill which can only be
removed with the aid of tooling. It shall be installed so that
it gives adequate protection against touching the fan. If a
maintenance panel exists in the ducting, it shall only be
possible to remove the panel by the aid of tooling to avoid
contact with the fan. The protection shall be according to
relevant European and local legislation. There are no
restrictions concerning the installation height.
4.
(1) Make sure the range of the units external static pressure is not exceeded.
(See the technical documentation for the range of the
external static pressure setting.)
(2) In case of front suction:
(1) Remove the protection net.
(2) Remove the chamber lid. (7 locations)
(3) Remove one leg on the opposite side of the el. compo
(for instruction, see page 4, Removing the legs).
(4) Reattach the removed chamber lid in the orientation
shown in picture 2 below. (7 locations)
(5) Attach the protection net to the front side.
(6) Reattach the leg if necessary.
(7) Attach the air filter (accessory) in the manner shown in
the diagram.
(1)
CAUTION
When moving the unit during or after unpacking, make sure
to lift it by holding its lifting lugs. Do not exert any pressure on
other parts, especially the refrigerant piping, drain piping and
flange parts.
If you think the humidity inside the wall might exceed 30C
and RH80%, reinforce the insulation on the unit body.
Use glass wool or polyethylene foam as insulation so that
it is no thicker than 10mm and fits inside the wall opening.
(1) Select an installation site where the following conditions
are fulfilled and that meets with your customers approval.
Where optimum air distribution can be ensured.
Where nothing blocks air passage.
Where condensate can be properly drained.
Where the wall/floor is strong enough to bear the indoor
unit weight.
Where the floor is not noticeably on an incline.
Where there is no risk of flammable gas leakage.
Where sufficient clearance for maintenance and service
can be ensured.
Where piping between indoor and outdoor units is possible within the allowable limit. (Refer to the installation
manual for the outdoor unit.)
The equipment is not intended for use in a potentially
explosive atmosphere.
[ PRECAUTION ]
Install the indoor and outdoor units, power supply wiring
and connecting wires at least 1 m away from televisions or
radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 m may not
be sufficient enough to eliminate the noise.)
If installing the wireless kit in a room with electronic fluorescent lighting (inverter or rapid start type), the remote
controllers transmission distance may be shortened.
Indoor units should be installed as far away from fluorescent lighting as possible.
English
(2)
Air discharge
Air discharge
Air inlet
Chamber lid
Protection net
Protection net
Chamber lid
Air inlet
Filter
Attach the
filter to the
main unit
Force
while pushing
down on the
bends.
Force
Insert below
washer
Hanger
bracket
Part to be procured
in the field
Tig
(do hten
ub
le
nu
t)
Washer
fixing plate
(accessory)
[ PRECAUTION ]
Since the unit uses a plastic drain pan, prevent welding
spatter and other foreign substances from the air outlet
during installation.
(2) Adjust the unit to fit between the walls.
(3) Check the unit is horizontally level.
Protection
net
Leg
CAUTION
Make sure the unit is installed level using a level or a
plastic tube filled with water. In using a plastic tube
instead of a level, adjust the top surface of the unit to the
surface of the water at both ends of the plastic tube and
adjust the unit horizontally. (One thing to watch out for in
particular is if the unit is installed so that the slope is not
in the direction of the drain piping, this might cause leaking.)
(1)
(2)
1750
Leg
5.
F
100E
CAUTION
Make sure no short circuit of air is caused when placing the
unit directly under a windowsill.
English
Air outlet
20
618
500
Suspension
bolt pitch
B
A
Unit
300
Model
20+25+32 type
40+50 type
63 type
300
1000
A
(Suspension bolt pitch)
A
B
C
D
(
A
740
940
1140
10
0
(
Model
20/25/35 40/50 63
Width of air inlet grille
660
860 1060
1550 1750
Width of maintenance area 1350
Air inlet direction
Air outlet direction
Height of the intake area
00
760
D
D
B
2) If the unit is in danger of falling over, either fasten to
the wall using the holes provided, or fasten to the
floor with a field supplied floor fastener.
6.
A
C
20
7.
Unit
300
10
1000
300
A
B
C
D
F
English
Model
20/25/35 40/50 63
660
860 1060
1350
1550 1750
CAUTION
Follow the points at below.
Use a pipe cutter and flare suitable for the type of refrigerant.
Apply ester oil or ether oil to the flare section when using a
flare connection.
Only use the flare nuts included with the unit. Using different
flare nuts may cause the refrigerant to leak.
To prevent dust, moisture or other foreign matter from infiltrating the piping, either pinch the end or cover it with tape.
Do not allow anything other than the designated refrigerant
to get mixed into the refrigerant circuit, such as air, etc. If any
refrigerant gas leaks while working on the unit, ventilate the
room thoroughly right away.
For the gas piping, wrap the mid. sealing pad (6) over the
insulation for fitting (4) (flare nut part).
Liquid Piping Insulation Procedure
Insulation for fitting (3)
(accessory)
Attach to base
Turn seams up
Main unit
Clamp (9) (accessory)
Liquid pipe
Gas pipe
Gas Piping Insulation Procedure
Insulation for fitting (4)
Piping insulation
material (main unit) (accessory)
Mid. sealing pad (6)
Flare nut connection
(accessory)
Attach to base
Turn seams up
Main unit
Flare nut
Clamp (9)
(accessory)
Piping union
33 39 Nm
12.8 13.2
12.7
50 60 Nm
16.2 16.6
15.9
63 75 Nm
19.3 19.7
CAUTION
Be sure to insulate any field piping all the way to the piping
connection inside the unit. Any exposed piping may cause
condensation or burns if touched.
When brazing the refrigerant piping, perform nitrogen
replacement first, or perform the brazing (CAUTION 2) while
feeding nitrogen into the refrigerant piping (CAUTION 1), and
finally connect the indoor unit using the flare connections.
(Refer to the picture below)
9.5
45 2
8.7 9.1
R0.4-0.8
A
15 17 Nm
6.4
Flare shape
Tightening torque
90 2
Pipe
size
CAUTION
Overtightening may damage the flare and cause leaks.
Be careful for oil not to adhere to any portions other
than a flare part. If oil adheres to resin parts etc., there
is a possibility of damaging by deterioration.
Refer to Table 2 if no torque wrench is available.
Using a wrench to tighten flare nuts causes the tightening
torque to suddenly grow much tighter after a certain point.
From there, tighten the nut further by the appropriate angle
listed in Table 2.
CAUTION
1. When brazing a pipe while feeding nitrogen inside the
pipe, make sure to set the nitrogen pressure to 0.02 MPa
2
(0.2 kg/cm ) using the pressure reducing valve. (This
pressure is such that breeze is blown to your cheek.)
2. Do not use a flux when brazing the refrigerant pipe joints.
Use phosphor copper brazer (BCuP-2: JIS Z 3264/BCu93P-710/795: ISO 3677) which does not require flux.
(Using a flux containing chlorine may cause the piping to
corrode. Using a welding flux containing fluorine may
cause the refrigerant lubricant to deteriorate, and affect
adversely the refrigerant piping system.)
Pressure-reducing valve
Part to be brazed
Nitrogen
Refrigerant piping
Taping
Hands
valve
Nitrogen
English
When you keep on tightening the flare nut with a spanner, there
is a point where the tightening torque suddenly increases. From
that position, further tighten the flare nut by the angle shown
below:
Table 2
Further tightening angle
Recommended arm
length of tool
6.4 (1/4)
60 to 90 degrees
Approx. 150mm
9.5 (3/8)
60 to 90 degrees
Approx. 200mm
12.7 (1/2)
30 to 60 degrees
Approx. 250mm
15.9 (5/8)
30 to 60 degrees
Approx. 300mm
Pipe size
end. Tighten the metal clamp (1) until the screw head is less
than 4 mm from the hose. (Refer to the following pictures)
The two areas below should be insulated because condensation may form there causing water to leak.
Drain piping passing indoors
Drain socket
Referring the figure below, insulate the metal clamp (1) and
drain hose (2) using the included large sealing pad (5).
(Refer to the right picture below)
8.
CAUTION
Make sure all water is out before making the duct connection.
Tape
Large sealing
pad (5)
(accessory)
Metal clamp (1)
(accessory)
4mm
PRECAUTIONS
Air outlet
CAUTION
Water accumulating in the drain piping can cause the
drain to clog.
To keep the drain piping from sagging, space hanging
bracket every 1 to 1.5 m.
Use the drain hose (2) and the metal clamp (1). Insert the
drain hose (2) fully into the drain socket and firmly tighten the
metal clamp (1) with the upper part of the tape on the hose
English
Portable pump
Refrigerant
pipes
Bucket
Drain pan
Drain outlet
9.
Aluminum tape
(Field supply)
Flange
Outlet side
Model
Main unit
Number
of units
Field
fuses
Wire
20 25 32 type
40 50 type
Size
Size must
H05VV-U3G
comply with
(NOTE 1)
local codes.
16 A
63 type
Transmission wiring
Remote controller wiring
Model
Wire
20 25 32 type
Size (mm2)
40 50 type
63 type
0.75 - 1.25
NOTES
1. Shows only in case of protected pipes. Use H07RN-F in
case of no protection.
2. Insulated thickness : 1mm or more.
3. If the wiring is in a place where there are people it can be
easily touched by people, install an earth leakage breaker to
prevent electric shock.
4. When using an earth leakage breaker, make sure to select
one useful also for protection against overcurrent and shortcircuit.
When using an earth leakage breaker only for earth device,
make sure to use a wiring interrupter together.
The length of the transmission wiring and remote controller
wiring are as follows.
Length of the transmission wiring and remote controller wiring
Max. 1000m
(Total wiring length: 2000m)
Max. 500m
Power supply
Hz Volts
Voltage
range
220240
Min.
198
Max.
264
20 25 32
40
50
50
63
20 25 32
40
50
63
60
220
Min.
198
Max.
242
MCA
MFA
Fan motor
KW
FLA
0.068
0.3
0.075
0.4
0.096
0.4
0.6
0.107
0.5
0.5
0.068
0.4
0.075
0.5
0.096
0.5
0.107
0.6
0.4
0.5
0.5
0.6
0.6
0.7
16
16
English
CAUTION
Be sure to attach power supply wiring and earth wire to the
control box with the clamp.
When doing the wiring, make sure the wiring is neat and
does not cause the control box lid to stick up, then close the
cover firmly. When attaching the control box lid, make sure
you do not pinch any wires.
Outside the air conditioners, separate the weak wiring (remote
controller and transmission wiring) and strong wiring (earth
wire and power supply wiring) at least 50 mm so that they do
not pass through the same place together. Proximity may
cause electrical interference, malfunctions, and breakage.
A main switch or other means for disconnection, having a
contact separation in all poles, must be incorporated in the
fixed wiring in accordance with relevant local and national
legislation.
Note that the operation will restart automatically if the main
power supply is turned off and then turned back on again.
[ PRECAUTIONS ]
Refer to the REMOTE CONTROLLER INSTALLATION
MANUAL on how to install and lay the wiring for the remote
controller.
See also the Wiring Diagram plate attached to the control
box lid when laying electrical wiring.
Connect the remote controller and transmission wiring their
respective terminal blocks.
CAUTION
Do not, under any circumstances, connect the power supply wiring to the remote controller or transmission wiring
terminal block. Doing so can destroy the entire system.
Wiring through
hole
REMOTE
CONTRL
TRANSMISSION
WIRING
Inside
unit
FORCED
OFF
Outside
unit
P1 P2 F1 F2 T1 T2
Wire
Control box
Control box
Indoor PCboard
(ASSY)
*Transmission wiring
*Remote controller wiring
* Do not connect power
supply wiring here.
That may cause malfunction
Clamps
(for preventing
slippage)
Power supply
wiring
Earth wire
English
Indoor PCboard
(ASSY)
Wiring through
hole
L N
IN/D OUT/D
F1 F2 F1 F2
Insulation sleeve
L N
P1 P2 F1 F2 T1 T2
P1 P2 F1 F2 T1 T2
L N
L N
P1 P2 F1 F2 T1 T2
Electric wire
Do not connect
wires of the same
gauge to one side.
Connect wires of
the same gauge to
both sides.
Do not connect
wires of different
gauges.
Indoor unit B
Indoor
unit A
P1 P2
Remote controller
(option)
0.79 0.97
1.18 1.44
Outdoor unit
L N
IN/D OUT/D
F1 F2 F1 F2
LN
OUT/D IN/D
F1 F2 F1 F2
P1 P2 F1 F2 T1 T2
Indoor unit A
Remote controller
(option)
Power supply
single phase
50Hz
220-240V or
single phase
60Hz 220V
L N
IN/D
BS unit
P1 P2
Power supply
single phase
50Hz
220-240V or
single phase
60Hz 220V
Outdoor unit
P1 P2
Remote
(option)
For use with 2
remote controllers
L N
P1 P2
Remote
[ WIRING EXAMPLE ]
Power supply
single phase
50Hz
220-240V or
single phase
60Hz 220V
Most
downstream
indoor unit
L N
OUT/D
F1 F2 F1 F2
MAIN/SUB CHANGEOVER
(1) Insert a
screwdriver into the recess between the
upper and lower part of remote controller and, working
from the 2 positions, pry off the upper part (2 locations).
L N
P1 P2 F1 F2 T1 T2
Indoor unit A
P1 P2 F1 F2 T1 T2
Remote controller
(option)
L N
P1 P2 F1 F2 T1 T2
Most
downstream
indoor unit
Indoor unit B
P1 P2
10
L N
P1 P2
Remote controller
(option)
P1 P2
Remote controller
(option)
English
Upper part of
remote controller
P1 P2 F1 F2 T1 T2
REMOTE
CONTRL
TRANSMISSION
WIRING
FORCED
OFF
Input A
Lower part of
remote controller
Insert the screwdriver here and gently work off the
upper part of remote controller.
(Factory setting)
S
M
Remote controller
PC board
Only one remote controller
needs to be changed if
factory settings have
remained untouched.
S
M
TRANSMISSION
WIRING
FORCED
OFF
Remote
controller 2
(SUB)
Remote
controller 1
(MAIN)
[ PRECAUTIONS ]
Crossover wiring is needed when using group control and
2 remote controllers at the same time.
Connect the indoor unit at the end of the crossover wire
(P1, P2) to remote controller 2 (SUB).
Indoor unit 1
Indoor unit 2
Max. No. of
indoor units
Wire specification
Gauge
0.75 - 1.25 mm
Length
Max. 100 m
External terminal
Contact that can ensure the minimum applicable load of 15 V DC, 1 mA.
Mode No.
SETTING
FIELD SET
MODE
Mode No.
FIRST
CODE NO.
13(23)
Standard
Crossover wire (P1.P2)
Remote controller 1
(MAIN)
Remote controller 2
(SUB)
English
SECOND
CODE NO.
01
02
Mode No.
FIRST
CODE NO.
SECOND
CODE NO.
11
Forced off
12(22)
01
02
ON/OFF operation
Input A of forced off and ON/OFF operation work as shown in
the table below.
Forced off
ON/OFF operation
10 (20)
SECOND
CODE NO.
Content
01
02
display
display
Filter dirt
low
high
1 (low/high)
Displayed time
(units: hours)
2500/
1250
10000/
5000
Filter sign
display
ON
OFF
display
display
display
No display
CAUTION
Always stop the test run using the remote controller to stop
operation.
12
English
L
N
BLK
BLU
BRN
GRY
ORG
PNK
: BLACK
: BLUE
: BROWN
: GREY
: ORANGE
: PINK
PRP
RED
WHT
YLW
GRN
: PURPLE
: RED
: WHITE
: YELLOW
: GREEN
INDOOR UNIT
RECEIVER/DISPLAY UNIT
C105.......................CAPACITOR
F2U.........................FIELD FUSE
R1T.........................THERMISTOR (AIR)
R2T, R3T ................THERMISTOR (COIL)
(OPTIONAL ACCESSORY)
(Optional accessory)
TRANSMISSION WIRING
Transmission wiring
NOTE
English
1.
2.
WHEN USING THE CENTRAL REMOTE CONTROLLER, SEE MANUAL FOR CONNECTION TO THE UNIT.
3.
WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FORCED "OFF" OR "ON/OFF" CONTROL OPERATION CAN
BE SELECTED BY THE REMOTE CONTROLLER. SEE INSTALLATION MANUAL FOR MORE DETAILS.
4.
REMOTE CONTROLLER MODEL VARIES ACCORDING TO THE COMBINATION SYSTEM, CONFIRM ENGINEERING
DATA AND CATALOGS, ETC. BEFORE CONNECTING.
13