Time Current Curves TD012019EN

Effective March 2014

Series G L-Frame
100630A, 220690V
Contents
Description

Page

Catalog Number Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


Digitrip 310+ Electronic Trip Unit Types LGE, LGS, LGH, LGC, LGU, LGX
Long Delay Response and Short Delay with Flat Response Curve
(LSI, LSIG, ALSI, ALSIG) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC01207004E . . . . . .
Long Delay Response and Short Delay with I2t Response Curve (LS, LSG) . . . . . . . TC01207005E . . . . . .
Ground Fault Delay Response Curve (LSG, LSIG, ALSIG). . . . . . . . . . . . . . . . . . . . . . TC01207006E . . . . . .
Maintenance Mode / Instantaneous Setting (ALSI, ALSIG) . . . . . . . . . . . . . . . . . . . . TC01207014E. . . . . . .

5
6
7
8

Thermal/Magnetic Trip Unit


LGE, LGS, LGH, LGC, LGU, and LGX Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . TC01208002E . . . . . . 9
LHH High Instantaneous Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC01206004E . . . . . 10
Peak Let-Through (IP) and Clearing (I2T) Curves
LG, JG, EG, and EG CL (with Current Limiter), Molded-Case
Circuit Breakers240V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC01200001E-A. . . .
LG, JG CL, JG, EG, and EG CL (with Current Limiter), Molded-Case
Circuit Breakers480V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC01200001E-B. . . .
LG, JG CL, JG, EG, and EG CL (with Current Limiter), Molded-Case
Circuit Breakers600V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC01200001E-C. . . .
LGU and JGU Molded-Case Circuit Breakers240V . . . . . . . . . . . . . . . . . . . . . . . . . TC01200001E-D. . . .
LGU and JGU Molded-Case Circuit Breakers480V . . . . . . . . . . . . . . . . . . . . . . . . . TC01200001E-E. . . .
LGU and JGU Molded-Case Circuit Breakers600V . . . . . . . . . . . . . . . . . . . . . . . . . TC01200001E-F. . . .
LGX and JGX Molded-Case Circuit Breakers240V . . . . . . . . . . . . . . . . . . . . . . . . . TC01200001E-G. . . .
LGX and JGX Molded-Case Circuit Breakers480V . . . . . . . . . . . . . . . . . . . . . . . . . TC01200001E-H. . . .
LGX, JG CL, and JGX Molded-Case Circuit Breakers600V . . . . . . . . . . . . . . . . . . TC01200001E-I . . . .
Peak Let-Through Currents (Ip) and Clearing (I2t) Summary Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

11
12
13
14
15
16
17
18
19
20

Earth Leakage Module Curves


UL LG Circuit Breaker Earth Leakage Module, Three- and Four-Pole, 110480V . . . . TC01212009E . . . . . 21
IEC LG Circuit Breaker Earth Leakage Module, Three- and Four-Pole, 110480V . . . TC01212008E . . . . . 22
NNote:
The following curves meet the requirements of UL,T CSA,T IEC, CCC, and CE.
The following circuit breakers are derived from Eaton, Westinghouse,T or Cutler-HammerT brand.

Time Current Curves TD012019EN

Series G
L-Frame

Effective March 2014

NNote: Unless noted below, all curves remain unchanged from their prior revision.

Revision

Curve Number

eaton www.eaton.com

Page

Date

Time Current Curves TD012019EN

Series G
L-Frame

Effective March 2014

Catalog Number Selection


This information is presented only as an aid to understanding catalog numbers.
It is not to be used to build catalog numbers for circuit breakers or trip units.
Table 1. Series GLG-Frame (250630A)

L G S 3 600 FA G C
Frame

Rating

G = IEC/CE/UL/CSA
Performance

600

480

415

240

18

35

35

65

25

50

50

85

H 35

65

70

100

100

100

200

50

Trip Unit

Number of Poles

Standard/Application

U 65

150

150

200

65

200

200

200

Molded-case switch

Blank = 80% rated


C
= 100% rated

3 = Three
4 = FourNeutral 0% protected
6 = FourNeutral 60% protected
7 = FourNeutral 100% protected
8 = FourNeutral 060% protected
9 = FourNeutral 0100 protected

AA = Adj. adj.
FA = Fixed adj.
KS = Molded-case switch
33 = 310+ electronic LS
32 = 310+ electronic LSI
35 = 310+ electronic LSG
36 = 310+ electronic LSIG
38 = 310+ electronic ALSI
39 = 310+ electronic ALSIG
NN = Frame only (no trip)

Amperes

250
300
350
400
500
600
630

Terminations/Hardware
Terminals

M = Metric end caps


E = Imperial end caps
G = Line/load standard
W = Without terminals

Mounting Hardware

Metric
Imperial
Metric

Table 2. Trip Unit

LT 3 600 FA
Frame

Trip Unit
Number of Poles

LT

Amperes

3 = Three
4 = Fourneutral 0% protected
8 = Fourneutral 060% protected
9 = Fourneutral 0100 protected

AA = Adj. adj., thermal-magnetic


FA = Fixed adj., thermal-magnetic
KS = Molded case switch
33 = 310+ electronic LS
32 = 310+ electronic LSI
35 = 310+ electronic LSG
36 = 310+ electronic LSIG
38 = 310+ electronic ALSI
39 = 310+ electronic ALSIG

250
300
350
400
500
600
630

Table 3. Earth Leakage Modules

ELLB N 3 400 W
Frame

ELLB

Rating

N = UL rated
E = IEC rated

Amperes
Number of Poles

3 = Three
4 = Four

400
600
630

Trip Unit

W = Without terminals

eaton www.eaton.com

Time Current Curves TD012019EN

Series G
L-Frame

Effective March 2014

LSIG

ALSIG (With Maintenance Mode)

68C 4580 H17

Push to Trip
Remote MM

I i (xIn)
INST
7 8 10
6
12
4
2.5
Maintenance Mode

TEST /
ALARM

C
B

IR
D E F
A

G
H

STATUS

t R (s)

I sd (xIR)

Settings

50
t sd 120
(ms)
300

I g (xIn)

50
J
M
P

t g (ms)
120
K
N
Q

Push to Trip

TEST /
ALARM

IR

SHORT
LONG
GND
SHORT / GND
10 12 15
5 6 7
.6 .8 1.0 M N O
7
20 4
8 .4
L
P
4
24 3
10 .3
K
Q
R
2
2
.2
J
12

C
B

D E F
A

G
H

STATUS

I sd (xIR )

t R (s)

LONG
SHORT
10 12 15
5 6 7
7
20 4
8
4
24 3
10
12 I i
2
2

t g (ms)
Inst. 120
K
N
Q

Settings

t sd

t sd / t g (ms)

ALSI (With Maintenance Mode)

68C 4580 H01

300
L
O
R

(ms)

I g (xI n)

GND
.6 .8 1.0
.4
.3
.2

Inst. J
120 M
300 P

t sd / t g (ms)
SHORT / GND
M N O
L
K

P
Q

LSI

68C 4580 H18

68C 4580 H03

Push to Trip

Push to Trip

Remote MM

I i (xIn)
INST
7 8 10
6
12
4
2.5
Maintenance Mode

TEST /
ALARM

C
B

IR
D E F
A

G
H

TEST /
ALARM

STATUS

t R (s)

I sd (xIR)

t sd (ms)

LONG
SHORT
10 12 15
5 6 7
7
20 4
8
4
24 3
10
2
2
12

IR

SHORT
120

50

C
B

300

LSG

D E F
A

G
H

LS
68C 4580 H04

68C 4580 H02

Push to Trip

Push to Trip

TEST /
ALARM

C
B

IR
D E F
A

G
H

TEST /
ALARM

STATUS

t R (s)

I sd (xIR )

I g (xI n)

t g (ms)

SHORT
GND
LONG
GND
120
10 12 15
5 6 7
.6 .8 1.0
7
20 4
8 .4
4
24 3
10 .3
Inst.
300
2
2
12 I i .2

Figure 1. Digitrip 310+ Faceplates

STATUS

t R (s)
I sd (xIR)
SHORT
LONG
10 12 15
5 6 7
7
20 4
8
4
24 3
10
2
2
12 I i

eaton www.eaton.com

IR

C
B

D E F
A

G
H

STATUS

t R (s)
I sd (xIR)
LONG
SHORT
10 12 15
5 6 7
7
20 4
8
4
24 3
10
2
2
12 I i

t sd (ms)
SHORT
120

Inst.

300

300
L
O
R

Time Current Curves TD012019EN

1 Hour

2 Hours

Series G
L-Frame

Effective March 2014

10,000
9000
8000
7000
6000
5000
4000

0.5 0.7

Current in Multiples of (Ir)


3 4 5
7
10 12
20

30
DigitripE 310+ Circuit Breaker Time/Current Curves (Phase Current)
Series G L-Frame Circuit Breakers
Catalog Types: LGE, LGS, LGH, LGC, LGU, LGX, GLE, GLS, GLH, GLC, GLU, and GLX
circuit breakers, three- and four-pole.

1.15

Trip Unit Types: 32 (LSI), 36 (LSIG), 38 (ALSI), and 39 (ALSIG).


Available Sensors (In): 250A, 400A, 600A, and 630A.

3000

Long Delay and Short Delay with Flat Response

2000

1000
900
800
700
600
500
400

A
B
C
D
E
F
G
H

Maximum Total
Clearing Time

300

1 Minute

Available
Long Delay Time
(Seconds +0/30%):
2*, 4*, 7*, 10, 12, 15*, 20, 24*
*Shown below at 6x

100
90
80
70
60
50
40
30

.
24

Time in Seconds

20

.
15

MinimumTotal
ClearingTime

400

600

630

100
125
150
160
175
200
225
250

160
200
225
250
300
315
350
400

250
300
315
350
400
450
500
600

250
300
315
350
400
500
600
630

1. Curve accuracy applies from 20C to +55C ambient. For possible continuous Ampere
derating for ambient above +40C, refer to Eaton. Temperatures above +85C cause an
overtemperature protection trip.
2. Application frequency is 50/60 Hz.
3. There is a memory effect that can act to shorten the Long Delay. If the breaker trips on a
Long Delay overload and is quickly reset, the memory capacitor will still have charge and a
subsequent overload will cause the breaker to trip in a shorter time than normal. The amount
of time delay reduction is inverse to the amount of time that has elapsed since the previous
overload. Approximately five minutes is required between overloads to completely
reset memory.
4. The right portion of the curve is determined by the interrupting rating of the circuit breaker.
5. The left portion of the curve is shown as a multiple of the Long Delay Setting
(Long Delay Pickup = 115% of Ir). Range is 110120%.
6. Total clearing times shown include the response times of the trip unit, the breaker opening,
and the interruption of the current.
7. The Short Delay Pickup has nine settings/positions: 28, 10, and 12.
For high fault current levels, an additional fixed Instantaneous Override is provided.
Instantaneous Override tolerance is +/ 20%. The Instantaneous Override pickup value (Ii)
is a multiple of the breaker sensor rating (In). The Instantaneous Override has precedence
over a SDPU. When Rated Amps (Ir) is set to the maximum (position H), then both the
SDPU and the Instantaneous Override pickup are equivalent. Therefore, the breaker will
trip on Instantaneous Override.
In = 250A Instantaneous Override (Ii) = 28X(In)
In = 400A, 600A, 630A Instantaneous Override (Ii) = 12X(In)

.
4

LSI

LSIG
68C 4580 H03

.
Available Short
Delay Pickup
Settings 28,
10, 12 x Ir 5%
(See Note 7)

C
B

4
3

G
H

t R (s)
I sd (xIR)
SHORT
LONG
10 12 15
5 6 7
7
20 4
8
4
24 3
10
2
2
12 I i

t sd (ms)
SHORT
120

Inst.

C
B

300

IR
D E F
A

G
H

C
B

IR
D E F
A

G
H

STATUS

t R (s)

I sd (xIR)

LONG
SHORT
10 12 15
5 6 7
7
20 4
8
4
24 3
10
2
2
12

t sd (ms)
SHORT
120

50

300

Push to Trip
Remote MM

TEST /
ALARM

t g (ms)
Settings
Inst. 120 300
K
J
L
t sd Inst.
N
O
120 M
(ms)
Q
R
300 P

t R (s)
I sd (xIR)
I g (xIn) t sd / t g (ms)
LONG
GND
SHORT / GND
SHORT
10 12 15
5 6 7
.6 .8 1.0 M N O
7
20 4
8 .4
L
P
4
24 3
10 .3
K
Q
R
2
2
J
12 I i .2

68C 4580 H17

Push to Trip

I i (xIn)
INST
7 8 10
6
12
4
2.5
Maintenance Mode

STATUS

ALSIG (With Maintenance Mode)

68C 4580 H18

Remote MM

IR
D E F

Push to Trip

TEST /
ALARM

STATUS

ALSI (With Maintenance Mode)

12
6

68C 4580 H01

Push to Trip

TEST /
ALARM

1
0.9
0.8
0.7
0.6
0.5
0.4

250

N Notes:

200

10
9
8
7
6
5
4

Rated Amperes

Available Sensors
(Ir) / (In)

I i (xIn)
INST
7 8 10
6
12
4
2.5
Maintenance Mode

TEST /
ALARM

C
B

IR
D E F
A

G
H

STATUS

t R (s)

I sd (xIR)

Settings

50
t sd 120
(ms)
300

I g (xIn)

300 ms
(P, Q, R)

0.5
0.4
0.3

Instantaneous
Override (See Note 8)

Application
Determines
End of Curve

120 ms
(M, N, O)

0.1
0.09
0.08
0.07
0.06
0.05
0.04

120 300
K
L
N
O
Q
R

Inst.
(J, K, L)

0.2

0.1
0.09
0.08
0.07
0.06
0.05
0.04

Time in Seconds

0.2

t g (ms)

LONG
SHORT
GND
SHORT / GND
10 12 15
5 6 7
.6 .8 1.0 M N O
7
20 4
8 .4
L
P
4
24 3
10 .3
K
Q
R
2
2
.2
J
12

10

0.3

50
J
M
P

t sd / t g (ms)

0.03

0.03
28X

0.02

0.02

12X
0.01

0.5 0.7

20
30 40 50 70 100
3 4 5
7
10 12
2
3 4 5
7
10
20
30 40 50
Current in Multiples of (Ir)
Current in Multiples of (In)
Adjustable Flat Trip Style (LSI, LSIG, ALSI, ALSIG)

0.01
70 100

Figure 2. Digitrip 310+ Long Delay Response and Short Delay with Flat Response Curve (LSI, LSIG, ALSI, ALSIG)
Curve Number TC01207004E, May 2008
eaton www.eaton.com

Time Current Curves TD012019EN

Series G
L-Frame

1 Hour

2 Hours

Effective March 2014

0.5 0.7
10,000
9000
8000
7000
6000
5000
4000

Current in Multiples of (Ir)


3 4 5
7 10 12

20

30
Digitrip 310+ Circuit Breaker Time/Current Curves (Phase Current)
Series G L-Frame Circuit Breakers
Catalog Types: LGE, LGS, LGH, LGC, LGU, LGX, GLE, GLS, GLH, GLC, GLU, and GLX
circuit breakers, three- and four-pole.

1.15

Trip Unit Types: 33 (LS) and 35 (LSG).


Available Sensors (In): 250A, 400A, 600A, and 630A.

3000

Long Delay and Short Delay with I2T Response

2000

1000
900
800
700
600
500
400

A
B
C
D
E
F
G
H

Maximum Total
Clearing Time

300

1 Minute

100
90
80
70
60
50
40

400

600

630

100
125
150
160
175
200
225
250

160
200
225
250
300
315
350
400

250
300
315
350
400
450
500
600

250
300
315
350
400
500
600
630

1. Curve accuracy applies from 20C to +55C ambient. For possible continuous Ampere
derating for ambient above +40C, refer to Eaton. Temperatures above +85C cause an
overtemperature protection trip.
2. Application frequency is 50/60 Hz.
3. There is a memory effect that can act to shorten the Long Delay. If the breaker trips on a
Long Delay overload and is quickly reset, the memory capacitor will still have charge and a
subsequent overload will cause the breaker to trip in a shorter time than normal. The amount
of time delay reduction is inverse to the amount of time that has elapsed since the previous
overload. Approximately five minutes is required between overloads to completely reset
memory.
4. The right portion of the curve is determined by the interrupting rating of the circuit breaker.
5. The left portion of the curve is shown as a multiple of the Long Delay Setting
(Long Delay Pickup = 115% of Ir). Range is 110120%.
6. Total clearing times shown include the response times of the trip unit, the breaker opening,
and the interruption of the current.
7. The Short Delay Pickup has nine settings/positions: 28, 10, and 12.
8. Short Delay I2t band has a tolerance of 15%.
9. Breakpoint back to FLAT response occurs at 8X Ir for upper line of the I2t curve.
10. For high fault current levels, an additional fixed Instantaneous Override is provided.
Instantaneous Override tolerance is +/ 20%. The Instantaneous Override pickup value (Ii)
is a multiple of the breaker sensor rating (In). The Instantaneous Override has precedence
over a SDPU. When Rated Amps (Ir) is set to the maximum (position H), then both the
SDPU and the Instantaneous Override pickup are equivalent. Therefore, the breaker will
trip on Instantaneous Override.
In = 250A Instantaneous Override. (Ii) = 28X(In)
In = 400A, 600A, 630A Instantaneous Override (Ii) = 12X(In)

Available Long Delay Time


(Seconds +0/30%):
2*, 4*, 7*, 10, 12, 15*, 20, 24*
*Shown below at 6x

.
.

30

24

20
Time in Seconds

250

N Notes:

200

10
9
8
7
6
5
4

Rated Amperes

Available Sensors
(Ir) / (In)

15

Minimum Total
Clearing Time

3
2
2

1
0.9
0.8
0.7
0.6
0.5
0.4

LS

68C 4580 H04

Push to Trip

TEST /
ALARM

4
C
B

IR
D E F
A

G
H

STATUS

t R (s)
I sd (xIR )
SHORT
LONG
10 12 15
5 6 7
7
20 4
8
4
24 3
10
2
2
12 I i

5
LSG

12

68C 4580 H02

Push to Trip

0.3

TEST /
ALARM

0.2

I 2t Short Delay
(See Note 8)

10

IR

C
B

D E F
A

G
H

0.3

STATUS

t R (s)
I g (xI n)
t g (ms)
I sd (xIR )
SHORT
GND
LONG
GND
120
10 12 15
5 6 7
.6 .8 1.0
7
20 4
8 .4
4
24 3
10 .3
Inst.
300
2
2
12 I i .2

Instantaneous
Override
(See Note 10)

67 ms

0.2

Application
Determines
End of Curve

0.03

0.03
See Note 9

28X

0.02

0.02

12X

0.01
0.5 0.7

7 10 12
20 30 40 50
Current in Multiples of (Ir)

70

100

I 2t Trip Style (LS and LSG)

7
10
20
30 40 50
Current in Multiples of (In)

Figure 3. Digitrip 310+ Long Delay Response and Short Delay with I2t Response Curve (LS, LSG)
Curve Number TC01207005E, May 2008
6

0.1
0.09
0.08
0.07
0.06
0.05
0.04

eaton www.eaton.com

70

0.01
100

Time in Seconds

0.1
0.09
0.08
0.07
0.06
0.05
0.04

Available Short Delay


Pickup Settings
28, 10 and 12 x Ir 5%
(See Notes 7 and 10)

Time Current Curves TD012019EN

Series G
L-Frame

Effective March 2014

10,000
9000
8000
7000
6000
5000
4000

0.1

0.2

0.3 0.4 0.5

0.7

2
Digitrip 310+ Circuit Breaker Time/Current Curves (Ground Current)
Series G L-Frame Circuit Breakers
Catalog Types: LGE, LGS, LGH, LGC, LGU, LGX, GLE, GLS, GLH, GLC, GLU, and GLX
circuit breakers, three- and four-pole.

3000

LSG
68C 4580 H02

2000

Push to Trip

TEST /
ALARM

IR

1000
900
800
700
600
500

C
B

400

~
E

G
H

STATUS

t R (s)
I g (xI n)
t g (ms)
I sd (xIR )
SHORT
GND
LONG
GND
120
10 12 15
5 6 7
.6 .8 1.0
7
20 4
8 .4
4
24 3
10 .3
Inst.
300
2
2
12 I i .2

LSIG

300

68C 4580 H01

Push to Trip

200
TEST /
ALARM

1 Minute

100
90
80
70
60
50

C
B

IR
D E F
A

G
H

(ms)

STATUS

I sd (xIR )
t R (s)
LONG
SHORT
10 12 15
5 6 7
7
20 4
8
4
24 3
10
12 I i
2
2

I g (xI n)
GND
.6 .8 1.0
.4
.3
.2

t g (ms)
Inst. 120
K
N
Q

Inst. J
120 M
300 P

300
L
O
R

t sd / t g (ms)
SHORT / GND
M N O
L
K

P
Q

ALSIG (With Maintenance Mode)

40

68C 4580 H17

30

Push to Trip

I i (xIn)
INST
7 8 10
6
12
4
2.5
Maintenance Mode

20

10
9
8
7
6
5

Ground Fault Pickup Settings


(Tolerance 10%)

Settings

50
120
(ms)
300

Remote MM

Time in Seconds

Settings

t sd

t sd

TEST /
ALARM

IR

C
B

D E F
A

G
H

STATUS

50
J
M
P

t g (ms)
120
K
N
Q

300
L
O
R

t R (s)
I sd (xIR)
I g (xIn) t sd / t g (ms)
SHORT
LONG
GND
SHORT / GND
10 12 15
5 6 7
.6 .8 1.0 M N O
7
20 4
8 .4
L
P
4
24 3
10 .3
K
Q
R
2
2
.2
J
12

N Note: Refer to table below for variations.

Available Sensors (In): 250A, 400A, 600A, and 630A.

SD/GF Delay Settings Table

2
0.2X

1
0.9
0.8
0.7
0.6
0.5
0.4

0.4X

0.6X

1X

0.3X

tsd

0.8X

(ms)
300 ms
(L, O, R)

0.3
0.2

120 ms
(K, N, Q)

0.1
0.09
0.08
0.07
0.06
0.05

Inst.
(J, M, P)

0.04

tg (ms)

Settings
Inst.
120
300

Inst. 120

300

J
M
P

L
O
R

K
N
Q

Ground Fault Delay Response Notes:


1. Curve accuracy applies from 20C to +55C ambient. For possible continuous Ampere
derating for ambient above +40C, refer to Eaton. Temperatures above +85C cause an
overtemperature protection trip.
2. Application frequency is 50/60 Hz.
3. Trip units are suitable for functional field testing with test kit style #70C1056G52.
4. For LD Response and SD with Flat Response curve, see TC01207004E.
5. For LD Response and SD with I2t Response curve, see TC01207005E.
6. For testing information, please contact Eaton.

0.03
0.02

0.01

0.1

0.2
0.3 0.4 0.5 0.7 1
Ground Current in Multiple of (In)

Figure 4. Ground Fault Delay Response Curve (LSG, LSIG, ALSIG)Curve Number TC01207006E, May 2008

eaton www.eaton.com

Time Current Curves TD012019EN

Series G
L-Frame

Effective March 2014

N Notes:
1. The Maintenance Mode feature must be ENABLED for these curves to apply, when in
Maintenance Mode.
2. The Maintenance Mode is Enabled locally by turning the Maintenance Mode/INST dial to the
2.5X or 4X position, or via remote signal. Enabling the Maintenance Mode via remote signal
sets the pickup to 2.5X regardless of Maintenance Mode/INST dial position.
3. The end of the curve is determined by the interrupting rating of the circuit breaker.
4. Total clearing times shown include the response times of the trip unit,the breaker opening,
and the interruption of the current.
5. Nominal Values (Pickup) (Tolerance is 15%) 2.5X In, 4X In, 6X In, 7X In, 8X In, 10X In, 12X In.
6. These curves are comprehensive for the complete family of Series G L-Frame electronic
breakers, including all frame sizes, ratings, and constructions. The total clearing times
shown are conservative and consider the maximum response times of the trip unit,
the circuit breaker opening, and the interruption of the current in worst case conditions,
such as maximum rated voltages, single-phase interruption, and minimum power factor.
Faster clearing times are possible depending on the specific system conditions.
7. For L-Frame breakers with 250A sensors (In = 250A), an INST setting of 12 is equal to
28X (7000A).
8. Contact Eaton for additional information.

Digitrip 310+ Circuit Breaker Time/Current Curves


Maintenance Mode / Instantaneous Setting
Series G L-Frame Trip Unit Nameplates
ALSI (With Maintenance Mode)
68C 4580 H18

Push to Trip
Remote MM

I i (xIn)
INST
7 8 10
6
12
4
2.5
Maintenance Mode

TEST /
ALARM

IR

C
B

D E F
A

G
H

STATUS

t R (s)
I sd (xIR)
LONG
SHORT
10 12 15
5 6 7
7
20 4
8
4
24 3
10
2
2
12

t sd (ms)
SHORT
120

50

300

ALSIG (With Maintenance Mode)

68C 4580 H17

Push to Trip

I i (xIn)
INST
7 8 10
6
12
4
2.5
Maintenance Mode

NO
NC
Settings

50
120
(ms)
300

Remote MM

t sd

TEST /
ALARM

IR

C
B

D E F
A

G
H

STATUS

This feature allows enabling of the


maintenance mode remotely by applying
24 Vdc to the yellow (+) and black ()
wires that exit the left hand side of the
breaker. The maintenance mode settings
that is enabled is the 2.5X setting.

50
J
M
P

t g (ms)

There are two indicators that can verify


that the trip unit has been remotely
activated/enabled into the maintenance
mode feature:

120 300
K
L
N
O
Q
R

t R (s)
I sd (xIR)
I g (xIn) t sd / t g (ms)
SHORT
LONG
GND
SHORT / GND
10 12 15
5 6 7
.6 .8 1.0 M N O
7
20 4
8 .4
L
P
4
24 3
10 .3
K
Q
R
2
2
.2
J
12

Left Side of Breaker


Black

AND/OR

Yellow

B.





24 Vdc
Black
Blue

Relay Wiring

Red

Maintenance Mode Trip

10
9
8
7
6
5

The relay output is provided by


three wires exiting the left hand
side of the breaker: blue = C,
red = NO, black = NC. The relay
will change state when the
maintenance mode is
remotely enabled.

Instantaneous Mode Trip

10
9
8
7
6
5
4

0.3

0.3

2.5

0.2

0.2
10

0.1
0.09
0.08
0.07
0.06
0.05
0.04

12

Application
Determines
End of Curve

28

Application
Determines
End of Curve 0.04

0.03

0.03

0.02

0.02

0.01

0.6 0.8 1
0.5 0.7 0.9

4 5 6 789
10

20

30 40 50

10

Current in Multiples of Rating (In)

Figure 5. Maintenance Mode / Instantaneous Setting (ALSI, ALSIG)Curve Number TC01207014E, May 2008

0.1
0.09
0.08
0.07
0.06
0.05

eaton www.eaton.com

0.01
100

Time in Seconds

0.4

1
0.9
0.8
0.7
0.6
0.5
0.4

1
0.9
0.8
0.7
0.6
0.5

Time in Seconds

A. The blue LED (MM) located on the


top left side of the trip unit
will light.

Time Current Curves TD012019EN

Series G
L-Frame

Effective March 2014

10,000

10,000
Thermal-Magnetic Circuit Breaker Time/Current Curves
Series G LG-Frame Circuit Breakers
Catalog Types: LGE, LGS, LGH, LGC, LGU, and LGX circuit breakers, three- and four-pole.
For application and coordination purposes only. Thermal calibration based on +40C ambient,
cold start. Connected with four feet of rated wire (+75C) per terminal. Tested in open air
with current in all poles. Instantaneous calibration based on single-pole tests.
Maximum Voltage: 690 Vac (50/60 Hz)250 Vdc.

Breaker Rating

1000

1000

Rated
Amperes (In)

Instantaneous Trip
Amperes

250630

500 to 1000% of trip unit rating (DC values are approximately 40% higher)

Interrupting Rating

100

Maximum
Minimum

Time in Seconds

10

Breaker Type

UL/CSA rms Sym. kA, 50/60 Hz


240V
480V
600V

LGE
LGS
LGH
LGC
LGU
LGX

65
85
100
200
200
200

Breaker Type

IEC 60947-2 rms Sym. kA, 50/60 Hz


240V, (Ue)
415V, (Ue)
690V,

(Ue)

kA, DC
250V, (Ue)

LGE
LGS
LGH
LGC
LGU
LGX

Icu
65
85
100
200
200
300

Ics
6
10
13
15
18
35 10

Icu
22
22
42
42
50
50

35
50
65
100
150
200

Ics
65
65
100
200
200
200

Icu
35
50
70
100
150
200

18
25
35
50
65
65

Ics
35
50
70
100
150
200

Icu
12
20
25
30
35
65

kA, DC
250V

22
22
42
100 42
50
50

Ics
22
22
42
42
50
50

Adjustable Magnetic Trip


1

20%

5X

10X

0.1

10%

0.1

Maximum Clearing Time

0.01

0.01

Interrupting Rating Determines End of Curve

0.001

10

100
Current in Multiples of Rating (In)

1000

0.001
10,000

Figure 6. Thermal-Magnetic LGE, LGS, LGH, LGC, LGU, and LGX Circuit BreakersCurve Number TC01208002E, January 2010

eaton www.eaton.com

Time Current Curves TD012019EN

Series G
L-Frame

Effective March 2014

Thermal-Magnetic Circuit Breaker Time/Current Curves


Series G LG-Frame Circuit Breakers
Catalog Types: LHH circuit breakers, three-pole.
For application and coordination purposes only. Thermal calibration based on 40C ambient,
cold start. Connected with four (feet of rated wire (+75C) per terminal. Tested in open air
with current in all poles. Instantaneous calibration based on single-pole tests.
Maximum Voltage: 690 Vac (50/60 Hz)250 Vdc (2 poles in series).

Breaker Rating

10,000

Thermal Curve

Time in Seconds

1000

Rated
Amperes (In)

Magnetic
Trip Point a

Approx. Continuous
Current Multiplier

125
150
175
200
225
250
300
350
400

2500
2500
4000
4000
6000
6000
6000
6000
6000

20X
17X
22X
20X
26X
24X
20X
17X
15X

Instantaneous
Trip Amperes

See curve below


(DC values are approx.
40% higher)
Note: Magnetic
pickup tolerance
is 20%

Interrupting Rating
UL/CSA rms Sym. kA, 50/60 Hz
240V
480V
600V

kA, DC
250V

LHH

100

42

Breaker Type

IEC 60947-2 rms Sym. kA, 50/60 Hz


240V, (Ue)
415V, (Ue)
690V,

(Ue)

kA, DC
250V, (Ue)

LHH

Icu
100

Ics
13

Icu
42

Breaker Type

100

Maximum

65

Ics
100

Icu
70

35

Ics
70

Icu
25

a Magnetic trip point tolerance is 20%.

10
Minimum

10

100

1000

10,000

Current in Multiples of Rating (In)

Magnetic Pickup
1

4000A
2500A

6000A

Time in Seconds

20%

0.1

Maximum
Interruption
Time

0.01

Interrupting Rating Determines End of Curve

0.001
100

1000

10,000

100,000

1,000,000

Current in Amperes (I)

Figure 7. Thermal-Magnetic LHH High Instantaneous Circuit BreakerCurve Number TC01206004E, September 2009

10

eaton www.eaton.com

Ics
42

Time Current Curves TD012019EN

Series G
L-Frame

Available Short-Circuit Current, kA rms

1000 kA
1 kA

5 kA

10 kA

50 kA

100 kA

1 kA

5 kA

Available Ip for 1st


symm. 1/2 cycle

10 kA

50 kA 100 kA

200 kA

EG CL100A

EG3125

LG3600

JG3250

Effective March 2014

Peak Let-Through Current, kA

Available Short-Circuit Current, kA rms

1000 kA
200 kA

10,000

100,000

500,000

1,000,000

5,000,000

10,000,000

1 kA

5 kA

10 kA

50 kA 100 kA

EG CL 100A

LG3600

JG3250

EG3125

Figure 8. Peak Let-Through Current Series G Types LG, JG, EG, and EG CL (with Current Limiter), Molded-Case Circuit Breakers
240VCurve Number TC01200001E-A, April 2012

Peak Let-Through I2t, A2 sec

Figure 9. Peak Let-Through I2t Series G Types LG, JG, EG, and EG CL (with Current Limiter), Molded-Case Circuit Breakers
240VCurve Number TC01200001E-A, April 2012
NNote: All values are typical.
eaton www.eaton.com

11

Time Current Curves TD012019EN

Series G
L-Frame

Available Short-Circuit Current, kA rms

1000 kA

500 kA
1 kA

5 kA

10 kA

50 kA

100 kA

1 kA

5 kA

Available lp for 1st


symm. 1/2 cycle

10 kA

50 kA

100 kA

EG CL 100A

EG3125

JG3250

JG CL 250A

LG3600

Effective March 2014

Peak Let-Through Current, kA

Available Short-Circuit Current, kA rms

1000 kA

500 kA
100,000

500,000

1,000,000

500,000

10,000,000

1 kA

5 kA 10 kA

50 kA 100 kA

EG3125

EG CL 100A

JG CL 250A

LG3600

JG3250

Figure 10. Peak Let-Through Current Series G Types LG, JG CL, JG, EG, and EG CL (with Current Limiter), Molded-Case Circuit
Breakers480VCurve Number TC01200001E-B, April 2012

Peak Let-Through I2t, A2 sec

Figure 11. Peak Let-Through I2t Series G Types LG, JG, JG CL, EG, and EG CL (with Current Limiter), Molded-Case Circuit Breakers
480VCurve Number TC01200001E-B, April 2012
NNote: All values are typical.
12

eaton www.eaton.com

Time Current Curves TD012019EN

Series G
L-Frame

10 kA
1 kA

5 kA

10 kA

100 kA

50 kA

1 kA

5 kA

Available Ip for 1st


symm. 1/2 cycle

Available Short-Circuit Current, kA rms

1000 kA

500 kA
50 kA

100 kA

EG CL 100A
EG3125

JG3250

LG3600

JG CL 250A

Effective March 2014

Peak Let-Through Current, kA

5 kA 10 kA
100,000

500,000

1,000,000

5,000,000

10,000,000

1 kA

Available Short-Circuit Current, kA rms

500 kA
1000 kA
50 kA 100 kA

EG CL 100A
EG3125

JG3250

LG3600

JG CL 250A

Figure 12. Peak Let-Through Current Series G Types LG, JG CL, JG, EG, and EG CL (with Current Limiter), Molded-Case Circuit
Breakers600VCurve Number TC01200001E-C, April 2012

Peak Let-Through I2t, A2 sec

Figure 13. Peak Let-Through I2t Series G Types LG, JG, JG CL, EG, and EG CL (with Current Limiter), Molded-Case Circuit Breakers
600VCurve Number TC01200001E-C, April 2012
NNote: All values are typical.
eaton www.eaton.com

13

Time Current Curves TD012019EN

Series G
L-Frame

Available Short-Circuit Current, kA rms

1000 kA

500 kA
1 kA

5 kA

10 kA

50 kA

100 kA

1 kA

5 kA

Available Ip for 1st


symm. 1/2 cycle

10 kA

50 kA

100 kA

JGU3250

LGU3600

Effective March 2014

Peak Let-Through Current, kA

1000 kA
Available Short-Circuit Current, kA rms

500 kA
10,000

100,000

500,000

1,000,000

5,000,000

10,000,000

1 kA

5 kA 10 kA

50 kA 100 kA

JGU3250

LGU3600

Figure 14. Peak Let-Through Current Series G Types LGU and JGU Molded-Case Circuit Breakers240VCurve Number
TC01200001E-D, April 2012

Peak Let-Through I2t, A2 sec

Figure 15. Peak Let-Through I2t Series G Types LGU and JGU Molded-Case Circuit Breakers240VCurve Number TC01200001E-D,
April 2012
NNote: All values are typical.
14

eaton www.eaton.com

Time Current Curves TD012019EN

Series G
L-Frame

1000 kA
Available Short-Circuit Current, kA rms

500 kA
1 kA

5 kA

10 kA

50 kA

100 kA

1 kA

5 kA

Available Ip for 1st


symm. 1/2 cycle

10 kA

50 kA

100 kA

JGU3250

LGU3600

Effective March 2014

Peak Let-Through Current, kA

Available Short-Circuit Current, kA rms

1000 kA

100,000

500,000

1,000,000

5,000,000

10,000,000

1 kA

5 kA 10 kA

50 kA 100 kA

LGU3600

JGU3250

500 kA

Figure 16. Peak Let-Through Current Series G Types LGU and JGU Molded-Case Circuit Breakers480VCurve Number
TC01200001E-E, April 2012

Peak Let-Through I2t, A2 sec

Figure 17. Peak Let-Through I2t Series G Types LGU and JGU Molded-Case Circuit Breakers480VCurve Number TC01200001E-E,
April 2012
NNote: All values are typical.
eaton www.eaton.com

15

Time Current Curves TD012019EN

Series G
L-Frame

100 kA
1 kA

5 kA

10 kA

50 kA

100 kA

1 kA

Available Ip for 1st


symm. 1/2 cycle

5 kA

10 kA

Available Short-Circuit Current, kA rms

50 kA

JGU3250

LGU3600

Effective March 2014

Peak Let-Through Current, kA

Available Short-Circuit Current, kA rms

100 kA
100,000

500,000

1,000,000

5,000,000

10,000,000

1 kA

5 kA

10 kA

50 kA

JGU3250

LGU3600

Figure 18. Peak Let-Through Current Series G Types LGU and JGU Molded-Case Circuit Breakers600VCurve Number
TC01200001E-F, April 2012

Peak Let-Through I2t, A2 sec

Figure 19. Peak Let-Through I2t Series G Types LGU and JGU Molded-Case Circuit Breakers600VCurve Number TC01200001E-F,
April 2012
NNote: All values are typical.
16

eaton www.eaton.com

Time Current Curves TD012019EN

Series G
L-Frame

1000 kA
Available Short-Circuit Current, kA rms

1 kA

5 kA

10 kA

50 kA

100 kA

1 kA

Available Ip for 1st


symm. 1/2 cycle

5 kA 10 kA

50 kA 100 kA

LGX3600

JGX3250

500 kA

Effective March 2014

Peak Let-Through Current, kA

Available Short-Circuit Current, kA rms

1000 kA

500 kA
10,000
1 kA

100,000

500,000

1,000,000

5,000,000

10,000,000

5 kA 10 kA

50 kA 100 kA

JGX3250

LGX3600

Figure 20. Peak Let-Through Current Series G Types LGX and JGX Molded-Case Circuit Breakers240VCurve Number
TC01200001E-G, April 2012

Peak Let-Through I2t, A2 sec

Figure 21. Peak Let-Through I2t Series G Types LGX and JGX Molded-Case Circuit Breakers240VCurve Number TC01200001E-G,
April 2012
NNote: All values are typical.
eaton www.eaton.com

17

Time Current Curves TD012019EN

Series G
L-Frame

1000 kA
Available Short-Circuit Current, kA rms

1 kA

5 kA

10 kA

100 kA

50 kA

1 kA

5 kA

Available Ip for 1st


symm. 1/2 cycle

10 kA

50 kA 100 kA

LGX3600

JGX3250

500 kA

Effective March 2014

Peak Let-Through Current, kA

Available Short-Circuit Current, kA rms

1000 kA

500 kA
100,000

500,000

1,000,000

5,000,000

10,000,000

1 kA

5 kA 10 kA

50 kA 100 kA

JGX3250

LGX3600

Figure 22. Peak Let-Through Current Series G Types LGX and JGX Molded-Case Circuit Breakers480VCurve Number
TC01200001E-H, April 2012

Peak Let-Through I2t, A2 sec

Figure 23. Peak Let-Through I2t Series G Types LGX and JGX Molded-Case Circuit Breakers480VCurve Number TC01200001E-H,
April 2012
NNote: All values are typical.
18

eaton www.eaton.com

Time Current Curves TD012019EN

Series G
L-Frame

Available Short-Circuit Current, kA rms

1000 kA

500 kA
1 kA

5 kA

10 kA

50 kA

100 kA

1 kA

5 kA

Available Ip for 1st


symm. 1/2 cycle

10 kA

50 kA 100 kA

JGX3250

LGX3600

JG CL 250A

Effective March 2014

Peak Let-Through Current, kA

Available Short-Circuit Current, kA rms

1000 kA

500 kA
100,000

500,000

1,000,000

5,000,000

10,000,000

1 kA

5 kA 10 kA

50 kA 100 kA

JGX3250

LGX3600

JG CL 250A

Figure 24. Peak Let-Through Current Series G Types LGX, JG CL and JGX Molded-Case Circuit Breakers600VCurve Number
TC01200001E-I, April 2012

Peak Let-Through I2t, A2 sec

Figure 25. Peak Let-Through I2t Series G Types LGX, JG CL and JGX Molded-Case Circuit Breakers600VCurve Number
TC01200001E-I, April 2012
NNote: All values are typical.
eaton www.eaton.com

19

Time Current Curves TD012019EN

Series G
L-Frame

Effective March 2014

Table 4. 240V Peak Let-Through (Ip) and Clearing (I2t) Values for Series G High-Performance Breakers
Maximum Available Fault Current
Frame/Max.
Amperes (UL)

65 kA

100 kA

150 kA

Ip (kA)

35 kA
I2t (A2 sec)

42 kA
Ip (kA)

I2t (A2 sec)

Ip (kA) I2t (A2 sec)

Ip (kA) I2t (A2 sec)

Ip (kA)

I2t (A2 sec)

Ip (kA)

I2t (A2 sec)

LGC/600A
LGU/600A
LGX/600A

30
30
30

2,000,000
2,000,000
2,000,000

33
33
33

2,100,000
2,100,000
2,100,000

38
38
38

45
45
45

N/A
48
48

N/A
2,800,000
2,800,000

N/A
N/A
52

N/A
N/A
2,900,000

2,300,000
2,300,000
2,300,000

2,600,000
2,600,000
2,600,000

200 kA

Table 5. 480V Peak Let-Through (Ip) and Clearing (I2t) Values for Series G High-Performance Breakers
Maximum Available Fault Current
Frame/Max.
Amperes (UL)

100 kA

150 kA

Ip (kA)

35 kA
I2t (A2 sec)

50 kA
Ip (kA)

I2t (A2 sec)

Ip (kA)

65 kA
I2t (A2 sec)

Ip (kA) I2t (A2 sec)

Ip (kA)

I2t (A2 sec)

Ip (kA)

I2t (A2 sec)

LGC/600A
LGU/600A
LGX/600A

37
37
37

4,300,000
4,300,000
4,300,000

42
42
42

5,000,000
5,000,000
5,000,000

48
48
48

5,500,000
5,500,000
5,500,000

55
55
55

N/A
62
62

N/A
6,800,000
6,800,000

N/A
N/A
69

N/A
N/A
7,000,000

6,000,000
6,000,000
6,000,000

Table 6. 600V Peak Let-Through (Ip) and Clearing (I2t) Values for Series G High-Performance Breakers
Maximum Available Fault Current
35 kA
Frame/Max.
Amperes (UL) Ip (kA) I2t (A2 sec)

50 kA

65 kA

Ip (kA)

I2t (A2 sec) Ip (kA) I2t (A2 sec)

LGC/600A
LGU/600A
LGX/600A

46
46
46

7,200,000
7,200,000
7,200,000

20

39
39
39

6,400,000
6,400,000
6,400,000

eaton www.eaton.com

N/A
50
50

N/A
8,000,000
8,000,000

200 kA

Time Current Curves TD012019EN

Series G
L-Frame

1000
900
800
700
600
500

Effective March 2014

0.01

0.05
0.07 0.1
0.02 0.03 0.04

0.2

0.3 0.4 0.5 0.7

1.0

2.0

50.0

20.0

3.0 4.0 5.0 7.0 10.0

80.0

Circuit Breaker Time/Current Curves


Earth Leakage LG Circuit BreakersUL
Catalog Types: ELLBN circuit breakers, three- and four-pole.

400

N Notes:

400

1000
900
800
700
600
500

1. LG Circuit Breaker Earth Leakage Module, three- and four-pole,110480V 60 Hz.


300
2. For application and coordination purposes only. 20C to +55C ambient.
3. Total clearing times include the response time of the Earth Leakage Module, the opening
200
time of the circuit breaker, and the interruption of the current.
4. For additional curve tolerances, contact Eaton.

300
200

100
90
80
70
60
50

100
90
80
70
60
50

40

40

30

30

20

20

10
9
8
7
6
5

Available Ig (A)
Settings

0.03

0.1

0.5

30

10
9
8
7
6
5

1
0.9
0.8
0.7
0.6
0.5

500 ms

1
0.9
0.8
0.7
0.6
0.5

0.4

300 ms

0.4

0.3

0.3
150 ms

0.2

0.1
0.09
0.08
0.07
0.06
0.05

0.2

0.1
0.09
0.08
0.07
0.06
0.05

60 ms

0.04

0.04

0.03

0.03
Inst.

0.02

0.02

0.01
0.009
0.008
0.007
0.006
0.005

0.01
0.009
0.008
0.007
0.006
0.005

0.004

0.004

0.003

0.003

0.002

0.002

0.001

Time in Seconds

Time in Seconds

1S

0.01

0.02 0.03 0.04


0.07 0.1
0.05

0.2

0.3 0.4 0.5 0.7


Ig (A)

10

20

50

80

0.001

Figure 26. UL LG Circuit Breaker Earth Leakage Module, Three- and Four-Pole, 110480VCurve Number TC01212009E,
September 2005
eaton www.eaton.com

21

Time Current Curves TD012019EN

Series G
L-Frame

Effective March 2014

1000
900
800
700
600
500

0.01

0.05
0.02 0.03 0.04
0.07 0.1

0.2

0.3 0.4 0.5 0.7 1.0

2.0

3.0 4.0 5.0 7.0 10.0

20.0

50.0

80.0

Catalog Types: ELLBE circuit breakers, three- and four-pole.

1000
900
800
700
600
500

400

N Notes:

400

300

1. LG Circuit Breaker Earth Leakage Module, three- and four-pole,110480V 60 Hz. 300
2. For application and coordination purposes only. 20C to +55C ambient.
3. Total clearing times include the response time of the Earth Leakage Module, the opening
200
time of the circuit breaker, and the interruption of the current.
4. For additional curve tolerances, contact Eaton.

Circuit Breaker Time/Current Curves


Earth Leakage LG Circuit BreakersIEC

200

100
90
80
70
60
50
40

100
90
80
70
60
50
40

30

30

20

20
0.03

10
9
8
7
6
5
4

0.1

0.3

10

Available In Settings

10
9
8
7
6
5
4

1
0.9
0.8
0.7
0.6
0.5
0.4

1
0.9
0.8
0.7
0.6
0.5
0.4

500 ms

300 ms

0.3

0.3

0.2

150 ms

0.2

0.1
0.09
0.08
0.07
0.06
0.05
0.04

60 ms

0.1
0.09
0.08
0.07
0.06
0.05
0.04

0.03

0.03
Inst.

0.02

0.02

0.01
0.009
0.008
0.007
0.006
0.005
0.004

0.01
0.009
0.008
0.007
0.006
0.005
0.004

0.003

0.003

0.002

0.002

0.001

0.01

0.02 0.03 0.04


0.07 0.1
0.05

0.2

0.3 0.4 0.5 0.7 1


In (Amperes)

10

20

50

80

Figure 27. IEC LG Circuit Breaker Earth Leakage Module, Three- and Four-Pole, 110480VCurve Number TC01212008E,
September 2005
22

eaton www.eaton.com

0.001

Time in Seconds

Time in Seconds

1S

Series G
L-Frame

Time Current Curves TD012019EN


Effective March 2014

eaton www.eaton.com

23

Time Current Curves TD012019EN


Effective March 2014

Series G
L-Frame

Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
2014 Eaton
All Rights Reserved
Printed in USA
Publication No. TD012019EN / Z14584
March 2014

Eaton is a registered trademark.


All other trademarks are property
of their respective owners.

You might also like