Boiler feed pump

Boiler feed pumps are also referred to as feed pumps (see Reactor pump) and designed as
multistage radial flow pumps. (Also see Multistage pump.)
They serve to feed a steam generator such as a boiler or a nuclear reactor with a quantity of
feed water corresponding to the quantity of steam emitted. Today, all boiler feed pumps
are centrifugal pumps.
The design of boiler feed pumps regarding power input, material, type of
pump and drive is largely governed by the developments which have taken place in power
station technology. The trend in fossil-fuelled power stations is towards larger and larger
power station units (> 1000 MW in 2011). This has led to boiler feed pumps with a drive
rating of 30 - 50 MW.
Until 1950, the average pressure in the outlet cross-section of the pump (discharge pressure
of the feed pump) was in the 200 bar region. By 1955 the average discharge pressure had
risen to 400 bar. The mass flow rates were in the region of 350 tonnes/h in 1950, compared
to 3200 tonnes/h (in some exceptions up to 4000 tonnes/h) today. Boiler feed pumps operate
at fluid temperatures of 160 to 210 C. In exceptional cases the temperature of the fluid
handled may be higher still.
Feed pumps for 1600 MW nuclear power stations are constructed for mass flow rates of up to
4000 tonnes/h and feed pump discharge pressures of 70 to 100 bar.
Until 1950 approximately, boiler feed pumps were made of unalloyed steels; since then they
have been made of steels with a chrome content of 13 - 14 %. This change of materials was
made necessary by the introduction of new chemical feed water compositions. The
development of highstrength, corrosion and erosion resistant martensitic chrome steels with
good anti-seizure properties as well as the continuous development of all pump components
(bearings, shaft seal, pump hydraulic system, etc.) paved the way for present-day boiler feed
pumps with rotational speeds of 4500 to 6000 rpm.
The mass flow rates of centrifugal pumps rose rapidly in conjunction with the rise of unit
outputs in power stations. Today's full load feed pumps for conventional 800 to 1100 MW
power station units are constructed with four to six stages with stage pressures of up to 80
bar. Feed pumps for 1600 MW nuclear power stations are of the single-stage type.
Drive
In the case of conventional power stations above 500 MW full load feed pumps are
increasingly driven by steam turbines. In most cases condensing turbines running at 5000 to
6000 rpm are used.
Electric motors usually drive part load feed pumps, both in fossil-fuelled and in nuclear
power stations. Speed control of electrically driven feed pumps is effected by either fluid

coupling (e. g. variable speed turbo couplings) or by electrical closed-loop control systems
by means of thyristors (up to a drive rating of approximately 18 MW in 2011).
Four options of installing boiler feed pump drives are commonly used at present. See Fig. 1
Boiler feed pump

Fig. 1 Boiler feed pump: Model


with VP-EM-RG-HP layout

The low-speed booster pump is usually driven by the free shaft end of the turbine via a stepdown gear or directly by the free end of the electric motor. See Fig. 2 Boiler feed pump

Fig. 2 Boiler feed pump:


Arrangement layouts of feed pump sets

The single or double suction booster pump serves to generate the necessary NPSHR of the
system for the high-speed boiler feed pump connected downstream. Fig. 3 Boiler feed pump

Fig. 3 Boiler feed pump:


Double-suction boiler feed booster pump

Design
For conventional power stations boiler feed pumps are designed as:

Multistage barrel pull-out pumps, see Fig. 4 Boiler feed pump

Ring-section pumps, see Fig. 5 Boiler feed pump

Fig. 4 Boiler feed pump: Barrel


pull-out model with tapping stage

Fig. 5 Boiler feed pump: Ringsection model with tapping stage

These two types only differ in the construction of their pressure-retaining enclosure, which
influences the manufacturing costs and ease of installation. There are no differences with
regard to operating reliability and robustness also in abnormal operating conditions. The
dimensions of the rotating parts and flow passages can be designed identically.
Two aspects of deciding between a ring-section and a barrel pull-out pump are
described below:

The smaller the mass flow rate and the higher the pressure, the higher the material
and manufacturing costs of barrel pull-out pumps. This does not apply to the same extent
to ring-section pumps.

Barrel pull-out pumps have some advantages over ring-section pumps when it comes
to repairing a pump installed in the system. If a rotor has to be replaced, the barrel
(see Pump casing) can remain installed in the piping. This is significant with regard to
the availability of a power station unit, if no full pump back-up is available or if pump
replacement is very time-consuming.
In the case of nuclear power stations, single-stage feed pumps with doubleentry impeller (see Double-suction pump) and double volute casing are usually
adopted. See Fig. 6 Boiler feed pump

Fig. 6 Boiler feed pump:


Double-suction reactor feed pump made of cast iron

Cast pressure-retaining casing parts are increasingly replaced by forged parts. As an example,
such a feed pump could be designed with a flow rate of about 4200 m3/h and a head of
about 700 m at a rotational speed of 5300 rpm. See Fig. 5 Boiler feed pump
Heads of reactor feed pumps are in the region of 800 m for boiling water reactors and 600 m
for pressurised water reactors. The flow rates are about twice as high as those of a
comparable boiler feed pump in a fossil-fuelled power station.
Casing
For boiler feed pumps two factors have to be considered regarding the wall thickness of the
casing: the pressure loads and the different temperature conditions it needs to withstand.
These two criteria are satisfied by adopting a high-strength ferritic casing material which
enables the wall thickness to be kept thin enough to avoid any overloads as a result of
temperature fluctuations, yet of adequate thickness to guarantee the requisite safety against
internal pressure.
Barrel casing

The casings of barrel pull-out pumps and barrel casing pumps are usually made of
unalloyed or low-alloyed ductile forged steel. Deposit welding is used on all surfaces in
contact with the feed water to coat them with corrosion and erosion resistant material.

In order to weld the pump into the piping, an adapter must be provided if the
materials of the nozzles to be connected are from different material groups.

The discharge-side (discharge pressure containing) barrel cover is fastened by means


of large non-torqued studs. Sealing is provided by a profile joint which is pressurised purely
by the prevailing pressure (of up to several 100 bar) without any external forces acting on
it. See Fig. 7 Boiler feed pump

Fig. 7 Boiler feed pump: Profile


rings

Ring-section pumps

The casings of ring-section pumps are preferably made of forged chrome or carbon
steel plated with austenitic (iron solid solution) material.

The sealing element between the individual stage casings (see Stage) seals off by
metal-to-metal contact, the individual casings being clamped together axially by tie bolts
between the suction and discharge casings (see Pump casing).

Thermal shocks causing various thermal expansions mainly lead to additional loads on
the tie bolts and sealing surfaces of the stage casings.
A common feature of barrel pull-out pumps and ring-section pumps is that the greater the
wall thickness, the greater the thermal stress caused by thermal shocks, which in turn
reduces the service life of the pump. The provision of injection water at a pressure situated
between the suction and discharge pressure of the pump is a frequent requirement. This is
taken care of by tapping water from one of the pump stages of both barrel pull-out pumps and
ring-section pumps.
Tapping a stage of a boiler feed pump

In the case of ring-section pumps, a partial flow at an intermediate pressure can easily
be tapped through a tapping nozzle in one of the stage casings. See Fig. 5 Ring-section
pump

In the case of barrel pull-out pumps, the inside of the barrel is divided into three
pressure zones so that a partial flow at the required intermediate pressure can be led off
directly to the outside. See Fig. 4 Barrel pull-out pump
The sealing function is taken care of by a profile joint between the discharge and the
tapping pressure, and by a metal-to-metal joint between the tapping and the inlet
pressure. See Fig. 7 Boiler feed pump
Especially the profile joint allows a great degree of relative motion of the sealing surface, as
required for any temperature shocks.
Rotor design

The pump shaft of boiler feed pumps has a very small static deflection as the bearings are
spaced as closely as possible, the shaft diameter is relatively large and the impellers are
usually shrunk onto the shaft (for high performance). The pump shaft is generally insensitive
to vibrations and runs smoothly (see Smooth running) without any radial contact during
normal operation. The hub diameter at the back of the impeller is increased and the impeller
inlet geometry is designed with a minimum diameter, so as to reduce the remaining axial
forces (see Axial thrust) which have to be absorbed by the balancing device.
The rotors of single-stage reactor feed pumps are even stiffer than those of boiler feed
pumps, and their static deflection is smaller than that of multistage boiler feed pumps.
Axial thrust balancing
Some impeller arrangements of boiler feed pumps for conventional power stations
cause axial thrust at the impellers. See Figs. 10 to 12 Axial thrust
The magnitude of this axial thrust depends on the position of the operating point on the
characteristic curve, the rotational speed and the amount of wear on the internal clearances
(see Controlled gap seal). Additional disturbing forces can arise in the event of abnormal
operating conditions, e.g. cavitation.
On larger boiler feed pumps the axial forces at the pump rotor are balanced by means of a
hydraulic balancing device through which the fluid handled flows. The balancing device is
often combined with an oil-lubricated thrust bearing (see Plain bearing). As this balancing
device absorbs more than 90 % of the axial thrust, a relatively small thrust bearing can be
used. The balancing device may comprise a balance disc with balance disc seat, or a balance
drum or double drum with the corresponding throttle bushes.
Axial thrusts arising in reactor feed pumps with double-entry impeller (see Double-suction
pump) are balanced hydraulically; residual thrusts are absorbed by an oil-lubricated thrust
bearing. See Fig. 6 Boiler feed pump
Balancing of radial forces on the pump rotor
Radial forces arise from the weight of the rotor, mechanical unbalance or hydraulic radial
thrust. The radial forces are balanced by two oil-lubricated radial bearings as well as by
throttling clearances through which the fluid handled flows in axial direction. Such throttling
clearances are located at the impeller neck on the impeller inlet side, or in the case of
multistage boiler feed pumps for conventional power stations on the discharge side of the
impeller (interstage bush) and at the balance drum. If the rotor is in an off-centre position, a
re-centring reaction force will be generated in these clearances, which largely depends on the
pressure difference and the clearance geometry (LOMAKIN effect).
The LOMAKIN effect is severely reduced when, due to abnormal operating conditions, the feed
water in the clearance is not in a purely liquid phase (see Cavitation).
The hydrostatic action of the clearances contributes more to reducing shaft deflection than
the mechanical stiffness does. The system is designed in such a way that operating speed
always remains well away from the critical speed of the rotor, allowing hydraulic exciting
forces (particularly in low flow operation) to be absorbed in addition.

An additional diffuser or a double volute can reduce radial thrust. See Fig. 6 Volute casing
pump
Shaft seal
Common shaft seals for boiler feed pumps are mechanical seals, floating ring seals and
labyrinth seals. Gland packings are less common these days. (Also see Shaft seal).
Warming up and keeping warm
Transient or low flow operating conditions cause additional loads on boiler feed pumps. This
leads to additional stresses and strains as well as to deformation of components with various
consequences on their functionality.
Nowadays, almost all boiler feed pumps must be able to handle both cold starts (hightemperature shock loads) and semi-warm starts without any damage. In these start-up
procedures hot feed water abruptly flows into the cold pump, which results in the inner
components heating up much faster than the pressure boundary. Depending on the frequency
of starts and the gradient curves of pressure and temperature(load cycles) this can shorten
the service life of the pump.
On machines with particularly thick walls the heat will propagate more slowly in the thickwalled components, thus increasing internal stresses.
Contact between parts of the rotor and the stator cannot, generally, be ruled out as narrow
clearances are used as controlled gap seals. This applies to the impeller neck on the
impeller inlet side, the discharge-side clearance between impeller, diffuser and interstage
bush as well as the balancing device with several throttling clearances (depending on the
design).
Critical operating conditions such as the formation of vapour bubbles, for example, cannot be
completely avoided in the inlet line. Brief contact between the stator and the rotor leads to
high unbalance forces in the narrow clearances. For this reason the material pairs have to be
resistant not only to corrosion and erosion but also especially to wear (incorporating good
anti-seizure properties). Profiled chrome steels and a special clearance geometry have proven
successful.
In operating conditions with a very low or zero flow, e.g. in the turning gear mode of a turbinedriven boiler feed pump, temperature layers establish in the fluid handled, which may cause
deformation of the rotors and, after a slight delay, also of the non-rotating components. Once
the clearance gaps are closed the rotor will be subjected to a significantly higher friction
moment, leading to overload of the turning gear and to standstill of the pump. In this case,
the temperature will no longer be equalised at the rotor, which will further aggravate the rotor
deformation.

This can result in several hours of downtime for the pump. Usually the only remedy is to let
the machine cool down to reduce or eliminate the critical temperature layers and the
deformation.
Several actions can be taken to optimise the thermal behaviour of the pump:
Avoid large differences in temperature in and on the pump

Thermally separate the cold areas (shaft seal area) from the area through which the
hot fluid passes (hydraulic system and balancing device) by means of an insulation
chamber system; provide a thermal seal to prevent convection flows and special
thermosleeves.

Insulate the outside of the pump.

Warm up or keep warm the pump by means of forced flow through the machine,
usually via throttled pressure supply.

Temporarily or permanently interrupt the cooling water supply in the area of the
mechanical seal (secondary circuit).

Limit the operating parameters for critical operating conditions (T) (top/bottom of the
barrel casing) and/or T between casing and feed water.
Reduce the effects of large temperature differences

Rotate the pump in stand-by mode using turning gear.

Employ synchronised turning gear (minimise or prevent actual standstill time).

Drain water from critical thermal areas.


Select good thermal characteristics when choosing shaft seals

Fit a non-contacting seal (floating ring seal).


The above measures are frequently used for barrel casing pumps (barrel pull-out pumps)
as their outer dimensions, wall thickness, drive (turbine with turning gear) and operating
modes are considered more critical than those of ring-section pumps. If possible, these
measures are always automated to safeguard the availability of the pump set.
Minimum flow valve
A minimum flow valve (automatic recirculation valve) ensures a minimum flow rate and
thus prevents damage which could occur in low flow operation as a result of either an
impermissible increase in temperature leading to vaporisation of the pump content or low
flow cavitation.