PEMEX REFINACION

HVAC Load Analysis


for

REFINERIA ING. ANTONIO M. AMOR


SUBESTACION ELECTRICA SE-EC-04

Prepared By:
CORPORACION IPSA S.A DE C.V
J.A.A.
G.N.L.O.
Agosto 2015

Chvac - Full Commercial HVAC Loads Calculation Program


Pimaarc
Cuajimalpa de Morelos, DF 05410

Elite Software Development, Inc.


PEMEX REFINACION
Page 2

General Project Data Input


General Project Information
Project file name:
Project title:
Project date:
Weather reference city:
Client name:
Client address:
Company name:
Company address:
Company city:
Company e-mail address:
Company website:

CC SALAMANCA EC-04 AGO 2015 2.CH8


PEMEX REFINACION
Agosto 2015
SALAMANCA, GUANAJUATO, MEXICO
REFINERIA ING. ANTONIO M. AMOR
SUBESTACION ELECTRICA SE-EC-04
CORPORACION IPSA S.A DE C.V
J.A.A.
G.N.L.O.
ventas@corporacionipsa.com
http://www.corporacionipsa.mx/

Barometric pressure:
Altitude:
Latitude:
Mean daily temperature range:
Starting & ending time for HVAC load calculations:
Number of unique rooms in this project:

24.303
5643
21
19
1am - 12am
1

in.Hg.
feet
Degrees
Degrees

Building Default Values


Calculations performed:
Lighting requirements:
Equipment requirements:
People sensible load multiplier:
People latent load multiplier:
Room sensible safety factor:
Room latent safety factor:
Room heating safety factor:
People diversity factor:
Lighting profile number:
Equipment profile number:
People profile number:
Building default ceiling height:
Building default wall height:

Cooling loads only


2.00
0.00
250
200
10
10
0
100
10
10
2
14.14
14.14

Watts per square foot


Watts per square foot
Btuh per person
Btuh per person
%
%
%
%

feet
feet

Internal Operating Load Profiles (C = 100)


1
2
3
4
5
6
7
8
9
10

hr
1
C
C
C
C
C
C
C
C
C
C

hr
2
C
C
C
C
C
C
C
C
C
C

hr
3
C
C
C
C
C
C
C
C
C
C

hr
4
C
C
C
C
C
C
C
C
C
C

hr
5
C
C
C
C
C
C
C
C
C
C

hr
6
C
C
C
C
C
C
C
C
C
C

hr
7
C
C
C
C
C
C
C
C
C
C

hr
8
C
C
C
C
C
C
C
C
C
C

hr
9
C
C
C
C
C
C
C
C
C
C

hr
10
C
C
C
C
C
C
C
C
C
C

hr
11
C
C
C
C
C
C
C
C
C
C

hr
12
C
C
C
C
C
C
C
C
C
C

hr
13
C
C
C
C
C
C
C
C
C
C

hr
14
C
C
C
C
C
C
C
C
C
C

hr
15
C
C
C
C
C
C
C
C
C
C

hr
16
C
C
C
C
C
C
C
C
C
C

hr
17
C
C
C
C
C
C
C
C
C
C

hr
18
C
C
C
C
C
C
C
C
C
C

hr
19
C
C
C
C
C
C
C
C
C
C

hr
20
C
C
C
C
C
C
C
C
C
C

hr
21
C
C
C
C
C
C
C
C
C
C

hr
22
C
C
C
C
C
C
C
C
C
C

hr
23
C
C
C
C
C
C
C
C
C
C

hr
24
C
C
C
C
C
C
C
C
C
C

Chvac - Full Commercial HVAC Loads Calculation Program


Pimaarc
Cuajimalpa de Morelos, DF 05410

Elite Software Development, Inc.


PEMEX REFINACION
Page 3

General Project Data Input (cont'd)


Building-Level Design Conditions
Design
Month

Outdoor
Dry Bulb

Outdoor
Wet Bulb

Indoor
Rel.Hum

Indoor
Dry Bulb

Grains
Diff

In/Outdoor
Correction

August
Winter

93
10

70

50%

75
75

17.67

Master Roofs
Roof
No.
1

ASHRAE
Roof#

Roof
U-Fac

Dark
Color

Susp.
Ceil

0.641

No

No

ASHRAE
Group

Wall
U-Fac

Wall
Color

0.543

Master Walls
Wall
No.
1

Chvac - Full Commercial HVAC Loads Calculation Program


Pimaarc
Cuajimalpa de Morelos, DF 05410

Elite Software Development, Inc.


PEMEX REFINACION
Page 4

Air Handler Input


Air Handler Number 1 Input Data
Name:
Terminal type:
Method for CV
Supply fan type:
Calculations performed:
Excess supply air:
Occurrences:
People profile number:
Lighting profile number:
Equipment profile number:
Exhaust may not exceed supply air:
Leaving heating coil CFM:
Leaving cooling coil temp (deg.F):
Cooling coil CFM
Misc. Btuh gain - supply side:
Misc. Btuh gain - return side:
Combined fan & motor efficiency:
Static pressure across fan (in.wg.):
Summer supply duct temp rise (deg.F):
Summer return duct temp rise (deg.F):
Winter supply duct temp drop (deg.F):
Winter return duct temp drop (deg.F):
Chilled water temp difference (deg.F):
Hot water temp difference (deg.F):
Cooling ventilation:
Cooling infiltration:
Heating ventilation:
Heating infiltration:
Pretreated outside air:
Pretreated air Summer DB (deg.F):
Pretreated air Summer WB (deg.F):
Pretreated air Winter DB (deg.F):

Uma 101/101r
Constant Volume
Sum of Peaks
Draw-thru fan
Cooling loads only
Reheat
1
0
0
0
No
0.0
55.0
0
0
0
85
2.00
1.000
0.750
2.000
1.000
0.000
0.000
551 Direct
0 Direct
0 AC/Hr
0 AC/Hr
none
0
0
0

Design
Month

Outdoor
Dry Bulb

Outdoor
Wet Bulb

Indoor
Rel.Hum

Indoor
Dry Bulb

Grains
Diff

In/Outdoor
Correction

August
Winter

93
10

70

50%

75
75

17.67

Chvac - Full Commercial HVAC Loads Calculation Program


Pimaarc
Cuajimalpa de Morelos, DF 05410

Elite Software Development, Inc.


PEMEX REFINACION
Page 5

Room Input
Room 1: Cuarto De Tableros Electricos (1170.534 sq.ft) (Zone 1)
Air Handler number:
Room length: (feet)
Lighting Watts:
Number of people in room:
Lighting profile number:
Ceiling height (feet):
Sensible safety factor (%):
Sensible heat per person (Btuh):
Cooling ventilation method:
Cooling infiltration method:
Heating ventilation method:
Heating infiltration method:
Winter exhaust air CFM:
Minimum supply CFM:
Ceil. exposed to plenum (sq.ft):
Cooling loads only are calculated for this room.
Roof
1
Wall
1
2
3
4

1
45.44
1,152
2
10
14.14
10
250
Direct
Direct
AC/Hr
Direct
0
0
1

Room occurrences:
Room width (feet):
Equipment Watts:
People profile number:
Equipment profile number:
Heating safety factor (%):
Latent safety factor (%):
Latent heat per person (Btuh):
Cooling ventilation value:
Cooling infiltration value:
Heating ventilation value:
Heating infiltration value:
Summer exhaust air CFM:
Latent Btuh equipment load:
Exposed floor slab perimeter (ft):

1
25.76
16,764
2
10
0
10
475
551.000
35.000
0.000
35.000
0
667
0

Type

ASHRAE#

U-Factor

Dark

Length

Width

Area

Susp.Ceil

0.641

No

1.00

1,177.10

1,177.1

No

Type

ASHRAE#

U-Factor

Color

Height

Width

Area

Direction

1
1
1
1

E
E
E
E

0.543
0.543
0.543
0.543

M
M
M
M

13.18
13.18
14.14
14.14

45.44
45.44
25.76
25.76

598.9
598.9
364.2
364.2

N
S
E
W

Chvac - Full Commercial HVAC Loads Calculation Program


Pimaarc
Cuajimalpa de Morelos, DF 05410

Elite Software Development, Inc.


PEMEX REFINACION
Page 6

Building Envelope Report


Envelope Report Using Summer U-Factors
Material
Types

Gross
Area

Glass
Area

Net
Area

-UFactor

Area x
U-Factor

Average
U-Factor

Roof
Tot.Roof

1,177.1
1,177.1

0.0
0.0

1,177.1
1,177.1

0.641
N/A

754.521
754.521

0.641
0.641

Wall
Tot.Wall

1,926.3
1,926.3

0.0
0.0

1,926.3
1,926.3

0.543
N/A

1,045.976
1,045.976

0.543
0.543

1,800.497

0.580

Totals

3,103.4

Wall
Direction

Wall
Area

Glass
Area

Wall Net
Area

Wall Avg
U-Factor

Glass Avg
U-Factor

Glass Avg
Shd.Coef

N
NE
E
SE
S
SW
W
NW

598.9
0.0
364.2
0.0
598.9
0.0
364.2
0.0

0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

598.9
0.0
364.2
0.0
598.9
0.0
364.2
0.0

0.543
0.000
0.543
0.000
0.543
0.000
0.543
0.000

0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000

0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000

1,926.3

0.0

1,926.3

0.543

0.000

0.000

Totals

Chvac - Full Commercial HVAC Loads Calculation Program


Pimaarc
Cuajimalpa de Morelos, DF 05410

Elite Software Development, Inc.


PEMEX REFINACION
Page 7

Building Summary Loads


Building peaks in August at 5pm.

Bldg Load
Descriptions

Area
Quan

Sen
Loss

%Tot
Loss

Lat
Gain

Sen
Gain

Net
Gain

%Net
Gain

Roof
Wall
Glass
Floor Slab

1,177
1,926
0
0

0
0
0
0

0.00
0.00
0.00
0.00

0
0
0
0

27,140
28,084
0
0

27,140
28,084
0
0

10.84
11.22
0.00
0.00

0.00

55,224

55,224

22.06

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00

0
1,467
0
1,045
0
0
0
6,851
0
441
0
0
0
0
0
0
0
0
0

4,324
142,882
0
550
0
0
0
7,877
0
561
0
9,667
0
0
0
11,318
8,120
0
0

4,324
144,349
0
1,595
0
0
0
14,728
0
1,002
0
9,667
0
0
0
11,318
8,120
0
0

1.73
57.66
0.00
0.64
0.00
0.00
0.00
5.88
0.00
0.40
0.00
3.86
0.00
0.00
0.00
4.52
3.24
0.00
0.00

0.00

9,804

240,522

250,326

100.00

Skin Loads
Lighting
Equipment
Pool Latent
People
Partition
Cool. Pret.
Heat. Pret.
Cool. Vent.
Heat. Vent.
Cool. Infil.
Heat. Infil.
Draw-Thru Fan
Blow-Thru Fan
Reserve Cap.
Reheat Cap.
Supply Duct
Return Duct
Misc. Supply
Misc. Return

1,152
16,764
0
2
0
0
0
551
0
35
0
0
0
0
0
0
0
0
0

Building Totals

Building
Summary

Sen
Loss

%Tot
Loss

Lat
Gain

Sen
Gain

Net
Gain

%Net
Gain

Ventilation
Infiltration
Pretreated Air
Room Loads
Plenum Loads
Fan/Duct/Misc Loads

0
0
0
0
0
0

0.00
0.00
0.00
0.00
0.00
0.00

6,851
441
0
2,512
0
0

7,877
561
0
202,979
0
29,105

14,728
1,002
0
205,492
0
29,105

5.88
0.40
0.00
82.09
0.00
11.63

Building Totals

0.00

9,804

240,522

250,326

100.00

Check Figures
Total Building Supply Air (based on a 20 TD):
Total Building Vent. Air (4.35% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling Required With Outside Air:

12,668 CFM
551 CFM
1,171
10.8223
56.1
0.0178
0.00

Sq.ft
CFM/Sq.ft
Sq.ft/Ton
Tons/Sq.ft
Btuh/Sq.ft

0 Btuh
20.86 Tons

Chvac - Full Commercial HVAC Loads Calculation Program


Pimaarc
Cuajimalpa de Morelos, DF 05410

Elite Software Development, Inc.


PEMEX REFINACION
Page 8

Air Handler #1 - Uma 101/101r - Summary Loads


Rm
No

Description
Room Peak Time

Cuarto De Tableros
Electricos
6pm August
Room Peak Totals:
Total Rooms: 1
Unique Rooms: 1

Area
People
Volume

Htg.Loss
Htg.CFM
CFM/Sqft

Sen.Gain
Clg.CFM
CFM/Sqft

Lat.Gain
S.Exh
W.Exh

Htg.O.A.
Req.CFM
Act.CFM

Clg.O.A.
Req.CFM
Act.CFM

1,171
2
16,551

0
0
0.00

205,382
12,668
10.82

2,899
0
0

None
0
0

Direct
551
551

1,171
2
16,551

0
0
0.00

205,382
12,668
10.82

2,899
0
0

0
0

551
551

Chvac - Full Commercial HVAC Loads Calculation Program


Pimaarc
Cuajimalpa de Morelos, DF 05410

Elite Software Development, Inc.


PEMEX REFINACION
Page 9

Air Handler #1 - Uma 101/101r - Total Load Summary


Air Handler Description:
Supply Air Fan:
Fan Input:
Sensible Heat Ratio:

Uma 101/101r Constant Volume - Sum of Peaks


Draw-Thru with program estimated horsepower of 4.69 HP
85% motor and fan efficiency with 2 in. water across the fan
0.99
--- This system occurs 1 time(s) in the building. ---

Air System Peak Time:


Outdoor Conditions:
Indoor Conditions:

5pm in August.
Clg: 91 DB, 70 WB, 100.61 grains
Clg: 75 DB, 50% RH

Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Room Space sensible loss:
Infiltration sensible loss:
Outside Air sensible loss:
Supply Duct sensible loss:
Return Duct sensible loss:
Return Plenum sensible loss:
Total System sensible loss:

0
0
0
0
0
0

Btuh
Btuh
Btuh
Btuh
Btuh
Btuh

0 CFM
0 CFM

0 Btuh

Heating Supply Air: 0 / (.812 X 1.08 X 0) =


Winter Vent Outside Air (0.0% of supply) =

0 CFM
0 CFM

Room space sensible gain:


202,979
Infiltration sensible gain:
561
Draw-thru fan sensible gain:
9,667
Supply duct sensible gain:
11,318
Reheat sensible gain:
0
Total sensible gain on supply side of coil:

Btuh
Btuh
Btuh
Btuh
Btuh

Cooling Supply Air: 226,367 / (.812 X 1.1 X 20) =


Summer Vent Outside Air (4.3% of supply) =
Return duct sensible gain:
8,120 Btuh
Return plenum sensible gain:
0 Btuh
Outside air sensible gain:
7,877 Btuh
Blow-thru fan sensible gain:
0 Btuh
Total sensible gain on return side of coil:
Total sensible gain on air handling system:
Room space latent gain:
Infiltration latent gain:
Outside air latent gain:
Total latent gain on air handling system:
Total system sensible and latent gain:

224,526 Btuh
12,668 CFM
551 CFM

551 CFM
15,996 Btuh
240,522 Btuh

2,512 Btuh
441 Btuh
6,851 Btuh
9,804 Btuh
250,326 Btuh

Check Figures
Total Air Handler Supply Air (based on a 20 TD):
Total Air Handler Vent. Air (4.35% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling Required With Outside Air:

12,668 CFM
551 CFM
1,171
10.8223
56.1
0.0178
0.00

Sq.ft
CFM/Sq.ft
Sq.ft/Ton
Tons/Sq.ft
Btuh/Sq.ft

0 Btuh
20.86 Tons

Chvac - Full Commercial HVAC Loads Calculation Program


Pimaarc
Cuajimalpa de Morelos, DF 05410

Elite Software Development, Inc.


PEMEX REFINACION
Page 10

Zone Detailed Loads (At Zone Peak Times)


Load
Unit
-SCCLTD
U.Fac
Sen.
Lat.
Htg.
Htg.
Description
Quan
CFAC
SHGF
-CLFGain
Gain
Mult.
Loss
Room 1-Cuarto De Tableros Electricos - Air Handler 1 (Uma 101/101r), Zone 1 peaks (sensible) in August at 6pm.
Roof-1-6-No.Clg-L
Wall-1-N-E-M
Wall-2-S-E-M
Wall-3-E-E-M
Wall-4-W-E-M
Lights-Prof=10
Equipment-Prof=10
People-Prof=2
Cool. Infil.Direct CFM
Heat. Infil.Direct CFM
Sub-total
Safety factors:
Total w/ safety factors:

1,177
599
599
364
364
1,152
16,764
2.0
35
0

0.50
0.83
0.83
0.83
0.83
1.000
1.000
1.000

33.7
17.0
25.7
27.4
36.6

0.641
0.543
0.543
0.543
0.543

25,427
5,513
8,347
5,425
7,231
3,931
129,893
500
444
186,711
+10%
--------205,382

41.665
35.295
35.295
35.295
35.295

49,044
21,138
21,138
12,856
12,856

0.000

1,334
950
351
2,635
+10%
--------2,899

0
+0%
--------0

Chvac - Full Commercial HVAC Loads Calculation Program


Pimaarc
Cuajimalpa de Morelos, DF 05410

Elite Software Development, Inc.


PEMEX REFINACION
Page 11

Room Detailed Loads (At Room Peak Times)


Load
Unit
-SCCLTD
U.Fac
Sen.
Lat.
Htg.
Htg.
Description
Quan
CFAC
SHGF
-CLFGain
Gain
Mult.
Loss
Room 1-Cuarto De Tableros Electricos peaks (sensible) in August at 6pm, Air Handler 1 (Uma 101/101r), Zone 1,
45.4 x 25.8, Construction Type: 24 (Heavy)
Roof-1-6-No.Clg-L
Wall-1-N-E-M
Wall-2-S-E-M
Wall-3-E-E-M
Wall-4-W-E-M
Lights-Prof=10
Equipment-Prof=10
People-Prof=2
Cool. Infil.Direct CFM
Heat. Infil.Direct CFM

1,177
599
599
364
364
1,152
16,764
2.0
35
0

0.50
0.83
0.83
0.83
0.83
1.000
1.000
1.000

33.7
17.0
25.7
27.4
36.6

0.641
0.543
0.543
0.543
0.543

Sub-total
Safety factors:

25,427
5,513
8,347
5,425
7,231
3,931
129,893
500
444

49,044
21,138
21,138
12,856
12,856

0.000

1,334
950
351

186,711
+10%
--------205,382

Total w/ safety factors:

41.665
35.295
35.295
35.295
35.295

2,635
+10%
--------2,899

0
+0%
--------0

Equipment Cooling Loads


Item
Name

Nominal
Output
Sensible

Quantity
Type
Sensible

Nominal
Output
Latent

Quantity
Type
Latent

Sensible
Load
(Btuh)

Latent
Load
(Btuh)

18
16,764

watts/sq.ft.
watts

667
195

Btuh
watts

72,691
57,201

667
667

129,893

1,334

EQUPO INTERIOR TABLEROS


Miscellaneous Equipment
Total

Lighting Cooling Loads


Item
Name
Compact Fluorescent,
Twin, (2) 40 W lamp,
Mag-Std ballast
Total

Quantity

Quantity
Type

Special
Allowance
Factor

12

watts

Space
Fraction

Occurrences

Usage
Factor

Load
(Btuh)

12

3,931

3,931

Chvac - Full Commercial HVAC Loads Calculation Program


Pimaarc
Cuajimalpa de Morelos, DF 05410

Elite Software Development, Inc.


PEMEX REFINACION
Page 12

Air System #1 (Uma 101/101r) Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Room Loads
Reheat

Grains

Sensible

Temp

CFM

9,667
0
11,318
205,382
0

55.000
0.854
0.000
1.000
18.146
0.000

541
0
633
11,494
0

226,367
8,120
0
0
7,877
0

75.000
0.750
0.000
0.000
0.663
0.000

12,668

242,363

76.413

12,668

79.391

Room Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 551 CFM
Blow-Thru Fan
Entering Coil Condition

0.000

2,953

0.422

2,953

79.813

0
6,851

0.000
0.981

9,804

80.794

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH
TSH
TLH

= (Barometric pressure of site / Standard ASHRAE pressure of 29.921)


=
PR x 1.10 x CFM x (DB entering - DB leaving)
=
PR x 0.68 x CFM x (Grains entering - Grains leaving)
=
PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)
=
=

0.812
0.812

x
x

1.10
0.68

x
x

12,668
12,668

x(
x(

76.4
80.8

55.0
79.4

)=
)=

SUM
=
GTH
=
0.812
Total System Load

4.50

12,668

x(

31.0

25.5

)=
=

242,363
9,818
---------252,180
253,113
250,326

Btuh
Btuh
Btuh
Btuh
Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM
Heating GPM
Steam Req.

=
=
=

253,113 / (
0 /(
0/

0.00 x
0.00 x
0

500
500

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

=
=
=

0.0 GPM
0.0 GPM
0.0 lb./hr

Entering Heating Coil Conditions


76.41
62.26
48.25
30.98 Btu/lbm

Dry bulb temperature:

55.00
54.98
99.87
25.51 Btu/lbm

Dry bulb temperature:

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

75.00

Leaving Heating Coil Conditions


75.00

Chvac - Full Commercial HVAC Loads Calculation Program


Pimaarc
Cuajimalpa de Morelos, DF 05410

Elite Software Development, Inc.


PEMEX REFINACION
Page 13

Air System #1 (Uma 101/101r) Psychrometric Chart


RC
LC
SD
DTF
RE
SM
PRE
MIX

Room Condition
Leaving Coil Condition
Supply Duct Temperature Rise
Draw Through Fan Sensible Gain
Reserve or Reheat Sensible Gain
Supply Side Miscellaneous Sensible Gain
Pretreated Air Condition
Mixed Air Condition

OC
EC
RD
BTF
PL
MR
HRV
RML

Outdoor Condition
Entering Coil Condition
Return Duct Temperature Rise
Blow Through Fan Sensible Gain
Return Air Plenum Sensible Gain
Return Side Miscellaneous Gain
Heat Recovery Ventilator Condition
Return Miscellaneous Latent Gain

Chvac - Full Commercial HVAC Loads Calculation Program


Pimaarc
Cuajimalpa de Morelos, DF 05410

Elite Software Development, Inc.


PEMEX REFINACION
Page 14

Building Pie Charts


Building peaks in August at 5pm.

Roof - 10.84%

Return Duct - 3.24%


Supply Duct - 4.52%
Draw-Thru Fan - 3.86%
Cool. Infil. - 0.40%
Cool. Vent. - 5.88%

Wall - 11.22%

People - 0.64%

Building
Net Gain
250,326
Btuh

Lighting - 1.73%

Equipment - 57.66%

Chvac - Full Commercial HVAC Loads Calculation Program


Pimaarc
Cuajimalpa de Morelos, DF 05410

Elite Software Development, Inc.


PEMEX REFINACION
Page 15

Room #1 - Cuarto De Tableros Electricos - Pie Charts


Room #1 peaks in August at 6pm

Roof - 13.43%

Cool. Infil. - 0.42%


People - 0.77%

Wall - 14.00%
Room #1
Net Gain
208,280
Btuh

Lighting - 2.08%

Equipment - 69.31%