You are on page 1of 1094

MiCOM P437

Distance Protection Device


P437/EN M/R-11-A
Version

P437 -311 -412/413 -650

Technical Manual

General Note on the PDF Version of this Technical Manual


All entries in the Table of Contents and all cross-references to other sections,
figures etc. in green letters are hyperlinks, i.e. by a single mouse click on the
reference one can navigate directly to the referenced part of the manual.
In the Adobe Reader (or the Acrobat Pro), one can return back to the previous
view by using the menu point View / Page Navigation / Previous View (keyboard
shortcut: ALT + Left cursor key). (It might be necessary to do this several times,
if the view at the target location has also been changed (e.g. by scrolling or
changing the zoom setting).

WARNING
When electrical equipment is in operation dangerous voltage will be present
in certain parts of the equipment. Failure to observe warning notices,
incorrect use or improper use may endanger personnel and equipment and
cause personal injury or physical damage.
Before working in the terminal strip area, the P437 must be isolated. Where
stranded conductors are used, insulated crimped wire end ferrules must be
employed.
The signals MAI N: Bl ocked/faulty and SFMON: War ning (LED)
(permanently assigned to the LEDs labeled OUT OF SERVICE and ALARM) can
be assigned to output relays to indicate the health of the P437. Schneider
Electric strongly recommends that these output relays are hardwired into the
substation's automation system, for alarm purposes.
Any modifications to this P437 must be in accordance with the manual. If any
other modification is made without the express permission of Schneider
Electric, it will invalidate the warranty, and may render the product unsafe.
Proper and safe operation of this P437 depends on appropriate shipping and
handling, proper storage, installation and commissioning, and on careful
operation, maintenance and servicing.
For this reason only qualified personnel may work on or operate this P437.
The User should be familiar with the warnings in the Safety Guide
(SFTY/4LM/G11 or later version), with the warnings in Chapter 5, (p. 5-1),
Chapter 10, (p. 10-1), Chapter 11, (p. 11-1) and Chapter 12, (p. 121) and with the content of Chapter 14, (p. 14-1), before working on the
equipment. If the warnings are disregarded, it will invalidate the warranty,
and may render the product unsafe.

Qualified Personnel
are individuals who

are familiar with the installation, commissioning and operation of the P437
and of the system to which it is being connected;

are able to perform switching operations in accordance with safety


engineering standards and are authorized to energize and de-energize
equipment and to isolate, ground and label it;

are trained in the care and use of safety apparatus in accordance with
safety engineering standards;

are trained in emergency procedures (first aid).

Note
This operating manual gives instructions for installation, commissioning and
operation of the P437. However, the manual cannot cover all conceivable
circumstances or include detailed information on all topics. In the event of
questions or specific problems, do not take any action without proper
authorization. Contact the appropriate technical sales office of Schneider Electric
and request the necessary information.
Any agreements, commitments, and legal relationships and any obligations on
the part of Schneider Electric, including settlement of warranties, result solely

from the applicable purchase contract, which is not affected by the contents of
the operating manual.

Changes after going to press

P437
Table of Contents
1

Application and Scope ........................................................................................ 1-1


1.1

Overview .....................................................................................................................1-1

1.2

General Functions ....................................................................................................... 1-5

1.3

Global Functions ......................................................................................................... 1-6

1.4

Design .........................................................................................................................1-7

1.5

Configurable Function Keys ........................................................................................ 1-8

1.6

Inputs and Outputs ..................................................................................................... 1-9

1.7

Control and Display ...................................................................................................1-10

1.8

Information Interfaces ...............................................................................................1-11

Technical Data .................................................................................................... 2-1


2.1

Conformity .................................................................................................................. 2-1

2.2

General Data ...............................................................................................................2-2

2.2.1

General Device Data ..................................................................................................................................... 2-2

2.2.2

Environmental Conditions ..............................................................................................................................2-3

2.3

Tests ........................................................................................................................... 2-4

2.3.1

Type Tests ..................................................................................................................................................... 2-4

2.3.2

Routine Tests .................................................................................................................................................2-7

2.4

Inputs and Outputs ..................................................................................................... 2-9

2.4.1

Measuring Inputs ........................................................................................................................................... 2-9

2.4.2

Binary Signal Inputs .....................................................................................................................................2-10

2.4.3

IRIGB Interface ........................................................................................................................................... 2-11

2.4.4

Direct Current Input .....................................................................................................................................2-11

2.4.5

Resistance Thermometer ............................................................................................................................ 2-11

2.4.6

Direct Current Output ..................................................................................................................................2-11

2.4.7

Output Relays ..............................................................................................................................................2-12

2.4.8

BCD Measured Data Output ........................................................................................................................ 2-12

2.5

Interfaces .................................................................................................................. 2-13

2.5.1

Local Control Panel ......................................................................................................................................2-13

2.5.2

PC Interface ................................................................................................................................................. 2-13

2.5.3

Serial Communication Interface .................................................................................................................. 2-13

2.5.4

IEC Communication Interface ...................................................................................................................... 2-14

2.5.5

IRIGB Interface ........................................................................................................................................... 2-15

2.6

Information Output ................................................................................................... 2-16

2.7

Settings Typical Characteristic Data .......................................................................2-17

2.7.1

Main Function .............................................................................................................................................. 2-17

2.7.2

Distance Protection ..................................................................................................................................... 2-17

2.7.3

Definite-Time and Inverse-Time Overcurrent Protection ............................................................................. 2-17

2.7.4

Time-Voltage Protection .............................................................................................................................. 2-17

2.7.5

Power Directional Protection ....................................................................................................................... 2-17

2.8

Deviations ................................................................................................................. 2-18

2.8.1

Deviations of the Operate Values ................................................................................................................ 2-18

2.8.2

Deviations of the Timer Stages ................................................................................................................... 2-19

2.8.3

Deviations of Measured Data Acquisition .................................................................................................... 2-20

2.9

Resolution of the Fault Data Acquisition ................................................................... 2-21

2.9.1

Time Resolution ...........................................................................................................................................2-21

2.9.2

Phase Currents System ............................................................................................................................... 2-21

2.9.3

Residual Current ..........................................................................................................................................2-21

2.9.4

Phase-to-Ground Voltages and Neutral-Point Displacement Voltage ...........................................................2-21

P437/EN M/R-11-A // P437311650

P437

Table of Contents

2.10

Recording Functions ................................................................................................. 2-22

2.10.1

Organization of the Recording Memories .................................................................................................... 2-22

2.11

Power Supply ............................................................................................................ 2-24

2.12

Current Transformer Specifications .......................................................................... 2-25

2.12.1

Symbols .......................................................................................................................................................2-25

2.12.2

General Equations ....................................................................................................................................... 2-27

2.12.3

Distance Protection ..................................................................................................................................... 2-27

Operation ............................................................................................................3-1
3.1

Modular Structure ....................................................................................................... 3-1

3.2

Operator-Machine Communication ............................................................................. 3-3

3.3

Configuration of the Bay Panel and of the Measured Value Panels, Selection of the
Control Point (Function Group LOC) ............................................................................ 3-4

3.3.1

Operation Panel .............................................................................................................................................3-5

3.3.2

Fault Panel .....................................................................................................................................................3-6

3.3.3

Overload Panel .............................................................................................................................................. 3-7

3.3.4

Configurable Clear Key .................................................................................................................................. 3-7

3.4

Serial Interfaces .......................................................................................................... 3-8

3.4.1

PC Interface (Function Group PC) .................................................................................................................. 3-9

3.4.2

Communication Interface 1 (Function Group COMM1) ................................................................................ 3-10

3.4.3

Communication Interface 2 (Function Group COMM2) ................................................................................ 3-19

3.4.4

InterMiCOM Protective Interfaces (Function Groups COMM3, COMM4) ........................................................3-21

3.4.5

Communication Interface IEC 61850 (Function Groups IEC, GOOSE and GSSE) .......................................... 3-26

3.5

IRIG-B Clock Synchronization (Function Group IRIGB) ...............................................3-38

3.6

Configurable Function Keys (Function Group F_KEY) ................................................ 3-39

3.6.1

Configuration of Function Keys with a Single Function ................................................................................ 3-39

3.6.2

Configuration of Function Keys with Menu Jump Lists ................................................................................. 3-39

3.6.3

Configuration of the READ Key .................................................................................................................... 3-39

3.6.4

Operating Mode of the Function Keys ..........................................................................................................3-39

3.6.5

Handling Keys ..............................................................................................................................................3-39

3.7

Configuration and Operating Mode of the Binary Inputs (Function Group INP) ......... 3-41

3.8

Measured Data Input (Function Group MEASI) .......................................................... 3-43

3.8.1

Direct Current Input on the Analog (I/O) Module Y ...................................................................................... 3-44

3.8.2

Connecting a Resistance Thermometer to the PT 100 Analog Input on the Analog (I/O) Module Y .......... 3-47

3.9

Configuration, Operating Mode, and Blocking of the Output Relays (Function Group
OUTP) ........................................................................................................................3-49

3.10

Measured Data Output (Function Group MEASO) ......................................................3-52

3.10.1

General Settings ..........................................................................................................................................3-52

3.10.2

BCD Measured Data Output ........................................................................................................................ 3-54

3.10.3

Analog Measured Data Output .................................................................................................................... 3-58

3.10.4

Output of External Measured Data ........................................................................................................... 3-64

3.11

Configuration and Operating Mode of the LED Indicators (Function Group LED) ...... 3-65

3.11.1

Configuring the LED Indicators .................................................................................................................... 3-65

3.11.2

Layout of the LED Indicators ........................................................................................................................3-65

3.11.3

Operating Mode of the LED Indicators ......................................................................................................... 3-66

3.12

Main Functions of the P437 (Function Group MAIN) .................................................. 3-69

3.12.1

Conditioning of the Measured Variables ...................................................................................................... 3-69

3.12.2

Operating Data Measurement ..................................................................................................................... 3-71

3.12.3

Configuring and Enabling the Device Functions .......................................................................................... 3-87

3.12.4

Current Flow Monitoring .............................................................................................................................. 3-88

3.12.5

Inrush Stabilization (Harmonic Restraint) .................................................................................................... 3-89

3.12.6

Multiple Blocking ......................................................................................................................................... 3-91

3.12.7

Blocked/Faulty ............................................................................................................................................. 3-92

P437/EN M/R-11-A // P437311650

Table of Contents

P437

3.12.8

Monitoring and Processing of CB Status Signals ..........................................................................................3-92

3.12.9

Close Command .......................................................................................................................................... 3-94

3.12.10

Starting Signals and Tripping Logic ............................................................................................................. 3-96

3.12.11

Time Tagging and Clock Synchronization .................................................................................................. 3-104

3.12.12

Resetting Actions .......................................................................................................................................3-106

3.12.13

Assigning Communications Interfaces to Physical Communications Channels .......................................... 3-109

3.12.14

Test Mode ..................................................................................................................................................3-110

3.13

Parameter Subset Selection (Function Group PSS) ................................................. 3-111

3.14

Self-Monitoring (Function Group SFMON) ................................................................3-113

3.14.1

Tests During Start-up ................................................................................................................................ 3-113

3.14.2

Cyclic Tests ................................................................................................................................................3-113

3.14.3

Signal ........................................................................................................................................................ 3-113

3.14.4

Device Response ....................................................................................................................................... 3-114

3.14.5

Monitoring Signal Memory .........................................................................................................................3-115

3.14.6

Monitoring Signal Memory Time Tag ......................................................................................................... 3-115

3.15

Operating Data Recording (Function Group OP_RC) ............................................... 3-116

3.16

Monitoring Signal Recording (Function Group MT_RC) ............................................ 3-117

3.17

Overload Data Acquisition (Function Group OL_DA) ............................................... 3-118

3.17.1

Overload Duration ..................................................................................................................................... 3-118

3.17.2

Acquiring Measured Overload Data from the Thermal Overload Protection .............................................. 3-119

3.18

Overload Recording (Function Group OL_RC) ..........................................................3-120

3.18.1

Start of Overload Recording ...................................................................................................................... 3-120

3.18.2

Counting Overload Events ......................................................................................................................... 3-120

3.18.3

Time Tagging .............................................................................................................................................3-120

3.18.4

Overload Logging ...................................................................................................................................... 3-121

3.19

Fault Data Acquisition (Function Group FT_DA) ...................................................... 3-122

3.19.1

Running Time and Fault Duration .............................................................................................................. 3-122

3.19.2

Fault Data Acquisition Time .......................................................................................................................3-123

3.19.3

Selection of the Measuring Loop for Determining Fault Data .................................................................... 3-124

3.19.4

Acquisition of Short Circuit Data ................................................................................................................3-126

3.19.5

Acquisition of Fault Location ......................................................................................................................3-128

3.19.6

Fault Data Reset ........................................................................................................................................3-129

3.20

Fault Recording (Function Group FT_RC) ................................................................ 3-130

3.20.1

Start of Fault Recording .............................................................................................................................3-130

3.20.2

Fault Counting ........................................................................................................................................... 3-131

3.20.3

Time Tagging .............................................................................................................................................3-131

3.20.4

Fault Recordings ........................................................................................................................................3-132

3.20.5

Fault Value Recording ............................................................................................................................... 3-133

3.21

Distance Protection (Function Group DIST) ............................................................. 3-135

3.21.1

Fault Detection Logic .................................................................................................................................3-135

3.21.2

Selection of Measured Values ....................................................................................................................3-148

3.21.3

Distance and Directional Measurement .....................................................................................................3-153

3.21.4

Impedance-Time Characteristics ............................................................................................................... 3-172

3.21.5

Distance Protection Trip Signals ................................................................................................................ 3-176

3.21.6

Selection of Trip Mode for Zone 1 ..............................................................................................................3-181

3.22

Power Swing Blocking (Function Group PSB) .......................................................... 3-183

3.22.1

Measurement ............................................................................................................................................ 3-183

3.22.2

Power Swing Detection ..............................................................................................................................3-184

3.22.3

Load Blinding .............................................................................................................................................3-185

3.22.4

Behavior with a Short-Circuit Fault During a Power Swing Event .............................................................. 3-188

3.22.5

PSB Blocking ..............................................................................................................................................3-189

3.22.6

Out-of-Step Tripping .................................................................................................................................. 3-191

3.22.7

Enhanced Counting-Based Trip Logic ........................................................................................................ 3-191

P437/EN M/R-11-A // P437311650

P437

Table of Contents

3.23

Measuring-Circuit Monitoring (Function Group MCMON) ......................................... 3-197

3.23.1

Current Monitoring .................................................................................................................................... 3-197

3.23.2

Voltage Monitoring .................................................................................................................................... 3-198

3.23.3

Phase-Sequence Monitoring ...................................................................................................................... 3-200

3.23.4

Fuse Failure Monitoring of Phase-to-Ground Voltages ............................................................................... 3-201

3.23.5

Fuse Failure Monitoring of the Reference Voltage ..................................................................................3-205

3.24

Backup Overcurrent-Time Protection (Function Group BUOC) ................................ 3-206

3.25

Switch on to Fault Protection (Function Group SOTF) ............................................. 3-208

3.25.1

Decision Line dead ................................................................................................................................. 3-210

3.26

Protective Signaling (Function group PSIG) .............................................................3-212

3.26.1

Disabling and Enabling Protective Signaling ..............................................................................................3-212

3.26.2

Readiness of Protective Signaling ..............................................................................................................3-212

3.26.3

Three-Ended Line Application .................................................................................................................... 3-214

3.26.4

Monitoring the Transmission Section .........................................................................................................3-215

3.26.5

Frequency Monitoring ................................................................................................................................3-216

3.26.6

Transient Blocking ..................................................................................................................................... 3-216

3.26.7

Protective Signaling Operating Modes .......................................................................................................3-217

3.26.8

Measuring Zone Extension of Zone 1 of Distance Protection .................................................................... 3-232

3.26.9

Weak-Infeed Logic ..................................................................................................................................... 3-232

3.26.10

Echo Function ............................................................................................................................................ 3-236

3.26.11

Testing the Communication Channels ....................................................................................................... 3-238

3.27

Auto-Reclosing Control in the P437 (Function Group ARC) ..................................... 3-240

3.27.1

ARC Operating Modes ................................................................................................................................3-240

3.27.2

Enabling and Disabling the ARC Function ..................................................................................................3-241

3.27.3

ARC Blocked .............................................................................................................................................. 3-243

3.27.4

ARC Tripping Times ................................................................................................................................... 3-244

3.27.5

Starting the ARC Cycle .............................................................................................................................. 3-245

3.27.6

High-Speed Reclosure (HSR) ..................................................................................................................... 3-245

3.27.7

Time-Delay Reclosure (TDR) in the P437 ...................................................................................................3-257

3.27.8

Rapid Reclosure (RRC) ...............................................................................................................................3-259

3.27.9

Secondary Fault Treatment in the P437 .................................................................................................... 3-261

3.27.10

Parallel Blocking in the P437 ..................................................................................................................... 3-263

3.27.11

Zone Extension in the P437 .......................................................................................................................3-266

3.27.12

Control Using External Auto-Reclosing Control ..........................................................................................3-268

3.27.13

General ARC Control Functions in the P437 ...............................................................................................3-269

3.27.14

ARC Counters in the P437 ......................................................................................................................... 3-272

3.28

Automatic Synchronism Check (Function Group ASC) ............................................ 3-273

3.28.1

Disabling and Enabling the ASC Function .................................................................................................. 3-273

3.28.2

ASC Readiness and Blocking ..................................................................................................................... 3-275

3.28.3

Close Request ............................................................................................................................................3-276

3.28.4

ASC Operating Modes ................................................................................................................................3-278

3.28.5

Continuous Synchronism Check ................................................................................................................ 3-278

3.28.6

Extended Settings for the Close Enable Conditions ................................................................................... 3-279

3.28.7

Considering the CB Close Time ..................................................................................................................3-280

3.28.8

Voltage-Checked Close Enable .................................................................................................................. 3-281

3.28.9

Synchronism-Checked Close Enable ..........................................................................................................3-284

3.28.10

Voltage/Synchronism-Checked Close Enable .............................................................................................3-287

3.28.11

Testing the ASC Function .......................................................................................................................... 3-287

3.28.12

ASC Counters .............................................................................................................................................3-289

3.29

Ground fault (short-circuit) protection (Function Group GFSC) ............................... 3-290

3.29.1

Disabling or Enabling Ground Fault (Short-Circuit) Protection ................................................................... 3-290

3.29.2

Measured Values from the Ground Fault (Short-Circuit) Protection ........................................................... 3-291

3.29.3

Blocking ground fault (short-circuit) protection ......................................................................................... 3-292

3.29.4

Starting ......................................................................................................................................................3-293

3.29.5

Directional Tripping ................................................................................................................................... 3-294

P437/EN M/R-11-A // P437311650

Table of Contents

P437

3.29.6

Improved Directional Measurement for Series-Compensated Line Applications xyz ................................. 3-295

3.29.7

Improved Phase Selection ......................................................................................................................... 3-297

3.29.8

Voltage-Dependent or Current-Dependent Tripping ..................................................................................3-299

3.29.9

Non-Directional Tripping ............................................................................................................................3-306

3.29.10

Counters .................................................................................................................................................... 3-307

3.29.11

Monitoring the Measured Values ............................................................................................................... 3-308

3.30

Ground Fault (Short-Circuit) Protection Signaling (Function Group GSCSG) ............3-309

3.30.1

Disabling or Enabling Ground Fault (Short-Circuit) Protection Signaling ................................................... 3-309

3.30.2

Readiness of Ground Fault (Short-Circuit) Protection Signaling .................................................................3-310

3.30.3

Communication Link Faulty Signal .............................................................................................................3-313

3.30.4

Tripping Time ............................................................................................................................................ 3-314

3.30.5

Frequency Monitoring ................................................................................................................................3-314

3.30.6

Transient Blocking ..................................................................................................................................... 3-315

3.30.7

Operating Modes of Ground Fault (Short-Circuit) Protection Signaling and the Communication Channel . 3-315

3.30.8

Signal Comparison Release Scheme ..........................................................................................................3-316

3.30.9

Signal Comparison Blocking Scheme .........................................................................................................3-317

3.30.10

Weak-Infeed Logic ..................................................................................................................................... 3-318

3.30.11

Trip Mode .................................................................................................................................................. 3-319

3.30.12

Echo Function ............................................................................................................................................ 3-320

3.30.13

Testing the Communication Channel .........................................................................................................3-321

3.31

Definite-Time Overcurrent Protection (Function Group DTOC) ................................3-323

3.31.1

Enabling or Disabling DTOC Protection ......................................................................................................3-323

3.31.2

Monitoring the Maximum Phase Current ................................................................................................... 3-323

3.31.3

Negative-Sequence Current Stages ...........................................................................................................3-324

3.31.4

Residual Current Stages ............................................................................................................................ 3-326

3.31.5

Hold-Time Logic for Intermittent Ground Faults ........................................................................................ 3-335

3.32

Inverse-Time Overcurrent Protection (Function Group IDMT) ................................. 3-338

3.32.1

Disabling and Enabling IDMT Protection .................................................................................................... 3-338

3.32.2

Time-Dependent Characteristics ............................................................................................................... 3-339

3.32.3

Enable Thresholds ..................................................................................................................................... 3-343

3.32.4

Phase Current Stage ..................................................................................................................................3-344

3.32.5

Negative-Sequence Current Stage ............................................................................................................ 3-346

3.32.6

Selecting the Measured Variable for the Residual Current Stage .............................................................. 3-348

3.32.7

Residual Current Stage ..............................................................................................................................3-348

3.32.8

Holding Time ............................................................................................................................................. 3-349

3.33

Thermal Overload Protection (Function Group THERM) .......................................... 3-351

3.33.1

Readiness of Thermal Overload Protection ................................................................................................3-351

3.33.2

Operating Modes ....................................................................................................................................... 3-351

3.33.3

Coolant Temperature Effect ...................................................................................................................... 3-352

3.33.4

Thermal Overload Protection Operation without Coolant Temperature (Ambient) Acquisition ..................3-353

3.33.5

Relative Replica .........................................................................................................................................3-353

3.33.6

Absolute Replica ........................................................................................................................................3-354

3.33.7

Tripping Characteristics .............................................................................................................................3-355

3.33.8

Warning Signal .......................................................................................................................................... 3-356

3.33.9

Trip ............................................................................................................................................................ 3-356

3.33.10

Cooling ...................................................................................................................................................... 3-356

3.33.11

Resetting ................................................................................................................................................... 3-357

3.34

Under and Overvoltage Protection (Function Group V<>) ......................................3-359

3.34.1

Disabling and Enabling V<> Protection .....................................................................................................3-359

3.34.2

V<> Protection Readiness .........................................................................................................................3-359

3.34.3

Minimum Current Monitoring .....................................................................................................................3-360

3.34.4

Monitoring the Phase Voltages .................................................................................................................. 3-361

3.34.5

Monitoring the Positive- and Negative-Sequence Voltages ....................................................................... 3-366

3.34.6

Monitoring the Neutral-Point Displacement Voltage ..................................................................................3-370

3.34.7

Monitoring the Reference Voltage ............................................................................................................. 3-370

P437/EN M/R-11-A // P437311650

P437
3.35

Table of Contents

Over-/Underfrequency Protection (Function Group f<>) ........................................ 3-373

3.35.1

Disabling or Enabling Over/Underfrequency Protection ............................................................................3-373

3.35.2

Selecting the Measuring Voltage ............................................................................................................... 3-374

3.35.3

Undervoltage Blocking and Evaluation Time ............................................................................................. 3-375

3.35.4

Operating Modes of Over-/Underfrequency Protection .............................................................................. 3-375

3.35.5

Frequency Monitoring ................................................................................................................................3-375

3.35.6

Frequency Monitoring Combined with Differential Frequency Gradient Monitoring (df/dt) ........................3-376

3.35.7

Frequency Monitoring Combined with Mean Frequency Gradient Monitoring (f/t) ................................ 3-376

3.35.8

fmin-/fmax Measurement ............................................................................................................................. 3-379

3.36

Directional Power Protection (Function Group P<>) ............................................... 3-380

3.36.1

Disabling and Enabling P<> Protection .....................................................................................................3-380

3.36.2

Power Determination .................................................................................................................................3-380

3.36.3

Power Monitoring .......................................................................................................................................3-381

3.36.4

Active Power Monitoring when Set Thresholds are Exceeded ................................................................... 3-382

3.36.5

Active Power Direction when Set Thresholds are Exceeded ...................................................................... 3-383

3.36.6

Reactive Power Monitoring when Set Thresholds are Exceeded ................................................................3-384

3.36.7

Reactive Power Direction when Set Thresholds are Exceeded .................................................................. 3-385

3.36.8

Active Power Monitoring when Values Fall Below Set Thresholds ..............................................................3-386

3.36.9

Active Power Direction when Values Fall Below Set Thresholds ................................................................ 3-388

3.36.10

Reactive Power Monitoring when Values Fall Below Set Thresholds ..........................................................3-391

3.36.11

Reactive Power Direction when Values Fall Below Set Thresholds ............................................................ 3-392

3.36.12

Starting Signal with Direction .................................................................................................................... 3-395

3.37

Circuit Breaker Failure Protection (Function Group CBF) ........................................ 3-396

3.37.1

Disabling and Enabling Circuit Breaker Failure Protection .........................................................................3-396

3.37.2

Readiness of Circuit Breaker Protection .................................................................................................... 3-397

3.37.3

Detecting a CB Tripping .............................................................................................................................3-397

3.37.4

Current Flow Monitoring ............................................................................................................................ 3-398

3.37.5

Evaluation of CB Status Signals .................................................................................................................3-399

3.37.6

Startup Criteria ..........................................................................................................................................3-400

3.37.7

Timer Stages and Output Logic ................................................................................................................. 3-400

3.37.8

Trip Commands ......................................................................................................................................... 3-402

3.37.9

Starting Trigger ......................................................................................................................................... 3-404

3.37.10

Fault Behind CB Protection ........................................................................................................................ 3-404

3.37.11

CB Synchronization Supervision ................................................................................................................ 3-405

3.38

Circuit Breaker Monitoring (Function Group CBM) .................................................. 3-406

3.38.1

Disabling and Enabling Circuit Breaker Monitoring ....................................................................................3-406

3.38.2

Variants ..................................................................................................................................................... 3-406

3.38.3

CB Wear Characteristic ..............................................................................................................................3-407

3.38.4

Calculating the CB Wear State .................................................................................................................. 3-408

3.38.5

Operating Modes ....................................................................................................................................... 3-408

3.38.6

Cycle for Circuit Breaker Monitoring ..........................................................................................................3-408

3.38.7

Pole-Selective Counter Values and Measured Values ................................................................................ 3-410

3.38.8

Resetting Measured Values ....................................................................................................................... 3-411

3.38.9

Setting Measured Values ........................................................................................................................... 3-411

3.38.10

Monitoring the Number of CB Operations ..................................................................................................3-413

3.38.11

Monitoring Ruptured Currents ................................................................................................................... 3-413

3.38.12

Blocking Circuit Breaker Monitoring .......................................................................................................... 3-414

3.39

Limit Value Monitoring (Function Group LIMIT) ....................................................... 3-415

3.39.1

Enable/Disable the Limit Value Monitoring Function ................................................................................. 3-415

3.39.2

Monitoring Phase Currents and Phase Voltages ........................................................................................ 3-415

3.39.3

Monitoring the Neutral-Point Displacement Voltage ..................................................................................3-418

3.39.4

Monitoring the Linearized Measured DC Values ........................................................................................ 3-419

3.39.5

Monitoring the Reference Voltage ............................................................................................................. 3-420

3.39.6

Monitoring the Measured PT 100 Temperature Value ............................................................................ 3-421

3.40

Programmable Logic (Function Groups LOGIC and LOG_2) ..................................... 3-422


P437/EN M/R-11-A // P437311650

Table of Contents

P437

3.41

Binary Counts (Function Group COUNT) ..................................................................3-430

3.41.1

Enable/Disable the Counting Function .......................................................................................................3-430

3.41.2

Debouncing ............................................................................................................................................... 3-430

3.41.3

Counting Function ..................................................................................................................................... 3-430

3.41.4

Transmitting the Counter Values via Communications Interface ...............................................................3-431

3.41.5

Counter Values Reset ................................................................................................................................ 3-431

Design .................................................................................................................4-1
4.1

Designs ....................................................................................................................... 4-2

4.2

Dimensional Drawings ................................................................................................ 4-4

4.2.1

Dimensional Drawings for the 84 TE Case .....................................................................................................4-4

4.3

Hardware Modules ...................................................................................................... 4-6

Installation and Connection ................................................................................ 5-1


5.1

Unpacking and Packing ...............................................................................................5-3

5.2

Checking Nominal Data and Design Type ................................................................... 5-4

5.3

Location Requirements ............................................................................................... 5-5

5.3.1

Environmental Conditions ..............................................................................................................................5-5

5.3.2

Mechanical Conditions ...................................................................................................................................5-5

5.3.3

Electrical Conditions for Auxiliary Voltage of the Power Supply .................................................................... 5-5

5.3.4

Electromagnetic Conditions ...........................................................................................................................5-5

5.4

Installation .................................................................................................................. 5-6

5.5

Protective and Operational Grounding ......................................................................5-12

5.6

Connection ................................................................................................................5-13

5.6.1

Connecting Measuring and Auxiliary Circuits .............................................................................................. 5-13

5.6.2

Connecting the IRIGB Interface .................................................................................................................. 5-15

5.6.3

Connecting the Serial Interfaces ................................................................................................................. 5-15

5.7

Location and Connection Diagrams .......................................................................... 5-19

5.7.1

Location Diagrams P437 412/413 ...............................................................................................................5-19

5.7.2

Terminal Connection Diagrams P437412/413 ............................................................................................ 5-19

Local Control (HMI) ............................................................................................. 6-1


6.1

Local Control Panel (HMI) ............................................................................................6-1

6.2

Display and Keypad .................................................................................................... 6-2

6.2.1

Text Display ...................................................................................................................................................6-2

6.2.2

Display Illumination ....................................................................................................................................... 6-2

6.2.3

Contrast of the Display .................................................................................................................................. 6-2

6.2.4

Short Description of Keys .............................................................................................................................. 6-3

6.3

Display Levels ............................................................................................................. 6-5

6.4

Display Panels .............................................................................................................6-6

6.5

Menu Tree and Data Points ......................................................................................... 6-7

6.6

List Data Points ........................................................................................................... 6-8

6.7

Note Concerning the Step-by-Step Descriptions ......................................................... 6-9

6.8

Configurable Function Keys ...................................................................................... 6-10

6.8.1

Configuration of the Function Keys F1 to Fx ................................................................................................ 6-11

6.9

Changing Between Display Levels ............................................................................ 6-14

6.10

Control at Panel Level ............................................................................................... 6-15

6.11

Control at the Menu Tree Level .................................................................................6-16

6.11.1

Navigation in the Menu Tree ....................................................................................................................... 6-16

6.11.2

Switching Between Address Mode and Plain Text Mode .............................................................................. 6-17

P437/EN M/R-11-A // P437311650

P437

10

6.11.3

Change-Enabling Function ...........................................................................................................................6-18

6.11.4

Changing Parameters .................................................................................................................................. 6-21

6.11.5

List Parameters ........................................................................................................................................... 6-22

6.11.6

Memory Readout ......................................................................................................................................... 6-25

6.11.7

Resetting ..................................................................................................................................................... 6-28

6.11.8

Password-Protected Control Actions ............................................................................................................ 6-29

6.11.9

Changing the Password ............................................................................................................................... 6-31

Settings ...............................................................................................................7-1
7.1

Paramete rs .............................................................................................................. 7-1

7.1.1

D e v i c e I d e n t i f i c a t i o n ............................................................................................................................. 7-3

7.1.2

C o n f i g u r a t i o n P a r a m e t e r s .................................................................................................................. 7-12

7.1.3

F u n c t i o n P a r a m e t e r s ............................................................................................................................ 7-88

Information and Control Functions ......................................................................8-1


8.1

Operat ion ................................................................................................................. 8-1

8.1.1

C y c l i c V a l u e s ............................................................................................................................................ 8-1

8.1.2

C o n t r o l a n d T e s t i n g ............................................................................................................................8-127

8.1.3

O p e r a t i n g D a t a R e c o r d i n g ................................................................................................................8-146

8.2

E vent s ................................................................................................................... 8-147

8.2.1

E v e n t C o u n t e r s .................................................................................................................................... 8-147

8.2.2

M e a s u r e d E v e n t D a t a .........................................................................................................................8-153

8.2.3

E v e n t R e c o r d i n g .................................................................................................................................. 8-160

IEC 61850 Settings via IED Configurator .............................................................9-1


9.1

Manage IED .................................................................................................................9-2

9.2

IED Details .................................................................................................................. 9-3

9.3

Communications ......................................................................................................... 9-4

9.4

SNTP ........................................................................................................................... 9-5

9.4.1

General Config ...............................................................................................................................................9-5

9.4.2

External Server 1 ...........................................................................................................................................9-5

9.4.3

External Server 2 ...........................................................................................................................................9-5

9.5

Dataset Definitions ..................................................................................................... 9-6

9.6

GOOSE Publishing ....................................................................................................... 9-7

9.6.1

System/LLN0 ................................................................................................................................................. 9-7

9.7

GOOSE Subscribing .....................................................................................................9-9

9.7.1

Mapped Inputs ...............................................................................................................................................9-9

9.8

Report Control Blocks ............................................................................................... 9-12

9.8.1

System/LLN0 ............................................................................................................................................... 9-12

9.9

Controls .....................................................................................................................9-13

9.9.1

Control Objects ............................................................................................................................................9-13

9.9.2

Uniqueness of Control ................................................................................................................................. 9-13

9.10

Measurements .......................................................................................................... 9-15

9.11

Configurable Data Attributes .................................................................................... 9-16

9.11.1

System/LLN0 ............................................................................................................................................... 9-16

Commissioning ................................................................................................. 10-1


10.1

Table of Contents

Safety Instructions .................................................................................................... 10-1

10.2

Commissioning Tests ................................................................................................ 10-4

10.2.1

Preparation ..................................................................................................................................................10-4

10.2.2

Tests ............................................................................................................................................................10-6

10.2.3

Checking the Binary Signal Inputs ............................................................................................................... 10-6

P437/EN M/R-11-A // P437311650

Table of Contents

P437

10.2.4

Checking the Output Relays ........................................................................................................................ 10-6

10.2.5

Checking the Communications Interfaces Signals ....................................................................................... 10-7

10.2.6

Checking the Protection Function ................................................................................................................10-7

10.2.7

Completing Commissioning ....................................................................................................................... 10-21

11

Troubleshooting ................................................................................................ 11-1

12

Maintenance ..................................................................................................... 12-1


12.1

Maintenance Procedures in the Power Supply Area .................................................. 12-2

12.2

Routine Functional Testing ....................................................................................... 12-4

12.3

Analog Input Circuits .................................................................................................12-5

12.4

Binary Opto Inputs .................................................................................................... 12-6

12.5

Binary Outputs .......................................................................................................... 12-7

12.6

Serial Interfaces ........................................................................................................ 12-8

13

Storage ............................................................................................................. 13-1

14

Accessories and Spare Parts ............................................................................. 14-1

15

Order Information ............................................................................................. 15-1

A1

Function Groups ............................................................................................... A1-1

A2

Internal Signals .................................................................................................A2-1

A3

Glossary ............................................................................................................A3-1
Modules ...................................................................................................................................... A3-1
Symbols ...................................................................................................................................... A3-1
Examples of Signal Names ......................................................................................................... A3-7
Symbols Used ............................................................................................................................. A3-8

A4

A5

Telecontrol Interfaces ....................................................................................... A4-1


A4.1

Telecontrol Interface per EN 60870-5-101 or IEC 870-5-101 (Companion Standard)


.................................................................................................................................. A4-1

A4.1.1

Interoperability ............................................................................................................................................A4-1

A4.2

Communication Interface per IEC 60870-5-103 ........................................................ A4-9

A4.2.1

Interoperability ............................................................................................................................................A4-9

P437 Version History ........................................................................................ A5-1

P437/EN M/R-11-A // P437311650

P437

10

Table of Contents

P437/EN M/R-11-A // P437311650

P437
1

Application and Scope

1.1

Overview
The P437 distance protection device has been designed for selective short-circuit
protection, ground fault protection, and overload protection of transmission lines
and cables in medium-, high- and extra-high-voltage systems. The systems can
be solidly-grounded or resistance grounded.

Fig. 1-1: P437 in a 84 TE sized case.

The multitude of protection functions incorporated into the P437 enable the user
to cover a wide range of applications in the line protection. The relevant
protection parameters can be stored in four independent parameter subsets in
order to adapt the protection device to varying system operation conditions.
The P437 is equipped with a large number of protection functions. These can be
individually configured and cancelled.
All main functions are individually configurable. The user can adapt the P437
flexibly to the scope of protection required in each particular application.
The powerful programmable logic provided by the protection device also makes
it possible to accommodate special applications.

P437/EN M/R-11-A // P437311650

1-1

P437

1 Application and Scope

Protection functions

P437

ANSI

IEC 61850

Function
group

Function

21

DisPDISn

DIST

Distance protection

Overcurrent and undervoltage starting

Underimpedance starting with adjustable load


blinding

Polygonal (quadrilateral) or circular tripping


characteristics

Six distance zones, one zone for special


applications

Eight timer stages, including two backup stages

Directional voltage memory

68

RPSB1

PSB

Power swing blocking and out-of-step tripping

30/ 74

AlmGGIO1

MCMON

Measuring-circuit monitoring

50TD P/ DtpPhs- /
N
DtpEftPTCOx

BUOC

Backup overcurrent protection

50/ 27

SofPhs- /
SofEftPSOF1

SOTF

Switch on to fault protection

85 - 21

PsgPhsPSCH1

PSIG

Protective signaling

79

RREC1

ARC

Auto-reclosing control

25

RSYN1

ASC

Automatic synchronism check

()

67 N

GfsResPTOC1
/ PTOV1 /
RDIR1

GFSC

Ground fault short circuit protection

85 67N

PsgGfsPSCH1

GFCSG

Ground fault short circuit protection signaling

50TD P/ DtpPhs- /
DTOC
Q/ N
DtpEft- /
DtpNgsPTCOx

Definite-time overcurrent protection, four stages,


phase-selective

51 P/ Q/ ItpPhs- /
N
ItpEft- /
ItpNgsPTCOx

IDMT

Inverse-time overcurrent protection, single-stage,


phase-selective

49

THERM

Thermal overload protection

27/ 59/ VtpPhs- /


47 P/ Q/ VtpNgs- /
N
VtpPss- /
VtpRefPTyVx

V<>

Over- /Undervoltage Protection

81

f<>

Over- /Underfrequency protection

1-2

ThmPTTR1

FrqPTyFx

P437/EN M/R-11-A // P437311650

P437

1 Application and Scope

Protection functions

P437

ANSI

IEC 61850

32

PdpAct- /
P<>
PdpRealPDyPx

Directional power protection

50/ 62
BF

RBRFx

CBF

Circuit breaker failure protection

LIMIT

Limit value monitoring

PloGGIOx

LOGIC /
LOG_2

Programmable logic

PHAR1

MAIN

Inrush stabilization

LGC

Function
group

Function

Communication functions
ANSI

IEC 61850

P437

Function
group

Function

16S

COMM1,
COMM2

2 communication interfaces serial, RS 422 / 485 or


fiber optic

()

CLK

IRIGB

Time synchronization IRIG-B

()

COMM3,
COMM4

Protection communication interface InterMiCOM,


serial, RS 422/485, or FO

()

IEC

Communication interface Ethernet

()

GOOSE

IEC 61850

()

16E
16E

GosGGIOx

Measured value functions, binary inputs and outputs


ANSI

IEC 61850

P437

Function
group

Function

INP

4 to 20 optical coupler inputs

()

OUTP

8 to 30 output relays

()

P437/EN M/R-11-A // P437311650

1-3

P437

1 Application and Scope

Measured value functions, analog inputs and outputs


ANSI

IEC 61850

Function
group

Mmuxxx
26

RtdGGIO1

MEASI

IdcGGIO1
MEASO

P437

Function

Measuring

RTD input

()

1 Measuring data input 20 mA, one settable input


value

()

2 Measuring data output 20 mA, two settable


output values

()

Miscellaneous functions
ANSI

P437

IEC 61850

Function
group

Function

F_KEY

4 configurable function keys

LLN0.SGCB

PSS

Parameter subset selection

PTRCx /
RDRE1

FT_RC

Fault recording

= Standard; () = Ordering option.

For a list of all available function groups see the Appendix.

16S
COMM1

16S
COMM2

Self
Monitoring

CLK
IRIGB

16E
IEC

Communication to SCADA/
substation control/ RTU/modem, via RS485
or fiber optics using IEC 60870-5-101,
-103, Modbus, DNP3, Courier, or via RJ45
or fiber optics using IEC 61850.

LIMIT

Recording
and data
acquisition

Overload Rec.

Metering

Fault Rec.

Vref

21
DIST

50/27
SOTF

MCMON

51P,N
BUOC

50/51 P,Q,N
DTOC

51/67 P,Q,N
IDMT

67N
GFSC

79
ARC

25
ASC

49
THERM

32
P<>

27/59 P,Q,N
V<>

50BF/62
CBF

I
V
IN,par
81 O/U
f<>

85-67N
GFCSG
85-21
PSIG

68
PSB

LGC
LOGIC

LGC
LOG_2

Scheme signaling
77
InterMiCOM
serial

COUNT
conventional

26
MEASI

MEASO

Always Available

Optional

Distance Protection
MiCOM P437

Fig. 1-2: Functional diagram.

1-4

P437/EN M/R-11-A // P437311650

1 Application and Scope

1.2

P437

General Functions
Functions listed in the tables above are self-contained function groups (except
for ILOCK) and can be individually configured or de-configured according to the
specific application requirements. Unused or cancelled function groups are
hidden to the user, thus simplifying the menu.
This concept provides a large choice of functions and makes wide-ranging
application of the protection device possible, with just one model version. On the
other hand simple and clear parameter settings can be made.
In this way the protection and control functions (except for ILOCK) can be
included in or excluded from the configuration; they are arranged on the branch
"General Functions" of the menu tree.

P437/EN M/R-11-A // P437311650

1-5

P437

1.3

1 Application and Scope

Global Functions
In addition to the listed features, and extensive self-monitoring, the P437 is
equipped with the following global functions:

Parameter subset selection

System measurements to support the user during commissioning, testing


and operation

Operating data recording


(time-tagged event logging)

Overload data acquisition

Overload recording
(time-tagged event logging)

Ground fault data acquisition

Ground fault recording


(time-tagged event logging)

Fault recording
(time-tagged event logging together with fault value recording of the three
phase currents, the residual current as well as the three phase-to-ground
voltages and the neutral-point displacement voltage).

1-6

P437/EN M/R-11-A // P437311650

1 Application and Scope

1.4

P437

Design
The P437 is modular in design. The plug-in modules are housed in a robust
aluminum case and electrically interconnected via one analog p/c board and one
digital p/c board.

P437/EN M/R-11-A // P437311650

1-7

P437

1.5

1 Application and Scope

Configurable Function Keys


To the right of the text display, there are six freely configurable function keys
available. These may be used for easy control operation access.

1-8

P437/EN M/R-11-A // P437311650

1 Application and Scope

1.6

P437

Inputs and Outputs


The following inputs and outputs are available with the basic device:

1 current measuring input

4 or 5 voltage measuring inputs

8 output relays, freely-configurable

4 binary signal inputs (opto-coupler)

Depending on the order options (Chapter 15, (p. 15-1)) there are several more
modules available. The location diagrams (Section 5.7, (p. 5-19)) give an
overview of the combinations of modules that are technically possible. The
module list (Section 4.3, (p. 4-6)) details the designations that appear in the
location diagrams.
The nominal currents and nominal voltages of the standard measuring inputs can
be set.
The nominal voltage range of the binary signal inputs (opto-coupler) is 24 to
250 V DC. As an option binary signal input modules with a higher operate
threshold are available.
The auxiliary voltage input for the power supply is also designed for an extended
range. The nominal voltage ranges are 60 to 250 V DC and 100 to 230 V AC. As
an option there is a variant available for the lower nominal voltage range 24 V to
60 V DC.
All output relays can be utilized for signaling and command purposes.
The optional PT 100 input (on the analog module Y(4I)) is lead-compensated and
balanced and linearized for PT 100 resistance thermometers as per IEC 751.
The optional 0 to 20 mA input provides open-circuit and overload monitoring,
zero suppression defined by a setting, plus the option of linearizing the input
variable via 20 adjustable interpolation points.
Two selectable measured variables (cyclically updated measured operating data
and stored measured fault data) can be output as a burden-independent direct
current via the two optional 0 to 20 mA outputs. The characteristics are defined
by 3 adjustable interpolation points allowing a minimum output current (4 mA,
for example) for slave-side open-circuit monitoring, knee-point definition for fine
scaling, and a limitation to lower nominal currents (10 mA, for example). Where
sufficient output relays are available, a selectable measured variable can be
output in BCD-coded form by contacts.

P437/EN M/R-11-A // P437311650

1-9

P437

1.7

1-10

1 Application and Scope

Control and Display

Local control panel with an LC display containing 4 20 alphanumeric


characters.

23 LED indicators, 18 of which allow freely configurable function


assignment for the colors red and green. Furthermore there are various
operating modes and flashing functions available.

PC interface.

One or two communication interface(s) for connection to a substation


control system (optional).

P437/EN M/R-11-A // P437311650

1 Application and Scope

1.8

P437

Information Interfaces
Information is exchanged through the local control panel, the PC interface, or two
optional communication interfaces (channel 1 and channel 2).
Using the first channel of the communication interfaces (COMM1), the P437 can
be wired either to the substation control system or to a telecontrol system. This
channel is optionally available with a switchable protocol (per IEC 608705103,
IEC 8705101, DNP 3.0, MODBUS or Courier).
The second communication interface (COMM2, communication protocol per
IEC 608705103 only) is designed for remote control.
As an order option, there is an Ethernet interface for communication per
IEC 61850 available instead of channel 1.
External clock synchronization can be accomplished via one of the
communication protocols or by using the optional IRIGB input.
A direct link to one or two other MiCOM protection devices can be set up by
applying the optional InterMiCOM interfaces (COMM3, COMM4).

P437/EN M/R-11-A // P437311650

1-11

P437

1-12

1 Application and Scope

P437/EN M/R-11-A // P437311650

P437
2

Technical Data

2.1

Conformity

Notice
Applicable to P437, version -311 -412/413 -650.
Declaration of Conformity
The product designated P437 Distance Protection Device has been designed
and manufactured in conformance with the European standards EN 6025526
and EN 6025527 and with the EMC Directive and the Low Voltage Directive
issued by the Council of the European Community.

P437/EN M/R-11-A // P437311650

2-1

P437

2 Technical Data

2.2

General Data

2.2.1

General Device Data

Design

Surface-mounted case suitable for wall installation, or

Flush-mounted case for 19 cabinets and for control panels.

Vertical 30.

Installation Position

Degree of Protection
Per DIN VDE 0470 and EN 60529 or IEC 529.

IP 52 for the front panel.

Flush-mounted case:

IP 50 for the case (excluding the rear connection area)


IP 20 for the rear connection area, pin-terminal connection
IP 10 for the rear connection area, ring-terminal connection

Surface-mounted case:

IP 50 for the case


IP 50 for the fully enclosed connection area with the supplied rubber
grommets fitted

Weight

84 TE case: Approx. 11 kg

Dimensions and Connections


See dimensional drawings (Section 4.2, (p. 4-4)), and the location and
terminal connection diagrams (Section 5.7, (p. 5-19)).
Terminals
PC interface (X6)

EIA RS232 (DIN 41652) connector, type D-Sub, 9-pin

Communication interfaces COMM1 to COMM4

Fiber (X7, X8 and X31, X32 and X36, X37)

F-SMA optical fiber connection per IEC 608742 (for plastic fibers), or

optical fiber connection BFOC-ST connector 2.5 per IEC 60874101 (for
glass fibers).
(ST is a registered trademark of AT&T Lightguide Cable Connectors.)

Wire leads (X9, X10, X33, X38)

IRIG-B Interface (X11)

2-2

M2 threaded terminal ends for wire cross-sections up to 1.5 mm.


BNC plug

P437/EN M/R-11-A // P437311650

P437

2 Technical Data

Communication interface IEC 61850

Fiber (X7, X8)

optical fiber connection BFOC-ST connector 2.5 per IEC 6087410 (for
glass fibers).
(ST is a registered trademark of AT&T Lightguide Cable Connectors.)

Fiber (X13)

SC connector per IEC 60874144 (for glass fibers)

Wire leads (X12)

RJ45 connector per ISO/IEC 8877.

Current measuring inputs (conventional inputs)

Threaded terminal ends, pin-type cable lugs: M5, self-centering with cage
clamp to protect conductor cross-sections 4 mm, or:

Threaded terminal, ring-terminal connection: M4.

Other inputs and outputs

Threaded terminal ends, pin-type cable lugs: M3, self-centering with cage
clamp to protect conductor cross-sections 0.2 to 2.5 mm, or:

Threaded terminal ends, ring-type cable lugs: M4.

Creepage Distances and Clearances

2.2.2

Per EN 60255-27.

Pollution degree 3, working voltage 250 V,

overvoltage category III, impulse test voltage 5 kV.

Environmental Conditions

Temperatures
Recommended temperature range

-5C to +55C [+23F to +131F].

Limit temperature range

Operation: -25C to +55C [-13F to +131F].

Storage and transport: -25C to +70C [-13F to +158F].

Ambient Humidity Range

75 % relative humidity (annual mean).

56 days at 95 % relative humidity and 40C [104F].

Condensation not permitted.

Solar Radiation
Direct solar radiation on the front of the device must be avoided.

P437/EN M/R-11-A // P437311650

2-3

P437

2 Technical Data

2.3

Tests

2.3.1

Type Tests

Type Tests
All tests per EN 60255-26.
2.3.1.1

Electromagnetic Compatibility (EMC)

Interference Suppression
Per EN 55022 or IEC CISPR 22, Class A.
1 MHz Burst Disturbance Test
Per EN 60255-22-1, Class III.

Common-mode test voltage: 2.5 kV.

Differential test voltage: 1.0 kV.

Test duration: > 2 s.

Source impedance: 200 .

Immunity to Electrostatic Discharge


Per EN 60255-22-2 and IEC 60255-22-2, severity level 4.
Contact discharge

Single discharges: > 10.

Holding time: > 5 s.

Test voltage: 8 kV.

Test generator: 50 to 100 M, 150 pF / 330 .

Immunity to Radiated Electromagnetic Energy


Per EN 6100043 and ENV 50204, severity level 3.

Antenna distance to tested device: > 1 m on all sides.

Test field strength, frequency band 80 to 1000 MHz: 10 V / m.

Test using AM: 1 kHz / 80 %.

Single test at 900 MHz: AM 200 Hz / 100%.

Electrical Fast Transient or Burst Requirements


Per EN 61000-44 and IEC 60255224, severity levels 3 and 4.

Rise time of one pulse: 5 ns.

Impulse duration (50% value): 50 ns.

Amplitude: 2 kV / 1 kV or 4 kV / 2 kV.

Burst duration:15 ms.

Burst period: 300 ms.

Burst frequency: 5 kHz.

Source impedance: 50 .

Power Frequency Immunity


Per IEC 60255227, Class A:

2-4

P437/EN M/R-11-A // P437311650

P437

2 Technical Data

Phase-to-phase

RMS value 150 V.

Coupling resistance 100 .

Coupling capacitor 0.1 F, for 10 s.

Phase-to-ground

RMS value 300 V.

Coupling resistance 220 .

Coupling capacitor 0.47 F, for 10 s.

To comply with this standard, it is suggested to set the parameter (010 220)
IN P: F il ter to 6 [steps].
Current/Voltage Surge Immunity Test
Per EN 61000-45 and EN 60255-225, insulation class 4.
Testing of circuits for power supply and asymmetrical or symmetrical
lines.

Open-circuit voltage, front time / time to half-value: 1.2 / 50 s.

Short-circuit current, front time / time to half-value: 8 / 20 s.

Amplitude: 4 / 2 kV.

Pulse frequency: > 5 / min.

Source impedance: 12 / 42 .

Immunity to Conducted Disturbances Induced by Radio Frequency Fields


Per EN 61000-4-6 and EN 60255-226, severity level 3.

Test voltage: 10 V.

Power Frequency Magnetic Field Immunity


Per EN 61000-4-8 or IEC 61000-4-8, severity level 4.

Test frequency: 50 Hz

Test field strength: 30 A / m.

Alternating Component (Ripple) in DC Auxiliary Energizing Quantity


Per EN 60255-11.

2.3.1.2

12 %.

Insulation

Voltage Test
Per EN 60255-27.

2 kV AC, 60 s

Only direct voltage (2.8 kV DC) must be used for the voltage test on the power
supply inputs. The PC interface must not be subjected to the voltage test.
Impulse Voltage Withstand Test
Per EN 60255-27.

Front time: 1.2 s

Time to half-value: 50 s

Peak value: 5 kV

Source impedance: 500

P437/EN M/R-11-A // P437311650

2-5

P437
2.3.1.3

2 Technical Data

Environmental tests

Temperature Stability Test


Per IEC 60068-2-1

-25C (-13F) storage (96 hours)

-40C (-40F) operation (96 hours)

Per IEC 60068-2-2

+85C (185F) storage (96 hours)

+85C (185F) operation (96 hours)

Per IEC 60068-2-14

Change of temperature, 5 cycles, 1C / min rate of change

Ambient Humidity Range Test


Per IEC 60068-2-3

56 days at 93% relative humidity and 40C (104F)

Per IEC 60068-2-30

Damp heat, cyclic (12 + 12 hours)


93 % relative humidity, +25C +55C (77F 131F)

Corrosive Environment Tests


Per IEC 60068-2-60: 1995, Part 2, Test Ke, Method (class) 3
Industrial corrosive environment/ poor environmental control, mixed gas flow
test.

2.3.1.4

21 days at 75% relative humidity and 30C (86F) with exposure to


elevated concentrations of H2S, NO2, Cl2 and SO2.

Mechanical Robustness 1
Applicable to the following case variants:

Flush mounted case, flush-mounting method 1 (without angle brackets and


frame)

Vibration Test
Per EN 6025521-1 or IEC 6025521-1, test severity class 1.
Frequency range in operation

10 to 60 Hz, 0.035 mm, and

60 to 150 Hz, 0.5 g

Frequency range during transport

10 to 150 Hz, 1 g

Shock Response and Withstand Test, Bump Test


Per EN 60255-21-2 or IEC 60255-21-2.
Acceleration and pulse duration:

Shock Response tests are carried out to verify full operability (during
operation), test severity class 1:
5 g for 11 ms.

Shock Withstand tests are carried out to verify the endurance (during
transport), test severity class 1:
15 g for 11 ms.

2-6

P437/EN M/R-11-A // P437311650

P437

2 Technical Data

Seismic Test
Per EN 60255213 or IEC 60255213, test procedure A, class 1.
Frequency range

2.3.1.5

5 to 8 Hz, 3.5 mm / 1.5 mm, 8 to 35 Hz, 10 / 5 m/s, 3 x 1 cycle.

Mechanical Robustness 2
Applicable to the following case variants:

Flush mounted case, flush-mounting method 2 (with angle brackets and


frame)

Surface-mounted case

Vibration Test
Per EN 6025521-1 or IEC 6025521-1, test severity class 2.
Frequency range in operation

10 to 60 Hz, 0.075 mm, and

60 to 150 Hz, 1.0 g

Frequency range during transport

10 to 150 Hz, 2 g

Shock Response and Withstand Test, Bump Test


Per EN 60255-21-2 or IEC 60255-21-2.
Acceleration and pulse duration:

Shock Response tests are carried out to verify full operability (during
operation), test severity class 2:
10 g for 11 ms.

Shock Withstand tests are carried out to verify the endurance (during
transport), test severity class 1:
15 g for 11 ms.

Shock bump tests are carried out to verify permanent shock (during
transport), test severity class 1:
10 g for 16 ms.

Seismic Test
Per EN 60255213 or IEC 60255213, test procedure A, class 2.
Frequency range

2.3.2

5 to 8 Hz, 7.5 mm / 3.5 mm, 8 to 35 Hz, 20 / 10 m/s, 3 x 1 cycle.

Routine Tests
All tests per EN 60255-1.

Voltage Test
Per EN 60255-27.

2.2 kV AC, 1 s

Only direct voltage (2.8 kV DC) must be used for the voltage test on the power
supply inputs.
The PC interface must not be subjected to the voltage test.

P437/EN M/R-11-A // P437311650

2-7

P437

2 Technical Data

Additional Thermal Test

2-8

100% controlled thermal endurance test, inputs loaded.

P437/EN M/R-11-A // P437311650

P437

2 Technical Data

2.4

Inputs and Outputs

2.4.1

Measuring Inputs

Current Measuring Inputs

Nominal current Inom: 1 and 5 A AC (adjustable).

Nominal consumption per phase: < 0.1 VA at Inom.

Load rating:

continuous: 20 A,
for 10 s: 150 A,
for 1 s: 500 A.

Nominal surge current: 1250 A.

Voltage Measuring Inputs

Nominal voltage Vnom: 50 to 130 V AC (adjustable).

Nominal consumption per phase: < 0.3 VA at Vnom = 130 V AC.

Load rating:

continuous: 150 V AC
for 10 s: 300 V AC

Frequency

Nominal frequency fnom: 50 Hz and 60 Hz (adjustable).

Operating range: 0.95 to 1.05 fnom.

Frequency protection: 40 to 70 Hz.

P437/EN M/R-11-A // P437311650

2-9

P437
2.4.2

2 Technical Data

Binary Signal Inputs


Threshold pickup and drop-off points as per ordering option

18 V standard variant (VA,nom: = 24 to 250 V DC):

Switching threshold in the range 14 V to 19 V.

Special variants with switching thresholds from 58% to 72% of the nominal input
voltage (i.e. definitively low for VA < 58% of the nominal supply voltage,
definitively high for VA > 72% of the nominal supply voltage).

Special variant 72 V: Nominal supply voltage 110 V DC.

Special variant 83 V: Nominal supply voltage 127 V DC.

Special variant 143 V: Nominal supply voltage 220 V DC.

Special variant 163 V: Nominal supply voltage 250 V DC.

Power consumption per input

18 V standard variant:
VA = 19 to 110 V DC : 0.5 W 30%,
VA > 110 V DC: VA 5 mA 30%.

Special variants:
VA > switching threshold: VA 5 mA 30%.

The standard variant of binary signal inputs (opto couplers) is recommended in


most applications, as these inputs operate with any voltage from 19 V. Special
versions with higher pick-up/drop-off thresholds are provided for applications where
a higher switching threshold is expressly required.
The maximum voltage permitted for all binary signal inputs is 300 V DC.

2-10

P437/EN M/R-11-A // P437311650

P437

2 Technical Data

2.4.3

2.4.4

2.4.5

IRIGB Interface

Minimum / maximum input voltage level (peak-peak): 100 mVpp / 20 Vpp

Input impedance: 33 k at 1 kHz

Electrical isolation: 2 kV

Direct Current Input

Input current: 0 to 26 mA

Value range: 0.00 to 1.20 IDC,nom (IDC,nom = 20 mA)

Maximum continuous input current permitted: 50 mA

Maximum input voltage permitted: 17 V DC

Input load: 100

Open-circuit monitoring: 0 to 10 mA (adjustable)

Overload monitoring: > 24.8 mA

Zero suppression: 0.000 to 0.200 IDC,nom (adjustable).

Resistance Thermometer
Only PT 100 permitted for analog (I/O) module, mapping curve per IEC 75.1.
PT 100, Ni 100 or Ni 120 permitted for temperature p/c board (the RTD module).

2.4.6

Value range: 40.0C to +215.0C (40F to +419F).

3-wire configuration: max. 20 per conductor.

Open and short-circuited input permitted.

Open-circuit monitoring: > +215C and < -40C ( > +419F and
< -40F).

Direct Current Output

Output current: 0 to 20 mA

Maximum permissible load: 500

Maximum output voltage: 15 V

P437/EN M/R-11-A // P437311650

2-11

P437
2.4.7

2 Technical Data

Output Relays
Binary I/O Module X(4H)

All other modules

with high-break contacts, applicable to


DC circuits only.

Rated voltage:

250 V DC

250 V DC, 250 V AC.

Continuous
current:

10 A

5A

Short-duration
current:
Making capacity:
Breaking capacity:

250 A for 0.03 s,

30 A for 3 s

30 A

30 A for 0.5 s.
1000 W (VA) at L/R = 40 ms.

7500 W resistive or 30 A at
250 V DC,

0.2 A at 220 V DC and L/


R = 40 ms,

Maximum values: 30 A and


300 V DC.

4 A at 230 V AC and cos = 0.4.

2500 W inductive (L/R = 40 ms) or


10 A at 250 V DC,
Maximum values: 10 A and
300 V DC.

Operating time:

less than 0.2 ms

less than 5 ms

Reset time:

less than 8 ms

less than 5 ms

2.4.8

BCD Measured Data Output


Maximum numerical value that can be displayed: 399

2-12

P437/EN M/R-11-A // P437311650

P437

2 Technical Data

2.5

Interfaces

2.5.1

Local Control Panel


Input or output

With 13 keys and a 4 20 character liquid crystal display (LCD).

State and fault signals

2.5.2

PC Interface

2.5.3

23 LED indicators (5 permanently assigned, 18 freely configurable).

Transmission rate: 300 to 115,200 baud (adjustable)

Serial Communication Interface


The communication modules can be provided with up to four communication
channels, depending on the module variant. Channel 1, 3 and 4 may either be
equipped to connect wire leads or optical fibers and channel 2 is only available to
connect wire leads.
For communication interface 1, communication protocols based on
IEC 870-5103, IEC 608705101, MODBUS, DNP 3.0, or Courier can be set.

Transmission rate: 300 Baud to 64.0 kBaud (adjustable via setting


parameter CO MM1: Bau d r ate).

Communication interface 2 can only be operated with the interface protocol


based on IEC 60870-5-103.

Transmission rate: 300 Baud to 57.6 kBaud (adjustable via setting


parameter CO MM2: Bau d r ate).

Communication interfaces COMM3 and COMM4 (InterMiCOM protective


interfaces) permit end-end channel-aided digital communication schemes to be
configured for real time protective signaling between two protection devices.

Transmission rate: 600 baud to 19200 baud (adjustable via setting


parameter C O MM3: Baud r ate or C OMM4 : Bau d rat e, respectively).

Per RS 485 or RS 422, 2 kV isolation

Distance to be bridged

Wire Leads

Point-to-point connection: max. 1200 m


Multipoint connection: max. 100 m

Plastic Fiber Connection

Optical wavelength: typically 660 nm

Optical output: min. -7.5 dBm

Optical sensitivity: min. -20 dBm

Optical input: max. -5 dBm

Distance to be bridged: max. 45 m


(Distance to be bridged given for identical optical outputs and inputs at
both ends, a system reserve of 3 dB, and typical fiber attenuation)

P437/EN M/R-11-A // P437311650

2-13

P437

2 Technical Data

Glass Fiber Connection G 50/125

Optical wavelength: typically 820 nm

Optical output: min. -19.8 dBm

Optical sensitivity: min. -24 dBm

Optical input: max. -10 dBm

Distance to be bridged: max. 400 m


(Distance to be bridged given for identical optical outputs and inputs at
both ends, a system reserve of 3 dB, and typical fiber attenuation)

Glass Fiber Connection G 62.5/125

Optical wavelength: typically 820 nm

Optical output: min. -16 dBm

Optical sensitivity: min. -24 dBm

Optical input: max. -10 dBm

Distance to be bridged: max. 1,400 m


(Distance to be bridged given for identical optical outputs and inputs at
both ends, a system reserve of 3 dB, and typical fiber attenuation)

2.5.4

IEC Communication Interface


Ethernet-based communications per IEC 61850:
Wire Leads

RJ45, 1.5 kV isolation

Transmission rate: 100 Mbit/s

Distance to be bridged: max. 100 m

Optical Fiber (100 Mbit/s)

Optical wavelength: typically 1300 nm

ST connector

Glass fiber G50/125:

Glass fiber G62.5/125:

2-14

Optical output: min. 18.85 dBm


Optical sensitivity: min. 32.5 dBm
Optical input: max. 12 dBm

Optical output: min. 15 dBm


Optical sensitivity: min. 32.5 dBm
Optical input: max. 12 dBm

P437/EN M/R-11-A // P437311650

P437

2 Technical Data

SC connector

Glass fiber G50/125:

Glass fiber G62.5/125:

2.5.5

Optical output: min. 23.5 dBm


Optical sensitivity: min. 31 dBm
Optical input: max. 14 dBm

Optical output: min. 20 dBm


Optical sensitivity: min. 31 dBm
Optical input: max. 14 dBm

IRIGB Interface

B122 format

Amplitude modulated signal

Carrier frequency: 1 kHz

BCD- coded variable data (daily)

P437/EN M/R-11-A // P437311650

2-15

P437

2.6

2 Technical Data

Information Output
Counters, measured data, and indications: see chapter Information and Control
Functions.

2-16

P437/EN M/R-11-A // P437311650

P437

2 Technical Data

2.7

Settings Typical Characteristic Data

2.7.1

Main Function

2.7.2

2.7.3

2.7.4

Minimum output pulse for trip command: 0.1 to 10 s (adjustable)

Minimum output pulse for close command: 0.1 to 10 s (adjustable)

Distance Protection

Minimum fault detection time: 7 ms

Fault detector reset time 30 ms 10 ms

Directional sensitivity up to 2 s after fault detection:

Directional sensitivity after 2 s after fault detection and for switching on to


fault: 200 mV 10%

Shortest tripping time: approx. 17 ms

Fault detection and measurement resetting ratio: 0.95

Definite-Time and Inverse-Time Overcurrent Protection

Operate time including output relay (measured variable from 0 to 2-fold


operate value): 40 ms, approx. 30 ms

Reset time (measured variable from 2-fold operate value to 0): 40 ms,
approx. 30 ms

Starting resetting ratio: approx. 0.95

Time-Voltage Protection

Operate time including output relay (measured variable from nominal value
to 1.2-fold operate value or measured variable from nominal value to 0.8fold operate value):

Reset time (measured variable from 1.2-fold operate value to nominal


value or measured variable from 0.8-fold operate value to nominal value):

45 ms, approx. 30 ms

Resetting ratio for V<>:

2.7.5

40 ms, approx. 30 ms

1% to 10% (adjustable)

Power Directional Protection

Operate time including output relay (measured variable from nominal value
to 1.2-fold operate value or measured variable from nominal value to 0.8fold operate value): 60 ms, approx. 50 ms

Reset time (measured variable from 1.2-fold operate value to nominal


value or measured variable from 0.8-fold operate value to nominal value):
40 ms, approx. 30 ms

Resetting ratio for P>, Q>: 0.05 to 0.95 (adjustable)

Resetting ratio for P<, Q<: 1.05 to 20 (adjustable)

P437/EN M/R-11-A // P437311650

2-17

P437

2 Technical Data

2.8

Deviations

2.8.1

Deviations of the Operate Values

2.8.1.1

Definitions
Reference Conditions

Sinusoidal signals at nominal frequency fnom, total harmonic distortion 2


%, ambient temperature 20C (68F), and nominal auxiliary voltage VA,nom.

Deviation

2.8.1.2

Distance Protection

Starting V<, VNG>, VNG>>: 3%

Starting I>, I>>, IN>:

Setting range 0.1 to 0.25 Inom: 5%

Setting range > 0.25 Inom: 3%

Starting Z< at K = 0, 30, 60, 90: 5%

Impedance Measurement Z<

2.8.1.3

Deviation relative to the setting under reference conditions.

Deviation at K = 0, 90: 3%

Deviation at K = 30, 60: 5%

Directional Determination: 3

Measuring-Circuit Monitoring
Operate values Ineg, Vneg

2.8.1.4

Deviation: 3 %

Overcurrent-Time Protection
Operate values I>, IN>

2.8.1.5

Deviation: 5%

Thermal Overload Protection


Operate value

2.8.1.6

Deviation: 5%

Time-Voltage Protection
Operate values

2.8.1.7

V<>, Vpos<>: 1% (in the range 0.6 to 1.4 Vnom)

VNG>, Vneg>: 1% (in the range > 0.3 Vnom)

Frequency Protection
Operate values f<>

2-18

30 mHz (f

nom

= 50 Hz)

40 mHz (f

nom

= 60 Hz)
P437/EN M/R-11-A // P437311650

P437

2 Technical Data

Operate values df/dt

2.8.1.8

0.1 Hz/s (f

nom

= 50 or 60 Hz)

Power Directional Protection


Operate values P<>, Q<>

2.8.1.9

Direct Current Input

2.8.1.10

Deviation: 1 %

Resistance Thermometer

2.8.1.11

Deviation: 5 %

Deviation: 2C

Analog Measured Data Output

Deviation: 1 %

Output residual ripple with max. load

1%

2.8.2

Deviations of the Timer Stages

2.8.2.1

Definitions
Reference conditions

Sinusoidal signals at nominal frequency fnom, total harmonic distortion 2


%, ambient temperature 20C (68F), and nominal auxiliary voltage VA,nom.

Deviation

2.8.2.2

Definite-time stages

2.8.2.3

Deviation relative to the setting under reference conditions.

Deviation: 1% + 20 ms to 40 ms

Inverse-time stages

Deviation when I 2 Iref: 5% + 10 to 25 ms

For extremely inverse IEC characteristics and for thermal overload


characteristics: 7.5% + 10 to 20 ms

P437/EN M/R-11-A // P437311650

2-19

P437

2 Technical Data

2.8.3

Deviations of Measured Data Acquisition

2.8.3.1

Definitions
Reference conditions

Sinusoidal signals at nominal frequency fnom, total harmonic distortion


2%, ambient temperature 20C (68F), and nominal auxiliary voltage
VA,nom.

Deviation

2.8.3.2

Deviation relative to the setting under reference conditions.

Operating Data Measurement


Measuring input currents

Deviation: 1%

Measuring input voltages

Deviation: 0.5%

Internally formed resultant current and negative-sequence system


current

Deviation: 2%

Internally formed neutral-point displacement voltage and voltages of


positive- and negative-sequence systems

Deviation: 2%

Active and reactive power / active and reactive energy

Deviation: 2% when cos = 0.7

Deviation: 5% when cos = 0.3

Load angle

Deviation: 1

Frequency

2.8.3.3

Deviation: 10 mHz

Fault Data
Short-circuit current and voltage

Deviation: 3%

Short-circuit impedance, reactance, and fault location

2.8.3.4

Deviation: 5%

Internal Clock
With free running internal clock

Deviation: < 1 min/month

With external synchronization (with a synchronization interval 1 min)

Deviation: < 10 ms

With synchronization via IRIG-B interface

2-20

1 ms

P437/EN M/R-11-A // P437311650

P437

2 Technical Data

2.9

Resolution of the Fault Data Acquisition

2.9.1

Time Resolution

2.9.2

20 sampled values per period

Phase Currents System


Dynamic range

100 Inom or 25 Inom

Amplitude resolution

2.9.3

at Inom = 1 A: 6.1 mArms or 1.5 mArms

at Inom = 5 A: 30.5 mArms or 7.6 mArms

Residual Current
Dynamic range

16 Inom

Amplitude resolution

2.9.4

at Inom = 1 A: 1.0 mArms

at Inom = 5 A: 4.9 mArms

Phase-to-Ground Voltages and Neutral-Point Displacement


Voltage
Dynamic range

150 V

Amplitude resolution

9.2 mVrms

P437/EN M/R-11-A // P437311650

2-21

P437

2 Technical Data

2.10

Recording Functions

2.10.1

Organization of the Recording Memories

Operating Data Memory


Scope for signals

All signals relating to normal operation; from a total of 1024 different logic
state signals.

Depth for signals

The 1000 most recent signals.

Monitoring Signal Memory


Scope for signals

All signals relevant for self-monitoring from a total of 1024 different logic
state signals.

Depth for signals

Up to 30 signals.

Overload Memory
Number

The 8 most recent overload events

Scope for signals

All signals relevant for an overload event from a total of 1024 different logic
state signals.

Depth for signals

200 entries per overload event.

Ground Fault Memory


Number

The 8 most recent ground fault events

Scope for signals

All signals relevant for a ground fault event from a total of 1024 different
logic state signals.

Depth for signals

200 entries per ground fault event.

Fault Memory
Number

The 8 most recent faults.

Scope for signals and fault values

2-22

All fault-relevant signals from a total of 1024 different logic state signals.

Sampled values for all measured currents and voltages

P437/EN M/R-11-A // P437311650

P437

2 Technical Data

Depth for signals and fault values

200 entries per fault event

max. number of cycles per fault can be set by user;


820 periods in total for all faults, that is 16.4 s (for fnom = 50 Hz) or 13.7 s
(for fnom = 60 Hz).

Resolution of the Recorded Data

As per Section 2.9, (p. 2-21), with maximum current dynamic ranges
(100 Inom / 16 IN,nom)

P437/EN M/R-11-A // P437311650

2-23

P437

2.11

2 Technical Data

Power Supply
Nominal auxiliary voltage VA,nom

24 to 60 V DC or 60 to 250 V DC and 100 to 230 V AC (ordering option).

Operating range for direct voltage

0.8 to 1.1 VA,nom with a residual ripple of up to 12 % VA,nom.

Operating range for alternating voltage

0.9 to 1.1 VA,nom.

Nominal burden

where VA = 220 V DC and with maximum module configuration

84 TE case, relays de-energized/energized): approx. 14.5 W / 42.3 W

Start-up peak current

< 3 A for duration of 0.25 ms

Stored energy time

2-24

50 ms for interruption of VA 220 V DC (upper range supply)

50 ms for interruption of VA 60 V DC (lower range supply)

P437/EN M/R-11-A // P437311650

P437

2 Technical Data

2.12

Current Transformer Specifications

2.12.1

Symbols
The following symbols are used in accordance with IEC 600441 and IEC 600446
standards:

P437/EN M/R-11-A // P437311650

2-25

P437

2 Technical Data

Ipn

Rated primary current (nominal primary current) of the CT

Isn

Rated secondary current (nominal secondary current) of the CT

Ipsc

Rated primary (symmetrical) short-circuit current

Kssc

Rated symmetrical short-circuit current factor:


K ssc =

I psc
I pn

Iref

Reference current of IDMT protection element

Rbn

Rated resistive burden (secondary connected) of the CT

Pbn

Equivalent power over the rated resistive burden of the CT for rated
secondary current:
2
Pbn = Rbn I sn

Rb

Actual resistive burden (secondary connected) of the CT

Pb

Equivalent power over the actual resistive burden of the CT for rated
secondary current:
2
Pb = Rb I sn

Rct

Secondary winding resistance of the CT

Pct

Equivalent power over the secondary winding resistance of the CT for


secondary rated current:
2
Pct = Rct I sn

Vsal

Secondary accuracy limiting voltage (e.m.f.) of the CT

Vk

Rated knee point voltage (e.m.f.) of the CT

nn

Rated accuracy limit factor of the CT

nb

Actual accuracy limit factor of the CT:


nb = nn

Rct + Rbn
Rct + Rb

= nn

Pct + Pbn
Pct + Pb

Rl

One-way lead resistance from CT to relay

Rrel

Resistive burden of relays CT input

Tp

Primary time constant (primary system time constant)

(System) angular frequency

Xp/Rp Primary impedance ratio (system impedance ratio):


Xp
Rp

Kd

= Tp

Dimensioning factor for the CT

Kemp Relay specific, empirically determined dimensioning factor for the CT

2-26

P437/EN M/R-11-A // P437311650

P437

2 Technical Data

2.12.2

General Equations
The current transformer can be dimensioned

either for the minimum required secondary accuracy limiting voltage acc.
to IEC 600441, 2.3.4:
V sal K d K ssc I sn (Rct + Rb)

or for the minimum required rated accuracy limit factor acc. to


IEC 600441, 2.3.3, as follows:
nn K d K ssc

Rct + Rb
Rct + Rbn

= K d K ssc

Pct + Pb
Pct + Pbn

The relation between both methods is given as follows:


V sal = nn (

Pbn
I sn

+ I sn Rct )

The actual secondary connected burden Rb is given as follows:

For phase-to-ground faults: Rb = 2 Rl + Rrel

For phase-to-phase faults: Rb = Rl + Rrel

The wire lead burden is calculated as:


Rl =

l
A

= specific conductor resistance


(e.g. for copper 0.021 mm/m = 2.110-8 m, at 75C)

l = wire length

A = wire cross section

The MiCOM Px3x input CT burden Rrel is less than 20 m, independent of the set
nominal current (1A or 5A). Usually this relay burden can be neglected.
The rated knee point voltage Vk according to IEC 600441, 2.3.12 is lower than
the secondary accuracy limiting voltage Vsal according to IEC 600441, 2.3.4. It is
not possible to give a general relation between Vk and Vsal, but for standard core
material the following relations applies:

VK0.85Vsal for class 5P CTs, and

VK0.75Vsal for class 10P CTs, respectively.

Theoretically, the specifications of the current transformer could be calculated to


avoid saturation by inserting its maximum value, instead of the required overdimensioning factor Kd:
K d = K max 1 +

Xp
Rp

= 1 + Tp

However, this is not necessary. Instead, it is sufficient to consider an empirically


determined dimensioning factor Kd=Kemp such that the appropriate operation of
the protection function is ensured under the given conditions. This factor
depends on application and relay type, as outlined in the following.

2.12.3

Distance Protection
For the P437, the empirical dimensioning factor Kd = Kemp can be taken from the
following diagram, which shows three practical curves:

P437/EN M/R-11-A // P437311650

2-27

P437

2 Technical Data

Curve A (red): Choosing Kemp according to this line assures that transient
CT saturation practically does not affect distance protection: Distance
(instantaneous) zone trip is assured within 0/+40 ms for up to 95% of the
set zone reach.

Curve B (blue): Choosing Kemp according to this line allows transient CT


saturation to slightly affect distance protection: Distance (instantaneous)
zone trip is assured within 0/+50 ms for up to 90% of the set zone reach.

Curve C (green): Choosing Kemp according to this line allows transient CT


saturation to affect distance protection: Distance zone trip is assured for up
to 85% of the set zone reach.

30
A

25

20

15
B

K emp
10

0
0

20

40

60

80

100

120

140

160

Xp / R p

As per IEC 60255-121 (draft 2011), the following 4 fault conditions have to be
checked to determine the required CT dimensioning.

A
DIST

1
Fig. 2-1: Check conditions.

2-28

P437/EN M/R-11-A // P437311650

P437

2 Technical Data

Case 1:

Close-up backward short-circuit (security case)


Acceptance criteria: Stable backward direction decision, no trip
Select required Kemp per curve C

Case 2:

Close-up forward short-circuit (dependability case)


Acceptance criterion: Instantaneous trip with less than 1 period add. delay
Required Kemp = 1.5

Case 3:

Short-circuit at 80% of Zone 1 reach limit (dependability case)


Acceptance criterion: Trip with less than 3 periods add. delay
Select required Kemp per curve B

Case 4:

Short-circuit at 110% of Zone 1 reach limit (security case)


Acceptance criterion: Correct time delayed zone 2 trip
Select required Kemp per curve C

Depending on the fault location, different maximum short-circuit currents and


primary system X/R ratios apply! Therefore the required CT dimensioning has to
be calculated separately for all 4 cases. The biggest sizing from all 4 cases then
has to be used.
It is recommended to use CTs of accuracy class 5P (or equivalent).

P437/EN M/R-11-A // P437311650

2-29

P437

2-30

2 Technical Data

P437/EN M/R-11-A // P437311650

P437
3

Operation

3.1

Modular Structure
The P437, a numerical device, is part of the MiCOM P30 family of devices. The
device types included in this family are built from identical uniform hardware
modules. The figure below shows the basic hardware structure of the P437.

EDIT MODE

Processor module

Analog
module
Digital
busbus
module

Voltages

Currents

Binary I/O module

Signals

Commands

Signals

Commands

Signals

Commands

Measured data

Power supply module

Analog bus module

Transformer module

HEALTHY

C
Analog I/O module

TRIP
ALARM
OUT OF SERVICE

Analog I/O module

Local control module

Protection interface
InterMiCOM

Communic. module

Communication
interface(s)

PC interface

Signals
Commands

Commands Auxiliary voltage


Signals

D5Z5201C

Fig. 3-1: Basic hardware structure.

External analog quantities and binary quantities electrically isolated are


converted to the internal processing levels by the peripheral modules T, Y, and X.
The optional binary I/O modules X are equipped with optical couplers for binary
signal input as well as output relays for the output of signals and commands or
combinations of these.
The external auxiliary voltage is applied to the power supply module V, which
supplies the auxiliary voltages that are required internally.
Analog data is transferred from the transformer module T via the analog bus
module B to the processor module P. The processor module contains all the
elements necessary for the conversion of measured analog variables, including
multiplexers and analog/digital converters. The analog data conditioned by the
analog I/O module Y is transferred to the processor module P via the digital bus
module. The optional transient ground fault module N evaluates the measured
variables according to the transient ground fault evaluation scheme.
The processor handles the processing of digitized analog variables and of binary
signals, generates the protective trip and signals, and transfers them to the
binary I/O modules X via the digital bus module. The processor module also
handles overall device communication.

P437/EN M/R-11-A // P437311650

3-1

P437

3 Operation

The optional communication modules provide one or two serial communication


interfaces for the integration of the protection and control unit into a substation
control system and for remote access respectively a protection communication
interface for the transfer of digital information between two protection devices.
The local control module L is located behind the front panel and connected to the
processor module via a ribbon cable. It encompasses all control and display
elements as well as a PC interface for running the operating program S1.

3-2

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.2

Operator-Machine Communication
The following interfaces are available for the exchange of information between
the user and the P437:

Integrated user interface (LOC: local control panel)

PC interface

Communication interface

All settings and signals as well as all measurements and control functions are
arranged within the branches of the menu tree following a scheme that is
uniform throughout the device family. The main branches are:
Parameters Branch
All settings are contained in this branch. This branch carries all settings,
including the identification data of the P437, the configuration parameters for
adapting the P437 interfaces to the system, and the function parameters for
adapting the device functions to the process. All values in this group are stored
in non-volatile memory, which means that the values will be preserved even if
the power supply fails.
Operation Branch
This branch includes all information relevant for operation such as measured
operating data and binary signal states. This information is updated periodically
and consequently is not stored. In addition, various controls are grouped here,
for example those for resetting counters, memories and displays.
Events Branch
The third branch is reserved for the recording of events. All information in this
group is therefore stored. In particular, the start/end signals during a fault, the
measured fault data, and the sampled fault waveforms are stored here and can
be read out when required.
Display of Settings and Signals
Settings and signals are displayed either in plain text or as addresses, in
accordance with the users choice. All settings and signals of the P437 are
documented in a separate collection of documents, the so-called
DataModelExplorer. The Addresses document (being part of the
DataModelExplorer) is complete in the sense that it contains all settings,
signals and measured variables that are relevant for the user of the P437.
The configuration of the local control panel also permits the installation of
Measured Value Panels on the LCD display. Different Panels are automatically
displayed for specific system operating conditions. Priority increases from normal
operation to operation under overload conditions and finally to operation
following a short circuit in the system. Thus the P437 provides the measured
data relevant for the prevailing conditions.

P437/EN M/R-11-A // P437311650

3-3

P437

3.3

3 Operation

Configuration of the Bay Panel and of the Measured Value


Panels, Selection of the Control Point (Function Group LOC)
When the graphic display has been fitted then the layout of a bay with its
switchgear units will be shown on the Bay Panel. A Bay Panel usually consists of
one Bay Panel image as a standard but after applying the bay editor from the PC
Access Software MiCOM S1 and having loaded a customized Bay Panel it can be
sub-divided into up to eight pages. The graphic display also permits the display
of the Event Panel and the configurable Signal Panel. When the text display has
been fitted the Bay Panel will display switching state signals from external
devices (closed, open, intermediate position) and the active control site (local or
remote).
In addition the P437 offers Measured Value Panels, which display the measured
values relevant at a given time.
During normal power system operation; the Bay Panel or if activated the
Operation Panel is displayed. If the Operation Panel is activated as an event
occurs, the display switches to the appropriate Event Panel provided that
measured values have been selected for the Event Panels. In the event of
overload or ground fault events, the display will automatically switch to the
Operation Panel at the end of the event. In the event of a fault, the Fault Panel
remains active until the LED indicators or the fault memories are reset.
If the change enabling command has been issued (LOC: Param. change
e nabl.) it will be cancelled after the time period, defined by setting LOC: Holdtime for Panels has elapsed and the Bay Panel will be called up.

3-4

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.3.1

Operation Panel
The Operation Panel is displayed after the set return time has elapsed, provided
that at least one measured value has been configured.
The user can select which of the measured operating values will be displayed on
the Operation Panel by means of an m out of n parameter. When more
measured operating values are selected for display than the LC display can
accommodate, then the display will either switch to the next set of measured
operating values at intervals defined by the setting for LOC: Hold-time for
Pa nels or when the appropriate key on the local control panel is pressed.

LOC:
Fct. Operation Panel
[ 053 007 ]
Measured value 1

m out of n

Measured value 2
Measured value 3
Measured value N
Selected meas. val.

FT_RC:
Record. in progress
[ 035 000 ]

S1 1

LOC:
Autom. return time
[ 003 014 ]

LOC:
Autom. return time

LOC:
Hold-time for Panels
[ 031 075 ]

LOC:
Hold-time for Panels

R1

OL_RC:
Record. in progress
[ 035 003 ]

Operation Panel

MAIN:
General reset USER
[ 003 002 ]
1: execute

MAIN:
General reset EXT
[ 005 255 ]
FT_RC:
Reset record. USER
[ 003 006 ]
1: execute
FT_RC:
Reset record. EXT
[ 005 243 ]
MAIN:
Reset LED
306 020

47Z1301A

Fig. 3-2: Operation Panel.

P437/EN M/R-11-A // P437311650

3-5

P437
3.3.2

3 Operation

Fault Panel
The Fault Panel is displayed in place of another data panel when there is a fault,
provided that at least one measured value has been configured. The Fault Panel
remains on display until the LED indicators or the fault memories are cleared.
The user can select the measured fault values that will be displayed on the Fault
Panel by setting an m out of n parameter. When more measured fault values
are selected for display than the LC display can accommodate, then the display
will either switch to the next set of measured fault values at intervals defined by
the setting for LOC : Hold-time for P ane ls or when the appropriate key on the
local control panel is pressed.

LOC:
Fct. Fault Panel
[ 053 003 ]
Measured value 1

m out of n

Measured value 2
Measured value 3
Measured value N
Selected meas. val.
LOC:
Hold-time for Panels
[ 031 075 ]

MAIN:
General reset USER
[ 003 002 ]
1: execute

Fault Panel

MAIN:
General reset EXT
[ 005 255 ]
FT_RC:
Reset record. USER
[ 003 006 ]
1: execute
FT_RC:
Reset record. EXT
[ 005 243 ]
MAIN:
Reset LED

306 020

50Z01EJA

Fig. 3-3: Fault panel.

3-6

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.3.3

Overload Panel
The Overload Panel is automatically displayed in place of another data panel
when there is an overload, provided that at least one measured value has been
configured. The Overload Panel remains on display until the overload ends,
unless a fault occurs. In this case the display switches to the Fault Panel.
The user can select the measured values that will be displayed on the Overload
Panel by setting a m out of n parameter. When more measured fault values are
selected for display than the LC display can accommodate, then the display will
either switch to the next set of measured fault values at intervals defined by the
setting for LOC : Hol d-time for P ane ls or when the appropriate key on the
local control panel is pressed.

LOC:
Fct. Overload Panel
[ 053 005 ]
Measured value 1

m out of n

Measured value 2
Measured value 3
Measured value n
Select. meas. values
LOC:
Hold-time for Panels
[ 031 075 ]
R
MAIN:
General reset USER
[ 003 002 ]
1: execute

Overload Panel

MAIN:
General reset EXT
[ 005 255 ]
OL_RC:
Reset record. USER
[ 100 003 ]
1: execute
OL_RC:
Reset record. EXT
[ 005 241 ]
MAIN:
Reset LED
306 020

50Z0140A

Fig. 3-4: Overload Panel.

3.3.4

Configurable Clear Key


, to which one or more reset functions can be
The P437 has a Clear key
assigned by selecting the required functions at L OC : Assignment rese t ke y.
Details on the functions' resetting features are given in Section 3.12.12, (p. 3106).

P437/EN M/R-11-A // P437311650

3-7

P437

3.4

3 Operation

Serial Interfaces
The P437 has a PC interface as a standard component. Communication module A
is optional and can be provided with one or two communication channels
depending on the design version. Communication between the P437 and the
control stations computer is through the communication module A. Setting and
interrogation is possible through all the P437's interfaces.
If the communication module A with two communication channels is installed,
settings for two communication interfaces will be available. The setting of
communication interface 1 (COMM1) may be assigned to the physical
communication channels 1 or 2 (see Section 3.12.13, (p. 3-109)). If the COMM1
settings have been assigned to communication channel 2, then the settings of
communication interface 2 (COMM2) will automatically be active for
communication channel 1.
COMM2 can only be used to transmit data to and from the P437 if its PC interface
has been de-activated. As soon as the PC interface is used to transmit data,
COMM2 becomes dead. It will only be enabled again when the time-out
period for the PC interface has elapsed.
If tests are run on the P437, the user is advised to activate the test mode. In this
way the PC or the control system will recognize all incoming test signals
accordingly (see Section 3.12.14, (p. 3-110)).

3-8

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.4.1

PC Interface (Function Group PC)


Communication between the P437 and a PC is through the PC interface. In order
for data transfer between the P437 and the PC to function, several settings must
be made in the P437.
There is support software available as an accessory for P437 control.

PC:
Bay address
[ 003 068 ]
PC:
Device address
[ 003 069 ]
PC:
Baud rate
[ 003 081 ]
PC:
Parity bit
[ 003 181 ]
PC:
Spontan. sig. enable
[ 003 187 ]
PC:
Select. spontan.sig.
[ 003 189 ]
PC:
Transm.enab.cycl.dat
[ 003 084 ]
PC:
Cycl. data ILS tel.
[ 003 185 ]
PC:
Delta V
[ 003 055 ]
PC:
Delta I
[ 003 056 ]
PC:
Sig./meas.val.block.
[ 003 086 ]

PC:
Delta P
[ 003 059 ]
0
1

0: No

PC:
Delta f
[ 003 057 ]
PC:
Delta meas.v.ILS tel
[ 003 155 ]

1: Yes

PC:
Delta t
[ 003 058 ]

MAIN:
Prot. ext. disabled
[ 038 046 ]

PC:
Time-out
[ 003 188 ]

PC:
Command blocking
[ 003 182 ]
0
1
0: No
1: Yes

PC interface
MAIN:
Test mode
[ 037 071 ]

19Z80ECA

Fig. 3-5: PC interface settings.

P437/EN M/R-11-A // P437311650

3-9

P437
3.4.2

3 Operation

Communication Interface 1 (Function Group COMM1)


There are several different interface protocols available at the communication
interface 1. The following user-selected interface protocols are available for use
with the P437:

IEC 608705103, "Transmission protocols - Companion standard for the


informative interface of protection equipment, first edition, 1997-12
(corresponds to VDEW / ZVEI Recommendation, Protection communication
companion standard 1, compatibility level 2, February 1995 edition) with
additions covering control and monitoring

IEC 8705101, "Telecontrol equipment and systems Part 5: Transmission


protocols Section 101 Companion standard for basic telecontrol tasks,"
first edition 199511

ILSC, internal protocol of Schneider Electric

MODBUS

DNP 3.0

COURIER

In order for data transfer to function properly, several settings must be made in
the P437.
Communication interface 1 can be blocked through a binary signal input. In
addition, a signal or measured-data block can also be imposed through a binary
signal input.

3-10

P437/EN M/R-11-A // P437311650

P437

3 Operation

COMM1:
Command block. USER
[ 003 172 ]

0
1
COMM1:
Command blocking
[ 003 174 ]

0: No
COMM1:
Command block. EXT
[ 003 173 ]

1: Yes

COMM1:
Basic IEC870-5 enabl
[ 003 215 ]

COMM1:
Communicat. protocol
[ 003 167 ]
0
1

0: No
1: Yes

COMM1:
Addit. -101 enable
[ 003 216 ]

Selected protocol

COMM1:
Selected protocol
304 415

1
0: No
1: Yes

COMM1:
Addit. ILS enable
[ 003 217 ]

0
1
0: No
1: Yes

COMM1:
MODBUS enable
[ 003 220 ]

0
1
0: No
1: Yes

COMM1:
DNP3 enable
[ 003 231 ]

0
1
0: No
1: Yes

COMM1:
COURIER enable
[ 103 040 ]

0
1
0: No
1: Yes

64Z51FEA

Fig. 3-6: Communication interface 1, selecting the interface protocol.

P437/EN M/R-11-A // P437311650

3-11

P437

3 Operation

COMM1:
-103 prot. variant

COMM1:
Select. spontan.sig.

[ 003 178 ]

[ 003 179 ]

COMM1:
Line idle state

COMM1:
Transm.enab.cycl.dat

[ 003 165 ]

[ 003 074 ]

COMM1:
Baud rate

COMM1:
Cycl. data ILS tel.

[ 003 071 ]

[ 003 175 ]

COMM1:
Parity bit

COMM1:
Delta V

[ 003 171 ]

[ 003 050 ]

COMM1:
Dead time monitoring

COMM1:
Delta I

[ 003 176 ]

[ 003 051 ]

COMM1:
Mon. time polling

COMM1:
Delta P

[ 003 202 ]

[ 003 054 ]

COMM1:
Octet comm. address

COMM1:
Delta f

[ 003 072 ]

[ 003 052 ]

COMM1:
Test monitor on

COMM1:
Delta meas.v.ILS tel

[ 003 166 ]

[ 003 150 ]

COMM1:
Name of manufacturer

COMM1:
Delta t

[ 003 161 ]

[ 003 053 ]

COMM1:
Octet address ASDU

COMM1:
Delta t (energy)

[ 003 073 ]

[ 003 151 ]

COMM1:
Spontan. sig. enable

COMM1:
Contin. general scan

[ 003 177 ]

[ 003 077 ]

COMM1:
Selected protocol
304 415

COMM1:
IEC 870-5-103
[ 003 219 ]

COMM1:
General enable USER
[ 003 170 ]
1: Yes

COMM1:
Command blocking
[ 003 174 ]
MAIN:
Test mode
[ 037 071 ]

COMM1:
Communication error

Communic. interface

304 422

COMM1:
Sig./meas.block.USER
[ 003 076 ]
0
1
0: No

COMM1:
Sig./meas.val.block.

1: Yes

[ 037 075 ]

COMM1:
Sig./meas. block EXT
[ 037 074 ]
MAIN:
Prot. ext. disabled
[ 038 046 ]

12Z62FFA

Fig. 3-7: Communication interface 1, settings for the IEC 608705-103 interface protocol.

3-12

P437/EN M/R-11-A // P437311650

P437

3 Operation

COMM1:
Selected protocol
304 415

COMM1:
IEC 870-5-101
[ 003 218 ]

COMM1:
Line idle state
[ 003 165 ]

COMM1:
Delta t
[ 003 053 ]

COMM1:
Baud rate
[ 003 071 ]

COMM1:
Delta t (energy)
[ 003 151 ]

COMM1:
Parity bit
[ 003 171 ]

COMM1:
Contin. general scan
[ 003 077 ]

COMM1:
Dead time monitoring
[ 003 176 ]

COMM1:
Comm. address length
[ 003 201 ]

COMM1:
Mon. time polling
[ 003 202 ]

COMM1:
Octet 2 comm. addr.
[ 003 200 ]

COMM1:
Octet comm. address
[ 003 072 ]

COMM1:
Cause transm. length
[ 003 192 ]

COMM1:
Test monitor on
[ 003 166 ]

COMM1:
Address length ASDU
[ 003 193 ]

COMM1:
Name of manufacturer
[ 003 161 ]

COMM1:
Octet 2 addr. ASDU
[ 003 194 ]

COMM1:
Octet address ASDU
[ 003 073 ]

COMM1:
Addr.length inf.obj.
[ 003 196 ]

COMM1:
Spontan. sig. enable
[ 003 177 ]

COMM1:
Oct.3 addr. inf.obj.
[ 003 197 ]

COMM1:
Select. spontan.sig.
[ 003 179 ]

COMM1:
Inf.No.<->funct.type
[ 003 195 ]

COMM1:
Transm.enab.cycl.dat
[ 003 074 ]

COMM1:
Time tag length
[ 003 198 ]

COMM1:
Cycl. data ILS tel.
[ 003 175 ]

COMM1:
ASDU1 / ASDU20 conv.
[ 003 190 ]

COMM1:
Delta V
[ 003 050 ]

COMM1:
ASDU2 conversion
[ 003 191 ]

COMM1:
Delta I
[ 003 051 ]

COMM1:
Initializ. signal
[ 003 199 ]

COMM1:
Delta P
[ 003 054 ]

COMM1:
Balanced operation
[ 003 226 ]

COMM1:
Delta f
[ 003 052 ]

COMM1:
Direction bit
[ 003 227 ]

COMM1:
Delta meas.v.ILS tel
[ 003 150 ]

COMM1:
Time-out interval
[ 003 228 ]

COMM1:
General enable USER
[ 003 170 ]
1: Yes

COMM1:
Command blocking
[ 003 174 ]
MAIN:
Test mode
[ 037 071 ]

COMM1:
Sig./meas.block.USER
[ 003 076 ]
0

Comm. interface

1
0: No
1: Yes

COMM1:
Communication error
304 422

COMM1:
Sig./meas.val.block.
[ 037 075 ]

COMM1:
Sig./meas. block EXT
[ 037 074 ]
MAIN:
Prot. ext. disabled
[ 038 046 ]

19Z51FGA

Fig. 3-8: Communication interface 1, settings for the IEC 870-5-101 interface protocol.

P437/EN M/R-11-A // P437311650

3-13

P437

3 Operation

COMM1:
Line idle state
[ 003 165 ]

COMM1:
Transm.enab.cycl.dat
[ 003 074 ]

COMM1:
Baud rate
[ 003 071 ]

COMM1:
Cycl. data ILS tel.
[ 003 175 ]

COMM1:
Parity bit
[ 003 171 ]

COMM1:
Delta V
[ 003 050 ]

COMM1:
Dead time monitoring
[ 003 176 ]

COMM1:
Delta I
[ 003 051 ]

COMM1:
Mon. time polling
[ 003 202 ]

COMM1:
Delta P
[ 003 054 ]

COMM1:
Octet comm. address
[ 003 072 ]

COMM1:
Delta f
[ 003 052 ]

COMM1:
Test monitor on
[ 003 166 ]

COMM1:
Delta meas.v.ILS tel
[ 003 150 ]

COMM1:
Name of manufacturer
[ 003 161 ]

COMM1:
Delta t
[ 003 053 ]

COMM1:
Octet address ASDU
[ 003 073 ]

COMM1:
Delta t (energy)
[ 003 151 ]

COMM1:
Spontan. sig. enable
[ 003 177 ]

COMM1:
Contin. general scan
[ 003 077 ]

COMM1:
Select. spontan.sig.
[ 003 179 ]
COMM1:
Selected protocol
304 415

COMM1:
IEC 870-5, ILS
[ 003 221 ]

COMM1:
General enable USER
[ 003 170 ]
1: Yes
COMM1:
Command blocking
[ 003 174 ]

Comm. interface

COMM1:
Communication error
304 422

MAIN:
Test mode
[ 037 071 ]

COMM1:
Sig./meas.block.USER
[ 003 076 ]
0
1
0: No
1: Yes

COMM1:
Sig./meas.val.block.
[ 037 075 ]

COMM1:
Sig./meas. block EXT
[ 037 074 ]
MAIN:
Prot. ext. disabled
[ 038 046 ]

19Z51FHA

Fig. 3-9: Communication interface 1, settings for the ILS-C interface protocol.

3-14

P437/EN M/R-11-A // P437311650

P437

3 Operation

COMM1:
MODBUS prot. variant
[ 003 214 ]

COMM1:
Test monitor on
[ 003 166 ]

COMM1:
Line idle state
[ 003 165 ]

COMM1:
Reg.asg. selec. cmds
[ 003 210 ]

COMM1:
Baud rate
[ 003 071 ]

COMM1:
Reg.asg. selec. sig.
[ 003 211 ]

COMM1:
Parity bit
[ 003 171 ]

COMM1:
Reg.asg. sel. m.val.
[ 003 212 ]

COMM1:
Dead time monitoring
[ 003 176 ]

COMM1:
Reg.asg. sel. param.
[ 003 213 ]

COMM1:
Mon. time polling
[ 003 202 ]

COMM1:
Delta t (MODBUS)
[ 003 152 ]

COMM1:
Octet comm. address
[ 003 072 ]

COMM1:
Autom.event confirm.
[ 003 249 ]

COMM1:
Selected protocol
304 415

COMM1:
MODBUS
[ 003 223 ]

COMM1:
General enable USER
[ 003 170 ]
1: Yes
Commun. interface
COMM1:
Command blocking
[ 003 174 ]

COMM1:
Communication error
304 422

MAIN:
Test mode
[ 037 071 ]

19Z50FJB

Fig. 3-10: Communication interface 1, settings for the MODBUS protocol.

P437/EN M/R-11-A // P437311650

3-15

P437

COMM1:
Selected protocol

3 Operation

COMM1:
Line idle state
[ 003 165 ]

COMM1:
Link Confirm.Timeout
[ 003 244 ]

COMM1:
Baud rate
[ 003 071 ]

COMM1:
Link Max. Retries
[ 003 245 ]

COMM1:
Parity bit
[ 003 171 ]

COMM1:
Appl.Confirm.Timeout
[ 003 246 ]

COMM1:
Dead time monitoring
[ 003 176 ]

COMM1:
Appl. Need Time Del.
[ 003 247 ]

COMM1:
Mon. time polling
[ 003 202 ]

COMM1:
Ind./cl. bin. inputs
[ 003 232 ]

COMM1:
Octet comm. address
[ 003 072 ]

COMM1:
Ind./cl. bin.outputs
[ 003 233 ]

COMM1:
Oct.2 comm.addr.DNP3
[ 003 240 ]

COMM1:
Ind./cl. bin. count.
[ 003 234 ]

COMM1:
Test monitor on
[ 003 166 ]

COMM1:
Ind./cl. analog inp.
[ 003 235 ]

COMM1:
Phys. Charact. Delay
[ 003 241 ]

COMM1:
Ind./cl. analog outp
[ 003 236 ]

COMM1:
Phys. Char. Timeout
[ 003 242 ]

COMM1:
Delta meas.v. (DNP3)
[ 003 250 ]

COMM1:
Link Confirm. Mode
[ 003 243 ]

COMM1:
Delta t (DNP3)
[ 003 248 ]

304 415

COMM1:
DNP3
[ 003 230 ]

COMM1:
General enable USER
[ 003 170 ]
1: Yes

COMM1:
Command blocking
[ 003 174 ]

MAIN:
Test mode
[ 037 071 ]

Commun. interface

COMM1:
Communication error
304 422

19Z50AZA

Fig. 3-11: Communication interface 1, settings for the DNP 3.0 protocol.

3-16

P437/EN M/R-11-A // P437311650

P437

3 Operation

COMM1:
Selected protocol
304 415

COMM1:
COURIER
[ 103 041 ]

COMM1:
General enable USER
[ 003 170 ]

COMM1:
Line idle state
[ 003 165 ]

COMM1:
Test monitor on
[ 003 166 ]

COMM1:
Baud rate
[ 003 071 ]

COMM1:
Command selection
[ 103 042 ]

COMM1:
Parity bit
[ 003 171 ]

COMM1:
Signal selection
[ 103 043 ]

COMM1:
Dead time monitoring
[ 003 176 ]

COMM1:
Meas. val. selection
[ 103 044 ]

COMM1:
Mon. time polling
[ 003 202 ]

COMM1:
Parameter selection
[ 103 045 ]

COMM1:
Octet comm. address
[ 003 072 ]

COMM1:
Delta t (COURIER)
[ 103 046 ]

0
1
0: No
1: Yes
COMM1:
Command blocking
[ 003 174 ]

MAIN:
Test mode
[ 037 071 ]

Commun. interface

COMM1:
Communication error
304 422

19Z51BAA

Fig. 3-12: Communication interface 1, settings for the COURIER protocol.

P437/EN M/R-11-A // P437311650

3-17

P437
3.4.2.1

3 Operation

COMM1 Checking Spontaneous Signals


For interface protocols based on IEC 608705103, IEC 8705101, or ILS-C it is
possible to select a signal for test purposes. The transmission of this signal to the
control station as sig. start or sig. end can then be triggered using setting
parameters.

COMM1:
Sel.spontan.sig.test
[ 003 180 ]

Signal 1
Signal 2
Signal 3
Signal n
Selected signals

COMM1:
Test spont.sig.start
[ 003 184 ]

COMM1:
Spontan. sig. start
[ --- --- ]

1
0: don't execute
1: execute

COMM1:
Test spont.sig. end
[ 003 186 ]

COMM1:
Spontan. sig. end
[ --- --- ]

1
0: don't execute
1: execute

48Z50FKA

Fig. 3-13: COMM1 Checking spontaneous signals.

3-18

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.4.3

Communication Interface 2 (Function Group COMM2)


Communication interface 2 supports the IEC 608705103 interface protocol.
In order for data transfer to function properly, several settings must be made in
the P437.

COMM2:
Line idle state
[ 103 165 ]
COMM2:
Baud rate
[ 103 071 ]
COMM2:
Parity bit
[ 103 171 ]
COMM2:
Dead time monitoring
[ 103 176 ]
COMM2:
Mon. time polling
[ 103 202 ]
COMM2:
Octet comm. address
[ 103 072 ]
COMM2:
Name of manufacturer
[ 103 161]
COMM2:
Octet address ASDU
[ 103 073 ]
COMM2:
Spontan. sig. enable
[ 103 177 ]
COMM2:
Select. spontan.sig.

COMM2:
General enable USER
[ 103 170 ]

[ 103 179 ]
0
1

0: No

COMM2:
Transm.enab.cycl.dat
[ 103 074 ]
COMM2:
Cycl. data ILS tel.
[ 103 175 ]

1: Yes

COMM2:
Delta V
[ 103 050 ]
COMM2:
Delta I
[ 103 051 ]

COMM2:
Sig./meas.block.USER
[ 103 076 ]

COMM2:
Delta P
[ 103 054 ]
0

COMM2:
Delta f

[ 103 052 ]

0: No

COMM2:
Delta meas.v.ILS tel

1: Yes

[ 103 150 ]
COMM2:
Delta t

MAIN:
Prot. ext. disabled

[ 103 053 ]

[ 038 046 ]

COMM2:
Command block. USER
[ 103 172 ]
0
1
0: No
1: Yes
Commun. interface
MAIN:
Test mode
[ 037 071 ]

40Z5070A

Fig. 3-14: Settings for communication interface 2.

P437/EN M/R-11-A // P437311650

3-19

P437
3.4.3.1

3 Operation

COMM2 Checking Spontaneous Signals


It is possible to select a signal for test purposes. The transmission of this signal to
the control station as sig. start or sig. end can then be triggered via the local
control panel.

COMM2:
Sel.spontan.sig.test
[ 103 180 ]

Signal 1
Signal 2
Signal 3
Signal n
Selected signals

COMM2:
Test spont.sig.start
[ 103 184 ]

COMM2:
Spontan. sig. start
[ --- --- ]

1
0: don't execute
1: execute

COMM2:
Test spont.sig. end
[ 103 186 ]

COMM2:
Spontan. sig. end
[ --- --- ]

1
0: don't execute
1: execute

48Z50FLA

Fig. 3-15: COMM2 Checking spontaneous signals.

3-20

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.4.4

InterMiCOM Protective Interfaces (Function Groups COMM3,


COMM4)

3.4.4.1

Application
The InterMiCOM protection signaling interface is designed to establish a digital
communication link between two MiCOM devices over which up to 8 binary
protection signals may be transmitted. Whereas communication interfaces 1
(Section 3.4.2, (p. 3-10)) and 2 (Section 3.4.3, (p. 3-19)) are designed as
information interfaces to connect to data acquisition subsystems and for remote
access, the InterMiCOM interface (also called communication interfaces 3 and 4)
is designed as a protection signaling interface that will transmit real time signals.
Its main application is to transmit signals from protective signaling (function
group PSIG). In addition, any other internal or external binary signals may also be
transmitted.

3.4.4.2

Physical Medium
COMM3 and COMM4 are provided as asynchronous, full-duplex communication
interfaces. To transmit data the following physical media are available for each:
Direct link without use of external supplementary equipment:

Glass fiber (e.g. via 2 x G62.5/125 up to max. 1.4 km)

Twisted pair (RS 422 up to max. 1.2 km)

Use of external transmission equipment:

FO module (e.g. OZD 485 BFOC1300 / Hirschmann up to max. 8/14/20 km)

Universal modem (e.g. PZ 511 via twisted pair 2x2x0.5 mm up to max.


10 km)

Voice frequency modem (e.g. TD32 DC / Westermo up to max. 20 km)

Digital network:

3.4.4.3

Asynchronous data interface of primary multiplexing equipment

Configuration and Enabling


In order to use InterMiCOM, the communication interface COMM3 (and/or
COMM4, depending on order options and application) has to be configured using
the parameter C OMM3 : F un ction grou p COMM3 (COMM4: Fu nct ion
group C OMM4). This setting parameter is only visible if the relevant optional
communication module is fitted. After activation of COMM3 (COMM4), all
addresses associated to this function group (setting parameters, binary state
signals etc.) become visible.
The function can then be enabled or disabled by setting COMM3: General
e nable U SER (CO MM4: Gen eral en able USER).

3.4.4.4

Telegram Configuration
For the remainder of this COMM3 / COMM4 description, COMM3 represents COMM4
as well, this means that the description is also valid for COMM4.
The parameter addresses given apply to COMM3. The corresponding addresses for
function group COMM4 are given in Chapter 7, (p. 7-1) and Chapter 8, (p. 81).

The communication baud rate is settable (COMM3 : Baud rat e) to adapt to the
transmission channel requirements. Sending and receiving addresses

P437/EN M/R-11-A // P437311650

3-21

P437

3 Operation

COMM 3: S ource ad dres s and COMM3: Rece i ving addr ess can be set to
different values, thus avoiding that the P437 communicates with itself.
The InterMiCOM protection signaling interface provides independent transmission
of eight binary signals in each direction. For the send signals COMM3: Fct .
a ssignm. send 1, ) any signal from the selection table of the binary outputs
(OUTP) can be chosen. For the receive signals (COMM3 : F ct . assignm . re c.
1, ) any signal from the selection table of the binary inputs (INP) can be
chosen.
For each receive signal, an individual operating mode can be set
C OMM3: Op er. mode re ce ive 1, ), thus defining the required checks for
accepting the received binary signal. In addition a specifically selected telegram
structure subdivides the 8 binary signals into two groups. The signal encoding
along with the set operating mode for the telegram check defines the actual
balance of Speed, Security and Dependability for each signal:

Binary signals 1 to 4:
Operating mode settable to Blocking or Direct intertrip

Binary signals 5 to 8:
Operating mode settable to Permissive or Direct intertrip

EN 608341 classifies 3 categories of command based teleprotection schemes


according to their specific requirements (see Fig. 3-16, (p. 3-23)). By selection
of a binary signal and by setting its operating mode appropriately, these
requirements can be fulfilled as follows:
Direct transfer trip or intertripping:

Preference:

Security.

Implication:

No spurious pickup in the presence of channel noise.

Recommended setting:

Select binary signal from groups 1 to 4 or 5 to 8 and set operating


mode Direct intertrip.

Permissive teleprotection scheme:

Preference:

Dependability.

Implication:

Maximizes probability of signal transmission in the presence of


channel noise.

Recommended setting:

Select binary signal from group 5 to 8 and set operating mode


Permissive.

Blocking teleprotection scheme:

Preference:

Speed.

Implication:

Fast peer-to-peer signal transfer.

Recommended setting:

Select binary signal from group 1 to 4 and set operating mode


Blocking.

3-22

P437/EN M/R-11-A // P437311650

P437

3 Operation

Speed

Blocking

Permissive
slow
low

high

Security

Direct
Intertrip

high

Dependability
47Z1030A

Fig. 3-16: Comparison of speed, security and dependability offered by the three operating modes.

3.4.4.5

Communication Monitoring
Timer stage C OMM3 : Time -out comm.f aul t is used for monitoring the
transmission channel (this timer is re-triggered with each complete and correct
received telegram). The wide setting range allows adaptation to the actual
channel transmission times and above all this is needed for time-critical schemes
such as the blocking scheme. After the timer has elapsed, signals
COMM3: C ommu nicati ons fau lt and SFMON: Commun ic.fau lt COMM3
are issued and the received signals are automatically set to their user-defined
default values (COMM3: De fault value rec. 1, , CO MM3: D efault v alue
rec. 8). As the main application for this protective signaling the fault signal may
be mapped to the corresponding input signal in function group PSIG with the
COMM3: Si g.asg. comm.f ault setting.
Timer stage COMM3 : Time -ou t link fail .. is used to determine a persistent
failure of the data transmission channel. After the timer has elapsed, signals
COMM3: Comm. link fai l ur e and SFMON: Comm.lin k fail.COMM3 are
issued.

P437/EN M/R-11-A // P437311650

3-23

P437

3 Operation

Message
received

Character frame &


Source address check

Blocking signals
accepted

Telegram
receive check

Permissive signals
accepted

Telegram CRC check

Direct Trip signals


accepted

(Re)start of the
monitoring
timer stages

COMM3:
Time-out comm.fault
[ 120 033 ]

COMM3:
Communications fault
[ 120 043 ]

COMM3:
Time-out link fail.
[ 120 035 ]

COMM3:
Comm. link failure
[ 120 044 ]

47Z1031B

Fig. 3-17: Message processing and communication monitoring.

3-24

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.4.4.6

Supervision of Communication Link Quality


After a syntax check of each received message, InterMiCOM updates the ratio of
incorrectly received messages, based on a total of the last 1000 received
messages. The result is provided as an updating measurand COMM3: No. tel.
err ors p.u.. and the overall maximum ratio can be read from
COMM 3: N o.t .err.,max,s t or ed.
If the set threshold C OMM3 : Limi t te le gr. er rors is exceeded the
corresponding signals C OMM3 : L im.e xcee d. ,te l.er r. and
SFMON: Lim.e xc.te l.e r. COMM3 will be issued. All corrupted telegrams are
counted (C OMM3: No. tel e gram errors). This counter as well as the stored
maximum ratio of corrupted messages can be reset via COMM3: R set
No.t lg.e rr.USE R (as well as via the binary signal CO MM3: Res et
No.t lg.e rr.EXT).

3.4.4.7

Commissioning Tools
The actual values of send and receive signals can be read from the P437 as
physical state signals (COMM3: State se nd 1 and C OMM3 : Stat e re ce iv e
1, with x = 1 to 8). In addition, InterMiCOM provides 2 test facilities for
commissioning of the protection interface.
For a loop-back test, the send output is directly linked back to the receive input.
After setting the bit pattern wanted (as an equivalent decimal number at
C OMM3: Loop back se nd) the test can be triggered via COMM3: Loop back
t est. This bit pattern is sent for the duration of the hold time set at
C OMM3: Hold ti me for te st. For this test only, the source address is set to
'0'; this value is not used for regular end-to-end communication. The test result
can be checked as long as the hold-time is running by reading the measured
operating data C OMM3 : L oop back re su lt and C OMM3: L oop back
receiv e. As soon as the hold-time has expired, the loopback test is terminated
and InterMiCOM reverts to the normal sending mode (e.g. sending the actual
values of the configured send signals, using the set source address).
Thus, in case of problems with the InterMiCOM protection signaling interface, the
loopback test can be used to verify or to exclude a defective device. The
transmission channel including the receiving device can be checked manually by
setting individual binary signals (COMM3: Se nd s ignal for t est) to userdefined test values (C OMM3: L og. state f or te st). After triggering the test by
C OMM3: Send signal, te st, the preset binary signal is sent with the preset
value for the set hold time COMM3: Hold time for t est. The 7 remaining
binary signals are not affected by this test procedure and remain to be sent with
their actual values. During the hold time, a received signal can be checked at the
receiving device, e.g. by reading the physical state signal. After the hold time
has expired, the test mode is reset automatically and the actual values of all
8 signals are transmitted again.

P437/EN M/R-11-A // P437311650

3-25

P437
3.4.5

3 Operation

Communication Interface IEC 61850 (Function Groups IEC, GOOSE


and GSSE)
The IEC 61850 communication protocol is implemented by these function groups
and the Ethernet module.
Function group IEC is only available as an alternative to function group COMM1
(hardware ordering option!).

3.4.5.1

Communication Interface IEC 61850 (Function Group IEC)


The P437 offers as an ordering option a communication protocol according to the
Ethernet based IEC 61850 protocol.

3.4.5.1.1

IEC 61850
IEC 61850 was created jointly by users and manufacturers as an international
standard. The main target of IEC 61850 is interoperability of devices. This
includes the capability of two or more intelligent electronic devices (IED),
manufactured by the same company or different companies, to exchange data
for combined operation.
This communication standard IEC 61850 has now created an open and common
basis for communication from the process control level down to the network
control level, for the exchange of signals, data, measured values and commands.
For a standardized description of all information and services available in a field
device a data model, which lists all visible functions, is created. Such a data
model, specifically created for each device, is used as a basis for an exchange of
data between the devices and all process control installations interested in such
information. In order to facilitate engineering at the process control level a
standardized description file of the device, based on XML, is created with the
help of the data model. This file can be imported and processed further by the
relevant configuration program used by the process control device. This makes
possible an automated creation of process variables, substations and signal
images.
Available is the following documentation providing the description of the
IEC 61850 data model which is used with the P437:

ICD file based on XML in the SCL (Substation Configuration Description


Language) with a description of data, properties and services, available
from the P437, that are to be imported into the configuration tool IED
Configurator or into a system configurator.

PICS_MICS_ADL file with the following contents:

3-26

PICS (Protocol Implementation Conformance Statement) with an


overview of available services.
MICS (Model Implementation Conformance Statement) with an overview
of available object types.
ADL (Address Assignment List) with an overview of the assignment of
parameter addresses (signals, measuring values, commands, etc.) used
by the P437 with the device data model as per IEC 61850.

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.4.5.1.2

Ethernet Module
The optional Ethernet module provides an RJ45 connection and a fiber optic
interface where an Ethernet network can be connected. The selection which of
the two interfaces is to be used to connect to the Ethernet network is made by
setting the parameter [ IC]: Me di a.
Setting parameters identified by [ I C ] : in the IEC function group are set with the
IED Configurator. They cannot be modified from the local control panel (HMI) or
with the operating program.

There are two ordering variants available for the fiber-optic interface: the ST
connector and the SC connector both for 100 Mbit/s and 1300 nm (a third variant
ST connector for 100 Mbit/s and 1300 nm is pending). The RJ45 connector
supports 10 Mbit/s and 100 Mbit/s.
The optional Ethernet module additionally provides an RS485 interface for
remote access with the MiCOM S1 support software (function group COMM2).
The P437 may be equipped with the optional Ethernet module only as an
alternative to the standard optional communication module. Therefore the
Ethernet-based communication protocol IEC 61850 is available only as an
alternative to function group COMM1.

3.4.5.1.3

Configuration and Enabling


The IEC function group can be included in the configuration by setting the
parameter I EC : Fun ction group IE C. This parameter is only visible if the
optional Ethernet communication module is fitted to the P437. After having
included the parameter IEC: Functi on group IEC in the configuration the
parameter IEC : Gen eral en abl e USER and the parameters for internal clock
tracking are visible and freely configurable.
The function can then be enabled or disabled by setting COMM3 : Ge ne ral
enab le USER.
The setting parameters from the IEC function group as well as the related
function groups GOOSE and GSSE are not automatically active in the P437. The
P437 features two memory "banks" one of which includes the active setting
parameters. The other memory bank is used with the configuration procedure for
parameters from the IED Configurator and the operating system. Specific projectrelated extensions of the IEC 61850 parameters from the IED Configurator are
loaded into the P437 by downloading a .MCL file. The inactive communication
parameters are activated by executing the command IE C: Switch Config.
Bank. This command may also be issued from the IED Configurator.

P437/EN M/R-11-A // P437311650

3-27

P437

3 Operation

System configurator

PACiS SCE

.iid
.scd

.icd

IED Configurator

IED Configurator

S&R 103

.mcl

.x3v

Operating program

19Z7001B

Fig. 3-18: Configuration according to IEC 61850-6.

3-28

P437/EN M/R-11-A // P437311650

P437

3 Operation

IEC 61850 parameters separate from protection device parameters!

IED

Control PC

Processor module
Operating program
Device
parameters
Parameter
switch

Parameter download

Ethernet module

IED
Configurator

Parameter upload

IEC 61850
parameter

IEC 61850
parameter

Bank 1

Bank 2

Bank switching to enable the


device parameters

New approach to IED parameter management


19Z7002B

Fig. 3-19: Saving configuration parameters.

3.4.5.1.4

Client Log-on
Communication in Ethernet no longer occurs in a restrictive master slave system,
as is common with other protocols. Instead, server or client functionalities, as
defined in the Abstract Communication Service Interface (ACSI, IEC 6187072),
are assigned to the devices. A server is always that device which provides
information to other devices. A client may log on to this server in order to receive
information, for instance reports. In its function as server the P437 can supply
up to 16 clients, linked into the network, with spontaneous or cyclic information.

3.4.5.1.5

Clock Synchronization
With IEC 61850 clock synchronization is effected via the SNTP protocol, defined
as standard for Ethernet. Here the P437 functions as an SNTP client.
For clock synchronization one can choose between the operating modes Anycast
from SNTP Server or Request from Server. With the first operating mode
synchronization occurs by a broadcast message sent from the SNTP server to all
devices in the network, and in the second operating mode the P437 requests a
device-specific time signal during a settable cycle.
Two SNTP servers may be set. In this case, clock synchronization is preferably
performed by the first server. The second server is only reverted to if no signal is
received from the first server.
When looking at the source priority for clock synchronization, which is set at the
MAIN function then, by selecting COMM1, synchronization per IEC 61850 is
automatically active but only if this communication protocol is applied.

P437/EN M/R-11-A // P437311650

3-29

P437
3.4.5.1.6

3 Operation

Generating Datasets, Reporting


The specific project related feature of the P437s communications behavior is
determined by the configuration of datasets, reports and high priority
transmission methods. A piece of information must be included in a dataset so as
to be transmitted as a signal. A dataset is a list to transmit certain data objects.
The selection of data objects and the resulting length of the dataset is
determined by the application; merely the maximum size of a dataset to be
transmitted by GOOSE (see Section 3.4.5.2, (p. 3-32)) is limited to 1500 bytes.
Data objects provided by the P437 are available for selection with a structure as
specified by IEC 61850. Within the quality descriptor for each piece of
information the invalid bit and the test bit are served according to the P437s
state; the other attributes are not set. Any number of datasets may be created
with the IED Configurator. Saving datasets at System\LLN0 is compulsory. The
knowledge of dataset content is imperative for decoding and evaluating received
signals. Configuration files possess a listing of all datasets with a description of
all data objects included.
Next to their use with high priority transmission methods (see Section 3.4.5.1.10,
(p. 3-31)) datasets are used mainly for reporting. The P437 provides up to
sixteen unbuffered reports and eight buffered reports independent of the number
of clients logged-on. Management is arranged into sixteen Unbuffered Report
Control Blocks (urcbA to urcbP) and eight Buffered Report Control Blocks (brcbA
to brcbH). Whereas with unbuffered reporting pieces of information may be lost
during a communications failure, the buffered report control blocks support a
buffered transmission which is required for the uninterrupted writing of events. A
pre-defined dataset may be assigned to each report which will then determine
which data object will be transmitted with the relevant report. Assigning datasets
is not limited; the same dataset may be referenced in various reports or even in
GOOSEs.
The P437 can serve up to sixteen clients. Each client can log-on to any number of
available reports. One unbuffered report can be allocated to max. 8 clients, and
one buffered report can be allocated to max. 4 clients. A client is then able to
activate the wanted report for himself and to set the transmission behavior to his
requirements. The system concept with intended clients must be taken into
account when datasets are assigned to the reports.
Reports are not received by the P437.

3.4.5.1.7

Transmitting Modeled Signals Not Provided by the IEC 61850 Data Model
In addition to the information included in the IEC 61850 data model an optional
number of up to 16 signals can be selected from all the signals available in the
P437 to be transmitted via reporting. A selection of state signals (shuttling to
communications) is made by setting I EC: SigGGI O1 selection. The data
object indexes defined for SigGGIO1 must follow the sequence given for the m
out of n selection for the state signals. The indexes SigGGIO1.ST.ind1 to
SigGGIO1.ST.ind16 may then be included in the datasets just as the other data
objects.

3.4.5.1.8

Single Commands
Single commands (e.g. short command, long command, persistent command)
are configured with the operating program. Sending commands to the P437 can
be carried out from all clients that have previously logged-on to the P437. But
only one command at a time is carried out. The operating mode Direct control
with normal security is provided for single commands.

3-30

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.4.5.1.9

Fault Transmission
Including fault transmission for the IEC 61850 in the configuration is only possible
with the IED Configurator.
Transmission of fault files is supported per File Transfer. COMTRADE fault files
in the P437 are transmitted uniformly either as ASCII or binary formatted files.
Fault transmission can be cancelled from the configuration.

3.4.5.1.10

High Priority Transmission of Information


Whereas normal server-client services are transmitted at the MMS and TCP/IP
level the high priority transmission of information is carried out directly at
Ethernet level. Furthermore messages in such a particular form can be received
by all participants in the relevant sub-network, independent of their server or
client function. They are deployed in instances where high speed transmission of
information is wanted between two or more devices. Applications, for example,
are reverse interlocking, transfer trip or decentralized substation interlock.
The standard IEC 61850 provides two modes for high priority transmission of
information: the GSSE and the GOOSE. The GSSE (also named UCA2-GOOSE ) is
used to transmit binary information with a simple configuration by 'bit pairs', and
it is compatible with UCA2. The GOOSE enables transmission of all data formats
available in the data model, such as binary information, integer values, two-pole
contact position signals or analog measured values. The P437 supports receipt
and evaluation of GOOSE including binary information and two-pole contact
position signals from external devices.

3.4.5.1.11

Communication with the MiCOM S1 Support Software via the Ethernet Interface
Direct access by the MiCOM S1 support software via the Ethernet interface on
the P437 may occur through the tunneling principle. Transmission is carried
out by an Ethernet Standard Protocol, but this is only supported by the
associated MiCOM S1 support software (specific manufacturer solution). Such
transmission is accomplished over the same hardware for the network, which is
used for server-client communication. Available are all the familiar functions
offered by the MiCOM S1 support software such as reading/writing of setting
parameters or retrieving stored data.

P437/EN M/R-11-A // P437311650

3-31

P437
3.4.5.2

3 Operation

Generic Object Oriented Substation Event (Function Group GOOSE)


For high priority exchange of information between individual devices (IEDs) in a
local network, the P437 provides the function group GOOSE as defined in the
standard IEC 61850. GOOSE features high-speed and secure transmission of
information for reverse interlocking, decentralized substation interlock, trip
commands, blocking, enabling, contact position signals and other signals.
GOOSE Messages are only transmitted by switches but not by routers. GOOSE
messages therefore remain in the local network to which the P437 is connected.

3.4.5.2.1

Configuration and Enabling


Function group GOOSE can be configured by setting the parameter
GOOSE: Functi on group GOOSE This parameter is only visible if the optional
Ethernet communication module is fitted to the P437. After having configured the
GOOSE all parameters associated to this function group are then visible and
ready to be configured.
Further setting parameters from function group GOOSE are set with the
IED Configurator, but they cannot be modified from the local control panel (MMI)
or with the operating program.
The function can then be enabled or disabled by setting GO OSE: General
enab le USER.

3-32

P437/EN M/R-11-A // P437311650

P437

3 Operation

Device A
IEC 61850
Mapping

S1 Studio

Device B
S1 Studio

System/GosGGIO2

GOOSE: Input 1 ... 32

GOOSE: Output 1 ... 32

System/GosGGIO2.ST.ind1 ... 32

IED Configurator

IED Configurator

System/LLN0/Dataset x

System/GosGGIO1

Pos1.stVal ... Pos32.stVal

IED Configurator
System/LLN0/gcb01 ... 08

MCL

IED Configurator

System/DevGosGGIO3

Pos1.stVal ... Pos32.stVal

Fixed assignment

S1 Studio

Ext.Dev 1 32
19Z7003A

Fig. 3-20: GOOSE configuration.

3.4.5.2.2

Sending GOOSE
The GOOSE can send up to eight different GOOSE messages which are managed
in eight GOOSE Control Blocks (gcb01 to gcb08). Information content depends on
the respective dataset assigned to GOOSE. The maximum size of a dataset to be
sent by GOOSE is limited to 1500 bytes. A control display is shown by the IED
Configurator to check this limit.
When defining the datasets for GOOSE it is advised to select the individual data
attributes and not the overlapping data objects. By this the amount of data is
kept within a limit and decoding is guaranteed on the receiving end.
In addition to the information included in the IEC 61850 data model an optional
number of up to 32 signals can be selected from all the signals available in the
P437 to be transmitted via GOOSE, as it is also possible with reporting.
Selection of binary state signals (shuttling to communications) is made by setting
GO OSE: Outp ut 1 fct.ass ig.. (or Output 2, ..., Output 32). The data object
indexes defined for SigGGIO1 must follow the function assignments for the
GOOSE outputs. The indexes GosGGIO2.ST.ind1 to GosGGIO2.ST.ind32 may then
be included in the datasets just as the other data objects.
When a state change occurs with a selected state signal or a measured value
changes which is greater than the dead band set for the relevant data point then
the complete GOOSE is sent. There will be multiple send repetitions at ascending

P437/EN M/R-11-A // P437311650

3-33

P437

3 Operation

time periods. The first send repetition occurs at the given cycle time set with the
parameter [IC]: Minimum Cycle Time. The cycles for the following send
repetitions result from a conditional equation with the increment set with the
parameter [IC ] : I ncreme nt. Should no further state changes occur up to the
time when the maximum cycle time has elapsed [ IC]: Maximum Cycle Time,
then GOOSE will be sent cyclically at intervals as set for the maximum cycle
time.
In order to have unambiguous identification of a GOOSE sent, characteristics
such as [IC ]: Mult icast MAC Addres s, [ IC]: Application ID (hex),
[I C]: VLA N I dent ifie r (h ex), [IC] : V LA N P r iority and
[I C]: GOOSE I de nt if ie r must be entered in the IED Configurator settings.
Further characteristics are [ IC ]: Datase t R ef e rence and
[IC]: Config urat ion Revis ion.
Each GOOSE is given the state change index and the number of send repetitions.
3.4.5.2.3

Receiving GOOSE
With GOOSE up to 32 logic binary state signals as well as 32 two-pole contact
position signals from external devices (Ext.Devxx) can be received. For each
state signal or contact position signal to be received a specific GOOSE message
is to be selected, which will contain the information wanted, by setting
[IC ]: Mu lt icast MA C Addres s, [IC] : A ppl ication ID (hex),
[IC]: Source Pat h, [IC] : GOOSE Iden ti f ie r and [IC]: DataSet Refere nce.
With the further setting of [ IC]: Data Obj I nde x / Type, which corresponds to
the GOOSE position index and the information structure of the sending device,
the required information from the chosen GOOSE will be selected. The
identification features "VLAN identifier" and [IC] : Configuration Re vision
that are also included in the GOOSE received will not be evaluated.
These parameters characterizing the information may be taken either from
device or project planning documentation of the sending device or from a
configuration file which is conform to IEC 61850. The IED Configurator will
support the import of .IID, .SCD and .MCL files when the "browse function"
(virtual key) is applied. The selection and acceptance of parameters from an
existing project planning is distinguished by a simplified and very reliable data
input.
Should the data type of the selected data object provide quality information then
this can be evaluated. When activating [ IC]: Quality Obj Index the distance
of the quality descriptor to the data object (if not preset) must be given as well
as the quality criterion, which is to be tested. A signal is rejected when one of the
bits ([IC ]: Invalidit y Qu ality bits, see displayed bar with bit state) is received
as a set bit. These parameters are usually described in a configuration file and
are accepted from there during an import action.
Each GOOSE includes time information on the duration of validity of its
information. This corresponds to the double time period to the next GOOSE
repetition. If the duration of validity has elapsed without having received this
GOOSE again (i.e. because of a fault in communications), the signals received
will automatically be set to their respective default value
[IC]: De fault I npu t Val ue. Which of the possible state values will set the
wanted security grade is dependent on the relevant application.
The following configuration (shuttling to the device functions) of the logic state
signals received from the logic node GosGGIO1 (GOOSE: Input 1 fct.assig.
(or Input 2, , Input 32)) is made on the basis of the selection table of the binary
signal inputs (optocoupler inputs). Contact position signals received from
external devices (LN: DevGosGGIO3) are listed in the selection table for
interlocking equations of the function group ILOCK, which are available to design
a decentralized substation interlock.

3-34

P437/EN M/R-11-A // P437311650

P437

3 Operation

The virtual key "Unmap" may be used to remove the link of a binary signal input
to an external data point. In such a case all entries for this binary signal input are
deleted.
3.4.5.2.4

Uniqueness of Control within a System


If with a system application it must be ensured that only one control command at
a time is being processed system wide (uniqueness) then interlocking of
secondary devices among themselves is setup with GOOSE. The P437 sets the
status information Control/LLN0.ST.OrdRun.stVal. when it has received a control
command. This information stored in a dataset is distributed in the system by
GOOSE and is therefore available to all other devices as an interlocking
condition. The state information is reset and accordingly signaled after
termination of the command sequence.
The P437 is capable to monitor the command status of up to 32 further devices.
With the IED Configurator OrdRunGGIO1.ind1.stVal to OrdRunGGIO1.ind32.stVal
are configured in a similar way to the other GOOSE inputs. A shuttling to the
interlocking equations is not necessary as their consideration within command
checking is automatically enabled when the first binary signal input is configured.
During a signaling receipt phase command effecting will be rejected.

Device A
IED Configurator

Device B

S1 Studio

Control/LLN0.ST.OrdRun.stVal

IED Configurator
System/LLN0/Dataset
x

IED Configurator
System/LLN0/gcb01 ... 08

IED Configurator

MCL

System/OrdRunGGIO1

Ind1.stVal ... Ind32.stVal

19Z7004A

Fig. 3-21: Uniqueness of Control.

P437/EN M/R-11-A // P437311650

3-35

P437
3.4.5.3

3 Operation

Generic Substation State Event (Function Group GSSE)


For high-speed exchange of information between individual IEDs (intelligent
electronic devices) in a local network, the P437 provides, as an additional
functionality, the GSSE function group (UCA2.0-GOOSE) as defined in the
IEC 61850 standard. GSSE features high-speed and secure transmission of logic
binary state signals such as reverse interlocking, trip commands, blocking,
enabling and other signals.

3.4.5.3.1

Configuration and Enabling


Function Group GSSE can be configured by setting the parameter
GSSE: Functi on grou p GSSE. This parameter is only visible if the optional
Ethernet communication module is fitted to the P437. After configuration of
GSSE, all data points associated with this function group (setting parameters,
binary state signals etc.) become visible. The function can then be enabled or
disabled by setting GSSE : Ge ne ral e nable USER.
The setting parameters for function groups IEC, GOOSE and GSSE in the P437 are
not automatically activated. The P437 features two memory banks one of
which includes the active setting parameters. The other memory bank is used
with the configuration procedure for parameters from the IED Configurator and
the operating system. Specific project-related extensions of the IEC 61850
parameters from the IED Configurator are loaded into the P437 by downloading
a .MCL file. The inactive communication parameters are activated by executing
the command IEC : Switch Con fig. Ban k. This command may also be issued
from the IED Configurator.

3.4.5.3.2

Sending GSSE
With GSSE up to 32 logic binary state signals can be sent. Selection of binary
state signals is made by setting GSSE: Out put 1 fct.assig. (or Output 2, ,
Output 32). Each selected state signal is to be assigned to a bit pair in GSSE
(GSS E: Out pu t 1 b it pa ir (or Output 2, , Output 32)), which will transmit
this state signal.
GSSE is automatically sent with each state change of a selected state signal.
There will be multiple send repetitions at ascending time periods. The first send
repetition occurs at the given cycle time set with the parameter GSSE: Min.
cycle. The cycles for the following send repetitions result from a conditional
equation with the increment set with the parameter GSSE: Increment. Should
no further state changes occur up to the time when the maximum cycle time has
elapsed (GSSE: Max. cycl e), then GSSE will be sent cyclically at intervals as
set for the max. cycle time.
In order to have unambiguous identification of a GSSE sent, the IED name is used
which was set in function group IEC.

3.4.5.3.3

Receiving GSSE
With GSSE up to 32 logic binary state signals can be received. Configuration of
the logic binary state signals received (GOOSE: Input 1 fct.assig., or Input 2,
, Input 32) is made on the basis of the selection table of the binary inputs (opto
coupler inputs).
For each state signal to be received, the GSSE message, which will include the
required information, must be selected by setting the IED name (e.g.
GSSE: In put 1 IE D name). Selection of information wanted from the selected
GSSE will occur by setting the bit pair (e.g. GSSE: Input 1 bit pair).
Each GSSE includes time information on the validity duration of its information.
This corresponds to the double time period to the next GSSE repetition. If the

3-36

P437/EN M/R-11-A // P437311650

P437

3 Operation

validity duration has elapsed without this GSSE being received again (i.e.
because of a communications fault), the signals received will automatically be
set to their respective default value (e.g. GSSE: In put 1 default).
The various settings, measured values and signals for function group GOOSE are
described in chapters 7 and 8.

P437/EN M/R-11-A // P437311650

3-37

P437

3.5

3 Operation

IRIG-B Clock Synchronization (Function Group IRIGB)


If, for example, a GPS receiver with IRIG-B connection is available, the internal
clock of the P437 can be synchronized to run on GPS time using the optional
IRIG-B interface. It should be noted that the IRIG-B signal holds information on
the day only (day of the current year). Using this information and the year set at
the P437, the P437 calculates the current date (DD.MM.YY).

Disabling and Enabling the IRIG-B Interface


The IRIGB interface can be disabled or enabled using a setting parameter.
Synchronization Readiness
If the IRIG-B interface is enabled and receiving a signal, the P437 checks the
received signal for plausibility. Implausible signals are rejected by the P437. If
the P437 does not receive a correct signal in the long run, synchronization will
not be ready any longer.

IRIGB:
General enable USER
[ 023 200 ]

IRIGB:
Enabled
[ 023 201 ]
IRIGB:
Synchron. ready
[ 023 202 ]

47Z02BAA

Fig. 3-22: IRIGB interface.

3-38

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.6

Configurable Function Keys (Function Group F_KEY)


The P437 provides six freely configurable function keys. A password may be
configured for each function key (e.g. for F1 at F _KEY: Pass word funct .k ey
1), and if a password has been configured then the respective function key will
only be enabled when the configured password is entered.
As an example the operation of function key F1 is shown in Fig. 3-23, (p. 3-40).
After the password has been entered the function key will remain active for the
time period set at F_KE Y: Re tur n ti me f ct.ke ys. Thereafter, the function key
is disabled until the password is entered again. The same is valid for function
keys F2 to F6. Exception: If a function key is configured as a control key a
password request is only issued when the function Local/Remote switching has
been assigned to this function key.

3.6.1

Configuration of Function Keys with a Single Function


One function may be assigned to each function key (e.g. for F1) at F _KEY: Fct.
assignm. F1 or by selecting a logic state signal (except L OC: Trig. me nu
jmp 1 EXT and L O C: Trig. me nu j mp 2 E XT). The assigned function is
triggered by pressing the respective function key on the P437.

3.6.2

Configuration of Function Keys with Menu Jump Lists


Instead of a single function each function key may have one of the two menu
jump lists assigned (e.g. for F1) at F _KEY: Fct. as sign m. F1 by selecting the
listing at LO C : Tr ig. me nu jmp 1 EXT or LOC: Trig. m en u jmp 2 EXT. The
functions of the selected menu jump list are triggered in sequence by repeated
pressing of the assigned function key.
Both menu jump lists are assembled at LO C: Fct. m en u jmp lis t 1 or
LOC: Fct. men u jmp lis t 2. Up to 16 functions such as setting parameters,
event counters and/or event logs may be selected.
LED indicators including the six positioned directly next to the function keys are
configured independently and in this respect there is no relationship to the
respective function key configuration.

3.6.3

Configuration of the READ Key


As with LO C : Fct. m e nu j mp lis t 1 or LO C: Fct. m enu jmp list 2 up to 16
functions may also be selected from the same menu jump list at
LOC: Assi gnment re ad ke y. They are triggered in sequence by repeated
pressing of the READ key.

3.6.4

Operating Mode of the Function Keys


For each function key the operating mode may be selected (e.g. for F1) at
F _KEY: Operating mode F1. Here it is possible to select whether the function
key operates as a key or as a switch. In the Key operating mode the selected
function is active while the function key is pressed. In the Switch operating mode
the selected function is switched on or off every time the function key is pressed.
The state of the function keys can be displayed.

3.6.5

Handling Keys
If backlighting for the LC display is switched off it will automatically light up when
a function key or the READ key is pressed. The assigned function will only be

P437/EN M/R-11-A // P437311650

3-39

P437

3 Operation

triggered when the respective key is pressed a second time. This is also valid for
the other keys.

F_KEY:
Fct. assignm. F1
[ 080 112 ]
Function 1 EXT
Function 2 EXT
Function 3 EXT
Function n EXT
Selected function

&

Activate function

F_KEY:
Operating mode F1
[ 080 132 ]

F_KEY:
State F1
[ 080 122 ]

&

2
1: Key
2: Switch
&

&

S1 1

&

R1 0

1)

1) Keys, local control

40Z5003A

Fig. 3-23: Configuration and operating mode of function keys. The assigned function is either a single function or a
menu jump list.

3-40

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.7

Configuration and Operating Mode of the Binary Inputs


(Function Group INP)
The P437 has opto coupler inputs for processing binary signals from the
substation. The functions that will be activated in the P437 by triggering these
binary signal inputs are defined by the configuration of the binary signal inputs.
In order to ensure that during normal operation the P437 will recognize an input
signal, it must persist for at least 20 ms. With the occurrence of a general
starting this time period may have to be increased to 40 ms under unfavorable
conditions.

Configuring the Binary Inputs


One function can be assigned to each binary signal input by configuration. The
same function can be assigned to several signal inputs. Thus one function can be
activated from several control points having different signal voltages.
It should be noted that time-critical applications such as time synchronization
commands should not be mapped to the binary signal inputs of the analog I/O
module as these have an increased reaction time due to internal processing.
In this technical manual, it is assumed that the required functions (marked EXT
in the address description) have been assigned to binary signal inputs by
configuration.
Operating Mode of the Binary Inputs
The operating mode for each binary signal input can be defined. The user can
specify whether the presence (Active "high" mode) or absence (Active "low"
mode) of a voltage shall be interpreted as the logic 1 signal. The display of the
state of a binary signal input "low" or "high" is independent of the setting for
the operating mode of the signal input.
Filter Function
An additional filter function may be enabled in order to suppress transient
interference peaks at the logic signal inputs (operating modes Active "high", filt.
or Active "low", filt.). With this function enabled a status change at the binary
logic input is only signaled when the input signal remains at a steady signal level
during a set number of sampling steps (sampling step size = period / 20). The
number of sampling steps is set at parameter INP : Filt er.

P437/EN M/R-11-A // P437311650

3-41

P437

3 Operation

INP:
Fct. assignm. U xxx
[ XXX XXX ]

Function 1 EXT
Function 2 EXT
Function 3 EXT
Function n EXT
Selected function

&

Activate function

INP:
Oper. mode U xxx
[ YYY XXX ]

0
1
2
3
0: Active "low"
1: Active "high"
2: Active "low", filt.
3: Active "high", filt.
-Uxxx

&

Input signal

&
INP:
Filter
[ 010 220 ]

&
&
&

INP:
State U xxx
[ ZZZ ZZZ ]

&

12Z6213A

Fig. 3-24: Configuration and operating mode of the binary signal inputs.

3-42

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.8

Measured Data Input (Function Group MEASI)


The P437 has a measured data input function involving two inputs. Direct current
is fed to the P437 through one of the inputs. The other input is designed for
connection of a resistance thermometer.
The input current IDC present at the analog (I/O) module Y is displayed as a
measured operating value. The current that is conditioned for monitoring
purposes (IDC,lin) is also displayed as a measured operating value. In addition, it is
monitored by the Limit Value Monitoring function to detect whether it exceeds or
falls below set thresholds (see Section 3.39, (p. 3-415)).
The measured temperatures are also displayed as measured operating values
and monitored by the Limit Value Monitoring function to determine whether they
exceed or fall below set thresholds (see Section 3.39, (p. 3-415)).

Disabling or Enabling the Measured Data Input Function


The Measured Data Input function can be disabled or enabled via setting
parameters.

MEASI:
General enable USER
[ 011 100 ]

0
1

MEASI:
Enabled
[ 035 008 ]

0: No
1: Yes

S8Z52H1A

Fig. 3-25: Disabling or enabling the measured data input function.

P437/EN M/R-11-A // P437311650

3-43

P437

3 Operation

3.8.1

Direct Current Input on the Analog (I/O) Module Y


External measuring transducers normally supply an output current of 0 to 20 mA
that is directly proportional to the physical quantity being measured the
temperature, for example.
If the output current of the measuring transducer is directly proportional to the
measured quantity only in certain ranges, linearization can be arranged,
provided that the measured data input is set accordingly. Furthermore, for
certain applications it may be necessary to limit the range being monitored or to
monitor certain parts of the range with a higher or lower sensitivity.
By setting the value pair MEA SI: IDC 1 and MEASI: IDC,lin 1, the user
specifies which input current IDC will correspond to the current that is monitored
by the Limit Value Monitoring function, i.e. IDC,lin. (These two setting parameters
refer to value pair number 1; setting parameters for value pairs 2 to 20 are
available, too.)
The resulting points, called interpolation points, are connected by straight lines
in an IDCIDC,lin diagram. In order to implement a simple characteristic, it is
sufficient to specify two interpolation points, which are also used as limiting
values (see Fig. 3-26, (p. 3-44)). Up to 20 interpolation points are available to
implement a complex characteristic.
When setting the characteristic the user must remember that only a rising/rising
or falling/falling curve sense is allowed (no peak or vee-shapes). If the setting
differs, the signal SFMON: In vali d scal in g IDC will be generated.

I DC,lin / I DC,nom
1.2
1.1

I DC,lin20

1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1

I DC,lin1

0
0

0.1

0.2

I DC1

0.25

0.3

0.35

0.4

0.45

0.5

0.6

I DC / I DC,nom

I DC20
19Z5266A_EN

Fig. 3-26: Example of the conversion of 4 to 10 mA input current to 0 to 20 mA monitored current, IDC,lin.

3-44

P437/EN M/R-11-A // P437311650

P437

3 Operation

IDC,lin / IDC,nom

0.8
Interpolation points

IDC,lin20

0.7

0.6

IDC,lin4

0.5

0.4

IDC,lin3

0.3

IDC,lin2

0.2

IDC,lin1

0.1

0
0

0.1

0.2
IDC1

0.3

0.4

0.5

0.6

IDC2 IDC3

0.7

0.8

0.9
IDC4

1
IDC20

1.1

1.2
IDC / IDC,nom

Enable IDC p.u.


D5Z52KEC_EN

Fig. 3-27: Example of a characteristic with five interpolation points (characteristic with zero suppression setting of
0.1 IDC,nom is shown as a broken line).

P437/EN M/R-11-A // P437311650

3-45

P437

3 Operation

MEASI:
IDC 1
[ 037 150 ]

MEASI:
IDC 8
[ 037 164 ]

MEASI:
IDC 15
[ 037 178 ]

MEASI:
IDC,lin 1
[037 151 ]

MEASI:
IDC,lin 8
[037 165 ]

MEASI:
IDC,lin 15
[037 179 ]

MEASI:
IDC 2
[ 037 152 ]

MEASI:
IDC 9
[ 037 166 ]

MEASI:
IDC 16
[ 037 180 ]

MEASI:
IDC,lin 2
[ 037 153 ]

MEASI:
IDC,lin 9
[ 037 167 ]

MEASI:
IDC,lin 16
[ 037 181 ]

MEASI:
IDC 3
[ 037 154 ]

MEASI:
IDC 10
[ 037 168 ]

MEASI:
IDC 17
[ 037 182 ]

MEASI:
IDC,lin 3
[ 037 155 ]

MEASI:
IDC,lin 10
[ 037 169 ]

MEASI:
IDC,lin 17
[ 037 183 ]

MEASI:
IDC 4
[ 037 156 ]

MEASI:
IDC 11
[ 037 170 ]

MEASI:
IDC 18
[ 037 184 ]

MEASI:
IDC,lin 4
[ 037 157 ]

MEASI:
IDC,lin 11
[ 037 171 ]

MEASI:
IDC,lin 18
[ 037 185 ]

MEASI:
IDC 5
[ 037 158 ]

MEASI:
IDC 12
[ 037 172 ]

MEASI:
IDC 19
[ 037 186 ]

MEASI:
IDC,lin 5
[ 037 159 ]

MEASI:
IDC,lin 12
[ 037 173 ]

MEASI:
IDC,lin 19
[ 037 187 ]

MEASI:
IDC 6
[ 037 160 ]

MEASI:
IDC 13
[ 037 174 ]

MEASI:
IDC 20
[ 037 188 ]

MEASI:
IDC,lin 6
[ 037 161 ]

MEASI:
IDC,lin 13
[ 037 175 ]

MEASI:
IDC,lin 20
[ 037 189 ]

MEASI:
IDC 7
[ 037 162 ]

MEASI:
IDC 14
[ 037 176 ]

MEASI:
Enable IDC p.u.
[ 037 190 ]

MEASI:
IDC,lin 7
[ 037 163 ]

MEASI:
IDC,lin 14
[ 037 177 ]

MEASI:
IDC< open circuit
[ 037 191 ]

MEASI:
Enabled
[ 035 008 ]

SFMON:
Invalid scaling IDC
[ 093 116 ]
MEASI:
Overload 20mA input
[ 040 191 ]
Input channel 1(I-1)

SFMON:
Overload 20 mA input
[ 098 025 ]
MEASI:
Open circ. 20mA inp.
[ 040 192 ]
SFMON:
Open circ. 20mA inp.
[ 098 026 ]

MEASI:
Curr. IDC,lin p.u.
[ 004 136 ]

MEASI:
Current IDC p.u.
[ 004 135 ]

MEASI:
Current IDC
[ 004 134 ]

S8Z52H2A

Fig. 3-28: Analog direct current input.

Beyond the linearization described above, the user has the option of scaling the
linearized values. Thereby negative values, for example, can be displayed as well
and are available for further processing by protection functions.

3-46

P437/EN M/R-11-A // P437311650

P437

3 Operation

MEASI:
Scaled val. IDC,lin1
[ 037 192 ]
MEASI:
Scaled val.IDC,lin20
[ 037 193 ]

MEASI:
Curr. IDC,lin p.u.
[ 004 136 ]

MEASI:
Scaled value IDC,lin
[ 004 180 ]

Q9Z5029A

Fig. 3-29: Scaling of the linearized measured value.

3.8.1.1

Zero Suppression
Zero suppression is defined by setting MEA SI: En able ID C p. u. If the direct
current does not exceed the set threshold, the per-unit input current IDC p.u. and
the current IDC,lin will be displayed as having a value of 0.

3.8.1.2

Open-Circuit and Overload Monitoring


The P437 is equipped with an open-circuit monitoring function. If current IDC falls
below the set threshold MEA SI: ID C < open cir cuit, the signal MEA SI: Open
ci rc. 20mA inp. is issued.
The input current is monitored in order to protect the 20 mA analog input against
overloading. If it exceeds the set threshold of 24.8 mA, the signal
M EASI : O ve rload 20mA in put is issued.

3.8.2

Connecting a Resistance Thermometer to the PT 100 Analog


Input on the Analog (I/O) Module Y
This analog input on the analog (I/O) module Y is designed to connect a PT 100
resistance thermometer. The mapping curve R = f(T) of PT 100 resistance
thermometers is defined in standard IEC 751. If the PT 100 resistance
thermometer is connected using the 3-wire method, then no further calibration is
required.
The result of a temperature measurement can be read out as a direct measurand
(temperature T), a normalized value (temperature norm. T), and as the maximum
value since the last reset.

P437/EN M/R-11-A // P437311650

3-47

P437

3 Operation

MEASI:
Enabled
[ 035 008 ]

MEASI:
PT100 faulty
[ 040 190 ]

Measur. input PT100

SFMON:
PT100 open circuit
[ 098 024 ]

MEASI:
Temperature
[ 004 133 ]

MEASI:
Temperature p.u.
[ 004 221 ]

MEASI:
Temperature Tmax
[ 004 233 ]

19Z5262A

Fig. 3-30: Temperature measurement using a PT 100 resistance thermometer connected to the analog (I/O)
module.

3.8.2.1

Open-Circuit Monitoring
If there is an open measuring circuit due to a broken wire, the signal
MEASI : PT100 faulty is issued.

3-48

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.9

Configuration, Operating Mode, and Blocking of the Output


Relays (Function Group OUTP)
The P437 has output relays for the output of binary signals. The binary signal
assignment is freely configurable by the user.

Configuration of the Output Relays


One binary signal can be assigned to each output relay. The same binary signal
can be assigned to several output relays by configuration.
Operating Mode of the Output Relays
The user can set an operating mode for each output relay that determines
whether the output relay operates in a normally open arrangement (NO) or
normally closed arrangement (NC) and whether it operates in latching mode.
Depending on the selected operating mode, latching can be disabled, either
manually using a setting parameter or by an appropriately configured binary
signal input at the start of a new fault, signalized by the onset of a general
starting, or of a new system disturbance.
Blocking the Output Relays
The P437 offers the option of blocking all output relays via a setting parameter or
by way of an appropriately configured binary signal input. The output relays are
likewise blocked if the device is disabled via appropriately configured binary
inputs.
In these cases the relays are treated according to their set operating mode, i.e.
relays in a normally open arrangement (NO) are not triggered, whereas relays in
a normally closed arrangement (NC) are triggered.
This does not apply to the relays associated with the signals SF MO N: Warning
(relay ) or MAIN : Block ed/f au lty. Self-monitoring alarms are thus correctly
indicated.
If the self-monitoring detects a serious hardware fault (see error messages in
Chapter 11, (p. 11-1), which will lead to a blocking of the protection), all
output relays are reset regardless of the set operating mode or signal
configuration.

P437/EN M/R-11-A // P437311650

3-49

P437

3 Operation

OUTP:
Outp.rel.block USER
[ 021 014 ]
0
OUTP:
Outp. relays blocked
[ 021 015 ]

1
0: No
1: Yes
OUTP:
Block outp.rel. EXT
[ 040 014 ]
MAIN:
Prot. ext. disabled
[ 038 046 ]
SFMON:
Hardware fault
304 950

OUTP:
Oper. mode K xxx
[ xxx xxx ]
1
2
3
-K xxx

4
5
6
1: ES updating
2: ES manual reset
3: ES reset (fault)

OUTP:
State K xxx
[ ZZZ ZZZ ]

4: ES reset (syst.dist)
5: NE updating
6: NE manual reset

S1 1
R1

OUTP:
Fct.assignment K xxx
[ yyy yyy ]
Signal 1
Signal 2
Signal 3
Signal n

Selected signal

OUTP:
Latching reset
[ 040 088 ]

FT_RC:
Record. in progress
[ 035 000 ]
FT_RC:
System disturb. runn
[ 035 004 ]
MAIN:
General reset USER
[ 003 002 ]
1: execute
MAIN:
General reset EXT
[ 005 255 ]
OUTP:
Reset latch. USER
[ 021 009 ]
0
1
0: don't execute

1
100 ms

1: execute
OUTP:
Reset latch. EXT
[ 040 015 ]

64Z8038A

Fig. 3-31: Configuration, setting the operating mode, and blocking the output relays

Testing the Output Relays


For testing purposes, the user can select an output relay and trigger it via a
setting parameter. Therefore the P437 must be switched to off-line. Triggering
persists for the duration of the set hold time.
3-50

P437/EN M/R-11-A // P437311650

P437

3 Operation

OUTP:
Relay assign. f.test
[ 003 042 ]

OUTP:
Fct.assignment K xx1
[ AAA AAA ]
OUTP:
Fct.assignment K xx2
[ BBB BBB ]
OUTP:
Fct.assignment K xx3
[ CCC CCC ]

-K yyy

OUTP:
Fct.assignment K xxx
[ ZZZ ZZZ ]
MAIN:
Device on-line
[ 003 030 ]
0: No (= off)

Selected relay

OUTP:
Relay test
[ 003 043 ]

OUTP:
Hold-time for test
[ 003 044 ]
0
1

0: don't execute
1: execute

47Z1050A

Fig. 3-32: Testing the output relays

P437/EN M/R-11-A // P437311650

3-51

P437

3.10

3 Operation

Measured Data Output (Function Group MEASO)


Measurands made available by the P437 can be provided in BCD (binary coded
decimal) form through output relays or in analog form as direct current output.
Output as direct current can only occur if the P437 is equipped with analog
module Y. BCD output is always possible, whether the P437 is equipped with
analog module Y or not.

3.10.1

General Settings

3.10.1.1

Disabling or Enabling the Measured Data Output Function


The Measured Data Output function can be disabled or enabled via setting
parameters.

MEASI:
General enable USER
[ 011 100 ]

0
1

MEASI:
Enabled
[ 035 008 ]

0: No
1: Yes

S8Z52H1A

Fig. 3-33: Disabling or enabling the measured data output function.

3.10.1.2

Enabling Measured Data Output


The measured data output can be enabled through a binary signal input,
provided that the function MEASO: Outp. e nable d EXT has been configured.
If the function ME ASO: Ou tp. en abl ed E XT has not been configured to a
binary signal input, then the measured data output is always enabled.

INP:
Fct. assignm. U xxx
[ xxx xxx ]

U x1
U x2
U x3
U xx
Address

036 085

MEASO:
Outp. enabled EXT
[ 036 085 ]

MEASO:
Enable
304 600

S8Z52H5A

Fig. 3-34: Enabling measured data output.

3-52

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.10.1.3

Resetting the Measured Data Output Function


BCD or analog output of measurands is terminated for the duration of the hold
time if one of the following conditions is met:

The measured data output function is reset from the integral local control
panel or through an appropriately configured binary signal input.

There is a general reset.

LED indicators reset

MEASO:
Reset output USER
[ 037 116 ]

0
1
0: don't execute
1: execute

MEASO:
Reset output EXT
[ 036 087 ]

MEASO:
Output reset
[ 037 117 ]

MAIN:
General reset USER
[ 003 002 ]
1: execute

MEASO:
Reset meas.val.outp.
304 601

MAIN:
Reset indicat. USER
[ 021 010 ]
1: execute
MAIN:
General reset EXT
[ 005 255 ]
MAIN:
Reset indicat. EXT
[ 065 001 ]

47Z13H6A

Fig. 3-35: Resetting the measured data output function.

3.10.1.4

Scaling
Scaling is used to map the physical measuring range to the P437 inherent setting
range.
Scaling of analog output is also suited for directional-signed output of some fault
measurands, in particular fault location in percent.

P437/EN M/R-11-A // P437311650

3-53

P437
3.10.2

3 Operation

BCD Measured Data Output


The user can select a measurand for output in BCD form by assigning output
relays.
The selected measurand is available in BCD-coded form for the duration of the
set hold time MEA SO: Hol d t ime ou tpu t BCD. If the selected variable was
not measured, then there is no output of a measurand value.

3.10.2.1

Output of Measured Event Values


If the measured event value is updated during the hold time, the measurand
output memory is cleared and the hold time is re-started. This leads to an
immediate availability at the output of the updated value.

3.10.2.2

Output of Measured Operating Values


The selected measured operating value is available for the duration of the set
hold time. After the hold time has elapsed, the current value is saved and the
hold time is re-started. If the hold time has been set to blocked, the measured
operating value that has been output will be stored until the measured data
output function is reset.

3.10.2.3

Scaling of BCD Output


In order to define the resolution for measured data output the measurand range
(Mx,min ... Mx,max) in scaled form (as Mx,scal,min ... Mx,scal,max) and the
associated BCD display range (BCD,min ... BCD,max) have to be set.

MEA SO: Scale d min . val. BCD

MEASO: Scal ed m ax. val. BCD

ME ASO: BC D-Out m in . value

MEA SO: BC D-Out max. val ue

The BCD display range should be set so that the value 399 is never exceeded. If
this should occur or if the measurand is outside the acceptable measuring range,
then the value for "Overflow" (all relays triggered) is transmitted.
Measurands

Range

Measurands of the variable Mx

Mx,RL1 ... Mx,RL2

Associated scaled measurands

0 ... 1

Scaling is made with reference to the complete range of values for the selected
measurand (variable Mx). The complete range of values is defined by their end
values Mx,RL1 and Mx,RL2. (Mx,RL1 and Mx,RL2 are listed in the operating
program S&R-103 - PC Access Software MiCOM S1 - under minimum and
maximum.)

3-54

P437/EN M/R-11-A // P437311650

P437

3 Operation

Measurands to be output

Range

Measurands to be output

Mx,min. ... Mx,max.

Scaled measurands to be output

Mx,scal,min ... Mx,scal,max


with:
Mx,scal,min = (Mx,min - Mx,RL1) / (Mx,RL2 - Mx,RL1
Mx,scal,max = (Mx,max - Mx,RL1) / (Mx,RL2 - Mx,RL1

Designation of the set values in the data


model

"Scaled min. val. BCD" ... "Scaled max. val. BCD"

Measurands

BCD display values

Measurands in the range "Measurands to BCD-Out min. value ... BCD-Out max. value
be output"
(Valid BCD value)
Measurands:

BCD-Out min. value (BCD value not valid)

Mx,RL1 = Mx = Mx,min
Measurands Mx:

BCD-Out max. value (BCD value not valid)

Mx,max = Mx = Mx,RL2
Measurands Mx:

BCD-Out max. value (Overflow)

Mx < Mx,RL1
or
Mx > Mx,RL2
3.10.2.4

Example for Scaling of BCD Output


The value range for the fault measurand is set from 320.00% to +320.00%.
The PU fault location is given in the range from 0% to 200%.

Measurands

Range

Fault measurand:

-320.00% ... +320.00%

FT_DA: Fa ult locat . pe rcent


Associated scaled measurands

0 ... 1

Measurands to be output

Range

Measurands to be output

0% ... 200%

Scaled measurands to be output

0.5 ... 0.813


with:
0.500 = 320/640
0.813 = 520/640

P437/EN M/R-11-A // P437311650

3-55

P437

3 Operation

Measurands

BCD display values

Measurands in the range Measurands to be


output

0 ... 200

In this example the following P437 settings are selected:


Address

Description

Current value

056 020

MEASO : F unction group


MEASO

With

031 074

MEASO : Ge ne ral en able


USE R

Yes

053 002

ME ASO : F ct. assi gnm. BC D

FT_DA: Fau lt locat. pe rcent

010 010

MEASO : Hold time output


BCD

1.00 s

037 140

ME ASO : Scal ed m in . val.


BCD

0.500

037 141

M EASO : Scale d m ax. val .


BCD

0.813

037 142

MEASO : BC D-Out m in . valu e 0

037 143

MEASO : BC D-Out m ax.


va lue

200

The following figure displays the values output as a function of the fault location.
The BCD value and the signal MEASO: Vali d BCD value = Yes are only issued
in the value range 0% to 200%.

BCD value

FT_DA:
Fault locat. percent

MEASO:
Valid BCD value

[004 027]

FT_DA:
Fault locat. percent
[004 027]

[037 050]

200

0
-320%

0%

200%

320%

FT_DA:
Fault locat. percent
[004 027]

47Z1040A

Fig. 3-36: Example of BCD output of fault location.

3-56

P437/EN M/R-11-A // P437311650

P437

3 Operation

Except from radial, single circuit lines the fault location value gives a reasonable
value only for faults up to the line end. For any fault on a subsequent line the fault
location is more or less incorrect due to unknown fault current infeed in the remote
substation.
It is recommended to limit the calculation of a fault location to a practical and
sensible range on the line by setting F T _ D A : O u t p . f l t . l o c a t . P S x = Only
aft.tr.t1/t1,ze.

MEASO:
Hold time output BCD
[ 010 010 ]

MEASO:
Enabled
[ 037 102 ]

MEASO:
1-digit bit 0 (BCD)
[ 037 051 ]
MEASO:
1-digit bit 1 (BCD)
[ 037 052 ]
Setting blocked

MEASO:
1-digit bit 2 (BCD)
[ 037 053 ]

MEASO:
Enable

MEASO:
1-digit bit 3 (BCD)
[ 037 054 ]

304 600

MEASO:
10-digit bit 0 (BCD)
[ 037 055 ]
MEASO:
10-digit bit 1 (BCD)
[ 037 056 ]

MEASO:
Reset meas.val.outp.

MEASO:
10-digit bit 2 (BCD)
[ 037 057 ]

304 601

MEASO:
10-digit bit 3 (BCD)
[ 037 058 ]
MEASO:
100-dig. bit 0 (BCD)
[ 037 059 ]
Selected
meas. oper. value

MEASO:
100-dig. bit 1 (BCD)
[ 037 060 ]

Selected
Meas. event value
being updated
Selected meas. val.

MEASO:
Valid BCD value

Value not measured

[ 037 050 ]

Selected meas. val.


Overflow

MEASO:
Fct. assignm. BCD
[ 053 002 ]

Meas. value 399

Measured value 1
Measured value 2
Measured value 3

c1

Measured value n

c2
Scaling of the
BCD output

Selected meas. val.

++

2
1...2

MEASO:
Output value x
[ * ]

0 . . . 100 %

++

Scaling of the BCD output

Address

MEASO:
Scaled min. val. BCD

037 140

x: 1

037 120

MEASO:
Scaled max. val. BCD

037 141

x: 2

037 121

MEASO:
BCD-Out min. value

037 142

037 122

MEASO:
BCD-Out max. value

037 143

MEASO:
Output value x

x: 3

19Z5264A

Fig. 3-37: BCD measured data output. Overflow behavior is displayed in BCD example (see previous figure).

P437/EN M/R-11-A // P437311650

3-57

P437
3.10.3

3 Operation

Analog Measured Data Output


Analog output of measured data is two-channel.
The user can select two of the measurands available in the P437 for output in the
form of load-independent direct current. Three interpolation points per channel
can be defined for specific adjustments such as adjustment to the scaling of a
measuring instrument. The direct current that is output is displayed as a
measured operating value.
The selected measurand is output as direct current for the duration of the set
hold time MEA SO: Ho ld ti me ou tpu t A -1. If the selected variable was not
measured, then there is no output of a measurand value.

3.10.3.1

Output of Measured Event Values


If the measured event value is updated during the hold time, the measurand
output memory is cleared and the hold time is re-started. This leads to an
immediate availability at the output of the updated value.

3.10.3.2

Output of Measured Operating Values


The selected measured operating value is available for the duration of the set
hold time. After the hold time has elapsed, the current value is saved and the
hold time is re-started. If the hold time has been set to blocked, the measured
operating value that has been output will be stored until the measured data
output function is reset.

3.10.3.3

Configuration of Output Relays Assigned to the Output Channels


The user must keep in mind that direct current output only occurs when the
output relays assigned to the output channels are configured for MEA SO: Value
A-1 outp ut, since the output channels would otherwise remain short-circuited
(see the terminal connection diagrams, Section 5.7, (p. 5-19)).

3.10.3.4

Scaling the Analog Display


In order to define the resolution for measured data output the measurand range
in scaled form and the associated display range have to be set. One additional
value for the knee point must also be defined. In this way the user can obtain an
analog output characteristic similar to the characteristic shown in Fig. 3-38, (p. 362).

3.10.3.5

Measurand Range to be Output


The measurand range to be output is (Mx,min ... Mx,knee ... Mx,max), with:

Mx,min: minimum value to be output

Mx,knee: Knee-point value for the measurand range to be output

Mx,max: maximum value to be output

This measurand range to be output is defined by setting the following


parameters:

MEA SO: S cale d min . val . A-1 or ME ASO: Scaled min. val. A- 2,
resp.

MEASO : Scal ed k ne e val. A -1 or MEASO: Scaled knee val. A -2,


resp.

MEASO: Scal ed max. val. A-1 or ME ASO: Scaled max. val. A- 2,


resp.

Scaling is made with reference to the complete range of values for the selected
measurand (variable Mx). The complete range of values is defined by their end
3-58

P437/EN M/R-11-A // P437311650

P437

3 Operation

values Mx,RL1 and Mx,RL2. (Mx,RL1 and Mx,RL2 are listed in the operating
program S&R-103 PC Access Software MiCOM S1 under minimum and
maximum.)
Measurands

Range

Measurands of the variable Mx

Mx,RL1 ... Mx,RL2

Associated scaled measurands

0 ... 1

Measurands to be output

Range

Measurands with knee-point to be output

Mx,min ... Mx,knee ... Mx,max

Scaled measurands with a scaled knee-point to be Mx,scal,min ... Mx,scal,knee ... Mx,scal,max
output
with:
Mx,scal,min = (Mx,min - Mx,RL1) / (Mx,RL2 Mx,RL1
Mx,scal,knee = (Mx,knee - Mx,RL1) / (Mx,RL2 Mx,RL1)
Mx,scal,max = (Mx,max - Mx,RL1) / (Mx,RL2 Mx,RL1
Designation of the set values in the data model

"Scal. min. value Ax" ...


... "Scal. knee-point Ax"
... "Scaled max. val. Ax"

3.10.3.6

Associated Display Range


The associated display range is defined by setting the following parameters:

ME ASO: A nOu t min . val. A -1 or MEASO: AnOut min. val. A-2, resp.

ME AS O: An Out kne e point A -1 or MEA SO : AnOut knee point A -2,


resp.

MEA SO: A nOu t max. val . A-1 or ME ASO: AnOut max. val. A-2,
resp.

Measurands

Analog display values

Measurands in the range "Measurands to be


output"

"AnOut min. val. A-x" ...


... "AnOut knee point A-x" ...
... "AnOut max. val." (Value A-x valid)

Measurands:

"AnOut min. val." (Value A-x not valid)

Mx,RL1 = Mx = Mx,min
Measurands Mx:

"AnOut max. val." (Value A-x not valid)

Mx,max = Mx = Mx,RL2
Measurands Mx:

"AnOut max. val." (Overflow)

Mx < Mx,RL1
or
Mx > Mx,RL2

P437/EN M/R-11-A // P437311650

3-59

P437
3.10.3.7

3 Operation

Example for Scaling of Analog Display Ranges


Voltage A-B is selected as the measurand to be transmitted by channel A-1.
The measuring range is from 0 to 1.5 Vnom with Vnom = 100 V.
The range to be transmitted is from 0.02 to 1 Vnom with the associated display
range from 4 mA to 18 mA.
The knee-point of the characteristic is 0.1 Vnom with an associated display of
16 mA.

Measurands

Range

Measurands of the variable Mx

0 V ... 150 V

Associated scaled measurands

0 ... 1

Measurands to be output

Range

Measurands with knee-point to be output

2 V ...10 V... 100 V

Associated scaled measurands

0.013 ... 0.067 ... 0.67


with:
Mx,scal,min = (2 V - 0 V ) / (150 V - 0 V ) = 0.013
Mx,scal,knee = (10 V - 0 V ) / (150 V - 0 V ) =
0.067
Mx,scal,max = (100 V - 0 V ) / (150 V - 0 V ) =
0.67

Measurands

Analog display values

Measurands in the range "Measurands to be


output"

4 mA ... 16 mA ... 18 mA

0.02 ... 0.1 Vnom ... 1 Vnom


In this example the following P437 settings are selected in the menu branch
Parameter/Config. parameters:

3-60

P437/EN M/R-11-A // P437311650

P437

3 Operation

Address

Description

Current value

056 020

MEASO : F uncti on group MEA SO

With

031 074

MEASO : Ge ne ral ena bl e USER

Yes

053 000

MEASO : F ct. assignm. A -1

MAIN: Volta ge A -B p.u.

010 114

M EASO : Hol d t ime output A -1

1.00 s

037 104

MEASO : Sca le d m in . val. A-1

0.013 (corresponds with 0.02 Vnom)

037 105

MEASO : S cale d k ne e val. A -1

0.067 (corresponds with 0.10 Vnom)

037 106

ME ASO : S caled m ax . val. A -1

0.667 (corresponds with 1.00 Vnom)

037 107

ME ASO : A nOu t mi n. val. A -1

4 mA

037 108

ME ASO : AnOut knee poi nt A -1

16 mA

037 109

MEASO : AnOut max. val . A-1

18 mA

By setting MEASO: A nOut m in . val. A-1, the user can specify the output
current that will be output when values are smaller than or equal to the set
minimum measured value to be transmitted. The setting at MEASO: AnO ut
max . va l. A-1 defines the output current that is output for the maximum
measured value to be transmitted. By defining the knee-point, the user can
obtain two characteristic curve sections with different slopes. When entering this
setting the user must keep in mind that only a rising/rising or falling/falling curve
sense is permitted (peaky or vee shapes not allowed). If the setting was not
properly entered, the signal SFMON: In val i d s caling A -1 will be issued.
A check of the set characteristic and its acceptance by the P437, if the setting was
properly entered, will only occur after the P437 is switched on-line again (with the
setting M A I N : D e v i c e o n - l i n e).

P437/EN M/R-11-A // P437311650

3-61

P437

3 Operation

Ia / mA
20
18
Max.
output value
Knee point 16
output value
14
12
10
8
6
4
Min.
output value
2
0
0

0.02
0.013

0.1
0.067

1
0.667

1.2

1.3

1.4

1.5
1.0

Vnom

Mx,scal
19Z5265A

Fig. 3-38: Example of a characteristic curve for analog measured data output . In this example the range starting
value is = 0; also possible is directional-signed output (see corresponding example in section BCD Measured Data
Output).

3-62

P437/EN M/R-11-A // P437311650

P437

3 Operation

MEASO:
Value A-1 output
[ 037 118 ]

MEASO:
Hold time output A-1
[ 010 114 ]

MEASO:
Enabled
[ 037 102 ]

R
c

Setting(s) blocked

MEASO:
Enable
304 600

An. outp. ch.1 (A-1)


[ ------ ]

MEASO:
Reset meas.val.outp.

304 601

Selected
meas. oper. value
OUTP:
Fct.assignment K xxx
[ xxx xxx ]

Selected
Meas. event value
being updated

c
K x1
K x2
K x3
K xx
MEASO:
Value A-1 output
[ 037 118 ]

MEASO:
Fct. assignm. A-1
[ 053 000 ]
Measured value 1

MEASO:
Scaled min. val. A-1
[ 037 104 ]
MEASO:
Scaled knee val. A-1
[ 037 105 ]

MEASO:
Scaled max. val. A-1
[ 037 106 ]
MEASO:
AnOut min. val. A-1
[ 037 107 ]
MEASO:
AnOut knee point A-1
[ 037 108 ]
MEASO:
AnOut max. val. A-1
[ 037 109 ]

Measured value 2
Measured value 3
Measured value n

SFMON:
Invalid scaling A-1
[ 093 114 ]

Selected meas. val.

Value in AnOut range

MEASO:
Output value x
[
*
]

Value in AnOut range


but above scaled
range

0...100 %

Value < AnOut range

MEASO:
Output value x

Address

AnOut value

X: 1

037 120
037 121

X: 3

037 122

c1
c2
c3
1
2

AnOut min. value

X: 2

MEASO:
Value A-1 valid
[ 069 014 ]

and in scaled range

3
1...3

AnOut max. value

MEASO:
Current A-1
[ 005 100 ]

Selected meas. val.


Value not measured
Selected meas. val.
Value measured
Selected meas. val.
Overflow

S8Z52H8B

Fig. 3-39: Analog measured data output.

P437/EN M/R-11-A // P437311650

3-63

P437
3.10.4

3 Operation

Output of External Measured Data


Measured data from external devices, which must be scaled to 0 ... 100%, can be
written to the following parameters of the P437 via the communications
interface.

MEASO : Out put valu e 1

MEASO: Out put valu e 1

ME AS O: Out put valu e 1

These external measured values are output by the P437 either in BCD data
form or as load-independent direct current, provided that the BCD measured
data output function or the channels of the analog measured data output
function are configured accordingly.

3-64

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.11

Configuration and Operating Mode of the LED Indicators


(Function Group LED)
The P437 has 23 LED indicators for the indication of binary signals. Some of the
LED indicators are permanently assigned to fixed functions. The other LED
indicators are freely configurable. These freely configurable LEDs will emit either
red or green or amber light (amber is made up of red and green light and may
not be configured independently).

3.11.1

Configuring the LED Indicators


One binary signal can be assigned to each of the red and green LED color
indications. The same binary signal can be assigned to several LED indicators (or
colors), if required.

LED indicator

Label

Configuration

H 1 (green)

HEALTHY

Not configurable. H 1 indicates the operational readiness of the


P437 (supply voltage is present).

H 17 (red)

EDIT MODE

Not configurable. H 17 indicates the input (edit) mode. Only when


the P437 is in this mode, can parameter settings be changed by
pressing the Up and Down keys. (See Section 6.2, (p. 6-2))

H 2 (amber)

OUT OF SERVICE

Permanently configured with function MA IN: B locked/ fault y.

H 3 (amber)

ALARM

Permanently configured with function SFMON: Warning (L ED).

H 4 (red)

TRIP

With the P437 this LED indicator is customarily configured with


function MAIN: Ge n. trip s ign al, but the configuration may be
modified.

H 4 (green)

Function assignment to this green LED indicator is freely


configurable.

H 5 to H 16

For each of these LED indicators both colors (red & green) may
be configured freely and independently.

3.11.2

Layout of the LED Indicators


The following figure illustrates the layout of LED indicators situated on the local
control panel.

P437/EN M/R-11-A // P437311650

3-65

P437

3 Operation

TRIP

H18

ALARM
OUT OF SERVICE
HEALTHY

H19

EDIT MODE

H20

H21

H22

H23

Fig. 3-40: Layout of the LED indicators.

3.11.3

Operating Mode of the LED Indicators


For each of the freely configurable LED indicators, the operating mode can be
selected separately. This setting will determine whether the LED indicator will
operate either in energize-on-signal (ES) or normally-energized (NE) mode,
whether it will be flashing and whether it will be in latching mode.
Latching is disabled, depending on the selected operating mode:

either manually via setting parameters or by an appropriately configured


binary signal input (see Section 3.12.12, (p. 3-106))

or at the onset of a new fault, signalized by the onset of a general starting


or of a new system disturbance.

Therefore there are eight operating modes available, which are built from
combinations of the following components:

continuous (i.e. not


flashing)

flashing

updating

latching with manual


reset

energize-on-signal
(ES)

ES updating

ES manual reset

normally-energized
(NE)

NE updating

NE manual reset

energize-on-signal
(ES)

ES updating bl

ES manual reset bl

normally-energized
(NE)

NE updating bl

NE manual reset bl

In addition to these there are the following 4 operating modes:


3-66

P437/EN M/R-11-A // P437311650

P437

3 Operation

energize-on-signal (ES) with reset


after new fault

energize-on-signal (ES) with reset


after new system disturbance

continuous (i.e. not


flashing)

ES reset (fault)

ES reset (syst.dist)

flashing

ES reset (fault) bl

ES rst (syst.dst) bl

Finally, as the 13th operating mode, every LED (except the permanently
configured ones, see Section 3.11.1, (p. 3-65)) can be set to the mode ES
Alarmunit. This mode has the following flashing behavior:

The LED starts flashing with the first starting of the signal that has been
assigned to it.
The LED assumes the color that has been assigned via setting parameter. If
both colors (red and green) have been configured to different signals, and
these two signals both become active then the LED flashes in amber color.

If an LED reset is executed and the configured signal is still active the LED
changes to continuous light.
Important: If the LED was flashing in amber color then this color is kept,
even if one of the two signals is no longer active.

If all the configured signals are no longer active at the time of the LED
reset, or become inactive at a later time, the LED goes out.

If later, after the LED has gone out, any of the configured signals becomes
active again then the LED starts flashing again (in the assigned color).
If both colors have been configured and the LED shines continuously in
amber color, then it is possible that one of these two signals becomes
inactive and active again whilst the other signal stays active all the time. In
this case the LED starts flashing again with the starting of that signal. But
since the LED permanently keeps the amber color it is no longer possible to
tell the two signals from each other. Therefore general caution is
recommended whenever two different signals are configured to an LED
with this operating mode.

P437/EN M/R-11-A // P437311650

3-67

P437

3 Operation

LED:
Oper. mode H xx
[ xxx xxx ]

1
2
3
4
5
6
7
8
9
10
11
12
13

1: ES updating
2: ES manual reset
3: ES reset (fault)
4: ES reset (syst.dist)
5: NE updating
6: NE manual reset
7: ES updating bl
8: ES manual reset bl
9: ES reset (fault) bl
10: ES rst (syst.dst) bl
11: NE updating bl
12: NE manual reset bl
13: ES Alarmunit

!G!

-Hxx (red)

&

LED:
State Hxx red
[ zzz zzz ]

&

LED:
Fct.assig. Hxx red
[ yyy yyy ]

&
Signal
Signal
Signal
Signal

1
2
3
n

&

&

m out of n

Selected signals

&

S1 1

&

R1

&

FT_RC:
Record. in progress
[ 035 000 ]
FT_RC:
System disturb. runn
[ 035 004 ]

&
&

MAIN:
General reset EXT
[ 005 255 ]
MAIN:
General reset USER
[ 003 002 ]
1: execute
MAIN:
Reset LED
306 020

47Z8000A

Fig. 3-41: Configuration and Operating Mode of the LED Indicators, showing the example of the red LED color.

3-68

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.12

Main Functions of the P437 (Function Group MAIN)

3.12.1

Conditioning of the Measured Variables


The secondary phase currents of the system transformers are fed into the P437
and are electrically isolated converted to normalized electronics levels. Airgap transformers are used in the phase current path to suppress low frequency
(DC decays and offsets) signal components. The analog quantities are digitized
and are thus available for further processing.
Settings that do not refer to nominal quantities are converted by the P437 to
nominal quantities. The user must therefore set the secondary nominal currents
and voltages of the system transformers.
The connection direction of the measuring circuits on the P437 must also be set.
The diagram below shows the standard connection. By this setting the phase of
the digitized currents is rotated by 180.

P437/EN M/R-11-A // P437311650

3-69

P437

3 Operation

A
B
C

MAIN:
Vref,nom V.T. sec.
[ 031 052 ]
1U
Vref

2U

MAIN:
Conn. meas. circ. IP
[ 010 004 ]

IA

MAIN:
Inom device
[ 010 003 ]

XY

IA

XY

IB

IC

XY

IC

IN

1: Standard
(Y = 1)
2: Opposite

IB

(Y = -1)
MAIN:
Conn. meas. circ. IN
[ 010 019 ]
X

MAIN:
IN,nom device
[ 010 026 ]

XY

IN

1: Standard
(Y = 1)
2: Opposite
(Y = -1)
MAIN:
Conn.meas.crc.IN,par
[ 010 020 ]

MAIN:
IN,nom device
[ 010 023 ]

2IN
X

XY

IN,par

1: Standard
(Y = 1)
2: Opposite
(Y = -1)

Parallel line

MAIN:
VNG,nom V.T. sec.
[ 010 028 ]
N(e)
E(n)

VN-G

U
V

MAIN:
Vnom V.T. sec.
[ 010 009 ]

VA-G
VB-G

VC-G

Line
47Z0203B

Fig. 3-42: Connecting the P437 measuring circuits. (If markings P1 P2 and S1 S2 are used for CT polarity
then the dots shown here represent the P1 and S1 terminals.)

3-70

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.12.2

Operating Data Measurement


The P437 has an operating data measurement function for the display of currents
and voltages measured as well as quantities derived from these measured
values. For the display of measured values, set lower thresholds need to be
exceeded, to avoid fluctuating small values from noise. If these lower thresholds
are not exceeded, the value Not measured is displayed. The following measured
variables are displayed:

Phase currents for all three phases

Delayed and stored phase currents for all three phases demand values for
the three phases

Minimum and maximum phase current

Delayed and stored maximum phase current maximum demand values

Residual current measured by the P437 at the T 4 transformer, and


calculated resultant current

Residual current of the parallel line, which is measured by the P437 at the
T 24 transformer

Calculated unfiltered resultant current

Phase-to-ground voltages

Sum of the three phase-to-ground voltages and neutral-point displacement


voltage measured by the P437 at the T 90 transformer

Reference voltage measured by the P437 at the T 15 transformer

Phase-to-phase voltages

Minimum and maximum phase-to-phase voltage and minimum and


maximum phase-to-ground voltage

Positive-sequence current and negative-sequence current (in units of Inom),


taking into account the set phase sequence

Positive-sequence voltage and negative-sequence voltage (in units of Vnom)

Active, reactive and apparent power

Active power factor

Active and reactive energy output and input

Load angle in all three phases

Angle between measured residual current and measured neutral-point


displacement voltage

Phase relation between measured neutral current and calculated residual


current (binary indication of equal or reverse phase)

System frequency

The measured data are updated at 1 s intervals. Updating is interrupted if the


self-monitoring function detects a hardware fault.

P437/EN M/R-11-A // P437311650

3-71

P437
3.12.2.1

3 Operation

Measured Current Values


The measured current values are displayed both as per-unit quantities referred
to the nominal quantities of the P437 and as primary quantities. To allow display
in primary values, the primary nominal current of the system current transformer
should be set in the P437.
Phase sequence A-B-C (clockwise rotating field)

Negative-sequence current:

I neg = 3 | (I A + a 2 I B + a I C) |



Positive-sequence current:

I pos = 3 | (I A + a I B + a 2 I C) |



Phase sequence A-C-B (anti-clockwise rotating field)

Negative-sequence current:

I neg = 3 | (I A + a I B + a 2 I C) |



Positive-sequence current:

I pos = 3 | (I A + a 2 I B + a I C) |



Symbols used:

a = e2j/3 = e j120

a 2 = e4j/3 = e j240

3-72

P437/EN M/R-11-A // P437311650

P437

3 Operation

MAIN:
Meas. value rel. IP
[ 011 030 ]

MAIN:
General start. int.
306 539

MAIN:
Hardware fault

306 540

IA

c1

IB

c2

IC

c3
c4
c5
c6

+
+
+

MAIN:
Current A p.u.
[ 005 041 ]

MAIN:
Current B p.u.
[ 006 041 ]

MAIN:
Current C p.u.
[ 007 041 ]

MAIN:
Current (IP) p.u.
[ 005 011 ]

MAIN:
Current IP,max p.u.
[ 005 051 ]

MAIN:
Current IP,min p.u.
[ 005 056 ]

COMP

Imax
Imin

MAIN:
Inom C.T. prim.
[ 010 001 ]

MAIN:
Current A prim.
[ 005 040 ]
MAIN:
Current B prim.
[ 006 040 ]
MAIN:
Current C prim.
[ 007 040 ]
MAIN:
Current (IP) prim.
[ 005 010 ]
MAIN:
Curr. IP,max prim.
[ 005 050 ]
MAIN:
Curr. IP,min prim.
[ 005 055 ]

19Z6403A

Fig. 3-43: Measured operating data - phase current, part 1.

P437/EN M/R-11-A // P437311650

3-73

P437

3 Operation

MAIN:
IA p.u.,demand
[ 006 235 ]
MAIN:
IB p.u.,demand
[ 006 236 ]
MAIN:
IC p.u.,demand
[ 006 237 ]
MAIN:
Settl. t. IP,max,del
[ 010 113 ]

MAIN:
IP,max p.u.,delay
[ 005 037 ]

MAIN:
IA p.u.,demand stor.
[ 006 232 ]

MAIN:
Current B p.u.
[ 006 041 ]

MAIN:
IB p.u.,demand stor.
[ 006 233 ]

MAIN:
Current C p.u.
[ 007 041 ]

MAIN:
Current IP,max p.u.
[ 005 051 ]

MAIN:
Current A p.u.
[ 005 041 ]

MAIN:
IC p.u.,demand stor.
[ 006 234 ]
MAIN:
IP,max p.u.,stored
[ 005 035 ]

MAIN:
Inom C.T. prim.
[ 010 001 ]

MAIN:
IA prim,demand
[ 006 226 ]
MAIN:
IB prim,demand
[ 006 227 ]
MAIN:
IC prim,demand
[ 006 228 ]
MAIN:
IP,max prim.,delay
[ 005 036 ]

MAIN:
Reset IP,max,st.USER
[ 003 033 ]

MAIN:
IA prim,demand stor.
[ 006 223 ]
0
1

MAIN:
General reset USER
[ 003 002 ]
1: execute
MAIN:
General reset EXT
[ 005 255 ]
MAIN:
Rst IP,max,stor. EXT
[ 005 211 ]

0: don't execute
1: execute

MAIN:
IB prim,demand stor.
[ 006 224 ]
MAIN:
IC prim,demand stor.
[ 006 225 ]
MAIN:
IP,max prim.,stored
[ 005 034 ]

19Z6404A

Fig. 3-44: Measured operating data - phase current, part 2: demand values (delayed and stored phase currents and
maximum phase current).

3-74

P437/EN M/R-11-A // P437311650

P437

3 Operation

MAIN:
General start. int.
306 539

MAIN:
Meas. value rel. IN
[ 011 031 ]

MAIN:
Hardware fault
306 540

IN

MAIN:
Current IN p.u.
[ 004 044 ]
MAIN:
IN,nom C.T. prim.
[ 010 018 ]

MAIN:
Current IN prim.
[ 004 043 ]

S8Z5097A

Fig. 3-45: Measured operating data - residual current.

MAIN:
General start. int.
306 539

MAIN:
Meas.val.rel. IN,par
[ 011 043 ]

MAIN:
Hardware fault
306 018

IN,par

MAIN:
Current IN par p.u.
[ 008 001 ]
MAIN:
IN,nom,par C.T. prim
[ 010 152 ]

MAIN:
Current IN,par prim.
[ 008 000 ]

47Z0210A

Fig. 3-46: Measured operating data residual current of the parallel line.

3.12.2.2

Display of Demand Values Delayed Maximum Phase Current


The P437 offers the option of a delayed display of the maximum value of the
three phase currents (thermal ammeter function). The delayed maximum phase
current display is an exponential function of the maximum phase current IP,max
(see upper curve in Fig. 3-47, (p. 3-76)). The time after which the delayed
maximum phase current display will have reached 95 % of maximum phase
current IP,max is set at MAI N: Settl . t. IP ,max,del.

3.12.2.3

Display of Demand Values Stored Maximum Phase Current


The stored maximum phase current follows the delayed maximum phase current.
If the value of the delayed maximum phase current is declining, then the highest
value of the delayed maximum phase current remains stored. The display
remains constant until the actual delayed maximum phase current exceeds the
value of the stored maximum phase current (see middle curve in Fig. 3-47, (p. 376)). The stored maximum phase current to the actual value of the delayed
maximum phase current is set at MA IN: Re s et IP ,max ,s t. USE R (see lower
curve in Fig. 3-47, (p. 3-76)).

P437/EN M/R-11-A // P437311650

3-75

P437
3.12.2.4

3 Operation

Display of Demand Values Delayed and Stored Values of the Three


Phase Currents
The P437 offers the option of a delayed display of the three phase currents. This
functionality is equivalent to the display of the maximum value of the three
phase currents. However, in this case, the delayed phase current display will
have reached 90 % (not 95 %) of IA , IB or IC , respectively, after the set delay.
The stored phase currents are implemented as for the stored maximum phase
current.
The delay for these six operating data values is set at MAIN: Se ttl. t.
IP,max,del as for the delayed maximum phase current.

MAIN:
Current IP,max p.u.
[ 005 051 ]

MAIN:
IP,max p.u.,delay
[ 005 037 ]

MAIN:
Settl. t. IP,max,del
[ 010 113 ]

MAIN:
Settl. t. IP,max,del
[ 010 113 ]

MAIN:
Settl. t. IP,max,del
[ 010 113 ]

MAIN:
Settl. t. IP,max,del
[ 010 113 ]

MAIN:
Settl. t. IP,max,del
[ 010 113 ]

MAIN:
Settl. t. IP,max,del
[ 010 113 ]

MAIN:
Current IP,max p.u.
[ 005 051 ]

MAIN:
IP,max p.u.,stored
[ 005 035 ]

MAIN:
Current IP,max p.u.
[ 005 051 ]

MAIN:
IP,max p.u.,stored
[ 005 035 ]

MAIN:
Reset IP,max,st.USER
[ 003 033 ]
MAIN:
Rst IP,max,stor. EXT
[ 005 211 ]

50Z0115A

Fig. 3-47: Operation of delayed and stored maximum phase current display display of demand values.

3-76

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.12.2.5

Measured Voltage Values


The measured voltage values are displayed both as per-unit quantities referred
to the nominal quantities of the P437 and as primary quantities. To allow a
display in primary values, the primary nominal voltage of the system transformer
needs to be set in the P437.

COMP

VA-G
VB-G
VC-G
VPG,max

VPG,max

VPG,min

VPG,min

+
+
+

(VPG)/3

(VPG)/3

VA-B

VB-C

VC-A

MAIN:
Phase sequence

COMP

[ 010 049 ]

VPP,max

VPP,max

VPP,min

VPP,min

1: A - B - C
2: A - C - B
Vneg

Vneg

Vpos

Vpos

47Z0106A

Fig. 3-48: Determining the minimum and maximum phase-to-ground and phase-to-phase voltages as well as the
negative-sequence and positive-sequence voltages.

P437/EN M/R-11-A // P437311650

3-77

P437

MAIN:
General start. int.

3 Operation

306 539

MAIN:
Hardware fault
306 540

MAIN:
Meas. value rel. V
[ 011 032 ]

VA-G

C1

VB-G

C2

VC-G

C3

VPG,max

C4

VPG,min

C5

(VPG)/3

C6

VA-B

C7

VB-C

C8

VC-A

C9

VPP,max

C10

VPP,min

C11

Vneg

C12

Vpos

C13

MAIN:
Voltage A-G p.u.
[ 005 043 ]
MAIN:
Voltage B-G p.u.
[ 006 043 ]
MAIN:
Voltage C-G p.u.
[ 007 043 ]
MAIN:
Voltage VPG,max p.u.
[ 008 043 ]
MAIN:
Voltage VPG,min p.u.
[ 009 043 ]
MAIN:
Volt. (VPG)/3 p.u.
[ 005 013 ]
MAIN:
Voltage A-B p.u.
[ 005 045 ]
MAIN:
Voltage B-C p.u.
[ 006 045 ]

1
2
3
4
5
6
7

MAIN:
Voltage C-A p.u.
[ 007 045 ]
MAIN:
Voltage VPP,max p.u.
[ 008 045 ]
MAIN:
Voltage VPP,min p.u.
[ 009 045 ]
MAIN:
Voltage Vneg p.u.
[ 009 017 ]
MAIN:
Voltage Vpos p.u.
[ 009 018 ]

8
9
10
11
12
13
MAIN:
Vnom V.T. prim.
[ 010 002 ]

MAIN:
Voltage A-G prim.
[ 005 042 ]
MAIN:
Voltage B-G prim.
[ 006 042 ]
MAIN:
Voltage C-G prim.
[ 007 042 ]
MAIN:
Volt. VPG,max prim.
[ 008 042 ]
MAIN:
Volt. VPG,min prim.
[ 009 042 ]
MAIN:
Volt. (VPG)/3 prim.
[ 005 012 ]
MAIN:
Voltage A-B prim.
[ 005 044 ]
MAIN:
Voltage B-C prim.
[ 006 044 ]
MAIN:
Voltage C-A prim.
[ 007 044 ]
MAIN:
Volt. VPP,max prim.
[ 008 044 ]
MAIN:
Volt. VPP,min prim.
[ 009 044 ]
MAIN:
Volt. VPP,min prim.
[ 009 044 ]

12Z6204B

Fig. 3-49: Measured operating data phase-to-ground and phase-to-phase voltages.

3-78

P437/EN M/R-11-A // P437311650

P437

3 Operation

MAIN:
General start. int.
306 539

MAIN:
Hardware fault
306 018

MAIN:
Meas. val. rel. VNG
[ 011 033 ]

VN-G

MAIN:
Voltage VNG p.u.
[ 004 042 ]
MAIN:
VNG,nom V.T. prim.
[ 010 027 ]

MAIN:
Voltage VNG prim.
[ 004 041 ]

19Z5064A

Fig. 3-50: Measured operating data neutral-point displacement voltage.

MAIN:
Meas. val. rel. Vref
[ 011 034 ]
MAIN:
Hardware fault
306 018

Vref

MAIN:
Voltage Vref p.u.
[ 005 047 ]
MAIN:
Vref,nom V.T. prim.
[ 010 100 ]

MAIN:
Voltage Vref prim.
[ 005 046 ]

47Z0109A

Fig. 3-51: Measured operating data reference voltage.

P437/EN M/R-11-A // P437311650

3-79

P437
3.12.2.6

3 Operation

Measured Values for Power, Active Power Factor, and Angle


Calculation of these derived operating quantities is subject to the following
conditions:

Values for active and reactive power will always be calculated and
displayed as these quantities are required for the subsequent energy
measurement. Greater deviations in measurements may occur with low
phase currents or a critical power factor value.

The active power factor will be calculated only if the apparent power value
exceeds 5% of the nominal apparent power Snom.

Load angles will be displayed only if the respective phase current exceeds
0.1Inom and if the phase-to-ground voltage exceeds 1.5 V.

The angle between the measured values for the residual current and the
neutral-point displacement voltage will only be displayed if the residual
current exceeds 0.02IN,nom and the neutral-point displacement voltage
exceeds 1.5 V.

The setting for MAIN : Meas . di recti on P,Q may be changed from Standard to
Opposite if the user wishes to have the following measured operating data
displayed with the opposite sign (see Fig. 3-52, (p. 3-81)):

MAI N: Acti ve power P p. u.

MAI N: Reac. power Q p.u .

MAI N: Act ive power P pri m.

MAI N: Reac. power Q prim.

This setting parameter does not influence the remaining measured operating
data. It must be noted that inverting the sign will only affect the display of
measured operating data, all protection functions will internally use non-inverted
measured values.

3-80

P437/EN M/R-11-A // P437311650

P437

3 Operation

MAIN:
Inom C.T. prim.
[ 010 001 ]
MAIN:
Vnom V.T. prim.
[ 010 002 ]

MAIN:
Appar. power S p.u.
[ 005 026 ]

S > 0.05 Snom

MAIN:
Active power factor
[ 004 054 ]
IA

> 0.025 Inom

IB

MAIN:
Meas. direction P,Q
[ 006 096 ]

> 0.025 Inom

IC

> 0.025 Inom

VA-G

> 1.5 V

VB-G

> 1.5 V

VC-G

> 1.5 V

IN

> 0.02 INnom

X Y

X Y

X Y

X Y

1: Standard
(Y = 1)
2: Opposite
(Y = -1)

&
VN-G

> 1.5 V

MAIN:
Appar. power S prim.
[ 005 025 ]

MAIN:
Active power P p.u.
[ 004 051 ]
MAIN:
Reac. power Q p.u.
[ 004 053 ]
MAIN:
Active power P prim.
[ 004 050 ]
MAIN:
Reac. power Q prim.
[ 004 052 ]

MAIN:
Load angle phi A p.u
[ 005 073 ]

MAIN:
Load angle phi A
[ 004 055 ]

&

MAIN:
Load angle phi B p.u
[ 005 074 ]
MAIN:
Load angle phi B
[ 004 056 ]

&

MAIN:
Load angle phi C p.u
[ 005 075 ]
MAIN:
Load angle phi C
[ 004 057 ]

&

MAIN:
Angle phi N p.u.
[ 005 076 ]

MAIN:
Angle phi N
[ 004 072 ]

&

+
+
+

MAIN:
Angle VPG/IN p.u.
[ 005 072 ]

MAIN:
Angle VPG vs. IN
[ 005 009 ]

MAIN:
Hardware fault
306 018

19Z8003A

Fig. 3-52: Measured operating data power, active power factor, and angle.

P437/EN M/R-11-A // P437311650

3-81

P437

3 Operation

3.12.2.7

Phase Relation IN
The P437 checks if the phase relations of calculated residual current and
measured residual current are coherent. If the phase displacement between the
two currents is 45, then the indication Equal phase is displayed.

IA
IB
IC
IN
1

MAIN:
Phase rel. IN vs IP
[ 004 073 ]

1: Equal phase
2: Reverse phase

47Z0112A

Fig. 3-53: Phase relation between calculated and measured residual current.

3.12.2.8

Phase Relation Between Phase-to-Ground Voltage A and Residual


Currents
The P437 determines the phase displacement between the phase-to-ground
voltage VAG and the residual currents measured at transformers T 14 and T 24.

MAIN:
General start. int.

306 539

MAIN:
Hardware fault
306 018

IN

>0.02 INnom

IN,par

>0.02 INnom

VA-G

> 1.5 V

&

&

MAIN:
Angle VAG, IN
[ 008 004 ]

MAIN:
Angle VAG, IN,par
[ 008 003 ]

47Z8013

Fig. 3-54: Phase relation between phase-to-ground voltage A and residual currents.

3.12.2.9

Frequency
The P437 determines the frequency from the voltage VA-B. This voltage needs to
exceed a minimum threshold of 0.65 Vnom in order for frequency to be
determined.

3-82

P437/EN M/R-11-A // P437311650

P437

3 Operation

MAIN:
General start. int.

306 539

MAIN:
Hardware fault

>0.65Vnom

306 018

VA-G

VB-G

MAIN:
Frequency f p.u.
[ 004 070 ]

MAIN:
Frequency f
[ 004 040 ]

12Z6209A

Fig. 3-55: Frequency measurement.

P437/EN M/R-11-A // P437311650

3-83

P437
3.12.2.10

3 Operation

Active and Reactive Energy Output and Input


The P437 determines the active and reactive energy output and input based on
the primary active or reactive power.
There are two procedures available to determine active and reactive energy. If
procedure 1 is selected, active and reactive energy are determined every 2 s
(approximately). If procedure 2 is selected, active and reactive energy are
determined every 100 ms (approximately). In this way higher accuracy is
achieved.
Measured energy values are presented as text parameters with a value range of
about 0 6.5 TWh and a resolution of 10 kWh. In addition, 16 bit values and
overflow counters are provided, which are needed for transmission via serial
protocols (e.g. Modbus, DNP3, Courier).

Energy values as 32 bit / text


values

Energy values as 16 bit values


Value range: 0 655,35 MWh

Value range: 0
6553500.00 MWh

Overflow counters for the 16 bit


energy values
Value range: 0 10000

(008 065) MAIN: Act .energy


ou tp. prim

(005 061) MAI N: A ct. en ergy


outp.pri m

(009 090)
MA IN: No.overfl .act.en.out

(008 066) MAIN: Act .energy


in p. p rim

(005 062) MAI N: A ct.en ergy


inp. prim

(009 091)
MA IN: No.overfl. act.e n.inp

(008 067) M AIN: React .en.


outp. prim

(005 063) MA IN: React.e n.


out p. prim

(009 092) MAI N: No.ov/


fl .re ac.en.ou t

(008 068) MAIN: R eact . en.


inp. prim

(005 064) MA IN: React. en .


inp. prim

(009 093) MA IN: No.ov/


f l.reac.en .in p

The total energy is calculated as follows:


Total energy = number of overflows 655.35 + current count
For example:
(MAIN : Act .en ergy outp. pri m) = (MA IN: No.overfl.act.en.out) 655.35 +
(MAIN : Act .en ergy outp. pri m)

3-84

P437/EN M/R-11-A // P437311650

P437

3 Operation

MAIN:
Op. mode energy cnt.
[ 010 138 ]

MAIN:
Active power P prim.
[ 004 050 ]

P(t) dt

MAIN:
Act.energy outp.prim
[ 005 061 ]

-P(t) dt

MAIN:
Act.energy inp. prim
[ 005 062 ]

Q(t) dt

MAIN:
React.en. outp. prim
[ 005 063 ]

-Q(t) dt

MAIN:
React. en. inp. prim
[ 005 064 ]

MAIN:
Reac. power Q prim.
[ 004 052 ]
MAIN:
Reset meas.v.en.USER
[ 003 032 ]

0
1

0: don't execute
1: execute

Overflow
Transfer

MAIN:
Rst meas.v.ener. EXT
[ 005 212 ]
Overflow
Transfer

Overflow
Transfer

Overflow
Transfer

MAIN:
No.overfl.act.en.out
[ 009 090 ]

MAIN:
No.overfl.act.en.inp
[ 009 091 ]

MAIN:
No.ov/fl.reac.en.out
[ 009 092 ]

MAIN:
No.ov/fl.reac.en.inp
[ 009 093 ]

19Z8033A

Fig. 3-56: Determining the active and reactive energy output and input.

P437/EN M/R-11-A // P437311650

3-85

P437
3.12.2.11
Procedure

3 Operation

Selection of the Procedure to Determine Energy Output


Characteristics

Applications

Determination of the active and


reactive energy every 2 s
(approximately)

Constant load and slow load


variations (no significant load
variations within 1 second).

Reduced system loading

Phase angles below 70


(cos > 0.3 ).

Determination of the active and


reactive energy every 100 ms
(approximately).

Fast load variations

Phase angles below 70


(cos > 0.3 ).

Increased system loading

Fault

The maximum phase-angle error of the P437 of 1 leads to greater errors in


measurement when the phase angle increases, as shown (for the range
0 < 90) in the following diagram.

5%

2%

45

70

Phase Angle
S8Z0401B

Fig. 3-57: Error of measurement in the determination of energy output resulting from the phase angle error of the
P437.

Error of measurement:

Approx. 2% of the measured value for |cos | 0.7

Approx. 5% of the measured value for |cos | 0.3

where the whole measuring range is 180 180.

For phase angles with |cos | < 0.3, or when the error of measurement
resulting from the maximum phase-angle error is not acceptable, external
counters should be used to determine the energy output.

3-86

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.12.3

Configuring and Enabling the Device Functions


The P437 can be adapted to the requirements of a specific high-voltage system
by configuring the available function range. By including the desired P437
functions in the configuration and canceling all other, the user creates an
individually configured device appropriate to the specific application. Parameters,
signals and measured values of cancelled device functions are not displayed on
the local control panel. Functions of general applicability such as operating data
recording (OP_RC) or main functions (MAIN) cannot be cancelled.

3.12.3.1

Canceling a Device Function


The following conditions must be met before a P437 function can be cancelled or
removed:

The P437 function must be disabled.

None of the functions of the P437 function to be cancelled can be assigned


to a binary input.

None of the signals of the P437 function can be assigned to a binary output
or an LED indicator.

None of the functions of the P437 function to be cancelled may be selected


in a list parameter setting.

If the above conditions are met, proceed through the Configuration branch of
the menu tree to access the setting relevant for the P437 function to be
cancelled. If, for example, the LIMIT function group is to be cancelled, the
setting of LI MI T: Function gr ou p L IMI T is set to Without. To re-include the
LIMIT function in the P437 configuration, the same setting is accessed and its
value is changed to With.
The P437 function to which a setting, a signal, or a measured value belongs is
defined by the function group designation (example: LIMIT). In the following
description of the P437 functions, it is presumed that the corresponding P437
function is included in the configuration.
3.12.3.2

Enabling or Disabling a Device Function


Besides cancelling P437 functions from the configuration, it is also possible to
disable protection via a function parameter or binary signal inputs. Protection
can only be disabled or enabled through binary signal inputs if the
MAIN : D isab le protect. EXT and MAIN: E nabl e prot ect. E XT functions are
both configured. When neither or only one of the two functions is configured, the
condition is interpreted as Protection externally enabled. If the triggering
signals of the binary signal inputs are implausible i.e. both are at logic level =
1 then the last plausible state remains stored in memory.
If the protection is disabled via a binary signal input that is configured for
M A I N : D i s a b l e p r o t e c t . E X T, the signal M A I N : B l o c k e d / f a u l t y is not issued.

P437/EN M/R-11-A // P437311650

3-87

P437

3 Operation

MAIN:
Device on-line
[ 003 030 ]
0

0: No (= off)

MAIN:
Protection active
306 001

0: No (= off)
1: Yes (= on)

INP:
Fct. assignm. U xxx
[ 152 xxx ]

U x1
U x2
U x3
U xx

Address

003 027

Address

003 026

MAIN:
Enable protect. EXT
[ 003 027 ]

MAIN:
Prot. ext. enabled
[ 003 028 ]

MAIN:
Prot. ext. disabled
[ 038 046 ]

MAIN:
Disable protect. EXT
[ 003 026 ]

D5Z5004A

Fig. 3-58: Enabling or disabling a device function.

3.12.4

Current Flow Monitoring


The current flow is monitored continuously and pole-selectively, independent of
the current flow monitoring performed by the CBF function. The sampled current
values are continuously compared with the fixed threshold value 0.05Inom.
As long as current flow criteria are met the monitoring function will continuously
issue the phase selective signals MA IN: Curre nt flow A, MA IN : C urr ent flow
B, MAIN : Cu rre nt fl ow C.

>0.05Inom
IA

IB

MAIN:
Current flow A
[ 010 223 ]
MAIN:
Current flow B
[ 010 224 ]

IC

MAIN:
Current flow C
[ 010 225 ]

19Z8039A

Fig. 3-59: Current flow monitoring.

3-88

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.12.5

Inrush Stabilization (Harmonic Restraint)


The inrush stabilization function detects high inrush current flows that occur
when transformers or machines are switched on. For all selected stages of the
Definite-Time and Inverse-Time Overcurrent Protection (DTOC, IDMT), of the
Backup Overcurrent Protection (BUOC) and of the Distance Protection (DIST), the
selective starting will be blocked if an inrush current flow is detected.
The inrush stabilization function detects an inrush current by evaluating the ratio
of the second harmonic current component to the fundamental. If this ratio
exceeds the threshold that can be set with the parameter MA IN: Ru sh I(2 fn)/
I(fn)PS x, then the inrush stabilization operates.
The current trigger MAI N: I > l i ft rush r. P Sx and a fixed threshold of 0.1 Inom
define the range in which the inrush stabilization operates. If the current is
outside of this range then the inrush stabilization is blocked.
The parameter MAIN: t li ft rush r str.PSx defines the maximum hold-time for
the inrush stabilization.

MAIN:
Protection active

&

MAIN:
I> lift rush r. PSx
[
*
]

MAIN:
t lift rush rstr.PSx
[
*
]

306 001

&

MAIN:
Rush restr. A trig.

&

&

[ 041 028 ]

&

[ 041 029 ]

[ 041 027 ]

IA

&
IB

&

MAIN:
Rush restr. B trig.

MAIN:
Rush restr. C trig.

IC

>0.1 Inom

&
MAIN:
Op. mode rush r. PSx
[

]
MAIN:
Inrush stabil. trigg

306 014

1
2

MAIN:
Rush I(2fn)/I(fn)PSx

0: Without
1: Not phase-selective

2: Phase-selective
fnom
I(2fn)/I(fn)

2*fnom

Parameter

MAIN:
Op. mode rush r. PSx

MAIN:
I> lift rush r. PSx

set 1

017 097

017 095

set 2

001 088

001 085

set 3

001 089

001 086

set 4

001 090

001 087

fnom
2*fnom

I(2fn)/I(fn)

fnom
2*fnom

I(2fn)/I(fn)

Parameter

MAIN:
Rush I(2fn)/I(fn)PSx

MAIN:
t lift rush rstr.PSx

set 1

017 098

019 001

set 2

001 091

019 002

set 3

001 092

019 003

set 4

001 093

019 004

12Z7306A

Fig. 3-60: Inrush stabilization.

P437/EN M/R-11-A // P437311650

3-89

P437

3 Operation

3.12.5.1

Selection of Functions
The inrush stabilization is designed with respect to function groups DIST, BUOC,
DTOC and IDMT. Depending on the parameter MA IN: Funct.Rush restr. PSx
the starting of these function groups is blocked selectively.

MAIN:
Funct.Rush restr.PSx

m out of n

DIST:
Starting I>>
011 139

DIST:
Starting Z<

MAIN:
Inrush stabil. trigg

036 241

BUOC:
Starting

306 014

010 185

MAIN:
Rush restr. B trig.
[ 041 028 ]

MAIN:
Rush restr. C trig.
[ 041 029 ]

DTOC:
Bl.Start. I>>
450 209

035 021

DTOC:
Starting I>>>

450 207

DTOC:
Bl.Start. I>
450 208

035 020

DTOC:
Starting I>>

450 205

BUOC:
Block. Starting
BUOC:
Bl.Zero-sequ.start.

BUOC:
Zero-sequ. starting
DTOC:
Starting I>

450 204

DIST:
Bl.Start. Z<

450 206

036 013

MAIN:
Rush restr. A trig.
[ 041 027 ]

DIST:
Bl.Start. I>>

035 022

DTOC:
Bl.Start. I>>>
450 210

DTOC:
Starting I>>>>
035 023

DTOC:
Starting Ineg>
035 024

DTOC:
Starting Ineg>>

DTOC:
Bl.Start. I>>>>
450 211

DTOC:
Block.Start. Ineg>
450 153

DTOC:
Block.Start. Ineg>>
450 154

035 025

DTOC:
Starting Ineg>>>

DTOC:
Block.Start. Ineg>>>
450 155

035 026

DTOC:
Starting Ineg>>>>

DTOC:
Bl.Start. Ineg>>>>
450 212

035 027

DTOC:
Starting IN>
035 028

DTOC:
Starting IN>>
035 029

DTOC:
Starting IN>>>

DTOC:
Block. Start. IN>
450 149

DTOC:
Block. Start. IN>>
450 150

DTOC:
Block. Start. IN>>>
450 151

035 030

DTOC:
Starting IN>>>>

Parameter

MAIN:
Funct.Rush restr.PSx

set 1

017 093

set 2

017 064

set 3

017 082

set 4

017 083

DTOC:
Block. Start. IN>>>>

035 031

450 152

IDMT:
Starting Iref,P>

IDMT:
Bl.Start.Iref,P> Px

040 080

IDMT:
Starting Iref,N>

450 156

IDMT:
Bl.Start.Iref,N>

040 081

450 160

IDMT:
Starting Iref,neg>

IDMT:
Bl.Start.Iref,neg>

040 107

450 161

45Z8031A

Fig. 3-61: Selection of the stabilization criteria for the inrush stabilization.

3-90

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.12.6

Multiple Blocking
Two multiple blocking conditions can be defined via m out of n parameters.
The functions defined by selection may be blocked via an appropriately
configured binary signal input.

MAIN:
Fct.assign. block. 1
[ 021 021 ]
Function 1

m out of n

Function 2

Function 3
Selected functions

MAIN:
Blck.1 sel.functions
306 022

MAIN:
Blocking 1 EXT
[ 040 060 ]
MAIN:
Fct.assign. block. 2
[ 021 022 ]
Function 1

m out of n

Function 2

Function 3
Selected functions

MAIN:
Blck.2 sel.functions
306 023

MAIN:
Blocking 2 EXT
[ 040 061 ]

D5Z50CLA

Fig. 3-62: Multiple blocking.

P437/EN M/R-11-A // P437311650

3-91

P437
3.12.7

3 Operation

Blocked/Faulty
If the protective functions are blocked, the condition is signaled by continuous
illumination of the amber LED indicator H 2 on the local control panel and by a
signal from an output relay configured MA IN: B locked/fault y. In addition
functions can be selected that will issue the MA IN: Blocked/faulty signal by
setting a m out of n parameter.

MAIN:
Device on-line
[ 003 030 ]
0: No (= off)

MAIN:
Device not ready
[ 004 060 ]
MAIN:
Blocked/faulty
[ 004 065 ]

SFMON:
Blocking
304 951

MAIN:
Trip cmd. blocked
[ 021 013 ]
MAIN:
Fct. assign. fault
[ 021 031 ]
Signal 1
Signal 2

m out of n

Signal 3
Signal n
Selected signals

D5Z50EHA

Fig. 3-63: Blocked/Faulty signal.

3.12.8

Monitoring and Processing of CB Status Signals

Extended CB Status Signals


An extended monitoring of the circuit breaker (CB) status signals is available in
the main function group. It is possible to select whether the multiple signals
MAI N: C B closed 3p / MA IN : C B open 3p or pole selective Closed
status signals will be monitored. Simultaneous monitoring of all status signals is
not feasible and should therefore not be undertaken.
The diagram below shows the logical processing of the various input signals. The
plausibility logic will be triggered should one of the following discrepancies be
detected:

A minimum of one 3pole monitoring signal and one 1pole monitoring


signal are configured at the same time.

Both multiple signals MAI N: C B cl ose d 3p EXT and MA IN: C B open 3p


E XT are present simultaneously.

There is no pole-selective status signal (MA IN: CB closed A EX T or for B


or C) present (i.e. CB contact is open) but at the same time there is a
current flow exceeding 0.05Inom in this conductor.

In order to suppress triggering during transient actions, the signal issued when a
plausibility discrepancy is detected has a generally delayed pickup of 100 ms.
Besides monitoring for signaling purposes, status signals are also processed in
these functions:

3-92

P437/EN M/R-11-A // P437311650

P437

3 Operation

MAIN: Ending a CB (re-)close command.


If the (re-)close command is to be terminated by the CB closed signal
(setting at MAIN: RC i nh ib.by CB cl ose = Yes) then the resulting
MA IN: C B close d 3p signal is read.

ARC: Ready indication.


If the ARC should only be available when the circuit breaker has already
been closed (setting at ARC: CB clos.pos.s ig. PSx = With) then the
resulting signal MA IN: CB clos e d 3p is read.

ARC: Plausibility check on single-pole HSR.


If pole selective status signals have been configured then the device will
check that just this CB contact will be opened during a single-pole HSR. The
single-pole HSR is terminated and a three-pole trip command is issued
when at least one further CB contact is opened. This trip command is either
final (with AR C: HSR oper. mode P Sx = 1-pole or 1-/3-pole and with the
timer stage ARC: tDi scri m. P Sx having elapsed) or the dead time for the
three-pole HSR is triggered (with A RC : HSR ope r. m ode PSx = 1-/3-pole
and with the timer stage AR C: tD is cr im . PSx still running).
The same procedure is carried out should the multiple signal MAIN: CB
closed 3 p EXT occur during the dead time of a single-pole HSR.

PSIG and CSCSG: Un-delayed echo if CB is open.


If the CB is open, the echo signal (if enabled) is issued without additional
delay. For this the MAI N: CB open 3p signal is used.

MCMON: Release of negative-sequence voltage protection using CB


status indication.
With the operating mode set to Vneg w.CB cont.enab. the internally
generated MA IN: CB close d 3p signal is used.

P437/EN M/R-11-A // P437311650

3-93

P437

3 Operation

MAIN:
CB open 3p EXT
[ 031 028 ]

&

&
&

MAIN:
CB open 3p
[ 031 040 ]

&

[ 031 028 ]
configured

&

MAIN:
CB closed 3p EXT
[ 036 051 ]

MAIN:
CB open >=1p
[ 031 039 ]

&

MAIN:
CB closed 3p
[ 031 042 ]

&

MAIN:
CB closed >= 1p
[ 031 038 ]

&

&

MAIN:
CB closed A
[ 031 035 ]

&

&

MAIN:
CB open A
[ 031 032 ]

&

&

MAIN:
CB closed B
[ 031 036 ]

&

&

MAIN:
CB open B
[ 031 033 ]

&

&

MAIN:
CB closed C
[ 031 037 ]

&

&

MAIN:
CB open C
[ 031 034 ]

&
&
&

[ 036 051 ]
configured

MAIN:
CB closed A EXT
[ 031 029 ]

[ 031 029 ]
configured

MAIN:
CB closed B EXT
[ 031 030 ]

[ 031 030 ]
configured

MAIN:
CB closed C EXT
[ 031 031 ]

[ 031 031 ]
configured

10

100 ms
0

MAIN:
CB pos.sig. implaus.
[ 031 041 ]

>0.05 Inom
Plausibility
check
IA
IB
IC

47Z1021C

Fig. 3-64: Monitoring of CB status signals.

3.12.9

Close Command
The circuit breaker can be closed by the auto-reclosing control function (ARC), by
a setting parameter or via an appropriately configured binary signal input. The
close command by setting parameters or a binary signal input is only executed if
there is no trip command 1 present and no trip has been issued by a protection

3-94

P437/EN M/R-11-A // P437311650

P437

3 Operation

device operating in parallel. Moreover, with the setting of MA IN: RC inhib.by


CB close to Yes, the close command is not executed if there is a CB closed
position signal present. The signal MAI N: CB cl osed 3 p is read for this
purpose.
The duration of the close command can be set. The close command is reset when
the trip command is issued.
If the ARC function issues a close request while the ASC function is enabled, then
the close command requires a close enable by the ASC function.
Close Command Counter
The number of close commands are counted. This counter may be reset
individually or together with other counters (see Section 3.12.12, (p. 3-106)).
MAIN:
Gen. trip signal 1
[ 036 005 ]
MAIN:
Parallel trip EXT
[ 037 019 ]
MAIN:
Parallel trip A EXT
[ 036 052 ]
MAIN:
Parallel trip B EXT
[ 036 053 ]
MAIN:
Parallel trip C EXT
[ 036 054 ]
MAIN:
CB closed 3p
[ 031 042 ]
MAIN:
RC inhib.by CB close
[ 015 042 ]
0
1
0: No
1: Yes

MAIN:
Man. close cmd. USER
[ 018 033 ]
0
1

500ms

0: don't execute

[ 037 068 ]

1: execute
MAIN:
Man. close cmd. EXT
[ 041 022 ]

MAIN:
Close cmd.pulse time
[ 015 067 ]

MAIN:
Man.cl.cmd.enabl.EXT
[ 041 023 ]

1
t

[ 037 009 ]

ARC:
Close command
303 021

MAIN:
Reset c. cl/tr.cUSER
[ 003 007 ]
0
1

+
[ 009 055 ]

0: don't execute
MAIN:
General reset USER
[ 003 002 ]
1: execute

1: execute

MAIN:
General reset EXT
[ 005 255 ]
MAIN:
Reset.c.cl./tr.c EXT
[ 005 210 ]

47Z1322A

Fig. 3-65: Close command.

P437/EN M/R-11-A // P437311650

3-95

P437

3 Operation

3.12.10

Starting Signals and Tripping Logic

3.12.10.1

Starting Signals
The starting signals of the distance protection and backup overcurrent time
protection functions are linked to form common starting signals. The number of
general starting signals (GS) is counted.

MAIN:
General reset USER
[ 003 002 ]
1: execute

+
R

MAIN:
No. general start.
[ 004 000 ]

MAIN:
General reset EXT
[ 005 255 ]
DIST:
General starting
[ 036 240 ]
BUOC:
Starting
[ 036 013 ]

MAIN:
General starting
[ 036 000 ]

DIST:
Starting A

MAIN:
Starting A
[ 036 001 ]

303 529

BUOC:
IA> triggered
304 750

DIST:
Starting B

MAIN:
Starting B
[ 036 002 ]

303 530

BUOC:
IB> triggered
304 751

DIST:
Starting C

MAIN:
Starting C
[ 036 003 ]

303 531

BUOC:
IC> triggered
304 752

DIST:
Signal block start.G
303 594

&

DIST:
Starting N1

MAIN:
Starting GF
[ 036 004 ]

303 535

BUOC:
SN
304 757

45Z63ASA

Fig. 3-66: Fault detection signals of the P437.

For solidly grounded systems (setting MAIN: Neu tr.pt. treat. PSx = Lowimped. grounding), it can be selected whether a ground fault is determined by an
'OR'-linked or an 'AND'-linked condition of the IN> and VNG> detectors in the
distance protection. The parameter setting MA IN : Ground starting PSx may
then be used.
3.12.10.2

Phase Selection Logic


Various internal protection functions, such as distance protection, issue a phaseselective trip signal. Processing of such trip signals is shown in Fig. 3-68, (p. 399) below.
Other internal protection functions (e.g. overcurrent protection in the residual
current system in function groups DTOC-N and GFSC) and external protection
devices (MiCOM P547 for example) issue only a 3-pole trip signal. In order to
allow phase-selective single-pole tripping in case of single-phase-to-ground short
circuits the P437 now provides a faulted phase detection and trip selection logic.
This phase-selective trip is controlled by a new setting parameter and an existing
binary input function (see Fig. 3-67, (p. 3-98)). The P437 now features an m
out of n selection of trip signals in order to offer maximum flexibility.
In order to obtain a single-pole trip the selected trip signals must not be
configured into the trip command 1! (Setting M A I N : F c t . a s s i g . t r i p c m d . 1)

3-96

P437/EN M/R-11-A // P437311650

P437

3 Operation
In addition the function must be enabled by setting the four parameters
MAIN : Enab le 1p trip PSx.

When setting MA IN : Fct.as sig.tri p cm d.1 the following signals may be


selected:

All trip signals issued by function groups DTOC, IDMT, PSB, GFSC, SOTF,
THERM, V<>, P<>, CBF

All output signals issued by function group LOGIC

MA IN : Manual tri p signal

MAIN : Transfe r tr ip. EXT

In addition the P437 now provides a time delayed 3-pole transfer trip feature.
This is issued if during the time period set at MA IN: 3p t rans f 1p trp PSx no
phase starting takes place and therefore no phase-selection is possible.
The internal ARC is also controlled by this trip logic.

If at least one phase starting takes place, then the ARC operative timer
stages are triggered, as usual, with general starting. The ARC dead time is
started if the trip signal is terminated within the set operative time. In this
case it is assumed that the operating mode HSR permits that the ARC dead
time is not triggered if only a singlepole HSR has been set and the trip is
multi-pole.

In case no starting takes place and the 3-pole trip is issued, then the ARC
operative timer stages are triggered together with the general trip signal 1.
The ARC dead time is started if the trip signal is terminated within the set
operative time. In this case it is assumed that a 3-pole HSR (for a 3-pole
trip) is permitted.

Phase-selective trip-logic

ARC: HSR oper. mode PSx

Number of
phases
selected

Trip decision

1-pole

1-/3-pole

3-pole

3-pole (only for


1p)

3-pole trip

no

yes (3-pole)

yes (3-pole)

yes (3-pole)

1-pole trip

yes

yes (1-pole)

yes (3-pole)

yes (3-pole)

>1

3-pole trip

no

yes (3-pole)

yes (3-pole)

no

P437/EN M/R-11-A // P437311650

3-97

P437

3 Operation

MAIN:
Fct.ass.1p trip cmd1
[ 002 060 ]
DTOC:
tI> elapsed
[ 040 010 ]
DTOC:
Trip signal tIN>
[ 035 043 ]
MAIN:
Par. trip (1p) EXT
[ 002 066 ]

...

m out of n

Selected signals

MAIN:
* Parameter MAIN:
Enable 1p trip PSx
3p transf 1p trp PSx
set 1
002 061
002 184
set 2
002 062
002 185
set 3
002 063
002 186
set 4
002 064
002 187

MAIN:
Enable 1p trip PSx
[
*
]
0
1
0: No
1: Yes

&

MAIN:
Trip A
306 009

MAIN:
Starting A
[ 036 001 ]

&

MAIN:
Trip B
306 010

MAIN:
Starting B
[ 036 002 ]

&

MAIN:
Trip C
306 011

MAIN:
Starting C
[ 036 003 ]

&
1
1

MAIN:
Blocking 1p trip EXT
[ 041 078 ]

MAIN:
3p transf 1p trp PSx
[
*
]
&

&

47Z1101A

Fig. 3-67: Phase selection for single-pole tripping.

3-98

P437/EN M/R-11-A // P437311650

P437

3 Operation

DIST:
Trip signal Z1, A
BUOC:
Trip A

MAIN:
Trip A

303 623

306 009

304 754

PSIG:
Trip channel 1
402 575

PSIG:
Trip V<, A
305 159

ARC:
External trip A
303 016

ARC:
Test HSR A, internal
303 011

GSCSG:
Trip A

304 004

MAIN:
Manual trip signal A
[ 034 047 ]
MAIN:
Trip 1,A
310 003

DIST:
Trip signal Z1, B

MAIN:
Trip B

303 624

306 010

BUOC:
Trip B

304 755

PSIG:
Trip channel 2
402 576

PSIG:
Trip V<, B

305 160

ARC:
External trip B
303 017

ARC:
Test HSR B, internal
303 012

GSCSG:
Trip B

304 005

MAIN:
Manual trip signal B
[ 034 048 ]
MAIN:
Trip 1,B
310 004

DIST:
Trip signal Z1, C

MAIN:
Trip C

303 625

306 011

BUOC:
Trip C
304 756

PSIG:
Trip channel 3
402 577

PSIG:
Trip V<, C

305 161

MAIN:
Trip signal 1, 1p
[ 037 252 ]

=1

ARC:
External trip C
303 018

ARC:
Test HSR C, internal

303 013

&

MAIN:
Trip signal 1, 3p
[ 037 253 ]

=3

GSCSG:
Trip C

304 006

MAIN:
Manual trip signal C
[ 034 049 ]
MAIN:
Trip 1,C
310 005

MAIN:
3p tr.if HSR off PSx
[
*
]
0
1

&

0: No
1: Yes
ARC:
Enabled
[ 015 064 ]
ARC:
3-pole transfer int.

Parameter
set
set
set
set

303 020

1
2
3
4

MAIN:
3p tr.if HSR off PSx
015 065
024 034
024 094
025 054

47Z1123A

Fig. 3-68: Phase-selective trip.

3.12.10.3

Trip Command
The P437 provides two trip commands. The functions required to trip can be
selected by setting an m out of n parameter independently for each of the two

P437/EN M/R-11-A // P437311650

3-99

P437

3 Operation

trip commands. The minimum trip command time is settable. The trip signals are
present only as long as the conditions for the signal are met.
MAIN:
Trip cmd. blocked
[ 021 013 ]

MAIN:
Trip signal 1, A
[ 036 006 ]

MAIN:
Trip A

306 009

MAIN:
Trip command 1, A
[ 036 072 ]

MAIN:
Trip signal 1, B
[ 036 007 ]

MAIN:
Trip B
306 010

MAIN:
Trip command 1, B
[ 036 073 ]

MAIN:
Trip signal 1, C
[ 036 008 ]

MAIN:
Trip C
306 011

MAIN:
Trip command 1, C
[ 036 074 ]

MAIN:
Gen. trip signal 1
[ 036 005 ]
DIST:
Trip zone 2

MAIN:
Gen. trip command 1
[ 036 071 ]

303 585

DIST:
Trip zone 3

MAIN:
Min.dur. trip cmd. 1
[ 021 003 ]

303 586

DIST:
Trip zone 4
303 587

DIST:
Trip zone 5
303 588

DIST:
Trip zone 6
303 621

DIST:
Trip zone 7
303 622

DIST:
Trip zone 8

MAIN:
Fct.assig.trip cmd.1
[ 021 001 ]

303 626

MAIN:
Manual trip signal
[ 034 017 ]

m out of n

Signal 1
Signal 2
Signal 3
Signal n
MAIN:
Trip signal 1

Selected signals

306 017

MAIN:
Fct.assig.trip cmd.2
[ 021 002 ]

m out of n

MAIN:
Gen. trip signal 2
[ 036 023 ]

Selected signals

MAIN:
General starting
[ 036 000 ]

MAIN:
Min.dur. trip cmd. 2
[ 021 004 ]

MAIN:
Gen. trip command 2
[ 036 022 ]
MAIN:
Gen. trip command 1
[ 036 071 ]

47Z10AUA

Fig. 3-69: Forming of trip commands.

3-100

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.12.10.3.1

Direct Underreaching Transfer Trip


Direct transfer tripping independently of the protective signaling scheme logic
(function group PSIG) is possible by using the following input signals:

MA IN: Tran sfe r tri p. EXT

MA IN : Transfe r trip A EXT

MA IN : Transfe r tri p B EXT

MAI N: Transfe r trip C EXT

This feature makes it possible to use direct transfer tripping and any classical
scheme logic (such as permissive or blocking schemes) concurrently.
3.12.10.3.2

Direct Transfer Trip


There are special send signals for the direct transfer trip of the switch at the
remote end:

MA IN: Se nd tran sf er trip

MA IN : S en d trans fer trip A

MA IN : Se nd tran sf er trip B

MA IN : Se nd trans fer trip C

These send signals were designed for applications with bi-directional transfer
tripping so as to avoid that, for instance, a transfer trip signal is sent only
because such a transfer trip signal was received from the remote station.
With a 3-pole trip, the MAIN: Se nd transf e r trip signal is sent as soon as the
MAI N: Gen . tri p command 1 signal has been issued, except when this trip
command was caused by receiving the MAI N: Tr ans fer t rip. EXT signal (see
Fig. 3-70, (p. 3-101)).
For the P437 with 1/3-pole tripping the same applies to 1-pole send signals.
The P437 should either be used with phase-selective transfer tripping (1-pole) or 3pole transfer tripping, but never with both transfer trip types used simultaneously.
The reason for this is that with each 1-pole trip command a 3-pole general trip
command 1 is issued. If, for instance, the M A I N : T r a n s f e r t r i p A E X T signal is
received without a local trip signal being present, then the P437 will issue a 1-pole
M A I N : T r i p c o m m a n d 1 , A as well as the 3-pole M A I N : G e n . t r i p c o m m a n d
1. Since no 3-pole transfer trip signal M A I N : T r a n s f e r t r i p . E X T was received,
the P437 will send the M A I N : S e n d t r a n s f e r t r i p signal (but not the
M A I N : S e n d t r a n s f e r t r i p A signal).

Signal assignm. Kxx:

Signal assignm. Kxx:

MAIN:
Send transfer trip
[ 001 207 ]

MAIN:
Send transfer trip
[ 001 207 ]

Signal assignm. Uxx:


MAIN:
Transfer trip. EXT
[ 120 046 ]

VG
VG

Signal assignm. Uxx:


MAIN:
Transfer trip. EXT
[ 120 046 ]

MAIN:
Gen. trip command 1
[ 036 071 ]

P437

&

11

P437

45Z6304A

Fig. 3-70: 3-pole transfer trip.

P437/EN M/R-11-A // P437311650

3-101

P437
3.12.10.3.3

3 Operation

Manual Trip Command


Phase-selective as well as 3-pole manual trip commands may be issued via
setting parameters or appropriately configured binary signal inputs. However, a
3-pole manual trip command will be executed only if it is included in the
selection of possible functions to cause a trip.

MAIN:
Man. trip cmd. USER
[ 003 040 ]
0
1

MAIN:
Man. trip cmd. EXT
[ 037 018 ]

100 ms

MAIN:
Manual trip signal
[ 034 017 ]

100 ms

MAIN:
Manual trip signal A
[ 034 047 ]

100 ms

MAIN:
Manual trip signal B
[ 034 048 ]

100 ms

MAIN:
Manual trip signal C
[ 034 049 ]

0: don't execute
1: execute

MAIN:
Man.trip cmd. A USER
[ 003 017 ]
0
1

0: don't execute
1: execute
MAIN:
Man def. trip A EXT
[ 038 030 ]

MAIN:
Man.trip cmd. B USER
[ 003 018 ]
0
1

0: don't execute
1: execute
MAIN:
Man def. trip B EXT
[ 038 031 ]
MAIN:
Man.trip cmd. C USER
[ 003 019 ]
0
1
0: don't execute
1: execute

MAIN:
Man def. trip C EXT
[ 038 032 ]

47Z11AVA

Fig. 3-71: Manual trip command.

3.12.10.3.4

Latching of the Trip Commands


Each of the trip commands can be individually set to operate in the latching
mode (via MA IN : L atch in g tr ip cmd. 1 or MAI N: Latching trip cmd . 2,
respectively).
The trip command, set to latch mode, will remain active until reset by parameter
(MAIN: Rset .lat ch.tri p USE R) or reset through an appropriately configured
binary signal input (MAIN: Re se t latch .tri p EXT).

3.12.10.3.5

Blocking of the Trip Commands


The trip commands can be blocked via parameters or an appropriately
configured binary signal input. This blocking is then effective for both trip
commands. The trip signals are not affected by this blocking. If the trip
commands are both blocked, it is indicated by the continuously illuminated
amber LED indicator H 2 on the local control panel and by a signal from an
output relay configured to Blocked/Faulty.

3-102

P437/EN M/R-11-A // P437311650

P437

3 Operation

MAIN:
Trip cmd.block. USER
[ 021 012 ]

0
MAIN:
Trip cmd. blocked
[ 021 013 ]

1
0: No
1: Yes
MAIN:
Trip cmd. block. EXT
[ 036 045 ]

47Z01AWA

Fig. 3-72: Blocking of the trip commands.

3.12.10.3.6

Counter of Trip Commands


The number of trip commands is counted. The counters can be reset either
individually or jointly with other counters, see Section 3.12.12, (p. 3-106).

ARC:
External trip A 303 016

ARC:
External trip B 303 017
ARC:
External trip C 303 018
DIST:
Trip signal
[ 036 009 ]
BUOC:
Trip signal
[ 036 014 ]
ARC:
Cycle running
[ 037 000 ]

MAIN:
No. final trip cmds.
[ 004 005 ]

MAIN:
Final trip
[ 038 103 ]

S1 1
R1

MAIN:
Close command
[ 037 009 ]
MAIN:
Manual trip signal A
[ 034 047 ]
MAIN:
Manual trip signal B
[ 034 048 ]
MAIN:
Manual trip signal C
[ 034 049 ]
MAIN:
Trip signal 1
306 017

MAIN:
Trip cmd. blocked
[ 021 013 ]
MAIN:
Trip command 1, A
[ 036 072 ]

MAIN:
Trip command 1, B
[ 036 073 ]

MAIN:
Trip command 1, C
[ 036 074 ]

MAIN:
Gen. trip command 1
[ 036 071 ]

MAIN:
Gen. trip command 2
[ 036 022 ]

MAIN:
Reset c. cl/tr.cUSER
[ 003 007 ]

MAIN:
No. trip cmds. 1, A
[ 005 006 ]
MAIN:
No. trip cmds. 1, B
[ 005 007 ]
MAIN:
No. trip cmds. 1, C
[ 005 008 ]
MAIN:
No. gen.trip cmds. 1
[ 004 006 ]
MAIN:
No. gen.trip cmds. 2
[ 009 050 ]

0
1
0: don't execute
MAIN:
General reset USER
[ 003 002 ]
1: execute

1: execute

MAIN:
General reset EXT
[ 005 255 ]
MAIN:
Reset.c.cl./tr.c EXT
[ 005 210 ]

47Z13AXA

Fig. 3-73: Trip command counter.

P437/EN M/R-11-A // P437311650

3-103

P437
3.12.11

3 Operation

Time Tagging and Clock Synchronization


The data stored in the operating data memory, the monitoring signal memory
and the event memories are date- and time-tagged. For correct tagging, the date
and time need to be set in the P437.
The time of different devices may be synchronized by a pulse given to an
appropriately configured binary signal input. The P437 evaluates the rising edge.
This will set the clock to the nearest full minute, rounding either up or down. If
several start/end signals occur (bouncing of a relay contact), only the last edge is
evaluated.

MAIN:
Date
[ 003 090 ]
MAIN:
Time of day
[ 003 091 ]
MAIN:
Time switching
[ 003 095 ]

MAIN:
Min-pulse clock EXT
[ 060 060 ]
MAIN:
Time tag
306 021

Setting

MAIN:
Time switching

0: Standard time
1: Daylight saving time

Q6Z0152B

Fig. 3-74: Date/time setting and clock synchronization with minute pulses presented at a binary signal input.

3-104

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.12.11.1

Synchronization Source
The P437 provides numerous options to synchronize the internal clock:

Telegram with the time of day via the communication interface COMM1/IEC
(full time)

Telegram with the time of day via the communication interface COMM2/PC
(full time)

IRIG-B Signal (IRIGB; time of day only)

Minute pulse presented at a binary signal input (MAIN), see Fig. 3-74, (p. 3104) and previous paragraph

With older P437 versions these interfaces had equal ranking i.e. clock
synchronization was carried out regardless of which sub-function initiated
triggering. No conflicts have to be taken into account as long as synchronization
sources (communication master, IRIGB and minute pulse source) operate at the
same time of day. Should the synchronization sources operate with a different
time basis unwanted step changes in the internal clock may occur. On the other
hand a redundant time of day synchronization is often used so as to sustain time
synchronization via IRIGB interface even if and while the SCADA communication
is out of service.
With the current P437 versions a primary and a backup source for time of day
synchronization may now be set, where both provide the four options listed in
the above.
MAI N: Prim.Source Ti me Sync
MAI N: Backu pS ourceTi meSyn c
With this feature synchronization occurs continuously from the primary source as
long as time synchronization telegrams are received within a time-out period set
at MAIN : Time sy n c. time -out The backup source is required if after the set
time-out there is no synchronization through the primary source.
When selecting the time telegram via IEC as the primary source the P437 will
expect time synchronization telegrams from server SNTP2 after server SNTP 1
has become defective, before it will switch over to the backup source.
Time synchronization occurs solely from the primary source when the time-out
stage is blocked.

P437/EN M/R-11-A // P437311650

3-105

P437
3.12.12

3 Operation

Resetting Actions
Stored data such as event logs, measured fault data etc, can be cleared in
several ways. The following types of resetting actions are possible:

Automatic resetting of the event signals provided by LED indicators (given


that the LED operating mode has been set accordingly) and of the display
of measured event data on the local control panel LCD whenever a new
event occurs. In this case only the displays on the local control panel LCD
are cleared but not the internal memories such as the fault memory.

Resetting of LED indicators and measured event data displayed on the local
control panel LCD by pressing the Clear key
located on the local
control panel. By selecting the required function at L OC: Assignme nt
reset ke y further memories may be assigned which will then also be
cleared when the Clear key is pressed.

Selective resetting of a particular memory type (e.g. only the fault memory)
via setting parameters. (For this example: Navigate to menu point
FT_R C: R ese t r e cord. U SER and set to execute, see also the exact stepby-step description in Section 6.11.7, (p. 6-28).)

Selective resetting of a particular memory type (e.g. only the fault memory)
through appropriately configured binary signal inputs. (For this example:
Assign parameter FT_RC : Res e t record. EXT to the relevant binary
signal input e.g. INP: Fct. assignm. U xxx .)

Group resetting by setting parameters, by navigating to menu point


MAIN : Gr ou p re set 1 USER (or MA IN: Group reset 2 USER) and
setting it to execute. For this the relevant memories (i.e. those to be reset)
must be assigned to parameter MA IN: Fct.assign. rese t 1 (or
MAIN : F ct .assign. r es et 2, resp.)

Group resetting through appropriately configured binary signal inputs.


(That is assign parameter MA IN: Group re set 1 EXT (or MAIN: Group
reset 2 EXT) to the relevant binary signal input, e.g. INP: Fct. assignm. U
xxx after memories to be reset have been assigned to parameter
MAIN : F ct .assign. r e se t 1 (or MAIN: Fct.assign. r eset 2).

General resetting by setting parameters (menu point MAIN: General


reset USER). All memories, counters, events etc. are reset without any
special configuration options.

General resetting through appropriately configured binary signal inputs.


(MAI N: General res et EXT is assigned to the relevant binary signal
input.) All memories, counters, events etc. are reset without any special
configuration options.

Should several resetting actions have been configured for one particular memory
then they all have equal priority.
In the event of a cold restart, namely simultaneous failure of both internal
battery and substation auxiliary supply, all stored signals and values will be lost.

3-106

P437/EN M/R-11-A // P437311650

P437

3 Operation

MAIN:
General reset USER
[ 003 002 ]
0
1: execute

1
0: don't execute
1: execute

MAIN:
Reset indicat. USER
[ 021 010 ]
0
1
0: don't execute
1: execute

MAIN:
Reset LED

MAIN:
Reset indicat. EXT
[ 065 001 ]

306 020

12Z6115A

Fig. 3-75: General reset, LED reset and measured event data reset from the local control panel

LOC:
Reset key active

&

310 024

OP_RC:
Reset record. EXT
[ 005 213 ]

LOC:
Assignment reset key
[ 005 251 ]

m out of n

OP_RC:
Reset record. EXT
[005 213]

MAIN:
Group reset 1 USER
[ * ]

MAIN:
Group reset 2 USER
[ * ]

0
1

MAIN:
Group reset 1 EXT
[

&

0: don't execute

0: don't execute

1: execute

1: execute

&

MAIN:
Group reset 2 EXT
[

MAIN:
Fct.assign. reset 1
[

m out of n

OP_RC:
Reset record. EXT
[005 213]

MAIN:
Fct.assign. reset 2
[

m out of n

OP_RC:
Reset record. EXT
[005 213]

12Z61RMB

Fig. 3-76: CLEAR key on the local control panel and, as an example, group resetting of the operating data
recording (e.g. as an example for the reset signal O P _ R C : R e s e t r e c o r d . E X T.

A complete list of all resetting parameters that can be used in the way shown in
Fig. 3-76, (p. 3-107) can be obtained from the separately available
DataModelExplorer: Look up the setting parameter MAI N: F ct .as sign. re set 1
in the file P437650_en_Addresses.pdf, and there follow the link to the referenced
config. table.

P437/EN M/R-11-A // P437311650

3-107

P437
3.12.12.1

3 Operation

Resetting Actions through Keys on the Local Control Panel


Further resetting possibilities are basically not distinct resetting actions but make
access especially easy to one of the resetting actions described above i.e. by
configuring them to a function key.

3-108

Function keys may be configured such that resetting of a specific memory


is assigned. Technically this is similar to resetting through an appropriately
configured binary signal input. When a function key is pressed a signal to a
binary signal input is simulated. (See Section 3.6, (p. 3-39).)

Alternatively one can assign one of the two menu jump lists (LO C: Tr ig.
menu jm p 1 EXT or LOC: Tri g. me nu jmp 2 EXT) to a function key
and include the relevant resetting action in the definition (LO C: Fct .
menu jm p list 1 or L OC: Fct. me nu j mp list 2) of the selected menu
jump list.

The same may be achieved with the READ ( ) key by assigning it a


menu point for a resetting action through L OC : A ssignment read ke y.

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.12.13

Assigning Communications Interfaces to Physical


Communications Channels
Depending on the design version of the communications module A there are up
to two communications channels available (see Chapter Technical Data). These
physical communications channels may be assigned to communications
interfaces COMM1 and COMM2.
If communications interface COMM1 is assigned to communications channel 2,
then the settings of communications interface COMM2 are automatically
assigned to communications channel 1.
COMM2 can only be used to transmit data to and from the P437 if its PC interface
has been de-activated. As soon as the PC interface is used to transmit data,
COMM2 becomes dead. It will only be enabled again when the "time-out"
period for the PC interface has elapsed.

MAIN:
Chann.assign.COMM1/2
[ 003 169 ]

1
2
1: COMM1->chann.1,(2-2)
2: COMM1->chann.2,(2-1)

"Logical"
Communic. interface
COMM1

Comm. interface
Channel 1

"Logical"
Communic. interface
COMM2

Comm. interface
Channel 2

45Z5171A

Fig. 3-77: Assignment of communication interfaces to physical communication channels.

P437/EN M/R-11-A // P437311650

3-109

P437
3.12.14

3 Operation

Test Mode
If tests are run on the P437, the user is advised to activate the test mode so that
all incoming signals via the serial interfaces will be identified accordingly.

MAIN:
Test mode USER
[ 003 012 ]
0
1

MAIN:
Test mode
[ 037 071 ]

0: No
1: Yes
MAIN:
Test mode EXT
[ 037 070 ]

D5Z50EBA

Fig. 3-78: Setting the test mode.

3-110

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.13

Parameter Subset Selection (Function Group PSS)


With the P437, four independent parameter subsets may be pre-set. The user
may switch between parameter subsets during operation without interrupting the
protection function.

Selecting the Parameter Subset


The control path determining the active parameter subset (function setting or
binary signal input) may be selected via the function setting PSS: C ontrol via
USE R or via the external signal PSS: Control via us er E XT. Correspondingly,
the parameter subset is selected either in accordance with the pre-set function
setting PSS: Par am.su bs. se l. USE R or in accordance with external signals.
Which parameter subset is actually active at a particular time may be
determined by scanning the logic state signals PSS: A ctual param . subset or
PSS : PS 1 act iv e.
Selecting the Parameter Subset via Binary Inputs
If the binary signal inputs are to be used for parameter subset selection, then the
P437 first checks to determine whether at least two binary inputs are configured
for parameter subset selection. If this is not the case, then the parameter subset
selected via the function setting will be active. The P437 also checks whether the
signals present at the binary signal inputs allow an unambiguous parameter
subset selection. This is only true when only one binary signal input is set to a
logic level of 1. If more than one signal input is set to a logic level of 1, then
the parameter subset previously selected remains active. Should a dead interval
occur while switching between parameter subsets (this is the case if all binary
signal inputs have a logic level of 0), then the stored hold time is started. While
this timer stage is running, the previously selected parameter subset remains
active. As soon as a signal input has a logic level of 1, the associated
parameter subset becomes active. If, after the stored time has elapsed, there is
still no signal input with a logic level of 1, the parameter subset selected via
the function parameter becomes active.
If, after the supply voltage is turned on, no logic level of 1 is present at any of
the binary signal inputs selected for the parameter subset selection, then the
parameter subset selected via the function parameter will become active once
the stored time has elapsed. The previous parameter subset remains active while
the stored hold timer stage is running.
Parameter subset selection may also occur during a starting condition. When
subset selection is handled via binary signal inputs, a maximum inherent delay of
approximately 100 ms must be taken into account.
Settings for which only one address is given in the following sections are equally
effective for all four parameter subsets.

P437/EN M/R-11-A // P437311650

3-111

P437

3 Operation

PSS:
Control via USER
[ 003 100 ]
0
1
0: No
PSS:
Control via user
[ 036 102 ]

1: Yes
PSS:
Control via user EXT
[ 036 101 ]

PSS:
Param.subs.sel. USER
[ 003 060 ]

INP:
Fct. assignm. U xxx
[ 152 xxx ]

1
2

U x1

U x2

U x3
U xx

1: Parameter subset 1
2: Parameter subset 2

Address

065 002

Address

065 003

3: Parameter subset 3

Address

065 004

4: Parameter subset 4

Address

065 005

1
2
3
4
1

PSS:
Actual param. subset
[ 003 062 ]
PSS:
PS 1 active
[ 036 090 ]

PSS:
Activate PS 1 EXT
[ 065 002 ]

PSS:
PS 2 active
[ 036 091 ]

PSS:
Activate PS 2 EXT
[ 065 003 ]

PSS:
PS 3 active
[ 036 092 ]

PSS:
Activate PS 3 EXT
[ 065 004 ]

PSS:
PS 4 active
[ 036 093 ]

PSS:
Activate PS 4 EXT
[ 065 005 ]

0
PSS:
Keep time
[ 003 063 ]

1
2
3
4
0

PSS:
Ext.sel.param.subset
[ 003 061 ]
PSS:
PS 1 activated ext.
[ 036 094 ]
PSS:
PS 2 activated ext.
[ 036 095 ]
PSS:
PS 3 activated ext.
[ 036 096 ]
PSS:
PS 4 activated ext.
[ 036 097 ]

D5Z5002A

Fig. 3-79: Activating the parameter subsets.

3-112

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.14

Self-Monitoring (Function Group SFMON)


Comprehensive monitoring routines in the P437 ensure that internal faults are
detected and do not lead to malfunctions. The selection of function assignments
to the alarm signal includes, among others, self-monitoring signals from the
communications monitor, measuring-circuit monitoring, open-circuit monitoring
and the logic outputs.

3.14.1

Tests During Start-up


After the supply voltage has been turned on, various tests are carried out to
verify full operability of the P437. If the P437 detects a fault in one of the tests,
then start-up is terminated. The display shows which test was running when
termination occurred. No control actions may be carried out. A new attempt to
start up the P437 can only be initiated by turning the supply voltage off and then
on again.

3.14.2

Cyclic Tests
After start-up has been successfully completed, cyclic self-monitoring tests will
be run during operation. In the event of a positive test result, a specified
monitoring signal will be issued and stored in a non-volatile(NV) memory the
monitoring signal memory along with the assigned date and time (see
Section 3.16, (p. 3-117)).
The self-monitoring function monitors the built-in battery for any drop below the
minimum acceptable voltage level. If the associated monitoring signal is
displayed, then the power supply module should be replaced within a month,
since otherwise there is the danger of data loss if the supply voltage should fail.
Section 12.1, (p. 12-2) gives further information on maintenance procedures.

3.14.3

Signal
The monitoring signals are also signaled via the output relay configured
SFMON: Warning ( re la y). The output relay operates as long as an internal
fault is detected.

SFMON:
Fct. assign. warning
[ 021 030 ]

Signal 1
m out of n
Signal 2
Signal 3
Signal n
Selected monit. sig.

SFMON:
Hardware fault

SFMON:
Warning (LED)
[ 036 070 ]
SFMON:
Warning (relay)
[ 036 100 ]

304 950

Q6Z0154A

Fig. 3-80: Monitoring signals.

P437/EN M/R-11-A // P437311650

3-113

P437
3.14.4

3 Operation

Device Response
The response of the P437 is dependent on the type of monitoring signal. The
following responses are possible:

Signaling Only
If there is no malfunction associated with the monitoring signal, then only a
signal is issued, and there are no further consequences. This situation
exists, for example, when internal data acquisition memories overflow.

Selective Blocking
If a fault is diagnosed solely in an area that does not affect the protective
functions, then only the affected area is blocked. This would apply, for
example, to the detection of a fault on the communication module or in the
area of the PC interface.

Warm Restart
If the self-monitoring function detects a fault that might be eliminated by a
system restart such as a fault in the hardware , then a procedure called
a warm restart is automatically initiated. During this procedure, as with any
start-up, the computer system is reset to a defined state. A warm restart is
characterized by the fact that no stored data and, in particular, no setting
parameters are affected by the procedure. A warm restart can also be
triggered manually by control action. During a warm restart sequence the
protective functions and the communication through serial interfaces will
be blocked. If the same fault is detected after a warm restart has been
triggered by the self-monitoring system, then the protective functions
remain blocked but communication through the serial interfaces will usually
be possible again.

Cold Restart
If a corrupted parameter subset is diagnosed during the checksum test,
which is part of the self-monitoring procedure, then a cold restart is carried
out. This is necessary because the P437 cannot identify which parameter in
the subset is corrupted. A cold restart causes all internal memories to be
reset to a defined state. This means that all the protection device settings
are also erased after a cold restart. In order to establish a safe initial state,
the default values have been selected so that the protective functions are
blocked. Both the monitoring signal that triggered the cold restart and the
value indicating parameter loss are entered in the monitoring signal
memory.

3-114

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.14.5

Monitoring Signal Memory


Depending on the type of internal fault detected the P437 will respond by trying
to eliminate the problem with a warm restart. (See above; for further details read
also about P437 behavior with problems in Chapter 11, (p. 11-1).) Whether or
not this measure will suffice can only be determined if the monitoring signal has
not already been stored in the monitoring signal memory because of a previous
fault. If it was already stored and a second fault is detected then, depending on
the type of fault detected, the P437 will be blocked after the second warm
restart.
In order to better monitor this behavior the parameter at SFMON: Mon. sig.
re t ent ion is applied. This parameter may either be set to Blocked or to a time
duration (in hours). (It is, however, discouraged to set it to 0, because in this
case, there would be no blocking at all, so that there would be the danger of
maloperation in case of a permanent failure.)
The default for this timer stage is Blocked, i.e. blocking of the protection device
with two identical faults occurs independently of the time elapsed since the first
fault monitoring signal was issued.
The behavior caused by sporadic faults could lead to an unwanted blocking of the
P437 if the monitoring signal memory had not been reset in the interim, for
example, because the substation is difficult to reach in wintertime or reading-out
and clearing of the monitoring signal memory via the communication interfaces
was not enabled. To defuse this problem it is suggested to set the function
parameter to a specific time period so that blocking will only occur if the same
fault occurs again within this time period. Otherwise, the P437 will continue to
operate normally after a warm restart.

3.14.6

Monitoring Signal Memory Time Tag


The time when the device fault occurred last is recorded.

P437/EN M/R-11-A // P437311650

3-115

P437

3.15

3 Operation

Operating Data Recording (Function Group OP_RC)


For the continuous recording of processes in system operation as well as of
events, a non-volatile memory is provided (cyclic buffer). The operationally
relevant signals, each fully tagged with date and time at signal start and signal
end, are entered in chronological order. The signals relevant for operation
include control actions such as function disabling and enabling and triggers for
testing and resetting. The start and end of system events that represent a
deviation from normal operation such as overloads, ground faults or short-circuits
are also recorded. The operating data memory can be cleared/reset.

Counter for Signals Relevant to System Operation


The signals stored in the operating data memory are counted.

OP_RC:
Operat. data record.
[ 003 024 ]

Operating memory

MAIN:
Oper.-relev. signal
306 024

MAIN:
General reset USER
[ 003 002 ]
1: execute

OP_RC:
No. oper. data sig.
[ 100 002 ]

+
R

MAIN:
General reset EXT
[ 005 255 ]
OP_RC:
Reset record. EXT
[ 005 213 ]
OP_RC:
Reset record. USER
[ 100 001 ]

0
1
0: don't execute
1: execute

12Z61CMA

Fig. 3-81: Operating data recording and counter for signals relevant to system operation.

3-116

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.16

Monitoring Signal Recording (Function Group MT_RC)


The monitoring signals generated by the self-monitoring function are recorded in
the monitoring signal memory. The memory buffer allows for a maximum of
30 entries. If more than 29 monitoring signals occur without interim memory
clearance, the SFMO N: O ve rf low MT_RC signal is entered as the last entry.
Monitoring signals prompted by a hardware fault in the unit are always entered
in the monitoring signal memory. Monitoring signals prompted by a peripheral
fault can be entered into the monitoring signal memory, if desired. The user can
select this option by setting an m out of n parameter (see Section 3.14, (p. 3113)).
If at least one entry is stored in the monitoring signal memory, this fact is
signaled by the red LED indicator H 3 on the local control panel. Each new entry
causes the LED to flash (on/off/on....).
The monitoring signal memory can only be cleared manually by a control action.
Entries in the monitoring signal memory are not cleared automatically, even if
the corresponding test in a new test cycle now shows the P437 to be healthy.
The contents of the monitoring signal memory can be read from the local control
panel or through the PC or communication interface. The time and date
information assigned to the individual entries can be read out through the PC or
communication interface or from the local control panel.

Monitoring Signal Counter


The number of entries stored in the monitoring signal memory is displayed on
the monitoring signal counter (MT_RC : N o. mon it . sign als).

MT_RC:
Mon. signal record.
[ 003 001 ]

MAIN:
Time tag
306 021

SFMON:
Hardware fault
304 950

Selected monit. sig.

MT_RC:
Reset record. USER
[ 003 008 ]

1
0
1

0: don't execute
MT_RC:
Reset record. EXT
[ 005 240 ]

CT30

SFMON:
Overflow MT_RC
[ 090 012 ]
MT_RC:
No. monit. signals
[ 004 019 ]

1: execute

12Z6155A

Fig. 3-82: Monitoring signal recording and the monitoring signal counter.

P437/EN M/R-11-A // P437311650

3-117

P437

3 Operation

3.17

Overload Data Acquisition (Function Group OL_DA)

3.17.1

Overload Duration
In the event of an overload, the P437 determines the overload duration. The
overload duration is defined as the time between the start and end of the
FT_RC : R ecord. in pr ogre ss signal.

OL_RC:
Record. in progress
[ 035 003 ]

MAIN:
General reset USER
[ 003 002 ]
1: execute

+
R

OL_DA:
Overload duration
[ 004 102 ]

MAIN:
General reset EXT
[ 005 255 ]
OL_RC:
Reset record. EXT
[ 005 241 ]
OL_RC:
Reset record. USER
[ 100 003 ]
1: execute

50Z0137A

Fig. 3-83: Overload duration.

3-118

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.17.2

Acquiring Measured Overload Data from the Thermal Overload


Protection
Measured overload values are derived from the thermal overload protections
measured operating data. They are stored at the end of an overload event.

OL_RC:
Record. in progress
[ 035 003 ]

THERM:
Status THERM replica
[ 004 016 ]
R

THERM:
I
305 202

THERM:
Object temperature
[ 004 137 ]
R

THERM:
Coolant temperature
[ 004 149 ]
R

THERM:
Pre-trip time left
[ 004 139 ]

OL_DA:
Status THERM replica
[ 004 147 ]

OL_DA:
Load current THERM
[ 004 058 ]

OL_DA:
Object temp. THERM
[ 004 035 ]

OL_DA:
Coolant temp. THERM
[ 004 036 ]

OL_DA:
Pre-trip t.leftTHERM
[ 004 148 ]
R

THERM:
Temp. offset replica
[ 004 109 ]

OL_DA:
Offset THERM replica
[ 004 154 ]
R

MAIN:
General reset USER
[ 003 002 ]
1: execute

MAIN:
General reset EXT
[ 005 255 ]
OL_RC:
Reset record. EXT
[ 005 241 ]
OL_RC:
Reset record. USER
[ 100 003 ]
1: execute

12Z6238A

Fig. 3-84: Measured overload values from the thermal overload protection.

P437/EN M/R-11-A // P437311650

3-119

P437

3 Operation

3.18

Overload Recording (Function Group OL_RC)

3.18.1

Start of Overload Recording


An overload exists and consequently overload recording begins if at least the
signal THE RM: St art in g k*I ref> is issued.

3.18.2

Counting Overload Events


Overload events are counted and identified by sequential numbers.
OL_RC:
Record. in progress
[ 035 003 ]

THERM:
Starting k*Iref>
[ 041 108 ]

+
R

MAIN:
General reset USER
[ 003 002 ]

OL_RC:
No. overload
[ 004 101 ]

1: execute
MAIN:
General reset EXT
[ 005 255 ]
OL_RC:
Reset record. EXT
[ 005 241 ]
OL_RC:
Reset record. USER
[ 100 003 ]
1: execute

52Z01C3A

Fig. 3-85: Counting overload events.

3.18.3

Time Tagging
The date of each overload event is stored. The overload start or end signals are
likewise time-tagged by the internal clock. The date and time assigned to an
overload event when the event begins can be read out from the overload
memory on the local control panel or through the PC and communication
interfaces. The time information (relative to the onset of the overload) can be
retrieved from the overload memory or through the PC or one of the
communication interfaces.

3-120

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.18.4

Overload Logging
Protection signals during an overload event are logged in chronological order
with reference to the specific event. A total of eight overload events, each
involving a maximum of 200 start or end signals, can be stored in the nonvolatile overload memories. After eight overload events have been logged, the
oldest overload log will be overwritten, unless memories have been cleared in
the interim. If more than 199 start or end signals have occurred during a single
overload event, then OL _RC: Overl. me m. overflow will be entered as the
last signal.
In addition to the signals, the measured overload data will also be entered in the
overload memory.
The overload logs can be read from the local control panel or through the PC or
communication interfaces.

OL_RC:
Record. in progress
[ 035 003 ]
Signal 1

Signal 3

Signal n

Signal 2

OL_RC:
Overl. mem. overflow
[ 035 007 ]

CT200

OL_RC:
Overload recording 1
[
*
]

Measured value 1
Measured value 2
Measured value 3
Measured value N
MAIN:
Time tag

306 021

&

FT_RC:
Record. in progress
[ 035 000 ]

OL_RC:
Reset record. USER
[ 100 003 ]

OL_RC:
Overload recording 1

033 020

033 021

033 022

033 023

033 024

033 025

033 026

033 027

0
MAIN:
General reset USER
[ 003 002 ]
1: execute
MAIN:
General reset EXT
[ 005 255 ]
OL_RC:
Reset record. EXT
[ 005 241 ]

0: don't execute
1: execute

12Z6117A

Fig. 3-86: Overload memory.

P437/EN M/R-11-A // P437311650

3-121

P437

3.19

3 Operation

Fault Data Acquisition (Function Group FT_DA)


When there is a primary system fault, the P437 collects the following measured
fault data:

3.19.1

Running time

Fault duration

Fault current (short-circuit current)

Fault voltage (short-circuit voltage)

Fault impedance (short-circuit impedance)

Fault reactance (short-circuit reactance) in percent of the line reactance


and in

Line fault loop angle

Fault distance

Ground fault (short-circuit) current

Ground fault loop angle

Relative fault location

Fault location in km

Running Time and Fault Duration


The running time is defined as the time between the start and end of the general
starting signal, and the fault duration is defined as the time between the start
and end of the FT_RC : Re cor d. i n pr ogre ss signal.

!G!

MAIN:
General starting
[ 036 000 ]

FT_DA:
Running time
[ 004 021 ]

!G!

FT_RC:
Record. in progress
[ 035 000 ]

FT_DA:
Fault duration
[ 008 010 ]

R
MAIN:
General reset USER
[ 003 002 ]
1: execute

1
1

MAIN:
General reset EXT
[ 005 255 ]
MAIN:
Reset LED
306 020

49Z64DMA

Fig. 3-87: Running time and fault duration.

3-122

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.19.2

Fault Data Acquisition Time


The setting at FT_DA : St art data acqu . PSx determines at which time during
a fault the acquisition of fault data takes place. The following settings are
possible:

End of fault Acquisition at the end of the fault.

Trigger/Trip/End Acquisition at the following points:

when an appropriately configured binary signal input is triggered during


a general starting state,
when a general trip signal is issued,
at the end of the fault.

The setting at FT_D A: Ou tp. flt.locat. P Sx determines the conditions under


which calculation and output of the fault location occur. The following settings
are possible:

Always: Calculation and output of the fault location always occurs if the
other measured fault data are also being determined.

Only after trip t1: Calculation and output of the fault location occurs if the
P437 decides in favor of a trip in impedance zone 1 with standard reach
(non-extended zone).

Only aft.tr.t1/t1,ze: Calculation and output of the fault location occurs if the
P437 decides in favor of a trip in impedance zone 1 with standard and
extended reach.

P437/EN M/R-11-A // P437311650

3-123

P437

3 Operation

FT_DA:
Start data acqu. PSx
[

]
1
2

1: End of fault
2: Trigger/Trip/End
FT_DA:
Output meas. values

MAIN:
General starting
[ 036 000 ]

305 050

FT_DA:
Trigger EXT
[ 036 088 ]
MAIN:
Gen. trip signal 1
[ 036 005 ]
MAIN:
Gen. trip signal 2
[ 036 023 ]
FT_DA:
Outp. flt.locat. PSx
[

]
1
2
3

1: Always
2: Only after trip t1
3: Only aft.tr.t1/t1,ze
FT_DA:
Outp. fault location
305 051

DIST:
Trip signal zone 1
[ 035 072 ]
DIST:
Trip signal Z1,ze
[ 035 074 ]
FT_DA:
Trigger N
310 059

FT_DA:
Flt.loc. determ. PSx
[

]
0
1

0: with GS
1: with GS or N

Parameter

FT_DA:
Start data acqu. PSx

FT_DA:
Outp. flt.locat. PSx

FT_DA:
Flt.loc. determ. PSx

set
set
set
set

010
010
010
010

010
010
010
010

008
008
008
008

1
2
3
4

011
042
043
044

032
033
034
035

007
008
009
027

49Z7005A

Fig. 3-88: Enabling of measured fault data acquisition and fault location output.

3.19.3

Selection of the Measuring Loop for Determining Fault Data


If the distance protection function detects a fault, one of the measuring loops
that is used by distance protection for measurement purposes is selected, and
the data from this loop are displayed as the fault data. Selection of the
measuring loop is based on the following criteria:
When there is a general starting condition for distance protection, calculation of
impedances is enabled as a function of ground starting (zero-sequence starting):
either phase-to-ground impedances (in the case of grounded starting) or phaseto-phase impedances (in the case of ungrounded starting). If the distance
protection function decides in favor of a trip in none or in all phases, then the
impedance loop having the lowest impedance is selected. In the case of multipole ungrounded starting and a trip decision in a phase-to-phase loop, the loop in
which the trip decision is made is selected. If there is multi-pole grounded
starting and a trip decision is made in only one phase, the corresponding phaseto-ground loop is selected. If there is a trip decision in two phases, then the ratio

3-124

P437/EN M/R-11-A // P437311650

P437

3 Operation

of the impedances of these two phase-to-ground loops is determined according


to the following formula:

| Zloop1 | | Zloop2 |
| Zmin |

Zloop1: Impedance of phase-to-ground loop 1

Zloop2: Impedance of phase-to-ground loop 2

Zmin: Lowest impedance of the two phase-to-ground loops

If the ratio is smaller than 0.1, then the phase-to-phase loop is selected, and if
the ratio is 0.1, then the phase-to-ground loop having the lowest impedance is
selected.
The phase-to-ground impedances are determined depending on the setting
based on the residual current of the parallel line.

FT_DA:
Mutual comp. PSx
[ * ]
0
1
2
0: Without
1: Depend. on IN/IN,par
2: Always
C 1,2,3

DIST:
With mutual comp.
[ 038 039 ]

C 4,5,6

IA

IB

IC

DIST:
IkG,par
303 605

5
6

DIST:
IkG
303 604

1,4
Parameter
set
set
set
set

1
2
3
4

FT_DA:
Mutual comp. PSx
025 096
024 016
027 076
025 036

2,5
3,6

FT_DA:
IA,corr.

305 061

FT_DA:
IB,corr.

305 062

FT_DA:
IC,corr.

305 063

47Z01ANC

Fig. 3-89: Conditioning of the phase currents for determination of phase-to-ground impedances.

P437/EN M/R-11-A // P437311650

3-125

P437

3 Operation

DIST:
Trip signal A
303 664

DIST:
Trip signal B
303 665

DIST:
Trip signal C
303 666

c1
c2
c3
||Zloop1|/|Zmin||Zloop2|/|Zmin||
< 0.1
||Zloop1|/|Zmin||Zloop2|/|Zmin||
0.1

DIST:
Multipole starting
303 534

c
c
c
c
c
c
c
c

DIST:
General starting
[ 036 240 ]
DIST:
Starting N1
VA-G

IA
IB
VC-G
IC

ZPP,min

ZPG,min

c 1,2,3
c 4,5,6

303 535

VB-G

2
1,2
3
4
5
6
7
8

A-B

B-C

C-A

A-G

B-G

B-G

4
5
6

FT_DA:
VMeas
305 053

8
1

FT_DA:
IA,corr.

305 063

FT_DA:
Select.meas.loop A-B
305 058

FT_DA:
Select.meas.loop B-C
1,4
1,5

305 062

FT_DA:
IC,corr.

305 054

1,3

305 061

FT_DA:
IB,corr.

2,6
2,7

FT_DA:
IMeas

2,8

305 059

FT_DA:
Select.meas.loop C-A
305 060

FT_DA:
Select.meas.loop A-G
305 055

FT_DA:
Select.meas.loop B-G
305 056

FT_DA:
Select.meas.loop C-G
305 057

FT_DA:
Select. meas.loop PG
305 064

47Z11AMA

Fig. 3-90: Selection of the measuring loop for determining fault data.

3.19.4

Acquisition of Short Circuit Data


The fault must last for at least 60 ms in order for fault data (short-circuit data) to
be determined.

3-126

P437/EN M/R-11-A // P437311650

P437

3 Operation

One phase current is selected as the fault current in accordance with the
measuring loop selected by the fault data acquisition function. If a phase-tophase loop has been selected, then the fault current will be the current of the
leading phase in the cycle. The primary fault reactance is calculated from the
per-unit fault reactance using the nominal data for the set primary current and
voltage transformers.
The ground fault data are only determined if a phase-to-ground loop has been
selected for display. The geometric sums of the three phase currents of the line
being protected or of the parallel line are displayed as the ground fault current.
The ground fault angle is the phase displacement between ground fault current
and measuring voltage as selected by the fault data acquisition function.
If the fault is detected by the backup overcurrent-time protection function, then
only the fault current can be determined. The maximum phase current is
displayed.
Fault current and voltage are displayed as per-unit quantities referred to Inom and
Vnom. If the measured or calculated values are outside the acceptable measuring
range, the Overflow indication will be displayed.

P437/EN M/R-11-A // P437311650

3-127

P437

3 Operation

FT_DA:
Output meas. values

C 1,2

305 050

MAIN:
Inom C.T. prim.
[ 010 001 ]
MAIN:
Vnom V.T. prim.
[ 010 002 ]
FT_DA:
Select. meas.loop PG

C2

305 064

DIST:
General starting
[ 036 240 ]

c 1,3,4,5

BUOC:
Starting
[ 036 013 ]

c 2

FT_DA:
IMeas

FT_DA:
Fault current P p.u.
[ 004 025 ]

FT_DA:
Flt.volt. PG/PP p.u.
[ 004 026 ]

FT_DA:
Fault loop angle P
[ 004 024 ]

305 054

R
IA

2
Imax

IB
IC

IN,par

IN

1
R

FT_DA:
Fault impedance, sec
[ 004 023 ]

5
1

FT_DA:
Fault reactance,sec.
[ 004 028 ]

FT_DA:
Fault react., prim.
[ 004 029 ]

FT_DA:
Fault loop angle N
[ 004 048 ]

FT_DA:
Fault curr. N p.u.
[ 004 049 ]

FT_DA:
Fault curr.N,par p.u
[ 004 059 ]

2 ... 3
FT_DA:
Select.meas.loop A-G

1
c 1

305 055

FT_DA:
Select.meas.loop B-G

5
R

c 2

305 056

FT_DA:
Select.meas.loop C-G

c 3

305 057

FT_DA:
Select.meas.loop A-B
305 058

FT_DA:
Select.meas.loop B-C

R
c 1

c 2

305 059

FT_DA:
Select.meas.loop C-A

c 3

305 060

R
1
2
3
1 ... 3

FT_DA:
Meas. loop selected
[ 004 079 ]

FT_DA:
VMeas
305 053

MAIN:
General reset USER
[ 003 002 ]
1: execute

MAIN:
General reset EXT
[ 005 255 ]
MAIN:
Reset LED
306 020

47Z11APB

Fig. 3-91: Acquisition of short circuit data.

3.19.5

Acquisition of Fault Location


In order to determine the fault location as a percentage of the line length and in
km, the value of the line reactance, which corresponds to 100% of the monitored
line section, as well as the corresponding line length in km, must be set.

3-128

P437/EN M/R-11-A // P437311650

P437

3 Operation

FT_DA:
Line length PSx
[ * ]
FT_DA:
Line reactance PSx
[ * ]

FT_DA:
Output fault locat.

305 076

FT_DA:
Fault location
[ 004 022 ]

FT_DA:
Fault reactance,sec.
[ 004 028 ]

MAIN:
General reset USER
[ 003 002 ]
1: execute

FT_DA:
Fault locat. percent
[ 004 027 ]

MAIN:
General reset EXT
[ 005 255 ]
MAIN:
Reset LED

Parameter

FT_DA:
Line length PSx

FT_DA:
Line reactance PSx

set
set
set
set

010
010
010
010

010
010
010
010

306 020

1
2
3
4

005
006
007
008

012
013
014
015

50Z01B4B

Fig. 3-92: Acquisition of fault location.

3.19.6

Fault Data Reset


on the local control panel, the fault data value is
After pressing the reset key
displayed as Not measured. However, the values are not erased and can
continue to be read out through the PC and communication interfaces.

P437/EN M/R-11-A // P437311650

3-129

P437

3 Operation

3.20

Fault Recording (Function Group FT_RC)

3.20.1

Start of Fault Recording


A fault exists and fault recording begins if at least one of the following signals is
present:

MAIN : Gen eral star tin g

MAIN : Ge n. trip si gn al 1

MAIN : Gen. trip s ignal 2

FT_RC : Trigger

FT_RC : I > tri ggere d

In addition, the user can set a logical OR combination of logic signals (m out of
n parameter) whose appearance will trigger fault recording.

3-130

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.20.2

Fault Counting
Faults are counted and identified by sequential numbers.

FT_RC:
Fct. assig. trigger
[ 003 085 ]
Signal 1
Signal 2

m out of n

Signal 3
Signal n
Selected signals

FT_RC:
Trigger EXT
[ 036 089 ]

FT_RC:
Trigger
[ 037 076 ]

FT_RC:
Record. trig active
[ 002 002 ]

FT_RC:
Trigger USER
[ 003 041 ]
0
1

1 min

FT_RC:
Record. in progress
[ 035 000 ]

0: don't execute
1: execute
MAIN:
General starting
[ 036 000 ]
MAIN:
Gen. trip signal 1
[ 036 005 ]
MAIN:
Gen. trip signal 2
[ 036 023 ]

MAIN:
General reset USER
[ 003 002 ]
1: execute

FT_RC:
No. of faults
[ 004 020 ]

MAIN:
General reset EXT
[ 005 255 ]

FT_RC:
Reset record. USER
[ 003 006 ]
1: execute

FT_RC:
No. system disturb.
[ 004 010 ]

FT_RC:
Reset record. EXT
[ 005 243 ]

&

ARC:
Cycle running
[ 037 000 ]

&

FT_RC:
System disturb. runn
[ 035 004 ]

S1 1
R1

45Z6325A

Fig. 3-93: Start of fault recording and fault counter.

3.20.3

Time Tagging
The date that is assigned to each fault by the internal clock is stored. A faults
individual start or end signals are likewise time-tagged. The date and time
assigned to a fault when the fault begins can be read out from the fault memory
on the local control panel or through the PC and communication interfaces. The
time information (relative to the onset of the fault) that is assigned to the signals
can be retrieved from the fault memory or through the PC or communication
interfaces.

P437/EN M/R-11-A // P437311650

3-131

P437
3.20.4

3 Operation

Fault Recordings
Protection signals, including the signals during the settable pre-fault and postfault times, are logged in chronological order with reference to the specific fault.
A total of eight faults, each involving a maximum of 200 start or end signals, can
be stored in the non-volatile fault memories. After eight faults have been
recorded, the oldest fault recording will be overwritten, unless memories have
been cleared in the interim. If more than 199 start or end signals have occurred
during a single fault, then FT_RC: Faul t me m. overf low will be entered as the
last signal. If the time and date are changed during the pre-fault time, the signal
FT_R C: Faul ty t ime tag is generated.
In addition to the fault signals, the measured RMS fault data will also be entered
in the fault memory.
The fault recordings can be read from the local control panel or through the PC or
communication interfaces.

FT_RC:
Record. in progress
[ 035 000 ]
Signal 1

Signal 2

Signal 3

Signal n

FT_RC:
Fault mem. overflow
[ 035 001 ]

CT200

FT_RC:
Fault recording n
[

FT_RC:
Pre-fault time
[ 003 078 ]
FT_RC:
Post-fault time
[ 003 079 ]

Fault memory n

FT_RC:
Fault recording n

003 000

033 001

033 002

Measured value 1

033 003

Measured value 2

033 004

Measured value 3

033 005

Measured value N

033 006

MAIN:
Time tag

033 007

306 021

MAIN:
General reset USER
[ 003 002 ]
1: execute

&

MAIN:
General reset EXT
[ 005 255 ]

FT_RC:
Reset record. EXT
[ 005 243 ]

FT_RC:
Reset record. USER
[ 003 006 ]

0
1

1: execute

0: don't execute
1: execute

12Z6161B

Fig. 3-94: Fault memory.

3-132

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.20.5

Fault Value Recording


The following analog signals are recorded:

Phase currents

Phase-to-ground voltages

Residual current measured by the P437 at the T 4 transformer

Neutral-point displacement voltage measured by the P437 at the T 90


transformer

Reference voltage Vref measured by the P437 at the T 15 transformer

Residual current of the parallel line, measured by the P437 at the T 24


transformer

The signals are recorded before, during and after a fault. The window length for
oscillography recording before and after the fault can be set. A maximum time
period of 16.4 s is available for recording. This period can be divided among a
maximum of eight faults. The maximum recording time per fault can be set. If a
fault, including the set pre-fault and post-fault times, lasts longer than the set
maximum recording time, then recording will terminate when the set maximum
recording time is reached.
The pre-fault time is exactly adhered to if it is shorter than the set maximum
recording time. Otherwise the pre-fault time is set to the maximum recording
time minus a sampling increment, and the post-fault time is set to zero.
If the maximum recording time of 16.4 s is exceeded, the analog values for the
oldest fault are overwritten, but not the binary values. If more than eight faults
have occurred since the last reset, then all data for the oldest fault are
overwritten.
The analog oscillography data of the fault record can only be read out through
the PC or communication interfaces.
When the supply voltage is interrupted or after a warm restart, the values of all
faults remain stored.

P437/EN M/R-11-A // P437311650

3-133

P437

3 Operation

FT_RC:
Record. in progress
[ 035 000 ]

FT_RC:
Max. recording time
[ 003 075 ]
FT_RC:
Pre-fault time
[ 003 078 ]
FT_RC:
Post-fault time
[ 003 079 ]

IA

IB

IC

VA-G

VB-G

VC-G

IN

VN-G

Vref

IN,par
FT_RC:
Reset record. USER
[ 003 006 ]
1: execute

Analog channel 1

Analog channel 2

Analog channel 3

Analog channel 4

Analog channel 5

Analog channel 6

Analog channel 7

Analog channel 8

Analog channel 9

Analog channel 10

MAIN:
General reset USER
[ 003 002 ]
1: execute
MAIN:
General reset EXT
[ 005 255 ]
FT_RC:
Reset record. EXT
[ 005 243 ]

47Z1319A

Fig. 3-95: Fault value recording.

3-134

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.21

Distance Protection (Function Group DIST)

Disabling or Enabling Distance Protection


Distance protection can be disabled or enabled using a setting parameter
(see Fig. 3-96, (p. 3-135)).

3.21.1

Fault Detection Logic


The fault detection logic in distance protection serves to detect short-circuits
phase-selectively. Fault detection logic is divided into the following areas:

Overcurrent detection

Ground fault detection

Undervoltage detection

Underimpedance fault detection

The fault detection decisions of the individual areas are linked by the fault
detection logic.
Short-circuit currents that are greater than the maximum operating load currents
can be detected by the overcurrent detection logic. Undervoltage detection logic
is provided for short circuits that cannot be identified by overcurrent detection. In
order to control difficult conditions for fault detection, the P437 is also equipped
with a highly angle-dependent true underimpedance detection logic function.
Ground fault detection logic distinguishes between grounded and ungrounded
faults.
The fault detection logic starts the timer stages of the trigger levels and as a
function of the phase-selective fault detection decision selects the measuring
loops in which the fault impedances are determined. The fault detection logic is
blocked if one of the following conditions is met:

The protection function is disabled using setting parameters or


appropriately configured binary signal inputs.

Monitoring (VT supervision) detects a fault in the voltage-measuring circuit.

If distance protection is blocked, the user may switch to backup overcurrent-time


protection provided that the appropriate setting has been selected.

DIST:
General enable USER
[ 031 073 ]

0
1
0: No

DIST:
Enabled
[ 036 104 ]

1: Yes
DIST:
Starting blocked
303 500

MCMON:
Meas. circ. V faulty
[ 038 023 ]
MAIN:
Protection active
306 001

D5Z5029A

Fig. 3-96: Fault detection blocking.

P437/EN M/R-11-A // P437311650

3-135

P437
3.21.1.1

3 Operation

Overcurrent Detection
Overcurrent fault detection monitors the phase currents for values in excess of
the threshold values I>> and I>>>. The I>> threshold can be set. I>>> is equal to
2I>>. The thresholds are identical for all three phases.
The output signals of the I>> trigger assume a logic value of 1 if the threshold
is exceeded in two consecutive half-waves. In the case of the I>>> trigger only
one halfwave must exceed the threshold for the output signals to assume a logic
value of 1. Triggering of inrush stabilization prevents operation of the I>>
trigger.
If I>> is exceeded in one phase, then it is sufficient for overcurrent detection if
I>>> is exceeded in the other phases. In this case the fault detection time is
shortened since there is no longer any need to wait for the second half-wave.
Evaluation of the trigger decisions is a function of the type of neutral-point
treatment set in the P437. If isolated neutral/resonant grounding or shortduration grounding is set, then I>> overcurrent detection occurs in the phase(s)
in which the I>> threshold is exceeded. With the setting Low-imped. grounding
the following condition must also be satisfied:
I

3-136

2
3

| I max |

P437/EN M/R-11-A // P437311650

P437

3 Operation

MAIN:
Neutr.pt. treat. PSx
[ * ]
1: Low-imped. grounding

2: Isol./res.w.start.PG

3: Isol./res.w/o st. PG
4: Short-durat. ground.

MAIN:
Rush restr. A trig.
[ 041 027 ]
MAIN:
Rush restr. B trig.
[ 041 028 ]
MAIN:
Rush restr. C trig.
[ 041 029 ]
DIST:
I>> PSx
[ * ]

DIST:
Starting blocked
303 500

IA
IB
IC
DIST:
I>> triggered
303 597

I>>> = 2I>>

DIST:
I>>> triggered
303 501

(2/3)Imax

Imax

DIST:
IA>> triggered
303 511

DIST:
IB>> triggered
303 512

DIST:
IC>> triggered
303 513

* Parameter
set
set
set
set

1
2
3
4

MAIN:
Neutr.pt. treat. PSx

DIST:
I>> PSx

010
001
001
001

010
010
010
011

048
076
077
078

054
074
094
014

47Z1155A

Fig. 3-97: Overcurrent detection.

3.21.1.2

Ground Fault Detection


To detect ground faults, the ground fault detection function monitors the average
magnitude of the residual current calculated from the phase currents and the
neutral-displacement voltage calculated from the phase-to-ground voltages for
values exceeding set thresholds. For the two possible dynamic ranges of current
measurement, one parameter each is available for setting the fault detection
value for ground fault monitoring.

P437/EN M/R-11-A // P437311650

3-137

P437

3 Operation

5% of the current maximum phase current is added to the set threshold IN>,
which means that the operate value of the ground current function increases
with an increasing phase current level as a form of stabilization.

IA

COMP

IB
IC
DIST:
IN> PSx

Imax

DIST:
Start. IN> triggered
303 502

|Ix|
|Ix|+IN>

0.05|Imax|

DIST:
tIN> PSx
[ * ]

DIST:
Starting blocked

DIST:
tIN> elapsed

303 500

303 503

DIST:
tIN> running
[ 036 105 ]
MAIN:
Neutr.pt. treat. PSx
[ * ]
4: Short-durat. ground.

50ms

DIST:
VNG> PSx
[

DIST:
VNG>> exceeded
303 596

DIST:
Start.VNG> triggered

VA-G
VB-G

303 504

VC-G

DIST:
VNG>> PSx
[

DIST:
tVNG>> PSx

DIST:
tVNG>> elapsed

MAIN:
Neutr.pt. treat. PSx

303 506

[ * ]
1: Low-imped. grounding

DIST:
VNG>> triggered
[ 036 015 ]
DIST:
tVNG>> elapsed
[ 036 016 ]

* Parameter
set
set
set
set

1
2
3
4

MAIN:
Neutr.pt. treat. PSx

DIST:
IN> PSx

DIST:
tIN> PSx

DIST:
VNG> PSx

DIST:
VNG>> PSx

DIST:
tVNG>> PSx

010
001
001
001

010
010
010
011

010
010
010
011

010
010
010
011

010
010
011
011

010
010
011
011

048
076
077
078

055
075
095
015

057
077
097
017

056
076
096
016

062
082
002
022

061
081
001
021

45Z8056A

Fig. 3-98: Monitoring the residual current and the neutral-displacement voltage.

The ground fault detection mode is a function of the neutral-point treatment set
in the P437.

3-138

P437/EN M/R-11-A // P437311650

P437

3 Operation

MA IN: N e ut r .pt. tre at. PSx = Low-imped. grounding


Ground fault detection DIST: Starting G occurs with this setting when the
threshold of the IN> or VNG> trigger is exceeded. Furthermore, triggering of
stage VNG>> and the lapse of timer stage tVNG>> is signaled (see Fig. 3-98,
(p. 3-138)).

MA IN : Ne ut r.pt. treat. P Sx = Isol./res.w.start.PG


MA IN : Ne ut r.pt. tre at. PSx = Isol./res.w/o st. PG
If any of these two settings is selected, instantaneous ground fault
detection DIST: Starting G operates in the event of multiple phase-toground fault detection when the thresholds of the IN> and VNG> triggers are
exceeded. Even in the case of a single-phase fault, that is, in the event that
only one base point is detected, ground fault detection will operate, but not
until tIN> has elapsed.

MA IN: Ne utr .pt. treat. P Sx = Short-durat. ground.


Operation here corresponds to operation with the setting Isol./
res.w.start.PG or Isol./res.w/o st. PG except that in the case of a sustained
ground fault the timer stage tIN> remains activated due to the operating
trigger VNG>> and therefore no longer has any effect in the event of
subsequent short-duration grounding.

MAIN:
Neutr.pt. treat. PSx
[ * ]
2: Isol./res.w.start.PG
3: Isol./res.w/o st. PG
4: Short-durat. ground.

DIST:
Starting G

1: Low-imped. grounding

303 507

DIST:
Start. IN> triggered
DIST:
Start. switch. to PG
[ 040 052 ]

303 502

DIST:
Start.VNG> triggered
303 504

100ms

FT_RC:
Trigger N

310 058

DIST:
tIN> elapsed

FT_DA:
Trigger N

303 503

310 059

DIST:
IA>> triggered
303 511

DIST:
IB>> triggered
303 512

DIST:
IC>> triggered
303 513

* Parameter

DIST:
VPP< triggered

set
set
set
set

303 509

DIST:
Start.ZPP< triggered
303 510

1
2
3
4

MAIN:
Neutr.pt. treat. PSx
010
001
001
001

048
076
077
078

49Z7004A

Fig. 3-99: Evaluation of trigger signals.

3.21.1.3

Enabling Undervoltage and Underimpedance Fault Detection


The undervoltage and underimpedance fault detection functions are enabled by
I>(Imin) in the corresponding measuring systems. For the two possible dynamic
ranges of current measurement, one parameter each is available for setting the
fault detection value for I>(Imin). In order to control contention problems when
current and voltage appear at the same time (branch voltage transformers),
measuring system enabling is delayed by 15 ms.
For sensitive detection of double ground faults with isolated neutral/resonant
grounding, the P437 checks to determine whether the base point current I>(Imin)
is exceeded in one phase only and whether the measured value falls below the

P437/EN M/R-11-A // P437311650

3-139

P437

3 Operation

set threshold for underimpedance fault detection in two phases. Enabling


proceeds in the phases where the voltage is below the set threshold.

DIST:
Starting blocked

DIST:
I> (Ibl) PSx

303 500

IA

DIST:
IA>(Ibl) trigg.
303 598

IB

DIST:
IB>(Ibl) trigg.

IC

303 599

DIST:
IC>(Ibl) trigg.
303 600

DIST:
V< PSx
[ * ]

Meas.val.> set value


C
15ms

DIST:
Enable V<, Z<, A
303 514

VA-G
VB-G
VC-G

15ms

DIST:
Enable V<, Z<, B
303 515

15ms

DIST:
Enable V<, Z<, C
303 516

Meas.val< set value

VA-G3
VB-G3
VC-G3

MAIN:
Neutr.pt. treat. PSx
[ * ]
2: Isol./res.w.start.PG
4: Short-durat. ground.

* Parameter
set
set
set
set

1
2
3
4

DIST:
V< PSx

MAIN:
Neutr.pt. treat. PSx

DIST:
I> (Ibl) PSx

010
010
011
011

010
001
001
001

010
010
011
011

069
089
009
029

048
076
077
078

068
088
008
028

45Z8029A

Fig. 3-100: Enabling undervoltage and underimpedance fault detection.

3.21.1.4

Undervoltage Detection
Undervoltage fault detection monitors the phase-to-ground voltages or the
phase-to-phase voltages to determine whether they fall below the set
threshold V<.
Operation of undervoltage fault detection can be determined by selecting the
operating mode. The following operating modes are possible:

3-140

Undervoltage fault detection is disabled.

The undervoltage fault detection function evaluates only the decisions of


the phase-to-ground loops, once these functions have been enabled by
ground fault detection.

Ground fault detection brings about a switch from phase-to-phase to phaseto-ground loops.

P437/EN M/R-11-A // P437311650

P437

3 Operation

DIST:
Operat. mode V< PSx
[ * ]
0
1
2
0: W/o V< starting
1: With V< start. PG
2: With V< start.PG,PP
DIST:
Start. switch. to PG
[ 040 052 ]
DIST:
Enable V<, Z<, A
303 514

DIST:
Enable V<, Z<, B
303 515

DIST:
Enable V<, Z<, C
303 516

DIST:
V< PSx
[ * ]

VA-G

VA-G3

VB-G

VB-G3

VC-G

VC-G3

DIST:
VA< triggered
303 517

DIST:
VB< triggered
303 518

DIST:
VC< triggered
303 519

DIST:
VPP< triggered
303 509

Parameter

DIST:
V< PSx

DIST:
Operat. mode V< PSx

set
set
set
set

010
010
011
011

010
010
011
011

1
2
3
4

069
089
009
029

067
087
007
027

47Z0157A

Fig. 3-101: Undervoltage detection.

3.21.1.5

Underimpedance Fault Detection


Underimpedance fault detection determines the impedances of the phase-toground or phase-to-phase loops.
The underimpedance fault detection mode can be set by selecting the operating
mode via DIST: Ope rat. mode Z< P Sx. The following operating modes are
possible:

W/o Z< starting: Underimpedance fault detection is disabled.

With Z< starting P-G: The underimpedance fault detection function


evaluates only the decisions of the phase-to-ground loops, once these
functions have been enabled by ground fault detection.

With Z< start.PG,PP: Ground fault detection brings about a switch from
phase-to-phase to phase-to-ground loops.

All underimpedance fault detection measuring loops are blocked when the I>>>
trigger operates (see Section 3.21.1.1, (p. 3-136)). When overcurrent or
undervoltage fault detection operates, the corresponding measuring loops are
blocked phase-selectively.

P437/EN M/R-11-A // P437311650

3-141

P437

3 Operation

DIST:
Operat. mode Z< PSx
[ * ]

0
1
2

0: W/o Z< starting


DIST:
Enable ZP-G
303 508

0: W/o Z< starting


1: With Z< starting P-G
2: With Z< start.PG,PP

DIST:
Start. switch. to PG
[ 040 052 ]
DIST:
I>>> triggered
303 501

DIST:
Enable ZA-G starting

DIST:
Enable V<, Z<, A
303 514

303 520

DIST:
IA>> triggered
303 511

DIST:
VA< triggered
303 517

DIST:
Enable V<, Z<, B

DIST:
Enable ZB-G starting

303 515

303 521

DIST:
IB>> triggered
303 512

DIST:
VB< triggered
303 518

DIST:
Enable V<, Z<, C

DIST:
Enable ZC-G starting

303 516

303 522

DIST:
IC>> triggered
303 513

DIST:
VC< triggered
303 519

DIST:
Enable ZA-B starting
303 523

DIST:
Enable ZB-C starting
303 524

Parameter

DIST:
Operat. mode Z< PSx

set
set
set
set

010
010
011
011

1
2
3
4

066
086
006
026

DIST:
Enable ZC-A starting
303 525

D5Z5010A

Fig. 3-102: Enabling underimpedance fault detection.

If measurement is enabled, the loop impedance is determined and compared to


ascertain that it is within the set impedance range. The loop impedance of the
phase-to-ground loops is determined, depending on the setting DIST: Z
evaluat ion PSx, by using the ground current corrected by the set ground factor
kG or by using the phase current multiplied by 2 or by (1+kG).

3-142

P437/EN M/R-11-A // P437311650

P437

3 Operation

Setting ZPG=VPG/(IP + kG*IN): The calculation is carried out using the


ground current corrected by the set ground factor kG:
Z PG =

I P + kG I N

Setting ZPG=VPG/2*IP: The calculation is carried out using the phase


current multiplied by 2:
Z PG =

V PG

V PG
2 I P

Setting ZPG=VPG/IP*(1 + kG): The calculation is carried out using the


phase current and the ground factor kG:
Z PG =

V PG
I P (1 + kG )

The following values must be set in order to determine the underimpedance fault
detection characteristic:

Reactance in forward direction Xfw

Load angle

Ratio Zbw/Zfw, where

Zbw: Impedance in backward (reverse) direction;

Zfw: Impedance in forward direction)

Phase-to-ground impedance in forward direction Zfw,PG

Phase-to-phase impedance in forward direction Zfw,PP

Phase-to-ground resistance in forward direction Rfw,PG

Phase-to-phase resistance in forward direction Rfw,PP

If, on the basis of the settings, the reach in the backward (reverse) direction is
greater than 3Znom, then the range is limited to 3Znom (where
Znom = Vnom / Inom).

P437/EN M/R-11-A // P437311650

3-143

P437

3 Operation

110

Rfw,PG

Forward direction
Rfw,PP

Backward direction

Xfw
Xfw

w
Zf

70

Zfw
, PP
Zf
w,
PG

bw

70

D5Z5212A

Fig. 3-103: Fault detection characteristic of the underimpedance fault detection function.

DIST:
Abs. value kG PSx
[ * ]
DIST:
Angle kG PSx
[ * ]

+
+
+

IA
IB
IC

IN

INkG

DIST:
INkG
450 171

IA(1+kG)

DIST:
IA(1+kG)
450 168

IB(1+kG)

DIST:
IB(1+kG)
450 169

IC(1+kG)

DIST:
IC(1+kG)
450 170

Parameter

DIST:
Abs. value kG PSx

DIST:
Angle kG PSx

set
set
set
set

012
012
013
013

012
012
013
013

1
2
3
4

037
087
037
087

036
086
036
086

47Z1458

Fig. 3-104: Formation of currents corrected by the ground factor.

3-144

P437/EN M/R-11-A // P437311650

P437

3 Operation

DIST:
Enable ZP-G
303 508

DIST:
Z evaluation PSx
[ * ]

DIST:
INkG
450 171

DIST:
Xfw PSx
[ * ]

IA
IB

DIST:
PSx
[ * ]

DIST:
Zbw/Zfw PSx
[ * ]

IC
2IA
2IB
2IC

DIST:
Zfw,PG PSx
[ * ]

DIST:
IA(1+kG)

450 168

DIST:
Zfw,PP PSx
[ * ]

DIST:
IB(1+kG)
450 169

1. . .3

DIST:
IC(1+kG)

DIST:
Rfw,PG PSx
[ * ]

1: ZPG=VPG/(IP + kG*IN)
2: ZPG=VPG/2*IP
3: ZPG=VPG/IP*(1 + kG)

450 170

DIST:
Enable ZA-G starting

DIST:
Rfw,PP PSx
[ * ]

303 520

VA-G

COMP
ZA-G

DIST:
ZA< start. triggered

DIST:
ZB< start. triggered

DIST:
ZC< start. triggered

DIST:
Start.ZPP< triggered

303 526

COMP
DIST:
Enable ZB-G starting

303 527

COMP

303 521

VB-G

303 528

COMP

ZB-G

303 510

COMP
DIST:
Enable ZC-G starting

c
COMP

303 522

VC-G
ZC-G

DIST:
Enable ZA-B starting

303 523

ZA-B

DIST:
Enable ZB-C starting

303 524

ZB-C

DIST:
Enable ZC-A starting

303 525

+
ZC-A

Parameter

DIST:
Rfw,PG PSx

DIST:
Rfw,PP PSx

set
set
set
set

010
010
010
011

010
010
010
011

1
2
3
4

051
071
091
011

Parameter

DIST:
Z evaluation PSx

DIST:
Xfw PSx

DIST:
PSx

DIST:
Zbw/Zfw PSx

DIST:
Zfw,PG PSx

DIST:
Zfw,PP PSx

set
set
set
set

025
024
024
025

010
010
010
011

010
010
011
011

010
010
010
011

010
010
010
011

010
010
010
011

1
2
3
4

093
013
073
033

050
070
090
010

063
083
003
023

053
073
093
013

101
102
103
104

052
072
092
012

105
106
107
108

47Z1459B

Fig. 3-105: Underimpedance detection.

P437/EN M/R-11-A // P437311650

3-145

P437
3.21.1.6

3 Operation

Fault Detection Logic


The fault detection logic links the phase-selective output signals from the
following fault detections to form common phase-selective starting decisions (SA,
SB, and SC) and SN1:

Overcurrent detection (I>>)

Ground fault detection

Undervoltage detection (V<)

Underimpedance detection (Z<)

. The phase-selective starting decisions are combined to form general


starting and thus produce the MAIN: Ge ne ral s tarting signal. Ground fault
detection alone does not bring about general starting.
If fault detection operates via overcurrent fault detection, single-phase fault
detection may operate without ground fault detection. In order for the measuring
loops for distance and directional measurement to be properly selected even in
this case, either SN1 or starting in another phase must be triggered as well. It is
possible to specify whether, in the case of single-phase starting, SN1 will always
be triggered or whether depending on the magnitude of the phase currents
SN1 or starting in one phase will be transfer-triggered.

MA IN : Transfe r f or 1 p P Sx = Ground
With single-phase overcurrent fault detection, SN1 is started and transferred
after the timer stage tIN> has elapsed (see Section 3.21.1.2, (p. 3-137) for
setting).
If there is a change from single-phase overcurrent fault detection without
ground to multi-phase fault detection or single-phase-to-ground fault
detection, starting will occur instantaneously.

MA IN : Transfer for 1p PSx = P or G =f(Imed,Imax)


For single-pole overcurrent fault detection, the decision as to whether
starting in one phase or SN1 starting will be transferred depends on the
Imed / Imax ratio. The magnitude of the medium phase current must be more
than 2/3 the magnitude of the maximum current for the phase to be
transfer-triggered. If the current with the medium-sized magnitude is
smaller, SN1 will be triggered after timer stage tIN> has elapsed.
If there is a change from single-phase overcurrent fault detection without
ground to multi-phase fault detection or single-phase-to-ground fault
detection, starting will occur instantaneously.

3-146

P437/EN M/R-11-A // P437311650

P437

3 Operation

DIST:
VA< triggered

DIST:
Starting A

303 517

303 529

DIST:
ZA< start. triggered
303 526

DIST:
IA>> triggered
303 511

DIST:
VB< triggered

DIST:
Starting B

303 518

303 530

DIST:
ZB< start. triggered
303 527

DIST:
IB>> triggered
303 512

DIST:
VC< triggered

DIST:
Starting C

303 519

303 531

DIST:
ZC< start. triggered
303 528

DIST:
General starting
[ 036 240 ]

DIST:
IC>> triggered
303 513

DIST:
1-pole starting
303 533

DIST:
Multipole starting
DIST:
Starting G

303 534

303 507

DIST:
tIN> PSx
[ * ]

DIST:
Starting N1
303 535

DIST:
Zero-sequ. starting
[ 036 021 ]

MAIN:
Transfer for 1p PSx
[ * ]
1: Ground
2: P or G =f(Imed,Imax)

IA

|Imedium|/|Imax|2/3

COMP
IB
IC

|Imedium|/|Imax|>2/3

Imax
Imedium

COMP

COMP

COMP

Parameter

DIST:
tIN> PSx

MAIN:
Transfer for 1p PSx

set
set
set
set

010
010
010
011

010
001
001
001

1
2
3
4

057
077
097
017

040
079
080
081

45Z8030A

Fig. 3-106: Fault detection and starting logic.

If a general starting condition is present, then the decisions of the following


systems are signaled:

Overcurrent fault detection

Undervoltage fault detection

Underimpedance fault detection

P437/EN M/R-11-A // P437311650

3-147

P437

DIST:
Bl.Start. I>>

3 Operation

450 204

DIST:
General starting
[ 036 240 ]
DIST:
IA>> triggered
303 511

DIST:
IB>> triggered
303 512

DIST:
Starting I>>
[ 011 139 ]

&

DIST:
Starting I>> A
[ 040 064 ]

&

DIST:
Starting I>> B
[ 040 065 ]

&

DIST:
Starting I>> C
[ 040 097 ]

&

DIST:
Starting V< A
[ 040 067 ]

&

DIST:
Starting V< B
[ 040 075 ]

&

DIST:
Starting V< C
[ 040 096 ]

&

DIST:
Starting Z< A
[ 040 070 ]

&

DIST:
Starting Z< B
[ 040 071 ]

DIST:
IC>> triggered
303 513

DIST:
VA< triggered
303 517

DIST:
VB< triggered
303 518

DIST:
VC< triggered
303 519

DIST:
ZA< start. triggered
303 526

DIST:
ZB< start. triggered

DIST:
Starting Z< C
[ 040 072 ]

&

303 527

DIST:
ZC< start. triggered
303 528

DIST:
Bl.Start. Z<

DIST:
Starting Z<
[ 036 241 ]

450 205

45Z8032A

Fig. 3-107: Fault detection signals of distance protection.

3.21.2

Selection of Measured Values


The P437 selects measuring loops based on the phase-selective fault detection
decision. The fault impedances (short-circuit impedances) and the fault direction
are determined from the voltage and current values collected from these
measuring loops.
For multi-phase-to-ground faults, the user can specify whether phase-to-ground
or phase-to-phase variables will be used for measurement. For single-phase
faults, it is possible to disable impedance and directional measurement.

3-148

P437/EN M/R-11-A // P437311650

P437

3 Operation

Measuremen PG Loops
t with Phaseto-Ground
Fault
Detection

PP Loops or
No Loops

Measuring Loop 1

PG Loops

PP Loops

Measuring Loop 2

PG Loops

PP Loops

Measuring Loop 3

Starting

Vmea Imeas Vmea Imeas Vmea Imeas Vmea Imeas Vmea Imeas Vmea Imeas
s,1
,1
s,1
,1
s,2
,2
s,2
,2
s,3
,3
s,3
,3

A, B, C, G

VA-G

IA,cor VA-B
r

IA-B

VB-G

IB,cor VB-C
r

IB-C

VC-G

IC,cor VC-A
r

IC-A

A, B, C

VA-B

IA-B

VA-B

IA-B

VB-C

IB-C

IB-C

VC-A

IC-A

IC-A

A, B, G

VA-G

IA,cor VA-B
r

IA-B

VB-G

IB,cor /
r

B, C, G

VB-G

IB,cor VB-C
r

IB-C

VC-G

IC,cor /
r

A, C, G

VA-G

IA,cor VC-A
r

IC-A

VC-G

IC,cor /
r

A, B

VA-B

IA-B

VA-B

IA-B

B, C

VB-C

IB-C

VB-C

IB-C

A, C

VC-A

IC-A

VC-A

IC-A

A, G

VA-G

IA,cor /
r

B, G

VB-G

IB,cor /
r

C, G

VC-G

IC,cor /
r

VB-C

VC-A

Only one measuring loop is shown in the following block diagrams. If several
measurement loops are selected, the P437 links the measuring decisions with an
OR operator.

P437/EN M/R-11-A // P437311650

3-149

P437

3 Operation

DIST:
Starting N1
303 535

DIST:
Starting A
303 529

DIST:
Starting B
303 530

DIST:
Starting C
303 531

DIST:
Meas. start. 1pG PSx
[ * ]

1
2
1: PG loops
2: None

DIST:
Select.meas.loop A-G
303 537

DIST:
Select.meas.loop B-G
303 538

DIST:
Select.meas.loop C-G
303 539

DIST:
Select.meas.loop P-G

DIST:
Meas. start. 2pG PSx
[ * ]

303 543

1
2
1: PG loops
2: PP loops

DIST:
Select.meas.loop A-B
303 540

DIST:
Select.meas.loop B-C
303 541

DIST:
Select.meas.loop C-A
303 542

DIST:
Meas. start. 3pG PSx
[ * ]
DIST:
Select.meas.loop P-P
303 544

1
2
1: PG loops
2: PP loops
Parameter

DIST:
Meas. start. 1pG PSx

DIST:
Meas. start. 2pG PSx

DIST:
Meas. start. 3pG PSx

set 1
set 2
set 3
set 4

012 172
012 173
012 174
012 175

012 176
012 177
012 178
012 179

012 180
012 181
012 182
012 183

47Z0161A

Fig. 3-108: Selection of measuring loops.

3.21.2.1

Parallel Line Compensation


In the case of grounded faults, it is possible to activate parallel line compensation
if the proper setting has been made. If parallel line compensation has been
enabled, then the residual current of the parallel line will be included in distance

3-150

P437/EN M/R-11-A // P437311650

P437

3 Operation

and directional measurement as a function of the decision of the zero current


scale. The zero current scale compares the magnitude of the residual currents
in the line and the parallel line. Compensation is only permitted if the ratio of the
residual current in the parallel line to the residual current in the line to be
protected is lower than the value set at MAIN: k P ar PSx. Otherwise there is the
danger of incorrect compensation in the healthy line with a residual current in
the shorted parallel line. The ratio should be set to a value smaller than 1, so as
to prevent such incorrect compensation, even with faults at the line's end (with
residual currents of differing magnitude caused by unbalanced lines).

P437/EN M/R-11-A // P437311650

3-151

P437

3 Operation

DIST:
IN,par> PSx
[ * ]

DIST:
IN,par> triggered
[ 037 210 ]

IN,par

DIST:
kG,par angle PSx
[ * ]
DIST:
kG,par abs.value PSx
[ * ]

DIST:
IkG,par

kG,par IG,par

303 605

MAIN:
kPar PSx
[ * ]
IA
IB
IC

|IN,par|kPar.line <

DIST:
With mutual comp.
[ 038 039 ]

|IN|

|IN,par|kPar.line
|IN|

DIST:
Mutual comp. PSx
[ * ]
0
1

c 1,2,3

0: Without

c 4,5,6

1: Depend. on IN/IN,par

1
DIST:
IkG
303 604

1,4

DIST:
IA,corr.

2,5

DIST:
IB,corr.

3,6

DIST:
IC,corr.

303 606

303 607

303 608

Parameter

DIST:
IN,par> PSx

DIST:
kG,par abs.value PSx

DIST:
kG,par angle PSx

DIST:
Mutual comp. PSx

MAIN:
kPar PSx

set 1

012 184

012 049

012 048

025 095

set 2

012 185

012 099

012 098

024 015

024 017

set 3

012 186

013 049

013 048

024 075

024 077

025 097

set 4

012 187

013 099

013 098

025 035

025 037

47Z0162B

Fig. 3-109: Parallel line compensation.

3.21.2.2

CVT Stabilization
Only the fundamental component of the selected measuring voltages is
evaluated. If stabilization for capacitive voltage transformers (CVT stabilization)

3-152

P437/EN M/R-11-A // P437311650

P437

3 Operation

has been enabled, the device checks to determine whether the second harmonic
exceeds the threshold of 0.01Vnom. If so, a special filter designed specifically for
CVTs is activated.

DIST:
Select.meas.loop A-G
303 537

DIST:
Select.meas.loop B-G
303 538

DIST:
Select.meas.loop C-G
303 539

DIST:
Select.meas.loop A-B
303 540

DIST:
Select.meas.loop B-C
303 541

DIST:
Select.meas.loop C-A
303 542

DIST:
IA,corr.

DIST:
CVT stabilization
[ 010 031 ]

303 606

DIST:
IB,corr.
303 607

DIST:
IC,corr.

303 608

0: No
IA

1: Yes

IB

IC

VA-G
2fnom
VB-G

VC-G

> 0.01 Vnom

fnom
1
Filter 1
fnom
2
Filter 2

DIST:
Vmeas
303 546

DIST:
Imeas
303 545

47Z0163A

Fig. 3-110: CVT stabilization and selection of measured variables.

3.21.3

Distance and Directional Measurement


The P437 determines the fault impedance and the fault direction on the basis of
the selected measured values. A voltage memory is available so that
measurement will function correctly, even with very low fault voltages.

P437/EN M/R-11-A // P437311650

3-153

P437
3.21.3.1

3 Operation

Voltage Memory
Voltage VA-B is the reference voltage for the voltage memory. If the voltage
exceeds the fixed value of 0.65Vnom and there is no starting of the distance
protection function, then the voltage memory will be synchronized.
Synchronization requires approximately 300 ms. Then a check is carried out to
determine whether the frequency satisfies the following condition:
0.95fnom < f < 1.05fnom
If the condition is satisfied, the voltage memory is enabled. The frequency
condition is checked cyclically. As soon as the frequency condition is no longer
met, the enable is canceled.
If the magnitude of the reference voltage drops below 0.65Vnom or if a starting of
the distance protection function occurs, synchronization of the voltage memory
will be terminated. The voltage memory is then free-running and remains
enabled for 2 s.

DIST:
I>> triggered
303 597

DIST:
General starting
[ 036 240 ]

>0.65Vnom
DIST:
corr

corr

303 547

f/fnom = f

+
0.95fnom<f<1.05fnom

DIST:
Voltage mem. enabled

1
300ms

S1 1

303 549

R1
1

DIST:
tVmemory running
[ 040 034 ]

2s

DIST:
VA-B (stored)

VA-G

303 548

VB-G

49Z6433A

Fig. 3-111: Storing the reference voltage in memory.

3.21.3.2

Angle Determination
When general starting of distance protection occurs, the angles F and S are
determined. Angle F is the fault angle that is determined using the selected
measuring voltage Vmeas and the selected measuring current Imeas. Angle S is
determined on the basis of the voltage stored in memory and the selected
measuring current Imeas. Since the frequency of the stored voltage can differ
from the nominal frequency, a phase correction must be made. This correction is
determined by the frequency deviation and the time that has elapsed since
synchronization was terminated. Furthermore, an angle correction based on the
selected measuring loop and the setting at MA IN: Phase sequence is
required. The resulting angle, X, is used for further processing.

3-154

P437/EN M/R-11-A // P437311650

P437

3 Operation

DIST:
Voltage mem. enabled
303 549

DIST:
Vmeas

DIST:
F

303 546

303 550

DIST:
Imeas
303 545

DIST:
VA-B (stored)
303 548

DIST:
corr
303 547

MAIN:
Phase sequence
[ 010 049 ]
1: A - B - C

X1

2: A - C - B

X(-1)

DIST:
Select.meas.loop A-B

X = 0

303 540

DIST:
Select.meas.loop B-C

X = -120

303 541

DIST:
Select.meas.loop C-A

X = +120

303 542

DIST:
Select.meas.loop A-G

X = +150

303 537

DIST:
Select.meas.loop B-G

X = +30

303 538

DIST:
Select.meas.loop C-G

X = -90

303 539

DIST:
X
303 551

47Z0165A

Fig. 3-112: Angle determination.

3.21.3.3

Selecting the Angle for Direction Determination


For distance and directional measurement, the following angles are used as a
function of the magnitude of the selected measuring voltage and the fault
duration:

Fault angle F

Angle X

Set angle

If the selected measuring voltage Vmeas is above the threshold set at


DI ST: Op er.v al.Vm emory P Sx when the fault occurs, then the direction is
determined using fault angle F. If the measuring voltage is below the threshold
set at DI ST: Ope r.val .V mem or y PSx then angle X is used for directional
measurement. If the voltage memory is not enabled, angle X cannot be
determined. In this case the P437 checks whether the measuring voltage Vmeas is
within this range:
0.002Vnom < Vmeas < DIST: Oper. val.V me mory PSx
If such is the case then the direction is determined with fault angle F. Direction
determination using X or F is not possible if the voltage memory is not enabled
or if the measuring voltage is less than 0.002Vnom. In these cases, set angle is
used for directional measurement. This means that a decision is made for the
forward direction.

P437/EN M/R-11-A // P437311650

3-155

P437

3 Operation

Angle for Direction Determination:


V memory

Vmeas < 0.002Vnom

0.002Vnom < Vmeas < D I S T : O p e r . v a l . V m e m o r y P S x

Enabled

Not enabled

F
A decision is made for the forward direction if the angle selected for direction
determination is in this range:
45 < < +135
In the case of angles outside this range, a decision is made for the backward
(reverse) direction.

3-156

P437/EN M/R-11-A // P437311650

P437

3 Operation

DIST:
Voltage mem. enabled
303 549

DIST:
General starting
[ 036 240 ]

DIST:
Forw. w/o meas. y
[ 1* ]

< 0,002 Vnom

DIST:
Dir.using Vmeas y
[ 1* ]

DIST:
Vmeas
303 546

DIST:
Oper.val.Vmemory PSx
[

]
DIST:
Dir.using Vmem y
[ 1* ]
C1
C2
C3

DIST:

303 552

DIST:
F

2
303 550

DIST:
X

-45 < N < 135

303 551

1 ... 3

135 < N < 315

set 1

010 109

set 2

010 116

set 3

010 117

set 4

010 118

y:

DIST:
Fault backward / BS
[ 036 019 ]
DIST:
Fault forwd. / LS, x
[ 2* ]

DIST:
Oper.val.Vmemory PSx

* Parameter

DIST:
Fault forward / LS
[ 036 018 ]

DIST:
Fault backwd / BS, x
[ 2* ]

Sys1. Sys2, Sys3

Starting

Active measur. loop

DIST:
Dir.using Vmeas y

DIST:
Dir.using Vmem y

DIST:
Forw. w/o meas. y

1p, 2p, 3p

Measuring loop 1

038 045

038 047

038 044

2p, 3p

Measuring loop 2

038 105

038 106

038 104

3p

Measuring loop 3

038 108

038 109

038 107

Selected meas. var.


x: A, B, C

Possible signals

Vmeas

Imeas

DIST:
Fault forwd. / LS, x

VA-G

IA,corr.

038 010

038 011

VB-G

IB,corr.

038 012

038 013

VC-G

IC,corr.

038 014

038 015

VA-B

IA-B

038 010
038 012

038 011
038 013

VB-C

IB-C

038 012
038 014

038 013
038 015

IC-A

038 010
038 014

038 011
038 015

VC-A

DIST:
Fault backwd / BS, x

47Z1162B

Fig. 3-113: Directional measurement.

3.21.3.4

Selecting the Angle for Impedance Calculation


The angle that is used to calculate fault impedance is selected according to the
following criteria:

P437/EN M/R-11-A // P437311650

3-157

P437

3 Operation

If the measuring voltage Vmeas is greater than the set threshold


(D IST : Op er.v al.V memory PSx) when the fault occurs, then fault angle
F is used to calculate fault impedance.

If the fault voltages are lower than the set threshold


(D IS T: O pe r.val.V memory PSx) and the voltage memory is enabled, a
check is made to determine whether angles F and X are in the forward
direction, i.e.: 45 < < +135

If both angles are in the same direction, either forward or backward,


then fault angle F is selected for distance measurement.

If angle F is in the forward direction and angle X is in the backward


direction, then an angle of (180 + ) is specified for the calculation.
If angle X is in the forward direction and angle F is in the backward
direction, then set angle is used for distance measurement.

If voltage memory is not enabled, the P437 checks whether:

the measuring voltage Vmeas is within this range:


0.002Vnom < Vmeas < DIST: O pe r.val .V memory PSx
If such is the case then the impedance is calculated using fault angle F.

3-158

the selected measuring voltage Vmeas < 0.002Vnom. In this case, the
impedance is calculated using set angle .

P437/EN M/R-11-A // P437311650

P437

3 Operation

DIST:
Voltage mem. enabled
303 549

DIST:
General starting
[ 036 240 ]
< 0,002 Vnom

DIST:
Vmeas
303 546

DIST:
Oper.val.Vmemory PSx
[ * ]

DIST:
F

-45 < F < 135


303 550

DIST:
X

-45 < X < 135


1

303 551

2
3
4
2
DIST:

180+

303 552

3
4
1 ... 4

1
2
3
1 ... 3

DIST:
Z
303 553

Parameter

DIST:
Oper.val.Vmemory PSx

set
set
set
set

010
010
010
011

1
2
3
4

109
116
117
118

49Z6436A

Fig. 3-114: Selecting the angle for impedance calculation.

3.21.3.5

Distance Measurement
One of the following types of characteristics may be selected for distance
measurement by way of the setting at DI ST: C haract erist ic PSx:

Circle

Polygon

P437/EN M/R-11-A // P437311650

3-159

P437

3 Operation

DIST:
Characteristic PSx
[ * ]

1: Circle

2: Polygon

1: Circle
2: Polygon

Parameter

DIST:
Characteristic PSx

set
set
set
set

012
073
074
075

1
2
3
4

040
097
097
097

D5Z5019A

Fig. 3-115: Selecting the characteristic.

3.21.3.5.1

Extending the Measuring Range for Single-Phase Fault Detection


The user has the option of specifying whether the measuring range of impedance
zone 1 shall be extended by zone extension factor kze HSR in the case of singlephase fault detection. If this is desired, the measuring range of impedance zone
1 is extended if the following conditions are met:

There is an enable.

ARC (auto-reclosing control) was ready before general starting occurred.

The enable is issued from the local control panel or through an appropriately
configured binary signal input. If the enable signal is to be issued from the local
control panel, it is possible to define conditions that must be met so that the
enable signal is issued.

3-160

P437/EN M/R-11-A // P437311650

P437

3 Operation

DIST:
Zone extens. for 1pG
[ 011 049 ]
0
1
0: No
1: Yes

DIST:
Enable ZE f. 1pG PSx
[

Parameter

DIST:
Enable ZE f. 1pG PSx

set 1
set 2
set 3
set 4

012 039
012 089
013 039
013 089

1
2
0: Without
1: If PSIG not ready
2: Always
DIST:
Zone ext. 1pG active
[ 039 028 ]

PSIG:
Not ready
[ 037 028 ]
DIST:
Enable ZE f. 1pG EXT
[ 038 025 ]

DIST:
Zone ext. HSR 1pG
[ 039 029 ]

ARC:
Ready
[ 004 068 ]
MAIN:
General starting
[ 036 000 ]
DIST:
1-pole starting
303 533

DIST:
Starting N1
303 535

47Z0175A

Fig. 3-116: Extending the measuring range for single-phase fault detection.

3.21.3.5.2

Circle Characteristic
The fault impedance value ZF is determined using the selected measuring
quantities Vmeas and Imeas. If the setting Arc compensation has been chosen
(DI ST: A rc comp . ci rcle P Sx = Yes), then a correction to the measured fault
impedance is calculated for angles Z in the range of 45 < Z < or
135 < Z < (+180) as follows:

| Z

F,corr

|=

| Z F |
1 + sin

The following relation applies in the range 45 < Z < :


= Z
The following relation applies in the range 135 < Z < (+180):
= Z+180

P437/EN M/R-11-A // P437311650

3-161

P437

3 Operation

DIST:
Arc comp. circle PSx
[ * ]

0
1
0: No

1: Yes

-45<Z<
DIST:
Z
303 553

135<Z<(+180)

1
1

1 =-Z

DIST:

DIST:
|Zmeas|
303 567

303 552

2 =-Z+180
DIST:
Characteristic PSx
[ * ]
1: Circle

|ZF,corr|=
|ZF|/(1+sin)
DIST:
Vmeas
303 546

|ZF|=|Vmeas|/|Imeas|

DIST:
Imeas
303 545

Parameter

DIST:
Arc comp. circle PSx

DIST:
Characteristic PSx

set
set
set
set

012
012
012
012

012
073
074
075

1
2
3
4

038
090
091
092

040
097
097
097

D5Z5026B

Fig. 3-117: Impedance measurement with the circle characteristic.

In the R-X diagram, the characteristic shown in the following figure is obtained. If
the characteristic were to be measured with sine variables for the setting
Arc compensation, the dot-dash line would be obtained.

3-162

P437/EN M/R-11-A // P437311650

P437

3 Operation

In this diagram, the following example settings have been used: n = 1 to 6, =


60; dot-dash line: with arc compensation; dashed line: kze = 1.2 (adjustable in
Zone 1 only).
+135
Forward direction

Zn

Z
R

Backward direction

45 315
D5Z5025A

Fig. 3-118: P437 impedance and direction characteristic for the Circle setting.

The calculated impedance |Zmeas| is compared with the set impedance in the six
impedance zones. If the measured impedance is smaller than or equal to the set
impedance, then a distance decision is made for the corresponding zone(s).

P437/EN M/R-11-A // P437311650

3-163

P437

3 Operation

DIST:
Z2 (circle) PSx
[ * ]
DIST:
2 (circle) PSx

DIST:

[ * ]

DIST:
|Zmeas|

303 552

DIST:
Dist.decision zone n

|Zmeas|f(Zn, n)

303 567

303 561

Impedance zone2(n=2)
* Parameter
set
set
set
set

1
2
3
4

Impedance zone3(n=3)

DIST:
Z2 (circle) PSx

DIST:
2 (circle) PSx

012
073
074
075

072
073
074
075

043
092
092
092

set
set
set
set

1
2
3
4

set
set
set
set

095
095
095
095

1
2
3
4

DIST:
Z3 (circle) PSx

DIST:
3 (circle) PSx

012
073
074
075

072
073
074
075

044
093
093
093

096
096
096
096

Impedance zone5(n=5)

Impedance zone4(n=4)
* Parameter

* Parameter

DIST:
Z4 (circle) PSx

DIST:
4 (circle) PSx

012
073
074
075

072
073
074
075

045
094
094
094

* Parameter

099
099
099
099

set
set
set
set

1
2
3
4

DIST:
Z5 (circle) PSx

DIST:
5 (circle) PSx

012
012
012
012

012
012
012
012

148
149
150
151

164
165
166
167

Impedance zone6(n=6)
* Parameter
set
set
set
set

1
2
3
4

DIST:
Z6 (circle) PSx

DIST:
6 (circle) PSx

012
012
012
012

012
012
012
012

152
153
154
155

168
169
170
171

47Z1467A

Fig. 3-119: Setting impedance zones 2 to 6 and distance measurement.

In addition to the settings described above, the zone extension factors kze for
high-speed reclosure (HSR) and time-delay reclosure (TDR) can also be set
separately for phase-to-ground (PG) and phase-to-phase (PP) loops for
impedance zone 1. The impedances modified by zone extension factor kze are
calculated as follows:
Z1,kze = kzeZ1
The increase in reach by zone extension factor kze HSR is controlled by the
following:

Protective signaling (PSIG: Z1 e xten ded)

Internal auto-reclosing control, if protective signaling is not ready or


irrespective of the readiness of protective signaling during the reclose
command.

Switch on to fault protection (SOTF: Z1 e xte nded)

An external signal (D IST: Zone exte nsi on EXT).

The impedance characteristic is extended by zone extension factor kze TDR if a


time-delay reclosure is carried out by internal auto-reclosing control.

3-164

P437/EN M/R-11-A // P437311650

P437

3 Operation

PSIG:
Ready
[ 037 027 ]
ARC:
Zone extension TDR

DIST:
Zone extension TDR
[ 038 022 ]

303 000

ARC:
Zone extension HSR
303 001

DIST:
Zone extension HSR
[ 036 103 ]

ARC:
Meas.r.extd. ext.ARC
303 025

PSIG:
Z1 extended
[ 035 075 ]
ARC:
Zone extension RC

DIST:
Zone extension
[ 036 065 ]

303 002

SOTF:
Z1 extended
[ 035 076 ]
DIST:
Zone extension EXT
[ 036 046 ]

DIST:
Z1 (circle) PSx
[ * ]
DIST:
1 (circle) PSx
[ * ]

DIST:
Zone ext. HSR 1pG
[ 039 029 ]

DIST:

303 552

DIST:
Select.meas.loop P-G

DIST:
kze,PG TDR PSx
[ * ]

DIST:
kze,PP TDR PSx
[ * ]

DIST:
kze,PG HSR PSx
[ * ]

DIST:
kze,PP HSR PSx
[ * ]

303 543

DIST:
Select.meas.loop P-P
303 544

|Zmeas|f(Z1,1)

DIST:
Dist.decision Z1, x

|Zmeas|f(Z1,1,kze)

DIST:
Dist.decision Z1ze,x

303 629

DIST:
|Zmeas|

303 630

303 567

S1 1
MAIN:
General starting
[ 036 000 ]

R1

ASC:
Manual close request

set 1
set 2
set 3
set 4

303 565

x: A-N, B-N, C-N,


A-B, B-C, C-A

305 000

* Parameter

DIST:
Dist.decis.Z1 stored

DIST:
Z1 (circle) PSx

DIST:
1 (circle) PSx

DIST:
kze,PG TDR PSx

DIST:
kze,PP TDR PSx

DIST:
kze,PG HSR PSx

DIST:
kze,PP HSR PSx

012 042
073 091
074 091
075 091

072 090
073 090
074 090
075 090

012 046
012 096
013 046
013 096

012 047
012 097
013 047
013 097

012 034
012 084
013 034
013 084

012 035
012 085
013 035
013 085

47Z1468A

Fig. 3-120: Setting impedance Zone 1 and distance measurement.

3.21.3.5.3

Polygon (Quadrilateral) Characteristic


The ZF fault impedance value is determined using the selected measuring
quantities: Vmeas and Imeas. By multiplying this value by the cosine or sine of the
angle selected for distance measurement, Z, we then calculate the fault
resistance RF or fault reactance XF.

P437/EN M/R-11-A // P437311650

3-165

P437

3 Operation

DIST:
Characteristic PSx
[ * ]
2: Polygon

DIST:
Vmeas
303 546

|ZF|=|Vmeas|/|Imeas|

DIST:
Imeas

DIST:
XF

|ZF|sinZ

303 555

303 545

DIST:
RF

|ZF|cosZ

303 554

DIST:
Z
303 553

Parameter

DIST:
Characteristic PSx

set
set
set
set

012
073
074
075

1
2
3
4

040
097
097
097

D5Z5021B

Fig. 3-121: Impedance measurement with the polygon characteristic.

The calculated quantities, RF and XF, are compared with the reference quantities,
Rref and Xref, of the four impedance zones. The reference quantities are
determined using the settings for determining the impedance zone(s). If both
quantities lie within the set impedance zone(s), then a distance decision is made
for the corresponding zone(s).
The impedance zones are determined by the following settings:

Reactance X

Resistance R, separately for phase-to-ground and phase-to-phase loops

Angle

Angle

Note that the specified precision of measurement can only be reached if the ratio
R / X is less than 8:
Rn,PG / Xn < 8, and
Rn,PP / Xn < 8
If the ratio is greater than this (i.e. the polygon becomes extremely flat), the
measurement conditions for high fault resistances become quite bad, because in
this case, the angle of the fault impedance gets small, which results in quite big
measurement deviations for the reactance.

Using these settings in the R-X diagram we obtain the characteristic shown in the
following figure.

3-166

P437/EN M/R-11-A // P437311650

P437

3 Operation

In this diagram, the following example settings have been used: n = 1 to 6, Xn =


6.5 , Rn = 2.0 , n = 50 , n = 15; dashed line: kze = 1.2 (adjustable in
Zone 1 only).
+135
Forward direction

Xn

45
n
Rfw,PP
Rfw,PG

Backward direction

45 315
D5Z5022A

Fig. 3-122: P437 impedance and directional characteristics for the Polygon setting.

The resistances for phase-to-ground and phase-to-phase loops can be set


separately for each zone. The different impedances are therefore compared with
different impedance characteristics.

P437/EN M/R-11-A // P437311650

3-167

P437

3 Operation

DIST:

c R2,PG (polygon) PSx

DIST:
Select.meas.loop P-G

303 543

DIST:
Select.meas.loop P-P

DIST:
R2,PP (polygon) PSx
[ * ]

DIST:
X2,PG (polygon) PSx
[ * ]

DIST:
X2,PP (polygon) PSx
[ * ]

303 544

DIST:
2 (polygon) PSx
[ * ]
DIST:
2 (polygon) PSx
[ * ]

DIST:
Z

Rnref=f(Rn,n,n,Z)
Rn,ref RF

303 553

Xnref=f(Rn,n,n,Z)

DIST:
Dist.decision zone n

Xn,ref XF

303 561

DIST:
RF
303 554

DIST:
XF
303 555

Impedance zone2(n=2)
Parameter

DIST:
R2,PG (polygon) PSx

DIST:
R2,PP (polygon) PSx

DIST:
X2,PG (polygon) PSx

DIST:
X2,PP (polygon) PSx

DIST:
2 (polygon) PSx

DIST:
2 (polygon) PSx

set
set
set
set

012
012
013
013

012
012
013
013

012
012
013
013

002
002
002
002

012
012
013
013

072
073
074
075

1
2
3
4

007
057
007
057

008
058
008
058

002
052
002
052

080
081
082
083

014
064
014
064

087
087
087
087

Impedance zone3(n=3)
Parameter

DIST:
R3,PG (polygon) PSx

DIST:
R3,PP (polygon) PSx

DIST:
X3,PG (polygon) PSx

DIST:
X3,PP (polygon) PSx

DIST:
3 (polygon) PSx

DIST:
3 (polygon) PSx

set
set
set
set

012
012
013
013

012
012
013
013

012
012
013
013

002
002
002
002

012
012
013
013

072
073
074
075

1
2
3
4

009
059
009
059

010
060
010
060

003
053
003
053

084
085
086
087

015
065
015
065

088
088
088
088

Impedance zone4(n=4)
Parameter

DIST:
R4,PG (polygon) PSx

DIST:
R4,PP (polygon) PSx

DIST:
X4,PG (polygon) PSx

DIST:
X4,PP (polygon) PSx

DIST:
4 (polygon) PSx

DIST:
4 (polygon) PSx

set
set
set
set

012
012
013
013

012
012
013
013

012
012
013
013

002
002
002
002

012
012
013
013

072
073
074
075

1
2
3
4

011
061
011
061

012
062
012
062

004
054
004
054

089
090
091
092

016
066
016
066

089
089
089
089

Impedance zone5(n=5)
Parameter

DIST:
R5,PG (polygon) PSx

DIST:
R5,PP (polygon) PSx

DIST:
X5,PG (polygon) PSx

DIST:
X5,PP (polygon) PSx

DIST:
5 (polygon) PSx

DIST:
5 (polygon) PSx

set
set
set
set

012
012
012
012

012
012
012
012

012
012
012
012

002
002
002
002

012
012
012
012

012
012
012
012

1
2
3
4

108
109
110
111

112
113
114
115

100
101
102
103

093
094
095
096

124
125
126
127

156
157
158
159

Impedance zone6(n=6)
Parameter

DIST:
R6,PG (polygon) PSx

DIST:
R6,PP (polygon) PSx

DIST:
X6,PG (polygon) PSx

DIST:
X6,PP (polygon) PSx

DIST:
6 (polygon) PSx

DIST:
6 (polygon) PSx

set
set
set
set

012
012
012
012

012
012
012
012

012
012
012
012

002
002
002
002

012
012
012
012

012
012
012
012

1
2
3
4

116
117
118
119

120
121
122
123

104
105
106
107

097
098
099
126

128
129
130
131

160
161
162
163

45Z8069A

Fig. 3-123: Setting impedance zones 2 to 6 (showing the example of zone 2) and distance measurement.

In addition to the settings described above, the kze zone extension factors for
high-speed reclosure (HSR) and time-delay reclosure (TDR) can also be set
separately for phase-to-ground (PG) and phase-to-phase (PP) loops for
impedance zone 1.
As a result of these settings, impedance zone 1 is extended accordingly in the R
and X directions. The R and X values modified by the kze zone extension factor
are calculated according to the following equations:
R1,kze = kzeR1
X1,kze = kzeX1

3-168

P437/EN M/R-11-A // P437311650

P437

3 Operation

The increase in reach by zone extension factor kze HSR is controlled by the
following:

Protective signaling (PSIG: Z1 exten de d)

Internal auto-reclosing control, if protective signaling is not ready or


irrespective of the readiness of protective signaling during the reclose
command.

Switch on to fault protection (SOTF: Z1 exte nded)

An external signal (DI ST: Zone e xten sion EXT).

The impedance characteristic is extended by zone extension factor kze TDR if a


time-delay reclosure is carried out by internal auto-reclosing control.
Reactive reach settings Xn,PP and Xn,PG
The reactive component of the distance zones may be set separately for the
phase-tophase (PP) and phase-to-ground (PG) measuring loops.

D IST: X1,PG ( polygon ) PSx

DIST: X 6,PG (polygon ) PSx

DIST: X1,PP (polygon) P Sx

DI ST: X6 ,PP ( polygon) PSx

This feature may be helpful with double-circuit lines without using mutual
compensation. In order to cope with effects of mutual coupling, the zone 1 reach
for faults with grounding can now be set to the smallest possible reactance value
(depending on possible switching states of the parallel circuit), while the phaseto-phase loop measurement is set to a "normal" underreaching reach.
A further application is to selectively block the phase-to-ground measurement in
protection schemes where backup protection for ground fault short circuits is
provided with time-graded directional neutral overcurrent protection elements.
Zone 1 extension already provides various factors for phase-to-phase and phasetoground measuring loops. Further precaution measures are therefore not required
here.

Increased reach settings


The maximum setting values for R and X zone reaches, including the
underimpedance starting zone, are 400 at Inom = 1 A (and 80 at Inom = 5
A). Therefore exceptionally high secondary impedances in backup protection
applications may now be taken into account.
For such especially high reach settings the accuracy of an impedance
measurement will naturally be limited because of the then very low short circuit
currents available, so that the user will have to abide with tolerance deviations in
the order of 10%.

P437/EN M/R-11-A // P437311650

3-169

P437

3 Operation

DIST:
Zone extension TDR
[ 038 022 ]

PSIG:
Ready
[ 037 027 ]
ARC:
Zone extension TDR
303 000

ARC:
Zone extension HSR
303 001

DIST:
Zone extension HSR
[ 036 103 ]

ARC:
Meas.r.extd. ext.ARC
303 025

PSIG:
Z1 extended
[ 035 075 ]
ARC:
Zone extension RC

DIST:
X1,PG (polygon) PSx
[ * ]

DIST:
Zone extension
[ 036 065 ]

DIST:
X1,PP (polygon) PSx
[ * ]

303 002

SOTF:
Z1 extended
[ 035 076 ]
DIST:
Zone extension EXT
[ 036 046 ]

DIST:
1 (polygon) PSx
[ * ]

DIST:
Zone ext. HSR 1pG
[ 039 029 ]

DIST:

303 552

DIST:
1 (polygon) PSx
[ * ]
DIST:
kze,PG TDR PSx
[ * ]

DIST:
Select.meas.loop P-G

DIST:
kze,PP TDR PSx
[ * ]

303 543

DIST:
Select.meas.loop P-P

DIST:
kze,PG HSR PSx
[ * ]

303 544

DIST:
kze,PP HSR PSx
[ * ]
DIST:
R1,PG (polygon) PSx
[ * ]
DIST:
R1,PP (polygon) PSx
[ * ]
DIST:
Z

R1,ref1 =

303 553

R1,ref1 RF

f(R1, 1, 1, Z)

DIST:
Dist.decision Z1, x

X1,ref1 =

303 629

X1,ref1 XF

f(X1, 1, 1, Z)
R1,ref2 =

R1,ref2 RF

f(R1,1,1,Z,kze)

DIST:
Dist.decision Z1ze,x

X1,ref2 =

303 630

X1,ref2 XF

f(X1,1,1,Z,kze)
DIST:
RF

DIST:
Dist.decis.Z1 stored

S1 1
R1

303 554

303 565

DIST:
XF
303 555

MAIN:
General starting
[ 036 000 ]
ASC:
Gen. close request

x: A-N, B-N, C-N,


A-B, B-C, C-A

306 012

* Parameter
set 1
set 2
set 3
set 4
* Parameter
set 1
set 2
set 3
set 4

DIST:
X1,PG (polygon) PSx

DIST:
X1,PP (polygon) PSx

DIST:
1 (polygon) PSx

DIST:
kze,PG HSR PSx

DIST:
kze,PP HSR PSx

DIST:
R1,PG (polygon) PSx

012 001
012 051
013 001
013 051

002 076
002 077
002 078
002 079

012 013
012 063
013 013
013 063

012 034
012 084
013 034
013 084

012 035
012 085
013 035
013 085

012 005
012 055
013 005
013 055

DIST:
R1,PP (polygon) PSx

DIST:
kze,PG TDR PSx

DIST:
kze,PP TDR PSx

DIST:
1 (polygon) PSx

012 006
012 056
013 006
013 056

012 046
012 096
013 046
013 096

012 047
012 097
013 047
013 097

072 086
073 086
074 086
075 086

47Z1457A

Fig. 3-124: Setting impedance Zone 1 and distance measurement.

3.21.3.5.4

Distance Decision for 2pG-Faults


To provide correct operation for cross-country faults or inter-system faults on
double circuit lines (2pGG faults), it is mandatory to evaluate only the both
phase-ground loop impedances. This is possible by setting, yet during tests this
setting resulted in staggered tripping for very close 2pG faults, because one PG
loop impedance could appear in backward direction. The reason for this is that

3-170

P437/EN M/R-11-A // P437311650

P437

3 Operation

the impedance is calculated by using the ground factor kG of the line, yet as no
line impedance is involved in the measuring loop any more and as the source
ground factor was significantly smaller than the line factor, thus one PG loop
impedance is misleading.
Therefore the following solution is implemented:
If starting identifies a 2pG fault condition, and PG loops evaluation is selected,
than the phase-phase voltage is used to determine whether it is a close fault,
which is the case for VPP < 10%Vnom. In this case, the PG-loop impedances (for
the distance and directional measurement) are calculated with kG = 0; otherwise
normal equation with set kG is used.
Additionally to the 2 PG impedances the PP impedance is calculated, too, to
secure simultaneous 3-pole tripping, because it could happen that the 2 PG
impedances settle in zone 1 (or Z1e) with different speed just depending on
the fault transients. Always all 3 impedances (e.g. BN, CN and BC for a BCN fault)
are calculated, and the zone decisions are then compared:
1.

If both PG impedances are in zone 1, P437 immediately trips 3-pole.

2.

If one PG and the PP impedance are in zone 1 and the 2nd PG loop is in
forward direction, then P437 trips 3-pole, too.
Taking care for the directional decision acertains, that just in case of
cross-country and intersystem faults (2pGG faults) both PG faults are on
the protected line. The zone 1 decision of the PP loop then is sufficient to
secure that both faults are in zone 1, too.
In applications with parallel lines, during intersystem faults one PG fault
could be on the parallel line, but then either its direction is backwards or
the PP loop impedance is outside zone 1.

3.

If after the first calculation loop just one zone 1 decision is determined,
than the DIST processing task duration is prolonged and all 3 impedances
are calculated again.
This is done to make shure that normal 2pG faults are immediately
tripped 3-pole and the risk of staggered tripping is minimized.
The disadvantage is that for parallel line applications in case of crosscountry/intersystem faults the correct 1pole trip could be delayed by up to
~7 ms.
So in order to get a proper balance of speed and correct 1p/3p trip
decision, this measuring repitition is only done once.

3.21.3.5.5

1pG Starting During 2pG Faults


In some cases a fast 1pG starting was observed during a 2pG fault. This
incomplete fault type determination also forced an initial 1-pole trip. During the
2nd processing cycle the correct type of fault was identified and 3-pole trip was
issued, thus an unfortunate staggered tripping took place.
To solve this problem, the starting conditions are now checked again during the
first distance measuring cycle.

3.21.3.5.6

Settable Directional Characteristic


In some cases with external phase-phase faults with a high intermediate infeed
at the remote busbar, the apparent directional angle (calculated from memorised
voltage and fault current) appeared at about 40 70, i.e. close to the
directional line, sometimes even in the forward section. This resulted from a
severe phase shift of VAB voltage upon fault inception.

P437/EN M/R-11-A // P437311650

3-171

P437

3 Operation

The solution implemented for this condition is a settable directional characteristic


angle as figure below.

45

Setting

DIST:
Directional char PSx
[ * ]
R

* Parameter
set 1
set 2
set 3
set 4

DIST:
Directional char PSx
002 234
002 235
002 236
002 237

47Z1201A

Fig. 3-125: Settable distance directional characteristic.

3.21.4

Impedance-Time Characteristics
A maximum of six impedance zones and eight timer stages are available for
impedance time grading. All impedance zones can be operated in a forward
direction, backward (reverse) direction, or non-directionally. Distanceindependent timer stage t7 can also operate forward-directionally, backwarddirectionally, or non-directionally. Timer stage t8 operates independently of
distance and direction. All zone timer stages are triggered by the general starting
of distance protection if an appropriate setting has been selected at
DIST : Mode t im e r start (otherwise see Separate Zone Timer Start below).

3.21.4.1

Timer Stage Logic for Extended Zone 1


The measuring range of zone 1 can be extended by the set zone extension
factors. The timer stage logic for the device is described below.
If neither protective signaling nor auto-reclosing control (ARC) is active or if zone
extension proceeds while the ARC close command is present, then tripping in the
extended zone takes place once the set time (DIST: t1,ze PSx) has elapsed. If
protective signaling is ready, there is a trip in the extended zone after the
protective signaling tripping time has elapsed.
If protective signaling is not ready but ARC is active, then the following occurs in
the 1-/3-pole, 3-pole and 3-pole (only for 1p) ARC modes: in extended zone 1 a
trip is issued once the ARC tripping time has elapsed, whereas with standard
reach (non-extended zone) it is issued after timer stage t1 of distance protection

3-172

P437/EN M/R-11-A // P437311650

P437

3 Operation

has elapsed or after the HSR tripping time of ARC has elapsed. (The shortest time
setting is effective.)
In the 1-pole ARC mode, a three-pole trip occurs in zone 1 after t1 has elapsed
and in extended zone 1 after timer stage t1,ze of distance protection has elapsed.
A single-pole trip is issued in extended zone 1 once the ARC tripping time has
elapsed, whereas with standard reach (non-extended zone) it is issued after
timer stage t1 of distance protection has elapsed or after the HSR tripping time
of ARC has elapsed. (The shortest time setting is effective.)
Separate Zone Timer Start
If at DI ST: Mode t ime r s tart the mode with zone starting has been selected,
then only the timer stage of the specific distance protection zone Zn is triggered
for which the measured loop impedance is inside the zone.
The trigger is issued by the respective signal DI ST: Zone 1 s tart ing (or
DI ST: Z one 2 startin g, D IST: Zone 8 s tar tin g, resp.)
These signals are only supported if the mode with zone starting has been
selected, otherwise as is mandatory in IEC 61850 modeling all zone startings
are still visible, but will have no influence on the functional sequence.
Compensation of Starting Time
The P437 automatically subtracts starting time from grading time.

P437/EN M/R-11-A // P437311650

3-173

P437

3 Operation

ARC:
Zone extension RC

DIST:
t1 PSx

303 002

DIST:
Zone extension HSR
[ 036 103 ]
C
DIST:
Zone extension TDR
[ 038 022 ]

DIST:
General starting
[ 036 240 ]

&

DIST:
t1,ze PSx
*

t1

t1,ze

DIST:
t1 elapsed
[ 036 026 ]
DIST:
t1,ze elapsed
[ 035 079 ]

DIST:
Mode timer start
[ 001 236 ]
0
1
0: With DIST gen.start.
1: With zone starting

&
DIST:
Zone 1 starting
[ 001 094 ]

&

DIST:
Zone 1,ze starting
[ 002 067 ]
ARC:
HSR oper. mode PSx
[ * ]
1: 1-pole
2: 1-/3-pole
3: 3-pole
4: 3-pole (only for 1p)
DIST:
Zone extension HSR
[ 036 103 ]
DIST:
Timer st. 1 elapsed

DIST:
Zone extension TDR
[ 038 022 ]

303 614

&

ARC:
Trip time elapsed

&

303 003

MAIN:
Trip signal 1, 1p
[ 037 252 ]

&
&
&
PSIG:
Trip time elapsed
305 150

SOTF:
Trip time elapsed
460 528

Parameter

ARC:
HSR oper. mode PSx

DIST:
t1 PSx

DIST:
t1,ze PSx

set
set
set
set

015
024
024
023

012
012
013
013

026
027
028
029

1
2
3
4

051
025
085
045

028
078
028
078

025
025
025
025

47Z8033

Fig. 3-126: Timer stage logic for impedance zone 1.

3-174

P437/EN M/R-11-A // P437311650

P437

3 Operation

DIST:
General starting
[ 036 240 ]

&

DIST:
t2 PSx
[ * ]

DIST:
Mode timer start
[ 001 236 ]

DIST:
t2 elapsed
[ 036 027 ]

1
0
1
0: With DIST gen.start.
1: With zone starting

DIST:
t3 PSx
[ * ]

&

DIST:
Zone 2 starting
[ 001 095 ]

DIST:
t3 elapsed
[ 036 028 ]

&

DIST:
t4 PSx
[ * ]

DIST:
Zone 3 starting
[ 001 096 ]

DIST:
t4 elapsed
[ 036 029 ]

1
&
DIST:
Zone 4 starting
[ 001 097 ]

DIST:
t5 PSx
[ * ]
0

DIST:
t5 elapsed
[ 036 030 ]

1
&
DIST:
Zone 5 starting
[ 001 098 ]

DIST:
t6 PSx
[ * ]

DIST:
t6 elapsed
[ 036 031 ]

1
&
DIST:
Zone 6 starting
[ 001 099 ]

DIST:
t7 PSx
[ * ]

DIST:
t7 elapsed
[ 037 127 ]

1
&
DIST:
Zone 7 starting
[ 001 100 ]

DIST:
t8 PSx
[ * ]

DIST:
t8 elapsed
[ 037 128 ]

1
&
DIST:
Zone 8 starting
[ 001 101 ]

* Parameter
set
set
set
set

1
2
3
4

* Parameter
set
set
set
set

DIST:
t2 PSx

DIST:
t3 PSx
012
012
013
013

029
079
029
079

012
012
013
013

032
082
032
082

DIST:
t5 PSx

1
2
3
4

DIST:
t4 PSx
012
012
013
013

030
080
030
080

012
012
013
013

033
083
033
083

DIST:
t6 PSx

012
012
013
013

031
081
031
081

012
012
012
012

140
141
142
143

DIST:
t7 PSx

DIST:
t8 PSx
012
012
012
012

144
145
146
147

47Z1154A

Fig. 3-127: Time settings for timer stages 2 to 8.

P437/EN M/R-11-A // P437311650

3-175

P437

3 Operation

DIST:
Fault forwd. / LS, A

DIST:
N1,fw

[ 038 010 ]

303 572

DIST:
Fault forwd. / LS, B
[ 038 012 ]

DIST:
N1,bw

DIST:
Fault forwd. / LS, C

303 571

[ 038 014 ]
DIST:
N1,fw, A

DIST:
Fault backwd / BS, A

303 631

[ 038 011 ]
DIST:
Fault backwd / BS, B
[ 038 013 ]
DIST:
Fault backwd / BS, C
[ 038 015 ]

DIST:
N1,fw, B

DIST:
Direction N1 PSx
[ * ]
Parameter

DIST:
Direction N1 PSx

set 1
set 2
set 3
set 4

012 023
012 073
013 023
013 073

303 632

DIST:
N1,fw, C
1
2
3

DIST:
Direction N2 PSx

set 1
set 2
set 3
set 4

012 024
012 074
013 024
013 074

303 635

303 636

DIST:
N2,fw
1
2

DIST:
Direction N3 PSx

set 1
set 2
set 3
set 4

012 025
012 075
013 025
013 075

set 1
set 2
set 3
set 4

1
2

set 1
set 2
set 3
set 4

DIST:
Direction N4 PSx

DIST:
Direction N7 PSx

set 1
set 2
set 3
set 4

012 136
012 137
012 138
012 139

303 579

DIST:
N6,fw
1
2

303 616

DIST:
N6,bw

303 615

DIST:
Direction N7 PSx
[ * ]
Parameter

303 580

DIST:
N5,bw

DIST:
Direction N6 PSx
[ * ]

012 132
012 133
012 134
012 135

303 577

DIST:
N5,fw
1

012 027
012 077
013 027
013 077

set 1
set 2
set 3
set 4

303 578

DIST:
N4,bw

DIST:
Direction N5 PSx

DIST:
Direction N6 PSx

303 575

DIST:
N4,fw
1

012 026
012 076
013 026
013 076

Parameter

303 576

DIST:
N3,bw

DIST:
Direction N5 PSx
[ * ]
Parameter

303 573

DIST:
N3,fw

DIST:
Direction N4 PSx
[ * ]
Parameter

303 574

DIST:
N2,bw

DIST:
Direction N3 PSx
[ * ]
Parameter

303 634

DIST:
N1,bw, B

DIST:
N1,bw, C

DIST:
Direction N2 PSx
[ * ]
Parameter

303 633

DIST:
N1,bw, A

DIST:
N7,fw
1
2

303 618

DIST:
N7,bw

303 617

3
1: Forward directional
2: Backward directional
3: Non-directional

47Z0173A

Fig. 3-128: Directional settings.

3.21.5

Distance Protection Trip Signals


A trip signal is issued for each measuring loop in zones 1 to 6 if the following
criteria are satisfied simultaneously:

3-176

P437/EN M/R-11-A // P437311650

P437

3 Operation

A distance decision exists for the zone.

The timer stage of this impedance zone has elapsed.

The measured direction agrees with the directional setting of this


impedance zone.

If several timer stages and directions are set to the same values, a distance trip
occurs in the zone having the highest number.
A trip signal is issued in zone 7 if the following conditions are satisfied
simultaneously:

Timer stage t7 has elapsed.

The measured direction agrees with the directional setting for N7.

After timer stage t8 has elapsed, a trip signal for zone 8 is issued.
Trip signals from all zones may be blocked individually by the power swing
blocking function (P SB: Blocki ng in iti ated, see Section 3.26, (p. 3-212))
DIST:
Dist. decis. Z1, A-G
303 637

DIST:
Dist. decis. Z1, B-G
303 638

DIST:
Dist. decis. Z1, C-G
303 639

DIST:
Dist. decision Z1, A
303 649

DIST:
Dist. decision Z1, B
303 650

DIST:
Dist. decision Z1, C
303 651

DIST:
Dist. decis. Z1, A-B
303 640

DIST:
Dist. decis. Z1, B-C
303 641

DIST:
Dist. decis. Z1, C-A
303 642

DIST:
Dist. dec. Z1ze, A-G
303 643

DIST:
Dist. dec. Z1ze, B-G
303 644

DIST:
Dist. dec. Z1ze, C-G
303 645

DIST:
Dist. decis. Z1ze, A
303 652

DIST:
Dist. decis. Z1ze, B
303 653

DIST:
Dist. decis. Z1ze, C
303 654

DIST:
Dist. dec. Z1ze, A-B
303 646

DIST:
Dist. dec. Z1ze, B-C
303 647

DIST:
Dist. dec. Z1ze, C-A
303 648

47Z0183A

Fig. 3-129: Linking of loop-selective distance decisions for impedance zone 1.

P437/EN M/R-11-A // P437311650

3-177

P437

PSB:
Block. sel. zone

3 Operation

304 862

DIST:
Blocking Z1 EXT
[ 036 034 ]
DIST:
Blocking Z1,ze EXT
[ 036 036 ]
DIST:
Dist. decision Z1, A
303 649
DIST:
Timer st. 1 elapsed
303 614
DIST:
N1,fw, A
303 631

DIST:
N1,bw, A
303 634

DIST:
Dist. decision Z1, B

S11

11

S21

21

R60,80,100,120,140,160,180
S12

DIST:
N1,bw, B

303 632

12

22
DIST:
Trip zone 1, C

S13

DIST:
N1,bw, C

303 633

DIST:
Dist. decis. Z1ze, A
DIST:
t1,ze elapsed
[ 035 079 ]

23

303 652

S31

303 657

DIST:
Trip zone 1

R60,80,100,120,140,160,180
31

303 584

DIST:
Trip signal zone 1
[ 035 072 ]
DIST:
Trip zone 1,ze, A
303 658

R50,70,90,110,130,150,170
S41

DIST:
Dist. decis. Z1ze, B

13

R50,70,90,110,130,150,170
S23

303 636

303 656

R60,80,100,120,140,160,180

303 651

DIST:
N1,fw, C

DIST:
Trip zone 1, B

R50,70,90,110,130,150,170
S22

303 635

DIST:
Dist. decision Z1, C

303 655

R50,70,90,110,130,150,170

303 650

DIST:
N1,fw, B

DIST:
Trip zone 1, A

41

R60,80,100,120,140,160,180
303 653

S32

32

DIST:
Trip zone 1,ze, B
303 659

R50,70,90,110,130,150,170
S42
DIST:
Dist. decis. Z1ze, C

42

R60,80,100,120,140,160,180
303 654

S33

33

R50,70,90,110,130,150,170
S43
R60,80,100,120,140,160,180
DIST:
General starting
[ 036 240 ]

DIST:
Trip zone 1,ze, C
303 660

DIST:
Trip zone 1,ze
43

303 595

DIST:
Trip signal Z1,ze
[ 035 074 ]

47Z8058A

Fig. 3-130: Distance protection trip signals in zone 1.

3-178

P437/EN M/R-11-A // P437311650

P437

3 Operation

PSB:
Block. sel. zone

304 862

DIST:
Blocking Z2 EXT
[ 036 037 ]
DIST:
Blocking Z3 EXT
[ 036 039 ]
DIST:
Blocking Z4 EXT
[ 036 041 ]
DIST:
Blocking Z5 EXT
[ 036 044 ]
DIST:
Blocking Z6 EXT
[ 036 061 ]
DIST:
Blocking Z7 EXT
[ 036 067 ]
DIST:
Blocking Z8 EXT
[ 036 068 ]
DIST:
Dist.decision zone 2
DIST:
t2 elapsed
[ 036 027 ]
DIST:
N2,fw

S50

DIST:
N3,bw

50

R1x,3x,70,90,110,130,150,170
303 574

DIST:
N2,bw
303 573
DIST:
Dist.decision zone 3
DIST:
t3 elapsed
[ 036 028 ]
DIST:
N3,fw

DIST:
Trip zone 2

303 581

S60

60

R2x,4x,80,100,120,140,160,180

DIST:
Trip zone 3

303 582

S70

70

R1x,3x,50,90,110,130,150,170
303 576

S80

303 575

R2x,4x,60,100,120,140,160,180

DIST:
Dist.decision zone 4
DIST:
303 583
t4 elapsed
[ 036 029 ]
DIST:
N4,fw

S90

90

R1x,3x,50,70,110,130,150,170
S100

303 577

DIST:
Dist.decision zone 5303 619
DIST:
t5 elapsed
[ 036 030 ]

DIST:
N5,bw

DIST:
Dist.decision zone 6
303 620
DIST:
t6 elapsed
[ 036 031 ]
DIST:
N6,fw
303 616

DIST:
N6,bw
DIST:
t7 elapsed
[ 037 127 ]
DIST:
N7,fw
DIST:
N7,bw

303 615

S140

303 617

S160

150

DIST:
General starting
[ 036 240 ]

160

R2x,4x,60,80,100,120,140,180
S170

DIST:
Fault forward / LS
[ 036 018 ]
DIST:
Fault backward / BS
[ 036 019 ]

303 621

DIST:
Trip signal zone 6
[ 040 059 ]

DIST:
Trip zone 7
303 622

DIST:
Trip signal zone 7
[ 037 129 ]

DIST:
Trip zone 8
170

R1x,3x,50,70,90,110,130,150
S180

303 588

DIST:
Trip signal zone 5
[ 040 058 ]

140

R2x,4x,60,80,100,120,160,180

R1x,3x,50,70,90,110,130,170
303 618

303 587

DIST:
Trip signal zone 4
[ 040 057 ]

DIST:
Trip zone 6
130

R1x,3x,50,70,90,110,150,170

S150

DIST:
t8 elapsed
[ 037 128 ]

DIST:
Trip signal Z1, A
DIST:
Trip signal Z1, B
DIST:
Trip signal Z1, C

120

R2x,4x,60,80,100,140,160,180
S130

DIST:
Trip zone 4

DIST:
Trip zone 5
110

R1x,3x,50,70,90,130,150,170
S120

303 579

100

R2x,4x,60,80,120,140,160,180
S110

303 586

DIST:
Trip signal zone 3
[ 040 056 ]

80

303 578

DIST:
N4,bw

303 585

DIST:
Trip signal zone 2
[ 041 084 ]

180

R2x,4x,60,80,100,120,140,160

303 626

DIST:
Trip signal zone 8
[ 037 130 ]
DIST:
Trip sig. zone 2-8
[ 035 073 ]

303 623

DIST:
Trip signal
[ 036 009 ]

303 624
303 625

47Z8059A

Fig. 3-131: Distance protection trip signals in zones 2 to 8.

P437/EN M/R-11-A // P437311650

3-179

P437

3 Operation

t8

t8

t7

t7

t6

t6

t5

t5

t4

t4

t3

t3
t2

t2
t1
t1 = 0 s
Z1

Z2

Z3

Z4

Z5

Z6

Z2

Z1

Z1

Z3

Z4

Z5

Z6

Z3

Z4

Z5

Z6

t8

t8
t7

t6, t7

t6

t5

t5

t4

t4

t3

t3

t2

t2

t1 = 0 s

t1 = 0 s
Z1

Z2

Z3

Z4

Z5

Z6

Z6

Z5

Z4

Z3

Z2

t8

t8
t7

t6

t6

t5

t5

t4
t7

t4
t3

t3
t2

t2

t1 = 0 s

t1 = 0 s
Z5

Z3

Z1

Z1

Z1

Z2

Z4

Z6

Z1

Z1

Z2

47Z0176A

Fig. 3-132: Example of a feasible impedance-time characteristic.

For special applications (such as the application of the impedance dependent


blocking scheme see function group PSIG), the P437 generates the signal
DIS T: I mp ed ance in zon e 6, if the following conditions are satisfied
simultaneously:
3-180

P437/EN M/R-11-A // P437311650

P437

3 Operation

A distance decision exists for zone 6.

The measured direction agrees with the directional setting of zone 6.

DIST:
Impedance in zone 6
[ 037 200 ]

DIST:
Dist.decision zone 6
303 620

DIST:
N6,fw
303 616

DIST:
N6,bw
303 615

47Z0185A

Fig. 3-133: Signal D I S T : I m p e d a n c e i n z o n e 6.

3.21.6

Selection of Trip Mode for Zone 1


For zone 1(including the extended zone) the user can specify whether the
distance trip in zone 1 shall be single-pole or three-pole. This choice is separately
available both for single-pole ground faults (1pN) and two-phase ungrounded
faults (2p).
In the case of a two-phase ungrounded fault, the P437 checks if there is a ground
fault detection signal. If this is the case, there is a three-pole trip transfer. If
there is no ground fault detection signal and if a single-pole trip for a two-phase
ungrounded fault has been selected , then a trip decision is issued in the leading
or trailing phase, depending on the setting. This is based on the setting at
MAI N: Pha se se que nce. A three-pole trip can be forced via an appropriately
configured binary signal input.
If the P437 carries out a single-pole trip when a two-phase ungrounded fault has
occurred, then a fault change is ignored for 100 ms if a trip decision is reached in
the phase, which has not been cleared. This takes differing fault clearing time
periods at both line ends into account that lead to a transient ground starting. If,
after a fault change, a trip decision is reached in the third phase, which was not
involved previously, then a three-pole transfer occurs instantaneously.

P437/EN M/R-11-A // P437311650

3-181

P437

3 Operation

ARC:
Zone extension RC
303 002

SOTF:
Z1 extended
[ 035 076 ]

DIST:
Trip zone 1 PG PSx

DIST:
Zone extension EXT
[ 036 046 ]

PSIG:
Not
[ 037ready
028 ]

3: 3-pole

1: 1-pole

PSIG:
Trip enable
305 157

PSIG:
Trip enable, ch. 1
305 166

DIST:
Trip signal Z1, A

PSIG:
Trip enable, ch. 2

303 623

305 167

DIST:
Trip signal Z1, B

PSIG:
Trip enable, ch. 3

303 624

305 168

DIST:
Trip zone 1, A
303 655

DIST:
Trip zone 1,ze, A

DIST:
Trip signal Z1, C

303 658

DIST:
Trip zone 1, B

303 625

303 656

DIST:
Trip zone 1,ze, B

S1 1

303 659

DIST:
Trip zone 1, C

DIST:
Signal block start.G

R1

303 657

303 594

S1 1

DIST:
Trip zone 1,ze, C

R1

303 660

S1 1
R1
DIST:
General starting
[036 240 ]

1
100ms

DIST:
Starting N1
303 535

DIST:
Trip zone 1 PP PSx
[

MAIN:
Phase sequence
[ 010 049 ]

3: 3-pole

1: 1-pole leading phase

1
2

2: 1-pole trailing phas

2: A - C - B
1: A - B - C
MAIN:
Blocking 1p trip EXT
[ 041 078 ]

* Parameter
set 1
set 2
set 3
set 4

DIST:
Trip zone 1 PG PSx

DIST:
Trip zone 1 PP PSx

011 050
011 051
011 052
011 053

011 054
011 055
011 056
011 057

47Z1164A

Fig. 3-134: Selection of zone 1 trip mode.

3-182

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.22

Power Swing Blocking (Function Group PSB)


The power swing blocking (PSB) function offers these options should a power
swing occur in the power system:

The user can block distance trip signals in selected distance zones by
PSB: Fct . assi gn. block.. These zones may be selected for blocking: Zx
(x=1 to 8) and Z1,ze. This will prevent unwanted tripping by apparent low
impedances during a power swing.

Moreover, PSB: Fct. ass ign . bl ock. allows for blocking undervoltage
stages of function group V<>.

A trip signal can be generated so as to end a power swing, by initiation of


system splitting (or islanding).

Disabling or Enabling Power Swing Blocking


The power swing blocking function can be disabled or enabled individually in
each parameter subset via the setting parameter PSB: En able PSx.
When the monitoring of the voltage-measuring circuit is triggered the PSB
function will be blocked.

PSB:
General enable USER
[ 014 050 ]

0
1
0: No
1: Yes

PSB:
Enable PSx
[ * ]
PSB:
Enabled
[ 040 095 ]

0
1
0: No

PSB:
Ready

1: Yes
* Parameter

MAIN:
Protection active
306 001

set
set
set
set

MCMON:
Meas. circ. V faulty
[ 038 023 ]

1
2
3
4

304 859

PSB:
Enable PSx
015
015
015
015

090
091
092
093

47Z11CBB

Fig. 3-135: Disabling or enabling power swing blocking.

3.22.1

Measurement
The P437 continuously measures the positive-sequence impedance. Because of
this measurement in the positive-sequence system, the protection is also
available during a single-pole HSR.
Blocking of selected zones of the distance protection or a power swing starting
occurs only when the measured positive-sequence impedance lies within the
settable power swing polygon.

P437/EN M/R-11-A // P437311650

3-183

P437

3 Operation

PSB:
R
[ 014 060 ]
PSB:
posX
[ 014 061 ]
PSB:
negX
[ 006 185 ]
PSB:

PSB:
Asyn. power swing

[ 014 062 ]

304 860

VA-G
VB-G

Vpos

VC-G
PSB:
Z within polygon

Zpos

IA

[ 036 024 ]

Ipos

IB
IC

45Z80CCA

Fig. 3-136: Measurement.

The diagram shows: Typical trajectory of a stable power swing; typical


trajectory of an instable power swing.

PSB:
posX

Zpos(t)

PSB:

PSB:
R

PSB:
negX
47Z13CFA

Fig. 3-137: Trajectory of the positive-sequence impedance during a power swing.

3.22.2

Power Swing Detection


Power swing detection is based on impedance variation (Delta Z).
The rate of change of the resistance component of positive-sequence impedance
Rpos, when entering the power swing polygon, is measured and interpreted. The
function decides on power swing only if the rate of change is smaller than the
set threshold Rx/T and subsequently blocks all selected zones.
The threshold Rx has a fixed value:

Rx = 5 for Inom = 1 A

Rx = 1 for Inom = 5 A.

Timer stage T can be set at P SB: Ope r. valu e Delta T.


3-184

P437/EN M/R-11-A // P437311650

P437

3 Operation

A power swing decision once made is stored until one of the following conditions
is met:

The positive-sequence impedance locus exits the power swing polygon.

The expected maximum power swing duration (PSB: Max. PS cycle


dur.) has elapsed.

One of the PSB current stages has started.

Furthermore, several timer stages are triggered by a power swing decision,


which lead to a blocking signal (P SB: Bl ocked). This blocking signals resets the
blocking of the distance zones and undervoltage stages that have been selected
via PSB: Fct. assign. block.. (All other PSB functionality is not affected by
PSB: Blocked.) The details are described in the following section.
MiCOM P437 operates task oriented. The PSB task is processed approximately
every 15 ms. The internal Rx threshold value will be adapted according to the
measured actual time delay between 2 consecutive measurements. With each
processing step, the impedance Zpos is determined and stored. Thus Rpos is
calculated from 2 consecutive processing steps:
Rpos = Rpos(n) - Rpos(n-1),
Where:

Rmit(n): the first measurement inside the power swing detection


polygon

Rmit(n-1): the previous measurement outside the power swing


detection polygon

R stab. = [ 014 060 ]PSB:


R

= [ 014 061 ]PSB:


posX

= [ 006 185 ]PSB:


negX

= [ 014 090 ]PSB:


Oper. value Delta T

= [ 014 062 ]PSB:

Zpos(t)
PSP:
Rx
T

R stab.

47Z1352A

Fig. 3-138: Power swing detection zone.

3.22.3

Load Blinding
In the case of parallel lines (i.e. double-circuit lines) with a high rate of power
transmission to neighboring networks the failure of one three-phase system may
lead to a short-time (typically 20 to 30 minutes) increase in the power flow rate
on the remaining line. Here the positive-sequence impedance locus will then lie

P437/EN M/R-11-A // P437311650

3-185

P437

3 Operation

within the load blinding area of the distance protection starting characteristic.
This is displayed in the figure below, with the following fault sequence:
1.

Operation under load conditions (blue area, 2 operational systems).

2.

Fault on the parallel line will lead to a selective disconnection of this


parallel line.

3.

Operation under overload conditions on the remaining system (red area,


1 faulted system).

4.

Start of a power swing due to instable network conditions.

150

Power swing polygon


Starting characteristic

100

50

50

50

100

50
Load area

Load area

1 faulted system

2 operational systems
47Z2000A

Fig. 3-139: Impedance trajectory with a fault in one three-phase system.

It is therefore not possible to selectively set the power swing polygon where:

3-186

P437/EN M/R-11-A // P437311650

P437

3 Operation

The setting for the resistance reach Rfwd of the starting polygon is such that
the impedance locus could possibly not leave the power swing polygon
after the initial short-circuit fault has been cleared, and therefore power
swing blocking cannot be enabled when a power swing occurs.
It is also possible that because of load variations the impedance locus will
leave the power swing polygon for a short-time and then return, which
could cause power swing blocking to be enabled erroneously (resulting in a
protection malfunction if a chance short-circuit fault should then occur).

The setting for the starting impedance in the load area Zfwd (minimum load
impedance) is such that power swing blocking may occur too late if a power
swing has started in the normal blue area and then crosses the starting
characteristic in the power swing polygon area (above the angle ).

To cope with this problem a load blinding feature is now available for the power
swing polygon:
The time for a measurement sample to be taken to determine the speed of
resistance change may be set at P SB: A ctivation con d. dZ (with two
selection options Power Swing polygon and PS-polygon + 3pStart):
With the Power Swing polygon setting (entry into the power swing polygon),
the function will operate as before, i.e. when the positive-sequence impedance
locus enters the power swing polygon, the speed of change of the positivesequence impedances real component is measured and evaluated.
With the PS-polygon + 3pStart setting (power swing polygon + 3-phase start),
the speed of change of the positive-sequence impedances real component is
measured under these conditions only:
[The updated positive-sequence impedance locus determined lies within the
power swing polygon]
AND([A 3-phase - without ground - start has occurred]
OR([A 2-phase - without ground - start has occurred]
AND["The negative-sequence current value is sufficiently
small"]))
The result is that the state positive-sequence impedance locus in the power
swing polygon will now also be a simple enabling condition for the Z method.
In this case whether the positive-sequence impedance is now being measured for
the first time within the power swing polygon or it was already there during a
previous measurement is irrelevant.
Crucial for a measurement decision is the onset of the (distance) general start.
In theory, a 3-phase start (without ground) is to be expected, as power swing
occurrences are symmetrical (i.e. the same measurement conditions are to be
found in all 3 phases).The result is that with the onset of a phase-ground start
there will be no power swing occurence (i.e. when with the onset of a start there
is also a phase-ground start or it is already present, then the blocking effect can
no longer be set).
In practice all currents and voltages will be unbalanced (mainly because of
unbalanced lines, but asymmetrical loads and infeeds, as well as measurement
errors by transformers and even by the protection device itself are also to be
considered) so that possibly one of the three phase-phase starting systems will
trigger first. Therefore, with a high R1 reach for zone 1, the 2-phase start may
have already led to a trip command during a power swing event, even before a
3-phase start has activated power swing blocking. Therefore, in order to also
have control of this state, the power swing blocking function carries out the R
measurement at the onset of the 2-phase start, but only if currents are
P437/EN M/R-11-A // P437311650

3-187

P437

3 Operation

adequately balanced. To ensure this, the negative-sequence current is measured


continuously. With the onset of the first 2-phase start, caused by a power swing
event, the Ineg value must not be significant, i.e. in this case:
Ineg < 0.1Inom + 0.2IP,max
On the other hand, the device will make a (2-phase) short-circuit decision when
the negative-sequence current value exceeds this value.
In order for power swing blocking to become effective in time with such a
selection of sampling times, it will be implemented after the distance protection
start and before the distance zone detection.
This is the preferred approach when looking at a parallel undervoltage start. The
reach of the undervoltage start is basically not definable in the impedance plane
and can therefore not be covered safely by a purely impedance-defined power
swing polygon. Since it is now possible to select the sampling times of power
swing events, the first occurence of the undervoltage condition can be
ascertained in time if the power swing polygon is set to a sufficient size.
Overlapping of the power swing polygon with the area of minimum load
impedance is permitted.
According to the basic Z principle, the decision is taken only once (in this case
with the onset of above mentioned starting conditions). If a power swing event is
detected, power swing blocking is set and stored until the reset condition is met.
The power swing blocking is adapted (extended) when this new acquisition
method is used. The blocking effect is lifted if one of the following conditions is
met:

3.22.4

The general start is terminated (only with the setting PS-polygon +


3pStart), or (as before)

the positive-sequence impedance leaves the power swing polygon, or

(at least) one current trigger (IP>, Ineg>, IN>) is triggered, or

the maximum blocking time has been reached.

Behavior with a Short-Circuit Fault During a Power Swing Event


A short-circuit fault condition may occur during a power swing event. With the Z
operating mode, blocking is lifted because one current trigger (IP>, Ineg>, IN>)
has operated. Until now this would occur instantaneously. As distance
measurement was already active during the blocking the following problems
could be encountered:
1.

The zone-time grading measurement is already running (since the general


start or since the zone entry because of the power swing event). For
example a short-circuit fault has occurred in backup zones: this will then
lead to an instantaneous triggering when power swing blocking is lifted
(which is an overreaction).

2.

When a general starting is present for a length of time the measurement


window of the distance measurement is shifted backwards in time so as to
prevent incorrect decisions at fault clearance (tripping by an upstream
protection device).
If no change in starting occurs when power swing blocking is lifted, (i.e. a
3pole fault is detected) then distance measurement operates, for the
time being, with the previous measured values from the power swing area
which were collected before the short-circuit fault had occurred. Therefore
distance and zone decisions are of no use.

With protection systems where phase-differential protection is applied along with


distance protection, the overreaction as given under item 1. can be avoided if,
after the current short-circuit trigger has operated, blocking of distance
3-188

P437/EN M/R-11-A // P437311650

P437

3 Operation

protection is lifted with a short release delay (100 ms), which will then give
preference to the selective differential protection.
Such a short release delay is of no use with protection systems where two
distance protection devices are used.
For this a new release delay for blocking is available. It is set at PSB: Abort
d elay (in the range from 0.00 s to 1.00 s with the default value = 0.00 s). This
release delay will become active when blocking is lifted because a current trigger
has operated (IP>, Ineg>, IN>). For technical reasons this release delay will also
be activated when the maximum blocking time has elapsed so that, including
this release delay, the set maximum blocking time may be exceeded.

3.22.5

PSB Blocking
The blocking of the distance zones and undervoltage stages that have been
selected via PSB: F ct. as s ign. bl ock.PSB: Fct. assign. block. is reset as soon
as the signal PSB: Blocked is issued.
The following signal flow diagram shows how this PSB blocking signal is set up.

A
B
C

PS condition
[008 234] PSB:
Abort delay

PS condition
reset

PSB:
Blocking initiated
[036 032]

set

reset
set

(re)trig.

reset

set

reset

set

(re)trig.

(re)trig.

(re)trig.

PSB:
Hold time running
[011 142] PSB:
Hold time

[011 142] PSB:


Hold time

(B or C)

D
E
F

trigger

trigger

PSB:
Max.block.time runn.
PSB:
Blocked
[011 144]

[010 179] PSB:


Max. blocking time

trigger

[010 179] PSB:


Max. blocking time

[011 143] PSB:


Blocking time int.
45Z8009

Fig. 3-140: Signal flow diagram for P S B : B l o c k e d.

The signal flow diagram is based on the assumption that PSB is enabled and not
blocked by an external input signal (i.e. by P SB: Blockin g E XT = Yes).

P437/EN M/R-11-A // P437311650

3-189

P437

3 Operation

A: The first line in the signal flow diagram represents the basic relevant
measuring and logic condition that is used to establish the power swing
blocking condition (i.e. Zpos is within the power swing polygon, the PSB
activation condition was fulfilled, and no unblocking condition is present, or
abort delay P SB: Abor t de lay).

B: If PSB is not blocked, the signal P SB: Blocking initiated is issued.


This signal is the condition used to block the selected DIST zones and V<
stages.

C: When the signal P SB: Blocki ng in iti ate d falls back to No, a settable
hold timer is triggered or retriggered. It does not matter, whether the reset
of power swing blocking was caused because Zpos has left the power swing
polygon, or because of any unblocking condition (current triggers or
PS B: Max. PS cycl e du r. elapsed).

D: Signal D is the result of a logical OR operation: B or C.

E: The raising edge of the signal D (i.e. the beginning of a measured power
swing condition) triggers a timer. If this timer reaches the set PSB: Max.
bl ocki ng ti me a further pulse timer (=signal F) is triggered, which is
running for the set time PSB: Bl ocking ti me int..

F: While this pulse timer is elapsing (i.e. during the time interval
PSB: Blocking ti me int.) the signal PSB: Blocked Is issued. It is also
issued along with external blocking of PSB (P SB: Blocking EXT) or with
internal blocking initiated from current trigger operation (PSB: IP >
t riggere d, P SB: In eg> tri gge re d, P SB: IN> trigge red). The blocking
of the distance zones and undervoltage stages that have been selected via
PSB: F ct. assign. bl ock. is reset as soon as this signal (PSB: Block ed)
is issued.
[036 032]
PSB:
Blocking initiated
= Yes

PSB:
Blocking EXT
not active
PSB:
Blocked
ext.
[008 248]
PSB:
Blocking
EXT
=
Yes

PSB:
Blocking EXT
active

(per 012 017 selected


DIST zones and V<> stages
are blocked.)

Normal
[040 095]
PSB:
Enabled
= Yes

Activation condition fulfilled


(basically:
[036 024]
PSB:
Z within polygon = Yes)

Block. time
elapsed
PSB:
Blocking time int.

PSB:
Blocking initiated

De-activation condition fulfilled


(basically [036 024] = No)
Short-circuit condition present (I>, Ineg>, IN> triggered)
max. PS cycle duration elapsed (Tmax elapsed)

PSB:
Hold time
elapsed

[011 144]
PSB:
Blocked

PSB:
Abort delay
running

PSB:
Hold time running

PSB:
Max.block.time runn.

Fig. 3-141: PSB state diagram.

3-190

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.22.6

Out-of-Step Tripping
A power swing starting may become necessary when a power swing with low
damping has to be terminated by deliberately splitting system sections. For such
a procedure the device has three independent methods available:

1st criterion for a safe system split at an instable power swing.


The positive-sequence impedance leaves the power swing polygon on the
opposite side (see impedance trajectory in Fig. 3-137, (p. 3-184)).
The sign for the positive-sequence impedances resistive component is
stored when the measured positive-sequence impedance locus enters the
power swing polygon. This stored sign is compared with the sign when
crossing the R(OOS) boundary (description of R(OOS) below). Should the
signs differ, a trip signal is issued immediately.
When this criterion is applied an instable power swing will be determined,
regardless of swing frequencies.

2nd criterion Enhanced counting-based tripping.


Detailed description follows below.

The trip signal of the 1st criterion is issued as PSB: Trip sign al.
The counting-based trip signals per 2nd criterion are available as individual
signals, described below. They are not linked into this PSB: Trip s ignal, but
could be individually linked into the general trip commands.

3.22.7

Enhanced Counting-Based Trip Logic


The basic considerations could be discussed on a simple (simplified) 2-machine
power system as shown in Fig. 3-142, (p. 3-191). Sources A and B represent
power system equivalents, impedance A-B represents (positive sequence) line
impedance. The distance protection to be discussed is located on the line at end
A.

Source A

Line AB

AS

Source B

BS

DIST

Fig. 3-142: Power system equivalent circuit.

Based on this equivalent circuit, the impedance plot per Fig. 3-143, (p. 3-192)
could be drawn. The origin of the complex plane is put at the location of the
distance protection device, that is at system bus A.
For this simplified description any apparent impedance Z measured from the
distance protection during a steady-state out-of-step condition moves along
circles with its origin in either AS or BS source, depending on the ratio of the
absolute values of the 2 source voltages. The rotation sense further depends on
which source is leading.
P437/EN M/R-11-A // P437311650

3-191

P437

3 Operation

This description of power swings is rather simplified but sufficient to describe the
functionality as implemented in the P437.

BS

B
Z

AS
47Z1351A

Fig. 3-143: Power system equivalent impedances.

The basic power swing detection zone of P437 is of quadrilateral shape. While
resistive reach in forward and backward direction is equal, the reactive reaches
can be set independently to provide coverage adjustable to the power system
impedances (essentially to cover differences in reverse source impedance and
forward line plus remote source impedances).
Power swing detection is done by measuring the rate of change of the resistance
(real part) of the positive sequence impedance. A power swing is detected, if a
resistance change of Rx = 5 (at Inom = 1 A) takes more time than a settable
timer T (see Fig. 3-138, (p. 3-185)).
Inside the power swing detection zone, 2 more lines are defined by a settable
resistance PSB: R (OOS) to determine an out-of-step condition. Thus this
decision could be taken before leaving the power swing detection zone.

3-192

P437/EN M/R-11-A // P437311650

P437

3 Operation
The relay checks that settings are valid:

The resistive lines have to be inside the power swing detection zone:
Rinst.P. Rstab.P
Otherwise the internal R(OOS) variable is limited to the R(PSB) value as per
Fig. 3-145, (p. 3-194) (left-hand part).
The resistive lines must not cross the X-axis.
Otherwise the lines are limited to the X-axis as per Fig. 3-145, (p. 3-194)
(right-hand part).

3.22.7.1

Counters
An out-of-step condition is determined if the apparent positive-sequence
impedance moves along its trajectory from the right side into the power swing
detection zone and then crosses the left side OOS detection line (trajectory in
Fig. 3-144, (p. 3-194) below), or vice versa (trajectory ). In both cases the outof-step counter nOOS is incremented by 1.
If the apparent positive-sequence impedance leaves the power swing detection
zone on the same side as it entered, a stable power swing is determined (e.g.
trajectory ). In this case the power swing counter nPSB is incremented by 1.
By this definition, the counter values are only available during a power swing or
out-of-step condition, respectively. As it is desirable to have the counter values
available for post-mortem analysis, the values are stored as event counters, too.
The following counters are implemented to count unstable and stable swings as
described above:

3.22.7.2

ninst.P.: PS B: No. OOS-Swi ng

nstab.P.: PS B: No. stab. P Sw ing

Counter Reset
During a power swing a dedicated timer stage is triggered upon each
incrementing the counter. If this timer elapses while no further incrementing of
the same counter takes place, then it is assumed that the power swing condition
has stopped and this counter is reset to 0.
For this timer stage the setting PSB: Max. P S cycle dur. is used, which is
recommended to be set to the anticipated maximum power swing cycle time.
The counters are reset automatically with the detection of a new power swing. A
manual reset of the counters, however, can also be done by setting the
parameter PSB: R e se t cou nters to execute.

P437/EN M/R-11-A // P437311650

3-193

P437

3 Operation

R stab. = [ 014 060 ]PSB:


R
R instab. = [ 006 184 ]PSB:
R (OOS)
n instab. = [ 006 026 ]PSB:
No. OOS-Swing
n stab. = [ 006 025 ]PSB:
No. stab. PSwing

BS

n instab.+1
n instab.+1

n stab.+1

Rinstab.

R
+Rinstab.

+Rstab.

AS

47Z1353A

Fig. 3-144: Out-of-step detection and counter incrementing conditions.

Left: Limiting at Rstab, if Rinst > Rstab; right: Limiting X-axis.


R instab. = [ 006 184 PSB:
]
R (OOS)
R stab. = [ 014 060 PSB:
]
R

BS

BS

Rinstab.

Rinstab.
R

+Rinstab.

AS

+Rinstab.

AS

47Z1354A

Fig. 3-145: Automatic limiting for the position of the resistive lines.

3-194

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.22.7.3

Counter Comparators
Out-of-step tripping is raised, if the number of counted out-of-step swings nOOS
reaches a settable limit.
In order to take into account the electrical center of the oscillation, the
impedance area between the OOS detection lines inside the power swing
detection zone is split into 3 areas, divided by 2 settable reactances as per
Fig. 3-146, (p. 3-196). The reactances are set at:

P SB : posX (O OS)

P SB: ne gX (OOS)

The inner main area is used to identify swings with electrical center on the line.
The back-up area is the remaining part of this corridor. Typically the back-up
area counter is set to a higher number of swings to provide only back-up tripping
(system splitting) in case the protection system closest to the electrical center of
the oscillation failed to operate.
As the OOS counter is incremented when the positive-sequence impedance
trajectory crosses the resistive detection lines, the decision which counter limit to
compare with is practically linked to the section on this resistive detection line
rather than the area the impedance moved through.
Fig. 3-146, (p. 3-196) shows 2 cases:

OOS tripping as nOOS reaches nOOS,trp,a.

OOS tripping as nOOS reaches nOOS,trp,b .

In the same way, an additional power swing tripping is raised if the number of
counted power swings nPSB reaches a settable limit nPSB,trp (case ). This feature
may be used as back-up protection, if stable swings persist for too many power
swing cycles.
These counter thresholds are also known as permissible number of unstable or
stable power swings, respectively.

3.22.7.4

ninst,zul,a is set at P SB: Per m. N o. OOS ( a).

ninst,zul,b is set at P SB : Pe rm. No. OOS ( b).

nstab,zul is set at P SB: P e rm . No. stab. P S.

Counting Based Trip Signals


The following individual tripping signals are issued:

P SB: Tri p sign al OOS ( a)

PSB: Trip signal OOS ( b)

PS B: Trip signal stab. PS

These binary signals remain active for a pulse duration of 100 ms.
All out-of-step and power swing trip signals are available in the selection list of
the general trip commands of the relay.

P437/EN M/R-11-A // P437311650

3-195

P437

3 Operation

X instab,= [ 014 060 ]PSB:


R
X instab,= [ 006 184 ]PSB:
R (OOS)
n instab,a = [ 006 028 ]PSB:
Perm. No. OOS (a)
n instab,b = [ 006 189 ]PSB:
Perm. No. OOS (b)
n stab
= [ 006 027 ]PSB:
Perm. No. stab. PS

X instab,

BS
n instab,b

n instab,a

n stab

X instab,

n instab,b

AS
47Z1355A

Fig. 3-146: Out-of-step tripping conditions.

3-196

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.23

Measuring-Circuit Monitoring (Function Group MCMON)


The P437 monitors the phase currents and the voltages for balance during
healthy system operation. If either unbalance or the lack of measuring voltage is
detected, action is taken to prevent the unit from malfunctioning.

Monitoring the Starting Conditions


If ground starting SG is present for more than 10 s without phase starting, the
following monitoring signal is issued: MCMON: Zero-sequ . st artin g
DIST:
General starting
[ 036 240 ]

10s

MCMON:
Zero-sequ. starting
[ 041 080 ]

DIST:
Starting G

SFMON:
Zero-sequ. starting
[ 098 015 ]

303 507

MCMON:
Enabled
[ 040 094 ]

300ms

MAIN:
M.c.b. trip V EXT
[ 004 061 ]

SFMON:
M.c.b. trip V
[ 098 000 ]
MCMON:
Meas. circ. V faulty
[ 038 023 ]

MCMON:
Undervoltage
[ 038 038 ]

SFMON:
Meas. circ. V faulty
[ 098 017 ]

MCMON:
Vneg> triggered
[ 041 079 ]
MCMON:
FF, V triggered
[ 035 081 ]

MCMON:
M.circ. V,Vref flty.
[ 040 078 ]

MCMON:
FF, Vref triggered
[ 038 100 ]

SFMON:
M.circ. V,Vref flty.
[ 098 023 ]

MAIN:
M.c.b. trip Vref EXT
[ 036 086 ]

300ms

SFMON:
M.c.b. trip Vref
[ 098 011 ]
MCMON:
Meas.circ.V,I faulty
[ 037 020 ]
SFMON:
Meas.circ.V,I faulty
[ 098 016 ]

MCMON:
Meas. circ. I faulty
[ 040 087 ]
GFSC:
Monitor. triggered
[ 038 095 ]

MCMON:
Peripheral fault
[ 038 024 ]
PSIG:
Telecom. faulty
[ 036 060 ]

SFMON:
Peripheral fault
[ 098 018 ]

47Z1145B

Fig. 3-147: Monitoring signals.

Measuring-circuit monitoring can be disabled by the appropriate setting. In the


event of a fault, measuring-circuit monitoring is blocked.

3.23.1

Current Monitoring
The current-measuring circuit monitoring function is enabled when the current
exceeds the settable value MC MO N: Imi n cu rr. monit or. in at least one
phase. Once monitoring is enabled, the absolute value of the negative-sequence
component of the current system is determined in accordance with the definition
of the symmetrical components. This is based on the setting at MAI N: Phase
seque nce.

P437/EN M/R-11-A // P437311650

3-197

P437

3 Operation

Phase sequence A-B-C

(Alternative terminology: clockwise rotating field)


1

I neg = 3 | (I A + a 2 I B + a I C) |



Phase sequence A-C-B

(Alternative terminology: anti-clockwise rotating field)

I neg = 3 | (I A + a I B + a 2 I C) |



Symbols used:

a = e2j/3 = e j120

a 2 = e4j/3 = e j240

This value is divided by the maximum phase current |Imax| and compared with
the set threshold operate value. If the set operate value is exceeded, a
monitoring signal is issued once the operate delay + 300 ms have elapsed.

MCMON:
General enable USER
[ 014 001 ]
0
MCMON:
Enabled
[ 040 094 ]

1
0: No
1: Yes

MCMON:
Current monitoring
[ 014 006 ]
0
1
0: No
1: Yes
MAIN:
General starting
[ 036 000 ]
MCMON:
Imin curr. monitor.

MAIN:
Prot. ext. disabled
[ 038 046 ]

[ 010 183 ]

IA
IB
IC
MAIN:
Phase sequence
[ 010 049 ]

|Ineg|

MCMON:
Operate delay
[ 017 011 ]

MCMON:
Ineg>
[ 014 002 ]

|Ineg|/|Imax|
Imax

+ 300 ms
SFMON:
Meas. circ. I faulty
[ 098 005 ]

MCMON:
Meas. circ. I faulty
[ 040 087 ]

45Z8022A

Fig. 3-148: Monitoring the current-measuring circuits.

3.23.2

Voltage Monitoring
The voltages used by distance protection as measured values are monitored for
plausibility by the voltage-measuring-circuit monitoring function.

3-198

P437/EN M/R-11-A // P437311650

P437

3 Operation

Monitoring of voltage-measuring circuits is based on the following criteria:

Phase-to-phase voltages are monitored for voltages that fall below the
default threshold of 0.4Vnom. This monitoring function is enabled when the
current exceeds MCMON: Imin Vn eg monit oring in one phase.

The negative-sequence component of phase-to-ground voltages is


monitored in accordance with the definition of symmetrical components.
Monitoring is enabled when a phase-to-ground voltage exceeds the default
threshold of 0.7Vnom / 3.

In addition to these conditions, either a minimum current having the default


threshold setting of I>0.05Inom or the closed position of the circuit breaker
contacts can be used as enabling criteria. If there is an enable, the absolute
value of the negative-sequence component of the voltage system is determined
in accordance with the definition of symmetrical components. This is based on
the MAIN : Ph ase s e que nce setting.
Phase sequence A-B-C (alternative terminology: clockwise rotating
field)

Negative-sequence voltage
V

neg

1
3

| (V
A-G

+ a2 V

+ aV

B-G

)|

C-G

Phase sequence A-C-B (alternative terminology: anti-clockwise rotating


field)

Negative-sequence voltage
V
neg

1
3

| (V
A-G

+ aV

B-G

+ a2 V

)|

C-G

Symbols used:

a = e2j/3 = e j120

a 2 = e4j/3 = e j240

This value is compared with the default threshold operate value 0.2Vnom / 3. If
the threshold operate value is exceeded, a monitoring signal is issued after the
operate delay has elapsed.
If one of the monitoring functions described above operates, then distance
protection is blocked, and the device switches to backup overcurrent time
protection provided the appropriate setting has been selected.
In addition, the MC MON: Me as . voltage o.k. monitoring signal is issued if all
phase-to-phase voltages exceed the default threshold of 0.65Vnom and negativesequence monitoring has not operated.

P437/EN M/R-11-A // P437311650

3-199

P437

3 Operation

MAIN:
Phase sequence
[ 010 049 ]

MCMON:
Enabled
[ 040 094 ]
MAIN:
Prot. ext. disabled
[ 038 046 ]

0.7Vnom/3

VA-G
VB-G

>0.2Vnom/3
C

VC-G

|Vneg|

MCMON:
Operate delay
[ 017 011 ]

SFMON:
Vneg> triggered
[ 098 014 ]
0
MCMON:
Vneg> triggered
[ 041 079 ]

DIST:
General starting
[ 036 240 ]

S11

SFMON:
Undervoltage
[ 098 009 ]

R1

MCMON:
Undervoltage
[ 038 038 ]

BUOC:
Starting
[ 036 013 ]

MCMON:
Op. mode volt. mon.

MCMON:
Phase sequ. V faulty
[ 038 049 ]

[ 014 007 ]

SFMON:
Phase sequ. V faulty
[ 098 001 ]

1
2
3
1: Vneg
2: Vneg with curr. enab
3: Vneg w.CB cont.enab.
MAIN:
CB closed 3p EXT
[ 036 051 ]

MCMON:
Imin Vneg monitoring
[ 010 184 ]

IA
IB
IC

<0.4Vnom
C

>0.65Vnom
C
0

5s

MCMON:
Meas. voltage o.k.
[ 038 048 ]

45Z8041B

Fig. 3-149: Monitoring the voltage-measuring circuit.

3.23.3

Phase-Sequence Monitoring
Phase-sequence monitoring is enabled only if the following conditions are
simultaneously met:

3-200

P437/EN M/R-11-A // P437311650

P437

3 Operation

Measuring circuit monitoring is enabled.

Phase-sequence monitoring is enabled.

All three phase-to-ground voltages exceed 0.4Vnom.

No general starting signal is present.

In order to suppress short-term transients, the phase-sequence monitoring


trigger is followed by a set time-delay of 1 s. Once the time-delay has elapsed,
the signal MC MON: Phase s e qu. V faulty is issued.

3.23.4

Fuse Failure Monitoring of Phase-to-Ground Voltages


In addition to monitoring the voltage-measuring circuits, as described above, the
P437 also provides for fuse failure monitoring. This function is used in particular
when there is no voltage transformer m.c.b. auxiliary contact. If fuse failure
monitoring is not desired it can be disabled by setting parameters.
The fuse failure monitoring function must distinguish between a short circuit in
the three-phase current system and a lack of measuring voltage due to a short
circuit or open circuit (broken wire) in the secondary circuit of the voltage
transformer.
A short circuit exists in the three-phase current system being monitored, if one of
the following conditions is satisfied:

Distance protection has started. (This signal has a time delayed reset of
30 ms so as to avoid startings by transients that may occur at the end of a
short circuit.)

Major current variations occur:

The current increases by more than +5% in at least one phase.


The current decreases by more than 10% in at least two phases.
The current increases by more than +5% in the positive-sequence
current system.

The P437 uses different criteria to detect single- or two-phase faults or threephase faults in the secondary circuit of the voltage transformer.

A single- or two-phase fault is present in the secondary circuit of the


voltage transformer if the following conditions are satisfied simultaneously:

The phase currents exceed the distance protection's I> thresholds either
in none or in all of the three phases (= symmetrical load condition).
A current increase I/t > 10% occurs during 3 cycles (= 3T) in not
exactly one phase.
The negative-sequence current does not exceed an internal threshold.
The negative-sequence voltage has exceeded an internal threshold.

A three-phase fault is present in the secondary circuit of the voltage


transformer if the following conditions are satisfied simultaneously:

At least one of the phase currents exceeds the distance protection's I>
threshold.
The positive-sequence voltage has fallen below an internal threshold.
The positive-sequence current may only vary less than 10% or +5%
within 3 cycles after the positive-sequence voltage has fallen below this
threshold.

P437/EN M/R-11-A // P437311650

3-201

P437

3 Operation

Fuse failure monitoring for 3-phase faults in the measuring circuit is only active
within a 50 ms time window after a positive sequence undervoltage condition is
detected.

If the above conditions are satisfied, a memory is set. The settable operate delay
timer should remain at 0 s to ensure that fuse failure monitoring is able to
prevent false pick up of distance protection.
The memory is reset when the positive-sequence voltage exceeds the fixed
threshold of 0.5Vnom and the negative-sequence voltage falls below an internal
threshold.
If the buffer memory has been set the P437 decides that the secondary circuit of
the voltage transformer is faulty if the following conditions are met:

At least one of the phase currents exceeds the I> threshold, or:

The set threshold of the negative-sequence voltage has been exceeded and
three cycles previously at least one phase-to-ground voltage had been
above 50% Vnom/3.

In this case distance protection is blocked, and the device switches to backup
overcurrent time protection provided that the appropriate setting has been
selected.

3-202

P437/EN M/R-11-A // P437311650

P437

3 Operation

DIST:
IA>(Ibl) trigg.

>1 &

>1

303 598

303 599

>1

DIST:
IC>(Ibl) trigg.
303 600

&

DIST:
General starting
[ 036 240 ]
ARC:
Dead time running
[ 037 002 ]

MCMON:
FF, V triggered
[ 035 081 ]

DIST:
IB>(Ibl) trigg.

30ms

1 1

SFMON:
FF, V triggered
[ 098 021 ]

>1

MAIN:
CB open >=1p
[ 031 039 ]

IA(t) < 0.9IA(t-3T)

>2
&

IB(t) < 0.9IB(t-3T)

MCMON:
Blocking FF, V EXT
[ 002 182 ]

>1
IC(t) < 0.9IC(t-3T)

IA(t) > 1.05IA(t-3T)

>1

IB(t) > 1.05IB(t-3T)

&

&

IC(t) > 1.05IC(t-3T)


IA

IA(t) < 1.1IA(t-3T)

IB

IB(t) < 1.1IB(t-3T)

IC

IC(t) < 1.1IC(t-3T)

=1

MAIN:
Phase sequence
[ 010 049 ]
Ipos(t) > 0.9Ipos(t-3T)

Ipos

& >1

Ipos(t) < Ipos(t-3T)


Ipos(t) > 1,05Ipos(t-3T)

&

&

Ineg
1

50 ms

VA-G

&

VB-G

Vneg

VC-G

&
VA-G(t-3T)>0.5 Vnom/3 >1
VB-G(t-3T)>0.5 Vnom/3
VC-G(t-3T)>0.5 Vnom/3

Vpos
|Vpos| > 0.5 Vnom

45Z8025A

Fig. 3-150: Fuse failure monitoring (after setting M C M O N : F F , V e n a b l e d U S E R = Yes).

P437/EN M/R-11-A // P437311650

3-203

P437
3.23.4.1

3 Operation

Extend Fuse Failure Blocking Condition


Fuse failure determination is prohibited under the following conditions, to avoid
false operation due to voltage transients during de-energized line conditions:

The dead time of the internal auto-reclosing control (ARC) is running.

At least one CB pole is open i.e. MA IN: CB open >=1 p is set to Yes.
This blocking prevents false operation based on discharge-transients of line
reactors, or if the line is energized from the remote end while the fault is
still present. The device at the open CB end then may determine a fuse
failure condition due to a sudden asymmetric change of voltage with no
current. This operation of fuse failure monitoring is basically non-critical (as
the local CB is still open), but jeopardizes faster fault clearance at the
remote end, aided by protection signaling, because PSIG/Echo logic is also
blocked, if MCMON determines a voltage measuring circuit failure.

A fuse failure blocking input signal is activated (MCMON: Blocking FF, V


E XT).

This signal is implemented to establish further flexible blocking conditions, e.g.


through the LOGIC function.

3-204

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.23.5

Fuse Failure Monitoring of the Reference Voltage


The P437 includes Fuse Failure monitoring of the reference voltage function,
which is required by the Automatic Synchronism Check (ASC).
Fuse Failure monitoring of the reference voltage is only possible if the ASC
function has been configured. This is specifically applied when no auxiliary
contact is available on the voltage transformer m.c.b. If fuse failure monitoring is
not desired it can be disabled by setting parameters.
Fuse Failure monitoring must be able to discriminate between a short circuit in
the three-phase network being monitored and a reference voltage missing
because of a short circuit or an open circuit in the secondary circuits of the
reference voltage.
A short circuit or an open circuit in the secondary circuits of the reference
voltage is present when the following conditions are met:

The circuit breaker is closed.

The voltage difference between the line side and the busbar must exceed
0.1Vnom.

MCMON:
FF,Vref enabled USER
[ 014 013 ]

0
1

0: No
1: Yes

Vref
|Vref|-|VMeas|
ASC:
Vmeas

0.1 Vnom

305 007

INP:
Fct. assignm. U xxx
[ 152 xxx ]

U x1

MCMON:
Oper. delay FF, Vref
[ 014 012 ]

U x2
U x3
U xx
Address

MCMON:
FF, Vref triggered
[ 038 100 ]

036 051

MAIN:
CB closed 3p
[ 031 042 ]

SFMON:
FF, Vref triggered
[ 098 022 ]

47Z0178B

Fig. 3-151: Fuse Failure monitoring of the reference voltage.

P437/EN M/R-11-A // P437311650

3-205

P437

3.24

3 Operation

Backup Overcurrent-Time Protection (Function Group BUOC)


If there is a fault in the voltage-measuring circuit, distance protection is blocked,
since accurate impedance measurement is not possible. Backup overcurrenttime protection (BUOC) is then automatically activated if set accordingly.
Backup overcurrent-time protection (BUOC) is enabled if there is a fault in the
voltage-measuring circuit. It monitors the phase currents for overcurrents
exceeding the set values I>. If a phase current exceeds the set value, timer stage
tI> is started. After the set time period has elapsed, a trip signal is issued. If
inrush stabilization is triggered, BUOC protection is blocked (if included in the
selection, see Section 3.12.5.1, (p. 3-90)).
If the Low impedance-grounding setting has been selected for the neutral point
treatment, ground current IN is also monitored by the settable trigger IN>, in
addition to the phase currents. If the ground current exceeds the set value, timer
stage tIN> is started. After the set time period has elapsed, a trip signal is issued.
Inrush stabilization blocks the ground starting of BUOC protection (if included in
the selection, see Section 3.12.5.1, (p. 3-90)).
The setting for the operating mode controls whether the BUOC protection
function will trigger an auto-reclosure (ARC). If auto-reclosure is desired, timer
stages tI> and tIN> will be blocked when the ARC function is ready. With phase
starting, the trip signal will then be issued instantaneously; with ground starting,
it will be issued after an 80 ms delay. Timer stage tIN> (or fixed 80 ms starting
time in case of ARC) is also blocked by phase starting.
If auto-reclosure is not required or if auto-reclosure with three-pole HSR is
required, then the trip signal is always three-pole.

3-206

P437/EN M/R-11-A // P437311650

P437

3 Operation

MCMON:
Meas. circ. V faulty
[ 038 023 ]

BUOC:
General enable USER
[ 014 011 ]

SFMON:
BUOC not active
[ 098 002 ]

0
1
0: No

BUOC:
Enabled

1: Yes

[ 040 093 ]

DIST:
Enabled
[ 036 104 ]

BUOC:
Operating mode
[ 014 000 ]

SFMON:
BUOC active w/o ARC
[ 098 003 ]
1
2

SFMON:
BUOC active with ARC

[ 098 004 ]

1: Without ARC
2: With ARC, 3p HSR

BUOC:
Active

3: With ARC, 1/3p. HSR

[ 037 021 ]

MAIN:
Blocking 1p trip EXT
[ 041 078 ]
ARC:
Ready
[ 004 068 ]

BUOC:
tI> PSx
[ * ]

MAIN:
Rush restr. A trig.
[ 041 027 ]
MAIN:
Rush restr. B trig.
[ 041 028 ]

BUOC:
Trip A

MAIN:
Rush restr. C trig.

304 754

[ 041 029 ]

BUOC:
Trip B
304 755

BUOC:
Trip C

BUOC:
I> PSx
[ * ]

MAIN:
Protection active

304 756

BUOC:
IA> triggered

306 001

304 750

IA

BUOC:
IB> triggered

IB

304 751

IC

BUOC:
IC> triggered
304 752

ARC:
Dead time running
[ 037 002 ]
BUOC:
tIN> PSx
[ * ]

BUOC:
IN> PSx
[ * ]

BUOC:
Trip signal
[ 036 014 ]

80ms

0
BUOC:
Starting

BUOC:
Block. Starting

[ 036 013 ]
BUOC:
SN

450 206

BUOC:
Bl.Zero-sequ.start.

304 757

BUOC:
Zero-sequ. starting
[ 010 185 ]

450 207

Parameter

BUOC:
I> PSx

BUOC:
tI> PSx

BUOC:
IN> PSx

BUOC:
tIN> PSx

set
set
set
set

010
010
010
011

010
010
010
011

010
010
011
011

010
010
011
011

1
2
3
4

058
078
098
018

059
079
099
019

064
084
004
024

065
085
005
025

45Z8024B

Fig. 3-152: Backup overcurrent-time protection (BUOC).

P437/EN M/R-11-A // P437311650

3-207

P437

3.25

3 Operation

Switch on to Fault Protection (Function Group SOTF)


When the circuit breaker is closed manually, it is possible to switch on to an
existing fault. This is especially critical if a maintenance ground clamp were
inadvertently left connected at the remote end of the line, since the distance
protection function would not clear the fault until zone 2 delay t2 had elapsed. In
this situation, however, the fastest possible clearance is desired.
To ensure rapid clearing with manual closing, the manual close signal must be
applied not only to the circuit breaker but also to the P437. The MAIN: Manual
close E XT signal must be configured separately to a binary signal input (and
triggered during the closing action) even if the close command is issued via the
P437. The manual close signal is converted to an internal pulse, of settable
duration. The pulse time can be set. The user may specify whether the following
shall occur during operation of this timer stage:

The occurrence of a general start shall cause a trip


(SOTF: Trip signa l).

A zone extension of impedance zone 1 shall occur


(SOTF : Z 1 ext e nde d).

Moreover, the overcurrent protection of SOTF features an additional phase


overcurrent element. This allows full, current based SOTF protection even during
a voltage measuring failure. The featured settings are SOTF: I> PSx for the
current threshold and SOTF: tI > P Sx for the timer stage. The signal
SOTF: St art in g I > is set to Yes in case of an overcurrent situation.
Switch on to fault protection can be blocked by external auto-reclosing control
(ARC), provided that a binary signal input has been configured accordingly. An
internal blocking signal is generated together with the trigger signal for the timer
stage. This internal blocking signal will prevent that ARC is activated during an
existing fault when a manual close signal is issued.
Moreover, an external trigger SOTF : Tri gge r EXT may now be applied as an
alternative to the external trigger MAI N: Man ual close EXT. In some
applications, SOTF triggering is required when line energizing is initiated from an
external A/R device. This is how the P437 provides the feature Zone extension
during reclosure. Although this functionality can be achieved by using the
existing binary input MAIN: Manu al clos e EXT, the use of this signal might be
confusing.
An additional option SOTF: Activati on m ode P Sx can be set to either Trigger
(which is the situation described above) or to Line Dead State. With the latter
setting, SOTF becomes permanently active during dead line condition, so that no
external trigger is necessary.

3-208

P437/EN M/R-11-A // P437311650

P437

3 Operation

SOTF:
Active
[ 006 146 ]

SOTF:
Evaluation IN PSx
[*]

SOTF:
tIN> PSx
[*]

0
SOTF:
tIN> elapsed
[ 001 188 ]

2
1: Calculated
2: Measured

SOTF:
IN> (meas.) PSx
[*]
SOTF:
Starting IN>
[ 001 187 ]

&
IN(meas.)

SOTF:
tI> PSx

SOTF:
IN> (calc.) PSx
[*]

[*]

IN(calc.)

SOTF:
tI> elapsed
[ 006 129 ]

SOTF:
I> PSx
[*]

SOTF:
Starting I>
[ 006 128 ]

&

IA
IB
IC

Parameter

SOTF:
Evaluation IN PSx

SOTF:
IN> (meas.) PSx

SOTF:
IN> (calc.) PSx

SOTF:
I> PSx

SOTF:
tIN> PSx

SOTF:
tI> PSx

set 1
set 2

001 191
001 192

001 189
001 195

001 190
001 198

001 177
001 178

set 3
set 4

001 193
001 194

001 196
001 197

001 199
001 202

006
006
006
006

006
006
006
006

130
131
132
133

001 179
001 180

134
135
136
137

47Z1306A

Fig. 3-153: Switch on to fault protection function, overcurrent stage in the residual current system.

P437/EN M/R-11-A // P437311650

3-209

P437

3 Operation

SOTF:
General enable USER
[*]

0
1

0: No
1: Yes

SOTF:
Enable PSx

Parameter

SOTF:
Enable PSx

SOTF:
Man. close timer PSx

SOTF:
Operating mode PSx

SOTF:
Activation mode PSx

set
set
set
set

001
001
001
001

011
001
001
001

011
001
001
001

006
006
006
006

1
2
3
4

203
204
205
206

Parameter

SOTF:
Tripping time PSx

set
set
set
set

010
010
010
010

1
2
3
4

060
181
182
183

061
184
185
186

**

218
219
221
222

142
143
144
145

PSU:
PS y active

1
2
3
4

036
036
036
036

090
091
092
093

[*]

SOTF:
Enabled
[ 040 069 ]

&

1
0: No
PSU:
PS y active
[**]

1: Yes

SOTF:
tI> elapsed
[ 006 129 ]

SOTF:
Trip signal
[ 036 064 ]

SOTF:
tIN> elapsed
[ 001 188 ]
MAIN:
General starting
[ 036 000 ]

&
&

SOTF:
Par. ARC running EXT
[ 039 063 ]

SOTF:
Man. close timer PSx
[*]

MAIN:
Protection active

&

SOTF:
Z1 extended
[ 035 076 ]

306 001

SOTF:
Line dead trig. en.

&

310 006

MAIN:
Manual close EXT
[ 036 047 ]

SOTF:
Active
[ 006 146 ]

SOTF:
tManual-close runn.
[ 036 063 ]

&

SOTF:
Trigger EXT
[ 002 127 ]

SOTF:
ARC blocked

ARC:
Close command

305 650

303 021

SOTF:
Activation mode PSx
[*]

SOTF:
Operating mode PSx
[*]

1
2

&

1: Trigger

4: Trip with starting

2: Line Dead State

5: Trip with overreach

SOTF:
Line dead
[ 006 147 ]

SOTF:
Tripping time PSx
[*]

&

DIST:
General starting
[ 036 240 ]

SOTF:
Trip time elapsed
460 528

45Z8040A

Fig. 3-154: Switch on to Fault Protection.

3.25.1

Decision Line dead


The setting SO TF : W ith V< en abl e P Sx allows the function SOTF to be
enabled only when the phase voltage is low. If this is set to Yes, then a settable
timer stage will have to elapse before an undervoltage condition will lead to the
decision 'Line dead'. This will prevent timing problems between the line
energizing control function and triggering of the SOTF function.
On the other hand, in few cases CT failures occurred from picking up load
current. For such cases it is not desirable to inhibit SOTF, even if the line is
already energized. To take care for this condition, too, the dead line inhibit logic
can be disabled by setting SOTF: With V < e nable PSx to No.

3-210

P437/EN M/R-11-A // P437311650

P437

3 Operation

Moreover, the decision Line dead is set only if also all 3 phase currents are
below an undercurrent threshold. This threshold is fixed to 0.05Inom.
A settable timer SO TF : Oper ate de lay PSx makes the SOTF function active (in
permanent modes) or triggered (in trigger modes) only after the conditions for
Line dead are present for a sufficiently long time. This time delay should be set
longer than the slowest delayed auto-reclose dead time, but shorter than the
time in which the system operator might re-energize a circuit once it had
opened/tripped. 110 seconds is the default setting.

SOTF:
With V< enable PSx
[*]

0
1
0: No
1: Yes

SOTF:
Operate delay PSx
[*]
SOTF:
Release delay PSx
[*]

V < 0.7 Vnom/3

t
&

VA-G

SOTF:
Line dead trig. en.

310 006

&

&

VB-G
VC-G
SOTF:
Line dead
[ 006 147 ]

MCMON:
Meas. circ. V faulty
[ 038 023 ]
I < 0.05 Inom
IA
IB
IC

&

Parameter

SOTF:
With V< enable PSx

SOTF:
Operate delay PSx

SOTF:
Release delay PSx

set
set
set
set

006
006
006
006

006
006
006
006

002
002
002
002

1
2
3
4

005
006
007
008

138
139
140
141

128
129
133
134

47Z1304B

Fig. 3-155: Decision Line dead in the Switch on to fault protection function.

P437/EN M/R-11-A // P437311650

3-211

P437

3.26

3 Operation

Protective Signaling (Function group PSIG)


The reach of the first impedance zone of the distance protection function is
normally set for values less than 100%. Protective signaling is used to extend
protection to 100% of the line section. This is achieved by logical linking of the
signals that are transmitted by the remote stations protection device.

3.26.1

Disabling and Enabling Protective Signaling


The function can be disabled or enabled using setting parameters or through
binary signal inputs.
The function is enabled independently of parameter subsets via PSIG: Gener al
enable U SER. It is enabled as a function of a parameter subset via
PSI G: En able PSx. If these enabling functions have been activated, protective
signaling can be disabled or enabled using setting parameters or through
appropriately configured binary signal inputs. Parameters and configured binary
signal inputs have equal status. If only the P SIG: Enable EXT function is
assigned to a binary signal input, then protective signaling is enabled by a
positive edge of the input signal and it is disabled by a negative edge. If only the
PSI G: D isa ble EXT function is assigned to a binary signal input, then a signal
at this input will have no effect.

3.26.2

Readiness of Protective Signaling


In order for protective signaling (PSIG) to function, the following requirements
must be satisfied:

3-212

It must be enabled.

There must be no external block.

There must be no transmission fault.

P437/EN M/R-11-A // P437311650

P437

3 Operation

PSIG:
General enable USER
[ 015 004 ]

0
1

0: No
1: Yes

PSIG:
Enable PSx
[ * ]

0
1

PSIG:
Enabled
[ 015 008 ]

0: No
1: Yes

INP:
Fct. assignm. U xxx
[ xxx xxx ]

U x1
U x2
U x3
U xx
Address

037 025

Address

037 026
PSIG:
Ext./user enabled
[ 037 023 ]

PSIG:
Enable EXT
[ 037 025 ]
PSIG:
Enable USER
[ 003 132 ]

0
1
0: don't execute
1: execute
PSIG:
Disable EXT
[ 037 026 ]
PSIG:
Disable USER
[ 003 131 ]

0
1
0: don't execute

PSIG:
Ready
[ 037 027 ]

1: execute

MAIN:
Protection active
306 001

PSIG:
Blocking EXT
[ 036 049 ]
PSIG:
Telecom. faulty
[ 036 060 ]

PSIG:
Not ready
[ 037 028 ]

Parameter

PSIG:
Enable PSx

set
set
set
set

015
015
015
015

1
2
3
4

014
015
016
017

45Z5032C

Fig. 3-156: Enabling, disabling and readiness of protective signaling.

If protective signaling is ready, distance protection tripping takes place in zone 1.

With normal reach: After distance protection stage t1 has elapsed.

With extended reach: after the protective signaling tripping time has
elapsed.

P437/EN M/R-11-A // P437311650

3-213

P437

3 Operation

PSIG:
Operating mode PSx
[ * ]
2: PUTT

8: Direction comparison

ARC:
Zone extension RC

303 002

SOTF:
Z1 extended
[ 035 076 ]

PSIG:
Tripping time PSx
[ *
]

DIST:
Zone extension EXT
[ 036 046 ]

PSIG:
Ready
[ 037 027 ]

PSIG:
Timer stage elapsed
305 164

&

PSIG:
Trip time elapsed
305 150

DIST:
General starting
[ 036 240 ]

Parameter

PSIG:
Tripping time PSx

PSIG:
Operating mode PSx

set
set
set
set

015
024
024
025

015
024
024
025

1
2
3
4

011
003
063
023

000
000
060
020

47Z8042A

Fig. 3-157: Protective signaling tripping time.

3.26.3

Three-Ended Line Application


In general the PSI G: Re ce i ve ( A ) EXT or P SIG: Re ce ive ( B) EXT signals are
simply used in an OR combination.
In case a permissive scheme is applied to 3-ended lines, the permissive signals
from both remote end units must be received, and these two signals have then
to be used in an AND combination.
Forming such an AND combination externally would mean having to accept
additional delays and loss of data with respect to the transmitted signals. In
order to have this operation available and overcome the shortcomings of the
usual single channel data transmission links, the P437 features the possibility to
use these two signals directly by setting parameters PSIG: 3ended line p ro t
PSx to Yes .
These two signals are further processed as shown in the figure below to create a
new signal (PS IG: Receive which is used in the various PSIG operating modes.
If 3ended line protection is enabled then both receive signals are linked in an
AND gate, otherwise they are linked in an OR gate. The latter permits the use
of either the A or the B signal, or even both signals in case of redundant signaling
channels, on 2ended lines.
The same principle is true of the phase-selective input signals, see figure below.

3-214

P437/EN M/R-11-A // P437311650

P437

3 Operation

PSIG:
3ended line prot PSx
[ * ]
0
1

Parameter

PSIG:
3ended line prot PSx

set 1
set 2
set 3
set 4

006 039
006 046
006 047
006 048

0: No
1: Yes

&

PSIG:
Receive (A) EXT
[ 036 048 ]
PSIG:
Receive (B) EXT
[ 006 037 ]

&

PSIG:
Chan. B1 receive EXT
[ 008 241 ]

&

&

PSIG:
Chan. B3 receive EXT
[ 008 243 ]

&

PSIG:
Channel 2 receive
[ 008 245 ]

&

&

PSIG:
Chan. A3 receive EXT
[ 038 093 ]

PSIG:
Channel 1 receive
[ 008 244 ]

&

&

PSIG:
Chan. A2 receive EXT
[ 038 092 ]
PSIG:
Chan. B2 receive EXT
[ 008 242 ]

&

&

PSIG:
Chan. A1 receive EXT
[ 038 091 ]

PSIG:
Receive
[ 006 036 ]

PSIG:
Channel 3 receive
[ 008 246 ]

&

47Z2004B

Fig. 3-158: Three-ended line protection.

3.26.4

Monitoring the Transmission Section


A transmission fault leads to a blocking of the protective signaling function
(see Fig. 3-159, (p. 3-216)). If protective signaling is being carried out via a
signal transmission or communication device, the device's fault signal can be
connected. With protective signaling over pilot wires or with the operating mode
set to reverse interlocking the internal monitoring function will detect a fault in
the transmission channel.

P437/EN M/R-11-A // P437311650

3-215

P437

3 Operation

PSIG:
Operating mode PSx
[ *
]
6: DC loop operat. mode

&

PSIG:
Release t. send PSx
[ *
]

PSIG:
Telecom. faulty
[ 036 060 ]
SFMON:
Telecom. faulty/PSIG
[ 098 006 ]

Set value+600ms

PSIG:
Receive
[ 006 036 ]

&

DIST:
General starting
[ 036 240 ]

PSIG:
Telecom. faulty int.
305 151

PSIG:
Telec.faulty (A) EXT
[ 004 064 ]

&

&

&

PSIG:
Telec.faulty (B) EXT
[ 008 094 ]

PSIG:
Blk.f.telcom.flt PSx
[ * ]
1
2
1: Ch. (A)OR(B) faulty
2: Ch. (A)AND(B) faulty

Parameter

PSIG:
Operating mode PSx

PSIG:
Release t. send PSx

PSIG:
Blk.f.telcom.flt PSx

set
set
set
set

015
024
024
025

015
024
024
025

012
012
012
012

1
2
3
4

000
000
060
020

002
001
061
021

PSIG:
Telecom. faulty (A)
[ 012 244 ]
PSIG:
Telecom. faulty (B)
[ 012 245 ]

246
247
248
249

47Z8047A

Fig. 3-159: Transmission fault.

3.26.5

Frequency Monitoring
Failure of frequency transmission may be signaled to the P437 via an
appropriately configured binary signal input (PSIG: F req. m on. trig. EX T). If
frequency monitoring is enabled, the P437 once a time-delay of approximately
20 ms has elapsed will generate a receive signal for a duration of 150 ms.

PSIG:
Frequency monit. PSx
[

0
1
0: No
1: Yes

20ms

PSIG:
Receive
[ 006 036 ]

PSIG:
Frequ. monit. trigg.
1
150ms

305 152

PSIG:
Freq. mon. trig. EXT
[ 038 080 ]
Parameter

PSIG:
Frequency monit. PSx

set
set
set
set

015
024
024
025

1
2
3
4

025
011
071
031

45Z6348A

Fig. 3-160: Frequency monitoring.

3.26.6

Transient Blocking
In the event of a direction change, protective signaling will be blocked for the
time set at PSI G: tBlock PSx.

3-216

P437/EN M/R-11-A // P437311650

P437

3 Operation

PSIG:
tBlock PSx
[ * ]

DIST:
Fault forward / LS
[ 036 018 ]

S1 1
R1

DIST:
Fault backward / BS
[ 036 019 ]

S1 1

1
t

PSIG:
tBlock PSx
[ * ]

PSIG:
Transient blocking
305 154

R1

DIST:
General starting
[ 036 240 ]

Parameter

PSIG:
tBlock PSx

set
set
set
set

015
024
024
025

1
2
3
4

024
010
070
030

49Z6444A

Fig. 3-161: Transient blocking.

3.26.7

Protective Signaling Operating Modes


Protective signaling can be operated in eight different modes, which can be
selected with the setting parameter P SI G: Operat ing mode PSx:

Direct underreaching transfer trip (setting: Dir.trans.trip.under, see


Section 3.26.7.3, (p. 3-219))

Permissive underreaching transfer trip (setting: PUTT, see Section 3.26.7.4,


(p. 3-220))

Zone extension (setting: Zone extension, see Section 3.26.7.5, (p. 3-222))

Release (permissive) scheme (setting: Release scheme, see


Section 3.26.7.6, (p. 3-224))

Blocking scheme (setting: Blocking scheme, see Section 3.26.7.7, (p. 3228))

P437/EN M/R-11-A // P437311650

3-217

P437

3 Operation

PSIG:
Operating mode PSx
[ * ]

0: Without

1: Dir.trans.trip.under

2: PUTT

3: Zone extension

4: Release scheme

5: Blocking scheme

6: DC loop operat. mode

7: Reverse interlocking

8: Direction comparison

8
0: Without
1: Dir.trans.trip.under
2: PUTT
3: Zone extension
4: Release scheme
5: Blocking scheme
6: DC loop operat. mode
7: Reverse interlocking
8: Direction comparison

Parameter

PSIG:
Operating mode PSx

set
set
set
set

015
024
024
025

1
2
3
4

000
000
070
020

D5Z5061A

Fig. 3-162: Setting the protective signaling operating modes.

3.26.7.1

Checking the Operating Mode Setting


The P437 features protective signaling and ground fault (short-circuit) protection
signaling. If the P437 is operating with protective signaling and ground fault
protective signaling, then the user has the option to specify whether ground fault
protective signaling will share the channel used by protective signaling (distance
schemes) for signal transmission. If this is the case, the operating modes for
protective signaling and ground fault protection signaling must be set identically.
Otherwise a signal will be issued.

PSIG:
Operating mode PSx
[ * ]
4: Release scheme
5: Blocking scheme

GSCSG:
Operating mode
[ 023 079 ]
1: Signal comp. release

& 1

&

&

SFMON:
Op.mode PSIG inval.
[ 098 019 ]

2: Signal comp. block.

GSCSG:
Channel mode
[ 023 078 ]
2: Common channel
Parameter

PSIG:
Operating mode PSx

set
set
set
set

015
024
024
025

1
2
3
4

000
000
060
020

47Z8037A

Fig. 3-163: Checking the operating mode setting.

3-218

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.26.7.2

Limiting to Weak-Infeed Logic or Echo Function


If only the weak-infeed logic or the echo function will be used and no other
protective signaling functions, then this can be implemented by setting the
operating mode to Without.

3.26.7.3

Operating Mode Dir.trans.trip.under


When a distance protection trip zone 1 has occurred, a signal is sent to the
remote stations protection device. Signals are transmitted through one or three
channels, depending on the setting.
Upon receipt of the signal by the remote station, the remote stations circuit
breaker is tripped. The settings DIST: Trip zon e 1 PG PSx and DI ST: Trip
zone 1 PP PSx are taken into account.

PSIG:
Ready
[ 037 027 ]
PSIG:
Operating mode PSx
[ * ]
1: Dir.trans.trip.under

&

PSIG:
No. telecom. ch. PSx
[ * ]

PSIG:
Release t. send PSx
[ * ]

&

1: 1 channel
3: 3 channels

&

DIST:
Trip zone 1
303 584

&

DIST:
Trip zone 1, A
303 655

&

DIST:
Trip zone 1, B
303 656

&

DIST:
Trip zone 1, C

PSIG:
Send
[ 012 243 ]
PSIG:
Send (signal)
[ 036 035 ]
PSIG:
Channel 1 send
[ 038 081 ]
PSIG:
Channel 2 send
[ 038 082 ]
PSIG:
Channel 3 send
[ 038 083 ]

303 657

Parameter

PSIG:
Operating mode PSx

PSIG:
No. telecom. ch. PSx

PSIG:
Release t. send PSx

set
set
set
set

015
024
024
025

015
024
024
025

015
024
024
025

1
2
3
4

000
000
060
020

026
012
072
032

002
001
061
021

47Z8088B

Fig. 3-164: Protective signaling transmission with the Dir.trans.trip.under operating mode.

P437/EN M/R-11-A // P437311650

3-219

P437

3 Operation

PSIG:
Ready
[ 037 027 ]
PSIG:
Operating mode PSx
[ * ]
1: Dir.trans.trip.under
PSIG:
No. telecom. ch. PSx
[ * ]
1
3
1: 1 channel

Parameter

PSIG:
Operating mode PSx

PSIG:
No. telecom. ch. PSx

set 1
set 2
set 3
set 4

015 000
024 000
024 060
025 020

015 026
024 012
024 072
025 032

Parameter

DIST:
Trip zone 1 PG PSx

DIST:
Trip zone 1 PP PSx

set 1
set 2
set 3
set 4

011 050
011 051
011 052
011 053

011 054
011 055
011 056
011 057

3: 3 channels
PSIG:
Receive (A) EXT
[ 036 048 ]
PSIG:
Frequ. monit. trigg.
305 152
PSIG:
Transient blocking305 154
PSIG:
Channel 1 receive
[ 008 244 ]
PSIG:
Frequ. monit. ch. 1305 169
PSIG:
Ch. 1 transient bl. 305 172
PSIG:
Channel 2 receive
[ 008 245 ]
PSIG:
Frequ. monit. ch. 2305 170
PSIG:
Ch. 2 transient bl. 305 173
PSIG:
Channel 3 receive
[ 008 246 ]
PSIG:
Frequ. monit. ch. 3305 171
PSIG:
Ch. 3 transient bl. 305 174

PSIG:
Receive (signal)
[ 037 029 ]

DIST:
Trip zone 1 PG PSx
[ * ]
3: 3-pole

PSIG:
Trip channel 1

1: 1-pole

402 575

PSIG:
Trip channel 2
402 576

PSIG:
Trip channel 3
402 577

PSIG:
Trip signal
[ 038 007 ]

DIST:
Trip zone 1 PP PSx
[ * ]
1: 1-pole leading phase
2: 1-pole trailing phas
3: 3-pole
MAIN:
Phase sequence
[ 010 049 ]
2: A - C - B
1: A - B - C

47Z0189C

Fig. 3-165: Protective signaling trip with operating mode Dir.trans.trip.under.

3.26.7.4

Operating Mode PUTT


When a distance protection trip zone 1 has occurred, a signal is sent to the
remote stations protection device. Signals are transmitted through one or three
channels, depending on the setting.
On receipt of the signal by the remote station, the remote stations circuit
breaker is subject to permissive underreaching transfer tripping (PUTT) once the
protective signaling tripping time has elapsed. The DIST: Tr ip zone 1 PG PSx
(with starting in the zero-sequence system )and D IST: Tr ip zone 1 PP PS x
(without starting in the zero-sequence system) settings are taken into account by
the P437.

3-220

P437/EN M/R-11-A // P437311650

P437

3 Operation

Mode set at DI ST: Trip zone 1 P G PSx = 1-pole or 3-pole.

Mode set at DIST: Tr ip zone 1 PP PSx = 1-pole leading phase or 1-pole


trailing phas or 3-pole.

PSIG:
Ready
[ 037 027 ]
PSIG:
Operating mode PSx
[ * ]
2: PUTT

&

PSIG:
No. telecom. ch. PSx
[ * ]

PSIG:
Release t. send PSx
[ * ]

1
3

&

1: 1 channel
3: 3 channels

&

DIST:
Trip zone 1
303 584

&

DIST:
Trip zone 1, A
303 655

&

DIST:
Trip zone 1, B
303 656

&

DIST:
Trip zone 1, C

PSIG:
Send
[ 012 243 ]
PSIG:
Send (signal)
[ 036 035 ]
PSIG:
Channel 1 send
[ 038 081 ]
PSIG:
Channel 2 send
[ 038 082 ]
PSIG:
Channel 3 send
[ 038 083 ]

303 657

Parameter

PSIG:
Operating mode PSx

PSIG:
No. telecom. ch. PSx

PSIG:
Release t. send PSx

set
set
set
set

015
024
024
025

015
024
024
025

015
024
024
025

1
2
3
4

000
000
060
020

026
012
072
032

002
001
061
021

47Z8090A

Fig. 3-166: Protective signaling transmission with operating mode PUTT (permissive underreaching transfer
tripping).

P437/EN M/R-11-A // P437311650

3-221

P437

3 Operation

PSIG:
Ready
[ 037 027 ]
PSIG:
Operating mode PSx
[ * ]
2: PUTT
PSIG:
No. telecom. ch. PSx
[ * ]

Parameter

PSIG:
Operating mode PSx

PSIG:
No. telecom. ch. PSx

set 1
set 2
set 3
set 4

015 000
024 000
024 060
025 020

015 026
024 012
024 072
025 032

Parameter

DIST:
Trip zone 1 PG PSx

DIST:
Trip zone 1 PP PSx

set 1
set 2
set 3
set 4

011 050
011 051
011 052
011 053

011 054
011 055
011 056
011 057

1: 1 channel
3: 3 channels

PSIG:
Timer stage elapsed
305 164
MAIN:
General starting
[ 036 000 ]
PSIG:
Receive (A) EXT
[ 036 048 ]
PSIG:
Frequ. monit. trigg.
305 152
PSIG:
Transient blocking
305 154
DIST:
Starting A
303 529
PSIG:
Channel 1 receive
[ 008 244 ]
PSIG:
Frequ. monit. ch.
1
305 169
PSIG:
Ch. 1 transient305
bl.172
DIST:
Starting B
303 530
PSIG:
Channel 2 receive
[ 008 245 ]
PSIG:
Frequ. monit. ch. 2305 170
PSIG:
Ch. 2 transient bl. 305 173
DIST:
Starting C
303 531
PSIG:
Channel 3 receive
[ 008 246 ]
PSIG:
Frequ. monit. ch. 3305 171
PSIG:
Ch. 3 transient bl. 305 174

PSIG:
Receive (signal)
[ 037 029 ]

DIST:
Trip zone 1 PG PSx
[ * ]
3: 3-pole

PSIG:
Trip channel 1

1: 1-pole

402 575

PSIG:
Trip channel 2
402 576

PSIG:
Trip channel 3
402 577

PSIG:
Trip signal
[ 038 007 ]

DIST:
Trip zone 1 PP PSx
[ * ]
1: 1-pole leading phase
2: 1-pole trailing phas
3: 3-pole
MAIN:
Phase sequence
[ 010 049 ]
2: A - C - B
1: A - B - C

47Z0191C

Fig. 3-167: Protective signaling trip with operating mode PUTT (permissive underreaching transfer tripping).

3.26.7.5

Operating Mode Zone extension


When a distance protection trip has occurred in zone 1, a signal is sent to the
remote stations protection device. Upon receipt of the transmitted signal, the
measuring range of zone 1 in the remote station is increased by the zone
extension factor kze HSR (see Fig. 3-177, (p. 3-232)). Signals are transmitted
through one or three channels, depending on the setting.
The response of the protection device in the remote station is determined by the
setting at PS IG: Oper. mode trip P Sx in the remote station.

3-222

P437/EN M/R-11-A // P437311650

P437

3 Operation

Direct.-dependent
After the protective signaling tripping time has elapsed, tripping occurs in
the phase(s) in which there is a receive signal and distance protection has
decided in favor of forward direction. The D IST: Trip zon e 1 PG PSx and
DIST: Trip zo ne 1 PP PSx settings are taken into account by the P437. If
transient blocking is operating, then the receive signal will be ignored.

Dist.-dependent
If the fault is located within the extended zone, then the protection device
of the remote station also decides in favor of a trip after the protective
signaling tripping time has elapsed. If transient blocking is operating, then
the receive signal will be ignored.

Dashed line: measuring range extended by zone extension factor kze HSR

Zone 1, prot.dev. a
Zone 1, prot.dev. b

D5Z5053A

Fig. 3-168: Reaches with zone extension.

PSIG:
Ready
[ 037 027 ]
PSIG:
Operating mode PSx
[ * ]
3: Zone extension

PSIG:
No. telecom. ch. PSx
[ * ]

1
3
1: 1 channel
3: 3 channels
DIST:
Trip zone 1
303 584

DIST:
Trip zone 1, A
303 655

DIST:
Trip zone 1, B
303 656

DIST:
Trip zone 1, C
303 657

Parameter

PSIG:
Operating mode PSx

PSIG:
No. telecom. ch. PSx

PSIG:
Release t. send PSx

set
set
set
set

015
024
024
025

015
024
024
025

015
024
024
025

1
2
3
4

000
000
060
020

026
012
072
032

002
001
061
021

47Z8092A

Fig. 3-169: Protective signaling transmission with operating mode Zone extension.

P437/EN M/R-11-A // P437311650

3-223

P437

3 Operation

DIST:
Trip zone 1 PG PSx
[ * ]
3: 3-pole

PSIG:
Trip channel 1

1: 1-pole

402 575

PSIG:
Trip channel 2

PSIG:
Oper. mode trip PSx
[ * ]

402 576

PSIG:
Trip channel 3

402 577

ARC:
(Re)close signal HSR
[ 038 007 ]

1: Direct.-dependent
DIST:
Trip zone 1 PP PSx
[ * ]
1: 1-pole leading phase

2: Dist.-dependent

2: 1-pole trailing phas


3: 3-pole
MAIN:
Phase sequence
[ 010 049 ]
1: A - B - C
2: A - C - B
PSIG:
Ready
[ 037 027 ]
PSIG:
Operating mode PSx
[ * ]
3: Zone extension
PSIG:
Timer stage elapsed305 164
DIST:
Fault forward / LS
[ 036 018 ]
PSIG:
Receive (A) EXT
[ 036 048 ]
PSIG:
Frequ. monit. trigg. 305 152
PSIG:
Transient blocking 305 154
DIST:
Trip zone 1,ze
303 595
DIST:
Fault forwd. / LS, A
[ 038 010 ]
PSIG:
Channel 1 receive
[ 008 244 ]
PSIG:
Frequ. monit. ch. 1 305 169
PSIG:
Ch. 1 transient bl. 305 172
DIST:
Trip zone 1,ze, A
303 658
DIST:
Fault forwd. / LS, B
[ 038 012 ]
PSIG:
Channel 2 receive
[ 008 245 ]
PSIG:
Frequ. monit. ch. 2305 170
PSIG:
Ch. 2 transient bl. 305 173
DIST:
Trip zone 1,ze, B 303 659
DIST:
Fault forwd. / LS, C
[ 038 014 ]
PSIG:
Channel 3 receive
[ 008 246 ]
PSIG:
Frequ. monit. ch. 3 305 171
PSIG:
Ch. 3 transient bl. 305 174
DIST:
Trip zone 1,ze, C 303 660

PSIG:
Trip enable
305 157

PSIG:
Trip enable, ch. 1
305 166

PSIG:
Trip enable, ch. 2
305 167

PSIG:
Trip enable, ch. 3
305 168

PSIG:
Receive (signal)
[ 038 029 ]
* Parameter

MAIN:
General starting
[ 036 000 ]

set 1
set 2
set 3
set 4

PSIG:
No. telecom. ch. PSx
[ * ]
3
1
3: 3 channels
1: 1 channel

* Parameter
set 1
set 2
set 3
set 4

PSIG:
Operating mode PSx

PSIG:
No. telecom. ch. PSx

015 000
024 000
024 060
025 020

015 026
024 012
024 072
025 032

PSIG:
Oper. mode trip PSx

DIST:
Trip zone 1 PG PSx

DIST:
Trip zone 1 PP PSx

015 107
015 108
015 113
015 114

011 050
011 051
011 052
011 053

011 054
011 055
011 056
011 057

47Z0293D

Fig. 3-170: Protective signaling trip and trip enable in operating mode Zone extension.

3.26.7.6

Operating Mode Release scheme


Zone extension in zone 1 of distance protection is a function of the setting at
PS IG: Op er. mode se nd PSx.

3-224

P437/EN M/R-11-A // P437311650

P437

3 Operation

'Direct.-dependent'
The measuring range of zone 1 of distance protection is not extended.

'Dist.-dependent'
In the idle state, the measuring range of zone 1 in both protection devices
is extended by the zone extension factor kze HSR (see Fig. 3-177, (p. 3232)). The distance protection trip in extended zone 1 is blocked in both
protection devices.

Dashed line: measuring range extended by zone extension factor kze HSR.

Nfw, b
Zone 1, prot.dev. a
Nfw, b
Zone 1, prot.dev. b

D5Z5054A

Fig. 3-171: Zone reaches with the release (permissive) scheme.

The setting at PSIG: Ope r. mode se nd P Sx defines when the P437 sends a
signal to the remote station.

Direct.-dependent
If the distance protection function detects a fault in the forward direction,
the P437 sends a signal to the remote station.

Dist.-dependent
If the distance protection function detects a fault within extended zone 1,
the P437 sends a signal to the remote station.

Signals are transmitted through one or three channels, depending on the setting.
The response of the protection device in the remote station is determined by the
setting at PSIG: Oper. mode tri p PSx in the remote station.

P437/EN M/R-11-A // P437311650

3-225

P437

3 Operation

Direct.-dependent
After the protective signaling tripping time has elapsed, tripping occurs in
the phase(s) in which there is a receive signal and distance protection has
decided in favor of forward direction.

Detected fault type phase phase with ground will cause a 3-pole trip.
Detected fault type phase phase without ground will cause a 1-pole or
3-pole trip, depending on the setting at DIST: Trip zone 1 PP PSx.
Detected fault type 1p phase ground will cause a 1-pole or 3-pole trip,
depending on the setting at DI ST: Trip zone 1 PG PSx.

The receive signal is ignored during transient blocking.

Dist.-dependent
If the fault is located within the extended zone 1, then the protection device
of the remote station also decides in favor of a trip after the protective
signaling tripping time has elapsed and a receive signal is present. The
receive signal is ignored during transient blocking.
If for a 2pG fault or for an inter-system fault on double circuit lines there
are forward and backward (reverse) decisions present at the same time,
then the send signal is based on the selective Z1 decision only (not on
Z1e). This, however, is not the case with the setting PSIG: 3ended line
p rot PSx = Yes, because this functionality could result in an underfunctioning of the Protective Signaling in case of 3-ended line applications
(different lengths of the line parts, different feed-in power).

3-226

P437/EN M/R-11-A // P437311650

P437

3 Operation

GSCSG:
Send internal signal
304 002

PSIG:
Ready
[ 037 027 ]
PSIG:
Operating mode PSx
[ * ]
4: Release scheme

&
PSIG:
Oper. mode send PSx
[ * ]

PSIG:
No. telecom. ch. PSx
[ * ]

1: Direct.-dependent

1: 1 channel

2: Dist.-dependent

3: 3 channels

PSIG:
Release t. send PSx
[ * ]

&

PSIG:
Send
[ 012 243 ]

PSIG:
Send (signal)
[ 036 035 ]

PSIG:
Channel 1 send
[ 038 081 ]

PSIG:
Channel 2 send
[ 038 082 ]

PSIG:
Channel 3 send
[ 038 083 ]

& 1
DIST:
Fault forward / LS
[ 036 018 ]

&
1
& 1

DIST:
Fault forwd. / LS, A
[ 038 010 ]

&

DIST:
Dist. decis. Z1ze, A

& 1

303 652

DIST:
Fault forwd. / LS, B
[ 038 012 ]

&

DIST:
Dist. decis. Z1ze, B

& 1

303 653

DIST:
Fault forwd. / LS, C
[ 038 014 ]

&

DIST:
Dist. decis. Z1ze, C
303 654

Parameter

PSIG:
Operating mode PSx

PSIG:
Oper. mode send PSx

PSIG:
No. telecom. ch. PSx

PSIG:
Release t. send PSx

set
set
set
set

015
024
024
025

015
015
015
015

015
024
024
025

015
024
024
025

1
2
3
4

000
000
060
020

036
037
040
041

026
012
072
032

002
001
061
021

47Z8094A

Fig. 3-172: Protective signaling transmission with operating mode Signal comparison release scheme.

P437/EN M/R-11-A // P437311650

3-227

P437

3 Operation

DIST:
Trip zone 1 PG PSx
[ * ]
3: 3-pole

PSIG:
Trip channel 1

1: 1-pole

402 575

PSIG:
Trip channel 2

PSIG:
Oper. mode trip PSx
[ * ]

402 576

PSIG:
Trip channel 3

402 577

ARC:
(Re)close signal HSR
[ 038 007 ]

1: Direct.-dependent
DIST:
Trip zone 1 PP PSx
[ * ]
1: 1-pole leading phase

2: Dist.-dependent

2: 1-pole trailing phas


3: 3-pole
MAIN:
Phase sequence
[ 010 049 ]
1: A - B - C
2: A - C - B
PSIG:
Ready
[ 037 027 ]
PSIG:
Operating mode PSx
[ * ]
4: Release scheme
PSIG:
Timer stage elapsed
305 164
DIST:
Fault forward / LS
[ 036 018 ]
PSIG:
Receive (A) EXT
[ 036 048 ]
PSIG:
Frequ. monit. trigg. 305 152
PSIG:
Transient blocking 305 154
DIST:
Trip zone 1,ze
303 595
DIST:
Fault forwd. / LS, A
[ 038 010 ]
PSIG:
Channel 1 receive
[ 008 244 ]
PSIG:
Frequ. monit. ch.3051 169
PSIG:
Ch. 1 transient bl.
305 172
DIST:
Trip zone 1,ze, A

PSIG:
Trip enable
305 157

PSIG:
Trip enable, ch. 1
305 166

303 658

DIST:
Fault forwd. / LS, B
[ 038 012 ]
PSIG:
Channel 2 receive
[ 008 245 ]
PSIG:
Frequ. monit. ch. 2 305 170
PSIG:
Ch. 2 transient bl. 305 173
DIST:
Trip zone 1,ze, B 303 659
DIST:
Fault forwd. / LS, C
[ 038 014 ]
PSIG:
Channel 3 receive
[ 008 246 ]
PSIG:
Frequ. monit. ch. 3 305 171
PSIG:
Ch. 3 transient bl. 305 174
DIST:
Trip zone 1,ze, C 303 660

PSIG:
Trip enable, ch. 2
305 167

PSIG:
Trip enable, ch. 3
305 168

PSIG:
Receive

305 165

PSIG:
Receive (signal)
[ 038 029 ]

MAIN:
General starting
[ 036 000 ]

* Parameter
set 1
set 2
set 3
set 4

PSIG:
No. telecom. ch. PSx
[ * ]
3
1
3: 3 channels
1: 1 channel

* Parameter
set 1
set 2
set 3
set 4

PSIG:
Operating mode PSx

PSIG:
No. telecom. ch. PSx

015 000
024 000
024 060
025 020

015 026
024 012
024 072
025 032

PSIG:
Oper. mode trip PSx

DIST:
Trip zone 1 PG PSx

DIST:
Trip zone 1 PP PSx

015 107
015 108
015 113
015 114

011 050
011 051
011 052
011 053

011 054
011 055
011 056
011 057

47Z0295C

Fig. 3-173: Protective signaling trip and trip enable in operating mode 'Signal comparison release scheme'.

3.26.7.7

Operating Mode Blocking scheme


Zone extension in zone 1 of distance protection is a function of the setting at
PSI G: O pe r. m ode se nd PSx.

3-228

P437/EN M/R-11-A // P437311650

P437

3 Operation

Direct.-dependent
The measuring range of zone 1 of distance protection is not extended.

Dist.-dependent
In the idle state, the measuring range of zone 1 in both protection devices
is extended by the zone extension factor kze HSR (see Fig. 3-177, (p. 3232)). The distance protection trip in extended zone 1 is enabled in both
protection devices.

Dashed line: measuring range extended by zone extension factor kze HSR.

Nbw, a
Zone 1, prot.dev. a
Nbw, b
Zone 1, prot.dev. b

D5Z5055A

Fig. 3-174: Zone reaches with signal comparison blocking scheme.

The setting at PSI G: Ope r. mode s en d P Sx defines when the P437 sends a
signal to the remote station.

Direct.-dependent
If distance protection detects a fault in the backward (reverse) direction
or for a directional change for the transient blocking time (setting at
PSI G: t Block PSx), a signal is sent to the remote station.

Dist.-dependent
If the distance protection function detects a fault within zone 6 and if the
measured impedance lies in zone 6 (signal DI ST: I mpedance in zone
6), then the P437 sends a signal to the remote station. A signal is also sent
to the remote station during transient blocking.

Signals are transmitted through one or three channels, depending on the setting.
The response of the protection device in the remote station is determined by the
setting at PSI G: Oper. mode trip P Sx in the remote station.

Direct.-dependent
After the protective signaling tripping time has elapsed, tripping occurs in
the phase(s) in which there is no receive signal and distance protection has
decided in favor of forward direction. If transient blocking is operating, then
the receive signal will be ignored.

Dist.-dependent
After the protective signaling tripping time has elapsed, tripping occurs in
the phase(s) in which there is no receive signal and distance protection
detects a fault within extended zone 1. If transient blocking is operating,
then the receive signal will be ignored.

P437/EN M/R-11-A // P437311650

3-229

P437

3 Operation

GSCSG:
Send internal signal
304 002

PSIG:
Ready
[ 037 027 ]
PSIG:
Operating mode PSx
[ * ]
5: Blocking scheme
PSIG:
Oper. mode send PSx
[ * ]

PSIG:
No. telecom. ch. PSx
[ * ]

1
3

2
1: Direct.-dependent

1: 1 channel

2: Dist.-dependent

3: 3 channels

PSIG:
Release t. send PSx
[ * ]

PSIG:
Send
[ 012 243 ]
PSIG:
Send (signal)
[ 036 035 ]
DIST:
Fault backward / BS
[ 036 019 ]
PSIG:
Transient blocking

PSIG:
Channel 1 send
[ 038 081 ]

305 154

PSIG:
Channel 2 send
[ 038 082 ]

DIST:
Impedance in zone 6
[ 037 200 ]
DIST:
Fault backwd / BS, A
[ 038 011 ]
PSIG:
Ch. 1 transient bl.

PSIG:
Channel 3 send
[ 038 083 ]

305 172

DIST:
Impedance zone 6, A
303 661

DIST:
Fault backwd / BS, B
[ 038 013 ]
PSIG:
Ch. 2 transient bl.
305 173

DIST:
Impedance zone 6, B
303 662

DIST:
Fault backwd / BS, C
[ 038 015 ]
PSIG:
Ch. 3 transient bl.
305 174

DIST:
Impedance zone 6, C
303 663

Parameter

PSIG:
Operating mode PSx

PSIG:
Oper. mode send PSx

PSIG:
No. telecom. ch. PSx

PSIG:
Release t. send PSx

set
set
set
set

015
024
024
025

015
015
015
015

015
024
024
025

015
024
024
025

1
2
3
4

000
000
060
020

036
037
040
041

026
012
072
032

002
001
061
021

47Z8096A

Fig. 3-175: Protective signaling transmission with operating mode Signal comparison blocking scheme.

3-230

P437/EN M/R-11-A // P437311650

P437

3 Operation

DIST:
Trip zone 1 PG PSx
[ * ]
3: 3-pole

PSIG:
Trip channel 1

1: 1-pole

402 575

PSIG:
Trip channel 2

PSIG:
Oper. mode trip PSx
[ * ]

402 576

PSIG:
Trip channel 3

402 577

ARC:
(Re)close signal HSR
[ 038 007 ]

1: Direct.-dependent
DIST:
Trip zone 1 PP PSx

2: Dist.-dependent

[ * ]
1: 1-pole leading phase
2: 1-pole trailing phas
3: 3-pole
MAIN:
Phase sequence
[ 010 049 ]
1: A - B - C
2: A - C - B
PSIG:
Ready
[ 037 027 ]
PSIG:
Operating mode PSx
[ * ]
5: Blocking scheme
PSIG:
Timer stage elapsed305 164
DIST:
Fault forward / LS
[ 036 018 ]
PSIG:
Receive (A) EXT
[ 036 048 ]
PSIG:
Frequ. monit. trigg. 305 152
PSIG:
Transient blocking 305 154
DIST:
Trip zone 1,ze
303 595
DIST:
Fault forwd. / LS, A
[ 038 010 ]
PSIG:
Channel 1 receive
[ 008 244 ]
PSIG:
Frequ. monit. ch. 1 305 169
PSIG:
Ch. 1 transient bl. 305 172
DIST:
Trip zone 1,ze, A 303 658
DIST:
Fault forwd. / LS, B
[ 038 012 ]
PSIG:
Channel 2 receive
[ 008 245 ]
PSIG:
Frequ. monit. ch. 2 305 170
PSIG:
Ch. 2 transient bl. 305 173
DIST:
Trip zone 1,ze, B 303 659
DIST:
Fault forwd. / LS, C
[ 038 014 ]
PSIG:
Channel 3 receive
[ 008 246 ]
PSIG:
Frequ. monit. ch. 3 305 171
PSIG:
Ch. 3 transient bl. 305 174
DIST:
Trip zone 1,ze, C 303 660

PSIG:
Trip enable
305 157

PSIG:
Trip enable, ch. 1
305 166

PSIG:
Trip enable, ch. 2
305 167

PSIG:
Trip enable, ch. 3
305 168

PSIG:
Receive (signal)
[ 038 029 ]
* Parameter

MAIN:
General starting
[ 036 000 ]

set 1
set 2
set 3
set 4

PSIG:
No. telecom. ch. PSx
[ * ]
3
1
3: 3 channels
1: 1 channel

* Parameter
set 1
set 2
set 3
set 4

PSIG:
Operating mode PSx

PSIG:
No. telecom. ch. PSx

015 000
024 000
024 060
025 020

015 026
024 012
024 072
025 032

PSIG:
Oper. mode trip PSx

DIST:
Trip zone 1 PG PSx

DIST:
Trip zone 1 PP PSx

015 107
015 108
015 113
015 114

011 050
011 051
011 052
011 053

011 054
011 055
011 056
011 057

47Z0297C

Fig. 3-176: Protective signaling trip and trip enable in operating mode Signal comparison blocking scheme.

P437/EN M/R-11-A // P437311650

3-231

P437

3 Operation

3.26.8
PSIG:
Ready
[ 037 027 ]
PSIG:
Receive (A) EXT
[ 036 048 ]
PSIG:
Frequ. monit. trigg.
PSIG:
Transient blocking

Measuring Zone Extension of Zone 1 of Distance Protection

305 152
305 154

PSIG:
Channel 1 receive
[ 008 244 ]
PSIG:
Frequ. monit. ch. 1
PSIG:
Ch. 1 transient bl.
PSIG:
Channel 2 receive
[ 008 245 ]
PSIG:
Frequ. monit. ch. 2
PSIG:
Ch. 2 transient bl.
PSIG:
Channel 3 receive
[ 008 246 ]
PSIG:
Frequ. monit. ch. 3
PSIG:
Ch. 3 transient bl.

305 169
305 172

305 170
305 173

PSIG:
Z1 extended
[ 035 075 ]
305 171
305 174

PSIG:
Operating mode PSx
[ * ]
3: Zone extension
4: Release scheme
5: Blocking scheme

PSIG:
Oper. mode send PSx
[ * ]

PSIG:
Oper. mode trip PSx
[ * ]

1: Direct.-dependent

1: Direct.-dependent

2: Dist.-dependent

2: Dist.-dependent

Parameter

PSIG:
Operating mode PSx

PSIG:
Oper. mode send PSx

PSIG:
Oper. mode trip PSx

set 1
set 2
set 3
set 4

015 000
024 000
024 060
025 020

015 036
015 037
015 040
015 041

015 107
015 108
015 113
015 114

47Z0298A

Fig. 3-177: Zone extension by protective signaling.

3.26.9

Weak-Infeed Logic
The P437 features a weak-infeed logic function. Weak-infeed logic can either
be triggered by a binary signal input configured to PSIG: We ak inf. trig g. EXT
or by binary signal inputs configured to either P SIG: Receive (A) EXT or
PSI G: Receiv e (B) EXT.
The weak-infeed logic checks the phase-to-ground voltages to determine
whether they fall below the P SI G: V < we ak in fe e d PSx set threshold. If the
voltage in one phase falls below the set threshold, then a timer stage is started.
If PSIG: St art cond . tV < P Sx is set to V< & WI start, then the timer stage is
only started if both the undervoltage condition and the weak-infeed starting are
present. Once the set time has elapsed provided that the appropriate setting
has been selected a protective signaling trip is issued. The DIST: Trip zone 1
PG PSx setting is taken into account.
If the device has not issued its own protective starting the receive signal
(PS IG: R eceiv e ( A) EXT or PSIG: Re ceive ( B) EXT) is reset after the set
time delay (PSI G: tV < PSx + 100 ms). This will always ensure that weak-infeed
logic trips independently of the reset time of the send signal.

3-232

P437/EN M/R-11-A // P437311650

P437

3 Operation

The weak-infeed logic function is blocked by a 3-pole open circuit breaker, when
this status is either signaled by the CB auxiliary contacts or when the newly
implemented monitoring function detects this state from a 3p undervoltage
condition.
The phase selective starting signals are stored in RS flip-flops, which are only
reset after the received signal has ended. This excludes an over reaction during a
reset of its own starting when the received signal from the other end is still
present.
Detection
of
dead line by
undervoltage
criterion (only with
line side
VT connection)

V < 0.35Vnom/3

VA-G

5s

&

VB-G

PSIG:
Weak inf. blocked
310 015

VC-G

MAIN:
CB open 3p
[ 031 040 ]

Detection
of
dead line by
CB status contact

47Z1014C

Fig. 3-178: Enable for the weak-infeed logic, part 1.


PSIG:
Ready
[ 037 027 ]

&

PSIG:
Weak inf. ready
310 014

PSIG:
Weak inf. blocked
310 015

GSCSG:
Bl. PSIG weak infeed
304 003

DIST:
General starting
[ 036 240 ]

47Z1143B

Fig. 3-179: Enable for the weak-infeed logic, part 2.

P437/EN M/R-11-A // P437311650

3-233

P437

3 Operation

PSIG:
No. telecom. ch. PSx
[ * ]
1
3
1: 1 channel
3: 3 channels

PSIG:
Weak inf. trigg. EXT
[ 043 062 ]

&

[ 043 062 ] is
configured
to a
binary input

&
1
1

&
PSIG:
Receive
[ 006 036 ]

PSIG:
Ch. 1 receive weak inf.
310 011

&

1
1

PSIG:
Frequ. monit. trigg.
305 152

&

PSIG:
Channel 1 receive
[ 008 244 ]

310 012

&

PSIG:
Ch. 2 receive weak inf.

PSIG:
Frequ. monit. ch. 1
305 169

&

PSIG:
Ch. 3 receive weak inf.
310 013

PSIG:
Channel 2 receive
[ 008 245 ]

&

1
1

PSIG:
Frequ. monit. ch. 2
305 170

&

PSIG:
Channel 3 receive
[ 008 246 ]

PSIG:
Frequ. monit. ch. 3
305 171

Parameter

PSIG:
No. telecom. ch. PSx

set 1
set 2
set 3
set 4

015 026
024 012
024 072
025 032

47Z1011C

Fig. 3-180: Phase selective receive signals of the weak-infeed logic.

3-234

P437/EN M/R-11-A // P437311650

P437

3 Operation

ARC:
HSR oper. mode PSx
[ * ]
4: 3-pole (only for 1p)

&

ARC:
3p trip for 1p fault

310 019

MAIN:
Starting A
[ 036 001 ]

S 1 1

PSIG:
Ch. 1 receive weak inf.

&

50ms

PSIG:
Inhibit weak inf. A

PSIG:
Inhibit weak inf. B

PSIG:
Inhibit weak inf. C

310 016

R 1

310 011

MAIN:
CB closed A
[ 031 035 ]

S 1 1

MAIN:
Starting B
[ 036 002 ]

&
0

PSIG:
Ch. 2 receive weak inf.

R 1

310 017

50ms

310 012

MAIN:
CB closed B
[ 031 036 ]

1
MAIN:
Starting C
[ 036 003 ]

S 1 1
&
0

PSIG:
Ch. 3 receive weak inf.

R 1

310 018

50ms

310 013

MAIN:
CB closed C
[ 031 037 ]
*

Parameter

ARC:
HSR oper. mode PSx

set 1
set 2
set 3
set 4

015 051
024 025
024 085
025 045

47Z1203B

Fig. 3-181: Phase selective blocking of the weak-infeed logic.

If the ARC operating mode (A RC: HSR ope r . mode PSx) is set to 3-pole (only
for 1p) and ARC issues a 3-pole trip for this reason, then the weak infeed logic is
blocked.
This refinement was necessary based on the following application:
Assuming a weak infeed condition and the P437 receives a signal from the
remote end device because of a ground fault short-circuit, it then issues a singlepole PSIG trip as soon as weak infeed timer tV< has elapsed. According to the
operating mode being set to 3-pole (only for 1p) the ARC now converts this
single-pole trip into a 3-pole trip. As soon as the CBs are open on both sides, the
undervoltage condition becomes true for the remaining 2 phases. Consequently
the week-infeed trip condition becomes true for the 2 healthy phases, and PSIG
raised a 3-pole trip. This in turn leads to aborting the HSR.
In this example it is assumed that blocking of the weak infeed logic by CB auxiliary
contacts is not generally fast enough to prevent the 3-pole tripping.

P437/EN M/R-11-A // P437311650

3-235

P437

PSIG:
Weak inf. ready

3 Operation

PSIG:
V< weak infeed PSx
[ * ]

310 014

PSIG:
V< triggered

VA-G

310 020

VB-G
VC-G

PSIG:
tV< PSx

[ * ]

PSIG:
Start cond. tV< PSx
[

&

1
2

&

1: V<

PSIG:
Trip signal V< PSx

2: V< & WI start

[ * ]

&

0
1
0: No
1: Yes

PSIG:
Trip V<, A
[ 006 152 ]

&

&

&

&

PSIG:
Trip V<, B
[ 006 153 ]

&

&

PSIG:
Trip V<, C
[ 006 154 ]

&

PSIG:
Trip V<

PSIG:
Ch. 1 receive weak inf.
310 011

PSIG:
Inhibit weak inf. A
310 016

PSIG:
Ch. 2 receive weak inf.
310 012

PSIG:
Inhibit weak inf. B
310 017

PSIG:
Ch. 3 receive weak inf.
310 013

PSIG:
Inhibit weak inf. C
310 018

305 158

DIST:
Trip zone 1 PG PSx
[ * ]
1: 1-pole

&

3p-trip in case
of 2-/3-pole faults
or 3p-transfer trip,
with
setting
no 1p-trip

PSIG:
Weak infeed start.
[ 043 064 ]

Parameter

PSIG:
V< weak infeed PSx

PSIG:
Start cond. tV< PSx

PSIG:
tV< PSx

PSIG:
Trip signal V< PSx

DIST:
Trip zone 1 PG PSx

set 1

015 020

006 148

015 019

015 021

011 050

set 2

024 006

006 149

024 005

024 007

011 051

set 3

024 066

006 150

024 065

024 067

011 052

set 4

025 026

006 151

025 025

025 027

011 053

47Z8014A

Fig. 3-182: Tripping logic of the weak-infeed logic.

3.26.10

Echo Function
If operation with the echo function is desired, then the user may specify whether
the receive signal alone is to be employed in activating the echo pulse or
whether the receive signal and the triggering signal of the weak-infeed logic are
to be used. The conditions for activation of the echo pulse must persist for a
period in excess of the set time-delay, and distance protection starting must be

3-236

P437/EN M/R-11-A // P437311650

P437

3 Operation

absent for the echo pulse to be activated. This time-delay is ineffective with an
open circuit breaker (i.e. when the signal MA IN: CB ope n 3 p is present).
The echo pulse is then transmitted to the remote station for the set pulse
duration. Thereafter, the transmission of the receive signal is blocked for the set
pulse duration + 1 s. This prevents a permanent signal from being transmitted.
The echo function may be disabled.
If the P437 is operating with ground fault protective signaling and if directional
measurement of ground fault protection has been enabled, the echo signal will
be blocked if protective signaling (distance schemes) and ground fault protective
signaling are sharing a common transmission channel.

P437/EN M/R-11-A // P437311650

3-237

P437

3 Operation

GSCSG:
Ready
[ 043 057 ]
GSCSG:
Channel mode
[ 023 078 ]
2: Common channel
GFSC:
Direct.determ.enabl.
[ 043 061 ]
PSIG:
Op. delay echo PSx
[ * ]

PSIG:
Echo on receive PSx
[ * ]
0

1
2
0: Without
1: On receive
2: On receive & V<

PSIG:
No. telecom. ch. PSx
[ * ]
1
3

PSIG:
Pulse dur. echo PSx
[ * ]

1: 1 channel

PSIG:
Send
[ 012 243 ]

3: 3 channels
PSIG:
Send (signal)
[ 036 035 ]

PSIG:
V< triggered
305 162

PSIG:
Receive (A) EXT
[ 036 048 ]
PSIG:
Receive (B) EXT
[ 006 037 ]
PSIG:
Frequ. monit. trigg.

t+1s

PSIG:
Channel 1 send
[ 038 081 ]

1
0

305 152

PSIG:
A1 receive
EXT
[Chan.
038 091
]

t+1s

PSIG:
Channel 2 send
[ 038 082 ]

PSIG:
Chan. B1 receive EXT
[ 008 241 ]
PSIG:
Frequ. monit. ch. 1

t+1s

305 169

PSIG:
Channel 3 send
[ 038 083 ]

PSIG:
Chan. A2 receive EXT
[ 038 092 ]
PSIG:
Chan. B2 receive EXT
[ 008 242 ]
PSIG:
Frequ. monit. ch. 2

t+1s

305 170

PSIG:
Chan. A3 receive EXT
[ 038 093 ]
PSIG:
Chan. B3 receive EXT
[ 008 243 ]
PSIG:
Frequ. monit. ch. 3
305 171

DIST:
General starting
[ 036 240 ]
MAIN:
CB open 3p
[ 031 040 ]
*

Parameter

PSIG:
Echo on receive PSx

PSIG:
Op. delay echo PSx

PSIG:
Pulse dur. echo PSx

PSIG:
No. telecom. ch. PSx

set
set
set
set

015
024
024
025

015
024
024
025

015
024
024
025

015
024
024
025

1
2
3
4

003
002
062
022

022
008
068
028

023
009
069
029

026
012
072
032

47Z8097A

Fig. 3-183: Echo function.

3.26.11

Testing the Communication Channels


The communication link can be tested. For this purpose a 500 ms send signal is
issued through a binary signal input or by a setting parameter. It is extended by

3-238

P437/EN M/R-11-A // P437311650

P437

3 Operation

the reset time-delay of the send signal. The remote station receives this signal if
the transmission link is in order.

PSIG:
No. telecom. ch. PSx
[ * ]

&

1
3

PSIG:
Release t. send PSx

1: 1 channel

3: 3 channels
PSIG:
Test telecom. EXT
[ 036 038 ]

PSIG:
Send
[ 012 243 ]

1
PSIG:
Test telecom. USER
[ 015 009 ]

1
500ms

PSIG:
Send (signal)
[ 036 035 ]
PSIG:
Channel 1 send
[ 038 081 ]

PSIG:
Channel 2 send

[ 038 082 ]

0: don't execute
1: execute
PSIG:
Test telecom. 1 EXT
[ 038 085 ]

PSIG:
Channel 3 send

&

1
500ms

[ 038 083 ]
PSIG:
Test telecom. chann.

PSIG:
Test telecom. 1 USER
[ 015 027 ]

[ 034 016 ]

PSIG:
Test telecom. ch. 1

[ 034 026 ]

0: don't execute
1: execute
PSIG:
Test telecom. 2 EXT
[ 038 086 ]

1
500ms

1
500ms

PSIG:
Test telecom. 2 USER
[ 015 028 ]

PSIG:
Test telecom. ch. 2

&

[ 034 027 ]

0
1
0: don't execute
1: execute

PSIG:
Test telecom. 3 EXT
[ 038 087 ]

PSIG:
Test telecom. 3 USER
[ 015 029 ]

0
1
0: don't execute
1: execute

PSIG:
Test telecom. ch. 3

&

[ 034 028 ]

Parameter

PSIG:
No. telecom. ch. PSx

PSIG:
Release t. send PSx

set
set
set
set

015
024
024
025

015
024
024
025

1
2
3
4

026
012
072
032

002
001
061
021

47Z80ABA

Fig. 3-184: Testing the communication channels.

P437/EN M/R-11-A // P437311650

3-239

P437

3.27

3 Operation

Auto-Reclosing Control in the P437 (Function Group ARC)


After certain faults, the auto-reclosing control function (ARC) brings about
automatic reclosing of the line section that was interrupted by a protection
device.

3.27.1

ARC Operating Modes


The integral ARC function in the P437 offers the possibility of multiple reclosures.
When the ARC operating mode has been set accordingly, multiple reclosures first
begin with a high-speed reclosure (HSR). If the fault is not cleared after reclosure
by an HSR, then another attempt can be made to clear the fault with a timedelayed reclosure (TDR). Multiple reclosures using only TDRs are also possible if
the ARC operating mode is set accordingly.

ARC:
Operating mode PSx
[ * ]

ARC:
Operating mode PSx
[ * ]
1
2
3

1: HSR/TDR permitted

Parameter

ARC:
Operating mode PSx

2: TDR only permitted

set
set
set
set

015
015
015
015

3: Test HSR only permit

1
2
3
4

100
101
102
103

D5Z5095A

Fig. 3-185: Setting the ARC operating mode in the P437.

3-240

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.27.2

Enabling and Disabling the ARC Function


The function can be disabled or enabled using setting parameters or through
binary signal inputs.
The activation of the function is enabled generally (independently of parameter
subsets) via AR C: Ge ne ral e nabl e U SER. It is enabled as a function of a
parameter subset via A RC: E nabl e P Sx. If these enabling functions have been
activated, the auto-reclose control function can be disabled or enabled using
setting parameters or through appropriately configured binary signal inputs.
Parameters and configured binary signal inputs have equal status. If only the
AR C: Enable EXT function is assigned to a binary signal input, then ARC will be
enabled by a positive edge of the input signal and disabled by a negative edge. If
only the AR C: D isable EXT parameter has been assigned to a binary signal
input, then a signal at this input will have no effect.

P437/EN M/R-11-A // P437311650

3-241

P437

3 Operation

ARC:
General enable USER
[ 015 060 ]
0
1
0: No
1: Yes

ARC:
Enable PSx
[ * ]
ARC:
Enabled
[ 015 064 ]

0
1
0: No
1: Yes

INP:
Fct. assignm. U xxx
[ xxx xxx ]

U x1
U x2
U x3
U xx
Address

037 010

Address

037 011
ARC:
Ext./user enabled
[ 037 013 ]

ARC:
Enable EXT
[ 037 010 ]
ARC:
Enable USER
[ 003 134 ]

0
1
0: don't execute
1: execute
ARC:
Disable EXT
[ 037 011 ]
ARC:
Disable USER
[ 003 133 ]

0
1
0: don't execute
1: execute

Parameter

ARC:
Enable PSx

set
set
set
set

015
015
015
015

1
2
3
4

046
047
048
049

45Z5039A

Fig. 3-186: Disabling and enabling auto-reclosing control in the P437.

ARC is ready when the following conditions are satisfied:

3-242

Protection is activated (on).

ARC is not blocked.

No ARC cycle is running.

The circuit breaker must be capable of opening and closing again (CB
opening and closing mechanism ready).

The circuit breaker is in closed position. (Position scanning is optional.)

No automatic synchronism check cycle is running.


P437/EN M/R-11-A // P437311650

P437

3 Operation

ARC:
CB clos.pos.sig. PSx
[

]
0
1

0: Without

ARC:
CB closed

1: With

303 004

MAIN:
CB closed 3p EXT
[ 036 051 ]

ARC:
Ready
[ 004 068 ]

MAIN:
Protection active
306 001

ARC:
CB drive ready EXT
[ 004 066 ]
ARC:
Blocked
[ 004 069 ]

ARC:
Not ready
[ 037 008 ]

ASC:
Cycle running
[ 038 019 ]
ARC:
Cycle running
[ 037 000 ]

Parameter

ARC:
CB clos.pos.sig. PSx

set
set
set
set

015
024
024
025

1
2
3
4

050
024
084
044

D5Z5066A

Fig. 3-187: ARC readiness in the P437.

3.27.3

ARC Blocked
ARC will be blocked if one of the following conditions applies:

A manual close is carried out.

A manual open command is issued.

A switch to backup overcurrent time protection (BUOC) is made, but due to


the setting no ARC is to be carried out.

A trip signal is issued by ground fault (short-circuit) protection.

A ground fault (short-circuit) protection signaling trip occurs, but no autoreclosing is to occur.

A trip signal is issued by circuit breaker failure protection.

The binary signal input configured to ARC : Block ing EXT is triggered.

The HSR mode selection is to be made by external control (setting at


A RC : Contr ol vi a U SER = No) but no binary signal inputs have been
configured.

After all blocking conditions have dropped out, the relevant blocking time is
started, and when this time has elapsed, the block is canceled.

P437/EN M/R-11-A // P437311650

3-243

P437

3 Operation

ARC:
Blocked
[ 004 069 ]

ARC:
Enabled
[ 015 064 ]
SOTF:
ARC blocked
305 650

MAIN:
Manual trip signal
[ 034 017 ]

ARC:
Block. time int. PSx
[ * ]

MAIN:
Manual trip signal A
[ 034 047 ]
MAIN:
Manual trip signal B
[ 034 048 ]
MAIN:
Manual trip signal C
[ 034 049 ]

ARC:
Block. time running

[ 037 004 ]

SFMON:
BUOC active w/o ARC
[ 098 003]
CBF:
Trip signal
[ 040 026 ]
GFSC:
Trip
[ 039signal
092 ]
GSCSG:
Blocking ARC

ARC:
Block. time ext. PSx
[ * ]

304 008

ARC:
Blocking EXT
[ 036 050 ]

Parameter

ARC:
Block. time int. PSx

ARC:
Block. time ext. PSx

set 1
set 2
set 3
set 4

015 043
024 021
024 081
025 041

015 058
024 032
024 092
025 052

47Z11ADA

Fig. 3-188: ARC blocking.

3.27.4

ARC Tripping Times


If protective signaling is not ready, the HSR or TDR tripping times of the ARC
function are initiated by the general starting condition.
If the HSR operating mode (A RC : HSR ope r. m ode PSx) has been set to 1-/3pole, 3-pole or 3-pole (only for 1p) then the tripping times replace the timer
stage t1,ze of distance protection.
If the 1-pole operating mode has been set, a single-pole trip is issued once the
HSR tripping time has elapsed, or a multi-pole trip is issued after distance
protection grading time (depending on the zone) has elapsed or after the BUOC
timer stages have elapsed.

3-244

P437/EN M/R-11-A // P437311650

P437

3 Operation

ARC:
Sig.interr. CB trip
[ 036 040 ]
ARC:
Dead time running
[ 037 002 ]
ARC:
(Re)close request
[ 037 077 ]
ASC:
Operat.time running
[ 037 093 ]
ARC:
Cycle running
[ 037 000 ]
ARC:
Ready
[ 004 068 ]
PSIG:
Not ready
[ 037 028 ]
SFMON:
BUOC active with ARC
[ 098 004 ]

ARC:
Trip time HSR PSx
[ * ]

ARC:
TDR

ARC:
Trip time HSR PSx
[ * ]

303 006

MAIN:
General starting
[ 036 000 ]

ARC:
Trip time elapsed
303 003

ARC:
Trip time TDR PSx
[ * ]

Parameter

ARC:
Trip time HSR PSx

ARC:
Trip time TDR PSx

set
set
set
set

015
024
025
025

015
024
025
025

1
2
3
4

072
040
000
060

073
041
001
061

D5Z5068A

Fig. 3-189: ARC tripping times in the P437.

3.27.5

Starting the ARC Cycle


When the ARC function is ready, an ARC cycle is started by one of the following
functions:

The general starting state formed internally or the general starting signal of
a parallel protection device, provided that a binary signal input has been
configured accordingly.

A trip without general starting, such as through the protective signaling


direct transfer trip or through the function MA IN: Trans fe r t rip. EXT.

A backup overcurrent-time protection trip (BUOC trip), provided that the


ARC is to be activated by the BUOC function.

The trip signal of ground fault (short-circuit) protection signaling, provided


that the ARC is to be activated by ground fault protection signaling.

The trip signal of an external protection device, provided that the


parameters of this device have been set accordingly (A RC : Parallel t rip
PSx).

A test HSR.

The ARC cycle is completed after the last reclaim time has elapsed.

3.27.6

High-Speed Reclosure (HSR)


When the ARC cycle starts, operative times 1 and 2 are started. The starting
conditions for the ARC cycle must drop out while the operative times are
elapsing. This means that the circuit breaker must have opened so that the dead
time is started. If both operative times are set at 25 ms, then ARC will not be
ready in the event of starting; in the event of a trip, the reclaim time is started.

P437/EN M/R-11-A // P437311650

3-245

P437

3 Operation

After starting drops out without a subsequent trip, ARC is immediately ready
again. Operative time 1 has priority over operative time 2. Selection of the HSR
operating mode determines which dead time is started. The following settings
are possible:
3.27.6.1

HSR Operating Modes


ARC : HSR oper. mode P Sx

1-pole

1-/3-pole

3-pole

3-pole (only for 1p)

With the operating mode 3-pole (only for 1p) only a three-pole HSR will result
from single-pole ground faults.

ARC:
HSR oper. mode PSx
[ * ]

1:
2:
3:
4:

ARC:
HSR oper. mode PSx
[ * ]

1: 1-pole

2: 1-/3-pole

3: 3-pole

4: 3-pole (only for 1p)

1-pole
1-/3-pole
3-pole
3-pole (only for 1p)

Parameter

ARC:
HSR oper. mode PSx

set
set
set
set

015
024
024
025

1
2
3
4

051
025
085
045

45Z8094

Fig. 3-190: Setting the HSR operating mode in the P437.

3.27.6.1.1

Selecting Operating Mode via Binary Signal Inputs


The operating mode can be selected via binary signal inputs, if this selection
mode has been enabled (A RC: Con trol vi a USE R = No) and the required
binary signal inputs have been configured.
When using binary signal inputs the operating mode is set according to the
following terms:

3-246

P437/EN M/R-11-A // P437311650

P437

3 Operation

ARC: 1p-HSR enable


EXT

ARC: 3p-HSR enable


EXT

ARC: 3p-HSR(1p)
enab. EXT

HSR operating mode

ARC is blocked. (RRC


and TDR are also
blocked.)

Only single-pole HSR


permitted under 1p trip
condition.
Three-pole tripping is
always final.

Three-pole HSR for all


types of fault.

Trip-dependent HSR:
single-pole HSR with
single-pole trip decision,
three-pole HSR with
three-pole trip decision

0 or 1

Three-pole HSR only


with single-pole trip
decision.

0 or 1

Three-pole HSR for all


types of fault.

Logic input signals may be fed from physical binary signal inputs, signal
assignment within the LOGIC or through the InterMiCOM communication
interface. If not all the available operating modes are required, it is not necessary
to configure all 3 signals. Signals that are not configured are internally used with
their default value 0.
3.27.6.1.2

HSR Operating Mode 2


The setting at A RC : HSR oper. mode 2 P Sx determines whether starting (of
distance or backup overcurrent-time protection) or a trip will be used for a singleor three-pole HSR. If the setting is Trip-dependent, then trip decisions will be
used as the criterion. If the setting is Start-dependent, then starting decisions will
also be used.

P437/EN M/R-11-A // P437311650

3-247

P437

3 Operation

ARC:
HSR oper. mode PSx
[ * ]
1
2
3
4
1: 1-pole
2: 1-/3-pole
3: 3-pole
4: 3-pole (only for 1p)

ARC:
HSR oper. mode 2 PSx
[ * ]

Parameter

ARC:
HSR oper. mode PSx

ARC:
HSR oper. mode 2 PSx

set 1
set 2
set 3
set 4

015 051
024 025
024 085
025 085

015 044
024 022
024 082
025 042

1
2
1: Trip-dependent
2: Start-dependent

47Z1067A

Fig. 3-191: Setting the HSR operating mode and HSR operating mode 2.

3.27.6.1.3

1-pole
If HSR operating mode 2 is set for Start-dependent then the single-pole HSR is
only executed if there is a single-pole starting signal when the trip occurs. If
there is a multipole starting signal when the trip occurs, then there is a threepole final trip, and the reclaim time is started.
If the setting is Trip-dependent then the HSR is only executed if a single-pole trip
decision is reached. In the event of a three-pole trip, no HSR is executed, and
instead a final trip occurs. In addition, the HSR is started by a single-pole test
HSR.
A single-pole trip can occur as the result of the following protective functions:

Distance protection in impedance zone 1 or extended zone 1.

Backup overcurrent-time protection (BUOC).

Protective signaling.

Ground fault (short-circuit) protection signaling.

The integrated phase selection logic (see function MAIN).

A parallel protective device.

If the HSR is started by a parallel protective device, protective signaling, ground


fault (short-circuit) protection signaling, or the phase selection logic and if the
P437 has not started, then the trip is always used as the criterion for the HSR
irrespective of whether the setting is Start-dependent or Trip-dependent.
The single-pole dead time (A RC: Dead time 1p PSx) is started if the starting
conditions drop out while operative time 1 is elapsing. After the dead time
elapses, a close request is sent to the automatic synchronism check function
(ASC), and a close command is issued immediately, without a check by the ASC.
If the starting conditions for the ARC cycle drop out after operative time 1 has
elapsed but during operative time 2, then the maximum dead time (ARC: De ad
t im e max PSx) is started. When the dead time is started, a close request is
sent to the ASC. The ASC checks to determine whether reclosure is possible. If a
positive decision is reached during the ASC operative time and while the dead
time is elapsing, then there is a close enable, and the close command is issued.

3-248

P437/EN M/R-11-A // P437311650

P437

3 Operation

If the ASC function determines that reclosing may not occur (depending on the
setting or with ASC disabled or blocked), then the reclaim time is started and a
three-pole trip occurs (final trip).
Plausibility check on single-pole HSR: If pole selective status signals have
been configured (see Section 3.12.8, (p. 3-92)) then the device will check that
just this CB contact will be opened during a single-pole HSR. The single-pole HSR
is terminated and a three-pole trip command is issued when at least one further
CB contact is opened. This trip command is final when the discrimination time
has elapsed (timer stage ARC: tDis crim. P Sx) or if this timer stage is set to
0 s. The same procedure is carried out should the multiple signal MAI N: CB
open 3 p EXT occur during the dead time of a single-pole HSR.

P437/EN M/R-11-A // P437311650

3-249

P437

3 Operation

Trip dur. op. time 1

Trip dur. op. time 2

Close reject

ARC:
Ready
[ 004 068 ]

ARC:
Cycle running
[ 037 000 ]

ARC:
Oper. time 1 running
[ 037 005 ]
ARC:
Oper. time 2 running
[ 037 065 ]
MAIN:
Trip signal 1, 1p
[ 037 252 ]

ARC:
Dead time 1p running
[ 037 066 ]

ARC:
Max. dead time runn.
[ 037 069 ]
ARC:
Dead time running
[ 037 002 ]
ARC:
(Re)close request
[ 037 077 ]

ASC:
Operat.time running
[ 037 093 ]
ASC:
Close enable
[ 037 083 ]
ARC:
(Re)close signal HSR
[ 037 007 ]

MAIN:
Close command
[ 037 009 ]
ARC:
3p final trip
[ 036 043 ]
ARC:
Reclaim time running
[ 036 042 ]
ARC:
Sig.interr. CB trip
[ 036 040 ]
Parameter
set 1
set 2
set 3
set 4

ARC:
Operative time 1 PSx
015 066
024 035
024 095
025 055

ARC:
Operative time 2 PSx
015 083
024 042
025 002
025 062

MAIN:
Close cmd.pulse time

ARC:
Dead time 1p PSx
015 055
024 029
024 089
025 049

[ 015 067 ]

4
ARC:
Dead time max PSx
015 084
024 043
025 003
025 063

5
ASC:
Operative time PSx
018 010
077 034
078 034
079 034

7
ARC:
Reclaim time PSx
015 054
024 028
024 088
025 048
47Z1061A

Fig. 3-192: Signal flow for the 1-pole operating mode.

3.27.6.1.4

1-/3-pole
If HSR operating mode 2 is set for Start-dependent then a single-pole HSR is
executed if there is a single-pole starting signal when the trip occurs. If there is a
multipole starting signal when the trip occurs, then a three-pole HSR is executed.

3-250

P437/EN M/R-11-A // P437311650

P437

3 Operation

With the Trip-dependent setting, the decision as to whether a single- or threepole HSR will be executed is contingent upon the trip decisions. In addition, a
single- or three-pole HSR is started by a corresponding test HSR.
A single-pole trip can occur as the result of the following protective functions:

Distance protection in impedance zone 1 or extended zone 1.

Backup overcurrent-time protection (BUOC).

Protective signaling.

Ground fault (short-circuit) protection signaling.

The integrated phase selection logic (see function MAIN).

A parallel protective device.

If the HSR is started by a parallel protective device, protective signaling, ground


fault (short-circuit) protection signaling or the phase selection logic and if the
P437 has not started, then the trip is always used as the criterion for the HSR
irrespective of whether the setting is Start-dependent or Trip-dependent.
If the conditions for a single-pole HSR are satisfied the single-pole dead time
(ARC : Dead t ime 1p PSx) is started if the starting conditions for an ARC cycle
drop out while operative time 1 is elapsing. After the dead time elapses, a close
request is sent to the automatic synchronism check function (ASC), and a close
command is issued immediately, without a check by the ASC.
If the conditions for a three-pole HSR are satisfied the three-pole dead time
(ARC : Dead t ime 3p runn in g) is started if the starting conditions for an ARC
cycle drop out while operative time 1 is elapsing. After the dead time has
elapsed, a close request is sent to the ASC. If ASC is to be activated
(ASC : Act ive for HSR PSx) it first checks to determine whether reclosure is
possible. If a positive decision is reached during the ASC operative time, then
there is a close enable, and the close command is issued.
If ARC is disabled or blocked a close command may be issued immediately
(ASC : C los.re j.w.bl ock P Sx = No).
If the starting conditions for an ARC cycle drop out after operative time 1 has
elapsed but during operative time 2, then the maximum dead time (A RC : Dead
time ma x PSx) is started. This occurs with both single-pole and three-pole trips.
When the dead time is started, a close request is sent to the ASC. The ASC
checks to determine whether reclosure is possible. If a positive decision is
reached during the ASC operative time and while the dead time is elapsing, then
there is a close enable, and the close command is issued.
If the ASC function determines that reclosing may not occur or if the ASC
function is not ready, then the reclaim time is started after the dead time has
elapsed, and three-pole tripping occurs (final trip).
Plausibility check on single-pole HSR: If pole selective status signals have
been configured (see Section 3.12.8, (p. 3-92)) then the device will check that
just this CB contact will be opened during a single-pole HSR. The single-pole HSR
is terminated and a three-pole trip command is issued when at least one further
CB contact is opened. This trip command is final when the discrimination time
has elapsed (timer stage ARC: tDis crim. P Sx) or if this timer stage is set to
0 s. The dead time for the three-pole HSR is triggered when the discrimination
timer stage is still running. The same procedure is carried out should the multiple
signal MAI N: C B ope n 3p E XT occur during the dead time of a single-pole
HSR.

P437/EN M/R-11-A // P437311650

3-251

P437

3 Operation

1-pole trip

3-pole trip

ARC:
Ready
[ 004 068 ]

ARC:
Cycle running
[ 037 000 ]

ARC:
Oper. time 1 running
[ 037 005 ]
ARC:
Oper. time 2 running
[ 037 065 ]
MAIN:
Trip signal 1, 1p
[ 037 252 ]
MAIN:
Trip signal 1, 3p
[ 037 253 ]

ARC:
Dead time 1p running
[ 037 066 ]

ARC:
Dead time 3p running
[ 037 067 ]
ARC:
Dead time running
[ 037 002 ]
ARC:
(Re)close request
[ 037 077 ]
ASC:
Operat.time running
[ 037 093 ]
ASC:
Close enable
[ 037 083 ]
ARC:
(Re)close signal HSR
[ 037 007 ]
MAIN:
Close command
[ 037 009 ]
ARC:
Reclaim time running
[ 036 042 ]
ARC:
Sig.interr. CB trip
[ 036 040 ]
Parameter
set 1
set 2
set 3
set 4

ARC:
Operative time 1 PSx
015 066
024 035
024 095
025 055

ARC:
Operative time 2 PSx
015 083
024 042
025 002
025 062

3
ARC:
Dead time 1p PSx
015 055
024 029
024 089
025 049

4
ARC:
Dead time 3p PSx
015 056
024 030
024 090
025 050

5
ASC:
Operative time PSx
018 010
077 034
078 034
079 034

MAIN:
[ 015 067 ]
Close cmd.pulse time

7
ARC:
Reclaim time PSx
015 054
024 028
024 088
025 048
47Z1062A

Fig. 3-193: Signal flow with the operating mode 1-/3-pole, tripping during operative time 1.

3-252

P437/EN M/R-11-A // P437311650

P437

3 Operation

Trip dur. op. time 2

Close reject

ARC:
Ready
[ 004 068 ]

ARC:
Cycle running
[ 037 000 ]

ARC:
Oper. time 1 running
[ 037 005 ]

ARC:
Oper. time 2 running
[ 037 065 ]
MAIN:
Trip signal 1, 1p
[ 037 252 ]
MAIN:
Trip signal 1, 3p
[ 037 253 ]
ARC:
Max. dead time runn.
[ 037 069 ]

ARC:
Dead time running
[ 037 002 ]

ARC:
(Re)close request
[ 037 077 ]
ASC:
Operat.time running
[ 037 093 ]

ASC:
Close enable
[ 037 083 ]
MAIN:
Close command
[ 037 009 ]

ARC:
3p final trip
[ 036 043 ]
ARC:
Reclaim time running
[ 036 042 ]

ARC:
Sig.interr. CB trip
[ 036 040 ]

Parameter
set 1
set 2
set 3
set 4

ARC:
Operative time 1 PSx
015 066
024 035
024 095
025 055

ARC:
Operative time 2 PSx
015 083
024 042
025 002
025 062

MAIN:
Close cmd.pulse time

ARC:
Dead time max PSx
015 084
024 043
025 003
025 063
[ 015 067 ]

ASC:
Operative time PSx
018 010
077 034
078 034
079 034

ARC:
Reclaim time PSx
015 054
024 028
024 088
025 048
47Z1063B

Fig. 3-194: Signal flow with the operating mode 1-/3-pole, tripping during operative time 2, and close rejection.

3.27.6.1.5

3-pole
The three-pole HSR is executed both with a single-pole trip and a three-pole trip
irrespective of whether the setting is Start-dependent or Trip-dependent. If the

P437/EN M/R-11-A // P437311650

3-253

P437

3 Operation

setting is Trip-dependent then there is a three-pole trip transfer in the event of a


single-pole trip.
The three-pole dead time (AR C: De ad ti me 3p PSx) is started if the starting
conditions for an ARC cycle drop out while operative time 1 is elapsing. After the
dead time has elapsed, a close request is sent to the automatic synchronism
check function (ASC). If ASC is to be activated (A SC: Active f or HSR PS x) it
first checks to determine whether reclosure is possible. If a positive decision is
reached during the ASC operative time, then there is a close enable, and the
close command is issued.
If the ASC is disabled or deactivated, or if its decisions are to be ignored, then a
close command is issued immediately (A SC : C los .rej.w.block PSx = No i.e.
close rejection when blocked).
If the starting conditions for an ARC cycle drop out after operative time 1 has
elapsed but during operative time 2 then the maximum dead time (ARC: Dead
t ime max PSx) is started. When the dead time is started, a close request is
sent to the ASC. The ASC checks to determine whether reclosure is possible. If a
positive decision is reached during the ASC operative time and while the
maximum dead time is elapsing, then there is a close enable, and the close
command is issued.
If the ASC function determines that reclosing may not occur, then the reclaim
time is started and the final trip signal is issued.

3-254

P437/EN M/R-11-A // P437311650

P437

3 Operation

Trip dur. op. time 1

Trip dur. op. time 2

Close reject

ARC:
Ready
[ 004 068 ]

ARC:
Cycle running
[ 037 000 ]

ARC:
Oper. time 1 running
[ 037 005 ]
ARC:
Oper. time 2 running
[ 037 065 ]
MAIN:
Trip signal 1, 3p
[ 037 253 ]
ARC:
Dead time 3p running
[ 037 067 ]

ARC:
Max. dead time runn.
[ 037 069 ]
ARC:
Dead time running
[ 037 002 ]
ARC:
(Re)close request
[ 037 077 ]
ASC:
Operat.time running
[ 037 093 ]
ASC:
Close enable
[ 037 083 ]
ARC:
(Re)close signal HSR
[ 037 007 ]

MAIN:
Close command
[ 037 009 ]
ARC:
3p final trip
[ 036 043 ]
ARC:
Reclaim time running
[ 036 042 ]
ARC:
Sig.interr. CB trip
[ 036 040 ]
Parameter
set 1
set 2
set 3
set 4

ARC:
Operative time 1 PSx
015 066
024 035
024 095
025 055

ARC:
Operative time 2 PSx
015 083
024 042
025 002
025 062

MAIN:
Close cmd.pulse time

ARC:
Dead time 3p PSx
015 056
024 030
024 090
025 050
[ 015 067 ]

ARC:
Dead time max PSx
015 084
024 043
025 003
025 063

ASC:
Operative time PSx
018 010
077 034
078 034
079 034

ARC:
Reclaim time PSx
015 054
024 028
024 088
025 048
47Z1064A

Fig. 3-195: Signal flow for the operating mode 3-pole.

3.27.6.1.6

3-pole (only for 1p)


With this operating mode no further trip command is issued when a HSR cycle is
terminated (a 3-pole trip has already occurred); only the signal MA IN: F inal
trip = Yes is generated.

P437/EN M/R-11-A // P437311650

3-255

P437
3.27.6.1.7

3 Operation

All HSR Operating Modes


The following applies to all HSR operating modes:
Should the circuit breaker fail to clear the fault within the operative times, the
reclaim time will be started and a three-pole trip will occur (final trip). If the
operative times elapse without a trip decision, then the ARC is immediately ready
again as soon as the general starting condition has dropped out.

3.27.6.2

Test HSR
A single- or three-pole test HSR can be carried out using setting parameters or
through appropriately configured binary signal inputs. If a single-pole test HSR is
triggered in the 3-pole operating mode, then a three-pole trip occurs.

3-256

P437/EN M/R-11-A // P437311650

P437

3 Operation

MAIN:
General starting
[ 036 000 ]
MAIN:
Gen. trip command 1
[ 036 071 ]
MAIN:
Gen. trip command 2
[ 036 022 ]
ARC:
Ready
[ 004 068 ]
ARC:
Operating mode PSx
[ * ]
2: TDR only permitted

ARC:
Reject test HSR
[ 036 055 ]

ARC:
HSR oper. mode PSx
[ * ]
1: 1-pole

ARC:
Test-HSR A USER
[ 011 063 ]
ARC:
Test HSR A, internal

303 011

1
0: don't execute
1: execute
ARC:
Test HSR A EXT
[ 037 014 ]

ARC:
Test HSR A
[ 034 020 ]

ARC:
Test-HSR B USER
[ 011 064 ]
ARC:
Test HSR B, internal

303 012

1
0: don't execute
1: execute

ARC:
Test HSR B
[ 034 021 ]

ARC:
Test HSR B EXT
[ 037 015 ]
ARC:
Test-HSR C USER
[ 011 065 ]

ARC:
Test HSR C, internal

303 013

1
0: don't execute
1: execute
ARC:
Test HSR C EXT
[ 037 016 ]

ARC:
Test HSR C
[ 034 022 ]

ARC:
Test HSR A-B-C USER
[ 011 066 ]

0
1
0: don't execute
1: execute

ARC:
Test HSR A-B-C
[ 034 023 ]

ARC:
Test HSR A-B-C EXT
[ 037 017 ]
ARC:
HSR oper. mode PSx
[ * ]
3: 3-pole

Parameter

ARC:
Operating mode PSx

ARC:
HSR oper. mode PSx

set
set
set
set

015
015
015
015

015
024
024
025

1
2
3
4

100
101
102
103

051
025
085
045

47Z01AFA

Fig. 3-196: Test HSR.

3.27.7

Time-Delay Reclosure (TDR) in the P437


A TDR may occur after an HSR if reclosure has occurred as the result of the HSR
or if the operating mode set for the ARC allows only TDRs. This is possible only if
the setting for A RC : No. pe rm it. TDR P Sx (number of permitted TDRs) is not

P437/EN M/R-11-A // P437311650

3-257

P437

3 Operation

zero. The TDR is always a three-pole process. This means that three-pole transfer
tripping will occur in the event of a single-pole trip.
The TDR is started if either a new general starting condition or the trip of an
external protection device (if configured accordingly) occurs while the reclaim
time is elapsing. Operative times 1 and 2 are started. If the starting conditions
for the TDR drop out while operative time 1 or 2 is elapsing, then the TDR dead
time is started. After the dead time has elapsed, a close request is sent to the
automatic synchronism check function (ASC). The ASC checks to determine
whether reclosure is possible. If a positive decision is reached during the ASC
operative time, then there is a close enable, and the close command is issued.
If ASC is disabled or blocked a close command may be issued immediately
(ASC: C los.re j.w.bl ock P Sx = No i.e. close rejection when blocked).
If the ASC function determines that reclosing may not occur, then a final trip
occurs after the ASC operative time has elapsed, and the ARC reclaim time is
started.
If the fault is still present even after another reclosing, the TDR can be started
again. This process can be repeated as often as allowed by the number of
permitted TDRs. If the fault is still present after that, then a final trip occurs.

3-258

P437/EN M/R-11-A // P437311650

P437

3 Operation

Reclosure

Close reject

ARC:
Ready
[ 004 068 ]
ARC:
Cycle running
[ 037 000 ]

MAIN:
Close command
[ 037 009 ]

ARC:
Reclaim time running
[ 036 042 ]
MAIN:
General starting
[ 036 000 ]

ARC:
Oper. time 1 running
[ 037 005 ]
ARC:
Oper. time 2 running
[ 037 065 ]

MAIN:
Trip signal 1, 3p
[ 037 253 ]

ARC:
Dead time TDR runn.
[ 037 003 ]

ARC:
Dead time running
[ 037 002 ]

ARC:
(Re)close request
[ 037 077 ]

ASC:
Operat.time running
[ 037 093 ]

ASC:
Close enable
[ 037 083 ]
ARC:
(Re)close signal TDR
[ 037 006 ]

ARC:
Sig.interr. CB trip
[ 036 040 ]

Parameter
set 1
set 2
set 3
set 4

ARC:
Reclaim time PSx
015 054
024 028
024 088
025 048

ARC:
Operative time 1 PSx
015 066
024 035
024 095
025 055

ARC:
Operative time 2 PSx
015 083
024 042
025 002
025 062

ARC:
TDR dead time PSx
015 057
024 031
024 091
025 051

ASC:
Operative time PSx
018 010
077 034
078 034
079 034

MAIN:
Close cmd.pulse time
[ 015 067 ]

47Z1065A

Fig. 3-197: Signal sequence with time-delayed reclosure (TDR).

3.27.8

Rapid Reclosure (RRC)


Rapid reclosure (RRC) operates along with HSR or TDR. If the P437 carries out
appropriate measurements and concludes that the line is carrying voltage and
that the line voltages are healthy, then reclosing is carried out by RRC which in
turn reduces the dead times of HSR or TDR. For this, VTs must be connected on
the line side.

P437/EN M/R-11-A // P437311650

3-259

P437

3 Operation

If the setting at MAI N: Ne utr.pt. tre at. PSx is Low-imped. grounding, then
both phase-to-ground and phase-to-phase voltages are checked. If the setting is
either Isol./res.w.start.PG, Isol./res.w/o st. PG or Short-durat. ground., then only
the phasetophase voltages are checked.

ARC:
Enable RRC PSx
[ * ]

0
1
0: No
1: Yes

ARC:
V> RRC PSx
[ * ]
ARC:
V> for RRC triggered

VA-G3

VA-G

303 014

VB-G3

VB-G
VC-G

VC-G3

MAIN:
Neutr.pt. treat. PSx
[ * ]
1: Low-imped. grounding

* Parameter
set
set
set
set

1
2
3
4

ARC:
Enable RRC PSx

ARC:
V> RRC PSx

MAIN:
Neutr.pt. treat. PSx

015
024
025
025

015
024
025
025

010
001
001
001

085
044
004
064

087
046
006
066

048
076
077
078

49Z64AHA

Fig. 3-198: Voltage monitoring for RRC.

If the starting conditions for rapid reclosing drop out during operative time 1, the
RRC timer stage tRRC is started. After the timer stage has elapsed, the P437
checks to determine whether the voltages measured by distance protection were
greater than or equal to the set threshold value (A RC: V> RRC PSx) during the
last 100 ms. If this was the case, then a close request is sent to the automatic
synchronism check function (ASC). The ASC response depends on whether the
conditions for a single- or three-pole HSR are satisfied.
If the conditions for a single-pole HSR are satisfied then a close command is
immediately issued.
If the conditions for a three-pole HSR or TDR were satisfied the ASC checks to
determine whether reclosing can occur. If the ASC decision is positive, a close
enable and then a close command are issued. If reclosing is not permitted, there
is a final trip.
If the ASC is disabled or deactivated or if its decisions are to be ignored, then the
close request is immediately acknowledged and a close command is issued, even
in the case of a three-pole trip.
If it is determined after timer stage tRRC has elapsed that the voltages were not
greater or equal to the set threshold (ARC: V > RRC PSx), then the ARC cycle is
continued by the HSR or TDR.

3-260

P437/EN M/R-11-A // P437311650

P437

3 Operation

1-pole trip

3-pole trip

Close reject

ARC:
Ready
[ 004 068 ]

ARC:
Cycle running
[ 037 000 ]

ARC:
Oper. time 1 running
[ 037 005 ]

ARC:
Oper. time 2 running
[ 037 065 ]
MAIN:
Trip signal 1, 1p
[ 037 252 ]
MAIN:
Trip signal 1, 3p
[ 037 253 ]
ARC:
tRRC running
303 015

ARC:
V> for RRC triggered
303 014

ARC:
(Re)close request
[ 037 077 ]

ASC:
Operat.time running
[ 037 093 ]

ASC:
Close enable
[ 037 083 ]
MAIN:
Close command
[ 037 009 ]

ARC:
3p final trip
[ 036 043 ]

ARC:
Reclaim time running
[ 036 042 ]

ARC:
Sig.interr. CB trip
[ 036 040 ]

Parameter
set 1
set 2
set 3
set 4

ARC:
Operative time 1 PSx
015 066
024 035
024 095
025 055

ARC:
Operative time 2 PSx
015 083
024 042
025 002
025 062

ARC:
tRRC PSx
015 086
024 045
025 005
025 065

ASC:
Operative time PSx
018 010
077 034
078 034
079 034

ARC:
Reclaim time PSx
015 054
024 028
024 088
025 048

Minimum time 100 ms


MAIN:
Close cmd.pulse time

[ 015 067 ]
47Z1066A

Fig. 3-199: Signal sequence for rapid reclosure (RRC).

3.27.9

Secondary Fault Treatment in the P437


If a repeat trip occurs in another phase during the dead time, then this is referred
to as a secondary fault and results in three-pole tripping. This is carried out as a

P437/EN M/R-11-A // P437311650

3-261

P437

3 Operation

three-pole trip. The response of the ARC to a secondary fault is a function of


whether the secondary fault occurs during a high-speed reclosure (HSR), a timedelay reclosure (TDR) or a rapid reclosure (RRC).
Secondary fault treatment during HSR
If a secondary fault occurs during an HSR, then the response is a function of the
HSR operating mode that has been set.

AR C: HSR ope r. mode P Sx = 1-pole


If a trip starts during the single-pole dead time in a different phase than at
the beginning of the ARC cycle, then tripping is three-pole (final trip) and
the reclaim time is started. Reclosing does not occur.
If starting or a trip occurs again during the single-pole dead time in the
same phase as at the beginning of the ARC cycle, the ARC cycle is
continued. The ARC cycle is terminated only if the starting signal or the trip
are still present immediately before the close command is issued.
If a secondary fault occurs in the same phase while the maximum dead
time is elapsing, the ARC cycle is terminated normally. If a secondary fault
occurs in a different phase, there is a three-pole trip transfer and the
reclaim time is started.

ARC : HSR op er. mode P Sx = 1-/3-pole


If starting or a trip occurs again during the single-pole dead time in the
same phase as at the beginning of the ARC cycle, the ARC cycle is
continued. The ARC cycle is terminated only if a starting signal or trip is still
present immediately before the close command is issued.
If a secondary fault occurs during the single-pole dead time, then operative
time 1 is started. The single-pole dead time continues. If the secondary
fault's starting condition and trip drop out while operative time 1 is
elapsing, the P437 checks to determine whether the fault change occurred
during the course of the time set at A RC : tDiscrim. PSx, which is started
with the single-pole dead time. If this is the case, a switch is made to the
three-pole dead time, and the ARC cycle is terminated as in the case of a
three-pole trip. If the fault change occurred after the tDiscrim. time had
elapsed then final tripping occurs and the reclaim time is started.
A secondary fault during the course of the three-pole dead time is ignored.
Termination of the ARC cycle only occurs if the starting signal or trip has
not yet dropped out immediately before the close command is issued.
If a secondary fault occurs while the maximum dead time is elapsing, then
a three-pole trip transfer occurs. The dead time and checking by the ASC
function continue. If the ASC decision is that reclosing is permissible, a
close command is issued.

ARC: HSR ope r. mode P Sx = 3-pole


In this HSR operating mode, a secondary fault is ignored. The ARC cycle is
terminated only if a starting signal or trip is still present immediately before
the close command is issued.

Secondary fault treatment during TDR


A secondary fault is ignored. The ARC cycle is terminated only if a starting signal
or trip is still present immediately before the close command is issued.
Secondary fault treatment during RRC
Rapid reclosing is blocked in the event of a secondary fault.

3-262

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.27.10

Parallel Blocking in the P437


If a second protection device is operating in parallel with the P437, then the trip
from this protection device can be integrated into the ARC functional sequence
provided that the binary signal inputs have been configured appropriately. The
effect exercised by the trip of the parallel protection device is a function of
whether it intervenes in a high-speed reclosure (HSR), a time-delay reclosure
(TDR), or a rapid reclosure (RRC). In addition, the AR C: Paralle l tr ip PSx
setting is a determining factor (see Figure Fig. 3-204, (p. 3-271)).

P437/EN M/R-11-A // P437311650

3-263

P437
3.27.10.1

3 Operation

Parallel Blocking with HSR


The trip of an external protection device may intervene in the HSR functional
sequence depending on the set HSR operating mode and the ARC: Par allel
tri p P Sx setting.

AR C: HSR ope r. mode P Sx = 1-pole

A RC : Parall el tri p PSx = Without function

The trip of the external protection device does not intervene in the
functional sequence.
ARC : P aral le l trip P Sx = Parall. bloc.w/o ini

If the P437 has not started, the trip of the external protection device is
ignored. If a trip decision has been reached in the P437, then while the
operative times and the single-pole or maximum dead time are elapsing
the P437 checks to determine whether the trip of the external protection
device is in the same phase as the P437 trip. If this is the case, then the
ARC cycle is continued. If a trip decision of the external protection device
has been reached in another phase, then the ARC cycle is terminated
and the reclaim time is started.
ARC : P aral le l trip P Sx = Parall. bloc.w. init
If the setting at ARC: H SR oper. mode 2 PSx is Start-dependent and
if the P437 has started, then the trip of the external protection device
does not intervene in the HSR functional sequence. If the P437 has not
started then the trips of the external protection device are used as the
criterion for a single-pole HSR, irrespective of the Start-dependent
setting. If the setting is Trip-dependent the ARC cycle is started by the
trip of the external protection device and proceeds normally in the event
that the P437 does not reach a trip decision or not in the same phase.
However, if a trip decision has been reached by the P437 in a different
phase from that of the external protection device, then the reclaim time
is started and three-pole tripping occurs (final trip). Reclosing does not
occur.
If the trip of an external protection device occurs while the dead time is
elapsing, the process is the same as was described for secondary fault
treatment.

3-264

AR C: HS R ope r. mode PSx = 1-/3-pole

P437/EN M/R-11-A // P437311650

P437

3 Operation

ARC : Paral lel tri p PSx = Without function

The trip of the external protection device does not intervene in the
functional sequence.
ARC : P aral le l tri p PSx = Parall. bloc.w/o ini
If the P437 has not started, the trip of the external protection device is
ignored.
If a single-pole trip decision has been reached in the P437, then while
operative time 1 and the time set at AR C: t Dis crim. PSx are elapsing
the P437 checks to determine whether the trip of the external protection
device is in the same phase as the P437 trip. If this is the case, then the
single-pole ARC cycle is continued. If a trip decision of the external
protection device has been reached in another phase while operative
time 1 was elapsing, then the three-pole dead time is started and the
ARC cycle is terminated as is the case with a three-pole HSR. If the trip
of the external protection device occurs while time tDiscrim. is elapsing,
then a switch is made to the three-pole dead time, and the ARC cycle is
continued as with a three-pole trip. If the trip of the external protection
device occurs after the time set at ARC : t Dis crim. PSx has elapsed,
then final three-pole tripping occurs, the ARC cycle is terminated, and
the reclaim time is started.

If a single-pole HSR with maximum dead time is carried out, then timer
stage tDiscrim. is started at the same time as the maximum dead time.
The P437 checks to determine whether, while operative time 2 or timer
stage tDiscrim. was elapsing, a trip of the external protection device has
occurred in the same phase as in the P437. If this is the case, then the
ARC cycle is continued. If the external protection device reaches a trip
decision in a different phase, then there is a three-pole trip transfer and
the ARC cycle is continued. If the trip of the external protection device
occurs after time tDiscrim. has elapsed, then three-pole final tripping
occurs and the reclaim time is started.
A RC : Parall el trip P Sx = Parall. bloc.w. init
If the setting at ARC: H SR oper. mode 2 PSx is Start-dependent and
if the P437 has started, then the trip of the external protection device
does not intervene in the HSR functional sequence. If the P437 has not
started, then the trips of the external protection device are used as the
criterion for a single- or three-pole HSR, irrespective of the Parall. bloc.w.
init setting. If the setting is Parall. bloc.w/o ini the ARC cycle is started by
the trip of the external protection device and proceeds normally if the
P437 does not reach a trip decision or has reached a trip decision in the
same phase. However, if the P437 has reached a trip decision in a
different phase from that of the external protection device, then threepole tripping occurs (3-pole transfer). The ARC cycle is terminated as
with a three-pole HSR.
If the trip of an external protection device occurs while the dead time is
elapsing, the process is the same as was described for secondary fault
treatment.

AR C: HSR ope r. mode PSx '3-pole'

P437/EN M/R-11-A // P437311650

3-265

P437

3 Operation

ARC : Parallel trip P Sx 'Without function'

The trip of the external protection device does not intervene in the
functional sequence.
ARC : Parall el trip P Sx 'Parall. bloc.w/o ini'

The trip of the parallel protection device does not intervene in the HSR
functional sequence.
ARC : Parallel trip P Sx 'Parall. bloc.w. init'
As a result of the trip of the external protection device, the ARC cycle is
started and proceeds normally.

3.27.10.2

Parallel Blocking for TDR or RRC


The trip of the external protection device may intervene in the TDR or RRC
functional sequence depending on the setting of the A RC : Parallel trip PS x
parameter.

AR C: P aralle l t rip PSx = Without function


The trip of the external protection device does not intervene in the
functional sequence.

ARC: Paral le l t r ip P Sx = Parall. bloc.w/o ini


The trip of the parallel protection device does not intervene in the TDR or
RRC functional sequence.

ARC : Parall el tri p PSx = Parall. bloc.w. init


The trip of the external protection device starts a TDR or RRC. The
sequence is the same as with initiation by the P437.

3.27.11

Zone Extension in the P437


Zone extension (ZE) of impedance zone 1 of the distance protection function is
only initiated by the ARC if protective signaling is not ready.
HSR and TDR activate different zone extension factors.

3-266

P437/EN M/R-11-A // P437311650

P437

3 Operation

BUOC:
Trip signal
[ 036 014 ]
DIST:
Trip signal
[ 036 009 ]
ARC:
External trip A
303 016

ARC:
External trip B

ARC:
Zone ext. f. HSR PSx
[ * ]

303 017

ARC:
External trip C
303 018

0
ARC:
Reclaim time running
[ 036 042 ]

ARC:
Zone extension HSR
303 001

0: No
1: Yes

ARC:
Ready
[ 004 068 ]
ARC:
Oper. time 1 running
[ 037 005 ]
ARC:
Oper. time 2 running
[ 037 065 ]

ARC:
Zone ext.dur. RC PSx
[ * ]

ASC:
Close enable
[ 037 083 ]
ARC:
(Re)close signal HSR
[ 037 007 ]

MAIN:
Close command
[ 037 009 ]

ARC:
Zone extension RC
303 002

0: Without
1: Following HSR
2: Always

ARC:
Zone ext. f. TDR PSx
[ * ]

0
1
0: No

ARC:
Zone extension TDR
303 000

1: Yes

ARC:
TDR permitted
303 019

ARC:
Dead time TDR runn.
[ 037 003 ]
Parameter

ARC:
Zone ext. f. HSR PSx

ARC:
Zone ext.dur. RC PSx

ARC:
Zone ext. f. TDR PSx

set
set
set
set

015
024
024
025

015
024
025
025

015
024
024
025

1
2
3
4

059
033
093
053

088
047
007
067

071
039
099
059

D5Z5099A

Fig. 3-200: Zone extension by ARC.

3.27.11.1

Zone Extension by kze HSR


Zone extension by the zone extension factor kze HSR is affected by the following
settings:

P437/EN M/R-11-A // P437311650

3-267

P437

3 Operation

Setting for A RC : Zon e e xt. f . H SR P Sx Yes


The measuring range is extended when the ARC is ready and while
operative times 1 and 2 are elapsing.

Setting for A RC : Zone ext.du r. RC P Sx

Following HSR

The measuring range is extended while the close command time is


elapsing if the close command is issued by a non-synchronism-checked
HSR. There is no zone extension with a rapid reclosure (RRC).
Always
The measuring range is extended while the close command time is
elapsing. How the close command is triggered is not important.

If the two parameters are set for No or Without, respectively, then there is no
zone extension.
3.27.11.2

Zone Extension by kze TDR


The measuring range of impedance zone 1 is extended by the zone extension
factor kze HSR after a close command is issued by the TDR function, as long as
another TDR is permitted and the setting for A RC: Zone ext. f. TDR PSx is
Yes. Zone extension is canceled during the course of the TDR dead time. If the
setting is No, there is no zone extension.

3.27.12

Control Using External Auto-Reclosing Control


If an external ARC is used in place of the ARC function implemented in the P437,
the operating mode of the external ARC is defined for the P437 by selecting the
appropriate setting at ARC: Op. mode e xt ARC PSx. Control of the zone
extension factor kze HSR and enabling of the distance protection trip in zone 1
with extended reach is handled in the P437 in accordance with this setting.
The measuring range is only extended if protective signaling is not ready,
internal ARC is disabled, and the binary signal input configured for ARC: Ena ble
ext . AR C EXT is triggered. If the setting at A RC: Op. mode ext ARC PSx is
1-pole, trip-depend., there must also be a single-pole starting signal, or in the
case of a two-pole starting signal the setting at D IST: Trip zone 1 PP PSx
must be 1-pole leading phase or 1-pole trailing phas, so that the zone extension
factor kze HSR is activated. If the setting at A RC: Op. mode e xt ARC PSx is 1pole, trip-depend., then the distance protection trip with extended reach is only
enabled if the trip is single-pole.

3-268

P437/EN M/R-11-A // P437311650

P437

3 Operation

ARC:
Enabled
[ 015 064 ]
ARC:
Enable ext. ARC EXT
[ 038 003 ]
DIST:
Starting A

ARC:
Op. mode ext ARC PSx
[ * ]

303 529

DIST:
Starting B
303 530

DIST:
Starting C

303 531

BUOC:
IA> triggered

ARC:
Meas.r.extd. ext.ARC
303 025

304 750

BUOC:
IB> triggered

0: Without

304 751

1: 1-pole, trip-depend.

BUOC:
IC> triggered

2: 1-pole,start-depend.

304 752

3: 3-pole

DIST:
Trip zone 1 PP PSx
[ * ]
1: 1-pole leading phase
2: 1-pole trailing phas

ARC:
Enable dist.tripZ1ze
303 026

DIST:
Trip zone 1,ze, A
303 658

DIST:
Trip zone 1,ze, B
303 659

DIST:
Trip zone 1,ze, C
303 660

Parameter

ARC:
Op. mode ext ARC PSx

DIST:
Trip zone 1 PP PSx

set 1
set 2
set 3
set 4

015 045
024 043
024 083
025 043

011 054
011 055
011 056
011 057

47Z01ALA

Fig. 3-201: Control with external ARC.

3.27.13

General ARC Control Functions in the P437

Monitoring the Receive Signals of Protective Signaling


The user can specify whether there will be intervention in the ARC sequence
when a signal is received by protective signaling. If this is desired, then the ARC
cycle is continued in different ways depending on the number of receive signals
that are received by the P437 while operative time 1 or the single- or three-pole
dead times are elapsing.
At the end of the dead time, the P437 checks to determine whether protective
signaling has received one signal while the above-mentioned times are elapsing.
If this is the case, then the HSR is terminated normally. If protective signaling
receives no signal or more than one signal, the HSR is terminated as if the fault
had been cleared during operative time 2. This means that even with single-pole
starting signals or trips reclosing is preceded by a synchronism check by ASC.

P437/EN M/R-11-A // P437311650

3-269

P437

3 Operation

ARC:
Mon. PSIG recv. PSx
[ * ]

0
1
0: No
ARC:
Switch to tPmax

1: Yes

PSIG:
No. telecom. ch. PSx
[ * ]
1: 1 channel

303 024

PSIG:
Receive (A) EXT
[ 036 048 ]
ARC:
Oper. time 1 running
[ 037 005 ]
ARC:
Dead time 1p running
[ 037 066 ]
ARC:
Dead time 3p running
[ 037 067 ]
ARC:
Max. dead time runn.
[ 037 069 ]

Parameter

ARC:
Mon. PSIG recv. PSx

PSIG:
No. telecom. ch. PSx

set 1
set 2
set 3
set 4

015 082
024 050
025 010
025 070

015 026
024 012
024 072
025 032

47Z80AHA

Fig. 3-202: Monitoring the receive signals of protective signaling.

Signal ARC: Ext. 1p trip pe rm.


If ARC is ready or if one of the operative times is elapsing, the P437 will generate
the following signal: ARC: Ext. 1p trip pe rm..

ARC:
Ready
[ 004 068 ]

ARC:
Ext. 1p trip perm.
[ 039 086 ]

ARC:
Oper. time 1 running
[ 037 005 ]
ARC:
Oper. time 2 running
[ 037 065 ]

100ms

&

ARC:
Dead time 1p running
[ 037 066 ]

47Z13AKB

Fig. 3-203: Signal A R C : E x t . 1 p t r i p p e r m ..

Switch to Maximum Dead Time via Binary Signal Input


If the binary signal input configured for AR C: 3p transfer trip EXT is triggered
while the single-pole or three-pole dead time is elapsing, the P437 switches to
the maximum dead time. The ARC cycle will then be terminated as if starting or
trip signals had dropped out during operative time 2.

3-270

P437/EN M/R-11-A // P437311650

P437

3 Operation

ARC Sequence Control


ARC:
Operating mode PSx
[ * ]

ARC:
Operative time 1 PSx
[ * ]
ARC:
Operative time 2 PSx
[ * ]
ARC:
Dead time 1p PSx
[ * ]
ARC:
Dead time 3p PSx
[ * ]
ARC:
Dead time max PSx
[ * ]
ARC:
No. permit. TDR PSx
[ * ]
ARC:
TDR dead time PSx
[ * ]

ARC:
HSR oper. mode PSx
[ * ]
ARC:
HSR oper. mode 2 PSx
[ * ]
ARC:
Enable RRC PSx
[ * ]

Parameter
set 1
set 2
set 3
set 4

ARC:
HSR oper. mode 2 PSx
015 044
024 022
024 082
025 042

ARC:
tRRC PSx
[ * ]
ARC:
tDiscrim. PSx
[ * ]
ARC:
Reclaim time PSx
[ * ]
ARC:
Parallel trip PSx
[ * ]

Setting
ARC:
Parallel trip PSx
0: Without function
1: Parall. bloc.w/o ini
2: Parall. bloc.w. init
ARC:
General starting EXT
[ 037 096 ]
MAIN:
General starting
[ 036 000 ]
MAIN:
Starting A
[ 036 001 ]
MAIN:
Starting B
[ 036 002 ]
MAIN:
Starting C
[ 036 003 ]
MAIN:
Trip A
306 009

MAIN:
Trip B

306 010

MAIN:
Trip C

306 011

MAIN:
Parallel trip A EXT
[ 036 052 ]
MAIN:
Parallel trip B EXT
[ 036 053 ]
MAIN:
Parallel trip C EXT
[ 036 054 ]
MAIN:
Parallel trip EXT
[ 037 019 ]
ARC:
3p transfer trip EXT
[ 038 043 ]
ARC:
Switch to tPmax

Parameter
set 1
set 2
set 3
set 4
Parameter
set 1
set 2
set 3
set 4
Parameter
set 1
set 2
set 3
set 4
Parameter
set 1
set 2
set 3
set 4

ARC:
Operating mode PSx
015 100
015 101
015 102
015 103

ARC:
HSR oper. mode PSx
015 051
024 025
024 085
025 045

ARC:
Enable RRC PSx
015 085
024 044
025 004
025 064

ARC:
Operative time 1 PSx
015 066
024 035
024 095
025 055

ARC:
Operative time 2 PSx
015 083
024 042
025 002
025 062

ARC:
Dead time 1p PSx
015 055
024 029
024 089
025 049

ARC:
Dead time 3p PSx
015 056
024 030
024 090
025 050

ARC:
Dead time max PSx
015 084
024 043
025 003
025 063

ARC:
Cycle running
[ 037 000 ]
ARC:
Oper. time 1 running
[ 037 005 ]
ARC:
Oper. time 2 running
[ 037 065 ]
ARC:
Dead time 1p running
[ 037 066 ]
ARC:
Dead time 3p running
[ 037 067 ]
ARC:
Max. dead time runn.
[ 037 069 ]
ARC:
Dead time running
[ 037 002 ]
ARC:
Dead time TDR runn.
[ 037 003 ]
ARC:
tDiscrim running
[ 039 087 ]
ARC:
(Re)close request
[ 037 077 ]
ARC:
Close command
303 021

ARC:
Reclaim time running
[ 036 042 ]
ARC:
Sig.interr. CB trip
[ 036 040 ]
ARC:
External trip A

303 024

303 016

ARC:
V> for RRC triggered

ARC:
External trip B

ASC:
Close enable w.block

ARC:
External trip C

ASC:
Close enable
[ 037 083 ]
ASC:
Close rejection
[ 037 086 ]
ARC:
CB closed

ARC:
TDR permitted

303 017

303 014

303 018

305 001

303 019

ARC:
3-pole transfer int.
303 020

ARC:
3p final trip
[ 036 043 ]
ARC:
HSR A

303 004

Parameter
set 1
set 2
set 3
set 4
Parameter
set 1
set 2
set 3
set 4
Parameter
set 1
set 2
set 3
set 4

ARC:
No. permit. TDR PSx
015 068
024 037
024 097
025 057
ARC:
tRRC PSx
015 086
024 045
025 005
025 065
ARC:
Parallel trip PSx
015 053
024 027
024 087
025 047

ARC:
TDR dead time PSx
015 057
024 031
024 091
025 051
ARC:
Reclaim time PSx
015 054
024 028
024 088
025 048
ARC:
tDiscrim. PSx
018 051
024 049
025 009
025 069

ARC:
HSR B

303 008

303 009

ARC:
HSR C

303 010

ARC:
HSR A-B-C
ARC:
TDR

303 005

303 006

ARC:
3-pole RRC

303 007

ARC:
tRRC running
303 015

ARC:
(Re)close signal HSR
[ 037 007 ]
ARC:
(Re)close signal TDR
[ 037 006 ]
ARC:
Reclosure successful
[ 036 062 ]

47Z01AJA

Fig. 3-204: ARC sequence control.

P437/EN M/R-11-A // P437311650

3-271

P437
3.27.14

3 Operation

ARC Counters in the P437


The following ARC signals are counted:

Number of single-pole high-speed reclosures, pole-selectively.

Number of three-pole high-speed reclosures.

Number of time-delayed reclosures.

The counters can be reset either individually or as a group.

ARC:
HSR A

303 008

ARC:
HSR B

303 009

ARC:
HSR C

303 010

ARC:
No. of HSR A
[ 004 001 ]
ARC:
No. of HSR B
[ 004 002 ]
ARC:
No. of HSR C
[ 004 003 ]

ARC:
Trip time elapsed

303 005

ARC:
No. of HSR A-B-C
[ 004 004 ]

ARC:
TDR

+
303 006

ARC:
Number TDR
[ 004 008 ]

MAIN:
General reset USER
[ 003 002 ]
1: execute
MAIN:
General reset EXT
[ 005 255 ]
ARC:
Reset counters EXT
[ 005 244 ]

ARC:
Reset counters USER
[ 003 005 ]

0
1
0: don't execute
1: execute

45Z63ACA

Fig. 3-205: ARC Counters.

3-272

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.28

Automatic Synchronism Check (Function Group ASC)


The automatic synchronism check (ASC) function allows the P437 to verify that
before a close or reclose command is issued synchronism exists between system
sections that are to be synchronized (paralleled) or whether one of the system
sections is de-energized. In order to check for synchronism, two voltages
generally the voltages on the line and busbar sides are compared for
differences in frequency, angle, and voltage. Connecting the reference voltage
transformer will determine which of the system sections will provide the
reference voltage (e.g. the line side or the busbar side). The measurement loop
must be set to correspond to the reference voltage connection
(ASC: Measur eme nt loop P Sx) so that the correct measuring voltage is
selected for the comparison. In the connection example shown in section
Conditioning of the Measured values (see Section 3.12, (p. 3-69)), the busbar
voltage VA-B is the reference voltage.

ASC:
Measurement loop PSx
[ * ]
VA-G
VB-G
VC-G

ASC:
Select. meas.loop PG
305 008

1: Loop A-G
2: Loop B-G

ASC:
Vmeas
305 007

3: Loop C-G
4: Loop A-B
Parameter

ASC:
Measurement loop PSx

set
set
set
set

031
077
078
079

1
2
3
4

5: Loop B-C
6: Loop C-A

060
044
044
044

47Z0125A

Fig. 3-206: Selecting the measurement loop.

3.28.1

Disabling and Enabling the ASC Function


The function can be disabled or enabled using setting parameters or through
binary signal inputs.
The function is enabled generally (independently of the parameter subsets) at
AR C : Gener al enabl e U SER. It is enabled as a function of a parameter subset
via ARC : Enable PSx. If these enabling functions have been activated, ASC can
be disabled or enabled using setting parameters or through appropriately
configured binary signal inputs. Parameters and configured binary signal inputs
have equal status. If only the ARC: Enabl e EX T function is assigned to a binary
signal input, then the ASC will be enabled by a positive edge of the input signal
and disabled by a negative edge. If only the AR C: Dis able E XT function has
been assigned to a binary signal input, then a signal at this input will have no
effect.

P437/EN M/R-11-A // P437311650

3-273

P437

3 Operation

If the ASC function is disabled an activation enable will always be issued.

ASC:
General enable USER
[ 018 000 ]
0
1

0: No
1: Yes

ASC:
Enable PSx
[ * ]
0
1

ASC:
Enabled
[ 018 024 ]

0: No
1: Yes

INP:
Fct. assignm. U xxx
[ xxx xxx ]
U x1
U x2
U x3
U xx
Address

037 049

Address

037 061
ASC:
Ext./user enabled
[ 037 092 ]

ASC:
Enable EXT
[ 037 049 ]
ASC:
Enable USER
[ 003 136 ]
0
1

0: don't execute
1: execute
ASC:
Disable EXT
[ 037 061 ]
ASC:
Disable USER
[ 003 135 ]
0
1
0: don't execute
1: execute

Parameter

ASC:
Enable PSx

set
set
set
set

018
018
018
018

1
2
3
4

020
021
022
023

19Z5232A

Fig. 3-207: Enabling/disabling the automatic synchronism check function.

3-274

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.28.2

ASC Readiness and Blocking


The ASC function is ready if it is activated and enabled and if there is no
blocking. Blocking can be brought about if a voltage transformer m.c.b. was
tripped or by an appropriately configured binary signal input. The user can
specify whether closing or reclosing will always be enabled or not (reclosure with
or without a check) when the ASC function is blocked.
The user can also specify separately for high-speed reclosures (HSR) and timedelayed reclosures (TDR) whether reclosure will be carried out with or without a
check.

MAIN:
M.c.b. trip V EXT
[ 004 061 ]
MAIN:
M.c.b. trip Vref EXT
[ 036 086 ]
ASC:
Blocking EXT
[ 037 048 ]

ASC:
Blocked
[ 038 018 ]

ASC:
Enabled
[ 018 024 ]

ASC:
Ready
[ 037 079 ]
ASC:
Not ready
[ 037 082 ]

MAIN:
Protection active
306 001

ASC:
Clos.rej.w.block PSx
[ * ]

ASC:
Close enable w.block
305 001

0
1

ASC:
Close reject.w.block
305 002

0: No
1: Yes

ASC:
Active for HSR PSx
[ * ]

ASC:
Active
305 003

1
0: No
1: Yes
ARC:
HSR
303 156

ASC:
Active for TDR PSx
[ * ]
0
1
0: No
1: Yes

ARC:
TDR
303 006

ASC:
Manual close request
305 000

Parameter

ASC:
Clos.rej.w.block PSx

ASC:
Active for HSR PSx

ASC:
Active for TDR PSx

set
set
set
set

018
077
078
079

018
077
078
079

018
077
078
079

1
2
3
4

003
032
032
032

001
030
030
030

002
031
031
031

19Z51BCA

Fig. 3-208: ASC readiness and blocking.

P437/EN M/R-11-A // P437311650

3-275

P437
3.28.3

3 Operation

Close Request
The ASC function can be triggered by ARC, via setting parameters or from an
appropriately configured binary signal input. Close requests via a setting
parameter or the binary signal input are accepted only if no ARC cycle is running.

ARC:
(Re)close request
[ 037 077 ]

ASC:
Gen. close request

ARC:
Cycle running
[ 037 000 ]

ASC:
Manual close request

306 012

305 000

ASC:
MC close requ. USER
[ 018 004 ]
0
1

500ms

0: don't execute
1: execute

ASC:
MC Close request
034 018 ]

ASC:
MC Close request EXT
[ 037 062 ]

50ms

ASC:
Enabl.close requ.EXT
[ 037 063 ]

50ms

1
500ms

INP:
Fct. assignm. U xxx
[ 152 xxx ]

U x1
U x2
U x3
U x4
U xx
Address

037 063

ASC:
Test MC close r USER
[ 018 005 ]

ASC:
Test
305 004

0
1

100ms

0: don't execute

1
500ms

1: execute
ASC:
Test MC close r. EXT
[ 037 064 ]

ASC:
Test MC close requ.
[ 034 019 ]

47Z8072

Fig. 3-209: Close request for auto-reclose control.

3-276

P437/EN M/R-11-A // P437311650

P437

3 Operation

ARC:
(Re)close request
[ 037 077 ]

ASC:
Gen. close request

ARC:
Cycle running
[ 037 000 ]

ASC:
Manual close request

306 012

305 000

ASC:
AR close requ. USER
[ 008 238 ]
0
1

500ms

0: don't execute
1: execute

ASC:
AR close request
[ 008 239 ]

ASC:
AR close request EXT
008 236 ]

50ms

ASC:
Enabl.close requ.EXT
[ 037 063 ]

50ms

1
500ms

INP:
Fct. assignm. U xxx
[ 152 xxx ]

U x1
U x2
U x3
U x4
U xx
Address

037 063

ASC:
Test AR close r.USER
[ 008 237 ]

ASC:
Test
305 004

0
1

100ms

0: don't execute

1
500ms

1: execute
ASC:
Test AR close requ.
008 240 ]

ASC:
Test AR close r. EXT
[ 000 106 ]

47Z8073

Fig. 3-210: Close request for manual close command.

The ASC operative time is started with the close request. If the close enable is
issued before the ASC operative time has elapsing, the close command is issued.
Otherwise an A SC : C lose r e j ecti on signal is generated for 100 ms.

P437/EN M/R-11-A // P437311650

3-277

P437

3 Operation

Close enable

Close reject

ASC:
Cycle running
[ 038 019 ]

ASC:
Cycle running
[ 038 019 ]

ASC:
Gen. close request

ASC:
Gen. close request

306 012

306 012

ASC:
Operat.time running
[ 037 093 ]

ASC:
Operat.time running
[ 037 093 ]

ASC:
Close enable
[ 037 083 ]

ASC:
Close rejection
[ 037 086 ]

MAIN:
Close command
[ 037 009 ]

MAIN:
Close command
[ 037 009 ]

Parameter

ASC:
Operative time PSx

set
set
set
set

018
077
078
079

1
2
3
4

010
034
034
034

MAIN:
Close cmd.pulse time
[ 015 067 ]

D5Z5073B

Fig. 3-211: Signal flow for a close enable and a close rejection.

3.28.4

ASC Operating Modes


The criteria for a close enable are determined by the ASC operating mode setting
(see Section 3.28.9, (p. 3-284)). The following operating mode settings are
possible:

3.28.5

Voltage-checked

Synchronism-checked

Voltage/synchronism-checked

Continuous Synchronism Check


Synchronism checks, e.g. monitoring of voltage and/or synchronism
requirements, are carried out continuously during the duration of the set ASC
operative time. The following signals are updated according to their current
states:

A SC: Close en abl e

ASC : Close e nable, volt .ch

A SC: Close en able ,s yn c.ch

AS C: C lose reje ction

The ASC maximum operative time setting is 6000 s (100 minutes).

3-278

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.28.6

Extended Settings for the Close Enable Conditions


The close enable conditions can now be set separately for auto-reclose control
and manual close command. This makes it possible to select different operating
modes as well as different tolerance ranges.

Close enable conditions for Auto-reclose control

Close enable conditions for Manual close


command

ASC: AR op. mod e P Sx

ASC: MC op. mode PSx

ASC : AR with tCB PSx

A SC: MC wit h tC B P Sx

ASC : AR Op .m od e v -chk .PSx

A SC: MC op.mode v-chk.P Sx

ASC: AR V> volt .che ck PSx

A SC: MC V> volt.che ck P Sx

ASC: AR V< volt.ch eck PSx

ASC: MC V < vol t. che ck P Sx

ASC: AR tmin v -check PSx

A SC: MC tmin v-ch eck P Sx

ASC: AR V> syn c.che ck PSx

ASC: MC V > sync.che ck PSx

ASC: AR de lta V max PSx

ASC: MC del ta V m ax P Sx

ASC: AR de lta f max PSx

A SC: MC de lta f max PSx

ASC: AR de lta phi max PSx

ASC: MC delta phi max PSx

ASC: AR t min sy nc.ch k PSx

ASC: MC tmin s yn c.chk PSx

The automatic reclosure setting parameters become active when a close request
is issued by the integrated ARC (for an RRC, HSR or TDR) or by a close request
from an external ARC device sent to the binary signal input function ASC: AR
close req ue st EXT.

P437/EN M/R-11-A // P437311650

3-279

P437

3 Operation

3.28.7

Considering the CB Close Time


In slightly asynchronous power systems, setting A SC: AR with tC B PSx to Yes
makes it possible to consider the circuit breaker closing time when issuing a
close command.
The condition for slightly asynchronous power systems is given if the difference
in frequencies lies within the range of 10 mHz < f < fmax. If this condition and
the voltage condition (V < Vmax) are met then the next point in time is
continuously calculated at which the phasors for Vref and the corresponding
voltage of the three-phase system are in phase (e.g. difference in voltage phase
angles approaches 0). The close command, allowing for the set CB close time
M AIN: t C B,cl ose is then issued sooner.

yes

yes

Close with tCB

f < 10 mHz

no

no

Normal mode,

Asynchronous mode,

Synchronous mode,

close if:

close if:

close if:

V < Vmax

V < Vmax

V < Vmax

f < fmax

f < fmax

< max

< max

for tmin,synchr.

for tmin,synchr.

for tmin,synchr.

within operative time.

within operative time.

within operative time.


Raise close command
so that closing takes place at
= 0
(taking CD close time and
internal delays into account).

47Z1085A_EN

Fig. 3-212: Functional sequence and close conditions for the Synchronism check.

3-280

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.28.8

Voltage-Checked Close Enable


The synchronism-checked close enable can be bypassed using the voltagechecked close enable without affecting the former. For this purpose the three
phase-to-ground voltages and the reference voltage Vref are monitored to
determine whether they exceed or fall below the set threshold values.

ASC: AR V> vo lt .check PSx

ASC: MC V > vol t.ch eck PSx

ASC: AR V< vo lt .check PSx

ASC: MC V< vol t.ch eck P Sx

Depending on the operating mode selected for the voltage check, all three
phase-to-ground voltages need to exceed or fall below the set value in order to
meet the condition for voltage-checked closing. If the conditions corresponding
to the set operating mode for the voltage synchronism check are met, then the
close enable is issued after the set minimum time has elapsed.
ASC: AR tm in v-ch eck PSx

A SC: MC tmin v-ch eck P Sx

The following operating modes for voltage checking can be selected separately
for each parameter subset:

Vref but not V

V but not Vref

Not V and not Vref

Not V or not Vref

Vref & Z1 but not V

N V&Vref or V&n Vref

Where the operating mode is set to Vref & Z1 but not V the significance of Z1
has been modified several times during the development of the P437. Basically
this condition should guarantee that the voltage-checked reclose control will only
occur after a highspeed trip issued to clear a line fault. With a time-delayed trip
(ARC start via operative time 2) the reclose control should only occur after a
voltage input is received from the remote end, including a synchronism check
(V, f, ).
Originally Z1 was actually the condition that would make distance protection
trip in zone 1. This was sufficient with plain protection systems. As of version
P437 611, the significance of &Z1 was then extended to [Trip with DIST Z1]
OR [Trip with Z1,ze and PSIG].
Perhaps this approach did not suffice for applications with line differential
protection operating concurrently. Causes for problems were for example:

States during the loss of the protective signaling interface and faults at the
remote end of the line.

Extremely short fault duration (2 periods) with a too fast trip command
by L-DIFF and CB, so that DIST starting has already dropped out before the
PSIG enable signal has been received.

High ohmic faults where DIST does not start but L-DIFF does.

The line selective trip signals from L-DIFF operating in parallel (or DIFF operating
in parallel) have been mapped to binary signal inputs on the P437
(MAIN : Parall el tri p EXT etc.). Together with this trip a start by the ARC will
also occur.

P437/EN M/R-11-A // P437311650

3-281

P437

3 Operation

In order to address these problems the condition Z1 is now (as of version


P437 630) no longer dependent on individual protection functions but rather on
the recognition that the trip has occurred during operative time 1 of ARC.

ASC:
Enabled
[ 018 024 ]
ASC:
Active

305 003

ASC:
AR op. mode PSx
[ * ]
1: Voltage-checked

ASC:
AR V> volt.check PSx
[ * ]

3: Volt.&sync.-checked
VA-G

VA-G3

VB-G

VB-G3

VC-G

VC-G3

ASC:
AR V< volt.check PSx
[ * ]
VA-G3
VB-G3
VC-G3

ASC:
Select. meas.loop PG
305 008

Vref

ASC:
AR tmin v-check PSx
[ * ]

ASC:
AR Op.mode v-chk.PSx
[ * ]

1
2
1

Vref3

2
1

6
1: Vref but not V
2: V but not Vref
3: Not V and not Vref
4: Not V or not Vref
5: Vref & Z1 but not V
6: N V&Vref or V&n Vref

DIST:
Trip signal Z1,ze
[ 035 074 ]
DIST:
Dist.decis.Z1 stored
303 565

ASC:
Close enable,volt.ch
[ 037 085 ]

1
100ms

ARC:
Cycle running
[ 037 000 ]

ASC:
Close enable
[ 037 083 ]

1
100ms

ARC:
HSR A
303 008

ARC:
HSR B

303 009

ARC:
HSR C
303 010

ASC:
Close enable,sync.ch
[ 037 084 ]

Parameter

ASC:
AR op. mode PSx

ASC:
AR V> volt.check PSx

ASC:
AR V< volt.check PSx

ASC:
AR Op.mode v-chk.PSx

ASC:
AR tmin v-check PSx

set 1
set 2
set 3
set 4

018 025
018 026
018 027
018 028

026 017
077 043
078 043
079 043

018 017
077 040
078 040
079 040

018 029
018 030
018 031
018 032

018 018
077 041
078 041
079 041

47Z1380C

Fig. 3-213: Voltage-checked close enable for autoreclose control.

3-282

P437/EN M/R-11-A // P437311650

P437

3 Operation

ASC:
Enabled
[ 018 024 ]
ASC:
Active

305 003

ASC:
MC op. mode PSx
[ * ]
1: Voltage-checked
ASC:
MC V> volt.check PSx
[ * ]

3: Volt./sync.-checked
VA-G

VA-G3

VB-G

VB-G3

VC-G

VC-G3

ASC:
MC V< volt.check PSx
[ * ]
VA-G3
VB-G3
VC-G3

ASC:
Select. meas.loop PG
305 008

Vref

ASC:
MC tmin v-check PSx
[ * ]

ASC:
MC op.mode v-chk.PSx
[ * ]

1
2
1

Vref3

2
1

6
1: Vref but not V
2: V but not Vref
3: Not V and not Vref
4: Not V or not Vref
5: Vref & Z1 but not V
6: N V&Vref or V&n Vref
DIST:
Trip signal Z1,ze
[ 035 074 ]
DIST:
Dist.decis.Z1 stored
303 565

ASC:
Close enable,volt.ch
[ 037 085 ]
ASC:
Close enable
[ 037 083 ]

1
100ms

ARC:
Cycle running
[ 037 000 ]

1
100ms

ARC:
HSR A

303 008

ARC:
HSR B

303 009

ARC:
HSR C

303 010

ASC:
Close enable,sync.ch
[ 037 084 ]

Parameter

ASC:
MC op. mode PSx

ASC:
MC V> volt.check PSx

ASC:
MC V< volt.check PSx

ASC:
MC op.mode v-chk.PSx

ASC:
MC tmin v-check PSx

set 1
set 2
set 3
set 4

000 056
000 057
000 058
000 059

000 064
000 065
000 066
000 067

000 068
000 069
000 070
000 071

000 060
000 061
000 062
000 063

000 072
000 073
000 074
000 075

47Z1381C

Fig. 3-214: Voltage-checked close enable for manual close control.

P437/EN M/R-11-A // P437311650

3-283

P437
3.28.9

3 Operation

Synchronism-Checked Close Enable


Before a close enable signal is issued, the ASC checks the voltages for
synchronism. Synchronism is recognized if the following conditions are met
simultaneously:

The three phase voltages and the reference voltage must exceed the set
threshold value.
(When with a three-phase voltage the setting of MAIN: Neutr.pt. t reat .
P Sx is Low-imped. grounding both the phase-to-ground and the phase-tophase voltages are checked. If the setting is Isol./res.w.start.PG only the
phase-to-phase voltages are checked.)

ASC: AR V> sync.che ck P Sx

The difference in magnitude between measuring voltage and reference


voltage must not exceed the set threshold value.

ASC : AR de lt a Vmax PS x

ASC: MC delta V m ax P Sx

The frequency difference between measuring voltage and reference


voltage must not exceed the set threshold value.

ASC : AR de lt a f max PSx

ASC: MC V> sync.che ck PSx

ASC: MC delta f max PSx

The angle difference between measuring voltage and reference voltage


must not exceed the set threshold value. (In these comparisons the set
offset angle AS C: Ph i of fs e t PSx is taken into account.)

ASC : AR de lt a ph i m ax P Sx

A SC: MC de lta phi max PSx

If these conditions are met for at least the set time ASC : A R tmin sync.chk
PS x or A SC: MC tmi n sync. chk P Sx, respectively, then a close enable signal
is issued. The ASC operating time for the determination of differences in voltage,
angle, and frequency is approximately 100 ms.
The voltage magnitude difference, angle difference, and frequency difference are
stored as measured synchronism data at the time the close request is issued. In
the event of another close request, they are automatically overwritten by the
new data.

3-284

P437/EN M/R-11-A // P437311650

P437

3 Operation

ASC:
Active

Parameter

MAIN:
Neutr.pt. treat. PSx

ASC:
AR op. mode PSx

ASC:
Phi offset PSx

ASC:
AR V> sync.check PSx

set
set
set
set

010
001
001
001

018
018
018
018

018
077
078
079

018
077
078
079

305 003

ASC:
AR op. mode PSx
[ * ]

1
2
3
4

048
076
077
078

025
026
027
028

034
042
042
042

011
035
035
035

1
*

2
3
1: Voltage-checked
2: Sync.-checked

Parameter

ASC:
AR delta Vmax PSx

ASC:
AR delta f max PSx

ASC:
AR delta phi max PSx

ASC:
AR tmin sync.chk PSx

set
set
set
set

018
077
078
079

018
077
078
079

018
077
078
079

018
077
078
079

1
2
3
4

012
036
036
036

014
038
038
038

013
037
037
037

015
039
039
039

3: Volt.&sync.-checked
MAIN:
Neutr.pt. treat. PSx
[ * ]
1: Low-imped. grounding
ASC:
AR V> sync.check PSx
[ * ]

VA-G

VA-G3

VB-G

VB-G3

VC-G

VC-G3

ASC:
Select. meas.loop PG
305 008

Vref

1
2
ASC:
AR tmin sync.chk PSx

Vref3

[ * ]

2
1

100ms

ASC:
Close enable,sync.ch
[ 037 084 ]

ASC:
Test
305 004

ASC:
AR delta Vmax PSx

[ * ]

Vmax

ASC:
Volt. sel. meas.loop
[ 004 088 ]

ASC:
Volt. magn. diff.
[ 004 091 ]

ASC:
Frequ. difference
[ 004 090 ]

ASC:
AR delta f max PSx
[ * ]

ASC:
Angle difference
[ 004 089 ]

fmax

ASC:
Phi offset PSx

ASC:
AR delta phi max PSx

[ * ]

[ * ]
max
- corr

47Z1112A

Fig. 3-215: Synchronism-checked close enable for auto-reclose control.

P437/EN M/R-11-A // P437311650

3-285

P437

3 Operation

ASC:
Active

Parameter

MAIN:
Neutr.pt. treat. PSx

ASC:
MC op. mode PSx

ASC:
Phi offset PSx

ASC:
MC V> sync.check PSx

set
set
set
set

010
001
001
001

000
000
000
000

018
077
078
079

000
000
000
000

305 003

ASC:
MC op. mode PSx
[ * ]

1
2
3
4

048
076
077
078

056
057
058
059

034
042
042
042

052
053
054
055

1
*

2
3
1: Voltage-checked
2: Sync.-checked

Parameter

ASC:
MC delta Vmax PSx

ASC:
MC delta f max PSx

ASC:
MC delta phi max PSx

ASC:
MC tmin sync.chk PSx

set
set
set
set

000
000
000
000

000
000
000
000

000
000
000
000

000
000
000
000

1
2
3
4

080
081
082
083

084
086
087
088

089
091
092
093

098
099
100
101

3: Volt./sync.-checked
MAIN:
Neutr.pt. treat. PSx
[ * ]
1: Low-imped. grounding
ASC:
MC V> sync.check PSx
[ * ]

VA-G

VA-G3

VB-G

VB-G3

VC-G

VC-G3

ASC:
Select. meas.loop PG

305 008

Vref

ASC:
MC tmin sync.chk PSx
[ * ]

Vref3

2
1

100ms

ASC:
Close enable,sync.ch
[ 037 084 ]

ASC:
Test
305 004

ASC:
MC delta Vmax PSx
[ * ]

Vmax

ASC:
Volt. sel. meas.loop
[ 004 088 ]

ASC:
MC delta f max PSx
[ * ]

ASC:
Volt. magn. diff.
[ 004 091 ]

ASC:
Frequ. difference
[ 004 090 ]

ASC:
Angle difference
[ 004 089 ]

fmax

ASC:
Phi offset PSx
[ * ]

ASC:
MC delta phi max PSx
[ * ]

max
- corr

47Z1113A

Fig. 3-216: Synchronism-checked close enable for manual close command.

3-286

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.28.10

Voltage/Synchronism-Checked Close Enable


If this setting has been selected, then the close enable signal is issued if the
conditions for voltage- or synchronism-checked closing are met.

ASC:
Operative time PSx
[ * ]
ASC:
Cycle running
[ 038 019 ]

ASC:
Gen. close request
306 012

ASC:
Close rejection
[ 037 086 ]

ASC:
Test
305 004

ASC:
Operat.time running
[ 037 093 ]

ASC:
Close reject.w.block
305 002

Parameter

ASC:
Operative time PSx

set
set
set
set

018
077
078
079

1
2
3
4

010
034
034
034

D5Z5076A

Fig. 3-217: ASC sequence control.

3.28.11

Testing the ASC Function


For test purposes a close request can be issued via a setting parameters or an
appropriately configured binary signal input (see Fig. 3-218, (p. 3-288)). In this
case no close command is issued and it is not counted.
Separate triggering parameters are available for testing the function with
parameters for manual (MC) and automatic (AR) reclosure.

Triggering parameter for auto-reclose control

Triggering parameter for manual close command

ASC: AR close re qu. USER

ASC: MC close re qu . USER

ASC: AR close re qu est EXT

ASC: MC Close re qu es t EXT

ASC: AR close re quest

A SC: MC Cl ose requ es t

ASC: Tes t AR close r.USER

ASC: Te st MC close r USER

ASC: Tes t AR close r. EXT

ASC: Te st MC close r. EXT

ASC: Tes t AR close re qu.

A SC: Test MC close re qu.

The ASC cycle and the operating time are started by the test close request.
The network synchronism is checked during the whole operating time and
ASC : Cl ose e nable is set accordingly. If at the end of the operate time no
network synchronism is registered, a 100 ms signal ASC : C lose r ejection is
issued.

P437/EN M/R-11-A // P437311650

3-287

P437

3 Operation

Close enable

Close reject

ASC:
Cycle running
[ 038 019 ]

ASC:
Cycle running
[ 038 019 ]

ASC:
Gen. close request

ASC:
Gen. close request

306 012

306 012

ASC:
Operat.time running
[ 037 093 ]

ASC:
Operat.time running
[ 037 093 ]

ASC:
Close enable
[ 037 083 ]

ASC:
Close rejection
[ 037 086 ]

ASC:
Close rejection
[ 037 086 ]

ASC:
Close enable
[ 037 083 ]

Parameter

ASC:
Operative time PSx

set
set
set
set

018
077
078
079

1
2
3
4

>

100 ms

010
034
034
034

19Z5230A

Fig. 3-218: ASC sequence during testing.

3-288

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.28.12

ASC Counters
The following ASC signals are counted:

Number of reclosures after a close request via setting parameters or an


appropriately configured binary signal input

Number of close requests

Number of close rejections

The counters can either be reset individually (at the address at which they are
displayed) or as a group.
ASC:
Manual close request

>S 1 1

305 000

>R 1

MAIN:
Close command
[ 037 009 ]
ASC:
Gen. close request

&

+
R

306 012

ASC:
No. RC aft. man.clos
[ 004 009 ]

ASC:
No. close requests
[ 009 033 ]

R
ASC:
Close rejection
[ 037 086 ]

ASC:
No. close rejections
[ 009 034 ]

R
MAIN:
General reset USER
[ 003 002 ]
1: execute
MAIN:
General reset EXT
[ 005 255 ]
ASC:
Reset counters EXT
[ 006 074 ]
ASC:
Reset counters USER
[ 003 089 ]

0
1
0: don't execute
1: execute

47Z1377A

Fig. 3-219: ASC counters.

P437/EN M/R-11-A // P437311650

3-289

P437

3.29

3 Operation

Ground fault (short-circuit) protection (Function Group


GFSC)
In the event of single-phase high-resistance faults, the measured fault data are
often insufficient for fault detection and selective clearing by the distance
protection function. To cover for this situation, ground fault (short-circuit)
protection is integrated into the protection device as a highly sensitive backup
protection function. Consequently, ground fault (short-circuit) protection is
operating in parallel with and independently of distance protection.

3.29.1

Disabling or Enabling Ground Fault (Short-Circuit) Protection


The function can be disabled or enabled using setting parameters or through
binary signal inputs.
The activation of the function is enabled generally (independently of parameter
subsets) via GFSC : Gen er al en able USER. It is enabled as a function of a
parameter subset at GFSC: E nabl e P Sx. If these enabling functions have been
activated, ground fault (short-circuit) protection (GFSC) can be disabled or
enabled via setting parameters or through appropriately configured binary signal
inputs. The local control panel or operating program and the binary signal inputs
have equal status in this regard. If only the GFSC: Enable EXT function is
assigned to a binary signal input, then ground fault (short-circuit) protection
(GFSC) is enabled by a positive edge of the input signal and it is disabled by a
negative edge. If only the GFSC: Di sable EXT function is assigned to a binary
signal input, then a signal at this input will have no effect.

3-290

P437/EN M/R-11-A // P437311650

P437

3 Operation

GFSC:
General enable USER
018[ 060 ]
0
1
0: No
1: Yes

GFSC:
Enable PSx
[ * ]
0

GFSC:
Enabled

[ 038 094 ]

0: No
1: Yes

INP:
Fct. assignm. U xxx
xxx[ xxx ]
U x1
U x2
U x3
U x4
Address

039 095

Address

039 096
GFSC:
Ext. enabled
[ 039 097 ]

GFSC:
Enable EXT
[ 039 095 ]
GFSC:
Enable USER
003[ 138 ]
0
1
0: don't execute
1: execute

GFSC:
Disable EXT
[ 039 096 ]

GFSC:
Disable USER
003[ 137 ]

0
1
0: don't execute
GFSC:
Ready
[ 039 093 ]

1: execute
MAIN:
Protection active
306 001

GFSC:
Not ready
[ 039 094 ]

GFSC:
Blocked
310 002

Parameter

GFSC:
Enable PSx

set
set
set
set

018
018
018
018

1
2
3
4

072
073
074
075

47Z1117A

Fig. 3-220: Disabling or enabling ground fault (short-circuit) protection.

3.29.2

Measured Values from the Ground Fault (Short-Circuit) Protection

Measured variables for the GFSC function


Depending on the setting the neutral-displacement voltage used is either the
value calculated by the P437 or the measured value of the neutral-point
displacement voltage.

P437/EN M/R-11-A // P437311650

3-291

P437

3 Operation

As a value for the calculated neutral-displacement voltage, ground fault (shortcircuit) protection uses measurements of the same phase-to-ground voltages
measured by distance protection. From these voltages the P437 calculates the
neutral-displacement voltage VNG.
With the second option (measured value), it is possible to establish ground fault
(short-circuit) protection (GFSC) and its associated ground fault (short-circuit)
protection signaling (GSCSG) irrespective of the installed system voltage
transformers.
As the measured value for the neutral-point displacement voltage, ground fault
(short-circuit) protection (GFSC) uses the neutral-displacement voltage formed
externally via the fourth voltage measuring input, for example the neutraldisplacement voltage from the open delta winding of the voltage transformers
(see Section 3.12.1, (p. 3-69)).
The residual current IN is drawn from a separate transformer in the P437 that is
looped into the phase current transformer neutral or connected to a Holmgreen
group. The connection example shown in Fig. 3-42, (p. 3-70) shows the
transformer looped into the current transformer neutral.

3.29.3

Blocking ground fault (short-circuit) protection


If the calculated value for the neutral-displacement voltage is used then ground
fault (short-circuit) protection is blocked should the signal MC MON: Meas. circ.
V fault y = Yes is present.
With the second option (measured value) GFSC is not blocked by this signal as an
other measuring circuit is used. The signal MAI N: M.c.b. trip VNG EX T is used
instead.

3-292

P437/EN M/R-11-A // P437311650

P437

3 Operation

GFSC:
Blocking EXT
[ 043 068 ]

GFSC:
Blocked

MCMON:
Meas. circ. V faulty
[ 038 023

310 002

GFSC:
Evaluation VNG
002 136 ]

1
2
1: Calculated
2: Measured
MAIN:
M.c.b. trip VNG EXT
[ 002 183 ]
300ms
GFSC:
Fct.assign. blocking
[ 006 020 ]
MAIN:
CB open >=1p
[ 031 039 ]
MAIN:
General starting
[ 036 000 ]

SFMON:
M.c.b. trip VNG
[ 098 132 ]

m out of n

DIST:
Trip signal
[ 036 009 ]
ARC:
Dead time 1p running
[ 037 066 ]
LOGIC:
Output 01
[ 042 032
. ]
.
.
LOGIC:
Output 32
[ 042 094 ]
Any of the
selected
conditions occurs

47Z1307 B

Fig. 3-221: Blocking ground fault (short-circuit) protection.

GFSC:
Evaluation VNG
[ 002 136 ]

VN-G

VA-G

VB-G
VC-G

1 ... 2
1: Calculated

GFSC:
VNG
310 001

2: Measured

0.7Vnom/3

GFSC:
Voltage present
303 953

47Z1115A

Fig. 3-222: Selecting the measured variable.

3.29.4

Starting
The digitally filtered fundamental waves of current and voltage are measured.
They are monitored to determine whether they exceed set thresholds
(GFSC : IN > and GFSC: V NG>). If both thresholds have been exceeded, a
settable timer stage (GFSC: Start. ope r. de lay) is started. Once the trigger

P437/EN M/R-11-A // P437311650

3-293

P437

3 Operation

has dropped out, the starting persists until the settable release delay
(GFSC : St art. re le as. de lay) has elapsed. Directional measurement is
enabled if the current reaches 70% of the set threshold (GFSC : IN>) and the
voltage exceeds the trigger threshold (GFSC : VNG >).

GFSC:
IN>
[ 018 063 ]

GFSC:
Ready
[ 039 093 ]
f0

GFSC:
IN> triggered

IN

[ 039 088 ]

IN / 0.7

GFSC:
VNG>
[ 018 062 ]

f0

VA-G
VB-G
VC-G

GFSC:
VNG> triggered
GFSC:
Start. oper. delay
[ 018 064 ]

[ 039 089 ]

GFSC:
Start. releas. delay
[ 018 065 ]

GFSC:
Starting
[ 038 096 ]
GFSC:
Direct.determ.enabl.
[ 043 061 ]
GFSC:
IN filtered
303 951

GFSC:
VNG filtered
303 950

0.7Vnom/3

GFSC:
Voltage present
303 953

47Z0127A

Fig. 3-223: Starting.

3.29.5

Directional Tripping
The P437 determines the angle between the residual current and the neutraldisplacement voltage for the direction determination. The measured angle is
displayed. The position of the straight line separating forward and backward
(reverse) directions is determined by setting GFSC: Angle phi N. A forward or
backward (reverse)-directional decision results if the following angle conditions
are met:
Forward direction: (90+G) < (270+G)
Backward (reverse) direction: (90+G) > (270+G)
where:
: Measured angle between the residual current and the neutral-point
displacement voltage
G: Setting for GFS C: Angle phi N

3-294

P437/EN M/R-11-A // P437311650

P437

3 Operation

The directional decisions (GFSC : F au lt forward / L S and GFSC: Fault


backward / BS) are followed by timer stages GFSC: t1 (forward) and
GF SC: t2 (back ward). Once the timer stages have elapsed, a trip signal is
issued.

Backward direction

VC-G

90+(IN)
VG-N = -VN-G

VA-G

(IN)

IN
Forward direction
VB-G
47Z1090A

Fig. 3-224: Directional characteristic.

3.29.6

Improved Directional Measurement for Series-Compensated Line


Applications xyz
Ground fault protection is based on the assumption of inductive zero-sequence
source impedances. In case of series compensated lines with a high
compensation degree this condition may not be fulfilled.
The following figures show the measuring conditions of GFSC for forward and
backward (reverse) short-circuits. Problematic is the measurement of line side
faults: Due to the line side VT, the measured voltage results from the voltage
drop caused by the zero-sequence current across the (inductive) equivalent
source impedance ZS0(fwd) and the series-capacitance XC0. Depending on whether
the source reactance is bigger or smaller than the series capacitance the voltage
is inductive or capacitive versus the zero-sequence current. Problems will occur
for a high compensation degree (big XC0) and for strong sources (small XS0(fwd)).
The fault location or distance to the fault does not matter at all.
For backward (reverse) faults, this problem needs not to be considered, as the
source impedance then is always inductive.
Adding a current-proportional voltage to the measured voltage (crosspolarization) as follows solved this problem:
V(GFSC) = Vmeas + jX0I0 = (ZS0(fwd) - jXC0 + jX0)I0
X0 is settable at GF SC : C omp. re actan ce X0, the recommended setting is X0
= XC0, so that the same condition as on a normal inductive line is obtained:
V(GFSC) = ZS0(fwd)I0

P437/EN M/R-11-A // P437311650

3-295

P437

3 Operation

The ground fault starting condition VNG> remains using the directly measured
neutral displacement voltage. In order to secure that directional measurement is
only done with a reliably high absolute value of the line-to-line voltage V(GFSC),
this value must always exceed a minimum of 50 mV.

1pG faults forward (on the line)


-jXC0

To neg.-sequ.
system neutral

ZL0

Imeas = IN = 3 I0

Z S0(fwd)

Vmeas = VNG = - V0 = ( ZS0(fwd) - jXC0) * I0

Via RF
to pos.-sequ. system

Zero-sequence equivalent network and measurands

Backward
Vmeas (capacitive, if Im{ZS0(fwd)} < XC0)

Vmeas (inductive, if Im{ZS0(fwd)} > XC0)

Forward
Typical directional characteristic
(for inductive OHL application)

Imeas= IN = 3 I0

Phasor relations (resistances neglected)


47Z11X1A_EN

Fig. 3-225: Zero-sequence fault measurands on series compensated lines, faults in forward direction.

3-296

P437/EN M/R-11-A // P437311650

P437

3 Operation

1pG faults backward


To neg.-sequ.
system neutral

-jXC0

ZL0

Imeas = - IN = - 1/3 I0

ZS0(bwd)

Vmeas = VNG = - V0 = ( ZL0 + ZS0(bwd) ) * I0

Via RF
to pos.-sequ. system

Zero-sequence equivalent network and measurands

Imeas

Backward
Vmeas (always inductive!)

Forward
Typical directional characteristic
(for inductive OHL application)

IN = 1/3 I0

Phasor relations (resistances neglected)


47Z11X2A_EN

Fig. 3-226: Zero-sequence fault measurands on series compensated lines, faults in backward (reverse) direction.

3.29.7

Improved Phase Selection


In cases with very high fault resistances the neutral displacement voltage is too
small to get a starting of P437 ground fault protection. Also the faulty phase
selection based on distance starting could not be secured in such cases, and so
no 1pole trip of ground fault signaling could be obtained.
To resolve these issues, there are the following concepts:

3.29.7.1

Faulty Phase Selection


If neutral overcurrent starting (GFSC IN>) operates, then the relay checks
whether the faulty phase could be determined based on a delta-current
measurement (where the delta is calculated over a 5 cycle period). This delta

P437/EN M/R-11-A // P437311650

3-297

P437

3 Operation

measurement is only done at the IN> starting. Its valid result is memorized until
the IN> trigger resets.
The phase selection is further depending on the operation of the distance
function:

If DIST has identified a multi-phase(-to-ground) fault, then the above phase


selection is disabled.

If DIST has identified a single phase-to-ground fault, then this phase is


used.

These signals are used to provide 1-pole tripping of ground fault signaling
function (GSCSG) if no phase selection by distance starting is available (initiating
1p HSR cycle, as previously guided by distance starting). They are also used to
apply the virtual current polarization technique (Section 3.29.7.2, (p. 3-298)).
3.29.7.2

Virtual Current Polarization


If sufficient neutral displacement voltage is present (VNG> starting), then GFSC
uses this voltage for directional measurement.
Otherwise, virtual current polarization is applied, i.e. based on the
determination of the faulty phase the relay calculates the polarizing voltage as
sum of the 2 healthy phase voltages, e.g. for an AG fault:
Vpol = VBN + VCN
This Vpol is equal to the inverted faulty-phase voltage, so it is clearly high enough
to secure reliable measurement.
Ideally, for VNG = 0 this polarizing voltage gets Vpol = VBN + VCN = VAN where
the sign is automatically taken into consideration in the direction
determination.
To provide backwards compatible operation, this method needs to be enabled by
user, setting GFSC: V irtual curr e nt pol. to Yes.

3-298

P437/EN M/R-11-A // P437311650

P437

3 Operation

GFSC

GFSC:
IN> triggered

no

[ 039 088 ]
yes
Determination of faulty
phase

GFSC reset
DIST:
Starting

>2p(E)

multi-phase fault

DIST:
Starting

= AN [BN, CN]

Phase A [B, C]

DIST:
Starting

= only N

Phase with max. I

No DIST: Starting

Phase with max. I

GFSC:
VNG> triggered
[ 039 089 ]

yes

no

no

GFSC:
Virtual current pol.
[ 006 009 ]

yes

no

Faulty phase
determined?

yes
Calculation
of
Vpol = VPG
only the 2
healthy phases)

Direction cannot
be determined

Directional Determ.

Directional Determ.

= (Vpol,IN)

= (VNG,IN)

GFSC

47Z1205B

Fig. 3-227: GFSC Phase selection and optional virtual current polarization.

3.29.8

Voltage-Dependent or Current-Dependent Tripping


By setting operating mode tS, the user can choose between voltage-dependent
or current-dependent tripping. After the voltage-dependent or current-dependent
time has elapsed, a trip signal is issued either independently of the directional

P437/EN M/R-11-A // P437311650

3-299

P437

3 Operation

decision or when there is a directional decision for the forward direction


depending on the setting at GF SC : C rite ria tS active.
3.29.8.1

Voltage-Dependent Tripping
Starting of ground fault (short-circuit) protection enables determination of the
voltage-dependent tripping time. Tripping time tS is calculated as follows.
tS =

2s
| VN-G |
10
V nom - 0.2
0.6364 1.1
3
Time-Voltage Characteristic (for Vnom = 100V)

45
s
40

35

Tripping Time tS

30

25

20

15

10

V
0

10

11

Voltage VN-G
47Z0129A

Fig. 3-228: Voltage-time characteristic.

3-300

P437/EN M/R-11-A // P437311650

P437

3 Operation

GFSC:
Operating mode tS
[ 018 080 ]

1
2
1: VNG-dependent
2: IN-dependent
GFSC:
Criteria tS active
[ 018 071 ]
0: blocked

GFSC:
Starting
[ 038 096 ]

tA
GFSC:
Volt.-dep. trip sig.

GFSC:
VNG filtered
303 950

VNG

303 954

47Z0130A

Fig. 3-229: Forming the voltage-dependent trip signal.

3.29.8.2

Current-Dependent Tripping
Starting of ground fault (short-circuit) protection enables determination of the
current-dependent tripping time. The user can select from a large number of
characteristics (see table below). If the current exceeds 1.05 times the set
reference current, calculation of the tripping time begins. A trip signal is issued
as a function of the set characteristic. The tripping characteristics available for
selection are shown in figures Fig. 3-230, (p. 3-303) to Fig. 3-233, (p. 3-305).

P437/EN M/R-11-A // P437311650

3-301

P437

No.

Tripping
Characteristic
Characteristic
settable factor:
k = 0.05 ... 10.00

3 Operation

Formula for the


Tripping
Characteristic

Definite Time

t=k

Per IEC 2553

t =k

Standard Inverse

I
ref

0.02

Very Inverse

13.50

1.00

Extremely Inverse

80.00

2.00

Long Time Inverse

120.00

1.00

t = k (
(I

Moderately Inverse

6
7

b
) -1

0.14

Per IEEE C37.112

a
(I

Formula for the


Reset
Characteristic

Constants

I
ref

)b - 1

tr =

+ c)

k R
I 2
(I
) -1
ref

0.0515

0.0200

0.1140

4.85

Very Inverse

19.6100

2.0000

0.4910

21.60

Extremely Inverse

28.2000

2.0000

0.1217

29.10

Per ANSI

t = k (
(I

I
ref

+ c)

tr =

) -1

k R
I 2
(I
) -1
ref

Normally Inverse

8.9341

2.0938

0.17966

9.00

Short Time Inverse

0.2663

1.2969

0.03393

0.50

10

Long Time Inverse

5.6143

1.0000

2.18592

15.75

11

RI-Type Inverse

t =k

1
0.339 -

12

3-302

RXIDG-Type Inverse

0.236
I
)
(I
ref

t = k (5.8 - 1.35 ln I

I
ref

P437/EN M/R-11-A // P437311650

P437

3 Operation

IDMT Tripping Characteristics per IEC 2553


Characteristic 2: IEC 2553, Very Inverse

Characteristic 1: IEC 2553, Standard Inverse


1000

1000

100

100
k=10

10

10

t/s

k=1

k=10

t/s

1
k=0.1
k=0.05

0.1

0.01

k=1

0.1

k=0.1
k=0.05

0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

I/Iref

I/Iref

Characteristic 3: IEC 2553, Extremely Inverse

Characteristic 4: IEC 2553, Long Time Inverse

1000

1000

100

100

k=10

10

10

t/s

k=10

k=1

t/s
1

k=0.1
k=0.05

k=1
0.1

0.1
k=0.1
k=0.05

0.01

0.01

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

I/Iref

I/Iref

Fig. 3-230: Tripping characteristics as per IEC 255-3.

P437/EN M/R-11-A // P437311650

3-303

P437

3 Operation

IDMT Tripping Characteristics per IEEE C37.112


Characteristic 6: IEEE C37.112, Very Inverse

Characteristic 5: IEEE C37.112, Moderately Inverse


1000

1000

100

100

10

10

k=10

t/s

k=10

t/s
1

k=1

1
k=1

0.1

k=0.1
k=0.05

0.01

0.1
k=0.1
k=0.05
0.01

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

I/Iref

I/Iref

Characteristic 7: IEEE C37.112, Extremely Inverse


1000

100

10

t/s

k=10
1
k=1
0.1
k=0.1
k=0.05

0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

I/Iref

Fig. 3-231: Tripping characteristics as per IEEE C37.112.

3-304

P437/EN M/R-11-A // P437311650

P437

3 Operation

IDMT Tripping Characteristics per ANSI


Characteristic 9: ANSI, Short Time Inverse

Characteristic 8: ANSI, Normally Inverse


1000

1000

100

100

10

10

t/s

k=10

t/s
1

k=10
k=1
0.1

0.1

k=1
k=0.1
k=0.05

0.01

0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 k=0.1
k=0.05

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

I/Iref

I/Iref

Characteristic 10: ANSI, Long Time Inverse


1000

100
k=10
10

t/s

k=1
1
k=0.1
k=0.05

0.1

0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

I/Iref

Fig. 3-232: Tripping characteristics as per ANSI.


IDMT Tripping Characteristics, RI-Type Inverse and RXIDG-Type Inverse
Characteristic 12: RXIDG-Type Inverse

Characteristic 11: RI-Type Inverse


1000

1000

100

100
k=10

10

k=10

10

t/s

k=1
1

t/s

k=1

1
k=0.1
k=0.05

0.1

0.01

k=0.1
k=0.05

0.1

0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

I/Iref

I/Iref

Fig. 3-233: RI-type inverse and RXIDGtype inverse tripping characteristics.

P437/EN M/R-11-A // P437311650

3-305

P437

3 Operation

GFSC:
Operating mode tS
[ 018 080 ]
2: IN-dependent
GFSC:
Criteria tS active
[ 018 071 ]
0: blocked
GFSC:
Starting
[ 038 096 ]

GFSC:
Iref,N
[ 018 076 ]

1.05 Iref,G

GFSC:
IN filtered
303 951

GFSC:
Characteristic N
[ 018 078 ]
GFSC:
Factor kt,N
[ 018 077 ]

GFSC:
Curr.-dep. trip sig.

|IN|/Iref,G

303 955

GFSC:
Characteristic N
0: Definite Time
1: IEC Standard Inverse
2: IEC Very Inverse
3: IEC Extr. Inverse
4: IEC Long Time Inv.
5: IEEE Moderately Inv.
6: IEEE Very Inverse
7: IEEE Extremely Inv.
8: ANSI Normally Inv.
9: ANSI Short Time Inv.
10: ANSI Long Time Inv.
11: RI-Type Inverse
12: RXIDG-Type Inverse

47Z0131A

Fig. 3-234: Forming the current-dependent trip signal.

3.29.9

Non-Directional Tripping
Starting of ground fault (short-circuit) protection starts settable timer stage t3.
Once t3 and tS have elapsed, a trip signal is issued by ground fault (short-circuit)
protection.

3-306

P437/EN M/R-11-A // P437311650

P437

3 Operation

Note: After timer stage t1 or t2 has elapsed, a trip signal is issued and remains
present until the starting drops off even if the direction decision changes or is
reset. This latching is not shown in the diagram.

GFSC:
Fault forward / LS
[ 039 090 ]
GFSC:
Fault backward / BS
[ 039 091 ]

GFSC:
Direct.determ.enabl.

GFSC:
Angle phi N
[ 018 061 ]

[ 043 061 ]
GFSC:
IN filtered
303 951

GFSC:
t1 elapsed

GFSC:
t2 (backward)
[ 018 067 ]

GFSC:
t2 elapsed

[ 038 097 ]

[ 038 098 ]
GFSC:
Trip signal

(90+G)>(270+G)

GFSC:
VNG filtered

GFSC:
t1 (forward)
[ 018 066 ]

[ 039 092 ]

(90+G)<(270+G)

303 950

GFSC:
Starting
[ 038 096 ]

GFSC:
Criteria tS active
[ 018 071 ]

0
1
2
0: blocked
1: forward
2: non-directional

GFSC:
Volt.-dep. trip sig.
303 954

GFSC:
Curr.-dep. trip sig.
303 955

GFSC:
t3 (non-directional)
[ 018 068 ]

GFSC:
t3 elapsed
[ 038 099 ]

GFSC:
Angle VNG/IN
[ 009 098 ]

47Z0132A

Fig. 3-235: Forming the trip signal.

3.29.10

Counters
The trip signals issued by ground fault (short-circuit) protection are counted. The
counter can be reset either at the counter address or by a general reset action.

P437/EN M/R-11-A // P437311650

3-307

P437

3 Operation

GFSC:
Trip signal
[ 039 092 ]

GFSC:
No. of trip signals
[ 009 054 ]

+
R

MAIN:
General reset USER
[ 003 002 ]
1: execute
MAIN:
General reset EXT
[ 005 255 ]

47Z13AHA

Fig. 3-236: Counting the trip signals.

3.29.11

Monitoring the Measured Values


If only one of the two triggers has responded (IN> or VNG>), and if at least one of
the phase-to-ground voltages exceeds 0.7 Vnom/3, a signal will be issued after
10 s.

GFSC:
IN> triggered
[ 039 088 ]
GFSC:
VNG> triggered
[ 039 089 ]

& 1

10 s

GFSC:
Monitor. triggered
[ 038 095 ]

&

SFMON:
Meas. circuits GFSC
[ 098 013 ]

GFSC:
Voltage present
303 953

D5Z50AJB

Fig. 3-237: Monitoring the measured values.

3-308

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.30

Ground Fault (Short-Circuit) Protection Signaling (Function


Group GSCSG)
In order to make selective instantaneous tripping possible ground fault (shortcircuit) protection includes the ground fault (short-circuit) protection signaling
function. Ground fault (short-circuit) protection signaling operates in parallel with
and independently of the protective signaling function of distance protection.
Only when a common communication channel is used is it necessary to block the
protective signaling echo. Furthermore, measures for blocking the weak-indeed
logic of distance protection protective signaling are implemented in the Signal
comp. release operating mode. Ground fault (short-circuit) protection signaling is
coordinated with distance protection protective signaling through appropriate
time delays.
An external signal transmission device is required for operation of ground fault
(short-circuit) protection signaling.

3.30.1

Disabling or Enabling Ground Fault (Short-Circuit) Protection


Signaling
The function can be disabled or enabled using setting parameters or through
binary signal inputs.
The activation of the function is enabled generally (independently of parameter
subsets) via GSC SG: Ge ne ral e nable USE R. It is enabled as a function of a
parameter subset via GSC SG: Enable PSx. If these enabling functions have
been activated, ground fault (short-circuit) protection signaling can be disabled
or enabled via setting parameters or through appropriately configured binary
signal inputs. Parameters and configured binary signal inputs have equal status.
If only the PSI G: Enable E XT function is assigned to a binary signal input, then
protective signaling is enabled by a positive edge of the input signal and it is
disabled by a negative edge. If only the GSCSG: D isable EXT function is
assigned to a binary signal input, then a signal at this input will have no effect.

P437/EN M/R-11-A // P437311650

3-309

P437

3 Operation

GSCSG:
General enable USER
[ 023 069 ]
0
1
0: No
1: Yes

GSCSG:
Enable PSx
[ * ]
0
1

GSCSG:
Enabled
[ 023 070 ]

0: No
1: Yes

INP:
Fct. assignm. U xxx
[ xxx xxx ]

U x1
U x2
U x3
U xx
Address

043 050

Address

043 051
GSCSG:
Ext. enabled
[ 043 066 ]

GSCSG:
Enable EXT
[ 043 050 ]
GSCSG:
Enable USER
[ 003 140 ]

0
1
0: don't execute
1: execute
GSCSG:
Disable EXT
[ 043 051 ]
GSCSG:
Disable USER
[ 003 139 ]

0
1
0: don't execute
1: execute

Parameter

GSCSG:
Enable PSx

set
set
set
set

023
023
023
023

1
2
3
4

071
072
073
074

45Z5043A

Fig. 3-238: Disabling or enabling ground fault (short-circuit) protection signaling.

3.30.2

Readiness of Ground Fault (Short-Circuit) Protection Signaling


Ground fault (short-circuit) protection signaling is ready if the following
conditions are satisfied:

3-310

P437/EN M/R-11-A // P437311650

P437

3 Operation

Ground fault (short-circuit) protection signaling is enabled.

Ground fault (short-circuit) protection is ready.

There is no external blocking.

No fault has been detected in the communication channel.

The GFSC function is not inhibited by either MCMON: Me as. circ. V


faulty (in case GFSC: Evaluati on V NG = Calculated) or by
MA IN : M.c.b. tri p VNG EXT (in case GFSC: Ev aluat ion VNG =
Measured).

None of the conditions selected with GFSC: Fct .as sign . blocking has
been detected.

External blocking is carried out either via a binary signal input configured for
GSC SG: Block ing EXT or via a binary signal input configured for
PSIG: Blockin g E XT, depending on the operating mode setting for the
communication channel.
The fault signal from the external signal transmission device can be either
connected to a binary signal input, configured for GSCSG: Telecom. faulty
EX T or to a binary signal input, configured for P SIG: Te le c. fault y (A) EXT or
PSI G: Telec.fault y (B) EXT depending on the operating mode setting for the
communication channel.
The condition for blocking the ground fault protection scheme logic is user
settable at GSCSG: Fct.assign. blocking because of sometimes conflicting
application restraints. Some considerations about the various blocking conditions
are given below:

P437/EN M/R-11-A // P437311650

3-311

P437

3 Operation

Blocking with CB auxiliary contacts

If distance starting resets, but the trip signal is still present (e.g. because of
the presence of parallel or transfer trip signals), then the start of the 1-pole
dead time of internal autoreclosing is delayed. In order to prevent a 3-pole
trip decision from GSCSG now (as phase selection is no longer possible),
GSCSG needs to be blocked by using the CBs auxiliary contacts.

No instant blocking with 1-pole distance trip

3-312

If one (strong infeed) end issues a fast zone 1 distance 1-pole trip, then
previously GSCSG was blocked almost immediately. At the remote (weak
infeed) end only GFSC senses the fault. In order to allow a fast tripping of
GSCSG at the remote end under this condition, the function must remain

P437/EN M/R-11-A // P437311650

P437

3 Operation

active at the strong infeed end as long as possible, i.e. until a "CB open"
condition is signaled.
GSCSG:
Not ready

MAIN:
Protection active

[ 043 058 ]

306 001

GSCSG:
Enabled

GFSC:
Not ready
GSCSG:
Channel mode
[ 023 078 ]

GSCSG:
Ready
[ 043 057 ]

2
1: Independent channel
2: Common channel
GSCSG:
Blocking EXT
[ 043 052 ]
PSIG:
Blocking EXT
[ 036 049 ]

SFMON:
Telecom.faulty/GSCSG

GSCSG:
Telecom. faulty EXT
[ 043 053 ]

[ 098 027 ]

PSIG:
Telec.faulty (A) EXT
[ 004 064 ]
PSIG:
Telec.faulty (B) EXT
[ 008 094 ]
COMM3:
Communications fault
[ 120 043 ]

GSCSG:
Telecom. faulty
[ 046 060 ]

COMM3:
Sig.asg. comm.fault
[ 120 034 ]
0
1
2
3
4
5
0:
1:
2:
3:
4:
5:

None
Telecom. flt.(A)PSIG
Telecom.faulty GSCSG
TCflt.(A)PSIG &GSCSG
Telecom. flt.(B)PSIG
TCflt.(B)PSIG &GSCSG

GSCSG:
Fct.assign. blocking
[ 002 180 ]
MAIN:
CB open >=1p
[ 031 039 ]
MAIN:
General starting
[ 036 000 ]
DIST:
Trip signal
[ 036 009 ]
ARC:
Dead time 1p running
[ 037 066 ]
LOGIC:
Output 01

m out of n

[ 042 032 ]
.
.
.
LOGIC:
Output 32
[ 042 094 ]
Any of the
conditions occurs

47Z8018A

Fig. 3-239: Readiness of ground fault (short-circuit) protection signaling.

3.30.3

Communication Link Faulty Signal


The GS CSG: Te le com. f aul ty status signal is available in conjunction with the
implementation of the protective interface.
This signal is set by the G SCSG: Te l e com. fau lt y E XT logic binary input
function as well as by COMM3: Commu nications fau lt if the
C OM M3 : Sig.asg. comm.f aul t parameter has been set accordingly.

P437/EN M/R-11-A // P437311650

3-313

P437
3.30.4

3 Operation

Tripping Time
If ground fault (short-circuit) protection signaling is ready, then the tripping timer
is started by ground fault (short-circuit) protection starting.

GSCSG:
Tripping time
[ 023 075 ]

GSCSG:
Ready
[ 043 057 ]

&

GSCSG:
Tripping time elaps.
[ 043 063 ]

GFSC:
Fault forward / LS
[ 039 090 ]

&
GFSC:
Virtual current pol.
[ 006 009 ]
GFSC:
IN> triggered
[ 039 088 ]

47Z1325 A

Fig. 3-240: Tripping time of ground fault (short-circuit) protection signaling.

3.30.5

Frequency Monitoring
Failure of frequency transmission can be signaled to the P437 via an
appropriately configured binary signal input. Which inputs are activated is
determined by the channel operating mode setting at GSCSG: C hannel mode.
If ground fault (short-circuit) protection signaling uses a different communication
channel than protective signaling, then the following occurs, as long as
frequency monitoring has been enabled: when the binary signal input configured
for GSC SG: Fre qu .mon .tri gd. E XT is triggered, the P437 allows an operate
delay of approximately 20 ms to elapse and then generates a receive signal for
150 ms.

3-314

P437/EN M/R-11-A // P437311650

P437

3 Operation

GSCSG:
Frequency monitoring
[ 023 085 ]

GSCSG:
Channel mode
[ 023 078 ]

2
1: Independent channel

0: No

2: Common channel

1: Yes
GSCSG:
Frequ.mon. triggered
304 000

GSCSG:
Frequ.mon.trigd. EXT
[ 043 054 ]
GSCSG:
Receive EXT
[ 043 055 ]
PSIG:
Frequ. monit. trigg.
305 152

PSIG:
Frequ. monit. ch. 1
305 169

PSIG:
Frequ. monit. ch. 2
305 170

PSIG:
Frequ. monit. ch. 3
305 171

47Z0135A

Fig. 3-241: Frequency monitoring.

3.30.6

Transient Blocking
In the event of a directional change of ground fault (short-circuit) protection from
backward (reverse) to forward, ground fault (short-circuit) protection signaling
will generate a blocking signal for the time period set at GSCSG: tBlock.

GSCSG:
tBlock
[ 023 077 ]

GFSC:
Fault backward / BS

S1 1

[ 039 091 ]

R1

&

1
t

GSCSG:
Transient blocking
304 001

GFSC:
Fault forward / LS
[ 039 090 ]
GFSC:
Direct.determ.enabl.
[ 043 061 ]

47Z0136B

Fig. 3-242: Transient blocking.

3.30.7

Operating Modes of Ground Fault (Short-Circuit) Protection


Signaling and the Communication Channel
Ground fault (short-circuit) protection signaling can be operated in two different
modes: Signal comparison release or Signal comparison blocking. For the
communication channel, the user can specify whether ground fault (short-circuit)
protection signaling will use a different communication channel than distance
protection protective signaling or whether the same channel will be used. If the
same communication channel is being used, then the operating mode settings
for protective signaling and ground fault (short-circuit) protection signaling must
be identical. Otherwise there will be a fault signal (see Section 3.26, (p. 3-212)).

P437/EN M/R-11-A // P437311650

3-315

P437
3.30.8

3 Operation

Signal Comparison Release Scheme


If ground fault (short-circuit) protection detects a fault in the forward direction, a
signal is sent to the remote station once the tripping time of ground fault (shortcircuit) protection signaling has elapsed. In the event of a directional change
from backward (reverse) to forward, the send signal is blocked for the duration of
transient blocking.
The circuit breaker in the remote station is tripped if the following conditions are
satisfied:

There is a receive signal.

The ground fault (short-circuit) protection function has detected a fault in


the forward direction.

The tripping time of the ground fault (short-circuit) protection signaling


function has elapsed.

No transient blocking has been set.

If ground fault (short-circuit) protection signaling and distance protection


protective signaling use a common communication channel, then blocking of the
weak indeed logic of distance protection protective signaling will be implemented
if the following conditions are satisfied:

3-316

The tripping time of the ground fault (short-circuit) protection signaling


function has elapsed.

Ground fault (short-circuit) protection has detected a fault in the backward


(reverse) direction.

P437/EN M/R-11-A // P437311650

P437

3 Operation

GSCSG:
Ready
[ 043 057 ]

GSCSG:
Operating mode
[ 023 079 ]

1
2
1: Signal comp. release
2: Signal comp. block.

GSCSG:
Channel mode
[ 023 078 ]

1
2
1: Independent channel
2: Common channel

GSCSG:
Release time send
[ 023 076 ]

GSCSG:
Send signal
[ 043 059 ]
GFSC:
Fault forward / LS

GSCSG:
Send internal signal

[ 039 090 ]

304 002

GFSC:
IN> triggered
[ 039 088 ]
GSCSG:
Transient blocking

GSCSG:
Trip signal
[ 043 060 ]

[ 037 254 ]
GSCSG:
Tripping time elaps.
[ 043 063 ]

GSCSG:
Receive EXT
[ 043 055 ]
PSIG:
Receive
305 165

GSCSG:
Frequ.mon. triggered
GSCSG:
Bl. PSIG weak infeed

304 000

304 003

GFSC:
Fault backward / BS
[ 039 091 ]

45Z8038A

Fig. 3-243: GSCSG send signal and trip signal in the Signal comp. release (permissive) operating mode and
blocking of the weak indeed logic of distance protection protective signaling.

3.30.9

Signal Comparison Blocking Scheme


If ground fault (short-circuit) protection detects a fault in the backward (reverse)
direction, a signal is sent to the remote station. In the event of a directional
change from backward (reverse) to forward, the send signal is extended for the
set duration of transient blocking. Depending on the setting at GSCSG: Block.
sig. n ondir ., a send signal is already generated if directional measurement of
ground fault (short-circuit) protection has been enabled and ground fault (shortcircuit) protection has not made a forward decision.
The circuit breaker in the remote station is tripped if the following conditions are
satisfied:

There is no receive signal.

The ground fault (short-circuit) protection function has detected a fault in


the forward direction.

The tripping time of the ground fault (short-circuit) protection signaling


function has elapsed.

There is no transient blocking in the remote station.

P437/EN M/R-11-A // P437311650

3-317

P437

3 Operation

GSCSG:
Ready
[ 043 057 ]

GSCSG:
Operating mode
[ 023 079 ]

1
2
1: Signal comp. release
2: Signal comp. block.

GSCSG:
Channel mode
[ 023 078 ]

1
2
1: Independent channel
GSCSG:
Release time send
[ 023 076 ]

2: Common channel

GFSC:
Fault backward / BS
[ 039 091 ]

GSCSG:
Send signal
[ 043 059 ]

GSCSG:
Transient blocking

GSCSG:
Send internal signal

304 001

304 002

GSCSG:
Block. sig. nondir.
[ 023 089 ]

0
1
0: No
1: Yes
GFSC:
Direct.determ.enabl.
[ 043 061 ]
GFSC:
Fault forward / LS

GSCSG:
Trip signal
[ 043 060 ]

[ 039 090 ]
GSCSG:
Tripping time elaps.
[ 043 063 ]
GSCSG:
Receive EXT
[ 043 055 ]
PSIG:
Receive
305 165

GSCSG:
Frequ.mon. triggered
304 000

47Z0139A

Fig. 3-244: Send signal and trip signal in the operating mode Signal comp. block..

3.30.10

Weak-Infeed Logic
Ground fault (short-circuit) protection signaling has a weak-infeed logic
function that makes tripping possible if ground fault (short-circuit) protection
does not start. The user has the option to choose whether in this case the trip
signal will be issued by ground fault (short-circuit) protection signaling when
there is a directional decision by ground fault (short-circuit) protection in the
forward direction or when the GFSC: VNG> trigger value is exceeded.

3-318

P437/EN M/R-11-A // P437311650

P437

3 Operation

GSCSG:
Weak infeed trip
[ 023 084 ]
0
1
2
0: No
1: With directional r.
2: With VNG> release

GSCSG:
Channel mode
[ 023 078 ]

1
2

GSCSG:
Op.delay weak infeed
[ 023 087 ]

1: Independent channel
2: Common channel

GSCSG:
Trip signal
[ 043 060 ]

GSCSG:
Receive EXT
[ 043 055 ]
PSIG:
Receive
305 165

GSCSG:
Frequ.mon. triggered
304 000

GFSC:
Fault forward / LS
[ 039 090 ]
GFSC:
VNG> triggered
[ 039 089 ]
GFSC:
IN> triggered
[ 039 088 ]
GSCSG:
Transient blocking
[ 037 254 ]

45Z8039A

Fig. 3-245: Weak-infeed logic.

3.30.11

Trip Mode
Depending on the GSCSG: Trip mode setting, ground fault (short-circuit)
protection signaling can trigger a single-pole or three-pole trip that can activate
the ARC function. If the trip mode setting is 1/3-pole trip w.HSR then when there
is single-pole starting of the distance protection function there will be a trip in the
phase in which the starting condition is present. When there is multi-pole starting
of the distance protection function, ground fault (short-circuit) protection
signaling will reach a three-pole trip decision. If one of the other two operating
modes has been set, then ground fault (short-circuit) protection signaling always
generates a three-pole trip. If the operating mode is 3p-pole trip w/o.HSR, then
the ARC will be blocked by a trip generated by ground fault (short-circuit)
protection signaling.

P437/EN M/R-11-A // P437311650

3-319

P437

3 Operation

GSCSG:
Trip mode
[ 023 088 ]
1
2
3
1: 1/3-pole trip w.HSR
2: 3p-pole trip w.HSR
3: 3p-pole trip w/o.HSR

GSCSG:
Trip A

GSCSG:
Trip signal

304 004

[ 043 060 ]
DIST:
Starting A
GSCSG:
Trip B

303 529

304 005

DIST:
Starting B

GSCSG:
Trip C

303 530

304 006

DIST:
Starting C
303 531

GSCSG:
Blocking ARC
304 008

47Z0142A

Fig. 3-246: Operating mode trip.

3.30.12

Echo Function
When a signal is received, an echo pulse can be formed depending on the
setting if ground fault (short-circuit) protection has not detected a fault in the
backward direction. The receive signal must be present for a period longer than
the set operate delay in order for the echo pulse to be activated. If the circuit
breaker is in the open position, then the operate delay is not active. The echo
pulse is transmitted to the remote station for the set pulse duration. When the
echo pulse is activated, a set blocking time is also started, during the course of
which a new echo pulse is prevented. This prevents a permanent signal from
being transmitted.

3-320

P437/EN M/R-11-A // P437311650

P437

3 Operation

GSCSG:
Echo on receive
[ 023 080 ]

0
1
0: No
1: Yes

GSCSG:
Channel mode
[ 023 078 ]

1
2
1: Independent channel

GSCSG:
Operate delay echo
[ 023 081 ]

2: Common channel

GSCSG:
Pulse duration echo
[ 023 082 ]
GSCSG:
Send signal
[ 043 059 ]

GFSC:
IN> triggered
[ 039 088 ]

S1 1

GSCSG:
Send internal signal
304 002

R1

GSCSG:
Receive EXT
[ 043 055 ]
PSIG:
Receive

305 165

GSCSG:
Frequ.mon. triggered
304 000

GFSC:
Fault backward / BS
[ 039 091 ]
MAIN:
CB closed 3p
[ 031 042 ]
MAIN:
CB closed 3p EXT
[ 036 051 ]
GSCSG:
tBlock echo
[ 023 083 ]

45Z6310A

Fig. 3-247: Echo function.

3.30.13

Testing the Communication Channel


The communications link can be tested. For this purpose a 500 ms send signal is
issued through a binary signal input or from the local control panel. It is extended
by the reset time-delay of the send signal. The remote station receives this signal
if the transmission link is in order.

P437/EN M/R-11-A // P437311650

3-321

P437

3 Operation

GSCSG:
Channel mode
[ 023 078 ]
1: Independent channel
2: Common channel

GSCSG:
Test telecom. USER
[ 023 086 ]

0
1
0: don't execute
1: execute

GSCSG:
Test telecom. EXT

GSCSG:
Release time send
[ 023 076 ]

GSCSG:
Send signal
[ 043 059 ]

GSCSG:
Send internal signal
304 002

[ 043 056 ]
GSCSG:
Test telecom. chann.
[ 034 029 ]

47Z0143A

Fig. 3-248: Testing the communication channel.

3-322

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.31

Definite-Time Overcurrent Protection (Function Group


DTOC)
A four-stage definite-time overcurrent protection function (DTOC) can be enabled
concurrently with distance protection. Three separate measuring systems are
available for this purpose for:

Maximum phase current

Negative-sequence current

Residual current

The inrush stabilization function may intervene in the functional sequence of the
DTOC function.

3.31.1

Enabling or Disabling DTOC Protection


DTOC protection can be disabled or enabled via parameter settings. Moreover,
enabling can be carried out separately for each parameter subset.

DTOC:
General enable USER
[ 031 068 ]

0
DTOC:
Enabled
[ 040 120 ]

1
0: No
1: Yes

DTOC:
Enable PSx
[ * ]

0
1
0: No

Parameter

DTOC:
Enable PSx

set
set
set
set

072
073
074
075

1
2
3
4

098
098
098
098

1: Yes

45Z8089A

Fig. 3-249: Disabling or enabling DTOC protection.

3.31.2

Monitoring the Maximum Phase Current


The three phase currents are monitored by the P437 to detect when they exceed
the set thresholds. After the set operate delays have elapsed, a signal is issued.
The elapsing of the operate delays may be blocked via appropriately configured
binary signal inputs.
When the inrush stabilization function is triggered, the selected stages of the
DTOC function are blocked (see Section 3.12.5, (p. 3-89)).

P437/EN M/R-11-A // P437311650

3-323

P437

3 Operation

DTOC:
Blocking tI> EXT
[ 041 060 ]
DTOC:
Bl.Start. I>

&

450 208

MAIN:
Protection active

&

DTOC:
tI> PSx
[ * ]

306 001

DTOC:
Enabled
[ 040 120 ]

DTOC:
I> PSx
[ * ]

IA

DTOC:
tI> elapsed
[ 040 010 ]

IB
DTOC:
Starting I>
[ 035 020 ]

IC
DTOC:
Blocking tI>> EXT
[ 041 061 ]

DTOC:
tI>> PSx
[ * ]

c
c

&

DTOC:
Bl.Start. I>>

DTOC:
I>> PSx
[ * ]

450 209

DTOC:
tI>> elapsed
[ 040 011 ]
DTOC:
Starting I>>
[ 035 021 ]

DTOC:
Blocking tI>>> EXT
[ 041 062 ]

DTOC:
tI>>> PSx
[ * ]

c
c

&

DTOC:
Bl.Start. I>>>

DTOC:
I>>> PSx
[ * ]

450 210

DTOC:
tI>>> elapsed
[ 040 012 ]
DTOC:
Starting I>>>
[ 035 022 ]

DTOC:
Blocking tI>>>> EXT
[ 041 100 ]

DTOC:
tI>>>> PSx
[ * ]

c
c

&

DTOC:
Bl.Start. I>>>>

DTOC:
I>>>> PSx
[ * ]

450 211

DTOC:
tI>>>> elapsed
[ 035 032 ]
DTOC:
Starting I>>>>
[ 035 023 ]

Parameter

DTOC:
I> PSx

DTOC:
I>> PSx

DTOC:
I>>> PSx

DTOC:
I>>>> PSx

set
set
set
set

072
073
074
075

072
073
074
075

072
073
074
075

072
073
074
075

1
2
3
4

007
007
007
007

008
008
008
008

009
009
009
009

010
010
010
010

Parameter

DTOC:
tI> PSx

DTOC:
tI>> PSx

DTOC:
tI>>> PSx

DTOC:
tI>>>> PSx

set
set
set
set

072
073
074
075

072
073
074
075

072
073
074
075

072
073
074
075

1
2
3
4

019
019
019
019

020
020
020
020

021
021
021
021

022
022
022
022

45Z80ALA

Fig. 3-250: Monitoring the phase currents.

3.31.3

Negative-Sequence Current Stages


The P437 calculates the negative-sequence current from the three phase current
values according to this formula. The result depends on the MAIN: Phase
se quence setting.

3-324

P437/EN M/R-11-A // P437311650

P437

3 Operation

Phase sequence A-B-C

(Alternative terminology: clockwise rotating field)


1

I neg = 3 | (I A + a 2 I B + a I C) |



Phase sequence A-C-B

(Alternative terminology: anti-clockwise rotating field)

I neg = 3 | (I A + a I B + a 2 I C) |



Symbols used:

a = e2j/3 = e j120

a 2 = e4j/3 = e j240

The negative-sequence current is monitored by the P437 to detect when it


exceeds the set thresholds. After the set operate delays have elapsed, a signal is
issued. The operate delays may be blocked via appropriately configured binary
signal inputs.

P437/EN M/R-11-A // P437311650

3-325

P437

3 Operation

DTOC:
Blocking tIneg> EXT
[ 041 102 ]
MAIN:
Inrush stabil. trigg
306 014

MAIN:
Protection active
306 001

DTOC:
Enabled
[ 040 120 ]
DTOC:
Ineg> PSx
[ * ]

MAIN:
Phase sequence
[ 010 049 ]

DTOC:
tIneg> PSx
[ * ]

IA
IB

DTOC:
tIneg> elapsed
[ 035 033 ]

Ineg

IC

DTOC:
Starting Ineg>
[ 035 024 ]

DTOC:
Blocking tIneg>> EXT
[ 041 103 ]

DTOC:
tIneg>> PSx
[ * ]

DTOC:
Ineg>> PSx
[ * ]

DTOC:
tIneg>> elapsed
[ 035 034 ]
DTOC:
Starting Ineg>>
[ 035 025 ]

DTOC:
Block. tIneg>>> EXT
[ 041 104 ]

DTOC:
Ineg>>> PSx
[ * ]

DTOC:
tIneg>>> PSx
[ * ]

DTOC:
tIneg>>> elapsed
[ 035 035 ]
DTOC:
Starting Ineg>>>
[ 035 026 ]

DTOC:
Block. tIneg>>>> EXT
[ 041 105 ]

DTOC:
tIneg>>>> PSx
[ * ]

DTOC:
Ineg>>>> PSx
[ * ]

DTOC:
tIneg>>>> elapsed
[ 035 036 ]
DTOC:
Starting Ineg>>>>
[ 035 027 ]
Parameter

DTOC:
Ineg> PSx

DTOC:
Ineg>> PSx

DTOC:
Ineg>>> PSx

DTOC:
Ineg>>>> PSx

set
set
set
set

072
073
074
075

072
073
074
075

072
073
074
075

072
073
074
075

1
2
3
4

011
011
011
011

012
012
012
012

013
013
013
013

014
014
014
014

Parameter

DTOC:
tIneg> PSx

DTOC:
tIneg>> PSx

DTOC:
tIneg>>> PSx

DTOC:
tIneg>>>> PSx

set
set
set
set

072
073
074
075

072
073
074
075

072
073
074
075

072
073
074
075

1
2
3
4

023
023
023
023

024
024
024
024

025
025
025
025

026
026
026
026

D5Z52AMA

Fig. 3-251: Monitoring the negative-sequence current.

3.31.4

Residual Current Stages


Depending on the setting, the P437 monitors the residual current, derived from
the three phase currents or measured at the current transformer T 4.

3-326

P437/EN M/R-11-A // P437311650

P437

3 Operation

DTOC:
Evaluation IN PSx
[ * ]
IA
IB
IC

1
2

IN

1
1: Calculated
2: Measured

Parameter

DTOC:
Evaluation IN PSx

set
set
set
set

073
073
073
073

1
2
3
4

...

DTOC:
IN
402 625

189
190
202
219

45Z5045B

Fig. 3-252: Selecting the measured value.

The residual current is monitored to determine whether it exceeds the set


thresholds. After the set operate delays have elapsed, a signal is issued. The
operate delays may be blocked via appropriately configured binary signal inputs.

P437/EN M/R-11-A // P437311650

3-327

P437

3 Operation

DTOC:
Blocking tIN> EXT
[ 041 063 ]
MAIN:
Inrush stabil. trigg
306 014

MAIN:
Protection active

DTOC:
IN> PSx
[ * ]

306 001

DTOC:
Enabled

DTOC:
tIN> PSx
[ * ]

[ 040 120 ]
DTOC:
tIN> elapsed
[ 035 037 ]

DTOC:
IN
402 625

DTOC:
Starting IN>
[ 035 028 ]

DTOC:
Blocking tIN>> EXT
[ 041 064 ]
DTOC:
IN>> PSx
[ * ]

DTOC:
tIN>> PSx
[ * ]

DTOC:
tIN>> elapsed
[ 035 038 ]
DTOC:
Starting IN>>
[ 035 029 ]

DTOC:
Blocking tIN>>> EXT
[ 041 065 ]
DTOC:
IN>>> PSx
[ * ]

DTOC:
tIN>>> PSx
[ * ]

DTOC:
tIN>>> elapsed
[ 035 039 ]
DTOC:
Starting IN>>>
[ 035 030 ]

DTOC:
Blocking tIN>>>> EXT
[ 041 101 ]
DTOC:
IN>>>> PSx
[ * ]

DTOC:
tIN>>>> PSx
[ * ]

DTOC:
tIN>>>> elapsed
[ 035 040 ]

Parameter

DTOC:
IN> PSx

DTOC:
IN>> PSx

DTOC:
IN>>> PSx

DTOC:
IN>>>> PSx

set
set
set
set

072
073
074
075

072
073
074
075

072
073
074
075

072
073
074
075

1
2
3
4

015
015
015
015

016
016
016
016

017
017
017
017

018
018
018
018

Parameter

DTOC:
tIN> PSx

DTOC:
tIN>> PSx

DTOC:
tIN>>> PSx

DTOC:
tIN>>>> PSx

set
set
set
set

072
073
074
075

072
073
074
075

072
073
074
075

072
073
074
075

1
2
3
4

027
027
027
027

028
028
028
028

029
029
029
029

DTOC:
Starting IN>>>>
[ 035 031 ]

030
030
030
030

45Z5046A

Fig. 3-253: Monitoring the residual current.

3.31.4.1

Direction-Dependent Trip of the Residual Current Stages


The P437 determines the angle between the residual current and the neutraldisplacement voltage for the direction determination. The direction
determination is enabled when a current stage is started and the neutraldisplacement voltage exceeds the set threshold DTOC: VNG> PSx. The
measured angle is displayed. The position of the straight line separating forward
and backward (reverse) directions is determined by setting DTOC: Angle phi N
PSx. A forward or backward (reverse)-directional decision results if the following
angle conditions are met:

Forward direction: (90+G)>(270+G)

Backward (reverse) direction: (90+G)<(270+G)

Where:
3-328

P437/EN M/R-11-A // P437311650

P437

3 Operation

: Measured angle between the residual current and the neutral-point


displacement voltage

G = (IN): Setting DTOC : A ngl e ph i N PSx

Backward direction

VC-G

90+(IN)
VG-N = -VN-G

VA-G

(IN)

IN
Forward direction
VB-G
47Z1090A

Fig. 3-254: Directional characteristic of definite-time overcurrent protection (DTOC).


DTOC:
Starting IN>
[ 035 028 ]
DTOC:
Starting IN>>
[ 035 029 ]
DTOC:
Starting IN>>>
[ 035 030 ]

DTOC:
VNG> PSx

DTOC:
Starting IN>>>>
[ 035 031 ]

f0

VA-G
VB-G
VC-G

DTOC:
Angle VNG/IN
[ 009 004 ]

DTOC:
IN
402 625

DTOC:
Angle phi N PSx
[

(90+G)>(270+G)

(90+G)<(270+G)

Parameter

DTOC:
VNG> PSx

DTOC:
Angle phi N PSx

set
set
set
set

010
010
010
010

004
004
004
004

1
2
3
4

045
060
080
139

092
247
248
249

DTOC:
Fault N forward
[ 035 047 ]
DTOC:
Fault N backward
[ 035 048 ]

42Z50CGA

Fig. 3-255: Direction measurement of definite-time overcurrent protection (DTOC).

P437/EN M/R-11-A // P437311650

3-329

P437

3 Operation

After the operate delay has elapsed, a trip signal of the respective residual
current stage is issued if the set direction matches the measured direction.
DTOC:
Fault N forward
[ 035 047 ]
DTOC:
Fault N backward
[ 035 048 ]

DTOC:
Direction tIN> PSx
[

]
1
2
3

1: Forward directional
2: Backward directional
3: Non-directional
DTOC:
Trip signal tIN>
[ 035 043 ]

DTOC:
tIN> elapsed
[ 035 037 ]
DTOC:
Direction tIN>> PSx
[

]
1
2
3

1: Forward directional
2: Backward directional
3: Non-directional
DTOC:
Trip signal tIN>>
[ 035 044 ]

DTOC:
tIN>> elapsed
[ 035 038 ]
DTOC:
Direction tIN>>> PSx
[

]
1
2
3

1: Forward directional
2: Backward directional
3: Non-directional
DTOC:
Trip signal tIN>>>
[ 035 045 ]

DTOC:
tIN>>> elapsed
[ 035 039 ]
DTOC:
Direction tIN>>>>PSx
[ * ]
1
2
3
1: Forward directional
2: Backward directional
3: Non-directional

DTOC:
Trip sign. tIN>>>>
[ 035 046 ]

DTOC:
tIN>>>> elapsed
[ 035 040 ]

Parameter

DTOC:
Direction tIN> PSx

DTOC:
Direction tIN>> PSx

DTOC:
Direction tIN>>> PSx

DTOC:
Direction tIN>>>>PSx

set
set
set
set

072
072
072
072

072
072
072
072

072
072
072
072

072
072
072
072

1
2
3
4

032
042
082
091

033
043
083
092

034
044
084
093

035
045
085
094

42Z50CHA

Fig. 3-256: Trip signals of the DTOC residual current stages.

3-330

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.31.4.2

Settable timer start condition of the residual current system


The triggering of the timers for the residual current system can be set as
direction-dependent by setting the following parameter:
DT OC: tI N time r start PSx = With direction
The timers only start if the relevant OC threshold is exceeded and the direction
measured corresponds to the set direction of the respective stage:

D TOC : Dire cti on tIN> P Sx

DTOC: D irection tIN>> P Sx

DTOC: D irecti on tIN>>> PSx

D TOC : Dire ction tIN>>>>PSx

The relevant settings are:

Forward directional

Backward directional

Non-directional

This expanded logic is displayed in Fig. 3-259, (p. 3-334).


3.31.4.3

Settable Operation Mode During 1-Pole Dead Time of HSR


The operation mode of each residual current system timer stage and negativesequence overcurrent timer stage during the 1-pole dead time of the high-speed
reclosure (HSR) of an ARC cycle may be set individually.
The following setting parameters are available for the neutral OC elements:

D TOC : tI N> (1pH SR) PSx

D TOC : tI N>> ( 1pH SR ) P Sx

D TOC : tI N>>> ( 1pH SR ) P Sx

DTOC: t IN >>>> ( 1pH SR) PSx

The relevant settings are:

Normal: No change for the DTOC timer stage during a 1-pole dead time.

Normal: The directional decision is ignored during the 1-pole dead time; the
DTOC timer stage operates as if it where set to 'Non-directional'

Normal: During a 1-pole dead time the DTOC timer stage is automatically
blocked. If a starting was present it will be reset. The time delay stage is
also reset.

The same is valid for the negative-sequence elements, but here there are only
two setting options available:

D TOC : tI ne g> ( 1pH SR) PSx

D TOC : tI ne g>> (1pHSR) P Sx

D TOC : tI ne g>>> ( 1pHSR) PSx

DTOC: t In eg >>>>( 1pH SR ) P Sx

The relevant settings are:

3.31.4.4

Normal

Blocked

Neutralizing Directional Operation by Binary Signal Inputs


For each residual current system timer stage, a binary signal input is provided to
disable directional operation. While this binary input signal is TRUE, the stage
operates non-directional. If the stage is set to 'non-directional', then this input
has no influence.

P437/EN M/R-11-A // P437311650

3-331

P437

3 Operation

D TOC: Block . di r. t IN > E XT

DT OC : Blck . di r. tIN>> EXT

D TOC : Blk. dir. tIN>>> EX T

DTOC: Bl . dir. tIN>>>> EXT

This input function may also be applied to block the directional operation should a
measuring circuit failure occur (by using the signal from the associated m.c.b.).

DTOC:
tIneg> (1pHSR) PSx
[ * ]

0
1
0: Normal

& >1

DTOC:
tIneg> PSx
[ * ]

1: Blocked

ARC:
Dead time 1p running
[ 037 066 ]

0
DTOC:
tIneg> elapsed

DTOC:
Blocking tIneg> EXT
[ 041 102 ]

[ 035 033 ]

DTOC:
Starting Ineg>
[ 035 024 ]

Parameter

DTOC:
tIneg> (1pHSR) PSx

DTOC:
tIneg> PSx

set
set
set
set

002
002
002
002

072
073
074
075

1
2
3
4

160
161
162
163

023
023
023
023

47Z1119A

Fig. 3-257: DTOC operation of negative-sequence elements show for the stage Ineg> with the setting
D T O C : t I n e g > ( 1 p H S R ) P S x to D T O C : t I n e g > > > > ( 1 p H S R ) P S x = Blocked.

3-332

P437/EN M/R-11-A // P437311650

P437

3 Operation

DTOC:
tIN> (1pHSR) PSx
[

* Parameter

set
set
set
set

1
2
3
4

DTOC:
tIN> (1pHSR) PSx

DTOC:
Direction tIN> PSx

DTOC:
tIN> PSx

002
002
002
002

072
072
072
072

072
073
074
075

144
145
146
147

032
042
082
091

027
027
027
027

1
2

& >1

0: Normal
1: Non-directional
ARC:
Dead time 1p running
[ 037 066 ]

2: Blocked

DTOC:
Blocking tIN> EXT
[ 041 063 ]

& >1

&

DTOC:
Trip signal tIN>
[ 035 043 ]

DTOC:
Fault N forward

&

[ 035 047 ]
DTOC:
Fault N backward

&

[ 035 048 ]
DTOC:
Block. dir. tIN> EXT
[ 002 176 ]
DTOC:
Direction tIN> PSx
[

1
2
3
1: Forward directional

DTOC:
tIN> PSx

2: Backward directional
DTOC:
Starting IN>
[ 035 028 ]

3: Non-directional

DTOC:
tIN> elapsed
[ 035 037 ]

47Z1108A

Fig. 3-258: DTOC operation of neutral OC elements show for the stage IN> with the setting D T O C : t I N t i m e r
s t a r t P S x = With starting and D T O C : t I N > ( 1 p H S R ) P S x to D T O C : t I N > > > > ( 1 p H S R ) P S x set to Nondirectional or Blocked.

P437/EN M/R-11-A // P437311650

3-333

P437

3 Operation

DTOC:
tIN> (1pHSR) PSx
[

Parameter

DTOC:
tIN> (1pHSR) PSx

DTOC:
Direction tIN> PSx

DTOC:
tIN> PSx

set
set
set
set

002
002
002
002

072
072
072
072

072
073
074
075

1
2
3
4

144
145
146
147

032
042
082
091

027
027
027
027

1
2

& >1

0: Normal
1: Non-directional
2: Blocked
ARC:
Dead time 1p running
[ 037 066 ]
DTOC:
Blocking tIN> EXT
[ 041 063 ]

& >1
DTOC:
Fault N forward
[ 035 047 ]

&

DTOC:
Fault N backward
[ 035 048 ]

&

DTOC:
Block. dir. tIN> EXT
[ 002 176 ]
DTOC:
Direction tIN> PSx
[

1
2
3

DTOC:
tIN> PSx

1: Forward directional

DTOC:
Trip signal tIN>
[ 035 043 ]

2: Backward directional
3: Non-directional
DTOC:
Starting IN>
[ 035 028 ]

t
&

DTOC:
tIN> elapsed
[ 035 037 ]

47Z1107A

Fig. 3-259: DTOC operation of neutral OC elements show for the stage IN> with the setting D T O C : t I N t i m e r
s t a r t P S x = With direction and D T O C : t I N > ( 1 p H S R ) P S x to D T O C : t I N > > > > ( 1 p H S R ) P S x set to Nondirectional or Blocked.

3-334

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.31.5

Hold-Time Logic for Intermittent Ground Faults


A hold-time logic for the treatment of intermittent ground faults is available in
the P437.

As the IN> starting in the residual current stage commences, the hold time
is reset. At the same time, the starting time is accumulated when IN>
starting commences.

As IN> starting ends, the timer stage DTOC: Puls .prol. IN>,int PSx is
started and the charging of the accumulation buffer is thereby lengthened
by the set value of the timer stage.

The accumulation result is compared to the settable limit value at


DTOC: t IN >,int erm. P Sx.

If the limit value is reached and a general starting is present, then a trip
results (D TOC: Trip s ig. tI N>,intm .), which can be configured to the
trip commands 1 and 2.

MAI N: Fct .ass ig.tri p cmd.1 (Address 021 001)


MA IN : Fct.as sig.tri p cmd.2 (Address 021 002)

If the limit value is reached while the timer stage


D TOC : Puls.prol.IN >,i ntP Sx is running, then a trip will occur when the
next general starting phase commences.

With each release of the trigger stage IN>, the set hold-time D TOC: Holdt . tI N>,int m P Sx is restarted. When the hold time has elapsed or after the
hold-time logic has issued a trip (D TO C: Tr ip s ig. tI N>,in tm.)
accumulation is stopped and the accumulation buffer is cleared.

DTOC:
Puls.prol.IN>,intPSx
[ * ]
DTOC:
tIN>,interm. PSx
[ * ]
DTOC:
Hold-t. tIN>,intmPSx
[ * ]

&

DTOC:
Starting IN>
[ 035 028 ]

Hold-time logic

DTOC:
Trip sig. tIN>,intm.
[ 039 073 ]
DTOC:
t2 N
305 454

DTOC:
Pulse prolong. runn.
0

MAIN:
General starting
[ 036 000 ]

305 462

DTOC:
H.-time tIN>,i. runn
[ 040 086 ]
DTOC:
tIN>,interm. elapsed
[ 040 099 ]

Parameter

DTOC:
Puls.prol.IN>,intPSx

DTOC:
tIN>,interm. PSx

DTOC:
Hold-t. tIN>,intmPSx

set
set
set
set

017
073
074
075

017
073
074
075

017
073
074
075

1
2
3
4

055
042
042
042

056
038
038
038

057
039
039
039

49Z6449A

Fig. 3-260: Hold-time logic for definite-time characteristics.

P437/EN M/R-11-A // P437311650

3-335

P437

3 Operation

DTOC:
Starting IN>
[ 035 028 ]

DTOC:
Pulse prolong. runn.
305 462

DTOC:
H.-time tIN>,i. runn
[ 040 086 ]

DTOC:
t2 N
305 454

DTOC:
Trip sig. tIN>,intm.
[ 039 073 ]

Settings

DTOC:
Puls.prol.IN>,intPSx

DTOC:
tIN>,interm. PSx

DTOC:
Hold-t. tIN>,intmPSx

Setting = 80ms

Setting = 15ms

Setting = 300ms

49Z6450A

Fig. 3-261: Signal flow for values below the accumulation limit value.

3-336

P437/EN M/R-11-A // P437311650

P437

3 Operation

DTOC:
Starting IN>
[ 035 028 ]

DTOC:
Pulse prolong. runn.
305 462

DTOC:
H.-time tIN>,i. runn
[ 040 086 ]

DTOC:
t2 N
305 454

DTOC:
Trip sig. tIN>,intm.
[ 039 073 ]

<1>= Startings not


illustrated
have occurred
here.

Settings
DTOC:
Puls.prol.IN>,intPSx

DTOC:
tIN>,interm. PSx

DTOC:
Hold-t. tIN>,intmPSx

Setting = 80ms

Setting = 15ms

Setting = 300ms
49Z6451A

Fig. 3-262: Signal flow for values at the accumulation limit value.

P437/EN M/R-11-A // P437311650

3-337

P437

3.32

3 Operation

Inverse-Time Overcurrent Protection (Function Group IDMT)


The inverse-time overcurrent protection function (IDMT) operates with three
separate measuring systems for:

Phase currents system

Negative-sequence current

Residual current.

The inrush stabilization function may intervene in the functional sequence of the
IDMT function.

3.32.1

Disabling and Enabling IDMT Protection


IDMT protection can be disabled or enabled using setting parameters. Moreover,
enabling can be carried out separately for each parameter subset.

IDMT:
General enable USER
[ 017 096 ]
0
IDMT:
Enabled
[ 040 100 ]

1
0: No
1: Yes

IDMT:
Enable PSx
[ * ]

0
1
0: No
1: Yes

Parameter

IDMT:
Enable PSx

set
set
set
set

072
073
074
075

1
2
3
4

070
070
070
070

19Z5020A

Fig. 3-263: Disabling or enabling IDMT protection. (Only IDMT1 is shown; the logic, however, also applies to IDMT2
with different numerical addresses.)

3-338

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.32.2

Time-Dependent Characteristics
The measuring systems for phase currents, residual current and negativesequence current operate independently of each other and can be set
separately. The user can select from a large number of characteristics (see table
below). The measured variable is the maximum phase current, the negativesequence current, or the residual current, depending on the measuring system.
The tripping characteristics available for selection are shown in the following
figures (Fig. 3-264, (p. 3-340) to Fig. 3-267, (p. 3-342)).

No.

Tripping
Characteristic
Characteristic
settable factor:
k = 0.05 ... 10.00

Formula for the


Tripping
Characteristic

Definite Time

t=k

Per IEC 2553

t =k

Standard Inverse

I
ref

0.02

Very Inverse

13.50

1.00

Extremely Inverse

80.00

2.00

Long Time Inverse

120.00

1.00

t = k (
(I

Moderately Inverse

6
7

b
) -1

0.14

Per IEEE C37.112

Formula for the


Reset
Characteristic

a
(I

Constants

I
ref

)b - 1

tr =

+ c)

k R
I 2
(I
) -1
ref

0.0515

0.0200

0.1140

4.85

Very Inverse

19.6100

2.0000

0.4910

21.60

Extremely Inverse

28.2000

2.0000

0.1217

29.10

Per ANSI

t = k (
(I

I
ref

+ c)

tr =

) -1

k R
I 2
(I
) -1
ref

Normally Inverse

8.9341

2.0938

0.17966

9.00

Short Time Inverse

0.2663

1.2969

0.03393

0.50

10

Long Time Inverse

5.6143

1.0000

2.18592

15.75

11

RI-Type Inverse

t =k

1
0.339 -

12

RXIDG-Type Inverse

0.236
I
)
(I
ref

t = k (5.8 - 1.35 ln I

P437/EN M/R-11-A // P437311650

I
ref

3-339

P437

3 Operation

IDMT Tripping Characteristics per IEC 2553


Characteristic 2: IEC 2553, Very Inverse

Characteristic 1: IEC 2553, Standard Inverse


1000

1000

100

100
k=10

10

10

t/s

k=1

k=10

t/s

1
k=0.1
k=0.05

0.1

0.01

k=1

0.1

k=0.1
k=0.05

0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

I/Iref

I/Iref

Characteristic 3: IEC 2553, Extremely Inverse

Characteristic 4: IEC 2553, Long Time Inverse

1000

1000

100

100

k=10

10

10

t/s

k=10

k=1

t/s
1

k=0.1
k=0.05

k=1
0.1

0.1
k=0.1
k=0.05

0.01

0.01

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

I/Iref

I/Iref

Fig. 3-264: Tripping characteristics as per IEC 255-3.

3-340

P437/EN M/R-11-A // P437311650

P437

3 Operation

IDMT Tripping Characteristics per IEEE C37.112


Characteristic 6: IEEE C37.112, Very Inverse

Characteristic 5: IEEE C37.112, Moderately Inverse


1000

1000

100

100

10

10

k=10

t/s

k=10

t/s
1

k=1

1
k=1

0.1

k=0.1
k=0.05

0.01

0.1
k=0.1
k=0.05
0.01

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

I/Iref

I/Iref

Characteristic 7: IEEE C37.112, Extremely Inverse


1000

100

10

t/s

k=10
1
k=1
0.1
k=0.1
k=0.05

0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

I/Iref

Fig. 3-265: Tripping characteristics as per IEEE C37.112.

P437/EN M/R-11-A // P437311650

3-341

P437

3 Operation

IDMT Tripping Characteristics per ANSI


Characteristic 9: ANSI, Short Time Inverse

Characteristic 8: ANSI, Normally Inverse


1000

1000

100

100

10

10

t/s

k=10

t/s
1

k=10
k=1
0.1

0.1

k=1
k=0.1
k=0.05

0.01

0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 k=0.1
k=0.05

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

I/Iref

I/Iref

Characteristic 10: ANSI, Long Time Inverse


1000

100
k=10
10

t/s

k=1
1
k=0.1
k=0.05

0.1

0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

I/Iref

Fig. 3-266: Tripping characteristics as per ANSI.


IDMT Tripping Characteristics, RI-Type Inverse and RXIDG-Type Inverse
Characteristic 12: RXIDG-Type Inverse

Characteristic 11: RI-Type Inverse


1000

1000

100

100
k=10

10

k=10

10

t/s

k=1
1

t/s

k=1

1
k=0.1
k=0.05

0.1

0.01

k=0.1
k=0.05

0.1

0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

I/Iref

I/Iref

Fig. 3-267: RI-type inverse and RXIDGtype inverse tripping characteristics.

3-342

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.32.3

Enable Thresholds

Minimum Operate Value


A minimum operate value (threshold) may be defined for each of the phase
currents, the residual current and the negative-sequence current, valid for
function group IDMT. Each factor IDMT: Factor I,y (y=P for the phase
currents, y=N for the residual current, y=neg for the negative-sequence
current) is multiplied by the reference quantity (Iref,P or Iref,N or Iref,neg,
respectively) in order to form the minimum operate value. The timer stage is
triggered only when the current exceeds the set threshold.
Minimum Trip Time
A minimum trip time ID MT: Min. tri p ti me y PSx may be defined for the
phase currents (y=P), the residual current (y=N) and the negative-sequence
current (y=neg). The respective timer stage is started as soon as the
associated minimum operate value is exceeded. After the timer has elapsed, the
trip signal is issued, regardless of the value of the current.

t/s 10

neg

IDMT:
Iref,y PSx

IDMT:
Min. trip time y PSx

1
1

10

P
Parameter

IDMT:
Factor KI,P PSx

100

G
IDMT:
Factor KI,N PSx

neg
IDMT:
Factor KI,neg PSx

set 1

007 250

001 173

007 254

set 2

007 251

001 174

007 255

set 3

007 252

001 175

008 002

set 4

007 253

001 176

008 005

Parameter

IDMT:
Min. trip time P PSx

IDMT:
Min. trip time N PSx

set 1

072 077

072 079

072 078

set 2

073 077

073 079

073 078

neg
IDMT:
Min.trip time negPSx

set 3

074 077

074 079

074 078

set 4

075 077

075 079

075 078
45Z8004A

Fig. 3-268: Influence of the minimum operate value and the minimum trip time on the IDMT characteristics.

P437/EN M/R-11-A // P437311650

3-343

P437
3.32.4

3 Operation

Phase Current Stage


The three phase currents are monitored by the P437 to detect when they exceed
the set thresholds. The IDMT protection will trigger when the 1.05-fold of the set
reference current value is exceeded in one phase. The P437 will then determine
the maximum current flowing in the three phases and this value is used for
further processing. Depending on the characteristic selected and the current
magnitude the P437 will determine the tripping time. Moreover the tripping time
will under no circumstances fall below a settable minimum time threshold
irrespective of the current flow magnitude.
When the inrush stabilization function (see Section 3.12.5, (p. 3-89)) is triggered,
the phase current stage as well as the residual current stage is blocked.
However, when a phase starting is present then no subsequent triggering of the
inrush stabilization will be taken into account. (When a change from a singlephase fault to a two-phase fault or from a two-phase fault to a three-phase fault
had occurred, it was possible that, because of transients during the change, the
inrush stabilization was momentarily triggered which would reset the starting
and the timer.)
The inverse-time stage can be blocked by an appropriately configured binary
signal input.

3-344

P437/EN M/R-11-A // P437311650

P437

3 Operation

IDMT:
Bl.Start.Iref,P> Px
450 156

IDMT:
Enabled
[ 040 100 ]

&

MAIN:
Protection active
306 001

IDMT:
Starting A

IDMT:
Iref,P PSx
[
*
]

304 359

IDMT:
Starting B
304 360

IDMT:
Starting C

1.05 Iref

304 361

IA

&

IB

&

IC

&

Setting
IDMT:
Characteristic P PSx

IDMT:
Characteristic P PSx
[

0: Definite Time

IDMT:
Min. trip time P PSx
[

1: IEC Standard Inverse

2: IEC Very Inverse


3: IEC Extr. Inverse

IDMT:
Factor kt,P PSx
[

Setting
IDMT:
Release P PSx

4: IEC Long Time Inv.

5: IEEE Moderately Inv.

IDMT:
Hold time P PSx
[

1: Without delay

6: IEEE Very Inverse


7: IEEE Extremely Inv.

8: ANSI Normally Inv.

IDMT:
Release P PSx

2: Delayed as per char.

9: ANSI Short Time Inv.

10: ANSI Long Time Inv.


11: RI-Type Inverse

IDMT:
Factor KI,P PSx
[

IDMT:
Starting Iref,P>
[ 040 080 ]

12: RXIDG-Type Inverse

IDMT:
Block. tIref,P> EXT
[ 040 101 ]

c
IDMT:
Memory P clear
[ 040 110 ]
IP,max/Iref,P

IDMT:
Hold time P running
[ 040 053 ]
IDMT:
tIref,P> elapsed
[ 040 082 ]

Parameter

IDMT:
Iref,P PSx

IDMT:
Characteristic P PSx

set
set
set
set

072
073
074
075

072
073
074
075

1
2
3
4

050
050
050
050

056
056
056
056

Parameter

IDMT:
Factor kt,P PSx

IDMT:
Min. trip time P PSx

IDMT:
Hold time P PSx

IDMT:
Release P PSx

IDMT:
Factor KI,P PSx

set
set
set
set

072
073
074
075

072
073
074
075

072
073
074
075

072
073
074
075

007
007
007
007

1
2
3
4

053
053
053
053

077
077
077
077

071
071
071
071

059
059
059
059

250
251
252
253

45Z8034A

Fig. 3-269: Phase current stage for IDMT.

P437/EN M/R-11-A // P437311650

3-345

P437
3.32.5

3 Operation

Negative-Sequence Current Stage


According to the following formulas the P437 will determine the negativesequence current and positive-sequence current, taking into account the set
phase sequence (alternative terminology: Rotary field):
Phase sequence A-B-C (alternative terminology: clockwise rotating field):
1

I neg = 3 | (I A + a 2 I B + a I C) |



Phase sequence A-C-B (alternative terminology: anti-clockwise rotating field):
I neg =

1
3

| (I A + a I B + a 2 I C) |

a = e2j/3 = e j120

a 2 = e4j/3 = e j240

The negative-sequence current is monitored by the P437 to detect when it


exceeds the set thresholds. The IDMT protection will trigger when the 1.05-fold of
the set reference current value is exceeded by the negative-sequence current.
Depending on the characteristic selected and the residual current magnitude the
P437 will determine the tripping time. Moreover the tripping time will under no
circumstances fall below a settable minimum time threshold irrespective of the
negative-sequence current flow magnitude.
When the inrush stabilization function (Section 3.12.5, (p. 3-89)) is triggered, the
negative-sequence current stage is blocked.
The inverse-time stage can be blocked by an appropriately configured binary
signal input. In addition the inverse-time stage can also be automatically blocked
by single-pole or multi-pole starting (depending on the setting).

3-346

P437/EN M/R-11-A // P437311650

P437

3 Operation

IDMT:
Bl.Start.Iref,neg>
450 161

IDMT:
Enabled
[ 040 100 ]
MAIN:
Protection active

&

306 001

IDMT:
Iref,neg PSx
[
*
]

1.05 Iref

Ineg/Iref,neg

MAIN:
Phase sequence
[ 010 049 ]

&

IA

IDMT:
Starting Iref,neg>
[ 040 107 ]

Ineg

IB
IC

Setting
IDMT:
Character. neg. PSx

IDMT:
Character. neg. PSx
[
*
]
IDMT:
Factor kt,neg PSx
[
*
]

Setting
IDMT:
Release neg. PSx

0: Definite Time
1: IEC Standard Inverse

IDMT:
Min.trip time negPSx
[
*
]

2: IEC Very Inverse

IDMT:
Hold time neg PSx
[ * ]

4: IEC Long Time Inv.

3: IEC Extr. Inverse


5: IEEE Moderately Inv.
6: IEEE Very Inverse

IDMT:
Release neg. PSx
[
*
]

1: Without delay
2: Delayed as per char.

7: IEEE Extremely Inv.


8: ANSI Normally Inv.
9: ANSI Short Time Inv.

IDMT:
Factor KI,neg PSx
[
*
]

&

10: ANSI Long Time Inv.


11: RI-Type Inverse
12: RXIDG-Type Inverse

IDMT:
Block. tIref,neg>EXT
[ 040 102 ]
IDMT:
Memory neg clear

MAIN:
Bl. timer st. IN,neg
306 400

[ 040 111 ]
IDMT:
Hold time neg runn.
[ 040 113 ]
IDMT:
tIref,neg> elapsed
[ 040 109 ]

Parameter

IDMT:
Iref,neg PSx

IDMT:
Character. neg. PSx

set
set
set
set

072
073
074
075

072
073
074
075

1
2
3
4

051
051
051
051

057
057
057
057

Parameter

IDMT:
Factor kt,neg PSx

IDMT:
Min.trip time negPSx

IDMT:
Hold time neg PSx

IDMT:
Release neg. PSx

IDMT:
Factor KI,neg PSx

set
set
set
set

072
073
074
075

072
073
074
075

072
073
074
075

072
073
074
075

007
007
008
008

1
2
3
4

054
054
054
054

078
078
078
078

072
072
072
072

060
060
060
060

254
255
002
005

45Z8035A

Fig. 3-270: Negative-sequence current stage.

P437/EN M/R-11-A // P437311650

3-347

P437

3 Operation

3.32.6

Selecting the Measured Variable for the Residual Current Stage


A setting specifies which current will be used by the P437 as the residual current:
either the residual current calculated from the three phase currents or the
residual current directly measured at the fourth current transformer (T 4).

IDMT:
Evaluation IN PSx
[ * ]
IN

2
1

IA
IB
IC

1
1: Calculated

IDMT:
IN
307 100

2: Measured
Parameter

IDMT:
Evaluation IN PSx

set
set
set
set

072
073
074
075

1
2
3
4

075
075
075
075

19Z5022A

Fig. 3-271: Selecting the measured variable.

3.32.7

Residual Current Stage


The residual current is monitored by the P437 to detect when it exceeds the set
thresholds. The IDMT protection will trigger when the 1.05-fold of the set
reference current value is exceeded by the residual current. Depending on the
characteristic selected and the residual current magnitude the P437 will
determine the tripping time. Moreover the tripping time will under no
circumstances fall below a settable minimum time threshold irrespective of the
residual current flow magnitude.
The inverse-time stage can be blocked by an appropriately configured binary
signal input. In addition the inverse-time stage can also be automatically blocked
by single-pole or multi-pole starting (depending on the setting).

3-348

P437/EN M/R-11-A // P437311650

P437

3 Operation

IDMT:
Bl.Start.Iref,N>
450 160

IDMT:
Enabled
[ 040 100 ]

IDMT:
Iref,N PSx

c
1.05 Iref
IDMT:
Starting Iref,N>
[ 040 081 ]

&

IN/Iref,N

IDMT:
IN
307 100

IDMT:
Characteristic N PSx
[ * ]

IDMT:
Characteristic N PSx

IDMT:
Factor kt,N PSx
[ * ]

1: IEC Standard Inverse

IDMT:
Min. trip time N PSx
[ * ]
IDMT:
Hold time N PSx
[ * ]
Setting
IDMT:
Release N PSx

IDMT:
Release N PSx
[ * ]

Setting

0: Definite Time
2: IEC Very Inverse
3: IEC Extr. Inverse
4: IEC Long Time Inv.
5: IEEE Moderately Inv.
6: IEEE Very Inverse
7: IEEE Extremely Inv.
8: ANSI Normally Inv.
9: ANSI Short Time Inv.
10: ANSI Long Time Inv.

1: Without delay

IDMT:
Factor KI,N PSx
[ * ]

2: Delayed as per char.

11: RI-Type Inverse


12: RXIDG-Type Inverse

&
IDMT:
Block. tIref,N> EXT
[ 040 103 ]
MAIN:
Bl. timer st. IN,neg

IDMT:
Memory N clear
[ 040 112 ]

306 400

IDMT:
Hold time N running
[ 040 054 ]

Parameter

IDMT:
Iref,N PSx

set
set
set
set

072
073
074
075

1
2
3
4

IDMT:
tIref,N> elapsed
[ 040 083 ]

052
052
052
052

Parameter

IDMT:
Characteristic N PSx

IDMT:
Factor kt,N PSx

IDMT:
Min. trip time N PSx

IDMT:
Hold time N PSx

IDMT:
Release N PSx

IDMT:
Factor KI,N PSx

set
set
set
set

072
073
074
075

072
073
074
075

072
073
074
075

072
073
074
075

072
073
074
075

001
001
001
001

1
2
3
4

058
058
058
058

055
055
055
055

079
079
079
079

073
073
073
073

061
061
061
061

173
174
175
176

45Z8036A

Fig. 3-272: Residual current stage for IDMT.

3.32.8

Holding Time
Depending on the current flow the P437 will determine the tripping time and a
timer stage is started. The setting of the hold time defines the time period during
which the IDMT protection starting time is stored after the starting has dropped
out. Should starting recur during the hold time period then the time of the
renewed starting will be added to the time period stored. When the starting
times sum reach the tripping time value determined by the P437 then the
corresponding signal will be issued. Should starting not recur during the hold
time period then, depending on the setting, the memory storing the accumulated
starting times value will either be cleared without delay or according to the

P437/EN M/R-11-A // P437311650

3-349

P437

3 Operation

characteristic set. In Fig. 3-273, (p. 3-350), the effect of hold time is shown by
the example of a phase current stage.

Case A
IDMT:
Starting Iref,P>
[ 040 080 ]

IDMT:
Hold time P running
[ 040 053 ]

Determ. trip time

Per characteristic
Non-delayed

IDMT:
tIref,P> elapsed
[ 040 082 ]

Case B
IDMT:
Starting Iref,P>
[ 040 080 ]

IDMT:
Hold time P running
[ 040 053 ]

Determ. trip time


Non-delayed
Per characteristic

IDMT:
tIref,P> elapsed
[ 040 082 ]

Parameter

IDMT:
Hold time P PSx

set
set
set
set

072
073
074
075

1
2
3
4

071
071
071
071

19Z5025A

Fig. 3-273: Effect of hold time shown with a phase current stage as an example. Example A: Hold time determined
is not reached. Example B: Hold time determined is reached.

3-350

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.33

Thermal Overload Protection (Function Group THERM)


Using this function, thermal overload protection can be implemented.

Disabling and Enabling Thermal Overload Protection


Thermal overload protection may be disabled or enabled by setting parameters.
Moreover, enabling can be carried out separately for each parameter subset.

THERM:
General enable USER
[ 022 050 ]

0
1

THERM:
Enabled
[ 040 068 ]

&

0: No
1: Yes

THERM:
Enable PSx
[

0
1
0: No
1: Yes
PSU:
PS y active
[ * ]

PSU:
PS y active

Parameter

THERM:
Enable PSx

1
2
3
4

036
036
036
036

set
set
set
set

072
073
074
075

090
091
092
093

1
2
3
4

175
175
175
175

19Z6112B

Fig. 3-274: Disabling or enabling thermal overload protection.

3.33.1

Readiness of Thermal Overload Protection


Thermal overload protection is not ready (THERM: N ot re ady) if one of the
following conditions applies:

3.33.2

Thermal overload protection is disabled.

Thermal overload protection is blocked because of a fault in the coolant


temperature (ambient) acquisition.

Thermal overload protection is blocked because of an incorrect setting.

The thermal replica is blocked via an appropriately configured binary signal


input.

Operating Modes
Two operating modes can be selected for thermal overload protection.

Relative replica

Absolute replica

Either operating mode can be enabled or disabled individually. Only one of the
operating modes may be enabled for thermal overload protection. However, if
both operating modes are enabled at the same time, the thermal overload
protection is blocked and the error message TH ERM: Sett ing e rror,block . is
generated by the P437.

P437/EN M/R-11-A // P437311650

3-351

P437
3.33.3

3 Operation

Coolant Temperature Effect


To permit coolant temperature (ambient) acquisition, the analog (I/O) module Y
with a 20 mA current input and the PT100 input must be fitted.
One of the 11 measuring inputs listed above is selected for the primary
measurement of coolant temperature by setting the parameter THERM: S ele ct
mea s.inputPSx.
If the parameters THERM: Sel e ct me as.in putPSx have been set incorrectly
the thermal overload protection is blocked and the error message
THERM: Setti ng error,block. is generated.
An open measuring circuit, due to a broken wire, is determined by the measured
value inputs (function group MEASI). This will result in the issuance of these
signals:

MEA SI: Open circ. 20mA i np.

MEA SI: PT100 faul ty

The thermal model uses these signals as a criterion to determine a fault in the
coolant temperature measurement. A fault at both measured value inputs
selected will lead to the issuance of the signal THE RM: CTA er ror.
The setting for THERM: Fu nct.f .CTA fail .PSx determines how the thermal
overload protection is to continue functioning when the coolant temperature
measurement has failed. The following functions can be selected to guarantee
continued and stable performance of the thermal overload protection when the
coolant temperature measurement has failed.

Default temperature value:


The coolant temperature set at THE RM: Coolant t emp. PSx is applied.
The thermal overload protection function is not blocked.
As a rule there is an erratic change of the measured value when a fault has
occurred in the coolant temperature measurement. The temperature
measured before such an erratic change is stored and applied. The thermal
overload protection function is not blocked.

Last measured temperature:


The coolant temperature set at THE RM: Coolant te mp. PSx is applied if
no last measured values are available because a device warm restart or a
parameter subset selection was carried out.

Blocking:
The signals THERM: W arni ng and TH ER M: Trip signal are reset and
blocked. The thermal model will then be continued and displayed on the
basis of the measured current alone. All further measured values are issued
as Not measured.

All parameters relevant to coolant temperature (ambient) acquisition are hidden


if the analog module Y has not been fitted in the P437. The tripping time is
calculated by including the setting for TH ER M: Coolant temp. PSx.

3-352

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.33.4

Thermal Overload Protection Operation without Coolant


Temperature (Ambient) Acquisition
In order to ensure thermal overload protection, without taking into account an
offset due to a variable coolant temperature, it is recommended to set the
THE RM: Coolant temp. PSx parameter to the maximum permitted coolant
temperature.

THERM:
Select meas.inputPSx
[ * ]

0
1
2

&

THERM:
With CTA

0: Default temp. value

305 201

1: From PT100
2: From 20 mA input

&

MEASI:
PT100 faulty
[ 040 190 ]

&

MEASI:
Overload 20mA input
[ 040 191 ]
MEASI:
Open circ. 20mA inp.

THERM:
CTA error
[ 039 111 ]

[ 040 192 ]
THERM:
CTA error EXT
[ 038 062 ]

SFMON:
CTA error
[ 098 034 ]

THERM:
Funct.f.CTA fail.PSx
[ * ]

1
2

&

THERM:
Block. by CTA error
305 200

1: Default temp. value


2: Last meas.temperat.
3: Blocking

Parameter

THERM:
Select meas.inputPSx

THERM:
Funct.f.CTA fail.PSx

set
set
set
set

072
073
074
075

076
077
078
079

1
2
3
4

177
177
177
177

177
177
177
177

45Z8010A

Fig. 3-275: Coolant temperature monitoring.

3.33.5

Relative Replica
The rated operating current of the protected object and its overload tolerance for
maximum coolant (ambient) temperature are the basis of the relative thermal
replica.
In the Relative replica operating mode, the following settings have to be made
for thermal overload protection:

The rated operating current of the protected object: THE RM: Iref PSx

The tripping threshold trip is set at THERM: t r ip PSx.

If coolant temperature (ambient) acquisition is used, the following parameters


must be set:

The maximum permissible temperature of the protected object max,


THERM: Max .obj ect te mp. PSx

The maximum coolant temperature (maximum ambient) c,max,


THERM: Max . cool. t e mp. P Sx

P437/EN M/R-11-A // P437311650

3-353

P437
3.33.6

3 Operation

Absolute Replica
The thermal limit current of the protected object is the reference current of the
absolute thermal replica. For this limit current, an overtemperature results at the
maximum coolant temperature.
In the Absolute replica operating mode, the following parameters have to be set
for thermal overload protection:

The thermal limit current of the protected object: IDMT: Min. trip time N
P Sx

The limit temperature for tripping max, THE RM: Max.object tem p. PSx

The overtemperature as a result of a persistent limit current (max c,max ), THERM: O/T f. Ire f pers . PSx

The maximum permitted coolant temperature c,max is derived from the difference
between the T H E R M : M a x . o b j e c t t e m p . P S x and T H E R M : O / T f . I r e f p e r s .
P S x settings.

3-354

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.33.7

Tripping Characteristics
The maximum RMS phase current I is used to track a first-order thermal replica
as specified in IEC 255-8. Other than the operating mode dependent settings the
following parameters will govern the tripping time:

The set thermal time constant of the protected object,


THERM: Tim.cons t.1,>Ibl PSx

The accumulated thermal load 0

The current measured coolant temperature c

The tripping threshold in the two operating modes is calculated as follows:


(I

t = ln
(I

I
ref

)2 - 0

a - a,max
)2 - trip (1 -
)
ref
max - a,max
I

The trip tripping threshold is set to a fixed value of 100% if the operating mode
is Absolute replica.

/%

10000

1000

/ min
100
200
110

10

1000

50

t / min
1

200
110

30

50

0.1

200
110

0.01

50

0.001
0

I / I ref

10

11

D5Z50BEB_EN

Fig. 3-276: Tripping characteristics of thermal overload protection (tripping characteristics apply to P = 0 % and
identical settings for the maximum permissible coolant temperature and coolant temperature).

P437/EN M/R-11-A // P437311650

3-355

P437
3.33.8

3 Operation

Warning Signal
Depending on the selected operating mode, a warning signal can be set at one of
the following parameters:

Relative replica: THERM: warni ng P Sx

Absolute replica: THERM: Warni ng tem p. PSx

Additionally, a time-to-tripping threshold (pre-trip time) can be set. When the


time left until tripping falls below this setting, a warning signal will be issued.

3.33.9

Trip
The trip threshold is set according to the selected operating mode with the
following parameters:

Relative replica: THERM: tri p PSx

Absolute replica: THERM: Max.obje ct te m p. PSx

If a trip command is issued, the trip signal is maintained until the status of the
thermal replica has decreased by the value set at TTHERM: Hystere s. ,tr ip
PS x, at least for a fixed time of 5 s.

3.33.10

Cooling
If the current falls below the default threshold of 0.1 Iref, the thermal replica is
applied with the time constant set at THERM: Ti m.const.2,<Ibl PSx. This
element in the thermal model takes account of the cooling characteristics of
stopped motors.
These two time constants should be set to the same value for transformers and
power lines.

3-356

P437/EN M/R-11-A // P437311650

P437

3 Operation

IA

THERM:
I

COMP

IB

305 202

IC
IP,max

MAIN:
Protection active

AR_MV

&

306 001

THERM:
Enabled
[ 040 068 ]

THERM:
Starting k*Iref>
[ 041 108 ]

THERM:
Block replica EXT
[ 041 074 ]
THERM:
Block. by CTA error

&

305 200

THERM:
Tim.const.1,>Ibl PSx
[ * ]

c
THERM:
Iref PSx
[ * ]

<0.1 Iref

THERM:
Tim.const.2,<Ibl PSx
[ * ]

THERM:
Start.fact.OL_RC PSx
[ * ]

kIref

THERM:
O/T f.Iref pers. PSx
[ * ]
THERM:
Warning temp. PSx
[ * ]

THERM:
c Max.object temp. PSx
[ * ]

THERM:
Absolute replica
[ 022 065 ]

THERM:
c Max. cool. temp. PSx
[ * ]
c

THERM:
warning PSx
[ * ]

THERM:
trip PSx
[ * ]

THERM:
Coolant temp. PSx
[ * ]

0
1
0: No
1: Yes

THERM:
Relative replica
[ 022 064 ]

THERM:
Within pre-trip time
[ 041 109 ]
SFMON:
Setting error THERM
[ 098 035 ]
THERM:
Setting error,block.
[ 039 110 ]
THERM:
Warning
[ 039 025 ]
THERM:
Trip signal
[ 039 020 ]

THERM:
Hysteres. ,trip PSx
[ * ]
THERM:
Warning pre-trip PSx
[ * ]

0
1

THERM:
Buffer empty
[ 039 112 ]

0: No
1: Yes

THERM:
With CTA

THERM:
Status THERM replica
[ 004 016 ]

305 201

Coolant temperature

THERM:
Object temperature
[ 004 137 ]
THERM:
Coolant temperature
[ 004 149 ]

I/Iref

THERM:
Reset replica
[ 039 061 ]
c

Parameter

THERM:
Iref PSx

THERM:
Start.fact.OL_RC PSx

THERM:
Tim.const.1,>Ibl PSx

set
set
set
set

072
073
074
075

072
073
074
075

072
073
074
075

1
2
3
4

179
179
179
179

180
180
180
180

THERM:
Pre-trip time left
[ 004 139 ]
THERM:
Temp. offset replica
[ 004 109 ]
THERM:
Coolant temp. p.u.
[ 004 178 ]
THERM:
Object temp. p.u.
[ 004 179 ]

187
187
187
187

Parameter

THERM:
Tim.const.2,<Ibl PSx

THERM:
O/T f.Iref pers. PSx

THERM:
Warning temp. PSx

THERM:
Max.object temp. PSx

set
set
set
set

072
073
074
075

072
073
074
075

072
073
074
075

072
073
074
075

1
2
3
4

188
188
188
188

167
167
167
167

153
153
153
153

THERM:
Therm. replica p.u.
[ 004 017 ]
THERM:
Current I,therm prim
[ 007 220 ]

182
182
182
182

THERM:
Current I,therm p.u
[ 007 221 ]

Parameter

THERM:
Max. cool. temp. PSx

THERM:
warning PSx

THERM:
trip PSx

THERM:
Coolant temp. PSx

THERM:
Hysteres. ,trip PSx

THERM:
Warning pre-trip PSx

set
set
set
set

072
073
074
075

072
073
074
075

072
073
074
075

072
073
074
075

072
073
074
075

072
073
074
075

1
2
3
4

185
185
185
185

184
184
184
184

181
181
181
181

186
186
186
186

183
183
183
183

191
191
191
191

19Z8042A

Fig. 3-277: Thermal overload protection.

3.33.11

Resetting
The thermal replica may be reset either via a setting parameter or via an
appropriately configured binary signal input. Resetting is possible even when

P437/EN M/R-11-A // P437311650

3-357

P437

3 Operation

thermal overload protection is disabled. Thermal overload protection can be


blocked via an appropriately configured binary signal input.

THERM:
Reset replica USER
[ 022 061 ]

0
1

THERM:
Reset replica
[ 039 061 ]

0: don't execute
1: execute

THERM:
Enabled
[ 040 068 ]
THERM:
Reset replica EXT
[ 038 061 ]

Q9Z5020A

Fig. 3-278: Resetting the thermal replica.

3-358

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.34

Under and Overvoltage Protection (Function Group V<>)


The time-voltage protection function evaluates the fundamental wave of the
phase voltages and of the neutral-point displacement voltage as well as the
positive-sequence voltage and negative-sequence voltage obtained from the
fundamental waves of the three phase-to-ground voltages.

3.34.1

Disabling and Enabling V<> Protection


V<> protection can be disabled or enabled using setting parameters. Moreover,
enabling can be carried out separately for each parameter subset.

3.34.2

V<> Protection Readiness


V<> protection is ready if it is enabled and no fault has been detected in the
voltage-measuring circuit by the measuring-circuit monitoring function.

V<>:
General enable USER
[ 023 030 ]

0
1
0: No

V<>:
Enabled
[ 040 066 ]

1: Yes

MCMON:
Meas. circ. V faulty
[ 038 023 ]

V<>:
Ready
[ 042 003 ]
V<>:
Not ready
[ 042 004 ]

45Z8085A

Fig. 3-279: Enabling, disabling and readiness of V<> protection.

P437/EN M/R-11-A // P437311650

3-359

P437

3 Operation

3.34.3

Minimum Current Monitoring


There is an optional enabling threshold available with the V<> element which is
based on minimum current monitoring for the undervoltage stages (V<, V<<,
V<<<, Vpos<, Vpos<<).
The following two settings may be used to activate the operating mode for
minimum current monitoring and to set the enabling threshold:

V <>: I enable V< PSx

V <>: Op. mode V < mon. P Sx

The undervoltage stages are blocked if during active monitoring the set
threshold of at least one phase is not exceeded by the phase currents.

V<>:
Op. mode V< mon. PSx
[

]
V<>:
V< ready

460 506

1
0: Without
1: With

V<>:
I enable V< PSx
[

IA
IB
IC

Parameter

V<>:
Op. mode V< mon. PSx

V<>:
I enable V< PSx

set
set
set
set

001
001
001
001

001
001
001
001

1
2
3
4

162
163
164
165

155
159
160
161

19Z8089A

Fig. 3-280: Enabling threshold for the undervoltage stages.

3-360

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.34.4

Monitoring the Phase Voltages


The P437 checks the voltages to determine whether they exceed or fall below set
thresholds. Dependent on the set operating mode of V<> protection, either the
phase-to-ground voltages (Star operating mode) or the phase-to-phase voltages
(Delta operating mode) are monitored. The triggers are followed by timer stages
that can be blocked via appropriately configured binary signal inputs.
If undervoltage monitoring decisions are to be included in the trip commands,
then it is recommended that transient signals be used. Otherwise the trip
command would always be present when the system voltage was disconnected,
and it would therefore not be possible to close the circuit breaker again.

V<>:
Operating mode PSx
[ * ]
MAIN:
Protection active
306 001

V<>:
Ready
[ 042 003 ]
fnom
VA-G
VB-G
fnom

VC-G
fnom

fnom
VA-G 3

fnom
2

VB-G 3

fnom
VC-G 3

1VA(-B)
1

1VB(-C)
1VC(-A)

1: Delta
2: Star
Parameter

V<>:
Operating mode PSx

set
set
set
set

076
077
078
079

1
2
3
4

001
001
001
001

47Z0147A

Fig. 3-281: Selection of the measured values.

P437/EN M/R-11-A // P437311650

3-361

P437

3 Operation

V<>:
Hyst. V<> meas. PSx
[ * ]
V<>:
tV> PSx
[ * ]

V<>:
Hyst. V<> meas. PSx
[ * ]
V<>:
V> PSx
[ * ]

V<>:
tV> elapsed
[ 041 034 ]

1VA(-B)
1VB(-C)

V<>:
Starting V>
[ 041 030 ]

1VC(-A)
V<>:
tV> 3-pole PSx
[ * ]
V<>:
Blocking tV> EXT
[ 041 068 ]

V<>:
tV> 3-pole elapsed
[ 041 098 ]
V<>:
Starting V> 3-pole
[ 041 097 ]
V<>:
tV>> PSx
[ * ]

V<>:
V>> PSx
[ * ]
V<>:
tV>> elapsed
[ 041 035 ]
V<>:
Starting V>>
[ 041 096 ]
V<>:
tV>> 3-pole PSx
[ * ]
V<>:
Blocking tV>> EXT
[ 041 069 ]

V<>:
tV>> 3-pole elapsed
[ 010 227 ]
V<>:
Starting V>>>
[ 010 231 ]

V<>:
Starting V>/>> A(-B)
[ 041 031 ]

V<>:
Starting V>/>> B(-C)
[ 041 032 ]

Parameter

V<>:
V> PSx

V<>:
tV> PSx

V<>:
tV> 3-pole PSx

set
set
set
set

076
077
078
079

076
077
078
079

076
077
078
079

1
2
3
4

003
003
003
003

005
005
005
005

V<>:
Starting V>/>> C(-A)
[ 041 033 ]

027
027
027
027

Parameter

V<>:
V>> PSx

V<>:
tV>> PSx

V<>:
tV>> 3-pole PSx

V<>:
Hyst. V<> meas. PSx

set
set
set
set

076
077
078
079

076
077
078
079

011
011
011
011

076
077
078
079

1
2
3
4

004
004
004
004

006
006
006
006

092
094
095
096

048
048
048
048

19Z8091A

Fig. 3-282: Overvoltage monitoring, Part 1: stages V> and V>>.

3-362

P437/EN M/R-11-A // P437311650

P437

3 Operation

V<>:
Hyst. V<> meas. PSx
[ * ]
V<>:
tV>>> PSx
V<>:
Hyst. V<> meas. PSx
[

V<>:
V>>> PSx
[

]
V<>:
tV>>> elapsed
[ 010 233 ]

1VA(-B)
1VB(-C)

V<>:
Starting V>>>
[ 010 231 ]

1VC(-A)
V<>:
tV>>> 3-pole PSx
[

V<>:
Blocking tV>>> EXT
[ 010 246 ]

V<>:
tV>>> 3-pole elapsed
[ 010 234 ]
V<>:
Starting V>>> 3-pole
[ 010 232 ]

Parameter

V<>:
V>>> PSx

V<>:
tV>>> PSx

V<>:
tV>>> 3-pole PSx

V<>:
Hyst. V<> meas. PSx

set
set
set
set

011
011
011
011

011
011
011
011

011
011
011
011

076
077
078
079

1
2
3
4

075
076
077
078

079
080
081
082

099
105
117
118

048
048
048
048

19Z8092A

Fig. 3-283: Overvoltage monitoring, Part 2: stage V>>>.

P437/EN M/R-11-A // P437311650

3-363

P437

3 Operation

V<>:
Blocking tV< EXT
[ 041 070 ]

V<>:
tV< PSx
[ * ]

V<>:
Hyst. V<> meas. PSx
[ * ]
V<>:
V< ready
V<>:
tV< elapsed
[ 041 041 ]

V<>:
V< PSx
[

]
Setting(s) blocked

1VA(-B)
1VB(-C)

V<>:
Starting V<
[ 041 037 ]

V<>:
tV< 3-pole PSx
[ * ]

1VC(-A)

V<>:
Fault V<
[ 041 110 ]

V<>:
tV< 3-pole elapsed
[ 042 006 ]

Setting(s) blocked
V<>:
Starting V< 3-pole
[ 042 005 ]

V<>:
tV<< PSx
[ * ]

V<>:
Fault V< 3-pole
[ 041 111 ]
V<>:
V<< PSx
[ * ]

V<>:
tV<< elapsed
[ 041 042 ]
Setting(s) blocked

V<>:
Starting V<<
[ 041 099 ]

V<>:
tV<< 3-pole PSx
[ * ]

V<>:
Fault V<<
[ 041 112 ]

V<>:
Blocking tV<< EXT
[ 041 071 ]

V<>:
tV>> 3-pole elapsed
[ 010 227 ]
Setting(s) blocked
V<>:
tV< elaps. transient
[ 042 023 ]

V<>:
Starting V<< 3-pole
[ 010 228 ]

V<>:
tV< 3p elaps. trans.
[ 042 024 ]
V<>:
tV<< elapsed trans.
[ 042 025 ]
V<>:
tV<< 3p elaps. trans
[ 010 230 ]

V<>:
Fault V<< 3-pole
[ 011 132 ]

Parameter

V<>:
Hyst. V<> meas. PSx

set
set
set
set

076
077
078
079

1
2
3
4

V<>:
Starting V</<< A(-B)
[ 041 038 ]
V<>:
Starting V</<< B(-C)
[ 041 039 ]

048
048
048
048

V<>:
Starting V</<< C(-A)
[ 041 040 ]

Parameter

V<>:
V< PSx

V<>:
tV< PSx

V<>:
tV< 3-pole PSx

V<>:
V<< PSx

V<>:
tV<< PSx

V<>:
tV<< 3-pole PSx

set
set
set
set

076
077
078
079

076
077
078
079

076
077
078
079

076
077
078
079

076
077
078
079

011
011
011
011

1
2
3
4

007
007
007
007

009
009
009
009

028
028
028
028

008
008
008
008

010
010
010
010

119
124
125
126

19Z8093A

Fig. 3-284: Undervoltage monitoring, Part 1: stages V< and V<<. (Transient pulse: See following diagram.)

3-364

P437/EN M/R-11-A // P437311650

P437

3 Operation

V<>:
Blocking tV<<< EXT
[ 010 247 ]

V<>:
tV<<< PSx
[ * ]

V<>:
Hyst. V<> meas. PSx
[ * ]
V<>:
V< ready
V<>:
tV<<< elapsed
[ 010 237 ]

V<>:
V<<< PSx
[ * ]
Setting(s) blocked
1VA(-B)
1VB(-C)

V<>:
Starting V<<<
[ 010 235 ]

V<>:
tV<<< 3-pole PSx
[ * ]

1VC(-A)

V<>:
Fault V<<<
[ 011 134]

V<>:
tV<<< 3-pole elapsed
[ 010 239 ]

Setting(s) blocked

V<>:
Starting V<<< 3-pole
[ 010 236 ]
V<>:
Fault V<<< 3-pole
[ 011 133 ]

V<>:
tTransient pulse PSx
[
*
]

V<>:
tTransient pulse PSx
[ * ]

V<>:
tV< elapsed
[ 041 041 ]

V<>:
tV< elaps. transient
[ 042 023 ]

V<>:
tV< 3-pole elapsed
[ 042 006 ]

V<>:
tV< 3p elaps. trans.
[ 042 024 ]

V<>:
tV<< elapsed
[ 041 042 ]

V<>:
tV<< elapsed trans.
[ 042 025 ]

V<>:
tV<< elapsed
[ 041 042 ]

V<>:
tV<< 3p elaps. trans
[ 010 230 ]
V<>:
tV<<< elaps.transien
[ 010 238 ]
V<>:
tV<<< 3p elaps.trans
[ 010 240]
V<>:
tV</<</<<< el.trans
[ 042 007 ]

Parameter

V<>:
V<<< PSx

V<>:
tV<<< PSx

V<>:
tV<<< 3-pole PSx

V<>:
Hyst. V<> meas. PSx

V<>:
tTransient pulse PSx

set
set
set
set

011
011
011
011

011
011
011
011

011
011
011
011

076
077
078
079

076 029

1
2
3
4

083
083
083
083

088
088
088
088

127
127
127
127

048
048
048
048

077 029
078 029
079 029

19Z8094A

Fig. 3-285: Undervoltage monitoring, Part 2: stage V<<< and transient pulse for stages V</<</<<<.

P437/EN M/R-11-A // P437311650

3-365

P437
3.34.5

3 Operation

Monitoring the Positive- and Negative-Sequence Voltages


The P437 determines the positive-sequence and negative-sequence voltages
from the fundamental components of the phase-to-ground voltages according to
the formulas given below. This is based on the MA IN: Phase seque nce setting
(alternative terminology: Rotary field).
Phase sequence A-B-C (clockwise rotating field)

Negative-sequence voltage:
Vneg =

| (VAG + a2 VBG + a VCG) |

Positive-sequence voltage:
Vpos =

3-366

1
3
1
3

| (VAG + a VBG + a2 VCG) |

P437/EN M/R-11-A // P437311650

P437

3 Operation

Phase sequence A-C-B (anti-clockwise rotating field)

Negative-sequence voltage:
Vneg =

| (VAG + a VBG + a2 VCG) |

Positive-sequence voltage:
Vpos =

1
3
1
3

| (VAG + a2 VBG + a VCG) |

Symbols used:
a = e2j/3 = e j120

a 2 = e4j/3 = e j240

MAIN:
Phase sequence
[ 010 049 ]
MAIN:
Protection active

&

306 001

V<>:
Ready
[ 042 003 ]

fnom
VA-G

V<>:
Vpos
305 250

fnom
VB-G

Vpos

fnom
VC-G

Vneg

V<>:
Vneg
305 251

D5Z50AYB

Fig. 3-286: Determination of positive- and negative-sequence voltages. (Note: The previous terminology for
MAIN: Phase sequence was MAIN: Rotary field.)

The positive-sequence voltage is monitored to determine whether it exceeds or


falls below set thresholds, and the negative-sequence voltage is monitored to
determine whether it exceeds set thresholds. If the voltage exceeds or falls
below the set thresholds, then a signal is issued once the set operate delays
have elapsed. The timer stages can be blocked by appropriately configured
binary signal inputs.
If undervoltage monitoring decisions are to be included in the trip commands,
then it is recommended that transient signals be used. Otherwise the trip
command would always be present when the system voltage was disconnected,
and it would therefore not be possible to close the circuit breaker again.

P437/EN M/R-11-A // P437311650

3-367

P437

3 Operation

V<>:
Blocking tVpos> EXT
[ 041 090 ]

V<>:
Hyst. V<> deduc. PSx
[ * ]

V<>:
Hyst. V<> deduc. PSx
[ * ]

V<>:
tVpos> PSx
[ * ]

V<>:
Vpos> PSx
[ * ]

V<>:
tVpos> elapsed
[ 042 012 ]

V<>:
Vpos
305 250

V<>:
Starting Vpos>
[ 042 010 ]

V<>:
Blocking tVpos>> EXT
[ 041 091 ]
V<>:
tVpos>> PSx
[ * ]
V<>:
Vpos>> PSx
[ * ]

V<>:
tVpos>> elapsed
[ 042 013 ]

V<>:
Blocking tVpos< EXT
[ 041 092 ]

V<>:
Starting Vpos>>
[ 042 011 ]

V<>:
tVpos< PSx
[ * ]

V<>:
V< ready
460 506

V<>:
Vpos< PSx
[ * ]

V<>:
tVpos< elapsed
[ 042 016 ]

Setting(s) blocked
V<>:
Starting Vpos<
[ 042 014 ]

V<>:
tVpos<< PSx
[ * ]

V<>:
Blocking tVpos<< EXT
[ 041 093 ]

V<>:
Fault Vpos<
[ 041 113 ]

V<>:
tVpos<< elapsed
[ 042 017 ]
V<>:
Vpos<< PSx
[ * ]

Setting(s) blocked
V<>:
Starting Vpos<<
[ 042 015 ]
V<>:
Fault Vpos<<
[ 041 114 ]

V<>:
tTransient pulse PSx
[ * ]

Parameter
set
set
set
set

1
2
3
4

Parameter
set
set
set
set

1
2
3
4

Parameter
set
set
set
set

1
2
3
4

V<>:
Vpos> PSx
076 015
077 015
078 015
079 015

V<>:
tVpos> PSx
076 017
077 017
078 017
079 017

V<>:
Vpos>> PSx
076 016
077 016
078 016
079 016

V<>:
tVpos>> PSx
076 018
077 018
078 018
079 018

V<>:
Vpos< PSx
076 019
077 019
078 019
079 019

V<>:
tVpos< PSx
076 021
077 021
078 021
079 021

V<>:
tVpos< elaps. trans.
[ 042 026 ]
V<>:
tVpos<< elaps.trans.
[ 042 027 ]
V<>:
tVpos</<< elap.trans
[ 042 018 ]

V<>:
Vpos<< PSx
076 020
077 020
078 020
079 020

V<>:
tVpos<< PSx
076 022
077 022
078 022
079 022

V<>:
tTransient pulse PSx
076 029
077 029
078 029
079 029

V<>:
Hyst. V<> deduc. PSx
076 049
077 049
078 049
079 049

19Z80AZA

Fig. 3-287: Monitoring the positive-sequence voltage.

3-368

P437/EN M/R-11-A // P437311650

P437

3 Operation

V<>:
Blocking tVneg> EXT
[ 041 094 ]

V<>:
tVneg> PSx
[ * ]

V<>:
Hyst. V<> deduc. PSx
[ * ]
V<>:
Vneg> PSx
[ * ]

V<>:
tVneg> elapsed
[ 042 021 ]

V<>:
Vneg
305 251

V<>:
Starting Vneg>
[ 042 019 ]

V<>:
Blocking tVneg>> EXT
[ 041 095 ]
V<>:
tVneg>> PSx
[ * ]
V<>:
Vneg>> PSx
[ * ]

V<>:
tVneg>> elapsed
[ 042 022 ]
V<>:
Starting Vneg>>
[ 042 020 ]
Parameter
set
set
set
set

1
2
3
4

V<>:
Vneg> PSx
076 023
077 023
078 023
079 023

V<>:
tVneg> PSx
076 025
077 025
078 025
079 025

V<>:
Vneg>> PSx
076 024
077 024
078 024
079 024

V<>:
tVneg>> PSx
076 026
077 026
078 026
079 026

V<>:
Hyst. V<> deduc. PSx
076 049
077 049
078 049
079 049

D5Z52BAA

Fig. 3-288: Monitoring the negative-sequence voltage.

P437/EN M/R-11-A // P437311650

3-369

P437

3 Operation

3.34.6

Monitoring the Neutral-Point Displacement Voltage


Depending on the setting, the V<> function monitors either the neutral-point
displacement voltage calculated by the P437 from the three phase-to-ground
voltages or the neutral-point displacement voltage formed externally via the
fourth voltage measuring input, for example the neutral-point displacement
voltage from the open delta winding of the voltage transformers (see
Section 3.12, (p. 3-69)). The neutral-point displacement voltage is monitored to
determine whether it exceeds set thresholds. The triggers are followed by timer
stages that can be blocked via appropriately configured binary signal inputs.

V<>:
Evaluation VNG PSx
[ * ]
VN-G

2
1

VA-G
VB-G
VC-G

V<>:
VNG

305 252

1: Calculated
2: Measured
Parameter

V<>:
Evaluation VNG PSx

set
set
set
set

076
077
078
079

1
2
3
4

002
002
002
002

47Z0148A

Fig. 3-289: Selecting the measured value.

V<>:
Blocking tVNG> EXT
[ 041 072 ]

V<>:
tVNG> PSx
[ * ]

V<>:
Hyst. V<> deduc. PSx
[ * ]

V<>:
VNG> PSx
[ * ]

MAIN:
Protection active
306 001

V<>:
Ready
[ 042 003 ]

V<>:
tVNG> elapsed
[ 041 045 ]

V<>:
Blocking tVNG>> EXT
[ 041 073 ]

V<>:
Starting VNG>
[ 041 044 ]
V<>:
VNG>> PSx
[ * ]

V<>:
tVNG>> PSx
[ * ]

V<>:
tVNG>> elapsed
[ 041 046 ]

V<>:
VNG
305 252

Parameter
set
set
set
set

1
2
3
4

V<>:
VNG> PSx
076 011
077 011
078 011
079 011

V<>:
tVNG> PSx
076 013
077 013
078 013
079 013

V<>:
VNG>> PSx
076 012
077 012
078 012
079 012

V<>:
tVNG>> PSx
076 014
077 014
078 014
079 014

V<>:
Hyst. V<> deduc. PSx
076 049
077 049
078 049
079 049

V<>:
Starting VNG>>
[ 042 008 ]

D5Z52BCA

Fig. 3-290: Monitoring the neutral-point displacement voltage.

3.34.7

Monitoring the Reference Voltage


The reference voltage is monitored to determine whether it exceeds or falls
below set thresholds. The triggers are followed by respective timer stages that
can be blocked via appropriately configured binary signal inputs.

3-370

P437/EN M/R-11-A // P437311650

P437

3 Operation

V<>:
Blocking tVref> EXT
[ 007 036 ]

V<>:
tVref> PSx

V<>:
Hyst. V<> deduc. PSx
[ * ]

[
C

V<>:
Vref> PSx
[

V<>:
tVref> elapsed

Vref

[ 007 047 ]
V<>:
Starting Vref>

V<>:
Blocking tVref>> EXT
[ 007 037 ]

[ 007 051 ]
V<>:
tVref>> PSx
[
C

V<>:
Vref>> PSx
[

V<>:
tVref>> elapsed
[ 007 048 ]
V<>:
Block. tVref>>> EXT
[ 010 248 ]

V<>:
Starting Vref>>
[ 007 052 ]

V<>:
tVref>>> PSx
[

MAIN:
Protection active

306 001

V<>:
Vref>>> PSx
[ * ]

MCMON:
M.circ. Vref faulty
[ 007 213 ]
V<>:
tVref>>> elapsed
[ 010 242 ]
V<>:
Starting Vref>>>
[ 010 241 ]
Parameter

V<>:
Hyst. V<> deduc. PSx

set
set
set
set

076
077
078
079

1
2
3
4

049
049
049
049

Parameter

V<>:
Vref> PSx

V<>:
tVref> PSx

V<>:
Vref>> PSx

V<>:
tVref>> PSx

V<>:
Vref>>> PSx

V<>:
tVref>>> PSx

set
set
set
set

007
007
007
007

007
007
007
007

007
007
007
007

007
007
007
007

007
007
007
007

007
007
007
007

1
2
3
4

064
071
075
079

066
069
073
077

065
068
072
076

067
070
074
078

065
068
072
076

067
070
074
078

19Z8095A

Fig. 3-291: Monitoring the reference voltage, part 1: stages Vref>/>>/>>>.

P437/EN M/R-11-A // P437311650

3-371

P437

3 Operation

V<>:
Blocking tVref< EXT
[ 007 039 ]
V<>:
tVref< PSx

V<>:
Hyst. V<> deduc. PSx
[ * ]

[
C

V<>:
Vref< PSx
[ * ]

]
V<>:
tVref< elapsed
[ 007 053 ]

V<>:
Fault Vref<
[ 007 061 ]

Vref

V<>:
Blocking tVref<< EXT
[ 007 046 ]

Setting(s) blocked
V<>:
Starting Vref<
[ 007 055 ]

V<>:
tVref<< PSx
[
C

V<>:
Vref<< PSx
[

V<>:
tVref<< elapsed
[ 007 054 ]

V<>:
Fault Vref<<
[ 007 062 ]

Setting(s) blocked
V<>:
Block. tVref<<< EXT
[ 010 249 ]

V<>:
Starting Vref<<
[ 007 056 ]
V<>:
tVref<<< PSx
[

MAIN:
Protection active

306 001

V<>:
Vref<<< PSx
[

V<>:
tVref<< elapsed
[ 007 054 ]

MCMON:
M.circ. Vref faulty
[ 007 213 ]
V<>:
Fault Vref<<<
[ 011 135 ]

Setting(s) blocked
V<>:
Starting Vref<<<
[ 010 243 ]
V<>:
tTransient pulse PSx
[ * ]

V<>:
tVref< elaps. trans.
[ 007 057 ]
V<>:
tVref<< elaps.trans.
[ 007 060 ]
V<>:
tVref<<< elaps.trans
[ 010 245 ]

Parameter

V<>:
tTransient pulse PSx

V<>:
Hyst. V<> deduc. PSx

set 1
set 2
set 3
set 4

076
077
078
079

076
077
078
079

029
029
029
029

V<>:
tVref</<</<<< el.tr.
[ 007 063 ]

049
049
049
049

Parameter

V<>:
Vref< PSx

V<>:
tVref< PSx

V<>:
Vref<< PSx

V<>:
tVref<< PSx

V<>:
Vref<<< PSx

V<>:
tVref<<< PSx

set
set
set
set

007
007
007
007

007
007
007
007

007
007
007
007

007
007
007
007

011
011
011
011

011
011
011
011

1
2
3
4

086
097
101
105

088
099
103
107

087
098
102
106

096
100
104
108

059
062
069
070

071
072
073
074

19Z8096A

Fig. 3-292: Monitoring the reference voltage, part 2: stages Vref</<</<<<.

3-372

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.35

Over-/Underfrequency Protection (Function Group f<>)


The P437 monitors the voltage to determine whether it exceeds or falls below set
frequencies. The frequency is determined from the difference in time between
the zero crossings of the voltage (voltage zeroes). The over-/underfrequency
protection function has four stages. The operation of over-/underfrequency
protection will be explained below using the first stage as an example.

3.35.1

Disabling or Enabling Over/Underfrequency Protection


The frequency protection can be disabled or enabled using setting parameters.
Moreover, enabling can be carried out separately for each parameter subset.

f<>:
General enable USER
[ 023 031 ]

0
1
0: No

f<>:
Enabled
[ 042 100 ]

1: Yes

f<>:
Enable PSx
[ * ]

f<>:
Ready
[ 042 101 ]

1
0: No
1: Yes

Parameter

f<>:
Enable PSx

set
set
set
set

018
018
018
018

1
2
3
4

f<>:
Not ready
[ 042 140 ]

196
197
198
199

F5Z0104C

Fig. 3-293: Enabling, disabling and readiness of f<> protection.

P437/EN M/R-11-A // P437311650

3-373

P437
3.35.2

3 Operation

Selecting the Measuring Voltage


By selecting a measuring voltage setting, the user defines the voltage that is
used by the over-/underfrequency protection function for measurement
purposes. This can be either a phase-to-ground voltage or a phase-to-phase
voltage.

f<>:
Selection meas. volt
[ 018 202 ]

MAIN:
Protection active
306 001

f<>:
Ready
[ 042 101 ]
fnom
VA-G

VA-G 3

VB-G

VB-G 3

VC-G

VC-G 3

fnom
2

fnom
3

fnom
4

fnom
5

fnom
6

f<>:
VMeas
305 725

1: Voltage A-G
2: Voltage B-G
3: Voltage C-G
4: Voltage A-B
5: Voltage B-C
6: Voltage C-A

47Z0150A

Fig. 3-294: Selecting the measuring voltage.

3-374

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.35.3

Undervoltage Blocking and Evaluation Time


Over-/underfrequency protection requires a measuring voltage of sufficient
magnitude. Over-/underfrequency protection will be blocked instantaneously if
the measuring voltage falls below the set threshold of the undervoltage stage.
In order to avoid frequency stage starting caused by brief frequency fluctuations
or interference, the evaluation time can be set by the user. The operate
conditions must be satisfied for at least the duration of the set evaluation time in
order for a signal to be issued.

f<>:
Undervolt. block. V<
[ 018 200 ]

f<>:
Blocked by V<
[ 042 102 ]

f<>:
VMeas
305 725

f<>:
Evaluation time
[ 018 201 ]

f<>:
No. periods reached
305 701

f<>:
fMeas
305 726

47Z0151A

Fig. 3-295: Undervoltage blocking and evaluation time setting.

3.35.4

Operating Modes of Over-/Underfrequency Protection


For each stage of the over-/underfrequency protection function, the user can
choose between the following operating modes:

3.35.5

Frequency monitoring

Frequency monitoring combined with differential frequency gradient


monitoring (df/dt)

Frequency monitoring combined with mean frequency gradient monitoring


(f/t)

Frequency Monitoring
Depending on the setting, the P437 monitors the frequency to determine
whether it exceeds or falls below set thresholds. If an operate threshold in excess
of the set nominal frequency is set, the P437 checks to determine whether the
frequency exceeds the operate threshold. If an operate threshold below the set
nominal frequency is set, the P437 checks to determine whether the frequency
falls below the operate threshold. If it exceeds or falls below the set threshold, a
set timer stage is started. The timer stage can be blocked by way of an
appropriately configured binary signal input.

P437/EN M/R-11-A // P437311650

3-375

P437
3.35.6

3 Operation

Frequency Monitoring Combined with Differential Frequency


Gradient Monitoring (df/dt)
In this operating mode of the over-/ underfrequency protection function, the
frequency is also checked to determine whether the set frequency gradient is
reached (in addition to being monitored for exceeding or falling below the set
threshold). Monitoring for overfrequency is combined with monitoring for a
frequency increase; monitoring for underfrequency is combined with monitoring
for a frequency decrease. If both operate conditions are satisfied, a set timer
stage is started. The timer stage can be blocked by way of an appropriately
configured binary signal input.

3.35.7

Frequency Monitoring Combined with Mean Frequency Gradient


Monitoring (f/t)
The frequency gradient can differ for system disturbances in individual
substations and may vary over time due to power swings. Therefore it makes
sense to take the mean value of the frequency gradient into account for loadshedding systems.
In this operating mode of over-/underfrequency protection, frequency monitoring
must be set for underfrequency monitoring.
Monitoring the mean value of the frequency gradient is started with the starting
of frequency monitoring. If the frequency decreases by the set value f within
the set time t, then the t/f monitoring function operates instantaneously and
generates a trip signal. If a frequency change does not lead to an operate
decision of the monitoring function, then the t/f monitoring function will be
blocked until the underfrequency monitoring function drops out. The trip signal
can be blocked by way of an appropriately configured binary signal input.

3-376

P437/EN M/R-11-A // P437311650

P437

3 Operation

f<

t
Start t

Start t

Function blocked

Trip f/t

F5Z0128C

Fig. 3-296: Operation of frequency monitoring combined with f/t monitoring.

P437/EN M/R-11-A // P437311650

3-377

P437

3 Operation

f<>:
Blocking f1 EXT
[ 042 103 ]
f<>:
Oper. mode f1 PSx
[ * ]

1
2
3
1: f
2: f with df/dt

f<>:
f1 PSx
[ * ]

3: f w. Delta f/Delta t

MAIN:
Nominal frequ. fnom
[ 010 030 ]
f<>:
tf1 PSx
[ * ]

f<>:
Ready
[ 042 101 ]
MAIN:
Protection active
306 001

f<>:
Trip signal f1
[ 042 111 ]

f<>:
Blocked by V<
[ 042 102 ]
MAIN:
M.c.b. trip V EXT
[ 004 061 ]

f<>:
Starting f1
[ 042 107 ]
f<>:
df1/dt PSx
[
*
]

f<>:
No. periods reached
305 701

f<>:
fMeas

df/dt

305 726

f<>:
Starting f1/df1
[ 042 108 ]

Start. cond. met

SFMON:
Setting error f<>
[ 098 028 ]

f>
f<>:
Delta f1 PSx
[ * ]
f<>:
Delta t1 PSx
[ * ]

df/dt

f<>:
Delta f1 triggered
[ 042 109 ]
Start. cond. met
f<>:
Delta t1 elapsed
[ 042 110 ]

Parameter

f<>:
Oper. mode f1 PSx

f<>:
f1 PSx

f<>:
df1/dt PSx

f<>:
Delta f1 PSx

f<>:
Delta t1 PSx

f<>:
tf1 PSx

set
set
set
set

018
018
018
018

018
018
018
018

018
018
018
018

018
018
018
018

018
018
018
018

018
018
018
018

1
2
3
4

120
121
122
123

100
101
102
103

108
109
110
111

112
113
114
115

116
117
118
119

104
105
106
107

47Z0152A

Fig. 3-297: First stage of the over-/ underfrequency protection function.

3-378

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.35.8

fmin-/fmax Measurement
For the acquisition of the minimum frequency during an underfrequency
condition and for the acquisition of the maximum frequency during an
overfrequency condition, the two following measured event values are available:

f<>: Max . fre qu. for f>

f<>: Min. frequ. f or f <

Both measured event values are reset automatically at the onset of a new
overfrequency or underfrequency situation. A manual reset is also possible:

f<>: Reset meas .val. USER

P437/EN M/R-11-A // P437311650

3-379

P437

3.36

3 Operation

Directional Power Protection (Function Group P<>)


The power directional protection function determines the active and reactive
power from the fundamental currents and voltages. The sign of the active or the
reactive power, respectively, is evaluated for direction determination

3.36.1

Disabling and Enabling P<> Protection


The power directional protection can be disabled or enabled via setting
parameters. Moreover, enabling can be carried out separately for each
parameter subset.

P<>:
General enable USER
[ 014 220 ]

0
1
0: No
1: Yes

P<>:
Enabled PSx
[ * ]
P<>:
Enabled
[ 036 250 ]

0
1
0: No
1: Yes

Parameter

P<>:
Enabled PSx

set
set
set
set

014
014
014
014

1
2
3
4

252
253
254
255

45Z5051A

Fig. 3-298: Enabling or disabling power directional protection.

3.36.2

Power Determination
The P437 determines the active and reactive power from the three phase
currents and the phase-to-ground voltages. If the measuring-circuit monitoring
function detects malfunctioning in the voltage measuring circuit, power
determination will be blocked.

3-380

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.36.3

Power Monitoring
The P437 checks the determined power values to detect whether they exceed or
fall below set thresholds. The triggers are followed by timer stages that can be
blocked via appropriately configured binary signal inputs.
If the decisions of power monitoring are to be included in the trip commands
when values have fallen below set thresholds, then it is recommended that
transient signals be used. Otherwise the trip command would always be present
when the system voltage was disconnected, and it would therefore not be
possible to close the circuit breaker again.

P<>:
Enabled
[ 036 250 ]
MCMON:
Meas. circ. V faulty
[ 038 023 ]
fnom
P<>:
P

IA

402 631

fnom
IB

fnom
IC

fnom
VA-G

fnom
VB-G

fnom
VC-G

P<>:
P+
402 633

P<>:
P402 634

P<>:
Q
402 632

P<>:
Q+
402 635

P<>:
Q402 636

45Z5052A

Fig. 3-299: Power determination.

P437/EN M/R-11-A // P437311650

3-381

P437

3 Operation

3.36.4

Active Power Monitoring when Set Thresholds are Exceeded


The P437 monitors the active power with two-stage functions to detect when it
exceeds the set thresholds. The resetting ratio of the threshold stages can be
set.
When the active power exceeds the set thresholds, a starting results. The
starting signal is followed by the set operate and resetting delays.

P<>:
Operate delay P> PSx
[

]
P<>:
Release delay P> PSx
[ * ]

P<>:
Blocking tP> EXT
[ 035 082 ]

P<>:
Signal P> delayed
[ 035 087 ]

P<>:
P> PSx
[ * ]
P<>:
Diseng. ratio P> PSx
[ * ]

P<>:
P

P<>:
Starting P>
[ 035 086 ]

402 631

P<>:
Operate delay P>>PSx
[ * ]
P<>:
Release delay P>>PSx
[ * ]

P<>:
Blocking tP>> EXT
[ 035 083 ]

P<>:
Signal P>> delayed
[ 035 090 ]

P<>:
P>> PSx
[ * ]
P<>:
Diseng. ratio P>>PSx
[ * ]

P<>:
Starting P>>
[ 035 089 ]

Parameter

P<>:
P> PSx

P<>:
Diseng. ratio P> PSx

P<>:
Operate delay P> PSx

P<>:
Release delay P> PSx

set
set
set
set

017
017
017
017

017
017
017
017

017
017
017
017

017
017
017
017

1
2
3
4

120
200
201
202

124
125
126
127

128
129
130
131

132
133
134
135

Parameter

P<>:
P>> PSx

P<>:
Diseng. ratio P>>PSx

P<>:
Operate delay P>>PSx

P<>:
Release delay P>>PSx

set
set
set
set

017
017
017
017

017
017
017
017

017
017
017
017

017
017
017
017

1
2
3
4

140
141
142
143

144
145
146
147

148
149
150
151

152
153
154
155

19Z5271A

Fig. 3-300: Active power monitoring when the set thresholds are exceeded.

3-382

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.36.5

Active Power Direction when Set Thresholds are Exceeded


The P437 determines the sign of the active power. If the sign is positive, a
forward-directional decision is issued; if it is negative, a backward- (reverse-)
directional decision results. A setting determines whether a trip signal is
triggered by a forward-directional, a backward- (reverse-) directional or a nondirectional decision.

P<>:
Direction P> PSx
[

1
2
3
1: Forward directional
2: Backward directional
3: Non-directional

P<>:
Trip signal P>
[ 035 088 ]

P<>:
Signal P> delayed
[ 035 087 ]
P<>:
P+
402 633

P<>:
P402 634

P<>:
Direction P>> PSx
[ * ]

1
2
3
1: Forward directional
2: Backward directional
3: Non-directional

P<>:
Trip signal P>>
[ 035 091 ]

P<>:
Signal P>> delayed
[ 035 090 ]

Parameter

P<>:
Direction P> PSx

P<>:
Direction P>> PSx

set
set
set
set

017
017
017
017

017
017
017
017

1
2
3
4

136
137
138
139

156
157
158
159

45Z5054A

Fig. 3-301: Direction-dependent trip signal of the active power protection function when the set thresholds are
exceeded.

P437/EN M/R-11-A // P437311650

3-383

P437

3 Operation

3.36.6

Reactive Power Monitoring when Set Thresholds are Exceeded


The P437 monitors the reactive power with two-stage functions to detect when it
exceeds the set thresholds. The resetting ratio of the threshold stages can be
set.
When the reactive power exceeds the set thresholds, a starting results. The
starting signal is followed by the set operate and resetting delays.

P<>:
Operate delay Q> PSx
[ * ]
P<>:
Release delay Q> PSx
[ * ]

P<>:
Blocking tQ> EXT
[ 035 084 ]

P<>:
Signal Q> delayed
[ 035 093 ]

P<>:
Q> PSx
[ * ]
P<>:
Diseng. ratio Q> PSx
[

P<>:
Starting Q>
[ 035 092 ]

P<>:
Q
402 632

P<>:
Operate delay Q>>PSx
[ * ]
P<>:
Release delay Q>>PSx
[ * ]

P<>:
Blocking tQ>> EXT
[ 035 085 ]

P<>:
Signal Q>> delayed
[ 035 096 ]

P<>:
Q>> PSx
[ * ]
P<>:
Diseng. ratio Q>>PSx
[ * ]

P<>:
Starting Q>>
[ 035 095 ]

Parameter

P<>:
Q> PSx

P<>:
Diseng. ratio Q> PSx

P<>:
Operate delay Q> PSx

P<>:
Release delay Q> PSx

set
set
set
set

017
017
017
017

017
017
017
017

017
017
017
017

017
017
017
017

1
2
3
4

160
161
162
163

164
165
166
167

168
169
170
171

172
173
174
175

Parameter

P<>:
Q>> PSx

P<>:
Diseng. ratio Q>>PSx

P<>:
Operate delay Q>>PSx

P<>:
Release delay Q>>PSx

set
set
set
set

017
017
017
017

017
017
017
017

017
017
017
017

017
017
017
017

1
2
3
4

180
181
182
183

184
185
186
187

188
189
190
191

192
193
194
195

19Z5270A

Fig. 3-302: Reactive power monitoring when the set thresholds are exceeded.

3-384

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.36.7

Reactive Power Direction when Set Thresholds are Exceeded


The P437 determines the sign of the reactive power. If the sign is positive, a
forward-directional decision is issued; if it is negative, a backward- (reverse-)
directional decision results. A setting determines whether a trip signal is
triggered by a forward-directional, a backward- (reverse-) directional or a nondirectional decision.

P<>:
Direction Q> PSx
[ * ]

1
2
3
1: Forward directional
2: Backward directional
3: Non-directional

P<>:
Trip signal Q>
[ 035 094 ]

P<>:
Signal Q> delayed
[ 035 093 ]
P<>:
Q+
P<>:
Q-

402 635

402 636

P<>:
Direction Q>> PSx
[ * ]

1
2
3
1: Forward directional
2: Backward directional
3: Non-directional

P<>:
Trip signal Q>>
[ 035 097 ]

P<>:
Signal Q>> delayed
[ 035 096 ]

Parameter

P<>:
Direction Q> PSx

P<>:
Direction Q>> PSx

set
set
set
set

017
017
017
017

017
017
017
017

1
2
3
4

176
177
178
179

196
197
198
199

45Z5056A

Fig. 3-303: The direction-dependent trip signal of the reactive power protection function when the set thresholds
are exceeded.

P437/EN M/R-11-A // P437311650

3-385

P437
3.36.8

3 Operation

Active Power Monitoring when Values Fall Below Set Thresholds


The P437 monitors the active power with two-stage functions to detect when it
falls below the set thresholds. The resetting ratio of the threshold stages can be
set. When the active power falls below the set thresholds, a starting results. The
starting signal is followed by the set operate and resetting delays.

3-386

P437/EN M/R-11-A // P437311650

P437

3 Operation

P<>:
Blocking tP< EXT
[ 035 050 ]
P<>:
P< PSx
[ * ]

P<>:
Operate delay P< PSx
[ * ]

P<>:
Diseng. ratio P< PSx
[

P<>:
P

P<>:
Release delay P< PSx
C

P<>:
Signal P< delayed
[ 035 055 ]

402 631

Setting(s) blocked
P<>:
Starting P<
[ 035 054 ]

&
P<>:
Blocking tP<< EXT
[ 035 051 ]

P<>:
Fault P<
[ 035 057 ]

&

P<>:
P<< PSx
[ * ]

P<>:
Operate delay P<<PSx
[ * ]
P<>:
Release delay P<<PSx

P<>:
Diseng.ratio P<< PSx
[

P<>:
Signal P<< delayed
[ 035 061 ]
Setting(s) blocked
P<>:
Starting P<<
[ 035 060 ]

&

P<>:
Fault P<<
[ 035 063 ]

&

P<>:
tTransient pulse PSx
[ * ]

P<>:
tTransient pulse PSx
[ * ]

P<>:
tP< elapsed trans.
[ 035 056 ]
P<>:
tP<< elapsed trans.
[ 035 062 ]
P<>:
tP</tP<< elaps.trans
[ 035 178 ]

Parameter

P<>:
P< PSx

P<>:
Diseng. ratio P< PSx

set 1

017 030

017 034

017 060

set 2
set 3

017 031
017 032
017 033

017 035
017 036
017 037

017 061

Parameter

P<>:
P<< PSx

P<>:
Diseng.ratio P<< PSx

P<>:
Operate delay P<<PSx

P<>:
Release delay P<<PSx

P<>:
tTransient pulse PSx

set 1
set 2

017 234

017 238

017 242

017 246

017 235
017 236
017 237

017 239
017 240
017 241

017 243
017 244
017 245

017 247
017 248
017 249

018 246
018 247

set 4

set 3
set 4

P<>:
Operate delay P< PSx

017 062
017 063

P<>:
Release delay P< PSx
017 226
017 227
017 228
017 229

018 248
018 249

19Z5272B

Fig. 3-304: Active power monitoring when values fall below set thresholds.

P437/EN M/R-11-A // P437311650

3-387

P437
3.36.9

3 Operation

Active Power Direction when Values Fall Below Set Thresholds


The P437 determines the sign of the active power. If the sign is positive, a
forward-directional decision is issued; if it is negative, a backward- (reverse-)
directional decision results. A setting determines whether a trip signal is
triggered by a forward-directional, a backward- (reverse-) directional or a nondirectional decision.

3-388

P437/EN M/R-11-A // P437311650

P437

3 Operation

P<>:
Starting P<
[ 035 054 ]
Apparent power S

> 0,010 Snom

P<>:
Direction P< PSx
[ * ]

1
2
3
1: Forward directional
2: Backward directional
3: Non-directional

P<>:
Signal P< delayed
[ 035 055 ]

&

&

P<>:
Trip signal P<
[ 035 058 ]

&

P<>:
Trip signal P< trans
[ 035 059 ]

&

&

P<>:
tP< elapsed trans.
[ 035 056 ]
P<>:
P+

P<>:
P-

&

402 633

&

&

402 634

P<>:
Starting P<<
[ 035 060 ]

P<>:
Direction P<< PSx
[ * ]

1
2
3

1: Forward directional
2: Backward directional
3: Non-directional

&

P<>:
Signal P<< delayed
[ 035 061 ]

&

P<>:
Trip signal P<<
[ 035 064 ]

&

&
&

P<>:
tP<< elapsed trans.
[ 035 062 ]

&

P<>:
Trip sig. P<< trans.
[ 035 065 ]

&

Parameter

P<>:
Direction P< PSx

P<>:
Direction P<< PSx

set 1

017 230

017 250

set 2
set 3

017 231
017 232
017 233

017 251
017 252
017 253

set 4

&

19Z5273B

Fig. 3-305: The direction-dependent trip signal of the active power protection function when values fall below set
thresholds.

P437/EN M/R-11-A // P437311650

3-389

P437

3 Operation

1
P<>:
Starting P<
035 054

P<>:
Operate delay P< PSx
*
P<>:
Release delay P< PSx

*
P<>:
Signal P< delayed
035 055
P<>:
tP< elapsed trans.
035 056

P<>:
Fault P<
035 057

Parameter

P<>:
Operate delay P< PSx

P<>:
Release delay P< PSx

P<>:
tTransient pulse PSx

set 1

017 060

017 226

018 246

set 2
set 3

017 061
017 062
017 063

017 227
017 228
017 229

018 247
018 248
018 249

set 4

19Z5278A

Fig. 3-306: Performance of the transient signal and the fault signal issued by the active power monitoring.

3-390

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.36.10

Reactive Power Monitoring when Values Fall Below Set


Thresholds
The P437 monitors the reactive power with two-stage functions to detect when it
falls below the set thresholds. The resetting ratio of the threshold stages can be
set.
When the reactive power falls below the set thresholds, a starting results. The
starting signal is followed by the set operate and resetting delays.

P<>:
Blocking tQ< EXT
[ 035 052 ]
P<>:
Q< PSx
[ * ]

P<>:
Operate delay Q< PSx
[ * ]

P<>:
Diseng. ratio Q< PSx
[

P<>:
Q

P<>:
Release delay Q< PSx
C

P<>:
Signal Q< delayed
[ 035 067 ]

402 632

Setting(s) blocked
P<>:
Starting Q<
[ 035 066 ]

&
P<>:
Blocking tQ<< EXT
[ 035 053 ]

P<>:
Fault Q<
[ 035 069 ]

&

P<>:
Q<< PSx
[ * ]
P<>:
Diseng.ratio Q<< PSx
[ * ]

P<>:
Operate delay Q<<PSx
[ * ]
P<>:
Release delay Q<<PSx
C

P<>:
Signal Q<< delayed
[ 035 011 ]
Setting(s) blocked
P<>:
Starting Q<<
[ 035 010 ]

&

P<>:
Fault Q<<
[ 035 049 ]

&

P<>:
tTransient pulse PSx
[

P<>:
tTransient pulse PSx
[ * ]

P<>:
tQ< elapsed trans.
[ 035 068 ]
P<>:
tQ<< elapsed trans.
[ 035 016 ]

Parameter

P<>:
Q< PSx

P<>:
Diseng. ratio Q< PSx

P<>:
Operate delay Q< PSx

P<>:
tQ</tQ<< elaps.trans
[ 035 179 ]

P<>:
Release delay Q< PSx

set 1

018 035

018 044

018 052

018 056

set 2
set 3

018 036
018 037

018 045
018 046

018 053
018 054

018 057
018 058

set 4

018 038

018 047

018 055

018 059

Parameter

P<>:
Q<< PSx

P<>:
Diseng.ratio Q<< PSx

P<>:
Operate delay Q<<PSx

P<>:
Release delay Q<<PSx

P<>:
tTransient pulse PSx

set 1
set 2

018 085
018 086

018 095
018 096

018 213
018 214

018 236
018 237

018 246
018 247

set 3
set 4

018 087
018 088

018 097
018 098

018 215
018 216

018 238
018 239

018 248
018 249

19Z5276B

Fig. 3-307: Reactive power monitoring when values fall below set thresholds.

P437/EN M/R-11-A // P437311650

3-391

P437
3.36.11

3 Operation

Reactive Power Direction when Values Fall Below Set Thresholds


The P437 determines the sign of the reactive power. If the sign is positive, a
forward-directional decision is issued; if it is negative, a backward- (reverse-)
directional decision results. A setting determines whether a trip signal is
triggered by a forward-directional, a backward- (reverse-) directional or a nondirectional decision.

3-392

P437/EN M/R-11-A // P437311650

P437

3 Operation

P<>:
Starting Q<
[ 035 066 ]

Apparent power S

> 0,010 Snom

P<>:
Direction Q< PSx
[ * ]

1
2
3
1: Forward directional
2: Backward directional
3: Non-directional

P<>:
Signal Q< delayed
[ 035 067 ]

&

&

P<>:
Trip signal Q<
[ 035 155 ]

&

&

P<>:
tQ< elapsed trans.
[ 035 068 ]

&

&

P<>:
Trip sig. Q< trans.
[ 035 156 ]

P<>:
Q+

&

402 635

P<>:
Q-

&

402 636

P<>:
Starting Q<<
[ 035 010 ]

P<>:
Direction Q<< PSx
[ * ]

1
2
3
1: Forward directional
2: Backward directional
3: Non-directional

&

P<>:
Signal Q<< delayed
[ 035 011 ]

&

P<>:
Trip signal Q<<
[ 035 176 ]

&

P<>:
Trip sig. Q<< trans.
[ 035 177 ]

&

&
&

P<>:
tQ<< elapsed trans.
[ 035 016 ]

&

Parameter

P<>:
Direction Q< PSx

P<>:
Direction Q<< PSx

set 1

018 081

018 242

set 2
set 3

018 082
018 083
018 084

018 243
018 244
018 245

set 4

&

19Z5277B

Fig. 3-308: Direction-dependent trip signal of the reactive power protection function when values fall below set
thresholds.

P437/EN M/R-11-A // P437311650

3-393

P437

3 Operation

1
P<>:
Starting Q<
035 066

P<>:
Operate delay Q< PSx
*
P<>:
Release delay Q< PSx

*
P<>:
Signal Q< delayed
035 067
P<>:
tQ< elapsed trans.

035 068
P<>:
Fault Q<
035 069

P<>:
Operate delay Q< PSx

P<>:
Release delay Q< PSx

P<>:
tTransient pulse PSx

set 1

018 052

018 056

018 246

set 2
set 3

018 053
018 054
018 055

018 057
018 058
018 059

018 247
018 248
018 249

Parameter

set 4

19Z5279A

Fig. 3-309: Performance of the transient signal and the fault signal issued by the reactive power monitoring.

3-394

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.36.12
Apparent power S

Starting Signal with Direction


> 0,010 Snom

P<>:
Starting P>
[ 035 086 ]

&

P<>:
Direction P forw.
[ 035 181 ]

&

P<>:
Direction P backw.
[ 035 191 ]

P<>:
Starting P>>
[ 035 089 ]
P<>:
Starting P<
[ 035 054 ]
P<>:
Starting P<<
[ 035 060 ]
P<>:
P+

402 633

P<>:
P-

402 634

19Z5274B

Fig. 3-310: Directional starting signal issued by the active power monitoring.

P<>:
Q+
402 635

P<>:
Q402 636

P<>:
Starting Q>
[ 035 092 ]

&

P<>:
Direction Q forw.
[ 035 193 ]

&

P<>:
Direction Q backw.
[ 035 194 ]

P<>:
Starting Q>>
[ 035 095 ]
P<>:
Starting Q<
[ 035 066 ]
P<>:
Starting Q<<
[ 035 010 ]

Apparent power S

> 0,010 Snom

19Z5275B

Fig. 3-311: Directional starting signal issued by the reactive power monitoring.

P437/EN M/R-11-A // P437311650

3-395

P437

3 Operation

3.37

Circuit Breaker Failure Protection (Function Group CBF)


The P437 features the CB failure protection function. After a trip command has
been issued the CBF function checks that the circuit breaker has actually been
opened.

3.37.1

Disabling and Enabling Circuit Breaker Failure Protection


The function is enabled at CBF: Ge ne ral e nabl e USER. If this parameter has
been activated the CBF function may be enabled or disabled using setting
parameters or through appropriately configured binary signal inputs. Parameters
and configured binary signal inputs have equal status. If C BF: Enable USER is
the only function assigned to a binary signal input, then circuit breaker
protection will be enabled by a positive edge of the input signal and disabled by
a negative edge. If C BF: Dis able EXT is the only function assigned to a binary
signal input, then a signal at this input will have no effect.
CBF:
General enable USER
[ 022 080 ]
0
1

&

CBF:
Enabled
[ 040 055 ]

0: No
1: Yes

INP:
Fct. assignm. U xxx
[ xxx xxx ]
U x1
U x2
U x3
U xx
Address 038 041

&

Address 038 042

&
&
CBF:
Enable EXT
[ 038 041 ]

&
&

1
1

S1

CBF:
Ext./user enabled
[ 038 040 ]

CBF:
Enable USER
[ 003 016 ]
0
1
0: don't execute
1: execute

CBF:
Disable EXT
[ 038 042 ]

&

CBF:
Disable USER
[ 003 015 ]
0
1
0: don't execute
1: execute

47Z1138B

Fig. 3-312: Disabling or enabling circuit breaker failure protection.

3-396

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.37.2

Readiness of Circuit Breaker Protection


Circuit breaker failure protection will be unavailable under the following
conditions:

The CBF function is not activated.

Circuit breaker protection is being blocked by an appropriately configured


binary signal input.

All CBF timer stages have been set to blocked.

CBF:
Enabled
[ 040 055 ]

CBF:
Not ready
[ 040 025 ]

&

CBF:
Blocking EXT
[ 038 058 ]
CBF:
t1 1p
[ 022 164 ]
blocked
CBF:
t1 3p
[ 022 165 ]
blocked
CBF:
t2
[ 022 166 ]
blocked

&

CBF:
Delay/starting trig.
[ 022 155 ]
blocked
CBF:
Delay/fault beh. CB
[ 022 171 ]
blocked
CBF:
Delay/CB sync.superv
[ 022 172 ]
blocked

45Z6364A

Fig. 3-313: Signal C B F : N o t r e a d y.

3.37.3

Detecting a CB Tripping
A break in current flow is the preferred criterion to detect a successful CB
tripping.
Protection functions that have tripping criteria not directly dependent on current
flow may additionally be provided with status signals from CB auxiliary contacts
for evaluation.

P437/EN M/R-11-A // P437311650

3-397

P437
3.37.4

3 Operation

Current Flow Monitoring


This function is used to detect a break in current flow safely, immediately and
pole-selectively. The CBF function continuously compares sampled current values
with the set threshold value C BF: I<.
As long as current flow criteria are met the monitoring function will continuously
issue the phase selective signals CBF : C urr en t f low A, CBF: Curre nt flow B,
CBF : C ur rent fl ow C and the multiple signal CBF: Current flow Phx.
Moreover, there is a residual current monitoring function which can be enabled/
disabled. For this either the residual current value measured directly at the CT or
the value derived from the three phase currents may be used.
As long as a residual current exceeding the comparator threshold is flowing, the
current flow criterion is not met and the corresponding signal (C BF: Curre nt
flow N) is issued. When the residual current monitoring function is disabled, no
monitoring is carried out and the CBF : C urr en t f low N = No signal is issued
continuously.

CBF:
I<
[ 022 160 ]

IA

CBF:
Current flow A
[ 038 230 ]

IB

CBF:
Current flow B
[ 038 231 ]

IC

CBF:
Current flow C
[ 038 232 ]

CBF:
Current flow Phx
[ 038 233 ]

CBF:
Evaluation IN
[ 022 184 ]
0
1
2
0: Without
1: Calculated
2: Measured

c1
c2
+
+
+

IN

1
2

1 ... 2

CBF:
IN<
[ 022 180 ]

1
CBF:
Current flow N
[ 038 235 ]
CBF:
IN
460 394

64Z1103C

Fig. 3-314: Current flow monitoring.

3-398

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.37.5

Evaluation of CB Status Signals


Trip signals included in MAI N: Gen . tri p command 1, which use CB status
signals in addition to current flow monitoring, can be selected with the parameter
CBF: Fct.assignm. CBAux..
Applying CB status signals depends on the type of auxiliary contacts available.
The P437 can check the following CB status signals for plausibility and evaluate
them:

The open signal from the circuit breaker, MAIN: CB open 3p EXT

The closed signal from the circuit breaker, MA IN: CB clos e d 3 p EXT

The evaluation of the CB status signals is blocked, if the configuration of the


respective binary signal inputs or the signal levels are not plausible. As a result,
the P437 will issue the CBF: CB pos. im pl ausi ble signal. The evaluation of
current criteria is not affected by this blocking.
If only one of the two possible CB status signals has been configured, then this
configured signal will always be considered plausible by the P437.

INP:
Fct. assignm. U xxx
[ xxx yyy ]

U x01
U x02
U x03
U xxx
Address

031 028

Address

036 051

MAIN:
CB open 3p EXT
[ 031 028 ]
MAIN:
CB closed 3p EXT
[ 036 051 ]

&

&
&

CBF:
CB pos. implausible
[ 038 210 ]

&

19Z6131C

Fig. 3-315: Plausibility check of CB status signals.

P437/EN M/R-11-A // P437311650

3-399

P437
3.37.6

3 Operation

Startup Criteria
Startup of the circuit breaker failure protection function will occur when the CB is
recognized as closed during a startup criterion. The following criteria are
evaluated as a startup criterion:
Internal startup criterion

Generating the Gen. Trip signal 1 is considered a start criterion. In addition


it may be selected, by setting the parameter CBF: Start with m an. t rip,
that a manual trip signal will be used as a start criterion.
Current flow monitoring is the primary evaluation criterion. The CB auxiliary
contacts are evaluated when no current flow is registered and the
respective trip signal, included in the Gen. Trip command 1, has been
selected from the protection function in parameter C BF: Fct.assig nm.
C BAu x. for the evaluation of the CB auxiliary contacts.

External startup criterion

Triggering by a protection device operating in parallel (CBF: Start 3p


E XT) may be used as a start criterion.
To be on the safe side an additional two pole trigger may be implemented
by applying the CBF: Star t e nabl e E XT signal.
Current flow monitoring is the primary evaluation criterion. The CB auxiliary
contacts are evaluated when no current flow is registered.

After a CBF startup, the state of the general trip signal or the external trigger
signal is no longer taken into account. The CBF function will thus reset only if the
current criterion is met (current values to fall below I< with all three phases) or
the CB's state is open.

3.37.7

Timer Stages and Output Logic


Associated timer stages are started when a startup criterion is met.

The signals C BF: Trip s ign al t 1, A, C BF: Tr ip signal t1, B, CBF: T rip
sign al t 1 , C will be issued if the startup criterion is still present when the
time period, set at timer stage CBF: t1 1p, has elapsed. The output
command from this timer stage is intended for a second CB trip coil.

The C BF: t1 3p signal will be issued if the startup criterion is still present
when the time delay set at timer stage CBF: Trip signal t1. The output
command from this timer stage is intended for a second CB trip coil.

The CBF: t 2 signal will be issued if the startup criterion is still present
when the time delay set at timer stage CBF: Trip signal t 2, has elapsed.
The output command from this timer stage is intended for a backup circuit
breaker or protection system.

The trip signals will be issued as long as the current criterion is not met or the
CB's state is signaled as closed. Should a loss of gas pressure occur in the arcing
chambers of installed type SF-6 circuit breakers then all surrounding circuit
breakers must be immediately tripped without waiting for a reaction from the
damaged switch. In case of an external CB fault the elapsing of timer stage t2
may be interrupted by a signal to a binary signal input appropriately configured
at CBF : C B fault y EXT.

3-400

P437/EN M/R-11-A // P437311650

P437

3 Operation

CBF:
Fct.assignm. CBAux.
[ 022 159 ]
Signal 1
m out of n

Signal 2
Signal n

Selected signals
CBF:
CB pos. implausible
[ 038 210 ]

&

CBF:
I<
[ 022 160 ]

&
&

IA

S 1

R 1

MAIN:
CB closed >= 1p
[ 031 038 ]

CBF:
Start with man. trip
[ 022 154 ]

&

&

CBF:
Startup A
[ 038 212 ]

1
0: No
MAIN:
Trip cmd. blocked
[ 021 013 ]

&

1: Yes

&
&

MAIN:
Trip signal 1, A
[ 036 006 ]
MAIN:
Manual trip signal
[ 034 017 ]

INP:
Fct. assignm. U xxx
[ xxx yyy ]

&

U x01
U x02
U x03

&

U xxx
Address

038 209

&

CBF:
Start enable EXT
[ 038 209 ]
CBF:
Start A EXT
[ 038 206 ]
CBF:
Startup 3p
[ 038 211 ]
CBF:
Start A
310 007

>2
CBF:
Start B

CBF:
Start >1p

310 010

310 008

CBF:
Start C
310 009

45Z6363A

Fig. 3-316: 1-pole starting of circuit breaker failure protection.

P437/EN M/R-11-A // P437311650

3-401

P437

3 Operation

CBF:
Trip 1p
[ 022 163 ]
0
1

0: No
1: Yes

CBF:
Not ready
[ 040 025 ]

CBF:
Startup A
[ 038 212 ]
CBF:
Startup B
[ 038 213 ]
CBF:
Startup C
[ 038 214 ]

CBF:
t1 1p

&
&
&

CBF:
Startup 3p
[ 038 211 ]

CBF:
Trip signal t1, B
[ 038 217 ]
CBF:
Trip signal t1, C
[ 038 218 ]
CBF:
Trip signal t1
[ 038 215 ]

CBF:
t1 3p
[ 022 165 ]

CBF:
Trip signal t1, A
[ 038 216 ]

CBF:
CB failure
[ 036 017 ]

CBF:
t2
[ 022 166 ]

CBF:
Trip signal t2
[ 038 219 ]

&
CBF:
CB faulty EXT
[ 038 234 ]

47Z1133A

Fig. 3-317: Timer stages of circuit breaker failure protection.

3.37.8

Trip Commands
While trip signals issued by the CB failure protection have no timer stages
available, the user can set minimum time-delays for trip commands.
By appropriate setting it can be selected that trip commands, issued by the CB
failure protection function, will operate in latching mode. The corresponding trip
command, set to latch mode, will remain active until reset by operating
parameters or through an appropriately configured binary signal input.

3-402

P437/EN M/R-11-A // P437311650

P437

3 Operation

CBF:
Min.dur. trip cmd.t1
[ 022 167 ]
CBF:
Latching trip cmd.t1
[ 022 169 ]

0
1

0: No
CBF:
Trip command t1, A
[ 038 221 ]

1: Yes

MAIN:
Trip cmd. blocked
[ 021 013 ]

&

CBF:
Trip signal t1, A
[ 038 216 ]

&

1 1
CBF:
Trip command t1, B
[ 038 222 ]

R 1

&
CBF:
Trip signal t1, B
[ 038 217 ]

&

1 1

R 1

CBF:
Trip command t1, C
[ 038 223 ]

&
CBF:
Trip signal t1, C
[ 038 218 ]

&

1 1

R 1

CBF:
Trip command t1
[ 038 220 ]

&
CBF:
Trip signal t1
[ 038 215 ]

&

1 1

R 1
CBF:
Min.dur. trip cmd.t2
[ 022 168 ]

CBF:
Latching trip cmd.t2
[ 022 170 ]

0
1
0: No

&

1: Yes

CBF:
Trip signal t2
[ 038 219 ]

0
CBF:
Trip command t2
[ 038 224 ]

>1
&

1 1

R 1
MAIN:
Rset.latch.trip USER
[ 021 005 ]
0
1

0: don't execute

MAIN:
Latch. trip c. reset
[ 040 139 ]

1: execute

MAIN:
Reset latch.trip EXT
[ 040 138 ]

47Z1134B

Fig. 3-318: CBF trip commands.

P437/EN M/R-11-A // P437311650

3-403

P437
3.37.9

3 Operation

Starting Trigger
The signal CBF : St arti ng will be issued when the signal CBF: Starting tr ig.
EX T is presented to an appropriately configured binary signal input and a
general starting condition is present. The signal C BF: Delay/starting tr ig. will
be issued after timer stage CBF : Tri p s ignal. has elapsed.

CBF:
Delay/starting trig.
[ 022 155 ]
MAIN:
General starting
[ 036 000 ]
CBF:
Starting trig. EXT
[ 038 016 ]

&

CBF:
Trip signal
[ 040 026 ]
CBF:
Starting
[ 038 021 ]

45Z8037A

Fig. 3-319: Starting trigger.

3.37.10

Fault Behind CB Protection


A fault behind a CB (downstream) is a fault that may occur between a circuit
breaker already open and a CT, which is fed from the remote end.
Fault behind CB protection recognizes such faults through the current criterion if
the circuit breaker does not indicate that it is closed after the time delay set at
C BF: D el ay/faul t be h. CB has elapsed.
When such a fault is detected behind the CB the CBF : F ault behind CB signal
is issued. In such a case the far end circuit breaker may be triggered by an
InterMiCOM protective interface. This may also prevent unwanted triggering of
the circuit breaker failure function.

CBF:
Delay/fault beh. CB
[ 022 171 ]

CBF:
I<
[ 022 160 ]
IA
IB

&

&

CBF:
Fault behind CB
[ 038 225 ]

IC
MAIN:
CB open 3p EXT
[ 031 028 ]
MAIN:
CB closed 3p EXT
[ 036 051 ]
MAIN:
CB closed A EXT
[ 031 029 ]
MAIN:
CB closed B EXT
[ 031 030 ]
MAIN:
CB closed C EXT
[ 031 031 ]
CBF:
CB pos. implausible
[ 038 210 ]

45Z6365A

Fig. 3-320: Fault behind CB protection.

3-404

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.37.11

CB Synchronization Supervision
CB synchronization supervision recognizes states where not all circuit breaker
contacts are open or closed. This function uses both current flow monitoring and
evaluation of CB state signals to detect CB synchronization. In order to bridge CB
operating times the time-delay CB F: D e lay/CB sy nc.su perv can be used.
When this time-delay has elapsed the signal CBF: TripSig CBs yn c.s uper is
issued. Poles that are recognized as being open will still be signaled.

CBF:
Delay/CB sync.superv
[ 022 172 ]
CBF:
CB pos. implausible
[ 038 210 ]

&

CBF:
TripSig CBsync.super
[ 038 226 ]

MAIN:
CB closed A EXT
[ 031 029 ]
MAIN:
CB closed B EXT
[ 031 030 ]
MAIN:
CB closed C EXT
[ 031 031 ]

&
MAIN:
CB open 3p EXT
[ 031 028 ]
MAIN:
CB closed 3p EXT
[ 036 051 ]

<3

&
&

CBF:
I<
[ 022 160 ]
IA

&

CBF:
CBsync.superv A open
[ 038 227 ]
CBF:
CBsync.superv B open
[ 038 228 ]
CBF:
CBsync.superv C open
[ 038 229 ]

&

IB
IC

45Z6366A

Fig. 3-321: CB synchronization supervision.

P437/EN M/R-11-A // P437311650

3-405

P437

3.38

3 Operation

Circuit Breaker Monitoring (Function Group CBM)


The P437 features a circuit breaker monitoring function. This function supports
state-controlled maintenance of circuit breakers.

3.38.1

Disabling and Enabling Circuit Breaker Monitoring


Circuit breaker monitoring may be disabled or enabled using setting parameters.

CBM:
General enable USER
[ 022 010 ]

0
CBM:
Enabled
[ 044 130 ]

1
0: No
1: Yes

48Z5404A

Fig. 3-322: Enabling or disabling circuit breaker monitoring.

3.38.2

Variants
The wear condition of a circuit breaker may be determined using a variety of
methods:

3-406

Monitoring the mechanical switching operations

Accumulating ruptured current values

Accumulating the squared ruptured current values

Calculating the current-time integral of ruptured and accumulated current


values

Calculating the remaining switching operations with reference to the CB


wear characteristic.

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.38.3

CB Wear Characteristic
Manufacturers of circuit breakers usually provide wear characteristics displaying
the maximum number of permissible CB operations in relation to the ruptured
current.

Number of permissible CB operations

Fig. 3-323, (p. 3-407) displays the wear characteristics for a circuit breaker with
a nominal current of 2000 A and a maximum ruptured current of 63 kA. The
mean ruptured current is 48 kA.
100000

10000

1000

100

10
0.1

10

100

Disconnection current in kA

19Z6123A_EN

Fig. 3-323: Circuit breaker wear characteristic.

The knee points in Fig. 3-323, (p. 3-407) are necessary to set the wear
characteristic for the circuit breaker:

The circuit breaker's nominal current (CBM: I nom, CB) and the permitted
number of CB operations at nominal current (CBM: Perm. CB op.
I nom,C B)

The circuit breaker's mean ruptured current (CBM: Med. cu rr. It rip,CB)
and the permitted number of CB operations at mean ruptured current
(C BM: P erm. CB op. I m ed,C B)

The circuit breaker's maximum ruptured current (CBM: Max. curr.


It rip,CB) and the permitted number of CB operations at maximum
ruptured current (CBM: P e rm. CB op. Imax ,CB)

The mean ruptured current is not available for all types of circuit breakers.
In such a case the parameters for this knee point are to be set to Blocked. A knee
point is not considered in the characteristic when at least one of the parameters
for the knee point is set to Blocked.
For proper performance of circuit breaker monitoring it should be observed that
the knee points must be applied in a logically correct sequence (continuously
descending). When set currents and numbers of CB operations are not plausible
according to the characteristic the P437 will issue an error message and block
circuit breaker monitoring.
P437/EN M/R-11-A // P437311650

3-407

P437
3.38.4

3 Operation

Calculating the CB Wear State


The current wear state of the circuit breaker is given as the number of remaining
CB operations at nominal current conditions. The number of remaining CB
operations nrem(Inom,CB) is calculated and displayed phase selectively after each
disconnection by the P437.
Calculation is per this equation:
nrem(I nom,CB) = nrem,0(I nom,CB) -

n(I nom,CB)
n(I d,CB)

Where:

3.38.5

Inom,CB: Nominal current for the CB

n(Inom,CB): Max permitted number of CB operations at Inom,CB

Id,CB: Ruptured current

n(Id,CB): Permitted number of CB operations at Id,CB according to wear


characteristics

nrem,0(Inom,CB): Remaining permitted number of CB operations at Inom,CB


before disconnection

nrem,(Inom,CB): Remaining permitted number of CB operations at Inom,CB after


disconnection

Operating Modes
Setting the parameter CBM: Operati ng mode will select the condition under
which the function will be triggered:

With trip cmd. only: Function triggered only by the general trip command 1

With CB sig.EXT only: Function triggered by the CB open signal generated


by an auxiliary contact

CB sig. EXT or trip: Function triggered by the general trip command 1 or CB


open signal generated by an auxiliary contact

Measured values and counters are re-determined with each triggering and
compared with set threshold values.
A correction value can be set in order to determine the trip time at CBM: Cor r.
acqu.t ime tr ip to be triggered by the open command. Another correction value
can be set at CB M: C orr. acqui s. time to be triggered by the position signal
issued by the CB auxiliary contacts. This enables to correctly evaluate the
leading or lagging auxiliary contacts or the delay between issuing the trip
command and opening of the CB contacts. In addition differing inherent time
delays from the two command chains can be configured independently of each
other so as to achieve optimum time adjustment.

3.38.6

Cycle for Circuit Breaker Monitoring


The circuit breaker monitoring cycle is defined pole-selectively. During an active
cycle the signals CBM: C ycle ru nni ng A, CBM: Cycle r unning B or
C BM: C y cle runnin g C are issued.
The cycle is started by a trigger criterion. Definition for the end of a cycle: The
remaining time of a power cycle duration has elapsed after the last detected
current zero crossing. The CBM: Curr. f l ow en ded A (CBM: Curr. flow
e nded B, CBM: C urr. fl ow en de d C) signal is then issued.
The maximum cycle time duration is defined with 220 milliseconds. The start of
the cycle time is corrected by the settable correction times. A fault on a CB pole
is considered to be apparent if further current zero crossings are detected after

3-408

P437/EN M/R-11-A // P437311650

P437

3 Operation

the maximum cycle time has elapsed. Measured values from the respective CB
tripping are canceled and the CBM: tmax> A (CBM: tmax> B, CBM: tmax >
C) signal is issued.

P437/EN M/R-11-A // P437311650

3-409

P437
3.38.7

3 Operation

Pole-Selective Counter Values and Measured Values


The P437 separately evaluates each phase current and generates an individual
wear presentation for each CB pole.
The following counter values are presented pole-selectively:

The number of mechanical switching operations made

The number of remaining CB operations at CB nominal current


This value is derived by evaluating wear with reference to the CB's wear
characteristic.

The following measured values are presented pole-selectively, and per-unit


values refer to the CB's nominal current:

Primary ruptured current


This value is applied to evaluate wear with reference to the CB's wear
characteristic.

Per-unit ruptured current

Squared per-unit ruptured current

Sum of the per-unit ruptured currents

Sum of the squared per-unit ruptured currents

Current-time integral of the per-unit ruptured current

Sum of the current-time integrals of the per-unit ruptured currents

The ruptured current is derived from the RMS current value detected before a
last zero crossing.
The integral of the current-time area is calculated between the trip time and the
current's disappearance. The current's disappearance is recognized when no
further current zero crossings are detected. An example for calculation of the
current-time integral is displayed in Fig. 3-324, (p. 3-411).

3-410

P437/EN M/R-11-A // P437311650

P437

3 Operation

20,00
15,00
10,00
5,00
0,00
-5,00
-10,00
-15,00
-20,00

Calculating the
current-time integral

Gen. trip command 1

Corr. time running


19Z6126A

Fig. 3-324: Calculation of the current-time integral when CBM is triggered by a general trip command 1.

3.38.8

Resetting Measured Values


Measured values from the respective last CB trip may be reset via the interfaces
on the P437. Accumulated measured values are not affected by such a reset
operation.

3.38.9

Setting Measured Values


Setting measured values in the circuit breaker monitoring function is necessary
when the respective CB has already been exposed to operating conditions or has
been replaced. The available interfaces on the P437 may be used to set
measured values in the circuit breaker monitoring function.
Only such measured values and counter values in the P437 may be set to new
values that do not have their default values set to Blocked.
The stored value will remain unchanged if the default value is set to Blocked.
Executing the set command results in initializing all default values in the P437 to
Blocked.

P437/EN M/R-11-A // P437311650

3-411

P437

3 Operation

MAIN:
Protection active

&

306 001

CBM:
Enabled
[ 044 130 ]

CBM:
Operating mode
[ 022 007 ]
1

&

&

&

MAIN:
Inom C.T. prim.
[ 010 001 ]

1: With trip cmd. only

CBM:
Perm. CB op. Inom,CB
[ 022 013 ]

2: With CB sig.EXT only


3: CB sig. EXT or trip

CBM:
Blocked
[ 044 199 ]
CBM:
internal trip cmd.

CBM:
Inom,CB
[ 022 012 ]

CBM:
Med. curr. Itrip,CB
[ 022 014 ]
CBM:
Perm. CB op. Imed,CB
[ 022 015 ]

310 025

CBM:
Internal CB trip

CBM:
Max. curr. Itrip,CB
[ 022 016 ]

310 030

fnom
I_x

CBM:
Perm. CB op. Imax,CB
[ 022 017 ]
CBM:
Corr. acquis. time
[ 022 018 ]
C

CBM:
Corr. acqu.time trip
[ 007 249 ]

CBM:
Set No. CB oper. A
[
*
]
CBM:
Set remain. CB op. A
[
*
]
CBM:
Set Itrip A
[
*
]
CBM:
Set Itrip**2 A
[
*
]
CBM:
Set I*t A
[
*
]

CBM:
Itrip A
[
*

CBM:
I*t A
[
*

CBM:
Itrip,prim A
[
*
]

CBM:
Itrip**2 A
[
*
]

CBM:
Itrip A
[
*
]

CBM:
Itrip**2 A
[
*
]

CBM:
I*t A
[
*

CBM:
No. of CB oper. A
[
*
]

CBM:
Remain. No. CB op. A
[
*
]

CBM:
Initialize values
[ 003 011 ]
CBM:
Reset meas.val. USER
[ 003 013 ]
Phase x /
Current Ix

CBM:
Set No. CB oper. A

CBM:
Set remain. CB op. A

CBM:
Set Itrip A

CBM:
Set Itrip**2 A

CBM:
Set I*t A

CBM:
No. of CB oper. A

CBM:
Remain. No. CB op. A

A / IA

022 131

022 134

022 137

022 140

022 143

008 011

008 014

B / IB

022 132

022 135

022 138

022 141

022 144

008 012

008 015

C / IC

022 133

022 136

022 139

022 142

022 145

008 013

008 016

Phase x /
Current Ix

CBM:
Itrip A

CBM:
I*t A

CBM:
Itrip,prim A

CBM:
Itrip**2 A

CBM:
Itrip A

CBM:
Itrip**2 A

CBM:
I*t A

A / IA

009 047

009 061

009 212

009 051

009 071

009 077

009 087

B / IB

009 048

009 062

009 213

009 052

009 073

009 078

009 088

C / IC

009 049

009 063

009 214

009 053

009 076

009 079

009 089

52Z0145A

Fig. 3-325: Triggering and calculating circuit breaker monitoring.

3-412

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.38.10

Monitoring the Number of CB Operations


Depending on the selected operating mode the P437 will calculate the current
wear state of the circuit breaker after each disconnection. The number of
remaining CB operations at CB nominal current are calculated and displayed. A
threshold value can be set with the parameter CBM: Remain No. CB op. <.
An alarm is issued should the number of remaining CB operations drop below this
threshold.

CBM:
Remain No. CB op. <
[ 022 020 ]

CBM:
Remain. No. CB op. A
[ 008 014 ]

CBM:
Sig. Rem. No.CB op.<
[ 044 136 ]

CBM:
Remain. No. CB op. B
[ 008 015 ]
CBM:
Remain. No. CB op. C
[ 008 016 ]

19Z6121B

Fig. 3-326: Monitoring the remaining number of CB operations at nominal current.

At the same time each switching operation will increment the P437's counter for
the number of CB operations. The number of CB operations performed is
displayed. A threshold value can be set with the parameter CBM: No. CB
ope rat ions >. An alarm is issued should the number of CB operations
performed exceed this threshold.

CBM:
No. CB operations >
[ 022 019 ]

CBM:
No. of CB oper. A
[ 008 011 ]

CBM:
Sig. No. CB op. >
[ 044 135 ]

CBM:
No. of CB oper. B
[ 008 012 ]
CBM:
No. of CB oper. C
[ 008 013 ]

19Z6122B

Fig. 3-327: Monitoring the number of CB operations performed.

3.38.11

Monitoring Ruptured Currents


In addition to the evaluation of the CB wear state and monitoring of the number
of CB operations performed, the P437 features the means to accumulate and
display the ruptured current values and the square of these values. Threshold
values can be set with the parameters C BM: I trip>, C BM: It rip**2> and
CBM: I*t >. An alarm is issued should the accumulated current values exceed
any of these thresholds.

P437/EN M/R-11-A // P437311650

3-413

P437
3.38.12

3 Operation

Blocking Circuit Breaker Monitoring


When protection injection testing is carried out the circuit breaker monitoring
function should be blocked, so that such testing does not corrupt monitoring
results. CBM protection is blocked if one of the following conditions is met:

Circuit breaker monitoring is blocked by parameters.

Circuit breaker monitoring is blocked by an appropriately configured binary


signal input.

CBM:
Blocked
[ 044 199 ]

CBM:
General enable USER
[ 022 010 ]

&
CBM:
Blocking EXT
[ 044 128 ]
CBM:
Blocking USER
[ 022 150 ]
0
1
0: No
1: Yes

48Z5346B

Fig. 3-328: Blocking circuit breaker monitoring.

3-414

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.39

Limit Value Monitoring (Function Group LIMIT)


Limit Value Monitoring is not designed to be a high-speed protection function; it
is only applied for monitoring and signaling purposes as well as to monitor
temperature limits.

3.39.1

Enable/Disable the Limit Value Monitoring Function


The Limit Value Monitoring function can be disabled or enabled via setting
parameters.

3.39.2

Monitoring Phase Currents and Phase Voltages


With the P437 monitoring of the following measured values is possible in order to
determine if they exceed set upper limit values or fall below set lower limit
values:

Maximum phase current

Minimum phase current

Maximum phase-to-phase voltage

Minimum phase-to-phase voltage

Maximum phase-to-ground voltage

Minimum phase-to-ground voltage

If any of the measured values exceeds or falls below the corresponding upper or
lower limit values, then a signal is issued after the associated time period has
elapsed.

P437/EN M/R-11-A // P437311650

3-415

P437

3 Operation

LIMIT:
General enable USER
[ 014 010 ]

0
LIMIT:
Enabled
[ 040 074 ]

1
0: No
1: Yes

LIMIT:
I>
[ 014 004 ]

LIMIT:
tI>
[ 014 031 ]

MAIN:
Protection active
306 001

LIMIT:
tI> elapsed
[ 040 220 ]

LIMIT:
I>>
[ 014 020 ]

IA
IB

LIMIT:
tI>>
[ 014 032 ]

IC
LIMIT:
tI>> elapsed
[ 040 221 ]

Imax
Imin

LIMIT:
I<
[ 014 021 ]

LIMIT:
tI<
[ 014 033 ]

LIMIT:
tI< elapsed
[ 040 222 ]

LIMIT:
I<<
[ 014 022 ]

LIMIT:
tI<<
[ 014 034 ]

LIMIT:
tI<< elapsed
[ 040 223 ]

47Z0153A

Fig. 3-329: Limit Value Monitoring of minimum and maximum phase current.

3-416

P437/EN M/R-11-A // P437311650

P437

3 Operation

LIMIT:
Enabled
[ 040 074 ]

&

LIMIT:
VPP>

LIMIT:
tVPP>

[ 014 027 ]

[ 014 039 ]

MAIN:
Protection active
306 001

VA-G

COMP

LIMIT:
VPP>>

LIMIT:
tVPP> elapsed
[ 040 228 ]

LIMIT:
tVPP>> elapsed
[ 040 229 ]

LIMIT:
tVPP< elapsed
[ 040 230 ]

LIMIT:
tVPP>>

[ 014 028 ]

VB-G

[ 014 040 ]

VC-G
t

VPP,max
VPP,min

LIMIT:
VPP<

LIMIT:
tVPP<

[ 014 029 ]

[ 014 041 ]

LIMIT:
VPP<<

LIMIT:
tVPP<<

[ 014 030 ]

[ 014 042 ]

LIMIT:
VPG>

LIMIT:
tVPG>

[ 014 023 ]

[ 014 035 ]

COMP

LIMIT:
VPG>>

LIMIT:
tVPG> elapsed
[ 040 224 ]

LIMIT:
tVPG>> elapsed
[ 040 225 ]

LIMIT:
tVPG>>

[ 014 024 ]

[ 014 036 ]

VPG,max
VPG,min

LIMIT:
VPG<

LIMIT:
tVPG<

[ 014 025 ]

[ 014 037 ]

LIMIT:
tVPP<< elapsed
[ 040 231 ]

LIMIT:
VPG<<

LIMIT:
tVPG<<

[ 014 026 ]

[ 014 038 ]

LIMIT:
tVPG< elapsed
[ 040 226 ]

LIMIT:
tVPG<< elapsed
[ 040 227 ]

47Z0154B

Fig. 3-330: Limit Value Monitoring of maximum and minimum phase-to-phase voltage and maximum and minimum
phase-to-ground voltage.

P437/EN M/R-11-A // P437311650

3-417

P437
3.39.3

3 Operation

Monitoring the Neutral-Point Displacement Voltage


The neutral displacement voltage, calculated from the three phase-to-ground
voltages, is monitored by two stages to determine whether it exceeds set
thresholds. If any of the thresholds are exceeded, then a signal is issued after the
associated time period has elapsed.

LIMIT:
Enabled
[ 040 074 ]

MAIN:
Protection active
306 001

VA-G

LIMIT:
VNG>
[ 014 043 ]

LIMIT:
tVNG>
[ 014 045 ]

LIMIT:
tVNG> elapsed
[ 040 168 ]

VB-G

VC-G
LIMIT:
VNG>>
[ 014 044 ]

LIMIT:
tVNG>>
[ 014 046 ]

LIMIT:
tVNG>> elapsed
[ 040 169 ]

S8Z52G8A

Fig. 3-331: Monitoring the neutral-point displacement voltage.

3-418

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.39.4

Monitoring the Linearized Measured DC Values


The direct current, linearized by the analog measured data input, is monitored by
two stages to determine if it exceeds or falls below set thresholds. If any of the
measured values exceed or fall below the corresponding upper or lower limit
values then a signal is issued after the associated time period has elapsed.

LIMIT:
Starting IDC,lin>
[ 040 180 ]
LIMIT:
Enabled
[ 040 074 ]

LIMIT:
IDC,lin>
[ 014 110 ]

LIMIT:
tIDC,lin>
[ 014 112 ]

MAIN:
Protection active
306 001

LIMIT:
tIDC,lin> elapsed
[ 040 182 ]

MEASI:
Curr. IDC,lin p.u.
[ 004 136 ]

LIMIT:
Starting IDC,lin>>
[ 040 181 ]
LIMIT:
IDC,lin>>
[ 014 111 ]

LIMIT:
tIDC,lin>>
[ 014 113 ]

LIMIT:
tIDC,lin>> elapsed
[ 040 183 ]

LIMIT:
Starting IDC,lin<
[ 040 184 ]
LIMIT:
IDC,lin<
[ 014 114 ]

LIMIT:
tIDC,lin<
[ 014 116 ]

LIMIT:
tIDC,lin< elapsed
[ 040 186 ]

LIMIT:
Starting IDC,lin<<
[ 040 185 ]
LIMIT:
IDC,lin<<
[ 014 115 ]

LIMIT:
tIDC,lin<<
[ 014 117 ]

LIMIT:
tIDC,lin<< elapsed
[ 040 187 ]

S8Z52G6A

Fig. 3-332: Monitoring the linearized measured DC values.

P437/EN M/R-11-A // P437311650

3-419

P437

3 Operation

3.39.5

Monitoring the Reference Voltage


The reference voltage Vref (when synchrocheck VT is fitted) is monitored by two
stages to determine whether it exceeds or falls below the corresponding upper or
lower limit values. If the measured value exceeds or falls below the
corresponding upper or lower limit values then a signal is issued after the
associated time period has elapsed.

LIMIT:
General enable USER
[ 014 010 ]

LIMIT:
Enabled
[ 040 074 ]

0: No
1: Yes
MAIN:
Device on-line
[ 003 030 ]

LIMIT:
Vref>
[ 042 144 ]

LIMIT:
tVref>
[ 042 148 ]

1: Yes (= on)
LIMIT:
tVref> elapsed
[ 042 152 ]

LIMIT:
Vref>>
[ 042 145 ]

LIMIT:
tVref>>
[ 042 149 ]

LIMIT:
tVref>> elapsed
[ 042 153 ]

Vref

LIMIT:
Vref<
[ 042 146 ]

LIMIT:
tVref<
[ 042 150 ]

LIMIT:
tVref< elapsed
[ 042 154 ]

LIMIT:
Vref<<
[ 042 147 ]

LIMIT:
tVref<<
[ 042 151 ]

LIMIT:
tVref<< elapsed
[ 042 155 ]

19Z5215A

Fig. 3-333: Monitoring the reference voltage.

3-420

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.39.6

Monitoring the Measured PT 100 Temperature Value


The temperature value that is measured by the P437 with a resistance
thermometer (PT 100) connected to the analog (I/O) module Y, is monitored by
two stages to determine whether it exceeds or falls below the corresponding
upper or lower limit values. If any of the measured values exceed or fall below
the corresponding upper or lower limit values then a signal is issued after the
associated time period has elapsed.

LIMIT:
Starting T>
[ 040 170 ]
LIMIT:
Enabled
[ 040 074 ]

LIMIT:
T>
[ 014 100 ]

LIMIT:
tT>
[ 014 103 ]

MAIN:
Protection
306 active
001
MEASI:
Temperature
[ 004 133 ]

LIMIT:
tT> elapsed
[ 040 172 ]

LIMIT:
Starting T>>
[ 040 171 ]

LIMIT:
T>>
[ 014 101 ]

LIMIT:
tT>>
[ 014 104 ]

LIMIT:
tT>> elapsed
[ 040 173 ]

LIMIT:
Starting T<
[ 040 174 ]

LIMIT:
T<
[ 014 105 ]

LIMIT:
tT<
[ 014 107 ]

LIMIT:
tT< elapsed
[ 040 176 ]

LIMIT:
Starting T<<
[ 040 175 ]

LIMIT:
T<<
[ 014 106 ]

LIMIT:
tT<<
[ 014 108 ]

LIMIT:
tT<< elapsed
[ 040 177 ]

19Z5212A

Fig. 3-334: Monitoring the measured PT 100 temperature value.

P437/EN M/R-11-A // P437311650

3-421

P437

3.40

3 Operation

Programmable Logic (Function Groups LOGIC and LOG_2)


Programmable (or user-configurable) logic enables the user to link binary signals
within a framework of Boolean equations.
Two function groups for programmable logic are available, that can be used
independently of each other. There are only two differences between these two
function groups:

LOGIC offers 128 logical equations.


LOG_2 offers only 4 logical equations.

On the other hand, LOG_2 features long-term timers.


For example for output 1:

L O GIC : Ti me t1 output 1 and LOGIC: Time t2 output 1: settable


from 0 to 600 s.
LOG_2 : Time t1 outpu t 1 and L OG_2: Time t2 output 1: settable
from 0 to 60,000 s.

The following description concentrates on the function group LOGIC. Where


applicable, any differences to LOG_2 are mentioned.

Binary signals in the P437 may be linked by logical OR or AND operations


with the option of additional NOT operations by setting L OGIC: Fct.assignm.
outp. 1 (or LOGIC : F ct.as s ignm . outp. 2 to L OGIC : Fct.assignm. outp .
32, or LOG_2: Fct.assi gnm. ou tp. 1 to L O G_2 : F ct .assignm. outp. 4).
The Boolean equations need to be defined without the use of brackets. The
following rule applies to the operators: NOT before AND before OR.
A maximum of 32 elements can be processed in one Boolean equation. In
addition to the signals generated by the P437, initial conditions for governing the
equations can be set using setting parameters, through binary signal inputs, or
through the serial interfaces.
Logical operations of the function group LOGIC can be controlled through the
binary signal inputs in different ways.
The binary input signals LOGI C: Inpu t 01 EXT (or LOGIC: Input 0 2 EXT, ,
LOGIC : I np ut 4 0 EXT) have an updating function, whereas the input signals
LOGIC : Set 1 EXT (or LOGI C: Set 2 E XT, , LOGIC: Set 8 EXT) are
latched. The logic can only be controlled from the binary signal inputs configured
for LOGIC : Se t 1 E XT if the corresponding reset input LOGIC: Reset 1 EX T)
has been configured for a binary signal input. If only one or neither of the two
functions is configured, then this is interpreted as Logic externally set. If the
input signals of the two binary signal inputs are implausible (such as when they
both have a logic value of 1), then the last plausible state remains stored in
memory. (For LOG_2, there are no such parameters for assigning binary input
signals.)

3-422

P437/EN M/R-11-A // P437311650

P437

3 Operation

WARNING
When using the programmable logic, the user must carry out a functional
type test to conform with the requirements of the relevant protection/control
application. In particular, it is necessary to verify that the requirements for
the implementation of logic linking (by setting) as well as the time
performance during startup of the P437, during operation and when there is a
fault (blocking of the P437) are fulfilled.

LOGIC:
Set 1 USER
[ 034 030 ]
0
1
0: No

LOGIC:
1 has been set
[ 034 067 ]

1: Yes

INP:
Fct. assignm. U xxx
[ xxx xxx ]

U x1
U x2
U x3
U xx
Address

036 051

Address

036 059

LOGIC:
1 set externally
[ 034 075 ]

LOGIC:
Set 1 EXT
[ 034 051 ]

LOGIC:
Reset 1 EXT
[ 034 059 ]

D5Z52FAB

Fig. 3-335: Control of logic operations via setting parameters or stored input signals. (The logic does not apply to
LOG_2.)

The LOGIC : Trigge r 1 signal is a triggering function that causes a 100 ms


pulse to be issued.

P437/EN M/R-11-A // P437311650

3-423

P437

3 Operation

LOGIC:
General enable USER
[ 031 099 ]

LOGIC:
Enabled
[ 034 046 ]

0
1
0: No
1: Yes

MAIN:
Protection active

LOGIC:
Fct.assignm. outp. 1
[ 030 000 ]

306 001

Signal 1
Signal 2
Signal 3

Signal n

LOGIC:
Op. mode t output 1
[ 030 001 ]

LOGIC:
Input 01 EXT
[ 034 000 ]

LOGIC:
Input 16 EXT
[ 034 015 ]

1
2
3

LOGIC:
1 has been set
[ 034 067 ]

4
5
0

LOGIC:
8 has been set
[ 034 074 ]

0: Without timer stage


1: Oper./releas.delay
2: Oper.del./puls.dur.

LOGIC:
1 set externally
[ 034 075 ]

3: Op./rel.delay,retrig

5
LOGIC:
Time t1 output 1
[ 030 002 ]
LOGIC:
Time t2 output 1
[ 030 003 ]

4: Op.del./puls.dur.,rt
5: Minimum time

LOGIC:
8 set externally
[ 034 082 ]

LOGIC:
Output 01 (t)
[ 042 033 ]

LOGIC:
Set 1 USER
[ 034 030 ]

LOGIC:
Set 8 USER
[ 034 037 ]

LOGIC:
Trigger 1
[ 034 038 ]
0
LOGIC:
Output 01
[ 042 032 ]

1
0: don't execute
1: execute

LOGIC:
Trigger 8
[ 034 045 ]
0
1
0: don't execute
1: execute

D5Z52CDA

Fig. 3-336: Setting options for programmable logic, function group LOGIC (shown here for output 1).

3-424

P437/EN M/R-11-A // P437311650

P437

3 Operation

LOG_2:
General enable USER
[ 011 137 ]

LOG_2:
Enabled
[ 011 138 ]

0
1
0: No
1: Yes

LOG_2:
Op. mode t output 1
[ 050 001 ]

MAIN:
Protection active

LOG_2:
Fct.assignm. outp. 1
[ 050 000 ]

306 001

0
1
2

Signal 1

3
Signal 2

Signal 3

5
0

Signal n

0: Without timer stage


1: Oper./releas.delay
2: Oper.del./puls.dur.
3: Op./rel.delay,retrig
4: Op.del./puls.dur.,rt
5: Minimum time

5
LOG_2:
Time t1 output 1
[ 050 002 ]
LOG_2:
Time t2 output 1
[ 050 003 ]

LOG_2:
Output 1 (t)
[ 052 033 ]

LOG_2:
Output 1
[ 052 032 ]

19Z80CDA

Fig. 3-337: Setting options for programmable logic, function group LOG_2 (shown here for output 1).

The output signal of an equation can be fed into a further, higher order, equation
as an input signal thus creating a sequence of interlinked Boolean equations. The
equations are processed in the sequence defined by the order of each equation.
It should be noted that in the case of overlapping equations, the result is
provided by the equation with the highest order.
The output signal of each equation is fed to a separate timer stage with two
timer elements and a choice of operating modes. This offers the possibility of
assigning a freely configurable time characteristic to the output signal of each
Boolean equation. In the Minimum time operating mode, the setting of timer
stage t2 has no effect. The following diagrams (Fig. 3-338, (p. 3-426) to
Fig. 3-342, (p. 3-428)) show the time characteristics for the various timer stage
operating modes.
If the P437 is switched to offline the equations are not processed and all outputs
are set to the 0 logic level.

P437/EN M/R-11-A // P437311650

3-425

P437

3 Operation

t2 = 0s
LOGIC:
Output n
LOGIC:
Output n (t)
t1

t1

t1 = 0s
LOGIC:
Output n
LOGIC:
Output n (t)

t2

t2

t1, t2 > 0s
LOGIC:
Output n
LOGIC:
Output n (t)

t1

t2

t1

t2

D5Z50BYA

Fig. 3-338: Operating mode 1: Pickup/reset delay (Oper./releas.delay). (This diagram is also valid for LOG_2, if the
signal parameters are replaced by the corresponding ones from LOG_2 .)

t2 = 0s
LOGIC:
Output n
LOGIC:
Output n (t)

t1

t1

t1 = 0s
LOGIC:
Output n
LOGIC:
Output n (t)

t2

t2

t1, t2 > 0s
LOGIC:
Output n
LOGIC:
Output n (t)

t1

t2

t1

t2

D5Z50BZA

Fig. 3-339: Operating mode 2: Pulse, delayed pickup (Oper.del./puls.dur.). (This diagram is also valid for LOG_2, if
the signal parameters are replaced by the corresponding ones from LOG_2 .)

3-426

P437/EN M/R-11-A // P437311650

P437

3 Operation

t2 = 0s
LOGIC:
Output n
LOGIC:
Output n (t)

t1

t1

Retrigger pulse

t1 = 0s
LOGIC:
Output n
LOGIC:
Output n (t)

t2

t2

t2

Retrigger pulse

t1, t2 > 0s
LOGIC:
Output n
LOGIC:
Output n (t)
t2

t1

t1

t2
t2
t2

D5Z50CAA

Fig. 3-340: Operating mode 3: Pickup/reset delay, retriggerable (Op./rel.delay,retrig). (This diagram is also valid for
LOG_2, if the signal parameters are replaced by the corresponding ones from LOG_2 .)

t2 = 0s
LOGIC:
Output n
LOGIC:
Output n (t)
t1

t1

t1 = 0s
LOGIC:
Output n
LOGIC:
Output n (t)

t2

t2

Retrigger pulse

t1, t2 > 0s
LOGIC:
Output n
LOGIC:
Output n (t)
t1
t1

t2

t1

t2

t1

D5Z50CBA

Fig. 3-341: Operating mode 4: Pulse, delayed pickup, retriggerable (Op.del./puls.dur.,rt). (This diagram is also valid
for LOG_2, if the signal parameters are replaced by the corresponding ones from LOG_2 .)

P437/EN M/R-11-A // P437311650

3-427

P437

3 Operation

LOGIC:
Output n
LOGIC:
Output n (t)
t1

t1

D5Z50CCA

Fig. 3-342: Operating mode 5: Minimum time (Minimum time). (This diagram is also valid for LOG_2, if the signal
parameters are replaced by the corresponding ones from LOG_2 .)

Through appropriate configuration, it is possible to assign the function of a binary


input signal to each output of a logic operation. The output of the logic operation
then has the same effect as if the binary signal input to which this function has
been assigned were triggered.

3-428

P437/EN M/R-11-A // P437311650

P437

3 Operation

LOGIC:
Sig.assig. outp. 1
[ 044 000 ]

Signal 1 EXT
[ AAA AAA ]
Signal 2 EXT
[ BBB BBB ]
Signal 3 EXT
[ CCC CCC ]

Signal n EXT
[ NNN NNN ]
Address

AAA AAA

LOGIC:
Output 01
[ 042 032 ]

Signal 1 EXT
[ AAA AAA ]

INP:
Fct. assignm. U xxx
[ xxx xxx ]

Address

AAA AAA

-Uxxx

LOGIC:
Sig.assig.outp. 1(t)
[ 044 001 ]

Address

BBB BBB

LOGIC:
Output 01 (t)
[ 042 033 ]

Signal 2 EXT
[ BBB BBB ]

INP:
Fct. assignm. U xxx
[ xxx xxx ]

Address

BBB BBB

-Uxxx

D5Z52FBA

Fig. 3-343: Signal assignment to outputs of Boolean equations. (This diagram is also valid for LOG_2, if the
parameters from LOGIC are replaced by the corresponding ones from LOG_2 .)

P437/EN M/R-11-A // P437311650

3-429

P437

3.41

3 Operation

Binary Counts (Function Group COUNT)


The P437 features four binary counters. Each of these can count the positive
pulse edges of a binary signal present at an appropriately configured binary
signal input. Such a binary signal can be provided with debouncing.

3.41.1

Enable/Disable the Counting Function


The counting function (COUNT) can be disabled or enabled via setting
parameters.

3.41.2

Debouncing
The first positive pulse edge of the binary input signal to be counted will trigger a
timer stage which will continue to run for the set debouncing time period. Each
positive pulse edge during the debouncing time re-triggers the timer stage. The
binary input signal will be counted if it is stable during the set debouncing time
period.
The debouncing time can be set separately for each of the four counters.
After the set debouncing time has elapsed, the state of the signal is checked. If it
is the same as prior to the occurrence of the first pulse edge, it will not be
counted.

Count

Signal sequence

19Z50APA

Fig. 3-344: Debouncing signal flow. Set debouncing time: 50 ms.

3.41.3

Counting Function
The debounced binary signal is counted by a 16 bit counter. The counters may
be set to a specific count value (preload function) by setting a parameter or via
the serial interfaces. The values of the counters can be shown on the LC-display
and read out via the PC interface or the communications interface.
For each of the four counters, there is a limit value that can be optionally set:

C O UN T: L imit coun te r 1 (and the same way for counters 2 to 4),

settable from 1 to 65000,

setting Blocked disables the limit check. (This setting is the default
value.)

A warning signal (COUNT: Warni ng coun t 1 and the same way for counters 2
to 4) is issued if the associated counter value exceeds the set limit.

3-430

P437/EN M/R-11-A // P437311650

P437

3 Operation

3.41.4

Transmitting the Counter Values via Communications Interface


The counter values are transmitted via the communications interface when a
signal is presented to an appropriately configured binary signal input, a trigger
signal is issued by a setting parameter or at cyclic intervals as set at the cycle
time stage C OUN T: C ycle t.cou nt trans m. When the counter value is
transmitted at cyclic intervals, then transmission is time synchronized if the ratio
60/(set cycle time) comes to an integer. In all other cases the counter values are
transmitted at time intervals determined by a free running internal clock.

3.41.5

Counter Values Reset


The counter values may be reset all at once by setting parameter
COUN T: R ese t USER or via an appropriately configured binary signal input as
well as by the general reset action.

COUNT:
General enable USER
[ 217 000 ]

0
COUNT:
Enabled
[ 217 001 ]

1
0: No
MAIN:
Device on-line
[ 003 030 ]
1: Yes (= on)

1: Yes

COUNT:
Count 1
[ 217 100 ]

COUNT:
Debounce t. count. 1
[ 217 160 ]

COUNT:
Set counter 1 EXT
[ 217 130 ]

COUNT:
Count 1
[ 217 100 ]

CT=m

Debouncing

R
COUNT:
Transmit counts USER
[ 217 008 ]
0
COUNT:
Transmit counts
[ 217 010 ]

1
0: don't execute
1: execute
C

COUNT:
Transmit counts EXT
[ 217 009 ]
C

COUNT:
Cycle t.count transm
[ 217 007 ]

COMM1:
Count 1
[ --- --- ]

G
COUNT:
Reset USER
[ 217 003 ]

0
1
0: don't execute

= 0 min
COUNT:
Reset
[ 217 005 ]

1: execute
COUNT:
Reset EXT
[ 217 004 ]
MAIN:
General reset USER
[ 003 002 ]
1: execute

MAIN:
General reset EXT
[ 005 255 ]

19Z82ANA

Fig. 3-345: Binary Count. (This diagram shows counter 1 as an example. The displayed logic is also valid for
counters 2 to 4, where C O U N T : S e t c o u n t e r 1 E X T and C O U N T : C o u n t 1 have to be replaced by the
respective parameters.

P437/EN M/R-11-A // P437311650

3-431

P437

3-432

3 Operation

P437/EN M/R-11-A // P437311650

P437
4

Design
The P437 is available in different types of cases and with different combinations
of modules.
Irrespective of the type a P437 is equipped with a detachable HMI or a fixed local
control panel. The local control panel is covered with a tough film so that the
specified degree of IP protection will be maintained. In addition to the essential
control and display elements, a parallel display consisting of multi-colored LED
indicators is also incorporated (see Section 6.2, (p. 6-2)). The meaning of the
various LED indications is shown in plain text on a label strip.
The PC interface (9-pin D-Sub female connector) is located under the hinged
cover at the bottom of the local control panel.

P437/EN M/R-11-A // P437311650

4-1

P437

4.1

4 Design

Designs
The P437 is available in a surface-mounted and a flush-mounted case. Depending
on the connection type pin-terminal or ring-terminal connection the case sizes
differ. The location diagrams (Section 5.7, (p. 5-19)) show the available
combinations of case widths and connection types.
Electrical connections are made via plug-in threaded terminal blocks. The
threaded terminal blocks in the surface-mounted case are accessible from the
front of the device after unscrewing the crosshead screws on the sides (see
Fig. 4-1, (p. 4-3), ) and removing the local control panel. The local control
panel can then be secured by inserting the tabs in the slots in the left side wall
(see Fig. 4-1, (p. 4-3), ). The flush-mounted case is connected at the back of
the case.

WARNING
The local control panel is connected to processor module P by a plug-in
connecting cable. Do not bend the connecting cable! Secure the local control
panel by inserting it in the slots provided on the left.

WARNING
The secondary circuit of live system current transformers must not be
opened! If the secondary circuit of a live CT is opened, there is the danger
that the resulting voltages will endanger personnel and damage the
insulation.

WARNING
For pin-terminal connection devices, the terminal block for system current
transformer connection is not a shorting block! Therefore always short-circuit
the system current transformers before loosening the threaded terminals.

4-2

P437/EN M/R-11-A // P437311650

4 Design

P437

47Z14BBA

Fig. 4-1: Surface-mounted case, removal of local control panel (or in case of a detachable HMI the case front
panel). The illustration shows the 84TE case with (fixed) local control panel.

P437/EN M/R-11-A // P437311650

4-3

P437

4 Design

Dimensional Drawings

4.2.1

Dimensional Drawings for the 84 TE Case

147.5
177.5
184.5

4.2

X6

434.8
464.0
481.6

257.1

177.5

Fig. 4-2: Surface-mounted 84 TE case. (Dimensions in mm.)

X6

434.8

227.9
253.6

159.0
168.0

284.9
259.0
25.9

5.0

410.0

5.0

Fig. 4-3: Flush-mounted case 84 TE with panel opening, flush-mount method 1 (without angle brackets).
(Dimensions in mm.)

4-4

P437/EN M/R-11-A // P437311650

P437

177.5

101.6

4 Design

X6

227.9
253.6

434.8
464.0

101.6

6.4

186.5

481.6

445.9
464.0

Fig. 4-4: Flush-mounted case 84 TE with panel opening, flush-mount method 2 (with angle brackets and frame).
(Dimensions in mm.)
The device has increased mechanical robustness if flush-mount method 2 (with
angle brackets and frame) is used for the flush-mounted case.

P437/EN M/R-11-A // P437311650

4-5

P437

4.3

4 Design

Hardware Modules
The P437 is constructed from standard hardware modules. The following table
gives an overview of the modules relevant for the P437.
Key:

4-6

: standard equipment,

: optional,

: depending on order,

*: Module is not depicted in the terminal connection diagrams (Section 5.7,


(p. 5-19)).

P437/EN M/R-11-A // P437311650

P437

4 Design

Type

Item Number

Description

A(CH1 CH2)

009650356

A ff

A(CH1 CH2)

009650355

A(CH1 CH2)

Width

P437
412

P437
413

Communication module (for RS 485 wire 4TE


connection)

A ff

Communication module (for plastic


fiber)

4TE

009650354

A ff

Communication module (for glass fiber,


ST connector)

4TE

A(CH3)

009651567

D ff

InterMiCOM Module COMM3 (RS 485)

4TE

A(CH3)

009651569

D ff

InterMiCOM Module COMM3 (for glass


fiber)

4TE

A(CH4)

InterMiCOM Module COMM4 (RS 485)

4TE

A(CH4)

InterMiCOM Module COMM4 (for glass


fiber)

4TE

A(ETH CH2)

009651427

E ff

Ethernet module (for 100 Mbit/s


Ethernet, glass fiber, SC connector and
RJ45 wire)

4TE

A(ETH CH2)

009651471

E ff

Ethernet module (for 100 Mbit/s


Ethernet, glass fiber, ST connector and
RJ45 wire)

4TE

A(Red. ETH
CH2)

009651531

B ff

Redundant Ethernet Board (100 Mbit/s,


SHP Protocol, glass fiber, ST connector)

4TE

A(Red. ETH
CH2)

009651532

B ff

Redundant Ethernet Board (100 Mbit/s, 4TE


RSTP Protocol, glass fiber, ST connector)

A(Red. ETH
CH2)

009651533

B ff

Redundant Ethernet Board (100 Mbit/s,


DHP Protocol, glass fiber, ST connector)

4TE

000336188

C ff

* Bus module (digital, for 84 TE device)

4TE

000336421

B ff

* Bus module (analog)

4TE

009651571

E ff

* Processor Unit

4TE

T(4I 4V)

009650307

A ff

Transformer module 4 x I, 4 x V (pin


connection)

8TE

T(4I 4V)

009650321

A ff

Transformer module 4 x I, 4 x V (ring


connection)

8TE

T(4I 5V)

009650308

A ff

Transformer module 4 x I, 5 x V (pin


connection)

8TE

T(4I 5V)

009650322

A ff

Transformer module 4 x I, 5 x V (ring


connection)

8TE

P437/EN M/R-11-A // P437311650

4-7

P437

4 Design

Type

Item Number

Description

Width

P437
412

T(1I)

009650313

Transformer module 1 x I (pin


connection)

8TE

T(1I)

009650327

Transformer module 1 x I (ring


connection)

8TE

V(4I 8O)

009651534

B ff

Power supply module 24 - 60 V DC,


standard variant (switching threshold
18 V)

4TE

V(4I 8O)

009651536

B ff

Power supply module 24 - 60 V DC,


switching threshold 73 V

4TE

V(4I 8O)

009651537

B ff

Power supply module 24 - 60 V DC,


switching threshold 90 V

4TE

V(4I 8O)

009651539

B ff

Power supply module 24 - 60 V DC,


switching threshold 155 V

4TE

V(4I 8O)

009651538

B ff

Power supply module 24 - 60 V DC,


switching threshold 146 V

4TE

V(4I 8O)

009651544

B ff

Power supply module 60 - 250 V DC /


100 - 230 V AC, standard variant
(switching threshold 18 V)

4TE

V(4I 8O)

009651546

B ff

Power supply module 60 - 250 V DC /


100 - 230 V AC, switching threshold
73 V

4TE

V(4I 8O)

009651547

B ff

Power supply module 60 - 250 V DC /


100 - 230 V AC, switching threshold
90 V

4TE

V(4I 8O)

009651549

B ff

Power supply module 60 - 250 V DC /


100 - 230 V AC, switching threshold
155 V

4TE

V(4I 8O)

009651548

B ff

Power supply module 60 - 250 V DC /


100 - 230 V AC, switching threshold
146 V

4TE

X(4H)

009651493

B ff

Binary module (4 high-break contacts)

4TE

X(6I 8O)

000336971

D ff

Binary I/O module (6 binary inputs, 8


output relays), standard variant
(switching threshold 18 V)

4TE

X(6I 8O)

009651306

A ff

Binary I/O module (6 binary inputs, 8


4TE
output relays), switching threshold 73 V

X(6I 8O)

009651334

A ff

Binary I/O module (6 binary inputs, 8


4TE
output relays), switching threshold 90 V

4-8

P437
413

P437/EN M/R-11-A // P437311650

P437

4 Design

Type

Item Number

Description

Width

P437
412

P437
413

X(6I 8O)

009651445

A ff

Binary I/O module (6 binary inputs, 8


output relays), switching threshold
146 V

4TE

X(6I 8O)

009651362

A ff

Binary I/O module (6 binary inputs, 8


output relays), switching threshold
155 V

4TE

X(6O)

000336973

B ff

Binary module (6 output relays)

4TE

Y(4I)

000337406

D ff

Analog I/O module, standard variant


(switching threshold 18 V)

4TE

Y(4I)

009651307

A ff

Analog I/O module, switching threshold


73 V

4TE

Y(4I)

009651335

A ff

Analog I/O module, switching threshold


90 V

4TE

Y(4I)

009651446

A ff

Analog I/O module, switching threshold


146 V

4TE

Y(4I)

009651363

A ff

Analog I/O module, switching threshold


155 V

4TE

The space available for the modules measures 4 HE in height by 40 TE or 84 TE


in width (HE = 44.45 mm, TE = 5.08 mm).
The location of the individual modules and the position of the threaded terminal
blocks in the P437 are shown in the location figures and terminal connection
diagrams (Section 5.7, (p. 5-19)).

P437/EN M/R-11-A // P437311650

4-9

P437

4-10

4 Design

P437/EN M/R-11-A // P437311650

P437
5

Installation and Connection


WARNING
Sustained exposure to high humidity during storage may cause damage to
electronics and reduce the lifetime of the equipment.
We recommend that storage humidity shall not exceed 50% relative
humidity.
Once the MiCOM products have been unpacked, we recommend that they are
energized within the three following months.
Where electrical equipment is being installed, sufficient time should be
allowed for acclimatization to the ambient temperature of the environment,
before energization.

WARNING
Only qualified personnel, familiar with the Warning page at the beginning of
this manual, may work on or operate this device.

WARNING
The instructions given in the Section 5.5, (p. 5-12) (Protective and
Operational Grounding) should be noted. In particular, check that the
protective ground connection is secured with a tooth lock washer, as per the
diagram Installing the protective grounding conductor terminal (Fig. 5-8,
(p. 5-12)).
If a cable screen is added to this connection or removed from it, then the
protective grounding should be checked again.

WARNING
The SC connector and RJ45 wire of the Ethernet module cannot be connected
at the same time.

P437/EN M/R-11-A // P437311650

5-1

P437

5 Installation and Connection

WARNING
Installation of the detachable HMI: A protective conductor (protective
earth) with a cross section at least 1.5 mm (US:AWG14 or thicker) must be
connected to the protective grounding conductor terminal on the detachable
HMI at one end and on the other end to the protective grounding conductor
terminal on the devices case. Both the detachable HMI and the device have
to be installed in the same substation.
In order to prevent personal injuries the communications cable installed to
the detachable HMI must never come in contact with parts that may be
subjected to dangerous live voltages.
It is prohibited to install or run the communications cable to the detachable
HMI next to high-voltage lines or high-voltage connections. This is to prevent
induced currents that would lead to electromagnetic interferences.

5-2

P437/EN M/R-11-A // P437311650

5 Installation and Connection

5.1

P437

Unpacking and Packing


All P437 overcurrent and control devices are packaged separately into dedicated
cartons and shipped with outer packaging. Use special care when opening
cartons and unpacking devices, and do not use force. In addition, make sure to
remove supporting documents and the type identification label supplied with
each individual device from the inside carton. The design revision level of each
module included in the device when shipped can be determined from the list of
components (assembly list). This list of components should be filed carefully.
After unpacking, each device should be inspected visually to confirm it is in
proper mechanical condition.
If the P437 needs to be shipped, both inner and outer packaging must be used. If
the original packaging is no longer available, make sure that packaging conforms
to DIN ISO 2248 specifications for a drop height 0.8 m.

P437/EN M/R-11-A // P437311650

5-3

P437

5.2

5 Installation and Connection

Checking Nominal Data and Design Type


The nominal data and design type of the P437 can be determined by checking
the type identification label (see below). One type identification label is located
under the upper hinged cover on the front panel and a second label can be found
on the inside of the device. Another copy of the type identification label is fixed
to the outside of the P437 packaging.

Fig. 5-1: Example of the type identification label of a MiCOM P3x3 device.

The P437 design version can be determined from the order number. A
breakdown of the order number is given in Chapter Order Information of this
manual.

5-4

P437/EN M/R-11-A // P437311650

P437

5 Installation and Connection

5.3

Location Requirements
The P437 has been designed to conform to EN 60255-6. Therefore it is important
when choosing the installation location to make certain that it provides the
operating conditions as specified in above DIN norm sections 3.2 to 3.4. Several
of these important operating conditions are listed below.

5.3.1

Environmental Conditions
Ambient temperature: -5 C to +55 C [+23 F to +131 F]
Air pressure:

800 to 1100 hPa

Relative humidity:

The relative humidity must not result in the formation of


either condensed water or ice in the P437.

Ambient air:

The ambient air must not be significantly polluted by dust,


smoke, gases or vapors, or salt.

Solar Radiation:

Direct solar radiation on the front of the device must be


avoided to ensure that the LC-Display remains readable.

5.3.2

Mechanical Conditions
Vibration stress:

10 to 60 Hz, 0.035 mm and 60 to 150 Hz, 0.5 g

Earth quake resistance: 5 ... 8 Hz, 3.5 mm / 1.5 mm, 8 ... 35 Hz, 5 m/s,
3 x 1 cycle

5.3.3

Electrical Conditions for Auxiliary Voltage of the Power Supply


Operating range: 0.8 to 1.1 VA,nom with a residual ripple of up to 12 % VA,nom

5.3.4

Electromagnetic Conditions
Substation secondary system design must follow the best of modern practices,
especially with respect to grounding and EMC.

P437/EN M/R-11-A // P437311650

5-5

P437

5.4

5 Installation and Connection

Installation
The dimensions and mounting dimensions for surface-mounted cases are given
in Section 4.2, (p. 4-4). When the P437 is surface-mounted on a panel, the wiring
to the P437 is normally run along the front side of the mounting plane. If the
wiring is to be at the back, an opening can be provided above or below the
surface-mounted case. Fig. 5-2, (p. 5-6) shows such an opening.

D5Z50MBA

Fig. 5-2: Opening (cutout) for running the connecting leads to an 40 TE surface-mounted case.

The opening width for the 40 TE surface-mounted case: 213 mm (shown in this
figure), for the 84 TE surface-mounted case: 435 mm. The other dimensions are
the same for all cases.
Flush-mounted cases are designed for control panels. The dimensions and
mounting dimensions are given in Chapter Design. When the P437 is mounted
on a cabinet door, special sealing measures are necessary to provide the degree
of protection required for the cabinet (IP 51).
Connection of protective grounding conductor: See Protective and Operational
Grounding (Section 5.5, (p. 5-12))
Instructions for selecting the flush-mount method:
The P437 has increased mechanical robustness if either the surface-mounted case
or for the flush-mounted case flush-mount method 2 (with angle brackets and
frame) is used. In this case, test severity class 2 of the vibration test, test severity
class of the shock resistance test on operability as well as test severity class 1 of
the shock resistance test on permanent shock are applied additionally.

Dimensions of the panel cutouts:


Dimensional drawings of the panel cutouts for all cases and for the detachable HMI
can be found in Section 4.2, (p. 4-4).

5-6

P437/EN M/R-11-A // P437311650

P437

5 Installation and Connection

For flush-mount method 1 (without angle brackets and frame), the procedure is
as follows:
Before the P437 can be installed into a control panel, the local control panel (or
the front element of the case for devices with detachable display) must be taken
down. The local control panel is removed as described below:
1.

Remove both top and bottom hinged flaps from the device. (Lift/lower
both hinged flaps 180 up/down. Hold them in the middle and bend them
slightly. The side mountings of both hinged flaps can then be disengaged.)

2.

Remove the M3.5 screws (see Fig. 5-3, (p. 5-8)).

3.

Then remove the local control panel.

WARNING
The local control panel (or front element) is connected to processor module P
by a plug-in connecting cable. Make sure the connector position is correct. Do
not bend the connecting cable!

Then remove the lower M4 screws and only loosen the upper M4 screws (see
Fig. 5-3, (p. 5-8)). Now insert the P437 into the panel opening from the rear
so that the upper M4 screws fit into the corresponding holes. Then tighten all the
M4 screws. After this, replace the local control panel.

WARNING
When replacing the local control panel, take care not to tighten the M3.5
screws with too much strength! (Fastening torque 1.5 to 1.8 Newton meters.)

If the control panel thickness is 2 mm, the longer M3.5 and M4 bolts must be
used. Longer screws are enclosed within the device packing.

P437/EN M/R-11-A // P437311650

5-7

P437

5 Installation and Connection

For panels with a


thickness 2 mm,
replace the M3 bolts
with the enclosed
longer M3 bolts

Merely loosen the


upper screws and
hook device on side
plates to mount

< 3 mm

M4

M3.5

Remove the lower


screws completely
prior to mounting

12Y6181B

Fig. 5-3: Installation of a case into a control panel. Flush-mount method 1 (without the angle brackets and frame ).
Example for a device with a 40 TE case.

WARNING
The P437 has increased mechanical robustness if either the surface-mounted
case or for the flush-mounted case flush-mount method 2 (with angle
brackets and frame, see Fig. 5-5, (p. 5-9)) is used.
Connection of protective grounding conductor: See Section 5.5, (p. 5-12).

For flush-mount method 2 (using the angle brackets and frame), the procedure is
as follows:

5-8

1.

Remove the screws as shown in Fig. 5-4, (p. 5-9), and mount the
enclosed angle brackets using these same screws.

2.

Then push the device into the control panel cutout from the front.

3.

Secure the device to the control panel by using the enclosed M6 screws
(see Fig. 5-5, (p. 5-9)).

4.

Assemble the cover frame and snap-fasten onto the fixing screws.

P437/EN M/R-11-A // P437311650

P437

5 Installation and Connection

45Z5058A

Fig. 5-4: Mounting the angle brackets.


Angle brackets

M6
B6
6.4

Height: 204mm

M6 x 15

Frame

for
280mm
Width:
E case
the 40T
12Y6183B

Fig. 5-5: Installation of a case into a control panel, flush-mount method 2 (with angle brackets and frame). Example
for a device in a 40 TE case.

The cover frame width of the 40 TE surface-mounted case is: 280 mm, of the
84 TE case is: 486 mm. The cover frame height is for all cases: 204 mm.

P437/EN M/R-11-A // P437311650

5-9

P437

5 Installation and Connection

WARNING
The P437 has increased mechanical robustness if either the surface-mounted
case or for the flush-mounted case flush-mount method 2 (with angle
brackets and frame, see Fig. 5-5, (p. 5-9)) is used.
Connection of protective grounding conductor: See Section 5.5, (p. 5-12).

A rack mounting kit can be used to combine a flush-mounted 40 TE case with a


second sub-rack to form a 19 mounting rack (see Fig. 5-6, (p. 5-10)). The
second sub-rack can be another device, for example, or an empty sub-rack with a
blank front panel. Fit the 19 mounting rack to a cabinet as shown in Fig. 5-7,
(p. 5-11).

Connection flange

Tapped bush

Bolt

61Y5077A

Fig. 5-6: Combining 40 TE flush-mounted cases to form a 19 mounting rack.

WARNING
Connection of protective grounding conductor: See Section 5.5, (p. 5-12).

5-10

P437/EN M/R-11-A // P437311650

P437

5 Installation and Connection

Covering flange

Rack frame

61Y5078A

Fig. 5-7: Installing the P437 in a cabinet with a 19 mounting rack.

WARNING
Connection of protective grounding conductor: See Section 5.5, (p. 5-12).

P437/EN M/R-11-A // P437311650

5-11

P437

5 Installation and Connection

5.5

Protective and Operational Grounding


The device must be reliably grounded to meet protective equipment grounding
requirements. The surface-mounted case is grounded using the bolt and nut,
appropriately marked, as the ground connection. The flush-mounted case must
be grounded in the area of the rear sidepieces at the location provided.
The bracket is marked with the protective ground symbol:
The cross-section of the ground conductor must conform to applicable national
standards. A minimum cross section of 2.5 mm (AWG12) is required.
In addition, a protective ground connection at the terminal contact on the power
supply module (identified by the letters PE on the terminal connection
diagram) is also required for proper operation of the device. The cross-section of
this ground conductor must also conform to applicable national standards. A
minimum cross section of 1.5 mm (US:AWG14 or thicker) is required.
If a detachable HMI is installed, a further protective conductor (ground/earth) of
at least 1.5 mm (US:AWG14 or thicker) must be connected to the DHMI
protective conductor terminal to link the DHMI and the main relay case; these
must be located within the same substation.
All grounding connections must be low-inductance, i.e. it must be kept as short
as possible.

1
2

2
3
4

PE terminal

PE terminal

surface-mount. case

flush-mount. case

Pos.

Description

Pos.

Description

Nut M4

Nut M4

Tooth lock wash.A4.3

Tooth lock wash.A4.3

Clamp bracket

Clamp bracket

Bolt M4

Bolt M4

19Y5220B

Fig. 5-8: Installing the protective grounding conductor terminal.

The protective conductor (earth) must always be connected to the protective


grounding conductor terminal in order to guarantee the safety given by this setup.

5-12

P437/EN M/R-11-A // P437311650

P437

5 Installation and Connection

5.6

Connection
The P437 Distance Protection Device must be connected in accordance with the
terminal connection diagram as indicated on the type identification label. The
relevant terminal connection diagrams that apply to the P437 are to be found
either in the supporting documents supplied with the device, or in Section 5.7,
(p. 5-19).
In general copper conductors with a cross section of 2.5 mm (US:AWG12) are
sufficient to connect a system current transformer to a current input on the P437.
To reduce CT knee-point voltage requirements, it may be necessary to install
shorter copper conductors with a greater cross section between the system
current transformers and the current inputs on the P437. Copper conductors
having a cross section of 1.5 mm (US:AWG14) are adequate to connect binary
signal inputs, the output relays and the power supply input.
All connections run into the system must always have a defined potential.
Connections that are pre-wired but not used should preferably be grounded when
binary inputs and output relays are isolated. When binary inputs and output
relays are connected to common potential, the pre-wired but unused connections
should be connected to the common potential of the grouped connections.

5.6.1

Connecting Measuring and Auxiliary Circuits

5.6.1.1

Power Supply
Before connecting the auxiliary voltage VA for the P437 power supply, it must be
ensured that the nominal value of the auxiliary device voltage corresponds with
the nominal value of the auxiliary system voltage.

5.6.1.2

Current-Measuring Inputs
When connecting the system transformers, it must be ensured that the
secondary nominal currents of the system and the device correspond.

WARNING
The secondary circuit of live system current transformers must not be
opened! If the secondary circuit of a live CT is opened, there is the danger
that the resulting voltages will endanger personnel and damage the
insulation.

WARNING
For pin-terminal connection devices, the terminal block for system current
transformer connection is not a shorting block! Therefore always short-circuit
the system current transformers before loosening the threaded terminals.

5.6.1.3

Connecting the Measuring Circuits


The system transformers must be connected in accordance with the standard
schematic diagram shown in Fig. 5-9, (p. 5-14).

P437/EN M/R-11-A // P437311650

5-13

P437

5 Installation and Connection

It is essential that the grounding configuration shown in the diagram be followed.


If the CT or VT connection is reversed, this can be taken into account when
making settings (see Chapter Settings).

A
B
C

1U
2U

1IA

1IB

1IC

1IN

2IN

e
n

W
N

P437

Line

Parallel line
47Z01BCA

Fig. 5-9: Standard schematic diagram.

5-14

P437/EN M/R-11-A // P437311650

P437

5 Installation and Connection

5.6.1.4

Connecting a Resistance Thermometer


A resistance thermometer can be connected if the device is fitted with analog
module Y. This analog I/O module input is designed to connect a PT 100
resistance thermometer. The PT 100 should be connected using the 3-wire
method (see Fig. 5-10, (p. 5-15)). No supply conductor compensation is
required in this case.

PT 100

P437

S8Z52H9A

Fig. 5-10: Connecting a PT 100 using the 3-wire method.

5.6.1.5

Connecting Binary Inputs and Output Relays


The binary inputs and output relays are freely configurable. When configuring
these components it is important to note that the contact rating of the binary I/O
modules (X) varies (see Section 2.4.7, (p. 2-12)).
The polarity for connected binary signal inputs is to be found in the terminal
connection diagrams (see supporting documents supplied with the device or in
Section 5.7, (p. 5-19)). This is to be understood as a recommendation only.
Connection to binary inputs can be made as desired.

5.6.2

Connecting the IRIGB Interface


An IRIGB interface for time synchronization may be installed as an optional
feature. It is connected by a BNC connector. A coaxial cable having a
characteristic impedance of 50 must be used as the connecting cable.

5.6.3

Connecting the Serial Interfaces

5.6.3.1

PC Interface
The PC interface is provided so that personnel can operate the device from a
personal computer (PC).

WARNING
The PC interface is not designed as a permanent connection. Consequently,
the female connector does not have the extra insulation from circuits
connected to the system that is required per VDE 0106, part 101.

5.6.3.2

Communication Interfaces
The communication interfaces are provided as a permanent connection of the
device to a control system for substations or to a central substation unit.

P437/EN M/R-11-A // P437311650

5-15

P437

5 Installation and Connection

Depending on the type, communication interface 1 on the device is connected


either by a special fiber-optic connector or an RS 485 interface with twisted pair
copper wires. Communication interface 2 is only available as an RS 485 interface.
The selection and assembly of a properly cut fiber-optic connecting cable
requires special knowledge and expertise and is therefore not covered in this
operating manual.

WARNING
The fiber-optic interface may only be connected or disconnected when the
supply voltage for the device is shut off.

An RS 485 data transmission link between a master and several slave devices
can be established by using the optional communication interface. The
communication master could be, for instance, a central control station. Devices
linked to the communication master, e.g. P437, are set-up as slave devices.
The RS 485 interface available on the P437 was designed so that data transfer in
a full duplex transmission mode is possible using a 4-wire data link between
devices. Data transfer between devices using the RS 485 interface is set up only
for a half duplex transmission mode. To connect the RS 485 communication
interface the following must be observed:

Only twisted pair shielded cables must be used, that are common in
telecommunication installations.

At least one symmetrical twisted pair of wires is necessary.

Conductor insulation and shielding must only be removed from the core in
the immediate vicinity of the terminal strips and connected according to
national standards.

All shielding must be connected to an effective protective ground surface at


both ends.

Unused conductors must all be grounded at one end.

A 4wire data link as an alternative to a 2-wire communications link is also


possible. A cable with two symmetrical twisted pair wires is required for a 4-wire
data link. A 2-wire data link is shown in Fig. 5-11, (p. 5-17), and a 4-wire data
link is shown in Fig. 5-12, (p. 5-18) as an example for channel 2 on the
communication module. The same is valid if channel 1 on the communication
module is available as a RS 485 interface.
2-wire data link:
The transmitter must be bridged with the receiver on all devices equipped
electrically with a full duplex communication interface, e.g. the P437. The two
devices situated at either far end must have a 200 to 220 resistor installed to
terminate the data transmission conductor. In MiCOM Px3x devices, and also in
the P437, a 220 resistor is integrated into the RS 485 interface hardware and
can be connected with a wire jumper. An external resistor is therefore not
necessary.
4-wire data link:
Transmitter and receiver must be bridged in the device situated on one far end
of the data transmission conductor. The receivers of slave devices, that have an
electrically full-duplex communication interface as part of their electrical system,
e.g. the P437, are connected to the transmitter of the communication master
device, and the transmitters of slave devices are connected to the receiver of the
master device. Devices equipped electrically with only a half duplex RS 485
communication interface are connected to the transmitter of the communication
5-16

P437/EN M/R-11-A // P437311650

P437

5 Installation and Connection

master device. The last device in line (master or slave device) on the data
transmission conductor must have the transmitter and receiver terminated with
a 200 to 220 resistor each. In MiCOM Px3x devices, and also in the P437, a
220 resistor is integrated into the RS 485 interface hardware and can be
connected with a wire jumper. An external resistor is therefore not necessary.
The second resistor must be connected externally to the device (resistor order
number see Chapter Accessories and Spare Parts).
-X10
200 ... 220

D1[T]

D2[R]

D2[R]

D1[T]

P437

XXXX
First participant

Last participant

connect. to the line

connect. to the line

(e.g. the master)

-X10

D2[R]

P437

D1[T]

D2[R]

D1[T]

XXXX
Device with halfduplex interface
19Z6480A

Fig. 5-11: 2-wire data link.

P437/EN M/R-11-A // P437311650

5-17

P437

5 Installation and Connection

-X10

200 ... 220

D1[T]

D2[R]

D2[R]

D1[T]

P437

XXXX
First participant

Last participant

connect. to the line

connect. to the line

(e.g. the master)

-X10

D2[R]

P437

D1[T]

D2[R]

D1[T]

XXXX
Device with halfduplex interface

19Z6481A

Fig. 5-12: 4-wire data link.

5-18

P437/EN M/R-11-A // P437311650

P437

5 Installation and Connection

5.7

Location and Connection Diagrams

5.7.1

Location Diagrams P437 412/413


Location diagrams for P437 in 84 TE case
Pin-terminal connection (P437 412)

01

02

03

04

05

CH1
CH2

4I
4V

06

07

08

09

1I

10

11

4I

12

13

6I
8O

15

6I
8O

17

18

19

6I
8O

20

21

4H

CH4

4I
5V

16

6I
8O

ETH
CH2

14

4I
8O

CH3

6O

Red.
ETH
CH2

01

02

03

04

01

02

03

05

05

ETH
CH2

06

07

4I
4V

07

08

09

10

11

12

13

14

15

16

17

18

19

20

21

16

17

18

19

20

21

Ring-terminal connection (P437 413)


04

CH1
CH2

06

08

09

1I

10

11

4I

12

13

6I
8O

14

15

6I
8O

6I
8O

4H

CH4

4I
5V

6I
8O

4I
8O

CH3

6O

Red.
ETH
CH2

01

02

03

04

05

06

07

08

09

10

11

12

13

14

15

16

17

18

19

20

21

Each of the numbered slots can be fitted with max. 1 module.


If a location diagram shows several modules for a particular slot, then these are
alternatives, depending on the ordering options (Chapter 15, (p. 15-1)).

5.7.2

Terminal Connection Diagrams P437412/413


_ is a placeholder for the slot.
See also Section 5.5, (p. 5-12), Protection Conductor Terminal (PCT) / Case
Grounding / Protective Earth

P437/EN M/R-11-A // P437311650

5-19

P437

5 Installation and Connection

Transformer
module

Type T
4I / 4/5V

Transformer
module

Type T
1I

Type Y

Analog
module

4I

Voltage measuring

Ring Pin

inputs

X051 X052

X031 X031
1

14

15

16

17

18

VAG
VBG
VCG

T5
T6
T7

VNG

T90

IN,par

T24

12

X032
1

Pin

X_1

X_1

Measuring outputs
K_01
valid

#
0..20 mA

Option:
11

Ring

VRef

T15

X_1

Output relays

K_07

17

18

U_09

Signal and
measuring inputs

Type X

Binary
module

4H

Ring

Pin

X_1

X_1

High-break
contacts

13

14

15

16

17

19

20

21

22

23

24

Pin

X_1

X_1

K_02

4
5

K_01

X_2
11

12

Vin

U_02

Vin

U_03
U_04

Vin

10

11

11

12

12

13

13

14

14

15

15

16

16

17

17

18

X_3
2

26

27

K_03

5-20

24

Type V
4I / 8O

18

20

21

22

23

24

25

26

27

20

21

22

23

25

24

26

27

9
25

26

27

U_02

Vin

U_03

Vin

U_04

Vin

U_05

Vin

U_06

Communication
Type A
module
Red. ETH / CH2

RX

X/Y

U17

X/Y

U18

X8
TX

K_02

K_03

Ethernet [IEC], Port 2


optical fiber link ST
X14

X/Y

U28

X/Y

U29

X15

K_04
K_05
K_06
K_07
K_08

TX

X10
1
2

Vin

Serial [COMM2]
wire link only
X//Y
D2[R]

U20

U_01

X_3

K_04

Vin

X7

K_01

19

U_01

Ethernet [IEC], Port 1


optical fiber link ST

Output relays

Signal inputs

K_04

X_3

23

U_06

RX
1

PT100

19

X_2
10

20

0..20 mA

U_05

K_02

X_2

19

Vin

X_3

Power supply
module

Ring

K_08

Signal inputs

U_01

Vin

K_01

K_03

22

21

K_02

16

20

15

19

14

K_03

K_01

13

Pin

X_1

X_2

Ring

valid

X_3

6O

Output relays

K_02

0..20 mA

T4

Type X

K_04
K_05
K_06

18

Binary
module

IN

12

T3

X_1

12

11

IC

Pin

X_1

inputs

T2

Ring

X_2
1

IB

6I / 8O

11

10

T1

module

10

Current measuring

IA

U_08

13

Current measuring
input

Ring Pin

Type X

Binary

D1[T]
RS 422 / 485

Vin
Vin

K_05

Vin

U_02
U_03

Port supervision
7
8

Alarm Port 2

K22

IRIG-B
time synchronization

Power supply

+ Vaux
-

K21

U_04

K_06

PE

Alarm Port 1

X11

U100

#
#

U21

P437/EN M/R-11-A // P437311650

P437

5 Installation and Connection

Type A

Communication
module

CH1 / CH2

Per order

Serial [Channel 1]
optical fiber link

Ethernet [IEC]
optical fiber link ST
X7

X//Y U17

RX

X//Y U18

TX

X//Y
D2[R]

U19

4
5

U17

Communication Type A
module (InterMiCOM) CH3

X/Y

U18

TX

Per order
COMM4
optical fiber link ST
X36

X//Y U22

RX

U26
X/Y

X//Y U23

X//Y U31

1
2

U24
D1[T]

X//Y U32
or wire link

D2[R]

RS 485

RS 422 / 485

TX

X38

X//Y

3
4

D1[T]

RX
X37

or wire link
X33

X13

TX

Per order

X31
RX

Communication Type A
module (InterMiCOM) CH4

COMM3
optical fiber link ST

X32

or
optical fiber link SC

or wire link

X/Y

X8

X8

ETH / CH2

Per order

X7

X9

Type A

Communication
module

X//Y
D2[R]

3
4
5

U33
D1[T]
RS 485

and wire link


X12

Serial [Channel 2]
wire link only
X10
1
2

X//Y

D1[T]
X10

RS 422 / 485
IRIG-B
time synchronization
X11
1

Serial [COMM2]
wire link

U20

X//Y U25
RJ45

D2[R]

3
5

#
#

U21

P437/EN M/R-11-A // P437311650

1
2

X//Y
D2[R]

U20

4
5

D1[T]
RS 422 / 485

5-21

P437

5-22

5 Installation and Connection

P437/EN M/R-11-A // P437311650

P437
6

Local Control (HMI)

6.1

Local Control Panel (HMI)


Switchgear installed in the bay can be controlled from the local control panel
(HMI). All the data required for operation of the protection device is entered from
the local control panel, and the data important for system management is read
out there as well. The following tasks can be handled from the local control
panel:

Controlling switchgear units

Readout and modification of settings

Readout of cyclically updated measured operating data and logic status


signals

Readout of operating data logs and of monitoring signal logs

Readout of event logs after overload situations, ground faults, or short


circuits in the power system

Device resetting and triggering of additional control functions used in


testing and commissioning

Control is also possible through the PC interface. This requires a suitable PC and
a specific operating program.

P437/EN M/R-11-A // P437311650

6-1

P437

6 Local Control (HMI)

6.2

Display and Keypad

6.2.1

Text Display
The local control panel as a text display includes an LC display containing 4 20
alphanumeric characters.
There are seven keys with permanently assigned functions situated below the
LCD and six additional freely configurable function keys on the right hand side of
the LCD.
Furthermore the local control panel (HMI) is provided with 23 LED indicators. 17
of these are on the left hand side of the LCD. The other six LED indicators are
situated to the right of the six freely configurable function keys. (See
Section 3.11, (p. 3-65) for the configuration of the LED indicators.)

TRIP

H18

ALARM
OUT OF SERVICE
HEALTHY

H19

EDIT MODE

H20

H21

H22

H23

Fig. 6-1: View of the local control panel and layout of the LED indicators for the text display.

6.2.2

Display Illumination
If none of the control keys are pressed, the display illumination will switch off
once the set return time illumination (setting in menu tree: Par/Conf/LOC)
has elapsed. Pressing any of the control keys will turn the display illumination on
again. In this case the control action that is normally triggered by that key will
not be executed. Reactivation of the display illumination is also possible by using
a binary input.
If continuous display illumination is required, the function return time
illumination (LO C : Re tu rn ti me i llu min.) is set to blocked.

6.2.3

Contrast of the Display


The contrast of the LC display can be adjusted by pressing 3 keys on the local
control panel at the same time, as follows:

6-2

P437/EN M/R-11-A // P437311650

6 Local Control (HMI)

P437

Keep the Enter key ( ) and the Clear key ( ) pressed simultaneously, then you
can press Up or Down (
,
) to raise or lower the contrast, respectively.

6.2.4

Short Description of Keys

6.2.4.1

Up and Down Keys

Panel Level: The up/down keys switch between the pages of the Measured
Value Panel.
Menu Tree Level: Press the up and down keys to navigate up and down
through the menu tree in a vertical direction. If the unit is in input mode, the
up and down keys have a different function.
Input mode: Settings can only be changed in the input mode, which is signaled
by the LED indicator labeled EDIT MODE. Press the up and down keys in this
mode to change the setting value.

Up key: the next higher value is selected.

Down key: the next lower value is selected.

With list settings, press the up and down key to change the logic operator of
the value element.
6.2.4.2

Left and Right Keys

Menu Tree Level: Press the left and right keys to navigate through the
menu tree in a horizontal direction. If the unit is in input mode, the left and
right keys have a different function.
Input mode: Settings can only be changed in the input mode, which is signaled
by the LED indicator labeled EDIT MODE. When the left and right keys are
pressed, the cursor positioned below one of the digits in the change-enabled
value moves one digit to the right or left.

Left key: the cursor moves to the next digit on the left.

Right key: the cursor moves to the next digit on the right.

In the case of a list setting, press the left and right keys to navigate through
the list of items available for selection.
6.2.4.3

ENTER Key

Panel Level: Press the ENTER key at the Panel level to go to the menu tree.
Menu Tree Level: Press the ENTER key to enter the input mode. Press the
ENTER key a second time to accept the changes as entered and exit the input
mode. The LED indicator labeled EDIT MODE signals that the input mode is
active.
6.2.4.4

CLEAR Key

P437/EN M/R-11-A // P437311650

6-3

P437

6 Local Control (HMI)

Press the CLEAR key to reset the LED indicators and clear all measured event
data. The records in the recording memories are not affected by this action.
Input mode: When the CLEAR key is pressed all changes entered are rejected
and the input mode is exited.
6.2.4.5

READ Key

Press the READ key to access a selected event recording from either the Panel
level or from any other point in the menu tree.
6.2.4.6

Configurable Function Keys

By pressing a function key the assigned function is triggered.


More details on assigning functions to function keys can be found in Section 3.6,
(p. 3-39).
More details on handling function keys can be found in Section 6.8, (p. 6-10).

6-4

P437/EN M/R-11-A // P437311650

6 Local Control (HMI)

6.3

P437

Display Levels
All data relevant for operation and all device settings are displayed on two levels.
At the Panel level, data such as measurements are displayed in Panels that
provide a quick overview of the current state of the bay. The menu tree level
below the panel level allows the user to select all data points (settings, signals,
measured variables, etc.) and to change them, if appropriate. To access a
selected event recording from either the panel level or from any other point in
the menu tree, press the READ key:

P437/EN M/R-11-A // P437311650

6-5

P437

6 Local Control (HMI)

6.4

Display Panels
The text display of the P437 can display Measured Value Panels which are called
up according to system conditions.
Selected measured values are displayed on the Measured Value Panels. The
system condition determines which Panel is called up (examples are the
Operation Panel and the Fault Panel). Only the Measured Value Panels relevant
for the particular design version of the given device and its associated range of
functions are actually available.
The Operation Panel is always provided.

Measured Value
Panel(s)

Record View

Voltage VAB prim.


20.7 kV
Voltage VBC prim.
20.6 kV

Oper/Rec/OP_RC
Operat. data record

+
Device type

Parameters

Operation

Device ID

Cyclic measurements

Configuration parameters
Function parameters

Global

Control and testing


Operating data recordings

Events

Event counters
Measured fault data
Event recordings

Measured operating data

Main functions
Parameter subset 1
Parameter subset ...
Control

Physical state signals


Logical state signals

Menu tree

Fig. 6-2: Display panels and menu tree.

6-6

P437/EN M/R-11-A // P437311650

6 Local Control (HMI)

6.5

P437

Menu Tree and Data Points


All data points (setting values, signals, measured values, etc.) are selected using
a menu tree. When navigating through the menu tree, the first two lines of the
LC-Display always show the branch of the menu tree that is active, as selected
by the user. The data points are found at the lowest level of a menu tree branch
and they are displayed either with their plain text description or in numerically
encoded form, as selected by the user. The value associated with the selected
data point, its meaning, and its unit of measurement are displayed in the line
below.

P437/EN M/R-11-A // P437311650

6-7

P437

6.6

6 Local Control (HMI)

List Data Points


List data points are a special category. In contrast to other data points, list data
points generally have more than one associated value element. This category
includes tripping matrices, programmable logic functions, and event logs. When
a list data point is selected, the symbol is displayed in the bottom line of the
LCD, indicating that a sub-level is situated below this displayed level. The
individual value elements of a list data point are found at this sub-level. In the
case of a list parameter, the individual value elements are linked by operators
such as OR.

6-8

P437/EN M/R-11-A // P437311650

6 Local Control (HMI)

6.7

P437

Note Concerning the Step-by-Step Descriptions


The following presentation of the individual control steps shows which displays
can be changed in each case by pressing keys. A small black square to the right
of the enter key indicates that the LED indicator labeled Edit Mode is illuminated.
The examples used here are not necessarily valid for the device type described
in this manual; they merely serve to illustrate the control principles involved.

P437/EN M/R-11-A // P437311650

6-9

P437

6.8

6-10

6 Local Control (HMI)

Configurable Function Keys

P437/EN M/R-11-A // P437311650

6 Local Control (HMI)

6.8.1

P437

Configuration of the Function Keys F1 to Fx


Function keys [F1] to [Fx] can be assigned a password (see Section 6.11.9, (p. 631)). In such a case they are effective only after that password has been
entered. By default, no password is required to use the function key.
It is assumed for the following operating example that function key [F1] is
enabled only after the password (as assigned at F_K EY: Pass word funct. key
1) has been entered. After the password has been entered the function key will
remain active for the duration set at F _KE Y: R etu rn tim e fct.k ey s.
Thereafter, the function key is disabled until the password is entered again.

P437/EN M/R-11-A // P437311650

6-11

P437

6 Local Control (HMI)

Control Step / Description

Step 0

Display example.

Step 1

Press function key [F1].


Eight asterisks (*) appear in the fourth line as a prompt
to enter the password if it is required.

Control
Action

Display
Voltage A-B prim.
20.7 kV
Voltage B-C prim.
20.6 kV

********

(By default, i.e. no password required, this step and the


next do not exist and the function key is effective
immediately as described in Step 3.)
Step 2a

If a password is set, press the keys corresponding to


the set password, for example:
Left

Down
*

Right
*

Up
The display will change as shown in the right hand side
column.
Now press the ENTER key. If the correct password has
been entered, the active display will re-appear.
Function key [F1] is now effective for the set return
time.

*
Voltage A-B prim.
20.7 kV
Voltage B-C prim.
20.6 kV

By default, no password is required and therefore


function key [F1] is always effective.
Each function key can be assigned its own password,
and the return time is running after correct password
entry for each individual function key!)
If an invalid password has been entered, the display
shown above in Step 1 will appear.
Step 2b

6-12

This control step can be canceled at any time by


pressing the CLEAR key before the ENTER key is
pressed.

Voltage A-B prim.


20.7 kV
Voltage B-C prim.
20.6 kV

P437/EN M/R-11-A // P437311650

P437

6 Local Control (HMI)

Control Step / Description

Control
Action

Display

Step 3

Press [F1] again. The function configured to this


function key is carried out.

Voltage A-B prim.


20.7 kV
Voltage B-C prim.
20.6 kV

Step 4

When function keys are pressed during their associated


return time, then the set function is carried out directly,
i.e. without checking for the password again.

Oper/CtrlTest/LOC
Param. change enabl.
Yes

(By default, i.e. no password required, this step does


not exist and the function key is permanently effective.)

P437/EN M/R-11-A // P437311650

6-13

P437

6.9

6 Local Control (HMI)

Changing Between Display Levels

Jumping from Menu Tree Level to Panel Level


After start-up of the device, the menu tree level is displayed.
Control Step / Description

Control
Action

Display

Step 0

From the Menu Tree Level, the user can jump to the
Panel Level from any position within the menu tree.

Par/Func/Glob/MAIN
Device on-line
No (=off)

Step 1

First press the up key and hold it down while pressing


the CLEAR key.

Voltage A-B prim.


20.7 kV
Voltage B-C prim.
20.6 kV

Note: It is important to press the up key first and


release it last in order to avoid unintentional resetting of
stored data.

Jumping from Panel Level to Menu Tree Level


Control Step / Description

Control
Action

Display

Step 0

Example of a Measured Value Panel.

Voltage A-B prim.


20.7 kV
Voltage B-C prim.
20.6 kV

Step 1

Press the Enter key to go from the Panel Level to the


Menu Tree Level.

P437

After the set return time has elapsed (setting in menu tree: Par/Conf/LOC), the
display will automatically switch to the Panel level if a Measured Value Panel has
been configured.

6-14

P437/EN M/R-11-A // P437311650

P437

6 Local Control (HMI)

6.10

Control at Panel Level


The measured values that will be displayed on the Measured Value Panels can
first be selected in the menu tree under Par/Conf/LOC. The user can select
different sets of measured values for the Operation Panel (L OC : F ct .
Op erat ion P ane l), the Overload Panel (LOC: Fct . Overload Panel), and the
Fault Panel (LOC : Fct. F aul t P ane l).
Only the Measured Value Panels relevant for the particular design version of the
given device and its associated range of functions are actually available. The
selected set of values for the Operation Panel is always available. Please see
Section 6.11.5.1, (p. 6-22) for instructions regarding selection. If
MAIN: Wit hout fu nction has been selected for a given panel, then that
panel is disabled.
The Measured Value Panels are called up according to system conditions. If, for
example, the device detects an overload or a ground fault, then the
corresponding Measured Value Panel will be displayed as long as the overload or
ground fault situation exists. Should the device detect a fault, then the Fault
Panel is displayed and remains active until the measured fault values are reset,
by pressing the CLEAR key, for example.
Control Step / Description

Control
Action

Display

Step 0

Two measured values can be displayed simultaneously


on the Panel.

Voltage A-B prim.


20.7 kV
Voltage B-C prim.
20.6 kV

Step 1

If more than two measured values have been selected,


they can be viewed one page at a time by pressing the
up or down keys.

Voltage C-A prim.


20.8 kV
Current A prim.
415 A

The device will also show the next page of the


Measured Value Panel after the set Hold-Time for
Panels (LOC : Hold-t im e for Pan el s, located at Par/
Conf in the menu tree) has elapsed.

P437/EN M/R-11-A // P437311650

or

6-15

P437

6 Local Control (HMI)

6.11

Control at the Menu Tree Level

6.11.1

Navigation in the Menu Tree

Folders and Function Groups


All data points are organized in different folders based on practical control
requirements.
At the root of the menu tree is the unit type; the tree branches into the three
main folders Settings, Measurements & Tests and Fault & Event Records,
which form the first folder level. Up to two further folder levels follow so that the
entire folder structure consists of three main branches and a maximum of three
folder levels.
At the end of each branch of folders are the various function groups in which the
individual data points (settings) are combined.

Unit
type

Folder
plane 1

PX yyy

PX yyy
Parameters

Folder
plane 2

Folder
plane 3

Function
groups

Data
points

PX yyy
Operation

PX yyy
Events

Oper/
Cyclic measurements

Oper/Cycl/
Meas. operating data

Oper/Cycl/Data/
MAIN

Oper/Cycl/Data/MAIN
Date
01.01.99 dd.mm.yy

Fig. 6-3: Basic menu tree structure.

6-16

P437/EN M/R-11-A // P437311650

P437

6 Local Control (HMI)

6.11.2

Switching Between Address Mode and Plain Text Mode


The display on the local control panel can be switched between address mode
and plain text mode. In the address mode the display shows settings, signals,
and measured values in numerically coded form, that is, as addresses. In plain
text mode the settings, signals, and measured values are displayed in the form
of plain text descriptions. In either case, control is guided by the menu tree. The
active branch of the menu tree is displayed in plain text in both modes. In the
following examples, the display is shown in plain text mode only.
Control Step / Description

Control
Action

Display

Step 0

In this example, the user switches from plain text mode


to address mode.

Par/Func/Glob/MAIN
Device online
No (=off)

Step 1

To switch from address mode to plain text mode or vice


versa, press the CLEAR key and either the left key or
the right key simultaneously. This can be done at any
+
point in the menu tree.

Par/Func/Glob/MAIN
003.030
0

or

P437/EN M/R-11-A // P437311650

6-17

P437
6.11.3

6 Local Control (HMI)

Change-Enabling Function
Although it is possible to select any data point in the menu tree and read the
associated value by pressing the keys, it is not possible to switch directly to the
input mode. This safeguard prevents unintended changes in the settings.
There are two ways to enter the input mode.

Global change-enabling function: To activate the global changeenabling function, set the LOC: P aram. cha nge enabl. parameter to
Yes (menu tree: Oper/CtrlTest/LOC).
The change can only be made after the password has been entered.
Thereafter, all further changes with the exception of specially protected
control actions (see Section 6.11.8, (p. 6-29)) are enabled without
entering the password.

Selective change-enabling function: Password input prior to any setting


change.
This setup is designed to prevent accidental output and applies even when
the global change-enabling function has been activated. The following
example is based on the factory-set password. If the password has been
changed by the user (see Section 6.11.9, (p. 6-31)), the following
description will apply accordingly.

6-18

P437/EN M/R-11-A // P437311650

P437

6 Local Control (HMI)

Control Step / Description

Control
Action

Display

Step 0

In the menu tree Oper/CtrlTest/LOC, select the


LOC: Param. change enabl. parameter.

Oper/CtrlTest/LOC
Param. change enabl.
No

Step 1

Press the ENTER key. Eight asterisks (*) appear in the


fourth line of the display.

Oper/CtrlTest/LOC
Param. change enabl.
No
********

Step 2

Press the following keys in sequence:

Oper/CtrlTest/LOC
Param. change enabl.
No
*

Left

Right

Oper/CtrlTest/LOC
Param. change enabl.
No
*

Up

Oper/CtrlTest/LOC
Param. change enabl.
No
*

Down

Oper/CtrlTest/LOC
Param. change enabl.
No
*

The display will change as shown in the column on the


right.
Now press the enter key. The LED indicator labeled
EDIT MODE will light up. This indicates that the setting
can now be changed by pressing the up or down
keys.

Oper/CtrlTest/LOC
Param. change enabl.
No

If an invalid password has been entered, the display


shown in Step 1 appears.
Step 3

Change the setting to Yes.

Oper/CtrlTest/LOC
Param. change enabl.
Yes

Step 4

Press the enter key again. The LED indicator will go out.
The unit is enabled for further setting changes.

Oper/CtrlTest/LOC
Param. change enabl.
Yes

The same procedure applies to any setting change unless the global changeenabling function has been activated. This method is recommended for a single
setting change only. If several settings are to be changed, then the global
change-enabling function is preferable. In the following examples, the global
change-enabling function has been activated.
6.11.3.1

Automatic Return
The automatic return function prevents the change-enabling function from
remaining activated after a change of settings has been completed. Once the set
return time (L O C: Aut om. re tur n ti me, menu tree Par/Conf/LOC) has
elapsed, the change-enabling function is automatically deactivated, and the

P437/EN M/R-11-A // P437311650

6-19

P437

6 Local Control (HMI)

display switches to a Measured Value Panel corresponding to the current system


condition. The return time is restarted when any of the control keys is pressed.
6.11.3.2

Forced Return
The return described above can be forced from the local control panel by first
pressing the up key and then holding it down while pressing the CLEAR key.
It is important to press the up key first and release it last in order to avoid
unintentional deletion of stored data.

Even when the change-enabling function is activated, not all settings can be
changed. For some settings it is also necessary to disable the protective function
(MAIN : D ev ice on-li ne, menu tree: Par/Func/Glob/MAIN). Such settings include
the configuration settings, by means of which the device interfaces can be
adapted to the system. The following entries in the Change column of the
Telegram Documentation (part of the separately available
DataModelExplorer) indicate whether values can be changed or not:

on: The value can be changed even when the protective function is
enabled.

off: The value can only be changed when the protective function is
disabled.

: The value can be read out but cannot be changed.

The device is factory-set so that the protective function is disabled.

6-20

P437/EN M/R-11-A // P437311650

P437

6 Local Control (HMI)

6.11.4

Changing Parameters
If all the conditions for a value change are satisfied, the desired setting can be
entered.
Control Step / Description

Step 0

Example of a display.
In this example, the change-enabling function is
activated and the protective function is disabled, if
necessary.

Control
Action

Display
Oper/CtrlTest/LOC
Param. change enabl.
Yes

Step 1

Select the desired setting by pressing the keys.

Par/Conf/LOC
Autom. return time
50000 s

Step 2

Press the ENTER key. The LED indicator labeled EDIT


MODE will light up. The last digit of the value is
highlighted by a cursor (underlined).

Par/Conf/LOC
Autom. return time
50000 s

Step 3

Press the left or right keys to move the cursor to


the left or right.

Par/Conf/LOC
Autom. return time
50000 s

Step 4

Change the value highlighted by the cursor by pressing


the up and down keys. In the meantime the device
will continue to operate with the old value.

Par/Conf/LOC
Autom. return time
50010 s

Step 5

Press the ENTER key. The LED indicator labeled EDIT


MODE will go out and the device will now operate with
the new value. Press the keys to select another setting
for a value change.

Par/Conf/LOC
Autom. return time
50010 s

Step 6

If you wish to reject the new setting while you are still
entering it (LED indicator labeled EDIT MODE is on),
press the CLEAR key. The LED indicator will go out and
the device will continue to operate with the old value.
A further setting can be selected for a value change by
pressing the keys.

Par/Conf/LOC
Autom. return time
50000 s

P437/EN M/R-11-A // P437311650

6-21

P437

6 Local Control (HMI)

6.11.5

List Parameters

6.11.5.1

Setting a List Parameter


Using list settings, the user is able to select several elements from a list in order
to perform tasks such as defining a trip command or defining the measurements
that will be displayed on Measured Value Panels. As a rule, the selected elements
are linked by an OR operator. Other operators (NOT, OR, AND, NOT OR and
NOT AND) are available in the LOGIC function group for linking the selected list
items. In this way binary signals and binary input signals can be processed in a
Boolean equation tailored to meet user requirements. For the DNP 3.0
communication protocol, the user defines the class of a setting instead of
assigning operators. The definition of a trip command shall be used here as an
illustration.

6-22

P437/EN M/R-11-A // P437311650

P437

6 Local Control (HMI)

Control Step / Description

Control
Action

Display

Select a list setting (in this example, the parameter


MAIN : Fct .assig.t rip cmd.1 at Par/Func/Glob/
MAIN in the menu tree). The down arrow () indicates
that a list setting has been selected.

Par/Func/Glob/MAIN
Fct.assign.trip cmd.

Step 1

Press the down key. The first function and the first
selected signal will appear in the third and fourth lines,
respectively. The symbol #01 in the display indicates
the first item of the selection. If MA IN: Wi th out
funct ion appears for the first item, then this means
that no function assignment has yet been made.

Par/Func/Glob/MAIN
Fct.assign.trip cmd.
#01 DIST
Trip zone 1

Step 2

Scroll through the list of assigned functions by pressing


the right and left keys.

Par/Func/Glob/MAIN
Fct.assign.trip cmd.
OR
#02 DIST
Trip zone 2

Once the end of the list is reached, the display shown


on the right will appear.

Par/Func/Glob/MAIN
Fct.assign.trip cmd.
#05 MAIN
?????

Step 3

Press the ENTER key at any position in the list. The LED
indicator labeled EDIT MODE will light up.

Par/Func/Glob/MAIN
Fct.assign.trip cmd.
#02 DIST
Trip zone 2

Step 4

Scroll through the assignable functions by pressing the


right and left keys in the input mode.

Par/Func/Glob/MAIN
Fct.assign.trip cmd.
#02 DIST
Trip zone 4

Step 5

Select the operator or the class using the up and


down keys. In this particular case, only the OR
operator can be selected. There is no limitation on the
selection of classes.

Par/Func/Glob/MAIN
Fct.assign.trip cmd.
OR
#02 DIST
Trip zone 4

Step 6

Press the ENTER key. The LED indicator will go out. The
assignment has been made. The unit will now operate
with the new settings.

Par/Func/Glob/MAIN
Fct.assign.trip cmd.
OR
#02 DIST
Trip zone 4

Step 0

If no operator has been selected, the OR operator is


always assigned automatically when the ENTER key is
pressed. There is no automatic assignment of classes.
Step 7

Press the up key to exit the list at any point in the


list.

Par/Func/Glob/MAIN
Fct.assign.trip cmd.

Step 8

If you wish to reject the new setting while you are still
entering it (LED indicator labeled EDIT MODE is on),
press the CLEAR key. The LED indicator labeled EDIT
MODE will be extinguished.

P437/EN M/R-11-A // P437311650

Par/Func/Glob/MAIN
Fct.assign.trip cmd.
OR
#02 DIST
Trip zone 2

6-23

P437
6.11.5.2

6 Local Control (HMI)

Deleting a List Parameter


If MAIN : Wit hou t fun ction is assigned to a given item, then all the following
items are deleted. If this occurs for item #01, everything is deleted.

6-24

P437/EN M/R-11-A // P437311650

P437

6 Local Control (HMI)

6.11.6

Memory Readout
Memories can be read out after going to the corresponding entry point. This does
not necessitate activating the change-enabling function or even disabling the
protective functions. Inadvertent clearing of a memory at the entry point is not
possible.
The following memories are available:

In the menu tree Oper/Rec/OP_RC: Operating data memory

In the menu tree Oper/Rec/MT_RC: Monitoring signal memory

Event memories

In the menu tree Events/Rec/FT_RC: Fault memories 1 to 8


In the menu tree Events/Rec/OL_RC: Overload memories 1 to 8

Not all of these event memories are present in each unit.


6.11.6.1

Readout of the Operating Data Memory


The operating data memory contains stored signals of actions that occur during
operation, such as the enabling or disabling of a device function. A maximum of
100 entries is possible, after which the oldest entry is overwritten.
Control Step / Description

Step 0

Select the entry point for the operating data memory.

Control
Action

Display
Oper/Rec/OP_RC
Operat. data record.

Step 1

Press the down key to enter the operating data


memory. The latest entry is displayed.

Oper/Rec/OP_RC
01.01.13 11:33 ARC
Enabled USER
No

Step 2

Press the left key repeatedly to display the entries


one after the other in chronological order. Once the
end of the operating data memory has been reached,
pressing the left key again will have no effect.

Oper/Rec/OP_RC
01.01.13 11:33 PSIG
Enabled USER
Yes

Step 3

Press the right key to display the previous entry.

Oper/Rec/OP_RC
01.01.13 11:33 ARC
Enabled USER
No

Step 4

Press the up key at any point within the operating


data memory to return to the entry point.

Oper/Rec/OP_RC
Operat. data record.

P437/EN M/R-11-A // P437311650

6-25

P437

6 Local Control (HMI)

6.11.6.2

Readout of the Monitoring Signal Memory


If the unit detects an internal fault in the course of internal self-monitoring
routines or if it detects power system conditions that prevent flawless functioning
of the unit, then an entry is made in the monitoring signal memory. A maximum
of 30 entries is possible. After that an overflow signal is issued.
Control Step / Description

Step 0

Select the entry point for the monitoring signal


memory.

Control
Action

Display
Oper/Rec/MT_RC
Mon. signal record.

Step 1

Press the down key to enter the monitoring signal


memory. The oldest entry is displayed.

Mon. signal record.


01.01.13 13:33 SFMON
Checksum error param

Step 2

Press the right key repeatedly to display the entries


one after the other in chronological order. If more than
30 monitoring signals have been entered since the last
reset, the overflow signal is displayed as the last
entry.

Mon. signal record.


01.01.13 10:01 SFMON
Exception oper. syst.

Step 3

Press the left key to display the previous entry.

Mon. signal record.


01.01.13 13:33 SFMON
Checksum error param

Step 4

If the down key is held down while a monitoring


signal is being displayed, the following additional
information will be displayed:

Mon. signal record.


01.01.13 13:33 SFMON
Checksum error param

First
Time when the signal first occurred

Updated

First:
13:33:59.744
Updated: Yes
Acknowledged:
No
Number:
5

The fault is still being detected (Yes) or is no


longer detected (No) by the self-monitoring
function.

Acknowledged
The fault was no longer detected by the selfmonitoring function and has been reset (Yes).

Number
The signal occurred x times.

Step 5

Press the up key at any point within the monitoring


signal memory to return to the entry point.

Oper/Rec/MT_RC
Mon. signal record.

6-26

P437/EN M/R-11-A // P437311650

P437

6 Local Control (HMI)

6.11.6.3

Readout of the Event Memories (Records)


There are eight event memories for each type of event. The latest event is stored
in event memory 1, the previous one in event memory 2, and so forth.
Readout of event memories is illustrated using the fault memory as an example.
Control Step / Description

Control
Action

Display

Step 0

Select the entry point for the first fault memory, for
example. If the memory contains entries, the third line
of the display will show the date and time the fault
began. If the third line is blank, then there are no entries
in the fault memory.

Events/Rec/FT_RC
Fault recording 1
01.01.13 10:00:33

Step 1

Press the down key to enter the fault memory. First,


the fault number is shown. In this example it is the 22nd
fault since the last reset.

Fault recording 1
FT_RC
Event
22

Step 2

Press the right key repeatedly to see first the


measured fault data and then the binary signals in
chronological order. The time shown in the second line is
the time, measured from the onset of the fault, at which
the value was measured or the binary signal started or
ended.

Fault recording 1
200 ms
FT_DA
Running time
0.17 s

Once the end of the fault has been reached (after the
right key has been pressed repeatedly), pressing the
right key again will have no effect.

Fault recording 1
0 ms
FT_RC
Record. in progress
Start

Fault recording 1
241 ms
FT_RC
Record. in progress
End

Step 3

Press the left key to see the previous measured value


or the previous signal.

Fault recording 1
0 ms
FT_RC
Record. in progress
Start

Step 4

Press the up key at any point within the fault memory


to return to the entry point.

Events/Rec/FT_RC
Fault recording 1
01.01.13 10:00:33

P437/EN M/R-11-A // P437311650

6-27

P437
6.11.7

6 Local Control (HMI)

Resetting
All information memories including the event memories and the monitoring
signal memory as well as the LED indicators can be reset manually. In addition,
the LED indicators are automatically cleared and initialized at the onset of a new
fault provided that the appropriate operating mode has been selected so that
they always indicate the latest fault.
The LED indicators can also be reset manually by pressing the CLEAR key, which
is always possible in the standard control mode. This action also triggers an LED
indicator test and an LCD display test. The event memories are not affected by
this action, so that inadvertent deletion of the records associated with the reset
signal pattern is reliably prevented.
Because of the ring structure of the event memories, the data for eight
consecutive events are updated automatically so that manual resetting should
not be necessary, in principle.
Deleting the event memories completely (e.g. after a function test), can be
accomplished by various resetting actions including the configuration of a group
resetting for several memories. An overview of all resetting actions can be found
in section Resetting Actions in Chapter Operation.
Resetting a single memory from the local control panel is described in the
following with the example of a fault memory. In this example the global changeenabling function has already been activated.
Control Step / Description

Control
Action

Display

Step 0

Select the reset setting. Line 3 of the display shows the


number of faults since the last reset, 10 in this
example.

Oper/CtrlTest/FT_RC
Reset recording
10

Step 1

Press the ENTER key. The LED indicator labeled EDIT


MODE will light up.

Oper/CtrlTest/FT_RC
Reset recording
10
Don't execute

Step 2

Press the Up or Down keys to change the setting to


Execute.

Oper/CtrlTest/FT_RC
Reset recording
10
Execute

Step 3

Press the ENTER key. The LED indicator labeled EDIT


MODE will be extinguished. The value in line 3 is reset
to 0.

Oper/CtrlTest/FT_RC
Reset recording
0

Step 4

To cancel the intended clearing of the fault recordings


after leaving the standard control mode (the LED
indicator labeled EDIT MODE is on), press the CLEAR
key. The LED indicator will be extinguished, and the
fault recordings remain stored unchanged in the
protection units memory. Any setting can be selected
again for a value change by pressing the keys.

Oper/CtrlTest/FT_RC
Reset recording
10

6-28

P437/EN M/R-11-A // P437311650

6 Local Control (HMI)

6.11.8

P437

Password-Protected Control Actions


Certain actions from the local control panel such as a manual trip command for
testing purposes can only be carried out by entering a password so as to prevent
unwanted output even though the global change-enabling function has been
activated (see section Change-Enabling Function).
This setup is designed to prevent accidental output and applies even when the
global change-enabling function has been activated. The password consists of a
pre-defined sequential key combination entered within a specific time interval. If
the password has been changed by the user (see section Changing the
Password), the following description will apply accordingly.

P437/EN M/R-11-A // P437311650

6-29

P437

6 Local Control (HMI)

Control Step / Description

Control
Action

Display

Step 0

In the menu tree Oper/CtrlTest/MAIN, select the


parameter MAI N: Man . trip cm d. USE R.

Oper/CtrlTest/MAIN
Man. trip cmd. USER
Don't execute

Step 1

Press the ENTER key. Eight asterisks (*) appear in the


fourth line of the display.

Oper/CtrlTest/MAIN
Man. trip cmd. USER
Don't execute
********

Step 2

Press the following keys in sequence:

Oper/CtrlTest/MAIN
Man. trip cmd. USER
Don't execute
*

Left

Right

Oper/CtrlTest/MAIN
Man. trip cmd. USER
Don't execute
*

Up

Oper/CtrlTest/MAIN
Man. trip cmd. USER
Don't execute
*

Down

Oper/CtrlTest/MAIN
Man. trip cmd. USER
Don't execute
*

The display will change as shown in the column on the


right.
Now press the enter key. The LED indicator labeled
EDIT MODE will light up. This indicates that the setting
can now be changed by pressing the up or down
keys.

Oper/CtrlTest/MAIN
Man. trip cmd. USER
Don't execute

Step 3

Change the setting to execute.

Oper/CtrlTest/MAIN
Man. trip cmd. USER
Execute

Step 4

Press the enter key again. The LED indicator labeled


EDIT MODE will go out. The unit will execute the
command.

Oper/CtrlTest/MAIN
Man. trip cmd. USER
Don't execute

Step 5

As long as the LED indicator labeled EDIT MODE is on,


the control action can be terminated by pressing the
CLEAR key. The LED indicator labeled EDIT MODE will
be extinguished.

Oper/CtrlTest/MAIN
Man. trip cmd. USER
Don't execute

6-30

P437/EN M/R-11-A // P437311650

P437

6 Local Control (HMI)

6.11.9

Changing the Password

6.11.9.1

Local Control Panel with Password Protection


The password consists of a combination of keys that must be entered
sequentially within a specific time interval. The left, right, up and down
keys may be used to define the password and represent the numbers 1, 2, 3 and
4, respectively:

4
The password can be changed by the user at any time. The procedure for this
change is described below. The starting point is the factory-set password.

P437/EN M/R-11-A // P437311650

6-31

P437

6 Local Control (HMI)

Control Step / Description

Control
Action

Display

Step 0

In the menu tree Par/Conf/LOC, select the


LOC: P assword setting.

Par/Conf/LOC
Password
********

Step 1

Press the ENTER key. Eight asterisks (*) appear in the


fourth line of the display.

Par/Conf/LOC
Password
********
********

Step 2

Press the left, right, up and down keys to enter


the valid password. The display will change as shown in
the column on the right.

Par/Conf/LOC
Password
********
*
Par/Conf/LOC
Password
********
*
Par/Conf/LOC
Password
********
*
Par/Conf/LOC
Password
********
*

Step 3

Now press the enter key. The LED indicator labeled


EDIT MODE will light up. The third line shows an
underscore character ( _ ) as the prompt for entering a
new password.

Par/Conf/LOC
Password
_

Step 4

Enter the new password, which in this example is done


by pressing the up key followed by the down key.

Par/Conf/LOC
Password
*
Par/Conf/LOC
Password
**

Step 5

Press the enter key again. Asterisks appear in the third


line, and a cursor (underscore) in the fourth line
prompts the user to enter the new password again.

Par/Conf/LOC
Password
**
_

Step 6

Re-enter the password.

Par/Conf/LOC
Password
**
*
Par/Conf/LOC
Password
**
**

6-32

P437/EN M/R-11-A // P437311650

P437

6 Local Control (HMI)

Control Step / Description

Control
Action

Display

Step 7a

Press the ENTER key again. If the password has been


re-entered correctly, the LED indicator labeled EDIT
MODE goes out and the display appears as shown on
the right. The new Password is now valid.

Par/Conf/LOC
Password
********

Step 7b

If the password has been re-entered incorrectly, the


LED indicator labeled EDIT MODE remains on and the
display shown on the right appears. The password has
to be re-entered. It is also possible to cancel the
change of the Password by pressing the CLEAR key (see
Step 8).

Par/Conf/LOC
Password
**
_

Step 8

The change in password can be canceled at any time


before Step 7 by pressing the CLEAR key. If this is
done, the original Password continues to be valid.

Par/Conf/LOC
Password
********

6.11.9.2

Local Control Panel without Password Protection


Operation from the local control panel without password protection is also
possible. To select this option, immediately press the ENTER key a second time in
steps 4 and 6 of Table, (p. 6-32), without entering anything else. This will
configure the local control panel without password protection, and no control
actions involving changes will be possible until the global change-enabling
function has been activated (see Change-Enabling Function, Section 6.11.3,
(p. 6-18)).

P437/EN M/R-11-A // P437311650

6-33

P437
6.11.9.3

6 Local Control (HMI)

Display the Password


If the configured password has been forgotten, it can be called up on the LCD
display as described below. The procedure involves turning the device off and
then on again.
Control Step / Description

Step 0

Turn off the device.

Step 1

Turn the device on again. At the very beginning of


device startup, press the four directional keys (left,
right, up and down) at the same time and hold
them down.

Step 2

Step 3

When this condition is detected during startup, the


password is displayed.

Control
Action

Display

TEST

Password
1234

After the four keys are released, startup will continue.


TEST

6-34

P437/EN M/R-11-A // P437311650

P437
7

Settings

7.1

Parameters
The P437 must be adjusted to the system and to the protected equipment by
appropriate settings. This chapter gives instructions for determining the settings,
which are located in the folder titled Parameters in the menu tree. The
sequence in which the settings are listed and described in this chapter
corresponds to their sequence in the menu tree.
The P437 devices are supplied with a factory-set standard configuration of
settings that, in most cases, correspond to the default settings or become
apparent after a cold restart. The P437 is blocked in that case. All settings
must be re-entered after a cold restart.

Note
Detailed information about all parameters, including complete selection tables and
IEC 608705103 protocol properties, are separately available as a set of interlinked
PDF files for user-friendly navigation, packed in one ZIP archive named
DataModelExplorer_P437_en_P01.zip.

In contrast to P437 versions before P437630, the implementation of the IEC 61850
protocol now features parameters that cannot be modified from the local control
panel (HMI) or with the operating program. Instead, these parameters are set with
a special IEC 61850 operating software, named IED Configurator.
Therefore these settings are not listed in this chapter or the following chapter.
These parameters are described in Chapter IEC 61850 Settings via IED
Configurator.

Cancelling a Protection Function


The user can adapt the device to the requirements of a particular high-voltage
system by including the relevant protection functions in the device configuration
and cancelling all others (removing them from the device configuration).
The following conditions must be met before cancelling a protection function:

The protection function in question must be disabled.

None of the functions of the protection function to be cancelled may be


assigned to a binary input.

None of the signals of the protection function may be assigned to a binary


output or an LED indicator.

No functions of the device function being cancelled can be selected in a list


setting.

None of the signals of the protection function may be linked to other signals
by way of an m out of n parameter.

The protection function to which a parameter, a signal, or a measured value


belongs is defined by the function group designation (example: LIMIT:).
General Notes on the Configuration of Function Group Binary Input (INP)
The P437 has optical coupler inputs for processing binary signals from the
system. The number and connection schemes for the available binary inputs are
shown in the terminal connection diagrams. The DataModelExplorer (available
as a separate ZIP archive file) gives information about the configuration options
for all binary inputs.

P437/EN M/R-11-A // P437311650

7-1

P437

7 Settings

The P437 identifies the installed modules during startup. If a given binary I/O
module is not installed or has fewer binary signal inputs than the maximum
number possible at this slot, then the configuration addresses for the missing
binary signal inputs are automatically hidden in the menu tree.
When configuring binary inputs, one should keep in mind that the same function
can be assigned to several signal inputs. Thus one function can be activated from
several control points having different signal voltages.
In order to ensure that the device will recognize the input signals, the triggering
signals must persist for at least 30 ms. The operating mode for each binary
signal input can be defined.
The user can specify whether the presence (active high mode) or absence
(active low mode) of a voltage shall be interpreted as the logic 1 signal.
General Notes on the Configuration of Function Group Binary Output (OUTP)
The P437 has output relays for the output of binary signals. The number and
connection schemes for the available binary output relays are shown in the
terminal connection diagrams. The DataModelExplorer (available as a separate
ZIP archive file) gives information about the configuration options for all binary
outputs.
The P437 identifies the installed modules during startup. If a given binary I/O
module is not installed or has fewer output relays than the maximum number
possible at this slot, then the configuration addresses for the missing output
relays are automatically hidden in the menu tree.
The contact data for the all-or-nothing relays permits them to be used either as
command relays or as signal relays. It is important to note that the contact rating
of the binary I/O modules (X) varies (see Chapter Technical Data). One signal
can also be assigned simultaneously to several output relays for the purpose of
contact multiplication.
An operating mode can be defined for each output relay. Depending on the
selected operating mode, the output relay will operate in either an energize-onsignal (ES) mode or a normally-energized (NE) mode and in either a latching or
non-latching mode. For output relays operating in latching mode, the operating
mode setting also determines when latching will be cancelled.
General Notes on the Configuration of the LED Indicators
The P437 has LED indicators for parallel display of binary signals. LED indicator
H 1 is not configurable. It is labeled HEALTHY and signals the operational
readiness of the protection unit (supply voltage present). LED indicators H 2 and
H 3 are not configurable either. H 2 is labeled OUT OF SERVICE and signals a
blocking or malfunction; H 3 is labeled ALARM and signals a warning alarm.
LED indicator H 17 indicates that the user is in the EDIT MODE. Section
Configuration and Operating Mode of the LED Indicators (Function Group LED)
in Chapter Operation describes the layout of the LED indicators and the factory
setting for LED indicator H 4.
An operating mode can be defined for each LED indicator. Depending on the set
operating mode, the LED indicator will operate in either energize-on-signal (ES)
mode (open-circuit principle) or normally-energized (NE) mode (closed-circuit
principle) and in either latching or non-latching mode. For LED indicators
operating in latching mode, the operating mode setting also determines when
latching will be cancelled.
With the multi-color LED indicators (H 4 H 16) the colors red and green can be
independently assigned with functions. The third color amber results as a
mixture of red and green, i.e. when both functions assigned to the LED indicator
are simultaneously present.
7-2

P437/EN M/R-11-A // P437311650

P437

7 Settings

7.1.1

Device Identification
The device identification settings are used to record the ordering information and
the design version of the P437. They have no effect on the device functions.
These settings should only be changed if the design version of the P437 is
modified.

P437/EN M/R-11-A // P437311650

7-3

P437

7 Settings

Parameter
Default

Device

Address
Min

Max

Unit

Logic Diagram

DVICE: De vice t ype


437

000 000

1000

[spacer]

The device type is displayed. This display cannot be altered.

[spacer]

DVICE: S oft ware ve rsi on


Not measured

[spacer]

655.35

DVICE: S oft ware ve rsi on 6X X


Not measured

[spacer]

0.00

002 120

010 167

65535

DVICE: S oft ware ve rsi on 7X X


Not measured

010 168

65535

[spacer]

Software version for the device. This display cannot be altered.

[spacer]

DVICE: S W date
01.01.97

[spacer]

002 122

01.01.97 07.11.98 dd.mm.yy

Date the software was created. This display cannot be altered.


Note: The centuries are not displayed. The supported dates range from January
1st, 1997, until November 7th, 2098.

[spacer]

DVICE: S W ve rsion communic.


Not measured

0.00

002 103

655.35

[spacer]

Software version for the device's communication software. This display cannot
be altered.

[spacer]

DVICE: DM I EC 618 50 ve rsion


Not measured

002 059

65535

[spacer]

Software version of the communication software based on the device's protocol


per IEC 61850. This display cannot be altered.

[spacer]

DVICE: Lang uage v ersion


0.0

0.0

002 123

899.9

[spacer]

Identification of the change level of the texts of the data model. This display
cannot be altered.

[spacer]

DVICE: Text vers .dat a mode l


0

002 121

255

[spacer]

Using the text replacement tool' provided by the operating program, the user
can change the parameter descriptors (plain text designations) and load them
into the device. These customized data models contain an identifier defined by
the user while preparing the data model. This identifier is displayed at this point
in the menu tree. Standard data models have the identifier 0' (factory-set
default).

[spacer]

DVICE: F numb er
0

[spacer]

7-4

002 124

9999

The F number is the serial number of the device. The display cannot be altered.
P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

DVICE: AFS Orde r No.

Logic Diagram
001 000

0:
[spacer]

DVICE: PCS Or de r No.

001 200

0:
[spacer]

Order numbers for the device. The user cannot alter this number.

[spacer]

DVICE: Order ext . No. 1


0

[spacer]

000 010

999

000 011

999

000 012

999

000 013

999

000 014

999

000 015

999

000 016

999

DVICE: Order ext . No. 15


0

[spacer]

999

DVICE: Order ext . No. 14


0

[spacer]

000 009

DVICE: Order ext . No. 13


0

[spacer]

999

DVICE: Order ext . No. 12


0

[spacer]

000 008

DVICE: Order ext . No. 11


0

[spacer]

999

DVICE: Order ext . No. 10


0

[spacer]

000 007

DVICE: Order ext . No. 9


0

[spacer]

999

DVICE: Order ext . No. 8


0

[spacer]

000 006

DVICE: Order ext . No. 7


0

[spacer]

999

DVICE: Order ext . No. 6


0

[spacer]

000 005

DVICE: Order ext . No. 5


0

[spacer]

999

DVICE: Order ext . No. 4


0

[spacer]

000 004

DVICE: Order ext . No. 3


0

[spacer]

999

DVICE: Order ext . No. 2


0

[spacer]

000 003

000 017

999

DVICE: Order ext . No. 16


0

P437/EN M/R-11-A // P437311650

000 018

999

7-5

P437

7 Settings

Parameter
Default
[spacer]

999

000 023

999

000 024

999

000 025

999

000 026

999

000 027

999

DVICE: Order ext . No. 26


0

[spacer]

000 022

DVICE: Order ext . No. 25


0

[spacer]

999

DVICE: Order ext . No. 24


0

[spacer]

000 021

DVICE: Order ext . No. 23


0

[spacer]

999

DVICE: Order ext . No. 22


0

[spacer]

000 020

DVICE: Order ext . No. 21


0

[spacer]

000 028

999

DVICE: Order ext . No. 27


0

Logic Diagram

999

DVICE: Order ext . No. 20


0

[spacer]

Unit

000 019

DVICE: Order ext . No. 19


0

[spacer]

Max

DVICE: Order ext . No. 18


0

[spacer]

Min

DVICE: Order ext . No. 17


0

[spacer]

Address

000 029

999

[spacer]

Order extension numbers for the device.

[spacer]

DVICE: M odule var. slot 1

086 050

1: Module P: 0336411
[spacer]

DVICE: M odule var. slot 2

086 051

65535: Not fitted


[spacer]

DVICE: M odule var. slot 3

086 052

65535: Not fitted


[spacer]

DVICE: M odule var. slot 4

086 053

65535: Not fitted


[spacer]

DVICE: M odule var. slot 5

086 054

65535: Not fitted


[spacer]

DVICE: M odule var. slot 6

086 055

65535: Not fitted


[spacer]

DVICE: M odule var. slot 7

086 056

65535: Not fitted

7-6

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

DVICE: M odule v ar. slot 8

Logic Diagram
086 057

65535: Not fitted


[spacer]

DVICE: M odule v ar. slot 9

086 058

65535: Not fitted


[spacer]

DVICE: M odule v ar. slot 1 0

086 059

65535: Not fitted


[spacer]

DVICE: M odule v ar. slot 1 2

086 061

65535: Not fitted


[spacer]

DVICE: M odule v ar. slot 1 3

086 062

65535: Not fitted


[spacer]

DVICE: M odule v ar. slot 1 4

086 063

65535: Not fitted


[spacer]

DVICE: M odule v ar. slot 1 5

086 064

65535: Not fitted


[spacer]

DVICE: M odule v ar. slot 1 6

086 065

65535: Not fitted


[spacer]

DVICE: M odule v ar. slot 1 7

086 066

65535: Not fitted


[spacer]

DVICE: M odule v ar. slot 1 8

086 067

65535: Not fitted


[spacer]

DVICE: M odule v ar. slot 1 9

086 068

65535: Not fitted


[spacer]

DVICE: M odule v ar. slot 2 0

086 069

65535: Not fitted


[spacer]

Item number of the module inserted in the respective slot 1 to 21.


The display always shows the actual component configuration at any given time.

[spacer]

DVICE: M odule v ers . slot 1

086 193

27: Not fitted


[spacer]

DVICE: M odule v ers . slot 2

086 194

27: Not fitted


[spacer]

DVICE: M odule v ers . slot 3

086 195

27: Not fitted


[spacer]

DVICE: M odule v ers . slot 4

086 196

27: Not fitted


[spacer]

DVICE: M odule v ers . slot 5

086 197

27: Not fitted


[spacer]

DVICE: M odule v ers . slot 6

086 198

27: Not fitted

P437/EN M/R-11-A // P437311650

7-7

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

DVICE: M odule vers . slot 7

Logic Diagram
086 199

27: Not fitted


[spacer]

DVICE: M odule vers . slot 8

086 200

27: Not fitted


[spacer]

DVICE: M odule vers . slot 9

086 201

27: Not fitted


[spacer]

DVICE: M odule vers . slot 1 0

086 202

27: Not fitted


[spacer]

DVICE: M odule vers . slot 1 2

086 204

27: Not fitted


[spacer]

DVICE: M odule vers . slot 1 3

086 205

27: Not fitted


[spacer]

DVICE: M odule vers . slot 1 4

086 206

27: Not fitted


[spacer]

DVICE: M odule vers . slot 1 5

086 207

27: Not fitted


[spacer]

DVICE: M odule vers . slot 1 6

086 208

27: Not fitted


[spacer]

DVICE: M odule vers . slot 1 7

086 209

27: Not fitted


[spacer]

DVICE: M odule vers . slot 1 8

086 210

27: Not fitted


[spacer]

DVICE: M odule vers . slot 2 0

086 212

27: Not fitted


[spacer]

Index letter specifying the version of the module fitted in the respective slot.

[spacer]

DVICE: Variant of module A

086 047

65535: Not fitted


[spacer]

Item number of module A in this design version.

[spacer]

DVICE: Vers ion of module A

086 190

27: Not fitted


[spacer]

Index letter specifying the version of module A.

[spacer]

DVICE: M AC add ress module A

104 061

2:
[spacer]

7-8

MAC address for the network hardware of the Ethernet module. This address is
introduced during manufacture and can only be read.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

DVICE: Variant of module L

Logic Diagram
086 048

65535: Not fitted


[spacer]

Item number of module L in this design version.

[spacer]

DVICE: Vers ion of module L

086 191

27: Not fitted


[spacer]

Index letter specifying the version of module L.

[spacer]

DVICE: Variant of module B

086 049

65535: Not fitted


[spacer]

Item number of module B in this design version.

[spacer]

DVICE: Vers ion of module B

086 192

27: Not fitted


[spacer]

Index letter specifying the version of the digital bus module B.

[spacer]

DVICE: Variant module B (a)

086 046

65535: Not fitted


[spacer]

Item number of the analog bus module B in this design version.

[spacer]

DVICE: Vers ion modul e B (a)

086 189

27: Not fitted


[spacer]

Index letter specifying the version of the digital bus module B.

[spacer]

DVICE: IP addres s

111 000

2:
[spacer]

DVICE: S ubnet mas k

111 001

2:
[spacer]

DVICE: M AC address

111 003

2:
[spacer]

Display of the IP address (or subnet mask, MAC address, respectively) of the
Ethernet interface of the processor module. This can be useful for network
analysis, especially if these settings have been retrieved via DHCP.

[spacer]

DVICE: Cust omer ID data 1


0.00

[spacer]

0.00

000 041

99.99

DVICE: Cust omer ID data 3


0.00

[spacer]

99.99

DVICE: Cust omer ID data 2


0.00

[spacer]

0.00

000 040

0.00

000 042

99.99

DVICE: Cust omer ID data 4


0.00

P437/EN M/R-11-A // P437311650

0.00

000 043

99.99

7-9

P437

7 Settings

Parameter
Default
[spacer]

Unit

Logic Diagram

0.00

000 044

99.99

0.00

000 045

99.99

DVICE: Cust omer ID data 7


0.00

[spacer]

Max

DVICE: Cust omer ID data 6


0.00

[spacer]

Min

DVICE: Cust omer ID data 5


0.00

[spacer]

Address

0.00

000 046

99.99

DVICE: Cust omer ID data 8


0.00

0.00

000 047

99.99

[spacer]

Set your numerically coded user data here for your records.

[spacer]

DVICE: Location

001 201

0:
[spacer]

Reference input for the device's location as selected by user.

[spacer]

DVICE: De vice I D
0

000 035

9999

[spacer]

ID code for use by the PC programs for operating and setting. Further
instructions on this setting are given in the description of the respective
operating program.

[spacer]

DVICE: S ubst ation ID


0

000 036

9999

[spacer]

ID code for use by the PC programs for operating and setting. Further
instructions on this setting are given in the description of the respective
operating program.

[spacer]

DVICE: Fee de r ID
0

000 037

9999

[spacer]

ID code for use by the PC programs for operating and setting. Further
instructions on this setting are given in the description of the respective
operating program.

[spacer]

DVICE: De vice p assword 1


0

[spacer]

000 048

9999

DVICE: De vice p assword 2


0

000 049

9999

[spacer]

ID code used by the operating program for identification purposes. See


description of the respective operating program for more detailed setting
instructions.

[spacer]

DVICE: S W ve rsion DHMI


Not measured

7-10

0.00

002 131

655.35

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Min

Max

Unit

0.00

002 132

655.35

Internal software version numbers.


Parameter
Default

Local control panel

Logic Diagram

DVICE: S W ve rsion DHMI DM


1.10

[spacer]

Address

Address
Min

Max

Unit

Logic Diagram

LOC: Local HM I ex is ts

221 099

1: Yes
[spacer]

When set to Yes it is apparent that the device is fitted with the local control
panel (HMI).

P437/EN M/R-11-A // P437311650

7-11

P437
7.1.2

7 Settings

Configuration Parameters
Parameter
Default

Local control panel

Address
Min

Max

Unit

Logic Diagram

LOC: Languag e

003 020

2: Reference language
[spacer]

Language in which texts will be displayed on the user interface (HMI).

[spacer]

LOC: De cim al delimit er

003 021

1: Dot
[spacer]

Character to be used as decimal delimiter on the local control panel.

[spacer]

LOC: Pas s word


1234

003 035

4444

[spacer]

The password to be used for changing settings from the local control panel can
be defined here.

[spacer]

LOC: Ass ig nment r es et ke y


060 000: MAIN: Without function

005 251

Fig. 3-76, (p. 3-107)

[spacer]

Selection of counters and memories that are reset by pressing the RESET key on
the local control panel. (Resetting LED indicators and measured event values is
permanently assigned internally, so that they are always reset when the RESET
key is pressed.)

[spacer]

LOC: Ass ig nment r ead k e y

080 110

060 000: MAIN: Without function


[spacer]

Selection of up to 16 functions to be triggered when pressing the read key.


Event counters and event recordings are offered for selection. If several
functions have been selected then they will be sequentially triggered by
repeated pressing of the read key.

[spacer]

LOC: Fct. m enu jmp li st 1

030 238

060 000: MAIN: Without function


[spacer]

LOC: Fct. m enu jmp li st 2

030 239

060 000: MAIN: Without function


[spacer]

Selection of specified functions which will be sequentially displayed by repeated


reading of the menu jump list 1 (or 2).

[spacer]

LOC: Fct. Operation P anel


060 000: MAIN: Without function

053 007

Fig. 3-2, (p. 3-5)

[spacer]

Definition of the values to be displayed on the Measured Value Panel also


referred to as the Operation Panel.

[spacer]

LOC: Fct. Ove r load Pane l


060 000: MAIN: Without function

[spacer]

7-12

053 005

Fig. 3-4, (p. 3-7)

Definition of the values to be displayed on the Overload Panel.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

LOC: Fct. Fault Panel

053 003

060 000: MAIN: Without function

Fig. 3-3, (p. 3-6)

[spacer]

Definition of the values to be displayed on the Fault Panel.

[spacer]

LOC: Hold- tim e for P anels


5

031 075

10

Fig. 3-2, (p. 3-5)

[spacer]

Setting for the time period during which a panel is displayed, before switching to
the next panel. This setting is only relevant if more values are selected than can
be shown on the LC-Display.

[spacer]

LOC: Autom . re t ur n t ime


60

60

003 014

60000

Fig. 3-2, (p. 3-5)

[spacer]

If the user does not press a key on the local control panel during this set time
period, the change-enabling function is deactivated.

[spacer]

LOC: Re t ur n time illumi n.


60

[spacer]

60

003 023

60000

If the user does not press a key on the local control panel during this set time
period, then the backlighting of the LCD display is switched off.

P437/EN M/R-11-A // P437311650

7-13

P437

7 Settings

Parameter
Default

PC link

Min

Max

Unit

Logic Diagram

PC: Bay addre ss


1

[spacer]

Address

003 068

254

Fig. 3-5, (p. 3-9)

PC: De vice addr ess


1

003 069

255

Fig. 3-5, (p. 3-9)

[spacer]

Bay and device addresses are used to address the device in communication via
the PC interface. An identical setting must be selected for both addresses.

[spacer]

PC: Baud rate

003 081

115.2: 115.2 kBaud

Baud

[spacer]

Baud rate of the PC interface.

[spacer]

PC: Parit y bit

Fig. 3-5, (p. 3-9)

003 181

1: Even

Fig. 3-5, (p. 3-9)

[spacer]

Set the same parity that is set at the interface of the PC connected to the P437.

[spacer]

PC: Spontan. sig. e nable

003 187

0: None

Fig. 3-5, (p. 3-9)

[spacer]

Enable for the transmission of spontaneous signals via the PC interface.

[spacer]

PC: Select. s pontan. si g.

003 189

060 000: MAIN: Without function

Fig. 3-5, (p. 3-9)

[spacer]

Selection of spontaneous signals for transmission via the PC interface.

[spacer]

PC: Trans m.enab.cyc l. dat

003 084

0: Without

Fig. 3-5, (p. 3-9)

[spacer]

Enable for the cyclic transmission of measured values via the PC interface.

[spacer]

PC: Cycl. d ata ILS t e l.

003 185

060 000: MAIN: Without function

Fig. 3-5, (p. 3-9)

[spacer]

Selection of the measured values that are transmitted in a user-defined


telegram via the PC interface.

[spacer]

PC: De lta V
3.0

003 055

0.0

15.0

%Vnom

Fig. 3-5, (p. 3-9)

[spacer]

A measured voltage value is transmitted via the PC interface if it differs by the


set delta quantity from the last measured value transmitted.

[spacer]

PC: De lta I
3.0

003 056

0.0

15.0

%Inom

Fig. 3-5, (p. 3-9)

[spacer]

A measured current value is transmitted via the PC interface if it differs by the


set delta quantity from the last measured value transmitted.

[spacer]

PC: IP addr es s
192

7-14

111 004

255

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Unit

Logic Diagram

255

PC: IP addr es s 2

111 006

255

PC: IP addr es s 3
2

[spacer]

Max

111 005

1
[spacer]

Min

PC: IP addr es s 1
168

[spacer]

Address

111 007

255

IP address of the Ethernet interface of the P437's processor module.


This is the Ethernet interface of the processor module and can be used for
special service activities, e.g. for uploading new firmware.
Note: In the operating program, the complete IP address is displayed at PC: IP
addr es s. The devices front panel display only displays the IP address
distributed to these four data model addresses:

PC : IP add re ss,

PC: IP addr e ss 1,

PC: IP ad dres s 2,

PC: I P ad dres s 3.

Note: This interface can only be used if it has been configured (PC: IP
addr es s, PC: Subnet mas k, PC : IP addre ss mode) and activated via
PC: IP Enable co nf ig..
[spacer]

PC: Subnet mas k


255

[spacer]

255

PC: Subnet mas k 2

111 010

255

PC: Subnet mas k 3


0

[spacer]

111 009

255
[spacer]

255

PC: Subnet mas k 1


255

[spacer]

111 008

111 011

255

Subnet mask of the Ethernet interface of the processor module.


Note: In the operating program, the complete mask is displayed at
PC: Subnet mas k. The devices front panel display only displays the mask
distributed to these four data model addresses:

PC: Subnet mask,

PC: Sub net mas k 1,

PC: S ubnet mask 2,

PC: S ubne t mask 3.

P437/EN M/R-11-A // P437311650

7-15

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

PC: IP addr es s mode

111 016

1: DHCP
[spacer]

[spacer]

Setting of the method how the IP address of the Ethernet interface of the
processor module shall be defined.

DHCP: The IP address shall be retrieved from a DHCP server.

Fix: The setting of P C: IP addre ss shall be used.

Device address: The setting of PC : IP addr ess shall be used for the
first three number values of the IP address, the fourth number value of the
IP address shall be the value of PC : De v ic e addr ess.

PC: IP Enable conf ig.

111 017

0: don't execute
[spacer]

Activating the Ethernet interface of the processor module.

[spacer]

PC: De lta P
15.0

003 059

0.0

15.0

%Snom

Fig. 3-5, (p. 3-9)

[spacer]

The active power value is transmitted via the PC interface if it differs by the set
delta quantity from the last measured value transmitted.

[spacer]

PC: De lta f
2.0

003 057

0.0

2.0

%fnom

Fig. 3-5, (p. 3-9)

[spacer]

The measured frequency value is transmitted via the PC interface if it differs by


the set delta from the last measured value transmitted.

[spacer]

PC: De lta meas.v.ILS te l


3.0

0.0

003 155

15.0

Fig. 3-5, (p. 3-9)

[spacer]

The telegram is transmitted if a measured value differs by the set delta quantity
from the last measured value transmitted.

[spacer]

PC: De lta t
1

003 058

15

min

Fig. 3-5, (p. 3-9)

[spacer]

All measured values are transmitted again via the PC interface after this time
period has elapsed provided that transmission has not been triggered by the
other delta conditions.

[spacer]

PC: Time-out
1

[spacer]

7-16

003 188

60

min

Fig. 3-5, (p. 3-9)

Setting for the time to elapse after the last telegram exchange via the PC
interface before activating the second communication channel of
communication module A.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default

Logical
communication
interface 1

Address
Min

Max

Unit

Logic Diagram

COMM 1: Functio n gr oup CO MM1

056 026

0: Without
[spacer]

Cancelling function group COMM1 or including it in the configuration. If the


function group is cancelled from the configuration, then all associated settings
and signals are hidden, with the exception of this setting.

[spacer]

COMM 1: General enabl e USE R

003 170

0: No
[spacer]

Disabling or enabling communication interface 1.

[spacer]

COMM 1: Basic IE C87 0-5 e nabl


0: No

003 215

Fig. 3-6, (p. 3-11)

[spacer]

Common settings for enabling all protocols based on IEC 870-5-xxx.

[spacer]

COMM 1: Addit . - 10 1 e nable


0: No

003 216

Fig. 3-6, (p. 3-11)

[spacer]

Enabling additional settings that are relevant for the protocol based on
IEC 870-5-101.

[spacer]

COMM 1: Addit . I LS e nable


0: No

003 217

Fig. 3-6, (p. 3-11)

[spacer]

Enabling additional settings that are relevant for the ILS protocol.

[spacer]

COMM 1: MODB US e nable


0: No

[spacer]

Enabling settings relevant for the MODBUS protocol.

[spacer]

COMM 1: DNP3 enable


0: No

[spacer]

Enabling settings relevant for the DNP 3.0 protocol.

[spacer]

COMM 1: COUR IER e nable


0: No

[spacer]

Enabling settings relevant for the COURIER protocol.

[spacer]

COMM 1: Com m unicat. prot ocol


060 000: MAIN: Without function

[spacer]

003 220

Fig. 3-6, (p. 3-11)

003 231

Fig. 3-6, (p. 3-11)

103 040

Fig. 3-6, (p. 3-11)

003 167

Fig. 3-6, (p. 3-11)

Select the communication protocol that shall be used for the communication
interface.

P437/EN M/R-11-A // P437311650

7-17

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

COMM 1: -103 pr ot. var iant

003 178

1: Private
[spacer]

Logic Diagram

Fig. 3-7, (p. 3-12)

The user may select between two variants of the 103 protocol.
Note: This setting is hidden unless the IEC 870-5-xxx protocol is enabled.

[spacer]

COMM 1: MODB US prot . variant

003 214

1: Compatible
[spacer]

Fig. 3-10, (p. 3-15)

The user may select between two variants of the MODBUS protocol.
Note: This setting is hidden unless the MODBUS protocol is enabled.

[spacer]

COMM 1: Line idle stat e

003 165

1: Light on / high

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)
Fig. 3-10, (p. 3-15)
Fig. 3-11, (p. 3-16)
Fig. 3-12, (p. 3-17)

[spacer]

Setting for the line idle state indication.

[spacer]

COMM 1: Baud rate


19.2: 19.2 kBaud

003 071

Baud

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)
Fig. 3-10, (p. 3-15)
Fig. 3-11, (p. 3-16)
Fig. 3-12, (p. 3-17)

[spacer]

Baud rate of the communication interface.

[spacer]

COMM 1: Parity bit


2: Even

003 171

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)
Fig. 3-10, (p. 3-15)
Fig. 3-11, (p. 3-16)
Fig. 3-12, (p. 3-17)

[spacer]

7-18

Set the same parity that is set at the interface of the control system connected
to the P437.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

COMM 1: Dead t ime moni toring

003 176

1: Yes

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)
Fig. 3-10, (p. 3-15)
Fig. 3-11, (p. 3-16)
Fig. 3-12, (p. 3-17)

[spacer]

The P437 monitors telegram transmission to make sure that no excessive pause
occurs within a telegram. This monitoring function can be disabled if it is not
required.
Note: This setting is only necessary for modem transmission.

[spacer]

COMM 1: Mon. time pol ling


25

003 202

254

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)
Fig. 3-10, (p. 3-15)
Fig. 3-11, (p. 3-16)
Fig. 3-12, (p. 3-17)

[spacer]

The time between two polling calls from the communication master must be less
than the time set here.

[spacer]

COMM 1: Octet comm. addre ss


1

254

003 072

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)
Fig. 3-10, (p. 3-15)
Fig. 3-11, (p. 3-16)
Fig. 3-12, (p. 3-17)

[spacer]

The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be selected
for both addresses.
ASDU: Application Service Data Unit

[spacer]

COMM 1: Oct.2 comm.addr.DNP 3


0

[spacer]

255

003 240

Fig. 3-11, (p. 3-16)

In the DNP 3.0 protocol, a 16-bit address is used to identify devices.


The address that can be set here is the higher-order octet, whereas the address
set at COM M1: Octe t comm. addr ess is the lower-order octet of the
DNP address.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.

P437/EN M/R-11-A // P437311650

7-19

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

COMM 1: Pos. acknowle dge me nt

103 060

1: Single character E5
[spacer]

[spacer]

The following transmission frame formats are available (according to the


standard):

Short message FT 1.2: short message with a fixed block length of 5


characters

Single character E5: single control character

COMM 1: Tes t m onit or on

003 166

0: No

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)
Fig. 3-10, (p. 3-15)
Fig. 3-11, (p. 3-16)
Fig. 3-12, (p. 3-17)

[spacer]

Setting specifying whether data shall be recorded for service activities.

[spacer]

COMM 1: Name of manufac ture r


1: SE

003 161

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)

[spacer]

Setting for the name of the manufacturer.


Note:

[spacer]

This setting can be changed to ensure compatibility.

This setting is hidden unless an IEC 870-5 protocol is enabled.

COMM 1: Octet address ASD U


1

255

003 073

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)

[spacer]

The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be selected
for both addresses.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.
ASDU: Application Service Data Unit

[spacer]

COMM 1: Spontan. s ig. enabl e


65535: All

003 177

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)

[spacer]

Enable for the transmission of spontaneous signals via the communication


interface.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.

7-20

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

COMM 1: Se le ct. s pont an.sig.

003 179

060 000: MAIN: Without function

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)

[spacer]

Selection of spontaneous signals for transmission via logical communication


interface 1.

[spacer]

COMM 1: Transm.enab.c ycl.dat

003 074

0: Without

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)

[spacer]

Enabling of cyclic transmission of measured values via the communication


interface.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.

[spacer]

COMM 1: Cycl. dat a ILS t e l.

003 175

060 000: MAIN: Without function

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)

[spacer]

Selection of the measured values that are transmitted in a user-defined


telegram via the communication interface.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.

[spacer]

COMM 1: Delta V
3.0

003 050

0.0

15.0

%Vnom

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)

[spacer]

A measured voltage value is transmitted via the communication interface if it


differs by the set delta quantity from the last measured value transmitted.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.

[spacer]

COMM 1: Delta I
3.0

003 051

0.0

15.0

%Inom

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)

[spacer]

A measured current value is transmitted via the communication interface if it


differs by the set delta quantity from the last measured value transmitted.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.

[spacer]

COMM 1: Delta P
15.0

003 054

0.0

15.0

%Snom

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)

[spacer]

The active power value is transmitted via the communication interface if it


differs by the set delta quantity from the last measured value transmitted.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.

P437/EN M/R-11-A // P437311650

7-21

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

COMM 1: Delta f
2.0

003 052

0.0

2.0

%fnom

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)

[spacer]

The measured frequency value is transmitted via the communication interface if


it differs by the set delta quantity from the last measured value transmitted.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.

[spacer]

COMM 1: Delta m e as. v.ILS t el


3.0

0.0

003 150

15.0

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)

[spacer]

The telegram is transmitted if a measured value differs by the set delta quantity
from the last measured value transmitted.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.

[spacer]

COMM 1: Delta t
1

003 053

15

min

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)

[spacer]

All measured values are transmitted again via the communication interface after
this time period has elapsed provided that transmission has not been triggered
by the other delta conditions.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.

[spacer]

COMM 1: Delta t (e ne r gy)


Blocked

003 151

15

min

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)

[spacer]

The measured values for active energy and reactive energy are transmitted via
the communication interface after this time has elapsed.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.

[spacer]

COMM 1: Cont in. ge ner al scan


Blocked

10

9000

003 077

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)

[spacer]

A continuous or background general scan means that the P437 transmits all
settings, signals, and monitoring signals through the communication interface
during slow periods when there is not much activity. This ensures that there will
be data consistency with a connected control system. The time to be set defines
the minimum time difference between two telegrams.
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.

7-22

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Min

Max

Unit

Logic Diagram

COMM 1: Com m . addr ess le ngth


1

[spacer]

Address

003 201

Byte

Fig. 3-8, (p. 3-13)

Setting for the communication address length.


Note: This setting is hidden unless the IEC 870-5-101 protocol is set.

[spacer]

COMM 1: Octet 2 comm. addr.


0

[spacer]

003 200

255

Fig. 3-8, (p. 3-13)

Setting for the length of the higher-order communication address.


Note: This setting is hidden unless the IEC 870-5-101 protocol is set.

[spacer]

COMM 1: Caus e transm. le ngth

003 192

1: W/o source address


[spacer]

Fig. 3-8, (p. 3-13)

Setting for the length of the cause of transmission.


Note: This setting is hidden unless the IEC 870-5-101 protocol is set.

[spacer]

COMM 1: Address le ngt h AS DU


1

[spacer]

003 193

Byte

Fig. 3-8, (p. 3-13)

Setting for the length of the common address for identification of telegram
structures.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.
ASDU: Application Service Data Unit

[spacer]

COMM 1: Octet 2 addr. ASD U


0

[spacer]

003 194

255

Fig. 3-8, (p. 3-13)

Setting for the length of the common higher-order address for identification of
telegram structures.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.
ASDU: Application Service Data Unit

[spacer]

COMM 1: Addr.le ngth inf. obj.


2

[spacer]

003 196

Byte

Fig. 3-8, (p. 3-13)

Setting for the length of the address for information objects.


Note: This setting is hidden unless the IEC 870-5-101 protocol is set.

[spacer]

COMM 1: Oct.3 addr. inf.obj.


0

[spacer]

255

003 197

Fig. 3-8, (p. 3-13)

Setting for the length of the higher-order address for information objects.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.

[spacer]

COMM 1: Inf .No.<- >funct.t ype


0: No

[spacer]

003 195

Fig. 3-8, (p. 3-13)

Setting specifying whether information numbers and function type shall be


reversed in the object address.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.

P437/EN M/R-11-A // P437311650

7-23

P437

7 Settings

Parameter
Default
[spacer]

Min

Max

Unit

Logic Diagram

COMM 1: Tim e tag length


3

[spacer]

Address

003 198

Byte

Fig. 3-8, (p. 3-13)

Setting for the time tag length.


Note: This setting is hidden unless the IEC 870-5-101 protocol is set.

[spacer]

COMM 1: AS DU1 / ASDU20 conv .

003 190

1: Single signal
[spacer]

Fig. 3-8, (p. 3-13)

Setting specifying whether telegram structure 1 or 20 shall be converted as a


single signal or double signal.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.
ASDU: Application Service Data Unit

[spacer]

COMM 1: AS DU2 co nver si on

003 191

1: Single signal
[spacer]

Fig. 3-8, (p. 3-13)

Setting specifying whether telegram structure 2 shall be converted as a single


signal or double signal.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.
ASDU: Application Service Data Unit

[spacer]

COMM 1: Init ializ. signal

003 199

1: Yes
[spacer]

Fig. 3-8, (p. 3-13)

Setting specifying whether an initialization signal shall be issued.


Note: This setting is hidden unless the IEC 870-5-101 protocol is set.

[spacer]

COMM 1: Balance d ope ration

003 226

0: No
[spacer]

Fig. 3-8, (p. 3-13)

Setting that determines whether communication takes place on a balanced basis


(full duplex operation).
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.

[spacer]

COMM 1: Direction bit


0

[spacer]

003 227

Fig. 3-8, (p. 3-13)

Setting for the transmission direction. Normally this value will be set to '1' at
the control center and to '0' at the substation.
Note: This setting is hidden unless the IEC 870-5-101 protocol is enabled.

[spacer]

COMM 1: Tim e- out int erv al


0.40

[spacer]

0.10

003 228

2.55

Fig. 3-8, (p. 3-13)

Setting for the maximum time that will elapse until the status signal for the
acknowledgment command is issued.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.

7-24

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

COMM 1: Reg.asg. sel ec. cmds

003 210

060 000: MAIN: Without function


[spacer]

Logic Diagram

Fig. 3-10, (p. 3-15)

MODBUS registers in the range 00301 to 00400 are assigned to the selected
commands. Assignment is made in the order of selection. This means that the
first command is given the register no. 00301, the second the register no.
00302, etc.
Note: This setting is hidden unless the MODBUS protocol is enabled.

[spacer]

COMM 1: Reg.asg. sel ec. si g.

003 211

060 000: MAIN: Without function


[spacer]

Fig. 3-10, (p. 3-15)

MODBUS registers in the range 10301 to 10400 are assigned to the selected
signals. Assignment is made in the order of selection. This means that the first
signal is given the register no. 10301, the second the register no. 10302, etc.
Note: This setting is hidden unless the MODBUS protocol is enabled.

[spacer]

COMM 1: Reg.asg. sel . m. val.

003 212

060 000: MAIN: Without function


[spacer]

Fig. 3-10, (p. 3-15)

MODBUS registers in the range 30301 to 30400 are assigned to the selected
measured values. Assignment is made in the order of selection. This means that
the first measured value is given the register no. 30301, the second the register
no. 30302, etc.
Note: This setting is hidden unless the MODBUS protocol is enabled.

[spacer]

COMM 1: Reg.asg. sel . par am.

003 213

060 000: MAIN: Without function


[spacer]

Fig. 3-10, (p. 3-15)

MODBUS registers in the range 40301 to 40400 are assigned to the selected
parameters. Assignment is made in the order of selection. This means that the
first parameter is given the register no. 40301, the second the register no.
40302, etc.
Note: This setting is hidden unless the MODBUS protocol is enabled.

[spacer]

COMM 1: Delta t ( MO DBUS)


5

[spacer]

003 152

120

Fig. 3-10, (p. 3-15)

All MODBUS registers are transmitted again through the communication


interface after this time has elapsed.
Note: This setting is hidden unless the MODBUS protocol is enabled.

[spacer]

COMM 1: Autom .eve nt c onfirm.


0: Without

[spacer]

003 249

Fig. 3-10, (p. 3-15)

Setting specifying whether an event must be confirmed by the master in order


for an event to be deleted from the 'event queue'.
Note: This setting is hidden unless the MODBUS protocol is enabled.

P437/EN M/R-11-A // P437311650

7-25

P437

7 Settings

Parameter
Default
[spacer]

Min

Max

Unit

Logic Diagram

COMM 1: Phys . Char act . De lay


0

[spacer]

Address

254

003 241

Bit

Fig. 3-11, (p. 3-16)

Number of bits that must pass between the receipt of the 'request' and the start
of sending the 'response'.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.

[spacer]

COMM 1: Phys . Char . Time out


40

[spacer]

254

003 242

Bit

Fig. 3-11, (p. 3-16)

Number of bits that may be missing from the telegram before receipt is
terminated.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.

[spacer]

COMM 1: Link Confirm. M ode

003 243

1: Multi-frame fragment
[spacer]

Fig. 3-11, (p. 3-16)

Setting for the acknowledgment mode of the link layer.


Note: This setting is hidden unless the DNP 3.0 protocol is enabled.

[spacer]

COMM 1: Link Confirm.Timeout


0.10

[spacer]

0.05

2.54

003 244

Fig. 3-11, (p. 3-16)

Setting for the time period within which the master must acknowledge at the
link layer.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.

[spacer]

COMM 1: Link Max. Re tr ie s


2

[spacer]

003 245

10

Fig. 3-11, (p. 3-16)

Number of repetitions that are carried out on the link layer if errors have
occurred during transmission (such as failure to acknowledge).
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.

[spacer]

COMM 1: Appl.Con firm.T ime out


5.0

[spacer]

0.5

25.4

003 246

Fig. 3-11, (p. 3-16)

Setting for the time period within which the master must acknowledge at the
application layer.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.

[spacer]

COMM 1: Appl. Ne ed Time De l.


60

[spacer]

254

003 247

Fig. 3-11, (p. 3-16)

Time interval within which the slave requests time synchronization cyclically
from the master.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.

7-26

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

COMM 1: Ind ./cl. bin. input s

003 232

060 000: MAIN: Without function


[spacer]

Logic Diagram

Fig. 3-11, (p. 3-16)

Selection of data points and data classes for object 1 binary inputs.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.

[spacer]

COMM 1: Ind ./cl. bin.output s

003 233

060 000: MAIN: Without function


[spacer]

Fig. 3-11, (p. 3-16)

Selection of data points and data classes for object 10 binary outputs.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.

[spacer]

COMM 1: Ind ./cl. bin. count .

003 234

060 000: MAIN: Without function


[spacer]

Fig. 3-11, (p. 3-16)

Selection of data points and data classes for object 20 binary counters.
Assignment of indexes is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.

[spacer]

COMM 1: Ind ./cl. analog inp.

003 235

060 000: MAIN: Without function


[spacer]

Fig. 3-11, (p. 3-16)

Selection of data points and data classes for object 30 analog inputs.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.

[spacer]

COMM 1: Ind ./cl. analog outp

003 236

060 000: MAIN: Without function


[spacer]

Fig. 3-11, (p. 3-16)

Selection of data points and data classes for object 40 analog outputs.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.

[spacer]

COMM 1: Delta me as. v. ( DNP 3 )


16

[spacer]

003 250

255

Fig. 3-11, (p. 3-16)

Initialization value of threshold values for transmission of measured values in


object 30. The threshold values can be changed separately by the master for
each measured value by writing to object 34, 'analog input reporting deadband'.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.

[spacer]

COMM 1: Delta t ( DNP 3)


5

[spacer]

003 248

120

Fig. 3-11, (p. 3-16)

Cycle time for updating DNP object 30 (analog inputs).


Note: This setting is hidden unless the DNP 3.0 protocol is enabled.

P437/EN M/R-11-A // P437311650

7-27

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

COMM 1: Com m and sel ect ion

103 042

060 000: MAIN: Without function


[spacer]

Logic Diagram

Fig. 3-12, (p. 3-17)

Selection of commands to be issued via the COURIER protocol.


Note: This setting is hidden unless the COURIER protocol is enabled.

[spacer]

COMM 1: Signal s elec tion

103 043

060 000: MAIN: Without function


[spacer]

Fig. 3-12, (p. 3-17)

Selection of signals to be transmitted via the COURIER protocol.


Note: This setting is hidden unless the COURIER protocol is enabled.

[spacer]

COMM 1: Meas . val. sel ect ion

103 044

060 000: MAIN: Without function


[spacer]

Fig. 3-12, (p. 3-17)

Selection of measured values to be transmitted via the Courier protocol.


Note: This setting is hidden unless the Courier protocol is enabled.

[spacer]

COMM 1: Param et er s ele ct ion

103 045

060 000: MAIN: Without function


[spacer]

Fig. 3-12, (p. 3-17)

Selection of settings to be altered via the Courier protocol.


Note: This setting is hidden unless the Courier protocol is enabled.

[spacer]

COMM 1: Delta t (COURIE R)


5

[spacer]

103 046

120

Fig. 3-12, (p. 3-17)

Cycle time at the conclusion of which the selected measured values are again
transmitted.
Note: This setting is hidden unless the COURIER protocol is enabled.

7-28

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default

Logical
communication
interface 2

Address
Min

Max

Unit

Logic Diagram

COMM 2: Functio n gr oup CO MM2

056 057

0: Without
[spacer]

Cancelling function group COMM2 or including it in the configuration. If the


function group is cancelled from the configuration, then all associated settings
and signals are hidden, with the exception of this setting.

[spacer]

COMM 2: General enabl e USE R

103 170

0: No

Fig. 3-14, (p. 3-19)

[spacer]

Disabling or enabling communication interface 2.

[spacer]

COMM 2: Line idle stat e

103 165

1: Light on / high

Fig. 3-14, (p. 3-19)

[spacer]

Setting for the line idle state indication.

[spacer]

COMM 2: Baud rat e

103 071

19.2: 19.2 kBaud

Baud

[spacer]

Baud rate of the communication interface.

[spacer]

COMM 2: Parity bit

Fig. 3-14, (p. 3-19)

103 171

2: Even

Fig. 3-14, (p. 3-19)

[spacer]

Set the same parity that is set at the interface of the control system connected
to the P437.

[spacer]

COMM 2: Dead t ime moni toring

103 176

1: Yes
[spacer]

Fig. 3-14, (p. 3-19)

The P437 monitors telegram transmission to make sure that no excessive pause
occurs within a telegram. This monitoring function can be disabled if it is not
required.
Note: This setting is only necessary for modem transmission.

[spacer]

COMM 2: Mon. time pol ling


25

103 202

254

Fig. 3-14, (p. 3-19)

[spacer]

The time between two polling calls from the communication master must be less
than the time set here.

[spacer]

COMM 2: Posit ive ackn. faul t

103 203

0: No
[spacer]

It is possible to set whether or not faults can be acknowledged positively after


transmission (and consequently deleted from the fault overview at the
COMM2/PC interface).

P437/EN M/R-11-A // P437311650

7-29

P437

7 Settings

Parameter
Default
[spacer]

Min

Max

Unit

Logic Diagram

COMM 2: Octet comm. addre ss


1

[spacer]

Address

103 072

254

Fig. 3-14, (p. 3-19)

The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be selected
for both addresses.
ASDU: Application Service Data Unit

[spacer]

COMM 2: Name of manufac ture r

103 161

1: SE
[spacer]

Fig. 3-14, (p. 3-19)

Setting for the name of the manufacturer.


Note: This setting can be changed to ensure compatibility.

[spacer]

COMM 2: Octet address ASD U


1

[spacer]

103 073

255

Fig. 3-14, (p. 3-19)

The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be selected
for both addresses.
ASDU: Application Service Data Unit

[spacer]

COMM 2: Spontan. s ig. enabl e

103 177

0: None

Fig. 3-14, (p. 3-19)

[spacer]

Enable for the transmission of spontaneous signals via the communication


interface.

[spacer]

COMM 2: Se le ct. s pont an.sig.

103 179

060 000: MAIN: Without function

Fig. 3-14, (p. 3-19)

[spacer]

Selection of spontaneous signals for transmission via communication interface 2.

[spacer]

COMM 2: Transm .enab.c ycl.dat

103 074

0: Without

Fig. 3-14, (p. 3-19)

[spacer]

Enable for the cyclic transmission of measured values via the communication
interface.

[spacer]

COMM 2: Cycl. dat a ILS t e l.

103 175

060 000: MAIN: Without function

Fig. 3-14, (p. 3-19)

[spacer]

Selection of the measured values transmitted in a user-defined telegram via the


communication interface.

[spacer]

COMM 2: Delta V
3.0

[spacer]

7-30

103 050

0.0

15.0

%Vnom

Fig. 3-14, (p. 3-19)

A measured voltage value is transmitted via the communication interface if it


differs by the set delta quantity from the last measured value transmitted.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

COMM 2: Delta I
3.0

103 051

0.0

15.0

%Inom

Fig. 3-14, (p. 3-19)

[spacer]

A measured current value is transmitted via the communication interface if it


differs by the set delta quantity from the last measured value transmitted.

[spacer]

COMM 2: Delta P
15.0

103 054

0.0

15.0

%Snom

Fig. 3-14, (p. 3-19)

[spacer]

The active power value is transmitted via the communication interface if it


differs by the set delta quantity from the last measured value transmitted.

[spacer]

COMM 2: Delta f
2.0

103 052

0.0

2.0

%fnom

Fig. 3-14, (p. 3-19)

[spacer]

The measured frequency value is transmitted via the communication interface if


it differs by the set delta quantity from the last measured value transmitted.

[spacer]

COMM 2: Delta me as. v.ILS t el


3.0

0.0

103 150

15.0

Fig. 3-14, (p. 3-19)

[spacer]

The telegram is transmitted if a measured value differs by the set delta quantity
from the last measured value transmitted.

[spacer]

COMM 2: Delta t
1

[spacer]

103 053

15

min

Fig. 3-14, (p. 3-19)

All measured values are transmitted again via the communication interface after
this time period has elapsed provided that transmission has not been triggered
by the other delta conditions.

P437/EN M/R-11-A // P437311650

7-31

P437

7 Settings

Parameter
Default

InterMiCOM
interface

Address
Min

Max

Unit

Logic Diagram

COMM 3: Function gr oup CO MM3

056 058

0: Without
[spacer]

Cancelling function group COMM3 or including it in the configuration.


This setting parameter is only visible if the relevant optional communication
module is fitted.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.

[spacer]

COMM 3: General enabl e USE R

120 030

0: No
[spacer]

COMM 4: General enabl e USE R

122 030

0: No
[spacer]

Disabling or enabling communication interface 3.

[spacer]

COMM 3: Baud rate


9600: 9600 baud

[spacer]

120 038

Baud

COMM 4: Baud rate


9600: 9600 baud

122 038

Baud

[spacer]

Adjustment of the baud rate for telegram transmission via the guidance
interface (InterMiCOM interface) so as to meet the requirements of the
transmission carrier.

[spacer]

COMM 3: Source addr es s

120 031

1: 1
[spacer]

COMM 4: Source addr es s

122 031

1: 1
[spacer]

Address for send signals.

[spacer]

COMM 3: Receiving addr es s

120 032

2: 2
[spacer]

COMM 4: Function gr oup CO MM4

056 088

0: Without
[spacer]

COMM 4: Receiving addr es s

122 032

2: 2
[spacer]

Address for receive signals.

[spacer]

COMM 3: Fct. ass ignm. se nd 1

121 001

060 000: MAIN: Without function


[spacer]

COMM 3: Fct. ass ignm. se nd 2

121 003

060 000: MAIN: Without function


[spacer]

COMM 3: Fct. ass ignm. se nd 3

121 005

060 000: MAIN: Without function

7-32

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

COMM 3: Fct. ass ignm. se nd 4

Logic Diagram
121 007

060 000: MAIN: Without function


[spacer]

COMM 3: Fct. ass ignm. se nd 5

121 009

060 000: MAIN: Without function


[spacer]

COMM 3: Fct. ass ignm. se nd 6

121 011

060 000: MAIN: Without function


[spacer]

COMM 3: Fct. ass ignm. se nd 7

121 013

060 000: MAIN: Without function


[spacer]

COMM 3: Fct. ass ignm. se nd 8

121 015

060 000: MAIN: Without function


[spacer]

COMM 4: Fct. ass ignm. se nd 1

123 001

060 000: MAIN: Without function


[spacer]

COMM 4: Fct. ass ignm. se nd 2

123 003

060 000: MAIN: Without function


[spacer]

COMM 4: Fct. ass ignm. se nd 3

123 005

060 000: MAIN: Without function


[spacer]

COMM 4: Fct. ass ignm. se nd 4

123 007

060 000: MAIN: Without function


[spacer]

COMM 4: Fct. ass ignm. se nd 5

123 009

060 000: MAIN: Without function


[spacer]

COMM 4: Fct. ass ignm. se nd 6

123 011

060 000: MAIN: Without function


[spacer]

COMM 4: Fct. ass ignm. se nd 7

123 013

060 000: MAIN: Without function


[spacer]

COMM 4: Fct. ass ignm. se nd 8

123 015

060 000: MAIN: Without function


[spacer]

Assignment of functions for the 8 send signals.

[spacer]

COMM 3: Fct. ass ignm. re c. 1

120 001

061 000: MAIN: Without function


[spacer]

COMM 3: Fct. ass ignm. re c. 2

120 004

061 000: MAIN: Without function


[spacer]

COMM 3: Fct. ass ignm. re c. 3

120 007

061 000: MAIN: Without function


[spacer]

COMM 3: Fct. ass ignm. re c. 4

120 010

061 000: MAIN: Without function


[spacer]

COMM 3: Fct. ass ignm. re c. 5

120 013

061 000: MAIN: Without function

P437/EN M/R-11-A // P437311650

7-33

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

COMM 3: Fct. ass ignm. re c. 6

120 016

061 000: MAIN: Without function


[spacer]

COMM 3: Fct. ass ignm. re c. 7

120 019

061 000: MAIN: Without function


[spacer]

COMM 3: Fct. ass ignm. re c. 8

120 022

061 000: MAIN: Without function


[spacer]

COMM 4: Fct. ass ignm. re c. 1

122 001

061 000: MAIN: Without function


[spacer]

COMM 4: Fct. ass ignm. re c. 2

122 004

061 000: MAIN: Without function


[spacer]

COMM 4: Fct. ass ignm. re c. 3

122 007

061 000: MAIN: Without function


[spacer]

COMM 4: Fct. ass ignm. re c. 4

122 010

061 000: MAIN: Without function


[spacer]

COMM 4: Fct. ass ignm. re c. 5

122 013

061 000: MAIN: Without function


[spacer]

COMM 4: Fct. ass ignm. re c. 6

122 016

061 000: MAIN: Without function


[spacer]

COMM 4: Fct. ass ignm. re c. 7

122 019

061 000: MAIN: Without function


[spacer]

COMM 4: Fct. ass ignm. re c. 8

122 022

061 000: MAIN: Without function


[spacer]

Configuration (assignment of functions) for the 8 receive signals

[spacer]

COMM 3: Ope r. m ode rec eiv e 1

120 002

1: Direct intertrip
[spacer]

COMM 3: Ope r. m ode rec eiv e 2

120 005

1: Direct intertrip
[spacer]

COMM 3: Ope r. m ode rec eiv e 3

120 008

1: Direct intertrip
[spacer]

COMM 3: Ope r. m ode rec eiv e 4

120 011

1: Direct intertrip
[spacer]

COMM 4: Ope r. m ode rec eiv e 1

122 002

1: Direct intertrip
[spacer]

COMM 4: Ope r. m ode rec eiv e 2

122 005

1: Direct intertrip
[spacer]

COMM 4: Ope r. m ode rec eiv e 3

122 008

1: Direct intertrip

7-34

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

COMM 4: Ope r. mode rec eiv e 4

122 011

1: Direct intertrip
[spacer]

Selection of Blocking or Direct intertrip for the operating mode of receive signals
1 to 4 (single-pole transmission).

[spacer]

COMM 3: Ope r. mode rec eiv e 5

120 014

1: Direct intertrip
[spacer]

COMM 3: Ope r. mode rec eiv e 6

120 017

1: Direct intertrip
[spacer]

COMM 3: Ope r. mode rec eiv e 7

120 020

1: Direct intertrip
[spacer]

COMM 3: Ope r. mode rec eiv e 8

120 023

1: Direct intertrip
[spacer]

COMM 4: Ope r. mode rec eiv e 5

122 014

1: Direct intertrip
[spacer]

COMM 4: Ope r. mode rec eiv e 6

122 017

1: Direct intertrip
[spacer]

COMM 4: Ope r. mode rec eiv e 7

122 020

1: Direct intertrip
[spacer]

COMM 4: Ope r. mode rec eiv e 8

122 023

1: Direct intertrip
[spacer]

Selection of Permissive or Direct intertrip for the operating mode of receive


signals 5 to 8 (two-pole transmission).

[spacer]

COMM 3: Default value rec . 1

120 060

0: 0
[spacer]

COMM 3: Default value rec . 2

120 061

0: 0
[spacer]

COMM 3: Default value rec . 3

120 062

0: 0
[spacer]

COMM 3: Default value rec . 4

120 063

0: 0
[spacer]

COMM 3: Default value rec . 5

120 064

0: 0
[spacer]

COMM 3: Default value rec . 6

120 065

0: 0
[spacer]

COMM 3: Default value rec . 7

120 066

0: 0
[spacer]

COMM 3: Default value rec . 8

120 067

0: 0

P437/EN M/R-11-A // P437311650

7-35

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

COMM 4: Default value rec . 1

122 060

0: 0
[spacer]

COMM 4: Default value rec . 2

122 061

0: 0
[spacer]

COMM 4: Default value rec . 3

122 062

0: 0
[spacer]

COMM 4: Default value rec . 4

122 063

0: 0
[spacer]

COMM 4: Default value rec . 5

122 064

0: 0
[spacer]

COMM 4: Default value rec . 6

122 065

0: 0
[spacer]

COMM 4: Default value rec . 7

122 066

0: 0
[spacer]

COMM 4: Default value rec . 8

122 067

0: 0
[spacer]

Definition of the default value for the 8 receive signals.

[spacer]

COMM 3: Tim e- out comm.faul t


50

[spacer]

10

60000

120 033

ms

COMM 4: Tim e- out comm.faul t


50

10

60000

122 033

ms

[spacer]

This timer triggers the alarm signals COMM3: C ommunications faul t


and S F MON: Com munic .fault CO M M3 the received signals to their userdefined default values. Time-out occurs when the set time has elapsed since the
most recent 100% valid telegram was received.

[spacer]

COMM 3: Sig.as g. comm.fault

120 034

0: None
[spacer]

Fig. 3-239, (p. 3-313)

COMM 4: Sig.as g. comm.fault

122 034

0: None
[spacer]

Using this setting, the alarm signal can be configured (assigned) to the
corresponding PSIG input signal.

[spacer]

COMM 3: Tim e- out link fail.


5

7-36

120 035

600

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

COMM 4: Tim e- out link fail.


5

122 035

600

[spacer]

Time indicating a persistent failure of the transmission channel. After this timer
stage has elapsed, alarm signals C OMM 3: C omm. link failure and
SFMO N: Comm .link fail.C OMM3 are raised. These can be mapped to
give the operator a warning LED or contact to indicate that maintenance
attention is required.

[spacer]

COMM 3: Limit te le gr. e r r ors


Blocked

[spacer]

100

COMM 4: Limit te le gr. e r r ors


Blocked

[spacer]

120 036

100

122 036

Percentage of corrupted messages compared to total messages transmitted


before an alarm is raised (CO M M3 : Lim.e x ce e d.,tel.e rr. and
SFMO N: Lim .e x c.te l.e r .COM M3). When this threshold is exceeded, the
receive signals are set to their user-defined default values.
Parameter
Default

IRIGB interface

Address
Min

Max

Unit

Logic Diagram

IRIGB: Function group IRIG B

056 072

0: Without
[spacer]

Cancelling function group IRIGB or including it in the configuration. If the


function group is cancelled from the configuration, then all associated settings
and signals are hidden.

[spacer]

IRIGB: Gener al e nable US ER


0: No

[spacer]

023 200

Fig. 3-22, (p. 3-38)

Disabling or enabling the IRIG-B interface.

P437/EN M/R-11-A // P437311650

7-37

P437

7 Settings

Parameter
Default

IEC Generic
Substation Status
Events

Address
Min

Max

Unit

Logic Diagram

GSS E: Function group G SS E

056 060

0: Without
[spacer]

Cancelling function group GSSE or including it in the configuration.


If the function group is cancelled from the configuration, then all associated
settings and signals are hidden. Parameters included in this function group are
only effective when function group IEC is configured and enabled and when the
parameters in this function group have been activated by setting the parameter
IEC: Switch Config. Bank.

[spacer]

GSS E: Gene ral e nabl e US E R

104 049

0: No
[spacer]

Enabling and disabling function group GSSE.

[spacer]

GSS E: Min. cycle


10

[spacer]

104 052

60

ms

Minimum value for the GSSE repetition cycle time in ms. The repetition cycle
time for a GSSE message is calculated, according to a standard, with this
formula:
Repetition cycle time = Min. cycle + (1 + (increment/1000))N-1 [ms]
The repetitions counter N will be restarted at count 1 after each state change of
a GSSE bit pair.

[spacer]

GSS E: Max. cycle


1

104 053

60

[spacer]

Maximum value for the GSSE repetition cycle time in s. For the formula to
calculate the repetition cycle time see G SS E : Min. cycle. Should the
calculated value for the repetition cycle time be equal to or greater than the set
max. value then the GSSE message will be sent repeatedly at the set max. value
time.

[spacer]

GSS E: Incre ment


900

104 054

999

[spacer]

Increment for the GSSE repetition cycle. For the formula to calculate the
repetition cycle time see GS SE: Min. c ycle.

[spacer]

GSS E: Ope rat ing mode

104 055

0: Promiscuous
[spacer]

In the operating mode Broadcast all GSSE, independent of their MAC address
(network hardware characteristic), are always read and processed. In the
operating mode Promiscuous and after all GSSE sending devices have loggedon, only messages with the MAC addresses of IEDs, that have logged-on
successfully, are read and processed.

[spacer]

GSS E: Output 1 bit pair

104 101

0: No selection

7-38

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

GSS E: Output 2 bit pair

Max

Unit

Logic Diagram
104 104

0: No selection
[spacer]

GSS E: Output 3 bit pair

104 107

0: No selection
[spacer]

GSS E: Output 4 bit pair

104 110

0: No selection
[spacer]

GSS E: Output 5 bit pair

104 113

0: No selection
[spacer]

GSS E: Output 6 bit pair

104 116

0: No selection
[spacer]

GSS E: Output 7 bit pair

104 119

0: No selection
[spacer]

GSS E: Output 8 bit pair

104 122

0: No selection
[spacer]

GSS E: Output 9 bit pair

104 125

0: No selection
[spacer]

GSS E: Output 10 bit pair

104 128

0: No selection
[spacer]

GSS E: Output 11 bit pair

104 131

0: No selection
[spacer]

GSS E: Output 12 bit pair

104 134

0: No selection
[spacer]

GSS E: Output 13 bit pair

104 137

0: No selection
[spacer]

GSS E: Output 14 bit pair

104 140

0: No selection
[spacer]

GSS E: Output 15 bit pair

104 143

0: No selection
[spacer]

GSS E: Output 16 bit pair

104 146

0: No selection
[spacer]

GSS E: Output 17 bit pair

104 149

0: No selection
[spacer]

GSS E: Output 18 bit pair

104 152

0: No selection
[spacer]

GSS E: Output 19 bit pair

104 155

0: No selection
[spacer]

GSS E: Output 20 bit pair

104 158

0: No selection

P437/EN M/R-11-A // P437311650

7-39

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

GSS E: Output 21 bit pair

Max

Unit

Logic Diagram
104 161

0: No selection
[spacer]

GSS E: Output 22 bit pair

104 164

0: No selection
[spacer]

GSS E: Output 23 bit pair

104 167

0: No selection
[spacer]

GSS E: Output 24 bit pair

104 170

0: No selection
[spacer]

GSS E: Output 25 bit pair

104 173

0: No selection
[spacer]

GSS E: Output 26 bit pair

104 176

0: No selection
[spacer]

GSS E: Output 27 bit pair

104 179

0: No selection
[spacer]

GSS E: Output 28 bit pair

104 182

0: No selection
[spacer]

GSS E: Output 29 bit pair

104 185

0: No selection
[spacer]

GSS E: Output 30 bit pair

104 188

0: No selection
[spacer]

GSS E: Output 31 bit pair

104 191

0: No selection
[spacer]

GSS E: Output 32 bit pair

104 194

0: No selection
[spacer]

Setting with which GSSE bit pair the configured binary signal of the virtual GSSE
outputs is to be transmitted. A GSSE is always transmitted consisting of a fixed
number of 96 bit pairs, of which a maximum of 32 are used by this device (IED)
during a send operation.

[spacer]

GSS E: Output 1 fct.assig.

104 102

060 000: MAIN: Without function


[spacer]

GSS E: Output 2 fct.assig.

104 105

060 000: MAIN: Without function


[spacer]

GSS E: Output 3 fct.assig.

104 108

060 000: MAIN: Without function


[spacer]

GSS E: Output 4 fct.assig.

104 111

060 000: MAIN: Without function


[spacer]

GSS E: Output 5 fct.assig.

104 114

060 000: MAIN: Without function

7-40

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

GSS E: Output 6 fct.assig.

Max

Unit

Logic Diagram
104 117

060 000: MAIN: Without function


[spacer]

GSS E: Output 7 fct.assig.

104 120

060 000: MAIN: Without function


[spacer]

GSS E: Output 8 fct.assig.

104 123

060 000: MAIN: Without function


[spacer]

GSS E: Output 9 fct.assig.

104 126

060 000: MAIN: Without function


[spacer]

GSS E: Output 10 fct.assig.

104 129

060 000: MAIN: Without function


[spacer]

GSS E: Output 11 fct.assig.

104 132

060 000: MAIN: Without function


[spacer]

GSS E: Output 12 fct.assig.

104 135

060 000: MAIN: Without function


[spacer]

GSS E: Output 13 fct.assig.

104 138

060 000: MAIN: Without function


[spacer]

GSS E: Output 14 fct.assig.

104 141

060 000: MAIN: Without function


[spacer]

GSS E: Output 15 fct.assig.

104 144

060 000: MAIN: Without function


[spacer]

GSS E: Output 16 fct.assig.

104 147

060 000: MAIN: Without function


[spacer]

GSS E: Output 17 fct.assig.

104 150

060 000: MAIN: Without function


[spacer]

GSS E: Output 18 fct.assig.

104 153

060 000: MAIN: Without function


[spacer]

GSS E: Output 19 fct.assig.

104 156

060 000: MAIN: Without function


[spacer]

GSS E: Output 20 fct.assig.

104 159

060 000: MAIN: Without function


[spacer]

GSS E: Output 21 fct.assig.

104 162

060 000: MAIN: Without function


[spacer]

GSS E: Output 22 fct.assig.

104 165

060 000: MAIN: Without function


[spacer]

GSS E: Output 23 fct.assig.

104 168

060 000: MAIN: Without function


[spacer]

GSS E: Output 24 fct.assig.

104 171

060 000: MAIN: Without function

P437/EN M/R-11-A // P437311650

7-41

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

GSS E: Output 25 fct.assig.

Max

Unit

Logic Diagram
104 174

060 000: MAIN: Without function


[spacer]

GSS E: Output 26 fct.assig.

104 177

060 000: MAIN: Without function


[spacer]

GSS E: Output 27 fct.assig.

104 180

060 000: MAIN: Without function


[spacer]

GSS E: Output 28 fct.assig.

104 183

060 000: MAIN: Without function


[spacer]

GSS E: Output 29 fct.assig.

104 186

060 000: MAIN: Without function


[spacer]

GSS E: Output 30 fct.assig.

104 189

060 000: MAIN: Without function


[spacer]

GSS E: Output 31 fct.assig.

104 192

060 000: MAIN: Without function


[spacer]

GSS E: Output 32 fct.assig.

104 195

060 000: MAIN: Without function


[spacer]

Function assignment of a binary logical state signal to the virtual GSSE outputs.
The signal configured here is sent through the GSSE bit pair as configured
above.

[spacer]

GSS E: Inp ut 1 b it pair

105 001

0: No selection
[spacer]

GSS E: Inp ut 2 b it pair

105 006

0: No selection
[spacer]

GSS E: Inp ut 3 b it pair

105 011

0: No selection
[spacer]

GSS E: Inp ut 4 b it pair

105 016

0: No selection
[spacer]

GSS E: Inp ut 5 b it pair

105 021

0: No selection
[spacer]

GSS E: Inp ut 6 b it pair

105 026

0: No selection
[spacer]

GSS E: Inp ut 7 b it pair

105 031

0: No selection
[spacer]

GSS E: Inp ut 8 b it pair

105 036

0: No selection
[spacer]

GSS E: Inp ut 9 b it pair

105 041

0: No selection

7-42

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

GSS E: Inp ut 10 bit pair

Max

Unit

Logic Diagram
105 046

0: No selection
[spacer]

GSS E: Inp ut 11 bit pair

105 051

0: No selection
[spacer]

GSS E: Inp ut 12 bit pair

105 056

0: No selection
[spacer]

GSS E: Inp ut 13 bit pair

105 061

0: No selection
[spacer]

GSS E: Inp ut 14 bit pair

105 066

0: No selection
[spacer]

GSS E: Inp ut 15 bit pair

105 071

0: No selection
[spacer]

GSS E: Inp ut 16 bit pair

105 076

0: No selection
[spacer]

GSS E: Inp ut 17 bit pair

105 081

0: No selection
[spacer]

GSS E: Inp ut 18 bit pair

105 086

0: No selection
[spacer]

GSS E: Inp ut 19 bit pair

105 091

0: No selection
[spacer]

GSS E: Inp ut 20 bit pair

105 096

0: No selection
[spacer]

GSS E: Inp ut 21 bit pair

105 101

0: No selection
[spacer]

GSS E: Inp ut 22 bit pair

105 106

0: No selection
[spacer]

GSS E: Inp ut 23 bit pair

105 111

0: No selection
[spacer]

GSS E: Inp ut 24 bit pair

105 116

0: No selection
[spacer]

GSS E: Inp ut 25 bit pair

105 121

0: No selection
[spacer]

GSS E: Inp ut 26 bit pair

105 126

0: No selection
[spacer]

GSS E: Inp ut 27 bit pair

105 131

0: No selection
[spacer]

GSS E: Inp ut 28 bit pair

105 136

0: No selection

P437/EN M/R-11-A // P437311650

7-43

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

GSS E: Inp ut 29 bit pair

Max

Unit

Logic Diagram
105 141

0: No selection
[spacer]

GSS E: Inp ut 30 bit pair

105 146

0: No selection
[spacer]

GSS E: Inp ut 31 bit pair

105 151

0: No selection
[spacer]

GSS E: Inp ut 32 bit pair

105 156

0: No selection
[spacer]

Setting which GSSE bit pair is assigned to which virtual GSSE input. A GSSE is
always received consisting of a fixed number of 96 bit pairs, of which a
maximum of 32 are processed by this device (IED).

[spacer]

GSS E: Inp ut 1 I ED name

105 002

1: Remote IED
[spacer]

GSS E: Inp ut 2 I ED name

105 007

1: Remote IED
[spacer]

GSS E: Inp ut 3 I ED name

105 012

1: Remote IED
[spacer]

GSS E: Inp ut 4 I ED name

105 017

1: Remote IED
[spacer]

GSS E: Inp ut 5 I ED name

105 022

1: Remote IED
[spacer]

GSS E: Inp ut 6 I ED name

105 027

1: Remote IED
[spacer]

GSS E: Inp ut 7 I ED name

105 032

1: Remote IED
[spacer]

GSS E: Inp ut 8 I ED name

105 037

1: Remote IED
[spacer]

GSS E: Inp ut 9 I ED name

105 042

1: Remote IED
[spacer]

GSS E: Inp ut 10 IE D name

105 047

1: Remote IED
[spacer]

GSS E: Inp ut 11 IE D name

105 052

1: Remote IED
[spacer]

GSS E: Inp ut 12 IE D name

105 057

1: Remote IED
[spacer]

GSS E: Inp ut 13 IE D name

105 062

1: Remote IED

7-44

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

GSS E: Inp ut 14 IE D name

Max

Unit

Logic Diagram
105 067

1: Remote IED
[spacer]

GSS E: Inp ut 15 IE D name

105 072

1: Remote IED
[spacer]

GSS E: Inp ut 16 IE D name

105 077

1: Remote IED
[spacer]

GSS E: Inp ut 17 IE D name

105 082

1: Remote IED
[spacer]

GSS E: Inp ut 18 IE D name

105 087

1: Remote IED
[spacer]

GSS E: Inp ut 19 IE D name

105 092

1: Remote IED
[spacer]

GSS E: Inp ut 20 IE D name

105 097

1: Remote IED
[spacer]

GSS E: Inp ut 21 IE D name

105 102

1: Remote IED
[spacer]

GSS E: Inp ut 22 IE D name

105 107

1: Remote IED
[spacer]

GSS E: Inp ut 23 IE D name

105 112

1: Remote IED
[spacer]

GSS E: Inp ut 24 IE D name

105 117

1: Remote IED
[spacer]

GSS E: Inp ut 25 IE D name

105 122

1: Remote IED
[spacer]

GSS E: Inp ut 26 IE D name

105 127

1: Remote IED
[spacer]

GSS E: Inp ut 27 IE D name

105 132

1: Remote IED
[spacer]

GSS E: Inp ut 28 IE D name

105 137

1: Remote IED
[spacer]

GSS E: Inp ut 29 IE D name

105 142

1: Remote IED
[spacer]

GSS E: Inp ut 30 IE D name

105 147

1: Remote IED
[spacer]

GSS E: Inp ut 31 IE D name

105 152

1: Remote IED

P437/EN M/R-11-A // P437311650

7-45

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

GSS E: Inp ut 32 IE D name

105 157

1: Remote IED
[spacer]

IED name for the virtual GSSE input used to identify a GSSE received.

[spacer]

GSS E: Inp ut 1 d efault

105 003

0: 0
[spacer]

GSS E: Inp ut 2 d efault

105 008

0: 0
[spacer]

GSS E: Inp ut 3 d efault

105 013

0: 0
[spacer]

GSS E: Inp ut 4 d efault

105 018

0: 0
[spacer]

GSS E: Inp ut 5 d efault

105 023

0: 0
[spacer]

GSS E: Inp ut 6 d efault

105 028

0: 0
[spacer]

GSS E: Inp ut 7 d efault

105 033

0: 0
[spacer]

GSS E: Inp ut 8 d efault

105 038

0: 0
[spacer]

GSS E: Inp ut 9 d efault

105 043

0: 0
[spacer]

GSS E: Inp ut 10 de fault

105 048

0: 0
[spacer]

GSS E: Inp ut 11 de fault

105 053

0: 0
[spacer]

GSS E: Inp ut 12 de fault

105 058

0: 0
[spacer]

GSS E: Inp ut 13 de fault

105 063

0: 0
[spacer]

GSS E: Inp ut 14 de fault

105 068

0: 0
[spacer]

GSS E: Inp ut 15 de fault

105 073

0: 0
[spacer]

GSS E: Inp ut 16 de fault

105 078

0: 0
[spacer]

GSS E: Inp ut 17 de fault

105 083

0: 0

7-46

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

GSS E: Inp ut 18 de fault

Max

Unit

Logic Diagram
105 088

0: 0
[spacer]

GSS E: Inp ut 19 de fault

105 093

0: 0
[spacer]

GSS E: Inp ut 20 de fault

105 098

0: 0
[spacer]

GSS E: Inp ut 21 de fault

105 103

0: 0
[spacer]

GSS E: Inp ut 22 de fault

105 108

0: 0
[spacer]

GSS E: Inp ut 23 de fault

105 113

0: 0
[spacer]

GSS E: Inp ut 24 de fault

105 118

0: 0
[spacer]

GSS E: Inp ut 25 de fault

105 123

0: 0
[spacer]

GSS E: Inp ut 26 de fault

105 128

0: 0
[spacer]

GSS E: Inp ut 27 de fault

105 133

0: 0
[spacer]

GSS E: Inp ut 28 de fault

105 138

0: 0
[spacer]

GSS E: Inp ut 29 de fault

105 143

0: 0
[spacer]

GSS E: Inp ut 30 de fault

105 148

0: 0
[spacer]

GSS E: Inp ut 31 de fault

105 153

0: 0
[spacer]

GSS E: Inp ut 32 de fault

105 158

0: 0
[spacer]

Default for the virtual binary GSSE input. The state of a virtual two-pole GSSE
input will revert to default as soon as the continuously monitored
communication link to a GSSE sending device (IED situated on the opposite side)
is in fault or has disappeared altogether.

[spacer]

GSS E: Inp ut 1 f ct.assig.

105 004

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 2 f ct.assig.

105 009

061 000: MAIN: Without function

P437/EN M/R-11-A // P437311650

7-47

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

GSS E: Inp ut 3 f ct.assig.

Max

Unit

Logic Diagram
105 014

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 4 f ct.assig.

105 019

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 5 f ct.assig.

105 024

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 6 f ct.assig.

105 029

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 7 f ct.assig.

105 034

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 8 f ct.assig.

105 039

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 9 f ct.assig.

105 044

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 10 fct .assig.

105 049

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 11 fct .assig.

105 054

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 12 fct .assig.

105 059

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 13 fct .assig.

105 064

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 14 fct .assig.

105 069

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 15 fct .assig.

105 074

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 16 fct .assig.

105 079

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 17 fct .assig.

105 084

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 18 fct .assig.

105 089

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 19 fct .assig.

105 094

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 20 fct .assig.

105 099

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 21 fct .assig.

105 104

061 000: MAIN: Without function

7-48

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

GSS E: Inp ut 22 fct .assig.

Max

Unit

Logic Diagram
105 109

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 23 fct .assig.

105 114

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 24 fct .assig.

105 119

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 25 fct .assig.

105 124

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 26 fct .assig.

105 129

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 27 fct .assig.

105 134

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 28 fct .assig.

105 139

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 29 fct .assig.

105 144

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 30 fct .assig.

105 149

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 31 fct .assig.

105 154

061 000: MAIN: Without function


[spacer]

GSS E: Inp ut 32 fct .assig.

105 159

061 000: MAIN: Without function


[spacer]

Function assignment of the virtual GSSE input to a binary logical state signal on
the device (IED) so that it can be processed further by the protection or logic
functions. The signal configured at this point will receive the state of the bit
pair, as configured above, and which was received with GSSE.

P437/EN M/R-11-A // P437311650

7-49

P437

7 Settings

Parameter
Default

IEC 61850
Communication

Address
Min

Max

Unit

Logic Diagram

IEC: Function grou p IEC

056 059

0: Without
[spacer]

Cancelling function group IEC or including it in the configuration. If the function


group is cancelled from the configuration, then all associated settings and
signals are hidden.
Important notice: Some of the parameters in function group IEC are set with
the IEC 61850 configuration tool IED Configurator, they cannot be modified
from the local control panel (HMI) or with the operating program, and therefore
these parameters are listed separately.

[spacer]

IEC: Ge neral enable US ER

104 000

0: No
[spacer]

Enabling and disabling function group IEC.

[spacer]

IEC: Switch Config. Bank

104 043

0: don't execute
[spacer]

This parameter can only be sent individually. Accepting the previously set
communication parameters as the active communication settings.

[spacer]

IEC: Active Conf ig. Name

104 045

2:
[spacer]

Name of the configuration bank currently valid.


Setting is carried out with the IED Configurator.

[spacer]

IEC: Active Conf ig. Ve r s.

104 046

2:
[spacer]

Version number of the configuration bank currently valid.


Setting is carried out with the IED Configurator.

[spacer]

IEC: Inact . C onfig. Name

104 047

2:
[spacer]

Name of the inactive configuration bank.


Setting is carried out with the IED Configurator.

[spacer]

IEC: Inact . C onfig. Ve r s .

104 048

2:
[spacer]

Version number of the inactive configuration bank.


Setting is carried out with the IED Configurator.

7-50

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

IEC: IED nam e

104 057

2:
[spacer]

Explicitly assigned unit name for the function in the system (IED); is part of the
Logical Device Name.
Setting is carried out with the IED Configurator.
Important note: According to the IEC standard the name must consist of only
letters (A..Z, a..z), digits (0..9) and underscore characters (_), and neither a digit
nor the underscore character must be the first character. Note that a nonstandard name causes problems with the IEC 61850 communication.

[spacer]

IEC: IP address

104 001

2:
[spacer]

Assigned IP address of the device for the server function in the system.
Note: This is an information parameter ('read only') and its value is set from the
"IED Configurator" with Communications: IP Address.

[spacer]

IEC: Subnet m ask

104 005

2:
[spacer]

The subnet mask defines which part of the IP address is addressed by the subnetwork and which part by the device that is logged-on to the network.
Note: This is an information parameter ('read only') and its value is set from the
"IED Configurator" with Communications: SubNet Mask.

[spacer]

IEC: Gat eway addre s s

104 011

2:
[spacer]

This parameter shows the IPv4 address of the network gateway for
communication links to clients outside of the local network.
Note: This is an information parameter ('read only') and its value is set from the
"IED Configurator" with Communications: Gateway Address.

[spacer]

IEC: SNTP s erve r 1 IP

104 202

2:
[spacer]

IP address of the preferred server used for clock synchronization.


Note: This is an information parameter ('read only') and its value is set from the
"IED Configurator".

[spacer]

IEC: SNTP s erve r 2 IP

104 210

2:
[spacer]

IP address of the backup server used for clock synchronization.


Note: This is an information parameter ('read only') and its value is set from the
"IED Configurator".

P437/EN M/R-11-A // P437311650

7-51

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

IEC: SigGGI O1 sel ect ion

104 064

060 000: MAIN: Without function


[spacer]

Optional signal assignment for a transmission per communication protocol


IEC 61850 based on the selection table of the binary inputs (opto coupler
inputs).

[spacer]

IEC: Diff . local time


0

104 206

-1440

1440

min

[spacer]

Time difference between UTC and local time at the devices' substation (IED).

[spacer]

IEC: Diff . d ayl.s av. t ime


60

-1440

104 207

1440

min

[spacer]

Time difference of the daylight saving time to standard time.

[spacer]

IEC: Switch.dayl.sav .ti me

104 219

1: Yes
[spacer]

This setting defines whether an automatic switching to daylight saving time is


wanted.

[spacer]

IEC: Dayl.sav.tim e s tar t

104 220

5: Last
[spacer]

IEC: Dayl.sav.tim e s t. d

104 221

7: Sunday
[spacer]

IEC: Dayl.sav.tim e s t. m

104 222

3: March
[spacer]

These three parameters define the date (e.g. at what day of the year) for
switching from standard time over to daylight saving time. Available for
IEC: Dayl.sav.tim e s tar t are the values First, Second, Third, Fourth, and
Last. For IEC: Dayl.sav.ti me st . d the seven weekdays are available so
that for example a setting like on the last Sunday in March may be used.

[spacer]

IEC: Dayl.sav.t.st .0:00 +


120

104 223

1440

min

[spacer]

Time period in minutes after midnight when daylight saving time is switched to
standard time. If for example the clock is advanced one hour from 2:00 AM to
3:00 AM the parameter IE C: D ayl.sav .t .st .0:00 + is set to 120 (minutes).

[spacer]

IEC: Dayl.sav.tim e e nd

104 225

5: Last
[spacer]

IEC: Dayl.sav.tim e e nd d

104 226

7: Sunday
[spacer]

IEC: Dayl.sav.tim e e nd m

104 227

10: October

7-52

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Min

Max

Unit

IEC: Dayl.sav.t.e nd 0:00 +


180

[spacer]

Address

Logic Diagram
104 228

1440

min

This parameter defines the date and time of day for the clock changeover from
daylight saving time to standard time. The setting is similar to that for the clock
changeover to daylight saving time.

P437/EN M/R-11-A // P437311650

7-53

P437

7 Settings

Parameter
Default

Generic Object
Orientated
Substation Events

Address
Min

Max

Unit

GOOSE: Function group GOOS E

Logic Diagram
056 068

0: Without
[spacer]

Cancelling function group GOOSE or including it in the configuration.


If the function group is cancelled from the configuration, then all associated
settings and signals are hidden.
Parameters included in this function group are only effective when function
group IEC is configured and enabled and when the parameters in this function
group have been activated by setting the parameter IEC: Switch Conf ig.
Bank.

[spacer]

GOOSE: Gene ral e nable US ER

106 001

0: No
[spacer]

Enabling and disabling function group GOOSE.

[spacer]

GOOSE: Output 1 fct .as si g.

106 011

060 000: MAIN: Without function


[spacer]

GOOSE: Output 2 fct .as si g.

106 013

060 000: MAIN: Without function


[spacer]

GOOSE: Output 3 fct .as si g.

106 015

060 000: MAIN: Without function


[spacer]

GOOSE: Output 4 fct .as si g.

106 017

060 000: MAIN: Without function


[spacer]

GOOSE: Output 5 fct .as si g.

106 019

060 000: MAIN: Without function


[spacer]

GOOSE: Output 6 fct .as si g.

106 021

060 000: MAIN: Without function


[spacer]

GOOSE: Output 7 fct .as si g.

106 023

060 000: MAIN: Without function


[spacer]

GOOSE: Output 8 fct .as si g.

106 025

060 000: MAIN: Without function


[spacer]

GOOSE: Output 9 fct .as si g.

106 027

060 000: MAIN: Without function


[spacer]

GOOSE: Output 10 fct .as si g.

106 029

060 000: MAIN: Without function


[spacer]

GOOSE: Output 11 fct .as si g.

106 031

060 000: MAIN: Without function


[spacer]

GOOSE: Output 12 fct .as si g.

106 033

060 000: MAIN: Without function

7-54

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

GOOSE: Output 13 fct .as si g.

Unit

Logic Diagram
106 035

060 000: MAIN: Without function


[spacer]

GOOSE: Output 14 fct .as si g.

106 037

060 000: MAIN: Without function


[spacer]

GOOSE: Output 15 fct .as si g.

106 039

060 000: MAIN: Without function


[spacer]

GOOSE: Output 16 fct .as si g.

106 041

060 000: MAIN: Without function


[spacer]

GOOSE: Output 17 fct .as si g.

106 043

060 000: MAIN: Without function


[spacer]

GOOSE: Output 18 fct .as si g.

106 045

060 000: MAIN: Without function


[spacer]

GOOSE: Output 19 fct .as si g.

106 047

060 000: MAIN: Without function


[spacer]

GOOSE: Output 20 fct .as si g.

106 049

060 000: MAIN: Without function


[spacer]

GOOSE: Output 21 fct .as si g.

106 051

060 000: MAIN: Without function


[spacer]

GOOSE: Output 22 fct .as si g.

106 053

060 000: MAIN: Without function


[spacer]

GOOSE: Output 23 fct .as si g.

106 055

060 000: MAIN: Without function


[spacer]

GOOSE: Output 24 fct .as si g.

106 057

060 000: MAIN: Without function


[spacer]

GOOSE: Output 25 fct .as si g.

106 059

060 000: MAIN: Without function


[spacer]

GOOSE: Output 26 fct .as si g.

106 061

060 000: MAIN: Without function


[spacer]

GOOSE: Output 27 fct .as si g.

106 063

060 000: MAIN: Without function


[spacer]

GOOSE: Output 28 fct .as si g.

106 065

060 000: MAIN: Without function


[spacer]

GOOSE: Output 29 fct .as si g.

106 067

060 000: MAIN: Without function


[spacer]

GOOSE: Output 30 fct .as si g.

106 069

060 000: MAIN: Without function


[spacer]

GOOSE: Output 31 fct .as si g.

106 071

060 000: MAIN: Without function

P437/EN M/R-11-A // P437311650

7-55

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

GOOSE: Output 32 fct .as si g.

106 073

060 000: MAIN: Without function


[spacer]

Function assignment of a binary logical state signal to the virtual GOOSE


outputs. Signals configured here can be included as GosGGIO2.ST.ind1,
GosGGIO2.ST.ind2, in the datasets.

[spacer]

GOOSE: Input 1 fct.assig.

107 006

061 000: MAIN: Without function


[spacer]

GOOSE: Input 2 fct.assig.

107 016

061 000: MAIN: Without function


[spacer]

GOOSE: Input 3 fct.assig.

107 026

061 000: MAIN: Without function


[spacer]

GOOSE: Input 4 fct.assig.

107 036

061 000: MAIN: Without function


[spacer]

GOOSE: Input 5 fct.assig.

107 046

061 000: MAIN: Without function


[spacer]

GOOSE: Input 6 fct.assig.

107 056

061 000: MAIN: Without function


[spacer]

GOOSE: Input 7 fct.assig.

107 066

061 000: MAIN: Without function


[spacer]

GOOSE: Input 8 fct.assig.

107 076

061 000: MAIN: Without function


[spacer]

GOOSE: Input 9 fct.assig.

107 086

061 000: MAIN: Without function


[spacer]

GOOSE: Input 10 fct.assig.

107 096

061 000: MAIN: Without function


[spacer]

GOOSE: Input 11 fct.assig.

107 106

061 000: MAIN: Without function


[spacer]

GOOSE: Input 12 fct.assig.

107 116

061 000: MAIN: Without function


[spacer]

GOOSE: Input 13 fct.assig.

107 126

061 000: MAIN: Without function


[spacer]

GOOSE: Input 14 fct.assig.

107 136

061 000: MAIN: Without function


[spacer]

GOOSE: Input 15 fct.assig.

107 146

061 000: MAIN: Without function


[spacer]

GOOSE: Input 16 fct.assig.

107 156

061 000: MAIN: Without function

7-56

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

GOOSE: Input 17 fct.assig.

Max

Unit

Logic Diagram
107 157

061 000: MAIN: Without function


[spacer]

GOOSE: Input 18 fct.assig.

107 158

061 000: MAIN: Without function


[spacer]

GOOSE: Input 19 fct.assig.

107 159

061 000: MAIN: Without function


[spacer]

GOOSE: Input 20 fct.assig.

107 160

061 000: MAIN: Without function


[spacer]

GOOSE: Input 21 fct.assig.

107 161

061 000: MAIN: Without function


[spacer]

GOOSE: Input 22 fct.assig.

107 162

061 000: MAIN: Without function


[spacer]

GOOSE: Input 23 fct.assig.

107 163

061 000: MAIN: Without function


[spacer]

GOOSE: Input 24 fct.assig.

107 164

061 000: MAIN: Without function


[spacer]

GOOSE: Input 25 fct.assig.

107 165

061 000: MAIN: Without function


[spacer]

GOOSE: Input 26 fct.assig.

107 166

061 000: MAIN: Without function


[spacer]

GOOSE: Input 27 fct.assig.

107 167

061 000: MAIN: Without function


[spacer]

GOOSE: Input 28 fct.assig.

107 168

061 000: MAIN: Without function


[spacer]

GOOSE: Input 29 fct.assig.

107 169

061 000: MAIN: Without function


[spacer]

GOOSE: Input 30 fct.assig.

107 170

061 000: MAIN: Without function


[spacer]

GOOSE: Input 31 fct.assig.

107 171

061 000: MAIN: Without function


[spacer]

GOOSE: Input 32 fct.assig.

107 172

061 000: MAIN: Without function


[spacer]

Function assignment of the virtual binary GOOSE inputs (GosGGIO1/Pos1.stVal,


GosGGIO1/Pos2.stVal, ) to a binary logical state signal on the device so that
they can be processed further by the protection, control or logic functions.
Signals configured here contain the received and pre-processed state of data
attributes configured for GOOSE receipt.

P437/EN M/R-11-A // P437311650

7-57

P437

7 Settings

Parameter
Default

Binary input

Address
Min

Max

Unit

Logic Diagram

INP: Filter
0

010 220

20

Fig. 3-24, (p. 3-42)

[spacer]

Input filter which is activated when either the mode Active "high", filt. or Active
"low", filt. has been selected for INP: Ope r. mode U xxx. In order to
suppress transient interference peaks at the logic signal inputs it is suggested to
set this parameter to 6 [steps].

[spacer]

INP: Fct. as signm. U 801

184 002

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 802

184 006

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 803

184 010

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 804

184 014

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 805

184 018

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 806

184 022

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 100 1

152 163

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 100 2

152 166

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 100 3

152 169

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 100 4

152 172

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 100 5

152 175

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 100 6

152 178

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 120 1

152 199

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 120 2

152 202

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 120 3

152 205

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 120 4

152 208

061 000: MAIN: Without function

7-58

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

INP: Fct. as signm. U 120 5

Logic Diagram
152 211

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 120 6

152 214

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 140 1

190 002

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 140 2

190 006

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 140 3

190 010

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 140 4

190 014

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 140 5

190 018

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 140 6

190 022

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 160 1

192 002

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 160 2

192 006

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 160 3

192 010

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 160 4

192 014

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 160 5

192 018

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 160 6

192 022

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 200 1

153 087

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 200 2

153 090

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 200 3

153 093

061 000: MAIN: Without function


[spacer]

INP: Fct. as signm. U 200 4

153 096

061 000: MAIN: Without function


[spacer]

Assignment of functions to binary signal inputs.

P437/EN M/R-11-A // P437311650

7-59

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

INP: Oper. m ode U 801

Max

Unit

Logic Diagram
184 003

1: Active "high"
[spacer]

INP: Oper. m ode U 802

184 007

1: Active "high"
[spacer]

INP: Oper. m ode U 803

184 011

1: Active "high"
[spacer]

INP: Oper. m ode U 804

184 015

1: Active "high"
[spacer]

INP: Oper. m ode U 805

184 019

1: Active "high"
[spacer]

INP: Oper. m ode U 806

184 023

1: Active "high"
[spacer]

INP: Oper. m ode U 100 1

152 164

1: Active "high"
[spacer]

INP: Oper. m ode U 100 2

152 167

1: Active "high"
[spacer]

INP: Oper. m ode U 100 3

152 170

1: Active "high"
[spacer]

INP: Oper. m ode U 100 4

152 173

1: Active "high"
[spacer]

INP: Oper. m ode U 100 5

152 176

1: Active "high"
[spacer]

INP: Oper. m ode U 100 6

152 179

1: Active "high"
[spacer]

INP: Oper. m ode U 120 1

152 200

1: Active "high"
[spacer]

INP: Oper. m ode U 120 2

152 203

1: Active "high"
[spacer]

INP: Oper. m ode U 120 3

152 206

1: Active "high"
[spacer]

INP: Oper. m ode U 120 4

152 209

1: Active "high"
[spacer]

INP: Oper. m ode U 120 5

152 212

1: Active "high"
[spacer]

INP: Oper. m ode U 120 6

152 215

1: Active "high"
[spacer]

INP: Oper. m ode U 140 1

190 003

1: Active "high"

7-60

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

INP: Oper. m ode U 140 2

Logic Diagram
190 007

1: Active "high"
[spacer]

INP: Oper. m ode U 140 3

190 011

1: Active "high"
[spacer]

INP: Oper. m ode U 140 4

190 015

1: Active "high"
[spacer]

INP: Oper. m ode U 140 5

190 019

1: Active "high"
[spacer]

INP: Oper. m ode U 140 6

190 023

1: Active "high"
[spacer]

INP: Oper. m ode U 160 1

192 003

1: Active "high"
[spacer]

INP: Oper. m ode U 160 2

192 007

1: Active "high"
[spacer]

INP: Oper. m ode U 160 3

192 011

1: Active "high"
[spacer]

INP: Oper. m ode U 160 4

192 015

1: Active "high"
[spacer]

INP: Oper. m ode U 160 5

192 019

1: Active "high"
[spacer]

INP: Oper. m ode U 160 6

192 023

1: Active "high"
[spacer]

INP: Oper. m ode U 200 1

153 088

1: Active "high"
[spacer]

INP: Oper. m ode U 200 2

153 091

1: Active "high"
[spacer]

INP: Oper. m ode U 200 3

153 094

1: Active "high"
[spacer]

INP: Oper. m ode U 200 4

153 097

1: Active "high"
[spacer]

Selection of operating mode for binary signal inputs.

P437/EN M/R-11-A // P437311650

7-61

P437

7 Settings

Parameter
Default

Address
Min

Max

Unit

Logic Diagram

Measured data input MEASI: F unction group MEAS I

056 030

0: Without
[spacer]

Cancelling function group MEASI or including it in the configuration.


If the function group is cancelled from the configuration, then all associated
settings and signals are hidden.

[spacer]

MEASI: Ge ne ral enabl e US E R

011 100

0: No

Fig. 3-25, (p. 3-43)


Fig. 3-33, (p. 3-52)

[spacer]

Disabling or enabling analog measured data input.

[spacer]

MEASI: E nable IDC p. u.


0.000

0.000

037 190

0.200

IDC,nom

Fig. 3-28, (p. 3-46)

[spacer]

Setting for the minimum current that must flow in order for the P437 to display a
measured value > 0 (zero suppression).

[spacer]

MEASI: I DC < ope n circuit


3.0

0.0

037 191

10.0

mA

Fig. 3-28, (p. 3-46)

[spacer]

If the input current falls below the set threshold, the P437 will issue an open
circuit signal.

[spacer]

MEASI: I DC 1
0.000

[spacer]

Fig. 3-28, (p. 3-46)


037 154

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 156

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 158

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 160

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 162

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 164

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 166

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)

MEASI: I DC 10
Blocked

7-62

IDC,nom

MEASI: I DC 9
Blocked

[spacer]

1.200

MEASI: I DC 8
Blocked

[spacer]

0.000

MEASI: I DC 7
Blocked

[spacer]

037 152

MEASI: I DC 6
Blocked

[spacer]

Fig. 3-28, (p. 3-46)

MEASI: I DC 5
Blocked

[spacer]

IDC,nom

MEASI: I DC 4
Blocked

[spacer]

1.200

MEASI: I DC 3
Blocked

[spacer]

0.000

MEASI: I DC 2
Blocked

[spacer]

037 150

037 168

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Fig. 3-28, (p. 3-46)


037 172

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 174

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 176

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 178

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 180

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 182

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 184

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)

MEASI: I DC 19
Blocked

[spacer]

IDC,nom

MEASI: I DC 18
Blocked

[spacer]

1.200

MEASI: I DC 17
Blocked

[spacer]

0.000

MEASI: I DC 16
Blocked

[spacer]

037 170

MEASI: I DC 15
Blocked

[spacer]

Logic Diagram

MEASI: I DC 14
Blocked

[spacer]

Unit

MEASI: I DC 13
Blocked

[spacer]

Max

MEASI: I DC 12
Blocked

[spacer]

Min

MEASI: I DC 11
Blocked

[spacer]

Address

037 186

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)

MEASI: I DC 20
1.200

037 188

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)

[spacer]

Setting for the input current that will correspond to a linearized value that has
been set accordingly.

[spacer]

MEASI: I DC ,lin 1
0.000

[spacer]

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 155

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 157

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 159

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 161

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)

MEASI: I DC ,lin 7
Blocked

[spacer]

037 153

MEASI: I DC ,lin 6
Blocked

[spacer]

Fig. 3-28, (p. 3-46)

MEASI: I DC ,lin 5
Blocked

[spacer]

IDC,nom

MEASI: I DC ,lin 4
Blocked

[spacer]

1.200

MEASI: I DC ,lin 3
Blocked

[spacer]

0.000

MEASI: I DC ,lin 2
Blocked

[spacer]

037 151

037 163

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)

MEASI: I DC ,lin 8
Blocked

P437/EN M/R-11-A // P437311650

037 165

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)

7-63

P437

7 Settings

Parameter
Default
[spacer]

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 171

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 173

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 175

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 177

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 179

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 181

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 183

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)


037 185

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)

MEASI: I DC ,lin 19
Blocked

[spacer]

037 169

MEASI: I DC ,lin 18
Blocked

[spacer]

Fig. 3-28, (p. 3-46)

MEASI: I DC ,lin 17
Blocked

[spacer]

IDC,nom

MEASI: I DC ,lin 16
Blocked

[spacer]

1.200

MEASI: I DC ,lin 15
Blocked

[spacer]

0.000

MEASI: I DC ,lin 14
Blocked

[spacer]

037 167

MEASI: I DC ,lin 13
Blocked

[spacer]

Logic Diagram

MEASI: I DC ,lin 12
Blocked

[spacer]

Unit

MEASI: I DC ,lin 11
Blocked

[spacer]

Max

MEASI: I DC ,lin 10
Blocked

[spacer]

Min

MEASI: I DC ,lin 9
Blocked

[spacer]

Address

037 187

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)

MEASI: I DC ,lin 20
1.200

037 189

0.000

1.200

IDC,nom

Fig. 3-28, (p. 3-46)

[spacer]

Setting for the linearized current that will correspond to an input current that
has been set accordingly.

[spacer]

MEASI: S caled val. IDC ,lin1


0

-32768

037 192

32767

[spacer]

Setting for the scaled value of IDC,lin1.

[spacer]

MEASI: S caled val.IDC ,l in2 0


1200

[spacer]

7-64

-32768

32767

Fig. 3-29, (p. 3-47)

037 193

Fig. 3-29, (p. 3-47)

Setting for the scaled value of IDC,lin20.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default

Binary and analog


output

Address
Min

Max

OUTP: Fct. ass i gnm. K 8 0 1

Unit

Logic Diagram
150 169

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 8 0 2

150 172

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 8 0 3

150 175

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 8 0 4

150 178

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 8 0 5

150 181

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 8 0 6

150 184

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 8 0 7

150 187

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 8 0 8

150 190

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 1 0 01

150 217

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 1 0 02

150 220

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 1 0 03

150 223

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 1 0 04

150 226

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 1 0 05

150 229

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 1 0 06

150 232

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 1 0 07

150 235

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 1 0 08

150 238

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 1 2 01

151 009

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 1 2 02

151 012

060 000: MAIN: Without function

P437/EN M/R-11-A // P437311650

7-65

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

OUTP: Fct. ass ignm. K 1 2 03

Unit

Logic Diagram
151 015

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass ignm. K 1 2 04

151 018

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass ignm. K 1 2 05

151 021

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass ignm. K 1 2 06

151 024

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass ignm. K 1 2 07

151 027

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass ignm. K 1 2 08

151 030

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass ignm. K 1 4 01

169 002

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass ignm. K 1 4 02

169 006

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass ignm. K 1 4 03

169 010

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass ignm. K 1 4 04

169 014

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass ignm. K 1 4 05

169 018

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass ignm. K 1 4 06

169 022

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass ignm. K 1 4 07

169 026

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass ignm. K 1 4 08

169 030

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass ignm. K 1 6 01

171 002

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass ignm. K 1 6 02

171 006

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass ignm. K 1 6 03

171 010

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass ignm. K 1 6 04

171 014

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass ignm. K 1 6 05

171 018

060 000: MAIN: Without function

7-66

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

OUTP: Fct. ass i gnm. K 1 6 06

Unit

Logic Diagram
171 022

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 1 6 07

171 026

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 1 6 08

171 030

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 1 8 01

173 002

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 1 8 02

173 006

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 1 8 03

173 010

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 1 8 04

173 014

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 1 8 05

173 018

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 1 8 06

173 022

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 2 0 01

151 201

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 2 0 02

151 204

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 2 0 03

151 207

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 2 0 04

151 210

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 2 0 05

151 213

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 2 0 06

151 216

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 2 0 07

151 219

060 000: MAIN: Without function


[spacer]

OUTP: Fct. ass i gnm. K 2 0 08

151 222

060 000: MAIN: Without function


[spacer]

Assignment of functions to output relays.

[spacer]

OUTP: Oper. mode K 8 01

150 170

1: ES updating

P437/EN M/R-11-A // P437311650

7-67

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

OUTP: Oper. mode K 8 02

Max

Unit

Logic Diagram
150 173

1: ES updating
[spacer]

OUTP: Oper. mode K 8 03

150 176

1: ES updating
[spacer]

OUTP: Oper. mode K 8 04

150 179

1: ES updating
[spacer]

OUTP: Oper. mode K 8 05

150 182

1: ES updating
[spacer]

OUTP: Oper. mode K 8 06

150 185

1: ES updating
[spacer]

OUTP: Oper. mode K 8 07

150 188

1: ES updating
[spacer]

OUTP: Oper. mode K 8 08

150 191

1: ES updating
[spacer]

OUTP: Oper. mode K 1 001

150 218

1: ES updating
[spacer]

OUTP: Oper. mode K 1 002

150 221

1: ES updating
[spacer]

OUTP: Oper. mode K 1 003

150 224

1: ES updating
[spacer]

OUTP: Oper. mode K 1 004

150 227

1: ES updating
[spacer]

OUTP: Oper. mode K 1 005

150 230

1: ES updating
[spacer]

OUTP: Oper. mode K 1 006

150 233

1: ES updating
[spacer]

OUTP: Oper. mode K 1 007

150 236

1: ES updating
[spacer]

OUTP: Oper. mode K 1 008

150 239

1: ES updating
[spacer]

OUTP: Oper. mode K 1 201

151 010

1: ES updating
[spacer]

OUTP: Oper. mode K 1 202

151 013

1: ES updating
[spacer]

OUTP: Oper. mode K 1 203

151 016

1: ES updating
[spacer]

OUTP: Oper. mode K 1 204

151 019

1: ES updating

7-68

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

OUTP: Oper. mode K 1 205

Max

Unit

Logic Diagram
151 022

1: ES updating
[spacer]

OUTP: Oper. mode K 1 206

151 025

1: ES updating
[spacer]

OUTP: Oper. mode K 1 207

151 028

1: ES updating
[spacer]

OUTP: Oper. mode K 1 208

151 031

1: ES updating
[spacer]

OUTP: Oper. mode K 1 401

169 003

1: ES updating
[spacer]

OUTP: Oper. mode K 1 402

169 007

1: ES updating
[spacer]

OUTP: Oper. mode K 1 403

169 011

1: ES updating
[spacer]

OUTP: Oper. mode K 1 404

169 015

1: ES updating
[spacer]

OUTP: Oper. mode K 1 405

169 019

1: ES updating
[spacer]

OUTP: Oper. mode K 1 406

169 023

1: ES updating
[spacer]

OUTP: Oper. mode K 1 407

169 027

1: ES updating
[spacer]

OUTP: Oper. mode K 1 408

169 031

1: ES updating
[spacer]

OUTP: Oper. mode K 1 601

171 003

1: ES updating
[spacer]

OUTP: Oper. mode K 1 602

171 007

1: ES updating
[spacer]

OUTP: Oper. mode K 1 603

171 011

1: ES updating
[spacer]

OUTP: Oper. mode K 1 604

171 015

1: ES updating
[spacer]

OUTP: Oper. mode K 1 605

171 019

1: ES updating
[spacer]

OUTP: Oper. mode K 1 606

171 023

1: ES updating
[spacer]

OUTP: Oper. mode K 1 607

171 027

1: ES updating

P437/EN M/R-11-A // P437311650

7-69

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

OUTP: Oper. mode K 1 608

Logic Diagram
171 031

1: ES updating
[spacer]

OUTP: Oper. mode K 1 801

173 003

1: ES updating
[spacer]

OUTP: Oper. mode K 1 802

173 007

1: ES updating
[spacer]

OUTP: Oper. mode K 1 803

173 011

1: ES updating
[spacer]

OUTP: Oper. mode K 1 804

173 015

1: ES updating
[spacer]

OUTP: Oper. mode K 1 805

173 019

1: ES updating
[spacer]

OUTP: Oper. mode K 1 806

173 023

1: ES updating
[spacer]

OUTP: Oper. mode K 2 001

151 202

1: ES updating
[spacer]

OUTP: Oper. mode K 2 002

151 205

1: ES updating
[spacer]

OUTP: Oper. mode K 2 003

151 208

1: ES updating
[spacer]

OUTP: Oper. mode K 2 004

151 211

1: ES updating
[spacer]

OUTP: Oper. mode K 2 005

151 214

1: ES updating
[spacer]

OUTP: Oper. mode K 2 006

151 217

1: ES updating
[spacer]

OUTP: Oper. mode K 2 007

151 220

1: ES updating
[spacer]

OUTP: Oper. mode K 2 008

151 223

1: ES updating
[spacer]

7-70

Selection of operating mode for output relays.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default

Measured data
output

Address
Min

Max

Unit

Logic Diagram

MEASO: Functio n group M EASO

056 020

0: Without
[spacer]

Cancelling function group MEASI or including it in the configuration.


If the function group is cancelled from the configuration, then all associated
settings and signals are hidden. If the function group is cancelled from the
configuration, then all associated settings and signals are hidden.

[spacer]

MEASO: Ge ne ral e nable US ER

031 074

0: No
[spacer]

Disabling or enabling the measured data output function.

[spacer]

MEASO: Fct . as s ignm. BC D

053 002

060 000: MAIN: Without function

Fig. 3-37, (p. 3-57)

[spacer]

Selection of the measured value to be transmitted in BCD form.

[spacer]

MEASO: Hold t ime output BC D


0.10

0.10

10.00

010 010

Fig. 3-37, (p. 3-57)

[spacer]

Setting for the transmission time of the selected measured value in BCD form.

[spacer]

MEASO: Scale d min. val. B C D


0.000

[spacer]

1.000

MEASO: Scale d max. v al. BC D


1.000

[spacer]

0.000

0.000

P437/EN M/R-11-A // P437311650

037 141

1.000

MEASO: BC D-Out min. value


0

037 140

037 142

399

7-71

P437

7 Settings

Parameter
Default
[spacer]

Min

Max

Unit

Logic Diagram

MEASO: BC D-Out max. value


399

[spacer]

Address

037 143

399

The variable Mx is to be issued in BCD form.


For measured values in the range measured values to be issued the output
value should change linearly with the measured value.

Range of measured values for the variable Mx: Mx,RL1 ... Mx,RL2

Range of associated scaled measured values: 0 ... 1

Range of measured values to be issued: Mx,min ... Mx,max

Range of scaled measured values to be issued: Mx,scal,min ... Mx,scal,max

Designation of the set values in the data model: Scaled min. val. BCD ...
Scaled max. val. BCD

with:
Mx,scal,min = (Mx,min - Mx,RL1)/(Mx,RL2 - Mx,RL1)
Mx,scal,max = (Mx,max - Mx,RL1)/(Mx,RL2 - Mx,RL1)
BCD display values for measured values in the range measured values to be
issued; range: BCD-Out min. value ... BCD-Out max. value
BBCD display values for measured values Mx,min; range: BCD-Out min.
value
BCD display values for measured values Mx,max; range: BCD-Out max.
value
[spacer]

MEASO: Fct . as s ignm. A- 1

053 000

060 000: MAIN: Without function


[spacer]

Fig. 3-39, (p. 3-63)

MEASO: Fct . as s ignm. A- 2

053 001

060 000: MAIN: Without function


[spacer]

Selection of the measured value to be transmitted in analog form.

[spacer]

MEASO: Hold t ime output A- 1


0.10

[spacer]

0.10

10.00

010 114

Fig. 3-39, (p. 3-63)

MEASO: Hold t ime output A- 2


0.10

0.10

10.00

010 115

[spacer]

Setting for the time delay for output of the selected measured value.

[spacer]

MEASO: Scale d m in. val. A-1


0.000

[spacer]

0.000

1.000

0.000

1.000

MEASO: Scale d m in. val. A-2


0.000

7-72

Fig. 3-39, (p. 3-63)


037 105

Fig. 3-39, (p. 3-63)

MEASO: Scale d m ax. v al. A- 1


1.000

[spacer]

1.000

MEASO: Scale d kne e v al. A- 1


Blocked

[spacer]

0.000

037 104

0.000

037 106

Fig. 3-39, (p. 3-63)


037 110

1.000

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Max

Unit

Logic Diagram

0.000

037 111

1.000

MEASO: Scale d max. v al. A- 2


1.000

[spacer]

Min

MEASO: Scale d kne e v al. A- 2


Blocked

[spacer]

Address

0.000

037 112

1.000

After conversion via a characteristic the selected measured value Ax (x = 1, 2) is


to be issued as an output current. For this purpose a range measured values to
be issued is defined. In this range the characteristic has two linear sections,
which are separated by a knee point.

Range of measured values for the variable Mx: Mx,RL1 ... Mx,RL2

Range of associated scaled measured values: 0 ... 1

Range of measured values to be issued: Mx,min ... Mx,max

Range of scaled measured values to be output: Mx,scal,min ... Mx,scal,max

Designation of the set values in the data model: Scaled min. val. Ax ...
Scaled max. val. Ax

with:
Mx,scal,min = (Mx,min - Mx,RL1)/(Mx,RL2 - Mx,RL1)
Mx,scal,max = (Mx,max - Mx,RL1)/(Mx,RL2 - Mx,RL1)

Designation of value for knee point: Mx,knee

Designation of scaled knee point value: Mx,scaled,knee

Designation of this set value in the data model: Scaled knee val. Ax

with:
Mx,scaled,knee = (Mx,knee - Mx,RL1)/(Mx,RL2 - Mx,RL1)
[spacer]

MEASO: AnOut min. v al. A- 1


0.00

[spacer]

Fig. 3-39, (p. 3-63)

0.00

20.00

037 108

mA

Fig. 3-39, (p. 3-63)

0.00

20.00

037 109

mA

MEASO: AnOut min. v al. A- 2


0.00

[spacer]

mA

MEASO: AnOut max. v al. A- 1


20.00

[spacer]

20.00

MEASO: AnOut kne e point A- 1


Blocked

[spacer]

0.00

037 107

0.00

20.00

037 113

mA

MEASO: AnOut kne e point A- 2


Blocked

P437/EN M/R-11-A // P437311650

0.00

20.00

Fig. 3-39, (p. 3-63)

037 114

mA

7-73

P437

7 Settings

Parameter
Default
[spacer]

Min

Max

Unit

MEASO: AnOut max. v al. A- 2


20.00

[spacer]

Address

0.00

20.00

Logic Diagram
037 115

mA

Output current range for measured values in the range measured values to be
issued; designation in the data model: An-Out min. val. Ax ... An-Out max.
val. Ax
Output current to be set for measured values Mx,min; designation in the data
model: An-Out min. val. Ax
Output current to be set for measured values Mx,max; designation in the data
model: An-Out max. val. Ax
Output current to be set for measured values = Mx,knee; designation in the data
model: AnOut knee point Ax
with:
Mx,min ... Mx,max: measured values to be issued

[spacer]

MEASO: Output value 1


0.00

[spacer]

7-74

0.00

037 121

100.00

MEASO: Output value 3


0.00

[spacer]

100.00

MEASO: Output value 2


0.00

[spacer]

0.00

037 120

0.00

037 122

100.00

Measured values of external devices, which must be scaled to 0 to 100%, can be


issued.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default

LED indicators

Address
Min

Max

Unit

Logic Diagram

LED: F ct.ass ig. H 1 gre e n

085 184

060 001: MAIN: Healthy


[spacer]

Display of the operational readiness of the protection device.


The function MAIN: He althy is permanently assigned.

[spacer]

LED: F ct.ass ig. H 2 y ell.

085 001

004 065: MAIN: Blocked/faulty


[spacer]

Display of the function assigned to LED indicator H 2.


The function MAIN: Blocke d/ fault y is permanently assigned.

[spacer]

LED: F ct.ass ig. H 3 y ell.

085 004

036 070: SFMON: Warning (LED)


[spacer]

Display of the function assigned to LED indicator H 3.


The function SFM ON: Warning (LED ) is permanently assigned.

[spacer]

LED: F ct.ass ig. H 4 red

085 007

036 251: MAIN: Gen. trip signal


[spacer]

LED: F ct.ass ig. H 4 gre e n

085 057

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H 5 red

085 010

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H 5 gre e n

085 060

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H 6 red

085 013

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H 6 gre e n

085 063

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H 7 red

085 016

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H 7 gre e n

085 066

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H 8 red

085 019

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H 8 gre e n

085 069

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H 9 red

085 022

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H 9 gre e n

085 072

060 000: MAIN: Without function

P437/EN M/R-11-A // P437311650

7-75

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

LED: F ct.ass ig. H10 red

Max

Unit

Logic Diagram
085 025

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H10 gre e n

085 075

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H11 red

085 028

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H11 gre e n

085 078

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H12 red

085 031

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H12 gre e n

085 081

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H13 red

085 034

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H13 gre e n

085 084

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H14 red

085 037

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H14 gre e n

085 087

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H15 red

085 040

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H15 gre e n

085 090

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H16 red

085 043

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H16 gre e n

085 093

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H18 red

085 131

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H18 gre e n

085 161

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H19 red

085 134

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H19 gre e n

085 164

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H20 red

085 137

060 000: MAIN: Without function

7-76

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

LED: F ct.ass ig. H2 0 gre e n

Logic Diagram
085 167

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H2 1 red

085 140

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H2 1 gre e n

085 170

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H2 2 red

085 143

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H2 2 gre e n

085 173

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H2 3 red

085 146

060 000: MAIN: Without function


[spacer]

LED: F ct.ass ig. H2 3 gre e n

085 177

060 000: MAIN: Without function


[spacer]

Assignment of functions to LED indicators.

[spacer]

LED: F ct.ass ig. H1 7 red

085 185

080 111: LOC: Edit mode


[spacer]

Display of the function assigned to LED indicator H 17.


The function LOC: Edit mode is permanently assigned.

[spacer]

LED: O pe rating mode H 1

085 182

1: ES updating
[spacer]

The operating mode ES updating is permanently assigned.

[spacer]

LED: O pe rating mode H 2

085 002

1: ES updating
[spacer]

The operating mode ES updating is permanently assigned.

[spacer]

LED: O pe rating mode H 3

085 005

1: ES updating
[spacer]

The ES updating operating mode is permanently assigned.

[spacer]

LED: O pe rating mode H 4

085 008

3: ES reset (fault)
[spacer]

LED: O pe rating mode H 5

085 011

1: ES updating
[spacer]

LED: O pe rating mode H 6

085 014

1: ES updating
[spacer]

LED: O pe rating mode H 7

085 017

1: ES updating

P437/EN M/R-11-A // P437311650

7-77

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

LED: O pe rating mode H 8

085 020

1: ES updating
[spacer]

LED: O pe rating mode H 9

085 023

1: ES updating
[spacer]

LED: O pe rating mode H 10

085 026

1: ES updating
[spacer]

LED: O pe rating mode H 11

085 029

1: ES updating
[spacer]

LED: O pe rating mode H 12

085 032

1: ES updating
[spacer]

LED: O pe rating mode H 13

085 035

1: ES updating
[spacer]

LED: O pe rating mode H 14

085 038

1: ES updating
[spacer]

LED: O pe rating mode H 15

085 041

1: ES updating
[spacer]

LED: O pe rating mode H 16

085 044

1: ES updating
[spacer]

LED: O pe rating mode H 18

085 132

1: ES updating
[spacer]

LED: O pe rating mode H 19

085 135

1: ES updating
[spacer]

LED: O pe rating mode H 20

085 138

1: ES updating
[spacer]

LED: O pe rating mode H 21

085 141

1: ES updating
[spacer]

LED: O pe rating mode H 22

085 144

1: ES updating
[spacer]

LED: O pe rating mode H 23

085 147

1: ES updating
[spacer]

Selection of operating mode for LED indicators.

[spacer]

LED: O pe rating mode H 17

085 183

1: ES updating
[spacer]

7-78

The operating mode ES updating is permanently assigned.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default

Main function

Address
Min

Max

Unit

Logic Diagram

MAIN: Chann.ass ign.C OMM 1/ 2

003 169

1: COMM1->chann.1,(2-2)

Fig. 3-77, (p. 3-109)

[spacer]

Assignment of communication interfaces to physical communication channels.

[spacer]

MAIN: Prim .S ource TimeS ync

103 210

0: COMM1
[spacer]

Selection of the primary source for date and time synchronization. Available are
COMM1, COMM2/PC, IRIG-B or a binary input for minute signal pulses.

[spacer]

MAIN: Backup SourceT ime Sy nc

103 211

1: COMM2/PC
[spacer]

Selection of the backup source for date and time synchronization. Available are
COMM1, COMM2/PC, IRIG-B or a binary input for minute signal pulses. The
backup source is used when there is no synchronization generated by the
primary source after MAIN: Time s ync. time-out has elapsed.

[spacer]

MAIN: Tim e s yn c. t ime -out


Blocked

[spacer]

103 212

60

min

Time-out setting for the time synchronization generated by the primary source.

P437/EN M/R-11-A // P437311650

7-79

P437

7 Settings

Parameter
Default

Fault recording

Address
Min

Max

Unit

Logic Diagram

FT_RC: Rec. analog chann. 1

035 160

1: Current IA
[spacer]

FT_RC: Rec. analog chann. 2

035 161

2: Current IB
[spacer]

FT_RC: Rec. analog chann. 3

035 162

3: Current IC
[spacer]

FT_RC: Rec. analog chann. 4

035 163

5: Voltage A-G
[spacer]

FT_RC: Rec. analog chann. 5

035 164

6: Voltage B-G
[spacer]

FT_RC: Rec. analog chann. 6

035 165

7: Voltage C-G
[spacer]

FT_RC: Rec. analog chann. 7

035 166

4: Current IN
[spacer]

FT_RC: Rec. analog chann. 8

035 167

8: Voltage VNG
[spacer]

FT_RC: Rec. analog chann. 9

035 168

210: Voltage Vref


[spacer]

FT_RC: Rec. analog chann.1 0

035 169

0: Without
[spacer]

The user specifies the channel on which each physical variable is recorded.
Parameter
Default

Distance protection

Address
Min

DIST: Function g roup DIST

Max

Unit

Logic Diagram
056 014

1: With
[spacer]

7-80

Canceling function group DIST or including it in the configuration. If the function


group is cancelled from the configuration, then all associated settings and
signals are hidden.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default

Power swing
blocking

Address
Min

Max

Unit

PSB: Function group PSB

Logic Diagram
056 001

0: Without
[spacer]

Cancelling function group PSB or including it in the configuration. If any function


group is cancelled from the configuration, then all associated settings and
signals are hidden.
Parameter
Default

Measuring-circuit
monitoring

Address
Min

Max

Unit

MCM ON: Function group MC MON

Logic Diagram
056 015

0: Without
[spacer]

Cancelling function group MCMON or including it in the configuration.


If the function group is cancelled from the configuration, then all associated
settings and signals are hidden.
Parameter
Default

Address
Min

Max

Unit

Backup overcurrent- BUOC: Function group BUOC


time protection

Logic Diagram
056 002

0: Without
[spacer]

Cancelling function group BUOC or including it in the configuration. If the


function group is cancelled from the configuration, then all associated settings
and signals are hidden.
Parameter
Default

Switch on to fault
protection

Address
Min

Max

SOT F : Funct ion group SOTF

Unit

Logic Diagram
056 003

0: Without
[spacer]

Cancelling function group SOTF or including it in the configuration. If the


function group is cancelled from the configuration, then all associated settings
and signals are hidden.

P437/EN M/R-11-A // P437311650

7-81

P437

7 Settings

Parameter
Default

Protective signaling

Address
Min

Max

Unit

PSIG: Function gr oup P S IG

Logic Diagram
056 004

0: Without
[spacer]

Cancelling function group PSIG or including it in the configuration. If the


function group is cancelled from the configuration, then all associated settings
and signals are hidden.
Parameter
Default

Auto-reclosing
control

Address
Min

Max

Unit

ARC: Function gro up ARC

Logic Diagram
056 005

0: Without
[spacer]

Cancelling function group ARC or including it in the configuration. If the function


group is cancelled from the configuration, then all associated settings and
signals are hidden.
Parameter
Default

Automatic
synchronism check

Address
Min

Max

Unit

ASC: Function gr oup AS C

Logic Diagram
056 006

0: Without
[spacer]

Cancelling function group ASC or including it in the configuration. If any function


group is cancelled from the configuration, then all associated settings and
signals are hidden.
Parameter
Default

Ground fault (shortcircuit) protection

Address
Min

Max

GFS C: Function gr oup GF S C

Unit

Logic Diagram
056 011

0: Without
[spacer]

7-82

Cancelling function group GFSC or including it in the configuration. If any


function group is cancelled from the configuration, then all associated settings
and signals are hidden.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default

Ground fault (shortcircuit) protection


signaling

Address
Min

Max

Unit

GSCSG: Function gr oup G SC S G

Logic Diagram
056 028

0: Without
[spacer]

Cancelling function group GSCSG or including it in the configuration. If any


function group is cancelled from the configuration, then all associated settings
and signals are hidden.
Parameter
Default

Definite-time over
current protection

Address
Min

Max

Unit

DTOC: Function group D TOC

Logic Diagram
056 008

0: Without
[spacer]

Cancelling function group DTOC or including it in the configuration. If the


function group is cancelled from the configuration, then all associated settings
and signals are hidden.
Parameter
Default

Address
Min

Max

Unit

Inverse-time overcur IDMT: F unction group IDMT


rent protection

Logic Diagram
056 009

0: Without
[spacer]

Canceling function group IDMT or including it in the configuration. If the function


group is cancelled from the configuration, then all associated settings and
signals are hidden.
Parameter
Default

Thermal overload
protection

Address
Min

Max

THER M : Function group THER M

Unit

Logic Diagram
056 023

0: Without
[spacer]

Cancelling function group THERM or including it in the configuration. If the


function group is cancelled from the configuration, then all associated settings
and signals are hidden, with the exception of this setting.

P437/EN M/R-11-A // P437311650

7-83

P437

7 Settings

Parameter
Default

Address
Min

Max

Unit

Time-voltage protec V<>: Funct ion group V<>


tion

Logic Diagram
056 010

0: Without
[spacer]

Cancelling function group V<> or including it in the configuration. If the


function group is cancelled from the configuration, then all associated settings
and signals are hidden, with the exception of this setting.
Parameter
Default

Address
Min

Max

Unit

f<> : Function group f<>


Over-/
underfrequency pro
tection

Logic Diagram
056 033

0: Without
[spacer]

Canceling function group f<> or including it in the configuration. If the function


group is cancelled from the configuration, then all associated settings and
signals are hidden, with the exception of this setting.
Parameter
Default

Power directional
protection

Address
Min

Max

Unit

P<>: Function group P <>

Logic Diagram
056 045

0: Without
[spacer]

Cancelling function group P<> or including it in the configuration. If the


function group is cancelled from the configuration, then all associated settings
and signals are hidden.
Parameter
Default

Circuit breaker
failure protection

Address
Min

CBF: Function g ro up CBF

Max

Unit

Logic Diagram
056 007

0: Without
[spacer]

7-84

Cancelling function group CBF or including it in the configuration. If the function


group is cancelled from the configuration, then all associated settings and
signals are hidden, with the exception of this setting.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default

Address
Min

Max

Unit

CBM: Function group CBM


Circuit breaker
condition monitoring

Logic Diagram
056 062

0: Without
[spacer]

Cancelling function group CBM or including it in the configuration. If the function


group is cancelled from the configuration, then all associated settings and
signals are hidden.
Parameter
Default

Limit value
monitoring

Address
Min

Max

Unit

LIMIT : Function group LIMI T

Logic Diagram
056 025

0: Without
[spacer]

Cancelling function group LIMIT or including it in the configuration. If the


function group is cancelled from the configuration, then all associated settings
and signals are hidden, with the exception of this setting.
Parameter
Default

Address
Min

Max

Unit

Programmable Logic LOGIC: Function group LOGIC

Logic Diagram
056 017

0: Without
[spacer]

Cancelling function group LOGIC or including it in the configuration.


If the function group is cancelled from the configuration, then all associated
settings and signals are hidden.
Parameter
Default

Address
Min

Max

Programmable Logic LOG_2: Function gr oup L OG _2

Unit

Logic Diagram
056 089

0: Without
[spacer]

Cancelling function group LOG_2 (Logic 2) or including it in the configuration.


If the function group is cancelled from the configuration, then all associated
settings and signals are hidden.

P437/EN M/R-11-A // P437311650

7-85

P437

7 Settings

Parameter
Default

Binary counts

Address
Min

Max

COUNT : Function gr oup CO UNT

Unit

Logic Diagram
217 047

0: Without
[spacer]

7-86

Cancelling function group COUNT or including it in the configuration. If the


function group is cancelled from the configuration, then all associated settings
and signals are hidden, with the exception of this setting.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default

Configurable func
tion keys

003 036

030 242

4444
030 243

4444
030 244

4444
030 245

4444

F_KEY: Pas s wor d funct. key 6


0

Logic Diagram

4444

F_KEY: Pas s wor d funct. key 5


0

[spacer]

F_KEY: Pas s wor d funct. key 4


0

[spacer]

Unit

F_KEY: Pas s wor d funct. key 3


0

[spacer]

Max

F_KEY: Pas s wor d funct. key 2


0

[spacer]

Min

F_KEY: Pas s wor d funct. key 1


0

[spacer]

Address

030 246

4444

[spacer]

Definition of the password for enabling the function keys.

[spacer]

F_KEY: Fct. ass i gnm. F1

080 112

061 000: MAIN: Without function


[spacer]

F_KEY: Fct. ass i gnm. F2

080 113

061 000: MAIN: Without function


[spacer]

F_KEY: Fct. ass i gnm. F3

080 114

061 000: MAIN: Without function


[spacer]

F_KEY: Fct. ass i gnm. F4

080 115

061 000: MAIN: Without function


[spacer]

F_KEY: Fct. ass i gnm. F5

080 116

061 000: MAIN: Without function


[spacer]

F_KEY: Fct. ass i gnm. F6

080 117

061 000: MAIN: Without function


[spacer]

Assignment of functions to the function keys. Either a single function or a menu


jump list may be selected. There are two menu jump lists, which are assembled
at LOC: Fct. menu jmp lis t 1 or LO C: F ct . me nu jmp list 2,
respectively.

[spacer]

F_KEY: Oper ating mode F 1

080 132

1: Key
[spacer]

F_KEY: Oper ating mode F 2

080 133

1: Key
[spacer]

F_KEY: Oper ating mode F 3

080 134

1: Key
[spacer]

F_KEY: Oper ating mode F 4

080 135

1: Key

P437/EN M/R-11-A // P437311650

7-87

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

F_KEY: Oper ating mode F 5

080 136

1: Key
[spacer]

F_KEY: Oper ating mode F 6

080 137

1: Key
[spacer]

Choice between operation of the function key as a key or switch.

[spacer]

F_KEY: Re tur n time fct .k e ys


10

[spacer]

60000

003 037

Once the password has been entered, the function keys remain active for no
longer than this time. Thereafter, the function keys are disabled until the
password is entered again.

7.1.3

Function Parameters

7.1.3.1

Global
Parameter
Default

PC link

Address
Min

Max

Unit

Logic Diagram

PC: Command b lock ing


0: No

003 182

Fig. 3-5, (p. 3-9)

[spacer]

When command blocking is activated, commands are rejected at the PC


interface.

[spacer]

PC: Sig./m eas .val.bl ock .


0: No

[spacer]

7-88

003 086

Fig. 3-5, (p. 3-9)

When signal and measured value blocking is activated, no signals or measured


data are transmitted through the PC interface.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default

Logical
communication
interface 1

Address
Min

Max

Unit

Logic Diagram

COMM 1: Com m and bloc k. US ER

003 172

1: Yes

Fig. 3-6, (p. 3-11)

[spacer]

When command blocking is activated, commands are rejected at communication


interface 1.

[spacer]

COMM 1: Sig./ meas.block .US E R

003 076

0: No

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)

[spacer]

When signal and measured value blocking user is activated, no signals or


measured data are transmitted through communication interface COMM1.
Parameter
Default

Logical
communication
interface 2

Address
Min

Max

Unit

Logic Diagram

COMM 2: Com m and bloc k. US ER

103 172

0: No

Fig. 3-14, (p. 3-19)

[spacer]

When command blocking is activated, commands are rejected at communication


interface 2.

[spacer]

COMM 2: Sig./ meas.block .US E R

103 076

0: No
[spacer]

Fig. 3-14, (p. 3-19)

When signal and measured value blocking user is activated, no signals or


measured data are transmitted through communication interface COMM2.
Parameter
Default

Binary and analog


output

Min

Max

Unit

Logic Diagram

OUTP: Outp .rel.block USER


0: No

[spacer]

Address

021 014

Fig. 3-31, (p. 3-50)

When this blocking is activated, all output relays are blocked.

P437/EN M/R-11-A // P437311650

7-89

P437

7 Settings

Parameter
Default

Main function

Address
Min

Max

Unit

Logic Diagram

MAIN: Device on-line

003 030

0: No (= off)

Fig. 3-58, (p. 3-88)

[spacer]

Switching the device off-line or on-line. Some parameters can only be changed
when protection is disabled.

[spacer]

MAIN: Tes t m ode USER

003 012

0: No

Fig. 3-78, (p. 3-110)

[spacer]

When the test mode user is activated, signals or measured data for PC and
communication interfaces are labeled 'test mode'.

[spacer]

MAIN: Nominal fr equ. fnom

010 030

50: 50 Hz

Hz

[spacer]

Setting for the nominal frequency of the protected system.

[spacer]

MAIN: Phase s eque nce

010 049

1: A - B - C
[spacer]

Fig. 3-48, (p. 3-77)

Setting the phase sequence A-B-C or A-C-B.


(Alternative terminology: Setting for the rotary field's direction, either clockwise
or anticlockwise.)

[spacer]

MAIN: Inom C.T. prim.


1000

010 001

10000

Fig. 3-43, (p. 3-73)


Fig. 3-44, (p. 3-74)
Fig. 3-325, (p. 3-412)

[spacer]

Setting for the primary nominal current of the main current transformers for
measurement of phase currents.

[spacer]

MAIN: IN,nom C.T. prim.


1000

010 018

10000

Fig. 3-45, (p. 3-75)

[spacer]

Setting for the primary nominal current of the main current transformer for
measurement of residual current.

[spacer]

MAIN: IN,nom ,par C.T . pr im


1000

10000

010 152

Fig. 3-46, (p. 3-75)

[spacer]

Setting for the primary nominal current of the main current transformer for
measurement of the residual current of the parallel line.

[spacer]

MAIN: Vnom V.T. prim.


100.0

0.1

010 002

1000.0

kV

Fig. 3-49, (p. 3-78)

[spacer]

Setting for the primary nominal voltage of the system transformer for
measurement of phase-to-ground and phase-to-phase voltages.

[spacer]

MAIN: VNG,nom V.T . pr im.


100.0

[spacer]

7-90

0.1

010 027

1000.0

kV

Fig. 3-50, (p. 3-79)

Setting for the primary nominal voltage of the system transformer for
measurement of neutral-point displacement voltage.
P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

MAIN: Vref ,nom V.T. pri m.


100.0

0.1

010 100

1000.0

kV

Fig. 3-51, (p. 3-79)

[spacer]

Setting for the primary nominal voltage of the system transformer for
measurement of reference voltage for automatic synchronism check.

[spacer]

MAIN: Inom de vice

010 003

1.0: 1.0 A

Fig. 3-42, (p. 3-70)

[spacer]

Setting for the secondary nominal current of the system transformer for
measurement of phase currents. This also corresponds to the nominal device
current.

[spacer]

MAIN: IN,nom dev ice

010 026

1.0: 1.0 A

Fig. 3-42, (p. 3-70)

[spacer]

Setting for the secondary nominal current of the system transformer for
measurement of residual current. This also corresponds to the nominal device
current.

[spacer]

MAIN: IN,nom ,par de v ice

010 023

1.0: 1.0 A

[spacer]

Setting for the secondary nominal current of the system transformer for
measurement of the residual current of the parallel line. This also corresponds
to the nominal device current.

[spacer]

MAIN: Vnom V.T. sec.


100

50

010 009

130

Fig. 3-42, (p. 3-70)

[spacer]

Setting for the secondary nominal voltage of the system transformer for
measurement of phase-to-ground and phase-to-phase voltages.

[spacer]

MAIN: VNG,nom V.T . sec .


100

50

010 028

130

Fig. 3-42, (p. 3-70)

[spacer]

Setting for the secondary nominal voltage of the system transformer for
measurement of neutral-point displacement voltage.

[spacer]

MAIN: Vref ,nom V.T. s ec .


100

50

031 052

130

Fig. 3-42, (p. 3-70)

[spacer]

Setting for the secondary nominal voltage of the system transformer for
measurement of reference voltage for automatic synchronism check.

[spacer]

MAIN: Conn. m eas . circ. IP


1: Standard

[spacer]

010 004

Fig. 3-42, (p. 3-70)

Short-circuit direction determination depends on the connection of the


measuring circuits. If the connection is as shown in Chapter Installation and
Connection, then the setting must be Standard, if the P437's 'forward' decision
is to be in the direction of the outgoing feeder. If the connection direction is
reversed or given a connection scheme according to Chapter Installation and
Connection if the 'forward' decision is to be in the busbar direction, then the
setting must be Opposite.

P437/EN M/R-11-A // P437311650

7-91

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

MAIN: Conn. m eas . circ. IN

010 019

1: Standard

Fig. 3-42, (p. 3-70)

[spacer]

Direction determination of the ground fault measuring systems depends on the


connection of the measuring circuits. If the connection is as shown in Chapter
Installation and Connection, then the setting must be Standard, if the P437's
'forward' decision is to be in the direction of the outgoing feeder.
If the connection direction is reversed or given a connection scheme according
to Chapter Installation and Connection if the 'forward' decision is to be in the
busbar direction, then the setting must be Opposite.

[spacer]

MAIN: Me as. direct ion P,Q

006 096

1: Standard
[spacer]

[spacer]

Fig. 3-52, (p. 3-81)

This parameter allows inverting the sign for the following measured operating
values:

MAIN: Active powe r P prim.

MAIN: R eac. power Q prim.

MAIN: Active powe r P p.u.

M AIN: Reac. powe r Q p. u.

MAIN: Conn.m eas .c rc .IN,par

010 020

1: Standard

Fig. 3-42, (p. 3-70)

[spacer]

The directional measurement of the ground fault (short-circuit) measuring


systems depends on the connection of the measuring circuits. If the connection
is as shown in Chapter Installation and Connection, then the setting must be
Standard, if the P437's 'forward' decision is to be in the direction of the outgoing
feeder. If the connection direction is reversed or given a connection scheme
according to Chapter Installation and Connection if the 'forward' decision is
to be in the busbar direction, then the setting must be Opposite.

[spacer]

MAIN: Me as. value re l. IP


0.000

0.000

011 030

0.200

Inom

Fig. 3-43, (p. 3-73)

[spacer]

Setting for the minimum current that must be exceeded so that measured
operating values of the phase currents and, if applicable, derived currents are
displayed.

[spacer]

MAIN: Me as. value re l. IN


0.000

0.000

011 031

0.200

IN,nom

Fig. 3-45, (p. 3-75)

[spacer]

Setting for the minimum current that must be exceeded so that the measured
operating value of the residual current is displayed.

[spacer]

MAIN: Me as.val.rel. IN,par


0.000

[spacer]

7-92

0.000

011 043

0.200

IN,nom

Fig. 3-46, (p. 3-75)

Setting for the minimum current that must be exceeded in order for the
measured operating value of the residual current of the parallel line to be
displayed.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

MAIN: Me as. value re l. V


0.000

0.000

011 032

0.200

Vnom

Fig. 3-49, (p. 3-78)

[spacer]

Setting for the minimum voltage that must be exceeded so that measured
operating values of the phase-to-ground voltages, phase-to-phase voltages, and,
if applicable, derived voltages are displayed.

[spacer]

MAIN: Me as. val. re l. VNG


0.000

0.000

011 033

0.200

VNG,nom

Fig. 3-50, (p. 3-79)

[spacer]

Setting for the minimum voltage that must be exceeded so that the measured
operating value of the neutral-point displacement voltage is displayed.

[spacer]

MAIN: Me as. val. re l. Vref


0.000

0.000

011 034

0.200

Vref,nom

Fig. 3-51, (p. 3-79)

[spacer]

Setting for the minimum voltage that must be exceeded so that the measured
operating value of the reference voltage for the automatic synchronism check is
displayed.

[spacer]

MAIN: Op. m ode ene r gy cnt .

010 138

1: Procedure 1

Fig. 3-56, (p. 3-85)

[spacer]

Selection of the procedure to determine the active and reactive energy output.
1st procedure: Data acquisition every 2s (approximately). 2nd procedure: Data
acquisition every 100ms (approximately)

[spacer]

MAIN: Se tt l. t. IP,max,de l
15.0

0.1

010 113

60.0

min

Fig. 3-44, (p. 3-74)

[spacer]

Setting for the time after which the delayed maximum current display shall
reach 95% of the maximum current IP,max.

[spacer]

MAIN: Fct.as sign. res et 1


060 000: MAIN: Without function

005 248

Fig. 3-76, (p. 3-107)

[spacer]

Assigning specific memories and counters which are to be reset jointly if


MAIN: Group res e t 1 USER is enabled.

[spacer]

MAIN: Fct.as sign. res et 2


060 000: MAIN: Without function

005 249

Fig. 3-76, (p. 3-107)

[spacer]

Assigning specific memories and counters which are to be reset jointly if


MAIN: Group res e t 2 USER is enabled.

[spacer]

MAIN: Fct.as sign. bloc k. 1


060 000: MAIN: Without function

[spacer]

021 021

Fig. 3-62, (p. 3-91)

Assignment of functions that will be blocked simultaneously when blocking


input 1 (MAIN: B lock ing 1 EX T) is activated.

P437/EN M/R-11-A // P437311650

7-93

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

MAIN: Fct.as sign. bloc k. 2

021 022

060 000: MAIN: Without function

Fig. 3-62, (p. 3-91)

[spacer]

Assignment of functions that will be blocked simultaneously when blocking


input 2 (MAIN: B locking 2 EX T) is activated.

[spacer]

MAIN: Trip cm d.block . USER

021 012

0: No

Fig. 3-72, (p. 3-103)

[spacer]

Blocking the trip commands from the local control panel.

[spacer]

MAIN: Fct.as sig.t ri p cmd.1

021 001

060 000: MAIN: Without function

Fig. 3-69, (p. 3-100)

[spacer]

Assignment of signals that trigger trip command 1.

[spacer]

MAIN: Fct.as sig.t ri p cmd.2

021 002

060 000: MAIN: Without function

Fig. 3-69, (p. 3-100)

[spacer]

Assignment of the signals that trigger trip command 2.

[spacer]

MAIN: Fct.as s.1p t ri p cmd1

002 060

060 000: MAIN: Without function


[spacer]

[spacer]

Selecting signals for the phase-selective trip logic. Available are these signals:

All trip signals issued by functions DTOC, IDMT and GFSC

All output signals issued by function group LOGIC

MAIN: Par. tri p (1 p) EX T

MAIN: Min.dur . trip cmd. 1


0.10

0.10

021 003

10.00

Fig. 3-69, (p. 3-100)

[spacer]

Setting for the minimum duration of trip command 1.

[spacer]

MAIN: Min.dur . trip cmd. 2


0.10

0.10

021 004

10.00

Fig. 3-69, (p. 3-100)

[spacer]

Setting for the minimum duration of trip command 2.

[spacer]

MAIN: Latching tr ip cmd. 1

021 023

0: No
[spacer]

Specification as to whether trip command 1 should latch.

[spacer]

MAIN: Latching tr ip cmd. 2

021 024

0: No
[spacer]

Specification as to whether trip command 2 should latch.

[spacer]

MAIN: Clos e cmd .puls e ti me


0.100

[spacer]

7-94

0.100

10.000

015 067

Fig. 3-65, (p. 3-95)

Setting for the duration of the close command.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

MAIN: tCB,clos e
0.060

000 032

0.000

1.000

[spacer]

This setting determines the CB close time. In slightly asynchronous power


systems, the CB close time is taken into account by the automatic synchronism
check (ASC) to issue of a close command. This is only possible if
setting ASC: AR with t CB P Sx = Yes or ASC : M C with tCB PS x = Yes.

[spacer]

MAIN: RC inhib .by CB close

015 042

0: No

Fig. 3-65, (p. 3-95)

[spacer]

This setting determines whether the reclose command will be inhibited as soon
as the Circuit breaker closed signal starts.

[spacer]

MAIN: Re l.t . e nab. man.c md


60

3600

003 088

[spacer]

Setting for the release time of the enable for the manual close command.

[spacer]

MAIN: Fct. as s ign. fault

021 031

060 000: MAIN: Without function


[spacer]

Fig. 3-63, (p. 3-92)

Selection of the signals to be signaled as Blocked/Faulty in addition to the


messages that always result in the message Blocked/Faulty.
Parameter
Default

Parameter subset
selection

Address
Min

Max

Unit

Logic Diagram

PSS: Control via USE R

003 100

0: No

Fig. 3-79, (p. 3-112)

[spacer]

If parameter subset selection is to be handled from the integrated local control


panel rather than via binary signal inputs, choose the setting Yes.

[spacer]

PSS: Param.subs.se l. USE R

003 060

1: Parameter subset 1

Fig. 3-79, (p. 3-112)

[spacer]

Selection of the parameter subset from the local control panel.

[spacer]

PSS: Ke ep tim e
Blocked

[spacer]

003 063

0.000

65.000

Fig. 3-79, (p. 3-112)

The setting of this timer stage is relevant only if parameter subset selection is
carried out via the binary signal inputs. Any voltage-free pause that may occur
during selection is bridged. If, after this time period has elapsed, no binary
signal input has yet been set, then the parameter subset selected from the local
control panel shall apply.

P437/EN M/R-11-A // P437311650

7-95

P437

7 Settings

Parameter
Default

Self-monitoring

Address
Min

Max

Unit

Logic Diagram

SFMO N: F ct . as s ign. warni ng

021 030

060 000: MAIN: Without function

Fig. 3-80, (p. 3-113)

[spacer]

Selection of the signals whose appearance shall result in the signals Warning
(LED) and Warning (relay) and in the activation of the LED indicator labeled
ALARM. Signals caused by faulty hardware and leading to blocking of the
device are not configurable. They always result in the above signals and
indication.

[spacer]

SFMO N: M on.s ig. re t enti on


Blocked

[spacer]

021 018

240

This setting defines the duration (in hours) for which a device-internal fault is
stored, so that a decision may be taken between an automatic warm restart and
an automatic device blocking. (Setting to Blocked may be considered the same
as unlimited storage.)
Parameter
Default

Fault recording

Address
Min

Max

Unit

Logic Diagram

FT_RC: Fct. assig . t ri gge r

003 085

060 000: MAIN: Without function

Fig. 3-93, (p. 3-131)

[spacer]

This setting defines the signals that will trigger fault recording.

[spacer]

FT_RC: I>
Blocked

017 065

0.01

40.00

Inom

[spacer]

This setting defines the threshold value of the phase currents that will trigger
fault recording and fault data acquisition.

[spacer]

FT_RC: Pre- fault time


5

003 078

50

Periods

Fig. 3-95, (p. 3-134)

[spacer]

Setting for the time during which data will be recorded before the onset of a
fault (pre-fault recording time).

[spacer]

FT_RC: Post -f ault ti me


5

003 079

750

Periods

Fig. 3-95, (p. 3-134)

[spacer]

Setting for the time during which data will be recorded after the end of a fault
(post-fault recording time).

[spacer]

FT_RC: Max. re cording t ime


50

[spacer]

7-96

750

003 075

Periods

Fig. 3-95, (p. 3-134)

Setting for the maximum recording time per fault. This includes pre-fault and
post-fault recording times.

P437/EN M/R-11-A // P437311650

P437

7 Settings

7.1.3.2

General Functions
Parameter
Default

Distance protection

Address
Min

Max

Unit

Logic Diagram

DIST: Ge ne ral e nable U SE R


1: Yes

[spacer]

Enable/disable the distance protection function.

[spacer]

DIST: CVT s tabil iz ation


0: No

031 073

Fig. 3-96, (p. 3-135)

010 031

Fig. 3-110, (p. 3-153)

[spacer]

This setting defines whether distance protection will operate with or without
stabilization against transient transformation errors of capacitive voltage
transformers.

[spacer]

DIST: Zone e xtens . for 1pG

011 049

0: No
[spacer]

This setting enables zone extension in the case of single-phase-to-ground fault


detection.

[spacer]

DIST: Mode t im er star t


0: With DIST gen.start.

001 236

Fig. 3-126, (p. 3-174)


Fig. 3-127, (p. 3-175)

[spacer]

If the mode With zone starting has been selected, then only the timer stage of
the specific distance protection zone Zn is triggered for which the measured
loop impedance is inside the zone.

P437/EN M/R-11-A // P437311650

7-97

P437

7 Settings

Parameter
Default

Power swing
blocking

Address
Min

Max

Unit

PSB: Gene ral e nable US E R

014 050

0: No

Fig. 3-135, (p. 3-183)

[spacer]

Disabling or enabling power swing blocking.

[spacer]

PSB: R
50 | 10 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

0.1 |
0.02

200 | 40

Fig. 3-136, (p. 3-184)


014 061

0.1 |
0.02

200 | 40

Fig. 3-136, (p. 3-184)

PSB: ne gX
50 | 10 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

014 060

PSB: p osX
50 | 10 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

Logic Diagram

006 185

0.1 |
0.02

200 | 40

Fig. 3-136, (p. 3-184)

PSB:
75

014 062

40

90

[spacer]

Setting for the power swing polygon.

[spacer]

PSB: Op e r. value D el ta T
20

Fig. 3-136, (p. 3-184)

014 090

60

ms

[spacer]

Setting of the timer stage for operating mode PSB: Oper ating mode =
Delta Z.

[spacer]

PSB: Activation co nd. dZ

008 235

1: Power Swing polygon


[spacer]

Setting of the Activation condition for the power swing detection based on
impedance variation.

[spacer]

PSB: Fct . as s ign. block .

012 017

060 000: MAIN: Without function


[spacer]

Selection of the zones to be blocked if the blocking criterion is present.

[spacer]

PSB: Max . PS cycl e dur.


30.00

0.00

[spacer]

Time limit of the blocking effect.

[spacer]

PSB: Hold t ime


30.00

014 055

60.00

011 142

0.00

60.00

[spacer]

Setting of the timer stage by which the signal for power swing blocking condition
is extended.

[spacer]

PSB: B locking t ime i nt.


0.00

[spacer]

7-98

0.00

011 143

60.00

Duration of the signal PSB: Blocke d.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

PSB: Max . blocking ti me


Blocked

0.00

010 179

60.00

[spacer]

Setting of the timer stage by which the signal P S B: Blocked is delayed.

[spacer]

PSB: IP>
3.00

014 058

1.00

20.00

Inom

[spacer]

If the phase current exceeds this threshold, the blocking is cancelled without
time delay.

[spacer]

PSB: Ine g>


0.30

014 057

0.10

1.00

IP,max

[spacer]

If the negative-sequence current exceeds this threshold, the blocking is


cancelled without time delay.

[spacer]

PSB: IN>
0.40

014 056

0.10

1.00

IP,max

[spacer]

If the residual current exceeds this threshold, the blocking is cancelled without
time delay.

[spacer]

PSB: Abort de lay


0.00

008 234

0.00

1.00

[spacer]

Setting of the extension of the blocking effect, which will become active after a
current trigger has started or after the maximum blocking time period has
elapsed.

[spacer]

PSB: R (OOS )
50 | 10 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

0.1 |
0.02

200 | 40

PSB: p osX ( OOS)


50 | 10 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

006 184

006 186

0.1 |
0.02

200 | 40

PSB: ne gX ( OOS)
50 | 10 (For MAIN: Inom
device=1.0A | 5.0A)

006 187

0.1 |
0.02

200 | 40

[spacer]

Settings for the power swing polygon that is used for the enhanced countingbased tripping.

[spacer]

PSB: Pe rm. No. OOS (a)


Blocked

006 028

10

[spacer]

Tripping threshold value of the instable power swing counter, that counts power
swings crossing the inner zone (a).

[spacer]

PSB: Pe rm. No. OOS (b)


Blocked

[spacer]

006 189

10

Tripping threshold value of the instable power swing counter, that counts power
swings crossing the outer zone (b).

P437/EN M/R-11-A // P437311650

7-99

P437

7 Settings

Parameter
Default
[spacer]

7-100

Min

Max

Unit

Logic Diagram

PSB: Pe rm. No. s tab. PS


Blocked

[spacer]

Address

006 027

10

Tripping threshold value of the stable power swing counter.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default

Measuring-circuit
monitoring

Address
Min

Max

Unit

Logic Diagram

MCM ON: Gener al e nable USER

014 001

0: No

Fig. 3-148, (p. 3-198)

[spacer]

Enabling or disabling the measuring-circuit monitoring function.

[spacer]

MCM ON: C urre nt monitor ing

014 006

1: Yes

Fig. 3-148, (p. 3-198)

[spacer]

This setting defines whether the current-measuring circuits shall be monitored.

[spacer]

MCM ON: I min curr. monitor .


0.250

0.050

2.000

010 183

Inom

Fig. 3-148, (p. 3-198)

[spacer]

The current-measuring circuit monitoring function is enabled when the current


exceeds this setting in at least one phase.

[spacer]

MCM ON: I neg >


0.20

014 002

0.10

1.00

Imax

Fig. 3-148, (p. 3-198)

[spacer]

Setting for the operate value Ineg> (permissible unbalance threshold in the
current-measuring circuit).

[spacer]

MCM ON: Op . m ode volt. mon.

014 007

1: Vneg

Fig. 3-149, (p. 3-200)

[spacer]

Selection of the monitoring mode in the voltage-measuring circuit.

[spacer]

MCM ON: I min Vne g monit ori ng


0.050

0.050

2.000

010 184

Inom

Fig. 3-149, (p. 3-200)

[spacer]

The negative-sequence voltage monitoring function is enabled when the current


exceeds this setting in at least one phase.

[spacer]

MCM ON: Op erate delay


1.00

0.00

017 011

10.00

Fig. 3-149, (p. 3-200)

[spacer]

Setting for the operate delay after which the 'Meas. circ. (V/I) faulty' signals will
be issued.

[spacer]

MCM ON: FF, V e nable d USE R

014 009

0: No
[spacer]

Enabling or disabling the Fuse Failure monitoring function.

[spacer]

MCM ON: FF,Vre f enable d US ER


0: No

[spacer]

014 013

Fig. 3-151, (p. 3-205)

Enabling or disabling the Fuse Failure monitoring function of the reference


voltage Vref.

P437/EN M/R-11-A // P437311650

7-101

P437

7 Settings

Parameter
Default
[spacer]

Min

Max

Unit

Logic Diagram

MCM ON: Op er. de lay F F , Vre f


0.00

[spacer]

Address

0.00

10.00

014 012

Fig. 3-151, (p. 3-205)

Setting for the time delay for Fuse Failure monitoring of the reference voltage
Vref.
Parameter
Default

Address
Min

Max

Unit

Logic Diagram

Backup overcurrent- BUOC: Gener al e nable USE R


time protection

014 011

0: No

Fig. 3-152, (p. 3-207)

[spacer]

Enabling or disabling BUOC protection

[spacer]

BUOC: Oper ating mode

014 000

1: Without ARC
[spacer]

Fig. 3-152, (p. 3-207)

Setting for the BUOC protection operating mode.


Parameter
Default

Switch on to fault
protection

Address
Min

Max

Unit

SOT F : Ge ne ral e nable US ER

011 068

0: No
[spacer]

Logic Diagram

Fig. 3-154, (p. 3-210)

Enabling or disabling the switch on to fault (short circuit) protection.


Parameter
Default

Protective signaling

Address
Min

Max

7-102

Logic Diagram

PSIG: General enable USE R


0: No

[spacer]

Unit

015 004

Fig. 3-156, (p. 3-213)

Disabling or enabling protective signaling.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default

Auto-reclosing
control

Address
Min

Max

Unit

Logic Diagram

ARC: General e nable USE R

015 060

0: No

Fig. 3-186, (p. 3-242)

[spacer]

Disabling or enabling auto-reclosing control.

[spacer]

ARC: C ontrol via US E R

000 107

1: Yes
[spacer]

Setting this parameter to No enables selection of ARC operating mode via binary
signal inputs. This is possible only if the required binary signal inputs have been
configured.

[spacer]

ARC: Fct.as sgn. tLOG IC

015 033

060 000: MAIN: Without function


[spacer]

Function assignment to tLOGIC.


Parameter
Default

Automatic
synchronism check

Min

Max

Unit

Logic Diagram

ASC: General enable US ER


0: No

[spacer]

Address

018 000

Fig. 3-207, (p. 3-274)

Enabling or disabling the automatic synchronism check.

P437/EN M/R-11-A // P437311650

7-103

P437

7 Settings

Parameter
Default

Ground fault (shortcircuit) protection

Address
Min

Max

Unit

Logic Diagram

GFS C: General enable USER

018 060

0: No

Fig. 3-220, (p. 3-291)

[spacer]

Disabling or enabling ground fault (short-circuit) protection.

[spacer]

GFS C: Fct.as sign. bl ock ing

006 020

060 000: MAIN: Without function

Fig. 3-221, (p. 3-293)

[spacer]

Select those binary signals that will if present block the GFSC protection.

[spacer]

GFS C: Evaluat ion VNG

002 136

1: Calculated

Fig. 3-221, (p. 3-293)


Fig. 3-222, (p. 3-293)

[spacer]

Setting how the GFSC protection will determine the neutral-point displacement
voltage: It will either be internally calculated from the three measured phase-toground voltages, or measured from the open-delta VT.

[spacer]

GFS C: Virtual curr e nt pol.

006 009

0: No
[spacer]

Set to Yes if you want the device to apply virtual current polarization, i.e.
calculate the polarizing voltage as sum of the 2 healthy phase voltages. The
default is No to provide backwards compatibility.

[spacer]

GFS C: Comp . reac tance X0


0 | 0 (For MAIN: Inom
device=1.0A | 5.0A)

0|0

002 135

200 | 40

[spacer]

Setting of cross-polarization parameter X0 (see section GFSC, Improved


directional measurement for series compensated line applications).

[spacer]

GFS C: IN>
0.050

018 063

0.002

0.500

Inom

Fig. 3-223, (p. 3-294)

[spacer]

Setting for the operate value of the residual current.

[spacer]

GFS C: VNG>
0.030

018 062

0.010

0.500

Vnom

Fig. 3-223, (p. 3-294)

[spacer]

Setting for the operate value of the neutral-point displacement voltage.

[spacer]

GFS C: Angle phi N


0

018 061

-90

Fig. 3-235, (p. 3-307)

[spacer]

Setting for the position of the straight line separating forward and backward
(reverse) directions.

[spacer]

GFS C: St art. oper . de lay


1.00

[spacer]

7-104

0.00

018 064

10.00

Fig. 3-223, (p. 3-294)

Setting for the operate delay of starting.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

GFS C: St art. re le as. de lay


0.00

0.00

018 065

10.00

[spacer]

Setting for the release delay of the starting.

[spacer]

GFS C: t1 (forward)
Blocked

Fig. 3-223, (p. 3-294)

018 066

0.00

60.00

Fig. 3-235, (p. 3-307)

[spacer]

Setting for the operate delay of the trip signal in the event of a forward
decision.

[spacer]

GFS C: t2 (backward)
Blocked

018 067

0.00

60.00

Fig. 3-235, (p. 3-307)

[spacer]

Setting for the operate delay of the trip signal in the event of a backward
(reverse) decision.

[spacer]

GFS C: t3 (non-dir ect io nal )


Blocked

0.00

018 068

60.00

Fig. 3-235, (p. 3-307)

[spacer]

Setting for the operate delay of the non-directional trip signal.

[spacer]

GFS C: Crit eria tS acti ve

018 071

1: forward

Fig. 3-235, (p. 3-307)

[spacer]

This setting defines the direction of time-voltage protection tripping.

[spacer]

GFS C: Operatin g mode t S

018 080

1: VNG-dependent

Fig. 3-229, (p. 3-301)

[spacer]

This setting specifies whether the voltage-dependent or current-dependent


tripping time characteristic shall apply.

[spacer]

GFS C: Ire f,N


Blocked

018 076

0.01

[spacer]

Setting for the reference current.

[spacer]

GFS C: Charact e r is tic N

0.80

Inom

018 078

0: Definite Time

Fig. 3-234, (p. 3-306)

[spacer]

Setting for the tripping characteristic.

[spacer]

GFS C: Factor k t,N


1.00

[spacer]

Fig. 3-234, (p. 3-306)

018 077

0.05

10.00

Fig. 3-234, (p. 3-306)

Setting for the starting characteristic factor kP.

P437/EN M/R-11-A // P437311650

7-105

P437

7 Settings

Parameter
Default

Ground fault (shortcircuit) protection


signaling

Address
Min

Max

Unit

Logic Diagram

GSCSG: General e nabl e USE R

023 069

0: No

Fig. 3-238, (p. 3-310)

[spacer]

Disabling or enabling ground fault (short-circuit) protection signaling.

[spacer]

GSCSG: Fct.assig n. bloc king

002 180

060 000: MAIN: Without function

Fig. 3-239, (p. 3-313)

[spacer]

Select those binary signals that will if present block the GFSC protection.

[spacer]

GSCSG: C hanne l mode

023 078

1: Independent channel

Fig. 3-239, (p. 3-313)


Fig. 3-241, (p. 3-315)
Fig. 3-243, (p. 3-317)
Fig. 3-244, (p. 3-318)
Fig. 3-245, (p. 3-319)
Fig. 3-247, (p. 3-321)

[spacer]

This setting specifies whether GSCSG and PSIG operate with independent
communication channels or with a common communication channel.
Note: Operation with a common communication channel is only possible, if the
same operating mode is set for both PSIG and GSCSG. The correct assignment
of signals to the functions must be done by setting the time delays
appropriately.

[spacer]

GSCSG: Op erating mode

023 079

1: Signal comp. release

Fig. 3-243, (p. 3-317)


Fig. 3-244, (p. 3-318)

[spacer]

Setting for the operating mode of ground fault (short-circuit) protection


signaling.

[spacer]

GSCSG: T rip mod e

023 088

1: 1/3-pole trip w.HSR

Fig. 3-246, (p. 3-320)

[spacer]

This setting specifies whether there shall be a single-pole or three-pole trip and
whether an HSR shall be triggered.

[spacer]

GSCSG: T rip ping t ime


1.00

0.00

023 075

10.00

Fig. 3-240, (p. 3-314)

[spacer]

Setting for the delay of the send signal (of the signal comparison release
scheme) and the trip signal. This delay shall be used for coordinating GSCSG
with the other protection functions.

[spacer]

GSCSG: R eleas e t ime se nd


0.25

0.00

023 076

10.00

Fig. 3-243, (p. 3-317)


Fig. 3-244, (p. 3-318)
Fig. 3-248, (p. 3-322)

[spacer]

7-106

This setting specifies extension of the send signal after starting of ground fault
(short-circuit) protection has dropped out.
P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

GSCSG: t Block
1.00

023 077

0.00

10.00

Fig. 3-242, (p. 3-315)

[spacer]

Setting for the transient blocking time of ground fault (short-circuit) protection
signaling in the event of a change in fault direction.

[spacer]

GSCSG: Echo on rec eiv e

023 080

0: No
[spacer]

Fig. 3-247, (p. 3-321)

This setting determines whether ground fault (short-circuit) protection signaling


operates with or without echo.
Note: Use of the echo only makes sense if the signal comparison release
scheme has been selected as the operating mode.

[spacer]

GSCSG: Op erate de lay ec ho


0.20

0.00

10.00

023 081

[spacer]

Setting for the operate delay of the echo pulse.

[spacer]

GSCSG: Puls e d urat ion echo


0.05

0.00

[spacer]

Setting for echo pulse duration.

[spacer]

GSCSG: t Block echo


0.05

10.00

Fig. 3-247, (p. 3-321)

023 082

Fig. 3-247, (p. 3-321)

023 083

0.00

10.00

Fig. 3-247, (p. 3-321)

[spacer]

Setting for the transient blocking time of the echo signal in the event of a
change in fault direction.

[spacer]

GSCSG: W eak in fe ed tr ip

023 084

0: No
[spacer]

Fig. 3-245, (p. 3-319)

This setting determines whether a trip signal will be issued when the weakinfeed logic is triggered.
Note: Use of the weak-infeed logic only makes sense if the signal comparison
release scheme has been selected as the operating mode.

[spacer]

GSCSG: Op .delay weak i nfe e d


0.20

0.00

10.00

023 087

[spacer]

Setting for the operate delay of weak-infeed logic.

[spacer]

GSCSG: Block. sig. nondir .


0: No

Fig. 3-245, (p. 3-319)

023 089

Fig. 3-244, (p. 3-318)

[spacer]

This setting specifies whether the blocking signal will be transmitted only in the
event of a backward (reverse) decision by ground fault (short-circuit) protection
or whether it will be transmitted as long as there is no forward decision.

[spacer]

GSCSG: Frequency moni toring


0: No

[spacer]

023 085

Fig. 3-241, (p. 3-315)

This setting defines whether failure of frequency transmission will be monitored.

P437/EN M/R-11-A // P437311650

7-107

P437

7 Settings

Parameter
Default

Definite-time over
current protection

Address
Min

Max

Unit

DTOC: Gener al e nable USE R

031 068

0: No
[spacer]

Logic Diagram

Fig. 3-249, (p. 3-323)

Enable/disable the definite-time overcurrent protection function.


Parameter
Default

Address
Min

Max

Unit

Logic Diagram

Inverse-time overcur IDMT: Gene ral e nable US E R


rent protection

017 096

0: No
[spacer]

Fig. 3-263, (p. 3-338)

Enabling or disabling the inverse-time overcurrent protection function.


Parameter
Default

Thermal overload
protection

Address
Min

Max

Unit

THER M : Gene r al e nabl e US E R

022 050

0: No

Fig. 3-274, (p. 3-351)

[spacer]

Disabling or enabling thermal overload protection.

[spacer]

THER M : R e lat ive re pl ic a

022 064

1: Yes
[spacer]

Logic Diagram

Fig. 3-277, (p. 3-357)

Disabling or enabling the Relative replica mode of operation.


Note that it is not permitted to enable both Absolute replica and Relative replica
modes.

[spacer]

THER M : Absolut e r eplica

022 065

0: No
[spacer]

Fig. 3-277, (p. 3-357)

Enabling or disabling the Absolute replica mode of operation.


Note that it is not permitted to enable both Absolute replica and Relative replica
modes.
Parameter
Default

Address
Min

Max

Unit

Logic Diagram

Time-voltage protec V<>: General enable US ER


tion
0: No
[spacer]

7-108

023 030

Fig. 3-279, (p. 3-359)

Disabling or enabling time-voltage protection.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default

Address
Min

Max

Unit

Logic Diagram

f<> : Gene ral e nable USER


Over-/
underfrequency pro
tection

023 031

0: No

Fig. 3-293, (p. 3-373)

[spacer]

Disabling or enabling over-/underfrequency protection.

[spacer]

f<> : S election me as. v olt

018 202

4: Voltage A-B

Fig. 3-294, (p. 3-374)

[spacer]

Setting for the voltage that shall be used for frequency measurement.

[spacer]

f<> : Evaluation ti me
5

018 201

Periods

Fig. 3-295, (p. 3-375)

[spacer]

Setting for the evaluation time. The operate conditions must be met for the
duration of the set evaluation time in order for a signal to be issued.

[spacer]

f<> : Undervolt. block . V<


0.65

[spacer]

0.20

018 200

1.00

Vnom(/3) Fig. 3-295, (p. 3-375)

Setting for the threshold of undervoltage blocking. If the voltage falls below this
threshold, the over-/underfrequency protection function will be blocked.
Parameter
Default

Power directional
protection

Min

Max

Unit

Logic Diagram

P<>: General e nable USER


0: No

[spacer]

Address

014 220

Fig. 3-298, (p. 3-380)

Disabling or enabling the power directional protection function.

P437/EN M/R-11-A // P437311650

7-109

P437

7 Settings

Parameter
Default

Circuit breaker
failure protection

Address
Min

Max

Unit

Logic Diagram

CBF: Gener al e nable USE R

022 080

0: No

Fig. 3-312, (p. 3-396)

[spacer]

Disabling or enabling circuit breaker failure protection.

[spacer]

CBF: S tart with man. tr ip

022 154

0: No

Fig. 3-316, (p. 3-401)

[spacer]

Setting that permit a manual trip signal to also be used as a start criterion.

[spacer]

CBF: Fct.as signm. CBAux.

022 159

060 000: MAIN: Without function

Fig. 3-316, (p. 3-401)

[spacer]

Selection of trip signals assigned to Gen. trip command 1 for which, in


addition to current flow monitoring, status signals from CB auxiliary contacts are
evaluated.

[spacer]

CBF: I <
1.00

022 160

0.05

20.00

Inom

Fig. 3-314, (p. 3-398)


Fig. 3-316, (p. 3-401)
Fig. 3-320, (p. 3-404)
Fig. 3-321, (p. 3-405)

[spacer]

Setting for the threshold to detect a break in current flow.

[spacer]

CBF: Evaluation IN

022 184

0: Without

Fig. 3-314, (p. 3-398)

[spacer]

Select whether the measured or the calculated residual current shall be used for
residual current monitoring function. This choice is only possible when a
measuring input for the residual current is available, otherwise the internally
derived value of the residual current is always used, regardless of the setting.

[spacer]

CBF: I N<
1.00

022 180

0.05

20.00

Inom

[spacer]

Setting of the comparator threshold for residual current monitoring function.

[spacer]

CBF: T r ip 1p

022 163

0: No

Fig. 3-317, (p. 3-402)

[spacer]

Setting to Yes allows 1-pole monitoring and re-tripping of the CB. Then a 1-pole
general trip triggers the 1-pole startup of CBF (see section CBF 1-pole operating
mode).

[spacer]

CBF: t 1 1p
Blocked

022 164

0.00

100.00

[spacer]

Setting 1st CBF timer stage to 1-pole operating mode.

[spacer]

CBF: t 1 3p
0.15

[spacer]

7-110

022 165

0.00

100.00

Fig. 3-317, (p. 3-402)

Setting the 1st CBF timer stage to 3-pole operating mode.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

CBF: t 2
0.25

022 166

0.00

100.00

[spacer]

Setting for the 2nd CBF timer stage.

[spacer]

CBF: M in.dur. tr ip cmd. t1


0.25

0.10

Fig. 3-317, (p. 3-402)

022 167

10.00

Fig. 3-318, (p. 3-403)

[spacer]

Setting the 1st timer stage for minimum duration of trip command.

[spacer]

CBF: M in.dur. tr ip cmd. t2


0.25

0.10

022 168

10.00

Fig. 3-318, (p. 3-403)

[spacer]

Setting the 2nd timer stage for minimum duration of trip command.

[spacer]

CBF: Latching trip cmd.t 1

022 169

0: No

Fig. 3-318, (p. 3-403)

[spacer]

The 1st timer stage trip command, set to latch mode, will remain active until
reset by operating parameters or through an appropriately configured binary
signal input.

[spacer]

CBF: Latching trip cmd.t 2

022 170

0: No

Fig. 3-318, (p. 3-403)

[spacer]

The 2nd timer stage trip command, set to latch mode, will remain active until
reset by operating parameters or through an appropriately configured binary
signal input.

[spacer]

CBF: De lay/s tart ing t rig.


0.00

0.00

022 155

100.00

Fig. 3-319, (p. 3-404)

[spacer]

The signal CB F: Trip si gnal is issued when this timer stage's time duration
has elapsed.

[spacer]

CBF: De lay/f ault beh. C B


0.12

0.00

022 171

100.00

Fig. 3-320, (p. 3-404)

[spacer]

If during this delay time period the circuit breaker does not provide a signal from
its auxiliary contacts that it is closed, then faults behind the CB are recognized
through the current criterion (see section Fault behind CB protection).

[spacer]

CBF: De lay/C B s ync.supe rv


Blocked

[spacer]

0.00

022 172

100.00

Fig. 3-321, (p. 3-405)

Setting for the time delay to bridge circuit breaker operate times during CB
synchronization supervision.

P437/EN M/R-11-A // P437311650

7-111

P437

7 Settings

Parameter
Default

Address
Min

Max

Unit

Logic Diagram

CBM: Gener al e nable USE R


Circuit breaker
condition monitoring

022 010

0: No

Fig. 3-322, (p. 3-406)

[spacer]

Enabling or disabling circuit breaker monitoring.

[spacer]

CBM: S ig. as g. trip cmd.

022 152

060 000: MAIN: Without function


[spacer]

Using the setting for external devices the trip command issued by the control
function may be linked to the trip command 1 issued by the protection by
assigning the trip command issued by the control function by this parameter.

[spacer]

CBM: Op er ating mode

022 007

3: CB sig. EXT or trip

Fig. 3-325, (p. 3-412)

[spacer]

This setting defines starting criteria for circuit breaker monitoring. To evaluate
all trip commands issued by the protection device With trip cmd. only must be
selected. For further evaluation of operational trip commands the additional CB
auxiliary contact CB sig. EXT or trip is used.

[spacer]

CBM: I nom,CB
2000

022 012

65000

[spacer]

Setting for the CB nominal current.

[spacer]

CBM: Per m . CB op. Inom,CB


30000

Fig. 3-325, (p. 3-412)

022 013

65000

Fig. 3-325, (p. 3-412)

[spacer]

Setting for the maximum number of CB operations at nominal current.

[spacer]

CBM: M e d. curr. I t ri p,CB


Blocked

[spacer]

022 014

65000

Fig. 3-325, (p. 3-412)

Setting for the average CB disconnection current.


Note: In general valid only for pneumatically operated CBs.

[spacer]

CBM: Per m . CB op. Imed, CB


Blocked

[spacer]

022 015

65000

Fig. 3-325, (p. 3-412)

Setting for the maximum number of CB operations at average disconnection


(ruptured) current.
Note: In general valid only for pneumatically operated CBs.

[spacer]

CBM: M ax . curr. It r ip,CB


63000

022 016

65000

Fig. 3-325, (p. 3-412)

[spacer]

Setting for the maximum CB disconnection (ruptured) current.

[spacer]

CBM: Per m . CB op. Imax,CB


20

[spacer]

7-112

65000

022 017

Fig. 3-325, (p. 3-412)

Setting for the maximum number of CB operations permitted at maximum CB


disconnection (ruptured) current.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

CBM: No. CB ope rations >


10000

022 019

65000

Fig. 3-327, (p. 3-413)

[spacer]

Setting for the maximum number of mechanical CB switching operations.

[spacer]

CBM: R e main No. CB op. <


1000

022 020

65000

Fig. 3-326, (p. 3-413)

[spacer]

Setting for the warning stage with the number of remaining CB operations at CB
nominal current.

[spacer]

CBM: Itr ip >


1000

022 022

65000

Inom,CB

[spacer]

Setting for the warning stage with the accumulated CB disconnection (ruptured)
current values.

[spacer]

CBM: Itr ip **2>


1000

022 081

65000

Inom,CB**
2

[spacer]

Setting for the warning stage with the accumulated CB disconnection (ruptured)
current values to the second power.

[spacer]

CBM: I* t>
1000.0

022 096

1.0

4000.0

kAs

[spacer]

Setting for the warning stage with the sum of the current-time integrals of the
CB disconnection (ruptured) current values

[spacer]

CBM: C orr. acqu.t ime trip


0.000

0.000

007 249

0.200

Fig. 3-325, (p. 3-412)

[spacer]

Correction of the time tolerances permissible for leading or lagging CB auxiliary


contacts in case of a triggering by the open command.

[spacer]

CBM: C orr. acqui s. t ime


0.000

[spacer]

-0.200

022 018

0.200

Fig. 3-325, (p. 3-412)

Correction of the time tolerances permissible for leading or lagging CB auxiliary


contacts in case of a triggering by the position signal issued by the CB auxiliary
contacts.

P437/EN M/R-11-A // P437311650

7-113

P437

7 Settings

Parameter
Default

Limit value
monitoring

Address
Min

Max

Unit

Logic Diagram

LIMIT : Ge neral e nable US ER

014 010

0: No

Fig. 3-333, (p. 3-420)

[spacer]

Disabling or enabling limit value monitoring.

[spacer]

LIMIT : I>
1.10

014 004

0.10

2.40

Inom

Fig. 3-329, (p. 3-416)

[spacer]

Setting for the operate value of the first overcurrent stage for limit value
monitoring.

[spacer]

LIMIT : I> >


1.20

014 020

0.10

2.40

Inom

Fig. 3-329, (p. 3-416)

[spacer]

Setting for the operate value of the second overcurrent stage for limit value
monitoring.

[spacer]

LIMIT : tI>
1

014 031

1000

Fig. 3-329, (p. 3-416)

[spacer]

Setting for the operate delay of the first overcurrent stage of limit value
monitoring.

[spacer]

LIMIT : tI>>
1

014 032

1000

Fig. 3-329, (p. 3-416)

[spacer]

Setting for the operate delay of the second overcurrent stage of limit value
monitoring.

[spacer]

LIMIT : I<
0.90

014 021

0.10

2.40

Inom

Fig. 3-329, (p. 3-416)

[spacer]

Setting for the operate value of the first undercurrent stage of limit value
monitoring.

[spacer]

LIMIT : I< <


0.80

014 022

0.10

2.40

Inom

Fig. 3-329, (p. 3-416)

[spacer]

Setting for the operate value of the second undercurrent stage of limit value
monitoring.

[spacer]

LIMIT : tI<
1

014 033

1000

Fig. 3-329, (p. 3-416)

[spacer]

Setting for the operate delay of the first undercurrent stage of limit value
monitoring.

[spacer]

LIMIT : tI<<
1

[spacer]

7-114

014 034

1000

Fig. 3-329, (p. 3-416)

Setting for the operate delay of the second undercurrent stage of limit value
monitoring.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

LIMIT : VPG>
1.10

014 023

0.10

2.50

Vnom/3

Fig. 3-330, (p. 3-417)

[spacer]

Setting for the operate value of overvoltage stage VPG> of limit value
monitoring.

[spacer]

LIMIT : VPG>>
1.20

014 024

0.10

2.50

Vnom/3

Fig. 3-330, (p. 3-417)

[spacer]

Setting for the operate value of overvoltage stage VPG>> of limit value
monitoring.

[spacer]

LIMIT : tVPG>
1

014 035

1000

Fig. 3-330, (p. 3-417)

[spacer]

Setting for the operate delay of overvoltage stage VPG> of limit value
monitoring.

[spacer]

LIMIT : tVPG>>
1

014 036

1000

Fig. 3-330, (p. 3-417)

[spacer]

Setting for the operate delay of overvoltage stage VPG>> of limit value
monitoring.

[spacer]

LIMIT : VPG<
0.90

014 025

0.10

2.50

Vnom/3

Fig. 3-330, (p. 3-417)

[spacer]

Setting for the operate value of undervoltage stage VPG< of limit value
monitoring.

[spacer]

LIMIT : VPG<<
0.80

014 026

0.10

2.50

Vnom/3

Fig. 3-330, (p. 3-417)

[spacer]

Setting for the operate value of undervoltage stage VPG<< of limit value
monitoring.

[spacer]

LIMIT : tVPG<
1

014 037

1000

Fig. 3-330, (p. 3-417)

[spacer]

Setting for the operate delay of undervoltage stage VPG< of limit value
monitoring.

[spacer]

LIMIT : tVPG<<
1

014 038

1000

Fig. 3-330, (p. 3-417)

[spacer]

Setting for the operate delay of undervoltage stage VPG<< of limit value
monitoring.

[spacer]

LIMIT : VPP>
1.10

[spacer]

014 027

0.10

1.50

Vnom

Fig. 3-330, (p. 3-417)

Setting for the operate value of overvoltage stage VPP> of limit value
monitoring.

P437/EN M/R-11-A // P437311650

7-115

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

LIMIT : VPP>>
1.20

014 028

0.10

1.50

Vnom

Fig. 3-330, (p. 3-417)

[spacer]

Setting for the operate value of overvoltage stage VPP>> of limit value
monitoring.

[spacer]

LIMIT : tVPP>
1

014 039

1000

Fig. 3-330, (p. 3-417)

[spacer]

Setting for the operate delay of overvoltage stage VPP> of limit value
monitoring.

[spacer]

LIMIT : tVPP>>
1

014 040

1000

Fig. 3-330, (p. 3-417)

[spacer]

Setting for the operate delay of overvoltage stage VPP>> of limit value
monitoring.

[spacer]

LIMIT : VPP<
0.90

014 029

0.10

1.50

Vnom

Fig. 3-330, (p. 3-417)

[spacer]

Setting for the operate value of undervoltage stage VPP< of limit value
monitoring.

[spacer]

LIMIT : VPP<<
0.80

014 030

0.10

1.50

Vnom

Fig. 3-330, (p. 3-417)

[spacer]

Setting for the operate value of undervoltage stage VPP<< of limit value
monitoring.

[spacer]

LIMIT : tVPP<
1

014 041

1000

Fig. 3-330, (p. 3-417)

[spacer]

Setting for the operate delay of undervoltage stage VPP< of limit value
monitoring.

[spacer]

LIMIT : tVPP<<
1

014 042

1000

Fig. 3-330, (p. 3-417)

[spacer]

Setting for the operate delay of undervoltage stage VPP<< of limit value
monitoring.

[spacer]

LIMIT : VNG>
0.050

014 043

0.010

1.000

Vnom

Fig. 3-331, (p. 3-418)

[spacer]

Setting for the operate value of overvoltage stage VNG> of limit value
monitoring.

[spacer]

LIMIT : VNG>>
0.100

[spacer]

7-116

014 044

0.010

1.000

Vnom

Fig. 3-331, (p. 3-418)

Setting for the operate value of overvoltage stage VNG>> of limit value
monitoring.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

LIMIT : tVNG>
1

014 045

1000

Fig. 3-331, (p. 3-418)

[spacer]

Setting for the operate delay of overvoltage stage VNG> of limit value
monitoring.

[spacer]

LIMIT : tVNG>>
1

014 046

1000

Fig. 3-331, (p. 3-418)

[spacer]

Setting for the operate delay of overvoltage stage VNG>> of limit value
monitoring.

[spacer]

LIMIT : Vref >


1.10

042 144

0.10

2.50

Vnom

Fig. 3-333, (p. 3-420)

[spacer]

Setting for the operate value of overvoltage stage Vref> for limit value
monitoring.

[spacer]

LIMIT : Vref >>


1.20

042 145

0.10

2.50

Vnom

Fig. 3-333, (p. 3-420)

[spacer]

Setting for the operate value of overvoltage stage Vref>> for limit value
monitoring.

[spacer]

LIMIT : tVref>
1

042 148

1000

Fig. 3-333, (p. 3-420)

[spacer]

Setting for the operate delay of overvoltage stage Vref> for limit value
monitoring.

[spacer]

LIMIT : tVref>>
1

042 149

1000

Fig. 3-333, (p. 3-420)

[spacer]

Setting for the operate delay of overvoltage stage Vref>> for limit value
monitoring.

[spacer]

LIMIT : Vref <


0.90

042 146

0.10

2.50

Vnom

Fig. 3-333, (p. 3-420)

[spacer]

Setting for the operate value of undervoltage stage Vref< for limit value
monitoring.

[spacer]

LIMIT : Vref <<


0.80

042 147

0.10

2.50

Vnom

Fig. 3-333, (p. 3-420)

[spacer]

Setting for the operate value of undervoltage stage Vref<< for limit value
monitoring.

[spacer]

LIMIT : tVref<
1

[spacer]

042 150

1000

Fig. 3-333, (p. 3-420)

Setting for the operate delay of undervoltage stage Vref< for limit value
monitoring.

P437/EN M/R-11-A // P437311650

7-117

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

LIMIT : tVref<<
1

042 151

1000

Fig. 3-333, (p. 3-420)

[spacer]

Setting for the operate delay of undervoltage stage Vref<< for limit value
monitoring.

[spacer]

LIMIT : IDC,lin>
Blocked

014 110

0.100

1.100

IDC,nom

Fig. 3-332, (p. 3-419)

[spacer]

Setting for the operate value IDC,lin> for monitoring the linearized direct
current.

[spacer]

LIMIT : IDC,lin>>
Blocked

014 111

0.100

1.100

IDC,nom

Fig. 3-332, (p. 3-419)

[spacer]

Setting for the operate value IDC,lin>> for monitoring the linearized direct
current.

[spacer]

LIMIT : tIDC,lin>
Blocked

014 112

0.00

20.00

Fig. 3-332, (p. 3-419)

[spacer]

Setting for the operate delay of overcurrent stage IDC,lin>.

[spacer]

LIMIT : tIDC,lin>>
Blocked

014 113

0.00

20.00

Fig. 3-332, (p. 3-419)

[spacer]

Setting for the operate delay of overcurrent stage IDC,lin>>.

[spacer]

LIMIT : IDC,lin<
Blocked

014 114

0.100

1.100

IDC,nom

Fig. 3-332, (p. 3-419)

[spacer]

Setting for the operate value IDC,lin< for monitoring the linearized direct
current.

[spacer]

LIMIT : IDC,lin<<
Blocked

014 115

0.100

1.100

IDC,nom

Fig. 3-332, (p. 3-419)

[spacer]

Setting for the operate value IDC,lin<< for monitoring the linearized direct
current.

[spacer]

LIMIT : tIDC,lin<
Blocked

014 116

0.00

20.00

Fig. 3-332, (p. 3-419)

[spacer]

Setting for the operate delay of undercurrent stage IDC,lin<.

[spacer]

LIMIT : tIDC,lin<<
Blocked

014 117

0.00

20.00

Fig. 3-332, (p. 3-419)

[spacer]

Setting for the operate delay of undercurrent stage IDC,lin<<.

[spacer]

LIMIT : T>
200

[spacer]

7-118

014 100

-20

200

Fig. 3-334, (p. 3-421)

Setting for the operate value of temperature monitoring T>.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

LIMIT : T>>
200

014 101

-20

200

Fig. 3-334, (p. 3-421)

[spacer]

Setting for the operate value of temperature monitoring T>>.

[spacer]

LIMIT : tT >
Blocked

014 103

1000

Fig. 3-334, (p. 3-421)

[spacer]

Setting for the operate delay of temperature monitoring T>.

[spacer]

LIMIT : tT >>
Blocked

014 104

1000

Fig. 3-334, (p. 3-421)

[spacer]

Setting for the operate delay of temperature monitoring T>>.

[spacer]

LIMIT : T<
-20

014 105

-20

200

Fig. 3-334, (p. 3-421)

[spacer]

Setting for the operate value of temperature monitoring T<.

[spacer]

LIMIT : T<<
-20

014 106

-20

200

Fig. 3-334, (p. 3-421)

[spacer]

Setting for the operate value of temperature monitoring T<<.

[spacer]

LIMIT : tT <
Blocked

014 107

1000

Fig. 3-334, (p. 3-421)

[spacer]

Setting for the operate delay of temperature monitoring T<.

[spacer]

LIMIT : tT <<
Blocked

[spacer]

014 108

1000

Fig. 3-334, (p. 3-421)

Setting for the operate delay of temperature monitoring T<<.

P437/EN M/R-11-A // P437311650

7-119

P437

7 Settings

Parameter
Default

Address
Min

Max

Unit

Logic Diagram

Programmable Logic LOGIC: General enable USE R

031 099

0: No
[spacer]

Enable/disable the logic function.

[spacer]

LOGIC: Se t 1 US ER

Fig. 3-336, (p. 3-424)

034 030

0: No
[spacer]

Fig. 3-335, (p. 3-423)

LOGIC: Se t 2 US ER

034 031

0: No
[spacer]

LOGIC: Se t 3 US ER

034 032

0: No
[spacer]

LOGIC: Se t 4 US ER

034 033

0: No
[spacer]

LOGIC: Se t 5 US ER

034 034

0: No
[spacer]

LOGIC: Se t 6 US ER

034 035

0: No
[spacer]

LOGIC: Se t 7 US ER

034 036

0: No
[spacer]

LOGIC: Se t 8 US ER

034 037

0: No
[spacer]

These settings define the static input conditions for the logic function.

[spacer]

LOGIC: Fct.as s ignm. outp. 1

030 000

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 2


060 000: MAIN: Without function

[spacer]

Fig. 3-336, (p. 3-424)

LOGIC: Fct.as s ignm. outp. 3

030 004

s
030 008

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 4

030 012

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 5

030 016

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 6

030 020

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 7

030 024

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 8

030 028

060 000: MAIN: Without function

7-120

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

LOGIC: Fct.as s ignm. outp. 9

Unit

Logic Diagram
030 032

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 10

030 036

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 11

030 040

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 12

030 044

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 13

030 048

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 14

030 052

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 15

030 056

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 16

030 060

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 17

030 064

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 18

030 068

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 19

030 072

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 20

030 076

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 21

030 080

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 22

030 084

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 23

030 088

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 24

030 092

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 25

030 096

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 26

031 000

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 27

031 004

060 000: MAIN: Without function

P437/EN M/R-11-A // P437311650

7-121

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

LOGIC: Fct.as s ignm. outp. 28

Unit

Logic Diagram
031 008

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 29

031 012

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 30

031 016

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 31

031 020

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 32

031 024

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 33

030 100

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 34

030 104

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 35

030 108

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 36

030 112

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 37

030 116

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 38

030 120

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 39

030 124

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 40

030 128

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 41

030 132

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 42

030 136

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 43

030 140

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 44

030 144

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 45

030 148

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 46

030 152

060 000: MAIN: Without function

7-122

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

LOGIC: Fct.as s ignm. outp. 47

Unit

Logic Diagram
030 156

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 48

030 160

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 49

030 164

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 50

030 168

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 51

030 172

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 52

030 176

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 53

030 180

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 54

030 184

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 55

030 188

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 56

030 192

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 57

030 196

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 58

030 200

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 59

030 204

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 60

030 208

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 61

030 212

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 62

030 216

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 63

030 220

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 64

030 224

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 65

046 000

060 000: MAIN: Without function

P437/EN M/R-11-A // P437311650

7-123

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

LOGIC: Fct.as s ignm. outp. 66

Unit

Logic Diagram
045 004

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 67

045 008

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 68

045 012

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 69

045 016

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 70

045 020

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 71

045 024

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 72

045 028

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 73

045 032

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 74

045 036

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 75

045 040

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 76

045 044

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 77

045 048

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 78

045 052

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 79

045 056

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 80

045 060

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 81

045 064

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 82

045 068

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 83

045 072

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 84

045 076

060 000: MAIN: Without function

7-124

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

LOGIC: Fct.as s ignm. outp. 85

Unit

Logic Diagram
045 080

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 86

045 084

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 87

045 088

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 88

045 092

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 89

045 096

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 90

045 100

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 91

045 104

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 92

045 108

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 93

045 112

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 94

045 116

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 95

045 120

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 96

045 124

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 97

045 128

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 98

045 132

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm. outp. 99

045 136

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 00

045 140

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 01

045 144

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 02

045 148

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 03

045 152

060 000: MAIN: Without function

P437/EN M/R-11-A // P437311650

7-125

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

LOGIC: Fct.as s ignm.outp.1 04

Unit

Logic Diagram
045 156

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 05

045 160

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 06

045 164

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 07

045 168

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 08

045 172

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 09

045 176

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 10

045 180

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 11

045 184

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 12

045 188

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 13

045 192

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 14

045 196

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 15

045 200

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 16

045 204

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 17

045 208

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 18

045 212

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 19

045 216

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 20

045 220

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 21

045 224

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 22

045 228

060 000: MAIN: Without function

7-126

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

LOGIC: Fct.as s ignm.outp.1 23

045 232

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 24

045 236

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 25

045 240

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 26

045 244

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 27

045 248

060 000: MAIN: Without function


[spacer]

LOGIC: Fct.as s ignm.outp.1 28

045 252

060 000: MAIN: Without function


[spacer]

These settings assign functions to the outputs.

[spacer]

LOGIC: Op. m ode t output 1


0: Without timer stage

[spacer]

LOGIC: Op. m ode t output 2

030 001

Fig. 3-336, (p. 3-424)


030 005

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 3

030 009

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 4

030 013

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 5

030 017

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 6

030 021

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 7

030 025

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 8

030 029

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 9

030 033

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 1 0

030 037

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 1 1

030 041

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 1 2

030 045

0: Without timer stage

P437/EN M/R-11-A // P437311650

7-127

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

LOGIC: Op. m ode t output 1 3

Unit

Logic Diagram
030 049

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 1 4

030 053

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 1 5

030 057

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 1 6

030 061

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 1 7

030 065

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 1 8

030 069

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 1 9

030 073

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 2 0

030 077

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 2 1

030 081

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 2 2

030 085

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 2 3

030 089

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 2 4

030 093

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 2 5

030 097

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 2 6

031 001

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 2 7

031 005

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 2 8

031 009

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 2 9

031 013

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 3 0

031 017

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 3 1

031 021

0: Without timer stage

7-128

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

LOGIC: Op. m ode t output 3 2

Unit

Logic Diagram
031 025

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 3 3

030 101

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 3 4

030 105

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 3 5

030 109

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 3 6

030 113

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 3 7

030 117

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 3 8

030 121

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 3 9

030 125

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 4 0

030 129

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 4 1

030 133

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 4 2

030 137

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 4 3

030 141

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 4 4

030 145

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 4 5

030 149

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 4 6

030 153

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 4 7

030 157

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 4 8

030 161

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 4 9

030 165

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 5 0

030 169

0: Without timer stage

P437/EN M/R-11-A // P437311650

7-129

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

LOGIC: Op. m ode t output 5 1

Unit

Logic Diagram
030 173

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 5 2

030 177

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 5 3

030 181

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 5 4

030 185

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 5 5

030 189

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 5 6

030 193

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 5 7

030 197

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 5 8

030 201

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 5 9

030 205

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 6 0

030 209

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 6 1

030 213

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 6 2

030 217

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 6 3

030 221

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 6 4

030 225

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 6 5

046 001

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 6 6

045 005

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 6 7

045 009

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 6 8

045 013

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 6 9

045 017

0: Without timer stage

7-130

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

LOGIC: Op. m ode t output 7 0

Unit

Logic Diagram
045 021

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 7 1

045 025

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 7 2

045 029

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 7 3

045 033

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 7 4

045 037

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 7 5

045 041

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 7 6

045 045

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 7 7

045 049

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 7 8

045 053

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 7 9

045 057

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 8 0

045 061

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 8 1

045 065

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 8 2

045 069

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 8 3

045 073

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 8 4

045 077

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 8 5

045 081

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 8 6

045 085

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 8 7

045 089

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 8 8

045 093

0: Without timer stage

P437/EN M/R-11-A // P437311650

7-131

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

LOGIC: Op. m ode t output 8 9

Unit

Logic Diagram
045 097

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 9 0

045 101

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 9 1

045 105

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 9 2

045 109

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 9 3

045 113

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 9 4

045 117

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 9 5

045 121

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 9 6

045 125

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 9 7

045 129

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 9 8

045 133

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 9 9

045 137

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 10 0

045 141

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 10 1

045 145

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 10 2

045 149

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 10 3

045 153

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 10 4

045 157

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 10 5

045 161

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 10 6

045 165

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 10 7

045 169

0: Without timer stage

7-132

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

LOGIC: Op. m ode t output 10 8

Unit

Logic Diagram
045 173

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 10 9

045 177

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 11 0

045 181

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 11 1

045 185

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 11 2

045 189

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 11 3

045 193

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 11 4

045 197

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 11 5

045 201

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 11 6

045 205

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 11 7

045 209

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 11 8

045 213

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 11 9

045 217

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 12 0

045 221

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 12 1

045 225

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 12 2

045 229

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 12 3

045 233

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 12 4

045 237

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 12 5

045 241

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 12 6

045 245

0: Without timer stage

P437/EN M/R-11-A // P437311650

7-133

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

LOGIC: Op. m ode t output 12 7

045 249

0: Without timer stage


[spacer]

LOGIC: Op. m ode t output 12 8

045 253

0: Without timer stage


[spacer]

These settings define the operating modes for the output timer stages.

[spacer]

LOGIC: Tim e t1 output 1


0.00

[spacer]

0.00

030 022

600.00

0.00

030 026

600.00

0.00

030 030

600.00

0.00

030 034

600.00

0.00

030 038

600.00

0.00

030 042

600.00

0.00

030 046

600.00

0.00

030 050

600.00

0.00

030 054

600.00

0.00

030 058

600.00

LOGIC: Tim e t1 output 16


0.00

7-134

LOGIC: Tim e t1 output 15


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 14


0.00

[spacer]

0.00

030 018

LOGIC: Tim e t1 output 13


0.00

[spacer]

LOGIC: Tim e t1 output 12


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 11


0.00

[spacer]

0.00

030 014

LOGIC: Tim e t1 output 10


0.00

[spacer]

LOGIC: Tim e t1 output 9


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 8


0.00

[spacer]

0.00

030 010

LOGIC: Tim e t1 output 7


0.00

[spacer]

LOGIC: Tim e t1 output 6


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 5


0.00

[spacer]

0.00

0.00

Fig. 3-336, (p. 3-424)


030 006

LOGIC: Tim e t1 output 4


0.00

[spacer]

LOGIC: Tim e t1 output 3


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 2


0.00

[spacer]

0.00

030 002

030 062

600.00

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

0.00

030 086

600.00

0.00

030 090

600.00

0.00

030 094

600.00

0.00

030 098

600.00

0.00

031 002

600.00

0.00

031 006

600.00

0.00

031 010

600.00

0.00

031 014

600.00

0.00

031 018

600.00

0.00

031 022

600.00

0.00

031 026

600.00

0.00

030 102

600.00

LOGIC: Tim e t1 output 34


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 33


0.00

[spacer]

0.00

030 082

LOGIC: Tim e t1 output 32


0.00

[spacer]

LOGIC: Tim e t1 output 31


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 30


0.00

[spacer]

0.00

030 078

LOGIC: Tim e t1 output 29


0.00

[spacer]

LOGIC: Tim e t1 output 28


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 27


0.00

[spacer]

0.00

030 074

LOGIC: Tim e t1 output 26


0.00

[spacer]

LOGIC: Tim e t1 output 25


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 24


0.00

[spacer]

0.00

030 070

LOGIC: Tim e t1 output 23


0.00

[spacer]

LOGIC: Tim e t1 output 22


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 21


0.00

[spacer]

0.00

0.00

030 106

600.00

LOGIC: Tim e t1 output 35


0.00

P437/EN M/R-11-A // P437311650

0.00

Logic Diagram
030 066

LOGIC: Tim e t1 output 20


0.00

[spacer]

Unit

LOGIC: Tim e t1 output 19


0.00

[spacer]

Max

LOGIC: Tim e t1 output 18


0.00

[spacer]

Min

LOGIC: Tim e t1 output 17


0.00

[spacer]

Address

030 110

600.00

7-135

P437

7 Settings

Parameter
Default
[spacer]

0.00

030 134

600.00

0.00

030 138

600.00

0.00

030 142

600.00

0.00

030 146

600.00

0.00

030 150

600.00

0.00

030 154

600.00

0.00

030 158

600.00

0.00

030 162

600.00

0.00

030 166

600.00

0.00

030 170

600.00

0.00

030 174

600.00

0.00

030 178

600.00

0.00

030 182

600.00

LOGIC: Tim e t1 output 54


0.00

7-136

LOGIC: Tim e t1 output 53


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 52


0.00

[spacer]

0.00

030 130

LOGIC: Tim e t1 output 51


0.00

[spacer]

LOGIC: Tim e t1 output 50


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 49


0.00

[spacer]

0.00

030 126

LOGIC: Tim e t1 output 48


0.00

[spacer]

LOGIC: Tim e t1 output 47


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 46


0.00

[spacer]

0.00

030 122

LOGIC: Tim e t1 output 45


0.00

[spacer]

LOGIC: Tim e t1 output 44


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 43


0.00

[spacer]

0.00

030 118

LOGIC: Tim e t1 output 42


0.00

[spacer]

LOGIC: Tim e t1 output 41


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 40


0.00

[spacer]

0.00

0.00

Logic Diagram
030 114

LOGIC: Tim e t1 output 39


0.00

[spacer]

Unit

LOGIC: Tim e t1 output 38


0.00

[spacer]

Max

LOGIC: Tim e t1 output 37


0.00

[spacer]

Min

LOGIC: Tim e t1 output 36


0.00

[spacer]

Address

030 186

600.00

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

0.00

030 210

600.00

0.00

030 214

600.00

0.00

030 218

600.00

0.00

030 222

600.00

0.00

030 226

600.00

0.00

046 002

600.00

0.00

045 006

600.00

0.00

045 010

600.00

0.00

045 014

600.00

0.00

045 018

600.00

0.00

045 022

600.00

0.00

045 026

600.00

LOGIC: Tim e t1 output 72


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 71


0.00

[spacer]

0.00

030 206

LOGIC: Tim e t1 output 70


0.00

[spacer]

LOGIC: Tim e t1 output 69


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 68


0.00

[spacer]

0.00

030 202

LOGIC: Tim e t1 output 67


0.00

[spacer]

LOGIC: Tim e t1 output 66


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 65


0.00

[spacer]

0.00

030 198

LOGIC: Tim e t1 output 64


0.00

[spacer]

LOGIC: Tim e t1 output 63


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 62


0.00

[spacer]

0.00

030 194

LOGIC: Tim e t1 output 61


0.00

[spacer]

LOGIC: Tim e t1 output 60


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 59


0.00

[spacer]

0.00

0.00

045 030

600.00

LOGIC: Tim e t1 output 73


0.00

P437/EN M/R-11-A // P437311650

0.00

Logic Diagram
030 190

LOGIC: Tim e t1 output 58


0.00

[spacer]

Unit

LOGIC: Tim e t1 output 57


0.00

[spacer]

Max

LOGIC: Tim e t1 output 56


0.00

[spacer]

Min

LOGIC: Tim e t1 output 55


0.00

[spacer]

Address

045 034

600.00

7-137

P437

7 Settings

Parameter
Default
[spacer]

0.00

045 058

600.00

0.00

045 062

600.00

0.00

045 066

600.00

0.00

045 070

600.00

0.00

045 074

600.00

0.00

045 078

600.00

0.00

045 082

600.00

0.00

045 086

600.00

0.00

045 090

600.00

0.00

045 094

600.00

0.00

045 098

600.00

0.00

045 102

600.00

0.00

045 106

600.00

LOGIC: Tim e t1 output 92


0.00

7-138

LOGIC: Tim e t1 output 91


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 90


0.00

[spacer]

0.00

045 054

LOGIC: Tim e t1 output 89


0.00

[spacer]

LOGIC: Tim e t1 output 88


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 87


0.00

[spacer]

0.00

045 050

LOGIC: Tim e t1 output 86


0.00

[spacer]

LOGIC: Tim e t1 output 85


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 84


0.00

[spacer]

0.00

045 046

LOGIC: Tim e t1 output 83


0.00

[spacer]

LOGIC: Tim e t1 output 82


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 81


0.00

[spacer]

0.00

045 042

LOGIC: Tim e t1 output 80


0.00

[spacer]

LOGIC: Tim e t1 output 79


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 78


0.00

[spacer]

0.00

0.00

Logic Diagram
045 038

LOGIC: Tim e t1 output 77


0.00

[spacer]

Unit

LOGIC: Tim e t1 output 76


0.00

[spacer]

Max

LOGIC: Tim e t1 output 75


0.00

[spacer]

Min

LOGIC: Tim e t1 output 74


0.00

[spacer]

Address

045 110

600.00

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

0.00

045 134

600.00

0.00

045 138

600.00

0.00

045 142

600.00

0.00

045 146

600.00

0.00

045 150

600.00

0.00

045 154

600.00

0.00

045 158

600.00

0.00

045 162

600.00

0.00

045 166

600.00

0.00

045 170

600.00

0.00

045 174

600.00

0.00

045 178

600.00

LOGIC: Tim e t1 output 110


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 109


0.00

[spacer]

0.00

045 130

LOGIC: Tim e t1 output 108


0.00

[spacer]

LOGIC: Tim e t1 output 107


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 106


0.00

[spacer]

0.00

045 126

LOGIC: Tim e t1 output 105


0.00

[spacer]

LOGIC: Tim e t1 output 104


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 103


0.00

[spacer]

0.00

045 122

LOGIC: Tim e t1 output 102


0.00

[spacer]

LOGIC: Tim e t1 output 101


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 100


0.00

[spacer]

0.00

045 118

LOGIC: Tim e t1 output 99


0.00

[spacer]

LOGIC: Tim e t1 output 98


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 97


0.00

[spacer]

0.00

0.00

045 182

600.00

LOGIC: Tim e t1 output 111


0.00

P437/EN M/R-11-A // P437311650

0.00

Logic Diagram
045 114

LOGIC: Tim e t1 output 96


0.00

[spacer]

Unit

LOGIC: Tim e t1 output 95


0.00

[spacer]

Max

LOGIC: Tim e t1 output 94


0.00

[spacer]

Min

LOGIC: Tim e t1 output 93


0.00

[spacer]

Address

045 186

600.00

7-139

P437

7 Settings

Parameter
Default
[spacer]

0.00

045 206

600.00

0.00

045 210

600.00

0.00

045 214

600.00

0.00

045 218

600.00

0.00

045 222

600.00

0.00

045 226

600.00

0.00

045 230

600.00

0.00

045 234

600.00

0.00

045 238

600.00

0.00

045 242

600.00

0.00

045 246

600.00

LOGIC: Tim e t1 output 127


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 126


0.00

[spacer]

0.00

045 202

LOGIC: Tim e t1 output 125


0.00

[spacer]

LOGIC: Tim e t1 output 124


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 123


0.00

[spacer]

0.00

045 198

LOGIC: Tim e t1 output 122


0.00

[spacer]

LOGIC: Tim e t1 output 121


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 120


0.00

[spacer]

0.00

045 194

LOGIC: Tim e t1 output 119


0.00

[spacer]

LOGIC: Tim e t1 output 118


0.00

[spacer]

600.00

LOGIC: Tim e t1 output 117


0.00

[spacer]

0.00

045 190

LOGIC: Tim e t1 output 116


0.00

[spacer]

Logic Diagram

LOGIC: Tim e t1 output 115


0.00

[spacer]

Unit

LOGIC: Tim e t1 output 114


0.00

[spacer]

Max

LOGIC: Tim e t1 output 113


0.00

[spacer]

Min

LOGIC: Tim e t1 output 112


0.00

[spacer]

Address

0.00

045 250

600.00

LOGIC: Tim e t1 output 128


0.00

0.00

045 254

600.00

[spacer]

Settings of timer stage t1 for the respective outputs.

[spacer]

LOGIC: Tim e t2 output 1


0.00

7-140

0.00

030 003

600.00

Fig. 3-336, (p. 3-424)

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

0.00

030 027

600.00

0.00

030 031

600.00

0.00

030 035

600.00

0.00

030 039

600.00

0.00

030 043

600.00

0.00

030 047

600.00

0.00

030 051

600.00

0.00

030 055

600.00

0.00

030 059

600.00

0.00

030 063

600.00

0.00

030 067

600.00

0.00

030 071

600.00

LOGIC: Tim e t2 output 19


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 18


0.00

[spacer]

0.00

030 023

LOGIC: Tim e t2 output 17


0.00

[spacer]

LOGIC: Tim e t2 output 16


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 15


0.00

[spacer]

0.00

030 019

LOGIC: Tim e t2 output 14


0.00

[spacer]

LOGIC: Tim e t2 output 13


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 12


0.00

[spacer]

0.00

030 015

LOGIC: Tim e t2 output 11


0.00

[spacer]

LOGIC: Tim e t2 output 10


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 9


0.00

[spacer]

0.00

030 011

LOGIC: Tim e t2 output 8


0.00

[spacer]

LOGIC: Tim e t2 output 7


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 6


0.00

[spacer]

0.00

0.00

030 075

600.00

LOGIC: Tim e t2 output 20


0.00

P437/EN M/R-11-A // P437311650

0.00

Logic Diagram
030 007

LOGIC: Tim e t2 output 5


0.00

[spacer]

Unit

LOGIC: Tim e t2 output 4


0.00

[spacer]

Max

LOGIC: Tim e t2 output 3


0.00

[spacer]

Min

LOGIC: Tim e t2 output 2


0.00

[spacer]

Address

030 079

600.00

7-141

P437

7 Settings

Parameter
Default
[spacer]

0.00

031 003

600.00

0.00

031 007

600.00

0.00

031 011

600.00

0.00

031 015

600.00

0.00

031 019

600.00

0.00

031 023

600.00

0.00

031 027

600.00

0.00

030 103

600.00

0.00

030 107

600.00

0.00

030 111

600.00

0.00

030 115

600.00

0.00

030 119

600.00

0.00

030 123

600.00

LOGIC: Tim e t2 output 39


0.00

7-142

LOGIC: Tim e t2 output 38


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 37


0.00

[spacer]

0.00

030 099

LOGIC: Tim e t2 output 36


0.00

[spacer]

LOGIC: Tim e t2 output 35


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 34


0.00

[spacer]

0.00

030 095

LOGIC: Tim e t2 output 33


0.00

[spacer]

LOGIC: Tim e t2 output 32


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 31


0.00

[spacer]

0.00

030 091

LOGIC: Tim e t2 output 30


0.00

[spacer]

LOGIC: Tim e t2 output 29


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 28


0.00

[spacer]

0.00

030 087

LOGIC: Tim e t2 output 27


0.00

[spacer]

LOGIC: Tim e t2 output 26


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 25


0.00

[spacer]

0.00

0.00

Logic Diagram
030 083

LOGIC: Tim e t2 output 24


0.00

[spacer]

Unit

LOGIC: Tim e t2 output 23


0.00

[spacer]

Max

LOGIC: Tim e t2 output 22


0.00

[spacer]

Min

LOGIC: Tim e t2 output 21


0.00

[spacer]

Address

030 127

600.00

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

0.00

030 151

600.00

0.00

030 155

600.00

0.00

030 159

600.00

0.00

030 163

600.00

0.00

030 167

600.00

0.00

030 171

600.00

0.00

030 175

600.00

0.00

030 179

600.00

0.00

030 183

600.00

0.00

030 187

600.00

0.00

030 191

600.00

0.00

030 195

600.00

LOGIC: Tim e t2 output 57


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 56


0.00

[spacer]

0.00

030 147

LOGIC: Tim e t2 output 55


0.00

[spacer]

LOGIC: Tim e t2 output 54


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 53


0.00

[spacer]

0.00

030 143

LOGIC: Tim e t2 output 52


0.00

[spacer]

LOGIC: Tim e t2 output 51


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 50


0.00

[spacer]

0.00

030 139

LOGIC: Tim e t2 output 49


0.00

[spacer]

LOGIC: Tim e t2 output 48


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 47


0.00

[spacer]

0.00

030 135

LOGIC: Tim e t2 output 46


0.00

[spacer]

LOGIC: Tim e t2 output 45


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 44


0.00

[spacer]

0.00

0.00

030 199

600.00

LOGIC: Tim e t2 output 58


0.00

P437/EN M/R-11-A // P437311650

0.00

Logic Diagram
030 131

LOGIC: Tim e t2 output 43


0.00

[spacer]

Unit

LOGIC: Tim e t2 output 42


0.00

[spacer]

Max

LOGIC: Tim e t2 output 41


0.00

[spacer]

Min

LOGIC: Tim e t2 output 40


0.00

[spacer]

Address

030 203

600.00

7-143

P437

7 Settings

Parameter
Default
[spacer]

0.00

030 227

600.00

0.00

046 003

600.00

0.00

045 007

600.00

0.00

045 011

600.00

0.00

045 015

600.00

0.00

045 019

600.00

0.00

045 023

600.00

0.00

045 027

600.00

0.00

045 031

600.00

0.00

045 035

600.00

0.00

045 039

600.00

0.00

045 043

600.00

0.00

045 047

600.00

LOGIC: Tim e t2 output 77


0.00

7-144

LOGIC: Tim e t2 output 76


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 75


0.00

[spacer]

0.00

030 223

LOGIC: Tim e t2 output 74


0.00

[spacer]

LOGIC: Tim e t2 output 73


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 72


0.00

[spacer]

0.00

030 219

LOGIC: Tim e t2 output 71


0.00

[spacer]

LOGIC: Tim e t2 output 70


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 69


0.00

[spacer]

0.00

030 215

LOGIC: Tim e t2 output 68


0.00

[spacer]

LOGIC: Tim e t2 output 67


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 66


0.00

[spacer]

0.00

030 211

LOGIC: Tim e t2 output 65


0.00

[spacer]

LOGIC: Tim e t2 output 64


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 63


0.00

[spacer]

0.00

0.00

Logic Diagram
030 207

LOGIC: Tim e t2 output 62


0.00

[spacer]

Unit

LOGIC: Tim e t2 output 61


0.00

[spacer]

Max

LOGIC: Tim e t2 output 60


0.00

[spacer]

Min

LOGIC: Tim e t2 output 59


0.00

[spacer]

Address

045 051

600.00

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

0.00

045 075

600.00

0.00

045 079

600.00

0.00

045 083

600.00

0.00

045 087

600.00

0.00

045 091

600.00

0.00

045 095

600.00

0.00

045 099

600.00

0.00

045 103

600.00

0.00

045 107

600.00

0.00

045 111

600.00

0.00

045 115

600.00

0.00

045 119

600.00

LOGIC: Tim e t2 output 95


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 94


0.00

[spacer]

0.00

045 071

LOGIC: Tim e t2 output 93


0.00

[spacer]

LOGIC: Tim e t2 output 92


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 91


0.00

[spacer]

0.00

045 067

LOGIC: Tim e t2 output 90


0.00

[spacer]

LOGIC: Tim e t2 output 89


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 88


0.00

[spacer]

0.00

045 063

LOGIC: Tim e t2 output 87


0.00

[spacer]

LOGIC: Tim e t2 output 86


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 85


0.00

[spacer]

0.00

045 059

LOGIC: Tim e t2 output 84


0.00

[spacer]

LOGIC: Tim e t2 output 83


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 82


0.00

[spacer]

0.00

0.00

045 123

600.00

LOGIC: Tim e t2 output 96


0.00

P437/EN M/R-11-A // P437311650

0.00

Logic Diagram
045 055

LOGIC: Tim e t2 output 81


0.00

[spacer]

Unit

LOGIC: Tim e t2 output 80


0.00

[spacer]

Max

LOGIC: Tim e t2 output 79


0.00

[spacer]

Min

LOGIC: Tim e t2 output 78


0.00

[spacer]

Address

045 127

600.00

7-145

P437

7 Settings

Parameter
Default
[spacer]

0.00

045 151

600.00

0.00

045 155

600.00

0.00

045 159

600.00

0.00

045 163

600.00

0.00

045 167

600.00

0.00

045 171

600.00

0.00

045 175

600.00

0.00

045 179

600.00

0.00

045 183

600.00

0.00

045 187

600.00

0.00

045 191

600.00

0.00

045 195

600.00

0.00

045 199

600.00

LOGIC: Tim e t2 output 115


0.00

7-146

LOGIC: Tim e t2 output 114


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 113


0.00

[spacer]

0.00

045 147

LOGIC: Tim e t2 output 112


0.00

[spacer]

LOGIC: Tim e t2 output 111


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 110


0.00

[spacer]

0.00

045 143

LOGIC: Tim e t2 output 109


0.00

[spacer]

LOGIC: Tim e t2 output 108


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 107


0.00

[spacer]

0.00

045 139

LOGIC: Tim e t2 output 106


0.00

[spacer]

LOGIC: Tim e t2 output 105


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 104


0.00

[spacer]

0.00

045 135

LOGIC: Tim e t2 output 103


0.00

[spacer]

LOGIC: Tim e t2 output 102


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 101


0.00

[spacer]

0.00

0.00

Logic Diagram
045 131

LOGIC: Tim e t2 output 100


0.00

[spacer]

Unit

LOGIC: Tim e t2 output 99


0.00

[spacer]

Max

LOGIC: Tim e t2 output 98


0.00

[spacer]

Min

LOGIC: Tim e t2 output 97


0.00

[spacer]

Address

045 203

600.00

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

0.00

045 219

600.00

0.00

045 223

600.00

0.00

045 227

600.00

0.00

045 231

600.00

0.00

045 235

600.00

0.00

045 239

600.00

0.00

045 243

600.00

0.00

045 247

600.00

0.00

045 251

600.00

LOGIC: Tim e t2 output 128


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 127


0.00

[spacer]

0.00

045 215

LOGIC: Tim e t2 output 126


0.00

[spacer]

LOGIC: Tim e t2 output 125


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 124


0.00

[spacer]

0.00

045 211

LOGIC: Tim e t2 output 123


0.00

[spacer]

LOGIC: Tim e t2 output 122


0.00

[spacer]

600.00

LOGIC: Tim e t2 output 121


0.00

[spacer]

0.00

045 207

LOGIC: Tim e t2 output 120


0.00

[spacer]

Logic Diagram

LOGIC: Tim e t2 output 119


0.00

[spacer]

Unit

LOGIC: Tim e t2 output 118


0.00

[spacer]

Max

LOGIC: Tim e t2 output 117


0.00

[spacer]

Min

LOGIC: Tim e t2 output 116


0.00

[spacer]

Address

0.00

045 255

600.00

Settings for timer stage t2 for the respective outputs.


Note: This setting has no effect in the minimum time operating mode.

[spacer]

LOGIC: Sig .as sig. out p. 1


061 000: MAIN: Without function

[spacer]

LOGIC: Sig .as sig. out p. 2

044 000

Fig. 3-343, (p. 3-429)


044 002

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 3

044 004

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 4

044 006

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 5

044 008

061 000: MAIN: Without function

P437/EN M/R-11-A // P437311650

7-147

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

LOGIC: Sig .as sig. out p. 6

Max

Unit

Logic Diagram
044 010

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 7

044 012

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 8

044 014

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 9

044 016

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 1 0

044 018

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 1 1

044 020

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 1 2

044 022

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 1 3

044 024

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 1 4

044 026

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 1 5

044 028

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 1 6

044 030

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 1 7

044 032

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 1 8

044 034

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 1 9

044 036

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 2 0

044 038

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 2 1

044 040

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 2 2

044 042

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 2 3

044 044

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 2 4

044 046

061 000: MAIN: Without function

7-148

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

LOGIC: Sig .as sig. out p. 2 5

Max

Unit

Logic Diagram
044 048

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 2 6

044 050

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 2 7

044 052

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 2 8

044 054

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 2 9

044 056

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 3 0

044 058

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 3 1

044 060

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 3 2

044 062

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 3 3

044 064

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 3 4

044 066

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 3 5

044 068

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 3 6

044 070

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 3 7

044 072

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 3 8

044 074

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 3 9

044 076

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 4 0

044 078

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 4 1

044 080

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 4 2

044 082

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 4 3

044 084

061 000: MAIN: Without function

P437/EN M/R-11-A // P437311650

7-149

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

LOGIC: Sig .as sig. out p. 4 4

Max

Unit

Logic Diagram
044 086

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 4 5

044 088

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 4 6

044 090

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 4 7

044 092

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 4 8

044 094

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 4 9

044 096

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 5 0

044 098

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 5 1

044 100

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 5 2

044 102

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 5 3

044 104

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 5 4

044 106

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 5 5

044 108

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 5 6

044 110

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 5 7

044 112

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 5 8

044 114

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 5 9

044 116

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 6 0

044 118

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 6 1

044 120

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 6 2

044 122

061 000: MAIN: Without function

7-150

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

LOGIC: Sig .as sig. out p. 6 3

Max

Unit

Logic Diagram
044 124

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 6 4

044 126

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 6 5

048 128

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 6 6

048 002

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 6 7

048 004

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 6 8

048 006

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 6 9

048 008

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 7 0

048 010

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 7 1

048 012

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 7 2

048 014

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 7 3

048 016

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 7 4

048 018

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 7 5

048 020

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 7 6

048 022

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 7 7

048 024

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 7 8

048 026

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 7 9

048 028

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 8 0

048 030

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 8 1

048 032

061 000: MAIN: Without function

P437/EN M/R-11-A // P437311650

7-151

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

LOGIC: Sig .as sig. out p. 8 2

Max

Unit

Logic Diagram
048 034

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 8 3

048 036

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 8 4

048 038

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 8 5

048 040

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 8 6

048 042

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 8 7

048 044

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 8 8

048 046

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 8 9

048 048

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 9 0

048 050

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 9 1

048 052

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 9 2

048 054

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 9 3

048 056

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 9 4

048 058

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 9 5

048 060

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 9 6

048 062

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 9 7

048 064

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 9 8

048 066

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p. 9 9

048 068

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.10 0

048 070

061 000: MAIN: Without function

7-152

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

LOGIC: Sig .as sig. out p.10 1

Max

Unit

Logic Diagram
048 072

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.10 2

048 074

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.10 3

048 076

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.10 4

048 078

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.10 5

048 080

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.10 6

048 082

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.10 7

048 084

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.10 8

048 086

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.10 9

048 088

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.11 0

048 090

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.11 1

048 092

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.11 2

048 094

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.11 3

048 096

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.11 4

048 098

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.11 5

048 100

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.11 6

048 102

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.11 7

048 104

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.11 8

048 106

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.11 9

048 108

061 000: MAIN: Without function

P437/EN M/R-11-A // P437311650

7-153

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

LOGIC: Sig .as sig. out p.12 0

048 110

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.12 1

048 112

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.12 2

048 114

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.12 3

048 116

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.12 4

048 118

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.12 5

048 120

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.12 6

048 122

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.12 7

048 124

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig. out p.12 8

048 126

061 000: MAIN: Without function


[spacer]

These settings assign the function of a binary input signal to the output of the
logic equation.

[spacer]

LOGIC: Sig .as sig.out p. 1 (t )


061 000: MAIN: Without function

[spacer]

LOGIC: Sig .as sig.out p. 2 (t )

044 001

Fig. 3-343, (p. 3-429)


044 003

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p. 3 (t )

044 005

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p. 4 (t )

044 007

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p. 5 (t )

044 009

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p. 6 (t )

044 011

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p. 7 (t )

044 013

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p. 8 (t )

044 015

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p. 9 (t )

044 017

061 000: MAIN: Without function

7-154

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

LOGIC: Sig .as sig.out p.10 (t )

Unit

Logic Diagram
044 019

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.11 (t )

044 021

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.12 (t )

044 023

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.13 (t )

044 025

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.14 (t )

044 027

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.15 (t )

044 029

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.16 (t )

044 031

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.17 (t )

044 033

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.18 (t )

044 035

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.19 (t )

044 037

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.20 (t )

044 039

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.21 (t )

044 041

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.22 (t )

044 043

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.23 (t )

044 045

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.24 (t )

044 047

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.25 (t )

044 049

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.26 (t )

044 051

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.27 (t )

044 053

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.28 (t )

044 055

061 000: MAIN: Without function

P437/EN M/R-11-A // P437311650

7-155

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

LOGIC: Sig .as sig.out p.29 (t )

Unit

Logic Diagram
044 057

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.30 (t )

044 059

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.31 (t )

044 061

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.32 (t )

044 063

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.33 (t )

044 065

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.34 (t )

044 067

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.35 (t )

044 069

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.36 (t )

044 071

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.37 (t )

044 073

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.38 (t )

044 075

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.39 (t )

044 077

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.40 (t )

044 079

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.41 (t )

044 081

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.42 (t )

044 083

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.43 (t )

044 085

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.44 (t )

044 087

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.45 (t )

044 089

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.46 (t )

044 091

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.47 (t )

044 093

061 000: MAIN: Without function

7-156

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

LOGIC: Sig .as sig.out p.48 (t )

Unit

Logic Diagram
044 095

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.49 (t )

044 097

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.50 (t )

044 099

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.51 (t )

044 101

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.52 (t )

044 103

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.53 (t )

044 105

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.54 (t )

044 107

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.55 (t )

044 109

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.56 (t )

044 111

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.57 (t )

044 113

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.58 (t )

044 115

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.59 (t )

044 117

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.60 (t )

044 119

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.61 (t )

044 121

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.62 (t )

044 123

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.63 (t )

044 125

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.64 (t )

044 127

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.65 (t )

048 129

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.66 (t )

048 003

061 000: MAIN: Without function

P437/EN M/R-11-A // P437311650

7-157

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

LOGIC: Sig .as sig.out p.67 (t )

Unit

Logic Diagram
048 005

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.68 (t )

048 007

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.69 (t )

048 009

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.70 (t )

048 011

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.71 (t )

048 013

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.72 (t )

048 015

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.73 (t )

048 017

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.74 (t )

048 019

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.75 (t )

048 021

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.76 (t )

048 023

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.77 (t )

048 025

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.78 (t )

048 027

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.79 (t )

048 029

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.80 (t )

048 031

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.81 (t )

048 033

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.82 (t )

048 035

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.83 (t )

048 037

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.84 (t )

048 039

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.85 (t )

048 041

061 000: MAIN: Without function

7-158

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

LOGIC: Sig .as sig.out p.86 (t )

Unit

Logic Diagram
048 043

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.87 (t )

048 045

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.88 (t )

048 047

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.89 (t )

048 049

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.90 (t )

048 051

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.91 (t )

048 053

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.92 (t )

048 055

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.93 (t )

048 057

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.94 (t )

048 059

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.95 (t )

048 061

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.96 (t )

048 063

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.97 (t )

048 065

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.98 (t )

048 067

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p.99 (t )

048 069

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 00( t)

048 071

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 01( t)

048 073

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 02( t)

048 075

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 03( t)

048 077

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 04( t)

048 079

061 000: MAIN: Without function

P437/EN M/R-11-A // P437311650

7-159

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

LOGIC: Sig .as sig.out p1 05( t)

Unit

Logic Diagram
048 081

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 06( t)

048 083

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 07( t)

048 085

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 08( t)

048 087

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 09( t)

048 089

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 10( t)

048 091

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 11( t)

048 093

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 12( t)

048 095

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 12( t)

048 097

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 14( t)

048 099

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 15( t)

048 101

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 16( t)

048 103

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 17( t)

048 105

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 18( t)

048 107

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 19( t)

048 109

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 20( t)

048 111

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 21( t)

048 113

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 22( t)

048 115

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 23( t)

048 117

061 000: MAIN: Without function

7-160

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

LOGIC: Sig .as sig.out p1 24( t)

Unit

Logic Diagram
048 119

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 25( t)

048 121

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 26( t)

048 123

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 27( t)

048 125

061 000: MAIN: Without function


[spacer]

LOGIC: Sig .as sig.out p1 28( t)

048 127

061 000: MAIN: Without function


[spacer]

These settings assign the function of a binary input signal to the output of the
logic equation.

P437/EN M/R-11-A // P437311650

7-161

P437

7 Settings

Parameter
Default

Address
Min

Max

Unit

Logic Diagram

Programmable Logic LOG_2: General e nabl e USE R

011 137

0: No

Fig. 3-337, (p. 3-425)

[spacer]

Enable/disable the function group LOG_2 (Programmable Logic 2).

[spacer]

LOG_2: Fct.assig nm. outp. 1

050 000

060 000: MAIN: Without function


[spacer]

Fig. 3-337, (p. 3-425)

LOG_2: Fct.assig nm. outp. 2


060 000: MAIN: Without function

[spacer]

050 004

LOG_2: Fct.assig nm. outp. 3

050 008

060 000: MAIN: Without function


[spacer]

LOG_2: Fct.assig nm. outp. 4

050 012

060 000: MAIN: Without function


[spacer]

These settings assign functions to the outputs.

[spacer]

LOG_2: Op . m ode t output 1

050 001

0: Without timer stage


[spacer]

Fig. 3-337, (p. 3-425)

LOG_2: Op . m ode t output 2

050 005

0: Without timer stage


[spacer]

LOG_2: Op . m ode t output 3

050 009

0: Without timer stage


[spacer]

LOG_2: Op . m ode t output 4

050 013

0: Without timer stage


[spacer]

These settings define the operating modes for the output timer stages.

[spacer]

LOG_2: T im e t 1 output 1
0

[spacer]

Fig. 3-337, (p. 3-425)

050 006

60000

LOG_2: T im e t 1 output 3
0

[spacer]

60000

LOG_2: T im e t 1 output 2
0

[spacer]

050 002

050 010

60000

LOG_2: T im e t 1 output 4
0

050 014

60000

[spacer]

Settings of timer stage t1 for the respective outputs.

[spacer]

LOG_2: T im e t 2 output 1
0

[spacer]

Fig. 3-337, (p. 3-425)


050 007

60000

LOG_2: T im e t 2 output 3
0

7-162

60000

LOG_2: T im e t 2 output 2
0

[spacer]

050 003

050 011

60000

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Min

Max

Unit

Logic Diagram

LOG_2: T im e t 2 output 4
0

[spacer]

Address

050 015

60000

Settings for timer stage t2 for the respective outputs.


Note: This setting has no effect in the minimum time operating mode.

[spacer]

LOG_2: S ig.as sig. o ut p. 1

064 000

061 000: MAIN: Without function


[spacer]

LOG_2: S ig.as sig. o ut p. 2

064 002

061 000: MAIN: Without function


[spacer]

LOG_2: S ig.as sig. o ut p. 3

064 004

061 000: MAIN: Without function


[spacer]

LOG_2: S ig.as sig. o ut p. 4

064 006

061 000: MAIN: Without function


[spacer]

These settings assign the function of a binary input signal to the output of the
logic equation.

[spacer]

LOG_2: S ig.as sig.out p. 1 (t )

064 001

061 000: MAIN: Without function


[spacer]

LOG_2: S ig.as sig.out p. 2 (t )

064 003

061 000: MAIN: Without function


[spacer]

LOG_2: S ig.as sig.out p. 3 (t )

064 005

061 000: MAIN: Without function


[spacer]

LOG_2: S ig.as sig.out p. 4 (t )

064 007

061 000: MAIN: Without function


[spacer]

These settings assign the function of a binary input signal to the output of the
logic equation.

P437/EN M/R-11-A // P437311650

7-163

P437

7 Settings

Parameter
Default

Binary counts

Address
Min

Max

Unit

COUNT : General enable US ER

217 000

0: No

Fig. 3-345, (p. 3-431)

[spacer]

Disabling or enabling binary counts.

[spacer]

COUNT : Deb ounce t. c ount. 1


3

[spacer]

1000

ms

Fig. 3-345, (p. 3-431)

1000

217 161

ms

COUNT : Deb ounce t. c ount. 3


3

[spacer]

217 160

COUNT : Deb ounce t. c ount. 2


3

[spacer]

Logic Diagram

1000

217 162

ms

COUNT : Deb ounce t. c ount. 4


3

1000

217 163

ms

[spacer]

Setting for the debounce time of the binary signal to be counted.

[spacer]

COUNT : Limit count e r 1


Blocked

[spacer]

217 222

65000

COUNT : Limit count e r 3


Blocked

[spacer]

65000

COUNT : Limit count e r 2


Blocked

[spacer]

217 221

217 223

65000

COUNT : Limit count e r 4


Blocked

217 224

65000

[spacer]

Setting a limit for the counter value. A warning signal is issued if the counter
value exceeds the set limit. Setting this parameter to Blocked disables the limit
check.

[spacer]

COUNT : Cycle t.count t r ans m


0: No transmission

217 007

Fig. 3-345, (p. 3-431)

[spacer]

Setting the cycle time for the periodic transmission of the counts.

[spacer]

COUNT : IEC61850 pulsQty


1

[spacer]

221 096

1000

Setting the scaling factor to transmit the counter value via IEC 61850. According
to the standard the resulting value is calculated as:
Value transmitted = actual value pulsQty
(see IEC 61850: Value = actVal pulsQty).

7-164

P437/EN M/R-11-A // P437311650

P437

7 Settings

7.1.3.3

Param eter S ubs e ts


Parameter
Default

Main function

Address
Min

Max

Unit

MAIN: Neut r.p t. treat . PSx

Logic Diagram
010 048

001 076

001 077

001 078

001 250

001 251

002 001

1: Low-imped. grounding
[spacer]

The neutral-point treatment of the system must be set here.

[spacer]

MAIN: Ground starti ng PSx

001 249

1: IN> OR VNG>
[spacer]

Setting whether a ground fault is determined by an 'OR'-linked or an 'AND'linked condition of the IN> and VNG> thresholds.

[spacer]

MAIN: Transf e r for 1p P Sx

010 040

001 079

001 080

001 081

1: Ground
[spacer]

For single-phase overcurrent starting without ground starting, either ground


starting or another phase starting needs to be triggered. The user may choose
to always activate the ground starting or as a function of current magnitude
ratios to trigger ground or phase starting.

[spacer]

MAIN: Op. m ode rus h r. P Sx

017 097

0: Without

001 088

001 089

001 090

017 082

017 083

Fig. 3-60, (p. 3-89)

[spacer]

Setting for the operating mode of the inrush stabilization function.

[spacer]

MAIN: Funct.R u sh r est r. PS x

017 093

060 000: MAIN: Without function

017 064

Fig. 3-61, (p. 3-90)

[spacer]

Select the protection elements that shall be blocked when the inrush
stabilization is triggered.

[spacer]

MAIN: Rush I(2fn) /I( fn) PS x


20

10

017 098

35

[spacer]

Setting for the operate value of inrush stabilization.

[spacer]

MAIN: I> lif t rush r. PS x


10.0

1.0

Inom

001 092

001 093

001 086

001 087

Fig. 3-60, (p. 3-89)

017 095

20.0

001 091

001 085

Fig. 3-60, (p. 3-89)

[spacer]

Setting for the current threshold for disabling the inrush stabilization.

[spacer]

MAIN: kPar PS x
0.70

025 097

0.70

024 017

024 077

025 037

2.00

[spacer]

Setting for a correction factor by which the different grounding conditions for
line and parallel line shall be equalized.

[spacer]

MAIN: t lift rus h r st r. PSx


Blocked

[spacer]

0.01

019 001

10.00

019 002

019 003

019 004

Fig. 3-60, (p. 3-89)

Setting for the maximum duration of inrush stabilization.

P437/EN M/R-11-A // P437311650

7-165

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

MAIN: 3p tr.if HSR off PS x

Logic Diagram
015 065

024 034

024 094

025 054

1: Yes
[spacer]

This setting defines whether single-pole trip commands shall be converted to a


three-pole trip command when ARC is disabled.

[spacer]

MAIN: 3p transf 1p tr p PSx


Blocked

0.00

002 184

10.00

002 185

002 186

002 187

[spacer]

Setting the time delay period for the 3-pole transfer trip feature. This is issued if
no phase starting takes place and therefore no phase-selection is possible.

[spacer]

MAIN: Enable 1p t ri p PS x

002 061

002 062

002 063

002 064

0: No
[spacer]

7-166

Enabling the phase-selective trip logic.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default

Fault data
acquisition

Address
Min

Max

Unit

FT_DA: Line le ngth PS x


10.00

0.01

Logic Diagram
010 005

500.00

km

010 006

010 007

010 008

Fig. 3-92, (p. 3-129)

[spacer]

This setting defines the distance in km that the fault locator interprets as 100 %
when calculating the fault distance.

[spacer]

FT_DA: Line reac tance P S x


10 | 2 (For MAIN: Inom
device=1.0A | 5.0A)

0.1 |
0.02

010 012

200 | 40

010 013

010 014

010 015

Fig. 3-92, (p. 3-129)

[spacer]

This setting defines the reactance X that the fault locator interprets as 100 %
when calculating the fault distance.

[spacer]

FT_DA: Flt.loc. de t e rm. PSx


0: with GS

008 007

008 008

008 009

008 027

Fig. 3-88, (p. 3-124)

[spacer]

Select whether the fault location shall be determined only for short-circuits with
a general starting (with GS) or also in case of a sole neutral starting, e.g. during
a short-duration grounding (with GS or N).

[spacer]

FT_DA: S tart data acqu. PS x


1: End of fault

010 011

010 042

010 043

010 044

Fig. 3-88, (p. 3-124)

[spacer]

This setting determines at what point during a fault the acquisition of fault data
should take place.

[spacer]

FT_DA: Outp . f lt.locat . P Sx


1: Always

010 032

010 033

010 034

010 035

Fig. 3-88, (p. 3-124)

[spacer]

Setting for the conditions under which a fault location is output.

[spacer]

FT_DA: Mutual comp. PS x

025 096

024 016

024 076

025 036

0: Without
[spacer]

Setting for the conditions under which the residual current of the parallel line is
used to calculate the fault location.

P437/EN M/R-11-A // P437311650

7-167

P437

7 Settings

Parameter
Default

Distance protection

Address
Min

Max

Unit

Logic Diagram

DIST: I>> PS x
1.00

010 054

0.10

20.00

Inom

Setting for the operate value of overcurrent starting.

[spacer]

DIST: I> ( Ib l) PS x

010 068

0.05

1.00

Inom

010 094

011 014

Fig. 3-97, (p. 3-137)

[spacer]

0.20

010 074

010 088

011 008

011 028

Fig. 3-100, (p. 3-140)

[spacer]

Base current setting above which undervoltage and underimpedance starting is


enabled.

[spacer]

DIST: Ope rat. mode V< PS x

010 067

2: With V< start.PG,PP

Operating mode setting for undervoltage starting.

[spacer]

DIST: V< PS x

010 069

0.10

0.90

Setting for the operate value of undervoltage starting.

[spacer]

DIST: Ope rat. mode Z< PS x

010 066

2: With Z< start.PG,PP

010 089

011 009

011 029

010 086

011 006

011 026

Fig. 3-102, (p. 3-142)

[spacer]

Operating mode setting for underimpedance starting.

[spacer]

DIST: Xfw PS x

010 050

0.1 |
0.02

300 | 60

Setting for the reactance limit of underimpedance starting.

[spacer]

DIST: Rfw,PG PS x

010 051

0.1 |
0.02

300 | 60

010 070

010 090

011 010

Fig. 3-105, (p. 3-145)

[spacer]

10 | 2 (For MAIN: Inom


device=1.0A | 5.0A)

011 027

Vnom(/3) Fig. 3-101, (p. 3-141)

[spacer]

10 | 2 (For MAIN: Inom


device=1.0A | 5.0A)

011 007

Fig. 3-101, (p. 3-141)

[spacer]

0.70

010 087

010 071

010 091

011 011

Fig. 3-105, (p. 3-145)

[spacer]

Setting for the resistance limit of underimpedance starting for phase-to-ground


loops.

[spacer]

DIST: Rfw,PP PS x
10 | 2 (For MAIN: Inom
device=1.0A | 5.0A)

010 052

0.1 |
0.02

300 | 60

010 072

010 092

011 012

Fig. 3-105, (p. 3-145)

[spacer]

Setting for the resistance limit of underimpedance starting for phase-to-phase


loops.

[spacer]

DIST: PS x
30

[spacer]

7-168

010 063

15

65

010 083

011 003

011 023

Fig. 3-105, (p. 3-145)

Angle setting for load blinder of underimpedance starting characteristic.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

DIST: Zfw,PG PSx


0 | 0 (For MAIN: Inom
device=1.0A | 5.0A)

Logic Diagram
010 101

0|0

300 | 60

010 102

010 103

010 104

Fig. 3-105, (p. 3-145)

[spacer]

Setting for the circular reach (load-angle-independent limit) of underimpedance


starting characteristic for phase-to-ground loops.

[spacer]

DIST: Zfw,PP PSx


0 | 0 (For MAIN: Inom
device=1.0A | 5.0A)

010 105

0|0

300 | 60

010 106

010 107

010 108

Fig. 3-105, (p. 3-145)

[spacer]

Setting for the circular reach (load-angle-independent limit) of underimpedance


starting characteristic for phase-to-phase loops.

[spacer]

DIST: Zbw/ Zfw PSx


0.50

010 053

0.00

4.00

010 073

010 093

Fig. 3-105, (p. 3-145)

[spacer]

Setting for the limit of underimpedance starting in the backward (reverse)


direction.

[spacer]

DIST: Z evaluation PSx

025 093

1: ZPG=VPG/(IP + kG*IN)
[spacer]

011 013

024 013

024 073

025 033

Fig. 3-105, (p. 3-145)

This setting determines whether the P437 will carry out the starting impedance
calculation of the phase-to-ground loops using the phase current corrected by
the set ground factor or using twice the phase current.
Note: Calculation with twice the phase current may be necessary in lowimpedance-grounded networks in order to avoid inadvertent starting in healthy
lines as the result of the high ground fault current. Impedance is calculated by
the distance measuring system using solely the phase current corrected by the
set ground factor.

[spacer]

DIST: IN> PS x
0.20

010 055

0.05

2.00

Inom

010 075

010 095

Fig. 3-98, (p. 3-138)

[spacer]

Operate value setting for the residual current stage of ground starting.

[spacer]

DIST: tIN> PS x
0.100

010 057

0.000

0.500

011 015

010 077

010 097

011 017

Fig. 3-98, (p. 3-138)


Fig. 3-106, (p. 3-147)

[spacer]

In isolated-neutral or resonant-grounded systems, the operate delay tIN> should


be set so as to avoid erroneous transient ground starting resulting from residual
current flow due to switching phenomena related to phase-to-ground
capacitances.
Note: For single-phase faults, neutral starting does not proceed before tIN> has
elapsed. tIN> should be set to at least 20 ms so that starting transfer does not
occur.

[spacer]

DIST: VNG> PS x
0.10

[spacer]

010 056

0.02

1.00

Vnom

010 076

010 096

011 016

Fig. 3-98, (p. 3-138)

Operate value setting for the voltage trigger VNG> of ground starting.

P437/EN M/R-11-A // P437311650

7-169

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

DIST: VNG>> PS x
0.50

010 062

0.20

1.00

Vnom

010 082

011 002

Fig. 3-98, (p. 3-138)

[spacer]

Operate value setting for the voltage trigger VNG>> of ground starting.

[spacer]

DIST: tVNG>> PSx


1.000

010 061

0.000

60.000

010 081

011 001

011 021

Fig. 3-98, (p. 3-138)

[spacer]

Setting for the operate delay of the VNG>> trigger.

[spacer]

DIST: Meas. start. 1 pG PSx

012 172

1: PG loops

011 022

012 173

012 174

012 175

Fig. 3-108, (p. 3-150)

[spacer]

This setting defines whether the distance measuring system shall process
single-pole phase-to-ground faults.

[spacer]

DIST: Meas. start. 2 pG PSx

012 176

1: PG loops

012 177

012 178

012 179

Fig. 3-108, (p. 3-150)

[spacer]

This setting defines whether, in the event of two-phase-to-ground faults, the


distance measuring system shall process either the phase-to-phase loops or the
phase-to-ground loops.

[spacer]

DIST: Meas. start. 3 pG PSx

012 180

1: PG loops

012 181

012 182

012 183

Fig. 3-108, (p. 3-150)

[spacer]

This setting defines whether, in the event of three-phase-to-ground faults, the


distance measuring system shall process either the phase-to-phase loops or the
phase-to-ground loops.

[spacer]

DIST: Characteristic P Sx

012 040

2: Polygon

073 097

Selection of the characteristic used in distance measurement.

[spacer]

DIST: X1,PG ( polygon) PS x

[spacer]

[spacer]

0.05 |
0.01

200 | 40

0.05 |
0.01

200 | 40

0.05 |
0.01

200 | 40

0.05 |
0.01

200 | 40

012 051

013 001

013 051

Fig. 3-124, (p. 3-170)


012 002

012 052

013 002

013 052

Fig. 3-123, (p. 3-168)


012 003

012 053

013 003

013 053

012 004

012 054

013 004

013 054

012 100

012 101

012 102

012 103

DIST: X5,PG ( polygon) PS x


50 | 10 (For MAIN: Inom
device=1.0A | 5.0A)

7-170

DIST: X4,PG ( polygon) PS x


40 | 8 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

200 | 40

DIST: X3,PG ( polygon) PS x


30 | 6 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

0.05 |
0.01

012 001

DIST: X2,PG ( polygon) PS x


20 | 4 (For MAIN: Inom
device=1.0A | 5.0A)

075 097

Fig. 3-115, (p. 3-160)

[spacer]

10 | 2 (For MAIN: Inom


device=1.0A | 5.0A)

074 097

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

DIST: X6,PG ( polygon) PS x


60 | 12 (For MAIN: Inom
device=1.0A | 5.0A)

0.05 |
0.01

Logic Diagram
012 104

200 | 40

012 105

012 106

[spacer]

Setting for the reactance limit in impedance zones 1 to 6 of the polygon


characteristic for the phase-to-ground loops (in secondary values).

[spacer]

DIST: X1,PP (pol ygo n) P Sx


10 | 2 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

0.05 |
0.01

400 | 80

0.05 |
0.01

400 | 80

0.05 |
0.01

400 | 80

0.05 |
0.01

400 | 80

0.05 |
0.01

400 | 80

002 078

002 081

002 082

002 084

002 085

002 086

002 087

002 089

002 090

002 091

002 092

002 093

002 094

002 095

002 096

002 097

002 098

002 099

002 126

Setting for the reactance limit in impedance zones 1 to 6 of the polygon


characteristic for the phase-to-phase loops (in secondary values).

[spacer]

DIST: R1,PG ( polygon) PS x

[spacer]

0.1 |
0.02

200 | 40

0.1 |
0.02

200 | 40

0.1 |
0.02

200 | 40

P437/EN M/R-11-A // P437311650

0.1 |
0.02

200 | 40

013 005

013 055

012 057

013 007

013 057

Fig. 3-123, (p. 3-168)


012 009

012 059

013 009

013 059

012 011

012 061

013 011

013 061

012 108

012 109

012 110

012 111

DIST: R5,PG ( polygon) PS x


50 | 10 (For MAIN: Inom
device=1.0A | 5.0A)

012 055

Fig. 3-124, (p. 3-170)


012 007

DIST: R4,PG ( polygon) PS x


40 | 8 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

200 | 40

DIST: R3,PG ( polygon) PS x


30 | 6 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

012 005

DIST: R2,PG ( polygon) PS x


20 | 4 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

0.1 |
0.02

002 083

Fig. 3-123, (p. 3-168)

[spacer]

10 | 2 (For MAIN: Inom


device=1.0A | 5.0A)

002 079

DIST: X6,PP (pol ygo n) P Sx


60 | 12 (For MAIN: Inom
device=1.0A | 5.0A)

002 077

Fig. 3-124, (p. 3-170)


002 080

DIST: X5,PP (pol ygo n) P Sx


50 | 10 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

DIST: X4,PP (pol ygo n) P Sx


40 | 8 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

400 | 80

DIST: X3,PP (pol ygo n) P Sx


30 | 6 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

002 076

DIST: X2,PP (pol ygo n) P Sx


20 | 4 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

0.05 |
0.01

012 107

7-171

P437

7 Settings

Parameter
Default
[spacer]

Min

Max

Unit

DIST: R6,PG ( polygon) PS x


50 | 10 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

Address

0.1 |
0.02

Logic Diagram
012 116

200 | 40

012 117

012 118

012 119

Setting for the resistance limit in impedance zones 1 to 6 of the polygon


characteristic for the phase-to-ground loops (in secondary values).
Note: The specified precision of measurement can only be reached if the ratio
R / X is less than 8, i.e.:
Rn,PG / Xn < 8
If the ratio is greater than this (i.e. the polygon becomes extremely flat), the
measurement conditions for high fault resistances become quite bad, because in
this case, the angle of the fault impedance gets small, which results in quite big
measurement deviations for the reactance.

[spacer]

DIST: R1,PP (polygon) P Sx


10 | 2 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

0.1 |
0.02

200 | 40

0.1 |
0.02

200 | 40

0.1 |
0.02

200 | 40

0.1 |
0.02

200 | 40

013 006

013 056

012 058

013 008

013 058

Fig. 3-123, (p. 3-168)


012 010

012 060

013 010

013 060

012 012

012 062

013 012

013 062

012 112

012 113

012 114

012 115

012 120

012 121

012 122

012 123

DIST: R6,PP (polygon) P Sx


50 | 10 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

200 | 40

DIST: R5,PP (polygon) P Sx


50 | 10 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

0.1 |
0.02

012 056

Fig. 3-124, (p. 3-170)


012 008

DIST: R4,PP (polygon) P Sx


40 | 8 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

DIST: R3,PP (polygon) P Sx


30 | 6 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

200 | 40

DIST: R2,PP (polygon) P Sx


20 | 4 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

0.1 |
0.02

012 006

Setting for the resistance limit in impedance zones 1 to 6 of the polygon


characteristic for the phase-to-phase loops (in secondary values).
Note: The specified precision of measurement can only be reached if the ratio
R / X is less than 8, i.e.:
Rn,PP / Xn < 8
If the ratio is greater than this (i.e. the polygon becomes extremely flat), the
measurement conditions for high fault resistances become quite bad, because in
this case, the angle of the fault impedance gets small, which results in quite big
measurement deviations for the reactance.

[spacer]

DIST: 1 ( polyg on) PSx


75

[spacer]

90

DIST: 2 ( polyg on) PSx


75

7-172

40

012 013

40

013 013

013 063

Fig. 3-124, (p. 3-170)


012 014

90

012 063

012 064

013 014

013 064

Fig. 3-123, (p. 3-168)

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Unit

40

90

40

90

40

90

40

90

012 015

012 065

013 015

013 065

012 016

012 066

013 016

013 066

012 124

012 125

012 126

012 127

012 128

012 129

012 130

012 131

DIST: 6 ( polygon) PSx


75

Logic Diagram

DIST: 5 ( polygon) PSx


75

[spacer]

Max

DIST: 4 ( polygon) PSx


75

[spacer]

Min

DIST: 3 ( polygon) PSx


75

[spacer]

Address

[spacer]

Setting for the slope angle of the tripping polygon of impedance zones 1 to 6 in
R-direction (resistance line).

[spacer]

DIST: 1 ( polygon) P Sx
0

[spacer]

20

-20

20

-20

20

-20

20

-20

20

075 086

073 087

074 087

075 087

Fig. 3-123, (p. 3-168)


072 088

073 088

074 088

075 088

072 089

073 089

074 089

075 089

012 156

012 157

012 158

012 159

012 160

012 161

012 162

012 163

DIST: 6 ( polygon) P Sx
0

074 086

DIST: 5 ( polygon) P Sx
0

[spacer]

-20

073 086

Fig. 3-124, (p. 3-170)


072 087

DIST: 4 ( polygon) P Sx
0

[spacer]

DIST: 3 ( polygon) P Sx
0

[spacer]

20

DIST: 2 ( polygon) P Sx
0

[spacer]

-20

072 086

[spacer]

Setting for the slope angle of the tripping polygon of impedance zones 1 to 6 in
X-direction (reactance line).

[spacer]

DIST: Z1 (circle) PS x
10 | 2 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

0.05 |
0.01

200 | 40

0.05 |
0.01

200 | 40

0.05 |
0.01

200 | 40

P437/EN M/R-11-A // P437311650

0.05 |
0.01

200 | 40

074 091

075 091

073 092

074 092

075 092

Fig. 3-119, (p. 3-164)


012 044

073 093

074 093

075 093

012 045

073 094

074 094

075 094

012 148

012 149

012 150

012 151

DIST: Z5 (circle) PS x
50 | 10 (For MAIN: Inom
device=1.0A | 5.0A)

073 091

Fig. 3-120, (p. 3-165)


012 043

DIST: Z4 (circle) PS x
40 | 8 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

200 | 40

DIST: Z3 (circle) PS x
30 | 6 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

0.05 |
0.01

DIST: Z2 (circle) PS x
20 | 4 (For MAIN: Inom
device=1.0A | 5.0A)

[spacer]

012 042

7-173

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

DIST: Z6 (circle) PS x
60 | 12 (For MAIN: Inom
device=1.0A | 5.0A)

Logic Diagram
012 152

0.05 |
0.01

200 | 40

012 153

012 154

[spacer]

Setting for the impedance limit in impedance zones 1 to 6 of the circular


characteristic (in secondary values).

[spacer]

DIST: 1 ( circle) PS x
75

[spacer]

90

10

90

10

90

10

90

10

90

073 095

074 095

072 096

073 096

074 096

075 096

072 099

073 099

074 099

075 099

012 164

012 165

012 166

012 167

012 168

012 169

012 170

012 171

This setting is only important if the setting With arc compensation is active
(DI ST : Arc comp. ci rc le P Sx=Yes). In this case, the setting at this
address determines the angle where arc compensation becomes active in
zones 1 to 6.

[spacer]

DIST: Ar c com p. circle P Sx

012 038

0: No

012 090

012 091

Disabling or enabling arc compensation when the circular characteristic is


selected.

[spacer]

DIST: Dir ectional char PS x


10

002 234

80

002 235

Selection of the characteristic used in distance measurement.

[spacer]

DIST: Dir ection N1 PSx


1: Forward directional

DIST: Dir ection N2 PSx


1: Forward directional

DIST: Dir ection N3 PSx


1: Forward directional

[spacer]

DIST: Dir ection N4 PSx


1: Forward directional

[spacer]

DIST: Dir ection N5 PSx


1: Forward directional

7-174

002 236

002 237

013 023

013 073

[spacer]

[spacer]

012 092

Fig. 3-117, (p. 3-162)

[spacer]

[spacer]

075 095

Fig. 3-119, (p. 3-164)

[spacer]

45

075 090

DIST: 6 ( circle) PS x
75

074 090

DIST: 5 ( circle) PS x
75

[spacer]

10

073 090

Fig. 3-120, (p. 3-165)


072 095

DIST: 4 ( circle) PS x
75

[spacer]

DIST: 3 ( circle) PS x
75

[spacer]

90

DIST: 2 ( circle) PS x
75

[spacer]

072 090

10

012 155

012 023

012 073

Fig. 3-128, (p. 3-176)


012 024

012 074

013 024

013 074

Fig. 3-128, (p. 3-176)


012 025

012 075

013 025

013 075

Fig. 3-128, (p. 3-176)


012 026

012 076

013 026

013 076

Fig. 3-128, (p. 3-176)


012 027

012 077

013 027

013 077

Fig. 3-128, (p. 3-176)

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

DIST: Dir ection N6 PSx

012 132

1: Forward directional
[spacer]

Logic Diagram
012 133

012 134

012 135

Fig. 3-128, (p. 3-176)

DIST: Dir ection N7 PSx

012 136

1: Forward directional

012 137

012 138

012 139

Fig. 3-128, (p. 3-176)

[spacer]

This directional setting defines the direction in which impedance stages 1 to 6 or


final timer stage 7 measure relative to the basic measuring direction
determined by the connection of the measuring circuits and the setting at
MAIN: Conn. m eas . circ. IP.

[spacer]

DIST: Ope r.val.Vme mory P Sx


0.15

0.01

2.00

010 109

Vnom

010 116

010 117

010 118

Fig. 3-113, (p. 3-157)

[spacer]

Setting for the voltage threshold that must be exceeded so that the measured
fault angle is used for the direction determination and the impedance
calculation.

[spacer]

DIST: t1 PS x
0.00

[spacer]

0.00

60.00

60.00

60.00

60.00

60.00

DIST: t8 PS x
7.00

60.00

012 080

013 030

013 080

012 081

013 031

013 081

012 082

013 032

013 082

012 083

013 033

013 083

012 141

012 142

012 143

Fig. 3-127, (p. 3-175)


012 144

0.00

013 079

Fig. 3-127, (p. 3-175)


012 140

0.00

013 029

Fig. 3-127, (p. 3-175)


012 033

0.00

012 079

Fig. 3-127, (p. 3-175)


012 032

0.00

013 078

Fig. 3-127, (p. 3-175)


012 031

0.00

013 028

Fig. 3-127, (p. 3-175)


012 030

DIST: t7 PS x
6.00

[spacer]

60.00

DIST: t6 PS x
5.00

[spacer]

0.00

012 078

Fig. 3-126, (p. 3-174)


012 029

DIST: t5 PS x
4.00

[spacer]

DIST: t4 PS x
3.00

[spacer]

60.00

DIST: t3 PS x
2.00

[spacer]

0.00

DIST: t2 PS x
1.00

[spacer]

012 028

012 145

012 146

012 147

Fig. 3-127, (p. 3-175)

[spacer]

Setting for the timer stages of impedance zones 1 to 6 and of directional and
non-directional backup timer stages 7 and 8.

[spacer]

DIST: Enable ZE f. 1pG P Sx

012 039

012 089

013 039

013 089

0: Without
[spacer]

This setting defines the conditions under which the zone extension occurs in
zone 1 in the event of single-phase-to-ground fault detection.

[spacer]

DIST: kze,PG HS R PS x
1.50

1.00

012 034

450.00

012 084

013 034

013 084

Fig. 3-120, (p. 3-165)


Fig. 3-124, (p. 3-170)

P437/EN M/R-11-A // P437311650

7-175

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

DIST: kze,PP HS R PSx


1.50

1.00

012 035

450.00

012 085

013 035

013 085

Fig. 3-120, (p. 3-165)


Fig. 3-124, (p. 3-170)

[spacer]

Setting for the HSR zone extension factor for phase-to-ground loops or phase-tophase loops, respectively. The setting for the zone extension factor modifies the
zone 1 reactance and resistance limits of the polygon characteristic. The
following applies to the measurement:
X1,zeHSR = (kzeHSR)X1
R1,zeHSR = (kzeHSR)R1, if D IST: k ze (poly gon) PSx = R and X
R1,zeHSR = R1 (i.e. without extension), if DIS T : k ze (polygon) PSx = Only
X
X1,zeHSR: reactance modified by the zone extension factor
R1,zeHSR: resistance modified by the zone extension factor
The following applies to measurement using the circle characteristic:
Z1,zeHSR = (kzeHSR)Z1
Z1,zeHSR: impedance modified by the zone extension factor
The zone extension HSR is controlled by

[spacer]

Protective signaling,

Auto-reclosing control (ARC) before an HSR when protective signaling is


not ready,

a reclose command, whether or not protective signaling is ready,

Switch on to fault protection,

an appropriately configured binary signal input.

DIST: kze,PG TDR PSx


1.50

1.00

012 046

450.00

012 096

013 046

013 096

Fig. 3-120, (p. 3-165)


Fig. 3-124, (p. 3-170)

7-176

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

DIST: kze,PP TDR PS x


1.50

1.00

Logic Diagram
012 047

450.00

012 097

013 047

013 097

Fig. 3-120, (p. 3-165)


Fig. 3-124, (p. 3-170)

[spacer]

Setting for the TDR zone extension factor for phase-to-ground loops or phase-tophase loops, respectively. The setting for the zone extension factor modifies the
zone 1 reactance and resistance limits of the polygon characteristic. The
following applies to the measurement:
X1,zeTDR = (kzeTDR)X1
R1,zeTDR = (kzeTDR)R1, if DIST: kze (polygon ) PSx = R and X
R1,zeTDR = R1 (i.e. without extension), if DI S T: kz e (polygon) PSx = Only
X
X1,zeTDR: reactance modified by the zone extension factor
R1,zeTDR: resistance modified by the zone extension factor
The following applies to measurement using the circle characteristic:
Z1,zeTDR = (kzeTDR)Z1
Z1,zeTDR: impedance modified by the zone extension factor
Zone extension takes place before a TDR (time-delay reclosure), as long as a
further TDR is permitted.

[spacer]

DIST: kze (polygon) P S x

010 186

010 195

010 196

010 197

2: R and X
[spacer]

Select whether the impedance zone 1 of the polygon characteristic shall be


extended only in reactance direction (Only X) or for both reactance and
resistance (R and X).

[spacer]

DIST: t1,ze PSx


Blocked

[spacer]

026 025

0.00

10.00

027 025

028 025

029 025

Fig. 3-126, (p. 3-174)

Setting for the timer stage of impedance zone 1 with extended reach.
Note: This timer is only used if zone extension is activated from binary input.
When controlled from internal function, extended zone trip time is set from that
function (e.g. PSIG trip time).

[spacer]

DIST: Ab s . value k G P Sx
1.00

P437/EN M/R-11-A // P437311650

0.00

012 037

8.00

012 087

013 037

013 087

Fig. 3-104, (p. 3-144)

7-177

P437

7 Settings

Parameter

Address

Default
[spacer]

Min

Unit

DIST: Angle kG PSx


0

[spacer]

Max

Logic Diagram
012 036

-180

180

012 086

013 036

013 086

Fig. 3-104, (p. 3-144)

Setting for the absolute value and angle of the complex ground factor kG.
kG =

Z0 - Zpos
3 Zpos

Z0: zero-sequence impedance


Zpos: positive-sequence impedance
Angle(kG ) = arctan

| kG |

X 0 - X pos
R0 - Rpos

- arctan

X pos
Rpos

( X 0 - X pos)2 + (R0 - Rpos)2


2
2
3 X pos
+ Rpos

R0: resistance component of zero-sequence impedance


Rpos: resistance component of positive-sequence impedance
X0: reactance component of zero-sequence impedance
Xpos: reactance component of positive-sequence impedance
If the calculated value cannot be set exactly, then a next smaller value should
be set.
[spacer]

DIST: kG,par abs .v alue P Sx


1.00

7-178

0.00

012 049

8.00

012 099

013 049

013 099

Fig. 3-109, (p. 3-152)

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter

Address

Default
[spacer]

Min

Unit

DIST: kG,par angle P Sx


0

[spacer]

Max

-180

Logic Diagram
012 048

180

012 098

013 048

013 098

Fig. 3-109, (p. 3-152)

Setting the absolute value and the angle of the complex ground factor kG,par
k G,par =

Z 00
3 ZL

Z00: coupling impedance in the zero-sequence system of the parallel line


ZL: positive-sequence impedance

| kG , par |

2
2
X 00
+ R00

3 X L2 + RL2

kG Anglepar = arctan

X 00
R00

- arctan

XL
RL

R00: resistance component of coupling impedance in the zero-sequence system


of the double-circuit line
RL: resistance component of positive-sequence impedance
X00: reactance component of coupling impedance in the zero-sequence system
of the double-circuit line
XL: reactance component of positive-sequence impedance
If the calculated value cannot be set exactly, then a next smaller value should
be set.
[spacer]

DIST: Mutual comp. P Sx

025 095

0: Without

024 015

024 075

025 035

Fig. 3-109, (p. 3-152)

[spacer]

This setting determines whether distance protection operates with or without


zero current compensation.

[spacer]

DIST: IN,par> PSx


0.20

012 184

0.10

2.00

Inom

012 185

012 186

012 187

Fig. 3-109, (p. 3-152)

[spacer]

The residual current of the parallel line is monitored to determine whether it


exceeds the set threshold. This monitoring function is only used for signaling
purposes and has no functional effects on distance measurement.

[spacer]

DIST: Trip zone 1 PG PS x


3: 3-pole

[spacer]

DIST: Trip zone 2 PG PS x

011 050

011 051

011 052

011 053

Fig. 3-134, (p. 3-182)


010 171

010 172

010 173

010 174

3: 3-pole
[spacer]

For zone 1 and zone 2 the user can specify whether the distance trip in the
event of phase-to-ground faults shall be single-pole or three-pole.
Note: When the P437 is being operated with ARC, which will carry out a
reclosure in the event of a single-pole or three-pole trip, then the setting here
should be 1-pole.

[spacer]

DIST: Trip zone 1 PP PS x


3: 3-pole

P437/EN M/R-11-A // P437311650

011 054

011 055

011 056

011 057

Fig. 3-134, (p. 3-182)

7-179

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

DIST: Trip zone 2 PP PS x

Logic Diagram
010 175

010 176

010 177

010 178

3: 3-pole
[spacer]

For zone 1 and zone 2 the user can specify whether the distance trip in the
event of phase-to-phase faults shall be single-pole or three-pole. Where a singlepole trip has been selected, there is a choice as to whether the trip in the event
of a two-pole starting should be for the leading or the trailing phase.
Note: When the P437 is being operated with ARC, which will carry out a
reclosure in the event of a single-pole or three-pole trip, then the setting here
should be 1-pole leading phase or 1-pole trailing phas.
Parameter
Default

Power swing
blocking

Address
Min

Max

Unit

PSB: Enab le PS x

015 090

0: No
[spacer]

Logic Diagram
015 091

015 092

015 093

Fig. 3-135, (p. 3-183)

This setting defines the setting group in which the power swing blocking function
is enabled.
Parameter
Default

Address
Min

Max

Unit

Backup overcurrent- BUOC: I> PS x


time protection
1.00

Logic Diagram
010 058

0.10

20.00

Inom

010 078

010 098

011 018

Fig. 3-152, (p. 3-207)

[spacer]

Setting for operate threshold I> of the phase current of the backup overcurrenttime protection.

[spacer]

BUOC: tI> PS x
1.00

010 059

0.00

10.00

010 079

010 099

Fig. 3-152, (p. 3-207)

[spacer]

Setting for the operate delay of stage I> of the backup overcurrent-time
protection.

[spacer]

BUOC: IN> PS x
0.20

[spacer]

010 064

0.10

20.00

Inom

011 019

010 084

011 004

011 024

Fig. 3-152, (p. 3-207)

Operate value setting for the residual current of the backup overcurrent-time
protection function.
Note: For isolated / compensated networks it is possible to use the residual
stage as a backup; in this case the operate threshold has to be set greater than
the maximum ground-fault current (earth-fault current).

[spacer]

BUOC: tIN> PSx


1.00

[spacer]

7-180

010 065

0.00

10.00

010 085

011 005

011 025

Fig. 3-152, (p. 3-207)

Operate delay for the backup overcurrent-time protection.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default

Switch on to fault
protection

Address
Min

Max

Unit

SOT F : Enab le PS x

Logic Diagram
001 203

0: No

001 204

001 205

001 206

Fig. 3-154, (p. 3-210)

[spacer]

This setting defines the parameter subset in which function group SOTF is
enabled.

[spacer]

SOT F : Operating mode PS x

011 061

4: Trip with starting

001 184

001 185

001 186

Fig. 3-154, (p. 3-210)

[spacer]

The setting of the operating mode defines whether, while the timer is running, a
general starting will lead to a trip command (Trip with starting) or if the
measuring range of the impedance zone 1 is extended by the set zone extension
factor DIST : k ze,PG HSR P S x (Trip with overreach).

[spacer]

SOT F : Activation mode PS x

006 142

1: Trigger

006 143

Select the SOTF activation mode (either Trigger or Line Dead State).

[spacer]

SOT F : Man. close t ime r P Sx


0.00

10.00

011 060

001 181

Setting for the timer stage that will be started by a manual close.

[spacer]

SOT F : With V< e nabl e PSx

006 005

0: No

[spacer]

[spacer]

0.00

006 138

600.00

SOT F : Releas e delay PS x


1.00

001 183

006 006

006 007

006 008

Fig. 3-155, (p. 3-211)

SOT F : Operate delay PS x


110.00

001 182

Fig. 3-154, (p. 3-210)

[spacer]

[spacer]

006 145

Fig. 3-154, (p. 3-210)

[spacer]

1.00

006 144

0.00

006 140

006 141

Fig. 3-155, (p. 3-211)


002 128

10.00

006 139

002 129

002 133

002 134

Fig. 3-155, (p. 3-211)

If SOT F: Wit h V< e nable P Sx is set to Yes, then a Line dead condition is
determined if all 3 measured voltages are below a fixed threshold, conditioned
by settable operate and release timer stages.
If the Line dead condition is fulfilled either triggering of SOTF through binary
input is enabled or SOTF is permanently activated, depending on the SOTF
activation mode.

[spacer]

SOT F : Tripping t ime PSx


0.00

0.00

010 218

10.00

[spacer]

Setting for the time delay of SOTF tripping.

[spacer]

SOT F : I> PSx


Blocked

20.00

Inom

[spacer]

Setting for the phase current operate value I>.

[spacer]

SOT F : tI> PS x
0.00

[spacer]

10.00

010 222

006 131

006 132

006 133

Fig. 3-153, (p. 3-209)

006 134

0.00

010 221

Fig. 3-154, (p. 3-210)

006 130

0.10

010 219

006 135

006 136

006 137

Fig. 3-153, (p. 3-209)

Setting for the operate delay of stage I>.

P437/EN M/R-11-A // P437311650

7-181

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

SOT F : Evaluation IN PS x

Logic Diagram
001 191

1: Calculated

001 192

001 193

Fig. 3-153, (p. 3-209)

[spacer]

This setting defines which residual current will be monitored: the residual
current calculated from the three phase currents or the residual current
measured at the T 4 transformer.

[spacer]

SOT F : IN> (me as.) PSx


Blocked

[spacer]

0.01

001 189

4.00

Inom

SOT F : IN> (calc.) PSx


Blocked

0.10

Inom

001 196

001 198

001 199

[spacer]

SOT F : tIN> PS x

[spacer]

7-182

001 177

10.00

001 202

Fig. 3-153, (p. 3-209)

Settings for operate values of neutral current IN> (meas.) and IN> (calc.).

0.00

001 197

Fig. 3-153, (p. 3-209)


001 190

4.00

001 195

[spacer]

0.00

001 194

001 178

001 179

001 180

Fig. 3-153, (p. 3-209)

Setting for the operate delay of stages IN> (meas.) or IN> (calc.).

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default

Protective signaling

Address
Min

Max

PSIG: Enab le PS x
0: No

Unit

Logic Diagram
015 014

015 015

015 016

Fig. 3-156, (p. 3-213)

[spacer]

This setting defines the parameter subset in which protective signaling is


enabled.

[spacer]

PSIG: No. t ele co m. ch. P Sx


1: 1 channel

015 017

015 026

024 012

024 072

025 032

Fig. 3-164, (p. 3-219)


Fig. 3-165, (p. 3-220)
Fig. 3-166, (p. 3-221)
Fig. 3-167, (p. 3-222)
Fig. 3-169, (p. 3-223)
Fig. 3-170, (p. 3-224)
Fig. 3-172, (p. 3-227)
Fig. 3-173, (p. 3-228)
Fig. 3-175, (p. 3-230)
Fig. 3-176, (p. 3-231)
Fig. 3-180, (p. 3-234)
Fig. 3-183, (p. 3-238)
Fig. 3-184, (p. 3-239)

[spacer]

Setting for the number of communication channels for protective signaling.

[spacer]

PSIG: Blk.f.t elcom.flt PS x


1: Ch. (A)OR(B) faulty

012 246

012 247

012 248

012 249

Fig. 3-159, (p. 3-216)

[spacer]

Depending on this setting the Protective Signaling gets blocked if the


communication is faulty on either channel (setting value Ch. (A)OR(B) faulty), or
on both channels (setting value Ch. (A)AND(B) faulty).

[spacer]

PSIG: Operating mode PS x


2: PUTT

015 000

024 060

025 020

Fig. 3-162, (p. 3-218)

[spacer]

Setting for the operating mode of protective signaling.

[spacer]

PSIG: Oper. mode s end P Sx


1: Direct.-dependent

024 000

015 036

015 037

015 040

015 041

Fig. 3-172, (p. 3-227)


Fig. 3-175, (p. 3-230)
Fig. 3-177, (p. 3-232)

[spacer]

This setting defines whether protective signaling generates the send signal as a
function of direction or distance.

[spacer]

PSIG: Oper. mode t rip P S x


2: Dist.-dependent

015 107

015 108

015 113

015 114

Fig. 3-170, (p. 3-224)


Fig. 3-173, (p. 3-228)
Fig. 3-176, (p. 3-231)
Fig. 3-177, (p. 3-232)

[spacer]

This setting defines whether a trip triggered by protective signaling will be a


function of direction or distance.

P437/EN M/R-11-A // P437311650

7-183

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

PSIG: Tripping time PS x


0.08

0.00

Logic Diagram
015 011

10.00

024 003

024 063

Fig. 3-157, (p. 3-214)

[spacer]

The tripping time replaces timer stage t1,ze of distance protection when
protective signaling is ready.

[spacer]

PSIG: Re lease t. se nd PSx


0.25

0.00

015 002

10.00

025 023

024 001

024 061

025 021

Fig. 3-164, (p. 3-219)


Fig. 3-166, (p. 3-221)
Fig. 3-172, (p. 3-227)
Fig. 3-175, (p. 3-230)
Fig. 3-184, (p. 3-239)

[spacer]

This setting determines the duration of the send signal.

[spacer]

PSIG: Echo on recei ve P S x

015 003

0: Without

024 002

024 062

025 022

Fig. 3-183, (p. 3-238)

[spacer]

This setting determines whether protective signaling operates with or without


echo.

[spacer]

PSIG: Op. delay e cho P Sx


0.00

0.00

015 022

10.00

[spacer]

Setting for the operate delay of the echo pulse.

[spacer]

PSIG: Pulse dur. echo P Sx


0.10

0.00

[spacer]

Setting for echo pulse duration.

[spacer]

PSIG: Trip s ignal V< P S x

024 009

024 069

024 007

024 067

This setting determines whether a trip signal will be issued when the weakinfeed logic is triggered.

[spacer]

PSIG: V< weak infee d PSx


0.10

015 020

0.90

Setting for the threshold of the weak infeed logic.

[spacer]

PSIG: tV< PS x

015 019

0.00

10.00

[spacer]

Setting for the operate delay of weak-infeed logic.

[spacer]

PSIG: St art cond. t V< P Sx


1: V<

[spacer]

7-184

025 027

024 006

024 066

025 026

Vnom(/3) Fig. 3-182, (p. 3-236)

[spacer]

0.20

025 029

Fig. 3-182, (p. 3-236)

[spacer]

0.60

025 028

Fig. 3-183, (p. 3-238)

015 021

0: No

024 068

Fig. 3-183, (p. 3-238)

015 023

10.00

024 008

024 005

024 065

025 025

Fig. 3-182, (p. 3-236)

006 148

006 149

006 150

006 151

Fig. 3-182, (p. 3-236)

Select whether the undervoltage timer stage is started if the undervoltage


condition is present (V<), or if both the undervoltage condition and the weakinfeed starting are present (V< & WI start).

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

PSIG: tBlock PSx


0.05

Logic Diagram
015 024

0.00

10.00

024 010

025 030

Fig. 3-161, (p. 3-217)

[spacer]

Setting for the transient blocking time of protective signaling.

[spacer]

PSIG: 3ende d line prot PS x


0: No

024 070

006 039

006 046

006 047

006 048

Fig. 3-158, (p. 3-215)

[spacer]

Select whether the PS IG: Re ce ive ( A) E XT or PSIG: Receive (B ) EXT


signals shall be used in an OR combination (setting: No) or in an AND
combination (setting: Yes).

[spacer]

PSIG: Fre quency monit. PS x


0: No

[spacer]

015 025

024 011

024 071

025 031

Fig. 3-160, (p. 3-216)

This setting defines whether failure of frequency transmission will be monitored.

P437/EN M/R-11-A // P437311650

7-185

P437

7 Settings

Parameter
Default

Auto-reclosing
control

Address
Min

Max

Unit

ARC: Enable PS x

Logic Diagram
015 046

0: No

015 047

015 048

015 049

Fig. 3-186, (p. 3-242)

[spacer]

This setting defines the parameter subset in which ARC is enabled.

[spacer]

ARC: C B clos.pos .s ig. PS x

015 050

0: Without

024 024

024 084

025 044

Fig. 3-187, (p. 3-243)

[spacer]

This setting defines whether the CB closed position will be taken into account or
not. If the setting is With, a binary signal input must be configured accordingly.
Then the ARC function is ready only if the CB is closed.

[spacer]

ARC: Op erating mode P Sx

015 100

1: HSR/TDR permitted

015 101

015 102

015 103

Fig. 3-185, (p. 3-240)

[spacer]

This setting defines whether the ARC will carry out HSR and TDR, only TDR, or
only a test HSR.

[spacer]

ARC: Op erative time 1 P Sx


0.30

[spacer]

0.00

015 066

10.00

024 035

024 095

025 055

Fig. 3-204, (p. 3-271)

Setting for operative time 1.


If the fault is cleared within this time, the fixed dead time 1p or 3p (depending
on the trip condition and HSR operating mode) is started.

[spacer]

ARC: Op erative time 2 P Sx


0.30

[spacer]

0.00

015 083

10.00

024 042

025 002

025 062

Fig. 3-204, (p. 3-271)

Setting for operative time 2.


If the fault is cleared within this time, the maximum dead time is started.

[spacer]

ARC: HSR op er. mode PS x

015 051

3: 3-pole

024 025

024 085

025 045

Fig. 3-190, (p. 3-246)


Fig. 3-191, (p. 3-248)

[spacer]

The selection for the HSR operating mode defines whether a single-pole, single-/
three-pole, or three-pole HSR shall take place.
Note: If a single-pole HSR is to be carried out, then the user must select the 1pole setting at either DIST : Tr ip z one 1 P G P Sx or DIST: Trip zone 1
PP PS x, and at either DIST : Trip zone 2 P G PSx or DIST: Trip zone
2 PP PS x.

[spacer]

ARC: T rip tim e HSR PS x


0.08

[spacer]

7-186

0.00

015 072

10.00

024 040

025 000

025 060

Fig. 3-189, (p. 3-245)

The HSR tripping time replaces timer stage t1,ze of distance protection or the
operate delay of backup overcurrent-time protection provided that the BUOC
operating mode is set accordingly if a HSR is permitted and protective
signaling is not ready.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

ARC: HSR op er. mode 2 PS x

Logic Diagram
015 044

2: Start-dependent

024 022

024 082

025 042

Fig. 3-191, (p. 3-248)

[spacer]

This setting defines whether ARC will be controlled by the starting decisions
(Start-dependent) or the trip decisions (Trip-dependent).

[spacer]

ARC: Dead tim e 1p PSx


1.00

0.10

015 055

600.00

[spacer]

Dead time setting for a single-pole HSR.

[spacer]

ARC: Dead tim e 3p PSx


1.00

0.10

600.00

Dead time setting for a three-pole HSR.

[spacer]

ARC: Dead tim e max P Sx


0.10

600.00

Setting for the maximum dead time.

[spacer]

ARC: t Discrim. PSx

600.00

024 030

024 090

025 050

024 043

025 003

025 063

Fig. 3-204, (p. 3-271)

018 051

0.00

025 049

Fig. 3-204, (p. 3-271)

015 084

[spacer]

1.00

024 089

Fig. 3-204, (p. 3-271)

015 056

[spacer]

1.00

024 029

024 049

025 009

025 069

Fig. 3-204, (p. 3-271)

[spacer]

Setting for the discrimination time during which there will be a switch from a
single-pole HSR to a three-pole HSR when a secondary fault occurs.

[spacer]

ARC: Zone e x t . f. HS R P Sx

015 059

0: No
[spacer]

024 033

024 093

025 053

Fig. 3-200, (p. 3-267)

This setting determines whether the measuring range shall be extended by the
zone extension factor kze HSR during normal system operation and while the
operative times are elapsing.
Note: This setting is only active if protective signaling is not ready.

[spacer]

ARC: No. permit . T DR PS x


0

015 068

024 037

024 097

025 057

Fig. 3-204, (p. 3-271)

[spacer]

Setting for the number of time-delayed reclosures permitted. With the 0 setting,
only one HSR is carried out.

[spacer]

ARC: T rip tim e TDR PS x


0.08

0.00

015 073

10.00

024 041

025 001

025 061

Fig. 3-189, (p. 3-245)

[spacer]

The TDR tripping time replaces timer stage t1,ze of distance protection or the
operate delay of backup overcurrent-time protection provided that the BUOC
operating mode is set accordingly if a TDR is permitted and protective
signaling is not ready.

[spacer]

ARC: T DR d ead time PSx


1.00

[spacer]

0.10

015 057

600.00

024 031

024 091

025 051

Fig. 3-204, (p. 3-271)

Setting for the TDR dead time.

P437/EN M/R-11-A // P437311650

7-187

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

ARC: Zone e x t . f . T DR PS x

015 071

0: No

024 039

024 099

025 059

Fig. 3-200, (p. 3-267)

[spacer]

This setting determines whether the measuring range shall be extended prior to
a TDR.

[spacer]

ARC: Enable R R C PSx

015 085

0: No

024 044

025 004

025 064

Fig. 3-198, (p. 3-260)

[spacer]

Enabling the rapid reclosure (RRC) function.

[spacer]

ARC: t RRC PSx


0.20

015 086

0.10

2.00

Setting for the timer stage of rapid reclosure (RRC).

[spacer]

ARC: V> RR C PSx

015 087

0.40

0.90

025 005

025 065

Fig. 3-204, (p. 3-271)

[spacer]

0.75

024 045

024 046

025 006

025 066

Vnom(/3) Fig. 3-198, (p. 3-260)

[spacer]

Setting for the voltage threshold that must be exceeded in order for an RRC to
be carried out.

[spacer]

ARC: Zone e x t .d ur. RC P S x

015 088

0: Without
[spacer]

[spacer]

024 047

025 007

025 067

Fig. 3-200, (p. 3-267)

This setting defines whether the following takes place:

A zone extension will be carried out during a close command by a HSR that
is not synchronism-checked.

Zone extension will occur with each reclose command.

ARC: R eclaim time PS x


1.00

1.00

[spacer]

Setting for the reclaim time.

[spacer]

ARC: Block. tim e int . P Sx


5

015 054

600.00

024 088

025 048

Fig. 3-204, (p. 3-271)

015 043

600

024 028

024 021

024 081

025 041

Fig. 3-188, (p. 3-244)

[spacer]

Setting for the time that will elapse before the ARC will be ready again after
cancellation of the blocks set by internal functions, such as SOTF.

[spacer]

ARC: Block. tim e e xt. PS x


5

015 058

600

024 032

024 092

025 052

Fig. 3-188, (p. 3-244)

[spacer]

Setting for the time that will elapse before the ARC will be ready again after
blocking by a binary signal input.

[spacer]

ARC: Op . m ode ex t ARC PS x


0: Without

[spacer]

7-188

015 045

024 023

024 083

025 043

Fig. 3-201, (p. 3-269)

This setting defines the operating mode for an external ARC working together
with the P437.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

ARC: M on. PS IG re cv . PSx


0: No

Max

Unit

Logic Diagram
015 082

024 050

025 010

025 070

Fig. 3-202, (p. 3-270)

[spacer]

This setting determines whether the number of PSIG receive signals is monitored
during the dead time.

[spacer]

ARC: Paralle l trip PS x


0: Without function

[spacer]

015 053

024 027

024 087

025 047

Fig. 3-204, (p. 3-271)

This setting defines whether and how the trip command(s) of a protection device
operating in parallel to the P437 will affect operation of the ARC function.

P437/EN M/R-11-A // P437311650

7-189

P437

7 Settings

Parameter
Default

Automatic
synchronism check

Address
Min

Max

Unit

ASC: Enab le PS x

Logic Diagram
018 020

0: No

018 021

018 022

018 023

Fig. 3-207, (p. 3-274)

[spacer]

This setting defines the parameter subset in which automatic synchronism check
(ASC) is enabled.

[spacer]

ASC: Active for HSR PS x

018 001

0: No

077 030

078 030

079 030

Fig. 3-208, (p. 3-275)

[spacer]

This setting defines whether reclosing after a three-pole HSR will occur only
after being enabled by ASC.

[spacer]

ASC: Active for TDR PS x

018 002

0: No

077 031

078 031

079 031

Fig. 3-208, (p. 3-275)

[spacer]

This setting defines whether reclosing after a three-pole TDR will occur only
after being enabled by ASC.

[spacer]

ASC: Active for RRC PS x

018 006

077 033

078 033

079 033

0: No
[spacer]

This setting specifies whether enabling by the ASC function is required before
reclosing after a rapid reclosure can occur.

[spacer]

ASC: Clos .rej.w.block PS x

018 003

0: No

077 032

078 032

079 032

Fig. 3-208, (p. 3-275)

[spacer]

This setting defines whether reclosing is rejected after being blocked by ASC.

[spacer]

ASC: Op erative time PS x


100.0

0.0

018 010

6000.0

[spacer]

Setting for the operative time for ASC.

[spacer]

ASC: Me asur e ment loop P Sx

[spacer]

078 034

079 034

Fig. 3-217, (p. 3-287)

031 060

4: Loop A-B

077 034

077 044

078 044

079 044

Fig. 3-206, (p. 3-273)

The voltage measurement loop, corresponding to the reference voltage, must be


selected so that determination of differential values is correct.
Example: Connect transformer T 15 to measure the reference voltage to
phases A & B. The measurement loop should be set to Loop A-B.

[spacer]

ASC: Phi off set PS x


0

018 034

-180

180

077 042

078 042

079 042

Fig. 3-215, (p. 3-285)


Fig. 3-216, (p. 3-286)

[spacer]

Setting for a Phi offset that may be necessary so that determination of the
differential angle is correct.

[spacer]

ASC: AR op. m ode P Sx


1: Voltage-checked

[spacer]

7-190

018 025

018 026

018 027

018 028

Fig. 3-215, (p. 3-285)

Auto-reclosing control: Criteria for a close enable are defined by setting for the
operating mode.
P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

ASC: AR with tCB PSx

Logic Diagram
000 038

000 039

000 050

000 051

0: No
[spacer]

Function ASC provides a choice as to whether the CB operating time (tCB), as


configured at M AI N: tCB ,clos e is to be taken into account for the precisely
synchronized reclosure (AR) or not.

[spacer]

ASC: AR Op.m ode v- chk .P Sx

018 029

1: Vref but not V

018 030

018 031

018 032

Fig. 3-213, (p. 3-282)

[spacer]

Auto-reclosing control: This setting defines the logic linking of trigger decisions
for a voltage controlled close enable.

[spacer]

ASC: AR V> volt.che ck PS x


0.80

[spacer]

0.10

026 017

1.20

077 043

078 043

079 043

Vnom(/3) Fig. 3-213, (p. 3-282)

Auto-reclosing control: Setting the voltage threshold that the phase-to-ground


voltages and the reference voltage must exceed so that they are recognized as
Voltage present.
Note: The logic linking of trigger decisions is defined by setting ASC: AR
Op.mode v-chk.PS x.

[spacer]

ASC: AR V< volt.che ck PS x


0.20

[spacer]

0.10

018 017

1.20

077 040

078 040

079 040

Vnom(/3) Fig. 3-213, (p. 3-282)

Auto-reclosing control: Setting the voltage threshold that the phase-to-ground


voltages and the reference voltage must fall below so that they are recognized
as No voltage.
Note: The logic linking of trigger decisions is defined by setting ASC: AR
Op.mode v-chk.PS x.

[spacer]

ASC: AR tmin v- check PS x


0.10

0.00

018 018

10.00

077 041

078 041

079 041

Fig. 3-213, (p. 3-282)

[spacer]

Auto-reclosing control: Setting for the operate delay value to define the
minimum time period during which voltage conditions must be met so that the
close enable of the ASC is effected.

[spacer]

ASC: AR V> s ync.che ck PS x


0.80

0.40

1.20

018 011

077 035

078 035

Vnom(/3) Fig. 3-215, (p. 3-285)

[spacer]

Auto-reclosing control: Setting for the threshold of the minimum voltage to


obtain a synchronism checked close enable.

[spacer]

ASC: AR delta Vmax PSx


0.10

[spacer]

0.02

018 012

0.40

079 035

Vnom

077 036

078 036

079 036

Fig. 3-215, (p. 3-285)

Auto-reclosing control: Setting the maximum differential voltage between


measured and reference voltages to obtain a synchronism checked close enable.

P437/EN M/R-11-A // P437311650

7-191

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

ASC: AR delta f max PS x


0.20

0.01

Logic Diagram
018 014

2.00

Hz

077 038

078 038

079 038

Fig. 3-215, (p. 3-285)

[spacer]

Auto-reclosing control: Setting the maximum differential frequency between


measured and reference voltages to obtain a synchronism checked close enable.

[spacer]

ASC: AR delta p hi max PS x


15

018 013

100

077 037

078 037

079 037

Fig. 3-215, (p. 3-285)

[spacer]

Auto-reclosing control: Setting the maximum differential angle between


measured and reference voltages to obtain a synchronism checked close enable.

[spacer]

ASC: AR tmin sync.chk PS x


0.10

0.00

018 015

10.00

077 039

078 039

079 039

Fig. 3-215, (p. 3-285)

[spacer]

Auto-reclosing control: Setting for the operate delay value to define the
minimum time period during which synchronism conditions must be met so that
the close enable of the ASC is effected.

[spacer]

ASC: MC op. mod e P Sx

000 056

1: Voltage-checked

000 057

000 058

000 059

Fig. 3-216, (p. 3-286)

[spacer]

Manual close command: Criteria for a close enable are defined by setting for the
operating mode.

[spacer]

ASC: MC wit h tCB P Sx

000 102

000 103

000 104

000 105

0: No
[spacer]

Manual close command: In slightly asynchronous power systems, setting this


parameter to Yes ensures that the circuit breaker closing time is taken into
account by the automatic synchronism check (ASC) to issue of a close
command.

[spacer]

ASC: MC op.mode v- chk. PSx


1: Vref but not V

000 060

000 061

000 062

000 063

Fig. 3-214, (p. 3-283)

[spacer]

Manual close command: This setting defines the logic linking of trigger decisions
for a voltage controlled close enable.

[spacer]

ASC: MC V> volt .che ck PSx


0.80

[spacer]

0.10

000 064

1.20

000 065

000 066

000 067

Vnom(/3) Fig. 3-214, (p. 3-283)

Manual close command: Setting the voltage threshold that the phase-to-ground
voltages and the reference voltage must exceed so that they are recognized as
Voltage present.
Note: The logic linking of trigger decisions is defined by setting ASC: MC
op.mode v-chk .PS x.

7-192

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Min

Max

Unit

ASC: MC V< volt .che ck PSx


0.20

[spacer]

Address

0.10

Logic Diagram
000 068

1.20

000 069

000 070

000 071

Vnom(/3) Fig. 3-214, (p. 3-283)

Manual close command: Setting the voltage threshold that the phase-to-ground
voltages and the reference voltage must fall below so that they are recognized
as No voltage.
Note: The logic linking of trigger decisions is defined by setting ASC: MC
op.mode v-chk .PS x.

[spacer]

ASC: MC tm in v-che ck P Sx
0.10

0.00

000 072

10.00

000 073

000 074

000 075

Fig. 3-214, (p. 3-283)

[spacer]

Manual close command: Setting for the operate delay value to define the
minimum time period during which voltage conditions must be met so that the
close enable of the ASC is effected.

[spacer]

ASC: MC V> sync .che ck P Sx


0.80

0.40

1.20

000 052

000 053

000 054

000 055

Vnom(/3) Fig. 3-216, (p. 3-286)

[spacer]

Manual close command: Setting for the threshold of the minimum voltage to
obtain a synchronism checked close enable.

[spacer]

ASC: MC delta Vmax PS x


0.10

0.02

000 080

0.40

Vnom

000 081

000 082

000 083

Fig. 3-216, (p. 3-286)

[spacer]

Manual close command: Setting the maximum differential voltage between


measured and reference voltages to obtain a synchronism checked close enable.

[spacer]

ASC: MC delta f max P Sx


0.20

0.01

000 084

2.00

Hz

000 086

000 087

000 088

Fig. 3-216, (p. 3-286)

[spacer]

Manual close command: Setting the maximum differential frequency between


measured and reference voltages to obtain a synchronism checked close enable.

[spacer]

ASC: MC delta phi max P Sx


15

000 089

100

000 091

000 092

000 093

Fig. 3-216, (p. 3-286)

[spacer]

Manual close command: Setting the maximum differential angle between


measured and reference voltages to obtain a synchronism checked close enable.

[spacer]

ASC: MC tm in s ync.chk PS x
0.10

[spacer]

0.00

000 098

10.00

000 099

000 100

000 101

Fig. 3-216, (p. 3-286)

Manual close command: Setting for the operate delay value to define the
minimum time period during which synchronism conditions must be met so that
the close enable of the ASC is effected.

P437/EN M/R-11-A // P437311650

7-193

P437

7 Settings

Parameter
Default

Ground fault (shortcircuit) protection

Address
Min

Max

Unit

GFS C: Enable PSx

018 072

0: No
[spacer]

Logic Diagram
018 073

018 074

Fig. 3-220, (p. 3-291)

This setting defines the parameter subset in which ground fault (short-circuit)
protection is enabled.
Parameter
Default

Ground fault (shortcircuit) protection


signaling

GSCSG: Enable PSx

0: No
[spacer]

7-194

018 075

Address
Min

Max

Unit

Logic Diagram
023 071

023 072

023 073

023 074

Fig. 3-238, (p. 3-310)

This setting defines the parameter subset in which ground fault (short-circuit)
protection signaling is enabled.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default

Definite-time over
current protection

Address
Min

Max

Unit

DTOC: Enable PSx

Logic Diagram
072 098

0: No

073 098

074 098

075 098

Fig. 3-249, (p. 3-323)

[spacer]

This setting defines the parameter subset in which definite-time overcurrent


protection is enabled.

[spacer]

DTOC: I> PS x
1.00

[spacer]

20.00

Inom

0.10

20.00

Inom

20.00

Inom

DTOC: I>>>> PSx


1.00

20.00

Inom

[spacer]

Setting for operate value of the overcurrent stage.

[spacer]

DTOC: tI> PSx


1.00

[spacer]

0.00

30.00

30.00

DTOC: tI>>>> PSx


1.00

30.00

Setting for the operate delay of the overcurrent stage.

[spacer]

DTOC: Ineg> PSx

[spacer]

Inom

0.10

20.00

Inom

20.00

Inom

DTOC: Ineg>>>> PSx


1.00

0.10

Inom

074 010

075 010

073 019

074 019

075 019

073 020

074 020

075 020

073 021

074 021

075 021

073 022

074 022

075 022

073 011

074 011

075 011

073 012

074 012

075 012

073 013

074 013

075 013

Fig. 3-251, (p. 3-326)


072 014

20.00

073 010

Fig. 3-251, (p. 3-326)


072 013

0.10

075 009

Fig. 3-251, (p. 3-326)


072 012

DTOC: Ineg>>> PSx


1.00

[spacer]

20.00

DTOC: Ineg>> PSx


1.00

[spacer]

072 011

0.10

074 009

Fig. 3-250, (p. 3-324)

[spacer]

1.00

073 009

Fig. 3-250, (p. 3-324)


072 022

0.00

075 008

Fig. 3-250, (p. 3-324)


072 021

0.00

074 008

Fig. 3-250, (p. 3-324)


072 020

DTOC: tI>>> PSx


1.00

[spacer]

DTOC: tI>> PSx


1.00

[spacer]

30.00

073 008

Fig. 3-250, (p. 3-324)

072 019

0.00

075 007

Fig. 3-250, (p. 3-324)


072 010

0.10

074 007

Fig. 3-250, (p. 3-324)


072 009

0.10

073 007

Fig. 3-250, (p. 3-324)


072 008

DTOC: I>>> PS x
1.00

[spacer]

0.10

DTOC: I>> PS x
1.00

[spacer]

072 007

073 014

074 014

075 014

Fig. 3-251, (p. 3-326)

[spacer]

Setting for the operate value of the overcurrent stage of the negative-sequence
system.

[spacer]

DTOC: tIneg > PSx


1.00

072 023

0.00

30.00

073 023

074 023

075 023

Fig. 3-251, (p. 3-326)


Fig. 3-257, (p. 3-332)

P437/EN M/R-11-A // P437311650

7-195

P437

7 Settings

Parameter
Default
[spacer]

Max

Unit

Logic Diagram
072 024

0.00

30.00

072 025

0.00

30.00

0.00

072 026

30.00

074 024

075 024

073 025

074 025

075 025

Fig. 3-251, (p. 3-326)

DTOC: tIneg >>>> P Sx


1.00

073 024

Fig. 3-251, (p. 3-326)

DTOC: tIneg >>> PSx


1.00

[spacer]

Min

DTOC: tIneg >> PSx


1.00

[spacer]

Address

073 026

074 026

075 026

Fig. 3-251, (p. 3-326)

[spacer]

Setting for the operate delay of the overcurrent stage of the negative-sequence
system.

[spacer]

DTOC: tIneg > (1p HSR ) P Sx

002 160

0: Normal
[spacer]

002 161

002 162

002 163

Fig. 3-257, (p. 3-332)

DTOC: tIneg >> (1pHSR ) P Sx

002 164

002 165

002 166

002 167

002 168

002 169

002 170

002 171

002 172

002 173

002 174

002 175

0: Normal
[spacer]

DTOC: tIneg >>> (1pHSR ) P Sx


0: Normal

[spacer]

DTOC: tIneg >>>>(1 pHS R) P Sx


0: Normal

[spacer]

Setting for the operating mode of the DTOC timer stages for the negativesequence system during the 1-pole dead time of the high-speed reclosure (HSR)
of an ARC cycle. (See: Settable operation mode during 1-pole dead time of
HSR.)

[spacer]

DTOC: Evaluat ion IN P S x

073 189

2: Measured

073 190

073 202

073 219

Fig. 3-252, (p. 3-327)

[spacer]

This setting defines which residual current will be monitored by the residual
current stages: the residual current calculated from the three phase currents or
the residual current measured at the T 4 transformer.

[spacer]

DTOC: IN> PS x
1.00

072 015

0.10

20.00

Inom

Setting for operate value IN> (IN= residual current).

[spacer]

DTOC: IN>> PS x

072 016

0.10

20.00

Inom

Setting for operate value IN>> (IN= residual current).

[spacer]

DTOC: IN>>> PS x

[spacer]

7-196

072 017

0.10

20.00

Inom

075 015

073 016

074 016

075 016

Fig. 3-253, (p. 3-328)

[spacer]

1.00

074 015

Fig. 3-253, (p. 3-328)

[spacer]

1.00

073 015

073 017

074 017

075 017

Fig. 3-253, (p. 3-328)

Setting for operate value IN>>> (IN= residual current).

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Min

Max

Unit

DTOC: IN>>>> PS x
1.00

[spacer]

Address
Logic Diagram
072 018

0.10

20.00

Inom

073 018

074 018

075 018

Fig. 3-253, (p. 3-328)

Setting the operate value of the fourth overcurrent stage (residual current
stage).
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Chapter Technical Data).

[spacer]

DTOC: tIN tim er start P Sx

002 138

002 139

002 142

002 143

1: With starting
[spacer]

With this setting the triggering of the timers for the residual current system can
now be set as direction-dependent.

[spacer]

DTOC: tIN> PSx


1.00

072 027

0.00

30.00

073 027

074 027

075 027

Fig. 3-253, (p. 3-328)


Fig. 3-258, (p. 3-333)
Fig. 3-259, (p. 3-334)

[spacer]

Setting for the operate delay of overcurrent stage IN>.

[spacer]

DTOC: tIN>> PSx


1.00

072 028

0.00

30.00

Setting for the operate delay of overcurrent stage IN>>.

[spacer]

DTOC: tIN>>> PSx

072 029

0.00

30.00

Setting for the operate delay of overcurrent stage IN>>>.

[spacer]

DTOC: tIN>>>> PSx

072 030

0.00

30.00

073 029

074 029

075 029

073 030

074 030

075 030

Fig. 3-253, (p. 3-328)

[spacer]

Setting for the operate delay of overcurrent stage IN>>>>.

[spacer]

DTOC: tIN> (1pHSR ) P Sx


0: Normal

075 028

Fig. 3-253, (p. 3-328)

[spacer]

1.00

074 028

Fig. 3-253, (p. 3-328)

[spacer]

1.00

073 028

002 144

002 145

002 146

002 147

Fig. 3-258, (p. 3-333)


Fig. 3-259, (p. 3-334)

[spacer]

DTOC: tIN>> (1pHSR ) P Sx

002 148

002 149

002 150

002 151

002 152

002 153

002 154

002 155

002 156

002 157

002 158

002 159

0: Normal
[spacer]

DTOC: tIN>>> (1pHSR) PSx


0: Normal

[spacer]

DTOC: tIN>>>> (1pHSR) PSx


0: Normal

[spacer]

Setting for the operating mode of the DTOC timer stages for the residual current
system during the 1-pole dead time of the high-speed reclosure (HSR) of an ARC
cycle. (See: Settable operation mode during 1-pole dead time of HSR.)

P437/EN M/R-11-A // P437311650

7-197

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

DTOC: VNG> PSx


0.030

Logic Diagram
010 045

0.010

0.500

Vnom

010 060

010 080

Fig. 3-255, (p. 3-329)

[spacer]

This setting defines the threshold value that the neutral-point displacement
voltage must exceed so that the direction determination is enabled.

[spacer]

DTOC: Angle phi N P Sx


0

-90

004 092

90

010 139

004 247

004 248

004 249

Fig. 3-255, (p. 3-329)

[spacer]

Setting for the position of the straight line separating forward and backward
(reverse) directions.

[spacer]

DTOC: Direction t IN> P Sx

072 032

1: Forward directional

072 042

072 082

072 091

Fig. 3-256, (p. 3-330)


Fig. 3-258, (p. 3-333)
Fig. 3-259, (p. 3-334)

[spacer]

DTOC: Direction t IN>> P Sx

072 033

1: Forward directional
[spacer]

072 083

DTOC: Direction t IN>>> P Sx

072 034

072 044

072 084

072 093

Fig. 3-256, (p. 3-330)

DTOC: Direction t IN>>>>PS x

072 035

1: Forward directional

072 045

072 085

072 094

Fig. 3-256, (p. 3-330)

[spacer]

The setting for the measurement direction determines the measurement


direction of the residual current stages.

[spacer]

DTOC: Puls.prol.I N>,int PSx


0.08

072 092

Fig. 3-256, (p. 3-330)

1: Forward directional
[spacer]

072 043

0.00

017 055

10.00

073 042

074 042

075 042

Fig. 3-260, (p. 3-335)

[spacer]

Setting for the pulse prolongation time of the hold-time logic for intermittent
ground faults.

[spacer]

DTOC: tIN>,inte rm. P Sx


Blocked

0.00

017 056

100.00

073 038

074 038

075 038

Fig. 3-260, (p. 3-335)

[spacer]

Setting for the tripping time of the hold-time logic for intermittent ground faults.

[spacer]

DTOC: Hold- t. tI N>,int mPSx


0.0

[spacer]

7-198

0.0

600.0

017 057

073 039

074 039

075 039

Fig. 3-260, (p. 3-335)

Setting for the hold-time for intermittent ground faults.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default

Address
Min

Max

Unit

Inverse-time overcur IDMT: E nable PSx


rent protection

Logic Diagram
072 070

0: No

073 070

074 070

075 070

Fig. 3-263, (p. 3-338)

[spacer]

This setting defines the parameter subset in which IDMT protection is enabled.

[spacer]

IDMT: I ref ,P PSx


1.00

072 050

0.10

4.00

Inom

Setting for the reference current (phase current system).

[spacer]

IDMT: F actor KI,P PS x


1.00

007 250

10.00

074 050

075 050

Fig. 3-269, (p. 3-345)

[spacer]

1.00

073 050

007 251

007 252

007 253

Fig. 3-269, (p. 3-345)

[spacer]

Enable threshold for the IDMT protection starting for all types of characteristics.
This factor KI will result in a linear shifting of the enable threshold along the X
axis of the respective characteristic. The factor will not result in a shifting of the
characteristic itself.

[spacer]

IDMT: C haracte ri stic P PSx

072 056

0: Definite Time

073 056

075 056

Fig. 3-269, (p. 3-345)

[spacer]

Setting for the tripping characteristic (phase current system).

[spacer]

IDMT: F actor k t,P PS x


1.00

074 056

0.05

072 053

10.00

073 053

074 053

075 053

Fig. 3-269, (p. 3-345)

[spacer]

Setting for the factor kt,P of the starting characteristic (phase current system).

[spacer]

IDMT: M in. trip t ime P PS x


1.00

0.00

072 077

10.00

073 077

074 077

075 077

Fig. 3-269, (p. 3-345)

[spacer]

Setting for the minimum trip time (phase current system). As a rule, this value
should be set as for the first DTOC stage (I>).

[spacer]

IDMT: Hold t ime P PSx


0.00

0.00

072 071

600.00

073 071

074 071

Fig. 3-269, (p. 3-345)

[spacer]

Setting for the holding time for intermittent short circuits (phase current
system).

[spacer]

IDMT: R e le as e P PS x

072 059

1: Without delay

073 059

074 059

Setting for the release or reset characteristic (phase current system).

[spacer]

IDMT: I ref ,neg PS x

[spacer]

075 059

Fig. 3-269, (p. 3-345)

[spacer]

1.00

075 071

072 051

0.01

4.00

Inom

073 051

074 051

075 051

Fig. 3-270, (p. 3-347)

Setting for the reference current (negative-sequence current system).

P437/EN M/R-11-A // P437311650

7-199

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

IDMT: F actor KI,ne g PS x


1.00

1.00

Logic Diagram
007 254

10.00

007 255

008 002

008 005

Fig. 3-270, (p. 3-347)

[spacer]

Enable threshold for the IDMT protection starting for all Ineg types of
characteristics. This factor KI will result in a linear shifting of the enable
threshold along the X axis of the respective characteristic. The factor will not
result in a shifting of the characteristic itself.

[spacer]

IDMT: C haracter. ne g. P Sx

072 057

0: Definite Time

073 057

074 057

Fig. 3-270, (p. 3-347)

[spacer]

Setting for the tripping characteristic (negative-sequence current system).

[spacer]

IDMT: F actor k t,ne g PS x


1.00

075 057

0.05

072 054

10.00

073 054

074 054

075 054

Fig. 3-270, (p. 3-347)

[spacer]

Setting for the factor kt,neg of the starting characteristic (negative-sequence


current system).

[spacer]

IDMT: M in.trip time ne gP Sx


1.00

0.00

10.00

072 078

073 078

074 078

Fig. 3-270, (p. 3-347)

[spacer]

Setting for the minimum trip time (negative-sequence current system).


As a rule, this value should be set as for the first DTOC stage (I>).

[spacer]

IDMT: Hold t ime neg PSx


0.00

0.00

072 072

600.00

073 072

074 072

075 072

Fig. 3-270, (p. 3-347)

[spacer]

Setting the holding time for intermittent short circuits (negative-sequence


current system).

[spacer]

IDMT: R e le as e neg. PSx

072 060

1: Without delay

075 078

073 060

074 060

075 060

Fig. 3-270, (p. 3-347)

[spacer]

Setting for the release or reset characteristic (negative-sequence current


system).

[spacer]

IDMT: E valuatio n IN P Sx

072 075

2: Measured

073 075

074 075

075 075

Fig. 3-271, (p. 3-348)

[spacer]

This setting defines which residual current will be monitored by the residual
current stages: the residual current calculated from the three phase currents or
the residual current measured at the T 4 transformer.

[spacer]

IDMT: I ref ,N PS x
1.00

[spacer]

072 052

0.01

4.00

Inom

073 052

074 052

075 052

Fig. 3-272, (p. 3-349)

Setting for the reference current (residual current system).


Depending on the setting of IDMT: E val uation IN PSx, either the
calculated or the measured reference current is used.

7-200

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

IDMT: F actor KI,N PS x


1.00

1.00

Logic Diagram
001 173

10.00

001 174

001 175

001 176

Fig. 3-272, (p. 3-349)

[spacer]

The set factor I D MT: Fact or KI, N PS x is multiplied by the reference


quantity Iref,N in order to constitute the minimum operate value for the current
in the residual current measuring system.

[spacer]

IDMT: C haracte ri stic N P Sx

072 058

0: Definite Time

073 058

075 058

Fig. 3-272, (p. 3-349)

[spacer]

Setting for the tripping characteristic (residual current system).

[spacer]

IDMT: F actor k t,N P S x


1.00

074 058

0.05

072 055

10.00

073 055

074 055

075 055

Fig. 3-272, (p. 3-349)

[spacer]

Setting for the factor kt,N of the starting characteristic (residual current system).

[spacer]

IDMT: M in. trip t ime N P S x


1.00

0.00

072 079

10.00

073 079

074 079

075 079

Fig. 3-272, (p. 3-349)

[spacer]

Setting for the minimum trip time for the residual current measuring system.
This timer stage is started as soon as the minimum operate value is exceeded.
After the timer has elapsed, the trip signal is issued, regardless of the value of
the current.

[spacer]

IDMT: Hold t ime N P Sx


0.00

0.00

072 073

600.00

073 073

074 073

Fig. 3-272, (p. 3-349)

[spacer]

Setting for the holding time for intermittent short circuits (residual current
system).

[spacer]

IDMT: R e le as e N PSx
1: Without delay

[spacer]

075 073

072 061

073 061

074 061

075 061

Fig. 3-272, (p. 3-349)

Setting for for the reset characteristic (residual current system).

P437/EN M/R-11-A // P437311650

7-201

P437

7 Settings

Parameter
Default

Thermal overload
protection

Address
Min

Max

Unit

THER M : Enable PSx

Logic Diagram
072 175

0: No

073 175

074 175

075 175

Fig. 3-274, (p. 3-351)

[spacer]

This setting defines the parameter subset in which thermal overload protection
is enabled.

[spacer]

THER M : Ir ef PSx
1.00

072 179

0.10

4.00

[spacer]

Setting for the reference current.

[spacer]

THER M : S tar t .f act.OL_RC PS x


1.15

1.05

Inom

Setting for the starting factor to trigger overload recording.

[spacer]

THER M : Tim.const .1 ,>Ibl PSx


1.0

1000.0

075 179

073 180

074 180

075 180

Fig. 3-277, (p. 3-357)

[spacer]

30.0

074 179

Fig. 3-277, (p. 3-357)

072 180

1.50

073 179

072 187

min

073 187

074 187

075 187

Fig. 3-277, (p. 3-357)

[spacer]

Setting for the thermal time constants of the protected object with current flow
(Ibl: base line current).

[spacer]

THER M : Tim.const .2 ,<Ibl PSx


30.0

[spacer]

1.0

1000.0

072 188

min

073 188

074 188

075 188

Fig. 3-277, (p. 3-357)

Setting for the thermal time constants of the protected object without current
flow (cooling time constant).
Note: This setting option is only relevant when machines are running. In all
other cases, time constant 2 must be set equal to time constant 1.

[spacer]

THER M : M ax.obje ct temp. P Sx


120

300

072 182

073 182

074 182

Fig. 3-277, (p. 3-357)

[spacer]

Setting for the maximum permissible temperature of the protected object.

[spacer]

THER M : O/ T f .Iref pe r s. PS x
80

300

072 167

073 167

074 167

Setting for overtemperature resulting from a persistent limit current (max a,max).

[spacer]

THER M : Warning t emp. PS x

[spacer]

300

072 153

075 167

Fig. 3-277, (p. 3-357)

[spacer]

95

075 182

073 153

074 153

075 153

Fig. 3-277, (p. 3-357)

Setting for the temperature (in C) to trigger a warning alarm.


Note: This setting is only enabled in the Absolute replica mode of operation.

[spacer]

THER M : M ax. cool. t emp. PSx


40

[spacer]

70

072 185

073 185

074 185

075 185

Fig. 3-277, (p. 3-357)

Setting for the maximum permissible coolant temperature.


Note: This setting is active only if the coolant temperature is measured via the
PT 100 or the 20 mA input.

7-202

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

THER M : S ele ct me as.input PS x

Logic Diagram
072 177

0: Default temp. value

073 177

074 177

075 177

Fig. 3-275, (p. 3-353)

[spacer]

This setting defines whether coolant temperature (ambient) shall be measured


and, if so, whether data acquisition shall take place via the PT 100 or the 20 mA
input.

[spacer]

THER M : Coolant t emp. PS x


40

-40

072 186

70

073 186

074 186

075 186

Fig. 3-277, (p. 3-357)

[spacer]

Setting for the coolant temperature to be used for calculation of the trip time if
coolant temperature is not measured.

[spacer]

THER M : M inimu m te mper at.PS x


-40

-40

100

076 178

077 178

078 178

079 178

[spacer]

Setting for the minimum coolant temperature to be used for trip time calculation
if a cable runs in an underground tunnel system.

[spacer]

THER M : Funct.f.CT A fai l. PSx

076 177

3: Blocking

077 177

078 177

079 177

Fig. 3-275, (p. 3-353)

[spacer]

The setting defines how the thermal overload protection function will continue to
operate in the event of faulty coolant temperature acquisition. User can select
between Default temp. value, Last meas.temperat. and Blocking.

[spacer]

THER M : warn ing PSx


95

50

072 184

200

[spacer]

Setting for the operate value of the warning stage.

[spacer]

THER M : t rip PS x
100

[spacer]

200

074 184

075 184

Fig. 3-277, (p. 3-357)

072 181

50

073 184

073 181

074 181

075 181

Fig. 3-277, (p. 3-357)

Setting for the operate value of the trip stage.


Note: If the operating mode has been set to Absolute replica, the setting here
will be automatically set to 100% and this parameter will be hidden as far as the
local control panel is concerned.

[spacer]

THER M : Hyste re s. ,tr ip P Sx


2

30

[spacer]

Setting for the hysteresis of the trip stage.

[spacer]

THER M : Warning pre-t rip PS x


30.0

[spacer]

0.0

1000.0

072 183

074 183

075 183

Fig. 3-277, (p. 3-357)

072 191

min

073 183

073 191

074 191

075 191

Fig. 3-277, (p. 3-357)

A warning will be given in advance of the trip. The time difference between the
warning time and the trip time is set here.

P437/EN M/R-11-A // P437311650

7-203

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

THER M : R e tain re pl ic a PS x

Max

Unit

Logic Diagram
009 019

009 030

009 032

009 039

0: No
[spacer]

7-204

With this parameter it can be configured whether the thermal replica is retained
in the non-volatile section of the device's memory so that it will still be available
after an interruption of the supply voltage.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter

Address

Default

Min

Max

Unit

Time-voltage protec V<>: Enable PS x


tion

Logic Diagram
076 000

077 000

078 000

079 000

0: No
[spacer]

This setting defines the setting group in which V<> protection is enabled.

[spacer]

V<>: Ope rating mode PSx

076 001

1: Delta
[spacer]

077 001

078 001

079 001

Fig. 3-281, (p. 3-361)

This setting specifies whether the phase-to-ground voltages ('Star' operating


mode) or the phase-to-phase voltages ('Delta' operating mode) will be
monitored.
Note: In the settings for the operate values of the time-voltage protection
function, the reference quantity is Vnom in the Delta operating mode, but Vnom/
3 in the Star operating mode.
To work out the settings for the over/undervoltage stages, consider the following
example for Vnom = 100 V:
Setting in the Delta operating mode for an operate value of 80 V (phase-tophase):
Setting value =

operate value
80V
=
= 0.80
V nom
100V

Setting in the Star operating mode for an operate value of 46.2 V (phase-tophase):
Setting value =

[spacer]

operate value
46.2V
46.2V 3
=
=
= 0.80
V nom
100V
100V
3
3

V<>: V> PSx


1.10

076 003

0.20

[spacer]

Setting for operate value V>.

[spacer]

V<>: V> > PSx


1.10

0.20

Setting for operate value V>>.

[spacer]

V<>: V> >> PS x


0.20

Setting for operate value V>>>.

[spacer]

V<>: tV> PS x

1.50

100.00

Setting for the operate delay of overvoltage stage V>.

[spacer]

V<>: tV>> PS x

[spacer]

076 006

0.00

100.00

078 004

079 004

011 076

011 077

011 078

077 005

078 005

079 005

Fig. 3-282, (p. 3-362)

[spacer]

1.00

077 004

Vnom(/3) Fig. 3-283, (p. 3-363)

076 005

0.00

079 003

Vnom(/3) Fig. 3-282, (p. 3-362)

011 075

[spacer]

1.00

1.50

078 003

Vnom(/3) Fig. 3-282, (p. 3-362)

076 004

[spacer]

1.10

1.50

077 003

077 006

078 006

079 006

Fig. 3-282, (p. 3-362)

Setting for the operate delay of overvoltage stage V>>.

P437/EN M/R-11-A // P437311650

7-205

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

V<>: tV>>> PS x
1.00

Logic Diagram
011 079

0.00

100.00

Setting for the operate delay of overvoltage stage V>>>.

[spacer]

V<>: tV> 3-pole PS x

076 027

0.00

100.00

011 081

011 082

Fig. 3-283, (p. 3-363)

[spacer]

1.00

011 080

077 027

078 027

079 027

Fig. 3-282, (p. 3-362)

[spacer]

Setting for the operate delay of overvoltage stage V> when all three trigger
stages are activated.

[spacer]

V<>: tV>> 3- pole P S x


1.00

0.00

011 092

100.00

011 094

011 095

011 096

Fig. 3-282, (p. 3-362)

[spacer]

Setting for the operate delay of overvoltage stage V>> when all three trigger
stages are activated.

[spacer]

V<>: tV>>> 3- pole P Sx


1.00

0.00

011 099

100.00

011 105

011 117

011 118

Fig. 3-283, (p. 3-363)

[spacer]

Setting for the operate delay of overvoltage stage V>>> when all three trigger
stages are activated.

[spacer]

V<>: V< PSx


0.80

076 007

0.20

[spacer]

Setting for operate value V<.

[spacer]

V<>: V< < PSx


0.80

0.20

Setting for operate value V<<.

[spacer]

V<>: V< << PS x


0.20

Setting for operate value V<<<.

[spacer]

V<>: tV< PS x

1.50

100.00

Setting for the operate delay of undervoltage stage V<.

[spacer]

V<>: tV<< PS x

076 010

0.00

100.00

Setting for the operate delay of undervoltage stage V<<.

[spacer]

V<>: tV<<< PS x

[spacer]

7-206

011 088

0.00

100.00

079 008

011 084

011 085

011 086

077 009

078 009

079 009

077 010

078 010

079 010

Fig. 3-284, (p. 3-364)

[spacer]

1.00

078 008

Fig. 3-284, (p. 3-364)

[spacer]

1.00

077 008

Vnom(/3) Fig. 3-285, (p. 3-365)

076 009

0.00

079 007

Vnom(/3) Fig. 3-284, (p. 3-364)

011 083

[spacer]

1.00

1.50

078 007

Vnom(/3) Fig. 3-284, (p. 3-364)

076 008

[spacer]

0.80

1.50

077 007

011 089

011 090

011 091

Fig. 3-285, (p. 3-365)

Setting for the operate delay of undervoltage stage V<<<.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

V<>: tV< 3-pole PS x


1.00

Logic Diagram
076 028

0.00

100.00

077 028

078 028

079 028

Fig. 3-284, (p. 3-364)

[spacer]

Setting for the operate delay of undervoltage stage V< when all three trigger
stages are activated.

[spacer]

V<>: tV<< 3- pole P S x


1.00

0.00

011 119

100.00

011 124

011 125

011 126

Fig. 3-284, (p. 3-364)

[spacer]

Setting for the operate delay of undervoltage stage V<< when all three trigger
stages are activated.

[spacer]

V<>: tV<<< 3- pole P Sx


1.00

0.00

011 127

100.00

011 128

011 129

011 130

Fig. 3-285, (p. 3-365)

[spacer]

Setting for the operate delay of undervoltage stage V<<< when all three trigger
stages are activated.

[spacer]

V<>: Vpo s> PS x


1.10

076 015

0.20

[spacer]

Setting for operate value Vpos>.

[spacer]

V<>: Vpo s>> PSx


1.10

Vnom/3

0.20

Setting for operate value Vpos>>.

[spacer]

V<>: tVp os> PSx

1.50

Vnom/3

100.00

Setting for the operate delay of overvoltage stage Vpos>.

[spacer]

V<>: tVp os>> PSx

076 018

0.00

100.00

Setting for the operate delay of overvoltage stage Vpos>>.

[spacer]

V<>: Vpo s< PS x

076 019

0.20

[spacer]

Setting for operate value Vpos<.

[spacer]

V<>: Vpo s<< PSx


0.80

0.20

Setting for operate value Vpos<<.

[spacer]

V<>: tVp os< PSx

[spacer]

Vnom/3

1.50

Vnom/3

100.00

077 017

078 017

079 017

077 018

078 018

079 018

077 019

078 019

079 019

077 020

078 020

079 020

Fig. 3-287, (p. 3-368)

076 021

0.00

079 016

Fig. 3-287, (p. 3-368)

076 020

[spacer]

1.00

1.50

078 016

Fig. 3-287, (p. 3-368)

[spacer]

0.80

077 016

Fig. 3-287, (p. 3-368)

[spacer]

1.00

079 015

Fig. 3-287, (p. 3-368)

076 017

0.00

078 015

Fig. 3-287, (p. 3-368)

076 016

[spacer]

1.00

1.50

077 015

077 021

078 021

079 021

Fig. 3-287, (p. 3-368)

Setting for the operate delay of undervoltage stage Vpos<.

P437/EN M/R-11-A // P437311650

7-207

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

V<>: tVp os<< PSx


1.00

076 022

0.00

100.00

Setting for the operate delay of undervoltage stage Vpos<<.

[spacer]

V<>: Vneg> PS x

076 023

0.20

[spacer]

Setting for operate value Vneg>.

[spacer]

V<>: Vneg>> PS x
Blocked

Vnom/3

0.20

Setting for operate value Vneg>>.

[spacer]

V<>: tVneg> PSx

1.50

Vnom/3

100.00

Setting for the operate delay of overvoltage stage Vneg>.

[spacer]

V<>: tVneg>> PSx

076 026

0.00

100.00

078 023

077 024

078 024

Setting for the operate delay of overvoltage stage Vneg>>.

[spacer]

V<>: Evaluation VNG PS x

076 002

1: Calculated

077 025

078 025

077 026

078 026

077 002

078 002

This setting determines which neutral-point displacement voltage will be


monitored: The displacement voltage calculated by the P437 or the
displacement voltage measured at the T 90 voltage transformer.

[spacer]

V<>: VNG> PS x

076 011

0.02

[spacer]

Setting for operate value VNG>.

[spacer]

V<>: VNG>> PSx

1.00

0.02

Setting for operate value VNG>>.

[spacer]

V<>: tVNG> PS x

1.00

076 013

0.00

100.00

[spacer]

V<>: tVNG>> PS x

076 014

0.00

100.00

Setting for the operate delay of overvoltage stage VNG>>.

[spacer]

V<>: Vref> PS x

[spacer]

7-208

007 064

1.50

078 011

079 011

077 012

078 012

079 012

077 013

078 013

079 013

077 014

078 014

079 014

Fig. 3-290, (p. 3-370)

[spacer]

0.20

077 011

Fig. 3-290, (p. 3-370)

Setting for the operate delay of overvoltage stage VNG>.

1.10

079 002

Vnom(/3) Fig. 3-290, (p. 3-370)

[spacer]

1.00

079 026

Vnom(/3) Fig. 3-290, (p. 3-370)

076 012

[spacer]

1.00

079 025

Fig. 3-289, (p. 3-370)

[spacer]

Blocked

079 024

Fig. 3-288, (p. 3-369)

[spacer]

Blocked

079 023

Fig. 3-288, (p. 3-369)

[spacer]

1.00

077 023

Fig. 3-288, (p. 3-369)

076 025

0.00

079 022

Fig. 3-288, (p. 3-369)

076 024

[spacer]

1.00

1.50

078 022

Fig. 3-287, (p. 3-368)

[spacer]

Blocked

077 022

Vref,nom

007 071

007 075

007 079

Fig. 3-291, (p. 3-371)

Setting for operate value Vref>.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

V<>: Vref>> PSx


1.10

007 065

0.20

[spacer]

Setting for operate value Vref>>.

[spacer]

V<>: Vref>>> PS x
1.10

1.50

Vref,nom

0.20

Setting for operate value Vref>>>.

[spacer]

V<>: tVref> PSx

1.50

Vref,nom

100.00

Setting for the operate delay of overvoltage stage Vref>.

[spacer]

V<>: tVref>> PSx

007 067

0.00

100.00

Setting for the operate delay of overvoltage stage Vref>>.

[spacer]

V<>: tVref>>> PSx

010 254

0.00

100.00

Setting for the operate delay of overvoltage stage Vref>>>.

[spacer]

V<>: Vref< PS x

007 086

0.20

[spacer]

Setting for operate value Vref<.

[spacer]

V<>: Vref<< PSx


0.80

0.20

Setting for operate value Vref<<.

[spacer]

V<>: Vref<<< PS x

1.50

Vref,nom

0.20

Setting for operate value Vref<<<.

[spacer]

V<>: tVref< PSx

1.50

Vref,nom

100.00

[spacer]

V<>: tVref<< PSx

007 096

100.00

Setting for the operate delay of undervoltage stage Vref<<.

[spacer]

V<>: tVref<<< PSx

[spacer]

011 071

0.00

100.00

007 070

007 074

007 078

010 255

011 020

011 035

007 097

007 101

007 105

007 098

007 102

007 106

011 062

011 069

011 070

007 099

007 103

007 107

007 100

007 104

007 108

Fig. 3-292, (p. 3-372)

[spacer]

1.00

007 077

Fig. 3-292, (p. 3-372)

Setting for the operate delay of undervoltage stage Vref<.

0.00

007 073

Fig. 3-292, (p. 3-372)

[spacer]

1.00

007 069

Fig. 3-292, (p. 3-372)

007 088

0.00

010 253

Fig. 3-292, (p. 3-372)

011 059

[spacer]

1.00

Vref,nom

007 087

[spacer]

0.80

1.50

010 252

Fig. 3-291, (p. 3-371)

[spacer]

0.80

010 251

Fig. 3-291, (p. 3-371)

[spacer]

1.00

007 076

Fig. 3-291, (p. 3-371)

[spacer]

1.00

007 072

Fig. 3-291, (p. 3-371)

007 066

0.00

007 068

Fig. 3-291, (p. 3-371)

010 250

[spacer]

1.00

Logic Diagram

011 072

011 073

011 074

Fig. 3-292, (p. 3-372)

Setting for the operate delay of overvoltage stage Vref<<<.

P437/EN M/R-11-A // P437311650

7-209

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

V<>: Op. mode V< mon. P Sx

Logic Diagram
001 162

0: Without

001 163

001 164

001 165

Fig. 3-280, (p. 3-360)

[spacer]

Activation of the minimum current monitoring mode for undervoltage stage V<.

[spacer]

V<>: I enable V< PSx


0.10

0.04

001 155

1.00

Inom

001 159

001 160

001 161

Fig. 3-280, (p. 3-360)

[spacer]

This setting defines the threshold value of the minimum current monitoring for
undervoltage stage V<.

[spacer]

V<>: tT rans ient pulse P Sx


1.00

0.00

076 029

100.00

077 029

078 029

079 029

Fig. 3-285, (p. 3-365)

[spacer]

Setting for the time limit of the signals generated by the undervoltage stages.

[spacer]

V<>: Hyst . V<> meas. PSx


3

076 048

10

077 048

078 048

079 048

Fig. 3-282, (p. 3-362)


Fig. 3-283, (p. 3-363)

[spacer]

Setting for the hysteresis of the trigger stages for monitoring measured
voltages.

[spacer]

V<>: Hyst . V<> de duc . P Sx


3

[spacer]

7-210

10

076 049

077 049

078 049

079 049

Fig. 3-287, (p. 3-368)

Setting for the hysteresis of the trigger stages for monitoring deduced voltages
such as Vneg and VNG.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default

Address
Min

Max

Unit

f<> : Enable PSx


Over-/
underfrequency pro
tection

Logic Diagram
018 196

0: No

018 197

018 198

Fig. 3-293, (p. 3-373)

[spacer]

This setting defines the parameter subset in which over-/underfrequency


protection is enabled.

[spacer]

f<> : Oper. m ode f1 PS x

018 120

1: f
[spacer]

018 199

018 121

018 122

018 123

Fig. 3-297, (p. 3-378)

f<> : Oper. m ode f2 PS x

018 144

018 145

018 146

018 147

018 168

018 169

018 170

018 171

018 192

018 193

018 194

018 195

1: f
[spacer]

f<> : Oper. m ode f3 PS x


1: f

[spacer]

f<> : Oper. m ode f4 PS x


1: f

[spacer]

Setting for the operating mode of the timer stages of over-/underfrequency


protection.

[spacer]

f<> : f1 PS x
49.80

[spacer]

70.00

Hz

40.00

70.00

40.00

70.00

40.00

70.00

018 102

018 103

Fig. 3-297, (p. 3-378)


018 124

018 125

018 126

018 127

018 148

018 149

018 150

018 151

018 172

018 173

018 174

018 175

Hz

f<> : f4 PS x
49.80

018 101

Hz

f<> : f3 PS x
49.80

[spacer]

40.00

f<> : f2 PS x
49.80

[spacer]

018 100

Hz

[spacer]

Setting for the frequency threshold. The over-/underfrequency protection


function will operate if one of the following two conditions applies: The
threshold is higher than the set nominal frequency and the frequency exceeds
this threshold. The threshold is lower than the set nominal frequency and the
frequency falls below this threshold. Depending on the chosen operating mode,
either a signal is issued without further monitoring, or further monitoring
mechanisms are started.

[spacer]

f<> : tf1 PSx


0.00

[spacer]

0.00

10.00

f<> : tf2 PSx


0.00

[spacer]

018 104

0.00

10.00

P437/EN M/R-11-A // P437311650

0.00

10.00

018 106

018 107

Fig. 3-297, (p. 3-378)


018 128

018 129

018 130

018 131

018 152

018 153

018 154

018 155

f<> : tf3 PSx


0.00

018 105

7-211

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

f<> : tf4 PSx


0.00

018 176

0.00

10.00

018 177

Setting for the operate delay of over-/underfrequency protection.

[spacer]

f<> : df1/dt PS x

[spacer]

0.1

10.0

0.1

10.0

0.1

10.0

018 109

018 110

018 111

Fig. 3-297, (p. 3-378)


018 132

018 133

018 134

018 135

018 156

018 157

018 158

018 159

018 180

018 181

018 182

018 183

Hz/s

Hz/s

f<> : df4/dt PS x
2.0

[spacer]

Hz/s

f<> : df3/dt PS x
2.0

[spacer]

10.0

f<> : df2/dt PS x
2.0

[spacer]

018 108

0.1

018 179

[spacer]

2.0

018 178

Hz/s

Setting for the frequency gradient to be monitored.


Note: This setting is ineffective unless operating mode f with df/dt has been
selected.

[spacer]

f<> : De lta f1 PS x
0.30

[spacer]

Hz

0.01

5.00

0.01

5.00

0.01

5.00

018 113

018 114

018 115

Fig. 3-297, (p. 3-378)


018 136

018 137

018 138

018 139

018 160

018 161

018 162

018 163

018 184

018 185

018 186

018 187

Hz

Hz

f<> : De lta f4 PS x
0.30

[spacer]

5.00

f<> : De lta f3 PS x
0.30

[spacer]

0.01

f<> : De lta f2 PS x
0.30

[spacer]

018 112

Hz

Setting for Delta f.


Note: This setting is ineffective unless operating mode f w. Delta f/Delta t has
been selected.

[spacer]

f<> : De lta t1 PS x
0.30

[spacer]

0.04

3.00

0.04

3.00

0.04

3.00

018 117

018 118

018 119

Fig. 3-297, (p. 3-378)


018 140

018 141

018 142

018 143

018 164

018 165

018 166

018 167

018 188

018 189

018 190

018 191

f<> : De lta t4 PS x
0.30

[spacer]

3.00

f<> : De lta t3 PS x
0.30

[spacer]

0.04

f<> : De lta t2 PS x
0.30

[spacer]

018 116

Setting for Delta t.


Note: This setting is ineffective unless operating mode f w. Delta f/Delta t has
been selected.

7-212

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default

Power directional
protection

Address
Min

Max

Unit

Logic Diagram

P<>: Enabled PSx

014 252

0: No

014 253

014 254

014 255

Fig. 3-298, (p. 3-380)

[spacer]

This setting defines the parameter subset in which power directional protection
is enabled.

[spacer]

P<>: P> PS x
0.500

017 120

0.010

1.500

Snom

Setting for the operate value P> for the active power.

[spacer]

P<>: Op erate de lay P > PSx


0.00

100.00

[spacer]

Setting for the operate delay of stage P>.

[spacer]

P<>: R eleas e de lay P > PSx


0.00

0.00

017 128

[spacer]

Setting for the release delay of stage P>.

[spacer]

P<>: Direction P> PS x

017 129

017 130

017 131

017 133

017 134

017 135

Fig. 3-300, (p. 3-382)

017 136

1: Forward directional

017 202

Fig. 3-300, (p. 3-382)

017 132

100.00

017 201

Fig. 3-300, (p. 3-382)

[spacer]

0.10

017 200

017 137

017 138

017 139

Fig. 3-301, (p. 3-383)

[spacer]

This setting of the measuring direction determines whether a P>> trip signal will
be issued for forward, backward (reverse) or non-directional fault decisions.

[spacer]

P<>: Diseng. ratio P> PSx


0.95

0.05

017 124

0.95

017 125

017 126

Fig. 3-300, (p. 3-382)

[spacer]

Setting for the disengaging ratio of operate value P> of active power.

[spacer]

P<>: P>> PS x
0.500

017 140

0.010

1.500

Snom

Setting for the operate value P>> for the active power.

[spacer]

P<>: Op erate de lay P >>PS x


0.00

100.00

[spacer]

Setting for the operate delay of stage P>>.

[spacer]

P<>: R eleas e de lay P >>P Sx


0.00

0.00

100.00

[spacer]

Setting for the release delay of stage P>>.

[spacer]

P<>: Direction P>> PS x


1: Forward directional

[spacer]

017 148

017 142

017 143

017 149

017 150

017 151

Fig. 3-300, (p. 3-382)

017 152

017 141

Fig. 3-300, (p. 3-382)

[spacer]

Blocked

017 127

017 153

017 154

017 155

Fig. 3-300, (p. 3-382)

017 156

017 157

017 158

017 159

Fig. 3-301, (p. 3-383)

This setting of the measuring direction determines whether a P>> trip signal will
be issued for forward, backward (reverse) or non-directional fault decisions.

P437/EN M/R-11-A // P437311650

7-213

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

P<>: Diseng. ratio P>>P S x


0.95

0.05

Logic Diagram
017 144

0.95

017 145

017 146

Fig. 3-300, (p. 3-382)

[spacer]

Setting for the disengaging ratio of operate value P>> of active power.

[spacer]

P<>: Q> PS x
0.500

017 160

0.010

1.500

Snom

Setting for the operate value Q> of the reactive power.

[spacer]

P<>: Op erate de lay Q> P Sx


0.00

100.00

[spacer]

Setting for the operate delay of stage Q>.

[spacer]

P<>: R eleas e de lay Q> P Sx


0.00

0.00

10.00

[spacer]

Setting for the release delay of stage Q>.

[spacer]

P<>: Direction Q> PS x

017 168

017 163

017 169

017 170

017 171

017 173

017 174

017 175

Fig. 3-302, (p. 3-384)

017 176

1: Forward directional

017 162

Fig. 3-302, (p. 3-384)

017 172

017 161

Fig. 3-302, (p. 3-384)

[spacer]

Blocked

017 147

017 177

017 178

017 179

Fig. 3-303, (p. 3-385)

[spacer]

This setting of the measuring direction determines whether a Q> trip signal will
be issued for forward, backward (reverse) or non-directional fault decisions.

[spacer]

P<>: Diseng. ratio Q> P Sx


0.95

0.05

017 164

0.95

017 165

017 166

Fig. 3-302, (p. 3-384)

[spacer]

Setting for the disengaging ratio of operate value Q> of reactive power.

[spacer]

P<>: Q>> PS x
0.500

017 180

0.010

1.500

Snom

Setting for the operate value Q>> of the reactive power.

[spacer]

P<>: Op erate de lay Q>>P Sx


0.00

100.00

017 188

[spacer]

Setting for the operate delay of stage Q>>.

[spacer]

P<>: R eleas e de lay Q>>P Sx


0.00

0.00

100.00

[spacer]

Setting for the release delay of stage Q>>.

[spacer]

P<>: Direction Q>> PS x

017 183

017 189

017 190

017 191

017 193

017 194

017 195

Fig. 3-302, (p. 3-384)

017 196

1: Forward directional

017 182

Fig. 3-302, (p. 3-384)

017 192

017 181

Fig. 3-302, (p. 3-384)

[spacer]

Blocked

017 167

017 197

017 198

017 199

Fig. 3-303, (p. 3-385)

[spacer]

This setting of the measuring direction determines whether a Q>> trip signal
will be issued for forward, backward or non-directional fault decisions.

[spacer]

P<>: Diseng. ratio Q>>PS x


0.95

[spacer]

7-214

0.05

017 184

0.95

017 185

017 186

017 187

Fig. 3-302, (p. 3-384)

Setting for the disengaging ratio of operate value Q>> of reactive power.

P437/EN M/R-11-A // P437311650

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

P<>: P< PS x
0.500

017 030

0.010

1.500

Snom

[spacer]

Setting the operate value P< for the active power.

[spacer]

P<>: Op erate de lay P < PSx


0.10

0.00

100.00

[spacer]

Setting for the operate delay of stage P<.

[spacer]

P<>: R eleas e de lay P < PSx


0.00

0.00

017 061

017 062

017 063

017 227

017 228

017 229

Fig. 3-304, (p. 3-387)

[spacer]

Setting for the release delay (reset time) of stage P<.

[spacer]

P<>: Direction P< PS x

017 230

1: Forward directional

017 033

Fig. 3-304, (p. 3-387)

017 226

100.00

017 032

Fig. 3-304, (p. 3-387)

017 060

017 031

017 231

017 232

017 233

Fig. 3-305, (p. 3-389)

[spacer]

This setting of the measuring direction determines whether a P< trip signal will
be issued for forward, backward (reverse) or non-directional fault decisions.

[spacer]

P<>: Diseng. ratio P< PSx


1.05

1.05

017 034

20.00

017 035

017 036

Fig. 3-304, (p. 3-387)

[spacer]

Setting for the disengaging ratio of operate value P< of active power.

[spacer]

P<>: P<< PS x
0.500

017 234

0.010

1.500

Snom

[spacer]

Setting for operate value P<< of active power.

[spacer]

P<>: Op erate de lay P <<PS x


Blocked

0.00

100.00

[spacer]

Setting for the operate delay of stage P<<.

[spacer]

P<>: R eleas e de lay P <<P Sx


0.00

0.00

100.00

017 037

017 243

017 244

017 245

017 247

017 248

017 249

Fig. 3-304, (p. 3-387)

[spacer]

Setting for the release delay (reset time) of stage P<<.

[spacer]

P<>: Direction P<< PS x

017 250

1: Forward directional

017 237

Fig. 3-304, (p. 3-387)

017 246

017 236

Fig. 3-304, (p. 3-387)

017 242

017 235

017 251

017 252

017 253

Fig. 3-305, (p. 3-389)

[spacer]

This setting of the measuring direction determines whether a P<< trip signal will
be issued for forward, backward (reverse) or non-directional fault decisions.

[spacer]

P<>: Diseng.ratio P<< PS x


1.05

1.05

017 238

20.00

017 239

017 240

Fig. 3-304, (p. 3-387)

[spacer]

Setting for the disengaging ratio of operate value P<< of active power.

[spacer]

P<>: Q< PS x
0.500

[spacer]

018 035

0.010

0.500

017 241

Snom

018 036

018 037

018 038

Fig. 3-307, (p. 3-391)

Setting for operate value Q< of reactive power.

P437/EN M/R-11-A // P437311650

7-215

P437

7 Settings

Parameter
Default
[spacer]

Address
Min

Max

Unit

P<>: Op erate de lay Q< P Sx


Blocked

0.00

100.00

[spacer]

Setting for the operate delay of stage Q<.

[spacer]

P<>: R eleas e de lay Q< P Sx


0.00

0.00

100.00

Logic Diagram
018 052

018 055

018 057

018 058

018 059

Fig. 3-307, (p. 3-391)

[spacer]

Setting for the release delay (reset time) of stage Q<.

[spacer]

P<>: Direction Q< PS x

018 081

1: Forward directional

018 054

Fig. 3-307, (p. 3-391)

018 056

018 053

018 082

018 083

018 084

Fig. 3-308, (p. 3-393)

[spacer]

This setting of the measuring direction determines whether a Q< trip signal will
be issued for forward, backward (reverse) or non-directional fault decisions.

[spacer]

P<>: Diseng. ratio Q< P Sx


1.05

1.05

018 044

20.00

018 045

018 046

Fig. 3-307, (p. 3-391)

[spacer]

Setting for the disengaging ratio of operate value Q< of reactive power.

[spacer]

P<>: Q<< PS x
0.500

018 085

0.010

0.500

Snom

[spacer]

Setting for operate value Q<< of reactive power.

[spacer]

P<>: Op erate de lay Q<<P Sx


Blocked

0.00

100.00

Setting for the operate delay of stage Q<<.

[spacer]

P<>: R eleas e de lay Q<<P Sx


0.00

100.00

018 088

018 214

018 215

018 216

018 237

018 238

018 239

Fig. 3-307, (p. 3-391)

[spacer]

Setting for the release delay (reset time) of stage Q<<.

[spacer]

P<>: Direction Q<< PS x

018 242

1: Forward directional

018 087

Fig. 3-307, (p. 3-391)

018 236

018 086

Fig. 3-307, (p. 3-391)

018 213

[spacer]

0.00

018 047

018 243

018 244

018 245

Fig. 3-308, (p. 3-393)

[spacer]

This setting of the measuring direction determines whether a Q<< trip signal
will be issued for forward, backward (reverse) or non-directional fault decisions.

[spacer]

P<>: Diseng.ratio Q<< P Sx


1.05

1.05

018 095

20.00

018 096

018 097

Fig. 3-307, (p. 3-391)

[spacer]

Setting for the disengaging ratio of operate value Q<< of reactive power.

[spacer]

P<>: t Transient pulse P Sx


1.00

0.00

018 246

100.00

018 098

018 247

018 248

018 249

Fig. 3-304, (p. 3-387)


Fig. 3-307, (p. 3-391)

[spacer]

7.1.3.4

7-216

Setting for the time limit of the signals generated by stages P<, P<<, Q< and
Q<< after the respective operate delays have elapsed.
Cont rol

P437/EN M/R-11-A // P437311650

P437
8

Information and Control Functions

8.1

Operation
The P437 generates a large number of signals, processes binary input signals,
and acquires measured data during fault-free operation of the protected object
as well as fault-related data. A number of counters are available for statistical
purposes. This information can be read out from the integrated local control
panel or via the operating program.
All this information can be found in the Operation and Events folders in the
menu tree.

Note
Detailed information about all parameters, including complete selection tables and
IEC 608705103 protocol properties, are separately available as a set of interlinked
PDF files for user-friendly navigation, packed in one ZIP archive named
DataModelExplorer_P437_en_P01.zip.

A list of the Logical Nodes that have been implemented for the IEC 61850 protocol
can be found in a separate document.

8.1.1

Cyclic Values

8.1.1.1

M e as ur ed Ope rating Dat a


Parameter
Default

Device

Min

Max

Unit

Logic Diagram

DVICE: Process or fre quency


Not measured

[spacer]

Address

25

100

104 099

MHz

Display of the clock frequency of the processor on processor module P.

P437/EN M/R-11-A // P437311650

8-1

P437

8 Information and Control Functions

Parameter
Default

InterMiCOM
interface

Min

Max

Unit

COMM 3: No. t el. err ors p.u.


0.0

[spacer]

Address

0.0

100.0

120 040

COMM 4: No. t el. err ors p.u.


0.0

0.0

100.0

Logic Diagram

122 040

[spacer]

Display of the updated measured operating value for the number of corrupted
messages within the last 1000 received messages.

[spacer]

COMM 3: No.t.err.,max,st ore d


0.0

[spacer]

0.0

100.0

120 041

COMM 4: No.t.err.,max,st ore d


0.0

0.0

100.0

122 041

[spacer]

Display of the updated measured operating value for the proportion of corrupted
messages within the last 1000 received messages.

[spacer]

COMM 3: Loop back res ult

120 057

....: Not measured


[spacer]

COMM 3: Loop back rec eiv e


Not measured

[spacer]

120 056

255

COMM 4: Loop back res ult

122 057

....: Not measured


[spacer]

COMM 4: Loop back rec eiv e


Not measured

[spacer]

8-2

122 056

255

While the hold time is running, the loop back test results can be checked by
reading out these values.

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Address
Min

Max

Unit

Logic Diagram

Measured data input MEASI: Curr e nt IDC


Not measured

004 134

0.00

[spacer]

Display of the input current.

[spacer]

MEASI: Curr e nt IDC p.u.


Not measured

0.00

24.00

mA

004 135

1.20

IDC,nom

[spacer]

Display of the input current referred to IDC,nom.

[spacer]

MEASI: Curr . IDC ,lin p.u.


Not measured

0.00

Fig. 3-28, (p. 3-46)

Fig. 3-28, (p. 3-46)

004 136

1.20

IDC,nom

Fig. 3-28, (p. 3-46)

[spacer]

Display of the linearized input current referred to IDC,nom.

[spacer]

MEASI: S caled value IDC, lin


Not measured

-32000

32000

[spacer]

Display of the scaled linearized value.

[spacer]

MEASI: T emp eratur e


Not measured

004 180

Fig. 3-29, (p. 3-47)

004 133

-40.0

215.0

Fig. 3-30, (p. 3-48)

[spacer]

Display of the temperature measured at the PT 100 temperature input on the


analog p/c board.

[spacer]

MEASI: T emp eratur e p.u.


Not measured

-0.40

004 221

2.15

100C

Fig. 3-30, (p. 3-48)

[spacer]

Display of the temperature measured at the PT 100 temperature input on the


analog p/c board referred to 100C.

[spacer]

MEASI: T emp eratur e Tmax


Not measured

[spacer]

-40.0

004 233

215.0

Fig. 3-30, (p. 3-48)

Display of the maximum temperature measured at the PT 100 temperature


input on the analog p/c board.
Parameter
Default

Measured data
output

Max

Unit

Logic Diagram
005 100

0.00

20.00

mA

MEASO: Curr ent A- 2


0.00

[spacer]

Min

MEASO: Curr ent A- 1


0.00

[spacer]

Address

Fig. 3-39, (p. 3-63)


005 099

0.00

20.00

mA

Display of the current on the analog measured data output (A1: channel 1; A2:
channel 2).

P437/EN M/R-11-A // P437311650

8-3

P437

8 Information and Control Functions

Parameter
Default

Main function

Address
Min

Max

Unit

Logic Diagram

MAIN: Date
01.01.97

003 090

01.01.97 07.11.98 dd.mm.yy Fig. 3-74, (p. 3-104)

[spacer]

Date display. The date can also be set here. The centuries are not displayed.
The supported dates range from January 1st, 1997, until November 7th, 2098.

[spacer]

MAIN: Tim e of day


00:00:00

003 091

00:00:00 24:00:00 hh:mm:ss

Fig. 3-74, (p. 3-104)

[spacer]

Display of the time of day. The time can also be set here.

[spacer]

MAIN: Tim e s witch ing

003 095

0: Standard time
[spacer]

Fig. 3-74, (p. 3-104)

Setting for standard time or daylight saving time.


This setting is necessary in order to avoid misinterpretation of the times
assigned to signals and event data that can be read out through the PC or
communication interfaces.

[spacer]

MAIN: Fre que ncy f


Not measured

004 040

40.00

[spacer]

Display of system frequency.

[spacer]

MAIN: IA prim,demand
Not measured

[spacer]

Hz

Fig. 3-55, (p. 3-83)

006 226

25000

Fig. 3-44, (p. 3-74)

MAIN: IB prim,demand
Not measured

[spacer]

70.00

006 227

25000

Fig. 3-44, (p. 3-74)

MAIN: IC prim ,demand


Not measured

006 228

25000

Fig. 3-44, (p. 3-74)

[spacer]

Display the three delayed phase currents (demand values) as primary


quantities.

[spacer]

MAIN: IA prim,demand st or.


Not measured

[spacer]

25000

Fig. 3-44, (p. 3-74)

MAIN: IB prim,demand st or.


Not measured

[spacer]

006 223

25000

006 224

Fig. 3-44, (p. 3-74)

MAIN: IC prim ,demand stor .


Not measured

25000

006 225

Fig. 3-44, (p. 3-74)

[spacer]

Display the three stored phase currents (demand values) as primary quantities.

[spacer]

MAIN: Curr. IP,m ax prim.


Not measured

[spacer]

8-4

005 050

25000

Fig. 3-43, (p. 3-73)

Display of the maximum phase current as a primary quantity.

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

MAIN: IP,max p rim.,delay


Not measured

005 036

25000

Fig. 3-44, (p. 3-74)

[spacer]

Display of the delayed maximum phase current as a primary quantity.

[spacer]

MAIN: IP,max p rim.,s tor ed


Not measured

005 034

25000

Fig. 3-44, (p. 3-74)

[spacer]

Display of the delayed stored maximum phase current as a primary quantity.

[spacer]

MAIN: Curr. IP,min prim.


Not measured

005 055

25000

Fig. 3-43, (p. 3-73)

[spacer]

Display of the minimum phase current as a primary quantity.

[spacer]

MAIN: Current A pr im.


Not measured

005 040

25000

[spacer]

Display of phase current A as a primary quantity.

[spacer]

MAIN: Current B prim.


Not measured

006 040

25000

[spacer]

Display of phase current B as a primary quantity.

[spacer]

MAIN: Current C pr im.


Not measured

25000

Display of phase current C as a primary quantity.

[spacer]

MAIN: Current ( IP) pri m.


0

Fig. 3-43, (p. 3-73)

007 040

[spacer]

Not measured

Fig. 3-43, (p. 3-73)

Fig. 3-43, (p. 3-73)

005 010

25000

Fig. 3-43, (p. 3-73)

[spacer]

Display of the calculated resultant current as a primary quantity.

[spacer]

MAIN: Current IN pr im.


Not measured

004 043

25000

Fig. 3-45, (p. 3-75)

[spacer]

Display of the updated value for the residual current as a primary quantity. The
measured residual current is displayed.

[spacer]

MAIN: Current IN,par pr im.


Not measured

008 000

25000

Fig. 3-46, (p. 3-75)

[spacer]

Display of the measured residual current of the parallel line as a primary


quantity.

[spacer]

MAIN: Volt. VPG,max prim.


Not measured

0.0

008 042

2500.0

kV

Fig. 3-49, (p. 3-78)

[spacer]

Display of the maximum phase-to-ground voltage as a primary quantity.

[spacer]

MAIN: Volt. VPG,min prim.


Not measured

[spacer]

0.0

009 042

2500.0

kV

Fig. 3-49, (p. 3-78)

Display of the minimum phase-to-ground voltage as a primary quantity.

P437/EN M/R-11-A // P437311650

8-5

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

MAIN: Voltage A-G prim.


Not measured

0.0

005 042

2500.0

kV

Fig. 3-49, (p. 3-78)

[spacer]

Display of the updated value for phase-to-ground voltage A-G as a primary


quantity.

[spacer]

MAIN: Voltage B-G prim.


Not measured

0.0

006 042

2500.0

kV

Fig. 3-49, (p. 3-78)

[spacer]

Display of the updated value for phase-to-ground voltage B-G as a primary


quantity.

[spacer]

MAIN: Voltage C- G pr im.


Not measured

0.0

007 042

2500.0

kV

Fig. 3-49, (p. 3-78)

[spacer]

Display of the updated value for phase-to-ground voltage C-G as a primary


quantity.

[spacer]

MAIN: Volt. (VPG )/ 3 pr im.


Not measured

0.0

005 012

2500.0

kV

Fig. 3-49, (p. 3-78)

[spacer]

Display of the calculated neutral-displacement voltage as a primary quantity.

[spacer]

MAIN: Voltage VNG pr im.


Not measured

0.0

004 041

2500.0

kV

Fig. 3-50, (p. 3-79)

[spacer]

Display of the neutral-point displacement voltage measured at transformer T 90


as a primary quantity.

[spacer]

MAIN: Voltage Vref pri m.


Not measured

0.0

005 046

3000.0

kV

Fig. 3-51, (p. 3-79)

[spacer]

Display of the reference voltage measured at transformer T 15 as a primary


quantity.

[spacer]

MAIN: Volt. VPP,max prim.


Not measured

0.0

008 044

2500.0

kV

Fig. 3-49, (p. 3-78)

[spacer]

Display of the maximum phase-to-phase voltage as a primary quantity.

[spacer]

MAIN: Volt. VPP,min prim.


Not measured

0.0

009 044

2500.0

kV

Fig. 3-49, (p. 3-78)

[spacer]

Display of the minimum phase-to-phase voltage as a primary quantity.

[spacer]

MAIN: Voltage A-B pri m.


Not measured

0.0

005 044

2500.0

kV

Fig. 3-49, (p. 3-78)

[spacer]

Display of the updated value for phase-to-phase voltage A-B as a primary


quantity.

[spacer]

MAIN: Voltage B-C prim.


Not measured

[spacer]

8-6

0.0

006 044

2500.0

kV

Fig. 3-49, (p. 3-78)

Display of the updated value for phase-to-phase voltage B-C as a primary


quantity.
P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

MAIN: Voltage C- A prim.


Not measured

0.0

007 044

2500.0

kV

Fig. 3-49, (p. 3-78)

[spacer]

Display of the updated value for phase-to-phase voltage C-A as a primary


quantity.

[spacer]

MAIN: Appar . po we r S pri m.


Not measured

-1399.9

1400.0

005 025

MVA

Fig. 3-52, (p. 3-81)

[spacer]

Display of the updated apparent power value as a primary quantity.

[spacer]

MAIN: Active powe r P pr im.


Not measured

-3200.0

3200.0

004 050

MW

Fig. 3-52, (p. 3-81)

[spacer]

Display of the updated active power value as a primary quantity.

[spacer]

MAIN: Re ac. powe r Q prim.


Not measured

-3200.0

004 052

3200.0

Mvar

Fig. 3-52, (p. 3-81)

[spacer]

Display of the updated reactive power value as a primary quantity.

[spacer]

MAIN: Active powe r fac tor


Not measured

-1.000

004 054

1.000

[spacer]

Display of the updated active power factor.

[spacer]

MAIN: Act.energy outp. prim


2:

[spacer]

008 065

MWh

MAIN: Act.energy inp. pr im


2:

[spacer]

Fig. 3-52, (p. 3-81)

008 066

MWh

MAIN: Re act.en. outp. pri m


2:

P437/EN M/R-11-A // P437311650

008 067

Mvarh

8-7

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Logic Diagram

MAIN: Re act. en. inp. pr im

008 068

2:
[spacer]

Unit

Mvarh

Display of the updated active energy output (or active energy input, reactive
energy output, reactive energy input, respectively) as a primary quantity.
At run-time, the value is displayed with 32 bit precision. (But note that for
technical reasons, this value is internally stored as a text value.)
Value ranges:

MAIN: Act .e ne rgy outp.pr im 0 6,553,500.00 MWh

MAIN: Act.ene rgy inp. pri m 0 6,553,500.00 MWh

MAIN: Re act.e n. out p. pr im 0 6,553,500.00 Mvar h

MAIN: Re act. e n. inp. prim 0 6,553,500.00 Mvar h

Note: As an alternative, the same values also exist as numbers with 16 bit
precision:

[spacer]

(005 061) M AIN: Act .e ne rgy out p.prim

(005 062) M AI N: Act .e ne r gy inp. pri m

(005 063) M AIN: Re act .e n. out p. prim

(005 064) M AIN: Reac t. e n. inp. prim

MAIN: Act.energy outp. prim


0.00

[spacer]

MWh

Fig. 3-56, (p. 3-85)

0.00

005 062

655.35

MWh

Fig. 3-56, (p. 3-85)

MAIN: Re act.en. outp. pri m


0.00

8-8

655.35

MAIN: Act.energy inp. pr im


0.00

[spacer]

0.00

005 061

0.00

655.35

005 063

Mvar h

Fig. 3-56, (p. 3-85)

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Min

Max

Unit

Logic Diagram

MAIN: Re act. en. inp. pr im


0.00

[spacer]

Address

0.00

005 064

655.35

Mvar h

Fig. 3-56, (p. 3-85)

Display of the updated active energy output (or active energy input, reactive
energy output, reactive energy input, respectively) as a primary quantity.
The value is displayed as a number with 16 bit precision.
The setting at M AIN: Op. mode e nergy cnt . decides which procedure
shall be used to determine the active and reactive energy:

If procedure 1 is selected, active and reactive energy are determined


every 2 s (approximately).

If procedure 2 is selected, active and reactive energy are determined


every 100 ms (approximately).

Procedure 2 obviously gives more precise results but puts more strain on the
system.
Whenever the maximum value of 655.35 MWh or 655.35 MVAr h is exceeded,
the determination of the energy output is restarted, and the value that
exceeded the range is transferred to the new cycle. Moreover, a counter is
incremented:

(009 090) M AIN: No.ove rfl.act .e n.out: Counter for value overflow
of MAI N: Act .e nergy out p.pr im

(009 091) M AI N: No.ov e r fl.act .e n.inp: Counter for value overflow


of M AIN: Act .e ner gy inp. pr im

(009 092) M AIN: No. ov/ fl.r e ac. en.out: Counter for value overflow
of MAI N: R eact .en. out p. prim

(009 093) MAIN: No.ov/ fl. r e ac.e n.i np: Counter for value overflow
of M AIN: Re act . en. i np. pr im

Note that the maximum value of these counters is 10000.


As an alternative to these 16 bit numbers, there are also 32 bit precision values
available:

[spacer]

(008 065) M AIN: Act .e ne rgy o ut p.pri m

(008 066) M AIN: Act .ene rgy i np. prim

(008 067) M AIN: R eact .e n. outp. pri m

(008 068) M AIN: R eact . en. inp. pri m

MAIN: Load angle phi A


Not measured

-180.0

004 055

180.0

[spacer]

Display of the updated load angle value in phase A.

[spacer]

MAIN: Load angle phi B


Not measured

-180.0

004 056

180.0

[spacer]

Display of the updated load angle value in phase B.

[spacer]

MAIN: Load angle phi C


Not measured

[spacer]

-180.0

Fig. 3-52, (p. 3-81)

Fig. 3-52, (p. 3-81)

004 057

180.0

Fig. 3-52, (p. 3-81)

Display of the updated load angle value in phase C.

P437/EN M/R-11-A // P437311650

8-9

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

MAIN: Angle phi N


Not measured

004 072

-180.0

180.0

Fig. 3-52, (p. 3-81)

[spacer]

Display of the angle between the measured residual current system quantities IN
and VNG.

[spacer]

MAIN: Angle VPG vs. IN


Not measured

-180

005 009

180

Fig. 3-52, (p. 3-81)

[spacer]

Display of the angle between the calculated neutral-point displacement voltage


and the measured residual current system quantities IN.

[spacer]

MAIN: Phase re l. I N vs IP

004 073

....: Not measured

Fig. 3-53, (p. 3-82)

[spacer]

Display of the phase relation of measured and calculated residual current. (The
phase relation is displayed as either Equal phase or Reverse phase.)

[spacer]

MAIN: Fre que ncy f p.u.


Not measured

0.200

004 070

4.000

[spacer]

Display of system frequency referred to fn.

[spacer]

MAIN: IA p.u.,de mand


Not measured

[spacer]

Fig. 3-55, (p. 3-83)

006 235

25.000

Inom

Fig. 3-44, (p. 3-74)

MAIN: IB p.u.,de mand


Not measured

[spacer]

0.000

fnom

0.000

006 236

25.000

Inom

Fig. 3-44, (p. 3-74)

MAIN: IC p.u.,de mand


Not measured

0.000

006 237

25.000

Inom

Fig. 3-44, (p. 3-74)

[spacer]

Display of the delayed phase currents referred to Inom.

[spacer]

MAIN: IA p.u.,de mand s t or.


Not measured

[spacer]

25.000

Inom

Fig. 3-44, (p. 3-74)

MAIN: IB p.u.,de mand s tor.


Not measured

[spacer]

0.000

006 232

0.000

006 233

25.000

Inom

Fig. 3-44, (p. 3-74)

MAIN: IC p.u.,de mand st or.


Not measured

0.000

006 234

25.000

Inom

Fig. 3-44, (p. 3-74)

[spacer]

Display of the delayed stored phase currents referred to Inom.

[spacer]

MAIN: Current IP,max p.u.


Not measured

0.000

005 051

25.000

Inom

Fig. 3-43, (p. 3-73)

[spacer]

Display of the maximum phase current referred to Inom.

[spacer]

MAIN: IP,max p .u.,delay


Not measured

[spacer]

8-10

0.000

005 037

25.000

Inom

Fig. 3-44, (p. 3-74)

Display of the delayed maximum phase current referred to Inom.

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

MAIN: IP,max p .u.,st or ed


Not measured

0.000

005 035

25.000

Inom

Fig. 3-44, (p. 3-74)

[spacer]

Display of the delayed stored maximum phase current referred to Inom.

[spacer]

MAIN: Current IP,min p.u.


Not measured

0.000

005 056

25.000

Inom

Fig. 3-43, (p. 3-73)

[spacer]

Display of the minimum phase current referred to Inom.

[spacer]

MAIN: Current A p.u.


Not measured

005 041

0.000

25.000

[spacer]

Display of phase current A referred to Inom.

[spacer]

MAIN: Current B p.u.


Not measured

0.000

25.000

Display of phase current B referred to Inom.

[spacer]

MAIN: Current C p.u.

Inom

Fig. 3-43, (p. 3-73)

007 041

0.000

25.000

[spacer]

Display of phase current C referred to Inom.

[spacer]

MAIN: Current Ipos p.u.


Not measured

Fig. 3-43, (p. 3-73)

006 041

[spacer]

Not measured

Inom

0.000

Inom

Fig. 3-43, (p. 3-73)

009 016

25.000

Inom

[spacer]

Display of the positive sequence current referred to Inom.

[spacer]

MAIN: Current Ine g p.u.


Not measured

0.000

009 015

25.000

Inom

[spacer]

Display of the negative-sequence current referred to Inom.

[spacer]

MAIN: Current ( IP) p.u.


Not measured

0.000

005 011

25.000

Inom

Fig. 3-43, (p. 3-73)

[spacer]

Display of the calculated residual current referred to Inom.

[spacer]

MAIN: Current IN p. u.
Not measured

0.000

004 044

25.000

IN,nom

Fig. 3-45, (p. 3-75)

[spacer]

Display of the updated residual current value referred to Inom. The measured
residual current is displayed.

[spacer]

MAIN: Current IN par p.u.


Not measured

0.000

008 001

25.000

IN,nom

Fig. 3-46, (p. 3-75)

[spacer]

Display of the measured residual current of the parallel line referred to Inom.

[spacer]

MAIN: Voltage VP G,max p.u.


Not measured

[spacer]

0.000

25.000

008 043

Vnom

Fig. 3-49, (p. 3-78)

Display of the maximum phase-to-ground voltage referred to Vnom.

P437/EN M/R-11-A // P437311650

8-11

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

MAIN: Voltage VPG,min p.u.


Not measured

0.000

25.000

009 043

Vnom

Fig. 3-49, (p. 3-78)

[spacer]

Display of the minimum phase-to-ground voltage referred to Vnom.

[spacer]

MAIN: Angle VPG/IN p.u.


Not measured

-1.80

005 072

1.80

phi,ref

Fig. 3-52, (p. 3-81)

[spacer]

Display of the angle between the calculated neutral-point displacement voltage


and the measured residual current system quantities IN referred to 100.

[spacer]

MAIN: Voltage A-G p.u.


Not measured

0.000

005 043

25.000

Vnom

Fig. 3-49, (p. 3-78)

[spacer]

Display of the updated value for phase-to-ground voltage A-G referred to Vnom.

[spacer]

MAIN: Voltage B-G p.u.


Not measured

0.000

006 043

25.000

Vnom

Fig. 3-49, (p. 3-78)

[spacer]

Display of the updated value for phase-to-ground voltage B-G referred to Vnom.

[spacer]

MAIN: Voltage C- G p. u.
Not measured

0.000

007 043

25.000

Vnom

Fig. 3-49, (p. 3-78)

[spacer]

Display of the updated value for phase-to-ground voltage C-G referred to Vnom.

[spacer]

MAIN: Voltage Vpos p.u.


Not measured

0.000

009 018

25.000

Vnom

Fig. 3-49, (p. 3-78)

[spacer]

Display of the positive-sequence voltage referred to Vnom.

[spacer]

MAIN: Voltage Vne g p.u.


Not measured

0.000

009 017

25.000

Vnom

Fig. 3-49, (p. 3-78)

[spacer]

Display of the negative-sequence voltage referred to Vnom.

[spacer]

MAIN: Volt. (VPG )/ 3 p.u.


Not measured

0.000

005 013

12.000

Vnom

Fig. 3-49, (p. 3-78)

[spacer]

Display of the calculated neutral-point displacement voltage referred to Vnom.

[spacer]

MAIN: Voltage VNG p.u.


Not measured

0.000

004 042

25.000

VNG,nom

Fig. 3-50, (p. 3-79)

[spacer]

Display of the neutral-point displacement voltage measured at transformer T 90


referred to Vnom.

[spacer]

MAIN: Voltage Vref p.u.


Not measured

[spacer]

8-12

0.000

005 047

3.000

Vnom

Fig. 3-51, (p. 3-79)

Display of the reference voltage measured at transformer T 15 referred to Vnom.

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

MAIN: Voltage VP P,max p.u.


Not measured

0.000

25.000

008 045

Vnom

Fig. 3-49, (p. 3-78)

[spacer]

Display of the maximum phase-to-phase voltage referred to Vnom.

[spacer]

MAIN: Voltage VP P,min p.u.


Not measured

0.000

25.000

009 045

Vnom

Fig. 3-49, (p. 3-78)

[spacer]

Display of the minimum phase-to-phase voltage referred to Vnom.

[spacer]

MAIN: Voltage A- B p.u.


Not measured

0.000

005 045

25.000

Vnom

Fig. 3-49, (p. 3-78)

[spacer]

Display of the updated value for phase-to-phase voltage A-B referred to Vnom.

[spacer]

MAIN: Voltage B-C p.u.


Not measured

0.000

006 045

25.000

Vnom

Fig. 3-49, (p. 3-78)

[spacer]

Display of the updated value for phase-to-phase voltage B-C referred to Vnom.

[spacer]

MAIN: Voltage C- A p.u.


Not measured

0.000

007 045

25.000

Vnom

Fig. 3-49, (p. 3-78)

[spacer]

Display of the updated value for phase-to-phase voltage C-A referred to Vnom.

[spacer]

MAIN: Appar . po we r S p.u.


Not measured

-10.700

005 026

10.700

Snom

Fig. 3-52, (p. 3-81)

[spacer]

Display of the updated apparent power value referred to nominal apparent


power Snom.

[spacer]

MAIN: Active powe r P p. u.


Not measured

-7.500

004 051

7.500

Snom

Fig. 3-52, (p. 3-81)

[spacer]

Display of the updated active power value referred to nominal apparent power
Snom.

[spacer]

MAIN: Re ac. powe r Q p.u.


Not measured

-7.500

004 053

7.500

Snom

Fig. 3-52, (p. 3-81)

[spacer]

Display of the updated value for reactive power referred to nominal apparent
power Snom.

[spacer]

MAIN: Load angle phi A p.u


Not measured

-1.80

005 073

1.80

phi,ref

Fig. 3-52, (p. 3-81)

[spacer]

Display of the updated load angle value in phase A referred to 100C.

[spacer]

MAIN: Load angle phi B p.u


Not measured

[spacer]

-1.80

005 074

1.80

phi,ref

Fig. 3-52, (p. 3-81)

Display of the updated load angle value in phase B referred to 100C.

P437/EN M/R-11-A // P437311650

8-13

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

MAIN: Load angle phi C p.u


Not measured

-1.80

005 075

1.80

phi,ref

Fig. 3-52, (p. 3-81)

[spacer]

Display of the updated load angle value in phase C referred to 100C.

[spacer]

MAIN: Angle phi N p.u.


Not measured

-1.80

005 076

1.80

phi,ref

Fig. 3-52, (p. 3-81)

[spacer]

Display of the angle between the measured residual current system quantities IN
and VNG referred to 100.

[spacer]

MAIN: Angle VAG, IN


Not measured

[spacer]

008 004

-180.0

180.0

MAIN: Angle VAG, IN,par


Not measured

-180.0

008 003

180.0

[spacer]

Display of the angle between VAG and the two residual currents for the purpose
of checking correct connection of the transformer for measuring IN,par.

[spacer]

MAIN: Current I unfilt .


Not measured

0.000

004 074

25.000

Inom

[spacer]

Display of calculated unfiltered resultant current.

[spacer]

MAIN: Dumm y entry


Not measured

8-14

000 031

0.000

25.000

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter

Address

Default

Thermal overload
protection

Min

Max

Unit

Logic Diagram

THER M : S tatus THERM replica


Not measured

-25000

25000

004 016

Fig. 3-277, (p. 3-357)

[spacer]

Display of the buffer content of the thermal overload protection function.

[spacer]

THER M : Curre nt I,t he rm pr im


Not measured

[spacer]

Fig. 3-277, (p. 3-357)

THER M : Curre nt I,t he rm p. u


Not measured

[spacer]

25000

007 220

0.000

2.400

007 221

Iref

Fig. 3-277, (p. 3-357)

Display of the thermal current (as a primary quantity, or as a per unit quantity,
respectively).
These measured operating values are calculated as follows:
I therm,prim =
I therm,p.u. =

Statustherm. repl.
100

I ref I nom,CT,prim

I therm,prim
I ref I nom,CT,prim

With:

Itherm,prim = THER M: C urr e nt I,t he rm prim

Itherm,p.u. = THE RM: C ur r ent I,t he rm p.u

Statustherm. repl. = THE RM : Stat us THE RM r eplica

Iref = THER M: Ire f P Sx

Inom,CT,prim = MAIN: Inom C.T. prim.

In a measured values message the thermal current is processed as a per-unit


variable referred to Iref.
[spacer]

THER M : Object te mpe r at ur e


Not measured

-40

300

004 137

[spacer]

Display of the temperature of the protected object.

[spacer]

THER M : Coolant t empe ratur e


Not measured

[spacer]

-40

200

Fig. 3-277, (p. 3-357)

004 149

Fig. 3-277, (p. 3-357)

Display of coolant temperature, dependent on the setting for THE RM: Sel ect
meas .inputPS x.
When set to Default temp. value the set temperature value will be displayed.
When set to From PT100 the temperature measured by the resistance
thermometer will be displayed. When set to From 20 mA input the temperature
measured via an external 20 mA transducer will be displayed.

[spacer]

THER M : Pre - trip t ime left


Not measured

[spacer]

0.0

004 139

1000.0

min

Fig. 3-277, (p. 3-357)

Display of the time remaining before the thermal overload protection function
will reach the tripping threshold (time-to-trip).

P437/EN M/R-11-A // P437311650

8-15

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

THER M : The rm . replica p.u.


Not measured

-2.50

2.50

004 017

100%

Fig. 3-277, (p. 3-357)

[spacer]

Display of the buffer content of the thermal overload protection function


referred to a buffer content of 100%.

[spacer]

THER M : Object te mp. p.u.


Not measured

-0.40

004 179

3.00

100C

Fig. 3-277, (p. 3-357)

[spacer]

Display of the temperature of the protected object referred to 100C.

[spacer]

THER M : Coolant t emp. p.u.


Not measured

-0.40

004 178

2.00

100C

Fig. 3-277, (p. 3-357)

[spacer]

Display of the coolant temperature referred to 100C.

[spacer]

THER M : Te m p. offse t re pli ca


Not measured

[spacer]

-25000

25000

004 109

Fig. 3-277, (p. 3-357)

Display of the additional reserve if coolant temperature is taken into account


and if the measured coolant temperature is lower than the set maximum
permissible coolant temperature. (In this case, the thermal model has been
shifted downwards.)
If there is no coolant temperature acquisition and if the coolant temperature and
the maximum permissible coolant temperature have been set to the same
value, then the coolant temperature is not taken into account and the
characteristic is a function of the current only. The additional reserve amounts
to 0 in this case.
Parameter
Default

Binary counts

Logic Diagram
217 100

65535

Fig. 3-345, (p. 3-431)


217 080

65535
217 081

65535

COUNT : Count 4
0

[spacer]

Unit

COUNT : Count 3
0

[spacer]

Max

COUNT : Count 2
0

[spacer]

Min

COUNT : Count 1
0

[spacer]

Address

217 082

65535

Display of the updated count.


Note: The count value can be set here (Preload-Function).

8-16

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

8.1.1.2

Physical St ate Sign als


Parameter
Default

InterMiCOM
interface

Address
Min

Max

COMM 3: State r ece iv e 1

Unit

Logic Diagram
120 000

0: 0
[spacer]

COMM 3: State r ece iv e 2

120 003

0: 0
[spacer]

COMM 3: State r ece iv e 3

120 006

0: 0
[spacer]

COMM 3: State r ece iv e 4

120 009

0: 0
[spacer]

COMM 3: State r ece iv e 5

120 012

0: 0
[spacer]

COMM 3: State r ece iv e 6

120 015

0: 0
[spacer]

COMM 3: State r ece iv e 7

120 018

0: 0
[spacer]

COMM 3: State r ece iv e 8

120 021

0: 0
[spacer]

COMM 4: State r ece iv e 1

122 000

0: 0
[spacer]

COMM 4: State r ece iv e 2

122 003

0: 0
[spacer]

COMM 4: State r ece iv e 3

122 006

0: 0
[spacer]

COMM 4: State r ece iv e 4

122 009

0: 0
[spacer]

COMM 4: State r ece iv e 5

122 012

0: 0
[spacer]

COMM 4: State r ece iv e 6

122 015

0: 0
[spacer]

COMM 4: State r ece iv e 7

122 018

0: 0
[spacer]

COMM 4: State r ece iv e 8

122 021

0: 0
[spacer]

Display of the relevant receive signal.

[spacer]

COMM 3: State send 1

121 000

0: 0

P437/EN M/R-11-A // P437311650

8-17

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

COMM 3: State s end 2

121 002

0: 0
[spacer]

COMM 3: State s end 3

121 004

0: 0
[spacer]

COMM 3: State s end 4

121 006

0: 0
[spacer]

COMM 3: State s end 5

121 008

0: 0
[spacer]

COMM 3: State s end 6

121 010

0: 0
[spacer]

COMM 3: State s end 7

121 012

0: 0
[spacer]

COMM 3: State s end 8

121 014

0: 0
[spacer]

COMM 4: State s end 1

123 000

0: 0
[spacer]

COMM 4: State s end 2

123 002

0: 0
[spacer]

COMM 4: State s end 3

123 004

0: 0
[spacer]

COMM 4: State s end 4

123 006

0: 0
[spacer]

COMM 4: State s end 5

123 008

0: 0
[spacer]

COMM 4: State s end 6

123 010

0: 0
[spacer]

COMM 4: State s end 7

123 012

0: 0
[spacer]

COMM 4: State s end 8

123 014

0: 0
[spacer]

8-18

Display of the updated value for the relevant send signal.

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

IEC Generic
Substation Status
Events

Address
Min

GSS E: Output 1 st ate

Max

Unit

Logic Diagram
104 100

0: 0
[spacer]

GSS E: Output 2 st ate

104 103

0: 0
[spacer]

GSS E: Output 3 st ate

104 106

0: 0
[spacer]

GSS E: Output 4 st ate

104 109

0: 0
[spacer]

GSS E: Output 5 st ate

104 112

0: 0
[spacer]

GSS E: Output 6 st ate

104 115

0: 0
[spacer]

GSS E: Output 7 st ate

104 118

0: 0
[spacer]

GSS E: Output 8 st ate

104 121

0: 0
[spacer]

GSS E: Output 9 st ate

104 124

0: 0
[spacer]

GSS E: Output 10 st at e

104 127

0: 0
[spacer]

GSS E: Output 11 st at e

104 130

0: 0
[spacer]

GSS E: Output 12 st at e

104 133

0: 0
[spacer]

GSS E: Output 13 st at e

104 136

0: 0
[spacer]

GSS E: Output 14 st at e

104 139

0: 0
[spacer]

GSS E: Output 15 st at e

104 142

0: 0
[spacer]

GSS E: Output 16 st at e

104 145

0: 0
[spacer]

GSS E: Output 17 st at e

104 148

0: 0
[spacer]

GSS E: Output 18 st at e

104 151

0: 0

P437/EN M/R-11-A // P437311650

8-19

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

GSS E: Output 19 st at e

Logic Diagram
104 154

0: 0
[spacer]

GSS E: Output 20 st at e

104 157

0: 0
[spacer]

GSS E: Output 21 st at e

104 160

0: 0
[spacer]

GSS E: Output 22 st at e

104 163

0: 0
[spacer]

GSS E: Output 23 st at e

104 166

0: 0
[spacer]

GSS E: Output 24 st at e

104 169

0: 0
[spacer]

GSS E: Output 25 st at e

104 172

0: 0
[spacer]

GSS E: Output 26 st at e

104 175

0: 0
[spacer]

GSS E: Output 27 st at e

104 178

0: 0
[spacer]

GSS E: Output 28 st at e

104 181

0: 0
[spacer]

GSS E: Output 29 st at e

104 184

0: 0
[spacer]

GSS E: Output 30 st at e

104 187

0: 0
[spacer]

GSS E: Output 31 st at e

104 190

0: 0
[spacer]

GSS E: Output 32 st at e

104 193

0: 0
[spacer]

Display of the virtual binary GSSE output state.

[spacer]

GSS E: Inp ut 1 s tat e

105 000

0: 0
[spacer]

GSS E: Inp ut 2 s tat e

105 005

0: 0
[spacer]

GSS E: Inp ut 3 s tat e

105 010

0: 0
[spacer]

GSS E: Inp ut 4 s tat e

105 015

0: 0

8-20

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

GSS E: Inp ut 5 st at e

Address
Min

Max

Unit

Logic Diagram
105 020

0: 0
[spacer]

GSS E: Inp ut 6 st at e

105 025

0: 0
[spacer]

GSS E: Inp ut 7 st at e

105 030

0: 0
[spacer]

GSS E: Inp ut 8 st at e

105 035

0: 0
[spacer]

GSS E: Inp ut 9 st at e

105 040

0: 0
[spacer]

GSS E: Inp ut 10 stat e

105 045

0: 0
[spacer]

GSS E: Inp ut 11 stat e

105 050

0: 0
[spacer]

GSS E: Inp ut 12 stat e

105 055

0: 0
[spacer]

GSS E: Inp ut 13 stat e

105 060

0: 0
[spacer]

GSS E: Inp ut 14 stat e

105 065

0: 0
[spacer]

GSS E: Inp ut 15 stat e

105 070

0: 0
[spacer]

GSS E: Inp ut 16 stat e

105 075

0: 0
[spacer]

GSS E: Inp ut 17 stat e

105 080

0: 0
[spacer]

GSS E: Inp ut 18 stat e

105 085

0: 0
[spacer]

GSS E: Inp ut 19 stat e

105 090

0: 0
[spacer]

GSS E: Inp ut 20 stat e

105 095

0: 0
[spacer]

GSS E: Inp ut 21 stat e

105 100

0: 0
[spacer]

GSS E: Inp ut 22 stat e

105 105

0: 0
[spacer]

GSS E: Inp ut 23 stat e

105 110

0: 0

P437/EN M/R-11-A // P437311650

8-21

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

GSS E: Inp ut 24 stat e

Logic Diagram
105 115

0: 0
[spacer]

GSS E: Inp ut 25 stat e

105 120

0: 0
[spacer]

GSS E: Inp ut 26 stat e

105 125

0: 0
[spacer]

GSS E: Inp ut 27 stat e

105 130

0: 0
[spacer]

GSS E: Inp ut 28 stat e

105 135

0: 0
[spacer]

GSS E: Inp ut 29 stat e

105 140

0: 0
[spacer]

GSS E: Inp ut 30 stat e

105 145

0: 0
[spacer]

GSS E: Inp ut 31 stat e

105 150

0: 0
[spacer]

GSS E: Inp ut 32 stat e

105 155

0: 0
[spacer]

8-22

Display of the virtual binary GSSE input state.

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Generic Object
Orientated
Substation Events

Address
Min

GOOSE: Output 1 stat e

Max

Unit

Logic Diagram
106 010

0: 0
[spacer]

GOOSE: Output 2 stat e

106 012

0: 0
[spacer]

GOOSE: Output 3 stat e

106 014

0: 0
[spacer]

GOOSE: Output 4 stat e

106 016

0: 0
[spacer]

GOOSE: Output 5 stat e

106 018

0: 0
[spacer]

GOOSE: Output 6 stat e

106 020

0: 0
[spacer]

GOOSE: Output 7 stat e

106 022

0: 0
[spacer]

GOOSE: Output 8 stat e

106 024

0: 0
[spacer]

GOOSE: Output 9 stat e

106 026

0: 0
[spacer]

GOOSE: Output 10 s tate

106 028

0: 0
[spacer]

GOOSE: Output 11 s tate

106 030

0: 0
[spacer]

GOOSE: Output 12 s tate

106 032

0: 0
[spacer]

GOOSE: Output 13 s tate

106 034

0: 0
[spacer]

GOOSE: Output 14 s tate

106 036

0: 0
[spacer]

GOOSE: Output 15 s tate

106 038

0: 0
[spacer]

GOOSE: Output 16 s tate

106 040

0: 0
[spacer]

GOOSE: Output 17 s tate

106 042

0: 0
[spacer]

GOOSE: Output 18 s tate

106 044

0: 0

P437/EN M/R-11-A // P437311650

8-23

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

GOOSE: Output 19 s tate

Logic Diagram
106 046

0: 0
[spacer]

GOOSE: Output 20 s tate

106 048

0: 0
[spacer]

GOOSE: Output 21 s tate

106 050

0: 0
[spacer]

GOOSE: Output 22 s tate

106 052

0: 0
[spacer]

GOOSE: Output 23 s tate

106 054

0: 0
[spacer]

GOOSE: Output 24 s tate

106 056

0: 0
[spacer]

GOOSE: Output 25 s tate

106 058

0: 0
[spacer]

GOOSE: Output 26 s tate

106 060

0: 0
[spacer]

GOOSE: Output 27 s tate

106 062

0: 0
[spacer]

GOOSE: Output 28 s tate

106 064

0: 0
[spacer]

GOOSE: Output 29 s tate

106 066

0: 0
[spacer]

GOOSE: Output 30 s tate

106 068

0: 0
[spacer]

GOOSE: Output 31 s tate

106 070

0: 0
[spacer]

GOOSE: Output 32 s tate

106 072

0: 0
[spacer]

Display of the virtual binary GOOSE output state.

[spacer]

GOOSE: Input 1 st ate

106 200

0: 0
[spacer]

GOOSE: Input 2 st ate

106 201

0: 0
[spacer]

GOOSE: Input 3 st ate

106 202

0: 0
[spacer]

GOOSE: Input 4 st ate

106 203

0: 0

8-24

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

GOOSE: Input 5 st ate

Max

Unit

Logic Diagram
106 204

0: 0
[spacer]

GOOSE: Input 6 st ate

106 205

0: 0
[spacer]

GOOSE: Input 7 st ate

106 206

0: 0
[spacer]

GOOSE: Input 8 st ate

106 207

0: 0
[spacer]

GOOSE: Input 9 st ate

106 208

0: 0
[spacer]

GOOSE: Input 10 st at e

106 209

0: 0
[spacer]

GOOSE: Input 11 st at e

106 210

0: 0
[spacer]

GOOSE: Input 12 st at e

106 211

0: 0
[spacer]

GOOSE: Input 13 st at e

106 212

0: 0
[spacer]

GOOSE: Input 14 st at e

106 213

0: 0
[spacer]

GOOSE: Input 15 st at e

106 214

0: 0
[spacer]

GOOSE: Input 16 st at e

106 215

0: 0
[spacer]

GOOSE: Input 17 st at e

106 216

0: 0
[spacer]

GOOSE: Input 18 st at e

106 217

0: 0
[spacer]

GOOSE: Input 19 st at e

106 218

0: 0
[spacer]

GOOSE: Input 20 st at e

106 219

0: 0
[spacer]

GOOSE: Input 21 st at e

106 220

0: 0
[spacer]

GOOSE: Input 22 st at e

106 221

0: 0
[spacer]

GOOSE: Input 23 st at e

106 222

0: 0

P437/EN M/R-11-A // P437311650

8-25

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

GOOSE: Input 24 st at e

Logic Diagram
106 223

0: 0
[spacer]

GOOSE: Input 25 st at e

106 224

0: 0
[spacer]

GOOSE: Input 26 st at e

106 225

0: 0
[spacer]

GOOSE: Input 27 st at e

106 226

0: 0
[spacer]

GOOSE: Input 28 st at e

106 227

0: 0
[spacer]

GOOSE: Input 29 st at e

106 228

0: 0
[spacer]

GOOSE: Input 30 st at e

106 229

0: 0
[spacer]

GOOSE: Input 31 st at e

106 230

0: 0
[spacer]

GOOSE: Input 32 st at e

106 231

0: 0
[spacer]

8-26

Display of the virtual binary GOOSE input state.

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Binary input

INP: State U 801

Address
Min

Max

Unit

Logic Diagram
184 001

0: "Low"
[spacer]

INP: State U 802

184 005

0: "Low"
[spacer]

INP: State U 803

184 009

0: "Low"
[spacer]

INP: State U 804

184 013

0: "Low"
[spacer]

INP: State U 805

184 017

0: "Low"
[spacer]

INP: State U 806

184 021

0: "Low"
[spacer]

INP: State U 100 1

152 162

0: "Low"
[spacer]

INP: State U 100 2

152 165

0: "Low"
[spacer]

INP: State U 100 3

152 168

0: "Low"
[spacer]

INP: State U 100 4

152 171

0: "Low"
[spacer]

INP: State U 100 5

152 174

0: "Low"
[spacer]

INP: State U 100 6

152 177

0: "Low"
[spacer]

INP: State U 120 1

152 198

0: "Low"
[spacer]

INP: State U 120 2

152 201

0: "Low"
[spacer]

INP: State U 120 3

152 204

0: "Low"
[spacer]

INP: State U 120 4

152 207

0: "Low"
[spacer]

INP: State U 120 5

152 210

0: "Low"
[spacer]

INP: State U 120 6

152 213

0: "Low"
[spacer]

INP: State U 140 1

190 001

0: "Low"

P437/EN M/R-11-A // P437311650

8-27

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

INP: State U 1402

190 005

0: "Low"
[spacer]

INP: State U 1403

190 009

0: "Low"
[spacer]

INP: State U 1404

190 013

0: "Low"
[spacer]

INP: State U 1405

190 017

0: "Low"
[spacer]

INP: State U 1406

190 021

0: "Low"
[spacer]

INP: State U 1601

192 001

0: "Low"
[spacer]

INP: State U 1602

192 005

0: "Low"
[spacer]

INP: State U 1603

192 009

0: "Low"
[spacer]

INP: State U 1604

192 013

0: "Low"
[spacer]

INP: State U 1605

192 017

0: "Low"
[spacer]

INP: State U 1606

192 021

0: "Low"
[spacer]

INP: State U 2001

153 086

0: "Low"
[spacer]

INP: State U 2002

153 089

0: "Low"
[spacer]

INP: State U 2003

153 092

0: "Low"
[spacer]

INP: State U 2004

153 095

0: "Low"
[spacer]

The state of the binary signal inputs is displayed as follows:

Without function: No functions are assigned to the binary signal input.

"Low": Not energized.

"High": Energized.

This display appears regardless of the setting for the binary signal input mode.

8-28

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Binary and analog


output

OUTP: St ate K 801

Address
Min

Max

Unit

Logic Diagram
150 168

0: Inactive
[spacer]

OUTP: St ate K 802

150 171

0: Inactive
[spacer]

OUTP: St ate K 803

150 174

0: Inactive
[spacer]

OUTP: St ate K 804

150 177

0: Inactive
[spacer]

OUTP: St ate K 805

150 180

0: Inactive
[spacer]

OUTP: St ate K 806

150 183

0: Inactive
[spacer]

OUTP: St ate K 807

150 186

0: Inactive
[spacer]

OUTP: St ate K 808

150 189

0: Inactive
[spacer]

OUTP: St ate K 100 1

150 216

0: Inactive
[spacer]

OUTP: St ate K 100 2

150 219

0: Inactive
[spacer]

OUTP: St ate K 100 3

150 222

0: Inactive
[spacer]

OUTP: St ate K 100 4

150 225

0: Inactive
[spacer]

OUTP: St ate K 100 5

150 228

0: Inactive
[spacer]

OUTP: St ate K 100 6

150 231

0: Inactive
[spacer]

OUTP: St ate K 100 7

150 234

0: Inactive
[spacer]

OUTP: St ate K 100 8

150 237

0: Inactive
[spacer]

OUTP: St ate K 120 1

151 008

0: Inactive
[spacer]

OUTP: St ate K 120 2

151 011

0: Inactive

P437/EN M/R-11-A // P437311650

8-29

P437

8 Information and Control Functions

Parameter
Default
[spacer]

OUTP: St ate K 120 3

Address
Min

Max

Unit

Logic Diagram
151 014

0: Inactive
[spacer]

OUTP: St ate K 120 4

151 017

0: Inactive
[spacer]

OUTP: St ate K 120 5

151 020

0: Inactive
[spacer]

OUTP: St ate K 120 6

151 023

0: Inactive
[spacer]

OUTP: St ate K 120 7

151 026

0: Inactive
[spacer]

OUTP: St ate K 120 8

151 029

0: Inactive
[spacer]

OUTP: St ate K 140 1

169 001

0: Inactive
[spacer]

OUTP: St ate K 140 2

169 005

0: Inactive
[spacer]

OUTP: St ate K 140 3

169 009

0: Inactive
[spacer]

OUTP: St ate K 140 4

169 013

0: Inactive
[spacer]

OUTP: St ate K 140 5

169 017

0: Inactive
[spacer]

OUTP: St ate K 140 6

169 021

0: Inactive
[spacer]

OUTP: St ate K 140 7

169 025

0: Inactive
[spacer]

OUTP: St ate K 140 8

169 029

0: Inactive
[spacer]

OUTP: St ate K 160 1

171 001

0: Inactive
[spacer]

OUTP: St ate K 160 2

171 005

0: Inactive
[spacer]

OUTP: St ate K 160 3

171 009

0: Inactive
[spacer]

OUTP: St ate K 160 4

171 013

0: Inactive
[spacer]

OUTP: St ate K 160 5

171 017

0: Inactive

8-30

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

OUTP: St ate K 160 6

Address
Min

Max

Unit

Logic Diagram
171 021

0: Inactive
[spacer]

OUTP: St ate K 160 7

171 025

0: Inactive
[spacer]

OUTP: St ate K 160 8

171 029

0: Inactive
[spacer]

OUTP: St ate K 180 1

173 001

0: Inactive
[spacer]

OUTP: St ate K 180 2

173 005

0: Inactive
[spacer]

OUTP: St ate K 180 3

173 009

0: Inactive
[spacer]

OUTP: St ate K 180 4

173 013

0: Inactive
[spacer]

OUTP: St ate K 180 5

173 017

0: Inactive
[spacer]

OUTP: St ate K 180 6

173 021

0: Inactive
[spacer]

OUTP: St ate K 200 1

151 200

0: Inactive
[spacer]

OUTP: St ate K 200 2

151 203

0: Inactive
[spacer]

OUTP: St ate K 200 3

151 206

0: Inactive
[spacer]

OUTP: St ate K 200 4

151 209

0: Inactive
[spacer]

OUTP: St ate K 200 5

151 212

0: Inactive
[spacer]

OUTP: St ate K 200 6

151 215

0: Inactive
[spacer]

OUTP: St ate K 200 7

151 218

0: Inactive

P437/EN M/R-11-A // P437311650

8-31

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

OUTP: St ate K 200 8

151 221

0: Inactive
[spacer]

The state of the output relays is displayed as follows:

Without function: No functions are assigned to the output relay.

Inactive: The output relay is not energized.

Active: The output relay is energized.

This display appears regardless of the operating mode set for the output relay.

8-32

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

LED indicators

LED: S tat e H 1 green

Address
Min

Max

Unit

Logic Diagram
085 180

1: Active
[spacer]

LED: S tat e H 2 ye ll.

085 000

0: Inactive
[spacer]

LED: S tat e H 3 ye ll.

085 003

0: Inactive
[spacer]

LED: S tat e H 4 re d

085 006

0: Inactive
[spacer]

LED: S tat e H 5 re d

085 009

0: Inactive
[spacer]

LED: S tat e H 6 re d

085 012

0: Inactive
[spacer]

LED: S tat e H 7 re d

085 015

0: Inactive
[spacer]

LED: S tat e H 8 re d

085 018

0: Inactive
[spacer]

LED: S tat e H 9 re d

085 021

0: Inactive
[spacer]

LED: S tat e H10 re d

085 024

0: Inactive
[spacer]

LED: S tat e H11 re d

085 027

0: Inactive
[spacer]

LED: S tat e H12 re d

085 030

0: Inactive
[spacer]

LED: S tat e H13 re d

085 033

0: Inactive
[spacer]

LED: S tat e H14 re d

085 036

0: Inactive
[spacer]

LED: S tat e H15 re d

085 039

0: Inactive
[spacer]

LED: S tat e H16 re d

085 042

0: Inactive
[spacer]

LED: S tat e H17 re d.

085 181

0: Inactive
[spacer]

LED: S tat e H18 re d

085 130

0: Inactive
[spacer]

LED: S tat e H19 re d

085 133

0: Inactive

P437/EN M/R-11-A // P437311650

8-33

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

LED: S tat e H20 red

Max

Unit

Logic Diagram
085 136

0: Inactive
[spacer]

LED: S tat e H21 red

085 139

0: Inactive
[spacer]

LED: S tat e H22 red

085 142

0: Inactive
[spacer]

LED: S tat e H23 red

085 145

0: Inactive
[spacer]

LED: S tat e H 4 g reen

085 056

0: Inactive
[spacer]

LED: S tat e H 5 g reen

085 059

0: Inactive
[spacer]

LED: S tat e H 6 g reen

085 062

0: Inactive
[spacer]

LED: S tat e H 7 g reen

085 065

0: Inactive
[spacer]

LED: S tat e H 8 g reen

085 068

0: Inactive
[spacer]

LED: S tat e H 9 g reen

085 071

0: Inactive
[spacer]

LED: S tat e H10 gr e en

085 074

0: Inactive
[spacer]

LED: S tat e H11 gr e en

085 077

0: Inactive
[spacer]

LED: S tat e H12 gr e en

085 080

0: Inactive
[spacer]

LED: S tat e H13 gr e en

085 083

0: Inactive
[spacer]

LED: S tat e H14 gr e en

085 086

0: Inactive
[spacer]

LED: S tat e H15 gr e en

085 089

0: Inactive
[spacer]

LED: S tat e H16 gr e en

085 092

0: Inactive
[spacer]

LED: S tat e H18 gr e en

085 160

0: Inactive
[spacer]

LED: S tat e H19 gr e en

085 163

0: Inactive

8-34

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

LED: S tat e H20 gr e en

085 166

0: Inactive
[spacer]

LED: S tat e H21 gr e en

085 169

0: Inactive
[spacer]

LED: S tat e H22 gr e en

085 172

0: Inactive
[spacer]

LED: S tat e H23 gr e en

085 176

0: Inactive
[spacer]

The state of the LED indicators is displayed as follows:

Inactive: The LED indicator is not energized.

Active: The LED indicator is energized.

Parameter
Default

Configurable func
tion keys

Address
Min

Max

Unit

Logic Diagram

F_KEY: St ate F1

080 122

0: "Off"
[spacer]

F_KEY: St ate F2

080 123

0: "Off"
[spacer]

F_KEY: St ate F3

080 124

0: "Off"
[spacer]

F_KEY: St ate F4

080 125

0: "Off"
[spacer]

F_KEY: St ate F5

080 126

0: "Off"
[spacer]

F_KEY: St ate F6

080 127

0: "Off"
[spacer]

The state of the function keys is displayed as follows:

Without function: No functions are assigned to the function key.

"Off": The function key is in the Off position.

"On": The function key is in the On position.

P437/EN M/R-11-A // P437311650

8-35

P437
8.1.1.3

8 Information and Control Functions

Logic S tat e Sig nals


Parameter
Default

Local control panel

Address
Min

LOC: Ed it mode

Max

Unit

Logic Diagram
080 111

0: No
[spacer]

Signal that the protection unit is in edit mode. As a standard this signal is linked
to LED: Fct.as sig. H1 7 r ed.

[spacer]

LOC: Tr ig. m enu jmp 1 E XT

030 230

0: No
[spacer]

Signal that menu jump list 1 is being triggered. (See the corresponding setting
at LOC: Fct. menu jmp lis t 1.)

[spacer]

LOC: Tr ig. m enu jmp 2 E XT

030 231

0: No
[spacer]

Signal that menu jump list 2 is being triggered. (See the corresponding setting
at LOC: Fct. menu jmp lis t 2.)

[spacer]

LOC: Illum ination on EX T

037 101

0: No
[spacer]

8-36

This signal shows that the backlighting for the front panel LCD is switched on.

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Logical
communication
interface 1

Address
Min

Max

Unit

Logic Diagram

COMM 1: Com m and bloc k. E X T

003 173

0: No
[spacer]

COMM 1: Sig./ meas. block EX T

037 074

0: No
[spacer]

COMM 1: Com m and bloc king

003 174

0: No
[spacer]

Fig. 3-6, (p. 3-11)

COMM 1: Sig./ meas.v al.block.

037 075

0: No

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)

[spacer]

COMM 1: IEC 870-5 -10 3

003 219

0: No
[spacer]

COMM 1: IEC 870-5 -10 1

003 218

0: No
[spacer]

COMM 1: IEC 870-5 , ILS

003 221

0: No
[spacer]

COMM 1: MODB US

003 223

0: No
[spacer]

COMM 1: DNP3

003 230

0: No
[spacer]

COMM 1: COUR IER

103 041

0: No

Parameter
Default

InterMiCOM
interface

Address
Min

Max

COMM 3: Res et No.t lg. er r.EX T

Unit

Logic Diagram
006 054

0: No
[spacer]

COMM 3: Com m unicati ons fault

120 043

0: No
[spacer]

COMM 3: Com m . link fai lur e

120 044

0: No
[spacer]

COMM 3: Lim.ex ce e d.,te l.e rr .

120 045

0: No

P437/EN M/R-11-A // P437311650

8-37

P437

8 Information and Control Functions

Parameter
Default

InterMiCOM
interface

Address
Min

Max

Unit

Logic Diagram

COMM 4: Res et No.t lg. er r.EX T

011 243

0: No
[spacer]

COMM 4: Com m unicati ons fault

122 043

0: No
[spacer]

COMM 4: Com m . link fai lur e

122 044

0: No
[spacer]

COMM 4: Lim.ex cee d.,te l.e rr .

122 045

0: No

Parameter
Default

IRIGB interface

Address
Min

Max

Unit

IRIGB: Enabled

023 201

0: No
[spacer]

Fig. 3-22, (p. 3-38)

IRIGB: S ynchron. re ady

023 202

0: No

Fig. 3-22, (p. 3-38)

Parameter
Default

IEC Generic
Substation Status
Events

Logic Diagram

Address
Min

Max

Unit

GSS E: IE D link f aulty

Logic Diagram
105 181

0: No
[spacer]

Display which appears as soon as receipt of at least one of the configured


GOOSEs is faulty or not available. To each GOOSE the GOOSE sending device
will attach a validity stamp, up to which a repetition of GOOSE will be carried out
independent of a change of state. Thus the unit monitors the time period at
which the next state signal must be received.
Parameter
Default

IEC 61850
Communication

Address
Min

IEC: Com m . link fault y

Max

Unit

Logic Diagram
105 180

0: No
[spacer]

8-38

Display when an Ethernet module is not operational, i.e. if the MAC address is
missing or there is a non-plausible parameter setting.

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Generic Object
Orientated
Substation Events

Address
Min

GOOSE: IE D01 link fault y

Max

Unit

Logic Diagram
107 180

0: No
[spacer]

GOOSE: IE D02 link fault y

107 181

0: No
[spacer]

GOOSE: IE D03 link fault y

107 182

0: No
[spacer]

GOOSE: IE D04 link fault y

107 183

0: No
[spacer]

GOOSE: IE D05 link fault y

107 184

0: No
[spacer]

GOOSE: IE D06 link fault y

107 185

0: No
[spacer]

GOOSE: IE D07 link fault y

107 186

0: No
[spacer]

GOOSE: IE D08 link fault y

107 187

0: No
[spacer]

GOOSE: IE D09 link fault y

107 188

0: No
[spacer]

GOOSE: IE D10 link fault y

107 189

0: No
[spacer]

GOOSE: IE D11 link fault y

107 190

0: No
[spacer]

GOOSE: IE D12 link fault y

107 191

0: No
[spacer]

GOOSE: IE D13 link fault y

107 192

0: No
[spacer]

GOOSE: IE D14 link fault y

107 193

0: No
[spacer]

GOOSE: IE D15 link fault y

107 194

0: No
[spacer]

GOOSE: IE D16 link fault y

107 195

0: No
[spacer]

GOOSE: IE D17 link fault y

107 200

0: No
[spacer]

GOOSE: IE D18 link fault y

107 201

0: No

P437/EN M/R-11-A // P437311650

8-39

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

GOOSE: IE D19 link fault y

Max

Unit

Logic Diagram
107 202

0: No
[spacer]

GOOSE: IE D20 link fault y

107 203

0: No
[spacer]

GOOSE: IE D21 link fault y

107 204

0: No
[spacer]

GOOSE: IE D22 link fault y

107 205

0: No
[spacer]

GOOSE: IE D23 link fault y

107 206

0: No
[spacer]

GOOSE: IE D24 link fault y

107 207

0: No
[spacer]

GOOSE: IE D25 link fault y

107 208

0: No
[spacer]

GOOSE: IE D26 link fault y

107 209

0: No
[spacer]

GOOSE: IE D27 link fault y

107 210

0: No
[spacer]

GOOSE: IE D28 link fault y

107 211

0: No
[spacer]

GOOSE: IE D29 link fault y

107 212

0: No
[spacer]

GOOSE: IE D30 link fault y

107 213

0: No
[spacer]

GOOSE: IE D31 link fault y

107 214

0: No
[spacer]

GOOSE: IE D32 link fault y

107 215

0: No
[spacer]

8-40

Display whether GOOSE receipt of the configured signal is faulty or not


available. To each GOOSE the GOOSE sending device will attach a validity
stamp, up to which a repetition of GOOSE will be carried out independent of a
change of state. Thus the protection and control unit monitors the time period at
which the next state signal must be received.

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

GOOSE: IE D link fault y

107 250

0: No
[spacer]

Display which appears as soon as receipt of at least one of the configured


GOOSEs is faulty or not available. To each GOOSE the GOOSE sending device
will attach a validity stamp, up to which a repetition of GOOSE will be carried out
independent of a change of state. Thus the unit monitors the time period at
which the next state signal must be received.

[spacer]

GOOSE: IE D01-16 link ed

107 251

2:
[spacer]

GOOSE: IE D17-32 link ed

107 252

2:
[spacer]

GOOSE: Or dRun01 -1 6 link ed

107 248

2:
[spacer]

GOOSE: Or dRun17 -3 2 link ed

107 249

2:
[spacer]

GOOSE: Uniquene ss 1- 16
Not measured

[spacer]

007 217

65535

GOOSE: Uniquene ss 17-3 2


Not measured

007 218

65535

Parameter
Default

Address
Min

Max

Unit

Logic Diagram

Measured data input MEASI: Rs t. temp. T max E X T

006 076

0: No
[spacer]

MEASI: E nable d
0: No

035 008

Fig. 3-25, (p. 3-43)


Fig. 3-33, (p. 3-52)

[spacer]

MEASI: PT 100 fault y


0: No

[spacer]

Fig. 3-30, (p. 3-48)

MEASI: O ve rload 2 0 mA input


0: No

[spacer]

040 190

040 191

Fig. 3-28, (p. 3-46)

MEASI: O pe n circ. 2 0 mA inp.


0: No

P437/EN M/R-11-A // P437311650

040 192

Fig. 3-28, (p. 3-46)

8-41

P437

8 Information and Control Functions

Parameter
Default

Binary and analog


output

Address
Min

Max

Unit

Logic Diagram

OUTP: Block outp .r el. EXT

040 014

0: No
[spacer]

OUTP: Re s e t latch. E XT

040 015

0: No
[spacer]

OUTP: Outp . relays blocke d


1: Yes

[spacer]

Fig. 3-31, (p. 3-50)

OUTP: Latching res et


0: No

8-42

021 015

040 088

Fig. 3-31, (p. 3-50)

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Measured data
output

Address
Min

Max

Unit

Logic Diagram

MEASO: Outp. e nabled E XT

036 085

1: Yes
[spacer]

MEASO: Rese t output EX T

036 087

0: No
[spacer]

MEASO: Enab led

037 102

0: No
[spacer]

MEASO: Output r ese t


0: No

[spacer]

Fig. 3-37, (p. 3-57)


037 056

Fig. 3-37, (p. 3-57)


037 057

Fig. 3-37, (p. 3-57)


037 058

Fig. 3-37, (p. 3-57)


037 059

Fig. 3-37, (p. 3-57)


037 060

Fig. 3-37, (p. 3-57)


069 014

Fig. 3-39, (p. 3-63)

MEASO: Value A- 1 out put


0: No

[spacer]

037 055

MEASO: Value A- 1 valid


0: No

[spacer]

Fig. 3-37, (p. 3-57)

MEASO: 100-dig. bit 1 (BC D)


0: No

[spacer]

037 054

MEASO: 100-dig. bit 0 (BC D)


0: No

[spacer]

Fig. 3-37, (p. 3-57)

MEASO: 10-digit bit 3 (BC D)


0: No

[spacer]

037 053

MEASO: 10-digit bit 2 (BC D)


0: No

[spacer]

Fig. 3-37, (p. 3-57)

MEASO: 10-digit bit 1 (BC D)


0: No

[spacer]

037 052

MEASO: 10-digit bit 0 (BC D)


0: No

[spacer]

Fig. 3-37, (p. 3-57)

MEASO: 1-digit bit 3 (B C D)


0: No

[spacer]

037 051

MEASO: 1-digit bit 2 (B C D)


0: No

[spacer]

Fig. 3-37, (p. 3-57)

MEASO: 1-digit bit 1 (B C D)


0: No

[spacer]

037 050

MEASO: 1-digit bit 0 (B C D)


0: No

[spacer]

Fig. 3-35, (p. 3-53)

MEASO: Valid BC D value


0: No

[spacer]

037 117

MEASO: Value A- 2 valid

037 118

Fig. 3-39, (p. 3-63)


069 015

0: No

P437/EN M/R-11-A // P437311650

8-43

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

MEASO: Value A-2 out put

Max

Unit

Logic Diagram
037 119

0: No

8-44

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Main function

Address
Min

Max

MAIN: Enable prot ect . E XT

Unit

Logic Diagram
003 027

2: Not configured
[spacer]

MAIN: Dis able prot ect . E XT

003 026

2: Not configured
[spacer]

MAIN: General re s et E XT

005 255

0: No
[spacer]

MAIN: Group res e t 1 E XT

005 209

0: No
[spacer]

MAIN: Group res e t 2 E XT

005 252

0: No
[spacer]

MAIN: Re s e t indicat. EX T

065 001

0: No
[spacer]

MAIN: Re s e t latch.tr ip E X T

040 138

0: No
[spacer]

MAIN: Re s e t.c.cl ./ tr.c EXT

005 210

0: No
[spacer]

MAIN: Rs t I P,m ax,st or. E X T

005 211

0: No
[spacer]

MAIN: Rs t me as.v.e ne r. E X T

005 212

0: No
[spacer]

MAIN: CB open 3p E XT

031 028

0: No
[spacer]

MAIN: CB close d 3 p EXT

036 051

0: No
[spacer]

MAIN: CB close d A EXT

031 029

0: No
[spacer]

MAIN: CB close d B E XT

031 030

0: No
[spacer]

MAIN: CB close d C EX T

031 031

0: No
[spacer]

MAIN: Blocking 1 E X T

040 060

0: No
[spacer]

MAIN: Blocking 2 E X T

040 061

0: No
[spacer]

MAIN: M.c.b. trip V EXT

004 061

0: No
[spacer]

MAIN: M.c.b. trip VNG E X T

002 183

0: No

P437/EN M/R-11-A // P437311650

8-45

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

MAIN: M.c.b. trip Vr e f E XT

Unit

Logic Diagram
036 086

0: No
[spacer]

MAIN: Trip cm d. block . E XT

036 045

0: No
[spacer]

MAIN: Man. trip cmd. E XT

037 018

0: No
[spacer]

MAIN: Man def. tri p A EX T

038 030

0: No
[spacer]

MAIN: Man def. tri p B E X T

038 031

0: No
[spacer]

MAIN: Man def. tri p C E X T

038 032

0: No
[spacer]

MAIN: Paralle l tr ip EX T

037 019

0: No
[spacer]

MAIN: Paralle l tr ip A E XT

036 052

0: No
[spacer]

MAIN: Paralle l tr ip B E XT

036 053

0: No
[spacer]

MAIN: Paralle l tr ip C E XT

036 054

0: No
[spacer]

MAIN: Par. trip ( 1p) E XT

002 066

0: No
[spacer]

MAIN: Transf e r t ri p. E X T

120 046

0: No
[spacer]

MAIN: Transf e r t ri p A EX T

120 047

0: No
[spacer]

MAIN: Transf e r t ri p B EX T

120 048

0: No
[spacer]

MAIN: Transf e r t ri p C E X T

120 049

0: No
[spacer]

MAIN: Blocking 1p trip E XT

041 078

0: No
[spacer]

MAIN: Man.cl.cmd.e nabl. EXT

041 023

0: No
[spacer]

MAIN: Man. clos e cmd. E X T

041 022

0: No
[spacer]

MAIN: Manual close E XT

036 047

0: No

8-46

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

MAIN: Tes t m ode EXT

037 070

0: No
[spacer]

MAIN: Tim e s witc hing E X T

003 096

0: Standard time
[spacer]

MAIN: Min-puls e c lock EXT

060 060

0: No
[spacer]

MAIN: Healthy

060 001

1: Yes
[spacer]

Signal that the protection unit is operational. By default this signal is linked to
LED: F ct.ass ig. H 1 gre e n.

[spacer]

MAIN: Tim e s yn chr oniz ed

009 109

0: No
[spacer]

MAIN: Blocked/fault y
1: Yes

[spacer]

Fig. 3-59, (p. 3-88)


010 224

Fig. 3-59, (p. 3-88)


010 225

Fig. 3-59, (p. 3-88)


031 040

Fig. 3-64, (p. 3-94)


031 039

Fig. 3-64, (p. 3-94)


031 032

Fig. 3-64, (p. 3-94)

MAIN: CB open B
0: No

[spacer]

010 223

MAIN: CB open A
0: No

[spacer]

Fig. 3-58, (p. 3-88)

MAIN: CB open >=1p


0: No

[spacer]

038 046

MAIN: CB open 3p
0: No

[spacer]

Fig. 3-58, (p. 3-88)

MAIN: Current flow C


0: No

[spacer]

003 028

MAIN: Current flow B


0: No

[spacer]

Fig. 3-78, (p. 3-110)

MAIN: Current flow A


0: No

[spacer]

037 071

MAIN: Prot. ex t. dis able d


1: Yes

[spacer]

Fig. 3-63, (p. 3-92)

MAIN: Prot. ex t. e nable d


0: No

[spacer]

004 060

MAIN: Tes t m ode


0: No

[spacer]

Fig. 3-63, (p. 3-92)

MAIN: Device not re ady


1: Yes

[spacer]

004 065

031 033

Fig. 3-64, (p. 3-94)

MAIN: CB open C
0: No

P437/EN M/R-11-A // P437311650

031 034

Fig. 3-64, (p. 3-94)

8-47

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

031 036

Fig. 3-64, (p. 3-94)


031 037

Fig. 3-64, (p. 3-94)


031 041

Fig. 3-64, (p. 3-94)


021 013

Fig. 3-72, (p. 3-103)

MAIN: Latch. trip c. res et


0: No

[spacer]

Fig. 3-64, (p. 3-94)

MAIN: Trip cm d. block ed


1: Yes

[spacer]

031 035

MAIN: CB pos .s ig. implaus.


0: No

[spacer]

Fig. 3-64, (p. 3-94)

MAIN: CB close d C
0: No

[spacer]

031 038

MAIN: CB close d B
0: No

[spacer]

Fig. 3-64, (p. 3-94)

MAIN: CB close d A
0: No

[spacer]

031 042

MAIN: CB close d >= 1p


0: No

[spacer]

Logic Diagram

MAIN: CB close d 3 p
0: No

[spacer]

Unit

040 139

Fig. 3-318, (p. 3-403)

MAIN: Gen. t rip command

035 071

0: No
[spacer]

MAIN: Gen. t rip command 1


0: No

[spacer]

036 073

Fig. 3-69, (p. 3-100)


036 074

Fig. 3-69, (p. 3-100)

MAIN: Gen. t rip command 2


0: No

[spacer]

Fig. 3-69, (p. 3-100)

MAIN: Trip com mand 1, C


0: No

[spacer]

036 072

MAIN: Trip com mand 1, B


0: No

[spacer]

Fig. 3-69, (p. 3-100)

MAIN: Trip com mand 1, A


0: No

[spacer]

036 071

036 022

Fig. 3-69, (p. 3-100)

MAIN: Gen. t rip signal

036 251

0: No
[spacer]

MAIN: Gen. t rip signal 1


0: No

[spacer]

Fig. 3-69, (p. 3-100)


036 007

Fig. 3-69, (p. 3-100)

MAIN: Trip s ignal 1, C


0: No

8-48

036 006

MAIN: Trip s ignal 1, B


0: No

[spacer]

Fig. 3-69, (p. 3-100)

MAIN: Trip s ignal 1, A


0: No

[spacer]

036 005

036 008

Fig. 3-69, (p. 3-100)

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

037 253

Fig. 3-68, (p. 3-99)


036 023

Fig. 3-69, (p. 3-100)

MAIN: Final trip


0: No

[spacer]

Fig. 3-68, (p. 3-99)

MAIN: Gen. t rip signal 2


0: No

[spacer]

037 252

MAIN: Trip s ignal 1, 3p


0: No

[spacer]

Logic Diagram

MAIN: Trip s ignal 1, 1p


0: No

[spacer]

Unit

038 103

Fig. 3-73, (p. 3-103)

MAIN: Se nd tr ans fe r tr ip

001 207

0: No
[spacer]

MAIN: Se nd tr ans fe r tr ip A

001 208

0: No
[spacer]

MAIN: Se nd tr ans fe r tr ip B

001 209

0: No
[spacer]

MAIN: Se nd tr ans fe r tr ip C

001 210

0: No
[spacer]

MAIN: Manual t ri p s ignal


0: No

[spacer]

Fig. 3-71, (p. 3-102)


034 048

Fig. 3-71, (p. 3-102)

MAIN: Manual t ri p s ignal C


0: No

[spacer]

034 047

MAIN: Manual t ri p s ignal B


0: No

[spacer]

Fig. 3-71, (p. 3-102)

MAIN: Manual t ri p s ignal A


0: No

[spacer]

034 017

MAIN: Man. cl. cmd.enabl.

034 049

Fig. 3-71, (p. 3-102)


039 113

0: No
[spacer]

MAIN: Man. clos e command

037 068

0: No
[spacer]

MAIN: Clos e command

037 009

0: No
[spacer]

MAIN: Clos e aft .man.cl.rqu

037 012

0: No
[spacer]

MAIN: Rush re str . A trig.

041 027

0: No
[spacer]

MAIN: Rush re str . B tr ig.

041 028

0: No
[spacer]

MAIN: Rush re str . C t ri g.

041 029

0: No

P437/EN M/R-11-A // P437311650

8-49

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

MAIN: General star ting

036 000

0: No
[spacer]

Fig. 3-66, (p. 3-96)

MAIN: St arting A

036 001

0: No
[spacer]

Fig. 3-66, (p. 3-96)

MAIN: St arting B

036 002

0: No
[spacer]

Fig. 3-66, (p. 3-96)

MAIN: St arting C

036 003

0: No
[spacer]

Fig. 3-66, (p. 3-96)

MAIN: St arting GF

036 004

0: No
[spacer]

Logic Diagram

Fig. 3-66, (p. 3-96)

MAIN: Short circuit AG

006 011

0: No
[spacer]

MAIN: Short circuit BG

006 012

0: No
[spacer]

MAIN: Short circuit C G

006 013

0: No
[spacer]

MAIN: Dumm y entry

004 129

0: No
[spacer]

MAIN: Without func tion

060 000

0: No
[spacer]

MAIN: Without func tion

061 000

0: No

Parameter
Default

Fault data
acquisition

FT_DA: Tr igger EX T

Address
Min

Max

Unit

Logic Diagram
036 088

0: No

8-50

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Parameter subset
selection

Address
Min

Max

Unit

Logic Diagram

PSS: Control via user EX T

036 101

0: No
[spacer]

PSS: Activate PS 1 EX T

065 002

2: Not configured
[spacer]

PSS: Activate PS 2 EX T

065 003

2: Not configured
[spacer]

PSS: Activate PS 3 EX T

065 004

2: Not configured
[spacer]

PSS: Activate PS 4 EX T

065 005

2: Not configured
[spacer]

PSS: Control via user


0: No

[spacer]

Fig. 3-79, (p. 3-112)


036 097

Fig. 3-79, (p. 3-112)


003 062

Fig. 3-79, (p. 3-112)


036 090

Fig. 3-79, (p. 3-112)


036 091

Fig. 3-79, (p. 3-112)

PSS: PS 3 active
0: No

[spacer]

036 096

PSS: PS 2 active
0: No

[spacer]

Fig. 3-79, (p. 3-112)

PSS: PS 1 active
1: Yes

[spacer]

036 095

PSS: Actual p ar am. s ubs e t


1: Parameter subset 1

[spacer]

Fig. 3-79, (p. 3-112)

PSS: PS 4 activat ed ext .


0: No

[spacer]

036 094

PSS: PS 3 activat ed ext .


0: No

[spacer]

Fig. 3-79, (p. 3-112)

PSS: PS 2 activat ed ext .


0: No

[spacer]

003 061

PSS: PS 1 activat ed ext .


0: No

[spacer]

Fig. 3-79, (p. 3-112)

PSS: Ex t.s el.param.s ubse t


0: No param. subset sel

[spacer]

036 102

036 092

Fig. 3-79, (p. 3-112)

PSS: PS 4 active
0: No

P437/EN M/R-11-A // P437311650

036 093

Fig. 3-79, (p. 3-112)

8-51

P437

8 Information and Control Functions

Parameter
Default

Self-monitoring

Address
Min

Max

Unit

Logic Diagram

SFMO N: C B faulty E X T

098 072

0: No
[spacer]

SFMO N: W arning (LE D)


0: No

[spacer]

Fig. 3-80, (p. 3-113)

SFMO N: W arning (re lay )


0: No

[spacer]

036 070

SFMO N: W arm restart e x ec.

036 100

Fig. 3-80, (p. 3-113)


041 202

0: No
[spacer]

SFMO N: C old re star t exe c.

041 201

0: No
[spacer]

SFMO N: C old re st. che ck sum

093 024

0: No
[spacer]

SFMO N: C old re st. SW updat e

093 025

0: No
[spacer]

SFMO N: B locking HW failur e

090 019

0: No
[spacer]

SFMO N: R elay Kxx faulty

041 200

0: No
[spacer]

SFMO N: Hardware clock fai l.

093 040

0: No
[spacer]

SFMO N: B at te ry failure

090 010

0: No
[spacer]

SFMO N: I nt e rm.volt. fail.RAM

093 026

0: No
[spacer]

SFMO N: +15V s upply faulty

093 081

0: No
[spacer]

SFMO N: +24V s upply faulty

093 082

0: No
[spacer]

SFMO N: - 15V s upply faulty

093 080

0: No
[spacer]

SFMO N: W rong m odule s lot 1

096 100

0: No
[spacer]

SFMO N: W rong m odule s lot 2

096 101

0: No
[spacer]

SFMO N: W rong m odule s lot 3

096 102

0: No
[spacer]

SFMO N: W rong m odule s lot 4

096 103

0: No

8-52

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

SFMO N: W rong module s lot 5

Unit

Logic Diagram
096 104

0: No
[spacer]

SFMO N: W rong module s lot 6

096 105

0: No
[spacer]

SFMO N: W rong module s lot 7

096 106

0: No
[spacer]

SFMO N: W rong module s lot 8

096 107

0: No
[spacer]

SFMO N: W rong module s lot 9

096 108

0: No
[spacer]

SFMO N: W rong module s lot 10

096 109

0: No
[spacer]

SFMO N: W rong module s lot 11

096 110

0: No
[spacer]

SFMO N: W rong module s lot 12

096 111

0: No
[spacer]

SFMO N: W rong module s lot 13

096 112

0: No
[spacer]

SFMO N: W rong module s lot 14

096 113

0: No
[spacer]

SFMO N: W rong module s lot 15

096 114

0: No
[spacer]

SFMO N: W rong module s lot 16

096 115

0: No
[spacer]

SFMO N: W rong module s lot 17

096 116

0: No
[spacer]

SFMO N: W rong module s lot 18

096 117

0: No
[spacer]

SFMO N: W rong module s lot 19

096 118

0: No
[spacer]

SFMO N: W rong module s lot 20

096 119

0: No
[spacer]

SFMO N: W rong module s lot 21

096 120

0: No
[spacer]

SFMO N: W rong module D ig.Bus

096 123

0: No
[spacer]

SFMO N: W rong module HM I

096 124

0: No

P437/EN M/R-11-A // P437311650

8-53

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

SFMO N: W rong m odule C omm

Unit

Logic Diagram
096 125

0: No
[spacer]

SFMO N: W rong m odule Ana. Bus

096 126

0: No
[spacer]

SFMO N: D e fe ct.module slot 1

097 000

0: No
[spacer]

SFMO N: D e fe ct.module slot 2

097 001

0: No
[spacer]

SFMO N: D e fe ct.module slot 3

097 002

0: No
[spacer]

SFMO N: D e fe ct.module slot 4

097 003

0: No
[spacer]

SFMO N: D e fe ct.module slot 5

097 004

0: No
[spacer]

SFMO N: D e fe ct.module slot 6

097 005

0: No
[spacer]

SFMO N: D e fe ct.module slot 7

097 006

0: No
[spacer]

SFMO N: D e fe ct.module slot 8

097 007

0: No
[spacer]

SFMO N: D e fe ct.module slot 9

097 008

0: No
[spacer]

SFMO N: D e fe ct.module slot10

097 009

0: No
[spacer]

SFMO N: D e fe ct.module slot11

097 010

0: No
[spacer]

SFMO N: D e fe ct.module slot12

097 011

0: No
[spacer]

SFMO N: D e fe ct.module slot13

097 012

0: No
[spacer]

SFMO N: D e fe ct.module slot14

097 013

0: No
[spacer]

SFMO N: D e fe ct.module slot15

097 014

0: No
[spacer]

SFMO N: D e fe ct.module slot16

097 015

0: No
[spacer]

SFMO N: D e fe ct.module slot17

097 016

0: No

8-54

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

SFMO N: D e fe ct.module slot18

Unit

Logic Diagram
097 017

0: No
[spacer]

SFMO N: D e fe ct.module slot19

097 018

0: No
[spacer]

SFMO N: D e fe ct.module slot20

097 019

0: No
[spacer]

SFMO N: D e fe ct.module slot21

097 020

0: No
[spacer]

SFMO N: M odule Y DP R fault y

093 110

0: No
[spacer]

SFMO N: M odule Y RAM fault y

093 111

0: No
[spacer]

SFMO N: E rror K 8 01

097 086

0: No
[spacer]

SFMO N: E rror K 8 02

097 087

0: No
[spacer]

SFMO N: E rror K 8 03

097 088

0: No
[spacer]

SFMO N: E rror K 8 04

097 089

0: No
[spacer]

SFMO N: E rror K 8 05

097 090

0: No
[spacer]

SFMO N: E rror K 8 06

097 091

0: No
[spacer]

SFMO N: E rror K 8 07

097 092

0: No
[spacer]

SFMO N: E rror K 8 08

097 093

0: No
[spacer]

SFMO N: E rror K 1 001

097 102

0: No
[spacer]

SFMO N: E rror K 1 002

097 103

0: No
[spacer]

SFMO N: E rror K 1 003

097 104

0: No
[spacer]

SFMO N: E rror K 1 004

097 105

0: No
[spacer]

SFMO N: E rror K 1 005

097 106

0: No

P437/EN M/R-11-A // P437311650

8-55

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

SFMO N: E rror K 1 006

Max

Unit

Logic Diagram
097 107

0: No
[spacer]

SFMO N: E rror K 1 007

097 108

0: No
[spacer]

SFMO N: E rror K 1 008

097 109

0: No
[spacer]

SFMO N: E rror K 1 201

097 118

0: No
[spacer]

SFMO N: E rror K 1 202

097 119

0: No
[spacer]

SFMO N: E rror K 1 203

097 120

0: No
[spacer]

SFMO N: E rror K 1 204

097 121

0: No
[spacer]

SFMO N: E rror K 1 205

097 122

0: No
[spacer]

SFMO N: E rror K 1 206

097 123

0: No
[spacer]

SFMO N: E rror K 1 207

097 124

0: No
[spacer]

SFMO N: E rror K 1 208

097 125

0: No
[spacer]

SFMO N: E rror K 1 401

097 134

0: No
[spacer]

SFMO N: E rror K 1 402

097 135

0: No
[spacer]

SFMO N: E rror K 1 403

097 136

0: No
[spacer]

SFMO N: E rror K 1 404

097 137

0: No
[spacer]

SFMO N: E rror K 1 405

097 138

0: No
[spacer]

SFMO N: E rror K 1 406

097 139

0: No
[spacer]

SFMO N: E rror K 1 407

097 140

0: No
[spacer]

SFMO N: E rror K 1 408

097 141

0: No

8-56

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

SFMO N: E rror K 1 601

Max

Unit

Logic Diagram
097 150

0: No
[spacer]

SFMO N: E rror K 1 602

097 151

0: No
[spacer]

SFMO N: E rror K 1 603

097 152

0: No
[spacer]

SFMO N: E rror K 1 604

097 153

0: No
[spacer]

SFMO N: E rror K 1 605

097 154

0: No
[spacer]

SFMO N: E rror K 1 606

097 155

0: No
[spacer]

SFMO N: E rror K 1 607

097 156

0: No
[spacer]

SFMO N: E rror K 1 608

097 157

0: No
[spacer]

SFMO N: E rror K 1 801

097 166

0: No
[spacer]

SFMO N: E rror K 1 802

097 167

0: No
[spacer]

SFMO N: E rror K 1 803

097 168

0: No
[spacer]

SFMO N: E rror K 1 804

097 169

0: No
[spacer]

SFMO N: E rror K 1 805

097 170

0: No
[spacer]

SFMO N: E rror K 1 806

097 171

0: No
[spacer]

SFMO N: E rror K 2 001

097 182

0: No
[spacer]

SFMO N: E rror K 2 002

097 183

0: No
[spacer]

SFMO N: E rror K 2 003

097 184

0: No
[spacer]

SFMO N: E rror K 2 004

097 185

0: No
[spacer]

SFMO N: E rror K 2 005

097 186

0: No

P437/EN M/R-11-A // P437311650

8-57

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

SFMO N: E rror K 2 006

097 187

0: No
[spacer]

SFMO N: E rror K 2 007

097 188

0: No
[spacer]

SFMO N: E rror K 2 008

097 189

0: No
[spacer]

SFMO N: U nd ef . ope r at. code

093 010

0: No
[spacer]

SFMO N: Abnormal t erminat ion

093 030

0: No
[spacer]

SFMO N: B ad arg. s ys t em call

093 031

0: No
[spacer]

SFMO N: M ute x de adloc k

093 032

0: No
[spacer]

SFMO N: I nvalid memory ref.

093 033

0: No
[spacer]

SFMO N: U ne xpe ct e d e xc ept ion

093 034

0: No
[spacer]

SFMO N: I nvalid ar ithm. op.

093 011

0: No
[spacer]

SFMO N: U nd ef ined i nter rupt

093 012

0: No
[spacer]

SFMO N: E x ce pt ion oper .s ys t .

093 013

0: No
[spacer]

SFMO N: Pr ote ction f ailure

090 021

0: No
[spacer]

SFMO N: C he ck s um error param

090 003

0: No
[spacer]

SFMO N: C lock sync. e rror

093 041

0: No
[spacer]

SFMO N: O ve rflow MT_RC


0: No

[spacer]

SFMO N: S em aph. M T_RC block .

090 012

Fig. 3-82, (p. 3-117)


093 015

0: No
[spacer]

SFMO N: T im e -out module Y

093 112

0: No
[spacer]

SFMO N: I nvalid SW d.loade d

096 121

0: No

8-58

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

SFMO N: I nvalid SW ver s DHMI

093 145

0: No
[spacer]

SFMO N: I nval. SW ve r s .C OMM1

093 075

0: No
[spacer]

SFMO N: I nval. C onfig. I EC

093 079

0: No
[spacer]

SFMO N: I nvalid SW ver s. Y

093 113

0: No
[spacer]

SFMO N: I nom not adjust able

093 118

0: No
[spacer]

SFMO N: I nvalid scali ng BCD

093 124

0: No
[spacer]

SFMO N: I nvalid scali ng A-1


0: No

[spacer]

093 114

Fig. 3-39, (p. 3-63)

SFMO N: I nvalid scali ng A-2

093 115

0: No
[spacer]

SFMO N: I nvalid scali ng IDC


0: No

[spacer]

098 035

Fig. 3-277, (p. 3-357)

SFMO N: S etting e rror f<>


0: No

[spacer]

Fig. 3-28, (p. 3-46)

SFMO N: S etting e rror THE RM


0: No

[spacer]

093 116

098 028

Fig. 3-297, (p. 3-378)

SFMO N: S etting e rror CB M

098 020

0: No
[spacer]

SFMO N: Pe riphe ral fault


0: No

[spacer]

Fig. 3-221, (p. 3-293)


098 011

Fig. 3-147, (p. 3-197)


098 001

Fig. 3-149, (p. 3-200)

SFMO N: Vne g> tr igger e d


0: No

[spacer]

098 132

SFMO N: Phas e se qu. V faulty


0: No

[spacer]

Fig. 3-147, (p. 3-197)

SFMO N: M .c.b. trip Vref


0: No

[spacer]

098 000

SFMO N: M .c.b. trip VNG


0: No

[spacer]

Fig. 3-147, (p. 3-197)

SFMO N: M .c.b. trip V


0: No

[spacer]

098 018

098 014

Fig. 3-149, (p. 3-200)

SFMO N: U nd er volt age


0: No

P437/EN M/R-11-A // P437311650

098 009

Fig. 3-149, (p. 3-200)

8-59

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

098 022

Fig. 3-151, (p. 3-205)


098 023

Fig. 3-147, (p. 3-197)

SFMO N: M eas . cir c. V f aul ty


0: No

[spacer]

Fig. 3-150, (p. 3-203)

SFMO N: M .circ. V,Vref fl ty.


0: No

[spacer]

098 021

SFMO N: F F, Vref trigge re d


0: No

[spacer]

Logic Diagram

SFMO N: F F, V trigge r ed
0: No

[spacer]

Unit

098 017

Fig. 3-147, (p. 3-197)

SFMO N: M eas .circ .VNG faulty

098 254

0: No
[spacer]

SFMO N: M .circ. Vre f fault y

098 255

0: No
[spacer]

SFMO N: B UOC not act iv e


0: No

[spacer]

098 005

Fig. 3-148, (p. 3-198)


098 016

Fig. 3-147, (p. 3-197)


098 015

Fig. 3-147, (p. 3-197)

SFMO N: M eas . cir cuits GF S C


0: No

[spacer]

Fig. 3-152, (p. 3-207)

SFMO N: Z ero-se qu. s tart ing


0: No

[spacer]

098 004

SFMO N: M eas .circ .V,I fault y


0: No

[spacer]

Fig. 3-152, (p. 3-207)

SFMO N: M eas . cir c. I fault y


0: No

[spacer]

098 003

SFMO N: B UOC act ive wit h ARC


0: No

[spacer]

Fig. 3-152, (p. 3-207)

SFMO N: B UOC act ive w/ o ARC


0: No

[spacer]

098 002

SFMO N: C ommunic.fault C OMM 3

098 013

Fig. 3-237, (p. 3-308)


093 140

0: No
[spacer]

SFMO N: C ommunic.fault C OMM 4

093 146

0: No
[spacer]

SFMO N: Hardware e r ror COM M3

093 143

0: No
[spacer]

SFMO N: Hardware e r ror COM M4

093 149

0: No
[spacer]

SFMO N: C omm.link fail.C OMM3

093 142

0: No
[spacer]

SFMO N: C omm.link fail.C OMM4

093 148

0: No

8-60

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

SFMO N: L im .e x c.te l.e r .COM M3

093 141

0: No
[spacer]

SFMO N: L im .e x c.te l.e r .COM M4

093 147

0: No
[spacer]

SFMO N: T elecom. faulty / PSI G


0: No

[spacer]

098 019

Fig. 3-163, (p. 3-218)

SFMO N: T elecom.faulty / GSC SG


0: No

[spacer]

Fig. 3-159, (p. 3-216)

SFMO N: O p.mode PS IG inv al.


0: No

[spacer]

098 006

SFMO N: C B pos .s ig. implaus.

098 027

Fig. 3-239, (p. 3-313)


098 124

0: No
[spacer]

SFMO N: C B No. C B op. >

098 066

0: No
[spacer]

SFMO N: C B rem. No. C B op. <

098 067

0: No
[spacer]

SFMO N: C B I trip >

098 068

0: No
[spacer]

SFMO N: C B I trip**2 >

098 069

0: No
[spacer]

SFMO N: C B tm ax> A

098 070

0: No
[spacer]

SFMO N: C B tm ax> B

098 071

0: No
[spacer]

SFMO N: C B tm ax> C

098 077

0: No
[spacer]

SFMO N: I nv.inp.f.cloc k sy nc

093 120

0: No
[spacer]

SFMO N: O utput 30

098 053

0: No
[spacer]

SFMO N: O utput 30 ( t)

098 054

0: No
[spacer]

SFMO N: O utput 31

098 055

0: No
[spacer]

SFMO N: O utput 31 ( t)

098 056

0: No
[spacer]

SFMO N: O utput 32

098 057

0: No

P437/EN M/R-11-A // P437311650

8-61

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

SFMO N: O utput 32 ( t)

098 058

0: No
[spacer]

SFMO N: PT 100 open c ir cuit

098 024

0: No
[spacer]

Fig. 3-30, (p. 3-48)

SFMO N: O ve rload 20 mA input

098 025

0: No
[spacer]

Fig. 3-28, (p. 3-46)

SFMO N: O pe n circ. 20 mA inp.

098 026

0: No
[spacer]

Fig. 3-28, (p. 3-46)

SFMO N: C T A error

098 034

0: No

Fig. 3-275, (p. 3-353)

Parameter
Default

Operating data
recording

Address
Min

Max

Unit

Logic Diagram

OP_R C: Res e t record. EX T

005 213

0: No

Fig. 3-76, (p. 3-107)

Parameter
Default

Monitoring signal
recording

Address
Min

Max

Unit

Logic Diagram

MT _RC: Res et record. E XT

005 240

0: No

Parameter
Default

Overload recording

Address
Min

Max

Unit

Logic Diagram

OL_RC: R e s et reco rd. EXT

005 241

0: No
[spacer]

OL_RC: R e cord. in progr es s

035 003

0: No
[spacer]

Fig. 3-85, (p. 3-120)

OL_RC: Over l. me m. ove rfl ow

035 007

0: No

Fig. 3-86, (p. 3-121)

Parameter
Default

Ground fault
recording

Address
Min

GF_R C: Re se t recor d. E X T

Max

Unit

Logic Diagram
005 242

0: No

8-62

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Fault recording

Address
Min

Max

Unit

Logic Diagram

FT_RC: Res et record. E XT

005 243

0: No
[spacer]

FT_RC: Trigg er E X T

036 089

0: No
[spacer]

FT_RC: Trigg er
0: No

[spacer]

037 076

Fig. 3-93, (p. 3-131)

FT_RC: I> triggere d

040 063

0: No
[spacer]

FT_RC: Record. t rig acti ve


0: No

[spacer]

Fig. 3-93, (p. 3-131)


035 004

Fig. 3-93, (p. 3-131)

FT_RC: Fault m e m. ov e rf low


0: No

[spacer]

035 000

FT_RC: Syst e m dis t urb. runn


0: No

[spacer]

Fig. 3-93, (p. 3-131)

FT_RC: Record. i n progre ss


0: No

[spacer]

002 002

FT_RC: Faulty time t ag

035 001

Fig. 3-94, (p. 3-132)


035 002

0: No

P437/EN M/R-11-A // P437311650

8-63

P437

8 Information and Control Functions

Parameter
Default

Distance protection

Address
Min

Max

Unit

Logic Diagram

DIST: Blocking Z1 EXT

036 034

0: No
[spacer]

DIST: Blocking Z1,ze E XT

036 036

0: No
[spacer]

DIST: Blocking Z2 EXT

036 037

0: No
[spacer]

DIST: Enable ZE f. 1pG E X T

038 025

0: No
[spacer]

DIST: Blocking Z3 EXT

036 039

0: No
[spacer]

DIST: Blocking Z4 EXT

036 041

0: No
[spacer]

DIST: Blocking Z5 EXT

036 044

0: No
[spacer]

DIST: Blocking Z6 EXT

036 061

0: No
[spacer]

DIST: Blocking Z7 EXT

036 067

0: No
[spacer]

DIST: Blocking Z8 EXT

036 068

0: No
[spacer]

DIST: Enabled
0: No

[spacer]

040 065

Fig. 3-107, (p. 3-148)


040 097

Fig. 3-107, (p. 3-148)


040 067

Fig. 3-107, (p. 3-148)


040 075

Fig. 3-107, (p. 3-148)

DIST: Starting V< C


0: No

8-64

Fig. 3-107, (p. 3-148)

DIST: Starting V< B


0: No

[spacer]

040 064

DIST: Starting V< A


0: No

[spacer]

Fig. 3-107, (p. 3-148)

DIST: Starting I>> C


0: No

[spacer]

011 139

DIST: Starting I>> B


0: No

[spacer]

Fig. 3-106, (p. 3-147)

DIST: Starting I>> A


0: No

[spacer]

036 240

DIST: Starting I>>


0: No

[spacer]

Fig. 3-96, (p. 3-135)

DIST: Ge ne ral s tarti ng


0: No

[spacer]

036 104

040 096

Fig. 3-107, (p. 3-148)

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

040 052

Fig. 3-99, (p. 3-139)


036 015

Fig. 3-98, (p. 3-138)


036 021

Fig. 3-106, (p. 3-147)


036 105

Fig. 3-98, (p. 3-138)


036 016

Fig. 3-98, (p. 3-138)

DIST: Fault for ward / LS


0: No

[spacer]

Fig. 3-107, (p. 3-148)

DIST: tVNG>> elapsed


0: No

[spacer]

040 072

DIST: tIN> running


0: No

[spacer]

Fig. 3-107, (p. 3-148)

DIST: Zero-s e qu . st art ing


0: No

[spacer]

040 071

DIST: VNG>> t riggere d


0: No

[spacer]

Fig. 3-107, (p. 3-148)

DIST: Start. swit ch. t o PG


0: No

[spacer]

040 070

DIST: Starting Z < C


0: No

[spacer]

Fig. 3-107, (p. 3-148)

DIST: Starting Z < B


0: No

[spacer]

036 241

DIST: Starting Z < A


0: No

[spacer]

Logic Diagram

DIST: Starting Z <


0: No

[spacer]

Unit

036 018

Fig. 3-113, (p. 3-157)

DIST: Fault for wd. / LS , A

038 010

0: No
[spacer]

DIST: Fault for wd. / LS , B

038 012

0: No
[spacer]

DIST: Fault for wd. / LS , C

038 014

0: No
[spacer]

DIST: Fault back war d / BS


0: No

[spacer]

DIST: Fault back wd / BS, A

036 019

Fig. 3-113, (p. 3-157)


038 011

0: No
[spacer]

DIST: Fault back wd / BS, B

038 013

0: No
[spacer]

DIST: Fault back wd / BS, C

038 015

0: No
[spacer]

DIST: Dir ect. using Vme as

038 045

0: No
[spacer]

DIST: Dir .us ing Vmeas S ys2

038 105

0: No

P437/EN M/R-11-A // P437311650

8-65

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

DIST: Dir .us ing Vmeas S ys3

038 108

0: No
[spacer]

DIST: Dir ect. us ing me mory

038 047

0: No
[spacer]

DIST: Dir .us ing Vmem S y s2

038 106

0: No
[spacer]

DIST: Dir .us ing Vmem S y s3

038 109

0: No
[spacer]

DIST: Forw. w/o me asure m.

038 044

0: No
[spacer]

DIST: Forw. w/o me as. S ys2

038 104

0: No
[spacer]

DIST: Forw. w/o me as. S ys3

038 107

0: No
[spacer]

DIST: tVme m ory r unning


0: No

[spacer]

040 034

Fig. 3-111, (p. 3-154)

DIST: Zone e xtens ion


0: No

036 065

Fig. 3-120, (p. 3-165)


Fig. 3-124, (p. 3-170)

[spacer]

DIST: Zone e xtens ion E XT

036 046

0: No
[spacer]

DIST: Zone e xtens ion HS R


0: No

036 103

Fig. 3-120, (p. 3-165)


Fig. 3-124, (p. 3-170)

[spacer]

DIST: Zone e xt. HSR 1pG


0: No

[spacer]

039 029

Fig. 3-116, (p. 3-161)

DIST: Zone e xtens ion T D R


0: No

038 022

Fig. 3-120, (p. 3-165)


Fig. 3-124, (p. 3-170)

[spacer]

DIST: Zone e xt. 1 pG acti ve


0: No

[spacer]

DIST: Zone 1 s tart ing

039 028

Fig. 3-116, (p. 3-161)


001 094

0: No
[spacer]

DIST: Zone 1,ze s tart ing

002 067

0: No
[spacer]

DIST: Zone 2 s tart ing

001 095

0: No
[spacer]

DIST: Zone 3 s tart ing

001 096

0: No

8-66

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

DIST: Zone 4 s tart ing

001 097

0: No
[spacer]

DIST: Zone 5 s tart ing

001 098

0: No
[spacer]

DIST: Zone 6 s tart ing

001 099

0: No
[spacer]

DIST: Zone 7 s tart ing

001 100

0: No
[spacer]

DIST: Zone 8 s tart ing

001 101

0: No
[spacer]

DIST: t1 elaps e d
0: No

[spacer]

036 031

Fig. 3-127, (p. 3-175)


037 127

Fig. 3-127, (p. 3-175)


037 128

Fig. 3-127, (p. 3-175)


036 009

Fig. 3-131, (p. 3-179)


035 072

Fig. 3-130, (p. 3-178)


035 074

Fig. 3-130, (p. 3-178)

DIST: Trip s ig. zone 2 -8


0: No

[spacer]

Fig. 3-127, (p. 3-175)

DIST: Trip s ignal Z1,ze


0: No

[spacer]

036 030

DIST: Trip s ignal zone 1


0: No

[spacer]

Fig. 3-127, (p. 3-175)

DIST: Trip s ignal


0: No

[spacer]

036 029

DIST: t8 elaps e d
0: No

[spacer]

Fig. 3-127, (p. 3-175)

DIST: t7 elaps e d
0: No

[spacer]

036 028

DIST: t6 elaps e d
0: No

[spacer]

Fig. 3-127, (p. 3-175)

DIST: t5 elaps e d
0: No

[spacer]

036 027

DIST: t4 elaps e d
0: No

[spacer]

Fig. 3-126, (p. 3-174)

DIST: t3 elaps e d
0: No

[spacer]

035 079

DIST: t2 elaps e d
0: No

[spacer]

Fig. 3-126, (p. 3-174)

DIST: t1,ze elapse d


0: No

[spacer]

036 026

035 073

Fig. 3-131, (p. 3-179)

DIST: Trip s ignal zone 2


0: No

P437/EN M/R-11-A // P437311650

041 084

Fig. 3-131, (p. 3-179)

8-67

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

040 059

Fig. 3-131, (p. 3-179)


037 129

Fig. 3-131, (p. 3-179)


037 130

Fig. 3-131, (p. 3-179)


037 200

Fig. 3-133, (p. 3-181)


038 039

Fig. 3-109, (p. 3-152)

DIST: IN,par> trigger ed


0: No

8-68

Fig. 3-131, (p. 3-179)

DIST: With mutual comp.


0: No

[spacer]

040 058

DIST: Impe dance in zone 6


0: No

[spacer]

Fig. 3-131, (p. 3-179)

DIST: Trip s ignal zone 8


0: No

[spacer]

040 057

DIST: Trip s ignal zone 7


0: No

[spacer]

Fig. 3-131, (p. 3-179)

DIST: Trip s ignal zone 6


0: No

[spacer]

040 056

DIST: Trip s ignal zone 5


0: No

[spacer]

Logic Diagram

DIST: Trip s ignal zone 4


0: No

[spacer]

Unit

DIST: Trip s ignal zone 3


0: No

[spacer]

Max

037 210

Fig. 3-109, (p. 3-152)

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Power swing
blocking

Address
Min

Max

Unit

Logic Diagram

PSB: B locking E XT

008 248

0: No
[spacer]

PSB: B locked

011 144

0: No
[spacer]

PSB: B locking init. EX T

036 069

0: No
[spacer]

PSB: Enab led


0: No

[spacer]

Fig. 3-135, (p. 3-183)

PSB: Z within polygon


0: No

[spacer]

040 095

PSB: B locking initi ated

036 024

Fig. 3-136, (p. 3-184)


036 032

0: No
[spacer]

PSB: T rip s ignal

036 025

0: No
[spacer]

PSB: T rip s ignal OOS ( a)

006 035

0: No
[spacer]

PSB: T rip s ignal OOS ( b)

006 192

0: No
[spacer]

PSB: T rip s ignal st ab. P S

006 030

0: No
[spacer]

PSB: IP> tr igge re d

036 012

0: No
[spacer]

PSB: Ine g> tr igge re d

036 011

0: No
[spacer]

PSB: IN> t r iggere d

036 010

0: No

P437/EN M/R-11-A // P437311650

8-69

P437

8 Information and Control Functions

Parameter
Default

Measuring-circuit
monitoring

Address
Min

Max

Unit

Logic Diagram

MCM ON: Blocking FF, V E X T

002 182

0: No
[spacer]

MCM ON: Enabled


0: No

[spacer]

Fig. 3-149, (p. 3-200)


041 079

Fig. 3-149, (p. 3-200)


035 081

Fig. 3-150, (p. 3-203)


038 100

Fig. 3-151, (p. 3-205)

MCM ON: M e as . circ . V faulty


0: No

[spacer]

038 049

MCM ON: FF, Vr e f tr iggere d


0: No

[spacer]

Fig. 3-149, (p. 3-200)

MCM ON: FF, V t rigge re d


0: No

[spacer]

038 038

MCM ON: Vneg> trigger ed


0: No

[spacer]

Fig. 3-148, (p. 3-198)

MCM ON: Phas e s equ. V faulty


0: No

[spacer]

040 087

MCM ON: Und ervolt age


0: No

[spacer]

Fig. 3-148, (p. 3-198)

MCM ON: M e as . circ . I faul ty


0: No

[spacer]

040 094

038 023

Fig. 3-147, (p. 3-197)

MCM ON: M .circ. Vre f fault y

007 213

0: No
[spacer]

MCM ON: M .circ. VNG f aul ty

007 214

0: No
[spacer]

MCM ON: M .circ. V,Vr ef fl ty.


0: No

[spacer]

041 080

Fig. 3-147, (p. 3-197)


038 024

Fig. 3-147, (p. 3-197)

MCM ON: M e as . volt age o.k .


0: No

8-70

Fig. 3-147, (p. 3-197)

MCM ON: Peripheral fault


0: No

[spacer]

037 020

MCM ON: Ze ro-s equ. star ting


0: No

[spacer]

Fig. 3-147, (p. 3-197)

MCM ON: M e as .circ.V, I fault y


0: No

[spacer]

040 078

038 048

Fig. 3-149, (p. 3-200)

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Address
Min

Max

Unit

Logic Diagram

Backup overcurrent- BUOC: Enabled


time protection
0: No
[spacer]

Fig. 3-152, (p. 3-207)


036 013

Fig. 3-152, (p. 3-207)

BUOC: Tr ip s ignal
0: No

[spacer]

037 021

BUOC: St arting
0: No

[spacer]

Fig. 3-152, (p. 3-207)

BUOC: Active
0: No

[spacer]

040 093

036 014

Fig. 3-152, (p. 3-207)

BUOC: Ze ro-se qu. star ting


0: No

P437/EN M/R-11-A // P437311650

010 185

Fig. 3-152, (p. 3-207)

8-71

P437

8 Information and Control Functions

Parameter
Default

Switch on to fault
protection

Address
Min

Max

Unit

Logic Diagram

SOT F : Trigge r EXT

002 127

0: No
[spacer]

SOT F : Par. ARC r unning EX T

039 063

0: No
[spacer]

SOT F : Enab led


0: No

[spacer]

040 069

Fig. 3-154, (p. 3-210)

SOT F : Line d ead

006 147

0: No
[spacer]

SOT F : Active
0: No

[spacer]

Fig. 3-153, (p. 3-209)


001 187

Fig. 3-153, (p. 3-209)


006 129

Fig. 3-153, (p. 3-209)


001 188

Fig. 3-153, (p. 3-209)

SOT F : Trip s ignal


0: No

8-72

006 128

SOT F : tIN> elap se d


0: No

[spacer]

Fig. 3-154, (p. 3-210)

SOT F : tI> e laps ed


0: No

[spacer]

035 076

SOT F : Starting I N>


0: No

[spacer]

Fig. 3-154, (p. 3-210)

SOT F : Starting I >


0: No

[spacer]

036 063

SOT F : Z1 extended
0: No

[spacer]

Fig. 3-154, (p. 3-210)

SOT F : tManual-close runn.


0: No

[spacer]

006 146

036 064

Fig. 3-154, (p. 3-210)

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Protective signaling

Address
Min

Max

Unit

Logic Diagram

PSIG: Enab le EX T

037 025

2: Not configured
[spacer]

PSIG: Dis able EXT

037 026

2: Not configured
[spacer]

PSIG: Blocking E X T

036 049

0: No
[spacer]

PSIG: Tes t telecom. EXT

036 038

0: No
[spacer]

PSIG: Tes t telecom. 1 E X T

038 085

0: No
[spacer]

PSIG: Tes t telecom. 2 E X T

038 086

0: No
[spacer]

PSIG: Tes t telecom. 3 E X T

038 087

0: No
[spacer]

PSIG: Telec.fault y (A) EXT


0: No

[spacer]

Fig. 3-159, (p. 3-216)

PSIG: Telec.fault y (B) EXT


0: No

[spacer]

004 064

PSIG: Block. we ak inf. E XT

008 094

Fig. 3-159, (p. 3-216)


036 255

0: No
[spacer]

PSIG: Weak inf . t rigg. E XT

043 062

0: No
[spacer]

PSIG: Fre q. mon. tr ig. E XT

038 080

0: No
[spacer]

PSIG: Re ceive ( A) E XT

036 048

0: No
[spacer]

PSIG: Re ceive ( B ) EX T

006 037

0: No
[spacer]

PSIG: Chan. A1 r ece ive EX T

038 091

0: No
[spacer]

PSIG: Chan. A2 r ece ive EX T

038 092

0: No
[spacer]

PSIG: Chan. A3 r ece ive EX T

038 093

0: No
[spacer]

PSIG: Chan. B1 rec eiv e EXT

008 241

0: No
[spacer]

PSIG: Chan. B2 rec eiv e EXT

008 242

0: No

P437/EN M/R-11-A // P437311650

8-73

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

PSIG: Chan. B3 rec eiv e EXT

008 243

0: No
[spacer]

PSIG: Channe l 1 re cei ve


0: No

[spacer]

Fig. 3-156, (p. 3-213)


037 027

Fig. 3-156, (p. 3-213)


037 028

Fig. 3-156, (p. 3-213)


036 060

Fig. 3-159, (p. 3-216)


012 244

Fig. 3-159, (p. 3-216)

PSIG: Telecom . f aulty ( B)


0: No

[spacer]

015 008

PSIG: Telecom . f aulty ( A)


0: No

[spacer]

Fig. 3-156, (p. 3-213)

PSIG: Telecom . f aulty


0: No

[spacer]

037 023

PSIG: Not re ady


1: Yes

[spacer]

Fig. 3-158, (p. 3-215)

PSIG: Re ady
0: No

[spacer]

008 246

PSIG: Enab le d
0: No

[spacer]

Fig. 3-158, (p. 3-215)

PSIG: Ex t./us e r enable d


1: Yes

[spacer]

008 245

PSIG: Channe l 3 re cei ve


0: No

[spacer]

Fig. 3-158, (p. 3-215)

PSIG: Channe l 2 re cei ve


0: No

[spacer]

008 244

012 245

Fig. 3-159, (p. 3-216)

PSIG: Transie nt bloc king

037 255

0: No
[spacer]

PSIG: Tes t telecom. chann.


0: No

[spacer]

Fig. 3-184, (p. 3-239)


034 027

Fig. 3-184, (p. 3-239)

PSIG: Tes t telecom. ch. 3


0: No

[spacer]

034 026

PSIG: Tes t telecom. ch. 2


0: No

[spacer]

Fig. 3-184, (p. 3-239)

PSIG: Tes t telecom. ch. 1


0: No

[spacer]

034 016

034 028

Fig. 3-184, (p. 3-239)

PSIG: Se nd
0: No

012 243

Fig. 3-164, (p. 3-219)


Fig. 3-166, (p. 3-221)
Fig. 3-172, (p. 3-227)
Fig. 3-175, (p. 3-230)
Fig. 3-183, (p. 3-238)
Fig. 3-184, (p. 3-239)

8-74

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

PSIG: Se nd (s ignal)
0: No

036 035

Fig. 3-164, (p. 3-219)


Fig. 3-166, (p. 3-221)
Fig. 3-172, (p. 3-227)
Fig. 3-175, (p. 3-230)
Fig. 3-183, (p. 3-238)
Fig. 3-184, (p. 3-239)

[spacer]

PSIG: Channe l 1 se nd
0: No

038 081

Fig. 3-164, (p. 3-219)


Fig. 3-166, (p. 3-221)
Fig. 3-172, (p. 3-227)
Fig. 3-175, (p. 3-230)
Fig. 3-183, (p. 3-238)
Fig. 3-184, (p. 3-239)

[spacer]

PSIG: Channe l 2 se nd
0: No

038 082

Fig. 3-164, (p. 3-219)


Fig. 3-166, (p. 3-221)
Fig. 3-172, (p. 3-227)
Fig. 3-175, (p. 3-230)
Fig. 3-183, (p. 3-238)
Fig. 3-184, (p. 3-239)

[spacer]

PSIG: Channe l 3 se nd
0: No

038 083

Fig. 3-164, (p. 3-219)


Fig. 3-166, (p. 3-221)
Fig. 3-172, (p. 3-227)
Fig. 3-175, (p. 3-230)
Fig. 3-183, (p. 3-238)
Fig. 3-184, (p. 3-239)

[spacer]

PSIG: Re ceive
0: No

[spacer]

006 036

Fig. 3-158, (p. 3-215)

PSIG: Re ceive ( s ignal)


0: No

037 029

Fig. 3-165, (p. 3-220)


Fig. 3-167, (p. 3-222)
Fig. 3-170, (p. 3-224)
Fig. 3-173, (p. 3-228)
Fig. 3-176, (p. 3-231)

[spacer]

PSIG: Z1 ex te nde d
0: No

[spacer]

043 064

Fig. 3-182, (p. 3-236)

PSIG: Trip V<, A


0: No

[spacer]

Fig. 3-177, (p. 3-232)

PSIG: Weak inf ee d s tar t.


0: No

[spacer]

035 075

006 152

Fig. 3-182, (p. 3-236)

PSIG: Trip V<, B


0: No

P437/EN M/R-11-A // P437311650

006 153

Fig. 3-182, (p. 3-236)

8-75

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Min

Max

Unit

Logic Diagram

PSIG: Trip V<, C


0: No

[spacer]

Address

006 154

Fig. 3-182, (p. 3-236)

PSIG: Trip s ignal


0: No

038 007

Fig. 3-165, (p. 3-220)


Fig. 3-167, (p. 3-222)

8-76

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Auto-reclosing
control

Address
Min

Max

Unit

Logic Diagram

ARC: R ese t counte rs E X T

005 244

0: No
[spacer]

ARC: Enable EXT

037 010

2: Not configured
[spacer]

ARC: Disable EXT

037 011

2: Not configured
[spacer]

ARC: T est HS R A E XT

037 014

0: No
[spacer]

ARC: T est HS R B E XT

037 015

0: No
[spacer]

ARC: T est HS R C EXT

037 016

0: No
[spacer]

ARC: T est HS R A- B- C E X T

037 017

0: No
[spacer]

ARC: General s tarti ng EXT

037 096

0: No
[spacer]

ARC: Blocking E XT

036 050

0: No
[spacer]

ARC: C B d rive ready EX T

004 066

0: No
[spacer]

ARC: 1p- HS R enable EXT

000 108

0: No
[spacer]

ARC: 3p- HS R enable EXT

000 109

0: No
[spacer]

ARC: 3p- HS R(1p) enab. EXT

000 110

0: No
[spacer]

ARC: Enable e xt. ARC EX T

038 003

0: No
[spacer]

ARC: 3p trans fe r t r ip E X T

038 043

0: No
[spacer]

ARC: Ex t./us er enable d


1: Yes

[spacer]

Fig. 3-186, (p. 3-242)

ARC: Enable d
0: No

[spacer]

037 013

015 064

Fig. 3-186, (p. 3-242)

ARC: T est HS R A
0: No

P437/EN M/R-11-A // P437311650

034 020

Fig. 3-196, (p. 3-257)

8-77

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Fig. 3-196, (p. 3-257)


034 022

Fig. 3-196, (p. 3-257)


034 023

Fig. 3-196, (p. 3-257)

ARC: Blocke d
0: No

[spacer]

034 021

ARC: T est HS R A-B- C


0: No

[spacer]

Logic Diagram

ARC: T est HS R C
0: No

[spacer]

Unit

ARC: T est HS R B
0: No

[spacer]

Max

004 069

Fig. 3-188, (p. 3-244)

ARC: S tart by LOGIC

037 078

0: No
[spacer]

ARC: R eady
0: No

[spacer]

Fig. 3-204, (p. 3-271)


037 002

Fig. 3-204, (p. 3-271)


037 066

Fig. 3-204, (p. 3-271)


037 067

Fig. 3-204, (p. 3-271)


037 069

Fig. 3-204, (p. 3-271)


039 087

Fig. 3-204, (p. 3-271)


037 003

Fig. 3-204, (p. 3-271)

ARC: R eclaim time running


0: No

8-78

037 065

ARC: Dead tim e TDR r unn.


0: No

[spacer]

Fig. 3-204, (p. 3-271)

ARC: t Discrim running


0: No

[spacer]

037 005

ARC: M ax . d ead time runn.


0: No

[spacer]

Fig. 3-204, (p. 3-271)

ARC: Dead tim e 3p running


0: No

[spacer]

037 000

ARC: Dead tim e 1p running


0: No

[spacer]

Fig. 3-188, (p. 3-244)

ARC: Dead tim e running


0: No

[spacer]

037 004

ARC: Op er. tim e 2 running


0: No

[spacer]

Fig. 3-196, (p. 3-257)

ARC: Op er. tim e 1 running


0: No

[spacer]

036 055

ARC: C ycle running


0: No

[spacer]

Fig. 3-187, (p. 3-243)

ARC: Block. tim e running


0: No

[spacer]

037 008

ARC: R eject tes t HS R


0: No

[spacer]

Fig. 3-187, (p. 3-243)

ARC: Not ready


1: Yes

[spacer]

004 068

036 042

Fig. 3-204, (p. 3-271)

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Unit

Logic Diagram

ARC: ( Re)close r e que st


0: No

[spacer]

Max

037 077

Fig. 3-204, (p. 3-271)

ARC: ( Re)close s ignal HSR


0: No

037 007

Fig. 3-170, (p. 3-224)


Fig. 3-173, (p. 3-228)
Fig. 3-176, (p. 3-231)
Fig. 3-204, (p. 3-271)

[spacer]

ARC: ( Re)close s ignal TD R


0: No

[spacer]

Fig. 3-204, (p. 3-271)


036 040

Fig. 3-204, (p. 3-271)

ARC: Ex t. 1p t rip pe rm.


0: No

[spacer]

036 062

ARC: S ig.inte rr. CB tr ip


0: No

[spacer]

Fig. 3-204, (p. 3-271)

ARC: R eclosure s uc ce ss ful


0: No

[spacer]

037 006

039 086

Fig. 3-203, (p. 3-270)

ARC: 3p final tr ip
0: No

P437/EN M/R-11-A // P437311650

036 043

Fig. 3-204, (p. 3-271)

8-79

P437

8 Information and Control Functions

Parameter
Default

Automatic
synchronism check

Address
Min

Max

Unit

Logic Diagram

ASC: R es et counter s E XT

006 074

0: No
[spacer]

ASC: Enab le EXT

037 049

2: Not configured
[spacer]

ASC: Disable EXT

037 061

2: Not configured
[spacer]

ASC: Blocking EXT

037 048

0: No
[spacer]

ASC: Te s t AR clos e r . E XT

000 106

0: No
[spacer]

Close request via external signal for a test triggering of the ASC in operating
mode automatic reclosure.

[spacer]

ASC: Te s t M C close r. EXT

037 064

0: No
[spacer]

Close request via external signal for a test triggering of the ASC in operating
mode manual reclosure.

[spacer]

ASC: Enab l.close re qu.E X T

037 063

1: Yes
[spacer]

ASC: MC Close r eques t EXT

037 062

0: No
[spacer]

Close request via external signal for a triggering of the ASC in operating mode
manual reclosure.

[spacer]

ASC: AR close re que st E X T

008 236

0: No
[spacer]

Close request via external signal for a triggering of the ASC in operating mode
automatic reclosure.

[spacer]

ASC: Ext./us e r enabled


1: Yes

[spacer]

038 018

Fig. 3-208, (p. 3-275)


037 079

Fig. 3-208, (p. 3-275)

ASC: Not re ady


1: Yes

8-80

Fig. 3-207, (p. 3-274)

ASC: R eady
0: No

[spacer]

018 024

ASC: Blocked
0: No

[spacer]

Fig. 3-207, (p. 3-274)

ASC: Enab le d
0: No

[spacer]

037 092

037 082

Fig. 3-208, (p. 3-275)

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

ASC: Te s t AR clos e r equ.


0: No

008 240

Fig. 3-210, (p. 3-277)

[spacer]

Signaling of a close request for a test triggering of the ASC in operating mode
automatic reclosure.

[spacer]

ASC: Te s t M C clos e re qu.


0: No

034 019

Fig. 3-209, (p. 3-276)

[spacer]

Signaling of a close request for a test triggering of the ASC in operating mode
manual reclosure.

[spacer]

ASC: AR close re que st


0: No

008 239

Fig. 3-210, (p. 3-277)

[spacer]

Signaling of a close request for a triggering of the ASC in operating mode


automatic reclosure.

[spacer]

ASC: MC Close r eques t


0: No

034 018

Fig. 3-209, (p. 3-276)

[spacer]

Signaling of a close request for a triggering of the ASC in operating mode


manual reclosure.

[spacer]

ASC: Cycle running


0: No

[spacer]

Fig. 3-217, (p. 3-287)

ASC: Op erat.t ime running


0: No

[spacer]

038 019

037 093

Fig. 3-217, (p. 3-287)

ASC: Clos e e nable


0: No

037 083

Fig. 3-213, (p. 3-282)


Fig. 3-214, (p. 3-283)

[spacer]

ASC: Clos e e nable,vol t.ch


0: No

037 085

Fig. 3-213, (p. 3-282)


Fig. 3-214, (p. 3-283)

[spacer]

ASC: Clos e e nable,sy nc. ch


0: No

037 084

Fig. 3-215, (p. 3-285)


Fig. 3-216, (p. 3-286)

[spacer]

ASC: Clos e re je ct ion


0: No

P437/EN M/R-11-A // P437311650

037 086

Fig. 3-217, (p. 3-287)

8-81

P437

8 Information and Control Functions

Parameter
Default

Ground fault (shortcircuit) protection

Address
Min

Max

Unit

Logic Diagram

GFS C: Enable EXT

039 095

2: Not configured
[spacer]

GFS C: Dis able EXT

039 096

2: Not configured
[spacer]

GFS C: Blocking EXT

043 068

0: No
[spacer]

GFS C: Ex t. enabled
1: Yes

[spacer]

039 089

Fig. 3-223, (p. 3-294)


038 096

Fig. 3-223, (p. 3-294)


039 090

Fig. 3-235, (p. 3-307)


039 091

Fig. 3-235, (p. 3-307)


038 097

Fig. 3-235, (p. 3-307)


038 098

Fig. 3-235, (p. 3-307)


038 099

Fig. 3-235, (p. 3-307)

GFS C: Trip s ignal


0: No

8-82

Fig. 3-223, (p. 3-294)

GFS C: t3 elaps ed
0: No

[spacer]

043 061

GFS C: t2 elaps ed
0: No

[spacer]

Fig. 3-223, (p. 3-294)

GFS C: t1 elaps ed
0: No

[spacer]

039 088

GFS C: Fault backward / B S


0: No

[spacer]

Fig. 3-237, (p. 3-308)

GFS C: Fault forward / LS


0: No

[spacer]

038 095

GFS C: St arting
0: No

[spacer]

Fig. 3-220, (p. 3-291)

GFS C: VNG> trigge r ed


0: No

[spacer]

039 094

GFS C: Direct.d et erm. e nabl .


0: No

[spacer]

Fig. 3-220, (p. 3-291)

GFS C: IN> t riggered


0: No

[spacer]

039 093

GFS C: Monit or. tr iggere d


0: No

[spacer]

Fig. 3-220, (p. 3-291)

GFS C: Not re ady


1: Yes

[spacer]

038 094

GFS C: Re ady
0: No

[spacer]

Fig. 3-220, (p. 3-291)

GFS C: Enable d
0: No

[spacer]

039 097

039 092

Fig. 3-235, (p. 3-307)

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Ground fault (shortcircuit) protection


signaling

Address
Min

Max

Unit

Logic Diagram

GSCSG: Enable E XT

043 050

2: Not configured
[spacer]

GSCSG: Disab le EXT

043 051

2: Not configured
[spacer]

GSCSG: Blocking E X T

043 052

0: No
[spacer]

GSCSG: T elecom. fault y EXT

043 053

0: No
[spacer]

GSCSG: Frequ.mon.trigd. E X T

043 054

0: No
[spacer]

GSCSG: R eceive EXT

043 055

0: No
[spacer]

GSCSG: T es t tele com. EX T

043 056

0: No
[spacer]

GSCSG: Enable d
0: No

[spacer]

Fig. 3-239, (p. 3-313)


043 058

Fig. 3-239, (p. 3-313)


034 029

Fig. 3-248, (p. 3-322)

GSCSG: T elecom. fault y


0: No

[spacer]

043 057

GSCSG: T es t tele com. chann.


0: No

[spacer]

Fig. 3-238, (p. 3-310)

GSCSG: Not ready


1: Yes

[spacer]

043 066

GSCSG: R eady
0: No

[spacer]

Fig. 3-238, (p. 3-310)

GSCSG: Ex t. enabled
1: Yes

[spacer]

023 070

046 060

Fig. 3-239, (p. 3-313)

GSCSG: S end s i gnal


0: No

043 059

Fig. 3-243, (p. 3-317)


Fig. 3-244, (p. 3-318)
Fig. 3-247, (p. 3-321)
Fig. 3-248, (p. 3-322)

[spacer]

GSCSG: T rip s ignal


0: No

043 060

Fig. 3-243, (p. 3-317)


Fig. 3-244, (p. 3-318)
Fig. 3-245, (p. 3-319)

[spacer]

GSCSG: T rip ping t ime e laps .


0: No

P437/EN M/R-11-A // P437311650

043 063

Fig. 3-240, (p. 3-314)

8-83

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

GSCSG: T rans ient block ing

Max

Unit

Logic Diagram
037 254

0: No

8-84

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Definite-time over
current protection

Address
Min

Max

Unit

Logic Diagram

DTOC: Block. dir. tIN> EX T

002 176

0: No
[spacer]

DTOC: Blck. dir. tIN>> EX T

002 177

0: No
[spacer]

DTOC: Blk. dir. t IN>>> E XT

002 178

0: No
[spacer]

DTOC: Bl. d ir. tIN>>>> EXT

002 179

0: No
[spacer]

DTOC: Blocking t I> EX T

041 060

0: No
[spacer]

DTOC: Blocking t I>> EX T

041 061

0: No
[spacer]

DTOC: Blocking t I>> > EX T

041 062

0: No
[spacer]

DTOC: Blocking t I>> >> E X T

041 100

0: No
[spacer]

DTOC: Blocking t Ine g> EXT

041 102

0: No
[spacer]

DTOC: Blocking t Ine g>> EXT

041 103

0: No
[spacer]

DTOC: Block. tIne g>>> EX T

041 104

0: No
[spacer]

DTOC: Block. tIne g>>>> EX T

041 105

0: No
[spacer]

DTOC: Blocking t IN> EX T

041 063

0: No
[spacer]

DTOC: Blocking t IN> > EX T

041 064

0: No
[spacer]

DTOC: Blocking t IN> >> EX T

041 065

0: No
[spacer]

DTOC: Blocking t IN> >>> E X T

041 101

0: No
[spacer]

DTOC: Enabled
0: No

[spacer]

040 120

Fig. 3-249, (p. 3-323)

DTOC: St arting I>


0: No

P437/EN M/R-11-A // P437311650

035 020

Fig. 3-250, (p. 3-324)

8-85

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

040 011

Fig. 3-250, (p. 3-324)


040 012

Fig. 3-250, (p. 3-324)


035 032

Fig. 3-250, (p. 3-324)


035 024

Fig. 3-251, (p. 3-326)


035 025

Fig. 3-251, (p. 3-326)


035 026

Fig. 3-251, (p. 3-326)

DTOC: St arting I neg>>>>


0: No

[spacer]

Fig. 3-250, (p. 3-324)

DTOC: St arting I neg>>>


0: No

[spacer]

040 010

DTOC: St arting I neg>>


0: No

[spacer]

Fig. 3-250, (p. 3-324)

DTOC: St arting I neg>


0: No

[spacer]

035 023

DTOC: tI>>>> elapse d


0: No

[spacer]

Fig. 3-250, (p. 3-324)

DTOC: tI>>> elapse d


0: No

[spacer]

035 022

DTOC: tI>> elap se d


0: No

[spacer]

Fig. 3-250, (p. 3-324)

DTOC: tI> e lap sed


0: No

[spacer]

035 021

DTOC: St arting I >>>>


0: No

[spacer]

Logic Diagram

DTOC: St arting I >>>


0: No

[spacer]

Unit

DTOC: St arting I >>


0: No

[spacer]

Max

035 027

Fig. 3-251, (p. 3-326)

DTOC: tIneg > e laps ed


0: No

035 033

Fig. 3-251, (p. 3-326)


Fig. 3-257, (p. 3-332)

[spacer]

DTOC: tIneg >> elaps ed


0: No

[spacer]

Fig. 3-251, (p. 3-326)


035 028

Fig. 3-253, (p. 3-328)


035 029

Fig. 3-253, (p. 3-328)

DTOC: St arting I N>>>


0: No

8-86

035 036

DTOC: St arting I N>>


0: No

[spacer]

Fig. 3-251, (p. 3-326)

DTOC: St arting I N>


0: No

[spacer]

035 035

DTOC: tIneg >>>> e laps ed


0: No

[spacer]

Fig. 3-251, (p. 3-326)

DTOC: tIneg >>> elaps ed


0: No

[spacer]

035 034

035 030

Fig. 3-253, (p. 3-328)

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Fig. 3-253, (p. 3-328)


035 047

Fig. 3-255, (p. 3-329)

DTOC: Fault N back ward


0: No

[spacer]

035 031

DTOC: Fault N forward


0: No

[spacer]

Logic Diagram

DTOC: St arting IN>>>>


0: No

[spacer]

Unit

035 048

Fig. 3-255, (p. 3-329)

DTOC: tIN> e lapse d


0: No

035 037

Fig. 3-253, (p. 3-328)


Fig. 3-258, (p. 3-333)
Fig. 3-259, (p. 3-334)

[spacer]

DTOC: tIN>> elapse d


0: No

[spacer]

035 039

Fig. 3-253, (p. 3-328)

DTOC: tIN>>>> elapse d


0: No

[spacer]

Fig. 3-253, (p. 3-328)

DTOC: tIN>>> elapse d


0: No

[spacer]

035 038

035 040

Fig. 3-253, (p. 3-328)

DTOC: Tr ip s ignal tIN>


0: No

035 043

Fig. 3-256, (p. 3-330)


Fig. 3-258, (p. 3-333)
Fig. 3-259, (p. 3-334)

[spacer]

DTOC: Tr ip s ignal tIN>>


0: No

[spacer]

035 046

Fig. 3-256, (p. 3-330)


040 086

Fig. 3-260, (p. 3-335)

DTOC: tIN>,inte rm. e laps ed


0: No

[spacer]

Fig. 3-256, (p. 3-330)

DTOC: H.-time tIN>,i . runn


0: No

[spacer]

035 045

DTOC: Tr ip s ign. t IN>>>>


0: No

[spacer]

Fig. 3-256, (p. 3-330)

DTOC: Tr ip s ignal tIN>>>


0: No

[spacer]

035 044

040 099

Fig. 3-260, (p. 3-335)

DTOC: Tr ip s ig. t IN>, int m.


0: No

P437/EN M/R-11-A // P437311650

039 073

Fig. 3-260, (p. 3-335)

8-87

P437

8 Information and Control Functions

Parameter
Default

Address
Min

Max

Unit

Logic Diagram

Inverse-time overcur IDMT: B lock. tIr e f,P > EX T


rent protection

040 101

0: No
[spacer]

IDMT: B lock. tIr e f,neg>EX T

040 102

0: No
[spacer]

IDMT: B lock. tIr e f,N> EXT

040 103

0: No
[spacer]

IDMT: E nabled
0: No

[spacer]

040 109

Fig. 3-270, (p. 3-347)


040 113

Fig. 3-270, (p. 3-347)


040 111

Fig. 3-270, (p. 3-347)


040 081

Fig. 3-272, (p. 3-349)


040 083

Fig. 3-272, (p. 3-349)


040 054

Fig. 3-272, (p. 3-349)

IDMT: M em ory N clear


1: Yes

8-88

Fig. 3-270, (p. 3-347)

IDMT: Hold t ime N r unning


0: No

[spacer]

040 107

IDMT: t I re f,N> elaps ed


0: No

[spacer]

Fig. 3-269, (p. 3-345)

IDMT: S tar t ing Ir e f,N>


0: No

[spacer]

040 110

IDMT: M em ory neg cle ar


1: Yes

[spacer]

Fig. 3-269, (p. 3-345)

IDMT: Hold t ime neg r unn.


0: No

[spacer]

040 053

IDMT: t I re f,neg> elaps e d


0: No

[spacer]

Fig. 3-269, (p. 3-345)

IDMT: S tar t ing Ir e f,ne g>


0: No

[spacer]

040 082

IDMT: M em ory P cl ear


1: Yes

[spacer]

Fig. 3-269, (p. 3-345)

IDMT: Hold t ime P runni ng


0: No

[spacer]

040 080

IDMT: t I re f,P> elaps e d


0: No

[spacer]

Fig. 3-263, (p. 3-338)

IDMT: S tar t ing Ir e f,P>


0: No

[spacer]

040 100

040 112

Fig. 3-272, (p. 3-349)

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Thermal overload
protection

Address
Min

Max

Unit

Logic Diagram

THER M : B lock re plica EXT

041 074

0: No
[spacer]

THER M : R e s et re pli ca E XT

038 061

0: No
[spacer]

THER M : CTA e rror EX T

038 062

0: No
[spacer]

THER M : Enable d
0: No

[spacer]

040 068

Fig. 3-274, (p. 3-351)

THER M : Not r eady

040 035

1: Yes
[spacer]

THER M : R e s et re pli ca
0: No

[spacer]

039 025

Fig. 3-277, (p. 3-357)


041 109

Fig. 3-277, (p. 3-357)

THER M : Tr ip s ignal
0: No

[spacer]

Fig. 3-277, (p. 3-357)

THER M : Within pre-t rip t ime


1: Yes

[spacer]

041 108

THER M : Warning
0: No

[spacer]

Fig. 3-278, (p. 3-358)

THER M : S tar t in g k*Ire f>


0: No

[spacer]

039 061

039 020

Fig. 3-277, (p. 3-357)

THER M : R e clos ur e block e d

039 024

0: No
[spacer]

THER M : B uf fer empty


1: Yes

[spacer]

Fig. 3-277, (p. 3-357)

THER M : CTA e rror


0: No

[spacer]

039 112

039 111

Fig. 3-275, (p. 3-353)

THER M : S et ting e rror,bl ock .


0: No

P437/EN M/R-11-A // P437311650

039 110

Fig. 3-277, (p. 3-357)

8-89

P437

8 Information and Control Functions

Parameter
Default

Address
Min

Max

Time-voltage protec V<>: Blocking tV> E XT


tion

Unit

Logic Diagram
041 068

0: No
[spacer]

V<>: Blocking tV>> E XT

041 069

0: No
[spacer]

V<>: Blocking tV>>> E XT

010 246

0: No
[spacer]

V<>: Blocking tV< E XT

041 070

0: No
[spacer]

V<>: Blocking tV<< E XT

041 071

0: No
[spacer]

V<>: Blocking tV<<< E XT

010 247

0: No
[spacer]

V<>: Blocking tVpos> EXT

041 090

0: No
[spacer]

V<>: Blocking tVpos>> EXT

041 091

0: No
[spacer]

V<>: Blocking tVpos< EXT

041 092

0: No
[spacer]

V<>: Blocking tVpos<< EXT

041 093

0: No
[spacer]

V<>: Blocking tVne g> EX T

041 094

0: No
[spacer]

V<>: Blocking tVne g>> EX T

041 095

0: No
[spacer]

V<>: Blocking tVNG > EX T

041 072

0: No
[spacer]

V<>: Blocking tVNG >> EX T

041 073

0: No
[spacer]

V<>: Blocking tVre f> EX T

007 036

0: No
[spacer]

V<>: Blocking tVre f>> EX T

007 037

0: No
[spacer]

V<>: Block. tVref>>> E XT

010 248

0: No
[spacer]

V<>: Blocking tVre f< EX T

007 039

0: No

8-90

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

V<>: Blocking tVre f<< EX T

007 046

0: No
[spacer]

V<>: Block. tVre f<<< E XT

010 249

0: No
[spacer]

V<>: Enable d
0: No

[spacer]

Fig. 3-282, (p. 3-362)


041 032

Fig. 3-282, (p. 3-362)


041 033

Fig. 3-282, (p. 3-362)


041 030

Fig. 3-282, (p. 3-362)

V<>: Starting V>>


0: No

[spacer]

041 031

V<>: Starting V>


0: No

[spacer]

Fig. 3-279, (p. 3-359)

V<>: Starting V>/ >> C( -A)


0: No

[spacer]

042 004

V<>: Starting V>/ >> B(-C )


0: No

[spacer]

Fig. 3-279, (p. 3-359)

V<>: Starting V>/ >> A(-B)


0: No

[spacer]

042 003

V<>: Not ready


1: Yes

[spacer]

Fig. 3-279, (p. 3-359)

V<>: Ready
0: No

[spacer]

040 066

041 096

Fig. 3-282, (p. 3-362)

V<>: Starting V>>>


0: No

010 231

Fig. 3-282, (p. 3-362)


Fig. 3-283, (p. 3-363)

[spacer]

V<>: Starting V> 3-pol e


0: No

[spacer]

041 097

Fig. 3-282, (p. 3-362)

V<>: Starting V>> 3 -pole

010 226

0: No
[spacer]

V<>: Starting V>>> 3 -pole


0: No

[spacer]

Fig. 3-282, (p. 3-362)


041 035

Fig. 3-282, (p. 3-362)

V<>: tV>>> elapse d


0: No

[spacer]

041 034

V<>: tV>> elapse d


0: No

[spacer]

Fig. 3-283, (p. 3-363)

V<>: tV> elaps e d


0: No

[spacer]

010 232

010 233

Fig. 3-283, (p. 3-363)

V<>: tV> 3-pole elaps e d


0: No

P437/EN M/R-11-A // P437311650

041 098

Fig. 3-282, (p. 3-362)

8-91

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

V<>: tV>> 3- pole e laps e d


0: No

010 227

Fig. 3-282, (p. 3-362)


Fig. 3-284, (p. 3-364)

[spacer]

V<>: tV>>> 3- pole e laps ed


0: No

[spacer]

010 235

Fig. 3-285, (p. 3-365)


042 005

Fig. 3-284, (p. 3-364)


010 228

Fig. 3-284, (p. 3-364)


010 236

Fig. 3-285, (p. 3-365)


041 041

Fig. 3-284, (p. 3-364)


041 042

Fig. 3-284, (p. 3-364)

V<>: tV<<< elap se d


0: No

[spacer]

Fig. 3-284, (p. 3-364)

V<>: tV<< elap se d


0: No

[spacer]

041 099

V<>: tV< elaps e d


0: No

[spacer]

Fig. 3-284, (p. 3-364)

V<>: Starting V<<< 3 -pole


0: No

[spacer]

041 037

V<>: Starting V<< 3 -pole


0: No

[spacer]

Fig. 3-284, (p. 3-364)

V<>: Starting V< 3-pol e


0: No

[spacer]

041 040

V<>: Starting V<<<


0: No

[spacer]

Fig. 3-284, (p. 3-364)

V<>: Starting V<<


0: No

[spacer]

041 039

V<>: Starting V<


0: No

[spacer]

Fig. 3-284, (p. 3-364)

V<>: Starting V</ << C( -A)


0: No

[spacer]

041 038

V<>: Starting V</ << B(-C )


0: No

[spacer]

Fig. 3-283, (p. 3-363)

V<>: Starting V</ << A(-B)


0: No

[spacer]

010 234

010 237

Fig. 3-285, (p. 3-365)

V<>: tV< elaps . transient


0: No

042 023

Fig. 3-284, (p. 3-364)


Fig. 3-285, (p. 3-365)

[spacer]

V<>: tV<< elap se d t rans .


0: No

042 025

Fig. 3-284, (p. 3-364)


Fig. 3-285, (p. 3-365)

[spacer]

V<>: tV<<< elap s.transien


0: No

[spacer]

Fig. 3-285, (p. 3-365)

V<>: tV</ <</<<< el .t rans


0: No

8-92

010 238

042 007

Fig. 3-285, (p. 3-365)

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Logic Diagram

V<>: tV< 3-pole elaps e d


0: No

[spacer]

Unit

042 006

Fig. 3-284, (p. 3-364)

V<>: tV<< 3- pole e laps e d

010 229

0: No
[spacer]

V<>: tV<<< 3- pole e laps ed


0: No

[spacer]

010 239

Fig. 3-285, (p. 3-365)

V<>: tV< 3p elaps . tr ans.


0: No

042 024

Fig. 3-284, (p. 3-364)


Fig. 3-285, (p. 3-365)

[spacer]

V<>: tV<< 3p e laps . tr ans


0: No

010 230

Fig. 3-284, (p. 3-364)


Fig. 3-285, (p. 3-365)

[spacer]

V<>: tV<<< 3p e laps .t rans


0: No

[spacer]

Fig. 3-284, (p. 3-364)


011 133

Fig. 3-285, (p. 3-365)


042 010

Fig. 3-287, (p. 3-368)


042 011

Fig. 3-287, (p. 3-368)


042 012

Fig. 3-287, (p. 3-368)


042 013

Fig. 3-287, (p. 3-368)

V<>: Starting Vpos <


0: No

[spacer]

011 132

V<>: tVp os>> elaps ed


0: No

[spacer]

Fig. 3-284, (p. 3-364)

V<>: tVp os> elaps ed


0: No

[spacer]

041 111

V<>: Starting Vpos >>


0: No

[spacer]

Fig. 3-285, (p. 3-365)

V<>: Starting Vpos >


0: No

[spacer]

011 134

V<>: Fault V<<< 3 -pol e


0: No

[spacer]

Fig. 3-284, (p. 3-364)

V<>: Fault V<< 3 -pol e


0: No

[spacer]

041 112

V<>: Fault V< 3 -pol e


0: No

[spacer]

Fig. 3-284, (p. 3-364)

V<>: Fault V<<<


0: No

[spacer]

041 110

V<>: Fault V<<


0: No

[spacer]

Fig. 3-285, (p. 3-365)

V<>: Fault V<


0: No

[spacer]

010 240

042 014

Fig. 3-287, (p. 3-368)

V<>: Starting Vpos <<


0: No

P437/EN M/R-11-A // P437311650

042 015

Fig. 3-287, (p. 3-368)

8-93

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

042 020

Fig. 3-288, (p. 3-369)


042 021

Fig. 3-288, (p. 3-369)


042 022

Fig. 3-288, (p. 3-369)


041 044

Fig. 3-290, (p. 3-370)


042 008

Fig. 3-290, (p. 3-370)


041 045

Fig. 3-290, (p. 3-370)


041 046

Fig. 3-290, (p. 3-370)


007 051

Fig. 3-291, (p. 3-371)


007 052

Fig. 3-291, (p. 3-371)


010 241

Fig. 3-291, (p. 3-371)

V<>: tVref> elap se d


0: No

8-94

Fig. 3-288, (p. 3-369)

V<>: Starting Vref>>>


0: No

[spacer]

042 019

V<>: Starting Vref>>


0: No

[spacer]

Fig. 3-287, (p. 3-368)

V<>: Starting Vref>


0: No

[spacer]

041 114

V<>: tVNG>> e lapse d


0: No

[spacer]

Fig. 3-287, (p. 3-368)

V<>: tVNG> e lapse d


0: No

[spacer]

041 113

V<>: Starting VNG>>


0: No

[spacer]

Fig. 3-287, (p. 3-368)

V<>: Starting VNG>


0: No

[spacer]

042 018

V<>: tVneg>> elapse d


0: No

[spacer]

Fig. 3-287, (p. 3-368)

V<>: tVneg> elaps e d


0: No

[spacer]

042 027

V<>: Starting Vne g>>


0: No

[spacer]

Fig. 3-287, (p. 3-368)

V<>: Starting Vne g>


0: No

[spacer]

042 017

V<>: Fault Vpos<<


0: No

[spacer]

Fig. 3-287, (p. 3-368)

V<>: Fault Vpos<


0: No

[spacer]

042 026

V<>: tVp os</<< e lap.t r ans


0: No

[spacer]

Fig. 3-287, (p. 3-368)

V<>: tVp os<< elaps .t r ans .


0: No

[spacer]

042 016

V<>: tVp os<< elaps ed


0: No

[spacer]

Logic Diagram

V<>: tVp os< elaps . t rans.


0: No

[spacer]

Unit

V<>: tVp os< elaps ed


0: No

[spacer]

Max

007 047

Fig. 3-291, (p. 3-371)

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

007 055

Fig. 3-292, (p. 3-372)


007 056

Fig. 3-292, (p. 3-372)


010 243

Fig. 3-292, (p. 3-372)


007 053

Fig. 3-292, (p. 3-372)

V<>: tVref<< elapse d


0: No

[spacer]

Fig. 3-291, (p. 3-371)

V<>: tVref< elapse d


0: No

[spacer]

010 242

V<>: Starting Vref<<<


0: No

[spacer]

Fig. 3-291, (p. 3-371)

V<>: Starting Vref<<


0: No

[spacer]

007 048

V<>: Starting Vref<


0: No

[spacer]

Logic Diagram

V<>: tVref>>> elapse d


0: No

[spacer]

Unit

V<>: tVref>> elapse d


0: No

[spacer]

Max

007 054

Fig. 3-292, (p. 3-372)

V<>: tVref<<< elapse d

010 244

0: No
[spacer]

V<>: tVref< elaps. trans.


0: No

[spacer]

Fig. 3-292, (p. 3-372)


007 063

Fig. 3-292, (p. 3-372)


007 061

Fig. 3-292, (p. 3-372)

V<>: Fault Vr ef<<


0: No

[spacer]

010 245

V<>: Fault Vr ef<


0: No

[spacer]

Fig. 3-292, (p. 3-372)

V<>: tVref</<</ <<< e l.t r.


0: No

[spacer]

007 060

V<>: tVref<<< elaps.tr ans


0: No

[spacer]

Fig. 3-292, (p. 3-372)

V<>: tVref<< elaps.tr ans.


0: No

[spacer]

007 057

007 062

Fig. 3-292, (p. 3-372)

V<>: Fault Vr ef<<<


0: No

P437/EN M/R-11-A // P437311650

011 135

Fig. 3-292, (p. 3-372)

8-95

P437

8 Information and Control Functions

Parameter
Default

Address
Min

Max

Unit

Logic Diagram

f<> : R es e t me as. vals EXT


Over-/
underfrequency pro
tection

006 075

0: No
[spacer]

f<> : Blocking f1 E XT

042 103

0: No
[spacer]

f<> : Blocking f2 E XT

042 104

0: No
[spacer]

f<> : Blocking f3 E XT

042 105

0: No
[spacer]

f<> : Blocking f4 E XT

042 106

0: No
[spacer]

f<> : Enable d
0: No

[spacer]

042 107

Fig. 3-297, (p. 3-378)


042 108

Fig. 3-297, (p. 3-378)


042 109

Fig. 3-297, (p. 3-378)


042 110

Fig. 3-297, (p. 3-378)

f<> : Trip signal f1


0: No

[spacer]

Fig. 3-295, (p. 3-375)

f<> : De lta t1 e laps ed


0: No

[spacer]

042 102

f<> : De lta f1 t rigge red


0: No

[spacer]

Fig. 3-293, (p. 3-373)

f<> : S tarting f1/df1


0: No

[spacer]

042 140

f<> : S tarting f1
0: No

[spacer]

Fig. 3-293, (p. 3-373)

f<> : Blocked b y V<


0: No

[spacer]

042 101

f<> : Not ready


0: No

[spacer]

Fig. 3-293, (p. 3-373)

f<> : R ead y
0: No

[spacer]

042 100

f<> : S tarting f2

042 111

Fig. 3-297, (p. 3-378)


042 115

0: No
[spacer]

f<> : S tarting f2/df2

042 116

0: No
[spacer]

f<> : De lta f2 t rigge red

042 117

0: No
[spacer]

f<> : De lta t2 e laps ed

042 118

0: No

8-96

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

f<> : Trip signal f2

Max

Unit

Logic Diagram
042 119

0: No
[spacer]

f<> : S tarting f3

042 123

0: No
[spacer]

f<> : S tarting f3 /df3

042 124

0: No
[spacer]

f<> : De lta f3 t ri gge red

042 125

0: No
[spacer]

f<> : De lta t3 e laps ed

042 126

0: No
[spacer]

f<> : Trip signal f3

042 127

0: No
[spacer]

f<> : S tarting f4

042 131

0: No
[spacer]

f<> : S tarting f4 /df4

042 132

0: No
[spacer]

f<> : De lta f4 t ri gge red

042 133

0: No
[spacer]

f<> : De lta t4 e laps ed

042 134

0: No
[spacer]

f<> : Trip signal f4

042 135

0: No

P437/EN M/R-11-A // P437311650

8-97

P437

8 Information and Control Functions

Parameter
Default

Power directional
protection

Address
Min

Max

Unit

Logic Diagram

P<>: Blocking tP> EX T

035 082

0: No
[spacer]

P<>: Blocking tP>> EX T

035 083

0: No
[spacer]

P<>: Blocking tQ> EXT

035 084

0: No
[spacer]

P<>: Blocking tQ>> EXT

035 085

0: No
[spacer]

P<>: Blocking tP< EX T

035 050

0: No
[spacer]

P<>: Blocking tP<< EX T

035 051

0: No
[spacer]

P<>: Blocking tQ< EXT

035 052

0: No
[spacer]

P<>: Blocking tQ<< EXT

035 053

0: No
[spacer]

P<>: Enabled
0: No

[spacer]

Fig. 3-300, (p. 3-382)


035 088

Fig. 3-301, (p. 3-383)


035 091

Fig. 3-301, (p. 3-383)


035 092

Fig. 3-302, (p. 3-384)


035 095

Fig. 3-302, (p. 3-384)

P<>: S ignal Q> d elay ed


0: No

8-98

035 090

P<>: S tarting Q>>


0: No

[spacer]

Fig. 3-300, (p. 3-382)

P<>: S tarting Q>


0: No

[spacer]

035 087

P<>: T rip s ignal P>>


0: No

[spacer]

Fig. 3-300, (p. 3-382)

P<>: T rip s ignal P>


0: No

[spacer]

035 089

P<>: S ignal P>> de laye d


0: No

[spacer]

Fig. 3-300, (p. 3-382)

P<>: S ignal P> de lay e d


0: No

[spacer]

035 086

P<>: S tarting P>>


0: No

[spacer]

Fig. 3-298, (p. 3-380)

P<>: S tarting P>


0: No

[spacer]

036 250

035 093

Fig. 3-302, (p. 3-384)

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Fig. 3-304, (p. 3-387)


035 062

Fig. 3-304, (p. 3-387)


035 178

Fig. 3-304, (p. 3-387)


035 057

Fig. 3-304, (p. 3-387)


035 063

Fig. 3-304, (p. 3-387)


035 058

Fig. 3-305, (p. 3-389)


035 064

Fig. 3-305, (p. 3-389)


035 059

Fig. 3-305, (p. 3-389)


035 065

Fig. 3-305, (p. 3-389)


035 066

Fig. 3-307, (p. 3-391)

P<>: S tarting Q<<


0: No

[spacer]

035 056

P<>: S tarting Q<


0: No

[spacer]

Fig. 3-304, (p. 3-387)

P<>: T rip s ig. P<< tr ans .


0: No

[spacer]

035 061

P<>: T rip s ignal P< trans


0: No

[spacer]

Fig. 3-304, (p. 3-387)

P<>: T rip s ignal P<<


0: No

[spacer]

035 055

P<>: T rip s ignal P<


0: No

[spacer]

Fig. 3-304, (p. 3-387)

P<>: Fault P<<


0: No

[spacer]

035 060

P<>: Fault P<


0: No

[spacer]

Fig. 3-304, (p. 3-387)

P<>: t P</tP<< el aps.tr ans


0: No

[spacer]

035 054

P<>: t P<< elapse d trans.


0: No

[spacer]

Fig. 3-303, (p. 3-385)

P<>: t P< elaps e d trans.


0: No

[spacer]

035 097

P<>: S ignal P<< de laye d


0: No

[spacer]

Fig. 3-303, (p. 3-385)

P<>: S ignal P< de lay e d


0: No

[spacer]

035 094

P<>: S tarting P<<


0: No

[spacer]

Fig. 3-302, (p. 3-384)

P<>: S tarting P<


0: No

[spacer]

035 096

P<>: T rip s ignal Q>>


0: No

[spacer]

Logic Diagram

P<>: T rip s ignal Q>


0: No

[spacer]

Unit

P<>: S ignal Q>> delay ed


0: No

[spacer]

Max

035 010

Fig. 3-307, (p. 3-391)

P<>: S ignal Q< delay ed


0: No

P437/EN M/R-11-A // P437311650

035 067

Fig. 3-307, (p. 3-391)

8-99

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Fig. 3-307, (p. 3-391)


035 155

Fig. 3-308, (p. 3-393)


035 176

Fig. 3-308, (p. 3-393)


035 156

Fig. 3-308, (p. 3-393)


035 177

Fig. 3-308, (p. 3-393)


035 181

Fig. 3-310, (p. 3-395)


035 191

Fig. 3-310, (p. 3-395)


035 193

Fig. 3-311, (p. 3-395)

P<>: Direction Q back w.


0: No

8-100

035 049

P<>: Direction Q for w.


0: No

[spacer]

Fig. 3-307, (p. 3-391)

P<>: Direction P bac kw.


0: No

[spacer]

035 069

P<>: Direction P forw.


0: No

[spacer]

Fig. 3-307, (p. 3-391)

P<>: T rip s ig. Q<< t rans.


0: No

[spacer]

035 179

P<>: T rip s ig. Q< t rans.


0: No

[spacer]

Fig. 3-307, (p. 3-391)

P<>: T rip s ignal Q<<


0: No

[spacer]

035 016

P<>: T rip s ignal Q<


0: No

[spacer]

Fig. 3-307, (p. 3-391)

P<>: Fault Q<<


0: No

[spacer]

035 068

P<>: Fault Q<


0: No

[spacer]

Fig. 3-307, (p. 3-391)

P<>: t Q</t Q<< elaps. trans


0: No

[spacer]

035 011

P<>: t Q<< elaps ed t rans.


0: No

[spacer]

Logic Diagram

P<>: t Q< elaps ed t rans.


0: No

[spacer]

Unit

P<>: S ignal Q<< delay ed


0: No

[spacer]

Max

035 194

Fig. 3-311, (p. 3-395)

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Circuit breaker
failure protection

Address
Min

Max

Unit

Logic Diagram

CBF: Enable EXT

038 041

2: Not configured
[spacer]

CBF: Disable EXT

038 042

2: Not configured
[spacer]

CBF: Blocking EXT

038 058

0: No
[spacer]

CBF: S tart e nable E X T

038 209

1: Yes
[spacer]

CBF: S tart 3p EXT

038 205

0: No
[spacer]

CBF: S tarting trig. EX T

038 016

0: No
[spacer]

CBF: C B f aulty EX T

038 234

0: No
[spacer]

CBF: Ex t./ us er enabled


1: Yes

[spacer]

Fig. 3-312, (p. 3-396)

CBF: Enabled
0: No

[spacer]

038 040

040 055

Fig. 3-312, (p. 3-396)

CBF: R eady

038 009

0: No
[spacer]

CBF: Not r e ady


1: Yes

[spacer]

040 025

Fig. 3-313, (p. 3-397)

CBF: S tart A EXT

038 206

0: No
[spacer]

CBF: S tart B EXT

038 207

0: No
[spacer]

CBF: S tart C EXT

038 208

0: No
[spacer]

CBF: C B p os . implausi ble


0: No

[spacer]

038 230

Fig. 3-314, (p. 3-398)

CBF: C urre nt f low B


0: No

[spacer]

Fig. 3-315, (p. 3-399)

CBF: C urre nt f low A


0: No

[spacer]

038 210

038 231

Fig. 3-314, (p. 3-398)

CBF: C urre nt f low C


0: No

P437/EN M/R-11-A // P437311650

038 232

Fig. 3-314, (p. 3-398)

8-101

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Unit

Logic Diagram

CBF: C urre nt f low Phx


0: No

[spacer]

Max

038 233

Fig. 3-314, (p. 3-398)

CBF: C urre nt f low N


0: No

038 235

Fig. 3-314, (p. 3-398)

[spacer]

Signal that the residual current is greater than the set value CBF: IN<.

[spacer]

CBF: S tartup 3p

038 211

0: No
[spacer]

CBF: S tartup A
0: No

[spacer]

038 212

Fig. 3-316, (p. 3-401)

CBF: S tartup B

038 213

0: No
[spacer]

CBF: S tartup C

038 214

0: No
[spacer]

CBF: T r ip s ignal t1
0: No

[spacer]

Fig. 3-318, (p. 3-403)


038 221

Fig. 3-318, (p. 3-403)


038 222

Fig. 3-318, (p. 3-403)


038 223

Fig. 3-318, (p. 3-403)


038 224

Fig. 3-318, (p. 3-403)


036 017

Fig. 3-317, (p. 3-402)

CBF: S tarting
0: No

8-102

038 220

CBF: C B f ailure
0: No

[spacer]

Fig. 3-317, (p. 3-402)

CBF: T r ip comm and t 2


0: No

[spacer]

038 219

CBF: T r ip comm and t 1, C


0: No

[spacer]

Fig. 3-317, (p. 3-402)

CBF: T r ip comm and t 1, B


0: No

[spacer]

038 218

CBF: T r ip comm and t 1, A


0: No

[spacer]

Fig. 3-317, (p. 3-402)

CBF: T r ip comm and t 1


0: No

[spacer]

038 217

CBF: T r ip s ignal t2
0: No

[spacer]

Fig. 3-317, (p. 3-402)

CBF: T r ip s ignal t1 , C
0: No

[spacer]

038 216

CBF: T r ip s ignal t1 , B
0: No

[spacer]

Fig. 3-317, (p. 3-402)

CBF: T r ip s ignal t1 , A
0: No

[spacer]

038 215

038 021

Fig. 3-319, (p. 3-404)

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Fig. 3-320, (p. 3-404)


038 226

Fig. 3-321, (p. 3-405)


038 227

Fig. 3-321, (p. 3-405)

CBF: C Bs ync.superv B ope n


0: No

[spacer]

038 225

CBF: C Bs ync.superv A ope n


0: No

[spacer]

Fig. 3-319, (p. 3-404)

CBF: T r ip Sig C Bsync.super


0: No

[spacer]

040 026

CBF: Fault behi nd CB


0: No

[spacer]

Logic Diagram

CBF: T r ip s ignal
0: No

[spacer]

Unit

038 228

Fig. 3-321, (p. 3-405)

CBF: C Bs ync.superv C ope n


0: No

P437/EN M/R-11-A // P437311650

038 229

Fig. 3-321, (p. 3-405)

8-103

P437

8 Information and Control Functions

Parameter
Default

Address
Min

Max

Unit

Logic Diagram

CBM: R e se t m eas .val . E XT


Circuit breaker
condition monitoring

005 247

0: No
[spacer]

CBM: Blocking EXT

044 128

0: No
[spacer]

CBM: Enabled
0: No

[spacer]

Fig. 3-328, (p. 3-414)


044 135

Fig. 3-327, (p. 3-413)

CBM: S ig. R em . No .C B op.<


0: No

[spacer]

044 199

CBM: S ig. No. CB op. >


0: No

[spacer]

Fig. 3-322, (p. 3-406)

CBM: Blocked
0: No

[spacer]

044 130

CBM: S ignal I trip>

044 136

Fig. 3-326, (p. 3-413)


044 137

0: No
[spacer]

CBM: S ignal I trip**2>

044 138

0: No
[spacer]

CBM: S ignal I *t>

044 139

0: No
[spacer]

CBM: C ycle running A

044 205

0: No
[spacer]

CBM: C ycle running B

044 206

0: No
[spacer]

CBM: C ycle running C

044 207

0: No
[spacer]

CBM: t max > A

044 177

0: No
[spacer]

CBM: t max > B

044 178

0: No
[spacer]

CBM: t max > C

044 179

0: No
[spacer]

CBM: C urr. flow e nded A

044 201

0: No
[spacer]

CBM: C urr. flow e nded B

044 202

0: No
[spacer]

CBM: C urr. flow e nded C

044 203

0: No

8-104

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

CBM: S e tting e rr or C BM

Max

Unit

Logic Diagram
044 204

0: No

P437/EN M/R-11-A // P437311650

8-105

P437

8 Information and Control Functions

Parameter
Default

Limit value
monitoring

Address
Min

Max

Unit

Logic Diagram

LIMIT : Enabled
0: No

040 074

Fig. 3-329, (p. 3-416)


Fig. 3-333, (p. 3-420)

[spacer]

LIMIT : tI> elaps e d


0: No

[spacer]

040 228

Fig. 3-330, (p. 3-417)


040 229

Fig. 3-330, (p. 3-417)


040 230

Fig. 3-330, (p. 3-417)


040 231

Fig. 3-330, (p. 3-417)


040 168

Fig. 3-331, (p. 3-418)


040 169

Fig. 3-331, (p. 3-418)


042 152

Fig. 3-333, (p. 3-420)


042 153

Fig. 3-333, (p. 3-420)

LIMIT : tVref< e lapse d


0: No

8-106

Fig. 3-330, (p. 3-417)

LIMIT : tVref>> e lapse d


0: No

[spacer]

040 227

LIMIT : tVref> e lapse d


0: No

[spacer]

Fig. 3-330, (p. 3-417)

LIMIT : tVNG>> elapse d


0: No

[spacer]

040 226

LIMIT : tVNG> e lapsed


0: No

[spacer]

Fig. 3-330, (p. 3-417)

LIMIT : tVPP<< e laps ed


0: No

[spacer]

040 225

LIMIT : tVPP< e laps e d


0: No

[spacer]

Fig. 3-330, (p. 3-417)

LIMIT : tVPP>> e laps ed


0: No

[spacer]

040 224

LIMIT : tVPP> e laps e d


0: No

[spacer]

Fig. 3-329, (p. 3-416)

LIMIT : tVPG<< elaps ed


0: No

[spacer]

040 223

LIMIT : tVPG< e laps ed


0: No

[spacer]

Fig. 3-329, (p. 3-416)

LIMIT : tVPG>> elaps ed


0: No

[spacer]

040 222

LIMIT : tVPG> e laps ed


0: No

[spacer]

Fig. 3-329, (p. 3-416)

LIMIT : tI<< elap se d


0: No

[spacer]

040 221

LIMIT : tI< elaps e d


0: No

[spacer]

Fig. 3-329, (p. 3-416)

LIMIT : tI>> elap se d


0: No

[spacer]

040 220

042 154

Fig. 3-333, (p. 3-420)

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

040 186

Fig. 3-332, (p. 3-419)


040 187

Fig. 3-332, (p. 3-419)


040 170

Fig. 3-334, (p. 3-421)


040 171

Fig. 3-334, (p. 3-421)


040 172

Fig. 3-334, (p. 3-421)


040 173

Fig. 3-334, (p. 3-421)


040 174

Fig. 3-334, (p. 3-421)


040 175

Fig. 3-334, (p. 3-421)


040 176

Fig. 3-334, (p. 3-421)

LIMIT : tT << elaps ed


0: No

[spacer]

Fig. 3-332, (p. 3-419)

LIMIT : tT < elaps ed


0: No

[spacer]

040 185

LIMIT : St arting T <<


0: No

[spacer]

Fig. 3-332, (p. 3-419)

LIMIT : St arting T <


0: No

[spacer]

040 184

LIMIT : tT >> elaps ed


0: No

[spacer]

Fig. 3-332, (p. 3-419)

LIMIT : tT > elaps ed


0: No

[spacer]

040 183

LIMIT : St arting T >>


0: No

[spacer]

Fig. 3-332, (p. 3-419)

LIMIT : St arting T >


0: No

[spacer]

040 182

LIMIT : tIDC,lin<< elaps ed


0: No

[spacer]

Fig. 3-332, (p. 3-419)

LIMIT : tIDC,lin< elaps ed


0: No

[spacer]

040 181

LIMIT : St arting IDC ,lin<<


0: No

[spacer]

Fig. 3-332, (p. 3-419)

LIMIT : St arting IDC ,lin<


0: No

[spacer]

040 180

LIMIT : tIDC,lin>> elaps ed


0: No

[spacer]

Fig. 3-333, (p. 3-420)

LIMIT : tIDC,lin> elaps ed


0: No

[spacer]

042 155

LIMIT : St arting IDC ,lin>>


0: No

[spacer]

Logic Diagram

LIMIT : St arting IDC ,lin>


0: No

[spacer]

Unit

LIMIT : tVref<< e lapse d


0: No

[spacer]

Max

LIMIT : tIPxx trigge re d

040 177

Fig. 3-334, (p. 3-421)


221 232

0: Not triggered
[spacer]

LIMIT : tVPGxx t rigger e d

221 233

0: Not triggered

P437/EN M/R-11-A // P437311650

8-107

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

LIMIT : tVPPxx t rigger ed

Max

Unit

Logic Diagram
221 234

0: Not triggered
[spacer]

LIMIT : tVNGxx t riggere d

221 235

0: Not triggered
[spacer]

LIMIT : tVrefx x trigge re d

221 237

0: Not triggered

8-108

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Programmable Logic LOGIC: Input 01 EXT

Address
Min

Max

Unit

Logic Diagram
034 000

0: No
[spacer]

LOGIC: Input 02 EXT

034 001

0: No
[spacer]

LOGIC: Input 03 EXT

034 002

0: No
[spacer]

LOGIC: Input 04 EXT

034 003

0: No
[spacer]

LOGIC: Input 05 EXT

034 004

0: No
[spacer]

LOGIC: Input 06 EXT

034 005

0: No
[spacer]

LOGIC: Input 07 EXT

034 006

0: No
[spacer]

LOGIC: Input 08 EXT

034 007

0: No
[spacer]

LOGIC: Input 09 EXT

034 008

0: No
[spacer]

LOGIC: Input 10 EXT

034 009

0: No
[spacer]

LOGIC: Input 11 EXT

034 010

0: No
[spacer]

LOGIC: Input 12 EXT

034 011

0: No
[spacer]

LOGIC: Input 13 EXT

034 012

0: No
[spacer]

LOGIC: Input 14 EXT

034 013

0: No
[spacer]

LOGIC: Input 15 EXT

034 014

0: No
[spacer]

LOGIC: Input 16 EXT

034 015

0: No
[spacer]

LOGIC: Input 17 EXT

034 086

0: No
[spacer]

LOGIC: Input 18 EXT

034 087

0: No
[spacer]

LOGIC: Input 19 EXT

034 088

0: No

P437/EN M/R-11-A // P437311650

8-109

P437

8 Information and Control Functions

Parameter
Default
[spacer]

LOGIC: Input 20 EXT

Address
Min

Max

Unit

Logic Diagram
034 089

0: No
[spacer]

LOGIC: Input 21 EXT

034 090

0: No
[spacer]

LOGIC: Input 22 EXT

034 091

0: No
[spacer]

LOGIC: Input 23 EXT

034 092

0: No
[spacer]

LOGIC: Input 24 EXT

034 093

0: No
[spacer]

LOGIC: Input 25 EXT

034 094

0: No
[spacer]

LOGIC: Input 26 EXT

034 095

0: No
[spacer]

LOGIC: Input 27 EXT

034 096

0: No
[spacer]

LOGIC: Input 28 EXT

034 097

0: No
[spacer]

LOGIC: Input 29 EXT

034 098

0: No
[spacer]

LOGIC: Input 30 EXT

034 099

0: No
[spacer]

LOGIC: Input 31 EXT

034 100

0: No
[spacer]

LOGIC: Input 32 EXT

034 101

0: No
[spacer]

LOGIC: Input 33 EXT

034 102

0: No
[spacer]

LOGIC: Input 34 EXT

034 103

0: No
[spacer]

LOGIC: Input 35 EXT

034 104

0: No
[spacer]

LOGIC: Input 36 EXT

034 105

0: No
[spacer]

LOGIC: Input 37 EXT

034 106

0: No
[spacer]

LOGIC: Input 38 EXT

034 107

0: No

8-110

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

LOGIC: Input 39 EXT

034 108

0: No
[spacer]

LOGIC: Input 40 EXT

034 109

0: No
[spacer]

LOGIC: Se t 1 EXT

034 051

2: Not configured
[spacer]

LOGIC: Se t 2 EXT

034 052

2: Not configured
[spacer]

LOGIC: Se t 3 EXT

034 053

2: Not configured
[spacer]

LOGIC: Se t 4 EXT

034 054

2: Not configured
[spacer]

LOGIC: Se t 5 EXT

034 055

2: Not configured
[spacer]

LOGIC: Se t 6 EXT

034 056

2: Not configured
[spacer]

LOGIC: Se t 7 EXT

034 057

2: Not configured
[spacer]

LOGIC: Se t 8 EXT

034 058

2: Not configured
[spacer]

LOGIC: Re s e t 1 E XT

034 059

2: Not configured
[spacer]

LOGIC: Re s e t 2 E XT

034 060

2: Not configured
[spacer]

LOGIC: Re s e t 3 E XT

034 061

2: Not configured
[spacer]

LOGIC: Re s e t 4 E XT

034 062

2: Not configured
[spacer]

LOGIC: Re s e t 5 E XT

034 063

2: Not configured
[spacer]

LOGIC: Re s e t 6 E XT

034 064

2: Not configured
[spacer]

LOGIC: Re s e t 7 E XT

034 065

2: Not configured
[spacer]

LOGIC: Re s e t 8 E XT

034 066

2: Not configured
[spacer]

LOGIC: 1 has been s et


0: No

P437/EN M/R-11-A // P437311650

034 067

Fig. 3-335, (p. 3-423)

8-111

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

LOGIC: 2 has been s et

034 068

0: No
[spacer]

LOGIC: 3 has been s et

034 069

0: No
[spacer]

LOGIC: 4 has been s et

034 070

0: No
[spacer]

LOGIC: 5 has been s et

034 071

0: No
[spacer]

LOGIC: 6 has been s et

034 072

0: No
[spacer]

LOGIC: 7 has been s et

034 073

0: No
[spacer]

LOGIC: 8 has been s et

034 074

0: No
[spacer]

LOGIC: 1 se t e xternally
0: No

[spacer]

034 075

Fig. 3-335, (p. 3-423)

LOGIC: 2 se t e xternally

034 076

0: No
[spacer]

LOGIC: 3 se t e xternally

034 077

0: No
[spacer]

LOGIC: 4 se t e xternally

034 078

0: No
[spacer]

LOGIC: 5 se t e xternally

034 079

0: No
[spacer]

LOGIC: 6 se t e xternally

034 080

0: No
[spacer]

LOGIC: 7 se t e xternally

034 081

0: No
[spacer]

LOGIC: 8 se t e xternally

034 082

0: No
[spacer]

LOGIC: Enabled
0: No

[spacer]

042 032

Fig. 3-336, (p. 3-424)

LOGIC: Output 01 (t)


0: No

[spacer]

Fig. 3-336, (p. 3-424)

LOGIC: Output 01
0: No

[spacer]

034 046

LOGIC: Output 02

042 033

Fig. 3-336, (p. 3-424)


042 034

0: No

8-112

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

LOGIC: Output 0 2 (t)

Address
Min

Max

Unit

Logic Diagram
042 035

0: No
[spacer]

LOGIC: Output 0 3

042 036

0: No
[spacer]

LOGIC: Output 0 3 (t)

042 037

0: No
[spacer]

LOGIC: Output 0 4

042 038

0: No
[spacer]

LOGIC: Output 0 4 (t)

042 039

0: No
[spacer]

LOGIC: Output 0 5

042 040

0: No
[spacer]

LOGIC: Output 0 5 (t)

042 041

0: No
[spacer]

LOGIC: Output 0 6

042 042

0: No
[spacer]

LOGIC: Output 0 6 (t)

042 043

0: No
[spacer]

LOGIC: Output 0 7

042 044

0: No
[spacer]

LOGIC: Output 0 7 (t)

042 045

0: No
[spacer]

LOGIC: Output 0 8

042 046

0: No
[spacer]

LOGIC: Output 0 8 (t)

042 047

0: No
[spacer]

LOGIC: Output 0 9

042 048

0: No
[spacer]

LOGIC: Output 0 9 (t)

042 049

0: No
[spacer]

LOGIC: Output 1 0

042 050

0: No
[spacer]

LOGIC: Output 1 0 (t)

042 051

0: No
[spacer]

LOGIC: Output 1 1

042 052

0: No
[spacer]

LOGIC: Output 1 1 (t)

042 053

0: No

P437/EN M/R-11-A // P437311650

8-113

P437

8 Information and Control Functions

Parameter
Default
[spacer]

LOGIC: Output 12

Address
Min

Max

Unit

Logic Diagram
042 054

0: No
[spacer]

LOGIC: Output 12 (t)

042 055

0: No
[spacer]

LOGIC: Output 13

042 056

0: No
[spacer]

LOGIC: Output 13 (t)

042 057

0: No
[spacer]

LOGIC: Output 14

042 058

0: No
[spacer]

LOGIC: Output 14 (t)

042 059

0: No
[spacer]

LOGIC: Output 15

042 060

0: No
[spacer]

LOGIC: Output 15 (t)

042 061

0: No
[spacer]

LOGIC: Output 16

042 062

0: No
[spacer]

LOGIC: Output 16 (t)

042 063

0: No
[spacer]

LOGIC: Output 17

042 064

0: No
[spacer]

LOGIC: Output 17 (t)

042 065

0: No
[spacer]

LOGIC: Output 18

042 066

0: No
[spacer]

LOGIC: Output 18 (t)

042 067

0: No
[spacer]

LOGIC: Output 19

042 068

0: No
[spacer]

LOGIC: Output 19 (t)

042 069

0: No
[spacer]

LOGIC: Output 20

042 070

0: No
[spacer]

LOGIC: Output 20 (t)

042 071

0: No
[spacer]

LOGIC: Output 21

042 072

0: No

8-114

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

LOGIC: Output 2 1 (t)

Address
Min

Max

Unit

Logic Diagram
042 073

0: No
[spacer]

LOGIC: Output 2 2

042 074

0: No
[spacer]

LOGIC: Output 2 2 (t)

042 075

0: No
[spacer]

LOGIC: Output 2 3

042 076

0: No
[spacer]

LOGIC: Output 2 3 (t)

042 077

0: No
[spacer]

LOGIC: Output 2 4

042 078

0: No
[spacer]

LOGIC: Output 2 4 (t)

042 079

0: No
[spacer]

LOGIC: Output 2 5

042 080

0: No
[spacer]

LOGIC: Output 2 5 (t)

042 081

0: No
[spacer]

LOGIC: Output 2 6

042 082

0: No
[spacer]

LOGIC: Output 2 6 (t)

042 083

0: No
[spacer]

LOGIC: Output 2 7

042 084

0: No
[spacer]

LOGIC: Output 2 7 (t)

042 085

0: No
[spacer]

LOGIC: Output 2 8

042 086

0: No
[spacer]

LOGIC: Output 2 8 (t)

042 087

0: No
[spacer]

LOGIC: Output 2 9

042 088

0: No
[spacer]

LOGIC: Output 2 9 (t)

042 089

0: No
[spacer]

LOGIC: Output 3 0

042 090

0: No
[spacer]

LOGIC: Output 3 0 (t)

042 091

0: No

P437/EN M/R-11-A // P437311650

8-115

P437

8 Information and Control Functions

Parameter
Default
[spacer]

LOGIC: Output 31

Address
Min

Max

Unit

Logic Diagram
042 092

0: No
[spacer]

LOGIC: Output 31 (t)

042 093

0: No
[spacer]

LOGIC: Output 32

042 094

0: No
[spacer]

LOGIC: Output 32 (t)

042 095

0: No
[spacer]

LOGIC: Output 33

042 180

0: No
[spacer]

LOGIC: Output 33 (t)

042 181

0: No
[spacer]

LOGIC: Output 34

042 182

0: No
[spacer]

LOGIC: Output 34 (t)

042 183

0: No
[spacer]

LOGIC: Output 35

042 184

0: No
[spacer]

LOGIC: Output 35 (t)

042 185

0: No
[spacer]

LOGIC: Output 36

042 186

0: No
[spacer]

LOGIC: Output 36 (t)

042 187

0: No
[spacer]

LOGIC: Output 37

042 188

0: No
[spacer]

LOGIC: Output 37 (t)

042 189

0: No
[spacer]

LOGIC: Output 38

042 190

0: No
[spacer]

LOGIC: Output 38 (t)

042 191

0: No
[spacer]

LOGIC: Output 39

042 192

0: No
[spacer]

LOGIC: Output 39 (t)

042 193

0: No
[spacer]

LOGIC: Output 40

042 194

0: No

8-116

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

LOGIC: Output 4 0 (t)

Address
Min

Max

Unit

Logic Diagram
042 195

0: No
[spacer]

LOGIC: Output 4 1

042 196

0: No
[spacer]

LOGIC: Output 4 1 (t)

042 197

0: No
[spacer]

LOGIC: Output 4 2

042 198

0: No
[spacer]

LOGIC: Output 4 2 (t)

042 199

0: No
[spacer]

LOGIC: Output 4 3

042 200

0: No
[spacer]

LOGIC: Output 4 3 (t)

042 201

0: No
[spacer]

LOGIC: Output 4 4

042 202

0: No
[spacer]

LOGIC: Output 4 4 (t)

042 203

0: No
[spacer]

LOGIC: Output 4 5

042 204

0: No
[spacer]

LOGIC: Output 4 5 (t)

042 205

0: No
[spacer]

LOGIC: Output 4 6

042 206

0: No
[spacer]

LOGIC: Output 4 6 (t)

042 207

0: No
[spacer]

LOGIC: Output 4 7

042 208

0: No
[spacer]

LOGIC: Output 4 7 (t)

042 209

0: No
[spacer]

LOGIC: Output 4 8

042 210

0: No
[spacer]

LOGIC: Output 4 8 (t)

042 211

0: No
[spacer]

LOGIC: Output 4 9

042 212

0: No
[spacer]

LOGIC: Output 4 9 (t)

042 213

0: No

P437/EN M/R-11-A // P437311650

8-117

P437

8 Information and Control Functions

Parameter
Default
[spacer]

LOGIC: Output 50

Address
Min

Max

Unit

Logic Diagram
042 214

0: No
[spacer]

LOGIC: Output 50 (t)

042 215

0: No
[spacer]

LOGIC: Output 51

042 216

0: No
[spacer]

LOGIC: Output 51 (t)

042 217

0: No
[spacer]

LOGIC: Output 52

042 218

0: No
[spacer]

LOGIC: Output 52 (t)

042 219

0: No
[spacer]

LOGIC: Output 53

042 220

0: No
[spacer]

LOGIC: Output 53 (t)

042 221

0: No
[spacer]

LOGIC: Output 54

042 222

0: No
[spacer]

LOGIC: Output 54 (t)

042 223

0: No
[spacer]

LOGIC: Output 55

042 224

0: No
[spacer]

LOGIC: Output 55 (t)

042 225

0: No
[spacer]

LOGIC: Output 56

042 226

0: No
[spacer]

LOGIC: Output 56 (t)

042 227

0: No
[spacer]

LOGIC: Output 57

042 228

0: No
[spacer]

LOGIC: Output 57 (t)

042 229

0: No
[spacer]

LOGIC: Output 58

042 230

0: No
[spacer]

LOGIC: Output 58 (t)

042 231

0: No
[spacer]

LOGIC: Output 59

042 232

0: No

8-118

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

LOGIC: Output 5 9 (t)

Address
Min

Max

Unit

Logic Diagram
042 233

0: No
[spacer]

LOGIC: Output 6 0

042 234

0: No
[spacer]

LOGIC: Output 6 0 (t)

042 235

0: No
[spacer]

LOGIC: Output 6 1

042 236

0: No
[spacer]

LOGIC: Output 6 1 (t)

042 237

0: No
[spacer]

LOGIC: Output 6 2

042 238

0: No
[spacer]

LOGIC: Output 6 2 (t)

042 239

0: No
[spacer]

LOGIC: Output 6 3

042 240

0: No
[spacer]

LOGIC: Output 6 3 (t)

042 241

0: No
[spacer]

LOGIC: Output 6 4

042 242

0: No
[spacer]

LOGIC: Output 6 4 (t)

042 243

0: No
[spacer]

LOGIC: Output 6 5

047 128

0: No
[spacer]

LOGIC: Output 6 5 (t)

047 129

0: No
[spacer]

LOGIC: Output 6 6

047 002

0: No
[spacer]

LOGIC: Output 6 6 (t)

047 003

0: No
[spacer]

LOGIC: Output 6 7

047 004

0: No
[spacer]

LOGIC: Output 6 7 (t)

047 005

0: No
[spacer]

LOGIC: Output 6 8

047 006

0: No
[spacer]

LOGIC: Output 6 8 (t)

047 007

0: No

P437/EN M/R-11-A // P437311650

8-119

P437

8 Information and Control Functions

Parameter
Default
[spacer]

LOGIC: Output 69

Address
Min

Max

Unit

Logic Diagram
047 008

0: No
[spacer]

LOGIC: Output 69 (t)

047 009

0: No
[spacer]

LOGIC: Output 70

047 010

0: No
[spacer]

LOGIC: Output 70 (t)

047 011

0: No
[spacer]

LOGIC: Output 71

047 012

0: No
[spacer]

LOGIC: Output 71 (t)

047 013

0: No
[spacer]

LOGIC: Output 72

047 014

0: No
[spacer]

LOGIC: Output 72 (t)

047 015

0: No
[spacer]

LOGIC: Output 73

047 016

0: No
[spacer]

LOGIC: Output 73 (t)

047 017

0: No
[spacer]

LOGIC: Output 74

047 018

0: No
[spacer]

LOGIC: Output 74 (t)

047 019

0: No
[spacer]

LOGIC: Output 75

047 020

0: No
[spacer]

LOGIC: Output 75 (t)

047 021

0: No
[spacer]

LOGIC: Output 76

047 022

0: No
[spacer]

LOGIC: Output 76 (t)

047 023

0: No
[spacer]

LOGIC: Output 77

047 024

0: No
[spacer]

LOGIC: Output 77 (t)

047 025

0: No
[spacer]

LOGIC: Output 78

047 026

0: No

8-120

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

LOGIC: Output 7 8 (t)

Address
Min

Max

Unit

Logic Diagram
047 027

0: No
[spacer]

LOGIC: Output 7 9

047 028

0: No
[spacer]

LOGIC: Output 7 9 (t)

047 029

0: No
[spacer]

LOGIC: Output 8 0

047 030

0: No
[spacer]

LOGIC: Output 8 0 (t)

047 031

0: No
[spacer]

LOGIC: Output 8 1

047 032

0: No
[spacer]

LOGIC: Output 8 1 (t)

047 033

0: No
[spacer]

LOGIC: Output 8 2

047 034

0: No
[spacer]

LOGIC: Output 8 2 (t)

047 035

0: No
[spacer]

LOGIC: Output 8 3

047 036

0: No
[spacer]

LOGIC: Output 8 3 (t)

047 037

0: No
[spacer]

LOGIC: Output 8 4

047 038

0: No
[spacer]

LOGIC: Output 8 4 (t)

047 039

0: No
[spacer]

LOGIC: Output 8 5

047 040

0: No
[spacer]

LOGIC: Output 8 5 (t)

047 041

0: No
[spacer]

LOGIC: Output 8 6

047 042

0: No
[spacer]

LOGIC: Output 8 6 (t)

047 043

0: No
[spacer]

LOGIC: Output 8 7

047 044

0: No
[spacer]

LOGIC: Output 8 7 (t)

047 045

0: No

P437/EN M/R-11-A // P437311650

8-121

P437

8 Information and Control Functions

Parameter
Default
[spacer]

LOGIC: Output 88

Address
Min

Max

Unit

Logic Diagram
047 046

0: No
[spacer]

LOGIC: Output 88 (t)

047 047

0: No
[spacer]

LOGIC: Output 89

047 048

0: No
[spacer]

LOGIC: Output 89 (t)

047 049

0: No
[spacer]

LOGIC: Output 90

047 050

0: No
[spacer]

LOGIC: Output 90 (t)

047 051

0: No
[spacer]

LOGIC: Output 91

047 052

0: No
[spacer]

LOGIC: Output 91 (t)

047 053

0: No
[spacer]

LOGIC: Output 92

047 054

0: No
[spacer]

LOGIC: Output 92 (t)

047 055

0: No
[spacer]

LOGIC: Output 93

047 056

0: No
[spacer]

LOGIC: Output 93 (t)

047 057

0: No
[spacer]

LOGIC: Output 94

047 058

0: No
[spacer]

LOGIC: Output 94 (t)

047 059

0: No
[spacer]

LOGIC: Output 95

047 060

0: No
[spacer]

LOGIC: Output 95 (t)

047 061

0: No
[spacer]

LOGIC: Output 96

047 062

0: No
[spacer]

LOGIC: Output 96 (t)

047 063

0: No
[spacer]

LOGIC: Output 97

047 064

0: No

8-122

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

LOGIC: Output 9 7 (t)

Max

Unit

Logic Diagram
047 065

0: No
[spacer]

LOGIC: Output 9 8

047 066

0: No
[spacer]

LOGIC: Output 9 8 (t)

047 067

0: No
[spacer]

LOGIC: Output 9 9

047 068

0: No
[spacer]

LOGIC: Output 9 9 (t)

047 069

0: No
[spacer]

LOGIC: Output10 0

047 070

0: No
[spacer]

LOGIC: Output10 0 ( t )

047 071

0: No
[spacer]

LOGIC: Output10 1

047 072

0: No
[spacer]

LOGIC: Output10 1 ( t )

047 073

0: No
[spacer]

LOGIC: Output10 2

047 074

0: No
[spacer]

LOGIC: Output10 2 ( t )

047 075

0: No
[spacer]

LOGIC: Output10 3

047 076

0: No
[spacer]

LOGIC: Output10 3 ( t )

047 077

0: No
[spacer]

LOGIC: Output10 4

047 078

0: No
[spacer]

LOGIC: Output10 4 ( t )

047 079

0: No
[spacer]

LOGIC: Output10 5

047 080

0: No
[spacer]

LOGIC: Output10 5 ( t )

047 081

0: No
[spacer]

LOGIC: Output10 6

047 082

0: No
[spacer]

LOGIC: Output10 6 ( t )

047 083

0: No

P437/EN M/R-11-A // P437311650

8-123

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

LOGIC: Output107

Max

Unit

Logic Diagram
047 084

0: No
[spacer]

LOGIC: Output107 ( t )

047 085

0: No
[spacer]

LOGIC: Output108

047 086

0: No
[spacer]

LOGIC: Output108 ( t )

047 087

0: No
[spacer]

LOGIC: Output109

047 088

0: No
[spacer]

LOGIC: Output109 ( t )

047 089

0: No
[spacer]

LOGIC: Output110

047 090

0: No
[spacer]

LOGIC: Output110 ( t )

047 091

0: No
[spacer]

LOGIC: Output111

047 092

0: No
[spacer]

LOGIC: Output111 ( t )

047 093

0: No
[spacer]

LOGIC: Output112

047 094

0: No
[spacer]

LOGIC: Output112 ( t )

047 095

0: No
[spacer]

LOGIC: Output113

047 096

0: No
[spacer]

LOGIC: Output113 ( t )

047 097

0: No
[spacer]

LOGIC: Output114

047 098

0: No
[spacer]

LOGIC: Output114 ( t )

047 099

0: No
[spacer]

LOGIC: Output115

047 100

0: No
[spacer]

LOGIC: Output115 ( t )

047 101

0: No
[spacer]

LOGIC: Output116

047 102

0: No

8-124

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

LOGIC: Output11 6 ( t )

Max

Unit

Logic Diagram
047 103

0: No
[spacer]

LOGIC: Output11 7

047 104

0: No
[spacer]

LOGIC: Output11 7 ( t )

047 105

0: No
[spacer]

LOGIC: Output11 8

047 106

0: No
[spacer]

LOGIC: Output11 8 ( t )

047 107

0: No
[spacer]

LOGIC: Output11 9

047 108

0: No
[spacer]

LOGIC: Output11 9 ( t )

047 109

0: No
[spacer]

LOGIC: Output12 0

047 110

0: No
[spacer]

LOGIC: Output12 0 ( t )

047 111

0: No
[spacer]

LOGIC: Output12 1

047 112

0: No
[spacer]

LOGIC: Output12 1 ( t )

047 113

0: No
[spacer]

LOGIC: Output12 2

047 114

0: No
[spacer]

LOGIC: Output12 2 ( t )

047 115

0: No
[spacer]

LOGIC: Output12 3

047 116

0: No
[spacer]

LOGIC: Output12 3 ( t )

047 117

0: No
[spacer]

LOGIC: Output12 4

047 118

0: No
[spacer]

LOGIC: Output12 4 ( t )

047 119

0: No
[spacer]

LOGIC: Output12 5

047 120

0: No
[spacer]

LOGIC: Output12 5 ( t )

047 121

0: No

P437/EN M/R-11-A // P437311650

8-125

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

LOGIC: Output126

047 122

0: No
[spacer]

LOGIC: Output126 ( t )

047 123

0: No
[spacer]

LOGIC: Output127

047 124

0: No
[spacer]

LOGIC: Output127 ( t )

047 125

0: No
[spacer]

LOGIC: Output128

047 126

0: No
[spacer]

LOGIC: Output128 ( t )

047 127

0: No

Parameter
Default

Address
Min

Max

Unit

Logic Diagram

Programmable Logic LOG_2: Enable d


0: No
[spacer]

052 032

Fig. 3-337, (p. 3-425)

LOG_2: Out put 1 (t )


0: No

[spacer]

Fig. 3-337, (p. 3-425)

LOG_2: Out put 1


0: No

[spacer]

011 138

LOG_2: Out put 2

052 033

Fig. 3-337, (p. 3-425)


052 034

0: No
[spacer]

LOG_2: Out put 2 (t )

052 035

0: No
[spacer]

LOG_2: Out put 3

052 036

0: No
[spacer]

LOG_2: Out put 3 (t )

052 037

0: No
[spacer]

LOG_2: Out put 4

052 038

0: No
[spacer]

LOG_2: Out put 4 (t )

052 039

0: No

8-126

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Binary counts

Address
Min

Max

Unit

Logic Diagram

COUNT : Se t counte r 1 E X T

217 130

0: No
[spacer]

COUNT : Se t counte r 2 E X T

217 085

0: No
[spacer]

COUNT : Se t counte r 3 E X T

217 086

0: No
[spacer]

COUNT : Se t counte r 4 E X T

217 087

0: No
[spacer]

COUNT : Transmit count s E XT

217 009

0: No
[spacer]

COUNT : Re s e t EX T

217 004

0: No
[spacer]

COUNT : Enab led

217 001

0: No
[spacer]

Fig. 3-345, (p. 3-431)

COUNT : Transmit count s

217 010

0: No
[spacer]

Fig. 3-345, (p. 3-431)

COUNT : Re s e t

217 005

0: No
[spacer]

Fig. 3-345, (p. 3-431)

COUNT : Warnin g count 1

217 191

0: No
[spacer]

COUNT : Warnin g count 2

217 192

0: No
[spacer]

COUNT : Warnin g count 3

217 193

0: No
[spacer]

COUNT : Warnin g count 4

217 194

0: No
[spacer]

8.1.2

Warning that the counter value has exceeded the set limit value.

Control and Testing


Parameter
Default

Device

Address
Min

Max

DVICE: S e rvice info 03 1 08 0

Unit

Logic Diagram
031 080

0: No

P437/EN M/R-11-A // P437311650

8-127

P437

8 Information and Control Functions

Parameter
Default

Local control panel

Address
Min

Max

Unit

Logic Diagram

LOC: Param . change enabl.

003 010

0: No
[spacer]

Setting the enable for changing values from the local control panel.
Parameter
Default

Logical
communication
interface 1

Address
Min

Max

Unit

Logic Diagram

COMM 1: Se l.s pont an.s ig.te st

003 180

060 000: MAIN: Without function

Fig. 3-13, (p. 3-18)

[spacer]

Signal selection for testing purposes.

[spacer]

COMM 1: Tes t s pont .s ig.s t ar t

003 184

0: don't execute

Fig. 3-13, (p. 3-18)

[spacer]

Triggering of transmission of a selected signal as starting.

[spacer]

COMM 1: Tes t s pont .s ig. end

003 186

0: don't execute
[spacer]

Fig. 3-13, (p. 3-18)

Triggering of transmission of a selected signal as ending.


Parameter
Default

Logical
communication
interface 2

Address
Min

Max

Unit

Logic Diagram

COMM 2: Se l.s pont an.s ig.te st

060 000: MAIN: Without function


[spacer]

Signal selection for testing purposes.

[spacer]

COMM 2: Tes t s pont .s ig.s t ar t


0: don't execute

103 180

Fig. 3-15, (p. 3-20)

103 184

Fig. 3-15, (p. 3-20)

[spacer]

Triggering of transmission of a selected signal as "starting".

[spacer]

COMM 2: Tes t s pont .s ig. end


0: don't execute

[spacer]

8-128

103 186

Fig. 3-15, (p. 3-20)

Triggering of transmission of a selected signal as "ending".

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

InterMiCOM
interface

Address
Min

Max

Unit

COMM 3: Rse t No.tlg.e rr .US ER

Logic Diagram
120 037

0: don't execute
[spacer]

COMM 4: Rse t No.tlg.e rr .US ER

122 037

0: don't execute
[spacer]

Resetting counter for number of telegram errors.

[spacer]

COMM 3: Se nd s ignal for t es t

120 050

0: None
[spacer]

COMM 3: Log. s tat e for t est

120 051

1: 1
[spacer]

COMM 3: Se nd s ignal , te st

120 053

0: don't execute
[spacer]

COMM 3: Loop back se nd


170

[spacer]

120 055

255

COMM 4: Loop back se nd


170

122 055

255

[spacer]

Setting a bit pattern consisting of 3 bits.

[spacer]

COMM 3: Loop back t est

120 054

0: don't execute
[spacer]

COMM 4: Loop back t est

122 054

0: don't execute
[spacer]

Carrying out a loop back test with the PCOMM interface.

[spacer]

COMM 3: Hold time for te s t


10

[spacer]

600

COMM 4: Hold time for te s t


10

[spacer]

120 052

122 052

600

Selecting the hold time (in seconds) for the functional testing.

P437/EN M/R-11-A // P437311650

8-129

P437

8 Information and Control Functions

Parameter
Default

InterMiCOM
interface

Address
Min

Max

COMM 4: Se nd s ignal for t es t

Unit

Logic Diagram
122 050

0: None
[spacer]

COMM 4: Log. s tat e for t est

122 051

1: 1
[spacer]

COMM 4: Se nd s ignal , te st

122 053

0: don't execute

8-130

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

IEC Generic
Substation Status
Events

Address
Min

Max

Unit

Logic Diagram

GSS E: Re s et s tat isti cs

105 171

0: don't execute
[spacer]

Command to reset monitoring counters as listed below.

[spacer]

GSS E: Enr oll. I EDs fl ags L


Not measured

105 160

65535

[spacer]

Bar with state bits for all GSSE inputs, showing if the respective GSSE sending
device has logged-on and is transmitting free of fault (input 1 to 16).

[spacer]

GSS E: Enr oll. I EDs fl ags H


Not measured

105 161

65535

[spacer]

Bar with state bits for all GSSE inputs, showing if the respective GSSE sending
device has logged-on and is transmitting free of fault (input 17 to 32).

[spacer]

GSS E: T x m es s age c ounter


Not measured

105 162

65535

[spacer]

Shows the number of GSSE messages sent. This counter is reset by


GSS E: Re s et s tat isti cs.

[spacer]

GSS E: Rx m es s age c ounter


Not measured

105 163

65535

[spacer]

Shows the number of GSSE messages received. This counter is reset by


GSS E: Re s et s tat isti cs.

[spacer]

GSS E: No. bin.s tate c hang.


Not measured

105 164

65535

[spacer]

Number of state changes included in a GSSE sent. This counter is reset by


GSS E: Re s et s tat isti cs.

[spacer]

GSS E: T x last s equence


Not measured

105 165

65535

[spacer]

State of the continuous counter sequence for the message counter sent with
each GSSE.

[spacer]

GSS E: T x last me ssage


Not measured

105 166

65535

[spacer]

State of the continuous counter sequence for state changes sent with each
GSSE.

[spacer]

GSS E: No. re je ct . mes sage s


Not measured

[spacer]

105 167

65535

Number of telegram rejections having occurred because of non-plausible


message content. This counter is reset by G SS E: Res et statistics.

P437/EN M/R-11-A // P437311650

8-131

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

GSS E: IE D vie w s ele ct ion

105 170

1: Remote IED
[spacer]

Setting for which GSSE sending device the following statistics information is to
be displayed.

[spacer]

GSS E: IE D receiv. me ssages


Not measured

65535

[spacer]

Counter of the received GSSE telegrams.

[spacer]

GSS E: IE D R x las t se quenc e


Not measured

105 172

105 173

65535

[spacer]

State of the continuous counter sequence for the message counter received with
each GSSE.

[spacer]

GSS E: IE D R x las t me ss age


Not measured

105 174

65535

[spacer]

State of the continuous counter sequence for state changes received with each
GSSE.

[spacer]

GSS E: IE D m iss ed me s s age s


Not measured

105 175

65535

[spacer]

Number of missing GSSE messages (gaps in the continuous sequence


numbering). This counter is reset by GS SE : Re se t statistics.

[spacer]

GSS E: IE D m iss ed change s


Not measured

105 176

65535

[spacer]

Number of missing state changes (gaps in the continuous sequence


numbering). This counter is reset by GS SE : Re se t statistics.

[spacer]

GSS E: IE D t ime-out s
Not measured

[spacer]

8-132

105 177

65535

Number of GSSE received after the validity time period has elapsed.
This counter is reset by GS SE : Res e t st atisti cs.

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

IEC 61850
Communication

Address
Min

Max

Unit

Logic Diagram

IEC: Se l.s pontan.si g.t est

104 245

060 000: MAIN: Without function


[spacer]

IEC: Tes t sp ont.sig.s tar t

104 246

0: don't execute
[spacer]

IEC: Tes t sp ont.sig. end

104 247

0: don't execute
[spacer]

IEC: Se l. pos . d ev .t es t

104 248

0: Not assigned
[spacer]

IEC: Tes t pos ition DEV

104 249

0: don't execute

Parameter
Default

Address
Min

Max

Unit

Logic Diagram

Measured data input MEASI: Rs t. temp. T max US ER

003 045

0: don't execute
[spacer]

Resetting measured maximum temperatures Tmax and Tmax Tx (x=1...9) to


updated measured values.
Parameter
Default

Binary and analog


output

Address
Min

Max

Unit

Logic Diagram

OUTP: Re s e t latch. US ER

021 009

0: don't execute

Fig. 3-31, (p. 3-50)

[spacer]

Reset of latched output relays from the user interface.

[spacer]

OUTP: Re lay assign. f.t e st

003 042

060 000: MAIN: Without function

Fig. 3-32, (p. 3-51)

[spacer]

Selection of the relay to be tested.

[spacer]

OUTP: Re lay te st

003 043

0: don't execute

Fig. 3-32, (p. 3-51)

[spacer]

The relay selected for testing is triggered for the duration set at OUTP: H ol d time f or tes t.

[spacer]

OUTP: Hold- tim e for t e st


1

[spacer]

003 044

10

Fig. 3-32, (p. 3-51)

Setting for the time period for which the selected output relay is triggered for
functional testing.

P437/EN M/R-11-A // P437311650

8-133

P437

8 Information and Control Functions

Parameter
Default

Measured data
output

Address
Min

Max

Unit

MEASO: Rese t output USE R


0: don't execute

[spacer]

8-134

Logic Diagram
037 116

Fig. 3-35, (p. 3-53)

Resetting the measured data output function.

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Main function

Address
Min

Max

[spacer]

[spacer]

003 002

Fig. 3-75, (p. 3-107)

Reset of the following memories:

All counters

LED indicators

Operating data memory

All event memories

Event counters

Fault data

Measured overload data

Recorded fault values

MAIN: Re s e t indicat. USE R


0: don't execute

[spacer]

Logic Diagram

MAIN: General re s et USER


0: don't execute

[spacer]

Unit

021 010

Fig. 3-75, (p. 3-107)

Reset of the following displays:

LED indicators

Fault data

MAIN: Rs e t .lat ch.t rip US ER


0: don't execute

021 005

Fig. 3-318, (p. 3-403)

[spacer]

Reset of latched trip commands from the local control panel.

[spacer]

MAIN: Re s e t c. cl/ t r. cUS ER


0: don't execute

003 007

Fig. 3-65, (p. 3-95)


Fig. 3-73, (p. 3-103)

[spacer]

The counters for counting the close and trip commands are reset.

[spacer]

MAIN: Re s e t IP,max,s t .USER


0: don't execute

003 033

Fig. 3-44, (p. 3-74)

[spacer]

The display of the stored maximum phase current is reset.

[spacer]

MAIN: Re s e t m eas .v. en.USE R


0: don't execute

003 032

Fig. 3-56, (p. 3-85)

[spacer]

The display of active and reactive energy output and input is reset.

[spacer]

MAIN: Group res e t 1 USER


0: don't execute

[spacer]

Fig. 3-76, (p. 3-107)

MAIN: Group res e t 2 USER


0: don't execute

[spacer]

005 253

005 254

Fig. 3-76, (p. 3-107)

Group of resetting commands.

P437/EN M/R-11-A // P437311650

8-135

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

MAIN: Man. trip cmd. US ER

003 040

0: don't execute
[spacer]

A 100 ms trip command is issued from the local control panel.


Note: The command is only executed if the manual trip command has been
configured as trip command 1 or 2.

[spacer]

MAIN: En.m an.clos .cmd.USE R

003 105

0: No
[spacer]

Setting the enable for the issue of a close command from the local control panel
(enables manual breaker close operations).

[spacer]

MAIN: Man.trip cmd. A US E R

003 017

0: don't execute
[spacer]

MAIN: Man.trip cmd. B USE R

003 018

0: don't execute
[spacer]

MAIN: Man.trip cmd. C US E R

003 019

0: don't execute
[spacer]

A phase-selective trip command is issued from the local control panel for
100 ms.

[spacer]

MAIN: Man. clos e cmd. US ER


0: don't execute

018 033

Fig. 3-65, (p. 3-95)

[spacer]

A close command is issued from the local control panel for the set reclose
command time.

[spacer]

MAIN: Sof t War m re st art

003 039

0: don't execute
[spacer]

A warm restart of the software is carried out. The device functions as it does
when the power supply is turned on, except that no hardware tests are carried
out.

[spacer]

MAIN: Warm re star t

010 166

0: don't execute
[spacer]

A warm restart is carried out. The device functions as it does when the power
supply is turned on.

[spacer]

MAIN: Sof t Cold re star t

000 085

0: don't execute
[spacer]

8-136

A cold restart of the software is carried out. This means that all settings and
recordings are cleared, but no tests of the hardware are carried out during the
restart. Parameter values used by the P437 after a cold restart have been
selected in such a manner that the P437 is blocked after a cold restart.

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

MAIN: Cold rest art

009 254

0: don't execute
[spacer]

A cold restart is carried out. A cold restart means that all settings and recordings
are cleared. Parameter values used by the P437 after a cold restart have been
selected in such a manner that the P437 is blocked after a cold restart.
Parameter
Default

Operating data
recording

Address
Min

Max

Unit

OP_R C: Res e t record. USE R

100 001

0: don't execute
[spacer]

Logic Diagram

Fig. 3-81, (p. 3-116)

The operating data memory and the counter for operation signals are reset.
Parameter
Default

Monitoring signal
recording

Address
Min

Max

Unit

MT _RC: Res et record. USE R

003 008

0: don't execute
[spacer]

Logic Diagram

Fig. 3-82, (p. 3-117)

Reset of the monitoring signal memory.


Parameter
Default

Overload recording

Address
Min

Unit

Logic Diagram

OL_RC: R e s et rec ord. US E R


0: don't execute

[spacer]

Max

100 003

Fig. 3-86, (p. 3-121)

Reset of the overload memory.

P437/EN M/R-11-A // P437311650

8-137

P437

8 Information and Control Functions

Parameter
Default

Fault recording

Address
Min

Max

Unit

Logic Diagram

FT_RC: Trigg er US E R

003 041

0: don't execute

Fig. 3-93, (p. 3-131)

[spacer]

Fault recording is enabled from the local control panel for 500 ms.

[spacer]

FT_RC: Res et record. USE R

003 006

0: don't execute
[spacer]

Fig. 3-94, (p. 3-132)

Reset of the following memories:

LED indicators

Fault memory

Fault counter

Fault data

Recorded fault values

Parameter
Default

Power swing
blocking

PSB: R e se t counters

Address
Min

Max

Unit

Logic Diagram
006 029

0: don't execute
[spacer]

8-138

Reset of the counters that are used for the enhanced counting-based tripping.

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Protective signaling

Address
Min

Max

Unit

Logic Diagram

PSIG: Enab le USE R


0: don't execute

003 132

Fig. 3-156, (p. 3-213)

[spacer]

Protective signaling is enabled from the local control panel.

[spacer]

PSIG: Dis able US ER


0: don't execute

003 131

Fig. 3-156, (p. 3-213)

[spacer]

Protective signaling is disabled from the local control panel.

[spacer]

PSIG: Tes t telecom. USE R


0: don't execute

[spacer]

A send signal is issued for 500 ms.

[spacer]

PSIG: Tes t telecom. 1 US ER


0: don't execute

[spacer]

015 027

Fig. 3-184, (p. 3-239)


015 028

Fig. 3-184, (p. 3-239)

PSIG: Tes t telecom. 3 US ER


0: don't execute

[spacer]

Fig. 3-184, (p. 3-239)

PSIG: Tes t telecom. 2 US ER


0: don't execute

[spacer]

015 009

015 029

Fig. 3-184, (p. 3-239)

A channel-selective send signal is issued for 500 ms.

P437/EN M/R-11-A // P437311650

8-139

P437

8 Information and Control Functions

Parameter
Default

Auto-reclosing
control

Address
Min

Max

Unit

Logic Diagram

ARC: Enable US ER
0: don't execute

003 134

Fig. 3-186, (p. 3-242)

[spacer]

The auto-reclosing control function is enabled from the local control panel.

[spacer]

ARC: Disable USER


0: don't execute

003 133

Fig. 3-186, (p. 3-242)

[spacer]

The auto-reclosing control function is disabled from the local control panel.

[spacer]

ARC: T est- HS R A USE R


0: don't execute

[spacer]

A test HSR is triggered in phase A.

[spacer]

ARC: T est- HS R B USE R


0: don't execute

[spacer]

A test HSR is triggered in phase B.

[spacer]

ARC: T est- HS R C USE R


0: don't execute

011 063

Fig. 3-196, (p. 3-257)

011 064

Fig. 3-196, (p. 3-257)

011 065

Fig. 3-196, (p. 3-257)

[spacer]

A single pole test HSR is triggered with phase selectivity.

[spacer]

ARC: T est HS R A-B- C US ER


0: don't execute

[spacer]

A three-pole test HSR is triggered.

[spacer]

ARC: R ese t counte rs US ER


0: don't execute

[spacer]

8-140

011 066

Fig. 3-196, (p. 3-257)

003 005

Fig. 3-205, (p. 3-272)

The ARC counters are reset.

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Automatic
synchronism check

Address
Min

Max

Unit

Logic Diagram

ASC: Enab le USER


0: don't execute

003 136

Fig. 3-207, (p. 3-274)

[spacer]

Automatic synchronism check is enabled from the local control panel.

[spacer]

ASC: Disable USER


0: don't execute

003 135

Fig. 3-207, (p. 3-274)

[spacer]

Automatic synchronism check is disabled from the local control panel.

[spacer]

ASC: AR close re qu. US E R


0: don't execute

008 238

Fig. 3-210, (p. 3-277)

[spacer]

A close request is issued with Automatic Reclose parameters. This will trigger
the ASC functional operation. A close command is transmitted to the CB if the
check of the ASC is positive.

[spacer]

ASC: MC clos e r e qu. USE R


0: don't execute

018 004

Fig. 3-209, (p. 3-276)

[spacer]

A close request is issued from the integrated local control panel. This will trigger
the ASC functional operation. A close command is transmitted to the CB if the
check of the ASC is positive.

[spacer]

ASC: Te s t AR clos e r .US ER


0: don't execute

008 237

Fig. 3-210, (p. 3-277)

[spacer]

A close request is issued with Automatic Reclose parameters. This will trigger
the ASC functional operation. No close command is transmitted to the CB if the
check of the ASC is positive. Only a signal is issued.

[spacer]

ASC: Te s t M C clos e r US ER
0: don't execute

018 005

Fig. 3-209, (p. 3-276)

[spacer]

A close request is issued from the integrated local control panel. This will trigger
the ASC functional operation. No close command is transmitted to the CB if the
check of the ASC is positive. Only a signal is issued.

[spacer]

ASC: R es et coun ter s US ER


0: don't execute

[spacer]

003 089

Fig. 3-219, (p. 3-289)

The ASC counters are reset.

P437/EN M/R-11-A // P437311650

8-141

P437

8 Information and Control Functions

Parameter
Default

Ground fault (shortcircuit) protection

Address
Min

Max

Unit

Logic Diagram

GFS C: Enable USER

003 138

0: don't execute

Fig. 3-220, (p. 3-291)

[spacer]

Ground fault (short-circuit) protection is enabled from the local control panel.

[spacer]

GFS C: Dis able US ER

003 137

0: don't execute
[spacer]

Fig. 3-220, (p. 3-291)

Ground fault (short-circuit) protection is disabled from the local control panel.
Parameter
Default

Ground fault (shortcircuit) protection


signaling

Address
Min

Max

Unit

Logic Diagram

GSCSG: Enable US ER

003 140

0: don't execute

Fig. 3-238, (p. 3-310)

[spacer]

Ground fault (short-circuit) protection signaling is enabled from the local control
panel.

[spacer]

GSCSG: Disab le USER

003 139

0: don't execute

Fig. 3-238, (p. 3-310)

[spacer]

Ground fault (short-circuit) protection signaling is disabled from the local control
panel.

[spacer]

GSCSG: T es t telecom. USE R

023 086

0: don't execute
[spacer]

Fig. 3-248, (p. 3-322)

A send signal is issued for 500 ms.


Parameter
Default

Thermal overload
protection

8-142

Min

Max

Unit

Logic Diagram

THER M : R e s et re pli ca USER


0: don't execute

[spacer]

Address

022 061

Fig. 3-278, (p. 3-358)

Resetting the thermal replica of the thermal overload protection function.

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Address
Min

Max

Unit

Logic Diagram

f<> : R es e t me as.val. US E R
Over-/
underfrequency pro
tection

003 080

0: don't execute
[spacer]

Resetting the measured event values f<>: M ax. frequ. for


f> and f<>: Min. fre qu. for f<.
Parameter
Default

Circuit breaker
failure protection

Address
Min

Max

Unit

Logic Diagram

CBF: Enable US ER
0: don't execute

003 016

Fig. 3-312, (p. 3-396)

[spacer]

Circuit breaker failure protection is enabled from the local control panel.

[spacer]

CBF: Disable USER


0: don't execute

[spacer]

003 015

Fig. 3-312, (p. 3-396)

Circuit breaker failure protection is disabled from the local control panel.

P437/EN M/R-11-A // P437311650

8-143

P437

8 Information and Control Functions

Parameter
Default

Address
Min

Max

Unit

Logic Diagram

CBM: I nitialize value s


Circuit breaker
condition monitoring

003 011

0: don't execute
[spacer]

Values are initialized to trigger circuit breaker condition monitoring.

[spacer]

CBM: Blocking USER

022 150

0: No

Fig. 3-328, (p. 3-414)

[spacer]

Setting for temporary blocking of circuit breaker monitoring during protection


injection testing.

[spacer]

CBM: R e se t m eas .val . USER

003 013

0: don't execute
[spacer]

Resetting circuit breaker condition monitoring

[spacer]

CBM: S e t No. CB oper. A


Blocked

[spacer]

[spacer]

Set the number of CB operations.

[spacer]

CBM: S e t remain. CB op. A


Blocked

[spacer]

Set the remaining CB operations.

[spacer]

CBM: S e t Itrip A
Blocked

65000

Fig. 3-325, (p. 3-412)


022 135

65000
022 136

65000

022 137

65000

Inom,CB

Fig. 3-325, (p. 3-412)


022 138

65000

Inom,CB
022 139

65000

Inom,CB
022 140

65000

Inom,CB** Fig. 3-325, (p. 3-412)


2

CBM: S e t Itrip** 2 B
Blocked

8-144

022 134

CBM: S e t Itrip** 2 A
Blocked

[spacer]

65000

CBM: S e t Itrip C
Blocked

[spacer]

022 133

CBM: S e t Itrip B
Blocked

[spacer]

65000

CBM: S e t remain. CB op. C


Blocked

[spacer]

022 132

CBM: S e t remain. CB op. B


Blocked

[spacer]

Fig. 3-325, (p. 3-412)

CBM: S e t No. CB oper. C


Blocked

[spacer]

65000

CBM: S e t No. CB oper. B


Blocked

[spacer]

022 131

022 141

65000

Inom,CB**
2

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Logic Diagram
022 142

65000

Inom,CB**
2
022 143

0.0

4000.0

kAs

Fig. 3-325, (p. 3-412)


022 144

0.0

4000.0

kAs

CBM: S e t I*t C
Blocked

[spacer]

Unit

CBM: S e t I*t B
Blocked

[spacer]

Max

CBM: S e t I*t A
Blocked

[spacer]

Min

CBM: S e t Itrip **2 C


Blocked

[spacer]

Address

022 145

0.0

4000.0

kAs

Set the limit values for the ruptured currents and their squares. (An alarm is
displayed if these limit values are exceeded.)
Parameter
Default

Address
Min

Max

Unit

Logic Diagram

Programmable Logic LOGIC: Trigger 1


0: don't execute
[spacer]

034 038

Fig. 3-336, (p. 3-424)

LOGIC: Trigger 2

034 039

0: don't execute
[spacer]

LOGIC: Trigger 3

034 040

0: don't execute
[spacer]

LOGIC: Trigger 4

034 041

0: don't execute
[spacer]

LOGIC: Trigger 5

034 042

0: don't execute
[spacer]

LOGIC: Trigger 6

034 043

0: don't execute
[spacer]

LOGIC: Trigger 7

034 044

0: don't execute
[spacer]

LOGIC: Trigger 8
0: don't execute

[spacer]

034 045

Fig. 3-336, (p. 3-424)

Intervention in the logic at the appropriate point by a 100 ms pulse.

P437/EN M/R-11-A // P437311650

8-145

P437

8 Information and Control Functions

Parameter
Default

Binary counts

Address
Min

Max

Unit

COUNT : Transm it count s USE R

217 008

0: don't execute
[spacer]

Count transmission.

[spacer]

COUNT : Re s e t USE R

Fig. 3-345, (p. 3-431)

217 003

0: don't execute
[spacer]

8.1.3

Logic Diagram

Fig. 3-345, (p. 3-431)

Count reset.

Operating Data Recording


Parameter
Default

Operating data
recording

Min

Max

Unit

Logic Diagram

OP_R C: Ope rat. data re cor d.


0

[spacer]

Address

003 024

1000

Fig. 3-81, (p. 3-116)

Point of entry into the operating data log.


Parameter
Default

Monitoring signal
recording

8-146

Min

Max

Unit

Logic Diagram

MT _RC: Mon. s ignal rec ord.


0

[spacer]

Address

003 001

30

Fig. 3-82, (p. 3-117)

Point of entry into the monitoring signal log.

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

8.2

Events

8.2.1

Event Counters
Parameter
Default

InterMiCOM
interface

Max

Unit

Logic Diagram
120 042

65535

COMM 4: No. t ele gram er ror s


0

[spacer]

Min

COMM 3: No. t ele gram er ror s


0

[spacer]

Address

122 042

65535

Number of corrupted telegrams.

P437/EN M/R-11-A // P437311650

8-147

P437

8 Information and Control Functions

Parameter
Default

Main function

Address
Min

Max

Unit

Logic Diagram

MAIN: No. g ene ral s tart .

004 000

0: don't execute
[spacer]

Number of general starting signals.

[spacer]

MAIN: No. g en.tri p cmds . 1

Fig. 3-66, (p. 3-96)

004 006

0: don't execute
[spacer]

Number of general trip commands 1.

[spacer]

MAIN: No. t rip cmds. 1, A

Fig. 3-73, (p. 3-103)

005 006

0: don't execute
[spacer]

Fig. 3-73, (p. 3-103)

MAIN: No. t rip cmds. 1, B

005 007

0: don't execute
[spacer]

Fig. 3-73, (p. 3-103)

MAIN: No. t rip cmds. 1, C

005 008

0: don't execute
[spacer]

Number of general trip commands 1 per phase.

[spacer]

MAIN: No. g en.tri p cmds . 2

Fig. 3-73, (p. 3-103)

009 050

0: don't execute
[spacer]

Number of general trip commands 2.

[spacer]

MAIN: No. f inal t rip c mds .

Fig. 3-73, (p. 3-103)

004 005

0: don't execute
[spacer]

Number of final trip commands.

[spacer]

MAIN: No. close c ommands

Fig. 3-73, (p. 3-103)

009 055

0: don't execute
[spacer]

Number of close commands.

[spacer]

MAIN: No.overfl.act.e n. out

009 090

0: don't execute
[spacer]

Fig. 3-56, (p. 3-85)

Counter for the number of times the measuring range of the active energy
output was exceeded.
Note: The maximum value of this counter is 10000.

[spacer]

MAIN: No.overfl.act.e n. inp

009 091

0: don't execute
[spacer]

Fig. 3-56, (p. 3-85)

Counter for the number of times the measuring range of the active energy input
was exceeded.
Note: The maximum value of this counter is 10000.

8-148

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

MAIN: No.ov/f l.re ac.e n.out

009 092

0: don't execute
[spacer]

Logic Diagram

Fig. 3-56, (p. 3-85)

Counter for the number of times the measuring range of the reactive energy
output was exceeded.
Note: The maximum value of this counter is 10000.

[spacer]

MAIN: No.ov/f l.re ac.e n.inp

009 093

0: don't execute
[spacer]

Fig. 3-56, (p. 3-85)

Counter for the number of times the measuring range of the reactive energy
input was exceeded.
Note: The maximum value of this counter is 10000.
Parameter
Default

Operating data
recording

Min

Max

Unit

Logic Diagram

OP_R C: No. oper. data sig.


0

[spacer]

Address

100 002

1000

Fig. 3-81, (p. 3-116)

Number of signals stored in the operating data memory.


Parameter
Default

Monitoring signal
recording

Min

Max

Unit

Logic Diagram

MT _RC: No. m onit. signals


0

[spacer]

Address

004 019

30

Fig. 3-82, (p. 3-117)

Number of signals stored in the monitoring signal memory.


Parameter
Default

Overload recording

Min

Max

Unit

Logic Diagram

OL_RC: No. overload


0

[spacer]

Address

004 101

9999

Fig. 3-85, (p. 3-120)

Number of overload events.

P437/EN M/R-11-A // P437311650

8-149

P437

8 Information and Control Functions

Parameter
Default

Fault recording

Address
Min

Unit

004 020

[spacer]

Number of faults.

[spacer]

FT_RC: No. sys te m dis t urb.


0

9999

Fig. 3-93, (p. 3-131)

004 010

9999

Fig. 3-93, (p. 3-131)

Number of system disturbances.


Parameter
Default

Power swing
blocking

Logic Diagram

FT_RC: No. of f aults


0

[spacer]

Max

Address
Min

Max

PSB: No. s tab . PSwi ng

Unit

Logic Diagram
006 025

0: don't execute
[spacer]

Number of stable power swing trajectories.

[spacer]

PSB: No. OO S-S wi ng

006 026

0: don't execute
[spacer]

8-150

Number of unstable power swings.

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Auto-reclosing
control

Address
Min

Max

Unit

ARC: No. of HSR A

004 001

0: don't execute

Fig. 3-205, (p. 3-272)

[spacer]

Number of high-speed reclosures in phase A.

[spacer]

ARC: No. of HSR B

004 002

0: don't execute

Fig. 3-205, (p. 3-272)

[spacer]

Number of high-speed reclosures in phase B.

[spacer]

ARC: No. of HSR C

004 003

0: don't execute

Fig. 3-205, (p. 3-272)

[spacer]

Number of high-speed reclosures in phase C.

[spacer]

ARC: No. of HSR A-B - C

004 004

0: don't execute

Fig. 3-205, (p. 3-272)

[spacer]

Number of three-pole high-speed reclosures.

[spacer]

ARC: Num be r T DR

004 008

0: don't execute
[spacer]

Logic Diagram

Fig. 3-205, (p. 3-272)

Number of time-delay reclosures.


Parameter
Default

Automatic
synchronism check

Address
Min

Max

Unit

ASC: No. R C aft. man.clos


0: don't execute

[spacer]

Number of reclosures after a manual close request.

[spacer]

ASC: No. clos e re que st s


0: don't execute

[spacer]

Number of close requests.

[spacer]

ASC: No. clos e re je ct ions


0: don't execute

[spacer]

Logic Diagram
004 009

Fig. 3-219, (p. 3-289)

009 033

Fig. 3-219, (p. 3-289)

009 034

Fig. 3-219, (p. 3-289)

Number of close rejections.

P437/EN M/R-11-A // P437311650

8-151

P437

8 Information and Control Functions

Parameter
Default

Ground fault (shortcircuit) protection

Address
Min

Max

Unit

Logic Diagram

GFS C: No. of trip s ignals

009 054

0: don't execute
[spacer]

Fig. 3-236, (p. 3-308)

Number of trip signals.


Parameter
Default

Address
Min

Max

Unit

Logic Diagram

CBM: No. of CB ope r. A


Circuit breaker
condition monitoring
0
[spacer]

65000

Fig. 3-325, (p. 3-412)

CBM: No. of CB ope r. B


0

[spacer]

008 011

008 012

65000

CBM: No. of CB ope r. C


0

008 013

65000

[spacer]

Number of mechanical switching operations made.

[spacer]

CBM: R e main. No. CB op. A


30000

[spacer]

8-152

Fig. 3-325, (p. 3-412)


008 015

65000

CBM: R e main. No. CB op. C


30000

[spacer]

65000

CBM: R e main. No. CB op. B


30000

[spacer]

008 014

008 016

65000

Number of remaining switching operations (as shown by evaluating wear with


reference to the CB wear characteristic).

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

8.2.2

Measured Event Data


Parameter
Default

Fault data
acquisition

Address
Min

Max

Unit

Logic Diagram

FT_DA: Fault d uration


Not measured

0.0

[spacer]

Display of the fault duration.

[spacer]

FT_DA: Running t ime


Not measured

008 010

6500.0

Fig. 3-87, (p. 3-122)

004 021

0.00

[spacer]

Display of the running time.

[spacer]

FT_DA: Fault t ype

65.00

Fig. 3-87, (p. 3-122)

010 198

....: Not measured


[spacer]

Display of the fault type. This value is determined from the starting signals of
the function group MAIN.

[spacer]

FT_DA: Me as . loop s ele ct e d

004 079

....: Not measured

Fig. 3-91, (p. 3-128)

[spacer]

Display of the measuring loop selected for determination of fault data.

[spacer]

FT_DA: Fault curre nt P prim


Not measured

25000

010 199

[spacer]

Display of the fault current as a primary quantity.

[spacer]

FT_DA: Fault curre nt P p.u.


Not measured

0.00

100.00

[spacer]

Display of the fault current referred to Inom.

[spacer]

FT_DA: Flt.volt . PG/ P P prim


Not measured

0.0

2500.0

004 025

Inom

010 217

kV

[spacer]

Display of the fault voltage as a primary quantity.

[spacer]

FT_DA: Flt.volt . PG/ P P p.u.


Not measured

0.000

004 026

3.000

Vnom

[spacer]

Display of the fault voltage referred to Vnom.

[spacer]

FT_DA: Fault loop angle P


Not measured

-180

[spacer]

Display of the fault angle.

[spacer]

FT_DA: Fault curr. N p.u.


Not measured

[spacer]

0.00

Fig. 3-91, (p. 3-128)

Fig. 3-91, (p. 3-128)

004 024

180

Fig. 3-91, (p. 3-128)

004 049

100.00

Inom

Fig. 3-91, (p. 3-128)

Display of the ground fault current referred to IN,nom.

P437/EN M/R-11-A // P437311650

8-153

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

FT_DA: Fault curr. N pri m.


Not measured

010 216

25000

[spacer]

Display of the ground fault current as a primary quantity.

[spacer]

FT_DA: Fault cur.N,par pr im


Not measured

[spacer]

25000

012 242

FT_DA: Fault curr.N,par p.u


Not measured

0.00

100.00

004 059

Inom

Fig. 3-91, (p. 3-128)

[spacer]

Display of the ground fault current of the parallel line (as a primary quantity or
referred to IN,par,nom, respectively).

[spacer]

FT_DA: Fault loop angle N


Not measured

-180

[spacer]

Display of the ground fault angle.

[spacer]

FT_DA: Fault react ., pr im.


Not measured

-320.00

004 048

180

Fig. 3-91, (p. 3-128)

004 029

320.00

Fig. 3-91, (p. 3-128)

[spacer]

Display of the fault reactance as a primary quantity.

[spacer]

FT_DA: Fault react ance, se c.


Not measured

-320.00

320.00

004 028

Fig. 3-91, (p. 3-128)

[spacer]

Display of the fault reactance as a secondary quantity.

[spacer]

FT_DA: Fault im pedance , s e c


Not measured

0.00

320.00

004 023

Fig. 3-91, (p. 3-128)

[spacer]

Display of the fault impedance as a secondary quantity.

[spacer]

FT_DA: Fault locat. pe rce nt


Not measured

-320.00

320.00

004 027

Fig. 3-92, (p. 3-129)

[spacer]

Display of the fault location of the last fault (in %) referred to the setting at
FT_DA: Line reactance P S x.

[spacer]

FT_DA: Fault location


Not measured

[spacer]

8-154

-500.0

004 022

500.0

km

Fig. 3-92, (p. 3-129)

Display of the fault location of the last fault in km.

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Automatic
synchronism check

Max

Unit

Logic Diagram
004 087

0.000

3.000

Vnom

ASC: Volt. se l. me as. loop


Not measured

[spacer]

Min

ASC: Voltage Vref


Not measured

[spacer]

Address

0.000

004 088

3.000

Vnom

ASC: Volt. m agn. diff.


Not measured

-3.000

004 091

3.000

Vnom

Fig. 3-215, (p. 3-285)


Fig. 3-216, (p. 3-286)

[spacer]

Display of the difference between amplitudes of the measurement loop voltage


and the reference voltage during a close request, referred to Vnom. The display
only appears if ASC is operating.

[spacer]

ASC: Angle dif fe re nce


Not measured

-180.0

004 089

180.0

Fig. 3-215, (p. 3-285)


Fig. 3-216, (p. 3-286)

[spacer]

Display of the angle difference between measured voltage and reference


voltage at the time of the close request (in degrees).
This display only appears when the automatic synchronism check function is
active.

[spacer]

ASC: Fre qu. dif fe re nce


Not measured

-5.00

004 090

5.00

Hz

Fig. 3-215, (p. 3-285)


Fig. 3-216, (p. 3-286)

[spacer]

Display of the frequency difference between measured voltage and reference


voltage at the time of the close request (in Hz). This display only appears when
the automatic synchronism check function is active.
Parameter
Default

Ground fault (shortcircuit) protection

Min

Max

Unit

Logic Diagram

GFS C: Angle VNG/ IN


Not measured

[spacer]

Address

009 098

360

Fig. 3-235, (p. 3-307)

Angle between residual current and neutral-displacement voltage when triggers


IN> and VNG> are both operating.
This display only appears when the ground fault (short-circuit) protection
function is active.

P437/EN M/R-11-A // P437311650

8-155

P437

8 Information and Control Functions

Parameter
Default

Definite-time over
current protection

Min

Max

Unit

Logic Diagram

DTOC: Angle VNG/IN


Not measured

[spacer]

Address

009 004

360

Fig. 3-255, (p. 3-329)

Angle between the residual current and the neutral-point displacement voltage.
Parameter
Default

Address
Min

Max

Unit

Logic Diagram

f<> : M ax. frequ. for f>


Over-/
underfrequency pro
tection
Not measured

12.00

005 002

70.00

Hz

[spacer]

Maximum frequency during an overfrequency condition.

[spacer]

f<> : M in. frequ. for f<


Not measured

[spacer]

8-156

12.00

005 001

70.00

Hz

Minimum frequency during an underfrequency condition.

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Address
Min

Max

Unit

Logic Diagram

CBM: I tr ip,p rim A


Circuit breaker
condition monitoring
Not measured
[spacer]

65000

A
009 214

65000

A
009 047

0.00

100.00

Inom,CB

009 048

0.00

100.00

Inom,CB
009 049

0.00

100.00

Inom,CB
009 051

0.0

6000.0

Inom,CB** Fig. 3-325, (p. 3-412)


2
009 052

0.0

6000.0

Inom,CB**
2

CBM: I tr ip** 2 C
Not measured

009 053

0.0

6000.0

Inom,CB**
2

[spacer]

Ruptured currents and their squared values.

[spacer]

CBM: Itr ip A
0

[spacer]

009 071

65000

Inom,CB

Fig. 3-325, (p. 3-412)

CBM: Itr ip B
0

[spacer]

Fig. 3-325, (p. 3-412)

CBM: I tr ip** 2 B
Not measured

[spacer]

CBM: I tr ip** 2 A
Not measured

[spacer]

009 213

CBM: I tr ip C
Not measured

[spacer]

Fig. 3-325, (p. 3-412)

CBM: I tr ip B
Not measured

[spacer]

CBM: I tr ip A
Not measured

[spacer]

65000

CBM: I tr ip,p rim C


Not measured

[spacer]

CBM: I tr ip,p rim B


Not measured

[spacer]

009 212

009 073

65000

Inom,CB

CBM: Itr ip C
0

009 076

65000

Inom,CB

[spacer]

Sum of the per-unit ruptured currents for each circuit breaker contact.

[spacer]

CBM: Itr ip **2 A


0

[spacer]

009 077

65000

Inom,CB** Fig. 3-325, (p. 3-412)


2

CBM: Itr ip **2 B


0

P437/EN M/R-11-A // P437311650

009 078

65000

Inom,CB**
2

8-157

P437

8 Information and Control Functions

Parameter
Default
[spacer]

Address
Min

Max

Unit

Logic Diagram

CBM: Itr ip **2 C


0

009 079

65000

Inom,CB**
2

[spacer]

Sum of the squared per-unit ruptured currents for each circuit breaker contact.

[spacer]

CBM: I *t A
Not measured

[spacer]

60000

As

Fig. 3-325, (p. 3-412)

CBM: I *t B
Not measured

[spacer]

009 061

009 062

60000

As

CBM: I *t C
Not measured

009 063

60000

As

[spacer]

Current-time integral of the per-unit ruptured current for each circuit breaker
contact.

[spacer]

CBM: I* t A
0.0

[spacer]

8-158

4000.0

kAs

Fig. 3-325, (p. 3-412)


009 088

0.0

4000.0

kAs

CBM: I* t C
0.0

[spacer]

0.0

CBM: I* t B
0.0

[spacer]

009 087

009 089

0.0

4000.0

kAs

Sum of the current-time integrals of the per-unit ruptured currents for each
circuit breaker contact.

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Overload data
acquisition

Address
Min

Max

Unit

Logic Diagram

OL_DA: Ove rload dur ation


Not measured

0.0

004 102

6500.0

[spacer]

Duration of the overload event.

[spacer]

OL_DA: S tatus THERM r e pl ic a


Not measured

250

Fig. 3-83, (p. 3-118)

004 147

Fig. 3-84, (p. 3-119)

[spacer]

Display of the buffer content of the thermal overload protection function.

[spacer]

OL_DA: L oad curre nt T HERM


Not measured

0.00

3.00

004 058

Inom

Fig. 3-84, (p. 3-119)

[spacer]

Display of the load current used by the thermal overload protection function to
calculate the tripping time.

[spacer]

OL_DA: Ob ject t emp. THE RM


Not measured

-40

300

004 035

[spacer]

Display of the temperature of the protected object.

[spacer]

OL_DA: C oolant te mp. T HERM


Not measured

[spacer]

-40

215

Fig. 3-84, (p. 3-119)

004 036

Fig. 3-84, (p. 3-119)

Display of coolant temperature, dependent on the setting for THE RM: Sel ect
meas .inputPS x.
When set to Default temp. value the set temperature value will be displayed.
When set to From PT100 the temperature measured by the resistance
thermometer will be displayed. When set to From 20 mA input the temperature
measured via an external 20 mA transducer will be displayed.

[spacer]

OL_DA: Pre - trip t .le ft THE RM


Not measured

0.0

1000.0

004 148

min

Fig. 3-84, (p. 3-119)

[spacer]

Display of the time remaining before the thermal overload protection function
will reach the tripping threshold (time-to-trip).

[spacer]

OL_DA: Of fs et THERM r epl ic a


Not measured

[spacer]

-25000

25000

004 154

Fig. 3-84, (p. 3-119)

Display of the additional reserve if coolant temperature is taken into account


and if the measured coolant temperature is lower than the set maximum
permissible coolant temperature. (In this case, the thermal model has been
shifted downwards.)
If there is no coolant temperature acquisition and if the coolant temperature and
the maximum permissible coolant temperature have been set to the same
value, then the coolant temperature is not taken into account and the
characteristic is a function of the current only. The additional reserve amounts
to 0 in this case.

P437/EN M/R-11-A // P437311650

8-159

P437
8.2.3

8 Information and Control Functions

Event Recording
Parameter
Default

Overload recording

8-160

Logic Diagram

033 020

Fig. 3-86, (p. 3-121)


033 021

033 022

9999
033 023

9999
033 024

9999
033 025

9999
033 026

9999

OL_RC: Over load re cor ding 8


0

[spacer]

OL_RC: Over load re cor ding 7


0

[spacer]

Unit

9999

OL_RC: Over load re cor ding 6


0

[spacer]

OL_RC: Over load re cor ding 5


0

[spacer]

9999

OL_RC: Over load re cor ding 4


0

[spacer]

OL_RC: Over load re cor ding 3


0

[spacer]

Max

OL_RC: Over load re cor ding 2


0

[spacer]

Min

OL_RC: Over load re cor ding 1


0

[spacer]

Address

033 027

9999

Point of entry into the overload log.

P437/EN M/R-11-A // P437311650

P437

8 Information and Control Functions

Parameter
Default

Fault recording

9999

033 003

9999

033 004

9999

033 005

9999

033 006

9999

FT_RC: Fault re cor ding 8


0

[spacer]

033 002

FT_RC: Fault re cor ding 7


0

[spacer]

9999

FT_RC: Fault re cor ding 6


0

[spacer]

033 001

FT_RC: Fault re cor ding 5


0

[spacer]

Logic Diagram

9999

FT_RC: Fault re cor ding 4


0

[spacer]

Unit

003 000

FT_RC: Fault re cor ding 3


0

[spacer]

Max

FT_RC: Fault re cor ding 2


0

[spacer]

Min

FT_RC: Fault re cor ding 1


0

[spacer]

Address

033 007

9999

Point of entry into the fault log.

P437/EN M/R-11-A // P437311650

8-161

P437

8-162

8 Information and Control Functions

P437/EN M/R-11-A // P437311650

P437
9

IEC 61850 Settings via IED Configurator


This chapter lists all IEC 61850-specific settings, that are carried out with the
configuration tool IED Configurator.
The sequence in which the settings are listed and described in this chapter
corresponds to their sequence in the menu tree of the IED Configurator.
However, only those setting parameters are described that are mandatory for
establishing the IEC 61850 communication.
Further setting parameters are listed in the Settings chapter under the function
groups IEC, GOOSE, GSSE. A list of all available Logical Nodes can be found in a
separate document.

P437/EN M/R-11-A // P437311650

9-1

P437

9.1

9 IEC 61850 Settings via IED Configurator

Manage IED
The menu item Manage IED allows for establishing a connection between the
IED Configurator and the device.
The P437 features two memory banks one of which includes the active setting
parameters. The other memory bank is used with the configuration procedure for
parameters via IED Configurator or operating program.
Toggling between active and inactive memory bank is carried out either by
executing the parameter IEC: Switch Config. Bank or via IED Configurator
(after the connection has been established) by pressing the Switch Banks
button.
Parameter

Active Bank

SCL File ID
Name of the configuration bank currently valid. Setting is carried out with the
IED Configurator, after a connection with the device has been established (via
menu item Manage IED).
SCL File Version
Version number of the configuration bank currently valid. Setting is carried out
with the IED Configurator, after a connection with the device has been
established (via menu item Manage IED).

Parameter

Inactive Bank

SCL File ID
Name of the inactive configuration bank. Setting is carried out with the IED
Configurator, after a connection with the device has been established (via menu
item Manage IED).
SCL File Version
Version number of the inactive configuration bank. Setting is carried out with
the IED Configurator, after a connection with the device has been established
(via menu item Manage IED).

9-2

P437/EN M/R-11-A // P437311650

P437

9 IEC 61850 Settings via IED Configurator

9.2

IED Details
The category IED Details contains several settings that characterize the device
as well as the SCL file, which identifies the IEC 61850 configuration.

SCL Details

Parameter

Default Value

SCL File ID

PX437

Identification of the .MCL configuration file. If required, this preset value may be
modified by, for example, entering a bay name.
SCL File Version

650.230

Specific value to identify the IEC 61850 data model and configuration.
If required, this preset value may be modified by, for example, identifying the
revision states during engineering.

IED Details

Parameter

Address

Name

104 057

Explicitly assigned device name for the function in the system (IED); is part of
the Logical Device Name.
Important note: According to the IEC standard the name must consist of only
letters (A..Z, a..z), digits (0..9) and underscore characters (_), and the name
must start with a letter. Note that a non-standard name causes problems with
the IEC 61850 communication.

Parameter

Template Details

ICD Template
SCL Schema Version
Description
Type
Configuration Revision
Supported Models
The values listed in the column Template Details only provide information.
They are preset and cannot be modified.

P437/EN M/R-11-A // P437311650

9-3

P437

9.3

9 IEC 61850 Settings via IED Configurator

Communications
The category Communications contains the general network-related settings.

Connected SubNetwork

Parameter

Default Value

Connected Sub-Network

NONE

Optional name available to identify the Ethernet network.


Access Point

AP1

Part of the communications control; preset, cannot be modified.

Address
Configuration

Parameter

Default Value

Address

IP Address

0.0.0.0

104 001

Assigned IP address of the P437 for the server function in the system.
SubNet Mask

0.0.0.0

104 005

The subnet mask defines which part of the IP address is addressed by the subnetwork and which part by the device that is logged-on to the network.
Gateway Address

0.0.0.0

104 011

This parameter shows the IPv4 address of the network gateway for
communication links to clients outside of the local network.

General
Configuration

Parameter

Default Value

Media

Fibre

Network hardware provided as fiber optics (Fibre) or twisted pair copper wires
(Copper).
TCP Keepalive

5 seconds

Communication monitoring at TCP level.


Database Lock Timeout

2 minutes

Return time period for setting procedures that have commenced. (The default
value above is in seconds. The IED Configurator, however, displays converts this
to minutes.)

9-4

P437/EN M/R-11-A // P437311650

P437

9 IEC 61850 Settings via IED Configurator

9.4

SNTP
The category SNTP contains the clock synchronization settings.

9.4.1

Client Operation

General Config
Parameter

Default Value

Poll Rate (seconds)

64

Polling interval for clock synchronization.


Accepted Stratum Level

All levels (0 - 15)

Quality criterion to accept an SNTP server for clock synchronization; preset,


cannot be modified.

9.4.2

External Server 1
Settings for the primary clock synchronization server.
Note that all values except IP Address and the Use Anycast button are usually
disabled and may be accepted only when imported from an XML configuration
file.

External Server
Parameters

Parameter

Default Value

Address

IP Address

0.0.0.0

104 202

IP address of the preferred server used for clock synchronization.


Clicking the Use Anycast button in the IED Configurator changes the value
such that any server in the local network is appointed to provide clock
synchronization.

9.4.3

External Server 2
Settings for the primary clock synchronization server.
Note that all values except IP Address and the Use Anycast button are usually
disabled and may be accepted only when imported from an XML configuration
file.

External Server
Parameters

Parameter

Default Value

Address

IP Address

0.0.0.0

104 210

IP address of the backup server used for clock synchronization.


Clicking the Use Anycast button in the IED Configurator changes the value
such that any server in the local network is appointed to provide clock
synchronization.

P437/EN M/R-11-A // P437311650

9-5

P437

9.5

9 IEC 61850 Settings via IED Configurator

Dataset Definitions
Parameter

Dataset Definitions

Name
Explicitly (and uniquely) assigned name for the dataset.
Location
Saving datasets at System/LLN0 is compulsory.
Contents
Content (data objects, data attributes) of a dataset.
The GOOSE Capacity display allows for checking the length of a dataset for
less than 1500 bytes to permit transmission in GOOSE messages. The display is
irrelevant when the dataset is only used in reports.
Note: It is not possible to read the IEC configuration back from the P437 if the
Dataset sizes exceed the GOOSE size limit significantly. Therefore it is
recommended to limit the Dataset size(s) to max. 120% of the GOOSE
capacity.

9-6

P437/EN M/R-11-A // P437311650

P437

9 IEC 61850 Settings via IED Configurator

9.6

GOOSE Publishing

9.6.1

System/LLN0

Network Parameters

Parameter

Default Value

Multicast MAC Address

01-0C-CD-01-00-00

Virtual MAC address that the sending device provides as the destination; preset.
Application ID (hex)

0000

Explicitly (and uniquely) assigned ID-number of the GOOSE.


VLAN Identifier (hex)

ID-number of the virtual LAN with which the GOOSE is sent; preset.
VLAN Priority

Priority with which the GOOSE is sent in the virtual LAN; preset.

Repeat Message
Transmission
Parameters

Parameter

Default Value

Minimum Cycle Time

10 ms

First send repetition of the GOOSE occurring after the set time period; preset.
Maximum Cycle Time

1s

Continuous send repetition of the GOOSE occurring after the set time period;
preset.
Increment

900

Specification factor for the transition of time intervals for GOOSE send
repetitions from the first to the continuous repetition.

P437/EN M/R-11-A // P437311650

9-7

P437

Message Data
Parameters

9 IEC 61850 Settings via IED Configurator

Parameter

Default Value

GOOSE Identifier

TEMPLATESystem/
LLN0$GO$gcb01

GOOSE ID consisting of the Device Name and the GOOSE Control Block.
Dataset Reference
Name of the dataset assigned to the GOOSE.
Configuration Revision

Revision status of the configuration.

9-8

P437/EN M/R-11-A // P437311650

P437

9 IEC 61850 Settings via IED Configurator

9.7

GOOSE Subscribing

9.7.1

Mapped Inputs

Source Network
Parameters

Parameter

Default Value

Multicast MAC Address

01-0C-CD-01-00-00

Virtual MAC address used as a receive filter; preset.


Application ID (hex)

ID-number of the GOOSE.

P437/EN M/R-11-A // P437311650

9-9

P437

9 IEC 61850 Settings via IED Configurator

Parameter

GOOSE Source
Parameters

Default Value

Source Path
Information data attribute in the transmitting device.
GOOSE Identifier
ID of the GOOSE in the transmitting device.
Dataset Reference
Name of the dataset assigned to the GOOSE in the transmitting device.
Configuration Revision

Configuration revision status of the transmitting device.


Data Obj Index

Position index of the data object within the GOOSE.


Data Obj Type

Unknown

Structure of the data object; possible settings:

Unknown

Boolean (logical value)

Int8 (Integer, with 8 digits)

Int16 (Integer, with 16 digits)

Int32 (Integer, with 32 digits)

UInt8 (Positive integer, with 8 digits)

UInt16 (Positive integer, with 16 digits)

UInt32 (Positive integer, with 32 digits)

Float (Floating-point number)

BStr2 (Binary state, with 2 digits)

SPS (Single-pole signal)

DPS (Two-pole signal)

Quality Obj Index

Distance of the quality descriptor to the data object if not preset. The quality of
the received information is to be tested if such has been configured.

9-10

P437/EN M/R-11-A // P437311650

P437

9 IEC 61850 Settings via IED Configurator

Destination
Parameters

Parameter

Default Value

Evaluation Expression

Equal to

Criteria to check the received information content by comparing it with a set


integer value; the parameter is not supported in the device.

Equal to (Compared to: equal)

Not equal to (Compared to: unequal)

Greater than (Compared to: greater)

Less than (Compared to: less)

Pass through (Do not compare)

Default Input Value

False

Default value for the information in case GOOSE receipt has failed.

False not set

True set

Last Known Value retain last value received

Double Point: intermediate (00) switching device in intermediate position

Double Point: Off (01) switching device open

Double Point: On (10) switching device closed

Double Point: Bad state (11) switching device in intermediate position

Invalidity Quality bits


Quality criterion, which is to be tested.

Invalid / Questionable: Invalid / questionable

Source: Information source is faulty

Relay test: Sending device is set to test mode

OperatorBlocked: Blocked by operator

and

Overflow: Measured value has exceeded its capacity

OutofRange: Measured value has exceeded its range

BadReference: Referenced value is faulty

Oscillatory: Value is volatile

Failure: Faulty

OldData: Information is out-of-date

Inconsistent: Information is unreliable

Inaccurate: Information is inaccurate

P437/EN M/R-11-A // P437311650

9-11

P437

9 IEC 61850 Settings via IED Configurator

9.8

Report Control Blocks

9.8.1

System/LLN0
Parameter

Report Parameters

Default Value

Report Type
Report type:

Unbuffered (updating)

Buffered (saving)

Report ID

TEMPLATESystem/
LLN0$RP
$urcbA, ...,
TEMPLATESystem/
LLN0$RP
$urcbP, ...,
TEMPLATESystem/
LLN0$BR
$brcbA, ...,
TEMPLATESystem/
LLN0$BR$brcbH

Report ID consisting of the Device Name and the Report Control Block.
Dataset Reference
Name of the dataset assigned to the report.
Configuration Revision

Revision status of the configuration.

9-12

P437/EN M/R-11-A // P437311650

P437

9 IEC 61850 Settings via IED Configurator

9.9

Controls

9.9.1

Control Objects
Parameter

Control Object
Parameters

ctlModel
To control external devices the following operating modes can be set:

Status only (manually operated switching device)

Direct control with enhanced security (direct command issue with


extended monitoring of command effecting)

SBO (Select before operate) with enhanced security (switching device


selection procedure with extended monitoring of command effecting)

sboTimeout
Return time period after selection without issuing a command.

9.9.2

Source Network
Parameters

Uniqueness of Control
Parameter

Default Value

Multicast MAC Address

01-0C-CD-01-00-00

Virtual MAC address used as a receive filter; preset.


Application ID (hex)

ID-number of the GOOSE.

P437/EN M/R-11-A // P437311650

9-13

P437

9 IEC 61850 Settings via IED Configurator

Parameter

GOOSE Source
Parameters

Default Value

Source Path
Information data attribute in the transmitting device.
GOOSE Identifier
ID of the GOOSE in the transmitting device.
Dataset Reference
Name of the dataset assigned to the GOOSE in the transmitting device.
Configuration Revision

Configuration revision status of the transmitting device.


Data Obj Index

Position index of the data object within the GOOSE.


Default Input Value

True

Default value for the information in case GOOSE receipt has failed:

9-14

False not set

True set

Last Known Value retain last value received

Double Point: intermediate (00) switching device in intermediate position

Double Point: Off (01) switching device open

Double Point: On (10) switching device closed

Double Point: Bad state (11) switching device in intermediate position

P437/EN M/R-11-A // P437311650

P437

9 IEC 61850 Settings via IED Configurator

9.10

Measurements
Parameter

Scaling

Unit Multiplier
Multiplication factor; not supported.

Parameter

Range configuration

Scaled Measurement Range: Min


Scaled Measurement Range: Max
Lower / Upper measuring range limit value; not supported.

Deadband
Configuration

Parameter

Default Value

Deadband

100

Multiplier for the smallest display value of the measured value. In order to have
the current measured value sent when it has changed from the value last sent
the result of the set dead band value multiplied by the smallest display value
must exceed the smallest display value.

P437/EN M/R-11-A // P437311650

9-15

P437

9 IEC 61850 Settings via IED Configurator

9.11

Configurable Data Attributes

9.11.1

System/LLN0

Mod.measCyc

Parameter

Default Value

Value

Transmission of measured values: Time interval in seconds between two dead


band evaluations.

Mod.enCyc

Parameter

Default Value

Value

65535

Cyclic transmission of measured values without dead band check: Time interval
in seconds between transmissions of two energy count values.

Mod.comtrade

Parameter

Default Value

Value

BINARY

Transmission of COMTRADE fault files formatted either as ASCII or binary files.

Mod.distExtr

Parameter

Default Value

Value

true

Cancelling fault transmission or including it in the configuration.

9-16

P437/EN M/R-11-A // P437311650

P437
10

Commissioning

10.1

Safety Instructions

DANGER
Only qualified personnel, familiar with the Warning page at the beginning of
this manual, may work on or operate this device.

DANGER
When installing and connecting the device the warning notices at the
beginning of Chapter Installation and Connection (Chapter 5, (p. 5-1)) must
be observed.

DANGER
The device must be reliably grounded before auxiliary voltage is turned on.
The surface-mounted case is grounded using the bolt and nut, appropriately
marked, as the ground connection. The flush-mounted case must be
grounded in the area of the rear sidepieces at the location provided. The
cross-section of the ground conductor must conform to applicable national
standards. A minimum cross section of 2.5 mm (US:AWG12 or thicker) is
required.
In addition, a protective ground connection at the terminal contact on the
power supply module (identified by the letters PE on the terminal
connection diagram) is also required for proper operation of the device. The
cross-section of this ground conductor must also conform to applicable
national standards. A minimum cross section of 1.5 mm (US:AWG14 or
thicker) is required.

DANGER
Before working on the device itself or in the space where the device is
connected, always disconnect the device from the supply.

P437/EN M/R-11-A // P437311650

10-1

P437

10 Commissioning

DANGER
The secondary circuit of live system current transformers must not be
opened! If the secondary circuit of a live CT is opened, there is the danger
that the resulting voltages will endanger personnel and damage the
insulation.
For pin-terminal connection devices, the terminal block for connection to the
current transformers is not a shorting block. Therefore always short-circuit
current transformers before loosening the threaded terminals.

DANGER
The power supply must be turned off for at least 5 s before power supply
module V is removed. Otherwise there is the danger of an electric shock.

DANGER
When increased-safety machinery is located in a hazardous area the P437
must always be installed outside of this hazardous area.

WARNING
The fiber-optic interface may only be connected or disconnected when the
supply voltage for the device is shut off.

WARNING
The PC interface is not designed for permanent connection. Consequently,
the female connector does not have the extra insulation from circuits
connected to the system that is required per VDE 0106 Part 101. Therefore,
when connecting the prescribed connecting cable be careful not to touch the
socket contacts.

WARNING
Application of analog signals to the measuring inputs must be in compliance
with the maximum permissible rating of the measuring inputs (see Technical
Data, Chapter 2, (p. 2-1)).

10-2

P437/EN M/R-11-A // P437311650

P437

10 Commissioning

WARNING
When using the programmable logic (function group LOGIC), the user must
carry out a functional type test to conform to the requirements of the
relevant protection/control application. In particular, it is necessary to verify
that the requirements for the implementation of logic linking (by setting) as
well as the time performance during device startup, during operation and
when there is a fault (device blocking) are fulfilled.

P437/EN M/R-11-A // P437311650

10-3

P437

10 Commissioning

10.2

Commissioning Tests

10.2.1

Preparation
After the P437 has been installed and connected as described in Chapter 5, (p. 51), the commissioning procedure can begin.
Before turning on the power supply voltage, the following items must be checked
again:

Is the device connected to the protective ground at the specified location?

Does the nominal voltage of the battery agree with the nominal auxiliary
voltage of the device?

Are the current and voltage transformer connections, grounding, and phase
sequences correct?

After the wiring work is completed, check the system to make sure it is properly
isolated. The conditions given in VDE 0100 must be satisfied.
Once all checks have been made, the power supply voltage may be turned on.
After voltage has been applied, the device starts up. During startup, various
startup tests are carried out (see Section 3.14, (p. 3-113)). The LED indicators for
HEALTHY (H1) and OUT OF SERVICE (H2) will light up. After approximately 15 s,
the P437 is ready for operation. By default (factory setting) or after a cold restart,
the device type P437 and the time are displayed on the first line of the LCD
after the device has started up.
Once the change enabling command has been issued (see Section 6.11.3, (p. 618)), all settings can be entered. The procedure for entering settings from the
integrated local control panel is described in Section 6.11.4, (p. 6-21).
If either the PC interface or the communication interface will be used for setting
the P437 and reading out event records, then the following settings must first be
made from the integrated local control panel.
Par/DvID menu branch:

10-4

DV IC E: De vice pas sword 1

DV IC E: De vice pas sword 2

P437/EN M/R-11-A // P437311650

P437

10 Commissioning

Par/Conf menu branch:

PC: Bay ad dre ss

PC : D e vice addr es s

PC : Baud rat e

PC : Parit y bit

COMM1: Fun cti on grou p COMM1

CO MM1: General en able USER

COMM1: N ame of man ufactu rer

CO MM1: L ine i dle s tat e

CO MM1: Bau d r ate

C OM M1: Parity bit

COMM1: C ommu nicat. protocol

COMM1: Oct et comm. addres s

C O MM 1: Octe t addre ss ASDU

COMM2: Fu nction group COMM2

COMM2: Ge n eral e nabl e USER

COMM2: N am e of m anuf actur e r

COMM2: L ine idle s tate

C OM M2: Bau d rate

COMM2: P arity bit

COMM2: Oct e t comm. addres s

COMM2: Oct et addre ss ASD U

COMM3: Function grou p COMM3

CO MM3: Gen eral e nable USE R

COMM3: Baud rate

COMM4: Fun cti on grou p COMM4

C O MM4: Gen eral en able USER

C OM M4: Bau d rate

Par/Func/Glob menu branch:

PC : C omm and blockin g

PC: S ig./me as.val .block.

COMM1: C ommand block. USER

C O MM1: S ig ./me as .block.USE R

COMM2: Comman d block. USER

C OMM2: Sig ./meas .block.USE R

Instructions on these settings are given in Chapters Settings and Information


and Control Functions.
The settings given above apply to the IEC 60870-5-103 communication protocol. If
another protocol is being used for the communication interface, additional settings
may be necessary. See Chapter Settings for further details.

After the settings have been made, the following checks should be carried out
again before the blocking is cancelled:

P437/EN M/R-11-A // P437311650

10-5

P437

10 Commissioning

Does the function assignment of the binary signal inputs agree with the
terminal connection diagram?

Has the correct operating mode been selected for the binary signal inputs?

Does the function assignment of the output relays agree with the terminal
connection diagram?

Has the correct operating mode been selected for the output relays?

Have all settings been made correctly?

Now blocking can be cleared as follows (Par/Func/Glob menu branch):

10.2.2

MA IN: D e vice on-lin e = Yes (= on)

Tests
By using the signals and displays generated by the P437, it is possible to
determine whether the P437 is correctly set and properly interconnected with the
station. Signals are signaled by output relays and LED indicators and entered into
the event memory. In addition, the signals can be checked by selecting the
appropriate signal in the menu tree.
If the user does not wish the circuit breaker to operate during protection testing,
the trip commands can be blocked through MAI N: Trip cmd.block. USER
(Par/Func/Glob menu branch) or an appropriately configured binary signal input.
If circuit breaker testing is desired, it is possible to issue a trip command for
100 ms through MAI N: Man . tr ip cmd. USER (Oper/CtrlTest menu branch) or
an appropriately configured binary signal input. Selection of the trip command
from the integrated local control panel is password-protected (see
Section 6.11.8, (p. 6-29)).
The manual trip command is not executed unless the manual trip is included in the
selection of possible functions to effect a trip (in the configuration of trip
commands).

If the P437 is connected at substation control level, the user is advised to


activate the test mode via MA IN : Te st mode USER (Par/Func/Glob menu
branch) or an appropriately configured binary signal input. The telegrams are
then identified accordingly (reason for transmission: test mode).

10.2.3

Checking the Binary Signal Inputs


By selecting the corresponding state signal (Oper/Cycl/Phys menu branch), it is
possible to determine whether the input signal that is present is recognized
correctly by the device. The values displayed have the following meanings:

"Low": Not energized.

"High": Energized.

Without function: No functions are assigned to the binary signal input.

This display appears regardless of the binary signal input mode selected.

10.2.4

Checking the Output Relays


It is possible to trigger the output relays for a settable time period for test
purposes (time setting at OUTP: Hold-ti me f or test in Oper/CtrlTest menu
branch). First select the output relay to be tested (OUTP: Relay assign.
f.test, Oper/CtrlTest menu branch).
Test triggering then occurs via OU TP : R elay te st (Oper/CtrlTest menu branch).
It is password-protected (see Section 6.11.8, (p. 6-29)).

10-6

P437/EN M/R-11-A // P437311650

P437

10 Commissioning

WARNING
Before starting the test, open any triggering circuits for external devices so
that no inadvertent switching operations will take place.

10.2.5

Checking the Communications Interfaces Signals


When using the IEC 608705103, IEC 8705101 or ILSC interface protocols,
each signal generated in the P437 can be transmitted to the connected control
station for test purposes. First select the signal to be tested
(C OM M1: Sel.spon tan .s ig.tes t, CO MM2: Sel .spontan.sig.te st, menu
branch Oper/CtrlTest).
The respective signal is transmitted according to CO MM1: Test
spont .sig .st art or C OMM1 : Te st s pont.s ig. en d (or COMM2: Te st
spont.sig.st art, COMM2 : Te st s pont.s ig. en d, all in menu branch Oper/
CtrlTest).
Signal generation is password-protected (see Section 6.11.8, (p. 6-29)).

10.2.6

Checking the Protection Function


Four parameter subsets are stored in the P437, one of which is activated. Before
checking the protective function, the user should determine which parameter
subset is activated. The active parameter subset is displayed at PSS: Act ual
p ar am . subset (Oper/Cycl/Log menu branch).

10.2.6.1

Checking Distance Protection


Before checking the distance protection function using a single-phase testing
device, disable the measuring circuit monitoring function (MC MON: Ena ble d,
Oper/Cycl/Log menu branch) and the fuse failure monitoring function
(MC MON: FF, V e nabl e d USE R, Par/Func/Gen menu branch) since they would
otherwise always operate and block distance protection after the set operate
delay had elapsed. Furthermore, the signal at the binary signal input configured
for MAI N: M.c.b . tri p V E XT must have a logic value of 0.

10.2.6.1.1

Checking Starting
The starting settings can be illustrated in a V-I diagram (see Fig. 10-1, (p. 108)). The slope of the impedance line plotted in the V-I diagram is a function of
the settings for underimpedance starting and the phase displacement between
the measured values (see Fig. 10-2, (p. 10-9)).

P437/EN M/R-11-A // P437311650

10-7

P437

10 Commissioning

V/Vnom(/3)

1.0

DIST:
V< PSx
[*]
0.5

DIST:
I> (Ibl) PSx
[*]

Parameter
set
set
set
set

1
2
3
4

DIST:
I>> PSx
[*]

1.0

DIST:
V< PSx
010
010
011
011

069
089
009
029

DIST:
I> (Ibl) PSx
010
010
011
011

068
088
008
028

2.0

I/Inom

DIST:
I>> PSx
010
010
010
011

054
074
094
014

D5Z50DFA

Fig. 10-1: Example of the starting settings in a V-I diagram.

Checking I>(Imin), V< and I>>:


The phase displacement between the measured values V and I should be
selected so as to be smaller than the angle set at DIST: PSx.
Checking Z<:
The phase displacement between the measured values V and I should be
selected so as to be greater than the angle set at DIST: PSx.
The measured values should be selected in accordance with the selected operate
values such that only one starting measuring system operates. Operation of the
checked starting threshold is possible by checking the phaseselective and
startingselective state signals.

10-8

P437/EN M/R-11-A // P437311650

P437

10 Commissioning

X
DIST:
Xfw PSx
[ * ]

Z<(Z)

70

L
R
DIST:
PSx
[ * ]

DIST:
Rfw,PP PSx
[ * ]
DIST:
Rfw,PG PSx
[ * ]
DIST:
Zbw/Zfw PSx
[ * ]

DIST:
Zfw,PG PSx
[ * ]
DIST:
Zfw,PP PSx
[ * ]

Parameter
set
set
set
set

1
2
3
4

DIST:
Xfw PSx
010 050
010 070
010 090
011 010

DIST:
Rfw,PG PSx
010 051
010 071
010 091
011 011

DIST:
Rfw,PP PSx
010 052
010 072
010 092
011 012

DIST:
PSx
010 063
010 083
011 003
011 023

DIST:
Zbw/Zfw PSx
010 053
010 073
010 093
011 013

DIST:
Zfw,PG PSx
010 101
010 102
010 103
011 104

DIST:
Zfw,PP PSx
010 105
010 106
010 107
011 108
D5Z52DGA

Fig. 10-2: Characteristic of underimpedance starting.

When checking underimpedance starting using single-phase test current, we


obtain the following relation for the operate condition for phase-to-phase
starting:
Vtest
Itest

= 2 Z<

| Vtest | e

jtest

| Itest | e j0

= 2 | Z< | e

jZ

For absolute value and angle this means:


| Vtest |
| Itest |

= 2 | Z< |

test = Z
where:

P437/EN M/R-11-A // P437311650

10-9

P437

10 Commissioning

Z< = Starting Impedance

Z = Impedance Angle

Vtest = Test Voltage

Itest = Test Current

test = Phase angle between test voltage and test current

In the range of the reactance limit, that is, for impedance angle Z in the range
L<Z<110, the starting impedance is calculated as follows:
| Z< | =

X fw
sinZ

Xfw = DI ST: Xfw PSx setting


The limit angle L is defined by the point of intersection of reactance and
resistance limits and is calculated as follows:
L = arctan

X fw
Rfw

Rfw = D I ST: Rfw,P G PSx or D IST: Rfw ,P P P Sx setting


If underimpedance starting is to be checked under all angle conditions, then the
starting impedances for the individual angle ranges are calculated according to
the following equations:
Angle Range

Starting Impedance

Z G

(180+) Z (180+G)

(180+G) < Z 290

| Z< | =

Rfw
cosZ

| Z< | =

Rfw
cosZ

| Z< | =

X fw
sinZ

: DIS T: PSx setting

Zbw / Zfw: DIS T: Zbw/Zf w P Sx setting

Z bw
Z fw
Z bw
Z fw

When phase-to-ground starting conditions are checked, the DIST: Z


e valuat ion PSx setting must be taken into account. If ZPG=VPG/2*IP is set,
then the equations given for phase-to-phase starting apply. If, on the other hand,
ZPG=VPG/(IP + kG*IN) is set, then the set complex ground factor kG must be
taken into account if the setting for D IST: Abs . value kG PSx is not equal to
one and/or the setting for DI ST: A ngle kG PSx is not equal to 0. When the
test is carried out using single-phase test current, the following relation for the
operate condition is obtained:
Vtest
Itest

= (1 + kG) Z<

| Vtest | e

jtest

| Itest | e j0

= (1 + | kG | e

jG

) | Z< | e

jZ

For absolute value and angle this means:


| Vtest |
| Itest |

10-10

= 1 + | kG|2 + 2 | kG | cosG | Z< |

P437/EN M/R-11-A // P437311650

P437

10 Commissioning
sinZ + | kG | sin(Z + G)
Z + | kG | cos(Z + G)

test = arctan cos


or

sintest + | kG | sin(test - G)
test + | kG | cos(test - G)

Z = arctan cos
where:

Z< = Starting Impedance

Z = Impedance Angle

|kG| = DI ST: Abs . val ue kG PSx setting

G = D IST: A ngl e kG PSx setting

Vtest = Test Voltage

Itest = Test Current

test = Phase angle between test voltage and test current

From the input measured values, the P437 calculates the residual current IN and
the neutral-displacement voltage VNG, which are used for zero-sequence starting.
They are calculated according to the following equations:
|IN| = |IA + IB + IC|
|VNG| = |VAG + VBG + VCG|
For a single-phase test where |VB-G| = |VC-G| = 0, the result of the calculation
formula for VNG given above is that the DIST: V NG> PSx or D IST: VNG>>
PSx triggers operate if the test voltage exceeds the following value:
| Vtest | = 3 V NG>

V nom
3

VNG> = setting DIS T: V N G> P Sx or DIST: VNG>> P Sx


For a single-phase test where |IB| = |IC| = 0, the following applies to currents:
|Itest| = IN>Inom
IN> = DI ST: IN > PSx setting
Operation of ground starting is only signaled by the LED indicator if starting also
operates in a phase. The operation of ground starting can be observed,
independently of the operation of phase starting, at DI ST: Zero-s equ.
st ar t ing (Oper/Cycl/Log menu branch).
The values determined by the P437 for the residual current IN and the neutralpoint displacement voltage VNG are displayed by the operating data display
(current: MAIN : C urre nt IN p. u. and voltage: MA IN : V oltage VNG p.u. in
the Oper/Cycl/Data menu branch).
10.2.6.1.2

Checking Distance and Directional Measurement


When checking the impedance zones using single-phase test current we obtain
the following relation for the operate condition for a phase-to-phase loop:
Vtest
Itest

= 2 Z<

| Vtest | e

jtest

| Itest | e j0

= 2 | Z< | e

jZ

For absolute value and angle this means:

P437/EN M/R-11-A // P437311650

10-11

P437

10 Commissioning
| Vtest |
| Itest |

= 2 | Z< |

test = Z
where:

10.2.6.1.3

Z<: Tripping Impedance

Z: Impedance Angle

Vtest: Test Voltage

Itest: Test Current

test: Phase angle between test voltage and test current

Characteristics
With the P437, the user may choose between a polygonal and a circular tripping
characteristic. This selection of the tripping characteristic will then govern
calculation of the tripping impedances.

10.2.6.1.3.1

Circle Characteristic
If the circle characteristic has been selected, the tripping impedance is set in the
P437. If the setting Arc compensation: yes has also been selected, then the
characteristic shown in the following diagram is obtained when measuring with
sinusoidal quantities.
+135
Forward direction

Zn

Z
R

Backward direction

45 315
D5Z5025A

Fig. 10-3: Impedance characteristic for distance and directional determination for the Circle setting.

The actual tripping impedance in the ranges 45 < Z < and 135 < Z < (
+180) is then calculated as follows:
|Ztrip| = |Z|(1+sin)
In the range 45 < Z < , the following relation applies: = Z
10-12

P437/EN M/R-11-A // P437311650

P437

10 Commissioning

In the range 135 < Z < (+180), the following relation applies: = Z
+180
where:
Ztrip: Actual tripping impedance
Z: settings DI ST: Z1 (ci rcl e ) P Sx to DIST: Z6 ( circle ) PSx
Z: Impedance Angle
: settings D I ST: 1 ( circle ) P Sx to DI ST: 6 ( circle) PSx
When phase-to-ground loops are checked, the set complex ground factor kG must
be taken into account if the setting for DIST: Abs . valu e k G PSx is not equal
to one and/or the setting for DIST: A n gl e kG P Sx is not equal to 0. When the
test is carried out using single-phase test current, the following relation for the
operate condition is obtained:
Vtest
Itest

= (1 + kG) Z<

| Vtest | e

jtest

| Itest | e j0

= (1 + | kG | e

jG

) | Z< | e

jZ

For absolute value and angle this means:


| Vtest |
| Itest |

= 1 + | kG|2 + 2 | kG | cosG | Z< |


sinZ + | kG | sin(Z + G)
Z + | kG | cos(Z + G)

test = arctan cos


or

sintest + | kG | sin(test - G)
test + | kG | cos(test - G)

Z = arctan cos
where:

Z<: Tripping Impedance

Z: Impedance Angle

|kG|: DI ST: Abs. valu e kG P Sx setting

G:DIS T: Angle kG PSx setting

Vtest: Test Voltage

Itest: Test Current

test: Phase angle between test voltage and test current

In impedance zone 1, the set zone extension factors kze enter into the tripping
impedance in all fault cases.
Ztrip = kze Z1
where:
Ztrip: Actual tripping impedance
kze:

DIS T: k ze,PG HSR PSx or

D IST: kze,PP H SR P Sx or

D IS T: k ze,PG TDR P Sx or

D IST: kze,PP TD R PSx setting

Z1: D IST: Z1 ( circle ) P Sx setting

P437/EN M/R-11-A // P437311650

10-13

P437

10 Commissioning

Whether the zone extension factors kze HSR are active or not is controlled by the
following protective functions:

Switch on to fault protection

An appropriately configured signal input.

Protective signaling.

If protective signaling is not ready, then control and switching to the zone
extension factor kzeTDR, if applicable, is handled by the internal auto-reclosing
function. Regardless of the readiness of protective signaling, the zone extension
factor kzeHSR may be activated during the reclose command if set accordingly.
10.2.6.1.3.2

Polygon (Quadrilateral) Characteristic


The tripping impedance is calculated in the range of the reactance limits (for
impedance angle Z this means in the range L < Z < 90) as follows:
| Z< | =

X
sinZ

X: D IST: X1 ,PG ( pol ygon ) PSx to D IST: X6, PG (polygon) PSx setting
The limit angle L is defined by the point of intersection of reactance and
resistance limits and is calculated as follows:
| L | = arctan

X
X
R + tan

R:

Settings DIS T: R1, PG ( pol ygon) P Sx

to D IS T: R 6,P G (polygon ) PSx

or D I ST: R1,PP ( polygon) P Sx

to D I ST: R6,PP (polygon ) PSx

: DIS T: 1 (pol ygon) PSx to DIST: 6 ( ci rcle) PSx

+135

DIST:
Xn
Z<

DIST:
n

Z
L

R
DIST:
Rn,PG

DIST:
Rn,PP

45
D5Z50DJA

Fig. 10-4: Impedance characteristic for distance and directional determination for the Polygon setting.

In the range of the resistance limits (for impedance angles this means in the
range of 0 < Z L), the tripping impedance is calculated according to the
following equation:

10-14

P437/EN M/R-11-A // P437311650

P437

10 Commissioning
| Z< | =

R
sinZ
cosZ - tan

When phase-to-ground loops are checked, the set complex ground factor kG
must be taken into account if the setting for DIST: Abs . valu e k G PSx is not
equal to one and/or the setting for DIST: A n gl e kG PSx is not equal to 0.
When the test is carried out using single-phase test current, the following relation
for the operate condition is obtained:
Vtest
Itest

= (1 + kG) Z<

| Vtest | e

jtest

| Itest | e j0

= (1 + | kG | e

jG

) | Z< | e

jZ

For absolute value and angle this means:


| Vtest |
| Itest |

= 1 + | kG|2 + 2 | kG | cosG | Z< |


sinZ + | kG | sin(Z + G)
Z + | kG | cos(Z + G)

test = arctan cos


or

sintest + | kG | sin(test - G)
test + | kG | cos(test - G)

Z = arctan cos
where:

Z<: Tripping Impedance

Z: Impedance Angle

|kG|: DI ST: Abs. valu e kG P Sx setting

G:DIS T: Angle kG PSx setting

Vtest: Test Voltage

Itest: Test Current

test: Phase angle between test voltage and test current

In impedance zone 1, the set zone extension factors kze enter into the tripping
impedance in all fault cases.
Rtrip = kze R1
Xtrip = kze X1
where:
Rtrip: Actual tripping resistance
Xtrip: Actual tripping reactance
kze:

setting DI ST: kze,P G H SR P Sx

or D I ST: kze ,P P H SR P Sx

or DI ST: kze,P G TDR P Sx

or D IST: kze,P P TDR PSx

R1: DIS T: R 1,P G (polygon) P Sx or DIST: R1 ,PP (polygon ) PSx setting


X1: DI ST: X1,P G (polygon) P Sx setting
Whether the kze HSR zone extension factors are active or not is controlled by the
following protective functions:

P437/EN M/R-11-A // P437311650

10-15

P437

10 Commissioning

Switch on to fault protection

An appropriately configured binary signal input.

Protective signaling.

If protective signaling is not ready, then control and switching to zone extension
factor kzeTDR, if applicable, is handled by the internal auto-reclosing function.
Regardless of the readiness of protective signaling, zone extension factor kzeHSR
may be activated during the reclose command if set accordingly.
10.2.6.1.4

Checking the Voltage Memory


The voltage stored by the voltage memory is used in certain cases for direction
determination. The voltage stored by the voltage memory is used in certain
cases for direction determination.
If the voltage memory is to be tested using a single-phase test device, checking
should only be done for an AB fault.
The voltage memory is cleared, if the following two conditions are fulfilled:

Voltage |VAB| is greater than the threshold set at


D IST: Oper.val.Vm e mory P Sx.

The frequency is in the range 0.95fnom < f < 1.05fnom .

With the starting signal, the voltage memory is decoupled from the synchronizing
voltage (VAB), and the stored voltage can be used for directional measurement
for 2 s maximum.
The P437 determines, on the basis of the magnitude of the fault voltage, whether
the direction will be determined using the fault voltage, the stored voltage, or the
set angle (D I ST: 1 (pol ygon) P Sx, , DIST: 6 ( polygon) PSx). The
following possibilities exist:
Angle for Direction Determination with:
V memory

0.002Vnom < Vmeas < D I S T : O p e r . v a l . V m e m o r y P S x

Vmeas < 0.002Vnom

Enabled

Not enabled

X: Angle determined using the stored voltage


F: Angle determined using the selected measured values
Vmeas: Selected measuring voltage
The method for determining X is described in Section 3.21, (p. 3-135).
The user can check to make sure connection to the systems current and voltage
transformers involves the correct phase by consulting the operating data
displays for load angle (MA IN: Load angle phi A, MAIN: Load angle phi B,
and MA IN : Load ang le ph i C in the Oper/Cycl/Data menu branch). The load
angles for all three phases must be approximately equal. The load angles are
only determined if at least 5% of the nominal device current is flowing.

10.2.6.2

Checking Measuring-Circuit Monitoring


Both the current- and voltage-measuring circuits are monitored. Operation of the
monitoring functions can be observed by selecting logic state signals
MC MON: Me as.circ.V ,I f aul ty (Oper/Cycl/Log menu branch ) or
MC MON: M.circ. V ,Vref fl ty. (Oper/Cycl/Log menu branch). The monitoring
signals can also be entered into the monitoring signal memory and identified by
reading out the monitoring signal memory.

10-16

P437/EN M/R-11-A // P437311650

P437

10 Commissioning

10.2.6.2.1

Current-Measuring Circuits
Monitoring of current-measuring circuits functions only if 0.125Inom flows in at
least one phase. The P437 determines the absolute value of the negativesequence component, from the three phase currents; the negative-sequence
component is calculated according to the following equation:
Phase sequence A-B-C

(Alternative terminology: clockwise rotating field)


1

I neg = 3 | (I A + a 2 I B + a I C) |



Phase sequence A-C-B

(Alternative terminology: anti-clockwise rotating field)

I neg = 3 | (I A + a I B + a 2 I C) |



Symbols used:

a = e2j/3 = e j120

a 2 = e4j/3 = e j240

The operate condition for the current measuring circuits is:


|Ineg| (Ineg>)|IP,max|
With
Ineg>: MC MON: I ne g> setting
With a single-phase test current we obtain:
|Ineg| = |Itest|
IP,max = Itest
For the operate condition that means:
|Itest| (Ineg>)|Itest|
0,333 (Ineg>)
Therefore operation of the monitoring function for current-measuring circuits
with single-phase test current is only possible if the threshold operate value is
set at less than 0.333.
For two-phase test current in phase opposition we obtain:
| Ineg | =

1
3

| Itest + a2 ( Itest) | =

1
3

| Itest |

IP,max = Itest
For the operate condition that means:
1
3

| Itest | (I neg>) | Itest |

0.577 (Ineg>)
Therefore operation of the monitoring function for current-measuring circuits
with a two-phase test current in phase opposition is only possible if the threshold
operate value is set at less than 0.577.
If the threshold operate value satisfies the respective condition, then the
monitoring function for current-measuring circuits operates with a test current
greater than 0.125Inom after the set operate delay of + 300 s has elapsed.
10.2.6.2.2

Voltage-Measuring Circuits
Negative-sequence monitoring of the voltage-measuring circuits is enabled if at
least one phase-to-ground voltage exceeds the value 0.7 Vnom/3. Other enabling

P437/EN M/R-11-A // P437311650

10-17

P437

10 Commissioning

criteria that can be activated if desired are the following (selection of enabling
criteria at MC MON : Op. mode vol t. mon. in the Par/Func/Main/ menu
branch):

One of the phase currents must exceed 0.05Inom.

The signal at the binary signal input configured for MAIN: CB close d 3 p
EX T must have a logic value of 1.

If negative-sequence monitoring has been enabled, the P437 determines the


absolute value of negative-sequence voltage according to the following equation:
Phase sequence A-B-C (alternative terminology: clockwise rotating
field)

Negative-sequence voltage
V

neg

1
3

| (V

+ a2 V

A-G

+ aV

B-G

)|

C-G

Negative-sequence current
1

I neg = 3 | (I A + a 2 I B + a I C) |



Phase sequence A-C-B (alternative terminology: anti-clockwise rotating
field)

Negative-sequence voltage
V
neg

1
3

| (V

+ aV

A-G

B-G

+ a2 V

Negative-sequence current

I neg = 3 | (I A + a I B + a 2 I C) |



Symbols used:

)|

C-G

a = e2j/3 = e j120

a 2 = e4j/3 = e j240

The trigger threshold of Vneg is set permanently at 0.2Vnom/3. The result of a


single-phase test using |VBG| = |VCG| = 0 and also of the calculation formula for
Vneg given above is that the trigger operates when the test voltage exceeds the
following value:
| Vtest | 3 0.2

V nom
3

A trip signal is issued once the set operate delay has elapsed.
10.2.6.3

Checking Backup Overcurrent-Time Protection


The switch to backup overcurrent-time protection (BUOC) provided it has been
appropriately set is brought about by the measuring-circuit monitoring function
or the tripping of the voltage transformer miniature circuit breaker on the line
side.
If the current exceeds the set operate value (BU OC: I> PSx), then starting
occurs in the corresponding phase(s). After the set time delay (BUOC : tI> PSx)
has elapsed, the P437 trips. If MAI N: Neu tr.pt. treat. PSx is set to Lowimped. grounding then SN starting occurs if the residual current IN calculated by
the P437 exceeds the operate value set at BUOC: IN> PSx. After the set time
delay has elapsed (BUOC: tIN> PSx), the P437 trips.
When the inrush stabilization function is triggered, the BUOC function is blocked.
If the BUOC is set to activate the ARC, then timer stages BUOC: tI> PSx
BUOC : tI N> PSx are blocked when the ARC is ready. The trip signal is then
issued instantaneously for phase starting or with an 80 ms delay for zero-

10-18

P437/EN M/R-11-A // P437311650

P437

10 Commissioning

sequence starting. Timer stage tIN> is also blocked by phase starting or while the
ARC hold time is elapsing.
The P437 calculates the resultant current IN according to the following equation:
|IN| = |IA+IB+IC|
In the case of a single-phase test (for example, IB = IC = 0), the following test
current is obtained:
|Itest| = IN>Inom
At this test current the operate value (BUOC : I N> PSx) is reached.
10.2.6.4

Checking Protective Signaling


The protective signaling function can only be tested if protective signaling is
ready. This can be determined by checking logic state signal PSIG: Ready
(Oper/Cycl/Log menu branch).
If protective signaling is not ready, this may be due to the following reasons:

Protective signaling is not enabled.


(This can be determined by checking PSIG: En able d in the Oper/Cycl/Log
menu branch.)
This may be due to the following reasons:

PSI G: Gen eral en abl e USER (Par/Func/Gen menu branch) is set to No


PSIG: Enable PSx (in one of the Par/Func/PSx menu branches,
depending on the parameter subset) is set to No.
Protective signaling is disabled via an appropriately configured binary
signal input or from the integrated local control panel. (This can be
determined by checking logic state signal P SIG: Ex t. /us e r enabled in
the Oper/Cycl/Log menu branch.)

Protective signaling is being blocked by triggering a correspondingly


configured binary signal input (P SI G: Bl ocking EXT).

A fault has been detected in the communications channel. (This can be


determined by checking logic state signal PSI G: Telecom . fau lty in the
Oper/Cycl/Log menu branch.)

If the conditions for testing are satisfied, it is possible to generate a send signal
for test purposes using a setting parameter (P SI G: Tes t telecom. U SER in the
Oper/CtrlTest menu branch) or by triggering an appropriately configured binary
signal input. This pulse will be present for 500 ms and is extended for the set
reset time. If the with echo setting has been selected in the protection device
at the remote station, then the received signal will be returned.
10.2.6.5

Checking the Auto-Reclosing Function


The auto-reclosing function (ARC) can only be checked if it is ready. This may be
determined by checking logic state signal AR C: CB driv e r eady E XT (Oper/
Cycl/Log).
If the ARC function is not ready, this may be due to the following reasons:

P437/EN M/R-11-A // P437311650

10-19

P437

10 Commissioning

The ARC function is not enabled.


(This can be determined by checking logic state signal ARC: Enabl ed,
(Oper/Cycl/Log menu branch)). This can have the following causes:

ARC : Ge ne ral e nable USER (Par/Func/Gen menu branch) is set to No


ARC : Enable PSx (in one of the Par/Func/PSx menu branches,
depending on the parameter subset) is set to No.
ARC is disabled via an appropriately configured binary signal input or a
setting parameter.
(This can be determined by checking logic state signal ARC: Ext ./user
e na bl ed, Oper/Cycl/Log menu branch)

The ARC function is blocked by Switch On To Fault protection, backup DTOC


protection, Ground Fault protection, Ground Fault (Short-Circuit) Protection
Signaling, a manual trip command or via an appropriately configured signal
input (ARC : Blockin g EXT). (This can be determined by checking logic
state signal ARC : Blocke d, Oper/Cycl/Log menu branch.)

There is no signal with a logic value of 1 at the binary signal input


configured for ARC: CB dri ve re ady E XT.

There is no signal with a logic value of 1 at the binary signal input


configured for MA IN: C B cl ose d 3p E XT. The circuit breaker position
signal is only necessary if the setting at A RC : C B clos.pos.sig. PSx is
Yes.

An ARC cycle is in progress. (This can be determined by checking logic


state signal ARC : Cycl e runn in g in the Oper/Cycl/Log menu branch.)

An ASC cycle is in progress. (This can be determined by checking logic


state signal AS C: Cycl e ru n ni ng, Oper/Cycl/Log menu branch).

A test HSR can be executed for testing purposes using a setting parameter or by
triggering binary signal inputs. The test HSR function first issues a trip command
and then issues a reclose command after the set dead time has elapsed.
10.2.6.6

Checking the Automatic Synchronism Check


The automatic synchronism check can only take place if it is ready. This can be
determined by checking logic state signal ASC: R eady.
The possible reasons for the ASC function not being ready are as follows:

The ASC function is not enabled. (This can be determined by checking logic
state signal ASC : Enable d, (Oper/Cycl/Log menu branch.) This can have
the following causes:

ASC : Gener al en able USER (Par/Func/Gen menu branch) has been


set to No.
ASC : Enab le PSx (Par/Func/PSx menu branch, depending on the
parameter subset) has been set to No.
ASC is disabled via an appropriately configured binary signal input or a
setting parameter.
(This can be determined by checking logic state signal ASC: Ext ./use r
e nabled, Oper/Cycl/Log menu branch.)

A logic 1 signal is present at the binary signal inputs configured for


M AI N: M.c.b. t rip V EXT.

The ASC function will be blocked by triggering the binary signal input
configured for A SC: Bl ocking E XT.

The setting determines whether a close enable may be carried out in case of
blocking.
10-20

P437/EN M/R-11-A // P437311650

P437

10 Commissioning

For test purposes, a close request can be generated for 500 ms using ASC: Test
M C close r USER the setting parameter (Oper/CtrlTest menu branch) or by
triggering an appropriately configured binary signal input (A SC: Tes t MC close
r. EXT). The check can only be carried out if there is no ARC cycle running. The
P437 checks whether enabling is permitted or not according to the set
conditions. If a positive decision is reached, then there is an A SC : C lose
enable signal. No (re-)close command takes place! If the check determines that
enabling is not permitted, the signal ASC: Cl ose rejection is issued.
10.2.6.7

Checking Ground Fault Short-Circuit Protection


Ground fault short-circuit protection can be checked only if it is ready. It can be
interrogated via the logic state signal GFSC: Re ady (Oper/Cycl/Log menu
branch).
If ground fault short-circuit protection is not ready, this may be due to the
following reasons:

Ground fault short-circuit protection is not enabled. (This can be


determined by checking logic state signal GFSC: En abled, Oper/Cycl/Log
menu branch). This may be due to the following reasons:

GF SC : Ge ne ral e nabl e U SER (Par/Func/Gen menu branch) has been


set to No.
GFS C: Enabl e PSx (Par/Func/PSx menu branch, depending on the
parameter subset) has been set to No.
Ground fault short-circuit protection is disabled via an appropriately
configured binary signal input or a setting parameter.
(This can be determined by checking logic state signal GFSC: Ext .
ena bled, Oper/Cycl/Log menu branch).

On the binary signal input configured to MA IN: M.c. b. trip V EXT a logic
1 signal is present.

The ground fault short-circuit protection function calculates the neutral


displacement voltage VN-G via the three phase-to-ground voltages according to
the following equation:
|VN-G| = |VA-G+VB-G+VC-G|
In the case of a single-phase test using |VB-G| = |VC-G| = 0, the result of the
calculation formula for VN-G given above is that trigger GF SC : V NG> operates
when the test voltage exceeds the following value:
| Vtest | = 3 V NG>

V nom
3

VN-G> > : Setting GF SC : VN G>


The operation of the trigger can be determined by checking logic state signal
GFSC: VNG> t riggere d (Oper/Cycl/Log menu branch)
10.2.6.8

Checking Ground Fault (Short-Circuit) Protection Signaling


Ground fault short-circuit protection signaling can be checked using a setting
parameter (GSC SG: Tes t tele com. USER) or by triggering an appropriately
configured binary signal input (GSCSG: Te st te l ecom. EXT). The P437 then
generates a send signal for 500 ms.

10.2.7

Completing Commissioning
Before the P437 is released for operation, the user should make sure that the
following steps have been taken:

P437/EN M/R-11-A // P437311650

10-21

P437

10 Commissioning

(Reset at MAI N: Ge ne ral re se t USER (password-protected) and


MT_RC : Reset r ecor d. USE R, both in Oper/CtrlTest menu branch.)

Blocking of output relays has been cancelled.


(OU TP: Out p.re l.bl ock U SER, Par/Func/Glob menu branch, setting No.)

Blocking of the trip command has been cancelled.


(MAI N: Trip cmd.bl ock. USER, Par/Func/Glob menu branch, setting No.)

The device is on-line.


(MAI N: D e vice on-lin e, Par/Func/Glob menu branch, setting Yes (= on).)

After completion of commissioning, only the green LED indicator signaling


HEALTHY (H1) should be on.

10-22

P437/EN M/R-11-A // P437311650

P437
11

Troubleshooting
This chapter describes problems that might be encountered, their causes, and
possible methods for eliminating them. It is intended as a general orientation
only, and in cases of doubt it is better to return the P437 to the manufacturer.
Please follow the packaging instructions in Section 5.1, (p. 5-3) when returning
equipment to the manufacturer.

WARNING
Only qualified personnel, familiar with the Warning page at the beginning of
this manual, may work on or operate this device.

WARNING
Before checking further, disconnect the P437 from the power supply.

The following instructions apply to surface-mounted cases:

WARNING
The local control panel is connected to processor module P by a plug-in
connecting cable. Remember the connector position! Do not bend the
connecting cable.

Problem

Lines of text are not displayed on the local control panel.

Check to see whether there is supply voltage at the device connection


points.
Check to see whether the magnitude of the auxiliary voltage is correct.
The P437 is protected against damage resulting from polarity reversal.

The P437 issues an Alarm signal on LED H 3.

Identify the specific problem by reading out the monitoring signal


memory (see Section 6.11.6.2, (p. 6-26)). The table below lists possible
monitoring or warning indication (provided that a configuration setting
has been entered at SFMON: Fct. ass ign. warning), the faulty area,
the P437's response, and the mode of the output relay configured for
Warning and Blocked/faulty.

Key

: No reaction and/or no output relay triggered.

Yes: The corresponding output relay is triggered.

Updating: The output relay configured for 'Warning' starts only if the
monitoring signal is still present.

P437/EN M/R-11-A // P437311650

11-1

P437

11 Troubleshooting

Parameter

Address

Self-monitoring

SFMO N: F ct . as s ign. war ning

021 030

[spacer]

SFMO N: M on.s ig. re t enti on

021 018

11-2

P437/EN M/R-11-A // P437311650

11 Troubleshooting

Parameter

Self-monitoring

SFMO N: C B faulty E X T

[spacer]

The external input CBF : CB fault y EX T has become active.

P437

Address
098 072

Device reaction:
'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: W arning (LE D)

[spacer]

Warning configured for LED H3.

[spacer]

SFMO N: W arning (re lay )

[spacer]

Warning configured for an output relay.

[spacer]

SFMO N: W arm re start e x ec.

[spacer]

A warm restart has been carried out.

[spacer]

SFMO N: C old re star t exe c.

[spacer]

A cold restart has been carried out.

[spacer]

SFMO N: C old re st. che ck sum

[spacer]

A cold restart has been carried out on account of a checksum error in the
memory (NOVRAM).

036 070

036 100

041 202

041 201

093 024

1st device reaction: Warm restart


2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]

SFMO N: C old re st. SW updat e

[spacer]

A cold restart has been carried out following a software update.

093 025

1st device reaction: Warm restart


2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]

SFMO N: B lockin g HW failur e

[spacer]

Supplementary warning that this device is blocked.

090 019

'Warning' output relay: Updating


'Blocked/faulty' output relay:
[spacer]

SFMO N: R elay Kxx faulty

[spacer]

Multiple signal: output relay defective.

041 200

Device reaction:
'Warning' output relay: Updating
'Blocked/faulty' output relay: Yes

P437/EN M/R-11-A // P437311650

11-3

P437

11 Troubleshooting

Parameter
[spacer]

SFMO N: Hardware clock fail.

[spacer]

The hardware clock has failed.

Address
093 040

Device reaction:
'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: B at te ry failure

[spacer]

Battery voltage too low. Replace battery.

090 010

Device reaction:
'Warning' output relay: Updating
'Blocked/faulty' output relay:
[spacer]

SFMO N: I nt e rm.volt. fail.RAM

[spacer]

Faulty test pattern in the RAM. This can occur, for example, if the processor
module or the power supply module is removed from the bus module (digital).
This fault is only detected during device startup. After the fault is detected, the
software initializes the RAM. This means that all records are deleted.

093 026

1st device reaction: Warm restart


2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]

SFMO N: +15V s upply faulty

[spacer]

The +15 V internal supply voltage has dropped below a minimum value.

093 081

1st device reaction: Warm restart


2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]

SFMO N: +24V s upply faulty

[spacer]

The +24 V internal supply voltage has dropped below a minimum value.

093 082

1st device reaction: Warm restart


2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]

SFMO N: - 15V s upply faulty

[spacer]

The 15 V internal supply voltage has dropped below a minimum value.

093 080

1st device reaction: Warm restart


2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]

SFMO N: W rong m odule s lot 1

096 100

[spacer]

SFMO N: W rong m odule s lot 2

096 101

[spacer]

SFMO N: W rong m odule s lot 3

096 102

11-4

P437/EN M/R-11-A // P437311650

11 Troubleshooting

Parameter

P437

Address

[spacer]

SFMO N: W rong module s lot 4

096 103

[spacer]

SFMO N: W rong module s lot 5

096 104

[spacer]

SFMO N: W rong module s lot 6

096 105

[spacer]

SFMO N: W rong module s lot 7

096 106

[spacer]

SFMO N: W rong module s lot 8

096 107

[spacer]

SFMO N: W rong module s lot 9

096 108

[spacer]

SFMO N: W rong module s lot 10

096 109

[spacer]

SFMO N: W rong module s lot 11

096 110

[spacer]

SFMO N: W rong module s lot 12

096 111

[spacer]

SFMO N: W rong module s lot 13

096 112

[spacer]

SFMO N: W rong module s lot 14

096 113

[spacer]

SFMO N: W rong module s lot 15

096 114

[spacer]

SFMO N: W rong module s lot 16

096 115

[spacer]

SFMO N: W rong module s lot 17

096 116

[spacer]

SFMO N: W rong module s lot 18

096 117

[spacer]

SFMO N: W rong module s lot 19

096 118

[spacer]

SFMO N: W rong module s lot 20

096 119

[spacer]

SFMO N: W rong module s lot 21

096 120

[spacer]

Module in wrong slot.


1st device reaction: Warm restart
2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes

[spacer]

SFMO N: W rong module D ig.Bus

[spacer]

The device has been fitted with a wrong digital bus. Since this is checked using
the module variant number this signal can also occur after a firmware upgrade
to a version that is not compatible with the hardware.

096 123

1st device reaction: Warm restart


2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]

SFMO N: W rong module HM I

[spacer]

The device has been fitted with a wrong HMI. Since this is checked using the
module variant number this signal can also occur after a firmware upgrade to a
version that is not compatible with the hardware.

096 124

1st device reaction: Warm restart


2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes

P437/EN M/R-11-A // P437311650

11-5

P437

11 Troubleshooting

Parameter

Address

[spacer]

SFMO N: W rong m odul e Comm

[spacer]

The device has been fitted with a wrong communication module. Since this is
checked using the module variant number this signal can also occur after a
firmware upgrade to a version that is not compatible with the hardware.

096 125

1st device reaction: Warm restart


2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]

SFMO N: W rong m odule Ana. Bus

[spacer]

The device has been fitted with a wrong analog bus. Since this is checked using
the module variant number this signal can also occur after a firmware upgrade
to a version that is not compatible with the hardware.

096 126

1st device reaction: Warm restart


2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]

SFMO N: D e fe ct.module slot 1

097 000

[spacer]

SFMO N: D e fe ct.module slot 2

097 001

[spacer]

SFMO N: D e fe ct.module slot 3

097 002

[spacer]

SFMO N: D e fe ct.module slot 4

097 003

[spacer]

SFMO N: D e fe ct.module slot 5

097 004

[spacer]

SFMO N: D e fe ct.module slot 6

097 005

[spacer]

SFMO N: D e fe ct.module slot 7

097 006

[spacer]

SFMO N: D e fe ct.module slot 8

097 007

[spacer]

SFMO N: D e fe ct.module slot 9

097 008

[spacer]

SFMO N: D e fe ct.module slot10

097 009

[spacer]

SFMO N: D e fe ct.module slot11

097 010

[spacer]

SFMO N: D e fe ct.module slot12

097 011

[spacer]

SFMO N: D e fe ct.module slot13

097 012

[spacer]

SFMO N: D e fe ct.module slot14

097 013

[spacer]

SFMO N: D e fe ct.module slot15

097 014

[spacer]

SFMO N: D e fe ct.module slot16

097 015

[spacer]

SFMO N: D e fe ct.module slot17

097 016

[spacer]

SFMO N: D e fe ct.module slot18

097 017

[spacer]

SFMO N: D e fe ct.module slot19

097 018

[spacer]

SFMO N: D e fe ct.module slot20

097 019

11-6

P437/EN M/R-11-A // P437311650

11 Troubleshooting

Parameter
[spacer]

SFMO N: D e fe ct.module slot21

[spacer]

Defective module in slot x.

P437

Address
097 020

Device reaction:
'Warning' output relay: Updating
'Blocked/faulty' output relay:
[spacer]

SFMO N: M odule Y DP R fault y

[spacer]

The checksum feature of analog I/O module Y has detected a fault in the data
transmission of the Dual-Port-RAM.

093 110

Device reaction:
'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: M odule Y RAM fault y

[spacer]

Fault in the program or data memory of the analog I/O module.

093 111

Device reaction:
'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: E rror K 8 01

097 086

[spacer]

SFMO N: E rror K 8 02

097 087

[spacer]

SFMO N: E rror K 8 03

097 088

[spacer]

SFMO N: E rror K 8 04

097 089

[spacer]

SFMO N: E rror K 8 05

097 090

[spacer]

SFMO N: E rror K 8 06

097 091

[spacer]

SFMO N: E rror K 8 07

097 092

[spacer]

SFMO N: E rror K 8 08

097 093

[spacer]

SFMO N: E rror K 1 001

097 102

[spacer]

SFMO N: E rror K 1 002

097 103

[spacer]

SFMO N: E rror K 1 003

097 104

[spacer]

SFMO N: E rror K 1 004

097 105

[spacer]

SFMO N: E rror K 1 005

097 106

[spacer]

SFMO N: E rror K 1 006

097 107

[spacer]

SFMO N: E rror K 1 007

097 108

[spacer]

SFMO N: E rror K 1 008

097 109

[spacer]

SFMO N: E rror K 1 201

097 118

[spacer]

SFMO N: E rror K 1 202

097 119

[spacer]

SFMO N: E rror K 1 203

097 120

[spacer]

SFMO N: E rror K 1 204

097 121

[spacer]

SFMO N: E rror K 1 205

097 122

P437/EN M/R-11-A // P437311650

11-7

P437

11 Troubleshooting

Parameter

Address

[spacer]

SFMO N: E rror K 12 0 6

097 123

[spacer]

SFMO N: E rror K 1 207

097 124

[spacer]

SFMO N: E rror K 1 208

097 125

[spacer]

SFMO N: E rror K 1 401

097 134

[spacer]

SFMO N: E rror K 1 402

097 135

[spacer]

SFMO N: E rror K 1 403

097 136

[spacer]

SFMO N: E rror K 1 404

097 137

[spacer]

SFMO N: E rror K 1 405

097 138

[spacer]

SFMO N: E rror K 1 406

097 139

[spacer]

SFMO N: E rror K 1 407

097 140

[spacer]

SFMO N: E rror K 1 408

097 141

[spacer]

SFMO N: E rror K 1 601

097 150

[spacer]

SFMO N: E rror K 1 602

097 151

[spacer]

SFMO N: E rror K 1 603

097 152

[spacer]

SFMO N: E rror K 1 604

097 153

[spacer]

SFMO N: E rror K 1 605

097 154

[spacer]

SFMO N: E rror K 1 606

097 155

[spacer]

SFMO N: E rror K 1 607

097 156

[spacer]

SFMO N: E rror K 1 608

097 157

[spacer]

SFMO N: E rror K 1 801

097 166

[spacer]

SFMO N: E rror K 1 802

097 167

[spacer]

SFMO N: E rror K 1 803

097 168

[spacer]

SFMO N: E rror K 1 804

097 169

[spacer]

SFMO N: E rror K 1 805

097 170

[spacer]

SFMO N: E rror K 1 806

097 171

[spacer]

SFMO N: E rror K 2 001

097 182

[spacer]

SFMO N: E rror K 2 002

097 183

[spacer]

SFMO N: E rror K 2 003

097 184

[spacer]

SFMO N: E rror K 2 004

097 185

[spacer]

SFMO N: E rror K 2 005

097 186

[spacer]

SFMO N: E rror K 2 006

097 187

[spacer]

SFMO N: E rror K 2 007

097 188

[spacer]

SFMO N: E rror K 2 008

097 189

[spacer]

Output relay K xxx defective.


Device reaction:
'Warning' output relay: Updating
'Blocked/faulty' output relay:

11-8

P437/EN M/R-11-A // P437311650

11 Troubleshooting

Parameter
[spacer]

SFMO N: U nd ef . ope r at. code

[spacer]

Undefined operation code.

P437

Address
093 010

1st device reaction: Warm restart


2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]

SFMO N: Abnormal t erminat ion

[spacer]

The application has been terminated in an unexpected way. If this error occurs
during a (re-)start of the device then this message is displayed and the device is
blocked.

093 030

1st device reaction: Warm restart


2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]

SFMO N: B ad arg. s ys t em call

[spacer]

Invalid parameter when calling a function of the operating system. If this error
occurs during a (re-)start of the device then this message is displayed and the
device is blocked.

093 031

1st device reaction: Warm restart


2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]

SFMO N: M ute x de adloc k

[spacer]

Software threads are locked from each other by mutex. If this error occurs
during a (re-)start of the device then this message is displayed and the device is
blocked.

093 032

1st device reaction: Warm restart


2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]

SFMO N: I nvalid memory ref.

[spacer]

Attempt to access an invalid memory segment. If this error occurs during a


(re-)start of the device then this message is displayed and the device is blocked.

093 033

1st device reaction: Warm restart


2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes

P437/EN M/R-11-A // P437311650

11-9

P437

11 Troubleshooting

Parameter

Address

[spacer]

SFMO N: U ne xpe ct ed ex ce ption

[spacer]

Miscellaneous error message from the processor or operating system. If this


error occurs during a (re-)start of the device then this message is displayed and
the device is blocked.

093 034

1st device reaction: Warm restart


2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]

SFMO N: I nvalid ar ithm. op.

[spacer]

Invalid arithmetic operation.

093 011

1st device reaction: Warm restart


2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]

SFMO N: U nd ef ined i nter rupt

[spacer]

Undefined interrupt.

093 012

1st device reaction: Warm restart


2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]

SFMO N: E x ce pt ion oper .s ys t .

[spacer]

Interrupt of the operating system.

093 013

1st device reaction: Warm restart


2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]

SFMO N: Pr ote ction f ailure

[spacer]

Watchdog is monitoring the periodic start of protection routines. It has detected


an error.

090 021

1st device reaction: Warm restart


2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]

SFMO N: C he ck s um error param

[spacer]

A checksum error involving the parameters in the memory (NOVRAM) has been
detected.

090 003

1st device reaction: Warm restart


2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes

11-10

P437/EN M/R-11-A // P437311650

11 Troubleshooting

Parameter

P437

Address

[spacer]

SFMO N: C lock sync. e rror

[spacer]

In 10 consecutive clock synchronization telegrams, the difference between the


time of day given in the telegram and that of the hardware clock is greater than
10 ms.

093 041

Device reaction:
'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: O ve rflow MT_RC

[spacer]

Last entry in the monitoring signal memory in the event of overflow.

090 012

Device reaction:
'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: S em aph. M T_RC block .

[spacer]

Software overloaded.

093 015

Device reaction:
'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: T im e -out module Y

[spacer]

Watchdog is monitoring the periodic status signal of the analog I/O module Y. It
has detected an error.

093 112

Device reaction:
'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: I nvalid SW d.loade d

[spacer]

Wrong or invalid software has been downloaded.

096 121

1st device reaction: Warm restart


2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]

SFMO N: I nvalid SW ver s DHMI

[spacer]

Incorrect or invalid software was loaded to operate the detachable display


(DHMI).

093 145

Device reaction:
'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: I nval. SW ve r s .C OMM1

[spacer]

Incorrect or invalid communication software has been downloaded.

093 075

Device reaction:
'Warning' output relay: Yes
'Blocked/faulty' output relay:
P437/EN M/R-11-A // P437311650

11-11

P437

11 Troubleshooting

Parameter
[spacer]

SFMO N: I nval. C onfig. I E C

[spacer]

Invalid parameters in the IEC configuration.

Address
093 079

Device reaction:
'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: I nvalid SW ver s. Y

[spacer]

Incorrect or invalid software for analog I/O module Y has been downloaded.

093 113

Device reaction:
'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: I nom not adjust able

[spacer]

Transformer module T is not suitable for setting Inom.

093 118

Device reaction:
'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: I nvalid scali ng BCD

[spacer]

An invalid characteristic has been set for the BCD output channel of analog I/O
module Y.

093 124

Device reaction: Depends on type of fault detected.


'Warning' output relay: Updating
'Blocked/faulty' output relay:
[spacer]

SFMO N: I nvalid scali ng A-1

093 114

[spacer]

SFMO N: I nvalid scali ng A-2

093 115

[spacer]

An invalid characteristic has been set for one of the analog output channels of
analog I/O module Y.
Device reaction: Depends on type of fault detected.
'Warning' output relay: Updating
'Blocked/faulty' output relay:

[spacer]

SFMO N: I nvalid scali ng IDC

[spacer]

An invalid characteristic has been set for the analog input channel of analog I/O
module Y.

093 116

Device reaction: Depends on type of fault detected.


'Warning' output relay: Updating
'Blocked/faulty' output relay:
[spacer]

SFMO N: S etting e rror THE RM

[spacer]

Invalid parameters in the setting for the thermal replica.

098 035

Device reaction: Blocking of thermal overload protection.


'Warning' output relay: Yes
'Blocked/faulty' output relay:

11-12

P437/EN M/R-11-A // P437311650

11 Troubleshooting

Parameter

P437

Address

[spacer]

SFMO N: S etting e rror f<>

[spacer]

The over-/underfrequency protection function has been set for 'overfrequency'


monitoring (based on the settings for operate value and nominal frequency).
This setting is not valid in the f w. Delta f/Delta t operating mode.

098 028

Device reaction: Blocking of the over-/under frequency protection function


'Warning' output relay: Updating
'Blocked/faulty' output relay:
[spacer]

SFMO N: S etting e rror CB M

[spacer]

An invalid characteristic has been set for circuit breaker monitoring.

098 020

Device reaction: Depends on type of fault.


'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: Pe riphe ral fault

[spacer]

Multiple signal.

098 018

'Warning' output relay: Yes


'Blocked/faulty' output relay:
[spacer]

SFMO N: M .c.b. trip V

[spacer]

The line-side voltage transformer m.c.b. has tripped.

098 000

Device reaction: Blocking of the short-circuit direction determination.


'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: M .c.b. trip VNG

[spacer]

The m.c.b. monitoring the neutral-displacement voltage has tripped.

098 132

The Ground fault protection (GFSC and GSCSG) is blocked (if these function
groups are operated with measured neutral-displacement voltage)
'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: M .c.b. trip Vref

[spacer]

The m.c.b. monitoring the reference voltage transformer has tripped.

098 011

Device reaction: Blocking of automatic synchronism check (ASC).


'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: Phas e se qu. V faulty

[spacer]

Measuring-circuit monitoring has detected a fault in the phase sequence of the


phase-to-ground voltages.

098 001

'Warning' output relay: Yes


'Blocked/faulty' output relay:

P437/EN M/R-11-A // P437311650

11-13

P437

11 Troubleshooting

Parameter

Address

[spacer]

SFMO N: Vne g> tr igge re d

[spacer]

The negative-sequence monitoring function of measuring-circuit monitoring has


been triggered.

098 014

'Warning' output relay: Yes


'Blocked/faulty' output relay:
[spacer]

SFMO N: U nd er volt age

[spacer]

The measuring-circuit monitoring function has detected an undervoltage.

098 009

'Warning' output relay: Yes


'Blocked/faulty' output relay:
[spacer]

SFMO N: F F, V trigge r ed

[spacer]

The fuse failure monitoring function has detected a fault in the voltagemeasuring circuit.

098 021

'Warning' output relay: Yes


'Blocked/faulty' output relay:
[spacer]

SFMO N: F F, Vref trigge re d

[spacer]

The fuse failure monitoring function has detected a fault in the reference
voltage-measuring circuit.

098 022

'Warning' output relay: Yes


'Blocked/faulty' output relay:
[spacer]

SFMO N: M .circ. V,Vref fl ty.

[spacer]

Multiple signal: Voltage-measuring circuits for phase-to-ground voltages or the


reference voltage faulty.

098 023

Device reaction: Depends on type of fault.


'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: M eas . cir c. V f aul ty

[spacer]

Multiple signal: Voltage-measuring circuits faulty.

098 017

Device reaction: Depends on type of fault.


'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: M eas .circ .VNG faulty

[spacer]

The voltage-measuring circuits for the neutral-point displacement voltage are


faulty.

098 254

Device reaction: Selective blocking of the neutral-point displacement voltage


monitor (in function group V<>) if it were set so that it would evaluate the
measured value of the neutral-point displacement voltage.
'Warning' output relay: Yes
'Blocked/faulty' output relay:

11-14

P437/EN M/R-11-A // P437311650

11 Troubleshooting

Parameter
[spacer]

SFMO N: M .circ. Vre f fault y

[spacer]

The voltage-measuring circuits for the reference voltage are faulty.

P437

Address
098 255

Device reaction: Selective blocking of the neutral-point displacement voltage


monitor in function groups V<> and LIMIT as well as blocking of ASC.
'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: B UOC n ot act iv e

[spacer]

Due to a fault in the voltage-measuring circuit, distance protection has been


blocked, but the unit has not switched to backup overcurrent-time protection.

098 002

'Warning' output relay: Yes


'Blocked/faulty' output relay:
[spacer]

SFMO N: B UOC act ive w/ o ARC

[spacer]

Due to a fault in the voltage-measuring circuit, distance protection has been


blocked, and the unit has switched to backup overcurrent-time protection. ARC
is not activated by the backup overcurrent-time protection function.

098 003

'Warning' output relay: Yes


'Blocked/faulty' output relay:
[spacer]

SFMO N: B UOC act ive wit h ARC

[spacer]

Due to a fault in the voltage-measuring circuit, distance protection has been


blocked, and the unit has switched to backup overcurrent-time protection. ARC
is activated by the backup overcurrent-time protection function.

098 004

'Warning' output relay: Yes


'Blocked/faulty' output relay:
[spacer]

SFMO N: M eas . cir c. I fault y

[spacer]

The measuring-circuit monitoring function has detected a fault in the currentmeasuring circuits.

098 005

'Warning' output relay: Yes


'Blocked/faulty' output relay:
[spacer]

SFMO N: M eas .circ .V,I fault y

[spacer]

Multiple signal: Multiple signaling: Current- or voltage-measuring circuits faulty.

098 016

Device reaction: Depends on type of fault.


'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: Z ero-se qu. s tart ing

[spacer]

The zero-sequence starting of distance protection has been triggered without


phase starting.

098 015

'Warning' output relay: Yes


'Blocked/faulty' output relay:

P437/EN M/R-11-A // P437311650

11-15

P437

11 Troubleshooting

Parameter

Address

[spacer]

SFMO N: M eas . cir cuit s G FS C

[spacer]

Ground fault (short-circuit) protection monitoring has been triggered.

098 013

'Warning' output relay: Yes


'Blocked/faulty' output relay:
[spacer]

SFMO N: C ommunic.fault C OMM 3

093 140

[spacer]

SFMO N: C ommunic.fault C OMM 4

093 146

[spacer]

The set time C OMM3: T ime -out comm.faul t (or COM M4: Time -out
comm.fault, resp.) has elapsed since the most recent 100% valid telegram
was received. The receive signals are set to their user-defined default values.
'Warning' output relay: Yes
'Blocked/faulty' output relay:

[spacer]

SFMO N: Hardware e r ror COM M3

[spacer]

The device has detected a hardware error in the effective connection


InterMiCOM (communication interface 3).

093 143

'Warning' output relay: Yes


'Blocked/faulty' output relay:
[spacer]

SFMO N: Hardware e r ror COM M4

[spacer]

The device has detected a hardware error in the effective connection


InterMiCOM (communication interface 4).

093 149

'Warning' output relay: Yes


'Blocked/faulty' output relay:
[spacer]

SFMO N: C omm.link fail.C OMM3

093 142

[spacer]

SFMO N: C omm.link fail.C OMM4

093 148

[spacer]

Timer stage COM M3: T ime -out link fail . (or COMM4: Time-out l ink
fail., resp.) has elapsed indicating a persistent failure of the transmission
channel. The receive signals are set to their user-defined default values.
'Warning' output relay: Yes
'Blocked/faulty' output relay:

[spacer]

SFMO N: L im .e x c.te l.e r .COM M3

093 141

[spacer]

SFMO N: L im .e x c.te l.e r .COM M4

093 147

[spacer]

The threshold set for timer stage COMM3: Limit telegr. e rrors was
exceeded and the receive signals are set to their user-defined default values.
'Warning' output relay: Yes
'Blocked/faulty' output relay:

[spacer]

SFMO N: T elecom. faulty / PSI G

[spacer]

The transmission channel of protective signaling is faulty.

098 006

Device reaction: Blocking of protective signaling.


'Warning' output relay: Yes
'Blocked/faulty' output relay:

11-16

P437/EN M/R-11-A // P437311650

11 Troubleshooting

Parameter

P437

Address

[spacer]

SFMO N: O p.mode PS IG inv al.

[spacer]

The operating mode settings for protective signaling and ground fault (shortcircuit) protection signaling are not identical.

098 019

'Warning' output relay: Yes


'Blocked/faulty' output relay:
[spacer]

SFMO N: T elecom.faulty / GSC SG

[spacer]

The transmission channel of ground fault (short-circuit) protection signaling is


faulty.

098 027

'Warning' output relay: Yes


'Blocked/faulty' output relay:
[spacer]

SFMO N: C B pos .s ig. implaus.

[spacer]

The plausibility logic was triggered during the acquisition of the circuit breaker's
(CB) status signals.

098 124

'Warning' output relay: Yes


'Blocked/faulty' output relay:
[spacer]

SFMO N: C B No. C B op. >

[spacer]

The maximum number of CB operations performed has been exceeded.

098 066

Device reaction: Depends on type of fault.


'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: C B rem. No. C B op. <

[spacer]

The minimum number of CB operations performed at nominal current has fallen


below the threshold.

098 067

Device reaction: Depends on type of fault.


'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: C B I trip >

[spacer]

The maximum sum of disconnection current values has been exceeded.

098 068

Device reaction: Depends on type of fault.


'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: C B I trip**2 >

[spacer]

The maximum sum of the disconnection current values to the second power has
been exceeded.

098 069

Device reaction: Depends on type of fault.


'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: C B tm ax> A

098 070

[spacer]

SFMO N: C B tm ax> B

098 071

P437/EN M/R-11-A // P437311650

11-17

P437

11 Troubleshooting

Parameter

Address

[spacer]

SFMO N: C B tm ax> C

[spacer]

The maximum duration for the opening of a CB pole has been exceeded.
Disconnection is not determined for this CB pole.

098 077

Device reaction: Depends on type of fault.


'Warning' output relay: Yes
'Blocked/faulty' output relay:
[spacer]

SFMO N: I nv.inp.f.cloc k sy nc

[spacer]

The function was configured to a binary signal input on the analog I/O module Y.
Such a configuration is not permitted for this function.

093 120

Device reaction:
'Warning' output relay: Updating
'Blocked/faulty' output relay:
[spacer]

SFMO N: O utput 30

098 053

[spacer]

SFMO N: O utput 30 ( t)

098 054

[spacer]

SFMO N: O utput 31

098 055

[spacer]

SFMO N: O utput 31 ( t)

098 056

[spacer]

SFMO N: O utput 32

098 057

[spacer]

SFMO N: O utput 32 ( t)

098 058

[spacer]

These LOGIC outputs can be included in the list of warning signals by selection
at S FMON: Fct. ass ign. warning. The warning signals are also recorded
in the monitoring signal memory.
'Warning' output relay: Yes
'Blocked/faulty' output relay:

[spacer]

SFMO N: PT 100 open c ir cuit

[spacer]

The P437 has detected an open circuit in the connection of the resistance
thermometer PT100 to the analog I/O module Y.

098 024

Device reaction: Depends on type of fault detected.


'Warning' output relay: Updating
'Blocked/faulty' output relay:
[spacer]

SFMO N: O ve rload 20 mA input

[spacer]

The 20 mA input of analog I/O module Y is overloaded.

098 025

Device reaction: Depends on type of fault detected.


'Warning' output relay: Updating
'Blocked/faulty' output relay:
[spacer]

SFMO N: O pe n circ. 20 mA inp.

[spacer]

The P437 has detected an open circuit in the connection of the 20 mA input.

098 026

Device reaction: Depends on type of fault detected.


'Warning' output relay: Updating
'Blocked/faulty' output relay:

11-18

P437/EN M/R-11-A // P437311650

11 Troubleshooting

Parameter

P437

Address

[spacer]

SFMO N: C T A error

[spacer]

Measurement of the coolant temperature via the analog module is faulty.

098 034

'Warning' output relay: Yes


'Blocked/faulty' output relay:

P437/EN M/R-11-A // P437311650

11-19

P437

11-20

11 Troubleshooting

P437/EN M/R-11-A // P437311650

P437
12

Maintenance
WARNING
Only qualified personnel, familiar with the Warning page at the beginning of
this manual, may work on or operate this device.

The P437 is a low-maintenance device. The components used in the units are
selected to meet exacting requirements. Recalibration is not necessary.

P437/EN M/R-11-A // P437311650

12-1

P437

12.1

12 Maintenance

Maintenance Procedures in the Power Supply Area


Replacement of the power supply module must be carried out by trained
personnel, and the power supply voltage must be turned off while the work is
being performed.

DANGER
Always turn off the power supply voltage before removing a hardware
module.
The power supply must be turned off for at least 5 s before power supply
module V is removed.
Otherwise there is the danger of an electric shock.

WARNING
The following instructions apply to surface-mounted cases:
The local control panel is connected to processor module P by a plug-in
connecting cable. Remember the connector position! Do not bend the
connecting cable.

NOTICE
The replaced power supply module must be disposed of in compliance with
applicable national regulations.

In general, the electronic components of the MiCOM P30 family of devices are
designed for a long service life.
For the power supply, however, dimensioning requirements dictate the use of
electrolytic capacitors that are subject to increased wear and tear. The useful life
of these capacitors depends on their temperature and thus on the components
fitted in the device, the load conditions, device location and environmental
conditions.
The internal voltage levels are cyclically checked by the P30 self-monitoring
functions. In case the voltage levels deviate from their specified values a warning
message will be issued or, for persistent problems, the device will be set to a
safe condition (blocking). Hence, there is no imperative need to replace the
power supply module after a pre-defined period of time. However, should you
need to guarantee a high availability of the device then we recommend
preventive replacement of the power supply module after a period of 8 to 10
years.
Moreover, the power supply module of the P437 is equipped with a lithium
battery for non-volatile storage of fault data and for keeping the internal clock
running in the event of failure of the auxiliary power supply. The useful life of the
lithium battery depends on the auxiliary power supply of the device.

12-2

P437/EN M/R-11-A // P437311650

P437

12 Maintenance

If the P437 is continuously connected to the auxiliary power supply, then


there is no discharging of the battery, and the battery will thus not be
depleted during its service life.

Should the P437 be disconnected from the auxiliary power supply for
several years, then the battery capacity would decrease.

During normal operation, the battery voltage is monitored. If the voltage falls
below a pre-defined threshold, a warning message will be issued and the battery
has to be replaced.
After the maintenance procedures described above have been completed, new
commissioning tests as described in Section 10.2, (p. 10-4) must be carried out.

P437/EN M/R-11-A // P437311650

12-3

P437

12.2

12 Maintenance

Routine Functional Testing


The P437 is used as a safety device and must therefore be routinely injection
tested for proper operation. The first functional tests should be carried out
approximately 6 to 12 months after commissioning. Functional tests should be
performed at intervals of 2 to 3 years 4 years at the maximum.
The P437 incorporates in its system a very extensive self-monitoring function for
hardware and software. The internal structure guarantees, for example, that
communication within the processor system will be checked on a continuing
basis.
Nonetheless, there are a number of subfunctions that cannot be checked by the
self-monitoring feature without injection testing from the device terminals. The
respective device-specific properties and settings must be observed in such
cases.
In particular, none of the control and signaling circuits that are run to the device
from the outside are checked by the self-monitoring function.

12-4

P437/EN M/R-11-A // P437311650

P437

12 Maintenance

12.3

Analog Input Circuits


The analog inputs are fed through an analog preprocessing feature (anti-aliasing
filtering) to a common analog-to-digital converter. In conjunction with the selfmonitoring function, the CT/VT supervision function that is available for the
devices general functions can detect deviations in many cases. However, it is
still necessary to test from the device terminals in order to make sure that the
analog measuring circuits are functioning correctly.
The best way to carry out a static test of the analog input circuits is to check the
primary measured operating data using the operating data measurement
function or to use a suitable testing instrument. A small measured value (such
as the nominal current in the current path) and a large measured value (such
as the nominal voltage in the voltage path) should be used to check the
measuring range of the A/D converter. This makes it possible to check the entire
dynamic range.
The accuracy of operating data measurement is <1%. An important factor in
evaluating device performance is long-term performance based on comparison
with previous measurements.
In addition, a dynamic test can be used to check transmission performance and
the phase relation of the current transformers and the anti-aliasing filter. This
can best be done by measuring the trigger point of the first zone when there is a
two-phase ungrounded fault. For this test, the value of the short-circuit current
should be such that a loop voltage of approximately 2 V is obtained at the
device's terminals with the set impedance. Furthermore, a suitable testing
instrument that correctly replicates the two-phase ungrounded fault should be
used for this purpose.
This dynamic test is not absolutely necessary, since it only checks the stability of
a few less passive components. Based on reliability analysis, the statistical
expectation is that only one component in 10 years in 1000 devices will be
outside the tolerance range.
Additional analog testing of such factors as the impedance characteristic or the
starting characteristic is not necessary, in our opinion, since information
processing is completely digital and is based on the measured analog current
and voltage values. Proper operation was checked in conjunction with type
testing.

P437/EN M/R-11-A // P437311650

12-5

P437

12.4

12 Maintenance

Binary Opto Inputs


The binary inputs are not checked by the self-monitoring function. However, a
testing function is integrated into the software so that the trigger state of each
input can be read out (Oper/Cycl/Phys menu branch). This check should be
performed for each input being used and can be done, if necessary, without
disconnecting any device wiring.

12-6

P437/EN M/R-11-A // P437311650

P437

12 Maintenance

12.5

Binary Outputs
With respect to binary outputs, the integrated self-monitoring function includes
even two-phase triggering of the relay coils of all the relays. There is no
monitoring function for the external contact circuit. In this case, the all-or-nothing
relays must be triggered by way of device functions or integrated test functions.
For these testing purposes, triggering of the output circuits is integrated into the
software through a special control function (Oper/CtrlTest menu branch).

WARNING
Before starting the test, open any triggering circuits for external devices so
that no inadvertent switching operations will take place.

P437/EN M/R-11-A // P437311650

12-7

P437

12.6

12 Maintenance

Serial Interfaces
The integrated self-monitoring function for the PC or communication interface
also includes the communication module. The complete communication system,
including connecting link and fiber-optic module (if applicable), is always totally
monitored as long as a link is established through the control program or the
communication protocol.

12-8

P437/EN M/R-11-A // P437311650

P437
13

Storage
Devices must be stored in a dry and clean environment. A temperature range of
-25C to +70C (-13F to +158F) must be maintained during storage (see
chapter entitled Technical Data). The relative humidity must be controlled so
that neither condensation nor ice formation will result.
If the units are stored without being connected to auxiliary voltage, then the
electrolytic capacitors in the power supply area need to be recharged every
4 years. Recharge the capacitors by connecting auxiliary voltage to the P437 for
approximately 10 minutes.
If the units are stored during a longer time, the battery of the power supply
module is used for the continuous buffering of the event data in the working
memory of the processor module. Therefore the battery is permanently required
and discharges rapidly. In order to avoid this continuous discharge, it is
recommended to remove the power supply module from the mounting rack
during long storage periods. The contents of the event memory should be
previously read out and stored separately!

P437/EN M/R-11-A // P437311650

13-1

P437

13-2

13 Storage

P437/EN M/R-11-A // P437311650

P437
14

Accessories and Spare Parts


The P437 is supplied with standard labeling for the LED indicators. LED indicators
that are not already configured and labeled can be labeled using the label strips
supplied. Affix the label strips to the front of the unit at the appropriate location.
The label strips can be filled in using a Stabilo brand pen containing waterresistant ink (Type OH Pen 196 PS).

Description

Order No.

Cable bushings

88512-4-0337414-301

Resistor 200

255.002.696

84 TE frame

88512-4-9650723-301

Operating program for Windows

On request (MiCOM S1)

P437/EN M/R-11-A // P437311650

14-1

P437

14-2

14 Accessories and Spare Parts

P437/EN M/R-11-A // P437311650

P437
15

Order Information

Module Configuration Variants


Order Information MiCOM P437
Distance Protection Device

P 4 37-

-311 -4xx -650

-7xx

-46x -9x x -9x x

-8xx

Basic device:
Basic device 84TE, pin-terminal connection,
Basic device 84TE, ring-terminal connection,

7
8

-412
-413

basic complement with 4 binary inputs, 8output relays


and 6 function keys
Mounting option and display:
Surface-mounted, local control panel with text display
Flush-mounted, local control panel with text display

3
4

Current transformer:
Inom =1A / 5 A (T1...
T4) 2)

Parallel Line Mutual Compensation CT:


Without
Inom =1A / 5 A (T24) 2)

0
9

Voltage transformer:
Vnom =50 ...130 V (4-pole)
Vnom =50 ...130 V (5-pole) for Automatic Synchronism Check

4
5

Additional binary I/O options:


Without
With 1binary module (add. 6 binary inputs and 8output relays)
With 2 binary modules (add. 12 binary inputs and 16 output relays)
With 3 binary modules (add. 18 binary inputs and 24 output relays) 23)
With 4 binary modules (add. 24 binary inputs and 32 output relays) 3)

0
1
2
3
4

Power supply and additional binary I/O options:


VA,nom =24 60 VDC

VA,nom =60 ...250 VDC / 100 ...230 VAC

VA,nom =24 ...60 VDC and 6 output relays

VA,nom =60 ...250 VDC / 100 ...230 VAC and 6 output relays

VA,nom =24 60 VDC and 4 high break contacts

VA,nom =60 ...250 VDC / 100 ...230 VAC and 4 high break contacts

Further add. options:


Without
With analog module

P437/EN M/R-11-A // P437311650

0
2

15-1

P437

15 Order Information

Further Options
Order information MiCOM P437
Distance Protection Device

P 4 37-

-311 -4xx -650

-7xx

-46x -9x x -9x x

-8xx

Switching threshold on binary inputs:


>18 V (standard variant)

Without order extension No.

>90 V (60...70%of VA,nom =125...1


50 V) 8)

-461
-462
-463
-464

>155V (60...70%of VA,nom =220...250 V) 8)


>73 V (67%of VA,nom =110 V) 8)
>146 V (67%of VA,nom =220 V) 8)
With communication / information interface:
Without

Without order extension No.


-90

Protocol can be switched between:


IEC 60870-5-101/-103, Modbus, DNP3, Courier
and IRIG-B input for clock synchronization
and 2nd interface (RS485, IEC 60870-5-103)

1
2
4

For connection to wire, RS485, isolated


For connection to plastic fiber, FSMA connector
For connection to glass fiber, ST connector

-90

Protocol IEC 61850, single connection

For connection to 100 Mbit/s Ethernet, glass fiber SC and wire RJ 45


and 2nd interface (RS485, IEC 60870-5-103)

For connection to 100 Mbit/s Ethernet, glass fiber ST and wire RJ 45


and 2nd interface (RS485, IEC 60870-5-103)

-98

Protocol IEC 61850, redundant connection

For connection to 100 Mbit/s Ethernet, glass fiber ST, SHP


and IRIG-B input for clock synchronization
and 2nd interface (RS485, IEC 60870-5-103)

For connection to 100 Mbit/s Ethernet, glass fiber ST, RSTP


and IRIG-B input for clock synchronization
and 2nd interface (RS485, IEC 60870-5-103)

For connection to 100 Mbit/s Ethernet, glass fiber ST, dual homing
and IRIG-B input for clock synchronization
and 2nd interface (RS485, IEC 60870-5-103)
With guidance / protection interface:
Without

Without order extension No.


-95
-96

Protocol InterMiCOM, Channel 1


Protocol InterMiCOM, Channel 2

1
4

For connection to wire, RS485, isolated


For connection to glass fiber, ST connector
Language:
English (German)4)

Without order extension No.

German (English)4)
French(English)4)
Spanish (English)4)
Polish (English)4)
Russian (English)4) 7)

15-2

Not yet available - on request


Not yet available - on request
Not yet available - on request

-801
-802
-803
-804
-805

P437/EN M/R-11-A // P437311650

P437

15 Order Information

Key

2) Switching via parameter, default setting is underlined!

3) This option is excluded if the InterMiCOM interface (95x) is


ordered.

4) Second included language in brackets.

7) Hardware option, supports Cyrillic letters instead of special West


European characters.

8) Standard variant recommended if higher pickup threshold not


explicitly required by the application.

23) This option is excluded if the InterMiCOM Channel 2 interface


(96x) is ordered.

Information about Ordering Options


Language version
In order to display the Russian data model, the corresponding order extension
number (805) must be added upon ordering so that the hardware option
supporting Cyrillic characters is integrated. With this ordering option, reference
menu texts (English) will be available for display. However, other Western
European languages containing extra characters will not be fully supported.
Consequently, selecting the Russian / English ordering option means that it will
not be possible to download Western European data models into the device.
Binary Inputs' Switching Threshold
The standard version of binary signal inputs (opto-couplers) is recommended in
most applications, as these inputs operate with any voltage from 18 V. Special
versions with higher pick-up/drop-off thresholds (see also Technical Data,
Chapter 2, (p. 2-1)) are provided for applications where a higher switching
threshold is expressly required.

P437/EN M/R-11-A // P437311650

15-3

P437

15-4

15 Order Information

P437/EN M/R-11-A // P437311650

P437
A1

Function Groups
ARC

Auto-reclosing control

ASC

Automatic synchronism check

BUOC

Backup overcurrent-time protection

CBF

Circuit breaker failure protection

CBM

Circuit breaker condition monitoring

COMM1

Logical communication interface 1

COMM2

Logical communication interface 2

COMM3

InterMiCOM interface

COMM4

InterMiCOM interface

COUNT

Binary counts

DIST

Distance protection

DTOC

Definite-time overcurrent protection

DVICE

Device

F_KEY

Configurable function keys

f<>

Over-/underfrequency protection

FT_DA

Fault data acquisition

FT_RC

Fault recording

GF_RC

Ground fault recording

GFSC

Ground fault (short-circuit) protection

GOOSE

Generic Object Orientated Substation Events

GSCSG

Ground fault (short-circuit) protection signaling

GSSE

IEC Generic Substation Status Events

IDMT

Inverse-time overcurrent protection

IEC

IEC 61850 Communication

INP

Binary input

IRIGB

IRIGB interface

LED

LED indicators

LIMIT

Limit value monitoring

LOC

Local control panel

P437/EN M/R-11-A // P437311650

A1-1

P437

A1-2

A1 Function Groups

LOG_2

Programmable Logic

LOGIC

Programmable Logic

MAIN

Main function

MCMON

Measuring-circuit monitoring

MEASI

Measured data input

MEASO

Measured data output

MT_RC

Monitoring signal recording

OL_DA

Overload data acquisition

OL_RC

Overload recording

OP_RC

Operating data recording

OUTP

Binary and analog output

P<>

Power directional protection

PC

PC link

PSB

Power swing blocking

PSIG

Protective signaling

PSS

Parameter subset selection

SFMON

Self-monitoring

SOTF

Switch on to fault protection

THERM

Thermal overload protection

V<>

Time-voltage protection

P437/EN M/R-11-A // P437311650

P437
A2

Internal Signals
ARC: 3-pole RRC

Fig. 3-204, (p. 3-271)

ARC: 3-pole transfer int.

Fig. 3-204, (p. 3-271)

ARC: CB closed

Fig. 3-187, (p. 3-243)

ARC: Close command

Fig. 3-204, (p. 3-271)

ARC: Enable dist.tripZ1ze

Fig. 3-201, (p. 3-269)

ARC: External trip A

Fig. 3-204, (p. 3-271)

ARC: External trip B

Fig. 3-204, (p. 3-271)

ARC: External trip C

Fig. 3-204, (p. 3-271)

ARC: HSR A

Fig. 3-204, (p. 3-271)

ARC: HSR A-B-C

Fig. 3-204, (p. 3-271)

ARC: HSR B

Fig. 3-204, (p. 3-271)

ARC: HSR C

Fig. 3-204, (p. 3-271)

ARC: Meas.r.extd. ext.ARC

Fig. 3-201, (p. 3-269)

ARC: Switch to tPmax

Fig. 3-202, (p. 3-270)

ARC: TDR

Fig. 3-204, (p. 3-271)

ARC: TDR permitted

Fig. 3-204, (p. 3-271)

ARC: Test HSR A, internal

Fig. 3-196, (p. 3-257)

ARC: Test HSR B, internal

Fig. 3-196, (p. 3-257)

ARC: Test HSR C, internal

Fig. 3-196, (p. 3-257)

ARC: Trip time elapsed

Fig. 3-189, (p. 3-245)

ARC: tRRC running

Fig. 3-204, (p. 3-271)

ARC: V> for RRC triggered

Fig. 3-198, (p. 3-260)

ARC: Zone extension HSR

Fig. 3-200, (p. 3-267)

ARC: Zone extension RC

Fig. 3-200, (p. 3-267)

ARC: Zone extension TDR

Fig. 3-200, (p. 3-267)

ASC: Active

Fig. 3-208, (p. 3-275)

ASC: Close enable w.block

Fig. 3-208, (p. 3-275)

ASC: Close reject.w.block

Fig. 3-208, (p. 3-275)

ASC: Gen. close request

Fig. 3-209, (p. 3-276)


Fig. 3-210, (p. 3-277)

P437/EN M/R-11-A // P437311650

A2-1

P437

A2 Internal Signals

ASC: Manual close request

Fig. 3-209, (p. 3-276)


Fig. 3-210, (p. 3-277)

ASC: Select. meas.loop PG

Fig. 3-206, (p. 3-273)

ASC: Test

Fig. 3-209, (p. 3-276)


Fig. 3-210, (p. 3-277)

ASC: Vmeas

Fig. 3-206, (p. 3-273)

BUOC: Bl.Zero-sequ.start.

Fig. 3-61, (p. 3-90)

BUOC: Block. Starting

Fig. 3-61, (p. 3-90)

BUOC: IA> triggered

Fig. 3-152, (p. 3-207)

BUOC: IB> triggered

Fig. 3-152, (p. 3-207)

BUOC: IC> triggered

Fig. 3-152, (p. 3-207)

BUOC: SN

Fig. 3-152, (p. 3-207)

BUOC: Trip A

Fig. 3-152, (p. 3-207)

BUOC: Trip B

Fig. 3-152, (p. 3-207)

BUOC: Trip C

Fig. 3-152, (p. 3-207)

CBF: IN

Fig. 3-314, (p. 3-398)

CBF: Start >1p

Fig. 3-316, (p. 3-401)

CBF: Start A

Fig. 3-316, (p. 3-401)

COMM1: Communication error

Fig. 3-7, (p. 3-12)


Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)
Fig. 3-10, (p. 3-15)
Fig. 3-11, (p. 3-16)
Fig. 3-12, (p. 3-17)

A2-2

COMM1: Count 1

Fig. 3-345, (p. 3-431)

COMM1: Selected protocol

Fig. 3-6, (p. 3-11)

DIST: |Zmeas|

Fig. 3-117, (p. 3-162)

DIST: 1-pole starting

Fig. 3-106, (p. 3-147)

DIST: Bl.Start. I>>

Fig. 3-61, (p. 3-90)

DIST: Bl.Start. Z<

Fig. 3-61, (p. 3-90)

DIST: Dir.using Vmeas y

Fig. 3-113, (p. 3-157)

DIST: Dir.using Vmem y

Fig. 3-113, (p. 3-157)

DIST: Dist. decis. Z1ze, A

Fig. 3-129, (p. 3-177)

DIST: Dist. decis. Z1ze, B

Fig. 3-129, (p. 3-177)


P437/EN M/R-11-A // P437311650

P437

A2 Internal Signals

DIST: Dist. decis. Z1ze, C

Fig. 3-129, (p. 3-177)

DIST: Dist. decision Z1, A

Fig. 3-129, (p. 3-177)

DIST: Dist. decision Z1, B

Fig. 3-129, (p. 3-177)

DIST: Dist. decision Z1, C

Fig. 3-129, (p. 3-177)

DIST: Dist.decis.Z1 stored

Fig. 3-120, (p. 3-165)


Fig. 3-124, (p. 3-170)

DIST: Dist.decision Z1, x

Fig. 3-120, (p. 3-165)


Fig. 3-124, (p. 3-170)

DIST: Dist.decision Z1ze,x

Fig. 3-120, (p. 3-165)


Fig. 3-124, (p. 3-170)

DIST: Dist.decision zone n

Fig. 3-119, (p. 3-164)


Fig. 3-123, (p. 3-168)

DIST: Enable V<, Z<, A

Fig. 3-100, (p. 3-140)

DIST: Enable V<, Z<, B

Fig. 3-100, (p. 3-140)

DIST: Enable V<, Z<, C

Fig. 3-100, (p. 3-140)

DIST: Enable ZA-B starting

Fig. 3-102, (p. 3-142)

DIST: Enable ZA-G starting

Fig. 3-102, (p. 3-142)

DIST: Enable ZB-C starting

Fig. 3-102, (p. 3-142)

DIST: Enable ZB-G starting

Fig. 3-102, (p. 3-142)

DIST: Enable ZC-A starting

Fig. 3-102, (p. 3-142)

DIST: Enable ZC-G starting

Fig. 3-102, (p. 3-142)

DIST: Enable ZP-G

Fig. 3-102, (p. 3-142)

DIST: Fault backwd / BS, x

Fig. 3-113, (p. 3-157)

DIST: Fault forwd. / LS, x

Fig. 3-113, (p. 3-157)

DIST: Forw. w/o meas. y

Fig. 3-113, (p. 3-157)

DIST: I>> triggered

Fig. 3-97, (p. 3-137)

DIST: I>>> triggered

Fig. 3-97, (p. 3-137)

DIST: IA,corr.

Fig. 3-109, (p. 3-152)

DIST: IA(1+kG)

Fig. 3-104, (p. 3-144)

DIST: IA>(Ibl) trigg.

Fig. 3-100, (p. 3-140)

DIST: IA>> triggered

Fig. 3-97, (p. 3-137)

DIST: IB,corr.

Fig. 3-109, (p. 3-152)

DIST: IB(1+kG)

Fig. 3-104, (p. 3-144)

P437/EN M/R-11-A // P437311650

A2-3

P437

A2-4

A2 Internal Signals

DIST: IB>(Ibl) trigg.

Fig. 3-100, (p. 3-140)

DIST: IB>> triggered

Fig. 3-97, (p. 3-137)

DIST: IC,corr.

Fig. 3-109, (p. 3-152)

DIST: IC(1+kG)

Fig. 3-104, (p. 3-144)

DIST: IC>(Ibl) trigg.

Fig. 3-100, (p. 3-140)

DIST: IC>> triggered

Fig. 3-97, (p. 3-137)

DIST: IkG,par

Fig. 3-109, (p. 3-152)

DIST: Imeas

Fig. 3-110, (p. 3-153)

DIST: INkG

Fig. 3-104, (p. 3-144)

DIST: Multipole starting

Fig. 3-106, (p. 3-147)

DIST: N1,bw

Fig. 3-128, (p. 3-176)

DIST: N1,bw, A

Fig. 3-128, (p. 3-176)

DIST: N1,bw, B

Fig. 3-128, (p. 3-176)

DIST: N1,bw, C

Fig. 3-128, (p. 3-176)

DIST: N1,fw

Fig. 3-128, (p. 3-176)

DIST: N1,fw, A

Fig. 3-128, (p. 3-176)

DIST: N1,fw, B

Fig. 3-128, (p. 3-176)

DIST: N1,fw, C

Fig. 3-128, (p. 3-176)

DIST: N2,bw

Fig. 3-128, (p. 3-176)

DIST: N2,fw

Fig. 3-128, (p. 3-176)

DIST: N3,bw

Fig. 3-128, (p. 3-176)

DIST: N3,fw

Fig. 3-128, (p. 3-176)

DIST: N4,bw

Fig. 3-128, (p. 3-176)

DIST: N4,fw

Fig. 3-128, (p. 3-176)

DIST: N5,bw

Fig. 3-128, (p. 3-176)

DIST: N5,fw

Fig. 3-128, (p. 3-176)

DIST: N6,bw

Fig. 3-128, (p. 3-176)

DIST: N6,fw

Fig. 3-128, (p. 3-176)

DIST: N7,bw

Fig. 3-128, (p. 3-176)

DIST: N7,fw

Fig. 3-128, (p. 3-176)

DIST: RF

Fig. 3-121, (p. 3-166)

DIST: Select.meas.loop A-B

Fig. 3-108, (p. 3-150)


P437/EN M/R-11-A // P437311650

P437

A2 Internal Signals

DIST: Select.meas.loop A-G

Fig. 3-108, (p. 3-150)

DIST: Select.meas.loop B-C

Fig. 3-108, (p. 3-150)

DIST: Select.meas.loop B-G

Fig. 3-108, (p. 3-150)

DIST: Select.meas.loop C-A

Fig. 3-108, (p. 3-150)

DIST: Select.meas.loop C-G

Fig. 3-108, (p. 3-150)

DIST: Select.meas.loop P-G

Fig. 3-108, (p. 3-150)

DIST: Select.meas.loop P-P

Fig. 3-108, (p. 3-150)

DIST: Signal block start.G

Fig. 3-134, (p. 3-182)

DIST: Start. IN> triggered

Fig. 3-98, (p. 3-138)

DIST: Start.VNG> triggered

Fig. 3-98, (p. 3-138)

DIST: Start.ZPP< triggered

Fig. 3-105, (p. 3-145)

DIST: Starting A

Fig. 3-106, (p. 3-147)

DIST: Starting B

Fig. 3-106, (p. 3-147)

DIST: Starting blocked

Fig. 3-96, (p. 3-135)

DIST: Starting C

Fig. 3-106, (p. 3-147)

DIST: Starting G

Fig. 3-99, (p. 3-139)

DIST: Starting N1

Fig. 3-106, (p. 3-147)

DIST: Timer st. 1 elapsed

Fig. 3-126, (p. 3-174)

DIST: tIN> elapsed

Fig. 3-98, (p. 3-138)

DIST: Trip signal Z1, A

Fig. 3-134, (p. 3-182)

DIST: Trip signal Z1, B

Fig. 3-134, (p. 3-182)

DIST: Trip signal Z1, C

Fig. 3-134, (p. 3-182)

DIST: Trip zone 1

Fig. 3-130, (p. 3-178)

DIST: Trip zone 1, A

Fig. 3-130, (p. 3-178)

DIST: Trip zone 1, B

Fig. 3-130, (p. 3-178)

DIST: Trip zone 1, C

Fig. 3-130, (p. 3-178)

DIST: Trip zone 1,ze

Fig. 3-130, (p. 3-178)

DIST: Trip zone 1,ze, A

Fig. 3-130, (p. 3-178)

DIST: Trip zone 1,ze, B

Fig. 3-130, (p. 3-178)

DIST: Trip zone 1,ze, C

Fig. 3-130, (p. 3-178)

DIST: Trip zone 2

Fig. 3-131, (p. 3-179)

DIST: Trip zone 3

Fig. 3-131, (p. 3-179)

P437/EN M/R-11-A // P437311650

A2-5

P437

A2 Internal Signals

DIST: Trip zone 4

Fig. 3-131, (p. 3-179)

DIST: Trip zone 5

Fig. 3-131, (p. 3-179)

DIST: Trip zone 6

Fig. 3-131, (p. 3-179)

DIST: Trip zone 7

Fig. 3-131, (p. 3-179)

DIST: Trip zone 8

Fig. 3-131, (p. 3-179)

DIST: tVNG>> elapsed

Fig. 3-98, (p. 3-138)

DIST: VA-B (stored)

Fig. 3-111, (p. 3-154)

DIST: VA< triggered

Fig. 3-101, (p. 3-141)

DIST: VB< triggered

Fig. 3-101, (p. 3-141)

DIST: VC< triggered

Fig. 3-101, (p. 3-141)

DIST: Vmeas

Fig. 3-110, (p. 3-153)

DIST: VNG>> exceeded

Fig. 3-98, (p. 3-138)

DIST: Voltage mem. enabled

Fig. 3-111, (p. 3-154)

DIST: VPP< triggered

Fig. 3-101, (p. 3-141)

DIST: XF

Fig. 3-121, (p. 3-166)

DIST: ZA< start. triggered

Fig. 3-105, (p. 3-145)

DIST: ZB< start. triggered

Fig. 3-105, (p. 3-145)

DIST: ZC< start. triggered

Fig. 3-105, (p. 3-145)

DIST:

Fig. 3-119, (p. 3-164)


Fig. 3-120, (p. 3-165)
Fig. 3-124, (p. 3-170)

A2-6

DIST: corr

Fig. 3-111, (p. 3-154)

DIST: F

Fig. 3-112, (p. 3-155)

DIST: X

Fig. 3-112, (p. 3-155)

DTOC: Bl.Start. I>

Fig. 3-61, (p. 3-90)

DTOC: Bl.Start. I>>

Fig. 3-61, (p. 3-90)

DTOC: Bl.Start. I>>>

Fig. 3-61, (p. 3-90)

DTOC: Bl.Start. I>>>>

Fig. 3-61, (p. 3-90)

DTOC: Bl.Start. Ineg>>>>

Fig. 3-61, (p. 3-90)

DTOC: Block. Start. IN>

Fig. 3-61, (p. 3-90)

DTOC: Block. Start. IN>>

Fig. 3-61, (p. 3-90)

DTOC: Block. Start. IN>>>

Fig. 3-61, (p. 3-90)

P437/EN M/R-11-A // P437311650

P437

A2 Internal Signals

DTOC: Block. Start. IN>>>>

Fig. 3-61, (p. 3-90)

DTOC: Block.Start. Ineg>

Fig. 3-61, (p. 3-90)

DTOC: Block.Start. Ineg>>

Fig. 3-61, (p. 3-90)

DTOC: Block.Start. Ineg>>>

Fig. 3-61, (p. 3-90)

DTOC: IN

Fig. 3-252, (p. 3-327)

DTOC: Pulse prolong. runn.

Fig. 3-260, (p. 3-335)

DTOC: t2 N

Fig. 3-260, (p. 3-335)

f<>: fMeas

Fig. 3-295, (p. 3-375)

f<>: No. periods reached

Fig. 3-295, (p. 3-375)

f<>: VMeas

Fig. 3-294, (p. 3-374)

FT_DA: IMeas

Fig. 3-90, (p. 3-126)

FT_DA: Outp. fault location

Fig. 3-88, (p. 3-124)

FT_DA: Output meas. values

Fig. 3-88, (p. 3-124)

FT_DA: Select. meas.loop PG

Fig. 3-90, (p. 3-126)

FT_DA: Select.meas.loop A-B

Fig. 3-90, (p. 3-126)

FT_DA: Select.meas.loop A-G

Fig. 3-90, (p. 3-126)

FT_DA: Select.meas.loop B-C

Fig. 3-90, (p. 3-126)

FT_DA: Select.meas.loop B-G

Fig. 3-90, (p. 3-126)

FT_DA: Select.meas.loop C-A

Fig. 3-90, (p. 3-126)

FT_DA: Select.meas.loop C-G

Fig. 3-90, (p. 3-126)

FT_DA: Trigger N

Fig. 3-99, (p. 3-139)

FT_DA: VMeas

Fig. 3-90, (p. 3-126)

FT_RC: Fault recording n

Fig. 3-94, (p. 3-132)

FT_RC: Trigger N

Fig. 3-99, (p. 3-139)

GFSC: Blocked

Fig. 3-221, (p. 3-293)

GFSC: Curr.-dep. trip sig.

Fig. 3-234, (p. 3-306)

GFSC: IN filtered

Fig. 3-223, (p. 3-294)

GFSC: VNG

Fig. 3-222, (p. 3-293)

GFSC: VNG filtered

Fig. 3-223, (p. 3-294)

GFSC: Volt.-dep. trip sig.

Fig. 3-229, (p. 3-301)

GFSC: Voltage present

Fig. 3-222, (p. 3-293)


Fig. 3-223, (p. 3-294)

P437/EN M/R-11-A // P437311650

A2-7

P437

A2 Internal Signals

GSCSG: Bl. PSIG weak infeed

Fig. 3-243, (p. 3-317)

GSCSG: Blocking ARC

Fig. 3-246, (p. 3-320)

GSCSG: Frequ.mon. triggered

Fig. 3-241, (p. 3-315)

GSCSG: Send internal signal

Fig. 3-243, (p. 3-317)


Fig. 3-244, (p. 3-318)
Fig. 3-247, (p. 3-321)
Fig. 3-248, (p. 3-322)

GSCSG: Transient blocking

Fig. 3-242, (p. 3-315)

GSCSG: Trip A

Fig. 3-246, (p. 3-320)

GSCSG: Trip B

Fig. 3-246, (p. 3-320)

GSCSG: Trip C

Fig. 3-246, (p. 3-320)

IDMT: Bl.Start.Iref,N>

Fig. 3-61, (p. 3-90)

IDMT: Bl.Start.Iref,neg>

Fig. 3-61, (p. 3-90)

IDMT: Bl.Start.Iref,P> Px

Fig. 3-61, (p. 3-90)

IDMT: IN

Fig. 3-271, (p. 3-348)

IDMT: Starting A

Fig. 3-269, (p. 3-345)

IDMT: Starting B

Fig. 3-269, (p. 3-345)

IDMT: Starting C

Fig. 3-269, (p. 3-345)

INP: Fct. assignm. U xxx

Fig. 3-24, (p. 3-42)


Fig. 3-34, (p. 3-52)
Fig. 3-58, (p. 3-88)
Fig. 3-79, (p. 3-112)
Fig. 3-151, (p. 3-205)
Fig. 3-156, (p. 3-213)
Fig. 3-186, (p. 3-242)
Fig. 3-207, (p. 3-274)
Fig. 3-209, (p. 3-276)
Fig. 3-210, (p. 3-277)
Fig. 3-220, (p. 3-291)
Fig. 3-238, (p. 3-310)
Fig. 3-312, (p. 3-396)
Fig. 3-315, (p. 3-399)
Fig. 3-316, (p. 3-401)
Fig. 3-335, (p. 3-423)
Fig. 3-343, (p. 3-429)

A2-8

INP: Oper. mode U xxx

Fig. 3-24, (p. 3-42)

INP: State U xxx

Fig. 3-24, (p. 3-42)

P437/EN M/R-11-A // P437311650

P437

A2 Internal Signals

LED: Fct.assig. Hxx red

Fig. 3-41, (p. 3-68)

LED: Oper. mode H xx

Fig. 3-41, (p. 3-68)

LED: State Hxx red

Fig. 3-41, (p. 3-68)

MAIN: Blck.1 sel.functions

Fig. 3-62, (p. 3-91)

MAIN: Blck.2 sel.functions

Fig. 3-62, (p. 3-91)

MAIN: Protection active

Fig. 3-58, (p. 3-88)

MAIN: Reset LED

Fig. 3-75, (p. 3-107)

MAIN: Time tag

Fig. 3-74, (p. 3-104)

MAIN: Trip A

Fig. 3-67, (p. 3-98)


Fig. 3-68, (p. 3-99)

MAIN: Trip B

Fig. 3-67, (p. 3-98)


Fig. 3-68, (p. 3-99)

MAIN: Trip C

Fig. 3-67, (p. 3-98)


Fig. 3-68, (p. 3-99)

MAIN: Trip signal 1

Fig. 3-69, (p. 3-100)

MEASO: Enable

Fig. 3-34, (p. 3-52)

MEASO: Output value x

Fig. 3-37, (p. 3-57)


Fig. 3-39, (p. 3-63)

MEASO: Reset meas.val.outp.

Fig. 3-35, (p. 3-53)

OUTP: Fct.assignment K xxx

Fig. 3-31, (p. 3-50)


Fig. 3-39, (p. 3-63)

OUTP: Oper. mode K xxx

Fig. 3-31, (p. 3-50)

OUTP: State K xxx

Fig. 3-31, (p. 3-50)

P<>: P

Fig. 3-299, (p. 3-381)

P<>: P-

Fig. 3-299, (p. 3-381)

P<>: P+

Fig. 3-299, (p. 3-381)

P<>: Q

Fig. 3-299, (p. 3-381)

P<>: Q-

Fig. 3-299, (p. 3-381)

P<>: Q+

Fig. 3-299, (p. 3-381)

PSB: Asyn. power swing

Fig. 3-136, (p. 3-184)

PSB: Ready

Fig. 3-135, (p. 3-183)

PSIG: Ch. 1 receive weak inf.

Fig. 3-180, (p. 3-234)

PSIG: Ch. 2 receive weak inf.

Fig. 3-180, (p. 3-234)

P437/EN M/R-11-A // P437311650

A2-9

P437

A2 Internal Signals

PSIG: Ch. 3 receive weak inf.

Fig. 3-180, (p. 3-234)

PSIG: Frequ. monit. trigg.

Fig. 3-160, (p. 3-216)

PSIG: Inhibit weak inf. A

Fig. 3-181, (p. 3-235)

PSIG: Inhibit weak inf. B

Fig. 3-181, (p. 3-235)

PSIG: Inhibit weak inf. C

Fig. 3-181, (p. 3-235)

PSIG: Receive

Fig. 3-173, (p. 3-228)

PSIG: Timer stage elapsed

Fig. 3-157, (p. 3-214)

PSIG: Transient blocking

Fig. 3-161, (p. 3-217)

PSIG: Trip channel 1

Fig. 3-165, (p. 3-220)


Fig. 3-167, (p. 3-222)
Fig. 3-170, (p. 3-224)
Fig. 3-173, (p. 3-228)
Fig. 3-176, (p. 3-231)

PSIG: Trip channel 2

Fig. 3-165, (p. 3-220)


Fig. 3-167, (p. 3-222)
Fig. 3-170, (p. 3-224)
Fig. 3-173, (p. 3-228)
Fig. 3-176, (p. 3-231)

PSIG: Trip channel 3

Fig. 3-165, (p. 3-220)


Fig. 3-167, (p. 3-222)
Fig. 3-170, (p. 3-224)
Fig. 3-173, (p. 3-228)
Fig. 3-176, (p. 3-231)

PSIG: Trip enable

Fig. 3-170, (p. 3-224)


Fig. 3-173, (p. 3-228)
Fig. 3-176, (p. 3-231)

PSIG: Trip enable, ch. 1

Fig. 3-170, (p. 3-224)


Fig. 3-173, (p. 3-228)
Fig. 3-176, (p. 3-231)

PSIG: Trip enable, ch. 2

Fig. 3-170, (p. 3-224)


Fig. 3-173, (p. 3-228)
Fig. 3-176, (p. 3-231)

PSIG: Trip enable, ch. 3

Fig. 3-170, (p. 3-224)


Fig. 3-173, (p. 3-228)
Fig. 3-176, (p. 3-231)

A2-10

PSIG: Trip time elapsed

Fig. 3-157, (p. 3-214)

PSIG: Trip V<

Fig. 3-182, (p. 3-236)

PSIG: V< triggered

Fig. 3-182, (p. 3-236)


P437/EN M/R-11-A // P437311650

P437

A2 Internal Signals

PSIG: Weak inf. blocked

Fig. 3-178, (p. 3-233)

PSIG: Weak inf. ready

Fig. 3-179, (p. 3-233)

Signal 1 EXT

Fig. 3-343, (p. 3-429)

Signal 2 EXT

Fig. 3-343, (p. 3-429)

SOTF: ARC blocked

Fig. 3-154, (p. 3-210)

SOTF: Line dead trig. en.

Fig. 3-155, (p. 3-211)

SOTF: Trip time elapsed

Fig. 3-154, (p. 3-210)

THERM: Block. by CTA error

Fig. 3-275, (p. 3-353)

THERM: I

Fig. 3-277, (p. 3-357)

THERM: With CTA

Fig. 3-275, (p. 3-353)

V<>: V< ready

Fig. 3-280, (p. 3-360)

V<>: Vneg

Fig. 3-286, (p. 3-367)

V<>: VNG

Fig. 3-289, (p. 3-370)

V<>: Vpos

Fig. 3-286, (p. 3-367)

P437/EN M/R-11-A // P437311650

A2-11

P437

A2-12

A2 Internal Signals

P437/EN M/R-11-A // P437311650

P437
A3

Glossary

Modules
A:

Communication module

B:

Digital bus module

L:

MMI module

Transient ground fault evaluation module

P:

Processor module

T:

Transformer module

V:

Power supply module

X:

Binary I/O module

Y:

Analog I/O module

Symbols
Graphic symbols for block diagrams
Binary elements in compliance with DIN 40900 part 12, September 1992,
IEC 617-12: modified 1991
Analog information processing in compliance with DIN 40900 part 13, January
1981. To document the linking of analog and binary signals, additional symbols
have been used, taken from several DIN documents.
As a rule, direction of the signal flow is from left to right and from top to bottom.
Other flow directions are marked by an arrow. Input signals are listed on the left
side of the signal flow, output signals on the right side.

P437/EN M/R-11-A // P437311650

A3-1

P437

A3 Glossary

Symbol

Description
To obtain more space for representing a group of related
elements, contours of the elements may be joined or cascaded if
the following rules are met:
There is no functional linkage between elements whose common
contour line is oriented in the signal flow direction.

Note:

D5Z08X1B

This rule does not necessarily apply to configurations with two or


more signal flow directions, such as for symbols with a control
block and an output block.
There exists at least one logical link between elements whose
common contour line runs perpendicularly to the signal flow
direction.
Components of a symbol
A symbol consists of a contour or contour combination and one or
more qualifiers.
Description of the example symbol in the left column

D5Z08X2B

Blue line: Contur

Dark red lines: Inputs

Green lines: Outputs

Green hash characters: Preferred location for the general


function qualifying symbol

Dark blue asterisk characters: Alternative location for the


general function qualifying symbol

Control block
A control block contains an input function common to several
symbols. It is used for the collective setting of several trigger
elements, for example.

D5Z08X3B

Output block
An output block contains an output function common to several
symbols.

D5Z08X4B

A3-2

P437/EN M/R-11-A // P437311650

P437

A3 Glossary

Settable control block


The 6 digits in square brackets represent the address under
which the function shown in the text is implemented.

MAIN:
Inom device
[ 010 003 ]
D5Z08X5B

Settable control block with function blocks


The digits in the function block show the settings that are
possible for this function.

MAIN:
Inom device
[ 010 003 ]
1.0
5.0
1.0: 1.0 A
5.0: 5.0 A

The text below the symbol assigns the corresponding unit or


meaning to each setting.

D5Z08X6B

Static input
Only the state of the binary input variable is effective.
D5Z08XBB

Dynamic input
Only the transition from value 0 to value 1 is effective.
D5Z08XAB

Negation of an output
The value up to the border line is negated at the output.
D5Z08X8B

Negation of an input
The input value is negated before the border line.
D5Z08X7B

Dynamic input with negation


Only the transition from value 1 to value 0 is effective.
D5Z08X9B

AND element
The output variable will be 1 only if all input variables are 1.

&
D5Z08XCB

OR element
D5Z08XDB

P437/EN M/R-11-A // P437311650

The output variable will be 1 only if at least one input variable is


1.

A3-3

P437

A3 Glossary

Threshold element
D5Z08XEB

The output variable will be 1 only if at least two input variables


are 1. The number in the symbol may be replaced by any other
number.
(m out of n) element
The output variable will be 1 only if just one input variable is 1.

D5Z08XFB

The number in the symbol may be replaced by any other number


if the number of inputs is increased or decreased accordingly.
Delay element

t1

t2

D5Z08XGB

The transition from value 0 to 1 at the output occurs after a time


delay of t1 relative to the corresponding transition at the input.
The transition from value 1 to 0 at the output occurs after a time
delay of t2 relative to the corresponding transition at the input.
t1 and t2 may be replaced by the actual delay values (in seconds
or strobe ticks).
Monostable flip-flop

1
100ms
D5Z08XHB

The output variable will be 1 only if the input variable changes to


1. The output variable will remain 1 for 100 ms, regardless of the
duration of the input value 1 (non-retriggerable).
Without a 1 in the function block, the monostable flip-flop is
retriggerable.
The time is 100 ms in this example, but it may be changed to any
other duration.
Analog-digital converter
An analog input signal is converted to a binary signal.

D5Z08XJB

Subtractor
D5Z08XKB

The output variable is the difference between the two input


variables.
A summing element is obtained by changing the minus sign to
a plus sign at the symbol input.
Schmitt Trigger with binary output signal

D5Z08XLB

The binary output variable will be 1 if the input signal exceeds a


specific threshold. The output variable remains 1 until the input
signal drops below the threshold again.
Memory, general
Storage of a binary or analog signal.

D5Z08XMB

A3-4

P437/EN M/R-11-A // P437311650

P437

A3 Glossary

Non-stable flip-flop
D5Z08XNB

When the input variable changes to 1, a pulse sequence is


generated at the output.
The ! to the left of the G indicates that the pulse sequence starts
with the input variable transition (synchronized start).
If there is a ! to the right of the G, the pulse sequence ends with
the ending of the 1 signal at the input (synchronized stop).
Amplifier
The output variable is 1 only if the input variable is also 1.

D5Z08XOB

Band pass filter


50Hz

D5Z08XPB

The output only transmits the 50 Hz component of the input


signals. All other frequencies (above and below 50 Hz) are
attenuated.
Counter

+
R
D5Z08YFB

At the + input the input variable transitions from 0 to 1 are


counted and stored in the function block.
At the R(eset) input a transition of the input variable from 0 to 1
resets the counter to 0.
Electromechanical drive in general, here a relay, for example.

D5Z08YGB

Signal level converter

L+

with electrical isolation between input and output.

V1
LD5Z08XQB

L+ = pos. voltage input


L = neg. voltage input
U1 = device identifier

P437/EN M/R-11-A // P437311650

A3-5

P437

A3 Glossary

Input transformer with phase and item identifiers (according to


DIN EN 60445)

A.1
A.2

IA

T1
D5Z08XRB

Phase identifiers for current inputs:

for A: A1 and A2

for B: B1 and B2

for C: C1 and C2

for N: N1 and N2

Phase identifiers for voltage inputs

via transformer 1:

for
for
for
for

A: 1U
B: 1V
C: 1W
N: 1N

via transformer 2:

for A: 2U
for B: 2V

Item identifiers

for current transformers:

for
for
for
for

A: T1
B: T2
C: T3
N: T4

for voltage transformer 1:

for
for
for
for

A: T5
B: T6
C: T7
N: T8

for VG-N transformer: T90

for voltage transformer 2:

for A: T15

Change-over contact
with item identifier
D5Z08XSB

Special symbol
D5Z08XTB

A3-6

Output relay in normally-energized arrangement (closed-circuit


operation).

P437/EN M/R-11-A // P437311650

P437

A3 Glossary

V24

PC interface
12V

+12V

0V

RXD

TXD

with pin connections

D5Z08XVB

Multiplier
D5Z08XWB

The output variable is the result of the multiplication of the two


input variables.
Divider

D5Z08XXB

The output variable is the result of the division of the two input
variables.
Comparator
The output variable becomes 1 only if the input variable(s) are
equal to the function in the function block.

D5Z08XYB

Formula block
The output variable becomes 1 only if the input variable(s) satisfy
the equation in the function block

2.5

D5Z08XZB

Examples of Signal Names


All settings and signals relevant for protection are shown in the block diagrams of
Chapter Operation as follows:
Signal Name

Description

FT_RC: Fault recording n

Internal signal names are not coded by a data model address.


In the block diagrams they are marked with a diamond. The
small figure underneath the signal name represents a code that
is irrelevant to the user.

305 100

The internal signal names used and their origins are listed in
Appendix.
DIST: VNG>> triggered
[ 036 015 ]

Signal names coded by a data model address are represented


by their address (shown in square brackets). Their origin is
given in Chapters Setting and Information and Control
Functions.

MAIN: General reset USER


[ 003 002 ]
1: Execute

A specific setting to be used later on is shown with its signal


name, address, and the setting preceded by the setting arrow.

P437/EN M/R-11-A // P437311650

A3-7

P437

A3 Glossary

Symbols Used
Symbol

Meaning

Time duration

Voltage, potential difference

Complex voltage

Electrical current

Complex current

Complex impedance

|Z|

Modulus of complex impedance

Frequency

Temperature in C

Sum, result

Unit of electrical resistance

Angle

Phase angle. With subscripts: specific angle between a defined current


and a defined voltage.

Time constant

Temperature difference in K

A3-8

P437/EN M/R-11-A // P437311650

P437
A4

Telecontrol Interfaces

A4.1

Telecontrol Interface per EN 60870-5-101 or IEC 870-5-101


(Companion Standard)
This section incorporates Section 8 of EN 60870-5-101 (1996), which includes a
general definition of the telecontrol interface for substation control systems.

A4.1.1

Interoperability
This application-based standard (companion standard) specifies parameter sets
and other options from which subsets are to be selected in order to implement
specific telecontrol systems. Certain parameters such as the number of bytes
(octets) in the COMMON ADDRESS of the ASDU are mutually exclusive. This
means that only one value of the defined parameter is allowed per system. Other
parameters, such as the listed set of different process information in the
command and monitor direction, permit definition of the total number or of
subsets that are suitable for the given application. This section combines the
parameters given in the previous sections in order to facilitate an appropriate
selection for a specific application. If a system is made up of several system
components supplied by different manufacturers, then it is necessary for all
partners to agree on the selected parameters.
The boxes for the selected parameters should be checked [see National Preface
of EN 60870-5-101].
The overall definition of a system may also require individual selection of certain
parameters for specific parts of a system such as individual selection of scaling
factors for individually addressable measured values.

A4.1.1.1

Network Configuration (Network-Specific Parameters)

[]

Point-to-point configuration

[]

Multipoint-party line configuration

[]

Multiple point-to-point configuration

[]

Multipoint-star configuration

P437/EN M/R-11-A // P437311650

A4-1

P437
A4.1.1.2

A4 Telecontrol Interfaces

Physical Layer (Network-Specific Parameters)


(See National Preface of EN 60870-5-101.)
Transmission Rate (Control Direction)
(The transmission rates for control direction and monitor direction must be
identical.)

Unbalanced interface V.24/V.28,


Standardized

Unbalanced interface V.24/V.28, Balanced interface X.24/X.27


Recommended with > 1 200 bit/s

[] 100 bit/s

[] 2400 bit/s

[] 2400 bit/s

[] 200 bit/s

[] 4800 bit/s

[] 4800 bit/s

[] 300 bit/s

[] 9600 bit/s

[] 9600 bit/s

[] 600 bit/s

[] 19200 bit/s

[] 1200 bit/s

[] 38400 bit/s
[] 56000 bit/s
[] 64000 bit/s

Transmission Rate (Monitor Direction)


(The transmission rates for control direction and monitor direction must be
identical.)
Unbalanced interface V.24/V.28,
Standardized

Unbalanced interface V.24/V.28, Balanced interface X.24/X.27


Recommended with > 1 200 bit/s

[] 100 bit/s

[] 2400 bit/s

[] 2400 bit/s

[] 200 bit/s

[] 4800 bit/s

[] 4800 bit/s

[] 300 bit/s

[] 9600 bit/s

[] 9600 bit/s

[] 600 bit/s

[] 19200 bit/s

[] 1200 bit/s

[] 38400 bit/s
[] 56000 bit/s
[] 64000 bit/s

A4-2

P437/EN M/R-11-A // P437311650

A4 Telecontrol Interfaces

A4.1.1.3

P437

Link Layer (Network-Specific Parameters)


(See National Preface of EN 60870-5-101.)
Frame format FT 1.2, single character 1, and the fixed time-out interval are used
exclusively in this companion standard.
Link Transmission Procedure

[]

Balanced transmission

[]

Unbalanced transmission
Address Field of the Link

[]

Not present (balanced transmission only)

[]

One octet

[]

Two octets (balanced transmission only)

[]

Structured

[]

Unstructured
Frame Length

[240]

Maximum length L (number of octets)

P437/EN M/R-11-A // P437311650

A4-3

P437

A4 Telecontrol Interfaces

A4.1.1.4

Application Layer
(See National Preface of EN 60870-5-101.)
Transmission mode for application data
Mode 1 (least significant octet first), as defined in clause 4.10 of IEC 870-5-4, is
used exclusively in this companion standard.
Common Address of ASDU (System-Specific Parameter)

[]

One octet

[]

Two octets

Information Object Address (System-Specific Parameter)


[]

One octet

[]

Structured

[]

Two octets

[]

Unstructured

[]

Three octets
Cause of Transmission (System-Specific Parameter)

[]

One octet

[]

Two octets (with originator address)

Selection of Standard ASDUs


Process Information in Monitor Direction (Station-Specific Parameter)

A4-4

P437/EN M/R-11-A // P437311650

A4 Telecontrol Interfaces

P437

[]

<1>

Single-point information

M_SP_NA_1

[]

<2>

Single-point information with time tag

M_SP_TA_1

[]

<3>

Double-point information

M_DP_NA_1

[]

<4>

Double-point information with time tag

M_DP_TA_1

[]

<5>

Step position information

M_ST_NA_1

[]

<6>

Step position information with time tag

M_ST_TA_1

[]

<7>

Bit string of 32 bit

M_BO_NA_1

[]

<8>

Bit string of 32 bit with time tag

M_BO_TA_1

[]

<9>

Measured value, normalized value

M_ME_NA_1

[]

<10>

Measured value, normalized value with time tag

M_ME_TA_1

[]

<11>

Measured value, scaled value

M_ME_NB_1

[]

<12>

Measured value, scaled value with time tag

M_ME_TB_1

[]

<13>

Measured value, short floating point value

M_ME_NC_1

[]

<14>

Measured value, short floating point value with time tag M_ME_TC_1

[]

<15>

Integrated totals

M_IT_NA_1

[]

<16>

Integrated totals with time tag

M_IT_TA_1

[]

<17>

Event of protection equipment with time tag

M_EP_TA_1

[]

<18>

Packed start events of protection equipment with time


tag

ME_EP_TB_1

[]

<19>

Packed output circuit information of protection


equipment with time tag

M_EP_TC_1

[]

<20>

Packed single-point information with status change


detection

M_PS_NA_1

[]

<21>

Measured value, normalized value without quality


descriptor

M_ME_ND_1

Process Information in Monitor Direction (Station-Specific Parameter)


(Incorrectly identified with control direction in IEC 870-5-101.)

P437/EN M/R-11-A // P437311650

A4-5

P437

A4 Telecontrol Interfaces

[]

<45>

Single command

C_SC_NA_1

[]

<46>

Double command

C_DC_NA_1

[]

<47>

Regulating step command

C_IT_NA_1

[]

<48>

Set point command, normalized value

C_RC_NA_1

[]

<49>

Set point command, scaled value

C_SE_NB_1

[]

<50>

Set point command, short floating point value

C_SE_NC_1

[]

<51>

Bit string of 32 bit

C_BO_NA_1

System Information in Monitor Direction (Station-Specific Parameter)


[]

<70>

End of initialization

ME_EI_NA_1

System Information in Control Direction (Station-Specific Parameter)


[]

<100>

Interrogation command

C_IC_NA_1

[]

<101>

Counter interrogation command

C_CI_NA_1

[]

<102>

Read command

C_RD_NA_1

[]

<103>

Clock synchronization command

C_CS_NA_1

[]

<104>

Test command

C_TS_NB_1

[]

<105>

Reset process command

C_RP_NC_1

[]

<106>

Delay acquisition command

C_CD_NA_1

(See National Preface of EN 60870-5-101.)


Parameter in Control Direction (Station-Specific Parameter)
[]

<110> =

Parameter of measured value, normalized value

P_ME_NA_1

[]

<111> =

Parameter of measured value, scaled value

P_ME_NB_1

[]

<112> =

Parameter of measured value, short floating point value P_ME_NC_1

[]

<113> =

Parameter activation

P_AC_NA_1

File Transfer (Station-Specific Parameter)

A4-6

P437/EN M/R-11-A // P437311650

A4 Telecontrol Interfaces

P437

[]

<120>

File ready

F_FR_NA_1

[]

<121>

Section ready

F_SR_NA_1

[]

<122>

Call directory, select file, call file, call section

F_SC_NA_1

[]

<123>

Last section, last segment

F_LS_NA_1

[]

<124>

Ack file, ack section

F_AF_NA_1

[]

<125>

Segment

F_SG_NA_1

[]

<126>

Directory

F_DR_TA_1

P437/EN M/R-11-A // P437311650

A4-7

P437

A4 Telecontrol Interfaces

A4.1.1.5

Basic Application Functions


(See National Preface of EN 60870-5-101.)
Station Initialization (Station-Specific Parameter)

[]

Remote initialization
General Interrogation (System- or Station-Specific Parameter)

[] Global
[] Group 1

[] Group 7

[] Group 13

[] Group 2

[] Group 8

[] Group 14

[] Group 3

[] Group 9

[] Group 15

[] Group 4

[] Group 10

[] Group 16

[] Group 5

[] Group 11

[] Group 6

[] Group 12
Addresses per group have to be defined.
Clock Synchronization (Station-Specific Parameter)

[]

Clock synchronization
Command Transmission (Object-Specific Parameter)

[]

Direct command transmission

[]

Select and execute command

[]

Direct set point command


transmission

[]

Select and execute set point


command

[]

C_SE ACTTERM used

[]

No additional definition

[]

Short pulse duration (Execution duration determined by a system parameter in the


outstation)

[]

Long pulse duration (Execution duration determined by a system parameter in the


outstation)

[]

Persistent output
Transmission of Integrated Totals (Station- or Object-Specific
Parameter)

A4-8

P437/EN M/R-11-A // P437311650

P437

A4 Telecontrol Interfaces

[]

Counter request

[]

General request counter

[]

Counter freeze without reset

[]

Request counter group 1

[]

Counter freeze with reset

[]

Request counter group 2

[]

Counter reset

[]

Request counter group 3

[]

Request counter group 4

Addresses per group have to be specified


Parameter Loading (Object-Specific Parameter)
[]

Threshold value

[]

Smoothing value

[]

Low limit for transmission of measured value

[]

High limit for transmission of measured value


Parameter Activation (Object-Specific Parameter)

[]

Act/deact of persistent cyclic or periodic transmission of the addressed object


File Transfer (Station-Specific Parameter)

[]

File transfer in monitor direction

F_FR_NA_1

[]

File transfer in control direction

F_FR_NA_1

A4.2

Communication Interface per IEC 60870-5-103


This section incorporates Section 8 of IEC 60870-5-103, including definitions
applicable to the P437.

A4.2.1

Interoperability

A4.2.1.1

Physical Layer

A4.2.1.1.1

Electrical Interface

[]

EIA RS 485

[]

No. of loads: 32 for one device


Note: EIA RS 485 defines the loads in such a way that 32 of such loads can be
operated on one line. For detailed information see EIA RS 485, Section 3.

P437/EN M/R-11-A // P437311650

A4-9

P437

A4 Telecontrol Interfaces

A4.2.1.1.2

Optical Interface

[]

Glass fiber

[]

Plastic fiber

[]

F-SMA connector

[]

BFOC/2.5 connector

A4.2.1.1.3

Transmission Rate

[]

9600 bit/s

[]

19200 bit/s

A4.2.1.2

Link Layer
There are no selection options for the link layer.

A4.2.1.3

Application Layer

A4.2.1.3.1

Transmission Mode for Application Data


Mode 1 (least significant octet first) as defined in clause 4.10 of IEC 6087054 is
used exclusively in this companion standard.

A4.2.1.3.2

Common Address of ASDU

[]

One COMMON ADDRESS of ASDU (identical to the station address)

[]

More than one COMMON ADDRESS of ASDU

A4.2.1.3.3

Selection of Standard Information Numbers in Monitor Direction

System Functions in Monitor Direction


INF

Description

[]

<0>

End of general interrogation

[]

<0>

Time synchronization

[]

<2>

Reset FCB

[]

<3>

Reset CU

[]

<4>

Start / restart

[]

<5>

Power on

A4-10

P437/EN M/R-11-A // P437311650

P437

A4 Telecontrol Interfaces

Status Indications in Monitor Direction


INF

Description

P437 Designations
(Address) Description

[]

<16>

Auto-recloser active

(015 064) A RC : En able d

[]

<17>

Teleprotection active

(015 008) P SIG: Enabl ed

[]

<18>

Protection active

(003 030) MA IN: Devi ce on-l i ne

[]

<19>

LED reset

(021 010) MA IN: Res et in dicat. USER

[]

<20>

Blocking of monitor direction

(037 075) C OMM1 : Si g./meas .val. blo ck.

[]

<21>

Test mode

(037 071) MA IN: Te st mode

[]

<22>

Local parameter setting

[]

<23>

Characteristic 1

(036 090) P SS: PS 1 active

[]

<24>

Characteristic 2

(036 091) P SS: PS 2 active

[]

<25>

Characteristic 3

(036 092) P SS: PS 3 active

[]

<26>

Characteristic 4

(036 093) P SS: PS 4 active

[]

<27>

Auxiliary input 1

(034 000) L OGIC : I npu t 01 EXT

[]

<28>

Auxiliary input 2

(034 001) L OGIC : I npu t 02 EXT

[]

<29>

Auxiliary input 3

(034 002) L OGIC : I npu t 03 EXT

[]

<30>

Auxiliary input 4

(034 003) L OGIC : I npu t 04 EXT

P437/EN M/R-11-A // P437311650

A4-11

P437

A4 Telecontrol Interfaces

Monitoring Signals (Supervision Indications) in Monitor Direction


INF

Description

P437 Designations
(Address) Description

[]

<32>

Measurand supervision I

(040 087) MCMON: Mea s. circ. I faulty

[]

<33>

Measurand supervision V

(038 023) MCMON: Mea s. circ. V fault y

[]

<35>

Phase sequence supervision

(038 049) MCMON: Ph ase se qu. V f aul ty

[]

<36>

Trip circuit supervision

(041 200) SFMON: Rel ay K xx faulty

(The message content is


formed from the OR operation
of the individual signals.)
[]

<37>

I>> back-up operation

(037 021) BUOC : A ctive

[]

<38>

VT fuse failure

(004 061) MA IN: M.c. b. trip V EXT

[]

<39>

Teleprotection disturbed

(036 060) P SI G: Te le com. fau lty

[]

<46>

Group warning

(036 100) SFMON: Warnin g ( re lay)

[]

<47>

Group alarm

(004 065) MA IN: Blocke d/f aul ty

Earth Fault Indications in Monitor Direction


INF

Description

P437 Designations
(Address) Description

[]

<48>

Earth fault A

[]

<49>

Earth fault B

[]

<50>

Earth fault C

[]

<51>

Earth fault forward, i.e. line

[]

<52>

Earth fault reverse, i.e. busbar

A4-12

P437/EN M/R-11-A // P437311650

P437

A4 Telecontrol Interfaces

Fault Indications in Monitor Direction


INF

Description

P437 Designations
(Address) Description

[]

<64>

Start / pick-up A

(036 001) MA IN: Starti ng A

[]

<65>

Start / pick-up B

(036 002) MA IN: Starti ng B

[]

<66>

Start / pick-up C

(036 003) MA IN: Starti ng C

[]

<67>

Start / pick-up N

(036 004) MA IN: Starti ng GF

[]

<68>

General trip

(036 071) MA IN: Gen . tri p command 1

[]

<69>

Trip A

(036 072) MA IN: Tri p comman d 1, A

[]

<70>

Trip B

(036 073) MA IN: Tri p comman d 1, B

[]

<71>

Trip C

(036 074) MA IN: Tri p comman d 1, C

[]

<72>

Trip I>> (back-up operation)

(036 014) BUOC : Tri p s ignal

[]

<73>

Fault location X in ohms

(004 029) F T_DA : F aul t re act., pri m.

[]

<74>

Fault forward/line

(036 018) D IST: Fault f orw ard / LS

[]

<75>

Fault reverse/busbar

(036 019) D IST: Fault backw ar d / B S

[]

<76>

Teleprotection signal
transmitted

(036 035) P SI G: Sen d ( sign al)

[]

<77>

Teleprotection signal received

(037 029) P SI G: R ece ive (s ignal )

[]

<78>

Zone 1

(036 026) D IST: t1 e l apse d

[]

<79>

Zone 2

(036 027) D IST: t2 e l apse d

[]

<80>

Zone 3

(036 028) D IST: t3 e l apse d

[]

<81>

Zone 4

(036 029) D IST: t4 e l apse d

[]

<82>

Zone 5

(036 030) D IST: t5 e l apse d

[]

<83>

Zone 6

(036 031) D IST: t6 e l apse d

[]

<84>

General starting

(036 000) MA IN: Gen eral startin g

[]

<85>

Breaker failure

(036 017) C BF: CB failu re

[]

<86>

Trip measuring system A

[]

<87>

Trip measuring system B

[]

<88>

Trip measuring system C

[]

<89>

Trip measuring system N

[]

<90>

Trip I>

[]

<91>

Trip I>>

P437/EN M/R-11-A // P437311650

A4-13

P437

A4 Telecontrol Interfaces

INF

Description

P437 Designations
(Address) Description

[]

<92>

Trip IN>

[]

<93>

Trip IN>>

Auto-Reclosure Indications in Monitor Direction


INF

Description

P437 Designations
(Address) Description

[]

<128>

CB on by AR

(037 007) A RC : (Re ) clos e si gn al HSR

[]

<129>

CB on by long-time AR

(037 006) A RC : (Re ) clos e si gn al TDR

[]

<130>

AR blocked

(037 008) A RC : Not re ady

Measurands in Monitor Direction


INF

Description

P437 Designations
(Address) Description

[]

<144>

Measurand I

(006 041) MA IN: Cu rre nt B p. u.

(only with setting


COMM1: Tran sm.e n ab.cycl
.dat to ASDU 3.1 per IEC)
[]

<145>

Measurands I, V

(006 041) MA IN: Cu rre nt B p. u.

(only with setting


(005 045) MA IN: V oltage A -B p.u.
COMM1: Tran sm.e n ab.cycl
.dat to ASDU 3.2 per IEC)
[]

<146>

Measurands I, V, P, Q

(006 041) MA IN: Cu rre nt B p. u.

(only with setting


(005 045) MA IN: V oltage A -B p.u.
COMM1: Tran sm.e n ab.cycl (004 051) MAIN: A ctive powe r P p. u.
.dat to ASDU 3.3 per IEC)
(004 053) MA IN: Reac. pow er Q p.u.
[]

<147>

Measurands IN, VEN

(005 011) MA IN: Current ( IP ) p.u.

(005 013) MAI N: V olt. ( VP G)/3 p.u.


(only with setting
C OM M1 : Tran sm.en ab.cycl
.dat to ASDU 3.4 per IEC)
[]

<148>

Measurands IA,B,C, VA,B,C, P, Q, f (005 041) MAI N: Cu rre nt A p.u.


(006 041) MAIN: Curren t B p.u .
(only with setting
C OMM1 : Transm.e nab.cycl (007 041) MAI N: Cu rre nt C p. u.
.dat to ASDU 9 per IEC)
(005 043) MAIN: V ol tage A-G p.u .
(006 043) MA IN: Voltage B-G p.u .
(007 043) MA IN: Voltage C-G p. u.
(004 051) MA IN: Act ive power P p.u.
(004 053) MAIN: Re ac. powe r Q p.u.
(004 040) MAIN: Fre que ncy f

A4-14

P437/EN M/R-11-A // P437311650

A4 Telecontrol Interfaces

P437

Generic Functions in Monitor Direction


INF

Description

[]

<240>

Read headings of all defined groups

[]

<241>

Read values or attributes of all entries of one group

[]

<243>

Read directory of a single entry

[]

<244>

Read value or attribute of a single entry

[]

<245>

General interrogation of generic data

[]

<249>

Write entry with confirmation

[]

<250>

Write entry with execution

[]

<251>

Write entry abort

A4.2.1.3.4

Selection of Standard Information Numbers in Control Direction

System Functions in Control Direction


INF

Description

[]

<0>

Initiation of general interrogation

[]

<0>

Time synchronization

P437/EN M/R-11-A // P437311650

A4-15

P437

A4 Telecontrol Interfaces

General Commands in Control Direction


INF

Description

P437 Designations
(Address) Description

[]

<16>

Auto-recloser on/off

(015 064) A RC : En able d

[]

<17>

Teleprotection on/off

(015 008) P SIG: Enabl ed

[]

<18>

Protection on/off

(003 030) MA IN: Devi ce on-l i ne

[]

<19>

LED reset

(021 010) MA IN: Res et in dicat. U SER

[]

<23>

Activate characteristic 1

(003 060) P SS: Param .s u bs. se l. USE R

(Switches
PSS: Pa ram.su bs. se l .
USE R to Parameter subset
1.)
[]

<24>

Activate characteristic 2

(003 060) P SS: Param .s u bs. se l. USE R

(Switches
PSS: Pa ram.su bs. se l .
USE R to Parameter subset
2.)
[]

<25>

Activate characteristic 3

(003 060) P SS: Param .s u bs. se l. USE R

(Switches
PSS: Pa ram.su bs. se l .
USE R to Parameter subset
3.)
[]

<26>

Activate characteristic 4

(003 060) P SS: Param .s u bs. se l. USE R

(Switches
PSS: Pa ram.su bs. se l .
USE R to Parameter subset
4.)

A4-16

P437/EN M/R-11-A // P437311650

A4 Telecontrol Interfaces

P437

Generic Functions in Control Direction


INF

Description

[]

<240> Read headings of all defined groups

[]

<241> Read values or attributes of all entries of one group

[]

<243> Read directory of a single entry

[]

<244> Read value or attribute of a single entry

[]

<245> General interrogation of generic data

[]

<248> Write entry

[]

<249> Write entry with confirmation

[]

<250> Write entry with execution

[]

<251> Write entry abort

P437/EN M/R-11-A // P437311650

A4-17

P437

A4 Telecontrol Interfaces

A4.2.1.3.5

Basic Application Functions

[]

Test mode

[]

Blocking of monitor direction

[]

Disturbance data

[]

Generic services

[]

Private data

A4.2.1.3.6

Miscellaneous
Measured values are transmitted both with ASDU 3 and ASDU 9. As defined in
Sec. 7.2.6.8, the maximum MVAL can be either 1.2 or 2.4 times the rated value.
In ASDU 3 and ASDU 9, different ratings may not be used; in other words, there is
only one choice for each measurand.

Measured value

Max. MVAL = nom. value multiplied by

1.2

or

2.4

Current A

[]

[]

Current B

[]

[]

Current C

[]

[]

Voltage A-G

[]

[]

Voltage B-G

[]

[]

Voltage C-G

[]

[]

Enabled power P

[]

[]

Reactive power Q

[]

[]

Frequency f

[]

[]

Voltage A-B

[]

[]

A4-18

P437/EN M/R-11-A // P437311650

P437
A5

P437 Version History

Version

P437

Changes

Hardware

301

Initial product release.

401
601

Diagram

Release: 2000-06-09

Initial product release.


Software
Initial product release.

P437

Hardware

301

No changes.

401
601-701

Diagram

Release: 2000-08-28

No changes.
Software
COMM1

Bug fixing:

P437

Hardware

302

As an alternative there is now an optional


communication module available providing an IRIG-B
input for clock time synchronization.

402
602
Release: 2000-11-20

Bug fixing in MODBUS protocol.

Diagram
The updated diagram now includes the new IRIG-B
interface.
Software
IRIGB

P437

Hardware

302

No changes.

402
602-702

New function used for clock time synchronization as per


IRIG-B standard.

Diagram

Release: 2001-02-20

No changes.
Software
COMM1

P437/EN M/R-11-A // P437311650

Various modifications of protocols to be consistent with


MiCOM standards.

A5-1

P437

A5 P437 Version History

Version

P437

Changes

Hardware

302

No changes.

402
602-703

Diagram

Release: 2001-07-27

No changes.
Software
MAIN

P437

Realization of a single-pole enabling/disabling of the


protection via the binary input function (003 026)
MA IN: Disable protect. EX T.

Hardware

303

An additional variant with ring-terminal connection is


now available.

402/403
603

As an alternative there is now an optional


communication module available, providing two serial
interfaces and an IRIG-B input for time synchronization.

Release: 2002-01-28

Installing the devices into a panel is now possible in


two variants: with and without angle brackets. The
dimensional drawings for the cases and the required
panel cutouts are included in the supporting documents
supplied with the devices. Also included in the
supporting documents are assembly diagrams and
terminal connection diagrams.
The binary (I/O) module X(6xO) is now optionally
available with rapid-response output by 4 thyristors.
Diagram
The updated diagram 402 now includes the additional
COMM2 interface.
Diagram 403 describes the variant with ring terminal
connection.
Software

A5-2

FT_DA

Extended setting range for fault location output.

SFMON

Correction in the range of peripheral fault signals


SFMON: Me as. ci rc. V f aul ty.

PSIG, ARC,
ASC, GFSC,
GSCSG

New functionality with equal-priority enabling or


disabling of a function via any device interface.

PSB

The Power Swing Blocking function has been revised


completely. An Out of Step tripping has also been
added.

P437/EN M/R-11-A // P437311650

P437

A5 P437 Version History

Version

Changes

PSIG

The permissive signaling scheme logic is further


accelerated by processing the send and trip decisions
within the distance task.
Improvement of the weak-infeed logic.

P437

COMM2

Logical communication interface 2 (function group


COMM2) added to communication.

DIST

Minimum starting time is now reduced to less than


10 ms. The distance zones may now be blocked
individually via appropriately configured binary signal
inputs.

Hardware

303

No changes.

402/403
603-704

Diagram

Release: 2002-02-13

No changes.
Software
f<>

P437

Hardware

303

No changes.

402/403
603-705

Bug fixing.

Diagram

Release: 2002-08-09

No changes.
Software
LOC

P437

Hardware

303

No changes.

402/403
604

The Russian character set has been corrected.

Diagram

Release: 2002-10-29

No changes.
Software

P437/EN M/R-11-A // P437311650

MAIN

The acquisition of pole-selective CB status signals has


been added, and the application of these status signals
adapted to and enhanced in functions ARC, PSIG,
GSCSG and MCMON.

PSIG, ARC,
ASC, GFSC,
GSCSG

The functionality of equal-priority enabling or disabling


a function via any device interface is modified now in
such a way, that the functions are enabled by default.

A5-3

P437

A5 P437 Version History

Version

Changes

MEASO

P437

Hardware

304

A new communication module A, providing the


InterMiCOM protective interface COMM3 (InterMiCOM),
is available now as an ordering option.

404/405
605
Release: 2002-11-19

Scaling of the BCD coded output of measurands now


allows the setting of an output values range. This
feature is required if signed event measurands are
assigned to the BCD output (like fault location or shortcircuit reactance,).

Diagram
The new connection diagrams include the InterMiCOM
communication interface (function group COMM3).

P437-404 (pin-terminal connection)

P437-405 (ring-terminal connection)

Software
IDMT

Accuracy of tripping time is improved. Particularly the


characteristic IEC extremely inverse is now within the
claimed tolerance range.
Residual current measuring system: it is now possible
to select whether the residual current value calculated
from the three phase currents or the current value
measured by the fourth CT is to be applied.
The enable logic within the parameter subsets has
been enhanced and adapted to the other devices in the
MiCOM Px3x range.

DTOC

Residual current measuring system: it is now possible


to select whether the residual current value calculated
from the three phase currents or the current value
measured by the fourth CT is to be applied.
DTOC ground fault protection is now able to operate in
directional mode.

MAIN

The values range for the primary power measured


values has been expanded.
New input signals allow direct transfer tripping without
use of protective signaling scheme logic (function
group PSIG).

A5-4

P437/EN M/R-11-A // P437311650

P437

A5 P437 Version History

Version

Changes

COMM1

P437

IEC-60850-5-103: The trip signal of back-up


overcurrent (BUOC) was transmitted with ASDU 1
(instead of ASDU 2).

IEC 60870-5-103: For the reclose commands of


high-speed and time-delayed reclosing (Function
Type 80h, Information Numbers 80h and 81h), the
status changes On to Off were signaled
spontaneously and were transmitted as part of
the response to a general scan.

GSCSG

The status signal GSCSG: Te lecom. f aul ty EXT was


made available in conjunction with the implementation
of the InterMiCOM protective interface.

f<>

Measurements of minimum frequency during an


underfrequency situation and maximum frequency
during an overfrequency situation have been added.

COMM3

New function group COMM3 (InterMiCOM protection


interface) permits end-end channel-aided schemes to
be configured, without the need of discrete carrier
equipment.

Hardware

304

No changes.

404/405
605-706

Bug fixing:

Diagram

Release: 2003-01-30

No changes.
Software
IDMT

When ANSI/IEEE characteristics with reset behavior


according to characteristic are selected, the trip signal
now resets as soon as 3% of the reset time has been
exceeded. In previous versions the trip signal was only
reset when the reset time had elapsed completely.
The direction characteristic for short circuit direction
measurement based on negative-sequence current and
voltage is now corrected.

DTOC

P437/EN M/R-11-A // P437311650

DTOC ground fault protection stages set with no time


delay (e.g. DTOC: tI N> P Sx = 0 s) are processed with
a higher priority so as to ensure tripping times of
< 30 ms.

A5-5

P437

A5 P437 Version History

Version

Changes

GFSC

Accuracy of tripping time is improved. Particularly the


characteristic IEC extremely inverse is now within the
claimed tolerance range.
Bug notice: With this version only non-directional
timer stage t3 will not operate when timer stage t2 is
set to blocked.

P437

Hardware

304

No changes.

404/405
605-707

Diagram

Release: 2003-02-12

No changes.
Software
COMM3

P437

Minor modifications so that telegram errors on


communication channels with heavy noise interference
are better identified.

Hardware

304

Binary signal inputs with a higher switching threshold


are now available. Installation is only recommended if
the application specifically requires such binary signal
inputs.

404/405
605-708
Release: 2003-07-28
Diagram

No changes.
Software
COMM1

DIST

Advanced communications software was designed to


cope with communication problems with ESC field
units.
Bug fixing:

DIST, PSIG

A5-6

The distance protection function could fail to


operate when angle settings 0 and zone
extension factors kze > 2 were combined.

The PSIG send signal is now being processed within the


distance protection function to get very short signal
processing times.

P437/EN M/R-11-A // P437311650

P437

A5 P437 Version History

Version

Changes

MCMON

Bug fixing:

ARC

Bug fixing:

P437

Voltage-measuring circuit monitoring was


incorrectly blocked by the general starting
(instead of the distance protection starting). This
bug does not apply to the processing of the m.c.b.
trip signal input and the fuse failure monitoring
function.

If configured into the trip command 1 the signal


(120 046) MAIN: Trans fe r tri p. E XT did not
lead to a start of ARC.

Hardware

305

This version is project-specific and only available on


request!

406/407
606

The Ethernet communication module is available.

Release: 2003-11-11
Diagram

The updated connection diagrams now include the


interfaces for the Ethernet communication module:

P437 406 (for 84 TE case, pin-terminal


connection)

P437 407 (for 84 TE, ring-terminal connection)

Software
UCA2
P437

Hardware

305

No changes.

406/407
607

Initial implementation of the UCA2 communication


protocol.

Diagram

Release: 2004-05-03

No changes.
Software
SOTF

Bug fixing:

UCA2

P437/EN M/R-11-A // P437311650

A transient undervoltage starting could occur with


the switching on of a feeder, which led to an
overreaction when the function SOTF was applied,
with the operating mode set to Trip with starting.

Extension to the expanded spontaneous signaling


range. In addition, GOOSE messages and fault
transmission are now supported.

A5-7

P437

A5 P437 Version History

Version

Changes

PSIG

The transient blocking has been extended to block any


distance zone trip decisions for 2 cycles after the global
direction decision changed from backwards to forwards
(only).

DTOC

In order to better control transient effects with the


protection of series-compensated lines the direction
determination of the DTOC ground fault protection now
operates with a 2-cycle Fourier filter.

PSB

Extension of the power swing detection function by the


operating mode Z. Here the rate of change of the
resistance component of positive-sequence impedance,
when entering the power swing polygon, is interpreted.

SFMON

A number of device bugs previously led to a blocking


with the second entry to the monitoring signal memory
(i.e. if the recurring fault was already stored in the
monitoring signal memory see Chapter
Troubleshooting in the Technical Manual). This
reaction was modified in such a manner that device
blocking will only occur if a renewed appearance of the
same device fault lies within a set memory retention
time (021 018) SF MON : Mon .sig. re te ntion. This
makes it possible to tolerate sporadic faults, resulting
from control actions, without having to clear the
monitoring signal memory in the interim.
The significance of the time stamp was modified to
accommodate this new feature. The time stamp now
represents the last appearance of the fault.

MAIN

P437

Hardware

305

No changes.

406/407
608

The parameter (010 049) MAI N: Rotar y f iel d was


renamed to (010 049) MA IN: P hase s e que nce. In
addition the parameter selection for clockwise and
anticlockwise was also changed to A-B-C and A-C-B.

Diagram

Release: 2004-07-23

No changes.
Software

A5-8

P437/EN M/R-11-A // P437311650

P437

A5 P437 Version History

Version

Changes

MAIN

The new signals (037 252) MAIN: Trip si gn al 1, 1 p


and (037 253) MAIN: Tri p si gnal 1, 3p replace the
previous signals MA IN: 1-pol e tr ip and MA IN: 3pole tri p.
The CB close time (e.g. time from close command to
closing of CB contacts) can now be set at MA IN:
tCB,close (000 032). This time duration may be
applied in the function ASC for the new functionality
switch on at point of synchronism.

PSIG

The new signal (037 255) PSIG: Trans ie nt blocking


is now available.

ARC

HSR was extended by the 3-pole (only for 1p) operating


mode. With this setting there is a three-pole HSR only
with single-pole ground faults.
The operating mode may now be set via binary signal
inputs.
The setting range of the discrimination time has been
extended to 0.00 600.00 s.

GSCSG
COMM1

ASC

The new signal (037 254) GSC SG: Tran si ent


bl ocki ng is now available.
Bug fixing:

DNP3: Double transmission of spontaneous


signals is now reliably prevented.

MODBUS: Status signals of LED indicators are now


supported.

IEC 870-5-101: Conversion from the 3-byte time


tag (only for time of day) to the 7-byte time tag
(time of day and date) at COMM1: Time tag
l en gt h is now supported.

New functionality Switch on at point of synchronism:


In slightly asynchronous networks the reclose
command can be controlled in such a way that it will be
issued at the exact point of synchronism.
The close command conditions can now be set
individually for ARC and manual closing.
The reference voltage Vref and the voltage from the
corresponding measuring loop are stored as event
data.

FT_RC

P437/EN M/R-11-A // P437311650

The signal (036 050) A RC: Bl ockin g EXT is now


stored in the fault recording (previously only the
resulting signal (004 069) A RC: Blocke d was
recorded).

A5-9

P437

A5 P437 Version History

Version

Changes

COMM2

P437

Hardware

305

No changes.

406/407
608-711

It is now possible to select by setting (103 203)


COMM2: P ositi ve ackn . fault whether a fault read
out at COMM2 is to be acknowledged positively and
consequently deleted from the fault overview at the
COMM2/PC interface or not.

Diagram

Release: 2004-10-21

No changes.
Software
FT_DA

The measuring window for fault data acquisition is


determined by the distance element for fault durations
shorter than 55 ms.
The output of the primary short-circuit reactance
(004 029) F T_DA : F au lt react., prim. is now made
in the same way as the fault location.
Bug fixing:

Fault locations of numerical values >655.35%


were falsely displayed as small values.

COMM1

The fault location (004 029) FT_DA : Fau lt react. ,


prim. (Function Type 80h, Information Number 49h),
will no longer be sent spontaneously, if its value is Not
measured.

PSIG

The blocking logic for the weak-infeed logic was


extended.
With the occurrence of a general starting no longer an
immediate output of the send signal is done when the
operating mode was set to Blocking scheme. It is now
only possible to send the blocking signal within the
distance protection task after the distance directional
decision backward or zone 6 decision is determined
(depending on the operating mode set for sending).

ARC

P437

Function change: There is no longer a zone extension


with a rapid reclosure (RRC) when the parameter at
A RC: Zone ext.du r. RC P Sx (015 088) is set to
Following HSR.

Hardware

306
406/407
609
Release: 2005-02-25

A5-10

P437/EN M/R-11-A // P437311650

P437

A5 P437 Version History

Version

Changes

The new hardware variants now offer, per ordering


option, additional operating thresholds for the binary
signal inputs:

>73 V (67% of VA,nom = 110 V) (Order ext. No.


463)

>146 V (67% of VA,nom = 220 V) (Order ext. No.


464)

Installation of the standard variant is generally


recommended if the application does not specifically
require such binary signal inputs with higher operating
thresholds.
Diagram
No changes.
Software
FT_RC

COMM1

The recording duration for binary tracks is now limited


to 1 minute in order to prevent recording of endless
events.
Bug fixing:

MAIN

DIST

The direct transfer trip function has now been extended


by dedicated send signals so as to avoid latching,
which could occur when the trip signal was used as a
send signal.
Bug fixing:

P437/EN M/R-11-A // P437311650

Where the Courier protocol was selected a device


warm restart occurred when individual
communication parameters (e.g. baud rate,
address, etc.) were changed.

An erroneous loop selection could occur with a


two-phase short circuit fault between phases C
and A, which then led to incorrect distance and
directional decisions, when only the overcurrent
starting for phase A was triggered and phase C
starting was only activated because of a current
plausibility check [setting (010 040) MAIN:
Tran sfe r f or 1p = P or G =f(Imed,Imax)]

A5-11

P437

A5 P437 Version History

Version

Changes

MCMON

Bug fixing:

SOTF

In one case an unwanted overreaction of the fuse


failure monitoring function was observed, which
led to distance protection blocking when a short
circuit in the power system had occurred. In the
new version the functional sequence has been
enhanced and the default value for the negative
voltage threshold was set to a higher value:
(031 056) MCMON: Vne g>, F F = 0.16 Vnom).

The function parameters are now available in the


parameter subsets so as to provide adjustment to
changed operating conditions.
An additional sensitive ground overcurrent threshold is
now available.
Bug notice: Unfortunately this current threshold is
permanently active (not limited to the duration of the
manual close time) and can therefore not be applied
as intended.

PSIG

The tripping logic in the Zone extension operating


mode has been accelerated by additionally processing
this logic within the distance protection task. Now
typical tripping times of 20 30 ms can be obtained
(without delay from signal transmission).
The weak-infeed logic has been extended by an
external blocking option: P SIG: Bl ock. we ak i nf .
EXT

ARC

Bug fixing:

IDMT

The change of operating mode via binary inputs


previously was only accepted if the relay was
switched from off-line mode back to on-line mode.

Bug notice: In this version the directional dependence


of the residual current stage is not operational.
The residual current stage has been enhanced by a
minimum trip time and a minimum trip current
threshold.

P437

Hardware

306

No changes.

406/407
609-712

Diagram

Release: 2005-0x-xx

No changes.
Software

A5-12

P437/EN M/R-11-A // P437311650

P437

A5 P437 Version History

Version

Changes

PSIG

P437

Hardware

306

No changes.

406/407
609-713

When P SI G: Operati ng mode PSx = Release


scheme and P SI G: Oper. mode se nd P Sx = Direct.dependent are combined, a send signal with
interruptions may occur.

Diagram

Release: 2005-10-30

No changes.
Software
ASC

P437

Bug fixing:

The internal timer clock was corrupted during the


ASC operative time. This led to implausible time
tags added to binary signals, which in turn made
fault records difficult to interpret. Protection
functions were in no way affected.

The offset angle ASC: P hi off se t P Sx) was


taken into account but by a factor of 10 less than
required (for instance when set to 90 an internal
value of only 9 was taken into account).

Hardware

307

An optional processor board with a DSP coprocessor is


now available. This coprocessor provides a better
overall performance of the supplementary functions of
the device.

408/409
610
Release: 2006-02-26
Diagram

The designation texts of the binary signal inputs and


output relays have been replaced by the standard Px3x
texts, i.e. the designation comprises the board location
number (1 or 2 digits) followed by a consecutive
number (2 digits).
Example: K2001 replaces K201 (= first relay in slot 20).
Software

P437/EN M/R-11-A // P437311650

A5-13

P437

A5 P437 Version History

Version

Changes

SFMON

The configuration table of the user defined alarm


condition has been extended by the instantaneous and
timed outputs 3032(t) of the programmable LOGIC:

(098 053) SFMON: Ou tput 30 ~ (042 090)


LOGI C: Ou tpu t 30

(098 054) SFMON: Output 30 ( t) ~ (042 091)


LOGIC: Outpu t 30 (t)

(098 055) SFMON: Ou tput 31 ~ (042 092)


LOGI C: Ou tput 31

(098 056) SF MO N: Ou tpu t 31 (t) ~ (042 093)


L O GIC : Outpu t 31 ( t)

(098 057) SF MO N: Outpu t 32 ~ (042 094)


LO GIC : Output 32

(098 058) SFMON: Ou tpu t 3 2 (t) ~ (042 095)


LOGIC: Output 3 2 ( t)

These logic outputs are included in the warning signals


by setting SFMON: Fct. ass ign . war nin g and they
are also recorded in the monitoring signal memory.
These signals can be used to create an alarm signal
under complex application conditions. This signaling
has no influence on the device's operation (i.e. no
warm restart or blocking).
MAIN

Priority control of clock synchronization is now settable.


In view of the 3-pole (only for 1p) ARC operating
mode the phase-selective direct transfer trip logic has
been modified so that no 3-pole transfer trip will occur
with single-pole faults.
A distance-based phase selection logic has been
implemented, which allows phase selective 1-pole
tripping of ground faults by integrated supplementary
functions (e.g. GFSC or DTOC ground fault protection)
or from external parallel protection devices operating in
3-pole mode (e.g. phase comparison protection).

CBF

A5-14

The complete revision of the circuit breaker failure


protection function now includes a current breaking-off
criterion.

P437/EN M/R-11-A // P437311650

P437

A5 P437 Version History

Version

Changes

DIST

The ground fault starting condition has been made


settable by an OR-linked or an AND-linked
condition of the IN> and VNG> thresholds, if the system
star point is low-impedance grounded (setting at
(001 249) MA IN: Ground s tarti ng P Sx).
It can be selected whether grading timers are triggered
from the general starting condition or with the
respective zone starting signal.
Zone 1 and 2 now can be blocked during 1-pole HSR
dead time.
The reactance reach of the zones can now be set
separately for phase-ground and phase-phase
measuring loops.
The max. settable reach value has been extended to
400 .

MCMON
FT_RC

Fuse failure detection is blocked now during CB open


conditions.
Bug fixing:

The logging of the following signals was done in


the next processing cycle, typically 10 ms later
than when the actual state changed:

SOTF

(037 254) GSCSG: Trans ie nt blocki ng


(035 047) DTOC: Fau lt N f orward
(035 048) DTOC: Faul t N backward

The function has been supplemented by a Line dead


detector e.g. SOTF will only be active if the line has
been de-energized for at least a set minimum time
period.
The parameters (011 060) SO TF : Man . clos e timer
PSx and (011 061) SOTF: Ope ratin g mode P Sx
have been moved to the parameter sets.
Bug fixing:

P437/EN M/R-11-A // P437311650

The residual current stage is now active only


during the manual close time.

PSIG

In view of the 3-pole (only for 1p) ARC operating


mode the weak-infeed logic has been modified so that
no 3-pole trip will occur with single-pole faults.

ARC

The function is now also available when DIST is blocked


by a fault in the voltage-measuring circuit (MCMON)
and BUOC is not configured (external backup
protection), but it is without rapid reclosure (RRC).

A5-15

P437

A5 P437 Version History

Version

Changes

GFSC

By setting a parameter, either the internally calculated


value or the measured value for the neutral-point
displacement voltage can now be used.
The directional measurement has been enhanced by a
settable compensation reactance (zero-sequence
current compensation method) to allow correct
operation on series-compensated lines irrespective of
the power system's supply conditions.

GSCSG

The user-settable blocking conditions have been


expanded so as to deal safely with time-critical
applications in conjunction with the ARC function.

DTOC

Triggering of the residual current timer stages can now


occur either when the current threshold is exceeded or,
additionally when a directional decision is made
(settable).
Negative-sequence and residual current stages may
now be set so that they are blocked during the 1-pole
dead time of the high-speed reclosure (HSR) of an ARC
cycle.
The directional dependence of the ground fault stages
may now be blocked by a binary signal input function;
when blocked the respective stage operates as nondirectional.

IDMT

Directional measurement, based on the negativesequence current has been adapted to the new method
as implemented in GFSC, and the previously fixed
compensation impedance has been replaced by a
settable compensation reactance.
Bug fixing:

INP

The ground fault stage operated always as nondirectional, regardless of the setting.

The mean acquisition time for binary input signals has


been reduced:

with DSP: mean value is 2.1 ms (range 0 6 ms)

without DSP: mean value is 6.5 ms (range 0


12 ms).

Note: This software version is compatible to all


previous hardware versions.

A5-16

P437/EN M/R-11-A // P437311650

P437

A5 P437 Version History

Version

Changes

IEC, GOOSE,
GSSE

Implementation of the new substation communication


protocol per IEC 61850 standard.
Implementation of communication procedures for the
exchange of binary information in an Ethernet network
section.
Function group GSSE is compatible to previous UCA2GOOSE. Function group GOOSE is acc. to IEC 61850GOOSE.

UCA2
COMM3,
OUTP, LED,
MAIN, LOGIC

P437

Bug fixing:

In the selection list for the configuration of the


output relays, LED indicators, the InterMiCOM
communication interface, of the trip commands
and of the function assignment of the Boolean
equations the signal L OGIC: Out put 32 ( t)
(042 095) was missing.

Hardware

307

No changes.

408/409
610-714

The substation communication protocol per UCA2


standard is not supported with this firmware version.

Diagram

Release: 2006-09-20

No changes.
Software
MCMON

BUOC

Bug fixing:

The Ineg monitoring was without function.

The signal (040 087) MCMON: Meas . circ. I


f aul ty could not become active.

Bug fixing:

P437

Hardware

307

No changes.

408/409
610-715
P437/EN M/R-11-A // P437311650

Correct BUOC tripping times were re-established.


With the last version a change was implemented
to allow that ARC remains ready in case of a
voltage measurement circuit failure, even if no
BUOC protection is configured. Unfortunately, due
this change, the BUOC then tripped
instantaneously if ARC was ready. Moreover, an
HSR cycle was initiated from the BUOC trip, even
if the BUOC operating mode is set to Without
ARC.

Diagram
A5-17

P437

A5 P437 Version History

Version

Changes

Release: 2006-10-09

No changes.
Software
COMM1

IEC

P437

Bug fixing:

If communication was interrupted during control


access via the Ethernet interface using the
operating program MiCOM S1, renewed control
access was only possible after a warm restart of
the P437.

Previously a break in the client-server


communications link could occur after
approximately 49 days for about 20 minutes.
GOOSE and GSSE are not affected.

Hardware

307

No changes.

408/409
611

The upgraded communications software 3.18 is now


implemented. Various small bugs have been fixed in
communication protocols per IEC 60870-5-101 and
MODBUS.

Diagram

Release: 2007-02-28

No changes.
Software
COMM1

DIST

The following spontaneous messages were missing in


the IEC 608705 protocol:

(034 047) MA IN: Man ual tri p s ignal A

(034 048) MA IN: Manu al trip si gn al B

(034 048) MA IN: Man ual tri p s ignal C

Improved measuring logic to provide fast 3-pole


tripping in case of phase-phase-ground faults, with one
phase-ground loop impedance getting significantly
slower into zone 1.
The underimpedance starting logic has been improved
to pick up faster in case of faults with almost no change
in current magnitude.
The directional characteristic is now settable.

A5-18

P437/EN M/R-11-A // P437311650

P437

A5 P437 Version History

Version

Changes

PSB

Separate counters for number of stable swings as well


as number of pole slips have been implemented. These
counters are equipped with settable limits at which
binary signals are raised that could be used for tripping
purposes.
Bug fixing:

The measurement of Delta Z was not always


carried out correctly when the positive-sequence
impedance moved into the power swing polygon
from left to right.

The maximum blocking time is now re-started


again with each entry into the power swing
polygon.

SOTF

The SOTF dead line detection logic can now be enabled


or disabled.

PSIG

Transient blocking timer is now always started upon


reset of DIST backward direction decision.
The scheme logic has been enhanced to cope 3-ended
line applications.
The distance dependent send logic has been modified
for improved operation in case of 2pG faults: If fault
direction signals forward and backward are present at
the same time, the send signal is based on the
selective Z1 decision only (not on Z1e).
Bug fixing:

ARC

In distance-dependent blocking scheme, the PSIG


tripping time was not started, if the zone timing
setting was (001 236) DIST: Zone tim er
start = With zone starting.

Zone 1 extension tripping during reclosing is now


executed from ARC (in case of setting (015 088) ARC:
Zon e ext.dur. R C P Sx = Following HSR or Always),
even if PSIG is in operation.
The duration of the zone extension is as long as the set
reclose command (015 067 MA IN: Cl ose cmd.pulse
time), even if the reclose command is stopped
because of the close-signal from the CB (015 042
MA IN: R C i nh ib.by CB clos e = Yes).

P437/EN M/R-11-A // P437311650

A5-19

P437

A5 P437 Version History

Version

Changes

ASC

The selection of voltage control conditions (operating


modes) has been enlarged by an exclusive-OR
condition, i.e. (re-)closing is enabled, if exactly one side
is dead while the other side must be live (setting
abbreviated N V&Vref or V&n Vref means (NOT V
AND Vref) OR (V AND NOT Vref)).
When the operating mode is set to Vref & Z1 but not V
the significance of Z1 is extended so that with a trip
from distance zone 1 OR a PSIG trip the condition is
met. This then makes reclosing possible if the primary
fault was on the protected line.

GSCSG

Transient blocking timer is now always started upon


reset of a GSCSG backward direction decision (039 091
GFSC: Fau lt backward / BS).
The selection list for user defined blocking conditions
(002 180 GSCSG: Fct.ass ign. bl ocking) has been
further expanded by internal trip decisions as well as
parallel and transfer trip signals.
In case of (006 009) GF SC : V irtual curr en t pol . =
Yes the tripping timer is now started from (039 088)
GFSC: IN> tri gge r ed signal only.

P<>

Directional power protection function is now available.

GFSC

The user settable blocking condition of the function has


been changed to an m-out-of-n selection, using the
same enlarged list as for GSCSG. Consequentially, the
previous setting (002 137) GFSC: Block. w. DIST
start is removed.
For ground faults with small neutral displacement
voltage an optional virtual current polarisation has
been implemented. This feature uses a faulty phase
selector, which is based on the measured change of
phase currents.

P437

GFSC, GSCSG

The priority of GFSC and of the signaling scheme


(GSCSG) has been changed to provide faster 1-pole
trips.

IEC

Implementation of the communication protocol has


been extended:

A second SNTP server is supported.

VLAN priority can be set.

Hardware

308
408/409
612
Release: 2007-12-31

A5-20

P437/EN M/R-11-A // P437311650

P437

A5 P437 Version History

Version

Changes

The device is now equipped with a new HMI, which


provides 6 additional keys and LED indicators.

Six freely configurable LEDs (H18 to H23) are


situated next to six freely configurable function
keys.

All of the freely configurable LEDs (H4 to H16 and


H18 to H23) are provided as multi-color type
LEDs.

Diagram
No changes.
Software
IEC

Implementation of active monitoring of the


communications data links to logged-on clients with the
parameter (104 062) IEC: TCP ke e p-al ive t im e r.
This active monitoring now replaces previous passive
monitoring by parameter (104 050) IEC: I nact ivi ty
ti me r.
Instead of setting a router address and target network,
so as to establish a communication link to a client
situated exterior to the local network, now only the
setting of the gateway address is required via
(104 011) IEC: Gat eway addr es s.
Now unbuffered reports are available for all logical
nodes.
I EC : De adban d val ue (104 051) was divided into
several individual settings:

P437/EN M/R-11-A // P437311650

(104 229) I EC: Update Me as u rem en ts

(104 230) I EC : De ad band IP

(104 231) IE C: D ead ban d IN

(104 232) IE C: D ead ban d V PP

(104 233) I EC : De ad band VP G

(104 234) IE C: D ead ban d f

(104 235) IEC : De ad band P

(104 236) IEC: Dead ban d ph i

(104 237) IEC: Dead ban d Z

(104 238) IEC: De ad band mi n/max

(104 239) I EC: De ad band ASC

(104 240) IEC: Dead ban d te mp.

(104 241) I EC: De ad band 2 0mA

A5-21

P437

A5 P437 Version History

Version

Changes

With this version resetting options have been extended


such that now there is a corresponding external signal
available for each manual reset function; now the
respective counter or memory can be reset by an
appropriately assigned binary signal.
Similar to this all manual reset parameters have been
renamed by adding the phrase USER to the
descriptive text (it may be abbreviated so that the max
number of characters allowed is not exceeded).
Example:

LOC

MAIN: Ge ne ral r e se t was renamed to MAIN:


Gen eral re set USER.

A selection of memories to be reset may now be


assigned (with the new parameter LOC: Fct. rese t
k ey) to the CLEAR key situated on the local control
panel. Now each time the CLEAR key is pressed not
only the LED indicators and the display are reset but
the selected memory is also reset immediately.
Additionally two menu jump lists are now available that
can have functions assigned by setting these new
parameters:

LOC: Fct. men u jmp l is t 1 and

LOC: Fct. men u jmp l is t 2

The parameter (080 110) has been renamed to LO C:


Fct. rea d ke y (080 110) without any changes in their
functionality.
LOC, MAIN

F_KEY

Two menu jump lists may now be configured. These


menu jump lists make it possible to select individual
menu points (i.e. set values, counters, triggering
functions, event logs) in a freely definable sequence.

(030 238) L OC : Fct. me nu jmp l ist 1

(030 239) LOC: Fct. men u jmp l is t 2

The new control panel (HMI) is fitted with 6 freely


configurable function keys which may be used either as
switches or keys, and are password protected.
Because of this the function group F_KEY Configurable
Function Keys has been added.

A5-22

LED

The function group LED was enhanced to do the colorspecific settings related to the multi-colored LEDs.

SFMON

The following signals have been added to the selection


lists for the warning (Alarm) signaling:

(098 132) SFMON: M.c.b. trip VNG

(098 128) SFMON: Se ttin g e r ror P SB

P437/EN M/R-11-A // P437311650

P437

A5 P437 Version History

Version

Changes

MAIN

The following signal has been added to the selection


list for relay fault (Blocked/faulty) signaling:

DIST

(098 132) SFMON: M.c. b. trip V NG

The following parameters are now set in units of Vnom/


3 (instead of Vnom):

DIST: V NG> P Sx

DIST: VNG>> P Sx

Bug fixing:

In the unlikely case that mutual compensation is


used and the ground factor angle kG of the line
was set > 0, the impedance measurement of
phase-ground loops was using a wrong neutral
current compensation. This error affects only
standard processor hardware without DSP
coprocessor (up to 306). It results in false
directional decisions, which would have been
identified during normal commissioning tests.

PSB

The Out of Step tripping feature is enhanced by a new


Counting-based Tripping features and settable OOS
detection zones, which allow different operation,
depending on whether the electrical center of the
power swing is on the protected line or outside.

SOTF

A new option SOTF: A cti vation mode PSx allows for


switching the function permanently active during dead
line condition.
The undervoltage threshold of the dead line detector is
changed to the new value 0.7 Vnom/3. Furthermore,
the dead line detector has been enhanced by an
undercurrent detector and an operate-delay timer.
The detection of a dead line and SOTF activation is
now signaled:

(006 147) SOTF: Li ne dead

(006 146) SOTF: Acti ve

SOTF is enhanced by an additional phase overcurrent


detection.
PSIG

A new option PSIG: Start cond. tV< PSx (006 148)


allows for having the weak-infeed timer triggered only
if the undervoltage condition and the weak-infeed
starting are both present.
There is now a phase-selective signaling of tripping of
the weak-infeed logic:

P437/EN M/R-11-A // P437311650

(006 152) P SIG: Tri p V <, A

(006 153) PSIG: Tri p V<, B

(006 154) PSI G: Tri p V <, C

A5-23

P437

A5 P437 Version History

Version

Changes

GFSC, GSCSG

The signal DIST: Ge ne ral starting (036 240) has


been added to the selection lists for user-defined
GFSC / GSCSG blocking conditions.

GSCSG

The current reversal condition has been changed so


that transient blocking gets established each time the
GFSC: Fau lt backward / BS (039 091) decision
resets (whether or not a forward decision comes up is
of no relevance any more).
The GSCSG Trip timer is now triggered by GFSC: Fault
forward / LS (039 090) decision instead of starting
condition only.
The blocking of the function in case of a voltage
measuring circuit failure is now changed in the same
way as done with GFSC since version 610: If GFSC
operates on measured VNG, then the functions get only
blocked, if this VNG measuring circuit is defect,
otherwise, if GFSC operates on VNG calculated from the
3 phase voltages, then the functions get blocked, if the
3phase voltage measuring circuit is defect.

DTOC

The following parameter is now set in units of Vnom/3


(instead of Vnom):

LIMIT

CBF
P437

The following parameter isnow set in units of Vnom/3


(instead of Vnom):

(014 043) LIMIT: V NG>

(014 044) L IMIT: V NG>>

The signal (036 017) C BF: CB f ailu re is now available


as compatible IEC 608705103 spontaneous message.

Hardware

308

No changes.

408/409
613

DTOC: VNG> PSx

Diagram

Release: 2009-06-15

No changes.
Software

A5-24

P437/EN M/R-11-A // P437311650

P437

A5 P437 Version History

Version

Changes

IEC

MMXU: Limitation of number of reports: Only those


measured values out of a report are transmitted the
value of which has changed by a delta greater than the
dead band. (Previously all values were transmitted
whenever one of the values changed by a delta greater
than the dead band.)
Bug fixing:

Comtrade fault transmission: Error with 5 A


nominal current. The rated secondary current
(1 A / 5 A) is taken into account for scaling of the
measured values.

The automatically generated data file names are


now correct with fault numbers exceeding 999.
Data file names are issued according to this
format:
yyyymmdd_HHMMSS_xxx_rNNNN.eee
With: yyyy = year
mm = month
dd = day
HH = hour
MM = minute
SS = second
xxx = millisecond
r = permanent single character
NNNN = fault number
eee = file extension
In previous versions the dot (.) was overwritten
for fault numbers exceeding 999.

MAIN

Circuit breaker position signaling operates correctly


now even if only the binary input MA IN: C B closed
3 p EXT is configured.
The option COMM1 for the source of clock
synchronization was renamed to COMM1/IEC.
Bug fixing:

P437/EN M/R-11-A // P437311650

Without external clock synchronization (IRIG-B or


via communication protocol) there were leaps
(typ. 7 hours) in the system time.

The setting parameter MAI N: Grou nd st arting


P Sx was without function, ground starting always
occured based upon IN> OR VNG>.

A5-25

P437

A5 P437 Version History

Version

Changes

DIST

The following parameters have been given new default


values:

DIST: Zfw,PG PSx 0

D IST: Zf w,P P P Sx 0

D IST: kze ,PG HSR PSx 1.50

DIST: kze ,P P H SR P Sx 1.50

D IST: kze ,PG TDR P Sx 1.50

D IST: kze ,PP TDR P Sx 1.50

The selection of formulae for calculating the PG


impedances of the starting measuring system (to avoid
under impedance startings due to apparent
impedances) was enhanced by another option, which
uses the real value of the ground factor kG:
ZPG =

VPG
I P (1 + kG )

This calculation method is selected by setting D IST: Z


e val uati on P Sx
to ZPG=VPG/IP*(1 + kG).
PSIG

The following parameter has a new default value:

PSIG: Echo on re cei ve P Sx Without

The echo is issued (in consideration of the operating


delay and the CB status signals) as soon as at least one
PSIG signal is received (independent of P SI G: 3ended
l in e prot PSx) and there is no distinct general
starting.
The following change was introduced with version 611:
If for a 2pG fault or for an inter-system fault on double
circuit lines there are forward and backward (reverse)
decisions present at the same time, then the send
signal is based on the selective Z1 decision only (not on
Z1e).
This was again modified as of the current version, so
that this is not the case with the setting P SIG:
3 en de d li ne prot PSx = Yes, because this
functionality could result in an under functioning of the
Protective Signaling in case of 3-ended line applications
(different lengths of the line parts, different feed-in
power).
With triple-ended applications the fault signals of both
communication channels are now available for separate
use.

(004 064) PSIG: Tele c.faulty ( A) EXT

(008 094) PSIG: Tel ec.f aul ty (B) EXT

Bug fixing:

A5-26

After changing an offline parameter no more echo


was issued until the warm restart.

P437/EN M/R-11-A // P437311650

P437

A5 P437 Version History

Version

Changes

COMM1

FT_DA

Bug fixing:

In the MODBUS protocol only the eight VDEW


channels were transmitted, but not the analog
channels Vref and IN,par.

Under special circumstances discrepancies


between the timestamps of a spontaneous
message and the operating data recording were
possible.

Bug fixing:

FT_RC

Bug fixing:

PSB

The calculation of (004 029) FT_DA : Fault


react., pr im . used only Vnom = 100 V.

The messages (036 024) PSB: Z wi thi n


pol ygon and (006 192) P SB: Tri p s ignal OOS
(b) were not logged in the fault recording.

The duration of a starting signal issued at an instable


power swing was limited to 100 ms:

(006 035) P SB: Trip s ign al OO S (a)

(006 192) PSB: Tri p si gnal OOS ( b)

The counter (006 188) PSB: No. OOS-Swing (b) was


removed, and therefore (006 026) was renamed from
P SB: No. OO S-Swi ng (a) to PSB: No. OOS-Swing.
Bug fixing:

P437

LOGIC

Increase of the number of logic inputs from 16 to 40.

CBF

The parameter (011 067) C BF: tCBF has been


removed. This time-delay is no longer required by the
new circuit breaker failure function which includes the
undercurrent criterion.

Hardware

308

No changes.

408/409
630

The counters (for the number of stable and


instable cycles of the last power swing) were
reset when the max. blocking time elapsed.

Diagram

Release: 2009-09-10

No changes.
Software
CBF

P437/EN M/R-11-A // P437311650

The parameter designation for (022 160) CBF: I> was


changed to (022 160) CBF : I<.

A5-27

P437

A5 P437 Version History

Version

Changes

MAIN

New logic state signals for clock synchronization:


The parameter: MA IN: Ti me synch ron ized
(009 109) shows whether an external clock
synchronization had been carried out. This signal is
reset after 10 minutes.
Bug fixing:

DIST

In the offline operation mode the fault trigger


(036 089) FT_RC: Trigge r EXT was not
functioning.

Bug fixing:

For all previous versions these signals were


signaled as not ending:

(038
(038
(038
(038
(038
(038
(038
(038
(038

045)
105)
108)
047)
106)
109)
044)
104)
107)

DIST:
DI ST:
D IST:
D IST:
DIST:
DIST:
D IST:
D IST:
DIST:

Di r.u s in g V me as Sys1
Di r.u sing Vme as Sys2
D ir.us in g V meas Sys3
D ir.us in g V mem Sys1
Di r.u s in g V me m Sys2
Dir. usi ng Vme m Sys3
Forw . w/o me as . Sys1
F orw . w/o meas . Sys2
Forw. w/o me as . Sys3

(The distance protection function was in no way


affected.)

A5-28

The calculation of the impedance angle was


corrected which, with distorted current signals,
may have led to erroneous zone decisions by the
distance protection function.

P437/EN M/R-11-A // P437311650

P437

A5 P437 Version History

Version

Changes

PSB

The settable extension of the blocking effect is now


available which will become active after a current
trigger has started or after the maximum blocking time
period has elapsed.
Load blinding is now available within the power swing
polygon.
With (008 248) P SB: Blocki ng EXT a blocking signal
is now available with which PSB protection can be
blocked.
Bug fixing:

In the operating mode S the threshold value


could be exceeded in case of low values of the
apparent power.
This was caused by natural fluctuations of the
measured value during normal operation and
resulted in spurious signaling of (036 058) P SB:
Operate del ay ru nn..
To cope with this problem the apparent power is
now measured only after it has entered the power
swing polygon.

PSIG

The three-ended line feature has been extended by


phase-selective input signals.

ASC

When the operating mode is set to Vref & Z1 but not V


(setting parameters A SC: A R Op.m ode v-chk .PS x,
A SC: MC op.mode v-chk. PSx) the meaning of the
condition Z1 has been changed such that it is now no
longer dependent on the tripping signals issued by
individual protections but on the recognition that the
General trip has occurred during operative time 1 of
the ARC.
A test triggering by RC parameters is now available for
functional testing.

IEC, GOOSE

Phase 2 of the IEC 61850 communications protocol has


been implemented.

COMM1

Enhancement of the IEC 608705103 protocol: These


signals are now transmitted spontaneously in the
private range:

F_KEY

(008 094) PSIG: Tel ec.f aul ty (B) EXT

(040 055) CBF: En abl ed

The default setting of passwords for function keys has


been changed. A password is now no longer required
when pressing a function key.
However, a password may still be configured
individually for each function key.

P437

P437/EN M/R-11-A // P437311650

Hardware

A5-29

P437

A5 P437 Version History

Version

Changes

308

No changes.

408/409
614

Diagram

Release: 2011-01-07

No changes.
Software
IEC

In order to guarantee full compatibility with PACiS the


neutral-point displacement voltage (calculated and
measured) as well as the residual current (calculated
and measured) were assigned to the node MMXU so
that the node MSQI would then include only the
positive-sequence and negative-sequence values.

F_KEY

The default setting of passwords for function keys has


been changed. A password is now no longer required
when pressing a function key.
However, a password may still be configured
individually for each function key.

PC

The following parameter has been removed: P C:


Name of manufacturer (003 183).
Note: Compatibility even with older versions of the
operating program continues to be guaranteed.

COMM1

The data point (003 214) COMM1: MODB US prot.


vari an t may now be used to select between the
MODBUS protocol variants Private and Compatible. The
protocol variant Compatible corresponds to the
MODBUS implementation in the MiCOM Px20 and Px40
protection devices. The protocol variant Private
corresponds to the first implementation of the MODBUS
protocol.
Note: As before this setting is hidden unless the
MODBUS protocol is enabled.

A5-30

P437/EN M/R-11-A // P437311650

P437

A5 P437 Version History

Version

Changes

COMM1,
COMM2

The menu points (003 161) COMM1: Name of


manuf acturer and (103 161) COMM2: Name of
man uf actu re r can no longer be set by using a
selection list but, for reasons of compatibility, they may
now be defined as free text. The default is SE but, in
individual cases, it may become necessary to enter
texts differing from the default.
Notes:

P437

These parameters can only be set using the


operating program and it is not possible to set
them locally using the integrated local control
panel (HMI). The maximum text length is 8
characters and designations exceeding this will
be truncated.

The parameter COMM1 : Name of


ma nufactu re r is hidden unless an IEC 60870-5
protocol is enabled.

Hardware

308

No changes.

408/409
631

Diagram

Release: 2011-01-07

No changes.
Software
IEC

FT_RC

In order to guarantee full compatibility with PACiS the


neutral-point displacement voltage (calculated and
measured) as well as the residual current (calculated
and measured) were assigned to the node MMXU so
that the node MSQI would then include only the
positive-sequence and negative-sequence values.
Bug fixing:

PSIG

Bug fixing:

P437/EN M/R-11-A // P437311650

The signal (036 037) DIST: Block ing Z2 EXT


was not recorded by the fault recording function.

Tripping times were always longer than 40 ms


when the operating mode was set to Release
scheme with Direct.-dependent tripping. This was
because the execution of a process contained in
the distance protection function was not
terminated immediately with the start of the
tripping condition. This delay was added, under
certain conditions, to an intentional time-delay
set at data point P SIG: Tri ppi ng time PSx.

A5-31

P437

A5 P437 Version History

Version

Changes

PC

The following parameter has been removed: P C:


Name of manufacturer (003 183).
Note: Compatibility even with older versions of the
operating program continues to be guaranteed.

COMM1

The data point (003 214) COMM1: MOD B US prot.


varian t may now be used to select between the
MODBUS protocol variants Private and Compatible. The
protocol variant Compatible corresponds to the
MODBUS implementation in the MiCOM Px20 and Px40
protection devices. The protocol variant Private
corresponds to the first implementation of the MODBUS
protocol.
Note: As before this setting is hidden unless the
MODBUS protocol is enabled.

COMM1,
COMM2

The menu points (003 161) COMM1: Name of


manuf acturer and (103 161) COMM2: Name of
manuf acturer can no longer be set by using a
selection list but, for reasons of compatibility, they may
now be defined as free text. The default is SE but, in
individual cases, it may become necessary to enter
texts differing from the default.
Notes:

P437

These parameters can only be set using the


operating program and it is not possible to set
them locally using the integrated local control
panel (HMI). The maximum text length is 8
characters and designations exceeding this will
be truncated.

The parameter COMM1: Name of


manu factu rer is hidden unless an IEC 60870-5
protocol is enabled.

Hardware

308

No changes.

408/409
614-722

Diagram

Release: 2012-02-01

No changes.
Software

A5-32

P437/EN M/R-11-A // P437311650

P437

A5 P437 Version History

Version

Changes

IEC

GOOSE

PC, COMM2

Bug fixing:

If single-pole signals of function group SIG_1 were


active during device startup, this could lead to an
aborted initialization of the Ethernet
communication module.

During the process of connection with clients that


use the IntegrityPeriod option, sporadically the
MMS communication of the Ethernet
communication module would crash without an
internal monitoring response to re-establish the
functionality. (GOOSE messaging and other
communication tasks were not affected.)

Reports of events could get lost if too many state


changes occurred in a short period of time,
especially during secondary injection testing.

The GOOSE Time Allowed to Live (TAL) supervision is


enhanced with respect to simultaneous state changes
of multiple GOOSE messages.
Bug fixing:

EK_SV

P437

If clients did connect to the device immediately


after startup of the Ethernet communication
module, the initialization of the second internal
communication interface could remain
incomplete. As a consequence, access by the
operating program via the COMM2 interface or by
tunneling was not possible in this case.

An der Auslselogik des ErdkurzschlussSignalvergleiches wurden mit der vorliegenden


Softwareversion nderungen vorgenommen, die die
Gefahr einer falschen Auslsung weiter verringern.

Hardware

309
410/411
631-723
Release: 2012-02-01

P437/EN M/R-11-A // P437311650

A5-33

P437

A5 P437 Version History

Version

Changes

The P437 is now fitted with an improved power supply


module.
Note that the voltage range has changed for DC input:

For the DC / AC variant, the range is

now 60 250 VDC / 100 ... 230 VAC


(previously 48 250 VDC / 100 ... 230 VAC).

For the DC-only variant, the range is

now 24 60 VDC
(previously 24 VDC).

A new communication module (REB = Redundant


Ethernet Board) is now available as an ordering
option.
This module can be used for redundant communication
via IEC 61850 and may be fitted to slot 2, as an
alternative to the other communication modules. The
following communication protocols are supported:

SHP (Self-Healing Protocol).

RSTP (Rapid Spanning Tree Protocol).

DHP (Dual-Homing Protocol).

A detailed description of the module and the


appropriate network connections is available as a
separate document (Redundant Ethernet Board,
Application Guide).
Diagram
The diagrams now include the new REB module.

P437 -420: case 40 TE, pin-terminal connection

P437 -421: case 40 TE, CT/VT ring-, I/O pinterminal connection

P437 -422: case 84 TE, ring-terminal connection

The diagrams now include the new REB module.

P437 -410: case 84 TE, pin-terminal connection

P437 -411: case 84 TE, ring-terminal connection

Software

A5-34

P437/EN M/R-11-A // P437311650

P437

A5 P437 Version History

Version

Changes

IEC

GOOSE

PC, COMM2

Bug fixing:

If single-pole signals of function group SIG_1 were


active during device startup, this could lead to an
aborted initialization of the Ethernet
communication module.

During the process of connection with clients that


use the IntegrityPeriod option, sporadically the
MMS communication of the Ethernet
communication module would crash without an
internal monitoring response to re-establish the
functionality. (GOOSE messaging and other
communication tasks were not affected.)

Reports of events could get lost if too many state


changes occurred in a short period of time,
especially during secondary injection testing.

Events that occured after a communication link


had been interrupted and before this interruption
had been detected by the server, were not sent
as Buffered reports after the connection was reestablished.

The GOOSE Time Allowed to Live (TAL) supervision is


enhanced with respect to simultaneous state changes
of multiple GOOSE messages.
Bug fixing:

EK_SV

P437

An der Auslselogik des ErdkurzschlussSignalvergleiches wurden mit der vorliegenden


Softwareversion nderungen vorgenommen, die die
Gefahr einer falschen Auslsung weiter verringern.

Hardware

310

The P437 is now fitted with an improved


communication module for the InterMiCOM protocol.

410/411
632
Release: 2013-12-09

If clients did connect to the device immediately


after startup of the Ethernet communication
module, the initialization of the second internal
communication interface could remain
incomplete. As a consequence, access by the
operating program via the COMM2 interface or by
tunneling was not possible in this case.

Diagram
No changes.
Software
No changes.

P437/EN M/R-11-A // P437311650

A5-35

P437

A5 P437 Version History

Version

P437

Changes

Hardware

311

The binary I/O module X(4H) with four high-break


contacts is now available.

412/413
650

The P437 is now fitted with an improved processor


module.

Release: 2014-06-17

A second InterMiCOM communication module is now


optionally available.
Diagram
The updated terminal connection diagrams include the
terminal connection diagrams for the new modules:

P437 412 (for 84 TE pin-terminal connection)

P437 413 (for 84 TE ring-terminal connection)

Software
MEASI

Addition of this per unit measurand

(004 017) TH ER M: Th erm . re pli ca p.u .

The maximum temperature value since the last reset is


now displayed by the new measured operating value at
(004 233) MEA SI: Tempe rature Tmax.
This measured operating value is reset by the new
triggering parameter (003 045) MEA SI: Rs t. temp.
Tmax USER.
CBM

A5-36

Function group circuit breaker monitoring (CBM) has


been added.

P437/EN M/R-11-A // P437311650

P437

A5 P437 Version History

Version

Changes

MAIN

The following per unit measured operating values have


been added:

(004 070) MA IN: Freque ncy f p.u .

(005 072) MAIN: An gle V PG/IN p.u.

(005 073) MA IN: L oad an gl e phi A p.u

(005 074) MA IN: Load angl e ph i B p.u

(005 075) MA IN: Load angl e ph i C p. u

(005 076) MAIN: A ngle phi N p.u.

The parameter (006 096) MAI N: Meas . direct ion


P ,Q allows for setting the sign of the following
measured operating data values for active and reactive
power:

(004 050) MAIN: Active power P pri m.

(004 052) MA IN: R eac. powe r Q pri m.

(004 051) MA IN: A ctive powe r P p.u.

(004 052) MA IN: Reac. powe r Q p.u .

The following measured operating data for delayed/


stored phase current values have been added:

M AIN: I A prim,de mand (006 226)

MAI N: IB pri m,deman d (006 227)

MA IN : IC pri m,de man d (006 228)

MAIN: IA prim ,de m and stor. (006 223)

MAI N: I B pr im ,dem an d s tor. (006 224)

MA IN: IC prim,deman d s tor . (006 225)

MA IN : IA p.u.,de mand (006 235)

MAI N: IB p.u .,de mand (006 236)

MAI N: IC p.u .,de mand (006 237)

MAIN: IA p.u. ,demand s tor. (006 232)

MA IN : I B p.u.,deman d s tor. (006 223)

MAIN: I C p.u. ,de mand s tor. (006 234)

New addresses with a 32 bit measured value display


have been added for the 4 energy measured values:

(008 065) MA IN: A ct.e ne rgy ou tp.prim

(008 066) MAIN: A ct.e ne rgy inp. prim

0 ... 6,553,500.00 MWh

(008 067) MA IN: Re act.e n. outp. prim

0 ... 6,553,500.00 MWh

0 ... 6,553,500.00 Mvar h

(008 068) MAIN: Re act. e n. in p. pri m

0 ... 6,553,500.00 Mvar h

It is now possible to set the reset time of the manual


close command enable using this parameter:

(003 088) MA IN : Rel .t. e nab. man .cmd

IDMT and DTOC with settable inrush stabilization per


parameter subset: Stabilization selectable per stage
P437/EN M/R-11-A // P437311650

A5-37

P437

A5 P437 Version History

Version

Changes

(Phase; E/F and I2 stages): MAIN: Fu n ct.Rush


res tr .PSx (017 093, 017 064, 017 082, 017 083).
Settable maximum timer, for which inrush stabilization
should be effective: Blocked (w/o timer) or settable
from 0.01 to 10s. (019 001, 019 002, 019 003,
019 004) MA IN: t l ift rush rstr.P Sx.
The value range of (015 067) MA IN: C lose
cmd.pu ls e time has been increased to 0.100
10.000 s.
The previously available parameters (003 039) MAIN:
W arm res tart und (000 085) MA IN: C old re start
have been relabeled MAIN: Sof t W arm res tart and
MAI N: Sof t Col d re start, respectively. They still
trigger a restart of the device, but now the hardware
tests are not carried out anymore during the startup
phase. (This way the restart needs less time.)
For a restart including hardware tests, the following
new parameters can now be used:

(010 166) MA IN: Warm re start

(009 254) MA IN: C old re start

A setting for the release time of the enable for the


manual close command is now available:

(003 088) MA IN: R el. t. en ab. man.cmd

The manual trip command is enabled by:

(003 105) MAI N: E n.man .clos. cmd.USER

The enabling is signaled by the following new signal:

(039 113) MA IN: Man. cl. cm d.e nabl.

There is a phase-selective current flow monitoring


available now, identical to but independent of that in
function group CBF.

(010 223) MA IN: Curre nt f l ow A

(010 224) MA IN: C urr e nt flow B

(010 225) MA IN: C urr en t flow C

The MAIN: Fct.as si g.trip cmd.1 (021 001) is now


provided with a dedicated reduced selection table. This
prevents the configuration of signals that are already
linked in fixed logic such as DIST: Trip signal. This in
turn avoids jeopardizing fixed logic and thereby avoids
an unwanted 3-pole trip or non-selective trip of
extended zone 1.
INP

A5-38

The setting INP: Fi lter (010 220) is now available for


conformity with standard IEC 60255-22-7, class A.

P437/EN M/R-11-A // P437311650

P437

A5 P437 Version History

Version

Changes

MCMON

The following new signals are now available:

(007 213) MCMON: M. circ. V ref fau lty

(007 214) MC MO N: M.ci rc. VN G f aul ty

This permits blocking of only the associated voltage


timer stages in V<>, without blocking the entire V<>
function group.
V<>

There are now time voltage protection stages available


for Vref.
Stages V>>>, V<<<, Vref>>> and Vref<<< have been
added, including a separate timer for each of these new
stages.
For all three phase stages the 3p logic OR and AND
results are signaled.

IDMT

For all IP and Ineg types of characteristics the enable


threshold for the IDMT protection starting can now be
set with the factor KI (values range: 1 to 10) dependent
on Iref. This factor KI will result in a linear shifting of the
enable threshold along the X-axis of the respective
characteristic. The factor will not result in a shifting of
the characteristic itself.
Parameters:

IDMT: Factor KI ,P PSx

IDMT: F actor K I,ne g PSx

P437/EN M/R-11-A // P437311650

(007 250, 007 251, 007 252, 007 253)


(007 254, 007 255, 008 002, 008 005)

PC

The default value of (003 081) PC: Baud r ate has


been changed to 115.2 kBaud.

F_KEY

The value range of (003 037) F _KEY: Re tu rn t im e


fct .ke ys has been increased to 1 60000 s, the
default value has been changed to 10 s.

FT_RC

The maximum value of (003 079) FT_RC: Post-fault


tim e and (003 075) F T_R C: Max. re cordi ng t im e
has been increased to 750 periods.

GFSC

The value range of (018 062) GFSC: VNG> has been


changed to 0.010 0.500 Vnom.

PSB

The Power Swing Blocking function has been revised.


Inparticular, the S operating mode has been removed,
and PSB blocking has been enhanced.

COUNT

Function group COUNT has become available. Four


binary counters can be used to count the positive pulse
edges of a binary signal present at an appropriately
configured binary signal input.

A5-39

P437

A5 P437 Version History

Version

Changes

Many parameter labels have been modified so that


they harmonize with other MiCOM P30 devices.
DVICE

PC, DVICE

Instead of one parameter for the software version


(previously: (002 120) DVIC E: Software vers ion)
the version numbers 6XX and 7XX are now separately
stored in two new parameters:

(010 167) DV ICE: Sof tware ve rsi on 6XX

(010 168) DV ICE: Sof tware ve rsi on 7XX

It is now possible to upload new firmware into the


device via the TCP/IP protocol. For this purpose there
are several new network settings that are not identical
to the ones already existing within function group IEC:

(111 004) P C : IP addre ss

(111 005) PC: IP addre ss 1


(111 006) P C: I P addre s s 2
(111 006) P C: I P addres s 3

(111 008) P C : Su bn et mask

(111 009) PC: Subne t mask 1


(111 010) PC: Subne t mask 2
(111 011) PC: Subne t mask 3

(111 016) PC: IP addre ss mode

(111 017) P C: IP E nabl e confi g.

For testing purposes, information parameters store the


updated network settings for this firmware uploading
network.

IEC

A5-40

(111 000) D VIC E: I P addre s s

(111 001) DV IC E: Su bne t mask

(111 003) DV ICE: MAC addre s s

The number of clients for a report has been increased:


An unbuffered report (urcbA urcbP) can be allocated
to max. 8 clients (previously: 1), and a buffered report
(brcbA brcbH) can be allocated to max. 4 clients
(previously: 1).

P437/EN M/R-11-A // P437311650

P437

A5 P437 Version History

Version

Changes

FT_DA

The following measured fault data values have been


introduced:

(010 198) FT_D A: Fault type

(010 217) F T_DA : F lt.vol t. PG/P P prim

(010 199) FT_DA: F aul t curre nt P pr im

(010 216) F T_D A: F au lt curr. N pri m.

The parameters for the load data have been removed:

(004 037) FT_DA : L oad imped.pos t-f lt.

(004 038) FT_DA : Load angl e pos t-flt .

(004 039) FT_DA : Re si d.cu rr. post-f lt

The fault location may now be determined, based


solely on a ground starting condition (without a general
starting). For this the P437 determines all three phaseto-ground loop impedances and then provides the fault
location based on the reactance of the measurement
loop with the lowest impedance value.
THERM

With the new parameter THE RM: Re tain re pl ica


P Sx (009 019, 009 030, 009 032, 009 039) it can now
be configured whether the thermal replica is retained in
the non-volatile section of the devices memory so that
it will still be available after an interruption of the
supply voltage.

CBF

It is now possible to also use the residual current


(measured or calculated) as an additional criterion for
circuit breaker open.
The following setting parameters are new:

(022 184) CBF: Evalu ati on IN

(022 180) CB F: IN<

The signal (038 235) CBF : C u rren t flow N = Yes


flags that the residual current IE is greater than the
setting C BF: I N<.
LOG_2

There is a new function group LOG_2 (Programmable


Logic 2). It is identical to the previously available
function group LOGIC, but it offers only four logical
equations. These, however, have long-term timers,
settable from 0 to 60000 s (= 16 hours, 40 minutes).

LED

There is a new operating mode ES Alarmunit:


If this is set, the LED starts flashing with the first signal
edge of the assigned signal.
If this is acknowledged (i.e. the LED is reset), although
the assigned signal is still active, then the LED changes
to continuous light, and if the signal disappears later
on, then the LED goes off.
If the flashing LED is acknowledged (i.e. the LED is
reset) and the assigned signal is no longer present, the
LED immediately goes off.

P437/EN M/R-11-A // P437311650

A5-41

P437

A5 P437 Version History

Version

Changes

PSIG

The condition for signaling transmission channel failure


can now be set to match the application requirements:

P SIG: Bl k.f .t elcom.f lt PSx (012 246)


= Ch. (A)OR(B) faulty for 2- or 3-ended line
protection
= Ch. (A)AND(B) faulty for 2-ended line protection
with redundant channels

The send signal P SI G: Sen d (s ign al) (036 035) is


now raised even in 3-channel applications along with
any of the phase selective send signals, because it is
transmitted in the protocol according to IEC 103 as
compatible spontaneous message.
For unambiguous signaling an additional send signal is
implemented which is used along with a 1-channel
transmission:

A5-42

P SI G: Se nd (012 243)

LOGIC

The number of logic outputs (equations) has been


extended to 128.

DIST

The sensitive range has been combined with the high


range.

COMM4

The new function group COMM4 is available for devices


with a second InterMiCOM module. It features the same
setting parameters and signals as COMM3.

P437/EN M/R-11-A // P437311650

2014 Schneider Electric. All rights reserved.

Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com
Publication: P437/EN M/R-11-A

Publishing: Schneider Electric


08/2014

You might also like