You are on page 1of 4

Main_Data

MOTOR STARTING
Client:
Project:
Motor: 800 hp Motor
Case:
Utility Supply & Base Data:
Utility Gen. Volts (UGV):
25
Base MVA:
100
Base Pri. Volts:
25
SCMVA:
36.3274
X/R Ratio:
1.4
Base Sec. Volts:
4160

Transformer:
kV
MVA
kV
MVA at
p.u.
V

25

kV

Feeders:

Heating & Lighting Loads:


Capacitor on Starter Term.
Capacitor on MCC Bus

Motor Starting:
Initial Load:

Auto-Transformer:

80

Reactor:
2.19 Ohms
5.80 mH

65

338155896.xls

Motor
1 AWG/MCM
1
200 ft

0 kVA
750 kVA
60 kVA

49.9 kVA
FV Inrush:
83.15 %
Bases:
25
Tap
Prim.
%
%Volts
Voltage 100.00

Across the Line:

Short-Circuit:
Steady-state
RMS from utility
system only.

1
25
4160
6
10

MVA
kV
V
%
p.u.

800
4160
98.5
750
17
88.5
92
140
95

hp
V
A
%FLC
%
%
%
%FLT
%

Motor:
MCC
500
1
100

Conductor Size:
#/Phase:
Length:
Other Loads:

PF Capacitor:
Cap. Correct. PF:

Size:
Primary Volts
Secondary Volts:
Impedance:
X/R Ratio:

Voltage
Flicker
Voltage
Flicker
Voltage
Flicker

Based on UGV
25 kV
MVA:
Current (A):
X/R:

90 %PF
3300 V
4160 V

Horsepower:
Rated Voltage:
Full Load Current:
Inrush Current:
Locked Rotor PF:
Full Load PF:
Cap. Correct. PF:
Starting Torque:
Efficiency:

Calculations:
5322.94 kVA
Horsepower:
738.75 A
Full Load Current:
4160
4160
4160
FLT
Sec.
MCC
Motor Torque
%Volts %Volts %Volts
%
100.00 100.00

800 hp
99 Amps
Motor
A

MCC
kVA

92.31
7.69
94.60
5.40
94.62
5.38

74.28

74.22

73.96

71

546

2,247

81.97

81.93

65.31

55

482

1,738

81.56

81.52

53.66

37

396

1,777

Prim.
Bus
36.33
838.9
1.40

Sec.
Bus
11.77
1633
3.74

MCC
Bus
11.74
1629
3.72

Motor
Bus
11.62
1613
3.45

Accel

MOTOR ACCELERATION
Client:
0
Project:
0
Motor: 800 hp Motor
Case:
0
Input Data:
Synchronous Speed (SS):
Full Load Torque (FLT):
Total Inertia (WK^2):
Motor Locked Rotor Torque:
Motor Pull-up Torque (PUTQ):
Motor Pull-up Torque Speed (max. 75%):
Motor Break-down Torque:
Load Curve Exponent (0=level, 1=lin., 2=sq.):
Load Break-away Torque:
Load Rated Speed Torque:

Motor
%Speed
0
10
20
30
40
50
60
70
80
90
95
97.5
99

Load
%FLT
2.0
20.0
30.0
40.0
45.0
48.0
50.0
50.5
51.0
51.0
51.0
51.0
51.0

Motor
%FLT
150.0
146.4
143.6
141.6
140.4
140.0
141.6
145.1
153.7
183.7
220.0
168.6
100.0

3600
1167
122
150
140
50
220
0.1
2
51

rpm
lb.ft.
lb.ft^2
%FLT
%FLT
%SS
%FLT
%FLT
%FLT

Auto-Transformer Start, at 80 % Tap.


Motor
Motor
MtrRV
MtrRV
%FLA
%PF
%Volts
%FLA
750
17.0
65.3
490
745
17.6
65.4
487
740
18.1
65.5
485
734
18.7
65.6
482
729
19.2
65.7
479
724
19.8
65.8
477
711
20.3
66.1
470
688
22.5
66.6
458
656
28.0
67.2
441
568
39.0
69.3
393
480
50.0
71.6
343
295
67.6
77.0
227
100
88.5
83.3
83

MtrRV
%FLT
59.2
58.0
57.1
56.4
56.1
56.2
57.3
59.5
64.3
81.6
104.4
92.6
64.2

Time
Sec.
0.0
0.3
0.6
1.2
2.1
3.4
5.0
6.5
7.6
8.2
8.4
8.4
8.5

Pri.V
%Volts
94.6
94.6
94.6
94.7
94.7
94.7
94.8
94.9
95.1
95.6
96.3
98.2
100.7

MCC.V
%Volts
81.9
82.1
82.2
82.3
82.4
82.6
82.9
83.5
84.4
87.0
89.9
96.6
104.2

Accel.T
%FLT
57.2
38.0
27.1
16.4
11.1
8.2
7.3
9.0
13.3
30.6
53.4
41.6
13.2

250.0

Torque (%FLT)

200.0
150.0

MTRFVT
MtrRVT

100.0

Load T

50.0
0.0
0.0

338155896.xls

1.0

2.0

3.0

4.0

5.0

6.0

7.0

Page 2

8.0

9.0

Time (sec.)

Accel

Err:502

120.0

100.0

% Base Volts

80.0

Pri. V
60.0

MCC V
Motor V

40.0

20.0

Tim e (sec.)

0.0
0.0

1.0

2.0

3.0

4.0

5.0

6.0

7.0

8.0

9.0

Motor Amps (Log-Log)

Time (sec.) -->

10.0

1.0

0.1

100

1000
Amps (%FLC)

338155896.xls

Page 3

Miscel.

XLSTAR
MISCELLANEOUS CALCULATIONS
System Impedance and Short-Circuit MVA:
R1 =
X1 =
BMVA =

1.6 per unit


2.24 per unit
100 MVA

SCMVA: 36.32739 MVA


X/R Ratio:
1.4
Z1: 2.752744 per unit

Pre-start Voltage (%)


New SCMVA:

BMVA =
100 MVA
SCMVA = 36.32739 MVA
X/R Ratio=
1.4

Z1: 2.752744 per unit


R1:
1.6 per unit
X1:
2.24 per unit

100
36.327

Torque

Torque = hp x 5252 / rpm ft.lb.=

800 hp
3600 rpm
1167.1111 ft. lb.

Page 4