Professional Documents
Culture Documents
Assume you have a motor rated 500 HP, .95 power factor & 90 % efficiency energized
from a 4.16 Kv source, using a microprocessor motor protection relay, provide the typical
settings.
The full load current can be taken from the motor nameplate as well as the service factor.
The motor full load current can be calculated from the following: I = 500 (.746)/1.732
(4.16)(.85)(.9) =60 amps
Function Description
Setting
Motor Nameplate FLA
Increments
1.00 - 1.30 SF
.05
NEMA / UL Class 5 30
Overload Reset
1
.60 15kV
Line Frequency
60
50 or 60 Hz
Acceleration Time
30
1 - 20 seconds
.01
1
1(%)
1 (Second)
1 (%)
1 - 20 seconds
Under Current %
35
1 (%)
1 - 60 seconds
5 (%)
1 - 10 seconds
10(%)
0..01 - .5 seconds
.01
1 (%)
1
1 (%)
1 20 seconds
1 (%)
1 20 seconds
1 (%)
1 180 seconds
1 (%)
1 20 seconds
1 20 seconds
1 20 seconds
1 20 seconds
Motor KW Trip
0
1
1%
.01 1
.01
0 - 1, [0=Normal, 1= Reversed]
1 minute
0 = Disabled, or 1 10 starts
1 minute
12
Note: NEMA Class trip curves are based on a common tripping point of 600% of motor
Full Load Amps (FLA). Curves vary by the amount of time before the unit trips. As an
example, a Class 20 curve will trip in 20 seconds at 600% of FLA. Another example, Class
10 will trip in 10 seconds at 600% of FLA.
PT Value:1-200 (: 1) 1:1 = direct voltage input, 2-200: 1 = kV Voltage Input 1
(4160/104) V
CT Value: 5-2000 (:5)
Number of Turns through CT:
5
1 5 (in 1 increments)
40
60
1
Typical Settings
Typical Settings and Remarks
PU: 1.1*VNOM/60; TD: 0.3; reset TD: 5 alarm P.U.:
1.18*VNOM/60
alarm delay: 2.5s
25
Synchronism Check Max Slip: 6RPM; Max phase angle error: 10 Max
VMAG error:
2.5% VNOM
32
Reverse Power (one stage) PU: turbine 1% of rated; 15 s . PU:
Reciprocating engine:
10% of rated; 5 s
32-1
40
Loss-of-field (VAR Flow approach)
0.2s; Level 2
46
49
50/87
Differential via flux summation Cts
be used
50/27 IE
Inadvertent Energization Overcurrent with 27, 81
INOM) 27: 85%
Supervision
51N
Stator Ground Over- current (Low, Med Z Gnd, PU: 10% INOM; curve: EI;
TD: 4. Inst:
Phase CT Residual)
none. Higher PU required to
coordinate
with load. No higher than
25% INOM.
50/51N Stator Ground Over- current (Low, Med Z Gnd, P.U.: 10% INOM; Curve EI**,
TD4; Inst
Neutral CT or Flux Summation CT)
100% INOM. Higher PU if
required to
coordinate with load. No
higher than
25% INOM.
51GN, 51N Stator Ground Over- current (High Z Gnd) PU: 10% IFAULT at HV
Term.; Curve:
VI***; TD:4.
51VC
Voltage Controlled overcurrent
VI***; TD: 4.
51VR
Voltage Restrained overcurrent
TD: 4. Zero
Ground Overvoltage
10s 59P:
80% VNOM
67IE
Directional O/C for Inadvertent Energization PU: 75-100% INOM GEN; Definite
Time (0.10.25 sec.) ; Inst: 200% INOM GEN
81
Over/under frequency
0.5s; For
0.1s
87G
Generator Phase Differential
0.1 * Tap;
87N
Generator Ground
Slope 15%;
low tap
67N: current polarization; time:
0.25A; Curve:
VI***; TD: 2; Instantaneous:
disconnect
87UD 13
30%
Unit Differential
Coordinacin y Proteccin: :