PLC5ProcessorsOverview
The PLC5 processors are singleslot modules that are placed into the left
most slot of a 1771 I/O chassis. They are available in a range of I/O,
memory, and communication capability.
PLC5 processors have ports configurable for either a Data Highway Plus
messaging communication link or a Universal Remote I/O link. As a Universal
Remote I/O port, it can be configured as either an I/O scanner port or an
I/O adapter port. As an I/O scanner port, it monitors and controls the I/O on
the link by communicating with the I/O adapters for those I/O. As an
adapter port, it communicates only with the I/O scanner port on the link,
passing a maximum of one I/O rack of input and output data between the
two to provide distributed processing.
All PLC5 processors have Data Highway Plus and RS232C/422A/423A
communication ports. In addition to these ports, each Ethernet PLC5
processor has an Ethernet communication port, and each ControlNet PLC5 processor has a ControlNet communication port.
Although each Ethernet PLC5 processor has onboard Ethernet ports; additional Ethernet ports can be added to any PLC5
processor system with a 1785ENET Ethernet Interface Module. PLC5 processors do not have an onboard DeviceNet port. A
DeviceNet port can be added to the system with a 1771SDN scanner module.
Benefits
Ladderlogic and structuredtext programming
Advanced instruction set including file handling, sequencer, diagnostic, shift register, immediate I/O, and program control
instructions
Multiple main control programs for segregation of control tasks
Processor input interrupts and global status flags
Programmable fault response for reacting to a fault before the system goes down
Timed interrupt routine for examining specific information at specific time intervals
Protected memory selectable by word on selected processors
512 through 3072 maximum forcible I/O in any mix
Up to 50,176 maximum nonforcible I/O
Processorresident local I/O (1771 I/O modules)
Extendedlocal I/O on selected processors (1771 I/O modules)
Universal Remote I/O (1746, 1771, and 1794 I/O modules and 1791 I/O blocks)
DeviceNet I/O (1794 I/O modules, 1792D I/O blocks)
ControlNet I/O on selected processors (1771, 1734, 1794, 1797 I/O modules)
Universal Remote I/O ports can be configured as either an I/O scanner port or an I/O adapter port
BuiltinWebServices
Ethernet PLC5 processors (1785L20E, L40E, and L80E), and the Ethernet interface module (1785ENET) provide builtin web
http://www.ab.com/en/epub/catalogs/12762/2181376/2416247/1239760/1551229/print.html
1/8
11/27/2016
AutomationSystemsPLC5Processors
capabilities:
Web Diagnostics and Module Information lets a standard web browser access information stored in the PLC5 processor data
table, including module diagnostic information (requires RSLogix5, version 5.2 or later).
Web User Provided Pages allows for unique Web page creation to provide custom data table information. Any Internet user
who has network access to the PLC5 processor can view these pages, which can be either HTML pages that contain data
table elements, text and images, or Custom Data Monitor pages that contain data table elements in table form.
Domain Name Service (DNS) lets Internet users access the builtin Web server by a specified name instead of by IP address
(requires RSLogix5, version 5.2 or later).
PLC5ProcessorswithProtectedMemory(1785L26B,L46B,L86B,L46C15)
All enhanced PLC5 processors have memory protection. However, those processors designated as having the memory protection
feature have the added capability of limiting access to individual words.
Choose a PLC5 processor with protected memory when access must be limited to critical or proprietary areas of programs,
selectively guard processor memory and I/O words, or restrict use of processor operations.
The PLC5 protected memory feature expands system validity and security beyond what is provided by the passwordandprivilege
capability of the other PLC5 enhanced processors. Custom software protection schemes can be designed for each application.
Rockwell Software programming software can be used to assign class privileges to specific user accounts or a user job function,
such as system administrator, plant engineer, maintenance engineer, or operator. Using four privilege classes and associated
passwords, access can be limited to critical program areas and restrict access to:
Communication channels
Remote nodes attached to a DH+ or ControlNet network
Program files
Data files
Individual data words
The PLC5/26, PLC5/46, and PLC5/86 protected processors are equivalent to the PLC5/20, PLC5/40, and PLC5/80 standard
processors, respectively, plus the added memory protection feature. These processors are listed under the heading "Standard PLC5
Processors with Protected Memories" in the PLC5 Processor selection tables.
The PLC5/46C15 protected processor is equivalent to the PLC5/40C15 ControlNet processor plus the added memory protection
feature. This processor is listed under the heading "ControlNet PLC5 Processors with Protected Memories" in the PLC5 Processor
selection tables.
Specifications
TimeofDay Clock/Calendar
Maximum Variations at 60 C
Typical Variations at 20 C
Timing Accuracy
1 program scan
Battery
1770XYC
Operating Shock
Nonoperating Shock
Vibration
1 g at 10500 Hz
0.012 in. peaktopeak displacement
Operating Temperature
060 C (32140 F)
Nonoperating Temperature
4085 C (40185 F)
http://www.ab.com/en/epub/catalogs/12762/2181376/2416247/1239760/1551229/print.html
2/8
11/27/2016
AutomationSystemsPLC5Processors
Relative Humidity
595% noncondensing
Certifications
When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification
details.
SelectingtheProcessorCategory
Three categories of PLC5 processor are available:
Standard Standard PLC5 processors feature versatile builtin communication options that permit development of a control
architecture that is specific to an application, and an advanced programming instruction set.
Ethernet Ethernet PLC5 processors offer embedded TCP/IP communication capabilities that let them communicate with
other Ethernet PLC5 processors and host computers. They thus integrate AllenBradley architecture into the industry
standard TCP/IP network, offering highperformance peertopeer communication via use of PLC5 message instructions.
Ethernet PLC5 processors are optimized for realtime sequential and regulatory control.
ControlNet ControlNet PLC5 processors are used for control and information processing. They offer highspeed
communication through a ControlNet port. The ControlNet network provides both I/O control faster than the Universal
Remote I/O link and peertopeer communication faster than the DH+ network. These processors eliminate the need for
block transfer programming when communicating with 1771 I/O modules on the ControlNet network that require a onetime
configuration and then continuously read or write.
PLC5ProcessorCategories
Processor Category
I/O, Max.
I/O Chassis,
Max.
I/O Communication
General
Communication
Ports
Standard PLC5
Processor
512 to 3072
(any mix)
5 to 93
Processorresident
local I/O
Extended local I/O
Universal Remote I/O
DeviceNet I/O
8K to 100K words
protected (PLC5/26, 5/46, and
5/86 only)
Ethernet
DH+
RS232C/422
A/423A
Ethernet
PLC5 Processor
512 to 3072
(any mix)
13 to 65
Processorresident
local I/O
Universal Remote I/O
DeviceNet I/O
Ethernet
DH+
RS232C/422
A/423A
ControlNet PLC5
Processor
Forcible
512 to 3072 (any
mix)
Nonforcible
3200 to 50176
77 to 125
Processorresident
local I/O
Universal Remote I/O
DeviceNet I/O
ControlNet I/O
6K to 100K words
protected (PLC5/46C only)
Ethernet
ControlNet
DH+
RS232C/422
A/423A
PLC5Processors
StandardPLC5Processors
Total I/O, Max. is the actual I/O circuits, regardless of the number of connection points or I/O image bits. The number of
I/O image bits (8, 16, or 32) that correspond to an I/O module limit the number of I/O at that module; however, some
modules may have less I/O than I/O image bits. This includes local I/O, extended local I/O, and Universal Remote I/O
combined. This does not include DeviceNet I/O.
Any mix means that any number of the I/O can be inputs and any number can be outputs, with no placement restrictions.
Complementary means that to configure this many I/O, pairs of modules must have duplicate addresses. This pair must be
either 2 output modules sharing the same output image bits or an input module and an output module complementing each
other. In either case, module placement must conform to these restrictions.
I/O rack is an I/O addressing unit that can contain a max. of 128 I/O with unique addressing of I/O modules or 256 I/O with
duplicate addressing of I/O modules.
http://www.ab.com/en/epub/catalogs/12762/2181376/2416247/1239760/1551229/print.html
3/8
11/27/2016
Cat. No.
AutomationSystemsPLC5Processors
Memory Types
Analog I/O,
Max.
PLC5/11
8K
512
10 ms at 57.6 kbit/s
7 ms at 115.2 kbit/s
3 ms at 230.4 kbit/s
1785L20B
PLC5/20
16kB
512
10 ms at 57.6 kbit/s
7 ms at 115.2 kbit/s
3 ms at 230.4 kbit/s
1785L30B
PLC5/30
32K
1024
10 ms at 57.6 kbit/s
7 ms at 115.2 kbit/s
3 ms at 230.4 kbit/s
1785L40B
PLC5/40
48kB
2048
10 ms at 57.6 kbit/s
7 ms at 115.2 kbit/s
3 ms at 230.4 kbit/s
1785L40L
PLC5/40L
48K
2048
1785L60B
PLC5/60
64kB
3072
10 ms at 57.6 kbit/s
7 ms at 115.2 kbit/s
3 ms at 230.4 kbit/s
1785L60L
PLC5/60L
64kB
3072
1785L80B
PLC5/80
100kB
3072
10 ms at 57.6 kbit/s
7 ms at 115.2 kbit/s
3 ms at 230.4 kbit/s
PLC5/26
16kB
512
10 ms at 57.6 kbit/s
7 ms at 115.2 kbit/s
3 ms at 230.4 kbit/s
1785L46B
PLC5/46
48K
2048
10 ms at 57.6 kbit/s
7 ms at 115.2 kbit/s
3 ms at 230.4 kbit/s
1785L86B
PLC5/86
100kB
3072
10 ms at 57.6 kbit/s
7 ms at 115.2 kbit/s
3 ms at 230.4 kbit/s
Max. number of data table words and max. number of timers and counters are userconfigured.
Limit of 32K words per data table file.
Limit of 32K words per data table file and 56K words per program file.
Limit of 32K words per data table file and a total data table size of 64K words. Limit of 56K words per program file.
In a single chassis, extendedlocal or remote. For Universal Remote I/O unless otherwise specified.
http://www.ab.com/en/epub/catalogs/12762/2181376/2416247/1239760/1551229/print.html
4/8
11/27/2016
AutomationSystemsPLC5Processors
StandardPLC5Processors(continued)
Cat. No.
RS232C / 422A
/ 423A Ports
Backplane
Current Load @
5V
2.3A
PLC5/11
1785L20B
PLC5/20
1 DH+
1 DH+/Remote I/O (Adap or Scan)
13
12
2.3A
1785L30B
PLC5/30
29
28
2.3A
1785L40B
PLC5/40
61
32 max. per
I/O link
3.3A
1785L40L
PLC5/40L
61
16
32 max. per
I/O link
3.3A
1785L60B
PLC5/60
93
32 max. per
I/O link
3.3A
1785L60L
PLC5/60L
81
16
32 max. per
I/O link
3.3A
1785L80B
PLC5/80
93
32 max. per
I/O link
3.3A
PLC5/26
1 DH+
1 DH+/Remote I/O (Adap or Scan)
13
12
2.3A
1785L46B
PLC5/46
61
32 max. per
I/O link
3.3A
1785L86B
PLC5/86
93
32 max. per
I/O link
3.3A
Universal Remote I/O Chassis any device with a remote I/O adapter port compatible with the AllenBradley Universal Remote I/O link. This includes
1771 I/O chassis, 1791 I/O blocks, PanelView displays, RediPANEL displays, Dataliner displays, 1336 drives.
RS422A and RS423A both have a cable length limitation of 61 m (200 ft).
EthernetandControlNetPLC5Processors
Total I/O, Max. is the actual I/O circuits, regardless of the number of connection points or I/O image bits. The number of
I/O image bits (8, 16, or 32) that correspond to an I/O module limit the number of I/O at that module; however, some
modules may have less I/O than I/O image bits. This includes local I/O, ControlNet I/O, and Universal Remote I/O combined.
This does not include DeviceNet I/O.
Any mix means that any number of the I/O can be inputs and any number can be outputs, with no placement restrictions.
Complementary means that to configure this many I/O, pairs of modules must have duplicate addresses. This pair must be
either 2 output modules sharing the same output image bits or an input module and an output module complementing each
other. In either case, module placement must conform to these restrictions.
I/O rack is an I/O addressing unit that can contain a max. of 128 I/O with unique addressing of I/O modules or 256 I/O with
duplicate addressing of I/O modules.
Cat. No.
Memory Types
Analog
I/O, Max.
512
10 ms at 57.6
kbit/s
7 ms at 115.2
kbit/s
3 ms at 230.4
kbit/s
PLC5/20E
16K
http://www.ab.com/en/epub/catalogs/12762/2181376/2416247/1239760/1551229/print.html
5/8
11/27/2016
AutomationSystemsPLC5Processors
1785L40E
PLC5/40E
48K
2048
10 ms at 57.6
kbit/s
7 ms at 115.2
kbit/s
3 ms at 230.4
kbit/s
1785L80E
PLC5/80E
100K
3072
10 ms at 57.6
kbit/s
7 ms at 115.2
kbit/s
3 ms at 230.4
kbit/s
PLC5/20C
16K
Forcible
512 (any mix) or
512 in + 512 out
(complementary)
Nonforcible
32000
Forcible
512
Non
forcible
32000
ControlNet I/O
0.5 ms
(average)
Universal Remote
I/O
10 ms @ 57.6
kbit/s
7 ms @ 115.2
kbit/s
3 ms @ 230.4
kbit/s
1785L40C15
PLC5/40C
48K
Forcible
2048 (any mix) or
2048 in + 2048 out
(complementary)
Nonforcible
48000
Forcible
2048
Non
forcible
48000
ControlNet I/O
0.5 ms
(average)
Universal Remote
I/O
10 ms @ 57.6
kbit/s
7 ms @ 115.2
kbit/s
3 ms @ 230.4
kbit/s
1785L80C15
PLC5/80C
100K
Forcible
3072 (any mix) or
3072 in + 2048 out
(complementary)
Nonforcible
50176
Forcible
3072
Non
forcible
50176
ControlNet I/O
0.5 ms
(average)
Universal Remote
I/O
10 ms @ 57.6
kbit/s
7 ms @ 115.2
kbit/s
3 ms @ 230.4
kbit/s
Forcible
2048 (any mix) or
2048 in + 2048 out
(complementary)
Nonforcible
48000
Forcible
2048
Non
forcible
48000
ControlNet I/O
0.5 ms
(average)
Universal Remote
I/O
10 ms @ 57.6
kbit/s
7 ms @ 115.2
kbit/s
3 ms @ 230.4
kbit/s
PLC5/46C
48K
Max. number of data table words and max. number of timers and counters are userconfigured.
Limit of 32K words per data table file.
Limit of 32K words per data table file and a total data table size of 64K words. Limit of 56K words per program file.
In a single nonlocal chassis.
Non forcible I/O is only available as ControlNet I/O.
With several I/O chassis connected to the processor across a ControlNet link, the average I/O scan time per I/O rack in a single chassis is 0.5 ms. However
the min. time for a complete ControlNet I/O scan (network update time) is 2 ms. Therefore, with a single I/O chassis connected to the processor across a
ControlNet link, the min. I/O scan time for that single I/O chassis is 2 ms. Even with several I/O chassis connected to the processor across a ControlNet link,
the min. time for an individual I/O chassis to be updated is 2 ms.
EthernetandControlNetPLC5Processors(continued)
Cat. No.
RS232C /
422A / 423A
Total Extended Universal Ports
http://www.ab.com/en/epub/catalogs/12762/2181376/2416247/1239760/1551229/print.html Local
Remote
Backplane
Current Load
at 5V
6/8
11/27/2016
AutomationSystemsPLC5Processors
Local
Remote
PLC5/20E
1 Ethernet
1 DH+
1 DH+/Remote I/O (Adap or Scan)
13
12
3.6A
1785L40E
PLC5/40E
1 Ethernet
2 DH+/Remote I/O (Adap or Scan)
61
60
3.6A
1785L80E
PLC5/80E
1 Ethernet
2 DH+/Remote I/O (Adap or Scan)
65
64
3.6A
PLC5/20C
77
12
2.7 A (typ)
3.0A (max)
1785L40C15
PLC5/40C
125
60
3.0A
1785L80C15
PLC5/80C
125
60
3.0A
125
60
3.0A
PLC5/46C
Limited by datatable size and how much data table you use for each chassis.
Universal Remote I/O Chassis any device with a remote I/O adapter port compatible with the AllenBradley Universal Remote I/O link. This includes
1771 I/O chassis, 1791 I/O blocks, PanelView displays, RediPANEL displays, Dataliner displays, 1336 drives.
The ControlNet I/O map table can contain up to 128 entries. Each maptable entry corresponds to one scheduled transfer of data.
RS422A and RS423A both have a cable length limitation of 61m (200 ft).
MemoryDevices
Cat. No.
Function
Memory Size
1785ME16
EEPROM
Program backup
16K words
1785ME32
EEPROM
Program backup
32K words
1785ME64
EEPROM
Program backup
64K words
1785M100
EEPROM
Program backup
100K words
PLC5ProcessorBackupSystem
Benefits
Easy to configure
Needs no additional programming for most systems
Applies stateoftheart ControlNet services to enable synchronized scanning without the need for a dedicated connection
Offers redundant media for increased network availability
Performs equivalence checking of key structures and files to detect divergence automatically, without additional
programming
Provides userconfigurable file transfers of applicationspecific data for increased system integrity
Enables manual switchover for ease of testing and troubleshooting
Records switchover activity with timestamping for subsequent diagnostics
HotBackupMemoryCartridge
Cat. No.
Compatible Processors
Memory Size
http://www.ab.com/en/epub/catalogs/12762/2181376/2416247/1239760/1551229/print.html
7/8
11/27/2016
1785CHBM
AutomationSystemsPLC5Processors
1785L40C15 or 1785L80C15
100K words
TypicalConfigurationforControlNetPLC5BackupSystem
Copyright2016RockwellAutomation,Inc.AllRightsReserved.
http://www.ab.com/en/epub/catalogs/12762/2181376/2416247/1239760/1551229/print.html
8/8