You are on page 1of 10

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO.

2, APRIL 2011 799

Practical Power Quality Charts


for Motor Starting Assessment
Xiaoyu Wang, Member, IEEE, Jing Yong, Member, IEEE, Wilsun Xu, Fellow, IEEE, and
Walmir Freitas, Member, IEEE

Abstract—The impact of motor starting on power quality can be curve [8], the Information Technology Industry Council (ITIC)
assessed using detailed computer simulation studies. However, not curve [9], and the IEC/IEEE flicker standards [10].
every motor installation case needs such an extensive assessment. The voltage sag and flicker effects of motor starting can be as-
Utility planners are interested in quick evaluation of the potential
sessed by detailed system simulations [11], [12]. However, this
impact of a motor installation proposal. Based on the findings, they
can then determine if detailed case studies and what types of case process is complicated and time-consuming in practice. In many
studies are necessary. This paper presents three charts for motor cases, utilities and motor users are more interested in a simpler
starting planning according to three power quality concerns. These and faster method for a first-cut understanding of the potential
concerns are the amount of voltage drop caused by motor starting, impact of a motor starting situation [13], [14]. With limited in-
the compliance to the ITIC curve, and the compliance to the IEC formation available, the method shall reveal whether an induc-
flicker meter limits. These charts can help utility planers to con- tion motor application may cause any power quality problem. If
duct quick and first-cut assessment of a motor starting situation.
They also reveal the key factors affecting the motor starting related
the results indicate violations of voltage sag or flicker limits, a
power quality concerns. The principles behind these charts are ex- detailed investigation can then be undertaken.
plained. Examples are given to show how to use them for quick A simple method utilizing the constant energy criterion to
assessment of motor starting impact. estimate the voltage sag impact of induction motor starting was
Index Terms—Flicker, motor starting, power quality (PQ), described in [15]. Although the method simplifies the motor
voltage sag. starting analysis, it is not intuitive enough for quick motor
starting assessment. This is partially due to the fact that two key
parameters, motor size and system short-circuit level, are not
I. INTRODUCTION explicitly used. In addition, the applied specific energy curve
OWER-QUALITY issues caused by induction motor [16] has relative large error compared with the ITIC curve,
P starting have been recognized and investigated for a long
time. It is known that direct motor starting typically produces
which was recently designated to replace the CBEMA curve.
In North America, the historic flicker curves [17], [18] have
voltage sags with a duration longer than 30 cycles, especially been gradually replaced by the IEC flicker assessment method
when a large size motor with high inertia load is connected to a [19]. The IEC method requires the implementation of a sophis-
weak power system [1]–[6]. Such long duration sags can lead ticated flicker meter scheme which is designed mainly for mea-
to a wide range of sensitive equipment to drop out [7]. In addi- surement purposes. Little work has been done on how to apply
tion, voltage flicker may arise because of frequent or sporadic the IEC flicker meter to the planning process.
motor starting. Whenever an induction motor is connected or In this paper, a systematic and practical method to evaluate
started, system planning engineers are interested to know if the effect of voltage sag and flicker generated by induction
the motor starting would result in the unacceptable voltage motor starting is presented. Analytical approaches are used
sags and flicker according to the restriction of the established to derive charts that can provide a quick and first-cut under-
power acceptability curves or standards, such as the Computer standing of the potential impact of a motor starting situation.
The paper is organized as follows. Three motor starting guide-
& Business Equipment Manufacturers Association (CBEMA)
line charts are proposed in Section II. The use of the charts is
also explained in this section. Sections III–V present the devel-
Manuscript received October 14, 2009; revised July 12, 2010; accepted opment process of the guideline charts for three types of power
November 21, 2010. Date of current version March 25, 2011. This work was
supported by Alberta power industry. Paper no. TPWRD-00777-2009. quality concerns: voltage drop, voltage sag and voltage flicker,
X. Wang is with the Department of Electrical Engineering, State Key Lab respectively. Sensitivity studies results are also presented
of Power Systems, Tsinghua University, Beijing 100084, China (e-mail: xi- in these sections. Since the proposed methods are based on
aoyuw@tsinghua.edu.cn).
J. Yong is with the State Key Laboratory of Power Transmission Equipment simplifications, electromagnetic transient (EMT) simulations
and System Security and New Technology, Chongqing University, Chongqing are used in Section VI to validate the proposed charts. The
400044, China (e-mail: yongjingcq@yahoo.com.cn). conclusions are summarized in Section VII.
W. Xu is with the Department of Electrical and Computer Engineering, Uni-
versity of Alberta, Edmonton, AB T6G 2V4, Canada (e-mail: wxu@ualberta.
ca).
W. Freitas is with the Department of Electrical Energy Systems, University
II. PRACTICAL CHARTS FOR MOTOR STARTING ASSESSMENT
of Campinas, Campinas 13083-852, Brazil (e-mail: walmir@ieee.org). The direct motor starting applies the network voltage to the
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. motor terminal directly. Fig. 1 shows the schematic diagram of
Digital Object Identifier 10.1109/TPWRD.2010.2096237 a real-life direct motor starting case. This case involves a 25 kV
0885-8977/$26.00 © 2011 IEEE
800 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 2, APRIL 2011

Fig. 1. Diagram of direct motor starting in power distribution systems.

Fig. 3. Voltage sag chart for motor starting assessment.


Fig. 2. Voltage drop chart for motor starting assessment.

MW motor is to be installed at the PCC through a step down


distribution feeder typically seen in rural North America. The transformer. A point (1.1 MW, 28 MVA) can be drawn in the
parameters of this system are listed in Appendix A. A 1.1 MW chart, which is shown as a red circle in Fig. 2. This point re-
(1500 hp) induction motor is planned to be connected to the sides in the region with power quality (PQ) concern. Thus it can
feeder. The voltage quality at the point of common coupling be concluded that the 1.1 MW motor is likely to cause exces-
(PCC) is of concern during the starting process of the motor sive voltage drop at the PCC when the motor is directly started.
in Fig. 1. Three guideline charts proposed in this paper can be Consequently, detailed motor starting analysis is recommended
used to quickly assess the motor starting from the perspective to further investigate the voltage drop problem.
of voltage drop, voltage sag and flicker limitations. The voltage
drop chart is designed to address the concern on the amount of B. Use of Voltage Sag Chart
voltage drop caused by motor starting. The voltage sag chart Considering the voltage drop amount alone is not sufficient
considers both the voltage drop amount and the sag duration to understand the impact of motor starting, since the severity
according to the ITIC curve. The flicker chart is developed based of a voltage sag event is a function of both the voltage drop
on the IEC flicker limit. amount and its duration. If a motor has a large inertia con-
stant, the motor starting process can be long enough to cause
A. Use of Voltage Drop Chart
a voltage sag problem. The voltage sag chart that can take into
According to utility practices [20], a motor starting procedure account both factors is then proposed. The basic idea of the
that causes a voltage drop of 5% or more at the PCC during the chart is that a motor starting event should not cause violation
starting process is not acceptable. The voltage drop chart is de- of the ITIC curve. Fig. 3 shows the voltage sag chart developed
veloped for utility planners to quickly determine if a motor in- for direct motor starting. In this chart, the x-axis is the ratio of
stallation scenario will result in unacceptable voltage drop (i.e., the motor size to the short-circuit level at the PCC
greater than 5%). The proposed chart is a set of curves whose where the voltage sag is assessed for motor starting. The y-axis
x-axis is the motor capacity and y-axis is the system short-circuit is the motor inertia constant . Like the curve in the voltage
level at the PCC. Fig. 2 displays the simplest and a conserva- drop chart, the curve in the voltage sag chart also indicates a
tively constructed chart, which has only one curve. This curve boundary below which the impact of direct motor starting can
indicates a boundary above which the impact of direct motor be considered as insignificant in terms of its voltage sag impact,
starting can be considered as insignificant in terms of voltage while above which direct motor starting could cause a problem.
drop amount, while below which direct motor starting could Detailed motor starting analysis is therefore recommended for
cause a voltage drop exceeding 5%. Detailed motor starting the latter case. Some examples are given as follows to illustrate
analysis is therefore recommended for the latter case. the use of the voltage sag chart.
As an example, we consider the case shown in Fig. 1 where 1) Case 1: Motor Starting Will Not Cause Power Quality
the system short-circuit level is 28 MVA at the PCC and a 1.1 Concern: In the first example, assume that the ratio of the motor
WANG et al.: PRACTICAL PQ CHARTS FOR MOTOR STARTING ASSESSMENT 801

size to the system short-circuit level is 0.032 at the PCC. For


the illustrated system shown in Fig. 1 the motor will be 0.9 MW
(1250 hp) as the system short-circuit level is 28 MVA at the
PCC. The motor has an inertia constant of 1 s. Then a point C
(0.032, 1) can be found in the region without PQ concern in the
chart shown in Fig. 3. As a result, this point (point C) will not
cause a voltage sag problem at the PCC when the ITIC curve is
applied for direct motor starting.
2) Case 2: Motor Starting Will Cause Power Quality Con-
cern: In Fig. 3, point D is related to the point with
0.044 and . This point is above the boundary curve
and a detailed analysis needs to be conducted for this point.
3) Case 3: Terminal Points of the Boundary Curve: The
points at the terminals of the boundary curve (point A and point
B) represent two extreme conditions. For point A, the value of
is 0.022. If is less than 0.022, the ITIC curve
will not be violated no matter what the inertia constant is. On the
other hand, if is greater than 0.052, which is related to
point B, the ITIC curve will always be violated no matter how
small the inertia constant is. Note that motor starting usually
lasts more than 0.5 second for medium and large motors and for
small motors usually one does not need to do a detailed analysis.
The classification of a motor as small, medium and large can be
done based on [21]. Accordingly, an induction motor with 2, 4
or 6 poles is classified as small, medium or large when the nom-
inal power is smaller than 0.75 kW (1 hp); higher than 0.75 kW
and smaller than 370 kW (500 hp); or larger than 370 kW (500
hp), respectively.

C. Use of Voltage Flicker Chart


Fig. 4. Voltage flicker chart for motor starting assessment. (a) P = 0:9 curve.
Another motor starting concern is the voltage flicker. The (b) P = 07: curve.
flicker level caused by motor starting is determined not only by
the voltage drop amount but also by the frequency of occurrence
of starting. Another complication is that the human element is the IEC standard [23], where is required to be less than 0.9
involved when determining the permissible amount of flicker for utility medium voltage (MV) system planning purposes.
voltage. In recent years, the IEC flicker meter has gained wide Fig. 4(b) shows the (MV planning level [23]) curve
acceptance, which should be applied to motor starting assess- for the motor starting cases within the starting frequency less
ment [10]. than once per 10 minutes and more than once per two hours.
In this paper, an approximate formula that connects the IEC The time interval of 2 hours is defined by IEC for calcula-
flicker meter results (i.e., the short-term flicker severity index tions. Similar to the curve, the boundary flicker curve
and the long-term flicker severity index levels) with also indicates whether a detailed flicker analysis should be per-
the frequency of motor starting and the corresponding voltage formed or not.
drop amount at the PCC is used to derive a motor starting flicker Examples of how to use the flicker chart are given as follows.
chart. The flicker chart consists of two curves: the curve and 1) Case 1: Example For the Curve: It is known that the
the curve. The chart shows, for a given voltage drop amount, motor connected to the PCC in Fig. 1 is started 3 times per 10
what is the highest frequency of repetitive motor starting that minutes and that the voltage drop amount at the PCC for
will lead to the violation of the IEC flicker meter limits. each start is 4.8%. The question is if the motor will cause the
Fig. 4(a) shows the flicker curve for motor starting. flicker problem according to the IEC flicker standard. Fig. 4(a)
In this figure, the x-axis is the number of motor starting per 10 displays that the above motor starting event is related to point A
minutes and the y-axis is the voltage drop amount at the PCC which is located inside the region with flicker concern. Thus, the
in per unit . The time interval 10 minutes is exploited flicker problem could be incurred, and a detailed flicker analysis
when expressing the motor starting frequency. This is because is needed for this case. However, if the voltage drop amount
the value of is calculated every 10 minutes by the IEC is decreased to 3.5% for each time (point A’ in Fig. 4(a)), the
flicker meter. From Fig. 4(a) one can see that when the repeti- flicker problem caused by motor starting will not occur.
tive motor starting event is located above the boundary flicker 2) Case 2: Example For the Curve: The objective is to
curve, a flicker problem occurs for this motor starting. The limit assess the motor starting flicker at the PCC with the following
of for the boundary flicker curve is recommended by conditions: and motor starting frequency is
802 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 2, APRIL 2011

is (i.e., cosine of the angle of the motor equivalent


impedance for slip equal to 1), then in the motor base, we have

(4)

(5)
Fig. 5. Equivalent circuit for voltage drop amount assessment.
Also we can assume and
(where and are the stator resistance and reactance,
2 times per hour. In this case, the motor starting frequency is and are the rotor resistance and reactance, respectively,
less than once per 10 minutes so that the curve cannot be and the shunt magnetization impedance is neglected). Based on
used. The curve will be applied for this case. Point B in Fig. the above circuit, the voltage level at the PCC, , can be esti-
4(b) can be found to represent the motor starting case. Fig. 4(b) mated, which can be symbolically represented as
reveals that point B is above the curve and within
the region with flicker concern. As a result, the flicker problem (6)
could happen.
The boundary curves of the proposed guideline charts are es- Since we are interested in determining the system size
tablished using different power quality limits at the PCC. All the for a given or threshold, the above equation can be re-
charts are developed by considering the worst case voltage vio- arranged to show the relationship of as a function of and
lation conditions and the motor starting characteristics. Details and other parameters. Based on the procedure shown in Ap-
on the derivation of the curves are described in the following pendix B, such a relationship can be established as:
sections.
(7)
III. DEVELOPMENT OF THE VOLTAGE DROP CHART
where
A. Chart Derivation
In order to construct the voltage drop chart, one has to execute
two steps: (1) determine the system parameters based only on
the motor size and on the system short-circuit level at the PCC
and (2) create the chart based on a simple formula with the re-
lationship between the system short-circuit level and the motor
size. The system presented in Fig. 1 will be used as an example.
Fig. 5 shows the equivalent circuit of the example system. In these expressions, represents the open circuit voltage at
Initially, the following parameters are usually known for the the PCC and represents the PCC voltage level at the instant of
motor starting analysis: motor energization. The short-circuit level for different voltage
• Motor size— (MVA). drop limits imposed by the distribution utility can be obtained
• System short-circuit level at the PCC— (MVA). using these expressions. For the chart developed in this paper
In order to evaluate the motor starting impact the impedance and (i.e., ) are used. Other
parameters shown in Fig. 5 must be determined based only on parameters used for generating the basic chart shown in Fig. 2
the available information. First, we represent the system equiv- are: , , , 6, .
alent impedance based on the ratio and the
system ratio, which are known. Thus, and referred B. Sensitivity Analysis
to the motor size can be calculated as follows: The development process of the chart shows that the chart
is sensitive to the system ratio , transformer reactance
(1) (determined by the parameters of and ), motor starting
power factor , motor starting inrush current coefficient .
(2) Sensitivity studies on these factors were conducted, and the re-
sults are reported in the following figures.
where is the system ratio. Fig. 6 presents the chart for different ratios of the
If we assume that the rated capacity of the transformer short-circuit level seen from the PCC. This figure shows that
is times the motor size , and that the transformer percent the lower the ratio is, the higher the maximum allowable
impedance referred to the transformer base is , then the trans- motor size is for the same . This phenomenon is expected
former impedance referred to the motor size is as the lower the ratio, which is equivalent to a smaller
reactance and a higher resistance , the lower the reactive
(3) power losses in the system impedance. Consequently, the reac-
tive power delivered to the motor can be reduced, allowing the
Assuming that the inrush current of the motor is times increase of the maximum motor capacity. Fig. 7 presents the
the motor rated current and that the initial motor power factor chart considering different sizes of the step-down transformer
WANG et al.: PRACTICAL PQ CHARTS FOR MOTOR STARTING ASSESSMENT 803

Fig. 6. X=R ratio sensitivity (k = 6; cos ' = 0:2; = 1:2; = 5%). ; ' = 0:2; = 1:2; =
Fig. 8. Inrush current factor sensitivity ( = 10 cos
5%).


Fig. 9. Motor power factor sensitivity ( = 10 ;k = 6; = 1:2; = 5%).
k ;
Fig. 7. Transformer size sensitivity ( = 6 cos ' = 0:2; = 10; = 5%).

connecting the motor, which is represented as a percentage of


the motor size. A transformer reactance of 5% in the trans-
former base was used and the transformer size is times the
motor size. Fig. 7 reveals that larger transformers will limit the
connecting motor capacity for the same . This result is ex-
pected since the higher the factor is, corresponding to a lower
value of transformer impedance (referred to the motor base),
the higher the inrush current drawn by the motor is. Thus, the
voltage drop through the system impedance is higher. Conse-
quently, the maximum motor size is reduced. The inrush cur-
rent factor was analyzed in Fig. 8, which indicates that the
lower the inrush current factor is, the higher the maximum motor Fig. 10. Motor starting voltage sag mapped to the ITIC curve.
size is. This result is expected since the lower the inrush factor,
the higher the motor impedance, in accordance to (4) and (5).
As a result, the inrush current drawn by the motor is smaller. IV. DEVELOPMENT OF THE VOLTAGE SAG CHART
Therefore, the maximum capacity of the motor can be further Fig. 10 shows the voltage sag boundary of the bottom ITIC
increased. In Fig. 9 the initial motor power factor is ana- curve. On this curve, voltage levels above 80% of the nom-
lyzed. This factor reflects the relationship between and inal are acceptable if their duration is less than 10 seconds,
of the motor equivalent circuit in Fig. 5 for a slip equal to 1. The and voltage levels between 70% and 80% of the nominal are
result displayed in Fig. 9 reveals that the curve will not be con- acceptable if the duration is less than 0.5 second. The curve
siderably changed when the initial motor power factor is small. further reveals that voltage levels above 90% of the nominal
804 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 2, APRIL 2011

are considered as always acceptable. Fig. 10 also plots sev-


eral motor starting events marked as “ ”. As the motor size in-
creases, the voltage drop amount increases and the trace will
cross the 80% threshold. The results also reveal that the motor
starting cases often involve sag durations between 0.5 to 10 sec-
onds or higher. So the region of concern is the 80% threshold
line and the boundary between the 80% and the 90% threshold
lines.
Now let’s consider the barely acceptable motor starting cases
that result in 20% voltage drop. If the motor inertia constant
increases without causing voltage drop change, the sag event
points will move rightward as it takes more time to start the
motor. Point corresponds to the largest inertia constant that
can be accepted without violating the ITIC curve. The voltage
sag impact chart shows this largest acceptable inertia constant
as a function of the motor and system sizes while the 20% Fig. 11. Motor starting H 0S curve for S = 10 MVA.
voltage drop amount is not violated. With the above background
introduction, the development of the voltage sag chart can be
described as follows. First, we know that for a given system
short-circuit level at the PCC, we can use (8) to calculate
the voltage drop amount of the PCC caused by motor
starting

(8)

where is the function defined in (7). Equations (8) shows that


each motor size is related to a value of if is
known. Since, from the previous explanation, we have

(9)

thus, we can get a motor size range from (8).


is the motor size causing and is the motor
size causing . Fig. 12. Impact of inertia constant on motor starting time.
Then, for each motor size within the range ,a
boundary motor inertia constant can be calculated from the
following equations by setting as 10 seconds: boundary value for , and is the boundary value for
. A boundary curve shown in Fig. 11 can then be plotted
for with a given value. When the system
(10) short-circuit level is changed, different curves can
be plotted. However, further study shows that these curves can
be unified if the x-axis in Fig. 11 is expressed as the ratio of
where is the motor starting time or the voltage sag duration,
. Then, a generalized curve like the one shown in Fig. 3
is the electromagnetic torque, is the mechanical torque of
can be drawn for motor starting voltage sag assessment.
the load, is the electric rotor speed, and is its steady-state
The largest motor starting time of 10 seconds is used to get
value. The torques are expressed in the per unit system with the
the boundary value. The meaning of this boundary value
motor size as the base system capacity. The mechanical torque
is that if a motor has inertia constant larger than the boundary
usually has the following form:
value when and are known, the motor starting time
will be over 10 seconds. This duration will result in the motor
(11) starting event being located in the No Damage Region of the
ITIC curve. The voltage sag problem will then occur. In Fig. 12,
where is the coefficient for the load torque which points C, D, E cause the same voltage sag magnitude 0.85 pu
changes with the rotor speed during the motor starting process because they have the same values of and
and reaches the rated motor torque at steady state [22]. is . However, they have different values. Point D is related
determined by . From (10), we know that the motor starting to the boundary value. The inertia constant value at point C is
time is proportional to once the motor size is decided. smaller than the boundary value, thus, it is in the safe region.
Based on (11), a motor inertia constant range can Point E has an inertia constant value larger than the boundary
be obtained for the motor size range . is the value, consequently, point E is not allowed for motor starting.
WANG et al.: PRACTICAL PQ CHARTS FOR MOTOR STARTING ASSESSMENT 805

V. DEVELOPMENT OF THE VOLTAGE FLICKER CHART


Motor starting can occur once per hour as well as several
times per week. is calculated every 10 minutes. As a re-
sult, IEC has suggested an analytical method in which a “shape
factor ” is defined for motor starting voltage characteristics
[23]. With the shape factor definition, the motor starting flicker
can be calculated by using the following procedure. The an-
alytical calculation equation recommended by IEC is shown
in (12)

(12)

where is the sum of the flicker impression times. If we


assume that the motor starting voltage drop amount is the same
for all the motor starts, the total flicker impression time can be
expressed as follows:

(13)

where is the time of motor starting within the assessment time


period . is calculated as follows [23]:

(14)

where is the maximum relative voltage change (the voltage


drop amount) which is expressed as a percentage of the nom-
inal voltage. Equation (14) is defined by IEC. For motor starting
without special mitigation methods for inrush current reduc-
tion, the shape factor is normally about 1, as recommended in
[23]. From (12)–(14) the relationship between the motor starting
times and the voltage drop amount can be obtained Fig. 13. Simulation verification of the voltage drop chart. (a) Voltage drop chart
( = 3; = 6:8; = 6%; k = 5:5; cos ' = 0:3). (b) Motor starting
by simulation waveforms.

(15)
VI. VALIDATION RESULTS
In the IEC standards, should be smaller than the planning The section presents the EMT simulation results executed in
level 0.9 in MV system and the evaluation time for is 10 PSCAD/EMTDC to verify the accuracy and limitations of the
min. With these two conditions, the boundary flicker curve with proposed power quality charts for motor starting. The real case
, shown in Fig. 4(a), can be plotted based on (15). shown in Fig. 1 is employed to run the simulation. The field data
Similarly, the value of can also be calculated by using (12) of the distribution system are listed in Table I of Appendix A
by replacing the evaluation time segment with 2 hours and the selected motor data [24] are shown in Table II of Ap-
pendix C. The comparisons are summarized as follows.
(16)
A. Simulation Results for the Voltage Drop Chart

Then, (15) will be changed as follows for the flicker curve: In Fig. 13(a), the following four cases are analyzed with the
voltage drop chart:
Case 1 (1500 hp); ;
(17) Case 2 (500 hp); ;
Case 3 (100 hp); ;
The planning level limit for is suggested as 0.7 by IEC Case 4 (500 hp); .
[23]. The flicker curve developed from (17) is shown in Fig. The parameters used to plot the chart are 3, 6.8,
4(b) where . When the maximum voltage drop amount , 5.5, and 0.3. From Fig. 13(a) one
is determined by the flicker curves, the maximum motor size can see that Case 1 and Case 2 are in the region with PQ
related to this voltage drop amount can be checked from the concern whereas Case 3 and Case 4 are in the region without
flicker chart. PQ concern. The detailed motor starting situation for the four
806 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 2, APRIL 2011

Fig. 14. Voltage sag chart determined by repetitive EMT simulations and by
the proposed formulas ( = 10; cos ' = 0:2; = 1:2; = 5%).

cases are simulated respectively and the simulation results are


displayed in Fig. 13(b). In the simulations, the motor starting
instant is 1 s and the 25 kV/4.16 kV transformer capacity
is changed to maintain 6.8 for the different cases. The
distribution system line impedances are also changed when
is increased from 28 MVA to 56 MVA; however, is always
kept as 3 in order to assure the same conditions in Fig. 13(a)
and (b). Fig. 13(b) reveals that the PCC voltage for Case 1 and
Case 2 is below 0.95 pu during the motor starting, whereas it
is above 0.95 pu for Case 3 and Case 4. Thus, the voltage drop
chart has successfully predicted the motor starting impact of
the illustrated cases.
In order to further validate the voltage drop chart, Fig. 14
Fig. 15. Simulation verification of the voltage sag chart. (a) Voltage sag chart
( = 3; = 6:8; = 6%; k = 5:5; cos ' = 0:3). (b) Motor starting
shows the curve behavior for a variation of . In this figure, the
curves determined by the proposed formulas are compared to simulation waveforms.
the curves obtained by repetitive EMT simulations done with
PSCAD/EMTDC. As one can see the results obtained with the
proposed method are very accurate. Similar results are also ob- Step 7) Run a direct motor starting simulation by using
tained for the other sensitivity analysis presented in Part B of PSCAD/EMTDC
Section III. In the EMT simulations, the induction motor is rep- • If
resented by the traditional squirrel cage model, the transformer Do
by the T-model and the equivalent system by a voltage source Go to Step 6
behind an impedance. The algorithm used to trace the curve by • If
repetitive EMT simulations is as follows: Store the points
Step 1) Set , , and ; Do
Step 2) Set (step of motor capability) and (step Go to Step 4.
of system short-circuit level);
Step 3) Do short-circuit level under anal-
B. Simulation Results for the Voltage Sag Chart
ysis;
Step 4) If short-circuit level under analysis Fig. 15(a) shows the voltage sag chart based on the parame-
plot the points ters set in Fig. 13(a). Point C and point D in Fig. 15(a) are all
end; related to Case 1 in Part A of Section VI. The only difference
Step 5) Do motor capability under anal- between the two points is that for point C and
ysis; for point D. From Fig. 15(a) one can see that point C is in the
Step 6) Set: region without PQ concern and point D is in the region with PQ
and using (1) and (2) (system parameters) concern. This observation can be validated by the EMT simu-
using (3) (transformer parameter) lation results shown in Fig. 15(b) where the motor starting time
and using (4) and (5) is 3.2 s for and is 14 s for . The voltage
, and drop amount is the same (around 17%) for the two points. Ac-
(motor parameters); cording to the ITIC curve displayed in Fig. 10, the case
WANG et al.: PRACTICAL PQ CHARTS FOR MOTOR STARTING ASSESSMENT 807

TABLE I
DISTRIBUTION SYSTEM PARAMETERS

at the PCC. The analysis of this problem usually is done by


using electromagnetic transient simulations, which is a very
time-consuming process and requires elaborated data. Thus,
three power quality charts were proposed in this paper to
provide practical guidelines for motor starting assessment. The
developed charts can be used to fast determine if a motor is
permitted to be connected to the PCC based on the voltage drop
amount criterion defined by the utilities as well as the ITIC
curve and the IEC flicker standard. The proposed three charts,
i.e., the voltage drop, the voltage sag and the flicker charts, were
applied to several real cases and no case related to power quality
Fig. 16. Simulation verification of the voltage flicker chart. (a) Motor starting
issues was classified as power quality free. Due to the lack
waveform. (b) Comparison of P (T = 100 ms; T = 100 ms; F = 0:8). of space, these cases were not included in the paper; instead,
we have decided to include only simple examples in order
to facilitate the understanding of the proposed method. The
is in the No Interruption in Function Region (without PQ con- results of these several cases showed that the proposed charts
cern) and the case is in the No Damage Region (with can be applied with confidence to separate the cases where the
PQ concern). As a result, the conclusions from Fig. 15(a) are power quality is not a concern, not demanding further analysis,
confirmed in Fig. 15(b). It is worth noting that the range and from the cases where the power quality may be a concern and
the boundary values (point A and point B) in Fig. 15(a) are dif- more detailed investigation must be conducted. Therefore, the
ferent from those in Fig. 3 due to the change of the parameters usage of these charts can significantly reduce the time spent by
, , , , and . engineers when analyzing the installation of a new induction
motor. The examples illustrated that the application of the
C. Simulation Results for the Voltage Flicker Chart guideline charts is straightforward and based on them one
From Section V, we know that the proposed voltage flicker can know how the results may be interpreted. The sensitivity
chart was developed based on (12)–(17); consequently, the studies presented in Section III-B also showed which are the
accuracy of (12)–(17) determines the validation of the proposed main factors affecting the impact of the motor starting process
voltage flicker chart. In this section, the analytical motor starting on the power quality issues. The analyzed factors were: feeder
flicker assessment method is verified by using a digital IEC ratio, transformer size, inrush current factor and the initial
flicker meter set up in Matlab/Simulink. Fig. 16(a) shows the motor power factor. The accuracy of the proposed charts was
motor starting waveform adopted by the analytical assessment also verified by motor starting simulations in PSCAD/EMTDC
method. Three main parameters, which are , (front time), and the IEC flicker meter in Matlab/Simulink.
and (tail time), are used to determine the shape factor of the
waveform [25]. Fig. 16(b) shows the comparison result of the APPENDIX A
values obtained from the analytical method and the simulation
Table I lists the parameters of the distribution system shown
method when is varied. In the analytical method,
in Fig. 1.
is determined by and according
to Fig. 7 of [25]. A digital IEC flicker meter [19] is designed in
Matlab/Simulink to run measure the of the motor starting APPENDIX B
waveform shown in Fig. 16(a). The motor starting frequency is This section presents the development procedure of the
once per minute. From Fig. 16(b) one can see the analytical voltage drop amount equation shown in Section III. From Fig. 5
result and the simulation result match well. the voltage at the PCC can be derived as

VII. CONCLUSIONS
(18)
Induction motor starting draws high inrush current from
the system, which may result in an unacceptable voltage drop
808 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 2, APRIL 2011

TABLE II [12] X. Yang and M. Kratz, “Power system flicker analysis by RMS voltage
THREE-PHASE MOTOR PARAMETERS (4.16 kV) values and numeric flicker meter emulation,” IEEE Trans. Power Del.,
vol. 24, no. 3, pp. 1310–1318, Jul. 2009.
[13] X. Yang and J. Gauthier, “How can flicker level be determined before a
customer is connected to the electric grid,” in Proc. IEEE Power Energy
Soc. Gen. Meeting, Calgary, AB, Canada, 2009, pp. 1–6.
[14] A. Polycarpou and H. Nouri, “Validation of a proposed voltage sag
prediction methodology for interconnected systems during motor
starting,” in Proc. 44th Int. Universities Power Engineering Conf.,
Glasgow, U.K., 2009, pp. 1–5.
[15] J. C. Gomez and M. M. Morcos, “Voltage sag effects on sensitive equip-
ment due to starting cycles of induction motor,” IEEE Power Eng. Rev.,
vol. 22, no. 8, pp. 51–52, Aug. 2002.
[16] J. C. Gomez and M. M. Morcos, “Voltage sag and recovery time
The equivalent system parameters can be calculated by in repetitive events,” IEEE Trans. Power Del., vol. 17, no. 4, pp.
1037–1043, Oct. 2002.
(19) [17] IEEE Recommended Practice for Electric Power Distribution for In-
dustrial Plants, IEEE Std. 141-1993 (Revision of IEEE Std. 141-1986),
1993.
(20) [18] “1C.5.1—Voltage Fluctuation and Light Flicker, PacifiCorp Engi-
neering Handbook,” [Online]. Available: www.rockymtnpower.net/
File/File57576.pdf
Substituting and in (18) results in the following equation: [19] Flickermeter Functional and Design Specifications, IEC Std.
61000-4-15, 2003.
[20] Distribution Point-of-Delivery Interconnection Process Guideline-
Standards of Service, Alberta Electric System Operator. [Online].
(21) Available: http://www.aeso.ca/files/FINALStandardsofServiceRevi-
sion0.pdf
There are two solutions for the above equation. One is expressed [21] Motors and Generators. VA: National Electrical Manufacturers As-
sociation MG1, 2006.
by (7) and the other is (22). However, (22) will get a negative [22] P. Kundur, Power System Stability and Control. New York: McGraw-
value because , , and . Thus, only (7) is Hill, 1994.
considered in the analysis [23] Assessment of Emission Limits for Fluctuating Loads in MV and HV
Power Systems—Basic EMC Publication, IEC Std. 1000-3-7, 1996.
[24] G. S. Grewal, S. Pocsai, and M. M. Hakim, “Transient motor reaccel-
(22) eration study in an integrated petrochemical facility,” IEEE Trans. Ind.
Appl., vol. 35, no. 4, pp. 968–977, Jul./Aug. 1999.
[25] Limitation of Voltage Fluctuations and Flicker in Low-Voltage Supply
APPENDIX C 
Systems for Equipment With Rated Current 16 A—Basic EMC Pub-
lication, IEC Std. 1000-3-3, 1994.
Table II lists the motor parameters used in the simulations.

REFERENCES Xiaoyu Wang (M’08) received the B.Sc. and M.Sc. degrees in electrical engi-
[1] M. H. J. Bollen, Understanding Power Quality Problems: Voltage Sags neering from Tsinghua University, Beijing, China, in 2000 and 2003, respec-
and Interruptions. New York: IEEE Press, 1999. tively, and the Ph.D. degree in electrical and computer engineering from the
[2] M. F. McGranaghan, D. R. Mueller, and M. J. Samotyj, “Voltage University of Alberta, Edmonton, AB, Canada, in 2008.
sags in industrial systems,” IEEE Trans. Ind. Appl., vol. 29, no. 2, pp. Currently, he is an Assistant Researcher at Tsinghua University. His research
397–403, Mar./Apr. 1993. interests include distributed generation and power quality.
[3] J. Lamoree, D. Mueller, P. Vinett, W. Jones, and M. Samotyj, “Voltage
sags analysis case studies,” IEEE Trans. Ind. Appl., vol. 30, no. 4, pp.
1083–1089, Jul. 1994.
[4] J. C. Gomez, C. Reineri, G. Campetelli, and M. M. Morcos, “A study Jing Yong (M’08) received the B.Sc., M.Sc., and Ph.D. degrees in electrical
of voltage sags generated by induction motor starting,” Elect. Power engineering from Chongqing University, Chongqing, China, in 1985, 1988, and
Compon. Syst., vol. 32, no. 6, pp. 645–653, Jun. 2004. 2007, respectively.
[5] C. Hsu, H. Chuang, and C. Chen, “Power quality assessment of large She has been a Postdoctoral Fellow at the University of Alberta since 2008.
motor starting and loading for the integrated steel-making cogeneration Her current interest is power quality.
facility,” IEEE Trans. Ind. Appl., vol. 43, no. 2, pp. 395–402, Mar. 2007.
[6] X. Liang and O. Ilochonwu, “Induction motor starting in practical in-
dustrial applications,” in Proc. IEEE Industrial and Commercial Power
Systems Technical Conf., Tallahassee, FL, 2010, pp. 1–10. Wilsun Xu (M’90–SM’95–F’05) received the Ph.D. degree from the University
[7] R. F. McElveen and M. K. Tony, “Starting high-inertia loads,” IEEE of British Columbia, Vancouver, BC, Canada, in 1989.
Trans. Ind. Appl., vol. 37, no. 1, pp. 137–144, Jan./Feb. 2001. He was an Engineer with BC Hydro from 1990 to 1996. Currently, he is a
[8] G. Lee, M. M. Albu, and G. Heydt, “A power quality index based on Professor and an NSERC/iCORE Industrial Research Chair at the University of
equipment sensitivity, cost, and network vulnerability,” IEEE Trans. Alberta, Edmonton, AB, Canada. His research interests are power quality and
Power Del., vol. 19, no. 3, pp. 1504–1510, Jul. 2004. harmonics.
[9] ITI (CBEMA) Curve Application Notes. Washington, DC: Inf. Tech.
Ind. Council, 2000.
[10] S. M. Halpin, R. Bergeron, T. M. Blooming, R. F. Burch, L. E. Conrad,
and T. S. Key, “Voltage and lamp flicker issues: Should the IEEE Walmir Freitas (M’02) received the Ph.D. degree in electrical engineering from
adopt the IEC approach?,” IEEE Trans. Power Del., vol. 18, no. 3, pp. the University of Campinas, Campinas, Brazil, in 2001.
1088–1097, Jul. 2003. From 2002 to 2003, he was a Postdoctoral Fellow with the University of Al-
[11] S. M. Halpin and R. F. Burch, “An improved simulation approach for berta, Edmonton, AB, Canada. Currently, he is an Associate Professor with the
the analysis of voltage flicker and the evaluation of mitigation strate- University of Campinas, Campinas, Brazil. His research interests are the anal-
gies,” IEEE Trans. Power Del., vol. 12, no. 3, pp. 1285–1291, Jul. 1997. ysis of distribution systems and distributed generation.

You might also like