Agenda
PresenterBiographies
February2013
DennisStanke,staffapplicationsengineer,Trane
ASHRAEStandard62.1
With a BSME from the University of Wisconsin, Dennis joined Trane in 1973, as a controls
development engineer. He is now a Staff Applications Engineer specializing in airside systems
including controls, ventilation, indoor air quality, and dehumidification. He has written
numerous applications manuals and newsletters, has published many technical articles and
columns, and has appeared in many Trane Engineers Newsletter Live broadcasts.
An ASHRAE Fellow, he currently serves as Chairman for ASHRAE Standard 189.1, Standard
for the Design of High-Performance Green Buildings Except Low-Rise Residential Buildings.
He recently served as Chairman for ASHRAE Standard 62.1, Ventilation for Acceptable Indoor
Air Quality, and he served on the USGBC LEED Technical Advisory Group for Indoor
Environmental Quality (the LEED EQ TAG).
PaulSolberg,applicationsengineer,Trane
A mechanical engineer from the University of Wisconsin at Platteville, Paul is a 33-year
veteran of Trane. He specializes in compressor and refrigeration systems, and has authored
numerous Trane publications on these subjects, including application manuals, engineering
bulletins, and Engineers Newsletters.
Paul served in the technical service and applications engineering areas at various
manufacturing locations, where he developed particular expertise supporting split systems,
small packaged chillers, rooftop air conditioners, and other unitary products.
JohnMurphy,applicationsengineer,Trane
John has been with Trane since 1993. His primary responsibility as an applications engineer is
to aid design engineers and Trane sales personnel in the proper design and application of
HVAC systems. As a LEED Accredited Professional, he has helped our customers and local
offices on a wide range of LEED projects. His main areas of expertise include energy
efficiency, dehumidification, dedicated outdoor-air systems, air-to-air energy recovery,
psychrometry, and ventilation.
John is the author of numerous Trane application manuals and Engineers Newsletters, and is
a frequent presenter on Tranes Engineers Newsletter Live series. He also is a member of
ASHRAE, has authored several articles for the ASHRAE Journal, and has been a member of
ASHRAEs Moisture Management in Buildings and Mechanical Dehumidifiers technical
committees. He was a contributing author of the Advanced Energy Design Guide for K-12
Schools and the Advanced Energy Design Guide for Small Hospitals and Health Care
Facilities, a technical reviewer for the ASHRAE Guide for Buildings in Hot and Humid
Climates, and a presenter on the 2012 ASHRAE Dedicated Outdoor Air Systems webcast.
Bibliography
February2013
IndustryStandards
ASHAREStandard62.1
AmericanSocietyofHeating,Refrigerating,andAirConditioningEngineers(ASHRAE).
ANSI/ASHRAEStandard62.12010:VentilationforAcceptableIndoorAirQuality.
Availableatwww.ashrae.org/bookstore
AmericanSocietyofHeating,RefrigeratingandAirConditioningEngineers,Inc.(ASHRAE).
Standard62.12010UsersManual.Availableatwww.ashrae.org/bookstore
IndustryArticles
Stanke,D.Addendum62n:SingleZoneandDedicatedOASystems.ASHRAEJournal
(October2004):1221.Availableatwww.trane.com/articles
Stanke,D.Standard622001Addendum62n:VentilationforChangeoverBypassVAV
Systems.ASHRAEJournal(November2004):2232.Availableatwww.trane.com/articles
Stanke,D.Addendum62n:SinglePathMultipleZoneSystemDesign.ASHRAEJournal
(January2005):2835.Availableatwww.trane.com/articles
Stanke,D.Standard62.12004:DesigningDualPath,MultipleZoneSystems.ASHRAE
Journal(May2005):2030.Availableatwww.trane.com/articles
Stanke,D.Standard62.12004SystemOperation:DynamicResetOptions.ASHRAE
Journal(December2006):1832.Availableatwww.trane.com/articles
Stanke,D.DynamicResetforMultipleZoneSystems.ASHRAEJournal(March2010):22
35.Availableatwww.trane.com/articles
TranePublicationsandBroadcasts
Murphy.J.andB.Bradley.CO2BasedDemandControlledVentilationwithASHRAE
Standard62.12004.EngineersNewsletter345(2005).Availablefrom
www.trane.com/engineersnewsletter
Stanke,D.andB.Bradley.ASHRAE62nBreathesNewLifeintoASHRAEStandard62.
EngineersNewsletter331(2004).Availablefromwww.trane.com/engineersnewsletter
Stanke,D.andJ.Harshaw.PotentialASHRAEStandardConflicts:IndoorAirQualityand
EnergyStandards.EngineersNewsletter374(2008).Availablefrom
www.trane.com/engineersnewsletter
Stanke,D.andJ.Harshaw.MinimumOutdoorAirflowUsingtheIAQProcedure.
EngineersNewsletter403(2011).Availablefromwww.trane.com/engineersnewsletter
Trane.CO2BasedDemandControlledVentilation.EngineersNewsletterLivebroadcast
(2005),APPCMC024EN(DVD).Availablefromwww.trane.com/ENL
Trane.ASHRAEStandards62.1and90.1,andVAVSystems.EngineersNewsletterLive
broadcast(2008),APPCMC034EN(DVD).Availablefromwww.trane.com/ENL
AnalysisSoftware
TraneAirConditioningandEconomics(TRACE700).Availableatwww.trane.com/TRACE
Ingersoll Rand
1.5
Copyrighted Materials
This presentation is protected by U.S. and international
copyright laws. Reproduction, distribution, display, and
use of the presentation without written permission of
Trane is prohibited.
2013 Trane, a business of Ingersoll-Rand. All rights reserved.
learning objectives
Todays Presenters
Dennis Stanke
Paul Solberg
John Murphy
Applications
Engineer
Applications
Engineer
Applications
Engineer
Agenda
Overview of ASHRAE Standard 62.1
Ventilation Rate Procedure
Zone calculations
System calculations
Exhaust ventilation
Dynamic reset strategies
Agenda
Overview of ASHRAE Standard 62.1
Ventilation Rate Procedure
Zone calculations
System calculations
Exhaust ventilation
Dynamic reset strategies
10
Purpose
Scope
Definitions
Outdoor air quality
Systems and equipment
Procedures
Construction and system start-up
Operations and maintenance
Multiple-zone systems
Standard 62.1
ASHRAE
Standards
Energy Label
IgCC
189.1
ENERGY STAR
62.1
bEQ
IMC
UMC
Sec 4, 5
Sec 6
Local Codes
Sec 7
Building Rating
LEED EQp1
Sec 8
12
Standard 62.1
Sections 4 - 8
IMC, UMC
IgCC
Sections 4 - 8
LEED certification
Sections 4 - 7
13
Table of Contents
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
App A
14
Purpose
Scope
Definitions
Outdoor air quality
Systems and equipment
Procedures
Construction and system start-up
Operations and maintenance
Multiple-zone systems
10
Section 6.0
Procedures
6.1
6.2
6.3
6.4
6.5
6.6
15
General
Ventilation rate procedure
Indoor air quality (IAQ) procedure
Natural ventilation procedure
Exhaust ventilation
Documentation
Section 6.2
16
Prescribed
equations
Zone and
intake OA
rates
11
Section 6.3
Sources
Source strength
Target levels
Mass balance
Contaminants
2
Contaminant
based zone
& intake OA
Larger of
4
Air cleaning
17
Subjective
zone &
intake OA
Subjective
evaluation
3
Similar
zone
Section 6.4
12
Section 6.2
12/2010
20
13
04/2011
21
Ozone
0.107 ppm
Nonattainment areas are indicated by color.
When only a portion of a county is shown in
color, it indicates that only that part of the
county is within a nonattainment area boundary.
22
07/2012
14
Section 6.2.1
References
PM2.5
http://www.epa.gov/oar/oaqps/greenbk/rindex.html
http://www.epa.gov/oar/oaqps/greenbk/mappm25_2006.html
PM10
http://www.epa.gov/oar/oaqps/greenbk/pindex.html
http://www.epa.gov/oar/oaqps/greenbk/mappm10.html
Ozone
http://www.epa.gov/oar/oaqps/greenbk/hindex.html
http://www.epa.gov/oar/oaqps/greenbk/map8hr_2008.html
23
Agenda
Overview of ASHRAE Standard 62.1
Ventilation Rate Procedure
Zone calculations
System calculations
Exhaust ventilation
Dynamic reset strategies
24
15
Section 6.2
System calculations
Calculate outdoor-air intake flow for the entire system,
based on prescribed calculation procedures
25
Section 6.2.2
Zone Calculations
1. Calculate outdoor airflow to the breathing zone,
16
Rp
Ra
cfm/p
cfm/ft
5.0
0.06
10.0
0.12
Lecture classroom
7.5
0.06
Retail sales
7.5
0.12
Auditorium
5.0
0.06
Religious Worship
5.0
0.06
Motel room
5.0
0.06
Office
Classroom (ages 5-8)
27
Section 6.2.2
Zone Calculations
1. Calculate outdoor airflow to the breathing zone,
17
Section 6.2.2
Zone Calculations
1. Calculate outdoor airflow to the breathing zone,
29
Rp
Ra
Pz
Az
Vbz
=
=
=
=
RpPz + RaAz
55
+ 0.061000
25 cfm + 60 cfm
85 cfm
Vbz
85 cfm
breathing zone
30
18
Vbz
=
=
=
=
RpPz + RaAz
517
+ 0.061000
85 cfm + 60 cfm
145 cfm
Vbz
145 cfm
breathing zone
31
Section 6.2.2
Zone Calculations
1. Calculate outdoor airflow to the breathing zone,
19
Supply
Return
SA temperature
Ez
Ceiling
Ceiling or floor
Cool
1.0
Ceiling
Floor
Warm
1.0
Ceiling
Ceiling
1.0
Ceiling
Ceiling
0.8
Floor
Ceiling
1.0
Floor
Ceiling
Cool (displacement)
1.2
Floor
Ceiling
Warm
0.7
Floor
Floor
Warm
1.0
0.8
0.5
33
Section 6.2.2
Zone Calculations
1. Calculate outdoor airflow to the breathing zone,
20
= 85/1.0
= 85 cfm
85 cfm
Voz
85 cfm
0 cfm
Vbz
85 cfm
breathing zone
35
= 85/0.8
= 106 cfm
106 cfm
Voz
106 cfm
21 cfm
Vbz
85 cfm
breathing zone
36
21
Supply
Return
SA temperature
Ez
Voz
Ceiling
Ceiling or floor
Cool
1.0
85
Ceiling
Floor
Warm
1.0
85
Ceiling
Ceiling
1.0
85
Ceiling
Ceiling
0.8
106
Floor
Ceiling
1.0
85
Floor
Ceiling
Cool (displacement)
1.2
71
Floor
Ceiling
Warm
0.7
121
Floor
Floor
Warm
1.0
85
0.8
106
0.5
170
37
Agenda
Overview of ASHRAE Standard 62.1
Ventilation Rate Procedure
Zone calculations
System calculations
38
22
Section 6.2
System calculations
Calculate outdoor-air intake flow for the entire system,
based on prescribed calculation procedures
39
Section 6.2
40
23
Single-Zone System
One air handler brings in OA through one intake
and distributes it to a single zone
OA
RA
EA
SA
RA
zone
41
zone 1
RA
42
CA
SA
zone 2
RA
CA
SA
zone 3
RA
24
EA
RA
RA
PA
zone 1
43
RA
PA
zone 2
PA
zone 3
example
zone 1
Voz = 300
44
zone 2
Voz = 400
zone 3
Voz = 500
25
Section 6.2.3
Single-Zone System
Find the required outdoor-air intake flow for the system (Vot):
Vot = Voz
OA
OA
RA
EA
SA
OA
RA
SA
RA
zone 1
Voz = 300
45
RA
RA
SA
zone 2
Voz = 400
RA
zone 3
Voz = 500
Section 6.2.4
100% OA System
Find the required outdoor-air intake flow for the system (Vot):
Vot = Voz
OA Vot = 1200 cfm
EA
CA
= 300 + 400 + 500
= 1200 cfm
SA
zone 1
Voz = 300
RA
46
CA
SA
zone 2
Voz = 400
RA
CA
SA
zone 3
Voz = 500
RA
26
Section 6.2.5
EA
RA
PA
RA
zone 1
OVERVENTILATED
47
PA
RA
zone 2
PROPERLY
VENTILATED
PA
RA
zone 3
OVERVENTILATED
48
27
section 6.2.5
Multiple-Zone Recirculating
1. Zone outdoor air fraction (Zpz)
2. Uncorrected outdoor air intake (Vou)
3. System ventilation efficiency (Ev)
Default Ev method (Table 6-3)
Calculated Ev method (Appendix A)
4. System outdoor air intake (Vot)
49
example
OA
EA
RA
VAV
PA
50
VAV
RA
PA
VAV
RA
PA
RA
zone 1
zone 2
zone 3
Voz
Voz
Voz
= 300
= 400
= 500
28
section 6.2.5
Multiple-Zone Recirculating
1. Zone outdoor air fraction (Zpz)
2. Uncorrected outdoor air intake (Vou)
3. System ventilation efficiency (Ev)
Default Ev method (Table 6-3)
Calculated Ev method (Appendix A)
4. System outdoor air intake (Vot)
51
RA
VAV
PA
RA
zone 1
Vpz
= 2600
Voz
52
= 300
VAV
PA
RA
zone 2
Vpz
= 3400
Voz
= 400
VAV
PA
RA
zone 3
Vpz
= 4000
Voz
= 500
29
53
RA
VAV
PA
zone
Vpz
Vpzm
Voz
Zpz
54
VAV
RA
1
=
=
=
=
2600
650
300
0.46
PA
zone
Vpz
Vpzm
Voz
Zpz
VAV
RA
2
=
=
=
=
3400
850
400
0.47
PA
zone
Vpz
Vpzm
Voz
Zpz
RA
3
=
=
=
=
4000
1000
500
0.50
30
Section 6.2.5
Multiple-Zone Recirculating
1. Zone outdoor air fraction (Zpz)
2. Uncorrected outdoor air intake (Vou)
3. System ventilation efficiency (Ev)
Default Ev method (Table 6-3)
Calculated Ev method (Appendix A)
4. System outdoor air intake (Vot)
55
(Ra Az)
D = Ps / P z
where,
D
= occupant diversity
Ps
31
example
Occupant Diversity
D = Ps / Pz
= 80/120
= 0.66
OA
EA
RA
PA
PA
RA
zone 1
Pz = 30
Pz = 120
RA
zone 2
Pz = 40
PA
RA
zone 3
Pz = 50
Ps = 80 people
57
Rp Pz
5 30 = 150
5 40 = 200
5 50 = 250
R a Az
0.06 2500 = 150
0.06 3340 = 200
0.06 4170 = 250
(Ra Az) = 600 cfm
32
section 6.2.5
Multiple-Zone Recirculating
1. Zone outdoor air fraction (Zpz)
2. Uncorrected outdoor air intake (Vou)
3. System ventilation efficiency (Ev)
Default Ev method (Table 6-3)
Calculated Ev method (Appendix A)
4. System outdoor air intake (Vot)
59
Appendix A
3b.
Evz = 1 + Xs Zpz
for secondary recirculation systems:
3c.
60
33
61
OA
EA
RA
VAV
PA
62
VAV
RA
zone 1
Vpz
= 2600
PA
VAV
RA
zone 2
Vpz
= 3400
PA
RA
zone 3
Vpz
= 4000
34
63
Appendix A
3b.
Evz = 1 + Xs Zpz
for secondary recirculation systems:
3c.
64
35
multiple-zone recirculating
Single-Supply System
All air supplied to each zone is a mixture of outdoor
air and system-level (centralized) recirculated air
65
OA
RA
EA
RA
PA
zone 1
VAV
VAV
VAV
RA
PA
RA
zone 2
PA
zone 3
66
36
multiple-zone recirculating
67
OA
RA
EA
RA
RA
RA
SFPVAV
SA
zone 1
RA
RA
SFPVAV
SA
zone 2
RA
SFPVAV
SA
zone 3
68
37
OA cooling AHU
RA
EA
SA
DDVAV
DDVAV
DDVAV
RA
RA
zone 1
SA
RA
zone 2
SA
zone 3
69
appendix A
3b.
Evz = 1 + Xs Zpz
for secondary recirculation systems:
3c.
70
38
71
zone
Xs
Zpz
Evz
1
2
3
0.17
0.17
0.17
0.46
0.47
0.50
0.71
0.70
0.67
72
zone
Xs
Zpz
Evz
1
2
3
0.17
0.17
0.17
0.46
0.47
0.50
0.71
0.70
0.67
39
section 6.2.5
Multiple-Zone Recirculating
1. Zone outdoor air fraction (Zpz)
2. Uncorrected outdoor air intake (Vou)
3. System ventilation efficiency (Ev)
Default Ev method (Table 6-3)
Calculated Ev method (Appendix A)
4. System outdoor air intake (Vot)
73
= Vou / Ev
= 1000 / 0.67
= 1490 cfm
OA
EA
RA
VAV
PA
VAV
RA
zone 1
Voz = 300
74
PA
VAV
RA
zone 2
Voz = 400
PA
RA
zone 3
Voz = 500
40
Section 6.2.5
Multiple-Zone Recirculating
1. Zone outdoor air fraction (Zpz)
2. Uncorrected outdoor air intake (Vou)
3. System ventilation efficiency (Ev)
Default Ev method (Table 6-3)
Calculated Ev method (Appendix A)
4. System outdoor air intake (Vot)
75
76
0.50
max Zpz
Ev
0.15
1.0
0.25
0.9
0.35
0.8
0.45
0.7
0.55
0.6
> 0.55
Appendix A
0.65
41
= Vou / Ev
= 1000 / 0.65
= 1540 cfm
OA
EA
RA
VAV
PA
VAV
PA
RA
zone 1
Voz = 300
77
VAV
RA
zone 2
Voz = 400
PA
RA
zone 3
Voz = 500
Ev
Vot
Table 6-3
0.65
1540
Appendix A
0.67
1490
78
42
Mode (Ez)
Zpz
Ev
Vot
0.50
0.67
1490
Heating (0.8)
0.63
0.77
1300
79
80
43
81
Comparison of Results
ventilation system
Vot
Ev
single zone
1200
1200
single-path VAV
1490
0.67
series FPVAV
1180
0.85
82
19%1.00
lower Vot than VAV
44
100% OA System
Ev = Vou / Vot
= 1000 / 1200
= 0.83
EA
CA
= 300 + 400 + 500
= 1200 cfm
CA
zone 1
Voz = 300
SA
SA
RA
83
CA
zone 2
Voz = 400
zone 3
Voz = 500
SA
RA
RA
Single-Zone System
Ev = Vou / Vot
= 1000 / 1200
= 0.83
SA
OA
RA
EA
OA
RA
RA
zone 1
Voz = 300
Vou = 300
Ev = 1.0
84
SA
RA
RA
zone 2
Voz = 400
Vou = 400
Ev = 1.0
SA
RA
zone 3
Voz = 500
Vou = 500
Ev = 1.0
45
Comparison of Results
Vot
Ev
single zone
1200
0.83
1200
0.83
single-path VAV
1490
0.67
series FPVAV
1180
0.85
ventilation system
85
Agenda
Overview of ASHRAE Standard 62.1
Ventilation Rate Procedure
Zone calculations
System calculations
Exhaust ventilation
Dynamic reset strategies
86
46
Section 6.0
Procedures
6.1
6.2
6.3
6.4
6.5
6.6
87
General
Ventilation rate procedure
Indoor air quality (IAQ) procedure
Natural ventilation procedure
Exhaust ventilation
Documentation
0.70
0.60
0.50
Kitchenettes
0.30
Locker/dressing rooms
0.25
Toilets public
(heavy use areas)
88
cfm/ft2
50 cfm/unit
70 cfm/unit
47
Section 6.5
Exhaust Ventilation
To ensure removal of local contaminants, some
zones require exhaust rates (Table 6-4)
the requirements for exhaust ventilation in
Section 6.5 shall be met regardless of the method used
to determine minimum outdoor airflow rates.
(Section 6.1)
Agenda
Overview of ASHRAE Standard 62.1
Ventilation Rate Procedure
Zone level calculations
System level calculations
Exhaust ventilation
Dynamic reset strategies
90
48
Section 6.2.7
Dynamic Reset
Systems may be designed to reset the outdoor air
intake flow (Vot) and/or zone outdoor airflow (Voz) as
operating conditions change.
Variations in zone population (DCV)
Variations in ventilation efficiency due to changes in
airflow (ventilation reset control)
Variations in intake airflow during economizer cooling
91
92
49
Section 6.2.7.1
93
Section 6.2.7.1
50
DCV
N
= 0.0105 cfm of CO2/person (for office work)
Vbz-est = current breathing-zone OA required, cfm
Pz
= current zone population
95
51
550
Vbz
(cfm)
60
0
97
Section 6.2.7
Dynamic Reset
Systems may be designed to reset the outdoor air
intake flow (Vot) and/or zone outdoor airflow (Voz) as
operating conditions change.
Variations in zone population (DCV)
Variations in ventilation efficiency due to changes in
airflow (ventilation reset control)
Variations in intake airflow during economizer cooling
98
52
Section 6.2.7.2
RA
communicating BAS
Calculate new OA setpoint
per ASHRAE 62
99
Section 6.2.7.2
100
53
101
102
54
103
104
55
106
56
Single-Zone Systems
107
Use VAV controls for all zones and use either population
estimates or CO2-based approaches in DCV zones to find
current intake airflow needed (Vot)
OA
EA
VAV
VAV
CA
VAV
CA
CA
OCC
SA
zone 1
RA
108
SA
zone 2
RA
SA
zone 3
CO2
RA
57
EA
VAV
RA
VAV
PA
RA
VAV
RA
PA
PA
OCC
zone 1
109
zone 2
zone 3
CO2
dynamic reset
Summary
Single-zone systems
No credit for population diversity
Can use zone DCV to meet energy standards
100% OA systems
No credit for population diversity
Constant-airflow systems cannot provide zone DCV
Variable-airflow systems can provide zone DCV, but
require a VAV box at each zone and AHU controls
110
58
dynamic reset
Summary
Multiple-zone systems
Credit for population diversity (D) reduces installed cost
Dynamic reset of OA intake flow is allowed based on:
Ventilation optimization control
Zone DCV combined with ventilation optimization
111
www.trane.com/EN
112
59
www.trane.com/ENL
114
60
115
116
61
Agenda
Supplemental content
Review of Section 4.0 and 5.0 requirements
Design for varying operating conditions
VRP calculations for systems with a secondary
recirculation air path
118
62
Purpose
Scope
Definitions
Outdoor air quality
Systems and equipment
Procedures
Construction and system start-up
Operations and maintenance
Multiple-zone systems
Section 4
63
Section 5.0
121
5.11
5.12
5.13
5.14
5.15
5.16
5.17
Section 5.1
64
Section 5.2
123
Section 5.3
65
Section 5.4
Airstream Surfaces
Use duct materials that resist microbial growth per
UL 181 to reduce space contamination due to air
distribution system
Use duct materials that resist erosion per UL 181
to reduce space contamination due to air distribution
system
Most matte-face finishes meet these requirements
125
Section 5.5
66
127
Distance (ft.)
10
15
30
10
15
15
25
25
15
15
25
Section 5.6
Capture of Contaminants
Reduce recirculation of indoor contaminants, exhaust
locally captured contaminants (e.g., printers) directly
to outdoors
128
67
Section 5.7
Combustion Air
Reduce pollutants from combustion appliances
Provide sufficient combustion air
Provide sufficient air for removal of combustion products
129
Section 5.8
68
Section 5.9
Dehumidification Systems
Reduce dampness in buildings during mechanical
cooling, systems must:
Limit space RH to 65% or less when analyzed at design
dew point condition without solar load
Ensure that design intake exceeds exhaust airflow
Section 5.10
Drain Pans
Ensure condensate drainage without flooding/carryover
Slope drain pan at least 1/8 in. per ft.
Locate drain opening at lowest point of drain pan
Use P-trap or other seal to prevent ingestion of air while
allowing complete drainage with fan on or off
Size drain pan to limit carryover
69
Drain Seals
Section 5.11
134
70
Section 5.12
135
Section 5.13
71
Section 5.14
137
Section 5.15
138
72
Section 5.16
139
Section 5.16
140
73
Section 5.17
141
Agenda
Supplemental content
Review of Section 4.0 and 5.0 requirements
Design for varying operating conditions
VRP calculations for systems with a secondary
recirculation air path
142
74
Section 6.2.6
Short-Term Conditions
May use Equation 6-9 to find averaging time and adjust
design for short-term conditions
T = 3 v / Vbz
where,
v
143
144
Rp Pz + Ra Az
55
+ 0.06 1000
25 cfm + 60 cfm
85 cfm
=
=
=
3 v / Vbz
3 10000 / 85
353 minutes
6 hours
75
16
14
12
Highest Pz
averaged over a
6-hr period (T)
is 3.8 people
10
8
6
4
Pz = 5
2
0
midnight
145
6 a.m.
noon
6 p.m.
midnight
146
Rp Pz + Ra Az
55
+ 0.06 1000
25 cfm + 60 cfm
85 cfm
Rp Pz + Ra Az
5 3.8 + 0.06 1000
19 cfm + 60 cfm
79 cfm
76
147
Rp Pz + Ra Az
5 17 + 0.06 1000
85 cfm + 60 cfm
145 cfm
=
=
=
3 v / Vbz
3 10000 / 145
207 minutes
4 hours
16
Pz = 17
14
Highest Pz
averaged over a
4-hr period (T)
is 9.75 people
12
10
8
6
4
2
0
midnight
148
6 a.m.
noon
6 p.m.
midnight
77
149
Rp Pz + Ra Az
5 17 + 0.06 1000
85 cfm + 60 cfm
145 cfm
Rp Pz + Ra Az
5 9.75+ 0.06 1000
49 cfm + 60 cfm
109 cfm
Agenda
Supplemental content
Review of Section 4.0 and 5.0 requirements
Design for varying operating conditions
VRP calculations for systems with a secondary
recirculation air path
150
78
multiple-zone recirculating
151
OA
RA
EA
RA
RA
RA
SFPVAV
SA
zone 1
RA
RA
SFPVAV
SA
zone 2
RA
SFPVAV
SA
zone 3
152
79
Section 6.2.5
Multiple-Zone Recirculating
1. Zone outdoor air fraction (Zpz)
2. Uncorrected outdoor air intake (Vou)
3. System ventilation efficiency (Ev)
Calculated Ev method (Appendix A)
4. System outdoor air intake (Vot)
153
RA
RA
DA
zone
Vdz
Vpzm
Voz
Zpz
154
1
=
=
=
=
SFPVAV
2600
650
300
0.46
DA
zone
Vdz
Vpzm
Voz
Zpz
RA
2
=
=
=
=
RA
3400
850
400
0.47
DA
zone
Vdz
Vpzm
Voz
Zpz
3
=
=
=
=
4000
1000
500
0.50
80
Section 6.2.5
Multiple-Zone Recirculating
1. Zone outdoor air fraction (Zpz)
2. Uncorrected outdoor air intake (Vou)
3. System ventilation efficiency (Ev)
Calculated Ev method (Appendix A)
4. System outdoor air intake (Vot)
155
Rp Pz
5 30 = 150
5 40 = 200
5 50 = 250
R a Az
0.06 2500 = 150
0.06 3340 = 200
0.06 4170 = 250
(Ra Az) = 600 cfm
81
Appendix A
3b.
Evz = 1 + Xs Zpz
for secondary recirculation systems:
3c.
157
158
82
zone
Xs
Fa
1
2
3
159
0.17
0.17
0.17
Fb
Zpz
Ep
Fc
Evz
0.46
0.47
0.50
160
83
RA
SFPVAV
RA
161
RA
RA
DA
zone 1
Vdz
= 2600
Vpzm = 650
DA
zone 2
= 3400
Vdz
Vpzm = 850
DA
zone 3
= 4000
Vdz
Vpzm = 1000
Ep
Ep
Ep
= 0.25
= 0.25
= 0.25
OA
RA
EA
RA
RA
RA
SFPVAV
SA
RA
RA
SFPVAV
SA
RA
SFPVAV
SA
zone 1
zone 2
zone 3
Er = 0
Er = 0
Er = 0
84
OA
RA
EA
RA
RA
RA
SFPVAV
RA
SA
RA
SFPVAV
RA
SA
SFPVAV
SA
zone 1
zone 2
zone 3
Er = 0.3
Er = 0.5
Er = 0.9
OA cooling AHU
RA
EA
SA
DDVAV
DDVAV
DDVAV
RA
RA
SA
RA
SA
zone 1
zone 2
zone 3
Er = 1.0
Er = 1.0
Er = 1.0
85
165
zone
Ep
Er
Fa
1
2
3
0.25
0.25
0.25
0.3
0.5
0.9
0.48
0.63
0.93
166
zone
Ep
Fb
1
2
3
0.25
0.25
0.25
0.25
0.25
0.25
86
zone
1
2
3
167
Ez
Er
Ep
Fc
1.0
1.0
1.0
0.3
0.5
0.9
0.25
0.25
0.25
1.0
1.0
1.0
zone
1
2
3
168
Ez
Er
Ep
Fc
0.8
0.8
0.8
0.3
0.5
0.9
0.25
0.25
0.25
0.90
0.93
0.99
87
zone
1
2
3
169
Fa
Xs
Fb
Zpz
Ep
Fc
Evz
0.25
0.25
0.25
1.0
1.0
1.0
0.85
0.88
0.91
zone
1
2
3
170
Fa
Xs
Fb
Zpz
Ep
Fc
Evz
0.25
0.25
0.25
1.0
1.0
1.0
0.85
0.88
0.91
88
Section 6.2.5
Multiple-Zone Recirculating
1. Zone outdoor air fraction (Zpz)
2. Uncorrected outdoor air intake (Vou)
3. System ventilation efficiency (Ev)
Calculated Ev method (Appendix A)
4. System outdoor air intake (Vot)
171
= Vou / Ev
= 1000 / 0.85
= 1180 cfm
OA
EA
RA
SFPVAV
RA
DA
RA
zone 1
Voz = 300
172
RA
DA
RA
RA
zone 2
Voz = 400
DA
RA
zone 3
Voz = 500
89
Ev
Vot
Table 6-3
0.65
1540
Appendix A
0.67
1490
Appendix A
0.85
1180
(single-path equations)
(dual-path equations)
173
174
90
175
Az
D
Ev
Ez
Ps
Pz
Ra
Rp
T
v
Vbz
Vot
Vou
Voz
Vpz
Zp
176
91
92