8KV S/S
Project Title: CONSTRUCTION OF MUBARKIYAH 115/13.8KV SUBSTATION IN AL-HASSA
CONTRACTOR: AL SHARIF KEC
National Grid-SA Cont # 4400001840/00
J. O. No.
Dated:
1-1233049.02
Monday, September 15, 2014
Locations
Specified
Minimum lux
Calculated
Minimum lux
Calculated
Calculated
Average lux Maximum lux
200
293
453
576
Toilet
100
100
204
327
200
210
299
402
100
140
146
152
Staircase 1
100
Staircase 2
100
Staircase 3
100
NG-SA Remarks
Source: ISD
Evaluation
ASKEC Response
Not
This room is not available
Acceptable
2 x 100W
2 x 28W
Not
Mt Ht=3.20m
Acceptable
Incandescent lamp is not permitted for
normal lighting
Not
This room is not available
Acceptable
2pcx100W
Not
Mt Ht=3.2m
Acceptable Incandescent lamp is not permitted for
normal lighting
Not
No calculation
Acceptable
Not
No calculation
Acceptable
Not
No calculation
Acceptable
2. DC EMERGENCY LIGHTING
Sr. No#
Locations
Calculated
Max lux
Control Room
10
15
0.29
19
Communication Room
10
11
1.73
16
10
15
13
17
10
11
2.98
15
10
13
9.07
14
Staircase 1
10
NG-SA Remarks
Source: ISD
Evaluation
16x60W AR
Not
Mt Ht=3.2m
Acceptable
Adjust the min to at least 5 lux
1x60W AR
Not
Mt Ht=3.20m
Acceptable
Adjust the min to at least 5 lux
Not
This room is not available
Acceptable
40pcsx60W
Not
Mt Ht=2.35m
Acceptable
Adjust the min to at least 5 lux
Not
This room is not available
Acceptable
Not
No calculation
Acceptable
CONCURRED
ASKEC Response
COMPLIANCE STATEMENT FOR SOE POINT LIST COMMENTS OF MUBARKIYAH 115/13.8KV S/S
Project Title: CONSTRUCTION OF MUBARKIYAH 115/13.8KV SUBSTATION IN AL-HASSA
CONTRACTOR: AL SHARIF KEC
National Grid-SA Cont # 4400001840/00
J. O. No.
Dated:
1-1233049.02
Monday, September 15, 2014
Staircase 2
10
Staircase 3
10
Not
No calculation
Acceptable
Not
No calculation
Acceptable
3. LIGHTING MATERIALS
NG-SA Comments
Sr. No#
Source
ASKEC Response
ASKEC Response
ISD
4. ELECTRICAL DRAWINGS
NG-SA Comments
Sr. No#
Source
1
1.1
Note 5.B, correct PVC conduit to RSG conduit for above suspended ceiling.
1.2
1.2.1
Along grid U, interchange the location of search light and egress lighting.
1.2.2
Along grid 4, add one (1) egress at column S4 and shift egress light from column Q4
to M4 and egress light from column K4 to H4
1.2.3
Along grid 7, shift the egress light to column S7 and provide egress light at column H7
1.2.4
1.2.5
1.3
1.3.1
Along grid A, re-distribute the egress lighting at column A3, A6, A10 and A18.
1.3.2
Along grid D, re-distribute the egress lighting at column D3, D6, D15 and D19.
1.3.3
Change the exit light to double face type over the door to staircase 2.
ISD
ISD
ISD
CONCURRED
COMPLIANCE STATEMENT FOR SOE POINT LIST COMMENTS OF MUBARKIYAH 115/13.8KV S/S
Project Title: CONSTRUCTION OF MUBARKIYAH 115/13.8KV SUBSTATION IN AL-HASSA
CONTRACTOR: AL SHARIF KEC
National Grid-SA Cont # 4400001840/00
J. O. No.
Dated:
1-1233049.02
Monday, September 15, 2014
Along grid 21, shift the lighting switches near the single leaf door.
1.4
1.5
1.6
1.6.1
1.6.2
1.6.3
1.6.4
ISD
See our comments for DC emergency lighting calculations for the following room
Control Room
Communication Room
Cable Entry Room
Staircase 1, 2 & 3.
1.7
1.8
At battery room, shift the lighting switch outside near the door.
1.9
At staircase 2, show in section the method of installing the normal and emergency
lighting fixtures. See Section A of drawing #EA 274686 Sht 3 of 4 Rev B.
ISD
Note: At battery room, shift the Eye/Face Wash near the exit door.. Coordinate with Mechanical design.
NG-SA Comments
Sr. No#
ISD
NG-SA Comments
Sr. No#
ASKEC Response
Source
3
3.1
2
2.1
ASKEC Response
Source
ISD
CONCURRED
COMPLIANCE STATEMENT FOR SOE POINT LIST COMMENTS OF MUBARKIYAH 115/13.8KV S/S
Project Title: CONSTRUCTION OF MUBARKIYAH 115/13.8KV SUBSTATION IN AL-HASSA
CONTRACTOR: AL SHARIF KEC
National Grid-SA Cont # 4400001840/00
J. O. No.
Dated:
1-1233049.02
Monday, September 15, 2014
Sr. No#
4.2
4.3
4.4
4.5
4.6
Raise the cable tray when it is only in two layers for adequate passageway.
4.7
Provide sectional view showing the height of egress lighting against with the lower
cable tray.
NG-SA Comments
Sr. No#
ASKEC Response
Source
ISD
NG-SA Comments
Sr. No#
ASKEC Response
Source
6
6.1
ISD
5
5.1
4
4.1
ASKEC Response
Source
ISD
CONCURRED
COMPLIANCE STATEMENT FOR SOE POINT LIST COMMENTS OF MUBARKIYAH 115/13.8KV S/S
Project Title: CONSTRUCTION OF MUBARKIYAH 115/13.8KV SUBSTATION IN AL-HASSA
CONTRACTOR: AL SHARIF KEC
National Grid-SA Cont # 4400001840/00
J. O. No.
Dated:
1-1233049.02
Monday, September 15, 2014
Sr. No#
7
7.1
ASKEC Response
Source
At staircase 1,
7.1.1
Replace the exit light with incandescent lamp over the door outside
7.1.2
7.2
7.2.1
At control room,
Along grid 8,
7.2.2.1
7.2.2.2
7.2.2.3
Add one egress lighting fixture and distribute the fixtures at equal distance.
7.2.2
ISD
7.2.4
Along grid A, add one egress lighting fixure and distribute the fixtures at equal
distance.
Along grid D,
7.2.4.1
Add one (1) egress light and distribute it at column D15 and D19.
7.2.4.2
7.2.3
ISD
ISD
NG-SA Comments
Sr. No#
8
8.1
ASKEC Response
Source
ISD
CONCURRED
COMPLIANCE STATEMENT FOR SOE POINT LIST COMMENTS OF MUBARKIYAH 115/13.8KV S/S
Project Title: CONSTRUCTION OF MUBARKIYAH 115/13.8KV SUBSTATION IN AL-HASSA
CONTRACTOR: AL SHARIF KEC
National Grid-SA Cont # 4400001840/00
J. O. No.
Dated:
1-1233049.02
Monday, September 15, 2014
Sr. No#
NG-SA Comments
ISD
NG-SA Comments
Sr. No#
ASKEC Response
Source
11
ISD
NG-SA Comments
Sr. No#
ASKEC Response
Source
12
12.1
ASKEC Response
Source
10
11.1
ISD
Sr. No#
10.1
9
9.1
ASKEC Response
Source
ISD
CONCURRED
COMPLIANCE STATEMENT FOR SOE POINT LIST COMMENTS OF MUBARKIYAH 115/13.8KV S/S
Project Title: CONSTRUCTION OF MUBARKIYAH 115/13.8KV SUBSTATION IN AL-HASSA
CONTRACTOR: AL SHARIF KEC
National Grid-SA Cont # 4400001840/00
J. O. No.
Dated:
1-1233049.02
Monday, September 15, 2014
Sr. No#
NG-SA Comments
NG-SA Comments
15
16
16.1
Sr. No#
17
17.1
17.2
ISD
Sr. No#
Sr. No#
ASKEC Response
Source
14
15.1
ISD
Sr. No#
14.1
13
13.1
ASKEC Response
Source
ASKEC Response
SOE POINT LIST
SOE POINT LIST AT AL-MUBARKIYAH 115/13.8KV S/S
#EA 274681 Sheet 2 of 2 Rev B Indoor Auxiliary Power Layout Plan First Floor
Source
ISD
ASKEC Response
SOE POINT LIST
SOE POINT LIST AT AL-MUBARKIYAH 115/13.8KV S/S
#EA 274682 Sheet 1 of 4 Rev B Indoor Power and Lighting Details
Detail 2, 115KV GIS Room, the indicated height of lighting is 9.0m while 8.2 in the
ISD
calculation.
NG-SA Comments
Source
NG-SA Comments
Source
ASKEC Response
SOE POINT LIST
SOE POINT LIST AT AL-MUBARKIYAH 115/13.8KV S/S
#EA 274686 Sheet 1 of 4 Rev B Cable Raceway Layout Plan & Sections
Raise the portion of cable trays when routed across passageways and when routed
across the doorway.
ISD
Raise the two layers cable tray for adequate passageway.
CONCURRED