ABSTRACT:

This project includes the analysis of the conditions of the current operation
and the year 2020 of the primary feeders, belonging to Substation No 4
(Calpi-San Juan), EERSA, for this was used CYMDIST program, a tool that
allows to simulate The behavior of the primary feeders, that is, calculate the
operating conditions of the primary and its power losses at maximum
demand. In the primary feeder 104, operating with the demand projected to
the year 2020, a reconfiguration was realized that includes: division into 2
circuits, with the denomination San Juan and Espoch, then it was proceeded
to reconfigure the San Juan circuit, where it is contemplated: From Load,
change of gauge and the installation of a voltage regulator. For the feeder
204, 2 alternatives of the solution are developed, in the first alternative,
reconfiguration divided into 2 circuits with the denominations: 204 (San
Andrs) and 204 (Urbano), then the reconfiguration of the San Andrs circuit
was carried out that contemplates the change Driver's gauge; In the second
alternative, the reconfiguration is performed: the change of gauge in a small
section and the installation of a voltage regulator, the two alternatives are
taken first, which produces better profitability and less time to recover
capital. For feeders 304 and 404, their operating conditions for the year
2020 are within the norm, therefore, no investment is needed to improve or
justify an economic analysis.

Este proyecto comprende el anlisis de las condiciones de operacin actuales y al


ao 2020 de los alimentadores primarios, pertenecientes a la Subestacin No 4
(Calpi-San Juan), de la EERSA, para ello se utiliz el programa CYMDIST, herramienta
que permite simular el comportamiento de los alimentadores primarios, esto es,
calcular las condiciones de operacin del primario y sus prdidas de potencia a
demanda mxima. En el alimentador primario 104, operando con la demanda
proyectada al ao 2020, se realiz una reconfiguracin que comprende: divisin en
2 circuitos, con la denominacin San Juan y Espoch, luego se procedi a
reconfigurar el circuito San Juan, donde se contempla: transferencia de carga,
cambio de calibre y la instalacin de un regulador de voltaje. Para el alimentador
204 se desarrollan 2 alternativas de solucin, en la primera alternativa, se
reconfigura dividindolo en 2 circuitos con las denominaciones: 204 (San Andrs) y
204 (Urbano), luego se realiz la reconfiguracin del circuito San Andrs que
contempla cambio de calibre del conductor; en la segunda alternativa se realiza la
reconfiguracin que contempla: cambio de calibre en un pequeo tramo y la
instalacin de un regulador de voltaje, de las dos alternativas se toma la primera,
ya que produce mejor rentabilidad y menor tiempo de recuperacin del capital. Para
los alimentadores 304 y 404, sus condiciones operativas para el ao 2020, estn
dentro de la norma, por lo tanto, no se necesitan inversiones para mejoras ni se
justifica un anlisis econmico.

You might also like