You are on page 1of 52

Control

ACS1000 Control
Hardware
ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 1

ACS1000 Control Hardware

ACS1000 Control Overview


Standard Boards
Internal Option Modules
Fieldbus Adapter Summary
Control Panel CDP 312
AMC3 board
INT Board
EPS Board
VLSCD Board
ADCVI Board
OVVP Board
SCA Subprint
SVA Subprint

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 2

Control

ACS1000 Control Hardware

IOEC Board
GUSP Board
IGCT
Option module connection to AMC3
Pulse Encoder Interface (NTAC)
Profibus Adapter (NPBA)
Modbus Adapter (NMBA)
CS31 Adapter (NCSA)
Comparison ACS600-ACS1000

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 3

Control

ACS1000 Control Overview


Internal Connections

PANEL

14 DI
6 DO
2 AO
4 AI

IOEC 1

Fan Pump1

DO 1 ORD ON Fan / Pump 1


DI 1 Trip Fan / Pump 1

Service plus
Drive-Windows

Optional Break chopper

Interface

DI 4 DP Cool air SV trip

FOL

DO 2 ORD ON Fan / Pump 2


DI 2 Trip Fan / Pump 2
DI 5 L exp vessel low

Fan Pump2

Control

Electronic power
supply (incl. battery)

FOL

4
Sec. 1
FOL
Sec. 2

Gate Unit Power Supply

FOL

DDE
Aux Fan

DO 6 MCB ORD Trip (low active) aux.


DI 3 Trip aux. Fan

Battery is ON

Gate Drive units

Battery is OK
FOL

Earth isolation switch

Battery ON
DI 10 Earth isolation open

14

DDCS 3

RS485

DI 11 Earth isolation closed


ENABLE

TEST Battery

DO 4 Earth. Isolator Unlocked

FRONT DOOR
OPEN

CLOSED

DO 5 MCB-CLOSED

EARTH. I SOL .
UNLOCKED

LSD-1

AMC-3

DI 6 Pushbutton OFFLINE

UP Short circuit + (FOL)

DI 7 Pushbutton ONLINE

di / dt

PPCS
I filt A I filt C U dc1 U dc2

FCB

DI 8 DISABLE LOCAL
DI 9 Air filter supervision

PPCS

DDCS 2

DO 3 Order ON Motor Heater

I Inv A I Inv C Irerd

AMC-Tabelle

PPCC
LSD-2

EPLD

DI 12 Motor Heater trip

DOWN Short circuit + (FOL)

di / dt

PPCC
ADCVI

DI 13 External Trafo protection trip

Extern

Control und Macros


DI 14 External Motor protection Trip

PPCS 1

AO 1 Raw water control valve ref value


AO 2 TORQUE (Raw water control valve ref value 2 ??)
T

4..20mA

4..20mA

PT100
PT100

4..20mA

I Inv A I Inv C

DDCS 1

PPCC

Optional Fieldbus
Interace

Optional Tacho
Channel A and B

Iinv A

Filter Over-current (FOL)

14 DI
6 DO
2 AO
4 AI

AI 1 Motor WDG Temp U


AI 2 Motor WDG Temp V
AI 3 Motor WDG Temp W

Ifilt C

DC-Overvoltage

Iinv C

Inverter-Overcurrent(FOL)

I Rerd1

MCB

OVPP

open MCB FOL


DC-Overvoltage (FOL)

Intermediate link
overvoltage

Emergency-OFF fol

Macros

Ifilt A

PPCC

Irerd1

IOEC 2 (adr = A)
4..20mA
4..20mA

DDCS 2
DDCS 0

PPCS 3

AI 4 Reference Value 2 Manual

PT100

PPCS 2

AI 2 P coolant
AI 3 Conductivity

4..20mA

External Connections

AI 1 T coolant or T air beef heat sink


(OPTION if needed)

4..20mA

DO 6 MCB order close

U dc1
U dc2

DO 5 MCB order open (low active)

Main circuit breaker

U dc1
U dc2

PPCC

I filt A I filt C U dc1 U dc2

OR

DI 9 MCB open

10

11

12

13

Synch. M1
Synch. M2
Synch. M3

Order ON Output Isolator

Order ON Input Isolator

Input isolator open

Input isolator closed

Output isolator closed

External water cooling alarm

El. Door interlock

BRG Temp NDE actual value

temperature breakchopper trip (> max2)

1
5

DI 2 Forward / Reverse (Manual)

Output isolator open

External water cooling trip

14 DI
6 DO
2 AO
4 AI

IOEC 4

temperature breakchopper alarm (> max1)

Input voltage unbalanced

Motor cooler trip

External motor protection Alarm

BRG Temp DE actual value

DI 1 Start / stop (Manual)

Motor cooler Order ON

AO 2 Current

AO 1 Speed

Vibration SV Trip

4..20mA

Vibration SV Alarm

4..20mA

AI 4 Reference Value 1 Auto

14 DI
6 DO
2 AO
4 AI

Overspeed Trip

A
rpm

4..20mA

Motor Cooling Trip

DO 4 Trip

REMOTE
CONTROL

Motor Cooling Alarm

Oil temp Trip or Trafo winding temp trip

DO 3 Alarm

Buchholz alarm

DO 2 Running

ALARM

Oil level Alarm

RUNNING

T RIP

Oil temp alarm or Trafo winding temp alarm

IOEC 3
DO 1 Ready

Bucholz trip

DI 11 MCB Not available

READY

AI 1 oil temp./ Trafo winding temp. -actual value

DI 10 MCB closed

CUSTOMER
CONTACTS

9 10 11 3 4 5

12 13 14 6

14

DI 3 (macro depending)

DI 6 (macro depending)
DI 7 Remote MCB order close
DI 8 Process_stop

TRANSFORMER
Protection

DI 12 Remote Reset
DI 13 Remote MCB order open
5 DI and 1 AI
DI 14 Emergency-OFF

Intern

MOTOR
Protection
7 DI , 1 DO and 2 AI

Input Voltage

DI 4 (macro depending)
DI 5 (macro depending)

FREE

External
water
cooling

break
chopper

Output
Isolator

Synch. for
PUMP Appl
Input
Isolator

OPTIONS

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 4

FREE

Standard Boards
AMC3 Application and Motor Control Board

NAMC

INT Main Circuit Interface Board


Gate amplifiers with GCTs (x14)
EPS Electronic Power Supply + 2 x GUPS
IOEC Standard I/O Board (2 pcs)
ADCVI,OVVP, VLSCD Meas. & Protection Boards
CDP 312 : CONTROL PANEL

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 5

Control

Internal Option Modules


IOEC3, I/O Extension Board
IOEC4, I/O Extension Board
NTAC2, Pulse encoder
NAIO-02 , Analog IO Extension module
NDNA-01, DeviceNet adapter
NCSA-01, CS31 adapter
NIBA-01, Interbus S adapter
NPBA-02, Profibus adapter
NMBA-01, Modbus adapter
NMBP-01, Modbus plus adapter
NAFA-01, AF100 Fieldbus
Others

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 6

Control

Fieldbus Adapter Summary


Adapter

Protocol

Size of
Link

Transmission
Speed

Control

Original
Vendor

NPBA-02

Profibus-DP

31 stations

9.6...1500 kBit

Siemens

NCSA-01

ABB Procontic
CS31

22 stations

187.5 kBaud

ABB

247 stations

1.2...19.2 kBaud

AEG

NMBA-01 1) Modicon Modbus


1)

NMBP-01

Modbus+

64 stations

1 MBaud

AEG

NDNA-01

DeviceNet

63 stations

125...500 kBaud

Allen-Bradley

NIBA-01 1)

Interbus-S

32 stations (!)

500 kBaud

Phoenix

1)

Ability to Read and Write ACS1000 parameters in the groups 1 to 99.

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 7

Control Panel CDP 312

1 L 1242 rmp I
SPEED 1242 rmp
CURRENT 76 A
POWER 55 %

ACT

PAR

FUNC

DRIVE

ENTER

LOC
REM

RESET

REF

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 8

Control

Mounted on converter door


Local operation of drive
Monitoring actual and reference values
Macros and parameter settings
Fault memory monitoring
Parameter up/down load
RS485 connection with AMC3 board

Control Panel CDP 312

Control
Panel
Display

Status Line

1 L 1242 rmp I
SPEED 1242 rmp
CURRENT 76 A
POWER 55 %

ACT

PAR

FUNC

DRIVE

ENTER

Control
Panel
Keypad

LOC
REM

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 9

RESET

REF

Control

Mode Selection Keys


Up & Double up Arrows,
Enter,
Down & Double Down Arrows
Local/Remote, Reset,
Reference, Start
Forward, Reverse, Stop

LINK B INT1 PPCS1

BOOT EPROM
JTAG / OnCE Connector
DSP processor
RAM
FLASH
LINK A INT0 PPCS0

24Vdc power supply

CH5 DDCS5

CH4 DDCS4

CH3 DDCS3

CH2 DDCS2

CH1 DDCS1

CH0 DDCS0

RS485 bus for panel


Rx
Tx
Rx
Tx
Rx
Tx
Rx
Tx
Rx
Tx
Rx
Tx

CH6 DDCS6

CH7 DDCS7

5conthw1.ppt / Version A / 1998-05-08 / Page 10

Rx

Rx

ABB Industrie AG
Drive Products / IUS

Tx
Tx

Tx

ASIC

Rx
Tx
Rx

LEDs

Control

AMC3 Board

AMC3 Board
(PPCS-PROTOCOL)

IOEC Board

FIELD BUS
APC 2

LINK A
INT Board

CH0

INT0

D3TXD
D3RXD

TXD
RXD

GND

CLK

CLK

+24V_RS

ICMC0-ASIC

A0-15
D0-23

A0-15
D0-23

ICMC1-ASIC

+5V
+3.3V
DGND
+24V_RS
+5V_RS
AGND

CH1

OSCILLATOR
32 MHz

TXD
RXD

D3TXD
D3RXD

D2TXD
D2RXD

D1TXD
D1RXD

D0TXD
D0RXD

+5V_RS

PANEL & BUS INTERFACE

POWER_FAIL

CH2

1 2 3 4 5 6
TRANS
FAULT

X17

CH3

D2TXD
D2RXD

INT1

MASTER /
FOLLOWER

CH4

D1TXD
D1RXD

CH5

DRIVE
WINDOWS

CH6

(PPCS-PROTOCOL)

D0TXD
D0RXD

LINK B
INT Board

TACHO

CH7

FIBER OPTIC LINKS


(DDCS-PROTOCOL)

CONTROL
PANEL

BA+
AGND
+24V_RS

FIBER OPTIC LINKS


(DDCS-PROTOCOL)

Control

CONTROL BUS
GAL
ADDRESS BUS

POWER

RESET

DGND

PROM
32k*8

5V / 3.3V

DATA BUS
FLASH
2048k*8

GND
REAL
TIME
CLOCK

+24V
GND

X14 1 2 3 4

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 11

SRAM

SRAM

SRAM

512k*8 512k*8 512k*8

DSP
56303

OnCE

AMC3 Board

Control

Auxiliary power- on
Auxiliary power 27V for
boards from EPS- board

AMC- board PROM

Purpose

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 12

Color

Description

Red

Green

R
M

Green Power OK

T1&T2
(Traffic)

S0-3
(State display)

Control panel
CDP 312
loading

F
M
T1
S3
S2

Fault

(State.display mode)

Program loading
FLASH--> RAM
7...10 seconds

Red
Green
Yellow
Yellow
Yellow

Green

R
P
T2
S1
S0

Green
Green
Yellow
Yellow
Yellow

Illuminated, when booting up the AMC3


Illuminated, when booting up the AMC3

Software implemented. Not used .

turned on when DDCS-channels 0 (T1)


Yellow LED:s
(APC 2 Field bus) and 3 (T2) (Drive windows)
are receiving data. Hardware implemented.

Yellow

Software implemented. Not used

AMC3 Board

Control

AMC3 Application Motor Controller


AMC3 handles all motor & drive information and status,
motor model, torque and flux calculations, SW protection,
SW tripping levels
AMC3 communicates with the IEOC & INT boards through the
DDCS (Distributed Drive Control System) and
PPCS (Power Plate Control System) channels
Fast DSP 56303 (Digital Signal Processor), 66 MHz
Status indication by Leeds
MMI interface to ABB Support Tool, Drives Windows,
CDP312 Panel, Field buses

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 13

AMC3 Board
Fast SRAM memory 512 x 24 bits (Variables)
Flash memory 2048 k x 8 bit (subprint)
Program code , initial values of SW and parameters
RS485 interface for Modbus communication (panel)
8 DDCS communication channels, 4 MBPS
2 PPCS communication channels, 8 MBPS
Watchdog
Boot-PROM
Galvanically isolated 27VDC power supply

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 14

Control

AMC3 Board

Control

Contents of different memories


SRAM memory: Variables (SW are loaded after booting)
Flash memory: Program code , initial values of SW and
parameters
Boot-PROM:

Booting code for AMC3 board

Replacement of AMC3 board


1)

Change the flash from the old AMC3 board


to the new AMC3 board

2)

Change the AMC3 board with programmed Flash and


download application parameters to Flash the memory

Attention: Check compatibility of FLASH SW with EPLD SW


ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 15

A404
TX_AMC0

A541
RX_ADCVI1

A531
RX_ADCVI2

A209
RX_SPARE4

A403
RX_AMC0

FOL

FOL

A210
OVC_M

A592
TX_ADCVI2

FOL

FOL

FOL

A202
OVV_ZK

A302
TX_ADCVI1

FOL

FOL

A201
RX_SPARE3

A551
RX_ADCVI0
FOL

FOL

A204
OVV_ULS2

A402
TX_ADCVI0
FOL

FOL

A203
OVV_ULS1

A303
RX_AMC1
FOL

FOL

A207
PWF_GUSP1
A208
PWF_GUSP2

A304
TX_AMC1
FOL

FOL

A206
RX_SPARE2

LINK E LINK D LINK C LINK B LINK A

FOL

FOL

FOL

A641
OVVP

Control

FOL

A205
RX_SPARE1

INT Board

2x27Vdc
supply
from EPS
X1

FOL

FOL

3 2 1

Control
connector
to EPS

A591

X201

V591
V568
.
.
.
.
.
.
V561

V103
5V

PPCC

FLEX 10K40

V641
PPCC

FOL

FOL

FOL

FOL

FOL

FOL

FOL

FOL

FOL

FOL

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 16

A724
MCBOFF

A712
GUBC1
A713
GUBC2

A593
TX_SPARE1
A594
MCBOFF1

A723
GUP2

A714
GUBC3
A715
GUBC4

A722
GUP1

FOL

FOL

A804
GU10
A814
GU11
A815
GU12

FOL

FOL

FOL

A805
GU9

FOL

A803
GU6
A813
GU7
A705
GU8

FOL

A703
GU5

FOL

A812
GU3
A704
GU4

FOL

A702
GU1

FOL

Green LED V103 lights when internal 5V is OK


Green LED V113 lights when redundant secured 5V for critical function is OK
Red LED V591 lights when EPLD is on booting from A591
Red LED V641 lights when DC overvoltage occurred. (Resetting by aux. power)

FOL

A802
GU2

SR

V113
5V save

Gnd

INT Board

Control
14 gate units

Overvoltage limit (OVVP)


Current limit (Inverter)
Voltage limits +Uls
Voltage limits -Uls
Voltage limits IL
Power fail GUSP1
Power fail GUSP2
Spare
Spare
Spare
Spare
LINK C PPCS - ADCVI0

4 brake chopper
gate units
FORX
FORX
FORX

OVVP - DELAY
AND LATCH

FOTX

FOTX

FOTX

FOTX

FOTX

FOTX

FOTX

FOTX

FOTX

FOTX

FOTX

FOTX

FOTX

FORX
FOTX
FORX
FORX

HARDWIRED
LOGIC

FORX

DRIVER

FORX

FOTX

FORX

FOTX

FORX

FOTX

FORX
FORX

FORX

BOOT-EPROM

EPLD
FLEX 10K40

PPCC

PPCC

+ 5V/3A
GENERAL

DC

FOTX

5conthw1.ppt / Version A / 1998-05-08 / Page 17

FORX

PPCS - AMC 3 LINK B

FOTX

FORX

ABB Industrie AG
Drive Products / IUS

PPCS - AMC3 LINK A

Osz.

FORX

6 galvanic inputs
2 galvanic outputs

MCB_OFF to IOEC1
MCB_OFF1to IOEC2
Spare

FOTX

FOTX

LINK E PPCS - ADCVI2

FOTX

FOTX

FOTX

LINK D PPCS - ADCVI1

FOTX
FOTX

EPS_MAIN_OK
EPS_CTP_OK (+-20V)
EPS_BAT_OK
EPS_BAT_IS_ON
EPS_I_GUSP1
EPS_I_GUSP2
EPS_BAT_TEST (OUTPUT)
EPS_BAT_ON (OUTPUT)

DC

SUPPLY
0V

ORING
NETWORK

+ 5V/1A
SECURED

DC
DC

+
24 V DC
24 V DC
+

INT Board

Control

INT : INTerface board


Control of IGCTs via optic links (also optional Braking
Chopper)
contains EPLD chip for selection of optimum voltage
switching, also for protections
Measurement interface between the current and voltage
measuring board ADCVI to AMC3 Board
Communicates with AMC3 via optic links, receives torque,
flux and sector information from AMC3 Board
Protection signals from ADCVI, GUSPs, OVPP and
VLSCD1/VLSCD2 boards to EPLD and AMC3 Board
Control of EPS (Electronic Power Supply)
MCB control signals through IOEC1 and IOEC2 boards
Galvanically isolated 27VDC power supply
ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 18

INT Board
- 12 fiber optic outputs to inverter
- 2 fiber optic outputs to protection igcts
- 4 fiber optic outputs to braking chopper
- 2 fiber optic outputs to IOEC2 board for MCB
- 7 fiber optic inputs for protection
- Galvanic connection to EPS
- 2 PPCS channels for communication with AMC3
- 3 PPCS channels for communication with ADCVI

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 19

Control

EPS Board

Control

EPS ( KU C720 )
R26
2

R24
6

Gr. LED +/- 20V OK


Yel. LED GUSP1 I>1,5A
Yel. LED GUSP2 I >1,5A

V307
V171
V174

V111

V183

Gr. LED 27V supply OK


Gr. LED Battery connected

V186

Yel. LED Battery test on

V177
F101

F113

F112

F109

F110

F111

F108

F107

F106

F105

F104

F103

F102

X101_3

F114

F2

F1

TP101

32VAC
INPUT

X6_3

X6_2

X6_1

X101_4

1 2 3

1 2 3 4

1 2 3 4 5 6

1 2 3 4 5 6

1 2 3 4 5 6

1 2 3 4 5 6

X8

X9

X1

X2

X3

X4

X51
X5

27VDC CONTROL
27VDC
27VDC
27VDC
24VAC 24VAC
E_ISOL 3A INT (1) 3A IOEC3 3A IOEC4 3A SIGNALS
INPUT POWER
RELAIS 3A IOEC 1,2 3A INT (2) 3A GUSP1 10A OVVP 3A BETWEEN
CONDUCT. DC_AC 3A AMC3 3A GUSP2 10A NTAC 3A INT&EPS
MEASUR.. 3A

1 2 3 4

X7

+-20VDC
ADCVI

27VDC output voltage is adjusted with trimmer R262 at factory and maximum output current is limited to 18A with R246
Green battery polarity LED lights when positive wire from battery is put on test pin TP101. F114 is 20A fuse for batteries

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 20

EPS Board

Control
BATTERY 2 * 12V / 6 Ah

575V
480V
400V

32V

DC

AUX.
MAINS

BATTERY MANAGEMENT & INTERFACE

DC

DC
DC

24V AC

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 21

+20V 0V -20V

27V 0V

BTEST
BBATON
MTEST
MBATON
MLGON
MPNON
MIGUSP1
MIGUSP2

EPS Board

Control

EPS : electronic power supply


- Supply for all electronic boards AMC3, INT, ADCVI, OVPP,
GUPS1 and GUPS2 (27 VDC)
- Battery back-up (2 x 12VDC, 6 ah) for 10 minutes keep
IGCTs conducting to avoiding self-excitation
- Battery control (on-off) and supervision (battery test function)
- Supply for external relays (24VAC)
- Auxiliary power failure information to AMC3 via INT
- Galvanically isolated 32 & 24VAC power supply from T1

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 22

EPS Board

Electronic power supply inputs


- 3 x 32 VAC, 50/60 hz from aux. Transformer
- 3 x 24 VAC, 50/60 hz from aux. Transformer
(output to external relays and contactors)
- 24 VDC (2 x 12 V) from battery

Electronic power supply outputs


- 14 x 27 VDC, max 16 A for boards and GUSP
- +20 VDC, max 45 W for ADCVI board
- 24 VAC, 50/60 hz, max 50 VA for external relays

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 23

Control

VLSCD Board

Control
VLSCD

Rectifier
bridge

Vls1

+
+

Ia

Inverter
bridge

Motor

NP +
Ib

Vls2

VLSCD

Optical fiber to INT board

Z2

HFBR 1528
R5

VLSCD

Z3

LS choke

LS choke

R1

R2

C1
Z1

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 24

R3

R4

VLSCD Board

Control

VLSCD : Voltage Level Short-Circuit Detection


- Short-circuit detection in the inverter power stage
- Detection is based on the measurement of voltage across the
commutation reactors
- Separate protection for + and - parts of the inverter
- Optical signal informs when commutation is going on in
inverter
If signal lasts too long (over 10us) -> short-circuit indication
If signal does not appear every 50ms, when inverter operates
with sufficient load current -> VLSCD fault detection
- short circuit in output terminals detected by currentmeasuring transducers (overcurrent)
Caution: VLSCD board is at intermediate DC potential

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 25

ADCVI Board

Control

NP

PPCC
ASIC
CH 0

PPCC
ASIC
CH 2

SVA
VOLTAGE ADJUST

X3

Iw
X4

Iuf

PPCC
ASIC
CH 1

INSULATION

Iu

X6

SCA Iwf
X7
-15V

CURRENT ADJUST

Ignd
X8

+15V

-DCBUS

PE
CH 0
A8

A1

TX RX

LINK C

CH1
A9 A2

A6

TX RX

TX RX

TX TX

IOC INVERTER / FILTER OVERCURRENT


DCOV DC OVERVOLTAGE
POWER SUPPLY OK LEDs +5V +15V AND -15V

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 26

X1 -

+5V
CH 2
A10 A3

LINK D LINK E

+
+
+
+
+

A4

PE

IOC DCOV

CURRENT
TRANSDUCERS

ADCVI BOARD

+DCBUS

POWER
+ SUPPLY
+/- 20V

ADCVI Board
5M

Control

5M

+DCBUS
NP

+
-

-DCBUS
voltage adjust

1 +20V
2
3 -20V

IUinverter

RANGE
ADJUST

+DC

FILTER

/ -DC
DCBUS NOMINAL =

IWinverter

X4

( 4kV or 3.3kV or 2.4kV )


x
2 x 1.045

IUinv, IWinv, Ignd/5.33


A4

IUfilter
R
C

RANGE
ADJUST

1 +20V
2 IW filter
3 -20V
X7
1 +20V
Iearth
2
3 -20V

current adjust

X6

AGND

COMMUNICATION
&
DATA TRANSFER
IUinv.

FILTER

IWinv. PPCC ASIC


+DC CHANNEL 0
Temp

OVER LIMITS
SUPERVISION

A6

DCOV 129% DCBUS


( nominal)
IOC 220% Iinverter
( nominal)

A8

LINK C
A1

IUfil

SCA

X8
1 +20V
0V
2
3 -20V

AGND

SVA
AGND

1 +20V
2
3 -20V

DIFFERENTIAL
MEASURING

1 +20V
2
3 -20V
X3

power
supply

burden
resistors

AGND

Temperature
Sensor

Earth
+15V
-15V
+5V

X1

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 27

AGND

IWfil. PPCC ASIC


-DC CHANNEL 1

LINK D

0V

A2

-10C ....+ 76C


Ignd
0V
0V
0V

DGND

A9

PPCC ASIC
CHANNEL 2

A10

LINK E
A3

ADCVI Board

Control

ADCVI : analogue-digital current-voltage interface


- Measuring of converter DC voltage (DC+ and DC-)
- HW protection of DC overvoltage
- Measuring of converter currents (2 inverter output currents,
2 filter currents and earth current)
- HW overcurrent protection for inverter
- Temperature measurement of by PTC
- 3 PPCC communication channels to interface board
(measured current and voltage values)
- Fiber optic links to trip inverter in overcurrent and overvoltage
- SCA subprint make current adaptation
- SVA subprint make voltage adaptation
Caution:

ADCVI board is connected to intermediate DC potential


via high ohmic resistors

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 28

OVVP Board

5M

5M

5M

5M

NP

-DC

5M

5M

ELECTRONICS
SVA
SUBPRINT

+DC

Control

-15V OK

OVP

+15V OK

power 27VDC

OVVP OVERVOLTAGE PROTECTION AGAINST SELF EXITATION


POWER SUPPLY OK LEDS FOR -15V AND 15V

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 29

OVVP Board

Control

OVVP BOARD

SVA SUBPRINT

5M

5M

+DCBUS

47K5

+DCBUS
+

+
-

+
+

5M

DCBUS NOMINAL =

+
+DC

( 4kV or 3.3kV or 2.4kV )


x
2 x 1.045

COMPARATOR

139%DCBUS
( nominal)

NP
-

47K5

NP

5M

DIFFERENTIAL
MEASURING

OPTICAL TRANSMITTER

+
-

+
-DC

-DCBUS

5M

-DCBUS

COMPARATOR

47K5

5M

+15V

+27V

DC

AGND
-15V

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 30

DC

FROM
EPS
GND

OVVP Board

Control

OVVP : overvoltage protection board


- Supervises DC overvoltage against self-excitation
- Fiber optic output to trip the MCB in case of overvoltage
(Self-excitation)
- Powered separately by EPS
- SVA subprint make voltage adaptation
Caution: OVVP board is connected to intermediate DC potential
via
high ohmic resistors

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 31

SCA Subprint

Control

SCA : Subprint Current Adjust


- SCA subprint adjust different current ranges (17)
- SCA subprint is used together with ADCVI board.
- ADCVI board is common for all power ranges and SCA
has to be selected in order to adjust current measuring.
40 - 50 mm
5
1

8
4

X1
X2
5
1
TW O
8 POLE CONNECTORS

SCA 5140A

X3
4 8

ABB INDUSTRIE AG
HIEE YYYXXXA
8
4

UF CXXYYAE

40 - 60mm
1 5

SCA Subprint
8 POLE CONNECTOR

10mm

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 32

ADCVI BOARD
COMPONENT SIDE

SCA Subprint
POWER TYPE
AND CURRENT
TRANSFORMER TYPE
3823A
ES300 (motor & filter)
3833A
ES300 (motor & filter
3840A
ES300 (motor & filter)
5123A
ES500 (motor & filter)
5133A
ES500 (motor & filter)
5140A
ES300 (motor & filter)
6823A
ES500 (motor & filter)
6833A
ES500 (motor & filter)
6840A
ES500 (motor & filter)
6823W
ES500 (motor & filter)
6833W
ES500 (motor & filter)
6840W
ES500 (motor & filter)
9123WR
ES2000 (motor & filter)
9133WR
ES2000 (motor & filter)
9140WR
ES1000 (motor & filter)
9133W
ES2000 (motor & filter)
9140W
ES1000 (motor & filter)

Control

Inverter nominal
current / Measuring
range
190Arms
570Apeak
150Arms
450Apeak
115Arms
345Apeak
335Arms
1005Apeak
270Arms
810Apeak
190Arms
570Apeak
440Arms
1320Apeak
360Arms
1080Apeak
250Arms
750Apeak
650Arms
1950Apeak
500Arms
1500Apeak
380Arms
1140Apeak
920Arms
2760Apeak
700Arms
2100Apeak
580Arms
1740Apeak
920Arms
2760Apeak
750Arms
2250Apeak

Filter nominal
current / measuring
range
190Arms /
570Apeak
150Arms
450Apeak
115Arms
345Apeak
335Arms
1005Apeak
270Arms
810Apeak
190Arms
570Apeak
440Arms
1320Apeak
360Arms
1080Apeak
250Arms
750Apeak
650Arms
1950Apeak
500Arms
1500Apeak
380Arms
1140Apeak
920Arms
2760Apeak
700Arms
2100Apeak
580Arms
1740Apeak
920Arms
2760Apeak
750Arms
2250Apeak

Earth current

SAP Code

RFB resistance

3BHL2953R0001

15.78
0.5W
20.00
0.5W
26.087
0.33W
22.39
0.33W
27.78
1W
15.79
0.5W
17.045
0.5W
20.8333
0.4W
30.00
0.33W
11.54
0.5W
15
0.5W
19.74
0.4W
8.15
0.8W
10.71
0.8W
12.93
0.5W
8.15
0.8W
10.0
0.7W

(measuring range =
56.25% Iinv)

ES-300
107A 84.21 / 0.3W
ES-300
84.4A 106.7 / 0.2W
ES-300
64.7A 139.13 / 0.15W
ES-300
188.44A 47.76 / 0.5W
ES-300
151.88A 59.26 / 0.5W
ES-300
107A 84.2 / 0.3W
ES-300
247.5A 36.36 / 0.7W
ES-300
202.5A 44.44 / 0.5W
ES-300
140.625A 64 / 0.33W
ES-300
365.6A 24.61 / 0.85W
ES-300
281.25A 32 / 0.6W
ES-300
213.75A 42.1 / 0.5W
ES-300
517.5A 17.4 / 1W
ES-300
394A 22.86 / 0.9W
ES-300
326.25A 27.58 / 0.75W
ES-300
517.5A 17.4 / 1W
ES-300
421.9A 21.33 / 1W

3BHL2953R0002
3BHL2953R0003
3BHL2953R0004
3BHL2953R0005
3BHL2953R0006
3BHL2953R0007
3BHL2953R0008
3BHL2953R0009
3BHL2953R0010
3BHL2953R0011
3BHL2953R0012
3BHL2953R0013
3BHL2953R0014
3BHL2953R0015
3BHL2953R0016
3BHL2953R0017

table 1: Nominal and Maximal currents for each power type

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 33

SVA Subprint

Control

SVA : Subprint Voltage Adjust


- SVA subprint adjust the interface boards OVVP and
ADCVI to the different voltages ( 4k16V / 3k3V / 2k4V)
ATTENTION:
4K16V
2K4V

soldering
bridges

4K16V
3K3V
2K4V

4K16V
3K3V
2K4V

In order to get the correct identification (part number and code),


the adjusting of the subprint to the right voltage has to be made in
ABB Industrie AG CH-5300. ABB will deliver the subprint with the
correct adjust and part number to all distributor centers worldwide.

ABB INDUSTRIE AG
CODE
PART NUMBER

3K3V

SVA BOARD (SOLDERING SIDE)


10 mm

The differential voltage measuring is performed by voltage dividers


with high voltage resistors and very precise operational amplifiers.
The different types of SVA subprint are provided by connecting two
soldering points soldering side of the board) in order to perform the
right voltage divider of the wished voltage.

Inverter type
Line voltage Motor voltage
2400 Vac
3300 Vac
4160 Vac
ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 34

2400Vac
3300Vac
4160Vac

Voltages
Maximal measuring
type
voltage range
0 - 2425 Vdc
SVA2K4
0 - 3475 Vdc
SVA3K3
0 - 4200Vdc
SVA4K16

IOEC Board

Control

Setting of analog inputs is made by dip switches


AI_ 20mA AI_ 10V
ON
OFF
Current input 4-20mA
OFF
ON
Voltage input 0-10V
ON
ON
Current input, wrong amplification
OFF
OFF
Voltage input, wrong amplification

IOEC board address has to be selected by node address


switch: IOEC1->2, IOEC2->4, IOEC3->6, IOEC4->8
Node address Solder joint for
switch
direct MCB_OFF
X6
1

V740

Gnd

V504

V514

V107

V524

V534

V544

V117

V127

V137

V147

V157

V177

V187

V197

V207

V217

V227

V237

V554

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 35

X31-1
X32-1 X31-2
X32-2 X31-3
X32-3 X31-4
X32-4 X31-5
X32-5 X31-6
X32-6 X31-7
X32-7

X11-1
X11-2
X11-3
X11-4
X11-5
X11-6
X11-7
X11-8
X11-9
X11-10
X12-1
X12-2
X12-3
X12-4
X12-5
X12-6
X12-7
X12-8
X12-9
X12-10
X13-1
X13-2
X13-3
X13-4
X13-5
X13-6
X13-7
X13-8
X13-9
X13-10

X26-1
X26-2
X26-3

X25-1
X25-2
X25-3

X24-1
X24-2
X24-3

X23-1
X23-2
X23-3

X22-1
X22-2
X22-3

X21-1
X21-2
X21-3

1
2
3
4

ON

ON

AI1
AI1
AI2
AI2

V726

20mA
10V
20mA
10V

A451

AI3
AI3
AI4
AI4

A405

MCBOFF

1
2
3
4

A403

TX_DDCS

20mA
10V
20mA
10V

RX_DDCS

V167

V402

IOEC Board

Control

6 DO

14 DI

>1
>1
MCB - DO

2 AO

I
U
I
U

4 AI
10V

DC
DC

FORX

24V

A
DC

24 V DC

D
+15V

DC

BIO

- 15V

FORX
IOCC

+ 5V
DC

PWM1
PWM2
Node adr.
Reset Osz.

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 36

MCB_OFF

Uref

DC

FOTX

DDCS1

IOEC Board

Control

IOEC = Input-Output Electronic Card

Analog and digital interface of the converter:


-14 Digital inputs, 230 VAC / 20 ...160VDC
- 6 Digital outputs, max. switching voltage:
120 VDC/ 250 VAC, max. currents: 24 VDC 8 A ,
125 VDC 0.4 A , 250 VAC 8 A
- 4 Analog inputs, 4-20 mA or 0-10 V, 10 bit 0,25% +-30mV
- 2 Analog outputs, 4-20 mA , 12 bit 0,25% +-0,1mA ,
Load max.250 ohm.
Optical DDCS link for communication (4 Mbit/s)
Converter has 2 IOEC boards as standard , 2 optional
Interrogation voltage 24Vdc+-20% limited to 180mA by PTC
can be supplied from IOEC board
IOEC is monitored by SW

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 37

IOEC Board

Control

Isolation levels of i/os:


- DI: input-input 2300VAC , input-logic 1350VAC ,
Input-ground 1350 VAC
- Do:
4000 vac
- AI: input-input 350VAC 60 hz , input-logic 350 VAC 60 hz ,
input-ground 350VAC 60 hz
- AO:
output-output 350VAC 60 hz , output-logic 350VAC 60 hz
,
output-ground 350VAC 60 hz
Status indication leds for power supply green V740 , for
interrogated supply green V726 , for communication fault red
V402 and for digital inputs and outputs yellow leds
If soldering pads are soldered together, DO5 and DO6 will be
deactivated and controlled via fiber optical MCB_OFF input.
(Light: DO5 and DO6 relay outputs on, no light: relays off)
Caution: risk of external voltage

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 38

GUSP Board

Control
GUSP1

EPS

Sub-board 1

GU

Power supply
22.4 ....28.4V

Sub-board 2

GU

Sub-board 3

GU

Sub-board 4

GU

Sub-board 5

GU

Sub-board 6

GU

Sub-board 7

GU

Main
board

GUSP2

CONNECTION OF GATE UNITS


( 20 Volt + 0.5 Volt, 4A )
GALVANIC ISOLATION BETWEEN SUB-BOARDS
GALVANIC ISOLATION BETWEEN LOW AND MIDDLE VOLTAGE SIDE

Main-board

Sub-boards

From supply
22.4 . . 28.4 V
X1:4 (0V)
X1:3 (+24V)

20 Volt
Filter
15 Volt Supply

Monitoring
signal for
INT-board
A1

Chopper
controlled
supply
transformer
for sub-boards

20 Volt
Control

Monitoring

ISOLATION TRANSFORMER

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 39

Short circuit 0 Volt


Protection

GUSP Board
GUSP: gate unit supply power
- GUSP = main board + transformer + sub-boards (7pcs)
- Powering of igcts
- Isolation transformer separates inverter potential from
supply voltage (27VDC) by EPS
- In self-excitation, both power supplies have battery
back-up for 10 minutes to keep motor short-circuited
- Fiber optic link to control electronics to indicate fault.
Fault indication -> no solid light come on case of switching
loss (one or both primary windings) or supply under
21,5vdc
- Indication leds in sub-board
Caution: sub-boards of GUSP and transformer secondary are at
inverter potential (medium voltage)
ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 40

Control

GUSP Board

Control

Sub-board has two indications LED


Yellow LED

Green LED

light

State of control sub-board

light

Output state operate correctly, no over load

weak light

blink

Output state operates correctly, over load /


short circuit in output: output voltage has
dropped under 10V, sub-board will try
continually switch in.

no light

light

LED or serial resistance defect

no light

no light

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 41

Supply voltage loss or control sub-board defect

IGCT

Control

IGCT = GCT + Gate Driver

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 42

IGCT

Control

Inverter and protection IGCTs (6 types) for air cooled types:

38/51/68mm/4,5kv for 2,3kv and 3,3kv units

38/51/68mm/6,0kv for 4,0kv units


Gate unit is integrated with the GCT, each GCT has its own
gate unit
Gate unit is fed by GUSP (20vdc +-0,5V)
Fiber optic link to INT (interface) card to receive
commands of GCT switching (receive light -> turn on the
GCT)
Separate channels for turn-on, continuous gate current
and turn off
LED status indications only in GUSP sub-board
Caution: gate unit and cables between GU- and GUSP
board are at inverter potential (medium voltage)

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 43

IGCT

Control

GATE UNIT
20V DC

Supply

From EPS

Turn
on
circuit

Gate

Turn
off
circuit

Cathode

Logic,
Monitoring
Control signal
(Light)

Rx

From INT

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 44

IGCT

Control

Fault behavior of gate unit

Cause

Effect to Gate Unit

Reaction of Gate Unit

GCT is switched too fast Under voltage on capacitors


or turn off circuit of Gate of Gate Unit
Unit is in short circuit

1. If a turn-off pulse is not possible, the following


a turn on pulse is ignored.
2. When requirements for a turn off pulse are again
fulfilled a switching signal can be executed.

No supply or too low supply


voltage

1. If a turn-off pulse is not possible, the following


turn on pulse is ignored.
2. When requirements for a turn off pulse are again
fulfilled a switching signal can be executed.

loss of GUSP

3. If VGU falls below 10V. This is detected as


a short circuit between the gate and the cathode.
Short circuit impedance must be very small and
that state must stand 5 minutes
Auxiliary supply or
cooling fan

Six Gate Units will be turned on


(0-Vector). This state will remain
15 minutes without inverter
cooling. Surface temperature
of heat sinks can be 60C in the
beginning and falls to ambient
temperature of inverter in time
constant about 3 minutes.

Other loss of Gate Unit

Undefined effect

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 45

Gate Unit must hold this load.

Undefined Reaction. Switching circuit of the Gate


Unit is protect against fault propagate by GUSP.

Option module connections to AMC3

ACS 1000
AMC 3
NTAC-02

Pulse encoder

NMFA-01

Master Field Bus


ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 46

Control

Pulse Encoder Interface (NTAC)


CONNECTIONS
Supply
Earthings
Tacho
Fiber optic link

+24V

0V

24

15

Control

24/15

+V

-V

X2

SETTINGS
See Installation and Start-up Guide
Node address

TXD

NTAC-02
PULSE
ENCODER
INTERFACE

PARAMETERS IN ACS1000
See Users Manual
Activation P75.03
Parameters in group 50
.
.
.

RXD

X1
A+

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 47

A-

B+

B-

Z+

Z-

SH

PE

Profibus Adapter (NPBA)


CONNECTIONS
Supply
Earthings
PROFIBUS bus cable
Fiber optic link

Control

PE

+24V

X2

RXD

0V

SH

SHF

DG

D(N)

D(P)

SETTINGS
See Installation and Start-up Guide
Bus termination
TXD

PARAMETERS IN ACS1000
See Users Manual
Activation P75.04
Parameters in group 51
.
.
.

PROFIBUS
ADAPTER
MASTER
BUS
TERMINATION
MSG

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 48

ON
OFF

DDCS

INDICATION LEDs

NPBA-01

Modbus Adapter (NMBA)


CONNECTIONS
Supply
Earthings
MODBUS bus cable
Fiber optic link

SETTINGS
See Installation and Start-up Guide
Bus termination

PARAMETERS IN ACS1000
See Users Manual
Activation P75.04
Parameters in group 51
.
.
.

INDICATION LEDs

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 49

Control

CS31 Adapter (NCSA)


CONNECTIONS
Supply power
Earthings
CS 31 bus cable
Fiber optic link

Control

PE

X2

SH

SHF

DG

D(N)

RXD

SETTINGS
See Installation and Start-up Guide
Bus termination

TXD

CS 31
ADAPTER

PARAMETERS IN ACS1000
See Users Manual
Activation P75.04
Parameters in group 51
.
.
.

DDCS
BUS
TERMINATION
UART

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 50

ON
OFF

ERROR

INDICATION LEDs

NCSA-01

D(P)

Comparison ACS600-ACS1000
Main Motor Control

ACS600

ACS1000

Motor Control Board

NAMC1

AMC3

Digital Signal Processor 40 Mhz

66 Mhz

Communication DDCS

8 channels

4 channels

Communication PPCS

Control

2 channels

RAM memory

3 x 128 k

1 x 512 k

Flash memory

512k

2M

Controlling inverter

2 level (8 switching
positions)

3 level (27 switching


positions)

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 51

Comparison ACS600-ACS1000

Standard I/O Boards

ACS600

ACS1000

I/O Board

1x NIOC-01

2 x IOEC

Number of DI

6 pcs

14 pcs

Number of DO

3 pcs

6 pcs

Number of AI

3 pcs

4 pcs

Number of AO

2 pcs

2 pcs

ABB Industrie AG
Drive Products / IUS
5conthw1.ppt / Version A / 1998-05-08 / Page 52

Control