You are on page 1of 10

Digital Control System

Addendum to Technical Manual


System version: from 5.1.0 to 5.1.5
DS Agile/EN M/C65a

WARNING
This Addendum added to the Technical Manual that it complements give instructions for installation,
commissioning and operation of the DS Agile System. However, the guide cannot cover all conceivable
circumstances or include detailed information on all topics. In the event of questions or specific problems,
do not take any action without proper authorization. Please, contact the appropriate Alstom technical
sales office and request the necessary information.
Refer to the System Release Notes for new features.
Any agreements, commitments, and legal relationships and any obligations on the part of Alstom,
including settlement of warranties, result solely from the applicable purchase contract, which is not
affected by the contents of the guide.

DS Agile System

Addendum to Technical Manual

Contents
1

SCOPE OF THE DOCUMENT

CHANGES TO THE FUNCTIONAL DESCRIPTION CHAPTER


(DS AGILE/EN FT)

Section 1.10.3 Local/remote control operating modes:


Cancels and replaces the existing section.

2.1

DS Agile/EN AD/C65a

AD-1

Addendum to Technical Manual

AD-2

DS Agile System

DS Agile/EN AD/C65a

DS Agile System

Addendum to Technical Manual

SCOPE OF THE DOCUMENT

The present document is an addendum to the DS Agile System Technical Manual ref. DS Agile/EN M/C60
(system version 5.1.0).
It covers a feature added to the system between system version 5.1.0 and system version 5.1.5:

Addition of a new Substation Local/Remote mode independently settable for each electrical bay
managed by a C26x
The changes are presented as standard "cancels and replaces" existing sections in the chapter impacted by
the system's evolutions:

Functional Description chapter:

Section 1.10.3 Local/remote control operating modes

DS Agile/EN AD/C65a

AD-3

Addendum to Technical Manual

DS Agile System

CHANGES TO THE FUNCTIONAL DESCRIPTION CHAPTER


(DS AGILE/EN FT)

2.1

SECTION 1.10.3 LOCAL/REMOTE CONTROL OPERATING MODES:


CANCELS AND REPLACES THE EXISTING SECTION.

1.10.3

LOCAL/REMOTE CONTROL OPERATING MODES

1.10.3.1

GLOBAL SUBSTATION LOCAL/REMOTE MODE (STATION BUS LEVEL)

A substation can be in remote control mode or local control mode.


Remote mode means that the substation is controlled from the Remote Control Point (RCP), via a gateway.
No control command can be sent from the Substation Control Point (SCP) level (except if the target bay is in
SBMC mode, see below).
Local mode means that the substation is controlled from the DS Agile Operator Interface (Substation Control
Point). The control commands issued from the RCP are not taken into account by the system, they are
refused.
Some control commands, defined during the configuration stage, can be independent of the global
substation L/R control mode: It means that they can be issued from the SCP or the RCP, regardless of the
current L/R control mode. Control commands from a configurable automation (ISaGRAF) are accepted,
regardless of the current L/R mode.
1.10.3.2

SUBSTATION LOCAL/REMOTE MODE PER BAY (STATION BUS LEVEL)

This feature is similar to the Global Substation L/R mode described above, except that the Substation L/R
mode can be switched independently for each bay.
Remote mode means that the bay is controlled from the Remote Control Point (RCP), via a gateway. No
control command can be sent from the Substation Control Point (SCP) level (except if the bay is in SBMC
mode, see below).
Local mode means that the bay is controlled from the DS Agile Operator Interface (Substation Control Point).
The control commands issued from the RCP are not taken into account by the system, they are refused.
Some control commands, defined during the configuration stage, can be independent of the substation L/R
control mode of the bay: It means that they can be issued from the SCP or the RCP, regardless of the
current L/R control mode. Control commands from a configurable automation (ISaGRAF) are accepted,
regardless of the current L/R mode.
Note:
The substation L/R mode per bay can only be used in bays managed by a C26x. This means that the datapoint MUST
NOT be placed under bays managed by gateways or protection IEDs for instance.

Note:
The global substation L/R mode and the substation L/R mode per bay are mutually exclusive. When the L/R mode per
bay is declared in a database, the global L/R mode MUST be set to REMOTE by default and must not be switchable.

AD-4

DS Agile/EN AD/C65a

DS Agile System

1.10.3.3

Addendum to Technical Manual

BAY LOCAL/REMOTE MODE (C26X/BCP LEVEL)

Each electrical bay can be independently set to Remote or Local mode.


Remote mode means that the bay is controlled from the upper level, i.e. the Remote Control Point (RCP) or
the Substation Control Point (SCP), depending on the current substation control mode. No control
commands can be sent from the Bay Control Point (BCP) level, i.e. the front panel LHMI of the DS Agile
C26x controller that manages the bay.
Local mode means that the bay is controlled from the BCP. Control commands issued from upper levels are
refused.
Some control commands, defined during the configuration stage, can be independent of the bay L/R control
mode: It means that they can be issued from any control points, regardless of the current control mode.
Control commands from a configurable automation (ISaGRAF) are accepted in remote mode.
1.10.3.4

SBMC MODE

The SBMC (Site Based Maintenance Control) mode is used to control a specific bay from the controllers
Local HMI or from the systems Operator Interface even if the substation is in remote mode. This feature is
normally used during commissioning and maintenance operations. It also makes it possible to filter the data
transmitted from the bay to the SCADA.
The Gateway manages the filtering of SBMC-dependant datapoints in both directions (control and indication)
so that:

While in SBMC mode, an electrical bay does not receive, and therefore does not execute, SBMCdependent xPC commands received from the Remote Control Point (RCP), even if the substation is in
remote mode and whatever device manages them,

Whatever the device that manages them, SBMC-dependent information signals from a bay in SBMC
mode are not forwarded to the RCB and are suppressed or substituted with a preset value instead.
All the information signals received from C26x BCUs and IEDs, as well as from the IEC 61850/IEC 61850
Gateway's lower level, can be sent to the RCP when the SBMC mode is not active.
The datapoints that control and indicate SBMC mode for an electrical bay can be managed by the following
devices:

a DS Agile C26x BCU,


an IEC 61850/IEC 61850 Gateway or
another compatible IED.
Note:
Only the device that manages the electrical bay can manage the SBMC datapoints attached to it.

DS Agile/EN AD/C65a

AD-5

Addendum to Technical Manual

DS Agile System

The diagram below shows an example of configuration where the SBMC mode allows blocking the
commands from the SCADA and filtering information datapoints:

SCADA

Key:
IEC 61850 network

SCADA
Network

IEC 60870-5-104 network


Bay management relation
Datapoint management

DS Agile
Substation Operator

GTW (slave protocol)

Switch 3

Bay 1
(managed by C264)
SBMC1
Datapoints
managed by C264
in both bays

DB for Upper Network

Switch 1

DB for Lower Network

Switch 2

C264

Bay 2
(managed by C264)
SBMC2

GTW1-T104M
IEC 60870-5-104

IED3

Datapoints
managed by
IED1 in Bay 1

IED1
IED4
Datapoints
managed by
IED2 in Bay 2

IED 1
(T104 slave)

IED 2
(T104 slave)

IED2
S1052ENc

The availability of SBMC filtering is defined independently for each electrical bay during the configuration
process.
Note:
An SBMC SPS datapoint covers all the SBMC-dependent datapoints of its electrical bay, including datapoints managed
by a device other than the one that manages the SBMC SPS. It cannot manage any other datapoint.

1.10.3.5

LOCAL/REMOTE MANAGEMENT ON IEC/IEC GATEWAY

A configuration attribute allows you to define that the IEC61850 / IEC61850 gateway must use the
Substation Local/Remote information. The Substation Local/Remote xPS comes from the lower
IEC 61850-8-1 network.

Note:
Substation Local/Remote per bay can only be used in single ring Station Bus networks; it cannot be used in an
IEC 61850/IEC 61850 architecture.

AD-6

DS Agile/EN AD/C65a

Alstom Grid
- ALSTOM 2015. All rights reserved.
Information contained in this document is
indicative only. No representation or warranty
is given or should be relied on that it is
complete or correct or will apply to any
particular project. This will depend on the
technical and commercial circumstances. It is
provided without liability and is subject to
change without notice. Reproduction, use or
disclosure to third parties, without express
written authority, is strictly prohibited.
Alstom Grid Worldwide Contact Centre
www.alstom.com/grid/contactcentre/
Tel: +44 (0) 1785 250 070

www.alstom.com

You might also like