Professional Documents
Culture Documents
Distribution System
Manohar Singh, B. K. Panigrahi, Senior Member, IEEE and A. R. Abhyankar, Member, IEEE
I. INTRODUCTION
Protection systems must respond quick, selective and
reliable to faults in the distribution system. Overcurrent
protection, one of the basic protective relaying protection
schemes is frequently used for distribution system protection.
Overcurrent protection is more economical and therefore,
favored on a distribution level. It operates without the
application of costly communication equipment as needed in
distance and differential protection schemes.
Selectivity problem of overcurrent relays can be tackle by
time grading. But this result in delayed relay operational time
for faults which are more severe and close to the source.
Inverse type overcurrent relay clears the heaviest fault
quickly. Backup protection is provided to each unit if primary
relay fails to operate. Primary and backup relay pairs are
chosen from the graph theory so that there is proper
coordination between Primary and backup relay pairs. To
coordinate this backup protection with the primary relay
characteristic will ensure that the backup relay has sufficient
time delay to allow the primary relay (and its breaker) to clear
the fault.
Several methods have been proposed for the coordination
of overcurrent relays. These methods can be classified into
three classes: trial and error [1], topological analysis method
[2, 3], and optimization method. However, the solutions found
by the first two classes, are not optimal in any strict sense, but
only the best of the tried possible solution. In other words,
Manohar Singh, Research Scholar Department of Electrical Engineering,
IIT-Delhi (e-mail: manoharsingh33@gmail.com).
Dr. B. K. Panigrahi is with the Department of Electrical Engineering, IITDelhi(bkpanigrahi@ee.iitd.in, Delhi-110016, INDIA
Dr. A. R. Abhyankar is with the Department of Electrical Engineering,
IIT-Delhi(abhyankar@ee.iitd.ac.in, Delhi-110016, INDIA
(978-1-4673-0136-7/11/$26.00 2011 IEEE)
min( Z ) = wi * ti ,k
i =1
(2)
wi = 1 .The
f (I p , Ii ) =
+L
1
(3)
TABLE I
VALUES OF , AND l FOR DIFFERENT TYPES OF OCRS [4]
L
Relay type
Standard
Moderately inverse
IEEE
0.02
0.0515
0.114
Very inverse
IEEE
2.0
19.61
0.491
Extremely inverse
IEEE
2.0
28.2
0.1217
Standard inverse
IEC
0.02
0.14
0.0
Very inverse
IEC
1.0
13.5
0.0
min
i
and
TDS
max
i
are
Ri . TDS
min
i
(4)
and TDS i
are taken as
top = a * TDS
a = 1 + L; M =
(5)
I fault
I pickup
min
max
I pickup
I p I pickup
For standard IDMT relay, is 0.02 and is 0.14 as per
(6)
Ri ,
t i ,k t j ,k = t
TABLE III
PRIMARY-BACKUP RELATIONSHIP OF RELAYS
V.
CASE STUDIES
Impedance ()
1-2
0.08+j1
2-3
0.08+j1
1-3
0.16+j2
TABLE V
CT RATIOS AND PLUG SETTINGS OF RELAYS
Relay
CT ratio
1000:1
300:1
1000:1
600:1
600:1
600:1
TABLE VII
OPTIMIZED TDS
TMS
Bhibe et al
Proposed
TMS(1)
0.0765
0.0590
TMS(2)
0.034
TMS(3)
Problem formulation
In this case there are six variables (TMS of six relays), six
constraints due to bounds on relay operating time and four
constraints due to coordination criteria (actually there are five
constraints due to coordination criteria, but one of them is
redundant). The minimum operating time of each relay is
taken as 0.1 s. The normal range of TMS is taken as 0.025 to
1.2. This constraint is also taken into account. The CTI is set
to its typical value of 0.3 s. TMS of the six relays are taken as
TMS1TMS6.
Fault current at different location and corresponding relay
coefficients for a standard IDMT relay having and , 0.02
and 0.14 respectively are shown in Table VI.
0.0339
0.0250
0.0250
TMS(4)
0.036
0.0300
TMS(5)
0.0711
0.0640
TMS(6)
0.0294
0.0250
Min(z)
15.1170
11.9435
TABLE IX
COMPARSION OF OPERATING TIME OF PRIMARY AND
BACKUP
TABLE VI
CURRENT SEEN BY THE RELAYS AND THE
a j ,i CONSTANT
B CASE STUDY 2
In this case a single end fed, multi loop distribution
system, with eight OC relays as shown in Fig. 3 is considered.
The system is multi loop system because depending on the
fault point, different configurations (depending on the
direction of current in various feeders) are formed. Six
different fault points are taken for illustration
= 38.1252
+ 36.6709
+ 13.4823
* TMS(1)
* TMS(3)
* TMS(5)
+ 9.2049
+ 4.3590
+ 2.3451
* TMS(2)
(7)
* TMS(4)
* TMS(6)
* TMS
* TMS
(4)
(1)
- 1.4553
- 3.3674
* TMS
* TMS
(2) 0.3
(3) 0.3
3.3674
28.039
5.2636
* TMS
* TMS
* TMS
(5)
(3)
(1)
- 3.3674
- 4.3590
- 5.2636
* TMS
* TMS
* TMS
(4)
(6)
(3)
0.1 TMS(i)
0.025,
0.3
0.3
0.3
i = 1 to 6
Result
The above mathematical model of case 1 is optimized
using Genetic algorithm. The optimize TDS of six
TABLE XIII
Problem formulation
The optimization problem is formed in the same way as
explained in illustration I. In this case there are eight variables
(TMS of eight relays), eight constraints due to bounds on
relay operating time and nine constraints due to coordination
criteria.
TABLE XI
CURRENT SEEN BY THE RELAYS AND THE
a j ,i CONSTANT
CONCLUSION
(8)
[2]
4 . 00 * TMS ( 3 ) 4 . 00 * TMS ( 8 ) 0 . 3
2 . 00 * TMS ( 8 ) 8 . 00 * TMS ( 5 ) 0 . 3
2 . 00 * TMS ( 8 ) 8 . 00 * TMS ( 6 ) 0 . 3
0.1 TMS(i)
0.025, i = 1 to 8
Result
The optimum values of TDS obtained using GA technique
are given in Table XII.
TABLE XII OPTIMIZED TDS
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
[14]