You are on page 1of 256

HYUNDAI U-Series

Building a better future

HYUNDAI U-Series

Molded Case Circuit Breaker

The philosophy of HYUNDAI U-series MCCB is

for YOU and being NEW


The word U represents
YOU, our business partner and
NEW, your latest needs
The design concepts of U-Series MCCB pursue advanced technology in size,
customized characteristic in range and powerful capability in specification.
All come out from our sincerity to be close to you.

for YOU & being NEW to come close to you with

ADVANCED TECHNOLOGY in size


CUSTOMIZED CHARACTERISTIC in range
POWERFUL CAPABILITY in specification

UAB type
UCB type
UPB type

www.hyundai-elec.com

Upgrade your electric systems with U-Series MCCB!

Molded Case Circuit Breaker

CONTENTS
06 Introduction 08 Features 13 Quick Selection Table 17 Rating Overview
35 Specifications and Standard Order Codes 137 Characteristic Curves & Dimensions 189 Accessories
223 Technical Information 238 Order Information 248 Handling Instruction | Inspection and Maintenance

U-Series

Molded Case Circuit Breaker

Introduction

| Wide and powerful range |

UAB, UCB Type


[ up to 1600AF ]
| Compact size

| Wide and powerful range

High breaking capacity in 60mm depth, up to 250AF

50, 125, 250, 400, 630, 800, 1000, 1250, 1600AF

Application of current-limiting technology

Fixed or adjustable thermal trip mechanism up to 800AF

UAB type

Double protected electronic trip mechanism for 1600AF

- up to 25kA at AC380/415V in W75 x H130 x D60mm


UCB type
- up to 50kA at AC380/415V in W90/105 x H165 x D60mm

| Various accessories

| Reliable quality

Motor operator and operating handles for smooth


operation
Terminal cover and terminal busbar for safety

Type-tested by KEMA Netherlands

DIN rail adapter and mounting base for easy installation


Switches and trip devices for control by signals

MCCB

| Modern and customized design |

UPB, HBL Type

Miniature Type

[ 125, 160, 250, 400, 630AF ]

[ 30, 50, 100AF ]

| High breaking capacity

| Industrial and residential application

Up to 150kA at AC380/415V
Based on current-limiting technology
Ics = 100% Icu

Mini molded case circuit breaker


Mini earth leakage circuit breaker
Up to 100A, 10kA

| Reliable quality

| Various protection

Type-tested by international test authorities


KEMA for IEC standard, KERI for NEMA standard

Short-circuit and overload


Earth leakage protection

| Diverse trip mechanism and application

| Internal accessories

Fixed & adjustable thermal, electronic


Motor protection, nuclear power plant

Auxiliary switch
Trip alarm switch
Shunt trip

Molded Case Circuit Breaker_ 7

U-Series

Molded Case Circuit Breaker

Features
| Adjustable rating in full range with diverse trip mechanisms |
U-Series MCCB adopts adjustable rating function in full range from 50 to 1600AF. With diverse trip mechanisms
of U-Series MCCB, you will be provided with wide options for system design and more flexible load fluctuations.

[ UAB, UCB type ]

Fixed thermal

Adjustable thermal

[ UPB type ]

Fixed thermal

Adjustable thermal

Electronic

Adjustable instantaneous
for motor protection

MCCB

| Wide and powerful production range |


U-Series MCCB supplies you with wide and powerful production range; 3 to 1600A, 5 to 150kA at AC415V from general
distribution boards to nuclear power plants.
U-Series MCCB also completely covers Hi-Series MCCB range with better characteristics.

Thermal magnetic type


Icu
150 kA
130 kA
100 kA
85 kA
50 kA
42 kA
36 kA
30 kA
25 kA
18 kA
10 kA
5 kA
(at 415V)

Hydraulic magnetic
Fixed thermal
Adjustable thermal

UPB160X
UPB100X
UPB160L
UPB100L
UPB100H
UPB160H
UPB100S
UPB160S
UCB100L
UCB160L
UCB100H
UCB160H

UCB50L
UCB50H

UCB100S
UAB100S
UAB100R, UCB100R

UAB50H
UAB50S, UCB50R
UAB30R
UAB50R
UAB30C UAB50C

30AF

UPB250X
UCB630L
UPB250L
UCB800L
UCB630H
UCB400L
UPB250H
UCB800H
UCB630S
UPB250S
UCB400H
UCB800S
UCB800R
UCB250L
UCB630R
(45kA)
(45kA)
UCB250H
UCB400S
UCB250N
UCB400R
UCB250S
UCB250R

UAB60R UAB100C
UAB60C

50AF

60AF

100AF

125AF

160AF

250AF

400AF

630AF

800AF

Electronic type
Icu
150 kA

130 kA
100 kA
85 kA

UPB100X

UPB160X

UPB160L

UPB100L
UPB100H
UPB100S

UPB250X

UPB160H

UPB250L

UPB400H

UPB250S

UPB630L

UPB400L

UPB250H

UPB160S

UPB630X

UPB400X

UPB400S

UPB630H

UCB1000L
UCB1000S

UCB1250L
UCB1250S

UPB630S
UCB1600S

65 kA

(at 415V)

125AF

160AF

250AF

400AF

630AF

1000AF

1250AF

1600AF

Miniature type
Fixed Thermal

Icu
10 kA

UMB30S, UDB30S
UMG30S, UDG30S

5 kA
2.5 kA

UMB50H, UDB50H
UMG50H, UDG50H

UMB30H, UDB30H
UMG30H, UDG30H
UMB50S, UDB50S
UMG50S, UDG50S

UDB100H
UDG100H
UDB100S
UDG100S

UMB30R
UMG30R

(at 220V)

30AF

50AF

100AF

Motor protection - UPB type 125-250AF


Q-class HBL type - 100-225AF
Switch disconnector - UAD type 50-100AF, UCD type 50-1250AF, UPD type 125-630AF

Molded Case Circuit Breaker_ 9

U-Series

Molded Case Circuit Breaker

Features
| High breaking capacity, realized by advanced technology and optimized design |
Our optimized design by advanced current-limiting technology allows U-Series MCCB to realize high breaking capacity
in a smaller size compared to Hi-Series MCCB, contributing to compact design of system.

Same breaking capacity


in 30% smaller size

High breaking capacity


in same size

The current-limiting characteristic of U-Series MCCB also minimizes the effects from fault currents and offers cost-effectiveness.
[UPB type]
Handle
Trip button
Trip(OCR) unit

Arc-chamber unit
Terminal

Mechanism

Moving contact device

Fixed contact device

Maximized repulsive-force trip mechanism


Realized by twin contact structure (two contacts in fixed
contact device, other two in moving contact device), up-down
direction repulsion at both sides of rotary structure, and
u-shaped terminal structure of fixed contact.
Contribute to increase of main contact travel distance,
prevention of arc re-ignition, and correct lead of arc
projection to arc chute.

Arc pressure actuator (APA)


Arc pressure occurred by short-circuit
current can be detected through APA and
operates trip mechanism before the
response of trip sensor.

Minimizing total breaking time, Maximizing current-limiting performance

10

MCCB

| Standardization of dimensions |
U-Series MCCB minimizes the difference in size of each model, so that they can be easily replaced whenever the
specifications of the system changes.

50mm

60mm

50AF

125AF

UAB type : 30-100AF

250AF

UCB type : 50-250AF

| Reliable quality and various applications |


U-Series MCCB is type-tested by international test authorities such as KEMA and KERI as well satisfying IEC60947-2
and NEMA AB-1 standards. It also acquired various marine classes and certificates for nuclear power plants.

Molded Case Circuit Breaker_ 11

U-Series

Molded Case Circuit Breaker

Features
| Modern and refined design |

Model name

Line side terminal

UPB : Type
250 : Ampere frame size
X : Recognition code for order

Rated frequency

Utilization category
Ampere frame size

Suitability of isolation
Rated current

Standard

Main characterisitics
Ui : Rated insulation voltage
Uimp : Rated impulse
withstand voltage
Ue : Rated operational voltage
Icu : Rated ultimate
short-circuit breaking
capacity
Ics : Rated service
short-circuit breaking
capacity

Trip unit

Trip button

Load side terminal

Approvals and certificates

12

Quick Selection Table

U-Series

Molded Case Circuit Breaker

Quick Selection Table


| UAB type / 30-100AF |
Ampere
frame
30

50

60

100

Model

Number
of poles

Breaking capacity [Icu] (kA r.m.s.) Trip mechanism & Characteristics Dimensions (mm)
Rated current (A)

AC220V
AC240V

AC380V
AC415V

AC440V
AC460V

AC600V
AC660V

UAB30C

2, 3

3,5,10,15,20,30

10

7.5/5

2.5

UAB30R

2, 3

5,10,15,20,30

25

14/10

10

5
2.5

Hydraulic
magnetic

Thermal magnetic
Fixed Adjustable

50/75 130 60

UAB50C

2, 3, 4

5,10,15,20,30,40,50

10

7.5/5

UAB50R

2, 3, 4

5,10,15,20,30,40,50

25

14/10

10

UAB50S

2, 3, 4

15,16,20,25,30,32,40,50

42

25

21

7.5

1)

UAB50H

2, 3, 4

15,16,20,25,30,32,40,50

50

30

25

10

1)

UAB60C

2, 3, 4

5,10,15,20,30,40,50,60

10

7.5/5

2.5

UAB60R

2, 3, 4

5,10,15,20,30,40,50,60

25

14/10

10

Width Height Depth

50/75/100 130 60

UAB100C

2, 3, 4

5,10,15,20,30,40,50,60,75,100

25

14/10

10

UAB100R

2, 3, 4

15,16,20,25,30,32,40,50,60,63,75,80,100

42

25

21

7.5

1)

UAB100S

2, 3, 4

15,16,20,25,30,32,40,50,60,63,75,80,100

50

30

25

10

1)

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Not applicable to 2P breaker.

| UCB type / 50-1600AF |


Ampere
frame
50

125

160

250

400

630

800

1000
1250
1600

Model

Number
of poles

Breaking capacity [Icu] (kA r.m.s.) Trip mechanism & Characteristics Dimensions (mm)
Rated current (A)

AC220V
AC240V

AC380V
AC415V

AC440V
AC460V

AC600V
AC660V

Thermal magnetic
Fixed Adjustable Electronic

UCB50R

2, 3, 4 15,20,30,40,50

50

30/25

25

10

UCB50H

2, 3, 4 15,16,20,25,30,32,40,50

85

42

42

20

UCB50L

2, 3, 4 15,16,20,25,30,32,40,50

100

50

50

25

UCB100R

2, 3, 4 15,16,20,25,30,32,40,50,60,63,75,80,100,125

50

30/25

25

10

UCB100S

2, 3, 4 15,16,20,25,30,32,40,50,60,63,75,80,100,125

65

42/36

35

18

UCB100H

2, 3, 4 15,16,20,25,30,32,40,50,60,63,75,80,100,125

85

42

42

20

UCB100L

2, 3, 4 15,16,20,25,30,32,40,50,60,63,75,80,100,125

100

50

50

25

UCB160H

2, 3, 4 100,125,160

85

42

42

20

UCB160L

2, 3, 4 100,125,160

100

50

50

25

UCB250R

2, 3, 4 100,125,150,160,175,200,225,250

35

25/18

18

7.5

UCB250S

2, 3, 4 100,125,150,160,175,200,225,250

50

35/25

25

10

UCB250N

2, 3, 4 100,125,150,160,175,200,225,250

65

42/36

35

18

UCB250H

2, 3, 4 100,125,150,160,175,200,225,250

85

42

42

20

UCB250L

2, 3, 4 100,125,150,160,175,200,225,250

100

50

50

25

UCB400R

2, 3, 4 250,300,320,350,400

35

30

25

18

UCB400S

2, 3, 4 250,300,320,350,400

50

42

35

22

UCB400H

2, 3, 4 250,300,320,350,400

85

65

50

25

UCB400L

2, 3, 4 250,300,320,350,400

125

100

85

30

UCB630R

2, 3, 4 500,630

50

45

35

22

UCB630S

2, 3, 4 500,630

100

65

50

25

UCB630H

2, 3, 4 500,630

100

85

65

35

UCB630L

2, 3, 4 500,630

125

100

85

35

UCB800R

2, 3, 4 700,800

50

45

35

25

UCB800S

2, 3, 4 700,800

100

65

50

25

UCB800H

2, 3, 4 700,800

100

85

65

35

UCB800L

2, 3, 4 700,800

125

100

85

35

UCB1000S

3, 4

505-1000

100

100

75

40

210/280 370 110

UCB1000L

3, 4

505-1000

150

130

100

60

210/280 370 200

UCB1250S

3, 4

630-1250

100

100

75

40

210/280 370 110

UCB1250L

3, 4

630-1250

150

130

100

60

210/280 370 200

UCB1600S

640-1600

100

65

45

25

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
2P breaker has same dimension as 3P breaker, but the middle pole is removed.

14

Width Height Depth

60/90/120 155 60
90/90/120 155 60
60/90/120 155 60
90/90/120 155 60
105/105/140 165 60

105/105/140 164 60

105/105/140 165 60

140/140/185 257 110

210/210/280 280 110

210

371 151

MCCB

| UPB type / 125-630AF |


Ampere
frame

125

160

250

400

630

Model

Breaking capacity [Icu] (kA r.m.s.) Trip mechanism & Characteristics Dimensions (mm)

Number
of poles

Rated current (A)

AC220V
AC240V
1)

AC380V
AC415V

AC440V
AC460V

AC660V
AC690V

UPB100S

3, 4

15,16,20,25,30,32,40,50,60, 63,75, 80,100,125

100

85

65

10

UPB100H

3, 4

15,16,20,25,30,32,40,50,60, 63,75, 80,100,1251)

130

100

85

10

UPB100L

3, 4

15,16,20,25,30,32,40,50,60, 63,75, 80,100,1251)

150

130

100

25

UPB100X

3, 4

1)

15,16,20,25,30,32,40,50,60, 63,75, 80,100,125

200

150

150

25

UPB160S

3, 4

100,125,1601)

100

85

65

10

UPB160H

3, 4

100,125,1601)

130

100

85

10

UPB160L

3, 4

100,125,1601)

150

130

100

25

UPB160X

3, 4

100,125,1601)

200

150

150

25

UPB250S

3, 4

125,150,160,175,200,225,2501)

100

85

65

10

UPB250H

3, 4

125,150,160,175,200,225,2501)

130

100

85

10

UPB250L

3, 4

125,150,160,175,200,225,2501)

150

130

100

25

UPB250X

3, 4

1)

125,150,160,175,200,225,250

200

150

150

25

UPB400S

3, 4

200-400

100

85

65

10

UPB400H

3, 4

200-400

130

100

85

10

UPB400L

3, 4

200-400

150

130

100

25

UPB400X

3, 4

200-400

200

150

150

25

UPB630S

3, 4

320-630

100

85

65

10

UPB630H

3, 4

320-630

130

100

85

10

UPB630L

3, 4

320-630

150

130

100

25

UPB630X

3, 4

320-630

200

150

150

25

Thermal magnetic
Electronic
Fixed Adjustable

Width Height Depth

105/140 165 86.5

140/185 255 117

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
UPB100: 50-125A
UPB160: 63-160A
UPB250: 100-250A
1) Rated current of electronic types are as followings;

| Motor protection / UPB type 125-250AF |


Ampere
frame
125
250

Model

Number
of poles

Rated current (A)

UPB100H

UPB100L

UPB250H
UPB250L

Breaking capacity [Icu] (kA r.m.s.)


AC220V
AC240V

AC380V
AC415V

2.5,3.2,6.3,12.5,20,32,50,63,80,100

130

2.5,3.2,6.3,12.5,20,32,50,63,80,100

150

125,150,175,200,225

125,150,175,200,225

Dimensions (mm)

AC440V
AC460V

AC660V
AC690V

100

85

10

130

100

25

130

100

85

10

150

130

100

25

Width

Height

Depth

105

165

86.5

The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.

| Q-class (for nuclear power plant application) / HBL type 100-225AF |


Ampere
frame

100

225

Model

Number
of poles

Rated current (A)

Breaking capacity [Icu] (kA r.m.s.)


AC220V
AC240V

AC380V AC440V AC480V AC660V


AC415V AC460V AC500V AC690V

HBL103U

15,20,30,40,50,60,75,100

200

150

100

85

25

HBL103UQ

15,20,30,40,50,60,75,100

200

150

100

85

25

HBL103UM

2.5,3.2,6.3,12.5,20,32,50,63,80,100

200

150

100

85

25

HBL103UMQ

2.5,3.2,6.3,12.5,20,32,50,63,80,100

200

150

100

85

25

HBL203U

125,150,175,200,225

200

150

100

85

25

HBL203UQ

125,150,175,200,225

200

150

100

85

25

HBL203UM

125,150,175,200,225

200

150

100

85

25

HBL203UMQ

125,150,175,200,225

200

150

100

85

25

Characteristics

Dimensions (mm)

Motor
E1 class protection
Width

105

Height

Depth

165

86.5

The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
Molded Case Circuit Breaker_ 15

U-Series

Molded Case Circuit Breaker

Quick Selection Table


| Switch disconnector / 50-1250AF |
Type

Ampere
frame

Model

50

UCD50H

Dimensions (mm)
Number Rated
Ampere
Type
of poles current (A) Width Height Depth
frame
3

50

Model

Dimensions (mm)
Number Rated
of poles current (A) Width Height Depth

UAD50C

50

UAD50S

50

100

UAD100R

100

50
90

155

60

100

UCD100S

100

125

UCD100H

125

160

UCD160H

160

105

165

60

125

UPD100S

125

UCD250S

250

105

164

60

160

UPD160S

160

UCD250H

250

105

165

60

250

UPD250S

250

400

UCD400S

400

140

257

110

400

UPD400S

400

630

UCD630S

630

630

UPD630S

630

800

UCD800S

800

1000

UCD1000S

1000

1250

UCD1250S

1250

UAD

75

130

60

105

165

86.5

140

255

117

250
UCD

210

280

110

210

370

110

UPD

| Miniature type / 30-100AF |


Model
Number
Type Ampere Molded case Earth leakage of poles
frame circuit breaker circuit breaker

UMB

30

UMG

Rated current (A)

Rated residual
current [I n]
(mA) for ELCB

Breaking capacity [Icu] (kA r.m.s.)


AC220V
AC240V

AC380V
AC415V

AC440V
AC460V

UMB30R

UMG30R

15,20,30

15, 30

2.5

UMB30S

UMG30S

15,20,30

15, 30

UMB30H

UMG30H

15,20,30

15, 30

10

UMB50S

UMG50S

15,20,30,40,50

15, 30

UMB50H

UMG50H

15,20,30,40,50

15, 30

10

UDB30S

UDG30S

2, 3

3,5,10,15,20,30

15, 30

2.5

2.5

UDB30H

UDG30H

2, 3

2.5

2.5

10

2.5

2.5

2.5

2.5

10

Dimensions (mm)
Width

Height

Depth

33

70

57

35

80

60

50/75

96

60

75/75

96

60

50

30

5,10
15, 30
15,20,30

UDB
UDG

50

UDB50S

UDG50S

2, 3

UDB50H

UDG50H

2, 3

5,10,15,20,30,40,50
5,10

15, 30
15, 30

15,20,30,40,50
UDB100S UDG100S

2, 3

15,20,30,40,50,60,75,100

30, 100

2.5

2.5

UDB100H UDG100H

2, 3

15,20,30,40,50,60,75,100

30, 100

10

100
- KS certified products. English nameplate and 50Hz marking are not available.
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
2P breaker has same dimension as 3P breaker, but the middle pole is removed.

16

Rating Overview

U-Series

Molded Case Circuit Breaker

Rating Overview
| UAB type / 30-50AF |
Model

UAB30

UAB50

Figure

Ampere frame size


Number of poles (P)
Degree of protection (with terminal cover)
Utilization category
Suitability of isolation
Protection
Rated current (A)
Rated insulation voltage [Ui] (V)
Rating
Rated operational voltage [Ue] (V)
Rated impulse withstand voltage [Uimp] (kV)
Recognition code for order
AC600/660V, 50-60Hz
Rated
short-circuit Ultimate AC480/500V, 50-60Hz
AC440/460V, 50-60Hz
breaking
[Icu]
capacity
(kA r.m.s.) AC380/415V, 50-60Hz
AC220/240V, 50-60Hz
IEC 60947-2
DC250V
K 60947-2
DC125V
Service [Ics] % of [Icu]
Hydraulic Fixed thermal,
magnetic Fixed instantaneous INST
Trip
mechanism
Fixed thermal,
& Protection Thermal Fixed instantaneous INST
characteristics magnetic Adjustable thermal, LTD
Fixed instantaneous INST
Direct mounting by screw
Both line & load side
for
Switchboard Line side only
Mounting Plug-in
for Distribution board
DIN-rail with DIN-rail adaptor
Terminal connection Screw
Auxiliary switch
AUX
Trip alarm switch
ALT
Signal
Shunt trip
SHT
Under voltage trip
UVT
Operating Surface type TFG
handle
Extended type TFH
Accessories Operating Motor operator
MOT
Mechanical interlock MIF
Padlock plate
PLD
DIN-rail adaptor
DRA
Mounting
Plug-in mounting base
TDM
Cage terminal block CTB
Terminal Terminal cover
TCF
Interpole barrier
TQQ
Durability Mechanical operation
(times)
Electrical operation
Dimensions
a
Width
(mm)
b
Height
2/3/4P
c
Depth
d
Weight ( , breaker only) 2/3/4P

30AF
2, 3
IP20
A

2, 3, 4
IP20
A

50AF
2, 3, 4
IP20
A

overload, inst., short-circuit


3,5,10,15,20,30 5,10,15,20,30
AC690
AC660
6
C
R
2.5
5
2.5
7.5
5
10
7.5/5
14/10
10
25
50

overload, inst., short-circuit


5,10,15,20,30,40,50
AC690
AC660
6
C
R
2.5
5
2.5
7.5
5
10
7.5/5
14/10
10
25
50

overload, inst., short-circuit


15,16,20,25,30,32,40,50
AC690
AC660
DC250
6
S
H
7.5
10
7.5
14
21
25
25
30
42
50
10
14
15
20
25

12 In

12 In
15-32A: 20 In, 40-100A: 10 In
(0.8-0.9-1) In
15-32A: 20 In, 40-100A: 10 In

1)

1)

1)

1)

1)

1)

1)

1)

1)

1)

2)

2)

1)

2)

2)

1)

2)

2)

1)

1)

1)

3)

25,000
15,000
50/75
130
60
82
0.45/0.65

3)

25,000
15,000
50/75/100
130
60
82
0.45/0.65/0.85

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker 2) Available for 3P, 4P breaker
3) Supplied as standard component

18

3)

25,000
15,000
50/75/100
130
60
82
0.6/0.78/0.96

MCCB

| UAB type / 60-100AF |


Model

UAB60

UAB100

Figure

Ampere frame size


Number of poles (P)
Degree of protection (with terminal cover)
Utilization category
Suitability of isolation
Protection
Rated current (A)
Rated insulation voltage [Ui] (V)
Rating
Rated operational voltage [Ue] (V)
Rated impulse withstand voltage [Uimp] (kV)
Recognition code for order
AC600/660V, 50-60Hz
Rated
AC480/500V, 50-60Hz
short-circuit
Ultimate
AC440/460V, 50-60Hz
breaking
[Icu]
AC380/415V, 50-60Hz
capacity
(kA r.m.s.)
AC220/240V, 50-60Hz
IEC 60947-2
DC250V
K 60947-2
DC125V
Service [Ics] % of [Icu]
Hydraulic Fixed thermal,
magnetic Fixed instantaneous INST
Trip
mechanism
Fixed thermal,
& Protection Thermal Fixed instantaneous INST
characteristics magnetic Adjustable thermal, LTD
Fixed instantaneous INST
Direct mounting by screw
for
Both line & load side
Mounting Plug-in
Switchboard Line side only
for Distribution board
DIN-rail with DIN-rail adaptor
Terminal connection Screw
Auxiliary switch
AUX
Trip alarm switch
ALT
Signal
Shunt trip
SHT
Under voltage trip
UVT
Operating Surface type TFG
handle
Extended type TFH
Accessories Operating Motor operator
MOT
Mechanical interlock MIF
Padlock plate
PLD
DIN-rail adaptor
DRA
Mounting
Plug-in mounting base
TDM
Cage terminal block CTB
Terminal Terminal cover
TCF
Interpole barrier
TQQ
Durability Mechanical operation
(times)
Electrical operation
Dimensions
a
Width
(mm)
b
Height
2/3/4P
c
Depth
d
Weight ( , breaker only) 2/3/4P

60AF
2, 3, 4
IP20
A

100AF
2, 3, 4
IP20
A

2, 3, 4
IP20
A

overload, inst., short-circuit


overload, inst., short-circuit
overload, inst., short-circuit
5,10,15,20,30,40,50,60 5,10,15,20,30,40,50,60,75,100 15,16,20,25,30,32,40,50,60,63,75,80,100
AC690
AC690
AC690
AC660
AC660
AC660
DC250
6
6
6
C
R
C
R
S
2.5
5
5
7.5
10
2.5
7.5
7.5
7.5
14
5
10
10
21
25
7.5/5
14/10
14/10
25
30
10
25
25
42
50
10
14
15
20
50
50
25
12 In

12 In
15-32A: 20 In, 40-100A: 10 In
(0.8-0.9-1) In2)
15-32A: 20 In, 40-100A: 10 In

1)

1)

1)

1)

1)

1)

2)

2)

2)

2)

2)

2)

2)

2)

2)

1)

1)

1)

3)

25,000
10,000
50/75/100
130
60
82
0.45/0.65/0.85

3)

25,000
10,000
50/75/100
130
60
82
0.45/0.65/0.85

3)

25,000
10,000
50/75/100
130
60
82
0.6/0.78/0.96

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker 2) Available for 3P, 4P breaker
3) Supplied as standard component
Molded Case Circuit Breaker_ 19

U-Series

Molded Case Circuit Breaker

Rating Overview
| UCB type / 50-125AF |
Model

UCB50

UCB100

Figure

Ampere frame size


Number of poles (P)
Degree of protection (with terminal cover)
Utilization category
Suitability of isolation

50AF

Protection
Rated current (A)
Rating

Rated insulation voltage [Ui] (V)


Rated operational voltage [Ue] (V)

Rated impulse withstand voltage [Uimp] (kV)


Recognition code for order
AC600/660V, 50-60Hz
Rated
AC480/500V, 50-60Hz
short-circuit
Ultimate AC440/460V, 50-60Hz
breaking
[Icu]
AC380/415V, 50-60Hz
capacity
(kA r.m.s.)
AC220/240V, 50-60Hz
IEC 60947-2
DC250V
K 60947-2
DC125V
Service [Ics] % of [Icu]
Fixed thermal,
Trip
Fixed instantaneous
mechanism Thermal
& Protection magnetic
Adjustable thermal,
characteristics
Fixed instantaneous

INST

2, 3, 4
IP20
A

overload, inst.,
short-circuit

overload, inst.,
short-circuit

15,20,30,40,50

15,16,20,25,30,32,40,50

AC690
AC660
DC250
6
R
10
14
25
30/25
50
14
20
50

AC690
AC660
DC250
6

10 In

LTD
INST

Direct mounting by screw


1)
Both line & load side
for
1)
Switchboard Line side only
Plug-in
1)
for Distribution board
Terminal connection Screw
Auxiliary switch
AUX
Trip alarm switch
ALT
Signal
Shunt trip
SHT
Under voltage trip
UVT
2)
Operating Surface type TFG
2)
handle
Extended type TFH
Accessories
Operating Motor operator
MOT
Mechanical interlock MIF
Padlock plate
PLD
1)
TDM
Mounting Plug-in mounting base
Cage terminal block CTB
Terminal Terminal cover
TCF
3)
Interpole barrier
TQQ
25,000
Durability Mechanical operation
(times)
Electrical operation
10,000
a
Width 60/90/120
Dimensions
b
Height
(mm)
155
2/3/4P
c
Depth
60
d
84.5
Weight ( , breaker only) 2/3/4P
0.7/1.0/1.2
Mounting

100AF
2, 3, 4
IP20
A

2, 3, 4
IP20
A

H
20
30
42
42
85
25
40

L
25
35
50
50
100
40
60
50

15-32A: 15
40-50A: 10
(0.8-0.9-1)
15-32A: 15
40-50A: 10

In,
In
In
In,
In

overload, inst.,
short-circuit
15,16,20,25,30,32,40,
50,60,63,75,80,100,125
AC690
AC660
DC250
6
R
S
10
18
14
25
25
35
30/25
42/36
50
65
14
18
20
25
75
10 In
(0.8-0.9-1) In
10 In

overload, inst.,
short-circuit
15,16,20,25,30,32,40,
50,60,63,75,80,100,125
AC690
AC660
DC250
6
H
L
20
25
30
35
42
50
42
50
85
100
25
40
40
60
75
15-32A: 15
40-125A: 10
(0.8-0.9-1)
15-32A: 15
40-125A: 10

1)

1)

1)

1)

1)

1)

1)

1)

1)

2)
2)

2)

1)

3)

25,000
10,000
904)/90/120
155
60
84.5
0.9/1.0/1.3

3)

25,000
10,000
60/90/120
155
60
84.5
0.7/1.0/1.2

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
2) Available for 3P, 4P breaker
3) Supplied as standard component 4) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.

20

125AF
2, 3, 4
IP20
A

1)

3)

25,000
10,000
904)/90/120
155
60
84.5
0.9/1.0/1.3

In,
In
In
In,
In

MCCB

| UCB type / 160-250AF |


Model

UCB160

UCB250

Figure

Ampere frame size


Number of poles (P)
Degree of protection (with terminal cover)
Utilization category
Suitability of isolation
Protection
Rated current (A)
Rated insulation voltage [Ui] (V)
Rating
Rated operational voltage [Ue] (V)
Rated impulse withstand voltage [Uimp] (kV)
Recognition code for order
AC600/660V, 50-60Hz
Rated
AC480/500V, 50-60Hz
short-circuit
Ultimate AC440/460V, 50-60Hz
breaking
[Icu]
AC380/415V, 50-60Hz
capacity
(kA r.m.s.)
AC220/240V, 50-60Hz
IEC 60947-2
DC250V
K 60947-2
DC125V
Service [Ics] % of [Icu]
Fixed thermal,
Trip
mechanism Thermal Fixed instantaneous INST
& Protection magnetic Adjustable thermal, LTD
characteristics
Fixed instantaneous INST
Direct mounting by screw
Both line & load side
for
Mounting
Switchboard Line side only
Plug-in
for Distribution board
Screw
Terminal connection
Bus bar
Auxiliary switch
AUX
Trip alarm switch
ALT
Signal
Shunt trip
SHT
Under voltage trip
UVT
Operating Surface type TFG
handle
Extended type TFH
Accessories Operating Motor operator
MOT
Mechanical interlock MIF
Padlock plate
PLD
TDM
Mounting Plug-in mounting base
Terminal bus bar
TBB
Cage terminal block CTB
Terminal
Terminal cover
TCF
Interpole barrier
TQQ
Durability Mechanical operation
(times)
Electrical operation
a
Width
Dimensions
(mm)
b
Height
2/3/4P
c
Depth
d
Weight ( , breaker only) 2/3/4P

160AF
2, 3, 4
IP20
A
overload, inst., short-circuit
100,125,160
AC690
AC660
DC250
6
H
L
20
25
30
35
42
50
42
50
85
100
25
40
40
60
50
10 In
(0.8-0.9-1) In
10 In

250AF
2, 3, 4
IP20
A

2, 3, 4
IP20
A

overload, inst., short-circuit


overload, inst., short-circuit
100,125,150,160,175,200,225,250 100,125,150,160,175,200,225,250
AC690
AC690
AC660
AC660
DC250
DC250
6
6
R
S
N
H
L
7.5
10
18
20
25
10
14
25
30
35
18
25
35
42
50
25/18
35/25
42/36
42
50
35
50
65
85
100
10
14
18
25
40
15
20
25
40
60
50
50
10 In
(0.8-0.9-1) In
10 In

10 In
(0.8-0.9-1) In
10 In

1)

1)

1)

1)

1)

1)

1)

1)

1)

1)

1)

1)

2)

2)

2)

25,000
10,000
1053)/105/140
165
60
84.5
1.1/1.3/1.6

25,000
10,000
1053)/105/140
164
60
84
1.1/1.2/1.5

25,000
10,000
1053)/105/140
165
60
84.5
1.1/1.3/1.6

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker 2) Supplied as standard component
3) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.
Molded Case Circuit Breaker_ 21

U-Series

Molded Case Circuit Breaker

Rating Overview
| UCB type / 400-800AF |
Model

UCB400

UCB630

UCB800

400AF
2, 3, 4
IP20
A

630AF
2, 3, 4
IP20
A

800AF
2, 3, 4
IP20
A

overload, inst., short-circuit


250,300,320,350,400
AC690
AC660
DC250
6
R
S
H
L
18
22
25
30
18
25
35
65
25
35
50
85
30
42
65
100
35
50
85
125
14
25
40
40
20
30
50
60
50

overload, inst., short-circuit


500, 630
AC690
AC660
DC250
6
R
S
H
L
22
25
35
35
25
45
50
65
35
50
65
85
45
65
85
100
50
100
100 125
20
40
40
40
30
50
50
60
50

overload, inst., short-circuit


700, 800
AC690
AC660
DC250
6
R
S
H
L
25
25
35
35
35
45
50
65
35
50
65
85
45
65
85
100
50
100
100
125
20
40
40
40
30
50
50
60
50

10 In
(0.8-0.9-1) In
10 In

10 In
(0.8-0.9-1) In
10 In

10 In
(0.8-0.9-1) In
10 In

Figure

Ampere frame size


Number of poles (P)
Degree of protection (with terminal cover)
Utilization category
Suitability of isolation
Protection
Rated current (A)
Rated insulation voltage [Ui] (V)
Rating
Rated operational voltage [Ue] (V)
Rated impulse withstand voltage [Uimp] (kV)
Recognition code for order
AC600/660V, 50-60Hz
Rated
AC480/500V, 50-60Hz
short-circuit
Ultimate
AC440/460V, 50-60Hz
breaking
[Icu]
capacity
(kA r.m.s.) AC380/415V, 50-60Hz
AC220/240V, 50-60Hz
IEC 60947-2
DC250V
K 60947-2
DC125V
Service [Ics] % of [Icu]
Fixed thermal,
Trip
mechanism Thermal Fixed instantaneous INST
& Protection magnetic Adjustable thermal, LTD
characteristics
Fixed instantaneous INST
Direct mounting by screw
Mounting
Both line & load side
for
Plug-in
Switchboard Line side only
Screw
Terminal connection
Bus bar
Auxiliary switch
AUX
Trip alarm switch
ALT
Signal
Shunt trip
SHT
Under voltage trip
UVT
Operating Surface type TFG
handle
Extended type TFH
Motor operator
MOT
Accessories Operating
Mechanical interlock MIF
Padlock plate
PLD
Extension handle
THA
Mounting Plug-in mounting base TDM
Terminal bus bar
TBB
Cage terminal block CTB
Terminal
Terminal cover
TCF
Interpole barrier
TQQ
Durability Mechanical operation
(times)
Electrical operation
a
Width
Dimensions
(mm)
b
Height
2/3/4P
c
Depth
d
Weight ( , breaker only) 2/3/4P

1)

1)

1)

1)

1)

1)

2)

2)

2)

1)

1)

1)

2)

20,000
6,000
1403)/140/185
257
110
145
4/4.5/5.4

2)

20,000
6,000
2103)/210/280
280
110
145
8.7/9.5/12.5

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker 2) Supplied as standard component
3) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.

22

2)

10,000
3,000
2103)/210/280
280
110
145
8.7/9.5/12.5

MCCB

| UCB type / 1000-1600AF |


Model

UCB1000

UCB1250

UCB1600

1000AF

1250AF

1600AF

Figure

Ampere frame size


Number of poles (P)

3, 4

3, 4

Degree of protection (without terminal bus bar)

IP20

IP20

IP20

overload, inst., short-circuit

overload, inst., short-circuit

overload, inst., short-circuit

505-1,000

630-1,250

640-1,600

Rated insulation voltage [Ui] (V)

AC750

AC750

AC750

Rated operational voltage [Ue] (V)

AC690

AC690

AC690

Utilization category
Suitability of isolation
Protection
Rated current (A)
Rating

Rated impulse withstand voltage [Uimp] (kV)


Recognition code for order
Rated
AC600/660V, 50-60Hz
short-circuit
Ultimate AC480/500V, 50-60Hz
breaking
[Icu]
AC440/460V, 50-60Hz
capacity
(kA r.m.s.)
AC380/415V, 50-60Hz
IEC 60947-2
AC220/240V, 50-60Hz
K 60947-2
Service [Ics] % of [Icu]

40

60

40

60

25

75

100

75

100

35

75

100

75

100

45

100

130

100

130

65

150

100

150

100

100
50

50

(0.5-1)1) In (15 setting)

(0.5-1)1) In (15 setting)

50

Long time delay

LTD

Short time delay


Trip
Instantaneous
mechanism
Electronic Ground fault trip
& Protection
Pre-trip alarm
characteristics
I2T lamp

STD

(2-4-6-8-10) Ir

(2-4-6-8-10) Ir

INST

(3-6-8-10-11) In

(3-6-8-10-11) In

GFT

(0.2-0.3-0.4) In

(0.2-0.3-0.4) In

PTA

0.9 Ir

0.9 Ir

(0.4-1)2) In (8 setting)
(2-3-4-5-6-7-8-10) In

Pick-up LED
Mounting

Direct mounting by screw

Terminal connection

Signal

Accessories

Bus bar
Auxiliary switch

AUX

Trip alarm switch

ALT

Shunt trip

SHT

Under voltage trip

UVT

Operating
handle

Extended type TFH

Operating Motor operator

MOT

Padlock plate

PLD

Extension handle

THA

Terminal bus bar

TBB

Terminal Terminal cover


Interpole barrier

3)

3/4P

4)

3)

3)

3)

TQQ

3)

10,000

10,000

3,000

3,000

10,000
3,000

Width

210/280

210/280

210/280

210/280

210

Height

370

370

370

370

371

Depth

110

200

110

200

151

159

249

159

249

215

13/17

25/33

13.5/17.5

25.5/33.5

27

d
Weight ( , breaker only) 3/4P

3)

4)

TCF

Durability Mechanical operation


(times)
Electrical operation
Dimensions
(mm)

3)

4)

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) (0.5-1): (0.63-0.8-1)x(0.8-0.85-0.9-0.95-1) 2) (0.4-1): (0.4-0.5-0.6-0.7-0.8-0.9-0.95-1)
3) Supplied as standard component
4) Supplied as standard component that attached in breaker

Molded Case Circuit Breaker_ 23

U-Series

Molded Case Circuit Breaker

Rating Overview
| UPB type / 125-250AF |
Model

UPB100

UPB160

UPB250

160AF
3, 4
IP20
A

250AF
3, 4
IP20
A

overload, inst., short-circuit


100,125,160
63-160
AC750
AC690
DC5001)
8
S
H
L
X
10
10
25
25
50
65
85
85
65
85
100 150
85
100
130 150
100
130
150 200
501)
651)
851) 1001)
651)
1001) 1001) 1001)
100

overload, inst., short-circuit


125,150,160,175,200,225,250
100-250
AC750
AC690
DC5001)
8
S
H
L
X
10
10
25
25
50
65
85
85
65
85
100
150
85
100
130
150
100
130
150
200
501)
651)
851)
1001)
651)
1001) 1001) 1001)
100

Figure

Ampere frame size


125AF
Number of poles (P)
3, 4
Degree of protection (with terminal cover)
IP20
Utilization category
A
Suitability of isolation
Protection
overload, inst., short-circuit
Thermal magnetic type 15,16,20,25,30,32,40,50,60,63,75,80,100,125
Rated current (A)
Electronic type
50-125
Rated insulation voltage [Ui] (V)
AC750
Rating
AC690
Rated operational voltage [Ue] (V)
DC5001)
Rated impulse withstand voltage [Uimp] (kV)
8
Recognition code for order
S
H
L
X
AC660/690V, 50-60Hz
10
10
25
25
Rated
AC480/500V, 50-60Hz
50
65
85
85
short-circuit Ultimate
AC440/460V,
50-60Hz
65
85
100
150
breaking
[Icu]
AC380/415V, 50-60Hz
85
100
130
150
capacity
(kA r.m.s.)
AC220/240V, 50-60Hz
100
130
150
200
IEC 60947-2
DC250V
501)
651)
851)
1001)
K 60947-2
DC125V
651)
1001) 1001) 1001)
Service [Ics] % of [Icu]
100
2)
Fixed thermal, Fixed instantaneous
Thermal
2)
Trip
Adjustable thermal, Fixed inst.
mechanism magnetic Adjustable thermal, Adjustable inst.
& Protection
2)
characteristics Electronic LTD, STD, INST
PTA, Pick-up LED
Direct mounting by screw
3)
Mounting
Both line & load side
for
Plug-in
3)
Switchboard Line side only
Screw
Terminal connection
Bus bar
Auxiliary switch
AUX
Trip alarm switch
ALT
Signal
Shunt trip
SHT
Under voltage trip
UVT
Operating Surface type TFG
handle
Extended type TFH
Operating Motor operator
MOT
Accessories
Mechanical interlock MIF
Padlock plate
PLD
3)
Mounting Plug-in mounting base TDM
Terminal bus bar
TBB
Cage terminal block CTB
Terminal
Terminal cover
TCF
4)
Interpole barrier
TQQ
Mechanical
operation
25,000
Durability
(times)
Electrical operation
10,000
a
Width
105/140
b
Height
165
Dimensions
3/4P
(mm)
c
Depth
86.5
d
112
Weight ( , breaker only) 3/4P
1.8/2.2

2)

2)

2)

2)

2)

2)

2)

2)

3)

3)

3)

3)

3)

3)

4)

4)

25,000
10,000
105/140
165
86.5
112
2.0/2.4

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) DC is not applicable for electronic breaker.
2) For the detail protection characteristics, please refer to following pages; UPB100: page 92 UPB160: page 98 UPB250: page 102
3) Available for 3P breaker 4) Supplied as standard component

24

25,000
10,000
105/140
165
86.5
112
2.0/2.4

MCCB

| UPB type / 400-630AF |


Model

UPB400

UPB630

400AF
3, 4
IP20
A

630AF
3, 4
IP20
A

Figure

Ampere frame size


Number of poles (P)
Degree of protection (with terminal cover)
Utilization category
Suitability of isolation
Protection
Rated current (A)
Rated insulation voltage [Ui] (V)
Rating
Rated operational voltage [Ue] (V)
Rated impulse withstand voltage [Uimp] (kV)
Recognition code for order
Rated
AC660/690V, 50-60Hz
short-circuit Ultimate
AC480/500V, 50-60Hz
breaking
[Icu]
capacity
(kA r.m.s.) AC440/460V, 50-60Hz
AC380/415V, 50-60Hz
IEC 60947-2
AC220/240V, 50-60Hz
K 60947-2
Service [Ics] % of [Icu]
Trip
LTD, STD, INST
mechanism
Electronic
GFT, I2T lamp
& Protection
characteristics
PTA, Pick-up LED
Direct mounting by screw
Mounting
Both line & load side
for
Plug-in
Switchboard Line side only
Screw
Terminal connection
Bus bar
Auxiliary switch
AUX
Trip alarm switch
ALT
Signal
Shunt trip
SHT
Under voltage trip
UVT
Operating Surface type TFG
handle
Extended type TFH
Motor operator
MOT
Operating
Accessories
Mechanical interlock MIF
Padlock plate
PLD
Extension handle
THA
Mounting Plug-in mounting base TDM
Terminal bus bar
TBB
Cage terminal block CTB
Terminal
Terminal cover
TCF
Interpole barrier
TQQ
Durability Mechanical operation
(times)
Electrical operation
a
Width
b
Height
Dimensions
3/4P
(mm)
c
Depth
d
Weight ( , breaker only) 3/4P

S
10
50
65
85
100

overload, inst., short-circuit


200-400
AC750
AC690
8
H
L
10
25
65
85
85
100
100
130
130
150
100

X
25
85
150
150
200

S
10
50
65
85
100

overload, inst., short-circuit


320-630
AC750
AC690
8
H
L
X
10
25
25
65
85
85
85
100
150
100
130
150
130
150
200
100

1)

1)

1)

1)

2)

2)

2)

2)

3)

3)

2)

2)

3)

3)

20,000
6,000
140/185
255
117
159.5
6.0/7.8

20,000
6,000
140/185
255
117
159.5
6.0/7.8

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) For the detail protection characteristics, please refer to following pages; UPB400: page 108 UPB630: page 110
2) Available for 3P breaker 3) Supplied as standard component
Molded Case Circuit Breaker_ 25

U-Series

Molded Case Circuit Breaker

Rating Overview
| Motor protection / UPB type 125-250AF |
Model

UPB100

UPB250

125AF
3
IP20
A

250AF
3
IP20
A

instantaneous, short-circuit
2.5,3.2,6.3,12.5,20,32,50,63,80,100
AC750
AC690
DC500
8
H
L
10
25
65
85
85
100
100
130
130
150
65
85
100
100
100

instantaneous, short-circuit
125,150,175,200,225
AC750
AC690
DC500
8
H
L
10
25
65
85
85
100
100
130
130
150
65
85
100
100
100

Figure

Ampere frame size


Number of poles (P)
Degree of protection (with terminal cover)
Utilization category
Suitability of isolation
Protection
Rated current (A)
Rated insulation voltage [Ui] (V)
Rating
Rated operational voltage [Ue] (V)
Rated impulse withstand voltage [Uimp] (kV)
Recognition code for order
AC660/690V, 50-60Hz
Rated
short-circuit Ultimate AC480/500V, 50-60Hz
AC440/460V, 50-60Hz
breaking
[Icu]
capacity
(kA r.m.s.) AC380/415V, 50-60Hz
AC220/240V, 50-60Hz
IEC 60947-2
DC250V
K 60947-2
DC125V
Service [Ics] % of [Icu]
Trip
mechanism Thermal Adjustable instantaneous
& Protection magnetic
characteristics
Direct mounting by screw
Both line & load side
Mounting
for
Plug-in
Switchboard Line side only
Screw
Terminal connection
Bus bar
Auxiliary switch
AUX
Trip alarm switch
ALT
Signal
Shunt trip
SHT
Under voltage trip
UVT
Operating Surface type TFG
handle
Extended type TFH
Operating Motor operator
MOT
Accessories
Mechanical interlock MIF
Padlock plate
PLD
Mounting Plug-in mounting base TDM
Terminal bus bar
TBB
Cage terminal block CTB
Terminal
Terminal cover
TCF
Interpole barrier
TQQ
Durability Mechanical operation
(times)
Electrical operation
Width
a
b
Height
Dimensions
3P
c
Depth
(mm)
d
Weight ( , breaker only) 3P

(6-7-8-9-10-11-12-13) In

1)

25,000
10,000
105
165
86.5
112
1.8

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Supplied as standard component

26

(5-6-7-8-9-10) In

1)

25,000
10,000
105
165
86.5
112
2.0

MCCB

| Q-class (for nuclear power plant application) / HBL type 100-225AF |


HBL103

HBL203

100AF
3
IP20
A

225AF
3
IP20
A

overload, inst., short-circuit instantaneous, short-circuit


15,20,30,40,
2.5,3.2,6.3,12.5,
50,60,75,100
20,32,50,63,80,100
AC750
AC690
DC500
8
U1)
UQ1)
UM1)
UMQ1)
25
25
25
25
85
85
85
85
100
100
100
100
150
150
150
150
200
200
200
200
100
100
100
100
100
100
100
100
100

overload, inst., short-circuit instantaneous, short-circuit

Model

Figure

Ampere frame size


Number of poles (P)
Degree of protection (with terminal cover)
Utilization category
Suitability of isolation
Protection
Rated current (A)
Rated insulation voltage [Ui] (V)
Rating
Rated operational voltage [Ue] (V)
Rated impulse withstand voltage [Uimp] (kV)
Recognition code for order
AC660/690V, 50-60Hz
Rated
AC480/500V, 50-60Hz
short-circuit Ultimate AC440/460V, 50-60Hz
breaking
[Icu]
AC380/415V, 50-60Hz
capacity
(kA r.m.s.) AC220/240V, 50-60Hz
DC250V
IEC 60947-2
DC125V
K 60947-2
Service [Ics] % of [Icu]
Trip mechanism Thermal Fixed thermal,
& Protection
Fixed instantaneous INST
characteristics magnetic Adjustable instantaneous
Non-E1
Q-class
E1
Mounting Direct mounting by screw
Screw
Terminal connection
Bus bar
Auxiliary switch
AUX
Trip alarm switch
ALT
Signal
Shunt trip
SHT
Under voltage trip
UVT
Operating
Surface type TFG
handle
Operating Motor operator
MOT
Accessories
Mechanical interlock MIF
Padlock plate
PLD
Mounting Plug-in mounting base TDM
Terminal bus bar
TBB
Cage terminal block CTB
Terminal
Terminal cover
TCF
Interpole barrier
TQQ
Durability Mechanical operation
(times)
Electrical operation
a
Width
b
Height
Dimensions
3P
c
Depth
(mm)
d
Weight ( , breaker only) 3P

125,150,175,200,225
AC750
AC690
DC500
8
U1)
25
85
100
150
200
100
100

10 In

UQ1)
25
85
100
150
200
100
100

UM1)
25
85
100
150
200
100
100

UMQ1)
25
85
100
150
200
100
100

100
10 In

(6-7-8-9-10-11-12-13) In

(5-6-7-8-9-10) In

2)

2)

2)

2)

2)

2)

2)

2)

3)

3)

3)

3)

25,000
10,000
105
165
86.5
112
1.8

25,000
10,000
105
165
86.5
112
2.0

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) U: non-E1 class UQ: E1 class UM: non-E1 class, motor protection UMQ: E1 class, motor protection
2) Signal accessories shall be installed in breaker before ex-working. 3) Supplied as standard component
Molded Case Circuit Breaker_ 27

U-Series

Molded Case Circuit Breaker

Rating Overview
| Switch disconnector / UAD type 50-100AF |
Model

UAD50C

UAD50S

UAD100R

Figure

Ampere frame size

50AF

Number of poles (P)

100AF

IP20

IP20

IP20

Conventional thermal current [Ith] (A)

50

50

100

Rated current (A)

50

50

100

AC690

AC690

AC690

Degree of protection (with terminal cover)


Utilization category
Suitability of isolation

Rated insulation voltage [Ui] (V)


Rating

Durability

AC660

AC660

AC660

DC250

DC250

DC250

Rated impulse withstand voltage [Uimp] (kV)

Rated short-circuit making capacity [Icm] (kA peak at AC460V)

17

52.5

52.5

Rated short-time withstand current for 1sec. [Icw] (kA r.m.s.)

Mechanical operation (times)

25,000

25,000

25,000

Electrical operation (times)

15,000

15,000

10,000

Rated operational voltage [Ue] (V)

Direct mounting by screw


Mounting

Plug-in

Both line & load side


for
Switchboard Line side only
for Distribution board

DIN-rail
Terminal connection

Signal

with DIN-rail adaptor


Screw
Auxiliary switch

AUX

Trip alarm switch

ALT

Shunt trip

SHT

Under voltage trip

UVT

Operating Surface type


handle
Extended type

TFH

Accessories Operating Motor operator

Mounting
Terminal

MOT

Mechanical interlock

MIF

Padlock plate

PLD

DIN-rail adaptor

DRA

Plug-in mounting base

TDM

Terminal cover

TCF

Interpole barrier

TQQ

Dimensions
(mm)
3P

Weight ( , breaker only) 3P


1) Supplied as standard component

1)

1)

1)

Width

75

75

75

Height

130

130

130

Depth

60

60

60

28

TFG

82

82

82

0.65

0.78

0.78

MCCB

| Switch disconnector / UCD type 50-250AF |


Model

UCD50H

UCD100S

UCD100H

UCD160H

UCD250S

UCD250H

Ampere frame size

50AF

100AF

125AF

160AF

Number of poles (P)

IP20

IP20

IP20

IP20

IP20

IP20

Conventional thermal current [Ith] (A)

50

100

125

160

250

250

Rated current (A)

50

100

125

160

250

250

AC690

AC690

AC690

AC690

AC690

AC690

Figure

Degree of protection (with terminal cover)


Utilization category

250AF

Suitability of isolation

Rated insulation voltage [Ui] (V)


Rating

AC660

AC660

AC660

AC660

AC660

AC660

DC250

DC250

DC250

DC250

DC250

DC250

Rated short-circuit making capacity [Icm] (kA peak at AC460V)

105

73.5

105

105

73.5

105

Rated short-time withstand current for 1sec. [Icw] (kA r.m.s.)

Mechanical operation (times)

25,000

25,000

25,000

25,000

25,000

25,000

Electrical operation (times)

10,000

10,000

10,000

10,000

10,000

10,000

Rated operational voltage [Ue] (V)


Rated impulse withstand voltage [Uimp] (kV)

Durability

Direct mounting by screw


Mounting

Plug-in

Both line & load side


for
Switchboard Line side only
for Distribution board

Terminal connection

Signal

Screw
Bus bar
Auxiliary switch

AUX

Trip alarm switch

ALT

Shunt trip

SHT

Under voltage trip

UVT

Operating Surface type


handle
Extended type

TFH

Accessories Operating Motor operator

TFG
MOT

Mechanical interlock

MIF

Padlock plate

PLD

Mounting Plug-in mounting base


Cage terminal block
Terminal Terminal cover
Interpole barrier
Dimensions
(mm)
3P

CTB
TCF
TQQ

1)

1)

1)

1)

1)

1)

Width

90

90

90

105

105

105

Height

155

155

155

165

164

165

Depth

60

60

60

60

60

60

84.5

84.5

84.5

84.5

84

84.5

1.3

1.2

1.3

d
Weight ( , breaker only) 3P

TDM

1) Supplied as standard component

Molded Case Circuit Breaker_ 29

U-Series

Molded Case Circuit Breaker

Rating Overview
| Switch disconnector / UCD type 400-1250AF |
Model

UCD400S

UCD630S

UCD800S

UCD1000S

UCD1250S

Ampere frame size

400AF

630AF

800AF

1000AF

1250AF

Number of poles (P)

IP20

IP20

IP20

IP201)

IP201)

Conventional thermal current [Ith] (A)

400

630

800

1,000

1,250

Rated current (A)

400

630

800

1,000

1,250

AC690

AC690

AC690

AC750

AC750

AC690

AC690
8

Figure

Degree of protection (with terminal cover)


Utilization category
Suitability of isolation

Rated insulation voltage [Ui] (V)


Rating

AC660

AC660

AC660

DC250

DC250

DC250

Rated short-circuit making capacity [Icm] (kA peak at AC460V)

187

187

187

165

165

Rated short-time withstand current for 1sec. [Icw] (kA r.m.s.)

6.3

10

12.5

Mechanical operation (times)

20,000

20,000

10,000

10,000

10,000

Electrical operation (times)

6,000

6,000

3,000

3,000

3,000

Rated operational voltage [Ue] (V)


Rated impulse withstand voltage [Uimp] (kV)

Durability

Direct mounting by screw


Mounting

Plug-in

Terminal connection

Signal

Accessories Operating

Both line & load side


for
Switchboard Line side only
Screw
Bus bar
Auxiliary switch

AUX

Trip alarm switch

ALT

Shunt trip

SHT

Under voltage trip

UVT

Operating Surface type


handle
Extended type

TFH

Motor operator

MOT

Mechanical interlock

MIF

Padlock plate

PLD

Extension handle

THA

Mounting Plug-in mounting base


Terminal bus bar
Terminal

TFG

CTB
TCF

Interpole barrier

TQQ

2)

2)

3)

3)

2)

2)

2)

2)

2)

Width

140

210

210

210

210

Height

257

280

280

370

370

Depth

110

110

110

110

110

145

145

145

159

159

4.5

9.5

9.5

13

13.5

d
Weight ( , breaker only) 3P
1) Without terminal bus bar
2) Supplied as standard component
3) Supplied as standard component that attached in breaker

30

2)

TBB

Terminal cover

3P

2)

TDM

Cage terminal block

Dimensions
(mm)

2)

MCCB

| Switch disconnector / UPD type 125-630AF |


Model

UPD100S

UPD160S

UPD250S

UPD400S

UPD630S

Ampere frame size

125AF

160AF

250AF

400AF

630AF

Number of poles (P)

IP20

IP20

IP20

IP20

IP20

Conventional thermal current [Ith] (A)

125

160

250

400

630

Rated current (A)

125

160

250

400

630

AC750

AC750

AC750

AC750

AC750

AC690

AC690

Figure

Degree of protection (with terminal cover)


Utilization category
Suitability of isolation

Rated insulation voltage [Ui] (V)


Rating

AC690

AC690

AC690

DC500

DC500

DC500

Rated short-circuit making capacity [Icm] (kA peak at AC460V)

200

200

200

200

200

Rated short-time withstand current for 1sec. [Icw] (kA r.m.s.)

1.6

2.5

6.3

Mechanical operation (times)

25,000

25,000

25,000

20,000

20,000

Electrical operation (times)

10,000

10,000

10,000

6,000

6,000

Rated operational voltage [Ue] (V)


Rated impulse withstand voltage [Uimp] (kV)

Durability

Direct mounting by screw


Mounting

Plug-in

Terminal connection

Signal

Accessories

Operating

Both line & load side


for
Switchboard Line side only
Screw
Bus bar
Auxiliary switch

AUX

Trip alarm switch

ALT

Shunt trip

SHT

Under voltage trip

UVT

Operating Surface type


handle
Extended type

TFH

Motor operator

MOT

Mechanical interlock

MIF

Padlock plate

PLD

Extension handle

THA

Mounting Plug-in mounting base


Terminal bus bar
Terminal

Dimensions
(mm)

TFG

TBB
CTB

Terminal cover

TCF

Interpole barrier

TQQ

1)

1)

1)

1)

1)

Width

105

105

105

140

140

Height

165

165

165

255

255

Depth

86.5

86.5

86.5

117

117

112

112

112

159.5

159.5

1.8

d
Weight ( , breaker only) 3P

1)

TDM

Cage terminal block

3P

1)

1) Supplied as standard component

Molded Case Circuit Breaker_ 31

U-Series

Molded Case Circuit Breaker

Rating Overview
| Miniature type / Molded case circuit breaker 30-100AF |
Model

UMB30

UMB50

UDB30

UDB50

UDB100

Ampere frame size

30AF

50AF

30AF

50AF

100AF

Number of poles (P)

2, 3

2, 3

2, 3

Degree of protection

IP20

IP20

IP20

IP20

IP20

Utilization category

overload,
short-circuit

overload,
short-circuit

overload,
short-circuit

overload,
short-circuit

overload,
short-circuit

15, 20, 30

15, 20,
30, 40, 50

31), 5, 10,
15, 20, 30

5, 10, 15,
20, 30, 40, 50

15, 20, 30, 40,


50, 60, 75, 100

Rated insulation voltage [Ui] (V)

AC250

AC250

AC460

AC460

AC460

Rated operational voltage [Ue] (V)

AC220

AC220

2P: AC220
3P: AC220/460

2P: AC220
3P: AC220/460

2P: AC220
3P: AC220/460

Figure

Protection

Rated current (A)

Rating

Rated impulse withstand voltage [Uimp] (kV)


Recognition code for order

AC220/240V, 50-60Hz

5-10A: 2.5
15-30A: 5

AC440/460V, 50-60Hz
Rated
short-circuit Ultimate
[Icu]
breaking
(kA r.m.s.) AC380/415V, 50-60Hz
capacity
IEC 60947-2
K 60947-2

2.5

Service [Ics] % of [Icu]

10

50

10

5-10A: 2.5
15-30A: 5

2.5

5-10A: 2.5
15-30A: 5

2.55

5-10A: 2.5
15-30A: 5

2.5

5-10A: 5
15-30A:10

5-10A: 5
15-30A:10

10

50

50

50

50

Hydraulic magnetic
Trip
mechanism Thermal magnetic
Direct mounting by screw
Mounting
DIN-rail
Terminal connection

Accessories

Signal

Screw
Auxiliary switch

AUX

Trip alarm switch

ALT

Shunt trip

SHT

Terminal Interpole barrier

Dimensions
(mm)

TQQ

Width

33

35

35

50/75

50/75

752)/75

Height

70

80

80

96

96

96

Depth

42

60

60

60

60

60

57

76

76

80

80

80

0.1

0.13

0.15

0.2/0.35

0.2/0.35

0.2/0.35

2/3P
d

Weight (kg, breaker only) 2/3P

- KS certified products. English nameplate and 50Hz marking are not available.
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) 3A is not applicable for UDB30H. 2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.

32

MCCB

| Miniature type / Earth leakage circuit breaker 30-100AF |


Model

UMG30

UMG50

UDG30

UDG50

UDG100

Ampere frame size

30AF

50AF

30AF

50AF

100AF

Number of poles (P)

2, 3

2, 3

2, 3

Degree of protection

IP20

IP20

IP20

IP20

IP20

Utilization category

earth leakage,
overload,
short-circuit

earth leakage,
overload,
short-circuit

earth leakage,
overload,
short-circuit

earth leakage,
overload,
short-circuit

15, 20, 30

15, 20,
30, 40, 50

31), 5, 10,
15, 20, 30

5, 10, 15,
20, 30, 40, 50

15, 20, 30, 40,


50, 60, 75, 100

Rated residual current [I n] (mA)

15, 30

15, 30

15, 30

15, 30

30, 100

Rated insulation voltage [Ui] (V)

AC250

AC250

AC460

AC460

AC460

Rated operational voltage [Ue] (V)

AC220

AC220

2P: AC220
3P: AC220/460

2P: AC220
3P: AC220/460

Figure

Protection

Rated current (A)

Rating

Rated impulse withstand voltage [Uimp] (kV)


Rated operating time (sec.)
Recognition code for order

Rated
AC440/460V, 50-60Hz
short-circuit Ultimate
breaking
[Icu]
capacity
(kA r.m.s.) AC380/415V, 50-60Hz
IEC 60947-2
K 60947-2

AC220/240V, 50-60Hz

2.5

0.03

0.03

0.03

0.03

2.5

5-10A: 2.5
15-30A: 5

2.5

5-10A: 2.5
15-30A: 5

2.5

2.5

5-10A: 2.5
15-30A: 5

2.5

5-10A: 2.5
15-30A: 5

2.5

5-10A: 5
15-30A: 10

5-10A: 5
15-30A: 10

10

10

10
50

by current
transformer

Earth leakage detection


Earth
leakage
protection Earth leakage test button
Earth leakage indicator

2P: AC220
3P: AC220/460

0.03

50

Service [Ics] % of [Icu]

earth leakage,
overload,
short-circuit

by current
transformer

50

50

50

by current
transformer

by current
transformer

by current
transformer

Hydraulic magnetic
Trip
mechanism Thermal magnetic
Direct mounting by screw

Mounting

DIN-rail
Terminal connection
Accessories

Signal

Screw
Auxiliary switch

AUX

Trip alarm switch

ALT

Terminal Interpole barrier

Width

33

35

35

50/75

50/75

752)/75

Height

70

80

80

96

96

96

Depth

42

60

60

60

60

60

a
Dimensions
(mm)

2/3P

d
Weight (kg, breaker only) 2/3P

TQQ

57

76

76

80

80

80

0.1

0.13

0.15

0.33/0.44

0.33/0.44

0.46/0.63

- KS certified products. English nameplate and 50Hz marking are not available.
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) 3A is not applicable for UDG30H. 2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.
Molded Case Circuit Breaker_ 33

Specifications and Standard Order Codes

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UAB type / 30AF |
UAB30C 7.5/5kA
UAB30R 14/10kA

UAB30C

Number of poles (P)


Degree of protection (with terminal cover)
Utilization category
Suitability of isolation
Protection
Rated current (A)
Rated insulation voltage [Ui] (V)
Rating
Rated operational voltage [Ue] (V)
Rated impulse withstand voltage [Uimp] (kV)
AC600/660V, 50-60Hz
Rated
short-circuit
AC480/500V, 50-60Hz
Ultimate
breaking
AC440/460V, 50-60Hz
[Icu]
capacity
AC380/415V, 50-60Hz
(kA r.m.s.)
AC220/240V, 50-60Hz
IEC 60947-2
K 60947-2
Service [Ics] % of [Icu]
Trip mechanism
& Protection
characteristics

Hydraulic
magnetic

Fixed thermal,
Fixed instantaneous

UAB30R

2, 3
IP20
A
overload, inst., short-circuit
3,5,10,15,20,30
5,10,15,20,30
AC690
AC660
6
2.5
5
2.5
7.5
5
10
7.5/5
14/10
10
25
50

INST

12 In

Direct mounting by screw


Both line & load side
for
Switchboard Line side only
for Distribution board
Terminal connection
Screw
Mechanical operation
Durability
(times)
Electrical operation
a
Width
b
Height
Dimensions
2/3P
(mm)
c
Depth
d
Weight (kg, breaker only)
2/3P
Mounting

1)
1)

Plug-in

1)

25,000
15,000
50/75
130
60
82
0.45/0.65

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker

Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip1)
Under voltage trip2)

1C, right-hand-side
2C, right-hand-side
AUX 10A R1
AUX 10A R2
1C, right-hand-side
ALT 10A R1
DC24V
DC100-110V
SHT 10A A
SHT 10A C
DC24V
DC100-110V
UVT 10A J
UVT 10A L

AC100-120V
SHT 10A F
AC100-120V
UVT 10A N

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.

36

AC200-230V
AC200-230V
UVT 10A P

AC380-415V
SHT 10A H
AC380-415V
UVT 10A Q

AC440-480V
AC440-480V
UVT 10A R

MCCB

Operating
Power supply direction
S type
Operating Surface
L type
1)
handle
S type
Extended
L type

Upper
TFG 10AS U4
TFG 10AL U4

Right
TFG 10AS R4
TFH 10AS
TFH 10AL
AC/DC110V
MOT 10A ADC110

DC24V
MOT 10A DC24

Motor operator2)

2 pole

Mechanical interlock
Padlock plate3)

Left
TFG 10AS L4
TFG 10AL L4

AC/DC220V
MOT 10A ADC220
3 pole
MIF 10A 3

PLD 10UA

1) Available for 3P breaker. For detail type information, please refer to page 197-205. 2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.

Mounting

Plug-in1)

Structure
Mounting base
Connection 2C contact
block 2)
3C contact
Conn. block barrier

For both line & load side


TDM 10AP
CBM 10AB 2

For line side only


TDM 10AF

CBM 10AB 3
CBM BARR

1) Available for 3P breaker


2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.

Terminal
3EA/SET
CTB 10A 3S50

Cage terminal block

2 pole
3 pole
TCF 10AP 2
TCF 10AP 3
TQQ 10A 3PLINE

Terminal cover1)
Interpole barrier 2)

2EA/SET

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA

Standard order code and unit


Fixed thermal & fixed instantaneous / Hydraulic magnetic trip
40/45
Model /
Breaking
capacity at
AC380/415V

2 pole

3 pole

Rated
current

Code

Unit
(EA)

3A

UAB30C 2PT4S0000C 00003

30

UAB30C 3PT4S0000C 00003

20

5A

UAB30C 2PT4S0000C 00005

30

UAB30C 3PT4S0000C 00005

20

UAB30C

10A

UAB30C 2PT4S0000C 00010

30

UAB30C 3PT4S0000C 00010

20

7.5/5kA

15A

UAB30C 2PT4S0000C 00015

30

UAB30C 3PT4S0000C 00015

20

20A

UAB30C 2PT4S0000C 00020

30

UAB30C 3PT4S0000C 00020

20

30A

UAB30C 2PT4S0000C 00030

30

UAB30C 3PT4S0000C 00030

20

UAB30R
14/10kA

Code

Unit
(EA)

5A

UAB30R 2PT4S0000C 00005

30

UAB30R 3PT4S0000C 00005

20

10A

UAB30R 2PT4S0000C 00010

30

UAB30R 3PT4S0000C 00010

20

15A

UAB30R 2PT4S0000C 00015

30

UAB30R 3PT4S0000C 00015

20

20A

UAB30R 2PT4S0000C 00020

30

UAB30R 3PT4S0000C 00020

20

30A

UAB30R 2PT4S0000C 00030

30

UAB30R 3PT4S0000C 00030

20

Specification

Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M1

Molded Case Circuit Breaker_ 37

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UAB type / 50AF |
UAB50C 7.5/5kA
UAB50R 14/10kA

UAB50C

Number of poles (P)


Degree of protection (with terminal cover)
Utilization category
Suitability of isolation
Protection
Rated current (A)
Rated insulation voltage [Ui] (V)
Rating
Rated operational voltage [Ue] (V)
Rated impulse withstand voltage [Uimp] (kV)
AC600/660V, 50-60Hz
Rated
short-circuit
AC480/500V, 50-60Hz
Ultimate
breaking
AC440/460V, 50-60Hz
[Icu]
capacity
(kA r.m.s.)
AC380/415V, 50-60Hz
IEC 60947-2
AC220/240V, 50-60Hz
K 60947-2
Service [Ics] % of [Icu]
Trip mechanism
& Protection
characteristics

Hydraulic
magnetic

Fixed thermal,
Fixed instantaneous

UAB50R

2, 3, 4
IP20
A
overload, inst., short-circuit
5,10,15,20,30,40,50
AC690
AC660
6
2.5
2.5
5
7.5/5
10

5
7.5
10
14/10
25
50

INST

12 In

Direct mounting by screw


Both line & load side
for
Switchboard Line side only
for Distribution board
Terminal connection
Screw
Mechanical operation
Durability
(times)
Electrical operation
a
Width
b
Height
Dimensions
2/3/4P
(mm)
c
Depth
d
Weight (kg, breaker only)
2/3/4P
Mounting

1)

Plug-in

1)
1)

25,000
15,000
50/75/100
130
60
82
0.45/0.65/0.85

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker

Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip1)
Under voltage trip2)

1C, right-hand-side
2C, right-hand-side
AUX 10A R1
AUX 10A R2
1C, right-hand-side
ALT 10A R1
DC24V
DC100-110V
SHT 10A A
SHT 10A C
DC24V
DC100-110V
UVT 10A J
UVT 10A L

AC100-120V
SHT 10A F
AC100-120V
UVT 10A N

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.

38

AC200-230V
AC200-230V
UVT 10A P

AC380-415V
SHT 10A H
AC380-415V
UVT 10A Q

AC440-480V
AC440-480V
UVT 10A R

MCCB

Operating
Upper
TFG 10AS U4
TFG 10AL U4

Power supply direction


S type
Operating Surface
L type
1)
handle
S type
Extended
L type

Right
TFG 10AS R4
TFH 10AS
TFH 10AL
AC/DC110V
MOT 10A ADC110
3 pole
MIF 10A 3
PLD 10UA

DC24V
MOT 10A DC24
2 pole

Motor operator 2)
Mechanical interlock

Left
TFG 10AS L4
TFG 10AL L4

Padlock plate3)

AC/DC220V
MOT 10A ADC220
4 pole
MIF 10A 4

1) Available for 3P, 4P breaker. For detail type information, please refer to page 197-205. 2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.

Mounting
Structure
Mounting base
Plug-in1) Connection 2C contact
block 2)
3C contact
Conn. block barrier

For both line & load side


TDM 10AP
CBM 10AB 2
CBM 10AB 3
CBM BARR

For line side only


TDM 10AF

1) Available for 3P breaker


2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.

Terminal
3EA/SET
CTB 10A 3S50
2 pole
TCF 10AP 2

Cage terminal block


Terminal cover1)
Interpole barrier 2)

2EA/SET

4EA/SET
CTB 10A 4S50
3 pole
4 pole
TCF 10AP 3
TCF 10AP 4
TQQ 10A 3PLINE

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA

Standard order code and unit


Fixed thermal & fixed instantaneous / Hydraulic magnetic trip
40/45
Model /
Breaking capacity at
AC380/415V

UAB50C
7.5/5kA

UAB50R
14/10kA

Rated
current

2 pole
Code

Unit
(EA)

3 pole
Code

Unit
(EA)

4 pole
Code

Unit
(EA)

Specification Category

5A

UAB50C 2PT4S0000C 00005

30

UAB50C 3PT4S0000C 00005

20

UAB50C 4PT4S0000C 00005

16

10A

UAB50C 2PT4S0000C 00010

30

UAB50C 3PT4S0000C 00010

20

UAB50C 4PT4S0000C 00010

16

15A

UAB50C 2PT4S0000C 00015

30

UAB50C 3PT4S0000C 00015

20

UAB50C 4PT4S0000C 00015

16

20A

UAB50C 2PT4S0000C 00020

30

UAB50C 3PT4S0000C 00020

20

UAB50C 4PT4S0000C 00020

16

30A

UAB50C 2PT4S0000C 00030

30

UAB50C 3PT4S0000C 00030

20

UAB50C 4PT4S0000C 00030

16

40A

UAB50C 2PT4S0000C 00040

30

UAB50C 3PT4S0000C 00040

20

50A

UAB50C 2PT4S0000C 00050

30

UAB50C 3PT4S0000C 00050

20

5A

UAB50R 2PT4S0000C 00005

30

UAB50R 3PT4S0000C 00005

20

10A

UAB50R 2PT4S0000C 00010

30

UAB50R 3PT4S0000C 00010

20

Screw type
terminal
connection,
UAB50R 4PT4S0000C 00005 16 No option,
50/60Hz
UAB50R 4PT4S0000C 00010 16

15A

UAB50R 2PT4S0000C 00015

30

UAB50R 3PT4S0000C 00015

20

UAB50R 4PT4S0000C 00015 16

20A

UAB50R 2PT4S0000C 00020

30

UAB50R 3PT4S0000C 00020

20

UAB50R 4PT4S0000C 00020 16

30A

UAB50R 2PT4S0000C 00030

30

UAB50R 3PT4S0000C 00030

20

UAB50R 4PT4S0000C 00030 16

40A

UAB50R 2PT4S0000C 00040

30

UAB50R 3PT4S0000C 00040

20

UAB50R 4PT4S0000C 00040 16

50A

UAB50R 2PT4S0000C 00050

30

UAB50R 3PT4S0000C 00050

20

UAB50R 4PT4S0000C 00050 16

UAB50C 4PT4S0000C 00040

16

UAB50C 4PT4S0000C 00050

16

MCCB
/M1

Molded Case Circuit Breaker_ 39

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UAB type / 50AF |
UAB50S 25kA
UAB50H 30kA

UAB50S

UAB50H

Number of poles (P)

2, 3, 4

Degree of protection (with terminal cover)

IP20

Utilization category

Suitability of isolation
Protection

overload, inst., short-circuit


Rated current (A)

15,16,20,25,30,32,40,50

Rated insulation voltage [Ui] (V)

AC690

Rating

AC660

Rated operational voltage [Ue] (V)

DC250

Rated impulse withstand voltage [Uimp] (kV)

Rated
short-circuit
breaking
capacity

Ultimate
[Icu]
(kA r.m.s.)

IEC 60947-2
K 60947-2

7.5

10

AC480/500V, 50-60Hz

7.5

14

AC440/460V, 50-60Hz

21

25

AC380/415V, 50-60Hz

25

30

AC220/240V, 50-60Hz

42

50

DC250V

10

14

DC125V

15

20

Service [Ics] % of [Icu]


Trip
Thermal
mechanism
& Protection
magnetic
characteristics

AC600/660V, 50-60Hz

25

Fixed thermal,
Fixed instantaneous
Adjustable thermal,
Fixed instantaneous

INST

15-32A: 20 In, 40-100A: 10 In

LTD

(0.8-0.9-1) In 2)

INST

15-32A: 20 In, 40-100A: 10 In

Direct mounting by screw

Mounting

Plug-in

DIN-rail
Terminal connection

Both line & load side


for
Switchboard Line side only

1)

for Distribution board

1)

1)

with DIN-rail adaptor


Screw

Durability

Mechanical operation

25,000

(times)

Electrical operation

15,000

Dimensions
(mm)

2/3/4P

Width

50/75/100

Height

130

Depth

60

d
Weight (kg, breaker only)

2/3/4P

82
0.6/0.78/0.96

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker 2) Available for 3P, 4P breaker

40

MCCB

Accessories
Signal
1C, right-hand-side

Auxiliary switch
Trip alarm switch
Shunt trip

1)

Under voltage trip2)

1C, left-hand-side

AUX 10UA R1

AUX 10UA L1

1C, right-hand-side

1C, left-hand-side

ALT 10UA R1

ALT 10UA L1

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

SHT 10UA A

SHT 10UA F

SHT 10UA H

SHT 10UA B

SHT 10UA D

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

AC440-480V

UVT 10UA J

UVT 10UA L

UVT 10UA N

UVT 10UA P

UVT 10UA Q

UVT 10UA R

AC440-480V

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.

Operating
Upper

Right

Left

S type

TFG 10UAS U4

TFG 10UAS R4

TFG 10UAS L4

L type

TFG 10UAL U4

Power supply direction


Operating Surface
handle1)
Extended

TFG 10UAL L4

S type

TFH 10UAS

L type

TFH 10UAL

Motor operator2)

DC24V

AC/DC110V

AC/DC220V

MOT 10UA DC24

MOT 10UA ADC110

MOT 10UA ADC220

2 pole

Mechanical interlock
Padlock plate3)

3 pole

4 pole

MIF 10UA 3

MIF 10UA 4

PLD 10UA

1) Available for 3P, 4P breaker. For detail type information, please refer to page 197-205.
2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.

Mounting
DRA 10UA

DIN-rail adaptor
Structure
Mounting base
Plug-in1) Connection 2C contact
block2)

3C contact

Conn. block barrier

For both line & load side

For line side only

TDM 10AP

TDM 10AF

CBM 10AB 2
CBM 10AB 3
CBM BARR

1) Available for 3P breaker


2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.

Terminal
3EA/SET

Cage terminal block

CTB 10A 3S50

Terminal cover1)
Interpole barrier2)

2EA/SET

4EA/SET
CTB 10A 4S50

2 pole

3 pole

4 pole

TCF 10AP 2

TCF 10AP 3

TCF 10AP 4

TQQ 10A 3PLINE

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA

Molded Case Circuit Breaker_ 41

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


Standard order code and unit
Fixed thermal & fixed instantaneous / Thermal magnetic trip
40/45
Model /
Breaking
capacity at
AC380/415V

Rated
current

2 pole

3 pole

4 pole

Code

Unit
(EA)

Code

Unit
(EA)

15A

UAB50S 2PT4S0000C 00015

30

UAB50S 3PT4S0000C 00015

20

UAB50S 4PT4S0000C 00015

16

16A

UAB50S 2PT4S0000C 00016

30

UAB50S 3PT4S0000C 00016

20

UAB50S 4PT4S0000C 00016

16

Code

Unit
(EA)

Specification Category

20A

UAB50S 2PT4S0000C 00020

30

UAB50S 3PT4S0000C 00020

20

UAB50S 4PT4S0000C 00020

16

UAB50S

25A

UAB50S 2PT4S0000C 00025

30

UAB50S 3PT4S0000C 00025

20

UAB50S 4PT4S0000C 00025

16

25kA

30A

UAB50S 2PT4S0000C 00030

30

UAB50S 3PT4S0000C 00030

20

UAB50S 4PT4S0000C 00030

16

32A

UAB50S 2PT4S0000C 00032

30

UAB50S 3PT4S0000C 00032

20

UAB50S 4PT4S0000C 00032

16

40A

UAB50S 2PT4S0000C 00040

30

UAB50S 3PT4S0000C 00040

20

UAB50S 4PT4S0000C 00040

50A

UAB50S 2PT4S0000C 00050

30

UAB50S 3PT4S0000C 00050

20

UAB50S 4PT4S0000C 00050

15A

UAB50H 2PT4S0000C 00015

30

UAB50H 3PT4S0000C 00015 20

UAB50H 4PT4S0000C 00015

16A

UAB50H 2PT4S0000C 00016

30

UAB50H 3PT4S0000C 00016 20

UAB50H 4PT4S0000C 00016

16 Screw type
16 terminal
connection,
16 No option,
16 50/60Hz

20A

UAB50H 2PT4S0000C 00020

30

UAB50H 3PT4S0000C 00020 20

UAB50H 4PT4S0000C 00020

16

UAB50H

25A

UAB50H 2PT4S0000C 00025

30

UAB50H 3PT4S0000C 00025 20

UAB50H 4PT4S0000C 00025

16

30kA

30A

UAB50H 2PT4S0000C 00030

30

UAB50H 3PT4S0000C 00030 20

UAB50H 4PT4S0000C 00030

16

32A

UAB50H 2PT4S0000C 00032

30

UAB50H 3PT4S0000C 00032 20

UAB50H 4PT4S0000C 00032

16

40A

UAB50H 2PT4S0000C 00040

30

UAB50H 3PT4S0000C 00040 20

UAB50H 4PT4S0000C 00040

16

50A

UAB50H 2PT4S0000C 00050

30

UAB50H 3PT4S0000C 00050 20

UAB50H 4PT4S0000C 00050

16

MCCB
/M2

50
Model /
Breaking
capacity at
AC380/415V

42

Rated
current

2 pole

3 pole

4 pole

Unit
(EA)

Code

Unit
(EA)

15A

UAB50S 2PT5S0000C 00015

30

UAB50S 3PT5S0000C 00015

20

UAB50S 4PT5S0000C 00015

16

16A

UAB50S 2PT5S0000C 00016

30

UAB50S 3PT5S0000C 00016

20

UAB50S 4PT5S0000C 00016

16

20A

UAB50S 2PT5S0000C 00020

30

UAB50S 3PT5S0000C 00020

20

UAB50S 4PT5S0000C 00020

16

UAB50S

25A

UAB50S 2PT5S0000C 00025

30

UAB50S 3PT5S0000C 00025

20

UAB50S 4PT5S0000C 00025

16

25kA

30A

UAB50S 2PT5S0000C 00030

30

UAB50S 3PT5S0000C 00030

20

UAB50S 4PT5S0000C 00030

16

32A

UAB50S 2PT5S0000C 00032

30

UAB50S 3PT5S0000C 00032

20

UAB50S 4PT5S0000C 00032

16

40A

UAB50S 2PT5S0000C 00040

30

UAB50S 3PT5S0000C 00040

20

UAB50S 4PT5S0000C 00040

50A

UAB50S 2PT5S0000C 00050

30

UAB50S 3PT5S0000C 00050

20

UAB50S 4PT5S0000C 00050

15A

UAB50H 2PT5S0000C 00015

30

UAB50H 3PT5S0000C 00015 20

UAB50H 4PT5S0000C 00015

16A

UAB50H 2PT5S0000C 00016

30

UAB50H 3PT5S0000C 00016 20

UAB50H 4PT5S0000C 00016

16 Screw type
16 terminal
connection,
16 No option,
16 50/60Hz

Code

Unit
(EA)

Specification Category

Code

20A

UAB50H 2PT5S0000C 00020

30

UAB50H 3PT5S0000C 00020 20

UAB50H 4PT5S0000C 00020

16

UAB50H

25A

UAB50H 2PT5S0000C 00025

30

UAB50H 3PT5S0000C 00025 20

UAB50H 4PT5S0000C 00025

16

30kA

30A

UAB50H 2PT5S0000C 00030

30

UAB50H 3PT5S0000C 00030 20

UAB50H 4PT5S0000C 00030

16

32A

UAB50H 2PT5S0000C 00032

30

UAB50H 3PT5S0000C 00032 20

UAB50H 4PT5S0000C 00032

16

40A

UAB50H 2PT5S0000C 00040

30

UAB50H 3PT5S0000C 00040 20

UAB50H 4PT5S0000C 00040

16

50A

UAB50H 2PT5S0000C 00050

30

UAB50H 3PT5S0000C 00050 20

UAB50H 4PT5S0000C 00050

16

MCCB
/M2

MCCB

Adjustable thermal & fixed instantaneous / Thermal magnetic trip


40/45
Model /
Breaking
capacity at
AC380/415V

Rated
current

3 pole

4 pole

Code

Unit
(EA)

Code

Unit
(EA)

15A

UAB50S 3PT4S0000C 00015F

20

UAB50S 4PT4S0000C 00015F

16

16A

UAB50S 3PT4S0000C 00016F

20

UAB50S 4PT4S0000C 00016F

16

20A

UAB50S 3PT4S0000C 00020F

20

UAB50S 4PT4S0000C 00020F

16

UAB50S

25A

UAB50S 3PT4S0000C 00025F

20

UAB50S 4PT4S0000C 00025F

16

25kA

30A

UAB50S 3PT4S0000C 00030F

20

UAB50S 4PT4S0000C 00030F

16

32A

UAB50S 3PT4S0000C 00032F

20

UAB50S 4PT4S0000C 00032F

16

40A

UAB50S 3PT4S0000C 00040F

20

UAB50S 4PT4S0000C 00040F

16

50A

UAB50S 3PT4S0000C 00050F

20

UAB50S 4PT4S0000C 00050F

16

15A

UAB50H 3PT4S0000C 00015F

20

UAB50H 4PT4S0000C 00015F

16

16A

UAB50H 3PT4S0000C 00016F

20

UAB50H 4PT4S0000C 00016F

16

20A

UAB50H 3PT4S0000C 00020F

20

UAB50H 4PT4S0000C 00020F

16

UAB50H

25A

UAB50H 3PT4S0000C 00025F

20

UAB50H 4PT4S0000C 00025F

16

30kA

30A

UAB50H 3PT4S0000C 00030F

20

UAB50H 4PT4S0000C 00030F

16

32A

UAB50H 3PT4S0000C 00032F

20

UAB50H 4PT4S0000C 00032F

16

40A

UAB50H 3PT4S0000C 00040F

20

UAB50H 4PT4S0000C 00040F

16

50A

UAB50H 3PT4S0000C 00050F

20

UAB50H 4PT4S0000C 00050F

16

Specification

Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

Specification

Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

50
Model /
Breaking
capacity at
AC380/415V

Rated
current

3 pole

4 pole

Code

Unit
(EA)

Code

Unit
(EA)

15A

UAB50S 3PT5S0000C 00015F

20

UAB50S 4PT5S0000C 00015F

16

16A

UAB50S 3PT5S0000C 00016F

20

UAB50S 4PT5S0000C 00016F

16

20A

UAB50S 3PT5S0000C 00020F

20

UAB50S 4PT5S0000C 00020F

16

UAB50S

25A

UAB50S 3PT5S0000C 00025F

20

UAB50S 4PT5S0000C 00025F

16

25kA

30A

UAB50S 3PT5S0000C 00030F

20

UAB50S 4PT5S0000C 00030F

16

32A

UAB50S 3PT5S0000C 00032F

20

UAB50S 4PT5S0000C 00032F

16

40A

UAB50S 3PT5S0000C 00040F

20

UAB50S 4PT5S0000C 00040F

16

50A

UAB50S 3PT5S0000C 00050F

20

UAB50S 4PT5S0000C 00050F

16

15A

UAB50H 3PT5S0000C 00015F

20

UAB50H 4PT5S0000C 00015F

16

16A

UAB50H 3PT5S0000C 00016F

20

UAB50H 4PT5S0000C 00016F

16

20A

UAB50H 3PT5S0000C 00020F

20

UAB50H 4PT5S0000C 00020F

16

UAB50H

25A

UAB50H 3PT5S0000C 00025F

20

UAB50H 4PT5S0000C 00025F

16

30kA

30A

UAB50H 3PT5S0000C 00030F

20

UAB50H 4PT5S0000C 00030F

16

32A

UAB50H 3PT5S0000C 00032F

20

UAB50H 4PT5S0000C 00032F

16

40A

UAB50H 3PT5S0000C 00040F

20

UAB50H 4PT5S0000C 00040F

16

50A

UAB50H 3PT5S0000C 00050F

20

UAB50H 4PT5S0000C 00050F

16

Molded Case Circuit Breaker_ 43

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UAB type / 60AF |
UAB60C 7.5/5kA
UAB60R 14/10kA

UAB60C

2, 3, 4
IP20
A

Number of poles (P)


Degree of protection (with terminal cover)
Utilization category
Suitability of isolation
Protection
Rated current (A)
Rated insulation voltage [Ui] (V)
Rating
Rated operational voltage [Ue] (V)
Rated impulse withstand voltage [Uimp] (kV)
Rated
short-circuit
breaking
capacity
IEC 60947-2
K 60947-2
Trip mechanism
& Protection
characteristics

Fixed thermal,
Fixed instantaneous

overload, inst., short-circuit


5,10,15,20,30,40,50,60
AC690
AC660
6
2.5
2.5
5
7.5/5
10

AC600/660V, 50-60Hz
AC480/500V, 50-60Hz
Ultimate
[Icu]
AC440/460V, 50-60Hz
(kA r.m.s.)
AC380/415V, 50-60Hz
AC220/240V, 50-60Hz
Service [Ics] % of [Icu]
Hydraulic
magnetic

UAB60R

5
7.5
10
14/10
25
50

INST

12 In

Direct mounting by screw


Both line & load side
for
Switchboard Line side only
for Distribution board
Terminal connection
Screw
Mechanical operation
Durability
(times)
Electrical operation
a
Width
b
Height
Dimensions
2/3/4P
(mm)
c
Depth
d
Mounting

Plug-in

Weight (kg, breaker only)

1)
1)

25,000
10,000
50/75/100
130
60
82
0.45/0.65/0.85

2/3/4P

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker

Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip1)
Under voltage trip2)

1C, right-hand-side
2C, right-hand-side
AUX 10A R1
AUX 10A R2
1C, right-hand-side
ALT 10A R1
DC24V
DC100-110V
SHT 10A A
SHT 10A C
DC24V
DC100-110V
UVT 10A J
UVT 10A L

AC100-120V
SHT 10A F
AC100-120V
UVT 10A N

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.

44

AC200-230V
AC200-230V
UVT 10A P

AC380-415V
SHT 10A H
AC380-415V
UVT 10A Q

AC440-480V
AC440-480V
UVT 10A R

MCCB

Operating
Power supply direction
S type
Operating Surface
L type
1)
handle
S type
Extended
L type

Upper
TFG 10AS U4
TFG 10AL U4

Right
TFG 10AS R4
TFH 10AS
TFH 10AL
AC/DC110V
MOT 10A ADC110
3 pole
MIF 10A 3
PLD 10UA

DC24V
MOT 10A DC24
2 pole

Motor operator 2)
Mechanical interlock

Left
TFG 10AS L4
TFG 10AL L4

Padlock plate3)

AC/DC220V
MOT 10A ADC220
4 pole
MIF 10A 4

1) Available for 3P, 4P breaker. For detail type information, please refer to page 197-205. 2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.

Mounting

Plug-in1)

Structure
Mounting base
Connection 2C contact
3C contact
block2)
Conn. block barrier

For both line & load side


TDM 10AP
CBM 10AB 2
CBM 10AB 3
CBM BARR

For line side only


TDM 10AF

1) Available for 3P, 4P breaker


2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.

Terminal
Cage terminal block

5-50A
60A

Terminal cover1)
Interpole barrier2)

3EA/SET
CTB 10A 3S50
CTB 10A 3S100
2 pole
TCF 10AP 2

2EA/SET

4EA/SET
CTB 10A 4S50
CTB 10A 4S100
3 pole
4 pole
TCF 10AP 3
TCF 10AP 4
TQQ 10A 3PLINE

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA

Standard order code and unit


Fixed thermal & fixed instantaneous / Hydraulic magnetic trip
40/45
Model /
Breaking capacity at
AC380/415V

Rated
current

2 pole
Code

Unit
(EA)

3 pole
Code

Unit
(EA)

4 pole
Code

Unit
(EA)

Specification Category

5A

UAB60C 2PT4S0000C 00005

30

UAB60C 3PT4S0000C 00005

20

UAB60C 4PT4S0000C 00005

16

10A

UAB60C 2PT4S0000C 00010

30

UAB60C 3PT4S0000C 00010

20

UAB60C 4PT4S0000C 00010

16

15A

UAB60C 2PT4S0000C 00015

30

UAB60C 3PT4S0000C 00015

20

UAB60C 4PT4S0000C 00015

16

UAB60C

20A

UAB60C 2PT4S0000C 00020

30

UAB60C 3PT4S0000C 00020

20

UAB60C 4PT4S0000C 00020

16

7.5/5kA

30A

UAB60C 2PT4S0000C 00030

30

UAB60C 3PT4S0000C 00030

20

UAB60C 4PT4S0000C 00030

16

40A

UAB60C 2PT4S0000C 00040

30

UAB60C 3PT4S0000C 00040

20

UAB60C 4PT4S0000C 00040

16

50A

UAB60C 2PT4S0000C 00050

30

UAB60C 3PT4S0000C 00050

20

UAB60C 4PT4S0000C 00050

60A

UAB60C 2PT4S0000C 00060

30

UAB60C 3PT4S0000C 00060

20

UAB60C 4PT4S0000C 00060

5A

UAB60R 2PT4S0000C 00005

30

UAB60R 3PT4S0000C 00005

20

UAB60R 4PT4S0000C 00005

10A

UAB60R 2PT4S0000C 00010

30

UAB60R 3PT4S0000C 00010

20

UAB60R 4PT4S0000C 00010

15A

UAB60R 2PT4S0000C 00015

30

UAB60R 3PT4S0000C 00015

20

UAB60R 4PT4S0000C 00015

16 Screw type
16 terminal
connection,
16 No option,
16
50/60Hz
16

UAB60R

20A

UAB60R 2PT4S0000C 00020

30

UAB60R 3PT4S0000C 00020

20

UAB60R 4PT4S0000C 00020

16

14/10kA

30A

UAB60R 2PT4S0000C 00030

30

UAB60R 3PT4S0000C 00030

20

UAB60R 4PT4S0000C 00030

16

40A

UAB60R 2PT4S0000C 00040

30

UAB60R 3PT4S0000C 00040

20

UAB60R 4PT4S0000C 00040

16

50A

UAB60R 2PT4S0000C 00050

30

UAB60R 3PT4S0000C 00050

20

UAB60R 4PT4S0000C 00050

16

60A

UAB60R 2PT4S0000C 00060

30

UAB60R 3PT4S0000C 00060

20

UAB60R 4PT4S0000C 00060

16

MCCB
/M1

Molded Case Circuit Breaker_ 45

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UAB type / 100AF |
UAB100C 14/10kA

UAB100C

Number of poles (P)


Degree of protection (with terminal cover)
Utilization category
Suitability of isolation
Protection
Rated current (A)
Rated insulation voltage [Ui] (V)
Rating
Rated operational voltage [Ue] (V)
Rated impulse withstand voltage [Uimp] (kV)
AC600/660V, 50-60Hz
Rated
short-circuit
AC480/500V, 50-60Hz
Ultimate
breaking
AC440/460V, 50-60Hz
[Icu]
capacity
(kA r.m.s.)
AC380/415V, 50-60Hz
IEC 60947-2
AC220/240V, 50-60Hz
K 60947-2
Service [Ics] % of [Icu]
Trip mechanism
& Protection
characteristics

Hydraulic
magnetic

Fixed thermal,
Fixed instantaneous

2, 3, 4
IP20
A
overload, inst., short-circuit
5,10,15,20,30,40,50,60,75,100
AC690
AC660
6
5
7.5
10
14/10
25
50

INST

12 In

Direct mounting by screw


Both line & load side
for
Switchboard Line side only
for Distribution board
Terminal connection
Screw
Mechanical operation
Durability
(times)
Electrical operation
a
Width
b
Height
Dimensions
2/3/4P
(mm)
c
Depth
d
Weight (kg, breaker only)
2/3/4P
Mounting

1)

Plug-in

1)

25,000
10,000
50/75/100
130
60
82
0.45/0.65/0.85

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker

Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip1)
Under voltage trip2)

1C, right-hand-side
2C, right-hand-side
AUX 10A R1
AUX 10A R2
1C, right-hand-side
ALT 10A R1
DC24V
DC100-110V
SHT 10A A
SHT 10A C
DC24V
DC100-110V
UVT 10A J
UVT 10A L

AC100-120V
SHT 10A F
AC100-120V
UVT 10A N

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.

46

AC200-230V
AC200-230V
UVT 10A P

AC380-415V
SHT 10A H
AC380-415V
UVT 10A Q

AC440-480V
AC440-480V
UVT 10A R

MCCB

Operating
Power supply direction
S type
Operating Surface
L type
1)
handle
S type
Extended
L type

Upper
TFG 10AS U4
TFG 10AL U4

Right
TFG 10AS R4
TFH 10AS
TFH 10AL
AC/DC110V
MOT 10A ADC110
3 pole
MIF 10A 3
PLD 10UA

DC24V
MOT 10A DC24
2 pole

Motor operator 2)
Mechanical interlock

Left
TFG 10AS L4
TFG 10AL L4

Padlock plate3)

AC/DC220V
MOT 10A ADC220
4 pole
MIF 10A 4

1) Available for 3P, 4P breaker. For detail type information, please refer to page 197-205. 2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.

Mounting

Plug-in1)

Structure
Mounting base
Connection 2C contact
block2)
3C contact
Conn. block barrier

For both line & load side


TDM 10AP
CBM 10AB 2
CBM 10AB 3
CBM BARR

For line side only


TDM 10AF

1) Available for 3P, 4P breaker


2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.

Terminal
Cage terminal block

5-50A
60-100A

Terminal cover1)
Interpole barrier2)

3EA/SET
CTB 10A 3S50
CTB 10A 3S100
2 pole
TCF 10AP 2

2EA/SET

4EA/SET
CTB 10A 4S50
CTB 10A 4S100
3 pole
4 pole
TCF 10AP 3
TCF 10AP 4
TQQ 10A 3PLINE

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA

Standard order code and unit


Fixed thermal & fixed instantaneous / Hydraulic magnetic trip
40/45
Model /
Breaking capacity at
AC380/415V

Rated
current

2 pole
Code

3 pole
Unit
(EA)

Code

4 pole
Unit
(EA)

Code

Unit
(EA)

5A

UAB100C 2PT4S0000C 00005 30 UAB100C 3PT4S0000C 00005 20 UAB100C 4PT4S0000C 00005 16

10A

UAB100C 2PT4S0000C 00010 30 UAB100C 3PT4S0000C 00010 20 UAB100C 4PT4S0000C 00010 16

15A

UAB100C 2PT4S0000C 00015 30 UAB100C 3PT4S0000C 00015 20 UAB100C 4PT4S0000C 00015 16

20A

UAB100C 2PT4S0000C 00020 30 UAB100C 3PT4S0000C 00020 20 UAB100C 4PT4S0000C 00020 16

UAB100C

30A

UAB100C 2PT4S0000C 00030 30 UAB100C 3PT4S0000C 00030 20 UAB100C 4PT4S0000C 00030 16

14/10kA

40A

Specification Category

50A

Screw type
terminal
connection,
UAB100C 2PT4S0000C 00040 30 UAB100C 3PT4S0000C 00040 20 UAB100C 4PT4S0000C 00040 16 No option,
50/60Hz
UAB100C 2PT4S0000C 00050 30 UAB100C 3PT4S0000C 00050 20 UAB100C 4PT4S0000C 00050 16

60A

UAB100C 2PT4S0000C 00060 30 UAB100C 3PT4S0000C 00060 20 UAB100C 4PT4S0000C 00060 16

75A

UAB100C 2PT4S0000C 00075 30 UAB100C 3PT4S0000C 00075 20 UAB100C 4PT4S0000C 00075 16

100A

UAB100C 2PT4S0000C 00100 30 UAB100C 3PT4S0000C 00100 20 UAB100C 4PT4S0000C 00100 16

MCCB
/M1

Molded Case Circuit Breaker_ 47

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UAB type / 100AF |
UAB100R 25kA
UAB100S 30kA

UAB100S

UAB100R

Number of poles (P)

2, 3, 4

Degree of protection (with terminal cover)

IP20
A

Utilization category
Suitability of isolation

overload, inst., short-circuit

Protection

15,16,20,25,30,32,40,50,60,63,75,80,100

Rated current (A)

AC690

Rated insulation voltage [Ui] (V)


Rating

AC660

Rated operational voltage [Ue] (V)

DC250
Rated impulse withstand voltage [Uimp] (kV)

Rated
short-circuit
breaking
capacity

Ultimate
[Icu]
(kA r.m.s.)

IEC 60947-2
K 60947-2

7.5

10

AC480/500V, 50-60Hz

7.5

14

AC440/460V, 50-60Hz

21

25

AC380/415V, 50-60Hz

25

30

AC220/240V, 50-60Hz

42

50

DC250V

10

14

DC125V

15

20

Service [Ics] % of [Icu]


Trip
mechanism
Thermal
& Protection
magnetic
characteristics

AC600/660V, 50-60Hz

25

Fixed thermal,
Fixed instantaneous
Adjustable thermal,
Fixed instantaneous

INST

15-32A: 20 In, 40-100A: 10 In

LTD

(0.8-0.9-1) In 2)

INST

15-32A: 20 In, 40-100A: 10 In

Direct mounting by screw

Mounting

Plug-in

Both line & load side


for
Switchboard Line side only

1)

for Distribution board


DIN-rail
Terminal connection
Durability
(times)

1)

with DIN-rail adaptor


Screw

Mechanical operation

25,000

Electrical operation

10,000

Dimensions
(mm)

2/3/4P

Width

50/75/100

Height

130

Depth

60

d
Weight (kg, breaker only)

2/3/4P

82
0.6/0.78/0.96

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker 2) Available for 3P, 4P breaker

48

MCCB

Accessories
Signal
1C, right-hand-side 1C, left-hand-side

Auxiliary switch

AUX 10UA R1

Trip alarm switch


Shunt trip

AUX 10UA L1

1C, right-hand-side 1C, left-hand-side

1)

Under voltage trip2)

ALT 10UA R1

ALT 10UA L1

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

SHT 10UA A

SHT 10UA F

SHT 10UA H

SHT 10UA B

SHT 10UA D

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

AC440-480V

UVT 10UA J

UVT 10UA L

UVT 10UA N

UVT 10UA P

UVT 10UA Q

UVT 10UA R

AC440-480V

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.

Operating
Upper

Right

Left

S type

TFG 10UAS U4

TFG 10UAS R4

TFG 10UAS L4

L type

TFG 10UAL U4

Power supply direction


Operating Surface
handle1)
Extended

TFG 10UAL L4
TFH 10UAS

S type

TFH 10UAL

L type
Motor operator 2)

DC24V

AC/DC110V

AC/DC220V

MOT 10UA DC24

MOT 10UA ADC110

MOT 10UA ADC220

2 pole

Mechanical interlock
Padlock plate3)

3 pole

4 pole

MIF 10UA 3

MIF 10UA 4

PLD 10UA

1) Available for 3P, 4P breaker. For detail type information, please refer to page 197-205.
2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.

Mounting
DRA 10UA

DIN-rail adaptor
Structure
Mounting base
Plug-in1) Connection 2C contact
block2)

3C contact

Conn. block barrier

For both line & load side

For line side only

TDM 10AP

TDM 10AF

CBM 10AB 2
CBM 10AB 3
CBM BARR

1) Available for 3P breaker


2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.

Terminal
Cage terminal block

3EA/SET

4EA/SET

15-50A

CTB 10A 3S50

CTB 10A 4S50

60-100A

CTB 10A 3S100

Terminal cover1)
Interpole barrier2)

2EA/SET

CTB 10A 4S100

2 pole

3 pole

4 pole

TCF 10AP 2

TCF 10AP 3

TCF 10AP 4

TQQ 10A 3PLINE

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA

Molded Case Circuit Breaker_ 49

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


Standard order code and unit
Fixed thermal & fixed instantaneous / Thermal magnetic trip
40/45
Model /
Breaking capacity at
AC380/415V

UAB100R
25kA

UAB100S
30kA

2 pole

3 pole

4 pole

Rated
current

Code

Unit
(EA)

Code

Unit
(EA)

15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A

UAB100R 2PT4S0000C 00015


UAB100R 2PT4S0000C 00016
UAB100R 2PT4S0000C 00020
UAB100R 2PT4S0000C 00025
UAB100R 2PT4S0000C 00030
UAB100R 2PT4S0000C 00032
UAB100R 2PT4S0000C 00040
UAB100R 2PT4S0000C 00050
UAB100R 2PT4S0000C 00060
UAB100R 2PT4S0000C 00063
UAB100R 2PT4S0000C 00075
UAB100R 2PT4S0000C 00080
UAB100R 2PT4S0000C 00100
UAB100S 2PT4S0000C 00015
UAB100S 2PT4S0000C 00016
UAB100S 2PT4S0000C 00020
UAB100S 2PT4S0000C 00025
UAB100S 2PT4S0000C 00030
UAB100S 2PT4S0000C 00032
UAB100S 2PT4S0000C 00040
UAB100S 2PT4S0000C 00050
UAB100S 2PT4S0000C 00060
UAB100S 2PT4S0000C 00063
UAB100S 2PT4S0000C 00075
UAB100S 2PT4S0000C 00080
UAB100S 2PT4S0000C 00100

30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

UAB100R 3PT4S0000C 00015


UAB100R 3PT4S0000C 00016
UAB100R 3PT4S0000C 00020
UAB100R 3PT4S0000C 00025
UAB100R 3PT4S0000C 00030
UAB100R 3PT4S0000C 00032
UAB100R 3PT4S0000C 00040
UAB100R 3PT4S0000C 00050
UAB100R 3PT4S0000C 00060
UAB100R 3PT4S0000C 00063
UAB100R 3PT4S0000C 00075
UAB100R 3PT4S0000C 00080
UAB100R 3PT4S0000C 00100
UAB100S 3PT4S0000C 00015
UAB100S 3PT4S0000C 00016
UAB100S 3PT4S0000C 00020
UAB100S 3PT4S0000C 00025
UAB100S 3PT4S0000C 00030
UAB100S 3PT4S0000C 00032
UAB100S 3PT4S0000C 00040
UAB100S 3PT4S0000C 00050
UAB100S 3PT4S0000C 00060
UAB100S 3PT4S0000C 00063
UAB100S 3PT4S0000C 00075
UAB100S 3PT4S0000C 00080
UAB100S 3PT4S0000C 00100

20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

Rated
current

Code

Unit
(EA)

Code

Unit
(EA)

15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A

UAB100R 2PT5S0000C 00015


UAB100R 2PT5S0000C 00016
UAB100R 2PT5S0000C 00020
UAB100R 2PT5S0000C 00025
UAB100R 2PT5S0000C 00030
UAB100R 2PT5S0000C 00032
UAB100R 2PT5S0000C 00040
UAB100R 2PT5S0000C 00050
UAB100R 2PT5S0000C 00060
UAB100R 2PT5S0000C 00063
UAB100R 2PT5S0000C 00075
UAB100R 2PT5S0000C 00080
UAB100R 2PT5S0000C 00100
UAB100S 2PT5S0000C 00015
UAB100S 2PT5S0000C 00016
UAB100S 2PT5S0000C 00020
UAB100S 2PT5S0000C 00025
UAB100S 2PT5S0000C 00030
UAB100S 2PT5S0000C 00032
UAB100S 2PT5S0000C 00040
UAB100S 2PT5S0000C 00050
UAB100S 2PT5S0000C 00060
UAB100S 2PT5S0000C 00063
UAB100S 2PT5S0000C 00075
UAB100S 2PT5S0000C 00080
UAB100S 2PT5S0000C 00100

30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30

UAB100R 3PT5S0000C 00015


UAB100R 3PT5S0000C 00016
UAB100R 3PT5S0000C 00020
UAB100R 3PT5S0000C 00025
UAB100R 3PT5S0000C 00030
UAB100R 3PT5S0000C 00032
UAB100R 3PT5S0000C 00040
UAB100R 3PT5S0000C 00050
UAB100R 3PT5S0000C 00060
UAB100R 3PT5S0000C 00063
UAB100R 3PT5S0000C 00075
UAB100R 3PT5S0000C 00080
UAB100R 3PT5S0000C 00100
UAB100S 3PT5S0000C 00015
UAB100S 3PT5S0000C 00016
UAB100S 3PT5S0000C 00020
UAB100S 3PT5S0000C 00025
UAB100S 3PT5S0000C 00030
UAB100S 3PT5S0000C 00032
UAB100S 3PT5S0000C 00040
UAB100S 3PT5S0000C 00050
UAB100S 3PT5S0000C 00060
UAB100S 3PT5S0000C 00063
UAB100S 3PT5S0000C 00075
UAB100S 3PT5S0000C 00080
UAB100S 3PT5S0000C 00100

20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

Code
UAB100R 4PT4S0000C 00015
UAB100R 4PT4S0000C 00016
UAB100R 4PT4S0000C 00020
UAB100R 4PT4S0000C 00025
UAB100R 4PT4S0000C 00030
UAB100R 4PT4S0000C 00032
UAB100R 4PT4S0000C 00040
UAB100R 4PT4S0000C 00050
UAB100R 4PT4S0000C 00060
UAB100R 4PT4S0000C 00063
UAB100R 4PT4S0000C 00075
UAB100R 4PT4S0000C 00080
UAB100R 4PT4S0000C 00100
UAB100S 4PT4S0000C 00015
UAB100S 4PT4S0000C 00016
UAB100S 4PT4S0000C 00020
UAB100S 4PT4S0000C 00025
UAB100S 4PT4S0000C 00030
UAB100S 4PT4S0000C 00032
UAB100S 4PT4S0000C 00040
UAB100S 4PT4S0000C 00050
UAB100S 4PT4S0000C 00060
UAB100S 4PT4S0000C 00063
UAB100S 4PT4S0000C 00075
UAB100S 4PT4S0000C 00080
UAB100S 4PT4S0000C 00100

Unit
(EA)

Specification Category

16
16
16
16
16
16
16
16
16
16
16
16 Screw type
terminal
16
connection,
16
No option,
16
50/60Hz
16
16
16
16
16
16
16
16
16
16
16

MCCB
/M2

50
Model /
Breaking capacity at
AC380/415V

UAB100R
25kA

UAB100S
30kA

50

2 pole

3 pole

4 pole
Code
UAB100R 4PT5S0000C 00015
UAB100R 4PT5S0000C 00016
UAB100R 4PT5S0000C 00020
UAB100R 4PT5S0000C 00025
UAB100R 4PT5S0000C 00030
UAB100R 4PT5S0000C 00032
UAB100R 4PT5S0000C 00040
UAB100R 4PT5S0000C 00050
UAB100R 4PT5S0000C 00060
UAB100R 4PT5S0000C 00063
UAB100R 4PT5S0000C 00075
UAB100R 4PT5S0000C 00080
UAB100R 4PT5S0000C 00100
UAB100S 4PT5S0000C 00015
UAB100S 4PT5S0000C 00016
UAB100S 4PT5S0000C 00020
UAB100S 4PT5S0000C 00025
UAB100S 4PT5S0000C 00030
UAB100S 4PT5S0000C 00032
UAB100S 4PT5S0000C 00040
UAB100S 4PT5S0000C 00050
UAB100S 4PT5S0000C 00060
UAB100S 4PT5S0000C 00063
UAB100S 4PT5S0000C 00075
UAB100S 4PT5S0000C 00080
UAB100S 4PT5S0000C 00100

Unit
(EA)

Specification Category

16
16
16
16
16
16
16
16
16
16
16
16 Screw type
terminal
16
connection,
16
No option,
16
50/60Hz
16
16
16
16
16
16
16
16
16
16
16

MCCB
/M2

MCCB

Adjustable thermal & fixed instantaneous / Thermal magnetic trip


40/45
Model /
Breaking capacity at
AC380/415V

UAB100R
25kA

UAB100S
30kA

Rated
current
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A

3 pole
Code
UAB100R 3PT4S0000C 00015F
UAB100R 3PT4S0000C 00016F
UAB100R 3PT4S0000C 00020F
UAB100R 3PT4S0000C 00025F
UAB100R 3PT4S0000C 00030F
UAB100R 3PT4S0000C 00032F
UAB100R 3PT4S0000C 00040F
UAB100R 3PT4S0000C 00050F
UAB100R 3PT4S0000C 00060F
UAB100R 3PT4S0000C 00063F
UAB100R 3PT4S0000C 00075F
UAB100R 3PT4S0000C 00080F
UAB100R 3PT4S0000C 00100F
UAB100S 3PT4S0000C 00015F
UAB100S 3PT4S0000C 00016F
UAB100S 3PT4S0000C 00020F
UAB100S 3PT4S0000C 00025F
UAB100S 3PT4S0000C 00030F
UAB100S 3PT4S0000C 00032F
UAB100S 3PT4S0000C 00040F
UAB100S 3PT4S0000C 00050F
UAB100S 3PT4S0000C 00060F
UAB100S 3PT4S0000C 00063F
UAB100S 3PT4S0000C 00075F
UAB100S 3PT4S0000C 00080F
UAB100S 3PT4S0000C 00100F

4 pole
Unit
(EA)

20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

Code
UAB100R 4PT4S0000C 00015F
UAB100R 4PT4S0000C 00016F
UAB100R 4PT4S0000C 00020F
UAB100R 4PT4S0000C 00025F
UAB100R 4PT4S0000C 00030F
UAB100R 4PT4S0000C 00032F
UAB100R 4PT4S0000C 00040F
UAB100R 4PT4S0000C 00050F
UAB100R 4PT4S0000C 00060F
UAB100R 4PT4S0000C 00063F
UAB100R 4PT4S0000C 00075F
UAB100R 4PT4S0000C 00080F
UAB100R 4PT4S0000C 00100F
UAB100S 4PT4S0000C 00015F
UAB100S 4PT4S0000C 00016F
UAB100S 4PT4S0000C 00020F
UAB100S 4PT4S0000C 00025F
UAB100S 4PT4S0000C 00030F
UAB100S 4PT4S0000C 00032F
UAB100S 4PT4S0000C 00040F
UAB100S 4PT4S0000C 00050F
UAB100S 4PT4S0000C 00060F
UAB100S 4PT4S0000C 00063F
UAB100S 4PT4S0000C 00075F
UAB100S 4PT4S0000C 00080F
UAB100S 4PT4S0000C 00100F

Unit
(EA)

16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

Specification

Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

Specification

Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

50
Model /
Breaking capacity at
AC380/415V

UAB100R
25kA

UAB100S
30kA

Rated
current
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A

3 pole
Code
UAB100R 3PT5S0000C 00015F
UAB100R 3PT5S0000C 00016F
UAB100R 3PT5S0000C 00020F
UAB100R 3PT5S0000C 00025F
UAB100R 3PT5S0000C 00030F
UAB100R 3PT5S0000C 00032F
UAB100R 3PT5S0000C 00040F
UAB100R 3PT5S0000C 00050F
UAB100R 3PT5S0000C 00060F
UAB100R 3PT5S0000C 00063F
UAB100R 3PT5S0000C 00075F
UAB100R 3PT5S0000C 00080F
UAB100R 3PT5S0000C 00100F
UAB100S 3PT5S0000C 00015F
UAB100S 3PT5S0000C 00016F
UAB100S 3PT5S0000C 00020F
UAB100S 3PT5S0000C 00025F
UAB100S 3PT5S0000C 00030F
UAB100S 3PT5S0000C 00032F
UAB100S 3PT5S0000C 00040F
UAB100S 3PT5S0000C 00050F
UAB100S 3PT5S0000C 00060F
UAB100S 3PT5S0000C 00063F
UAB100S 3PT5S0000C 00075F
UAB100S 3PT5S0000C 00080F
UAB100S 3PT5S0000C 00100F

4 pole
Unit
(EA)

20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20

Code
UAB100R 4PT5S0000C 00015F
UAB100R 4PT5S0000C 00016F
UAB100R 4PT5S0000C 00020F
UAB100R 4PT5S0000C 00025F
UAB100R 4PT5S0000C 00030F
UAB100R 4PT5S0000C 00032F
UAB100R 4PT5S0000C 00040F
UAB100R 4PT5S0000C 00050F
UAB100R 4PT5S0000C 00060F
UAB100R 4PT5S0000C 00063F
UAB100R 4PT5S0000C 00075F
UAB100R 4PT5S0000C 00080F
UAB100R 4PT5S0000C 00100F
UAB100S 4PT5S0000C 00015F
UAB100S 4PT5S0000C 00016F
UAB100S 4PT5S0000C 00020F
UAB100S 4PT5S0000C 00025F
UAB100S 4PT5S0000C 00030F
UAB100S 4PT5S0000C 00032F
UAB100S 4PT5S0000C 00040F
UAB100S 4PT5S0000C 00050F
UAB100S 4PT5S0000C 00060F
UAB100S 4PT5S0000C 00063F
UAB100S 4PT5S0000C 00075F
UAB100S 4PT5S0000C 00080F
UAB100S 4PT5S0000C 00100F

Unit
(EA)

16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

Molded Case Circuit Breaker_ 51

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UCB type / 50AF |
UCB50R 30/25kA

UCB50R

Number of poles (P)


Degree of protection (with terminal cover)
Utilization category
Suitability of isolation
Protection
Rated current (A)
Rated insulation voltage [Ui] (V)
Rating

Rated
short-circuit
breaking
capacity
IEC 60947-2
K 60947-2
Trip mechanism
& Protection
characteristics

2, 3, 4
IP20
A
overload, inst., short-circuit
15,20,30,40,50
AC690
AC660
DC250
6
10
14
25
30/25
50
14
20
50

Rated operational voltage [Ue] (V)


Rated impulse withstand voltage [Uimp] (kV)
AC600/660V, 50-60Hz
AC480/500V, 50-60Hz
AC440/460V, 50-60Hz
Ultimate
AC380/415V, 50-60Hz
[Icu]
(kA r.m.s.)
AC220/240V, 50-60Hz
DC250V
DC125V
Service [Ics] % of [Icu]
Thermal
magnetic

Fixed thermal,
Fixed instantaneous

INST

10 In

Direct mounting by screw


1)

Both line & load side


for
Switchboard Line side only
for Distribution board
Terminal connection
Screw
Mechanical operation
Durability
(times)
Electrical operation
a
Width
b
Height
Dimensions
2/3/4P
(mm)
c
Depth
d
Weight (kg, breaker only)
2/3/4P
Mounting

1)

Plug-in

1)

25,000
10,000
60/90/120
155
60
84.5
0.7/1.0/1.2

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker

Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip1)
Under voltage trip2)

52

1C, left-hand-side
AUX 10B L1
1C, left-hand-side
ALT 10B L1
DC24V
SHT 10B A
DC24V
UVT 10B J

DC100-110V
DC100-110V
UVT 10B L

AC100-120V
SHT 10B F
AC100-120V
UVT 10B N

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.

AC200-230V
AC200-230V
UVT 10B P

AC380-415V
SHT 10B H
AC380-415V
UVT 10B Q

AC440-480V
AC440-480V
UVT 10B R

MCCB

Operating
Power supply direction
S type
Operating Surface
L type
1)
handle
S type
Extended
L type

Upper
TFG 10BS U4
TFG 10BL U4

Right
TFG 10BS R4
TFH 10BS
TFH 10BL
AC/DC110V
MOT 10UB ADC110
3 pole
MIF 10UF 3
PLD 10UF

DC24V
MOT 10UB DC24
2 pole

Motor operator 2)
Mechanical interlock

Left
TFG 10BS L4
TFG 10BL L4

Padlock plate3)

AC/DC220V
MOT 10UB ADC220
4 pole
MIF 10UF 4

1) Available for 3P, 4P breaker. For detail type information, please refer to page 197-205. 2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.

Mounting

Plug-in1)

Structure
Mounting base
Connection 2C contact
block2)
3C contact
Conn. block barrier

For both line & load side


TDM 10BP
CBM 10AB 2
CBM 10AB 3
CBM BARR

For line side only


TDM 10BF

1) Available for 3P breaker


2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.

Terminal
3EA/SET
CTB 10B 3S
2 pole
TCF 10BP 2

Cage terminal block


Terminal cover1)
Interpole barrier 2)

2EA/SET

4EA/SET
CTB 10B 4S
3 pole
TCF 10BP 3
TQQ 10B 3PLINE

4 pole
TCF 10BP 4

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA

Standard order code and unit


Fixed thermal & fixed instantaneous / Thermal magnetic trip
40/45
Model /
Breaking capacity at
AC380/415V

UCB50R
30/25kA

Rated
current

2 pole
Code

3 pole
Unit
(EA)

4 pole

Code

Unit
(EA)

Code

Unit
(EA)

15A

UCB50R 2PT4S0000C 00015 16

UCB50R 3PT4S0000C 00015

10

UCB50R 4PT4S0000C 00015

20A

UCB50R 2PT4S0000C 00020 16

UCB50R 3PT4S0000C 00020

10

UCB50R 4PT4S0000C 00020

30A

UCB50R 2PT4S0000C 00030 16

UCB50R 3PT4S0000C 00030

10

UCB50R 4PT4S0000C 00030

40A

UCB50R 2PT4S0000C 00040 16

UCB50R 3PT4S0000C 00040

10

UCB50R 4PT4S0000C 00040

50A

UCB50R 2PT4S0000C 00050 16

UCB50R 3PT4S0000C 00050

10

UCB50R 4PT4S0000C 00050

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M1

50
Model /
Breaking capacity at
AC380/415V

UCB50R
30/25kA

2 pole

3 pole

4 pole

Rated
current

Code

15A

UCB50R 2PT5S0000C 00015

16 UCB50R 3PT5S0000C 00015

10

UCB50R 4PT5S0000C 00015

20A

UCB50R 2PT5S0000C 00020

16 UCB50R 3PT5S0000C 00020

10

UCB50R 4PT5S0000C 00020

30A

UCB50R 2PT5S0000C 00030

16 UCB50R 3PT5S0000C 00030

10

UCB50R 4PT5S0000C 00030

40A

UCB50R 2PT5S0000C 00040

16 UCB50R 3PT5S0000C 00040

10

UCB50R 4PT5S0000C 00040

50A

UCB50R 2PT5S0000C 00050

16 UCB50R 3PT5S0000C 00050

10

UCB50R 4PT5S0000C 00050

Unit
(EA)

Code

Unit
(EA)

Code

Unit
(EA)

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M1

Molded Case Circuit Breaker_ 53

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UCB type / 50AF |
UCB50H 42kA
UCB50L 50kA

UCB50H

UCB50L

Number of poles (P)

2, 3, 4

Degree of protection (with terminal cover)

IP20

Utilization category

Suitability of isolation
Protection

overload, inst., short-circuit


Rated current (A)

15,16,20,25,30,32,40,50

Rated insulation voltage [Ui] (V)


Rating

AC690
AC660

Rated operational voltage [Ue] (V)

DC250
Rated impulse withstand voltage [Uimp] (kV)

Rated
short-circuit
breaking
capacity

Ultimate
[Icu]
(kA r.m.s.)

IEC 60947-2
K 60947-2

AC600/660V, 50-60Hz

20

25

AC480/500V, 50-60Hz

30

35

AC440/460V, 50-60Hz

42

50

AC380/415V, 50-60Hz

42

50

AC220/240V, 50-60Hz

85

100

DC250V

25

40

DC125V

40

60

Service [Ics] % of [Icu]


Trip
mechanism
Thermal
& Protection
magnetic
characteristics

50

Fixed thermal,
Fixed instantaneous
Adjustable thermal,
Fixed instantaneous

INST

15-32A: 15 In, 40-50A: 10 In

LTD

(0.8-0.9-1) In

INST

15-32A: 15 In, 40-50A: 10 In

Direct mounting by screw


Mounting
Plug-in

Terminal connection
Durability
(times)

Both line & load side


for
Switchboard Line side only

1)

for Distribution board

1)

Screw

Mechanical operation

25,000

Electrical operation

Dimensions
(mm)

2/3/4P

10,000
a

Width

902)/90/120

Height

155

Depth

60

d
Weight (kg, breaker only)

1)

2/3/4P

84.5
0.9/1.0/1.3

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.

54

MCCB

Accessories
Signal
1C, left-hand-side 2C, left-hand-side

Auxiliary switch

AUX 12FG L1

AUX 12FG L2

1C, right-hand-side 1C, left-hand-side

Trip alarm switch


1)

Shunt trip

Under voltage trip2)

ALT 12FG R1

ALT 12FG L1

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

SHT 12FG A

SHT 12FG C

SHT 12FG F

SHT 12FG H

SHT 12FG B

SHT 12FG D

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

AC440-480V

UVT 12FG J

UVT 12FG L

UVT 12FG N

UVT 12FG P

UVT 12FG Q

UVT 12FG R

AC440-480V

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.

Operating
Upper

Right

Left

S type

TFG 10UFS U4

TFG 10UFS R4

TFG 10UFS L4

L type

TFG 10UFL U4

Power supply direction


Operating Surface
handle1)
Extended

TFG 10UFL L4
TFH 10UFS

S type

TFH 10UFL

L type
Motor operator 2)

DC24V

AC/DC110V

AC/DC220V

MOT 10F DC24

MOT 10F ADC110

MOT 10F ADC220

2 pole

3 pole

4 pole

MIF 10UF 3

MIF 10UF 4

Mechanical interlock
Padlock plate3)

PLD 10UF

1) For detail type information, please refer to page 197-205.


2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.

Mounting
Structure
Mounting base
Plug-in1) Connection 2C contact
block 2)

3C contact

Conn. block barrier

For both line & load side

For line side only

TDM 10BP

TDM 10BF

CBM 10AB 2
CBM 10AB 3
CBM BARR

1) Available for 3P breaker


2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.

Terminal
Cage terminal block
Terminal cover1)
Interpole barrier2)

2EA/SET

3EA/SET

4EA/SET

CTB 10B 3S

CTB 10B 4S

2 pole

3 pole

4 pole

TCF 10FP 3

TCF 10FP 3

TCF 10FP 4

TQQ 12FG 3PLINE

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 4EA, 3 pole 4EA, 4 pole 6EA

Molded Case Circuit Breaker_ 55

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


Standard order code and unit
Fixed thermal & fixed instantaneous / Thermal magnetic trip
40/45
Model /
Breaking
capacity at
AC380/415V

Rated
current

2 pole

3 pole

4 pole

Code

Unit
(EA)

Code

Unit
(EA)

15A

UCB50H 2PT4S0000C 00015

UCB50H 3PT4S0000C 00015

UCB50H 4PT4S0000C 00015

16A

UCB50H 2PT4S0000C 00016

UCB50H 3PT4S0000C 00016

UCB50H 4PT4S0000C 00016

Code

Unit
(EA)

20A

UCB50H 2PT4S0000C 00020

UCB50H 3PT4S0000C 00020

UCB50H 4PT4S0000C 00020

UCB50H

25A

UCB50H 2PT4S0000C 00025

UCB50H 3PT4S0000C 00025

UCB50H 4PT4S0000C 00025

42kA

30A

UCB50H 2PT4S0000C 00030

UCB50H 3PT4S0000C 00030

UCB50H 4PT4S0000C 00030

32A

UCB50H 2PT4S0000C 00032

UCB50H 3PT4S0000C 00032

UCB50H 4PT4S0000C 00032

40A

UCB50H 2PT4S0000C 00040

UCB50H 3PT4S0000C 00040

UCB50H 4PT4S0000C 00040

50A

UCB50H 2PT4S0000C 00050

UCB50H 3PT4S0000C 00050

UCB50H 4PT4S0000C 00050

15A

UCB50L 2PT4S0000C 00015

UCB50L 3PT4S0000C 00015

UCB50L 4PT4S0000C 00015

16A

UCB50L 2PT4S0000C 00016

UCB50L 3PT4S0000C 00016

UCB50L 4PT4S0000C 00016

20A

UCB50L 2PT4S0000C 00020

UCB50L 3PT4S0000C 00020

UCB50L 4PT4S0000C 00020

UCB50L

25A

UCB50L 2PT4S0000C 00025

UCB50L 3PT4S0000C 00025

UCB50L 4PT4S0000C 00025

50kA

30A

UCB50L 2PT4S0000C 00030

UCB50L 3PT4S0000C 00030

UCB50L 4PT4S0000C 00030

32A

UCB50L 2PT4S0000C 00032

UCB50L 3PT4S0000C 00032

UCB50L 4PT4S0000C 00032

40A

UCB50L 2PT4S0000C 00040

UCB50L 3PT4S0000C 00040

UCB50L 4PT4S0000C 00040

50A

UCB50L 2PT4S0000C 00050

UCB50L 3PT4S0000C 00050

UCB50L 4PT4S0000C 00050

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

50
Model /
Breaking
capacity at
AC380/415V

56

Rated
current

2 pole

3 pole

4 pole

Code

Unit
(EA)

Code

Unit
(EA)

15A

UCB50H 2PT5S0000C 00015

UCB50H 3PT5S0000C 00015

UCB50H 4PT5S0000C 00015

16A

UCB50H 2PT5S0000C 00016

UCB50H 3PT5S0000C 00016

UCB50H 4PT5S0000C 00016

20A

UCB50H 2PT5S0000C 00020

UCB50H 3PT5S0000C 00020

UCB50H 4PT5S0000C 00020

UCB50H

25A

UCB50H 2PT5S0000C 00025

UCB50H 3PT5S0000C 00025

UCB50H 4PT5S0000C 00025

42kA

30A

UCB50H 2PT5S0000C 00030

UCB50H 3PT5S0000C 00030

UCB50H 4PT5S0000C 00030

32A

UCB50H 2PT5S0000C 00032

UCB50H 3PT5S0000C 00032

UCB50H 4PT5S0000C 00032

40A

UCB50H 2PT5S0000C 00040

UCB50H 3PT5S0000C 00040

UCB50H 4PT5S0000C 00040

50A

UCB50H 2PT5S0000C 00050

UCB50H 3PT5S0000C 00050

UCB50H 4PT5S0000C 00050

15A

UCB50L 2PT5S0000C 00015

UCB50L 3PT5S0000C 00015

UCB50L 4PT5S0000C 00015

16A

UCB50L 2PT5S0000C 00016

UCB50L 3PT5S0000C 00016

UCB50L 4PT5S0000C 00016

Code

Unit
(EA)

20A

UCB50L 2PT5S0000C 00020

UCB50L 3PT5S0000C 00020

UCB50L 4PT5S0000C 00020

UCB50L

25A

UCB50L 2PT5S0000C 00025

UCB50L 3PT5S0000C 00025

UCB50L 4PT5S0000C 00025

50kA

30A

UCB50L 2PT5S0000C 00030

UCB50L 3PT5S0000C 00030

UCB50L 4PT5S0000C 00030

32A

UCB50L 2PT5S0000C 00032

UCB50L 3PT5S0000C 00032

UCB50L 4PT5S0000C 00032

40A

UCB50L 2PT5S0000C 00040

UCB50L 3PT5S0000C 00040

UCB50L 4PT5S0000C 00040

50A

UCB50L 2PT5S0000C 00050

UCB50L 3PT5S0000C 00050

UCB50L 4PT5S0000C 00050

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

MCCB

Adjustable thermal & fixed instantaneous / Thermal magnetic trip


40/45
Model /
Breaking
capacity at
AC380/415V

Rated
current

2 pole
Code

3 pole
Unit
(EA)

Code

4 pole
Unit
(EA)

Code

Unit
(EA)

15A

UCB50H 2PT4S0000C 00015F 8

UCB50H 3PT4S0000C 00015F 8

UCB50H 4PT4S0000C 00015F 6

16A

UCB50H 2PT4S0000C 00016F 8

UCB50H 3PT4S0000C 00016F 8

UCB50H 4PT4S0000C 00016F 6

20A

UCB50H 2PT4S0000C 00020F 8

UCB50H 3PT4S0000C 00020F 8

UCB50H 4PT4S0000C 00020F 6

UCB50H

25A

UCB50H 2PT4S0000C 00025F 8

UCB50H 3PT4S0000C 00025F 8

UCB50H 4PT4S0000C 00025F 6

42kA

30A

UCB50H 2PT4S0000C 00030F 8

UCB50H 3PT4S0000C 00030F 8

UCB50H 4PT4S0000C 00030F 6

32A

UCB50H 2PT4S0000C 00032F 8

UCB50H 3PT4S0000C 00032F 8

UCB50H 4PT4S0000C 00032F 6

40A

UCB50H 2PT4S0000C 00040F 8

UCB50H 3PT4S0000C 00040F 8

UCB50H 4PT4S0000C 00040F 6

50A

UCB50H 2PT4S0000C 00050F 8

UCB50H 3PT4S0000C 00050F 8

UCB50H 4PT4S0000C 00050F 6

15A

UCB50L 2PT4S0000C 00015F

UCB50L 3PT4S0000C 00015F 8

UCB50L 4PT4S0000C 00015F 6

16A

UCB50L 2PT4S0000C 00016F

UCB50L 3PT4S0000C 00016F 8

UCB50L 4PT4S0000C 00016F 6

20A

UCB50L 2PT4S0000C 00020F

UCB50L 3PT4S0000C 00020F 8

UCB50L 4PT4S0000C 00020F 6

UCB50L

25A

UCB50L 2PT4S0000C 00025F

UCB50L 3PT4S0000C 00025F 8

UCB50L 4PT4S0000C 00025F 6

50kA

30A

UCB50L 2PT4S0000C 00030F

UCB50L 3PT4S0000C 00030F 8

UCB50L 4PT4S0000C 00030F 6

32A

UCB50L 2PT4S0000C 00032F

UCB50L 3PT4S0000C 00032F 8

UCB50L 4PT4S0000C 00032F 6

40A

UCB50L 2PT4S0000C 00040F

UCB50L 3PT4S0000C 00040F 8

UCB50L 4PT4S0000C 00040F 6

50A

UCB50L 2PT4S0000C 00050F

UCB50L 3PT4S0000C 00050F 8

UCB50L 4PT4S0000C 00050F 6

3 pole

4 pole

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

50
Model /
Breaking
capacity at
AC380/415V

Rated
current

2 pole
Code

Unit
(EA)

Code

Unit
(EA)

15A

UCB50H 2PT5S0000C 00015F

UCB50H 3PT5S0000C 00015F 8

UCB50H 4PT5S0000C 00015F

16A

UCB50H 2PT5S0000C 00016F

20A

UCB50H 2PT5S0000C 00020F

UCB50H 3PT5S0000C 00016F 8

UCB50H 4PT5S0000C 00016F

UCB50H 3PT5S0000C 00020F 8

UCB50H 4PT5S0000C 00020F

UCB50H

25A

42kA

30A

UCB50H 2PT5S0000C 00025F

UCB50H 3PT5S0000C 00025F 8

UCB50H 4PT5S0000C 00025F

UCB50H 2PT5S0000C 00030F

UCB50H 3PT5S0000C 00030F 8

UCB50H 4PT5S0000C 00030F

32A

UCB50H 2PT5S0000C 00032F

UCB50H 3PT5S0000C 00032F 8

UCB50H 4PT5S0000C 00032F

40A

UCB50H 2PT5S0000C 00040F

UCB50H 3PT5S0000C 00040F 8

UCB50H 4PT5S0000C 00040F

50A

UCB50H 2PT5S0000C 00050F

UCB50H 3PT5S0000C 00050F 8

UCB50H 4PT5S0000C 00050F

15A

UCB50L 2PT5S0000C 00015F

UCB50L 3PT5S0000C 00015F

UCB50L 4PT5S0000C 00015F

16A

UCB50L 2PT5S0000C 00016F

UCB50L 3PT5S0000C 00016F

UCB50L 4PT5S0000C 00016F

Code

Unit
(EA)

20A

UCB50L 2PT5S0000C 00020F

UCB50L 3PT5S0000C 00020F

UCB50L 4PT5S0000C 00020F

UCB50L

25A

UCB50L 2PT5S0000C 00025F

UCB50L 3PT5S0000C 00025F

UCB50L 4PT5S0000C 00025F

50kA

30A

UCB50L 2PT5S0000C 00030F

UCB50L 3PT5S0000C 00030F

UCB50L 4PT5S0000C 00030F

32A

UCB50L 2PT5S0000C 00032F

UCB50L 3PT5S0000C 00032F

UCB50L 4PT5S0000C 00032F

40A

UCB50L 2PT5S0000C 00040F

UCB50L 3PT5S0000C 00040F

UCB50L 4PT5S0000C 00040F

50A

UCB50L 2PT5S0000C 00050F

UCB50L 3PT5S0000C 00050F

UCB50L 4PT5S0000C 00050F

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

Molded Case Circuit Breaker_ 57

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UCB type / 100AF |
UCB100R 30/25kA
UCB100S 42/36kA

UCB100R

UCB100S

Number of poles (P)

2, 3, 4

Degree of protection (with terminal cover)

IP20

Utilization category

Suitability of isolation
Protection

overload, inst., short-circuit


Rated current (A)

15,16,20,25,30,32,40,50,60,63,75,80,100,125

Rated insulation voltage [Ui] (V)


Rating

AC690
AC660

Rated operational voltage [Ue] (V)

DC250
Rated impulse withstand voltage [Uimp] (kV)

Rated
short-circuit
breaking
capacity

Ultimate
[Icu]
(kA r.m.s.)

IEC 60947-2
K 60947-2

AC600/660V, 50-60Hz

10

18

AC480/500V, 50-60Hz

14

25

AC440/460V, 50-60Hz

25

35

AC380/415V, 50-60Hz

30/25

42/36

AC220/240V, 50-60Hz

50

65

DC250V

14

18

DC125V

20

25

Service [Ics] % of [Icu]


Trip
mechanism
Thermal
magnetic
& Protection
characteristics

75

Fixed thermal,
Fixed instantaneous
Adjustable thermal,
Fixed instantaneous

INST

10 In

LTD

(0.8-0.9-1) In

INST

10 In

Direct mounting by screw


Mounting
Plug-in

Terminal connection
Durability
(times)

Both line & load side


for
Switchboard Line side only

1)

for Distribution board

1)

Screw

Mechanical operation

25,000

Electrical operation

Dimensions
(mm)

2/3/4P

10,000
a

Width

60/90/120

Height

155

Depth

60

d
Weight (kg, breaker only)

1)

2/3/4P

84.5
0.7/1.0/1.2

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker

58

MCCB

Accessories
Signal
1C, left-hand-side

Auxiliary switch

AUX 10B L1
1C, left-hand-side

Trip alarm switch


Shunt trip

ALT 10B L1

1)

Under voltage trip 2)

DC24V

DC100-110V

AC100-120V

SHT 10B A

SHT 10B F

AC200-230V

AC380-415V

AC440-480V

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

AC440-480V

UVT 10B J

UVT 10B L

UVT 10B N

UVT 10B P

UVT 10B Q

UVT 10B R

SHT 10B H

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.

Operating
Upper

Right

Left

S type

TFG 10BS U4

TFG 10BS R4

TFG 10BS L4

L type

TFG 10BL U4

Power supply direction


Operating Surface
handle1)
Extended

TFG 10BL L4

S type

TFH 10BS

L type

TFH 10BL

Motor operator 2)

DC24V

AC/DC110V

AC/DC220V

MOT 10UB DC24

MOT 10UB ADC110

MOT 10UB ADC220

2 pole

Mechanical interlock

3 pole

4 pole

MIF 10UF 3

MIF 10UF 4

PLD 10UF

Padlock plate3)
1) For detail type information, please refer to page 197-205.
2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.

Mounting
Structure
Mounting base
Plug-in

1)

For both line & load side

For line side only

TDM 10BP

TDM 10BF

Connection 2C contact

CBM 10AB 2

block 2)

CBM 10AB 3

3C contact

Conn. block barrier

CBM BARR

1) Available for 3P breaker


2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.

Terminal
3EA/SET

Cage terminal block

CTB 10B 3S

Terminal cover1)
Interpole barrier2)

4EA/SET

2EA/SET

CTB 10B 4S

2 pole

3 pole

4 pole

TCF 10BP 2

TCF 10BP 3

TCF 10BP 4

TQQ 10B 3PLINE

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA

Molded Case Circuit Breaker_ 59

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


Standard order code and unit
Fixed thermal & fixed instantaneous / Thermal magnetic trip
40/45
Model /
Breaking capacity at
AC380/415V

UCB100R
30/25kA

UCB100S
42/36kA

2 pole

3 pole

4 pole

Rated
current

Code

Unit
(EA)

Code

Unit
(EA)

15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A

UCB100R 2PT4S0000C 00015


UCB100R 2PT4S0000C 00016
UCB100R 2PT4S0000C 00020
UCB100R 2PT4S0000C 00025
UCB100R 2PT4S0000C 00030
UCB100R 2PT4S0000C 00032
UCB100R 2PT4S0000C 00040
UCB100R 2PT4S0000C 00050
UCB100R 2PT4S0000C 00060
UCB100R 2PT4S0000C 00063
UCB100R 2PT4S0000C 00075
UCB100R 2PT4S0000C 00080
UCB100R 2PT4S0000C 00100
UCB100R 2PT4S0000C 00125
UCB100S 2PT4S0000C 00015
UCB100S 2PT4S0000C 00016
UCB100S 2PT4S0000C 00020
UCB100S 2PT4S0000C 00025
UCB100S 2PT4S0000C 00030
UCB100S 2PT4S0000C 00032
UCB100S 2PT4S0000C 00040
UCB100S 2PT4S0000C 00050
UCB100S 2PT4S0000C 00060
UCB100S 2PT4S0000C 00063
UCB100S 2PT4S0000C 00075
UCB100S 2PT4S0000C 00080
UCB100S 2PT4S0000C 00100
UCB100S 2PT4S0000C 00125

16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

UCB100R 3PT4S0000C 00015


UCB100R 3PT4S0000C 00016
UCB100R 3PT4S0000C 00020
UCB100R 3PT4S0000C 00025
UCB100R 3PT4S0000C 00030
UCB100R 3PT4S0000C 00032
UCB100R 3PT4S0000C 00040
UCB100R 3PT4S0000C 00050
UCB100R 3PT4S0000C 00060
UCB100R 3PT4S0000C 00063
UCB100R 3PT4S0000C 00075
UCB100R 3PT4S0000C 00080
UCB100R 3PT4S0000C 00100
UCB100R 3PT4S0000C 00125
UCB100S 3PT4S0000C 00015
UCB100S 3PT4S0000C 00016
UCB100S 3PT4S0000C 00020
UCB100S 3PT4S0000C 00025
UCB100S 3PT4S0000C 00030
UCB100S 3PT4S0000C 00032
UCB100S 3PT4S0000C 00040
UCB100S 3PT4S0000C 00050
UCB100S 3PT4S0000C 00060
UCB100S 3PT4S0000C 00063
UCB100S 3PT4S0000C 00075
UCB100S 3PT4S0000C 00080
UCB100S 3PT4S0000C 00100
UCB100S 3PT4S0000C 00125

10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

Rated
current

Code

Unit
(EA)

Code

Unit
(EA)

15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A

UCB100R 2PT5S0000C 00015


UCB100R 2PT5S0000C 00016
UCB100R 2PT5S0000C 00020
UCB100R 2PT5S0000C 00025
UCB100R 2PT5S0000C 00030
UCB100R 2PT5S0000C 00032
UCB100R 2PT5S0000C 00040
UCB100R 2PT5S0000C 00050
UCB100R 2PT5S0000C 00060
UCB100R 2PT5S0000C 00063
UCB100R 2PT5S0000C 00075
UCB100R 2PT5S0000C 00080
UCB100R 2PT5S0000C 00100
UCB100R 2PT5S0000C 00125
UCB100S 2PT5S0000C 00015
UCB100S 2PT5S0000C 00016
UCB100S 2PT5S0000C 00020
UCB100S 2PT5S0000C 00025
UCB100S 2PT5S0000C 00030
UCB100S 2PT5S0000C 00032
UCB100S 2PT5S0000C 00040
UCB100S 2PT5S0000C 00050
UCB100S 2PT5S0000C 00060
UCB100S 2PT5S0000C 00063
UCB100S 2PT5S0000C 00075
UCB100S 2PT5S0000C 00080
UCB100S 2PT5S0000C 00100
UCB100S 2PT5S0000C 00125

16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

UCB100R 3PT5S0000C 00015


UCB100R 3PT5S0000C 00016
UCB100R 3PT5S0000C 00020
UCB100R 3PT5S0000C 00025
UCB100R 3PT5S0000C 00030
UCB100R 3PT5S0000C 00032
UCB100R 3PT5S0000C 00040
UCB100R 3PT5S0000C 00050
UCB100R 3PT5S0000C 00060
UCB100R 3PT5S0000C 00063
UCB100R 3PT5S0000C 00075
UCB100R 3PT5S0000C 00080
UCB100R 3PT5S0000C 00100
UCB100R 3PT5S0000C 00125
UCB100S 3PT5S0000C 00015
UCB100S 3PT5S0000C 00016
UCB100S 3PT5S0000C 00020
UCB100S 3PT5S0000C 00025
UCB100S 3PT5S0000C 00030
UCB100S 3PT5S0000C 00032
UCB100S 3PT5S0000C 00040
UCB100S 3PT5S0000C 00050
UCB100S 3PT5S0000C 00060
UCB100S 3PT5S0000C 00063
UCB100S 3PT5S0000C 00075
UCB100S 3PT5S0000C 00080
UCB100S 3PT5S0000C 00100
UCB100S 3PT5S0000C 00125

10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

Code
UCB100R 4PT4S0000C 00015
UCB100R 4PT4S0000C 00016
UCB100R 4PT4S0000C 00020
UCB100R 4PT4S0000C 00025
UCB100R 4PT4S0000C 00030
UCB100R 4PT4S0000C 00032
UCB100R 4PT4S0000C 00040
UCB100R 4PT4S0000C 00050
UCB100R 4PT4S0000C 00060
UCB100R 4PT4S0000C 00063
UCB100R 4PT4S0000C 00075
UCB100R 4PT4S0000C 00080
UCB100R 4PT4S0000C 00100
UCB100R 4PT4S0000C 00125
UCB100S 4PT4S0000C 00015
UCB100S 4PT4S0000C 00016
UCB100S 4PT4S0000C 00020
UCB100S 4PT4S0000C 00025
UCB100S 4PT4S0000C 00030
UCB100S 4PT4S0000C 00032
UCB100S 4PT4S0000C 00040
UCB100S 4PT4S0000C 00050
UCB100S 4PT4S0000C 00060
UCB100S 4PT4S0000C 00063
UCB100S 4PT4S0000C 00075
UCB100S 4PT4S0000C 00080
UCB100S 4PT4S0000C 00100
UCB100S 4PT4S0000C 00125

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

50
Model /
Breaking capacity at
AC380/415V

UCB100R
30/25kA

UCB100S
42/36kA

60

2 pole

3 pole

4 pole
Code
UCB100R 4PT5S0000C 00015
UCB100R 4PT5S0000C 00016
UCB100R 4PT5S0000C 00020
UCB100R 4PT5S0000C 00025
UCB100R 4PT5S0000C 00030
UCB100R 4PT5S0000C 00032
UCB100R 4PT5S0000C 00040
UCB100R 4PT5S0000C 00050
UCB100R 4PT5S0000C 00060
UCB100R 4PT5S0000C 00063
UCB100R 4PT5S0000C 00075
UCB100R 4PT5S0000C 00080
UCB100R 4PT5S0000C 00100
UCB100R 4PT5S0000C 00125
UCB100S 4PT5S0000C 00015
UCB100S 4PT5S0000C 00016
UCB100S 4PT5S0000C 00020
UCB100S 4PT5S0000C 00025
UCB100S 4PT5S0000C 00030
UCB100S 4PT5S0000C 00032
UCB100S 4PT5S0000C 00040
UCB100S 4PT5S0000C 00050
UCB100S 4PT5S0000C 00060
UCB100S 4PT5S0000C 00063
UCB100S 4PT5S0000C 00075
UCB100S 4PT5S0000C 00080
UCB100S 4PT5S0000C 00100
UCB100S 4PT5S0000C 00125

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

MCCB

Adjustable thermal & fixed instantaneous / Thermal magnetic trip


40/45
Model /
Breaking capacity at
AC380/415V

UCB100R
30/25kA

UCB100S
42/36kA

2 pole

3 pole

4 pole

Rated
current

Code

Unit
(EA)

Code

Unit
(EA)

15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A

UCB100R 2PT4S0000C 00015F


UCB100R 2PT4S0000C 00016F
UCB100R 2PT4S0000C 00020F
UCB100R 2PT4S0000C 00025F
UCB100R 2PT4S0000C 00030F
UCB100R 2PT4S0000C 00032F
UCB100R 2PT4S0000C 00040F
UCB100R 2PT4S0000C 00050F
UCB100R 2PT4S0000C 00060F
UCB100R 2PT4S0000C 00063F
UCB100R 2PT4S0000C 00075F
UCB100R 2PT4S0000C 00080F
UCB100R 2PT4S0000C 00100F
UCB100R 2PT4S0000C 00125F
UCB100S 2PT4S0000C 00015F
UCB100S 2PT4S0000C 00016F
UCB100S 2PT4S0000C 00020F
UCB100S 2PT4S0000C 00025F
UCB100S 2PT4S0000C 00030F
UCB100S 2PT4S0000C 00032F
UCB100S 2PT4S0000C 00040F
UCB100S 2PT4S0000C 00050F
UCB100S 2PT4S0000C 00060F
UCB100S 2PT4S0000C 00063F
UCB100S 2PT4S0000C 00075F
UCB100S 2PT4S0000C 00080F
UCB100S 2PT4S0000C 00100F
UCB100S 2PT4S0000C 00125F

16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

UCB100R 3PT4S0000C 00015F


UCB100R 3PT4S0000C 00016F
UCB100R 3PT4S0000C 00020F
UCB100R 3PT4S0000C 00025F
UCB100R 3PT4S0000C 00030F
UCB100R 3PT4S0000C 00032F
UCB100R 3PT4S0000C 00040F
UCB100R 3PT4S0000C 00050F
UCB100R 3PT4S0000C 00060F
UCB100R 3PT4S0000C 00063F
UCB100R 3PT4S0000C 00075F
UCB100R 3PT4S0000C 00080F
UCB100R 3PT4S0000C 00100F
UCB100R 3PT4S0000C 00125F
UCB100S 3PT4S0000C 00015F
UCB100S 3PT4S0000C 00016F
UCB100S 3PT4S0000C 00020F
UCB100S 3PT4S0000C 00025F
UCB100S 3PT4S0000C 00030F
UCB100S 3PT4S0000C 00032F
UCB100S 3PT4S0000C 00040F
UCB100S 3PT4S0000C 00050F
UCB100S 3PT4S0000C 00060F
UCB100S 3PT4S0000C 00063F
UCB100S 3PT4S0000C 00075F
UCB100S 3PT4S0000C 00080F
UCB100S 3PT4S0000C 00100F
UCB100S 3PT4S0000C 00125F

10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

Rated
current

Code

Unit
(EA)

Code

Unit
(EA)

15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A

UCB100R 2PT5S0000C 00015F


UCB100R 2PT5S0000C 00016F
UCB100R 2PT5S0000C 00020F
UCB100R 2PT5S0000C 00025F
UCB100R 2PT5S0000C 00030F
UCB100R 2PT5S0000C 00032F
UCB100R 2PT5S0000C 00040F
UCB100R 2PT5S0000C 00050F
UCB100R 2PT5S0000C 00060F
UCB100R 2PT5S0000C 00063F
UCB100R 2PT5S0000C 00075F
UCB100R 2PT5S0000C 00080F
UCB100R 2PT5S0000C 00100F
UCB100R 2PT5S0000C 00125F
UCB100S 2PT5S0000C 00015F
UCB100S 2PT5S0000C 00016F
UCB100S 2PT5S0000C 00020F
UCB100S 2PT5S0000C 00025F
UCB100S 2PT5S0000C 00030F
UCB100S 2PT5S0000C 00032F
UCB100S 2PT5S0000C 00040F
UCB100S 2PT5S0000C 00050F
UCB100S 2PT5S0000C 00060F
UCB100S 2PT5S0000C 00063F
UCB100S 2PT5S0000C 00075F
UCB100S 2PT5S0000C 00080F
UCB100S 2PT5S0000C 00100F
UCB100S 2PT5S0000C 00125F

16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16

UCB100R 3PT5S0000C 00015F


UCB100R 3PT5S0000C 00016F
UCB100R 3PT5S0000C 00020F
UCB100R 3PT5S0000C 00025F
UCB100R 3PT5S0000C 00030F
UCB100R 3PT5S0000C 00032F
UCB100R 3PT5S0000C 00040F
UCB100R 3PT5S0000C 00050F
UCB100R 3PT5S0000C 00060F
UCB100R 3PT5S0000C 00063F
UCB100R 3PT5S0000C 00075F
UCB100R 3PT5S0000C 00080F
UCB100R 3PT5S0000C 00100F
UCB100R 3PT5S0000C 00125F
UCB100S 3PT5S0000C 00015F
UCB100S 3PT5S0000C 00016F
UCB100S 3PT5S0000C 00020F
UCB100S 3PT5S0000C 00025F
UCB100S 3PT5S0000C 00030F
UCB100S 3PT5S0000C 00032F
UCB100S 3PT5S0000C 00040F
UCB100S 3PT5S0000C 00050F
UCB100S 3PT5S0000C 00060F
UCB100S 3PT5S0000C 00063F
UCB100S 3PT5S0000C 00075F
UCB100S 3PT5S0000C 00080F
UCB100S 3PT5S0000C 00100F
UCB100S 3PT5S0000C 00125F

10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

Code
UCB100R 4PT4S0000C 00015F
UCB100R 4PT4S0000C 00016F
UCB100R 4PT4S0000C 00020F
UCB100R 4PT4S0000C 00025F
UCB100R 4PT4S0000C 00030F
UCB100R 4PT4S0000C 00032F
UCB100R 4PT4S0000C 00040F
UCB100R 4PT4S0000C 00050F
UCB100R 4PT4S0000C 00060F
UCB100R 4PT4S0000C 00063F
UCB100R 4PT4S0000C 00075F
UCB100R 4PT4S0000C 00080F
UCB100R 4PT4S0000C 00100F
UCB100R 4PT4S0000C 00125F
UCB100S 4PT4S0000C 00015F
UCB100S 4PT4S0000C 00016F
UCB100S 4PT4S0000C 00020F
UCB100S 4PT4S0000C 00025F
UCB100S 4PT4S0000C 00030F
UCB100S 4PT4S0000C 00032F
UCB100S 4PT4S0000C 00040F
UCB100S 4PT4S0000C 00050F
UCB100S 4PT4S0000C 00060F
UCB100S 4PT4S0000C 00063F
UCB100S 4PT4S0000C 00075F
UCB100S 4PT4S0000C 00080F
UCB100S 4PT4S0000C 00100F
UCB100S 4PT4S0000C 00125F

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

50
Model /
Breaking capacity at
AC380/415V

UCB100R
30/25kA

UCB100S
42/36kA

2 pole

3 pole

4 pole
Code
UCB100R 4PT5S0000C 00015F
UCB100R 4PT5S0000C 00016F
UCB100R 4PT5S0000C 00020F
UCB100R 4PT5S0000C 00025F
UCB100R 4PT5S0000C 00030F
UCB100R 4PT5S0000C 00032F
UCB100R 4PT5S0000C 00040F
UCB100R 4PT5S0000C 00050F
UCB100R 4PT5S0000C 00060F
UCB100R 4PT5S0000C 00063F
UCB100R 4PT5S0000C 00075F
UCB100R 4PT5S0000C 00080F
UCB100R 4PT5S0000C 00100F
UCB100R 4PT5S0000C 00125F
UCB100S 4PT5S0000C 00015F
UCB100S 4PT5S0000C 00016F
UCB100S 4PT5S0000C 00020F
UCB100S 4PT5S0000C 00025F
UCB100S 4PT5S0000C 00030F
UCB100S 4PT5S0000C 00032F
UCB100S 4PT5S0000C 00040F
UCB100S 4PT5S0000C 00050F
UCB100S 4PT5S0000C 00060F
UCB100S 4PT5S0000C 00063F
UCB100S 4PT5S0000C 00075F
UCB100S 4PT5S0000C 00080F
UCB100S 4PT5S0000C 00100F
UCB100S 4PT5S0000C 00125F

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

Molded Case Circuit Breaker_ 61

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UCB type / 125AF |
UCB100H 42kA
UCB100L 50kA

UCB100H

UCB100L

Number of poles (P)

2, 3, 4

Degree of protection (with terminal cover)

IP20

Utilization category

Suitability of isolation
Protection

overload, inst., short-circuit


Rated current (A)

15,16,20,25,30,32,40,50,60,63,75,80,100,125

Rated insulation voltage [Ui] (V)


Rating

AC690
AC660

Rated operational voltage [Ue] (V)

DC250
Rated impulse withstand voltage [Uimp] (kV)

Rated
short-circuit
breaking
capacity

Ultimate
[Icu]
(kA r.m.s.)

IEC 60947-2
K 60947-2

AC600/660V, 50-60Hz

20

25

AC480/500V, 50-60Hz

30

35

AC440/460V, 50-60Hz

42

50

AC380/415V, 50-60Hz

42

50

AC220/240V, 50-60Hz

85

100

DC250V

25

40

DC125V

40

60

Service [Ics] % of [Icu]


Trip
Thermal
mechanism
& Protection
magnetic
characteristics

75

Fixed thermal,
Fixed instantaneous
Adjustable thermal,
Fixed instantaneous

INST

15-32A: 15 In, 40-125A: 10 In

LTD

(0.8-0.9-1) In

INST

15-32A: 15 In, 40-125A: 10 In

Direct mounting by screw


Mounting
Plug-in

Terminal connection
Durability
(times)

Both line & load side


for
Switchboard Line side only

1)

for Distribution board

1)

Screw

Mechanical operation

25,000

Electrical operation

Dimensions
(mm)

2/3/4P

10,000
a

Width

902)/90/120

Height

155

Depth

60

d
Weight (kg, breaker only)

1)

2/3/4P

84.5
0.9/1.0/1.3

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.

62

MCCB

Accessories
Signal
1C, left-hand-side

Auxiliary switch
Trip alarm switch
Shunt trip

1)

Under voltage trip2)

2C, left-hand-side

AUX 12FG L1

AUX 12FG L2

1C, right-hand-side

1C, left-hand-side

ALT 12FG R1

ALT 12FG L1

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

SHT 12FG A

SHT 12FG C

SHT 12FG F

SHT 12FG H

SHT 12FG B

SHT 12FG D

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

AC440-480V

UVT 12FG J

UVT 12FG L

UVT 12FG N

UVT 12FG P

UVT 12FG Q

UVT 12FG R

AC440-480V

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.

Operating
Upper

Right

Left

S type

TFG 10UFS U4

TFG 10UFS R4

TFG 10UFS L4

L type

TFG 10UFL U4

Power supply direction


Operating Surface
handle1)
Extended

TFG 10UFL L4
TFH 10UFS

S type

TFH 10UFL

L type
Motor operator 2)

DC24V

AC/DC110V

AC/DC220V

MOT 10F DC24

MOT 10F ADC110

MOT 10F ADC220

Mechanical interlock

2 pole

3 pole

4 pole

MIF 10UF 3

MIF 10UF 3

MIF 10UF 4

PLD 10UF

Padlock plate3)
1) For detail type information, please refer to page 197-205.
2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.

Mounting
Structure
Mounting base
Plug-in1) Connection 2C contact
block 2)

3C contact

Conn. block barrier

For both line & load side

For line side only

TDM 10BP

TDM 10BF

CBM 10AB 2
CBM 10AB 3
CBM BARR

1) Available for 3P breaker


2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.

Terminal
Cage terminal block
Terminal cover1)
Interpole barrier2)

2EA/SET

3EA/SET

4EA/SET

CTB 10B 3S

CTB 10B 4S

2 pole

3 pole

4 pole

TCF 10FP 3

TCF 10FP 3

TCF 10FP 4

TQQ 12FG 3PLINE

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA

Molded Case Circuit Breaker_ 63

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


Standard order code and unit
Fixed thermal & fixed instantaneous / Thermal magnetic trip
40/45
Model /
Breaking capacity at
AC380/415V

UCB100H
42kA

UCB100L
50kA

Rated
current
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A

2 pole
Code
UCB100H 2PT4S0000C 00015
UCB100H 2PT4S0000C 00016
UCB100H 2PT4S0000C 00020
UCB100H 2PT4S0000C 00025
UCB100H 2PT4S0000C 00030
UCB100H 2PT4S0000C 00032
UCB100H 2PT4S0000C 00040
UCB100H 2PT4S0000C 00050
UCB100H 2PT4S0000C 00060
UCB100H 2PT4S0000C 00063
UCB100H 2PT4S0000C 00075
UCB100H 2PT4S0000C 00080
UCB100H 2PT4S0000C 00100
UCB100H 2PT4S0000C 00125
UCB100L 2PT4S0000C 00015
UCB100L 2PT4S0000C 00016
UCB100L 2PT4S0000C 00020
UCB100L 2PT4S0000C 00025
UCB100L 2PT4S0000C 00030
UCB100L 2PT4S0000C 00032
UCB100L 2PT4S0000C 00040
UCB100L 2PT4S0000C 00050
UCB100L 2PT4S0000C 00060
UCB100L 2PT4S0000C 00063
UCB100L 2PT4S0000C 00075
UCB100L 2PT4S0000C 00080
UCB100L 2PT4S0000C 00100
UCB100L 2PT4S0000C 00125

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

3 pole
Code
UCB100H 3PT4S0000C 00015
UCB100H 3PT4S0000C 00016
UCB100H 3PT4S0000C 00020
UCB100H 3PT4S0000C 00025
UCB100H 3PT4S0000C 00030
UCB100H 3PT4S0000C 00032
UCB100H 3PT4S0000C 00040
UCB100H 3PT4S0000C 00050
UCB100H 3PT4S0000C 00060
UCB100H 3PT4S0000C 00063
UCB100H 3PT4S0000C 00075
UCB100H 3PT4S0000C 00080
UCB100H 3PT4S0000C 00100
UCB100H 3PT4S0000C 00125
UCB100L 3PT4S0000C 00015
UCB100L 3PT4S0000C 00016
UCB100L 3PT4S0000C 00020
UCB100L 3PT4S0000C 00025
UCB100L 3PT4S0000C 00030
UCB100L 3PT4S0000C 00032
UCB100L 3PT4S0000C 00040
UCB100L 3PT4S0000C 00050
UCB100L 3PT4S0000C 00060
UCB100L 3PT4S0000C 00063
UCB100L 3PT4S0000C 00075
UCB100L 3PT4S0000C 00080
UCB100L 3PT4S0000C 00100
UCB100L 3PT4S0000C 00125

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

4 pole
Code
UCB100H 4PT4S0000C 00015
UCB100H 4PT4S0000C 00016
UCB100H 4PT4S0000C 00020
UCB100H 4PT4S0000C 00025
UCB100H 4PT4S0000C 00030
UCB100H 4PT4S0000C 00032
UCB100H 4PT4S0000C 00040
UCB100H 4PT4S0000C 00050
UCB100H 4PT4S0000C 00060
UCB100H 4PT4S0000C 00063
UCB100H 4PT4S0000C 00075
UCB100H 4PT4S0000C 00080
UCB100H 4PT4S0000C 00100
UCB100H 4PT4S0000C 00125
UCB100L 4PT4S0000C 00015
UCB100L 4PT4S0000C 00016
UCB100L 4PT4S0000C 00020
UCB100L 4PT4S0000C 00025
UCB100L 4PT4S0000C 00030
UCB100L 4PT4S0000C 00032
UCB100L 4PT4S0000C 00040
UCB100L 4PT4S0000C 00050
UCB100L 4PT4S0000C 00060
UCB100L 4PT4S0000C 00063
UCB100L 4PT4S0000C 00075
UCB100L 4PT4S0000C 00080
UCB100L 4PT4S0000C 00100
UCB100L 4PT4S0000C 00125

Unit
(EA)

6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

50
Model /
Breaking capacity at
AC380/415V

UCB100H
42kA

UCB100L
50kA

64

Rated
current
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A

2 pole
Code
UCB100H 2PT5S0000C 00015
UCB100H 2PT5S0000C 00016
UCB100H 2PT5S0000C 00020
UCB100H 2PT5S0000C 00025
UCB100H 2PT5S0000C 00030
UCB100H 2PT5S0000C 00032
UCB100H 2PT5S0000C 00040
UCB100H 2PT5S0000C 00050
UCB100H 2PT5S0000C 00060
UCB100H 2PT5S0000C 00063
UCB100H 2PT5S0000C 00075
UCB100H 2PT5S0000C 00080
UCB100H 2PT5S0000C 00100
UCB100H 2PT5S0000C 00125
UCB100L 2PT5S0000C 00015
UCB100L 2PT5S0000C 00016
UCB100L 2PT5S0000C 00020
UCB100L 2PT5S0000C 00025
UCB100L 2PT5S0000C 00030
UCB100L 2PT5S0000C 00032
UCB100L 2PT5S0000C 00040
UCB100L 2PT5S0000C 00050
UCB100L 2PT5S0000C 00060
UCB100L 2PT5S0000C 00063
UCB100L 2PT5S0000C 00075
UCB100L 2PT5S0000C 00080
UCB100L 2PT5S0000C 00100
UCB100L 2PT5S0000C 00125

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

3 pole
Code
UCB100H 3PT5S0000C 00015
UCB100H 3PT5S0000C 00016
UCB100H 3PT5S0000C 00020
UCB100H 3PT5S0000C 00025
UCB100H 3PT5S0000C 00030
UCB100H 3PT5S0000C 00032
UCB100H 3PT5S0000C 00040
UCB100H 3PT5S0000C 00050
UCB100H 3PT5S0000C 00060
UCB100H 3PT5S0000C 00063
UCB100H 3PT5S0000C 00075
UCB100H 3PT5S0000C 00080
UCB100H 3PT5S0000C 00100
UCB100H 3PT5S0000C 00125
UCB100L 3PT5S0000C 00015
UCB100L 3PT5S0000C 00016
UCB100L 3PT5S0000C 00020
UCB100L 3PT5S0000C 00025
UCB100L 3PT5S0000C 00030
UCB100L 3PT5S0000C 00032
UCB100L 3PT5S0000C 00040
UCB100L 3PT5S0000C 00050
UCB100L 3PT5S0000C 00060
UCB100L 3PT5S0000C 00063
UCB100L 3PT5S0000C 00075
UCB100L 3PT5S0000C 00080
UCB100L 3PT5S0000C 00100
UCB100L 3PT5S0000C 00125

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

4 pole
Code
UCB100H 4PT5S0000C 00015
UCB100H 4PT5S0000C 00016
UCB100H 4PT5S0000C 00020
UCB100H 4PT5S0000C 00025
UCB100H 4PT5S0000C 00030
UCB100H 4PT5S0000C 00032
UCB100H 4PT5S0000C 00040
UCB100H 4PT5S0000C 00050
UCB100H 4PT5S0000C 00060
UCB100H 4PT5S0000C 00063
UCB100H 4PT5S0000C 00075
UCB100H 4PT5S0000C 00080
UCB100H 4PT5S0000C 00100
UCB100H 4PT5S0000C 00125
UCB100L 4PT5S0000C 00015
UCB100L 4PT5S0000C 00016
UCB100L 4PT5S0000C 00020
UCB100L 4PT5S0000C 00025
UCB100L 4PT5S0000C 00030
UCB100L 4PT5S0000C 00032
UCB100L 4PT5S0000C 00040
UCB100L 4PT5S0000C 00050
UCB100L 4PT5S0000C 00060
UCB100L 4PT5S0000C 00063
UCB100L 4PT5S0000C 00075
UCB100L 4PT5S0000C 00080
UCB100L 4PT5S0000C 00100
UCB100L 4PT5S0000C 00125

Unit
(EA)

6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

MCCB

Adjustable thermal & fixed instantaneous / Thermal magnetic trip


40/45
Model /
Breaking capacity at
AC380/415V

UCB100H
42kA

UCB100L
50kA

Rated
current
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A

2 pole
Code
UCB100H 2PT4S0000C 00015F
UCB100H 2PT4S0000C 00016F
UCB100H 2PT4S0000C 00020F
UCB100H 2PT4S0000C 00025F
UCB100H 2PT4S0000C 00030F
UCB100H 2PT4S0000C 00032F
UCB100H 2PT4S0000C 00040F
UCB100H 2PT4S0000C 00050F
UCB100H 2PT4S0000C 00060F
UCB100H 2PT4S0000C 00063F
UCB100H 2PT4S0000C 00075F
UCB100H 2PT4S0000C 00080F
UCB100H 2PT4S0000C 00100F
UCB100H 2PT4S0000C 00125F
UCB100L 2PT4S0000C 00015F
UCB100L 2PT4S0000C 00016F
UCB100L 2PT4S0000C 00020F
UCB100L 2PT4S0000C 00025F
UCB100L 2PT4S0000C 00030F
UCB100L 2PT4S0000C 00032F
UCB100L 2PT4S0000C 00040F
UCB100L 2PT4S0000C 00050F
UCB100L 2PT4S0000C 00060F
UCB100L 2PT4S0000C 00063F
UCB100L 2PT4S0000C 00075F
UCB100L 2PT4S0000C 00080F
UCB100L 2PT4S0000C 00100F
UCB100L 2PT4S0000C 00125F

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

3 pole
Code
UCB100H 3PT4S0000C 00015F
UCB100H 3PT4S0000C 00016F
UCB100H 3PT4S0000C 00020F
UCB100H 3PT4S0000C 00025F
UCB100H 3PT4S0000C 00030F
UCB100H 3PT4S0000C 00032F
UCB100H 3PT4S0000C 00040F
UCB100H 3PT4S0000C 00050F
UCB100H 3PT4S0000C 00060F
UCB100H 3PT4S0000C 00063F
UCB100H 3PT4S0000C 00075F
UCB100H 3PT4S0000C 00080F
UCB100H 3PT4S0000C 00100F
UCB100H 3PT4S0000C 00125F
UCB100L 3PT4S0000C 00015F
UCB100L 3PT4S0000C 00016F
UCB100L 3PT4S0000C 00020F
UCB100L 3PT4S0000C 00025F
UCB100L 3PT4S0000C 00030F
UCB100L 3PT4S0000C 00032F
UCB100L 3PT4S0000C 00040F
UCB100L 3PT4S0000C 00050F
UCB100L 3PT4S0000C 00060F
UCB100L 3PT4S0000C 00063F
UCB100L 3PT4S0000C 00075F
UCB100L 3PT4S0000C 00080F
UCB100L 3PT4S0000C 00100F
UCB100L 3PT4S0000C 00125F

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

4 pole
Code
UCB100H 4PT4S0000C 00015F
UCB100H 4PT4S0000C 00016F
UCB100H 4PT4S0000C 00020F
UCB100H 4PT4S0000C 00025F
UCB100H 4PT4S0000C 00030F
UCB100H 4PT4S0000C 00032F
UCB100H 4PT4S0000C 00040F
UCB100H 4PT4S0000C 00050F
UCB100H 4PT4S0000C 00060F
UCB100H 4PT4S0000C 00063F
UCB100H 4PT4S0000C 00075F
UCB100H 4PT4S0000C 00080F
UCB100H 4PT4S0000C 00100F
UCB100H 4PT4S0000C 00125F
UCB100L 4PT4S0000C 00015F
UCB100L 4PT4S0000C 00016F
UCB100L 4PT4S0000C 00020F
UCB100L 4PT4S0000C 00025F
UCB100L 4PT4S0000C 00030F
UCB100L 4PT4S0000C 00032F
UCB100L 4PT4S0000C 00040F
UCB100L 4PT4S0000C 00050F
UCB100L 4PT4S0000C 00060F
UCB100L 4PT4S0000C 00063F
UCB100L 4PT4S0000C 00075F
UCB100L 4PT4S0000C 00080F
UCB100L 4PT4S0000C 00100F
UCB100L 4PT4S0000C 00125F

Unit
(EA)

6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

50
Model /
Breaking capacity at
AC380/415V

UCB100H
42kA

UCB100L
50kA

Rated
current
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A

2 pole
Code
UCB100H 2PT5S0000C 00015F
UCB100H 2PT5S0000C 00016F
UCB100H 2PT5S0000C 00020F
UCB100H 2PT5S0000C 00025F
UCB100H 2PT5S0000C 00030F
UCB100H 2PT5S0000C 00032F
UCB100H 2PT5S0000C 00040F
UCB100H 2PT5S0000C 00050F
UCB100H 2PT5S0000C 00060F
UCB100H 2PT5S0000C 00063F
UCB100H 2PT5S0000C 00075F
UCB100H 2PT5S0000C 00080F
UCB100H 2PT5S0000C 00100F
UCB100H 2PT5S0000C 00125F
UCB100L 2PT5S0000C 00015F
UCB100L 2PT5S0000C 00016F
UCB100L 2PT5S0000C 00020F
UCB100L 2PT5S0000C 00025F
UCB100L 2PT5S0000C 00030F
UCB100L 2PT5S0000C 00032F
UCB100L 2PT5S0000C 00040F
UCB100L 2PT5S0000C 00050F
UCB100L 2PT5S0000C 00060F
UCB100L 2PT5S0000C 00063F
UCB100L 2PT5S0000C 00075F
UCB100L 2PT5S0000C 00080F
UCB100L 2PT5S0000C 00100F
UCB100L 2PT5S0000C 00125F

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

3 pole
Code
UCB100H 3PT5S0000C 00015F
UCB100H 3PT5S0000C 00016F
UCB100H 3PT5S0000C 00020F
UCB100H 3PT5S0000C 00025F
UCB100H 3PT5S0000C 00030F
UCB100H 3PT5S0000C 00032F
UCB100H 3PT5S0000C 00040F
UCB100H 3PT5S0000C 00050F
UCB100H 3PT5S0000C 00060F
UCB100H 3PT5S0000C 00063F
UCB100H 3PT5S0000C 00075F
UCB100H 3PT5S0000C 00080F
UCB100H 3PT5S0000C 00100F
UCB100H 3PT5S0000C 00125F
UCB100L 3PT5S0000C 00015F
UCB100L 3PT5S0000C 00016F
UCB100L 3PT5S0000C 00020F
UCB100L 3PT5S0000C 00025F
UCB100L 3PT5S0000C 00030F
UCB100L 3PT5S0000C 00032F
UCB100L 3PT5S0000C 00040F
UCB100L 3PT5S0000C 00050F
UCB100L 3PT5S0000C 00060F
UCB100L 3PT5S0000C 00063F
UCB100L 3PT5S0000C 00075F
UCB100L 3PT5S0000C 00080F
UCB100L 3PT5S0000C 00100F
UCB100L 3PT5S0000C 00125F

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

4 pole
Code
UCB100H 4PT5S0000C 00015F
UCB100H 4PT5S0000C 00016F
UCB100H 4PT5S0000C 00020F
UCB100H 4PT5S0000C 00025F
UCB100H 4PT5S0000C 00030F
UCB100H 4PT5S0000C 00032F
UCB100H 4PT5S0000C 00040F
UCB100H 4PT5S0000C 00050F
UCB100H 4PT5S0000C 00060F
UCB100H 4PT5S0000C 00063F
UCB100H 4PT5S0000C 00075F
UCB100H 4PT5S0000C 00080F
UCB100H 4PT5S0000C 00100F
UCB100H 4PT5S0000C 00125F
UCB100L 4PT5S0000C 00015F
UCB100L 4PT5S0000C 00016F
UCB100L 4PT5S0000C 00020F
UCB100L 4PT5S0000C 00025F
UCB100L 4PT5S0000C 00030F
UCB100L 4PT5S0000C 00032F
UCB100L 4PT5S0000C 00040F
UCB100L 4PT5S0000C 00050F
UCB100L 4PT5S0000C 00060F
UCB100L 4PT5S0000C 00063F
UCB100L 4PT5S0000C 00075F
UCB100L 4PT5S0000C 00080F
UCB100L 4PT5S0000C 00100F
UCB100L 4PT5S0000C 00125F

Unit
(EA)

6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

Molded Case Circuit Breaker_ 65

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UCB type / 160AF |
UCB160H 42kA
UCB160L 50kA

UCB160H

2, 3, 4
IP20
A

Number of poles (P)


Degree of protection (with terminal cover)
Utilization category
Suitability of isolation
Protection
Rated current (A)
Rated insulation voltage [Ui] (V)
Rating
Rated operational voltage [Ue] (V)

Rated
short-circuit
breaking
capacity
IEC 60947-2
K 60947-2

overload, inst., short-circuit


100,125,160
AC690
AC660
DC250
6

Rated impulse withstand voltage [Uimp] (kV)


AC600/660V, 50-60Hz
AC480/500V, 50-60Hz
AC440/460V, 50-60Hz
Ultimate
[Icu]
AC380/415V, 50-60Hz
(kA r.m.s.)
AC220/240V, 50-60Hz
DC250V
DC125V
Service [Ics] % of [Icu]

Trip
Thermal
mechanism
& Protection
magnetic
characteristics

UCB160L

Fixed thermal,
Fixed instantaneous
Adjustable thermal,
Fixed instantaneous

20
30
42
42
85
25
40

25
35
50
50
100
40
60
50

INST
LTD
INST

10 In
(0.8-0.9-1) In
10 In

Direct mounting by screw


Both line & load side
for
Mounting
Switchboard Line side only
Plug-in
for Distribution board
Screw
Terminal connection
Bus bar
Mechanical operation
Durability
(times)
Electrical operation
a
Width
b
Height
Dimensions
2/3/4P
(mm)
c
Depth
d
Weight (kg, breaker only)
2/3/4P

1)
1)
1)

25,000
10,000
1052)/105/140
165
60
84.5
1.1/1.3/1.6

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.

Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip1)
Under voltage trip2)

66

1C, left-hand-side
AUX 12FG L1
1C, right-hand-side
ALT 12FG R1
DC24V
SHT 12FG A
DC24V
UVT 12FG J

2C, leftt-hand-side
AUX 12FG L2
1C, left-hand-side
ALT 12FG L1
DC100-110V
SHT 12FG C
DC100-110V
UVT 12FG L

AC100-120V
SHT 12FG F
AC100-120V
UVT 12FG N

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.

AC200-230V
SHT 12FG H
AC200-230V
UVT 12FG P

AC380-415V
SHT 12FG B
AC380-415V
UVT 12FG Q

AC440-480V
SHT 12FG D
AC440-480V
UVT 12FG R

MCCB

Operating
Operating
handle1)

Upper
TFG 20UGS U4
TFG 20UGL U4

Power supply direction


S type
Surface
L type
S type
Extended
L type

Right
TFG 20UGS R4
TFH 20UGS
TFH 20UGL
AC/DC110V
MOT 20G ADC110
3 pole
MIF 20UG 3
PLD 20UG

DC24V
MOT 20G DC24
2 pole
MIF 20UG 3

Motor operator 2)
Mechanical interlock

Left
TFG 20UGS L4
TFG 20UGL L4

Padlock plate3)

AC/DC220V
MOT 20G ADC220
4 pole
MIF 20UG 4

1) For detail type information, please refer to page 197-205. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied.

Mounting
Plug-in1)

Structure
Mounting base
Connection 2C contact
5C contact
block2)

For both line & load side


TDM 20CF3)
CBM 20C 2
CBM 20C 5

For line side only


TDM 20CF

1) Available for 3P breaker


2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.
3) 2EA are required for both line & load side plug-in type 3P breaker.

Terminal
2 pole (4EA/SET)
TBB 20C 2
3EA/SET
CTB 20C 3S
2 pole
TCF 20GP 3

Terminal bus bar


Cage terminal block
Terminal cover 1)
Interpole barrier 2)

2EA/SET

3 pole (6EA/SET)
4 pole (8EA/SET)
TBB 20C 3
TBB 20C 4
4EA/SET
CTB 20C 4S
3 pole
4 pole
TCF 20GP 3
TCF 20GP 4
TQQ 12FG 3PLINE

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 4EA, 3 pole 4EA, 4 pole 6EA

Standard order code and unit


Fixed thermal & fixed instantaneous / Thermal magnetic trip
40/45
Model /
Breaking capacity at
AC380/415V

UCB160H
42kA
UCB160L
50kA

Rated
current

2 pole
Code

100A
125A
160A
100A
125A
160A

UCB160H 2PT4S0000C 00100


UCB160H 2PT4S0000C 00125
UCB160H 2PT4S0000C 00160
UCB160L 2PT4S0000C 00100
UCB160L 2PT4S0000C 00125
UCB160L 2PT4S0000C 00160

Rated
current

2 pole
Code
UCB160H 2PT5S0000C 00100
UCB160H 2PT5S0000C 00125
UCB160H 2PT5S0000C 00160
UCB160L 2PT5S0000C 00100
UCB160L 2PT5S0000C 00125
UCB160L 2PT5S0000C 00160

Unit
(EA)

8
8
8
8
8
8

3 pole
Code
UCB160H 3PT4S0000C 00100
UCB160H 3PT4S0000C 00125
UCB160H 3PT4S0000C 00160
UCB160L 3PT4S0000C 00100
UCB160L 3PT4S0000C 00125
UCB160L 3PT4S0000C 00160

Unit
(EA)

8
8
8
8
8
8

4 pole
Code
UCB160H 4PT4S0000C 00100
UCB160H 4PT4S0000C 00125
UCB160H 4PT4S0000C 00160
UCB160L 4PT4S0000C 00100
UCB160L 4PT4S0000C 00125
UCB160L 4PT4S0000C 00160

Unit
(EA)

6
6
6
6
6
6

Specification Category
Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

50
Model /
Breaking capacity at
AC380/415V

UCB160H
42kA
UCB160L
50kA

100A
125A
160A
100A
125A
160A

Unit
(EA)

8
8
8
8
8
8

3 pole
Unit
Code
(EA)
UCB160H 3PT5S0000C 00100 8
UCB160H 3PT5S0000C 00125 8
UCB160H 3PT5S0000C 00160 8
UCB160L 3PT5S0000C 00100
8
UCB160L 3PT5S0000C 00125
8
UCB160L 3PT5S0000C 00160
8

4 pole
Code
UCB160H 4PT5S0000C 00100
UCB160H 4PT5S0000C 00125
UCB160H 4PT5S0000C 00160
UCB160L 4PT5S0000C 00100
UCB160L 4PT5S0000C 00125
UCB160L 4PT5S0000C 00160

Unit
(EA)

6
6
6
6
6
6

Specification Category
Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

Adjustable thermal & fixed instantaneous / Thermal magnetic trip


40/45
Model /
Breaking capacity at
AC380/415V

UCB160H
42kA
UCB160L
50kA

Rated
current
100A
125A
160A
100A
125A
160A

2 pole
Unit
Code
(EA)
UCB160H 2PT4S0000C 00100F 8
UCB160H 2PT4S0000C 00125F 8
UCB160H 2PT4S0000C 00160F 8
UCB160L 2PT4S0000C 00100F 8
UCB160L 2PT4S0000C 00125F 8
UCB160L 2PT4S0000C 00160F 8

3 pole
Code
UCB160H 3PT4S0000C 00100F
UCB160H 3PT4S0000C 00125F
UCB160H 3PT4S0000C 00160F
UCB160L 3PT4S0000C 00100F
UCB160L 3PT4S0000C 00125F
UCB160L 3PT4S0000C 00160F

Unit
(EA)

8
8
8
8
8
8

4 pole
Unit Specification Category
Code
(EA)
UCB160H 4PT4S0000C 00100F 6
UCB160H 4PT4S0000C 00125F 6 Screw type
terminal
MCCB
UCB160H 4PT4S0000C 00160F 6
connection,
/M2
UCB160L 4PT4S0000C 00100F 6
No option,
UCB160L 4PT4S0000C 00125F 6
50/60Hz
UCB160L 4PT4S0000C 00160F 6

50
Model /
Breaking capacity at
AC380/415V

UCB160H
42kA
UCB160L
50kA

Rated
current
100A
125A
160A
100A
125A
160A

2 pole
3 pole
4 pole
Unit
Unit
Unit Specification Category
Code
Code
Code
(EA)
(EA)
(EA)
UCB160H 2PT5S0000C 00100F 8 UCB160H 3PT5S0000C 00100F 8 UCB160H 4PT5S0000C 00100F 6
Screw type
UCB160H 2PT5S0000C 00125F 8 UCB160H 3PT5S0000C 00125F 8 UCB160H 4PT5S0000C 00125F 6
terminal
UCB160H 2PT5S0000C 00160F 8 UCB160H 3PT5S0000C 00160F 8 UCB160H 4PT5S0000C 00160F 6 connection, MCCB
/M2
UCB160L 2PT5S0000C 00100F 8 UCB160L 3PT5S0000C 00100F 8 UCB160L 4PT5S0000C 00100F 6
No option,
UCB160L 2PT5S0000C 00125F 8 UCB160L 3PT5S0000C 00125F 8 UCB160L 4PT5S0000C 00125F 6
50/60Hz
UCB160L 2PT5S0000C 00160F 8 UCB160L 3PT5S0000C 00160F 8 UCB160L 4PT5S0000C 00160F 6
Molded Case Circuit Breaker_ 67

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UCB type / 250AF |
UCB250R 25/18kA
UCB250S 35/25kA
UCB250N 42/36kA

UCB250R

UCB250S

Number of poles (P)

2, 3, 4

Degree of protection (with terminal cover)

IP20

Utilization category

UCB250N

Suitability of isolation
Protection

overload, inst., short-circuit


Rated current (A)

125,150,160,175,200,225,250

Rated insulation voltage [Ui] (V)


Rating

AC690
AC660

Rated operational voltage [Ue] (V)

DC250
Rated impulse withstand voltage [Uimp] (kV)

Rated
short-circuit
breaking
capacity

Ultimate
[Icu]
(kA r.m.s.)

IEC 60947-2
K 60947-2

AC600/660V, 50-60Hz

7.5

10

18

AC480/500V, 50-60Hz

10

14

25

AC440/460V, 50-60Hz

18

25

35

AC380/415V, 50-60Hz

25/18

35/25

42/36

AC220/240V, 50-60Hz

35

50

65

DC250V

10

14

18

DC125V

15

20

25

Service [Ics] % of [Icu]


Trip
mechanism
Thermal
magnetic
& Protection
characteristics

50

Fixed thermal,
Fixed instantaneous
Adjustable thermal,
Fixed instantaneous

INST

10 In

LTD

(0.8-0.9-1) In

INST

10 In

Direct mounting by screw


Mounting
Plug-in

Terminal connection

Both line & load side


for
Switchboard Line side only

1)

for Distribution board

1)

1)

Screw
Bus bar

Durability
(times)

Mechanical operation

25,000

Electrical operation

10,000

Dimensions
(mm)

2/3/4P

Width

1052)/105/140

Height

164

Depth

60

d
Weight (kg, breaker only)

2/3/4P

84
1.1/1.2/1.5

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.

68

MCCB

Accessories
Signal
1C, left-hand-side

Auxiliary switch

AUX 20C L1
1C, left-hand-side

Trip alarm switch


Shunt trip

ALT 20C L1

1)

Under voltage trip 2)

DC24V

DC100-110V

AC100-120V

SHT 20C A

SHT 20C F

AC200-230V

AC380-415V

AC440-480V

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

AC440-480V

UVT 20C J

UVT 20C L

UVT 20C N

UVT 20C P

UVT 20C Q

UVT 20C R

SHT 20C H

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.

Operating
Upper

Right

Left

S type

TFG 20CS U4

TFG 20CS R4

TFG 20CS L4

L type

TFG 20CL U4

Power supply direction


Operating Surface
handle1)
Extended

TFG 20CL L4
TFH 20CS

S type

TFH 20CL

L type
Motor operator 2)

DC24V

AC/DC110V

AC/DC220V

MOT 20C DC24

MOT 20C ADC110

MOT 20C ADC220

2 pole

3 pole

4 pole

MIF 20UG 3

MIF 20UG 3

MIF 20UG 4

Mechanical interlock

PLD 20UG

Padlock plate3)
1) For detail type information, please refer to page 197-205.
2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.

Mounting
For both line & load side

For line side only

Mounting base

TDM 20CF 3)

TDM 20CF

Connection 2C contact

CBM 20C 2

block 2)

CBM 20C 5

Structure
Plug-in1)

5C contact

1) Available for 3P breaker


2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.
3) 2EA are required for both line & load side plug-in type 3P breaker.

Terminal
2 pole (4EA/SET) 3 pole (6EA/SET) 4 pole (8EA/SET)

Terminal bus bar

TBB 20C 2

Cage terminal block


Terminal cover

2EA/SET

TBB 20C 4

4EA/SET

CTB 20C 3S

1)

Interpole barrier 2)

TBB 20C 3

3EA/SET

CTB 20C 4S

2 pole

3 pole

4 pole

TCF 20CP 3

TCF 20CP 3

TCF 20CP 4

TQQ 20C 3PLINE

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 4EA, 3 pole 4EA, 4 pole 6EA

Molded Case Circuit Breaker_ 69

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


Standard order code and unit
Fixed thermal & fixed instantaneous / Thermal magnetic trip
40/45
Model /
Breaking capacity at
AC380/415V

UCB250R
25/18kA

UCB250S
35/25kA

UCB250N
42/36kA

Rated
current
100A
125A
150A
160A
175A
200A
225A
250A
100A
125A
150A
160A
175A
200A
225A
250A
100A
125A
150A
160A
175A
200A
225A
250A

2 pole
Code
UCB250R 2PT4S0000C 00100
UCB250R 2PT4S0000C 00125
UCB250R 2PT4S0000C 00150
UCB250R 2PT4S0000C 00160
UCB250R 2PT4S0000C 00175
UCB250R 2PT4S0000C 00200
UCB250R 2PT4S0000C 00225
UCB250R 2PT4S0000C 00250
UCB250S 2PT4S0000C 00100
UCB250S 2PT4S0000C 00125
UCB250S 2PT4S0000C 00150
UCB250S 2PT4S0000C 00160
UCB250S 2PT4S0000C 00175
UCB250S 2PT4S0000C 00200
UCB250S 2PT4S0000C 00225
UCB250S 2PT4S0000C 00250
UCB250N 2PT4S0000C 00100
UCB250N 2PT4S0000C 00125
UCB250N 2PT4S0000C 00150
UCB250N 2PT4S0000C 00160
UCB250N 2PT4S0000C 00175
UCB250N 2PT4S0000C 00200
UCB250N 2PT4S0000C 00225
UCB250N 2PT4S0000C 00250

Unit
(EA)

10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

3 pole
Code
UCB250R 3PT4S0000C 00100
UCB250R 3PT4S0000C 00125
UCB250R 3PT4S0000C 00150
UCB250R 3PT4S0000C 00160
UCB250R 3PT4S0000C 00175
UCB250R 3PT4S0000C 00200
UCB250R 3PT4S0000C 00225
UCB250R 3PT4S0000C 00250
UCB250S 3PT4S0000C 00100
UCB250S 3PT4S0000C 00125
UCB250S 3PT4S0000C 00150
UCB250S 3PT4S0000C 00160
UCB250S 3PT4S0000C 00175
UCB250S 3PT4S0000C 00200
UCB250S 3PT4S0000C 00225
UCB250S 3PT4S0000C 00250
UCB250N 3PT4S0000C 00100
UCB250N 3PT4S0000C 00125
UCB250N 3PT4S0000C 00150
UCB250N 3PT4S0000C 00160
UCB250N 3PT4S0000C 00175
UCB250N 3PT4S0000C 00200
UCB250N 3PT4S0000C 00225
UCB250N 3PT4S0000C 00250

Unit
(EA)

10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

4 pole
Code
UCB250R 4PT4S0000C 00100
UCB250R 4PT4S0000C 00125
UCB250R 4PT4S0000C 00150
UCB250R 4PT4S0000C 00160
UCB250R 4PT4S0000C 00175
UCB250R 4PT4S0000C 00200
UCB250R 4PT4S0000C 00225
UCB250R 4PT4S0000C 00250
UCB250S 4PT4S0000C 00100
UCB250S 4PT4S0000C 00125
UCB250S 4PT4S0000C 00150
UCB250S 4PT4S0000C 00160
UCB250S 4PT4S0000C 00175
UCB250S 4PT4S0000C 00200
UCB250S 4PT4S0000C 00225
UCB250S 4PT4S0000C 00250
UCB250N 4PT4S0000C 00100
UCB250N 4PT4S0000C 00125
UCB250N 4PT4S0000C 00150
UCB250N 4PT4S0000C 00160
UCB250N 4PT4S0000C 00175
UCB250N 4PT4S0000C 00200
UCB250N 4PT4S0000C 00225
UCB250N 4PT4S0000C 00250

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

50
Model /
Breaking capacity at
AC380/415V

UCB250R
25/18kA

UCB250S
35/25kA

UCB250N
42/36kA

70

Rated
current
100A
125A
150A
160A
175A
200A
225A
250A
100A
125A
150A
160A
175A
200A
225A
250A
100A
125A
150A
160A
175A
200A
225A
250A

2 pole
Code
UCB250R 2PT5S0000C 00100
UCB250R 2PT5S0000C 00125
UCB250R 2PT5S0000C 00150
UCB250R 2PT5S0000C 00160
UCB250R 2PT5S0000C 00175
UCB250R 2PT5S0000C 00200
UCB250R 2PT5S0000C 00225
UCB250R 2PT5S0000C 00250
UCB250S 2PT5S0000C 00100
UCB250S 2PT5S0000C 00125
UCB250S 2PT5S0000C 00150
UCB250S 2PT5S0000C 00160
UCB250S 2PT5S0000C 00175
UCB250S 2PT5S0000C 00200
UCB250S 2PT5S0000C 00225
UCB250S 2PT5S0000C 00250
UCB250N 2PT5S0000C 00100
UCB250N 2PT5S0000C 00125
UCB250N 2PT5S0000C 00150
UCB250N 2PT5S0000C 00160
UCB250N 2PT5S0000C 00175
UCB250N 2PT5S0000C 00200
UCB250N 2PT5S0000C 00225
UCB250N 2PT5S0000C 00250

Unit
(EA)

10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

3 pole
Code
UCB250R 3PT5S0000C 00100
UCB250R 3PT5S0000C 00125
UCB250R 3PT5S0000C 00150
UCB250R 3PT5S0000C 00160
UCB250R 3PT5S0000C 00175
UCB250R 3PT5S0000C 00200
UCB250R 3PT5S0000C 00225
UCB250R 3PT5S0000C 00250
UCB250S 3PT5S0000C 00100
UCB250S 3PT5S0000C 00125
UCB250S 3PT5S0000C 00150
UCB250S 3PT5S0000C 00160
UCB250S 3PT5S0000C 00175
UCB250S 3PT5S0000C 00200
UCB250S 3PT5S0000C 00225
UCB250S 3PT5S0000C 00250
UCB250N 3PT5S0000C 00100
UCB250N 3PT5S0000C 00125
UCB250N 3PT5S0000C 00150
UCB250N 3PT5S0000C 00160
UCB250N 3PT5S0000C 00175
UCB250N 3PT5S0000C 00200
UCB250N 3PT5S0000C 00225
UCB250N 3PT5S0000C 00250

Unit
(EA)

10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

4 pole
Code
UCB250R 4PT5S0000C 00100
UCB250R 4PT5S0000C 00125
UCB250R 4PT5S0000C 00150
UCB250R 4PT5S0000C 00160
UCB250R 4PT5S0000C 00175
UCB250R 4PT5S0000C 00200
UCB250R 4PT5S0000C 00225
UCB250R 4PT5S0000C 00250
UCB250S 4PT5S0000C 00100
UCB250S 4PT5S0000C 00125
UCB250S 4PT5S0000C 00150
UCB250S 4PT5S0000C 00160
UCB250S 4PT5S0000C 00175
UCB250S 4PT5S0000C 00200
UCB250S 4PT5S0000C 00225
UCB250S 4PT5S0000C 00250
UCB250N 4PT5S0000C 00100
UCB250N 4PT5S0000C 00125
UCB250N 4PT5S0000C 00150
UCB250N 4PT5S0000C 00160
UCB250N 4PT5S0000C 00175
UCB250N 4PT5S0000C 00200
UCB250N 4PT5S0000C 00225
UCB250N 4PT5S0000C 00250

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

MCCB

Adjustable thermal & fixed instantaneous / Thermal magnetic trip


40/45
Model /
Breaking capacity at
AC380/415V

UCB250R
25/18kA

UCB250S
35/25kA

UCB250N
42/36kA

Rated
current
100A
125A
150A
160A
175A
200A
225A
250A
100A
125A
150A
160A
175A
200A
225A
250A
100A
125A
150A
160A
175A
200A
225A
250A

2 pole
Code
UCB250R 2PT4S0000C 00100F
UCB250R 2PT4S0000C 00125F
UCB250R 2PT4S0000C 00150F
UCB250R 2PT4S0000C 00160F
UCB250R 2PT4S0000C 00175F
UCB250R 2PT4S0000C 00200F
UCB250R 2PT4S0000C 00225F
UCB250R 2PT4S0000C 00250F
UCB250S 2PT4S0000C 00100F
UCB250S 2PT4S0000C 00125F
UCB250S 2PT4S0000C 00150F
UCB250S 2PT4S0000C 00160F
UCB250S 2PT4S0000C 00175F
UCB250S 2PT4S0000C 00200F
UCB250S 2PT4S0000C 00225F
UCB250S 2PT4S0000C 00250F
UCB250N 2PT4S0000C 00100F
UCB250N 2PT4S0000C 00125F
UCB250N 2PT4S0000C 00150F
UCB250N 2PT4S0000C 00160F
UCB250N 2PT4S0000C 00175F
UCB250N 2PT4S0000C 00200F
UCB250N 2PT4S0000C 00225F
UCB250N 2PT4S0000C 00250F

Unit
(EA)

10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

3 pole
Code
UCB250R 3PT4S0000C 00100F
UCB250R 3PT4S0000C 00125F
UCB250R 3PT4S0000C 00150F
UCB250R 3PT4S0000C 00160F
UCB250R 3PT4S0000C 00175F
UCB250R 3PT4S0000C 00200F
UCB250R 3PT4S0000C 00225F
UCB250R 3PT4S0000C 00250F
UCB250S 3PT4S0000C 00100F
UCB250S 3PT4S0000C 00125F
UCB250S 3PT4S0000C 00150F
UCB250S 3PT4S0000C 00160F
UCB250S 3PT4S0000C 00175F
UCB250S 3PT4S0000C 00200F
UCB250S 3PT4S0000C 00225F
UCB250S 3PT4S0000C 00250F
UCB250N 3PT4S0000C 00100F
UCB250N 3PT4S0000C 00125F
UCB250N 3PT4S0000C 00150F
UCB250N 3PT4S0000C 00160F
UCB250N 3PT4S0000C 00175F
UCB250N 3PT4S0000C 00200F
UCB250N 3PT4S0000C 00225F
UCB250N 3PT4S0000C 00250F

Unit
(EA)

10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

4 pole
Code
UCB250R 4PT4S0000C 00100F
UCB250R 4PT4S0000C 00125F
UCB250R 4PT4S0000C 00150F
UCB250R 4PT4S0000C 00160F
UCB250R 4PT4S0000C 00175F
UCB250R 4PT4S0000C 00200F
UCB250R 4PT4S0000C 00225F
UCB250R 4PT4S0000C 00250F
UCB250S 4PT4S0000C 00100F
UCB250S 4PT4S0000C 00125F
UCB250S 4PT4S0000C 00150F
UCB250S 4PT4S0000C 00160F
UCB250S 4PT4S0000C 00175F
UCB250S 4PT4S0000C 00200F
UCB250S 4PT4S0000C 00225F
UCB250S 4PT4S0000C 00250F
UCB250N 4PT4S0000C 00100F
UCB250N 4PT4S0000C 00125F
UCB250N 4PT4S0000C 00150F
UCB250N 4PT4S0000C 00160F
UCB250N 4PT4S0000C 00175F
UCB250N 4PT4S0000C 00200F
UCB250N 4PT4S0000C 00225F
UCB250N 4PT4S0000C 00250F

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

50
Model /
Breaking capacity at
AC380/415V

UCB250R
25/18kA

UCB250S
35/25kA

UCB250N
42/36kA

Rated
current
100A
125A
150A
160A
175A
200A
225A
250A
100A
125A
150A
160A
175A
200A
225A
250A
100A
125A
150A
160A
175A
200A
225A
250A

2 pole
Code
UCB250R 2PT5S0000C 00100F
UCB250R 2PT5S0000C 00125F
UCB250R 2PT5S0000C 00150F
UCB250R 2PT5S0000C 00160F
UCB250R 2PT5S0000C 00175F
UCB250R 2PT5S0000C 00200F
UCB250R 2PT5S0000C 00225F
UCB250R 2PT5S0000C 00250F
UCB250S 2PT5S0000C 00100F
UCB250S 2PT5S0000C 00125F
UCB250S 2PT5S0000C 00150F
UCB250S 2PT5S0000C 00160F
UCB250S 2PT5S0000C 00175F
UCB250S 2PT5S0000C 00200F
UCB250S 2PT5S0000C 00225F
UCB250S 2PT5S0000C 00250F
UCB250N 2PT5S0000C 00100F
UCB250N 2PT5S0000C 00125F
UCB250N 2PT5S0000C 00150F
UCB250N 2PT5S0000C 00160F
UCB250N 2PT5S0000C 00175F
UCB250N 2PT5S0000C 00200F
UCB250N 2PT5S0000C 00225F
UCB250N 2PT5S0000C 00250F

Unit
(EA)

10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

3 pole
Code
UCB250R 3PT5S0000C 00100F
UCB250R 3PT5S0000C 00125F
UCB250R 3PT5S0000C 00150F
UCB250R 3PT5S0000C 00160F
UCB250R 3PT5S0000C 00175F
UCB250R 3PT5S0000C 00200F
UCB250R 3PT5S0000C 00225F
UCB250R 3PT5S0000C 00250F
UCB250S 3PT5S0000C 00100F
UCB250S 3PT5S0000C 00125F
UCB250S 3PT5S0000C 00150F
UCB250S 3PT5S0000C 00160F
UCB250S 3PT5S0000C 00175F
UCB250S 3PT5S0000C 00200F
UCB250S 3PT5S0000C 00225F
UCB250S 3PT5S0000C 00250F
UCB250N 3PT5S0000C 00100F
UCB250N 3PT5S0000C 00125F
UCB250N 3PT5S0000C 00150F
UCB250N 3PT5S0000C 00160F
UCB250N 3PT5S0000C 00175F
UCB250N 3PT5S0000C 00200F
UCB250N 3PT5S0000C 00225F
UCB250N 3PT5S0000C 00250F

Unit
(EA)

10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10

4 pole
Code
UCB250R 4PT5S0000C 00100F
UCB250R 4PT5S0000C 00125F
UCB250R 4PT5S0000C 00150F
UCB250R 4PT5S0000C 00160F
UCB250R 4PT5S0000C 00175F
UCB250R 4PT5S0000C 00200F
UCB250R 4PT5S0000C 00225F
UCB250R 4PT5S0000C 00250F
UCB250S 4PT5S0000C 00100F
UCB250S 4PT5S0000C 00125F
UCB250S 4PT5S0000C 00150F
UCB250S 4PT5S0000C 00160F
UCB250S 4PT5S0000C 00175F
UCB250S 4PT5S0000C 00200F
UCB250S 4PT5S0000C 00225F
UCB250S 4PT5S0000C 00250F
UCB250N 4PT5S0000C 00100F
UCB250N 4PT5S0000C 00125F
UCB250N 4PT5S0000C 00150F
UCB250N 4PT5S0000C 00160F
UCB250N 4PT5S0000C 00175F
UCB250N 4PT5S0000C 00200F
UCB250N 4PT5S0000C 00225F
UCB250N 4PT5S0000C 00250F

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

Molded Case Circuit Breaker_ 71

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UCB type / 250AF |
UCB250H 42kA
UCB250L 50kA

UCB250H

UCB250L

Number of poles (P)

2, 3, 4

Degree of protection (with terminal cover)

IP20

Utilization category

Suitability of isolation
Protection

overload, inst., short-circuit


Rated current (A)

125,150,160,175,200,225,250

Rated insulation voltage [Ui] (V)


Rating

AC690
AC660

Rated operational voltage [Ue] (V)

DC250
Rated impulse withstand voltage [Uimp] (kV)

Rated
short-circuit
breaking
capacity

Ultimate
[Icu]
(kA r.m.s.)

IEC 60947-2
K 60947-2

AC600/660V, 50-60Hz

20

25

AC480/500V, 50-60Hz

30

35

AC440/460V, 50-60Hz

42

50

AC380/415V, 50-60Hz

42

50

AC220/240V, 50-60Hz

85

100

DC250V

25

40

DC125V

40

60

Service [Ics] % of [Icu]


Trip
mechanism
Thermal
& Protection
magnetic
characteristics

50

Fixed thermal,
Fixed instantaneous

INST

10 In

Adjustable thermal,

LTD

(0.8-0.9-1) In

Fixed instantaneous

INST

10 In

Direct mounting by screw


Mounting
Plug-in

Terminal connection

Both line & load side


for
Switchboard Line side only

1)

for Distribution board

1)

1)

Screw
Bus bar

Durability
(times)

Mechanical operation

25,000

Electrical operation

10,000

Dimensions
(mm)

2/3/4P

Width

1052)/105/140

Height

165

Depth

d
Weight (kg, breaker only)

2/3/4P

60
84.5
1.1/1.3/1.6

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.

72

MCCB

Accessories
Signal
Auxiliary switch

2C, left-hand-side

AUX 12FG L1

AUX 12FG L2

1C, right-hand-side 1C, left-hand-side

Trip alarm switch


Shunt trip

1C, left-hand-side

1)

Under voltage trip 2)

ALT 12FG R1

ALT 12FG L1

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

SHT 12FG A

SHT 12FG C

SHT 12FG F

SHT 12FG H

SHT 12FG B

SHT 12FG D

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

AC440-480V

UVT 12FG J

UVT 12FG L

UVT 12FG N

UVT 12FG P

UVT 12FG Q

UVT 12FG R

AC440-480V

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.

Operating
Upper

Right

Left

S type

TFG 20UGS U4

TFG 20UGS R4

TFG 20UGS L4

L type

TFG 20UGL U4

Power supply direction


Operating Surface
handle1)
Extended

TFG 20UGL L4
TFH 20UGS

S type

TFH 20UGL

L type
Motor operator 2)

DC24V

AC/DC110V

AC/DC220V

MOT 20G DC24

MOT 20G ADC110

MOT 20G ADC220

2 pole

3 pole

4 pole

MIF 20UG 3

MIF 20UG 3

MIF 20UG 4

Mechanical interlock

PLD 20UG

Padlock plate3)
1) For detail type information, please refer to page 197-205.
2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.

Mounting
For both line & load side

For line side only

Mounting base

TDM 20CF 3)

TDM 20CF

Connection 2C contact

CBM 20C 2

block 2)

CBM 20C 5

Structure
Plug-in1)

5C contact

1) Available for 3P breaker


2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.
3) 2EA are required for both line & load side plug-in type 3P breaker.

Terminal
2 pole (4EA/SET) 3 pole (6EA/SET) 4 pole (8EA/SET)

Terminal bus bar

TBB 20C 2

Cage terminal block


Terminal cover 1)
Interpole barrier 2)

2EA/SET

TBB 20C 3

TBB 20C 4

3EA/SET

4EA/SET

CTB 20C 3S

CTB 20C 4S

2 pole

3 pole

4 pole

TCF 20GP 3

TCF 20GP 3

TCF 20GP 4

TQQ 12FG 3PLINE

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 4EA, 3 pole 4EA, 4 pole 6EA

Molded Case Circuit Breaker_ 73

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


Standard order code and unit
Fixed thermal & fixed instantaneous / Thermal magnetic trip
40/45
Model /
Breaking
capacity at
AC380/415V

UCB250H
42kA

UCB250L
50kA

Rated
current

2 pole
Code

3 pole
Unit
(EA)

Code

4 pole
Unit
(EA)

Code

Unit
(EA)

100A

UCB250H 2PT4S0000C 00100

8 UCB250H 3PT4S0000C 00100 8

UCB250H 4PT4S0000C 00100 6

125A

UCB250H 2PT4S0000C 00125

8 UCB250H 3PT4S0000C 00125 8

UCB250H 4PT4S0000C 00125 6

150A

UCB250H 2PT4S0000C 00150

8 UCB250H 3PT4S0000C 00150 8

UCB250H 4PT4S0000C 00150 6

160A

UCB250H 2PT4S0000C 00160

8 UCB250H 3PT4S0000C 00160 8

UCB250H 4PT4S0000C 00160 6

175A

UCB250H 2PT4S0000C 00175

8 UCB250H 3PT4S0000C 00175 8

UCB250H 4PT4S0000C 00175 6

200A

UCB250H 2PT4S0000C 00200

8 UCB250H 3PT4S0000C 00200 8

UCB250H 4PT4S0000C 00200 6

225A

UCB250H 2PT4S0000C 00225

8 UCB250H 3PT4S0000C 00225 8

UCB250H 4PT4S0000C 00225 6

250A

UCB250H 2PT4S0000C 00250

8 UCB250H 3PT4S0000C 00250 8

UCB250H 4PT4S0000C 00250 6

100A

UCB250L 2PT4S0000C 00100

8 UCB250L 3PT4S0000C 00100

UCB250L 4PT4S0000C 00100

125A

UCB250L 2PT4S0000C 00125

8 UCB250L 3PT4S0000C 00125

UCB250L 4PT4S0000C 00125

150A

UCB250L 2PT4S0000C 00150

8 UCB250L 3PT4S0000C 00150

UCB250L 4PT4S0000C 00150

160A

UCB250L 2PT4S0000C 00160

8 UCB250L 3PT4S0000C 00160

UCB250L 4PT4S0000C 00160

175A

UCB250L 2PT4S0000C 00175

8 UCB250L 3PT4S0000C 00175

UCB250L 4PT4S0000C 00175

200A

UCB250L 2PT4S0000C 00200

8 UCB250L 3PT4S0000C 00200

UCB250L 4PT4S0000C 00200

225A

UCB250L 2PT4S0000C 00225

8 UCB250L 3PT4S0000C 00225

UCB250L 4PT4S0000C 00225

250A

UCB250L 2PT4S0000C 00250

8 UCB250L 3PT4S0000C 00250

UCB250L 4PT4S0000C 00250

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

50
Model /
Breaking
capacity at
AC380/415V

2 pole

3 pole

4 pole

Code

Unit
(EA)

Code

Unit
(EA)

100A

UCB250H 2PT5S0000C 00100

UCB250H 3PT5S0000C 00100

UCB250H 4PT5S0000C 00100 6

125A

UCB250H 2PT5S0000C 00125

UCB250H 3PT5S0000C 00125

UCB250H 4PT5S0000C 00125 6

150A

UCB250H 2PT5S0000C 00150

UCB250H 3PT5S0000C 00150

UCB250H 4PT5S0000C 00150 6

UCB250H

160A

UCB250H 2PT5S0000C 00160

UCB250H 3PT5S0000C 00160

UCB250H 4PT5S0000C 00160 6

42kA

175A

UCB250H 2PT5S0000C 00175

UCB250H 3PT5S0000C 00175

UCB250H 4PT5S0000C 00175 6

200A

UCB250H 2PT5S0000C 00200

UCB250H 3PT5S0000C 00200

UCB250H 4PT5S0000C 00200 6

225A

UCB250H 2PT5S0000C 00225

UCB250H 3PT5S0000C 00225

UCB250H 4PT5S0000C 00225 6

250A

UCB250H 2PT5S0000C 00250

UCB250H 3PT5S0000C 00250

UCB250H 4PT5S0000C 00250 6

100A

UCB250L 2PT5S0000C 00100

UCB250L 3PT5S0000C 00100

UCB250L 4PT5S0000C 00100

125A

UCB250L 2PT5S0000C 00125

UCB250L 3PT5S0000C 00125

UCB250L 4PT5S0000C 00125

150A

UCB250L 2PT5S0000C 00150

UCB250L 3PT5S0000C 00150

UCB250L 4PT5S0000C 00150

160A

UCB250L 2PT5S0000C 00160

UCB250L 3PT5S0000C 00160

UCB250L 4PT5S0000C 00160

UCB250L
50kA

74

Rated
current

Code

Unit
(EA)

175A

UCB250L 2PT5S0000C 00175

UCB250L 3PT5S0000C 00175

UCB250L 4PT5S0000C 00175

200A

UCB250L 2PT5S0000C 00200

UCB250L 3PT5S0000C 00200

UCB250L 4PT5S0000C 00200

225A

UCB250L 2PT5S0000C 00225

UCB250L 3PT5S0000C 00225

UCB250L 4PT5S0000C 00225

250A

UCB250L 2PT5S0000C 00250

UCB250L 3PT5S0000C 00250

UCB250L 4PT5S0000C 00250

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

MCCB

Adjustable thermal & fixed instantaneous / Thermal magnetic trip


40/45
Model /
Breaking
capacity at
AC380/415V

UCB250H
42kA

UCB250L
50kA

Rated
current

2 pole

3 pole

Code

Unit
(EA)

100A

UCB250H 2PT4S0000C 00100F

125A

UCB250H 2PT4S0000C 00125F

150A

UCB250H 2PT4S0000C 00150F

160A

UCB250H 2PT4S0000C 00160F

4 pole
Code

Unit
(EA)

UCB250H 3PT4S0000C 00100F 8

UCB250H 4PT4S0000C 00100F

UCB250H 3PT4S0000C 00125F 8

UCB250H 4PT4S0000C 00125F

UCB250H 3PT4S0000C 00150F 8

UCB250H 4PT4S0000C 00150F

UCB250H 3PT4S0000C 00160F 8

UCB250H 4PT4S0000C 00160F

Code

Unit
(EA)

175A

UCB250H 2PT4S0000C 00175F

UCB250H 3PT4S0000C 00175F 8

UCB250H 4PT4S0000C 00175F

200A

UCB250H 2PT4S0000C 00200F

UCB250H 3PT4S0000C 00200F 8

UCB250H 4PT4S0000C 00200F

225A

UCB250H 2PT4S0000C 00225F

UCB250H 3PT4S0000C 00225F 8

UCB250H 4PT4S0000C 00225F

250A

UCB250H 2PT4S0000C 00250F

UCB250H 3PT4S0000C 00250F 8

UCB250H 4PT4S0000C 00250F

100A

UCB250L 2PT4S0000C 00100F

UCB250L 3PT4S0000C 00100F

UCB250L 4PT4S0000C 00100F

125A

UCB250L 2PT4S0000C 00125F

UCB250L 3PT4S0000C 00125F

UCB250L 4PT4S0000C 00125F

150A

UCB250L 2PT4S0000C 00150F

UCB250L 3PT4S0000C 00150F

UCB250L 4PT4S0000C 00150F

160A

UCB250L 2PT4S0000C 00160F

UCB250L 3PT4S0000C 00160F

UCB250L 4PT4S0000C 00160F

175A

UCB250L 2PT4S0000C 00175F

UCB250L 3PT4S0000C 00175F

UCB250L 4PT4S0000C 00175F

200A

UCB250L 2PT4S0000C 00200F

UCB250L 3PT4S0000C 00200F

UCB250L 4PT4S0000C 00200F

225A

UCB250L 2PT4S0000C 00225F

UCB250L 3PT4S0000C 00225F

UCB250L 4PT4S0000C 00225F

250A

UCB250L 2PT4S0000C 00250F

UCB250L 3PT4S0000C 00250F

UCB250L 4PT4S0000C 00250F

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

50
Model /
Breaking
capacity at
AC380/415V

Rated
current

2 pole

3 pole

4 pole

Code

Unit
(EA)

Code

Unit
(EA)

Code

Unit
(EA)

100A

UCB250H 2PT5S0000C 00100F

UCB250H 3PT5S0000C 00100F

UCB250H 4PT5S0000C 00100F

125A

UCB250H 2PT5S0000C 00125F

UCB250H 3PT5S0000C 00125F

UCB250H 4PT5S0000C 00125F

150A

UCB250H 2PT5S0000C 00150F

UCB250H 3PT5S0000C 00150F

UCB250H 4PT5S0000C 00150F

UCB250H

160A

UCB250H 2PT5S0000C 00160F

UCB250H 3PT5S0000C 00160F

UCB250H 4PT5S0000C 00160F

42kA

175A

UCB250H 2PT5S0000C 00175F

UCB250H 3PT5S0000C 00175F

UCB250H 4PT5S0000C 00175F

200A

UCB250H 2PT5S0000C 00200F

UCB250H 3PT5S0000C 00200F

UCB250H 4PT5S0000C 00200F

225A

UCB250H 2PT5S0000C 00225F

UCB250H 3PT5S0000C 00225F

UCB250H 4PT5S0000C 00225F

250A

UCB250H 2PT5S0000C 00250F

UCB250H 3PT5S0000C 00250F

UCB250H 4PT5S0000C 00250F

100A

UCB250L 2PT5S0000C 00100F

UCB250L 3PT5S0000C 00100F

UCB250L 4PT5S0000C 00100F

125A

UCB250L 2PT5S0000C 00125F

UCB250L 3PT5S0000C 00125F

UCB250L 4PT5S0000C 00125F

150A

UCB250L 2PT5S0000C 00150F

UCB250L 3PT5S0000C 00150F

UCB250L 4PT5S0000C 00150F

160A

UCB250L 2PT5S0000C 00160F

UCB250L 3PT5S0000C 00160F

UCB250L 4PT5S0000C 00160F

UCB250L
50kA

175A

UCB250L 2PT5S0000C 00175F

UCB250L 3PT5S0000C 00175F

UCB250L 4PT5S0000C 00175F

200A

UCB250L 2PT5S0000C 00200F

UCB250L 3PT5S0000C 00200F

UCB250L 4PT5S0000C 00200F

225A

UCB250L 2PT5S0000C 00225F

UCB250L 3PT5S0000C 00225F

UCB250L 4PT5S0000C 00225F

250A

UCB250L 2PT5S0000C 00250F

UCB250L 3PT5S0000C 00250F

UCB250L 4PT5S0000C 00250F

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

Molded Case Circuit Breaker_ 75

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UCB type / 400AF |
UCB400R 30kA
UCB400S 42kA
UCB400H 65kA
UCB400L 100kA

UCB400R

UCB400S

UCB400H

Number of poles (P)

2, 3, 4

Degree of protection (without terminal bus bar)

IP20

UCB400L

Utilization category
Suitability of isolation

overload, inst., short-circuit

Protection

250,300,320,350,400

Rated current (A)

AC690

Rated insulation voltage [Ui] (V)


Rating

AC660

Rated operational voltage [Ue] (V)

DC250
Rated impulse withstand voltage [Uimp] (kV)

Rated
short-circuit
Ultimate
breaking
[Icu]
capacity
(kA r.m.s.)
IEC 60947-2
K 60947-2

AC600/660V, 50-60Hz

18

22

25

30

AC480/500V, 50-60Hz

18

25

35

65

AC440/460V, 50-60Hz

25

35

50

85

AC380/415V, 50-60Hz

30

42

65

100

AC220/240V, 50-60Hz

35

50

85

125

DC250V

14

25

40

40

DC125V

20

30

50

60

Service [Ics] % of [Icu]


Trip
mechanism Thermal
& Protection magnetic
characteristics

50

Fixed thermal,
Fixed instantaneous
Adjustable thermal,
Fixed instantaneous

INST

10 In

LTD

(0.8 0.9 1) In

INST

10 In

Direct mounting by screw


Mounting

Plug-in

Terminal connection

Both line & load side


for
Switchboard Line side only

1)

1)

Screw
Bus bar

Durability
(times)

Dimensions
(mm)

Mechanical operation

20,000

Electrical operation

2/3/4P

6,000
a

Width

140 /140/185

Height

257

Depth

110

d
Weight (kg, breaker only) 2/3/4P

2)

145
4/4.5/5.4

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.

76

MCCB

Accessories
Signal
1C, right-hand-side

Auxiliary switch

AUX 46D R1
1C, left-hand-side

Trip alarm switch


Shunt trip

ALT 46D L1

1)

Under voltage trip 2)

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

SHT 46D A

SHT 46D C

SHT 46D F

SHT 46D H

SHT 46D B

SHT 46D D

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

AC440-480V

UVT 46D L

UVT 46D N

UVT 46D P

UVT 46D Q

UVT 46D R

UVT 46D J

AC440-480V

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.

Operating
Power supply direction
Operating
Surface S type
handle 1)
Extended S type
Motor operator 2)

Upper

Right

Left

TFG 46DS U2

TFG 46DS R2

TFG 46DS L2

DC24V

AC/DC110V

AC/DC220V

MOT 40D DC24

MOT 40D ADC110

MOT 40D ADC220

2 pole

3 pole

4 pole

MIF 40D 3

MIF 40D 3

MIF 40D 4

TFH 46DS

Mechanical interlock

PLD 40D

Padlock plate3)
Extension handle

THA 46D

4)

1) For detail type information, please refer to page no. 197-205.


2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.
4) Supplied as standard component

Mounting
Structure
Plug-in 1)

Mounting base

For both line & load side

For line side only

TDM 4BA 3)

TDM 4BA

Connection 2C contact

TYA 5/2 4)

block 2)

TYA 5/5 4)

5C contact

1) Available for 3P breaker


2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.
3) 2EA are required for both line & load side plug-in type 3P breaker.
4) TYA type connection blocks are to be installed with separate mounting angle. Separate mounting angle is not supplied.

Terminal
2 pole (4EA/SET) 3 pole (6EA/SET) 4 pole (8EA/SET)

Terminal bus bar

TBB 4S 2

Cage terminal block

TBB 4S 4
4EA/SET

CTB 40D 3S
2 pole

Terminal cover 1)
Interpole barrier 2)

TBB 4S 3

3EA/SET

TCF 40D 3
2EA/SET

CTB 40D 4S
3 pole

4 pole

TCF 40D 3

TCF 40D 4

TQQ 4BA 3PLINE

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 4EA, 3 pole 4EA, 4 pole 6EA

Molded Case Circuit Breaker_ 77

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


Standard order code and unit
Fixed thermal & fixed instantaneous / Thermal magnetic trip
40/45
Model /
Breaking capacity at
AC380/415V

UCB400R
30kA

UCB400S
42kA

UCB400H
65kA

UCB400L
100kA

Rated
current

2 pole
Code

Unit
(EA)

3 pole
Code

Unit
(EA)

4 pole
Code

Unit
(EA)

250A

UCB400R 2PT4S0000C 00250

UCB400R 3PT4S0000C 00250

UCB400R 4PT4S0000C 00250

300A

UCB400R 2PT4S0000C 00300

UCB400R 3PT4S0000C 00300

UCB400R 4PT4S0000C 00300

320A

UCB400R 2PT4S0000C 00320

UCB400R 3PT4S0000C 00320

UCB400R 4PT4S0000C 00320

350A

UCB400R 2PT4S0000C 00350

UCB400R 3PT4S0000C 00350

UCB400R 4PT4S0000C 00350

400A

UCB400R 2PT4S0000C 00400

UCB400R 3PT4S0000C 00400

UCB400R 4PT4S0000C 00400

250A

UCB400S 2PT4S0000C 00250

UCB400S 3PT4S0000C 00250

UCB400S 4PT4S0000C 00250

300A

UCB400S 2PT4S0000C 00300

UCB400S 3PT4S0000C 00300

UCB400S 4PT4S0000C 00300

320A

UCB400S 2PT4S0000C 00320

UCB400S 3PT4S0000C 00320

UCB400S 4PT4S0000C 00320

350A

UCB400S 2PT4S0000C 00350

UCB400S 3PT4S0000C 00350

UCB400S 4PT4S0000C 00350

400A

UCB400S 2PT4S0000C 00400

UCB400S 3PT4S0000C 00400

UCB400S 4PT4S0000C 00400

250A

UCB400H 2PT4S0000C 00250

UCB400H 3PT4S0000C 00250

UCB400H 4PT4S0000C 00250

300A

UCB400H 2PT4S0000C 00300

UCB400H 3PT4S0000C 00300

UCB400H 4PT4S0000C 00300

320A

UCB400H 2PT4S0000C 00320

UCB400H 3PT4S0000C 00320

UCB400H 4PT4S0000C 00320

350A

UCB400H 2PT4S0000C 00350

UCB400H 3PT4S0000C 00350

UCB400H 4PT4S0000C 00350

400A

UCB400H 2PT4S0000C 00400

UCB400H 3PT4S0000C 00400

UCB400H 4PT4S0000C 00400

250A

UCB400L 2PT4S0000C 00250

UCB400L 3PT4S0000C 00250

UCB400L 4PT4S0000C 00250

300A

UCB400L 2PT4S0000C 00300

UCB400L 3PT4S0000C 00300

UCB400L 4PT4S0000C 00300

320A

UCB400L 2PT4S0000C 00320

UCB400L 3PT4S0000C 00320

UCB400L 4PT4S0000C 00320

350A

UCB400L 2PT4S0000C 00350

UCB400L 3PT4S0000C 00350

UCB400L 4PT4S0000C 00350

400A

UCB400L 2PT4S0000C 00400

UCB400L 3PT4S0000C 00400

UCB400L 4PT4S0000C 00400

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

50
Model /
Breaking capacity at
AC380/415V

UCB400R
30kA

UCB400S
42kA

UCB400H
65kA

UCB400L
100kA

78

Rated
current

2 pole
Code

Unit
(EA)

3 pole
Code

Unit
(EA)

4 pole
Code

Unit
(EA)

250A

UCB400R 2PT5S0000C 00250

UCB400R 3PT5S0000C 00250

UCB400R 4PT5S0000C 00250

300A

UCB400R 2PT5S0000C 00300

UCB400R 3PT5S0000C 00300

UCB400R 4PT5S0000C 00300

320A

UCB400R 2PT5S0000C 00320

UCB400R 3PT5S0000C 00320

UCB400R 4PT5S0000C 00320

350A

UCB400R 2PT5S0000C 00350

UCB400R 3PT5S0000C 00350

UCB400R 4PT5S0000C 00350

400A

UCB400R 2PT5S0000C 00400

UCB400R 3PT5S0000C 00400

UCB400R 4PT5S0000C 00400

250A

UCB400S 2PT5S0000C 00250

UCB400S 3PT5S0000C 00250

UCB400S 4PT5S0000C 00250

300A

UCB400S 2PT5S0000C 00300

UCB400S 3PT5S0000C 00300

UCB400S 4PT5S0000C 00300

320A

UCB400S 2PT5S0000C 00320

UCB400S 3PT5S0000C 00320

UCB400S 4PT5S0000C 00320

350A

UCB400S 2PT5S0000C 00350

UCB400S 3PT5S0000C 00350

UCB400S 4PT5S0000C 00350

400A

UCB400S 2PT5S0000C 00400

UCB400S 3PT5S0000C 00400

UCB400S 4PT5S0000C 00400

250A

UCB400H 2PT5S0000C 00250

UCB400H 3PT5S0000C 00250

UCB400H 4PT5S0000C 00250

300A

UCB400H 2PT5S0000C 00300

UCB400H 3PT5S0000C 00300

UCB400H 4PT5S0000C 00300

320A

UCB400H 2PT5S0000C 00320

UCB400H 3PT5S0000C 00320

UCB400H 4PT5S0000C 00320

350A

UCB400H 2PT5S0000C 00350

UCB400H 3PT5S0000C 00350

UCB400H 4PT5S0000C 00350

400A

UCB400H 2PT5S0000C 00400

UCB400H 3PT5S0000C 00400

UCB400H 4PT5S0000C 00400

250A

UCB400L 2PT5S0000C 00250

UCB400L 3PT5S0000C 00250

UCB400L 4PT5S0000C 00250

300A

UCB400L 2PT5S0000C 00300

UCB400L 3PT5S0000C 00300

UCB400L 4PT5S0000C 00300

320A

UCB400L 2PT5S0000C 00320

UCB400L 3PT5S0000C 00320

UCB400L 4PT5S0000C 00320

350A

UCB400L 2PT5S0000C 00350

UCB400L 3PT5S0000C 00350

UCB400L 4PT5S0000C 00350

400A

UCB400L 2PT5S0000C 00400

UCB400L 3PT5S0000C 00400

UCB400L 4PT5S0000C 00400

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

MCCB

Adjustable thermal & fixed instantaneous / Thermal magnetic trip


40/45
Model /
Breaking capacity at
AC380/415V

UCB400R
30kA

UCB400S
42kA

UCB400H
65kA

UCB400L
100kA

Rated
current

2 pole
Code

Unit
(EA)

3 pole
Code

Unit
(EA)

4 pole
Code

Unit
(EA)

250A

UCB400R 2PT4S0000C 00250F 3

UCB400R 3PT4S0000C 00250F 3

UCB400R 4PT4S0000C 00250F 2

300A

UCB400R 2PT4S0000C 00300F 3

UCB400R 3PT4S0000C 00300F 3

UCB400R 4PT4S0000C 00300F 2

320A

UCB400R 2PT4S0000C 00320F 3

UCB400R 3PT4S0000C 00320F 3

UCB400R 4PT4S0000C 00320F 2

350A

UCB400R 2PT4S0000C 00350F 3

UCB400R 3PT4S0000C 00350F 3

UCB400R 4PT4S0000C 00350F 2

400A

UCB400R 2PT4S0000C 00400F 3

UCB400R 3PT4S0000C 00400F 3

UCB400R 4PT4S0000C 00400F 2

250A

UCB400S 2PT4S0000C 00250F

UCB400S 3PT4S0000C 00250F

UCB400S 4PT4S0000C 00250F

300A

UCB400S 2PT4S0000C 00300F

UCB400S 3PT4S0000C 00300F

UCB400S 4PT4S0000C 00300F

320A

UCB400S 2PT4S0000C 00320F

UCB400S 3PT4S0000C 00320F

UCB400S 4PT4S0000C 00320F

350A

UCB400S 2PT4S0000C 00350F

UCB400S 3PT4S0000C 00350F

UCB400S 4PT4S0000C 00350F

400A

UCB400S 2PT4S0000C 00400F

UCB400S 3PT4S0000C 00400F

UCB400S 4PT4S0000C 00400F

250A

UCB400H 2PT4S0000C 00250F 3

UCB400H 3PT4S0000C 00250F 3

UCB400H 4PT4S0000C 00250F 2

300A

UCB400H 2PT4S0000C 00300F 3

UCB400H 3PT4S0000C 00300F 3

UCB400H 4PT4S0000C 00300F 2

320A

UCB400H 2PT4S0000C 00320F 3

UCB400H 3PT4S0000C 00320F 3

UCB400H 4PT4S0000C 00320F 2

350A

UCB400H 2PT4S0000C 00350F 3

UCB400H 3PT4S0000C 00350F 3

UCB400H 4PT4S0000C 00350F 2

400A

UCB400H 2PT4S0000C 00400F 3

UCB400H 3PT4S0000C 00400F 3

UCB400H 4PT4S0000C 00400F 2

250A

UCB400L 2PT4S0000C 00250F

UCB400L 3PT4S0000C 00250F

UCB400L 4PT4S0000C 00250F

300A

UCB400L 2PT4S0000C 00300F

UCB400L 3PT4S0000C 00300F

UCB400L 4PT4S0000C 00300F

320A

UCB400L 2PT4S0000C 00320F

UCB400L 3PT4S0000C 00320F

UCB400L 4PT4S0000C 00320F

350A

UCB400L 2PT4S0000C 00350F

UCB400L 3PT4S0000C 00350F

UCB400L 4PT4S0000C 00350F

400A

UCB400L 2PT4S0000C 00400F

UCB400L 3PT4S0000C 00400F

UCB400L 4PT4S0000C 00400F

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

50
Model /
Breaking capacity at
AC380/415V

UCB400R
30kA

UCB400S
42kA

UCB400H
65kA

UCB400L
100kA

Rated
current

2 pole
Code

Unit
(EA)

3 pole
Code

Unit
(EA)

4 pole
Code

Unit
(EA)

Specification Category

250A

UCB400R 2PT5S0000C 00250F 3

UCB400R 3PT5S0000C 00250F 3

UCB400R 4PT5S0000C 00250F

300A

UCB400R 2PT5S0000C 00300F 3

UCB400R 3PT5S0000C 00300F 3

UCB400R 4PT5S0000C 00300F

320A

UCB400R 2PT5S0000C 00320F 3

UCB400R 3PT5S0000C 00320F 3

UCB400R 4PT5S0000C 00320F

350A

UCB400R 2PT5S0000C 00350F 3

UCB400R 3PT5S0000C 00350F 3

UCB400R 4PT5S0000C 00350F

400A

UCB400R 2PT5S0000C 00400F 3

UCB400R 3PT5S0000C 00400F 3

UCB400R 4PT5S0000C 00400F

250A

UCB400S 2PT5S0000C 00250F

UCB400S 3PT5S0000C 00250F

UCB400S 4PT5S0000C 00250F

300A

UCB400S 2PT5S0000C 00300F

UCB400S 3PT5S0000C 00300F

UCB400S 4PT5S0000C 00300F

320A

UCB400S 2PT5S0000C 00320F

UCB400S 3PT5S0000C 00320F

UCB400S 4PT5S0000C 00320F

350A

UCB400S 2PT5S0000C 00350F

UCB400S 3PT5S0000C 00350F

400A

UCB400S 2PT5S0000C 00400F

UCB400S 3PT5S0000C 00400F

250A

UCB400H 2PT5S0000C 00250F 3

UCB400H 3PT5S0000C 00250F 3

300A

UCB400H 2PT5S0000C 00300F 3

UCB400H 3PT5S0000C 00300F 3

320A

UCB400H 2PT5S0000C 00320F 3

UCB400H 3PT5S0000C 00320F 3

Screw type
terminal
UCB400S 4PT5S0000C 00400F 2
connection,
UCB400H 4PT5S0000C 00250F 2 No option,
UCB400H 4PT5S0000C 00300F 2
50/60Hz
UCB400H 4PT5S0000C 00320F 2

350A

UCB400H 2PT5S0000C 00350F 3

UCB400H 3PT5S0000C 00350F 3

UCB400H 4PT5S0000C 00350F 2

400A

UCB400H 2PT5S0000C 00400F 3

UCB400H 3PT5S0000C 00400F 3

UCB400H 4PT5S0000C 00400F 2

250A

UCB400L 2PT5S0000C 00250F

UCB400L 3PT5S0000C 00250F

UCB400L 4PT5S0000C 00250F

300A

UCB400L 2PT5S0000C 00300F

UCB400L 3PT5S0000C 00300F

UCB400L 4PT5S0000C 00300F

320A

UCB400L 2PT5S0000C 00320F

UCB400L 3PT5S0000C 00320F

UCB400L 4PT5S0000C 00320F

350A

UCB400L 2PT5S0000C 00350F

UCB400L 3PT5S0000C 00350F

UCB400L 4PT5S0000C 00350F

400A

UCB400L 2PT5S0000C 00400F

UCB400L 3PT5S0000C 00400F

UCB400L 4PT5S0000C 00400F

UCB400S 4PT5S0000C 00350F

MCCB
/M2

Molded Case Circuit Breaker_ 79

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UCB type / 630AF |
UCB630R 45kA
UCB630S 65kA
UCB630H 85kA
UCB630L 100kA

UCB630R

UCB630S

UCB630H

Number of poles (P)

2, 3, 4

Degree of protection (without terminal bus bar)

IP20

UCB630L

Utilization category
Suitability of isolation

overload, inst., short-circuit

Protection

500, 630

Rated current (A)

AC690

Rated insulation voltage [Ui] (V)


Rating

AC660

Rated operational voltage [Ue] (V)

DC250
Rated impulse withstand voltage [Uimp] (kV)

Rated
short-circuit
Ultimate
breaking
[Icu]
capacity
(kA r.m.s.)
IEC 60947-2
K 60947-2

AC600/660V, 50-60Hz

22

25

35

35

AC480/500V, 50-60Hz

25

45

50

65

AC440/460V, 50-60Hz

35

50

65

85

AC380/415V, 50-60Hz

45

65

85

100

AC220/240V, 50-60Hz

50

100

100

125

DC250V

20

40

40

40

DC125V

30

50

50

60

Service [Ics] % of [Icu]


Trip
mechanism Thermal
& Protection magnetic
characteristics

50

Fixed thermal,
Fixed instantaneous
Adjustable thermal,
Fixed instantaneous

INST

10 In

LTD

(0.8 0.9 1) In

INST

10 In

Direct mounting by screw


Mounting

Plug-in

1)

Both line & load side


for
Switchboard Line side only

1)

Screw
Terminal connection
Durability
(times)

Dimensions
(mm)

Bus bar

Mechanical operation

20,000

Electrical operation

2/3/4P

6,000
a

Width

210 /210/280

Height

280

Depth

110

d
Weight (kg, breaker only) 2/3/4P

2)

145
8.7/9.5/12.5

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.

80

MCCB

Accessories
Signal
1C, right-hand-side

Auxiliary switch

AUX 46D R1
1C, left-hand-side

Trip alarm switch

ALT 46D L1

Shunt trip 1)
Under voltage trip 2)

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

SHT 46D A

SHT 46D C

SHT 46D F

SHT 46D H

SHT 46D B

SHT 46D D

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

AC440-480V

UVT 46D L

UVT 46D N

UVT 46D P

UVT 46D Q

UVT 46D R

UVT 46D J

AC440-480V

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.

Operating
Upper
TFG 46DS U2

Power supply direction


Operating
Surface S type
handle 1)
Extended S type

Right
TFG 46DS R2
TFH 46DS
AC/DC110V
MOT 68E ADC110
3 pole
MIF 80E 3
PLD 40D
THA 46D

DC24V
MOT 68E DC24
2 pole
MIF 80E 3

Motor operator 2)
Mechanical interlock
Padlock plate3)
Extension handle 4)

Left
TFG 46DS L2
AC/DC220V
MOT 68E ADC220
4 pole
MIF 80E 4
`

1) For detail type information, please refer to page 197-205.


2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.
4) Supplied as standard component

Mounting
Plug-in 1)

Structure
Mounting base
Connection 2C contact
block 2)
5C contact

For both line & load side


TDM 5BA 3)
TYA 5/2 4)
TYA 5/5 4)

For line side only


TDM 5BA

1) Available for 3P breaker


2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.
3) 2EA are required for both line & load side plug-in type 3P breaker.
4) TYA type connection blocks are to be installed with separate mounting angle. Separate mounting angle is not supplied.

Terminal
2 pole (4EA/SET) 3 pole (6EA/SET) 4 pole (8EA/SET)

Terminal bus bar

TBB 6S 2

Cage terminal block


Terminal cover 1)
Interpole barrier 2)

TBB 6S 3

TBB 6S 4

3EA/SET

4EA/SET

CTB 80E 3S

CTB 80E 4S

2 pole

3 pole

4 pole

TCF 80E 3

TCF 80E 3

TCF 80E 4

2EA/SET

TQQ 5BA 3PLINE

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 4EA, 3 pole 4EA, 4 pole 6EA

Standard order code and unit


Please refer to page 84.

Molded Case Circuit Breaker_ 81

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UCB type / 800AF |
UCB800R 45kA
UCB800S 65kA
UCB800H 85kA
UCB800L 100kA

UCB800R

UCB800S

UCB800H

Number of poles (P)

2, 3, 4

Degree of protection (without terminal bus bar)

IP20

UCB800L

Utilization category
Suitability of isolation

overload, inst., short-circuit

Protection

700, 800

Rated current (A)

AC690

Rated insulation voltage [Ui] (V)


Rating

AC660

Rated operational voltage [Ue] (V)

DC250
Rated impulse withstand voltage [Uimp] (kV)

AC600/660V, 50-60Hz

25

25

35

35

Rated
short-circuit
Ultimate
breaking
[Icu]
capacity
(kA r.m.s.)

AC480/500V, 50-60Hz

35

45

50

65

AC440/460V, 50-60Hz

35

50

65

85

AC380/415V, 50-60Hz

45

65

85

100

AC220/240V, 50-60Hz

50

100

100

125

IEC 60947-2
K 60947-2

DC250V

20

40

40

40

DC125V

30

50

50

60

Service [Ics] % of [Icu]


Trip
mechanism Thermal
& Protection magnetic
characteristics

50

Fixed thermal,
Fixed instantaneous
Adjustable thermal,
Fixed instantaneous

INST

10 In

LTD

(0.8 0.9 1) In

INST

10 In

Direct mounting by screw


Mounting

Plug-in

Terminal connection

1)

Both line & load side


for
Switchboard Line side only

1)

Screw
Bus bar

Durability
(times)

Dimensions
(mm)

Mechanical operation

10,000

Electrical operation

2/3/4P

3,000
a

Width

210 /210/280

Height

280

Depth

110

d
Weight (kg, breaker only) 2/3/4P

2)

145
8.7/9.5/12.5

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.

82

MCCB

Accessories
Signal
1C, right-hand-side

Auxiliary switch

AUX 46D R1
1C, left-hand-side

Trip alarm switch


Shunt trip

ALT 46D L1

1)

Under voltage trip 2)

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

SHT 46D A

SHT 46D C

SHT 46D F

SHT 46D H

SHT 46D B

SHT 46D D

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

AC440-480V

UVT 46D L

UVT 46D N

UVT 46D P

UVT 46D Q

UVT 46D R

UVT 46D J

AC440-480V

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.

Operating
Upper
TFG 46DS U2

Power supply direction


Operating
Surface S type
handle1)
Extended S type

Right
TFG 46DS R2
TFH 46DS
AC/DC110V
MOT 68E ADC110
3 pole
MIF 80E 3
PLD 40D
THA 46D

DC24V
MOT 68E DC24
2 pole
MIF 80E 3

Motor operator 2)
Mechanical interlock
Padlock plate3)
Extension handle 4)

Left
TFG 46DS L2
AC/DC220V
MOT 68E ADC220
4 pole
MIF 80E 4

1) For detail type information, please refer to page no. 197-205.


2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.
4) Supplied as standard component

Mounting

Plug-in 1)

Structure
Mounting base
Connection 2C contact
block 2)
5C contact

For both line & load side


TDM 5BA 3)
TYA 5/2 4)
TYA 5/5 4)

For line side only


TDM 5BA

1) Available for 3P breaker


2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.
3) 2EA are required for both line & load side plug-in type 3p breaker.
4) TYA type connection blocks are to be installed with separate mounting angle. Separate mounting angle is not supplied.

Terminal
2 pole (4EA/SET) 3 pole (6EA/SET) 4 pole (8EA/SET)

Terminal bus bar

TBB 8S 2

Cage terminal block


Terminal cover 1)
Interpole barrier 2)

TBB 8S 3

TBB 8S 4

3EA/SET

4EA/SET

CTB 80E 3S

CTB 80E 4S

2 pole

3 pole

4 pole

TCF 80E 3

TCF 80E 3

TCF 80E 4

2EA/SET

TQQ 5BA 3PLINE

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 4EA, 3 pole 4EA, 4 pole 6EA

Standard order code and unit


Please refer to page 85.

Molded Case Circuit Breaker_ 83

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


Standard order code and unit / UCB type 630AF
Fixed thermal & fixed instantaneous / Thermal magnetic trip
40/45
Model /
Breaking
capacity at
AC380/415V

Rated
current

2 pole
Code

3 pole
Unit
(EA)

Code

4 pole
Unit
(EA)

Code

Unit
(EA)

UCB630R
45kA

500A

UCB630R 2PT4S0000C 00500 2

UCB630R 3PT4S0000C 00500 2

UCB630R 4PT4S0000C 00500

630A

UCB630R 2PT4S0000C 00630 2

UCB630R 3PT4S0000C 00630 2

UCB630R 4PT4S0000C 00630

UCB630S
65kA

500A

UCB630S 2PT4S0000C 00500 2

UCB630S 3PT4S0000C 00500 2

UCB630S 4PT4S0000C 00500

630A

UCB630S 2PT4S0000C 00630 2

UCB630S 3PT4S0000C 00630 2

UCB630S 4PT4S0000C 00630

UCB630H
85kA

500A

UCB630H 2PT4S0000C 00500 2

UCB630H 3PT4S0000C 00500 2

UCB630H 4PT4S0000C 00500 1

630A

UCB630H 2PT4S0000C 00630 2

UCB630H 3PT4S0000C 00630 2

UCB630H 4PT4S0000C 00630 1

UCB630L
100kA

500A

UCB630L 2PT4S0000C 00500 2

UCB630L 3PT4S0000C 00500 2

UCB630L 4PT4S0000C 00500

630A

UCB630L 2PT4S0000C 00630 2

UCB630L 3PT4S0000C 00630 2

UCB630L 4PT4S0000C 00630

2 pole

3 pole

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

50
Model /
Breaking
capacity at
AC380/415V

Rated
current

Code

Unit
(EA)

Code

4 pole
Unit
(EA)

Code

Unit
(EA)

UCB630R
45kA

500A

UCB630R 2PT5S0000C 00500 2

UCB630R 3PT5S0000C 00500 2

UCB630R 4PT5S0000C 00500

630A

UCB630R 2PT5S0000C 00630 2

UCB630R 3PT5S0000C 00630 2

UCB630R 4PT5S0000C 00630

UCB630S
65kA

500A

UCB630S 2PT5S0000C 00500 2

UCB630S 3PT5S0000C 00500 2

UCB630S 4PT5S0000C 00500

630A

UCB630S 2PT5S0000C 00630 2

UCB630S 3PT5S0000C 00630 2

UCB630S 4PT5S0000C 00630

UCB630H
85kA

500A

UCB630H 2PT5S0000C 00500 2

UCB630H 3PT5S0000C 00500 2

UCB630H 4PT5S0000C 00500 1

630A

UCB630H 2PT5S0000C 00630 2

UCB630H 3PT5S0000C 00630 2

UCB630H 4PT5S0000C 00630 1

UCB630L
100kA

500A

UCB630L 2PT5S0000C 00500 2

UCB630L 3PT5S0000C 00500 2

UCB630L 4PT5S0000C 00500

630A

UCB630L 2PT5S0000C 00630 2

UCB630L 3PT5S0000C 00630 2

UCB630L 4PT5S0000C 00630

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

Adjustable thermal & fixed instantaneous / Thermal magnetic trip


40/45
Model /
Breaking
capacity at
AC380/415V

Rated
current

2 pole
Code

3 pole
Unit
(EA)

Code

4 pole
Unit
(EA)

Code

Unit
(EA)

UCB630R
45kA

500A

UCB630R 2PT4S0000C 00500F 2

UCB630R 3PT4S0000C 00500F 2

UCB630R 4PT4S0000C 00500F 1

630A

UCB630R 2PT4S0000C 00630F 2

UCB630R 3PT4S0000C 00630F 2

UCB630R 4PT4S0000C 00630F 1

UCB630S
65kA

500A

UCB630S 2PT4S0000C 00500F

UCB630S 3PT4S0000C 00500F 2

UCB630S 4PT4S0000C 00500F

630A

UCB630S 2PT4S0000C 00630F

UCB630S 3PT4S0000C 00630F 2

UCB630S 4PT4S0000C 00630F

UCB630H
85kA

500A

UCB630H 2PT4S0000C 00500F 2

UCB630H 3PT4S0000C 00500F 2

UCB630H 4PT4S0000C 00500F 1

630A

UCB630H 2PT4S0000C 00630F 2

UCB630H 3PT4S0000C 00630F 2

UCB630H 4PT4S0000C 00630F 1

UCB630L
100kA

500A

UCB630L 2PT4S0000C 00500F

UCB630L 3PT4S0000C 00500F 2

UCB630L 4PT4S0000C 00500F

630A

UCB630L 2PT4S0000C 00630F

UCB630L 3PT4S0000C 00630F 2

UCB630L 4PT4S0000C 00630F

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

50
Model /
Breaking
capacity at
AC380/415V

84

Rated
current

2 pole
Code

3 pole
Unit
(EA)

Code

4 pole
Unit
(EA)

Code

Unit
(EA)

UCB630R
45kA

500A

UCB630R 2PT5S0000C 00500F 2

UCB630R 3PT5S0000C 00500F 2

630A

UCB630R 2PT5S0000C 00630F 2

UCB630R 3PT5S0000C 00630F 2

UCB630R 4PT5S0000C 00630F 1

UCB630S
65kA

500A

UCB630S 2PT5S0000C 00500F 2

UCB630S 3PT5S0000C 00500F 2

UCB630S 4PT5S0000C 00500F 1

630A

UCB630S 2PT5S0000C 00630F 2

UCB630S 3PT5S0000C 00630F 2

UCB630S 4PT5S0000C 00630F 1

UCB630H
85kA

500A

UCB630H 2PT5S0000C 00500F 2

UCB630H 3PT5S0000C 00500F 2

UCB630H 4PT5S0000C 00500F 1

630A

UCB630H 2PT5S0000C 00630F 2

UCB630H 3PT5S0000C 00630F 2

UCB630H 4PT5S0000C 00630F 1

UCB630L
100kA

500A

UCB630L 2PT5S0000C 00500F 2

UCB630L 3PT5S0000C 00500F 2

UCB630L 4PT5S0000C 00500F 1

630A

UCB630L 2PT5S0000C 00630F 2

UCB630L 3PT5S0000C 00630F 2

UCB630L 4PT5S0000C 00630F 1

Specification Category

UCB630R 4PT5S0000C 00500F 1


Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

MCCB

Standard order code and unit / UCB type 800AF


Fixed thermal & fixed instantaneous / Thermal magnetic trip
40/45
Model /
Breaking
capacity at
AC380/415V

Rated
current

2 pole

3 pole

Code

Unit
(EA)

Code

4 pole
Unit
(EA)

Code

Unit
(EA)

UCB800R
45kA

700A

UCB800R 2PT4S0000C 00700

UCB800R 3PT4S0000C 00700 2

UCB800R 4PT4S0000C 00700

800A

UCB800R 2PT4S0000C 00800

UCB800R 3PT4S0000C 00800 2

UCB800R 4PT4S0000C 00800

UCB800S
65kA

700A

UCB800S 2PT4S0000C 00700

UCB800S 3PT4S0000C 00700 2

UCB800S 4PT4S0000C 00700

800A

UCB800S 2PT4S0000C 00800

UCB800S 3PT4S0000C 00800 2

UCB800S 4PT4S0000C 00800

UCB800H
85kA

700A

UCB800H 2PT4S0000C 00700

UCB800H 3PT4S0000C 00700 2

UCB800H 4PT4S0000C 00700 1

800A

UCB800H 2PT4S0000C 00800

UCB800H 3PT4S0000C 00800 2

UCB800H 4PT4S0000C 00800 1

UCB800L
100kA

700A

UCB800L 2PT4S0000C 00700

UCB800L 3PT4S0000C 00700 2

UCB800L 4PT4S0000C 00700

800A

UCB800L 2PT4S0000C 00800

UCB800L 3PT4S0000C 00800 2

UCB800L 4PT4S0000C 00800

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

50
Model /
Breaking
capacity at
AC380/415V

Rated
current

2 pole

3 pole

Code

Unit
(EA)

Code

4 pole
Unit
(EA)

Code

Unit
(EA)

UCB800R
45kA

700A

UCB800R 2PT5S0000C 00700

UCB800R 3PT5S0000C 00700 2

UCB800R 4PT5S0000C 00700

800A

UCB800R 2PT5S0000C 00800

UCB800R 3PT5S0000C 00800 2

UCB800R 4PT5S0000C 00800

UCB800S
65kA

700A

UCB800S 2PT5S0000C 00700

UCB800S 3PT5S0000C 00700 2

UCB800S 4PT5S0000C 00700

800A

UCB800S 2PT5S0000C 00800

UCB800S 3PT5S0000C 00800 2

UCB800S 4PT5S0000C 00800

UCB800H
85kA

700A

UCB800H 2PT5S0000C 00700

UCB800H 3PT5S0000C 00700 2

UCB800H 4PT5S0000C 00700 1

800A

UCB800H 2PT5S0000C 00800

UCB800H 3PT5S0000C 00800 2

UCB800H 4PT5S0000C 00800 1

UCB800L
100kA

700A

UCB800L 2PT5S0000C 00700

UCB800L 3PT5S0000C 00700 2

UCB800L 4PT5S0000C 00700

800A

UCB800L 2PT5S0000C 00800

UCB800L 3PT5S0000C 00800 2

UCB800L 4PT5S0000C 00800

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

Adjustable thermal & fixed instantaneous / Thermal magnetic trip


40/45
Model /
Breaking
capacity at
AC380/415V

Rated
current

2 pole
Code

3 pole
Unit
(EA)

Code

4 pole
Unit
(EA)

Code

Unit
(EA)

UCB800R
45kA

700A

UCB800R 2PT4S0000C 00700F 2

UCB800R 3PT4S0000C 00700F 2

UCB800R 4PT4S0000C 00700F 1

800A

UCB800R 2PT4S0000C 00800F 2

UCB800R 3PT4S0000C 00800F 2

UCB800R 4PT4S0000C 00800F 1

UCB800S
65kA

700A

UCB800S 2PT4S0000C 00700F

UCB800S 3PT4S0000C 00700F 2

UCB800S 4PT4S0000C 00700F

800A

UCB800S 2PT4S0000C 00800F

UCB800S 3PT4S0000C 00800F 2

UCB800S 4PT4S0000C 00800F

UCB800H
85kA

700A

UCB800H 2PT4S0000C 00700F 2

UCB800H 3PT4S0000C 00700F 2

UCB800H 4PT4S0000C 00700F 1

800A

UCB800H 2PT4S0000C 00800F 2

UCB800H 3PT4S0000C 00800F 2

UCB800H 4PT4S0000C 00800F 1

UCB800L
100kA

700A

UCB800L 2PT4S0000C 00700F

UCB800L 3PT4S0000C 00700F 2

UCB800L 4PT4S0000C 00700F

800A

UCB800L 2PT4S0000C 00800F

UCB800L 3PT4S0000C 00800F 2

UCB800L 4PT4S0000C 00800F

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

50
Model /
Breaking
capacity at
AC380/415V

Rated
current

2 pole
Code

3 pole
Unit
(EA)

Code

4 pole
Unit
(EA)

Code

Unit
(EA)

UCB800R
45kA

700A

UCB800R 2PT5S0000C 00700F 2

UCB800R 3PT5S0000C 00700F 2

800A

UCB800R 2PT5S0000C 00800F 2

UCB800R 3PT5S0000C 00800F 2

UCB800R 4PT5S0000C 00800F 1

UCB800S
65kA

700A

UCB800S 2PT5S0000C 00700F 2

UCB800S 3PT5S0000C 00700F 2

UCB800S 4PT5S0000C 00700F 1

800A

UCB800S 2PT5S0000C 00800F 2

UCB800S 3PT5S0000C 00800F 2

UCB800S 4PT5S0000C 00800F 1

UCB800H
85kA

700A

UCB800H 2PT5S0000C 00700F 2

UCB800H 3PT5S0000C 00700F 2

UCB800H 4PT5S0000C 00700F 1

800A

UCB800H 2PT5S0000C 00800F 2

UCB800H 3PT5S0000C 00800F 2

UCB800H 4PT5S0000C 00800F 1

UCB800L
100kA

700A

UCB800L 2PT5S0000C 00700F 2

UCB800L 3PT5S0000C 00700F 2

UCB800L 4PT5S0000C 00700F 1

800A

UCB800L 2PT5S0000C 00800F 2

UCB800L 3PT5S0000C 00800F 2

UCB800L 4PT5S0000C 00800F 1

Specification Category

UCB800R 4PT5S0000C 00700F 1


Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

Molded Case Circuit Breaker_ 85

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UCB type / 1000AF |
UCB1000S 100kA
UCB1000L 130kA

UCB1000S

UCB1000L

Number of poles (P)

3, 4

Degree of protection (without terminal bus bar)

IP20

Utilization category

Suitability of isolation
Protection

overload, inst., short-circuit


Rated current (A)

505-1,000

Rated insulation voltage [Ui] (V)

AC750

Rated operational voltage [Ue] (V)

AC690

Rating
Rated impulse withstand voltage [Uimp] (kV)

Rated
short-circuit
breaking
capacity

Ultimate
[Icu]
(kA r.m.s.)

IEC 60947-2
K 60947-2

AC600/660V, 50-60Hz

40

60

AC480/500V, 50-60Hz

75

100

AC440/460V, 50-60Hz

75

100

AC380/415V, 50-60Hz

100

130

AC220/240V, 50-60Hz

100

150

Service [Ics] % of [Icu]

Trip
mechanism
Electronic
& Protection
characteristics

50
1)

Long time delay

LTD

Short time delay

STD

(2-4-6-8-10) Ir

Instantaneous

INST

(3-6-8-10-11) In

Ground fault trip

GFT

(0.2-0.3-0.4) In

Pre-trip alarm

PTA

0.9 In

(0.5-1)

In (15 setting)

I2T lamp
Pick-up LED
Mounting

Direct mounting by screw

Terminal connection
Durability
(times)

Bus bar

Mechanical operation

10,000

Electrical operation

3,000

Dimensions
(mm)

3/4P

Width

210/280

210/280

Height

370

370

Depth

110

200

159

249

13/17

25/33

d
Weight (kg, breaker only)

3/4P

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) (0.5-1): (0.63-0.8-1)x(0.8-0.85-0.9-0.95-1)

86

MCCB

Accessories
Signal
1C, right-hand-side 2C, right-hand-side 3C, right-hand-side

Auxiliary switch

AUX 80NE R1

Trip alarm switch


Shunt trip

AUX 80NE R2

AUX 80NE R3

1C, right-hand-side
ALT 80NE R1

1)

Under voltage trip 2)

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

AC440-480V

SHT 120NE A

SHT 120NE C

SHT 120NE F

SHT 120NE H

SHT 120NE B

SHT 120NE D

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

AC440-480V

UVT 120NE J

UVT 120NE L

UVT 120NE N

UVT 120NE P

UVT 120NE Q

UVT 120NE R

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.

Operating
Motor operator 1)

DC24V

AC/DC110V

AC/DC220V

MOT 80NE DC24

MOT 80NE ADC110

MOT 80NE ADC220

Padlock plate2)

PLD 120NE

Extension handle 3)

THA 120NE

1) Motor operator is not recommended for marine application.


2) Padlock is not supplied.
3) Supplied as standard component

Terminal
Interpole barrier 1)

2EA/SET

TQQ 80NE 3P

1) Supplied as standard component


Required quantity for both line and load side of breaker: 3 pole 4EA, 4 pole 6EA

Standard order code and unit


Electronic - LTD, STD, INST trip & PTA
Model /
Breaking capacity at
AC380/415V

Rated
current

UCB1000S 100kA

1000A

UCB1000S 3PESB0000X 01000

UCB1000S 4PESB0000X 01000

3 pole
Code

4 pole
Unit
(EA)

Code

Unit
(EA)

UCB1000L 130kA

1000A

UCB1000L 3PESB0000X 01000

UCB1000L 4PESB0000X 01000

UCB1000S 100kA

1000A

UCB1000S 3PESB0000Y 01000

UCB1000S 4PESB0000Y 01000

UCB1000L 130kA

1000A

UCB1000L 3PESB0000Y 01000

UCB1000S 4PESB0000Y 01000

Specification
Bus bar type
terminal connection,
No option, 50Hz
Bus bar type
terminal connection,
No option, 60Hz

Category

MCCB
/M3

Electronic - LTD, STD, INST, GFT trip & PTA


Model /
Breaking capacity at
AC380/415V

Rated
current

UCB1000S 100kA

1000A

UCB1000S 3PEGB0000X 01000

UCB1000S 4PEGB0000X 01000

UCB1000L 130kA

1000A

UCB1000L 3PEGB0000X 01000

UCB1000L 4PEGB0000X 01000

UCB1000S 100kA

1000A

UCB1000S 3PEGB0000Y 01000

UCB1000S 4PEGB0000Y 01000

UCB1000L 130kA

1000A

UCB1000L 3PEGB0000Y 01000

UCB1000L 4PEGB0000Y 01000

3 pole
Code

4 pole
Unit
(EA)

Code

Unit
(EA)

Specification
Bus bar type
terminal connection,
No option, 50Hz
Bus bar type
terminal connection,
No option, 60Hz

Category

MCCB
/M3

Molded Case Circuit Breaker_ 87

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UCB type / 1250AF |
UCB1250S 100kA
UCB1250L 130kA

UCB1250S

UCB1250L

Number of poles (P)

3, 4

Degree of protection (without terminal bus bar)

IP20

Utilization category

Suitability of isolation
Protection

overload, inst., short-circuit


Rated current (A)

630-1,250

Rated insulation voltage [Ui] (V)

AC750

Rated operational voltage [Ue] (V)

AC690

Rating
Rated impulse withstand voltage [Uimp] (kV)

Rated
short-circuit
breaking
capacity

Ultimate
[Icu]
(kA r.m.s.)

IEC 60947-2
K 60947-2

AC600/660V, 50-60Hz

40

60

AC480/500V, 50-60Hz

75

100

AC440/460V, 50-60Hz

75

100

AC380/415V, 50-60Hz

100

130

AC220/240V, 50-60Hz

100

150

Service [Ics] % of [Icu]

Trip
mechanism
Electronic
& Protection
characteristics

50
1)

Long time delay

LTD

Short time delay

STD

(2-4-6-8-10) Ir

Instantaneous

INST

(3-6-8-10-11) In

Ground fault trip

GFT

(0.2-0.3-0.4) In

Pre-trip alarm

PTA

0.9 In

(0.5-1)

In (15 setting)

I2T lamp
Pick-up LED
Mounting

Direct mounting by screw

Terminal connection
Durability
(times)

Bus bar

Mechanical operation

10,000

Electrical operation (times)

3,000

Dimensions
(mm)

3/4P

Width

210/280

210/280

Height

370

370

Depth

110

200

159

249

13.5/17.5

25.5/33.5

d
Weight (kg, breaker only)

3/4P

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) (0.5-1): (0.63-0.8-1)x(0.8-0.85-0.9-0.95-1)

88

MCCB

Accessories
Signal
1C, right-hand-side 2C, right-hand-side 3C, right-hand-side

Auxiliary switch

AUX 80NE R1

Trip alarm switch


Shunt trip

AUX 80NE R2

AUX 80NE R3

1C, right-hand-side
ALT 80NE R1

1)

Under voltage trip 2)

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

AC440-480V

SHT 120NE A

SHT 120NE C

SHT 120NE F

SHT 120NE H

SHT 120NE B

SHT 120NE D

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

AC440-480V

UVT 120NE J

UVT 120NE L

UVT 120NE N

UVT 120NE P

UVT 120NE Q

UVT 120NE R

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.

Operating
Motor operator 1)

DC24V

AC/DC110V

AC/DC220V

MOT 80NE DC24

MOT 80NE ADC110

MOT 80NE ADC220

Padlock plate2)

PLD 120NE

Extension handle 3)

THA 120NE

1) Motor operator is not recommended for marine application.


2) Padlock is not supplied.
3) Supplied as standard component

Terminal
Interpole barrier 1)

2EA/SET

TQQ 80NE 3P

1) Supplied as standard component


Required quantity for both line and load side of breaker: 3 pole 4EA, 4 pole 6EA

Standard order code and unit


Electronic - LTD, STD, INST trip & PTA
Model /
Breaking capacity at
AC380/415V

Rated
current

UCB1250S 100kA

1250A

UCB1250S 3PESB0000X 01250

UCB1250S 4PESB0000X 01250

3 pole
Code

4 pole
Unit
(EA)

Code

Unit
(EA)

UCB1250L 130kA

1250A

UCB1250L 3PESB0000X 01250

UCB1250L 4PESB0000X 01250

UCB1250S 100kA

1250A

UCB1250S 3PESB0000Y 01250

UCB1250S 4PESB0000Y 01250

UCB1250L 130kA

1250A

UCB1250L 3PESB0000Y 01250

UCB1250L 4PESB0000Y 01250

Specification
Bus bar type
terminal connection,
No option, 50Hz
Bus bar type
terminal connection,
No option, 60Hz

Category

MCCB
/M3

Electronic - LTD, STD, INST, GFT trip & PTA


Model /
Breaking capacity at
AC380/415V

Rated
current

UCB1250S 100kA

1250A

UCB1250S 3PEGB0000X 01250

3 pole
Code

4 pole
Unit
(EA)

Code
UCB1250S 4PEGB0000X 01250

Unit
(EA)

UCB1250L 130kA

1250A

UCB1250L 3PEGB0000X 01250

UCB1250L 4PEGB0000X 01250

UCB1250S 100kA

1250A

UCB1250S 3PEGB0000Y 01250

UCB1250S 4PEGB0000Y 01250

UCB1250L 130kA

1250A

UCB1250L 3PEGB0000Y 01250

UCB1250L 4PEGB0000Y 01250

Specification
Bus bar type
terminal connection,
No option, 50Hz
Bus bar type
terminal connection,
No option, 60Hz

Category

MCCB
/M3

Molded Case Circuit Breaker_ 89

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UCB type / 1600AF |
UCB1600S 65kA

UCB1600S

Number of poles (P)

Degree of protection (without terminal bus bar)

IP20

Utilization category

Suitability of isolation
Protection

overload, inst., short-circuit


Rated current (A)

640-1,600

Rated insulation voltage [Ui] (V)

AC750

Rated operational voltage [Ue] (V)

AC690

Rating
Rated impulse withstand voltage [Uimp] (kV)

Rated
short-circuit
breaking
capacity

Ultimate
[Icu]
(kA r.m.s.)

IEC 60947-2
K 60947-2

AC600/660V, 50-60Hz

25

AC480/500V, 50-60Hz

35

AC440/460V, 50-60Hz

45

AC380/415V, 50-60Hz

65

AC220/240V, 50-60Hz

100

Service [Ics] % of [Icu]


Trip
mechanism
Electronic
& Protection
characteristics
Mounting

Long time delay

LTD

(0.4-1)

Instantaneous

INST

(2-3-4-5-6-7-8-10) In

In (8 setting)

Pick-up LED

Direct mounting by screw

Terminal connection
Durability
(times)

50
1)

Bus bar

Mechanical operation

10,000

Electrical operation

3,000

Dimensions
(mm)

3/4P

Width

210

Height

371

Depth

151

d
Weight (kg, breaker only)

3/4P

215
27

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) (0.4-1): (0.4-0.5-0.6-0.7-0.8-0.9-0.95-1)

90

MCCB

Accessories
Signal
1C, right-hand-side 2C, right-hand-side

Auxiliary switch

AUX 160NE R1

Shunt trip 1)
Under voltage trip 2)

AUX 160NE R2

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380V

SHT 160NE A

SHT 160NE C

SHT 160NE F

SHT 160NE H

SHT 160NE B

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380V

AC440V

UVT 160NE P

UVT 160NE Q

UVT 160NE R

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.

Operating
Operating handle
Motor operator

1)

TFH 160NE

Extended type

MOT 160NE AC220

AC220V

THA 160NE

Extension handle 2)

1) Motor operator is not recommended for marine application.


2) Supplied as standard component

Terminal
Terminal cover 1)
Interpole barrier 2)

TCF 160NE 3
4EA/SET

TQQ 160NE 3P

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component

Standard order code and unit


Electronic - LTD, INST trip
Model /
Breaking capacity at
AC380/415V
UCB1600S 65kA

3 pole

Rated
current

Code

Unit (EA)

1600A

UCB1600S 3PESB0000C 01600

Specification

Category

Bus bar type terminal connection, No option, 50/60Hz

MCCB/M3

Molded Case Circuit Breaker_ 91

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UPB type / 125AF |
UPB100S 85kA
UPB100H 100kA
UPB100L 130kA
UPB100X 150kA

UPB100S

Number of poles (P)


Degree of protection (with terminal cover)
Utilization category
Suitability of isolation
Protection
Thermal magnetic type
Rated current (A)
Electronic type
Rated insulation voltage [Ui] (V)
Rating
Rated operational voltage [Ue] (V)
Rated impulse withstand voltage [Uimp] (kV)
AC660/690V, 50-60Hz
Rated
AC480/500V, 50-60Hz
short-circuit
AC440/460V, 50-60Hz
Ultimate
breaking
[Icu]
AC380/415V, 50-60Hz
capacity
(kA r.m.s.) AC220/240V, 50-60Hz
DC250V
IEC 60947-2
DC125V
K 60947-2
Service [Ics] % of [Icu]
Fixed thermal,
Thermal
Fixed instantaneous INST
magnetic
Adjustable thermal, LTD
Trip
Fixed instantaneous INST
mechanism
Long time delay
LTD
& Protection
characteristics
Short time delay
STD
Electronic Instantaneous
INST
Pre-trip alarm
PTA
Pick-up LED
Direct mounting by screw
Both line & load side
Mounting
for
Plug-in
Switchboard Line side only
Screw
Terminal connection
Bus bar
Mechanical operation
Durability
(times)
Electrical operation
a
Width
Dimensions
b
Height
3/4P
(mm)
c
Depth
d
Weight (kg, breaker only) 3/4P

UPB100H

UPB100L

UPB100X

3, 4
IP20
A

10
50
65
85
100
501)
651)

overload, inst., short-circuit


15,16,20,25,30,32,40,50,60, 63,75, 80,100,125
50-125
AC750
AC690
DC500 1)
8
10
25
65
85
85
100
100
130
130
150
65 1)
85 1)
100 1)
100 1)
100

25
85
150
150
200
1001)
1)
100

10 In
(0.8 0.9 1) In
10 In
50,55,63,70,80,90,100,115,125
(NON-2-3-4-5-6-7-8-9-10) Ir
11 In
0.9 Ir

2)
2)

25,000
10,000
105/140
165
86.5
112
1.8/2.2

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) DC is not applicable for electronic breaker. 2) Available for 3P breaker

Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip 1)
Under voltage trip 2)

92

1C, right-hand-side
AUX 12UP R1
1C, left-hand-side
ALT 12UP L1
DC24V
SHT 12UP A
DC24V
UVT 12UP J

DC100-110V
SHT 12UP C
DC100-110V
UVT 12UP L

AC100-120V
SHT 12UP F
AC100-120V
UVT 12UP N

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.

AC200-230V
SHT 12UP H
AC200-230V
UVT 12UP P

AC380-415V
SHT 12UP B
AC380-415V
UVT 12UP Q

AC440-480V
SHT 12UP D
AC440-480V
UVT 12UP R

MCCB

Operating
Upper
TFG 12UPS U4
TFG 12UPL U4

Power supply direction


S type
Operating Surface
1)
L type
handle
S type
Extended
L type

Right
TFG 12UPS R4
TFH 12UPS
TFH 12UPL
AC/DC110V
MOT 12UP ADC110

DC24V
MOT 12UP DC24
3 pole
MIF 12UP 3

Motor operator 2)
Mechanical interlock

Left
TFG 12UPS L4
TFG 12UPL L4

Padlock plate3)

AC/DC220V
MOT 12UP ADC220
4 pole
MIF 12UP 4

PLD 12UP

1) For detail type information, please refer to page 197-205.


2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.

Mounting
Plug-in 1)

Structure
Mounting base
Connection 6C contact
block 2)
12C contact

For both line & load side


TDM 12NEP
CBM 26NE 6
CBM 26NE 63)

For line side only


TDM 12NEF

1) Available for 3P breaker


2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.
3) 2EA shall be ordered for 12C contact.

Terminal
Terminal bus bar
Cage terminal block
Terminal cover

1)

Interpole barrier 2)

3 pole (6EA/SET)
4 pole (8EA/SET)
3EA/SET
4EA/SET
3 pole
4 pole
4EA/SET

TBB 12NE 3
TBB 12NE 4
CTB 12UP 3S
CTB 12UP 4S
TCF 12UP 3
TCF 12UP 4
TQQ 12NE 3P

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 3 pole 4EA, 4 pole 6EA

Standard order code and unit


Electronic - LTD, STD, INST trip & PTA
Model /
Breaking
capacity at
AC380/415V

Rated
current

3 pole
Code

4 pole
Unit
(EA)

Code

Unit
(EA)

UPB100S 85kA

125A

UPB100S 3PESS0000X 00125

UPB100S 4PESS0000X 00125

UPB100H 100kA

125A

UPB100H 3PESS0000X 00125

UPB100H 4PESS0000X 00125

UPB100L 130kA

125A

UPB100L 3PESS0000X 00125

UPB100L 4PESS0000X 00125

UPB100X 150kA

125A

UPB100X 3PESS0000X 00125

UPB100X 4PESS0000X 00125

UPB100S 85kA

125A

UPB100S 3PESS0000Y 00125

UPB100S 4PESS0000Y 00125

UPB100H 100kA

125A

UPB100H 3PESS0000Y 00125

UPB100H 4PESS0000Y 00125

UPB100L 130kA

125A

UPB100L 3PESS0000Y 00125

UPB100L 4PESS0000Y 00125

UPB100X 150kA

125A

UPB100X 3PESS0000Y 00125

UPB100X 4PESS0000Y 00125

Specification

Category

Screw type
terminal
connection,
No option,
50Hz
MCCB/M3
Screw type
terminal
connection,
No option,
60Hz

Molded Case Circuit Breaker_ 93

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


Standard order code and unit
Fixed thermal & fixed instantaneous / Thermal magnetic trip
40/45
Model /
Breaking capacity at
AC380/415V

UPB100S
85kA

UPB100H
100kA

UPB100L
130kA

UPB100X
150kA

94

Rated
current
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A

3 pole
Code
UPB100S 3PT4S0000C 00015
UPB100S 3PT4S0000C 00016
UPB100S 3PT4S0000C 00020
UPB100S 3PT4S0000C 00025
UPB100S 3PT4S0000C 00030
UPB100S 3PT4S0000C 00032
UPB100S 3PT4S0000C 00040
UPB100S 3PT4S0000C 00050
UPB100S 3PT4S0000C 00060
UPB100S 3PT4S0000C 00063
UPB100S 3PT4S0000C 00075
UPB100S 3PT4S0000C 00080
UPB100S 3PT4S0000C 00100
UPB100S 3PT4S0000C 00125
UPB100H 3PT4S0000C 00015
UPB100H 3PT4S0000C 00016
UPB100H 3PT4S0000C 00020
UPB100H 3PT4S0000C 00025
UPB100H 3PT4S0000C 00030
UPB100H 3PT4S0000C 00032
UPB100H 3PT4S0000C 00040
UPB100H 3PT4S0000C 00050
UPB100H 3PT4S0000C 00060
UPB100H 3PT4S0000C 00063
UPB100H 3PT4S0000C 00075
UPB100H 3PT4S0000C 00080
UPB100H 3PT4S0000C 00100
UPB100H 3PT4S0000C 00125
UPB100L 3PT4S0000C 00015
UPB100L 3PT4S0000C 00016
UPB100L 3PT4S0000C 00020
UPB100L 3PT4S0000C 00025
UPB100L 3PT4S0000C 00030
UPB100L 3PT4S0000C 00032
UPB100L 3PT4S0000C 00040
UPB100L 3PT4S0000C 00050
UPB100L 3PT4S0000C 00060
UPB100L 3PT4S0000C 00063
UPB100L 3PT4S0000C 00075
UPB100L 3PT4S0000C 00080
UPB100L 3PT4S0000C 00100
UPB100L 3PT4S0000C 00125
UPB100X 3PT4S0000C 00015
UPB100X 3PT4S0000C 00016
UPB100X 3PT4S0000C 00020
UPB100X 3PT4S0000C 00025
UPB100X 3PT4S0000C 00030
UPB100X 3PT4S0000C 00032
UPB100X 3PT4S0000C 00040
UPB100X 3PT4S0000C 00050
UPB100X 3PT4S0000C 00060
UPB100X 3PT4S0000C 00063
UPB100X 3PT4S0000C 00075
UPB100X 3PT4S0000C 00080
UPB100X 3PT4S0000C 00100
UPB100X 3PT4S0000C 00125

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

4 pole
Code
UPB100S 4PT4S0000C 00015
UPB100S 4PT4S0000C 00016
UPB100S 4PT4S0000C 00020
UPB100S 4PT4S0000C 00025
UPB100S 4PT4S0000C 00030
UPB100S 4PT4S0000C 00032
UPB100S 4PT4S0000C 00040
UPB100S 4PT4S0000C 00050
UPB100S 4PT4S0000C 00060
UPB100S 4PT4S0000C 00063
UPB100S 4PT4S0000C 00075
UPB100S 4PT4S0000C 00080
UPB100S 4PT4S0000C 00100
UPB100S 4PT4S0000C 00125
UPB100H 4PT4S0000C 00015
UPB100H 4PT4S0000C 00016
UPB100H 4PT4S0000C 00020
UPB100H 4PT4S0000C 00025
UPB100H 4PT4S0000C 00030
UPB100H 4PT4S0000C 00032
UPB100H 4PT4S0000C 00040
UPB100H 4PT4S0000C 00050
UPB100H 4PT4S0000C 00060
UPB100H 4PT4S0000C 00063
UPB100H 4PT4S0000C 00075
UPB100H 4PT4S0000C 00080
UPB100H 4PT4S0000C 00100
UPB100H 4PT4S0000C 00125
UPB100L 4PT4S0000C 00015
UPB100L 4PT4S0000C 00016
UPB100L 4PT4S0000C 00020
UPB100L 4PT4S0000C 00025
UPB100L 4PT4S0000C 00030
UPB100L 4PT4S0000C 00032
UPB100L 4PT4S0000C 00040
UPB100L 4PT4S0000C 00050
UPB100L 4PT4S0000C 00060
UPB100L 4PT4S0000C 00063
UPB100L 4PT4S0000C 00075
UPB100L 4PT4S0000C 00080
UPB100L 4PT4S0000C 00100
UPB100L 4PT4S0000C 00125
UPB100X 4PT4S0000C 00015
UPB100X 4PT4S0000C 00016
UPB100X 4PT4S0000C 00020
UPB100X 4PT4S0000C 00025
UPB100X 4PT4S0000C 00030
UPB100X 4PT4S0000C 00032
UPB100X 4PT4S0000C 00040
UPB100X 4PT4S0000C 00050
UPB100X 4PT4S0000C 00060
UPB100X 4PT4S0000C 00063
UPB100X 4PT4S0000C 00075
UPB100X 4PT4S0000C 00080
UPB100X 4PT4S0000C 00100
UPB100X 4PT4S0000C 00125

Unit
(EA)

6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6

Specification

Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

MCCB

50
Model /
Breaking capacity at
AC380/415V

UPB100S
85kA

UPB100H
100kA

UPB100L
130kA

UPB100X
150kA

Rated
current
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A

3 pole
Code
UPB100S 3PT5S0000C 00015
UPB100S 3PT5S0000C 00016
UPB100S 3PT5S0000C 00020
UPB100S 3PT5S0000C 00025
UPB100S 3PT5S0000C 00030
UPB100S 3PT5S0000C 00032
UPB100S 3PT5S0000C 00040
UPB100S 3PT5S0000C 00050
UPB100S 3PT5S0000C 00060
UPB100S 3PT5S0000C 00063
UPB100S 3PT5S0000C 00075
UPB100S 3PT5S0000C 00080
UPB100S 3PT5S0000C 00100
UPB100S 3PT5S0000C 00125
UPB100H 3PT5S0000C 00015
UPB100H 3PT5S0000C 00016
UPB100H 3PT5S0000C 00020
UPB100H 3PT5S0000C 00025
UPB100H 3PT5S0000C 00030
UPB100H 3PT5S0000C 00032
UPB100H 3PT5S0000C 00040
UPB100H 3PT5S0000C 00050
UPB100H 3PT5S0000C 00060
UPB100H 3PT5S0000C 00063
UPB100H 3PT5S0000C 00075
UPB100H 3PT5S0000C 00080
UPB100H 3PT5S0000C 00100
UPB100H 3PT5S0000C 00125
UPB100L 3PT5S0000C 00015
UPB100L 3PT5S0000C 00016
UPB100L 3PT5S0000C 00020
UPB100L 3PT5S0000C 00025
UPB100L 3PT5S0000C 00030
UPB100L 3PT5S0000C 00032
UPB100L 3PT5S0000C 00040
UPB100L 3PT5S0000C 00050
UPB100L 3PT5S0000C 00060
UPB100L 3PT5S0000C 00063
UPB100L 3PT5S0000C 00075
UPB100L 3PT5S0000C 00080
UPB100L 3PT5S0000C 00100
UPB100L 3PT5S0000C 00125
UPB100X 3PT5S0000C 00015
UPB100X 3PT5S0000C 00016
UPB100X 3PT5S0000C 00020
UPB100X 3PT5S0000C 00025
UPB100X 3PT5S0000C 00030
UPB100X 3PT5S0000C 00032
UPB100X 3PT5S0000C 00040
UPB100X 3PT5S0000C 00050
UPB100X 3PT5S0000C 00060
UPB100X 3PT5S0000C 00063
UPB100X 3PT5S0000C 00075
UPB100X 3PT5S0000C 00080
UPB100X 3PT5S0000C 00100
UPB100X 3PT5S0000C 00125

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

4 pole
Code
UPB100S 4PT5S0000C 00015
UPB100S 4PT5S0000C 00016
UPB100S 4PT5S0000C 00020
UPB100S 4PT5S0000C 00025
UPB100S 4PT5S0000C 00030
UPB100S 4PT5S0000C 00032
UPB100S 4PT5S0000C 00040
UPB100S 4PT5S0000C 00050
UPB100S 4PT5S0000C 00060
UPB100S 4PT5S0000C 00063
UPB100S 4PT5S0000C 00075
UPB100S 4PT5S0000C 00080
UPB100S 4PT5S0000C 00100
UPB100S 4PT5S0000C 00125
UPB100H 4PT5S0000C 00015
UPB100H 4PT5S0000C 00016
UPB100H 4PT5S0000C 00020
UPB100H 4PT5S0000C 00025
UPB100H 4PT5S0000C 00030
UPB100H 4PT5S0000C 00032
UPB100H 4PT5S0000C 00040
UPB100H 4PT5S0000C 00050
UPB100H 4PT5S0000C 00060
UPB100H 4PT5S0000C 00063
UPB100H 4PT5S0000C 00075
UPB100H 4PT5S0000C 00080
UPB100H 4PT5S0000C 00100
UPB100H 4PT5S0000C 00125
UPB100L 4PT5S0000C 00015
UPB100L 4PT5S0000C 00016
UPB100L 4PT5S0000C 00020
UPB100L 4PT5S0000C 00025
UPB100L 4PT5S0000C 00030
UPB100L 4PT5S0000C 00032
UPB100L 4PT5S0000C 00040
UPB100L 4PT5S0000C 00050
UPB100L 4PT5S0000C 00060
UPB100L 4PT5S0000C 00063
UPB100L 4PT5S0000C 00075
UPB100L 4PT5S0000C 00080
UPB100L 4PT5S0000C 00100
UPB100L 4PT5S0000C 00125
UPB100X 4PT5S0000C 00015
UPB100X 4PT5S0000C 00016
UPB100X 4PT5S0000C 00020
UPB100X 4PT5S0000C 00025
UPB100X 4PT5S0000C 00030
UPB100X 4PT5S0000C 00032
UPB100X 4PT5S0000C 00040
UPB100X 4PT5S0000C 00050
UPB100X 4PT5S0000C 00060
UPB100X 4PT5S0000C 00063
UPB100X 4PT5S0000C 00075
UPB100X 4PT5S0000C 00080
UPB100X 4PT5S0000C 00100
UPB100X 4PT5S0000C 00125

Unit
(EA)

6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6

Specification

Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

Molded Case Circuit Breaker_ 95

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


Standard order code and unit
Adjustable thermal & fixed instantaneous / Thermal magnetic trip
40/45
Model /
Breaking capacity at
AC380/415V

UPB100S
85kA

UPB100H
100kA

UPB100L
130kA

UPB100X
150kA

96

Rated
current
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A

3 pole
Code
UPB100S 3PT4S0000C 00015F
UPB100S 3PT4S0000C 00016F
UPB100S 3PT4S0000C 00020F
UPB100S 3PT4S0000C 00025F
UPB100S 3PT4S0000C 00030F
UPB100S 3PT4S0000C 00032F
UPB100S 3PT4S0000C 00040F
UPB100S 3PT4S0000C 00050F
UPB100S 3PT4S0000C 00060F
UPB100S 3PT4S0000C 00063F
UPB100S 3PT4S0000C 00075F
UPB100S 3PT4S0000C 00080F
UPB100S 3PT4S0000C 00100F
UPB100S 3PT4S0000C 00125F
UPB100H 3PT4S0000C 00015F
UPB100H 3PT4S0000C 00016F
UPB100H 3PT4S0000C 00020F
UPB100H 3PT4S0000C 00025F
UPB100H 3PT4S0000C 00030F
UPB100H 3PT4S0000C 00032F
UPB100H 3PT4S0000C 00040F
UPB100H 3PT4S0000C 00050F
UPB100H 3PT4S0000C 00060F
UPB100H 3PT4S0000C 00063F
UPB100H 3PT4S0000C 00075F
UPB100H 3PT4S0000C 00080F
UPB100H 3PT4S0000C 00100F
UPB100H 3PT4S0000C 00125F
UPB100L 3PT4S0000C 00015F
UPB100L 3PT4S0000C 00016F
UPB100L 3PT4S0000C 00020F
UPB100L 3PT4S0000C 00025F
UPB100L 3PT4S0000C 00030F
UPB100L 3PT4S0000C 00032F
UPB100L 3PT4S0000C 00040F
UPB100L 3PT4S0000C 00050F
UPB100L 3PT4S0000C 00060F
UPB100L 3PT4S0000C 00063F
UPB100L 3PT4S0000C 00075F
UPB100L 3PT4S0000C 00080F
UPB100L 3PT4S0000C 00100F
UPB100L 3PT4S0000C 00125F
UPB100X 3PT4S0000C 00015F
UPB100X 3PT4S0000C 00016F
UPB100X 3PT4S0000C 00020F
UPB100X 3PT4S0000C 00025F
UPB100X 3PT4S0000C 00030F
UPB100X 3PT4S0000C 00032F
UPB100X 3PT4S0000C 00040F
UPB100X 3PT4S0000C 00050F
UPB100X 3PT4S0000C 00060F
UPB100X 3PT4S0000C 00063F
UPB100X 3PT4S0000C 00075F
UPB100X 3PT4S0000C 00080F
UPB100X 3PT4S0000C 00100F
UPB100X 3PT4S0000C 00125F

Unit
(EA)

4 pole
Code

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

UPB100S 4PT4S0000C 00015F


UPB100S 4PT4S0000C 00016F
UPB100S 4PT4S0000C 00020F
UPB100S 4PT4S0000C 00025F
UPB100S 4PT4S0000C 00030F
UPB100S 4PT4S0000C 00032F
UPB100S 4PT4S0000C 00040F
UPB100S 4PT4S0000C 00050F
UPB100S 4PT4S0000C 00060F
UPB100S 4PT4S0000C 00063F
UPB100S 4PT4S0000C 00075F
UPB100S 4PT4S0000C 00080F
UPB100S 4PT4S0000C 00100F
UPB100S 4PT4S0000C 00125F
UPB100H 4PT4S0000C 00015F
UPB100H 4PT4S0000C 00016F
UPB100H 4PT4S0000C 00020F
UPB100H 4PT4S0000C 00025F
UPB100H 4PT4S0000C 00030F
UPB100H 4PT4S0000C 00032F
UPB100H 4PT4S0000C 00040F
UPB100H 4PT4S0000C 00050F
UPB100H 4PT4S0000C 00060F
UPB100H 4PT4S0000C 00063F
UPB100H 4PT4S0000C 00075F
UPB100H 4PT4S0000C 00080F
UPB100H 4PT4S0000C 00100F
UPB100H 4PT4S0000C 00125F
UPB100L 4PT4S0000C 00015F
UPB100L 4PT4S0000C 00016F
UPB100L 4PT4S0000C 00020F
UPB100L 4PT4S0000C 00025F
UPB100L 4PT4S0000C 00030F
UPB100L 4PT4S0000C 00032F
UPB100L 4PT4S0000C 00040F
UPB100L 4PT4S0000C 00050F
UPB100L 4PT4S0000C 00060F
UPB100L 4PT4S0000C 00063F
UPB100L 4PT4S0000C 00075F
UPB100L 4PT4S0000C 00080F
UPB100L 4PT4S0000C 00100F
UPB100L 4PT4S0000C 00125F
UPB100X 4PT4S0000C 00015F
UPB100X 4PT4S0000C 00016F
UPB100X 4PT4S0000C 00020F
UPB100X 4PT4S0000C 00025F
UPB100X 4PT4S0000C 00030F
UPB100X 4PT4S0000C 00032F
UPB100X 4PT4S0000C 00040F
UPB100X 4PT4S0000C 00050F
UPB100X 4PT4S0000C 00060F
UPB100X 4PT4S0000C 00063F
UPB100X 4PT4S0000C 00075F
UPB100X 4PT4S0000C 00080F
UPB100X 4PT4S0000C 00100F
UPB100X 4PT4S0000C 00125F

6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6

Specification

Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

MCCB

50
Model /
Breaking capacity at
AC380/415V

UPB100S
85kA

UPB100H
100kA

UPB100L
130kA

UPB100X
150kA

Rated
current
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A

3 pole
Code
UPB100S 3PT5S0000C 00015F
UPB100S 3PT5S0000C 00016F
UPB100S 3PT5S0000C 00020F
UPB100S 3PT5S0000C 00025F
UPB100S 3PT5S0000C 00030F
UPB100S 3PT5S0000C 00032F
UPB100S 3PT5S0000C 00040F
UPB100S 3PT5S0000C 00050F
UPB100S 3PT5S0000C 00060F
UPB100S 3PT5S0000C 00063F
UPB100S 3PT5S0000C 00075F
UPB100S 3PT5S0000C 00080F
UPB100S 3PT5S0000C 00100F
UPB100S 3PT5S0000C 00125F
UPB100H 3PT5S0000C 00015F
UPB100H 3PT5S0000C 00016F
UPB100H 3PT5S0000C 00020F
UPB100H 3PT5S0000C 00025F
UPB100H 3PT5S0000C 00030F
UPB100H 3PT5S0000C 00032F
UPB100H 3PT5S0000C 00040F
UPB100H 3PT5S0000C 00050F
UPB100H 3PT5S0000C 00060F
UPB100H 3PT5S0000C 00063F
UPB100H 3PT5S0000C 00075F
UPB100H 3PT5S0000C 00080F
UPB100H 3PT5S0000C 00100F
UPB100H 3PT5S0000C 00125F
UPB100L 3PT5S0000C 00015F
UPB100L 3PT5S0000C 00016F
UPB100L 3PT5S0000C 00020F
UPB100L 3PT5S0000C 00025F
UPB100L 3PT5S0000C 00030F
UPB100L 3PT5S0000C 00032F
UPB100L 3PT5S0000C 00040F
UPB100L 3PT5S0000C 00050F
UPB100L 3PT5S0000C 00060F
UPB100L 3PT5S0000C 00063F
UPB100L 3PT5S0000C 00075F
UPB100L 3PT5S0000C 00080F
UPB100L 3PT5S0000C 00100F
UPB100L 3PT5S0000C 00125F
UPB100X 3PT5S0000C 00015F
UPB100X 3PT5S0000C 00016F
UPB100X 3PT5S0000C 00020F
UPB100X 3PT5S0000C 00025F
UPB100X 3PT5S0000C 00030F
UPB100X 3PT5S0000C 00032F
UPB100X 3PT5S0000C 00040F
UPB100X 3PT5S0000C 00050F
UPB100X 3PT5S0000C 00060F
UPB100X 3PT5S0000C 00063F
UPB100X 3PT5S0000C 00075F
UPB100X 3PT5S0000C 00080F
UPB100X 3PT5S0000C 00100F
UPB100X 3PT5S0000C 00125F

Unit
(EA)

4 pole
Code

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

UPB100S 4PT5S0000C 00015F


UPB100S 4PT5S0000C 00016F
UPB100S 4PT5S0000C 00020F
UPB100S 4PT5S0000C 00025F
UPB100S 4PT5S0000C 00030F
UPB100S 4PT5S0000C 00032F
UPB100S 4PT5S0000C 00040F
UPB100S 4PT5S0000C 00050F
UPB100S 4PT5S0000C 00060F
UPB100S 4PT5S0000C 00063F
UPB100S 4PT5S0000C 00075F
UPB100S 4PT5S0000C 00080F
UPB100S 4PT5S0000C 00100F
UPB100S 4PT5S0000C 00125F
UPB100H 4PT5S0000C 00015F
UPB100H 4PT5S0000C 00016F
UPB100H 4PT5S0000C 00020F
UPB100H 4PT5S0000C 00025F
UPB100H 4PT5S0000C 00030F
UPB100H 4PT5S0000C 00032F
UPB100H 4PT5S0000C 00040F
UPB100H 4PT5S0000C 00050F
UPB100H 4PT5S0000C 00060F
UPB100H 4PT5S0000C 00063F
UPB100H 4PT5S0000C 00075F
UPB100H 4PT5S0000C 00080F
UPB100H 4PT5S0000C 00100F
UPB100H 4PT5S0000C 00125F
UPB100L 4PT5S0000C 00015F
UPB100L 4PT5S0000C 00016F
UPB100L 4PT5S0000C 00020F
UPB100L 4PT5S0000C 00025F
UPB100L 4PT5S0000C 00030F
UPB100L 4PT5S0000C 00032F
UPB100L 4PT5S0000C 00040F
UPB100L 4PT5S0000C 00050F
UPB100L 4PT5S0000C 00060F
UPB100L 4PT5S0000C 00063F
UPB100L 4PT5S0000C 00075F
UPB100L 4PT5S0000C 00080F
UPB100L 4PT5S0000C 00100F
UPB100L 4PT5S0000C 00125F
UPB100X 4PT5S0000C 00015F
UPB100X 4PT5S0000C 00016F
UPB100X 4PT5S0000C 00020F
UPB100X 4PT5S0000C 00025F
UPB100X 4PT5S0000C 00030F
UPB100X 4PT5S0000C 00032F
UPB100X 4PT5S0000C 00040F
UPB100X 4PT5S0000C 00050F
UPB100X 4PT5S0000C 00060F
UPB100X 4PT5S0000C 00063F
UPB100X 4PT5S0000C 00075F
UPB100X 4PT5S0000C 00080F
UPB100X 4PT5S0000C 00100F
UPB100X 4PT5S0000C 00125F

6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6

Specification

Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

Molded Case Circuit Breaker_ 97

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UPB type / 160AF |
UPB160S 85kA
UPB160H 100kA
UPB160L 130kA
UPB160X 150kA

UPB160S

UPB160H

UPB160X

3, 4
IP20
A

Number of poles (P)


Degree of protection (with terminal cover)
Utilization category
Suitability of isolation
Protection
Thermal magnetic type
Rated current (A)
Electronic type
Rated insulation voltage [Ui] (V)
Rating
Rated operational voltage [Ue] (V)
Rated impulse withstand voltage [Uimp] (kV)
AC660/690V, 50-60Hz
Rated
AC480/500V, 50-60Hz
short-circuit
AC440/460V, 50-60Hz
Ultimate
breaking
AC380/415V, 50-60Hz
[Icu]
capacity
(kA r.m.s.) AC220/240V, 50-60Hz
DC250V
IEC 60947-2
DC125V
K 60947-2
Service [Ics] % of [Icu]
Fixed thermal,
Fixed instantaneous INST
Thermal
Adjustable thermal, LTD
magnetic
Fixed instantaneous INST
Adjustable thermal, LTD
Trip
Adjustable instantaneous INST
mechanism
& Protection
Long time delay
LTD
characteristics
Short time delay
STD
Electronic Instantaneous
INST
Pre-trip alarm
PTA
Pick-up LED
Direct mounting by screw
Mounting
Both line & load side
for
Plug-in
Switchboard Line side only
Screw
Terminal connection
Bus bar
Durability
Mechanical operation
(times)
Electrical operation
a
Width
Dimensions
b
Height
3/4P
(mm)
c
Depth
d
Weight (kg, breaker only) 3/4P

UPB160L

overload, inst., short-circuit


100,125,160
63-160
AC750
AC690
DC500 1)
8
10
25
65
85
85
100
100
130
130
150
65 1)
85 1)
100 1)
100 1)
100

10
50
65
85
100
50 1)
65 1)

25
85
150
150
200
100 1)
100 1)

10 In
(0.8 0.9 1) In
10 In
(0.8 0.9 1) In
(5-6-7-8-9-10) In
63,70,80,90,100,110,125,140,160
(NON-2-3-4-5-6-7-8-9-10) Ir
11 In
0.9 Ir

2)
2)

25,000
10,000
105/140
165
86.5
112
2.0/2.4

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) DC is not applicable for electronic breaker. 2) Available for 3P breaker

Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip 1)
Under voltage trip 2)

98

1C, right-hand-side
AUX 12UP R1
1C, left-hand-side
ALT 12UP L1
DC24V
SHT 12UP A
DC24V
UVT 12UP J

DC100-110V
SHT 12UP C
DC100-110V
UVT 12UP L

AC100-120V
SHT 12UP F
AC100-120V
UVT 12UP N

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.

AC200-230V
SHT 12UP H
AC200-230V
UVT 12UP P

AC380-415V
SHT 12UP B
AC380-415V
UVT 12UP Q

AC440-480V
SHT 12UP D
AC440-480V
UVT 12UP R

MCCB

Operating
Upper
TFG 12UPS U4
TFG 12UPL U4

Power supply direction


S type
Operating Surface
L type
handle 1)
S type
Extended
L type

Right
TFG 12UPS R4
TFH 12UPS
TFH 12UPL
AC/DC110V
MOT 12UP ADC110

DC24V
MOT 12UP DC24
3 pole
MIF 12UP 3

Motor operator 2)
Mechanical interlock

Left
TFG 12UPS L4
TFG 12UPL L4

AC/DC220V
MOT 12UP ADC220
4 pole
MIF 12UP 4

PLD 12UP

Padlock plate3)
1) For detail type information, please refer to page 197-205.
2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.

Mounting
Plug-in 1)

Structure
Mounting base
Connection 6C contact
block 2)
12C contact

For both line & load side


TDM 12NEP
CBM 26NE 6
CBM 26NE 63)

For line side only


TDM 12NEF

1) Available for 3P breaker


2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.
3) 2EA shall be ordered for 12C contact.

Terminal
Terminal bus bar
Cage terminal block
Terminal cover 1)
Interpole barrier 2)

3 pole (6EA/SET)
4 pole (8EA/SET)
3EA/SET
4EA/SET
3 pole
4 pole
4EA/SET

TBB 12NE 3
TBB 12NE 4
CTB 12UP 3S
CTB 12UP 4S
TCF 12UP 3
TCF 12UP 4
TQQ 12NE 3P

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 3 pole 4EA, 4 pole 6EA

Standard order code and unit


Electronic - LTD, STD, INST trip & PTA
Model /
Breaking
capacity at
AC380/415V

Rated
current

3 pole
Code

4 pole
Unit
(EA)

Code

Unit
(EA)

UPB160S 85kA

160A

UPB160S 3PESS0000X 00160

UPB160S 4PESS0000X 00160

UPB160H 100kA

160A

UPB160H 3PESS0000X 00160

UPB160H 4PESS0000X 00160

UPB160L 130kA

160A

UPB160L 3PESS0000X 00160

UPB160L 4PESS0000X 00160

UPB160X 150kA

160A

UPB160X 3PESS0000X 00160

UPB160X 4PESS0000X 00160

UPB160S 85kA

160A

UPB160S 3PESS0000Y 00160

UPB160S 4PESS0000Y 00160

UPB160H 100kA

160A

UPB160H 3PESS0000Y 00160

UPB160H 4PESS0000Y 00160

UPB160L 130kA

160A

UPB160L 3PESS0000Y 00160

UPB160L 4PESS0000Y 00160

UPB160X 150kA

160A

UPB160X 3PESS0000Y 00160

UPB160X 4PESS0000Y 00160

Specification

Category

Screw type
terminal
connection,
No option, 50Hz
MCCB/M3
Screw type
terminal
connection,
No option, 60Hz

Molded Case Circuit Breaker_ 99

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


Standard order code and unit
Fixed thermal & fixed instantaneous / Thermal magnetic trip
40/45
Model /
Breaking capacity at
AC380/415V

Rated
current

3 pole
Code

4 pole
Unit
(EA)

Code

Unit
(EA)

100A

UPB160S 3PT4S0000C 00100

UPB160S 4PT4S0000C 00100

125A

UPB160S 3PT4S0000C 00125

UPB160S 4PT4S0000C 00125

160A

UPB160S 3PT4S0000C 00160

UPB160S 4PT4S0000C 00160

100A

UPB160H 3PT4S0000C 00100

UPB160H 4PT4S0000C 00100

125A

UPB160H 3PT4S0000C 00125

UPB160H 4PT4S0000C 00125

160A

UPB160H 3PT4S0000C 00160

UPB160H 4PT4S0000C 00160

100A

UPB160L 3PT4S0000C 00100

UPB160L 4PT4S0000C 00100

125A

UPB160L 3PT4S0000C 00125

UPB160L 4PT4S0000C 00125

160A

UPB160L 3PT4S0000C 00160

UPB160L 4PT4S0000C 00160

100A

UPB160X 3PT4S0000C 00100

UPB160X 4PT4S0000C 00100

UPB160X
150kA

125A

UPB160X 3PT4S0000C 00125

UPB160X 4PT4S0000C 00125

160A

UPB160X 3PT4S0000C 00160

UPB160X 4PT4S0000C 00160

Model /
Breaking capacity at
AC380/415V

Rated
current

UPB160S
85kA

UPB160H
100kA

UPB160L
130kA

Specification

Screw type
terminal
connection,
No option,
50/60Hz

Category

MCCB
/M2

50

UPB160S
85kA

UPB160H
100kA

UPB160L
130kA

UPB160X
150kA

3 pole
Code

4 pole
Unit
(EA)

Code

Unit
(EA)

100A

UPB160S 3PT5S0000C 00100

UPB160S 4PT5S0000C 00100

125A

UPB160S 3PT5S0000C 00125

UPB160S 4PT5S0000C 00125

160A

UPB160S 3PT5S0000C 00160

UPB160S 4PT5S0000C 00160

100A

UPB160H 3PT5S0000C 00100

UPB160H 4PT5S0000C 00100

125A

UPB160H 3PT5S0000C 00125

UPB160H 4PT5S0000C 00125

160A

UPB160H 3PT5S0000C 00160

UPB160H 4PT5S0000C 00160

100A

UPB160L 3PT5S0000C 00100

UPB160L 4PT5S0000C 00100

125A

UPB160L 3PT5S0000C 00125

UPB160L 4PT5S0000C 00125

160A

UPB160L 3PT5S0000C 00160

UPB160L 4PT5S0000C 00160

100A

UPB160X 3PT5S0000C 00100

UPB160X 4PT5S0000C 00100

125A

UPB160X 3PT5S0000C 00125

UPB160X 4PT5S0000C 00125

160A

UPB160X 3PT5S0000C 00160

UPB160X 4PT5S0000C 00160

Specification

Screw type
terminal
connection,
No option,
50/60Hz

Category

MCCB
/M2

Adjustable thermal & fixed instantaneous / Thermal magnetic trip


40/45
Model /
Breaking capacity at
AC380/415V
UPB160S
85kA

UPB160H
100kA

UPB160L
130kA

UPB160X
150kA

100

3 pole

4 pole

Rated
current

Code

Unit
(EA)

100A

UPB160S 3PT4S0000C 00100F

UPB160S 4PT4S0000C 00100F

125A

UPB160S 3PT4S0000C 00125F

UPB160S 4PT4S0000C 00125F

160A

UPB160S 3PT4S0000C 00160F

UPB160S 4PT4S0000C 00160F

100A

UPB160H 3PT4S0000C 00100F

UPB160H 4PT4S0000C 00100F

125A

UPB160H 3PT4S0000C 00125F

UPB160H 4PT4S0000C 00125F

160A

UPB160H 3PT4S0000C 00160F

UPB160H 4PT4S0000C 00160F

100A

UPB160L 3PT4S0000C 00100F

UPB160L 4PT4S0000C 00100F

125A

UPB160L 3PT4S0000C 00125F

UPB160L 4PT4S0000C 00125F

160A

UPB160L 3PT4S0000C 00160F

UPB160L 4PT4S0000C 00160F

100A

UPB160X 3PT4S0000C 00100F

UPB160X 4PT4S0000C 00100F

125A

UPB160X 3PT4S0000C 00125F

UPB160X 4PT4S0000C 00125F

160A

UPB160X 3PT4S0000C 00160F

UPB160X 4PT4S0000C 00160F

Code

Unit
(EA)

Specification

Screw type
terminal
connection,
No option,
50/60Hz

Category

MCCB
/M2

MCCB

50
Model /
Breaking capacity at
AC380/415V
UPB160S
85kA

UPB160H
100kA

UPB160L
130kA

UPB160X
150kA

3 pole

4 pole

Rated
current

Code

Unit
(EA)

100A

UPB160S 3PT5S0000C 00100F

UPB160S 4PT5S0000C 00100F

125A

UPB160S 3PT5S0000C 00125F

UPB160S 4PT5S0000C 00125F

160A

UPB160S 3PT5S0000C 00160F

UPB160S 4PT5S0000C 00160F

100A

UPB160H 3PT5S0000C 00100F

UPB160H 4PT5S0000C 00100F

125A

UPB160H 3PT5S0000C 00125F

UPB160H 4PT5S0000C 00125F

160A

UPB160H 3PT5S0000C 00160F

UPB160H 4PT5S0000C 00160F

100A

UPB160L 3PT5S0000C 00100F

UPB160L 4PT5S0000C 00100F

125A

UPB160L 3PT5S0000C 00125F

UPB160L 4PT5S0000C 00125F

160A

UPB160L 3PT5S0000C 00160F

UPB160L 4PT5S0000C 00160F

100A

UPB160X 3PT5S0000C 00100F

UPB160X 4PT5S0000C 00100F

125A

UPB160X 3PT5S0000C 00125F

UPB160X 4PT5S0000C 00125F

160A

UPB160X 3PT5S0000C 00160F

UPB160X 4PT5S0000C 00160F

Code

Unit
(EA)

Specification

Screw type
terminal
connection,
No option,
50/60Hz

Category

MCCB
/M2

Adjustable thermal & adjustable instantaneous / Thermal magnetic trip


40/45
Model /
Breaking capacity at
AC380/415V

3 pole

4 pole

Rated
current

Code

Unit
(EA)

100A

UPB160S 3PT4S0000C 00100H

UPB160S 4PT4S0000C 00100H

125A

UPB160S 3PT4S0000C 00125H

UPB160S 4PT4S0000C 00125H

160A

UPB160S 3PT4S0000C 00160H

UPB160S 4PT4S0000C 00160H

100A

UPB160H 3PT4S0000C 00100H

UPB160H 4PT4S0000C 00100H

125A

UPB160H 3PT4S0000C 00125H

UPB160H 4PT4S0000C 00125H

160A

UPB160H 3PT4S0000C 00160H

UPB160H 4PT4S0000C 00160H

100A

UPB160L 3PT4S0000C 00100H

UPB160L 4PT4S0000C 00100H

125A

UPB160L 3PT4S0000C 00125H

UPB160L 4PT4S0000C 00125H

160A

UPB160L 3PT4S0000C 00160H

UPB160L 4PT4S0000C 00160H

100A

UPB160X 3PT4S0000C 00100H

UPB160X 4PT4S0000C 00100H

UPB160X
150kA

125A

UPB160X 3PT4S0000C 00125H

UPB160X 4PT4S0000C 00125H

160A

UPB160X 3PT4S0000C 00160H

UPB160X 4PT4S0000C 00160H

Model /
Breaking capacity at
AC380/415V

Rated
current

Code

Unit
(EA)

100A

UPB160S 3PT5S0000C 00100H

UPB160S 4PT5S0000C 00100H

125A

UPB160S 3PT5S0000C 00125H

UPB160S 4PT5S0000C 00125H

160A

UPB160S 3PT5S0000C 00160H

UPB160S 4PT5S0000C 00160H

100A

UPB160H 3PT5S0000C 00100H

UPB160H 4PT5S0000C 00100H

125A

UPB160H 3PT5S0000C 00125H

UPB160H 4PT5S0000C 00125H

160A

UPB160H 3PT5S0000C 00160H

UPB160H 4PT5S0000C 00160H

100A

UPB160L 3PT5S0000C 00100H

UPB160L 4PT5S0000C 00100H

125A

UPB160L 3PT5S0000C 00125H

UPB160L 4PT5S0000C 00125H

160A

UPB160L 3PT5S0000C 00160H

UPB160L 4PT5S0000C 00160H

100A

UPB160X 3PT5S0000C 00100H

UPB160X 4PT5S0000C 00100H

125A

UPB160X 3PT5S0000C 00125H

UPB160X 4PT5S0000C 00125H

160A

UPB160X 3PT5S0000C 00160H

UPB160X 4PT5S0000C 00160H

UPB160S
85kA

UPB160H
100kA

UPB160L
130kA

Code

Unit
(EA)

Specification

Screw type
terminal
connection,
No option,
50/60Hz

Category

MCCB
/M2

50

UPB160S
85kA

UPB160H
100kA

UPB160L
130kA

UPB160X
150kA

3 pole

4 pole
Code

Unit
(EA)

Specification

Screw type
terminal
connection,
No option,
50/60Hz

Category

MCCB
/M2

Molded Case Circuit Breaker_ 101

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UPB type / 250AF |
UPB250S 85kA
UPB250H 100kA
UPB250L 130kA
UPB250X 150kA

UPB250S

UPB250H

UPB250L

Number of poles (P)

3, 4

Degree of protection (with terminal cover)

IP20

Utilization category

UPB250X

Suitability of isolation
Protection

overload, inst., short-circuit


Rated current (A)

Thermal magnetic type

125,150,160,175,200,225,250

Electronic type

100-250

Rated insulation voltage [Ui] (V)

AC750

Rating

AC690

Rated operational voltage [Ue] (V)

DC500 1)

Rated impulse withstand voltage [Uimp] (kV)

Rated
short-circuit
breaking
capacity

Ultimate
[Icu]
(kA r.m.s.)

IEC 60947-2
K 60947-2

AC660/690V, 50-60Hz

10

10

AC480/500V, 50-60Hz

50

65

85

85

AC440/460V, 50-60Hz

65

85

100

150

AC380/415V, 50-60Hz

85

100

130

150

AC220/240V, 50-60Hz

100

130

150

200

DC250V

50 1)

65 1)

85 1)

100 1)

DC125V

65 1)

100 1)

100 1)

100 1)

Service [Ics] % of [Icu]

25

100

Fixed thermal,

Thermal
magnetic
Trip
mechanism
& Protection
characteristics

Fixed instantaneous

INST

10 In

Adjustable thermal,

LTD

(0.8 0.9 1) In

Fixed instantaneous

INST

10 In

Adjustable thermal,

LTD

(0.8 0.9 1) In

Adjustable instantaneous INST

Electronic

(5-6-7-8-9-10) In

Long time delay

LTD

Short time delay

STD

Instantaneous

INST

11 In

Pre-trip alarm

PTA

0.9 Ir

100,110,125,140,160,175,200,225,250
(NON-2-3-4-5-6-7-8-9-10) Ir

Pick-up LED
Direct mounting by screw
Mounting

Plug-in

Terminal connection
Durability
(times)

Dimensions
(mm)

Both line & load side


for
Switchboard Line side only

2)
2)

Screw
Bus bar

Mechanical operation

25,000

Electrical operation

3/4P

10,000
a

Width

105/140

Height

165

Depth

86.5

d
Weight (kg, breaker only) 3/4P

112
2.0/2.4

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) DC is not applicable for electronic breaker. 2) Available for 3P breaker

102

25

MCCB

Accessories
Signal
1C, right-hand-side

Auxiliary switch

AUX 12UP R1
1C, left-hand-side

Trip alarm switch

ALT 12UP L1

Shunt trip 1)

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

AC440-480V

SHT 12UP A

SHT 12UP C

SHT 12UP F

SHT 12UP H

SHT 12UP B

SHT 12UP D

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

AC440-480V

Under voltage trip 2)

UVT 12UP J

UVT 12UP L

UVT 12UP N

UVT 12UP P

UVT 12UP Q

UVT 12UP R

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.

Operating
Power supply direction
S type
Operating Surface
L type
handle 1)
S type
Extended
L type

Upper

Right

Left

TFG 12UPS U4

TFG 12UPS R4

TFG 12UPS L4

TFG 12UPL U4

TFG 12UPL L4
TFH 12UPS
TFH 12UPL

DC24V

Motor operator 2)

AC/DC110V

MOT 12UP DC24

Mechanical interlock

MOT 12UP ADC110

AC/DC220V
MOT 12UP ADC220

3 pole

4 pole

MIF 12UP 3

MIF 12UP 4

3)

Padlock plate

PLD 12UP

1) For detail type information, please refer to page 197-205.


2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.

Mounting
Structure
Plug-in 1)

For both line & load side

For line side only

TDM 12NEP

TDM 12NEF

Mounting base
Connection 6C contact

CBM 26NE 6

block 2)

CBM 26NE 63)

12C contact

1) Available for 3P breaker


2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.
3) 2EA shall be ordered for 12C contact.

Terminal
Terminal bus bar
Cage terminal block
Terminal cover 1)
Interpole barrier 2)

3 pole (6EA/SET)

TBB 12NE 3

4 pole (8EA/SET)

TBB 12NE 4

3EA/SET

CTB 12UP 3S

4EA/SET

CTB 12UP 4S

3 pole

TCF 12UP 3

4 pole

TCF 12UP 4

4EA/SET

TQQ 12NE 3P

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 3 pole 4EA, 4 pole 6EA

Molded Case Circuit Breaker_ 103

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


Standard order code and unit
Electronic - LTD, STD, INST trip & PTA

104

Unit
(EA)

4 pole
Code

Unit
(EA)

UPB250S 3PESS0000X 00250

UPB250S 4PESS0000X 00250

250A

UPB250H 3PESS0000X 00250

UPB250H 4PESS0000X 00250

UPB250L
130kA

250A

UPB250L 3PESS0000X 00250

UPB250L 4PESS0000X 00250

UPB250X
150kA

250A

UPB250X 3PESS0000X 00250

UPB250X 4PESS0000X 00250

Model /
Breaking capacity at
AC380/415V

Rated
current

UPB250S
85kA

250A

UPB250H
100kA

3 pole
Code

Specification

Category

Screw type
terminal
connection,
No option,
50Hz

MCCB
/M3

UPB250S
85kA

250A

UPB250S 3PESS0000Y 00250

UPB250S 4PESS0000Y 00250

UPB250H
100kA

250A

UPB250H 3PESS0000Y 00250

UPB250H 4PESS0000Y 00250

UPB250L
130kA

250A

UPB250L 3PESS0000Y 00250

UPB250L 4PESS0000Y 00250

UPB250X
150kA

250A

UPB250X 3PESS0000Y 00250

UPB250X 4PESS0000Y 00250

Screw type
terminal
connection,
No option,
60Hz

MCCB

Standard order code and unit


Fixed thermal & fixed instantaneous / Thermal magnetic trip
40/45
Model /
Breaking capacity at
AC380/415V

UPB250S
85kA

UPB250H
100kA

UPB250L
130kA

UPB250X
150kA

Rated
current
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A

3 pole
Code
UPB250S 3PT4S0000C 00125
UPB250S 3PT4S0000C 00150
UPB250S 3PT4S0000C 00160
UPB250S 3PT4S0000C 00175
UPB250S 3PT4S0000C 00200
UPB250S 3PT4S0000C 00225
UPB250S 3PT4S0000C 00250
UPB250H 3PT4S0000C 00125
UPB250H 3PT4S0000C 00150
UPB250H 3PT4S0000C 00160
UPB250H 3PT4S0000C 00175
UPB250H 3PT4S0000C 00200
UPB250H 3PT4S0000C 00225
UPB250H 3PT4S0000C 00250
UPB250L 3PT4S0000C 00125
UPB250L 3PT4S0000C 00150
UPB250L 3PT4S0000C 00160
UPB250L 3PT4S0000C 00175
UPB250L 3PT4S0000C 00200
UPB250L 3PT4S0000C 00225
UPB250L 3PT4S0000C 00250
UPB250X 3PT4S0000C 00125
UPB250X 3PT4S0000C 00150
UPB250X 3PT4S0000C 00160
UPB250X 3PT4S0000C 00175
UPB250X 3PT4S0000C 00200
UPB250X 3PT4S0000C 00225
UPB250X 3PT4S0000C 00250

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

4 pole
Code
UPB250S 4PT4S0000C 00125
UPB250S 4PT4S0000C 00150
UPB250S 4PT4S0000C 00160
UPB250S 4PT4S0000C 00175
UPB250S 4PT4S0000C 00200
UPB250S 4PT4S0000C 00225
UPB250S 4PT4S0000C 00250
UPB250H 4PT4S0000C 00125
UPB250H 4PT4S0000C 00150
UPB250H 4PT4S0000C 00160
UPB250H 4PT4S0000C 00175
UPB250H 4PT4S0000C 00200
UPB250H 4PT4S0000C 00225
UPB250H 4PT4S0000C 00250
UPB250L 4PT4S0000C 00125
UPB250L 4PT4S0000C 00150
UPB250L 4PT4S0000C 00160
UPB250L 4PT4S0000C 00175
UPB250L 4PT4S0000C 00200
UPB250L 4PT4S0000C 00225
UPB250L 4PT4S0000C 00250
UPB250X 4PT4S0000C 00125
UPB250X 4PT4S0000C 00150
UPB250X 4PT4S0000C 00160
UPB250X 4PT4S0000C 00175
UPB250X 4PT4S0000C 00200
UPB250X 4PT4S0000C 00225
UPB250X 4PT4S0000C 00250

Unit
(EA)

6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6

Specification

Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

Specification

Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

50
Model /
Breaking capacity at
AC380/415V

UPB250S
85kA

UPB250H
100kA

UPB250L
130kA

UPB250X
150kA

Rated
current
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A

3 pole
Code
UPB250S 3PT5S0000C 00125
UPB250S 3PT5S0000C 00150
UPB250S 3PT5S0000C 00160
UPB250S 3PT5S0000C 00175
UPB250S 3PT5S0000C 00200
UPB250S 3PT5S0000C 00225
UPB250S 3PT5S0000C 00250
UPB250H 3PT5S0000C 00125
UPB250H 3PT5S0000C 00150
UPB250H 3PT5S0000C 00160
UPB250H 3PT5S0000C 00175
UPB250H 3PT5S0000C 00200
UPB250H 3PT5S0000C 00225
UPB250H 3PT5S0000C 00250
UPB250L 3PT5S0000C 00125
UPB250L 3PT5S0000C 00150
UPB250L 3PT5S0000C 00160
UPB250L 3PT5S0000C 00175
UPB250L 3PT5S0000C 00200
UPB250L 3PT5S0000C 00225
UPB250L 3PT5S0000C 00250
UPB250X 3PT5S0000C 00125
UPB250X 3PT5S0000C 00150
UPB250X 3PT5S0000C 00160
UPB250X 3PT5S0000C 00175
UPB250X 3PT5S0000C 00200
UPB250X 3PT5S0000C 00225
UPB250X 3PT5S0000C 00250

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

4 pole
Code
UPB250S 4PT5S0000C 00125
UPB250S 4PT5S0000C 00150
UPB250S 4PT5S0000C 00160
UPB250S 4PT5S0000C 00175
UPB250S 4PT5S0000C 00200
UPB250S 4PT5S0000C 00225
UPB250S 4PT5S0000C 00250
UPB250H 4PT5S0000C 00125
UPB250H 4PT5S0000C 00150
UPB250H 4PT5S0000C 00160
UPB250H 4PT5S0000C 00175
UPB250H 4PT5S0000C 00200
UPB250H 4PT5S0000C 00225
UPB250H 4PT5S0000C 00250
UPB250L 4PT5S0000C 00125
UPB250L 4PT5S0000C 00150
UPB250L 4PT5S0000C 00160
UPB250L 4PT5S0000C 00175
UPB250L 4PT5S0000C 00200
UPB250L 4PT5S0000C 00225
UPB250L 4PT5S0000C 00250
UPB250X 4PT5S0000C 00125
UPB250X 4PT5S0000C 00150
UPB250X 4PT5S0000C 00160
UPB250X 4PT5S0000C 00175
UPB250X 4PT5S0000C 00200
UPB250X 4PT5S0000C 00225
UPB250X 4PT5S0000C 00250

Unit
(EA)

6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6

Molded Case Circuit Breaker_ 105

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


Standard order code and unit
Adjustable thermal & fixed instantaneous / Thermal magnetic trip
40/45
Model /
Breaking capacity at
AC380/415V

UPB250S
85kA

UPB250H
100kA

UPB250L
130kA

UPB250X
150kA

Rated
current
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A

3 pole
Code
UPB250S 3PT4S0000C 00125F
UPB250S 3PT4S0000C 00150F
UPB250S 3PT4S0000C 00160F
UPB250S 3PT4S0000C 00175F
UPB250S 3PT4S0000C 00200F
UPB250S 3PT4S0000C 00225F
UPB250S 3PT4S0000C 00250F
UPB250H 3PT4S0000C 00125F
UPB250H 3PT4S0000C 00150F
UPB250H 3PT4S0000C 00160F
UPB250H 3PT4S0000C 00175F
UPB250H 3PT4S0000C 00200F
UPB250H 3PT4S0000C 00225F
UPB250H 3PT4S0000C 00250F
UPB250L 3PT4S0000C 00125F
UPB250L 3PT4S0000C 00150F
UPB250L 3PT4S0000C 00160F
UPB250L 3PT4S0000C 00175F
UPB250L 3PT4S0000C 00200F
UPB250L 3PT4S0000C 00225F
UPB250L 3PT4S0000C 00250F
UPB250X 3PT4S0000C 00125F
UPB250X 3PT4S0000C 00150F
UPB250X 3PT4S0000C 00160F
UPB250X 3PT4S0000C 00175F
UPB250X 3PT4S0000C 00200F
UPB250X 3PT4S0000C 00225F
UPB250X 3PT4S0000C 00250F

Unit
(EA)

4 pole
Code

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

UPB250S 4PT4S0000C 00125F


UPB250S 4PT4S0000C 00150F
UPB250S 4PT4S0000C 00160F
UPB250S 4PT4S0000C 00175F
UPB250S 4PT4S0000C 00200F
UPB250S 4PT4S0000C 00225F
UPB250S 4PT4S0000C 00250F
UPB250H 4PT4S0000C 00125F
UPB250H 4PT4S0000C 00150F
UPB250H 4PT4S0000C 00160F
UPB250H 4PT4S0000C 00175F
UPB250H 4PT4S0000C 00200F
UPB250H 4PT4S0000C 00225F
UPB250F 4PT4S0000C 00250F
UPB250L 4PT4S0000C 00125F
UPB250L 4PT4S0000C 00150F
UPB250L 4PT4S0000C 00160F
UPB250L 4PT4S0000C 00175F
UPB250L 4PT4S0000C 00200F
UPB250L 4PT4S0000C 00225F
UPB250L 4PT4S0000C 00250F
UPB250X 4PT4S0000C 00125F
UPB250X 4PT4S0000C 00150F
UPB250X 4PT4S0000C 00160F
UPB250X 4PT4S0000C 00175F
UPB250X 4PT4S0000C 00200F
UPB250X 4PT4S0000C 00225F
UPB250X 4PT4S0000C 00250F

6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6

Unit
(EA)

4 pole
Code

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

UPB250S 4PT5S0000C 00125F


UPB250S 4PT5S0000C 00150F
UPB250S 4PT5S0000C 00160F
UPB250S 4PT5S0000C 00175F
UPB250S 4PT5S0000C 00200F
UPB250S 4PT5S0000C 00225F
UPB250S 4PT5S0000C 00250F
UPB250H 4PT5S0000C 00125F
UPB250H 4PT5S0000C 00150F
UPB250H 4PT5S0000C 00160F
UPB250H 4PT5S0000C 00175F
UPB250H 4PT5S0000C 00200F
UPB250H 4PT5S0000C 00225F
UPB250F 4PT5S0000C 00250F
UPB250L 4PT5S0000C 00125F
UPB250L 4PT5S0000C 00150F
UPB250L 4PT5S0000C 00160F
UPB250L 4PT5S0000C 00175F
UPB250L 4PT5S0000C 00200F
UPB250L 4PT5S0000C 00225F
UPB250L 4PT5S0000C 00250F
UPB250X 4PT5S0000C 00125F
UPB250X 4PT5S0000C 00150F
UPB250X 4PT5S0000C 00160F
UPB250X 4PT5S0000C 00175F
UPB250X 4PT5S0000C 00200F
UPB250X 4PT5S0000C 00225F
UPB250X 4PT5S0000C 00250F

6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6

Specification

Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

Specification

Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

50
Model /
Breaking capacity at
AC380/415V

UPB250S
85kA

UPB250H
100kA

UPB250L
130kA

UPB250X
150kA

106

Rated
current
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A

3 pole
Code
UPB250S 3PT5S0000C 00125F
UPB250S 3PT5S0000C 00150F
UPB250S 3PT5S0000C 00160F
UPB250S 3PT5S0000C 00175F
UPB250S 3PT5S0000C 00200F
UPB250S 3PT5S0000C 00225F
UPB250S 3PT5S0000C 00250F
UPB250H 3PT5S0000C 00125F
UPB250H 3PT5S0000C 00150F
UPB250H 3PT5S0000C 00160F
UPB250H 3PT5S0000C 00175F
UPB250H 3PT5S0000C 00200F
UPB250H 3PT5S0000C 00225F
UPB250H 3PT5S0000C 00250F
UPB250L 3PT5S0000C 00125F
UPB250L 3PT5S0000C 00150F
UPB250L 3PT5S0000C 00160F
UPB250L 3PT5S0000C 00175F
UPB250L 3PT5S0000C 00200F
UPB250L 3PT5S0000C 00225F
UPB250L 3PT5S0000C 00250F
UPB250X 3PT5S0000C 00125F
UPB250X 3PT5S0000C 00150F
UPB250X 3PT5S0000C 00160F
UPB250X 3PT5S0000C 00175F
UPB250X 3PT5S0000C 00200F
UPB250X 3PT5S0000C 00225F
UPB250X 3PT5S0000C 00250F

MCCB

Standard order code and unit


Adjustable thermal & adjustable instantaneous / Thermal magnetic trip
40/45
Model /
Breaking capacity at
AC380/415V

UPB250S
85kA

UPB250H
100kA

UPB250L
130kA

UPB250X
150kA

Rated
current
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A

3 pole
Code
UPB250S 3PT4S0000C 00125H
UPB250S 3PT4S0000C 00150H
UPB250S 3PT4S0000C 00160H
UPB250S 3PT4S0000C 00175H
UPB250S 3PT4S0000C 00200H
UPB250S 3PT4S0000C 00225H
UPB250S 3PT4S0000C 00250H
UPB250H 3PT4S0000C 00125H
UPB250H 3PT4S0000C 00150H
UPB250H 3PT4S0000C 00160H
UPB250H 3PT4S0000C 00175H
UPB250H 3PT4S0000C 00200H
UPB250H 3PT4S0000C 00225H
UPB250H 3PT4S0000C 00250H
UPB250L 3PT4S0000C 00125H
UPB250L 3PT4S0000C 00150H
UPB250L 3PT4S0000C 00160H
UPB250L 3PT4S0000C 00175H
UPB250L 3PT4S0000C 00200H
UPB250L 3PT4S0000C 00225H
UPB250L 3PT4S0000C 00250H
UPB250X 3PT4S0000C 00125H
UPB250X 3PT4S0000C 00150H
UPB250X 3PT4S0000C 00160H
UPB250X 3PT4S0000C 00175H
UPB250X 3PT4S0000C 00200H
UPB250X 3PT4S0000C 00225H
UPB250X 3PT4S0000C 00250H

Unit
(EA)

4 pole
Code

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

UPB250S 4PT4S0000C 00125H


UPB250S 4PT4S0000C 00150H
UPB250S 4PT4S0000C 00160H
UPB250S 4PT4S0000C 00175H
UPB250S 4PT4S0000C 00200H
UPB250S 4PT4S0000C 00225H
UPB250S 4PT4S0000C 00250H
UPB250H 4PT4S0000C 00125H
UPB250H 4PT4S0000C 00150H
UPB250H 4PT4S0000C 00160H
UPB250H 4PT4S0000C 00175H
UPB250H 4PT4S0000C 00200H
UPB250H 4PT4S0000C 00225H
UPB250H 4PT4S0000C 00250H
UPB250L 4PT4S0000C 00125H
UPB250L 4PT4S0000C 00150H
UPB250L 4PT4S0000C 00160H
UPB250L 4PT4S0000C 00175H
UPB250L 4PT4S0000C 00200H
UPB250L 4PT4S0000C 00225H
UPB250L 4PT4S0000C 00250H
UPB250X 4PT4S0000C 00125H
UPB250X 4PT4S0000C 00150H
UPB250X 4PT4S0000C 00160H
UPB250X 4PT4S0000C 00175H
UPB250X 4PT4S0000C 00200H
UPB250X 4PT4S0000C 00225H
UPB250X 4PT4S0000C 00250H

6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6

Unit
(EA)

4 pole
Code

Unit
(EA)

8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8

UPB250S 4PT5S0000C 00125H


UPB250S 4PT5S0000C 00150H
UPB250S 4PT5S0000C 00160H
UPB250S 4PT5S0000C 00175H
UPB250S 4PT5S0000C 00200H
UPB250S 4PT5S0000C 00225H
UPB250S 4PT5S0000C 00250H
UPB250H 4PT5S0000C 00125H
UPB250H 4PT5S0000C 00150H
UPB250H 4PT5S0000C 00160H
UPB250H 4PT5S0000C 00175H
UPB250H 4PT5S0000C 00200H
UPB250H 4PT5S0000C 00225H
UPB250H 4PT5S0000C 00250H
UPB250L 4PT5S0000C 00125H
UPB250L 4PT5S0000C 00150H
UPB250L 4PT5S0000C 00160H
UPB250L 4PT5S0000C 00175H
UPB250L 4PT5S0000C 00200H
UPB250L 4PT5S0000C 00225H
UPB250L 4PT5S0000C 00250H
UPB250X 4PT5S0000C 00125H
UPB250X 4PT5S0000C 00150H
UPB250X 4PT5S0000C 00160H
UPB250X 4PT5S0000C 00175H
UPB250X 4PT5S0000C 00200H
UPB250X 4PT5S0000C 00225H
UPB250X 4PT5S0000C 00250H

6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6

Specification

Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

Specification

Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M2

50
Model /
Breaking capacity at
AC380/415V

UPB250S
85kA

UPB250H
100kA

UPB250L
130kA

UPB250X
150kA

Rated
current
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A

3 pole
Code
UPB250S 3PT5S0000C 00125H
UPB250S 3PT5S0000C 00150H
UPB250S 3PT5S0000C 00160H
UPB250S 3PT5S0000C 00175H
UPB250S 3PT5S0000C 00200H
UPB250S 3PT5S0000C 00225H
UPB250S 3PT5S0000C 00250H
UPB250H 3PT5S0000C 00125H
UPB250H 3PT5S0000C 00150H
UPB250H 3PT5S0000C 00160H
UPB250H 3PT5S0000C 00175H
UPB250H 3PT5S0000C 00200H
UPB250H 3PT5S0000C 00225H
UPB250H 3PT5S0000C 00250H
UPB250L 3PT5S0000C 00125H
UPB250L 3PT5S0000C 00150H
UPB250L 3PT5S0000C 00160H
UPB250L 3PT5S0000C 00175H
UPB250L 3PT5S0000C 00200H
UPB250L 3PT5S0000C 00225H
UPB250L 3PT5S0000C 00250H
UPB250X 3PT5S0000C 00125H
UPB250X 3PT5S0000C 00150H
UPB250X 3PT5S0000C 00160H
UPB250X 3PT5S0000C 00175H
UPB250X 3PT5S0000C 00200H
UPB250X 3PT5S0000C 00225H
UPB250X 3PT5S0000C 00250H

Molded Case Circuit Breaker_ 107

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UPB type / 400AF |
UPB400S 85kA
UPB400H 100kA
UPB400L 130kA
UPB400X 150kA

UPB400S

Number of poles (P)


Degree of protection (with terminal cover)
Utilization category
Suitability of isolation
Protection
Rated current (A)
Rated insulation voltage [Ui] (V)
Rating
Rated operational voltage [Ue] (V)
Rated impulse withstand voltage [Uimp] (kV)
AC660/690V, 50-60Hz
Rated
AC480/500V, 50-60Hz
short-circuit Ultimate
breaking
[Icu]
AC440/460V, 50-60Hz
capacity
(kA r.m.s.) AC380/415V, 50-60Hz
AC220/240V, 50-60Hz
IEC 60947-2
K 60947-2
Service [Ics] % of [Icu]
Long time delay
LTD
Short time delay
STD
Trip
Instantaneous
INST
mechanism
Ground fault trip
GFT
Electronic
& Protection
Pre-trip alarm
PTA
characteristics
I2T lamp
Pick-up LED
Direct mounting by screw
Mounting
Both line & load side
for
Plug-in
Switchboard Line side only
Screw
Terminal connection
Bus bar
Durability
Mechanical operation
(times)
Electrical operation
a
Width
Dimensions
b
Height
3/4P
(mm)
c
Depth
d
Weight (kg, breaker only) 3/4P

UPB400H

UPB400L

UPB400X

3, 4
IP20
A
overload, inst., short-circuit
200-400
AC750
AC690
8
10
25
65
85
85
100
100
130
130
150
100
(0.5-1) 1) In (15 setting)
(2-4-6-8-10) Ir
(3-6-8-10-11) In
(0.2-0.3-0.4) In
0.9 Ir

10
50
65
85
100

25
85
150
150
200

2)
2)

20,000
6,000
140/185
255
117
159.5
6.0/7.8

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) (0.5-1): (0.63-0.8-1)x(0.8-0.85-0.9-0.95-1)
2) Available for 3P breaker

Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip 1)
Under voltage trip 2)

1C, left-hand-side
AUX 46UP L1
1C, right-hand-side
ALT 46UP R1
DC24V
SHT 46UP A
DC24V
UVT 46UP J

DC100-110V
SHT 46UP C
DC100-110V
UVT 46UP L

AC100-120V
SHT 46UP F
AC100-120V
UVT 46UP N

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.

108

AC200-230V
SHT 46UP H
AC200-230V
UVT 46UP P

AC380-415V
SHT 46UP B
AC380-415V
UVT 46UP Q

AC440-480V
SHT 46UP D
AC440-480V
UVT 46UP R

MCCB

Operating
Power supply direction
Operating
Surface S type
1)
handle
Extended S type

Upper
TFG 46UPS U2

Right
TFG 46UPS R2
TFH 46UPS
AC/DC110V
MOT 46NE ADC110

DC24V
MOT 46NE DC24
3 pole
MIF 46UP 3

Motor operator 2)
Mechanical interlock
Padlock plate 3)
Extension handle 4)

Left
TFG 46UPS L2
AC/DC220V
MOT 46NE ADC220
4 pole
MIF 46UP 4

PLD 12UP
THA 46UP

1) For detail type information, please refer to page 197-205.


3) Padlock is not supplied.

2) Motor operator is not recommended for marine application.


4) Supplied as standard component

Mounting
Plug-in 1)

Structure
Mounting base
Connection 6C contact
block 2)
12C contact

For both line & load side


TDM 46NEP 3)
CBM 26NE 6
CBM 26NE 64)

For line side only


TDM 46NEF

1) Available for 3P breaker


2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.
3) 2EA are required for both line & load side plug-in type 3P breaker.
4) 2EA shall be ordered for 12C contact.

Terminal
3 pole (6EA/SET)
4 pole (8EA/SET)
3EA/SET
Cage terminal block
4EA/SET
3 pole
1)
Terminal cover
4 pole
Interpole barrier 2) 4EA/SET

TBB 40NE 3
TBB 40NE 4
CTB 46UP 3S
CTB 46UP 4S
TCF 46UP 3
TCF 46UP 4
TQQ 46NE 3P

Terminal bus bar

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 3 pole 4EA, 4 pole 6EA

Standard order code and unit


Electronic - LTD, STD, INST trip & PTA
Model /
Breaking
capacity at
AC380/415V
UPB400S 85kA
UPB400H 100kA
UPB400L 130kA
UPB400X 150kA
UPB400S 85kA
UPB400H 100kA
UPB400L 130kA
UPB400X 150kA

Rated
current
400A
400A
400A
400A
400A
400A
400A
400A

3 pole
Code
UPB400S 3PESS0000X 00400
UPB400H 3PESS0000X 00400
UPB400L 3PESS0000X 00400
UPB400X 3PESS0000X 00400
UPB400S 3PESS0000Y 00400
UPB400H 3PESS0000Y 00400
UPB400L 3PESS0000Y 00400
UPB400X 3PESS0000Y 00400

4 pole
Unit
(EA)

Code

Unit
(EA)

3
3
3
3
3
3
3
3

UPB400S 4PESS0000X 00400


UPB400H 4PESS0000X 00400
UPB400L 4PESS0000X 00400
UPB400X 4PESS0000X 00400
UPB400S 4PESS0000Y 00400
UPB400H 4PESS0000Y 00400
UPB400L 4PESS0000Y 00400
UPB400X 4PESS0000Y 00400

2
2
2
2
2
2
2
2

Specification

Category

Screw type
terminal
connection,
No option, 50Hz
MCCB/M3
Screw type
terminal
connection,
No option, 60Hz

Electronic - LTD, STD, INST, GFT trip & PTA


Model /
Breaking
capacity at
AC380/415V
UPB400S 85kA
UPB400H 100kA
UPB400L 130kA
UPB400X 150kA
UPB400S 85kA
UPB400H 100kA
UPB400L 130kA
UPB400X 150kA

Rated
current
400A
400A
400A
400A
400A
400A
400A
400A

3 pole
Code
UPB400S 3PEGS0000X 00400
UPB400H 3PEGS0000X 00400
UPB400L 3PEGS0000X 00400
UPB400X 3PEGS0000X 00400
UPB400S 3PEGS0000Y 00400
UPB400H 3PEGS0000Y 00400
UPB400L 3PEGS0000Y 00400
UPB400X 3PEGS0000Y 00400

4 pole
Unit
(EA)

Code

Unit
(EA)

3
3
3
3
3
3
3
3

UPB400S 4PEGS0000X 00400


UPB400H 4PEGS0000X 00400
UPB400L 4PEGS0000X 00400
UPB400X 4PEGS0000X 00400
UPB400S 4PEGS0000Y 00400
UPB400H 4PEGS0000Y 00400
UPB400L 4PEGS0000Y 00400
UPB400X 4PEGS0000Y 00400

2
2
2
2
2
2
2
2

Specification

Category

Screw type
terminal
connection,
No option, 50Hz
MCCB/M3
Screw type
terminal
connection,
No option, 60Hz
Molded Case Circuit Breaker_ 109

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| UPB type / 630AF |
UPB630S 85kA
UPB630H 100kA
UPB630L 130kA
UPB630X 150kA

UPB630S

Number of poles (P)


Degree of protection (with terminal cover)
Utilization category
Suitability of isolation
Protection
Rated current (A)
Rated insulation voltage [Ui] (V)
Rating
Rated operational voltage [Ue] (V)
Rated impulse withstand voltage [Uimp] (kV)
AC660/690V, 50-60Hz
Rated
AC480/500V, 50-60Hz
short-circuit Ultimate
breaking
[Icu]
AC440/460V, 50-60Hz
capacity
(kA r.m.s.) AC380/415V, 50-60Hz
AC220/240V, 50-60Hz
IEC 60947-2
K 60947-2
Service [Ics] % of [Icu]
Long time delay
LTD
Short time delay
STD
Trip
Instantaneous
INST
mechanism
GFT
Electronic Ground fault trip
& Protection
Pre-trip alarm
PTA
characteristics
I2T lamp
Pick-up LED
Direct mounting by screw
Mounting
Both line & load side
for
Plug-in
Switchboard Line side only
Screw
Terminal connection
Bus bar
Mechanical operation
Durability
(times)
Electrical operation
a
Width
b
Height
Dimensions
3/4P
(mm)
c
Depth
d
Weight (kg, breaker only) 3/4P

UPB630H

UPB630L

UPB630X

3, 4
IP20
A
overload, inst., short-circuit
320-630
AC750
AC690
8
10
25
65
85
85
100
100
130
130
150
100
(0.5-1) 1) In (15 setting)
(2-4-6-8-10) Ir
(3-6-8-10-11) In
(0.2-0.3-0.4) In
0.9 Ir

10
50
65
85
100

25
85
150
150
200

2)
2)

20,000
6,000
140/185
255
117
159.5
6.0/7.8

- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) (0.5-1): (0.63-0.8-1)x(0.8-0.85-0.9-0.95-1)
2) Available for 3P breaker

Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip 1)
Under voltage trip 2)

1C, left-hand-side
AUX 46UP L1
1C, right-hand-side
ALT 46UP R1
DC24V
SHT 46UP A
DC24V
UVT 46UP J

DC100-110V
SHT 46UP C
DC100-110V
UVT 46UP L

AC100-120V
SHT 46UP F
AC100-120V
UVT 46UP N

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.

110

AC200-230V
SHT 46UP H
AC200-230V
UVT 46UP P

AC380-415V
SHT 46UP B
AC380-415V
UVT 46UP Q

AC440-480V
SHT 46UP D
AC440-480V
UVT 46UP R

MCCB

Operating
Power supply direction
Operating Surface S type
handle 1)
Extended S type

Upper
TFG 46UPS U2

Right
TFG 46UPS R2
TFH 46UPS
AC/DC110V
MOT 46NE ADC110

DC24V
MOT 46NE DC24
3 pole
MIF 46UP 3

Motor operator 2)
Mechanical interlock
Padlock plate 3)
Extension handle 4)

Left
TFG 46UPS L2
AC/DC220V
MOT 46NE ADC220
4 pole
MIF 46UP 4

PLD 12UP
THA 46UP

1) For detail type information, please refer to page no. 197-205. 2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.
4) Supplied as standard component

Mounting
Plug-in

1)

Structure
Mounting base
Connection 6C contact
12C contact
block 2)

For both line & load side


TDM 46NEP 3)
CBM 26NE 6
CBM 26NE 64)

For line side only


TDM 46NEF

1) Available for 3P breaker


2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.
3) 2EA are required for both line & load side plug-in type 3P breaker.
4) 2EA shall be ordered for 12C contact.

Terminal
TBB 60NE 3
TBB 60NE 4
CTB 46UP 3S
CTB 46UP 4S
TCF 46UP 3
TCF 46UP 4
TQQ 46NE 3P

3 pole (6EA/SET)
4 pole (8EA/SET)
3EA/SET
Cage terminal block
4EA/SET
3 pole
1)
Terminal cover
4 pole
Interpole barrier 2) 4EA/SET
Terminal bus bar

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 3 pole 4EA, 4 pole 6EA

Standard order code and unit


Electronic - LTD, STD, INST trip & PTA
Model /
Breaking
capacity at
AC380/415V
UPB630S 85kA
UPB630H 100kA
UPB630L 130kA
UPB630X 150kA
UPB630S 85kA
UPB630H 100kA
UPB630L 130kA
UPB630X 150kA

Rated
current
630A
630A
630A
630A
630A
630A
630A
630A

3 pole
Code
UPB630S 3PESS0000X 00630
UPB630H 3PESS0000X 00630
UPB630L 3PESS0000X 00630
UPB630X 3PESS0000X 00630
UPB630S 3PESS0000Y 00630
UPB630H 3PESS0000Y 00630
UPB630L 3PESS0000Y 00630
UPB630X 3PESS0000Y 00630

4 pole
Unit
(EA)

Code

Unit
(EA)

3
3
3
3
3
3
3
3

UPB630S 4PESS0000X 00630


UPB630H 4PESS0000X 00630
UPB630L 4PESS0000X 00630
UPB630X 4PESS0000X 00630
UPB630S 4PESS0000Y 00630
UPB630H 4PESS0000Y 00630
UPB630L 4PESS0000Y 00630
UPB630X 4PESS0000Y 00630

2
2
2
2
2
2
2
2

Specification

Category

Screw type
terminal
connection,
No option, 50Hz
MCCB/M3
Screw type
terminal
connection,
No option, 60Hz

Electronic - LTD, STD, INST, GFT trip & PTA


Model /
Breaking
capacity at
AC380/415V
UPB630S 85kA
UPB630H 100kA
UPB630L 130kA
UPB630X 150kA
UPB630S 85kA
UPB630H 100kA
UPB630L 130kA
UPB630X 150kA

Rated
current
630A
630A
630A
630A
630A
630A
630A
630A

3 pole
Code
UPB630S 3PEGS0000X 00630
UPB630H 3PEGS0000X 00630
UPB630L 3PEGS0000X 00630
UPB630X 3PEGS0000X 00630
UPB630S 3PEGS0000Y 00630
UPB630H 3PEGS0000Y 00630
UPB630L 3PEGS0000Y 00630
UPB630X 3PEGS0000Y 00630

4 pole
Unit
(EA)

Code

Unit
(EA)

3
3
3
3
3
3
3
3

UPB630S 4PEGS0000X 00630


UPB630H 4PEGS0000X 00630
UPB630L 4PEGS0000X 00630
UPB630X 4PEGS0000X 00630
UPB630S 4PEGS0000Y 00630
UPB630H 4PEGS0000Y 00630
UPB630L 4PEGS0000Y 00630
UPB630X 4PEGS0000Y 00630

2
2
2
2
2
2
2
2

Specification

Category

Screw type
terminal
connection,
No option, 50Hz
MCCB/M3
Screw type
terminal
connection,
No option, 60Hz
Molded Case Circuit Breaker_ 111

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| Motor protection / UPB type 125AF |
UPB100H 100kA
UPB100L 130kA

UPB100H

UPB100L

Number of poles (P)

IP20

Degree of protection (with terminal cover)


Utilization category

Suitability of isolation
Protection

instantaneous, short-circuit
Rated current (A)

2.5,3.2,6.3,12.5,20,32,50,63,80,100

Rated insulation voltage [Ui] (V)

AC750

Rating

AC690

Rated operational voltage [Ue] (V)

DC500
Rated impulse withstand voltage [Uimp] (kV)

Rated
short-circuit
breaking
capacity

Ultimate
[Icu]
(kA r.m.s.)

IEC 60947-2
K 60947-2

AC660/690V, 50-60Hz

10

25

AC480/500V, 50-60Hz

65

85

AC440/460V, 50-60Hz

85

100

AC380/415V, 50-60Hz

100

130

AC220/240V, 50-60Hz

130

150

DC250V

65

85

DC125V

100

100

Service [Ics] % of [Icu]


Trip mechanism
Thermal
& Protection
characteristics magnetic

100
(6-7-8-9-10-11-12-13) In

Adjustable instantaneous

Direct mounting by screw


Mounting

Plug-in

Terminal connection

Both line & load side


for
Switchboard Line side only
Screw
Bus bar

Durability
(times)

Mechanical operation

25,000

Electrical operation

10,000

Dimensions
(mm)

3P

Width

105

Height

165

Depth

86.5

d
Weight (kg, breaker only)

3P

112
1.8

The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.

112

MCCB

Accessories
Signal
1C, right-hand-side
AUX 12UP R1
1C, left-hand-side
ALT 12UP L1
DC24V
SHT 12UP A
DC24V
UVT 12UP J

Auxiliary switch
Trip alarm switch
Shunt trip 1)
Under voltage trip 2)

DC100-110V
SHT 12UP C
DC100-110V
UVT 12UP L

AC100-120V
SHT 12UP F
AC100-120V
UVT 12UP N

AC200-230V
SHT 12UP H
AC200-230V
UVT 12UP P

AC380-415V
SHT 12UP B
AC380-415V
UVT 12UP Q

AC440-480V
SHT 12UP D
AC440-480
UVT 12UP R

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.

Operating
Power supply direction
S type
Operating Surface L type
1)
handle
S type
Extended
L type

Upper
TFG 12UPS U4
TFG 12UPL U4

Right
TFG 12UPS R4
TFH 12UPS
TFH 12UPL
AC/DC110V
MOT 12UP ADC110
MIF 12UP 3
PLD 12UP

DC24V
MOT 12UP DC24

Motor operator 2)
Mechanical interlock
Padlock plate 3)

1) For detail type information, please refer to page 197-205.


3) Padlock is not supplied.

Left
TFG 12UPS L4
TFG 12UPL L4

AC/DC220V
MOT 12UP ADC220

2) Motor operator is not recommended for marine application.

Mounting
Plug-in

Structure
Mounting base
Connection 6C contact
block 1)
12C contact

For both line & load side


TDM 12NEP
CBM 26NE 6
CBM 26NE 62)

For line side only


TDM 12NEF

1) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.
2) 2EA shall be ordered for 12C contact.

Terminal
Terminal bus bar
Cage terminal block
1)
Terminal cover
Interpole barrier 2)

3 pole (6EA/SET)
3EA/SET
3 pole
4EA/SET

TBB 12NE 3
CTB 12UP 3S
TCF 12UP 3
TQQ 12NE 3P

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 4EA

Standard order code and unit


Adjustable instantaneous only / recommended for motor protection
Model /
Breaking
capacity at
AC380/415V

Rated
current

UPB100H
100kA

2.5A
3.2A
6.3A
12.5A
20A
32A
50A
63A
80A
100A

3 pole
Code
UPB100H 3PMPS0000C 002.5
UPB100H 3PMPS0000C 003.2
UPB100H 3PMPS0000C 006.3
UPB100H 3PMPS0000C 012.5
UPB100H 3PMPS0000C 00020
UPB100H 3PMPS0000C 00032
UPB100H 3PMPS0000C 00050
UPB100H 3PMPS0000C 00063
UPB100H 3PMPS0000C 00080
UPB100H 3PMPS0000C 00100

Unit
(EA)

8
8
8
8
8
8
8
8
8
8

Model /
Breaking
capacity at
AC380/415V

Rated
current

UPB100L
130kA

2.5A
3.2A
6.3A
12.5A
20A
32A
50A
63A
80A
100A

3 pole
Code

Unit
(EA)

UPB100L 3PMPS0000C 002.5


UPB100L 3PMPS0000C 003.2
UPB100L 3PMPS0000C 006.3
UPB100L 3PMPS0000C 012.5
UPB100L 3PMPS0000C 00020
UPB100L 3PMPS0000C 00032
UPB100L 3PMPS0000C 00050
UPB100L 3PMPS0000C 00063
UPB100L 3PMPS0000C 00080
UPB100L 3PMPS0000C 00100

8
8
8
8
8
8
8
8
8
8

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M4

Molded Case Circuit Breaker_ 113

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| Motor protection / UPB type 250AF |
UPB250H 100kA
UPB250L 130kA

UPB250H

UPB250L

Number of poles (P)

IP20

Degree of protection (with terminal cover)


Utilization category

Suitability of isolation
Protection

instantaneous, short-circuit
Rated current (A)

125,150,175,200,225

Rated insulation voltage [Ui] (V)

AC750

Rating

AC690

Rated operational voltage [Ue] (V)

DC500
Rated impulse withstand voltage [Uimp] (kV)

Rated
short-circuit
breaking
capacity

Ultimate
[Icu]
(kA r.m.s.)

IEC 60947-2
K 60947-2

AC660/690V, 50-60Hz

10

25

AC480/500V, 50-60Hz

65

85

AC440/460V, 50-60Hz

85

100

AC380/415V, 50-60Hz

100

130

AC220/240V, 50-60Hz

130

150

DC250V

65

85

DC125V

100

100

Service [Ics] % of [Icu]


Trip mechanism
Thermal
& Protection
characteristics magnetic

100
(5-6-7-8-9-10) In

Adjustable instantaneous

Direct mounting by screw


Mounting

Plug-in

Both line & load side


for
Switchboard Line side only
Screw

Terminal connection
Bus bar
Durability
(times)

Mechanical operation

25,000

Electrical operation

10,000

Dimensions
(mm)

3P

Width

105

Height

165

Depth

86.5

d
Weight (kg, breaker only)

3P

112
2.0

The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.

114

MCCB

Accessories
Signal
1C, right-hand-side
AUX 12UP R1
1C, left-hand-side
ALT 12UP L1
DC24V
SHT 12UP A
DC24V
UVT 12UP J

Auxiliary switch
Trip alarm switch
Shunt trip 1)
Under voltage trip 2)

DC100-110V
SHT 12UP C
DC100-110V
UVT 12UP L

AC100-120V
SHT 12UP F
AC100-120V
UVT 12UP N

AC200-230V
SHT 12UP H
AC200-230V
UVT 12UP P

AC380-415V
SHT 12UP B
AC380-415V
UVT 12UP Q

AC440-480V
SHT 12UP D
AC440-480V
UVT 12UP R

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.

Operating
Power supply direction
S type
Operating Surface
L type
1)
handle
S type
Extended
L type

Upper
TFG 12UPS U4
TFG 12UPL U4

Right
TFG 12UPS R4
TFH 12UPS
TFH 12UPL
AC/DC110V
MOT 12UP ADC110
MIF 12UP 3
PLD 12UP

DC24V
MOT 12UP DC24

Motor operator 2)
Mechanical interlock
Padlock plate3)

1) For detail type information, please refer to page 197-205.


3) Padlock is not supplied.

Left
TFG 12UPS L4
TFG 12UPL L4

AC/DC220V
MOT 12UP ADC220

2) Motor operator is not recommended for marine application.

Mounting
Plug-in

Structure
Mounting base
Connection 6C contact
block 1)
12C contact

For both line & load side


TDM 12NEP
CBM 26NE 6
CBM 26NE 62)

For line side only


TDM 12NEF

1) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.
2) 2EA shall be ordered for 12C contact.

Terminal
Terminal bus bar
3 pole (6EA/SET)
Cage terminal block 3EA/SET
Terminal cover

1)

Interpole barrier 2)

TBB 12NE 3
CTB 12UP 3S
TCF 12UP 3
TCF 12UP 4
TQQ 12NE 3P

3 pole
4 pole
4EA/SET

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 4EA

Standard order code and unit


Adjustable instantaneous only / recommended for motor protection
Model /
Breaking
capacity at
AC380/415V

UPB250H
100kA

Rated
current

3 pole
Code

Unit
(EA)

Model /
Breaking
capacity at
AC380/415V

Rated
current

3 pole
Code

Unit
(EA)

125A

UPB250H 3PMPS0000C 00125

125A

UPB250L 3PMPS0000C 00125

150A

UPB250H 3PMPS0000C 00150

150A

UPB250L 3PMPS0000C 00150

175A

UPB250H 3PMPS0000C 00175

175A

UPB250L 3PMPS0000C 00175

200A

UPB250H 3PMPS0000C 00200

200A

UPB250L 3PMPS0000C 00200

225A

UPB250H 3PMPS0000C 00225

225A

UPB250L 3PMPS0000C 00225

UPB250L
130kA

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M4

Molded Case Circuit Breaker_ 115

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| Q-class (for nuclear power plant application) / HBL type 100AF |
HBL103U 85kA
HBL103UQ 85kA
HBL103UM 85kA
HBL103UMQ 85kA

HBL103U

HBL103UQ

overload, inst., short-circuit


15,20,30,40,50,60,75,100

Rated impulse withstand voltage [Uimp] (kV)

IEC 60947-2
K 60947-2
Trip mechanism
& Protection
characteristics

AC660/690V, 50-60Hz
AC480/500V, 50-60Hz
AC440/460V, 50-60Hz
Ultimate
[Icu]
AC380/415V, 50-60Hz
(kA r.m.s.) AC220/240V, 50-60Hz
DC250V
DC125V
Service [Ics] % of [Icu]
Thermal
magnetic

25
85
100
150
200
100
100

Fixed thermal,
Fixed instantaneous INST
Adjustable instantaneous

25
85
100
150
200
100
100

3P

a
b
c
d

instantaneous, short-circuit
2.5,3.2,6.3,12.5,20,32,50,63,80,100
AC750
AC690
DC500
8
25
25
85
85
100
100
150
150
200
200
100
100
100
100
100

10 In
(6-7-8-9-10-11-12-13) In

Non-E1
Q-class
E1
Mounting
Direct mounting by screw
Screw
Terminal connection
Bus bar
Mechanical operation
Durability
(times)
Electrical operation
Dimensions
(mm)

HBL103UMQ

3
IP20
A

Number of poles (P)


Degree of protection (with terminal cover)
Utilization category
Suitability of isolation
Protection
Rated current (A)
Rated insulation voltage [Ui] (V)
Rating
Rated operational voltage [Ue] (V)

Rated
short-circuit
breaking
capacity

HBL103UM

25,000
10,000
105
165
86.5
112
1.8

Width
Height
Depth

Weight (kg, breaker only) 3P

The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.

Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip 1)
Under voltage trip 2)

1C, right-hand-side
AUX 12UP R1
1C, left-hand-side
ALT 12UP L1
DC24V
SHT 12UP A
DC24V
UVT 12UP J

DC100-110V
SHT 12UP C
DC100-110V
UVT 12UP L

AC100-120V
SHT 12UP F
AC100-120V
UVT 12UP N

- Signal accessories shall be installed in breaker before ex-working.


1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.

116

AC200-230V
SHT 12UP H
AC200-230V
UVT 12UP P

AC380-415V
SHT 12UP B
AC380-415V
UVT 12UP Q

AC440-480V
SHT 12UP D
AC440-480V
UVT 12UP R

MCCB

Operating
Power supply direction
Operating
HBL103U, HBL103UM
1)
Surface
handle
HBL103UQ, HBL103UMQ
Motor operator 2)

Upper
TFG 20U U4
TFG 20UQ U4
DC24V
MOT 12UP DC24

Left
TFG 20U L4
TFG 20UQ L4
AC/DC110V
MOT 12UP ADC110
MIF 12UP 3
PLD 12UP

Mechanical interlock
Padlock plate3)

AC/DC220V
MOT 12UP ADC220

1) For detail type information, please refer to page 197-205.


2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.

Terminal
Terminal bus bar

6EA/SET

TBB 12NE 3

Cage terminal block

3EA/SET

CTB 12UP 3S

4EA/SET

TQQ 12NE 3P

Terminal cover 1)
Interpole barrier 2)

TCF 12UP 3

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 4EA

Standard order code and unit


Fixed thermal & fixed instantaneous
40/45
Model /
Breaking
capacity at
AC480/500V

Rated
current

HBL103U
85kA

15A
20A
30A
40A
50A
60A
75A
100A

Model /
Breaking
capacity at
AC480/500V

Rated
current

HBL103U
85kA

15A
20A
30A
40A
50A
60A
75A
100A

3 pole, Non-E1 class


Code

Unit
(EA)

HBL103U 3PT4S0000C 00015


HBL103U 3PT4S0000C 00020
HBL103U 3PT4S0000C 00030
HBL103U 3PT4S0000C 00040
HBL103U 3PT4S0000C 00050
HBL103U 3PT4S0000C 00060
HBL103U 3PT4S0000C 00075
HBL103U 3PT4S0000C 00100

8
8
8
8
8
8
8
8

Model /
Breaking
capacity at
AC480/500V

Rated
current

HBL103UQ
85kA

15A
20A
30A
40A
50A
60A
75A
100A

Model /
Breaking
capacity at
AC480/500V

Rated
current

HBL103UQ
85kA

15A
20A
30A
40A
50A
60A
75A
100A

3 pole, E1 class
Code

Unit
(EA)

HBL103UQ 3PT4S0000C 00015


HBL103UQ 3PT4S0000C 00020
HBL103UQ 3PT4S0000C 00030
HBL103UQ 3PT4S0000C 00040
HBL103UQ 3PT4S0000C 00050
HBL103UQ 3PT4S0000C 00060
HBL103UQ 3PT4S0000C 00075
HBL103UQ 3PT4S0000C 00100

8
8
8
8
8
8
8
8

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M1

50
3 pole, Non-E1 class
Code

Unit
(EA)

HBL103U 3PT5S0000C 00015


HBL103U 3PT5S0000C 00020
HBL103U 3PT5S0000C 00030
HBL103U 3PT5S0000C 00040
HBL103U 3PT5S0000C 00050
HBL103U 3PT5S0000C 00060
HBL103U 3PT5S0000C 00075
HBL103U 3PT5S0000C 00100

8
8
8
8
8
8
8
8

3 pole, E1 class
Code

Unit
(EA)

HBL103UQ 3PT5S0000C 00015


HBL103UQ 3PT5S0000C 00020
HBL103UQ 3PT5S0000C 00030
HBL103UQ 3PT5S0000C 00040
HBL103UQ 3PT5S0000C 00050
HBL103UQ 3PT5S0000C 00060
HBL103UQ 3PT5S0000C 00075
HBL103UQ 3PT5S0000C 00100

8
8
8
8
8
8
8
8

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M1

Adjustable instantaneous only / recommended for motor protection


Model /
Breaking
capacity at
AC480/500V

Rated
current

HBL103UM
85kA

2.5A
3.2A
6.3A
12.5A
20A
32A
50A
63A
80A
100A

3 pole, Non-E1 class


Code
HBL103UM 3PMPS0000C 002.5
HBL103UM 3PMPS0000C 003.2
HBL103UM 3PMPS0000C 006.3
HBL103UM 3PMPS0000C 012.5
HBL103UM 3PMPS0000C 00020
HBL103UM 3PMPS0000C 00032
HBL103UM 3PMPS0000C 00050
HBL103UM 3PMPS0000C 00063
HBL103UM 3PMPS0000C 00080
HBL103UM 3PMPS0000C 00100

Unit
(EA)

8
8
8
8
8
8
8
8
8
8

Model /
Breaking
capacity at
AC480/500V

Rated
current

HBL103UMQ
85kA

2.5A
3.2A
6.3A
12.5A
20A
32A
50A
63A
80A
100A

3 pole, E1 class
Code

Unit
(EA)

HBL103UMQ 3PMPS0000C 002.5


HBL103UMQ 3PMPS0000C 003.2
HBL103UMQ 3PMPS0000C 006.3
HBL103UMQ 3PMPS0000C 012.5
HBL103UMQ 3PMPS0000C 00020
HBL103UMQ 3PMPS0000C 00032
HBL103UMQ 3PMPS0000C 00050
HBL103UMQ 3PMPS0000C 00063
HBL103UMQ 3PMPS0000C 00080
HBL103UMQ 3PMPS0000C 00100

8
8
8
8
8
8
8
8
8
8

Specification Category

Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M4

Molded Case Circuit Breaker_ 117

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| Q-class (for nuclear power plant application) / HBL type 225AF |
HBL203U 85kA
HBL203UQ 85kA
HBL203UM 85kA
HBL203UMQ 85kA

HBL203U

HBL203UQ

HBL203UM

HBL203UMQ

3
IP20
A

Number of poles (P)


Degree of protection (with terminal cover)
Utilization category
Suitability of isolation
Protection
Rated current (A)
Rated insulation voltage [Ui] (V)
Rating
Rated operational voltage [Ue] (V)
Rated impulse withstand voltage [Uimp] (kV)
AC660/690V, 50-60Hz
Rated
AC480/500V, 50-60Hz
short-circuit Ultimate
AC440/460V, 50-60Hz
breaking
[Icu]
AC380/415V, 50-60Hz
capacity
(kA r.m.s.) AC220/240V, 50-60Hz
DC250V
IEC 60947-2
DC125V
K 60947-2
Service [Ics] % of [Icu]
Fixed thermal,
Trip mechanism Thermal
& Protection magnetic
Fixed instantaneous INST
characteristics
Adjustable instantaneous
Non-E1
Q-class
E1
Direct mounting by screw
Mounting
Both line & load side
for
Plug-in
Switchboard Line side only
Screw
Terminal connection
Bus bar
Mechanical operation
Durability
(times)
Electrical operation
a
Width
b
Height
Dimensions
3P
(mm)
c
Depth
d
Weight (kg, breaker only) 3P

overload, inst., short-circuit


instantaneous, short-circuit
125,150,175,200,225
AC750
AC690
DC500
8
25
25
25
25
85
85
85
85
100
100
100
100
150
150
150
150
200
200
200
200
100
100
100
100
100
100
100
100
100
10 In
(5-6-7-8-9-10) In

25,000
10,000
105
165
86.5
112
2.0

The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.

Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip 1)
Under voltage trip 2)

118

1C, right-hand-side
AUX 12UP R1
1C, left-hand-side
ALT 12UP L1
DC24V
SHT 12UP A
DC24V
UVT 12UP J

DC100-110V
SHT 12UP C
DC100-110V
UVT 12UP L

AC100-120V
SHT 12UP F
AC100-120V
UVT 12UP N

- Signal accessories shall be installed in breaker before ex-working.


1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.

AC200-230V
SHT 12UP H
AC200-230V
UVT 12UP P

AC380-415V
SHT 12UP B
AC380-415V
UVT 12UP Q

AC440-480V
SHT 12UP D
AC440-480V
UVT 12UP R

MCCB

Operating
Power supply direction
HBL203U, HBL203UM
Operating Surface
HBL203UQ, HBL203UMQ
handle 1)
HBL203U, HBL203UM
Extended
HBL203UQ, HBL203UMQ

Upper
TFG 20U U4
TFG 20UQ U4

Left
TFG 20U L4
TFG 20UQ L4
TFH 20U
TFH 20UQ

DC24V
MOT 12UP DC24

Motor operator 2)

AC/DC110V
MOT 12UP ADC110
MIF 12UP 3
PLD 12UP

Mechanical interlock
Padlock plate3)

AC/DC220V
MOT 12UP ADC220

1) For detail type information, please refer to page 197-205.


2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.

Terminal
Terminal bus bar

6EA/SET

TBB 12NE 3

Cage terminal block

3EA/SET

CTB 12UP 3S

4EA/SET

TQQ 12NE 3P

Terminal cover 1)
Interpole barrier 2)

TCF 12UP 3

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 4EA

Standard order code and unit


Fixed thermal & fixed instantaneous
40/45
Model /
Rated
Breaking capacity at
current
AC480/500V

HBL203U
85kA

125A
150A
175A
200A
225A

3 pole, Non-E1 class


Code
HBL203U 3PT4S0000C 00125
HBL203U 3PT4S0000C 00150
HBL203U 3PT4S0000C 00175
HBL203U 3PT4S0000C 00200
HBL203U 3PT4S0000C 00225

Model /
Unit Breaking capacity at
AC480/500V
(EA)

8
8
8
8
8

HBL203UQ
85kA

Rated
current
125A
150A
175A
200A
225A

3 pole, E1 class
Code

Unit
(EA)

HBL203UQ 3PT4S0000C 00125


HBL203UQ 3PT4S0000C 00150
HBL203UQ 3PT4S0000C 00175
HBL203UQ 3PT4S0000C 00200
HBL203UQ 3PT4S0000C 00225

8
8
8
8
8

Specification Category
Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M1

50
Model /
Rated
Breaking capacity at
current
AC480/500V

HBL203U
85kA

125A
150A
175A
200A
225A

3 pole, Non-E1 class


Code
HBL203U 3PT5S0000C 00125
HBL203U 3PT5S0000C 00150
HBL203U 3PT5S0000C 00175
HBL203U 3PT5S0000C 00200
HBL203U 3PT5S0000C 00225

Model /
Unit Breaking capacity at
AC480/500V
(EA)

8
8
8
8
8

HBL203UQ
85kA

Rated
current
125A
150A
175A
200A
225A

3 pole, E1 class
Code

Unit
(EA)

HBL203UQ 3PT5S0000C 00125


HBL203UQ 3PT5S0000C 00150
HBL203UQ 3PT5S0000C 00175
HBL203UQ 3PT5S0000C 00200
HBL203UQ 3PT5S0000C 00225

8
8
8
8
8

Specification Category
Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M1

Adjustable instantaneous only / recommended for motor protection


Model /
Rated
Breaking capacity at
current
AC480/500V

HBL203UM
85kA

125A
150A
175A
200A
225A

3 pole, Non-E1 class


Code
HBL203UM 3PMPS0000C 00125
HBL203UM 3PMPS0000C 00150
HBL203UM 3PMPS0000C 00175
HBL203UM 3PMPS0000C 00200
HBL203UM 3PMPS0000C 00225

Model /
Unit Breaking capacity at
AC480/500V
(EA)

8
8
8
8
8

HBL203UMQ
85kA

Rated
current
125A
150A
175A
200A
225A

3 pole, E1 class
Code

Unit
(EA)

HBL203UMQ 3PMPS0000C 00125


HBL203UMQ 3PMPS0000C 00150
HBL203UMQ 3PMPS0000C 00175
HBL203UMQ 3PMPS0000C 00200
HBL203UMQ 3PMPS0000C 00225

8
8
8
8
8

Specification Category
Screw type
terminal
connection,
No option,
50/60Hz

MCCB
/M4

Molded Case Circuit Breaker_ 119

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| Switch disconnector / UAD type 50-100AF |
UAD50C
UAD50S
UAD100R

UAD50C

50AF

Ampere frame size


Number of poles (P)
Degree of protection (with terminal cover)
Utilization category
Suitability of isolation
Conventional thermal current [Ith] (A)
Rated current (A)
Rated insulation voltage [Ui] (V)
Rating

UAD50S

Rated operational voltage [Ue] (V)

Rated impulse withstand voltage [Uimp] (kV)


Rated short-circuit making capacity [Icm] (kA peak at AC460V)
Rated short-time withstand current for 1sec. [Icw] (kA r.m.s)
Mechanical operation
Durability
(times)
Electrical operation
Direct mounting by screw
Both line & load side
for
Switchboard Line side only
Mounting
Plug-in
for Distribution board
DIN-rail
with DIN-rail adaptor
Terminal connection
Screw
a
Width
b
Height
Dimensions
3P
(mm)
c
Depth
d
Weight (kg, breaker only)
3P

UAD100R

3
IP20
A

3
IP20
A

100AF
3
IP20
A

50
50
AC690
AC660
DC250
6
17
1
25,000
15,000

50
50
AC690
AC660
DC250
6
52.5
1
25,000
15,000

100
100
AC690
AC660
DC250
6
52.5
1
25,000
10,000

75
130
60
82
0.65

75
130
60
82
0.78

75
130
60
82
0.78

Accessories
Signal
Auxiliary switch
UAD50C
UAD50S, UAD100R
Trip alarm switch
UAD50C
UAD50S, UAD100R
Shunt trip 1)
UAD50C
UAD50S, UAD100R
Under voltage trip2)
UAD50C
UAD50S, UAD100R

1C, right-hand-side
AUX 10A R1
AUX 10UA R1
1C, right-hand-side
ALT 10A R1
ALT 10UA R1
DC24V
SHT 10A A
SHT 10UA A
DC24V
UVT 10A J
UVT 10UA J

1C, left-hand-side

2C,right-hand-side
AUX 10A R2

AUX 10UA L1
1C, left-hand-side
ALT 10UA L1
AC100-120V
SHT 10A F
SHT 10UA F
DC100-110V
AC100-120V
UVT 10A L
UVT 10A N
UVT 10UA L
UVT 10UA N
DC100-110V
SHT 10A C

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.

120

AC200-230V
SHT 10UA H
AC200-230V
UVT 10A P
UVT 10UA P

AC380-415V
SHT 10A H
SHT 10UA B
AC380-415V
UVT 10A Q
UVT 10UA Q

AC440-480V
SHT 10UA D
AC440-480V
UVT 10A R
UVT 10UA R

MCCB

Operating
UAD50C
Power supply direction
S type

Operating Surface
L type
handle 1)
S type
Extended
L type
Motor operator 2)

UAD50S, UAD100R

Upper

Right

Left

Upper

Right

Left

TFG 10AS U4

TFG 10AS R4

TFG 10AS L4

TFG 10UAS U4

TFG 10UAS R4

TFG 10UAS L4

TFG 10AL L4

TFG 10UAL U4

TFG 10AL U4
TFH 10AS

TFG 10UAL L4
TFH 10UAS

TFH 10AL

TFH 10UAL

DC24V

AC/DC110V

AC/DC220V

DC24V

AC/DC110V

AC/DC220V

MOT 10A DC24

MOT 10A ADC110

MOT 10A ADC220

MOT 10UA DC24

MOT 10UA ADC110

MOT 10UA ADC220

Mechanical interlock

MIF 10A 3

MIF 10UA 3

Padlock plate3)

PLD 10UA

1) For detail type information, please refer to page 197-205.


2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.

Mounting
DIN-rail adaptor 1)
Structure
Mounting base
Plug-in Connection 2C contact
block 2)
3C contact
Conn block barrier

DRA 10UA
For both line & load side
TDM 10AP
CBM 10AB 2
CBM 10AB 3
CBM BARR

For line side only


TDM 10AF

1) Available for UAD50S, UAD100R


2) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.

Terminal
Cage terminal block

3EA/SET

UAD50C, UAD50S

UAD100R

CTB 10A 3S50

CTB 10A 3S100

Terminal cover 1)
Interpole barrier 2)

TCF 10AP 3
2EA/SET

TQQ 10A 3PLINE

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 4EA

Standard order code and unit


3 pole

Rated
current

Code

UAD50C

50A

UAD50C 3PDS0000C 00050

20

UAB50C

UAD50S

50A

UAD50S 3PDS0000C 00050

20

UAB50S

UAD100R

100A

UAD100R 3PDS0000C 00100

20

UAB100R

Model

Unit
(EA)

Originated
MCCB model

Specification

Category

Screw type
terminal connection,
No option, 50/60Hz

MCCB/M5

Molded Case Circuit Breaker_ 121

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| Switch disconnector / UCD type 50-250AF |
UCD50H
UCD100H
UCD250S

UCD100S
UCD160H
UCD250H

Ampere frame size


Number of poles (P)
Degree of protection (with terminal cover)
Utilization category
Suitability of isolation
Conventional thermal current [Ith] (A)
Rated current (A)
Rated insulation voltage [Ui] (V)
Rating

Rated operational voltage [Ue] (V)

Rated impulse withstand voltage [Uimp] (kV)


Rated short-circuit making capacity [Icm] (kA peak at AC460V)
Rated short-time withstand current for 1sec. [Icw] (kA r.m.s.)
Mechanical
operation
Durability
(times)
Electrical operation
Direct mounting by screw
Both line & load side
for
Mounting
Switchboard Line side only
Plug-in
for Distribution board
Screw
Terminal connection
Bus bar
a
Width
b
Height
Dimensions
3P
(mm)
c
Depth
d
Weight (kg, breaker only) 3P

UCD50H

UCD100S

UCD100H

UCD160H

UCD250S

UCD250H

50AF
3
IP20
A

100AF
3
IP20
A

125AF
3
IP20
A

160AF
3
IP20
A

3
IP20
A

3
IP20
A

50
AC690
AC660
DC250
6
105
1
25,000
10,000

100
AC690
AC660
DC250
6
73.5
1
25,000
10,000

125
AC690
AC660
DC250
6
105
1
25,000
10,000

160
AC690
AC660
DC250
6
105
2
25,000
10,000

250
AC690
AC660
DC250
6
73.5
2
25,000
10,000

250
AC690
AC660
DC250
6
105
2
25,000
10,000

90
155
60
84.5
1

90
155
60
84.5
1

90
155
60
84.5
1

105
165
60
84.5
1.3

105
164
60
84
1.2

105
165
60
84.5
1.3

250AF

Accessories
Signal
Auxiliary switch

1C, left-hand-side

UCD100S

AUX 10B L1

UCD250S

AUX 20C L1

UCD50H, UCD100H, UCD160H, UCD250H

AUX 20FG L1

Trip alarm switch

2C, left-hand-side

AUX 12FG L2

1C, right-hand-side

1C, left-hand-side

UCD100S

ALT 10B L1

UCD250S

ALT 20C L

UCD50H, UCD100H, UCD160H, UCD250H


Shunt trip 1)
UCD100S

DC24V

ALT 12FG R1
DC100-110V

SHT 10B A

AC100-120V

AC200-230V

SHT 10B F

ALT 12FG L1
AC380-415V

UCD250S

SHT 20C A

UCD50H, UCD100H, UCD160H, UCD250H

SHT 12FG A

SHT 12FG C

SHT 12FG F

SHT 12FG H

SHT 12FG B

SHT 12FG D

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

AC440-480V

UCD100S

UVT 10B J

UVT 10B L

UVT 10B N

UVT 10B P

UVT 10B Q

UVT 10B R

UCD250S

UVT 20C J

UVT 20C L

UVT 20C N

UVT 20C P

UVT 20C Q

UVT 20C R

UCD50H, UCD100H, UCD160H, UCD250H

UVT 12FG J

UVT 12FG L

UVT 12FG N

UVT 12FG P

UVT 12FG Q

UVT 12FG R

Under voltage trip 2)

SHT 20C F

SHT 20C H

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC)

Be sure not to use UVT for the electrical interlock system.

122

AC440-480V

SHT 10B H

MCCB

Operating
UCD50H, UDC100H
Power supply direction
S type

Operating Surface
L type
handle 1)
S type
Extended
L type
Motor operator 2)

UCD100S

Upper

Right

Left

Upper

Right

Left

TFG 10UFS U4

TFG 10UFS R4

TFG 10UFS L4

TFG 10BS U4

TFG 10BS R4

TFG 10BS L4

TFG 10UFL L4

TFG 10BL U4

TFG 10UFL U4
TFH 10UFS

TFG 10BL L4
TFH 10BS

TFH 10UFL

TFH 10BL

DC24V

AC/DC110V

AC/DC220V

DC24V

AC/DC110V

AC/DC220V

MOT 10F DC24

MOT 10F ADC110

MOT 10F ADC220

MOT 10UB DC24

MOT 10UB ADC110

MOT 10UB ADC220

MIF 10UF 3

Mechanical interlock

MIF 10UF 3

Padlock plate3)

PLD 10UF
UCD250S

Power supply direction


S type

Operating Surface
L type
handle 1)
S type
Extended
L type
Motor operator 2)

UCD160H, UCD250H

Upper

Right

Left

Upper

Right

Left

TFG 20CS U4

TFG 20CS R4

TFG 20CS L4

TFG 20UGS U4

TFG 20UGS R4

TFG 20UGS L4

TFG 20CL L4

TFG 20UGL U4

TFG 20CL U4
TFH 20CS

TFG 20UGL L4
TFH 20UGS

TFH 20CL

TFH 20UGL

DC24V

AC/DC110V

AC/DC220V

DC24V

AC/DC110V

AC/DC220V

MOT 20C DC24

MOT 20C ADC110

MOT 20C ADC220

MOT 20G DC24

MOT 20G ADC110

MOT 20G ADC220

Mechanical interlock

MIF 20UG 3

MIF 20UG 3

Padlock plate3)

PLD 20UG

1) For detail type information, please refer to page 197-205.


2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.

Mounting
UCD50H, UCD100S, UCD100H
Structure
For both line & load side For line side only
Mounting base
TDM 10BP
TDM 10BF
Plug-in Connection 2C contact
CBM 10AB 2
block 1)
3C/5C contact CBM 10AB 3 3)
Conn. block barrier
CBM BARR

UCD160H, UCD250S, UCD250H


For both line & load side

For line side only

TDM 20CF 2)
CBM 20C 2
CBM 20C 5 3)

TDM 20CF

1) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.
2) 2EA are required for both line & load side plug-in type 3P breaker.
3) CBM 10AB 3: 3C, CBM 20C 5: 5C

Terminal
UCD100S

UCD50H, UCD100H

UCD250S

Cage terminal block

3EA/SET

Terminal cover 1)
Interpole barrier 2)

UCD160H, UCD250H

TBB 20C 3

Terminal bus bar


CTB 10B 3S
TCF 10BP 3
2EA/SET

CTB 20C 3S

TCF 10FP 3

TCF 20CP 3

TCF 20GP 3

TQQ 10B 3PLINE TQQ 12FG 3PLINE TQQ 20C 3PLINE TQQ 12FG 3PLINE

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 4EA

Standard order code and unit


3 pole

Originated
MCCB model

Rated
current

Code

UCD50H

50A

UCD50H 3PDS0000C 00050

UCB50H

UCD100S

100A

UCD100S 3PDS0000C 00100

10

UCB100S

UCD100H

125A

UCD100H 3PDS0000C 00125

UCB100H

UCD160H

160A

UCD160H 3PDS0000C 00160

UCB160H

UCD250S

250A

UCD250S 3PDS0000C 00250

10

UCB250S

UCD250H

250A

UCD250H 3PDS0000C 00250

UCB250H

Model

Unit
(EA)

Specification

Category

Screw type
terminal connection,
No option, 50/60Hz

MCCB/M5

Molded Case Circuit Breaker_ 123

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| Switch disconnector / UCD type 400-1250AF |
UCD400S
UCD630S
UCD800S
UCD1000S
UCD1250S

Ampere frame size


Number of poles (P)
Degree of protection (with terminal cover)
Utilization category
Suitability of isolation
Conventional thermal current [Ith] (A)
Rated current (A)
Rated insulation voltage [Ui] (V)
Rating

Rated operational voltage [Ue] (V)


Rated impulse withstand voltage [Uimp] (kV)

Rated short-circuit making capacity [Icm] (kA peak at AC460V)


Rated short-time withstand current for 1sec. [Icw] (kA r.m.s.)
Mechanical
operation
Durability
(times)
Electrical operation
Direct mounting by screw
Mounting
Both line & load side
for
Plug-in
Switchboard Line side only
Screw
Terminal connection
Bus bar
a
Width
Dimensions
(mm)

3P

b
c
d

UCD400S

UCD630S

UCD800S

UCD1000S

UCD1250S

400AF
3
IP20
A

630AF
3
IP20
A

800AF
3
IP20
A

1000AF
3
IP20 1)
A

1250AF
3
IP20 1)
A

400
400
AC690
AC660
DC250
6
187
4
20,000
6,000

630
630
AC690
AC660
DC250
6
187
6.3
20,000
6,000

800
800
AC690
AC660
DC250
6
187
8
10,000
3,000

1,000
1,000
AC750
AC690

1,250
1,250
AC750
AC690

8
165
10
10,000
3,000

8
165
12.5
10,000
3,000

140
257
110
145
4.5

210
280
110
145
9.5

210
280
110
145
9.5

210
370
110
159
13

210
370
110
159
13.5

Height
Depth

Weight (kg, breaker only) 3P


1) IP20 without terminal bus bar

Accessories
Signal
Auxiliary switch
1C, right-hand-side
UCD400, UCD630, UCD800
AUX 46D R1
UCD1000, UCD1250
AUX 80NE R1
1C, left-hand-side
Trip alarm switch
ALT 46D L1
UCD400, UCD630, UCD800
UCD1000, UCD1250
Shunt trip 1)
DC24V
SHT 46D A
UCD400, UCD630, UCD800
SHT 120NE A
UCD1000, UCD1250
DC24V
Under voltage trip 2)
UVT 46D J
UCD400, UCD630,UCD800
UVT 120NE J
UCD1000, UCD1250

2C, right-hand-side

3C, right-hand-side

AUX 80NE R2
AUX 80NE R3
1C, right-hand-side
ALT 80NE R1
DC100-110V
AC100-120V
SHT 46D C
SHT 46D F
SHT 120NE C
SHT 120NE F
DC100-110V
AC100-120V
UVT 46D L
UVT 46D N
UVT 120NE L
UVT 120NE N

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)

Be sure not to use UVT for the electrical interlock system.


Reset is possible without power.

124

AC200-230V
SHT 46D H
SHT 120NE H
AC200-230V
UVT 46D P
UVT 120NE P

AC380-415V
SHT 46D B
SHT 120NE B
AC380-415V
UVT 46D Q
UVT 120NE Q

AC440-480V
SHT 46D D
SHT 120NE D
AC440-480V
UVT 46D R
UVT 120NE R

MCCB

Operating
UCD400, UCD630, UCD800
Power supply direction

Operating
Surface S type
handle 1)
Extended S type

Upper

Right

Left

TFG 46DS U2

TFG 46DS R2

TFG 46DS L2

TFH 46DS
UCD400
DC24V

Motor operator 2)

UCD630, UCD800

AC/DC110V

AC/DC220V

DC24V

AC/DC110V

MOT 40D DC24 MOT 40D ADC110 MOT 40D ADC220 MOT 68E DC24

Mechanical interlock

UCD1000, UCD1250

AC/DC220V

DC24V

AC/DC110V

AC/DC220V

MOT 68E ADC110 MOT 68E ADC220 MOT 80NE DC24 MOT 80NE ADC110 MOT 80NE ADC220

MIF 40D 3

MIF 80E 3

Padlock plate3)

PLD 40D

PLD 120NE

Extension handle 4)

THA 46D

THA 120NE

1) For detail type information, please refer to page 197-205.


2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.
4) Supplied as standard component.

Mounting
UCD400
Structure
Mounting base
Plug-in
Connection 2C contact
5C contact
block 1)

For both line & load side

TDM 4BA 2)
TYA 5/2 3)
TYA 5/5 3)

UCD630, UCD800

For line side only For both line & load side For line side only

TDM 4BA

TDM 5BA 2)
TYA 5/2 3)
TYA 5/5 3)

TDM 5BA

1) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.
2) 2EA are required for both line & load side plug-in type 3P breaker.
3) TYA type connection blocks are to be installed with separate mounting angle. Separate mounting angle is not supplied.

Terminal
Terminal bus bar
Cage terminal block

3EA/SET

Terminal cover 1)
Interpole barrier 2)

UCD400

UCD630

UCD800

TBB 4S 3

TBB 6S 3

TBB 8S 3

CTB 40D 3S

UCD1000, UCD1250

CTB 80E 3S

TCF 40D 3

TCF 80E 3

2EA/SET TQQ 4BA 3PLINE

TQQ 5BA 3PLINE

TQQ 80NE 3P

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 4EA

Standard order code and unit


3 pole

Originated
MCCB model

Model

Rated
current

Code

Unit
(EA)

UCD400S

400A

UCD400S 3PDS0000C 00400

UCB400S

UCD630S

630A

UCD630S 3PDS0000C 00630

UCB630S

UCD800S

800A

UCD800S 3PDS0000C 00800

UCB800S

UCD1000S

1000A

UCD1000S 3PDB0000C 01000

UCB1000S

UCD1250S

1250A

UCD1250S 3PDB0000C 01250

UCB1250S

Specification
Screw type
terminal connection,
No option, 50/60Hz

Category

MCCB/M5

Bus bar type


terminal connection,
No option, 50/60Hz

Molded Case Circuit Breaker_ 125

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| Switch disconnector / UPD type 125-630AF |
UPD100S
UPD160S
UPD250S
UPD400S
UPD630S

UPD100S

UPD160S

UPD250S

UPD400S

UPD630S

Ampere frame size

125AF

160AF

250AF

400AF

630AF

Number of poles (P)

IP20

IP20

IP20

IP20

IP20

Conventional thermal current [Ith] (A)

125

160

250

400

630

Rated current (A)

125

160

250

400

630

AC750

AC750

AC750

AC750

AC750

AC690

AC690

AC690

AC690

AC690

DC500

DC500

DC500

200

200

200

200

200

Degree of protection (with terminal cover)


Utilization category
Suitability of isolation

Rated insulation voltage [Ui] (V)


Rating

Rated operational voltage [Ue] (V)


Rated impulse withstand voltage [Uimp] (kV)
Rated short-circuit making capacity [Icm] (kA peak at AC460V)

1.6

2.5

6.3

25,000

25,000

25,000

20,000

20,000

10,000

10,000

10,000

6,000

6,000

Width

105

105

105

140

140

Height

165

165

165

255

255

Depth

86.5

86.5

86.5

117

117

112

112

112

159.5

159.5

1.8

Rated short-time withstand current for 1sec. [Icw] (kA r.m.s)


Durability Mechanical operation
(times)
Electrical operation
Direct mounting by screw
Mounting

Plug-in

Both line & load side


for
Switchboard Line side only
Screw

Terminal connection

Bus bar
a

Dimensions
(mm)

3P

d
Weight (kg, breaker only) 3P

Accessories
Signal
Auxiliary switch
1C, right-hand-side 1C, left-hand-side
UPD100, UPD160,UPD250
AUX 12UP R1
UPD400, UPD630
AUX 46UP L1
1C, right-hand-side 1C, left-hand-side
Trip alarm switch
ALT 12UP L1
UPD100, UPD160,UPD250
ALT 46UP R1
UPD400, UPD630
DC24V
DC100-110V
Shunt trip 1)
SHT 12UP A
SHT 12UP C
UPD100, UPD160,UPD250
UPD400, UPD630
SHT 46UP A
SHT 46UP C
Under voltage trip 2)
DC24V
DC100-110V
UPD100, UPD160,UPD250
UVT 12UP J
UVT 12UP L
UPD400, UPD630
UVT 46UP J
UVT 46UP L

AC100-120V
SHT 12UP F
SHT 46UP F
AC100-120V
UVT 12UP N
UVT 46UP N

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)

Be sure not to use UVT for the electrical interlock system.


Reset is possible without power.

126

AC200-230V
SHT 12UP H
SHT 46UP H
AC200-230V
UVT 12UP P
UVT 46UP P

AC380-415V
SHT 12UP B
SHT 46UP B
AC380-415V
UVT 12UP Q
UVT 46UP Q

AC440-480V
SHT 12UP D
SHT 46UP D
AC440-480V
UVT 12UP R
UVT 46UP R

MCCB

Operating
UPD100, UPD160, UPD250
Power supply direction
S type

Operating Surface
L type
handle 1)
S type
Extended
L type

Right

Left

Upper

Right

Left

TFG 12UPS U4

TFG 12UPS R4

TFG 12UPS L4

TFG 46UPS U2

TFG 46UPS R2

TFG 46UPS L2

TFG 12UPL U4

TFG 12UPL L4
TFH 12UPS

TFH 46UPS

TFH 12UPL
DC24V

Motor operator 2)

UPD400, UPD630

Upper

AC/DC110V

MOT 12UP DC24

AC/DC220V

DC24V

MOT 12UP ADC110 MOT 12UP ADC220

AC/DC110V

MOT 46NE DC24

Mechanical interlock

MIF 12UP 3

MIF 46UP 3

Padlock plate3)

PLD 12UP

PLD 12UP

Extension handle 4)

AC/DC220V

MOT 46NE ADC110 MOT 46NE ADC220

THA 46UP

1) For detail type information, please refer to page 197-205.


2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.
4) Supplied as standard component.

Mounting
UPD100, UPD160, UPD250
Structure
Plug-in

UPD400, UPD630

For both line & load side For line side only For both line & load side For line side only

Mounting base

TDM 12NEP

Connection 6C contact
block 1)
12C contact

CBM 26NE 6

TDM 12NEF

TDM 46NEP

TDM 46NEF

CBM 26NE 6

2)

2)

CBM 26NE 6

CBM 26NE 6

1) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.
2) 2EA shall be ordered for 12C contact.

Terminal
UPD100, UPD160, UPD250

UPD400

UPD630

Terminal bus bar

6EA/SET

TBB 12NE 3

TBB 40NE 3 TBB 60NE 3

Cage terminal block

3EA/SET

CTB 12UP 3S

CTB 46UP 3S

Terminal cover 1)
Interpole barrier 2)

4EA/SET

TCF 12UP 3

TCF 46UP 3

TQQ 12NE 3P

TQQ 46NE 3P

1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 4EA

Standard order code and unit


3 pole

Originated
MCCB model

Model

Rated
current

UPD100S

125A

UPD100S 3PDS0000C 00125

UPB100S

UPD160S

160A

UPD160S 3PDS0000C 00160

UPB160S

UPD250S

250A

UPD250S 3PDS0000C 00250

UPB250S

UPD400S

400A

UPD400S 3PDS0000C 00400

UPB400S

UPD630S

630A

UPD630S 3PDS0000C 00630

UPB630S

Code

Unit
(EA)

Specification

Category

Screw type
terminal connection,
No option, 50/60Hz

MCCB/M5

Molded Case Circuit Breaker_ 127

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


| Miniature type / Molded case circuit breaker UMB type 30-50AF |
UMB30R 2.5kA
UMB30S 5kA
UMB50S 5kA

UMB30R

UMB30S

UMB30H

UMB50S

UMB50H

UMB30H 10kA
UMB50H 10kA

Ampere frame size

30AF

Number of poles (P)

Degree of protection

IP20

IP20

Utilization category
Protection

overload, short-circuit

overload, short-circuit

Rated current (A)


Rating

15, 20, 30

15, 20, 30, 40, 50

Rated insulation voltage [Ui] (V)

AC250

AC250

Rated operational voltage [Ue] (V)

AC220

AC220

Rated impulse withstand voltage [Uimp] (kV)


Ultimate [Icu]
AC220/240V, 50-60Hz
(kA r.m.s.)

Rated
short-circuit
breaking capacity
IEC 60947-2
Service [Ics] % of [Icu]
K 60947-2
Trip mechanism

50AF

2.5

10

50

10
50

Hydraulic magnetic
Thermal magnetic

Mounting

Direct mounting by screw


DIN-rail

Terminal connection
Dimensions
(mm)

Screw

2P

Width

33

35

35

Height

70

80

80

Depth

42

60

60

57

76

76

0.1

0.13

0.15

d
Weight (kg, breaker only)

2P

- KS certified products. English nameplate and 50Hz marking are not available.
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.

Standard order code and unit


40/45
Model /
Breaking capacity at
AC220/240V

UMB30R
2.5kA
UMB30S
5kA
UMB30H
10kA

UMB50S
5kA

UMB50H
10kA

128

Rated
current
15A
20A
30A
15A
20A
30A
15A
20A
30A
15A
20A
30A
40A
50A
15A
20A
30A
40A
50A

2 pole
Code
UMB30R 2PT4S0000C 00015
UMB30R 2PT4S0000C 00020
UMB30R 2PT4S0000C 00030
UMB30S 2PT4S0000C 00015
UMB30S 2PT4S0000C 00020
UMB30S 2PT4S0000C 00030
UMB30H 2PT4S0000C 00015
UMB30H 2PT4S0000C 00020
UMB30H 2PT4S0000C 00030
UMB50S 2PT4S0000C 00015
UMB50S 2PT4S0000C 00020
UMB50S 2PT4S0000C 00030
UMB50S 2PT4S0000C 00040
UMB50S 2PT4S0000C 00050
UMB50H 2PT4S0000C 00015
UMB50H 2PT4S0000C 00020
UMB50H 2PT4S0000C 00030
UMB50H 2PT4S0000C 00040
UMB50H 2PT4S0000C 00050

Unit(EA)
150
150
150
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80

Specification

Category

Screw type
terminal connection,
No option, 50/60Hz

MCCB/M1

MCCB

| Miniature type / Molded case circuit breaker UDB type 30-100AF |


UDB30S 5kA
UDB50S 5kA
UDB100S 5kA

UDB30H 10kA
UDB50H 10kA
UDB100H 10kA

UDB30S

UDB30H

UDB50S

UDB50H

UDB100S

UDB100H

Ampere frame size

30AF

50AF

Number of poles (P)

2, 3

2, 3

2, 3

Degree of protection

IP20

IP20

IP20

Utilization category
Rated current (A)

Rated operational voltage [Ue] (V)

Service [Ics]
Trip mechanism

overload, short-circuit

5,10,15,20,30,40,50

AC460

AC460

AC460

2P: AC220

2P: AC220

2P: AC220

3P: AC220/460

3P: AC220/460

3P: AC220/460

Rated impulse withstand voltage [Uimp] (kV)

Rated
short-circuit
Ultimate
breaking capacity [Icu]
(kA r.m.s.)
IEC 60947-2
K 60947-2

overload, short-circuit

3 1) ,5,10,15,20,30

Rated insulation voltage [Ui] (V)

Rating

overload, short-circuit

Protection

100AF

AC440/460V, 50-60Hz

2.5

AC380/415V, 50-60Hz

2.5

AC220/240V, 50-60Hz

5-10A: 2.5
15-30A: 5
5-10A: 2.5
15-30A: 5
5-10A: 5
15-30A: 10

% of [Icu]

5-10A: 2.5

2.5

15-50A: 5
5-10A: 2.5

2.5

15-50A: 5
5-10A: 5

15-50A: 10

15,20,30,40,50,60,75,100

2.5

2.5

10

50

50

50

Hydraulic magnetic
Direct mounting by screw

Mounting

DIN-rail

Terminal connection

Screw

Dimensions
(mm)

2/3P

Width

50/75

50/75

75 2) /75

Height

96

96

96

Depth

60

60

60

80

80

80

0.2/0.35

0.2/0.35

0.2/0.35

d
Weight (kg, breaker only)

2/3P

- KS certified products. English nameplate and 50Hz marking are not available.
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) 3A is not applicable for UDB30H.
2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.

Accessories
Signal
Auxiliary switch 1C, left-hand-side

AUX 10UD L1

AUX 10UD L1T 2)

2 pole
Trip alarm switch 1C,
left-hand-side 3 pole

ALT 10UD 2L1

ALT 10UD 2L1T 2)

ALT 10UD 3L1

ALT 10UD 3L1T 2)

Shunt trip 1)

DC24V

DC100-110V

AC100-120V

AC200-230V

AC380-415V

AC440-480V

SHT 10UD A

SHT 10UD C

SHT 10UD F

SHT 10UD H

SHT 10UD B

SHT 10UD D

SHT 10UD AT 2)

SHT 10UD CT 2)

SHT 10UD FT 2)

SHT 10UD HT 2)

SHT 10UD BT 2)

SHT 10UD DT 2)

1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) Terminal block type

Terminal
Interpole barrier 1)

2EA/SET

TQQ 10A 3PLINE

1) Supplied as standard component


Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA
Molded Case Circuit Breaker_ 129

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


Standard order code and unit
40/45
Model /
Breaking capacity at
AC220/240V

3 pole

2 pole
Code

Unit
(EA)

Code

Unit
(EA)

3A

UDB30S 2PT4S0000C 00003

46

UDB30S 3PT4S0000C 00003

32

5A

UDB30S 2PT4S0000C 00005

46

UDB30S 3PT4S0000C 00005

32

UDB30S

10A

UDB30S 2PT4S0000C 00010

46

UDB30S 3PT4S0000C 00010

32

5kA

15A

UDB30S 2PT4S0000C 00015

46

UDB30S 3PT4S0000C 00015

32

20A

UDB30S 2PT4S0000C 00020

46

UDB30S 3PT4S0000C 00020

32

30A

UDB30S 2PT4S0000C 00030

46

UDB30S 3PT4S0000C 00030

32

5A

UDB30H 2PT4S0000C 00005

46

UDB30H 3PT4S0000C 00005

32

UDB30H

10A

UDB30H 2PT4S0000C 00010

46

UDB30H 3PT4S0000C 00010

32

5-10A : 5kA
15-30A : 10kA

15A

UDB30H 2PT4S0000C 00015

46

UDB30H 3PT4S0000C 00015

32

20A

UDB30H 2PT4S0000C 00020

46

UDB30H 3PT4S0000C 00020

32

30A

UDB30H 2PT4S0000C 00030

46

UDB30H 3PT4S0000C 00030

32

5A

UDB50S 2PT4S0000C 00005

46

UDB50S 3PT4S0000C 00005

32

10A

UDB50S 2PT4S0000C 00010

46

UDB50S 3PT4S0000C 00010

32

15A

UDB50S 2PT4S0000C 00015

46

UDB50S 3PT4S0000C 00015

32

20A

UDB50S 2PT4S0000C 00020

46

UDB50S 3PT4S0000C 00020

32

30A

UDB50S 2PT4S0000C 00030

46

UDB50S 3PT4S0000C 00030

32

40A

UDB50S 2PT4S0000C 00040

46

UDB50S 3PT4S0000C 00040

32

50A

UDB50S 2PT4S0000C 00050

46

UDB50S 3PT4S0000C 00050

32

5A

UDB50H 2PT4S0000C 00005

46

UDB50H 3PT4S0000C 00005

32

10A

UDB50H 2PT4S0000C 00010

46

UDB50H 3PT4S0000C 00010

32

UDB50H

15A

UDB50H 2PT4S0000C 00015

46

UDB50H 3PT4S0000C 00015

32

5-10A : 5kA
15-50A : 10kA

20A

UDB50H 2PT4S0000C 00020

46

UDB50H 3PT4S0000C 00020

32

30A

UDB50H 2PT4S0000C 00030

46

UDB50H 3PT4S0000C 00030

32

40A

UDB50H 2PT4S0000C 00040

46

UDB50H 3PT4S0000C 00040

32

50A

UDB50H 2PT4S0000C 00050

46

UDB50H 3PT4S0000C 00050

32

15A

UDB100S 2PT4S0000C 00015

32

UDB100S 3PT4S0000C 00015

32

20A

UDB100S 2PT4S0000C 00020

32

UDB100S 3PT4S0000C 00020

32

UDB50S
5kA

130

Rated
current

30A

UDB100S 2PT4S0000C 00030

32

UDB100S 3PT4S0000C 00030

32

UDB100S

40A

UDB100S 2PT4S0000C 00040

32

UDB100S 3PT4S0000C 00040

32

5kA

50A

UDB100S 2PT4S0000C 00050

32

UDB100S 3PT4S0000C 00050

32

60A

UDB100S 2PT4S0000C 00060

32

UDB100S 3PT4S0000C 00060

32

75A

UDB100S 2PT4S0000C 00075

32

UDB100S 3PT4S0000C 00075

32

100A

UDB100S 2PT4S0000C 00100

32

UDB100S 3PT4S0000C 00100

32

15A

UDB100H 2PT4S0000C 00015

32

UDB100H 3PT4S0000C 00015

32

20A

UDB100H 2PT4S0000C 00020

32

UDB100H 3PT4S0000C 00020

32

30A

UDB100H 2PT4S0000C 00030

32

UDB100H 3PT4S0000C 00030

32

UDB100H

40A

UDB100H 2PT4S0000C 00040

32

UDB100H 3PT4S0000C 00040

32

10kA

50A

UDB100H 2PT4S0000C 00050

32

UDB100H 3PT4S0000C 00050

32

60A

UDB100H 2PT4S0000C 00060

32

UDB100H 3PT4S0000C 00060

32

75A

UDB100H 2PT4S0000C 00075

32

UDB100H 3PT4S0000C 00075

32

100A

UDB100H 2PT4S0000C 00100

32

UDB100H 3PT4S0000C 00100

32

Specification

Screw type
terminal
connection,
No option,
50/60Hz

Category

MCCB
/M1

MCCB

| Miniature type / Earth leakage circuit breaker UMG type 30-50AF |


UMG30R 2.5kA
UMG30S 5kA
UMG50S 5kA

UMG30R

UMG30S

UMG30H

UMG50S

UMG50H

UMG30H 10kA
UMG50H 10kA

Ampere frame size

30AF

50AF

Number of poles (P)

Degree of protection

IP20

IP20

Utilization category

A
15, 20, 30

Rated current (A)

Rating

earth leakage, overload, short-circuit


15, 20, 30, 40, 50

Rated residual current [I n] (mA)

15,30

15,30

Rated insulation voltage [Ui] (V)

AC250

AC250

Rated operational voltage [Ue] (V)

AC220

AC220

0.03

0.03

Rated impulse withstand voltage [Uimp] (kV)


Rated operating time (sec.)
Rated
Ultimate [Icu]
short-circuit
(kA r.m.s.)
breaking capacity

AC220/240V, 50-60Hz

IEC 60947-2
K 60947-2

Service [Ics] % of [Icu]

Earth leakage
protection

Earth leakage detection

Trip mechanism

earth leakage, overload, short-circuit

Protection

2.5

10

10

50

50

by current transformer

by current transformer

Earth leakage test button


Hydraulic magnetic
Thermal magnetic

Mounting

Direct mounting by screw


DIN-rail

Terminal connection
Dimensions

Screw

2P

(mm)

Width

33

35

35

Height

70

80

80

Depth

42

60

60

57

76

76

0.1

0.13

0.15

d
Weight (kg, breaker only)

2P

- KS certified products. English nameplate and 50Hz marking are not available.
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.

Molded Case Circuit Breaker_ 131

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


Standard order code and unit
15mA
Model /
Breaking capacity at
AC220/240V
UMG30R
2.5kA
UMG30S
5kA
UMG30H
10kA

UMG50S
5kA

UMG50H
10kA

Rated
current

2 pole
Code

Unit(EA)

15A

UMG30R 2PG3S0000C 00015

150

20A

UMG30R 2PG3S0000C 00020

150

30A

UMG30R 2PG3S0000C 00030

150

15A

UMG30S 2PG3S0000C 00015

80

20A

UMG30S 2PG3S0000C 00020

80

30A

UMG30S 2PG3S0000C 00030

80

15A

UMG30H 2PG3S0000C 00015

80

20A

UMG30H 2PG3S0000C 00020

80

30A

UMG30H 2PG3S0000C 00030

80

15A

UMG50S 2PG3S0000C 00015

80

20A

UMG50S 2PG3S0000C 00020

80

30A

UMG50S 2PG3S0000C 00030

80

40A

UMG50S 2PG3S0000C 00040

80

50A

UMG50S 2PG3S0000C 00050

80

15A

UMG50H 2PG3S0000C 00015

80

20A

UMG50H 2PG3S0000C 00020

80

30A

UMG50H 2PG3S0000C 00030

80

40A

UMG50H 2PG3S0000C 00040

80

50A

UMG50H 2PG3S0000C 00050

80

Specification

Category

15mA, 40/45 ,
Screw type
terminal connection,
No option, 50/60Hz

ELCB/M6

Specification

Category

30mA
Model /
Breaking capacity at
AC220/240V
UMG30R
2.5kA
UMG30S
5kA
UMG30H
10kA

UMG50S
5kA

UMG50H
10kA

132

Rated
current

2 pole
Code

Unit(EA)

15A

UMG30R 2PG4S0000C 00015

150

20A

UMG30R 2PG4S0000C 00020

150

30A

UMG30R 2PG4S0000C 00030

150

15A

UMG30S 2PG4S0000C 00015

80

20A

UMG30S 2PG4S0000C 00020

80

30A

UMG30S 2PG4S0000C 00030

80

15A

UMG30H 2PG4S0000C 00015

80

20A

UMG30H 2PG4S0000C 00020

80

30A

UMG30H 2PG4S0000C 00030

80

15A

UMG50S 2PG4S0000C 00015

80

20A

UMG50S 2PG4S0000C 00020

80

30A

UMG50S 2PG4S0000C 00030

80

40A

UMG50S 2PG4S0000C 00040

80

50A

UMG50S 2PG4S0000C 00050

80

15A

UMG50H 2PG4S0000C 00015

80

20A

UMG50H 2PG4S0000C 00020

80

30A

UMG50H 2PG4S0000C 00030

80

40A

UMG50H 2PG4S0000C 00040

80

50A

UMG50H 2PG4S0000C 00050

80

30mA, 40/45 ,
Screw type
terminal connection,
No option, 50/60Hz

ELCB/M6

MCCB

| Miniature type / Earth leakage circuit breaker UDG type 30-100AF |


UDG30S 5kA
UDG50S 5kA
UDG100S 5kA

UDG30H 10kA
UDG50H 10kA
UDG100H 10kA

UDG30S

UDG30H

UDG50S

UDG50H

UDG100S

UDG100H

Ampere frame size

30AF
50AF
100AF
2, 3
2, 3
*2, 3
IP20
IP20
IP20
A
A
A
earth leakage, overload, short-circuit earth leakage, overload, short-circuit earth leakage, overload, short-circuit
3 1), 5,10,15,20,30
5,10,15,20,30,40,50
15,20,30,40,50,60,75,100
15, 30
15, 30
30, 100
AC460
AC460
AC460
Rating
2P: AC220
2P: AC220
2P: AC220
Rated operational voltage [Ue] (V)
3P: AC220/460
3P: AC220/460
3P: AC220/460
Rated impulse withstand voltage [Uimp] (kV)
6
6
6
Rated operating time (sec.)
0.03
0.03
0.03
5-10A: 2.5
5-10A: 2.5
AC440/460V, 50-60Hz
2.5
2.5
2.5
5
Rated
15-30A: 5
15-50A: 5
Ultimate
short-circuit
5-10A: 2.5
5-10A: 2.5
AC380/415V, 50-60Hz
2.5
2.5
2.5
5
breaking capacity [Icu]
15-30A: 5
15-50A: 5
(kA r.m.s.)
5-10A: 5
5-10A: 5
IEC 60947-2
AC220/240V, 50-60Hz
5
5
5
10
15-30A: 10
15-50A: 10
K 60947-2
Service [Ics] % of [Icu]
50
50
50
Earth leakage detection
by current transformer
by current transformer
by current transformer
Number of poles (P)
Degree of protection
Utilization category
Protection
Rated current (A)
Rated residual current [I n] (mA)
Rated insulation voltage [Ui] (V)

Earth leakage
protection

Earth leakage test button


Earth leakage indicator
Trip mechanism Hydraulic magnetic
Direct mounting by screw
Mounting
DIN-rail
Terminal connection
Screw
a
Width
Dimensions
b
Height
2/3P
(mm)
c
Depth
d
Weight (kg, breaker only)
2/3P

50/75
96
60
80
0.33/0.44

50/75
96
60
80
0.33/0.44

75 2)/75
96
60
80
0.46/0.63

- KS certified products. English nameplate and 50Hz marking are not available.
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) 3A is not applicable for UDG30H.
2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.

Accessories
Signal
Auxiliary switch

1C, left-hand-side

Trip alarm switch

1C, left-hand-side

AUX 10UD L1
2 pole

ALT 10UD 2L1

3 pole

ALT 10UD 3L1

Terminal
Interpole barrier 1)

2EA/SET

TQQ 10A 3PLINE

1) Supplied as standard component


Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA

Molded Case Circuit Breaker_ 133

U-Series

Molded Case Circuit Breaker

Specifications and Standard Order Codes


Standard order code and unit
15mA
Model /
Breaking capacity at
AC220/240V

UDG30S
5kA

UDG30H
5-10A : 5kA
15-30A : 10kA

UDG50S
5kA

UDG50H
5-10A : 5kA
15-50A : 10kA

Rated
current

2 pole
Code

3 pole
Unit
(EA)

Code

Unit
(EA)

3A

UDG30S 2PG3S0000C 00003

46

UDG30S 3PG3S0000C 00003

32

5A

UDG30S 2PG3S0000C 00005

46

UDG30S 3PG3S0000C 00005

32

10A

UDG30S 2PG3S0000C 00010

46

UDG30S 3PG3S0000C 00010

32

15A

UDG30S 2PG3S0000C 00015

46

UDG30S 3PG3S0000C 00015

32

20A

UDG30S 2PG3S0000C 00020

46

UDG30S 3PG3S0000C 00020

32

30A

UDG30S 2PG3S0000C 00030

46

UDG30S 3PG3S0000C 00030

32

5A

UDG30H 2PG3S0000C 00005

46

UDG30H 3PG3S0000C 00005

32

10A

UDG30H 2PG3S0000C 00010

46

UDG30H 3PG3S0000C 00010

32

15A

UDG30H 2PG3S0000C 00015

46

UDG30H 3PG3S0000C 00015

32

20A

UDG30H 2PG3S0000C 00020

46

UDG30H 3PG3S0000C 00020

32

30A

UDG30H 2PG3S0000C 00030

46

UDG30H 3PG3S0000C 00030

32

5A

UDG50S 2PG3S0000C 00005

46

UDG50S 3PG3S0000C 00005

32

10A

UDG50S 2PG3S0000C 00010

46

UDG50S 3PG3S0000C 00010

32

15A

UDG50S 2PG3S0000C 00015

46

UDG50S 3PG3S0000C 00015

32

20A

UDG50S 2PG3S0000C 00020

46

UDG50S 3PG3S0000C 00020

32

30A

UDG50S 2PG3S0000C 00030

46

UDG50S 3PG3S0000C 00030

32

40A

UDG50S 2PG3S0000C 00040

46

UDG50S 3PG3S0000C 00040

32

50A

UDG50S 2PG3S0000C 00050

46

UDG50S 3PG3S0000C 00050

32

5A

UDG50H 2PG3S0000C 00005

46

UDG50H 3PG3S0000C 00005

32

10A

UDG50H 2PG3S0000C 00010

46

UDG50H 3PG3S0000C 00010

32

15A

UDG50H 2PG3S0000C 00015

46

UDG50H 3PG3S0000C 00015

32

20A

UDG50H 2PG3S0000C 00020

46

UDG50H 3PG3S0000C 00020

32

30A

UDG50H 2PG3S0000C 00030

46

UDG50H 3PG3S0000C 00030

32

40A

UDG50H 2PG3S0000C 00040

46

UDG50H 3PG3S0000C 00040

32

50A

UDG50H 2PG3S0000C 00050

46

UDG50H 3PG3S0000C 00050

32

Specification

Category

15mA, 40/45 ,
Screw type
terminal
connection,
No option,
50/60Hz

ELCB
/M6

30mA
Model /
Breaking capacity at
AC220/240V

UDG30S
5kA

UDG30H
5-10A : 5kA
15-30A : 10kA

UDG50S
5kA

134

Rated
current

2 pole
Code

3 pole
Unit
(EA)

Code

Unit
(EA)

Specification

3A

UDG30S 2PG4S0000C 00003

46

UDG30S 3PG4S0000C 00003

32

5A

UDG30S 2PG4S0000C 00005

46

UDG30S 3PG4S0000C 00005

32

10A

UDG30S 2PG4S0000C 00010

46

UDG30S 3PG4S0000C 00010

32

15A

UDG30S 2PG4S0000C 00015

46

UDG30S 3PG4S0000C 00015

32

20A

UDG30S 2PG4S0000C 00020

46

UDG30S 3PG4S0000C 00020

32

30A

UDG30S 2PG4S0000C 00030

46

UDG30S 3PG4S0000C 00030

32

5A

UDG30H 2PG4S0000C 00005

46

UDG30H 3PG4S0000C 00005

32

30mA, 40/45 ,

10A

UDG30H 2PG4S0000C 00010

46

UDG30H 3PG4S0000C 00010

32

15A

UDG30H 2PG4S0000C 00015

46

UDG30H 3PG4S0000C 00015

32

20A

UDG30H 2PG4S0000C 00020

46

UDG30H 3PG4S0000C 00020

32

30A

UDG30H 2PG4S0000C 00030

46

UDG30H 3PG4S0000C 00030

32

5A

UDG50S 2PG4S0000C 00005

46

UDG50S 3PG4S0000C 00005

32

Screw type
terminal
connection,
No option,
50/60Hz

10A

UDG50S 2PG4S0000C 00010

46

UDG50S 3PG4S0000C 00010

32

15A

UDG50S 2PG4S0000C 00015

46

UDG50S 3PG4S0000C 00015

32

20A

UDG50S 2PG4S0000C 00020

46

UDG50S 3PG4S0000C 00020

32

30A

UDG50S 2PG4S0000C 00030

46

UDG50S 3PG4S0000C 00030

32

40A

UDG50S 2PG4S0000C 00040

46

UDG50S 3PG4S0000C 00040

32

50A

UDG50S 2PG4S0000C 00050

46

UDG50S 3PG4S0000C 00050

32

Category

ELCB
/M6

MCCB

Model /
Breaking capacity at
AC220/240V

Rated
current

2 pole
Code

3 pole
Unit
(EA)

Code

Unit
(EA)

Specification

5A

UDG50H 2PG4S0000C 00005

46

UDG50H 3PG4S0000C 00005

32

10A

UDG50H 2PG4S0000C 00010

46

UDG50H 3PG4S0000C 00010

32

UDG50H

15A

UDG50H 2PG4S0000C 00015

46

UDG50H 3PG4S0000C 00015

32

5-10A : 5kA
15-50A : 10kA

20A

UDG50H 2PG4S0000C 00020

46

UDG50H 3PG4S0000C 00020

32

30A

UDG50H 2PG4S0000C 00030

46

UDG50H 3PG4S0000C 00030

32

40A

UDG50H 2PG4S0000C 00040

46

UDG50H 3PG4S0000C 00040

32

50A

UDG50H 2PG4S0000C 00050

46

UDG50H 3PG4S0000C 00050

32

15A

UDG100S 2PG4S0000C 00015

32

UDG100S 3PG4S0000C 00015

32

20A

UDG100S 2PG4S0000C 00020

32

UDG100S 3PG4S0000C 00020

32

30A

UDG100S 2PG4S0000C 00030

32

UDG100S 3PG4S0000C 00030

32

30mA, 40/45 ,

40A

UDG100S 2PG4S0000C 00040

32

UDG100S 3PG4S0000C 00040

32

50A

UDG100S 2PG4S0000C 00050

32

UDG100S 3PG4S0000C 00050

32

60A

UDG100S 2PG4S0000C 00060

32

UDG100S 3PG4S0000C 00060

32

75A

UDG100S 2PG4S0000C 00075

32

UDG100S 3PG4S0000C 00075

32

Screw type
terminal
connection,
No option,
50/60Hz

100A

UDG100S 2PG4S0000C 00100

32

UDG100S 3PG4S0000C 00100

32

15A

UDG100H 2PG4S0000C 00015

32

UDG100H 3PG4S0000C 00015

32

20A

UDG100H 2PG4S0000C 00020

32

UDG100H 3PG4S0000C 00020

32

30A

UDG100H 2PG4S0000C 00030

32

UDG100H 3PG4S0000C 00030

32

40A

UDG100H 2PG4S0000C 00040

32

UDG100H 3PG4S0000C 00040

32

50A

UDG100H 2PG4S0000C 00050

32

UDG100H 3PG4S0000C 00050

32

60A

UDG100H 2PG4S0000C 00060

32

UDG100H 3PG4S0000C 00060

32

75A

UDG100H 2PG4S0000C 00075

32

UDG100H 3PG4S0000C 00075

32

100A

UDG100H 2PG4S0000C 00100

32

UDG100H 3PG4S0000C 00100

32

UDG100S
5kA

UDG100H
10kA

Category

ELCB
/M6

100mA
Model /
Breaking capacity at
AC220/240V

Rated
current

2 pole
Code

3 pole
Unit
(EA)

Code

Unit
(EA)

15A

UDG100S 2PG5S0000C 00015

32

UDG100S 3PG5S0000C 00015

32

20A

UDG100S 2PG5S0000C 00020

32

UDG100S 3PG5S0000C 00020

32

Specification

30A

UDG100S 2PG5S0000C 00030

32

UDG100S 3PG5S0000C 00030

32

UDG100S

40A

UDG100S 2PG5S0000C 00040

32

UDG100S 3PG5S0000C 00040

32

5kA

50A

UDG100S 2PG5S0000C 00050

32

UDG100S 3PG5S0000C 00050

32

60A

UDG100S 2PG5S0000C 00060

32

UDG100S 3PG5S0000C 00060

32

100mA, 40/45 ,

75A

UDG100S 2PG5S0000C 00075

32

UDG100S 3PG5S0000C 00075

32

100A

UDG100S 2PG5S0000C 00100

32

UDG100S 3PG5S0000C 00100

32

15A

UDG100H 2PG5S0000C 00015

32

UDG100H 3PG5S0000C 00015

32

20A

UDG100H 2PG5S0000C 00020

32

UDG100H 3PG5S0000C 00020

32

Screw type
terminal
connection,
No option,
50/60Hz

30A

UDG100H 2PG5S0000C 00030

32

UDG100H 3PG5S0000C 00030

32

40A

UDG100H 2PG5S0000C 00040

32

UDG100H 3PG5S0000C 00040

32

50A

UDG100H 2PG5S0000C 00050

32

UDG100H 3PG5S0000C 00050

32

60A

UDG100H 2PG5S0000C 00060

32

UDG100H 3PG5S0000C 00060

32

75A

UDG100H 2PG5S0000C 00075

32

UDG100H 3PG5S0000C 00075

32

100A

UDG100H 2PG5S0000C 00100

32

UDG100H 3PG5S0000C 00100

32

UDG100H
10kA

Category

ELCB
/M6

Molded Case Circuit Breaker_ 135

Characteristic Curves & Dimensions

U-Series

Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| UAB type / 30-100AF, 5-10kA |
Tripping & temperature derating curves
3-100A

Max. (3-30A)

UAB50C

UAB50R

UAB60C

UAB60R

36
60
120
180
240
360
480
600
720
900
1200

12
20
40
60
80
120
160
200
240
300
400

Min. (3-30A)
Second

UAB30R

Tripping time

Max. (40-100A)

UAB30C

Inst. trip
current (A)

3
5
10
15
20
30
40
50
60
75
100

Derating rate for tripping time (%)

Minute

Rated
current (A)

Min. (40-100A)

Ambient temperature (C)

UAB100C

UAD50C
Characteristic curves are
not applicable.

Percentage for rated current (%)

Current

Dimensions

: Center line

: Handle center line

(Unit: mm)

The allowance of 1.5mm is given around the handle frame.

Direct mounting
2P

Mounting hole

Mounting hole

3P

M5 screw (3-50A)
M8 screw (60-100A)

4P

Mounting hole

[Connection conductor]

24

7 (Max.)

5.5 (3~50A)
9 (60~100A)

Trip
button

50

130

82

C3.5
M4 0.7
mounting
screw

Trip
button

25

50

37.5

12.5

25

75

15

25

25

100

50

50

[Terminal part]

24

17

10

60
82

[Drilling holes for mounting]


2P

3P

4P

4P
3P
2P

[Panel cut-out]
2P

3P

4P

R5

12.5

25

M4 0.7
tapped hole

25

25
for handle exposure
(total breaker height: 64mm)

138

(Max.)

7.57.5

Trip
button

115

16

30.5

48

12.5

71

35.5

for handle and trip button exposure


(total breaker height: 60mm)

96

MCCB

Dimensions

: Center line

: Handle center line

(Unit: mm)

The allowance of 1.5mm is given around the handle frame.

Plug-in mounting
[Plug-in connection part]

[Mounting base]
41

80

M4 nut+S/W+P/W

50
20

18.5

RH screw
M4 L18+S/W+P/W

25

162

28

115

130

87

180

10.2

28

M4 nut+S/W+P/W

M6 nut+S/W+P/W

18.5

2
23.5
80

22

102

[Panel cut-out]

[Drilling holes for mounting]

[Connection conductor]

83
25

34

4- 6 hole

180

55

6.5

34

19.5

81

21(Max.)

10(Max.)

25

Cut-out before bus bar assembly.

Cut-out for wiring of signal accessories.

TDF 10A for line side only type plug-in mounting, please refer to page 212.

Installation of signal accessories

No.
of
Auxiliary
poles switch

Trip alarm
switch

Shunt
trip

Under
voltage trip

3
Right

Left

Handle

- AXT is combintaion of AUX and ALT.


- In case of 2P, all signal accessories shall be installed in left side of breaker.
- UVT operates at DC voltage. AC voltage will be converted to DC through UVT controller.

[ Front ]

Molded Case Circuit Breaker_ 139

U-Series

Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| UAB type / 50-100AF, 25-30kA |
Tripping & temperature derating curves









15-32A
Rated
current (A)

Minute

Inst. trip
current (A)

15
16
20
25
30
32








300
320
400
500
600
640

60
72
80
100
120
128

Tripping time







Second

UAB50S
UAB50H

Derating rate for rated current (%)

Max.




UAB100R

Min.















UAB100S











Ambient temperature (C)







UAD50S



UAD100R

   

     

     

Percentage for rated current (%)

Current

Characteristic curves are


not applicable.








40-100A

Minute



40
50
60
63
75
80
100








Inst. trip
current (A)

400
500
600
630
750
800
1000

80
100
120
126
150
160
200

Max.

Tripping time







Second




Min.





Derating rate for rated current (%)

Rated
current (A)









   

     

     

Percentage for rated current (%)

Current

Installation of signal accessories

No.
of
Auxiliary
poles switch

Trip alarm
switch

Shunt
trip

Under
voltage trip

3
Right

Left

Handle

[ Front ]

140

















Ambient temperature (C)







- AXT is combintaion of AUX and ALT.


- In case of 2P, all signal accessories shall be installed in left side of breaker.
- UVT operates at DC voltage. AC voltage will be converted to DC through UVT controller.

MCCB

Dimensions

: Center line

: Handle center line

(Unit: mm)

The allowance of 1.5mm is given around the handle frame.

Direct mounting
2P
Mounting hole

3P

4P

Mounting hole

M5 screw (15-50A)
M8 screw (60-100A)

Mounting hole

[Connection conductor]

24

7 (Max.)

5.5 (15~30A)
9 (60~100A)

C3.5

83.5

20.5

50
115
130

8.6

22
Trip
button

Trip
button

[Terminal part]
7.2

Trip
button

15 (Max.)

M4 0.7
mounting
screw

50
75

25

25
100

10

50
56
60

25
4.6

50

25
37.5

24

16.4

8
82

[Drilling holes for mounting]


4P

2P

3P

4P

53

3P

110

2P

[Panel cut-out]

4P
3P
2P

12.5

M4 0.7
tapped hole

25

25

25

48

for handle exposure


(total breaker height: 64mm)

12.5

35.5

71

96

for handle and trip button exposure


(total breaker height: 60mm)

Plug-in mounting
41
RH screw
M4 L18+S/W+P/W
56.100

[Mounting base]
80
50
25

23.5

80
101

[Panel cut-out]
83
25

115
162

10.2

87

[Drilling holes for mounting]


22

25

[Connection conductor]

34

Cut-out before bus bar assembly.

Cut-out for wiring of signal accessories.

55

21(Max.)
180

19.5

34

81

4- 6 hole
6.5

10(Max.)

M6 nut+S/W+P/W
2

18.5

28

130

180

28

M4 nut+S/W+P/W

M4 nut+S/W+P/W

20

18.5

[Plug-in connection part]

TDF 10A for line side only type plug-in mounting, please refer to page 212.

Molded Case Circuit Breaker_ 141

U-Series

Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| UCB type / 50-100AF, 25-36kA |
Tripping & temperature derating curves

Minute

15
16
20
25
30
32
40
50
60
63
75
80
100

Max. (60-100A)

Tripping time

Max. (40, 50A)

UCB50R

Min. (40-100A)

Inst. trip
current (A)

150
160
200
250
300
320
400
500
600
630
750
800
1000

30
32
40
50
60
64
80
100
120
126
150
160
200

Derating rate for rated current (%)

Hour

15-100A
Rated
current (A)

Max. (15-30A)

Min. (15-30A)
Second

UCB100R

15-30A
40-100A

UCB100S

Ambient temperature (C)

UCD100S
Characteristic curves
are not applicable.
Percentage for rated current (%)

Current

Dimensions

: Center line

: Handle center line

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

Direct mounting
4P

Mounting hole

Mounting hole

M8 screw

[Connection conductor]

24

8.5 (Max.)

3P

2P
Mounting hole

Trip
button

Trip
button

101.5
50

17 (Max.)
M4 0.7
mounting
screw

37

[Terminal part]
7.3

Trip
button

155

16

134

9 Hole

60

60

90

30

30

30

15 22
10

45
120

30

[Panel cut-out]
4P
3P
2P

4P

2P

3P

4P

53

15

24
Inhex bolt M8 L25

132

3P

6.5
17.4

84.5

[Drilling holes for mounting]


2P

60

10.5

30

M4 0.7
30
tapped hole

59

30

88

44

26
for handle exposure
(total breaker height: 64mm)

142

15

for handle and trip button exposure


(total breaker height: 60mm)

118

MCCB

Dimensions

: Center line

: Handle center line

(Unit: mm)

The allowance of 1.5mm is given around the handle frame.

Plug-in mounting
[Plug-in connection part]

[Mounting base]

41
RH screw
M5 L20+S/W+P/W

94

M5 nut+S/W+P/W
21

M5 nut+S/W+P/W

60

134

46

27.5

M6 nut+S/W+P/W

172.5

13.5

48
191

155

99

27.5

30

23.5
81

105.5

[Panel cut-out]

26.5

[Drilling holes for mounting]

97
80
A

30
4- 5.5 hole

33.5

26 (Max.)

191

55

19.5

6.5

33.5

93

13(Max.)

[Connection conductor]

Cut-out before bus bar assembly.

Cut-out for wiring of signal accessories.

TDF 10B for line side only type plug-in mounting, please refer to page 212.

Installation of signal accessories


No.
of
Auxiliary
poles switch

Trip alarm
switch

Shunt
trip

Under
voltage trip

3
Right

Left

Handle

- AXT is combintaion of AUX and ALT.


- In case of 2P, all signal accessories shall be installed in left side of breaker. SHT and UVT are not applicable to 2P.
- UVT operates at DC voltage. AC voltage will be converted to DC through UVT controller.

[ Front ]

Molded Case Circuit Breaker_ 143

U-Series

Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| UCB type / 50-125AF, 42-50kA |
Tripping & temperature derating curves

Hour

15-32A

Rated
current (A)

15
16
20
25
30
32

Minute








Inst. trip
current (A)

225
240
300
375
450
480

45
48
60
75
90
96

Derating rate for rated current (%)




Tripping time




UCB50H




Second

UCB50L
UCB100H

Max.



UCB100L

Min.



16-30A

Ambient temperature (C)






UCD50H


 

UCD100H





  



 

 

Percentage for rated current (%)

Current

Characteristic curves are


not applicable.

40-125A




Rated
current (A)



40
50
60
63
75
80
100
125







Max. (60-125A)

Inst. trip
current (A)

400
500
600
630
750
800
1000
1250

80
100
120
126
150
160
200
250

Tripping time




Max. (40, 50A)




Min. (40-125A)

Second





Derating rate for rated current (%)

Minute

Hour

Ambient temperature (C)






 





  



 

 

Percentage for rated current (%)

Current

Installation of signal accessories

No.
of
Auxiliary
poles switch

Trip alarm
switch

Shunt
trip

Under
voltage trip

3
Right

Left

Handle

[ Front ]

144

40-125A

- AXT is combintaion of AUX and ALT.


- UVT operates at DC voltage. AC voltage will be converted to DC through UVT controller.

MCCB

Dimensions

: Center line

: Handle center line

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

Direct mounting
2P, 3P

4P
M8 screw

24

[Connection conductor]

17 (Max.)

90

30
120

[Terminal part]
10

30

48
55
10
60
84.5

18

[Drilling holes for mounting]


3P

[Panel cut-out]
4P
3P

3P

30

53

132

4P

30

24
Inhex bolt M8 L25

30

4P

53

30

8.5

30

53

30

8.5(Max.)

101

M4 L60
mounting
screw

37

10.5

Trip
button

Trip
button

155

16

50
134

9 hole

44

88

25

118

M4 tapped hole

for handle exposure


(total breaker height: 66mm)

Plug-in mounting

for handle and trip button exposure


(total breaker height: 60mm)

[Mounting base]

[Plug-in connection part]


41
21

RH screw
M5 L20+S/W+P/W

94
60
30

M5 nut+S/W+P/W

134
27.0
46

M6 nut+S/W+P/W
2
23.5

81

105.5

26.5

[Drilling holes for mounting]

97
80

30

[Connection conductor]

A
4- 5.5 hole

26 (Max.)

191

55

19.5

6.5

33.5

93

33.5

13 (Max.)

[Panel cut-out]

172.5

99

155

191

13.5

46

27.5

M5 nut+S/W+P/W

Cut-out before bus bar assembly.

Cut-out for wiring of signal accessories.

TDF 10B for line side only type plug-in mounting, please refer to page 212.

Molded Case Circuit Breaker_ 145

U-Series

Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| UCB type / 250AF, 18-36kA |
Tripping & temperature derating curves
Hour

125-250A
Rated
current (A)

250
300
320
350
400
450
500

Derating rate for rated current (%)

Minute

1250
1500
1600
1750
2000
2250
2500

Max.

Tripping time

UCB250R

Inst. trip
current (A)

125
150
160
175
200
225
250

Min.

Second

UCB250S
UCB250N

Ambient temperature (C)

UCD250S
Characteristic curves
are not applicable.

Percentage for rated current (%)

Current

Dimensions

: Center line

: Handle center line

97
23

Direct mounting
Mounting hole

3P

4P

Mounting hole

(Unit: mm)

The allowance of 1.5mm is given around the handle frame.

23

[with terminal
bus bar*option]

M8 screw
23
35

24

[Terminal part]

Trip
button

11
M4 0.7
mounting
screw

[Connection conductor]
11 (Max.)

35

12

35

55
11
60
84

11

[Drilling holes for mounting]

M4 0.7
tapped hole

35

35

35

23 (Max.)

[Panel cut-out]
4P
3P

4P

3P

4P

53

125

3P

23
35

28
53

35
140

24
Inhex bolt
M8 L25

10.5

24

105

26

103

51.5
138

for handle exposure


(total breaker height: 64mm)

146

4
35
52.5

70

25
49.5

23

11.5

Trip
button

14.5

35.5

23.5 26.5
143
164

44.5

51.5

11

for handle and trip button exposure


(total breaker height: 60mm)

MCCB

Dimensions

: Center line

: Handle center line

Plug-in mounting

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

[Mounting base]

M5 nut+S/W+P/W

21

42

19.5

74

24

M5 screw+S/W+P/W

12.5

25.5
70

185

143

28.5
112

[Plug-in connection part]


M8 nut+S/W+P/W

57.5

77.5

24.7

25.5

28

Max. width of conductor : 25mm

[Drilling holes for mounting]


Attaching angle
25 25 t3

45

6 hole for CBM 20C 2/5

25

19

53

24

13

12

15 0.0

6 hole

-0.2

70

Installation of signal accessories


No.
of
Auxiliary
poles switch

Trip alarm
switch

Shunt
trip

Under
voltage trip

3
Right

Left

- AXT is combintaion of AUX and ALT.


- UVT operates at DC voltage. AC voltage will be converted to DC through UVT controller.

Handle

[ Front ]

Molded Case Circuit Breaker_ 147

U-Series

Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| UCB type / 160-250AF, 42-50kA |
Tripping & temperature derating curves
Hour

100-250A

Rated
current (A)

100
125
150
160
175
200
225
250





1000
1250
1500
1600
1750
2000
2250
2500

200
250
300
320
350
400
450
500

Derating rate for rated current (%)

Minute






Inst. trip
current (A)

Tripping time

UCB160H

Max.





Min.




Second

UCB160L
UCB250H
UCB250L

Ambient temperature (C)







UCD160H



UCD250H



Characteristic curves
are not applicable.

 



   







 

Percentage for rated current (%)

Current
: Handle center line

Direct mounting

97
23

Mounting hole

Mounting hole
M8 screw

24
4

[Terminal part]

[with terminal
bus bar*option]

23

4P
23
35

3P

23

101

4 24
M4 L60
mounting
screw

[Connection conductor]

8
10

9
35

48
55
60
84.5

10
11

[Drilling holes for mounting]

35
M4 Tapped hole

35

25
for handle exposure
(total breaker height: 66mm)

148

35

22 (Max.)

4P

53

3P

53

125
35

35

[Panel cut-out]
4P
3P

4P

3P

23
35

11.5

35 35
140

53

35

11(Max.)

16

50
144
165

11

35 35
105

(Unit: mm)

The allowance of 1.5mm is given around the handle frame.

11

: Center line

51.5

138

for handle and trip button exposure


(total breaker height: 60mm)

10.5

Dimensions

24
Inhex bolt
M8 L25

MCCB

Dimensions

: Center line

: Handle center line

Plug-in mounting

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

M5 nut + S/W + P/W


M5 screw + S/W + P/W

[Plug-in connection part]

[Mounting base]

42

186

144

12.5

19.5

74

24

M8 nut + S/W + P/W

Max. width of conductor : 25mm


28

25.5

25.5

28.5
70
112

24.7

77.5

57.5

[Drilling holes for mounting]

Attaching angle
25 25 t3

45

6 hole for CBM 20C 2/5

25

19

53

24

13

12

15 0.0

6 hole

-0.2

70

Installation of signal accessories

No.
of
Auxiliary
poles switch

Trip alarm
switch

Shunt
trip

Under
voltage trip

3
Right

Left

- AXT is combintaion of AUX and ALT.


- UVT operates at DC voltage. AC voltage will be converted to DC through UVT controller.

Handle

[ Front ]

Molded Case Circuit Breaker_ 149

U-Series

Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| UCB type / 400AF, 30-100kA |
Tripping & temperature derating curves
Hour

250-400A
Rated
current (A)

2500
3000
3200
3500
4000

Max.

Min.

UCB400S
Second

UCB400H

500
600
640
700
800

Derating rate for rated current (%)

Minute

Tripping time

UCB400R

Inst. trip
current (A)

250
300
320
350
400

UCB400L

Ambient temperature (C)

UCD400S
Characteristic curves are
not applicable.
Percentage for rated current (%)

Current

Dimensions

: Center line

: Handle center line

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

Direct mounting
2P, 3P

4P

143
59

12.5

12.5

59

84
8
37
4
13.5

30 11

12.5

24.5

40

150
95

24.5

317
225
215
150
95

257

30 11

44

59

9.5

59

12.5

202
59
44

15
25

44

25

44

25

25

44

25

140

44
185

25

44

25

80

30.5
13
29

Inhex bolt M8 L30

[Connection conductor]
11

12.5(Max.)

[Terminal part]

30(Max.)

150

8
95
110
115.5
145

37

M6
mounting
screw

MCCB

Dimensions

: Center line

: Handle center line

The allowance of 1.5mm is given around the handle frame.

[Drilling holes for mounting]

(Unit: mm)

[Panel cut-out]

4P

95
112

44

98

215

98

2P, 3P

54

2P, 3P (143)
4P (188)

for handle exposure

for handle and trip button exposure

Plug-in mounting
[Mounting base]

[Drilling holes for mounting]

M8 mounting screw
Attaching angle

M5 screw

71.5

65.5

[Plug-in connection part]


22

113

44.5
21

139.5

112.5

45
15

90
140

65.5

44.5 21

20 15
89

Supportor pportor

54

112.5

139.5

60

6 for supportor

9
60

10

Max. with of conductor : 35mm


M10 screw
18 46.5

35

Installation of signal accessories


No.
of
Auxiliary
poles switch

Trip alarm
switch

Shunt
trip

Under
voltage trip

3
Right

Left

UVT operates at DC voltage. AC voltage will be converted to DC through UVT controller.

Handle

[ Front ]

Molded Case Circuit Breaker_ 151

U-Series

Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| UCB type / 630AF, 45-100kA |
Tripping & temperature derating curves

Inst. trip
current (A)

500
630

5000 1000
6300 1260

Minute

Hour

500-630A
Rated
current (A)

UCB630R
UCB630S

Min.

Second

UCB630H

Derating rate for rated current (%)

Tripping time

Max.

UCB630L

Ambient temperature (C)

UCD630S
Characteristic curves
are not applicable.
Percentage for rated current (%)

Current

Dimensions

: Center line

: Handle center line

(Unit: mm)

The allowance of 1.5mm is given around the handle frame.

Direct mounting
2P, 3P

4P
84
280
70

210
70

70

70

8 34.5

70

74.5

9.5

280

24.5

74.5

150
95

24.5
280

243
150
95

13.5

70

70

32 16.5

58

70

70

M6
mounting
screw

40
70

40
70

Inhex bolt M12xL30

13

12.5

31

46

[Connection conductor]
12.5(Max.)

[Terminal part]

152

45

(Max.)

80

4
8 34.5 15
95
110
115.5
145

MCCB

Dimensions

: Center line

: Handle center line

(Unit: mm)

The allowance of 1.5mm is given around the handle frame.

[Drilling holes for mounting]

[Panel cut-out]

4P

95
112

70

98

243

98

2P, 3P

2P, 3P (213)

61

4P (283)
for handle exposure

for handle and trip button exposure

Plug-in mounting
[Mounting base]

[Drilling holes for mounting]

M10 mounting screw


90

Supportor

45
15

25 46.5
71.5

151.5

121.5

140
210

46.5 25
71.5

30 32 18 20
100

151.5

121.5

Attaching angle

[Plug-in connection part]

M5 screw
21 20

6 for supportor
90
116.2

59

11

45
Max. with of conductor : 40mm
M16 screw
44

60

Installation of signal accessories


No.
of
Auxiliary
poles switch

Trip alarm
switch

Shunt
trip

Under
voltage trip

3
Right

Left

UVT operates at DC voltage. AC voltage will be converted to DC through UVT controller.

Handle

[ Front ]

Molded Case Circuit Breaker_ 153

U-Series

Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| UCB type / 800AF, 45-100kA |
Tripping & temperature derating curves

Inst. trip
current (A)

700
800

7000 1400
8000 1600

Minute

Hour

700-800A
Rated
current (A)

UCB800R
UCB800S

Min.

Second

UCB800H

Derating rate for rated current (%)

Tripping time

Max.

UCB800L

Ambient temperature (C)

UCD800S
Characteristic curves
are not applicable.
Percentage for rated current (%)

Current

Dimensions

: Center line

: Handle center line

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

Direct mounting
2P, 3P

4P

210

280
70

70

70

70

84
10 34.5

70

74.5

9.5

280

150
95

24.5
280

243
150
95

13.5

70

70

32 16.5

74.5

58

70

70

M6
mounting
screw

40
70

40
70

80

Inhex bolt M12xL30

12.5

31

46

154

[Connection conductor]
13

12.5 (Max.)

[Terminal part]

45 (Max.)

4
10 34.5 15
95
110
115.5
145

MCCB

Dimensions

: Center line

: Handle center line

(Unit: mm)

The allowance of 1.5mm is given around the handle frame.

[Drilling holes for mounting]

[Panel cut-out]

4P

95
112

70

98

243

98

2P, 3P

61

2P, 3P (213)
4P (283)

for handle exposure

for handle and trip button exposure

Plug-in mounting
[Mounting base]

[Drilling holes for mounting]

M10 mounting screw


90

Supportor

45
15

25 46.5
71.5

121.5

151.5

140
210

46.5 25
71.5

30 32 18 20
100

121.5

151.5

Attaching angle

[Plug-in connection part]

M5 screw
21 20

6 for supportor
90
116.2

59

11

45
Max. with of conductor : 40mm

44

M16 screw
60

Installation of signal accessories


No.
of
Auxiliary
poles switch

Trip alarm
switch

Shunt
trip

Under
voltage trip

3
Right

Left

UVT operates at DC voltage. AC voltage will be converted to DC through UVT controller.

Handle

[ Front ]

Molded Case Circuit Breaker_ 155

U-Series

Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| UCB type / 1000AF, 100-130kA |
Tripping curves

Protection characteristics

Hour

4
3

505-1000A

Ir

Ig

Characteristics

Ip

1
50
40
30

Minute

20

8
6
5
4
3

505, 535, 565, 600, 630, 640,


680, 720, 760, 800, 850, 900,
950, 1000
Long time setting [tr] 2-4-6-8-12 sec. at Ir x 600%
Short time current
Ir x NON-200-400-600-8001000%
STD1) setting [Isd] (A)
Time delay setting
0-0.1-0.2-0.3 sec. at definite
[tsd]1)
time-limit section
Instantaneous
In x NON-300-600-800INST current setting
1000-1100%
[Ii] (A)
Ground fault
In x NON-20-30-40%
GFT2) current [Ig] (A)
Ground fault delay
0.1-0.2-0.3-0.4-0.8 sec. at
setting [tg]
definite time-limit section
Pre-trip alarm
Ir x 90%
PTA
current [Ip] (A)

Ii

1
50
40
30

Tripping time

UCB1000L

20
12
10

8
6
5
4
3

Second

for I2t "ON"

1
0.8
0.6
0.5
0.4
0.3
0.2

UCD1000S
Characteristics are
not applicable.

for I2t "OFF"

0.1
0.08
0.06
0.05
0.04
0.03

3000

2000

2500

500
600
700
800
900
1000
1100
1200
1300
1500

400

200

250

300

125

150

50
80
90
100

40

30

10
20

In %

20%
15%
50ms
20ms
20%
15%
50ms
20ms
10%

-The default values are underlined. Please check and adjust the
setting condition of each characteristic before use.
-1) I2t characteristic can be ON or OFF by adjusting the [tsd] knob.
-2) GFT protection is option.

0.02

0.01
0.008
0.006
0.005

Tolerance

Rated current
LTD setting [Ir] (A)

Isd

10

UCB1000S

Setting value or range

Rated (CT) current [In] (A) 1000

Ir %

Current

Dimensions

: Center line

Direct mounting

: Handle center line

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

UCB1000S
Mounting hole

4P

M8 mounting screw

73

3P

14

[Connection conductor]

310

516

370

30

16 36 21
73

[Terminal part]

70

14 25
110
115
159

45

45
70

70

210

70
280

5
7

70
80

[Drilling holes for mounting]


4P
3P

[Panel cut-out]
4P
3P

99

61.5

338

78.5

44

M8 tapped hole

156

70

Inhex bolt M10 L30

8 for trip button

37.5

13

MCCB

Dimensions

: Center line

Direct mounting

: Handle center line

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

UCB1000L

Mounting hole
M8 screw

4P
73

3P

120

14

45

70

70

210

14
5

70

280

7
80

16

45

70

115
200

14

45
70

[Terminal part]

25
54

205

25
115

249

Inhex bolt M10 L30

[Drilling holes for mounting]

[Panel cut-out]

4P

4P

3P

3P

99

61.5

338

78.5

37.5

13

73

16 36 21

36 20

310

516

370

[Connection conductor]

44

M8 tapped hole

70

8 for trip button

Installation of signal accessories


No.
of
Auxiliary
poles switch

Trip alarm
switch

Shunt
trip

Under
voltage trip

Left

Right

AXT is combintaion of AUX and ALT.

Handle

[ Front ]

Molded Case Circuit Breaker_ 157

U-Series

Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| UCB type / 1250AF, 100-130kA |
Tripping curves

Protection characteristics

Hour

4
3

630-1250A

Ir

Ig

Characteristics

Ip

1
50
40
30

630, 670, 710, 750, 790, 800,


850, 900, 950, 1000, 1060,
1125, 1190, 1250
Long time setting [tr] 2-4-6-8-12 sec. at Ir x 600%
Short time current
Ir x NON-200-400-600-8001000%
STD1) setting [Isd] (A)
Time delay setting
0-0.1-0.2-0.3 sec. at definite
[tsd]1)
time-limit section
Instantaneous
In x NON-300-600-800INST current setting
1000-1100%
[Ii] (A)
Ground fault
In x NON-20-30-40%
GFT2) current [Ig] (A)
Ground fault delay
0.1-0.2-0.3-0.4-0.8 sec. at
setting [tg]
definite time-limit section
Pre-trip alarm
Ir x 90%
PTA
current [Ip] (A)

Minute

20

8
6
5
4
3

Ii

1
50
40
30

Tripping time

UCB1250L

20
12
10

8
6
5
4
3

Second

UCD1250S
Characteristics are
not applicable.

for I2t "ON"

1
0.8
0.6
0.5
0.4
0.3
0.2

for I2t "OFF"

0.1
0.08
0.06
0.05
0.04
0.03

3000

2000

2500

500
600
700
800
900
1000
1100
1200
1300
1500

400

200

250

300

125

150

50
80
90
100

40

30

10
20

In %

20%
15%
50ms
20ms
20%
15%
50ms
20ms
10%

-The default values are underlined. Please check and adjust the
setting condition of each characteristic before use.
-1) I2t characteristic can be ON or OFF by adjusting the [tsd] knob.
-2) GFT protection is option.

0.02

0.01
0.008
0.006
0.005

Tolerance

Rated current
LTD setting [Ir] (A)

Isd

10

UCB1250S

Setting value or range

Rated (CT) current [In] (A) 1250

Ir %

Current

Dimensions

: Center line

Direct mounting

: Handle center line

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

UCB1250S
Mounting hole

4P
M8 mounting screw

73

3P

30

14

[Connection conductor]

45
70

70

36 20
16
17 25
110
115
159

45
70

210

70
280

5
7

70
80

[Drilling holes for mounting]

[Panel cut-out]

4P
3P

4P
3P

99

61.5

338

78.5

44

M8 tapped hole

158

70

25
54

8 for trip button

37.5

13

14

516

310

[Terminal part]

16 36 21
73

370

45

25
Inhex bolt M10 L30

MCCB

Dimensions

: Center line

Direct mounting

: Handle center line

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

UCB1250L

Mounting hole
M8 mounting screw

4P
73

3P

120

14

[Connection conductor]

36 20

310

516

370

45

16

45

70

70

210

70

17

70

280
80

115

200

205

14

45
70

25
54

25

115
Inhex bolt M10 L30

249

[Drilling holes for mounting]

[Panel cut-out]

4P

4P
3P

3P

99

61.5

338

78.5

37.5

13

73

16 36 21

[Terminal part]

44

M8 tapped hole

70

8 for trip button

Installation of signal accessories


No.
of
Auxiliary
poles switch

Trip alarm
switch

Shunt
trip

Under
voltage trip

Left

Right

AXT is combintaion of AUX and ALT.

Handle

[ Front ]

Molded Case Circuit Breaker_ 159

U-Series

Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| UCB type / 1600AF, 65kA |
Tripping curves

Protection characteristics
640-1600A

Setting value or range

Characteristics

UCB1600S

Tolerance

Rated (CT) current [In] (A) 1600


LTD

Second

Tripping time

I2

Rated current
setting [I1] (A)

640, 800, 960, 1120, 1250,


1440, 1520, 1600

Instantaneous
INST current setting
[I2] (A)

I1 x 200-300-400-500-600700-800-1000%

10%

-The default values are underlined. Please check and adjust the
setting condition of each characteristic before use.
20%

100

200

300 400 500 600 800 1000

2000

3000

Percentage for rated current (%)

Current

Dimensions

: Center line

: Handle center line

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

Direct mounting

13

[with terminal cover and extension handle]

[Drilling holes for mounting]

338

394

110

477

371

570

152

11

51

100
32

15

22

Trip
button

70

151
170
215

[Terminal cover]

[Extension handle]

210

151

297

210

50

109

40

e
R25

36

45 25

60
70

160

70

U-Series

Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| UPB type / 125-250AF, 85-150kA / Adjustable thermal |
Tripping & temperature derating curves

Tripping time








Max.































Ambient temperature (C)















Max.







































Percentage for rated current (%)

Current










































375
250
450
300
480
320
525
350
600
400
675
450
750
500













Current

Min.



Min.

Inst. trip
current (A)

1250
1500
1600
1750
2000
2250
2500









Second

Second
















125
150
160
175
200
225
250









Percentage for rated current (%)

Derating rate for rated current (%)

126
160
200
250









Rated
current (A)






Tripping time

Tripping time








125-250A




Minute



630
800
1000
1250






63
80
100
125

Inst. trip
current (A)











Hour

Rated
current (A)

Minute

Hour

63-125A



Current













Percentage for rated current (%)

Current

Characteristic curves
are not applicable.









Second








Percentage for rated current (%)

UPD250S

162





UPD160S







Max.

Min.












UPD100S
















UPB250X



UPB250L



UPB250H



UPB250S









Max.

Min.














UPB160X



UPB160L



UPB160H




UPB160S
















400 80
500 100










UPB100X

Inst. trip
current (A)

40
50














UPB100L

Tripping time

UPB100H

30
32
40
50
60
64









Second

UPB100S








Rated
current (A)








Minute



150
160
200
250
300
320

40-50A




15
16
20
25
30
32











Inst. trip
current (A)






Rated
current (A)

Hour

15-30A

Minute

Hour




MCCB

Dimensions

: Center line

: Handle center line

(Unit: mm)

The allowance of 1.5mm is given around the handle frame.

Direct mounting
4P
140
35

35

35

112

20 11

23

[Drilling holes for mounting]


4P
3P

4P
3P

27.5

144
165

144

*A

144
165

146

[Panel cut-out]

75.5

3P
105
35

11 19

45

11 20

11

R5

M4 0.7
tapped hole

45

35

90
113

[Connection conductor]

[Terminal part]

35
128

71
86.5

35

30

[with terminal bus bar*option]


Dimension A

8.5 9.5
9.5

9
(Max.)9

35

M4 tap O.7

23

23 (Max.)

24

10

Line side : 24mm for UPB100


26mm for UPB160, UPB250
Load side : 24mm

24
t4
A

Plug-in mounting
[Mounting base]
41
24 5

[Drilling holes for mounting]

[Plug-in connection part]

109
35

4- 6 mounting hole

26.5

15

23

[Panel cut-out]

96

4-M5 tap

4- 6 tap

37

30

15

31
92.5
110

35
70
105

190
179

113
144
175
190

35
107

30

31

M8 bolt

70

M8 mounting screw

22.5
26

Installation of signal accessories


No.
of
Auxiliary
poles switch

Trip alarm
switch

Shunt
trip

Under
voltage trip

Left

Right

Handle

[ Front ]

Molded Case Circuit Breaker_ 163

U-Series

Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| UPB type / 125-250AF, 85-150kA / Electronic |
Tripping curves

Hour

4
3
2

50-250A

1
50
40
30

Ir = 125, 160, 250

Minute

20
10
8
6
5
4
3
2

UPB100L

UPB100X

UPB160S

UPB160H

UPB160L

UPB160X

UPB250S

UPB250H

UPB250L

UPB250X

20

Tripping time

UPB100H

10
8
6
5
4
3
2

Isd = 2..... 10 x Ir
1
0.8
0.6
0.5
0.4
0.3
0.2

Second

UPB100S

1
50
40
30

0.1
0.8
0.6
0.5
0.4
0.3
0.2

Max. total breaking time


t < 10ms

Ii = 11 x In

0.01
0.8
0.6
0.5
50

70

100

150

200

300

400 500

700

1000

1500

2000

3000 4000 5000 7000 8000 10000 15000 20000

Ir %

Current

Protection characteristics

Setting value or range


Characteristics
Rated (CT) current [In] (A)

LTD

STD

PTA

UPB160

UPB250

125

160

250

Rated current setting [Ir] (A)

50, 55, 63, 70, 63, 70, 80, 90, 100, 110, 125,
80, 90, 100,
100, 110, 125, 140, 160, 175,
115, 125
140, 160
200, 225, 250

Long time setting [tr]

6.25 sec. at Ir x 600%

Short time current setting

Ir x NON-200-300-400-500-600-700-800-900-

[Isd] (A)
Time delay setting [tsd]

INST

UPB100

Instantaneous current

20%

1000%
0.05-0.1-0.2-0.3 sec. at definite time-limit

50ms

section

20ms

In x 1100%

20%

Ir x 90%

10%

setting [Ii] (A)


Pre-trip alarm current [Ip] (A)

Tolerance

-The default values are underlined. Please check and adjust the setting condition of each characteristic before use.

164

30000

MCCB

Dimensions

: Center line

: Handle center line

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

Direct mounting
4P
140
35

35

35

112

20 11

23

[Drilling holes for mounting]


4P
3P

4P
3P

27.5

144
165

144

*A

144
165

146

[Panel cut-out]

75.5

3P
105
35

11 19

45

11 20

11

R5

M4 0.7
tapped hole

45

35

90
113

[Connection conductor]

[Terminal part]

35
128

71
86.5

35

30

[with terminal bus bar*option]


Dimension A

8.5 9.5
9.5

9
(Max.)9

35

M4 tap O.7

23

23 (Max.)

24

10

Line side : 24mm for UPB100


26mm for UPB160, UPB250
Load side : 24mm

24
t4
A

Plug-in mounting
[Mounting base]
41
24 5

[Drilling holes for mounting]

[Plug-in connection part]

109
35

4- 6 mounting hole

26.5

15

23

[Panel cut-out]

96

4-M5 tap

31

4- 6 tap

37

30

15

92.5
110

35
70
105

190
179

113
144
175
190

35
107

30

31

M8 bolt

70

M8 mounting screw

22.5
26

Installation of signal accessories


No.
of
Auxiliary
poles switch

Trip alarm
switch

Shunt
trip

Under
voltage trip

Left

Right

Handle

[ Front ]

Molded Case Circuit Breaker_ 165

U-Series

/ Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| UPB type / 400-630AF, 85-150kA |
Tripping curves

Protection characteristics

Hour

4
3

200-630A

Ir

Ig

Setting value or range

Characteristics

1
50
40
30

UPB630
630

200, 215, 225,


240, 250, 255,
270, 290, 300,
320, 340, 360,
380, 400

320, 340, 360,


380, 400, 430,
450, 480, 500,
540, 570, 600,
630

Rated (CT) current [In] (A)

20

Minute

UPB400
400

Ip

Isd

10

8
6
5
4
3

LTD

Rated current
setting [Ir] (A)

Ii

Tolerance

UPB400L

UPB400X

UPB630S

UPB630H

UPB630L

UPB630X

Tripping time

UPB400H

Long time setting [tr]


Short time current
setting [Isd] (A)
1)
STD Time delay setting
[tsd]1)
Instantaneous
INST current setting
[Ii] (A)
Ground fault
current [Ig] (A)
GFT2)
Ground fault delay
setting [tg]
Pre-trip alarm
PTA
current [Ip] (A)

20
12
10

8
6
5
4
3
2

Second

UPB400S

50
40
30

for I2t "ON"

1
0.8
0.6
0.5
0.4
0.3
0.2

for I t "OFF"

0.1
0.08
0.06
0.05
0.04
0.03

Ir %

Current

Dimensions

: Center line

Direct mounting

: Handle center line

50ms
20ms

In x NON-300-600-8001000-1100%

20%

In x NON-20-30-40%

15%

0.1-0.2-0.3-0.4-0.8 sec. at
definite time-limit section

50ms
20ms

Ir x 90%

10%

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

15

12.5

39.5

16
47

M10 screw

201

161.5

112.5
142.5

255

98.5
128.5

16

16 16
47

[with terminal bus bar*option]

185
27.5
24

27.5
12.5 15
24

15

140

3P

16

52.5

13
60

150

[Drilling holes for mounting]

60
210

30

M5 mounting screw

15

60

16
47

16
47
60

15

30

13

15

16

81

10

60

119.5
159.5

[Panel cut-out]

4P

4P

3P

3P
[Connection conductor]

63

30

(Max.)

14 16

15 (Max.)

113
45

[Terminal part]

10.5

100
130

166

15%

UPB400, UPD400S
4P

M5 tapped hole

20%

-The default values are underlined. Please check and adjust the
setting condition of each characteristic before use.
-1) I2t characteristic can be ON or OFF by adjusting the [tsd] knob.
-2) GFT protection is option.

3000

2000

2500

500
600
700
800
900
1000
1100
1200
1300
1500

400

250

In %

300

125

150

200

50
80
90
100

Characteristics are
not applicable.

40

0.01
0.008
0.006
0.005

30

0.02

UPD630S

10
20

UPD400S

2-4-6-8-12 sec. at Ir x 600%


Ir x NON-200-400-600-8001000%
0-0.1-0.2-0.3 sec. at definite
time-limit section

34

33.5
Inhex bolt M10 L30

MCCB

Dimensions

: Center line

Direct mounting

: Handle center line

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

UPB630, UPD630S
[with terminal bus bar*option]

85.5

55
102.5

112.5
255
142.5

16
98.5
128.5

41.5

M10 screw

115.5

12.5
24

185
27.5

24

16 16 15
47

3P

27.5
12.5 15

16 15
47

4P
140

30

16
13
60

150

52.5
60

30

M5 mounting screw

15

60

15

16
47

16 16
47
60

15

13

81

10

119.5
159.5

60

210

[Drilling holes for mounting]


3P

[Panel cut-out]

4P

3P

4P
[Connection conductor]

[Terminal part]
14 16

113
41.5

130

M5 tapped hole 45

15 (Max.)

100

10.5

33.5
Inhex bolt M10 L30

34

30 (Max.)

63

Plug-in mounting
[Mounting base]

[Panel cut-out]
144
45

22.5

130
57.7
33.5 5

[Drilling holes for mounting]

27

155

M10
mounting screw

119.5
124.5
164.5

45
90
140

39 52.5

22.5

11.5

18.5

188
227
270
298

298
274

4-M5 tap

37.5 30 37.5
180

[Plug-in connection part]

90

27

Installation of signal accessories


No.
of
Auxiliary
poles switch

Trip alarm
switch

Shunt
trip

Under
voltage trip

Left

Right

Handle

[ Front ]

Molded Case Circuit Breaker_ 167

U-Series

/ Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| Motor protection / UPB type 125-250AF, 100-130kA |
Tripping curves

125A










Minute













Max.

Percentage for rated current (%)

Current

Instantaneous trip current


UPB100
Rated
current
(A)

10

11

12

13

2.5

15

17.5

20

22.5

25

27.5

30

32.5

3.2

19.2

22.4

25.6

28.8

32

35.2

38.4

41.6

6.3

37.8

44.1

50.4

56.7

63

69.3

75.6

81.9

12.5

75

87.5

100

112.5

125

137.5

150

162.5

20

120

140

160

180

200

220

240

260

32

192

224

256

288

320

352

384

416

50

300

350

400

450

500

550

600

650

63

378

441

504

567

630

693

756

819

80

480

560

640

720

800

880

960

1040

100

600

700

800

900

1000

1100

1200

1300

Multiple for rated current

Tolerance for setting current: -20% - +30%

UPB250
Rated
current
(A)

10

125

625

750

875

1000

1125

1250

150

750

900

1050

1200

1350

1500

175

875

1050

1225

1400

1575

1750

200

1000

1200

1400

1600

1800

2000

225

1125

1350

1575

1800

2025

2250

Multiple for rated current

Tolerance for setting current: -20% - +30%











Percentage for rated current (%)

Current

168























































Max.







Min.

Second





Min.

Instantaneous trip
current (500-1000%)




Tripping time

Tripping time



UPB250L



UPB250H



Second

UPB100L

Instantaneous trip
current (600-1300%)






Minute






UPB100H

250A

Hour

Hour

MCCB

Dimensions

: Center line

: Handle center line

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

Direct mounting
4P
140
35

35

35

112

20 11

23

[Drilling holes for mounting]


4P
3P

4P
3P

27.5

144
165

144

*A

144
165

146

[Panel cut-out]

75.5

3P
105
35

11 19

45

11 20

11

R5

M4 0.7
tapped hole

45

35

90
113

[Connection conductor]

[Terminal part]

35
128

71
86.5

35

30

Dimension A

8.5 9.5
9.5

9
(Max.)9

35

M4 tap O.7

[with terminal bus bar*option]

23 (Max.)

24

10

23

Line side : 24mm for UPB100


26mm for UPB250
Load side : 24mm

24
t4
A

Plug-in mounting
[Mounting base]
41
24 5

[Drilling holes for mounting]

[Plug-in connection part]

109
35

4- 6 mounting hole

26.5

15

23

[Panel cut-out]

96

4-M5 tap

31

4- 6 tap

37

30

15

92.5
110

35
70
105

190
179

113
144
175
190

35
107

30

31

M8 bolt

70

M8 mounting screw

22.5
26

Installation of signal accessories


No.
of
Auxiliary
poles switch

Trip alarm
switch

Shunt
trip

Under
voltage trip

Left

Right

Handle

[ Front ]

Molded Case Circuit Breaker_ 169

U-Series

/ Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| Q-class (for nuclear power plant application) / HBL type 100AF, 85kA |

4
3

1
50
10
30

Rated
current (A)

Inst. trip
current (A)

15
20
30

150 30
200 40
300 60

10
8
6
5
4
3

2
1
0.8
0.6
0.5
0.4
0.3
0.2

Percentage for rated current (%)

Hour

4
3

Rated
current (A)

Inst. trip
current (A)

60
75
100

600 120
750 150
1000 200

Derating rate for rated current (%)

Minute

10
8
6
5
4
3
2

Tripping time

1
50
40
30
20
10
8
6
5
4
3

Second

2
1
0.8
0.6
0.5
0.4
0.3

Min.

0.1
0.08
0.06
0.05
0.04
0.03

Max.

Current

Installation of signal accessories

170

Under
voltage trip

5000

6000
7000
8000

4000

3000

2500

2000

1500

1200

700
800
900
1000

600

500

400

300

250

200

150

125

100
105

Percentage for rated current (%)

Handle

5000

4000

6000
7000
8000

3000

2500

2000

110
105
100
95
90
85
80
5

10

15

20

25

30

35

40

Ambient temperature (C)

0.02
0.01
0.008
0.006
0.005

[ Front ]

115

0.2

Right

1500

60-100A

20

Left

1200

Current

1
50
10
30

700
800
900
1000

Percentage for rated current (%)

Current

Shunt
trip

Max.

500

300

250

200

100
105

5000

4000

6000
7000
8000

3000

2500

2000

1500

1200

700
800
900
1000

500

400

600

300

250

200

150

0.02
0.01
0.008
0.006
0.005

125

0.02
0.01
0.008
0.006
0.005
100
105

Min.

0.1
0.08
0.06
0.05
0.04
0.03

400

Max.

150

Min.

600

0.2

Trip alarm
switch

400 80
500 100

10
8
6
5
4
3
2

10
8
6
5
4
3

Second

2
1
0.8
0.6
0.5
0.4
0.3

0.1
0.08
0.06
0.05
0.04
0.03

No.
of
Auxiliary
poles switch

Inst. trip
current (A)

40
50

1
50
40
30
20

Tripping time

Tripping time

HBL103UQ

Rated
current (A)

20

1
50
40
30
20

Second

HBL103U

40-50A

2
1
50
10
30

125

Minute

20
10
8
6
5
4
3
2

4
3

Hour

15-30A

Minute

Hour

Tripping & temperature derating curves

45

50

55

60

MCCB

Dimensions

: Center line

: Handle center line

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

Direct mounting

112
35

Terminal cover

[with terminal bus bar*option]


A

M8 bolt

Dimension A

144
165

146

Line side : 24mm


Load side : 24mm

t4

[Connection conductor]

[Terminal part]

23 (Max.)

10

86.5

Terminal cover

[Drilling holes for mounting]

[Panel cut-out]

3P

3P

24

9.5

8.5 9.5

0.7
tap
M4

71

70
105

9 (Max.)

24

27.5

144

75.5

3P

R5

35

M4 0.7
tapped hole

30

Molded Case Circuit Breaker_ 171

U-Series

/ Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| Q-class (for nuclear power plant application) / HBL type 100AF, 85kA / Motor protection |
Tripping curves
4

100A

Hour

2
1
30
20
14
10

Minute

6
4
2
1

Tripping time

30
20

HBL103UM

Instantaneous trip
current (600-1300%)

10
5

HBL103UMQ

Min.

Max.

Second

1
0.5
0.2
0.1
0.05
0.04
0.03
0.02

7000

5000

3000

2000

400

600
700
800
900
100
1100
1200
1300

300

200

125

100

0.01

Percentage for rated current (%)

Current

Instantaneous trip current

Rated
current
(A)

10

11

12

13

2.5

15

17.5

20

22.5

25

27.5

30

32.5

3.2

19.2

22.4

25.6

28.8

32

35.2

38.4

41.6

6.3

37.8

44.1

50.4

56.7

63

69.3

75.6

81.9

12.5

75

87.5

100

112.5

125

137.5

150

162.5

20

120

140

160

180

200

220

240

260

32

192

224

256

288

320

352

384

416

50

300

350

400

450

500

550

600

650

63

378

441

504

567

630

693

756

819

80

480

560

640

720

800

880

960

1040

100

600

700

800

900

1000

1100

1200

1300

Multiple for rated current

Tolerance for setting current: -20% - +30%

Installation of signal accessories


No.
of
Auxiliary
poles switch

Trip alarm
switch

Left

Right

Handle

[ Front ]

172

Shunt
trip

Under
voltage trip

MCCB

Dimensions

: Center line

: Handle center line

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

Direct mounting

112
35

Terminal cover

[with terminal bus bar*option]


A

M8 bolt

Dimension A

144
165

146

Line side : 24mm


Load side : 24mm

t4

[Connection conductor]

[Terminal part]

23 (Max.)

10

86.5

Terminal cover

[Drilling holes for mounting]

[Panel cut-out]

3P

3P

24

9.5

8.5 9.5

0.7
tap
M4

71

70
105

9 (Max.)

24

27.5

144

75.5

3P

R5

35

M4 0.7
tapped hole

30

Molded Case Circuit Breaker_ 173

U-Series

/ Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| Q-class (for nuclear power plant application) / HBL type 225AF, 85kA |

25

1250

150

1500

20

175

1750

200

2000

225

2250

+375
-250
+450
-300
+525
-350
+600
-400
+675
-450

5000

Inst. trip
current (A)

1
50
40
30

4000

Rated
current (A)

55

60

10
8
6
5
4
3
2

10
8
6
5
4
3
2

Second

HBL203UQ

125-225A

1
50
40
30
20

Tripping time

HBL203U

4
3

3000

Minute

Hour

Tripping & temperature derating curves

1
0.8
0.6
0.5
0.4
0.3

Min.

Max.

0.2
0.1
0.08
0.06
0.05
0.04
0.03

Percentage for rated current (%)

Derating rate for rated current (%)

Current

115
110
105
100
95
90
85
80
0

10

15

20

25

30

35

40

Ambient temperature (C)

Installation of signal accessories


No.
of
Auxiliary
poles switch

Trip alarm
switch

Left

Right

Handle

[ Front ]

174

Shunt
trip

Under
voltage trip

45

50

8000

7000

6000

2500

1500

1200

700
800
900
1000

500

600

400

300

250

200

150

125

100
105

0.01
0.008
0.006
0.005

2000

0.02

MCCB

Dimensions

: Center line

: Handle center line

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

Direct mounting

112
35

Terminal cover

[with terminal bus bar*option]


A

M8 bolt

Dimension A

144
165

146

Line side : 26mm


Load side : 24mm

t4

[Connection conductor]

[Terminal part]

23 (Max.)

10

86.5

Terminal cover

[Drilling holes for mounting]

[Panel cut-out]

3P

3P

24

9.5

8.5 9.5

0.7
tap
M4

71

70
105

9 (Max.)

24

27.5

144

75.5

3P

R5

35

M4 0.7
tapped hole

30

Molded Case Circuit Breaker_ 175

U-Series

/ Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| Q-class (for nuclear power plant application) / HBL type 225AF, 85kA / Motor protection |
Tripping curves

Hour

225A

2
1

Minute

30
20
14
10
6
4
2
1

Tripping time

30
20

HBL203UM

Instantaneous trip
current (500-1000%)

10
5

HBL203UMQ

Min.

Max.

Second

1
0.5
0.2
0.1
0.05
0.04
0.03
0.02

7000

5000

3000

2000

1500

500
600
700
800
900
1000

400

300

200

100

125

0.01

Percentage for rated current (%)

Current

Instantaneous trip current

Rated
current
(A)

125

625

750

875

1000

1125

1250

150

750

900

1050

1200

1350

1500

Multiple for rated current


7

Left

Right

Handle

[ Front ]

176

Shunt
trip

10

875

1050

1225

1400

1575

1750

200

1000

1200

1400

1600

1800

2000

225

1125

1350

1575

1800

2025

2250

Installation of signal accessories

Trip alarm
switch

175

Tolerance for setting current: -20% - +30%

No.
of
Auxiliary
poles switch

Under
voltage trip

MCCB

Dimensions

: Center line

: Handle center line

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

Direct mounting
112
35

Terminal cover

[with terminal bus bar*option]


A

M8 bolt

Dimension A

144
165

146

Line side : 26mm


Load side : 24mm

t4

[Connection conductor]

[Terminal part]

23 (Max.)

10

86.5

Terminal cover

[Drilling holes for mounting]

[Panel cut-out]

3P

3P

24

9.5

8.5 9.5

0.7
tap
M4

71

70
105

9 (Max.)

24

27.5

144

75.5

3P

R5

35

M4 0.7
tapped hole

30

Molded Case Circuit Breaker_ 177

U-Series

/ Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| Miniature type / Molded case circuit breaker |
Tripping & temperature derating curves
240

15-30A

120

Minute

60

10

1
40

Tripping time

UMB30R

Derating rate for rated current (%)

Max.
20
10
6
4
2

Second

Min.
1

150

100

50

10

20

30

40

50

Ambient temperature (C)


0.2
0.1

Instantaneous trip
(800-2000%)

Max. total
breaking time

0.02
0.01

1.5 2

3 4 5 6 7 8 10

15 20 30 40 50

100

Multiple for rated current (times)

Current

Dimensions

: Center line

: Handle center line

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

Direct mounting

33
42

[Terminal part]

20

6.8

11.3

8.2

M5 11

8.2

Load side

57

[Panel cut-out]

59

38

[Drilling holes for mounting]

35

178

11.3

6.8

68

70

56

36

Line side

14.5

MCCB

Tripping & temperature derating curves




15-50A



Minute








Tripping time

UMB30S
UMB50S

Derating rate for rated current (%)



Max.




Second

Min.

















Ambient temperature (C)




Instantaneous trip
(800-2000%)

Max. total
breaking time





 

     

 

  

 

Multiple for rated current (times)

Current

Dimensions

: Center line

: Handle center line

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

Direct mounting
IEC 35mm
DIN-rail

80

35

M5 12

20.5

70

50
68
80

20.5

[Terminal part]

10.5
5

Line side 32
Load side 30

10.5
60
66
67.5
76

19
35

[Drilling holes for mounting]


35

[Panel cut-out]
M4 or 5

70

52

R2

Molded Case Circuit Breaker_ 179

U-Series

/ Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| Miniature type / Molded case circuit breaker |
Tripping & temperature derating curves



15-50A

Minute







Derating rate for rated current (%)





Tripping time




UMB30H

Max.





UMB50H
Second

Min.

















 





Ambient temperature (C)

Instantaneous trip
(800-1200%)



Max. total
breaking time






 

    

 

  

 

Multiple for rated current (times)

Current

Dimensions

: Center line

: Handle center line

The allowance of 1.5mm is given around the handle frame.

Direct mounting

M5 12

80

68

35

18.5

[Terminal part]
50

70

47.5

IEC 35mm
DIN-rail

10.5
5
Line side 32
Load side 30

10.5
60
19

66

35

67.5
76

[Drilling holes for mounting]

[Panel cut-out]

35

M4 or 5

180

70

52

R2

(Unit: mm)

MCCB

Tripping & temperature derating curves

3-30A








Max.

Tripping time








Second

UDB30S



UDB30H
UDB50S

Min.

Instantaneous trip
(800-1200%)






Derating rate for rated current (%)

Minute






















Max. total
breaking time






UDB50H











Ambient temperature (C)



UDB100S



 

    

 

    

Multiple for rated current (times)

UDB100H

Current

40-100A







Max.




Tripping time




Second







Min.

Instantaneous trip
(800-1200%)






Derating rate for rated current (%)

Minute






























Ambient temperature (C)



Max. total
breaking time








 

    

 

    

Multiple for rated current (times)

Current

Installation of signal accessories


No.
of
poles

Auxiliary
switch

Trip alarm
switch

Shunt
trip

Left

Right

- In case of 2P, all signal accessories shall be installed in left side of breaker.
- SHT is not applicable to 2P.

Handle

[ Front ]

Molded Case Circuit Breaker_ 181

U-Series

/ Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| Miniature type / Molded case circuit breaker |
Dimensions

: Center line

Direct mounting

: Handle center line

The allowance of 1.5mm is given around the handle frame.

UDB30, UDB50
IEC 35mm
DIN-rail

35
97.5

64
80
96

50
9 25

64
80
96

50
9 25

Mounting hole

13

Trip button

4.5
Trip button

25
50

50
53
60
65
80

50
75

2P

3P

[Terminal part]

M5 12

Line side 32
Load side 30

[Drilling holes for mounting]

[Panel cut-out]
M4 or 5

74

25

M4 or 5

49
R2

52

52

80-84

R2

2P

Direct mounting

3P

2P

3P

UDB100

Mounting hole
IEC 35mm
DIN-rail
M8 14

88

35
97.5

64
80

50
9 25

[Terminal part]

4.5

Trip button

[Drilling holes for mounting]

[Panel cut-out]
M4 or 5

74

Line side 32
Load side 30

17

50
53
60
65
80

50
75

25

182

80-84

52

R2

(Unit: mm)

MCCB

Tripping & temperature derating curves


240

15-30A

120

Minute

60

10

1
40

Tripping time

UMG30R

Derating rate for rated current (%)

Max.
20
10
6
4
2

Second

Min.
1

150

100

50

10

20

30

40

50

Ambient temperature (C)

0.2
0.1

Instantaneous trip
(800-2000%)

Max. total
breaking time

0.02
0.01

1.5 2

3 4 5 6 7 8 10

15 20 30 40 50

100

Multiple for rated current (times)

Current

Dimensions

: Center line

: Handle center line

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

Direct mounting
33
42
20

[Terminal part]

6.8

Line side

68

11.3

6.8

M5 11

14.5

8.2

Load side
57

[Panel cut-out]

38

[Drilling holes for mounting]

59

70

56

36

11.3

8.2

35

Molded Case Circuit Breaker_ 183

U-Series

/ Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| Miniature type / Earth leakage circuit breaker |
Tripping & temperature derating curves


15-50A



Minute








Tripping time

UMG30S



Max.





Second

UMG50S

Derating rate for rated current (%)

Min.

















Ambient temperature (C)




Instantaneous trip
(800-2000%)

Max. total
breaking time





 

     

 

  

 

Multiple for rated current (times)

Current

Dimensions

: Center line

: Handle center line

The allowance of 1.5mm is given around the handle frame.

Direct mounting
IEC 35mm
DIN-rail

[Terminal part]

80

35

6 6

20.5

70

50
68
80

20.5

M5 12

10.5
5

Line side 32
Load side 30

10.5
60
66
67.5
76

19
35

Earth leakage
test button

[Drilling holes for mounting]


35

[Panel cut-out]
M4 or 5

184

70

52

R2

(Unit: mm)

MCCB

Tripping & temperature derating curves





15-50A

Minute







Derating rate for rated current (%)





Tripping time




UMG30H
UMG50H

Max.





Second

Min.

















 





Ambient temperature (C)

Instantaneous trip
(800-1200%)



Max. total
breaking time






 

    

 

  

 

Multiple for rated current (times)

Current

Dimensions

: Center line

: Handle center line

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

Direct mounting
IEC 35mm
DIN-rail

Earth leakage
test button

80

68

35

18.5

M5 12
50

70

47.5

[Terminal part]

6 6

10.5
5

Line side 32
Load side 30

10.5
60
Trip button

19

66

35

67.5
76

[Drilling holes for mounting]


35

[Panel cut-out]
M4 or 5

70

52

R2

Molded Case Circuit Breaker_ 185

U-Series

/ Molded Case Circuit Breaker

Characteristic Curves & Dimensions


| Miniature type / Earth leakage circuit breaker |
Tripping & temperature derating curves

3-30A








Max.

Tripping time







Second

UDG30S



UDG30H
UDG50S

Min.

Instantaneous trip
(800-1200%)






Derating rate for rated current (%)

Minute






























Max. total
breaking time






UDG50H



Ambient temperature (C)



UDG100S



 

UDG100H

    

 

    

Multiple for rated current (times)

Current

40-100A







Max.

Tripping time





Second







Min.

Instantaneous trip
(800-1200%)






Max. total
breaking time








 

    

 

    

Multiple for rated current (times)

Current

Installation of signal accessories

Trip alarm
switch

3
Right

Left

Handle

[ Front ]

186













No.
of
Auxiliary
poles switch

Derating rate for rated current (%)

Minute










In case of 2P, all signal accessories shall be installed in left side of breaker.











Ambient temperature (C)

MCCB

Dimensions

: Center line

The allowance of 1.5mm is given around the handle frame.

(Unit: mm)

UGD30, UGD50

35
97.5

50
9 25

19.1

13

Trip button

IEC 35mm
DIN-rail

Earth leakage
indicator

Mounting hole

64
80
96

50
9 25

Earth leakage
indicator

64
80
96

Direct mounting

: Handle center line

Earth leakage
test button
Trip button

25
50

4.5
Earth leakage
test button
50
53
60
65
80

50
75

2P

3P

[Terminal part]

M5 12

17

[Drilling holes for mounting]

[Panel cut-out]
74

49

M4 or 5

80-84

52

52

2P

3P

80-84

R2

R2

Direct mounting

25

M4 or 5

2P

3P

UGD100
Earth leakage
indicator

Mounting hole

IEC 35mm
DIN-rail

[Terminal part]

88

35
97.5

64
80
96

50
9 25

M8 14

19.1
4.5
Earth leakage
test button

Line side 32
Load side 30

17
50
53
60
65
80

50
75

[Drilling holes for mounting]

[Panel cut-out]
M4 or 5

74

25

80-84

R2

52

Trip button

Molded Case Circuit Breaker_ 187

Accessories
| Signal Accessories | Operating Accessories | Mounting Accessories |
| Terminal Accessories | Portable Test Equipment |

U-Series

Molded Case Circuit Breaker

Accessories

| Signal accessories |

Accessories for UAB100

auxiliary switch
trip alarm switch
shunt trip
under voltage trip

| Operating accessories |
operating handle (surface and extended type)
motor operator
mechanical interlock
padlock plate
extension handle

| Mounting accessories |
DIN-rail adaptor
mounting base for plug-in mounting

Auxiliary switch [ AUX ]

| Terminal accessories |
terminal bus bar
cage terminal block
terminal cover
interpole barrier

Trip alarm switch [ ALT ]

| Portable test equipment |


MCCB trip unit tester
Surface type operating handle [ TFG ]

Extended type operating handle [ TFH ]

Motor operator [ MOT ]

The applicable accessories of each MCCB are not same as above. For exact application to each MCCB, please reter to next pages.

190

MCCB

Cage terminal block [ CTB ]

Terminal cover [ TCF ]

Interpole barrier [ TQQ ]

DIN-rail adaptor [ DRA ]

Plug-in mounting base [ TDM ]

Shunt trip [ SHT ]

Under voltage trip [ UVT ]

Cage terminal block [ CTB ]

Terminal cover [ TCF ]

Interpole barrier [ TQQ ]

Molded Case Circuit Breaker_ 191

U-Series

Molded Case Circuit Breaker

Signal Accessories

Signal accessories adopts cassette type assembly method, so they can be easily installed and removed.

Auxiliary

AUX

- Electrically indicates ON
and OFF status of breaker

Shunt trip

SHT

- Electrically trips breaker at


remote place

192

Trip alarm switch

ALT

- Electrically indicates TRIP


status of breaker

Under voltage trip

UVT

- Automatically trips breaker


when control voltage drops
below predetermined value

MCCB

| Installation and wiring of signal accessories |


Item

Installation
3 pole

Wiring

2 pole

1EA of 1ab type AUX

2EA of 1ab type AUX


Auxiliary
switch
[AUX]
3EA of 1ab type AUX

4EA of 1ab type AUX

Trip alarm
switch
[ALT]
Limit switch for coil protecton
1)

for SHT 10A H, SHT 10B H,


SHT 20C H

Shunt trip
[SHT]
2)

Under voltage
trip [UVT]
- For detail installation to each MCCB model, please refer to Characteristic curves & Dimensions from page 138 to 187.
1) Common for AC200-480V. Applicable for SHT 10A H, SHT 10B H and SHT 20C H only.
2) The coil is continuously energized, so that limit switch is not required.

| Operation of AUX and ALT |


MCCB
Status

Auxiliary switch [AUX]

Trip alarm switch [ALT]

ON

OFF

TRIP

Molded Case Circuit Breaker_ 193

U-Series

Molded Case Circuit Breaker

Signal Accessories
| Auxiliary switch (AUX) and trip alarm switch (ALT) |
Applicable MCCB
UAB30C, UAB30R, UAB50C, UAB50R,
UAB60C, UAB60R, UAB100C / UAD50C
UAB50S, UAB50H, UAB100R, UAB100S
/ UAD50S, UAD100R
UCB50R, UCB100R, UCB100S / UCD100S
UCB250R, UCB250S, UCB250N / UCD250S
UCB50H, UCB50L, UCB100H, UCB100L,
UCB160H, UCB160L, UCB250H, UCB250L
/ UCD50H, UCD100H, UCD160H, UCD250H
UCB400R, UCB400S, UCB400H, UCB400L, UCB630R,
UCB630S, UCB630H, UCB630L, UCB800R, UCB800S,
UCB800H, UCB800L / UCD400S, UCD630S, UCD800S
UCB1000S, UCB1000L, UCB1250S, UCB1250L
/ UCD1000S, UCD1250S
UCB1600S
UPB100S, UPB100H, UPB100L, UPB100X, UPB160S,
UPB160H, UPB160L, UPB160X, UPB250S, UPB250H,
UPB250L, UPB250X / UPD100S, UPD160S, UPD250S
UPB400S, UPB400H, UPB400L, UPB400X, UPB630S,
UPB630H, UPB630L, UPB630X / UPD400S, UPD630S
HBL103U, HBL103UM, HBL203U, HBL203UM,
HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ1)
UDB30S, UDB30H, UDB50S, UDB50H, UDB100S,
UDB100H / UDG30S, UDG30H, UDG50S, UDG50H,
UDG100S, UDG100H

Auxiliary switch (AUX)


Order code

Trip alarm switch (ALT)

Specification

AUX 10A R1
AUX 10A R2
AUX 10UA R1
AUX 10UA L1
AUX 10B L1
AUX 20C L1

1C, right-hand-side
2C, right-hand-side
1C, right-hand-side
1C, left-hand-side
1C, left-hand-side
1C, left-hand-side

AUX 12FG L1

Order code

Specification

ALT 10A R1

1C, right-hand-side

ALT 10UA R1
ALT 10UA L1
ALT 10B L1
ALT 20C L1

1C, right-hand-side
1C, left-hand-side
1C, left-hand-side
1C, left-hand-side

1C, left-hand-side

ALT 12FG R1

1C, right-hand-side

AUX 12FG L2

2C, left-hand-side

ALT 12FG L1

1C, left-hand-side

AUX 46D R1

1C, right-hand-side

ALT 46D L1

1C, left-hand-side

AUX 80NE R1
AUX 80NE R2
AUX 80NE R3
AUX 160NE R1
AUX 160NE R2

1C, right-hand-side
2C, right-hand-side
3C, right-hand-side
1C, right-hand-side
2C, right-hand-side

ALT 80NE R1

1C, right-hand-side

AUX 12UP R1

1C, right-hand-side

ALT 12UP L1

1C, left-hand-side

AUX 46UP L1

1C, left-hand-side

ALT 46UP R1

1C, right-hand-side

AUX 12UP R1

1C, right-hand-side

ALT 12UP L1

1C, left-hand-side

1C, left-hand-side

ALT 10UD 2L1


ALT 10UD 2L1T 2)
ALT 10UD 3L1
ALT 10UD 3L1T 2)

AUX 10UD L1
AUX 10UD L1T2)

1) Signal accessories for HBL type shall be installed in breaker before ex-working.

Category

MCCB MB

1C, left-hand-side
for 2 pole
1C, left-hand-side
for 3 pole

2) Terminal block type

| Shunt trip (SHT) |


Applicable MCCB
UAB30C, UAB30R, UAB50C, UAB50R,
UAB60C, UAB60R, UAB100C / UAD50C
UAB50S, UAB50H, UAB100R, UAB100S
/ UAD50S, UAD100R
UCB50R, UCB100R, UCB100S / UCD100S
UCB250R, UCB250S, UCB250N / UCD250S
UCB50H, UCB50L, UCB100H, UCB100L,
UCB160H, UCB160L, UCB250H, UCB250L
/ UCD50H, UCD100H, UCD160H, UCD250H
UCB400R, UCB400S, UCB400H, UCB400L, UCB630R,
UCB630S, UCB630H, UCB630L, UCB800R, UCB800S,
UCB800H, UCB800L / UCD400S, UCD630S, UCD800S
UCB1000S, UCB1000L, UCB1250S, UCB1250L
/ UCD1000S, UCD1250S
UCB1600S
UPB100S, UPB100H, UPB100L, UPB100X, UPB160S,
UPB160H, UPB160L, UPB160X, UPB250S, UPB250H,
UPB250L, UPB250X / UPD100S, UPD160S, UPD250S
UPB400S, UPB400H, UPB400L, UPB400X, UPB630S,
UPB630H, UPB630L, UPB630X / UPD400S, UPD630S
HBL103U, HBL103UM, HBL203U, HBL203UM,
HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ2)
UDB30S, UDB30H, UDB50S, UDB50H,
UDB100S, UDB100H

194

Order code / Exciting current (peak value)


DC24V
DC100-110V AC100-120V AC200-230V AC380-415V AC440-480V
SHT 10A A
SHT 10A C
SHT 10A F
SHT 10A H
5.2A
1.1A
0.76A
0.28A
SHT 10UA A
SHT 10UA F SHT 10UA H SHT 10UA B SHT 10UA D
5.7A
0.88A
0.42A
0.42A
0.42A
SHT 10B A
SHT 10B F
SHT 10B H
5.2A
0.76A
0.4A
SHT 20C A
SHT 20C F
SHT 20C H
5.2A
0.76A
0.4A
SHT 12FG A

SHT 12FG C

SHT 12FG F

SHT 12FG H

SHT 12FG B

SHT 12FG D

5.2A

2.2A

0.76A

0.4A

0.4A

0.4A

SHT 46D A

SHT 46D C

SHT 46D F

SHT 46D H

SHT 46D B

SHT 46D D

0.01A

0.01A

0.012A

0.011A

0.01A

0.01A

SHT 120NE A SHT 120NE C SHT 120NE F SHT 120NE H SHT 120NE B SHT 120NE D
2A
0.11A
0.24A
0.23A
0.23A
0.23A
SHT 160NE A SHT 160NE C SHT 160NE F SHT 160NE H SHT 160NE B1)
2A
1A
0.76A
0.4A
0.35A
SHT 12UP A

SHT 12UP C

SHT 12UP F

SHT 12UP H

SHT 12UP B

SHT 12UP D

0.023A

0.023A

0.023A

0.023A

0.023A

0.023A

SHT 46UP A
0.023A
SHT 12UP A
0.023A
SHT 10UD A
SHT 10UD AT3)
1.65A

SHT 46UP C
0.023A
SHT 12UP C
0.023A
SHT 10UD C
SHT 10UD CT3)
0.36A

SHT 46UP F
0.023A
SHT 12UP F
0.023A
SHT 10UD F
SHT 10UD FT3)
0.4A

SHT 46UP H
0.023A
SHT 12UP H
0.023A
SHT 10UD H
SHT 10UD HT3)
0.2A

SHT 46UP B
0.023A
SHT 12UP B
0.023A
SHT 10UD B
SHT 10UD BT3)
0.08A

SHT 46UP D
0.023A
SHT 12UP D
0.023A
SHT 10UD D
SHT 10UD DT3)
0.1A

- The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC.
1) SHT 160NE B is applicable for AC380V only.
2) Signal accessories for HBL type shall be installed in breaker before ex-working.
3) Terminal block type

Category

MCCB MB

MCCB

| Under voltage trip (UVT) |


Order code

Applicable MCCB

DC24V

UAB30C, UAB30R, UAB50C, UAB50R,


UAB60C, UAB60R, UAB100C / UAD50C
UAB50S, UAB50H, UAB100R, UAB100S
/ UAD50S, UAD100R
UCB50R, UCB100R, UCB100S / UCD100S
UCB250R, UCB250S, UCB250N / UCD250S
UCB50H, UCB50L, UCB100H, UCB100L,
UCB160H, UCB160L, UCB250H, UCB250L
/ UCD50H, UCD100H, UCD160H, UCD250H
UCB400R, UCB400S, UCB400H, UCB400L, UCB630R,
UCB630S, UCB630H, UCB630L, UCB800R, UCB800S,
UCB800H, UCB800L / UCD400S, UCD630S, UCD800S
UCB1000S, UCB1000L, UCB1250S, UCB1250L
/ UCD1000S, UCD1250S
UCB1600S
UPB100S, UPB100H, UPB100L, UPB100X, UPB160S,
UPB160H, UPB160L, UPB160X, UPB250S, UPB250H,
UPB250L, UPB250X / UPD100S, UPD160S, UPD250S
UPB400S, UPB400H, UPB400L, UPB400X, UPB630S,
UPB630H, UPB630L, UPB630X / UPD400S, UPD630S
HBL103U, HBL103UM, HBL203U, HBL203UM,
HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ2)

DC100-110V AC100-120V AC200-230V AC380-415V AC440-480V

UVT 10A J

UVT 10A L

UVT 10A N

UVT 10A P

UVT 10A Q

UVT 10A R

UVT 10UA J

UVT 10UA L

UVT 10UA N

UVT 10UA P

UVT 10UA Q

UVT 10UA R

UVT 10B J
UVT 20C J

UVT 10B L
UVT 20C L

UVT 10B N
UVT 20C N

UVT 10B P
UVT 20C P

UVT 10B Q
UVT 20C Q

UVT 10B R
UVT 20C R

UVT 12FG J

UVT 12FG L

UVT 12FG N

UVT 12FG P

UVT 12FG Q

UVT 12FG R

UVT 46D J

UVT 46D L

UVT 46D N

UVT 46D P

UVT 46D Q

UVT 46D R

Category

MCCB MB
UVT 120NE J UVT 120NE L UVT 120NE N UVT 120NE P UVT 120NE Q
-

UVT 120NE R

UVT 160NE P UVT 160NE Q1) UVT 160NE R1)

UVT 12UP J

UVT 12UP L

UVT 12UP N

UVT 12UP P

UVT 12UP Q

UVT 12UP R

UVT 46UP J

UVT 46UP L

UVT 46UP N

UVT 46UP P

UVT 46UP Q

UVT 46UP R

UVT 12UP J

UVT 12UP L

UVT 12UP N

UVT 12UP P

UVT 12UP Q

UVT 12UP R

- The permissible operating voltage: 85-110% of rated voltage for AC, 85~125% for DC. The tripping voltage: 20-70% of rated voltage.
- Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.
1) UVT 160NE Q is applicable for AC380V only, and UVT 160NE R is applicable for AC440V only.
2) Signal accessories for HBL type shall be installed in breaker before ex-working.

UVT controller is supplied as standard for UVT 10A, UVT 10UA, UVT 10B, UVT 20C, UVT 12FG, UVT 46D J, UVT 12UP and UVT 46UP type.
Fixing hole
(R/H M4 X L11 + P/W + S/W)

U2

88

100

16 15 18 15 16
8

16

ON
16.5

Mounting hole( 4.5)


(R/H M4 X L9 + P/W + S/W)

MCCB

U1
UC2 (-)

22

UC1 (+)
OFF

Terminal screw M3.5

63

56
45

UVT controller

Supportor

[ Wiring ]
Terminal U1 an U2 are connected by the cable of vw-1, 22AWG (0.324
Different cables are available on request.

[ Dimensions ]
700 ).

Molded Case Circuit Breaker_ 195

U-Series

Molded Case Circuit Breaker

Operating Accessories

Operating accessories offers convenience and safety in operation of breaker.

Operating handle

TFG, TFH

- Enables manual operation of breaker without panel door-open


- Offers panel door-lock and reverse interlock function
- Satisfies IP54

Surface type / TFG

Extended type / TFH


- Useful in case that panel door is far from breaker
- Mechanism part is installed on front of breaker and
connected with operating part by shaft

Motor operator

MOT

PLD

- Locks the breaker in OFF position

196

MIF

- Mechanically prevents simultaneous closing


of two breakers

- Enables automatic remote


ON and OFF operation as
well as manual operation
- Applied to electric
supervision and control
system
- Equips an emergency trip
button in all range

Padlock plate

Mechanical interlock

Extension handle

THA

- Reduces strength in operation of breaker

MCCB

| Operating handle (TFG/TFH) |


Surface type (TFG)
Applicable MCCB

UAB30C, UAB30R, UAB50C, UAB50R,


UAB60C, UAB60R, UAB100C / UAD50C
UAB50S, UAB50H, UAB100R, UAB100S
/ UAD50S, UAD100R
UCB50R, UCB100R, UCB100S / UCD100S
UCB250R, UCB250S, UCB250N / UCD250S
UCB50H, UCB50L, UCB100H, UCB100L
/ UCD50H, UCD100H
UCB160H, UCB160L, UCB250H, UCB250L
/ UCD160H, UCD250H
UCB400R, UCB400S, UCB400H, UCB400L, UCB630R,
UCB630S, UCB630H, UCB630L, UCB800R, UCB800S,
UCB800H, UCB800L / UCD400S, UCD630S, UCD800S
UCB1600S
UPB100S, UPB100H, UPB100L, UPB100X, UPB160S,
UPB160H, UPB160L, UPB160X, UPB250S, UPB250H,
UPB250L, UPB250X / UPD100S, UPD160S, UPD250S
UPB400S, UPB400H, UPB400L, UPB400X, UPB630S,
UPB630H, UPB630L, UPB630X / UPD400S, UPD630S
HBL103U, HBL103UM, HBL203U, HBL203UM
HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ

Extended type (TFH)

S type
L type
Right1)
Left1)
Upper1)
Left1)
Upper1)
power supply power supply power supply power supply power supply
type
type
type
type
type

S type

L type

TFG 10AL L4

TFH 10AS

TFH 10AL

TFG 10UAS U4 TFG 10UAS R4 TFG 10UAS L4 TFG 10UAL U4 TFG 10UAL L4

TFH 10UAS

TFH 10UAL

TFG 10BS U4 TFG 10BS R4 TFG 10BS L4 TFG 10BL U4 TFG 10BL L4
TFG 20CS U4 TFG 20CS R4 TFG 20CS L4 TFG 20CL U4 TFG 20CL L4

TFH 10BS
TFH 20CS

TFH 10BL
TFH 20CL

TFG 10UFS U4 TFG 10UFS R4 TFG 10UFS L4 TFG 10UFL U4 TFG 10UFL L4 TFH 10UFS

TFH 10UFL

TFG 20UGS U4 TFG 20UGS R4 TFG 20UGS L4 TFG 20UGL U4 TFG 20UGL L4

TFH 20UGS

TFH 20UGL

TFG 46DS U2 TFG 46DS R2 TFG 46DS L2

TFG 10AS U4 TFG 10AS R4 TFG 10AS L4 TFG 10AL U4

TFH 46DS

TFH 160NE

TFG 12UPS U4 TFG 12UPS R4 TFG 12UPS L4 TFG 12UPL U4 TFG 12UPL L4

TFH 12UPS

TFH 12UPL

TFG 46UPS U2 TFG 46UPS R2 TFG 46UPS L2

TFH 46UPS

TFG 20U U4 TFG 20U L4


TFG 20UQ U4 TFG 20UQ L4

- In case of surface type (TFG), there are three types for diverse panel door-lock application, above mentioned codes are standard type. For detail, please refer to following explanation.
1) Upper, right and left indicates the power supply direction of MCCB.

Power supply direction of MCCB


Surface type (TFG) operating handles are divided into three types by power supply direction of MCCB.

Power (Line side)

Power (Line side)

Power (Line side)

MCCB

MCCB
MCCB

[Upper power supply type]

[Right power supply type]

[Left power supply type]

ON, OFF and TRIP are not marked on real products.

Panel door-lock
Surface type (TFG) operating handles offer four options in panel door-lock application.
OFF OPEN type: Panel door opens when operating handle is in OFF position. Indicating code (last digit of full order code) is
1. ex. TFG 10AS U1
OFF OPEN type with reverse interlock: Panel door opens when operating handle is in OFF position. Reverse interlock keeps
MCCB not to be "ON" when panel door opens. This is standard type for 400-800AF MCCB and indicating code (last digit of
full order code) is 2. ex.TFG 46DS U2
RESET OPEN type: Panel door opens when operating handle is in RESET position. Indicating code (last digit of full order
code) is 3. ex.TFG 10AS U3
RESET OPEN type with reverse interlock: Panel door opens when operating handle is in RESET position. Reverse interlock
keeps MCCB not to be ON when panel door opens. This is standard type for 30-250AF MCCB and indicating code (last digit
of full order code) is 4. ex. TFG 46DS U4

When panel door is required to open in ON position of operating handle, please turn the RELEASE knob to
indicated direction and open the panel door.
For more operating function, please refer to following pages.
Molded Case Circuit Breaker_ 197

U-Series

Molded Case Circuit Breaker

Operating Accessories
Operation
Operating direction
Turn the handle in a clockwise direction for ON.

Operation in panel door-closed


MCCB ON: Turn the handle to ON position. (Fig. 1)
MCCB OFF: Turn the handle to OFF position. (Fig. 2)
MCCB TRIP: When MCCB trips, handle turns to TRIP position automatically.
After MCCB trips, turn the handle to RESET position first and turn to ON position for
MCCB ON. (Fig. 3 and Fig. 1)
When panel door is required to open in ON position of operating handle, please turn the
RELEASE knob to indicated direction and open the panel door. (Fig. 4)

ON, OFF and TRIP are not marked on real products.

Lock and release of panel door


When MCCB is in ON, OFF and TRIP status, both operating handle and panel door are locked.
When MCCB is in OFF and TRIP status, panel door can be opened by turning the handle to RESET position. (Fig. 3)
Panel door shall be locked automatically when you close the door in MCCB ON status. Please turn the handle to ON
position before closing the door.

Lock of operating handle


If required, you can lock operating handle in ON or OFF position with padlock ( 6-8 for S type,
not supplied. (Fig. 5)
When MCCB trips, handle turns to TRIP position automatically.

4-6 for L type). Padlock is

Handle position shall be same with MCCB position (ON, OFF, TRIP) before closing the panel door.

Fig.1

Fig.2

Fig.3

Fig.4

Fig.5

Trip button

[ S type ]

Fig.1

Fig.2

Fig.3

Fig.4

[ L type ]
ON, OFF and TRIP are not marked on real products.

198

Fig.5

MCCB

Dimensions and standard order code / Surface type (TFG)


30-250AF S type
[ Upper power supply type ]
Panel door

Line side

59

37

44

Handle center line

59
MCCB center line

[ Right power supply type ]

Handle center line


MCCB center line
Panel door

37

44

59

Line side

59

[ Left power supply type ]


Handle center line

MCCB center line


4

Panel door

Line side

59

37
4-

59

A
8

Order code
Applicable MCCB
UAB30C, UAB30R, UAB50C, UAB50R,
UAB60C, UAB60R, UAB100C / UAD50C
UAB50S, UAB50H, UAB100R, UAB100S
/ UAD50S, UAD100R
UCB50R, UCB100R, UCB100S / UCD100S
UCB250R, UCB250S, UCB250N / UCD250S
UCB50H, UCB50L, UCB100H, UCB100L
/ UCD50H, UCD100H
UCB160H, UCB160L, UCB250H, UCB250L
/ UCD160H, UCD250H
UPB100S, UPB100H, UPB100L, UPB100X, UPB160S,
UPB160H, UPB160L, UPB160X, UPB250S, UPB250H,
UPB250L, UPB250X / UPD100S, UPD160S, UPD250S

Upper power
supply type

Right power
supply type

Dimensions (mm)
Left power
supply type

Category
A

TFG 10AS U4

TFG 10AS R4

TFG 10AS L4

43

56

TFG 10UAS U4

TFG 10UAS R4

TFG 10UAS L4

43

56

TFG 10BS U4
TFG 20CS U4

TFG 10BS R4
TFG 20CS R4

TFG 10BS L4
TFG 20CS L4

9
9

47
47

56
56

TFG 10UFS U4

TFG 10UFS R4

TFG 10UFS L4

47

56

TFG 20UGS U4

TFG 20UGS R4

TFG 20UGS L4

47

56

TFG 12UPS U4

TFG 12UPS R4

TFG 12UPS L4

16.25

41

87

MCCB

MB

Molded Case Circuit Breaker_ 199

U-Series

Molded Case Circuit Breaker

Operating Accessories

30-250AF L type
[ Upper power supply type ]
Panel door
B
1.2-3.2

4-8

50

55
55

60

88
100

Handle center line

MCCB center line

88
100

25
4-M4 bolt hole

[ Left power supply type ]


Panel door
Handle center line

MCCB center line


A

1.2-3.2

88
100

25

88
100

4-8

MCCB center line Handle center line

50

60

55

55

ON, OFF and TRIP are not marked on real products.

Dimensions (mm)

Order code
Applicable MCCB
UAB30C, UAB30R, UAB50C, UAB50R,
UAB60C, UAB60R, UAB100C / UAD50C
UAB50S, UAB50H, UAB100R, UAB100S
/ UAD50S, UAD100R
UCB50R, UCB100R, UCB100S / UCD100S
UCB250R, UCB250S, UCB250N / UCD250S
UCB50H, UCB50L, UCB100H, UCB100L
/ UCD50H, UCD100H
UCB160H, UCB160L, UCB250H, UCB250L
/ UCD160H, UCD250H
UPB100S, UPB100H, UPB100L, UPB100X,
UPB160S, UPB160H, UPB160L, UPB160X,
UPB250S, UPB250H, UPB250L, UPB250X
/ UPD100S, UPD160S, UPD250S

200

Upper power
supply type

Left power
supply type

Category
A

TFG 10AL U4

TFG 10AL L4

106-111

TFG 10UAL U4

TFG 10UAL L4

106-111

TFG 10BL U4
TFG 20CL U4

TFG 10BL L4
TFG 20CL L4

9
9

111-116
111-116

TFG 10UFL U4

TFG 10UFL L4

111-116

TFG 20UGL U4

TFG 20UGL L4

111-116

TFG 12UPL U4

TFG 12UPL L4

14.5

136-140

MCCB

MB

MCCB

400-630AF S type
[ Upper power supply type ]
Handle center line

5
4-

Line side

MCCB center line

100

[ Right power supply type ]

100

10
5

100

Panel door
55

5~10

Handle center line

55

Panel door

15

10
5

Line side

100

4-

100

100
MCCB center line

5~10

[ Left power supply type ]


Handle center line

55

Line side

4-

15

100

10
5

100

Panel door

100
MCCB center line

5~10

ON, OFF and TRIP are not marked on real products.

Dimensions (mm)

Order code
Applicable MCCB

Upper power
supply type

Category

Right power
supply type

Left power
supply type

TFG 46DS R2

TFG 46DS L2

222

UCB400R, UCB400S, UCB400H, UCB400L,


UCB630R, UCB630S, UCB630H, UCB630L,

TFG 46DS U2

UCB800R, UCB800S, UCB800H, UCB800L


MCCB

/ UCD400S, UCD630S, UCD800S

MB

UPB400S, UPB400H, UPB400L, UPB400X,


UPB630S, UPB630H, UPB630L, UPB630X

TFG 46UPS U2

TFG 46UPS R2

TFG 46UPS L2

13

234

/ UPD400S, UPD630S

Molded Case Circuit Breaker_ 201

U-Series

Molded Case Circuit Breaker

Operating Accessories
Dimensions and standard order code / Extended type (TFH)

30-250AF S type

37

4-

Panel door

227

59

59

15

15
247

Applicable MCCB

38

Dimensions (mm)

Order code

Category
A

TFH 10AS

384-479

43

56

UAB50S, UAB50H, UAB100R, UAB100S / UAD50S, UAD100R

TFH 10UAS

384-479

43

56

UCB50R, UCB100R, UCB100S / UCD100S

TFH 10BS

388-383

47

56

UCB250R, UCB250S, UCB250N / UCD250S

TFH 20CS

388-383

47

56

UCB50H, UCB50L, UCB100H, UCB100L / UCD50H, UCD100H

TFH 10UFS

388-383

47

56

UCB160H, UCB160L, UCB250H, UCB250L / UCD160H, UCD250H

TFH 20UGS

388-383

47

56

TFH 12UPS

419-414

41

87

UAB30C, UAB30R, UAB50C, UAB50R, UAB60C, UAB60R,


UAB100C / UAD50C

UPB100S, UPB100H, UPB100L, UPB100X, UPB160S, UPB160H,


UPB160L, UPB160X, UPB250S, UPB250H, UPB250L, UPB250X /
UPD100S, UPD160S, UPD250S

202

MCCB

MB

MCCB

30-250AF L type
[ Upper power supply ]

B
Panel door

C
1.2-3.2

Handle center line


77

50

19

80

77
A

0
R1

80
MCCBcenter line
D

4-M4 bolt hole

[ Left power supply ]

Panel door
B
1.2-3.2

Handle center line


50

19

80

77

0
R1

77
A

80
Handle center line

MCCBcenter line

4-M4 bolt hole

ON, OFF and TRIP are not marked on real products.

Applicable MCCB

Dimensions (mm)

Order code

UAB30C, UAB30R, UAB50C, UAB50R, UAB60C, UAB60R, UAB100C / UAD50C


UAB50S, UAB50H, UAB100R, UAB100S / UAD50S, UAD100R
UCB50R, UCB100R, UCB100S / UCD100S
UCB250R, UCB250S, UCB250N / UCD250S
UCB50H, UCB50L, UCB100H, UCB100L / UCD50H, UCD100H
UCB160H, UCB160L, UCB250H, UCB250L / UCD160H, UCD250H
UPB100S, UPB100H, UPB100L, UPB100X, UPB160S, UPB160H, UPB160L, UPB160X,
UPB250S, UPB250H, UPB250L, UPB250X / UPD100S, UPD160S, UPD250S

Category
A

TFH 10AL
TFH 10UAL
TFH 10BL
TFH 20CL
TFH 10UFL
TFH 20UGL

5
5
9
9
9
9

210-360
210-360
210-360
210-360
210-360
210-360

160
160
164
164
164
164

106
106
110
110
110
110

TFH 12UPL

14.5

210-360

186

135

MCCB

MB

400-630AF S type
Panel door

250

125

10
5

100

4-

55
5-10

100
A

Applicable MCCB

Order code

Dimensions (mm)
A

UCB400R, UCB400S, UCB400H, UCB400L, UCB630R, UCB630S, UCB630H, UCB630L,


UCB800R, UCB800S, UCB800H, UCB800L / UCD400S, UCD630S, UCD800S

TFH 46DS

428

UPB400S, UPB400H, UPB400L, UPB400X, UPB630S, UPB630H, UPB630L, UPB630X /


UPD400S, UPD630S

TFH 46UPS

440

Category

MCCB

MB

Molded Case Circuit Breaker_ 203

U-Series

Molded Case Circuit Breaker

Operating Accessories
Dimensions and standard order code / Q-class (for nuclear power plant application)
Surface type (TFG)
[ Upper power supply type ]
Panel door
Max. 140 - Min. 136
35
Line

Handle center line

1.2-3.2

87.5

14.5

88
100

14.5

58.5

4- 8

88

MCCB center line

100
5.5

4-M4 bolt hole

C
D

[ Left power supply type ]


Panel door
Handle center line

MCCB center line Handle center line

MCCB center line

Max. 140 - Min. 136


1.2-3.2

4- 8

88
100
35
Line

88

58.5

87.5

100

73

73

5.5

C
D

14.5

ON, OFF and TRIP are not marked on real products.

Dimensions (mm)

Order code
Applicable MCCB

Upper power
supply type

Left power
supply type

Category
A

HBL103U, HBL103UM, HBL203U, HBL203UM

TFG 20U U4

TFG 20U L4

14.5

51.5

78

129.5

HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ

TFG 20UQ U4

TFG 20UQ L4

14.5

51.5

78

129.5

MCCB

204

MB

U-Series

Molded Case Circuit Breaker

Operating Accessories
| Motor operator (MOT) |

MOT-12NE

Applicable MCCB

Model

UAB30C, UAB30R, UAB50C, UAB50R,


UAB60C, UAB60R, UAB100C / UAD50C
UAB50S, UAB50H, UAB100R, UAB100S /
UAD50S, UAD100R
UCB50R, UCB100R, UCB100S / UCD100S
UCB50H, UCB50L, UCB100H, UCB100L /
UCD50H, UCD100H
UCB250R, UCB250S, UCB250N / UCD250S
UCB160H, UCB160L, UCB250H, UCB250L /
UCD160H, UCD250H
UCB400R, UCB400S, UCB400H, UCB400L /
UCD400S
UCB630R, UCB630S, UCB630H, UCB630L,
UCB800R, UCB800S, UCB800H, UCB800L /
UCD630S, UCD800S
UCB1000S, UCB1000L, UCB1250S,
UCB1250L / UCD1000S, UCD1250S
UCB1600S
UPB100S, UPB100H, UPB100L, UPB100X,
UPB160S, UPB160H, UPB160L, UPB160X,
UPB250S, UPB250H, UPB250L, UPB250X /
UPD100S, UPD160S, UPD250S
UPB400S, UPB400H, UPB400L, UPB400X,
UPB630S, UPB630H, UPB630L, UPB630X /
UPD400S, UPD630S
HBL103U, HBL103UM, HBL203U,
HBL203UM, HBL103UQ, HBL103UMQ,
HBL203UQ, HBL203UMQ

MOT-10A

Control
voltage (V)

Operational Operation time (ms) Power


Mechanical
consumption
life (times)
current (A) Closing Opening
(W)

DC24V
AC/DC110V
AC/DC220V

2.5
0.5
0.5

DC24V
AC/DC110V
AC/DC220V
DC24V
AC/DC110V
AC/DC220V

2.5
0.5
0.5
5.0
3.0
2.0

MOT-40D

DC24V
AC/DC110V
AC/DC220V

MOT-68E

MOT-68E

Dimensions (mm)
A

310

200

14

25,000

90

132

93

30

310

200

14

10,000

90

132

93

30

350

230

14

8,000

90

126

93

35

5.0
3.0
2.0

350

230

14

5,000

130 215 150

44

DC24V
AC/DC110V
AC/DC220V

5.0
3.0
2.0

500

350

35

5,000

130 243 137

70

MOT-80NE

DC24V
AC/DC110V
AC/DC220V

5.0
3.0
2.0

820

500

120

3,000

130 340 150

70

MOT-160NE

AC 220V

2.0

820

500

120

3,000

MOT-12UP

DC24V
AC/DC110V
AC/DC220V

5.0
3.0
2.0

700

420

35

10,000

130 130 150

45

DC24V
AC/DC110V
AC/DC220V
DC24V
AC/DC110V
AC/DC220V

5.0
3.0
2.0
5.0
3.0
2.0

700

420

35

5,000

130 130 150

45

700

420

35

10,000

130 130 150

45

MOT-10UA
MOT-10UB
MOT-10F
MOT-20C
MOT-20G

MOT-46NE

MOT-12UP

MCCB

A
D
MCCB

MCCB

C
Motor
operator

150
142

376
147

Handle

Motor
32 operator
97

Motor
operator
Motor
operator

[MOT-10/20/40/68/80/12/46]

206

210

122

[MOT-160NE]

MCCB

Control circuit and wiring diagram

S3

1
Control power

Power
K4
K5

K4

P1

P2

S1

S2

S4

POWER

K4

Ue

K3

ON

OFF

K5
ON

K1
K1
ON circuit

S1

S2

K3

M : Motor

K3

K3

K1 : ON relay

K4

K2 : OFF relay

K5

Motor control relay

K2
OFF

OFF circuit
5

K5

S1 : ON limit switch
S2 : OFF limit switch
S3 : Auto/Manual

K2

Standard order code


Applicable MCCB

Order code
DC24V

AC/DC110V

AC/DC220V

UAB30C, UAB30R, UAB50C, UAB50R, UAB60C, UAB60R, UAB100C / UAD50C

MOT 10A DC24

MOT 10A ADC110

MOT 10A ADC220

UAB50S, UAB50H, UAB100R, UAB100S / UAD50S, UAD100R

MOT 10UA DC24

MOT 10UA ADC110

MOT 10UA ADC220

UCB50R, UCB100R, UCB100S / UCD100S

MOT 10UB DC24

MOT 10UB ADC110

MOT 10UB ADC220

UCB50H, UCB50L, UCB100H, UCB100L / UCD50H, UCD100H

MOT 10F DC24

MOT 10F ADC110

MOT 10F ADC220

UCB250R, UCB250S, UCB250N / UCD250S

MOT 20C DC24

MOT 20C ADC110

MOT 20C ADC220

UCB160H, UCB160L, UCB250H, UCB250L / UCD160H, UCD250H

MOT 20G DC24

MOT 20G ADC110

MOT 20G ADC220

UCB400R, UCB400S, UCB400H, UCB400L / UCD400S

MOT 40D DC24

MOT 40D ADC110

MOT 40D ADC220

MOT 68E DC24

MOT 68E ADC110

MOT 68E ADC220

MOT 80NE DC24

MOT 80NE ADC110

MOT 80NE ADC220

MOT 160NE AC2201)

MOT 12UP DC24

MOT 12UP ADC110

MOT 12UP ADC220

MOT 46NE DC24

MOT 46NE ADC110

MOT 46NE ADC220

MOT 12UP DC24

MOT 12UP ADC110

MOT 12UP ADC220

UCB630R, UCB630S, UCB630H, UCB630L,


UCB800R, UCB800S, UCB800H, UCB800L / UCD630S, UCD800S
UCB1000S, UCB1000L, UCB1250S, UCB1250L / UCD1000S, UCD1250S
UCB1600S
UPB100S, UPB100H, UPB100L, UPB100X, UPB160S, UPB160H, UPB160L, UPB160X,
UPB250S, UPB250H, UPB250L, UPB250X / UPD100S, UPD160S, UPD250S
UPB400S, UPB400H, UPB400L, UPB400X,
UPB630S, UPB630H, UPB630L, UPB630X / UPD400S, UPD630S
HBL103U, HBL103UM, HBL203U, HBL203UM,
HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ

Category

MCCB

MB

- Motor operator is not recommended for marine application.


1) MOT 160NE AC220 is not applicable for DC220V.

Molded Case Circuit Breaker_ 207

U-Series

Molded Case Circuit Breaker

Operating Accessories
| Mechanical interlock (MIF) |

[ Lock in OFF of left side breaker ]

Applicable MCCB
UAB30C, UAB30R, UAB50C, UAB50R,

[ Lock of two breaker ]

[ Lock in OFF of right side breaker ]

Order code
2 pole

3 pole

4 pole

MIF 10A 3

MIF 10A 4

MIF 10UA 3

MIF 10AU 4

MIF 10UF 3

MIF 10UF 4

MIF 10UF 3

MIF 10UF 3

MIF 10UF 4

MIF 20UG 3

MIF 20UG 3

MIF 20UG 4

MIF 40D 3

MIF 40D 3

MIF 40D 4

Category

UAB60C, UAB60R, UAB100C / UAD50C


UAB50S, UAB50H, UAB100R, UAB100S
/ UAD50S, UAD100R
UCB50R, UCB100R, UCB100S / UCD100S
UCB50H, UCB50L, UCB100H, UCB100L
/ UCD50H, UCD100H
UCB160H, UCB160L, UCB250R, UCB250S, UCB250N,
UCB250H, UCB250L / UCD160H, UCD250S, UCD250H
UCB400R, UCB400S, UCB400H, UCB400L
/ UCD400S
MCCB

UCB630R, UCB630S, UCB630H, UCB630L,


UCB800R, UCB800S, UCB800H, UCB800L

MIF 80E 3

MIF 80E 3

MIF 80E 4

MIF 12UP 3

MIF 12UP 4

MIF 46UP 3

MIF 46UP 4

MIF 12UP 3

MIF 12UP 4

/ UCD630S, UCD800S
UPB100S, UPB100H, UPB100L, UPB100X,
UPB160S, UPB160H, UPB160L, UPB160X,
UPB250S, UPB250H, UPB250L, UPB250X
/ UPD100S, UPD160S, UPD250S
UPB400S, UPB400H, UPB400L, UPB400X,
UPB630S, UPB630H, UPB630L, UPB630X
/ UPD400S, UPD630S
HBL103U, HBL103UM, HBL203U, HBL203UM,
HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ

208

MB

MCCB

| Padlock plate (PLD) |


Applicable MCCB

Order code

Category

UAB30C, UAB30R, UAB50C, UAB50R,


UAB50S, UAB50H, UAB60C, UAB60R,

PLD 10UA

UAB100C, UAB100R, UAB100S


/ UAD50C, UAD50S, UAD100R
UCB50R, UCB50H, UCB50L,
PLD 10UF

UCB100R, UCB100S, UCB100H, UCB100L


/ UCD50H, UCD100S, UCD100H
UCB160H, UCB160L, UCB250R, UCB250S,

PLD 20UG

UCB250N, UCB250H, UCB250L


/ UCD160H, UCD250S, UCD250H
UCB400R, UCB400S, UCB400H, UCB400L,
UCB630R, UCB630S, UCB630H, UCB630L,

PLD 40D

UCB800R, UCB800S, UCB800H, UCB800L

MCCB

MB

/ UCD400S , UCD630S , UCD800S


UCB1000S, UCB1000L, UCB1250S, UCB1250L

PLD 120NE

/ UCD1000S, UCD1250S
UPB100S, UPB100H, UPB100L, UPB100X,
UPB160S, UPB160H, UPB160L, UPB160X,
UPB250S, UPB250H, UPB250L, UPB250X,
UPB400S, UPB400H, UPB400L, UPB400X,
UPB630S, UPB630H, UPB630L, UPB630X

PLD 12UP

/ UPD100S, UPD160S, UPD250S, UPD400S,


UPD630S
HBL103U, HBL103UM, HBL203U, HBL203UM,
HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ

| Extension handle (THA) |


Applicable MCCB
B

Order code

Dimensions
(mm)
A
B

Category

UCB400R, UCB400S, UCB400H, UCB400L,


UCB630R, UCB630S, UCB630H, UCB630L,
UCB800R, UCB800S, UCB800H, UCB800L

THA 46D

42

40

THA 120NE

56

40

THA 160NE

60

50

THA 46UP

42

30

/ UCD400S, UCD630S, UCD800S


UCB1000S, UCB1000L, UCB1250S,
UCB1250L / UCD1000S, UCD1250S

A
Mounting hole

UCB1600S

MCCB MB

UPB400S, UPB400H, UPB400L, UPB400X,


UPB630S, UPB630H, UPB630L, UPB630X
Excessive force in ON and OFF may break the handle of breaker.

/ UPD400S, UPD630S

Molded Case Circuit Breaker_ 209

U-Series

Molded Case Circuit Breaker

Mounting Accessories

Mounting accessories enable easy installation, maintenances and remove of breakers.

DIN-rail adaptor

DRA

- Mounted on back side of UAB type breaker and


enables direct installation on 35mm DIN-rail

Mounting base

TDM

- Installed on back plate of panel and breaker can be


easily replaced or maintained without cable
disconnection

| DIN-rail adaptor (DRA) |


Applicable MCCB

UAB50S, UAB50H, UAB100R, UAB100S / UAD50S, UAD100R

210

Order code

DRA 10UA

Category

MCCB

MB

MCCB

| Mounting base (TDM) and components for plug-in mounting |


Switchboard application

Conductor
Mounting base (TDM, TDF)

Connection block at MCCB side

Circuit conductor

Mounting angle

Lead cable for signal accessories

Connection block (CBM, TYA) at mounting base side

The shape of mounting bases of each MCCB are not same as above. For exact appearances, please refer to "Characteristic Curves & Dimensions" from page 138-187.

For line side only


plug-in mounting

For both line & load side plug-in mounting


Applicable MCCB

UAB30C, UAB30R, UAB50C, UAB50R,


UAB60C, UAB60R, UAB100C / UAD50C
UAB50S, UAB50H, UAB100R, UAB100S
/ UAD50S, UAD100R
UCB50R, UCB50H, UCB50L, UCB100R,
UCB100S, UCB100H, UCB100L
/ UCD100S, UCD50H, UCD100H
UCB160H, UCB160L, UCB250R, UCB250S,
UCB250N, UCB250H, UCB250L
/ UCD160H, UCD250S, UCD250H
UCB400R, UCB400S, UCB400H, UCB400L
/ UCD400S
UCB630R, UCB630S, UCB630H, UCB630L,
UCB800R, UCB800S, UCB800H, UCB800L
/ UCD630S, UCD800S
UPB100S, UPB100H, UPB100L, UPB100X,
UPB160S, UPB160H, UPB160L, UPB160X,
UPB250S, UPB250H, UPB250L, UPB250X
/ UPD100S, UPD160S, UPD250S
UPB400S, UPB400H, UPB400L, UPB400X,
UPB630S, UPB630H, UPB630L, UPB630X
/ UPD400S, UPD630S
HBL103U, HBL103UM, HBL203U, HBL203UM,
HBL103UQ, HBL103UMQ,
HBL203UQ, HBL203UMQ

Mounting base
Order
Required
code
quantity

TDM 10AP

TDM 10BP

TDM 20CF

1EA

TDM 5BA

2EA

TDM 12NEP

Conn. block barrier

Contact Required
quantity

CBM 10AB 2

2C

1EA

CBM 10AB 3

3C

1EA

CBM 10AB 2

2C

1EA

CBM 10AB 3

3C

1EA

CBM 20C 2

2C

1EA

CBM 20C 5

5C

1EA

TYA 5/22)
TYA 5/52)

2C
5C

1EA
1EA

TYA 5/22)

2C

1EA

2EA

2EA

TDM 46NEP

Connection block
Order
code

1EA

TDM 4BA

TDM 12NEP

1)

TYA 5/52)

5C

1EA

CBM 26NE 6

6C

1EA

CBM 26NE 6

12C

2EA

CBM 26NE 6

6C

1EA

CBM 26NE 6

12C

2EA

CBM 26NE 6

6C

1EA

CBM 26NE 6

12C

2EA

1EA

1EA

1EA

Mounting base

Order
code

Required
quantity

Order
code

Required
quantity

CBM BARR

1EA

TDM 10AF

1EA

CBM BARR

1EA

TDM 10BF

1EA

TDM 20CF

1EA

TDM 4BA

1EA

TDM 5BA

1EA

TDM 12NEF

1EA

TDM 46NEF

1EA

TDM 12NEF

1EA

Category

MCCB

MB

- Plug-in mounting is applicable for 3P breaker.


1) Connection blocks (CBM, TYA) are required for internal signal accessory installation in both line & load side plug-in type 3P breaker.
2) TYA type connection blocks are to be installed with separate mounting angle. Separate mounting angle is not supplied.

Molded Case Circuit Breaker_ 211

U-Series

Molded Case Circuit Breaker

Mounting Accessories
TDF 10A

(Unit : mm)

[ Mounting base ]

[ Connection conductor ]

81
75
25

79
25

130

12.5
59

153.3

76.5

78.3

76.5

40.8

7.5

76.5

RH M6 screw+S/W+P/W

15 (Max:18)

[ Panel cut-out ]

2
25

25
76.8

9
RH M6 screw+S/W+P/W

SEC A-A

5-M4 tapped hole

41

21

36

50

8.5

20

13.5

21.5
3

22

22

TDF 10B

(Unit : mm)

[ Mounting base ]

[ Connection conductor ]

92

89

172.3

2
30

30
97.3

155

75

75
86.3

75

39.3

7.5

58.5

15 (Max:18)

RH M6 screw+S/W+P/W

12.5

30

30
9

[ Panel cut-out ]

SEC A-A

41

36

8.5

20

13.5

21.8 21
5-M4 tapped hole

21.5
3

212

27

27

MCCB

Distribution board application


Application

Applicable MCCB

Order code

Required
quantity

TDA 10AD ASSY


TDA 10AS
2RT-PH A
22S-PH10 A
BRAN-BARR A
CONN-PL A
ARC-PL A
TDA 10BD ASSY
TDA 10BS
2RT-PH
22S-PH10
BRAN-BARR
CONN-PL
ARC-PL
TDA 10AS
1R-PH A
1S-PH
1T-PH
1R-PH10 A
1S-PH10
1T-PH10
TDA 10BS
1R-PH
1S-PH
1T-PH
1R-PH10
1S-PH10
1T-PH10

1EA
2EA
2EA
1EA
2EA
1EA
1EA
1EA
2EA
2EA
1EA
2EA
1EA
1EA
1EA
1EA
1EA
1EA
1EA
1EA
1EA
1EA
1EA
1EA
1EA
1EA
1EA
1EA

Item
Mounting base unit

UAB50R, UAB50S,
UAB50H, UAB60R,
UAB100C,
UAB100R,
UAB100S

For
component
order

Mounting base
Branching conductor
Arc protection barrier

Connection plate

Double
mounting

Mounting base unit


UCB50H, UCB50L,
UCB100R,
UCB100S,
UCB100H,
UCB100L

For
component
order

Mounting base
Branching conductor
Arc protection barrier

Connection plate
Mounting base

UAB50R, UAB50S,
UAB50H, UAB60R,
UAB100C,
UAB100R,
UAB100S

5-63A
Branching
conductor
75-125A

Single
mounting

Mounting base
UCB50H, UCB50L,
UCB100R,
UCB100S,
UCB100H,
UCB100L

5-63A
Branching
conductor
75-125A

Mounting screw

M5 x L18 4EA for mounting angle


M5 x L12 1EA for bus bar
M4 x L8 2EA for brancing conductor
M4 x L25 4EA

M5 x L20 4EA for mounting angle


M5 x L12 1EA for bus bar
M4 x L8 2EA for brancing conductor
M4 x L25 4EA
M4 x L30 4EA for mounting angle

M5 x L12 1EA for bus bar


M4 x L8 1EA for brancing conductor

M5 x L32 4EA for mounting angle

M5 x L12 1EA for bus bar


M4 x L8 1EA for brancing conductor

Mounting base shall be connected to load side of MCCB.

M5xL12

Branching conductor

1S-PH
1S-PH10

M4xL8

M4xL8
M4xL8
M4xL8

M4xL8
M5xL12

M5xL12

M5xL12

M4xL8

M4xL8
M4xL8

2RT-PH
2RT-PH A

Connection plate
CONN-PL
CONN-PL A

22S-PH
22S-PH10
22S-PH A
22S-PH10 A

1R-PH
1R-PH10
1R-PH A
1R-PH10 A

1T-PH
1T-PH10

Arc protection barrier


ARC-PL
ARC-PL A

Molded Case Circuit Breaker_ 213

U-Series

Molded Case Circuit Breaker

Mounting Accessories
TDA 10AD / Double mounting

Load side terminal

50

M5 tapped hole
for branching conductor
(22S-PH10 A)
Connection plate
(CONN-PL A)

43.7

18.5

Mounting angle

87

12.5

25

[ Drilling holes for mounting ]

M4 nut+S/W+P/W
RH screw
M4xL18+S/W+P/W

M5 tapped hole
for branching conductor
(2RT-PH A)

25
4- 4.5 hole

Line

Arc protection barrier


(BRAN-BARR A)

28
6

87

50

Line

235

37

RH screw
M4xL25+S/W+P/W

43.3

179.5

Connection plate
(ARC-PL A)

63

Line

360

235

63

Line

hole
nting
5 mou
28

M5 tapped hole
for branching conductor
(2RT-PH A)

15

12.5

50

25
22

80

80

21

TDA 10AS / Single mounting

M5 tapped hole
for branching conductor
(1T-PH, 1T-PH10)

M5 tapped hole for


branching conductor
(1S-PH, 1S-PH10)

50

M4 nut+S/W+P/W

[ Drilling holes for mounting ]

12

Line

Mounting angle

33

RH M4xL10+S/W+P/W

Line

RH screw
M4xL30+S/W
24.2

80.8
162

115.3
87

18.5
27.3

18.5

M5 tapped hole
for branching conductor
(1R-PH A, 1R-PH10 A)

46.5

43.7

50

180

162

46.5

9
80.8

Line

43.3

4- 4.5 hole
50

15

4.5 mounting hole

25 21
80

214

22

80

Insulation plate 1.6t


(not supplied)

25

MCCB

TDA 10BD / Double mounting

[ Drilling holes for mounting ]

Load side terminal


M5 nut+S/W+P/W

RH screw
M5xL20+S/W+P/W
27.518.5

8.5

30

M5 tapped hole for


branching conductor
(2RT-PH)

M5 tapped hole for


branching conductor
(22S-PH10)

4- 5.5 hole
Mounting angle
Line

50

Connection plate
(CONN-PL)

Arc protection barrier


(BRAN-BARR)

99

27.5

2
50

M4 tapped hole for


branching conductor

49.3

Line
M5 tapped hole for
branching conductor
(2RT-PH)

248.5

27.5
40

RH screw
M4xL25+S/W+P/W

49.7

193.5

Connection plate
(ARC-PL)

27.5

65.5

385

248.5

65.5

Line

Line

Mounting angle

8.5

18.5

5.8 mounting hole

60

15
26

94

24.5

81

20

30

TDA 10BS / Single mounting

M5 tapped hole for


branching conductor
(1T-PH, 1T-PH10)

50
M5 nut+S/W+P/W

12
RH screw
M5xL32+S/W+P/W
16
18.5
10

191

99
18.5

49.7

1.5

46

50

191
M5 tapped hole for
branching conductor
(1R-PH, 1R-PH10)

27

10
5.8 mounting hole

26 20
24.5

81

172.5

49.3

95.3

8.5
Line

94

86.8

M4 tapped hole

Line

46

Line

[ Drilling holes for mounting ]

85.7

M5 tapped hole for


branching conductor
(1T-PH, 1T-PH10)

Mounting angle

30

5.5 hole

Insulation plate 1.6t


(not supplied)

Molded Case Circuit Breaker_ 215

U-Series

Molded Case Circuit Breaker

Terminal Accessories

Terminal accessories offers convenience of connection, high protection for safety.

Terminal bus bar

TBB

- Increases the distances


between terminals

Cage terminal block

CTB

- Offers easy and direct


connection of cables

Rear barrier

REAR-BR

- Enhance the insulation of


terminal

216

Terminal cover

TCF

- Prevents direct contact to


live terminal as well as
insertion of external
material

Interpole barrier

TQQ

- Increases the insulation


between poles

MCCB

| Terminal connection screws / standard components |


Type

Clamp screw

Pan head screw

Size

Applicable MCCB

M5

- UAB30C, UAB30R, UAB50C, UAB50R, UAB50S, UAB50H, UAB60C, UAB60R,


UAB100C (5-50A), UAB100R (15-50A), UAB100S (15-50A) / UAD50C, UAD50S
- UCB50R
- UBD30L, UBD30H, UMB30R, UMB30S, UMB30H, UMB50S, UMB50H,
UDB30S, UDB30H, UDB50S, UDB50H, UDB100S (15-50A), UDB100H (15-50A),
UGD30L, UGD30H, UMG30R, UMG30S, UMG30H, UMG50S, UMG50H,
UDG30S,UDG30H, UDG50S, UDG50H, UDG100S (15-50A), UDG100H (15-50A)

M8

- UAB100C (60-100A), UAB100R (60-100A), UAB100S (60-100A) / UAD100R


- UCB50H, UCB50L, UCB100R, UCB100S, UCB100H, UCB100L,
UCB160H, UCB160L, UCB250R, UCB250S, UCB250N, UCB250H, UCB250L
/ UCD50H, UCD100S, UCD100H, UCD160H, UCD250S, UCD250H
- UDB100S (60-100A), UDB100H (60-100A), UDG100S (60-100A), UDG100H (60-100A)
- UPB100S, UPB100H, UPB100L, UPB100X, UPB160S, UPB160H, UPB160L, UPB160X,
UPB250S, UPB250H, UPB250L, UPB250X / UPD100S, UPD160S, UPD250S
- HBL103U, HBL103UM, HBL203U, HBL203UM, HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ

M10

- UCB400R, UCB400S, UCB400H, UCB400L / UCD400S


- UPB400S, UPB400H, UPB400L, UPB400X, UPB630S, UPB630H, UPB630L, UPB630X
/ UPD400S, UPD630S

M12

- UCB630R, UCB630S, UCB630H, UCB630L, UCB800R, UCB800S, UCB800H, UCB800L


/ UCD630S, UCD800S

M12

- UCB1000S, UCB1000L, UCB1250S, UCB1250L / UCD1000S, UCD1250S

M13

- UCB1600S

Hexagon socket head


screw

Hexagon head screw

| Terminal bus bar (TBB) |


Order code
Applicable MCCB
UCB250R, UCB250S, UCB250N / UCD250S
UCB160H, UCB160L, UCB250H, UCB250L
/ UCD160H, UCD250H
UCB400R, UCB400S, UCB400H, UCB400L
/ UCD400S
UCB630R, UCB630S, UCB630H,UCB630L
/ UCD630S
UCB800R, UCB800S, UCB800H, UCB800L
/ UCD800S
UPB100S, UPB100H, UPB100L, UPB100X,
UPB160S, UPB160H, UPB160L, UPB160X,
UPB250S, UPB250H, UPB250L, UPB250X
/ UPD100S, UPD160S, UPD250S
UPB400S, UPB400H, UPB400L, UPB400X
/ UPD400S
UPB630S, UPB630H, UPB630L, UPB630X
/ UPD630S
HBL103U, HBL103UM, HBL203U, HBL203UM,
HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ

2 pole
(4EA/SET)

3 pole
(6EA/SET)

4 pole
(8EA/SET)

Mounting
Category
hole

TBB 20C 2

TBB 20C 3

TBB 20C 4

11

TBB 4S 2

TBB 4S 3

TBB 4S 4

13

TBB 6S 2

TBB 6S 3

TBB 6S 4

13

TBB 8S 2

TBB 8S 3

TBB 8S 4

13

[ 2 pole ]

MCCB
-

TBB 12NE 3

TBB 12NE 4

11

TBB 40NE 3

TBB 40NE 4

13

TBB 60NE 3

TBB 60NE 4

13

TBB 12NE 3

11

[ 3 pole ]

MB

[ 4 pole ]

Molded Case Circuit Breaker_ 217

U-Series

Molded Case Circuit Breaker

Terminal Accessories

| Cage terminal block (CTB) |

CTB 10A
CTB 10B
CTB 20C

CTB 40D
CTB 46UP

CTB 80E

Wire

Order code
Applicable MCCB

Connection
Cable
connector
(EA)

S( )

L( )

Tightening
torque
kgf-

CTB 10A 3S50 CTB 10A 4S50

1 X 5.5-50

14

60

CTB 10A 3S100 CTB 10A 4S100

1 X 5.5-50

14

60

3EA/SET

4EA/SET

Wire size

Category

UAB30C, UAB30R, UAB50C, UAB50R, UAB50S,


UAB50H, UAB60C(5-50A), UAB60R(5-50A),
UAB100C(5-50A), UAB100R(15-50A),
UAB100S(15-50A) / UAD50L, UAD50S
UAB60C(60A), UAB60R(60A), UAB100C(60-100A),
UAB100R(60-100A), UAB100S(60-100A) / UAD100R
UCB50R, UCB100R, UCB100S / UCD100S
UCB50H, UCB50L, UCB100H, UCB100L

CTB 10B 3S

CTB 10B 4S

1 X 8-50

14

60

CTB 20C 3S

CTB 20C 4S

1 X 14-120

19

140

CTB 40D 3S

CTB 40D 4S

2 X 60-120

30-60

353

CTB 80E 3S

CTB 80E 4S

3 X 85-160

30-60

353

CTB 12UP 3S CTB 12UP 4S

1 X 14-120

19

140

CTB 46UP 3S CTB 46UP 4S

2 X 60-185

30-60

353

CTB 12UP 3S CTB 12UP 4S

1 X 14-120

19

140

/ UCD50H, UCD100H
UCB250R, UCB250S, UCB250N / UCD250S
UCB160H, UCB160L, UCB250H, UCB250L
/ UCD160H, UCD250H
UCB400R, UCB400S, UCB400H, UCB400L
/ UCD400S
UCB630R, UCB630S, UCB630H, UCB630L,
UCB800R, UCB800S, UCB800H, UCB800L
/ UCD630S, UCD800S
UPB100S, UPB100H, UPB100L, UPB100X
/ UPD100S
UPB160S, UPB160H, UPB160L, UPB160X,
UPB250S, UPB250H, UPB250L, UPB250X
/ UPD160S, UPD250S
UPB400S, UPB400H, UPB400L, UPB400X
/ UPD400S
UPB630S, UPB630H, UPB630L, UPB630X
/ UPD630S
HBL103U, HBL103UM, HBL203U, HBL203UM
HBL203U, HBL203UM, HBL203UQ, HBL203UMQ

218

MCCB MB

MCCB

| Terminal cover (TCF) |

2 pole
Applicable MCCB

3 pole

Dimensions

Order
code

TCF 10AP 2

50

21.5

UCB50R, UCB100R, UCB100S / UCD100S

TCF 10BP 2

57

UCB250R, UCB250S, UCB250N / UCD250S

TCF 20CP 3 102


90

4 pole

Dimensions

Category

58.5

TCF 10AP 3

75

21.5

28.5

58.5

TCF 10BP 3

87

28.5

58.5 TCF 10BP 4

117

28.5

58.5

32.5

58.5

TCF 20CP 3

102

32.5

58.5 TCF 20CP 4

137

32.5

58.5

10

59

TCF 10FP 3

90

10

59

TCF 10FP 4

120

10

59

TCF 20GP 3 105

10

59

TCF 20GP 3

105

10

59

TCF 20GP 4

140

10

59

TCF 40D 3

190

120

100

TCF 40D 3

190

120

100

TCF 40D 4

234

120

100

TCF 80E 3

230

139

100

TCF 80E 3

230

139

100

TCF 80E 4

300

139

100

TCF 160NE 3 210

51

151

TCF 12UP 3

105

29.5

82.5 TCF 12UP 4

140

29.5

82.5

TCF 46UP 3

140

35

106.5 TCF 46UP 4

185

35

106.5

TCF 12UP 3

105

29.5

Order
code

Dimensions

Order
code

100

21.5

58.5

UAB30C, UAB30R, UAB50C, UAB50R,


UAB60C, UAB60R, UAB100C / UAD50C
UAB50S, UAB50H, UAB100R, UAB100S

58.5 TCF 10AP 4

/ UAD50S, UAD100R

UCB50H, UCB50L, UCB100H, UCB100L


/ UCD50H, UCD100H
UCB160H, UCB160L, UCB250H, UCB250L
/ UCD160H, UCD250H
UCB400R, UCB400S, UCB400H, UCB400L
/ UCD400S

TCF 10FP 3

UCB630R, UCB630S, UCB630H, UCB630L,


UCB800R, UCB800S, UCB800H, UCB800L

MCCB MB

/ UCD630S, UCD800S
UCB1600S
UPB100S, UPB100H, UPB100L, UPB100X,
UPB160S, UPB160H, UPB160L, UPB160X,
UPB250S, UPB250H, UPB250L, UPB250X
/ UPD100S, UPD160S, UPD250S
UPB400S, UPB400H, UPB400L, UPB400X,
UPB630S, UPB630H, UPB630L, UPB630X
/ UPD400S, UPD630S
HBL103U, HBL103UM, HBL203U,
HBL203UM, HBL103UQ, HBL103UMQ,

82.5

HBL203UQ, HBL203UMQ
For both line and load side of MCCB, 2EA shall be ordered.

| Rear barrier (REAR-BR) |


Order code

Applicable MCCB

Category
2 pole

3 pole

4 pole

UAB30C, UAB30R, UAB50L, UAB50R,


UAB50S,UAB50H, UAB60C, UAB60R,
UAB100C, UAB100R, UAB100S
/ UAD50C, UAD50S, UAD100R

REAR-BR 10A 2

REAR-BR 10A 3

UCB50R, UCB100R, UCB100S / UCD100S

REAR-BR 10B 2

REAR-BR 10B 3

UCB250R, UCB250S, UCB250N / UCD250S

REAR-BR 20C 3

REAR-BR 20C 3

REAR-BR 20C 4

MCCB MB

For both line and load side of MCCB, 2EA shall be ordered.

Molded Case Circuit Breaker_ 219

U-Series

Molded Case Circuit Breaker

Terminal Accessories
| Interpole barrier (TQQ) |

Applicable MCCB

Order code

Required quantity for both


Description
(Quantity supplied as line and load side of MCCB
standard components
2 pole
3 pole
4 pole
of 3 pole MCCB)

Dimensions
Category
A

UAB30C, UAB30R, UAB50C, UAB50R,


UAB60C, UAB60R, UAB100C / UAD50C

TQQ 10A 3PLINE

2EA/SET

50

53

UCB50R, UCB100R, UCB100S / UCD100S

TQQ 10B 3PLINE

2EA/SET

50

53

UCB250R, UCB250S, UCB250N / UCD250S

TQQ 20C 3PLINE

2EA/SET

50

53

TQQ 12FG 3PLINE

2EA/SET

51

53

TQQ 4BA 3PLINE

2EA/SET

120

97

TQQ 5BA 3PLINE

2EA/SET

110

95

TQQ 80NE 3P

2EA/SET

125

92

TQQ 160NE 3P

4EA/SET

102

68

TQQ 12NE 3P

4EA/SET

71

54.5

TQQ 46NE 3P

4EA/SET

122

103

TQQ 12NE 3P

4EA/SET

71

54.5

TQQ 10A 3PLINE

2EA/SET

50

53

UAB50S, UAB50H, UAB100R, UAB100S


/ UAD50S, UAD100R

UCB50H, UCB50L, UCB100H, UCB100L,


UCB160H, UCB160L, UCB250H, UCB250L
/ UCD50H, UCD100H, UCD160H, UCD250H
UCB400R, UCB400S, UCB400H, UCB400L
/ UCD400S
UCB630R, UCB630S, UCB630H, UCB630L,
UCB800R, UCB800S, UCB800H, UCB800L
/ UCD630S, UCD800S
UCB1000S, UCB1000L, UCB1250S, UCB1250L
/ UCD1000S, UCD1250S
UCB1600S
UPB100S, UPB100H, UPB100L, UPB100X,
UPB160S, UPB160H, UPB160L, UPB160X,
UPB250S, UPB250H, UPB250L, UPB250X
/ UPD100S, UPD160S, UPD250S
UPB400S, UPB400H, UPB400L, UPB400X,
UPB630S, UPB630H, UPB630L, UPB630X
/ UPD400S, UPD630S
HBL103U, HBL103UM, HBL203U, HBL203UM,
HBL103UQ, HBL103UMQ,
HBL203UQ, HBL203UMQ
UDB30S, UDB30H, UDB50S, UDB50H,
UDB100S, UDB100H, UDG30S, UDG30H,
UDG50S, UDG50H, UDG100S, UDG100H

220

MCCB MB

MCCB

Portable Test Equipment


| MCCB trip unit tester |
MCCB trip unit tester (MCCB OCR TESTER) can test LTD and STD (below 600%) function of trip unit in the field

MCCB OCR TESTER

Order code
Rated
voltage

input

AC100-230V

output

DC 9V

Dimension

W320 x H115 x D265 mm

Weight

2.7 kg

Standard kit

Tester, DC9V adaptor, connector

Applicable MCCB

- UCB1000S, UCB1000L, UCB1250S, UCB1250L


- UPB100S, UPB100H, UPB100L, UPB100X,
UPB160S, UPB160H, UPB160L, UPB160X,
UPB250S, UPB250H, UPB250L, UPB250X,
UPB400S, UPB400H, UPB400L, UPB400X,
UPB630S, UPB630H, UPB630L, UPB630X

Molded Case Circuit Breaker_ 221

Technical Information

U-Series

Molded Case Circuit Breaker

Current Setting for UPB type and UCB 1000-1600 type


| UPB100, UPB160, UPB250 / Thermal magnetic type |
Protection characteristics and current setting
Rated current [In] (A)
Rated current
setting [Ir] (A)

LTD

15

In x

16

20

25

30

32

40

50

60

63

75

80 100 125 150 160 175 200 225 250

0.8

12

16

24

32

40

48

50

60

64

80 100 120

140 160 180 200

0.9

14

18

27

36

45

54

57

68

72

90 113 135

158 180 203 225

1.0

15

40

50

60

63

75

80 100 125 150 160 175 200 225 250

Fixed (In x 10)

16

20

25

30

32

150 160 200 250 300 320 400 500 600 630 750 800 1000 1250 1500 1600 1750 2000 2250 2500
20%

Tolerance

UPB100: MTM-10-JF, UPB160: MTM-16-JF, UPB250: MTM-25-JF

Trip unit
Instantaneous
1)
current setting Adjustable
[Ii] (A)
Tolerance

INST

In x 5-6-7-8-9-10
In x 5-9: 30%, 20%

In x 10:

Trip unit

20%

UPB160: MTM-16-JJ, UPB250: MTM-25-JJ

1) Adjustable instantataneous is available for UPB160 and UPB250.

1 LTD current [Ir] setting knob


2 INST current [Ii] setting knob

| UPB100, UPB160, UPB250 / Electronic type |


Protection characteristics and current setting
Model

UPB100

UPB160

UPB250

MOR-10-ES

MOR-16-ES

MOR-25-ES

125

160

250

50, 55, 63, 70, 80, 90, 100, 115, 125

63, 70, 80, 90, 100, 110, 125, 140, 160

Trip unit
Rated (CT) current [In] (A)
LTD
STD
INST
PTA

Rated current setting [Ir] (A)


Long time setting [tr]

100, 110, 125, 140, 160, 175, 200, 225, 250

6.25 sec. at Ir x 600%

Tolerance

Short time pick-up current [Isd] (A)

Ir x NON-2-3-4-5-6-7-8-9-10

Tolerance

Time delay setting [tsd]

0.05-0.1-0.2-0.3 sec. at definite time-limit section

Tolerance

In x 1100%

Tolerance

Ir x 90%

Tolerance

Instantaneous current setting


[Ii] (A)
Pre-trip alarm current [Ip] (A)

20%
+50ms, -20ms
20%

The default values are underlined. Please check and adjust the setting condition of each characteristic before use.

1 LTD current [Ir] setting knob


2 STD current [Isd] setting knob
3 Pick-up LED
4 STD time [tsd] setting knob
5 Frequency selection switch
6 Tester connection port

224

MCCB

| UPB400, UPB630 / Electronic type |


Protection characteristics and current setting
Model
Trip unit

UPB400

UPB630

MOR-40-ES2) / MOR-40-GS

MOR-63-ES2) / MOR-63-GS

400
0.8
0.85
0.9
0.95
1.0
Io Ir
0.63
200
215
225
240
250
Rated current setting [Ir] (A)
0.8
255
270
290
300
320
1.0
320
340
360
380
400
2-4-6-8-12 sec. at Ir x 600%
Long time setting [tr]
Short time pick-up current [Isd] (A) Ir x NON-2-4-6-8-10
0-0.1-0.2-0.3 sec. at definite time-limit section
Time delay setting [tsd]1)
Instantaneous current setting
In x NON-3-6-8-10-11
[Ii] (A)
In x NON-0.2-0.3-0.4
Ground fault current [Ig] (A)
0.1-0.2-0.3-0.4-0.8 sec. at definite time-limit section
Ground fault delay setting [tg]
Ir x 0.9
Pre-trip alarm current [Ip] (A)

Rated (CT) current [In] (A)

LTD

STD
INST
GFT2)
PTA

Io Ir
0.63
0.8
1.0

0.8
320
400
500

630
0.85
340
430
540

0.9
0.95
1.0
360
380
400
450
480
500
570
600
630
Tolerance
20%
Tolerance
15%
Tolerance +50ms,-20ms
Tolerance
Tolerance
Tolerance
Tolerance

20%
15%
+50ms, -20ms
10%

- The default values are underlined. Please check and adjust the setting condition of each characteristic before use.
1) I2t characteristic can be ON or OFF by adjusting the [tsd] knob .
2) GFT protection is option and not applicable for MOR-40-ES and MOR-63-ES trip unit.

1
2
3
4
5
6

LTD current [Ir] setting knob


LTD time [tr] setting knob
STD current [Isd] setting knob
STD time [tsd] setting knob
I2t ON-OFF indication
INST current [Ii] setting knob

GFT current [Ig] setting knob


GFT time [tg] setting knob
9 Tester connection port
10 Frequency selection switch
11 Base current [Io] setting knob
12 PTA [Ip] LED
7
8

| UCB1000, UCB1250 / Electronic type |


Protection characteristics and current setting
MCCB
Trip unit

UCB1000

UCB1250

MOR-100-ES2) / MOR-100-GS

MOR-125-ES2) / MOR-125-GS

1000
0.8
0.85
0.9
0.95
1.0
Io Ir
0.63
505
535
565
600
630
Rated current setting [Ir] (A)
0.8
640
680
720
760
800
1.0
800
850
900
950
1000
2-4-6-8-12 sec. at Ir x 600%
Long time setting [tr]
Short time pick-up current [Isd] (A) Ir x NON-2-4-6-8-10
0-0.1-0.2-0.3 sec. at definite time-limit section
Time delay setting [tsd]1)
Instantaneous current setting
In x NON-3-6-8-10-11
[Ii] (A)
In x NON-0.2-0.3-0.4
Ground fault current [Ig] (A)
0.1-0.2-0.3-0.4-0.8 sec. at definite time-limit section
Ground fault delay setting [tg]
Ir x 0.9
Pre-trip alarm current [Ip] (A)

Rated (CT) current [In] (A)

LTD

STD
INST
GFT2)
PTA

Io Ir
0.63
0.8
1.0

0.8
630
800
1000

1250
0.85
0.9
0.95
1.0
670
710
750
790
850
900
950
1000
1060
1125
1190
1250
Tolerance
20%
Tolerance
15%
Tolerance +50ms,-20ms
Tolerance
Tolerance
Tolerance
Tolerance

20%
15%
+50ms, -20ms
10%

- The default values are underlined. Please check and adjust the setting condition of each characteristic before use.
1) I2t characteristic can be activate by adjusting [tsd] knob .
2) GFT protection is option and not applicable for MOR-100-ES and MOR-125-ES trip unit.

1
2
3
4
5
6

LTD current [Ir] setting knob


LTD time [tr] setting knob
STD current [Isd] setting knob
STD time [tsd] setting knob
I2t ON-OFF indication
INST current [Ii] setting knob

GFT current [Ig] setting knob


GFT time [tg] setting knob
9 Tester connection port
10 Frequency selection switch
11 Base current [Io] setting knob
12 PTA [Ip] LED
7
8

Molded Case Circuit Breaker_ 225

U-Series

Molded Case Circuit Breaker

Current Setting for UPB type and UCB 1000-1600 type


| Current setting procedure / Electronic type 400-1250A|
In

In

Io

Io

Ir

Ir

Isd

Isd

570

Ir

Ir 3420

Ii

Ii
In 5040

In

Ig

Ig
In

In

In

In

Io

Io

Ir

Ir

190

1250

1125

Isd

Isd
Ir 6750

Ir

Ii

Ii
In

10000

In

Ig

Ig
In 375

In

| UCB1600 / Electronic type |


Protection characteristics and current setting
Rated (CT) current [In] (A)
0.4

0.5

0.6

0.7

0.8

0.9

0.95

1.0

640

800

960

1120

1250

1440

1520

1600

LTD

Rated current setting [I1] (A)

INST

Instantaneous current setting [Ii] (A)

I1 x 2-3-4-5-6-7-8-10

Red light

0A

Green light

0.4 x In

Yellow light

I1

LED
indication

226

1600
In x

MCCB

Selection By Application
| Model selection for transformer |
AC220V
Capacity of Three phase
transformer
Single phase
(kVA)

30

50

16

70-100

30

Breaking capacity of MCCB


(kA)(Sym)

150-300

50

2.5

500-750

150

10
UAB30R

UAB50C

UAB50R

UAB60C

UAB60R

35

42 50

65

UAB50H, UCB50R

UAB100C
MCCB

2000

300

25

UAB30C

1500

85

UCB50H

UAB100S, UCB100R

100

125

UCB50L

UCB100S

UCB100H

UCB100L

UPB100H, UPB100L

UCB250H

UCB250L

UPB250H, UPB250L

UCB250R

UCB250S

UCB250N

UCB400R

UCB400S

UCB400H

UCB630R

UCB630S, UCB630H

UPB400S, UPB400H,
UPB400L, UPB400X
UPB630S, UPB630H,
UPB630L, UPB630X

UCB800R

UCB800S, UCB800H

UCB800L

UCB400L

UCB1000L, UCB1250L

UCB1000S, UCB1250S

AC460V
Capacity of transformer
(kVA)

50

Breaking capacity of MCCB


(kA)(Sym)

1.5

75-200

300

750

10

UAB30C

UAB30R

UAB50C

UAB50R

UAB60C

UAB60R

UAB100C

18

25

2000

35

UAB50H, UCB50R

42

UCB50H

UAB100S, UCB100R

UCB250R

MCCB

1500

UCB250S

UCB400R

3000

50

65

75

85

100

UCB50L

UCB100S

UCB100H

UCB100L

UPB100H

UCB250N

UCB250H

UCB250L

UPB250H

UPB250L

UCB400L

UPB400L, UPB400X

UCB400S

UCB400H

UPB100L

UCB630R

UCB630S

UCB630H

UCB630L UPB630L, UPB630X

UCB800R

UCB800S

UCB800H

UCB800L

UCB1000S, UCB1250S

UCB1000L,UCB1250L

| Rated current selection for condenser |


Rated current of MCCB (A)
Capacity of
condenser
(kVAR)

Single phase (1 pole)


AC220V

Three phase (3 pole)


AC440V

AC220V

AC440V

50Hz

60Hz

50Hz

60Hz

50Hz

60Hz

50Hz

60Hz

60

50

30

30

40

50

30

20

10

75

60

40

40

50

50

30

30

15

100

100

60

50

60

60

40

40

20

175

175

75

60

100

75

50

40

25

200

200

100

100

100

100

50

50

30

225

225

100

100

175

150

60

60

40

400

400

150

125

200

200

100

75

50

400

400

175

175

225

225

100

100

75

600

500

300

300

400

400

150

150

100

800

800

400

400

400

400

225

225

150

1000

1000

600

500

600

600

300

300

200

1200

800

800

800

800

400

400

300

1000

1000

600

600

400

800

-The start-up inrush current is about 10 times of rated current.


-The mentioned value can be applied to maximum rated current of MCCB.
-The rated current of MCCB is recommended to be 150% of rated current of condenser.

Molded Case Circuit Breaker_ 227

U-Series

Molded Case Circuit Breaker

Selection By Application
| Model selection for lighting and heater |
The maximum operational current shall not exceed 80% of MCCB rated current.
Breaking capacity (kA)
Maximum
operational Rated current sym
2.5
5
current (A) of MCCB (A)
12

15

16

20

24

30

32

40

40

50

48

60

60

75

10

25

UAB30R

UAB30C

35

50

65

UAB50H,

UCB50H

UCB50R
UAB50C

UAB50R

UAB60C

UAB60R

UAB100S,
UCB100R

UAB100C

85

100

125

UCB50L

UCB100S

UCB100H

UCB100L

UPB100H,
UPB100L

UCB250H

UCB250L

UPB250H,
UPB250L,

80

100

100

125

120

150

140

175

160

200

180

225

200

250

240

300

280

350

320

400

400

500

500

630

560

700

640

800

800

1000

UCB1000S

UCB1000L

1000

1250

UCB1250S

UCB1250L

UCB250R

UCB250S

UCB250N

UCB400R

UCB400S

UCB400H

UPB400S,
UPB400H,
UPB400L,
UPB400X

UCB400L

UCB630R

UCB630S, UCB630H

UPB630S, UPB630H,
UPB630L, UPB630X

UCB800R

UCB800S, UCB800H

UCB800L

AC460V
Breaking capacity (kA)
Maximum
operational Rated current sym
1.5
5
current (A) of MCCB (A)

228

10

18

25

35

42

50

65

75

85

100

12

15

16

20

24

30

32

40

40

50

48

60

60

75

80

100

100

125

120

150

140

175

160

200

180

225

200

250

240

300

280

350

320

400

400

500

500

630

560

700

640

800

800

1000

UCB1000S

UCB1000L

1000

1250

UCB1250S

UCB1250L

UAB30R

UAB30C

UAB50H

UCB50H

UCB50R
UAB50C

UAB50R

UAB60C

UAB60R

UAB100C

UAB100S

UCB100S UCB100H UCB100L

UPB100H

UPB100L

UCB250S UCB250N UCB250H UCB250L

UPB250H

UPB250L

UAB100R

UCB250R

UCB400R

UCB50L

UCB400H

UCB400L

UCB630R

UCB630S

UCB630H UCB630L

UCB800R

UCB800S

UCB800H UCB800L

UCB400S

UPB400L,
UPB400X
UPB630L,
UPB630X

MCCB

| Rated current selection for motor and other loads |


Circuit diagram

Condition
IM1

IM

Permissible current of cable1) [Iw]

IL

Iw

IM+ IL

IM2

IN

IW

IL1

IM >

50A

IL

Iw 1.25 IM+ IL

IL2
IM : Load current of motor
IL : Load current of other loads

50A

IM

IL

Iw 1.1 IM+ IL

Rated current of MCCB [In]

Less value among IN 3 IM+ IL or


IN 2.5Iw.
In case of Iw 100A, when calculated
value is not matched with the rated
current of MCCB,
it is recommended to select the
right above value.

Molded Case Circuit Breaker_ 229

U-Series

Molded Case Circuit Breaker

Selection By Application
Rated current of MCCB for AC220V three phase induction motor
Maximum
Total
capacity of operational
current 0.75 / 1.5 /
motors
(below kW) (below A)
4.8
8
3
4.5
6.3
8.2
12
15.7
19.5
23.2
30
37.5
45
52.5
63.7
75
86.2
97.5
112.5
125
150
175
220

15
20
30
40
50
75
90
100
125
150
175
100
150
300
350
400
450
500
600
700
800

20
30
40
50
60
100
100
125
150
175
200
225
300
350
400
500
500
600
700
800
900

30
30
40
50
60
100
100
125
150
175
200
225
300
350
400
500
500
600
700
800
900

Capacity of the biggest motor:

Capacity of motor (kW) /


Full load current (A)

2.2 /
11.1

3.7 /
17.4

5.5 /
26

7.5 /
34

11 /
48

15 / 18.5 / 22 /
65
79
93

30 /
125

37 /
160

45 /
190

5/
230

75 /
310

90 /
360

110 / 132 /
440 500

30
30
40
50
60
100
100
125
150
175
200
225
300
350
400
500
500
600
700
800
900

50
50
50
60
100
100
125
150
175
200
225
300
350
400
500
500
600
700
800
900

60
75
75
100
100
125
150
175
200
225
300
350
400
500
500
600
700
800
900

100
100
100
100
125
150
175
200
225
300
350
400
500
500
600
700
800
900

125
125
125
150
175
200
225
300
350
400
500
500
600
700
800
900

150
150
150
150
175
200
225
300
350
400
500
500
600
700
800
900

300
300
300
300
350
400
500
500
600
700
800
900

400
400
400
400
400
500
500
600
700
800
900

500
500
500
500
500
500
600
700
800
900

500
500
500
500
500
600
700
800
900

600
600
700
700
700
800
900

700
700
700
800
800
900

1000
1000
1000
900

90 /
180

110 / 132 /
220 250

175
175
175
200
200
225
300
350
400
500
500
600
700
800
900

200
225
225
225
225
300
350
400
500
500
600
700
800
900

1000
1000
1000

-The rated currents are for MCCBs.


-The mentioned values are applicable when MCCB trips within 10 sec. at 600% of full load current and the start-up inrush current is within 1700% of full load current.
-Above selection is also applied in case that several loads starts up at same time.

Rated current of MCCB for AC440V three phase induction motor


Maximum
Total
capacity of operational
current 0.75 / 1.5 /
motors
(below kW) (below A)
2.4
4

3
4.5
6.3
8.2
12
15.7
19.5
23.2
30
37.5
45
52.5
63.7
75
86.2
97.5
112.5
125
150
175
200
250
300
350
400
450
500

7.5
10
15
20
25
38
45
50
63
75
88
100
125
150
175
200
225
250
300
350
400
500
600
700
700
900
1000

Capacity of the biggest motor:

2.2 /
5.5

3.7 /
8.7

5.5 /
13

7.5 /
17

11 /
24

Capacity of motor (kW) /


Full load current (A)

15 / 18.5 / 22 /
32
39
46

30 /
62

37 /
80

45 /
95

55 /
115

75 /
155

15
15
15
15
15
15
30
20
20
20
30
40
30
30
30
30
40
50
30
30
30
30
40
50
50
50
50
50
50
50
60
75
50
50
50
50
50
50
60
75
100
60
60
60
60
60
60
60
75
100 125
75
75
75
75
75
75
75
100 100 125
100 100 100 100 100 100 100 100 100 125 150
100 100 100 100 100 100 100 100 100 125 150 175
125 125 125 125 125 125 125 125 125 125 150 175 225
150 150 150 150 150 150 150 150 150 150 150 200 225 250
175 175 175 175 175 175 175 175 175 175 175 200 225 250
200 200 200 200 200 200 200 200 200 200 200 200 225 300 350
225 225 225 225 225 225 225 225 225 225 225 225 225 300 350 400
250 250 250 250 250 250 250 250 250 250 250 250 250 300 350 400
300 300 300 300 300 300 300 300 300 300 300 300 300 300 350 400 500
350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 400 500 500
400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 500 500 500
500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500
600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600
700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700
800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800
800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200

-The rated currents are for MCCBs.


-The mentioned values are applicable when MCCB trips within 10 sec. at 600% of full load current and the start-up inrush current is within 1700% of full load current.
-Above selection is also applied in case that several loads starts up at same time.

230

MCCB

Insulation Distance

Insulation plate

Upper plate of panel


Side plate of panel

B1

B1
B2

B1
B2

B2

A
D

Direct cable
connection

Taping

Bus bar
connection

Applicable MCCB

Rear or plug-in
connection

Distances
A

B1

B2

75

50

30

from 0

25

80

50

30

from 0

25

80

60

50

from 0

25 (?)

80

60

50

from 0

40

100

100

80

from 0

80

50

120

80

from 0

80

80

50

30

from 0

10

100

100

70

from 0

10

120

100

80

from 0

80

UAB30C, UAB30R, UAB50C, UAB50R, UAB50S, UAB50H,


UAB60C, UAB60R, UAB100C, UAB100R, UAB100S
/ UAD50C, UAD50S, UAD100R
UCB50R, UCB50H, UCB50L,
UCB100R, UCB100S, UCB100H, UCB100L
/ UCD50H, UCD100R, UCD100H
UCB250R
UCB160H, UCB160L,
UCB250S, UCB250N, UCB250H, UCB250L
/ UCD160H, UCD250S, UCD250H
UCB400R, UCB400S, UCB400H, UCB400L,
UCB630R, UCB630S, UCB630H, UCB630L,
UCB800R, UCB800S, UCB800H, UCB800L
/ UCD400S, UCD630S, UCD800S
UCB1000S, UCB1000L, UCB1250S, UCB1250L, UCB1600S
/ UCD1000S, UCD1250S
UPB100S, UPB100H, UPB100L, UPB100X / UPD100S
UPB160S, UPB160H, UPB160L, UPB160X,
UPB250S, UPB250H, UPB250L, UPB250X
/ UPD160S, UPD250S
UPB400S, UPB400H, UPB400L, UPB400X,
UPB630S, UPB630H, UPB630L, UPB630X
/ UPD400S, UPD630S
HBL103U, HBL103UM, HBL103UQ, HBL103UMQ

80

50

30

from 0

10

HBL203U, HBL203UM, HBL203UQ, HBL203UMQ

100

100

70

from 0

10

Molded Case Circuit Breaker_ 231

U-Series

Molded Case Circuit Breaker

Cascading Table
| AC240V |
Downstream

Upstream

UAB-C
Recognition
category

UAB-R

UAB/UCB-S

UAB100C UCB250R UCB400R UCB630R UCB800R UAB100S UCB250S UCB400S UCB630S UCB800S
Model
Rated
current
(A)

5-100

125-250

250-400

500,630

700,800

15-100

125-250

250-400

500,630

700,800

Breaking
capacity
[Icu]
(kA r.m.s)

25

35

35

50

50

50

50

50

100

100

UAB30C

3-30

10

25

30

30

35

35

35

UAB50C

5-50

10

25

30

30

35

35

35

UAB60C

5-60

10

25

30

30

35

35

35

UAB100C

5-100

25

35

35

42

42

42

42

65

65

UAB30R

5-30

25

35

35

42

42

42

42

42

65

65

UAB50R

5-50

25

35

35

42

42

42

42

42

65

65

UAB60R

5-60

25

35

35

42

42

42

42

42

65

65

UAB100R

15-100

42

50

50

50

50

75

75

UCB50R

15-50

50

85

85

UCB100R

15-100

50

85

85

UCB250R

125-250

35

65

65

UCB400R

250-400

35

UAB50S

15-50

42

UAB100S

15-100

UAB/UCB-S UCB100S

UAB-C

UAB/UCB-R

50

50

65

50
75

75

50

85

85

15-100

65

85

85

UCB250S

125-250

50

85

85

UCB400S

250-400

50

UAB50H

15-50

50

UCB50H

15-50

85

100

100

15-125

85

100

100

UCB250H

125-250

85

100

100

UCB400H

250-400

85

UCB50L

15-50

100

UCB100L

15-125

100

UCB250L

125-250

100

UCB400L

250-400

125

UPB100H

15-125

130

UPB250H

100-250

130

UPB100L

15-125

150

UPB250L

100-250

150

UAB/UCB-H UCB100H

UCB-L

UPB-H

UPB-L

232

50

50

50

50

50

50

85

100

MCCB

UCB-H

UCB-L

UPB-H

UPB-L

UCB100H UCB250H UCB400H UCB630H UCB800H UCB100L UCB250L UCB400L UCB630L UCB800L UPB100H UPB250H UPB100L UPB250L
15-125

125-250

250-400

500,630

700,800

15-125

125-250

250-400

500,630

700,800

15-125

100-250

15-125

100-250

85

85

85

100

100

100

100

125

125

125

130

130

150

150

50

50

50

50

50

65

50

50

50

50

50

65

50

50

50

50

50

65

65

65

65

65

65

85

85

85

65

65

65

65

65

65

65

85

85

85

85

85

100

100

65

65

65

65

65

65

65

85

85

85

85

85

100

100

65

65

65

65

65

65

65

85

85

85

85

85

100

100

75

75

75

75

75

100

100

100

85

85

85

85

100

100

100

100

85

85

85

85

100

100

100

100

65

65

65

100

100

100

85

100

100
100

100

130
130

100

130
130

100

65
100

100

100

100

100

85

100

125

125

125

100

130

85

85

100

125

125

125

100

130

85

85

125

125

125

85

85

75

75

85

85

85

85

85
85

100

100

125

125

125

100

125

125

125

100

125

125

125

100

100
100

100

130

130

125

85

100

100

130

130

130

130

130

130

150

150

130

150

125

100
125

125

125

125

125

125

125

125

125

130

130

150

150
150

130

150

150
150

Molded Case Circuit Breaker_ 233

U-Series

Molded Case Circuit Breaker

Cascading Table
| AC415V |
Downstream

Upstream

UAB-C
Recognition
category

UAB-R

UAB/UCB-S

UAB100C UCB250R UCB400R UCB630R UCB800R UAB100S UCB250S UCB400S UCB630S UCB800S
Model
Rated
current
(A)

5-100

125-250

250-400

500,630

700,800

15-100

125-250

250-400

500,630

700,800

Breaking
capacity
[Icu]
(kA r.m.s)

10

18

30

45

45

30

25

42

65

65

18

18

30

30

UAB30C

3-30

10

7.5

10

10

10

UAB50C

5-50

10

7.5

10

10

10

UAB60C

5-60

10

7.5

10

10

10

UAB100C

5-100

10

14

14

14

14

UAB30R

5-30

10

14

14

14

14

18

18

18

30

30

UAB50R

5-50

10

14

14

14

14

18

18

18

30

30

UAB60R

5-60

10

14

14

14

14

18

18

18

30

30

UAB100R

15-100

25

30

35

35

35

42

42

UCB50R

15-50

25

30

35

35

35

42

42

UCB100R

15-100

25

30

35

35

35

42

42

UCB250R

125-250

18

30

35

35

30

35

35

UCB400R

250-400

30

UAB50S

15-50

25

UAB100S

15-100

UAB/UCB-S UCB100S

UAB-C

UAB/UCB-R
30

50

35
30

35

42

42

35

35

42

42

45

45

42

50

50

35

35

35

42

42

35

35

30

35

15-100

36

UCB250S

125-250

25

UCB400S

250-400

42

UAB50H

15-50

30

35

35

UCB50H

15-50

42

45

15-125

42

UCB250H

125-250

42

UCB400H

250-400

65

UCB50L

15-50

UCB100L

30

30

65

45
42

42

42

45

50

50

45

45

50

50

45

45

50

50

50

65

65

15-125

50

65

65

UCB250L

125-250

50

65

65

UCB400L

250-400

100

UPB100H

15-125

100

UPB250H

100-250

100

UPB100L

15-125

130

UPB250L

100-250

130

UAB/UCB-H UCB100H

UCB-L

UPB-H

UPB-L

234

MCCB

UCB-H

UCB-L

UPB-H

UPB-L

UCB100H UCB250H UCB400H UCB630H UCB800H UCB100L UCB250L UCB400L UCB630L UCB800L UPB100H UPB250H UPB100L UPB250L
15-125

125-250

250-400

500,630

700,800

15-125

125-250

250-400

500,630

700,800

15-125

100-250

15-125

100-250

42

42

65

85

85

50

50

100

100

100

100

100

130

130

14

14

18

25

25

25

14

14

18

25

25

25

14

14

18

25

25

25

18

30

30

30

30

35

35

35

18

18

30

30

30

30

30

35

35

35

35

35

42

42

18

18

30

30

30

30

30

35

35

35

35

35

42

42

18

18

30

30

30

30

30

35

35

35

35

35

42

42

35

42

50

50

35

50

50

50

35

42

50

50

42

50

50

50

35

42

50

50

42

50

50

50

35

42

42

42

42

42

35

42

35

42

50

50

42

45

50

42

50
42

42

42

50

50

50

50
50

42

50

50

50

50

50

65

65

65

50

65

65

65

50

75

75

75

65

65

50

50

50

50

50

50

50

50

50

85

75
42

50

50

50

50
35

50

45

50

50

50

50

65

65

65

50

50

65

65

60

75

75

50

50

85

85

85

85

85

85

85

60

75

75

50

85

85

85

60

75

75

85

85

85

85

85

100

85
65

85

85

100

100

100

65

85

85

100

100

100

65

85

85

100

100

100

100

100

100

100

100
100

130

130
130

Molded Case Circuit Breaker_ 235

U-Series

Molded Case Circuit Breaker

Cascading Table
| AC440V |
Downstream

Upstream

UAB-C
Recognition
category

UAB-R

UAB/UCB-S

UAB100C UCB250R UCB400R UCB630R UCB800R UAB100S UCB250S UCB400S UCB630S UCB800S
Model
Rated
current
(A)

5-100

125-250

250-400

500,630

700,800

15-100

125-250

250-400

500,630

700,800

Breaking
capacity
[Icu]
(kA r.m.s)

10

18

25

35

35

25

25

35

50

50

14

14

21

21

UAB30C

3-30

7.5

7.5

7.5

7.5

7.5

UAB50C

5-50

7.5

7.5

7.5

7.5

7.5

UAB60C

5-60

7.5

7.5

7.5

7.5

7.5

UAB100C

5-100

10

10

10

10

10

UAB30R

5-30

10

10

10

10

10

14

14

14

21

21

UAB50R

5-50

10

10

10

10

10

14

14

14

21

21

UAB60R

5-60

10

10

10

10

10

14

14

14

21

21

UAB100R

15-100

21

25

30

30

25

30

30

35

UCB50R

15-50

25

35

35

35

35

42

UCB100R

15-100

25

35

35

35

35

42

UCB250R

125-250

18

25

25

25

35

35

UCB400R

250-400

25

UAB50S

15-50

21

UAB100S

15-100

25

UAB/UCB-S UCB100S

15-100

35

UCB250S

125-250

25

UCB400S

250-400

35

UAB50H

15-50

25

UCB50H

15-50

UAB-C

UAB/UCB-R

42

35
30

30

35

35

35

42

42

50

35

42

42

50

35

50

42

50

50

15-125

42

50

50

UCB250H

125-250

42

50

50

UCB400H

250-400

50

UCB50L

15-50

50

UCB100L

15-125

50

UCB250L

125-250

50

UCB400L

250-400

85

UPB100H

15-125

85

UPB250H

100-250

85

UPB100L

15-125

100

UPB250L

100-250

100

UAB/UCB-H UCB100H

UCB-L

UPB-H

UPB-L

236

25

25

30

30

35

35

35

35

35

35

25

25

35

35

MCCB

UCB-H

UCB-L

UPB-H

UPB-L

UCB100H UCB250H UCB400H UCB630H UCB800H UCB100L UCB250L UCB400L UCB630L UCB800L UPB100H UPB250H UPB100L UPB250L
15-125

125-250

250-400

500,630

700,800

15-125

125-250

250-400

500,630

700,800

15-125

100-250

15-125

100-250

42

42

50

65

65

50

50

85

85

85

85

100

85

130

10

10

14

18

18

18

10

10

14

18

18

18

10

10

14

18

18

18

14

25

25

25

25

30

30

30

14

14

25

25

25

25

25

30

30

30

30

35

30

35

14

14

25

25

25

25

25

30

30

30

30

35

30

35

14

14

25

25

25

25

25

30

30

30

30

35

30

35

30

35

35

35

30

35

35

35

45

45

35

35

35

35

40

45

45

45

45

45

35

35

35

35

40

45

45

45

45

45

30

30

30

30

30

30

45

45

35

40

30

35

35

35

35

38

40

42

50
38

38

38

42

42

42

40

45

50

50

50

45

50

50

50

45

55

55

55

50

50

40

40

45

45

45

35

45

45

55

55
35

45

42

40
30

45

40

45

45

42

42

45

45

45

35

45

35

45

50

55

55

50

50

65

65

65

65

65

65

65

50

55

55

50

65

65

65

65

65

50

55

55

65

65

65

85

85

85

85

85

65
65

65

85

85

85

65

65

85

85

85

65

65

85

85

85

85

85

Molded Case Circuit Breaker_ 237

Order Information

MCCB

Order Information
Fixed thermal & fixed instantaneous / UAB, UCB, UPB type

UPB250X

3P

Type

Code

Code

Pole

UAB

UAB30C
..
UAB100S

2P1)

2 pole

3P

UCB

UCB50R
..
UCB800L

4P2)

UPB

UPB100S
..
UPB250X

For the applicable breaker,


please refer to page 14-25.

Code

40/45

3 pole
4 pole

B2)

Bus bar

50

1) "T5" (50C) is not applicable to hydraulic


magnetic type UAB30C, UAB30R, UAB50C,
UAB50R, UAB60C, UAB60R & UAB100C.

00

Terminal connection
Direct mounting
Screw

Compensating temperature

T51)

Code

S1)

1) "2P" (2 pole) is
not applicable
to UPB.
2) "4P" (4 pole) is
not applicable
to UAB30.

T4

T4

Plug-in mounting3)
X4)

for both line & load side


without connection block

P5)

for both line & load side


with connection block

F6)

for line side only

1) "S" (screw terminal connection) is


default for whole range.
2) "B" (bus bar terminal connection) is
available for 250AF and above breaker.
- Bus bar TBB can be ordered
separately.
For details, please refer to page 217.
3) Plug-in mounting is available for
3pole breaker only.
- Mounting base TDM and components
for plug-in mounting shall be ordered
separately.
For details, please refer to page 211.
4) "X" (plug-in mounting for both line &
load side without connection block)
is recommended when the internal
signal accessory does not need to be
wired through the mounting base.
5) "P" (plug-in mounting for both line
& load side with connection block) is
recommended when the internal signal
accessory shall be plug-in also. Internal
signal accessory shall be ordered
along with breaker for wiring before
ex-work.
6) "F" (plug-in mounting for line side
only) is recommended when the
screw terminal connection is
required at load side.

00

00250

Code

Internal accessory

Code

Frequency

001)

without

50/60Hz

Code

Rated current

00003
..
00800

3A
..
800A

Auxiliary switch (AUX)


10
20

AUX 1C
AUX 2C
Trip alarm switch (ALT)

01

ALT 1C

Auxiliary switch (AUX)


& Trip alarm switch (ALT)
11

AUX 1C & ALT 1C

21

AUX 2C & ALT 1C

For the applicable rated current


to each breaker, please refer to
page 14-25.

1) Default for whole range


- For the applicable accessory to each
breaker, please refer to page 138-167.
- For "P" type plug-in mounting, internal
accessory shall be ordered.
- Internal accessory can be ordered
separately.
For details, please refer to page 194-195.

Code

Internal accessory

001)

without
Shunt trip (SHT)

S1

SHT AC110V

S2

SHT AC220V

S3

SHT AC380V

S4

SHT AC440V

S5

SHT DC24V

S6

SHT DC110V

Under voltage trip (UVT)


U1

UVT AC110V

U2

UVT AC220V

U3

UVT AC380V

U4

UVT AC440V

U5

UVT DC24V

U6

UVT DC110V

1) Default for whole range


- For the applicable accessory to each
breaker, please refer to page 138-167.
- For "P" type plug-in mounting, internal
accessory shall be ordered.
- Internal accessory can be ordered
separately.
For details, please refer to page
194-195.

Molded Case Circuit Breaker_ 239

U-Series

Molded Case Circuit Breaker

Order Information
Adjustable thermal - UAB, UCB, UPB type

UPB250X
Type

UAB

3P

Code

Code

Pole

UAB50S

2P1)

2 pole

UAB50H

3P

3 pole

UAB100R

4P

4 pole

B2)

1) "2P" (2 pole) is
available for UCB
only.

UCB50H

UPB

T4
T5

X4)

00

Terminal connection
Direct mounting

Bus bar

Rated current

00005
..
00800

5A
..
800A

Shunt trip (SHT)

SHT AC220V

for both line & load side


without connection block

S3

SHT AC380V

S4

SHT AC440V

for line side only

50

Code

without
SHT AC110V

F6)

40/45

Internal accessory

001)

S2

UCB100R
..
UCB800L

1) "S" (screw terminal connection) is


default for whole range.
2) "B" (bus bar terminal connection) is
available for 250AF and above breaker.
- Bus bar TBB can be ordered
separately. For details, please refer
to page 217.
3) Plug-in mounting is available for 3
pole breaker only.
- Mounting base TDM and components
for plug-in mounting shall be ordered
separately. For details, please refer
to page 211.
4) "X" (plug-in mounting for both line &
load side without connection block)
is recommended when the internal
signal accessory does not need to be
wired through the mounting base.
5) "P" (plug-in mounting for both line
& load side with connection block) is
recommended when the internal signal
accessory shall be plug-in also. Internal
signal accessory shall be ordered
along with breaker for wiring before
ex-work.
6) "F" (plug-in mounting for line side
only) is recommended when the
screw terminal connection is
required at load side.

S5

SHT DC24V

S6

SHT DC110V

For the applicable rated current


to each breaker, please refer to
page 14-25.

Code

Frequency

50/60Hz

Under voltage trip (UVT)


U1

UVT AC110V

U2

UVT AC220V

U3

UVT AC380V

U4

UVT AC440V

Code

Instantaneous
characteristic

U5

UVT DC24V

Fixed instantaneous

UVT DC110V

H1)

Adjustable instantaneous

U6

1) Default for whole range


- For the applicable accessory to
each breaker, please refer to page
138-167.
- For "P" type plug-in mounting,
internal accessory shall be ordered.
- Internal accessory can be ordered
separately. For details, please refer to
page 194-195.

Code

Internal accessory

001)

without
Auxiliary switch (AUX)

10
20

AUX 1C
AUX 2C
Trip alarm switch (ALT)

01

ALT 1C

Auxiliary switch (AUX)


& Trip alarm switch (ALT)
11

AUX 1C & ALT 1C

21

AUX 2C & ALT 1C

1) Default for whole range


For details, please refer to page 194-195.
- For the applicable accessory to each
breaker, please refer to page 138-167.
- For "P" type plug-in mounting, internal
accessory shall be ordered.
- Internal accessory can be ordered
separately.

240

00250

Code

S1

for both line & load side


with connection block

Compensating temperature

Plug-in mounting3)

P5)

UPB100S
..
UPB250X

00

Screw

UCB50L

For the applicable breaker,


please refer to page 14-25.

Code

Code
S1)

UAB100S

UCB

T4

1) "H" (adjustable instantaneous) is


available for UPB160 & UPB250.

MCCB

Order Information
Electronic / UCB, UPB type

UPB630X
Type

UCB

3P

Code

Code

Pole

UCB1000S

3P

3 pole

UCB1000L

4P1)

4 pole

UCB1250S

1) "4P" (4 pole) is
not applicable
to UCB1600S.

UCB1250L

Code

UPB100S
..
UPB630X

For the applicable breaker,


please refer to page 14-25.

Code

Protection characteristic

ES1)

LTD, STD, INST trip & PTA

EG2)

LTD, STD, INST, GFT trip & PTA

1) "ES" (LTD, STD, INST trip & PTA) is default


for whole range.
- STD trip & PTA are not applicable to
UCB1600S.
2) "EG" (LTD, STD, INST, GFT trip & PTA) is
available for UCB1000, UCB1250, UPB400 &
UPB630.

00

Terminal connection
Direct mounting

S1)

Screw

B2)

Bus bar
Plug-in mounting3)

X4)

UCB1600S
UPB

ES

for both line & load side


with connection block

P5)

for both line & load side


without connection block

F6)

for line side only

1) "S" (screw terminal connection) is


default for whole range.
2) "B" (bus bar terminal connection) is
default for UCB.
- "B" (bus bar terminal connection)
is available for 250AF and above
breaker.
- Bus bar TBB for UPB can be
ordered separately.
For details, please refer to page 217.
3) Plug-in mounting is available for 3
pole breaker only.
- Mounting base TDM and components
for plug-in mounting shall be ordered
separately.
For details, please refer to page 211.
4) "X" (plug-in mounting for both line &
load side without connection block)
is recommended when the internal
signal accessory does not need to be
wired through the mounting base.
5) "P" (plug-in mounting for both line &
load side with connection block) is
recommended when the internal
signal accessory shall be plug-in also.
Internal signal accessory shall be
ordered along with breaker for wiring
before ex-work.
6) "F" (plug-in mounting for line side
only) is recommended when the
screw terminal connection is
required at load side.

00

00630

Code

Internal accessory

Code

Frequency

001)

without

C1)

50/60Hz

50Hz

60Hz

Auxiliary switch (AUX)


10

AUX 1C

20

AUX 2C

30

AUX 3C

40

1) Only UCB1600S is
common use for both
50Hz & 60Hz ("C").

AUX 4C
Trip alarm switch (ALT)

01

ALT 1C

Auxiliary switch (AUX)


& Trip alarm switch (ALT)
11

AUX 1C & ALT 1C

21

AUX 2C & ALT 1C

31

AUX 3C & ALT 1C

Code

Rated current

00100
..
01600

100A
..
1600A

For the applicable rated


current to each breaker,
please refer to page 14-25.

1) Default for whole range


- For the applicable accessory to
each breaker, please refer to page
156-167.
- For "P" type plug-in mounting,
internal accessory shall be ordered.
- Internal accessory can be ordered
separately.
For details, please refer to page
194-195.

Code
001)

Internal accessory
without
Shunt trip (SHT)

S1

SHT AC110V

S2

SHT AC220V

S3

SHT AC380V

S42)

SHT AC440V

S5

SHT DC24V

S6

SHT DC110V

Under voltage trip (UVT)


U12)

UVT AC110V

U2

UVT AC220V

U3

UVT AC380V

U42)

UVT AC440V

U52)

UVT DC24V

U62)

UVT DC110V

1) Default for whole range


- For the applicable accessory to
each breaker, please refer to page
156-167.
- For "P" type plug-in mounting,
internal accessory shall be ordered.
- Internal accessory can be ordered
separately.
For details, please refer to page
194-195.

Molded Case Circuit Breaker_ 241

U-Series

Molded Case Circuit Breaker

Order Information
Motor protection / UPB type

UPB250L
Type

UPB

3P

Code

Code

Pole

UPB100H

3P

3 pole

MP
Code
S1)

UPB100L

00

Terminal connection
Direct mounting

X3)

UPB250L
For the applicable breaker,
please refer to page 15 & 26.

Code

Trip mechanism

MP

Adjustable instantaneous only

for both line & load side


without connection block

P4)

for both line & load side


with connection block

F5)

for line side only

1) "S" (screw terminal connection) is


default for whole range.
- Bus bar TBB can be ordered
separately. For details, please refer
to page 217.
2) Plug-in mounting is available for 3
pole breaker only.
- Mounting base TDM and components
for plug-in mounting shall be ordered
separately. For details, please refer
to page 211.
3) "X" (plug-in mounting for both line &
load side without connection block)
is recommended when the internal
signal accessory does not need to be
wired through the mounting base.
4) "P" (plug-in mounting for both line &
load side with connection block) is
recommended when the internal
signal accessory shall be plug-in also.
Internal signal accessory shall be
ordered along with breaker for wiring
before ex-work.
5) "F" (plug-in mounting for line side
only) is recommended when the
screw terminal connection is
required at load side.

00250

Code

Internal accessory

Code

Frequency

001)

without

50/60Hz

Code

Rated current

002.5
..
00225

2.5A
..
225A

Screw
Plug-in mounting2)

UPB250H

00

Auxiliary switch (AUX)


10
20

AUX 1C
AUX 2C
Trip alarm switch (ALT)

01

ALT 1C

Auxiliary switch (AUX)


& Trip alarm switch (ALT)
11

AUX 1C & ALT 1C

21

AUX 2C & ALT 1C

For the applicable rated


current to each breaker,
please refer to page 15 & 26.

1) Default for whole range


- For the applicable accessory to
each breaker, please refer to page
168-169.
- For "P" type plug-in mounting,
internal accessory shall be ordered.
- Internal accessory can be ordered
separately.
For details, please refer to page
194-195.

Code
001)

Internal accessory
without
Shunt trip (SHT)

S1

SHT AC110V

S2

SHT AC220V

S3

SHT AC380V

S4

SHT AC440V

S5

SHT DC24V

S6

SHT DC110V

Under voltage trip (UVT)


U1

UVT AC110V

U2

UVT AC220V

U3

UVT AC380V

U4

UVT AC440V

U5

UVT DC24V

U6

UVT DC110V

1) Default for whole range


- For the applicable accessory to
each breaker, please refer to page
168-169.
- For "P" type plug-in mounting,
internal accessory shall be ordered.
- Internal accessory can be ordered
separately.
For details, please refer to page
194-195.

242

MCCB

Order Information
Q-class (for nuclear power plant application) / HBL type

HBL203UMQ
Type

3P

T4

00

00225

Code

Code

Pole

Code

Internal accessory

Code

Frequency

HBL103U

3P

3 pole

001)

without

50/60Hz

Code

Rated current

002.5
..
00225

2.5A
..
225A

Auxiliary switch (AUX)

HBL103UQ
HBL103UM
HBL103UMQ
HBL

00

HBL203U
HBL203UQ
HBL203UM
HBL203UMQ

For the applicable breaker,


please refer to page 15 & 27.

Code Compensating temperature & trip mechanism


T41)

40/45C

T51)

50C

MP2)

Adjustable instantaneous only

1) Compensating temperature is applicable to fixed thermal


& fixed instantaneous type; HBL103U, HBL103UQ,
HBL203U, HBL203UQ
2) Adjustable instantaneous only trip mechanism is
applicable to motor protection type; HBL103UM,
HBL103UMQ, HBL203UM, HBL203UMQ

Code

Terminal connection
Direct mounting

Screw

10
20

AUX 1C
AUX 2C
Trip alarm switch (ALT)

01

ALT 1C

Auxiliary switch (AUX)


& Trip alarm switch (ALT)
11

AUX 1C & ALT 1C

21

AUX 2C & ALT 1C

For the applicable rated current


to each breaker, please refer to
page 15 & 27.

1) Default for whole range


- For the applicable accessory to
each breaker, please refer to page
170-177.
- Internal accessory can be ordered
separately.
For details, please refer to page
194-195.

Bus bar TBB can be ordered separately.


For details, please refer to page 217.

Code

Internal accessory

001)

without
Shunt trip (SHT)

S1

SHT AC110V

S2

SHT AC220V

S3

SHT AC380V

S4

SHT AC440V

S5

SHT DC24V

S6

SHT DC110V

Under voltage trip (UVT)


U1

UVT AC110V

U2

UVT AC220V

U3

UVT AC380V

U4

UVT AC440V

U5

UVT DC24V

U6

UVT DC110V

1) Default for whole range


- For the applicable accessory to each
breaker, please refer to page 170-177.
- Internal accessory can be ordered
separately. For details, please refer
to page 194-195.

Molded Case Circuit Breaker_ 243

U-Series

Molded Case Circuit Breaker

Order Information
Switch disconnector / UAD, UCD, UPD type

UPD630S
Type

UAD

3P

Code

Code

Pole

UAD50C

3P

3 pole

DS
Code

UAD50S

S1)

UAD100R

B2)

UCD100H
UCD160H

00

Terminal connection
Direct mounting

Protection
Code characteristic
DS

Switch
disconnector

X4)

Bus bar

for both line & load side


without connection block

P5)

for both line & load side


with connection block

F6)

for line side only

UCD250S
UCD

UCD250H
UCD400S
UCD630S
UCD800S
UCD1000S
UCD1250S
UPD100S
UPD160S

UPD

UPD250S
UPD400S
UPD630S

For the applicable breaker,


please refer to page 16-31.

00

1) "S" (screw terminal connection) is


default for UAD, UCB50-800 & UPD.
2) "B" (bus bar terminal connection) is
default for UCD1000 & UCD1250.
- "B" (bus bar terminal connection)
is available for 250AF and above
breaker.
- Bus bar TBB can be ordered
separately. For details, please refer
to page 217.
3) Plug-in mounting is available for 3
pole breaker only.
- Mounting base TDM and components
for plug-in mounting shall be ordered
separately. For details, please refer
to page 211.
4) "X" (plug-in mounting for both line &
load side without connection block)
is recommended when the internal
signal accessory does not need to be
wired through the mounting base.
5) "P" (plug-in mounting for both line
& load side with connection block)
is recommended when the internal
signal accessory shall be plug-in
also. Internal signal accessory shall
be ordered along with breaker for
wiring before ex-work.
6) "F" (plug-in mounting for line side
only) is recommended when the
screw terminal connection is
required at load side.

00630

Code

Internal accessory

Code

Frequency

001)

without

50/60Hz

Code

Rated current

00050
..
01250

50A
..
1250A

Screw

Plug-in mounting3)

UCD50H
UCC100S

Auxiliary switch (AUX)


10
20

AUX 1C
AUX 2C
Trip alarm switch (ALT)

01

ALT 1C

Auxiliary switch (AUX)


& Trip alarm switch (ALT)
11

AUX 1C & ALT 1C

21

AUX 2C & ALT 1C

For the applicable rated current


to each breaker, please refer to
page 15 & 27.

1) Default for whole range


- For the applicable accessory to
each breaker, please refer to page
138-167.
- For "P" type plug-in mounting,
internal accessory shall be ordered.
- Internal accessory can be ordered
separately.
For details, please refer to page 194-195.

Code

Internal accessory

001)

without
Shunt trip (SHT)

S1

SHT AC110V

S2

SHT AC220V

S3

SHT AC380V

S4

SHT AC440V

S5

SHT DC24V

S6

SHT DC110V

Under voltage trip (UVT)


U1

UVT AC110V

U2

UVT AC220V

U3

UVT AC380V

U4

UVT AC440V

U5

UVT DC24V

U6

UVT DC110V

1) Default for whole range


- For the applicable accessory to
each breaker, please refer to page
138-167.
- For "P" type plug-in mounting,
internal accessory shall be ordered.
- Internal accessory can be ordered
separately.
For details, please refer to page 194195.

244

MCCB

Order Information
Miniature type - Molded case circuit breaker / UBD, UMB, UDB type

UDB100H
Type

UMB

3P

Code

Code

Pole

UMB30R

2P

2 pole

UMB30S

3P1)

3 pole

UMB30H
UMB50S

T4

S
Code

00

Terminal
connection

00

Code

Internal accessory

Code

Frequency

00

without

50/60Hz

Code

Rated current

00003
..
00100

3A
..
100A

Screw

1) "3P" (3 pole) is
available for
UDB only.

UMB50H
Code Compensating temperature

UDB30S

T4

UDB30H
UDB

00100

40/45C

For the applicable rated current


to each breaker, please refer to
page 16 & 32.

UDB50S
UDB50H

Code

Internal accessory

UDB100S

00

without

UDB100H

Internal accessory for UDB can be


ordered separately.
For details, please refer to page
181 & 194.

For the applicable breaker,


please refer to page 16 & 32.

Miniature type - Earth leakage circuit breaker / UGD, UMG, UDG type

UDG100H
Type

UMG

3P

Code

Code

Pole

UMG30R

2P

2 pole

UMG30S

3P1)

3 pole

UMG30H
UMG50S

G4

S
Code

00

Terminal
connection

00

00100

Code

Internal accessory

Code

Frequency

00

without

50/60Hz

Screw

1) "3P" (3 pole) is
available for
UDB only.

UMG50H
UDG30S
UDG30H
UDG

UDG50S
UDG50H

Code

Code

Internal accessory

Code

Rated current

15mA

00

without

G4

30mA

3A
..
100A

G51)

100mA

Internal accessory for UDG can be


ordered separately.
For details, please refer to page 186 &
194.

00003
..
00100

G3

Rated residual current

1) "G5" (100mA) is available for UDB only.

For the applicable rated current


to each breaker, please refer to
page 16 & 33.

UDG100S
UDG100H
For the applicable breaker,
please refer to page 16 & 33.

Molded Case Circuit Breaker_ 245

U-Series

Molded Case Circuit Breaker

Order Information
Fixed instantaneous only / UCB type

UPB250X

3P

Type

Code

Code

Pole

3P

3 pole

UCB

UCB50R
..
UCB800L

For the applicable breaker,


please refer to page 14-22.

T4
Code
S1)
B2)

X4)

00

Terminal connection
Direct mounting

00

Internal accessory

Code

Rated current

without

00003
..
00800

3A
..
800A

Shunt trip (SHT)


S1

SHT AC110V

S2

SHT AC220V

for both line & load side


without connection block

S3

SHT AC380V

S4

SHT AC440V

Trip mechanism

P5)

for both line & load side


with connection block

MO

Magnetic only

F6)

for line side only

1) "S" (screw terminal connection) is


default for whole range.
2) "B" (bus bar terminal connection) is
available for 250AF and above breaker.
- Bus bar TBB can be ordered
separately. For details, please refer
to page 217.
3) Plug-in mounting is available for 3
pole breaker only.
- Mounting base TDM and components
for plug-in mounting shall be rdered
separately.
For details, please refer to page 211.
4) "X" (plug-in mounting for both line &
load side without connection block) is
recommended when the internal
signal accessory does not need to be
wired through the mounting base.
5) "P" (plug-in mounting for both line &
load side with connection block) is
recommended when the internal
signal accessory shall be plug-in
also. Internal signal accessory shall
be ordered along with breaker for
wiring before ex-work.
6) "F" (plug-in mounting for line side
only) is recommended when the
screw terminal connection is required
at load side.

For the applicable rated current


to each breaker, please refer to
page 14-22.

S5

SHT DC24V

Code

Frequency

S6

SHT DC110V

50/60Hz

Under voltage trip (UVT)


U1

UVT AC110V

U2

UVT AC220V

U3

UVT AC380V

Code

Instantaneous
characteristic

U4

UVT AC440V

10 x In

U5

UVT DC24V

12 x In

U6

UVT DC110V

15 x In

1) Default for whole range


- For the applicable accessory to
each breaker, please refer to page
142-155.
- For "P" type plug-in mounting,
internal accessory shall be ordered.
- Internal accessory can be ordered
separately.
For details, please refer to page
194-195.

Code

Internal accessory

001)

without
Auxiliary switch (AUX)

10
20

AUX 1C
AUX 2C
Trip alarm switch (ALT)

01

ALT 1C

Auxiliary switch (AUX)


& Trip alarm switch (ALT)
11

AUX 1C & ALT 1C

21

AUX 2C & ALT 1C

1) Default for whole range


- For the applicable accessory to
each breaker, please refer to page
142-155.
- For "P" type plug-in mounting,
internal accessory shall be ordered.
- Internal accessory can be ordered
separately.
For details, please refer to page 194195.

246

001)

Plug-in mounting3)

Code

00250

Code

Screw
Bus bar

Handling Instruction | Inspection and Maintenance

MCCB

Handling Instruction
| Storage |
Do not expose to corrosive gases.
Do not expose to harmful gases including sulfur, ammonia and so on.
Do not expose to high humidity for a long period.
Do not expose to direct sunlight for a long period.
Store at -20 to +60 without dust and humidity.
Keep the handle in OFF position.

| Transportation |
Do not drop or apply shock
during transportation.
These can cause
malfunctions in the
breaker.

Hold the breaker body for


transportation. Do not hold
terminal bus bar or
external lead cable of
accessories.

| Standard operating condition for normal performance |


Ambient temperature

-5

- +40

the average temperature for 24 hours shall not exceed 35

Relative humidity

45 - 85%

Vibration & shock

without excessive vibration and shock

Altitude
Surrounding

up to 2,000m
without excessive water vapor, oil vapor, smoke, dust, salts and corrosive materials

| Installation and connection |

Keep away from direct sunlight.

Avoid any vibration or shock.

High temperatures can cause malfunctions.

If vibration or shock is expected, install


breaker with shock absorber.

Do not cover the terminal part


completely for arc exhaust.

Do not take off the black insulation


plate in back side of breaker.

Otherwise the breaking capacity may


be decreased.

Otherwise insulation shall be decreased or


not secured.

Keep away from dust or metal


pieces.
When any work that accompanies dust
or metal cutting is required, please
cover the breaker first.

Molded Case Circuit Breaker_ 249

U-Series

Molded Case Circuit Breaker

Handling Instruction
| Installation and connection |

Tighten the terminal screws to


proper torque specified in manual.

Do not apply lubricant on terminal


parts.

The loose connection may cause


overheating, and excessive torque may
damage screws and terminal parts.

The lubricant lets screws loose and


overheating occurs.

Insulate exposed conductors.


To prevent short-circuit, be sure to insulate
exposed conductors by interpole barrier,
terminal cover, insulating tube, insulating
tape and so on.

Insulating
supporter

Do not modify the shape of studs or


terminal accessories.
Excessive force to stud and terminal
accessories should also be avoided.

Fix each conductor in parallel.


Short-circuit current can occur
electromagnetic force between conductors,
so each conductor is required to fixed firmly
in parallel.

[Electromagnetic force per 1m conductor at 3 phase short-circuit]


Short -circuit current
/ Internal power
factor (kA)

Reverse feeding of earth leakage


circuit breaker is not allowed.
In case of reverse feeding, power is
supplied to circuit even the breaker trips,
and it shall damage trip coil.

(Unit : N [kgf])

Distance between conductors


10cm

20cm

10/0.4

490/50

245/25

18/0.3

1863/190

932/95

25/0.2

4412/450

2206/225

35/0.23

8630/880

4315/440

42/0.2

12455/1270

6277/635

50/0.2

17652/1800

8826/900

65/0.2

29910/3050

14955/1525

85/0.2

51190/5220

25595/2510

100/0.2

70804/7220

35402/3610

125/0.2

110815/11300

55408/5650

| Connection of earth leakage circuit breaker |

250

Single phase three line circuit

Single phase two line circuit

Parallel connection is not allowed.

Power line shall be connected to both side


poles of breaker, and neutral line to
middle pole.

Circuit shall be connected to both side


poles of breaker, and middle pole shall not
be connected.

Parallel connection causes current


unbalance, malfunction and trip coil
damage.

MCCB

Inspection and Maintenance


| Initial inspection |
Please check the following prior to breaker operation.
Check point
Terminal part shall be clean from dust, metal pieces and so on.
Breaker shall not have any crack or damage.
There should be non condensation on terminal parts.
Insulation resistance should be more than 5M
Terminal screws shall be tightened with specified torque.

| Dielectric test |
The test shall be done in these conditions.
Main circuit
Rated insulation voltage (Ui)
Ui
AC300V

Secondary and control circuit


Test voltage

AC300V

AC2000V

Ui

AC2500V

AC600V

Rated insulation voltage (Uis)


Uis
AC60V

Test voltage
AC1000V

AC60V
Uis

2Uis + AC1000V (Max. AC1500V)

AC60V

Test for earth leakage circuit breaker


Insulation resistance test

Dielectric test

Handle position

Handle position

Test
Measuring parts

ON

OFF

ON

OFF

Charging parts and earth


R and S phase, S and T phase
R and T phase

Line side
Load side

Power and line side terminal

Insulation resistance test


- Please use AC500V insulation resistance tester.
- Do not measure between R and T phase. Measuring does not cause damage unless AC1000V is applied.
- The measured resistance value shall be almost 0 .

Dielectric test
- Do not apply test voltage, if test voltage is applied by mistake, the breaker can not be used.

Molded Case Circuit Breaker_ 251

U-Series

Molded Case Circuit Breaker

Inspection and Maintenance


| Periodic inspection |
In order to maintain the performance of breaker and prevent the unpredicted accident,
the inspection shall be accompanied after installation and operation.
- Once after one month of operation, thereafter as below.

Circumstance

Inspection cycle after installation


within 10 years :
Clean air, no humidity

once 2-3 year

more than 10 years : once a year


more than 15 years : once 6 month

Normal

within 10 years :
Dust but no corrosive gas

once a year

more than 10 years : once 6 month


more than 15 years : once a month

Sulfurous gas, salinity, vapor


Bad
Excessive corrosive gas

within 5 years :

once 6 year

more than 5 years :

once a month

once a month

| Inspection and processing after breaking of fault current |


If there is no pollution in arc exhaust parts and no other abnormality, the breaker can be re-used.
When carbonizing symptom is found around arc exhaust parts, please measure insulation resistance. If the
resistance value is more than 5M , no dielectric breakdown at withstand test voltage and no excessive
temperature rise of terminal parts, then the breaker can be re-used.
If the handle part is carbonized or there is metallic melting in internal of breaker, please replace it with a new one.

252

MCCB

| Troubleshooting |
In case of any abnormality during breaker operation, please handle it as below.
For cases not mentioned in below, please contact us.

Molded case circuit breaker


Symptom and possible cause

Overheating

Inferior
dielectric

Inability of
operation

High temperature of
terminal part
Damage in insulation
part of terminal

Troubleshooting

Loose connection between terminal and conductor

Tighten screws with specified torque

Heating by resistance increase of conductor

Replace with a new breaker

Heating from connection part between terminal bus bar and breaker

Tighten screws with specified torque

High temperature of
breaker body

Heating by resistance increase of conductor


Loose internal assembly screws
Increase of current density from cable disconnection

Replace with a new breaker

Abnormal voltage of
load side

Excessive contact abrasion


Foreign substances on contact
Corrosion of conductor by excessive ON-OFF or
corrosive gas

Replace with a new breaker

Inability of reset after trip

OFF the breaker after manual reset

Inability of ON and
RESET

Trip at under rated


current

Frequent trip

Non-energized UVT

Apply the power

Insufficient cooling of trip unit

Reset the breaker after cooling down

Corrosion, damage or deformation of bimetal


Abnormality or damage in mechanism
Exhaustion of durability
Contact melting by excessive high breaking current

Replace with a new breaker

High ambient temperature

Cool down ambient temperature by


ventilation or others

Heating by loose terminal screw connection

Tighten screws with specified torque

Heating from inside of breaker

Replace with a new breaker

Smaller connection conductor than specified size

Use the specified size of conductor or adjust


the rated current

Trip at start-up inrush current


Trip at change-over in star-delta operation
Instantaneous trip at reverse feeding
Trip at operational
current

Instantaneous trip at high start-up inrush current

Adjust the instantaneous trip setting or


replace with a higher current breaker

Replace with a higher current breaker

Instantaneous trip at long start-up inrush current

Malfunction

Non trip at the current


higher than specified

Short-circuit between motors

Repair or replace motors

Misconnection of SHT, UVT control circuit

Inspect circuit wiring

Current breaking by line side fuse or low coordination with


primary breaker

Redesign the coordination between


equipment

Extremely low ambient temperature

Out of rated frequency

Adjust the current according to temperature


derating curve
Apply the rated frequency or adjust breaker
frequency knob

Molded Case Circuit Breaker_ 253

U-Series

Molded Case Circuit Breaker

Inspection and Maintenance


Earth leakage circuit breaker
Symptom and possible cause
Earth leakage current higher than trip current since

Malfunction

Earth leakage test


button is projected as
soon as the breaker is
ON

increase of earth interruption capacity depending on wire


length
Parallel connection
Mis-connection or disconnection of neutral line

Troubleshooting
Adjust the residual current
Install the breaker closer to the load

Inspect the connection and wiring

Excessive surge
Trip during normal
operation

Induction noise by high current generating line

Remove or keep away from causes

Noise of electromagnetic waves

Accessories
Symptom and possible cause
Voltage drop of control circuit
Shunt trip (SHT)
Inability of
Under voltage trip (UVT)

254

Replace with a new breaker

Inferior mechanism

Replace with a new breaker

Different rated operational voltage

Apply the rated voltage to UVT

malfunction
Auxiliary switch (AUX)
and trip alarm switch
(ALT)

Adjust voltage to rated level

Coil damage by different voltage and malfunction of coil


protection limit switch

operation or

Troubleshooting

Damage in contact or contact operation at the current


higher than rated current
Inferior mechanism

Repair or replace with a new breaker


Replace with a new breaker

for YOU & being NEW

U-Series
Molded Case Circuit Breaker

HHIS-WC-LE-B56-02, 2012.1 Designed by JC Communication

www.hyundai-elec.com

Head Office

1000, Bangeojinsunhwan-doro Dong-gu, Ulsan, Korea


Tel: 82-52-202-8101~8
Fax: 82-52-202-8100

Seoul
(Sales & Marketing)

75, Yulgok-ro, Jongno-gu, Seoul, Korea


Tel: 82-2-746-8519, 7510
Fax: 82-2-746-7441

Atlanta

6100 Atlantic Blvd. Suite 201, Norcross, GA30097, U.S.A.


Tel: 1-678-823-7842
Fax: 1-678-823-7553

New Jersey

300 Sylvan Avenue, Englewood Cliffs, NJ, 07632, U.S.A.


Tel: 1-201-816-0286, 8028
Fax: 1-201-816-4083

London

2nd Floor, The Triangle, 5-17 Hammersmith Grove, London, W6 0LG, UK


Tel: 44-20-8741-0501
Fax: 44-20-8741-5620

Tokyo

8th Fl., Yurakucho Denki Bldg.1-7-1, Yuraku-Cho, Chiyoda-Ku, Tokyo, 100-0006, Japan
Tel: 81-3-3212-2076, 3215-7159
Fax: 81-3-3211-2093

Osaka

I-Room 5th Fl. Nagahori-Plaza Bldg. 2-4-8, Minami Senba, Chuo-Ku, Osaka, 542-0081, Japan
Tel: 81-6-6261-5766, 5767
Fax: 81-6-6261-5818

Riyadh

2nd Floor, The Plaza, P.O Box 21840, Riyadh 11485, Saudi Arabia
Tel: 966-1-462-2331
Fax: 966-1-464-4696

Dubai

205, Building 4, Emaar Square, Sheikh Zayed Road, Pobox 252458, Dubai, UAE
Tel: 971-4-425-7995
Fax: 971-4-425-7996

Kuwait

Floor 15, Al Sour Tower, Al Sour Street, Al-Qiblah, Kuwait


Tel: 965-2291-5354
Fax: 965-2291-5355

Moscow

World Trade Center, Ent. 3, #1902, Krasnopresnenskaya Nab. 12, Moscow, 123610, Russia
Tel: 7-495-258-1381
Fax: 7-495-258-1382

Madrid

Paseo De La Castellana 216, planta 0, 28046 Madrid, Spain


Tel: 34-91-732-0454, 733-6069
Fax: 34-91-733-2389

Sofia

1271, Sofia 41, Rojen Blvd., Bulgaria


Tel: 359-2-803-3200, 3220

Montgomery

201 Folmar Parkway, Montgomery, AL 36105, U.S.A.


Tel: 1-334-230-9921
Fax: 1-334-240-6869

Yangzhong

No.9 Xiandai Road, Xinba Scientific and Technologic Zone, Yangzhong, Jiangsu, P.R.C. Zip: 212212, China
Tel: 86-511-8842-0666, 0212
Fax: 86-511-8842-0668, 0231

Fax: 359-2-803-3203

You might also like