Professional Documents
Culture Documents
HYUNDAI U-Series
UAB type
UCB type
UPB type
www.hyundai-elec.com
CONTENTS
06 Introduction 08 Features 13 Quick Selection Table 17 Rating Overview
35 Specifications and Standard Order Codes 137 Characteristic Curves & Dimensions 189 Accessories
223 Technical Information 238 Order Information 248 Handling Instruction | Inspection and Maintenance
U-Series
Introduction
UAB type
| Various accessories
| Reliable quality
MCCB
Miniature Type
Up to 150kA at AC380/415V
Based on current-limiting technology
Ics = 100% Icu
| Reliable quality
| Various protection
| Internal accessories
Auxiliary switch
Trip alarm switch
Shunt trip
U-Series
Features
| Adjustable rating in full range with diverse trip mechanisms |
U-Series MCCB adopts adjustable rating function in full range from 50 to 1600AF. With diverse trip mechanisms
of U-Series MCCB, you will be provided with wide options for system design and more flexible load fluctuations.
Fixed thermal
Adjustable thermal
[ UPB type ]
Fixed thermal
Adjustable thermal
Electronic
Adjustable instantaneous
for motor protection
MCCB
Hydraulic magnetic
Fixed thermal
Adjustable thermal
UPB160X
UPB100X
UPB160L
UPB100L
UPB100H
UPB160H
UPB100S
UPB160S
UCB100L
UCB160L
UCB100H
UCB160H
UCB50L
UCB50H
UCB100S
UAB100S
UAB100R, UCB100R
UAB50H
UAB50S, UCB50R
UAB30R
UAB50R
UAB30C UAB50C
30AF
UPB250X
UCB630L
UPB250L
UCB800L
UCB630H
UCB400L
UPB250H
UCB800H
UCB630S
UPB250S
UCB400H
UCB800S
UCB800R
UCB250L
UCB630R
(45kA)
(45kA)
UCB250H
UCB400S
UCB250N
UCB400R
UCB250S
UCB250R
UAB60R UAB100C
UAB60C
50AF
60AF
100AF
125AF
160AF
250AF
400AF
630AF
800AF
Electronic type
Icu
150 kA
130 kA
100 kA
85 kA
UPB100X
UPB160X
UPB160L
UPB100L
UPB100H
UPB100S
UPB250X
UPB160H
UPB250L
UPB400H
UPB250S
UPB630L
UPB400L
UPB250H
UPB160S
UPB630X
UPB400X
UPB400S
UPB630H
UCB1000L
UCB1000S
UCB1250L
UCB1250S
UPB630S
UCB1600S
65 kA
(at 415V)
125AF
160AF
250AF
400AF
630AF
1000AF
1250AF
1600AF
Miniature type
Fixed Thermal
Icu
10 kA
UMB30S, UDB30S
UMG30S, UDG30S
5 kA
2.5 kA
UMB50H, UDB50H
UMG50H, UDG50H
UMB30H, UDB30H
UMG30H, UDG30H
UMB50S, UDB50S
UMG50S, UDG50S
UDB100H
UDG100H
UDB100S
UDG100S
UMB30R
UMG30R
(at 220V)
30AF
50AF
100AF
U-Series
Features
| High breaking capacity, realized by advanced technology and optimized design |
Our optimized design by advanced current-limiting technology allows U-Series MCCB to realize high breaking capacity
in a smaller size compared to Hi-Series MCCB, contributing to compact design of system.
The current-limiting characteristic of U-Series MCCB also minimizes the effects from fault currents and offers cost-effectiveness.
[UPB type]
Handle
Trip button
Trip(OCR) unit
Arc-chamber unit
Terminal
Mechanism
10
MCCB
| Standardization of dimensions |
U-Series MCCB minimizes the difference in size of each model, so that they can be easily replaced whenever the
specifications of the system changes.
50mm
60mm
50AF
125AF
250AF
U-Series
Features
| Modern and refined design |
Model name
UPB : Type
250 : Ampere frame size
X : Recognition code for order
Rated frequency
Utilization category
Ampere frame size
Suitability of isolation
Rated current
Standard
Main characterisitics
Ui : Rated insulation voltage
Uimp : Rated impulse
withstand voltage
Ue : Rated operational voltage
Icu : Rated ultimate
short-circuit breaking
capacity
Ics : Rated service
short-circuit breaking
capacity
Trip unit
Trip button
12
U-Series
50
60
100
Model
Number
of poles
Breaking capacity [Icu] (kA r.m.s.) Trip mechanism & Characteristics Dimensions (mm)
Rated current (A)
AC220V
AC240V
AC380V
AC415V
AC440V
AC460V
AC600V
AC660V
UAB30C
2, 3
3,5,10,15,20,30
10
7.5/5
2.5
UAB30R
2, 3
5,10,15,20,30
25
14/10
10
5
2.5
Hydraulic
magnetic
Thermal magnetic
Fixed Adjustable
50/75 130 60
UAB50C
2, 3, 4
5,10,15,20,30,40,50
10
7.5/5
UAB50R
2, 3, 4
5,10,15,20,30,40,50
25
14/10
10
UAB50S
2, 3, 4
15,16,20,25,30,32,40,50
42
25
21
7.5
1)
UAB50H
2, 3, 4
15,16,20,25,30,32,40,50
50
30
25
10
1)
UAB60C
2, 3, 4
5,10,15,20,30,40,50,60
10
7.5/5
2.5
UAB60R
2, 3, 4
5,10,15,20,30,40,50,60
25
14/10
10
50/75/100 130 60
UAB100C
2, 3, 4
5,10,15,20,30,40,50,60,75,100
25
14/10
10
UAB100R
2, 3, 4
15,16,20,25,30,32,40,50,60,63,75,80,100
42
25
21
7.5
1)
UAB100S
2, 3, 4
15,16,20,25,30,32,40,50,60,63,75,80,100
50
30
25
10
1)
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Not applicable to 2P breaker.
125
160
250
400
630
800
1000
1250
1600
Model
Number
of poles
Breaking capacity [Icu] (kA r.m.s.) Trip mechanism & Characteristics Dimensions (mm)
Rated current (A)
AC220V
AC240V
AC380V
AC415V
AC440V
AC460V
AC600V
AC660V
Thermal magnetic
Fixed Adjustable Electronic
UCB50R
2, 3, 4 15,20,30,40,50
50
30/25
25
10
UCB50H
2, 3, 4 15,16,20,25,30,32,40,50
85
42
42
20
UCB50L
2, 3, 4 15,16,20,25,30,32,40,50
100
50
50
25
UCB100R
2, 3, 4 15,16,20,25,30,32,40,50,60,63,75,80,100,125
50
30/25
25
10
UCB100S
2, 3, 4 15,16,20,25,30,32,40,50,60,63,75,80,100,125
65
42/36
35
18
UCB100H
2, 3, 4 15,16,20,25,30,32,40,50,60,63,75,80,100,125
85
42
42
20
UCB100L
2, 3, 4 15,16,20,25,30,32,40,50,60,63,75,80,100,125
100
50
50
25
UCB160H
2, 3, 4 100,125,160
85
42
42
20
UCB160L
2, 3, 4 100,125,160
100
50
50
25
UCB250R
2, 3, 4 100,125,150,160,175,200,225,250
35
25/18
18
7.5
UCB250S
2, 3, 4 100,125,150,160,175,200,225,250
50
35/25
25
10
UCB250N
2, 3, 4 100,125,150,160,175,200,225,250
65
42/36
35
18
UCB250H
2, 3, 4 100,125,150,160,175,200,225,250
85
42
42
20
UCB250L
2, 3, 4 100,125,150,160,175,200,225,250
100
50
50
25
UCB400R
2, 3, 4 250,300,320,350,400
35
30
25
18
UCB400S
2, 3, 4 250,300,320,350,400
50
42
35
22
UCB400H
2, 3, 4 250,300,320,350,400
85
65
50
25
UCB400L
2, 3, 4 250,300,320,350,400
125
100
85
30
UCB630R
2, 3, 4 500,630
50
45
35
22
UCB630S
2, 3, 4 500,630
100
65
50
25
UCB630H
2, 3, 4 500,630
100
85
65
35
UCB630L
2, 3, 4 500,630
125
100
85
35
UCB800R
2, 3, 4 700,800
50
45
35
25
UCB800S
2, 3, 4 700,800
100
65
50
25
UCB800H
2, 3, 4 700,800
100
85
65
35
UCB800L
2, 3, 4 700,800
125
100
85
35
UCB1000S
3, 4
505-1000
100
100
75
40
UCB1000L
3, 4
505-1000
150
130
100
60
UCB1250S
3, 4
630-1250
100
100
75
40
UCB1250L
3, 4
630-1250
150
130
100
60
UCB1600S
640-1600
100
65
45
25
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
2P breaker has same dimension as 3P breaker, but the middle pole is removed.
14
60/90/120 155 60
90/90/120 155 60
60/90/120 155 60
90/90/120 155 60
105/105/140 165 60
105/105/140 164 60
105/105/140 165 60
210
371 151
MCCB
125
160
250
400
630
Model
Breaking capacity [Icu] (kA r.m.s.) Trip mechanism & Characteristics Dimensions (mm)
Number
of poles
AC220V
AC240V
1)
AC380V
AC415V
AC440V
AC460V
AC660V
AC690V
UPB100S
3, 4
100
85
65
10
UPB100H
3, 4
130
100
85
10
UPB100L
3, 4
150
130
100
25
UPB100X
3, 4
1)
200
150
150
25
UPB160S
3, 4
100,125,1601)
100
85
65
10
UPB160H
3, 4
100,125,1601)
130
100
85
10
UPB160L
3, 4
100,125,1601)
150
130
100
25
UPB160X
3, 4
100,125,1601)
200
150
150
25
UPB250S
3, 4
125,150,160,175,200,225,2501)
100
85
65
10
UPB250H
3, 4
125,150,160,175,200,225,2501)
130
100
85
10
UPB250L
3, 4
125,150,160,175,200,225,2501)
150
130
100
25
UPB250X
3, 4
1)
125,150,160,175,200,225,250
200
150
150
25
UPB400S
3, 4
200-400
100
85
65
10
UPB400H
3, 4
200-400
130
100
85
10
UPB400L
3, 4
200-400
150
130
100
25
UPB400X
3, 4
200-400
200
150
150
25
UPB630S
3, 4
320-630
100
85
65
10
UPB630H
3, 4
320-630
130
100
85
10
UPB630L
3, 4
320-630
150
130
100
25
UPB630X
3, 4
320-630
200
150
150
25
Thermal magnetic
Electronic
Fixed Adjustable
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
UPB100: 50-125A
UPB160: 63-160A
UPB250: 100-250A
1) Rated current of electronic types are as followings;
Model
Number
of poles
UPB100H
UPB100L
UPB250H
UPB250L
AC380V
AC415V
2.5,3.2,6.3,12.5,20,32,50,63,80,100
130
2.5,3.2,6.3,12.5,20,32,50,63,80,100
150
125,150,175,200,225
125,150,175,200,225
Dimensions (mm)
AC440V
AC460V
AC660V
AC690V
100
85
10
130
100
25
130
100
85
10
150
130
100
25
Width
Height
Depth
105
165
86.5
The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
100
225
Model
Number
of poles
HBL103U
15,20,30,40,50,60,75,100
200
150
100
85
25
HBL103UQ
15,20,30,40,50,60,75,100
200
150
100
85
25
HBL103UM
2.5,3.2,6.3,12.5,20,32,50,63,80,100
200
150
100
85
25
HBL103UMQ
2.5,3.2,6.3,12.5,20,32,50,63,80,100
200
150
100
85
25
HBL203U
125,150,175,200,225
200
150
100
85
25
HBL203UQ
125,150,175,200,225
200
150
100
85
25
HBL203UM
125,150,175,200,225
200
150
100
85
25
HBL203UMQ
125,150,175,200,225
200
150
100
85
25
Characteristics
Dimensions (mm)
Motor
E1 class protection
Width
105
Height
Depth
165
86.5
The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
Molded Case Circuit Breaker_ 15
U-Series
Ampere
frame
Model
50
UCD50H
Dimensions (mm)
Number Rated
Ampere
Type
of poles current (A) Width Height Depth
frame
3
50
Model
Dimensions (mm)
Number Rated
of poles current (A) Width Height Depth
UAD50C
50
UAD50S
50
100
UAD100R
100
50
90
155
60
100
UCD100S
100
125
UCD100H
125
160
UCD160H
160
105
165
60
125
UPD100S
125
UCD250S
250
105
164
60
160
UPD160S
160
UCD250H
250
105
165
60
250
UPD250S
250
400
UCD400S
400
140
257
110
400
UPD400S
400
630
UCD630S
630
630
UPD630S
630
800
UCD800S
800
1000
UCD1000S
1000
1250
UCD1250S
1250
UAD
75
130
60
105
165
86.5
140
255
117
250
UCD
210
280
110
210
370
110
UPD
UMB
30
UMG
Rated residual
current [I n]
(mA) for ELCB
AC380V
AC415V
AC440V
AC460V
UMB30R
UMG30R
15,20,30
15, 30
2.5
UMB30S
UMG30S
15,20,30
15, 30
UMB30H
UMG30H
15,20,30
15, 30
10
UMB50S
UMG50S
15,20,30,40,50
15, 30
UMB50H
UMG50H
15,20,30,40,50
15, 30
10
UDB30S
UDG30S
2, 3
3,5,10,15,20,30
15, 30
2.5
2.5
UDB30H
UDG30H
2, 3
2.5
2.5
10
2.5
2.5
2.5
2.5
10
Dimensions (mm)
Width
Height
Depth
33
70
57
35
80
60
50/75
96
60
75/75
96
60
50
30
5,10
15, 30
15,20,30
UDB
UDG
50
UDB50S
UDG50S
2, 3
UDB50H
UDG50H
2, 3
5,10,15,20,30,40,50
5,10
15, 30
15, 30
15,20,30,40,50
UDB100S UDG100S
2, 3
15,20,30,40,50,60,75,100
30, 100
2.5
2.5
UDB100H UDG100H
2, 3
15,20,30,40,50,60,75,100
30, 100
10
100
- KS certified products. English nameplate and 50Hz marking are not available.
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
2P breaker has same dimension as 3P breaker, but the middle pole is removed.
16
Rating Overview
U-Series
Rating Overview
| UAB type / 30-50AF |
Model
UAB30
UAB50
Figure
30AF
2, 3
IP20
A
2, 3, 4
IP20
A
50AF
2, 3, 4
IP20
A
12 In
12 In
15-32A: 20 In, 40-100A: 10 In
(0.8-0.9-1) In
15-32A: 20 In, 40-100A: 10 In
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
2)
2)
1)
2)
2)
1)
2)
2)
1)
1)
1)
3)
25,000
15,000
50/75
130
60
82
0.45/0.65
3)
25,000
15,000
50/75/100
130
60
82
0.45/0.65/0.85
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker 2) Available for 3P, 4P breaker
3) Supplied as standard component
18
3)
25,000
15,000
50/75/100
130
60
82
0.6/0.78/0.96
MCCB
UAB60
UAB100
Figure
60AF
2, 3, 4
IP20
A
100AF
2, 3, 4
IP20
A
2, 3, 4
IP20
A
12 In
15-32A: 20 In, 40-100A: 10 In
(0.8-0.9-1) In2)
15-32A: 20 In, 40-100A: 10 In
1)
1)
1)
1)
1)
1)
2)
2)
2)
2)
2)
2)
2)
2)
2)
1)
1)
1)
3)
25,000
10,000
50/75/100
130
60
82
0.45/0.65/0.85
3)
25,000
10,000
50/75/100
130
60
82
0.45/0.65/0.85
3)
25,000
10,000
50/75/100
130
60
82
0.6/0.78/0.96
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker 2) Available for 3P, 4P breaker
3) Supplied as standard component
Molded Case Circuit Breaker_ 19
U-Series
Rating Overview
| UCB type / 50-125AF |
Model
UCB50
UCB100
Figure
50AF
Protection
Rated current (A)
Rating
INST
2, 3, 4
IP20
A
overload, inst.,
short-circuit
overload, inst.,
short-circuit
15,20,30,40,50
15,16,20,25,30,32,40,50
AC690
AC660
DC250
6
R
10
14
25
30/25
50
14
20
50
AC690
AC660
DC250
6
10 In
LTD
INST
100AF
2, 3, 4
IP20
A
2, 3, 4
IP20
A
H
20
30
42
42
85
25
40
L
25
35
50
50
100
40
60
50
15-32A: 15
40-50A: 10
(0.8-0.9-1)
15-32A: 15
40-50A: 10
In,
In
In
In,
In
overload, inst.,
short-circuit
15,16,20,25,30,32,40,
50,60,63,75,80,100,125
AC690
AC660
DC250
6
R
S
10
18
14
25
25
35
30/25
42/36
50
65
14
18
20
25
75
10 In
(0.8-0.9-1) In
10 In
overload, inst.,
short-circuit
15,16,20,25,30,32,40,
50,60,63,75,80,100,125
AC690
AC660
DC250
6
H
L
20
25
30
35
42
50
42
50
85
100
25
40
40
60
75
15-32A: 15
40-125A: 10
(0.8-0.9-1)
15-32A: 15
40-125A: 10
1)
1)
1)
1)
1)
1)
1)
1)
1)
2)
2)
2)
1)
3)
25,000
10,000
904)/90/120
155
60
84.5
0.9/1.0/1.3
3)
25,000
10,000
60/90/120
155
60
84.5
0.7/1.0/1.2
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
2) Available for 3P, 4P breaker
3) Supplied as standard component 4) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.
20
125AF
2, 3, 4
IP20
A
1)
3)
25,000
10,000
904)/90/120
155
60
84.5
0.9/1.0/1.3
In,
In
In
In,
In
MCCB
UCB160
UCB250
Figure
160AF
2, 3, 4
IP20
A
overload, inst., short-circuit
100,125,160
AC690
AC660
DC250
6
H
L
20
25
30
35
42
50
42
50
85
100
25
40
40
60
50
10 In
(0.8-0.9-1) In
10 In
250AF
2, 3, 4
IP20
A
2, 3, 4
IP20
A
10 In
(0.8-0.9-1) In
10 In
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
2)
2)
2)
25,000
10,000
1053)/105/140
165
60
84.5
1.1/1.3/1.6
25,000
10,000
1053)/105/140
164
60
84
1.1/1.2/1.5
25,000
10,000
1053)/105/140
165
60
84.5
1.1/1.3/1.6
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker 2) Supplied as standard component
3) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.
Molded Case Circuit Breaker_ 21
U-Series
Rating Overview
| UCB type / 400-800AF |
Model
UCB400
UCB630
UCB800
400AF
2, 3, 4
IP20
A
630AF
2, 3, 4
IP20
A
800AF
2, 3, 4
IP20
A
10 In
(0.8-0.9-1) In
10 In
10 In
(0.8-0.9-1) In
10 In
10 In
(0.8-0.9-1) In
10 In
Figure
1)
1)
1)
1)
1)
1)
2)
2)
2)
1)
1)
1)
2)
20,000
6,000
1403)/140/185
257
110
145
4/4.5/5.4
2)
20,000
6,000
2103)/210/280
280
110
145
8.7/9.5/12.5
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker 2) Supplied as standard component
3) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.
22
2)
10,000
3,000
2103)/210/280
280
110
145
8.7/9.5/12.5
MCCB
UCB1000
UCB1250
UCB1600
1000AF
1250AF
1600AF
Figure
3, 4
3, 4
IP20
IP20
IP20
505-1,000
630-1,250
640-1,600
AC750
AC750
AC750
AC690
AC690
AC690
Utilization category
Suitability of isolation
Protection
Rated current (A)
Rating
40
60
40
60
25
75
100
75
100
35
75
100
75
100
45
100
130
100
130
65
150
100
150
100
100
50
50
50
LTD
STD
(2-4-6-8-10) Ir
(2-4-6-8-10) Ir
INST
(3-6-8-10-11) In
(3-6-8-10-11) In
GFT
(0.2-0.3-0.4) In
(0.2-0.3-0.4) In
PTA
0.9 Ir
0.9 Ir
(0.4-1)2) In (8 setting)
(2-3-4-5-6-7-8-10) In
Pick-up LED
Mounting
Terminal connection
Signal
Accessories
Bus bar
Auxiliary switch
AUX
ALT
Shunt trip
SHT
UVT
Operating
handle
MOT
Padlock plate
PLD
Extension handle
THA
TBB
3)
3/4P
4)
3)
3)
3)
TQQ
3)
10,000
10,000
3,000
3,000
10,000
3,000
Width
210/280
210/280
210/280
210/280
210
Height
370
370
370
370
371
Depth
110
200
110
200
151
159
249
159
249
215
13/17
25/33
13.5/17.5
25.5/33.5
27
d
Weight ( , breaker only) 3/4P
3)
4)
TCF
3)
4)
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) (0.5-1): (0.63-0.8-1)x(0.8-0.85-0.9-0.95-1) 2) (0.4-1): (0.4-0.5-0.6-0.7-0.8-0.9-0.95-1)
3) Supplied as standard component
4) Supplied as standard component that attached in breaker
U-Series
Rating Overview
| UPB type / 125-250AF |
Model
UPB100
UPB160
UPB250
160AF
3, 4
IP20
A
250AF
3, 4
IP20
A
Figure
2)
2)
2)
2)
2)
2)
2)
2)
3)
3)
3)
3)
3)
3)
4)
4)
25,000
10,000
105/140
165
86.5
112
2.0/2.4
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) DC is not applicable for electronic breaker.
2) For the detail protection characteristics, please refer to following pages; UPB100: page 92 UPB160: page 98 UPB250: page 102
3) Available for 3P breaker 4) Supplied as standard component
24
25,000
10,000
105/140
165
86.5
112
2.0/2.4
MCCB
UPB400
UPB630
400AF
3, 4
IP20
A
630AF
3, 4
IP20
A
Figure
S
10
50
65
85
100
X
25
85
150
150
200
S
10
50
65
85
100
1)
1)
1)
1)
2)
2)
2)
2)
3)
3)
2)
2)
3)
3)
20,000
6,000
140/185
255
117
159.5
6.0/7.8
20,000
6,000
140/185
255
117
159.5
6.0/7.8
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) For the detail protection characteristics, please refer to following pages; UPB400: page 108 UPB630: page 110
2) Available for 3P breaker 3) Supplied as standard component
Molded Case Circuit Breaker_ 25
U-Series
Rating Overview
| Motor protection / UPB type 125-250AF |
Model
UPB100
UPB250
125AF
3
IP20
A
250AF
3
IP20
A
instantaneous, short-circuit
2.5,3.2,6.3,12.5,20,32,50,63,80,100
AC750
AC690
DC500
8
H
L
10
25
65
85
85
100
100
130
130
150
65
85
100
100
100
instantaneous, short-circuit
125,150,175,200,225
AC750
AC690
DC500
8
H
L
10
25
65
85
85
100
100
130
130
150
65
85
100
100
100
Figure
(6-7-8-9-10-11-12-13) In
1)
25,000
10,000
105
165
86.5
112
1.8
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Supplied as standard component
26
(5-6-7-8-9-10) In
1)
25,000
10,000
105
165
86.5
112
2.0
MCCB
HBL203
100AF
3
IP20
A
225AF
3
IP20
A
Model
Figure
125,150,175,200,225
AC750
AC690
DC500
8
U1)
25
85
100
150
200
100
100
10 In
UQ1)
25
85
100
150
200
100
100
UM1)
25
85
100
150
200
100
100
UMQ1)
25
85
100
150
200
100
100
100
10 In
(6-7-8-9-10-11-12-13) In
(5-6-7-8-9-10) In
2)
2)
2)
2)
2)
2)
2)
2)
3)
3)
3)
3)
25,000
10,000
105
165
86.5
112
1.8
25,000
10,000
105
165
86.5
112
2.0
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) U: non-E1 class UQ: E1 class UM: non-E1 class, motor protection UMQ: E1 class, motor protection
2) Signal accessories shall be installed in breaker before ex-working. 3) Supplied as standard component
Molded Case Circuit Breaker_ 27
U-Series
Rating Overview
| Switch disconnector / UAD type 50-100AF |
Model
UAD50C
UAD50S
UAD100R
Figure
50AF
100AF
IP20
IP20
IP20
50
50
100
50
50
100
AC690
AC690
AC690
Durability
AC660
AC660
AC660
DC250
DC250
DC250
17
52.5
52.5
25,000
25,000
25,000
15,000
15,000
10,000
Plug-in
DIN-rail
Terminal connection
Signal
AUX
ALT
Shunt trip
SHT
UVT
TFH
Mounting
Terminal
MOT
Mechanical interlock
MIF
Padlock plate
PLD
DIN-rail adaptor
DRA
TDM
Terminal cover
TCF
Interpole barrier
TQQ
Dimensions
(mm)
3P
1)
1)
1)
Width
75
75
75
Height
130
130
130
Depth
60
60
60
28
TFG
82
82
82
0.65
0.78
0.78
MCCB
UCD50H
UCD100S
UCD100H
UCD160H
UCD250S
UCD250H
50AF
100AF
125AF
160AF
IP20
IP20
IP20
IP20
IP20
IP20
50
100
125
160
250
250
50
100
125
160
250
250
AC690
AC690
AC690
AC690
AC690
AC690
Figure
250AF
Suitability of isolation
AC660
AC660
AC660
AC660
AC660
AC660
DC250
DC250
DC250
DC250
DC250
DC250
105
73.5
105
105
73.5
105
25,000
25,000
25,000
25,000
25,000
25,000
10,000
10,000
10,000
10,000
10,000
10,000
Durability
Plug-in
Terminal connection
Signal
Screw
Bus bar
Auxiliary switch
AUX
ALT
Shunt trip
SHT
UVT
TFH
TFG
MOT
Mechanical interlock
MIF
Padlock plate
PLD
CTB
TCF
TQQ
1)
1)
1)
1)
1)
1)
Width
90
90
90
105
105
105
Height
155
155
155
165
164
165
Depth
60
60
60
60
60
60
84.5
84.5
84.5
84.5
84
84.5
1.3
1.2
1.3
d
Weight ( , breaker only) 3P
TDM
U-Series
Rating Overview
| Switch disconnector / UCD type 400-1250AF |
Model
UCD400S
UCD630S
UCD800S
UCD1000S
UCD1250S
400AF
630AF
800AF
1000AF
1250AF
IP20
IP20
IP20
IP201)
IP201)
400
630
800
1,000
1,250
400
630
800
1,000
1,250
AC690
AC690
AC690
AC750
AC750
AC690
AC690
8
Figure
AC660
AC660
AC660
DC250
DC250
DC250
187
187
187
165
165
6.3
10
12.5
20,000
20,000
10,000
10,000
10,000
6,000
6,000
3,000
3,000
3,000
Durability
Plug-in
Terminal connection
Signal
Accessories Operating
AUX
ALT
Shunt trip
SHT
UVT
TFH
Motor operator
MOT
Mechanical interlock
MIF
Padlock plate
PLD
Extension handle
THA
TFG
CTB
TCF
Interpole barrier
TQQ
2)
2)
3)
3)
2)
2)
2)
2)
2)
Width
140
210
210
210
210
Height
257
280
280
370
370
Depth
110
110
110
110
110
145
145
145
159
159
4.5
9.5
9.5
13
13.5
d
Weight ( , breaker only) 3P
1) Without terminal bus bar
2) Supplied as standard component
3) Supplied as standard component that attached in breaker
30
2)
TBB
Terminal cover
3P
2)
TDM
Dimensions
(mm)
2)
MCCB
UPD100S
UPD160S
UPD250S
UPD400S
UPD630S
125AF
160AF
250AF
400AF
630AF
IP20
IP20
IP20
IP20
IP20
125
160
250
400
630
125
160
250
400
630
AC750
AC750
AC750
AC750
AC750
AC690
AC690
Figure
AC690
AC690
AC690
DC500
DC500
DC500
200
200
200
200
200
1.6
2.5
6.3
25,000
25,000
25,000
20,000
20,000
10,000
10,000
10,000
6,000
6,000
Durability
Plug-in
Terminal connection
Signal
Accessories
Operating
AUX
ALT
Shunt trip
SHT
UVT
TFH
Motor operator
MOT
Mechanical interlock
MIF
Padlock plate
PLD
Extension handle
THA
Dimensions
(mm)
TFG
TBB
CTB
Terminal cover
TCF
Interpole barrier
TQQ
1)
1)
1)
1)
1)
Width
105
105
105
140
140
Height
165
165
165
255
255
Depth
86.5
86.5
86.5
117
117
112
112
112
159.5
159.5
1.8
d
Weight ( , breaker only) 3P
1)
TDM
3P
1)
U-Series
Rating Overview
| Miniature type / Molded case circuit breaker 30-100AF |
Model
UMB30
UMB50
UDB30
UDB50
UDB100
30AF
50AF
30AF
50AF
100AF
2, 3
2, 3
2, 3
Degree of protection
IP20
IP20
IP20
IP20
IP20
Utilization category
overload,
short-circuit
overload,
short-circuit
overload,
short-circuit
overload,
short-circuit
overload,
short-circuit
15, 20, 30
15, 20,
30, 40, 50
31), 5, 10,
15, 20, 30
5, 10, 15,
20, 30, 40, 50
AC250
AC250
AC460
AC460
AC460
AC220
AC220
2P: AC220
3P: AC220/460
2P: AC220
3P: AC220/460
2P: AC220
3P: AC220/460
Figure
Protection
Rating
AC220/240V, 50-60Hz
5-10A: 2.5
15-30A: 5
AC440/460V, 50-60Hz
Rated
short-circuit Ultimate
[Icu]
breaking
(kA r.m.s.) AC380/415V, 50-60Hz
capacity
IEC 60947-2
K 60947-2
2.5
10
50
10
5-10A: 2.5
15-30A: 5
2.5
5-10A: 2.5
15-30A: 5
2.55
5-10A: 2.5
15-30A: 5
2.5
5-10A: 5
15-30A:10
5-10A: 5
15-30A:10
10
50
50
50
50
Hydraulic magnetic
Trip
mechanism Thermal magnetic
Direct mounting by screw
Mounting
DIN-rail
Terminal connection
Accessories
Signal
Screw
Auxiliary switch
AUX
ALT
Shunt trip
SHT
Dimensions
(mm)
TQQ
Width
33
35
35
50/75
50/75
752)/75
Height
70
80
80
96
96
96
Depth
42
60
60
60
60
60
57
76
76
80
80
80
0.1
0.13
0.15
0.2/0.35
0.2/0.35
0.2/0.35
2/3P
d
- KS certified products. English nameplate and 50Hz marking are not available.
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) 3A is not applicable for UDB30H. 2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.
32
MCCB
UMG30
UMG50
UDG30
UDG50
UDG100
30AF
50AF
30AF
50AF
100AF
2, 3
2, 3
2, 3
Degree of protection
IP20
IP20
IP20
IP20
IP20
Utilization category
earth leakage,
overload,
short-circuit
earth leakage,
overload,
short-circuit
earth leakage,
overload,
short-circuit
earth leakage,
overload,
short-circuit
15, 20, 30
15, 20,
30, 40, 50
31), 5, 10,
15, 20, 30
5, 10, 15,
20, 30, 40, 50
15, 30
15, 30
15, 30
15, 30
30, 100
AC250
AC250
AC460
AC460
AC460
AC220
AC220
2P: AC220
3P: AC220/460
2P: AC220
3P: AC220/460
Figure
Protection
Rating
Rated
AC440/460V, 50-60Hz
short-circuit Ultimate
breaking
[Icu]
capacity
(kA r.m.s.) AC380/415V, 50-60Hz
IEC 60947-2
K 60947-2
AC220/240V, 50-60Hz
2.5
0.03
0.03
0.03
0.03
2.5
5-10A: 2.5
15-30A: 5
2.5
5-10A: 2.5
15-30A: 5
2.5
2.5
5-10A: 2.5
15-30A: 5
2.5
5-10A: 2.5
15-30A: 5
2.5
5-10A: 5
15-30A: 10
5-10A: 5
15-30A: 10
10
10
10
50
by current
transformer
2P: AC220
3P: AC220/460
0.03
50
earth leakage,
overload,
short-circuit
by current
transformer
50
50
50
by current
transformer
by current
transformer
by current
transformer
Hydraulic magnetic
Trip
mechanism Thermal magnetic
Direct mounting by screw
Mounting
DIN-rail
Terminal connection
Accessories
Signal
Screw
Auxiliary switch
AUX
ALT
Width
33
35
35
50/75
50/75
752)/75
Height
70
80
80
96
96
96
Depth
42
60
60
60
60
60
a
Dimensions
(mm)
2/3P
d
Weight (kg, breaker only) 2/3P
TQQ
57
76
76
80
80
80
0.1
0.13
0.15
0.33/0.44
0.33/0.44
0.46/0.63
- KS certified products. English nameplate and 50Hz marking are not available.
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) 3A is not applicable for UDG30H. 2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.
Molded Case Circuit Breaker_ 33
U-Series
UAB30C
Hydraulic
magnetic
Fixed thermal,
Fixed instantaneous
UAB30R
2, 3
IP20
A
overload, inst., short-circuit
3,5,10,15,20,30
5,10,15,20,30
AC690
AC660
6
2.5
5
2.5
7.5
5
10
7.5/5
14/10
10
25
50
INST
12 In
1)
1)
Plug-in
1)
25,000
15,000
50/75
130
60
82
0.45/0.65
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip1)
Under voltage trip2)
1C, right-hand-side
2C, right-hand-side
AUX 10A R1
AUX 10A R2
1C, right-hand-side
ALT 10A R1
DC24V
DC100-110V
SHT 10A A
SHT 10A C
DC24V
DC100-110V
UVT 10A J
UVT 10A L
AC100-120V
SHT 10A F
AC100-120V
UVT 10A N
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.
36
AC200-230V
AC200-230V
UVT 10A P
AC380-415V
SHT 10A H
AC380-415V
UVT 10A Q
AC440-480V
AC440-480V
UVT 10A R
MCCB
Operating
Power supply direction
S type
Operating Surface
L type
1)
handle
S type
Extended
L type
Upper
TFG 10AS U4
TFG 10AL U4
Right
TFG 10AS R4
TFH 10AS
TFH 10AL
AC/DC110V
MOT 10A ADC110
DC24V
MOT 10A DC24
Motor operator2)
2 pole
Mechanical interlock
Padlock plate3)
Left
TFG 10AS L4
TFG 10AL L4
AC/DC220V
MOT 10A ADC220
3 pole
MIF 10A 3
PLD 10UA
1) Available for 3P breaker. For detail type information, please refer to page 197-205. 2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.
Mounting
Plug-in1)
Structure
Mounting base
Connection 2C contact
block 2)
3C contact
Conn. block barrier
CBM 10AB 3
CBM BARR
Terminal
3EA/SET
CTB 10A 3S50
2 pole
3 pole
TCF 10AP 2
TCF 10AP 3
TQQ 10A 3PLINE
Terminal cover1)
Interpole barrier 2)
2EA/SET
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA
2 pole
3 pole
Rated
current
Code
Unit
(EA)
3A
30
20
5A
30
20
UAB30C
10A
30
20
7.5/5kA
15A
30
20
20A
30
20
30A
30
20
UAB30R
14/10kA
Code
Unit
(EA)
5A
30
20
10A
30
20
15A
30
20
20A
30
20
30A
30
20
Specification
Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M1
U-Series
UAB50C
Hydraulic
magnetic
Fixed thermal,
Fixed instantaneous
UAB50R
2, 3, 4
IP20
A
overload, inst., short-circuit
5,10,15,20,30,40,50
AC690
AC660
6
2.5
2.5
5
7.5/5
10
5
7.5
10
14/10
25
50
INST
12 In
1)
Plug-in
1)
1)
25,000
15,000
50/75/100
130
60
82
0.45/0.65/0.85
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip1)
Under voltage trip2)
1C, right-hand-side
2C, right-hand-side
AUX 10A R1
AUX 10A R2
1C, right-hand-side
ALT 10A R1
DC24V
DC100-110V
SHT 10A A
SHT 10A C
DC24V
DC100-110V
UVT 10A J
UVT 10A L
AC100-120V
SHT 10A F
AC100-120V
UVT 10A N
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.
38
AC200-230V
AC200-230V
UVT 10A P
AC380-415V
SHT 10A H
AC380-415V
UVT 10A Q
AC440-480V
AC440-480V
UVT 10A R
MCCB
Operating
Upper
TFG 10AS U4
TFG 10AL U4
Right
TFG 10AS R4
TFH 10AS
TFH 10AL
AC/DC110V
MOT 10A ADC110
3 pole
MIF 10A 3
PLD 10UA
DC24V
MOT 10A DC24
2 pole
Motor operator 2)
Mechanical interlock
Left
TFG 10AS L4
TFG 10AL L4
Padlock plate3)
AC/DC220V
MOT 10A ADC220
4 pole
MIF 10A 4
1) Available for 3P, 4P breaker. For detail type information, please refer to page 197-205. 2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.
Mounting
Structure
Mounting base
Plug-in1) Connection 2C contact
block 2)
3C contact
Conn. block barrier
Terminal
3EA/SET
CTB 10A 3S50
2 pole
TCF 10AP 2
2EA/SET
4EA/SET
CTB 10A 4S50
3 pole
4 pole
TCF 10AP 3
TCF 10AP 4
TQQ 10A 3PLINE
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA
UAB50C
7.5/5kA
UAB50R
14/10kA
Rated
current
2 pole
Code
Unit
(EA)
3 pole
Code
Unit
(EA)
4 pole
Code
Unit
(EA)
Specification Category
5A
30
20
16
10A
30
20
16
15A
30
20
16
20A
30
20
16
30A
30
20
16
40A
30
20
50A
30
20
5A
30
20
10A
30
20
Screw type
terminal
connection,
UAB50R 4PT4S0000C 00005 16 No option,
50/60Hz
UAB50R 4PT4S0000C 00010 16
15A
30
20
20A
30
20
30A
30
20
40A
30
20
50A
30
20
16
16
MCCB
/M1
U-Series
UAB50S
UAB50H
2, 3, 4
IP20
Utilization category
Suitability of isolation
Protection
15,16,20,25,30,32,40,50
AC690
Rating
AC660
DC250
Rated
short-circuit
breaking
capacity
Ultimate
[Icu]
(kA r.m.s.)
IEC 60947-2
K 60947-2
7.5
10
AC480/500V, 50-60Hz
7.5
14
AC440/460V, 50-60Hz
21
25
AC380/415V, 50-60Hz
25
30
AC220/240V, 50-60Hz
42
50
DC250V
10
14
DC125V
15
20
AC600/660V, 50-60Hz
25
Fixed thermal,
Fixed instantaneous
Adjustable thermal,
Fixed instantaneous
INST
LTD
(0.8-0.9-1) In 2)
INST
Mounting
Plug-in
DIN-rail
Terminal connection
1)
1)
1)
Durability
Mechanical operation
25,000
(times)
Electrical operation
15,000
Dimensions
(mm)
2/3/4P
Width
50/75/100
Height
130
Depth
60
d
Weight (kg, breaker only)
2/3/4P
82
0.6/0.78/0.96
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker 2) Available for 3P, 4P breaker
40
MCCB
Accessories
Signal
1C, right-hand-side
Auxiliary switch
Trip alarm switch
Shunt trip
1)
1C, left-hand-side
AUX 10UA R1
AUX 10UA L1
1C, right-hand-side
1C, left-hand-side
ALT 10UA R1
ALT 10UA L1
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
SHT 10UA A
SHT 10UA F
SHT 10UA H
SHT 10UA B
SHT 10UA D
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
AC440-480V
UVT 10UA J
UVT 10UA L
UVT 10UA N
UVT 10UA P
UVT 10UA Q
UVT 10UA R
AC440-480V
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Operating
Upper
Right
Left
S type
TFG 10UAS U4
TFG 10UAS R4
TFG 10UAS L4
L type
TFG 10UAL U4
TFG 10UAL L4
S type
TFH 10UAS
L type
TFH 10UAL
Motor operator2)
DC24V
AC/DC110V
AC/DC220V
2 pole
Mechanical interlock
Padlock plate3)
3 pole
4 pole
MIF 10UA 3
MIF 10UA 4
PLD 10UA
1) Available for 3P, 4P breaker. For detail type information, please refer to page 197-205.
2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.
Mounting
DRA 10UA
DIN-rail adaptor
Structure
Mounting base
Plug-in1) Connection 2C contact
block2)
3C contact
TDM 10AP
TDM 10AF
CBM 10AB 2
CBM 10AB 3
CBM BARR
Terminal
3EA/SET
Terminal cover1)
Interpole barrier2)
2EA/SET
4EA/SET
CTB 10A 4S50
2 pole
3 pole
4 pole
TCF 10AP 2
TCF 10AP 3
TCF 10AP 4
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA
U-Series
Rated
current
2 pole
3 pole
4 pole
Code
Unit
(EA)
Code
Unit
(EA)
15A
30
20
16
16A
30
20
16
Code
Unit
(EA)
Specification Category
20A
30
20
16
UAB50S
25A
30
20
16
25kA
30A
30
20
16
32A
30
20
16
40A
30
20
50A
30
20
15A
30
16A
30
16 Screw type
16 terminal
connection,
16 No option,
16 50/60Hz
20A
30
16
UAB50H
25A
30
16
30kA
30A
30
16
32A
30
16
40A
30
16
50A
30
16
MCCB
/M2
50
Model /
Breaking
capacity at
AC380/415V
42
Rated
current
2 pole
3 pole
4 pole
Unit
(EA)
Code
Unit
(EA)
15A
30
20
16
16A
30
20
16
20A
30
20
16
UAB50S
25A
30
20
16
25kA
30A
30
20
16
32A
30
20
16
40A
30
20
50A
30
20
15A
30
16A
30
16 Screw type
16 terminal
connection,
16 No option,
16 50/60Hz
Code
Unit
(EA)
Specification Category
Code
20A
30
16
UAB50H
25A
30
16
30kA
30A
30
16
32A
30
16
40A
30
16
50A
30
16
MCCB
/M2
MCCB
Rated
current
3 pole
4 pole
Code
Unit
(EA)
Code
Unit
(EA)
15A
20
16
16A
20
16
20A
20
16
UAB50S
25A
20
16
25kA
30A
20
16
32A
20
16
40A
20
16
50A
20
16
15A
20
16
16A
20
16
20A
20
16
UAB50H
25A
20
16
30kA
30A
20
16
32A
20
16
40A
20
16
50A
20
16
Specification
Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
Specification
Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
50
Model /
Breaking
capacity at
AC380/415V
Rated
current
3 pole
4 pole
Code
Unit
(EA)
Code
Unit
(EA)
15A
20
16
16A
20
16
20A
20
16
UAB50S
25A
20
16
25kA
30A
20
16
32A
20
16
40A
20
16
50A
20
16
15A
20
16
16A
20
16
20A
20
16
UAB50H
25A
20
16
30kA
30A
20
16
32A
20
16
40A
20
16
50A
20
16
U-Series
UAB60C
2, 3, 4
IP20
A
Fixed thermal,
Fixed instantaneous
AC600/660V, 50-60Hz
AC480/500V, 50-60Hz
Ultimate
[Icu]
AC440/460V, 50-60Hz
(kA r.m.s.)
AC380/415V, 50-60Hz
AC220/240V, 50-60Hz
Service [Ics] % of [Icu]
Hydraulic
magnetic
UAB60R
5
7.5
10
14/10
25
50
INST
12 In
Plug-in
1)
1)
25,000
10,000
50/75/100
130
60
82
0.45/0.65/0.85
2/3/4P
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip1)
Under voltage trip2)
1C, right-hand-side
2C, right-hand-side
AUX 10A R1
AUX 10A R2
1C, right-hand-side
ALT 10A R1
DC24V
DC100-110V
SHT 10A A
SHT 10A C
DC24V
DC100-110V
UVT 10A J
UVT 10A L
AC100-120V
SHT 10A F
AC100-120V
UVT 10A N
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.
44
AC200-230V
AC200-230V
UVT 10A P
AC380-415V
SHT 10A H
AC380-415V
UVT 10A Q
AC440-480V
AC440-480V
UVT 10A R
MCCB
Operating
Power supply direction
S type
Operating Surface
L type
1)
handle
S type
Extended
L type
Upper
TFG 10AS U4
TFG 10AL U4
Right
TFG 10AS R4
TFH 10AS
TFH 10AL
AC/DC110V
MOT 10A ADC110
3 pole
MIF 10A 3
PLD 10UA
DC24V
MOT 10A DC24
2 pole
Motor operator 2)
Mechanical interlock
Left
TFG 10AS L4
TFG 10AL L4
Padlock plate3)
AC/DC220V
MOT 10A ADC220
4 pole
MIF 10A 4
1) Available for 3P, 4P breaker. For detail type information, please refer to page 197-205. 2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.
Mounting
Plug-in1)
Structure
Mounting base
Connection 2C contact
3C contact
block2)
Conn. block barrier
Terminal
Cage terminal block
5-50A
60A
Terminal cover1)
Interpole barrier2)
3EA/SET
CTB 10A 3S50
CTB 10A 3S100
2 pole
TCF 10AP 2
2EA/SET
4EA/SET
CTB 10A 4S50
CTB 10A 4S100
3 pole
4 pole
TCF 10AP 3
TCF 10AP 4
TQQ 10A 3PLINE
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA
Rated
current
2 pole
Code
Unit
(EA)
3 pole
Code
Unit
(EA)
4 pole
Code
Unit
(EA)
Specification Category
5A
30
20
16
10A
30
20
16
15A
30
20
16
UAB60C
20A
30
20
16
7.5/5kA
30A
30
20
16
40A
30
20
16
50A
30
20
60A
30
20
5A
30
20
10A
30
20
15A
30
20
16 Screw type
16 terminal
connection,
16 No option,
16
50/60Hz
16
UAB60R
20A
30
20
16
14/10kA
30A
30
20
16
40A
30
20
16
50A
30
20
16
60A
30
20
16
MCCB
/M1
U-Series
UAB100C
Hydraulic
magnetic
Fixed thermal,
Fixed instantaneous
2, 3, 4
IP20
A
overload, inst., short-circuit
5,10,15,20,30,40,50,60,75,100
AC690
AC660
6
5
7.5
10
14/10
25
50
INST
12 In
1)
Plug-in
1)
25,000
10,000
50/75/100
130
60
82
0.45/0.65/0.85
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip1)
Under voltage trip2)
1C, right-hand-side
2C, right-hand-side
AUX 10A R1
AUX 10A R2
1C, right-hand-side
ALT 10A R1
DC24V
DC100-110V
SHT 10A A
SHT 10A C
DC24V
DC100-110V
UVT 10A J
UVT 10A L
AC100-120V
SHT 10A F
AC100-120V
UVT 10A N
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.
46
AC200-230V
AC200-230V
UVT 10A P
AC380-415V
SHT 10A H
AC380-415V
UVT 10A Q
AC440-480V
AC440-480V
UVT 10A R
MCCB
Operating
Power supply direction
S type
Operating Surface
L type
1)
handle
S type
Extended
L type
Upper
TFG 10AS U4
TFG 10AL U4
Right
TFG 10AS R4
TFH 10AS
TFH 10AL
AC/DC110V
MOT 10A ADC110
3 pole
MIF 10A 3
PLD 10UA
DC24V
MOT 10A DC24
2 pole
Motor operator 2)
Mechanical interlock
Left
TFG 10AS L4
TFG 10AL L4
Padlock plate3)
AC/DC220V
MOT 10A ADC220
4 pole
MIF 10A 4
1) Available for 3P, 4P breaker. For detail type information, please refer to page 197-205. 2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.
Mounting
Plug-in1)
Structure
Mounting base
Connection 2C contact
block2)
3C contact
Conn. block barrier
Terminal
Cage terminal block
5-50A
60-100A
Terminal cover1)
Interpole barrier2)
3EA/SET
CTB 10A 3S50
CTB 10A 3S100
2 pole
TCF 10AP 2
2EA/SET
4EA/SET
CTB 10A 4S50
CTB 10A 4S100
3 pole
4 pole
TCF 10AP 3
TCF 10AP 4
TQQ 10A 3PLINE
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA
Rated
current
2 pole
Code
3 pole
Unit
(EA)
Code
4 pole
Unit
(EA)
Code
Unit
(EA)
5A
10A
15A
20A
UAB100C
30A
14/10kA
40A
Specification Category
50A
Screw type
terminal
connection,
UAB100C 2PT4S0000C 00040 30 UAB100C 3PT4S0000C 00040 20 UAB100C 4PT4S0000C 00040 16 No option,
50/60Hz
UAB100C 2PT4S0000C 00050 30 UAB100C 3PT4S0000C 00050 20 UAB100C 4PT4S0000C 00050 16
60A
75A
100A
MCCB
/M1
U-Series
UAB100S
UAB100R
2, 3, 4
IP20
A
Utilization category
Suitability of isolation
Protection
15,16,20,25,30,32,40,50,60,63,75,80,100
AC690
AC660
DC250
Rated impulse withstand voltage [Uimp] (kV)
Rated
short-circuit
breaking
capacity
Ultimate
[Icu]
(kA r.m.s.)
IEC 60947-2
K 60947-2
7.5
10
AC480/500V, 50-60Hz
7.5
14
AC440/460V, 50-60Hz
21
25
AC380/415V, 50-60Hz
25
30
AC220/240V, 50-60Hz
42
50
DC250V
10
14
DC125V
15
20
AC600/660V, 50-60Hz
25
Fixed thermal,
Fixed instantaneous
Adjustable thermal,
Fixed instantaneous
INST
LTD
(0.8-0.9-1) In 2)
INST
Mounting
Plug-in
1)
1)
Mechanical operation
25,000
Electrical operation
10,000
Dimensions
(mm)
2/3/4P
Width
50/75/100
Height
130
Depth
60
d
Weight (kg, breaker only)
2/3/4P
82
0.6/0.78/0.96
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker 2) Available for 3P, 4P breaker
48
MCCB
Accessories
Signal
1C, right-hand-side 1C, left-hand-side
Auxiliary switch
AUX 10UA R1
AUX 10UA L1
1)
ALT 10UA R1
ALT 10UA L1
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
SHT 10UA A
SHT 10UA F
SHT 10UA H
SHT 10UA B
SHT 10UA D
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
AC440-480V
UVT 10UA J
UVT 10UA L
UVT 10UA N
UVT 10UA P
UVT 10UA Q
UVT 10UA R
AC440-480V
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Operating
Upper
Right
Left
S type
TFG 10UAS U4
TFG 10UAS R4
TFG 10UAS L4
L type
TFG 10UAL U4
TFG 10UAL L4
TFH 10UAS
S type
TFH 10UAL
L type
Motor operator 2)
DC24V
AC/DC110V
AC/DC220V
2 pole
Mechanical interlock
Padlock plate3)
3 pole
4 pole
MIF 10UA 3
MIF 10UA 4
PLD 10UA
1) Available for 3P, 4P breaker. For detail type information, please refer to page 197-205.
2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.
Mounting
DRA 10UA
DIN-rail adaptor
Structure
Mounting base
Plug-in1) Connection 2C contact
block2)
3C contact
TDM 10AP
TDM 10AF
CBM 10AB 2
CBM 10AB 3
CBM BARR
Terminal
Cage terminal block
3EA/SET
4EA/SET
15-50A
60-100A
Terminal cover1)
Interpole barrier2)
2EA/SET
2 pole
3 pole
4 pole
TCF 10AP 2
TCF 10AP 3
TCF 10AP 4
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA
U-Series
UAB100R
25kA
UAB100S
30kA
2 pole
3 pole
4 pole
Rated
current
Code
Unit
(EA)
Code
Unit
(EA)
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
Rated
current
Code
Unit
(EA)
Code
Unit
(EA)
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
Code
UAB100R 4PT4S0000C 00015
UAB100R 4PT4S0000C 00016
UAB100R 4PT4S0000C 00020
UAB100R 4PT4S0000C 00025
UAB100R 4PT4S0000C 00030
UAB100R 4PT4S0000C 00032
UAB100R 4PT4S0000C 00040
UAB100R 4PT4S0000C 00050
UAB100R 4PT4S0000C 00060
UAB100R 4PT4S0000C 00063
UAB100R 4PT4S0000C 00075
UAB100R 4PT4S0000C 00080
UAB100R 4PT4S0000C 00100
UAB100S 4PT4S0000C 00015
UAB100S 4PT4S0000C 00016
UAB100S 4PT4S0000C 00020
UAB100S 4PT4S0000C 00025
UAB100S 4PT4S0000C 00030
UAB100S 4PT4S0000C 00032
UAB100S 4PT4S0000C 00040
UAB100S 4PT4S0000C 00050
UAB100S 4PT4S0000C 00060
UAB100S 4PT4S0000C 00063
UAB100S 4PT4S0000C 00075
UAB100S 4PT4S0000C 00080
UAB100S 4PT4S0000C 00100
Unit
(EA)
Specification Category
16
16
16
16
16
16
16
16
16
16
16
16 Screw type
terminal
16
connection,
16
No option,
16
50/60Hz
16
16
16
16
16
16
16
16
16
16
16
MCCB
/M2
50
Model /
Breaking capacity at
AC380/415V
UAB100R
25kA
UAB100S
30kA
50
2 pole
3 pole
4 pole
Code
UAB100R 4PT5S0000C 00015
UAB100R 4PT5S0000C 00016
UAB100R 4PT5S0000C 00020
UAB100R 4PT5S0000C 00025
UAB100R 4PT5S0000C 00030
UAB100R 4PT5S0000C 00032
UAB100R 4PT5S0000C 00040
UAB100R 4PT5S0000C 00050
UAB100R 4PT5S0000C 00060
UAB100R 4PT5S0000C 00063
UAB100R 4PT5S0000C 00075
UAB100R 4PT5S0000C 00080
UAB100R 4PT5S0000C 00100
UAB100S 4PT5S0000C 00015
UAB100S 4PT5S0000C 00016
UAB100S 4PT5S0000C 00020
UAB100S 4PT5S0000C 00025
UAB100S 4PT5S0000C 00030
UAB100S 4PT5S0000C 00032
UAB100S 4PT5S0000C 00040
UAB100S 4PT5S0000C 00050
UAB100S 4PT5S0000C 00060
UAB100S 4PT5S0000C 00063
UAB100S 4PT5S0000C 00075
UAB100S 4PT5S0000C 00080
UAB100S 4PT5S0000C 00100
Unit
(EA)
Specification Category
16
16
16
16
16
16
16
16
16
16
16
16 Screw type
terminal
16
connection,
16
No option,
16
50/60Hz
16
16
16
16
16
16
16
16
16
16
16
MCCB
/M2
MCCB
UAB100R
25kA
UAB100S
30kA
Rated
current
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
3 pole
Code
UAB100R 3PT4S0000C 00015F
UAB100R 3PT4S0000C 00016F
UAB100R 3PT4S0000C 00020F
UAB100R 3PT4S0000C 00025F
UAB100R 3PT4S0000C 00030F
UAB100R 3PT4S0000C 00032F
UAB100R 3PT4S0000C 00040F
UAB100R 3PT4S0000C 00050F
UAB100R 3PT4S0000C 00060F
UAB100R 3PT4S0000C 00063F
UAB100R 3PT4S0000C 00075F
UAB100R 3PT4S0000C 00080F
UAB100R 3PT4S0000C 00100F
UAB100S 3PT4S0000C 00015F
UAB100S 3PT4S0000C 00016F
UAB100S 3PT4S0000C 00020F
UAB100S 3PT4S0000C 00025F
UAB100S 3PT4S0000C 00030F
UAB100S 3PT4S0000C 00032F
UAB100S 3PT4S0000C 00040F
UAB100S 3PT4S0000C 00050F
UAB100S 3PT4S0000C 00060F
UAB100S 3PT4S0000C 00063F
UAB100S 3PT4S0000C 00075F
UAB100S 3PT4S0000C 00080F
UAB100S 3PT4S0000C 00100F
4 pole
Unit
(EA)
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
Code
UAB100R 4PT4S0000C 00015F
UAB100R 4PT4S0000C 00016F
UAB100R 4PT4S0000C 00020F
UAB100R 4PT4S0000C 00025F
UAB100R 4PT4S0000C 00030F
UAB100R 4PT4S0000C 00032F
UAB100R 4PT4S0000C 00040F
UAB100R 4PT4S0000C 00050F
UAB100R 4PT4S0000C 00060F
UAB100R 4PT4S0000C 00063F
UAB100R 4PT4S0000C 00075F
UAB100R 4PT4S0000C 00080F
UAB100R 4PT4S0000C 00100F
UAB100S 4PT4S0000C 00015F
UAB100S 4PT4S0000C 00016F
UAB100S 4PT4S0000C 00020F
UAB100S 4PT4S0000C 00025F
UAB100S 4PT4S0000C 00030F
UAB100S 4PT4S0000C 00032F
UAB100S 4PT4S0000C 00040F
UAB100S 4PT4S0000C 00050F
UAB100S 4PT4S0000C 00060F
UAB100S 4PT4S0000C 00063F
UAB100S 4PT4S0000C 00075F
UAB100S 4PT4S0000C 00080F
UAB100S 4PT4S0000C 00100F
Unit
(EA)
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
Specification
Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
Specification
Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
50
Model /
Breaking capacity at
AC380/415V
UAB100R
25kA
UAB100S
30kA
Rated
current
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
3 pole
Code
UAB100R 3PT5S0000C 00015F
UAB100R 3PT5S0000C 00016F
UAB100R 3PT5S0000C 00020F
UAB100R 3PT5S0000C 00025F
UAB100R 3PT5S0000C 00030F
UAB100R 3PT5S0000C 00032F
UAB100R 3PT5S0000C 00040F
UAB100R 3PT5S0000C 00050F
UAB100R 3PT5S0000C 00060F
UAB100R 3PT5S0000C 00063F
UAB100R 3PT5S0000C 00075F
UAB100R 3PT5S0000C 00080F
UAB100R 3PT5S0000C 00100F
UAB100S 3PT5S0000C 00015F
UAB100S 3PT5S0000C 00016F
UAB100S 3PT5S0000C 00020F
UAB100S 3PT5S0000C 00025F
UAB100S 3PT5S0000C 00030F
UAB100S 3PT5S0000C 00032F
UAB100S 3PT5S0000C 00040F
UAB100S 3PT5S0000C 00050F
UAB100S 3PT5S0000C 00060F
UAB100S 3PT5S0000C 00063F
UAB100S 3PT5S0000C 00075F
UAB100S 3PT5S0000C 00080F
UAB100S 3PT5S0000C 00100F
4 pole
Unit
(EA)
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
Code
UAB100R 4PT5S0000C 00015F
UAB100R 4PT5S0000C 00016F
UAB100R 4PT5S0000C 00020F
UAB100R 4PT5S0000C 00025F
UAB100R 4PT5S0000C 00030F
UAB100R 4PT5S0000C 00032F
UAB100R 4PT5S0000C 00040F
UAB100R 4PT5S0000C 00050F
UAB100R 4PT5S0000C 00060F
UAB100R 4PT5S0000C 00063F
UAB100R 4PT5S0000C 00075F
UAB100R 4PT5S0000C 00080F
UAB100R 4PT5S0000C 00100F
UAB100S 4PT5S0000C 00015F
UAB100S 4PT5S0000C 00016F
UAB100S 4PT5S0000C 00020F
UAB100S 4PT5S0000C 00025F
UAB100S 4PT5S0000C 00030F
UAB100S 4PT5S0000C 00032F
UAB100S 4PT5S0000C 00040F
UAB100S 4PT5S0000C 00050F
UAB100S 4PT5S0000C 00060F
UAB100S 4PT5S0000C 00063F
UAB100S 4PT5S0000C 00075F
UAB100S 4PT5S0000C 00080F
UAB100S 4PT5S0000C 00100F
Unit
(EA)
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
U-Series
UCB50R
Rated
short-circuit
breaking
capacity
IEC 60947-2
K 60947-2
Trip mechanism
& Protection
characteristics
2, 3, 4
IP20
A
overload, inst., short-circuit
15,20,30,40,50
AC690
AC660
DC250
6
10
14
25
30/25
50
14
20
50
Fixed thermal,
Fixed instantaneous
INST
10 In
1)
Plug-in
1)
25,000
10,000
60/90/120
155
60
84.5
0.7/1.0/1.2
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip1)
Under voltage trip2)
52
1C, left-hand-side
AUX 10B L1
1C, left-hand-side
ALT 10B L1
DC24V
SHT 10B A
DC24V
UVT 10B J
DC100-110V
DC100-110V
UVT 10B L
AC100-120V
SHT 10B F
AC100-120V
UVT 10B N
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
AC200-230V
AC200-230V
UVT 10B P
AC380-415V
SHT 10B H
AC380-415V
UVT 10B Q
AC440-480V
AC440-480V
UVT 10B R
MCCB
Operating
Power supply direction
S type
Operating Surface
L type
1)
handle
S type
Extended
L type
Upper
TFG 10BS U4
TFG 10BL U4
Right
TFG 10BS R4
TFH 10BS
TFH 10BL
AC/DC110V
MOT 10UB ADC110
3 pole
MIF 10UF 3
PLD 10UF
DC24V
MOT 10UB DC24
2 pole
Motor operator 2)
Mechanical interlock
Left
TFG 10BS L4
TFG 10BL L4
Padlock plate3)
AC/DC220V
MOT 10UB ADC220
4 pole
MIF 10UF 4
1) Available for 3P, 4P breaker. For detail type information, please refer to page 197-205. 2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.
Mounting
Plug-in1)
Structure
Mounting base
Connection 2C contact
block2)
3C contact
Conn. block barrier
Terminal
3EA/SET
CTB 10B 3S
2 pole
TCF 10BP 2
2EA/SET
4EA/SET
CTB 10B 4S
3 pole
TCF 10BP 3
TQQ 10B 3PLINE
4 pole
TCF 10BP 4
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA
UCB50R
30/25kA
Rated
current
2 pole
Code
3 pole
Unit
(EA)
4 pole
Code
Unit
(EA)
Code
Unit
(EA)
15A
10
20A
10
30A
10
40A
10
50A
10
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M1
50
Model /
Breaking capacity at
AC380/415V
UCB50R
30/25kA
2 pole
3 pole
4 pole
Rated
current
Code
15A
10
20A
10
30A
10
40A
10
50A
10
Unit
(EA)
Code
Unit
(EA)
Code
Unit
(EA)
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M1
U-Series
UCB50H
UCB50L
2, 3, 4
IP20
Utilization category
Suitability of isolation
Protection
15,16,20,25,30,32,40,50
AC690
AC660
DC250
Rated impulse withstand voltage [Uimp] (kV)
Rated
short-circuit
breaking
capacity
Ultimate
[Icu]
(kA r.m.s.)
IEC 60947-2
K 60947-2
AC600/660V, 50-60Hz
20
25
AC480/500V, 50-60Hz
30
35
AC440/460V, 50-60Hz
42
50
AC380/415V, 50-60Hz
42
50
AC220/240V, 50-60Hz
85
100
DC250V
25
40
DC125V
40
60
50
Fixed thermal,
Fixed instantaneous
Adjustable thermal,
Fixed instantaneous
INST
LTD
(0.8-0.9-1) In
INST
Terminal connection
Durability
(times)
1)
1)
Screw
Mechanical operation
25,000
Electrical operation
Dimensions
(mm)
2/3/4P
10,000
a
Width
902)/90/120
Height
155
Depth
60
d
Weight (kg, breaker only)
1)
2/3/4P
84.5
0.9/1.0/1.3
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.
54
MCCB
Accessories
Signal
1C, left-hand-side 2C, left-hand-side
Auxiliary switch
AUX 12FG L1
AUX 12FG L2
Shunt trip
ALT 12FG R1
ALT 12FG L1
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
SHT 12FG A
SHT 12FG C
SHT 12FG F
SHT 12FG H
SHT 12FG B
SHT 12FG D
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
AC440-480V
UVT 12FG J
UVT 12FG L
UVT 12FG N
UVT 12FG P
UVT 12FG Q
UVT 12FG R
AC440-480V
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Operating
Upper
Right
Left
S type
TFG 10UFS U4
TFG 10UFS R4
TFG 10UFS L4
L type
TFG 10UFL U4
TFG 10UFL L4
TFH 10UFS
S type
TFH 10UFL
L type
Motor operator 2)
DC24V
AC/DC110V
AC/DC220V
2 pole
3 pole
4 pole
MIF 10UF 3
MIF 10UF 4
Mechanical interlock
Padlock plate3)
PLD 10UF
Mounting
Structure
Mounting base
Plug-in1) Connection 2C contact
block 2)
3C contact
TDM 10BP
TDM 10BF
CBM 10AB 2
CBM 10AB 3
CBM BARR
Terminal
Cage terminal block
Terminal cover1)
Interpole barrier2)
2EA/SET
3EA/SET
4EA/SET
CTB 10B 3S
CTB 10B 4S
2 pole
3 pole
4 pole
TCF 10FP 3
TCF 10FP 3
TCF 10FP 4
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 4EA, 3 pole 4EA, 4 pole 6EA
U-Series
Rated
current
2 pole
3 pole
4 pole
Code
Unit
(EA)
Code
Unit
(EA)
15A
16A
Code
Unit
(EA)
20A
UCB50H
25A
42kA
30A
32A
40A
50A
15A
16A
20A
UCB50L
25A
50kA
30A
32A
40A
50A
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
50
Model /
Breaking
capacity at
AC380/415V
56
Rated
current
2 pole
3 pole
4 pole
Code
Unit
(EA)
Code
Unit
(EA)
15A
16A
20A
UCB50H
25A
42kA
30A
32A
40A
50A
15A
16A
Code
Unit
(EA)
20A
UCB50L
25A
50kA
30A
32A
40A
50A
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
MCCB
Rated
current
2 pole
Code
3 pole
Unit
(EA)
Code
4 pole
Unit
(EA)
Code
Unit
(EA)
15A
16A
20A
UCB50H
25A
42kA
30A
32A
40A
50A
15A
16A
20A
UCB50L
25A
50kA
30A
32A
40A
50A
3 pole
4 pole
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
50
Model /
Breaking
capacity at
AC380/415V
Rated
current
2 pole
Code
Unit
(EA)
Code
Unit
(EA)
15A
16A
20A
UCB50H
25A
42kA
30A
32A
40A
50A
15A
16A
Code
Unit
(EA)
20A
UCB50L
25A
50kA
30A
32A
40A
50A
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
U-Series
UCB100R
UCB100S
2, 3, 4
IP20
Utilization category
Suitability of isolation
Protection
15,16,20,25,30,32,40,50,60,63,75,80,100,125
AC690
AC660
DC250
Rated impulse withstand voltage [Uimp] (kV)
Rated
short-circuit
breaking
capacity
Ultimate
[Icu]
(kA r.m.s.)
IEC 60947-2
K 60947-2
AC600/660V, 50-60Hz
10
18
AC480/500V, 50-60Hz
14
25
AC440/460V, 50-60Hz
25
35
AC380/415V, 50-60Hz
30/25
42/36
AC220/240V, 50-60Hz
50
65
DC250V
14
18
DC125V
20
25
75
Fixed thermal,
Fixed instantaneous
Adjustable thermal,
Fixed instantaneous
INST
10 In
LTD
(0.8-0.9-1) In
INST
10 In
Terminal connection
Durability
(times)
1)
1)
Screw
Mechanical operation
25,000
Electrical operation
Dimensions
(mm)
2/3/4P
10,000
a
Width
60/90/120
Height
155
Depth
60
d
Weight (kg, breaker only)
1)
2/3/4P
84.5
0.7/1.0/1.2
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
58
MCCB
Accessories
Signal
1C, left-hand-side
Auxiliary switch
AUX 10B L1
1C, left-hand-side
ALT 10B L1
1)
DC24V
DC100-110V
AC100-120V
SHT 10B A
SHT 10B F
AC200-230V
AC380-415V
AC440-480V
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
AC440-480V
UVT 10B J
UVT 10B L
UVT 10B N
UVT 10B P
UVT 10B Q
UVT 10B R
SHT 10B H
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Operating
Upper
Right
Left
S type
TFG 10BS U4
TFG 10BS R4
TFG 10BS L4
L type
TFG 10BL U4
TFG 10BL L4
S type
TFH 10BS
L type
TFH 10BL
Motor operator 2)
DC24V
AC/DC110V
AC/DC220V
2 pole
Mechanical interlock
3 pole
4 pole
MIF 10UF 3
MIF 10UF 4
PLD 10UF
Padlock plate3)
1) For detail type information, please refer to page 197-205.
2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.
Mounting
Structure
Mounting base
Plug-in
1)
TDM 10BP
TDM 10BF
Connection 2C contact
CBM 10AB 2
block 2)
CBM 10AB 3
3C contact
CBM BARR
Terminal
3EA/SET
CTB 10B 3S
Terminal cover1)
Interpole barrier2)
4EA/SET
2EA/SET
CTB 10B 4S
2 pole
3 pole
4 pole
TCF 10BP 2
TCF 10BP 3
TCF 10BP 4
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA
U-Series
UCB100R
30/25kA
UCB100S
42/36kA
2 pole
3 pole
4 pole
Rated
current
Code
Unit
(EA)
Code
Unit
(EA)
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
Rated
current
Code
Unit
(EA)
Code
Unit
(EA)
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
Code
UCB100R 4PT4S0000C 00015
UCB100R 4PT4S0000C 00016
UCB100R 4PT4S0000C 00020
UCB100R 4PT4S0000C 00025
UCB100R 4PT4S0000C 00030
UCB100R 4PT4S0000C 00032
UCB100R 4PT4S0000C 00040
UCB100R 4PT4S0000C 00050
UCB100R 4PT4S0000C 00060
UCB100R 4PT4S0000C 00063
UCB100R 4PT4S0000C 00075
UCB100R 4PT4S0000C 00080
UCB100R 4PT4S0000C 00100
UCB100R 4PT4S0000C 00125
UCB100S 4PT4S0000C 00015
UCB100S 4PT4S0000C 00016
UCB100S 4PT4S0000C 00020
UCB100S 4PT4S0000C 00025
UCB100S 4PT4S0000C 00030
UCB100S 4PT4S0000C 00032
UCB100S 4PT4S0000C 00040
UCB100S 4PT4S0000C 00050
UCB100S 4PT4S0000C 00060
UCB100S 4PT4S0000C 00063
UCB100S 4PT4S0000C 00075
UCB100S 4PT4S0000C 00080
UCB100S 4PT4S0000C 00100
UCB100S 4PT4S0000C 00125
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
50
Model /
Breaking capacity at
AC380/415V
UCB100R
30/25kA
UCB100S
42/36kA
60
2 pole
3 pole
4 pole
Code
UCB100R 4PT5S0000C 00015
UCB100R 4PT5S0000C 00016
UCB100R 4PT5S0000C 00020
UCB100R 4PT5S0000C 00025
UCB100R 4PT5S0000C 00030
UCB100R 4PT5S0000C 00032
UCB100R 4PT5S0000C 00040
UCB100R 4PT5S0000C 00050
UCB100R 4PT5S0000C 00060
UCB100R 4PT5S0000C 00063
UCB100R 4PT5S0000C 00075
UCB100R 4PT5S0000C 00080
UCB100R 4PT5S0000C 00100
UCB100R 4PT5S0000C 00125
UCB100S 4PT5S0000C 00015
UCB100S 4PT5S0000C 00016
UCB100S 4PT5S0000C 00020
UCB100S 4PT5S0000C 00025
UCB100S 4PT5S0000C 00030
UCB100S 4PT5S0000C 00032
UCB100S 4PT5S0000C 00040
UCB100S 4PT5S0000C 00050
UCB100S 4PT5S0000C 00060
UCB100S 4PT5S0000C 00063
UCB100S 4PT5S0000C 00075
UCB100S 4PT5S0000C 00080
UCB100S 4PT5S0000C 00100
UCB100S 4PT5S0000C 00125
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
MCCB
UCB100R
30/25kA
UCB100S
42/36kA
2 pole
3 pole
4 pole
Rated
current
Code
Unit
(EA)
Code
Unit
(EA)
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
Rated
current
Code
Unit
(EA)
Code
Unit
(EA)
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
Code
UCB100R 4PT4S0000C 00015F
UCB100R 4PT4S0000C 00016F
UCB100R 4PT4S0000C 00020F
UCB100R 4PT4S0000C 00025F
UCB100R 4PT4S0000C 00030F
UCB100R 4PT4S0000C 00032F
UCB100R 4PT4S0000C 00040F
UCB100R 4PT4S0000C 00050F
UCB100R 4PT4S0000C 00060F
UCB100R 4PT4S0000C 00063F
UCB100R 4PT4S0000C 00075F
UCB100R 4PT4S0000C 00080F
UCB100R 4PT4S0000C 00100F
UCB100R 4PT4S0000C 00125F
UCB100S 4PT4S0000C 00015F
UCB100S 4PT4S0000C 00016F
UCB100S 4PT4S0000C 00020F
UCB100S 4PT4S0000C 00025F
UCB100S 4PT4S0000C 00030F
UCB100S 4PT4S0000C 00032F
UCB100S 4PT4S0000C 00040F
UCB100S 4PT4S0000C 00050F
UCB100S 4PT4S0000C 00060F
UCB100S 4PT4S0000C 00063F
UCB100S 4PT4S0000C 00075F
UCB100S 4PT4S0000C 00080F
UCB100S 4PT4S0000C 00100F
UCB100S 4PT4S0000C 00125F
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
50
Model /
Breaking capacity at
AC380/415V
UCB100R
30/25kA
UCB100S
42/36kA
2 pole
3 pole
4 pole
Code
UCB100R 4PT5S0000C 00015F
UCB100R 4PT5S0000C 00016F
UCB100R 4PT5S0000C 00020F
UCB100R 4PT5S0000C 00025F
UCB100R 4PT5S0000C 00030F
UCB100R 4PT5S0000C 00032F
UCB100R 4PT5S0000C 00040F
UCB100R 4PT5S0000C 00050F
UCB100R 4PT5S0000C 00060F
UCB100R 4PT5S0000C 00063F
UCB100R 4PT5S0000C 00075F
UCB100R 4PT5S0000C 00080F
UCB100R 4PT5S0000C 00100F
UCB100R 4PT5S0000C 00125F
UCB100S 4PT5S0000C 00015F
UCB100S 4PT5S0000C 00016F
UCB100S 4PT5S0000C 00020F
UCB100S 4PT5S0000C 00025F
UCB100S 4PT5S0000C 00030F
UCB100S 4PT5S0000C 00032F
UCB100S 4PT5S0000C 00040F
UCB100S 4PT5S0000C 00050F
UCB100S 4PT5S0000C 00060F
UCB100S 4PT5S0000C 00063F
UCB100S 4PT5S0000C 00075F
UCB100S 4PT5S0000C 00080F
UCB100S 4PT5S0000C 00100F
UCB100S 4PT5S0000C 00125F
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
U-Series
UCB100H
UCB100L
2, 3, 4
IP20
Utilization category
Suitability of isolation
Protection
15,16,20,25,30,32,40,50,60,63,75,80,100,125
AC690
AC660
DC250
Rated impulse withstand voltage [Uimp] (kV)
Rated
short-circuit
breaking
capacity
Ultimate
[Icu]
(kA r.m.s.)
IEC 60947-2
K 60947-2
AC600/660V, 50-60Hz
20
25
AC480/500V, 50-60Hz
30
35
AC440/460V, 50-60Hz
42
50
AC380/415V, 50-60Hz
42
50
AC220/240V, 50-60Hz
85
100
DC250V
25
40
DC125V
40
60
75
Fixed thermal,
Fixed instantaneous
Adjustable thermal,
Fixed instantaneous
INST
LTD
(0.8-0.9-1) In
INST
Terminal connection
Durability
(times)
1)
1)
Screw
Mechanical operation
25,000
Electrical operation
Dimensions
(mm)
2/3/4P
10,000
a
Width
902)/90/120
Height
155
Depth
60
d
Weight (kg, breaker only)
1)
2/3/4P
84.5
0.9/1.0/1.3
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.
62
MCCB
Accessories
Signal
1C, left-hand-side
Auxiliary switch
Trip alarm switch
Shunt trip
1)
2C, left-hand-side
AUX 12FG L1
AUX 12FG L2
1C, right-hand-side
1C, left-hand-side
ALT 12FG R1
ALT 12FG L1
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
SHT 12FG A
SHT 12FG C
SHT 12FG F
SHT 12FG H
SHT 12FG B
SHT 12FG D
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
AC440-480V
UVT 12FG J
UVT 12FG L
UVT 12FG N
UVT 12FG P
UVT 12FG Q
UVT 12FG R
AC440-480V
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Operating
Upper
Right
Left
S type
TFG 10UFS U4
TFG 10UFS R4
TFG 10UFS L4
L type
TFG 10UFL U4
TFG 10UFL L4
TFH 10UFS
S type
TFH 10UFL
L type
Motor operator 2)
DC24V
AC/DC110V
AC/DC220V
Mechanical interlock
2 pole
3 pole
4 pole
MIF 10UF 3
MIF 10UF 3
MIF 10UF 4
PLD 10UF
Padlock plate3)
1) For detail type information, please refer to page 197-205.
2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.
Mounting
Structure
Mounting base
Plug-in1) Connection 2C contact
block 2)
3C contact
TDM 10BP
TDM 10BF
CBM 10AB 2
CBM 10AB 3
CBM BARR
Terminal
Cage terminal block
Terminal cover1)
Interpole barrier2)
2EA/SET
3EA/SET
4EA/SET
CTB 10B 3S
CTB 10B 4S
2 pole
3 pole
4 pole
TCF 10FP 3
TCF 10FP 3
TCF 10FP 4
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 2EA, 3 pole 4EA, 4 pole 6EA
U-Series
UCB100H
42kA
UCB100L
50kA
Rated
current
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
2 pole
Code
UCB100H 2PT4S0000C 00015
UCB100H 2PT4S0000C 00016
UCB100H 2PT4S0000C 00020
UCB100H 2PT4S0000C 00025
UCB100H 2PT4S0000C 00030
UCB100H 2PT4S0000C 00032
UCB100H 2PT4S0000C 00040
UCB100H 2PT4S0000C 00050
UCB100H 2PT4S0000C 00060
UCB100H 2PT4S0000C 00063
UCB100H 2PT4S0000C 00075
UCB100H 2PT4S0000C 00080
UCB100H 2PT4S0000C 00100
UCB100H 2PT4S0000C 00125
UCB100L 2PT4S0000C 00015
UCB100L 2PT4S0000C 00016
UCB100L 2PT4S0000C 00020
UCB100L 2PT4S0000C 00025
UCB100L 2PT4S0000C 00030
UCB100L 2PT4S0000C 00032
UCB100L 2PT4S0000C 00040
UCB100L 2PT4S0000C 00050
UCB100L 2PT4S0000C 00060
UCB100L 2PT4S0000C 00063
UCB100L 2PT4S0000C 00075
UCB100L 2PT4S0000C 00080
UCB100L 2PT4S0000C 00100
UCB100L 2PT4S0000C 00125
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
3 pole
Code
UCB100H 3PT4S0000C 00015
UCB100H 3PT4S0000C 00016
UCB100H 3PT4S0000C 00020
UCB100H 3PT4S0000C 00025
UCB100H 3PT4S0000C 00030
UCB100H 3PT4S0000C 00032
UCB100H 3PT4S0000C 00040
UCB100H 3PT4S0000C 00050
UCB100H 3PT4S0000C 00060
UCB100H 3PT4S0000C 00063
UCB100H 3PT4S0000C 00075
UCB100H 3PT4S0000C 00080
UCB100H 3PT4S0000C 00100
UCB100H 3PT4S0000C 00125
UCB100L 3PT4S0000C 00015
UCB100L 3PT4S0000C 00016
UCB100L 3PT4S0000C 00020
UCB100L 3PT4S0000C 00025
UCB100L 3PT4S0000C 00030
UCB100L 3PT4S0000C 00032
UCB100L 3PT4S0000C 00040
UCB100L 3PT4S0000C 00050
UCB100L 3PT4S0000C 00060
UCB100L 3PT4S0000C 00063
UCB100L 3PT4S0000C 00075
UCB100L 3PT4S0000C 00080
UCB100L 3PT4S0000C 00100
UCB100L 3PT4S0000C 00125
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
4 pole
Code
UCB100H 4PT4S0000C 00015
UCB100H 4PT4S0000C 00016
UCB100H 4PT4S0000C 00020
UCB100H 4PT4S0000C 00025
UCB100H 4PT4S0000C 00030
UCB100H 4PT4S0000C 00032
UCB100H 4PT4S0000C 00040
UCB100H 4PT4S0000C 00050
UCB100H 4PT4S0000C 00060
UCB100H 4PT4S0000C 00063
UCB100H 4PT4S0000C 00075
UCB100H 4PT4S0000C 00080
UCB100H 4PT4S0000C 00100
UCB100H 4PT4S0000C 00125
UCB100L 4PT4S0000C 00015
UCB100L 4PT4S0000C 00016
UCB100L 4PT4S0000C 00020
UCB100L 4PT4S0000C 00025
UCB100L 4PT4S0000C 00030
UCB100L 4PT4S0000C 00032
UCB100L 4PT4S0000C 00040
UCB100L 4PT4S0000C 00050
UCB100L 4PT4S0000C 00060
UCB100L 4PT4S0000C 00063
UCB100L 4PT4S0000C 00075
UCB100L 4PT4S0000C 00080
UCB100L 4PT4S0000C 00100
UCB100L 4PT4S0000C 00125
Unit
(EA)
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
50
Model /
Breaking capacity at
AC380/415V
UCB100H
42kA
UCB100L
50kA
64
Rated
current
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
2 pole
Code
UCB100H 2PT5S0000C 00015
UCB100H 2PT5S0000C 00016
UCB100H 2PT5S0000C 00020
UCB100H 2PT5S0000C 00025
UCB100H 2PT5S0000C 00030
UCB100H 2PT5S0000C 00032
UCB100H 2PT5S0000C 00040
UCB100H 2PT5S0000C 00050
UCB100H 2PT5S0000C 00060
UCB100H 2PT5S0000C 00063
UCB100H 2PT5S0000C 00075
UCB100H 2PT5S0000C 00080
UCB100H 2PT5S0000C 00100
UCB100H 2PT5S0000C 00125
UCB100L 2PT5S0000C 00015
UCB100L 2PT5S0000C 00016
UCB100L 2PT5S0000C 00020
UCB100L 2PT5S0000C 00025
UCB100L 2PT5S0000C 00030
UCB100L 2PT5S0000C 00032
UCB100L 2PT5S0000C 00040
UCB100L 2PT5S0000C 00050
UCB100L 2PT5S0000C 00060
UCB100L 2PT5S0000C 00063
UCB100L 2PT5S0000C 00075
UCB100L 2PT5S0000C 00080
UCB100L 2PT5S0000C 00100
UCB100L 2PT5S0000C 00125
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
3 pole
Code
UCB100H 3PT5S0000C 00015
UCB100H 3PT5S0000C 00016
UCB100H 3PT5S0000C 00020
UCB100H 3PT5S0000C 00025
UCB100H 3PT5S0000C 00030
UCB100H 3PT5S0000C 00032
UCB100H 3PT5S0000C 00040
UCB100H 3PT5S0000C 00050
UCB100H 3PT5S0000C 00060
UCB100H 3PT5S0000C 00063
UCB100H 3PT5S0000C 00075
UCB100H 3PT5S0000C 00080
UCB100H 3PT5S0000C 00100
UCB100H 3PT5S0000C 00125
UCB100L 3PT5S0000C 00015
UCB100L 3PT5S0000C 00016
UCB100L 3PT5S0000C 00020
UCB100L 3PT5S0000C 00025
UCB100L 3PT5S0000C 00030
UCB100L 3PT5S0000C 00032
UCB100L 3PT5S0000C 00040
UCB100L 3PT5S0000C 00050
UCB100L 3PT5S0000C 00060
UCB100L 3PT5S0000C 00063
UCB100L 3PT5S0000C 00075
UCB100L 3PT5S0000C 00080
UCB100L 3PT5S0000C 00100
UCB100L 3PT5S0000C 00125
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
4 pole
Code
UCB100H 4PT5S0000C 00015
UCB100H 4PT5S0000C 00016
UCB100H 4PT5S0000C 00020
UCB100H 4PT5S0000C 00025
UCB100H 4PT5S0000C 00030
UCB100H 4PT5S0000C 00032
UCB100H 4PT5S0000C 00040
UCB100H 4PT5S0000C 00050
UCB100H 4PT5S0000C 00060
UCB100H 4PT5S0000C 00063
UCB100H 4PT5S0000C 00075
UCB100H 4PT5S0000C 00080
UCB100H 4PT5S0000C 00100
UCB100H 4PT5S0000C 00125
UCB100L 4PT5S0000C 00015
UCB100L 4PT5S0000C 00016
UCB100L 4PT5S0000C 00020
UCB100L 4PT5S0000C 00025
UCB100L 4PT5S0000C 00030
UCB100L 4PT5S0000C 00032
UCB100L 4PT5S0000C 00040
UCB100L 4PT5S0000C 00050
UCB100L 4PT5S0000C 00060
UCB100L 4PT5S0000C 00063
UCB100L 4PT5S0000C 00075
UCB100L 4PT5S0000C 00080
UCB100L 4PT5S0000C 00100
UCB100L 4PT5S0000C 00125
Unit
(EA)
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
MCCB
UCB100H
42kA
UCB100L
50kA
Rated
current
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
2 pole
Code
UCB100H 2PT4S0000C 00015F
UCB100H 2PT4S0000C 00016F
UCB100H 2PT4S0000C 00020F
UCB100H 2PT4S0000C 00025F
UCB100H 2PT4S0000C 00030F
UCB100H 2PT4S0000C 00032F
UCB100H 2PT4S0000C 00040F
UCB100H 2PT4S0000C 00050F
UCB100H 2PT4S0000C 00060F
UCB100H 2PT4S0000C 00063F
UCB100H 2PT4S0000C 00075F
UCB100H 2PT4S0000C 00080F
UCB100H 2PT4S0000C 00100F
UCB100H 2PT4S0000C 00125F
UCB100L 2PT4S0000C 00015F
UCB100L 2PT4S0000C 00016F
UCB100L 2PT4S0000C 00020F
UCB100L 2PT4S0000C 00025F
UCB100L 2PT4S0000C 00030F
UCB100L 2PT4S0000C 00032F
UCB100L 2PT4S0000C 00040F
UCB100L 2PT4S0000C 00050F
UCB100L 2PT4S0000C 00060F
UCB100L 2PT4S0000C 00063F
UCB100L 2PT4S0000C 00075F
UCB100L 2PT4S0000C 00080F
UCB100L 2PT4S0000C 00100F
UCB100L 2PT4S0000C 00125F
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
3 pole
Code
UCB100H 3PT4S0000C 00015F
UCB100H 3PT4S0000C 00016F
UCB100H 3PT4S0000C 00020F
UCB100H 3PT4S0000C 00025F
UCB100H 3PT4S0000C 00030F
UCB100H 3PT4S0000C 00032F
UCB100H 3PT4S0000C 00040F
UCB100H 3PT4S0000C 00050F
UCB100H 3PT4S0000C 00060F
UCB100H 3PT4S0000C 00063F
UCB100H 3PT4S0000C 00075F
UCB100H 3PT4S0000C 00080F
UCB100H 3PT4S0000C 00100F
UCB100H 3PT4S0000C 00125F
UCB100L 3PT4S0000C 00015F
UCB100L 3PT4S0000C 00016F
UCB100L 3PT4S0000C 00020F
UCB100L 3PT4S0000C 00025F
UCB100L 3PT4S0000C 00030F
UCB100L 3PT4S0000C 00032F
UCB100L 3PT4S0000C 00040F
UCB100L 3PT4S0000C 00050F
UCB100L 3PT4S0000C 00060F
UCB100L 3PT4S0000C 00063F
UCB100L 3PT4S0000C 00075F
UCB100L 3PT4S0000C 00080F
UCB100L 3PT4S0000C 00100F
UCB100L 3PT4S0000C 00125F
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
4 pole
Code
UCB100H 4PT4S0000C 00015F
UCB100H 4PT4S0000C 00016F
UCB100H 4PT4S0000C 00020F
UCB100H 4PT4S0000C 00025F
UCB100H 4PT4S0000C 00030F
UCB100H 4PT4S0000C 00032F
UCB100H 4PT4S0000C 00040F
UCB100H 4PT4S0000C 00050F
UCB100H 4PT4S0000C 00060F
UCB100H 4PT4S0000C 00063F
UCB100H 4PT4S0000C 00075F
UCB100H 4PT4S0000C 00080F
UCB100H 4PT4S0000C 00100F
UCB100H 4PT4S0000C 00125F
UCB100L 4PT4S0000C 00015F
UCB100L 4PT4S0000C 00016F
UCB100L 4PT4S0000C 00020F
UCB100L 4PT4S0000C 00025F
UCB100L 4PT4S0000C 00030F
UCB100L 4PT4S0000C 00032F
UCB100L 4PT4S0000C 00040F
UCB100L 4PT4S0000C 00050F
UCB100L 4PT4S0000C 00060F
UCB100L 4PT4S0000C 00063F
UCB100L 4PT4S0000C 00075F
UCB100L 4PT4S0000C 00080F
UCB100L 4PT4S0000C 00100F
UCB100L 4PT4S0000C 00125F
Unit
(EA)
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
50
Model /
Breaking capacity at
AC380/415V
UCB100H
42kA
UCB100L
50kA
Rated
current
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
2 pole
Code
UCB100H 2PT5S0000C 00015F
UCB100H 2PT5S0000C 00016F
UCB100H 2PT5S0000C 00020F
UCB100H 2PT5S0000C 00025F
UCB100H 2PT5S0000C 00030F
UCB100H 2PT5S0000C 00032F
UCB100H 2PT5S0000C 00040F
UCB100H 2PT5S0000C 00050F
UCB100H 2PT5S0000C 00060F
UCB100H 2PT5S0000C 00063F
UCB100H 2PT5S0000C 00075F
UCB100H 2PT5S0000C 00080F
UCB100H 2PT5S0000C 00100F
UCB100H 2PT5S0000C 00125F
UCB100L 2PT5S0000C 00015F
UCB100L 2PT5S0000C 00016F
UCB100L 2PT5S0000C 00020F
UCB100L 2PT5S0000C 00025F
UCB100L 2PT5S0000C 00030F
UCB100L 2PT5S0000C 00032F
UCB100L 2PT5S0000C 00040F
UCB100L 2PT5S0000C 00050F
UCB100L 2PT5S0000C 00060F
UCB100L 2PT5S0000C 00063F
UCB100L 2PT5S0000C 00075F
UCB100L 2PT5S0000C 00080F
UCB100L 2PT5S0000C 00100F
UCB100L 2PT5S0000C 00125F
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
3 pole
Code
UCB100H 3PT5S0000C 00015F
UCB100H 3PT5S0000C 00016F
UCB100H 3PT5S0000C 00020F
UCB100H 3PT5S0000C 00025F
UCB100H 3PT5S0000C 00030F
UCB100H 3PT5S0000C 00032F
UCB100H 3PT5S0000C 00040F
UCB100H 3PT5S0000C 00050F
UCB100H 3PT5S0000C 00060F
UCB100H 3PT5S0000C 00063F
UCB100H 3PT5S0000C 00075F
UCB100H 3PT5S0000C 00080F
UCB100H 3PT5S0000C 00100F
UCB100H 3PT5S0000C 00125F
UCB100L 3PT5S0000C 00015F
UCB100L 3PT5S0000C 00016F
UCB100L 3PT5S0000C 00020F
UCB100L 3PT5S0000C 00025F
UCB100L 3PT5S0000C 00030F
UCB100L 3PT5S0000C 00032F
UCB100L 3PT5S0000C 00040F
UCB100L 3PT5S0000C 00050F
UCB100L 3PT5S0000C 00060F
UCB100L 3PT5S0000C 00063F
UCB100L 3PT5S0000C 00075F
UCB100L 3PT5S0000C 00080F
UCB100L 3PT5S0000C 00100F
UCB100L 3PT5S0000C 00125F
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
4 pole
Code
UCB100H 4PT5S0000C 00015F
UCB100H 4PT5S0000C 00016F
UCB100H 4PT5S0000C 00020F
UCB100H 4PT5S0000C 00025F
UCB100H 4PT5S0000C 00030F
UCB100H 4PT5S0000C 00032F
UCB100H 4PT5S0000C 00040F
UCB100H 4PT5S0000C 00050F
UCB100H 4PT5S0000C 00060F
UCB100H 4PT5S0000C 00063F
UCB100H 4PT5S0000C 00075F
UCB100H 4PT5S0000C 00080F
UCB100H 4PT5S0000C 00100F
UCB100H 4PT5S0000C 00125F
UCB100L 4PT5S0000C 00015F
UCB100L 4PT5S0000C 00016F
UCB100L 4PT5S0000C 00020F
UCB100L 4PT5S0000C 00025F
UCB100L 4PT5S0000C 00030F
UCB100L 4PT5S0000C 00032F
UCB100L 4PT5S0000C 00040F
UCB100L 4PT5S0000C 00050F
UCB100L 4PT5S0000C 00060F
UCB100L 4PT5S0000C 00063F
UCB100L 4PT5S0000C 00075F
UCB100L 4PT5S0000C 00080F
UCB100L 4PT5S0000C 00100F
UCB100L 4PT5S0000C 00125F
Unit
(EA)
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
U-Series
UCB160H
2, 3, 4
IP20
A
Rated
short-circuit
breaking
capacity
IEC 60947-2
K 60947-2
Trip
Thermal
mechanism
& Protection
magnetic
characteristics
UCB160L
Fixed thermal,
Fixed instantaneous
Adjustable thermal,
Fixed instantaneous
20
30
42
42
85
25
40
25
35
50
50
100
40
60
50
INST
LTD
INST
10 In
(0.8-0.9-1) In
10 In
1)
1)
1)
25,000
10,000
1052)/105/140
165
60
84.5
1.1/1.3/1.6
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.
Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip1)
Under voltage trip2)
66
1C, left-hand-side
AUX 12FG L1
1C, right-hand-side
ALT 12FG R1
DC24V
SHT 12FG A
DC24V
UVT 12FG J
2C, leftt-hand-side
AUX 12FG L2
1C, left-hand-side
ALT 12FG L1
DC100-110V
SHT 12FG C
DC100-110V
UVT 12FG L
AC100-120V
SHT 12FG F
AC100-120V
UVT 12FG N
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
AC200-230V
SHT 12FG H
AC200-230V
UVT 12FG P
AC380-415V
SHT 12FG B
AC380-415V
UVT 12FG Q
AC440-480V
SHT 12FG D
AC440-480V
UVT 12FG R
MCCB
Operating
Operating
handle1)
Upper
TFG 20UGS U4
TFG 20UGL U4
Right
TFG 20UGS R4
TFH 20UGS
TFH 20UGL
AC/DC110V
MOT 20G ADC110
3 pole
MIF 20UG 3
PLD 20UG
DC24V
MOT 20G DC24
2 pole
MIF 20UG 3
Motor operator 2)
Mechanical interlock
Left
TFG 20UGS L4
TFG 20UGL L4
Padlock plate3)
AC/DC220V
MOT 20G ADC220
4 pole
MIF 20UG 4
1) For detail type information, please refer to page 197-205. 2) Motor operator is not recommended for marine application. 3) Padlock is not supplied.
Mounting
Plug-in1)
Structure
Mounting base
Connection 2C contact
5C contact
block2)
Terminal
2 pole (4EA/SET)
TBB 20C 2
3EA/SET
CTB 20C 3S
2 pole
TCF 20GP 3
2EA/SET
3 pole (6EA/SET)
4 pole (8EA/SET)
TBB 20C 3
TBB 20C 4
4EA/SET
CTB 20C 4S
3 pole
4 pole
TCF 20GP 3
TCF 20GP 4
TQQ 12FG 3PLINE
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 4EA, 3 pole 4EA, 4 pole 6EA
UCB160H
42kA
UCB160L
50kA
Rated
current
2 pole
Code
100A
125A
160A
100A
125A
160A
Rated
current
2 pole
Code
UCB160H 2PT5S0000C 00100
UCB160H 2PT5S0000C 00125
UCB160H 2PT5S0000C 00160
UCB160L 2PT5S0000C 00100
UCB160L 2PT5S0000C 00125
UCB160L 2PT5S0000C 00160
Unit
(EA)
8
8
8
8
8
8
3 pole
Code
UCB160H 3PT4S0000C 00100
UCB160H 3PT4S0000C 00125
UCB160H 3PT4S0000C 00160
UCB160L 3PT4S0000C 00100
UCB160L 3PT4S0000C 00125
UCB160L 3PT4S0000C 00160
Unit
(EA)
8
8
8
8
8
8
4 pole
Code
UCB160H 4PT4S0000C 00100
UCB160H 4PT4S0000C 00125
UCB160H 4PT4S0000C 00160
UCB160L 4PT4S0000C 00100
UCB160L 4PT4S0000C 00125
UCB160L 4PT4S0000C 00160
Unit
(EA)
6
6
6
6
6
6
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
50
Model /
Breaking capacity at
AC380/415V
UCB160H
42kA
UCB160L
50kA
100A
125A
160A
100A
125A
160A
Unit
(EA)
8
8
8
8
8
8
3 pole
Unit
Code
(EA)
UCB160H 3PT5S0000C 00100 8
UCB160H 3PT5S0000C 00125 8
UCB160H 3PT5S0000C 00160 8
UCB160L 3PT5S0000C 00100
8
UCB160L 3PT5S0000C 00125
8
UCB160L 3PT5S0000C 00160
8
4 pole
Code
UCB160H 4PT5S0000C 00100
UCB160H 4PT5S0000C 00125
UCB160H 4PT5S0000C 00160
UCB160L 4PT5S0000C 00100
UCB160L 4PT5S0000C 00125
UCB160L 4PT5S0000C 00160
Unit
(EA)
6
6
6
6
6
6
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
UCB160H
42kA
UCB160L
50kA
Rated
current
100A
125A
160A
100A
125A
160A
2 pole
Unit
Code
(EA)
UCB160H 2PT4S0000C 00100F 8
UCB160H 2PT4S0000C 00125F 8
UCB160H 2PT4S0000C 00160F 8
UCB160L 2PT4S0000C 00100F 8
UCB160L 2PT4S0000C 00125F 8
UCB160L 2PT4S0000C 00160F 8
3 pole
Code
UCB160H 3PT4S0000C 00100F
UCB160H 3PT4S0000C 00125F
UCB160H 3PT4S0000C 00160F
UCB160L 3PT4S0000C 00100F
UCB160L 3PT4S0000C 00125F
UCB160L 3PT4S0000C 00160F
Unit
(EA)
8
8
8
8
8
8
4 pole
Unit Specification Category
Code
(EA)
UCB160H 4PT4S0000C 00100F 6
UCB160H 4PT4S0000C 00125F 6 Screw type
terminal
MCCB
UCB160H 4PT4S0000C 00160F 6
connection,
/M2
UCB160L 4PT4S0000C 00100F 6
No option,
UCB160L 4PT4S0000C 00125F 6
50/60Hz
UCB160L 4PT4S0000C 00160F 6
50
Model /
Breaking capacity at
AC380/415V
UCB160H
42kA
UCB160L
50kA
Rated
current
100A
125A
160A
100A
125A
160A
2 pole
3 pole
4 pole
Unit
Unit
Unit Specification Category
Code
Code
Code
(EA)
(EA)
(EA)
UCB160H 2PT5S0000C 00100F 8 UCB160H 3PT5S0000C 00100F 8 UCB160H 4PT5S0000C 00100F 6
Screw type
UCB160H 2PT5S0000C 00125F 8 UCB160H 3PT5S0000C 00125F 8 UCB160H 4PT5S0000C 00125F 6
terminal
UCB160H 2PT5S0000C 00160F 8 UCB160H 3PT5S0000C 00160F 8 UCB160H 4PT5S0000C 00160F 6 connection, MCCB
/M2
UCB160L 2PT5S0000C 00100F 8 UCB160L 3PT5S0000C 00100F 8 UCB160L 4PT5S0000C 00100F 6
No option,
UCB160L 2PT5S0000C 00125F 8 UCB160L 3PT5S0000C 00125F 8 UCB160L 4PT5S0000C 00125F 6
50/60Hz
UCB160L 2PT5S0000C 00160F 8 UCB160L 3PT5S0000C 00160F 8 UCB160L 4PT5S0000C 00160F 6
Molded Case Circuit Breaker_ 67
U-Series
UCB250R
UCB250S
2, 3, 4
IP20
Utilization category
UCB250N
Suitability of isolation
Protection
125,150,160,175,200,225,250
AC690
AC660
DC250
Rated impulse withstand voltage [Uimp] (kV)
Rated
short-circuit
breaking
capacity
Ultimate
[Icu]
(kA r.m.s.)
IEC 60947-2
K 60947-2
AC600/660V, 50-60Hz
7.5
10
18
AC480/500V, 50-60Hz
10
14
25
AC440/460V, 50-60Hz
18
25
35
AC380/415V, 50-60Hz
25/18
35/25
42/36
AC220/240V, 50-60Hz
35
50
65
DC250V
10
14
18
DC125V
15
20
25
50
Fixed thermal,
Fixed instantaneous
Adjustable thermal,
Fixed instantaneous
INST
10 In
LTD
(0.8-0.9-1) In
INST
10 In
Terminal connection
1)
1)
1)
Screw
Bus bar
Durability
(times)
Mechanical operation
25,000
Electrical operation
10,000
Dimensions
(mm)
2/3/4P
Width
1052)/105/140
Height
164
Depth
60
d
Weight (kg, breaker only)
2/3/4P
84
1.1/1.2/1.5
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.
68
MCCB
Accessories
Signal
1C, left-hand-side
Auxiliary switch
AUX 20C L1
1C, left-hand-side
ALT 20C L1
1)
DC24V
DC100-110V
AC100-120V
SHT 20C A
SHT 20C F
AC200-230V
AC380-415V
AC440-480V
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
AC440-480V
UVT 20C J
UVT 20C L
UVT 20C N
UVT 20C P
UVT 20C Q
UVT 20C R
SHT 20C H
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Operating
Upper
Right
Left
S type
TFG 20CS U4
TFG 20CS R4
TFG 20CS L4
L type
TFG 20CL U4
TFG 20CL L4
TFH 20CS
S type
TFH 20CL
L type
Motor operator 2)
DC24V
AC/DC110V
AC/DC220V
2 pole
3 pole
4 pole
MIF 20UG 3
MIF 20UG 3
MIF 20UG 4
Mechanical interlock
PLD 20UG
Padlock plate3)
1) For detail type information, please refer to page 197-205.
2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.
Mounting
For both line & load side
Mounting base
TDM 20CF 3)
TDM 20CF
Connection 2C contact
CBM 20C 2
block 2)
CBM 20C 5
Structure
Plug-in1)
5C contact
Terminal
2 pole (4EA/SET) 3 pole (6EA/SET) 4 pole (8EA/SET)
TBB 20C 2
2EA/SET
TBB 20C 4
4EA/SET
CTB 20C 3S
1)
Interpole barrier 2)
TBB 20C 3
3EA/SET
CTB 20C 4S
2 pole
3 pole
4 pole
TCF 20CP 3
TCF 20CP 3
TCF 20CP 4
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 4EA, 3 pole 4EA, 4 pole 6EA
U-Series
UCB250R
25/18kA
UCB250S
35/25kA
UCB250N
42/36kA
Rated
current
100A
125A
150A
160A
175A
200A
225A
250A
100A
125A
150A
160A
175A
200A
225A
250A
100A
125A
150A
160A
175A
200A
225A
250A
2 pole
Code
UCB250R 2PT4S0000C 00100
UCB250R 2PT4S0000C 00125
UCB250R 2PT4S0000C 00150
UCB250R 2PT4S0000C 00160
UCB250R 2PT4S0000C 00175
UCB250R 2PT4S0000C 00200
UCB250R 2PT4S0000C 00225
UCB250R 2PT4S0000C 00250
UCB250S 2PT4S0000C 00100
UCB250S 2PT4S0000C 00125
UCB250S 2PT4S0000C 00150
UCB250S 2PT4S0000C 00160
UCB250S 2PT4S0000C 00175
UCB250S 2PT4S0000C 00200
UCB250S 2PT4S0000C 00225
UCB250S 2PT4S0000C 00250
UCB250N 2PT4S0000C 00100
UCB250N 2PT4S0000C 00125
UCB250N 2PT4S0000C 00150
UCB250N 2PT4S0000C 00160
UCB250N 2PT4S0000C 00175
UCB250N 2PT4S0000C 00200
UCB250N 2PT4S0000C 00225
UCB250N 2PT4S0000C 00250
Unit
(EA)
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
3 pole
Code
UCB250R 3PT4S0000C 00100
UCB250R 3PT4S0000C 00125
UCB250R 3PT4S0000C 00150
UCB250R 3PT4S0000C 00160
UCB250R 3PT4S0000C 00175
UCB250R 3PT4S0000C 00200
UCB250R 3PT4S0000C 00225
UCB250R 3PT4S0000C 00250
UCB250S 3PT4S0000C 00100
UCB250S 3PT4S0000C 00125
UCB250S 3PT4S0000C 00150
UCB250S 3PT4S0000C 00160
UCB250S 3PT4S0000C 00175
UCB250S 3PT4S0000C 00200
UCB250S 3PT4S0000C 00225
UCB250S 3PT4S0000C 00250
UCB250N 3PT4S0000C 00100
UCB250N 3PT4S0000C 00125
UCB250N 3PT4S0000C 00150
UCB250N 3PT4S0000C 00160
UCB250N 3PT4S0000C 00175
UCB250N 3PT4S0000C 00200
UCB250N 3PT4S0000C 00225
UCB250N 3PT4S0000C 00250
Unit
(EA)
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
4 pole
Code
UCB250R 4PT4S0000C 00100
UCB250R 4PT4S0000C 00125
UCB250R 4PT4S0000C 00150
UCB250R 4PT4S0000C 00160
UCB250R 4PT4S0000C 00175
UCB250R 4PT4S0000C 00200
UCB250R 4PT4S0000C 00225
UCB250R 4PT4S0000C 00250
UCB250S 4PT4S0000C 00100
UCB250S 4PT4S0000C 00125
UCB250S 4PT4S0000C 00150
UCB250S 4PT4S0000C 00160
UCB250S 4PT4S0000C 00175
UCB250S 4PT4S0000C 00200
UCB250S 4PT4S0000C 00225
UCB250S 4PT4S0000C 00250
UCB250N 4PT4S0000C 00100
UCB250N 4PT4S0000C 00125
UCB250N 4PT4S0000C 00150
UCB250N 4PT4S0000C 00160
UCB250N 4PT4S0000C 00175
UCB250N 4PT4S0000C 00200
UCB250N 4PT4S0000C 00225
UCB250N 4PT4S0000C 00250
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
50
Model /
Breaking capacity at
AC380/415V
UCB250R
25/18kA
UCB250S
35/25kA
UCB250N
42/36kA
70
Rated
current
100A
125A
150A
160A
175A
200A
225A
250A
100A
125A
150A
160A
175A
200A
225A
250A
100A
125A
150A
160A
175A
200A
225A
250A
2 pole
Code
UCB250R 2PT5S0000C 00100
UCB250R 2PT5S0000C 00125
UCB250R 2PT5S0000C 00150
UCB250R 2PT5S0000C 00160
UCB250R 2PT5S0000C 00175
UCB250R 2PT5S0000C 00200
UCB250R 2PT5S0000C 00225
UCB250R 2PT5S0000C 00250
UCB250S 2PT5S0000C 00100
UCB250S 2PT5S0000C 00125
UCB250S 2PT5S0000C 00150
UCB250S 2PT5S0000C 00160
UCB250S 2PT5S0000C 00175
UCB250S 2PT5S0000C 00200
UCB250S 2PT5S0000C 00225
UCB250S 2PT5S0000C 00250
UCB250N 2PT5S0000C 00100
UCB250N 2PT5S0000C 00125
UCB250N 2PT5S0000C 00150
UCB250N 2PT5S0000C 00160
UCB250N 2PT5S0000C 00175
UCB250N 2PT5S0000C 00200
UCB250N 2PT5S0000C 00225
UCB250N 2PT5S0000C 00250
Unit
(EA)
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
3 pole
Code
UCB250R 3PT5S0000C 00100
UCB250R 3PT5S0000C 00125
UCB250R 3PT5S0000C 00150
UCB250R 3PT5S0000C 00160
UCB250R 3PT5S0000C 00175
UCB250R 3PT5S0000C 00200
UCB250R 3PT5S0000C 00225
UCB250R 3PT5S0000C 00250
UCB250S 3PT5S0000C 00100
UCB250S 3PT5S0000C 00125
UCB250S 3PT5S0000C 00150
UCB250S 3PT5S0000C 00160
UCB250S 3PT5S0000C 00175
UCB250S 3PT5S0000C 00200
UCB250S 3PT5S0000C 00225
UCB250S 3PT5S0000C 00250
UCB250N 3PT5S0000C 00100
UCB250N 3PT5S0000C 00125
UCB250N 3PT5S0000C 00150
UCB250N 3PT5S0000C 00160
UCB250N 3PT5S0000C 00175
UCB250N 3PT5S0000C 00200
UCB250N 3PT5S0000C 00225
UCB250N 3PT5S0000C 00250
Unit
(EA)
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
4 pole
Code
UCB250R 4PT5S0000C 00100
UCB250R 4PT5S0000C 00125
UCB250R 4PT5S0000C 00150
UCB250R 4PT5S0000C 00160
UCB250R 4PT5S0000C 00175
UCB250R 4PT5S0000C 00200
UCB250R 4PT5S0000C 00225
UCB250R 4PT5S0000C 00250
UCB250S 4PT5S0000C 00100
UCB250S 4PT5S0000C 00125
UCB250S 4PT5S0000C 00150
UCB250S 4PT5S0000C 00160
UCB250S 4PT5S0000C 00175
UCB250S 4PT5S0000C 00200
UCB250S 4PT5S0000C 00225
UCB250S 4PT5S0000C 00250
UCB250N 4PT5S0000C 00100
UCB250N 4PT5S0000C 00125
UCB250N 4PT5S0000C 00150
UCB250N 4PT5S0000C 00160
UCB250N 4PT5S0000C 00175
UCB250N 4PT5S0000C 00200
UCB250N 4PT5S0000C 00225
UCB250N 4PT5S0000C 00250
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
MCCB
UCB250R
25/18kA
UCB250S
35/25kA
UCB250N
42/36kA
Rated
current
100A
125A
150A
160A
175A
200A
225A
250A
100A
125A
150A
160A
175A
200A
225A
250A
100A
125A
150A
160A
175A
200A
225A
250A
2 pole
Code
UCB250R 2PT4S0000C 00100F
UCB250R 2PT4S0000C 00125F
UCB250R 2PT4S0000C 00150F
UCB250R 2PT4S0000C 00160F
UCB250R 2PT4S0000C 00175F
UCB250R 2PT4S0000C 00200F
UCB250R 2PT4S0000C 00225F
UCB250R 2PT4S0000C 00250F
UCB250S 2PT4S0000C 00100F
UCB250S 2PT4S0000C 00125F
UCB250S 2PT4S0000C 00150F
UCB250S 2PT4S0000C 00160F
UCB250S 2PT4S0000C 00175F
UCB250S 2PT4S0000C 00200F
UCB250S 2PT4S0000C 00225F
UCB250S 2PT4S0000C 00250F
UCB250N 2PT4S0000C 00100F
UCB250N 2PT4S0000C 00125F
UCB250N 2PT4S0000C 00150F
UCB250N 2PT4S0000C 00160F
UCB250N 2PT4S0000C 00175F
UCB250N 2PT4S0000C 00200F
UCB250N 2PT4S0000C 00225F
UCB250N 2PT4S0000C 00250F
Unit
(EA)
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
3 pole
Code
UCB250R 3PT4S0000C 00100F
UCB250R 3PT4S0000C 00125F
UCB250R 3PT4S0000C 00150F
UCB250R 3PT4S0000C 00160F
UCB250R 3PT4S0000C 00175F
UCB250R 3PT4S0000C 00200F
UCB250R 3PT4S0000C 00225F
UCB250R 3PT4S0000C 00250F
UCB250S 3PT4S0000C 00100F
UCB250S 3PT4S0000C 00125F
UCB250S 3PT4S0000C 00150F
UCB250S 3PT4S0000C 00160F
UCB250S 3PT4S0000C 00175F
UCB250S 3PT4S0000C 00200F
UCB250S 3PT4S0000C 00225F
UCB250S 3PT4S0000C 00250F
UCB250N 3PT4S0000C 00100F
UCB250N 3PT4S0000C 00125F
UCB250N 3PT4S0000C 00150F
UCB250N 3PT4S0000C 00160F
UCB250N 3PT4S0000C 00175F
UCB250N 3PT4S0000C 00200F
UCB250N 3PT4S0000C 00225F
UCB250N 3PT4S0000C 00250F
Unit
(EA)
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
4 pole
Code
UCB250R 4PT4S0000C 00100F
UCB250R 4PT4S0000C 00125F
UCB250R 4PT4S0000C 00150F
UCB250R 4PT4S0000C 00160F
UCB250R 4PT4S0000C 00175F
UCB250R 4PT4S0000C 00200F
UCB250R 4PT4S0000C 00225F
UCB250R 4PT4S0000C 00250F
UCB250S 4PT4S0000C 00100F
UCB250S 4PT4S0000C 00125F
UCB250S 4PT4S0000C 00150F
UCB250S 4PT4S0000C 00160F
UCB250S 4PT4S0000C 00175F
UCB250S 4PT4S0000C 00200F
UCB250S 4PT4S0000C 00225F
UCB250S 4PT4S0000C 00250F
UCB250N 4PT4S0000C 00100F
UCB250N 4PT4S0000C 00125F
UCB250N 4PT4S0000C 00150F
UCB250N 4PT4S0000C 00160F
UCB250N 4PT4S0000C 00175F
UCB250N 4PT4S0000C 00200F
UCB250N 4PT4S0000C 00225F
UCB250N 4PT4S0000C 00250F
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
50
Model /
Breaking capacity at
AC380/415V
UCB250R
25/18kA
UCB250S
35/25kA
UCB250N
42/36kA
Rated
current
100A
125A
150A
160A
175A
200A
225A
250A
100A
125A
150A
160A
175A
200A
225A
250A
100A
125A
150A
160A
175A
200A
225A
250A
2 pole
Code
UCB250R 2PT5S0000C 00100F
UCB250R 2PT5S0000C 00125F
UCB250R 2PT5S0000C 00150F
UCB250R 2PT5S0000C 00160F
UCB250R 2PT5S0000C 00175F
UCB250R 2PT5S0000C 00200F
UCB250R 2PT5S0000C 00225F
UCB250R 2PT5S0000C 00250F
UCB250S 2PT5S0000C 00100F
UCB250S 2PT5S0000C 00125F
UCB250S 2PT5S0000C 00150F
UCB250S 2PT5S0000C 00160F
UCB250S 2PT5S0000C 00175F
UCB250S 2PT5S0000C 00200F
UCB250S 2PT5S0000C 00225F
UCB250S 2PT5S0000C 00250F
UCB250N 2PT5S0000C 00100F
UCB250N 2PT5S0000C 00125F
UCB250N 2PT5S0000C 00150F
UCB250N 2PT5S0000C 00160F
UCB250N 2PT5S0000C 00175F
UCB250N 2PT5S0000C 00200F
UCB250N 2PT5S0000C 00225F
UCB250N 2PT5S0000C 00250F
Unit
(EA)
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
3 pole
Code
UCB250R 3PT5S0000C 00100F
UCB250R 3PT5S0000C 00125F
UCB250R 3PT5S0000C 00150F
UCB250R 3PT5S0000C 00160F
UCB250R 3PT5S0000C 00175F
UCB250R 3PT5S0000C 00200F
UCB250R 3PT5S0000C 00225F
UCB250R 3PT5S0000C 00250F
UCB250S 3PT5S0000C 00100F
UCB250S 3PT5S0000C 00125F
UCB250S 3PT5S0000C 00150F
UCB250S 3PT5S0000C 00160F
UCB250S 3PT5S0000C 00175F
UCB250S 3PT5S0000C 00200F
UCB250S 3PT5S0000C 00225F
UCB250S 3PT5S0000C 00250F
UCB250N 3PT5S0000C 00100F
UCB250N 3PT5S0000C 00125F
UCB250N 3PT5S0000C 00150F
UCB250N 3PT5S0000C 00160F
UCB250N 3PT5S0000C 00175F
UCB250N 3PT5S0000C 00200F
UCB250N 3PT5S0000C 00225F
UCB250N 3PT5S0000C 00250F
Unit
(EA)
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
4 pole
Code
UCB250R 4PT5S0000C 00100F
UCB250R 4PT5S0000C 00125F
UCB250R 4PT5S0000C 00150F
UCB250R 4PT5S0000C 00160F
UCB250R 4PT5S0000C 00175F
UCB250R 4PT5S0000C 00200F
UCB250R 4PT5S0000C 00225F
UCB250R 4PT5S0000C 00250F
UCB250S 4PT5S0000C 00100F
UCB250S 4PT5S0000C 00125F
UCB250S 4PT5S0000C 00150F
UCB250S 4PT5S0000C 00160F
UCB250S 4PT5S0000C 00175F
UCB250S 4PT5S0000C 00200F
UCB250S 4PT5S0000C 00225F
UCB250S 4PT5S0000C 00250F
UCB250N 4PT5S0000C 00100F
UCB250N 4PT5S0000C 00125F
UCB250N 4PT5S0000C 00150F
UCB250N 4PT5S0000C 00160F
UCB250N 4PT5S0000C 00175F
UCB250N 4PT5S0000C 00200F
UCB250N 4PT5S0000C 00225F
UCB250N 4PT5S0000C 00250F
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
U-Series
UCB250H
UCB250L
2, 3, 4
IP20
Utilization category
Suitability of isolation
Protection
125,150,160,175,200,225,250
AC690
AC660
DC250
Rated impulse withstand voltage [Uimp] (kV)
Rated
short-circuit
breaking
capacity
Ultimate
[Icu]
(kA r.m.s.)
IEC 60947-2
K 60947-2
AC600/660V, 50-60Hz
20
25
AC480/500V, 50-60Hz
30
35
AC440/460V, 50-60Hz
42
50
AC380/415V, 50-60Hz
42
50
AC220/240V, 50-60Hz
85
100
DC250V
25
40
DC125V
40
60
50
Fixed thermal,
Fixed instantaneous
INST
10 In
Adjustable thermal,
LTD
(0.8-0.9-1) In
Fixed instantaneous
INST
10 In
Terminal connection
1)
1)
1)
Screw
Bus bar
Durability
(times)
Mechanical operation
25,000
Electrical operation
10,000
Dimensions
(mm)
2/3/4P
Width
1052)/105/140
Height
165
Depth
d
Weight (kg, breaker only)
2/3/4P
60
84.5
1.1/1.3/1.6
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.
72
MCCB
Accessories
Signal
Auxiliary switch
2C, left-hand-side
AUX 12FG L1
AUX 12FG L2
1C, left-hand-side
1)
ALT 12FG R1
ALT 12FG L1
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
SHT 12FG A
SHT 12FG C
SHT 12FG F
SHT 12FG H
SHT 12FG B
SHT 12FG D
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
AC440-480V
UVT 12FG J
UVT 12FG L
UVT 12FG N
UVT 12FG P
UVT 12FG Q
UVT 12FG R
AC440-480V
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Operating
Upper
Right
Left
S type
TFG 20UGS U4
TFG 20UGS R4
TFG 20UGS L4
L type
TFG 20UGL U4
TFG 20UGL L4
TFH 20UGS
S type
TFH 20UGL
L type
Motor operator 2)
DC24V
AC/DC110V
AC/DC220V
2 pole
3 pole
4 pole
MIF 20UG 3
MIF 20UG 3
MIF 20UG 4
Mechanical interlock
PLD 20UG
Padlock plate3)
1) For detail type information, please refer to page 197-205.
2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.
Mounting
For both line & load side
Mounting base
TDM 20CF 3)
TDM 20CF
Connection 2C contact
CBM 20C 2
block 2)
CBM 20C 5
Structure
Plug-in1)
5C contact
Terminal
2 pole (4EA/SET) 3 pole (6EA/SET) 4 pole (8EA/SET)
TBB 20C 2
2EA/SET
TBB 20C 3
TBB 20C 4
3EA/SET
4EA/SET
CTB 20C 3S
CTB 20C 4S
2 pole
3 pole
4 pole
TCF 20GP 3
TCF 20GP 3
TCF 20GP 4
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 4EA, 3 pole 4EA, 4 pole 6EA
U-Series
UCB250H
42kA
UCB250L
50kA
Rated
current
2 pole
Code
3 pole
Unit
(EA)
Code
4 pole
Unit
(EA)
Code
Unit
(EA)
100A
125A
150A
160A
175A
200A
225A
250A
100A
125A
150A
160A
175A
200A
225A
250A
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
50
Model /
Breaking
capacity at
AC380/415V
2 pole
3 pole
4 pole
Code
Unit
(EA)
Code
Unit
(EA)
100A
125A
150A
UCB250H
160A
42kA
175A
200A
225A
250A
100A
125A
150A
160A
UCB250L
50kA
74
Rated
current
Code
Unit
(EA)
175A
200A
225A
250A
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
MCCB
UCB250H
42kA
UCB250L
50kA
Rated
current
2 pole
3 pole
Code
Unit
(EA)
100A
125A
150A
160A
4 pole
Code
Unit
(EA)
Code
Unit
(EA)
175A
200A
225A
250A
100A
125A
150A
160A
175A
200A
225A
250A
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
50
Model /
Breaking
capacity at
AC380/415V
Rated
current
2 pole
3 pole
4 pole
Code
Unit
(EA)
Code
Unit
(EA)
Code
Unit
(EA)
100A
125A
150A
UCB250H
160A
42kA
175A
200A
225A
250A
100A
125A
150A
160A
UCB250L
50kA
175A
200A
225A
250A
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
U-Series
UCB400R
UCB400S
UCB400H
2, 3, 4
IP20
UCB400L
Utilization category
Suitability of isolation
Protection
250,300,320,350,400
AC690
AC660
DC250
Rated impulse withstand voltage [Uimp] (kV)
Rated
short-circuit
Ultimate
breaking
[Icu]
capacity
(kA r.m.s.)
IEC 60947-2
K 60947-2
AC600/660V, 50-60Hz
18
22
25
30
AC480/500V, 50-60Hz
18
25
35
65
AC440/460V, 50-60Hz
25
35
50
85
AC380/415V, 50-60Hz
30
42
65
100
AC220/240V, 50-60Hz
35
50
85
125
DC250V
14
25
40
40
DC125V
20
30
50
60
50
Fixed thermal,
Fixed instantaneous
Adjustable thermal,
Fixed instantaneous
INST
10 In
LTD
(0.8 0.9 1) In
INST
10 In
Plug-in
Terminal connection
1)
1)
Screw
Bus bar
Durability
(times)
Dimensions
(mm)
Mechanical operation
20,000
Electrical operation
2/3/4P
6,000
a
Width
140 /140/185
Height
257
Depth
110
d
Weight (kg, breaker only) 2/3/4P
2)
145
4/4.5/5.4
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.
76
MCCB
Accessories
Signal
1C, right-hand-side
Auxiliary switch
AUX 46D R1
1C, left-hand-side
ALT 46D L1
1)
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
SHT 46D A
SHT 46D C
SHT 46D F
SHT 46D H
SHT 46D B
SHT 46D D
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
AC440-480V
UVT 46D L
UVT 46D N
UVT 46D P
UVT 46D Q
UVT 46D R
UVT 46D J
AC440-480V
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.
Operating
Power supply direction
Operating
Surface S type
handle 1)
Extended S type
Motor operator 2)
Upper
Right
Left
TFG 46DS U2
TFG 46DS R2
TFG 46DS L2
DC24V
AC/DC110V
AC/DC220V
2 pole
3 pole
4 pole
MIF 40D 3
MIF 40D 3
MIF 40D 4
TFH 46DS
Mechanical interlock
PLD 40D
Padlock plate3)
Extension handle
THA 46D
4)
Mounting
Structure
Plug-in 1)
Mounting base
TDM 4BA 3)
TDM 4BA
Connection 2C contact
TYA 5/2 4)
block 2)
TYA 5/5 4)
5C contact
Terminal
2 pole (4EA/SET) 3 pole (6EA/SET) 4 pole (8EA/SET)
TBB 4S 2
TBB 4S 4
4EA/SET
CTB 40D 3S
2 pole
Terminal cover 1)
Interpole barrier 2)
TBB 4S 3
3EA/SET
TCF 40D 3
2EA/SET
CTB 40D 4S
3 pole
4 pole
TCF 40D 3
TCF 40D 4
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 4EA, 3 pole 4EA, 4 pole 6EA
U-Series
UCB400R
30kA
UCB400S
42kA
UCB400H
65kA
UCB400L
100kA
Rated
current
2 pole
Code
Unit
(EA)
3 pole
Code
Unit
(EA)
4 pole
Code
Unit
(EA)
250A
300A
320A
350A
400A
250A
300A
320A
350A
400A
250A
300A
320A
350A
400A
250A
300A
320A
350A
400A
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
50
Model /
Breaking capacity at
AC380/415V
UCB400R
30kA
UCB400S
42kA
UCB400H
65kA
UCB400L
100kA
78
Rated
current
2 pole
Code
Unit
(EA)
3 pole
Code
Unit
(EA)
4 pole
Code
Unit
(EA)
250A
300A
320A
350A
400A
250A
300A
320A
350A
400A
250A
300A
320A
350A
400A
250A
300A
320A
350A
400A
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
MCCB
UCB400R
30kA
UCB400S
42kA
UCB400H
65kA
UCB400L
100kA
Rated
current
2 pole
Code
Unit
(EA)
3 pole
Code
Unit
(EA)
4 pole
Code
Unit
(EA)
250A
300A
320A
350A
400A
250A
300A
320A
350A
400A
250A
300A
320A
350A
400A
250A
300A
320A
350A
400A
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
50
Model /
Breaking capacity at
AC380/415V
UCB400R
30kA
UCB400S
42kA
UCB400H
65kA
UCB400L
100kA
Rated
current
2 pole
Code
Unit
(EA)
3 pole
Code
Unit
(EA)
4 pole
Code
Unit
(EA)
Specification Category
250A
300A
320A
350A
400A
250A
300A
320A
350A
400A
250A
300A
320A
Screw type
terminal
UCB400S 4PT5S0000C 00400F 2
connection,
UCB400H 4PT5S0000C 00250F 2 No option,
UCB400H 4PT5S0000C 00300F 2
50/60Hz
UCB400H 4PT5S0000C 00320F 2
350A
400A
250A
300A
320A
350A
400A
MCCB
/M2
U-Series
UCB630R
UCB630S
UCB630H
2, 3, 4
IP20
UCB630L
Utilization category
Suitability of isolation
Protection
500, 630
AC690
AC660
DC250
Rated impulse withstand voltage [Uimp] (kV)
Rated
short-circuit
Ultimate
breaking
[Icu]
capacity
(kA r.m.s.)
IEC 60947-2
K 60947-2
AC600/660V, 50-60Hz
22
25
35
35
AC480/500V, 50-60Hz
25
45
50
65
AC440/460V, 50-60Hz
35
50
65
85
AC380/415V, 50-60Hz
45
65
85
100
AC220/240V, 50-60Hz
50
100
100
125
DC250V
20
40
40
40
DC125V
30
50
50
60
50
Fixed thermal,
Fixed instantaneous
Adjustable thermal,
Fixed instantaneous
INST
10 In
LTD
(0.8 0.9 1) In
INST
10 In
Plug-in
1)
1)
Screw
Terminal connection
Durability
(times)
Dimensions
(mm)
Bus bar
Mechanical operation
20,000
Electrical operation
2/3/4P
6,000
a
Width
210 /210/280
Height
280
Depth
110
d
Weight (kg, breaker only) 2/3/4P
2)
145
8.7/9.5/12.5
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.
80
MCCB
Accessories
Signal
1C, right-hand-side
Auxiliary switch
AUX 46D R1
1C, left-hand-side
ALT 46D L1
Shunt trip 1)
Under voltage trip 2)
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
SHT 46D A
SHT 46D C
SHT 46D F
SHT 46D H
SHT 46D B
SHT 46D D
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
AC440-480V
UVT 46D L
UVT 46D N
UVT 46D P
UVT 46D Q
UVT 46D R
UVT 46D J
AC440-480V
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.
Operating
Upper
TFG 46DS U2
Right
TFG 46DS R2
TFH 46DS
AC/DC110V
MOT 68E ADC110
3 pole
MIF 80E 3
PLD 40D
THA 46D
DC24V
MOT 68E DC24
2 pole
MIF 80E 3
Motor operator 2)
Mechanical interlock
Padlock plate3)
Extension handle 4)
Left
TFG 46DS L2
AC/DC220V
MOT 68E ADC220
4 pole
MIF 80E 4
`
Mounting
Plug-in 1)
Structure
Mounting base
Connection 2C contact
block 2)
5C contact
Terminal
2 pole (4EA/SET) 3 pole (6EA/SET) 4 pole (8EA/SET)
TBB 6S 2
TBB 6S 3
TBB 6S 4
3EA/SET
4EA/SET
CTB 80E 3S
CTB 80E 4S
2 pole
3 pole
4 pole
TCF 80E 3
TCF 80E 3
TCF 80E 4
2EA/SET
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 4EA, 3 pole 4EA, 4 pole 6EA
U-Series
UCB800R
UCB800S
UCB800H
2, 3, 4
IP20
UCB800L
Utilization category
Suitability of isolation
Protection
700, 800
AC690
AC660
DC250
Rated impulse withstand voltage [Uimp] (kV)
AC600/660V, 50-60Hz
25
25
35
35
Rated
short-circuit
Ultimate
breaking
[Icu]
capacity
(kA r.m.s.)
AC480/500V, 50-60Hz
35
45
50
65
AC440/460V, 50-60Hz
35
50
65
85
AC380/415V, 50-60Hz
45
65
85
100
AC220/240V, 50-60Hz
50
100
100
125
IEC 60947-2
K 60947-2
DC250V
20
40
40
40
DC125V
30
50
50
60
50
Fixed thermal,
Fixed instantaneous
Adjustable thermal,
Fixed instantaneous
INST
10 In
LTD
(0.8 0.9 1) In
INST
10 In
Plug-in
Terminal connection
1)
1)
Screw
Bus bar
Durability
(times)
Dimensions
(mm)
Mechanical operation
10,000
Electrical operation
2/3/4P
3,000
a
Width
210 /210/280
Height
280
Depth
110
d
Weight (kg, breaker only) 2/3/4P
2)
145
8.7/9.5/12.5
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) Available for 3P breaker
2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.
82
MCCB
Accessories
Signal
1C, right-hand-side
Auxiliary switch
AUX 46D R1
1C, left-hand-side
ALT 46D L1
1)
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
SHT 46D A
SHT 46D C
SHT 46D F
SHT 46D H
SHT 46D B
SHT 46D D
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
AC440-480V
UVT 46D L
UVT 46D N
UVT 46D P
UVT 46D Q
UVT 46D R
UVT 46D J
AC440-480V
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.
Operating
Upper
TFG 46DS U2
Right
TFG 46DS R2
TFH 46DS
AC/DC110V
MOT 68E ADC110
3 pole
MIF 80E 3
PLD 40D
THA 46D
DC24V
MOT 68E DC24
2 pole
MIF 80E 3
Motor operator 2)
Mechanical interlock
Padlock plate3)
Extension handle 4)
Left
TFG 46DS L2
AC/DC220V
MOT 68E ADC220
4 pole
MIF 80E 4
Mounting
Plug-in 1)
Structure
Mounting base
Connection 2C contact
block 2)
5C contact
Terminal
2 pole (4EA/SET) 3 pole (6EA/SET) 4 pole (8EA/SET)
TBB 8S 2
TBB 8S 3
TBB 8S 4
3EA/SET
4EA/SET
CTB 80E 3S
CTB 80E 4S
2 pole
3 pole
4 pole
TCF 80E 3
TCF 80E 3
TCF 80E 4
2EA/SET
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 2 pole 4EA, 3 pole 4EA, 4 pole 6EA
U-Series
Rated
current
2 pole
Code
3 pole
Unit
(EA)
Code
4 pole
Unit
(EA)
Code
Unit
(EA)
UCB630R
45kA
500A
630A
UCB630S
65kA
500A
630A
UCB630H
85kA
500A
630A
UCB630L
100kA
500A
630A
2 pole
3 pole
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
50
Model /
Breaking
capacity at
AC380/415V
Rated
current
Code
Unit
(EA)
Code
4 pole
Unit
(EA)
Code
Unit
(EA)
UCB630R
45kA
500A
630A
UCB630S
65kA
500A
630A
UCB630H
85kA
500A
630A
UCB630L
100kA
500A
630A
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
Rated
current
2 pole
Code
3 pole
Unit
(EA)
Code
4 pole
Unit
(EA)
Code
Unit
(EA)
UCB630R
45kA
500A
630A
UCB630S
65kA
500A
630A
UCB630H
85kA
500A
630A
UCB630L
100kA
500A
630A
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
50
Model /
Breaking
capacity at
AC380/415V
84
Rated
current
2 pole
Code
3 pole
Unit
(EA)
Code
4 pole
Unit
(EA)
Code
Unit
(EA)
UCB630R
45kA
500A
630A
UCB630S
65kA
500A
630A
UCB630H
85kA
500A
630A
UCB630L
100kA
500A
630A
Specification Category
MCCB
/M2
MCCB
Rated
current
2 pole
3 pole
Code
Unit
(EA)
Code
4 pole
Unit
(EA)
Code
Unit
(EA)
UCB800R
45kA
700A
800A
UCB800S
65kA
700A
800A
UCB800H
85kA
700A
800A
UCB800L
100kA
700A
800A
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
50
Model /
Breaking
capacity at
AC380/415V
Rated
current
2 pole
3 pole
Code
Unit
(EA)
Code
4 pole
Unit
(EA)
Code
Unit
(EA)
UCB800R
45kA
700A
800A
UCB800S
65kA
700A
800A
UCB800H
85kA
700A
800A
UCB800L
100kA
700A
800A
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
Rated
current
2 pole
Code
3 pole
Unit
(EA)
Code
4 pole
Unit
(EA)
Code
Unit
(EA)
UCB800R
45kA
700A
800A
UCB800S
65kA
700A
800A
UCB800H
85kA
700A
800A
UCB800L
100kA
700A
800A
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
50
Model /
Breaking
capacity at
AC380/415V
Rated
current
2 pole
Code
3 pole
Unit
(EA)
Code
4 pole
Unit
(EA)
Code
Unit
(EA)
UCB800R
45kA
700A
800A
UCB800S
65kA
700A
800A
UCB800H
85kA
700A
800A
UCB800L
100kA
700A
800A
Specification Category
MCCB
/M2
U-Series
UCB1000S
UCB1000L
3, 4
IP20
Utilization category
Suitability of isolation
Protection
505-1,000
AC750
AC690
Rating
Rated impulse withstand voltage [Uimp] (kV)
Rated
short-circuit
breaking
capacity
Ultimate
[Icu]
(kA r.m.s.)
IEC 60947-2
K 60947-2
AC600/660V, 50-60Hz
40
60
AC480/500V, 50-60Hz
75
100
AC440/460V, 50-60Hz
75
100
AC380/415V, 50-60Hz
100
130
AC220/240V, 50-60Hz
100
150
Trip
mechanism
Electronic
& Protection
characteristics
50
1)
LTD
STD
(2-4-6-8-10) Ir
Instantaneous
INST
(3-6-8-10-11) In
GFT
(0.2-0.3-0.4) In
Pre-trip alarm
PTA
0.9 In
(0.5-1)
In (15 setting)
I2T lamp
Pick-up LED
Mounting
Terminal connection
Durability
(times)
Bus bar
Mechanical operation
10,000
Electrical operation
3,000
Dimensions
(mm)
3/4P
Width
210/280
210/280
Height
370
370
Depth
110
200
159
249
13/17
25/33
d
Weight (kg, breaker only)
3/4P
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) (0.5-1): (0.63-0.8-1)x(0.8-0.85-0.9-0.95-1)
86
MCCB
Accessories
Signal
1C, right-hand-side 2C, right-hand-side 3C, right-hand-side
Auxiliary switch
AUX 80NE R1
AUX 80NE R2
AUX 80NE R3
1C, right-hand-side
ALT 80NE R1
1)
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
AC440-480V
SHT 120NE A
SHT 120NE C
SHT 120NE F
SHT 120NE H
SHT 120NE B
SHT 120NE D
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
AC440-480V
UVT 120NE J
UVT 120NE L
UVT 120NE N
UVT 120NE P
UVT 120NE Q
UVT 120NE R
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Operating
Motor operator 1)
DC24V
AC/DC110V
AC/DC220V
Padlock plate2)
PLD 120NE
Extension handle 3)
THA 120NE
Terminal
Interpole barrier 1)
2EA/SET
TQQ 80NE 3P
Rated
current
UCB1000S 100kA
1000A
3 pole
Code
4 pole
Unit
(EA)
Code
Unit
(EA)
UCB1000L 130kA
1000A
UCB1000S 100kA
1000A
UCB1000L 130kA
1000A
Specification
Bus bar type
terminal connection,
No option, 50Hz
Bus bar type
terminal connection,
No option, 60Hz
Category
MCCB
/M3
Rated
current
UCB1000S 100kA
1000A
UCB1000L 130kA
1000A
UCB1000S 100kA
1000A
UCB1000L 130kA
1000A
3 pole
Code
4 pole
Unit
(EA)
Code
Unit
(EA)
Specification
Bus bar type
terminal connection,
No option, 50Hz
Bus bar type
terminal connection,
No option, 60Hz
Category
MCCB
/M3
U-Series
UCB1250S
UCB1250L
3, 4
IP20
Utilization category
Suitability of isolation
Protection
630-1,250
AC750
AC690
Rating
Rated impulse withstand voltage [Uimp] (kV)
Rated
short-circuit
breaking
capacity
Ultimate
[Icu]
(kA r.m.s.)
IEC 60947-2
K 60947-2
AC600/660V, 50-60Hz
40
60
AC480/500V, 50-60Hz
75
100
AC440/460V, 50-60Hz
75
100
AC380/415V, 50-60Hz
100
130
AC220/240V, 50-60Hz
100
150
Trip
mechanism
Electronic
& Protection
characteristics
50
1)
LTD
STD
(2-4-6-8-10) Ir
Instantaneous
INST
(3-6-8-10-11) In
GFT
(0.2-0.3-0.4) In
Pre-trip alarm
PTA
0.9 In
(0.5-1)
In (15 setting)
I2T lamp
Pick-up LED
Mounting
Terminal connection
Durability
(times)
Bus bar
Mechanical operation
10,000
3,000
Dimensions
(mm)
3/4P
Width
210/280
210/280
Height
370
370
Depth
110
200
159
249
13.5/17.5
25.5/33.5
d
Weight (kg, breaker only)
3/4P
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) (0.5-1): (0.63-0.8-1)x(0.8-0.85-0.9-0.95-1)
88
MCCB
Accessories
Signal
1C, right-hand-side 2C, right-hand-side 3C, right-hand-side
Auxiliary switch
AUX 80NE R1
AUX 80NE R2
AUX 80NE R3
1C, right-hand-side
ALT 80NE R1
1)
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
AC440-480V
SHT 120NE A
SHT 120NE C
SHT 120NE F
SHT 120NE H
SHT 120NE B
SHT 120NE D
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
AC440-480V
UVT 120NE J
UVT 120NE L
UVT 120NE N
UVT 120NE P
UVT 120NE Q
UVT 120NE R
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Operating
Motor operator 1)
DC24V
AC/DC110V
AC/DC220V
Padlock plate2)
PLD 120NE
Extension handle 3)
THA 120NE
Terminal
Interpole barrier 1)
2EA/SET
TQQ 80NE 3P
Rated
current
UCB1250S 100kA
1250A
3 pole
Code
4 pole
Unit
(EA)
Code
Unit
(EA)
UCB1250L 130kA
1250A
UCB1250S 100kA
1250A
UCB1250L 130kA
1250A
Specification
Bus bar type
terminal connection,
No option, 50Hz
Bus bar type
terminal connection,
No option, 60Hz
Category
MCCB
/M3
Rated
current
UCB1250S 100kA
1250A
3 pole
Code
4 pole
Unit
(EA)
Code
UCB1250S 4PEGB0000X 01250
Unit
(EA)
UCB1250L 130kA
1250A
UCB1250S 100kA
1250A
UCB1250L 130kA
1250A
Specification
Bus bar type
terminal connection,
No option, 50Hz
Bus bar type
terminal connection,
No option, 60Hz
Category
MCCB
/M3
U-Series
UCB1600S
IP20
Utilization category
Suitability of isolation
Protection
640-1,600
AC750
AC690
Rating
Rated impulse withstand voltage [Uimp] (kV)
Rated
short-circuit
breaking
capacity
Ultimate
[Icu]
(kA r.m.s.)
IEC 60947-2
K 60947-2
AC600/660V, 50-60Hz
25
AC480/500V, 50-60Hz
35
AC440/460V, 50-60Hz
45
AC380/415V, 50-60Hz
65
AC220/240V, 50-60Hz
100
LTD
(0.4-1)
Instantaneous
INST
(2-3-4-5-6-7-8-10) In
In (8 setting)
Pick-up LED
Terminal connection
Durability
(times)
50
1)
Bus bar
Mechanical operation
10,000
Electrical operation
3,000
Dimensions
(mm)
3/4P
Width
210
Height
371
Depth
151
d
Weight (kg, breaker only)
3/4P
215
27
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) (0.4-1): (0.4-0.5-0.6-0.7-0.8-0.9-0.95-1)
90
MCCB
Accessories
Signal
1C, right-hand-side 2C, right-hand-side
Auxiliary switch
AUX 160NE R1
Shunt trip 1)
Under voltage trip 2)
AUX 160NE R2
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380V
SHT 160NE A
SHT 160NE C
SHT 160NE F
SHT 160NE H
SHT 160NE B
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380V
AC440V
UVT 160NE P
UVT 160NE Q
UVT 160NE R
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Operating
Operating handle
Motor operator
1)
TFH 160NE
Extended type
AC220V
THA 160NE
Extension handle 2)
Terminal
Terminal cover 1)
Interpole barrier 2)
TCF 160NE 3
4EA/SET
TQQ 160NE 3P
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
3 pole
Rated
current
Code
Unit (EA)
1600A
Specification
Category
MCCB/M3
U-Series
UPB100S
UPB100H
UPB100L
UPB100X
3, 4
IP20
A
10
50
65
85
100
501)
651)
25
85
150
150
200
1001)
1)
100
10 In
(0.8 0.9 1) In
10 In
50,55,63,70,80,90,100,115,125
(NON-2-3-4-5-6-7-8-9-10) Ir
11 In
0.9 Ir
2)
2)
25,000
10,000
105/140
165
86.5
112
1.8/2.2
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) DC is not applicable for electronic breaker. 2) Available for 3P breaker
Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip 1)
Under voltage trip 2)
92
1C, right-hand-side
AUX 12UP R1
1C, left-hand-side
ALT 12UP L1
DC24V
SHT 12UP A
DC24V
UVT 12UP J
DC100-110V
SHT 12UP C
DC100-110V
UVT 12UP L
AC100-120V
SHT 12UP F
AC100-120V
UVT 12UP N
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.
AC200-230V
SHT 12UP H
AC200-230V
UVT 12UP P
AC380-415V
SHT 12UP B
AC380-415V
UVT 12UP Q
AC440-480V
SHT 12UP D
AC440-480V
UVT 12UP R
MCCB
Operating
Upper
TFG 12UPS U4
TFG 12UPL U4
Right
TFG 12UPS R4
TFH 12UPS
TFH 12UPL
AC/DC110V
MOT 12UP ADC110
DC24V
MOT 12UP DC24
3 pole
MIF 12UP 3
Motor operator 2)
Mechanical interlock
Left
TFG 12UPS L4
TFG 12UPL L4
Padlock plate3)
AC/DC220V
MOT 12UP ADC220
4 pole
MIF 12UP 4
PLD 12UP
Mounting
Plug-in 1)
Structure
Mounting base
Connection 6C contact
block 2)
12C contact
Terminal
Terminal bus bar
Cage terminal block
Terminal cover
1)
Interpole barrier 2)
3 pole (6EA/SET)
4 pole (8EA/SET)
3EA/SET
4EA/SET
3 pole
4 pole
4EA/SET
TBB 12NE 3
TBB 12NE 4
CTB 12UP 3S
CTB 12UP 4S
TCF 12UP 3
TCF 12UP 4
TQQ 12NE 3P
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 3 pole 4EA, 4 pole 6EA
Rated
current
3 pole
Code
4 pole
Unit
(EA)
Code
Unit
(EA)
UPB100S 85kA
125A
UPB100H 100kA
125A
UPB100L 130kA
125A
UPB100X 150kA
125A
UPB100S 85kA
125A
UPB100H 100kA
125A
UPB100L 130kA
125A
UPB100X 150kA
125A
Specification
Category
Screw type
terminal
connection,
No option,
50Hz
MCCB/M3
Screw type
terminal
connection,
No option,
60Hz
U-Series
UPB100S
85kA
UPB100H
100kA
UPB100L
130kA
UPB100X
150kA
94
Rated
current
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
3 pole
Code
UPB100S 3PT4S0000C 00015
UPB100S 3PT4S0000C 00016
UPB100S 3PT4S0000C 00020
UPB100S 3PT4S0000C 00025
UPB100S 3PT4S0000C 00030
UPB100S 3PT4S0000C 00032
UPB100S 3PT4S0000C 00040
UPB100S 3PT4S0000C 00050
UPB100S 3PT4S0000C 00060
UPB100S 3PT4S0000C 00063
UPB100S 3PT4S0000C 00075
UPB100S 3PT4S0000C 00080
UPB100S 3PT4S0000C 00100
UPB100S 3PT4S0000C 00125
UPB100H 3PT4S0000C 00015
UPB100H 3PT4S0000C 00016
UPB100H 3PT4S0000C 00020
UPB100H 3PT4S0000C 00025
UPB100H 3PT4S0000C 00030
UPB100H 3PT4S0000C 00032
UPB100H 3PT4S0000C 00040
UPB100H 3PT4S0000C 00050
UPB100H 3PT4S0000C 00060
UPB100H 3PT4S0000C 00063
UPB100H 3PT4S0000C 00075
UPB100H 3PT4S0000C 00080
UPB100H 3PT4S0000C 00100
UPB100H 3PT4S0000C 00125
UPB100L 3PT4S0000C 00015
UPB100L 3PT4S0000C 00016
UPB100L 3PT4S0000C 00020
UPB100L 3PT4S0000C 00025
UPB100L 3PT4S0000C 00030
UPB100L 3PT4S0000C 00032
UPB100L 3PT4S0000C 00040
UPB100L 3PT4S0000C 00050
UPB100L 3PT4S0000C 00060
UPB100L 3PT4S0000C 00063
UPB100L 3PT4S0000C 00075
UPB100L 3PT4S0000C 00080
UPB100L 3PT4S0000C 00100
UPB100L 3PT4S0000C 00125
UPB100X 3PT4S0000C 00015
UPB100X 3PT4S0000C 00016
UPB100X 3PT4S0000C 00020
UPB100X 3PT4S0000C 00025
UPB100X 3PT4S0000C 00030
UPB100X 3PT4S0000C 00032
UPB100X 3PT4S0000C 00040
UPB100X 3PT4S0000C 00050
UPB100X 3PT4S0000C 00060
UPB100X 3PT4S0000C 00063
UPB100X 3PT4S0000C 00075
UPB100X 3PT4S0000C 00080
UPB100X 3PT4S0000C 00100
UPB100X 3PT4S0000C 00125
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
4 pole
Code
UPB100S 4PT4S0000C 00015
UPB100S 4PT4S0000C 00016
UPB100S 4PT4S0000C 00020
UPB100S 4PT4S0000C 00025
UPB100S 4PT4S0000C 00030
UPB100S 4PT4S0000C 00032
UPB100S 4PT4S0000C 00040
UPB100S 4PT4S0000C 00050
UPB100S 4PT4S0000C 00060
UPB100S 4PT4S0000C 00063
UPB100S 4PT4S0000C 00075
UPB100S 4PT4S0000C 00080
UPB100S 4PT4S0000C 00100
UPB100S 4PT4S0000C 00125
UPB100H 4PT4S0000C 00015
UPB100H 4PT4S0000C 00016
UPB100H 4PT4S0000C 00020
UPB100H 4PT4S0000C 00025
UPB100H 4PT4S0000C 00030
UPB100H 4PT4S0000C 00032
UPB100H 4PT4S0000C 00040
UPB100H 4PT4S0000C 00050
UPB100H 4PT4S0000C 00060
UPB100H 4PT4S0000C 00063
UPB100H 4PT4S0000C 00075
UPB100H 4PT4S0000C 00080
UPB100H 4PT4S0000C 00100
UPB100H 4PT4S0000C 00125
UPB100L 4PT4S0000C 00015
UPB100L 4PT4S0000C 00016
UPB100L 4PT4S0000C 00020
UPB100L 4PT4S0000C 00025
UPB100L 4PT4S0000C 00030
UPB100L 4PT4S0000C 00032
UPB100L 4PT4S0000C 00040
UPB100L 4PT4S0000C 00050
UPB100L 4PT4S0000C 00060
UPB100L 4PT4S0000C 00063
UPB100L 4PT4S0000C 00075
UPB100L 4PT4S0000C 00080
UPB100L 4PT4S0000C 00100
UPB100L 4PT4S0000C 00125
UPB100X 4PT4S0000C 00015
UPB100X 4PT4S0000C 00016
UPB100X 4PT4S0000C 00020
UPB100X 4PT4S0000C 00025
UPB100X 4PT4S0000C 00030
UPB100X 4PT4S0000C 00032
UPB100X 4PT4S0000C 00040
UPB100X 4PT4S0000C 00050
UPB100X 4PT4S0000C 00060
UPB100X 4PT4S0000C 00063
UPB100X 4PT4S0000C 00075
UPB100X 4PT4S0000C 00080
UPB100X 4PT4S0000C 00100
UPB100X 4PT4S0000C 00125
Unit
(EA)
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Specification
Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
MCCB
50
Model /
Breaking capacity at
AC380/415V
UPB100S
85kA
UPB100H
100kA
UPB100L
130kA
UPB100X
150kA
Rated
current
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
3 pole
Code
UPB100S 3PT5S0000C 00015
UPB100S 3PT5S0000C 00016
UPB100S 3PT5S0000C 00020
UPB100S 3PT5S0000C 00025
UPB100S 3PT5S0000C 00030
UPB100S 3PT5S0000C 00032
UPB100S 3PT5S0000C 00040
UPB100S 3PT5S0000C 00050
UPB100S 3PT5S0000C 00060
UPB100S 3PT5S0000C 00063
UPB100S 3PT5S0000C 00075
UPB100S 3PT5S0000C 00080
UPB100S 3PT5S0000C 00100
UPB100S 3PT5S0000C 00125
UPB100H 3PT5S0000C 00015
UPB100H 3PT5S0000C 00016
UPB100H 3PT5S0000C 00020
UPB100H 3PT5S0000C 00025
UPB100H 3PT5S0000C 00030
UPB100H 3PT5S0000C 00032
UPB100H 3PT5S0000C 00040
UPB100H 3PT5S0000C 00050
UPB100H 3PT5S0000C 00060
UPB100H 3PT5S0000C 00063
UPB100H 3PT5S0000C 00075
UPB100H 3PT5S0000C 00080
UPB100H 3PT5S0000C 00100
UPB100H 3PT5S0000C 00125
UPB100L 3PT5S0000C 00015
UPB100L 3PT5S0000C 00016
UPB100L 3PT5S0000C 00020
UPB100L 3PT5S0000C 00025
UPB100L 3PT5S0000C 00030
UPB100L 3PT5S0000C 00032
UPB100L 3PT5S0000C 00040
UPB100L 3PT5S0000C 00050
UPB100L 3PT5S0000C 00060
UPB100L 3PT5S0000C 00063
UPB100L 3PT5S0000C 00075
UPB100L 3PT5S0000C 00080
UPB100L 3PT5S0000C 00100
UPB100L 3PT5S0000C 00125
UPB100X 3PT5S0000C 00015
UPB100X 3PT5S0000C 00016
UPB100X 3PT5S0000C 00020
UPB100X 3PT5S0000C 00025
UPB100X 3PT5S0000C 00030
UPB100X 3PT5S0000C 00032
UPB100X 3PT5S0000C 00040
UPB100X 3PT5S0000C 00050
UPB100X 3PT5S0000C 00060
UPB100X 3PT5S0000C 00063
UPB100X 3PT5S0000C 00075
UPB100X 3PT5S0000C 00080
UPB100X 3PT5S0000C 00100
UPB100X 3PT5S0000C 00125
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
4 pole
Code
UPB100S 4PT5S0000C 00015
UPB100S 4PT5S0000C 00016
UPB100S 4PT5S0000C 00020
UPB100S 4PT5S0000C 00025
UPB100S 4PT5S0000C 00030
UPB100S 4PT5S0000C 00032
UPB100S 4PT5S0000C 00040
UPB100S 4PT5S0000C 00050
UPB100S 4PT5S0000C 00060
UPB100S 4PT5S0000C 00063
UPB100S 4PT5S0000C 00075
UPB100S 4PT5S0000C 00080
UPB100S 4PT5S0000C 00100
UPB100S 4PT5S0000C 00125
UPB100H 4PT5S0000C 00015
UPB100H 4PT5S0000C 00016
UPB100H 4PT5S0000C 00020
UPB100H 4PT5S0000C 00025
UPB100H 4PT5S0000C 00030
UPB100H 4PT5S0000C 00032
UPB100H 4PT5S0000C 00040
UPB100H 4PT5S0000C 00050
UPB100H 4PT5S0000C 00060
UPB100H 4PT5S0000C 00063
UPB100H 4PT5S0000C 00075
UPB100H 4PT5S0000C 00080
UPB100H 4PT5S0000C 00100
UPB100H 4PT5S0000C 00125
UPB100L 4PT5S0000C 00015
UPB100L 4PT5S0000C 00016
UPB100L 4PT5S0000C 00020
UPB100L 4PT5S0000C 00025
UPB100L 4PT5S0000C 00030
UPB100L 4PT5S0000C 00032
UPB100L 4PT5S0000C 00040
UPB100L 4PT5S0000C 00050
UPB100L 4PT5S0000C 00060
UPB100L 4PT5S0000C 00063
UPB100L 4PT5S0000C 00075
UPB100L 4PT5S0000C 00080
UPB100L 4PT5S0000C 00100
UPB100L 4PT5S0000C 00125
UPB100X 4PT5S0000C 00015
UPB100X 4PT5S0000C 00016
UPB100X 4PT5S0000C 00020
UPB100X 4PT5S0000C 00025
UPB100X 4PT5S0000C 00030
UPB100X 4PT5S0000C 00032
UPB100X 4PT5S0000C 00040
UPB100X 4PT5S0000C 00050
UPB100X 4PT5S0000C 00060
UPB100X 4PT5S0000C 00063
UPB100X 4PT5S0000C 00075
UPB100X 4PT5S0000C 00080
UPB100X 4PT5S0000C 00100
UPB100X 4PT5S0000C 00125
Unit
(EA)
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Specification
Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
U-Series
UPB100S
85kA
UPB100H
100kA
UPB100L
130kA
UPB100X
150kA
96
Rated
current
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
3 pole
Code
UPB100S 3PT4S0000C 00015F
UPB100S 3PT4S0000C 00016F
UPB100S 3PT4S0000C 00020F
UPB100S 3PT4S0000C 00025F
UPB100S 3PT4S0000C 00030F
UPB100S 3PT4S0000C 00032F
UPB100S 3PT4S0000C 00040F
UPB100S 3PT4S0000C 00050F
UPB100S 3PT4S0000C 00060F
UPB100S 3PT4S0000C 00063F
UPB100S 3PT4S0000C 00075F
UPB100S 3PT4S0000C 00080F
UPB100S 3PT4S0000C 00100F
UPB100S 3PT4S0000C 00125F
UPB100H 3PT4S0000C 00015F
UPB100H 3PT4S0000C 00016F
UPB100H 3PT4S0000C 00020F
UPB100H 3PT4S0000C 00025F
UPB100H 3PT4S0000C 00030F
UPB100H 3PT4S0000C 00032F
UPB100H 3PT4S0000C 00040F
UPB100H 3PT4S0000C 00050F
UPB100H 3PT4S0000C 00060F
UPB100H 3PT4S0000C 00063F
UPB100H 3PT4S0000C 00075F
UPB100H 3PT4S0000C 00080F
UPB100H 3PT4S0000C 00100F
UPB100H 3PT4S0000C 00125F
UPB100L 3PT4S0000C 00015F
UPB100L 3PT4S0000C 00016F
UPB100L 3PT4S0000C 00020F
UPB100L 3PT4S0000C 00025F
UPB100L 3PT4S0000C 00030F
UPB100L 3PT4S0000C 00032F
UPB100L 3PT4S0000C 00040F
UPB100L 3PT4S0000C 00050F
UPB100L 3PT4S0000C 00060F
UPB100L 3PT4S0000C 00063F
UPB100L 3PT4S0000C 00075F
UPB100L 3PT4S0000C 00080F
UPB100L 3PT4S0000C 00100F
UPB100L 3PT4S0000C 00125F
UPB100X 3PT4S0000C 00015F
UPB100X 3PT4S0000C 00016F
UPB100X 3PT4S0000C 00020F
UPB100X 3PT4S0000C 00025F
UPB100X 3PT4S0000C 00030F
UPB100X 3PT4S0000C 00032F
UPB100X 3PT4S0000C 00040F
UPB100X 3PT4S0000C 00050F
UPB100X 3PT4S0000C 00060F
UPB100X 3PT4S0000C 00063F
UPB100X 3PT4S0000C 00075F
UPB100X 3PT4S0000C 00080F
UPB100X 3PT4S0000C 00100F
UPB100X 3PT4S0000C 00125F
Unit
(EA)
4 pole
Code
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Specification
Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
MCCB
50
Model /
Breaking capacity at
AC380/415V
UPB100S
85kA
UPB100H
100kA
UPB100L
130kA
UPB100X
150kA
Rated
current
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
75A
80A
100A
125A
3 pole
Code
UPB100S 3PT5S0000C 00015F
UPB100S 3PT5S0000C 00016F
UPB100S 3PT5S0000C 00020F
UPB100S 3PT5S0000C 00025F
UPB100S 3PT5S0000C 00030F
UPB100S 3PT5S0000C 00032F
UPB100S 3PT5S0000C 00040F
UPB100S 3PT5S0000C 00050F
UPB100S 3PT5S0000C 00060F
UPB100S 3PT5S0000C 00063F
UPB100S 3PT5S0000C 00075F
UPB100S 3PT5S0000C 00080F
UPB100S 3PT5S0000C 00100F
UPB100S 3PT5S0000C 00125F
UPB100H 3PT5S0000C 00015F
UPB100H 3PT5S0000C 00016F
UPB100H 3PT5S0000C 00020F
UPB100H 3PT5S0000C 00025F
UPB100H 3PT5S0000C 00030F
UPB100H 3PT5S0000C 00032F
UPB100H 3PT5S0000C 00040F
UPB100H 3PT5S0000C 00050F
UPB100H 3PT5S0000C 00060F
UPB100H 3PT5S0000C 00063F
UPB100H 3PT5S0000C 00075F
UPB100H 3PT5S0000C 00080F
UPB100H 3PT5S0000C 00100F
UPB100H 3PT5S0000C 00125F
UPB100L 3PT5S0000C 00015F
UPB100L 3PT5S0000C 00016F
UPB100L 3PT5S0000C 00020F
UPB100L 3PT5S0000C 00025F
UPB100L 3PT5S0000C 00030F
UPB100L 3PT5S0000C 00032F
UPB100L 3PT5S0000C 00040F
UPB100L 3PT5S0000C 00050F
UPB100L 3PT5S0000C 00060F
UPB100L 3PT5S0000C 00063F
UPB100L 3PT5S0000C 00075F
UPB100L 3PT5S0000C 00080F
UPB100L 3PT5S0000C 00100F
UPB100L 3PT5S0000C 00125F
UPB100X 3PT5S0000C 00015F
UPB100X 3PT5S0000C 00016F
UPB100X 3PT5S0000C 00020F
UPB100X 3PT5S0000C 00025F
UPB100X 3PT5S0000C 00030F
UPB100X 3PT5S0000C 00032F
UPB100X 3PT5S0000C 00040F
UPB100X 3PT5S0000C 00050F
UPB100X 3PT5S0000C 00060F
UPB100X 3PT5S0000C 00063F
UPB100X 3PT5S0000C 00075F
UPB100X 3PT5S0000C 00080F
UPB100X 3PT5S0000C 00100F
UPB100X 3PT5S0000C 00125F
Unit
(EA)
4 pole
Code
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Specification
Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
U-Series
UPB160S
UPB160H
UPB160X
3, 4
IP20
A
UPB160L
10
50
65
85
100
50 1)
65 1)
25
85
150
150
200
100 1)
100 1)
10 In
(0.8 0.9 1) In
10 In
(0.8 0.9 1) In
(5-6-7-8-9-10) In
63,70,80,90,100,110,125,140,160
(NON-2-3-4-5-6-7-8-9-10) Ir
11 In
0.9 Ir
2)
2)
25,000
10,000
105/140
165
86.5
112
2.0/2.4
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) DC is not applicable for electronic breaker. 2) Available for 3P breaker
Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip 1)
Under voltage trip 2)
98
1C, right-hand-side
AUX 12UP R1
1C, left-hand-side
ALT 12UP L1
DC24V
SHT 12UP A
DC24V
UVT 12UP J
DC100-110V
SHT 12UP C
DC100-110V
UVT 12UP L
AC100-120V
SHT 12UP F
AC100-120V
UVT 12UP N
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.
AC200-230V
SHT 12UP H
AC200-230V
UVT 12UP P
AC380-415V
SHT 12UP B
AC380-415V
UVT 12UP Q
AC440-480V
SHT 12UP D
AC440-480V
UVT 12UP R
MCCB
Operating
Upper
TFG 12UPS U4
TFG 12UPL U4
Right
TFG 12UPS R4
TFH 12UPS
TFH 12UPL
AC/DC110V
MOT 12UP ADC110
DC24V
MOT 12UP DC24
3 pole
MIF 12UP 3
Motor operator 2)
Mechanical interlock
Left
TFG 12UPS L4
TFG 12UPL L4
AC/DC220V
MOT 12UP ADC220
4 pole
MIF 12UP 4
PLD 12UP
Padlock plate3)
1) For detail type information, please refer to page 197-205.
2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.
Mounting
Plug-in 1)
Structure
Mounting base
Connection 6C contact
block 2)
12C contact
Terminal
Terminal bus bar
Cage terminal block
Terminal cover 1)
Interpole barrier 2)
3 pole (6EA/SET)
4 pole (8EA/SET)
3EA/SET
4EA/SET
3 pole
4 pole
4EA/SET
TBB 12NE 3
TBB 12NE 4
CTB 12UP 3S
CTB 12UP 4S
TCF 12UP 3
TCF 12UP 4
TQQ 12NE 3P
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 3 pole 4EA, 4 pole 6EA
Rated
current
3 pole
Code
4 pole
Unit
(EA)
Code
Unit
(EA)
UPB160S 85kA
160A
UPB160H 100kA
160A
UPB160L 130kA
160A
UPB160X 150kA
160A
UPB160S 85kA
160A
UPB160H 100kA
160A
UPB160L 130kA
160A
UPB160X 150kA
160A
Specification
Category
Screw type
terminal
connection,
No option, 50Hz
MCCB/M3
Screw type
terminal
connection,
No option, 60Hz
U-Series
Rated
current
3 pole
Code
4 pole
Unit
(EA)
Code
Unit
(EA)
100A
125A
160A
100A
125A
160A
100A
125A
160A
100A
UPB160X
150kA
125A
160A
Model /
Breaking capacity at
AC380/415V
Rated
current
UPB160S
85kA
UPB160H
100kA
UPB160L
130kA
Specification
Screw type
terminal
connection,
No option,
50/60Hz
Category
MCCB
/M2
50
UPB160S
85kA
UPB160H
100kA
UPB160L
130kA
UPB160X
150kA
3 pole
Code
4 pole
Unit
(EA)
Code
Unit
(EA)
100A
125A
160A
100A
125A
160A
100A
125A
160A
100A
125A
160A
Specification
Screw type
terminal
connection,
No option,
50/60Hz
Category
MCCB
/M2
UPB160H
100kA
UPB160L
130kA
UPB160X
150kA
100
3 pole
4 pole
Rated
current
Code
Unit
(EA)
100A
125A
160A
100A
125A
160A
100A
125A
160A
100A
125A
160A
Code
Unit
(EA)
Specification
Screw type
terminal
connection,
No option,
50/60Hz
Category
MCCB
/M2
MCCB
50
Model /
Breaking capacity at
AC380/415V
UPB160S
85kA
UPB160H
100kA
UPB160L
130kA
UPB160X
150kA
3 pole
4 pole
Rated
current
Code
Unit
(EA)
100A
125A
160A
100A
125A
160A
100A
125A
160A
100A
125A
160A
Code
Unit
(EA)
Specification
Screw type
terminal
connection,
No option,
50/60Hz
Category
MCCB
/M2
3 pole
4 pole
Rated
current
Code
Unit
(EA)
100A
125A
160A
100A
125A
160A
100A
125A
160A
100A
UPB160X
150kA
125A
160A
Model /
Breaking capacity at
AC380/415V
Rated
current
Code
Unit
(EA)
100A
125A
160A
100A
125A
160A
100A
125A
160A
100A
125A
160A
UPB160S
85kA
UPB160H
100kA
UPB160L
130kA
Code
Unit
(EA)
Specification
Screw type
terminal
connection,
No option,
50/60Hz
Category
MCCB
/M2
50
UPB160S
85kA
UPB160H
100kA
UPB160L
130kA
UPB160X
150kA
3 pole
4 pole
Code
Unit
(EA)
Specification
Screw type
terminal
connection,
No option,
50/60Hz
Category
MCCB
/M2
U-Series
UPB250S
UPB250H
UPB250L
3, 4
IP20
Utilization category
UPB250X
Suitability of isolation
Protection
125,150,160,175,200,225,250
Electronic type
100-250
AC750
Rating
AC690
DC500 1)
Rated
short-circuit
breaking
capacity
Ultimate
[Icu]
(kA r.m.s.)
IEC 60947-2
K 60947-2
AC660/690V, 50-60Hz
10
10
AC480/500V, 50-60Hz
50
65
85
85
AC440/460V, 50-60Hz
65
85
100
150
AC380/415V, 50-60Hz
85
100
130
150
AC220/240V, 50-60Hz
100
130
150
200
DC250V
50 1)
65 1)
85 1)
100 1)
DC125V
65 1)
100 1)
100 1)
100 1)
25
100
Fixed thermal,
Thermal
magnetic
Trip
mechanism
& Protection
characteristics
Fixed instantaneous
INST
10 In
Adjustable thermal,
LTD
(0.8 0.9 1) In
Fixed instantaneous
INST
10 In
Adjustable thermal,
LTD
(0.8 0.9 1) In
Electronic
(5-6-7-8-9-10) In
LTD
STD
Instantaneous
INST
11 In
Pre-trip alarm
PTA
0.9 Ir
100,110,125,140,160,175,200,225,250
(NON-2-3-4-5-6-7-8-9-10) Ir
Pick-up LED
Direct mounting by screw
Mounting
Plug-in
Terminal connection
Durability
(times)
Dimensions
(mm)
2)
2)
Screw
Bus bar
Mechanical operation
25,000
Electrical operation
3/4P
10,000
a
Width
105/140
Height
165
Depth
86.5
d
Weight (kg, breaker only) 3/4P
112
2.0/2.4
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) DC is not applicable for electronic breaker. 2) Available for 3P breaker
102
25
MCCB
Accessories
Signal
1C, right-hand-side
Auxiliary switch
AUX 12UP R1
1C, left-hand-side
ALT 12UP L1
Shunt trip 1)
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
AC440-480V
SHT 12UP A
SHT 12UP C
SHT 12UP F
SHT 12UP H
SHT 12UP B
SHT 12UP D
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
AC440-480V
UVT 12UP J
UVT 12UP L
UVT 12UP N
UVT 12UP P
UVT 12UP Q
UVT 12UP R
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.
Operating
Power supply direction
S type
Operating Surface
L type
handle 1)
S type
Extended
L type
Upper
Right
Left
TFG 12UPS U4
TFG 12UPS R4
TFG 12UPS L4
TFG 12UPL U4
TFG 12UPL L4
TFH 12UPS
TFH 12UPL
DC24V
Motor operator 2)
AC/DC110V
Mechanical interlock
AC/DC220V
MOT 12UP ADC220
3 pole
4 pole
MIF 12UP 3
MIF 12UP 4
3)
Padlock plate
PLD 12UP
Mounting
Structure
Plug-in 1)
TDM 12NEP
TDM 12NEF
Mounting base
Connection 6C contact
CBM 26NE 6
block 2)
12C contact
Terminal
Terminal bus bar
Cage terminal block
Terminal cover 1)
Interpole barrier 2)
3 pole (6EA/SET)
TBB 12NE 3
4 pole (8EA/SET)
TBB 12NE 4
3EA/SET
CTB 12UP 3S
4EA/SET
CTB 12UP 4S
3 pole
TCF 12UP 3
4 pole
TCF 12UP 4
4EA/SET
TQQ 12NE 3P
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 3 pole 4EA, 4 pole 6EA
U-Series
104
Unit
(EA)
4 pole
Code
Unit
(EA)
250A
UPB250L
130kA
250A
UPB250X
150kA
250A
Model /
Breaking capacity at
AC380/415V
Rated
current
UPB250S
85kA
250A
UPB250H
100kA
3 pole
Code
Specification
Category
Screw type
terminal
connection,
No option,
50Hz
MCCB
/M3
UPB250S
85kA
250A
UPB250H
100kA
250A
UPB250L
130kA
250A
UPB250X
150kA
250A
Screw type
terminal
connection,
No option,
60Hz
MCCB
UPB250S
85kA
UPB250H
100kA
UPB250L
130kA
UPB250X
150kA
Rated
current
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
3 pole
Code
UPB250S 3PT4S0000C 00125
UPB250S 3PT4S0000C 00150
UPB250S 3PT4S0000C 00160
UPB250S 3PT4S0000C 00175
UPB250S 3PT4S0000C 00200
UPB250S 3PT4S0000C 00225
UPB250S 3PT4S0000C 00250
UPB250H 3PT4S0000C 00125
UPB250H 3PT4S0000C 00150
UPB250H 3PT4S0000C 00160
UPB250H 3PT4S0000C 00175
UPB250H 3PT4S0000C 00200
UPB250H 3PT4S0000C 00225
UPB250H 3PT4S0000C 00250
UPB250L 3PT4S0000C 00125
UPB250L 3PT4S0000C 00150
UPB250L 3PT4S0000C 00160
UPB250L 3PT4S0000C 00175
UPB250L 3PT4S0000C 00200
UPB250L 3PT4S0000C 00225
UPB250L 3PT4S0000C 00250
UPB250X 3PT4S0000C 00125
UPB250X 3PT4S0000C 00150
UPB250X 3PT4S0000C 00160
UPB250X 3PT4S0000C 00175
UPB250X 3PT4S0000C 00200
UPB250X 3PT4S0000C 00225
UPB250X 3PT4S0000C 00250
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
4 pole
Code
UPB250S 4PT4S0000C 00125
UPB250S 4PT4S0000C 00150
UPB250S 4PT4S0000C 00160
UPB250S 4PT4S0000C 00175
UPB250S 4PT4S0000C 00200
UPB250S 4PT4S0000C 00225
UPB250S 4PT4S0000C 00250
UPB250H 4PT4S0000C 00125
UPB250H 4PT4S0000C 00150
UPB250H 4PT4S0000C 00160
UPB250H 4PT4S0000C 00175
UPB250H 4PT4S0000C 00200
UPB250H 4PT4S0000C 00225
UPB250H 4PT4S0000C 00250
UPB250L 4PT4S0000C 00125
UPB250L 4PT4S0000C 00150
UPB250L 4PT4S0000C 00160
UPB250L 4PT4S0000C 00175
UPB250L 4PT4S0000C 00200
UPB250L 4PT4S0000C 00225
UPB250L 4PT4S0000C 00250
UPB250X 4PT4S0000C 00125
UPB250X 4PT4S0000C 00150
UPB250X 4PT4S0000C 00160
UPB250X 4PT4S0000C 00175
UPB250X 4PT4S0000C 00200
UPB250X 4PT4S0000C 00225
UPB250X 4PT4S0000C 00250
Unit
(EA)
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Specification
Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
Specification
Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
50
Model /
Breaking capacity at
AC380/415V
UPB250S
85kA
UPB250H
100kA
UPB250L
130kA
UPB250X
150kA
Rated
current
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
3 pole
Code
UPB250S 3PT5S0000C 00125
UPB250S 3PT5S0000C 00150
UPB250S 3PT5S0000C 00160
UPB250S 3PT5S0000C 00175
UPB250S 3PT5S0000C 00200
UPB250S 3PT5S0000C 00225
UPB250S 3PT5S0000C 00250
UPB250H 3PT5S0000C 00125
UPB250H 3PT5S0000C 00150
UPB250H 3PT5S0000C 00160
UPB250H 3PT5S0000C 00175
UPB250H 3PT5S0000C 00200
UPB250H 3PT5S0000C 00225
UPB250H 3PT5S0000C 00250
UPB250L 3PT5S0000C 00125
UPB250L 3PT5S0000C 00150
UPB250L 3PT5S0000C 00160
UPB250L 3PT5S0000C 00175
UPB250L 3PT5S0000C 00200
UPB250L 3PT5S0000C 00225
UPB250L 3PT5S0000C 00250
UPB250X 3PT5S0000C 00125
UPB250X 3PT5S0000C 00150
UPB250X 3PT5S0000C 00160
UPB250X 3PT5S0000C 00175
UPB250X 3PT5S0000C 00200
UPB250X 3PT5S0000C 00225
UPB250X 3PT5S0000C 00250
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
4 pole
Code
UPB250S 4PT5S0000C 00125
UPB250S 4PT5S0000C 00150
UPB250S 4PT5S0000C 00160
UPB250S 4PT5S0000C 00175
UPB250S 4PT5S0000C 00200
UPB250S 4PT5S0000C 00225
UPB250S 4PT5S0000C 00250
UPB250H 4PT5S0000C 00125
UPB250H 4PT5S0000C 00150
UPB250H 4PT5S0000C 00160
UPB250H 4PT5S0000C 00175
UPB250H 4PT5S0000C 00200
UPB250H 4PT5S0000C 00225
UPB250H 4PT5S0000C 00250
UPB250L 4PT5S0000C 00125
UPB250L 4PT5S0000C 00150
UPB250L 4PT5S0000C 00160
UPB250L 4PT5S0000C 00175
UPB250L 4PT5S0000C 00200
UPB250L 4PT5S0000C 00225
UPB250L 4PT5S0000C 00250
UPB250X 4PT5S0000C 00125
UPB250X 4PT5S0000C 00150
UPB250X 4PT5S0000C 00160
UPB250X 4PT5S0000C 00175
UPB250X 4PT5S0000C 00200
UPB250X 4PT5S0000C 00225
UPB250X 4PT5S0000C 00250
Unit
(EA)
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
U-Series
UPB250S
85kA
UPB250H
100kA
UPB250L
130kA
UPB250X
150kA
Rated
current
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
3 pole
Code
UPB250S 3PT4S0000C 00125F
UPB250S 3PT4S0000C 00150F
UPB250S 3PT4S0000C 00160F
UPB250S 3PT4S0000C 00175F
UPB250S 3PT4S0000C 00200F
UPB250S 3PT4S0000C 00225F
UPB250S 3PT4S0000C 00250F
UPB250H 3PT4S0000C 00125F
UPB250H 3PT4S0000C 00150F
UPB250H 3PT4S0000C 00160F
UPB250H 3PT4S0000C 00175F
UPB250H 3PT4S0000C 00200F
UPB250H 3PT4S0000C 00225F
UPB250H 3PT4S0000C 00250F
UPB250L 3PT4S0000C 00125F
UPB250L 3PT4S0000C 00150F
UPB250L 3PT4S0000C 00160F
UPB250L 3PT4S0000C 00175F
UPB250L 3PT4S0000C 00200F
UPB250L 3PT4S0000C 00225F
UPB250L 3PT4S0000C 00250F
UPB250X 3PT4S0000C 00125F
UPB250X 3PT4S0000C 00150F
UPB250X 3PT4S0000C 00160F
UPB250X 3PT4S0000C 00175F
UPB250X 3PT4S0000C 00200F
UPB250X 3PT4S0000C 00225F
UPB250X 3PT4S0000C 00250F
Unit
(EA)
4 pole
Code
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Unit
(EA)
4 pole
Code
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Specification
Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
Specification
Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
50
Model /
Breaking capacity at
AC380/415V
UPB250S
85kA
UPB250H
100kA
UPB250L
130kA
UPB250X
150kA
106
Rated
current
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
3 pole
Code
UPB250S 3PT5S0000C 00125F
UPB250S 3PT5S0000C 00150F
UPB250S 3PT5S0000C 00160F
UPB250S 3PT5S0000C 00175F
UPB250S 3PT5S0000C 00200F
UPB250S 3PT5S0000C 00225F
UPB250S 3PT5S0000C 00250F
UPB250H 3PT5S0000C 00125F
UPB250H 3PT5S0000C 00150F
UPB250H 3PT5S0000C 00160F
UPB250H 3PT5S0000C 00175F
UPB250H 3PT5S0000C 00200F
UPB250H 3PT5S0000C 00225F
UPB250H 3PT5S0000C 00250F
UPB250L 3PT5S0000C 00125F
UPB250L 3PT5S0000C 00150F
UPB250L 3PT5S0000C 00160F
UPB250L 3PT5S0000C 00175F
UPB250L 3PT5S0000C 00200F
UPB250L 3PT5S0000C 00225F
UPB250L 3PT5S0000C 00250F
UPB250X 3PT5S0000C 00125F
UPB250X 3PT5S0000C 00150F
UPB250X 3PT5S0000C 00160F
UPB250X 3PT5S0000C 00175F
UPB250X 3PT5S0000C 00200F
UPB250X 3PT5S0000C 00225F
UPB250X 3PT5S0000C 00250F
MCCB
UPB250S
85kA
UPB250H
100kA
UPB250L
130kA
UPB250X
150kA
Rated
current
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
3 pole
Code
UPB250S 3PT4S0000C 00125H
UPB250S 3PT4S0000C 00150H
UPB250S 3PT4S0000C 00160H
UPB250S 3PT4S0000C 00175H
UPB250S 3PT4S0000C 00200H
UPB250S 3PT4S0000C 00225H
UPB250S 3PT4S0000C 00250H
UPB250H 3PT4S0000C 00125H
UPB250H 3PT4S0000C 00150H
UPB250H 3PT4S0000C 00160H
UPB250H 3PT4S0000C 00175H
UPB250H 3PT4S0000C 00200H
UPB250H 3PT4S0000C 00225H
UPB250H 3PT4S0000C 00250H
UPB250L 3PT4S0000C 00125H
UPB250L 3PT4S0000C 00150H
UPB250L 3PT4S0000C 00160H
UPB250L 3PT4S0000C 00175H
UPB250L 3PT4S0000C 00200H
UPB250L 3PT4S0000C 00225H
UPB250L 3PT4S0000C 00250H
UPB250X 3PT4S0000C 00125H
UPB250X 3PT4S0000C 00150H
UPB250X 3PT4S0000C 00160H
UPB250X 3PT4S0000C 00175H
UPB250X 3PT4S0000C 00200H
UPB250X 3PT4S0000C 00225H
UPB250X 3PT4S0000C 00250H
Unit
(EA)
4 pole
Code
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Unit
(EA)
4 pole
Code
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
Specification
Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
Specification
Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M2
50
Model /
Breaking capacity at
AC380/415V
UPB250S
85kA
UPB250H
100kA
UPB250L
130kA
UPB250X
150kA
Rated
current
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
125A
150A
160A
175A
200A
225A
250A
3 pole
Code
UPB250S 3PT5S0000C 00125H
UPB250S 3PT5S0000C 00150H
UPB250S 3PT5S0000C 00160H
UPB250S 3PT5S0000C 00175H
UPB250S 3PT5S0000C 00200H
UPB250S 3PT5S0000C 00225H
UPB250S 3PT5S0000C 00250H
UPB250H 3PT5S0000C 00125H
UPB250H 3PT5S0000C 00150H
UPB250H 3PT5S0000C 00160H
UPB250H 3PT5S0000C 00175H
UPB250H 3PT5S0000C 00200H
UPB250H 3PT5S0000C 00225H
UPB250H 3PT5S0000C 00250H
UPB250L 3PT5S0000C 00125H
UPB250L 3PT5S0000C 00150H
UPB250L 3PT5S0000C 00160H
UPB250L 3PT5S0000C 00175H
UPB250L 3PT5S0000C 00200H
UPB250L 3PT5S0000C 00225H
UPB250L 3PT5S0000C 00250H
UPB250X 3PT5S0000C 00125H
UPB250X 3PT5S0000C 00150H
UPB250X 3PT5S0000C 00160H
UPB250X 3PT5S0000C 00175H
UPB250X 3PT5S0000C 00200H
UPB250X 3PT5S0000C 00225H
UPB250X 3PT5S0000C 00250H
U-Series
UPB400S
UPB400H
UPB400L
UPB400X
3, 4
IP20
A
overload, inst., short-circuit
200-400
AC750
AC690
8
10
25
65
85
85
100
100
130
130
150
100
(0.5-1) 1) In (15 setting)
(2-4-6-8-10) Ir
(3-6-8-10-11) In
(0.2-0.3-0.4) In
0.9 Ir
10
50
65
85
100
25
85
150
150
200
2)
2)
20,000
6,000
140/185
255
117
159.5
6.0/7.8
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) (0.5-1): (0.63-0.8-1)x(0.8-0.85-0.9-0.95-1)
2) Available for 3P breaker
Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip 1)
Under voltage trip 2)
1C, left-hand-side
AUX 46UP L1
1C, right-hand-side
ALT 46UP R1
DC24V
SHT 46UP A
DC24V
UVT 46UP J
DC100-110V
SHT 46UP C
DC100-110V
UVT 46UP L
AC100-120V
SHT 46UP F
AC100-120V
UVT 46UP N
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.
108
AC200-230V
SHT 46UP H
AC200-230V
UVT 46UP P
AC380-415V
SHT 46UP B
AC380-415V
UVT 46UP Q
AC440-480V
SHT 46UP D
AC440-480V
UVT 46UP R
MCCB
Operating
Power supply direction
Operating
Surface S type
1)
handle
Extended S type
Upper
TFG 46UPS U2
Right
TFG 46UPS R2
TFH 46UPS
AC/DC110V
MOT 46NE ADC110
DC24V
MOT 46NE DC24
3 pole
MIF 46UP 3
Motor operator 2)
Mechanical interlock
Padlock plate 3)
Extension handle 4)
Left
TFG 46UPS L2
AC/DC220V
MOT 46NE ADC220
4 pole
MIF 46UP 4
PLD 12UP
THA 46UP
Mounting
Plug-in 1)
Structure
Mounting base
Connection 6C contact
block 2)
12C contact
Terminal
3 pole (6EA/SET)
4 pole (8EA/SET)
3EA/SET
Cage terminal block
4EA/SET
3 pole
1)
Terminal cover
4 pole
Interpole barrier 2) 4EA/SET
TBB 40NE 3
TBB 40NE 4
CTB 46UP 3S
CTB 46UP 4S
TCF 46UP 3
TCF 46UP 4
TQQ 46NE 3P
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 3 pole 4EA, 4 pole 6EA
Rated
current
400A
400A
400A
400A
400A
400A
400A
400A
3 pole
Code
UPB400S 3PESS0000X 00400
UPB400H 3PESS0000X 00400
UPB400L 3PESS0000X 00400
UPB400X 3PESS0000X 00400
UPB400S 3PESS0000Y 00400
UPB400H 3PESS0000Y 00400
UPB400L 3PESS0000Y 00400
UPB400X 3PESS0000Y 00400
4 pole
Unit
(EA)
Code
Unit
(EA)
3
3
3
3
3
3
3
3
2
2
2
2
2
2
2
2
Specification
Category
Screw type
terminal
connection,
No option, 50Hz
MCCB/M3
Screw type
terminal
connection,
No option, 60Hz
Rated
current
400A
400A
400A
400A
400A
400A
400A
400A
3 pole
Code
UPB400S 3PEGS0000X 00400
UPB400H 3PEGS0000X 00400
UPB400L 3PEGS0000X 00400
UPB400X 3PEGS0000X 00400
UPB400S 3PEGS0000Y 00400
UPB400H 3PEGS0000Y 00400
UPB400L 3PEGS0000Y 00400
UPB400X 3PEGS0000Y 00400
4 pole
Unit
(EA)
Code
Unit
(EA)
3
3
3
3
3
3
3
3
2
2
2
2
2
2
2
2
Specification
Category
Screw type
terminal
connection,
No option, 50Hz
MCCB/M3
Screw type
terminal
connection,
No option, 60Hz
Molded Case Circuit Breaker_ 109
U-Series
UPB630S
UPB630H
UPB630L
UPB630X
3, 4
IP20
A
overload, inst., short-circuit
320-630
AC750
AC690
8
10
25
65
85
85
100
100
130
130
150
100
(0.5-1) 1) In (15 setting)
(2-4-6-8-10) Ir
(3-6-8-10-11) In
(0.2-0.3-0.4) In
0.9 Ir
10
50
65
85
100
25
85
150
150
200
2)
2)
20,000
6,000
140/185
255
117
159.5
6.0/7.8
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) (0.5-1): (0.63-0.8-1)x(0.8-0.85-0.9-0.95-1)
2) Available for 3P breaker
Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip 1)
Under voltage trip 2)
1C, left-hand-side
AUX 46UP L1
1C, right-hand-side
ALT 46UP R1
DC24V
SHT 46UP A
DC24V
UVT 46UP J
DC100-110V
SHT 46UP C
DC100-110V
UVT 46UP L
AC100-120V
SHT 46UP F
AC100-120V
UVT 46UP N
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.
110
AC200-230V
SHT 46UP H
AC200-230V
UVT 46UP P
AC380-415V
SHT 46UP B
AC380-415V
UVT 46UP Q
AC440-480V
SHT 46UP D
AC440-480V
UVT 46UP R
MCCB
Operating
Power supply direction
Operating Surface S type
handle 1)
Extended S type
Upper
TFG 46UPS U2
Right
TFG 46UPS R2
TFH 46UPS
AC/DC110V
MOT 46NE ADC110
DC24V
MOT 46NE DC24
3 pole
MIF 46UP 3
Motor operator 2)
Mechanical interlock
Padlock plate 3)
Extension handle 4)
Left
TFG 46UPS L2
AC/DC220V
MOT 46NE ADC220
4 pole
MIF 46UP 4
PLD 12UP
THA 46UP
1) For detail type information, please refer to page no. 197-205. 2) Motor operator is not recommended for marine application.
3) Padlock is not supplied.
4) Supplied as standard component
Mounting
Plug-in
1)
Structure
Mounting base
Connection 6C contact
12C contact
block 2)
Terminal
TBB 60NE 3
TBB 60NE 4
CTB 46UP 3S
CTB 46UP 4S
TCF 46UP 3
TCF 46UP 4
TQQ 46NE 3P
3 pole (6EA/SET)
4 pole (8EA/SET)
3EA/SET
Cage terminal block
4EA/SET
3 pole
1)
Terminal cover
4 pole
Interpole barrier 2) 4EA/SET
Terminal bus bar
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 3 pole 4EA, 4 pole 6EA
Rated
current
630A
630A
630A
630A
630A
630A
630A
630A
3 pole
Code
UPB630S 3PESS0000X 00630
UPB630H 3PESS0000X 00630
UPB630L 3PESS0000X 00630
UPB630X 3PESS0000X 00630
UPB630S 3PESS0000Y 00630
UPB630H 3PESS0000Y 00630
UPB630L 3PESS0000Y 00630
UPB630X 3PESS0000Y 00630
4 pole
Unit
(EA)
Code
Unit
(EA)
3
3
3
3
3
3
3
3
2
2
2
2
2
2
2
2
Specification
Category
Screw type
terminal
connection,
No option, 50Hz
MCCB/M3
Screw type
terminal
connection,
No option, 60Hz
Rated
current
630A
630A
630A
630A
630A
630A
630A
630A
3 pole
Code
UPB630S 3PEGS0000X 00630
UPB630H 3PEGS0000X 00630
UPB630L 3PEGS0000X 00630
UPB630X 3PEGS0000X 00630
UPB630S 3PEGS0000Y 00630
UPB630H 3PEGS0000Y 00630
UPB630L 3PEGS0000Y 00630
UPB630X 3PEGS0000Y 00630
4 pole
Unit
(EA)
Code
Unit
(EA)
3
3
3
3
3
3
3
3
2
2
2
2
2
2
2
2
Specification
Category
Screw type
terminal
connection,
No option, 50Hz
MCCB/M3
Screw type
terminal
connection,
No option, 60Hz
Molded Case Circuit Breaker_ 111
U-Series
UPB100H
UPB100L
IP20
Suitability of isolation
Protection
instantaneous, short-circuit
Rated current (A)
2.5,3.2,6.3,12.5,20,32,50,63,80,100
AC750
Rating
AC690
DC500
Rated impulse withstand voltage [Uimp] (kV)
Rated
short-circuit
breaking
capacity
Ultimate
[Icu]
(kA r.m.s.)
IEC 60947-2
K 60947-2
AC660/690V, 50-60Hz
10
25
AC480/500V, 50-60Hz
65
85
AC440/460V, 50-60Hz
85
100
AC380/415V, 50-60Hz
100
130
AC220/240V, 50-60Hz
130
150
DC250V
65
85
DC125V
100
100
100
(6-7-8-9-10-11-12-13) In
Adjustable instantaneous
Plug-in
Terminal connection
Durability
(times)
Mechanical operation
25,000
Electrical operation
10,000
Dimensions
(mm)
3P
Width
105
Height
165
Depth
86.5
d
Weight (kg, breaker only)
3P
112
1.8
The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
112
MCCB
Accessories
Signal
1C, right-hand-side
AUX 12UP R1
1C, left-hand-side
ALT 12UP L1
DC24V
SHT 12UP A
DC24V
UVT 12UP J
Auxiliary switch
Trip alarm switch
Shunt trip 1)
Under voltage trip 2)
DC100-110V
SHT 12UP C
DC100-110V
UVT 12UP L
AC100-120V
SHT 12UP F
AC100-120V
UVT 12UP N
AC200-230V
SHT 12UP H
AC200-230V
UVT 12UP P
AC380-415V
SHT 12UP B
AC380-415V
UVT 12UP Q
AC440-480V
SHT 12UP D
AC440-480
UVT 12UP R
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.
Operating
Power supply direction
S type
Operating Surface L type
1)
handle
S type
Extended
L type
Upper
TFG 12UPS U4
TFG 12UPL U4
Right
TFG 12UPS R4
TFH 12UPS
TFH 12UPL
AC/DC110V
MOT 12UP ADC110
MIF 12UP 3
PLD 12UP
DC24V
MOT 12UP DC24
Motor operator 2)
Mechanical interlock
Padlock plate 3)
Left
TFG 12UPS L4
TFG 12UPL L4
AC/DC220V
MOT 12UP ADC220
Mounting
Plug-in
Structure
Mounting base
Connection 6C contact
block 1)
12C contact
1) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.
2) 2EA shall be ordered for 12C contact.
Terminal
Terminal bus bar
Cage terminal block
1)
Terminal cover
Interpole barrier 2)
3 pole (6EA/SET)
3EA/SET
3 pole
4EA/SET
TBB 12NE 3
CTB 12UP 3S
TCF 12UP 3
TQQ 12NE 3P
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 4EA
Rated
current
UPB100H
100kA
2.5A
3.2A
6.3A
12.5A
20A
32A
50A
63A
80A
100A
3 pole
Code
UPB100H 3PMPS0000C 002.5
UPB100H 3PMPS0000C 003.2
UPB100H 3PMPS0000C 006.3
UPB100H 3PMPS0000C 012.5
UPB100H 3PMPS0000C 00020
UPB100H 3PMPS0000C 00032
UPB100H 3PMPS0000C 00050
UPB100H 3PMPS0000C 00063
UPB100H 3PMPS0000C 00080
UPB100H 3PMPS0000C 00100
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
Model /
Breaking
capacity at
AC380/415V
Rated
current
UPB100L
130kA
2.5A
3.2A
6.3A
12.5A
20A
32A
50A
63A
80A
100A
3 pole
Code
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M4
U-Series
UPB250H
UPB250L
IP20
Suitability of isolation
Protection
instantaneous, short-circuit
Rated current (A)
125,150,175,200,225
AC750
Rating
AC690
DC500
Rated impulse withstand voltage [Uimp] (kV)
Rated
short-circuit
breaking
capacity
Ultimate
[Icu]
(kA r.m.s.)
IEC 60947-2
K 60947-2
AC660/690V, 50-60Hz
10
25
AC480/500V, 50-60Hz
65
85
AC440/460V, 50-60Hz
85
100
AC380/415V, 50-60Hz
100
130
AC220/240V, 50-60Hz
130
150
DC250V
65
85
DC125V
100
100
100
(5-6-7-8-9-10) In
Adjustable instantaneous
Plug-in
Terminal connection
Bus bar
Durability
(times)
Mechanical operation
25,000
Electrical operation
10,000
Dimensions
(mm)
3P
Width
105
Height
165
Depth
86.5
d
Weight (kg, breaker only)
3P
112
2.0
The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
114
MCCB
Accessories
Signal
1C, right-hand-side
AUX 12UP R1
1C, left-hand-side
ALT 12UP L1
DC24V
SHT 12UP A
DC24V
UVT 12UP J
Auxiliary switch
Trip alarm switch
Shunt trip 1)
Under voltage trip 2)
DC100-110V
SHT 12UP C
DC100-110V
UVT 12UP L
AC100-120V
SHT 12UP F
AC100-120V
UVT 12UP N
AC200-230V
SHT 12UP H
AC200-230V
UVT 12UP P
AC380-415V
SHT 12UP B
AC380-415V
UVT 12UP Q
AC440-480V
SHT 12UP D
AC440-480V
UVT 12UP R
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.
Operating
Power supply direction
S type
Operating Surface
L type
1)
handle
S type
Extended
L type
Upper
TFG 12UPS U4
TFG 12UPL U4
Right
TFG 12UPS R4
TFH 12UPS
TFH 12UPL
AC/DC110V
MOT 12UP ADC110
MIF 12UP 3
PLD 12UP
DC24V
MOT 12UP DC24
Motor operator 2)
Mechanical interlock
Padlock plate3)
Left
TFG 12UPS L4
TFG 12UPL L4
AC/DC220V
MOT 12UP ADC220
Mounting
Plug-in
Structure
Mounting base
Connection 6C contact
block 1)
12C contact
1) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.
2) 2EA shall be ordered for 12C contact.
Terminal
Terminal bus bar
3 pole (6EA/SET)
Cage terminal block 3EA/SET
Terminal cover
1)
Interpole barrier 2)
TBB 12NE 3
CTB 12UP 3S
TCF 12UP 3
TCF 12UP 4
TQQ 12NE 3P
3 pole
4 pole
4EA/SET
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 4EA
UPB250H
100kA
Rated
current
3 pole
Code
Unit
(EA)
Model /
Breaking
capacity at
AC380/415V
Rated
current
3 pole
Code
Unit
(EA)
125A
125A
150A
150A
175A
175A
200A
200A
225A
225A
UPB250L
130kA
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M4
U-Series
HBL103U
HBL103UQ
IEC 60947-2
K 60947-2
Trip mechanism
& Protection
characteristics
AC660/690V, 50-60Hz
AC480/500V, 50-60Hz
AC440/460V, 50-60Hz
Ultimate
[Icu]
AC380/415V, 50-60Hz
(kA r.m.s.) AC220/240V, 50-60Hz
DC250V
DC125V
Service [Ics] % of [Icu]
Thermal
magnetic
25
85
100
150
200
100
100
Fixed thermal,
Fixed instantaneous INST
Adjustable instantaneous
25
85
100
150
200
100
100
3P
a
b
c
d
instantaneous, short-circuit
2.5,3.2,6.3,12.5,20,32,50,63,80,100
AC750
AC690
DC500
8
25
25
85
85
100
100
150
150
200
200
100
100
100
100
100
10 In
(6-7-8-9-10-11-12-13) In
Non-E1
Q-class
E1
Mounting
Direct mounting by screw
Screw
Terminal connection
Bus bar
Mechanical operation
Durability
(times)
Electrical operation
Dimensions
(mm)
HBL103UMQ
3
IP20
A
Rated
short-circuit
breaking
capacity
HBL103UM
25,000
10,000
105
165
86.5
112
1.8
Width
Height
Depth
The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip 1)
Under voltage trip 2)
1C, right-hand-side
AUX 12UP R1
1C, left-hand-side
ALT 12UP L1
DC24V
SHT 12UP A
DC24V
UVT 12UP J
DC100-110V
SHT 12UP C
DC100-110V
UVT 12UP L
AC100-120V
SHT 12UP F
AC100-120V
UVT 12UP N
116
AC200-230V
SHT 12UP H
AC200-230V
UVT 12UP P
AC380-415V
SHT 12UP B
AC380-415V
UVT 12UP Q
AC440-480V
SHT 12UP D
AC440-480V
UVT 12UP R
MCCB
Operating
Power supply direction
Operating
HBL103U, HBL103UM
1)
Surface
handle
HBL103UQ, HBL103UMQ
Motor operator 2)
Upper
TFG 20U U4
TFG 20UQ U4
DC24V
MOT 12UP DC24
Left
TFG 20U L4
TFG 20UQ L4
AC/DC110V
MOT 12UP ADC110
MIF 12UP 3
PLD 12UP
Mechanical interlock
Padlock plate3)
AC/DC220V
MOT 12UP ADC220
Terminal
Terminal bus bar
6EA/SET
TBB 12NE 3
3EA/SET
CTB 12UP 3S
4EA/SET
TQQ 12NE 3P
Terminal cover 1)
Interpole barrier 2)
TCF 12UP 3
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 4EA
Rated
current
HBL103U
85kA
15A
20A
30A
40A
50A
60A
75A
100A
Model /
Breaking
capacity at
AC480/500V
Rated
current
HBL103U
85kA
15A
20A
30A
40A
50A
60A
75A
100A
Unit
(EA)
8
8
8
8
8
8
8
8
Model /
Breaking
capacity at
AC480/500V
Rated
current
HBL103UQ
85kA
15A
20A
30A
40A
50A
60A
75A
100A
Model /
Breaking
capacity at
AC480/500V
Rated
current
HBL103UQ
85kA
15A
20A
30A
40A
50A
60A
75A
100A
3 pole, E1 class
Code
Unit
(EA)
8
8
8
8
8
8
8
8
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M1
50
3 pole, Non-E1 class
Code
Unit
(EA)
8
8
8
8
8
8
8
8
3 pole, E1 class
Code
Unit
(EA)
8
8
8
8
8
8
8
8
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M1
Rated
current
HBL103UM
85kA
2.5A
3.2A
6.3A
12.5A
20A
32A
50A
63A
80A
100A
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
Model /
Breaking
capacity at
AC480/500V
Rated
current
HBL103UMQ
85kA
2.5A
3.2A
6.3A
12.5A
20A
32A
50A
63A
80A
100A
3 pole, E1 class
Code
Unit
(EA)
8
8
8
8
8
8
8
8
8
8
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M4
U-Series
HBL203U
HBL203UQ
HBL203UM
HBL203UMQ
3
IP20
A
25,000
10,000
105
165
86.5
112
2.0
The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
Accessories
Signal
Auxiliary switch
Trip alarm switch
Shunt trip 1)
Under voltage trip 2)
118
1C, right-hand-side
AUX 12UP R1
1C, left-hand-side
ALT 12UP L1
DC24V
SHT 12UP A
DC24V
UVT 12UP J
DC100-110V
SHT 12UP C
DC100-110V
UVT 12UP L
AC100-120V
SHT 12UP F
AC100-120V
UVT 12UP N
AC200-230V
SHT 12UP H
AC200-230V
UVT 12UP P
AC380-415V
SHT 12UP B
AC380-415V
UVT 12UP Q
AC440-480V
SHT 12UP D
AC440-480V
UVT 12UP R
MCCB
Operating
Power supply direction
HBL203U, HBL203UM
Operating Surface
HBL203UQ, HBL203UMQ
handle 1)
HBL203U, HBL203UM
Extended
HBL203UQ, HBL203UMQ
Upper
TFG 20U U4
TFG 20UQ U4
Left
TFG 20U L4
TFG 20UQ L4
TFH 20U
TFH 20UQ
DC24V
MOT 12UP DC24
Motor operator 2)
AC/DC110V
MOT 12UP ADC110
MIF 12UP 3
PLD 12UP
Mechanical interlock
Padlock plate3)
AC/DC220V
MOT 12UP ADC220
Terminal
Terminal bus bar
6EA/SET
TBB 12NE 3
3EA/SET
CTB 12UP 3S
4EA/SET
TQQ 12NE 3P
Terminal cover 1)
Interpole barrier 2)
TCF 12UP 3
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 4EA
HBL203U
85kA
125A
150A
175A
200A
225A
Model /
Unit Breaking capacity at
AC480/500V
(EA)
8
8
8
8
8
HBL203UQ
85kA
Rated
current
125A
150A
175A
200A
225A
3 pole, E1 class
Code
Unit
(EA)
8
8
8
8
8
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M1
50
Model /
Rated
Breaking capacity at
current
AC480/500V
HBL203U
85kA
125A
150A
175A
200A
225A
Model /
Unit Breaking capacity at
AC480/500V
(EA)
8
8
8
8
8
HBL203UQ
85kA
Rated
current
125A
150A
175A
200A
225A
3 pole, E1 class
Code
Unit
(EA)
8
8
8
8
8
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M1
HBL203UM
85kA
125A
150A
175A
200A
225A
Model /
Unit Breaking capacity at
AC480/500V
(EA)
8
8
8
8
8
HBL203UMQ
85kA
Rated
current
125A
150A
175A
200A
225A
3 pole, E1 class
Code
Unit
(EA)
8
8
8
8
8
Specification Category
Screw type
terminal
connection,
No option,
50/60Hz
MCCB
/M4
U-Series
UAD50C
50AF
UAD50S
UAD100R
3
IP20
A
3
IP20
A
100AF
3
IP20
A
50
50
AC690
AC660
DC250
6
17
1
25,000
15,000
50
50
AC690
AC660
DC250
6
52.5
1
25,000
15,000
100
100
AC690
AC660
DC250
6
52.5
1
25,000
10,000
75
130
60
82
0.65
75
130
60
82
0.78
75
130
60
82
0.78
Accessories
Signal
Auxiliary switch
UAD50C
UAD50S, UAD100R
Trip alarm switch
UAD50C
UAD50S, UAD100R
Shunt trip 1)
UAD50C
UAD50S, UAD100R
Under voltage trip2)
UAD50C
UAD50S, UAD100R
1C, right-hand-side
AUX 10A R1
AUX 10UA R1
1C, right-hand-side
ALT 10A R1
ALT 10UA R1
DC24V
SHT 10A A
SHT 10UA A
DC24V
UVT 10A J
UVT 10UA J
1C, left-hand-side
2C,right-hand-side
AUX 10A R2
AUX 10UA L1
1C, left-hand-side
ALT 10UA L1
AC100-120V
SHT 10A F
SHT 10UA F
DC100-110V
AC100-120V
UVT 10A L
UVT 10A N
UVT 10UA L
UVT 10UA N
DC100-110V
SHT 10A C
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.
120
AC200-230V
SHT 10UA H
AC200-230V
UVT 10A P
UVT 10UA P
AC380-415V
SHT 10A H
SHT 10UA B
AC380-415V
UVT 10A Q
UVT 10UA Q
AC440-480V
SHT 10UA D
AC440-480V
UVT 10A R
UVT 10UA R
MCCB
Operating
UAD50C
Power supply direction
S type
Operating Surface
L type
handle 1)
S type
Extended
L type
Motor operator 2)
UAD50S, UAD100R
Upper
Right
Left
Upper
Right
Left
TFG 10AS U4
TFG 10AS R4
TFG 10AS L4
TFG 10UAS U4
TFG 10UAS R4
TFG 10UAS L4
TFG 10AL L4
TFG 10UAL U4
TFG 10AL U4
TFH 10AS
TFG 10UAL L4
TFH 10UAS
TFH 10AL
TFH 10UAL
DC24V
AC/DC110V
AC/DC220V
DC24V
AC/DC110V
AC/DC220V
Mechanical interlock
MIF 10A 3
MIF 10UA 3
Padlock plate3)
PLD 10UA
Mounting
DIN-rail adaptor 1)
Structure
Mounting base
Plug-in Connection 2C contact
block 2)
3C contact
Conn block barrier
DRA 10UA
For both line & load side
TDM 10AP
CBM 10AB 2
CBM 10AB 3
CBM BARR
Terminal
Cage terminal block
3EA/SET
UAD50C, UAD50S
UAD100R
Terminal cover 1)
Interpole barrier 2)
TCF 10AP 3
2EA/SET
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 4EA
Rated
current
Code
UAD50C
50A
20
UAB50C
UAD50S
50A
20
UAB50S
UAD100R
100A
20
UAB100R
Model
Unit
(EA)
Originated
MCCB model
Specification
Category
Screw type
terminal connection,
No option, 50/60Hz
MCCB/M5
U-Series
UCD100S
UCD160H
UCD250H
UCD50H
UCD100S
UCD100H
UCD160H
UCD250S
UCD250H
50AF
3
IP20
A
100AF
3
IP20
A
125AF
3
IP20
A
160AF
3
IP20
A
3
IP20
A
3
IP20
A
50
AC690
AC660
DC250
6
105
1
25,000
10,000
100
AC690
AC660
DC250
6
73.5
1
25,000
10,000
125
AC690
AC660
DC250
6
105
1
25,000
10,000
160
AC690
AC660
DC250
6
105
2
25,000
10,000
250
AC690
AC660
DC250
6
73.5
2
25,000
10,000
250
AC690
AC660
DC250
6
105
2
25,000
10,000
90
155
60
84.5
1
90
155
60
84.5
1
90
155
60
84.5
1
105
165
60
84.5
1.3
105
164
60
84
1.2
105
165
60
84.5
1.3
250AF
Accessories
Signal
Auxiliary switch
1C, left-hand-side
UCD100S
AUX 10B L1
UCD250S
AUX 20C L1
AUX 20FG L1
2C, left-hand-side
AUX 12FG L2
1C, right-hand-side
1C, left-hand-side
UCD100S
ALT 10B L1
UCD250S
ALT 20C L
DC24V
ALT 12FG R1
DC100-110V
SHT 10B A
AC100-120V
AC200-230V
SHT 10B F
ALT 12FG L1
AC380-415V
UCD250S
SHT 20C A
SHT 12FG A
SHT 12FG C
SHT 12FG F
SHT 12FG H
SHT 12FG B
SHT 12FG D
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
AC440-480V
UCD100S
UVT 10B J
UVT 10B L
UVT 10B N
UVT 10B P
UVT 10B Q
UVT 10B R
UCD250S
UVT 20C J
UVT 20C L
UVT 20C N
UVT 20C P
UVT 20C Q
UVT 20C R
UVT 12FG J
UVT 12FG L
UVT 12FG N
UVT 12FG P
UVT 12FG Q
UVT 12FG R
SHT 20C F
SHT 20C H
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC) The tripping voltage: 20-70% of rated voltage(AC/DC)
122
AC440-480V
SHT 10B H
MCCB
Operating
UCD50H, UDC100H
Power supply direction
S type
Operating Surface
L type
handle 1)
S type
Extended
L type
Motor operator 2)
UCD100S
Upper
Right
Left
Upper
Right
Left
TFG 10UFS U4
TFG 10UFS R4
TFG 10UFS L4
TFG 10BS U4
TFG 10BS R4
TFG 10BS L4
TFG 10UFL L4
TFG 10BL U4
TFG 10UFL U4
TFH 10UFS
TFG 10BL L4
TFH 10BS
TFH 10UFL
TFH 10BL
DC24V
AC/DC110V
AC/DC220V
DC24V
AC/DC110V
AC/DC220V
MIF 10UF 3
Mechanical interlock
MIF 10UF 3
Padlock plate3)
PLD 10UF
UCD250S
Operating Surface
L type
handle 1)
S type
Extended
L type
Motor operator 2)
UCD160H, UCD250H
Upper
Right
Left
Upper
Right
Left
TFG 20CS U4
TFG 20CS R4
TFG 20CS L4
TFG 20UGS U4
TFG 20UGS R4
TFG 20UGS L4
TFG 20CL L4
TFG 20UGL U4
TFG 20CL U4
TFH 20CS
TFG 20UGL L4
TFH 20UGS
TFH 20CL
TFH 20UGL
DC24V
AC/DC110V
AC/DC220V
DC24V
AC/DC110V
AC/DC220V
Mechanical interlock
MIF 20UG 3
MIF 20UG 3
Padlock plate3)
PLD 20UG
Mounting
UCD50H, UCD100S, UCD100H
Structure
For both line & load side For line side only
Mounting base
TDM 10BP
TDM 10BF
Plug-in Connection 2C contact
CBM 10AB 2
block 1)
3C/5C contact CBM 10AB 3 3)
Conn. block barrier
CBM BARR
TDM 20CF 2)
CBM 20C 2
CBM 20C 5 3)
TDM 20CF
1) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.
2) 2EA are required for both line & load side plug-in type 3P breaker.
3) CBM 10AB 3: 3C, CBM 20C 5: 5C
Terminal
UCD100S
UCD50H, UCD100H
UCD250S
3EA/SET
Terminal cover 1)
Interpole barrier 2)
UCD160H, UCD250H
TBB 20C 3
CTB 20C 3S
TCF 10FP 3
TCF 20CP 3
TCF 20GP 3
TQQ 10B 3PLINE TQQ 12FG 3PLINE TQQ 20C 3PLINE TQQ 12FG 3PLINE
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 4EA
Originated
MCCB model
Rated
current
Code
UCD50H
50A
UCB50H
UCD100S
100A
10
UCB100S
UCD100H
125A
UCB100H
UCD160H
160A
UCB160H
UCD250S
250A
10
UCB250S
UCD250H
250A
UCB250H
Model
Unit
(EA)
Specification
Category
Screw type
terminal connection,
No option, 50/60Hz
MCCB/M5
U-Series
3P
b
c
d
UCD400S
UCD630S
UCD800S
UCD1000S
UCD1250S
400AF
3
IP20
A
630AF
3
IP20
A
800AF
3
IP20
A
1000AF
3
IP20 1)
A
1250AF
3
IP20 1)
A
400
400
AC690
AC660
DC250
6
187
4
20,000
6,000
630
630
AC690
AC660
DC250
6
187
6.3
20,000
6,000
800
800
AC690
AC660
DC250
6
187
8
10,000
3,000
1,000
1,000
AC750
AC690
1,250
1,250
AC750
AC690
8
165
10
10,000
3,000
8
165
12.5
10,000
3,000
140
257
110
145
4.5
210
280
110
145
9.5
210
280
110
145
9.5
210
370
110
159
13
210
370
110
159
13.5
Height
Depth
Accessories
Signal
Auxiliary switch
1C, right-hand-side
UCD400, UCD630, UCD800
AUX 46D R1
UCD1000, UCD1250
AUX 80NE R1
1C, left-hand-side
Trip alarm switch
ALT 46D L1
UCD400, UCD630, UCD800
UCD1000, UCD1250
Shunt trip 1)
DC24V
SHT 46D A
UCD400, UCD630, UCD800
SHT 120NE A
UCD1000, UCD1250
DC24V
Under voltage trip 2)
UVT 46D J
UCD400, UCD630,UCD800
UVT 120NE J
UCD1000, UCD1250
2C, right-hand-side
3C, right-hand-side
AUX 80NE R2
AUX 80NE R3
1C, right-hand-side
ALT 80NE R1
DC100-110V
AC100-120V
SHT 46D C
SHT 46D F
SHT 120NE C
SHT 120NE F
DC100-110V
AC100-120V
UVT 46D L
UVT 46D N
UVT 120NE L
UVT 120NE N
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
124
AC200-230V
SHT 46D H
SHT 120NE H
AC200-230V
UVT 46D P
UVT 120NE P
AC380-415V
SHT 46D B
SHT 120NE B
AC380-415V
UVT 46D Q
UVT 120NE Q
AC440-480V
SHT 46D D
SHT 120NE D
AC440-480V
UVT 46D R
UVT 120NE R
MCCB
Operating
UCD400, UCD630, UCD800
Power supply direction
Operating
Surface S type
handle 1)
Extended S type
Upper
Right
Left
TFG 46DS U2
TFG 46DS R2
TFG 46DS L2
TFH 46DS
UCD400
DC24V
Motor operator 2)
UCD630, UCD800
AC/DC110V
AC/DC220V
DC24V
AC/DC110V
MOT 40D DC24 MOT 40D ADC110 MOT 40D ADC220 MOT 68E DC24
Mechanical interlock
UCD1000, UCD1250
AC/DC220V
DC24V
AC/DC110V
AC/DC220V
MOT 68E ADC110 MOT 68E ADC220 MOT 80NE DC24 MOT 80NE ADC110 MOT 80NE ADC220
MIF 40D 3
MIF 80E 3
Padlock plate3)
PLD 40D
PLD 120NE
Extension handle 4)
THA 46D
THA 120NE
Mounting
UCD400
Structure
Mounting base
Plug-in
Connection 2C contact
5C contact
block 1)
TDM 4BA 2)
TYA 5/2 3)
TYA 5/5 3)
UCD630, UCD800
For line side only For both line & load side For line side only
TDM 4BA
TDM 5BA 2)
TYA 5/2 3)
TYA 5/5 3)
TDM 5BA
1) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.
2) 2EA are required for both line & load side plug-in type 3P breaker.
3) TYA type connection blocks are to be installed with separate mounting angle. Separate mounting angle is not supplied.
Terminal
Terminal bus bar
Cage terminal block
3EA/SET
Terminal cover 1)
Interpole barrier 2)
UCD400
UCD630
UCD800
TBB 4S 3
TBB 6S 3
TBB 8S 3
CTB 40D 3S
UCD1000, UCD1250
CTB 80E 3S
TCF 40D 3
TCF 80E 3
TQQ 80NE 3P
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 4EA
Originated
MCCB model
Model
Rated
current
Code
Unit
(EA)
UCD400S
400A
UCB400S
UCD630S
630A
UCB630S
UCD800S
800A
UCB800S
UCD1000S
1000A
UCB1000S
UCD1250S
1250A
UCB1250S
Specification
Screw type
terminal connection,
No option, 50/60Hz
Category
MCCB/M5
U-Series
UPD100S
UPD160S
UPD250S
UPD400S
UPD630S
125AF
160AF
250AF
400AF
630AF
IP20
IP20
IP20
IP20
IP20
125
160
250
400
630
125
160
250
400
630
AC750
AC750
AC750
AC750
AC750
AC690
AC690
AC690
AC690
AC690
DC500
DC500
DC500
200
200
200
200
200
1.6
2.5
6.3
25,000
25,000
25,000
20,000
20,000
10,000
10,000
10,000
6,000
6,000
Width
105
105
105
140
140
Height
165
165
165
255
255
Depth
86.5
86.5
86.5
117
117
112
112
112
159.5
159.5
1.8
Plug-in
Terminal connection
Bus bar
a
Dimensions
(mm)
3P
d
Weight (kg, breaker only) 3P
Accessories
Signal
Auxiliary switch
1C, right-hand-side 1C, left-hand-side
UPD100, UPD160,UPD250
AUX 12UP R1
UPD400, UPD630
AUX 46UP L1
1C, right-hand-side 1C, left-hand-side
Trip alarm switch
ALT 12UP L1
UPD100, UPD160,UPD250
ALT 46UP R1
UPD400, UPD630
DC24V
DC100-110V
Shunt trip 1)
SHT 12UP A
SHT 12UP C
UPD100, UPD160,UPD250
UPD400, UPD630
SHT 46UP A
SHT 46UP C
Under voltage trip 2)
DC24V
DC100-110V
UPD100, UPD160,UPD250
UVT 12UP J
UVT 12UP L
UPD400, UPD630
UVT 46UP J
UVT 46UP L
AC100-120V
SHT 12UP F
SHT 46UP F
AC100-120V
UVT 12UP N
UVT 46UP N
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) The permissible operating voltage: 85-110% of rated voltage(AC), 85~125% of rated voltage(DC)
The tripping voltage: 20-70% of rated voltage(AC/DC)
126
AC200-230V
SHT 12UP H
SHT 46UP H
AC200-230V
UVT 12UP P
UVT 46UP P
AC380-415V
SHT 12UP B
SHT 46UP B
AC380-415V
UVT 12UP Q
UVT 46UP Q
AC440-480V
SHT 12UP D
SHT 46UP D
AC440-480V
UVT 12UP R
UVT 46UP R
MCCB
Operating
UPD100, UPD160, UPD250
Power supply direction
S type
Operating Surface
L type
handle 1)
S type
Extended
L type
Right
Left
Upper
Right
Left
TFG 12UPS U4
TFG 12UPS R4
TFG 12UPS L4
TFG 46UPS U2
TFG 46UPS R2
TFG 46UPS L2
TFG 12UPL U4
TFG 12UPL L4
TFH 12UPS
TFH 46UPS
TFH 12UPL
DC24V
Motor operator 2)
UPD400, UPD630
Upper
AC/DC110V
AC/DC220V
DC24V
AC/DC110V
Mechanical interlock
MIF 12UP 3
MIF 46UP 3
Padlock plate3)
PLD 12UP
PLD 12UP
Extension handle 4)
AC/DC220V
THA 46UP
Mounting
UPD100, UPD160, UPD250
Structure
Plug-in
UPD400, UPD630
For both line & load side For line side only For both line & load side For line side only
Mounting base
TDM 12NEP
Connection 6C contact
block 1)
12C contact
CBM 26NE 6
TDM 12NEF
TDM 46NEP
TDM 46NEF
CBM 26NE 6
2)
2)
CBM 26NE 6
CBM 26NE 6
1) Connection blocks are required for internal accessory installation in both line & load side plug-in type 3P breaker.
2) 2EA shall be ordered for 12C contact.
Terminal
UPD100, UPD160, UPD250
UPD400
UPD630
6EA/SET
TBB 12NE 3
3EA/SET
CTB 12UP 3S
CTB 46UP 3S
Terminal cover 1)
Interpole barrier 2)
4EA/SET
TCF 12UP 3
TCF 46UP 3
TQQ 12NE 3P
TQQ 46NE 3P
1) For both line and load side of breaker, 2EA shall be ordered.
2) Supplied as standard component
Required quantity for both line and load side of breaker: 4EA
Originated
MCCB model
Model
Rated
current
UPD100S
125A
UPB100S
UPD160S
160A
UPB160S
UPD250S
250A
UPB250S
UPD400S
400A
UPB400S
UPD630S
630A
UPB630S
Code
Unit
(EA)
Specification
Category
Screw type
terminal connection,
No option, 50/60Hz
MCCB/M5
U-Series
UMB30R
UMB30S
UMB30H
UMB50S
UMB50H
UMB30H 10kA
UMB50H 10kA
30AF
Degree of protection
IP20
IP20
Utilization category
Protection
overload, short-circuit
overload, short-circuit
15, 20, 30
AC250
AC250
AC220
AC220
Rated
short-circuit
breaking capacity
IEC 60947-2
Service [Ics] % of [Icu]
K 60947-2
Trip mechanism
50AF
2.5
10
50
10
50
Hydraulic magnetic
Thermal magnetic
Mounting
Terminal connection
Dimensions
(mm)
Screw
2P
Width
33
35
35
Height
70
80
80
Depth
42
60
60
57
76
76
0.1
0.13
0.15
d
Weight (kg, breaker only)
2P
- KS certified products. English nameplate and 50Hz marking are not available.
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
UMB30R
2.5kA
UMB30S
5kA
UMB30H
10kA
UMB50S
5kA
UMB50H
10kA
128
Rated
current
15A
20A
30A
15A
20A
30A
15A
20A
30A
15A
20A
30A
40A
50A
15A
20A
30A
40A
50A
2 pole
Code
UMB30R 2PT4S0000C 00015
UMB30R 2PT4S0000C 00020
UMB30R 2PT4S0000C 00030
UMB30S 2PT4S0000C 00015
UMB30S 2PT4S0000C 00020
UMB30S 2PT4S0000C 00030
UMB30H 2PT4S0000C 00015
UMB30H 2PT4S0000C 00020
UMB30H 2PT4S0000C 00030
UMB50S 2PT4S0000C 00015
UMB50S 2PT4S0000C 00020
UMB50S 2PT4S0000C 00030
UMB50S 2PT4S0000C 00040
UMB50S 2PT4S0000C 00050
UMB50H 2PT4S0000C 00015
UMB50H 2PT4S0000C 00020
UMB50H 2PT4S0000C 00030
UMB50H 2PT4S0000C 00040
UMB50H 2PT4S0000C 00050
Unit(EA)
150
150
150
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
Specification
Category
Screw type
terminal connection,
No option, 50/60Hz
MCCB/M1
MCCB
UDB30H 10kA
UDB50H 10kA
UDB100H 10kA
UDB30S
UDB30H
UDB50S
UDB50H
UDB100S
UDB100H
30AF
50AF
2, 3
2, 3
2, 3
Degree of protection
IP20
IP20
IP20
Utilization category
Rated current (A)
Service [Ics]
Trip mechanism
overload, short-circuit
5,10,15,20,30,40,50
AC460
AC460
AC460
2P: AC220
2P: AC220
2P: AC220
3P: AC220/460
3P: AC220/460
3P: AC220/460
Rated
short-circuit
Ultimate
breaking capacity [Icu]
(kA r.m.s.)
IEC 60947-2
K 60947-2
overload, short-circuit
3 1) ,5,10,15,20,30
Rating
overload, short-circuit
Protection
100AF
AC440/460V, 50-60Hz
2.5
AC380/415V, 50-60Hz
2.5
AC220/240V, 50-60Hz
5-10A: 2.5
15-30A: 5
5-10A: 2.5
15-30A: 5
5-10A: 5
15-30A: 10
% of [Icu]
5-10A: 2.5
2.5
15-50A: 5
5-10A: 2.5
2.5
15-50A: 5
5-10A: 5
15-50A: 10
15,20,30,40,50,60,75,100
2.5
2.5
10
50
50
50
Hydraulic magnetic
Direct mounting by screw
Mounting
DIN-rail
Terminal connection
Screw
Dimensions
(mm)
2/3P
Width
50/75
50/75
75 2) /75
Height
96
96
96
Depth
60
60
60
80
80
80
0.2/0.35
0.2/0.35
0.2/0.35
d
Weight (kg, breaker only)
2/3P
- KS certified products. English nameplate and 50Hz marking are not available.
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) 3A is not applicable for UDB30H.
2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.
Accessories
Signal
Auxiliary switch 1C, left-hand-side
AUX 10UD L1
2 pole
Trip alarm switch 1C,
left-hand-side 3 pole
Shunt trip 1)
DC24V
DC100-110V
AC100-120V
AC200-230V
AC380-415V
AC440-480V
SHT 10UD A
SHT 10UD C
SHT 10UD F
SHT 10UD H
SHT 10UD B
SHT 10UD D
SHT 10UD AT 2)
SHT 10UD CT 2)
SHT 10UD FT 2)
SHT 10UD HT 2)
SHT 10UD BT 2)
SHT 10UD DT 2)
1) The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC
2) Terminal block type
Terminal
Interpole barrier 1)
2EA/SET
U-Series
3 pole
2 pole
Code
Unit
(EA)
Code
Unit
(EA)
3A
46
32
5A
46
32
UDB30S
10A
46
32
5kA
15A
46
32
20A
46
32
30A
46
32
5A
46
32
UDB30H
10A
46
32
5-10A : 5kA
15-30A : 10kA
15A
46
32
20A
46
32
30A
46
32
5A
46
32
10A
46
32
15A
46
32
20A
46
32
30A
46
32
40A
46
32
50A
46
32
5A
46
32
10A
46
32
UDB50H
15A
46
32
5-10A : 5kA
15-50A : 10kA
20A
46
32
30A
46
32
40A
46
32
50A
46
32
15A
32
32
20A
32
32
UDB50S
5kA
130
Rated
current
30A
32
32
UDB100S
40A
32
32
5kA
50A
32
32
60A
32
32
75A
32
32
100A
32
32
15A
32
32
20A
32
32
30A
32
32
UDB100H
40A
32
32
10kA
50A
32
32
60A
32
32
75A
32
32
100A
32
32
Specification
Screw type
terminal
connection,
No option,
50/60Hz
Category
MCCB
/M1
MCCB
UMG30R
UMG30S
UMG30H
UMG50S
UMG50H
UMG30H 10kA
UMG50H 10kA
30AF
50AF
Degree of protection
IP20
IP20
Utilization category
A
15, 20, 30
Rating
15,30
15,30
AC250
AC250
AC220
AC220
0.03
0.03
AC220/240V, 50-60Hz
IEC 60947-2
K 60947-2
Earth leakage
protection
Trip mechanism
Protection
2.5
10
10
50
50
by current transformer
by current transformer
Mounting
Terminal connection
Dimensions
Screw
2P
(mm)
Width
33
35
35
Height
70
80
80
Depth
42
60
60
57
76
76
0.1
0.13
0.15
d
Weight (kg, breaker only)
2P
- KS certified products. English nameplate and 50Hz marking are not available.
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
U-Series
UMG50S
5kA
UMG50H
10kA
Rated
current
2 pole
Code
Unit(EA)
15A
150
20A
150
30A
150
15A
80
20A
80
30A
80
15A
80
20A
80
30A
80
15A
80
20A
80
30A
80
40A
80
50A
80
15A
80
20A
80
30A
80
40A
80
50A
80
Specification
Category
15mA, 40/45 ,
Screw type
terminal connection,
No option, 50/60Hz
ELCB/M6
Specification
Category
30mA
Model /
Breaking capacity at
AC220/240V
UMG30R
2.5kA
UMG30S
5kA
UMG30H
10kA
UMG50S
5kA
UMG50H
10kA
132
Rated
current
2 pole
Code
Unit(EA)
15A
150
20A
150
30A
150
15A
80
20A
80
30A
80
15A
80
20A
80
30A
80
15A
80
20A
80
30A
80
40A
80
50A
80
15A
80
20A
80
30A
80
40A
80
50A
80
30mA, 40/45 ,
Screw type
terminal connection,
No option, 50/60Hz
ELCB/M6
MCCB
UDG30H 10kA
UDG50H 10kA
UDG100H 10kA
UDG30S
UDG30H
UDG50S
UDG50H
UDG100S
UDG100H
30AF
50AF
100AF
2, 3
2, 3
*2, 3
IP20
IP20
IP20
A
A
A
earth leakage, overload, short-circuit earth leakage, overload, short-circuit earth leakage, overload, short-circuit
3 1), 5,10,15,20,30
5,10,15,20,30,40,50
15,20,30,40,50,60,75,100
15, 30
15, 30
30, 100
AC460
AC460
AC460
Rating
2P: AC220
2P: AC220
2P: AC220
Rated operational voltage [Ue] (V)
3P: AC220/460
3P: AC220/460
3P: AC220/460
Rated impulse withstand voltage [Uimp] (kV)
6
6
6
Rated operating time (sec.)
0.03
0.03
0.03
5-10A: 2.5
5-10A: 2.5
AC440/460V, 50-60Hz
2.5
2.5
2.5
5
Rated
15-30A: 5
15-50A: 5
Ultimate
short-circuit
5-10A: 2.5
5-10A: 2.5
AC380/415V, 50-60Hz
2.5
2.5
2.5
5
breaking capacity [Icu]
15-30A: 5
15-50A: 5
(kA r.m.s.)
5-10A: 5
5-10A: 5
IEC 60947-2
AC220/240V, 50-60Hz
5
5
5
10
15-30A: 10
15-50A: 10
K 60947-2
Service [Ics] % of [Icu]
50
50
50
Earth leakage detection
by current transformer
by current transformer
by current transformer
Number of poles (P)
Degree of protection
Utilization category
Protection
Rated current (A)
Rated residual current [I n] (mA)
Rated insulation voltage [Ui] (V)
Earth leakage
protection
50/75
96
60
80
0.33/0.44
50/75
96
60
80
0.33/0.44
75 2)/75
96
60
80
0.46/0.63
- KS certified products. English nameplate and 50Hz marking are not available.
- The breaking capacity highlighted with blue and thick type is standard nominal value for each model in this catalogue.
1) 3A is not applicable for UDG30H.
2) 2P breaker has same dimension as 3P breaker, but the middle pole is removed.
Accessories
Signal
Auxiliary switch
1C, left-hand-side
1C, left-hand-side
AUX 10UD L1
2 pole
3 pole
Terminal
Interpole barrier 1)
2EA/SET
U-Series
UDG30S
5kA
UDG30H
5-10A : 5kA
15-30A : 10kA
UDG50S
5kA
UDG50H
5-10A : 5kA
15-50A : 10kA
Rated
current
2 pole
Code
3 pole
Unit
(EA)
Code
Unit
(EA)
3A
46
32
5A
46
32
10A
46
32
15A
46
32
20A
46
32
30A
46
32
5A
46
32
10A
46
32
15A
46
32
20A
46
32
30A
46
32
5A
46
32
10A
46
32
15A
46
32
20A
46
32
30A
46
32
40A
46
32
50A
46
32
5A
46
32
10A
46
32
15A
46
32
20A
46
32
30A
46
32
40A
46
32
50A
46
32
Specification
Category
15mA, 40/45 ,
Screw type
terminal
connection,
No option,
50/60Hz
ELCB
/M6
30mA
Model /
Breaking capacity at
AC220/240V
UDG30S
5kA
UDG30H
5-10A : 5kA
15-30A : 10kA
UDG50S
5kA
134
Rated
current
2 pole
Code
3 pole
Unit
(EA)
Code
Unit
(EA)
Specification
3A
46
32
5A
46
32
10A
46
32
15A
46
32
20A
46
32
30A
46
32
5A
46
32
30mA, 40/45 ,
10A
46
32
15A
46
32
20A
46
32
30A
46
32
5A
46
32
Screw type
terminal
connection,
No option,
50/60Hz
10A
46
32
15A
46
32
20A
46
32
30A
46
32
40A
46
32
50A
46
32
Category
ELCB
/M6
MCCB
Model /
Breaking capacity at
AC220/240V
Rated
current
2 pole
Code
3 pole
Unit
(EA)
Code
Unit
(EA)
Specification
5A
46
32
10A
46
32
UDG50H
15A
46
32
5-10A : 5kA
15-50A : 10kA
20A
46
32
30A
46
32
40A
46
32
50A
46
32
15A
32
32
20A
32
32
30A
32
32
30mA, 40/45 ,
40A
32
32
50A
32
32
60A
32
32
75A
32
32
Screw type
terminal
connection,
No option,
50/60Hz
100A
32
32
15A
32
32
20A
32
32
30A
32
32
40A
32
32
50A
32
32
60A
32
32
75A
32
32
100A
32
32
UDG100S
5kA
UDG100H
10kA
Category
ELCB
/M6
100mA
Model /
Breaking capacity at
AC220/240V
Rated
current
2 pole
Code
3 pole
Unit
(EA)
Code
Unit
(EA)
15A
32
32
20A
32
32
Specification
30A
32
32
UDG100S
40A
32
32
5kA
50A
32
32
60A
32
32
100mA, 40/45 ,
75A
32
32
100A
32
32
15A
32
32
20A
32
32
Screw type
terminal
connection,
No option,
50/60Hz
30A
32
32
40A
32
32
50A
32
32
60A
32
32
75A
32
32
100A
32
32
UDG100H
10kA
Category
ELCB
/M6
U-Series
Max. (3-30A)
UAB50C
UAB50R
UAB60C
UAB60R
36
60
120
180
240
360
480
600
720
900
1200
12
20
40
60
80
120
160
200
240
300
400
Min. (3-30A)
Second
UAB30R
Tripping time
Max. (40-100A)
UAB30C
Inst. trip
current (A)
3
5
10
15
20
30
40
50
60
75
100
Minute
Rated
current (A)
Min. (40-100A)
UAB100C
UAD50C
Characteristic curves are
not applicable.
Current
Dimensions
: Center line
(Unit: mm)
Direct mounting
2P
Mounting hole
Mounting hole
3P
M5 screw (3-50A)
M8 screw (60-100A)
4P
Mounting hole
[Connection conductor]
24
7 (Max.)
5.5 (3~50A)
9 (60~100A)
Trip
button
50
130
82
C3.5
M4 0.7
mounting
screw
Trip
button
25
50
37.5
12.5
25
75
15
25
25
100
50
50
[Terminal part]
24
17
10
60
82
3P
4P
4P
3P
2P
[Panel cut-out]
2P
3P
4P
R5
12.5
25
M4 0.7
tapped hole
25
25
for handle exposure
(total breaker height: 64mm)
138
(Max.)
7.57.5
Trip
button
115
16
30.5
48
12.5
71
35.5
96
MCCB
Dimensions
: Center line
(Unit: mm)
Plug-in mounting
[Plug-in connection part]
[Mounting base]
41
80
M4 nut+S/W+P/W
50
20
18.5
RH screw
M4 L18+S/W+P/W
25
162
28
115
130
87
180
10.2
28
M4 nut+S/W+P/W
M6 nut+S/W+P/W
18.5
2
23.5
80
22
102
[Panel cut-out]
[Connection conductor]
83
25
34
4- 6 hole
180
55
6.5
34
19.5
81
21(Max.)
10(Max.)
25
TDF 10A for line side only type plug-in mounting, please refer to page 212.
No.
of
Auxiliary
poles switch
Trip alarm
switch
Shunt
trip
Under
voltage trip
3
Right
Left
Handle
[ Front ]
U-Series
15-32A
Rated
current (A)
Minute
Inst. trip
current (A)
15
16
20
25
30
32
300
320
400
500
600
640
60
72
80
100
120
128
Tripping time
Second
UAB50S
UAB50H
Max.
UAB100R
Min.
UAB100S
UAD50S
UAD100R
Current
40-100A
Minute
40
50
60
63
75
80
100
Inst. trip
current (A)
400
500
600
630
750
800
1000
80
100
120
126
150
160
200
Max.
Tripping time
Second
Min.
Rated
current (A)
Current
No.
of
Auxiliary
poles switch
Trip alarm
switch
Shunt
trip
Under
voltage trip
3
Right
Left
Handle
[ Front ]
140
MCCB
Dimensions
: Center line
(Unit: mm)
Direct mounting
2P
Mounting hole
3P
4P
Mounting hole
M5 screw (15-50A)
M8 screw (60-100A)
Mounting hole
[Connection conductor]
24
7 (Max.)
5.5 (15~30A)
9 (60~100A)
C3.5
83.5
20.5
50
115
130
8.6
22
Trip
button
Trip
button
[Terminal part]
7.2
Trip
button
15 (Max.)
M4 0.7
mounting
screw
50
75
25
25
100
10
50
56
60
25
4.6
50
25
37.5
24
16.4
8
82
2P
3P
4P
53
3P
110
2P
[Panel cut-out]
4P
3P
2P
12.5
M4 0.7
tapped hole
25
25
25
48
12.5
35.5
71
96
Plug-in mounting
41
RH screw
M4 L18+S/W+P/W
56.100
[Mounting base]
80
50
25
23.5
80
101
[Panel cut-out]
83
25
115
162
10.2
87
25
[Connection conductor]
34
55
21(Max.)
180
19.5
34
81
4- 6 hole
6.5
10(Max.)
M6 nut+S/W+P/W
2
18.5
28
130
180
28
M4 nut+S/W+P/W
M4 nut+S/W+P/W
20
18.5
TDF 10A for line side only type plug-in mounting, please refer to page 212.
U-Series
Minute
15
16
20
25
30
32
40
50
60
63
75
80
100
Max. (60-100A)
Tripping time
UCB50R
Min. (40-100A)
Inst. trip
current (A)
150
160
200
250
300
320
400
500
600
630
750
800
1000
30
32
40
50
60
64
80
100
120
126
150
160
200
Hour
15-100A
Rated
current (A)
Max. (15-30A)
Min. (15-30A)
Second
UCB100R
15-30A
40-100A
UCB100S
UCD100S
Characteristic curves
are not applicable.
Percentage for rated current (%)
Current
Dimensions
: Center line
(Unit: mm)
Direct mounting
4P
Mounting hole
Mounting hole
M8 screw
[Connection conductor]
24
8.5 (Max.)
3P
2P
Mounting hole
Trip
button
Trip
button
101.5
50
17 (Max.)
M4 0.7
mounting
screw
37
[Terminal part]
7.3
Trip
button
155
16
134
9 Hole
60
60
90
30
30
30
15 22
10
45
120
30
[Panel cut-out]
4P
3P
2P
4P
2P
3P
4P
53
15
24
Inhex bolt M8 L25
132
3P
6.5
17.4
84.5
60
10.5
30
M4 0.7
30
tapped hole
59
30
88
44
26
for handle exposure
(total breaker height: 64mm)
142
15
118
MCCB
Dimensions
: Center line
(Unit: mm)
Plug-in mounting
[Plug-in connection part]
[Mounting base]
41
RH screw
M5 L20+S/W+P/W
94
M5 nut+S/W+P/W
21
M5 nut+S/W+P/W
60
134
46
27.5
M6 nut+S/W+P/W
172.5
13.5
48
191
155
99
27.5
30
23.5
81
105.5
[Panel cut-out]
26.5
97
80
A
30
4- 5.5 hole
33.5
26 (Max.)
191
55
19.5
6.5
33.5
93
13(Max.)
[Connection conductor]
TDF 10B for line side only type plug-in mounting, please refer to page 212.
Trip alarm
switch
Shunt
trip
Under
voltage trip
3
Right
Left
Handle
[ Front ]
U-Series
Hour
15-32A
Rated
current (A)
15
16
20
25
30
32
Minute
Inst. trip
current (A)
225
240
300
375
450
480
45
48
60
75
90
96
Tripping time
UCB50H
Second
UCB50L
UCB100H
Max.
UCB100L
Min.
16-30A
UCD50H
UCD100H
Current
40-125A
Rated
current (A)
40
50
60
63
75
80
100
125
Max. (60-125A)
Inst. trip
current (A)
400
500
600
630
750
800
1000
1250
80
100
120
126
150
160
200
250
Tripping time
Min. (40-125A)
Second
Minute
Hour
Current
No.
of
Auxiliary
poles switch
Trip alarm
switch
Shunt
trip
Under
voltage trip
3
Right
Left
Handle
[ Front ]
144
40-125A
MCCB
Dimensions
: Center line
(Unit: mm)
Direct mounting
2P, 3P
4P
M8 screw
24
[Connection conductor]
17 (Max.)
90
30
120
[Terminal part]
10
30
48
55
10
60
84.5
18
[Panel cut-out]
4P
3P
3P
30
53
132
4P
30
24
Inhex bolt M8 L25
30
4P
53
30
8.5
30
53
30
8.5(Max.)
101
M4 L60
mounting
screw
37
10.5
Trip
button
Trip
button
155
16
50
134
9 hole
44
88
25
118
M4 tapped hole
Plug-in mounting
[Mounting base]
RH screw
M5 L20+S/W+P/W
94
60
30
M5 nut+S/W+P/W
134
27.0
46
M6 nut+S/W+P/W
2
23.5
81
105.5
26.5
97
80
30
[Connection conductor]
A
4- 5.5 hole
26 (Max.)
191
55
19.5
6.5
33.5
93
33.5
13 (Max.)
[Panel cut-out]
172.5
99
155
191
13.5
46
27.5
M5 nut+S/W+P/W
TDF 10B for line side only type plug-in mounting, please refer to page 212.
U-Series
125-250A
Rated
current (A)
250
300
320
350
400
450
500
Minute
1250
1500
1600
1750
2000
2250
2500
Max.
Tripping time
UCB250R
Inst. trip
current (A)
125
150
160
175
200
225
250
Min.
Second
UCB250S
UCB250N
UCD250S
Characteristic curves
are not applicable.
Current
Dimensions
: Center line
97
23
Direct mounting
Mounting hole
3P
4P
Mounting hole
(Unit: mm)
23
[with terminal
bus bar*option]
M8 screw
23
35
24
[Terminal part]
Trip
button
11
M4 0.7
mounting
screw
[Connection conductor]
11 (Max.)
35
12
35
55
11
60
84
11
M4 0.7
tapped hole
35
35
35
23 (Max.)
[Panel cut-out]
4P
3P
4P
3P
4P
53
125
3P
23
35
28
53
35
140
24
Inhex bolt
M8 L25
10.5
24
105
26
103
51.5
138
146
4
35
52.5
70
25
49.5
23
11.5
Trip
button
14.5
35.5
23.5 26.5
143
164
44.5
51.5
11
MCCB
Dimensions
: Center line
Plug-in mounting
(Unit: mm)
[Mounting base]
M5 nut+S/W+P/W
21
42
19.5
74
24
M5 screw+S/W+P/W
12.5
25.5
70
185
143
28.5
112
57.5
77.5
24.7
25.5
28
45
25
19
53
24
13
12
15 0.0
6 hole
-0.2
70
Trip alarm
switch
Shunt
trip
Under
voltage trip
3
Right
Left
Handle
[ Front ]
U-Series
100-250A
Rated
current (A)
100
125
150
160
175
200
225
250
1000
1250
1500
1600
1750
2000
2250
2500
200
250
300
320
350
400
450
500
Minute
Inst. trip
current (A)
Tripping time
UCB160H
Max.
Min.
Second
UCB160L
UCB250H
UCB250L
UCD160H
UCD250H
Characteristic curves
are not applicable.
Current
: Handle center line
Direct mounting
97
23
Mounting hole
Mounting hole
M8 screw
24
4
[Terminal part]
[with terminal
bus bar*option]
23
4P
23
35
3P
23
101
4 24
M4 L60
mounting
screw
[Connection conductor]
8
10
9
35
48
55
60
84.5
10
11
35
M4 Tapped hole
35
25
for handle exposure
(total breaker height: 66mm)
148
35
22 (Max.)
4P
53
3P
53
125
35
35
[Panel cut-out]
4P
3P
4P
3P
23
35
11.5
35 35
140
53
35
11(Max.)
16
50
144
165
11
35 35
105
(Unit: mm)
11
: Center line
51.5
138
10.5
Dimensions
24
Inhex bolt
M8 L25
MCCB
Dimensions
: Center line
Plug-in mounting
(Unit: mm)
[Mounting base]
42
186
144
12.5
19.5
74
24
25.5
25.5
28.5
70
112
24.7
77.5
57.5
Attaching angle
25 25 t3
45
25
19
53
24
13
12
15 0.0
6 hole
-0.2
70
No.
of
Auxiliary
poles switch
Trip alarm
switch
Shunt
trip
Under
voltage trip
3
Right
Left
Handle
[ Front ]
U-Series
250-400A
Rated
current (A)
2500
3000
3200
3500
4000
Max.
Min.
UCB400S
Second
UCB400H
500
600
640
700
800
Minute
Tripping time
UCB400R
Inst. trip
current (A)
250
300
320
350
400
UCB400L
UCD400S
Characteristic curves are
not applicable.
Percentage for rated current (%)
Current
Dimensions
: Center line
(Unit: mm)
Direct mounting
2P, 3P
4P
143
59
12.5
12.5
59
84
8
37
4
13.5
30 11
12.5
24.5
40
150
95
24.5
317
225
215
150
95
257
30 11
44
59
9.5
59
12.5
202
59
44
15
25
44
25
44
25
25
44
25
140
44
185
25
44
25
80
30.5
13
29
[Connection conductor]
11
12.5(Max.)
[Terminal part]
30(Max.)
150
8
95
110
115.5
145
37
M6
mounting
screw
MCCB
Dimensions
: Center line
(Unit: mm)
[Panel cut-out]
4P
95
112
44
98
215
98
2P, 3P
54
2P, 3P (143)
4P (188)
Plug-in mounting
[Mounting base]
M8 mounting screw
Attaching angle
M5 screw
71.5
65.5
113
44.5
21
139.5
112.5
45
15
90
140
65.5
44.5 21
20 15
89
Supportor pportor
54
112.5
139.5
60
6 for supportor
9
60
10
35
Trip alarm
switch
Shunt
trip
Under
voltage trip
3
Right
Left
Handle
[ Front ]
U-Series
Inst. trip
current (A)
500
630
5000 1000
6300 1260
Minute
Hour
500-630A
Rated
current (A)
UCB630R
UCB630S
Min.
Second
UCB630H
Tripping time
Max.
UCB630L
UCD630S
Characteristic curves
are not applicable.
Percentage for rated current (%)
Current
Dimensions
: Center line
(Unit: mm)
Direct mounting
2P, 3P
4P
84
280
70
210
70
70
70
8 34.5
70
74.5
9.5
280
24.5
74.5
150
95
24.5
280
243
150
95
13.5
70
70
32 16.5
58
70
70
M6
mounting
screw
40
70
40
70
13
12.5
31
46
[Connection conductor]
12.5(Max.)
[Terminal part]
152
45
(Max.)
80
4
8 34.5 15
95
110
115.5
145
MCCB
Dimensions
: Center line
(Unit: mm)
[Panel cut-out]
4P
95
112
70
98
243
98
2P, 3P
2P, 3P (213)
61
4P (283)
for handle exposure
Plug-in mounting
[Mounting base]
Supportor
45
15
25 46.5
71.5
151.5
121.5
140
210
46.5 25
71.5
30 32 18 20
100
151.5
121.5
Attaching angle
M5 screw
21 20
6 for supportor
90
116.2
59
11
45
Max. with of conductor : 40mm
M16 screw
44
60
Trip alarm
switch
Shunt
trip
Under
voltage trip
3
Right
Left
Handle
[ Front ]
U-Series
Inst. trip
current (A)
700
800
7000 1400
8000 1600
Minute
Hour
700-800A
Rated
current (A)
UCB800R
UCB800S
Min.
Second
UCB800H
Tripping time
Max.
UCB800L
UCD800S
Characteristic curves
are not applicable.
Percentage for rated current (%)
Current
Dimensions
: Center line
(Unit: mm)
Direct mounting
2P, 3P
4P
210
280
70
70
70
70
84
10 34.5
70
74.5
9.5
280
150
95
24.5
280
243
150
95
13.5
70
70
32 16.5
74.5
58
70
70
M6
mounting
screw
40
70
40
70
80
12.5
31
46
154
[Connection conductor]
13
12.5 (Max.)
[Terminal part]
45 (Max.)
4
10 34.5 15
95
110
115.5
145
MCCB
Dimensions
: Center line
(Unit: mm)
[Panel cut-out]
4P
95
112
70
98
243
98
2P, 3P
61
2P, 3P (213)
4P (283)
Plug-in mounting
[Mounting base]
Supportor
45
15
25 46.5
71.5
121.5
151.5
140
210
46.5 25
71.5
30 32 18 20
100
121.5
151.5
Attaching angle
M5 screw
21 20
6 for supportor
90
116.2
59
11
45
Max. with of conductor : 40mm
44
M16 screw
60
Trip alarm
switch
Shunt
trip
Under
voltage trip
3
Right
Left
Handle
[ Front ]
U-Series
Protection characteristics
Hour
4
3
505-1000A
Ir
Ig
Characteristics
Ip
1
50
40
30
Minute
20
8
6
5
4
3
Ii
1
50
40
30
Tripping time
UCB1000L
20
12
10
8
6
5
4
3
Second
1
0.8
0.6
0.5
0.4
0.3
0.2
UCD1000S
Characteristics are
not applicable.
0.1
0.08
0.06
0.05
0.04
0.03
3000
2000
2500
500
600
700
800
900
1000
1100
1200
1300
1500
400
200
250
300
125
150
50
80
90
100
40
30
10
20
In %
20%
15%
50ms
20ms
20%
15%
50ms
20ms
10%
-The default values are underlined. Please check and adjust the
setting condition of each characteristic before use.
-1) I2t characteristic can be ON or OFF by adjusting the [tsd] knob.
-2) GFT protection is option.
0.02
0.01
0.008
0.006
0.005
Tolerance
Rated current
LTD setting [Ir] (A)
Isd
10
UCB1000S
Ir %
Current
Dimensions
: Center line
Direct mounting
(Unit: mm)
UCB1000S
Mounting hole
4P
M8 mounting screw
73
3P
14
[Connection conductor]
310
516
370
30
16 36 21
73
[Terminal part]
70
14 25
110
115
159
45
45
70
70
210
70
280
5
7
70
80
[Panel cut-out]
4P
3P
99
61.5
338
78.5
44
M8 tapped hole
156
70
37.5
13
MCCB
Dimensions
: Center line
Direct mounting
(Unit: mm)
UCB1000L
Mounting hole
M8 screw
4P
73
3P
120
14
45
70
70
210
14
5
70
280
7
80
16
45
70
115
200
14
45
70
[Terminal part]
25
54
205
25
115
249
[Panel cut-out]
4P
4P
3P
3P
99
61.5
338
78.5
37.5
13
73
16 36 21
36 20
310
516
370
[Connection conductor]
44
M8 tapped hole
70
Trip alarm
switch
Shunt
trip
Under
voltage trip
Left
Right
Handle
[ Front ]
U-Series
Protection characteristics
Hour
4
3
630-1250A
Ir
Ig
Characteristics
Ip
1
50
40
30
Minute
20
8
6
5
4
3
Ii
1
50
40
30
Tripping time
UCB1250L
20
12
10
8
6
5
4
3
Second
UCD1250S
Characteristics are
not applicable.
1
0.8
0.6
0.5
0.4
0.3
0.2
0.1
0.08
0.06
0.05
0.04
0.03
3000
2000
2500
500
600
700
800
900
1000
1100
1200
1300
1500
400
200
250
300
125
150
50
80
90
100
40
30
10
20
In %
20%
15%
50ms
20ms
20%
15%
50ms
20ms
10%
-The default values are underlined. Please check and adjust the
setting condition of each characteristic before use.
-1) I2t characteristic can be ON or OFF by adjusting the [tsd] knob.
-2) GFT protection is option.
0.02
0.01
0.008
0.006
0.005
Tolerance
Rated current
LTD setting [Ir] (A)
Isd
10
UCB1250S
Ir %
Current
Dimensions
: Center line
Direct mounting
(Unit: mm)
UCB1250S
Mounting hole
4P
M8 mounting screw
73
3P
30
14
[Connection conductor]
45
70
70
36 20
16
17 25
110
115
159
45
70
210
70
280
5
7
70
80
[Panel cut-out]
4P
3P
4P
3P
99
61.5
338
78.5
44
M8 tapped hole
158
70
25
54
37.5
13
14
516
310
[Terminal part]
16 36 21
73
370
45
25
Inhex bolt M10 L30
MCCB
Dimensions
: Center line
Direct mounting
(Unit: mm)
UCB1250L
Mounting hole
M8 mounting screw
4P
73
3P
120
14
[Connection conductor]
36 20
310
516
370
45
16
45
70
70
210
70
17
70
280
80
115
200
205
14
45
70
25
54
25
115
Inhex bolt M10 L30
249
[Panel cut-out]
4P
4P
3P
3P
99
61.5
338
78.5
37.5
13
73
16 36 21
[Terminal part]
44
M8 tapped hole
70
Trip alarm
switch
Shunt
trip
Under
voltage trip
Left
Right
Handle
[ Front ]
U-Series
Protection characteristics
640-1600A
Characteristics
UCB1600S
Tolerance
Second
Tripping time
I2
Rated current
setting [I1] (A)
Instantaneous
INST current setting
[I2] (A)
I1 x 200-300-400-500-600700-800-1000%
10%
-The default values are underlined. Please check and adjust the
setting condition of each characteristic before use.
20%
100
200
2000
3000
Current
Dimensions
: Center line
(Unit: mm)
Direct mounting
13
338
394
110
477
371
570
152
11
51
100
32
15
22
Trip
button
70
151
170
215
[Terminal cover]
[Extension handle]
210
151
297
210
50
109
40
e
R25
36
45 25
60
70
160
70
U-Series
Tripping time
Max.
Max.
Current
375
250
450
300
480
320
525
350
600
400
675
450
750
500
Current
Min.
Min.
Inst. trip
current (A)
1250
1500
1600
1750
2000
2250
2500
Second
Second
125
150
160
175
200
225
250
126
160
200
250
Rated
current (A)
Tripping time
Tripping time
125-250A
Minute
630
800
1000
1250
63
80
100
125
Inst. trip
current (A)
Hour
Rated
current (A)
Minute
Hour
63-125A
Current
Current
Characteristic curves
are not applicable.
Second
UPD250S
162
UPD160S
Max.
Min.
UPD100S
UPB250X
UPB250L
UPB250H
UPB250S
Max.
Min.
UPB160X
UPB160L
UPB160H
UPB160S
400 80
500 100
UPB100X
Inst. trip
current (A)
40
50
UPB100L
Tripping time
UPB100H
30
32
40
50
60
64
Second
UPB100S
Rated
current (A)
Minute
150
160
200
250
300
320
40-50A
15
16
20
25
30
32
Inst. trip
current (A)
Rated
current (A)
Hour
15-30A
Minute
Hour
MCCB
Dimensions
: Center line
(Unit: mm)
Direct mounting
4P
140
35
35
35
112
20 11
23
4P
3P
27.5
144
165
144
*A
144
165
146
[Panel cut-out]
75.5
3P
105
35
11 19
45
11 20
11
R5
M4 0.7
tapped hole
45
35
90
113
[Connection conductor]
[Terminal part]
35
128
71
86.5
35
30
8.5 9.5
9.5
9
(Max.)9
35
M4 tap O.7
23
23 (Max.)
24
10
24
t4
A
Plug-in mounting
[Mounting base]
41
24 5
109
35
4- 6 mounting hole
26.5
15
23
[Panel cut-out]
96
4-M5 tap
4- 6 tap
37
30
15
31
92.5
110
35
70
105
190
179
113
144
175
190
35
107
30
31
M8 bolt
70
M8 mounting screw
22.5
26
Trip alarm
switch
Shunt
trip
Under
voltage trip
Left
Right
Handle
[ Front ]
U-Series
Hour
4
3
2
50-250A
1
50
40
30
Minute
20
10
8
6
5
4
3
2
UPB100L
UPB100X
UPB160S
UPB160H
UPB160L
UPB160X
UPB250S
UPB250H
UPB250L
UPB250X
20
Tripping time
UPB100H
10
8
6
5
4
3
2
Isd = 2..... 10 x Ir
1
0.8
0.6
0.5
0.4
0.3
0.2
Second
UPB100S
1
50
40
30
0.1
0.8
0.6
0.5
0.4
0.3
0.2
Ii = 11 x In
0.01
0.8
0.6
0.5
50
70
100
150
200
300
400 500
700
1000
1500
2000
Ir %
Current
Protection characteristics
LTD
STD
PTA
UPB160
UPB250
125
160
250
50, 55, 63, 70, 63, 70, 80, 90, 100, 110, 125,
80, 90, 100,
100, 110, 125, 140, 160, 175,
115, 125
140, 160
200, 225, 250
Ir x NON-200-300-400-500-600-700-800-900-
[Isd] (A)
Time delay setting [tsd]
INST
UPB100
Instantaneous current
20%
1000%
0.05-0.1-0.2-0.3 sec. at definite time-limit
50ms
section
20ms
In x 1100%
20%
Ir x 90%
10%
Tolerance
-The default values are underlined. Please check and adjust the setting condition of each characteristic before use.
164
30000
MCCB
Dimensions
: Center line
(Unit: mm)
Direct mounting
4P
140
35
35
35
112
20 11
23
4P
3P
27.5
144
165
144
*A
144
165
146
[Panel cut-out]
75.5
3P
105
35
11 19
45
11 20
11
R5
M4 0.7
tapped hole
45
35
90
113
[Connection conductor]
[Terminal part]
35
128
71
86.5
35
30
8.5 9.5
9.5
9
(Max.)9
35
M4 tap O.7
23
23 (Max.)
24
10
24
t4
A
Plug-in mounting
[Mounting base]
41
24 5
109
35
4- 6 mounting hole
26.5
15
23
[Panel cut-out]
96
4-M5 tap
31
4- 6 tap
37
30
15
92.5
110
35
70
105
190
179
113
144
175
190
35
107
30
31
M8 bolt
70
M8 mounting screw
22.5
26
Trip alarm
switch
Shunt
trip
Under
voltage trip
Left
Right
Handle
[ Front ]
U-Series
Protection characteristics
Hour
4
3
200-630A
Ir
Ig
Characteristics
1
50
40
30
UPB630
630
20
Minute
UPB400
400
Ip
Isd
10
8
6
5
4
3
LTD
Rated current
setting [Ir] (A)
Ii
Tolerance
UPB400L
UPB400X
UPB630S
UPB630H
UPB630L
UPB630X
Tripping time
UPB400H
20
12
10
8
6
5
4
3
2
Second
UPB400S
50
40
30
1
0.8
0.6
0.5
0.4
0.3
0.2
for I t "OFF"
0.1
0.08
0.06
0.05
0.04
0.03
Ir %
Current
Dimensions
: Center line
Direct mounting
50ms
20ms
In x NON-300-600-8001000-1100%
20%
In x NON-20-30-40%
15%
0.1-0.2-0.3-0.4-0.8 sec. at
definite time-limit section
50ms
20ms
Ir x 90%
10%
(Unit: mm)
15
12.5
39.5
16
47
M10 screw
201
161.5
112.5
142.5
255
98.5
128.5
16
16 16
47
185
27.5
24
27.5
12.5 15
24
15
140
3P
16
52.5
13
60
150
60
210
30
M5 mounting screw
15
60
16
47
16
47
60
15
30
13
15
16
81
10
60
119.5
159.5
[Panel cut-out]
4P
4P
3P
3P
[Connection conductor]
63
30
(Max.)
14 16
15 (Max.)
113
45
[Terminal part]
10.5
100
130
166
15%
UPB400, UPD400S
4P
M5 tapped hole
20%
-The default values are underlined. Please check and adjust the
setting condition of each characteristic before use.
-1) I2t characteristic can be ON or OFF by adjusting the [tsd] knob.
-2) GFT protection is option.
3000
2000
2500
500
600
700
800
900
1000
1100
1200
1300
1500
400
250
In %
300
125
150
200
50
80
90
100
Characteristics are
not applicable.
40
0.01
0.008
0.006
0.005
30
0.02
UPD630S
10
20
UPD400S
34
33.5
Inhex bolt M10 L30
MCCB
Dimensions
: Center line
Direct mounting
(Unit: mm)
UPB630, UPD630S
[with terminal bus bar*option]
85.5
55
102.5
112.5
255
142.5
16
98.5
128.5
41.5
M10 screw
115.5
12.5
24
185
27.5
24
16 16 15
47
3P
27.5
12.5 15
16 15
47
4P
140
30
16
13
60
150
52.5
60
30
M5 mounting screw
15
60
15
16
47
16 16
47
60
15
13
81
10
119.5
159.5
60
210
[Panel cut-out]
4P
3P
4P
[Connection conductor]
[Terminal part]
14 16
113
41.5
130
M5 tapped hole 45
15 (Max.)
100
10.5
33.5
Inhex bolt M10 L30
34
30 (Max.)
63
Plug-in mounting
[Mounting base]
[Panel cut-out]
144
45
22.5
130
57.7
33.5 5
27
155
M10
mounting screw
119.5
124.5
164.5
45
90
140
39 52.5
22.5
11.5
18.5
188
227
270
298
298
274
4-M5 tap
37.5 30 37.5
180
90
27
Trip alarm
switch
Shunt
trip
Under
voltage trip
Left
Right
Handle
[ Front ]
U-Series
125A
Minute
Max.
Current
10
11
12
13
2.5
15
17.5
20
22.5
25
27.5
30
32.5
3.2
19.2
22.4
25.6
28.8
32
35.2
38.4
41.6
6.3
37.8
44.1
50.4
56.7
63
69.3
75.6
81.9
12.5
75
87.5
100
112.5
125
137.5
150
162.5
20
120
140
160
180
200
220
240
260
32
192
224
256
288
320
352
384
416
50
300
350
400
450
500
550
600
650
63
378
441
504
567
630
693
756
819
80
480
560
640
720
800
880
960
1040
100
600
700
800
900
1000
1100
1200
1300
UPB250
Rated
current
(A)
10
125
625
750
875
1000
1125
1250
150
750
900
1050
1200
1350
1500
175
875
1050
1225
1400
1575
1750
200
1000
1200
1400
1600
1800
2000
225
1125
1350
1575
1800
2025
2250
Current
168
Max.
Min.
Second
Min.
Instantaneous trip
current (500-1000%)
Tripping time
Tripping time
UPB250L
UPB250H
Second
UPB100L
Instantaneous trip
current (600-1300%)
Minute
UPB100H
250A
Hour
Hour
MCCB
Dimensions
: Center line
(Unit: mm)
Direct mounting
4P
140
35
35
35
112
20 11
23
4P
3P
27.5
144
165
144
*A
144
165
146
[Panel cut-out]
75.5
3P
105
35
11 19
45
11 20
11
R5
M4 0.7
tapped hole
45
35
90
113
[Connection conductor]
[Terminal part]
35
128
71
86.5
35
30
Dimension A
8.5 9.5
9.5
9
(Max.)9
35
M4 tap O.7
23 (Max.)
24
10
23
24
t4
A
Plug-in mounting
[Mounting base]
41
24 5
109
35
4- 6 mounting hole
26.5
15
23
[Panel cut-out]
96
4-M5 tap
31
4- 6 tap
37
30
15
92.5
110
35
70
105
190
179
113
144
175
190
35
107
30
31
M8 bolt
70
M8 mounting screw
22.5
26
Trip alarm
switch
Shunt
trip
Under
voltage trip
Left
Right
Handle
[ Front ]
U-Series
4
3
1
50
10
30
Rated
current (A)
Inst. trip
current (A)
15
20
30
150 30
200 40
300 60
10
8
6
5
4
3
2
1
0.8
0.6
0.5
0.4
0.3
0.2
Hour
4
3
Rated
current (A)
Inst. trip
current (A)
60
75
100
600 120
750 150
1000 200
Minute
10
8
6
5
4
3
2
Tripping time
1
50
40
30
20
10
8
6
5
4
3
Second
2
1
0.8
0.6
0.5
0.4
0.3
Min.
0.1
0.08
0.06
0.05
0.04
0.03
Max.
Current
170
Under
voltage trip
5000
6000
7000
8000
4000
3000
2500
2000
1500
1200
700
800
900
1000
600
500
400
300
250
200
150
125
100
105
Handle
5000
4000
6000
7000
8000
3000
2500
2000
110
105
100
95
90
85
80
5
10
15
20
25
30
35
40
0.02
0.01
0.008
0.006
0.005
[ Front ]
115
0.2
Right
1500
60-100A
20
Left
1200
Current
1
50
10
30
700
800
900
1000
Current
Shunt
trip
Max.
500
300
250
200
100
105
5000
4000
6000
7000
8000
3000
2500
2000
1500
1200
700
800
900
1000
500
400
600
300
250
200
150
0.02
0.01
0.008
0.006
0.005
125
0.02
0.01
0.008
0.006
0.005
100
105
Min.
0.1
0.08
0.06
0.05
0.04
0.03
400
Max.
150
Min.
600
0.2
Trip alarm
switch
400 80
500 100
10
8
6
5
4
3
2
10
8
6
5
4
3
Second
2
1
0.8
0.6
0.5
0.4
0.3
0.1
0.08
0.06
0.05
0.04
0.03
No.
of
Auxiliary
poles switch
Inst. trip
current (A)
40
50
1
50
40
30
20
Tripping time
Tripping time
HBL103UQ
Rated
current (A)
20
1
50
40
30
20
Second
HBL103U
40-50A
2
1
50
10
30
125
Minute
20
10
8
6
5
4
3
2
4
3
Hour
15-30A
Minute
Hour
45
50
55
60
MCCB
Dimensions
: Center line
(Unit: mm)
Direct mounting
112
35
Terminal cover
M8 bolt
Dimension A
144
165
146
t4
[Connection conductor]
[Terminal part]
23 (Max.)
10
86.5
Terminal cover
[Panel cut-out]
3P
3P
24
9.5
8.5 9.5
0.7
tap
M4
71
70
105
9 (Max.)
24
27.5
144
75.5
3P
R5
35
M4 0.7
tapped hole
30
U-Series
100A
Hour
2
1
30
20
14
10
Minute
6
4
2
1
Tripping time
30
20
HBL103UM
Instantaneous trip
current (600-1300%)
10
5
HBL103UMQ
Min.
Max.
Second
1
0.5
0.2
0.1
0.05
0.04
0.03
0.02
7000
5000
3000
2000
400
600
700
800
900
100
1100
1200
1300
300
200
125
100
0.01
Current
Rated
current
(A)
10
11
12
13
2.5
15
17.5
20
22.5
25
27.5
30
32.5
3.2
19.2
22.4
25.6
28.8
32
35.2
38.4
41.6
6.3
37.8
44.1
50.4
56.7
63
69.3
75.6
81.9
12.5
75
87.5
100
112.5
125
137.5
150
162.5
20
120
140
160
180
200
220
240
260
32
192
224
256
288
320
352
384
416
50
300
350
400
450
500
550
600
650
63
378
441
504
567
630
693
756
819
80
480
560
640
720
800
880
960
1040
100
600
700
800
900
1000
1100
1200
1300
Trip alarm
switch
Left
Right
Handle
[ Front ]
172
Shunt
trip
Under
voltage trip
MCCB
Dimensions
: Center line
(Unit: mm)
Direct mounting
112
35
Terminal cover
M8 bolt
Dimension A
144
165
146
t4
[Connection conductor]
[Terminal part]
23 (Max.)
10
86.5
Terminal cover
[Panel cut-out]
3P
3P
24
9.5
8.5 9.5
0.7
tap
M4
71
70
105
9 (Max.)
24
27.5
144
75.5
3P
R5
35
M4 0.7
tapped hole
30
U-Series
25
1250
150
1500
20
175
1750
200
2000
225
2250
+375
-250
+450
-300
+525
-350
+600
-400
+675
-450
5000
Inst. trip
current (A)
1
50
40
30
4000
Rated
current (A)
55
60
10
8
6
5
4
3
2
10
8
6
5
4
3
2
Second
HBL203UQ
125-225A
1
50
40
30
20
Tripping time
HBL203U
4
3
3000
Minute
Hour
1
0.8
0.6
0.5
0.4
0.3
Min.
Max.
0.2
0.1
0.08
0.06
0.05
0.04
0.03
Current
115
110
105
100
95
90
85
80
0
10
15
20
25
30
35
40
Trip alarm
switch
Left
Right
Handle
[ Front ]
174
Shunt
trip
Under
voltage trip
45
50
8000
7000
6000
2500
1500
1200
700
800
900
1000
500
600
400
300
250
200
150
125
100
105
0.01
0.008
0.006
0.005
2000
0.02
MCCB
Dimensions
: Center line
(Unit: mm)
Direct mounting
112
35
Terminal cover
M8 bolt
Dimension A
144
165
146
t4
[Connection conductor]
[Terminal part]
23 (Max.)
10
86.5
Terminal cover
[Panel cut-out]
3P
3P
24
9.5
8.5 9.5
0.7
tap
M4
71
70
105
9 (Max.)
24
27.5
144
75.5
3P
R5
35
M4 0.7
tapped hole
30
U-Series
Hour
225A
2
1
Minute
30
20
14
10
6
4
2
1
Tripping time
30
20
HBL203UM
Instantaneous trip
current (500-1000%)
10
5
HBL203UMQ
Min.
Max.
Second
1
0.5
0.2
0.1
0.05
0.04
0.03
0.02
7000
5000
3000
2000
1500
500
600
700
800
900
1000
400
300
200
100
125
0.01
Current
Rated
current
(A)
125
625
750
875
1000
1125
1250
150
750
900
1050
1200
1350
1500
Left
Right
Handle
[ Front ]
176
Shunt
trip
10
875
1050
1225
1400
1575
1750
200
1000
1200
1400
1600
1800
2000
225
1125
1350
1575
1800
2025
2250
Trip alarm
switch
175
No.
of
Auxiliary
poles switch
Under
voltage trip
MCCB
Dimensions
: Center line
(Unit: mm)
Direct mounting
112
35
Terminal cover
M8 bolt
Dimension A
144
165
146
t4
[Connection conductor]
[Terminal part]
23 (Max.)
10
86.5
Terminal cover
[Panel cut-out]
3P
3P
24
9.5
8.5 9.5
0.7
tap
M4
71
70
105
9 (Max.)
24
27.5
144
75.5
3P
R5
35
M4 0.7
tapped hole
30
U-Series
15-30A
120
Minute
60
10
1
40
Tripping time
UMB30R
Max.
20
10
6
4
2
Second
Min.
1
150
100
50
10
20
30
40
50
Instantaneous trip
(800-2000%)
Max. total
breaking time
0.02
0.01
1.5 2
3 4 5 6 7 8 10
15 20 30 40 50
100
Current
Dimensions
: Center line
(Unit: mm)
Direct mounting
33
42
[Terminal part]
20
6.8
11.3
8.2
M5 11
8.2
Load side
57
[Panel cut-out]
59
38
35
178
11.3
6.8
68
70
56
36
Line side
14.5
MCCB
15-50A
Minute
Tripping time
UMB30S
UMB50S
Max.
Second
Min.
Instantaneous trip
(800-2000%)
Max. total
breaking time
Current
Dimensions
: Center line
(Unit: mm)
Direct mounting
IEC 35mm
DIN-rail
80
35
M5 12
20.5
70
50
68
80
20.5
[Terminal part]
10.5
5
Line side 32
Load side 30
10.5
60
66
67.5
76
19
35
[Panel cut-out]
M4 or 5
70
52
R2
U-Series
15-50A
Minute
Tripping time
UMB30H
Max.
UMB50H
Second
Min.
Instantaneous trip
(800-1200%)
Max. total
breaking time
Current
Dimensions
: Center line
Direct mounting
M5 12
80
68
35
18.5
[Terminal part]
50
70
47.5
IEC 35mm
DIN-rail
10.5
5
Line side 32
Load side 30
10.5
60
19
66
35
67.5
76
[Panel cut-out]
35
M4 or 5
180
70
52
R2
(Unit: mm)
MCCB
3-30A
Max.
Tripping time
Second
UDB30S
UDB30H
UDB50S
Min.
Instantaneous trip
(800-1200%)
Minute
Max. total
breaking time
UDB50H
UDB100S
UDB100H
Current
40-100A
Max.
Tripping time
Second
Min.
Instantaneous trip
(800-1200%)
Minute
Max. total
breaking time
Current
Auxiliary
switch
Trip alarm
switch
Shunt
trip
Left
Right
- In case of 2P, all signal accessories shall be installed in left side of breaker.
- SHT is not applicable to 2P.
Handle
[ Front ]
U-Series
: Center line
Direct mounting
UDB30, UDB50
IEC 35mm
DIN-rail
35
97.5
64
80
96
50
9 25
64
80
96
50
9 25
Mounting hole
13
Trip button
4.5
Trip button
25
50
50
53
60
65
80
50
75
2P
3P
[Terminal part]
M5 12
Line side 32
Load side 30
[Panel cut-out]
M4 or 5
74
25
M4 or 5
49
R2
52
52
80-84
R2
2P
Direct mounting
3P
2P
3P
UDB100
Mounting hole
IEC 35mm
DIN-rail
M8 14
88
35
97.5
64
80
50
9 25
[Terminal part]
4.5
Trip button
[Panel cut-out]
M4 or 5
74
Line side 32
Load side 30
17
50
53
60
65
80
50
75
25
182
80-84
52
R2
(Unit: mm)
MCCB
15-30A
120
Minute
60
10
1
40
Tripping time
UMG30R
Max.
20
10
6
4
2
Second
Min.
1
150
100
50
10
20
30
40
50
0.2
0.1
Instantaneous trip
(800-2000%)
Max. total
breaking time
0.02
0.01
1.5 2
3 4 5 6 7 8 10
15 20 30 40 50
100
Current
Dimensions
: Center line
(Unit: mm)
Direct mounting
33
42
20
[Terminal part]
6.8
Line side
68
11.3
6.8
M5 11
14.5
8.2
Load side
57
[Panel cut-out]
38
59
70
56
36
11.3
8.2
35
U-Series
15-50A
Minute
Tripping time
UMG30S
Max.
Second
UMG50S
Min.
Instantaneous trip
(800-2000%)
Max. total
breaking time
Current
Dimensions
: Center line
Direct mounting
IEC 35mm
DIN-rail
[Terminal part]
80
35
6 6
20.5
70
50
68
80
20.5
M5 12
10.5
5
Line side 32
Load side 30
10.5
60
66
67.5
76
19
35
Earth leakage
test button
[Panel cut-out]
M4 or 5
184
70
52
R2
(Unit: mm)
MCCB
15-50A
Minute
Tripping time
UMG30H
UMG50H
Max.
Second
Min.
Instantaneous trip
(800-1200%)
Max. total
breaking time
Current
Dimensions
: Center line
(Unit: mm)
Direct mounting
IEC 35mm
DIN-rail
Earth leakage
test button
80
68
35
18.5
M5 12
50
70
47.5
[Terminal part]
6 6
10.5
5
Line side 32
Load side 30
10.5
60
Trip button
19
66
35
67.5
76
[Panel cut-out]
M4 or 5
70
52
R2
U-Series
3-30A
Max.
Tripping time
Second
UDG30S
UDG30H
UDG50S
Min.
Instantaneous trip
(800-1200%)
Minute
Max. total
breaking time
UDG50H
UDG100S
UDG100H
Current
40-100A
Max.
Tripping time
Second
Min.
Instantaneous trip
(800-1200%)
Max. total
breaking time
Current
Trip alarm
switch
3
Right
Left
Handle
[ Front ]
186
No.
of
Auxiliary
poles switch
Minute
In case of 2P, all signal accessories shall be installed in left side of breaker.
MCCB
Dimensions
: Center line
(Unit: mm)
UGD30, UGD50
35
97.5
50
9 25
19.1
13
Trip button
IEC 35mm
DIN-rail
Earth leakage
indicator
Mounting hole
64
80
96
50
9 25
Earth leakage
indicator
64
80
96
Direct mounting
Earth leakage
test button
Trip button
25
50
4.5
Earth leakage
test button
50
53
60
65
80
50
75
2P
3P
[Terminal part]
M5 12
17
[Panel cut-out]
74
49
M4 or 5
80-84
52
52
2P
3P
80-84
R2
R2
Direct mounting
25
M4 or 5
2P
3P
UGD100
Earth leakage
indicator
Mounting hole
IEC 35mm
DIN-rail
[Terminal part]
88
35
97.5
64
80
96
50
9 25
M8 14
19.1
4.5
Earth leakage
test button
Line side 32
Load side 30
17
50
53
60
65
80
50
75
[Panel cut-out]
M4 or 5
74
25
80-84
R2
52
Trip button
Accessories
| Signal Accessories | Operating Accessories | Mounting Accessories |
| Terminal Accessories | Portable Test Equipment |
U-Series
Accessories
| Signal accessories |
auxiliary switch
trip alarm switch
shunt trip
under voltage trip
| Operating accessories |
operating handle (surface and extended type)
motor operator
mechanical interlock
padlock plate
extension handle
| Mounting accessories |
DIN-rail adaptor
mounting base for plug-in mounting
| Terminal accessories |
terminal bus bar
cage terminal block
terminal cover
interpole barrier
The applicable accessories of each MCCB are not same as above. For exact application to each MCCB, please reter to next pages.
190
MCCB
U-Series
Signal Accessories
Signal accessories adopts cassette type assembly method, so they can be easily installed and removed.
Auxiliary
AUX
- Electrically indicates ON
and OFF status of breaker
Shunt trip
SHT
192
ALT
UVT
MCCB
Installation
3 pole
Wiring
2 pole
Trip alarm
switch
[ALT]
Limit switch for coil protecton
1)
Shunt trip
[SHT]
2)
Under voltage
trip [UVT]
- For detail installation to each MCCB model, please refer to Characteristic curves & Dimensions from page 138 to 187.
1) Common for AC200-480V. Applicable for SHT 10A H, SHT 10B H and SHT 20C H only.
2) The coil is continuously energized, so that limit switch is not required.
ON
OFF
TRIP
U-Series
Signal Accessories
| Auxiliary switch (AUX) and trip alarm switch (ALT) |
Applicable MCCB
UAB30C, UAB30R, UAB50C, UAB50R,
UAB60C, UAB60R, UAB100C / UAD50C
UAB50S, UAB50H, UAB100R, UAB100S
/ UAD50S, UAD100R
UCB50R, UCB100R, UCB100S / UCD100S
UCB250R, UCB250S, UCB250N / UCD250S
UCB50H, UCB50L, UCB100H, UCB100L,
UCB160H, UCB160L, UCB250H, UCB250L
/ UCD50H, UCD100H, UCD160H, UCD250H
UCB400R, UCB400S, UCB400H, UCB400L, UCB630R,
UCB630S, UCB630H, UCB630L, UCB800R, UCB800S,
UCB800H, UCB800L / UCD400S, UCD630S, UCD800S
UCB1000S, UCB1000L, UCB1250S, UCB1250L
/ UCD1000S, UCD1250S
UCB1600S
UPB100S, UPB100H, UPB100L, UPB100X, UPB160S,
UPB160H, UPB160L, UPB160X, UPB250S, UPB250H,
UPB250L, UPB250X / UPD100S, UPD160S, UPD250S
UPB400S, UPB400H, UPB400L, UPB400X, UPB630S,
UPB630H, UPB630L, UPB630X / UPD400S, UPD630S
HBL103U, HBL103UM, HBL203U, HBL203UM,
HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ1)
UDB30S, UDB30H, UDB50S, UDB50H, UDB100S,
UDB100H / UDG30S, UDG30H, UDG50S, UDG50H,
UDG100S, UDG100H
Specification
AUX 10A R1
AUX 10A R2
AUX 10UA R1
AUX 10UA L1
AUX 10B L1
AUX 20C L1
1C, right-hand-side
2C, right-hand-side
1C, right-hand-side
1C, left-hand-side
1C, left-hand-side
1C, left-hand-side
AUX 12FG L1
Order code
Specification
ALT 10A R1
1C, right-hand-side
ALT 10UA R1
ALT 10UA L1
ALT 10B L1
ALT 20C L1
1C, right-hand-side
1C, left-hand-side
1C, left-hand-side
1C, left-hand-side
1C, left-hand-side
ALT 12FG R1
1C, right-hand-side
AUX 12FG L2
2C, left-hand-side
ALT 12FG L1
1C, left-hand-side
AUX 46D R1
1C, right-hand-side
ALT 46D L1
1C, left-hand-side
AUX 80NE R1
AUX 80NE R2
AUX 80NE R3
AUX 160NE R1
AUX 160NE R2
1C, right-hand-side
2C, right-hand-side
3C, right-hand-side
1C, right-hand-side
2C, right-hand-side
ALT 80NE R1
1C, right-hand-side
AUX 12UP R1
1C, right-hand-side
ALT 12UP L1
1C, left-hand-side
AUX 46UP L1
1C, left-hand-side
ALT 46UP R1
1C, right-hand-side
AUX 12UP R1
1C, right-hand-side
ALT 12UP L1
1C, left-hand-side
1C, left-hand-side
AUX 10UD L1
AUX 10UD L1T2)
1) Signal accessories for HBL type shall be installed in breaker before ex-working.
Category
MCCB MB
1C, left-hand-side
for 2 pole
1C, left-hand-side
for 3 pole
194
SHT 12FG C
SHT 12FG F
SHT 12FG H
SHT 12FG B
SHT 12FG D
5.2A
2.2A
0.76A
0.4A
0.4A
0.4A
SHT 46D A
SHT 46D C
SHT 46D F
SHT 46D H
SHT 46D B
SHT 46D D
0.01A
0.01A
0.012A
0.011A
0.01A
0.01A
SHT 120NE A SHT 120NE C SHT 120NE F SHT 120NE H SHT 120NE B SHT 120NE D
2A
0.11A
0.24A
0.23A
0.23A
0.23A
SHT 160NE A SHT 160NE C SHT 160NE F SHT 160NE H SHT 160NE B1)
2A
1A
0.76A
0.4A
0.35A
SHT 12UP A
SHT 12UP C
SHT 12UP F
SHT 12UP H
SHT 12UP B
SHT 12UP D
0.023A
0.023A
0.023A
0.023A
0.023A
0.023A
SHT 46UP A
0.023A
SHT 12UP A
0.023A
SHT 10UD A
SHT 10UD AT3)
1.65A
SHT 46UP C
0.023A
SHT 12UP C
0.023A
SHT 10UD C
SHT 10UD CT3)
0.36A
SHT 46UP F
0.023A
SHT 12UP F
0.023A
SHT 10UD F
SHT 10UD FT3)
0.4A
SHT 46UP H
0.023A
SHT 12UP H
0.023A
SHT 10UD H
SHT 10UD HT3)
0.2A
SHT 46UP B
0.023A
SHT 12UP B
0.023A
SHT 10UD B
SHT 10UD BT3)
0.08A
SHT 46UP D
0.023A
SHT 12UP D
0.023A
SHT 10UD D
SHT 10UD DT3)
0.1A
- The permissible operating voltage: 85-110% of rated voltage for AC , 75-125% for DC.
1) SHT 160NE B is applicable for AC380V only.
2) Signal accessories for HBL type shall be installed in breaker before ex-working.
3) Terminal block type
Category
MCCB MB
MCCB
Applicable MCCB
DC24V
UVT 10A J
UVT 10A L
UVT 10A N
UVT 10A P
UVT 10A Q
UVT 10A R
UVT 10UA J
UVT 10UA L
UVT 10UA N
UVT 10UA P
UVT 10UA Q
UVT 10UA R
UVT 10B J
UVT 20C J
UVT 10B L
UVT 20C L
UVT 10B N
UVT 20C N
UVT 10B P
UVT 20C P
UVT 10B Q
UVT 20C Q
UVT 10B R
UVT 20C R
UVT 12FG J
UVT 12FG L
UVT 12FG N
UVT 12FG P
UVT 12FG Q
UVT 12FG R
UVT 46D J
UVT 46D L
UVT 46D N
UVT 46D P
UVT 46D Q
UVT 46D R
Category
MCCB MB
UVT 120NE J UVT 120NE L UVT 120NE N UVT 120NE P UVT 120NE Q
-
UVT 120NE R
UVT 12UP J
UVT 12UP L
UVT 12UP N
UVT 12UP P
UVT 12UP Q
UVT 12UP R
UVT 46UP J
UVT 46UP L
UVT 46UP N
UVT 46UP P
UVT 46UP Q
UVT 46UP R
UVT 12UP J
UVT 12UP L
UVT 12UP N
UVT 12UP P
UVT 12UP Q
UVT 12UP R
- The permissible operating voltage: 85-110% of rated voltage for AC, 85~125% for DC. The tripping voltage: 20-70% of rated voltage.
- Be sure not to use UVT for the electrical interlock system.
Reset is possible without power.
1) UVT 160NE Q is applicable for AC380V only, and UVT 160NE R is applicable for AC440V only.
2) Signal accessories for HBL type shall be installed in breaker before ex-working.
UVT controller is supplied as standard for UVT 10A, UVT 10UA, UVT 10B, UVT 20C, UVT 12FG, UVT 46D J, UVT 12UP and UVT 46UP type.
Fixing hole
(R/H M4 X L11 + P/W + S/W)
U2
88
100
16 15 18 15 16
8
16
ON
16.5
MCCB
U1
UC2 (-)
22
UC1 (+)
OFF
63
56
45
UVT controller
Supportor
[ Wiring ]
Terminal U1 an U2 are connected by the cable of vw-1, 22AWG (0.324
Different cables are available on request.
[ Dimensions ]
700 ).
U-Series
Operating Accessories
Operating handle
TFG, TFH
Motor operator
MOT
PLD
196
MIF
Padlock plate
Mechanical interlock
Extension handle
THA
MCCB
S type
L type
Right1)
Left1)
Upper1)
Left1)
Upper1)
power supply power supply power supply power supply power supply
type
type
type
type
type
S type
L type
TFG 10AL L4
TFH 10AS
TFH 10AL
TFG 10UAS U4 TFG 10UAS R4 TFG 10UAS L4 TFG 10UAL U4 TFG 10UAL L4
TFH 10UAS
TFH 10UAL
TFG 10BS U4 TFG 10BS R4 TFG 10BS L4 TFG 10BL U4 TFG 10BL L4
TFG 20CS U4 TFG 20CS R4 TFG 20CS L4 TFG 20CL U4 TFG 20CL L4
TFH 10BS
TFH 20CS
TFH 10BL
TFH 20CL
TFG 10UFS U4 TFG 10UFS R4 TFG 10UFS L4 TFG 10UFL U4 TFG 10UFL L4 TFH 10UFS
TFH 10UFL
TFG 20UGS U4 TFG 20UGS R4 TFG 20UGS L4 TFG 20UGL U4 TFG 20UGL L4
TFH 20UGS
TFH 20UGL
TFH 46DS
TFH 160NE
TFG 12UPS U4 TFG 12UPS R4 TFG 12UPS L4 TFG 12UPL U4 TFG 12UPL L4
TFH 12UPS
TFH 12UPL
TFH 46UPS
- In case of surface type (TFG), there are three types for diverse panel door-lock application, above mentioned codes are standard type. For detail, please refer to following explanation.
1) Upper, right and left indicates the power supply direction of MCCB.
MCCB
MCCB
MCCB
Panel door-lock
Surface type (TFG) operating handles offer four options in panel door-lock application.
OFF OPEN type: Panel door opens when operating handle is in OFF position. Indicating code (last digit of full order code) is
1. ex. TFG 10AS U1
OFF OPEN type with reverse interlock: Panel door opens when operating handle is in OFF position. Reverse interlock keeps
MCCB not to be "ON" when panel door opens. This is standard type for 400-800AF MCCB and indicating code (last digit of
full order code) is 2. ex.TFG 46DS U2
RESET OPEN type: Panel door opens when operating handle is in RESET position. Indicating code (last digit of full order
code) is 3. ex.TFG 10AS U3
RESET OPEN type with reverse interlock: Panel door opens when operating handle is in RESET position. Reverse interlock
keeps MCCB not to be ON when panel door opens. This is standard type for 30-250AF MCCB and indicating code (last digit
of full order code) is 4. ex. TFG 46DS U4
When panel door is required to open in ON position of operating handle, please turn the RELEASE knob to
indicated direction and open the panel door.
For more operating function, please refer to following pages.
Molded Case Circuit Breaker_ 197
U-Series
Operating Accessories
Operation
Operating direction
Turn the handle in a clockwise direction for ON.
Handle position shall be same with MCCB position (ON, OFF, TRIP) before closing the panel door.
Fig.1
Fig.2
Fig.3
Fig.4
Fig.5
Trip button
[ S type ]
Fig.1
Fig.2
Fig.3
Fig.4
[ L type ]
ON, OFF and TRIP are not marked on real products.
198
Fig.5
MCCB
Line side
59
37
44
59
MCCB center line
37
44
59
Line side
59
Panel door
Line side
59
37
4-
59
A
8
Order code
Applicable MCCB
UAB30C, UAB30R, UAB50C, UAB50R,
UAB60C, UAB60R, UAB100C / UAD50C
UAB50S, UAB50H, UAB100R, UAB100S
/ UAD50S, UAD100R
UCB50R, UCB100R, UCB100S / UCD100S
UCB250R, UCB250S, UCB250N / UCD250S
UCB50H, UCB50L, UCB100H, UCB100L
/ UCD50H, UCD100H
UCB160H, UCB160L, UCB250H, UCB250L
/ UCD160H, UCD250H
UPB100S, UPB100H, UPB100L, UPB100X, UPB160S,
UPB160H, UPB160L, UPB160X, UPB250S, UPB250H,
UPB250L, UPB250X / UPD100S, UPD160S, UPD250S
Upper power
supply type
Right power
supply type
Dimensions (mm)
Left power
supply type
Category
A
TFG 10AS U4
TFG 10AS R4
TFG 10AS L4
43
56
TFG 10UAS U4
TFG 10UAS R4
TFG 10UAS L4
43
56
TFG 10BS U4
TFG 20CS U4
TFG 10BS R4
TFG 20CS R4
TFG 10BS L4
TFG 20CS L4
9
9
47
47
56
56
TFG 10UFS U4
TFG 10UFS R4
TFG 10UFS L4
47
56
TFG 20UGS U4
TFG 20UGS R4
TFG 20UGS L4
47
56
TFG 12UPS U4
TFG 12UPS R4
TFG 12UPS L4
16.25
41
87
MCCB
MB
U-Series
Operating Accessories
30-250AF L type
[ Upper power supply type ]
Panel door
B
1.2-3.2
4-8
50
55
55
60
88
100
88
100
25
4-M4 bolt hole
1.2-3.2
88
100
25
88
100
4-8
50
60
55
55
Dimensions (mm)
Order code
Applicable MCCB
UAB30C, UAB30R, UAB50C, UAB50R,
UAB60C, UAB60R, UAB100C / UAD50C
UAB50S, UAB50H, UAB100R, UAB100S
/ UAD50S, UAD100R
UCB50R, UCB100R, UCB100S / UCD100S
UCB250R, UCB250S, UCB250N / UCD250S
UCB50H, UCB50L, UCB100H, UCB100L
/ UCD50H, UCD100H
UCB160H, UCB160L, UCB250H, UCB250L
/ UCD160H, UCD250H
UPB100S, UPB100H, UPB100L, UPB100X,
UPB160S, UPB160H, UPB160L, UPB160X,
UPB250S, UPB250H, UPB250L, UPB250X
/ UPD100S, UPD160S, UPD250S
200
Upper power
supply type
Left power
supply type
Category
A
TFG 10AL U4
TFG 10AL L4
106-111
TFG 10UAL U4
TFG 10UAL L4
106-111
TFG 10BL U4
TFG 20CL U4
TFG 10BL L4
TFG 20CL L4
9
9
111-116
111-116
TFG 10UFL U4
TFG 10UFL L4
111-116
TFG 20UGL U4
TFG 20UGL L4
111-116
TFG 12UPL U4
TFG 12UPL L4
14.5
136-140
MCCB
MB
MCCB
400-630AF S type
[ Upper power supply type ]
Handle center line
5
4-
Line side
100
100
10
5
100
Panel door
55
5~10
55
Panel door
15
10
5
Line side
100
4-
100
100
MCCB center line
5~10
55
Line side
4-
15
100
10
5
100
Panel door
100
MCCB center line
5~10
Dimensions (mm)
Order code
Applicable MCCB
Upper power
supply type
Category
Right power
supply type
Left power
supply type
TFG 46DS R2
TFG 46DS L2
222
TFG 46DS U2
MB
TFG 46UPS U2
TFG 46UPS R2
TFG 46UPS L2
13
234
/ UPD400S, UPD630S
U-Series
Operating Accessories
Dimensions and standard order code / Extended type (TFH)
30-250AF S type
37
4-
Panel door
227
59
59
15
15
247
Applicable MCCB
38
Dimensions (mm)
Order code
Category
A
TFH 10AS
384-479
43
56
TFH 10UAS
384-479
43
56
TFH 10BS
388-383
47
56
TFH 20CS
388-383
47
56
TFH 10UFS
388-383
47
56
TFH 20UGS
388-383
47
56
TFH 12UPS
419-414
41
87
202
MCCB
MB
MCCB
30-250AF L type
[ Upper power supply ]
B
Panel door
C
1.2-3.2
50
19
80
77
A
0
R1
80
MCCBcenter line
D
Panel door
B
1.2-3.2
19
80
77
0
R1
77
A
80
Handle center line
MCCBcenter line
Applicable MCCB
Dimensions (mm)
Order code
Category
A
TFH 10AL
TFH 10UAL
TFH 10BL
TFH 20CL
TFH 10UFL
TFH 20UGL
5
5
9
9
9
9
210-360
210-360
210-360
210-360
210-360
210-360
160
160
164
164
164
164
106
106
110
110
110
110
TFH 12UPL
14.5
210-360
186
135
MCCB
MB
400-630AF S type
Panel door
250
125
10
5
100
4-
55
5-10
100
A
Applicable MCCB
Order code
Dimensions (mm)
A
TFH 46DS
428
TFH 46UPS
440
Category
MCCB
MB
U-Series
Operating Accessories
Dimensions and standard order code / Q-class (for nuclear power plant application)
Surface type (TFG)
[ Upper power supply type ]
Panel door
Max. 140 - Min. 136
35
Line
1.2-3.2
87.5
14.5
88
100
14.5
58.5
4- 8
88
100
5.5
C
D
4- 8
88
100
35
Line
88
58.5
87.5
100
73
73
5.5
C
D
14.5
Dimensions (mm)
Order code
Applicable MCCB
Upper power
supply type
Left power
supply type
Category
A
TFG 20U U4
TFG 20U L4
14.5
51.5
78
129.5
TFG 20UQ U4
TFG 20UQ L4
14.5
51.5
78
129.5
MCCB
204
MB
U-Series
Operating Accessories
| Motor operator (MOT) |
MOT-12NE
Applicable MCCB
Model
MOT-10A
Control
voltage (V)
DC24V
AC/DC110V
AC/DC220V
2.5
0.5
0.5
DC24V
AC/DC110V
AC/DC220V
DC24V
AC/DC110V
AC/DC220V
2.5
0.5
0.5
5.0
3.0
2.0
MOT-40D
DC24V
AC/DC110V
AC/DC220V
MOT-68E
MOT-68E
Dimensions (mm)
A
310
200
14
25,000
90
132
93
30
310
200
14
10,000
90
132
93
30
350
230
14
8,000
90
126
93
35
5.0
3.0
2.0
350
230
14
5,000
44
DC24V
AC/DC110V
AC/DC220V
5.0
3.0
2.0
500
350
35
5,000
70
MOT-80NE
DC24V
AC/DC110V
AC/DC220V
5.0
3.0
2.0
820
500
120
3,000
70
MOT-160NE
AC 220V
2.0
820
500
120
3,000
MOT-12UP
DC24V
AC/DC110V
AC/DC220V
5.0
3.0
2.0
700
420
35
10,000
45
DC24V
AC/DC110V
AC/DC220V
DC24V
AC/DC110V
AC/DC220V
5.0
3.0
2.0
5.0
3.0
2.0
700
420
35
5,000
45
700
420
35
10,000
45
MOT-10UA
MOT-10UB
MOT-10F
MOT-20C
MOT-20G
MOT-46NE
MOT-12UP
MCCB
A
D
MCCB
MCCB
C
Motor
operator
150
142
376
147
Handle
Motor
32 operator
97
Motor
operator
Motor
operator
[MOT-10/20/40/68/80/12/46]
206
210
122
[MOT-160NE]
MCCB
S3
1
Control power
Power
K4
K5
K4
P1
P2
S1
S2
S4
POWER
K4
Ue
K3
ON
OFF
K5
ON
K1
K1
ON circuit
S1
S2
K3
M : Motor
K3
K3
K1 : ON relay
K4
K2 : OFF relay
K5
K2
OFF
OFF circuit
5
K5
S1 : ON limit switch
S2 : OFF limit switch
S3 : Auto/Manual
K2
Order code
DC24V
AC/DC110V
AC/DC220V
Category
MCCB
MB
U-Series
Operating Accessories
| Mechanical interlock (MIF) |
Applicable MCCB
UAB30C, UAB30R, UAB50C, UAB50R,
Order code
2 pole
3 pole
4 pole
MIF 10A 3
MIF 10A 4
MIF 10UA 3
MIF 10AU 4
MIF 10UF 3
MIF 10UF 4
MIF 10UF 3
MIF 10UF 3
MIF 10UF 4
MIF 20UG 3
MIF 20UG 3
MIF 20UG 4
MIF 40D 3
MIF 40D 3
MIF 40D 4
Category
MIF 80E 3
MIF 80E 3
MIF 80E 4
MIF 12UP 3
MIF 12UP 4
MIF 46UP 3
MIF 46UP 4
MIF 12UP 3
MIF 12UP 4
/ UCD630S, UCD800S
UPB100S, UPB100H, UPB100L, UPB100X,
UPB160S, UPB160H, UPB160L, UPB160X,
UPB250S, UPB250H, UPB250L, UPB250X
/ UPD100S, UPD160S, UPD250S
UPB400S, UPB400H, UPB400L, UPB400X,
UPB630S, UPB630H, UPB630L, UPB630X
/ UPD400S, UPD630S
HBL103U, HBL103UM, HBL203U, HBL203UM,
HBL103UQ, HBL103UMQ, HBL203UQ, HBL203UMQ
208
MB
MCCB
Order code
Category
PLD 10UA
PLD 20UG
PLD 40D
MCCB
MB
PLD 120NE
/ UCD1000S, UCD1250S
UPB100S, UPB100H, UPB100L, UPB100X,
UPB160S, UPB160H, UPB160L, UPB160X,
UPB250S, UPB250H, UPB250L, UPB250X,
UPB400S, UPB400H, UPB400L, UPB400X,
UPB630S, UPB630H, UPB630L, UPB630X
PLD 12UP
Order code
Dimensions
(mm)
A
B
Category
THA 46D
42
40
THA 120NE
56
40
THA 160NE
60
50
THA 46UP
42
30
A
Mounting hole
UCB1600S
MCCB MB
/ UPD400S, UPD630S
U-Series
Mounting Accessories
DIN-rail adaptor
DRA
Mounting base
TDM
210
Order code
DRA 10UA
Category
MCCB
MB
MCCB
Conductor
Mounting base (TDM, TDF)
Circuit conductor
Mounting angle
The shape of mounting bases of each MCCB are not same as above. For exact appearances, please refer to "Characteristic Curves & Dimensions" from page 138-187.
Mounting base
Order
Required
code
quantity
TDM 10AP
TDM 10BP
TDM 20CF
1EA
TDM 5BA
2EA
TDM 12NEP
Contact Required
quantity
CBM 10AB 2
2C
1EA
CBM 10AB 3
3C
1EA
CBM 10AB 2
2C
1EA
CBM 10AB 3
3C
1EA
CBM 20C 2
2C
1EA
CBM 20C 5
5C
1EA
TYA 5/22)
TYA 5/52)
2C
5C
1EA
1EA
TYA 5/22)
2C
1EA
2EA
2EA
TDM 46NEP
Connection block
Order
code
1EA
TDM 4BA
TDM 12NEP
1)
TYA 5/52)
5C
1EA
CBM 26NE 6
6C
1EA
CBM 26NE 6
12C
2EA
CBM 26NE 6
6C
1EA
CBM 26NE 6
12C
2EA
CBM 26NE 6
6C
1EA
CBM 26NE 6
12C
2EA
1EA
1EA
1EA
Mounting base
Order
code
Required
quantity
Order
code
Required
quantity
CBM BARR
1EA
TDM 10AF
1EA
CBM BARR
1EA
TDM 10BF
1EA
TDM 20CF
1EA
TDM 4BA
1EA
TDM 5BA
1EA
TDM 12NEF
1EA
TDM 46NEF
1EA
TDM 12NEF
1EA
Category
MCCB
MB
U-Series
Mounting Accessories
TDF 10A
(Unit : mm)
[ Mounting base ]
[ Connection conductor ]
81
75
25
79
25
130
12.5
59
153.3
76.5
78.3
76.5
40.8
7.5
76.5
RH M6 screw+S/W+P/W
15 (Max:18)
[ Panel cut-out ]
2
25
25
76.8
9
RH M6 screw+S/W+P/W
SEC A-A
41
21
36
50
8.5
20
13.5
21.5
3
22
22
TDF 10B
(Unit : mm)
[ Mounting base ]
[ Connection conductor ]
92
89
172.3
2
30
30
97.3
155
75
75
86.3
75
39.3
7.5
58.5
15 (Max:18)
RH M6 screw+S/W+P/W
12.5
30
30
9
[ Panel cut-out ]
SEC A-A
41
36
8.5
20
13.5
21.8 21
5-M4 tapped hole
21.5
3
212
27
27
MCCB
Applicable MCCB
Order code
Required
quantity
1EA
2EA
2EA
1EA
2EA
1EA
1EA
1EA
2EA
2EA
1EA
2EA
1EA
1EA
1EA
1EA
1EA
1EA
1EA
1EA
1EA
1EA
1EA
1EA
1EA
1EA
1EA
1EA
Item
Mounting base unit
UAB50R, UAB50S,
UAB50H, UAB60R,
UAB100C,
UAB100R,
UAB100S
For
component
order
Mounting base
Branching conductor
Arc protection barrier
Connection plate
Double
mounting
For
component
order
Mounting base
Branching conductor
Arc protection barrier
Connection plate
Mounting base
UAB50R, UAB50S,
UAB50H, UAB60R,
UAB100C,
UAB100R,
UAB100S
5-63A
Branching
conductor
75-125A
Single
mounting
Mounting base
UCB50H, UCB50L,
UCB100R,
UCB100S,
UCB100H,
UCB100L
5-63A
Branching
conductor
75-125A
Mounting screw
M5xL12
Branching conductor
1S-PH
1S-PH10
M4xL8
M4xL8
M4xL8
M4xL8
M4xL8
M5xL12
M5xL12
M5xL12
M4xL8
M4xL8
M4xL8
2RT-PH
2RT-PH A
Connection plate
CONN-PL
CONN-PL A
22S-PH
22S-PH10
22S-PH A
22S-PH10 A
1R-PH
1R-PH10
1R-PH A
1R-PH10 A
1T-PH
1T-PH10
U-Series
Mounting Accessories
TDA 10AD / Double mounting
50
M5 tapped hole
for branching conductor
(22S-PH10 A)
Connection plate
(CONN-PL A)
43.7
18.5
Mounting angle
87
12.5
25
M4 nut+S/W+P/W
RH screw
M4xL18+S/W+P/W
M5 tapped hole
for branching conductor
(2RT-PH A)
25
4- 4.5 hole
Line
28
6
87
50
Line
235
37
RH screw
M4xL25+S/W+P/W
43.3
179.5
Connection plate
(ARC-PL A)
63
Line
360
235
63
Line
hole
nting
5 mou
28
M5 tapped hole
for branching conductor
(2RT-PH A)
15
12.5
50
25
22
80
80
21
M5 tapped hole
for branching conductor
(1T-PH, 1T-PH10)
50
M4 nut+S/W+P/W
12
Line
Mounting angle
33
RH M4xL10+S/W+P/W
Line
RH screw
M4xL30+S/W
24.2
80.8
162
115.3
87
18.5
27.3
18.5
M5 tapped hole
for branching conductor
(1R-PH A, 1R-PH10 A)
46.5
43.7
50
180
162
46.5
9
80.8
Line
43.3
4- 4.5 hole
50
15
25 21
80
214
22
80
25
MCCB
RH screw
M5xL20+S/W+P/W
27.518.5
8.5
30
4- 5.5 hole
Mounting angle
Line
50
Connection plate
(CONN-PL)
99
27.5
2
50
49.3
Line
M5 tapped hole for
branching conductor
(2RT-PH)
248.5
27.5
40
RH screw
M4xL25+S/W+P/W
49.7
193.5
Connection plate
(ARC-PL)
27.5
65.5
385
248.5
65.5
Line
Line
Mounting angle
8.5
18.5
60
15
26
94
24.5
81
20
30
50
M5 nut+S/W+P/W
12
RH screw
M5xL32+S/W+P/W
16
18.5
10
191
99
18.5
49.7
1.5
46
50
191
M5 tapped hole for
branching conductor
(1R-PH, 1R-PH10)
27
10
5.8 mounting hole
26 20
24.5
81
172.5
49.3
95.3
8.5
Line
94
86.8
M4 tapped hole
Line
46
Line
85.7
Mounting angle
30
5.5 hole
U-Series
Terminal Accessories
TBB
CTB
Rear barrier
REAR-BR
216
Terminal cover
TCF
Interpole barrier
TQQ
MCCB
Clamp screw
Size
Applicable MCCB
M5
M8
M10
M12
M12
M13
- UCB1600S
2 pole
(4EA/SET)
3 pole
(6EA/SET)
4 pole
(8EA/SET)
Mounting
Category
hole
TBB 20C 2
TBB 20C 3
TBB 20C 4
11
TBB 4S 2
TBB 4S 3
TBB 4S 4
13
TBB 6S 2
TBB 6S 3
TBB 6S 4
13
TBB 8S 2
TBB 8S 3
TBB 8S 4
13
[ 2 pole ]
MCCB
-
TBB 12NE 3
TBB 12NE 4
11
TBB 40NE 3
TBB 40NE 4
13
TBB 60NE 3
TBB 60NE 4
13
TBB 12NE 3
11
[ 3 pole ]
MB
[ 4 pole ]
U-Series
Terminal Accessories
CTB 10A
CTB 10B
CTB 20C
CTB 40D
CTB 46UP
CTB 80E
Wire
Order code
Applicable MCCB
Connection
Cable
connector
(EA)
S( )
L( )
Tightening
torque
kgf-
1 X 5.5-50
14
60
1 X 5.5-50
14
60
3EA/SET
4EA/SET
Wire size
Category
CTB 10B 3S
CTB 10B 4S
1 X 8-50
14
60
CTB 20C 3S
CTB 20C 4S
1 X 14-120
19
140
CTB 40D 3S
CTB 40D 4S
2 X 60-120
30-60
353
CTB 80E 3S
CTB 80E 4S
3 X 85-160
30-60
353
1 X 14-120
19
140
2 X 60-185
30-60
353
1 X 14-120
19
140
/ UCD50H, UCD100H
UCB250R, UCB250S, UCB250N / UCD250S
UCB160H, UCB160L, UCB250H, UCB250L
/ UCD160H, UCD250H
UCB400R, UCB400S, UCB400H, UCB400L
/ UCD400S
UCB630R, UCB630S, UCB630H, UCB630L,
UCB800R, UCB800S, UCB800H, UCB800L
/ UCD630S, UCD800S
UPB100S, UPB100H, UPB100L, UPB100X
/ UPD100S
UPB160S, UPB160H, UPB160L, UPB160X,
UPB250S, UPB250H, UPB250L, UPB250X
/ UPD160S, UPD250S
UPB400S, UPB400H, UPB400L, UPB400X
/ UPD400S
UPB630S, UPB630H, UPB630L, UPB630X
/ UPD630S
HBL103U, HBL103UM, HBL203U, HBL203UM
HBL203U, HBL203UM, HBL203UQ, HBL203UMQ
218
MCCB MB
MCCB
2 pole
Applicable MCCB
3 pole
Dimensions
Order
code
TCF 10AP 2
50
21.5
TCF 10BP 2
57
4 pole
Dimensions
Category
58.5
TCF 10AP 3
75
21.5
28.5
58.5
TCF 10BP 3
87
28.5
117
28.5
58.5
32.5
58.5
TCF 20CP 3
102
32.5
137
32.5
58.5
10
59
TCF 10FP 3
90
10
59
TCF 10FP 4
120
10
59
10
59
TCF 20GP 3
105
10
59
TCF 20GP 4
140
10
59
TCF 40D 3
190
120
100
TCF 40D 3
190
120
100
TCF 40D 4
234
120
100
TCF 80E 3
230
139
100
TCF 80E 3
230
139
100
TCF 80E 4
300
139
100
51
151
TCF 12UP 3
105
29.5
140
29.5
82.5
TCF 46UP 3
140
35
185
35
106.5
TCF 12UP 3
105
29.5
Order
code
Dimensions
Order
code
100
21.5
58.5
/ UAD50S, UAD100R
TCF 10FP 3
MCCB MB
/ UCD630S, UCD800S
UCB1600S
UPB100S, UPB100H, UPB100L, UPB100X,
UPB160S, UPB160H, UPB160L, UPB160X,
UPB250S, UPB250H, UPB250L, UPB250X
/ UPD100S, UPD160S, UPD250S
UPB400S, UPB400H, UPB400L, UPB400X,
UPB630S, UPB630H, UPB630L, UPB630X
/ UPD400S, UPD630S
HBL103U, HBL103UM, HBL203U,
HBL203UM, HBL103UQ, HBL103UMQ,
82.5
HBL203UQ, HBL203UMQ
For both line and load side of MCCB, 2EA shall be ordered.
Applicable MCCB
Category
2 pole
3 pole
4 pole
REAR-BR 10A 2
REAR-BR 10A 3
REAR-BR 10B 2
REAR-BR 10B 3
REAR-BR 20C 3
REAR-BR 20C 3
REAR-BR 20C 4
MCCB MB
For both line and load side of MCCB, 2EA shall be ordered.
U-Series
Terminal Accessories
| Interpole barrier (TQQ) |
Applicable MCCB
Order code
Dimensions
Category
A
2EA/SET
50
53
2EA/SET
50
53
2EA/SET
50
53
2EA/SET
51
53
2EA/SET
120
97
2EA/SET
110
95
TQQ 80NE 3P
2EA/SET
125
92
TQQ 160NE 3P
4EA/SET
102
68
TQQ 12NE 3P
4EA/SET
71
54.5
TQQ 46NE 3P
4EA/SET
122
103
TQQ 12NE 3P
4EA/SET
71
54.5
2EA/SET
50
53
220
MCCB MB
MCCB
Order code
Rated
voltage
input
AC100-230V
output
DC 9V
Dimension
Weight
2.7 kg
Standard kit
Applicable MCCB
Technical Information
U-Series
LTD
15
In x
16
20
25
30
32
40
50
60
63
75
0.8
12
16
24
32
40
48
50
60
64
80 100 120
0.9
14
18
27
36
45
54
57
68
72
90 113 135
1.0
15
40
50
60
63
75
16
20
25
30
32
150 160 200 250 300 320 400 500 600 630 750 800 1000 1250 1500 1600 1750 2000 2250 2500
20%
Tolerance
Trip unit
Instantaneous
1)
current setting Adjustable
[Ii] (A)
Tolerance
INST
In x 5-6-7-8-9-10
In x 5-9: 30%, 20%
In x 10:
Trip unit
20%
UPB100
UPB160
UPB250
MOR-10-ES
MOR-16-ES
MOR-25-ES
125
160
250
Trip unit
Rated (CT) current [In] (A)
LTD
STD
INST
PTA
Tolerance
Ir x NON-2-3-4-5-6-7-8-9-10
Tolerance
Tolerance
In x 1100%
Tolerance
Ir x 90%
Tolerance
20%
+50ms, -20ms
20%
The default values are underlined. Please check and adjust the setting condition of each characteristic before use.
224
MCCB
UPB400
UPB630
MOR-40-ES2) / MOR-40-GS
MOR-63-ES2) / MOR-63-GS
400
0.8
0.85
0.9
0.95
1.0
Io Ir
0.63
200
215
225
240
250
Rated current setting [Ir] (A)
0.8
255
270
290
300
320
1.0
320
340
360
380
400
2-4-6-8-12 sec. at Ir x 600%
Long time setting [tr]
Short time pick-up current [Isd] (A) Ir x NON-2-4-6-8-10
0-0.1-0.2-0.3 sec. at definite time-limit section
Time delay setting [tsd]1)
Instantaneous current setting
In x NON-3-6-8-10-11
[Ii] (A)
In x NON-0.2-0.3-0.4
Ground fault current [Ig] (A)
0.1-0.2-0.3-0.4-0.8 sec. at definite time-limit section
Ground fault delay setting [tg]
Ir x 0.9
Pre-trip alarm current [Ip] (A)
LTD
STD
INST
GFT2)
PTA
Io Ir
0.63
0.8
1.0
0.8
320
400
500
630
0.85
340
430
540
0.9
0.95
1.0
360
380
400
450
480
500
570
600
630
Tolerance
20%
Tolerance
15%
Tolerance +50ms,-20ms
Tolerance
Tolerance
Tolerance
Tolerance
20%
15%
+50ms, -20ms
10%
- The default values are underlined. Please check and adjust the setting condition of each characteristic before use.
1) I2t characteristic can be ON or OFF by adjusting the [tsd] knob .
2) GFT protection is option and not applicable for MOR-40-ES and MOR-63-ES trip unit.
1
2
3
4
5
6
UCB1000
UCB1250
MOR-100-ES2) / MOR-100-GS
MOR-125-ES2) / MOR-125-GS
1000
0.8
0.85
0.9
0.95
1.0
Io Ir
0.63
505
535
565
600
630
Rated current setting [Ir] (A)
0.8
640
680
720
760
800
1.0
800
850
900
950
1000
2-4-6-8-12 sec. at Ir x 600%
Long time setting [tr]
Short time pick-up current [Isd] (A) Ir x NON-2-4-6-8-10
0-0.1-0.2-0.3 sec. at definite time-limit section
Time delay setting [tsd]1)
Instantaneous current setting
In x NON-3-6-8-10-11
[Ii] (A)
In x NON-0.2-0.3-0.4
Ground fault current [Ig] (A)
0.1-0.2-0.3-0.4-0.8 sec. at definite time-limit section
Ground fault delay setting [tg]
Ir x 0.9
Pre-trip alarm current [Ip] (A)
LTD
STD
INST
GFT2)
PTA
Io Ir
0.63
0.8
1.0
0.8
630
800
1000
1250
0.85
0.9
0.95
1.0
670
710
750
790
850
900
950
1000
1060
1125
1190
1250
Tolerance
20%
Tolerance
15%
Tolerance +50ms,-20ms
Tolerance
Tolerance
Tolerance
Tolerance
20%
15%
+50ms, -20ms
10%
- The default values are underlined. Please check and adjust the setting condition of each characteristic before use.
1) I2t characteristic can be activate by adjusting [tsd] knob .
2) GFT protection is option and not applicable for MOR-100-ES and MOR-125-ES trip unit.
1
2
3
4
5
6
U-Series
In
Io
Io
Ir
Ir
Isd
Isd
570
Ir
Ir 3420
Ii
Ii
In 5040
In
Ig
Ig
In
In
In
In
Io
Io
Ir
Ir
190
1250
1125
Isd
Isd
Ir 6750
Ir
Ii
Ii
In
10000
In
Ig
Ig
In 375
In
0.5
0.6
0.7
0.8
0.9
0.95
1.0
640
800
960
1120
1250
1440
1520
1600
LTD
INST
I1 x 2-3-4-5-6-7-8-10
Red light
0A
Green light
0.4 x In
Yellow light
I1
LED
indication
226
1600
In x
MCCB
Selection By Application
| Model selection for transformer |
AC220V
Capacity of Three phase
transformer
Single phase
(kVA)
30
50
16
70-100
30
150-300
50
2.5
500-750
150
10
UAB30R
UAB50C
UAB50R
UAB60C
UAB60R
35
42 50
65
UAB50H, UCB50R
UAB100C
MCCB
2000
300
25
UAB30C
1500
85
UCB50H
UAB100S, UCB100R
100
125
UCB50L
UCB100S
UCB100H
UCB100L
UPB100H, UPB100L
UCB250H
UCB250L
UPB250H, UPB250L
UCB250R
UCB250S
UCB250N
UCB400R
UCB400S
UCB400H
UCB630R
UCB630S, UCB630H
UPB400S, UPB400H,
UPB400L, UPB400X
UPB630S, UPB630H,
UPB630L, UPB630X
UCB800R
UCB800S, UCB800H
UCB800L
UCB400L
UCB1000L, UCB1250L
UCB1000S, UCB1250S
AC460V
Capacity of transformer
(kVA)
50
1.5
75-200
300
750
10
UAB30C
UAB30R
UAB50C
UAB50R
UAB60C
UAB60R
UAB100C
18
25
2000
35
UAB50H, UCB50R
42
UCB50H
UAB100S, UCB100R
UCB250R
MCCB
1500
UCB250S
UCB400R
3000
50
65
75
85
100
UCB50L
UCB100S
UCB100H
UCB100L
UPB100H
UCB250N
UCB250H
UCB250L
UPB250H
UPB250L
UCB400L
UPB400L, UPB400X
UCB400S
UCB400H
UPB100L
UCB630R
UCB630S
UCB630H
UCB800R
UCB800S
UCB800H
UCB800L
UCB1000S, UCB1250S
UCB1000L,UCB1250L
AC220V
AC440V
50Hz
60Hz
50Hz
60Hz
50Hz
60Hz
50Hz
60Hz
60
50
30
30
40
50
30
20
10
75
60
40
40
50
50
30
30
15
100
100
60
50
60
60
40
40
20
175
175
75
60
100
75
50
40
25
200
200
100
100
100
100
50
50
30
225
225
100
100
175
150
60
60
40
400
400
150
125
200
200
100
75
50
400
400
175
175
225
225
100
100
75
600
500
300
300
400
400
150
150
100
800
800
400
400
400
400
225
225
150
1000
1000
600
500
600
600
300
300
200
1200
800
800
800
800
400
400
300
1000
1000
600
600
400
800
U-Series
Selection By Application
| Model selection for lighting and heater |
The maximum operational current shall not exceed 80% of MCCB rated current.
Breaking capacity (kA)
Maximum
operational Rated current sym
2.5
5
current (A) of MCCB (A)
12
15
16
20
24
30
32
40
40
50
48
60
60
75
10
25
UAB30R
UAB30C
35
50
65
UAB50H,
UCB50H
UCB50R
UAB50C
UAB50R
UAB60C
UAB60R
UAB100S,
UCB100R
UAB100C
85
100
125
UCB50L
UCB100S
UCB100H
UCB100L
UPB100H,
UPB100L
UCB250H
UCB250L
UPB250H,
UPB250L,
80
100
100
125
120
150
140
175
160
200
180
225
200
250
240
300
280
350
320
400
400
500
500
630
560
700
640
800
800
1000
UCB1000S
UCB1000L
1000
1250
UCB1250S
UCB1250L
UCB250R
UCB250S
UCB250N
UCB400R
UCB400S
UCB400H
UPB400S,
UPB400H,
UPB400L,
UPB400X
UCB400L
UCB630R
UCB630S, UCB630H
UPB630S, UPB630H,
UPB630L, UPB630X
UCB800R
UCB800S, UCB800H
UCB800L
AC460V
Breaking capacity (kA)
Maximum
operational Rated current sym
1.5
5
current (A) of MCCB (A)
228
10
18
25
35
42
50
65
75
85
100
12
15
16
20
24
30
32
40
40
50
48
60
60
75
80
100
100
125
120
150
140
175
160
200
180
225
200
250
240
300
280
350
320
400
400
500
500
630
560
700
640
800
800
1000
UCB1000S
UCB1000L
1000
1250
UCB1250S
UCB1250L
UAB30R
UAB30C
UAB50H
UCB50H
UCB50R
UAB50C
UAB50R
UAB60C
UAB60R
UAB100C
UAB100S
UPB100H
UPB100L
UPB250H
UPB250L
UAB100R
UCB250R
UCB400R
UCB50L
UCB400H
UCB400L
UCB630R
UCB630S
UCB630H UCB630L
UCB800R
UCB800S
UCB800H UCB800L
UCB400S
UPB400L,
UPB400X
UPB630L,
UPB630X
MCCB
Condition
IM1
IM
IL
Iw
IM+ IL
IM2
IN
IW
IL1
IM >
50A
IL
Iw 1.25 IM+ IL
IL2
IM : Load current of motor
IL : Load current of other loads
50A
IM
IL
Iw 1.1 IM+ IL
U-Series
Selection By Application
Rated current of MCCB for AC220V three phase induction motor
Maximum
Total
capacity of operational
current 0.75 / 1.5 /
motors
(below kW) (below A)
4.8
8
3
4.5
6.3
8.2
12
15.7
19.5
23.2
30
37.5
45
52.5
63.7
75
86.2
97.5
112.5
125
150
175
220
15
20
30
40
50
75
90
100
125
150
175
100
150
300
350
400
450
500
600
700
800
20
30
40
50
60
100
100
125
150
175
200
225
300
350
400
500
500
600
700
800
900
30
30
40
50
60
100
100
125
150
175
200
225
300
350
400
500
500
600
700
800
900
2.2 /
11.1
3.7 /
17.4
5.5 /
26
7.5 /
34
11 /
48
15 / 18.5 / 22 /
65
79
93
30 /
125
37 /
160
45 /
190
5/
230
75 /
310
90 /
360
110 / 132 /
440 500
30
30
40
50
60
100
100
125
150
175
200
225
300
350
400
500
500
600
700
800
900
50
50
50
60
100
100
125
150
175
200
225
300
350
400
500
500
600
700
800
900
60
75
75
100
100
125
150
175
200
225
300
350
400
500
500
600
700
800
900
100
100
100
100
125
150
175
200
225
300
350
400
500
500
600
700
800
900
125
125
125
150
175
200
225
300
350
400
500
500
600
700
800
900
150
150
150
150
175
200
225
300
350
400
500
500
600
700
800
900
300
300
300
300
350
400
500
500
600
700
800
900
400
400
400
400
400
500
500
600
700
800
900
500
500
500
500
500
500
600
700
800
900
500
500
500
500
500
600
700
800
900
600
600
700
700
700
800
900
700
700
700
800
800
900
1000
1000
1000
900
90 /
180
110 / 132 /
220 250
175
175
175
200
200
225
300
350
400
500
500
600
700
800
900
200
225
225
225
225
300
350
400
500
500
600
700
800
900
1000
1000
1000
3
4.5
6.3
8.2
12
15.7
19.5
23.2
30
37.5
45
52.5
63.7
75
86.2
97.5
112.5
125
150
175
200
250
300
350
400
450
500
7.5
10
15
20
25
38
45
50
63
75
88
100
125
150
175
200
225
250
300
350
400
500
600
700
700
900
1000
2.2 /
5.5
3.7 /
8.7
5.5 /
13
7.5 /
17
11 /
24
15 / 18.5 / 22 /
32
39
46
30 /
62
37 /
80
45 /
95
55 /
115
75 /
155
15
15
15
15
15
15
30
20
20
20
30
40
30
30
30
30
40
50
30
30
30
30
40
50
50
50
50
50
50
50
60
75
50
50
50
50
50
50
60
75
100
60
60
60
60
60
60
60
75
100 125
75
75
75
75
75
75
75
100 100 125
100 100 100 100 100 100 100 100 100 125 150
100 100 100 100 100 100 100 100 100 125 150 175
125 125 125 125 125 125 125 125 125 125 150 175 225
150 150 150 150 150 150 150 150 150 150 150 200 225 250
175 175 175 175 175 175 175 175 175 175 175 200 225 250
200 200 200 200 200 200 200 200 200 200 200 200 225 300 350
225 225 225 225 225 225 225 225 225 225 225 225 225 300 350 400
250 250 250 250 250 250 250 250 250 250 250 250 250 300 350 400
300 300 300 300 300 300 300 300 300 300 300 300 300 300 350 400 500
350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 400 500 500
400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 500 500 500
500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500
600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600
700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700
800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800
800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200
230
MCCB
Insulation Distance
Insulation plate
B1
B1
B2
B1
B2
B2
A
D
Direct cable
connection
Taping
Bus bar
connection
Applicable MCCB
Rear or plug-in
connection
Distances
A
B1
B2
75
50
30
from 0
25
80
50
30
from 0
25
80
60
50
from 0
25 (?)
80
60
50
from 0
40
100
100
80
from 0
80
50
120
80
from 0
80
80
50
30
from 0
10
100
100
70
from 0
10
120
100
80
from 0
80
80
50
30
from 0
10
100
100
70
from 0
10
U-Series
Cascading Table
| AC240V |
Downstream
Upstream
UAB-C
Recognition
category
UAB-R
UAB/UCB-S
UAB100C UCB250R UCB400R UCB630R UCB800R UAB100S UCB250S UCB400S UCB630S UCB800S
Model
Rated
current
(A)
5-100
125-250
250-400
500,630
700,800
15-100
125-250
250-400
500,630
700,800
Breaking
capacity
[Icu]
(kA r.m.s)
25
35
35
50
50
50
50
50
100
100
UAB30C
3-30
10
25
30
30
35
35
35
UAB50C
5-50
10
25
30
30
35
35
35
UAB60C
5-60
10
25
30
30
35
35
35
UAB100C
5-100
25
35
35
42
42
42
42
65
65
UAB30R
5-30
25
35
35
42
42
42
42
42
65
65
UAB50R
5-50
25
35
35
42
42
42
42
42
65
65
UAB60R
5-60
25
35
35
42
42
42
42
42
65
65
UAB100R
15-100
42
50
50
50
50
75
75
UCB50R
15-50
50
85
85
UCB100R
15-100
50
85
85
UCB250R
125-250
35
65
65
UCB400R
250-400
35
UAB50S
15-50
42
UAB100S
15-100
UAB/UCB-S UCB100S
UAB-C
UAB/UCB-R
50
50
65
50
75
75
50
85
85
15-100
65
85
85
UCB250S
125-250
50
85
85
UCB400S
250-400
50
UAB50H
15-50
50
UCB50H
15-50
85
100
100
15-125
85
100
100
UCB250H
125-250
85
100
100
UCB400H
250-400
85
UCB50L
15-50
100
UCB100L
15-125
100
UCB250L
125-250
100
UCB400L
250-400
125
UPB100H
15-125
130
UPB250H
100-250
130
UPB100L
15-125
150
UPB250L
100-250
150
UAB/UCB-H UCB100H
UCB-L
UPB-H
UPB-L
232
50
50
50
50
50
50
85
100
MCCB
UCB-H
UCB-L
UPB-H
UPB-L
UCB100H UCB250H UCB400H UCB630H UCB800H UCB100L UCB250L UCB400L UCB630L UCB800L UPB100H UPB250H UPB100L UPB250L
15-125
125-250
250-400
500,630
700,800
15-125
125-250
250-400
500,630
700,800
15-125
100-250
15-125
100-250
85
85
85
100
100
100
100
125
125
125
130
130
150
150
50
50
50
50
50
65
50
50
50
50
50
65
50
50
50
50
50
65
65
65
65
65
65
85
85
85
65
65
65
65
65
65
65
85
85
85
85
85
100
100
65
65
65
65
65
65
65
85
85
85
85
85
100
100
65
65
65
65
65
65
65
85
85
85
85
85
100
100
75
75
75
75
75
100
100
100
85
85
85
85
100
100
100
100
85
85
85
85
100
100
100
100
65
65
65
100
100
100
85
100
100
100
100
130
130
100
130
130
100
65
100
100
100
100
100
85
100
125
125
125
100
130
85
85
100
125
125
125
100
130
85
85
125
125
125
85
85
75
75
85
85
85
85
85
85
100
100
125
125
125
100
125
125
125
100
125
125
125
100
100
100
100
130
130
125
85
100
100
130
130
130
130
130
130
150
150
130
150
125
100
125
125
125
125
125
125
125
125
125
130
130
150
150
150
130
150
150
150
U-Series
Cascading Table
| AC415V |
Downstream
Upstream
UAB-C
Recognition
category
UAB-R
UAB/UCB-S
UAB100C UCB250R UCB400R UCB630R UCB800R UAB100S UCB250S UCB400S UCB630S UCB800S
Model
Rated
current
(A)
5-100
125-250
250-400
500,630
700,800
15-100
125-250
250-400
500,630
700,800
Breaking
capacity
[Icu]
(kA r.m.s)
10
18
30
45
45
30
25
42
65
65
18
18
30
30
UAB30C
3-30
10
7.5
10
10
10
UAB50C
5-50
10
7.5
10
10
10
UAB60C
5-60
10
7.5
10
10
10
UAB100C
5-100
10
14
14
14
14
UAB30R
5-30
10
14
14
14
14
18
18
18
30
30
UAB50R
5-50
10
14
14
14
14
18
18
18
30
30
UAB60R
5-60
10
14
14
14
14
18
18
18
30
30
UAB100R
15-100
25
30
35
35
35
42
42
UCB50R
15-50
25
30
35
35
35
42
42
UCB100R
15-100
25
30
35
35
35
42
42
UCB250R
125-250
18
30
35
35
30
35
35
UCB400R
250-400
30
UAB50S
15-50
25
UAB100S
15-100
UAB/UCB-S UCB100S
UAB-C
UAB/UCB-R
30
50
35
30
35
42
42
35
35
42
42
45
45
42
50
50
35
35
35
42
42
35
35
30
35
15-100
36
UCB250S
125-250
25
UCB400S
250-400
42
UAB50H
15-50
30
35
35
UCB50H
15-50
42
45
15-125
42
UCB250H
125-250
42
UCB400H
250-400
65
UCB50L
15-50
UCB100L
30
30
65
45
42
42
42
45
50
50
45
45
50
50
45
45
50
50
50
65
65
15-125
50
65
65
UCB250L
125-250
50
65
65
UCB400L
250-400
100
UPB100H
15-125
100
UPB250H
100-250
100
UPB100L
15-125
130
UPB250L
100-250
130
UAB/UCB-H UCB100H
UCB-L
UPB-H
UPB-L
234
MCCB
UCB-H
UCB-L
UPB-H
UPB-L
UCB100H UCB250H UCB400H UCB630H UCB800H UCB100L UCB250L UCB400L UCB630L UCB800L UPB100H UPB250H UPB100L UPB250L
15-125
125-250
250-400
500,630
700,800
15-125
125-250
250-400
500,630
700,800
15-125
100-250
15-125
100-250
42
42
65
85
85
50
50
100
100
100
100
100
130
130
14
14
18
25
25
25
14
14
18
25
25
25
14
14
18
25
25
25
18
30
30
30
30
35
35
35
18
18
30
30
30
30
30
35
35
35
35
35
42
42
18
18
30
30
30
30
30
35
35
35
35
35
42
42
18
18
30
30
30
30
30
35
35
35
35
35
42
42
35
42
50
50
35
50
50
50
35
42
50
50
42
50
50
50
35
42
50
50
42
50
50
50
35
42
42
42
42
42
35
42
35
42
50
50
42
45
50
42
50
42
42
42
50
50
50
50
50
42
50
50
50
50
50
65
65
65
50
65
65
65
50
75
75
75
65
65
50
50
50
50
50
50
50
50
50
85
75
42
50
50
50
50
35
50
45
50
50
50
50
65
65
65
50
50
65
65
60
75
75
50
50
85
85
85
85
85
85
85
60
75
75
50
85
85
85
60
75
75
85
85
85
85
85
100
85
65
85
85
100
100
100
65
85
85
100
100
100
65
85
85
100
100
100
100
100
100
100
100
100
130
130
130
U-Series
Cascading Table
| AC440V |
Downstream
Upstream
UAB-C
Recognition
category
UAB-R
UAB/UCB-S
UAB100C UCB250R UCB400R UCB630R UCB800R UAB100S UCB250S UCB400S UCB630S UCB800S
Model
Rated
current
(A)
5-100
125-250
250-400
500,630
700,800
15-100
125-250
250-400
500,630
700,800
Breaking
capacity
[Icu]
(kA r.m.s)
10
18
25
35
35
25
25
35
50
50
14
14
21
21
UAB30C
3-30
7.5
7.5
7.5
7.5
7.5
UAB50C
5-50
7.5
7.5
7.5
7.5
7.5
UAB60C
5-60
7.5
7.5
7.5
7.5
7.5
UAB100C
5-100
10
10
10
10
10
UAB30R
5-30
10
10
10
10
10
14
14
14
21
21
UAB50R
5-50
10
10
10
10
10
14
14
14
21
21
UAB60R
5-60
10
10
10
10
10
14
14
14
21
21
UAB100R
15-100
21
25
30
30
25
30
30
35
UCB50R
15-50
25
35
35
35
35
42
UCB100R
15-100
25
35
35
35
35
42
UCB250R
125-250
18
25
25
25
35
35
UCB400R
250-400
25
UAB50S
15-50
21
UAB100S
15-100
25
UAB/UCB-S UCB100S
15-100
35
UCB250S
125-250
25
UCB400S
250-400
35
UAB50H
15-50
25
UCB50H
15-50
UAB-C
UAB/UCB-R
42
35
30
30
35
35
35
42
42
50
35
42
42
50
35
50
42
50
50
15-125
42
50
50
UCB250H
125-250
42
50
50
UCB400H
250-400
50
UCB50L
15-50
50
UCB100L
15-125
50
UCB250L
125-250
50
UCB400L
250-400
85
UPB100H
15-125
85
UPB250H
100-250
85
UPB100L
15-125
100
UPB250L
100-250
100
UAB/UCB-H UCB100H
UCB-L
UPB-H
UPB-L
236
25
25
30
30
35
35
35
35
35
35
25
25
35
35
MCCB
UCB-H
UCB-L
UPB-H
UPB-L
UCB100H UCB250H UCB400H UCB630H UCB800H UCB100L UCB250L UCB400L UCB630L UCB800L UPB100H UPB250H UPB100L UPB250L
15-125
125-250
250-400
500,630
700,800
15-125
125-250
250-400
500,630
700,800
15-125
100-250
15-125
100-250
42
42
50
65
65
50
50
85
85
85
85
100
85
130
10
10
14
18
18
18
10
10
14
18
18
18
10
10
14
18
18
18
14
25
25
25
25
30
30
30
14
14
25
25
25
25
25
30
30
30
30
35
30
35
14
14
25
25
25
25
25
30
30
30
30
35
30
35
14
14
25
25
25
25
25
30
30
30
30
35
30
35
30
35
35
35
30
35
35
35
45
45
35
35
35
35
40
45
45
45
45
45
35
35
35
35
40
45
45
45
45
45
30
30
30
30
30
30
45
45
35
40
30
35
35
35
35
38
40
42
50
38
38
38
42
42
42
40
45
50
50
50
45
50
50
50
45
55
55
55
50
50
40
40
45
45
45
35
45
45
55
55
35
45
42
40
30
45
40
45
45
42
42
45
45
45
35
45
35
45
50
55
55
50
50
65
65
65
65
65
65
65
50
55
55
50
65
65
65
65
65
50
55
55
65
65
65
85
85
85
85
85
65
65
65
85
85
85
65
65
85
85
85
65
65
85
85
85
85
85
Order Information
MCCB
Order Information
Fixed thermal & fixed instantaneous / UAB, UCB, UPB type
UPB250X
3P
Type
Code
Code
Pole
UAB
UAB30C
..
UAB100S
2P1)
2 pole
3P
UCB
UCB50R
..
UCB800L
4P2)
UPB
UPB100S
..
UPB250X
Code
40/45
3 pole
4 pole
B2)
Bus bar
50
00
Terminal connection
Direct mounting
Screw
Compensating temperature
T51)
Code
S1)
1) "2P" (2 pole) is
not applicable
to UPB.
2) "4P" (4 pole) is
not applicable
to UAB30.
T4
T4
Plug-in mounting3)
X4)
P5)
F6)
00
00250
Code
Internal accessory
Code
Frequency
001)
without
50/60Hz
Code
Rated current
00003
..
00800
3A
..
800A
AUX 1C
AUX 2C
Trip alarm switch (ALT)
01
ALT 1C
21
Code
Internal accessory
001)
without
Shunt trip (SHT)
S1
SHT AC110V
S2
SHT AC220V
S3
SHT AC380V
S4
SHT AC440V
S5
SHT DC24V
S6
SHT DC110V
UVT AC110V
U2
UVT AC220V
U3
UVT AC380V
U4
UVT AC440V
U5
UVT DC24V
U6
UVT DC110V
U-Series
Order Information
Adjustable thermal - UAB, UCB, UPB type
UPB250X
Type
UAB
3P
Code
Code
Pole
UAB50S
2P1)
2 pole
UAB50H
3P
3 pole
UAB100R
4P
4 pole
B2)
1) "2P" (2 pole) is
available for UCB
only.
UCB50H
UPB
T4
T5
X4)
00
Terminal connection
Direct mounting
Bus bar
Rated current
00005
..
00800
5A
..
800A
SHT AC220V
S3
SHT AC380V
S4
SHT AC440V
50
Code
without
SHT AC110V
F6)
40/45
Internal accessory
001)
S2
UCB100R
..
UCB800L
S5
SHT DC24V
S6
SHT DC110V
Code
Frequency
50/60Hz
UVT AC110V
U2
UVT AC220V
U3
UVT AC380V
U4
UVT AC440V
Code
Instantaneous
characteristic
U5
UVT DC24V
Fixed instantaneous
UVT DC110V
H1)
Adjustable instantaneous
U6
Code
Internal accessory
001)
without
Auxiliary switch (AUX)
10
20
AUX 1C
AUX 2C
Trip alarm switch (ALT)
01
ALT 1C
21
240
00250
Code
S1
Compensating temperature
Plug-in mounting3)
P5)
UPB100S
..
UPB250X
00
Screw
UCB50L
Code
Code
S1)
UAB100S
UCB
T4
MCCB
Order Information
Electronic / UCB, UPB type
UPB630X
Type
UCB
3P
Code
Code
Pole
UCB1000S
3P
3 pole
UCB1000L
4P1)
4 pole
UCB1250S
1) "4P" (4 pole) is
not applicable
to UCB1600S.
UCB1250L
Code
UPB100S
..
UPB630X
Code
Protection characteristic
ES1)
EG2)
00
Terminal connection
Direct mounting
S1)
Screw
B2)
Bus bar
Plug-in mounting3)
X4)
UCB1600S
UPB
ES
P5)
F6)
00
00630
Code
Internal accessory
Code
Frequency
001)
without
C1)
50/60Hz
50Hz
60Hz
AUX 1C
20
AUX 2C
30
AUX 3C
40
1) Only UCB1600S is
common use for both
50Hz & 60Hz ("C").
AUX 4C
Trip alarm switch (ALT)
01
ALT 1C
21
31
Code
Rated current
00100
..
01600
100A
..
1600A
Code
001)
Internal accessory
without
Shunt trip (SHT)
S1
SHT AC110V
S2
SHT AC220V
S3
SHT AC380V
S42)
SHT AC440V
S5
SHT DC24V
S6
SHT DC110V
UVT AC110V
U2
UVT AC220V
U3
UVT AC380V
U42)
UVT AC440V
U52)
UVT DC24V
U62)
UVT DC110V
U-Series
Order Information
Motor protection / UPB type
UPB250L
Type
UPB
3P
Code
Code
Pole
UPB100H
3P
3 pole
MP
Code
S1)
UPB100L
00
Terminal connection
Direct mounting
X3)
UPB250L
For the applicable breaker,
please refer to page 15 & 26.
Code
Trip mechanism
MP
P4)
F5)
00250
Code
Internal accessory
Code
Frequency
001)
without
50/60Hz
Code
Rated current
002.5
..
00225
2.5A
..
225A
Screw
Plug-in mounting2)
UPB250H
00
AUX 1C
AUX 2C
Trip alarm switch (ALT)
01
ALT 1C
21
Code
001)
Internal accessory
without
Shunt trip (SHT)
S1
SHT AC110V
S2
SHT AC220V
S3
SHT AC380V
S4
SHT AC440V
S5
SHT DC24V
S6
SHT DC110V
UVT AC110V
U2
UVT AC220V
U3
UVT AC380V
U4
UVT AC440V
U5
UVT DC24V
U6
UVT DC110V
242
MCCB
Order Information
Q-class (for nuclear power plant application) / HBL type
HBL203UMQ
Type
3P
T4
00
00225
Code
Code
Pole
Code
Internal accessory
Code
Frequency
HBL103U
3P
3 pole
001)
without
50/60Hz
Code
Rated current
002.5
..
00225
2.5A
..
225A
HBL103UQ
HBL103UM
HBL103UMQ
HBL
00
HBL203U
HBL203UQ
HBL203UM
HBL203UMQ
40/45C
T51)
50C
MP2)
Code
Terminal connection
Direct mounting
Screw
10
20
AUX 1C
AUX 2C
Trip alarm switch (ALT)
01
ALT 1C
21
Code
Internal accessory
001)
without
Shunt trip (SHT)
S1
SHT AC110V
S2
SHT AC220V
S3
SHT AC380V
S4
SHT AC440V
S5
SHT DC24V
S6
SHT DC110V
UVT AC110V
U2
UVT AC220V
U3
UVT AC380V
U4
UVT AC440V
U5
UVT DC24V
U6
UVT DC110V
U-Series
Order Information
Switch disconnector / UAD, UCD, UPD type
UPD630S
Type
UAD
3P
Code
Code
Pole
UAD50C
3P
3 pole
DS
Code
UAD50S
S1)
UAD100R
B2)
UCD100H
UCD160H
00
Terminal connection
Direct mounting
Protection
Code characteristic
DS
Switch
disconnector
X4)
Bus bar
P5)
F6)
UCD250S
UCD
UCD250H
UCD400S
UCD630S
UCD800S
UCD1000S
UCD1250S
UPD100S
UPD160S
UPD
UPD250S
UPD400S
UPD630S
00
00630
Code
Internal accessory
Code
Frequency
001)
without
50/60Hz
Code
Rated current
00050
..
01250
50A
..
1250A
Screw
Plug-in mounting3)
UCD50H
UCC100S
AUX 1C
AUX 2C
Trip alarm switch (ALT)
01
ALT 1C
21
Code
Internal accessory
001)
without
Shunt trip (SHT)
S1
SHT AC110V
S2
SHT AC220V
S3
SHT AC380V
S4
SHT AC440V
S5
SHT DC24V
S6
SHT DC110V
UVT AC110V
U2
UVT AC220V
U3
UVT AC380V
U4
UVT AC440V
U5
UVT DC24V
U6
UVT DC110V
244
MCCB
Order Information
Miniature type - Molded case circuit breaker / UBD, UMB, UDB type
UDB100H
Type
UMB
3P
Code
Code
Pole
UMB30R
2P
2 pole
UMB30S
3P1)
3 pole
UMB30H
UMB50S
T4
S
Code
00
Terminal
connection
00
Code
Internal accessory
Code
Frequency
00
without
50/60Hz
Code
Rated current
00003
..
00100
3A
..
100A
Screw
1) "3P" (3 pole) is
available for
UDB only.
UMB50H
Code Compensating temperature
UDB30S
T4
UDB30H
UDB
00100
40/45C
UDB50S
UDB50H
Code
Internal accessory
UDB100S
00
without
UDB100H
Miniature type - Earth leakage circuit breaker / UGD, UMG, UDG type
UDG100H
Type
UMG
3P
Code
Code
Pole
UMG30R
2P
2 pole
UMG30S
3P1)
3 pole
UMG30H
UMG50S
G4
S
Code
00
Terminal
connection
00
00100
Code
Internal accessory
Code
Frequency
00
without
50/60Hz
Screw
1) "3P" (3 pole) is
available for
UDB only.
UMG50H
UDG30S
UDG30H
UDG
UDG50S
UDG50H
Code
Code
Internal accessory
Code
Rated current
15mA
00
without
G4
30mA
3A
..
100A
G51)
100mA
00003
..
00100
G3
UDG100S
UDG100H
For the applicable breaker,
please refer to page 16 & 33.
U-Series
Order Information
Fixed instantaneous only / UCB type
UPB250X
3P
Type
Code
Code
Pole
3P
3 pole
UCB
UCB50R
..
UCB800L
T4
Code
S1)
B2)
X4)
00
Terminal connection
Direct mounting
00
Internal accessory
Code
Rated current
without
00003
..
00800
3A
..
800A
SHT AC110V
S2
SHT AC220V
S3
SHT AC380V
S4
SHT AC440V
Trip mechanism
P5)
MO
Magnetic only
F6)
S5
SHT DC24V
Code
Frequency
S6
SHT DC110V
50/60Hz
UVT AC110V
U2
UVT AC220V
U3
UVT AC380V
Code
Instantaneous
characteristic
U4
UVT AC440V
10 x In
U5
UVT DC24V
12 x In
U6
UVT DC110V
15 x In
Code
Internal accessory
001)
without
Auxiliary switch (AUX)
10
20
AUX 1C
AUX 2C
Trip alarm switch (ALT)
01
ALT 1C
21
246
001)
Plug-in mounting3)
Code
00250
Code
Screw
Bus bar
MCCB
Handling Instruction
| Storage |
Do not expose to corrosive gases.
Do not expose to harmful gases including sulfur, ammonia and so on.
Do not expose to high humidity for a long period.
Do not expose to direct sunlight for a long period.
Store at -20 to +60 without dust and humidity.
Keep the handle in OFF position.
| Transportation |
Do not drop or apply shock
during transportation.
These can cause
malfunctions in the
breaker.
-5
- +40
Relative humidity
45 - 85%
Altitude
Surrounding
up to 2,000m
without excessive water vapor, oil vapor, smoke, dust, salts and corrosive materials
U-Series
Handling Instruction
| Installation and connection |
Insulating
supporter
(Unit : N [kgf])
20cm
10/0.4
490/50
245/25
18/0.3
1863/190
932/95
25/0.2
4412/450
2206/225
35/0.23
8630/880
4315/440
42/0.2
12455/1270
6277/635
50/0.2
17652/1800
8826/900
65/0.2
29910/3050
14955/1525
85/0.2
51190/5220
25595/2510
100/0.2
70804/7220
35402/3610
125/0.2
110815/11300
55408/5650
250
MCCB
| Dielectric test |
The test shall be done in these conditions.
Main circuit
Rated insulation voltage (Ui)
Ui
AC300V
AC300V
AC2000V
Ui
AC2500V
AC600V
Test voltage
AC1000V
AC60V
Uis
AC60V
Dielectric test
Handle position
Handle position
Test
Measuring parts
ON
OFF
ON
OFF
Line side
Load side
Dielectric test
- Do not apply test voltage, if test voltage is applied by mistake, the breaker can not be used.
U-Series
Circumstance
Normal
within 10 years :
Dust but no corrosive gas
once a year
within 5 years :
once 6 year
once a month
once a month
252
MCCB
| Troubleshooting |
In case of any abnormality during breaker operation, please handle it as below.
For cases not mentioned in below, please contact us.
Overheating
Inferior
dielectric
Inability of
operation
High temperature of
terminal part
Damage in insulation
part of terminal
Troubleshooting
Heating from connection part between terminal bus bar and breaker
High temperature of
breaker body
Abnormal voltage of
load side
Inability of ON and
RESET
Frequent trip
Non-energized UVT
Malfunction
U-Series
Malfunction
Troubleshooting
Adjust the residual current
Install the breaker closer to the load
Excessive surge
Trip during normal
operation
Accessories
Symptom and possible cause
Voltage drop of control circuit
Shunt trip (SHT)
Inability of
Under voltage trip (UVT)
254
Inferior mechanism
malfunction
Auxiliary switch (AUX)
and trip alarm switch
(ALT)
operation or
Troubleshooting
U-Series
Molded Case Circuit Breaker
www.hyundai-elec.com
Head Office
Seoul
(Sales & Marketing)
Atlanta
New Jersey
London
Tokyo
8th Fl., Yurakucho Denki Bldg.1-7-1, Yuraku-Cho, Chiyoda-Ku, Tokyo, 100-0006, Japan
Tel: 81-3-3212-2076, 3215-7159
Fax: 81-3-3211-2093
Osaka
I-Room 5th Fl. Nagahori-Plaza Bldg. 2-4-8, Minami Senba, Chuo-Ku, Osaka, 542-0081, Japan
Tel: 81-6-6261-5766, 5767
Fax: 81-6-6261-5818
Riyadh
2nd Floor, The Plaza, P.O Box 21840, Riyadh 11485, Saudi Arabia
Tel: 966-1-462-2331
Fax: 966-1-464-4696
Dubai
205, Building 4, Emaar Square, Sheikh Zayed Road, Pobox 252458, Dubai, UAE
Tel: 971-4-425-7995
Fax: 971-4-425-7996
Kuwait
Moscow
World Trade Center, Ent. 3, #1902, Krasnopresnenskaya Nab. 12, Moscow, 123610, Russia
Tel: 7-495-258-1381
Fax: 7-495-258-1382
Madrid
Sofia
Montgomery
Yangzhong
No.9 Xiandai Road, Xinba Scientific and Technologic Zone, Yangzhong, Jiangsu, P.R.C. Zip: 212212, China
Tel: 86-511-8842-0666, 0212
Fax: 86-511-8842-0668, 0231
Fax: 359-2-803-3203