P92x

VOLTAGE & FREQUENCY RELAYS


P921
P922
P923

Software Version

V4 to V6.C

Software Version

V4 to V6.C

Software Version

V4 to V6.E

Technical Data Sheet


P92X/EN TD/A12

This Document does not replace the Technical Manual

P920 Technical Data Sheet

Integrated with 3 independent phase over voltage and phase


under voltage thresholds, MiCOM P921, P922 and P923
relays provide effective voltage protection for typical
applications like protection of motors, generators., etc. The
configurable detection logic (AND, OR) can also indicate the
absence of voltage, when the under voltage protection is used.

MiCOM P92x range of relays provide reliable and


high performance voltage and frequency
protection.
Versatile application and integration of protection
functions with automation, control and
measurement functions, combined with reduced
maintenance, makes P92x relays an optimal and
innovative choice.

The 3 zero-sequence over voltage thresholds available in


P921, P22 & P923 relays can be applied :

A friendly, multi-lingual user interface with


programmable LEDs and logic equations, allows for
simple and flexible applications on any type of
network.

>
>

Connecting the relay to virtually any kind of Digital


Control System or SCADA is made possible by the
wide range of updated communication protocols
provided in P92x

The negative sequence over voltage protection provided by


the P922 and P923 relays is designed to detect unbalanced
conditions it could therefore be used for motor, in which any
unbalance will lead to overheating and damage.

APPLICATION

The P922 and P923 relays integrate 6 frequency thresholds


programmable as under or over frequency, which can be used
for automated load shedding/load restoration.

The MiCOM P92x relays provide fast and accurate protection


for use in numerous applications requiring voltage and
frequency based protection elements. To suit different
application needs and provide optimum solution, following
models are available:

In addition, the P923 relays provide 6 thresholds of


instantaneous rate of change of frequency (df/dt) or average
measurements over a settable time interval.

P921: Voltage protection, 2 logic inputs, 4 outputs.


P922: Voltage and frequency protection, event and fault
records, disturbance recorder, 5 logic inputs, and 8 output
contacts.
P923 : Voltage and frequency protection (plus the rate of
change of frequency element df/dt), event and fault records,
disturbance recorder, 5 logic inputs, 8 output contacts.

MANAGEMENT FUNCTIONS
The protection functions in P92x complemented with a wide
range of control, measurement, monitoring, post fault
analysis and self-diagnostic features assist efficient
management of the primary system. These include:

The relays can be ordered with one of the two voltage input
range, to suit the application:
>
>

>
>
>
>
>
>
>
>

57V to 130V
220V to 480V

>
>
>
>
>
>
>
>
>
>
>
>
>

P920 Technical Data Sheet

to detect earth faults at the neutral point of generators, as


the relays are insensitive to the 3rd harmonics
to detect earth faults in high impedance earthed or
isolated electrical systems .

Programmable logic equation


Programmable logic inputs and outputs
Circuit breaker control
Output contact latching
Circuit breaker status
Circuit breaker condition monitoring (in P922 & P923)
2 setting groups (in P922 & P923)
True rms phase to phase, phase to neutral and residual
voltage measurement
Frequency measurement
Positive and negative sequence voltage measurement (in
P922 & P923)
Rolling and peak value display (in P922 & P923)
Sequence of event recording (in P922 & P923)
Fault recording (in P922 & P923)
Comprehensive disturbance recording (in P922 & P923)
Frequency disturbance record (only in P923)
Local and remote communication ports
Programmable LEDs
Multiple communication protocol options
Password protection
Power-up diagnostics and continuous self-monitoring of
relay.
User friendly setting and analysis software (MiCOM S1)

PROTECTION FUNCTIONS OVERVIEW

27
59
59N
47
27D
81U/81
O
81R

Configuration depending on the number


and type of voltage transformers
Phase-to-neutral or phase-to-phase voltage
protection
Phase under voltage (AND/OR logic)
Phase over voltage (AND/OR logic)
Settable hysteresis
Zero-sequence over voltage
Negative sequence over voltage
Positive sequence under voltage
Under/over frequency
Rate of change of Frequency
Inhibition of voltage & frequency protection functions
Inhibition of timers(instantaneous forcing)
Blocking logic
Under voltage Blocking (settable for P923)
Digital inputs
Output relays
Remote communication (RS485 port)
Local communication (RS232 port)

P922

P923

x
x
x
x
-

x
x
x
x
x
x

x
x
x
x
x
x

x
2
4
x
x

x
x
5
8
x
x

x
x
x
5
8
x
x

VOLTAGE PROTECTION

CONFIGURATION DEPENDING
ON THE VT

For each of the voltage protection function listed below, an


instantaneous signal and a time delayed signal is available
for each threshold.

MiCOM P921, P922 and P923 relays can be used in the


following configurations:

For time-delayed signals, the first threshold of each function


("low threshold") offers the choice between a definite timer and
an inverse timer, to which a reset timer can be assigned. The
other thresholds only have one definite timer.

"3 phase-neutral VTs" or "3 phase-neutral VTs and 1


residual VT":
> The voltage protection element can therefore operate
either from measured phase-to-neutral voltages, or from
phase-to-phase voltages which have been internally
calculated by the relay. Zero-sequence over voltage
protection will always be available, the presence of the
residual VT is designed to display the true RMS value of
the residual voltage.
> "3 phase-phase VTs and 1 residual VT" or "2 phasephase VTs and 1 residual VT":
The voltage protection element can only operate from
measured phase-to-phase voltages. If the residual VT is
not connected, the zero-sequence over voltage protection
will not be available.
>

UNDER/OVERVOLTAGE
Three thresholds are available for each function: each one can
be independently activated or deactivated. If a threshold is
activated, it can be configured to detect:
>

>

RELAY SETTING USING MICOM S1


>

>

P920 Technical Data Sheet

P921

an over voltage on the 3 simultaneous phases (logic


"AND") or on at least one of the phases (logic "OR") for
the "Over voltage" function
an under voltage on the 3 simultaneous phases (absence
of voltage with the "AND" logic) or on at least one of the
phases (logic "OR") for the "Under voltage" function
The MiCOM P921, P922 and P923 relays provide a
programmable hysteresis (drop- out / pick-up ratio) as a
percentage of the under voltage and over voltage pick-up
values.
The P923 provides a settable under voltage block of all
the protection and control elements based on the
frequency.

ZERO-SEQUENCE OVERVOLTAGE

LOGIC EQUATIONS

Three thresholds are available: each one can be


independently activated or deactivated. Depending on the VT
configuration, MiCOM P921, P922 and P923 relays will
operate from the zero sequence voltage, which is calculated
internally, or from the residual voltage, which is measured
directly.

NEGATIVE SEQUENCE
OVERVOLTAGE
Two thresholds are available: each one can be independently
activated or deactivated. This function is based on the
negative-sequence component of the voltage, which is
calculated internally and displayed on the screen of the front
panel: It is designed to detect any voltage unbalance condition.

INPUTS/OUTPUTS/ PROGRAMMABLE
LEDs

POSITIVE SEQUENCE
UNDERVOLTAGE

All logic inputs, output contacts (excluding the RL0 changeover


output contact, dedicated to the "relay failed" function) and the
4 LEDs of the MiCOM P921, P922 and P923 relays can be
programmed. This affects in particular all logic signals
(instantaneous, time delayed) in the relays which can be
combined with the different output contacts and LEDs. The
output contacts can also be programmed to be latched.

Two thresholds are available: Each one can be


independently activated or deactivated. This function is based
on the positive phase sequence component of the voltage,
which is calculated internally.

FREQUENCY PROTECTIONS

BLOCKING LOGIC

The following frequency based protection functions are


available. Frequency protection functions are inhibited below a
certain level of the measured secondary voltage (adjustable
level in P923).

Operation of the different protection elements of P92x can be


coordinated with other devices in the system. Two blocking
inputs are independently configurable. When active, they
freeze the associated protection timers and when they dropoff, they re-impose the initial value if the fault conditions are
still present.

UNDER/OVERFREQUENCY
Six thresholds are available: Each one can be configured to
detect an under or over frequency within the range [fn - 10Hz,
fn + 10Hz], where fn is the nominal frequency selected (50Hz
or 60Hz). A definite timer is assigned to each threshold.

SETTING GROUPS FOR PROTECTION


FUNCTIONS

RATE OF CHANGE OF FREQUENCY

The MiCOM P922 and P923 relays have two independent


setting groups, which can be used to adapt the protection
functions to different operating conditions. The two groups can
be switched by activating a dedicated logic input, or by the
operator via the front panel, or locally (RS232 port) or remotely
(RS485 port).The switch from one setting group to another will
only take effect if no protection or automation functions are
running, to prevent unwanted tripping.

Six thresholds are available: Each can be configured


independently within the range [-10 Hz/s, +10 Hz/s].
These functions are based on the calculation of the
instantaneous rate of change of frequency over a settable
integration time (number of cycles).

MEASUREMENTS

PROGRAMMABLE LOGIC
EQUATIONS

Depending on the configuration of the VTs connected to


MiCOM P921, P922 and P923 relays, the following values will
be measured and displayed as true RMS values on the back-lit
screen:

Two programmable logic equations (AND) are available with


P921 and P922 relays. Four programmable logic equations
(AND) are available with P923. A pick-up timer and a drop-off
timer can be assigned to each equation. These equations can
be programmed directly from the front panel of the relay.

P920 Technical Data Sheet

>
>
>
>

DISTURBANCE RECORDS

phase-to-neutral voltages Ua, Ub, Uc


phase-to-phase voltages Uab, Ubc, Uca
residual voltage Vo
frequency.

Five disturbance records, each lasting 2.5 seconds, can be


stored in non-volatile memory by MiCOM P922 and P923
relays. The sampling frequency is fixed at 32 samples per
cycle. The event that triggers the recording can be configured:
Instantaneous signals, time-delayed signals, or activation
of a dedicated logic input.

In addition, the MiCOM P922 and P923 relays


calculate the following values internally:
>
>
>
>

positive sequence voltage


negative sequence voltage
peak values of phase-to-neutral or phase-to-phase
voltages
rolling values of phase-to-neutral or phase-to-phase
voltages

FREQUENCY DISTURBANCE
RECORDS
One frequency disturbance record, lasting 20 secs can be
stored in non-volatile memory by the MiCOM P923 relay. The
sampling frequency is fixed at 1 sample per cycle. The
mechanism that triggers the recording can be configured:
instantaneous or time delayed tripping, activation of a
dedicated logic input or time delayed logic equation signal.

All measurements are available locally and remotely.

LOGS AND RECORDS

CIRCUIT BREAKER STATUS &


CONTROL

All event, fault and disturbance records are time-stamped to


1ms by the internal real time clock. In the event of a loss of
auxiliary power, a lithium battery is used to save the records,
the date and the time. Monitored at regular intervals, the
battery can be easily accessed from the front panel if it has to
be replaced.
All records can be retrieved locally, using the MiCOM S1
setting software (RS232 port), or remotely (RS485 port).

With MiCOM P921, P922 and P923 relays, the circuit breaker
can be controlled manually via logic inputs (AUX1 and AUX2),
with local or remote communication: the opening and closing
commands will therefore activate the programmed output
contacts. The LEDs can be programmed to indicate the status
of the circuit breaker.

EVENT RECORDS

CIRCUIT BREAKER MAINTENANCE

Any change of state of logic inputs, output contacts or


protection functions will be recorded in the non-volatile
memory of the MiCOM P922 and P923 relays, with a
maximum of 75 events. When the memory is full, the oldest
events will be deleted, which will increase the storage capacity
for more recent events. Each event can be retrieved locally to
a PC using the MiCOM S1 support software through front
RS232 port or remotely using the rear RS485 port.

In addition to protecting and controlling the electrical network,


the P922 and P923 relays provide preventive and curative
maintenance of the circuit breakers. The MiCOM P922 and
P923 relays monitor the opening / closing time of the circuit
breaker and monitor the number of operations carried out. An
alarm is triggered as soon as the maximum opening or closing
time, or the maximum permitted number of operations is
exceeded.
DISTURBANCE RECORD ANALYSIS

FAULT RECORDS
The MiCOM P922 and P923 relays can store the last 5 faults
that have occurred in non-volatile memory. Each record
provides the following information:
>
>
>
>
>
>

date and time of fault


origin of fault (under voltage, etc.)
faulted phase(s)
magnitude of the quantity which lead to the fault
magnitude of phase-to-neutral or phase-to-phase
voltages
magnitude of the zero-sequence voltage (if available)

P920 Technical Data Sheet

COMMUNICATIONS

USER INTERFACE

Two communication ports are available on MiCOM P921,


P922 and P923 relays: A rear RS485 port for remote
communication and a local front RS232 port for local
communication. A MiCOM S1 software provided for relay
setting, record retrieving and analysis is fully Windows TM
compatible. This support Software allows easy setting of any
MiCOM relay model including P92x.

The user interface for MiCOM P921, P922 and P923 relays
comprises:
> back-lit, 2 x 16 characters LCD display,
> four dedicated LEDs to provide information such as
"Trip", "Alarm", "Warning" and "Relay Healthy"
> four programmable LEDs: Each one lights up when
protection information is displayed, or if a logic input state
changes
> five tactile keys for scrolling through the menus and
entering settings the pull-down structure of the menus
enables quick and easy access to required information
> 1 key for reading and one for acknowledging alarms

REMOTE COMMUNICATION
The P921, P922 and P923 relays can be ordered with any one
of the following communication protocols.
>
>
>
>

HARDWARE & CASE

MODBUS
IEC 60870-5-103
Courier(K bus).
DNP3.0

All the models of the MiCOM P92x range have a 4U


draw out metal case, and can be flush-mounted in
switchboard or panel or rack-mounted. External connections
are made via MIDOS type terminal blocks. Each connection
includes two 4.8 mm Faston and one M4 screw fixing.

The remote RS485 port can be connected to any SCADA or


digital control system to access settings, measurements and
alarms as well as all records.

BATTERY BOX
An optional external battery box type MiCOM E1 can be used
to set the relay without the need to provide an auxiliary supply.

LOCAL COMMUNICATION
The RS232 port on the front panel of MiCOM P921, P922 and
P923 relays has two functions:
>

>

EXTERNAL BATTERRY BOX

to download a software version to the relay (upgrade,


change the language setting, modify the remote
communication protocol, etc.)
to connect a PC which has the setting software

COMMUNICATION INTERFACES

P920 Technical Data Sheet

TECHNICAL DATA

TYPE TESTS
Insulation

MECHANICAL SPECIFICATIONS

Per IEC 60255-5: 2000,


Insulation resistance > 100MW at 500Vdc
(Using only electronic/brushless insulation tester).

Design
Modular MiCOM Px2x platform relay:
P921, P922 & P923 Case 20TE 4U
Weight approx.
1.7 Kg

High Voltage (Dielectric) Withstand


(i) Per IEC 60255-5: 2000, 2 kV rms AC, 1 minute:
Between all case terminals connected together, and the case
earth, and between all terminals of independent ircuits (RS232
ports excepted).

Mounting
Rack or flush mounting.
Connections

1kV rms AC for 1 minute, across open watchdog

Rear (double faxt on + M4 screw per connection)


Full draw-out with automatic CT shorting in the case of the
relay.

contacts.
1kV rms AC for 1 minute, across open contacts of
changeover output relays.

Enclosure Protection

Impulse Voltage Withstand Test

Front Panel: IEC 529: IP 52 and IK 07


Rear connection: IP 10

Per IEC 60255-5: 2000


1.2 / 50 s, peak value: 5 kV, 0.5J
Between all terminals, and all terminals and case earth.

Dimensions
See dimensions diagram.

Electromagnetic Compatibility (EMC)

PC Interface
DIN 41652 connector (X6),
type D-Sub, 9-pin.

1 MHz Burst Disturbance Test

ENVIRONMENTAL CONDITIONS

Immunity to Electrostatic Discharge

IEC 61000-4-12, Class 3


Per IEC 60255-22-2: 1996, Class 3 and 4

Recommended Ambient temperature range

Electrical Fast Transient bursts

Per IEC 60255-6: 1988

IEC 60255-22-4 class 4.


IEC 61000-4-4 class 4.

Operating Temperature Range:


Continuous Withstand

-25 to +55C

Limit(Note 1)

-25 to +70C.

Storage Temperature Range:

Immunity to Radiated Electromagnetic field


IEC60255-22-3 class 3.
IEC61000-4-3 class 3.

-25 to +70C

Note 1: The upper limit is permissible for a single 6 hour

Surge Immunity Test

duration within any 24 hour period.

IEC 61000-4-5, class 4.

Ambient Humidity Range

Immunity to Conducted Disturbances Induced by Radio


Frequency Fields

Per IEC 60068-2-3: 1969:


56 days at 93% relative humidity and +40 C
Per IEC 60068-2-30: 1980:
Damp heat cyclic, six (12 + 12) hour cycles, 93% RH,
+25 to +55 C

4 IEC 61000-4-6, class 3.


Power Frequency Magnetic Field Immunity
IEC 61000-4-8, class V.

Solar Radiation

EMC compliance

Avoid exposure of the front panel to direct solar radiation.

89/336/EEC
93/31/EEC

MECHANICAL ENVIRONMENT
Vibration Test

Compliance with European Commission EMC Directive.

IEC 60255-21-1, class 2.

Generic standards were used to establish conformity:

Shock and Bump Test

EN50081-2: 1994

IEC 60255-21-2, class 1.

EN60952-2: 1995
Per IEC 60529: 1989

Seismic Test

IP 52 Protection (front panel) against dust and dripping water,


IPx2 except P741 Protected against vertically falling drops of
water with the product in 4 fixed positions of 15 tilt with a flow
rate of 3mm/minute for 2.5 minutes.

IEC 60255-21-3, Class 2.


PRODUCT SAFETY
72/23/EEC
Compliance with European Commission Low Voltage
Directive. Compliance is demonstrated by reference to generic
safety standards:
EN61010-1: 1993/A2: 1995
EN60950: 1992/A11: 1997

P920 Technical Data Sheet

RATINGS

BURDENS

Voltages

Voltage circuits

Nominal voltage
57 130Vph - ph eff
220 480Vph - ph eff

Operating range
5 to 260Vph - ph eff
20 to 960Vph - ph eff

REFERENCE VOLTAGE (VN)


VN = 57 130V

<0,25 VA

VN = 220 480V

<0,36 VA

Duration
Thermal withstand
Continuous
10 seconds

(Vn = 57V 130V)


260Vph - ph eff
300Vph - ph eff

Thermal withstand
Continuous
10 seconds

(Vn = 220V 480V)


960Vph - ph eff
1300Vph - ph eff

Auxiliary supply
Nominal* : 3W
* Nominal is with 50% of the optos energised and one relay
per card energised
Optically-isolated inputs
Reference voltage

Auxiliary voltage
Nominal ranges 24 60 Vdc
Operating ranges

1972 V (Vdc)

Nominal ranges 48 150 Vdc


Operating ranges

38180 V (Vdc)

Nominal ranges 130 250 Vdc / 100 250 Vac, 50/60 Hz


Operating ranges

Current (per logic input)

24 60VDC

10mA

48 125 VDC

5mA

130 250VDC

2.5mA

PROTECTION SETTING RANGES

104 300 V (Vdc)

UNDERVOLTAGE (ANSI CODE 27)

88 300 V (Vac)

Threshold settings (secondary values)

Frequency
Nominal value 50Hz
Operating range 40 60 Hz
Nominal value 60Hz
Operating range 50 70 Hz

>

Logic inputs
All the logic inputs are optically-isolated and independent :
MiCOM P921 relay has 2 logic inputs

Nominal voltage range : 57 130V

V<= Voltage Set

0.5130.0V

V<<= Voltage Set

0.5130.0V

V<<<= Voltage Set

0.5130.0V

>

Nominal voltage range : 220 480V

MiCOM P922-P923 relays have 5 logic inputs.

V<= Voltage Set

20.0480.0V

(by step: 0.5V)

Energization of the logic inputs is realised with a DC or AC


auxiliary voltage.

V<<= Voltage Set

20.0480.0V

(by step: 0.5V)

V<<<= Voltage Set

20.0480.0V

(by step: 0.5V)

Logical ON
CORTEC

Aux. voltage :
nominal
ranges

Voltage
range

Min
voltage

Min
current
(mA)

24-60Vdc

19-60Vdc

15 Vdc

3,35 mA

48-150Vdc

32-50Vdc

25 Vdc

3,35 mA

130-250Vdc
100-250Vac

48-250Vdc

38 Vdc

2,20 mA

code

Time delay settings


Each voltage element is associated to an independent time
delay.
Each measuring element time delay can be blocked by the
operation of a user defined logic (optical isolated) input (see
Blocking logic1 or Blocking logic2 functions).

Logic input recognition time = 5 ms


Output Relay Contacts
The output contacts of the MiCOM P921-P922-P923 relays are
AgCdO dry contacts.
Make and carry :

30A for 3s

Carry :

5A continuous

Break :

DC
DC
AC
AC

:
:
:
:

50W resistive
25W inductive (L/R = 40ms)
1250VA
1250 VA inductive (cos = 0.5)

Maxima :

5A and 300V

Loaded contact :

10 000 operation minimum

Unloaded contact :

100 000 operation minimum

Operation time

< 7 ms

P920 Technical Data Sheet

Element

Time delay type

1st stage

Definite Time (DT) or IDMT

2nd stage

DT

3rd stage

DT

Inverse Time Delay Characteristic

Inverse Time Delay Characteristic

The inverse characteristic is defined by the following formula :

The inverse characteristic is defined by the following formula :

TMS

t=
V

Vs

TMS

t=
V

Vs

where :

where :
t
TMS
V
Vs
NOTE :

t
TMS
V
Vs

= operating time in seconds


= time Multiplier Setting
= applied input voltage
= relay setting voltage

this equation is only valid for

TMS

0.5100.0

TRESET (only DT)

0.00100.00s

V
ratio< than 0.95
Vs

NOTE : this equation is only valid for

(by step: 0.5)

V
Vs ratio > than 1.1

TMS

0.5100.0

TRESET (only DT)

0.00 100.00s

(by step: 0.5)

When the V> is associated with IDMT curve, the recommended


maximum setting value should be less or equal to max. setting
range divided by 20.

Definite time delay characteristics


tV<

= operating time in seconds


= time Multiplier Setting
= applied input voltage
= relay setting voltage

0.00 599.00s

tV<<

0.00 599.00s

tV<<<

0.00 599.00s

Definite time delay characteristics

Hysteresis
Hysteresis

1.02 1.05%

tV>

0.00 599.00s

tV>>

0.00 599.00s

tV>>>

0.00 599.00s

NOTE : this range is a percentage value of the pickup value of


the undervoltage elements

Hysteresis

OVERVOLTAGE (ANSI CODE 59)

NOTE : this range is a percentage value of the pickup value of


the overvoltage elements

Hysteresis

Threshold settings (secondary values)

>

Nominal voltage range : 57 130V

V>= Voltage Set


V>>= Voltage Set
V>>>= Voltage Set

>

RESIDUAL OVERVOLTAGE / NEUTRAL


DISPLACEMENT (ANSI CODE 59N)

0.5200.0V
0.5260.0V
0.5260.0V

Threshold settings (secondary values)

>

Nominal voltage range : 220 480V

V>= Voltage Set


V>>= Voltage Set
V>>>= Voltage Set

20.0 720.0V
20.0 960.0V
20.0 960.0V

(by step: 0.5V)


(by step: 0.5V)
(by step: 0.5V)

>

Time delay settings


Each voltage element is associated to an independent time
delay.
Each measuring element time delay can be blocked by the
operation of a user defined logic (optical isolated) input (see
Blocking logic1 or Blocking logic2 functions).
Element

Time delay type

1st stage

Definite Time (DT) or IDMT

2nd stage

DT

3rd stage

DT

P920 Technical Data Sheet

0.95 0.98%

10

Nominal voltage range : 57 130V


V0> Voltage set

0.5 130.0V

V0>> Voltage set

0.5 130.0V

V0>>> Voltage set

0.5 130.0V

Nominal voltage range : 220 480V


V0> Voltage set

2.0 480.0V

(by step: 0.5V)

V0>> Voltage set

2.0 480.0V

(by step: 0.5V)

V0>>> Voltage set

2.0 480.0V

(by step: 0.5V)

Time delay settings

Time delay settings

Each voltage element is associated to an independent time


delay.

Each voltage element is associated to an independent time


delay.

Each measuring element time delay can be blocked by the


operation of a user defined logic (optical isolated) input (see
Blocking logic1 or Blocking logic2 functions).

Each measuring element time delay can be blocked by the


operation of a user defined logic (optical isolated) input (see
Blocking logic1 or Blocking logic2 functions).
Element

Time delay type

1st stage

Definite Time (DT) or IDMT

2nd stage

DT

3rd stage

DT

Element

Time delay type

1st stage

Definite Time (DT) or IDMT

2nd stage

DT

Inverse Time Delay Characteristic


The inverse characteristic is defined by the following formula :

Inverse Time Delay Characteristic

TMS
t=

V2 1
V

The inverse characteristic is defined by the following formula :

TMS
t=

V0 1
V

where :
t
TMS
V2
Vs

where :
t
TMS
V0
Vs

= operating time in seconds


= time Multiplier Setting
= applied input voltage
= relay setting voltage

TMS

0,5 100.0

TRESET (only DT)

0.00 100.00s

(by step: 0.5)

0.00 599.00s

tV0>>

0.00 599.00s

tV0>>>

0.00 599.00s

0.00 100.00s

(by step: 0.5)

tV2>

0.00 599.00s

tV2>>

0.00 599.00s

95%

When the V2> is associated with IDMT curve, the


recommended maximum setting value should be less or equal
to max. withstand voltage of the VT inputs divided by 20.

95%

POSITIVE SEQUENCE UNDERVOLTAGE


(ANSI CODE 27D) ONLY P922 & P923
Threshold settings (secondary values)

NEGATIVE SEQUENCE OVERVOLTAGE


(ANSI CODE 47) ONLY P922 & P923

>

Threshold settings (secondary values)

>

tRESET (only DT)

Hysteresis fixed

When the V0> is associated with IDMT curve, the


recommended maximum setting value should be less or equal
to max. withstand voltage of the VT inputs divided by 20.

>

0,5 100.0

Hysteresis

Hysteresis
Hysteresis fixed

TMS

Definite time delay characteristics

Definite time delay characteristics


tV0>

= operating time in seconds


= time Multiplier Setting
= applied input voltage
= relay setting voltage

Nominal voltage range : 57 130V

Nominal voltage range : 57 130V

V1< Voltage set

5.0 130.0V

V1<< Voltage set

5.0 130.0V

V2> Voltage set

5.0 200.0V

>

V2>> Voltage set

5.0 200.0V

V1< Voltage set

20.0 480.0V

(by step: 0.5)

V1<< Voltage set

20.0 480.0V

(by step: 0.5)

Nominal voltage range: 220 480V


V2> Voltage set

20.0 720.0V

(by step: 0.5)

V2>> Voltage set

20.0 720.0V

(by step: 0.5)

P920 Technical Data Sheet

11

Nominal voltage range : 220 480V

RATE OF CHANGE OF FREQUENCY


(ANSI CODES 81R) ONLY P923

Time delay settings


Each voltage element is associated to an independent time
delay.
Each measuring element time delay can be blocked by the
operation of a user defined logic (optical isolated) input (see
Blocking logic1 or Blocking logic2 functions).

Threshold settings
Setting

Range

Step Size

df/dt1 threshold

10 Hz/s, +10 Hz/s

0.1 Hz/s

Element

Time delay type

df/dt2 threshold

10 Hz/s, +10 Hz/s

0.1 Hz/s

1st stage

Definite Time (DT) or IDMT

df/dt3 threshold

10 Hz/s, +10 Hz/s

0.1 Hz/s

2nd stage

DT

df/dt4 threshold

10 Hz/s, +10 Hz/s

0.1 Hz/s

Inverse Time Delay Characteristic

df/dt5 threshold

10 Hz/s, +10 Hz/s

0.1 Hz/s

The inverse characteristic is defined by the following formula :

df/dt6 threshold

10 Hz/s, +10 Hz/s

0.1 Hz/s

TMS
t=

V1 1
V

Integration time

= operating time in seconds


= time Multiplier Setting
= applied input voltage
= relay setting voltage

TMS

0,5 100.0

tRESET (only DT)

0.00 100.00s

0.00 599.00s

tV1<<

0.00 599.00s

Step Size

1 200

1 cycle

Setting

Range

Step Size

Validation

2 or 4

UNDER VOLTAGE BLOCKING

>

(by step: 0.5)

Nominal voltage range : 57-130V

protection block

>

Definite time delay characteristics


tV1<

Range

cycle number

Validation number of protection

where :
t
TMS
V1
Vs

Setting

5.0 130.0V

Nominal voltage range : 220-480V

protection block

20.0 480.0V

NOTE : For P922S the under voltage blocking threshold is


fixed to 10% of the nominal setting voltage range.

Hysteresis
Hysteresis fixed

MEASUREMENT AND RECORDS

105%

SETTINGS
The measured values are displayed on the LCD of the relay ;
th
they are true RMS values (up to the 10 harmonic) and are
primary values.

UNDER/OVERFREQUENCY
(ANSI CODES 81U/81O) ONLY P922 & P923

They can also be read through the communication ports


(RS232 or RS485).

Setting

Range

Step Size

F1 threshold

Fn 10Hz, Fn + 10Hz

0.01 Hz

tF1 (definite time delay)

0.00 599.00s

0.01s

F2 threshold

Fn 10Hz, Fn + 10Hz

0.01 Hz

tF2 (definite time delay)

0.00 599.00s

0.01s

Pre time

0.01 2.50s

F3 threshold

Fn 10Hz, Fn + 10Hz

0.01 Hz

Post time

0.01 2.50s

tF3 (definite time delay)

0.00 599.00s

0.01s

Sample rate

32 samples/cycle

F4 threshold

Fn 10Hz, Fn + 10Hz

0.01 Hz

Digital signals

Logic inputs and output contacts status

tF4 (definite time delay)

0.00 599.00s

0.01s

Trigger logic

F5 threshold

Fn 10Hz, Fn + 10Hz

0.01 Hz

tF5 (definite time delay)

0.00 599s.00

0.01s

Power on of the MiCOM relay,


Any selected protection alarm or trip,
Dedicated logic input,
Remote command.

F6 threshold

Fn 10Hz, Fn + 10Hz

0.01 Hz

tF6 (definite time delay)

0.00 599.00s

0.01s

DISTURBANCE RECORD (P922 AND P923)


The MiCOM P922-P923 is able to store up to 5 records of 2.5s
each.

NOTE : if both post- and pre-time are set equal to 2.5s, the
pre-time will be priority and equal to 2.5s. The posttime will then be equal to 0s.

Where : Fn : nominal frequency

P920 Technical Data Sheet

Fixed

12

FREQUENCY DISTURBANCE RECORD


(P923 ONLY)
The MiCOM P923 is able to store one record of 20s.

CIRCUIT BREAKER CONDITION MONITORING


Nb. Operations Alarm

0 50000

Open time alarm

0.1 5.0s

Close time alarm

0.1 5.0s

Pre time

5s (fixed)

Post time

15s (fixed)

Sample rate

1 sample/cycle (fixed)

LOGIC EQUATIONS

Digital signals

Logic inputs and output contacts status

Trigger logic

Instantaneous or time delayed tripping,


Dedicated logic input,
Logic equation,
Remote command.

2 or 4 logic equations are available.


The associated timers are :

COMMUNICATIONS
Front port

Communication Parameters (Fixed)

Protocol

Modbus RTU

Address

To be specified in the
COMMUNICATIONS menu of the
relay

Messages format

IEC60870FT1.2

Baud rate

19200 bits/s
Without

Stop bits

Data bits

0.0 3600.0s

tRESET

0.0 3600.0s

VT RATIOS
The primary and secondary rating can be independently set for
each set of VT inputs, for example the residual VT ratio can be
different to that used for the phase voltages.

FRONT PORT (RS232)

Parity

tOPERATE

Voltage ranges

Primary

Secondary

57 130V

0,1 100kV
step = 0.01kV

57 130V
step = 0.1V

220 480V

220 480V
step = 10V

220 480V
step = 10V

ACCURACY
If no range is specified for the validity of the accuracy, then the
specified accuracy shall be valid over the full setting range.

REAR PORT (RS485)

REFERENCE CONDITIONS

Rear port settings Setting options

Setting available
for:

Quantity

Remote address

0 - 255 (step = 1)

IEC / Kbus-Courier
/ Modbus RTU

General

Baud rate

9 600 or 19 200 bits/s

IEC

Baud rate

300, 600, 1200, 2400, Modbus


4800, 9600, 19 200 or
38 400 bits/s

Baud rate

64000 bits/s

Kbus

Input energising quantity

Parity

Even, Odd or
Without

Modbus RTU

Voltage

Stop bits

0 or 1 or 2

Modbus RTU

Trip pulse time

0.10 5.00s

(by step: 0.05)

P920 Technical Data Sheet

2C

Atmospheric pressure

86kPa to 106kPa

Relative humidity

45 to 75 %

Vn

5%

Frequency

50 or 60Hz

0.5%

Auxiliary supply

DC 48V or 110V

5%

MEASUREMENTS ACCURACY
Quantity

CIRCUIT BREAKER CONTROL


It is possible to control the circuit breaker via the communication
(RS232 or RS485 links).
(by step: 0.05)

20 C

AC 63.5V or 110V

CIRCUIT BREAKER STATE MONITORING


The MiCOM P921-P922-P923 relays monitor the state of the
circuit breaker using either 52a and/or 52b signals.

0.10 5.00s

Test tolerance

Ambient temperature

CONTROL FUNCTIONS SETTINGS

Close pulse time

Reference
conditions

13

Range

Accuracy

Voltage

Vn

2%

Frequency

40 - 70Hz

10mHz

PROTECTION ACCURACY
Functions

Range

Operate

Reset

Timer Accuracy

Undervoltage
protection
(V<, V<< and
V<<<)

5-130V (range 1)
20-480V (range 2)

DT : Vs 2%
IDMT : Voperate =
0.95Vs 2%

(1.02-1.05) Voperate
2%

Greater of 2% or 20ms
Greater of 5% or 40ms

Overvoltage
protection
(V>, V>> and
V>>>)

0.5-260V (range 1)
20-960V (range 2)

DT : Vs 2%
IDMT : Voperate =
1.1Vs 2%

(0.95-0.98) Voperate
2%

Greater of 2% or 20ms
Greater of 5% or 40ms

Residual
voltage
protection
(V0>, V0>>
and V0>>>)

0.5-130V (range 1)
2-480V (range 2)

DT : Vs 2%
IDMT : Voperate =
1.1Vs 2%
(if direct
measurement)

0.95 Voperate 2%

Greater of 2% or 20ms
Greater of 5% or 40ms

Under/Over
frequency

40 70Hz

DT : fs 10mHz

fs 50mHz

Greater of 2% or 20ms

NOTE :

For residual voltage protection :


0.5V 4V (range 1) :
hysteresis = Voperate 0.2V
2V 16V (range 2) :
hysteresis = Voperate 0.8V

The instantaneous operating time for


under/over frequency is 50 ms (minimum).
The instantaneous operating time for
under/over voltage is 30 ms.
No additional errors will be incurred for any
of the following influencing quantities.
Environmental

Operative range (typical only)

Temperature

-25C to +55C

Mechanical
According to :
(Vibration, Shock, IEC 60255-21-1:1988
Bump, Seismic)
IEC 60255-21-2:1988
IEC 60255-21-3:1995

Electrical

Operative range

Frequency

40 Hz to 70 Hz

Harmonics (single)

5% over the range 2nd to 17th

Auxiliary voltage range

0.8 LV to 1.2 HV (dc)


0.8 LV to 1.1 HV (ac)

Aux. supply ripple

12% Vn with a frequency of 2.fn

Power off withstand

50 ms

P920 Technical Data Sheet

14

CONNECTION DIAGRAMS

3VTs CONFIGURATION (Phase-Neutral)


A

Power supply

+
-

37
35
36

33

WD

34

Phase rotation

44
45

46
49

Programmable inputs :
EL1
EL2
EL3
EL4
EL5

+
22
_
24
26
+
_
28
17
+
_
19
21
+
_
23
25
+
_
27

RL2

RL3

16
14

RL3

RL4

20
18

RL4

RL5

3
1

RL5

RL6

7
5

RL6

RL7

9
11

RL7

RL8

13
15

RL8

See note 1

50

RL1

12
10
8

RL2

41
42
43

Output contacts programmable

6
4
2

RL1

MiCOM P92*

Watchdog

LEDs

4 programmable LEDs

*
See note 2

29
30
31

Earth
connection

Communication port RS485

32 _
(* System end resistance.
For last relay, connect 30 and 32 together).

Notes :
(1)
Additional hardware for MiCOM P922 and P923 relay
(2)
Additional hardware for MiCOM P922 and P923 relay
Scheme representing MiCOM relay off

P920 Technical Data Sheet

15

P0389ENa

3VTs CONFIGURATION (Phase-Neutral) + residual voltage


A

Power
supply

+
-

37
35
36

33

WD

34

Phase rotation

6
4
2

RL1

46
49

Programmable inputs :
EL1
EL2
EL3
EL4
EL5

+
22
_
24
26
+
_
28
17
+
_
19
21
+
_
23
25
+
_
27

RL2

16
14

RL3

RL4

20
18

RL4

RL5

3
1

RL5

RL6

7
5

RL6

RL7

9
11

RL7

RL8

13
15

RL8

See note 1

50

RL1

RL3

41

44
45

Output contacts (programmable) :

12
10
8

RL2

42
43

Watchdog

LEDs

4 programmable LEDs

*
*
See note 2

29
30
31

Earth
connection

Communication port RS485

32 _
(* System end resistance.
For last relay, connect 30 and 32 together)

Notes :
(1)
Additional hardware for MiCOM P922 and P923 relay
(2)
Additional hardware for MiCOM P922 and P923 relay
Scheme representing MiCOM relay off

P920 Technical Data Sheet

16

P0390ENa

2VTs CONFIGURATION + residual voltage


A

Power
supply

+
-

37
35
36

33

WD

34

Phase rotation

6
4
2

RL1

42
43
44
45

46
49

50

Programmable inputs :
EL1
EL2
EL3
EL4
EL5

+
22
_
24
26
+
_
28
17
+
_
19
21
+
_
23
25
+
_
27

Output contacts (programmable) :


RL1

12
10
8

RL2

41

Watchdog

RL2

RL3

16
14

RL3

RL4

20
18

RL4

RL5

3
1

RL5

RL6

7
5

RL6

RL7

9
11

RL7

RL8

13
15

RL8

See note 1

LEDs
4 programmable LEDs

*
*
See note 2

29
30
31

Earth
connection

Communication port RS485

32 _
(* System end resistance.
For last relay, connect 30 and 32 together)

Notes :
(1)
Additional hardware for MiCOM P922 and P923 relay
(2)
Additional hardware for MiCOM P922 and P923 relay
Scheme representing MiCOM relay off

P920 Technical Data Sheet

17

P0392ENa

LV connection for P92x (220-480V range)


A

Power
supply

+
-

37
35
36

33

WD

34

Phase rotation

6
4
2

RL1
A

42
43

44
45

46
49

50

Programmable inputs :

+
22
_
24
26
+
_
28
17
+
_
19
21
+
_
23
25
+
_
27

EL1
EL2
EL3
EL4
EL5

Power
supply

+
-

RL3

RL4

20
18

RL4

RL5

3
1

RL5

RL6

7
5

RL6

RL7

9
11

RL7

RL8

13
15

RL8

LEDs

4 programmable LEDs

**
See note 2

WD

44
45

46
49

EL1
EL2
EL3
EL4
EL5

RL1

RL2

RL3

16
14

RL3

RL4

20
18

RL4

RL5

3
1

RL5

RL6

7
5

RL6

RL7

9
11

RL7

RL8

13
15

RL8

See note 1

LEDs

4 programmable LEDs

**
See note 2

29
30
31

Earth
connection

Communication port RS485

32 _

Notes :
(1)
Additional hardware for MiCOM P922 and P923 relay
(2)
Additional hardware for MiCOM P922 and P923 relay
Scheme representing MiCOM relay off

P920 Technical Data Sheet

Communication port RS485

Output contacts (programmable) :

12
10
8

+
22
_
24
26
+
_
28
17
+
_
19
21
+
_
23
25
+
_
27

Earth
connection

Watchdog

6
4
2

RL2

42
43

Programmable inputs :

37
35
36

33

41

(* System end resistance.


For last relay, connect 30 and 32 together)

RL1

29
30
31

32 _

Phase rotation

RL2

16
14

See note 1

34

50

RL1

RL3

Notes :
(1)
Additional hardware for MiCOM P922 and P923 relay
(2)
Additional hardware for MiCOM P922 and P923 relay
Scheme representing MiCOM relay off

Output contacts (programmable) :

12
10
8

RL2

41

Watchdog

18

(* System end resistance.


For last relay, connect 30 and 32 together)

P0393ENa

CASES & DIMENSIONS

39 39
26 26

97

Dimensions
in mm.
168

158
Panel cut-out
Flush mounting fixing details

4 holes 3.4

103
MiCOM

49.5

49.5

4 holes 4.4 (M4 screw)

226

25.1
P921

VA = 214.50 A
Trip
Ala rm e
Equip. fail

151.2 max.

177

Auxiliary
supply
AUX. 1
AUX. 2
AUX. 3
AUX. 4

Flush mounting
P0395ENb
MiCOM P921, P922 & P923 4U 20TE

P920 Technical Data Sheet

19

MiCOM P920
GUIDE FORM SPECIFICATION
The voltage and frequency protections have to be of
entirely numerical technology and in a 4U draw out
metal case.
The following functions have to be available:
> 3 independent phase overvoltage thresholds
(instantaneous and time-delayed - ANSI 59 code)
> 3 independent phase undervoltage thresholds
(instantaneous and time-delayed - ANSI 27 code)
> Settable Hysteresis thresholds for Undervoltage
and Overvoltage functions
> 3 independent zero-sequence overvoltage
thresholds (instantaneous and time-delayed ANSI 59N code)
> programmable logic equations
> Programmable I/O
> Relay latching (ANSI 86 code)
> Display of true RMS values
> 2 setting groups
> An RS485 rear port compatible with the following
protocols: MODBUS, Courier, IEC 60870-5-103,
DNP3.0
> Records of the last 75 events, time-stamped to
1ms
> Data records relating to the last 5 faults
> Disturbance recorder with storage of 5 records,
each lasting 2.5 seconds, 32 samples per cycle
For frequency protection, the following functions have
to be added:
> 2 independent negative sequence phase
overvoltage thresholds (instantaneous and timedelayed - ANSI 47 code)
> 2 independent positive sequence phase
undervoltage thresholds (instantaneous and timedelayed - ANSI 27D code)
> Settable Hysteresis thresholds for Undervoltage
and Overvoltage functions.
> 6 independent over/underfrequency thresholds
(instantaneous and time-delayed - ANSI 81U/81O
codes)
For rate of change of frequency, the following functions
have to be added:
> 6 independent rate of change of frequency
thresholds - ANSI 81R codes
> 1 adjustable undervoltage Blocking threshold
> 4 programmable logic equations
The user interface must include the following elements:
> A 32-character alphanumeric back-lit LCD display
> An RS232 front port compatible with application
software and PC setting software
> Programmable LEDs with customised labelling

P920 Technical Data Sheet

20

ORDERING INFORMATION

MiCOM P92x - Voltage Protection Relays


P92
Relay Type
Voltage Relay
Voltage/Frequency relay
Voltage/Frequency relay with (df / dt) relay

1
2
3

Voltage Inputs
57 - 130 V
220 - 480 V

A
B

Application
Standard

Auxiliary Supply Voltage


24 - 60Vdc
48 - 150Vdc
130 - 250Vdc / 100 - 250Vac
48 - 150Vdc with 48 - 150 Vdc digital inputs voltage (special EA)
130 - 250Vdc with 130 - 250 Vdc digital inputs voltage (special EA)
125 - 250Vdc / 100 - 250Vac with 95 - 150 Vdc digital inputs voltage (special application)
Communications protocol options
Modbus
K-bus / Courier
IEC 60870-5-103
DNP3.0

1
2
3
4

User interface language options (see note 1)


French
English
Spanish
German
Italian
Russian
Polish
Portuguese (NOT YET AVAILABLE !)
Dutch (NOT YET AVAILABLE for P923 !)
Czech
Hungarian (NOT YET AVAILABLE !)

0
1
2
3
4
5
6
7
8
A
B

Case Type
Flush and/or panel mounted only

Note 1: Contact us for language availability

P920 Technical Data Sheet

A
F
M
T
U
H