Section 2

AC Machines

2.5 STANDARD TERMINAL MARKINGS AND CONNECTIONS


Note: All terminal markings and connections in this section are based on NEMA Stds. MG 1-2009, Rev. 1-2010, 2.41
or IEC Stds. 60034-8.

SINGLE-PHASE MOTORSCAPACITOR-START
NEMA NOMENCLATURE
SINGLE VOLTAGE

DUAL VOLTAGE
(MAIN AND AUXILIARY WINDING)

P1

THERMAL
PROTECTOR

THERMAL
PROTECTOR

P2
1

MAIN (RUN) WINDING

L1
1,8
1,5

MAIN (RUN) WINDING


CAP
CAP

L2
4,5
4,8

AUXILIARY (START) WINDING

High

DUAL VOLTAGE

Low

(MAIN WINDING ONLY)


P1
P2

2
3
4

High
Low

2-34

CCW
CW
CCW
CW

L1

1
1
1,3,8
1,3,5

L2

4,5
4,8
2,4,5
2,4,8

L2
4,5
4,8
2,4,5,7
2,4,6,8

Join
2&3,6&7
2&3,6&7

The direction of shaft rotation can be determined by facing


the end of the motor opposite the drive.

Auxiliary winding is always at low-voltage rating; capacitor


should be rated accordingly.
Rotation

L1
1,8
1,5
1,3,6,8
1,3,5,7

Rotation: CCW Counterclockwise



CW Clockwise

8
AUXILIARY (START)
WINDING
5
CAP SWITCH

Voltage

Rotation
CCW
CW
CCW
CW

The switch in the auxiliary winding circuit has been omitted


from this diagram. The connections to the switch must be
made so that both auxiliary windings become de-energized
when the switch is open.

1
MAIN (RUN) WINDING

2
3
4
8
7
6
5

Capacitors in auxiliary windings are rated for lower voltage.


Voltage

THERMAL
PROTECTOR

P2
1

4
8
AUXILIARY (START)
WINDING
5
CAP SWITCH

ROTATION
CCW
CW

P1

Join

2&3&8
2&3&5

TERMINAL MARKINGS IDENTIFIED BY COLOR


1-Blue

2-White
3-Orange
4-Yellow

5-Black
P1-No color assigned
6-No color assigned P2-Brown
7-No color assigned
8-Red

Reference: NEMA Stds. MG 1-2009, Rev. 1-2010, 2.41.


Note: May not apply for some definite-purpose motors.

EASA Technical Manual 1996-2012, Electrical Apparatus Service Association, Inc.

Section 2

AC Machines

STANDARD TERMINAL MARKINGS AND CONNECTIONS


THREE-PHASE MOTORSPART-WINDING START
3

NEMA NOMENCLATURE6 LEADS

Delta

Delta
7

9
3

Wye

Double Delta
OPER.
(ExtendedMODE
Delta)L1

L2
2
2,8

START 1
RUN
1,7

OPER.
MODE L1
START 1
RUN
1,7

Operating mode

Wye

Start

L3
3
3,9

L2

1,7

2,8

Run

L1

L2
2
2,8

L3
3
3,9

OPEN
7,8,9

L3

Open
7,8,9

3,9

OPEN
7,8,9

NEMA NOMENCLATURE9 LEADS


WYE-CONNECTED (LOW VOLTAGE ONLY)
T1

Motor leads

T2

T3

T7

T8

T9

Together

4&5&6

NEMA NOMENCLATURE12 LEADS

12

NEMA
6

Voltage

Low

W6
4

3
11

High*

W5
W2

7
10

85

Delta

W1
V6

T1

T2

T3

T7

T8

T9

1,12

2,10

3,11

6,7

4,8

5,9

12

U1

10

11

IEC
U2
U5

V5 V2

U6
V1

Open

4-7, 5-8, 6-9

*Not suitable for one-circuit internal connections.

EASA Technical Manual 1996-2012, Electrical Apparatus Service Association, Inc.

2-35

Section 2

AC Machines

STANDARD TERMINAL MARKINGS AND CONNECTIONS


THREE-PHASE MOTORSPART-WINDING START (CONTINUED)
NEMA AND IEC NOMENCLATURE12 LEADS
SINGLE VOLTAGE OR LOW VOLTAGE OF DUAL-VOLTAGE MOTORS

12

NEMA
6

IEC

2-36

T1

1,6

U1,W1

W6
4

3
11

NEMA

85
T2

2,4

V1,U2

U1

W5
W2

7
10

W1
V6

T3

3,5

W1,V2

IEC
U2
U5

V5 V2
T7

7,12

U5,W6

U6
V1
T8

8,10

V5,U6

T9

9,11

W5,V6

EASA Technical Manual 1996-2012, Electrical Apparatus Service Association, Inc.

Section 2

AC Machines

STANDARD TERMINAL MARKINGS AND CONNECTIONS


THREE-PHASE MOTORSREDUCED-CURRENT STARTING
NEMA NOMENCLATURE6 LEADS

NEMA NOMENCLATURE9 LEADS

WYE-CONNECTED

DELTA-CONNECTED

L1

L2

L3

1
1
1

1
9

Operating mode

Run

L2

2-step starting (1/21/2)


Two 3-pole contactors
L3

Open

1,7

2,8

3,9

8&9

Operating mode

Start
Run

2
3

7
8

Operating mode

Start
Run

L2

L3

Open

Mid-step

1,7

2,8

1,7

2,8

3,9

2
2

L1

L2

L3

Open

1,7

2,8

3,9

1,7

L1

L2

L3

8&9

2-step starting (1/21/2)


4- and 2-pole contactors

L1
1

7
8

2
2

L1

L2

L3

Open

1,7

2,8

3,9

1,7

1 1

2
3
3

2
3

2
3

Operating mode

Run

3-step starting
(1/21/31/6)wye connected
(1/21/61/3)delta connected
3-, 2- and 1-pole contactors
Start

DELTA-CONNECTED

L3

L2

1
1

2
8

WYE- OR DELTA-CONNECTED
L1

L3

L1

1,7

L2

2-step starting (2/31/3)


4- and 2-pole contactors
Start

L1

8&9

DELTA-CONNECTED

8&9

L1

L2

L3

7
1

3-step starting (1/21/61/3)


3-, 2- and 1-pole contactors
Operating mode

L1

Mid-step

1,7

Start
Run

EASA Technical Manual 1996-2012, Electrical Apparatus Service Association, Inc.

6
3
1

9
3

7 2
8

L2

L3

Open

2,8

2,8

1,7

2,8

3,9

7&9

2-37

Section 2

AC Machines

STANDARD TERMINAL MARKINGS AND CONNECTIONS


THREE-PHASE MOTORSSINGLE-SPEED
NEMA NOMENCLATURE6 LEADS
SINGLE VOLTAGE
EXTERNAL
WYE CONNECTION
L1
1

L2
2

L3

4&5&6

L2

1,6

3,5

4
7

2
6

L3

2,4

SINGLE VOLTAGE
EXTERNAL
DELTA CONNECTION
L1

DUAL VOLTAGE
WYE-CONNECTED

Join

NEMA NOMENCLATURE9 LEADS

4
5

Voltage

High
Low

4
6

L2

L3

1,7

2,8

3,9

Operating
mode

Start
Run

Voltage

High
Low

L2

L3

Delta

1,6

2,4

3,5

Wye

Dual voltage*

Connection

L1

L2

L3

Delta

1,6

2,4

3,5

Wye

4&5&6

Join

4&5&6

9
6

Single voltage
L1

4&7,5&8,6&9

Connection

Join

4
5

DUAL VOLTAGE
WYE-CONNECTED

85

L1

SINGLE AND DUAL VOLTAGE


WYE-DELTA CONNECTIONS

3
Voltage

High
Low

L1

L2

L3

1,6,7

2,4,8

3,5,9

Join

4&7,5&8,6&9

Join

4&5&6

*Voltage ratio: 1.732 to 1.

2-38

EASA Technical Manual 1996-2012, Electrical Apparatus Service Association, Inc.

Section 2

AC Machines

STANDARD TERMINAL MARKINGS AND CONNECTIONS


THREE-PHASE MOTORSSINGLE-SPEED
NEMA NOMENCLATURE12 LEADS

IEC NOMENCLATURE6 LEADS

DUAL VOLTAGE
EXTERNAL WYE CONNECTION

SINGLE AND DUAL VOLTAGE


WYE-DELTA CONNECTIONS

1
4
7

3
Voltage
High
Low

10
12
11

L1

L2

L3

1,7

2,8

W1

Start

4&7,5&8,6&9,
10&11&12

Volt. Conn.
High

Low

6
85

3
2

L1

L2

L3

Wye

Delta

1,12

2,10

3,11

Wye

1,7

2,8

3,9

Delta

1,6,7,12 2,4,8,10 3,5,9,11

L2

L3

V1

Join

W1

U1,W1 V1,U2 W1,V2


Dual voltage*

Conn.

L1

L2

U1

Delta

L3

V1

U2&V2&W2

Join

W1

U2&V2&W2

U1,W2 V1,U2 W1,V2

1
4

11

V1

*Voltage ratio: 1.732 to 1.

12

4
7

L1

Wye

Low

DUAL VOLTAGE
WYE-CONNECTED START
DELTA-CONNECTED RUN

V2

U1

Delta

High

U2

Single voltage

Wye

Run

4&5&6,
10&11&12

U1

W1

V1

Operating
mode
Conn.

Join

3,9

U2
V2

W2

Voltage

10
11
12

W2

U1

IEC NOMENCLATURE12 LEADS


7

DUAL VOLTAGE WYE-CONNECTED START


DELTA-CONNECTED RUN

10
2

8 5

U1

Join

4&7,5&8,6&9,
10&11&12
4&7,5&8,6&9
4&5&6,
10&11&12

W6

U2
U5

W1

W5
W2

W6

Volt. Conn.
High

Low

U6
V6

U2
U5

W5
W2
V5
V2

W1
V1

V6

L1

L2

L3

Wye

U1

V1

W1

Delta

U1,W6

V1,U6

W1,V6

Wye

U1,U5

V1,V5

W1,W5

Delta

U1,U5,
W2,W6

V1,V5,
U2,U6

W1,W5,
V2,V6

EASA Technical Manual 1996-2012, Electrical Apparatus Service Association, Inc.

U1

V5 V2

U6
V1

Join

U2&U5,V2&V5,
W2&W5,U6&V6&W6
U2&U5,V2&V5,
W2&W5
U2&V2&W2,
U6&V6&W6

2-39

Section 2

AC Machines

NON-STANDARD TERMINAL MARKINGS AND CONNECTIONS


THREE-PHASE MOTORSSINGLE-SPEED
NOMENCLATURE FORMERLY USED IN GREAT BRITIAN6 LEADS
SINGLE AND DUAL VOLTAGE
WYE-DELTA CONNECTIONS

C1

A2

C2

A1

C2

B1

B1

B2

Single voltage

Operating mode

Connection

Start

Wye

Run

High

A1

C1

Delta

L1

A2

A2,C1

Connection

Wye

Low

Delta

L1

A2

A2,C1

B2

L2

L3

B2

B2,A1

Dual voltage*

Voltage

A2

Join

C2

A1&B1&C1

L3

Join

C2,B1

L2

B2

C2

B2,A1

C2,B1

A1&B1&C1

*Voltage ratio: 1.732 to 1.

NOMENCLATURE FORMERLY USED IN GREAT BRITIAN12 LEADS


DUAL VOLTAGE
WYE-CONNECTED START, DELTA-CONNECTED RUN

A4

C1

A3
A2

C4
Voltage
High
Low

2-40

Connection

Wye

C3

C2

C1

L1

A4

A3
A2

C2
C3

A1
B1

A4

B2
B3

C4

B1

B2 B3

A1
B4

B4

L2

B4

L3

Join

C4

A3&A2,B3&B2,C3&C2,A1&B1&C1

Delta

A4,C1

B4,A1
B4,B2

C4,C2

A3&B3&C3, A1&B1&C1

Delta

A4,A2,C1,C3

B4,B2,A1,A3

C4,C2,B1,B3

Wye

A4,A2

C4,B1

A3&A2,B3&B2,C3&C2

EASA Technical Manual 1996-2012, Electrical Apparatus Service Association, Inc.

Section 2

AC Machines

NON-STANDARD TERMINAL MARKINGS AND CONNECTIONS


THREE-PHASE MOTORSSINGLE-SPEED
NOMENCLATURE FORMERLY USED IN EUROPE6 LEADS
SINGLE AND DUAL VOLTAGE
WYE-DELTA CONNECTIONS

Operating mode

Start
Run

High

Single voltage

Connection

L1

L2

L3

Delta

U,Z

V,X

W,Y

Wye

Dual voltage*

Voltage

L1

L2

L3

Delta

U,Z

V,X

W,Y

Join

Connection

Wye

Low

X&Y&Z

Join

X&Y&Z

*Voltage ratio: 1.732 to 1.

NOMENCLATURE FORMERLY USED IN GERMANY12 LEADS


DUAL VOLTAGE
WYE-CONNECTED START, DELTA-CONNECTED RUN
Ua

Zb

Xa
Ub

Wa

Voltage
High
Low

Connection

Wye

Delta

Za

Wb

Zb

Vb

Wa
Ya

L1

L2

Ua

Xa
Ub

Wb
Za

Xb
Yb

Ua

Yb

Vb Ya

Xb
Va

Va

Va

L3

Join

Wa

Xa&Ub,Ya&Yb,Za&Wb,Xb&Yb&Zb

Wye

Ua,Ub

Ua,Zb

Va,Xb
Va,Vb

Wa,Wb

Wa,Yb

Xa&Ya&Za,Xb&Yb&Zb

Delta

Ua,Ub,Za,Zb

Va,Vb,Xa,Xb

Wa,Wb,Ya,Yb

EASA Technical Manual 1996-2012, Electrical Apparatus Service Association, Inc.

Xa&Ub,Ya&Vb,Za&Wb

2-41

Section 2

AC Machines

STANDARD TERMINAL MARKINGS AND CONNECTIONS


THREE-PHASE MOTORSTWO-SPEED, SINGLE WINDING
NEMA NOMENCLATURE6 LEADS

IEC NOMENCLATURE6 LEADS

CONSTANT TORQUE CONNECTION

CONSTANT TORQUE CONNECTION

2U

1V

High
Low

L1

L2

L3

Typical
connection

1&2&3 Join 2 wye

4-5-6 Open 1 delta

Low

1V 1W 2U-2V-2W Open 1 delta

High

2W 2U
1U

High
Low

1V

Typical
connection

1&2&3 Join 2 wye

4-5-6 Open 1 delta

1V 1W 2U-2V-2W Open 1 wye

2W 2U
1U

High
Low

2-42

L1

L2

L3

2V

1U&1V&1W Join 2 wye

CONSTANT POWER, SIX TERMINALS


1W

2W

Low-speed horsepower is one-fourth of high speed horsepower.*


Speed

Typical
connection

Low

High

L3

2W

L2

1
2

1U

Speed L1

4
3

1W

2V

CONSTANT HORSEPOWER CONNECTION

1U&1V&1W Join 2 wye

VARIABLE TORQUE CONNECTION

Low-speed horsepower is one-fourth of high speed horsepower.*


L3

2V

1
2

L2

L3

2U

L1

Typical
connection

L2

Speed

2W

Speed L1

VARIABLE TORQUE CONNECTION

1U

2V

Low-speed horsepower is half of high speed horsepower.*


Speed

1W

Typical
connection

1-2-3 Open 1 delta

4&5&6 Join 2 wye

1U

2U
1W

2U
2V

1V

2W

1V

1U

2V

Typical
Speed L1 L2 L3
connection
High 2U 2V 2W 1U&1V&1W Open Series delta
Low 1U 1V 1W 2U&2V&2W Join Parallel wye

EASA Technical Manual 1996-2012, Electrical Apparatus Service Association, Inc.