You are on page 1of 50

JOB NO.

PGESCo Drawing No.

Rev.

10040

Subject/Title:

Calculation of Short-Circuit Currents, Load Flow and Voltage Drop

Proj.-Kennz.
Project Code

Document No.

UAS

EGY263

Handhabung:
Handling:

Inhaltskennzeichen
Contents Code

BN02

Nur fr internen Gebrauch


For Internal Use Only

Zhl-Nr.
Serial No.

B
Seitenzahl:
Pages:

UNID

700021
26

10 691 410
Anhnge:
Attachments:

10

Prfvermerke fr Erstausgabe / First Issue Document Review


Abteilung / Department:

SINUS GmbH

Abteilung / Department:

PG W741

Ersteller / Author:

sig. H. Specht

Geprft / Reviewed by:

sig. N. Kaiser

Datum / Date:

2005-07-29

Datum / Date:

2005-07-29
PG W-TAL

Abteilung / Department:

Projektleitung/Project Management:

Freigegeben / Released by:

Freigegeben / Released by:

sig. R. Gams

Datum / Date:

Datum / Date:

2005-07-29

Bemerkungen / Remarks:

Ausgabestnde / Document Issues


Dokumentenstand
Document index

Ausgabedatum
Date of issue

Erluterung des Dokuments, ggf. Seitenangabe


Description of document / page number if appropriate

2005-07-29 First issue / Erstausgabe

2005-08-04

Supplement with max. and min. short-circuit current


calculations.
2005-10-21
Results correspond to measured values of BAT and
BBT transformers.

Siemens

Freigabe / Release
technical
commercial

Calculation of MVA rating for generator transformer


according to IEEE C57.116-1989 added

Weitergabe sowie Vervielfltigung, Verbreitung und/oder Bearbeitung dieses Dokumentes, Verwertung und Mitteilung seines
Inhaltes sind verboten, soweit nicht ausdrcklich gestattet. Zuwiderhandlungen verpflichten zu Schadenersatz. Alle Rechte
fr den Fall der Patenterteilung, Gebrauchsmuster- oder Geschmacksmustereintragung vorbehalten.
Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders will be held liable for payment of damages. All
rights created by patent grant or registration of a utility model or design patent are reserved.
2005-08-04_EGY263-BN02-B-700021_Cover-Sheet_Rev_B

PG W741

Document No.:
Project:

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS,
LOAD FLOW AND VOLTAGE DROP

Status/Date:
Page:

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
1 of 26

NEW TALKHA POWER STATION


750 MW Combined Cycle Project

Calculation of Short-Circuit Currents,


Load Flow and Voltage Drop

Report

Editor: H. Specht
Order No: si0368

Document No.:

PG W741

Project:

SINUS GmbH

Status/Date:

CALCULATION OF SHORT-CIRCUIT CURRENTS,

Page:

LOAD FLOW AND VOLTAGE DROP

I.

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
2 of 26

Revisions

The revision history of the project is given on this page.

REVISION SHEET
Rev.

Date

2005-07-29

2005-08-04

2005-10-21

Table I:

Report

Caused by

Reason for Modification

First issue
Calculation of MVA rating for generator transformer
according to IEEE C57.116-1989 added.
Supplement with maximum and minimum short-circuit
current calculations.
Results correspond to measured values of BAT and
BBT transformers

Revisions

Editor: H. Specht
Order No: si0368

PG W741

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS,
LOAD FLOW AND VOLTAGE DROP

II.

Document No.:
Project:
Status/Date:
Page:

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
3 of 26

Contents List

INTRODUCTION .................................................................................................................. 5

SCOPE OF INVESTIGATION................................................................................................. 5

BASIS OF INVESTIGATION ................................................................................................. 6

3.1

Simulation Model ............................................................................................................................................ 6

3.2

Data Base ......................................................................................................................................................... 6

SHORT CIRCUIT CALCULATIONS ........................................................................................ 8

4.1

Short-Circuit Currents ................................................................................................................................... 8

4.2
Symbols and Remarks on Diagrams.............................................................................................................. 9
4.2.1
Three-Phase and Two-Phase Short-Circuit Currents................................................................................. 9
4.2.2
Single-Phase Short-Circuit Currents ....................................................................................................... 10
4.3

Investigated Operation Mode Configurations ............................................................................................ 11

4.4
Maximum Short-Circuit Currents .............................................................................................................. 13
4.4.1
Conditions for Calculation ...................................................................................................................... 13
4.4.2
Calculated Cases ..................................................................................................................................... 14
4.4.3
Results..................................................................................................................................................... 15
4.5
Minimum Short-Circuit Currents ............................................................................................................... 16
4.5.1
Conditions for Calculation ...................................................................................................................... 16
4.5.2
Calculated Cases ..................................................................................................................................... 17
4.5.3
Results..................................................................................................................................................... 17
5

VOLTAGE DROP CALCULATION FOR MOTOR START-UP ................................................... 18

5.1

Start-Up of Medium Voltage Motor 00LAC11 (HP FD WTR)................................................................. 18

5.2

Conditions for Calculation ........................................................................................................................... 18

5.3

Results ............................................................................................................................................................ 19

CHECK OF TRANSFORMER RATING FOR GENERATOR TRANSFORMER (BAT) .................. 20

6.1

Dependency of Power Output and Rating from Temperature.................................................................. 20

6.2

Reactive Capability Limits of Generator .................................................................................................... 21

6.3

Results ............................................................................................................................................................ 22

CHECK OF VOLTAGE PROFILE FOR AUXILIARY TRANSFORMER (BBT) ............................ 25

7.1

Conditions for Calculations.......................................................................................................................... 25

7.2

Summary of Results ...................................................................................................................................... 26

Report

Editor: H. Specht
Order No: si0368

PG W741

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS,

Document No.:
Project:
Status/Date:

LOAD FLOW AND VOLTAGE DROP

Page:

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
4 of 26

III. List of Annex


Annex 1:

Table of Input Data

Annex 1.1:

Switchgear

Annex 1.2:

Cables

Annex 1.3:

Induction Motors

Annex 1.4:

Synchronous Machines

Annex 1.5:

MV / LV Switchgear Cubicles for Motor Feeders

Annex 1.6:

MV / LV Switchgear Cubicles for Transformer Feeders

Annex 1.7:

MV / LV Switchgear Cubicles for Incoming and Coupling Feeders

Annex 1.8:

MV / LV Switchgear Cubicles for Synchronous Machines

Annex 2:

Single Line Diagram

Annex 3:

Calculation of Maximum Three-Phase Short-Circuit Currents

11 Pages

2 Pages

1 Page

Calculated Case 1
Annex 4:

Calculation of Maximum Single-Phase Short-Circuit Currents

1 Page

Calculated Case 2
Annex 5:

Calculation of Minimum Three-Phase Short-Circuit Currents

3 Pages

Calculated Cases 1 to 3
Annex 6:

Calculation of Minimum Two-Phase Short-Circuit Currents

3 Pages

Calculated Cases 4 to 6
Annex 7:

Calculation of Minimum Single-Phase Short-Circuit Currents

3 Pages

Calculated Cases 7 to 9
Annex 8:

Calculation of Short-Circuit Impedances for Minimum ShortCircuit Currents (0.4 kV)

1 Page

Annex 9:

Voltage Drop Calculation for Motor Start-Up of MV Motor

1 Page

Annex 10:

Check of Transformer Rating for Generator Transformer (BAT)

Report

3 Pages

Editor: H. Specht
Order No: si0368

PG W741

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS,
LOAD FLOW AND VOLTAGE DROP

Document No.:
Project:
Status/Date:
Page:

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
5 of 26

Introduction

In this study the maximum and minimum short-circuit currents at 220 kV switchgear, 16.5 kV generator
bus ducts and the medium voltage switchgear (6.3 kV) as well as the low voltage switchgear (0.4 kV) of
the unit auxiliary system of the New Talkha 750MW CCPP power plant are calculated. For calculation of
maximum three-phase short-circuit currents the short-circuit current contribution of 6.3/0.4 kV auxiliary
system is considered. Load flow calculations are performed in order to determine the voltage drop during
motor start-up, to check the rating of generator transformer (BAT) and to evaluate the voltage profile for
the auxiliary transformer (BBT).
In the dimension and selection of electrical equipment for a power plant it is necessary to take into
account that the planed and installed electrical equipment has to cope with the stress, which arises on
the occurrence of a fault (short circuit) in the considered system. The magnitude of short-circuit currents
is generally many times higher than the rated currents of electrical elements.
To fulfil these requirements, several calculation cases are performed. This documentation takes the focus
on operation modes which are relevant for the description of worst case design criteria.

Scope of Investigation

According to IEC EN 60909-0:2001 the network investigation consists of following short-circuit


calculations:

Maximum three-phase short-circuit currents

Maximum single-phase short-circuit currents

Minimum three-phase short-circuit currents

Minimum two-phase short-circuit currents

Minimum single-phase short-circuit currents

Additional the network investigation include voltage drop calculation for the largest 6.3 kV medium
voltage motor 00LAC11 (HP Feedwater Pump).
The rating of the generator transformer (11BAT01/12BAT01) is investigated for overexcited operation
(PF=0.85/lag) and underexcited operation (PF=0.92/lead and PF=0.93/lead) of the generator
(11MKA/12MKA) with consideration of the auxiliary load.
For the auxiliary transformer (11BBT01/12BBT01) the maximum and minimum operating voltages are
determined to fulfil the requirements concerning voltage range at 6.3 kV auxiliary system for different
loading conditions.
The short-circuit calculation and load flow calculations were carried out with the software package
NETOMAC.

Report

Editor: H. Specht
Order No: si0368

Document No.:

PG W741

Project:

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS,

Status/Date:

LOAD FLOW AND VOLTAGE DROP

Basis of Investigation

3.1

Simulation Model

Page:

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
6 of 26

The simulation model for the calculations comprises:


220 kV interconnected system as equivalent impedance.
313 MVA generators 11MKA/12MKA with unit transformers 11BAT01/12BAT01.
6.3 kV switchgear (10BBE, 10BBF, 11BBE, 11BBF, 12BBE and 12BBF).
0.4 kV switchgear (10BFJ, 10BFK, 10BJJ, 10BMA, 10BMB, 11BFE, 11BFG, 11BFH, 11BJH, 11BME,
12BFE, 12BFG, 12BFH, 12BJH and 12BME).
MV-motors at 6.3 kV switchgear are considered as individual motors.
LV-motors at 0.4 kV switchgear are considered as equivalent lumped LV-motors.
6.3 kV cables and 0.4 kV cables.

3.2

Data Base

The data of the study is based on the data provided by Siemens PG.
For the purpose of calculation the 220 kV network is modelled by an equivalent impedance which is
derived from the maximum and minimum initial symmetrical short-circuit currents present on the
220 kV substation.
The LV motors connected to each LV main distribution including their connection cables are treated as an
equivalent motor. For the equivalent lumped LV-motors the following data were assumed for short-circuit
calculations:

Un

0.4 kV

rated voltage of low voltage motors in kV

Ia/In

6.0 p.u.

ratio of locked-rotor current to rated motor current in p.u.

cos()n

0.84

rated power factor

etan

0.95 p.u.

rated efficiency in p.u.

The lumped equivalent LV motor for each switchgear is determined based on the consumer list. For LV
switchgear with missing motor data the total motor load is assumed in such a way that the utilization of
the LV transformer with motor load is 50% of rated power (worst case). If the incoming transformer of a
LV switchgear is out of service the tie feeder will be closed and the incoming transformer from the other
LV switchgear will supply the complete load of both LV switchgear. Therefore, the LV transformers are
designed so that utilization for normal operation is less than 50% of rated power. With the assumption
that complete load is only motor load already the worst case is considered.
Missing data for MV motors (LAC, LCB and PAC) were assumed for calculations.

Report

Editor: H. Specht
Order No: si0368

Document No.:

PG W741

Project:

SINUS GmbH

Status/Date:

CALCULATION OF SHORT-CIRCUIT CURRENTS,

Page:

LOAD FLOW AND VOLTAGE DROP

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
7 of 26

The MV cables (6.3 kV) and all considered cables in the 0.4 kV low voltage system are XLPE-insulated.
For the 6.3 kV and 0.4 kV feeder cables the estimated lengths are considered. For unknown cable length
the length is set to zero.
The following cable types were taken into consideration to calculate the maximum and minimum shortcircuit currents under worst case conditions for the MV and LV auxiliary system.

Type

Cross
Section

Un

TOP

TSC

[kV]

[C]

[C]

N2XSY 10kV 3x1x240

N2XSY

3x1x240

10

90

250

N2XSY 10kV 3x1x120

N2XSY

3x1x120

10

90

250

N2XY-O 1kV 3x1x240

N2XY-O

3x1x240

90

250

Type Indication

Table 3-1

Cable types

3x...

bunched

2x(3x...)
3x1x...
2x(3x1x...)

3x1x...
flat

single-core

three-core

Table 3-2 gives as an example for the indication of single-core and three-core cables in the single-line
diagrams.

2x(3x1x...)
Table 3-2

Report

Indication of cables in single-line diagrams

Editor: H. Specht
Order No: si0368

PG W741

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS,
LOAD FLOW AND VOLTAGE DROP

Document No.:
Project:
Status/Date:
Page:

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
8 of 26

Short Circuit Calculations

The short circuit calculation is divided into the determination of the maximum and minimum short-circuit
currents for normal and emergency operation of the unit auxiliary system. In this report the short-circuit
current calculation was carried out in accordance with the calculation procedure described in guideline
IEC EN 60909-0:2001 Short-Circuit Current Calculation in Three-Phase AC-Systems.
By means of a digital computer the partial and total short-circuit currents were determined.

4.1

Short-Circuit Currents

A complete calculation of short-circuit currents should give the currents as a function of time at the shortcircuit location from the initiation of the short circuit up to its end, corresponding to the instantaneous
value of the voltage at the beginning of the short circuit. In most practical cases a determination like this
is not necessary. Depending on the application of the results, it is of interest to know the r.m.s value of
the symmetrical a.c. component and the peak value ip of the short-circuit current following the
occurrence of a short circuit.
Definition of short-circuit currents:
Ik

Initial symmetrical short-circuit current

ip

Peak short-circuit current

Ik

Steady-state short-circuit current

id.c.

d.c. component of short-circuit current

Initial value of the d.c. component Id.c.

Figure 4-1

Report

Short-circuit current of a near-to-generator short-circuit with decaying a.c. component


(schematic diagram)

Editor: H. Specht
Order No: si0368

Document No.:

PG W741

Project:

SINUS GmbH

Status/Date:

CALCULATION OF SHORT-CIRCUIT CURRENTS,

Page:

LOAD FLOW AND VOLTAGE DROP

4.2
4.2.1

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
9 of 26

Symbols and Remarks on Diagrams


Three-Phase and Two-Phase Short-Circuit Currents

For each node following results are shown in the diagrams:


Sk

Initial symmetrical short-circuit power in MVA

Ik

Initial symmetrical short-circuit current (r.m.s.) in kA

Ib

Symmetrical short-circuit breaking current (r.m.s.) in kA

ip

Peak short-circuit current in kA

For each branch following results are shown in the diagrams:


Ik

Initial symmetrical short-circuit current (r.m.s.) in kA

ip

Peak short-circuit current in kA

The following figure gives an explanation for the short-circuit results of the diagrams.

Short-circuit currents from


infeeder for a fault at
busbar
Ik"[kA]
Sk"[MVA]

ip [kA]

Ik" [kA]
Ib [kA]
ip [kA]

Total short-circuit apparent


power and currents for a
fault at busbar

Report

Ik"[kA]
ip [kA]

M
3~

M
3~

Figure 4-2

Ik"[kA]
ip [kA]

Total short-circuit current


contribution of MV motors
connected to busbar

Total short-circuit current


contribution of LV motors
connected to busbar

Explanation of diagrams with three-phase and two-phase short-circuit results

Editor: H. Specht
Order No: si0368

Document No.:

PG W741

Project:

SINUS GmbH

Status/Date:

CALCULATION OF SHORT-CIRCUIT CURRENTS,

Page:

LOAD FLOW AND VOLTAGE DROP

4.2.2

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
10 of 26

Single-Phase Short-Circuit Currents

For each node following results are shown in the diagrams:


Ik L1

Initial symmetrical short-circuit current over phase L1 (r.m.s.) in kA

I0

Zero-sequence short-circuit current in kA

For each branch following results are shown in the diagrams:


Ik L1

Initial symmetrical short-circuit current over phase L1 (r.m.s.) in kA

I0

Zero-sequence short-circuit current in kA

Note:
In order to determine the single-phase short-circuit current flowing via the neutral star point the zero
sequence short-circuit current has to be multiplied by 3.

Short-circuit currents from


infeeder for a fault at
busbar
Ik L1" [kA]
I0

[kA]

Ik L1" [kA]
I0

[kA]
Ik L1" [kA]
I0

M
3~

Report

[kA]

I0

M
3~

Total short-circuit currents


for a fault at busbar

Figure 4-3

Ik L1" [kA]
[kA]

Total short-circuit current


contribution of MV motors
connected to busbar

Total short-circuit current


contribution of LV motors
connected to busbar

Explanation of diagrams with single-phase short-circuit results

Editor: H. Specht
Order No: si0368

PG W741

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS,

Document No.:
Project:
Status/Date:

LOAD FLOW AND VOLTAGE DROP

4.3

Page:

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
11 of 26

Investigated Operation Mode Configurations

For the calculation of the maximum and minimum short-circuit currents different operating conditions
must be considered in order to get the maximum and minimum contribution from the power plant and
network feeders.
Following operation mode configurations are considered for calculation of maximum and minimum shortcircuit currents:
Operation Mode Configuration 1:
Maximum short-circuit conditions occur at MV switchgear, if one of the two unit auxiliary
transformers 11BBT01/12BBT01 feeds all 6.3 kV switchgear. The unit auxiliary transformer
11BBT01 is supplied by the unit generator 11MKA connected via unit transformer 11BAT01
to the 220 kV network. The unit generator 12MKA is in operation and supplies the network
via the unit transformer 12BAT01.
Maximum short-circuit currents occur at LV switchgear 10BMA, if the emergency diesel
generator 10XKA11 feeds in parallel to LV transformer 10BFT01 during diesel test.
Switchgear 11BFE, 11BME, 11BFG, 11BJH and 11BFH are supplied by LV transformer
11BFT02, whereas switchgear 12BFE, 12BME, 12BFG, 12BJH and 12BFH are supplied by LV
transformer 12BFT02 and switchgear 10BJJ, 10BFJ and 10BFK are supplied by LV
transformer 10BHT02.
Operation Mode Configuration 2:
The minimum short-circuit current in the MV system is to be expected at the end of the
coupling chain of the MV switchgear, if one unit generator (11MKA) is shut down and the
remaining unit generator 12MKA is in isolated operation and supplies the auxiliary system.
The minimum short-circuit currents in the LV switchgear 11BME, 12BME, 10BMA and 10BMB
are calculated for emergency operation when the emergency diesel generator 10XKA11
supplies these switchgear.

Report

Editor: H. Specht
Order No: si0368

Document No.:

PG W741

Project:

SINUS GmbH

Status/Date:

CALCULATION OF SHORT-CIRCUIT CURRENTS,

Page:

LOAD FLOW AND VOLTAGE DROP

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
12 of 26

The circuit states for the investigated operation mode configurations are explained below.

OPERATING CONDITION
Operation Mode Configuration

Table 4-1

Report

MAX

MIN

Un

220 kV

ON

OFF

ADA

Busbar I / II

Transformer

11BAT01

240/16.5 kV

ON

OFF

Transformer

12BAT01

240/16.5 kV

ON

ON

Generator

11MKA

16.5 kV

ON

OFF

Generator

12MKA

16.5 kV

ON

ON

Infeeder from 11BBT01

11BBE

6.3 kV

ON

OFF

Infeeder from 11BBT01

11BBF

6.3 kV

ON

OFF

Infeeder from 11BBT01

12BBE

6.3 kV

ON

OFF

Infeeder from 11BBT01

12BBF

6.3 kV

ON

OFF

Infeeder from 12BBT01

11BBE

6.3 kV

OFF

ON

Infeeder from 12BBT01

11BBF

6.3 kV

OFF

ON

Infeeder from 12BBT01

12BBE

6.3 kV

OFF

ON

Infeeder from 12BBT01

12BBF

6.3 kV

OFF

ON

Infeeder from 10BFT01

10BMA

0.4 kV

ON

OFF

Infeeder from 10BFT02

10BMB

0.4 kV

ON

OFF

Infeeder from 11BFT01

11BFG

0.4 kV

OFF

OFF

Infeeder from 11BFT02

11BFH

0.4 kV

ON

ON

Infeeder from 12BFT01

12BFG

0.4 kV

OFF

OFF

Infeeder from 12BFT02

12BFH

0.4 kV

ON

ON

Infeeder from 10BHT01

11BFJ

0.4 kV

OFF

OFF

Infeeder from 10BHT02

10BFK

0.4 kV

ON

ON

Busbar Coupling

11BFE-11BME

0.4 kV

ON

OFF

Busbar Coupling

11BFE-11BFG

0.4 kV

ON

ON

Busbar Coupling

12BFE-12BME

0.4 kV

ON

OFF

Busbar Coupling

12BFE-12BFG

0.4 kV

ON

ON

Busbar Coupling

10BMA-11BME

0.4 kV

OFF

ON

Busbar Coupling

10BMB-12BME

0.4 kV

OFF

ON

Busbar Coupling

10BMA10BMB

0.4 kV

OFF

OFF

Infeeder from 10XKA11

10BMA

0.4 kV

ON

ON

Infeeder from 10XKA11

10BMB

0.4 kV

OFF

ON

Definition of operation mode configurations for short-circuit calculations

Editor: H. Specht
Order No: si0368

Document No.:

PG W741

Project:

SINUS GmbH

Status/Date:

CALCULATION OF SHORT-CIRCUIT CURRENTS,

Page:

LOAD FLOW AND VOLTAGE DROP

4.4

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
13 of 26

Maximum Short-Circuit Currents

The purpose of the short-circuit calculation is to determine whether the anticipated maximum threephase short-circuit currents are below the permissible short-circuit values of the rated switchgear. To
evaluate the dynamic stress imposed on the electric equipment, reference is made to the maximum
asymmetrical short-circuit current ip. The thermal stress depends on the magnitude of the initial a.c.
short-circuit current, the magnitude of symmetrical short-circuit breaking current and the duration of the
short-circuit.

4.4.1

Conditions for Calculation

When calculating maximum short-circuit currents, it is necessary to introduce the following conditions
according to IEC EN 60909-0:2001:

Voltage factors cmax were applied for the calculation of maximum short circuit currents.

Choosing of system configuration and the maximum contribution from power plants and
network feeders which lead to the maximum value of short-circuit current at the short-circuit
location.

The minimum equivalent short-circuit impedance is used for external networks represents by
equivalent impedances.

MV and LV motors are included.

Resistances of lines (overhead lines and cables) are introduced at a temperature of 20 oC.

For the calculation of the short-circuit breaking current Ib a minimum time delay of
tmin=0.05 sec is used for the breakers at 220 kV, 16.5 kV and 6.3 kV voltage levels and
tmin=0.02 sec for the LV circuit-breakers.

Remarks:

According to IEC EN 60909-0:2001 the tolerances of networks elements are not


considered. Preliminary calculations or calculations for design of equipment are performed
with rated values of network elements. For final calculations as basis for as-built
documentation measured values can be used (i. e. measured data based on test report of
transformer).

In accordance to IEC EN 60909-0:2001 following voltage factors are considered for the calculation of
maximum short-circuit currents:

Voltage Factor

cmax
Table 4-2

Report

Low Voltage

Medium Voltage

High Voltage

Un

Un

Un

100 V to 1000 V

> 1 kV to 35 kV

> 35 kV

1.10

1.10

1.10

Voltage factor cmax for the calculation of maximum short-circuit currents

Editor: H. Specht
Order No: si0368

Document No.:

PG W741

Project:

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS,

NEW TALKHA 750MW CCPP

Status/Date:

LOAD FLOW AND VOLTAGE DROP

4.4.2

EGY263-BN02-B-700021

B / 2005-10-21

Page:

14 of 26

Calculated Cases

Following cases for maximum short-circuit currents were investigated:

Calculated
Case

Table 4-3

Report

Description

Operation
Reference
Mode
to
Configuration
Annex

Maximum Three-Phase Short-Circuit Currents

Maximum Single-Phase Short-Circuit Currents

Investigated cases for calculation of maximum short-circuit currents

Editor: H. Specht
Order No: si0368

Document No.:

PG W741

Project:

SINUS GmbH

Status/Date:

CALCULATION OF SHORT-CIRCUIT CURRENTS,

Page:

LOAD FLOW AND VOLTAGE DROP

4.4.3

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
15 of 26

Results

The table further down contains the maximum three-phase short-circuit currents at selected busbars for
operation mode configuration 1.

Design
Switchgear

Calculation

Un
[kV]

Ik

tk

ipk

Ik"

ip

Ib

Sk"

[kA]

[sec]

[kA]

[kA]

[kA]

[kA]

[MVA]

ADA

220

42.7

101.9

42.4

16254

11BAA

16.5

149.3

399.2

129.2

4268

12BAA

16.5

145.7

390.5

126.4

4163

10BBE

6.3

31.5

80

15.4

33.4

14.6

168

10BBF

6.3

31.5

80

21.4

45.7

18.1

234

11BBE

6.3

31.5

80

26.9

65.0

22.6

293

11BBF

6.3

31.5

80

19.6

49.5

18.2

214

12BBE

6.3

31.5

80

19.7

50.1

18.3

215

12BBF

6.3

31.5

80

27.0

65.7

22.7

295

10BFJ

0.4

50

110

48.4

103.1

46.3

34

10BFK

0.4

50

110

48.4

104.4

46.3

34

10BJJ

0.4

50

110

44.1

89.1

42.4

31

10BMA

0.4

65

143

59.5

132.2

56.4

41

10BMB

0.4

65

143

40.6

91.1

39.6

28

11BFE

0.4

50

110

33.2

60.8

31.5

23

11BFG

0.4

50

110

48.9

105.2

46.1

34

11BFH

0.4

50

110

48.9

106.6

46.1

34

11BJH

0.4

50

110

42.6

85.0

40.6

30

11BME

0.4

50

110

33.2

60.8

31.5

23

12BFE

0.4

50

110

27.9

49.3

26.4

19

12BFG

0.4

50

110

48.8

104.8

46.0

34

12BFH

0.4

50

110

48.8

106.2

46.0

34

12BJH

0.4

50

110

42.5

84.7

40.6

29

12BME

0.4

50

110

27.9

49.2

26.4

19

Table 4-4

Maximum three-phase short-circuit currents

The results of the calculation for the maximum three-phase short-circuit currents show that the shortcircuit currents are lower than the permissible limiting design values of the switchgear.
Detailed results are shown in calculation drawings Annex 3 and Annex 4.

Report

Editor: H. Specht
Order No: si0368

Document No.:

PG W741

Project:

SINUS GmbH

Status/Date:

CALCULATION OF SHORT-CIRCUIT CURRENTS,

Page:

LOAD FLOW AND VOLTAGE DROP

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
16 of 26

4.5 Minimum Short-Circuit Currents


The purpose of minimum short-circuit calculation is to determine the lowest phase-to-phase and phaseto-earth short-circuits currents occurring during the faults in the system. The overcurrent protection
devices should be in a position to detect such faults and assure selective clearance of the faulty circuit.

4.5.1

Conditions for Calculation

When calculating minimum short-circuit currents, it is necessary to introduce the following conditions
according to IEC EN 60909-0:2001:

Voltage factor cmin shall be applied for the calculation of minimum short circuit currents.

Choosing of system configuration and the minimum contribution from the power plants and
network feeders which lead to the minimum value of short-circuit current at the short-circuit
location.

The maximum equivalent short-circuit impedance is used for external networks represents by
equivalent impedances.

LV motors are neglected and thus dont contribute to the total short-circuit current at the
considered short-circuit location.

Resistances of lines (overhead lines and cables) shall be introduced at a higher temperature.
Therefore, a resistance of cables at a conductor temperature of Tsc=250 oC [XLPE] is used for
calculating the minimum short-circuit currents.

For emergency operation mode the minimum short-circuit currents in LV switchgear (11BME,
12BME, 10BMA and 10BMB) were calculated on basis of the minimum short-circuit currents of
the diesel generators 10XKA11 (according to current decrement curve of generator
manufacturer).

In accordance to IEC EN 60909-0:2001 following voltage factors are considered for the calculation of
minimum short-circuit currents:

Voltage Factor

cmin
Table 4-5

Report

Low Voltage

Medium Voltage

High Voltage

Un

Un

Un

100 V to 1000 V

> 1 kV to 35 kV

> 35 kV

0.95

1.00

1.00

Voltage factor cmin for the calculation of minimum short-circuit currents

Editor: H. Specht
Order No: si0368

Document No.:

PG W741

Project:

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS,

NEW TALKHA 750MW CCPP

Status/Date:

LOAD FLOW AND VOLTAGE DROP

4.5.2

EGY263-BN02-B-700021

B / 2005-10-21

Page:

17 of 26

Calculated Cases

Following minimum short-circuit cases were investigated:

Calculated
Case

Table 4-6

4.5.3

Description

Operation
Reference
Mode
to
Configuration
Annex

Minimum Three-Phase-Short-Circuit Currents

Minimum Two-Phase-Short-Circuit Currents

Minimum Single-Phase-Short-Circuit Currents

Investigated cases for calculation of minimum short-circuit currents

Results

Detailed results of minimum short-circuit calculations with different operation mode configurations are
shown in the calculation drawings Annex 5 to Annex 7.
Calculation results of short-circuit impedances for minimum short-circuit currents at the low voltage
switchgear are shown in Annex 8.

Report

Editor: H. Specht
Order No: si0368

Document No.:

PG W741

Project:

SINUS GmbH

Status/Date:

CALCULATION OF SHORT-CIRCUIT CURRENTS,

Page:

LOAD FLOW AND VOLTAGE DROP

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
18 of 26

Voltage Drop Calculation for Motor Start-Up

5.1 Start-Up of Medium Voltage Motor 00LAC11 (HP FD WTR)


In the voltage drop calculation the motor being started is modelled by a constant impedance. The
running motors (pre-load) are considered as equivalent motors and simulated with constant power (worst
case).
Before motor start-up the pre-load voltage Upre being present on the HV side of the feeding transformer
12BBT01. On basis of the equivalent electrical circuit for the pre-load operation mode and the assumed
pre-load voltage the fictitious effective voltage U0 of the equivalent voltage source is calculated.

RQ

UnQ, IkQ, R/X

XQ

P, Q

Upre

U0

u =

Figure 5-1

5.2

U 0 U pre
U nQ

100% =

P RQ + Q X Q
2
U nQ

100%

Voltage drop calculation for network infeeder under consideration of pre-load

Conditions for Calculation

The voltage dip at motor terminals during its start-up is calculated for the 6.3 kV induction motor
00LAC11 (HP Feed Water Pump), which has the largest starting current.
For calculation of the minimum terminal voltages when starting motor 00LAC11 the voltage Upre0=95% Un
as equivalent source voltage at 16.5 kV is assumed before motor start-up. Before motor start-up the
voltage at 6.3 kV is adjusted with the on-load tap changer of 12BBT01, that the voltage at both LV
windings is as minimum 100% Un.
Additionally a maximum total pre-load of 29.6 MVA with power factor cos()=0.87 is considered which
causes a voltage drop (u) at 6.3 kV before motor start-up. The pre-load is determined in such a way
that the transformer is full loaded with 32 MVA after start-up of 00LAC11 (worst case).
The starting current of the motor 00LAC11 is Is/In=6.0 and the starting power factor is cos()s=0.23.
The OLTC is considered constant (no operation) during starting.

Report

Editor: H. Specht
Order No: si0368

Document No.:

PG W741

Project:

SINUS GmbH

Status/Date:

CALCULATION OF SHORT-CIRCUIT CURRENTS,

Page:

LOAD FLOW AND VOLTAGE DROP

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
19 of 26

Resistances of the 6.3 kV cables are introduced in the motor starting calculation (load flow) at a
conductor temperature of 90 oC. The MV cable in the motor feeder of 00LAC11 is not considered since no
data are available.

5.3

Results

The following table shows the voltages at selected busbars for the calculated voltages are referred to the
rated voltage of the motor and switchgear respectively.

Before Motor Starting


Busbar

Table 5-1

Un

[kV]

U / Un

[%]

During Motor Starting


U / Un

HV Transformer 12BBT01

16.5

95.0

93.8

11BBE

6.3

100.6

90.7

Motor Terminal 00LAC11

6.3

----

90.7

[%]

The value of U/Un [%] before and during motor starting

The minimum voltage at motor terminal 00LAC11 is 90.7% Un.


Detailed results are shown in calculation drawing Annex 9

Report

Editor: H. Specht
Order No: si0368

PG W741

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS,
LOAD FLOW AND VOLTAGE DROP

Document No.:
Project:
Status/Date:
Page:

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
20 of 26

Check of Transformer Rating for Generator Transformer


(BAT)

The aim of this investigation is to check the rating of the generator transformer (11BAT01/12BAT01) for
overexcited operation (PF=0.85/lag) and underexcited operation (PF=0.92/lead and PF=0.93/lead) of the
generator (11MKA/12MKA) with consideration of the auxiliary load.
Since the maximum active power output of gas turbine, the maximum apparent power of generator and
generator transformer output depends on the ambient air temperature as well as reactive capability
limits, the following chapters include a brief introduction to these items and considered data.

6.1

Dependency of Power Output and Rating from Temperature

The following diagram shows the relation between the maximum active power output of the gas turbine,
the maximum apparent power output of the generator and generator transformer output as a function of
the ambient air temperature.

Figure 6-1

Report

Active power output of gas turbine, apparent power of generator and generator transformer output dependent on
ambient air temperature

Editor: H. Specht
Order No: si0368

PG W741

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS,
LOAD FLOW AND VOLTAGE DROP

6.2

Document No.:
Project:
Status/Date:
Page:

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
21 of 26

Reactive Capability Limits of Generator

The following figure shows the reactive capability curve of the generator TLRI 115/52.

Figure 6-2

Reactive capability limits of generator TLRI 115/52

Synchronous generators are rated in terms of the maximum MVA output at a specified voltage and power
factor (usually 0.80 to 0.90 lagging) which they can carry without overheating. The active power is
limited by the prime mover to value within the MVA rating. The continuous reactive power output
capability is limited by following three considerations.
Armature current limit
The armature current results in R I2 power loss, and the energy associated with this loss must be
removed so as to limit the increase in temperature of the conductor and its immediate environment.
Therefore, one of the limitations on generator rating is the maximum current that can be carried by
the armature without exceeding the heating limitations. In the P-Q plane the armature current limit
appears as a circle with centre at the origin and radius equal to the to the MVA rating.
Field current limit
Because of the heating resulting from the Rfd i2fd power loss, the field current imposes a second limit
of the operation of the generator.
Report

Editor: H. Specht
Order No: si0368

Document No.:

PG W741

Project:

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS,
LOAD FLOW AND VOLTAGE DROP

Status/Date:
Page:

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
22 of 26

End region heating limit


The localized heating in the end region of the armature imposes a third limit on the operation of a
synchronous machine. This limit affects the capability of the machine in the underexcited condition.
The end-turn leakage flux enters and leaves in a direction perpendicular (axial) to the stator
limitations. This causes eddy currents in the limitations, resulting in localized heating in the end
region. The high field currents corresponding to the overexcited condition keep the retaining ring
saturated, so that end leakage flux is small. However, in the underexcited region the field current is
low and the retaining ring is not saturated; this permits an increase in armature end leakage flux.
In any balanced design, the thermal limits for the field and armature intersect at a point, which
represents the machine nameplate MVA and power factor rating (operating point 1 in Figure 6-2)
The above limits on the operation of the generator are those imposed by the capabilities of the machine
itself and are determined by the design of the machine. Additional limits may be imposed by power
system stability limits.

6.3

Results

The rating of the generator transformer (11BAT01/12BAT01) is checked for overexcited operation
(PF=0.85/lag) and underexcited operation (PF=0.92/lead and PF=0.93/lead) of the generator
(11MKA/12MKA).
Detailed input data and results are shown in tabular form and as diagram in Annex 10.
The following remarks include additional information about the calculation and considered data (see
references at right border of tables in Annex 10).
1) Rated power of generator transformer
According to ANSI/IEEE C57.12.00 standard for transformers is rated kVA defined as the output
that can be delivered at rated secondary voltage of transformer and rated current flows through
terminals of secondary winding.
The dependency of loading of generator transformer from ambient air temperature is based on
Figure 6-1.
2) Current carrying capacity of LV winding
The rated current flowing through a line terminal of a winding which is derived from rated power Sr
and rated voltage Ur for the winding.
For temperatures deviating from the temperature as base for rated power the maximum apparent
power is used for calculation of maximum current carrying capacity of the LV winding.
3) Current carrying capacity of HV winding
The ratio between the current at terminals of HV winding and LV winding is determined by the
turns ratio of the transformer (nHV number of turns of HV winding, nLV number of turns of LV
winding). The current of the HV winding can be calculated for a given current at LV winding with
following equation (neglecting of magnetizing current).

I HV =

nLV
U rLV
I LV =
I LV
nHV
tapping factor U rHV

In the case of full-power tapings and rated current at LV winding the HV winding is capable to
carrying for all tappings the corresponding current.
Report

Editor: H. Specht
Order No: si0368

PG W741

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS,
LOAD FLOW AND VOLTAGE DROP

Document No.:
Project:
Status/Date:
Page:

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
23 of 26

4) Maximum power output of gas turbine and generator


The maximum active power output of the gas turbine Pmax GT depends on the ambient air
temperature. The maximum apparent power of the generator Smax Gen depends also on the ambient
air temperature (or cold gas temperature). With use of rated power factor (PF=0.85) the maximum
active power output of the generator Pmax Gen can be calculated from Smax Gen.
5) Maximum active power output for overexcited operation
The minimum value of Pmax GT and Pmax Gen determines the maximum active power output of gas
turbine and generator together. From this value and with considering of rated power factor the
maximum apparent power output Slag GT/Gen can be calculated.
6) Maximum apparent power at LV winding of generator transformer for overexcited operation
The maximum reactive power will be feeded from the generator to the 220 kV interconnected
system if the auxiliary load is completely supplied from the other unit. For this case the auxiliary
load demand Slag Aux is set to zero (worst case). Therefore, the apparent power at LV winding of
generator transformer (Slag LV T) is equal to the apparent power output of the generator (Slag GT/Gen).
7) Maximum active power output for underexcited operation
In the case of underexcited operation the reactive power output is limited by the end region
heating limit of the generator (see Figure 6-2). For given power factors of PF=0.92/lead and
PF=0.93/lead the maximum active power output can be determined from the generator reactive
capability curve (see operating points 2 and 3). As a consequence of this limitation the active
power output Plead GT/Gen is limited for operating points with high active power output of gas turbine.
8) Maximum Apparent power at LV winding of generator transformer for underexcited operation
If the generator is operated underexcited and the auxiliary load is supplied from the other auxiliary
transformer, the maximum apparent power will flow from the generator to the 220 kV
interconnected system. For this case the auxiliary load demand is set to Slead Aux=0 MVA (worst
case). If the auxiliary load would be supplied from generator the reactive power flow via generator
transformer is larger but on the other side the active power flow will be reduced more which leads
to a lower value for the apparent power.
9) Operating current at LV winding of generator transformer
After determining of apparent power at LV winding of generator transformer for overexcited and
underexcited operation (items 6 and 8) the currents at terminal of LV winding (Ilag LV T and Ilaed LV T)
can be calculated for the generator operating voltage of 16.5 kV.
10) Comparison of operating currents with current carrying capacity of generator transformer
The comparison of Ilag LV T and Ilead LV T with Imax LV T shows that for all considered cases the current
carrying capacity of the LV winding (Imax LV T) of generator transformer is higher as the operating
currents. If the current carrying capacity of the LV winding is always higher than the operating
current, the current carrying capacity of the HV winding will also not be exceeded (independent of
the actual tap position for full-power tappings).
Generally, the current results in R I2 power loss, and the energy associated with this loss must be
removed so as to limit the increase in temperature of the conductor and its immediate
environment. Therefore, the currents of LV and HV winding are considered for check of rating of
generator transformer.

Report

Editor: H. Specht
Order No: si0368

PG W741

Document No.:
Project:

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS,
LOAD FLOW AND VOLTAGE DROP

Status/Date:
Page:

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
24 of 26

11) The calculation sheets in Annex 10 are used to determine the apparent power at low voltage side
of generator transformer for different ambient air temperatures. Based on this apparent power the
current at low voltage side of generator transformer is calculated and compared with rated current
of transformer.
Annex 10 includes corresponding load flow calculations (for ambient air temperature of 30 C)
which show also the load flow at the high voltage side of generator transformer for overexcited
operation with PF=0.85/lag (operating point 1) and for underexcited operation with PF=0.92/lead
as well as PF=0.93/lead (operating point 2 and 3). The difference between active and reactive
power flow at high voltage side and low voltage side of generator transformer is caused by the
losses of the generator transformer. The drawing includes the currents and the current utilizations
(based on rated current of winding) at the high and low voltage side of the generator transformer.
The results of the load flow calculations show that for all cases the currents and the apparent
powers at the high and low voltage side of the generator transformer are below rated current and
rated power.

Remarks:

Report

Generally, the currents at high and low voltage terminals of generator transformer
must be smaller or equal as rated current. If theoretically a transformer would be
operated with rated power and with 50% rated voltage at low voltage terminal the
current at low voltage terminal would be 200% of rated current. Under such conditions
the transformer is overloaded since the R I2 power losses cause an inadmissible
increase in temperature of the conductor. Therefore, the overload condition can not be
determined by the apparent power (in this example it would not exceed rated power).
The rated power of the transformer and the rated voltage of the winding are used to
define the rated current of the winding which is the basis for the design of the
transformer (i. e. cross section of conductors, losses, ).

Editor: H. Specht
Order No: si0368

Document No.:

PG W741

Project:

SINUS GmbH

Status/Date:

CALCULATION OF SHORT-CIRCUIT CURRENTS,

Page:

LOAD FLOW AND VOLTAGE DROP

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
25 of 26

Check of Voltage Profile for Auxiliary Transformer (BBT)

In order to determine the minimum and maximum operating voltages at HV side of auxiliary transformer
several load flow cases are calculated.

7.1

Conditions for Calculations

The voltage range of the operating voltage at 6.3 kV is +/-10% of rated voltage.

For the auxiliary load at 6.3 kV following three design critical cases are considered:

Both LV windings (LV1 and LV2) of the auxiliary transformer are full loaded
(SLoad LV1=SLoad LV2=16 MVA).

A single LV winding (LV1) of the auxiliary transformer is full loaded (SLoad LV1= 16 MVA)
and at the other LV winding no load is connected (SLoad LV2= 0 MVA).

At both LV windings (LV1 and LV2) of the auxiliary transformer no loads are connected
(SLoad LV1=SLoad LV2=0 MVA).

For the power factor of the auxiliary load a power factor range of 0.80 to 0.90 is considered.

The following tables include the maximum and minimum operating voltages at HV side (16.5 kV) of the
auxiliary transformer.

Operating

Sload LV1

Point

[MVA]

16.0

16.0

Table 7-1

Report

PFload LV1

ULV1 6.3kV

Sload LV2

[%]

[MVA]

0.80

90.0

16.0

0.85

90.0

PFload LV2

ULV2 6.3kV

UHV 16.5 kV

[%]

[%]

0.80

90.0

83.3

16.0

0.85

90.0

82.7

16.0

0.90

90.1

16.0

0.90

90.0

81.8

4
5

16.0
16.0

0.80
0.85

90.0
90.0

-----

-----

96.2
95.6

82.4
81.8

16.0

0.90

90.0

---

---

94.9

81.1

---

---

90.0

---

---

90.0

76.3

Minimum operating voltage at HV side (16.5 kV) of auxiliary transformer (BBT)

Editor: H. Specht
Order No: si0368

Document No.:

PG W741

Project:

SINUS GmbH

Status/Date:

CALCULATION OF SHORT-CIRCUIT CURRENTS,

Page:

LOAD FLOW AND VOLTAGE DROP

Operating

Sload LV1

Point

[MVA]

8
9

16.0
16.0

Table 7-2

7.2

PFload LV1

0.80
0.85

ULV1 6.3kV

Sload LV2

[%]

[MVA]

110.0
110.0

16.0
16.0

PFload LV2

EGY263-BN02-B-700021
NEW TALKHA 750MW CCPP
B / 2005-10-21
26 of 26

ULV2 6.3kV

UHV 16.5 kV

[%]

[%]

0.80
0.85

109.9
110.0

123.9
123.2

10

16.0

0.90

110.0

16.0

0.90

110.0

122.3

11
12

16.0
16.0

0.80
0.85

104.7
105.2

-----

-----

110.0
110.0

117.7
117.6

13

16.0

0.90

105.9

---

---

110.0

117.5

14

---

---

110.0

---

---

110.0

116.8

Maximum operating voltage at HV side (16.5 kV) of auxiliary transformer (BBT)

Summary of Results

The maximum and minimum operating voltages at HV side of auxiliary transformer are limited by
the allowed voltage range at 6.3 kV and the tapping range of the auxiliary transformer.

In order to fulfil the voltage requirements at 6.3 kV (U=+/-10% Un) for all cases (1 to 14) the
operating voltage at HV side of auxiliary transformer must be larger than 83.3% Un (13.7 kV) and
smaller than 116.8% Un (19.3 kV). For individual operating points the possible voltage range at
16.5 kV is larger.

The operating voltage range of the generator is +/5% Un. If the generator is operated according
to this voltage range the voltage at 6.3 kV auxiliary system will be smaller than +/-10% Un and
the requirements are fulfilled.

Report

Editor: H. Specht
Order No: si0368

PG W 741

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS AND VOLTAGE DROP

Document No.:
Project:

EGY263-BN02-B-700021
NEW TALKHA 750 MW CCPP

Date:

B / 2005-10-21

Page:

1 of 11

Annex 1

Table of Input Data


Annex 1.1:

Switchgear

Annex 1.2:

Cables

Annex 1.3:

Induction Motors

Annex 1.4:

Synchronous Machines

Annex 1.5:

MV/LV Switchgear Cubicles for Motor Feeders

Annex 1.6:

MV/LV Switchgear Cubicles for Transformer Feeders

Annex 1.7:

MV/LV Switchgear Cubicles for Incoming and Coupling Feeders

Annex 1.8:

MV/LV Switchgear Cubicles for Synchronous Machines

Annex 1: Table of Input Data

Editor: H. Specht
Ord. No.: si0368

Document No.:

PG W 741

Project:

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS AND VOLTAGE DROP

Annex 1.1:
Un
Ik
tk
ip

EGY263-BN02-B-700021
NEW TALKHA 750 MW CCPP

Date:

B / 2005-10-21

Page:

2 of 11

Switchgear
Nominal voltage of switchgear in kV
Steady-state short-circuit current in kA
Short-circuit time in sec
Peak short-circuit current in kA

KKS
ID-Code
ADA
11BAA
12BAA
10BBE
10BBF
11BBE
11BBF
12BBE
12BBF
10BFJ
10BFK
10BJJ
10BMA
10BMB
11BFE
11BFG
11BFH
11BJH
11BME
12BFE
12BFG
12BFH
12BJH
12BME
Annex 1: Table of Input Data

Un

Ik

tk

ip

[kV]

[kA]

[sec]

[kA]

220
16.5
16.5
6.3
6.3
6.3
6.3
6.3
6.3
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4

31.5
31.5
31.5
31.5
31.5
31.5
50
50
50
65
65
50
50
50
50
50
50
50
50
50
50

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

80
80
80
80
80
80
110
110
110
143
143
110
110
110
110
110
110
110
110
110
110
Editor: H. Specht
Ord. No.: si0368

Project:

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS AND VOLTAGE DROP

Annex 1.2:

Un
r 20
x
c
lr
l1s
TOP
TSC
R0/R1
X0/X1

EGY263-BN02-B-700021

Document No.:

PG W 741

NEW TALKHA 750 MW CCPP

Date:

B / 2005-10-21

Page:

3 of 11

Cables

Rated voltage in kV
Resistance at 20C in /km
Reactance in /km
Capacitance in nF/km
Rating current for normal operation in A
Permissible short-circuit current for a short-circuit duration of tkr=1sec in kA
Permissible operating temperature in C
Permissible short-circuit temperature in C
Ratio resistance zero / positive sequence in p.u.
Ratio reactance zero / positive sequence in p.u.

Type Indication
N2XSY (10 kV) 3x1x240
N2XSY (10 kV) 3x1x120
N2XY-O (1 kV) 3x1x240
LXC0741 (1 kV) 3x1,586/2,934

Type Indication
N2XSY (10kV) 2x(3x1x240)
N2XSY (10kV) 3x(3x1x240)
N2XSY (10kV) 3x1x120
N2XSY (10kV) 3x1x240
LXC0741 (1kV) 3x1,586/2x1,586
N2XY-O (1kV) 2x(3x1x240)/1x240
N2XY-O (1kV) 3x(3x1x240)/2x240
N2XY-O (1kV) 6x(3x1x240)/3x240

Annex 1: Table of Input Data

Type
N2XSY
N2XSY
N2XY-O
LXC0741

Type
N2XSY
N2XSY
N2XSY
N2XSY
LXC0741
N2XY-O
N2XY-O
N2XY-O

Cross

Un

r 20

lr

l 1s

TOP

Tsc

Section

[kV]

[/km]

[/km]

[nF/km]

[A]

[kA]

[C]

[C]

10
10
1
1

0.0754
0.153
0.0754
0.013

0.105
0.117
0.086
0.011

90
90
90
90

250
250
250
250

Cross

Un

R0/R1

X0/X1

Section

[kV]

[p.u.]

[p.u.]

10
10
10
10
1
1
1
1

8.81
8.81
6.45
8.81
4.15
7
5.54
7

2.67
2.67
4.55
2.67
4.45
3.67
3.67
3.67

3x1x240
3x1x120
3x1x240
3x1,586/2,934

3x1x240
3x1x240
3x1x120
3x1x240
3x1,586/2,934
3x1x240
3x1x240
3x1x240

Editor: H. Specht
Ord. No.: si0368

Document No.:

PG W 741

Project:

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS AND VOLTAGE DROP

Annex 1.3:

Motor Type
Lumped
Pn
Ir
Un
cos n
R/X
n
Ia/In
p
I max
I no load

KKS
ID-Code

EGY263-BN02-B-700021
NEW TALKHA 750 MW CCPP

Date:

B / 2005-10-21

Page:

4 of 11

Induction Motors

t start 100
t start 80
t LRT
t heat
t run
t rest
cos s
No. start cold
No. start warm
I(t) Curve
I2/Ir
U2/Un

Type of motor
Lumped low-voltage motors
Rated active power of motor in kW
Rated current of motor in A
Nominal voltage of motor in kV
Rated power factor of motor
Ratio of resistance to reactance in p.u.
Rated efficiency of motor in %
Ratio starting current to rated current of motor in p.u.
Number of pole pairs
Maximum continous current (K x Irated ) of motor in A
No-Load current (Idle-Current) in A

Lumped

Pn

Ir

Un

[kW]

[A]

[kV]

cos n

R/X

Ia/In

[p.u.]

[%]

[p.u.]

Starting time (at U=100% Urated) in sec


Starting time (at U=80% Urated) in sec
Maximum locked rotor time (warm mode at U=100% Urated) in sec
Thermal time constant of stator for heating in min
Thermal time constant of stator for cooling running motor in min
Thermal time constant of stator for cooling at rest in min
Starting power factor of motor
Number of permissible start-ups per hour for starting at cold operating point
Number of permissible start-ups per hour for starting at warm operating point
Available thermal withstand curve (no; yes)
Maximum permissible negative sequence current ratio in p.u.
Continuously negative sequence voltage ratio in p.u.

I max

I no load

t start 100

t start 80

t LRT

t heat

t run

t rest

[A]

[A]

[sec]

[sec]

[sec]

[min]

[min]

[min]

cos s

No.

No.

Start

Start

I(t)

Cold Warm Curve

I2/Ir

U2/Un

[p.u.]

[p.u.]

PCC

no

270

32.3

6.3

0.81

0.15

94.6

5.4

35.2

10.6

0.4

0.9

16

3.8

60

240

0.29

yes

0.1

0.01

PGC

no

300

34.8

6.3

0.83

0.15

95.2

5.5

39.7

12

0.4

0.8

16

5.7

55

220

0.27

yes

0.1

SGA

no

220

24.1

6.3

0.87

0.15

96

no

LAC

no

2074

227.0

0.91

0.1

96.6

no

LCB

no

656

76.8

0.86

0.15

95.6

no

MBN

no

650

72.2

0.9

0.15

96.2

72.2

12.6

6.5

18

80

160

210

0.199

yes

0.09

MBU

no

450

50.2

0.9

0.15

95.8

50.2

10.2

3.5

18

160

210

0.173

yes

0.09

PAC

no

1537

209.1

0.74

0.15

95.6

no

Annex 1: Table of Input Data

Editor: H. Specht
Ord. No.: si0368

Document No.:

PG W 741

Project:

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS AND VOLTAGE DROP

Annex 1.4:

Sn
Un
R/X
xd
cosn

MKA
XKA

EGY263-BN02-B-700021
NEW TALKHA 750 MW CCPP

Date:

B / 2005-10-21

Page:

5 of 11

Synchronous Machines

Apparent power in MVA


Rated voltage of in kV
Ratio of resistance to reactance in p.u.
Subtransient reactance in %
Rated power factor

KKS

Sn

Un

R/X

x d"

ID-Code

[MVA]

[kV]

[p.u.]

[%]

313
1.65

16.5
0.4

0.05
0.15

15.2
13

Annex 1: Table of Input Data

cos n
0.85
0.8

Editor: H. Specht
Ord. No.: si0368

PG W 741

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS AND VOLTAGE DROP

Annex 1.5:

Document No.:
Project:

EGY263-BN02-B-700021
NEW TALKHA 750 MW CCPP

Date:

B / 2005-10-21

Page:

6 of 11

MV/LV Switchgear Cubicles for Motor Feeders

Un
Protection Device Name
CT
Cable CT
Cable Type
Cable l
Motor Type
Motor Pn

Annex 1: Table of Input Data

Nominal voltage of panel in kV


Order number of protection device (MLFB)
Transformer ratio of current transformer in A/A
Transformer ratio of cable current transformer in A/A
Cable type (corresponding data are shown in table ''Cables)
Length of cable in m
Motor type (corresponding motor data see table "Induction Motors")
Rated active power of motor in kW

Editor: H. Specht
Ord. No.: si0368

Project:

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS AND VOLTAGE DROP

KKS

Designation

ID-Code

EGY263-BN02-B-700021

Document No.:

PG W 741

Switchgear

Un

Protection Device

CT

[kV]

Name

[A/A]

Cable
CT
[A/A]

NEW TALKHA 750 MW CCPP

Date:

B / 2005-10-21

Page:

7 of 11

Motor

Cable
Type

Type

[m]

Pn
[kW]

00LAC11AP001 -M01

HP FD WTR PUMP A

11BBE

6.3

7SJ6111-5EB02-1HA0/7UT6121-5EB00-1AA0

300/1

100/1

LAC

2074

00LAC12AP001 -M01

HP FD WTR PUMP B

12BBF

6.3

7SJ6111-5EB02-1HA0/7UT6121-5EB00-1AA0

300/1

100/1

LAC

2074

00LAC13AP001 -M01

HP FD WTR PUMP C

12BBE

6.3

7SJ6111-5EB02-1HA0/7UT6121-5EB00-1AA0

300/1

100/1

LAC

2074

00LCB11AP001 -M01

CONDENSATE PUMP A

11BBF

6.3

7SJ6111-5EB02-1HA0

100/1

100/1

LCB

656

00LCB12AP001 -M01

CONDENSATE PUMP B

12BBF

6.3

7SJ6111-5EB02-1HA0

100/1

100/1

LCB

656

00PAC01AP001 -M01

CWP A

10BBE

6.3

7SJ6111-5EB02-1HA0/7UT6121-5EB00-1AA0

300/1

100/1

PAC

1537

00PAC02AP001 -M01

CWP B

10BBF

6.3

7SJ6111-5EB02-1HA0/7UT6121-5EB00-1AA0

300/1

100/1

PAC

1537

00PAC03AP001A -M01 CWP C

10BBE

6.3

7SJ6111-5EB02-1HA0/7UT6121-5EB00-1AA0

300/1

100/1

PAC

1537

00PAC03AP001B -M01 CWP C

10BBF

6.3

7SJ6111-5EB02-1HA0/7UT6121-5EB00-1AA0

300/1

100/1

PAC

1537

10PCC11AP001 -M01

SCWP 1

10BBE

6.3

7SJ6111-5EB02-1HA0

50/1

100/1

N2XSY (10kV) 3x1x120

122

PCC

270

10PCC12AP001 -M01

SCWP 2

10BBF

6.3

7SJ6111-5EB02-1HA0

50/1

100/1

N2XSY (10kV) 3x1x120

122

PCC

270

10PGC11AP001 -M01

CCWP 1

11BBF

6.3

7SJ6111-5EB02-1HA0

50/1

100/1

N2XSY (10kV) 3x1x120

178

PGC

300

10PGC12AP001 -M01

CCWP 2

12BBF

6.3

7SJ6111-5EB02-1HA0

50/1

100/1

N2XSY (10kV) 3x1x120

151

PGC

300

11MBN12AP001 -M01 FUEL OIL INJECTION PUMP

11BBE

6.3

7SJ6111-5EB02-1HA0

100/1

100/1

N2XSY (10kV) 3x1x120

144

MBN

650

11MBU25AP001 -M01 NOX WATER PUMP

11BBE

6.3

7SJ6111-5EB02-1HA0

50/1

100/1

N2XSY (10kV) 3x1x120

125

MBU

450

12MBN12AP001 -M01 FUEL OIL INJECTION PUMP

12BBE

6.3

7SJ6111-5EB02-1HA0

100/1

100/1

N2XSY (10kV) 3x1x120

200

MBN

650

12MBU25AP001 -M01 NOX WATER PUMP

12BBE

6.3

7SJ6111-5EB02-1HA0

50/1

100/1

N2XSY (10kV) 3x1x120

173

MBU

450

Annex 1: Table of Input Data

Editor: H. Specht
Ord. No.: si0368

Document No.:

PG W 741

Project:

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS AND VOLTAGE DROP

Annex 1.6:

EGY263-BN02-B-700021
NEW TALKHA 750 MW CCPP

Date:

B / 2005-10-21

Page:

8 of 11

MV/LV Switchgear Cubicles for Transformer Feeders

Un
Protection Device Name
CT
Cable CT
Cable Type
Cable l

S nT
U nT
uk
ur
Vector Group
I rush
t rush
R0/R1
X0/X1

Nominal voltage of panel in kV


Order number of protection device (MLFB)
Transformer ratio of current transformer in A/A
Transformer ratio of cable current transformer in A/A
Cable type (corresponding data are shown in table ''Cables)
Length of cable in m

Rated apparent power of transformer in MVA


Rated voltage of transformer in kV
Reference short circuit voltage in %
Rated resistance voltage drop in %
Vector group of transformer
Rush current of transformer in kA
Delay for rush of transformer in sec
Ratio resistance zero / positive sequence in p.u.
Ratio reactance zero / positive sequence in p.u.

For all LV-transformer (According IEC EN 60909-0:2001) R0/R1 = 1 p.u. and X0/X1 = 0.95 p.u..

KKS
ID-Code

Designation

Switchgear

Un
[kV]

Protection Device
Name

CT
[A/A]

Cable
CT
[A/A]

Transformer

Cable
Type

l
[m]

Name

S nT

U nT

uk

ur

Vector

[MVA]

[kV]

[%]

[%]

Group

10BFT01GT001

LV TRANSFORM

11BBE

6.3

7SJ6111-5EB02-1FA0

200/1

100/1

N2XSY 3x1x120

38

10BFT01

1.6

6.3/0.42

0.89

Dyn1

10BFT02GT001

LV TRANSFORM

12BBE

6.3

7SJ6111-5EB02-1FA0

200/1

100/1

N2XSY 3x1x120

38

10BFT02

1.6

6.3/0.42

0.89

Dyn1

10BHT01GT001

LV TRANSFORM

10BBE

6.3

7SJ6111-5EB02-1FA0

200/1

100/1

N2XSY 3x1x120

20

10BHT01

1.6

6.3/0.42

0.89

Dyn1

10BHT02GT001

LV TRANSFORM

10BBF

6.3

7SJ6111-5EB02-1FA0

200/1

100/1

N2XSY 3x1x120

20

10BHT02

1.6

6.3/0.42

0.89

Dyn1

11BBT01GT100

UNIT AUX TFR

11BAA

16.5

1200/1

11BBT01

32

16.5/6.6

8.6

0.3

Dyn11

11BFT01GT001

LV TRANSFORM

11BBF

6.3

7SJ6111-5EB02-1FA0

200/1

100/1

N2XSY 3x1x120

34

11BFT01

1.6

6.3/0.42

0.89

Dyn1

11BFT02GT001

LV TRANSFORM

12BBF

6.3

7SJ6111-5EB02-1FA0

200/1

100/1

N2XSY 3x1x120

33

11BFT02

1.6

6.3/0.42

0.89

Dyn1

11MBJ01GT001

SFC TRANSFORM

11BBE

6.3

7SJ6111-5EB00-1FA0

500/1

100/1

N2XSY 2x(3x1x240)

94

11MBJ01

2.57

6.3/1.8

0.51

Dy5

11MKC01GT001

SEE TRANSFORM

11BBE

6.3

7SJ6111-5EB00-1FA0

200/1

100/1

N2XSY 3x1x240

94

11MKC01

1.65

6.3/0.66

0.6

Dy5

12BBT01GT100

UNIT AUX TFR

12BAA

16.5

1200/1

12BBT01

32

16.5/6.6

8.6

0.3

Dyn11

12BFT01GT001

LV TRANSFORM

12BBE

6.3

7SJ6111-5EB02-1FA0

200/1

100/1

N2XSY 3x1x120

15

12BFT01

1.6

6.3/0.42

0.89

Dyn1

12BFT02GT001

LV TRANSFORM

11BBE

6.3

7SJ6111-5EB02-1FA0

200/1

100/1

N2XSY 3x1x120

43

12BFT02

1.6

6.3/0.42

0.89

Dyn1

12MBJ01GT001

SFC TRANSFORM

12BBE

6.3

7SJ6111-5EB00-1FA0

500/1

100/1

N2XSY 2x(3x1x240)

150

12MBJ01

2.57

6.3/1.8

0.51

Dy5

12MKC01GT001

SEE TRANSFORM

12BBE

6.3

7SJ6111-5EB00-1FA0

200/1

100/1

N2XSY 3x1x240

150

12MKC01

1.65

6.3/0.66

0.6

Dy5

Annex 1: Table of Input Data

7UM6121-5EB02-0BA0/7UT6331-5EB02-1BA0

7UM6121-5EB02-0BA0/7UT6331-5EB02-1BA0

Editor: H. Specht
Ord. No.: si0368

Document No.:

PG W 741

Project:

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS AND VOLTAGE DROP

Annex 1.7:

EGY263-BN02-B-700021
NEW TALKHA 750 MW CCPP

Date:

B / 2005-10-21

Page:

9 of 11

MV/LV Switchgear Cubicles for Incoming and Coupling Feeders

Nominal voltage of panel in kV


Order number of protection device or switching device (MFLB)
Nominal current protection device (feeder bimetal range end) in A
Number of fuses
Nominal current of fuse in A
Transformer ratio of current transformer in A/A
Transformer ratio of cable current transformer in A/A
Cable type (corresponding data are shown in table ''Cables)
Length of cable in m

Un
Protection Device Name
Protection Device In
Fuse No.
Fuse In
CT
Cable CT
Cable Type
Cable l

KKS

Designation

ID-Code

Switchgear

Un
[kV]

Protection Device
Name

Fuse
ln

No.

[A]

CT

ln
[A]

[A/A]

Cable
CT
[A/A]

Cable
Type

l
[m]

10BBE00GS001

TIE FEEDER *11BBF*

10BBE

6.3

7SJ6111-5EB00-1FA0

1000/1

N2XSY (10kV) 2x(3x1x240)

984

10BBF00GS001

TIE FEEDER *12BBF*

10BBF

6.3

7SJ6111-5EB00-1FA0

1000/1

N2XSY (10kV) 2x(3x1x240)

974

11BBF00GS001

TIE FEEDER *10BBE*

11BBF

6.3

7SJ6111-5EB00-1FA0

1000/1

N2XSY (10kV) 2x(3x1x240)

984

11BBT01GT210

MV INC FDR

11BBE

6.3

7SJ6111-5EB00-1FA0

2000/1

N2XSY (10kV) 3x(3x1x240)

98

11BBT01GT220

MV INC FDR

11BBF

6.3

7SJ6111-5EB00-1FA0

2000/1

N2XSY (10kV) 3x(3x1x240)

98

11BBT01GT230

MV INC FDR

12BBF

6.3

7SJ6111-5EB00-1FA0

2000/1

N2XSY (10kV) 3x(3x1x240)

92

11BBT01GT240

MV INC FDR

12BBE

6.3

7SJ6111-5EB00-1FA0

2000/1

N2XSY (10kV) 3x(3x1x240)

92

12BBF00GS001

TIE FEEDER *10BBF*

12BBF

6.3

7SJ6111-5EB00-1FA0

1000/1

N2XSY (10kV) 2x(3x1x240)

974

12BBT01GT210

MV INC FDR

12BBE

6.3

7SJ6111-5EB00-1FA0

2000/1

N2XSY (10kV) 3x(3x1x240)

152

12BBT01GT220

MV INC FDR

12BBF

6.3

7SJ6111-5EB00-1FA0

2000/1

N2XSY (10kV) 3x(3x1x240)

152

12BBT01GT230

MV INC FDR

11BBF

6.3

7SJ6111-5EB00-1FA0

2000/1

N2XSY (10kV) 3x(3x1x240)

161

12BBT01GT240

MV INC FDR

11BBE

6.3

7SJ6111-5EB00-1FA0

2000/1

N2XSY (10kV) 3x(3x1x240)

161

10BFJ00GS001

BUS COUPLER *BFJ-BFK*

10BFJ

0.4

3WL1232-3FB35-5FA4-Z

3200

10BFJ00GS002

TIE FDR *10BJJ*

10BFJ

0.4

3WL1112-3FG35-5FA4-Z

1250

N2XY-O (1kV) 3x(3x1x240)/2x240

15

10BFT01GT002

LV INC FEEDER

10BMA

0.4

3WL1232-3FG35-5FA4-Z

3200

LXC0741 (1kV) 3x1,586/2x1,586

10BFT02GT002

LV INC FEEDER

10BMB

0.4

3WL1232-3FG35-5FA4-Z

3200

LXC0741 (1kV) 3x1,586/2x1,586

10BHT01GT002

LV INC FEEDER

10BFJ

0.4

3WL1232-3FG35-5FA4-Z

3200

LXC0741 (1kV) 3x1,586/2x1,586

10BHT02GT002

LV INC FEEDER

10BFK

0.4

3WL1232-3FG35-5FA4-Z

3200

LXC0741 (1kV) 3x1,586/2x1,586

10BMA00GS001

BUS COUPLER *BMA-BMB*

10BMA

0.4

3WL1232-3FB35-5FA4-Z

3200

Annex 1: Table of Input Data

Editor: H. Specht
Ord. No.: si0368

Document No.:

PG W 741

Project:

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS AND VOLTAGE DROP

KKS

Designation

ID-Code

Switchgear

Un
[kV]

Protection Device
Name

Fuse
ln

No.

[A]

CT

ln
[A]

[A/A]

Cable
CT
[A/A]

EGY263-BN02-B-700021
NEW TALKHA 750 MW CCPP

Date:

B / 2005-10-21

Page:

10 of 11

Cable
Type

l
[m]

10BMA00GS011

LV TIE FEEDER *11BME*

10BMA

0.4

3WL1106-3FG35-5FA4-Z

630

N2XY-O (1kV) 2x(3x1x240)/240

101

10BMB00GS012

LV TIE FEEDER *12BME*

10BMB

0.4

3WL1106-3FG35-5FA4-Z

630

N2XY-O (1kV) 2x(3x1x240)/240

137

11BFE00GS001

BUS SECTIONALIZER BFE/BME

11BFE

0.4

3WL1106-3FB35-4GA4-Z

630

11BFE00GS002

GT 400V SWGR INC FDR

11BFE

0.4

3WL1112-3FB35-4GA4-Z

1250

11BFG00GS001

BUS COUPLER *BFG-BFH*

11BFG

0.4

3WL1232-3FB35-5FA4-Z

3200

11BFG00GS002

TIE FDR *11BFE*

11BFG

0.4

3WL1112-3FG35-5FA4-Z

1250

N2XY-O (1kV) 3x(3x1x240)/2x240

89

11BFH00GS003

TIE FDR *11BJH*

11BFH

0.4

3WL1106-3FG35-5FA4-Z

630

N2XY-O (1kV) 2x(3x1x240)/240

15

11BFT01GT002

LV INC FEEDER

11BFG

0.4

3WL1232-3FG35-5FA4-Z

3200

LXC0741 (1kV) 3x1,586/2x1,586

11BFT02GT002

LV INC FEEDER

11BFH

0.4

3WL1232-3FG35-5FA4-Z

3200

LXC0741 (1kV) 3x1,586/2x1,586

11BME00GS001

GT 400V SWGR INC FDR

11BME

0.4

3WL1106-3FB35-4GA4-Z

630

N2XY-O (1kV) 2x(3x1x240)/240

101

12BFE00GS001

BUS SECTIONALIZER BFE/BME

12BFE

0.4

3WL1106-3FB35-4GA4-Z

630

12BFE00GS002

GT 400V SWGR INC FDR

12BFE

0.4

3WL1112-3FB35-4GA4-Z

1250

12BFG00GS001

BUS COUPLER *BFG-BFH*

12BFG

0.4

3WL1232-3FB35-5FA4-Z

3200

12BFG00GS002

TIE FDR *12BFE*

12BFG

0.4

3WL1112-3FG35-5FA4-Z

1250

N2XY-O (1kV) 3x(3x1x240)/2x240

143

12BFH00GS003

TIE FDR *12BJH*

12BFH

0.4

3WL1106-3FG35-5FA4-Z

630

N2XY-O (1kV) 2x(3x1x240)/240

15

12BFT01GT002

LV INC FEEDER

12BFG

0.4

3WL1232-3FG35-5FA4-Z

3200

LXC0741 (1kV) 3x1,586/2x1,586

12BFT02GT002

LV INC FEEDER

12BFH

0.4

3WL1232-3FG35-5FA4-Z

3200

LXC0741 (1kV) 3x1,586/2x1,586

12BME00GS001

GT 400V SWGR INC FDR

12BME

0.4

3WL1106-3FB35-4GA4-Z

630

N2XY-O (1kV) 2x(3x1x240)/240

137

Annex 1: Table of Input Data

N2XY-O (1kV) 3x(3x1x240)/2x240


-

N2XY-O (1kV) 3x(3x1x240)/2x240


-

89
-

143
-

Editor: H. Specht
Ord. No.: si0368

Document No.:

PG W 741

Project:

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS AND VOLTAGE DROP

Annex 1.8:

ID-Code

NEW TALKHA 750 MW CCPP

Date:

B / 2005-10-21

Page:

11 of 11

MV/LV Switchgear Cubicles for Synchronous Machines

Un
Protection Device Name
Protection Device I n
Fuse No.
Fuse I n
CT
Cable CT
Cable Type
Cable l
Name
Sn
Type

KKS

EGY263-BN02-B-700021

Nominal voltage of panel in kV


Order number of protection device (MFLB)
Nominal current of protection device (feeder bimetal range end) in A
Number of fuses
Nominal current of fuse in A
Transformer ratio of current transformer in A/A
Transformer ratio of cable current transformer in A/A
Type of cable (corresponding cable data in table ''Cables")
Length of cable in m
Name of synchronous machine
Rated apparent power of synchronous machine in kW
Type (corresponding data see table ''Synchronous Machines")

Designation

Switch-

Un

gear

[kV]

Protection Device
Name

ln
[A]

CT
[A/A]

Cable
CT
[A/A]

Synchronous Machine

Cable
Type

l
[m]

Name

Sn
[MVA]

Type

10XKA11GS001

EMDG INC FEEDER

10BMA

0.4

3WL1232-3FB35-5FA4-Z

3200

N2XY-O (1kV) 6x(3x1x240)/3x240

73

10XKA11

1.65

XKA

10XKA11GS002

EMDG INC FEEDER

10BMB

0.4

3WL1232-3FB35-5FA4-Z

3200

N2XY-O (1kV) 6x(3x1x240)/3x240

73

10XKA11

1.65

XKA

Annex 1: Table of Input Data

Editor: H. Specht
Ord. No.: si0368

BB I

10

12

11

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

3~ 220kV 50Hz

ADA
BB II

F02

F03

11ADA02GS001 (QL1)
GS001 (QL1)
11ADA02GS101 (QE1)
GS101 (QE1)

11ADC02GS001 (QL8)
GS001 (QL8)
11ADC02GS101 (QE8)
GS101 (QE8)

CT1

12ADA03GS001 (QL1)
GS001 (QL1)
12ADA03GS101 (QE1)
GS101 (QE1)

CT6

CT5
11ADC02GS191 (QE7)
GS191 (QE7)

11ADA02GS091 (QL2)
11ADA02GS193 (QE9)
GS091 (QL2)
GS193 (QE9)
TV1

11BAT01GT101
GT101

1200/1A
1200/1A
30VA 5P20 30VA 5P20

180/240/300MVA
30C mean a. temp.
ONAN/ONAF1/ONAF2
2404x2,5%/16,5kV
YNd1, uk=16%

13000/1A
30VA 5P20

11ADC02GS091 (QL7)
GS091 (QL7)
11ADC02GS193 (QE10)
GS193 (QE10)

11ADA02GS009 (QL3)
GS009 (QL3)

11ADB02GS171 (QE4)
GS171 (QE4)

11ADB02GS172 (QE5)
GS172 (QE5)

1
8W /30sec

2000/1A
20VA 5P20

11BBT01GS410

750/1A
10VA 5P20
3

4000/1A
30VA 5P20

4000/1A
30VA 5P20

750/1A
10VA 5P20

QL6

12ADA03GS009 (QL3)
GS009 (QL3)

Y
11BBT01GS420

12BBT01GS410

2000/1A
20VA 5P20

750/1A
10VA 5P20

750/1A
10VA 5P20
4000/1A
30VA 5P20

12ADB03GS171 (QE4)
GS171 (QE4)

A
12BBT01GT241
GT241

2000/1A
10VA 0,5FS5

BATTERY

2000/1A
10VA 10P10

12BBT01GS420

2000/1A
20VA 5P20

12
10

3~ 6,3kV 2500A 50Hz 31,5kA 1s


09
08

11MKC01GT001
M
GT001

11MBN12AP001
M
AP001

500/1A
10VA 10P10

200/1A
10VA 10P10

100/1A
10VA 10P10

100/1A
10VA 1FS5

11MBJ01GT101
GT101

11MKC01GT101
GT101

11MBN12AP101
AP101

M
PLANT-DCS

.../1A
10VA 10P10

50/1A
10VA 1FS5

03

11BBE00GS001
GS001

M
PLANT-DCS

50/1A
10VA 10P10

11BBF

04

11MBU25AP001
AP001

02

G
3

3
6,3:v3/0,1:v3kV
50VA Cl.0,5

12BBT01GT240
GT240

.../1A
10VA 1FS5

11MBU25AP101
AP101

11BBE00GS101
GS101

07

00LAC11AP001
M
AP001

300/1A
10VA 10P10

12BFT02GT001
M
GT001

300/1A
10VA 1FS5

200/1A
10VA 10P10

09
11BBF00GS100
GS100

10BFT01GT001
GT001

200/1A
10VA 1FS5

00LAC11AP101
AP101

05

06

12BFT02GT101
GT101

11BFT01GT001
M
GT001

200/1A
10VA 10P10

200/1A
10VA 10P10

200/1A
10VA 1FS5

200/1A
10VA 1FS5

10BFT01GT101
GT101

50/1A
10VA 10P10

50/1A
10VA 1FS5

11BFT01GT101
GT101

10PGC11AP101
AP101

12BAA

DC/DC CONVERTER

100/1A
10VA 10P10
100/1A
10VA 1FS5

04

05

1000/1A
10VA 0,5FS5
1000/1A
10VA 10P10

00LCB11AP101
AP101

500/1A
10VA 10P10

11BBF00GS101
GS101

200/1A
10VA 10P10

200/1A
10VA 10P10

12MBJ01GT101
GT101

12MBN12AP001
M
AP001

12BFT01GT101
GT101

50/1A
10VA 10P10

100/1A
10VA 1FS5

04

03

06

12MBU25AP001
12BBE01GS001
00LAC13AP001
M
M
M
AP001
GS001
AP001
PLANT-DCS
PLANT-DCS

100/1A
10VA 10P10

200/1A
10VA 1FS5

12MKC01GT101
GT101

12BBF

3~ 6,3kV 2500A 50Hz 31,5kA 1s


09
08

12BFT01GT001
M
GT001

11BBF00GS102
GS102

07

.../1A
10VA 1FS5

3
6,3:v3/0,1:v3kV
50VA Cl.0,5

01

12MKC01GT001
GT001

11BBT01GT240
GT240

12
10

12MBJ01GT001
GT001

2000/1A
20VA 5P20

2000/1A
10VA 10P10

2000/1A
20VA 5P20

.../1A
10VA 10P10

2000/1A
10VA 10P10

11BBT01GT231
GT231

2000/1A
10VA 0,5FS5

02
11

12
12BBE00GS100
GS100

11BBF00GS001
11BBF00GS002
M
GS001
GS002
PLANT-DCS

2000/1A
10VA 0,5FS5

GT210

12BBE

08

11BBT01GT241
GT241

3
6,3:v3/0,1:v3kV
12BBT01GT210 50VA Cl.0,5

02

10PGC11AP001
00LCB11AP001
M
M
AP001
AP001
PLANT-DCS

12BBT01GT230
GT230

01 3~ 6,3kV 2500A 50Hz 31,5kA 1s


06
03

09
07

2000/1A
20VA 5P20

11BBT01GT220
GT220

2000/1A
10VA 10P10

2000/1A
20VA 5P20

12BBT01GT211
GT211

2000/1A
10VA 0,5FS5

2000/1A
10VA 10P10

2000/1A
20VA 5P20

11MBJ01GT001
M
GT001

EARTHING LINK

INVERTER

2
12BBT01GT231
GT231

2000/1A
10VA 0,5FS5

2000/1A
10VA 10P10

01
11

12
11BBE00GS100
GS100

CHARGER

3
11BBT01GT221
GT221

2000/1A
10VA 0,5FS5

GT210

11BBE

LINK

3
6,3:v3/0,1:v3kV
11BBT01GT210
50VA Cl.0,5

11BAA

QL6

12ADB03GS172 (QE5)
GS172 (QE5)

8W /30sec
2000/1A
20VA 5P20

4000/1A
30VA 5P20

11BBT01GT211
GT211

MANUAL OPERATED

LIMIT OF SUPPLY

CABLE CONNECTION

12ADB03GS072 (QL5)
GS072 (QL5)

12ADA03GS080 (QE3)
GS080 (QE3)

8W /30sec

8W /30sec
2000/1A
20VA 5P20

TRANSFORMER WITH
OFF-LOAD TAP CHANGER

QE6

32/16/16MVA
30C
19,2/9,6/9,6MVA ONAN/ONAF
16,59x1,25%/6,6/6,6kV
Dyn11yn11, uk=10%
1

12ADB03GS010 (QF2)
GS010 (QF2)
CT4

LIMIT OF SUPPLY

THREE-WINDING TRANSFORMER

1200/1A
30VA 5P20

12BBT01

VOLTAGE TRANSFORMER2xSEC.
2xSEC.

1200/1A
15VA 0,2FS10

11ADA02GS080 (QE3)
GS080 (QE3)

12ADC03GS091 (QL7)
GS091 (QL7)
12ADC03GS193 (QE10)
GS193 (QE10)

12ADB03GS071 (QL4)
GS071 (QL4)
CT3

1200/1A
30VA 5P20

QE6

32/16/16MVA
30C
19,2/9,6/9,6MVA ONAN/ONAF
16,59x1,25%/6,6/6,6kV
Dyn11yn11, uk=10%

VOLTAGE TRANSFORMER(VT)
(VT)

TRANSFORMER WITH
ON-LOAD TAP CHANGER

CT5
12ADC03GS191 (QE7)
GS191 (QE7)

12ADA03GS091 (QL2)
12ADA03GS193 (QE9)
GS091 (QL2)
GS193 (QE9)
TV1

12BAT01GT101
GT101

13000/1A
30VA 5P20

11BBT01

1200/1A
30VA 5P20

1200/1A
1200/1A
30VA 5P20 30VA 5P20

1200/1A
15VA 0,2FS10

1200/1A
30VA 5P20

180/240/300MVA
30C mean a. temp.
ONAN/ONAF1/ONAF2
2404x2,5%/16,5kV
YNd1, uk=16%

11ADB02GS072 (QL5)
GS072 (QL5)

1200/1A
30VA 5P20

12BAT01

11ADB02GS010 (QF2)
GS010 (QF2)
CT4

CURRENT TRANSFORMER(CT)
(CT)

1200/1A
30VA 0,2FS10

TV2

11ADB02GS071 (QL4)
GS071 (QL4)
CT3

1200/1A
30VA 5P20

G
3~

12ADC03GS010 (QF3)
GS010 (QF3)

CT2
12ADA03GS191 (QE2)
GS191 (QE2)

1200/1A
30VA 5P20

3
3

LIMIT OF SUPPLY

1200/1A
30VA 5P20

11BAT01

GENERATOR

CT6

12ADA03GS010 (QF1)
GS010 (QF1)

1200/1A
30VA 0,2FS10

1200/1A
30VA 5P20

11ADC02GS010 (QF3)
GS010 (QF3)

CT2
11ADA02GS191 (QE2)
GS191 (QE2)

1200/1A
30VA 5P20

Z
11ADA02GS010 (QF1)
GS010 (QF1)

LIMIT OF SUPPLY

12ADC03GS001 (QL8)
GS001 (QL8)
12ADC03GS101 (QE8)
GS101 (QE8)

CT1

SYMBOL DESCRIPTION

50/1A
10VA 1FS5

12MBN12AP101
AP101

.../1A
10VA 10P10

.../1A
10VA 1FS5

12MBU25AP101
AP101

3
3

12BBE01GS101
GS101

300/1A
10VA 10P10

10BFT02GT001
GT001

00LAC13AP101
AP101

2000/1A
10VA 0,5FS5
2000/1A
10VA 10P10

01

MINIATURE CIRCUIT-BREAKER (MCB) ORMOULDED CASECIRCUIT BREAKER (MCCB)


MOULDED CASECIRCUIT BREAKER (MCCB) RESISTOR
CIRCUIT BREAKER (MCCB)

12BBT01GT220
GT220

3~ 6,3kV 2500A 50Hz 31,5kA 1s


06
10

SMOOTHING CHOKE

2000/1A
20VA 5P20

11BBT01GT230
GT230

CIRCUIT BREAKER

2000/1A
10VA 10P10

2000/1A
20VA 5P20

LIGHTNING/SURGEARRESTER
ARRESTER

2000/1A
10VA 0,5FS5

LOAD-BREAK SWITCH

02
08

03

04

05
DIODE

11BFT02GT001
M
GT001

200/1A
10VA 1FS5

09
07

09
12BBF00GS100
GS100

200/1A
10VA 10P10

300/1A
10VA 1FS5

05

12BBT01GT221
GT221

NEUTRAL GROUNDINGTRANSF
E
TRANSFORMER WITHLOADING
LOADING RESISTANCE AND CT
ON THE SECONDARY

10BFT02GT101
GT101

200/1A
10VA 10P10

10PGC12AP001
00LAC12AP001
M
M
AP001
AP001
PLANT-DCS

200/1A
10VA 1FS5

50/1A
10VA 10P10

50/1A
10VA 1FS5

11BFT02GT101
GT101

10PGC12AP101
AP101

300/1A
10VA 10P10
300/1A
10VA 1FS5

12BBF00GS001 00LCB12AP001 12BBF00GS002


M
M
GS001
AP001
GS002
PLANT-DCS
PLANT-DCS

3
3

1000/1A
10VA 0,5FS5
1000/1A
10VA 10P10

00LAC12AP101
AP101

3
3

12BBF00GS101
GS101

100/1A
10VA 10P10
100/1A
10VA 1FS5

3
3

00LCB12AP101
AP101

DISCONNECTING SWITCH/ISOLATOR(DS)
(DS)

.../1A
10VA 10P10

GAS TURBINE

GT

.../1A
10VA 1FS5

EARTHING SWITCH(ES)
(ES)

12BBF00GS102
GS102

OPERATED BY ELECTRIC MOTOR

CONTACTOR WITH FUSE

H
1

100/1A
1VA 10P5

11MBJ01

100/1A
1VA 10P5

100/1A
1VA 10P5

100/1A
1VA 10P5

100/1A
1VA 10P5

100/1A
1VA 10P5

100/1A
1VA 10P5

100/1A
1VA 10P5

100/1A
1VA 10P5

100/1A
1VA 10P5

100/1A
1VA 10P5

100/1A
1VA 10P5

100/1A
1VA 10P5

11MKC01

2570kVA
6,32x2,5%/1,8kV
Dy5
uk=5%

12MBJ01

1650kVA
6,32x2,5%/0,66kV
Dy5
uk=6%

650kW

M
3~

365kW

11BAC

M
3~

300kW

11MBN12FUEL
11MBU25NOXWATERPUMP
OILINJECTION PUMP
SPARE
FUEL OILINJECTION
NOXWATERPUMP
PUMP
INJECTION PUMP
WATERPUMP
PUMP
PUMP

TOHP FD WTRPUMP
TOCTG
(A)(BY
2LOAD
OTHERS)
CENTER
HP FD WTRPUMP (A)(BY
CTG 2LOAD
OTHERS)
CENTER
PUMP (A)(BY OTHERS)
LOAD CENTER
(BY OTHERS)

SPACE

M
3~

TOCTG 1LOAD
10PGC11CLOSEDCOOLING
CENTER
TOCONDENSATEPUMP(BY
WATERPUMP
TIE FEEDER*10BBE*
OTHERS)
SPARE
CTG 1LOAD CENTER
CLOSEDCOOLING
CONDENSATEPUMP(BY
WATERPUMP
*10BBE*OTHERS)
LOAD CENTER
COOLING WATERPUMP
PUMP(BY OTHERS)
PUMP
(BY OTHERS)
750kVA
J

2250kVA

2570kVA
6,32x2,5%/1,8kV
Dy5
uk=5%

SPACE

PROTECTIONMEASURING
MEASURING
11BFG00GS001
11BFT01GT002
GS001
GT002

M
M
16,5:v3/0,1:v3kV
45VA Cl.0,2
16,5:v3/0,1:3kV
6P 100VA

PROTECTIONMEASURING
MEASURING
10BFT01GT002
GT002

10BMA
05

01
03

02

11BFH00GS003 10BTL22GU001
M
GS003
GU001

11BFH00GS001
11BFH00GS002M
M
GS001
GS002
PLANT-DCS
PLANT-DCS
M

07

3/PEN 400V 50Hz 65kA 1s


3000A
04

02

02

13000/1A
30VA 0,2FS10

11BFE3/PEN 400V 50Hz 50kA 1s

12BAC01GS009
M
GS009

10BFT02GT002
GT002

06

01

3/PEN 400V 50Hz 65kA 1s


3000A 03
04
02

06

02

02

10XKA11GS002
PLANT-DCS
GS002

10BMB00GS002
10BTL12GU001
10BMB00GS012
10BTL21GU001
M
GS002
GU001
GS012
GU001

10BRT01

10BRT02GT001
GT001

LIMIT OF SUPPLY

M
3~

10PGC12CLOSEDCOOLING
TIE
WATERPUMP
FEEDER*10BBF*
CONDENSATEPUMP(BY
SPACE
SPARE OTHERS)
TOCTG 1LOAD
CENTER
HPFD WTRPUMP
(B)(BY
OTHERS)
CLOSEDCOOLING
WATERPUMP
*10BBF*
PUMP(BY OTHERS)
CTG 1LOAD CENTER
FD WTRPUMP
(B)(BY OTHERS)
LOAD CENTERCOOLING WATERPUMP
PUMP (B)(BY OTHERS) (BY OTHERS)
750kVA
PUMP
(BY OTHERS)

2250kVA

11BJH

3/PEN 400V 50Hz 50kA 1s

1000A

10BTA10GS010
GS010

01

10BTL12

1000A

11BTL10GU001
GU001

11BTL20GU001
M
GU001

11BTA10

13000/1A
30VA 5P20

11BME00GS001
GS001

10BTA10GS020
GS020

10BUD

10BTL11GS011
GS011
2/PE DC 125V

10XKA11

11BTL10

11BTL20

63A

13000/1A
30VA 5P20

10BRU01GU001
GU001

11BTA10GS020
GS020

3000/1A
30VA 10P10

10BUE

12BAA20

10BTA20GS010
GS010

12MKA
12MBA

10BRU02GU001
GU001

-T1 L1,L2,L3
3

UBN
3

12BAA10

11BUK01GS001
GS001

4,13W/150A

11MKA

11BUC
11BUB00GS001
GS001

11BTL20GS011
GS011
2/PE 220V DC

10BRU01
50kVA

11BUK02GS001
GS001

11BUK01

11BUK02

11BAB11

ici ty
ct r
Pr o
du

THE ARAB REPUBLIC OF EGYPT

NEW TALKHA POWER STATION 750MW COMBINED CYCLE PRO

12BME 3/PEN 400V 50Hz 50kA 1s

12BJH

JOB NO

3/PEN 400V 50Hz 50kA 1s

01

01

12BTL10GU001
GU001

12BTL20GU001
M
GU001

12BTA10

13000/1A
30VA 5P20

12BTL10

12BTL20

63A

13000/1A
30VA 5P20

12BTA10GS020
GS020

2004-12-16

SCHNEIDER
SCHWARZ BALLAT

REVISION PROJECT START

2005-01-31

SCHNEIDER
KAISER

BALLAT

DETAIL DESIGN

2005-02-21

SCHNEIDER
KAISER

BALLAT

DETAIL DESIGN/SUPPLEMENTARY MARKING

10BMB

2005-04-25

SCHNEIDER
KAISER

BALLAT

DETAIL DESIGN/SUPPLEMENTARY MARKING

REV.

DATE

DRAWN

CHECKED

DETAILS OF REVISION

COORD.

ORIGINAL

12BUK01GS001
GS001

12MKA

12BTL20GS011
GS011
2/PE 220V DC

12BUC
12BUB00GS001
GS001

ORIGINAL-NO.

PC

NEW TALKHA POWER STATION


DATE

12BUK02GS001
GS001

12BUK02

NAME

TITLE

CONTENTS CODE

2004-07-16 E.SCHNEIDER
2004-07-16 ARNDT

CHECKED

2004-07-16 ARNDT

Siemens AG
Power Generation

I&C- Cabinets

12BAB11

TYPE OF DOC.

COORD.

W743

B
REG. NO.
SINGLE LINE DIAGRAM
RESP. DEPT.
UNID

W743

10

11

12

13

14

15

16

17

18

19

20

REV.INDEX

VERSION

10 567 517

EGY263-YU02-B-700001-H
21

700001

SHEET-NO.

12UBA01/02
6

YU02

SINGLE LINE DIAGRAM 2xGT V94.3A

SUPERSEDED BY

EGY263

SCALE

DRAWN

UNINTERRUPTIBLEPOWER SUPPLY
POWER SUPPLY

ORIG.-PC

PROJECT

12BUK01

13000/1A
30VA 5P20

12BTL10GS011
GS011
2/PE 220V DC

REV.

SERVICES COMPANY

12BME00GS001
GS001

63A

12BTA10GS010
GS010

DRAWING NO.

POWER GENERATION ENGINEERING AND

175Ah

13000/1A
30VA 0,2FS10

11UBA01/02
1

MINISTRY OF ELECTRICITY AND ENERGY

TLRI 115/52

4,13W/150A

90kVA/20sec
16,5:v3/0,5kV

e
El

12BFE00GS001
GS001

12BFE3/PEN 400V 50Hz 50kA 1s

12BUB

I&C- Cabinets

PLANT-DCS CB CONTROLLED BY PLANT DCS

DEPT.

UNINTERRUPTIBLEPOWER SUPPLY
POWER SUPPLY

EAST DELTA ELECTRICITY PRODUCTION COMPANY

12BFE00GS002
GS002

10BRU02
50kVA

HRSG MCC(BYMAIN
OTHERS)
DB2(BY OTHERS)
(BY OTHERS) (BY OTHERS)

03

G
3~

GT
313MVA
15C ambient temp.

13000/1A
30VA 5P20

11BTL10GS011
GS011
2/PE 220V DC

12BFH00GS003
GS003

ISOLATED PHASE BUSDUCT


SFC DISCONNECTING SWITCH
GENERATOR CIRCUIT BREAKER
GENERATOR TRANSFORMER
6,6kV UNIT SWITCHGEAR
UNIT AUXILIARY TRANSFORMER
GT 400V LV SWITCHGEAR
CTG LOAD CENTER
400V LOAD CENTER CRW WATER
LV TRANSFORMER
400V MSC LV SWITCHGEAR
STG LOAD CENTER
GT 400V EM LV SWITCHGEAR
CV TRANSFORMER
INVERTER
DC BATTERY (125V BOP, 220V GT)
DC BATTERY CHARGER
GT 220V DC SWITCHGEAR
125V DC SWITCHGEAR
DC/DC CONVERTER
SEE/SFC CUBICLE
HP FEED WATER PUMP
GAS TURBINE
SFC TRANSFORMER
FUEL OIL INJ PUMP
NOX WATER PUMP
GENERATOR
SEE TRANSFORMER
CIRCULATION PUMP
SERVICE COOLING WATER PUMP
CLOSED COOLING WATER PUMP
FIRE PUMP
EMERGENCY DIESEL SET

PROTECTIONMEASURING
MEASURING

13000/1A
30VA 5P20

16,5kV5%
50Hz, cosv=0,85

3000/1A
10VA 5P5

SPARE

13000/1A
30VA 0,2FS10

1000A

10BTL21GS011
GS011

CTG 2LOAD CENTER


LOAD CENTER

13000/1A
30VA 5P20

-T2 L1,L2,L3

10BTL22GS011
GS011
2/PE DC 125V

12BFH00GS001
12BFH00GS002
M
GS001
GS002
PLANT-DCS
PLANT-DCS
M

05

130nF

10BTL21
10BTA20GS020
GS020

04

3/PEN 400V 50Hz 50kA 1s


03
3000A

4200Ah
1000A

12BFH

10BTA20

10BTL22

3000/1A
30VA 10P10

PROTECTIONMEASURING
MEASURING
12BFT02GT002
GT002
01

06

12BFG00GS002
12BFG00GS003
M
GS002
GS003
PLANT-DCS

BAA
BAB40
BAC
BAT
BBE/BBF
BBT
BFE
BFG/BFH
BFJ/BFK
BFT/BHT
BJH
BMA/BMB
BME
BRT
BRU
BTA
BTL
BUB/BUC
BUD/BUE
BUK
CJT
LAC
MBA
MBJ
MBN
MBU
MKA
MKC
PAC
PCC
PGC
SGA
XKA11

16,5:v3/0,1:v3kV
45VA Cl.0,2

3000/1A
10VA 1FS5

G
3~
3

63A

11BTA10GS010
GS010

1600kVA
cosv=0,8

10BTL12GS011
GS011

175Ah

13000/1A
30VA 0,2FS10

3/PEN 400V 50Hz 50kA 1s


03
04 3000A

1200/1A
5VA 10P10

16,5:v3/0,1:3kV
6P 100VA

-T5 L1,L2,L3

II

4/2

4200Ah

10BTL11

10XKA11GS003
GS003

NO M

TLRI 115/52

90kVA/20sec
16,5:v3/0,5KV

100/1A
1VA 10P5

12BFG00GS001
M
GS001

01

TO11BAB40
11BAB40

16,5:v3/0,1:v3kV
45VA Cl.0,2

10BRT02

12BAC01GS081
GS081

-T6 L1,L2,L3

4/2

PROTECTIONMEASURING
MEASURING
12BFT01GT002
GT002

12CJT01

MSC MCC(BY
V OTHERS) K
(BY OTHERS)

1200/1A
5VA 10P10

12MBJ01GS012
GS012

12MBJ01GS091
GS091
M

1600kVA
6,32x2,5%/0,42kV
Dyn1
uk=6%

12BFG

12BAC01GS001
GS001

INT PROT

STG MCC(BY OTHERS)


(BY OTHERS)

10BTA10

01

11BUB

ELCAD-VERSION: ELCAD 7.1 / WINDOWS


VARIANTE:
STANDARD-NR.:
STANDARD-ERSTELLER:

PROTECTIONMEASURING
MEASURING

STGLOAD CENTER
LOAD CENTER

11BME3/PEN 400V 50Hz 50kA 1s

1600kVA
6,32x2,5%/0,42kV
Dyn1
uk=6%

12BAC01GS082
GS082

1/N/PE~230V 50Hz
~230V 50Hz

11BAA10

100/1A
1VA 10P5

12BFT02

16,5:v3/0,1:v3kV
22,5VA Cl.0,2

1/N/PE~230V 50Hz
~230V 50Hz

TRANSLATE:
EGY263.SPZ/2005-05-30/SCHN
ELCAD-PROJEKT:EGY263 / SLD
ELCAD-PLAN:
GESAMT/YU02/B/700001
STAND:
2005-06-27
FORMBLATT:CY08

100/1A
1VA 10P5

i o n Co .

100/1A
1VA 10P5

ct

-T1 L1,L2,L3

10BMB

INT PROT
10BRT01GT001
3
GT001
10XKA11GS001
M
GS001

10BMA00GS01110BTL11GU001 M
10BMA00GS002
GS011
GU001
GS002
PLANT-DCS

PROTECTIONMEASURING
MEASURING
11BFE00GS001
11BFE00GS002
GS001
GS002

03

SPACE
12MBN12FUEL OILINJECTIONPUMP
12MBU25NOX WATERPUMP
SPARE
HPFEEDWATERPUMP
TOSTGLOAD
(C)(BY
CENTER
OTHERS)
FUEL OILINJECTIONPUMP
NOX WATERPUMP
FEEDWATERPUMPSTGLOAD
(C)(BY OTHERS)
CENTER
INJECTIONPUMP PUMP
PUMP (C)(BYLOAD
OTHERS)
CENTER
PUMP
(BY OTHERS)
N
2250kVA

16,5kV5%
50Hz, cosv=0,85

10BMA00GS001
GS001

II

313MVA
15C ambient temp.

1200/1A
5VA 10P10

U
HRSG MCC(BY
WATERTREATM.MCC(BY
OTHERS)
OTHERS)
MAIN DB1(BY OTHERS)
(BY OTHERS) TREATM.MCC(BY OTHERS)
(BY OTHERS)
POWERINVERTER10BTL22
MCC(BY OTHERS)
INVERTER10BTL22
(BY OTHERS)
10BTL22

16,5:v3/0,1:v3kV
45VA Cl.0,2

G
3~

11MBA GT

100/1A
1VA 10P5

Copying of this document and giving it to others and the


use or communication of the contents thereof, are forbidden
without express authority. Offenders are Liable to the payment of damages. All rights are reserved in the event of the
grant of a patent or the registration of a utility model or design.

-T7 L1,L2,L3

13000/1A
30VA 5P20

11BAA20

CTG 1LOAD CENTER


LOAD CENTER

13000/1A
30VA 5P20

11MKA

1200/1A
5VA 10P10

130nF

-T2 L1,L2,L3

100/1A
1VA 10P5

300kW

12CJT01

PROTECTIONMEASURING
MEASURING
11BFT02GT002
GT002

01
11BFH3/PEN 400V 50Hz 50kA 1s
04
03
3000A

06

11BFG00GS002
11BFG00GS003
M
GS002
GS003
PLANT-DCS

01
11BFG3/PEN 400V 50Hz 50kA 1s
03
04 3000A

1200/1A
5VA 10P10

1600kVA
6,32x2,5%/0,42kV
Dyn1
uk=6%

11BAB40

1600kVA
6,32x2,5%/0,42kV
Dyn1
uk=6%

11MBJ01GS071
GS071
TO12CJT01

11BAC01GS081
GS081

-T5 L1,L2,L3

100/1A
1VA 10P5

M
3~

365kW

12BFT01

11CJT01

100/1A
1VA 10P5

East D
el t

1200/1A
5VA 10P10

11MBJ01GS012
GS012

11MBJ01GS091
GS091

1600kVA
6,32x2,5%/0,42kV
Dyn1
uk=6%

11BAC01GS001
GS001

-T6 L1,L2,L3

M
3~

650kW

16,5:v3/0,1:3kV
6P 100VA
16,5:v3/0,1:v3kV
22,5VA Cl.0,2

SFC 4.0

11BAC01GS009
M
GS009

-T8 L1,L2,L3

10BFT02

SFC 4.0

11BAC01GS082
GS082

1650kVA
6,32x2,5%/0,66kV
Dy5
uk=6%

1600kVA
6,32x2,5%/0,42kV
Dyn1
uk=6%

16,5:v3/0,1:v3kV
22,5VA Cl.0,2

10BFT01

SEE 660/1650

11BFT02

-T7 L1,L2,L3

100/1A
1VA 10P5

12MKC01

SEE 660/1650

11BFT01
3

100/1A
1VA 10P5

16,5:v3/0,1:v3kV
45VA Cl.0,2

16,5:v3/0,1:3kV
6P 100VA
16,5:v3/0,1:v3kV
22,5VA Cl.0,2

100/1A
1VA 10P5

130nF
16,5:v3/0,1:v3kV
45VA Cl.0,2

-T8 L1,L2,L3

100/1A
1VA 10P5

12BAC

130nF
3

100/1A
1VA 10P5

22

23

24

25

26

27

28

29

30

2
SUPERSEDES

31

32

33

10

12

11

13

14

15

16

17

18

19

20

21

22

23

24

SYMBOL DESCRIPTION
A

A
GENERATOR

G
3~

CURRENT TRANSFORMER(CT)
(CT)

TRANSFORMER WITH
ON-LOAD TAP CHANGER

TRANSFORMER WITH
OFF-LOAD TAP CHANGER

VOLTAGE TRANSFORMER(VT)
(VT)

VOLTAGE TRANSFORMER2xSEC.
2xSEC.

CABLE CONNECTION

MANUAL OPERATED

THREE-WINDING TRANSFORMER
LINK

BATTERY

CHARGER

EARTHING LINK

INVERTER

S
10BBE00GS101
GS101

DC/DC CONVERTER

10BBF00GS101
GS101

E
LIGHTNING/SURGEARRESTER
ARRESTER
1000/1A
10VA 0,5FS5

3
6,3:v3/0,1:v3kV
50VA Cl.0,5

10BBE

09
07

09
10BBE00GS100
GS100

01

G
3
3

3
6,3:v3/0,1:v3kV
50VA Cl.0,5

10BBF

3~ 6,3kV 2500A 50Hz 31,5kA 1s


05
03

02

04

08

00PAC01AP001
00PAC03AP001A
10BBE00GS002
M
M
M
AP001
AP001A
GS002
PLANT-DCS
PLANT-DCS
PLANT-DCS

10PCC11AP001
AP001

1000/1A
10VA 10P10

10BBE00GS001
GS001

1000/1A
10VA 10P10

50/1A
10VA 1FS5

10PCC11AP101
AP101

300/1A
10VA 10P10
300/1A
10VA 1FS5

3
3

00PAC01AP101
AP101

300/1A
10VA 10P10
300/1A
10VA 1FS5

3
3

00PAC03AP101A
AP101A

.../1A
10VA 10P10

.../1A
10VA 1FS5

10BBE00GS102
GS102

SMOOTHING CHOKE

MINIATURE CIRCUIT-BREAKER (MCB) ORMOULDED CASECIRCUIT BREAKER (MCCB)


MOULDED CASECIRCUIT BREAKER (MCCB) RESISTOR
CIRCUIT BREAKER (MCCB)

01

LOAD-BREAK SWITCH

3~ 6,3kV 2500A 50Hz 31,5kA 1s


03
02

06

08
10BBF00GS100
GS100

10BHT01GT001
GT001

50/1A
10VA 10P10

06

CIRCUIT BREAKER

10BBF00GS001
GS001

08

1000/1A
10VA 0,5FS5

NEUTRAL GROUNDINGTRANSFORMER WITHL


E
TRANSFORMER WITHLOADING RESISTANCE
LOADING RESISTANCE AND CTON THE SECO
ON THE SECONDARY

05

07

04
DIODE

10PCC12AP001
00PAC02AP001
00PAC03AP001B
10BBF00GS002
M
M
M
M
AP001
AP001
AP001B
GS002
PLANT-DCS
PLANT-DCS
PLANT-DCS

10BHT02GT001
GT001

50/1A
10VA 10P10

200/1A
10VA 10P10

200/1A
10VA 10P10

200/1A
10VA 1FS5

50/1A
10VA 1FS5

10BHT01GT101
GT101

10PCC12AP101
AP101

300/1A
10VA 10P10

300/1A
10VA 1FS5

00PAC02AP101
AP101

300/1A
10VA 10P10

300/1A
10VA 1FS5

00PAC03AP101B
AP101B

.../1A
10VA 10P10

.../1A
10VA 1FS5

10BBF00GS102
GS102

DISCONNECTING SWITCH/ISOLATOR(DS)
(DS)

G
GAS TURBINE

GT
EARTHING SWITCH(ES)
(ES)

200/1A
10VA 1FS5

10BHT02GT101
GT101

OPERATED BY ELECTRIC MOTOR

CONTACTOR WITH FUSE

H
1

260kW

100/1A
1VA 10P5

M
3~

SPACE

10PCC11
J

100/1A
1VA 10P5

100/1A
1VA 10P5

100/1A
1VA 10P5

100/1A
1VA10P5

CIRCULATIONPUMP
CIRCULATIONPUMP
(A)(BY OTHERS)
(C)(BY OTHERS)
SPARE
PUMP (A)(BY OTHERS)
PUMP (C)(BY OTHERS)
(BY OTHERS) (BY OTHERS)

SERVICE COOLINGWATER PUMP


WATER PUMP

2060kVA

100/1A
1VA 10P5

SPACE

260kW

100/1A
1VA 10P5

100/1A
1VA 10P5

100/1A
1VA10P5

LIMIT OF SUPPLY

CIRCULATIONPUMP
CIRCULATIONPUMP
(B)(BY OTHERS)
(C)(BY OTHERS)
SPARE
PUMP (B)(BY OTHERS)
PUMP (C)(BY OTHERS)
(BY OTHERS) (BY OTHERS)

M
3~

10PCC12

2060kVA

100/1A
1VA 10P5

2060kVA

SERVICE COOLINGWATER PUMP


WATER PUMP

SPACE

2060kVA

10BHT01

10BHT02

1600kVA
6,32x2,5%/0,42kV
Dyn1
uk=6%

50/1A
10VA 10P10

PROTECTIONMEASURING
MEASURING

50/1A
10VA 10P10

10BFJ00GS001
GS001

10BHT01GT002
GT002

PROTECTIONMEASURING
MEASURING
10BHT02GT002
GT002

01
03

04

10BFJ00GS002 M
10BFJ00GS003
GS002
GS003
PLANT-DCS

06

10BFK

02

10BTL31GU001
GU001

10BTL42GU001
GU001

3/PEN 400V 50Hz 50kA 1s


02
02

10BTL32GU001
GU001

01
03

10BTL41GU001
GU001

M
PLANT-DCS

10BFK00GS003
GS003

04

M
PLANT-DCS

05

10BFK00GS002
GS002

TO10BTL42
10BTL42

+10BTL30

TO10BFJ
10BFJ
+10BTL40

10BTA30

10BTA40

80Ah

10BTL32

TRANSLATE:
EGY263.SPZ/2005-05-30/SCHN
ELCAD-PROJEKT:EGY263 / SLD
ELCAD-PLAN:
GESAMT/YU02/B/700002
STAND:
2005-06-27
FORMBLATT:CY05

20A

10BTA30GS010
GS010

10BUF

10BUG

East D
el t

MINISTRY OF ELECTRICITY AND ENERGY

NEW TALKHA POWER STATION 750MW COMBINED CYCLE PRO


JOB NO

DRAWING NO.

REV.

POWER GENERATION ENGINEERING AND

SERVICES COMPANY

10BTA40GS020
GS020

M
3~

10SGA01AP001
10BTL32GS011
GS011

20A

10BTA40GS010
GS010

10BTA30GS020
GS020

10BTL31GS011
GS011
2/PE DC 125V

THE ARAB REPUBLIC OF EGYPT

10SGA01GH001
FIR FIGH E-PMP CTRL PANL

10BTL42

20A

ici ty
ct r
Pr o
du

CRWWATERMCC(BY OTHERS)
WATERMCC(BY OTHERS)
MCC(BY OTHERS)
SPARE FOROWNER USE
(BY OTHERS)
OWNER USE

220kVA

10BTL41GS011
GS011
2/PE DC 125V

2004-12-16

SCHNEIDER
SCHWARZ BALLAT

REVISION PROJECT START

2005-01-31

SCHNEIDER
KAISER

BALLAT

DETAIL DESIGN

2005-02-21

SCHNEIDER
KAISER

BALLAT

DETAIL DESIGN/SUPPLEMENTARY MARKING

2005-04-25

SCHNEIDER
KAISER

BALLAT

DETAIL DESIGN/SUPPLEMENTARY MARKING

REV.

DATE

DRAWN

CHECKED

DETAILS OF REVISION

COORD.

ORIGINAL

ORIGINAL-NO.

ORIG.-PC

FIRE FIGHTING PUMP

10BTL42GS011
GS011

PROJECT

PC

NEW TALKHA POWER STATION


DATE

3/PEN 400V 50Hz 50kA 1s

ELCAD-VERSION: ELCAD 7.1 / WINDOWS


VARIANTE:
STANDARD-NR.:
STANDARD-ERSTELLER:

10BJJ

10BTL41

20A

EAST DELTA ELECTRICITY PRODUCTION COMPANY

80Ah

10BTL31

e
El

i o n Co .

SPARE FOROWNER USE


OWNER USE

PLANT-DCS CB CONTROLLED BY PLANT DCS

CRW WATERLOAD CENTER


LOAD CENTER

ISOLATED PHASE BUSDUCT


SFC DISCONNECTING SWITCH
GENERATOR CIRCUIT BREAKER
GENERATOR TRANSFORMER
6,6kV UNIT SWITCHGEAR
UNIT AUXILIARY TRANSFORMER
GT 400V LV SWITCHGEAR
CTG LOAD CENTER
400V LOAD CENTER CRW WATER
LV TRANSFORMER
400V MSC LV SWITCHGEAR
STG LOAD CENTER
GT 400V EM LV SWITCHGEAR
CV TRANSFORMER
INVERTER
DC BATTERY (125V BOP, 220V GT)
DC BATTERY CHARGER
GT 220V DC SWITCHGEAR
125V DC SWITCHGEAR
DC/DC CONVERTER
SEE/SFC CUBICLE
HP FEED WATER PUMP
GAS TURBINE
SFC TRANSFORMER
FUEL OIL INJ PUMP
NOX WATER PUMP
GENERATOR
SEE TRANSFORMER
CIRCULATION PUMP
SERVICE COOLING WATER PUMP
CLOSED COOLING WATER PUMP
FIRE PUMP
EMERGENCY DIESEL SET

ct

Copying of this document and giving it to others and the


use or communication of the contents thereof, are forbidden
without express authority. Offenders are Liable to the payment of damages. All rights are reserved in the event of the
grant of a patent or the registration of a utility model or design.

3/PEN 400V 50Hz 50kA 1s


02

10BFJ

1600kVA
6,32x2,5%/0,42kV
Dyn1
uk=6%

BAA
BAB40
BAC
BAT
BBE/BBF
BBT
BFE
BFG/BFH
BFJ/BFK
BFT/BHT
BJJ
BMA/BMB
BME
BRT
BRU
BTA
BTL
BUB/BUC
BUD/BUE
BUK
CJT
LAC
MBA
MBJ
MBN
MBU
MKA
MKC
PAC
PCC
PGC
SGA
XKA11

NAME

TYPE OF DOC.

TITLE

CONTENTS CODE

DRAWN

2004-07-16 E.SCHNEIDER

COORD.

2004-07-16 ARNDT

CHECKED

2004-07-16 ARNDT

DEPT.

W743

Siemens AG
Power Generation

EGY263

SCALE

YU02

SINGLE LINE DIAGRAM 2xGT V94.3A


B
REG. NO.
SINGLE LINE DIAGRAM
RESP. DEPT.
UNID

W743

REV.INDEX

700002
VERSION

10 716 625

SHEET-NO.

EGY263-YU02-B-700002-H
SUPERSEDED BY

10

11

12

13

14

15

16

17

18

19

20

21

2
SUPERSEDES

22

23

24

Interconnected System
Sk''Act = 12956 MVA
c=1
R/X = 0.1436

Calculated Case 1:
37.4
87.6

ADA
16254
42.7
42.4
101.9

BB I

MAX. THREE-PHASE SHORT-CIRCUIT CURRENTS


(ACCORDING TO IEC EN 60909-0:2001)

37.4
87.6

3 ~ 220 kV 50 Hz

Operation Mode Configuration 1:

BB II
2.7
7.2

Maximum short-circuit conditions occur at MV switchgear,


if one of the two unit auxiliary transformers 11BBT01/12BBT01 feeds all 6.3 kV switchgear. The unit
auxiliary transformer 11BBT01 is supplied by the unit generator 11MKA connected via unit
transformer 11BAT01 to the 220 kV network. The unit generator 12MKA is in operation and supplies
the network via the unit transformer 12BAT01.

2.6
7.1

2.7
7.2

2.6
7.1

Maximum short-circuit currents occur at LV switchgear 10BMA, if the emergency diesel generator
10XKA11 feeds in parallel to LV transformer 10BFT01 during diesel test. Switchgear 11BFE, 11BME,
11BFG, 11BJH and 11BFH are supplied by LV transformer 11BFT02, where as switchgear 12BFE,
12BME, 12BFG, 12BJH and 12BFH are supplied by LV transformer 12BFT02
and switchgear 10BJJ, 10BFJ and 10BFK are supplied by LV transformer 10BHT02.
40.1
94.7

2.7
7.2

2.6
7.1

11MKC01GT001

500/1A

11MBN12
AP001

11MBU25
AP001

100/1A

200/1A

04

0.3
0.8

03
11BBE00
GS001

00LAC11
AP001

100/1A

50/1A

07

1.6
3.9

06

0.8
1.5

12BFT02GT001

07

10BFT01GT001

200/1A

300/1A

05

1.1
2.3

06

03

11BFT01GT001

10PGC11
AP001

00LCB11
AP001

05

14.9
36.5

47
14.9
14.7
36.5

0.0
0.0

0.0
0.0

23.6
57.9

27
23.6
23.6
57.9

259
23.7
20.6
50.4

0.5
1.2

25.3
60.9

293
26.9
22.6
64.8

0.3
0.8

1.6
3.9

3~

3~

11MBU25
Pn = 450 kW
In = 50.2 A
Un = 6 kV
cosphin = 0.9
Ia/In = 6
p=1
R/X = 0.15
etan = 95.8 %

Un = 6 kV
cosphin = 0.9
Ia/In = 6
p=1
R/X = 0.15
etan = 96.2 %

00LAC11
Pn = 2074 kW
In = 227.0 A
Un = 6 kV
cosphin = 0.91
Ia/In = 6
p=1
R/X = 0.1
etan = 96.6 %

25.2
58.4

283
25.9
22.0
59.9

0.8
1.5

34.4
80.1

34
48.9
46.2
107.1

14.8
27.1

34.4
80.0
25.3
52.0

00PAC03AP001A

300/1A

10BBE00
GS002

SFC

SEE

100/1A

100/1A

LXC0741 3x1586/1x2934
4m

11BFE-LVM
Pn = 240 kW
In = 434.1 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

11BME-LVM
Pn = 117 kW
In = 211.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

11BFG-LVM
Pn = 280 kW
In = 506.4 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

11

10

0.0
0.0

12MBJ01
GT001

12MKC01GT001

09
12BFT01GT001

12MBN12
AP001

200/1A

200/1A

08

0.5
1.2

N2XSY 3x1x120
122 m

166
15.2
14.4
32.7

0.5
1.2
M

3~

3~

3~

00LCB11
Pn = 656 kW
In = 76.8 A
Un = 6 kV
cosphin = 0.86
Ia/In = 6
p=2
R/X = 0.15
etan = 95.6 %

00PAC01
Pn = 1537 kW
In = 209.1 A
Un = 6 kV
cosphin = 0.74
Ia/In = 6
p=8
R/X = 0.15
etan = 95.6 %

10PCC11
Pn = 270 kW
In = 32.3 A
Un = 6.3 kV
cosphin = 0.81
Ia/In = 5.4
p=3
R/X = 0.15
etan = 94.6 %

04

0.3
0.8
12MBU25
AP001

100/1A

03

00LAC13
AP001

12BBE01
GS001

06

1.6
3.9

50/1A

05

0.4
0.8

01

07

M
10BFT02GT001

03

04

0.5
1.2

00LAC12
AP001

50/1A

100/1A

22
32.4
32.4
74.5

Spare

15.2
32.7
0.0
0.0

32.4
74.5

100/1A

19.0
46.5

207
19.0
17.6
46.5

10BHT01
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

14.1
34.6

44
14.1
14.0
34.6

0.0
0.0

22.8
56.0

26
22.8
22.8
56.0

0.0
0.0

12BFT01
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

12MKC01
6.3 2x2.5%/0.66 kV
1650 kVA
uk = 6 %
ur = 0.6 %
In = 151/1443 A
Dy5

10BFT02

100/1A

100/1A

18.2
43.5

199
18.2
17.0
43.5

0.0
0.0

12MBJ01
6.3 2x2.5%/1.8 kV
2570 kVA
uk = 5 %
ur = 0.51 %
In = 236/824 A
Dy5

100/1A

17.0
37.3

191
17.5
16.4
38.4

0.0
0.0

0.5
1.2

Spare

17.4
38.7

194
17.7
16.6
39.5

18.2
46.0

215
19.7
18.3
49.9

0.3
0.8

05

00LCB12
AP001

300/1A

3~

3~

00LAC13
Pn = 2074 kW
In = 227.0 A
Un = 6 kV
cosphin = 0.91
Ia/In = 6
p=1
R/X = 0.1
etan = 96.6 %

12MBU25
Pn = 450 kW
In = 50.2 A
Un = 6 kV
cosphin = 0.9
Ia/In = 6
p=1
R/X = 0.15
etan = 95.8 %

10BMB

SFC

SEE

0.4
0.8

33.4
78.2

28
40.8
39.8
92.1

10BMA-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

10BFT02
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

D
11BFH

13000/1A

12BME-LVM
Pn = 117 kW
In = 211.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

34.5
80.3
15.0
27.3

295
27.0
22.7
65.3

1.6
3.9

0.5
1.2

00LCB12
Pn = 656 kW
In = 76.8 A
Un = 6 kV
cosphin = 0.86
Ia/In = 6
p=2
R/X = 0.15
etan = 95.6 %

10PCC12
Pn = 270 kW
In = 32.3 A
Un = 6.3 kV
cosphin = 0.81
Ia/In = 5.4
p=3
R/X = 0.15
etan = 94.6 %

12BFH-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

10BFJ-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

3~

3~

3~

3~

3~

3~

3~

3~

3~

2.9
23
11BFE
5.3
33.2
31.5
60.8 3/PEN ~400V
50Hz 50 kA 1 s

03

29.0
53.0
0.0
0.0

01
31.8
58.3

1.4
2.6

11BME

1.4
2.6

3/PEN ~400V
50Hz 50 kA 1 s

0.0
0.0

01

23
33.2
31.5
60.8

11BFE00GS001

4.0
34
11BFG 03
7.3
48.9
46.1
105.2 3/PEN ~400V 50Hz 50 kA 1 s

01

3.3
6.1

11BFH 01

06
7.4
13.5

34.2
79.2

7.6
14.0
0.0
0.0

41
59.5
56.4
132.2

10BMA 01

34.2
78.9

7.6
14.0

03

0.0
0.0

11BFG00GS001
M

11BME00GS001

~ 0.0

0.0

0.0
11BTL20

11BJH
3/PEN ~400V 50Hz 50 kA 1 s

42.6
85.0

0.0
0.0

3/PEN ~400V 50Hz 65 kA 1 s 07

06

0.0
0.0

10BMA00
GS011

10BMA00GS001

10BMB 01

41
59.5
56.4
130.8

0.0
0.0

0.0
0.0

~ 0.0

0.0

0.0

10BTL11

~ 0.0

~ 0.0

0.0

0.0

10BRT02

10BTL12

10BTL21

30
42.6
40.6
85.0

~ 0.0
0.0

34.6
69.3
19.5
45.4

G
3~
3000/1A

26.5
46.7

1.4 3/PEN ~400V


2.6 50Hz 50 kA 1 s

0.0
0.0

01

19
27.9
26.4
49.2

34
12BFG 03
01
48.8
46.0
104.8 3/PEN ~400V 50Hz 50 kA 1 s

12BFT01
GT002

3.3
6.1

12BFH 01

06
7.3
13.2

12BFT02
GT002

34.2
79.0

7.6
14.0

12MKA
Sn = 313 MVA
Un = 16.5 kV
R/X = 0.05
xd'' = 15.2 %
cosphi = 0.85

~ 0.0

0.0

0.0

00PAC03
Pn = 1537 kW
In = 209.1 A
Un = 6 kV
cosphin = 0.74
Ia/In = 6
p=8
R/X = 0.15
etan = 95.6 %

00PAC02
Pn = 1537 kW
In = 209.1 A
Un = 6 kV
cosphin = 0.74
Ia/In = 6
p=8
R/X = 0.15
etan = 95.6 %

33.7
77.4

10BHT02
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

15.2
27.9

34
48.4
46.3
103.1

10BFJ

01

03

0.0
0.0

0.0
0.0

7.6
14.0

06

0.0
0.0

7.6
14.0

10BFK
M

40.9
89.1

MINISTRY OF ELECTRICITY AND ENERGY


EAST DELTA ELECTRICITY PRODUCTION COMPANY

10BHT02
GT002

3/PEN ~400V
50Hz 50 kA 1 s

THE ARAB REPUBLIC OF EGYPT

01

3/PEN ~400V
50Hz 50 kA 1 s

33.4
76.4

7.6
14.0

0.0
0.0

0.0
0.0

34
48.4
46.3
104.4

NEW TALKA POWER STATION 750MW COMBINED CYCLE PROJECT


JOB NO:

DRAWING NO.

REV.

12BTL20

12BJH
3/PEN ~400V 50Hz 50 kA 1 s

POWER GENERATION ENGINEERING AND


SERVICES COMPANY

42.5
84.7

44.1
89.1

Ursprung / Original

~ 0.0

~ 0.0

~ 0.0

~ 0.0

0.0

0.0

0.0

0.0

10BTL32

10BTL41

10BTL31

10BTL42

Ursprung-Nr. / Original-No.

PKZ / PC

NEW TALKHA 750MW CCPP


Name

Datum
Date

10BJJ
3/PEN ~400V 50Hz 50 kA 1 s

31
44.1
42.4
89.1

Urspr.-PKZ-Nr.
Orig.-PC

Projekt / Project

gezeich.
Drawn
bearb.
Coord.
geprft
Checked

2005-10-21

J.-H. Yang

2005-10-21

K. Specht

2005-10-21

H. Specht

10BRU02
N2XY-O 2x(3x1x240)/1x240
137 m

34
48.6
46.5
105.3

0.8
1.5

10BFJ00GS001

12BME00GS001

29
42.5
40.6
84.7

0.0

0.0
0.0

34
48.8
46.0
106.2

10BHT01
GT002

12BFG00GS001

~ 0.0
12BTL10

05

41.6 3/PEN ~400V 50Hz 50 kA 1 s


91.6

~ 0.0
10XKA11
Sn = 1.65 MVA
Un = 400 V
R/X = 0.15
xd'' = 13 %
cosphi = 0.80
In = 2382 A

1.4
2.6

3.9
7.1

3~

3000/1A

37
54.0
50.8
114.7

0.0
0.0

12BME

01

10XKA11GS003

10BTL22

23.6
41.4

10BMB00
GS012

GT

10BRT01

03

12BFE00GS001

10XKA11
GS002

N2XY-O 6x(3x1x240)/3x240
73 m

~ 0.0

2.9
19
12BFE
5.3
27.9
26.4
49.3 3/PEN ~400V
50Hz 50 kA 1 s

28
40.6
39.6
91.1

17.9
39.2

10BRU01
N2XY-O 2x(3x1x240)/1x240
101 m

3/PEN ~400V 50Hz 65 kA 1 s

03

0.0
0.0

10XKA11
GS001

7.6
14.0

33.1
77.1

06

17.9
39.2

41.6
91.5

N2XY-O 2x(3x1x240)/1x240
15 m

3~

~ 0.0

11BTL10

05

41.7 3/PEN ~400V 50Hz 50 kA 1 s


91.8

34
48.9
46.1
106.6

12BFG00
GS002

20.3
42.9

1.4
3.4

10BFK-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

3~

230
21.1
17.9
44.4

3~

12BFE00GS002

100/1A

LXC0741 3x1586/1x2934
4m

3~

1.4
3.4

10BFT02GT002

10BHT02GT001

200/1A

20.0
42.2

3~

234
21.4
18.1
45.6

234
21.4
18.1
45.6

10BFT01GT002

0.2
0.4

20.0
42.2

3~

10BBF00
GS002

04

0.8
1.5

100/1A

11BFT02
GT002

100/1A

3~

07

300/1A

11BFT01
GT002

300/1A

3~

00PAC03
AP001B

11BFG00
GS002

3~

00LAC12
Pn = 2074 kW
In = 227.0 A
Un = 6 kV
cosphin = 0.91
Ia/In = 6
p=1
R/X = 0.1
etan = 96.6 %

05

1.4
3.4

Spare

19.3
38.3

213
19.5
16.8
38.8

00PAC02AP001

100/1A

11BFE00GS002

02

1.4
3.4

Space

26.5
64.1

295
27.0
22.7
65.3

03

50/1A

Space

10PCC12
AP001

100/1A

25.4
61.4

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

0.2
0.4

10BHT01

12BFG-LVM
Pn = 280 kW
In = 506.4 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

06

Spare

258
23.6
20.5
0.2
49.9
0.5
11BFT02
6.3 2x2.5%/0.42 kV
1600 kVA
M
uk = 6 %
3~
ur = 0.89 %
In = 147/2199 A
10PGC12
Dyn1
Pn = 300 kW
R0/R1 = 1
In = 34.8 A
X0/X1 = 0.95
Un = 6.3 kV
cosphin = 0.83
Ia/In = 5.5
p=2
R/X = 0.15
etan = 95.2 %

17.6
37.0

10BBF 01

12BBF00GS002M

100/1A

100/1A

23.4
49.4

N2XY-O 3x(3x1x240)/2x240
143 m
12BFE-LVM
Pn = 240 kW
In = 434.1 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

0.8
1.5

34
49.1
46.3
107.6

7.6
14.0

12BFT02

10BMB-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

25.5
60.0

287
26.3
22.2
61.5

LXC0741 3x1586/1x2934
4m

10BFJ

100/1A

100/1A

18.9
46.5

211
19.3
17.9
47.4

1.6
3.9

3~

12MBN12
Pn = 650 kW
In = 72.2 A
Un = 6 kV
cosphin = 0.9
Ia/In = 6
p=1
R/X = 0.15
etan = 96.2 %

100/1A

100/1A

234
21.4
18.1
45.7

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

1.6
3.9

10PGC12
AP001

200/1A

3.6
7.9

10

10BBF00GS001

12BBF00GS001

08

0.2
0.5

11BFT02GT001

20.3
50.7

06

0.8
1.5

200/1A

300/1A

11BBT01
GT230

12BBF 02

295
27.0
22.7
65.7

11BFT02

11BFH-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

12BBT01GT220

16.9
43.4

01

07

0.0
0.0

500/1A

100/1A

100/1A

Spare

LXC0741 3x1586/1x2934
4m

10BHT01GT001 M

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

200/1A

11BFG

06

0.0
0.0

300/1A

19.1
48.3

214
19.6
18.2
49.5

08

11BFT01

N2XY-O 3x(3x1x240)/2x240
89 m

11MKA
Sn = 313 MVA
Un = 16.5 kV
R/X = 0.05
xd'' = 15.2 %
cosphi = 0.85

11BFT01
6.3 2x2.5%/0.42 kV
1600 kVA
M
uk = 6 %
3~
ur = 0.89 %
In = 147/2199 A
10PGC11
Dyn1
Pn = 300 kW
R0/R1 = 1
In = 34.8 A
X0/X1 = 0.95
Un = 6.3 kV
cosphin = 0.83
Ia/In = 5.5
p=2
R/X = 0.15
etan = 95.2 %

04

12BBE 02

: Peak short-circuit current in kA

1000/1A

Space

100/1A

N2XSY 3x1x120
178 m

10BFT01
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

12BFH

GT

1.1
2.3

00PAC01
AP001

50/1A

Spare

25.0
58.2

284
26.0
22.1
60.5
12BFT02
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95
41
59.6
56.5
132.1

13000/1A

N2XSY 3x1x120
34 m

N2XSY 3x1x120
38 m

N2XSY 3x1x120
43 m

N2XSY 3x1x120
125 m
263
24.1
20.8
51.8

11MKC01
6.3 2x2.5%/0.66 kV
M
1650 kVA
3~
uk = 6 %
ur = 0.6 %
11MBN12
In = 151/1443 A
Pn = 650 kW
Dy5
In = 72.2 A

0.0
0.0

23.7
51.0

100/1A

10PCC11AP001

02

215
19.7
18.3
50.1

11BBT01GT240

1000/1A

N2XY-O 3x(3x1x240)/2x240
15 m

11MBJ01
6.3 2x2.5%/1.8 kV
2570 kVA
uk = 5 %
ur = 0.51 %
In = 236/824 A
Dy5

273
25.1
21.5
57.8

23.2
49.3

Spare

100/1A

100/1A

LXC0741 3x1586/1x2934
4m

0.0
0.0

25.1
57.8

100/1A

100/1A

LXC0741 3x1586/1x2934
4m

283
25.9
22.0
61.1

N2XSY 3x1x120
144 m

N2XSY 3x1x240
94 m

N2XSY 2x(3x1x240)
94 m
25.9
61.1

100/1A

100/1A

LXC0741 3x1586/1x2934
4m

100/1A

03

12BAA

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

2000/1A

12BBT01GT210

07

Space

Space
100/1A

10BBE 01

11BBF00
GS002

100/1A

50/1A

200/1A

200/1A

04

0.5
1.2

168
15.4
14.6
33.4

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

2000/1A

2000/1A

N2XSY 3x1x120
122 m

08

0.5
1.2

08

15.4
33.4

2000/1A

2000/1A

LXC0741 3x1586/1x2934
4m

11MBJ01
GT001

09

0.0
0.0

02

0.0
0.0

10BBE00GS001

2000/1A

N2XSY 3x1x120
151 m

10

11BBF 01

19.1
48.3

11BBF00GS001

ip

N2XSY 2x(3x1x240)
974 m

2000/1A

N2XSY 3x1x120
33 m

0.0
0.0

214
19.6
18.2
49.5

02

12BBT01
GT230

[kA]

2000/1A

N2XY-O 2x(3x1x240)/1x240
15 m

11

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

11BBT01GT220

1000/1A

LXC0741 3x1586/1x2934
4m

22.7
55.4

11BBE 01

12BBT01GT240

1000/1A

11BBE

LXC0741 3x1586/1x2934
4m

2000/1A

N2XSY 3x1x120
38 m

2000/1A

2000/1A

11BBT01

LXC0741 3x1586/1x2934
4m

2000/1A

2000/1A

11BBT01

N2XSY 3x1x120
173 m

2000/1A

2000/1A

11BBF

N2XSY 2x(3x1x240)
984 m

2000/1A

11BBT01GT210

I b : Sym. short-circuit breaking current (r.m.s) in kA

I k " [kA]
ip
[kA]

177
16.2
16.2
42.6

N2XSY 3x1x120
200 m

12BBE

12BBT01

I k " : Initial symmetrical short-circuit current (r.m.s.) in kA

8
30 s

N2XSY 3x1x120
15 m

12BBT01

16.2
42.6

16.3
42.8

178
16.3
16.3
42.8

2000/1A

750/1A

N2XSY 3x1x240
150 m

0.5
1.2

750/1A

N2XSY 3x(3x1x240)
92 m

218
20.0
18.5
51.2

2000/1A

N2XSY 3x(3x1x240)
161 m

2.8
6.6

8
30 s

N2XSY 3x(3x1x240)
161 m

4.2
9.4

81.6
215.1

8
30 s

N2XSY 3x1x120
20 m

16.6
43.3

N2XSY 3x(3x1x240)
98 m

N2XSY 3x(3x1x240)
92 m

12BBF

293
26.9
22.6
65.0

16.5
43.2
6.7
14.7

11BAA

2000/1A

750/1A

LXC0741 3x1586/1x2934
4m

298
27.3
23.0
67.3

750/1A

N2XSY 3x(3x1x240)
98 m

2000/1A

N2XSY 3x(3x1x240)
161 m

8
30 s

0.0
0.0

LXC0741 3x1586/1x2934
4m

81.6
215.1

4163
145.7
126.4
390.5

N2XSY 3x(3x1x240)
161 m

3.8
9.1

64.1
175.4

ip

12BBT01
Dyn11yn11
16.5 9x1.25%/6.6/6.6 kV
32/16/16 MVA
uk = 8.66/8.71/15.15 %
ur = 0.48/0.48/0.96 %
In = 1120/1400/1400 A

1200/1A

1300/1A

N2XSY 3x(3x1x240)
92 m

4268
149.3
129.2
399.2

11BBT01
Dyn11yn11
16.5 9x1.25%/6.6/6.6 kV
32/16/16 MVA
uk = 8.61/8.64/15.13 %
ur = 0.48/0.48/0.96 %
In = 1120/1400/1400 A

1200/1A

1300/1A

63.9
175.0

1200/1A

S k " : Initial symmetrical short-circuit power in MVA

I k " [kA]
ip
[kA]

I k " [kA]
[kA]
Ib

1200/1A

N2XSY 3x(3x1x240)
152 m

1200/1A

1200/1A

N2XSY 3x(3x1x240)
92 m

1200/1A

Busbar/Node

Sk " [MVA]

N2XSY 3x(3x1x240)
152 m

1200/1A

12BAT01
240 4x2.5%/16.5 kV
300 MVA
uk = 16.22 %
ur = 0.16 %
In = 722/10497 A
YNd1
Z0/Z1 = 1

N2XSY 2x(3x1x240)
150 m

11BAT01
240 4x2.5%/16.5 kV
300 MVA
uk = 16.26 %
ur = 0.16 %
In = 722/10497 A
YNd1
Z0/Z1 = 1

Legend:

N2XSY 3x1x120
20 m

40.0
94.5

Abtlg.
Dept.

SINUS

GmbH

SIEMENS
Power Generation (PG)

UA / DCC
Type

Benennung / Title

Inhaltskennzeichen
Contents Code

CALCULATION OF
SHORT-CIRCUIT CURRENTS,
LOAD FLOW AND VOLTAGE DROP
Annex 3
Dienstst. / Dept.

BN02

B
Zhl.-Nr.
Reg. No.

UNID

W 741

Index / Rev. Version

10691410
Ang.-Var. / Offer -Var.

EGY263-BN02-B-700021
Erstellt mit
Designed with

EGY263

Mastab
Scale

B
Var. / Opt.

Blatt-Nr. / Page-No.

1
Ersatz fr
Supersedes

Interconnected System
Sk''Act = 12956 MVA
c=1
R/X = 0.1436
Z0/Z1 = 0.72

ADA
47.89
15.96

Calculated Case 2:

41.06
13.06

BB I

MAX. SINGLE-PHASE SHORT-CIRCUIT CURRENTS


(ACCORDING TO IEC EN 60909-0:2001)

41.06
13.06

3 ~ 220 kV 50 Hz

Operation Mode Configuration 1:

BB II
3.46
1.46

Maximum short-circuit conditions occur at MV switchgear,


if one of the two unit auxiliary transformers 11BBT01/12BBT01 feeds all 6.3 kV switchgear. The unit
auxiliary transformer 11BBT01 is supplied by the unit generator 11MKA connected via unit
transformer 11BAT01 to the 220 kV network. The unit generator 12MKA is in operation and supplies
the network via the unit transformer 12BAT01.

3.42
1.46

3.46
1.46

3.42
1.46

Maximum short-circuit currents occur at LV switchgear 10BMA, if the emergency diesel generator
10XKA11 feeds in parallel to LV transformer 10BFT01 during diesel test. Switchgear 11BFE, 11BME,
11BFG, 11BJH and 11BFH are supplied by LV transformer 11BFT02, where as switchgear 12BFE,
12BME, 12BFG, 12BJH and 12BFH are supplied by LV transformer 12BFT02
and switchgear 10BJJ, 10BFJ and 10BFK are supplied by LV transformer 10BHT02.
44.49
14.51

3.46
1.46

3.42
1.46

11MBJ01
GT001

11MKC01GT001

500/1A

08

0.01
0.00
11MBN12
AP001

11MBU25
AP001

100/1A

200/1A

04

0.00
0.00

03
11BBE00
GS001

00LAC11
AP001

100/1A

50/1A

07

0.02
0.00

06

0.01
0.00

12BFT02GT001

07

10BFT01GT001

200/1A

300/1A

05

0.01
0.00

11BBF 01

02

08

06

03

11BFT01GT001

10PGC11
AP001

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

04

0.01
0.00
00LCB11
AP001

0.00
0.00

0.00
0.00

0.00
0.00

0.00
0.00

0.00
0.00

0.00
0.00

0.50
0.17

0.01
0.00

11MKC01
6.3 2x2.5%/0.66 kV
M
1650 kVA
3~
uk = 6 %
ur = 0.6 %
11MBN12
In = 151/1443 A
Pn = 650 kW
Dy5
In = 72.2 A

0.48
0.17

0.50
0.17

0.00
0.00

0.02
0.00

3~

3~

11MBU25
Pn = 450 kW
In = 50.2 A
Un = 6 kV
cosphin = 0.9
Ia/In = 6
p=1
R/X = 0.15
etan = 95.8 %

Un = 6 kV
cosphin = 0.9
Ia/In = 6
p=1
R/X = 0.15
etan = 96.2 %

0.00
0.00

0.49
0.17

0.50
0.17

00LAC11
Pn = 2074 kW
In = 227.0 A
Un = 6 kV
cosphin = 0.91
Ia/In = 6
p=1
R/X = 0.1
etan = 96.6 %

0.49
0.17

0.50
0.17

45.58
15.19

0.01
0.00

36.54
15.19
9.22
0.00

SFC

SEE

00PAC01
AP001

50/1A

Space

00PAC03AP001A

300/1A

08
10BBE00
GS002

LXC0741 3x1586/1x2934
4m

11BFE-LVM
Pn = 240 kW
In = 434.1 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

11BME-LVM
Pn = 117 kW
In = 211.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

11BFG-LVM
Pn = 280 kW
In = 506.4 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

06

0.00
0.00

10

0.00
0.00

12MBJ01
GT001

12MKC01GT001

09
12BFT01GT001

12MBN12
AP001

200/1A

200/1A

08

0.01
0.00

N2XSY 3x1x120
122 m

Spare

3~

3~

3~

00LCB11
Pn = 656 kW
In = 76.8 A
Un = 6 kV
cosphin = 0.86
Ia/In = 6
p=2
R/X = 0.15
etan = 95.6 %

00PAC01
Pn = 1537 kW
In = 209.1 A
Un = 6 kV
cosphin = 0.74
Ia/In = 6
p=8
R/X = 0.15
etan = 95.6 %

10PCC11
Pn = 270 kW
In = 32.3 A
Un = 6.3 kV
cosphin = 0.81
Ia/In = 5.4
p=3
R/X = 0.15
etan = 94.6 %

Spare

0.49
0.16

0.49
0.16

0.01
0.00

100/1A

100/1A

100/1A

0.49
0.17

04

0.01
0.00
12MBU25
AP001

100/1A

03

12BBE01
GS001

06

0.03
0.00
00LAC13
AP001

50/1A

05

0.01
0.00

M
10BFT02GT001

200/1A

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

03

0.02
0.00

00LAC12
AP001

50/1A

0.00
0.00

34.60
11.53

34.60
11.53

100/1A

0.50
0.17

0.50
0.17
10BHT01
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

0.00
0.00

0.00
0.00

0.00
0.00

0.00
0.00

12BFT01
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

0.00
0.00

0.00
0.00

10BFT02

0.48
0.16

0.49
0.16
12MKC01
6.3 2x2.5%/0.66 kV
1650 kVA
uk = 6 %
ur = 0.6 %
In = 151/1443 A
Dy5

100/1A

100/1A

0.50
0.17

0.50
0.17

0.00
0.00

12MBJ01
6.3 2x2.5%/1.8 kV
2570 kVA
uk = 5 %
ur = 0.51 %
In = 236/824 A
Dy5

100/1A

0.00
0.00

0.01
0.00

Spare

0.49
0.16

0.49
0.16

0.47
0.17

0.50
0.17

0.01
0.00

04

0.01
0.00

3~

3~

00LAC13
Pn = 2074 kW
In = 227.0 A
Un = 6 kV
cosphin = 0.91
Ia/In = 6
p=1
R/X = 0.1
etan = 96.6 %

12MBU25
Pn = 450 kW
In = 50.2 A
Un = 6 kV
cosphin = 0.9
Ia/In = 6
p=1
R/X = 0.15
etan = 95.8 %

10BMB

SFC

SEE

0.01
0.00

35.61
13.51

40.54
13.51

0.50
0.17

10BMA-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

5.05
0.00

D
11BFH

13000/1A

12BME-LVM
Pn = 117 kW
In = 211.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

11BFT02
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

9.29
0.00

0.00
0.00

0.02
0.00

0.01
0.00

00LCB12
Pn = 656 kW
In = 76.8 A
Un = 6 kV
cosphin = 0.86
Ia/In = 6
p=2
R/X = 0.15
etan = 95.6 %

10PCC12
Pn = 270 kW
In = 32.3 A
Un = 6.3 kV
cosphin = 0.81
Ia/In = 5.4
p=3
R/X = 0.15
etan = 94.6 %

12BFH-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

10BFJ-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

10BFK-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

3~

3~

3~

3~

3~

3~

3~

3~

3~

3~

1.23
0.00

3/PEN ~400V
50Hz 50 kA 1 s

03

19.50
7.11
0.00
0.00

01
20.72
7.11

0.60
0.00

11BME

0.60
0.00

3/PEN ~400V
50Hz 50 kA 1 s

0.00
0.00

01

21.32
7.11

11BFE00GS001

44.95
14.98

11BFG

03

2.48
0.00

3/PEN ~400V 50Hz 50 kA 1 s

01

2.05
0.00

11BFH 01

06
4.52
0.00

35.92
14.98

4.68
0.00

05

40.50 3/PEN ~400V 50Hz 50 kA 1 s


14.98

0.00
0.00

44.95
14.98

55.25
18.42

10BMA 01

35.76
13.72

4.93
0.00

03

0.00
0.00

11BFG00GS001
M

11BME00GS001

0.00
0.00

3/PEN ~400V 50Hz 65 kA 1 s 07

10BMB 01

06 14.74

0.00
0.00

10BMA00
GS011

10BMA00GS001

06

4.83

3/PEN ~400V 50Hz 65 kA 1 s

03

0.00
0.00

10XKA11
GS001

5.01
0.00

35.02
13.30

0.00
0.00

0.00
0.00

15.95
5.32

39.91
13.30

12BFE

1.09
0.00

3/PEN ~400V
50Hz 50 kA 1 s

03

14.33
5.32
0.00
0.00

15.42
5.32

0.53
0.00

12BME

01
M

0.53 3/PEN ~400V


0.00 50Hz 50 kA 1 s

0.00
0.00

01

15.95
5.32

12BFE00GS001

10XKA11
GS002

44.85
14.95

12BFG 03

12BFG00
GS002

2.40
0.00

01

3/PEN ~400V 50Hz 50 kA 1 s

12BFT01
GT002

2.05
0.00

12BFH 01

06
4.45
0.00

12BFT02
GT002

35.89
14.95

4.69
0.00

05

40.48 3/PEN ~400V 50Hz 50 kA 1 s


14.95

0.00
0.00

44.85 44.67
14.95 14.89

10BFJ
03

01
0.00
0.00

10BHT01
GT002

3/PEN ~400V
50Hz 50 kA 1 s

4.70
0.00

06

0.00
0.00

0.00
0.00

4.70
0.00

10BFK
M

40.04
14.89

EAST DELTA ELECTRICITY PRODUCTION COMPANY

35.43

01 14.89

3/PEN ~400V
50Hz 50 kA 1 s

0.00
0.00

4.70
0.00
0.00
0.00

NEW TALKA POWER STATION 750MW COMBINED CYCLE PROJECT

44.67
14.89

JOB NO:

12BME00GS001

~ 0.00

0.00

0.00

11BTL10

11BTL20

11BJH
3/PEN ~400V 50Hz 50 kA 1 s

34.63
11.54

N2XY-O 6x(3x1x240)/3x240
73 m

~ 0.00

~ 0.00

0.00

0.00

10BRT01

~ 0.00

~ 0.00

0.00

0.00

10BTL12

10BTL21

10BRT02

10XKA11GS003

10BTL22

10BTL11
M

G
3~
12MKA
Sn = 313 MVA
Un = 16.5 kV
R/X = 0.05
xd'' = 15.2 %
cosphi = 0.85

~ 0.00

~ 0.00

0.00

0.00

12BTL10

12BTL20

3000/1A

34.63
11.54

~ 0.00
0.00

46.07
15.36

28.63
7.97
17.82
7.86

10BRU01

G
N2XY-O 2x(3x1x240)/1x240
101 m

GT

3~
3000/1A

34.57
11.52

~ 0.00
10XKA11
Sn = 1.65 MVA
Un = 400 V
R/X = 0.15
xd'' = 13 %
cosphi = 0.80
In = 2382 A

12BJH
3/PEN ~400V 50Hz 50 kA 1 s

34.57
11.52

37.77
12.59

Ursprung / Original

~ 0.00

~ 0.00

~ 0.00

~ 0.00

0.00

0.00

0.00

0.00

10BTL31

10BTL42

10BTL32

10BTL41

Ursprung-Nr. / Original-No.

PKZ / PC

NEW TALKHA 750MW CCPP


Name

Datum
Date

10BJJ
3/PEN ~400V 50Hz 50 kA 1 s

37.77
12.59

gezeich.
Drawn
bearb.
Coord.

2005-10-21

J.-H. Yang

2005-10-21

K. Specht

2005-10-21

H. Specht

10BRU02
N2XY-O 2x(3x1x240)/1x240
137 m

Urspr.-PKZ-Nr.
Orig.-PC

Projekt / Project

geprft
Checked

0.00

REV.

POWER GENERATION ENGINEERING AND


SERVICES COMPANY

N2XY-O 3x(3x1x240)/2x240
15 m

~ 0.00

14.74
4.83

DRAWING NO.

10BFJ00GS001

N2XY-O 2x(3x1x240)/1x240
15 m

3~
11MKA
Sn = 313 MVA
Un = 16.5 kV
R/X = 0.05
xd'' = 15.2 %
cosphi = 0.85

40.55
13.72

N2XY-O 2x(3x1x240)/1x240
15 m

9.48
0.00

MINISTRY OF ELECTRICITY AND ENERGY

55.25
18.42

GT

36.07
15.13

10BHT02
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

THE ARAB REPUBLIC OF EGYPT

10BHT02
GT002

12BFG00GS001

10BMB00
GS012

45.39
15.13

0.01
0.00

3~

12BFE00GS002

00PAC03
Pn = 1537 kW
In = 209.1 A
Un = 6 kV
cosphin = 0.74
Ia/In = 6
p=8
R/X = 0.15
etan = 95.6 %

00PAC02
Pn = 1537 kW
In = 209.1 A
Un = 6 kV
cosphin = 0.74
Ia/In = 6
p=8
R/X = 0.15
etan = 95.6 %

0.48
0.16

LXC0741 3x1586/1x2934
4m

3~

0.49
0.16

0.02
0.00

3~

10BFT02GT002

0.02
0.00
M

100/1A

0.47
0.16

3~

10BFT01GT002

0.49
0.16

0.00
0.00

0.49
0.16

0.47
0.16

3~

11BFT02
GT002

10BHT02GT001

200/1A

Spare

00LAC12
Pn = 2074 kW
In = 227.0 A
Un = 6 kV
cosphin = 0.91
Ia/In = 6
p=1
R/X = 0.1
etan = 96.6 %

10BBF00
GS002

04

0.01
0.00

100/1A

3~

100/1A

10PGC12
Pn = 300 kW
In = 34.8 A
Un = 6.3 kV
cosphin = 0.83
Ia/In = 5.5
p=2
R/X = 0.15
etan = 95.2 %

07

300/1A

3~

11BFT01
GT002

00PAC03
AP001B

0.48
0.16

0.49
0.16

11BFG00
GS002

300/1A

100/1A

00PAC02AP001

05

0.02
0.00

Space

11BFE00GS002

02

0.02
0.00

50/1A

Space

10PCC12
AP001

0.49
0.17

0.50
0.17

03

0.00
0.00

100/1A

0.48
0.17

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

3~

10BHT01

12BFG-LVM
Pn = 280 kW
In = 506.4 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

06

Spare

0.50
0.17

0.43
0.16

10BBF 01

12BBF00GS002M

100/1A

100/1A

0.49
0.16

0.49
0.16

N2XY-O 3x(3x1x240)/2x240
143 m
12BFE-LVM
Pn = 240 kW
In = 434.1 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

36.57
15.22

45.67
15.22

12BFT02

10BMB-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

0.01
0.00

10BFT02
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

LXC0741 3x1586/1x2934
4m

10BFJ

0.49
0.17

0.49
0.16

05

00LCB12
AP001

300/1A

100/1A

100/1A

0.49
0.17

0.50
0.17

0.03
0.00

3~

12MBN12
Pn = 650 kW
In = 72.2 A
Un = 6 kV
cosphin = 0.9
Ia/In = 6
p=1
R/X = 0.15
etan = 96.2 %

100/1A

100/1A

10BBF00GS001

0.04
0.00

10

10PGC12
AP001

1000/1A

12BBF00GS001

08

0.00
0.00

11BFT02GT001

200/1A

300/1A

06

0.01
0.00

0.42
0.17

01

07

1000/1A

11BBT01
GT230

12BBF 02

0.50
0.17

11BFT02

11BFH-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

12BBT01GT220

0.45
0.17

01

07

0.00
0.00

500/1A

200/1A

11BBT01GT240

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

11

N2XSY 3x(3x1x240)
92 m
2000/1A

12BBE 02

10BHT01GT001 M

300/1A

100/1A

LXC0741 3x1586/1x2934
4m

0.50
0.17

2000/1A

2000/1A

Space
100/1A

N2XSY 3x1x120
178 m

04

11BFG

N2XY-O 3x(3x1x240)/2x240
89 m

11BFE

19.52
4.70

11BFT01
6.3 2x2.5%/0.42 kV
1600 kVA
M
uk = 6 %
3~
ur = 0.89 %
In = 147/2199 A
10PGC11
Dyn1
Pn = 300 kW
R0/R1 = 1
In = 34.8 A
X0/X1 = 0.95
Un = 6.3 kV
cosphin = 0.83
Ia/In = 5.5
p=2
R/X = 0.15
etan = 95.2 %

02

11BFT01

12BFH

21.32
7.11

36.38
14.04

10BFT01
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

10PCC11AP001

100/1A

0.50
0.17

13000/1A

0.01
0.00

03

12BAA

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

2000/1A

2000/1A

12BBT01GT210

07

Spare

0.49
0.17

0.50
0.17
12BFT02
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95
55.72
18.57

100/1A

N2XSY 3x1x120
34 m

N2XSY 3x1x120
38 m

N2XSY 3x1x120
43 m

N2XSY 3x1x120
125 m

0.49
0.17

Spare

100/1A

100/1A

LXC0741 3x1586/1x2934
4m

0.50
0.17

0.00
0.00

11MBJ01
6.3 2x2.5%/1.8 kV
2570 kVA
uk = 5 %
ur = 0.51 %
In = 236/824 A
Dy5

0.50
0.17

100/1A

100/1A

LXC0741 3x1586/1x2934
4m

0.50
0.17

N2XSY 3x1x120
144 m

N2XSY 3x1x240
94 m

N2XSY 2x(3x1x240)
94 m
0.50
0.17

100/1A

100/1A

LXC0741 3x1586/1x2934
4m

100/1A

0.49
0.16

10BBE 01

11BBF00
GS002

Space
100/1A

0.49
0.16

05

100/1A

50/1A

200/1A

200/1A

0.00
0.00

10BBE00GS001

2000/1A

2000/1A

N2XSY 3x1x120
122 m

09

0.00
0.00

0.50
0.17

0.49
0.17

11BBF00GS001

2000/1A

LXC0741 3x1586/1x2934
4m

10

0.00
0.00

02

12BBT01
GT230

N2XSY 2x(3x1x240)
974 m

N2XSY 3x1x120
151 m

11

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

11BBT01GT220

1000/1A

11BBE

LXC0741 3x1586/1x2934
4m

0.45
0.17

11BBE 01

12BBT01GT240

1000/1A

N2XSY 3x1x120
33 m

2000/1A

11BBT01

LXC0741 3x1586/1x2934
4m

2000/1A

2000/1A

N2XSY 3x1x120
38 m

2000/1A

2000/1A

11BBT01

LXC0741 3x1586/1x2934
4m

2000/1A

2000/1A

11BBF

N2XSY 2x(3x1x240)
984 m

2000/1A

11BBT01GT210

: Zero-sequence short-circuit current (r.m.s)


in kA

0.50
0.17

N2XSY 3x1x120
173 m

12BBE

12BBT01

I0

8
30 s

N2XSY 3x1x120
200 m

12BBT01

0.50
0.17

0.50
0.17

0.50
0.17

2000/1A

750/1A

N2XSY 3x1x120
15 m

0.01
0.00

750/1A

N2XSY 3x1x240
150 m

0.05
0.00

0.50
0.17

2000/1A

N2XSY 3x(3x1x240)
161 m

0.05
0.00

8
30 s

N2XSY 3x(3x1x240)
161 m

0.44
0.17

0.00
0.00

8
30 s

N2XSY 3x1x120
20 m

12BBF

0.50
0.17

0.37
0.17

N2XSY 3x(3x1x240)
98 m

N2XSY 3x(3x1x240)
92 m

0.08
0.00

11BAA

2000/1A

750/1A

LXC0741 3x1586/1x2934
4m

0.50
0.17

750/1A

N2XSY 3x(3x1x240)
161 m

2000/1A

N2XSY 3x(3x1x240)
92 m

8
30 s

0.00
0.00

0.00
0.00

LXC0741 3x1586/1x2934
4m

0.00
0.00

12BBT01
Dyn11yn11
16.5 9x1.25%/6.6/6.6 kV
32/16/16 MVA
uk = 8.66/8.71/15.15 %
ur = 0.48/0.48/0.96 %
In = 1120/1400/1400 A

1200/1A

0.00
0.00

I k L1" : Initial symmetrical short-circuit current over


phase L1 (r.m.s.) in kA

I k L1" [kA]
I0
[kA]

1200/1A

1300/1A

N2XSY 3x(3x1x240)
161 m

0.00
0.00

N2XSY 3x(3x1x240)
98 m

0.00
0.00

11BBT01
Dyn11yn11
16.5 9x1.25%/6.6/6.6 kV
32/16/16 MVA
uk = 8.61/8.64/15.13 %
ur = 0.48/0.48/0.96 %
In = 1120/1400/1400 A

1200/1A

1300/1A

0.00
0.00

I k L1" [kA]
I0
[kA]

I k L1" [kA]
[kA]
I0

1200/1A

N2XSY 3x(3x1x240)
152 m

1200/1A

1200/1A

N2XSY 3x(3x1x240)
92 m

1200/1A

Busbar/Node

N2XSY 3x(3x1x240)
152 m

1200/1A

12BAT01
240 4x2.5%/16.5 kV
300 MVA
uk = 16.22 %
ur = 0.16 %
In = 722/10497 A
YNd1
Z0/Z1 = 1

N2XSY 2x(3x1x240)
150 m

11BAT01
240 4x2.5%/16.5 kV
300 MVA
uk = 16.26 %
ur = 0.16 %
In = 722/10497 A
YNd1
Z0/Z1 = 1

Legend:

N2XSY 3x1x120
20 m

44.45
14.51

Abtlg.
Dept.

SINUS

GmbH

SIEMENS
Power Generation (PG)

UA / DCC
Type

Benennung / Title

Inhaltskennzeichen
Contents Code

CALCULATION OF
SHORT-CIRCUIT CURRENTS,
LOAD FLOW AND VOLTAGE DROP
Annex 4
Dienstst. / Dept.

BN02

B
Zhl.-Nr.
Reg. No.

UNID

W 741

Index / Rev. Version

10691410
Ang.-Var. / Offer -Var.

EGY263-BN02-B-700021
Erstellt mit
Designed with

EGY263

Mastab
Scale

B
Var. / Opt.

Blatt-Nr. / Page-No.

1
Ersatz fr
Supersedes

Interconnected System
Sk''Act = 12956 MVA
c=1
R/X = 0.1436

Calculated Case 1:

MIN. THREE-PHASE SHORT-CIRCUIT CURRENTS

ADA

(ACCORDING TO IEC EN 60909-0:2001)

BB I

3 ~ 220 kV 50 Hz

Operation Mode Configuration 2:

BB II

The minimum short-circuit current in the MV system is to be expected at the end of the coupling
chain of the MV switchgear, if one unit generator (11MKA) is shut down and the remaining unit
generator 12MKA is in isolated operation and supplies the auxiliary system.

1.9
5.1

The minimum short-circuit currents in the LV switchgear 11BME, 12BME, 10BMA and 10BMB
are calculated for emergency operation when the emergency diesel generator 10XKA11 supplies
these switchgear.

1.9
5.1

Legend:

I k " [kA]
[kA]
Ib

1.9
5.1

8
30 s

8
30 s

2000/1A

11MBU25
AP001

100/1A

200/1A

11BBE00
GS001

00LAC11
AP001

100/1A

50/1A

07

0.0
0.0

06

0.0
0.0

12BFT02GT001

07

06

10BFT01GT001

200/1A

300/1A

05

0.0
0.0

11BFT01GT001

10PGC11
AP001

N2XSY 3x(3x1x240)
161 m

04

0.0
0.0
00LCB11
AP001

05

12.0
29.4

37
12.0
12.0
29.4

0.0
0.0

0.0
0.0

18.9
46.5

22
18.9
18.9
46.5

133
12.2
12.2
26.2

13.3
33.4

145
13.3
13.3
33.4

3~

3~

11MBU25
Pn = 450 kW
In = 50.2 A
Un = 6 kV
cosphin = 0.9
Ia/In = 6
p=1
R/X = 0.15
etan = 95.8 %

Un = 6 kV
cosphin = 0.9
Ia/In = 6
p=1
R/X = 0.15
etan = 96.2 %

00LAC11
Pn = 2074 kW
In = 227.0 A
Un = 6 kV
cosphin = 0.91
Ia/In = 6
p=1
R/X = 0.1
etan = 96.6 %

13.0
30.9

141
13.0
13.0
30.9

0.0
0.0

27.7
64.7

19
27.7
27.7
64.7

0.0
0.0

142
13.0
13.0
31.2
12BFT02
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95
19
27.7
27.7
64.8

0.0
0.0

27.7
64.8

10BFT01
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

SFC

SEE

10BBE00
GS002

100/1A

LXC0741 3x1586/1x2934
4m

11BFE-LVM
Pn = 240 kW
In = 434.1 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

11BME-LVM
Pn = 117 kW
In = 211.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

11BFG-LVM
Pn = 280 kW
In = 506.4 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

12BBE 02

10BHT01GT001 M

2000/1A

11

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

10

0.0
0.0

12MBJ01
GT001

11BBT01GT240

13.3
33.7

12MKC01GT001

09
12BFT01GT001

12MBN12
AP001

200/1A

200/1A

08

0.0
0.0

N2XSY 3x1x120
122 m

3~

3~

00LCB11
Pn = 656 kW
In = 76.8 A
Un = 6 kV
cosphin = 0.86
Ia/In = 6
p=2
R/X = 0.15
etan = 95.6 %

116
10.6
10.6
21.0

3~

00PAC01
Pn = 1537 kW
In = 209.1 A
Un = 6 kV
cosphin = 0.74
Ia/In = 6
p=8
R/X = 0.15
etan = 95.6 %

10PCC11
Pn = 270 kW
In = 32.3 A
Un = 6.3 kV
cosphin = 0.81
Ia/In = 5.4
p=3
R/X = 0.15
etan = 94.6 %

100/1A

100/1A

100/1A

10.0
18.6

109
10.0
10.0
18.6

04

0.0
0.0
12MBU25
AP001

100/1A

03

00LAC13
AP001

12BBE01
GS001

06

0.0
0.0

50/1A

05

0.0
0.0

12BBF 02

145
13.3
13.3
33.5

01

11BFT02GT001

200/1A

03

04

0.0
0.0

00LAC12
AP001

50/1A

19
26.8
26.8
60.3

Spare

10.6
21.0
0.0
0.0

26.8
60.3

100/1A

12.9
31.1

141
12.9
12.9
31.1

10BHT01
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

12.0
29.2

37
12.0
12.0
29.2

0.0
0.0

18.9
46.1

22
18.9
18.9
46.1

0.0
0.0

12BFT01
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

12MKC01
6.3 2x2.5%/0.66 kV
1650 kVA
uk = 6 %
ur = 0.6 %
In = 151/1443 A
Dy5

10BFT02

100/1A

100/1A

12.5
28.8

136
12.5
12.5
28.8

0.0
0.0

12MBJ01
6.3 2x2.5%/1.8 kV
2570 kVA
uk = 5 %
ur = 0.51 %
In = 236/824 A
Dy5

100/1A

11.9
24.3

130
11.9
11.9
24.3

0.0
0.0

Spare

12.1
25.3

132
12.1
12.1
25.3

13.3
33.7

146
13.3
13.3
33.7

3~

3~

3~

12MBN12
Pn = 650 kW
In = 72.2 A
Un = 6 kV
cosphin = 0.9
Ia/In = 6
p=1
R/X = 0.15
etan = 96.2 %

05

00LCB12
AP001

300/1A

SFC

SEE

0.0
0.0

27.7
64.9

19
27.7
27.7
64.9

10BMA-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

10BFT02
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

11BFH

13000/1A

12BME-LVM
Pn = 117 kW
In = 211.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

27.7
64.9
0.0
0.0

145
13.3
13.3
33.5

00LCB12
Pn = 656 kW
In = 76.8 A
Un = 6 kV
cosphin = 0.86
Ia/In = 6
p=2
R/X = 0.15
etan = 95.6 %

10PCC12
Pn = 270 kW
In = 32.3 A
Un = 6.3 kV
cosphin = 0.81
Ia/In = 5.4
p=3
R/X = 0.15
etan = 94.6 %

12BFH-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

10BFJ-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

3~

3~

3~

3~

3~

3~

3~

3~

3~

13
11BFE
18.5
18.5
31.6 3/PEN ~400V
50Hz 50 kA 1 s

03

18.5
31.6
0.0
0.0

11BME

01
M

3/PEN ~400V
50Hz 50 kA 1 s

01

0.0
0.0

3.3
6.7

2
3.3
3.3
6.7

11BFE00GS001

0.0
19
11BFG 03
0.0
27.5
27.5
63.9 3/PEN ~400V 50Hz 50 kA 1 s

01

11BFH 01

06
0.0
0.0

27.5
63.9
0.0
0.0

3
3.7
3.7
8.3

10BMA 01

3/PEN ~400V 50Hz 65 kA 1 s 07

03

0.0
0.0

11BFG00GS001
M

11BME00GS001

~ 0.0

0.0

0.0
11BTL20

11BJH
3/PEN ~400V 50Hz 50 kA 1 s

24.8
50.9

0.0
0.0

0.0
0.0

06

0.0
0.0

10BMA00
GS011

10BMA00GS001

10BMB 01
06

3.7
8.3

10XKA11
GS001

3
3.7
3.7
8.3

0.0
0.0

N2XY-O 2x(3x1x240)/1x240
15 m

3~

~ 0.0

11BTL10

05

27.5 3/PEN ~400V 50Hz 50 kA 1 s


63.9

19
27.5
27.5
63.9

3.7
8.3

03

0.0
0.0

0.0
0.0

0.0
0.0

0.0
0.0

~ 0.0

0.0

0.0

10BTL11

~ 0.0

~ 0.0

0.0

0.0

10BRT02

10BTL12

10BTL21

17
24.8
24.8
50.9

~ 0.0
0.0

0.0
0.0
3.7
8.7

G
3~
3000/1A

3/PEN ~400V
50Hz 50 kA 1 s

0.0
0.0

01

3.2
6.3

19
12BFG 03
01
27.5
27.5
63.7 3/PEN ~400V 50Hz 50 kA 1 s

12BFT01
GT002

12BFH 01

06
0.0
0.0

12BFT02
GT002

12MKA
Sn = 313 MVA
Un = 16.5 kV
R/X = 0.05
xd'' = 25.4 %
cosphi = 0.85

~ 0.0

0.0

0.0

00PAC03
Pn = 1537 kW
In = 209.1 A
Un = 6 kV
cosphin = 0.74
Ia/In = 6
p=8
R/X = 0.15
etan = 95.6 %

00PAC02
Pn = 1537 kW
In = 209.1 A
Un = 6 kV
cosphin = 0.74
Ia/In = 6
p=8
R/X = 0.15
etan = 95.6 %

10.6
21.1

19
26.8
26.8
60.4

26.8
60.4

0.0
0.0

10BHT02
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

0.0
0.0

0.0
0.0

18
26.6
26.6
59.5

10BFJ

01

03

0.0
0.0

0.0
0.0

06
0.0
0.0

10BFK

0.0
0.0

26.6
59.5

MINISTRY OF ELECTRICITY AND ENERGY


EAST DELTA ELECTRICITY PRODUCTION COMPANY

10BHT02
GT002

3/PEN ~400V
50Hz 50 kA 1 s

THE ARAB REPUBLIC OF EGYPT

01

3/PEN ~400V
50Hz 50 kA 1 s

26.6
59.5
0.0
0.0

0.0
0.0

18
26.6
26.6
59.5

NEW TALKA POWER STATION 750MW COMBINED CYCLE PROJECT


JOB NO:

DRAWING NO.

REV.

12BTL20

12BJH
3/PEN ~400V 50Hz 50 kA 1 s

POWER GENERATION ENGINEERING AND


SERVICES COMPANY

24.8
50.8

24.9
51.4

Ursprung / Original

~ 0.0

~ 0.0

~ 0.0

~ 0.0

0.0

0.0

0.0

0.0

10BTL32

10BTL41

10BTL31

10BTL42

Ursprung-Nr. / Original-No.

PKZ / PC

NEW TALKHA 750MW CCPP


Name

Datum
Date

10BJJ
3/PEN ~400V 50Hz 50 kA 1 s

17
24.9
24.9
51.4

Urspr.-PKZ-Nr.
Orig.-PC

Projekt / Project

gezeich.
Drawn
bearb.
Coord.
geprft
Checked

2005-10-21

J.-H. Yang

2005-10-21

K. Specht

2005-10-21

H. Specht

10BRU02
N2XY-O 2x(3x1x240)/1x240
137 m

116
10.6
10.6
21.1

10BFJ00GS001

12BME00GS001

17
24.8
24.8
50.8

0.0

05

27.5 3/PEN ~400V 50Hz 50 kA 1 s


63.7

19
27.5
27.5
63.7

10BHT01
GT002

12BFG00GS001

~ 0.0
12BTL10

27.5
63.7

~ 0.0
10XKA11
Sn = 1.65 MVA
Un = 400 V
R/X = 0.15
xd'' = 80.5 %
cosphi = 0.80
In = 2382 A

2
3.2
3.2
6.3

0.0
0.0

3~

3000/1A

3
3.7
3.7
8.7

0.0
0.0

12BME

01

10XKA11GS003

10BTL22

15.0
24.0

10BMB00
GS012

GT

10BRT01

03

12BFE00GS001

10XKA11
GS002

N2XY-O 6x(3x1x240)/3x240
73 m

~ 0.0

10
12BFE
15.0
15.0
24.0 3/PEN ~400V
50Hz 50 kA 1 s

3
3.7
3.7
8.3

3.7
8.3

10BRU01
N2XY-O 2x(3x1x240)/1x240
101 m

3/PEN ~400V 50Hz 65 kA 1 s

12BFG00
GS002

100/1A

10.8
21.6

10BFK-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

3~

200/1A

3~

12BFE00GS002

10BHT02GT001

LXC0741 3x1586/1x2934
4m

3~

117
10.8
10.8
21.6

117
10.8
10.8
21.6

10BFT02GT002

10.8
21.6

3~

Spare

10BFT01GT002

10BBF00
GS002

04

0.0
0.0

100/1A

3~

100/1A

11BFT02
GT002

07

300/1A

3~

300/1A

11BFT01
GT002

00PAC03
AP001B

3~

00LAC12
Pn = 2074 kW
In = 227.0 A
Un = 6 kV
cosphin = 0.91
Ia/In = 6
p=1
R/X = 0.1
etan = 96.6 %

05

0.0
0.0

3~

11BFG00
GS002

10.0
18.7

109
10.0
10.0
18.7

00PAC02AP001

100/1A

11BFE00GS002

02

0.0
0.0

Space

13.3
33.5

145
13.3
13.3
33.5

03

50/1A

Space

10PCC12
AP001

100/1A

13.3
33.5

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

0.0
0.0

10BHT01

12BFG-LVM
Pn = 280 kW
In = 506.4 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

06

Spare

133
12.2
12.2
26.0
11BFT02
6.3 2x2.5%/0.42 kV
1600 kVA
M
uk = 6 %
3~
ur = 0.89 %
In = 147/2199 A
10PGC12
Dyn1
Pn = 300 kW
R0/R1 = 1
In = 34.8 A
X0/X1 = 0.95
Un = 6.3 kV
cosphin = 0.83
Ia/In = 5.5
p=2
R/X = 0.15
etan = 95.2 %

10.8
21.6

10BBF 01

12BBF00GS002M

100/1A

100/1A

12.2
26.0

N2XY-O 3x(3x1x240)/2x240
143 m
12BFE-LVM
Pn = 240 kW
In = 434.1 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

0.0
0.0

19
27.7
27.7
64.9

12BFT02

10BMB-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

13.0
31.6

142
13.0
13.0
31.6

LXC0741 3x1586/1x2934
4m

10BFJ

100/1A

100/1A

13.1
31.4

143
13.1
13.1
31.4

00LAC13
Pn = 2074 kW
In = 227.0 A
Un = 6 kV
cosphin = 0.91
Ia/In = 6
p=1
R/X = 0.1
etan = 96.6 %

12MBU25
Pn = 450 kW
In = 50.2 A
Un = 6 kV
cosphin = 0.9
Ia/In = 6
p=1
R/X = 0.15
etan = 95.8 %

10BMB

100/1A

100/1A

117
10.8
10.8
21.6

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

0.0
0.0

10PGC12
AP001

10BBF00GS001

0.0
0.0

10

0.0
0.0

1000/1A

12BBF00GS001

08

06

0.0
0.0

200/1A

300/1A

1000/1A

11BBT01
GT230

13.3
33.5

07

M
10BFT02GT001

11BFT02

11BFH-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

12BBT01GT220

01

07

0.0
0.0

500/1A

200/1A

Spare

LXC0741 3x1586/1x2934
4m

06

0.0
0.0

300/1A

11BFG

N2XY-O 3x(3x1x240)/2x240
89 m

11MKA
Sn = 313 MVA
Un = 16.5 kV
R/X = 0.05
xd'' = 25.4 %
cosphi = 0.85

11BFT01
6.3 2x2.5%/0.42 kV
1600 kVA
M
uk = 6 %
3~
ur = 0.89 %
In = 147/2199 A
10PGC11
Dyn1
Pn = 300 kW
R0/R1 = 1
In = 34.8 A
X0/X1 = 0.95
Un = 6.3 kV
cosphin = 0.83
Ia/In = 5.5
p=2
R/X = 0.15
etan = 95.2 %

300/1A

100/1A

13.3
33.6

145
13.3
13.3
33.6

00PAC03AP001A

08

2000/1A

2000/1A

Space

100/1A

N2XSY 3x1x120
178 m
131
12.0
12.0
25.0

50/1A

Spare

12.0
25.0

00PAC01
AP001

04

11BFT01

12BFH

GT

13.0
31.2

13000/1A

N2XSY 3x1x120
34 m

N2XSY 3x1x120
38 m

N2XSY 3x1x120
43 m

N2XSY 3x1x120
125 m
135
12.4
12.4
27.0

11MKC01
6.3 2x2.5%/0.66 kV
M
1650 kVA
3~
uk = 6 %
ur = 0.6 %
11MBN12
In = 151/1443 A
Pn = 650 kW
Dy5
In = 72.2 A

0.0
0.0

12.4
27.0

100/1A

10PCC11AP001

02

146
13.3
13.3
33.7

2000/1A

2000/1A

N2XY-O 3x(3x1x240)/2x240
15 m

11MBJ01
6.3 2x2.5%/1.8 kV
2570 kVA
uk = 5 %
ur = 0.51 %
In = 236/824 A
Dy5

139
12.7
12.7
30.3

12.2
26.2

Spare

100/1A

100/1A

LXC0741 3x1586/1x2934
4m

0.0
0.0

12.7
30.3

100/1A

100/1A

LXC0741 3x1586/1x2934
4m

142
13.0
13.0
31.8

N2XSY 3x1x120
144 m

N2XSY 3x1x240
94 m

N2XSY 2x(3x1x240)
94 m
13.0
31.8

100/1A

100/1A

LXC0741 3x1586/1x2934
4m

100/1A

03

0.0
0.0

Space

Space
100/1A

07

11BBF00
GS002

100/1A

50/1A

200/1A

200/1A

03

0.0
0.0

12BAA

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

2000/1A

2000/1A

N2XSY 3x1x120
122 m

500/1A

11MBN12
AP001

03

10BBE 01

2000/1A

12BBT01GT210

N2XSY 2x(3x1x240)
974 m

LXC0741 3x1586/1x2934
4m

11MKC01GT001

04

0.0
0.0

117
10.8
10.8
21.5

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

11BBE

N2XSY 3x1x120
151 m

08

0.0
0.0

08

N2XSY 3x1x120
33 m

11MBJ01
GT001

09

0.0
0.0

02

11BBT01

N2XY-O 2x(3x1x240)/1x240
15 m

10

11BBF 01

10.8
21.5

11BBT01

LXC0741 3x1586/1x2934
4m

0.0
0.0

145
13.3
13.3
33.6

0.0
0.0

10BBE00GS001

0.0
0.0

LXC0741 3x1586/1x2934
4m

11

02

13.3
33.6

0.0
0.0

1000/1A

11BBF00GS001

0.0
0.0

148
13.6
13.6
35.5

N2XSY 3x1x120
38 m

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

13.3
33.4

12BBT01
GT230

1000/1A

LXC0741 3x1586/1x2934
4m

11BBE 01

11BBT01GT220

13.6
35.5

LXC0741 3x1586/1x2934
4m

2000/1A

13.6
35.7

N2XSY 2x(3x1x240)
150 m

2000/1A

2000/1A

N2XSY 3x1x120
20 m

2000/1A

2000/1A

: Peak short-circuit current in kA

8
30 s

LXC0741 3x1586/1x2934
4m

2000/1A

2000/1A

12BBT01GT240

11BBF

N2XSY 2x(3x1x240)
984 m

2000/1A

750/1A

0.0
0.0

2000/1A

12BBT01

N2XSY 3x(3x1x240)
161 m

12BBE

11BBT01GT210

145
13.3
13.3
33.4

12BBT01
N2XSY 3x(3x1x240)
98 m

12BBF

4
N2XSY 3x(3x1x240)
161 m

11BAA

N2XSY 3x(3x1x240)
92 m

N2XSY 3x(3x1x240)
98 m

N2XSY 3x(3x1x240)
92 m

149
13.6
13.6
35.7

750/1A

N2XSY 3x1x120
173 m

2000/1A

750/1A

46.6
122.8

N2XSY 3x1x120
200 m

750/1A

0.0
0.0

N2XSY 3x1x120
15 m

2000/1A

0.0
0.0

N2XSY 3x1x240
150 m

8
30 s

ip

12BBT01
Dyn11yn11
16.5 9x1.25%/6.6/6.6 kV
32/16/16 MVA
uk = 8.66/8.71/15.15 %
ur = 0.48/0.48/0.96 %
In = 1120/1400/1400 A

1200/1A

1300/1A

1332
46.6
40.3
122.8

N2XSY 3x(3x1x240)
161 m

1200/1A

1300/1A

I b : Sym. short-circuit breaking current (r.m.s) in kA

I k " [kA]
ip
[kA]

[kA]

1200/1A

N2XSY 3x(3x1x240)
92 m

11BBT01
Dyn11yn11
16.5 9x1.25%/6.6/6.6 kV
32/16/16 MVA
uk = 8.61/8.64/15.13 %
ur = 0.48/0.48/0.96 %
In = 1120/1400/1400 A

I k " : Initial symmetrical short-circuit current (r.m.s.) in kA

1200/1A

N2XSY 3x(3x1x240)
152 m

1200/1A

1200/1A

N2XSY 3x(3x1x240)
92 m

1200/1A

N2XSY 3x(3x1x240)
152 m

1200/1A

ip

12BAT01
240 4x2.5%/16.5 kV
300 MVA
uk = 16.22 %
ur = 0.16 %
In = 722/10497 A
YNd1
Z0/Z1 = 1

S k " : Initial symmetrical short-circuit power in MVA

I k " [kA]
ip
[kA]

Sk " [MVA]

0.0
0.0

11BAT01
240 4x2.5%/16.5 kV
300 MVA
uk = 16.26 %
ur = 0.16 %
In = 722/10497 A
YNd1
Z0/Z1 = 1

Busbar/Node

N2XSY 3x1x120
20 m

718
1.9
1.8
5.1

Abtlg.
Dept.

SINUS

GmbH

SIEMENS
Power Generation (PG)

UA / DCC
Type

Benennung / Title

Inhaltskennzeichen
Contents Code

CALCULATION OF
SHORT-CIRCUIT CURRENTS,
LOAD FLOW AND VOLTAGE DROP
Annex 5
Dienstst. / Dept.

BN02

B
Zhl.-Nr.
Reg. No.

UNID

W 741

Index / Rev. Version

10691410
Ang.-Var. / Offer -Var.

EGY263-BN02-B-700021
Erstellt mit
Designed with

EGY263

Mastab
Scale

B
Var. / Opt.

Blatt-Nr. / Page-No.

1
Ersatz fr
Supersedes

Interconnected System
Sk''Act = 12956 MVA
c=1
R/X = 0.1436

Calculated Case 2:

MIN. TWO-PHASE SHORT-CIRCUIT CURRENTS

ADA
BB I

(ACCORDING TO IEC EN 60909-0:2001)

3 ~ 220 kV 50 Hz

Operation Mode Configuration 2:

BB II

The minimum short-circuit current in the MV system is to be expected at the end of the coupling
chain of the MV switchgear, if one unit generator (11MKA) is shut down and the remaining unit
generator 12MKA is in isolated operation and supplies the auxiliary system.

1.6
4.4

1.6
4.4

The minimum short-circuit currents in the LV switchgear 11BME, 12BME, 10BMA and 10BMB
are calculated for emergency operation when the emergency diesel generator 10XKA11 supplies
these switchgear.

Legend:

0.0
0.0

40.4
106.4

8
30 s

8
30 s

2000/1A

500/1A

11MBN12
AP001

11MBU25
AP001

100/1A

200/1A

03
11BBE00
GS001

00LAC11
AP001

100/1A

50/1A

07

0.0
0.0

06

0.0
0.0

12BFT02GT001

07

06

10BFT01GT001

200/1A

300/1A

05

0.0
0.0

11BFT01GT001

10PGC11
AP001

N2XSY 3x(3x1x240)
161 m

04

0.0
0.0
00LCB11
AP001

05

10.4
25.5

19
10.4
10.4
25.5

0.0
0.0

0.0
0.0

16.4
40.2

11
16.4
16.4
40.2

67
10.6
10.6
22.7

11.5
29.0

72
11.5
11.5
29.0

3~

3~

11MBU25
Pn = 450 kW
In = 50.2 A
Un = 6 kV
cosphin = 0.9
Ia/In = 6
p=1
R/X = 0.15
etan = 95.8 %

Un = 6 kV
cosphin = 0.9
Ia/In = 6
p=1
R/X = 0.15
etan = 96.2 %

00LAC11
Pn = 2074 kW
In = 227.0 A
Un = 6 kV
cosphin = 0.91
Ia/In = 6
p=1
R/X = 0.1
etan = 96.6 %

11.2
26.8

71
11.2
11.2
26.8

0.0
0.0

24.0
56.0

10
24.0
24.0
56.0

0.0
0.0

71
11.3
11.3
27.0
12BFT02
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95
10
24.0
24.0
56.1

0.0
0.0

24.0
56.1

10BFT01
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

SFC

SEE

10BBE00
GS002

100/1A

LXC0741 3x1586/1x2934
4m

11BFE-LVM
Pn = 240 kW
In = 434.1 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

11BME-LVM
Pn = 117 kW
In = 211.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

11BFG-LVM
Pn = 280 kW
In = 506.4 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

12BBE 02

10BHT01GT001 M

2000/1A

2000/1A

2000/1A

2000/1A

2000/1A

2000/1A

2000/1A

11

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

10

0.0
0.0

12MBJ01
GT001

11BBT01GT240

11.5
29.2

12MKC01GT001

09
12BFT01GT001

12MBN12
AP001

200/1A

200/1A

08

0.0
0.0

N2XSY 3x1x120
122 m

3~

3~

00LCB11
Pn = 656 kW
In = 76.8 A
Un = 6 kV
cosphin = 0.86
Ia/In = 6
p=2
R/X = 0.15
etan = 95.6 %

58
9.2
9.2
18.2

3~

00PAC01
Pn = 1537 kW
In = 209.1 A
Un = 6 kV
cosphin = 0.74
Ia/In = 6
p=8
R/X = 0.15
etan = 95.6 %

10PCC11
Pn = 270 kW
In = 32.3 A
Un = 6.3 kV
cosphin = 0.81
Ia/In = 5.4
p=3
R/X = 0.15
etan = 94.6 %

100/1A

100/1A

100/1A

8.7
16.1

55
8.7
8.7
16.1

04

0.0
0.0
12MBU25
AP001

100/1A

03

00LAC13
AP001

12BBE01
GS001

06

0.0
0.0

50/1A

05

0.0
0.0

12BBF 02

72
11.5
11.5
29.0

01

11BFT02GT001

200/1A

03

04

0.0
0.0

00LAC12
AP001

50/1A

9
23.2
23.2
52.3

Spare

9.2
18.2
0.0
0.0

23.2
52.3

100/1A

11.2
26.9

70
11.2
11.2
26.9

10BHT01
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

10.4
25.3

19
10.4
10.4
25.3

0.0
0.0

16.4
39.9

11
16.4
16.4
39.9

0.0
0.0

12BFT01
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

12MKC01
6.3 2x2.5%/0.66 kV
1650 kVA
uk = 6 %
ur = 0.6 %
In = 151/1443 A
Dy5

10BFT02

100/1A

100/1A

10.8
25.0

68
10.8
10.8
25.0

0.0
0.0

12MBJ01
6.3 2x2.5%/1.8 kV
2570 kVA
uk = 5 %
ur = 0.51 %
In = 236/824 A
Dy5

100/1A

10.3
21.0

65
10.3
10.3
21.0

0.0
0.0

Spare

10.5
21.9

66
10.5
10.5
21.9

11.5
29.2

73
11.5
11.5
29.2

3~

3~

3~

12MBN12
Pn = 650 kW
In = 72.2 A
Un = 6 kV
cosphin = 0.9
Ia/In = 6
p=1
R/X = 0.15
etan = 96.2 %

05

00LCB12
AP001

300/1A

SFC

SEE

0.0
0.0

24.0
56.2

10
24.0
24.0
56.2

10BMA-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

10BFT02
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

11BFH

13000/1A

12BME-LVM
Pn = 117 kW
In = 211.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

24.0
56.2
0.0
0.0

72
11.5
11.5
29.0

00LCB12
Pn = 656 kW
In = 76.8 A
Un = 6 kV
cosphin = 0.86
Ia/In = 6
p=2
R/X = 0.15
etan = 95.6 %

10PCC12
Pn = 270 kW
In = 32.3 A
Un = 6.3 kV
cosphin = 0.81
Ia/In = 5.4
p=3
R/X = 0.15
etan = 94.6 %

12BFH-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

10BFJ-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

3~

3~

3~

3~

3~

3~

3~

3~

3~

6
11BFE
16.0
16.0
27.3 3/PEN ~400V
50Hz 50 kA 1 s

03

16.0
27.3
0.0
0.0

11BME

01
M

3/PEN ~400V
50Hz 50 kA 1 s

01

0.0
0.0

5.2
9.7

2
5.2
5.2
9.7

11BFE00GS001

0.0
10
11BFG 03
0.0
23.9
23.9
55.4 3/PEN ~400V 50Hz 50 kA 1 s

01

11BFH 01

06
0.0
0.0

23.9
55.4
0.0
0.0

3
6.3
6.3
13.9

10BMA 01

3/PEN ~400V 50Hz 65 kA 1 s 07

03

0.0
0.0

11BFG00GS001
M

11BME00GS001

~ 0.0

0.0

0.0
11BTL20

11BJH
3/PEN ~400V 50Hz 50 kA 1 s

21.5
44.1

0.0
0.0

0.0
0.0

06

0.0
0.0

10BMA00
GS011

10BMA00GS001

10BMB 01
06

6.3
13.9

10XKA11
GS001

3
6.3
6.3
13.9

0.0
0.0

N2XY-O 2x(3x1x240)/1x240
15 m

3~

~ 0.0

11BTL10

05

23.9 3/PEN ~400V 50Hz 50 kA 1 s


55.4

10
23.9
23.9
55.4

6.3
13.9

03

0.0
0.0

0.0
0.0

0.0
0.0

0.0
0.0

~ 0.0

0.0

0.0

10BTL11

~ 0.0

~ 0.0

0.0

0.0

10BRT02

10BTL12

10BTL21

9
21.5
21.5
44.1

~ 0.0
0.0

0.0
0.0
6.65
15.5

G
3~
3000/1A

3/PEN ~400V
50Hz 50 kA 1 s

0.0
0.0

01

4.9
8.7

10
12BFG 03
01
23.8
23.8
55.2 3/PEN ~400V 50Hz 50 kA 1 s

12BFT01
GT002

12BFH 01

06
0.0
0.0

12BFT02
GT002

12MKA
Sn = 313 MVA
Un = 16.5 kV
R/X = 0.05
xd'' = 25.4 %
cosphi = 0.85

~ 0.0

0.0

0.0

00PAC03
Pn = 1537 kW
In = 209.1 A
Un = 6 kV
cosphin = 0.74
Ia/In = 6
p=8
R/X = 0.15
etan = 95.6 %

00PAC02
Pn = 1537 kW
In = 209.1 A
Un = 6 kV
cosphin = 0.74
Ia/In = 6
p=8
R/X = 0.15
etan = 95.6 %

9.2
18.2

9
23.2
23.2
52.3

23.2
52.3

0.0
0.0

10BHT02
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

0.0
0.0

0.0
0.0

9
23.1
23.1
51.6

10BFJ

01

03

0.0
0.0

0.0
0.0

06
0.0
0.0

10BFK

0.0
0.0

23.1
51.6

MINISTRY OF ELECTRICITY AND ENERGY


EAST DELTA ELECTRICITY PRODUCTION COMPANY

10BHT02
GT002

3/PEN ~400V
50Hz 50 kA 1 s

THE ARAB REPUBLIC OF EGYPT

01

3/PEN ~400V
50Hz 50 kA 1 s

23.1
51.6
0.0
0.0

0.0
0.0

9
23.1
23.1
51.6

NEW TALKA POWER STATION 750MW COMBINED CYCLE PROJECT


JOB NO:

DRAWING NO.

REV.

12BTL20

12BJH
3/PEN ~400V 50Hz 50 kA 1 s

POWER GENERATION ENGINEERING AND


SERVICES COMPANY

21.5
44.0

21.5
44.5

Ursprung / Original

~ 0.0

~ 0.0

~ 0.0

~ 0.0

0.0

0.0

0.0

0.0

10BTL32

10BTL41

10BTL31

10BTL42

Ursprung-Nr. / Original-No.

PKZ / PC

NEW TALKHA 750MW CCPP


Name

Datum
Date

10BJJ
3/PEN ~400V 50Hz 50 kA 1 s

9
21.5
21.5
44.5

Urspr.-PKZ-Nr.
Orig.-PC

Projekt / Project

gezeich.
Drawn
bearb.
Coord.
geprft
Checked

2005-10-21

J.-H. Yang

2005-10-21

K. Specht

2005-10-21

H. Specht

10BRU02
N2XY-O 2x(3x1x240)/1x240
137 m

58
9.2
9.2
18.2

10BFJ00GS001

12BME00GS001

9
21.5
21.5
44.0

0.0

05

23.8 3/PEN ~400V 50Hz 50 kA 1 s


55.2

10
23.8
23.8
55.2

10BHT01
GT002

12BFG00GS001

~ 0.0
12BTL10

23.8
55.2

~ 0.0
10XKA11
Sn = 1.65 MVA
Un = 400 V
R/X = 0.15
xd'' = 31.5 %
cosphi = 0.80
In = 2382 A

2
4.9
4.9
8.7

0.0
0.0

3~

3000/1A

3
6.6
6.6
15.5

0.0
0.0

12BME

01

10XKA11GS003

10BTL22

12.9
20.8

10BMB00
GS012

GT

10BRT01

03

12BFE00GS001

10XKA11
GS002

N2XY-O 6x(3x1x240)/3x240
73 m

~ 0.0

5
12BFE
12.9
12.9
20.8 3/PEN ~400V
50Hz 50 kA 1 s

3
6.3
6.3
13.9

6.3
13.9

10BRU01
N2XY-O 2x(3x1x240)/1x240
101 m

3/PEN ~400V 50Hz 65 kA 1 s

12BFG00
GS002

100/1A

9.3
18.7

10BFK-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

3~

200/1A

3~

12BFE00GS002

10BHT02GT001

LXC0741 3x1586/1x2934
4m

3~

59
9.3
9.3
18.7

59
9.3
9.3
18.7

10BFT02GT002

9.3
18.7

3~

Spare

10BFT01GT002

10BBF00
GS002

04

0.0
0.0

100/1A

3~

100/1A

11BFT02
GT002

07

300/1A

3~

300/1A

11BFT01
GT002

00PAC03
AP001B

3~

00LAC12
Pn = 2074 kW
In = 227.0 A
Un = 6 kV
cosphin = 0.91
Ia/In = 6
p=1
R/X = 0.1
etan = 96.6 %

05

0.0
0.0

3~

11BFG00
GS002

8.7
16.2

55
8.7
8.7
16.2

00PAC02AP001

100/1A

11BFE00GS002

02

0.0
0.0

Space

11.5
29.0

72
11.5
11.5
29.0

03

50/1A

Space

10PCC12
AP001

100/1A

11.5
29.0

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

0.0
0.0

10BHT01

12BFG-LVM
Pn = 280 kW
In = 506.4 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

06

Spare

66
10.6
10.6
22.5
11BFT02
6.3 2x2.5%/0.42 kV
1600 kVA
M
uk = 6 %
3~
ur = 0.89 %
In = 147/2199 A
10PGC12
Dyn1
Pn = 300 kW
R0/R1 = 1
In = 34.8 A
X0/X1 = 0.95
Un = 6.3 kV
cosphin = 0.83
Ia/In = 5.5
p=2
R/X = 0.15
etan = 95.2 %

9.3
18.7

10BBF 01

12BBF00GS002M

100/1A

100/1A

10.6
22.5

N2XY-O 3x(3x1x240)/2x240
143 m
12BFE-LVM
Pn = 240 kW
In = 434.1 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

0.0
0.0

10
24.0
24.0
56.2

12BFT02

10BMB-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

11.3
27.4

71
11.3
11.3
27.4

LXC0741 3x1586/1x2934
4m

10BFJ

100/1A

100/1A

11.3
27.2

71
11.3
11.3
27.2

00LAC13
Pn = 2074 kW
In = 227.0 A
Un = 6 kV
cosphin = 0.91
Ia/In = 6
p=1
R/X = 0.1
etan = 96.6 %

12MBU25
Pn = 450 kW
In = 50.2 A
Un = 6 kV
cosphin = 0.9
Ia/In = 6
p=1
R/X = 0.15
etan = 95.8 %

10BMB

100/1A

100/1A

59
9.3
9.3
18.7

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

0.0
0.0

10PGC12
AP001

10BBF00GS001

0.0
0.0

10

0.0
0.0

1000/1A

12BBF00GS001

08

06

0.0
0.0

200/1A

300/1A

1000/1A

11BBT01
GT230

11.5
29.0

07

M
10BFT02GT001

11BFT02

11BFH-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

12BBT01GT220

01

07

0.0
0.0

500/1A

200/1A

Spare

LXC0741 3x1586/1x2934
4m

06

0.0
0.0

300/1A

11BFG

N2XY-O 3x(3x1x240)/2x240
89 m

11MKA
Sn = 313 MVA
Un = 16.5 kV
R/X = 0.05
xd'' = 25.4 %
cosphi = 0.85

11BFT01
6.3 2x2.5%/0.42 kV
1600 kVA
M
uk = 6 %
3~
ur = 0.89 %
In = 147/2199 A
10PGC11
Dyn1
Pn = 300 kW
R0/R1 = 1
In = 34.8 A
X0/X1 = 0.95
Un = 6.3 kV
cosphin = 0.83
Ia/In = 5.5
p=2
R/X = 0.15
etan = 95.2 %

300/1A

100/1A

11.5
29.1

73
11.5
11.5
29.1

00PAC03AP001A

08

2000/1A

Space

100/1A

N2XSY 3x1x120
178 m
66
10.4
10.4
21.7

50/1A

Spare

10.4
21.7

00PAC01
AP001

04

11BFT01

12BFH

GT

11.3
27.0

13000/1A

N2XSY 3x1x120
34 m

N2XSY 3x1x120
38 m

N2XSY 3x1x120
43 m

N2XSY 3x1x120
125 m
67
10.7
10.7
23.4

11MKC01
6.3 2x2.5%/0.66 kV
M
1650 kVA
3~
uk = 6 %
ur = 0.6 %
11MBN12
In = 151/1443 A
Pn = 650 kW
Dy5
In = 72.2 A

0.0
0.0

10.7
23.4

100/1A

02

73
11.5
11.5
29.2

N2XSY 2x(3x1x240)
974 m

N2XY-O 3x(3x1x240)/2x240
15 m

11MBJ01
6.3 2x2.5%/1.8 kV
2570 kVA
uk = 5 %
ur = 0.51 %
In = 236/824 A
Dy5

69
11.0
11.0
26.2

10.6
22.7

Spare

100/1A

100/1A

LXC0741 3x1586/1x2934
4m

0.0
0.0

11.0
26.2

100/1A

100/1A

LXC0741 3x1586/1x2934
4m

71
11.3
11.3
27.5

N2XSY 3x1x120
144 m

N2XSY 3x1x240
94 m

N2XSY 2x(3x1x240)
94 m
11.3
27.5

100/1A

100/1A

LXC0741 3x1586/1x2934
4m

100/1A

03

10PCC11AP001

12BAA

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

11BBE

12BBT01GT210

0.0
0.0

Space

Space
100/1A

07

11BBF00
GS002

100/1A

50/1A

200/1A

200/1A

03

0.0
0.0

10BBE 01

N2XSY 3x1x120
122 m

11MKC01GT001

04

0.0
0.0

59
9.3
9.3
18.7

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

: Peak short-circuit current in kA

LXC0741 3x1586/1x2934
4m

08

0.0
0.0

08

11BBT01

N2XSY 3x1x120
151 m

11MBJ01
GT001

09

0.0
0.0

02

9.3
18.7

11BBT01

N2XSY 3x1x120
33 m

10

11BBF 01

0.0
0.0

10BBE00GS001

0.0
0.0

LXC0741 3x1586/1x2934
4m

0.0
0.0

73
11.5
11.5
29.1

0.0
0.0

N2XY-O 2x(3x1x240)/1x240
15 m

11

02

11.5
29.1

0.0
0.0

1000/1A

11BBF00GS001

ip

74
11.7
11.7
30.8

LXC0741 3x1586/1x2934
4m

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

11.5
29.0

12BBT01
GT230

1000/1A

LXC0741 3x1586/1x2934
4m

11BBE 01

11BBT01GT220

11.7
30.8

N2XSY 3x1x120
38 m

2000/1A

11.8
30.9

N2XSY 2x(3x1x240)
150 m

2000/1A

2000/1A

N2XSY 3x1x120
20 m

2000/1A

2000/1A

[kA]

8
30 s

LXC0741 3x1586/1x2934
4m

2000/1A

2000/1A

12BBT01GT240

11BBF

N2XSY 2x(3x1x240)
984 m

2000/1A

750/1A

0.0
0.0

2000/1A

12BBT01

N2XSY 3x(3x1x240)
161 m

12BBE

11BBT01GT210

72
11.5
11.5
29.0

12BBT01
N2XSY 3x(3x1x240)
98 m

12BBF

4
N2XSY 3x(3x1x240)
161 m

11BAA

N2XSY 3x(3x1x240)
92 m

N2XSY 3x(3x1x240)
98 m

N2XSY 3x(3x1x240)
92 m

74
11.8
11.8
30.9

750/1A

LXC0741 3x1586/1x2934
4m

2000/1A

750/1A

0.0
0.0

N2XSY 3x1x120
173 m

750/1A

I b : Sym. short-circuit breaking current (r.m.s) in kA

I k " [kA]
ip
[kA]

12BBT01
Dyn11yn11
16.5 9x1.25%/6.6/6.6 kV
32/16/16 MVA
uk = 8.66/8.71/15.15 %
ur = 0.48/0.48/0.96 %
In = 1120/1400/1400 A

1200/1A

1300/1A

666
40.4
40.4
106.4

N2XSY 3x1x120
200 m

2000/1A

I k " : Initial symmetrical short-circuit current (r.m.s.) in kA

1200/1A

N2XSY 3x1x120
15 m

8
30 s

S k " : Initial symmetrical short-circuit power in MVA

I k " [kA]
ip
[kA]

1200/1A

N2XSY 3x1x240
150 m

1200/1A

1300/1A

ip
1200/1A

N2XSY 3x(3x1x240)
92 m

11BBT01
Dyn11yn11
16.5 9x1.25%/6.6/6.6 kV
32/16/16 MVA
uk = 8.61/8.64/15.13 %
ur = 0.48/0.48/0.96 %
In = 1120/1400/1400 A

I k " [kA]
[kA]
Ib

N2XSY 3x(3x1x240)
152 m

1200/1A

1.6
4.4

N2XSY 3x(3x1x240)
92 m

1200/1A

Sk " [MVA]

N2XSY 3x(3x1x240)
161 m

1200/1A

12BAT01
240 4x2.5%/16.5 kV
300 MVA
uk = 16.22 %
ur = 0.16 %
In = 722/10497 A
YNd1
Z0/Z1 = 1

0.0
0.0

N2XSY 3x(3x1x240)
152 m

11BAT01
240 4x2.5%/16.5 kV
300 MVA
uk = 16.26 %
ur = 0.16 %
In = 722/10497 A
YNd1
Z0/Z1 = 1

Busbar/Node

N2XSY 3x1x120
20 m

359
1.6
1.6
4.4

Abtlg.
Dept.

SINUS

GmbH

SIEMENS
Power Generation (PG)

UA / DCC
Type

Benennung / Title

Inhaltskennzeichen
Contents Code

CALCULATION OF
SHORT-CIRCUIT CURRENTS,
LOAD FLOW AND VOLTAGE DROP
Annex 6
Dienstst. / Dept.

BN02

B
Zhl.-Nr.
Reg. No.

UNID

W 741

Index / Rev. Version

10691410
Ang.-Var. / Offer -Var.

EGY263-BN02-B-700021
Erstellt mit
Designed with

EGY263

Mastab
Scale

B
Var. / Opt.

Blatt-Nr. / Page-No.

1
Ersatz fr
Supersedes

Interconnected System
Sk''Act = 12956 MVA
c=1
R/X = 0.1436

Calculated Case 3:

MIN. SINGLE-PHASE SHORT-CIRCUIT CURRENTS

ADA
2.41
0.80

BB I

(ACCORDING TO IEC EN 60909-0:2001)

3 ~ 220 kV 50 Hz

Operation Mode Configuration 2:

BB II

The minimum short-circuit current in the MV system is to be expected at the end of the coupling
chain of the MV switchgear, if one unit generator (11MKA) is shut down and the remaining unit
generator 12MKA is in isolated operation and supplies the auxiliary system.

2.41
0.80

2.41
0.80

The minimum short-circuit currents in the LV switchgear 11BME, 12BME, 10BMA and 10BMB
are calculated for emergency operation when the emergency diesel generator 10XKA11 supplies
these switchgear.

Legend:
Busbar/Node

I k L1" [kA]
I0
[kA]

0.00
0.00

I k L1" [kA]
[kA]
I0

2.41
0.80

2000/1A

11MKC01GT001

500/1A

08

0.00
0.00
11MBN12
AP001

11MBU25
AP001

100/1A

200/1A

04

0.00
0.00

03
11BBE00
GS001

00LAC11
AP001

100/1A

50/1A

07

0.00
0.00

06

0.00
0.00

12BFT02GT001

07

06

10BFT01GT001

200/1A

300/1A

05

0.00
0.00

11BFT01GT001

03

0.00
0.00
10PGC11
AP001

N2XSY 3x(3x1x240)
161 m

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

04

0.00
0.00
00LCB11
AP001

11MBJ01
6.3 2x2.5%/1.8 kV
2570 kVA
uk = 5 %
ur = 0.51 %
In = 236/824 A
Dy5

0.00
0.00

0.00
0.00

0.00
0.00

0.45
0.15

0.00
0.00

0.00
0.00

0.00
0.00

0.45
0.15

11MKC01
6.3 2x2.5%/0.66 kV
M
1650 kVA
3~
uk = 6 %
ur = 0.6 %
11MBN12
In = 151/1443 A
Pn = 650 kW
Dy5
In = 72.2 A

0.45
0.15

0.45
0.15

3~

3~

11MBU25
Pn = 450 kW
In = 50.2 A
Un = 6 kV
cosphin = 0.9
Ia/In = 6
p=1
R/X = 0.15
etan = 95.8 %

Un = 6 kV
cosphin = 0.9
Ia/In = 6
p=1
R/X = 0.15
etan = 96.2 %

0.00
0.00

0.45
0.15

0.45
0.15

00LAC11
Pn = 2074 kW
In = 227.0 A
Un = 6 kV
cosphin = 0.91
Ia/In = 6
p=1
R/X = 0.1
etan = 96.6 %

0.45
0.15

0.45
0.15

29.67
9.89

0.00
0.00

29.67
9.89
0.00
0.00

0.45
0.15
12BFT02
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95
29.68
9.89

0.00
0.00

29.68
9.89

10BFT01
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

11BFT01
6.3 2x2.5%/0.42 kV
1600 kVA
M
uk = 6 %
3~
ur = 0.89 %
In = 147/2199 A
10PGC11
Dyn1
Pn = 300 kW
R0/R1 = 1
In = 34.8 A
X0/X1 = 0.95
Un = 6.3 kV
cosphin = 0.83
Ia/In = 5.5
p=2
R/X = 0.15
etan = 95.2 %

10PCC11AP001

00PAC01
AP001

04
00PAC03AP001A

300/1A

08
10BBE00
GS002

SFC

SEE

100/1A

100/1A

LXC0741 3x1586/1x2934
4m

N2XY-O 3x(3x1x240)/2x240
89 m
11BFE-LVM
Pn = 240 kW
In = 434.1 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

11BME-LVM
Pn = 117 kW
In = 211.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

11BFG-LVM
Pn = 280 kW
In = 506.4 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

12BBE 02
11

10BHT01GT001 M

11BBE

2000/1A

2000/1A

2000/1A

2000/1A

2000/1A

2000/1A

2000/1A

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

10

12MBJ01
GT001

11BBT01GT240

0.00
0.00

12MKC01GT001

09
12BFT01GT001

12MBN12
AP001

200/1A

200/1A

08

0.00
0.00

12BBT01GT220

01

07

0.00
0.00

500/1A

0.43
0.14

0.43
0.14

3~

3~

00LCB11
Pn = 656 kW
In = 76.8 A
Un = 6 kV
cosphin = 0.86
Ia/In = 6
p=2
R/X = 0.15
etan = 95.6 %

0.44
0.15

3~

00PAC01
Pn = 1537 kW
In = 209.1 A
Un = 6 kV
cosphin = 0.74
Ia/In = 6
p=8
R/X = 0.15
etan = 95.6 %

10PCC11
Pn = 270 kW
In = 32.3 A
Un = 6.3 kV
cosphin = 0.81
Ia/In = 5.4
p=3
R/X = 0.15
etan = 94.6 %

100/1A

100/1A

100/1A

N2XSY 3x1x120
122 m

0.45
0.15

04

0.00
0.00
12MBU25
AP001

100/1A

03

12BBE01
GS001

06

0.00
0.00
00LAC13
AP001

50/1A

05

0.00
0.00

12BBF 02

0.45
0.15

07

M
10BFT02GT001

1000/1A

11BBT01
GT230

0.45
0.15

01

11BFT02GT001

200/1A

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

03

0.00
0.00

10PGC12
AP001

00LAC12
AP001

50/1A

28.99
9.66

Spare

0.44
0.15
0.00
0.00

28.99
9.66

100/1A

0.45
0.15

0.45
0.15
10BHT01
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

0.00
0.00

0.00
0.00

0.00
0.00

0.00
0.00

12BFT01
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

0.00
0.00

0.00
0.00

10BFT02

0.44
0.15

0.44
0.15
12MKC01
6.3 2x2.5%/0.66 kV
1650 kVA
uk = 6 %
ur = 0.6 %
In = 151/1443 A
Dy5

100/1A

100/1A

0.45
0.15

0.45
0.15

0.00
0.00

12MBJ01
6.3 2x2.5%/1.8 kV
2570 kVA
uk = 5 %
ur = 0.51 %
In = 236/824 A
Dy5

100/1A

0.00
0.00

Spare

0.44
0.15

0.44
0.15

0.45
0.15

0.45
0.15

3~

3~

3~

12MBN12
Pn = 650 kW
In = 72.2 A
Un = 6 kV
cosphin = 0.9
Ia/In = 6
p=1
R/X = 0.15
etan = 96.2 %

04

0.00
0.00

SFC

SEE

0.00
0.00

29.70
9.90

29.70
9.90

0.45
0.15

10BMA-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

D
11BFH

13000/1A

12BME-LVM
Pn = 117 kW
In = 211.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

11BFT02
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

0.00
0.00

M
3~

00LCB12
Pn = 656 kW
In = 76.8 A
Un = 6 kV
cosphin = 0.86
Ia/In = 6
p=2
R/X = 0.15
etan = 95.6 %

10PCC12
Pn = 270 kW
In = 32.3 A
Un = 6.3 kV
cosphin = 0.81
Ia/In = 5.4
p=3
R/X = 0.15
etan = 94.6 %

12BFH-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

10BFJ-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

10BFK-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

3~

3~

3~

3~

3~

3~

3~

3~

3~

3~

3~

11BFE
3/PEN ~400V
50Hz 50 kA 1 s

03

12.51
4.17
0.00
0.00

11BME

01
M

3/PEN ~400V
50Hz 50 kA 1 s

01

0.00
0.00

5.17
1.72

5.17
1.72

11BFE00GS001

29.24
9.75

11BFG

03

0.00
0.00

3/PEN ~400V 50Hz 50 kA 1 s

01

11BFH 01

06
0.00
0.00

29.24
9.75

05

29.24 3/PEN ~400V 50Hz 50 kA 1 s


9.75

0.00
0.00

29.24
9.75

9.99
3.33

10BMA 01

3/PEN ~400V 50Hz 65 kA 1 s 07

03

0.00
0.00

11BFG00GS001
M

11BME00GS001

0.00
0.00

0.00
0.00

06

0.00
0.00

10BMA00
GS011

10BMA00GS001

10BMB 01
06

9.99
3.33

10XKA11
GS001

3/PEN ~400V 50Hz 65 kA 1 s


9.99
3.33

12BFE00GS002

03

0.00
0.00

0.00
0.00

0.00
0.00

0.00
0.00

8.89
2.96

9.99
3.33

12BFE
3/PEN ~400V
50Hz 50 kA 1 s

03

8.89
2.96
0.00
0.00

12BME

01
M

3/PEN ~400V
50Hz 50 kA 1 s

0.00
0.00

01

4.34
1.45

4.34
1.45

12BFE00GS001

10XKA11
GS002

29.22
9.74

12BFG 03

12BFG00
GS002

0.00
0.00

12BFT01
GT002

01

06

3/PEN ~400V 50Hz 50 kA 1 s

0.00
0.00

12BFH 01
M

12BFT02
GT002

29.22
9.74

05

29.22 3/PEN ~400V 50Hz 50 kA 1 s


9.74

0.00
0.00

29.22 28.55
9.74 9.52

10BFJ
03

01
0.00
0.00

10BHT01
GT002

12BME00GS001

3/PEN ~400V
50Hz 50 kA 1 s
0.00
0.00

06
0.00
0.00

10BFK

0.00
0.00

28.55
9.52

EAST DELTA ELECTRICITY PRODUCTION COMPANY

01

3/PEN ~400V
50Hz 50 kA 1 s

28.55
9.52
0.00
0.00

0.00
0.00

NEW TALKA POWER STATION 750MW COMBINED CYCLE PROJECT

28.55
9.52

JOB NO:

~ 0.00

0.00

0.00

11BTL10

11BTL20

11BJH
3/PEN ~400V 50Hz 50 kA 1 s

22.40
7.47

N2XY-O 6x(3x1x240)/3x240
73 m

~ 0.00

~ 0.00

0.00

0.00

10BRT01

~ 0.00

~ 0.00

0.00

0.00

10BTL12

10BTL21

10BRT02

10XKA11GS003

10BTL22

10BTL11
M

G
3~
12MKA
Sn = 313 MVA
Un = 16.5 kV
R/X = 0.05
xd'' = 25.4 %
cosphi = 0.85

~ 0.00

~ 0.00

0.00

0.00

12BTL10

12BTL20

3000/1A

22.40
7.47

~ 0.00
0.00

11.82
3.94

0.00
0.00
11.82
3.94

10BRU01

G
N2XY-O 2x(3x1x240)/1x240
101 m

GT

3~
3000/1A

22.38
7.46

~ 0.00
10XKA11
Sn = 1.65 MVA
Un = 400 V
R/X = 0.15
xd'' = 19.9 %
cosphi = 0.80
In = 2382 A

12BJH
3/PEN ~400V 50Hz 50 kA 1 s

22.38
7.46

24.36
8.12

Ursprung / Original

~ 0.00

~ 0.00

~ 0.00

~ 0.00

0.00

0.00

0.00

0.00

10BTL31

10BTL42

10BTL32

10BTL41

Ursprung-Nr. / Original-No.

PKZ / PC

NEW TALKHA 750MW CCPP


Name

Datum
Date

10BJJ
3/PEN ~400V 50Hz 50 kA 1 s

24.36
8.12

gezeich.
Drawn
bearb.
Coord.

2005-10-21

J.-H. Yang

2005-10-21

K. Specht

2005-10-21

H. Specht

10BRU02
N2XY-O 2x(3x1x240)/1x240
137 m

REV.

Urspr.-PKZ-Nr.
Orig.-PC

Projekt / Project

geprft
Checked

0.00

DRAWING NO.

POWER GENERATION ENGINEERING AND


SERVICES COMPANY

N2XY-O 3x(3x1x240)/2x240
15 m

~ 0.00

9.99
3.33

0.00
0.00

10BFJ00GS001

N2XY-O 2x(3x1x240)/1x240
15 m

3~
11MKA
Sn = 313 MVA
Un = 16.5 kV
R/X = 0.05
xd'' = 25.4 %
cosphi = 0.85

0.00
0.00

N2XY-O 2x(3x1x240)/1x240
15 m

28.99
9.66

10BHT02
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

MINISTRY OF ELECTRICITY AND ENERGY

9.99
3.33

GT

28.99
9.66

0.00
0.00

THE ARAB REPUBLIC OF EGYPT

10BHT02
GT002

12BFG00GS001

10BMB00
GS012

00PAC03
Pn = 1537 kW
In = 209.1 A
Un = 6 kV
cosphin = 0.74
Ia/In = 6
p=8
R/X = 0.15
etan = 95.6 %

00PAC02
Pn = 1537 kW
In = 209.1 A
Un = 6 kV
cosphin = 0.74
Ia/In = 6
p=8
R/X = 0.15
etan = 95.6 %

0.44
0.15

3~

0.44
0.15

LXC0741 3x1586/1x2934
4m

10BFT02GT002

100/1A

0.44
0.15

3~

10BFT01GT002

0.44
0.15

0.44
0.15

0.44
0.15

3~

11BFT02
GT002

10BHT02GT001

200/1A

Spare

00LAC12
Pn = 2074 kW
In = 227.0 A
Un = 6 kV
cosphin = 0.91
Ia/In = 6
p=1
R/X = 0.1
etan = 96.6 %

10BBF00
GS002

04

0.00
0.00

100/1A

3~

100/1A

10PGC12
Pn = 300 kW
In = 34.8 A
Un = 6.3 kV
cosphin = 0.83
Ia/In = 5.5
p=2
R/X = 0.15
etan = 95.2 %

07

300/1A

3~

11BFT01
GT002

00PAC03
AP001B

0.43
0.14

0.43
0.14

11BFG00
GS002

300/1A

100/1A

00PAC02AP001

05

0.00
0.00

Space

11BFE00GS002

02

0.00
0.00

50/1A

Space

10PCC12
AP001

0.45
0.15

0.45
0.15

03

0.00
0.00

100/1A

0.45
0.15

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

3~

10BHT01

12BFG-LVM
Pn = 280 kW
In = 506.4 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

06

Spare

0.45
0.15

0.44
0.15

10BBF 01

12BBF00GS002M

100/1A

100/1A

0.44
0.15

0.44
0.15

N2XY-O 3x(3x1x240)/2x240
143 m
12BFE-LVM
Pn = 240 kW
In = 434.1 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

29.69
9.90

29.69
9.90

12BFT02

10BMB-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

0.00
0.00

10BFT02
6.3 2x2.5%/0.42 kV
1600 kVA
uk = 6 %
ur = 0.89 %
In = 147/2199 A
Dyn1
R0/R1 = 1
X0/X1 = 0.95

LXC0741 3x1586/1x2934
4m

10BFJ

0.45
0.15

0.44
0.15

05

00LCB12
AP001

300/1A

100/1A

100/1A

0.45
0.15

0.45
0.15

00LAC13
Pn = 2074 kW
In = 227.0 A
Un = 6 kV
cosphin = 0.91
Ia/In = 6
p=1
R/X = 0.1
etan = 96.6 %

12MBU25
Pn = 450 kW
In = 50.2 A
Un = 6 kV
cosphin = 0.9
Ia/In = 6
p=1
R/X = 0.15
etan = 95.8 %

10BMB

100/1A

100/1A

10BBF00GS001

0.00
0.00

10

0.00
0.00

1000/1A

12BBF00GS001

08

06

0.00
0.00

200/1A

300/1A

11BFT02

11BFH-LVM
Pn = 640 kW
In = 1157.6 A
cosphin = 0.84
Ia/In = 6
R/X = 0.42
etan = 95 %

N2XSY 2x(3x1x240)
974 m

2000/1A

0.45
0.15

200/1A

Spare

LXC0741 3x1586/1x2934
4m

06

0.00
0.00

300/1A

11BFG

0.45
0.15

Space

100/1A

0.45
0.15

02

50/1A

Spare

0.44
0.15

03

0.00
0.00

Space

N2XSY 3x1x120
178 m
0.44
0.15

07

12BAA

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

11BBT01

12BBT01GT210

11BFT01

12BFH

12.51
4.17

0.45
0.15

13000/1A

100/1A

N2XSY 3x1x120
34 m

N2XSY 3x1x120
38 m

N2XSY 3x1x120
43 m

N2XSY 3x1x120
125 m

0.45
0.15

Spare

100/1A

100/1A

LXC0741 3x1586/1x2934
4m

0.00
0.00

0.45
0.15

100/1A

100/1A

LXC0741 3x1586/1x2934
4m

0.45
0.15

N2XSY 3x1x120
144 m

N2XSY 3x1x240
94 m

N2XSY 2x(3x1x240)
94 m
0.45
0.15

100/1A

100/1A

LXC0741 3x1586/1x2934
4m

100/1A

10BBE 01

11BBF00
GS002

Space
100/1A

0.44
0.15

05

100/1A

50/1A

200/1A

200/1A

08

LXC0741 3x1586/1x2934
4m

11MBJ01
GT001

09

0.00
0.00

02

11BBT01

N2XSY 3x1x120
151 m

10

11BBF 01

0.44
0.15

0.45
0.15

N2XSY 3x1x120
33 m

0.00
0.00

0.45
0.15

0.00
0.00

10BBE00GS001

0.00
0.00

LXC0741 3x1586/1x2934
4m

11

02

0.45
0.15

1000/1A

11BBF00GS001

0.00
0.00

LXC0741 3x1586/1x2934
4m

3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

0.45
0.15

12BBT01
GT230

1000/1A

LXC0741 3x1586/1x2934
4m

11BBE 01

11BBT01GT220

0.00
0.00

N2XSY 3x1x120
38 m

2000/1A

0.45
0.15

N2XSY 2x(3x1x240)
150 m

2000/1A

2000/1A

N2XSY 3x1x120
20 m

2000/1A

2000/1A

0.45
0.15

8
30 s

LXC0741 3x1586/1x2934
4m

2000/1A

2000/1A

12BBT01GT240

11BBF

N2XSY 2x(3x1x240)
984 m

2000/1A

750/1A

0.00
0.00

2000/1A

12BBT01

N2XSY 3x(3x1x240)
161 m

12BBE

11BBT01GT210

0.45
0.15

12BBT01
N2XSY 3x(3x1x240)
98 m

12BBF

4
N2XSY 3x(3x1x240)
161 m

11BAA

N2XSY 3x(3x1x240)
92 m

N2XSY 3x(3x1x240)
98 m

N2XSY 3x(3x1x240)
92 m

0.45
0.15

750/1A

N2XSY 3x1x120
20 m

8
30 s

N2XSY 3x1x120
122 m

8
30 s

LXC0741 3x1586/1x2934
4m

2000/1A

750/1A

N2XSY 3x1x120
173 m

750/1A

0.00
0.00

N2XSY 3x1x120
200 m

2000/1A

0.00
0.00

N2XSY 3x1x120
15 m

8
30 s

0.00
0.00

12BBT01
Dyn11yn11
16.5 9x1.25%/6.6/6.6 kV
32/16/16 MVA
uk = 8.66/8.71/15.15 %
ur = 0.48/0.48/0.96 %
In = 1120/1400/1400 A

1200/1A

1300/1A

0.00
0.00

N2XSY 3x1x240
150 m

1200/1A

1300/1A

: Zero-sequence short-circuit current (r.m.s)


in kA

1200/1A

N2XSY 3x(3x1x240)
92 m

11BBT01
Dyn11yn11
16.5 9x1.25%/6.6/6.6 kV
32/16/16 MVA
uk = 8.61/8.64/15.13 %
ur = 0.48/0.48/0.96 %
In = 1120/1400/1400 A

I0

I k L1" [kA]
I0
[kA]

1200/1A

N2XSY 3x(3x1x240)
152 m

1200/1A

1200/1A

N2XSY 3x(3x1x240)
92 m

1200/1A

N2XSY 3x(3x1x240)
161 m

1200/1A

12BAT01
240 4x2.5%/16.5 kV
300 MVA
uk = 16.22 %
ur = 0.16 %
In = 722/10497 A
YNd1
Z0/Z1 = 1

N2XSY 3x(3x1x240)
152 m

11BAT01
240 4x2.5%/16.5 kV
300 MVA
uk = 16.26 %
ur = 0.16 %
In = 722/10497 A
YNd1
Z0/Z1 = 1

I k L1" : Initial symmetrical short-circuit current over


phase L1 (r.m.s.) in kA

Abtlg.
Dept.

SINUS

GmbH

SIEMENS
Power Generation (PG)

UA / DCC
Type

Benennung / Title

Inhaltskennzeichen
Contents Code

CALCULATION OF
SHORT-CIRCUIT CURRENTS,
LOAD FLOW AND VOLTAGE DROP
Annex 7
Dienstst. / Dept.

BN02

B
Zhl.-Nr.
Reg. No.

UNID

W 741

Index / Rev. Version

10691410
Ang.-Var. / Offer -Var.

EGY263-BN02-B-700021
Erstellt mit
Designed with

EGY263

Mastab
Scale

B
Var. / Opt.

Blatt-Nr. / Page-No.

1
Ersatz fr
Supersedes

Document No.:

PG W 741

Project:

SINUS GmbH
CALCULATION OF SHORT-CIRCUIT CURRENTS AND VOLTAGE DROP

EGY263-BN02-B-700021
NEW TALKHA 750 MW CCPP

Date:

B / 2005-10-21

Page:

1 of 1

Annex 8: Calculation of Short-Circuit Impedances for Minimum Short-Circuit Currents (0.4 kV)

Un
R1
X1
Z1
R0
X0
Z0
R0/R1
X0/X1
Z0/Z1
Ik''

Switchgear
10BFJ
10BFK
10BJJ
10BMA
10BMB
11BFE
11BFG
11BFH
11BJH
11BME
12BFE
12BFG
12BFH
12BJH
12BME

Rated voltage of switchgear in kV


Positive sequence resistance in
Positive sequence reactance in
Positive sequence impedance in
Zero sequence resistance in
Zero sequence reactance in
Zero sequence impedance in
Ratio zero sequence resistance to positive sequence resistance
Ratio zero sequence reactance to positive sequence reactance
Ratio zero sequence impedance to positive sequence impedance
Short-circuit current over phase L1 in kA

Un

R1

X1

Z1

R0

X0

Z0

[kV]

[]

[]

[]

[]

[]

[]

0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4

0.0015
0.0015
0.0023
0.0047
0.0047
0.0057
0.0012
0.0012
0.0023
0.0124
0.0085
0.0012
0.0012
0.0024
0.0151

0.0081
0.0081
0.0085
0.0200
0.0200
0.0104
0.0079
0.0079
0.0085
0.0244
0.0120
0.0079
0.0079
0.0085
0.0259

0.0082
0.0082
0.0088
0.0206
0.0206
0.0119
0.0080
0.0080
0.0088
0.0273
0.0147
0.0080
0.0080
0.0088
0.0300

0.0013
0.0013
0.0055
0.0158
0.0158
0.0263
0.0013
0.0013
0.0093
0.0697
0.0415
0.0013
0.0013
0.0093
0.0889

0.0065
0.0065
0.0080
0.0228
0.0228
0.0158
0.0065
0.0065
0.0088
0.0387
0.0215
0.0065
0.0065
0.0088
0.0444

0.0066
0.0066
0.0097
0.0278
0.0278
0.0307
0.0066
0.0066
0.0128
0.0797
0.0467
0.0066
0.0066
0.0128
0.0994

R0/R1

X0/X1

Z0/Z1

Ik"
[kA]

0.8289
0.8289
2.4057
3.3678
3.3678
4.5975
1.0493
1.0463
3.9565
5.6231
4.8961
1.0361
1.0361
3.9309
5.8726

0.7989
0.7989
0.9437
1.1396
1.1396
1.5188
0.8210
0.8214
1.0367
1.5909
1.7955
0.8203
0.8203
1.0359
1.7152

0.7999
0.7999
1.1031
1.3504
1.3504
2.5822
0.8269
0.8272
1.4482
2.9183
3.1852
0.8260
0.8260
1.4465
3.3128

28.55
28.55
24.36
9.99
9.99
12.51
29.24
29.25
22.40
5.17
8.89
29.22
29.22
22.38
4.34
Editor: H. Specht
Ord. No.: si0368

During Starting

Before Starting

Sk''Act = 1332 MVA


c=1
R/X = 0.05

Sk''Act = 1332 MVA


c=1
R/X = 0.05

U = 15.67 kV
U/Un = 95.0 %
phi = -1.2

16.5 kV

P = 25.9 MW
Q = 17.6 MVAr
I = 1155 A

U = 15.47 kV
U/Un = 93.8 %
phi = -1.3

P = -25.9 MW
Q = -17.6 MVAr
I = 1155 A

16.5 kV

P = 28.8 MW
Q = 32.2 MVAr
I = 1613 A
P = -28.8 MW
Q = -32.2 MVAr
I = 1613 A

12BBT01
Dyn11yn11
16.5 9x1.25%/6.6/6.6 kV
32/16/16 MVA
uk = 8.66/8.71/15.15 %
ur = 0.48/0.48/0.96 %
In = 1120/1400/1400 A
Tap pos. -5

U = 6.30 kV
U/Un = 100.0 %
phi = -6.1

P = 11.9 MW
Q = 6.7 MVAr
I = 1241 A

P = 13.9 MW
Q = 7.9 MVAr
I = 1466 A

P = -7.0 MW
Q = -3.9 MVAr
I = 728 A

P = -4.9 MW
Q = -2.8 MVAr
I = 514 A

P = -13.9 MW
Q = -7.9 MVAr
I = 1466 A

12BBT01
Dyn11yn11
16.5 9x1.25%/6.6/6.6 kV
32/16/16 MVA
uk = 8.66/8.71/15.15 %
ur = 0.48/0.48/0.96 %
In = 1120/1400/1400 A
Tap pos. -5

U = 6.35 kV
U/Un = 100.8 %
phi = -5.5

U = 6.14 kV
U/Un = 97.4 %
phi = -6.6

P = 14.6 MW
Q = 18.1 MVAr
I = 2341 A

P = 13.9 MW
Q = 7.9 MVAr
I = 1506 A
P = -13.9 MW
Q = -7.9 MVAr
I = 1506 A

Calculated Case 1:
P = -7.7 MW
Q = -14.2 MVAr
I = 1619 A

P = -7.0 MW
Q = -3.9 MVAr
I = 804 A

U = 5.74 kV
U/Un = 91.1 %
phi = -6.9

Voltage Drop Calculation for Motor Start-up of


00LAC11 - HP FD WTR PUMP A (6.3 kV)
Operation Mode Configuration:

M
3~

Pre-load 12BBF
S = 8000 kVA
cosphi = 0.87
etan = 96 %

N2XSY 3x(3x1x240)
161 m

Pre-load 12BBE + 11BFF


S = 16000 kVA
cosphi = 0.87
etan = 96 %

M
3~

M
3~

Pre-load 12BBE + 11BFF


S = 16000 kVA
cosphi = 0.87
etan = 96 %

Pre-load 12BBF
S = 8000 kVA
cosphi = 0.87
etan = 96 %

N2XSY 3x(3x1x240)
161 m

M
3~

Motor Start-up 00LAC11 via transformer 12BBT01


(Voltage at 16.5 kV is 95% of Un with pre-load, tap position -5 ).
Transformer 12BBT01 is full loaded after motor start up (worst case).
Legend:

02

: Voltage in kV

Q [MVAr]

U/U n

: Voltage/ Rated Voltage in %

phi

: Voltage Angle in

P [MW]

: Active Power in MW

Q [MVAr]

: Reactive Power in MVAr

: Current in A

[A]

12BBT01GT240

12BBT01GT240

P = -4.9 MW
Q = -2.8 MVAr
I = 514 A

I [A]

U/U n [%]
phi []

Busbar
Node

U = 6.34 kV
11BBE
U/Un = 100.6 %
phi = -5.5
3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

[kV]

P [MW]

P = 4.9 MW
Q = 2.8 MVAr
I = 514 A

11BBE
U = 5.71 kV
U/Un = 90.7 %
phi = -6.7
3 ~ 6.3 kV 2500 A 50 Hz 31.5 kA 1 s

03

02
P = -4.9 MW
Q = -2.8 MVAr
I = 570 A

P = 7.6 MW
Q = 14.1 MVAr
I = 1619 A

03

THE ARAB REPUBLIC OF EGYPT

P = -2.7 MW
Q = -11.3 MVAr
I = 1177 A

MINISTRY OF ELECTRICITY AND ENERGY

00LAC11AP001

00LAC11AP001

3~

3~

EAST DELTA ELECTRICITY PRODUCTION COMPANY


NEW TALKA POWER STATION 750MW COMBINED CYCLE PROJECT

Prel-load 11BBE
S = 5641 kVA
cosphi = 0.87
etan = 96 %

Prel-load 11BBE
S = 5641 kVA
cosphi = 0.87
etan = 96 %

JOB NO:

DRAWING NO.

REV.

POWER GENERATION ENGINEERING AND


SERVICES COMPANY

U = 5.71 kV
U/Un = 90.7 %
phi = -6.7

P = 2.7 MW
Q = 11.3 MVAr
I = 1177 A

Ursprung / Original

P = -2.7 MW
Q = -11.3 MVAr
I = 1177 A

Projekt / Project

HP FD WTR
Pn = 2074 kW
In = 227.0 A
Un = 6 kV
cosphin = 0.91
Ia/In = 6
p=1
R/X = 0.1
cosphi = 0.23
etan = 96.6 %

PKZ / PC

Name

Datum
Date

3~

HP FD WTR
Pn = 2074 kW
In = 227.0 A
Un = 6 kV
cosphin = 0.91
Ia/In = 6
p=1
R/X = 0.1
cosphi = 0.23
etan = 96.6 %

Urspr.-PKZ-Nr.
Orig.-PC

NEW TALKHA 750MW CCPP

M
3~

Ursprung-Nr. / Original-No.

gezeich.
Drawn
bearb.
Coord.
geprft
Checked

Abtlg.
Dept.

2005-10-21

J.-H. Yang

2005-10-21

K. Specht

2005-10-21

H. Specht

SINUS

GmbH

SIEMENS
Power Generation (PG)

Mastab
Scale

UA / DCC
Type

Benennung / Title

Inhaltskennzeichen
Contents Code

CALCULATION OF
SHORT-CIRCUIT CURRENTS,
LOAD FLOW AND VOLTAGE DROP
Annex 9
Dienstst. / Dept.

BN02

B
Zhl.-Nr.
Reg. No.

UNID

W 741

Index / Rev. Version

10691410
Ang.-Var. / Offer -Var.

EGY263-BN02-B-700021
Erstellt mit
Designed with

EGY263

B
Var. / Opt.

Blatt-Nr. / Page-No.

1
Ersatz fr
Supersedes

Document No.: EGY263-BN02-B-700021


Project: New Talkha 750MW CCPP
Status/Date: B / 2005-10-21

SIEMENS PG W741
SINUS GmbH

Case 1: Check of Rating of Generator Transformer (BAT)


Input Data
Generator Transformer (BAT)

Generator (MKA)
Sr T

[MVA]

300

Rated apparent power

Sr Gen

Rated voltage of HV winding

UrHV T

[kV]

240

Rated power factor

PFr Gen

Rated voltage of LV winding

UrLV T

Rated power

MVA

[kV]

16.5

Rated Voltage

Ur Gen

[kV]

Maximum tapping range

[%]

10.0

Operating Voltage

Uop Gen

[kV]

Minimum tapping range

[%]

-10.0

Power factor (lead)

PFlead Gen

Number of taps

+4/-4

Reactive power limit (operating with PF lead Gen)

Qlead Gen

[MVAr]

Vector group

YNd1
Apparent power (P.F.Gen/lag)

Slag Aux

MVA

Power factor (P.F.Gen/lag)

PFlag Aux

Short-circuit impedance

uk T

[%]

16.2

Short-circuit resistance

ur T

[%]

0.16

313
0.85
16.5
16.5
0.92
-105

Load Demand of Auxiliary System

Apparent power (P.F.Gen/lead)

Slead Aux

Power factor (P.F.Gen/lead)

PFlead Aux

0
0.85

MVA

0
0.85

Results
Current Carrying Capacity of Windings of Transformer
Ambient air temperature

Tamb air

10

15

20

25

30

35

40

Maximum apparent power

Smax T

MVA

346

338.3

330.7

323

315.5

308

300

290.8

282

1)

Imax LV T

12107

11837

11571

11302

11040

10777

10497

10175

9867

2)

Maximum current LV winding


Tap
Position

Tapping
factor

1.100

757

740

723

706

690

674

656

636

617

1.075

774

757

740

723

706

689

671

651

631

1.050

793

775

758

740

723

706

687

666

646

1.025

812

794

776

758

740

723

704

682

662

5 (0)

1.000

832

814

796

777

759

741

722

700

678

0.975

854

835

816

797

778

760

740

717

696

0.950

876

857

837

818

799

780

760

736

714

0.925

900

880

860

840

821

801

780

756

733

0.900

925

904

884

863

843

823

802

777

754

Maximum current HV winding

Imax HV T

3)

Gas Turbine
Ambient air temperature

Tamb air

10

15

20

25

30

35

40

Maximum active power output

Pmax GT

MW

280.2

274.8

269.4

264.0

256.2

248.3

238.9

228.4

217.9

4)

Generator
Ambient air temperature

Tamb air

10

15

20

25

30

35

40

Maximum apparent power output

Smax Gen

MVA

334.0

331.0

328.0

325.0

322.0

319.0

316.0

313.0

310.0

Maximum active power output (for operating with PF r Gen)

Pmax Gen

MW

283.9

281.4

278.8

276.3

273.7

271.2

268.6

266.1

263.5

4)

Loading of LV Winding of Transformer for Overexcited Operation of Generator (PF=0.85/lag)


Active power output generator

Plag GT/Gen

MW

280.2

274.8

269.4

264.0

256.2

248.3

238.9

228.4

217.9

Reactive power output generator

Qlag GT/Gen

MVAr

173.7

170.3

167.0

163.6

158.8

153.9

148.1

141.5

135.0

Apparent power output generator

Slag GT/Gen

MVA

329.7

323.3

316.9

310.6

301.4

292.2

281.1

268.7

256.3
217.9

Active power at LV winding of transformer (including P lag Aux)

Plag LV T

MW

280.2

274.8

269.4

264.0

256.2

248.3

238.9

228.4

Reactive power at LV winding of transformer (including Q lag Aux)

Qlag LV T

MVAr

173.7

170.3

167.0

163.6

158.8

153.9

148.1

141.5

135.0

Apparent power at LV winding of transformer (including S lag Aux)

Slag LV T

MVA

329.7

323.3

316.9

310.6

301.4

292.2

281.1

268.7

256.3
217.5

Active power at HV winding of transformer (incl. transformer losses)

Plag HV T

MW

279.6

274.2

268.9

263.5

255.7

247.9

238.5

228.0

Reactive power at HV winding of transformer (incl. transformer losses)

Qlag HV T

MVAr

114.8

113.7

112.6

111.4

109.6

107.7

105.3

102.5

99.5

Apparent power at HV winding of transformer (incl. transformer losses)

Slag HV T

MVA

302.3

296.9

291.5

286.1

278.2

270.3

260.7

250.0

239.2

Required MVA rating acc. IEEE C57.116-1989 (equation 1, see remarks)

MVAT1

MVA

329.7

323.3

316.9

310.6

301.4

292.2

281.1

268.7

256.3

Required MVA rating acc. IEEE C57.116-1989 (equation 2, see remarks)

MVAT2

MVA

307.8

301.9

295.9

290.0

281.4

272.8

262.4

250.9

239.3

Maximum apparent power transformer

Smax T

MVA

346.0

338.3

330.7

323.0

315.5

308.0

300.0

290.8

282.0

YES

YES

YES

YES

YES

YES

YES

YES

YES

217.9

Maximum apparent power transformer S maxT greater than MVAT1 and MVAT2

5)

6)

Loading of LV Winding of Transformer for Underexcited Operation of Generator (PF=0.92/lead)


Active power output generator

Plead GT/Gen

MW

246.5

246.5

246.5

246.5

246.5

246.5

238.9

228.4

Reactive power output generator

Qlead GT/Gen

MVAr

-105.0

-105.0

-105.0

-105.0

-105.0

-105.0

-101.8

-97.3

-92.8

Apparent power output generator

Slead GT/Gen

MVA

267.9

267.9

267.9

267.9

267.9

267.9

259.7

248.2

236.8
217.9

Active power at LV winding of transformer (including P lead Aux)

Plead LV T

MW

246.5

246.5

246.5

246.5

246.5

246.5

238.9

228.4

Reactive power at LV winding of transformer (including Q lead Aux)

Qlead LV T

MVAr

-105.0

-105.0

-105.0

-105.0

-105.0

-105.0

-101.8

-97.3

-92.8

Apparent power at LV winding of transformer (including S lead Aux)

Slead LV T

MVA

267.9

267.9

267.9

267.9

267.9

267.9

259.7

248.2

236.8

Active power at HV winding of transformer (incl. transformer losses)

Plead HV T

MW

246.1

246.1

246.1

246.1

246.1

246.1

238.5

228.1

217.6

Reactive power at HV winding of transformer (incl. transformer losses)

Qlead HV T

MVAr

-143.9

-143.9

-143.9

-143.9

-143.9

-143.9

-138.3

-130.6

-123.2

Apparent power at HV winding of transformer (incl. transformer losses)

Slead HV T

MVA

285.1

285.1

285.1

285.1

285.1

285.1

275.7

262.8

250.0

Required MVA rating acc. IEEE C57.116-1989 (equation 1, see remarks)

MVAT1

MVA

267.9

267.9

267.9

267.9

267.9

267.9

259.7

248.2

236.8

Required MVA rating acc. IEEE C57.116-1989 (equation 2, see remarks)

MVAT2

MVA

291.7

291.7

291.7

291.7

291.7

291.7

282.7

270.2

257.8

Maximum apparent power transformer

Smax T

MVA

346.0

338.3

330.7

323.0

315.5

308.0

300.0

290.8

282.0

YES

YES

YES

YES

YES

YES

YES

YES

YES

Maximum apparent power transformer S maxT greater than MVAT1 and MVAT2

7)

8)

Current Carrying Capacity of Transformer and Maximum Operating Currents (Lag/Lead)


Max. current carrying capacity of LV winding of transformer

Imax LV T

12107

11837

11571

11302

11040

10777

10497

10175

9867

Operating current at LV winding of transformer (lag)

Ilag LV T

11535

11313

11090

10868

10545

10223

9834

9402

8969

Operating current at LV winding of transformer (lead)

Ilead LV T

9375

9375

9375

9375

9375

9375

9086

8686

8286

Max. current carrying capacity of HV winding of transformer (middle tap pos.)

Imax HV T

832

814

796

777

759

741

722

700

678

Operating current at HV winding of transformer (lag, middle tap pos.)

Ilag HV T

793

778

762

747

725

703

676

646

617

Operating current at HV winding of transformer (lead, middle tap pos.)

Ilead HV T

644

644

644

644

644

644

625

597

570

YES

YES

YES

YES

YES

YES

YES

YES

YES

Oper. current smaller than current carrying capacity of trans.

9)

10)

Remarks:
1) If the operating current at LV winding of transformer is smaller than the current carrying capacity of this winding, the current carrying capacity of the
HV winding will not be exceeded (independent of the actual tap position for full-power tappings).
2) Equations for conservative MVA rating according IEEE C57.116-1989

MVAT 1 =

MW G2 + MVARG2

(1)

MVA T 2 =

MVAT 2 =
Annex 10

MW G2 + MVAR

0 . 925 X T (MVA T 2 )

lag P.F. (2)

MW + [MVARG + 1.075 X T (MVAT 2 )]

2
G

Page 1 of 3

lead P.F.

Editor: H. Specht
Order No.: si0368

Document No.: EGY263-BN02-B-700021


Project: New Talkha 750MW CCPP
Status/Date: B / 2005-10-21

SIEMENS PG W741
SINUS GmbH

Case 2: Check of Rating of Generator Transformer (BAT)


Input Data
Generator Transformer (BAT)

Generator (MKA)
Sr T

[MVA]

300

Rated apparent power

Sr Gen

Rated voltage of HV winding

UrHV T

[kV]

240

Rated power factor

PFr Gen

Rated voltage of LV winding

UrLV T

Rated power

MVA

[kV]

16.5

Rated Voltage

Ur Gen

[kV]

Maximum tapping range

[%]

10.0

Operating Voltage

Uop Gen

[kV]

Minimum tapping range

[%]

-10.0

Power factor (lead)

PFlead Gen

Number of taps

+4/-4

Reactive power limit (operating with PF lead Gen)

Qlead Gen

[MVAr]

Vector group

YNd1
Apparent power (P.F.Gen/lag)

Slag Aux

MVA

Power factor (P.F.Gen/lag)

PFlag Aux

Short-circuit impedance

uk T

[%]

16.2

Short-circuit resistance

ur T

[%]

0.16

313
0.85
16.5
16.5
0.93
-103

Load Demand of Auxiliary System

Apparent power (P.F.Gen/lead)

Slead Aux

Power factor (P.F.Gen/lead)

PFlead Aux

0
0.85

MVA

0
0.85

Results
Current Carrying Capacity of Windings of Transformer
Ambient air temperature

Tamb air

10

15

20

25

30

35

40

Maximum apparent power

Smax T

MVA

346

338.3

330.7

323

315.5

308

300

290.8

282

1)

Imax LV T

12107

11837

11571

11302

11040

10777

10497

10175

9867

2)

Maximum current LV winding


Tap
Position

Tapping
factor

1.100

757

740

723

706

690

674

656

636

617

1.075

774

757

740

723

706

689

671

651

631

1.050

793

775

758

740

723

706

687

666

646

1.025

812

794

776

758

740

723

704

682

662

5 (0)

1.000

832

814

796

777

759

741

722

700

678

0.975

854

835

816

797

778

760

740

717

696

0.950

876

857

837

818

799

780

760

736

714

0.925

900

880

860

840

821

801

780

756

733

0.900

925

904

884

863

843

823

802

777

754

Maximum current HV winding

Imax HV T

3)

Gas Turbine
Ambient air temperature

Tamb air

10

15

20

25

30

35

40

Maximum active power output

Pmax GT

MW

280.2

274.8

269.4

264.0

256.2

248.3

238.9

228.4

217.9

4)

Generator
Ambient air temperature

Tamb air

10

15

20

25

30

35

40

Maximum apparent power output

Smax Gen

MVA

334.0

331.0

328.0

325.0

322.0

319.0

316.0

313.0

310.0

Maximum active power output (for operating with PF r Gen)

Pmax Gen

MW

283.9

281.4

278.8

276.3

273.7

271.2

268.6

266.1

263.5

4)

Loading of LV Winding of Transformer for Overexcited Operation of Generator (PF=0.85/lag)


Active power output generator

Plag GT/Gen

MW

280.2

274.8

269.4

264.0

256.2

248.3

238.9

228.4

217.9

Reactive power output generator

Qlag GT/Gen

MVAr

173.7

170.3

167.0

163.6

158.8

153.9

148.1

141.5

135.0

Apparent power output generator

Slag GT/Gen

MVA

329.7

323.3

316.9

310.6

301.4

292.2

281.1

268.7

256.3
217.9

Active power at LV winding of transformer (including P lag Aux)

Plag LV T

MW

280.2

274.8

269.4

264.0

256.2

248.3

238.9

228.4

Reactive power at LV winding of transformer (including Q lag Aux)

Qlag LV T

MVAr

173.7

170.3

167.0

163.6

158.8

153.9

148.1

141.5

135.0

Apparent power at LV winding of transformer (including S lag Aux)

Slag LV T

MVA

329.7

323.3

316.9

310.6

301.4

292.2

281.1

268.7

256.3
217.5

Active power at HV winding of transformer (incl. transformer losses)

Plag HV T

MW

279.6

274.2

268.9

263.5

255.7

247.9

238.5

228.0

Reactive power at HV winding of transformer (incl. transformer losses)

Qlag HV T

MVAr

114.8

113.7

112.6

111.4

109.6

107.7

105.3

102.5

99.5

Apparent power at HV winding of transformer (incl. transformer losses)

Slag HV T

MVA

302.3

296.9

291.5

286.1

278.2

270.3

260.7

250.0

239.2

Required MVA rating acc. IEEE C57.116-1989 (equation 1, see remarks)

MVAT1

MVA

329.7

323.3

316.9

310.6

301.4

292.2

281.1

268.7

256.3

Required MVA rating acc. IEEE C57.116-1989 (equation 2, see remarks)

MVAT2

MVA

307.8

301.9

295.9

290.0

281.4

272.8

262.4

250.9

239.3

Maximum apparent power transformer

Smax T

MVA

346.0

338.3

330.7

323.0

315.5

308.0

300.0

290.8

282.0

YES

YES

YES

YES

YES

YES

YES

YES

YES

217.9

Maximum apparent power transformer S maxT greater than MVAT1 and MVAT2

5)

6)

Loading of LV Winding of Transformer for Underexcited Operation of Generator (PF=0.93/lead)


Active power output generator

Plead GT/Gen

MW

260.6

260.6

260.6

260.6

256.2

248.3

238.9

228.4

Reactive power output generator

Qlead GT/Gen

MVAr

-103.0

-103.0

-103.0

-103.0

-101.2

-98.1

-94.4

-90.3

-86.1

Apparent power output generator

Slead GT/Gen

MVA

280.2

280.2

280.2

280.2

275.4

267.0

256.9

245.6

234.3
217.9

Active power at LV winding of transformer (including P lead Aux)

Plead LV T

MW

260.6

260.6

260.6

260.6

256.2

248.3

238.9

228.4

Reactive power at LV winding of transformer (including Q lead Aux)

Qlead LV T

MVAr

-103.0

-103.0

-103.0

-103.0

-101.2

-98.1

-94.4

-90.3

-86.1

Apparent power at LV winding of transformer (including S lead Aux)

Slead LV T

MVA

280.2

280.2

280.2

280.2

275.4

267.0

256.9

245.6

234.3

Active power at HV winding of transformer (incl. transformer losses)

Plead HV T

MW

260.2

260.2

260.2

260.2

255.8

248.0

238.5

228.1

217.6

Reactive power at HV winding of transformer (incl. transformer losses)

Qlead HV T

MVAr

-145.5

-145.5

-145.5

-145.5

-142.3

-136.7

-130.1

-122.9

-115.8

Apparent power at HV winding of transformer (incl. transformer losses)

Slead HV T

MVA

298.1

298.1

298.1

298.1

292.7

283.2

271.7

259.1

246.5

Required MVA rating acc. IEEE C57.116-1989 (equation 1, see remarks)

MVAT1

MVA

280.2

280.2

280.2

280.2

275.4

267.0

256.9

245.6

234.3

Required MVA rating acc. IEEE C57.116-1989 (equation 2, see remarks)

MVAT2

MVA

303.7

303.7

303.7

303.7

298.6

289.4

278.4

266.2

253.9

Maximum apparent power transformer

Smax T

MVA

346.0

338.3

330.7

323.0

315.5

308.0

300.0

290.8

282.0

YES

YES

YES

YES

YES

YES

YES

YES

YES

Maximum apparent power transformer S maxT greater than MVAT1 and MVAT2

7)

8)

Current Carrying Capacity of Transformer and Maximum Operating Currents (Lag/Lead)


Max. current carrying capacity of LV winding of transformer

Imax LV T

12107

11837

11571

11302

11040

10777

10497

10175

9867

Operating current at LV winding of transformer (lag)

Ilag LV T

11535

11313

11090

10868

10545

10223

9834

9402

8969

Operating current at LV winding of transformer (lead)

Ilead LV T

9805

9805

9805

9805

9638

9343

8988

8593

8197

Max. current carrying capacity of HV winding of transformer (middle tap pos.)

Imax HV T

832

814

796

777

759

741

722

700

678

Operating current at HV winding of transformer (lag, middle tap pos.)

Ilag HV T

793

778

762

747

725

703

676

646

617

Operating current at HV winding of transformer (lead, middle tap pos.)

Ilead HV T

674

674

674

674

663

642

618

591

564

YES

YES

YES

YES

YES

YES

YES

YES

YES

Oper. current smaller than current carrying capacity of trans.

9)

10)

Remarks:
1) If the operating current at LV winding of transformer is smaller than the current carrying capacity of this winding, the current carrying capacity of the
HV winding will not be exceeded (independent of the actual tap position for full-power tappings).
2) Equations for conservative MVA rating according IEEE C57.116-1989

MVAT 1 =

MW G2 + MVARG2

(1)

MVA T 2 =

MVAT 2 =
Annex 10

MW G2 + MVAR

0 . 925 X T (MVA T 2 )

lag P.F. (2)

MW + [MVARG + 1.075 X T (MVAT 2 )]

2
G

Page 2 of 3

lead P.F.

Editor: H. Specht
Order No.: si0368

Overexcited Operation of Generator


(PF = 0.85 / lag)

Underexcited Operation of Generator


(PF = 0.93 / lead)

2a

Interconnected System
Sk''Act = 12956 MVA
c=1
R/X = 0.1436

Interconnected System
Sk''Act = 12956 MVA
c=1
R/X = 0.1436

P = -265.5 MW
Q = -111.8 MVAr
S = 288 MVA
I = 753 A

U = 220.88 kV
U/Un = 100.4 %
phi = 0.0

P = 265.5 MW
Q = 111.8 MVAr
S = 288 MVA
I = 753 A

Underexcited Operation of Generator


(PF = 0.92 / lead)

2b

ADA

P = -290.6 MW
Q = 168.2 MVAr
S = 336 MVA
I = 753 A

U = 257.40 kV
U/Un = 117.0 %
phi = 0.0

3 ~ 220 kV 50 Hz

P = 290.6 MW
Q = -168.2 MVAr
S = 336 MVA
I = 753 A

Interconnected System
Sk''Act = 12956 MVA
c=1
R/X = 0.1436

ADA

P = -287.4 MW
Q = 175.8 MVAr
S = 337 MVA
I = 753 A

U = 258.28 kV
U/Un = 117.4 %
phi = 0.0

3 ~ 220 kV 50 Hz

P = 287.4 MW
Q = -175.8 MVAr
S = 337 MVA
I = 753 A

ADA
3 ~ 220 kV 50 Hz

CHECK OF TRANSFORMER RATING FOR


GENERATOR TRANSFORMER
I/Inp = 95.6 %
I/Ins = 104.3 %
11BAT01
240 4x2.5%/16.5 kV
300 MVA
uk = 16.26 %
ur = 0.16 %
In = 722/10497 A
YNd1
Tap pos. 0

I/Inp = 95.7 %
I/Ins = 104.3 %
10BAT01
240 4x2.5%/16.5 kV
300 MVA
uk = 16.26 %
ur = 0.16 %
In = 722/10497 A
YNd1
Tap pos. 0
P = -266.1 MW
Q = -164.9 MVAr
S = 313 MVA
I = 10953 A

U = 16.50 kV
U/Un = 100.0 %
phi = 9.0

P = 266.1 MW
Q = 164.9 MVAr
S = 313 MVA
I = 10953 A

I/Inp = 95.7 %
I/Ins = 104.4 %
10BAT01
240 4x2.5%/16.5 kV
300 MVA
uk = 16.26 %
ur = 0.16 %
In = 722/10497 A
YNd1
Tap pos. 0
P = -291.1 MW
Q = 115.0 MVAr
S = 313 MVA
I = 10953 A

U = 16.50 kV
U/Un = 100.0 %
phi = 8.5

P = 291.1 MW
Q = -115.1 MVAr
S = 313 MVA
I = 10953 A

P = 0.0 MW
Q = 0.0 MVAr
S = 0 MVA
I=0A

Legend:

U
P = -288.0 MW
Q = 122.7 MVAr
S = 313 MVA
I = 10955 A

U = 16.50 kV
U/Un = 100.0 %
phi = 8.4

P = 288.0 MW
Q = -122.7 MVAr
S = 313 MVA
I = 10955 A

P = 0.0 MW
Q = 0.0 MVAr
S = 0 MVA
I=0A

P [MW]

: Voltage in kV

Q [MVAr]

U/U n

: Voltage/ Rated Voltage in %

phi

: Voltage Angle in

: Active Power in MW

P [MW]

: Reactive Power in MVAr

Q [MVAr]

: Apparent Power in MVA

S
I

: Current in A

S
I

[kV]

U/U n
phi []

[MVA]
[A]

[%]

Busbar
Node

P = 0.0 MW
Q = 0.0 MVAr
S = 0 MVA
I=0A

[MVA]
[A]

THE ARAB REPUBLIC OF EGYPT


GT

GT

3~
11MKA
P = 266.1 MW
Q = 164.9 MVAr

AUXILIARY LOAD
P = 0 kW
Q = 0 kVAr

GT

3~
11MKA
P = 291.1 MW
Q = -115.1 MVAr

AUXILIARY LOAD
P = 0 kW
Q = 0 kVAr

MINISTRY OF ELECTRICITY AND ENERGY

G
3~
11MKA
P = 288.0 MW
Q = -122.7 MVAr

EAST DELTA ELECTRICITY PRODUCTION COMPANY


NEW TALKA POWER STATION 750MW COMBINED CYCLE PROJECT

AUXILIARY LOAD
P = 0 kW
Q = 0 kVAr

JOB NO:

DRAWING NO.

REV.

POWER GENERATION ENGINEERING AND


SERVICES COMPANY

Ursprung / Or iginal

Ursprung-Nr. / Original-No.

Urspr.-PKZ-Nr.
Or ig.-PC

Projekt / Project

PKZ / PC

NEW TALKHA 750MW CCPP


Name

Datum
Date
gezeich.
Drawn
bearb.
Coord.
geprft
Checked

Abtlg.
Dept.

2005-10-21

J.-H. Yang

2005-10-21

K. Specht

2005-10-21

H. Specht

SINUS

GmbH

SIEMENS
Power Generation (PG)

Mastab
Scale

UA / DCC
Type

Benennung / Title

Inhaltskennzeichen
Contents Code

CALCULATION OF
SHORT-CIRCUIT CURRENTS,
LOAD FLOW AND VOLTAGE DROP
Annex 10
Dienstst. / Dept.

BN02

B
Zhl.-Nr.
Reg. No.

UNID

W 741

10691410
Ang.-Var. / Offer -Var.

EGY263-BN02-B-700021
Erstellt mit
Designed with

EGY263

Var. / Opt.

Index / Rev.

Ver sion

Blatt-Nr. / Page-No.

3/3
Ersatz fr
Supersedes

You might also like