RTU511

Data Sheet
Base Module 511CIM01

Base Module 511CIM01

ing system. The controller acts as master for the


serial I/O-bus (local I/O-Interface and Wired-ORBus).
It is responsible for interface management, event
handling, the time base and for preservation of
relevant data. System relevant configuration files
are stored in the non-volatile flash memory in order to guarantee a valid system configuration after
power on reset. An optional battery buffered RTC
is used to keep an exact time during power off
state.

Multi I/O board


The I/O functionality consists of several sub functions.

Application

Analog Input

The 511CIM01 is a unit consisting of a communication unit (CMU), a multi-I/O board and a power
supply in a durable module housing, which could
be mounted on a standard DIN rail.

6 analog input channels could be used for current


or voltage measurements in various sensitivity
ranges:
unipolar

The essential tasks of the 511CIM01 are:

Capturing of 6 analog input signals


(mA or V measurement)

Capturing of 16 digital input signals

Output of 8 digital signals by relay

(1 out of n) check for commands

Managing and controlling of external I/O


modules via serial interface (Wired-ORBus)

Communicating with control centers and


local MMI systems via integrated serial
line and LAN interfaces

Managing the time base for the base


module and synchronizing the I/O boards

Handling of the dialog between RTU and


Web-Browser via LAN or USB interface

The 511CIM01 is available in following 4 versions:


R0001: 24 48 V DC process voltage
R0011: 24 48 V DC process voltage
with battery buffered RTC
R0002: 60 110 V DC process voltage
R0012: 60 110 V DC process voltage
with battery buffered RTC

bipolar

0 2.5 mA
0 5 mA
0 10 mA
0 20 mA
4 20 mA

2.5 mA
5 mA
10 mA
20 mA

0 1 V DC
0 10 V DC

1 V DC
10 V DC

Table 1: Measurement ranges

The differential inputs are protected against static


and dynamic over-voltages by a protection circuit.
A low-pass filter suppresses non line frequency
AC disturbance. Configuration is done by switches, shunt resistors and configuration data.

Binary Input
The board supplies 16 galvanic isolated digital input channels for binary values. Scanning and processing of the inputs is executed with the high
time resolution of 1 ms. Allocation of an input to a
processing function could be done according the
rules of configuration. Following types of signals
could be processed:
max. 16 single indications with time stamp
max. 8 double indications with time stamp
max. 2 digital measured values with 8 bit

Communication unit

max. 1 digital measured value with 16 bit

The communication unit is equipped with an


ARM9 - controller running with a real-time operat-

max. 8 pulse counters

Doc. No.: 1KGT 150 825 V001 1

RTU511
Data Sheet Base Module 511CIM01
Binary Output
The binary output part of the board provides 8
galvanic isolated digital outputs using relay contacts. Following types of signals could be configured:

Object commands with 1 or 2 pole output


without (1 out of n) check

Object commands with 1.5 or 2 pole with


(1 out of n) check

Regulation commands, 1 and 2 pole

Digital setpoints (8 bit)

Bitstring commands (1, 2 or 8 bit)

(1 out of n) check
The integrated interface could be used to check
the resistance of an external process relay, before
a command is executed. The interface performs a
(1 out of n) check to ensure that only one process
relay is switched at that time.

Relay Voltage UE
The relay voltage 24 V DC could be used to supply the binary output modules 23BO62/211BOD52
or the analog output modules 23AO60.

Power supply
The power supply unit operates in wide input
range from 24 to 110 V DC.
The power supply unit generates the internal supply voltages 24 V DC, 18 V DC, 15 V DC and 5
V DC and the galvanic isolated process voltage of
24 V DC. It is placed on top of the Multi I/O board.
In addition an I/O subrack with 4 I/O modules
(max. 16 I/O boards) could be fed via the WiredOR bus.

Characteristics
Communication unit
The Communication Unit provides the following
interfaces:

Communication Port 1 (CP1): Serial interface according RS485 with RJ45 connector

Communication Port 2 (CP2): Serial interface according RS232 with RJ45 connector

Ethernet Interface (E1): 10/100BaseT with


RJ45 connector

Communication Port 3 (CPM): Serial interface according RS232 with supply outputs 15 V DC and 5 V DC for Modem
applications

Alarm-Interface with two galvanic isolated


inputs and one galvanic isolated output

Serial I/O-Bus interface (WRB) for communication with the I/O-modules.

USB 2.0-Interface for accessing the web


server

The communication unit indicates operational and


error states by LEDs. The exact definition of the
LED has to be taken from the functional description of the firmware release.
LED

Color

Meaning

Err

red

Activated during bootmode and on Error

Run

green

Error free conditions

CP1 (RxD, TxD)

green

Activity (RxD, TxD)


of CP1 (RS485)

CP2 (RxD, TxD)

green

Activity (RxD, TxD)


of CP2 (RS232C)

E1 (SP, L/A)

green

Speed and Link/Activity of


Ethernet interface

CPM (RxD, TxD)

green

Activity (RxD, TxD)


of CPM (RS232C)

Table 2: Meaning of LEDs

Doc. No.: 1KGT 150 825 V001 1

RTU511
Data Sheet Base Module 511CIM01
Multi I/O board
Binary Input
Analog Input
Basic checks and cyclic processing functions are
done by the communication unit.
During initialization and operation the communication unit carries out a number of tests. A failure of
the board is detected by the communication unit
The 6 differential inputs are not potentially isolated
against the power supply. It is only permitted to
connect SELV circuits.
The board resolves unipolar or bipolar values into
2000 steps (11 bit plus sign) for 100% of the
measuring signal.
The differential inputs are protected against static
and dynamic over voltages up to 150 V DC by a
protection circuit.

16 inputs are available in 2 groups of 8 inputs with


common return. The inputs are potentially isolated
by means of opto-couplers. The board allows process signal voltages from 24 to 48 V DC or with a
second variant from 60 to 110 V DC.
16 LEDs to indicate the signal state are mounted
on the power supply unit. The LEDs follow directly
the inputs.
The maximum permissible frequency for counter
pulses is 25 Hz.
The binary input can execute the following processing functions for the different types of signals:

Digital filtering to suppress contact


bounce

Suppression of technologically caused


chattering signals

Intermediate position suppression and


monitoring for double indications

Consistency check for all binary input


channels allocated to digital measured
values

Summation of increment pulses to form


counter values in 31-bit counter value registers

Relocation of count values into other relocation registers upon request

Figure 1: Block diagram analog input

Measuring range and line frequency are easily to


configure with switch registers respectively jumpers. This information is needed to setup the A/D
converter.
Measurement ranges and line frequency will be
configured by configuration parameter. The line
frequency is used to set up the conversion time of
the A/D converter. This will result in the total scan
cycle time for all six channels according to Table 3
(5 ms Hold time included for the multiplexer).
Line
frequency
[Hz]

Conversion period
per channel
[ms]

Scan
cycle
[ms]

60

16.67

130

50

20.0

150

16.6

66.67

430

Table 3: Scan cycle times


Figure 2: Block diagram binary input

Doc. No.: 1KGT 150 825 V001 1

RTU511
Data Sheet Base Module 511CIM01

R00x2:
Due to thermal conditions in the range
110 126.5 V DC only 50% or less of
the input signals may have active signals at the same time.

Binary Output
Relay contacts are used for the binary outputs.
The 8 outputs are galvanic isolated against the
electronic by optical coupler. They are also fully
galvanic isolated against each other. All 8 outputs
have a separate return. If using relay as load in
the process circuit a free-wheeling diode shall be
used.
8 LEDs to indicate the output states are mounted
on the power supply unit.

(1 out of n) check
In order to increase the command output security,
the board is equipped with an integrated (1 out of
n) check circuit. This circuit checks the resistance
of the connected process coils, and compares the
value with a parameter value range.
Two transistor outputs are available to connect
two external relays (GO -, Measurement relay).

Power Supply Unit


The power supply unit has following characteristics and functions:
Cooling by natural convection
Electronic power limitation
Short-circuit protection
Over-voltage protection
2 fuses for main and process supply
LEDs for displaying the voltages and the
status of the binary I/Os
The input voltage is galvanic isolated against the
output voltages.

Figure 3: Block diagram binary output

Doc. No.: 1KGT 150 825 V001 1

RTU511
Data Sheet Base Module 511CIM01

Technical Data
In addition to the RTU500 series general technical data, the following applies:

Communication unit
Main Processing Unit 511CMM01
CPU

ARM9, AT91SAM9260 @
200 MHz

RAM

64 MByte

NAND Flash

4 GByte

Alarm I/O (X2):


Connector

Connector

RJ45

Type

RS232C

Bit rate

50 b/s - 38.4 kb/s

Level

typical: 6 V DC

Ethernet interface E1 (X6):


6 pin, removable screw
terminal

Pin 1, 2 (Alarm Output):


Type

CMOS switched output,


galvanic isolation

Max switching voltage

48 V DC

Max switching current


RON resistance

Connector

RJ45

Type

IEEE 802.3, 10/100BaseT

Serial interface CPM (X7):


Connector

2 x 5 pin, male for standard


flat cable

100 mA

Type

RS232C

Typical 1

Bit rate

50 b/s 9,6 kb/s

Level

typical: 6V

Pin 3, 4 (AC fail/Battery fail input) and


Pin 5, 6 (Process voltage fail input)
Type

Serial interface CP2 (X5):

Digital inputs, galvanic


isolated with reverse voltage protection

Max. input voltage


(Pin3 to 4 or 5 to 6)

60 V DC

Reverse voltage protection

Max. 60 V DC for 10s

Logical 1 definitely detected

21 V DC

Logical 0 definitely detected

15 V DC

USB (X9):
Connector

Type B

Type

USB 2.0, Device, 12 MBit/s

SD card:
Connector

SD card slot

Type

SD 2.0, class 2

Capacity

2 GByte

RTC: (R0011/ R0012 only)


Wired Or Bus, Serial I/O (X3):
Connector

2 x 10 pin, male for


standard flat cable

Type

Serial I/O bus

Serial interface CP1 (X4):

Battery

Lithium 3 V DC, CR2032

Time resolution

1 sec

Battery live time

> 10 years

Current Consumption
5 V DC

Connector

RJ45

Type

RS485

Bit rate
Level

Max. 300 mA

15 V DC

50 b/s - 38.4 kb/s

18 V DC

= 3 V DC (typical)

24 V DC

Doc. No.: 1KGT 150 825 V001 1

RTU511
Data Sheet Base Module 511CIM01
Insulation at Alarm I/O (X2)
Isolation

500 V DC ,> 100M

Binary Outputs (X2, X3)


Connector

8 pin, removable screw


terminal

Outputs

8 Relay Contacts, single


pole

Max. Switching
Current

3.0 A at 24 V DC
1.4 A at 48 V DC

Max. Switching
Current

1.0 A at 60 V DC
0.4 A at 110 V DC

EN60255/6.2.2
Impulse

Impulse 1 KV / 5 KV

EN60255/6.1.3
AC voltage

2,5 KV / 1 KV

EN60255/6.1.4

50 Hz, 1 minute

Multi I/O board 23IO96

(1 out of n) Check Circuit (X1)


Connector

7 pin, removable screw


terminal

2 Solid State Outputs for external relays

Max 24 V DC
Max. 200 mA

Measurement range

10 9 000

Measurement
accuracy

2.0 %
10 1 000

Measurement
accuracy

0.5 %
1 000 9 000

Analog Inputs (X4, X5)


Connector

2 x 7 pin, removable screw


terminal

Inputs

6 differential inputs

Measuring
ranges

2.5 mA
5 mA
10 mA
20 mA
1 V DC
10 V DC

Shunt / impedance

50 at 2,5 20 mA

Continuous load
without destruction

max. 50 mA
for 1 minute

Connector

3 pin, removable screw


terminal

Resolution:

11 bit plus sign


10 bit plus sign at 2,5 mA

Input voltage

see Power Supply Unit,


DC Input

Common mode
voltage

Absolute maximum rating


150 V DC.
Common mode rejection
85 db
Power Supply rejection
75 db

Line frequency

(fN): 16.6, 50 or 60 Hz

Accuracy

0.25 % (DIN 43782)


0.5 % at 2.5 mA

Binary Inputs (X6, X7)


Connector

10 pin and 9 pin removable


screw terminal

Inputs

16 channels, in two groups of


8 with common return

Input voltage

24 48 V DC, +15 %
60 110 V DC, +15 %

Input current

Typically. 3-5 mA
for 24 110 V DC

Logical 1 definitely
detected at:

18 V at 24 48 V DC
45 V at 60 110 V DC

Supply Voltage (X8)

Test Voltage (Binary Inputs)


AC Test Voltage
EN61000-4-16
IEC 60870-2-1
(class VW 3)

2,5 kV, 50 Hz
Test duration: 1 min

Impulse Voltage
with stand test
IEC 60255-5
IEC 60870-2-1
(class VW 3)

5 kV (1,2 / 50 s)

Doc. No.: 1KGT 150 825 V001 1

RTU511
Data Sheet Base Module 511CIM01
Power Supply Unit 23PU63
DC Input
Voltage

24 110 V DC

Tolerance Range

20 %

Max. Current

1.5 A

Startup Current

< 10 A, 1.5 ms
at 24 V DC
(Class S1) according
IEC 60870-4

Efficiency

> 70%

Reverse voltage protection

No

Fuses
Fuse F1 (main supply)

5 A (fast-blow)

Fuse F2 (process supply)

1.6 A (fast-blow)

Overall Output Power


Power

25 W total

External Output UE
Voltage

24 V DC

Tolerance Range

20 %

Max. Current (*)

0.5 A at 24 V DC

Residual Ripple

200 mVss

Please note:
The total power consumption of all voltage outputs
(internal and external) is limited to the maximum
output power of 25 W.

Doc. No.: 1KGT 150 825 V001 1

RTU511
Data Sheet Base Module 511CIM01
Common
Mechanical Layout

Immunity Tests
Electrostatic Discharge
Immunity Test
IEC 61000-4-2
(level 3)

4 kV Contact
8 kV Air

Length

303 mm

Performance criteria A

Height

116 mm

Radiated RadioFrequency Electromagnetic Field Immunity


Test
IEC 61000-4-3
(level 3)

10 V/m

Depth

96 mm

Weight

ca. 1,2 kg

Immunity to Electrical
Fast Transient / Burst
IEC 61000-4-4
(level 3)

4 kV

Surge Immunity Test


IEC 61000-4-5
(level 3)

2 kV

Immunity to Conducted
Disturbances, induced
by Radio-Frequency
Fields
IEC 61000-4-6
(level 3)

10 V

Performance criteria A

Overall Current Consumption


Performance criteria A

Performance criteria A

Performance criteria A

Environmental Conditions
Nominal operating temperature range

-25 ... +70 C

Start up

-40 C

Relative Humidity
(EN60068 2-30)

5 ... 95 %
(non condensing)

1.5 A

24 V DC

Ordering Information
511CIM01
(24-48 V DC)

1KGT 032300 R0001

511CIM01
(24-48 V DC, RTC)

1KGT 032300 R0011

511CIM01
(60-110 V DC)

1KGT 032300 R0002

511CIM01
(60-110 V DC, RTC)

1KGT 032300 R0012

Doc. No.: 1KGT 150 825 V001 1

RTU511

Data Sheet
Base Module 511CIM01

Note:
We reserve the right to make technical changes or modify the contents of
this document without prior notice. With regard to purchase orders, the
agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this
document.
We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or
utilization of its contents - in whole or in parts - is forbidden without prior
written consent of ABB AG.
Copyright 2013 ABB