Professional Documents
Culture Documents
1/2 % and +5 % turns. If, on-load, the secondary voltage reduces to 4050 V then, which tap, should be
used to maintain 4160 V on-load (assuming the supply voltage remains constant)?
The following answer results:
To keep the secondary voltage at (or as close as possible to) 4160 V, either primary supply voltage or
the HV winding tap position must be altered.
Examining the relationship:
V1/V2 = N1/N2 or V1N2 = V2N1 indicates that, to keep the equation in balance with primary voltage and
secondary winding turns fixed, either V 2 or N1 must be adjusted. Since the objective is to raise V 2 back
to nominal, then N 1 must be reduced.
To raise V2 from 4050 to 4160V requires an increase in secondary volts of: 4160/4050 =
1.027 or 102.7 %. N1must be reduced to 1/1.027 = 0.974
The transformer voltage at the load side desired to be constant or as close to the design value. But the
load voltage may vary according to current drawn by the load or supply voltage.
Based on the above equation to maintain constant secondary voltage/load voltage or as close to the
desired value it is needed to change the turns ratio. The tap changer of the transformer performs this task
to change the turns ratio. The tap changer basic function is that it removes or connects some portion of
the winding to the load side or source side. Tap changer can be located on primary side or secondary
side. However it will be placed on high voltage winding side.
In this type the tap changer circuit is placed in primary side or supply side. As we know;
Turns ratio
By the above formulas it is stated that if the primary turns decreases the turns ratio increases hence then
secondary voltage decreases. Opposite for the reverse case i.e. primary turns increase leads to turns
ratio decrease which increases the secondary voltage.
Figure shows the tap changer on primary winding with tap changing interval of 2.5 % per tap. With this we
can understand three conditions:
1)
In normal operation the tap changer will be at 0% position to provide required designed secondary
voltage.
2) If the supply voltage increases or load current decreases there will be an increase in supply voltage
which is not desirable. At this case the tap position in the primary winding will rise towards positive
direction i.e. +2.5%, and hence decreases the Np. This will increases the turns ratio (Ns/Np) further
decreases the secondary voltage.
Consider the load voltage decreased then the tap changer shift towards negative side to increase the
primary turns and hence decreases the turns ratio. The secondary voltage will increase to compensate
the change.
Tap changer Secondary side:
In this the tap changer is placed in secondary side of the transformer. This type of taping is used in stepup transformer where low voltage winding is in primary side and high voltage winding is in secondary
side. Figure shows the tap changer circuit on secondary side with tap interval of 2.5 %. In some
distribution transformers the tap changer resolution can be up to 1% for fine adjustments.
IMPORTANCE OF RMU
SELECTION FOR THE SOLAR
PV POWER PLANTS [ Air
Insulated RMU Vs Gas
Insulated RMU]
LikeIMPORTANC E OF RMU SELEC TION FOR THE SOLAR PV POWER PLAN TS [ Air Insulated RMU Vs Gas Insulated RMU]
41
C omment
ShareShare IMPORTANCE OF RMU SELEC TION FOR THE SOLAR PV POWER PLANTS [ Air Insulat ed RMU Vs Gas Insulat ed RMU]
V.R V
FollowV.R V
Head of Design Department at Leading Solar Organisation in India.
Now a days, Most of the Government Solar PV Project Tender having Gas Insulated RMU in the
HT Area. So Every component having Merits & Demerits, This Article deals, the detailed
Engineering Analysis of Air Insulated RMU & Gas Insulated RMU.
Busbar Clearance
<=1000mm]
2. Easy to Identify the internal Faults & Easy to Replace the Faulted things.
7. We can install Surge Arrestor, if system needs. In Gas Insulated RMU, it's difficult to Place.
10. Variety in Product Range. Also Developer can fabricate the Panel with different make of
associated Components of RMU.
Example: If Developer Needs Breaker from 'X' Company & Relays need from 'B' Company then
it's possible in Air Insulated RMU Panel.
2. More Space is Required. It Requires More space compare than Gas insulated RMU.
3. Plinth is required if RMU is Outdoor, Developing Plinth, Fencing Around of RMU will add more
Cost.
3. Required Product Delivery time is less, compare than Air Insulated RMU.
4. Gas Insulated RMU Only Required, where the limited space is available for the HT RMU.
2. System Monitoring:
Special Monitoring should needed to Monitor the SF6 Gas Quantity & Property.
3. Maintenance Factor:
Difficult to Maintain, Trained person is needed to Maintain the system.
5. Risk for Fire is little More Compare than Air Insulated RMU.
6. Space Constraint. Need to find Separate Panel to House All Auxiliary Relays or Additional Relays
if Required.
7. Cost will be Additional incase of the Relay Panels, which are not able to place in the Gas
Insulated RMU.
10. Difficult to place the CT & PT subjected to the Burden Ratings, which are again Subjected to
System Requirements.
11. Difficult to Repair, during fault Times. If system needs to replace means, then Particular Power
Block of the Power Plant gets disturbed. Loss subjected to the Cost of the power will be high to
the Power Developers. [Special Trained Personal is needed to Repair the Whole System]
Conclusion:
Air Insulated RMU is better to Consider where System Needs More Protection, High level fault
current area, & Where the system required Less Maintenance.
Gas Insulated RMU is better to Consider or better to use, Where the Plant having less space for
the HT Systems, Where the Time Constraint to commission the Project, Where the Plant needs to
commission the Project by investing less money on the HT Systems.
Drawing is nothing but to know about details of the Main Content and Associated with the Main
Content. Well, So Drawings Plays Major role in all areas, Especially in Projects.
Projects are categorized in various types, but those are common with One of the Known part,
Which is nothing but SLD [Single Line Diagram]. So SLD is the Heart of the Project in
Electrical Domain, Also it needs to know What are the Components will occupy in your building
permisses.
Without knowing any details of the Project, Only based on the Available SLD, The Well versed
Electrical Engineer easily identified, What type of Project will come.
Definition of SLD:
As a layman View, SLD is nothing but consisting of various
components of the Electrical System like, Transformer, DG, Panels
consisting of HT Breaker, LT Breaker, CT, PT, Fuses, Meters, Capcitor
and many on. Also it have HT Cables, LT Cables & Earthing System.
Mainly SLD Consists of many single lines, which says Three Phase Distribution system how
distributed to the Load from the Power Generation Source.
I updated here,Various types of SLD which are Categorized according to the Type of the
Electrical Distribution System.
A) Power Plant Generation Scheme.
B) Power Plant Distribution Scheme.
c) Commercial Project Scheme. [It included like Commercial Building Project, Industrial
Project, Multi-stage Building Project, IT Parks, Residential Project, Hospital Project, Hotels &
Resorts Project, Educational Institution Project]
Success of the SLD, Which is Easily understandable even by the Layman also.
HT Breaker:
Fig.B. HT
Breaker Symbol in SLD
When you are mentioning HT Breaker in the SLD, the following
things should present: [Similar to LT Breaker]
Arc Quenching Medium. Now a days AIR, Vacuum, SF6 are the three
Major Arc Quenching Mediums used in the almost of the Breakers till
Manufactured.
Draw out Model : Whether Breaker having Electrical Draw Out [EDO]
or Manual Draw Out [MDO]. Upward & Downward Arrow indicates that
Draw out Symbol.
CABLE:
Voltage Rating [For Low Rated Cable 1.1kV, for High Voltage Cable
11kV, 22kV, 33kV, for EHT Cable > 33kV]
CT & PT:
When you are mentioning PT in the SLD, the following things should
present:
When you are Developing C&R Panel SLD, the following things
should present:
Indicative Lamps.
The Drawing Quality is depended on how symbols used, Also it incorporated details which are
needed to easily understand the scheme. SLD Should Cover Legend [Symbols Description],
Insulation Strength of the Voltage and General Notes associated with the SLD.