SPECIFICATIONS FOR FALSE CEILING FOR OFFRs DUs OF DG MAP IN PORT BLAIR
1.

The following specifications will be used for the Offrs DUs to be constructed in MAP Ph-II in Port Blair:
(a)
The false ceiling will be of 8300 Unplasticized Poly Vinyl Chloride (uPVC) hollow
section which will have a thickness of minimum 6 mm & width of minimum 250 mm. It will be tongue &
groove system based having sliding interlocking. No screw should be visible to the occupant.
(b)
The grid will be of G.I. channel which will have minimum 8mm side lips section of minimum
overall size 20mm x 60mm. It will be clipped on the G.I suspended C-section of minimum size 12mm
x 40mm and having thickness of minimum 0.5mm. The C section will be fixed on the side wall & will
be suspended in level with the hanging G.I. wire fastener & suitable holding system. The GI Channel
section should be fixed on the C-Section at right angles at an equal distance of minimum 1.0m
depending on the ceiling height and air circulation conditions.
(c)
The 8300 uPVC section should be fixed on GI channel section with the help of self tapping
steel screw of minimum size 5mm x 12mm keeping in mind that no screw is visible from front. A
suitable uPVC J Section of minimum size 10mm x 25mm will be provided on all the sides of profile to
cover the open edges. If any joint comes in the profile, it should be joined with the help of H Section
of minimum size 10mm x 55mm. The colour combination and designs will be provided in ceiling as
per the site requirement and as desired by the Project Manager.

2.
Executing Agencies and Planning Team of DG MAP must ensure the provisioning of the above
specifications in the Project.
3.
The above specifications will only be for the Offrs DUs. For JCOs and ORs DUs, the same
specification that was used in MAP Ph-I in Port Blair will be followed.

(JS Sodhi)