Professional Documents
Culture Documents
1.
This specification covers design, engineering, manufacture, assembly, stage testing, inspection & testing
before supply and delivery at site at of cross linked polyethylene (XLPE) insulated cables with aluminum
conductors and a messenger wire of aluminum alloy to be used for overhead LT distribution system. The
size arei) 3CX95 (Ph) + 1CX70 + 1CX16 (SL)
These cables are to be used for three (3) phase 4 wire systems with neutral solidly earthed rated voltage
up to and including 1100V.
This specification defines the requirements (electrical, mechanical properties etc.) and tests to be
performed on the LT Aerial Bunched cables.
1.2 REFERENCES
This specification shall be governed by following standards with all amendments unless otherwise
specified in this specification.
IS:8130 - Conductors for Insulated cables
IS:398 (Part IV) - Messenger conductor
IS:10810 - Methods of test for cables
IS:14255 - Aerial Bunched cables for 1100V
IS:10418 - Drums for Electric Cables
IEC 60502, Part 1, 2004 - Power Cables with extruded Insulation, cables for rated voltages of 1kV and
3kV
NFC 33-209 - Bundle Assembled Insulated Cables.
HD 626 (CENELEC standard) Overhead distribution cables of rated voltage Uo / U(Um): 0.6/1(1.2)
KV
NOTE: This specification has mostly considered references from Indian Standards. However, certain
references have also been derived from the above referred International standards wherever
deemed suitable in meeting the onerous site requirements of SBPDCL.
1.3
DEFINITIONS
1.3.1
A LT Aerial Bunched cable shall typically, at maximum, comprise of: Insulated phase conductors
(3 numbers), Insulated neutral conductor (1 number), Insulated street lighting conductor (1
conductor) and a insulated messenger wire (1 number).
Example:
i) Designation
3 x 95 (P) + 1 x 70 (M) + 1 x 16 (SL)
P=Phase Conductor
M= Messenger
SL=Street Light Conductor
ii) Size
3 x 95 sq. mm = 3-phase conductors.
1 x 70 sq. mm. = 1 messenger wire
1 x 16 sq. mm. = 1 lighting conductor
1.3.2 Messenger Wire: As defined in NFC 33-209 Wire or cable which has principal function of
supporting the cable in overhead systems and which may be separate or may be an integral part
of the cable which it supports. Messenger wire should also be insulated conductor.
1.4
Climate CONDITIONS:
The AB cable shall be suitable for satisfactory continuous operation under the following tropical
conditions:
1.5
SPECIFICATIONS
1.5.1 Conductor
The Aluminum conductor shall be of circular cross section, stranded and compacted. They shall be of
H2 or H4 grade (complying with IS: 8130:1984) and per the following:
a) Upto and including 50 sq. mm. conductors = H2 grade.
b) All sizes above 50 sq. mm. conductors = H4 grade.
1.5.2
Messenger Wire
The messenger wire shall be insulated stranded, circular, aluminum magnesium silicon alloy type.
They shall have minimum 7 strands. They shall comply with IS 398 (part 4). Specific attention is made
to Tables 1, 2 & 3 of IS 398.
1.5.3
Conductor Insulation
a) The cross-linked polyethylene (XLPE) insulating shall be black in colour and to be stabilized
against deterioration caused by exposure to direct sunlight and ultraviolet radiation conforming
to requirement specified in Table 1 of IS : 14255 1995 or IEC 60502. XLPE insulation shall be
pressure extruded
b) The nominal value of the carbon black content of the sheath (insulation) shall be 2.5 with a
tolerance of + 0.5% (Table 20 of IEC : 60502-1, 2004)
c) The XLPE material shall be preferably of BOREALIS, DOW or any other make subject to the prior
written approval of the buyer.
d) The average thickness of insulation shall comply to Table 4 of IS : 14255 1995. For nominal
area of conductors above 95 sq. mm., the average thickness of insulation shall not be less than
the nominal value mentioned hereunder :
Nominal Area of Conductor (sq. mm.) Nominal Thickness (mm.)
95
1.5
e) All other requirements related to insulation shall comply to clause 7 of IS: 14255 1995.
1.5.4
Core Identification
The core identification shall be as per clause no. 8.1 of IS: 14255 1995. Ridges shall be provided
over phase core and neutral core also.
1.5.5
Laying of Cores
The assembly (laying up) of cores shall be as per clause 9 of IS : 14255 1995.
1.5.6
Embossing on cores.
All the cable shall have the following embossing on insulated neutral conductor for identification in
interval not more than 2 meters. Font size of letters to be min. 5 mm.
i.
ii.
iii.
iv.
v.
vi.
vii.
viii.
ix.
1.6
6.1
Routine test
6.2
Acceptance test
6.3
Type Test
The AB Cable shall be wound on non-returnable wooden drums conforming to IS: 10418 with
latest amendments thereof. The drums should have supporting plate with bush at central
hole. The end of the cable shall be sealed by means of non-hygroscopic sealing material. The
marking of drum shall be in line with IS: 14255:1995.
1.6.2
The drums shall be of such construction as to assure delivery of cable in the field free from
displacement and damage and should be able to withstand all stresses due to handling and
the stringing operation so that cable surface is not dented, scratched or damaged in any way
during transportation and erection. The cable shall be properly lagged on the drums.
1.6.3
Technical Parameter
YEARS OF MANUFACTURING
SIMILAR CABLE
Unit
Nos.
NBPDCL Specification
3 or more years of supply of
similar sizes and
design / higher sizes of cables.
(Furnish client list)
Furnish for all type tests as
mentioned in IS 14255 1995. The tests should have
been performed NOT earlier
than 5 years.
Type test certificate shall be
from CPRI/REDA/KEMA shall be
submitted.
66 / 60 MONTHS
APPLICABLE STANDARDS
IS14255:1995,
IS 398 (part 4): 1979,
IS 8130: 1984,
IS 10810:1990,
IS 10418:1982, IEC-60502,
NFC-33-209
HD 626 (Cenelec standard.)
VOLTAGE GRADE
1.1KV Grade
NO. OF CORES/TYPE
i) PHASE CONDUCTOR
3 (Al)
1 (Al )
iii) MESSENGER
1 (Al Alloy)
1 (Al )
95 mm2
i) PHASE CONDUCTOR
(nom.) 95
ii) MESSENGER
(nom.) 70
(nom.) 16
Vendor Data
95 mm2
Sl.
No.
8
Technical Parameter
Unit
ii) MESSENGER
iii) STREET LIGHTING CONDUCTOR
10
Vendor Data
NUMBER OF STRANDS IN
i) PHASE CONDUCTOR
NBPDCL Specification
iii) MESSENGER
LINEAR RESISTANCE OF
CONDUCTOR AT
20 deg.C (max)
(with the combination of phase
conductor and
others per sl. No. 6 above)
i) PHASE CONDUCTOR
iii) MESSENGER
iv) STREET LIGHTING CONDUCTOR
95 mm2
ohm /
km
ohm /
km
ohm /
km
11
95 mm2
Amps
12
95 mm2
Amps
13
95 mm2
Sl.
No.
Technical Parameter
Unit
NBPDCL Specification
Vendor Data
KA
14
15
kN
36.640
kN
1.90
16
17
18
19
20
21
iii) MESSENGER
iv) STREET LIGHTING CONDUCTOR
Lay ratio and direction of lay of
conductor
i) Phase conductor
ii) Neutral conductor
iii) Messenger conductor
iv) Street light conductor
Type of insulation
i) Make of insulation
ii) Grade of insulation
COLOUR OF INSULATION
CARBON BLACK CONTENT (%)
EXTRUSION PROCESS
ISULATED CABLE OUSIDE DIAMETER
(mm)
i) PHASE CONDUCTOR
ii) NEUTRAL CONDUCTOR
22
70 mm2
Messenger
95 mm2
(min.)
(max.)
(min.)
(max.)
(nom.)
(nom.)
95 mm2
XLPE
Black
2.5% (MAX.)
PRESSURE EXTRUDER
95 mm2
(min.)
(max.)
(min.)
(max.)
(nom.)
Ridges per clause 8.1 of IS :
14255-1995
Ridges per clause 8.1 of IS :
14255-1995
None
i) PHASE CONDUCTOR
ii) NEUTRAL CONDUCTOR
23
24
25
70 mm2
Messenger
mm
Right Hand
Sl.
No.
26
27
Technical Parameter
WEIGHT OF THE CABLE
(with the combination of phase
conductor and others per sl. No. 6
above)
STANDARD LENGTH PER DRUM
(with the combination of phase
conductor and others per sl. No. 6
above)
Unit
27
Vendor Data
Kg/km
95mm2
mtr
28
NBPDCL Specification
95mm2
400
Wooden Drum
kg
28
29
30
31
32
mm
Kg/km
Kg/km
Kg/km
Kg/km
Kg/km
AS PER IS 5484:1997
AS PER IS 9997:1991
Note: Bidder shall furnish the GTP format with all details against each clause. Bidder shall not
change the format of GTP or clause description.
With bid
( 1 sets of
hard copies)
1
2
3
4
5
6
7
8
9
10
11
12
13
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Post bid
For review &
approval
(2 sets of hard
copies)
Prior to Dispatch
As built (2 sets of
hard copies and 1
CD-Rom )
2.
LOCATION:
Aerial bunched Cables for use in L.T. overhead lines are preferred than conventional L.T.overhead lines with
bare conductors as those are not subjected to frequent faults as happens with the bare conductors and also
to minimise problem of tree clearance etc. ABC System is safer and eliminates use of insulators and
associated hardwares required for bare conductors.
3.
APPLICABLE STANDARDS:
Unless otherwise stipulated in this specification, the following standard with up to date amendment shall be
applicable.
IS 14255-1995 Specification for AERIAL Bunched Cables for working Voltage Up to & including 1100 Volts.
IS : 8130 Specification for Conductors for Insulated Cables.
IS : 398 (Part-IV) Specification for Aluminium Alloy Conductor.
4.
RATED VOLTAGE :
The rated Voltage of LT AB Cables shall be 1100 Volts.
5.
CONDUCTORS :
The Aluminium Conductors for phase/street lightning conductor shall be H2 of H4 grade Aluminium
complying with the requirements of IS-8130-1984 with up to date amendments. For messenger wire
stranded All Aluminium Conductor shall be of heat treated Aluminium Magnesium-Silicon Alloy Wires
containing approximate 0.5% magnesium and 0.5% silicon conforming to IS-398 (Part-IV)/1984 with up to
date amendments. The stranded conductor shall be clean & reasonably uniform in size and shape and its
surface shall be free from sharp edges. Not more than two joints shall be allowed in any of the wires
forming every complete length of conductor and no joint shall be within 300 mm. of any other joint in the
same layer. The joint shall be brazed, silver soldered or electric or gas welded. No joint shall be made in the
conductor, once it has been stranded.
6.
INSULATION :
The Conductor (with protective barrier, wherever applied) shall be provided with cross linked polyethylene
applied by extrusion conforming to the standard Specification as per IS 4255/95.The average thickness of
insulation when measured in accordance with relevant clause of the specification, shall not be less than
standard value specified. Upper surface of Cable insulation should be Ultra Violet Ray resistant Colour of
insulation shall be black.
7.
CORE IDENTIFICATION :
The Phase Conductors shall e insulated with black weather resistant, XLPE suitable for 1100 Volt insulation.
The Phase Conductor shall be provided with one, two and three ridges for quick identification. The individual
cores thus formed shall then be laid up around insulated messenger wire. The insulated messenger wire
shall have four ridges as per IS 14255:1995. The insulated street lighting conductor shall not have any
identification mark.
8.
MESSENGER-CUM-NEUTRAL WIRE :
The insulated messenger wire shall be of aluminium alloy, generally conforming to IS 398 (Part-IV)/1994
and suitably compacted to have smooth round surface to avoid damage to the other insulating sheath of
phase conductor twisted around the messenger.
9.
LAYING UP :
Three Power Cores having Ridges one, two and three and one street lighting without any ridge, if any
should be twisted over insulated messenger wire with right hand direction of lay. This will from the Aerial
Bunched Cable. Lay ratio shall be as specified in IS:14255/ 1995.
13. INSPECTION :
The Cable shall be inspected at manufacturers works before despatch as per IS-7098 (Part-I)/1988 (with
upto date amendments) & IS 14255/1995. All the acceptance testsembodied in the above shall be
14.
15.
Size
Ph.Wire + St.Light Wire + MessengerCumNeutral Wire
1)
2)
3)
4)
3x25
3x35
3x50
3x70
+
+
+
+
1x16
1x16
1x16
1x16
+
+
+
+
1x25
1x25
1x35
1x50
sq.mm.
sq.mm.
sq.mm.
sq.mm.
[ Sizes of Power Conductor & Messenger Wire may vary as per requirement ]
B.
ACCESSORIES REQUIRED FOR DRAWAL OF L.T. OVERHEAD LINE WITH1100V GRADE AERIAL
BUNCHED CABLES ON PCE POLE SUPPORT
Sl.No.
1
2
Description
Anchor Clamp (3-Bolt and 2 Bolt Type)
Eye hook with Suspension Clamp Assembly.
3
4
5
NOTE: Offer for L.T. Aerial Bunched Cables should cover required accessories with details of dimensions,
materials and provisional quantity per K.M. of L.T. O/H Line.
16
25
35
50
70
4.4
5.5
6.8
7.9
9.4
65
95
12 7
170
1.20
0.868
0.641
0.443
1.2
1.2
1.5
1.5
85
100
120
155
42
1.91
1.2
Note : The resistance values given in the Table are the max. Permissible one.
Dia.of Compacted
Conductor (mm.)
Approx. mass
(Kg./Km.)
Max. D.C.
resistance
At 20C
(Ohm./Km.)
Minimum
Tensile
Strength (KN)
25
5.9
65
1.38
7.4
35
6.9
95
0.986
10.3
50
7.9
127
0.689
14.0
1. SCOPE :
The specification covers design, manufacture, testing before despatch, transportation,
supply and delivery of ISI marked 11 KV Grade XL PE insulated screened armoured all
aluminium conductor and PVC sheathed Power Cables suitable for effectively earthed
11KV Overhead Lines.
:
2. LOCATI ON
11KV Aerial bunched Cables are composite Cable especially intended for overhead line
use in forest areas where tree clearance poses a series problem and in other cases where
it is difficult to get clearance for bare conductor lines.
These Cables comprise of 3 XLPE insulated Single Phase Cables twisted around a bare
messenger wire, which will carry the weight of composite Cabl e.
3. APPLICABLE STANDARDS :
Unless otherwise stipulated in this specification, the foll owing standard with up to date
amendment shall be applicabl e.
IS 7098 (Part-II)-1985 Cross linked polyethylene insulated PVC sheathed Cables.
IS : 8130-1984 Conductors for Insulated Cabl es.
IS : 398 (Part-II)-1976 Galvanised Steel Wires.
IS : 398 (Part-IV)-1979 Aluminium All oy Conductors.
4. RATED VOLTAGE :
The rated Voltage of the Cables shall be 11KV and the maxi mum operating Voltage shall
be 12KV.
5. CONDUCTORS :
The Al uminium Conductors shall comply with the requirements as specified in
IS-8130-1984 with up to date amendments. The stranded conductor shall be clean &
reasonably uniform in size and shape and its surface shall be free from sharp edges. Not
more than two joints shall be allowed in any of the wires forming every complete length of
conductor and no joint shall be within 300 mm. of any other joint in the same l ayer.
Joints shall be brassed, silver soldered or electric or gas welded. No joint shall be made in
the conductor once, it has been stranded.
6. INSULAT ION :
The insulation shall be chemically cross linked polyethylene conforming to the physical,
electrical and ageing properties as required in the specification. Cross-linking may be
done by exposure to peroxide with nitrogen curing CCV line, method with intenti on to
ensure lowest tree formation. Only natural unfilled compound shall be used for
insulation. Thickness when measured in accordance with relevant Clause of the
Specification, shall not be less than the standard thickness value specified.
7. SCREENING :
The screening of insulated Cables shall consist of conductor screening and insulation
screening.
Screening Materials :
Two types of materials may be used for screening of Cables : non-metallic & metallic.
Conductor Screening :
Conductor screening shall be non- metallic and shall consist of a layer of extruded-semiconducting cross linked polythine compound of thickness no less than 0.5 mm.
Insulating Screening :
The insulation screening shall consist of non-metallic semi-conducting part in
combination with a metallic part. Non-metallic part shall be appli ed either directly over
the insulation of each core and shall consist of ei ther a semi-conducting tape or a layer of
extruded semi-conducting compound or a combination of these materials. The metallic
part shall be applied over the individual core. Metallic screening shall consist of either
tape or braid or concentric serving of wires or a sheath and shall be non-magnetic.
8. OUTER SHEATH :
Over the armouring/metallic screen the Cable shall be provided with extruded PVC outer
sheath. The composition of the PVC compound for outer sheath shall be Type ST2 of
IS-5831-1984. The col our of the outer sheath shall be black. The average thickness of the
sheath shall not be less than the standard values specified in the IS when measured as
laid in IS-7098(Part-II)/1985. The smallest thickness of the measured values of sheath
shall not fall below the standard value(s) specified with tolerance. Outer surface of the
Cable shall be ultra-violet Ray resistant.
9. CORE IDENTIFICATION :
The Core identification shall be done by Ridges one, two and three on PVC covering over
core.
10. BARE MESSENGER WIRE :
Bare messenger wire shall consist of combination of galvanised steel wires and
aluminium alloy wires. Central layer(s) shall be of galvanized steel wires and outer
layer(s) shall be of Aluminium Alloy Wires. Galvanised Steel Wires shall be tested as per
IS:398(Part-II)/1978 and
Aluminium Alloy Wires shall be tested as per
The number of strands and diameter of strand for Steel Wire &
IS:398(Part-IV) /1979.
Aluminium Alloy Wire for Bare Messenger Wire shall be calculated considering 100 mtrs.
Span Length on 9 mtrs. PCC Pole Support and Breaking Load of Messenger Wire.
11. LAYING UP :
Three Power Cores having Ridges one, two and three shall be twisted over bare
messenger wire with right hand direction of lay. This will from the Aerial Bunched Cabl e.
12. TESTS :
1. Copies of the type test certificates in respect of all the type tests as per IS:7098
(Part-II) 1985 for similar type of XLPE Cables from any Government recognised
Testing Labs, shall
be submitted along with the Tender.
LIST OF TYPE TESTS :
a)
ii)
iii)
iv)
b)
c)
d)
i)
As a function of Voltage.
As a function of temperature.
Insulation resistance (volume resistivity) test.
Heating cycle test.
m) Year of Manufacture.
The standard Drum Length will be 250 mtrs. in each Drum for all sizes subject to a
maximum tolerance of + 5%
18. LITERATURE AND MANUAL :
To be submitted as per General Terms & Conditions of Contract.
19. GUARANTEED TECHNICAL PARTICULARS :
To be submitted along with Tender documents.
A.
Size
Power Core Messenger Wire
NOTE : Offer for 11KV A B Cables should cover required accessories with details of
dimensions, materials and provisional quantity per K.M. of 11KV O/H Line.
------- --- ------ --- --- --- --- ------ --- --------------------------------------------------------------------------------------
95
11.3
120
12.7
150
14.1
185
15.8
0.320
0.253
0.206
0.164
3.6
3.6
3.6
3.6
8.96
11.32
14.16
17.46
230
265
300
345
70
95
180
180
180
210
210
2600
3000
3300
3800
4200
14
59
23 x 10 /0C
Stranded Compacted Circular
16
Power Cross(mm.)n/mm.
Messenger Core(mm)/n/mm.
B.
i)
ii)
C.
i)
ii)
D.
i)
Power Cores.
3.2 Insulation
i)
Power Cross (mm.)
a) Material.
b) Nominal thickness.
c) Method of application.
3.3 Conductor Screening ;
a) Material.
b) Nominal thickness
c) Method of application.
3.4 Insulation Screening :
a) Material
b) Nominal thickness.
c) Method application.
3.5 Metallic Screening :
a) Material.
b) Nominal thickness.
3.6 Outer Sheath :
a) Material.
b) Nominal thickness
4. Messenger Wire (Bare)
i)
Nom. Cross Sectional area (sq.mm.)
ii) Approx. breaking load (KN)
5. Current ratings
i) Continuous current carrying capacity of Cable in Air at
0 C (Amp.)
Ambient Temp. 40
6. Approx. Weight (Kg./Km.)
7. No. of Cores
i)
ii)
8. Derating factor
Derating factors for variation in Air Temp.
0 C
Air Temp.
9. Rating Factor.
9.1 Identification of Power Cores
9.2 Laying.
10. Details of Power/Messenger Core
10.1
Conductor :
a) Material
b) Flexibility Class as per IS : 8130/84
c) Form of Conductor.
10.2 Insulation
a) Material.
b) Form of Conductor
11. Voltage Grade of Power Cable.
a) Service Voltage.
b) Neutral Earthing.
12. Maximum Conductor Temperature.
a) Continuous (in Deg.C)
b) Short time (in Deg.C)
13. Type of curing of XLPE Insulati on
14. Completed Cable :
Approx. overall diameter.
Approx. Weight/KM
15. Cable Drums :
a) Length/Drum/
b) Dimension of Drum.
c) Shipping Weight.
d) Marking of Cable Drums as per IS
Yes/No.
2.
LOCATION:
Aerial bunched Cables for use in L.T. overhead lines are preferred than conventional L.T.overhead lines with
bare conductors as those are not subjected to frequent faults as happens with the bare conductors and also
to minimise problem of tree clearance etc. ABC System is safer and eliminates use of insulators and
associated hardwares required for bare conductors.
3.
APPLICABLE STANDARDS:
Unless otherwise stipulated in this specification, the following standard with up to date amendment shall be
applicable.
IS 14255-1995 Specification for AERIAL Bunched Cables for working Voltage Up to & including 1100 Volts.
IS : 8130 Specification for Conductors for Insulated Cables.
IS : 398 (Part-IV) Specification for Aluminium Alloy Conductor.
4.
RATED VOLTAGE :
The rated Voltage of LT AB Cables shall be 1100 Volts.
5.
CONDUCTORS :
The Aluminium Conductors for phase/street lightning conductor shall be H2 of H4 grade Aluminium
complying with the requirements of IS-8130-1984 with up to date amendments. For messenger wire
stranded All Aluminium Conductor shall be of heat treated Aluminium Magnesium-Silicon Alloy Wires
containing approximate 0.5% magnesium and 0.5% silicon conforming to IS-398 (Part-IV)/1984 with up to
date amendments. The stranded conductor shall be clean & reasonably uniform in size and shape and its
surface shall be free from sharp edges. Not more than two joints shall be allowed in any of the wires
forming every complete length of conductor and no joint shall be within 300 mm. of any other joint in the
same layer. The joint shall be brazed, silver soldered or electric or gas welded. No joint shall be made in the
conductor, once it has been stranded.
6.
INSULATION :
The Conductor (with protective barrier, wherever applied) shall be provided with cross linked polyethylene
applied by extrusion conforming to the standard Specification as per IS 4255/95.The average thickness of
insulation when measured in accordance with relevant clause of the specification, shall not be less than
standard value specified. Upper surface of Cable insulation should be Ultra Violet Ray resistant Colour of
insulation shall be black.
7.
CORE IDENTIFICATION :
The Phase Conductors shall e insulated with black weather resistant, XLPE suitable for 1100 Volt insulation.
The Phase Conductor shall be provided with one, two and three ridges for quick identification. The individual
cores thus formed shall then be laid up around insulated messenger wire. The insulated messenger wire
shall have four ridges as per IS 14255:1995. The insulated street lighting conductor shall not have any
identification mark.
8.
MESSENGER-CUM-NEUTRAL WIRE :
The insulated messenger wire shall be of aluminium alloy, generally conforming to IS 398 (Part-IV)/1994
and suitably compacted to have smooth round surface to avoid damage to the other insulating sheath of
phase conductor twisted around the messenger.
9.
LAYING UP :
Three Power Cores having Ridges one, two and three and one street lighting without any ridge, if any
should be twisted over insulated messenger wire with right hand direction of lay. This will from the Aerial
Bunched Cable. Lay ratio shall be as specified in IS:14255/ 1995.
13. INSPECTION :
The Cable shall be inspected at manufacturers works before despatch as per IS-7098 (Part-I)/1988 (with
upto date amendments) & IS 14255/1995. All the acceptance testsembodied in the above shall be
14.
15.
Size
Ph.Wire + St.Light Wire + MessengerCumNeutral Wire
1)
2)
3)
4)
3x25
3x35
3x50
3x70
+
+
+
+
1x16
1x16
1x16
1x16
+
+
+
+
1x25
1x25
1x35
1x50
sq.mm.
sq.mm.
sq.mm.
sq.mm.
[ Sizes of Power Conductor & Messenger Wire may vary as per requirement ]
B.
ACCESSORIES REQUIRED FOR DRAWAL OF L.T. OVERHEAD LINE WITH1100V GRADE AERIAL
BUNCHED CABLES ON PCE POLE SUPPORT
Sl.No.
1
2
Description
Anchor Clamp (3-Bolt and 2 Bolt Type)
Eye hook with Suspension Clamp Assembly.
3
4
5
NOTE: Offer for L.T. Aerial Bunched Cables should cover required accessories with details of dimensions,
materials and provisional quantity per K.M. of L.T. O/H Line.
16
25
35
50
70
4.4
5.5
6.8
7.9
9.4
65
95
12 7
170
1.20
0.868
0.641
0.443
1.2
1.2
1.5
1.5
85
100
120
155
42
1.91
1.2
Note : The resistance values given in the Table are the max. Permissible one.
Dia.of Compacted
Conductor (mm.)
Approx. mass
(Kg./Km.)
Max. D.C.
resistance
At 20C
(Ohm./Km.)
Minimum
Tensile
Strength (KN)
25
5.9
65
1.38
7.4
35
6.9
95
0.986
10.3
50
7.9
127
0.689
14.0
A
B
C
Type of DTR
Incomer
63 A SPN MCB
63 A TP MCCB
100 A TP MCCB
Outgoing
2 X 32 A SPN MCB
2X40 A TP MCCB
3 X 40 A TP MCCB
Mounting
Arrangement
Channel Frame
Channel Frame
Channel Frame
All outgoing LT feeders (numbers to be decided by utility based on number of service connection/
outgoing feeders) shall emanate from LT buses get connected toLT feeder through respective SPN MCB/TP
MCCB. Suitable no. of holes with cable glandsalong with IS approved gaskets shall be provided in the lower
compartment of thedistribution. Neoprene Rubber gasket shall be used in the door to avoid ingress ofmoisture
and other elements in the distribution box. The distribution box shall havepainting as per relevant IS standards.
The Switchboard shall be made of MS of thickness not less than 2.5 mm. door panel and 4 mm Body panel and
shall be dust, moisture, vermin and weather proof with degree of protection IP 55 as per IS: 13947 suitable for
outdoor use. Box shall be mounted on distribution transformer / pole structure.
All parts, doors, movable covers and panels shall be fitted all around with neoprene gaskets. The gaskets shall
be provided along a channel on periphery of the doors and covers. Ventilating louvers shall be provided with
brass screen and filters.
The Switchboard shall have neat appearance inside and outside with all equipment mounted flush having no
visible welds, with all exterior surfaces even and smooth.
The door is to be provided in front with internal hinges. Cable entries shall be from bottom. Cable gland plate
and gland shall be provided at the bottom plate. The wiring shall be such that terminals are accessible by use of
ordinary tools. Connections shall be provided with adequate clearance to avoid short circuits and risk of fire and
8. PROTOTYPE SAMPLE
A prototype sample of each category of the LV Switchboard should be initially manufactured and submitted for
approval of purchaser before taking up mass manufacture.
Transformer
Capacity
KVA
Full Load
Current
Amps
Incoming
Circuit
Configuration
Outgoing
Circuits
Configuration
Mounting
Arrangement
63
88 Amp
125 A TP MCCB
3 X 63 A TP MCCB
Channel Frame
100
139
200 A TP MCCB
2 X 63 A TP
MCCB& 1 X 100 A
TP MCCB
Channel Frame
The Switchboard shall be MS of thickness not less than 2.5 mm. door panel and 4 mm Body panel and shall be dust,
moisture, vermin and weather proof with degree of protection IP 55 as per IS: 13947 suitable for outdoor use. They
shall be of freestanding structure, independent floor mounting design or mounted on a channel frame at a suitable
height of about 1.2 meters from the floor. It shall have sufficient channel and angle re-enforcement to resist
vibrations and rigidity during transportation, erection and operation.
All parts, doors, movable covers and panels shall be fitted all around with neoprene gaskets. The gaskets shall be
provided along a channel on periphery of the doors and covers. Ventilating louvers shall be provided with brass
screen and filters.
The Switchboard shall have neat appearance inside and outside with all equipment mounted flush having no visible
welds, with all exterior surface even and smooth. The door is to be provided in front with internal hinges.
Cable entries shall be from bottom. Cable gland plate and gland shall be provided at the bottom plate. The wiring
shall be such that terminals are accessible by use of ordinary tools. Connections shall be provided with adequate
clearance to avoid short circuits and risk of fire and ease in connection and disconnection. All internal wiring should
be with fire resistance low smoke PVC insulated cables of copper core size 2.5 sq. mm minimum complying with IS:
1554.
The entire switchboard shall be suitable to withstand short circuit current equivalent to 25 MVA 415 Volts for one
second.
2. OPERATION AND SAFETY
All operations shall be from the front.
3. GOVERNING STANDARDS
The equipment will be manufactured in conformity with the following Indian Standard Specification (latest editions).
IS:2950 A.C. Connectors
IS:8623/1993 Low Voltage Switchgear and Control gear Assemblies
6. EARTHING
Earthing arrangement shall be provided with earth bars of electrolytic aluminium and earthing terminals at two
ends similar to the arrangement described in General Technical Specification. The earth bar shall be of
electrolytic aluminium running from end to end of the switchboard terminating in two earthing terminals at the
two ends. Earthing shall be accomplished as described in General Technical Specification.
7. ENERGY METER
Each incoming panel shall be provided with the energy meter. (Details of the energy meter shall be given
separately by purchaser)
8. TESTS
Each type of LV. Switchboard shall be completely assembled, wired, adjusted and tested at the factory as per
the relevant standards and during manufacture and on completion.
Routine Test
The tests shall be carried out in accordance with IS 13947 and 8623 include including but not necessarily limited
to the following:
(a) Visual Check
Type Test
All type tests shall be performed in accordance with IS 13947 and 8623
9. PROTOTYPE SAMPLE
A prototype sample of each category of the LV Switchboard should be initially manufactured and submitted for
approval of purchaser before taking up mass manufacture.
DISTRIBUTION TRANSFORMER
PART 1: GENERAL
1.
SCOPE
1.1 The specification covers the design, engineering, manufacture, stage inspection, testing, pre-delivery
inspection, supply, delivery, loading, unloading and performance requirements of 11/0.433 KV non-sealed type
aluminum wound BEE specified 3 Star Distribution Transformers for outdoor. The transformers shall be double
wound, three phase, CRGO M3 Grade (0.23mm) or better, oil immersed with ONAN cooling with Oil filled up to
maximum permissible level. The ratings required under this specification are 25 KVA, 63 KVA & 100 KVA with
Aluminum windings.
1.2 The equipment offered should have been successfully type tested within five years from date of tender and
the designs should have been in satisfactory operation for a period not less than one years as on the date of Bid
opening. Compliance shall be demonstrated (i) authenticated copies of the type test reports and (ii) performance
certificates from the users, specifically from Central Govt. / State Govt. or their undertakings.
2.
2.1 Except where modified by this specification, the transformers shall be designed, manufactured and tested in
accordance with the latest editions of the following standards.
IEC/ISO
Indian Standard
IEC 71
IEC 76
IEC 137
Insulation Coordination
IS 2026
Power Transformers.
IS 1180
IS 2099
IEC 156
IEC 296
IS 6792
IEC 354
Subject
IS 6600
strength of
Transformers
IEC 437
IEC 551
IEC 616
IEC 722
Galvanizing
This list is not to be considered exhaustive and reference to a particular standard or recommendation in this
specification does not relieve the Supplier of the necessity of providing the goods complying with other
relevant standards or recommendations.
3.
SERVICE CONDITIONS
The service conditions shall be as follows: (To be confirmed by PIA as per locality of project)
Hilly area
Plane
area
1000m
50 C
50 C
40 C
40 C
-5 C
-30 C
5000m
32 C
32 C
100%
100%
70
70
120
120
1500 mm
1500 mm
260Kg/m2
260Kg/m2
per
annum
60 C
60 C
Environmentally, the region where the equipment will be installed includes coastal areas, subject to high relative
humidity, which can give rise to condensation. Onshore winds will frequently be salt laden. On occasions, the
combination of salt and condensation may create pollution conditions for outdoor insulators.
Therefore, outdoor material and equipment shall be designed and protected for use in exposed, heavily
polluted, salty, corrosive, tropical and humid coastal atmosphere.
4.
SYSTEM CONDITIONS:
The equipment shall be suitable for installation in supply systems of the following characteristics.
Frequency
50 Hz 5%
11 KV System
LV System
433/250 V
11 KV System
LV System
Minimum LV voltage
(NEC)
11 KV System
11 KV
12 KV
476 V
392 V
Insulation levels :
11 KV System
11 KV System
28 KV (rms)
LV System
3 KV (rms)
LV System
Solidly earthed
PART 2 : TECHNICAL
SPECIFIC TECHNICAL REQUIREMENTS
2 No. of phases
3 Type of installation
Outdoor
4 Frequency
50 Hz ( 5% )
5 Cooling medium
6 Type of mounting
On Channels.
7 Rated voltage
a) High voltage winding
11 KV
0.433 KV
12 KV / 0.476 KV
11 KV / 0.433 KV
9 No. of windings
10 Type of cooling
100%
cooling system
12 Method of connection:
HV:
Delta
LV:
Star
13 Connection symbol
Dyn 11
14 System earthing
% Impedance + Tolerance %
4.5 + 10%
windings
17 a) Anticipated unbalanced loading
Around 10%
(HV / LV)
18 a) Type of tap changer
NA
b) Range of taping
No Tap
On LV side only
duration
21 Maximum Flux Density in any part of the
1.5 Tesla
HV: 95
LV: N.A.
withstand (KVP)
b) Power frequency voltage withstand (KVrms)
HV: 28
LV: 03
Uniform
b) LV winding
Uniform
2 Seconds
temperature of 500C
a) Of top oil measured by thermometer.
350C
400 C
280
b) Phase to ground
140
b) LV winding
HV
LV
95
Not applicable
28
25 mm/ KV
EC grade Aluminum
Boltless type
34. Losses:- The losses shall not exceed the value given below
KVA
Rating
Load
losses at
75C
Watts
25
No-load
losses
(Fixed
loss)
Watts
100
63
180
1235
100
260
1760
685
6. TYPE OF TRANSFORMER
6.1 The transformers shall be of core type construction, double wound, three phase, oil immersed, 11/0.433KV, 50
Hz with natural oil and air cooling (ONAN) to be used as step down transformers for outdoor use. The design of the
tank, fittings, bushings, etc shall be such that it will not be necessary to keep the transformer energized to prevent
deterioration as the transformers may be held in reserve, outdoors, for many years.
7.
7.1
7.2 The transformer shall be capable of supplying a continuous load equal to its KVA rating, under the following
conditions :
Continuous steady load;
Design at maximum ambient air temperature of 50C;
40C average winding temperature rise and 35C top oil temperature rise for conventional breathing
transformers.
7.3 The transformer may be overloaded during emergency up to 150% of its continuous rating in accordance with
IEC Publication 354 or IS: 6600. Bushings. and other current-carrying parts shall also be designed for this
condition.
7.4 The transformer shall be capable of withstanding for two seconds without damage to any external short
circuit, with the short circuit MVA available at the terminals of either winding with rated voltage on the other
winding. If short circuit tests have been carried out on the particular design of transformer offered, the test results
shall be supplied with the bid.
7.5 The thermal ability to withstand short circuit shall be demonstrated by calculation.
7.6 The transformer shall be capable of withstanding the thermal and dynamic effects of short circuits, as
specified in IEC 76-5 or IS: 2026: Ability to withstand short circuits.
7.7 The maximum flux density in any part of the core and yoke at rated KVA, Voltage and frequency shall not
exceed 1.5 Tesla.
8. VOLTAGE RATIO & TAPPING RANGE
8.1
The transformers shall have the following ratio :the nominal voltage ratio shall be 11,000/ 433 V for 25 KVA, 63 KVA, 100 KVA 11/0.4KV transformers;
Tolerance on the voltage ratio shall be 0.5%.
transformers up to 100 KVA, 11/0.4 KV no tap changer is required.
8.2 The bidder shall state in the technical schedule, the percentage regulation at full load, power factor 1.0 and at
full load, power factor 0.85 lagging.
Transformers shall be suitable for parallel operation with each other.
9. PERCENTAGE IMPEDANCE
9.1 The Percentage of Impedance at 75C shall be 4.5 % for 25 KVA,63 KVA & 100 KVA transformers. No negative
tolerance on percentage Impedance is allowed.
10 LOSSES
The load losses shall not exceed the values given below:KVA Rating
25
63
100
10.1 The above losses are maximum allowable and there should not be any positive tolerance. Transformer having
losses more than above values shall be rejected.
10.2 The offered transformer(s) should have been type-tested designed at CPRI/ NABL Accredited laboratory. The
bid shall be accompanied with type-test reports (short circuit test and Impulse test) conducted at Central Power
Research Institute / NABL Accredited laboratory for the offered transformers within five years from date of tender.
The short circuit test report(s) must contain the measured no load loss and load loss, determined by CPRI/ NABL
Accredited laboratory.
In case of any doubts, Employer reserves the right to verify the original type test reports of CPRI/ NABL Accredited
laboratory or ask the supplier to conduct the type tests at CPRI/ NABL Accredited laboratory at his (suppliers) cost
for re-confirmation of the test results particularly no load losses, load losses and percentage impedance.
10.3 If the bidder quotes lower values of losses than the CPRIs measured losses, he has to prove the same by
conducting the Impulse & short Circuit tests at CPRI/ NABL Accredited laboratory along with measurement of no
load losses and load losses at his own cost in presence of Contractor/manufacturer authorized representative
without any financial liability to Employer
10.4 However, if the loss figures will exceed the stipulated values as per specification, the transformer(s) shall be
out rightly rejected.
11. VECTOR GROUP
11.1 The transformers shall be connected delta-star, in accordance with vector group reference Dyn11 of IEC 76/
IS-2026
11.2 The LV neutral shall be brought out to a terminal bushing, which shall be identical to the phase bushings in all
respects.
12. LOSSES
12.1 Transformers would be out rightly rejected if losses exceed the values indicated at clause-10 above.
13. FLUX DENSITY
The flux density at rated voltage & rated frequency shall not exceed. 1.5 Tesla. The transformer must be capable
of operating at 10% over voltage and at frequency of 48.5 Hz without saturation.
14. INSULATION LEVELS
The insulation levels as defined in IEC 76-C/ IS: 2026 Insulation levels and dielectric test shall apply as per Table 2:
HV
Winding
95
LV Winding
28
Not
Applicable
Bushings and terminals shall be adequate for the winding insulation tests and shall flash over externally before
puncture or internal failure can occur.
15. NOISE LEVEL
The average noise level of the transformers shall not exceed 51 db. The measurement shall be carried out in
accordance with IEC 551 at a distance of 300mm from the envelope of the transformer.
16. RADIO INFLUENCE VOLTAGE
The maximum radio influence voltage shall be 250 V, measured as specified in IEC 437.
The core and winding shall be capable of withstanding shocks during transport, installation and service. Provision
shall be made to prevent movement of the core and windings relative to the tank during these conditions and also
during short circuits.
17.1.6 The design shall avoid the presence of pockets which would prevent the complete emptying of the tank
through the drain valve. The core material offered in the tender to be checked for its correctness before core coil
assembly. For this, the tendered must ask for core and coil inspection before its tanking.
17.1.7 The laminations shall be free of all burrs and sharp projections. Each sheet shall have an insulting coating
resistant to the action of hot oil.
17.1.8 The insulation structure for the core to bolts and core to clamp plates shall be such as to withstand 2000 V
DC voltage for one minute.
17.1.9 The completed core and coil shall be so assembled that the axis and the plane of the outer surface of the
core assemble shall not deviate from the vertical plane by more than 25mm.
17.1.10 all steel sections used for supporting the core shall be thoroughly shot or sand blasted, after cutting,
drilling and welding.
17.1.11 the finally assembled core with all the clamping structures shall be free from deformation and shall not
vibrate during operation.
17.1.12
the core clamping structure shall be designed to minimize eddy current loss.
17.1.13
17.1.14
the core shall be carefully assembled and rigidly clamped to ensure adequate mechanical strength.
17.1.15
Oil ducts shall be provided, where necessary, to ensure adequate cooling inside the core. The welding
structure and major insulation shall not obstruct the free flow of oil through such ducts.
17.1.16T the design of magnetic circuit shall be such as to avoid static discharges, development of short circuit
paths within itself or to the earth clamping structure and production of flux component at right angle to the plane of
the lamination, which may cause local heating. The supporting framework of the cores shall be so designed as to
avoid the presence of pockets, which would prevent complete emptying of the tank through the drain valve or cause
trapping of air during filling.
17.1.17 the construction is to be of boltless core type. The core shall be provided with lugs suitable for lifting the
complete core and coil assembly. The core and coil assembly shall be so fixed in the tank that shifting will not occur
during transport or short circuits.
17.2 INTERNAL EARTHING
17.2.1
All internal metal parts of the transformer, with the exception of individual laminations and their
individual clamping plates shall be earthed.
17.2.2
The top clamping structure shall be connected to the tank by a copper strap. The bottom clamping
structure shall be earthed by one or more the following methods:
a) By connection through vertical tie-rods to the top structure.
b) By direct metal to metal contact with the tank base.
c) By a connection to the structure on the same side of the core as the main earth connection to the tank.
17.2.3 The magnetic circuit shall be connected to the clamping structure at one point only and this shall be
brought out of the top cover of the transformer tank through a suitably rated insulator. A disconnecting link shall be
provided on transformer tank to facilitate disconnections from ground for IR measurement purpose.
17.2.4 Coil clamping rings of metal at earth potential shall be connected to the adjacent core clamping structure
on the same side as the main earth connections.
17.3
Windings
17.3.1 Winding shall be subjected to a shrinking and seasoning process, so that no further shrinkage occurs
during service. Adjustable devices shall be provided for taking up possible shrinkage in service.
17.3.2 All low voltage windings for use in the circular coil concentric winding shall be wound on a performed
insulating cylinder for mechanical protection of the winding in handling and placing around the core.
17.3.3 Winding shall not contain sharp bends which might damage the insulation or produce high dielectric
stresses. No strip conductor wound on edge shall have width exceeding six times the thickness.
17.3.4 The winding insulation shall be free from insulating compounds which are liable to soften, ooze out, shrink
or collapse. It shall be non catalytic and chemically inert in hot transformer oil during normal service.
17.3.5 The stacks of windings are to receive adequate shrinkage treatment.
17.3.6 The windings and connections are to be braced to withstand shocks during transport, switching, short
circuit or other transient conditions.
17.3.7 Permanent current carrying joints in the windings and leads shall be welded or brazed. Clamping bolts for
current carrying parts inside oil shall be made of oil resistant material which shall not be affected by acidity in the oil
steel bolts, if used, shall be suitably treated.
17.3.8 Terminals of all windings shall be brought out of the tank through bushings for external connections.
17.3.9 The windings shall be uniformly insulated and the L.V neutral points shall be insulated for full voltage.
17.3.10 The completed core and coil assemble shall be dried in vacuum at not more than 0.5mm of mercury
absolute pressure and shall be immediately impregnated with oil after the drying process to ensure the elimination
of air and moisture within the insulation. Vacuum may be applied in either vacuum over or in the transformer tank.
17.3.11 The winding shall be so designed that all coil assembles of identical voltage ratings shall be
interchangeable and field repairs to the winding can be made readily without special equipment. The coils shall have
high dielectric strength.
17.3.12 Coils shall be made of continuous smooth high grade electrolytic copper or aluminium conductor, shaped
and braced to provide for expansion and contraction due to temperature changes.
17.3.13 Adequate barriers shall be provided between coils and core and between high and low voltage coil. End
turn shall have additional protection against abnormal line disturbances.
17.3.14 The insulation of winding shall be designed to withstand voltage stress arising from surge in transmission
lines due to atmospheric or transient conditions caused by switching etc
17.3.15 Tapping shall not be brought out from inside the coil or from intermediate turns and shall be so arranged
as to preserve as far as possible magnetic balance of transformer at all voltage ratios.
17.3.16
Magnitude of impulse surges transferred from HV to LV windings by electromagnetic induction and
capacitance coupling shall be limited to BIL of LV winding.
17.3.17 The winding conductor shall be of Aluminum. The current density shall not exceed 1.6 Amp/ mm for
aluminium at normal full load current.
255 mm
Phase to earth
140 mm
18.1.3 The 11 KV bushings of transformers shall be provided with a bi-metallic terminal connector or suitable
device to receive 35100 mm AAAC or ACSR conductor directly without any bi-metallic action.
18.1.4 The dia of HT bushing stud should not be less than 12.5 mm. The secondary bushings of transformers shall
be fitted with non ferrous threaded terminals of dia not less than 20 mm. With the exception of brass the terminals
shall be protected from atmospheric deterioration by suitable tinning or by some other approved coating.
18.1.5 The terminals are to be supplied with one 16mm bolt, one conic spring washer, one matching flat washer,
one nut and one lock nut for each hole in the terminal plate.
The tendered shall state the top oil temperature at which the tank internal pressure shall reach the value of
100 kN/m and the value of steady load which will result in this top oil temperature with an ambient temperature of
45C.
Adequate space shall be provided at the bottom of the tank for collection of sediments.
19.2
Transformer tanks of all types shall be designed so that the completed transformer can be lifted and
transported without permanent deformation or oil leakage. Stiffeners provided on all the four side walls for rigidity
should be so designed that there is no accumulation of water.
19.3
The Tank shall be of rectangular shape with round edges fabricated from tested quality mild steel plates
with minimum thickness of 3.15 mm. for the side walls while top cover and the bottom plate of the tank shall have a
minimum thickness of 5 mm. The transformer tank and the top cover shall be designed in such a manner as to leave
no external pockets in which water can log, or any internal pocket where air/ gas can accumulate.
Edge of Top cover should be bend downwards so as to avoid water through cover plate gasket. The width of the
bend plate shall be 25mm minimum.
19.4
All sealing washers / gaskets shall be made of oil and heat resistant neoprene rubber or neoprene bonded
cork seals suitable for temperature as stipulated in this specification. Surfaces at gasketted joints shall be such that
an even face is presented to gasket, thereby eliminating the necessity for the gasket to take up surface
irregularities.
19.5
All pipes, radiators, stiffeners or corrugations which are welded to the tank wall shall be welded externally
and shall be double welded wherever possible. All welds shall be stress relieved.
19.6
The transformer tank shall be complete with all accessories, lifting lugs etc. and shall be designed to allow
the complete transformer filled with oil to be lifted by crane or jacks without risk of any damage and can be
transported by Rail/ Road without straining any joints and without causing any leakage of oil.
19.7
19.8 The height of the tank shall be such that minimum vertical clearance up to the top cover plate of 80mm is
achieved from the top of the yoke.
20 PRESSURE RELIEF DEVICES
Transformers shall be fitted with a pressure relief device in the form of explosion vent.
The tendered shall state the pressure at which it is designed to operate.
22.2 All transformers shall be fitted with a silica gel breather of weatherproof design at a convenient height with oil
seal at the bottom, draw in plug and filling holes with covers to isolate the silica gel from the atmosphere. The
breather pipe should be connected at top of the conservator tank with two bends at right angles. The cover of the
main tank and bushings turrets shall be provided with air release plug to enable the trapped air to be released.
23 FITTINGS AND ACCESSORIES
23.1 The following standard fittings and accessories shall be provided :
A magnetic oil level gauge 100 mm dia for all transformers indicating three position ( 3) of oil - minimum. 5C,
30C and 98C.
Set of Radiators.
Conservator Tank
Bi-metallic terminals on the bushings for connection with over head ACSR/ AAAC conductor. The Specification and
brief details of the salient features of these terminals should be stated.
24 RATING AND CONNECTION PLATE
Each transformer shall be provided with a rating plate of weatherproof material showing the following items indelibly
marked :
type of transformer
standard to which it is manufactured (preferably IEC 76)
manufacturers name
transformer serial number
year of manufacture
rated frequency in Hz (50)
rated voltages in KV (11/0.433)
number of phases (3)
rated power in KVA
type of cooling (ONAN)
rated currents in A
vector group symbol (Dyn11)
1.2/50s wave impulse voltage withstand level in KVp
power frequency withstand voltage in KV
impedance voltage at rated current and frequency in percentage at 75C at normal tap
Measured load loss in KW at rated current and at 75C at normal tap
Measured no-load loss in KW at rated voltage and rated frequency
continuous ambient temperature at which ratings apply in C
top oil and winding temperature rise at rated load in C
winding connection diagram
Total weight in kg with complete oil filled.
Total weight of the transformer without oil
Volume of oil in liters.
weight of core and windings in kg; and
Name of the employer
DISCOM, RGGVY-XII Plan Programme
The rating plate shall conform to the requirements of the section of Labels in this specification.
The requirement for the dry film thickness(DFT) of paint and the material to be used shall be as given below:
Sl.
No
Paint Type
1. Liquid paint
Area to be
painted
No of
Coats
Out side
01
30 micron
Out side
02
45 each
inside
01
35/10 micron
The colour of the finishing coat shall be Sky Blue/ Dark Admiral Gray/ Deep Green or any other colour as decided by
the Employer
28 SEALING GASKETS
All sealing washers / gaskets shall be made of oil and heat-resistant Nitrile/ Neoprene rubber/ synthetic rubber
bonded cork type RC-70C gaskets. Gaskets made of natural rubber or cork sheet are not permissible.
29 SUPRESSION OF HARMONICS
The transformer shall be designed with attention to the suppression of harmonic voltage, especially the third and
fifth.
30 TESTS
30.1 Routine Tests
Routine tests shall be carried out on all transformers and the tests shall be conducted in accordance with relevant
National/ International Standards. No sampling is allowed. In addition, tank tests in accordance with IS: 1180 shall
be carried out.
The following routine measurements and tests shall be carried out in presence of Employers authorized
representative(s):
a) Measurement of winding resistance.
b) Voltage ratio measurement and check of polarity and vector group. Bushing positions shall have permanent
markings at this stage of production;
c) Measurement of impedance voltages/ short circuit impedance at rated current and frequency
d) Measurement of load loss at full load and 75C;
e) Measurement of neutral unbalance current;
f) Temperature rise test on one transformer of each rating and measurement of hot resistance.
g) Measurement of no-load loss and no-load currents at full, 50%, 75%, 90%, 110%, 112.5% and 120% of rated
voltages;
h) Induced over voltage withstand test at 22KV for 60 sec on the HV windings;
i) Power frequency voltage withstand tests on HV and LV windings;
IEC 76/IS
2026/IS6600
IEC 76/IS 2026
IEC 551
IEC 76 / IS 2026
In accordance with IEC 76-3 the following sequence of impulses should have been/ should be applied;
30.2.2 If the type test report(s) submitted by the bidder do not fulfil the criteria, as stipulated in this technical
specification/ Bidders offer, the relevant type test(s) has/ have to be conducted by the Bidder at his own cost in
CPRI/ NABL accredited laboratory in the presence of employers representative(s) without any financial liability to
employer in the event of order placed on him.
30.2.3 The offeres transformer must be manufactured as per type tested design. A copy of type test certificate
must be submitted by manufacturer to Engineer/Employer. Transformers offered without type tested however
design shall not be accepted. In case manufacturer agrees for type testing of transformers, testing shall be
conducted on manufacturers cost. No claim shall be acceptable towards type testing. The transformers shall be
accepted only on acceptane of type testing results by employer.
30.2.4 The supplier shall furnish calculations in accordance with IS: 2026 to demonstrate the Thermal ability of
the transformers to withstand Short Circuit forces.
30.3
TEST VOLTAGE
Transformers shall be capable of withstanding the Power frequency and Impulse test voltage as described below:
Nominal
system voltage
Highest
System
voltage
Impulse Test
voltage
433 V (rms)
11 KV (rms)
Power
frequency
test
voltage
3 KV (rms)
12 KV (rms)
95 KV (Peak)
28 KV (rms)
The Supplier can offer for final inspection of the transformers subject to clearance of the stage inspection report by
the Employer.
33.2
The equipment shall successfully pass all the type tests and routine tests mentioned in the above Clauses
and those listed in the most recent edition of the standards given in Clause 2 of this specification.
33.3
The Employer reserves the right to reject an item of equipment if the test results do not comply with the
values specified or with the data given in the technical data schedule.
33.4
Routine tests shall be carried out by the Supplier at no extra charge at their works.
Adequate facility with calibrated testing equipment must be provided by the manufacturer free of cost to carry out
the tests. Type test certificates must be furnished along with the tender for reference of the Employer.
33.5
The Employer will witness all required tests. In order to facilitate this, the Supplier shall give the Employer
a minimum of 10 days notice that the materials are ready for testing.
33.6
The supplier shall submit to the Employer five signed copies of the test certificates, giving the results of the
tests as required. No materials shall be dispatched until material dispatch clearance is not issued by employer.
The test certificates must show the actual values obtained from the tests, in the units used in this specification, and
not merely confirm that the requirements have been met.
In the case of components for which specific type tests or routine tests are not given in this specification or in the
quoted standards in Clause 2, of this specification, The Supplier shall include a list of the tests normally required for
these components. All materials used in the Contract shall withstand and shall be certified to have satisfactorily
passed such tests.
33.7
The Employer at his discretion may re-confirm the Routine Test Results, particularly no load losses, load
losses and percentage impedance in his own laboratory or laboratory of his choice.
No inspection or lack of inspection or passing by the Employers Representative of equipment or materials whether
supplied by the Supplier or sub-supplier, shall relieve the Supplier from his liability to complete the contract works in
accordance with the contract or exonerate him from any of his guarantees.
However in case of future discrepancy, if any, after acceptance of equipments, observed at any stage during
guarantee period, the matter may be referred to Bureau of Energy Efficiency (B.E.E) for random testing of
equipments supplied. In such cases the observation of B.E.E shall be binding to both parties.
34 GUARANTEE
The supplier shall guarantee the following:
Satisfactory operation during the guarantee period from the date of commissioning, as per general terms
of condition of the contract.
The offered surface treatment shall protect the treated metal from corrosion for a period of not less than
five years from the date of delivery.
35 PACKING AND SHIPPING
35.1 Packing
The equipment and any supporting structures are to be transported adequately sealed against water ingress. All
accessories and spares shall be packed and securely clamped against movement in robust, wooden, non returnable
packing cases to ensure safe transit in rough terrain, cross country road conditions and in heavy rains from the
manufacturers works to the work sites/ earmarked destinations.
35.1.1 All accessories shall be carefully packed so that they are fully protected during transport and handling
operations and in storage. Internal surfaces of loose accessories shall be sealed by means of gaskets and blanking
off plates. All parts liable to rust shall receive an anti-rusting coat and shall be suitably protected. It shall be the
responsibility of the Supplier to make good any damage caused through insufficient packing. Each packing case shall
be indelibly marked, on two adjacent sides and on the top, with the following:
35.1.2 Each crate or container shall be marked clearly on the outside of the case to show TOP and BOTTOM
positions with appropriate signs to indicate where the mass is bearing and the correct positions for slings. All
component parts which are separately transported shall have permanent identification marks to facilitate correct
matching and assembly at site. Welded parts shall be marked before welding. Six copies of each packing list shall be
sent to the Employer prior to dispatching the equipment.
35.2 Transportation
The contractor shall be responsible for the transport of all plant and equipment supplied by them and for the
transport of all goods to the various specified destinations including all road clearance, offloading, warehousing and
insurance. The Supplier shall inform himself fully as to all relevant transport facilities and requirements and loading
gauges and ensure that the equipment as packed for transport conform to these limitations. The Supplier shall also
be responsible for verifying the access facilities specified.
The contractor shall be responsible for the transportation of all loads associated with the contract works and shall
take all reasonable steps to prevent any highways or bridges from being damaged by his traffic and shall select
routes, choose and use vehicles and restrict and distribute loads so that the risk of damage shall be avoided. The
Supplier shall immediately report to the Employer any claims made against the Supplier arising out of alleged
damage to a highway or bridge. All transport accessories, such as riding lugs, jacking pads or blanking off plates
shall become the property of the Employer.
All items of equipment shall be securely clamped against movement to ensure safe transit from the manufacturers
facilities to the specified destinations.
The Supplier shall advice the storage requirements for any plant and equipment that may be delivered to the
Employers stores. The Supplier shall be required to accept responsibility for the advice given in so far as these
arrangements may have a bearing on the behavior of the equipment in subsequent service.
36 Hazardous substances
The Supplier shall submit safety data sheets for all hazardous substances used with the equipment. The Supplier
shall give an assurance that there are no other substances classified as hazardous in the equipment supplied. No oil
shall be supplied or used at any stage of manufacture or test without a certificate acceptable to the Employer that it
has a PCB content of less than 2 mg/ kg. The Supplier shall accept responsibility for the disposal of such hazardous
substances, should any be found. The Supplier shall also be responsible for any injuries resulting from hazardous
substances due to non compliance with these requirements.
37 SUBMITTALS
37.1 Submittals required to employer is for approval of manufacturing of transformer
The
Type test certificates (short circuit withstand test and impulse test) of the offered transformers conducted
at CPRI/ or any NABL Accredited laboratory without which proposal will be out rightly rejected.
Sample routine test reports;
Detailed reference list of customers already using equipment offered along with performance certificates of
such equipment, during the last 3 (three) years with particular emphasis on units of similar design
and
rating;
Details of manufacturers quality assurance standards and programme and ISO 9000 series or equivalent
national certification;
Deviations from this specification. Only deviations approved in writing before award of contract shall be
accepted;
List of recommended spare parts and consumable items for five year of operation with prices and spare parts
catalogue with price list for future requirements.
37.2
37.2.1 Programme
Five copies of the programme for production and testing
37.2.2 Operation and Maintenance Instructions
A copy of installation and commissioning instructions and of the operation and maintenance instructions and
troubleshooting charts shall be supplied with each transformer.
37.3
Drawings
37.3.1 Within 15 days of award of contract, the Supplier shall submit 4 complete sets of drawings as detailed
below describing equipment in details. These drawings would be duly approved by the Employer after due
securitization and approval will be communicated within 15 days of receipt of these drawings. After the drawings are
approved and communicated to the supplier, he would supply ten complete sets of final drawings.
37.3.2 All detail drawings submitted for approval shall be to scale not less than 1:20. All important dimensions
shall be given and the material of which each part is to be constructed shall be indicated on the drawings. All
documents and drawings shall be submitted in accordance with the provisions of this specification and shall become
the property of the Employer.
37.3.3 All drawings and calculations, submitted to the Employer, shall be on international standard size paper,
either A0, A1, A2, A3 or A4. All such drawings and calculations shall be provided with a contract title block, which
shall include the name of the Employer and shall be assigned an unique project drawing number; the contract title
block and project numbering system shall be agreed with the Employer.
37.3.4 Script sizes and thickness of scripts and lines be selected so that if reduced by two stages the alphanumeric
characters and lines are still perfectly legible so as to facilitate microfilming.
37.3.5 For presentation of design drawings and circuit documents IEC Publication 617 or equivalent standards for
graphical symbols are to be followed. The drawing approval will be communicated within 15 days from the receipt of
drawings from the Bidder and for any delay in furnishing the drawings, if delivery period will be delayed, no
extension of delivery time will be granted due to this.
37.3.6 The following drawings for each item are to be submitted as part of this Contract.
a.
b.
c.
d.
e.
f. Schematic diagram showing the flow of oil in the cooling system as well as each limb and winding. Longitudinal
and cross- sectional views showing the duct sizes, cooling pipe etc. for transformer/ heat exchanger, drawn to
scale shall be furnished.
g. Large Scale drawings of high and low tension winding of the transformers showing the nature and
arrangements of insulation and terminal connection.
h.
Test Reports
38 FASTENERS
38.1 All bolts, studs, screw threads, pipe threads, bolt heads and nuts shall comply with the appropriate Indian
Standards for metric threads, or the technical equivalent.
38.2 Bolts or studs shall not be less than 6 mm in diameter except when used for small wiring terminals. All nuts
and pins shall be adequately locked.
38.3 Wherever possible, bolts shall be fitted in such a manner that in the event of failure of locking resulting in the
nuts working loose and falling off, the bolt will remain in position.
38.4 All ferrous bolts, nuts and washers placed in outdoor positions shall be of anti-corrosive materials except high
tensile steel bolts and spring washers which shall be electro galvanized to service condition stated elsewhere in the
Specification. Appropriate precautions shall be taken to prevent electrolytic action between dissimilar metals where
bolts are used on external horizontal surfaces and where water can collect, methods of preventing the ingress of
moisture to the threads shall be provided. Each bolt or stud shall project at least one thread but not more than
three threads through the nut, except when otherwise approved for terminal board studs or relay stems. If bolts
nuts are placed so that they are inaccessible by means of ordinary spanners, special spanners shall be provided. The
length of the screwed portion of the bolts shall be such that no screw thread may form part of a shear place
between members. Taper washers shall be provided where necessary. Protective washers of suitable material shall
be provided front and back on the securing screws.
39. LABELS
39.1 All apparatus shall be clearly labelled indicating, where necessary, its purpose and service positions. The
material of all labels and plates, their dimensions, legend and the method of printing shall be subject to approval of
the Employer. The surfaces of all labels and plates shall have a mat or satin finish to avoid dazzle from reflected
light. Colours shall be permanent and free from fading. Labels mounted on black surfaces shall have white lettering.
Danger plates shall have white lettering on a red background. All labels and plates for outdoor use shall be of incorrodible material. Where the use of enameled iron plates is approved, the whole surface including the back and
edges, shall be properly covered and resistant to corrosion. They shall be engraved in English. Name plates shall be
white with black engraved lettering and shall carry all the applicable information specified in the applicable items of
the Standards. No scratching, corrections or changes will be allowed on name plates.
39.2 Name plates shall be provided of white background with black engraved lettering carrying all the applicable
information specified in the standards and other details as required by the Employer. The name plate inscription and
the size and lettering shall be submitted to the Employer for approval.
40.PROFORMA FOR STAGE INSPECTION OF DISTRIBUTION TRANSFORMERS
(A)
GENERAL INFORMATION:
1. Name of Firm :
2. Order No and Date :
3. Rating wise quantity offered :
4. Details of offer
(a) Rating
(b) Quantity
(c) Serial Numbers
5. Details of last stage inspected lot :
(a) Total quantity inspected
(b) Serial Numbers
(c) Date of stage inspection
(d) Quantity offered for final inspection of
6.
(A) Inspection of BEE 3 Star Level/ Embossing / Punching requirement: whether satisfies the Specification: deviation
if any to be mentioned
(B) Availability of material for offered quantity
(C) Position of manufacturing stage of the offered
QUANTITY :
(a) Complete tanked assembly
(b) Core and coil assembly ready
(c) Core assembled
(d) Coils ready for assembly
(i) HV Coils
(ii) LV Coils
NOTE:
(i) A quantity if more than 100 nos shall not be entertained for stage inspection
(ii) The stage inspection shall be carried out in case:(a) At Least 25% quantity offered has been tanked and
(b) Core coil assembly of further at least 30% of the quantity offered has been completed.
(iii) Quantity offered for stage inspection should be offered for final inspection within 15 days from the date of
issuance of clearance for stage inspection, otherwise stage inspection already cleared shall be liable for cancellation.
A. CAPACITOR BANKS
3.
TEMPERATURE CATEGORY
The capacitor shall be suitable for upper limit of temperature category 500C as per IS:2834.
4. RATED VOLTAGE
4.1 The rated voltage of the 3-phase capacitor banks shall be12KV(phase-to-phase) and the individual capacitor
units shall be rated for 12/3 KV.
4.2 Supplier shall make extra allowance for voltage rise due to use of 6% reactors wherever provided, for
which necessary details will be provided by the purchaser.
5. RATED OUTPUT
5.1
The ratedout put of 3-phase capacitor banks shall be 600 KVAR and 1200 KVAR at the rated voltage of
12 KV intended for use on power transformers of 3.15 MVA and 5 MVA (see Clause 14.3).
5.2 The standard basic unit rating of capacitors (single phase) shall be 200 KVAR. The units shall be
connected in star formation with floating neutral.
6. PERMISSIBLE OVER LOADS
For capacitors covered in this specification, the maximum permissible overloads with regard to voltage,
current and reactive output shall not exceed the limits specified in IS:2834.
7. POWER LOSS
The power loss in capacitors shall not exceed 0.2 watt/KVAR (subject to a tolerance of +10%).
8. DISCHARGE DEVICE
Suitable discharge device shall be connected across the capacitor unit in accordance with the provision
of IS:2834.
The discharge device shall reduce the residual voltage from the crest value of the rated voltage to 50V
or less within 5 minutes after the capacitor is disconnected from the source of supply.
9. EARTHING CONNECTIONS
The container of each capacitor unit shall be provided with suitable earthing terminal clearly marked with
"Earth" Symbol.
AX
GENERAL REQUIREMENTS
11.1
The capacitors shall be of non-PCB type, using polypropylene film as the dielectric.
11.2
Complete mounting brackets supporting insulators and all other components for formation of capacitor
bank racks shall be supplied along with the capacitor units. Necessary foundation bolts/nuts shall
also be supplied.
11.3
The outside of the capacitor container and other structures should have smooth and tidy look and
should be coated with the weather-proof, corrosion-resistant paint of white or light grey shade.
12.
MARKING
The capacitor units shall be provided with a rating plate and terminal markings as stipulated in
IS:2834.
13.
TESTS
The switched capacitors shall be subjected to all the type, routine and acceptance tests in
accordance with IS:2834. In addition, Endurance Test as per IEC 871-2, 1981 shall be carried out
as a type test. (This test is under consideration for adoption by BIS).
B.
The Automatic Control Unit shall be provided inside the control room to continuously monitor total load
KVAR on secondary side of the transformer and shall automatically switch ON or switch OFF the
capacitor
banks
through
the
operation of 11KV Capacitor Switch in accordance
with
the parameters given in clause 14.3. Overriding provision shall also be made for electrical switching
ON or OFF of the capacitor switch by the operator from the ACU panel.
14.2
In the case of 3.15 MVA transformer, the capacitor banks will be controlled by two 11KV automatic
capacitor switches each controlling a 600 KVAR bank. For 5 MVA transformer, the capacitor banks will
be controlled by two 11KV automatic switches; the 1st switch controlling 600 KVAR bank and the 2nd
switch controlling 1200 KVAR bank.
AX
The following scheme shall be adopted for automatic operation of 11KV capacitor switches/capacitor
banks:
S.No
1
1
Transformer
Capacity
Capacitor
Bank Size
2
1x3.15MVA
3
1200 KVAR
split into
600 KVAR
+
600 KVAR
4
600 KVAR
1200 KVAR
1300KVAR
(Switches-I&II ON)
1800 KVAR
split into
600 KVAR
+
1200 KVAR
600 KVAR
700 KVAR(Switch-I
ON, Switch-II OFF)
1x5 MVA
Capacity
to be
Switched
on
1200 KVAR
1800 KVAR
Status of
capacitor
switches when
load KVAR on
transformer
reaches
5
700 KVAR (Switch-I
ON, Switch-II OFF)
1300 KVAR(Switch-I
OFF, Switch-II ON)
1900 KVAR
(Switches-I & II ON)
Status of
Capacitor
Switches when
load KVAR drops
to
6
600 KVAR (Switches
I & II OFF)
NOTE :
1.
For more than one transformer, a separate capacitor bank for each transformer shall be provided.
2.
The required 11KV CTs and PTs for measurement of Load KVAR are normally available at the Sub-station
and will not form part of the equipment to be supplied against this Specification.
CONTROLS
The automatic control unit shall instantly switch OFF the capacitor switch in the following
contingencies occurring in any of the phases :
i)
ii)
Power Transformer current imbalance (due to single phasing and for any other reasons) between any
of the two phases exceeding 20% of the lowest current of the 3-phases.
iii)
Current increases in any Capacitor unit by 30% above the rated current (only the relevant capacitor
switch will open).
AX
Current between any of the two phases of the capacitor bank differs more than 15% of the lowest
current of the 3-phases (only the relevant capacitor switch will open).
AX
SCOPE
This specification covers 11KV, 50Hz, out-door type automatic capacitor switches suitable for
switching capacitor banks of 600 KVAR and 1200 KVAR ratings or any other higher rating
specified.
23.
APPLICABLE STANDARDS
Unless otherwise stipulated in this specification the capacitor switch shall comply with the latest
version of IS:9920 (AC Switches for voltages above 1000V).
24.
RATED VOLTAGE
The rated voltage for the capacitor switch shall be 12KV. This represents the highest system
voltage corresponding to the nominal system voltage of 11KV.
25.
RATED CURRENT
The standard rated normal current shall be 200A.
26.
27.
28.
29.
30.
CONTROL SUPPLY
The control power for closing the switch shall be 230V single phase AC supply.
mechanism shall be suitable for a voltage variation of (+) 10% to (-) 20%.
31.
31.1
Type
The closing
The capacitor switches shall be of three phase construction and shall be suitable for remote
operation.
31.3
The capacitor switch shall be suitable for outdoor installation and shall have sealed weather proof type
construction.
AX
The capacitor switch shall be provided with a mechanical indicator to show whether the contact is in
open/closed position, locally, as also through indication on the ACU panel. Provision shall also be
made for manual closing and opening.
31.5
The metallic enclosure of the capacitor switch shall be provided with two earthing terminals
marked with the earth symbol.
31.6
The bushings provided on the switch shall have clamp type of terminals to directly receive aluminium
conductors
up
to
10mm
diameter in both horizontal
and
vertical
directions. The terminal arrangement shall be such as to avoid bimetallic corrosion.
32.
OPERATING MECHANISM
The operating mechanism shall be either solenoid or motor charged spring for which the control
supply shall be as per clause 30.
33.
34.
MARKING
The capacitor switch shall be provided with a legible and indelibly marked name plate with the
following :
a) Name of the manufacturer,
b) Type, designation and serial number.
c) Rated voltage and current.
d) Rated frequency.
e) Number of poles.
f)
35.
TESTS
The switch shall be subjected to the following tests in accordance with the IS:9920 (Part-IV).
35.1
Type Tests
a)
35.2
Tests to verify the insulation level, including withstand tests at power frequency voltages
on auxiliary equipment.
b)
Tests to prove that the temperature rise of any part does not exceed the specified values.
c)
Making and breaking tests including tests for the rated capacitive current
d)
Tests to prove the capability of the switch to carry the rated short time current.
e)
f)
Routine Tests
a) Power frequency voltage dry tests.
b) Voltage tests for auxiliary circuits.
c) Measurement of the resistance of the main circuits.
d) Tests to prove satisfactory operation.
AX
D. AUXILIARY EQUIPMENT
36. CURRENT TRANSFORMER
The current transformers of suitable current ratio and burden for measuring the capacitor current
shall form part of the equipment to be supplied. These CTs shall form either an integral part of
capacitor switches or may be of separate outdoor type.
The accuracy class for the purpose of measuring the current shall be 1.0.
37. HRC FUSES
Suitable outdoor type 11KV HRC fuses along with the mounting insulators etc. to provide proper
protection for the entire installation (and also HRC fuses for protection of individual capacitor
bank step where internal fuses for capacitors are not provided) shall form part of the equipment to
be supplied. The rupturing capacity of the fuses shall be 12.5 KA.
38. SURGE ARRESTERS
5 KA, 9 KV metal oxide surge arrestor, conforming to REC Specification of 11KV and 33 KV Metal
Oxide Lighting Arrester shall be used for the entire capacitor bank for each transformer and will form
part of the equipment to be supplied.
39. INRUSH SUPRESSION SERIES REACTOR (I SSR)
Suitable Inrush Suppression Series Reactors shall be provided on each capacitor Bank steps to limit
the inrush current due to parallel switching within a safe limits.
40. SCHEMATIC DIAGRAM
A Schematic diagram showing typical arrangement of 11KV automatically switched capacitor bank
for a 5 MVA transformer at 33/11 KV sub-station is given in the Annexure.
41. INSTALLATION OPERATION & MAINTENANCE
The supplier shall provide :
i)
Necessary manual on installation, operation and maintenance as also the schedule for routine testing
or check ups of all the equipment covered by the installation.
ii) List of recommended spares indicating prices and specialised test equipments required for routine
testing of the system.
42. GUIDANCE FOR PROCUREMENT
The entire equipment covered in this specification shall be covered as a single package to avoid
theproblem of mismatching and responsibility for maintenance etc.
43. WARRANTY
The supplier shall guarantee satisfactory performance of the complete capacitor bank installation for a
period of 18 months from the date of supply or 12 months from the date of commissioning,
whichever is earlier. During the warranty period, all repairs/replacements shall be carried out free of
cost.
AX
44. INSPECTION
All tests and inspection shall be made at the place of manufacture unless otherwise especially
agreed upon by the manufacturer and the purchaser at the time of purchase. The manufacturer shall
afford the inspector representing the purchaser, all reasonable facilities, without charge, to satisfy
him that the material being supplied is in accordance with the specification.
The purchaser has the right to get the tests carried out at his own cost by an independent agency,
whenever there is a dispute regarding the quality of supply.
AX
AX
INTRODUCTION
The section covers the specification of metal clad indoor vacuum type switchgear unit
with horizontal draw out circuit breaker as per IS 13118 [1991] / IEC 62271-100 or
latest amendment thereof.
1.1.2.
All the equipments shall be suitable for satisfactory operation in tropical climates and
dry dust laden atmosphere prevailing in the location where it shall be used against
the Contract. The equipment shall be able to with stand a wide range of
temperature variation in the required location.
1.1.3.
All the plant/apparatus/equipment supplied shall comply in all respect with the
requirement of Indian Electricity Act 2003 and Indian Electricity Rule 2003/IS and
latest amendment thereof during the execution of contract where-ever applicable.
1.2.
STANDARDS.
The circuit Breaker shall confirm to the latest revision with amendment available of
relevant standards, rules, and code. Some of which are listed herein for ready
reference.
Sl.
No.
1.
2.
3.
4.
5.
6.
7.
1.3.
1.3.1.
Standard
IEC62271-100
13118(1991)
IS-2705 (1992)
IS-3156 (1992)
IS-3231 (1987)
IS-1248
IS-375
Item
/IS-
IEC-60687/CBIP REPORT
NO-88 (JULY) 1996)
Switchgear
Current Transformer
Voltage Transformer
Relays
Ammeter & Voltmeter
Arrangement of Breakers Bus Bars
connection and auxiliary wiring.
Tri vector meter
main
CONSTRUCTION
The switchgear shall be of CRCA steel construction with sheet not less than 3mm
thickness for load bearing section and not less than 2 mm thickness for non-load
bearing and shall totally dust and vermin proof. However, if vendor has standardized
the thickness of enclosure other than above mentioned and it meets the performance
requirements and the design has been established through type test, the same shall
be accepted. The panels shall be rigid without using any external bracings. The
switchboard panels should comply with relevant IS/IEC and revision thereof and shall
be designed for easy operation maintenance and further extension. Bus bar,
metering circuit breaker chamber, cables and cable box chamber should have proper
access for maintenance, proper interlocks should be provided. All instruments shall
be non-draw out type and safe guard in every respect from damages and provided
with mechanical indicator of connection and disconnection position. The switchgear
BP
shall be completed with all necessary wiring fuses, auxiliary contacts terminal boards
etc.
1.3.2.
The arcing contacts and bus bar should be rated for 350 MVA for 3 seconds. Bus
bars shall be capable of connecting one switchgear panel to other through proper
insulated arrangement, which does not decrease the insulation strength of the bus
bar at the point of connection between two panels. The panels shall be modular in
design.
1.3.3.
The breakers should be able to be drawn out in horizontal position at ground level
[with vertical/horizontal isolation] when breaker is drawn out in horizontal position
none of the live components inside the 11 KV switchgear panel should be accessible.
The safety shutters shall be robust and shall automatically cover the live components
when the breaker is drawn out. The switchgear shall have complete interlocking
arrangements at the fully inserted and fully drawn out and test positions.
Withdrawal of the breaker should not be possible in ON position, it should not be
possible to close the circuit breaker in service unless the entire auxiliary and control
circuit are connected.
1.3.4.
Breaker should have three distinct positions inside the cubical; i.e. service, test and
isolated.
1.3.5.
Built-in/separate trolley mounted earthing switches for incomer and outgoing shall be
provided.
1.3.6.
All the high voltage compartments must have pressure discharge flap for the exit of
gas due to internal are to insure operator safety. All the HV compartment design
ensures conformity to IEC-60298 and must be type tasted for Internal Arc Test.
1.4.
1.4.1.
Bus bars and all other electrical connection between various components shall be
made of electrolytic copper of rectangular cross sections. The bus bars section shall
be ample capacity to carry the rated current of minimum 1250 Amp continuously
without excessive heating and for adequately meeting the thermal and dynamic
stresses in the case of short circuit in the system up to full MVA rating specified in
Para 3.2 above.
1.4.2.
All bus bars connections shall be firmly and rigidly mounted on suitable insulators to
withstand short circuit stresses and vibrations.
1.4.3.
Adequate clearance between 11 KV point and earth and between phase shall be
provided to ensure safety as per provision in Indian Electricity Rule 2003 and its
amendment thereof and also in accordance with the relevant Indian standard
specification and the same shall be capable of withstanding the specified high
voltage tests as per IS-13118/ IEC 62271-100 and amendment thereof.
1.4.4.
Sharp edges and bends either in the bus bars or bus bar connections shall be
avoided as far as possible. Wherever such bends or edges are un-avoidable, suitable
compound or any other insulation shall be supplied to prevent local ionization and
consequent flashover.
BP
1.5.
CIRCUIT BREAKER
1.5.1.
The vacuum circuit breaker shall be draw out type suitable for installation in the
switchgear cubicles (indoor). The breaker shall comply with IS-13118 (1991)/ IEC
62271-100 and latest amendment thereof. Construction of breaker shall be such
that the points, which require frequent maintenance, shall be easily accessible.
1.5.2.
The circuit breakers shall be spring operated, motor/manually charging of the spring
feature, manually released. VCB shall have spring closing mechanism for 3 pole
simultaneous operation. The speed of closing operation shall be independent of the
speed of hand operating level. The indication device shall show the OPEN and
CLOSE position of breaker visible from the front of cubical.
1.5.3.
The breakers shall be capable of making and breaking the short time current in
accordance with the requirement of IS 13118(1991)/ IEC 62271-100 and latest
amendment thereof and shall have three phase rupturing capacity of 350MVA for 3
second at 11 KV. The continuous current rating of breaker shall not be less than
1250 Amp for all items. The total break/make time shall be not more than 4 cycles
for break and 6 cycles for make time for all breakers.
1.5.4.
The vacuum circuit breakers shall ensure high speed extinction and adequate control
of pressure during breaking of current and also designed to limit excessive over
voltages.
1.5.5.
1.5.6.
Vacuum Circuit Breaker shall have completely sealed interrupting units for
interruption of arc inside the vacuum. The vacuum bottle sealed for life shall be
provided with contact wear indicator.
Vacuum interrupter should have an expected life of 10000 operations at rated
current and should be capable for operating more than 100 times at rated short
circuit current.
Vacuum interrupter technical data particularly provided by the manufacturer should
also be provided with Bid.
1.5.7.
1.5.8.
1.6.
PROTECTION RELAYS
1.6.1.
1.6.2.
The protective relays mounted on the panels shall be of the draw out type. The
relays must be capable of resetting with out necessity of opening the case. The
relays shall be provided with flag indicators. Each functional element of a relay shall
be provided with its own flag indicator to enable the type of fault condition to the
identified.
BP
1.6.3.
1.6.4.
High set instantaneous element of low transient over reach not exceeding 5%
should be incorporated in the O/C and Earth Fault relays for all the outgoing feeder
panels capable of adjusting the setting from about 5 to 20 times normal rating in the
O/C relays and 2 to 8 times in Earth Fault relays.
1.6.5.
During detail engineering provision for shunt trip or series trip relays shall be decided
by Employer for which contractor should not have any objection. Further, in this
case, the series trip relays auxiliary unit contracts in the tripping circuit should be
designed to handle current up to 150 Amp. and like wise trip coil voltage which
appears across open contact of the series-tripping unit, be limited to 150 volts.
1.6.6.
With CTs used as per Para 7.1 and taking into account the trip coil impedance of
breaker with the plunger DOWN and with plunger UP position, the VA burden of
relays offered etc. should be duly coordinated, so that the protection operates
without errors at fault current corresponding to the fault MVA of 350 for all the tap
position of the relays and the values of the impedance of the choke and resistance
which may be required should also be determined and incorporated.
1.6.7.
The protective relays shall withstand 20 times the maximum current for 3 second on
any tap setting. The over shoot time on removal of current setting shall not be
greater than 0.05 seconds.
1.7.
1.7.1.
CURRENT TRANSFORMERS:
The requirement of ratio, VA capacity, class or accuracy, limit factor etc. for resin
cast CTs installed in different type of units are tabulated below:
Item
Core/CT
Ratio
Incoming
Panel
Protection
600300/1A
Protection
600300/5A
600300/5A
600300/5A
600300/5A
Metering
Outgoing
Panel
Protection
Metering
VA
Burden
(min)
15
15
Knee
Point
Voltage
300
at
600/1A
tap
..
2.5
..
15
2.5
..
ALF
Class
of
accuracy
10
PS
10
5P
0.5
10
5P
0.5
BP
1.7.2.
Short time rating of CTs shall be 18.4 KA for 3 second. CTs shall be double core and
dual ratio. Saturation factor for metering core shall not exceed 2.5.
1.7.3.
The designed accuracy should be available even at the lowest ratios and all CTs shall
withstand fault current corresponding to 350 MVA for 3 sec.
1.7.4.
The secondary terminal of the current transformers shall be such that effective and
firm wire terminations are possible. Shorting links of adequate capacity shall be
provided at the terminal blocks for sorting of the leads from secondary terminals of
current transformers. The secondary terminal of the CTs shall be earthed at one
point.
1.7.5.
The secondary winding resistance of CTs shall be as low as possible but not greater
than 0.2 ohms per 100 turns.
1.7.6.
CTs shall confirm to IS 2705 with latest amendment, if any in all respect and will be
subjected to all routine and type test specified in the IS.
1.8.
1.8.1.
Two nos, brass-wiping glands for each incomer and one no. Brass wiping gland for
each outgoing panel of adequate dimension for XLPE cable of 3 cores up to 400 sq.
mm size shall be supplied along with panels. For bus coupler no cable glands should
be provided.
1.8.2.
Suitable cable boxes as per requirement of cable shall be arranged by the purchaser
at his end. The panel shall however provide a flat of size 50X6 mm 2 with suitable
clamp made of 50X6 mm2 flat along with Nuts Bolts and Washers for holding the
cable boxes. The flat should be fitted at a suitable height with allotted arrangement
for adjustment of height from 300mm to 500mm at site. The clamp and flat shall
have suitable stud type arrangement for earthing cable and cable box.
1.8.3.
All control cable/wire entries shall be by means of suitable cable glands, such glands
shall be of brass and tinned.
1.9.
AUXILIARY/CONTROL WIRING
All the secondary wiring in the panel shall have high quality PVC insulation and the
same shall have conductor size of not less than 2.5 mm 2 of copper Colours of the
secondary/auxiliary wiring should confirm to IS 375/1963 and latest amendment
thereof if any. All wiring shall be neatly run and group of wiring shall be securely
fixed by clips so that wiring can be checked without necessity of removing the
clamps. Wiring between fixed and moving portion of the panel shall be run in
flexible tubes and the same shall be so mounted to avoid any damage to them due
to mechanical movements. Ferrules with number shall be provided on both end of
the wiring.
BP
1.10.
MARKING OF PARTS
For facilitating the erection, the several parts of the plant and equipment shall be
suitably marked.
1.11.
1.12.
PAINTING
All metallic surface [except enameled and bright parts] exposed to weather shall be
given suitable primer coat and two coats of first quality paint of approved colour. The
supplier shall also supply adequate quantities of paints, Varnish etc. for use of finished
cost and for use of patching up any scratches received during transport, handling
erection testing and commissioning.
Instead of above proper powder coating after proper pre treatment is acceptable and
in that case earlier condition will not applicable.
1.13.
1.13.1.
ITEM NO. 1 INCOMING PANELS RATING; 1250 AMP WITH CT RATIO 600300/5A or 600-300/1A
Each unit shall have the fittings and equipments as follows:
BP
1 No steel totally enclosed, fully interlocked, indoor industrial pattern, metal clad,
horizontal draw out, vertical/horizontal isolation floor mounting switch unit complete with
transportation truck having integral mechanism and all necessary supports each
equipped as under:
1 No. Set of isolating plugs and sockets [6 nos. rated for 1250 Amp. With
automatic safety shutters and pad locking arrangements. Facilities shall be
provided for proper opening of the safety shutter for cleaning, inspection and
testing.
1 No. 1250 Amp triple pole VCB fitted with isolating sockets, spring operated,
manually as well motor charged, manually/ electrically released spring closing
mechanism with mechanical ON/OFF indicators suitable for a rupturing capacity
of not less than 350 MVA at 11 kV for 3 seconds and fitted with one set of direct
acting trip coils suitable for operation with AC series trip relays.
1 No. Auxiliary switch with minimum four normally closed and four normally
opened contacts. The contact terminals shall be brought out and terminated at
Terminal Board irrespective of whether terminals are used or not.
3 Nos. 600-300/5-5 A ratio double core resin cast current transformer of required
Accuracy, for protection and metering as per Para 4.7.1 of specification. Alternatively
single core dual ratio 5 nos., CTs [3 nos. for protection and 2 nos. for metering] shall
also be acceptable.
1 No. Ammeter digital static ammeter suitably scaled and must suit CT ratio.
1 No. 3 phase resin cast, draw out type bus bar connected potential transformers of
Ratio 11000/110 volts class 0.5 accuracy having minimum 50 VA output per phase to
operate the A.C. static H.T. Tri-vector meter, voltmeter etc. and complete with HT fuse
and LT MCB with monitoring contacts.
1 No. Voltmeter round flush pattern digital static suitably scaled to suit the PT ratio.
1 No. 3 way and off voltmeter selector switch for reading the voltage between any two
phases on the voltmeter.
1 No. static digital Tri vector energy meter suitable for three phase 3 wire unbalanced load and CT, PT, ratio mentioned above, 0.5 accuracy class with load,
survey and TOD/Tariff and MRI facility. TVM shall be as specification attached
with this specification.
1 No. Non directional adjustable IDMT series trip O/C relay with definite minimum 3
seconds at 10 times plug setting. The relay shall be arranged for over current protection
with setting from 50 to 200% of 5A on all three over current elements mounted in draw
out case tropicalised with flag indicator.
BP
1 No. set of indicating lamps operating at 230V AC single phase one coloured RED and
other GREEN to show the closed or open position of circuit breaker.
1 No. 80 watts continuously rated tubular/strip type heater with manual ON/OFF switch
working on 230 VAC single phase supply.
1 No. set of copper bus bars of not less than 1250 Amp. Continuous rating.
1 No. multi way plug box for secondary wiring between the fix and moving glands.
1 No. set of independently operated automatic shutters for bus bar cable and voltage
transformers orifices, which shall be clearly leveled and individually pad-locked.
1 No. Sheet instruments panel mounted on the front of the unit with hinged access
doors and totally enclosed wiring terminals mounted there.
1 No. Complete set of self contained inter connectors, foundation bolts, fine Wiring,
wiring terminals board, sundries to complete the unit.
1.13.2.
1.13.3.
CLARIFICATION
The total requirement of CTs for incomer of ratio 600-300/5A is as follows:
1.13.4.
3 CTs one for each phase of ratio 600-300/5A to connect to 3 nos., O/C relays.
2 nos. CTs one on R phase and other on B phase of ratio 600-300/5 A for
metering.
ITEM NO. 2 OUTGOING FEEDER PANEL WITH CT RATIO 600-300 /5A
The fittings and mountings shall be similar to item no. 1 above except the following:
The voltage transformers voltmeter and voltmeter selector switch shall be deleted.
BP
1.13.5.
1 no. non directional triple pole adjustable IDMT, combined O/C and E/F [3 no. O/C and
1 no. E/F] AC series trip relay with instantaneous high set trip feature of low transient
over reach not exceeding 5% with definite minimum 3 seconds at 10 times plug setting.
The relay shall be arranged for over current protection with setting 30-120 % of 5 Amp.
And for earth fault protection with setting 10-40 % mounted on a draw out case
tropicalised with flag indicators. High set element of O/C shall have setting range of 5 to
20 times the rated current and the E/F elements shall be 2 to 8 times of rated current.
1 No. All steel totally enclosed fully interlocked indoor industrial pattern, metal clad
horizontal draw out, horizontal/vertical isolation, floor mounting switch unit complete
with transportation truck having integral circuit breaker mechanism and all necessary
supports each equipped as under:
1 No. Set of isolating plug and sockets [6 nos. Rated for 1250 Amp.] with automatic
safety shutters and pad locking arrangement. Facilities shall be provided for proper
opening of the safety shutter for cleaning inspection and testing.
1 No. 1250 Amp. Triple pole VCB fitted with isolating sockets, spring operated, manually
charged, and manually released spring closing mechanism with mechanical ON/OFF
indicators suitable for a rupturing capacity of not less than 350 MVA at 11 kV for 3
second.
1 No. A set of Red and Green pigmy lamps for indicating opened and closed position of
breaker.
1 No. 3 way auxiliary switch with 4 normally closed and eight normally open contacts.
1 No. 80 watt. 230 VAC heaters with 6 Amp. Rotary cam switch.
1 No. Bus bar chamber with 1250 A rated copper Bus Bars.
1 No. A set of self aligning horizontal/vertical isolation type auxiliary plug and sockets.
1 No. Sheet steel instrument panel mounted on the front of the unit with hinged across
doors and totally enclosed wiring terminals mounted there.
The panel shall be without any metering protection CTs, cable box, series trip coils, and
relays.
The HT chambers [adopter chamber] will be gasketed to make it vermin proof. The gasket
shall be as specified in Section-I(Introduction and general technical requirements).
BP
NOTE Separate spring charging handle shall be provided and supplied with each set of the VCB.
1.14.
ANNUNCIATION SYSTEM
Alarm annunciation system shall be provided in the control board by means of visual
and audible alarm in order to draw the attention of the operator to the abnormal
operating conditions or the operation of some protective devices. The annunciation
equipment shall be suitable for operation on the voltages specified in this specification
i.e. 30 Volt DC for new substation or as existing DC supply system of the utility (This
shall be verified by the successful bidder before submission of the drawing for
approval).
Audible annunciation for the failure of DC supply to the annunciation system shall be
provided and this annunciation shall operate on 240 Volts AC supply. On failure of the
DC to the annunciation system for more than 2 or 3 seconds. (adjustable setting), a
bell shall sound. A separate push button shall be provided for the cancellation of this
audible alarm alone but the facia window shall remain steadily lighted till the supply to
annunciation system is restored.
A separate voltage check relay shall be provided to monitor the failure of supply (240V
AC) to the scheme mentioned in Clause above. If the failure of supply exists for more
than 2 to 3 seconds. this relay shall initiate visual and audible annunciation. This
annunciation shall operate on Annunciation DC and buzzer shall sound.
1.15.
TESTS
The design of circuit breaker shall be proven through all the routine and in accordance
with IS 13118: 1991/IEC 56 and any amendment thereof. Photocopy of all the test
reports must be enclosed with the tender. Type test report earlier than 7 year from
the date of tender opening shall not be acceptable.
TYPE TESTS:
Each circuit breaker shall comply with requirements of type tests prescribed in IEC
publication No.56.
i.
ii.
iii. Capacitive current switching test: Cable charging current breaking test (Ur less than
or equal to 52 kV).
iv. Dielectric test i.e., power frequency withstand and impulse withstand test
v.
1.16.
COMMISSIONING CHECKS/TESTS
BP
10
After installation of panels, power and Control wiring and connect Contractor shall
perform commissioning checks. as listed below to proper operation of switchgear/panels
and correctness of all respects.
In addition the Contractor shall carry out all other checks and tests recommended by the
manufacturers.
1.16.1. GENERAL
i)
ii)
iii)
iv)
v)
vi)
vii)
viii)
ix)
Check for alignment of busbars with the insulators to ensure alignment and
fitness of insulators.
x)
xi)
xii)
i)
ii)
iii)
iv)
v)
BP
11
vi)
vii)
viii)
ix)
x)
xi)
xii)
xiii)
xiv)
i) Insulation resistance
ii) Ratio test on all cores.
iii) Polarity test
iv) Line connections as per connection diagram.
1.16.5.
CUBICLE WIRING
i)
ii)
BP
12
iii)
iv)
v)
vi)
Wire ducting.
vii)
1.16.6.
RELAYS
i)
ii)
iii)
Megger AC to DC terminals
iv)
v)
vi)
vii)
viii)
Relay settings.
1.16.7. METERS
i)
Check CT & VT connections with particular reference to their polarities for power type
meter.
BP
13
1.
21.1
General requirements:
The cable fault locator shall be capable of Locating / detecting all under-ground
transmission and distribution (Paper/Oilfield/PVC/XLPE) power cable faults up to
33kV network. The equipment should a properly wired and capable to detect open
circuit / short circuit / low-insulation / lashing / earth type cable faults in
underground cable. The equipment should be capable to deliver high output energy
that is necessary to ascertain easily to condition and break down faults in power
cables, joints, and terminations and long cable network. All constituent
equipments for cable fault locating set should be independent and
separate in nature for easy transportation.
A. Test Technique:
Test technique should be based on Differential Arc reflection so as to eliminate
unwanted and confusing reflections leaving only locations of fault. This differential
arc reflection technique should be possible without a need to use extra channel of
healthy phase.
Multi trace capturing (at least 10) should be possible with single shot of HV in Arc
reflection method and user should be able to select the best trace out of all stored
traces.
Fault conditioning (proof / burn and A.R.M) and fault pre-location techniques (TDR,
ARM and ICE) should be integrated into one package / unit for ease of use. Selection
of HV operations should be easy to use PLC control to avoid confusion.
Built in Arc reflection filter or Arc stabilization unit should be an inductive filter circuit
so that the output pulse has minimum attenuation in it.
The unit shall be versatile, capable supportive to locate faults in a wide variety of
power distribution cable networks through modern, integrated coupling for multiple
cable testing and fault locating technologies to reduce the fault locating time. The
unit shall be complete in all respects with all the necessary items,
accessories and test techniques and shall be ideal to ensure its maximum
B.
: Up to 50 memories.
: 60m to 30000m
: 1 % of full scale.
4.
5.
6.
7.
Modes
: TDR, Impulse Current, Secondary Impulse.
Power supply
: Internal rechargeable battery with external charger.
Ports
: RS232 port for Printer & PC
Accessories
:
Output Connection Cables for TDR application and other required connection cables,
Caring case & Operating Manual
9. Accessories
:
a. Ground Microphone , Connection leads, Special Headphone, Caring Sticks,
Charring case and Operating Manual
21.1.4 Cable Route Tracer System
The cable route tracer system shall be user friendly and suitable to locate the exact location
of underground cables and cables laid in PVC/GI along the busy roadside up to 10 km
maximum length, depth measurement up to 5 meter and ground survey of under-ground
cables to get quick accurate results.
Required Features:
Pinpointing active power lines and other utilities where AC is present
Operation in multiple Frequencies
Push button depth measurement up to 4 meters
High power at low frequency suitable to solve problems in multipoint grounding
situations
The cable route tracing system consisting of the following units:
1) Audio frequency Generator:
i)
Impedance
: from 0.5 to 1000 ohms selectable
ii)
Power output
: 1-2-4-8 watts selectable.
iii)
Output freq.
: 480Hz, 1.45 kHz & 9.82 kHz
iv)
Indications :
i. Meter Indication of related transmitted power
ii. Charging status of internal rechargeable battery.
v)
Power Supply
: 230 V, 50 Hz AC OR 12V 3.3Ah internal rechargeable
battery and Ext.12 V DC source
2) Audio frequency receiver:
i)
Receiving frequency
: Passive-50/60 Hz & Active- 480Hz, 1.45 kHz &
9.82 kHz
ii)
Gain
: up/down button for automatic centering
iii)
Wide band-band frequency
: 350 to 3000Hz.
iv)
Power Supply
: 1.5 x 8 AA size batteries for 12V DC.
v)
Accessories
:
Universal Search Coil, Transmitter coil, Identification coil, Special.
Head phones, Earth spikes, Connection leads, Mains supply cords,
Carrying case and Operating Manual
Particulars
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15.0
1.0
(FOR 33 KV and 11 KV LINES SUITABLE FOR USE WITH TONGUE & CLEVIS
DISC INSULATORS (CONVENTTIONAL TYPE FITTINGS)
1.1
1.
2.
3.
4.
5.
1.2
1.
2.
3.
4.
5.
1.3
1.
2.
3.
(A)
TEST CERTIFICATE
The following shall constitute the type tests for clamps.
Visual examination
Verification of dimensions
Slip strength tests
Ultimate strength tests
Galvanizing/Electroplating tests.
The type tests are intended to prove the general qualities and design of a given
type of insulator fittings. These tests should have not been conducted earlier,
than 5 years from the date of opening of tender.
ACCEPTANCE TESTS
The following shall constitute the acceptance tests:Visual examination tests
Verification of dimensions
Galvanizing/electroplating test
Mechanical Tests
Ultimate Strength test
ROUTINE TESTS
The following shall constitute the routine tests:Visual examination tests
Mechanical routine tests on Conductor Tension clamp only
The routine tests will be carried out on each of insulator fittings to check
requirement which are likely to vary during production.
All the above three tests have been described in IS:2486 (Part-I)-1993.
Galvanizing tests for Hot Dip ferrous material shall be carried out in accordance
with IS:2633-1986 and satisfy the requirements in IS:4759-1984. Electrogalvanized ferrous fittings shall be checked in accordance with IS:1573-1986.
However one sample from each lot will be tested as per IS:4759-1984.
11KV STRAIN HARDWARE FITTINGS (T&C) TYPE
Each hardware fittings of the strain insulators shall comprise of:Hot dip galvanized cross arms & straps, properly profiled and suitable for use on
75/100 mm channel cross arms with 16mm dia hot dip galvanized bolts, nuts,
spring, washers, plain washer and 4mm dia split pin as per figures 26 of IS:2486
(Part-II)- 1984 and its latest amendment:
Spoil type clamp with clevis eye suitable for 33 KV and 11KV system for following
sizes of conductors:AAAC/ACSR
S.
Item
Stranding and Wire
Actual Area
No.
Dia of A.A. Alloy
i
AAA/ACSR
(37/2.88 mm)
200 Sq. mm
Conductor
(37/2.59 mm)
194.9 Sq mm
(Panther/Wolf)
ii
iii
AAA/ACSR
Conductor
(Dog)
ACSR Rabbit
(7/4.26 mm)
100 Sq. mm
(7/3.35 mm)
61.70 Sq mm
The ultimate strength of the clamp should not be less than 4500 Kg. The clamp
shall be made by process of Die-casting. The clamp made with process of sand
casting shall not be accepted.
All dimensions of cleaves and tongue connections shall be as per figure-25 of the
IS: 286 (Part-II) -1989 and its latest amendments.\
1.4
1.5
1.6
1.7
1.7.1
GENERAL REQUIREMENTS
All fittings shall be of same type and design manufactured under similar
conditions of production.
All forging and castings shall be of good finish and free from flaws and other
defects. The edges on the outside of fittings, such as the eye, clevis and holes,
shall be rounded. The clamp shall be manufactured by the process of die casting
or pressure die casting and shall be free from blow holes and other defects.
All ferrous fittings and the part other than those of stainless steel shall be
galvanized by the Hot Dip process. Only small fittings like, plain & spring
washers, nuts may be electroplated galvanized.
The nuts shall conform to property 4.8 of IS:1367 (Part-6)-1980.
The collar pins shall be provided with Galvanized Mild Steel Flat Washers in
addition to split pins.
The split pin to be used on the collar pin shall be of phosphor bronze conforming
to IS:7814-1975 or Stainless Steel conforming to IS:5577-1992 or brass
conforming to IS:410-1977 with a minimum hardness of 160 HV.
MARKING ON CLAMPS
The clamps shall have the following markings for their identification as per ISS.
Trade Mark of manufacturer
Please note that the marking should be legible and permanent (preferable die
caste).
PACKING
Strain clamps and related hardware shall be packed in double gunny bags or
wooden cases if deemed necessary. The gross weight of the packing shall not
exceed 50 Kg. Different fittings shall be packed in different bags or cases and
shall be complete with minor accessories fitted in place. All the nuts shall be
hand tightened over the bolt and screwed upto the farthest point with split pin in
position. The packing shall be fit to withstand rough handling during transit and
storage at destination.
CLAMPS & CONNECTORS
The conductor shall be AAA conductor Dog and Panther. The technical
parameters and other details of conductor.
CLAMPS & CONNECTORS:
Clamps & connectors shall conform to IS:5561. The clamps and connectors shall
be made of materials listed below:
For
connecting Aluminum alloy casting, conforming to designation
AAA/ACSR conductors
A6 of IS:617 and shall be tested for all tests as per
IS: 617
For
connecting
equipment
terminals
made of copper with
AAA/ACSR conductor
2.0
The hot dip galvanized MS Solid wire of sizes 5 mm, 4 mm and 3.15 mm
diameters shall conform to the relevant ISS specification, briefed here below: 2.1
MATERIAL
The Mild Steel wire shall have the chemical composition maximum sulphur .055%, Phosphorus 0.055%, Carbon 0.25%.
Zinc shall conform to grade Zen 98 specified in IS:209-1966 & IS: 4826-1979
with up to date amendments.
2.2
ZINC COATING
Zinc coating shall be in accordance with IS: 4826-1979 (Cl.4.2.1) for heavily
coated
hard quality.
2.3
GALVANIZING
Galvanizing shall be as per IS:2629-1985 and IS:4826-1979 with up to date
amendments.
2.4
UNIFORMITY OF ZINC COATING
Uniformity of Zinc coating shall be determined as per IS:2633-1972 with up to
date amendments.
2.5
TENSILE PROPERTIES
The tensile strength of the wire after, galvanizing shall be between 55-95
Kg/Sq.mm (heavily coated Hard as per IS:4826-1979 Tables-1) ensuring MS wire
Mechanical properties as per IS:28-1972 8.1 to 8.3.
2.6
FREEDOM FROM DEFECTS
To be ensured as per IS: 2629-1985 (Cl. 6.1) & IS:4826-1979 (Cl. 4.3) & with up
to date amendments.
2.7
TESTS
During the process of manufacture/ fabrication and finish all tests for chemical,
mechanical, galvanizing as per IS:280-1979, IS:1521-1972, IS:1755-1961,
IS:6745-1972 & IS:4826-1979 be carried out. Test certificate towards, chemical
composition (as per above) shall be submitted for each lot offered for inspection.
The following tests shall be conducted in presence of owners representative.
1. Visual Physical inspection and measurement of specified dimensions.
2. Coating test as per IS:1755-1961, IS:2629-1966, IS:2633-1972, IS:4826-1979
& IS: 6745-1972.
3. Adhesion test as per IS:1755-1961, IS:2629-1966, IS:2633-1972, IS:48261969 & 1979 IS:6745-1972.
4. Tensile strength and breaking load and elongation determined as per
IS:1521-1972 with up to date amendments.
2.8
PACKING
Packing shall be as per IS:280-1979 (Cl.3.1) and each coil shall be between 50100 Kg.
2.9
MARKING
As per IS:280-1972 (Cl.14.1 & 14.1.1) is required.
3.0
EARTHING
(AS PER IS:3043-1987)
3.1 Earthing shall generally be carried out in accordance with the requirements of
Indian Electricity Rules, 1956 amended from time to time and relevant
regulations under Electricity Supply Authority concerned. The drawings no
ADB/EZ- 33 & ADB/EZ- 34 for earthing are given in the bid document Vol. II.
3.2 In case of high and extra high voltages, the neutral points shall be earthed by not
less than two separate distinct connections with earth, each having its own
electrodes sub-station and will be earthed at any other point provided no
interference is caused by such earthing. If necessary, the neutral may be earthed
through suitable impedance.
3.3 As far as possible, all earth connections should be visible for inspection. Each
earthing system shall be so designed, that, the testing of individual earth
electrodes is possible. It is recommended that the value of any earth system
resistance shall be such as to conform to the degree of shock protection desired.
3.4 All materials, fittings etc., used in earthing shall conform to Indian Standard
Specifications, wherever they exist.
3.5 GENERAL REQUIREMENT AND PROCEDURES FOR EARTHING OF SUBSTATIONS:
3.5.1 The ground resistance for large sub-stations should not exceed 1 (one)
ohm, while in exceptional cases for small/remote sub-stations, a value up
to 2 (two) ohms may be allowed.
3.5.2 The joints/connections in the earthing system shall be welded only,
except the connections which require opening for testing/maintenance.
Such connections should be bolted tightly, using spring and ring washers
for proper contact pressure.
3.5.3 The MS flats to be provided for the horizontally laid earth grid should have
overlap welded joints, with length of welding at least twice the width of the
flat, e.g., 100 mm for 50 x 6 mm MS flats.
3.5.4 There should not be any dirt, grease, oil, enamel, paint or any such nonconductive coatings on the surfaces being joined or connected. Only
finished joints/ connections above ground may be provided with red oxide
or any other protective coating.
3.5.5 Underground earth electrodes and earth grid elements, when laid, should
have a clean metallic surface, free from paint, enamel, grease or any
such non-conductive coating.
3.5.6 As far as possible, all earth connections should be accessible for visual
inspection.
3.5.7 No cut-outs, links or switches other than linked switches arranged to
operate simultaneously on the earthed or earthed neutral conductor and
the live wire shall be inserted in the supply system.
3.5.8 The pipe/earth spikes electrodes should be driven into the ground to the
depth of 3 mtrs.
3.5.9 The strip electrodes, forming the horizontal grid, should be buried
underground to a minimum depth of 0.5 meter.
3.5.10
The path or earth wire should be out of normal reach of any person, as far
as possible.
3.5.11
In case of rocky top soil and sub-stratum, having very high resistivity, with
no scope of improvement by other means, the procedure given below
should be followed, strictly, carefully and invariably;
3.5.12
As least two bores of diameter little less than 40 mm, with a minimum
distance of 10 mtrs. between them, should be made in the ground at
suitable locations inside the S/s yard. The boring should be done until
soil sub-stratum rich in moisture and low in resistivity is encountered. GI
pipes of 40 dia should be descended in each bore, such that, the soil
mass around the pipes grips then tightly back filling of bores, if required,
with wet soil/clay may be done to ensure this condition. The GI pipes in
these deep bores should be interconnected with the main earthing grid of
the S/s through 50x6 mm MS flat. The GI pipes in the bores should also
be interconnected with each other. In extreme cases, the bore may have
to be made at remote locations i.e outside the S/s yard, with interconnections, through 50x6 mm flats, as explained before.
The procedures to be observed stringently for making connections and
joints between various elements of the earthing system are as follows:
i)
MS Flat to structure The MS flat should be welded to the
metallic portion (leg) of the structure after thoroughly cleaning the
surface to be welded.
ii)
GI wire to Structure The GI wire should be bolted to the
structure after making an eye formation and kept tight with the
help of spring and ring washers. Then, the entire arrangement
should be welded.
iii)
GI Wire to MS Flat The GI wire should be bolted and then
welded to MS Flat, as explained in sub-para of (i) above.
iv)
Earth spikes to MS Flat The earth spikes should be properly
welded to the MS flat.
v)
GI wire to GI pipe GI wire should be bolted to the GI pipe and
then welded, keeping in view the relevant precautions, mentioned
before.
should be in a separate pit, but in any case it must be connected with the
main mesh.
(iv) Power transformers: (a) The tank of the transformer shall be directly
connected to the main earth grid through 4/6 swg GI wire.
(b) The earthing of the neutral shall be by two separate distinct and direct
connections of stay wire7/8 or 7/10 swg may be used with proper lugs for
bushing
(c) The transformer track rails shall be connected to earth either
independently or by bounding to tank.
(v) Out door Kiosks, Circuit breakers: At least two legs preferably diagonally
opposite, of the supporting structure frame work of each circuit breaker unit
shall be connected to the earth grid, through 50x6 mm MS flats.
(vi) Fencing: All metal fencing wire-mesh and fencing poles (if metallic) where
provided shall be connected with the mesh.
(vii) CT/PT: (a) The base of the CT should be directly connected to the earth
grid through 4/6 swg GI wires.
(b) The base(neutral side) of the PTs should be directly connected to the
earth grid through 4/6 swg GI wires. Separate earth leads should be used for
PTs in each phase. The termination of leads on the PT neutral should be
bolted/clamped and not welded, to facilitate opening of the earth connection
for testing purposes.
(c) In addition, all bolted cover plates to which bushings are attached, within
the station grid area shall be connected to the earth grid.
3.7
Cables and supports: Armouring of armoured metal sheathed cables
within the station grid
area shall be connected to the earth grid.
3.8
Station transformer: The neutral earthing conductor used shall be 7/10 swg stay
wire.
3.9
The earthing pits (6 Nos) shall consist of 3 mtrs long 40 mm GI pipes (one no in
case of
black cotton soil and four no in case of rocky strata in each pit) buried
vertically inside the ground.
3.10
The dimensions of individual meshes in the grid may vary slightly according to
requirements of the lay-out, but the overall area (434 sq, mtrs) end to end
dimensions and
number of
meshes (13 Nos.) should be as per the drawing.
3.11
S.
No
1.
2.
3.
4.
5.
Schedule:
Particulars
50x6 mm MS Flat (2.36
kg/mtr)
Earth spike 3 mtr long 25 mm
dia
GI Pipe 40 mm Dia
GI wire 6 swg
Labour charges for complete
job
(For Black cotton soil)
Quantity
Kg
535.75
No
16
Mtr
Kg
LS
72
50
1 job
S.
No
1.
Particulars
Unit
Quantity
535.75
4.0
The hot dip galvanized MS Stranded wire of sizes 7/3.15 mm diameters shall
conform to the relevant ISS specification as detailed below:
4.1
MATERIAL
MS Wire used for each strand shall have the chemical composition (maximum)
Sulphur & Phosphorus 0.055% and Carbon 0.25%.
Zinc shall conform to grade Zen 98 specified ARE 209-1966 & ARE 2141-1968,
1979 with up to date amendments.
4.2
ZINC COATING
Zinc coating shall be in accordance with IS:4826-1979 (heavily coated hard
quality Grade-4 as per table-1) with up to date amendments.
4.3
GALVANISING
Hot dip galvanizing shall be as per IS:2629-1985 & IS:4826-1979 with up to date
amendments.
4.4
UNIFORMITY OF ZINC COATING
Uniformity of Zinc coating shall be determined as per IS:2633-1986 with up to
date amendments.
4.5
TENSILE PROPERTIES
Tensile properties of each strand ensuring MS Wire mechanical properties as per
IS:280-1972 (Cl.8.1 to 8.3) and after galvanizing each wire shall be of tensile
strength minimum 700N/mm2 (71 Kgs/mm2).
Tensile strength, bending load, lay & elongation of each wire and full strand shall
conform to IS: 2141-1968 & IS: 2141-1972 in the tensile grade given above).
4.6
CONSTRUCTION
Construction shall be as per IS: 2141-1979 (Cl. 5.3.1 to 5.3.3)
4.7
FREEDOM FROM DEFECTS
Freedom from defects be ensured as per IS: 2141-1979 (clause 4.1.6
respectively).
4.8
TESTS ON WIRE BEFORE MANUFACTURE
As per IS:2141-1979 (Col.7.1 to 7.2.2) shall be done.
4.9
PACKING
Each coil shall be between 50-100 Kgs. Packed as per IS: 2141-1968 (Cl. 9.1)
6594-1979 & 2141-1979 (Cl. 11).
4.10 MARKING
As per IS: 2141-1968 (Cl.8.1 to 8.1.1) and IS: 2141-1979 (Cl.10 & 10.1) is
required.
5.0
DANGER BOARD:
As per provisions of IE Rules 1956, Danger Notice plates in Hindi or English and,
in addition, in the local language with the sing of skull and bones is required to be
provided on power line supports and other installations.
This specification covers Danger Notice Plates to be displayed in accordance
with Rule No.35 of Indian Electricity Rules, 1956.
Unless otherwise modified in this specification, the Danger Notice Plates shall
comply with IS 2551-1982 or the latest version thereof.
Dimension: Two sizes of Danger Notice Plates as follows are to be installed at
each substation:
a)
For display at 11 KV installations
- 250 x 200mm
The corners of the plate shall be rounded off. All lettering shall be centrally
spaced. The dimensions of the letters, figures and their respective position shall
be as shown in figs. 1 to 4. The size of letters in the words in each language and
spacing between them shall be so chosen that these are uniformly written in the
space earmarked for them. Under Rule No. 35 of Indian Electricity Rules, 1956,
the owner of every medium, high and extra high voltage installation is required to
affix permanently in a conspicuous position a danger notice in Hindi or English
and, in addition, in the local language, with the sign of skull and bones. The type
and size of lettering to be done in Hindi is indicated in the specimen danger
notice plates shown in Fig. 2 and 4 and those in English are shown in Figs. 1 and
3 of REC specification. Adequate space has been provided in the specimen
danger notice plates for having the lettering in local language for the equivalent
of Danger. 11000 and Volts.
The plate shall be made from mild steel sheet of at least 1.6mm thick and
vitreous enameled white, with letters, figures and the conventional skull and
cross-bones in signal red color (refer IS:5-1978) on the front side. The rear side
of the plate shall also be enameled.
TESTS: The following tests shall be carried out:
i)
Visual examination as per IS:2551-1982
ii)
Dimensional check as per IS:2551-1982
iii)
Test for weather proof-ness as per IS:8709-1977 (or its latest version).
6.0
GI EARTHING PIPE :
3. When tested in accordance with IS:2329-1985 (Method for Bend test on Metallic
tubes) the finished tube shall be capable of with standing the bend test without
showing any sign of fracture or failure. Welded tubes shall be bent with the weld
at 90 degree to the plane of bending. The tubes shall not be filled for this test.
4. Galvanized tubes shall be capable of being bent cold without cracking of the
steel, through 90 degree round a former having a radius at the bottom of the
groove equal to 8 times the outside diameter of tube.
5. Flattening Test on Tubes above 50 mm Nominal Bore: Rings not less than 40
mm in length cut from the ends of selected tubes shall be flattered between
parallel plates with the weld, if any, at 90 degree (point of maximum bending) in
accordance with IS:2328-1983. No opening should occur by fracture in the weld
unless the distance between the plates is less than 75 percent of the original
outside diameter of the pipe and no cracks or breaks in the metal elsewhere than
in the weld shall occur, unless the distance between the plates is less than 60%
of the original outside diameter. The test rings may have the inner and outer
edges rounded.
6. GALVANIZING TEST:
Weight of zinc Coating: For tubes thickness upto 6 mm the minimum weight
of zinc coating, when determined on a 100 mm long test piece in accordance
with IS:4736-1986 shall be 400 gm/m2.
The weight of the coating expressed in gram/m2 shall be calculated by
dividing the total weight of the zinc (inside plus outside) by the total area
(inside plus outside) of the coated surface.
Test specimen for this test shall be cut approximately 100 mm in length from
opposite ends of the length of tubes selected for testing. Before cutting the
test specimen, 50 mm from both ends of the samples shall be discarded.
7. Free Bore Test:: A rod 230 mm long and of appropriate diameter shall be passed
through relevant nominal bore of the sample tubes to ensure a free bore.
8. Uniformity of Galvanized Coating: The galvanized coating when determined on a
100 mm long test piece [see V (a) (iii)] in accordance with IS:2633-1986 (Method
for testing uniformity of coating on zinc coated articles) shall with stand 4 one
minute dips.
WORKMANSHIP:
The tubes shall be cleanly finished and reasonably free from injurious defects.
They shall be reasonably straight, free from cracks, surface flaws, laminations,
and other defects, both internally and externally. The screw tubes and sockets
shall be clean and well-cut. The ends shall be cut cleanly and square with the
axis of tube.
MARKING
The medium class of tubes shall be distinguished by Blue colour bands, which
shall be applied before the tubes leave the manufacturers works. Tubes shall be
marked with the standard mark.
7.0
7.1
7.2
7.3
7.4
7.5
7.6
7.7
7.8
7.9
GALVANISED
All bolts and nuts shall conform to IS: 6639-1972 and shall be galvanized as per
IS:1367 (Part 13) & IS: 2629-1985. All bolts and nuts shall have hexagonal
heads, the heads being forged out of solid truly concentric, and square with the
shank, which must be perfectly straight.
Bolts up to M16 and having length up to 10 times the diameter of the bolt should
be manufactured by cold forging and thread rolling process to obtain good and
reliable mechanical properties and effective dimensional control. The shear
strength of bolt for 5.6 grade should be 310 MPA minimum as per IS:12427.
Bolts should be provided with washer face in accordance with IS:1363 (Part I)
to ensure proper bearing.
Nuts should be double chamfered as per the requirement of IS:1363 (Part III)1984. The manufacturer should ensure that nuts should not be over tapped
beyond 0.4 mm oversize on effective diameter for size up to M16.
Fully threaded bolts shall not be used. The length of the bolt shall be such that
the threaded portion shall not extend into the place of contact of the component
parts.
All bolts shall be threaded to take the full depth of the nuts and threaded enough
to permit the firm gripping of the component parts but no further. It shall be
ensured that the threaded portion of the bolt protruded not less than 3 mm and
not more than 8 mm when fully tightened.
All nuts shall fit and tight to the point where shank of the bolt connects to the
head. Flat washers and spring washers shall be provided wherever necessary
and shall be of positive lock type. Spring washers shall be electro-galvanized.
The thickness of washers shall conform to IS: 2016-1967.
The Bidder shall furnish bolt schedules giving thickness of components
connected the nut and the washer and the length of shank and the threaded
portion of bolts and size of holes and any other special details of this nature.
To obviate bending stress in bolt, it shall not connect aggregate thickness more
than three time its diameter. Bolts at the joints shall be so staggered that nuts
may be tightened with spanners without fouling.
To ensure effective in-process Quality control it is essential that the manufacturer
should have all the testing facilities for tests like weight of zinc coating, shear
strength, other testing facilities etc, in-house. The agency should also have
proper Quality Assurance system which should be in line with the requirement of
this specification and IS 14000 services Quality System standard.
Fasteners of grade higher than 8.8 are not to be used.
RAW MATERIALS
MS round 16mm / 12mm used shall be tested for quality as per IS:2062 Gr. A.
i.
SPECIFICATION OF FINISHED PRODUCTS:
The bolts & Nuts shall be ISI Marked Mild Steel of galvanized Grade B and
shall be round with hexagonal head.
The Bolts and Nuts shall be manufactured by Hot/Cold forging process neatly
and cleanly finished and shall have metric threads as per IS:4218-1967 with its
latest amendments.
The dimensions of the bolts & nuts and tolerances should conform to IS:1363
with their latest amendments in all respect. The eccentricity and angular errors of
various elements shall be within specified limits as per IS:1367-1967 with its
latest amendments. The bolts & nuts shall be free from forging and threading
defects such as cuts, splits, burns, bulging, taper, eccentricity, loose fill etc.
which may affect their serviceability.
The bolt heads and nuts shall be chamfered on one face only and other face
shall be machined made.
Mechanical property requirement of tester shall conform to IS:1367 (Part-III)1979 property class 4.6 for bolts & property class-5 for nuts as per IS:1367 (Part
VI) 1980.
The bolts & nuts shall be supplied in well-cleaned conditions and suitably
protected against corrosion in individual bags of 50 kgs.
ii.
ACCEPTANCE TESTS
The Supplier/Manufacturer shall furnish test certificate from his own/recognized
Govt. Laboratory giving the results of tests as per IS:1367 (Part-III) 1979 &
IS:1367 (Part-VI) -1980 witnessed by the Employers representative for each lot
under inspection. The test certificate shall be in respect of the following for all
sizes of both bolts & nuts as applicable given below:Dimensional particulars (Sampling in accordance with IS:2614 for both bolts &
nuts (tolerance as per drawing).
Tensile strength test on full size (for bolts min. 400 N/ Sq.mm and for Nuts. Proof
Stress (Min 610 N/Sq. mm).
Power load test on full size bolts and M-12-51400 N for 15 Sec.
(with Head soundness tests for bolts (no fracture).
Brinell hardness tests or Rockwell Hardness or Vickers Hardness tests for bolts
min-114 & max. 209 or min. 67 & max. 95 or min. 120 & max. 220 respectively.
For nuts Vickers Hardness min. 130 & max. 302.
Galvanizing test- mass of zinc
PRE-DESPATCH INSPECTION AND TEST
The contactor shall arrange to carryout acceptance tests in presence of
inspecting officer in his own laboratory. In case testing facilities are not available
at his works he will make necessary arrangements for carrying out these tests at
a Govt. recognized lab at his own expense(s) and will provide all testing
arrangement for Boards representative to witness the tests.
iii.
MARKINGS
On the bolt head, there shall be identification marking of the manufacturer as well
as property class 4.6. If possible property class 5 shall be marked on Nuts
also. Further ISI Mark shall be marked on Gunny Bags for proper
identifications.
.
SCOPE
8.1.1 The specification covers the design, manufacture and testing and delivery of ISI
marked 1100 volt grade, weather proof 3.5 core 16 sq.mm., with stranded aluminium
conductor, PVC insulated, PVC sheathed heavy duty galvanized, single flat steel
armoured cable.
8.2
APPLICABLE STANDARD
8.2.1 All the cables shall conform to the requirements of following standards with latest
amendments, if any:i)
ii)
IS:8130-1984
iii)
IS:5831-1984
iv)
IS:3975-1979
v)
vi)
IS:10810-1984
IS:3961 (Part-II) 1967
vii)
viii)
IS:4905-1968
IS:10418-1972
8.3
8.3.1 CONDUCTOR
Aluminium conductor used in power cables shall comply to the requirement to IS 81301984with latest amendments and shall be in accordance with clause 8.1 & 8.2 of IS 1554
(Part-I)-1988 with latest amendments.
8.3.2 PVC INSULATION, FILLER & INNER SHEATH
a)
PVC Insulation and sheath used shall comply to requirement of IS:5831-1984
with latest amendments.
b)
PVC insulatiion shall be suitable for continuous PVC conductor temperature of
70oC under normal operation & 160oC under short circuit conditions. Insulation shall
be of Type A PVC compound. The average thickness of insulation shall be not less
than nominal value specified
in Table 2 of IS:1554 (Part-I) 1988. The insulation
shall be applied by extrsion so that it fits closely on the conductor and it shall be
possible
to remove it without damage.
c)
The filler and inner sheath shall be of unvulcanised rubber or thermoplastic
material or proofed tape (for inner sheath only). Unvulcanised rubber or
thermoplastic material used shall not be harder than PVC used for insulation and
outer sheath. The material shall be chosen to be compatible with temperature
ratings of the cable and shall have no deleterious effect on any other
component of the cable.
d)
The laid-up cores shall be provided with inner sheath applied either by extrusion
or wrapping. It shall be ensured that the shape is as circular as possible. The
inner sheath shall be so applied that it fits closely on the laid up cores and it
shall be
possible to remove it without damage to the insulation. The
thickness of inner
sheath shall be as in Table-4 of IS 1554 (Part-I) 1988.
8.3.3 ARMOURING
The galvanized steel wires/strips shall comply with the requirement of IS: 3975-1979
with latest amendment. Armouring shall be applied over the inner sheath. The armour
wire/strips shall be applied as closely as practicable. A binder tape should be
provided on the armour. Type of armour and its dimension and procedure for its
laying and joints shall comply to the requirement of Clause-13.2,13.3, 13.1.3 & 13.4
respectively of IS:1554(Part-I)/1988. The D.C resistance of galvanized steel wire/strips
armour shall be measured and the result when corrected at 20oC shall comply with
approximate value given in Table-6 of IS:1554 (Pt-I)/1988.
8.3.4 OUTER SHEATH
The outer sheath shall be of type ST1 PVC Compound conforming to the
requirements of IS:5831-1984. The outer sheath shall be applied by extrusion
over the armouning and shall be so applied that it fits closely over armouring. It shall
be
possible to remove it without damage to inner sheath. The colour of outer sheath
shall be black. The minimum thickness of PVC outer sheath shall not fall below
the
nominal value (ts) specified in Table-7 of IS:1554 (Part-I) 1988 by more than 0.2
mm
Plus-minus 0.2 mtrs.
8.3.5 CORE INDENTIFICATION
Core shall be identified by different colouring of PVC in accordance with Clause10
of IS:1554 (Part-I) 1988.
8.3.6 IDENTIFICATION, PACKING & MARKING
Manufacturers Identification
In addition to manufacturers identification on cable as per clause-17.1 IS:1554
(Part- I)
following marking shall also be embossed over outer sheath at every
three metre :Cable size and voltage grade
Word BSEB & name of manufacturer at every 3 metre
The embossing shall be done in line throughout the length of the Cable and shall
be
legible and indelible.
8.3.7 Packing & Marking
a)
The cable shall be wound on a drum (ref. IS 10418-1972) of suitable size and
packed. The packing shall be robust for rough handling that is occasioned
during transportation by Rail/Road. The ends of the cable shall be sealed by means
of non-hygroscopic sealing material.
b)
The cable should carry the following information stenciled on the drum :1.
1.
2.
3.
4.
5.
6. Colour of cores
7. Length of cable on the drum
8. Number of lengths on drum (if more than one)
9. Direction of rotation of drum by means of an arrow
10. Approximate gross weight
11. Running end of cable
12. Country of Manufacturer &
13. Year of manufacture
14. ISI Certification Mark
The Cable (Drum) must bear ISI Certification Mark. In this connection, a certified
photo-stat copy of valid ISI marking License rights duly attested must be
submitted
along with the inspection offer as documentary evidence. In absence of
ISI License documents, the cable shall not be accepted.
8.3.8 Standard Length
The standard length of cable shall be 250 mtrs./500 mtrs. with plus minus 5%
tolerance.
8.4
TESTS
Following type tests, acceptance tests and routine tests are to be carried out in
accordance with clause-15 of IS/1554 (Part-I) 1988 with its latest amendments as
indicated below :8.4.1 TYPE TESTS
The following shall constitute type tests: Sl
.
A
i
ii
iii
B
i
ii
iii
iv
v
vi
vii
vii
i
C
Tests
TEST ON CONDUCTOR
Tensile Test
Wrapping Test
Conductor Resistance Test
TEST ON ARMOURING
WIRES/STRIP
Measurement
of
Dimension
Tensile Test
Elongation Test
Torsion Test (For round
wires only)
Winding Test (for strips
only)
Uniformity of zinc coating
test
Mass of zinc coating test
Resistance Test
2
3
5
36
-do-
39
-do-
40
-do-do-
41
42
37
37
38
Sl
.
i
ii
iii
iv
v
vi
vii
E
F
Tests
Tensile
Strength
elongation at break
Aging in Air oven
Shrinkage Test
Hot deformation
Loss of mass in air oven
Heat shock test
Thermal stability
11
12
15
10
14
Test method as per
IS:5831-1984 shall be
followed
43
of 45
of 45
of 53
The contractor shall be required to furnish the type test certificate from NABL
accredited Laboratory which shold not be more than three (3) years old at the
time of submission of bid.
23.4.2 Acceptance Tests
The following shall constitute acceptance tests:a)
Tensile Test (for aluminium)
b)
Wrapping Test (for aluminium)
c)
Conductor resistance test
d)
Test for thickness of insulations and sheath
e)
Tensile strength and elongation at break of insulation and sheath.
f)
Insulation resistance test
g)
High voltage test at Room temperature
All the above acceptance tests will be carried out by Employers
representative as per relevant ISS at the time of material inspection for the
purpose of clearing the lot offered by the bidder. Acceptance test shall be carried
out in each type and size of cable, on cable drum selected at random as per
following sampling plan :No. of drums in the lot
Upto 50
51 to 100
101 to 300
301 to 500
501 & above
no.
of
8.4.3
8.5
Routine Tests
The following shall constitute routine tests:a)
Conductor Resistance test
b)
High voltage test at room temperature
c)
The above routine tests shall be conducted by the bidder in accordance
with relevant ISS and test certificate as proof of it shall be submitted to
the Employer along with each inspection offer. In absence of routine test
certificate, the inspection offer shall not be considered valid and any or all
complication arising out of it Employer shall not be responsible.
Inspection
All the tests and inspection shall be made at the place of manufacturer
unless otherwise specially agreed upon by the contractor/manufacturer and
Employer. The contractor/manufacturer shall offer all reasonable facilities to the
Employer, without charges to satisfy him that the material is being furnished in
accordance with the specification. In order to ensure that quality of raw materials
used during manufacturing of PVC Cables as per requirement of IS:1554 (PtI)/1988, the Employers representative shall check quality of raw material, obtain
necessary invoices in proof that required quality of raw materials is being used.
The Employer reserves the right to have any or all types of acceptance test
carried out by NABL accredited laboratory. In case the material fails to pass the
test as per specification, the testing charges along with the other charges which
were actually incurred for arranging the test shall be recovered from the supplier.
9.0
A.
B.
9.1.1
The equipment offered shall be complete with all parts necessary for their effective
and
trouble free operation. Such parts will be deemed to be within the scope
irrespective of whether they are specifically indicated in the commercial order or not.
9.1.2 It is not the intent to specify herein complete details of design and construction. The
equipment offered shall conform to the relevant standards and be of high quality,
sturdy,
robust and of good design and workmanship complete in all respects and
capable to
perform continuous and satisfactory operations in the actual service
conditions at site and shall have sufficiently long life in service as per standard
requirements. The dimensional
drawings attached with the Technical Specification
in Volume II are generally of illustrative
nature. In actual practice, not withstanding
any anomalies, discrepancies, omissions, incompleteness, etc. in these specifications
and attached drawings, the design and
constructional aspects, including materials
and dimensions, will be subject to good
engineering practice in conformity with the
required quality of the product, and to such tolerances, allowances and requirements
for clearances etc. as are necessary by virtue
of various stipulation in that respect
in the relevant Indian Standards, IEC standards, I.E.
Rules and other statutory
provisions.
9.1.3 The Bidder / Supplier shall bind himself to abide by these considerations to the
entire satisfaction of the Employer and will be required to adjust such details at no extra
cost to the Employer over and above the tendered rates and prices.
9.1.4 Tolerances on all the dimensions shall be in accordance with provisions made in
the
relevant Indian/ IEC standards and in these specifications. Otherwise the same
will be governed by good engineering practice in conformity with required quality of the
product.
9.2
APPLICABLE STANDARDS:
Specification
Details about
No.
1
IS:6600-1978
IS:335-1983
IS:3347 (Part-I
Sec. 1 & 2)
Metal
parts
for
IS:7421
IS:2099-1986
IS:3639-1966
IS:1866-1978
10
IS:5484
11
IS:9335
12
IS:1576
13
IS:616 (Part I)
14
IS:6162(Part II)
15
IS:104
16
IS:649
17
IS:2362
18
IS: 4257
19
IS 6160
20
IS:10028
21
IS:3401
Silica gel
22
ii)
iii)
: 50C
: 35C
: 95 %
:
:
:
:
:
10%
40
90
125 cm
3 Months
: 100 Kg/mt
Not exceeding
9.4
PRINCIPAL PARAMETERS:
9.4.1
The Transformer shall be suitable for outdoor installation with three phase 50 Hz 11 KV
system in which the neutral is effectively earthed and should be suitable for outdoor
service as step down transformer under fluctuations in supply voltage up to (+) 10% to
minus (-) 15 % and frequency variation of +/- 3% from the rated frequency. The
transformer should be suitably designed for with-standing the unbalanced voltages
developed due to single phasing operation during load regulatory measures in 11KV
distribution system. It should be capable of withstanding the disturbance of back e.m.f.,
magnetic characteristic and consequential mechanical inter-play of forces, if any, under
such single phasing.
9.4.2
9.4.3
Primary winding shall be DELTA connected and the secondary winding shall be
STAR connected (vector symbol Dyn-11), so as to produce a positive
displacement of 30 from the primary to the secondary vectors of the same phase.
The neutral of the secondary winding shall be brought out to a separate insulated
terminal. The transformers shall be Aluminium Wound (EC grade).
9.4.4
9.5
RATING (KVA)
200/100
100
9.6.2 The above specified loss values are maximum guaranteed, without any positive
tolerance.
In case the actual loss values exceed the above guaranteed values, the
transformers shall
be rejected at the risk, cost and responsibility of the supplier.
9.7
9.7.1
TEMPERATURE RISE:
The temperature rise test shall be conducted by feeding total guaranteed losses
calculated at 100C as against 75oC in the ISS and tested in accordance with
IS:2026 or
equivalent standards and the same shall not exceed the limits of 50C
Total Losses to be fed (No load losses + Load Losses Corrected to 100oC)
100 + 742
= 842 Watts
9.7.2 It must be noted carefully that readings for hot resistance after shut down shall
be taken separately for HV & LV windings, which means, after completing the readings
for one winding (HV or LV), the transformer shall be connected again and rated current
passed for another 60 minutes (min.) and shut down taken again to take hot resistance
readings for the remaining winding. This is in line with the requirement of CBIP manual,
to ensure proper resistance v/s time curves.
9.7.3 The Hot spot temperature at annual weighted average ambient temperature of
35o C shall not exceed 98o C, when calculated as per IS: 2026 (Part-II)
However, the transformer shall be designed for class A insulation.
9.8
UNBALANCE CURRENT:
The maximum value of unbalance current in transformers shall not exceed 2% of
full load current.
9.9
IMPEDANCE:
The percentage impedance at rated current and at 75C shall be 4.5 % with (+/-)
10 % tolerance.
9.10 TAPPINGS:
Taps as standard are to be provided in these transformers.
9.11 FREQUENCY:
Transformers shall be designed for normal frequency of 50 Hz, but shall be
capable of
giving the rated output with the variation of (+/-) 3 % from the rated
frequency.
9.12 ELECTRICAL CLEARANCES:
(A) EXTERNAL (IN AIR)
Minimum external electrical clearances after mounting the bimetallic terminal
connectors
in position shall be maintained, as under; however, positive tolerance
shall be acceptable without any ceiling.
Voltage
Medium
11000 Volt
433 Volt
AIR
AIR
Clearance
Phase to phase
Phase to earth
255 mm
140 mm
75 mm
40 mm
200 KVA
25 mm
40 mm
25 mm
20 mm
3.5 mm
125 mm
11 mm
10 mm
The aforesaid external and internal clearances are minimum clearances and no
negative
tolerance on these clearances shall be allowed.
9.13
test
TEST VOLTAGE:
Transformers shall be capable of withstanding the power frequency and impulse
voltage prescribed below:
Nominal system
Voltage (RMS)
Highest system
voltage (RMS)
Impulse withstand
voltage
11 KV
0.433 KV
12.5 KV
----
75 KV (PEAK)
----
Power frequency
test voltage in
(RMS)
28 KV
3 KV
The Transformer shall have fully insulated windings designed for the above
impulse level.
9.14
500 W / m2
(Note: The area of top/bottom tank surface, headers, HV/LV bushing pocket shall
not be considered for purpose of above calculations).
ii) Elliptical tube of section
-55 watts/meter length.
9.14.4 There shall not be any price preference for providing of either type of radiators.
a)
b)
All delta leads from the HT coils as well as HT line leads shall be taken out
through multiple paper covered (MPC) copper wires of sufficient cross section
area to impart the desired mechanical strength. The current density in HV
lead wire shall not exceed 0.8 A/mm. These lead wires shall be provided with
multi layer paper insulation of minimum 1.0 mm thickness i.e. increase in
diameter due to paper insulation shall not be less than 2 mm. The layer of glass
sleeves/ glass tape shall also be provided on the delta MPC wire and it should be
further covered with kraft paper.
c)
e)
All the above leads shall then be clamped tightly with cotton twine directly on to
the special frame/ bracket making Pie shape connection. This structure
could be made up of Bakelite/ Permalli wood/ laminated PC board flats, having
minimum size of 25x4.5 mm. Line leads leading to the HV bushing terminals
shall be directly clamped to the horizontal support bar of the Pie structure so
that any tension which may develop in the HT leads due to jerks or at the time of
making the connection, is not passed to the HT coils.
Delta joint and lead from delta joint to bushing rod shall be made by brazing only.
B) LV Winding :
a)
The LV connection shall be taken out by cut on the top yoke channel duly
reinforced to compensate for the mechanical strength.
b)
The layers in LT Coil may be either even or odd in numbers but minimum layers
shall be
two.
c)
LV star point shall be formed of aluminium flat of sufficient strength. Leads from
winding shall be connected to the flat by brazing.
d) Firm connection of LT winding to bushing shall be made of adequate size of L
shape flat. Connection of LT coils to L shape flat shall be by brazing only.
e) L shape Flat shall be clamped to LV Bushing metal part(s) by using nut, lock
nut and washer.
f ) Neutral of the Secondary winding (LV) shall be brought out to a separate
insulated bushing.
g ) For Aluminium windings, L&T, ALKAPEE Aluminium brazing rods with suitable
flux will be used.
9.16 CORE CONSTRUCTION & CORE COIL ASSEMBLY DETAILS:
(i)
The core shall be of high grade cold rolled grain oriented (CRGO) annealed steel
laminations, having low loss and good grain properties, coated with hot oil
proof insulation, bolted together to the frames
firmly to prevent vibration or
noise. All core clamping bolts shall be effectively insulated. The complete design
of core must ensure the permanency of the core losses with continuous working
of the transformers. The value of
the flux density allowed in the designs and
grade of laminations used shall be clearly stated, along with the curves. The
transformer core shall be constructed out of the prime
class of materials.
CRGO Lamination used shall be of prime grade and not second grade
steel
laminations.
(ii)
It will be mandatory for all the transformer manufacturers to use only PRIME
grade CRGO Laminations with specific loss of 0.89 watt per kg. at 1.5 Tesla or
any other combination
of better
grades with any thickness subject to
maximum specific loss of 0.89 watt per
kg. at 1.5 Tesla will also be
acceptable. The bidder shall furnish the core loss (watt/Kg.) and power (VA/Kg)
curves of the laminations used. The core shall be properly
stress relieved
by annealing in inert atmosphere. Thetransformer shall be suitable
for
over fluxing (due to combined effect of voltage and frequency) upto 12.5%
without
injurious heating. The operating flux density shall be such that
there is a clear safe margin of 12.5%. over the fluxing limit.
(iii)
Full mitred core construction technique shall be adopted. Top yoke & bottom
yoke pieces shall all be in one single piece and no cut pieces shall be
acceptable. The cross sectional area of yoke & limb shall be approximately
same.
(iv)
Transformer core shall not get saturated for any value of V/f ratio to the
extent of 115% of the rated value of V/f ratio (i.e. 11000/ 50) due to combined
effect of voltage and frequency without injurious heating at full load conditions.
The bidder shall furnish
necessary design data in support of this situation.
(v)
Flux density at rated voltage and frequency of core and yoke shall not be more
than 1.60 Tesla. The Over fluxing shall be limited to 12.5 % of rated value.
200/100
3.25
At 112.5% rated
voltage
6.50
Item
Particulars
Minimum 4 Nos. of 12 mm each properly insulated and covered with
Kraft paper. Tie rods shall also be provided with lock nuts.
Minimum 4 Nos. of 12 mm each properly insulated and covered with
Kraft paper. The core studs shall also be provided with lock nuts.
a)
Tie rods
b)
Core studs
c)
Spacers
d)
e)
assembly base
Channels
for
4 MS Channels of 75 x 40 mm size (applicable for CRGO
clamping
core
transformers)
coil assembly
Guides on all the four sides shall be provided to prevent shifting of the active
parts and
thereby accidental touching the tank. Alternatively brass nut arrangement
at the top of core coil assembly to lock the same with the transformer tank be
provided.
The assembly fixing brass nut(s) are to be welded, 20-30 mm off the centre line
(and diagonally) ofthe tanks, so that assembly movement during transport etc. is
prevented.
MS Channel, tie Rods etc should be painted with hot oil and corrosion
resistant paint after phospating.
All core-coil assembly shall be punched on core channel / a identity plate welded
on core
channel with following details:
1.
Name of Supplier:
2.
Order / TN No:
3.
Rating:
In case the above marking is not found on the core assembly of physically
opened
transformer selected for physical verification during final inspection then
no further
inspection shall be carried out and re-inspection charges shall be payable
by the Supplier.
9.17
TRANSFORMER TANK:
(a)
I T E M S
200 KVA
5.0
2
3
3.15
5.0
5
5
6
7
8
9
10
1
2.0
40x40x 6 angle
50 x 6 Flat
M10/ 3/8 x 1.5
75 mm
2 Nos.
8t mm flat
2 ( 75 x 40 mm)
NOTE: Each cover bolt shall be complete with two flat washers, one nut and one spring
washer.
The above mentioned M S sections shall be subject to tolerance as per ISS.
(c) Lifting Lugs: Two Nos. welded heavy duty lifting lugs of MS plate of 8 mm thickness,
suitably
reinforced by vertical supporting flat welded edge wise below the lug on
side wall shall be provided, these shall be so extended that cutting of bent plate is not
required
(d) Top cover gasket & Bolt :
i)
The gasket provided in between top cover plate and tank shall be of min. 6
mm thick neoprene rubberized oil resistant cork sheets conforming to type B
or C as per IS:4253 part II.
ii)
G.I. Nut bolts shall be of size M 10 x 40 mm / 3/8x1.5 long with two flat
washers, suitably spaced (as specified) to press the cover.
iii)
Height of the tank shall be such that minimum clear height of 125 mm is
achieved between top of yoke and under side of the tank cover (with gasket
in place).
iv)
All steel screws, nuts and fasteners exposed to atmosphere shall be either
galvanised or cadmium plated or electroplated.
v)
All sealing washers / gaskets shall be made of oil and heat resistant
neoprene or
nitrile rubber. Gaskets made of natural rubber sheet are not permissible. The
minimum thickness of gaskets shall not be less than 6 mm for tank cover and
4mm for HT/LT gasket washers.
vi)
Talbros make neoprene/nitrile based rubberized cork sheet grade RC-70-C
shall
only be used as gasket material. Alternatively, other makes of gaskets having
type designations as under can also be used, if Talbros make gasket is not
available:
S.
No.
1.
2.
3.
RC-70-C
(Neoprene)
RC-70-C
4.
(e) Tank shall be reinforced by continuously welded angle on all the four sides of the
walls, on the edge of tank, as specified above. The permanent deflection shall not be
more than 5 mm upto 750 mm length and 6.5 mm up to 1250 mm length when
transformer tank without oil is
subjected to the vacuum of 250 mm of Mercury.
(f)
PAINTING & FINISHING :
Steel surface shall be prepared by sand / shot blast or chemical cleaning
including
phospating, as per IS 3618. Heat resistance paint (Hot oil proof) shall be
provided inside
the tank. On external surface, one coats of thermo-setting powder
paint or 2 coats of Zinc
chromate followed by two coats of synthetic
enamel
paint of dark admiral grey shade,
confirming to shade No. 632 of IS: 5-1961, shall be
applied.
The requirement for paint and the material to be used shall be as below.
Paint Type
a) Powder Paint
b)
Thermo
Setting
Powder
LIQUID PAINT
a) Zinc Chromate (Primer)
b)synthetic Enamel or
powder coating
(finish
coat)
c) Hot Oil Paint
Area to be Painted
No. of coats
Inside
Outside
01
01
Outside
Outside
02
02
Inside
01
All steel screws, nuts and fasteners exposed to atmosphere shall be either
galvanized or cadmium plated.
9.18
-5 C - Min.
30 C - Nor.
98 C Max.
i)
TRANSFORMER OIL:
9.23.1 The transformer shall be supplied complete with first filling of EHV Grade
transformer oil, up to the normal oil level. The oil shall conform to IS: 3351983 (latest amended) and should be ISI marked and having the specified
aging characteristics.
9.23.2 The transformer oil sample taken from the transformer shall be subjected to
testing as per provisions of IS:1866.
9.23.3 The oil manufacturers test certificate shall be made available at the time of
inspection
to the inspecting officer.
9.24 IDENTIFICATION DETAILS:
a)
Rating & terminal marking plate: Each Transformer shall be provided with non
detachable
name, rating and terminal marking plate fitted in a visible position.
All details shall be
given on one plate. Material of the plate shall be stainless
steel only. Thickness shall be 0.9 mm (with a tolerance of 0.1 mm). The plate
shall be made absolutely un-detachable either through welding or riveting or
through any other approved method.
Each HV & LV terminal shall be duly marked with its terminal numbers. (e.g. HV
terminal with capital letter 1U, 1V, 1W and LV terminal by corresponding small
letters) 2u, 2v, 2w and the neutral terminal by 2n). In the diagram to be given on
the name plate, the relative position of various terminals- when viewed from
top shall be clearly shown. Dispatch instruction will not be issued, unless all
these details are verified by the Inspecting Officer.
Besides other particulars, following details shall also be given on the name plate:
i)
P.O. No. - Month & year.
ii)
Sr. No. of transformer.
iii)
Date of despatch - month & year
iii)
Date of expiry of guarantee period month & year
iv)
Maximum Guaranteed No Load & Load Loss Figures
v)
Recommended fuse sizes for HV & LV sides.
vi)
Name & Full address of the manufacturer.
vii)
Weight of oil (In Kg).
viii)
Total Weight (In Kg).
ix)
Vol of oil (In Litre)
x)
Rating of the transformer.
xi)
Impedance volt. (%).
xii)
Volts at HV&LV.
xiii)
Frequency (Hz)
xiv)
Vector group (Dyn11)
S.NO. .
MAKE
c)
Identification mark:- Serial Number of Transformer is to be engraved on
transformer tank just below the
name plate with the letter size of 10 mm x 8 mm.
9.25 GUARANTEED
TRANSFORMER:
AND
OTHER
TECHNICAL
PARTICULARS
FOR
9.26.1 The bidder shall furnish type test certificates of the offered transformer with the
bid
which should not be more than 3 years old as on the date of opening of tender.
9.27
9.27.1 The Bid shall be accompanied with the following drawings / Calculation sheets,
as
per the offered designs. The drawings shall be only on A-3 (420 x 297
mm) size paper and calculation sheet shall be on A-4 size paper only.
a) Name rating / diagram plate drawing.
b) Outline and general arrangement drawing.
c) Core-coil assembly drawing.
d) Core section (for limb and yoke) along with flux density calculation sheet /
drawing.
e) Cooling area calculation sheet.
f) Thermal Ability short circuit calculation sheet.
g) Core loss and magnetization curves of the laminations.
h) Heat dissipation calculations (heat dissipation by tank walls excluding top
and bottom should be 500 W/sq. meter.
9.28
9.28.1 The Bidder shall furnish the details in respect of the items specially indicated in
the
schedules prescribed herein and annexed with this specification, failing which the
offer is
liable for rejection.
9.29
(i)
The inspection and testing shall be conducted at the place of
manufacture. The
transformers shall be completely assembled and tested at
the factory. The inspection may be carried out by the Employer at any stage of
manufacturing. The Supplier shall grant free access to the Employers
representative at all reasonable times when the manufacturing work is in
progress. Inspection and testing of any material under this specification by the
Employer shall not relieve the Supplier of his obligation of supplying the material
in accordance with the specification and shall not prevent subsequent rejection if
the material is found to be defective.
( ii )
The Supplier shall afford the inspector representing the Employer
all reasonable facilities, without charge, to satisfy him that the material is being
manufactured in accordance with the specification. The bidders must have
adequate set of instruments for conducting testing as per ISS Specification. The
instruments for measurement of losses shall be of accuracy class of
0.5
or
better. The instruments shall be duly calibrated and Calibration Certificate should
not be older than one year on the date of presentation to the Inspecting Officer.
The calibration shall be arranged from NABL accredited testing house. A
comprehensive list of testing equipment/instruments indicating make, Sr.No.,
type, class of accuracy, calibrating agency, calibration date etc.
should
be
furnished along with the bid. The calibrated instruments shall be duly sealed by
calibrating agency to avoid any tampering with calibration and the details thereof
shall be clearly mentioned in the Calibration Certificate(s).
( iii )
The Supplier shall keep the Employer informed in advance, about the
manufacturing programme so that arrangements can be made for
inspection. The
Supplier shall give preferably fifteen days advance
intimation to enable the Employer
to
depute
his authorised
representative for stage inspection/ witnessing of various
tests on the
equipment/ material.
9.30
STAGE INSPECTION:
9.30.1 The Employers representative may carry out stage inspection of the
transformers during manufacturing/ assembling stage. The Employer shall have
absolute right to reject
the raw material/ component/ sub assemblies or complete
equipment not found to be conforming to the requirement of specification or being of
poor quality/ workmanship. The
stage inspection will particularly
include
the
following tests/ checks besides the general routine tests to be conducted during
manufacturing stages as per manufacturers standard
practice.
a) Physical inspection/checking of winding, insulating material, core material for
annealing and prime quality and other accessories / fittings of Transformer.
b) Measurement of core area and flux density.
c) Verification of H.V. & L.V. coils, Conductor size, I.D., O.D. Axial length, weight,
insulation covering etc.
Insulation resistance
Separate source voltage withstand test
Induced over voltage withstand test
Measurement of windings resistance cold (at or near the test bed temperature)
Measurement of Voltage ratio and check of voltage vector relationship
Measurement of Impedance voltage and load losses at rated current and normal
frequency.
Measurement of No load losses at rated voltage and normal frequency.
Measurement of No load current at 100 % and 112.5% of rated voltage and
normal frequency.
Checking of rating and terminal marking plate.
10.
11.
12.
13.
9.31.3
Preferably Fifteen days clear notice shall be arranged for pre-despatch
inspection by Employers representative.
9.31.4
After successful inspection, the inspecting officer shall seal all the inspected
transformers by
numbered seals on diagonally opposite bolts of top cover
for identification. Before sealing, the inspecting officer will ensure that all the
offered transformers are complete and duly fitted with
name, rating and
diagram plate, identification plate (on tank body & Top cover) as specified in
this specification.
NOTE:
i)
11000 Volts
(HV)
433 Volts
(LV)
ii)
200 C.
800
300 C.
400
400 C.
200
500 C.
100
600 C.
50
400
200
100
50
25
This test shall be conducted as type test at the time of inspection of first
lot, at the
manufacturers works. The pressure gauge and vacuum gauge shall be
duly calibrated and sealed by an independent recognised test lab(s).
The test procedure shall be as detailed below :
The tank shall be fixed with a dummy cover with all fittings including
bushings in position and shall be subjected to air pressure of 0.8 Kg./ cm (gauge
pressure), for 30
minutes.
not
Permanent deflection of flat plate, after pressure has been released, shall
exceed the values given below:
Length of plate up to
750 mm
751 to 1250 mm
iii)
Deflection
5.0 mm
6.5 mm
TYPE TESTS:
9.32.1
In addition to above tests, the following type tests shall be arranged by the
supplier in
accordance with IS:2026 (Part I to III).
i)
ii)
Short circuit test for dynamic and thermal ability: The short circuit test for
dynamic and thermal ability shall be arranged at CPRI, Bangalore/ Bhopal or
ERDA, Vadodara on one unit of each rating. The transformer(s) for the test
shall be selected/ sealed by our inspecting officer from the first lot which shall
be of minimum 20 Nos. (if ordered quantity is 500 Nos.) OR 50 Nos. (if
ordered quantity is more than 500 Nos.). The short - circuit test shall be
conducted only after successful routine tests including measurement of noload and load losses. The supply shall be accepted only after successful type
test on the selected transformer(s).
Impulse voltage withstand test: The impulse voltage withstand test shall be
arranged at any testing house accredited to NABL for the purpose of impulse
test. The test shall be conducted on one unit to be selected by our inspecting
officer from the first lot of 20 Nos. (if ordered quantity is 500 Nos.) OR 50
Nos. (if ordered quantity is more than 500 Nos.). The test shall conform to
the requirement of Clause 13 of IS: 2026 (Part-III). The supply shall be
accepted only after successful impulse test on the selected transformer(s).
9.32.2
No extra time shall be allowed for arranging these type tests. The cost of
above Type Tests shall be borne by the Supplier.
9.32.3
9.32.4
The requirement of arranging short circuit & impulse voltage withstand test
shall however, not to be insisted on the Suppliers who have arranged Dynamic &
Thermal
Ability to withstand Short Circuit Test/ impulse voltage withstand test
within last 3 years as on the date of opening of the tender on similar design and make.
9.33 RANDOM SELECTION AND TESTING (RST):
(i)
Inspection of material before dispatch or waiver of inspection will,
however, not relieve, the supplier from his responsibility to supply the material
strictly in accordance with the specification. The Employer shall have option to
test the samples selected at random from the lot of 25 No received at site and
shall be subjected to routine testing as per IS:1180 and 2026 (with latest
amendments) at MTRU, Jabalpur/ CPRI, Bhopal, CPRI, Bangalore/ERDA,
Vadodara/any other NABL accredited Laboratory.
(ii)
(iii)
(iv)
9.33.1 The Employer may select transformer(s) from the supplied lot(s) at random for
conducting the routine tests, at any test house(s) as mentioned above. The
Supplier shall arrange these tests including loading, unloading and to & fro
transportation up to the test house(s). The charges for such tests shall be
reimbursable to the Supplier on actual basis on production of documentary
a)
One transformer will be selected out of every lot of 25 Nos. or part thereof for
measurement of No load Losses at rated voltage; No Load current (at 100% and
112.5% of rated voltage); Impedance voltage and Load Losses at rated current. The
testing shall be arranged either at Employers own testing lab and / or at independent
test lab. The testing charges for such tests hall be borne by the Employer. The test
results will be applicable to the respective lot of 25 Nos. or part thereof from which
sample was drawn.
b)
In case if dispatch instructions are less than 25 Nos. than one sample shall be
selected from
each store (s) and the test result so obtained shall be for the
quantity consigned / received by the store (s).
9.34
GUARANTEE PERIOD:
i)
(ii)
(iii)
Unit once failed within the said guarantee period of 36 months and returned
to site duly repaired free of charges, shall be guaranteed for a minimum of
12 months or un-expired guarantee period left as on the date of failure of
the unit, whichever is later.
(iv)
In case unit again subsequently fails within the period of 12 months
and the total period of service given by the unit is more than 24 months
but less than 36 months, then the unit shall have to be repaired again free
of charges, by the Supplier. In case the unit further fails within 12 months
of its last return duly repaired, then the unit shall berepaired again free of
charges by the Supplier but the guarantee for the repaired unit, in this case,
shall be for the un-expired period out of 12 months.
(v)
The outage period i.e. period from the date of failure till the unit is
repaired, shall not be counted for arriving at the guarantee period of 36
months. The period of failure and repairs, thus, shall be excluded from the
guaranteed service of 36 months/ 12 months, as the case may be.
(vi)
Further, it is clarified that all the charges towards carrying out repairs
including packing / forwarding, loading / unloading shall be borne by the
Supplier.
(vii)
The actual cost of dismantling and replacement of the equipments with new
one shall be charged to the Suppliers account.
(viii) To & fro transportation cost of such failed equipments shall be borne by the
Supplier.
ix)
If the supplier does not lift and repair the failed transformer within a reasonable
time of 30 days from the date of intimation by the Employer, the same will be got
repaired at Suppliers cost through other Supplier/repairer.
C.
The Enclosure shall be fabricated by using CRCA sheet steel of not less than 16
SWG thickness & shall comply with the requirement of I.P. 33 as per I.S.
13947/I/1993.
Box is to be provided with MCCB fixing arrangement such that front & back as
well as up
& down with tilting adjustment can be done to accommodate various type
& make of
MCCB. The box shall be provided to cover the LV bushing as shown in
the drawing.
9.35.1 MAIN FEATURES OF THE PROTECTION BOX:
The box shall be as per drawing no ADB/EZ-29 given in Volume II.
i) The single slide door panel shall be provided with slide opening.
ii) Name plate One door locking patti (25x40 mm) provided with MIG welded for
pad lock and sealing hole arrangement.
Louvres to be provided on both sides and in the bottom of MCCB Chamber.
v)
2 Nos. Earthing Bolt size 25x10mm each with 2 Nos. Washer and one Nut to
be provided.
2 Nos. Earth sticker or colour embossing with Earth Symbol to be provided.
1 Nos. hole provided at bottom in Cable Gland Hole. All hole meant for cable entry /
exit to be provided with rubber.
1 No. outcoming terminal lug size 35 sq.mm to be provided.
Outdoor (enclosed).
Utilization category
Type
Number of poles
Single
50 C.
600 V.
433 V.
600 A
0.4 (lag.)
Application Standard
The MCCB shall not cause any nuisance tripping due to switching current of
motor & capacitor loads.
The Bidder shall submit the type test reports as per I.S. 13947/1993 for test
sequence I,II & III complete with certified drawings, Oscillograms and approved
drawing from NABL approved laboratory along with the offer.
The MCCBs shall be marked with Brand Name of manufacture and Ics in KA by
embossing only whereas other particulars may be marked as per the
manufacturers
standard practice.
The contacts of MCCB should be self-wiping type so as to keep the contacts
clean and milli-volt drop low. The MCCB shall be provided with push to trip
facility.
The successful bidder shall be required to furnish the guarantee certificate of
three (3)
years obtained from the MCCB manufacture. The liability of guarantee
shall, however, be
that of the bidder/contractor. If during the course of 36 months
subsequent to the date of commissioning of MCCB, any of the goods is found to
be defective in
materials or workmanship or develops defects during service,
the same shall be
replaced / repaired by the bidder/contractor free of all charges.
All necessary arrangements on this account will be made by the bidder/contractor.
Acceptance Tests:
The following tests shall be carried out by the purchasers representative on MCCB on
the sample numbers equivalent to the number of transformer samples.
1.Overall Dimensional Checking.
2.High Voltage test at 3 kV for one minute.
3.Insulation resistance test.
Instruction and operation Manual
The successful bidder shall be required to submit 5 copies of Instruction and
Operation manual for each lot of 100 Transformers (or part thereof) supplied. This
instruction manual should give complete details about the pre-commissioning
tests/checks and
9.35.3
The MCCB enclosure shall be provided with LED indicating lamp (Three Nos.) to
indicate tripping of MCCB. An auxiliary relay with changeover contacts may be
used to connect LED indicating lamp to the transformer secondary terminals if
MCCB is not having auxiliary contacts. In case the MCCB trips or switched OFF,
the relay contacts are closed which turns ON the LED indicating lamp. When the
MCCB is reset and switched ON, the indicating lamp switches OFF. Signal light
shall be arranged to avoid damages while handling the MCCB enclosure at site.
ANNEXURE A
GUARANTEED TECHNICAL PARTICULARS FOR 200/100 KVA DISTRIBUTION
TRANSFORMERS.
Description
To
be
furnished
Manufacturer.
Place of Manufactures
-do-
Voltage Ratio
Sl.
No.
Ratings in
KVA
by
the
12.5%
50 deg. Max.
temperature
over
ambient
b) Oil by Thermometer
40 Deg. Max.
temperature
over
ambient
b) Max. Voltage
To
be
furnished
manufacturer.
by
the
by
the
100
b) Resistance of Winding
To
be
furnished
manufacturer
a) HV winding (ohms)
To
be
furnished
manufacturer.
b) LV winding (ohms)
-do-
10
685
11
Clearance:
12
13
a) 125%
Load
b) 100 %
Load
c) 75 %
Load
d) 50%
Load
e) 25%
Load
Regulation at
To
be
furnished
manufacturer.
by
the
by
the
-do-
a) Unit P.F.
b) 0.8. P.F. at 75 deg. Cent
14
15
To be confirmed
manufacturer.
16
-do-
by
the
18
19
a)
b)
c)
d)
Oil
e)
As per IS to be conformed.
(Ltrs).
Oil date
a) Qty. for first filling Ltrs (min)
To be furnished by manufacturer
20
c) Makers name
To be furnished by manufacturer
To be furnished by manufacturer
Transformers:
a) Overall LxBxH
To be furnished by manufacturer
b) Tank LxBxH
-do-
21
3.15mm
5.0 mm
To be furnished by manufacturer.
-do-
-do-
-do-
To
be
furnished
manufacturer
b) For core
23
by
the
-do-
LV
a) SWG
To be furnished by manufacturer
b) Dia
-do-
c) Area
-do-
a) Strip size
To be furnished by manufacturer
24.
-do-
25.
Particulars of bushings
HV
1. Makers Name
To be furnished by manufacture.
2. Type IS-3347/IS-1180
3. Rating as per IS
a) HV
LV
b) LV
4. Dry flashover voltage at 50 C/S
-do-
-do-
26
Not applicable
27
Radiation
1) Heat dissipation by tank walls
55 Watts/meter length
Item
Source of
Place of
Place of
Material
manufacture
& inspection
- - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ----1. Lamination
2. Copper Aluminium
3. Core plates
4. Steel castings
5. Tank
6. Radiators
7. Insulating cylinders
8. Insulating paper
9. Bushing HV/LV
10. Oil
11. Insulated winding wire
12. a) Tap changer
b) Thermometer
c) Pressure relief vent
Signature of
Bidder:
Name:
ADDITIONAL DETAIL
SL.NO.
DESCRIPTION
1.
Core grade
2.
Core diameter
mm
3.
sq cm
4.
sq cm
5.
Flux density
tesla
6.
7.
8.
9.
10.
No. of L.V.Turns
11.
No. of H.V.Turns.
12.
13.
14.
No. of parallels
15.
16.
17.
18.
19.
20.
21.
Height of LV winding mm
22.
Height of HV winding mm
23.
ID/DD of LV winding mm
24.
ID/DD of HV winding mm
25.
26.
27.
28.
HV winding to LV clearance
29.
30.
Calculated Impedance
31.
32.
mm
mm
mm
mm
SCHEDULE
LIST OF SUPPLIES MADE SO FAR WITH FULL DETAILS OF GOODS SUPPPLIED
AND TO WHOM SUPPLIED
- - - -- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ---SCHEDULE
WEIGHT AND DIMENSIONS OF PACKAGES OF DESPATCH
- - - -- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - --Sl.No.
Equipment
Contents of
Weight
Individual
Dimensions
Kg.
Packages
- - - -- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - --- - - -- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - --SCHEDULE
DESCRIPTIVE LITERATURE AND FULL PARTICULARS OF THE EQUIPMENT
OFFRED
- - - -- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -----Sl.No.
Item No.
Description
10.0
1.
P G CLAMP
SCOPE
This specification covers Design, manufacture, testing at works and supply of
Aluminum Alloy Parallel Groove Clamps (PG Clamps) for 50 Hz System.
2.0
Technical Details :
Al. Alloy parallel groove clamps shall apply in all respects with the Indian
Standard or any other authorized standard.
Aluminum Alloy used in manufacture shall conform to IS-617/1959 & IS-1307 of
1961. Nuts and bolts used will conform to IS-1363 of 1967 and its latest
amendments.
The clamps shall be smooth and free from cavity. Blow holes and such other
defects which would cause unsatisfactory service. These shall have finish
avoiding sharp edges curvatures, ridges & damage the conductors in service.
All parts of the clamp shall either be internally resistant to atmospheric corrosion
or be suitably protected during storage and service. All ferrous metal parts shall
be hot deep galvanized as per IS-2633/ 196. The threads of nuts and bolts shall
be cut after galvanizing and shall be well oiled or greased.
The current rating of the clamps shall not be less than the current rating of the
conductor. The rated short time current shall be as per annexure-A of IS:2121
part(4). The frequency of the power supply is 50 C/S.
The conductivity of PG clamps shall be above that of power conductor. The
ultimate strength under tension shall be as per IS 2121. PG clamp shall be
capable of safely withstanding stress due to short circuit effect atmospheric
condition or vibration both on conductor and clamps.
The clamps shall be indelibly marked with rated current or any identifying marked
to enable full particulars of the clamps.
The material shall be inspected as per Test plan made by BSEB before dispatch.
1.2
2.0
RAIL POLES
The rail poles shall be 13Meters long & above as specified in the
schedules & should be 105 Ib/yd(13 mt height and above as per
requirement), rails of standard quality & dimensions respectively.
The poles shall be rousted & painted with one coat of red oxide paint &
two coats of aluminium paint.
Marking
The pole shall be clearly and indelibly marked with the following particulars
either during or after manufacture but before testing at a position so as to
be easily read after erection in position.
a)
Month and year of manufacture
b)
Transverse strength of pole in Kg.
c)
Makers serial No. and mark.
3.0 Drawings
3.1
The drawings submitted by the Contractor shall be approved/commented by the Owner
as the case may be within thirty (30) days of receipt of drawings in Owner's design
office. If the designs/drawings are commented by the Owner, the Contractor shall
submit revised design/drawings duly incorporating all comments within fifteen (15) days
of date of issue of comments.
3.2
Pole accessories drawings like name plate, danger plate, anti-climbing device etc. shall
be prepared by the Contractor and submitted to the Owner in three copies alongwith
one re-producable, for record. These drawings shall be prepared in A4 size only.
3.3
While submitting the drawings, the Contractor shall clearly indicate on each drawing
Specification No., Name of the line, letter reference no. and date on which the
submission are made. The same practice is also to be followed while submitting
distribution copies.
3.4
The Contractor shall furnish the drawings in fifteen (15) copies to the Owner for
necessary distribution within fifteen (15) days after the receipt of the approval from the
Employer.
1.1.2
1.1.3
1.1.4
1.1.5
1.1.6
1.1.6.1
1.1.6.2
1.1.6.3
1.1.6.4
1.1.6.5
1.1.6.6
1.1.6.7
1.1.6.8
1.1.7
1.1.7.1
TECHNICAL REQUIREMENTS
General
The cables shall be suitable for laying in soft soil, hard soil, rocky soil,
ducts, trenches, conduits and underground buried installation with
uncontrolled back fill and chances of flooding by water.
They shall be designed to withstand all mechanical, electrical and
thermal stresses under steady state and transient operating conditions.
The XLPE /PVC insulated power cables of sizes 240 sq. mm. and above
shall withstand without damage a 3 phase fault current of at least 18.6 kA
for at least 1 second, with an initial peak of 39 kA in one of the phases.
The armour for these power cables shall be capable of carrying 18.6 kA for
at least 1 second without exceeding the maximum allowable temperature
of PVC outer sheath.
The XLPE insulated cables shall be capable of withstanding a conductor
temperature of 250C during a short circuit without any damage. The PVC
insulated cables shall be capable of withstanding a conductor
temperature of 160C during a short circuit.
The Aluminium wires used for manufacturing the cables shall be true
circular in shape before stranding and shall be uniformly good quality,
free from defects. All aluminium used in the cables shall be of electrolytic
H2 grade confirming to IS 8130-1984.
The fillers and inner sheath shall be non-hygroscopic, fire retardant
material, shall be softer than insulation and outer sheath shall be suitable
for the operating temperature of the cable.
Progressive sequential marking of the length of cable in metres at every
one metre shall be provided on the outer sheath of all cables.
Strip wire armouring method (a) mentioned in Table 5, Page-6 of IS: 1554
(Part 1 ) 1988 shall not be accepted for any of the cables.
The cables shall have outer sheath of a material with an oxygen index of
not less than 29.
All the cables shall pass fire resistance test as per IS: 1554 (Part-I)
The normal current rating of all PVC insulated cables shall be as per IS:
3961.
Repaired or old cables shall not be accepted.
Allowable tolerance on the overall diameter of the cables shall be plus or
minus 2 mm or as per IS whichever is lower.
All cables shall be suitable for neutral solidly earthed system.
Outer sheath of 33kV/11 kV cable shall be bright orange in permanent
colour.
XLPE Insulated Power Cables
The XLPE insulated cables shall be of FR type, C1 category conforming to
IS: 7098 and its amendments read along with this specification. The
conductor shall be stranded aluminum circular/sector shaped and
compacted confirming to IS 8130 1984. In multi core cables, the cores
shall be identified by red, yellow, blue and black colored strips or
colouring of insulation. A distinct inner sheath shall be provided in all
1.1.8
1.1.8.1
1.1.8.2
1.1.9
1.2
1.3
1.4
2
2.1
2.2
multi core cables. For XLPE insulated cables, the inner sheath shall be of
extruded PVC to type ST-2 of IS: 5831. When armoring is specified for
single core cables, the same shall consist of aluminum wires/strips. The
outer sheath shall be extruded PVC to Type ST-2 of IS: 5831 for all XLPE
insulated cables.
Semi-conducting layers and copper screens shall be provided as
required. All armouring shall confirm to IS 3975: 1992
PVC Power Cables
The PVC insulated 1100V grade power cables shall be of FR type, C1
category, conforming to IS: 1554 (Part-I) and its amendments, read along
with this specification and shall be suitable for a steady conductor
temperature of 70C and 90C for XLPE . The conductor shall be
electrolytic grade stranded aluminium conforming to IS: 8130 -1984. The
Insulation shall be extruded PVC to type-A of IS: 5831. In multi core
cables, the cores shall be identified by red, yellow, blue and black
coloured strips or colouring of insulation. A distinct inner sheath shall be
provided in all multi-core cables. For multi-core armoured cables, the
inner sheath shall be of extruded PVC. The outer sheath shall be
extruded PVC confirming to IS 4831 to Type ST-1 of IS: 5831 for all
cables.
All armouring shall confirm to IS 3975: 1992.
Single core cable for connection between transformer and LT board shall
be unarmoured.
HT CABLE
XLPE insulated, armoured cable shall be conforming to IS 7098 (Part-II)
and IEC 60502-2 1998. Terminating accessories shall conform to IEC
61442 1997/IEC 60502-4 1998.
The construction of XLPE insulated, armoured HT cable shall be generally
conforming to IS 7098 (Part-II). Terminating accessories shall conform to
IEC 60840 - 1999.
The first semi-conducting layer on conductor, Insulation and the second
semi-conducting layer, shall all be extruded in a single one time process.
Homogeneity and absence of void should be ensured. The manufacturer
should ensure hot cross linking process with gas or radiant curing. Cold
(chemical) galvanising process known as Sioplast process would not be
acceptable.
CABLE DRUMS
Cables shall be supplied returnable (empty drums will be the property of
contractor) wooden or steel drums of heavy construction conforming to
IS:10481. Wooden drum shall be properly seasoned sound and free from
defects. Wood preservative shall be applied to the entire drum.
Standard lengths for each size of power and control cables shall be
500/1000 meters. The cable length per drum shall be subject to a
tolerance of plus or minus 5% of the standard drum length. The owner
shall have the option of rejecting cable drums with shorter lengths.
However, the total quantity of cables after taking into consideration of all
cable drums for each size shall be within the tolerance of 2%.
2.3
A layer of water proof paper shall be applied to the surface of the drums
and over the outer most cable layer.
2.4
A clear space of at least 40 mm shall be left between the cables and the
lagging.
Each drums shall carry the manufacturer's name, the purchaser's name,
address and contract number and type, size and length of the cable, net
and gross weight and year of manufacture stencilled on both sides of
drum. A tag containing the same information shall be attached to the
leading end of the cable. An arrow and suitable accompanying wording
shall be marked on one end of the reel indicating the direction in which it
should be rolled.
Packing shall be sturdy and adequate to protect the cables, from any injury
due to mishandling or other conditions encountered during transportation,
handling and storage. Both cable ends shall be sealed with PVC/Rubber
caps so as to eliminate ingress of water during transportation and
erection.
2.5
2.6
3
3.1
3.2
3.3
TYPE TESTS
All cables shall be subjected to all type, routine and acceptance tests listed
in the relevant IS.
The type tests on cables shall be conducted on each type and size of
cables offered.
Following type tests as per IS: 7098 (Part 1) 1988 including its
amendments and additional type tests shall be carried out on 33 kV & 11
kV grade XLPE insulated cables:
a) Tests on conductor
i)
Annealing test (for Copper)
ii)
Tensile test (for aluminium)
iii)
Wrapping test (for aluminium)
iv)
Resistance test
b) Test for armouring wires/strips
c) Test for thickness of insulation and sheath
d) Physical tests for insulation
i)
Tensile strength and elongation at break
ii)
Ageing in air oven
iii)
Hot set test
iv)
Shrinkage test
e) Physical tests for outer sheath
i)
Tensile strength and elongation at break
ii)
Ageing in air oven
iii)
Loss of mass in air oven
iv)
Shrinkage test
v)
Hot deformation
vi)
Heat shock test
vii)
Thermal stability
viii)
ix)
Following type tests as per IS: 7098 (Part 2) - 1988 including its
amendments and additional type tests shall be carried out on XLPE
insulated HT cable up to 33kV earthed system:
a)
Tests on conductor
i)
Annealing test (for Copper)
ii)
Tensile test (for aluminum)
iii)
Wrapping test (for aluminum)
iv)
Resistance test
b)
Test for armouring wires/strips
c)
Test for thickness of insulation and sheath
d)
Physical tests for insulation
e)
Physical tests for outer sheath
f)
Partial discharge test
g)
Bending test
h)
Dielectric power factor test
i)
Heating cycle test
j)
Impulse withstand test
k)
High voltage test
l)
Oxygen index and temperature index test on outer sheath
Any other tests prescribed in the relevant IS/IEC.
3.5
Contractor shall submit type test reports with the bid as per
Technical Specification, Section: GTR for which test conducted once
are acceptable (i.e. The requirement of test conducted within last five
years shall only be applicable).
3.5.3
Terminating/jointing accessories as per IEC 60840:1999
a) Partial discharge test at ambient temperature;
b) Heating cycle voltage test
c) Partial discharge tests
-At ambient temperature
-At high temperature
d) Impulse voltage test followed by power frequency high voltage test
e) Test of outer protection for buried joints.
3.6
Acceptance Tests
The contractor shall offer each lot for acceptance tests to be witnessed by
Employer/BSEB representative as per test clause provided in General Technical
Requirement. The method of testing shall be as prescribed in the relevant IS/IEC.
1.1.2
1.1.3
1.1.4
1.1.5
1.1.6
1.1.7
1.1.8
The cable jointing accessories shall include the end terminating kits, straight
through joints, and also any special tools and tackles required for making these
joints.
33 kV and 11 kV cable shall be used for converting 33 kV & 11 kV overhead line
to 33kV& 11 kV underground line of suitable size.
Straight through joints shall be used in 33kV&11 kV cable. The contractor shall
minimise the use of straight joints.
T offs and spur lines may be emanating from the main 11 kV feeder. These T
offs may be through different size cables. Ring Main Unit (RMU) and termination
kits shall be used for Tee off/ Distribution transformer connections on 11 kV
cables.
The straight through joints shall be either pre-moulded type or heat shrinkable
type complete with accessories. The joint shall preferably be built up from the
same material as the main cable and shall have electrical and mechanical
withstand capabilities same as or better than the main cable. The joints shall be
suitable for tropical climatic conditions specified in this specification.
The end termination shall be outdoor anti-fog type and shall be of tapex type or
pre-moulded type or heat shrinkable type complete with accessories. The
outdoor termination should be suitable for heavily polluted atmospheric
conditions with total creepage distance of 25 mm/ kV and protected creepage
distance of not less than 50% of the total creepage distance.
The detailed description on jointing procedure shall be furnished along with the
bid. The joints should preferably be carried out by the manufacturers jointers.
The details of the end termination/ straight through joints in service with the
period in service shall be furnished.
TESTS ON ACCESSORIES
Type tests certificates shall be furnished to prove the general qualities and
design of given type of cable accessories. The type test shall conform to
relevant IEC/IS specifications.
Any damage caused, inadvertently to any utility services shall be the sole
responsibility of the contractor.
The scope also includes the Trench less laying of H.T.Cables
14.5
HANDLING
The inspection of cable on receipt, handling of cables, paying out, flaking, cushioning
with sand or sieved compacted native soil, back-filling, reinstatement of road
surfaces, providing and fixing joint markers, route markers , precautions of joint pits,
sump holes and all necessary precautions that are required shall be carefully
planned and in general conform to IS 1255-1983 or its equivalent.
14.6
DAMAGE TO PROPERTY
The contractor shall take all precautions while excavation of trench, trial pits etc., to
protect the public and private properties and to avoid accidental damage. Any
damage so caused shall be immediately repaired by contractor at his own cost and
brought to the notice of the concerned persons and to the Employer/BSEB .
- Contractor shall arrange third party liability insurance for the above purpose.
- The contractor shall bear all responsibilities and liabilities and shall bear all costs
of the damages so caused by him or by his workman or agents.
- At places where the cables cross private roads, gates of residential houses or
buildings, the cables shall be laid in RCC hume pipes.
14.7
14.8
14.9
14.11 FLAKING
The cables shall be flaked and left with slight extra lengths at jointing bays for
expansion and flexibility.
14.11.1
Sand Bedding shall be provided as detailed in section 2.10 and no special
thermal back filling is required.
14.11.2
BACK FILLING
Normally back filling shall consist of the material earlier excavated. However, bigger stones
or pieces of rock should be removed.
14.12
RCC Hume pipe shall be used for crossing of Road and cast iron or GI pipes for
railway track and water pipe line. One spare pipe at each location of 33kV & 11 kV
cable crossing shall be laid. Cable pipe size/ laying details shall be as per IS 12551983. The road cutting for cable trench, whether cement concrete, asphalt or
macadam road surface shall be undertaken after obtaining approval for cutting from
the road owning authorities, traffic police, telephone authorities and work should be
planned to be completed in the shortest possible time. Where necessary the work
shall be planned during night or light traffic periods. The railway track crossing design
shall be got approved from the railway authorities and the contractor shall do work in
coordination with them.
In the excavated trench across the road the pipes shall be laid, excavation backfilled
compacted and surface shall be redone in the shortest possible time.
Open Drain Crossing: Where ever the cable has to cross open drains, with long
span, the cable shall be laid in suitable size G. I. pipe properly joined with suitable
collars. The GI pipe shall be firmly supported on pillars, columns, or suitable support
of RCC foundation.
14.14 FOOT PATH CUTTING
The slabs, kerbstones, on the roads/ footpath shall be removed and reinstated
without damage.
14.15 REINSTATEMENT
After the cables and pipes have been laid and before the trench is backfilled, all joints
and cable positions should be carefully plotted in drawing and preserved and
provided to the Engineer of Employer/BSEB. The protective covers shall then be
provided, the excavated soil riddled, sieved and replaced. It is advisable to leave a
crown of earth not less than 50 mm and not more than 100 mm in the centre and
tapering towards the sides of the trench.
The temporary reinstatement of roadways should be inspected at regular intervals,
more frequently in rainy season and immediately after overnight rain for checking
settlement and if required, the temporary reinstatement should be redone.
After the subsidence has ceased the trench may be permanently reinstated and the
surface restored to the best possible condition.
In case of the road surface is cement concrete, asphalt or tarred macadam,
resurfacing may be done by the civic authorities against payment of the restoration
charges to be made by the contractor.
The bidders are instructed to give all the details of equipment at their disposal, to
carry out the work successfully and speedily.
14.18 BENDING RADIUS:
The minimum bending radius of XLPE insulated cables is as follows:
Cable
Bending radius
Three Core
15 x D
D means the overall diameter of the completed cable.
14.19
JOINTING AND TERMINATION OF CABLES
General: The cable jointing personnel and his crew shall have good experience in
the type of joints and terminations that are used. The jointing work shall commence
as soon as two or three lengths of cables have been laid. All care should be taken to
protect the factory-plumbed caps/ seals on the cable ends, and the cable end shall
be resealed whenever the end is exposed for tests.
Jointing of cables in carriage ways, drive ways under costly paving, under concrete
or asphalt surfaces and in proximity to telephone cables and water mains should be
avoided wherever possible.
Sufficient over lap of cables shall be allowed for making the joints.
The joint bay should be of sufficient dimensions to allow the jointers to work with as
much freedom of movement and comfort as possible. Sufficient space should be
kept below the cable to be jointed.
The joints of different phases shall be staggered.
All jointing shall be done by joint manufacturers jointers or under their supervision.
14.20 TENTS / COVERS
An enclosure or suitable protection cover shall be used in all circumstances wherever
jointing work is carried out in the open irrespective of the weather conditions. The
joint shall be made in dust free and clean atmosphere.
14.21 PRECAUTIONS BEFORE MAKING A JOINT/ END TERMINATION
The cable end seals should not be opened until all arrangement have been made for
jointing and all necessary precautions have been taken to prevent circumstances
arising out of rainy/ inclement weather conditions, which might become
uncontrollable.
If the cable end seals or cable ends are found to have suffered damage the cables
should not be jointed, without tests and rectification.
14.22 MEASUREMENT OF INSULATION RESISTANCE
Before and after jointing, the insulation resistance of both sections of cables shall be
checked.
14.23 IDENTIFICATION
The identification of each phase shall be clearly and properly noted. The cables shall
be jointed as per the design approved by the Employer/BSEB based on the proposal
submitted by the Contractor. Each cable shall have identification for phase and circuit
at joint bays.
14.24 MAKING A JOINT/ END TERMINATION
Comprehensive jointing instructions should be obtained from the manufacture of
jointing/end kits and meticulously followed.
The materials used in the joints/ end kits like ferrules, screen/armour continuity
bonds, lugs etc., shall be of good quality and conform to standards.
The jointing tools shall be appropriate and as per the requirement of jointing
XLPE/PVC cables.
14.25 CABLE TERMINATIONS
The cable terminations used are to be of outdoor type.
The preparation of the cable end for installing the terminations and the precautions to
be taken before fixing the terminations shall be followed as in the case of the cable
jointing procedures.
The instructions furnished by the termination manufacturer shall be strictly followed.
All terminations shall be done by joint manufacturers jointers or under their
supervision.
At cable terminating end, the following provisions for supply and erection are to be
included.
(i) A terminating structure should be provided where necessary for supporting the
cable to be terminated (except at the ring main unit ends)
(ii) A sufficient length of spare cable shall be left in the ground, for future needs.
(iii) The rise of the cable immediately from the ground shall be enclosed in 150 mm
dia PVC/GI pipe to protect against direct exposure to the sun.
(iv) The cable shall be properly fastened to the support using non-metallic clamps.
(v) Appropriate labels shall be fixed identifying the phase circuit, voltage and date of
commissioning etc., on the cable supporting structure.
(vi) The sealing end shall be mounted on insulators to isolate them from their
supporting steel work.
(vii) Protection from contact with the exposed metal work at the termination shall be
provided by resin bonded glass fibre shroud.
(viii) Providing earth stations with all required materials, like leads, connectors etc for
earthing of armour and screen.
14.26 BONDING OF SCREEN / ARMOUR
The screens and armour at both ends shall be brought out and solidly bonded to the
earth station.
All accessories and consumables used in the termination should be of good quality
and compatible with the cable.
14.27 CONNECTION OF RADIAL WATER BARRIER AND CABLE SCREEN
If the metallic radial water barrier is insulated from the metallic wire screen a
connection suitable to carry the currents occurring during operation must be installed
between metallic radial water barrier of the cable and metallic wire screen in joints
and sealing ends.
14.28
ERECTION OF CABLE TERMINATING STRUCTURES.
The terminating structure should be designed as per the requirement of the cable
end sealing, offered by bidder.
The mounting structure shall be of latticed GI suitably grouted to the ground.
After fixing the end termination, the cable shall be fixed to the support, with nonmagnetic material clamps to the required height securely.
The mounting structure includes the supports for cable end boxes, link boxes and
any other structure required for the intent of the contract.
All steel sections used shall be free from all imperfections, mill scales, slag
intrusions, laminations, fillings, rust etc., which may impair their strength, durability
and appearance. All materials shall be of tested quality only unless otherwise
permitted by the Employer/BSEB. The Contractor shall fabricate, provide and install
the structures.
14.29 TESTS AFTER INSTALLATION
15.
1.1. SCOPE
This specification covers requirement of 33 KV, 3x400 mm2 XLPE Cable. The
material has to be type tested as per relevant standard whenever applicable. The
test certificate issued from Laboratory recognized by Govt. of India will be accepted.
The cable should be manufactured through Dry Curing Process using Nitrogen
under controlled temperature & pressure.
1.2. APPLICABLE STANDARD:-
Except when it conflicts with the specific requirements of this specifications, the
cables, shall comply with latest version of IS: 7098 (PT-D)/ 1985 with latest
amendment specification for cross linked polythene insulated PVC sheathed cable.
The cable should be manufactured through Dry curing process using Nitrogen under
controlled temperature and pressure as medium.
Indian Standards
IS- 7098
Mild steel wires, formed wires and tapes for armoring of cables.
The rated voltage of the cables shall be 19 KV / 33 KV voltage grade and the
maximum operating voltage shall be 10 % higher than the rated voltage.
Maximum continuous operating temperature (combination of ambient temperature
and temperature rise due to load) shall be 900C under normal operation and 250oC
under short circuit conditions.
1.4. TYPE OF CABLES :
The type of cables under this specification shall be three cores armoured screened.
1.5. STANDARD SIZES OF CABLES.
The size of the cables required shall be 400 mm2, 33 KV (E), 3 cores.
1.6. CONTINUOUS CURRENT AND SHORT CIRCUIT RATINGS:-
Sl. No.
400 mm2
1.
In ground
(Amp)
In Air (Amp)
432
574
37.6
1.7.1. Conductor :
The cable conductor shall be round, stranded and compacted aluminum of nominal size
stipulated. The corresponding maximum Wire diameter & number of wires in the conductor
shall be as given in IS: 8130/1984.
Sl. No.
Sizes of 3 core
cables (Sq. mm)
1.
400 mm2
53
of
0.0778
1.7.3. Insulation
The insulation shall be of extended cross linked polyethylene (XLPE) of nominal insulation
thickness of 8.8 mm for 33kv and its properties shall conform to IS: 7098 (pt-II) with latest
amendment.
metallic, part shall be applied directly over the insulation of each core and shall
consist of either a semi-conducting tape or extruded semi-conducting
compound or a combination of the two or either material with semi-conducting
coating.
b) The metallic part shall consist of either tape, or braid or concentric serving of
wires or a sheath and shall be non-magnetic and shall be applied over the nonmetallic part.
1.7.5. Core Identification and laying up of cores.
The core identification and laying up of cores shall be as per IS: 7098 (pt-II). For
identification of different cores in three core cables, use of Colored stripes, red, yellow and
blue or use of numbered strips shall be employed.
1.7.7. Armoring:
For three core cables, armoring may be applied over the inner sheath . The method, type,
dimensions, joints, conductance etc. of armour shall conform to IS: 7098 (pt-II) with latest
amendment.
1.8.1. The following tests shall be carried out on the cables as per IS: 7098 (PartII). With latest amendment.
a) Type tests:
i)
Tests on conductor
ii)
iii)
iv)
v)
vi)
vii)
viii)
Tensile test.
Wrapping test
Resistance
ix)
x)
xi)
xii)
xiii)
xiv)
b) Acceptance tests.
i)
ii)
iii)
iv)
v)
vi)
vii)
viii)
ix)
Tensile test.
Wrapping test.
Conductor resistance test.
Test for thickness of insulation and sheath.
Hot set test for insulation.
Tensile strength and elongation at break test for insulation and sheath.
Partial discharge test.
High voltage test.
Insulation Resistance (volume resistivity) test.
c) Routine tests.
i)
ii)
iii)
i)
ii)
iii)
The above tests shall be carried out on a sample length of cable of approved size.
The manufactured cable will be acceptable only after such Sample test is carried out at
CPRI or at suppliers works and approved by the purchaser.
Alternatively the manufacturer shall submit a copy of the S.C. test certificate if the S.C.
test has been carried out earlier at CPRI or ERDA or any other accredited laboratory on
one of the sizes of each voltage grade.
1.9. PACKING AND MARKING:
1.9.1. Packing
The cables shall be supplied in wooden drums conforming to IS: 10418 with latest
amendment. The standard length of the cable in each drum shall be 0.200 KM 5%.
1.9.2. Marking:
The cable drum shall carry the information as per requirement of IS: 7098 (Part II) with
latest amendment.
1.9.3. The manufacturers name or trade mark, the voltage grade, year of
manufacture, etc. may be printed or embossed on the cable as stipulated in IS:
7098 (Part II) with latest amendment.
1.9.4. INSPECTION:
All the tests and inspection shall be made at the place of manufacturer unless otherwise
especially agreed upon by the manufactures and purchaser at the time of purchase. The
manufacturer shall afford the inspector representing the purchaser all reasonable facilities
without change, to satisfy him that material is being furnished in accordance with the
specification.
The purchaser has the right to have tests carried out at his own cost by an independent
agency whenever there is a dispute regarding the quality of supply.
1.10.
The Guaranteed technical particulars of the cables in the format as per Annexure-A shall be
given by the bidder along with the tender. This is essential for consideration of the tender
failing which the tender will be rejected.
Annexure- A
GUARANTEED TECHNICAL PARTICULARS (Three Core, 33 KV XLPE cable 3x400 mm2)
Sr. Description
SBPDCLs
requirement
1.0 Type
A Continuous
90C
250C
Short time
8.0 Conductor
A Material and Grade
Size
Offered
D Conductor Shape
E
Thickness (Approx.)
Diameter over conductor screen
As per Table 2 of IS
8130
Compacted Circular
Manufacturer
Standard( mm)
.mm
0.0778 (Ohms / km)
0.50 mm.
. mm
Insulation material
Nominal thickness
Minimum thickness
Diameter over Insulation (Approx.)
Make and grade of Insulation
compound
11.0 Insulation Screen
A
i) Thickness of freely
strippable
Semi
conducting screen
ii) Make and grade of
semiconducting
compound
2.1.3
8.8 mm
7.82 mm
--- mm
0.50 mm.
Yes / No
iii) Printing
iv) Thickness
& other details of Water
swell- able tapes
a) 0.30 mm
b) Weight : 118 gm/
sqmm
c) Swell height shall be
12mm in 1min.
d)
Compatible
to
strippable
/
nonstrippable semicon, over
which, it is applied.
e) Make & Grade
.(mm)
KA for Sec
mm
By colored strips over
cores applied helically /
longitudinally
Minimum thickness
14.0 Armour
A Minimum Number of Steel wires / GI
Strip
B
As per Table 4 of IS
7098 Part-2
4 x 0.8 mm
E
F
G
H
Min. 90 %
.
mm
..
15.0
A
Thickness (Minimum)
C
D
Colour
Embossing
Sqmm
16.0
.mm
17.0
18.0
Type of Drum
Steel / Wooden
19.0
20.0
Required
b. End cap
Required
Weight
a) Net Weight of cable ( Approx.)
21.0
22.0
23.0
Kg
Kg
. Amps
b) In duct 30 C
c) In Air 40 C
Short circuit current carrying capacity
for 1 sec of conductor
. Amps
. Amps
. K Amp
A
B
C
D
E
F
AC Resistance
Reactance at 50 C/s
Impedance
Zero sequence impedance
Positive sequence impedance
Negative sequence impedance
Capacitance
24.0
25.0
26.0
i)
ii)
Iii)
iv)
27.0
.. Kg / Km
Ohm/Km
Ohm/Km
Ohm/Km
Ohm/Km
Ohm/Km
Ohm/Km
)
)
)
)
)
)
C
C
C
C
C
..(
..(
..(
..(
..(
..(
Touching Trefoil
Nos.
Nos.
Nos.
Nos.
30 N / mm2
28.0
29.0
Required
16.
2.1. SCOPE: - The specification covers the design, manufacture, testing and inspection before
despatch and delivery at site Stores.
The specification covers Oil immersed, Naturally Air cooled (type ONAN), outdoor type, three
phase, 50 Hz, 11/.433 KV, CORE TYPE, step down conventional distribution transformers of
capacities 200 & 315 KVA. Transformers should be suitable for service under frequency
fluctuation of 4% and voltage fluctuation +10% / -25% on HV side. The full load rated
current on HV & LV side at normal voltage ratio of each rating of transformers shall be as
under:S.
No.
RATING IN
KVA
LV Side
200
10.50
266.67
315
16.53
420.00
2.2. APPLICABLE STANDARDS:e) Unless otherwise modified in the specification, the transformers shall comply with the
requirement of ISS: 1180 (latest issue) 2026 (latest issue) and REC Specification
2/1978 and ISS: 2099 (latest issue). The bushings used shall conform to ISS: 2099 &
3347 (latest issue) except as modified herein.
f) Type:
The transformers shall be double wound, three phase oil immersed, oil
Natural Air Natural cooled (type ONAN), CORE TYPE suitable for outdoor
installation in tropical climate and shall be insulated with DPC insulation on
HV & LV windings. Insulation should be of temperature class as per the
temperature rise stipulated in this specification.
The neutral point of the secondary (LV winding) is intended for solidly
earthed system and should be brought out to a separate insulated terminal,
enabling external insertion of a current transformer in the earth lead to be
connected wherever required.
g) Climatic Conditions:
i)
(
Peak outdoor temperature
500 C (minimum)
ii)
(
Maximum Oil temperature
iii)
(
Maximum relative humidity
95%
(
Minimum relative humidity
10%
iv)
v)
vi)
vii)
viii)
ix)
Average
(
No. of thunder storm
days per annum
Average
(
number of rainy days
per annum
Number
(
of months of tropical
monsoon conditions.
(
Average annual rainfall
(
Wind pressure
40 days
90 days
3 Months
1450mm
150 Kg/m2
The transformer shall generally be for use in moderately hot and humid tropical
climate, conducive to rust and fungus growth.
2.3. RATINGS:
Primary voltage - 11 KV
Secondary voltage - 0.433 KV
The windings of the transformers shall be connected in delta on primary side and star on the
secondary side. The neutral of the LT winding shall be brought out to a separate terminal.
The vector group shall be Dyn-11
2.4.
2.5.
TEMPERATURE RISE:Temperature rise for top oil over an ambient of 50 oC should be 45oC max. (Measured by
thermometer as per IS-2026) Temperature rise for windings over an ambient of 50 oC should
be 50oC max. (Measured by resistance in accordance with IS: 2026)
2.6.
2.7.
TAPS:
For ratings 200 KVA to 315 KVA, tapping shall be provided on the higher voltage winding for
variation of HV voltage within range of (+) 3% to (-) 9% in the steps of 3%. Tap changing
shall be carried out by means of an externally operated self position switch and when the
transformer is in de-energized condition, switch position No.1 shall correspond to the
maximum plus tapping. Each tap change shall result in variation of 3% in voltage. Provision
shall be made for locking the taping switch handle in position. Suitable Aluminium anodized
plate shall be fixed for tap changing switch to know the position no. of tap.
2.8.
should not get saturated. The supplier shall furnish necessary design data in support of this
situation.
(d) Flux Density: - Flux density at rated voltage and frequency shall not exceed 1.55 Webbers
per sq. meter. No load current at rated voltage and at 112.5% of rated voltage shall not
exceed the values given below:RATING
PERCENTAGE OF RATED FULL LOAD
IN KVA
CURRENT
100% OF RATED
112.5% OF RATED
VOLTAGE
VOLTAGE
200
2
4
315
Test for magnetic balance by connecting the LV phase by phase to rated phase voltage and
measurement of an, bn, cn voltages will be carried out.
(e) Details of Core: - The figures shown in the table are minimum acceptable values:S. No.
PARTICULARS
UNIT
RATING IN KVA
315
No.
mm
155
170
160
200
Core Clamping:
a.
Channel
mm x
100x50
125x65
b.
mm /
Nos.
16 /2 in Parallel
(Total 8 no s.)
16 /2 in parallel
(Total 8 nos.)
c.
mm /
Nos.
16 / 8
16 / 8
d.
Core Bolts & Tie Rods to be painted with Varnish/Hot oil paint and
effectively insulated
e.
f.
g.
h.
i.
2.9.
200
WINDINGS:
Cm2
a) Materials: - Double paper cover Aluminium Conductor shall be used for ratings upto 200
KVA. For ratings above 200 KVA double paper covered electrolytic copper shall be used.
b) Current Density for HV & LV should not be more than 2.8 A/sq. mm. for copper and 1.6
Ampere per sq. mm. for Aluminium Conductor in any part of the winding.
c) HV Cross section shall not be less than;i) 200 KVA 3.79 Sq. mm
ii)
315 KVA
3.40 Sq. mm
d) LV Cross section shall not be less than:i) 200 KVA 168.0 Sq. mm
ii)
315 KVA
156.0 Sq. mm
315 KVA
7.07 Ohms
2.10.
315 KVA
0.00278 Ohms
2.11.
(d) Phase to phase clearance between HV conductor shall not be less than 10 mm and
minimum of 2x1 mm press board must be provide to cover the Tie rods as phase barrier.
(e) The minimum electrical clearance between the winding and body of the tank (between
inside surface of the tank and outside edge of the windings) should be 30 mm.
(f) Minimum end insulation to earth shall be 25 mm.
(g) No. of coils HV/phase (minimum):
i) For 200 & 315 KVA - 6 Nos.
(h) Thickness of locking spacers between HV coils- 10 mm (Minimum)
(i) No. of axial wedges between LV and HV winding equi-spaced around L.V.- 8 for 200 KVA
- 12 for 315 KVA.
(j) Minimum external clearances after providing bimetallic clamps on Bushing terminals:
Phase to Phase
Phase to Phase
2.12.
HV
255 mm
140 mm
LV
75 mm
40 mm
TANK: The transformers tank shall be of robust construction and shall be built of
electrically welded M.S. Plates. All joints of tank and fittings shall be oil tight and no
bulging shall occur during service. The tank design shall be such that the core and
windings can be lifted freely. The tank plate shall be of such strength that the
complete transformer when filled with oil may be lifted easily by means of the lifting
lugs provided. Tank inside shall be painted by varnish/hot oil paint. Top cover shall
be slightly sloping (difference of heights should be 20 mm + 10%) towards H.V.
bushing and cover the top with end walls. Shape of the tank shall be rectangular
only. No other shape will be accepted. The tank shall be fabricated by welding at
corners. No Horizontal or vertical joints in tank side and its bottom or top cover will
be allowed.
(a)
(b) Reinforced by welded angle of size 50x50x6 mm on all the outside walls on the edge of
tank to form three equal compartments in case of transformers above 100 KVA rating. One
face of reinforcement angle should be continuous welded with the tank surface such that
other side of the angle forms inverted L. The permanent deflection is not more than 5 mm
up to 750 mm. length & 6 mm. up to 1250 mm. length, when transformers tank without oil is
subjected to a vacuum of 760 mm. of mercury.
(c) Lifting lugs: 4 Nos. welded heavy duty lifting lugs of M.S. Plate 8 mm. thick suitably
reinforced by vertical supporting flat welded edgewise below the lug on the side wall, upto
the reinforcing angle, for transformers of 200 KVA rating and above.
(d) Pulling Lugs : 4 Nos. of welded heavy duty pulling lugs of M.S. Plates of 8 mm. thick shall
be provided on width side to pull the transformers horizontally upto 100 KVA and on length
side for above 100 KVA.
(e) Top cover Gasket & Bolts:
The Gasket in one piece shall be provided in between Top Cover Plate
and Tank shall be of 6 mm thick oil resistant Neoprene Rubberized Cork
sheets of best quality confirming to IS: 4352, Part -II for ratings above
100 KVA.
For ratings above 100 KVA GI Nut Bolts of 1/2" dia with one plain washer
shall be used for top cover fixing spaced at 4" apart.
The height of the tank shall be such that the minimum clear height upto
the Top Cover Plate of 120 mm is achieved from Top Yoke in case of
transformers upto 100 KVA. The above clearance is achieved from the live
part of the tap changer in case of transformers above 100 KVA.
The top cover of the main tank shall be provided with an air release plug
to enable air trapped within to be released.
h) Heat dissipation by tank walls excluding top and bottom should be 500W/m 2.
i) Heat Dissipation by fin type radiator made of 1.25 mm thick MS sheet, will be worked
out on the basis of manufacturers data sheet. Supplier should submit the calculation
sheet.
j) 2 Nos. Radiators shall be provided on both LV and HV sides and shall be of fin type.
They should be fixed at right angle to the sides and not diagonally.
k) Arrangement for studs provided for fixing of HV bushings should be in diamond shape
so that the arcing horns are positioned vertically.
2.13.
RATING
IN KVA
PERMISSIBLE OIL
ABSORPTION
IN LITERS
200
400
15
315
500
19
NOTE: If the absorption of oil in core and winding Assembly is more than permissible value,
first filling of oil volume should be increased accordingly. Detail calculation of absorption
should be submitted.
2.14.
CONSERVATOR:
(a) The total volume of conservator shall be such as to contain 10% quantity of the oil.
Normally 3% quantity of the total oil will be contained in the conservator. Dimension of the
conservator shall be indicated in General arrangement drawing.
(b) Die cast Oil level indicator shall be provided on the side which is fully covered with
detachable flange with single gasket and tightened with M.S. Nut -Bolt and will be fixed on
the side of rating plate and drain valve.
(c) The pipe from the conservator tank connecting to main tank shall be of 30 mm internal
dia and shall have a slopping plate so that the oil falling from the pipe shall not fall directly on
the active job and shall fall on the side walls only. The pipe should project in the conservator
so that its end is approximately 20 mm above the bottom of the conservator. Thus slopping
plate should be fitted such that clearance from the yoke/live part of the tap changer is
maintained as prescribed i.e. 120 mm.
The conservator shall be provided with the drain plug and a filling hole, with cover. In
addition, the cover of the main tank shall be provided with an air release plug.
2.15.
BREATHER
Breather joints will be screwed type. It shall have die-cast Aluminium body with tin container.
Volume of breather shall be suitable for 500 gm. of silica gel for transformers upto 200 KVA
and 1 g for transformers above 200 KVA rating. After fitting breather, the thread must be
sealed with paint/compound to avoid air entry. The Breathers must be as per the technical
specifications, Guaranteed Technical Particulars and drawing enclosed.
2.16.
TERMINALS:
(a) For ratings above 100 KVA:
(i) Brass rods 12 mm dia for H.T. with necessary caps, nuts, check nuts and plain
thick washers of Brass.
(ii) Tinned copper rods 20 mm dia for 200 and 315 KVA and 30 mm dia for 500 KVA
transformers with necessary caps, nuts, check nuts and plain thick washers of tinned
copper for LT.
(b) H.T. and L.T. bimetallic connectors shall be provided with Transformer for all rating. The
technical specifications, Guaranteed Technical Particulars and drawings of these connectors
are shown in Annexure-VII(C). The type test certificates of the connectors being used shall
be produced at the time of inspection.
2.17.
BUSHINGS:
(i) For 11 KV - 12 KV Bushing will be used and for 433 volts 1.1 KV terminal bushing will be
used. Bushings of the same voltage class shall be interchangeable. Bushings with plain sheds
as per IS - 3347 shall be mounted on side wall of the tank and not on the top cover. Only
continuous sheet metal pocket shall be provided for mounting of all H.V. / L.V. bushings and
the same shall not be fixed on pipes. Sheet metal pocket shall be designed in such a way that
all HT bushings shall remain parallel and equidistance all through and inside connections of
windings to bushings shall remain within the pocket. Bushings having type tested as per IS3347 shall only be acceptable.
(ii) Internal Connections: In case of HV winding, all jumpers from windings to bushing
shall have cross section larger than the winding conductor (normally, 1.5 times). For copper
winding, joints will be made by using silver brazing alloy. For Aluminium winding, L & T
Alkapee Aluminium brazing rods with suitable flux will be used or alternatively joints will be
made by using tubular connectors properly crimped at three spots. Aluminium brazing rods to
be used, ring formed on other end and nut bolting on HV bushing stud.
LT star connection will be made by using 6mm thick Aluminium/Copper Flat and properly
brazed or bolted with the crimped lugs on windings by means of plain and spring washers
and lock nuts to the flat. Other end of the conductor is brazed on L shape 6mm thick
Aluminium /copper flat and flat nut bolted with neutral bushing stud. ALTERNATIVELY, for 63
& 100 KVA ratings all the three terminals of LV windings together with terminals for neutral
bushing shall be properly brazed and then covered with Aluminium tubular sleeve of suitable
length and cross sectional area duly crimped in order to provide sufficient strength to the
joint. The star connection should be wrapped with cotton/paper tape.
The connection for LV winding to bushings shall be made 6mm thick L shape Aluminium/
Copper flats nut bolted with LV Bushing stud.
For delta formation on HV side, copper wire having cross sectional area 1.5 times the HV
winding wire area should be used. SRBP tube/insulation paper should be used on delta
connection and on the portion of HV winding joining to HV bushing.
2.18.
ROLLERS:
For Transformers of rating 200 KVA and above four nos. flat rollers of 150 mm diameter and
50 mm width shall be provided.
2.19.
2.20.
2.21.
FITTINGS:
The fittings on the transformers shall be in accordance to the Annexure-II of the TS.
2.22.
TRANSFORMER OIL:
The transformer shall be supplied complete with first filling of oil and the same shall comply
with IS: 335-1983 with latest version thereof and ageing characteristics specified. These
characteristics are shown in Annexure-I. Type tests certificate of oil being used shall be
produced at the time of inspection.
2.23.
Liquid
paint
24.6
Epoxy
(primer)
24.7 P.U. Paint (Finish coat)
Hot oil paint/Varnish
Outside
Outside
Inside
01
02
01
30
25 each
35/10
The following routine tests and type tests are required to be carried out on the transformers:A) (i) Routine Tests:- Before despatch each of completely assembled transformer shall be
subjected at the manufacturers works to the following routine tests in accordance with the
details specified in IS:2026.
(a) Measurement of winding resistance.
(b) Ratio, polarity and phase relationships.
(c) Impedance voltage.
(d) No load losses and no load current.
(e) Load losses.
(f) Insulation resistance.
(g) Separate source voltage withstand.
(h) Induced over voltage with stand.
(ii) Unbalanced current test: The value of zero sequence current in the star winding shall not
be more than 2% of the full Load current in accordance with 26(d).
(iii) Pressure and vacuum test: The tank shall be fixed with a Dummy cover with all fittings
including bushing in position and be subjected to following pressure/vacuum created inside
the tank:(i) 0.8 Kg./cm sq. above atmospheric pressure for 30 minutes.
(ii) A vacuum corresponding to (-)0.7 Kg/cm sq. for 30 minutes.
Permanent deflection of flat plate, after pressure has been released, shall not exceed the
values given below:Length of plate Deflection:
Up to 750 mm 5 mm
751 to 1250 mm
6 mm
1251 to 1750 mm
8 mm
Supplier should ensure that each fabricated tank is subjected to pressure & vacuum test at
his work and confirmation to this effect is submitted in the test certificate along with routine
test certificate while offering the material for final/pre-dispatch inspection.
(iv) Vector Group Test: - All the transformers must be complied with requirements to confirm
the Vector Group of Dyn-11.
B) TYPE TESTS:
In addition to the routine tests as above, the following type tests shall be carried out on the
transformers in accordance with IS:1180 and 2026/1977 as amended from time to time:(a) Lightening impulse voltage withstand test
(b) Dynamic ability to withstand short circuit test.
2.25.
The suppliers may carefully note our following specific requirements of short circuits
& impulse voltage:
(a) Short Circuit Test and Impulse Voltage Withstand Test: The SBPDCL intends to procure
transformers designed and successfully tested for short circuit and impulse test. In case the
transformers proposed for supply against the order are not exactly as per the tested design,
the supplier shall be require to carry out the short circuit test and impulse voltage test at
their own cost in the presence of the representative of the SBPDCL. The supply shall be
accepted only after such test is done successfully, as it confirms on successful withstand of
short circuit and healthiness of the active parts thereafter on un-tanking after a short circuit
test. Apart from dynamic ability test, the transformers shall also be required to withstand
thermal ability test or thermal withstand ability will have to be established by way of
calculations. It may also be noted that the SBPDCL reserve the right to conduct short circuit
test and impulse voltage test in accordance with the ISS, afresh on each ordered rating at
SBPDCL cost, even if the transformers of the same rating and similar design are already
tested. This test shall be carried out on a transformer to be selected by the SBPDCL either at
their works when they are offered in a lot for supply or randomly from the supplies already
made to SBPDCL Area Stores. The findings and conclusions of these tests shall be binding on
the supplier.
In case the transformer does not pass in either of the tests and if the active part details are
not found to be in line with the design tested and approved, the following punitive measures
shall be taken:(i) 5% payment of the bill for the supplies already made will be recovered by the
SBPDCL.
(ii) For transformers already supplied, the guarantee period shall stand twice the
normal guarantee period incorporated in the order and the period of performance
Security Deposit shall be suitably extended to cover the extended guarantee period.
(iii) Further, supply of balance quantity of transformers will not be accepted by the
SBPDCL, till another transformer from the manufactured batch is satisfactorily tested
(OR transformers are modified according to the tested design) for both tests at your
cost and consequent to this if there is any delay in executing the order, the same
shall be to your account. SBPDCL reserves the right to take action as per terms and
conditions of the order.
(iv) The tests charges shall be borne by the firm. Please note that if the terms and
conditions detailed above regarding short circuit withstand test & impulse voltage test
on transformers and procedure for these tests are not accepted by you in full, action
will be taken as deemed fit as per the terms of the order.
(b) Temperature rise test: - Heat run test shall have to be conducted at suppliers cost on one
transformer of each rating in any offered lot during the course of supplies. In case of
transformers with tap, test shall be conducted on the lowest tap feeding corresponding losses
at 75oC.
To facilitate conduction of heat run test on any unit in any lot at any point of time during the
supplies, the manufacturers will provide a thermometer pocket which gets immersed in oil on
the side of the transformer in all the transformers. This pocket shall also be used for
connecting thermal sensing device to monitor the variations in temperature and whenever
required to operate the protective devices. The Sensor pocket shall be of 12mm diameter
with blanking screwed cap, removable at site. The depth of the projecting stem of this pocket
inside the transformer will be below oil level. It shall not infringe with electrical clearance nor
obstruct the un-tanking of the active part.
(c) Over Fluxing of Core:Transformer shall be subjected to test for over fluxing of core, wherever required by the
SBPDCLs inspecting officer.
(d) Test for spill current in neutral:The test will comprise of measuring current between shorted secondary phases and neutral
on applying impedance voltage at primary winding. The value should not exceed 2% of full
load current.
2.26.
ACCEPTANCE TESTS:
The following tests shall be witnessed by the Purchaser/Representative at the firms works:(i) All the routine tests as mentioned in 25(A) above shall be performed on minimum 10%
quantity of offered lot.
(ii) Heat run test On one unit out of total ordered quantity.
(iii) Verification of active parts on one unit of each rating of offered quantity along with
weighment of the complete unit.
2.27.
TESTING FACILITIES:
The tenderer should have adequate testing facilities for all routine and acceptance tests and
also arrangement for measurement of losses, resistance etc.
2.28.
INSPECTION:
(a) To ensure about the quality of transformers, the inspection shall be carried out by the
SBPDCLs representative at following two stages:(i) When the raw material is received, and the assembly is in process in the shop
floor.
(ii) At finished stage i.e. transformers are fully assembled and are ready for despatch.
(b) After the main raw-materials i.e. core and coil materials and tanks are arranged and
transformers are taken for production on shop floor and a few assembly have been
completed, the firm shall intimate the O/o C.E.(RE), SBPDCL, Patna in this regard, so that an
officer for carrying out such inspection could be deputed, as far as possible within seven days
from the date of intimation. During the stage inspection a few assembled core shall be
dismantled to ensure that the CRGO laminations used are of good quality. Further, as and
when the transformers are ready for despatch, an offer intimating about the readiness of
transformers, for final inspection for carrying out tests as per relevant I.S.S. and as in clause
25(A) above, shall be sent by the firm along with Routine Test Certificates. The inspection
shall normally be arranged by the O/o C.E.(RE), SBPDCL, Patna at the earliest after receipt of
offer for pre-delivery inspection.
(c) In case of any defect/defective workmanship observed at any stage by the SBPDCLs
Inspecting Officer, the same shall be pointed out to the firm in writing for taking remedial
measures. Further processing should only be done after clearance from the Inspecting
Officer/ this office.
(d) All tests and inspection shall be carried out at the place of manufacture unless otherwise
specifically agreed upon by the manufacturer and purchaser at the time of purchase. The
manufacturer shall offer the Inspector representing the Purchaser all reasonable facilities,
without charges, to satisfy him that the material is being supplied in accordance with this
specification. This will include Stage Inspection during manufacturing stage as well as Active
Part Inspection during Acceptance Tests.
2.29.
RANDOM TESTING OF TRANSFORMER:Random sample checking and testing of the transformer selected at random from the
supplies made to the Area Stores shall be done for verification of technical details, design,
routine test and losses as per approved G.T.P., drawings and technical specification of the
order. Please note that:(A) (i) Some of the transformers shall be selected randomly from the lot received in Area
Stores and shall be subjected to routine testing as per IS:1180 and 2026 (with latest
amendments) at MTRU, Jabalpur/ CPRI, Bhopal/CPRI, Bangalore/ERDA, Vadodara or any
reputed Govt. Laboratory.
(ii) It is only after the results of randomly selected transformers are found satisfactory, the
MRC shall be issued and the transformers of the lot shall be accepted/ issued to field units.
(iii) Serial number, name of the inspecting officer and his designation shall have to be
embossed by the manufacturer on the tank of every transformer.
(B) In case of emergency, the transformers are issued in the field before obtaining the test
results from the Laboratory and in the event of failure of any transformer in any/all routine
tests later on, the following action shall be taken for that particular lot/ order only:(i) 5% payment of the bill for the supplies already made will be recovered by
SBPDCL.
(ii) For transformers already supplied, the guarantee period shall stand twice the
normal guarantee period and the period of performance security deposit shall be
suitably extended to cover the extended guarantee period.
(iii) The supplier shall be intimated about the results of such test to make suitable
improvement in his manufacturing process and to ensure quality control.
(iv) If any transformer(s) are available in the area stores, these shall have to be
replaced by the manufacturer at his own cost.
(v) One unit of each capacity from the next lot shall be sent to the identified
laboratory for carrying out routine tests. In case the transformer fails again in any or
all routine test, no further supply shall be accepted and the transformers available at
area stores supplied against the current order shall have to be taken back by the
manufacturer at his own cost.
(vi) The manufacturer will have to carry out suitable improvement in the design of
the transformer and get it type tested in presence of Companys representative at his
own cost. It is only after the transformer successfully passes the type test, the
supplies shall be resumed. Further, the penalty towards delayed supplies shall be to
manufacturers account (if any).
(C) The Purchaser has all the rights to conduct the test including type tests, at his own cost
by an independent agency whenever there is dispute regarding the quality of supply or
interpretation of test results. In the event of failure of transformers in such tests, the
expenses incurred in testing shall be to the suppliers account as already mentioned above in
case of random testing.
2.30.
2.31.
2.32.
DRAWINGS:
The dimensional drawing and internal construction drawing of each rating of transformer &
Silica gel Breathers for 500 gm and 1 Kg capacity and HT & LT bimetallic connectors shall be
submitted with the tender. Guaranteed and other technical particulars of the transformers
should also be submitted in A-4 size for our approval.
2.33.
GUARANTEE:
2.33.1.1.
2.33.2.
2.33.3.
9.
Label design, manner of display of Star rating in the 200KVA Distribution
Transformer
9.1
Material of the label shall be non detachable weather proof type. The Design
of the Label, manner of display of label and its colour scheme will be in accordance with
the notification of Bureau of Energy Efficiency, New Delhi.
To ensure about the quality of transformers, the inspection shall be carried out by
the representative of the SBPDCL at following two stages:(i) Where raw material is received, and the assembly is in process on the shop floor.
(ii) At finished stage i.e. transformers are fully assembled and are ready for dispatch.
After the main raw-materials i.e. core and coil materials and tanks are arranged and
transformers are taken for production on shop floor and a few assembly have been
completed, the firm shall intimate the O/o C.E.(RE), SBPDCL, Patna in this regard, so
that a team of officers for carrying out such inspection could be deputed, as far as
possible within fifteen days from the date of intimation. During the stage inspection a
few assembled core shall be dismantled to ensure that the CRGO laminations used
are of good quality and manufacturing is confirmed in line with approved Guaranteed
Technical Particulars/Drawings. The report of stage inspection is to be prepared in
the prescribed proforma.
A quantity of more than 100 Nos. shall not be entertained for stage inspection.
Further, the stage inspection shall be carried out in case:(a) At least 25% quantity offered has been tanked, and
(b) Core coil assembly of further atleast 30% of the quantity offered has been completed.
Quantity offered for stage inspection should be offered for final inspection in full
within 15 days from the date of issue of clearance for stage inspection, otherwise
stage inspection already cleared shall be liable for cancellation.
The checks to be exercised during the stage inspection have been listed in the stage
inspection proforma.
As and when the transformers are ready for despatch, an offer intimating about the
readiness of transformers for carrying out pre-despatch inspection as per relevant
I.S.S. and as in clause-25 (A) of Annexure-III, shall be sent by the firm. The
inspection shall normally be arranged by the SBPDCL at the earliest after receipt of
offer for pre-delivery inspection.
During the pre-despatch inspection, the routine tests as per IS:1180 & 2026 shall be
carried out at the works of the firm on randomly selected transformers in presence of
companys representative.
Further, one unit of each rating offered shall be dismantled at the time of predespatch inspection for physical verification for the constructional details. The report
of pre-despatch inspection is to be prepared in the prescribed Performa.
Please ensure that reports of stage inspection and pre-despatch inspection are prepared
strictly in the prescribed Performa and no detail is left blank. Incomplete report may cause
delay in supply of transformers which shall be to the suppliers account.
Particulars
System Voltage (Max.)
Rated Voltage HV
Rated Voltage LV
Continuous Max. Rating (kVA)
Normal Ration of Transformation
Method of Connection (Vector Group)
Max. Hot spot Temp. (ambient air temp. shall be
taken as 50o C
Max. Oil Temp. (ambient air temp. taken as 50 o C)
10
Flux Density
11
12
Type of Transformer
CORE:
200 kVA
315 kVA
-- 12 kV --- 11 kV --- 433 250 --- 11/0.433 KV -Dyn 11 -
95 o C -
100 o C -
Magnetizing Current
(% of rated current)
Current Density
(i) HV winding
(ii) LV winding
15
Windings
(a) Material
(i) HV winding
(ii) LV winding
(b) Size of winding wires for
(i) HT
(ii) LT
(c) Type of insulation of
(i) HV winding
(ii) LV winding
(d) Internal & external diameter of
(i) HV coil
(ii) LV coil
(e) No. of coils/phase
(i) HV
(ii) LV
(f) No. of turns per coil
(i) HV
(ii) LV
17
18
19
20
21
22
23
24
25
e) Between phases
f) End insulation
CLEARANCES:a) LV to Core (Radial)
b) Between HV & LV (Radial)
c) Phase to phase between HV conductor (with
providing min. of 2x1 mm Press Board to cover the
rods)
d) Between winding & body
i) Length wise
ii) Breadth wise
e) End insulation
f) Thickness of locking spacers between HV coils
g) Axial wedges between HV & LV coils
h) Clearance between top cover and top most live part
of tap changer for 200 KVA and above
i) No. of radial spacers per phase between HV coil
j) Size of duct between LV & HV
TANK
(a) Shape
(b) Thickness of tank sheets:
(i) Top & Bottom
(ii) Side walls
(iii) Collar
(c)Internal dimension of tank:
(i) Length (l)
(ii)Breadth (b)
(iii)Height (h1)
(h2)
(Difference between h1 & h2 should be 20mm)
(d) Gasket used between top cover and tank
(i) Material (Must be of best quality and oil resistant)
(ii) Thickness
(iii) Whether the gasket is joint-less and in one piece
(e) Pulling lugs
(i) No.
(ii) Thickness
(iii) Position of fixing
(f) Lifting Lug
(i) No.
(ii) Thickness
(g) Reinforcement of tank sides by providing angle of
size 50x50x6mm at two places for transformers above
100 KVA, respectively.
(h) Dia & thickness of flat rollers for 200 KVA and above
ratings Transformers.
(i) Whether all the transformer tanks which are to be
supplied are complied with the pressure and vacuum
tests as per technical specifications.
(j) Top cover of the tank provided with the:(a) Air release plug 1 no.
(b) Thermometer pocket 1 no.
(c) Top cover lifting lugs 2 nos.
BUSHING:
(a) Characteristics:
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
(c) Conservator
(i) Volume
(ii) Weight
(d) Total oil filled
(i) Volume
(ii) Weight
Overall dimension of Transformer:
(a) Length
(b) Breadth
(c) Height
Engraving of S. No. & name of firm :
(a) On bottom core clamping channel
(b) On Side wall & top cover of tank
(c) Date of dispatch on the Tank
MS Plate of size 125x125mm welded on side wall
stiffener of tank with engraving of :
i) Name of the firm
ii) Rating
iii) Serial Number
iv) Order No. & date
v) Date of despatch
vi) Name of Inspecting Offer
vii) Designation
Weight of windings only (Dry/ without oil soaking)
a) HV
b) LV
Weight of core & winding assembly with core channels,
core bolts, Tie rods, insulation etc. complete
Un-tanking weight of core & winding (including oil
absorption)Weight of tank & fittings including radiators,
conservators etc.
Weight of complete transformer including fittings & oil
[S. No. 35 + 37 + 30 d(ii)]
Dry film thickness of Paint:(i) Thermosetting powder paint:(a) (Inside) one coat (30 micron)
(b) (Outside) one coat (60 micron)
(ii) Liquid Paint:(a) Epoxy (Primer)
(Outside) one coat (30 micron)
(b) PU Paint (Finish coat)
(Outside) two coats (25 micron each)
(c) Hot Oil paint/Varnish
(Inside) one coat (35/10 micron)
Colour of transformer:(i) Conservator tank
(ii) Main tank & radiator
Reference of type test reports:
(a) Short circuit test
(i) Report no.& date
(ii) S. No. of DTR.
(b) Impulse test
(i) Report no. & date.
REMARKS:
1. Firm should furnish type test reports of the transformer manufactured as per Technical
Specifications.
2. The proforma should be filled up for the type tested design and submitted within 10 days positively
along with drawings for approval. The drawings & GTP be legible and neatly drawn.
Signature of Representative of the firm with seal
Name :Designation :
Schedule of
characteristics
(Clauses 5.1 and 9.1 of
ISS)
Appearance
Pourpoint (Max.)
Neutralization value
a) Total acidity, Max .
Requirement
of transformer oil
The oil shall be clear and
transparent & free from
suspended
matter
or
sediments
140oC
Reference to test
methods as per IS 335 1993 and with latest
amendments.
A representative & sample of
the oil shall be examined in
100mm
thick layer
at
27oC.
I S : 1448/ 1970
( - ) 6oC
I S : 1448/ 1970
0.03 mg KOH/ gm
I S : 1448/ 1967
NIL
I S : 1448/ 1967
Corrosive Sulphur
Non - corrosive
Annexure-B of IS:335/1993
30 KV (r m s )
I S : 335/ 1993
I S : 335/ 1993
35 x 1012 Ohm
1500 x 1012 Ohm cm
IS : 6103/ 1971
Specific
(Resistivity)
resistance
(Min.)
90oC
a)
at
b) at 27oC
Oxidation stability:
0. 40 mg KOH / gm
b)
Total
oxidation
(Max.)
0.10% by weight
sludge
after
10
S.K. Value
11
Under consideration
cm
I S : 6262- 1971
Annexure
IS : 335 / 1993
Cof
Annexure
IS : 335 / 1993
Dof
resistance
i) at 27o C (Min.)
IS : 6103 / 1971
0.20
IS:6262/1971
0.05 mg KOH/gm
IS:1448/1967
0.05% by weight
Annex,-A of IS : 12177
12
0.04 N/m
IS:6104/1971
13
50 PPM
IS:13567/1972
14
0.89 g/cm3
IS:1448/1977
15
27 Cst
IS:1448/1976
16
Presence
inhibitor
S:13631/1992
(B)
of
Oxidation
The important characteristics of the transformer oil after it is filled in the transformer (within
3 months of filling) shall be as follows : S.
No.
1
Characteristics
30 KV(Min.)
0.01(Max.)
140 0C (Min.)
Water content
10 x 1012 Ohm-cm
0.05 mg KOH/g(Max.)
35 PPM (Max.)
1.
2.
3.
4.
Rating
2
3
Pipe
Connection
Thread
Material of Body
Aluminum
LM-6)
1000
Height in mm
290
Dia in mm
116
20
Oil content in ml
200
Pressure/
casting
10
Type of Painting
Powder coating
Tolerances applicable
(i) Overall length 10 mm
(ii) Overall width 2 mm
(iii) Silica Gel 50 g
5.
Alloy
gravity
(Grade
Die
i) Fabricated from high quality aluminum alloy LM-6 and powder coated for corrosion
resistance.
ii) Special grade nitrile gasket to ensure water proof and air tight joints.
iii) The glass/transparent polycarbonate window for visualizing Silica Gel & oil level should be
fixed by screws to the main body with gasket to prevent leakage of oil.
6.
1.
SCOPE
This specification covers the design, manufacture, supply and testing of H.T./L.T. Bimetallic
Clamps suitable for HT/LT Brass/Copper studs of following Transformers:S. No.
Rating in
KVA
200
on HT side
10.5
315
16.53
on LT side
266.67
420
2.
MATERIAL
The material of bimetallic Clamps shall be of Aluminum and Brass. The brass used should be
of high strength & corrosion resistant. The connector should be design for the purpose of the
connecting together two dissimilar materials for preventing electrolytic corrosion.
2.1 All Aluminum and Aluminum alloys used in the manufacture of bimetallic clamps should
conform to IS-5082/1998. The brass used should be of high strength & corrosion resistant.
The connector shall be smooth and free from cavities, blow holes and such other defects
which would be likely to cause them to be unsatisfactory in service.
2.2 The connector shall be so designed and proportioned that they are capable of safely
withstanding stresses to which they may be subjected(including those due to short-circuit and
climatic conditions) and that the effects of vibration both on the conductor and the connector
itself are minimized. They shall be designed, manufactured and finished so as to avoid sharp
radii of curvature, ridges and excrescences which might lead to localized pressure on or
damage to the conductor in service.
2.3 The finish should be natural and free from flaws, rust, crevices, cracks & other defects
harmful for the joints.
All the edges and corners shall be rounded off to avoid corona effect due to sharpness. The
Bimetallic joints should be protected from the effects of electrolytic action. The resistance of
the clamps shall be very low. These should be free from burrs.
2.4 Sufficient contact pressure should be maintained at the joint by the provision of the
required number of bolts or other fixing arrangements. But the contact pressure should not
be so great as to cause relaxation of the joint by cold flow. The joint should be such that the
pressure is maintained within this range under all conditions of service. To avoid excessive
local pressure, the contact pressure should be evenly distributed by use of pressure plates/
washers or suitable saddles of adequate area and thickness.
2.5 All parts of connectors shall either be inherently resistant to atmospheric corrosion or be
suitably protected against corrosion, both during storage and in service.
2.6 The temperature rise of bimetallic Clamp above a reference ambient temperature of 400
C when carrying rated current shall not exceed 450 C.
2.7 The bolts should be of galvanized mild steel. The fit joint between Al. alloy & brass
component of the connector shall be high pressure.
3.
4.
5.
MARKING
The connectors shall be indelibly marked with rated current or any identifying mark to enable
full particulars of the connector.
Rating of
Transformer in
KVA
i.
ii.
Insulation
of
winding
Place and
Institution where
tested (with date
of test)
Short
Impulse
circuit
PLACE:
Whether
certificate
furnished (please
indicate No. &
Date)
SIGNATURE OF TENDERER
DATE:
Note for the Tenderer: In case of the impulse voltage & short circuit tests have been
conducted, the detailed test report along with copies of the drawings of the design approved
in type test should be furnished with the tender, failing which, it will be presumed that no
test has been carried out and offer for the rating shall not be considered. However, the type
test reports should not be older than five years otherwise offer shall be considered as if no
type test reports have been furnished and shall be dealt with accordingly. The photocopy of
type test report shall subsequently be matched with the original reports at the time of placing
order.
SCHEDULE-SOURCE OF PROCUREMENT OF MATERIALS, PLACE OF MANUFACTURE,
TESTING AND INSPECTION
SN
ITEM
TRANSFORMERS:
Copper
/
Aluminum
SOURCE
OF
PROCUREMENT
OF MATERIAL /
EQUIPMENT
PLACE
OF
MANUFACTURE
PLACE
OF
TESTING
AND
INSPECTION
2
3
4
5
Core laminations
Steel Sections
Tanks
Insulating
Press
Board
6
Insulating Paper
7
Bushing:
(a) HV
(b) LV
8
Oil
9
Insulated winding
wire
10 Terminal
connectors
PLACE :
DATE:
SIGNATURE OF TENDERER
SEAL OF THE FIRM:
NAME :
DESIGNATION/ STATUS:
SCHEDULE-SCHEDULE OF SUPPLY DURING LAST FIVE FINANCIAL YEARS
S.
No.
Financial
Year
2004-05
2005-06
2006-07
2007-08
2008-09
PLACE:
DATE:
63KVA
100KVA
200KVA
and
higher
ratings
Total
Remarks
(Name of SEBs/
Discoms or any
other Power
Utilities to whom
supplied)
SIGNATURE OF TENDERER
SEAL OF THE FIRM:
NAME:
DESIGNATION/ STATUS:
SN
i.
SCHEDULE-PROFORMA FOR RATING-WISE TECHNICAL DETAILS OF THE 200 & 315 KVA
Particulars
Sr.no. of Date
No
Loa %ag Volta Details of core
Dia
/
Cross
DTRs on of type load
d
e
ge
Sectional Area of
whom
test
Loss
Los impe Ratio
bare
conductor
type test report
(Watt s
danc (KV)
used for HV/LV
has been
s)
(W e
Windings
carried
Max.
atts with
out
)
toler
Ma ance
SC IMP
SC I
HV
LV
x
as
M
Winding
Windi
per
Te P
ng
at
ISS
st
Design
Di dia Are
Area
75 at
T
a
) in a
in
C
75C
e
in
m
(in
mm2
s
m
m
mm
t
m
2)
Guarantee
--Report
11/0 Conventio
d technical
s
.433 nal
&
parameters
should
of
_____
not be
Core Type
DTRs as per
older
TS
than
(Alu.
five
Wound)
years
from
the
date
of
tender
openin
g.
Technical
parameters
of
_____ DTRs
as per type
test reports
DTRs
Whether
HV/LV
bushing
mounted
on top
No
(On side
walls
of
the tank)
Oil
volum
e
in
Ltrs
(Min.)
17
3.1. SCOPE:
Supply of overhead Fault Passage Indicators (FPI) for overhead lines to be installed on
33kV and 11 KV lines. The objective of this remote communicable FPI is to quickly
identification of the faulty circuit and automatic update to the SCADA control centre over
remote communication.
3.2.
PURPOSE:
To locate the exact passage of faults on overhead lines. The FPI shall indicate both
transient as well as permanent faults on the O/H lines
3.3.
OPERATION:
The Fault Passage Indicator shall operate on either passing over of the absolute
threshold current (user settable) or the current variation (di/dt). Upon the installation of
the indicator, the FPI shall adjust itself to the network frequency and voltage of perform
required function.
3.4.
FAULT TYPES:
The FPI shall detect and indicate both earth faults as well as phase to phase faults. In
addition to this, the FPI shall also detect and indicate transient and permanent faults.
3.6.
These FPI shall be of pole mounted type and shall have four separate sensors for all the
three phases and for ground. These sensors shall be interfaced with common FPI
controller device through wired or wireless medium.
FPI shall have LED/flag to indicate the passage of fault current through sensor. There shall be
various features to reset the FPI LED/ Flag
a) Self reset after set reset time (Through inbuilt timer)
b) Self reset after restoration of voltage
c) Manual reset from local through push button
d) Remote reset from SCADA control centre by issuing command
It shall also be possible to test the FPI by manually setting the FPI LED/Flag through push button.
The FPI shall be capable to communicate the FPI status to SCADA control centre using GSM/CDMA
network over IEC-101/IEC-104 protocol. There shall be provision to power-up and connect the
modem to this FPI for communication with SCADA control centre.
It shall be possible to configure the FPI as per the requirement from remote SCADA control centre.
The necessary hardware and software required for the configuration of FPI shall be provided by
supplier.
Details
Specific Requirements
Type
Frequency
RF output
Communication media
Communication
protocol
Type
Number of HV lines
monitored per RTU
9 phases
Mechanical
enclosure
100 m
Large
10
11
Transient
fault
detection if enabled
12
13
Equipment monitoring
Equipment monitoring
14
Local
radio
communication faulty
15
16
AC supply alarm
17
Inputs
6 digital inputs
18
Outputs
19
100 events
20
Downloading
archive
21
Power supply
22
Operating temperature
25C to +70C
23
Storage temperature
40C to +85C
24
Net weight in kg
8 kg
25
Protection level
IP 54
26
Standards
Standards
27
28
EMI/EFI immunity
29
of
local
Barbed Wire
TECHNICAL SPECIFICATION FOR G.I. BARBED WIRE
STANDARDS:
Unless otherwise specified elsewhere in this specification, the rating as well as
performance and testing of the G.I. Barbed wire shall conform to the latest revisions
available at the time of placement of order of all the relevant standards but not
limited to as listed below.
IS:280:1978 Mild steel wire for general engineering purposes (third revision)
IS:1340:1977 Code of practice for chromate conversion coating of zinc and cadmium
coated articles and zinc base alloys (first revision)
IS:1521:1972 Method for tensile testing of steel wire (first revision)
IS:1755:1983 Method for wrapping test for metallic wire (first revision)
IS:2633:1986 Method for testing uniformity of coating of zinc coated articles(second revision)
IS:4826:1979 Hot dipped galvanized coating on round steel wires (first revision)
IS:12753:1989 Electro galvanized coatings on round steel wire - Specification
GENERAL TECHNICAL REQUIREMENTS:
GI Barbed wire shall be 2 PLY with a 2.5mm diameter. The barbs shall have a 2mm diameter and be
12.5mm in length. The barbs shall have four points and shall be formed by twisting two point wires,
each two turns, tightly around both line wires making altogether four complete turns (see Fig. 1).
G.I. Barbed wire shall be of type IOWA (Type A in the fig. below) with size and dimensions as
under:Line wire - 2.5 mm
Point wire - 2.0 mm
Distance between two bars shall be 75 mm ( + 12 mm ). Wire shall be medium
However, other specific technical particulars shall be as per Annexure- I
ANNEXURE-I
SPECIFIC TECHNICAL PARTICULARS FOR 2.5 MM X 2.0 MM G.I.BARBED WIRE
Sl.No.
Particulars
Particulars
Bidders Offer
Specified
1
Size of wire- mm
Line wire- 2.5 mm + 0.08 mm
Point wire- 2.0 mm + 0.08 mm
2
Type of Barbed Wire
Iowa Type
3
Tensile strength of line
390 to 590 N/mm
wire
4
Minimum breaking load
3.7 KN
of completed Barbed wire
5
Mass of complete
115 gms / Mtr.
Barbed wire (minimum)
6
Distance between two
(75 + 12 ) mm
Barbs
7
No. of lays between the
4
Barbs ( minimum )
8
Method of Galvanising
Hot dipped according to IS:4826 /1979 with
medium coating.
9
Mass of coating (minimum)
Line wire- 120 gms/Mtr
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
Model GTP
Strain Hardware fitting for 33 & 11 KV Disc Insulator
Hot dip Galvanized G.S. Solid Wire
Earthing
Hot dip Galvanized M.S. Stranded Wire
Danger Board
GI Earthing Pipe
Galvanized Mild Steel Hexagonal Head Bolt& Nuts
PVC Insulated PVC Sheathed Al. Conductor Cable
3ph, 11/0.4KV, 100KVA, 200 KVA outdoor type distribution
transformer
PG Clamp
Rail Pole 13M
XLPE cables
Cable jointing accessories.
Laying & Installation
1.1 kV grade control & power cable
G.I. BARBED WIRE
SURGE ARRESTER
5MVA, 33/11 kV ONAN POWER TRANSFORMERS
33/11 kV ONAN 10 MVA POWER TRANSFORMERS
11 kV INSULATORS & INSULATOR FITTINGS
11KV LINE SECTIONALISERS/AB SWITCH
12 KV OUTDOOR VCB, 1200 A / 630A
INSULATORS PIN AND DISC INSULATORS
36 kV OUTDOOR VCB, 1250A
33 KV and 11 KV Post Insulator
AC Distribution Board
ACSR CONDUCTOR
BATTERY, BATTERY CHARGER AND DCDB
BAY MARSHALLING BOX
CONTROL & RELAY PANEL 33KV AND 11 KV
CIVIL WORKS AND SOIL INVESTIGATION
Current Transformer
ISOLATORS - 33KV (800A) & 11 KV (800A)
LATTICE, RAIL AND PIPE STRUCTURES
LIGHTING SYSTEM
Specification of LTDB
POWER AND CONTROL CABLES
39
40
41
42
43
CONTENTS
Section
Number
Section-4
Section-4
Section-4
Section-4
Section-4
Chapter
Number
1
2
3
4
Description
Specifications for 11 kV
Specification for PSC Pole
Specification for 11 kV Insulator
Specification for Stay Set
Specification for ACSR conductors
Section-4
Description
Page No.
1.
Power Transformers
2.
VCB
10
3.
13
4.
16
5.
19
6.
ACSR Conductor
24
7.
27
8.
AB switch
28
9.
31
10.
Pin Insulator
34
11.
36
12.
HT Guy Insulator
28
13
14
15.
G.I. Wire
Battery charger
Battery
39
40
41
16.
17.
Energy meter
Capacitor Bank
44
46
Description
1.
2.
3.
4.
PHASE CONNECTIONS
5.
a) HV Winding
b) LV Winding
b) Of Winding by resistance
6.
7.
8.
9.
Type of cooling
10.
11.
a) Core
b) Yoke
S.No
Description
12.
13.
14.
15.
16.
18.
19.
20.
S.No
a) Full load
b) LV Winding (Ohms)
b) LV Winding (Ohms)
Description
21.
22.
23.
24.
b) Positive Sequence HV
c) Positive Sequence LV
25.
26.
27.
Core
a) Material of Core lamination
:
:
S.No
28.
Description
Windings
a) Type of Winding
i) HV Winding
ii) LV Winding
b) Insulation of HV winding
c) Insulation of LV winding
d) Insulation between HV & LV winding
e) Power frequency High Voltage Tests
i) Test Voltage for 1 minute withstand test on
High Voltage Windings (Induced)
ii) Test Voltage for one minute withstand test on
Low voltage windings
iii) Test Voltage for one minute withstand test
on Neutral end of high voltage winding
iv) Impulse test on High Voltage Winding 1/50
full wave withstand
v) Impulse test on low voltage winding 1/50 full
wave withstand
vi) Wave form for impulse test
g) Inter turn insulation HV/LV
i)
ii)
S.No
Description
vi) Test Voltage for ten seconds 50 cycles
inter turn insulation test on (iii)
vii) Test Voltage for ten seconds 50 cycles
inter turn insulation test on main body of
the winding
h) Type of Axial coil supports
i)
ii)
ii)
30.
mm
mm
c) Radiator Plate mm
31.
32.
33.
S.No
34.
Description
Bushings:
a) Type
b) Dry flash over voltage
c) Wet flash over voltage
d) Dry 60s withstand test voltage
e) Wet 60s withstand test voltage
f) Full wave withstand test voltage with 1.2/50
micro seconds wave (+) Positive (-) Negative
g) Creepage distance in air
h) Recommended gap setting mm
i) Weight of assembled bushing (Kgs)
j) Quantity of oil (ltrs.)
35.
36.
37.
38.
Cooling system
a) Type and make of Fan motors for forced air
cooling equipment
b) Rating and speed of motors
c) Efficiency of motors at full load
d) Temperature rise of motors at full load
e) Number of fan motors
39.
40.
41.
S.No
42.
Description
Details of on load tap changing gear
a) Make
b) Type
c) Rating:
i)
Rated voltage
44.
45.
46.
47.
48.
49.
50.
S.No
Description
51.
Taps
52.
53.
54.
Yes/No.
55.
Yes / No
56.
57.
58.
59.
60.
61.
62.
63.
64.
S.No
Description
65.
66.
67.
Wheel base
68.
69.
Performance Guarantee
S. No
1.
Description
7.
8.
Duty cycle
9.
10.
16.
Standard applicable
Whether anti pumping device provided
(Yes/No)
Whether control circuitry suitable for
monitoring of closing and tripping circuit
(Yes/No)
Maximum design voltage
a) Symmerical breaking capacity for
various breakers (in KA)
b) Asymmeterical breaking capacity for
various breakers (in KA)
a) Rated continuous current rating for
various breakers & corresponding
temperature
b) Rated continuous current rating for
various breakers at the specified
ambient temperature
Number of breaks/phases
17.
2.
3.
4.
5.
6.
11.
12.
13.
14.
15.
Unit
a) Main
21.
b) Arcing
Whether contacts silver are plated and
thickness of plating
Whether breaker designed to close and
latch on making current release ?
Whether trip free or fixed trip
mechanically and electrically
Type of closing
22.
Type of tripping
18.
19.
20.
10
S. No
23.
Description
Unit
Normal voltage of :
a) Closing/tripping mechanism
b) Spring charging motor
24.
25.
27.
28.
29.
Opening time at :
26.
38.
b) Tripping coil
Schematic control diagram of circuit
breaker enclosed
Make of interrupter
39.
37.
mm Hg
11
S. No
40.
Description
Unit
12
3.0
1.
2.
Validity of tender
3.
4.
Type
5.
Terms of payment
6.A
Circuit Breaker
I.
II.
III.
IV.
V.
VI.
VII.
VIII.
IX.
X.
XI.
XII.
XIII.
6.B
:
:
Current Transformer
I.
II.
III.
IV.
V.
VI.
VII.
VIII.
IX.
X.
XI.
XII.
XIII.
XIV.
XV.
XVI.
13
XVII
XVIII
XIX
XX
6.C
Potential Transformer
I.
II.
III.
IV.
V.
VI.
VII.
VIII.
IX.
X.
XI.
6.D
b) Magnetisation curves
c) Ratio correction factor curves
Turns ratio
Secondary impedance
Highest system voltage
Time period for which secondary winding
can be left open when rated primary current
is following in primary winding.
Protective Relays
a) Manufacturers name & address :
b) Non-directional over current and earth fault
O/C relays
I.Name
II.Type
III.Current coil rating
IV.Tape range
V.VA Burden
VI.a) Highest tap
b) Lowest tap
VII.Time of operation at maximum
time dial setting at
VIII.Type of characteristic
IX.Trip contacts ratings (amp)
X.Whether seal in contact provided or not
XI.Description leaflet reference submitted.
XII.Impulse withstand test voltage
XIII.Over all dimensions
XIV.Total weight
XV.Mounting details
XVI.Characteristic curves
6.E
E/F relays
..KV (Peak)
..mm
...kg
11 KV Switchboard
I. Type & manufacturers name & address
II. Dimensions of Panels
14
Switchboard wiring
I.
II.
III.
IV.
V.
VI.
6.G
PT Circuits
CT Circuits
DC supply Circuits
Other Circuits.
IX.
X.
XI.
XII.
15
(To be filled in by the Bidder separately for each type and voltage rating)
1.
Type of tank/Installation
2.
Type of mounting
3.
4.
Conforming to standard
5.
a) i)
7.
8.
9.
10.
11.
12.
Type of insulation
13.
14.
15.
16
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
1.2/50 micro-second
impulse withstand
voltage (kVp)
28.
29.
17
31.
Details of Cores
31.1
31.2
31.3
Class of accuracy
31.4
31.5
31.6
Secondary resistance
corrected to 75 deg.C
31.7
__ __ __ __ __
31.8 Application
32.
33.
34.
Mounting details
35
Overall dimensions
36.
Characteristics (whether
graphs enclosed):
-- -- -- -- --
Core
a)
b)
18
Type
1.
2.
3.
4.
5.
Winding I
Winding II
Winding - I
7.
8.
9.
10.
11.
12.
19
13.
14.
15.
16.
17.
18.
19.
Mounting details
20.
21.
22.
Overall dimensions:
Height
mm
Length
mm
Breadth mm
23.
Grade of oil.
24.
.........................
20
6.0
Description
Unit
1.0
2.0
2.1
Aluminium
a)
b)
2.2
Steel Wires/Rods
a)
Carbon
b)
Manganese
c)
Phosphorus
d)
Sulphur
e)
Silicon
2.3
Zinc
a)
3.0
3.1
Diameter
a)
Nominal
mm
b)
Maximum
mm
c)
Minimum
mm
3.2
kN
3.3
4.0
4.1
Diameter
a)
Nominal
mm
b)
Maximum
mm
Particulars
Ohm
21
S.NO.
Description
c)
Minimum
5.0
Galvanizing
a)
Unit
Particulars
mm
gm/m2
Nos.
c)
Nos.
6.0
6.1
UTS of Conductor
6.2
a)
b)
c)
d)
6.3
6.4
kN
Max.
Ohm/Km
M
22
S.NO.
6.5
6.6
7.0
7.1
a)
b)
c)
8.0
9.0
Description
Maximum length of conductor that can be
Tolerance on standard length of conductor
Direction of lay for outside layer
Linear mass of the Conductor
Standard
Minimum
Maximum
No. of Cold pressure butt welding available at
works
Performance guarantee
Unit
Meter
%
Particulars
Kg/Km
Kg/Km
KgKm
Nos.
23
Makers name
b)
Brand name
c)
d)
e)
f)
g)
h)
Number of wires
i)
j)
k)
l)
m)
n)
o)
Performance guarantee
24
1.2
1.3
Validity of Tender
1.4
1.5
Terms of payment
1.6
:
:
:
voltage, KV
1.7
1.8
1.9
1.10
:
:
1.11
1.12
1.13
1.14
:
:
:
:
a) Against ground
i) Dry KV
25
:
:
c) Between phases
i) Dry KV
ii) Wet KV
:
:
Type
Material
Surface treatment
Contact area
Contact pressure
:
:
:
:
:
1.17
1.18
1.19
1.21
1.22
1.20
26
1.23
1.24
1.25
1.26
:
:
:
:
27
Description
Particulars
2.
3.
4.
Surge Arrestor
4.1
4.2
b)
c)
d)
Permitted leakage current of arrestor beyond
which arrestor is faulty :
5.
Frequency (Hz)
6.
7.
28
Sl.
No.
8.
Description
Particulars
9.
10.
11.
12.
13.
14.
15.
16.
Arrestor housing
16.1
16.2
16.3
Creepage distance
a)
Protected
b)
Total
16.4
16.5
29
Sl.
No.
17.
18.
Description
Particulars
Dis-connector
a)
Constructional Details
b)
Surge monitor
a)
Constructional details
b)
Degree of protection
19.
20.
22.
Details of packing
23.
24.
b)
Accurancy
c)
Range (mA)
25.
Residual voltage
26.
Follow current
27.
Performance guarantee
Name of the firm .............
Signature of Bidder...........
Name & Designation & Seal .
Date .........................
30
S.NO.
Description
Drawing Numbers
Height
b)
Out Diameter
(kV)
(kV)
10
11
12
13
a)
b)
Particulars
b)
14
15
16
17
18
19
20
21
22
Performance guarantee
31
32
S.NO.
PARAMETER
2
3
Height
b)
Out Diameter
Nominal System Voltage
(kV)
(kV)
8
9
10
11
12
13
GUARANTEED VALUE
14
15
16
17
18
19
20
21
33
34
S.NO.
PARAMETER
GUARANTEED VALUE
Type of insulator
Dimensions
Color of glaze
10
11
12
13
14
35
A.
G.I.Wire
1.
Size of Wire
2.
3.
Tensile strength
4.
Wrapping list
5.
Galvanising conforming to IS :
4826 1968
36
Sl.No.
Description
Units
Volts
Catalogue attached
Type designation
Applicable Standard
AC input current
a) Float
b) Boost
A
A
Volts
10
11
12
Power consumption
13
Efficiency of charger
14
Rectifier assembly
15
16
17
18
Rectifier transformer
Type/Make
Rating
Insulation class
% age impedance
Temperature rise
19
Remarks
Volts
Contactors
37
Description
Units
Remarks
Type/designation
20
AC MCCB
Type/Rating
21
DC MCCB
Type/Rating
22
Charger dimensions
Height
Depth
Width
mm
mm
mm
mm
23
15.0
Description
Units
Volts
Volts
Number of cells
Nos.
Cell designation
Type of electrode
Remarks
38
Description
Units
Volts
Volts
Volts
10
Ah
11
Material of container
12
Size of terminals
13
14
15
Recombination efficiency
16
Valve
regulated
recombination type
17
18
19
ml
20
ml
21
Nos.
22
Type of racks
23
Cell dimension:
24
25
or
Remarks
%
catalytic
(a) Height
(b) Width
(c) Depth
mm
mm
mm
Rack Dimensions
(a)Height
(b)Width
( c)Depth
Mm
Mm
Mm
Y/N
39
40
9.
10.
11.
12.
13.
14.
15.
16.
(a)
(b)
(C)
17.
18.
19.
20.
Description
Vendors Data
Vendors Data
41
22.
23.
24.
25.
26.
27.
28.
29.
30.
(a)
Description
Maximum size of cable which can be connected at
terminals
Are the terminals bi-metallic and suitable for
Aluminum Cables, (Yes / No)
Total weight of meter
HV withstand
Insulation resistance
Standard to which the meter conform
Type of energy registration mechanism
Insulation test (voltage 50 Hz for 1 min.)
Temp. coefficient from 10% of rated load to 100%
of rated load (0 deg. C to 55 deg. C)
Working range
Voltage
(b)
Current
31.
Auxiliary supply
32.
33.
34.
35.
Vendors Data
Vendors Data
36.
Sensitivity
37.
Memory Details
38.
42
17.Capacitor Bank
GTP PARAMETER
1.
2
3
4
5
DATA
of
IS
can
43
10
withstand continuously in KV
Capacitor
Bank
rating
KVAR(600).
Rated voltage of capacitor unit
in KV (12 KV Phase to Phase)
KVAR of individual unit at
rated voltage (200)
Mode of connection capacitor
bank (connected in star with
floated neutral)
Capacitor unit.
11
12
6
7
8
9
13
14
Dielectric
loss
capacitor (Tan 13925)
Delta) as per IS
angle
in
of
26
27
28
29
30
31
32
33
per
34
44
Signature of Bidder...........
45
46
SURGE ARRESTER
33kV VOLTAGE CLASS SURGE ARRESTORS
1.0
1.1
2.0
2.1
SCOPE
The specification covers the design, manufacture, shop & laboratory testing before
dispatch, supply, delivery, erection, testing & commissioning of 33kV voltage
level, 10 KA, Station class heavy duty, gapless metal (zinc) oxide single pole Surge
Arrestors complete with insulating bases, clamps, complete fittings & accessories
suitable for installation on outdoor type 33 kV switchgear, transmission lines, 33
kV transformers. Suitable brackets shall be fabricated and mounted on the
transformers for installing the surge arrestors.
STANDARDS
The design, manufacture and performance of Surge Arrestors shall comply with
IS: 3070 Part-3 and other specific requirements stipulated in the specification.
Unless otherwise specified, the equipment, material and processes shall conform to
the latest applicable Indian/International Standards as listed hereunder:
IS:2071-1993 (Part-1)
The metal oxide gap less Surge Arrestor shall be heavy duty station class suitable for
protection of 33kV switchgear, transformers, associated equipment and 33 kV lines
from voltage surges resulting from natural disturbance like lightning as well as
system disturbances including switching surges. They shall be single phase units
suitable for outdoor duty.
Page 1 of 14
3.2
The surge arrestor shall draw negligible current at operating voltage and at the
same time offer least resistance during the flow of surge current.
3.3
The surge arrestor shall consist of non-linear resistor elements placed in series and
housed in electrical grade porcelain housing of creepage distance of 900 mm. The
protected creepage distance shall not be less than 50% of total creepage. .
3.4
The assembly shall be hermetically sealed with suitable rubber gaskets with effective
sealing system arrangement to prevent ingress of moisture.
3.5
The surge arrestor shall be provided with one line and two earth terminals of suitable
size. The ground side terminal of surge arrestor shall be connected with 25x6
mm galvanized strip, one end connected to the surge arrestor and second end to a
separate ground electrode. The bidder shall also recommend the procedure which
shall be followed in providing the earthing/system to the Surge Arrestor.
3.6
The surge arrestor shall not operate under power frequency and temporary over
voltage conditions but under surge conditions, the surge arrestor shall change over to
the conducting mode.
3.7
The surge arrestor shall be suitable for circuit breaker performing O-0.3sec.-CO-3minCO- duty in the system.
3.8
Surge arrestors shall have a suitable pressure relief system to avoid damage to the
porcelain housing and providing path for flow of rated fault currents in the event of
arrestor failure.
3.9
The reference current of the arrestor shall be high enough to eliminate the influence
of grading and stray capacitance on the measured reference voltage.
3.10 The Surge Arrestor shall be thermally stable and the bidder shall furnish a copy of
thermal stability test with the bid.
3.11
The arrestors for 33 kV system shall be suitable for mounting on transformers, Bus,
Line. The supplier shall furnish the drawing indicating the dimensions, weights etc. of
the surge arrestors for the design of mounting brackets.
3.12
The arrestor shall be capable of handling terminal energy for high surges, external
pollution and transient over voltage and have low losses at operating voltages.
4.0
ARRESTOR HOUSING
4.1
The arrestor housing shall be made up of porcelain housing and shall be homogenous,
free from laminations, cavities and other flaws or imperfections that might affect the
mechanical and dielectric quality. The housing shall be of uniform brown colour, free
from blisters, burrs and other similar defects.
Arrestors shall be complete with fasteners for stacking units together, and terminal
connectors.
4.2
The housing shall be so coordinated that external flashover shall not occur due to
application of any impulse or switching surge voltage upto the maximum design value
Page 2 of 14
for arrestor. The arrestors shall not fail due to contamination. The 33 kV arrestors
housing shall be designed for pressure relief class as given in Technical Parameters of
the specification.
4.3
4.4
The arrester shall be suitable for mounting on a bracket on the HT end of 33/11 kV
transformer or on a lattice steel supporting structure.
5.0
5.1
The surge arrestor shall be complete with fasteners for stacking units together and
terminal connectors.
5.2
The terminals shall be non-magnetic, corrosion proof, robust and of adequate size
and shall be so located that incoming and outgoing connections are made with
minimum possible bends. The top metal cap and base of surge arrestor shall be
galvanized. The line terminal shall have a built in clamping device which can be
adjusted for both horizontal and vertical take off. It should be suitable for ACSR
conductor.
6.0
TESTS
6.1
6.2
Page 3 of 14
6.3
The bidder shall furnish the copies of the type tests and the characteristics curves
between the residual voltage and nominal discharge current of the offered surge
arrestor and power frequency voltage v/s time characteristic of the surge
arrestor subsequent to impulse energy consumption as per clause 6.6 of IS:3070
(Part-3) offered alongwith the bid.
6.4
The surge arrestor housing shall also be type tested and shall be subjected to routine
and acceptance tests in accordance with IS: 5621.
6.5
Galvanization Test
All Ferrous parts exposed to atmospheric condition shall have passed the type tests
and be subjected to routine and acceptance tests in accordance with IS:2633 & IS
6745.
7.0
NAME PLATE
7.1
The name plate attached to the arrestor shall carry the following information :
- Rated Voltage
- Continuous Operation Voltage
- Nominal discharge current
- Pressure relief rated current
- Manufacturers Trade Mark
- Name of Sub-station
- Year of Manufacturer
- Name of the manufacture
- Name of Client-APDP
- Purchase Order Number along with date
8.0
INSPECTION
8.1
All tests and inspection shall be made at the manufacturer's works unless
otherwise specifically agreed upon by the manufacturer and purchaser at the time of
placement of purchase order. The manufacturer shall afford to the inspector
representing the purchaser, all reasonable facilities, without charge to satisfy him
that the material being furnished is in accordance with these specifications. The
purchaser reserves the right to get any component/material being used by the
manufacturer of the Surge Arrestor tested from any recognised test house.
Page 4 of 14
8.2
The inspection by the purchaser or his authorised representative shall not relieve
the bidder of his obligation of furnishing equipment in accordance with the
specification.
9.0
(ii)
(iii)
(iv)
(v)
(vi)
Name plate
(vii)
Insulating base
(viii)
Instructions manual
(ix)
(x)
(xi)
11.2
The surge arrestors shall conform to the following standard technical requirements. The
Insulation values shall be enhanced considering the altitude of operation & other
atmospheric conditions.
Page 5 of 14
System Parameters :
12.2
12.3
33 kV
36 kV
Solidly earthed system
Frequency (Hz)
Lightning Impulse withstand Voltage (kVP)
50
170
70
Phase to earth
33 kV transformers
Surge Arrestors
Type of Surge Arrestor
30
25
10
Degree of protection
IP-55
Lightning Impulse at 10 kA
85
4.5
b) COV (kJ/kV)
4.9
100 KA
Insulator Housing
Power frequency withstand test voltage
(wet) (kV rms)
Lightning impulse withstand/tests voltage (kVP)
Pressure Relief Class
Creepage distance not less than
12.4
Class III
70
170
40
900 mm
Galvanisation
Fabricated Steel Aticles
-- 5 mm thick cover
-- Under 5 mm but not less than 2 mm thickness
610 g/m2
460 g/m2
340 g/m2
Page 6 of 14
thickness
Castings
-- Grey Iron, malleable iron
Threaded works other than tubes & tube fittings
-- Under 10 mm dia
-10 mm dia & above
Page 7 of 14
610 g/m2
300 g/m2
270 g/m2
1.0
SCOPE
The specification covers the design, manufacture, shop & laboratory testing before
dispatch, supply, delivery, erection and commissioning of 11kV voltage station Surge
Arrestors for installation on outdoor type 11kV switchgear, transmission lines,
transformers etc. 11kV side of which is not enclosed in a cable box.
2.0
STANDARDS
The design, manufacture and performance of Surge Arrestors shall comply with IS:
3070 Part-3 and other specific requirements stipulated in the specification. Unless
otherwise specified, the equipment, material & processes shall conform to the latest
amendments of the following:
IS:2071-1993
(Part-1)
IS:20711974 (Part-2)
IS: 2629-1985
IS: 2633-1986
The equipment complying with any other internationally accepted standards shall
also be considered if it ensures performance equivalent to or superior to the Indian
Standards.
3.0 GENERAL REQUIREMENT
3.1
The metal oxide gap less Surge Arrestor shall be suitable for protection of 11 kV side
of power transformers, associated equipment and 11kV lines from voltage surges
resulting from natural disturbance like lightning as well as system disturbances
including switching surges.
3.2
The surge arrestor shall draw negligible current at operating voltage and at the
same time offer least resistance during the flow of surge current.
Page 8 of 14
3.3
The surge arrestor shall consist of non-linear resistor elements placed in series and
housed in electrical grade porcelain housing of specified Creepage distance of 300 mm.
The protected creepage distance shall not be less than 50% of total creepage.
3.4
The assembly shall be hermetically sealed with suitable rubber gaskets with effective
sealing system arrangement to prevent ingress of moisture.
3.5
The surge arrestor shall be provided with one line and two earth terminals of suitable
size. The ground side terminal of surge arrestor shall be connected with 25x6 mm
galvanized strip, one end connected to the surge arrestor and second end to a
separate ground electrode. The bidder shall also recommend the procedure which
shall be followed in providing the earthing/system to the Surge Arrestor.
3.6
The surge arrestor shall not operate under power frequency and temporary over
voltage conditions but under surge conditions, the surge arrestor shall change over to
the conducting mode.
3.7
The surge arrestor shall be suitable for circuit breaker performing O-0.3 min-CO-3
min-CO- duty in the system.
3.8
Surge arrestors shall have a suitable pressure relief system to avoid damage to the
porcelain housing and providing path for flow of rated fault currents in the event of
arrestor failure.
3.9
The reference current of the arrestor shall be high enough to eliminate the influence of
grading and stray capacitance on the measured reference voltage.
3.10
The Surge Arrestor shall be thermally stable and the bidder shall furnish a copy of
thermal stability test with the bid.
3.13
The arrestor shall be capable of handling terminal energy for high surges, external
pollution and transient over voltage and have low losses at operating voltages.
3.14
The surge arrestor shall be provided with line and earth terminals of suitable size. The
line side terminal shall be suitable for 100 mm2 (code Name : Dog) Aluminimum area,
6/4.72 mm Aluminimum + 7/1.75 mm Steel SCA conductor.
4.0
ARRESTOR HOUSING
4.1
The arrestor housing shall be made up of porcelain housing and shall be homogenous,
free from laminations, cavities and other flaws of imperfections that might affect the
mechanical and dielectric quality. The housing shall be of uniform brown colour, free
from blisters, burrs and other similar defects.
Arrestors shall be complete with terminal connectors and disconnectors.
4.2
The housing shall be so coordinated that external flashover shall not occur due to
application of any impulse or switching surge voltage upto the maximum design
value for arrestor. The arrestors shall not fail due to contamination. The 11kV arrestors
housing shall be designed for pressure relief class as given in Technical Parameters of
the specification.
Page 9 of 14
4.3
5.0
6.0
6.1
The surge arrestor shall be complete provided with terminal connectors, disconnector.
6.2
The terminals shall be non-magnetic, corrosion proof, robust and of adequate size
and shall be so located that incoming and outgoing connections are made with
minimum possible bends. The top metal cap and base of surge arrestor shall be
galvanized. The line terminal shall have a built in clamping device which can be
adjusted for both horizontal and vertical take off. It should be suitable for ACSR
conductor.
7.0
TESTS
7.1
The Surge Arrestors offered shall be type tested and shall be subjected to routine and
acceptance tests in accordance with IS : 3070 (Part-3)-1993. In addition, the suitability of the
surge arresters shall also be established for the followings.
(A) Acceptance tests:
i) Measurement of power frequency reference voltage of arrester units.
ii) Lightning impulse residual voltage on arrester units (IEC clause 6.3.2)
(B) Special Acceptance tests:
i) Thermal stability test (IEC clause 7.2.2)
ii) Aging & Energy capability test on blocks (procedure to be mutually agreed)
iii) Watt loss test.
(C) Routine tests:
i) Measurement of reference voltage
ii) Residual voltage test of arrester unit
iii) Sealing test
iv) Verticality check on completely assembled surge arresters as a sample test on each lot.
7.2
7.3
The bidder shall furnish the copies of the type tests and the characteristics curves
between the residual voltage and nominal discharge current of the offered surge
arrestor and power frequency voltage v/s time characteristic of the surge
Page 10 of 14
The surge arrestor housing shall also be type tested and shall be subjected to routine
and acceptance tests in accordance with IS :5621.
7.5
Galvanization Test
All Ferrous parts exposed to atmospheric condition shall have passed the type tests
and be subjected to routine and acceptance tests in accordance with IS:2633 & IS
6745.
7.6
8.0
8.1
NAME PLATE
The name plate attached to the arrestor shall carry the following information :
- Rated Voltage
- Continuous Operation Voltage
- Normal discharge current
- Pressure relief rated current
- Manufacturers Trade Mark
- Name of Sub-station
- Year of Manufacturer
- Name of the manufacture
- Name of Client-APDP
- Purchase Order Number along with date
9.0 INSPECTION
9.1
All tests and inspection shall be made at the manufacturer's works unless
otherwise specifically agreed upon by the manufacturer and purchaser at the time of
placement of purchase order. The manufacturer shall afford to the inspector
representing the purchaser, all reasonable facilities, without charge to satisfy him
Page 11 of 14
that the material being furnished is in accordance with these specifications. The
purchaser reserves the right to get any component/material being used by the
manufacturer of the Surge Arrestor tested from any recognised test house.
9.2
The inspection by the purchaser or his authorised representative shall not relieve
the bidder of his obligation of furnishing equipment in accordance with the
specification.
10.0
11.0
QUALITY ASSURANCE
11.1
11.2
12.0
TECHNICAL PARTICULARS
12.1
The surge arrestors shall conform to the following standard technical requirements.
The Insulation values shall be enhanced considering the altitude of operation & other
atmospheric conditions.
System Parameters
i)
11kV
ii)
12 kV
iii)
System earthing
iv)
Frequency (Hz)
50
v)
75
vi)
28
vii)
Arrestor duty
-- Connection to system
-- Type of equipment to be protected
Phase to earth
transformers & outgoing lines
Type
ii)
iii)
7.65
a) Station Class
b) Line Class
10 KA
5 KA
v)
Degree of protection
IP 55
vi)
Steep current at 10 kA
45
vii)
Lightning Impulse at 10 kA
40
viii)
iv)
4.0
4.9
100 KA
65 KA
ii)
28
75
12.4 Galvanisation
i)
ii)
iii)
610 g/m2
460 g/m2
Castings
Grey Iron, malleable iron
610 g/m2
300 g/m2
270 g/m2
Page 14 of 14
1.
1.0
SCOPE
1.1
1.2
1
2
3
4
5
6
8
9
10
10 MVA
3
Outdoor
50 Hz
Insulating Oil
33kV
11kV
36kV
12kV
OFF-load tap changer
+5% to 15% of 2.5% each on HV
winding
On LV Side only
Range of tapings
Neutral terminal to be brought out
IS
Uniform
33 kV/70, 11kV/28
170
75
Delta
Star
Electrolytic Copper
Dyn 11
ONAN
LV neutral shall be solidly earthed
One no
Yes
arrangement
22
1.2.1
One
500
1.2.3
1.2.4
MARSHALLING BOX
A metal enclosed, weather, vermin and dust proof marshalling box fitted with required glands,
locks, glass door, terminal Board, heater with switch, illumination lamp with switch etc. shall
be provided with each transformer to accommodate temperature indicators, terminal blocks
etc. It shall have a degree of protection of IP 55 as per IS: 2147 (Refer Clause 3.12).
1.2.5
1.3
2
PERFORMANCE
i)
ii)
iii)
iv)
v)
vi)
vii)
1.4
Transformer shall be capable of withstanding for two seconds without damage to any
external short circuit, with the short circuit MVA available at the terminals.
The maximum flux density in any part of the core and yoke at rated MVA, voltage and
frequency shall be such that the flux density under 12.5% over voltage condition
shall not exceed 1.9 Tesla.
Transformer shall under exceptional circumstances due to sudden disconnection of the
load, be capable of operating at the voltage approximately 25% above normal rated
voltage for a period of not exceeding one minute and 40% above normal for a period of 5
seconds.
The transformer may be operated continuously without danger on any particular tapping
at the rated MVA 12.5% of the voltage corresponding to the tapping.
The thermal ability withstand short circuit shall be demonstrated by calculation.
With combined voltage variation of +12.5% and frequency variation of -5%, the flux
density shall not exceed 1.9 Tesla.
Transformer shall be capable of withstanding thermal and mechanical stress caused
by any symmetrical and asymmetrical faults on any winding.
b)
c)
e)
g)
.6
MISCELLANEOUS
i)
ii)
3
General outline drawing showing shipping dimensions and overall dimensions, net
weights and shipping weights, quality of insulating oil, spacing of wheels in either
direction of motion, location of coolers, marshalling box and tap changers etc.
Height of centre line of HV and LV connectors of transformers from the rail top
level.
Dimensions of the largest part to be transported. d)
GA drawings/details of various types of bushing.
Type test certificates of similar transformers from CPRI/NTH/ERDA. f)
Illustrative & descriptive literature of the Transformer.
Maintenance and Operating Instructions.
Padlocks alongwith duplicate keys as asked for various valves, marshalling box etc.,
shall be supplied by the Supplier, wherever locking arrangement is provided.
Foundation bolts for wheel locking devices of Transformer shall be supplied by the
Supplier.
1.7 SCHEDULES
All Schedules annexed to the specification, shall be duly filled by the bidder separately.
1.8
ALTITUDE FACTOR
If the equipment is to be installed in the hilly area, necessary correction factors as given in the
Indian Standard for oil temperature rise, insulation level etc. shall be applied to the Standard
Technical Parameters given above.
1.9
NAME PLATE
Transformer rating plate shall contain the information as given in clause 15 of IS-2026
(Part-I). The details on rating plate shall be finalised during the detailed engineering.
Further each transformer shall have inscription of Purchaser name-BSPHCL.
2.2
The equipment, materials and service covered by this specification shall conform to the
latest applicable provision of the following standards:
IS:5
IS : 325
IS:335
IS:1271
:
:
:
:
IS:2705
Current Transformers
IS:3202
IS:3347
IS:3637
IS:3639
:
:
IS:5561
IS: 10028
C.B.I.P. Publication
If the standard is not quoted for any item, it shall be presumed that the latest version of
Indian Standard shall be applicable to that item.
The equipment complying other internationally accepted standards, may also be considered if
they ensure performance superior to the Indian Standards.
2.3
DRAWINGS
a)
ii)
Foundation plan showing loading on each wheel and jacking points with respect
to centre line of transformer.
iii)
iv)
vi)
5
vii)
viii)
Interconnection diagrams.
ix)
x)
xi)
Control scheme/wiring diagram of marshalling box. xii)
Technical leaflets of major components and fittings. xiii)
As
built drawings of schematics, wiring diagram etc.
xiv) Setting of oil temperature indicator, winding temperature indicator. xv)
Completed technical data sheets.
xvi) Details including write-up of tap changing gear.
xvii) H.V conductor bushing.
xviii) Bushing Assembly.
xix)
xxi)
b)
All
drawings/documents,
technical
certificates/results/calculations shall be furnished.
data
sheets
and
test
2.4
Any approval given to the detailed drawings by the purchaser shall not relieve the Supplier of
the responsibility for correctness of the drawing and in the manufacture of the equipment.
The approval given by the purchaser shall be general with over all responsibility
with Supplier .
3.0
3.1
All material used shall be of best quality and of the class most suitable for working under the
conditions specified and shall withstand the variations of temperature and atmospheric conditions
without distortion or deterioration or the setting up of undue stresses which may impair
suitability of the various parts for the work which they have to perform.
3.2
3.3
Pipes and pipe fittings, screws, studs, nuts and bolts used for external connections shall be as
per the relevant standards. Steel bolts and nuts exposed to atmosphere shall be
galvanized.
3.4
Nuts, bolts and pins used inside the transformers and tap changer compartments shall be
provided with lock washers or locknuts.
3.5
Exposed parts shall not have pockets where water can collect.
3.6
Internal design of transformer shall ensure that air is not trapped in any location.
3.7
Material in contact with oil shall be such as not to contribute to the formation of acid in oil.
Surface in contact with oil shall not be galvanized or cadmium plated.
3.8
Labels, indelibly marked, shall be provided for all identifiable accessories like relays,
switches, current transformers etc. All label plates shall be of in corrodible material.
3.9
All internal connections and fastenings shall be capable of operating under overloads and
over-excitation, allowed as per specified standards without injury.
3.10
3.11
3.12
Schematic Drawing of the wiring, including external cables shall be put under the prospane
sheet on the inside door of the transformer marshalling box.
3.13
Painting
3.13.1
manufacturers
3.13.1.1
All paints, when applied in normal full coat, shall be free from runs, sags, wrinkles,
patchiness, brush marks or other defects.
3.13.1.2
All primers shall be well marked into the surface, particularly in areas where painting is
evident, and the first priming coat shall be applied as soon as possible after cleaning. The
paint shall be applied by airless spray according to the manufacturers recommendations.
However, wherever airless spray is not possible, conventional spray be used with prior
approval of purchaser.
3.13.1.3
The supplier shall, prior to painting protect nameplates, lettering gauges, sight glasses,
light fittings and similar such items.
3.13.2
3.13.2.1
After all machining, forming and welding has been completed, all steel work surfaces
shall be thoroughly cleaned of rust, scale, welding slag or spatter and other contamination
prior to any painting.
3.13.2.2
Steel surfaces shall be prepared by Sand / Shot blast cleaning or Chemical cleaning by
Seven tank process including Phosphating to the appropriate quality.
3.13.2.3
The Pressure and Volume of the compressed air supply for the blast cleaning shall meet the
work requirements and shall be sufficiently free from all water contamination prior to any
painting.
3.13.2.4
Chipping, scraping and steel wire brushing using manual or power driven tools cannot
remove firmly adherent mill-scale and shall only be used where blast cleaning is
impractical.
Protective Coating
As soon as all items have been cleaned and within four hours of the subsequent drying,
they shall be given suitable anticorrosion protection.
Paint Material
3.13.3
3.13.4
Followings are the type of paints that may be suitably used for the items to be painted at
shop and supply of matching paint to site:
i) Heat resistant paint (Hot oil proof) for inside surface.
ii) For external surfaces one coat of Thermo Setting Paint or 2 coats of Zinc
chromate followed by 2 coats of Synthetic Enamel paint. The color of the
finishing coats shall be dark admiral gray conforming to No. 632 of IS
5:1961
3.13.5
Painting Procedure
3.13.5.1
Al painting shall be carried out in conformity with both specifications and with the
paint manufacturers recommendations. All paints in any one particular system,
whether shop or site applied, shall originate from one paint manufacturer.
3.13.5.2
3.13.5.3
All prepared steel surfaces should be primed before visible re-rusting occurs or within 4 hours
whichever is sooner. Chemical treated steel surfaces shall be primed as soon as the
surface is dry and while the surface is warm.
3.13.5.4
Where the quality of film is impaired by excess film thickness (wrinkling, mud
cracking or general softness) the supplier shall remove the unsatisfactory paint coatings and
apply another. As a general rule, dry film thickness should not exceed the specified
minimum dry film thickness by more than 25 %. In all instances, where two or more
coats of the same paints are specifies, such coatings may or may not be of contrasting colors.
3.13.5.5
Paint applied to items that are not be painted, shall be removed at suppliers expense,
leaving the surface clean, un-stained and undamaged.
3.13.6
3.13.6.1
3.13.6.2
a)
3.13.6.3
The repainted surface shall present a smooth surface. This shall be obtained by
carefully chamfering the paint edges before & after priming.
3.13.7
3.13.7.1
To the maximum extent practicable, the coats shall be applied as a continuous film of
uniform thickness and free of pores. Over-spray, skips, runs, sags and drips should be
avoided. The different coats may or may not be of same color.
3.13.7.2
Each coat of paint shall allowed to hardened before the next is applied as per
manufacturers recommendations.
3.13.7.3
3.13.7.4
The requirement for the dry film thickness(DFT) of paint and the material to be used
shall be as given below:
S No
Paint Type
Powdered Paint
(a) Thermo
setting powder
Area to be
painted
Inside
outside
No of Coats
01
01
Liquid paint
a)
Zinc
Chromate(Prim
er
)
b) Syenthetic
Enamel(Fini
4.0 DETAILED DESCRIPTION
sh Coat)
4.1
Tank
c) Hot
4.1.1
The Transformer
tankOil
andpaint
cover
4.1.2
4.1.3
4.1.4
4.1.5
4.1.6
10
Out side
Outsid
e
inside
02
45 micron
02
35 micron
01
35 micron
4.1.7
Suitable guides shall be provided for positioning the various parts during assembly or
dismantling. Adequate space shall be provided between the cores and windings and the
bottom of the tank for collection of any sediment.
4.2
Tank Cover
The transformer top shall be provided with a detachable tank cover with bolted flanged
gasket joint. Lifting lugs shall be provided for removing the cover. The surface of the cover
shall be suitably sloped so that it does not retain rain water.
4.3
UNDER CARRIAGE
4.3.1
The transformer tank shall be supported on steel structure with detachable plain rollers
completely filled with oil. Suitable channels for movement of roller with transformer shall
be spaced
accordingly. rollers Wheels shall be provided with suitable rollers bearings,
which will resist rust and corrosion and shall be equipped with fittings for lubrication. It
shall be possible to swivel the wheels in two directions, at right angle to or parallel to the
main axis of the transformers.
4.3.2
Jacking pads shall be provided on the transformer. It shall be possible to change the
direction of the wheels through 90 degree when the transformer is lifted on jacks to
permit movement of the transformer both in longitudinal and transverse directions.
4.4
4.4.1
4.4.2
CORE
The core shall be wound or cut or stack type.
Stage level inspection for core construction shall be carried out by the owner.
4.4.3
Each lamination shall be insulated such that it will not deteriorate due to mechanical
pressure and the action of hot transformer oil.
4.4.4
The core shall be constructed either from high grade, non-aging Cold Rolled Grain Oriented
(CRGO) silicon steel laminations conforming to grade M4 or better or of amorphous metal.
The amorphous core shall be of high quality amorphous ribbons having very low loss
formed into wound cores of rectangular shape and clamped together by frames firmly
to prevent vibration or noise. The maximum flux density in any part of the cores and
yoke at normal voltage and frequency shall be such that the flux density with + 12.5 %
voltage variation from rated voltage and frequency variation of -5% shall not exceed 1.9
Tesla. The bidder shall provide saturation curve of the core material proposed to be used.
4.4.5
The bidder should offer the core for inspection and approval by the purchaser during the
manufacturing stage. Bidders call notice for the purpose should be accompanied with
the following documents as applicable as a proof towards use of prime core material:
a) Invoice of the supplier
b) Mills test certificate
c) Packing list d)
Bill of lading
11
The laminations shall be free of all burrs and sharp projections. Each sheet shall have an
insulating coating resistant to the action of hot oil.
4.4.7
The insulation structure for the core to bolts and core to clamp plates, shall be such as to
withstand 2000 V DC voltage for one minute.
4.4.8
The completed core and coil shall be so assembled that the axis and the plane of the outer
surface of the core assembly shall not deviate from the vertical plane by more than 25 mm.
4.4.9
All steel sections used for supporting the core shall be thoroughly shot or sand blasted, after
cutting, drilling and welding.
4.4.10
4.4.11
The finally assembled core with all the clamping structures shall be free
deformation and shall not vibrate during operation.
from
The core clamping structure shall be designed to minimize eddy current loss.
Oil ducts shall be provided, where necessary, to ensure adequate cooling inside the core.
The welding structure and major insulation shall not obstruct the free flow of oil through such
ducts.
4.4.15 The design of magnetic circuit shall be such as to avoid static discharges, development of short
circuit paths within itself or to the earthed clamping structure and production of flux
component at right angle to the plane of the lamination, which may cause local heating. The
supporting framework of the cores shall be so designed as to avoid the presence of pockets,
which would prevent complete emptying of the tank through the drain valve or cause trapping
of air during filling.
4.4.16 The construction is to be of `core type. The core shall be provided with lugs suitable for lifting
the complete core and coil assembly. The core and coil assembly shall be so fixed in the tank
that shifting will not occur during transport or short circuits.
4.5
INTERNAL EARTHING
4.5.1
All internal metal parts of the transformer, with the exception of individual laminations, core
bolts and their individual clamping plates shall be earthed.
4.5.2
The top clamping structure shall be connected to the tank by a copper strap. The bottom
12
4.5.3 The magnetic circuit shall be connected to the clamping structure at one point only and this shall
be brought out of the top cover of the transformer tank through a suitably rated insulator. A
disconnecting link shall be provided on transformer tank to facilitate disconnections from
ground for IR measurement purpose.
4.5.4
4.6
Coil clamping rings of metal at earth potential shall be connected to the adjacent core clamping
structure on the same side as the main earth connections.
WINDING
4.6.1
4.6.2
All low voltage windings for use in the circular coil concentric winding shall be wound on a
performed insulating cylinder for mechanical protection of the winding in handling and
placing around the core.
4.6.3
Winding shall not contain sharp bends which might damage the insulation or produce high
dielectric stresses. No strip conductor wound on edge shall have width exceeding six times
the thickness.
4.6.4
Materials used in the insulation and assembly of the windings shall be insoluble, non
catalytic and chemically inactive in the hot transformer oil and shall not soften or the
otherwise affected under the operating conditions.
4.6.5
Varnish application on coil windings may be given only for mechanical protection and not
for improvement in dielectric properties. In no case varnish or other adhesive be used
which will seal the coil and prevent evacuation of air and moisture and impregnation
by oil.
4.6.6
Winding and connections shall be braced to withstand shocks during transport or short
circuit.
4.6.7
Permanent current carrying joints in the windings and leads shall be welded or brazed.
Clamping bolts for current carrying parts inside oil shall be made of oil resistant
material which shall not be affected by acidity in the oil steel bolts, if used, shall be suitably
treated.
4.6.8
Terminals of all windings shall be brought out of the tank through bushings for external
13
connections.
4.6.8.1
4.6.8.2
4.6.8.3
14
The completed core and coil assembly shall be dried in vacuum at not more than
0.5mm of mercury absolute pressure and shall be immediately impregnated with oil
after the drying process to ensure the elimination of air and moisture within the
insulation. Vacuum may be applied in either vacuum over or in the transformer tank.
The winding shall be so designed that all coil assemblies of identical voltage ratings shall
be interchangeable and field repairs to the winding can be made readily without special
equipment. The coils shall have high dielectric strength.
Coils shall be made of continuous smooth high grade electrolytic copper conductor,
shaped and braced to provide for expansion and contraction due to temperature
changes.
4.6.8.4
4.6.8.5
4.6.8.6
4.6.8.7
4.7
4.7.1
4.7.2
4.7.3
4.7.4
Adequate barriers shall be provided between coils and core and between high and low
voltage coil. End turns shall have additional protection against abnormal line disturbances.
The insulation of winding shall be designed to withstand voltage stress arising from
surge in transmission lines due to atmospheric or transient conditions caused by
switching etc.
Tappings shall not be brought out from inside the coil or from intermediate turns and
shall be so arranged as to preserve as far as possible magnetic balance of the
transformer at all voltage ratios.
Magnitude of impulse surges transferred from HV to LV windings by electro magnetic
induction and capacitance coupling shall be limited to B.I.L. of LV winding.
INSULATING OIL
The insulating oil for the transformers shall be of LHV grade, generally conforming to
IS: 335. No inhibitors shall be used in the oil.
The quantity of oil required for the first filling of the transformer and its full
specification shall be stated in the bid. The bidder shall quote the price of transformer
complete with first filling of oil plus 10% extra. However, the rate of transformer oil in
Rupee per litre shall be quoted separately also. The transformer oil shall be supplied in nonreturnable drums.
The design and materials used in the construction of the transformer shall be such as to
reduce the risk of the development of acidity in the oil.
The Supplier
specifications.
S.No
1
Characteristic
Appearance
2
3
Density at 200C
Kinematic Viscosity at
27 deg.C Max
Interfacial tension at 27
deg. C Min.
Flash Point
Pour Point Max.
Neutralisation
Value
(Total Acidity) Max.
Electric
strength
BreakDown
(voltage)
Min.
Dielectric dissipation factor
tan delta at 900 C
4
5
6
7
8
15
Requirement
The oil shall be clear &
transparent & free from
suspended
matter
or
Sediment
0.89g/cm3 Max.
27 CST
IS: 1448
IS: 1448
0.03N/m
IS: 6104
136 deg.C
-6 deg.C
0.03 mg KOH/gm
IS: 1448
IS: 1448
IS: 335
IS: 6792
0.03
IS:6262
Max
Method of Test
A representative sample of oil
shall be examined in a 100
mm thick layer at ambient temp.
10
Min.
specific
resistance(resistivity)
at
90 deg.C
11
12
Oxidation stability
Neutralisation value after
oxidation
Total
sludge
after
oxidation
13
14
15
4.8
Presence
Inhibitor
of
oxidation
12
35 x 10
ohm cm
(min.)
IS: 6103
0.40 mg KOH/g
0.10% by weight max.
IS:335
IS: 2362
VALVES
i)
Valves shall be of forged carbon steel upto 50 mm size and of gun metal or of cast
iron bodies with gun metal fittings for sizes above 50 mm. They shall be of full way
type with screwed ends and shall be opened by turning counter clockwise when
facing the hand wheel. There shall be no oil leakage when the valves are in closed
position.
ii)
Each valve shall be provided with an indicator to show the open and closed
positions and shall be provided with facility for padlocking in either open or closed
position. All screwed valves shall be furnished with pipe plugs for protection. Padlocks
with duplicate keys shall be supplied alongwith the valves.
iii)
All valves except screwed valves shall be provided with flanges having
machined
faced drilled to suit the applicable requirements. Oil tight blanking plates shall be
provided for each connection for use when any radiator is detached and for all
valves opening to atmosphere. If any special radiator valve tools are required, the
Supplier shall supply the same.
iv)
Drain and filter valves shall be suitable for applying vacuum as specified in the
16
specifications.
4.9
ACCESSORIES
4.9.1 Bushing
i)
ii)
Stress due to expansion and contraction in any part of the bushing shall not lead to
deterioration.
iii)
Bushing shall be designed and tested to comply with the applicable standards.
iv)
Liquid/oil-filled bushings shall be equipped with liquid level indicators and means for
sampling and draining the liquid. The angle of inclination to vertical shall not exceed 30
degree.
v)
Oil in oil-filled bushings shall meet the requirements of the transformer oil
standards.
vi)
Bushing rated for 400A and above shall have non-ferrous flanges and hardware. vii)
Fittings made of steel or malleable iron shall be galvanized.
Bushing shall be so located on the transformers that full flashover strength will be
utilized. Minimum clearances as required for the BIL shall be realized between live parts
and live parts to earthed structures.
viii)
ix)
All applicable routine and type tests certificates of the bushings shall be furnished for
approval.
x)
xi)
xii)
The insulation class of high voltage neutral bushing shall be properly coordinated with
the insulation class of the neutral of the low voltage winding.
xiii)
Each bushing shall be so coordinated with the transformer insulation that all
flashover will occur outside the tank.
(ii)
(a)
The conservator tank shall have adequate capacity between highest and lowest
visible levels to meet the requirement of expansion of the total cold oil volume in the
transformer and cooling equipment.
(b)
The conservator tank shall be bolted into position so that it can be removed for cleaning
purposes.
(c)
The conservator shall be fitted with magnetic oil level gauge with low level
electrically insulated alarm contact.
(d)
(iii)
Buchholz Relay
A double float type Buchholz relay shall be provided. Any gas evolved in the transformer shall
collect in this relay. The relay shall be provided with a test cock suitable for a flexible pipe
connection for checking its operation. A copper tube shall be connected from the gas collector
to a valve located about 1200 mm above ground level to facilitate sampling with the
transformer in service. The device shall be provided with two electrically independent potential
free contacts, one for alarm on gas accumulation and the other for tripping on sudden rise of
pressure.
(iv)
Temperature Indicator
(a)
(b)
18
i)
ii)
iii)
iv)
v)
vi)
19
4.9.3
4.9.3.1
Oil Sealing
The oil preservation shall be diaphragm type oil sealing in conservator to prevent
oxidation and contamination of oil due to contact with atmospheric moisture.
The conservator shall be fitted with a dehydrating filter breather. It shall be so
designed that,
i)
ii)
iii)
iv)
4.10
20
MARSHALLING BOX
i)
Sheet steel, weather, vermin and dust proof marshalling box fitted with required
glands, locks, glass door, terminal Board, heater with switch, illumination lamp
with switch, water-tight hinged and padlocked door of a suitable construction shall be
provided with each transformer to accommodate temperature indicators, terminal blocks
etc. The box shall have slopping roof and the interior and exterior painting shall be in
accordance with the specification. Padlock alongwith duplicate keys shall be
supplied for marshalling box. The degree of protection shall be IP-55.
ii)
The schematic diagram of the circuitry inside the marshalling box be prepared and fixed
inside the door under a prospone sheet.
iii)
iii)
iv)
All incoming cables shall enter the kiosk from the bottom and the gland plate shall not
v)
4.11
be less than 450 mm from the base of the box. The gland plate and associated
compartment shall be sealed in suitable manner to prevent the ingress of moisture from
the cable trench.
The control connection, wiring etc. shall be as per Clause 3.15 of this specification.
4.12
FITTINGS
The following fittings shall be provided on the transformers:
i)
ii)
iii)
iv)
v)
21
Conservator with isolating valves, oil filling hole with cap and drain valve.
The conservator vessel shall be filled with constant oil pressure diaphragm oil
sealing system
Magnetic type oil level gauge (150 mm dia.) with low oil level alarm
contacts.
Prismatic/toughened glass oil level gauge.
Silica gel breather with oil seal and connecting pipe complete with first fill of
activated silica gel or Alumina mounted at a level of 1300 mm above ground
level.
A double float type Buchholz relay with isolating valve, bleeding pipe and a
testing cock, the test cock shall be suitable for a flexible (pipe connection for
checking its operation). A 5 mm dia. Copper pipe shall be connected from
the relay test cock to a valve located at a suitable height above ground
level to facilitate sampling of gas with the transformer in service.
Interconnection between gas collection box and relay shall also be
provided. The device shall be provided with two electrically independent
ungrounded contacts, one for alarm on gas accumulation and the other for
tripping on sudden oil surge. These contacts shall be wired upto
transformer marshalling box. The relay shall be provided with shut off
valve on the conservator side as well as on the tank side.
vi)
vii)
viii)
ix)
Pressure relief devices (including pressure relief valve) and necessary air
equalizer connection between this and the conservator with necessary alarm
and trip contacts.
Air release plugs in the top cover.
Inspection cover, access holes with bolted covers for access to inner ends of
bushing, etc.
Winding temperature (hot spot) indicating device for local mounting
complete in all respects. Winding temperature indicator shall have three sets of
contacts to operate at different settings :
22
(i)
The fittings listed above are indicative and any other fittings which are generally
required for satisfactory operation of the transformer are deemed to be included in the
5.0
(ii)
(iii)
Only one no of transformer will be subjected to type test at supplier cost from
CPRI/NTH/ERDA.
(iv)
The pre-shipment checks shall also be carried out by the Supplier. (v)
The requirements on site tests are as listed in the specifications.
(vi) Certified test report and oscillograms shall be furnished to the Purchaser/Consultants
for evaluation as per the schedule of distribution of documents. The Supplier
shall also evaluate the test results and rectify the defects in the equipment based on his
and the Purchasers evaluations of the tests without any extra charges to the Purchaser.
Manufacturers Test Certificates in respect of all associated auxiliary and ancillary
equipment shall be furnished.
(vii) The bidder shall state in his proposal the testing facilities available at his works. In case
full testing facilities are not available, the bidder shall state the method proposed
to be adopted so as to ascertain the transformer characteristics corresponding to full
capacity.
5.1
INSPECTION
i)
b)
c)
ii)
23
d)
e)
b)
f)
iv)
Winding
a)
v)
c)
vi)
vii)
Check insulating distances between low voltage connections and earth and
other parts.
d)
Insulating test for core earthing.
Checks During Drying Process
a)
Measurement and recording of temperature and drying time during vacuum
treatment.
Check for completeness of drying.
Assembled Transformer
a)
24
viii)
(ix)
b)
Jacking test on the assembled Transformer.
Oil
All standard test in accordance with IS: 335 shall be carried out on Transformer oil
sample before filling in the transformer.
Test Reports for bought out items
The Supplier shall submit the test reports for all bought out/sub Supplier items for
approval.
a)
Buchholz relay
b)
Sudden Pressure rise relay in OLTC
c)
Sudden Pressure rise relay on Main Tank
d)
Winding temperature indicators (for TX capacity >10 MVA)
e)
Oil temperature indicators
f)
Bushings
g)
Bushing current transformers in neutral (if provided)
h)
Marshalling box
i)
Any other item required to complete the works.
j)
Porcelain, bushings, bushing current transformers, wherever provided,
winding coolers, control devices, insulating oil and other associated
equipment shall be tested by the contractor in accordance with relevant IS. If
such equipment is purchased by the Supplier on a sub-contract, he shall have
them tested to comply with these requirements.
5.2.
25
FACTORY TESTS
i)
All standards routine tests in accordance IS: 2026 with dielectric tests
corresponding as per latest amendments to IS: 2026 shall be carried out.
ii)
All auxiliary equipment shall be tested as per the relevant IS. Test certificates shall be
submitted for bought out items.
iii)
High voltage withstand test shall be performed on auxiliary equipment and wiring
after complete assembly.
iv)
Following additional routine tests shall also be carried out on each transformer:
Magnetic Circuit Test
Each core shall be tested for 1 minute at 2000 Volt DC.
Oil leakage test on transformer
5.2.1
Routine Tests
Transformer routine tests shall include tests stated in latest issue of IS: 2026
(Part-I). These tests shall also include but shall not be limited to the following:
(i)
(ii)
(iii)
(iv)
(v)
Load losses.
(vi)
(vii)
(viii)
(ix)
(x)
(xi)
All routine & type tests should be done free of cost. If it is to be done on the cost basis, the same
may be indicated in the schedule of prices and delivery and this will be taken into account for
evaluation of prices.
Six (6) sets of certified test reports and oscillographs shall be submitted for evaluation prior to
dispatch of the equipment. The Supplier shall also evaluate the test results and shall correct
any defect indicated by his and Purchasers evaluation of the tests without charge to the
Purchaser.
5.3
TANK TESTS
a)
b)
26
period of not less than 12 hours for oil and one hour for air and during that time no leak
shall occur.
Pressure Test
Where required by the Purchaser, one transformer tank of each size together with its
radiator, conservator vessel and other fittings shall be subjected to a pressure
corresponding to twice the normal head of oil or to the normal pressure plus 35
KN/m2 whichever is lower, measured at the base of the tank and maintained for one
hour.
Vacuum Test
One transformer tank of each size shall be subjected to the vacuum pressure of 760 mm
of mercury. The tanks designed for full vacuum shall be tested at an internal pressure of
3.33 KN/m2 (25 mm of mercury) for one hour. The permanent deflection of flat
plates after the vacuum has been released shall not exceed the value specified in
C.B.I.P. Manual on Transformers (Revised 1999) without affecting the performance
of the transformer.
5.4
5.5
ii)
Check for proper provision of bracing to arrest the movement of core and
winding assembly inside the tank.
iii)
PERFORMANCE
The performance of the transformer shall be measured on the following aspects.
27
i)
ii)
The maximum flux density in any part of the cores and yokes at normal
voltage and frequency shall be such that the flux density on any tap position
with +12.5% voltage variations and 5% frequency variations shall not
exceed 1.9 wb/m2.
iii)
iv)
5.6
FAULT CONDITIONS
(a)
5.7
(ii)
(iii)
(iv)
(v)
(vi)
(vii)
The purchaser, at his option, may waive impulse tests provided type test
reports of impulse tests carried out on essentially identical units in their
factory in India are furnished by the manufacturer.
No load losses and exciting current shall be measured at rated voltage, rated
frequency and at 90% and 110% of rated voltage, both before and after the
lightning impulse tests.
The method of test loading shall be described in the test report for
determination of both average and hottest spot temperature. Where the
winding temperature equipment is specified, data shall also be included for
calibration of hottest spot temperature indicator.
Resistance of each winding of each phase shall be measured at principal and at
all the taps and corrected to 750C.
Impedance voltage shall be measured at principal and at all taps,
No load Loss Measurement at 415 Volt.
Certified test report and oscillograms shall be furnished to the
Purchaser/Consultants for evaluation as per the schedule of distribution of
documents. The Supplier shall also evaluate the test results and rectify the defects
in the equipment based on his and the Purchasers evaluations of the tests without
any extra charges to the Purchaser. Manufacturers Test Certificates in respect
of all associated auxiliary and ancillary equipment shall be furnished.
(viii)
5.8
The bidder shall state in his proposal the testing facilities available at his works.
In case full testing facilities are not available, the bidder shall state the method
proposed to be adopted so as to ascertain the transformer characteristics
corresponding to full capacity testing.
WITNESSING OF TESTS AND EXCESSIVE LOSSES
i)
ii)
The Purchaser and/or his representative reserve the right to witness any or all tests, or to
accord waival at its sole discretion.
The Purchaser reserves the right to reject the Transformer if losses exceed the
declared losses beyond tolerance limits as per IS or if temperature rise of oil and winding
exceed the values specified.
5.9 CAPITALISATION OF LOSSES AND LIQUIDATED DAMAGES FOR
28
EXCESSIVE LOSSES
5.9.1
LOSSES:
Transformers with lower losses shall be preferred. The bidder shall indicate the values of load
and no load losses of the transformer in his bid. The no load loss in Killowatts and the load
losses in Kilowatts at rated full load current and frequency at 75 Deg.C. shall be guaranteed to 8
KW and 50 KW respectively with no plus tolerance. The above losses are maximum allowable.
5.9.2 CAPITALISATION OF LOSSES
For total cost evaluation, the capitalized cost of losses will be taken into account as per the
following:
The no load loss in KW at the rated voltage and frequency and the load loss in
KW at rated voltage, rated frequency, rated output and at 75 degree centigrade shall be quoted
and these figures shall be guaranteed.
i) Note: Liquidated damages for non-performance for transformers shall be recovered from
the contractor in case he is unable to achieve the quoted guaranteed figures at the above rate.
This shall supercede any other provision on this matter specified elsewhere in the
specification.
5.9.3
REJECTION
The Purchaser may reject any transformer if during tests or service any of the following
conditions arise:
i)
No load loss exceeds the guaranteed value.
ii)
Load loss exceeds the guaranteed value.
iii)
Impedance value exceeds the guaranteed value by + 10% or more.
iv)
v)
vi)
vii)
viii)
29
The difference in impedance values of any two phases during single phase short
circuit impedance test exceeds 2% of the average value guaranteed by the vendor.
Oil or winding temperature rise exceeds the specified value.
Transformer fails on impulse test.
Transformer fails on power frequency voltage withstand test.
Transformer is proved to have been manufactured not in accordance with the agreed
specification.
6.0
SPARE PARTS
In case the manufacturer goes out of production of spare parts, then he shall make available the
drawings of spare parts and specification of materials at no extra cost to the Purchaser to
fabricate or procure spare parts from other sources.
6.1
INSTRUCTIONS MANUAL
Eight sets of the instruction manuals shall be supplied at least four (4) weeks before the
actual dispatch of equipment. The manuals shall be in bound volumes and shall contain all the
drawings and information required for erection, operation and maintenance of the
transformer. The manuals shall include amongst others, the following particulars :
a)
Marked erection prints identifying the components, parts of the transformer as
dispatched with assembly drawings.
b)
Detailed dimensions, assembly and description of all auxiliaries.
c)
6.2
7.0
Detailed views of the core and winding assembly, winding connections and tapings, tap
changer construction etc. These drawings are required for carrying out
overhauling operation at site.
d)
Salient technical particulars of the transformer.
e)
Copies of all final approved drawings.
f)
Detailed O&M instructions with periodical check lists and Performa etc.
COMPLETENESS OF EQUIPMENT
i)
All fittings and accessories, which may not be specifically mentioned in the
specification but which are necessary for the satisfactory operation of the plant,
shall be deemed to be included in the specification and shall be furnished by the
contractor without extra charges. The equipment shall be complete in all details,
whether such details are mentioned in the specification or not, without any financial
liability to the Purchaser under any circumstances.
ii)
All deviations from this specification shall be separately listed under the requisite
schedules, in the absence of which it will be presumed that all the provisions of the
specification are complied with by the bidder.
30
Scope
This Specification covers design, engineering, manufacture, assembly,
stage testing, inspection & testing before supply and delivery at site the
Pin insulators and disc insulators alongwith fittings for 11 kV lines.
2.0
Standards
The material shall conform in all respect to the relevant Indian standards
with latest amendments indicated below.
Indian Standards
Title
ISS: 731/1976
4.0
Technical Description
4.1
4.1.1
Page 1 of 16
4.1.2
4.1.2.1
The strain insulators shall be of Ball & Socket (B&S) type or Tongue &
Clevis (T&C) type with details as per per REC specification no. 3/1993
(fig. 2). The strain insulator assembly shall be as per fig. 5 for T&C type
and as per fig. 6 for B&S type insulators. The strain clamps shall be as per
fig. 7 for B&S type and fig. 8 for T&C type insulators.
5.0
5.1
Insulator Materials
Porcelain
The porcelain used in the manufacture of shells shall be sound, free from
defects thoroughly vitrified and smoothly glazed. It should not engage
directly with hard metal.
5.2
Glaze
The finished porcelain shall be glazed in brown colour. The glaze shall
cover all exposed parts of the insulator and shall have a good lusture,
smooth surface and good performance under the extreme weather
conditions of a tropical climate. It shall not crack or chip by ageing
under the normal service conditions. The glaze shall have the same coefficient of expansion as of the porcelain body throughout the working
temperature range. The insulator shall be so designed that the stresses
due to expansion and contraction in any part of the insulator shall not
lead to deterioration.
5.3
Cement
Cement used in the manufacture of the insulator shall not cause fracture
by expansion or loosening by contraction. The cement shall not give rise
to chemical reaction with metal fittings and its thickness shall be as
small and uniform as possible. Proper care shall be taken to correctly
centre and locate individual parts during cementing.
6.0
Creepage Distance
The insulators shall be used for Normal and moderately polluted
atmosphere. The minimum creepage distance for both pin & strain type
insulator shall be 230 mm.
Page 2 of 16
7.0
Insulators Fittings
7.1
Pins:
7.1.1
7.1.2
ii)
iii)
Type Test:
a)
b)
Galvanizing Test
c)
Visual Examination
d)
Mechanical Test
Acceptance Tests:
a)
b)
Galvanizing Test
c)
Mechanical Test
Routine Test:
a)
7.2
Visual Examination
7.2.1
The ties shall be suitable for the AAAC equivalent to ACSR Rabbit & Weasel
conductors.
Page 3 of 16
7.2.2
Elastometer pad for insulator shall be used with the ties to avoid
abrasion of the conductor coming
7.2.3
7.3
7.3.1
7.3.2
7.4
7.4.1
Fittings for Strain Insulators of Tongue & Clevis Type: This will consists
of:
a)
b)
c)
Helically formed dead end grip having pre fabricated loop to fit into
the grooved contour of the thimble on one end and for application
over the conductor at the other end. The formed fitting shall conform
to the requirement of IS 12048: 1987.
b)
Forged steel ball eye for attaching the socket end of the strain
insulator to the cross arm strap. Forging shall be made of steel as per
IS 2004:1978
c)
Page 4 of 16
d)
7.4.2
Nominal dimensions of Ball & Socket type insulator fittings shall be as per
dwg. referred in cl. 4.0.
7.5
The helically formed fitting for strain insulators shall be tested as per IS
12048: 1987 and other hardware fitting shall be tested as per IS 2486 (part
I) .
7.6
Failing Load
Mechanical Failing Load(For Pin Insulators only)
The insulators shall be suitable for a minimum failing load of 5 KN (for 11
kV) applied in transverse direction.
Electro Mechanical Failing Load(For Strain Insulators/String
Insulator Units)
The insulators shall be suitable for a minimum failing load of 45 KN (for
11 kV lines).
7.7
7.8
7.9
Tests on Castings
The chemical analysis, mechanical and metallographic tests and magnetic,
particle inspection for castings will be as per the internationally recognised
procedures for these tests. The samplings will be based on heat number
and heat treatment batch. The details regarding test will be as discussed
and mutually agreed to by the Contractor and Owner in Quality Assurance
Programme.
Page 5 of 16
8.0
Interchangeability
The disc insulators inclusive of fittings shall be of standard design suitable
for use with the hardware fittings of any make conforming to relevant
Indian/International Standards.
9.0
Workmanship
9.1
All the material shall be of the latest design and conform to the best modern
practices adopted in the distribution voltage field. Contractors shall offer
only such insulators as are guaranteed by him to be satisfactory and
suitable for specified voltage level lines and will give continued good
service.
9.2
9.3
The design of the insulators shall be such that stresses due to expansion and
contraction in any part of the insulator shall not lead to deterioration.
9.4
In disc insulators, metal caps shall be free from cracks, seams, shrinks, air
holes, burrs and rough edges. All surfaces of the metal parts shall be
perfectly smooth with no projecting points or irregularities. All load
bearing surfaces shall be smooth and uniform so as to distribute the
loading stresses uniformly.
9.5
All ferrous parts shall be hot dip galvanised to give a minimum average
coating of Zinc equivalent to 600 gm/sq.m. and shall be in accordance
with the requirement of IS:2629-1985 and shall satisfy the tests mentioned
in IS:2633 1986. The zinc used for galvanising shall be of Grade Zn 99.95
as per IS:209-1979. The zinc coating shall be uniform, adherent, smooth,
reasonably bright, continuous and free from imperfections such as flux,
ash, rust stains, bulky white deposits and blisters. The galvanised metal
parts shall be guaranteed to withstand at least six successive dips each
lasting for one (1) minute duration under the standard creep test.
9.6
Before ball fittings are galvanised, all die flashing on the shank surface of
the ball shall be carefully removed without reducing the dimensions below
the design requirements.
9.7
In disc insulators, the design of the insulators shall be such that the shell
shall not engage directly with hard metal. The design shall also be such
that when units are coupled together there is no contact between the shell
of one unit and metal of the next adjacent unit. The design of the shell
Page 6 of 16
ribs shall be such that the security clip of the insulator can be engaged and
disengaged easily with hot stick without damaging the shell ribs.
9.8
Insulator units after assembly shall be concentric and co-axial within limits
as permitted by the relevant Indian Standards.
10.0
Equipment Marking
10.1
Each insulator shall be legibly and indelibly marked with the trademark of
the manufacturer and month & year of manufacture. The guaranteed
combined mechanical and electrical strength shall be indicated in kilo
Newton followed by the word kN to facilitate easy identification and to
ensure proper use.
10.2
The marking shall be on porcelain, and shall be printed, not impressed and
shall be applied before firing.
11.0
Bid Drawings
11.1
The Bidder shall furnish full description and illustration of the material
offered.
11.2
The Bidder shall furnish along with the bid the outline drawing (6 copies)
of each insulator unit including a cross sectional view of the insulator
shell. The drawing shall include but not limited to the following
information:
(a)
(b)
(c)
(d)
(ii)
(e)
(f)
Size and weight of Pin Ball Shank / ball and socket parts
(g)
(h)
Materials
(i)
Identification mark
Page 7 of 16
(j)
11.3
12.0
12.1
Tests
The following type, acceptance, routine tests and tests during manufacture
shall be carried out on the insulator individually and along with hardware
fittings. For the purpose of this clause:
12.1.1
Type tests shall mean those tests which are to be carried out to prove the
design process of manufacture and general conformity of the material to
this specification. These tests shall be carried out on samples prior to
commencement of commercial production against the specification. The
Bidder shall indicate this schedule for carrying out these tests in the
activity schedule.
12.1.2
Acceptance tests shall mean those tests which are to be carried out on
samples taken from each lot offered for pre-dispatch inspection for the
purpose of acceptance of that lot.
12.1.3
Routine tests shall mean those tests, which are to be carried out on each
insulator/hardware fitting to check requirements which are likely to vary
during production.
12.1.4
Tests during manufacture shall mean those tests which are to be carried
out during the process of manufacture and end inspection by the Supplier
to ensure the desired quality of the end product to be supplied by him.
12.1.5
The norms and procedure of sampling for these tests will be as per the
Quality Assurance Programme to be mutually agreed to by the Supplier
and Owner.
12.1.6
The standards and norms to which these tests will be carried out are listed
against them. Where a particular test is a specific requirement of this
specification, the norms and procedure of these shall be as specified in
Annexure-A of this Section or as mutually agreed to between the Supplier
and the Owner in the Quality Assurance Programme.
Page 8 of 16
12.1.7
For all types and acceptance tests, the acceptance values shall be the
values guaranteed by the Bidder in the Guaranteed Technical Particulars
of this proposal or the acceptance value specified in this specification
whichever is more stringent for that particular test.
12.1.8
For all type and acceptance tests, the Bidder shall guarantee only
minimum values in the Guaranteed Technical Particulars. Bidder shall be
required to achieve the same or higher values, as guaranteed, during
testing for all type and acceptance tests.
12.2
Tests on insulators
The flowing test shall be performed on insulators
12.2.1
Type Tests
The following type tests shall be conducted on a suitable number of
individual insulator unit, components, materials or complete strings:
(a)
Visual examination
(b)
Verification of dimensions
(c)
(d)
(e)
(f)
(g)
(h)
(i)
Puncture Test
(j)
Porosity Test
(k)
Galvanizing Test
(l)
(m)
Page 9 of 16
12.2.2
12.2.3
12.2.4
Acceptance Tests
(a)
Verification of dimensions
(b)
(c)
(d)
Puncture Test
(e)
Porosity Test
(f)
Galvanizing Test
Routine Test
(a)
Visual Inspection
(b)
(c)
(d)
b)
castings.
c)
d)
for forgings
Page 10 of 16
Annexure - A
12.3
Testing Expenses
12.3.1
Testing charges for the type test specified shall be indicated separately in
the prescribed schedule
12.3.2
Bidder shall indicate unit type test charges for all type tests covered under
this specification separately, in the relevant schedule of Prices as
applicable.
12.3.3
12.3.4
12.3.5
The entire cost of testing for acceptance and routine tests and tests during
manufacture specified herein shall be treated as included in the quoted Exworks Price.
12.3.6
In case of failure in any type test, if repeat type tests are required to be
conducted, then all the expenses for deputation of Inspector / Owner's
representative shall be deducted from the contract price. Also if on receipt
of the Contractor's notice of testing, the Owner's representative does not
find 'PLANT' to be ready for testing the expenses incurred by the Owner
for re-deputation shall be deducted from contract price.
12.3.7
The Contractor shall intimate the Owner about carrying out of the type
tests along with detailed testing programme at least 3 weeks in advance of
the scheduled date of testing during which the Owner will arrange to
depute his representative to be present at the time of carrying out the tests.
12.4
12.4.1
The Contractor shall offer material for sample selection for type testing
only after getting Quality Assurance Programme approved by the Owner.
The Contractor shall offer at least three times the quantity of materials
required for conducting all the type tests for sample selection. The sample
for type testing will be manufactured strictly in accordance with the
Quality Assurance Programme approved by the Owner.
Page 11 of 16
12.4.2
Before sample selection for type testing, the Contractor shall be required
to conduct all the acceptance tests successfully in presence of Owners
representative.
12.5
Additional Tests
12.5.1
The Owner reserves the right of having at his own expense any other
test(s) of reasonable nature carried out at Contractors premises, at site, or
in any other place in addition to the aforesaid type, acceptance and routine
tests to satisfy himself that the material comply with the Specifications.
12.5.2
The Owner also reserves the right to conduct all the tests mentioned in this
specification at his own expense on the samples drawn from the site at
Contractors premises or at any other test center. In case of evidence of
non compliance, it shall be binding on the part of the Contractor to prove
the compliance of the items to the technical specifications by repeat tests
or correction of deficiencies, or replacement of defective items, all without
any extra cost to the Owner.
12.6
12.7
Guarantee
The Contractor of insulators shall guarantee overall satisfactory
performance of the insulators with the hardware fittings.
12.8
Test Reports
12.8.1
Copies of type test reports shall be furnished in at least six (6) copies
along with one original. One copy shall be returned duly certified by the
Owner only after which the commercial production of the concerned
material shall start.
12.8.2
12.8.3
Page 12 of 16
12.8.4
12.9
Inspection
12.9.1
12.9.2
The material for final inspection shall be offered by the Contractor only
under packed condition as detailed in the specification. The Owner shall
select samples at random from the packed lot for carrying out acceptance
tests. Insulators shall normally be offered for inspection in lots not
exceeding 5000 nos. The lot should be homogeneous and should contain
insulators manufactured in the span of not more than 3-4 consecutive
weeks.
12.9.3
The Contractor shall keep the Owner informed in advance of the time of
starting and the progress of manufacture of material in their various stages
so that arrangements could be made for inspection.
12.9.4
12.9.5
13.0
13.1
All insulators shall be packed in strong seasoned wooden crates. The gross
weight of the crates alongwith the material shall not normally exceed 200
Kg to avoid handling problem.
13.2
Page 13 of 16
13.3
13.4
Page 14 of 16
ANNEXURE A
1.0
2.0
The applied mechanical load during this test shall be 70% of the
rated electromechanical or mechanical value.
(2)
(a)
3.0
Standard deviation.
(b)
(c)
Page 15 of 16
4.0
Standard deviation.
(ii)
(iii)
5.0
6.0
Tests on Castings
The chemical analysis, mechanical and metallographic tests and magnetic,
particle inspection for castings will be as per the internationally recognised
procedures for these tests. The samplings will be based on heat number
and heat treatment batch. The details regarding test will be as discussed
and mutually agreed to by the Contractor and Owner in Quality Assurance
Programme.
Shackle insulators shall be suitable for a minimum failing load of
11.5KN for type I insulator and 16.0KN for type 2 insulator.
Guy strain insulator type A shall be suitable for a minimum failing
load of 44KN whereas, type C shall be suitable for a minimum failing
load of 88 KN
Page 16 of 16
SCOPE
This specification covers 3-pole, 11KV, 50Hz, pole-mounted manually
operated Line Sectionalisers/AB switch for outdoor installation in rural
electrification system.
2.
APPLICABLE STANDARDS
Unless otherwise stipulated in this specification
the line
sectionalisers/AB switch shall comply with the latest version of
IS:9921 (part I to V).
3.
RATED VOLTAGE
The rated voltage for the line sectionalisers/AB switch shall be 12 kV.
This represents the highest system voltage corresponding to the nominal
system voltage of 11 kV.
4.
RATED CURRENT
The standard rated normal current shall be 200/400 Amp.
5.
DESCRIPTION:
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
_________________________________________________________________________________________________
Page 1 of 2
5.10
6.
OPERATION
6.1
The middle post insulator i.e. the insulator where the moving contact is
mounted, shall have elf lubricating rocker bearing arrangement. The
central post shall tilt on this bearing.
6.2
A pantograph shall be used between the moving post and the end post.
6.3
All the three poles shall be ganged operated. No single pole operation
shall be possible.
6.4
6.5
7.0
5.9
TESTING
The sectionaliser shall be tested as per the referred IS.
_________________________________________________________________________________________________
Page 2 of 2
1.
1.1
GENERAL
1.1.1
1.1.2
The scope of supply shall also include necessary special tools and plants
required for erection, maintenance and necessary spares, required for normal
operation and maintenance of the circuit breakers for a period of five years.
1.1.3
1.2
STANDARDS
1.2.1
The circuit breaker shall conform in all respects to the requirements of latest
issue of IS/IEC specifications except for modifications specified herein. The
equipment manufactured according to any other authoritative standards which
ensure an equal or better quality than the provision of IS/IEC specifications shall
also be acceptable. The salient point of difference between the proposed standard
and provision of these specifications shall be clearly brought out in the tender. A
copy of English version of such specifications shall be enclosed with the tender.
1.2.2
The list of standards mentioned in this specification and to which the circuit
conform is given below:
S.
N.
IS
IEC
Description
1.
IS 13118
IEC-56
2.
IS 2099
IEC-137
3.
IS 12729
IEC-694
IEC-815
4.
Page | 1
5.
S.
N.
IS-4379
IS
Description
6.
IS-3072
7.
IS 9135
8.
IEC 60
9.
IEC-17A
Study Group
Dec.1981
Sealing of interrupters/breakers
IEC227
10.
IS-1554
11.
IS-5
12.
IEC 529
IEC 34
AC motors
13.
IS 996
14.
1.3
SERVICE CONDITONS
1.3.1
CLIMATIC CONDITONS
1.3.2
AC Supply
ii)
1.4
DC Supply
-15% to + 10%
ii)
iii)
1.4.1
iv)
v)
vi)
The breaker shall be totally restrike free under all duty conditions and shall
be capable of performing the duties without opening resistor. The details
of any device incorporated to limit or control the rate of rise of
restriking voltage across the circuit breaker contacts shall be stated. The
complete data for the phase factor, amplitude factor, etc., for rate of rise of
re-striking voltage shall be furnished in the tender
vii)
viii)
An operation counter, visible from the ground level even with the
mechanism housing closed shall be provided.
1.4.3
1.4.4
1.4.5
The circuit breaker shall be capable of satisfactory operation even under conditions of
phase opposition that may arise due to faulty synchronization. The maximum
power that the breaker can satisfactorily interrupt under Phase Opposition shall
be stated in the bid.
SEISMIC FACTOR
The insulators shall be capable to withstand the seismic acceleration of 0.5 g
in horizontal direction and 0.6g in vertical direction.
1.5
TEMPERATURE RISE
The maximum temperature attained by any part of the equipment when in
service at side and under continuous full load conditions and exposed to the direct
rays of the sun shall not exceed the permissible limits fixed by IEC. When the
standards specify the limits of temperature rise these shall not be exceeded when
corrected for the difference between ambient temperature specified in the approved
specification.
The limits of temperature rise shall also be corrected for altitude as per IEC and
stated in the bid.
1.6
The insulators shall be designed to have ample insulation, mechanical strength and
rigidity for satisfactory operation under conditions specified above. All bushings
of identical rating shall be interchangeable. The puncture strength of bushing shall
be greater than the flash over value. The design of bushing shall be such that the
complete bushing in a self-contained unit and no audible discharge shall be
detected at a voltage upto a working voltage (Phase Voltage) plus 10%. The
support insulator shall conform to IEC-137. Minimum clearance between phases,
between live parts and grounded objects shall be as per IS-3072-1975 and
should conform to Indian Electricity Rules- 1956.
The minimum creepage
distance for severely polluted atmosphere shall be 25 mm/KV. The protected
creepage distance shall be not less than 50% of total.
1.7
ii)
To hold the circuit breaker in closed position till the tripping signal is
received. iii) To allow the circuit breaker to open without delay immediately on
receiving tripping signal.
iv)
Tripping/Closing Coils
The circuit breakers shall be provided with two trip coils and one closing
coil per breaker. First trip coil shall be utilized for tripping the breaker on
Page | 6
main protection fault detection. Whereas second trip coil shall be used to
trip the breaker when first trip coil fails to trip the breaker and backup
protection comes into operation and shall also be used to trip the breaker on
command. The trip coils shall be suitable for preclosing and after closing
trip circuit supervision. All the breakers shall have provision for independent
electrical operation of trip coils from local as well as remote through
local/remote selector switch. The breaker shall be provided with suitable
protection device against discrepancies in the operation of individual pole.
b)
The trip free mechanism shall permit the circuit breaker to be tripped by the
protective relay even if it is under the process of closing. An antipumping device to prevent the circuit breaker from reclosing after an
automatic opening shall be provided to avoid the breaker from pumping i.e.,
anti pumping relay should interrupt the closing coil circuit.
c)
Controls
Page | 7
Bearing pins, bolts, nuts and other parts shall be adequately pinned or locked
to prevent loosening or changing adjustment with repeated operation of the
circuit breaker. It shall be possible to trip the circuit breaker even in
the event of failure of power supply.
Operating mechanism and all accessories shall be enclosed in control
cabinet. A common marshalling box for the three poles of the breaker shall be
provided, along with supply of tubing, cables from individual pole operating
boxes to the common marshalling box, local.
1.7.1
.
ii)
The spring charging motor shall be AC/DC operated and shall not take
more than 30 sec., to fully charge the closing spring made for automatic
charging. Charging of spring by the motor should not interfere with the
operation of the breakers.
d) The motor shall be adequately rated to carry out a minimum of one
duty cycle. Also provision shall be made to protect the motor against
overloads.
Page | 8
e)
Enclosure
The enclosure shall be made out of cold rolled steel plates not less than 3 mm thick
and of light section structural steel. It should be weather proof as well as dust and
vermin proof.
The enclosure shall have degree of protection IP55. The cabinet shall have full
width and full length hinged doors mounted on the front that swing fully open.
The doors shall be provided with latches to securely hold it with the cabinet.
Doors shall be of sturdy construction, with resilient material covering, fully
perimeterically contacting the cabinet frame to provide dust protection and prevent
metal to metal contact except at the latch points. Filtered ventilation, shall be
provided along with the rigid supports for control and other equipment. Mounting
cabinet members and equipment shall not restrict easy access to terminal blocks for
terminating and testing external connection or to equipment for maintenance.
All screws and bolts used for assembling and mounting wire and cable
termination, supports, devices and other equipment shall be provided with lock
washers or other locking devices. All metal parts shall be clean and free of weld
splatter, rust and mill scale prior to application of double coat of zinc chromate
primer which should be followed by an under coat to serve as base and binder
for the finishing coat. The exterior of the cubicle shall be painted matty grey to
shade No.692 of IS-5 or shade No.631 and interior to white shade. Sufficient
quantity of paints shall also be supplied along with the cubicle to restore at site
any
damage
during
transportation.
Page | 9
Lighting
One 20 watts fluorescent tube fixture and lamp holder working on 240 V 50 c/s
AC supply shall be provided in each switchgear control cubicle section and shall be
located to provide adequate interior lighting of the cubicle. A single-pole door
operated 20
Amp. `T rated lighting switch shall be provided for each cubicle. One duplex 220
volt
convenience outlet shall be provided inside each door or pair of doors inside
each cubicle.
The lighting and convenient outlet circuits shall be completely wired in conduit and
terminated on cubicle terminal blocks.
d)
1.
2.
All the control circuit and secondary wiring shall be wired completely
and brought out preferably to a vertical terminal block ready for
external connections in the control cabinet. The control wire shall not be
of cross- section less than 2.5 mm2 copper.
3.
All spare auxiliary contacts of the circuit breaker shall be supplied wired
upto terminal block. Each terminal in terminal block shall be suitable for at
least 2 x 2.5 mm copper conductor.
4.
5.
6.
All wires shall be identified with non-metallic sleeve or tube type markers
at each terminations.
Page | 10
7.
e)
Grounding
A ground bus of copper bar not less than 6 mm by 25 mm shall be provided along
the inside of the front or rear of the each cubicle and equipment rack. The ground
bus shall be bolted to the frame of each panel in such a way as to make good
electrical contact with each panel or section. Earth terminals at two ends of the
cabinet shall be provided for connection of the ground bus to the station earth mat.
1.8
ACCESSORIES
Each circuit breaker assembly shall be supplied with the following accessories. i)
Line and earthing terminals and terminal connectors.
ii)
Bimetalic terminal connectors iii)
Control housing with:
a)
One auxiliary switch with adequate number of auxiliary contacts, but not
less than 20 nos. (10 No + 10 NC) for each breaker.
b)
Operation counter
c)
Position indicator (Close/Open/Spring Charged)
d)
Necessary cable glands e)
MCBs as required
f)
Manual trip device and local test push buttons
g)
Terminal blocks and wiring for all control equipment and accessories
h)
Adequate number of heaters for continuous operation to prevent
moisture condensation in the housing of operating mechanism
i)
Selector switch for local/remote control.
j)
Internal Illumination fluorescent lamp
j)
5 Amp plug point and socket
k)
Motor for spring charging
iv)
Rating and diagram plate as per IS
1.9
SUPPORTING STRUCTURE
The circuit breakers shall be supplied complete with hot dip galvanized steel
supporting structures, foundation and fixing bolts, etc. The structure shall be
made of steel MS angle section conforming to IS 226. The galvanizing shall be as
per IS. The mounting of the breaker shall be such as to ensure the safety of the
operating staff and should conform to Indian Electricity Rules, 1956. Minimum
ground clearance of live part from ground level shall be as per IE Rules.
The bidder shall submit detailed design calculations and detailed drawings in
Page | 11
respect of supporting structures suitable for the equipment offered. The tenders
shall specify the
loads which shall be transmitted to the equipment foundation under most adverse
operating conditions of the breaker.
All material for making connections between the circuit breaker and its control
shall also be included in the scope of supply.
Extension brackets shall be
provided for directly mounting 12 KV out door current transformers on the
circuit breaker unit. Facility to earth the circuit breaker structure at two points shall
be provided.
1.10 SURFACE FINISH
1.10.1
All interiors and exteriors of control cubicles and other metal parts shall be
thoroughly cleaned to remove all rust, scales, corrosion, greases or other adhering
foreign matter.
1.10.2 All metal surfaces exposed to atmosphere shall be given two primer coats of
zinc chromate and two coats of epoxy paint with epoxy base thinner. All metal
parts not accessible for painting shall be made of corrosion resisting material.
All machine finished or bright surfaces shall be coated with a suitable preventive
compound and suitably wrapped otherwise protected.
All paints shall be
carefully selected to withstand tropical heat and extremes of weather within the
limits specified. The paint shall not scale off or wrinkle or be removed by abrasion
due to normal handling.
All external paintings shall be as per shade No.631 of
IS:5.
1.10.3 All ferrous hardware, exposed to atmosphere, shall be hot dip galvanized.
1.11
GALVANISING
1.11.1 All ferrous parts including all sizes of nuts, bolts, plain and spring washers,
support channels, structures, shall be hot dip galvanized conforming to latest version
of IS:2629 or any other equivalent authoritative standard.
1.12
CABLE TERMINATION
Suitable cable glands for terminating the multicore cable, shall be provided at
the bottom of the control cabinet.
1.13
1.13.1
Each circuit breaker connected with incoming and outgoing feeders shall be
provided with bolted type bi-directional bimetallic terminal connectors suitable for
ACSR conductor/ IPS Aluminium tube.
Page | 12
1.13.2
Each circuit breaker pole and control cabinet shall be provided with two
grounding terminals and clamps for receiving ground connections.
1.14
INTERLOCKS
Necessary interlocks to prevent closing or opening of the breaker under low
pressure of the contact spring and devices for initiating alarm shall be provided.
Provision shall also be made to enable electrical interlocking with the isolators
associated with the
breaker to prevent opening or closing of the isolators. The detailed interlocking
scheme based upon single line diagram of the substation shall be supplied with the
write-up. General requirement of interlock shall be as given below:
1.
2.
Line isolator shaft close only when the corresponding circuit breaker and
earthing switch of the corresponding line are open.
3 The circuit breaker shall close only after all isolators associated with it have
been locked in closed position.Both electrical and Mechanical (castell type)
interlock shall be provided for this.
In case of double bus bar arrangement following additional requirement
for interlocking shall be provided.
1.
2.
3.
1.15
One bus bar selector isolator of any bay excepting the bus coupler bay
shall close only when,
a)
The circuit breaker of corresponding bay is open and
locked. b)
The other bus isolator of that bay is open.
When one bus isolator of any bay excepting the bus coupler bay is closed.
The other shall close only when the bus coupler circuit breaker and both the
bus isolators are closed.
Bus isolator of bus coupler bay shall operate only when the bus coupler
breaker is open.
EARTHING SYSTEM
50x6 mm GI flat earthing connections shall be included in the scope of supply.
The system shall comprise of the leads between the circuit breaker and station mat
and the interconnection between phases where necessary. All switchgear enclosures
should be bolted metal to metal and should carry the full earth return
Page | 13
1.17
1.17.1 Within 30 days after the award of the contract, the contractor shall supply six sets of
drawings which will describe the equipment in details, for the approval of
purchaser. All the drawings and manuals should be in English Language and
dimensions and weights shall be in MKS units.
Following drawings and documents for each item are to be supplied as part of
the contract.
a)
b)
c)
Assembly and sub-assembly drawings with numbered
parts.
d)
e)
Dimension and assembly of important
auxiliaries. f) Detailed drawings of operating
mechanism.
g)
Test
certificates
and
oscillographs.
Page | 14
h)
Detailed drawings of mounting
structure. i) Spare parts and catalogue
j)
Wiring diagram showing the local and remote control scheme of
breaker. k)
Write up on working of control schematic of breaker.
l)
Foundation plan including weights of various components and impact
loadings for working foundation design.
Seven copies for each sub-station of the above drawings and instruction
manuals covering instructions for installations, operation and maintenance shall be
supplied by the contractor(s) without any extra cost.
1.18
Not Used
1.19
TESTS
ii)
Short circuit breaking capacity and making
capacity. iii) Single Capacitor Bank current switching
test.
iv)
Dielectric test i.e., power frequency withstand and impulse withstand
test
v)
test.
vi)
Test.
1.20
Temperature
rise
Mechanical
Endurance
ROUTINE TESTS
Routine Tests as per IEC-56 shall be carried out on each breaker in presence
of purchasers representative at the manufacturers expenses at his works except,
where agreed to otherwise. All test reports should be submitted and should be got
approved from the purchaser before despatch of the equipment.
Page | 15
1.21
1.22
Operation
Insulation Resistance
NAME PLATE
1.22.1 Equipment should be provided with name plate giving full details of
manufacture, capacities and other details as specified in the relevant IS.
Page | 16
1.23
TECHNICAL PARAMETERS
DESCRIPTION
VALUES
i)
11 KV
ii)
50
iii)
iv)
Vacuum
v)
vi)
Number of poles
vii)
Installation
Outdoor type
viii)
Temperature rise
ix)
a) Interrupting capacity at 11 KV
25 KA
As per
IEC
56
(Ref.Page51 21 of IEC)
x)
62.5 KA
xi)
1.5
xii)
25 KA
xiii)
3 Seconds
&
Page | 17
As per IS/IEC
xv)
As per IS/IEC
xvi)
Mounting
xvii)
xviii)
xix)
xx)
300
S.
NO.
DESCRIPTION
xxi)
As per IEC-56
xxii)
RRRV
Characteristics
Surge
Peak
Factor
VALUES
Page | 18
Rated operating
a) duty cycle
O - 0.3 Second CO - 3
Minutes - CO
b) Auto reclosing
xxiv)
75 KV
xxv)
28 KV
xxvi)
25% of
capacity
As oper IEC-56
c) Operating mechanism
Spring
operated,
Anti
pumping and Trip free
mechanism
xxiii)
d)
Power
mechanism
available
for operating
Impedence
Factor K=1.6 A
KV/ms=0.214
Z(ohms) = 450
rated
breaking
Page | 19
S.
NO.
1)
2)
1)
DESCRIPTION
In case of DC Power
supply voltage variation
shall be between 85% to
110%
of
normal
voltage.
2)
In case of AC power
supply voltage variation
VALUES
3% from normal 50 Hz as
per IS 2026 part-I 1977 para
4.4
15%
Page | 20
xxix)
Number of coils
xxx)
Page | 21
Page | 22
INSULATORS
PIN AND DISC INSULATORS
1.0
TECHNICAL DESCRIPTION
1.1
General Requirements
1.1.1
All insulators for 11kV and 33kV shall conform to Type B of latest version of
IS: 731.
1.1.2
1.1.3
The strain insulators shall be of Ball and Socket type or Tongue and Clevis
type.
1.1.4
The string insulators shall only be of Ball and Socket type. For 33 kV string will
consists of 3 nos of 12 kV disc insulators.
1.1.5
Following type of guy strain insulators shall be used on guy wires of overhead
lines of different voltage levels:
Power Line Voltage
11kV
33kV
2.0
3.0
Materials
3.1.
Porcelain
The porcelain used in the manufacture of shells shall be sound, free from
defects thoroughly vitrified and smoothly glazed.
3.2.
Glaze
Page 1 of 12
The finished porcelain shall be glazed in brown colour. The glaze shall cover all
exposed parts of the insulator and shall have a good lusture, smooth surface and
good performance under the extreme weather conditions of a tropical climate. It
shall not crack or chip by ageing under the normal service conditions. The glaze
shall have the same co-efficient of expansion as of the porcelain body
throughout the working temperature range.
3.3.
Cement
Cement used in the manufacture of the insulator shall not cause fracture by
expansion or loosening by contraction. The cement shall not give rise to
chemical reaction with metal fittings and its thickness shall be as small and
uniform as possible. Proper care shall be taken to correctly centre and locate
individual parts during cementing.
4.
Creepage Distance
Medium polluted atmosphere
Highest System
Voltage
Pin Insulator
Strain Insulator
kV
mm
mm
12
230
320
36
580
900
5.
Disc Insulators
5.1.
5.1.1
Pins and Caps shall be made of drop forged steel and malleable cast iron/
spheroidal graphite iron/drop forged steel respectively, duly hot dip galvanised
and shall not be made by jointing, welding, shrink fitting or any other process
from more than one piece of material.
5.1.2
Pin and Cap shall be designed to transmit the mechanical stresses to the shell by
compression and develop uniform mechanical strength in the insulator. The cap
shall be circular with the inner and outer surfaces concentric, of such design that
it will not yield or distort under load conditions.
5.1.3
The pin ball shall move freely in the cap socket but without danger of accidental
uncoupling during erection or in position. The design of the disc should be such
that stresses due to expansion or contraction in any part of the insulator shall not
lead to deterioration.
5.2
Security clip
5.2.1
Security clip for use with ball and socket coupling shall be of R-shaped hump
type which shall provide positive locking of the coupling as per IS:2486-(PartPage 2 of 12
Ill)/ IEC:372. The legs of the security clips shall be spread after installation to
prevent complete withdrawal from the socket. The locking device should be
resilient, corrosion resistant and of suitable mechanical strength. There shall be
no risk of the locking device being displaced accidentally or being rotated when
in position- under no circumstances shall locking device allow separation of
insulator units or fittings.
5.2.2
Security clips shall be made of good quality stainless steel or phosphor bronze
as per IS:1385-1968. 2.5% extra Security clip shall be provided.
5.3
6.0
Interchangeability
The disc insulators inclusive of fittings shall be of standard design suitable for
use with the hardware fittings of any make conforming to relevant
Indian/International Standards.
7.0
Maintenance
7.1
The insulators offered shall be suitable for employment of hot line maintenance
techniques so that the usual hot line operations can be carried out with ease,
speed and safety.
8.0
Workmanship
8.1
All the material shall be of the latest design and conform to the best modern
practices adopted in the distribution voltage field. Contractors shall offer only
such insulators as are guaranteed by him to be satisfactory and suitable for
specified voltage level and will give continued good service.
8.2
The design, manufacturing process and material control at various stages shall
be such as to give maximum working load, highest mobility, best resistance to
corrosion, good finish and elimination of sharp edges and corners.
8.3
The design of the insulators shall be such that stresses due to expansion and
contraction in any part of the insulator shall not lead to deterioration.
8.4
In disc insulators, metal caps shall be free from cracks, seams, shrinks, air holes,
burrs and rough edges. All surfaces of the metal parts shall be perfectly smooth
with no projecting points or irregularities. All load bearing surfaces shall be
smooth and uniform so as to distribute the loading stresses uniformly.
8.5
All ferrous parts shall be hot dip galvanised to give a minimum average coating
of Zinc equivalent to 600 gm/sq.m. and shall be in accordance with the
requirement of IS:2629-1985 and shall satisfy the tests mentioned in IS:2633
1986. The zinc used for galvanising shall be of Grade Zn 99.95 as per IS:2091979. The zinc coating shall be uniform, adherent, smooth, reasonably bright,
continuous and free from imperfections such as flux, ash, rust stains, bulky
white deposits and blisters. The galvanised metal parts shall be guaranteed to
Page 3 of 12
withstand at least six successive dips each lasting for one (1) minute duration
under the standard preece test.
8.6
Before ball fittings are galvanised, all die flashing on the shank surface of the
ball shall be carefully removed without reducing the dimensions below the
design requirements.
8.7
In disc insulators, the design of the insulators shall be such that the shell shall
not engage directly with hard metal. The design shall also be such that when
units are coupled together there is no contact between the shell of one unit and
metal of the next adjacent unit. The design of the shell ribs shall be such that
the security clip of the insulator can be engaged and disengaged easily with hot
stick without damaging the shell ribs.
8.8
Insulator units after assembly shall be concentric and co-axial within limits as
permitted by the relevant Indian Standards.
9.0
Equipment Marking
9.1
Each insulator shall be legibly and indelibly marked with the trademark of the
manufacturer and month & year of manufacture. The guaranteed combined
mechanical and electrical strength shall be indicated in kilo Newton followed by
the word kN to facilitate easy identification and to ensure proper use.
9.2
The marking shall be on porcelain, and shall be printed, not impressed and shall
be applied before firing.
10.0
Bid Drawings
10.1
The Bidder shall furnish full description and illustration of the material offered.
10.2
The Bidder shall furnish along with the bid the outline drawing (6 copies) of
each insulator unit including a cross sectional view of the insulator shell. The
drawing shall include but not limited to the following information:
(a)
(b)
(c)
(d)
(ii)
(e)
(f)
Size and weight of Pin Ball Shank / ball and socket parts
(g)
Page 4 of 12
(h)
Materials
(i)
Identification mark
(j)
10.3
11.0
11.1
Tests
The following type, acceptance, routine tests and tests during manufacture shall
be carried out on the insulator individually and along with hardware fittings. For
the purpose of this clause :
11.1.1
Type tests shall mean those tests which are to be carried out to prove the design
process of manufacture and general conformity of the material to this
specification. These tests shall be carried out on samples prior to
commencement of commercial production against the specification. The Bidder
shall indicate this schedule for carrying out these tests in the activity schedule.
11.1.2
Acceptance tests shall mean those tests which are to be carried out on samples
taken from each lot offered for pre-despatch inspection for the purpose of
acceptance of that lot.
11.1.3
Routine tests shall mean those tests, which are to be carried out on each
insulator/hardware fitting to check requirements which are likely to vary during
production.
11.1.4
Tests during manufacture shall mean those tests which are to be carried out
during the process of manufacture and end inspection by the Supplier to ensure
the desired quality of the end product to be supplied by him.
11.1.5
The norms and procedure of sampling for these tests will be as per the Quality
Assurance Programme to be mutually agreed to by the Supplier and Owner.
11.1.6
The standards and norms to which these tests will be carried out are listed
against them. Where a particular test is a specific requirement of this
specification, the norms and procedure of these shall be as specified in
Annexure-A of this Section or as mutually agreed to between the Supplier and
the Owner in the Quality Assurance Programme.
11.1.7
For all types and accpetance tests, the acceptance values shall be the values
guaranteed by the Bidder in the Guaranteed Technical Particulars of this
proposal or the acceptance value specified in this specification whichever is
more stringent for that particular test.
Page 5 of 12
11.1.8
For all type and acceptance tests, the Bidder shall guarantee only minimum
values in the Guaranteed Technical Particulars. Bidder shall be required to
achieve the same or higher values, as guaranteed, during testing for all type and
acceptance tests.
11.2
Type Tests
The following type tests shall be conducted on a suitable number of individual
insulator unit, components, materials or complete strings:
(a)
Verification of dimensions
(b)
(c)
Power frequency voltage withstand and flashover test (i) dry (ii) wet
(d)
(e)
(f)
(g)
(h)
11.3
Acceptance Tests
(a)
Visual examination
(b)
Verification of dimensions
(c)
(d)
Galvanising test
(e)
(f)
(g)
Eccentricity test
(h)
Metallurgical Test
(i)
(i)
Grain size
(ii)
Inclusion rating
(iii)
Chemical analysis
)
)
)
)
)
(iv)
Microstructure
Page 6 of 12
11.4
(j)
(k)
Porosity test
(l)
Routine Tests
11.5
(a)
Visual Inspection
(b)
(c)
)
)
(b)
(c)
(d)
)
)
)
)
)
)
)
)
)
)
11.6
Test Voltages
11.6.1
Visible
Wet Power
Discharge Frequency
Test
withstand Test
Annexure A
Annexure A
Strain/string
Insulators
Impulse
voltage
withstand
Test
KV(rms) Kv(rms)
KV(rms)
Kv(rms)
kV(rms)
Kv(rms)
12
35
105
75
Page 7 of 12
36
27
75
180
170
11.6.3
11.7
Failing Load
11.7.1
11.7.2
11.8
Testing Expenses
11.8.1
Bidder shall indicate unit type test charges for all type tests covered under this
specification separately, in the relevant schedule of Prices as applicable.
11.8.2
In case of failure of any type test, the Contractor is either required to modify
design of the material and successfully carryout all the type tests as has been
detailed out in this specification or to repeat that particular type test at least
three times successfully at his own expenses.
11.8.3
Contractor shall indicate the laboratories in which they propose to conduct the
type tests. They shall ensure that adequate facilities are available in the
laboratory and the tests can be completed in these laboratories within the time
schedule guaranteed by them in the appropriate schedule.
10.8.4
The entire cost of testing for acceptance and routine tests and tests during
manufacture specified herein shall be treated as included in the quoted Ex-works
Price.
11.8.5
In case of failure in any type test, if repeat type tests are required
to be conducted, then all the expenses for deputation of Inspector / Owner's
representative shall be deducted from the contract price. Also if on receipt of the
Page 8 of 12
Contractor's notice of testing, the Owner's representative does not find 'PLANT'
to be ready for testing the expenses incurred by the Owner for re-deputation
shall be deducted from contract price.
11.8.6
The Contractor shall intimate the Owner about carrying out of the type tests
along with detailed testing programme at least 3 weeks in advance of the
scheduled date of testing during which the Owner will arrange to depute his
representative to be present at the time of carrying out the tests.
11.9
11.9.1
The Contractor shall offer material for sample selection for type testing only
after getting Quality Assurance Programme approved by the Owner. The
Contractor shall offer at least three times the quantity of materials required for
conducting all the type tests for sample selection. The sample for type testing
will be manufactured strictly in accordance with the Quality Assurance
Programme approved by the Owner.
11.9.2
Before sample selection for type testing, the Contractor shall be required to
conduct all the acceptance tests successfully in presence of Owners
representative.
11.10
Not Used
11.11
Additional Tests
11.11.1
The Owner reserves the right of having at his own expense any other test(s) of
reasonable nature carried out at Contractors premises, at site, or in any other
place in addition to the aforesaid type, acceptance and routine tests to satisfy
himself that the material comply with the Specifications.
11.11.2
The Owner also reserves the right to conduct all the tests mentioned in this
specification at his own expense on the samples drawn from the site at
Contractors premises or at any other test centre. In case of evidence of non
compliance, it shall be binding on the part of the Contractor to prove the
compliance of the items to the technical specifications by repeat tests or
correction of deficiencies, or replacement of defective items, all without any
extra cost to the Owner.
11.12
11.13
Not Used.
11.14
Not Used.
11.15
Not Used.
11.16
Page 9 of 12
11.16.1
All insulators shall be packed in strong seasoned wooden crates. The gross
weight of the crates alongwith the material shall not normally exceed 200 kg to
avoid handling problem. For marine transportation, crates shall be paletted.
11.16.2
11.16.3
11.16.4
All packing cases shall be marked legibly and correctly so as to ensure safe
arrival at their destination and to avoid the possibility of goods being lost or
wrongly despatched on account of faulty packing and faulty or illegible
markings. Each wooden case/crate shall have all the markings stenciled on it in
indelible ink.
Page 10 of 12
ANNEXURE A
1.0
2.0
The applied mechanical load during this test shall be 70% of the rated
electromechanical or mechanical value.
(2)
(a)
Where
3.0
Standard deviation.
(b)
The minimum sample size shall be taken as 20 for disc insulator units.
(c)
(ii)
Standard deviation.
The minimum sample size shall be taken as 20 for disc insulators units.
However, for larger lot size, IEC 591 shall be applicable.
Page 11 of 12
(iii)
4.0
5.0
6.0
Tests on Castings
The chemical analysis, mechanical and metallographic tests and magnetic,
particle inspection for castings will be as per the internationally recognised
procedures for these tests. The samplings will be based on heat number and
heat treatment batch. The details regarding test will be as discussed and
mutually agreed to by the Contractor and Owner in Quality Assurance
Programme.
Page 12 of 12
1.
1.1
SCOPE
1.1.1. This section of specification covers the design, manufacture, assembly, shop
testing/inspection before dispatch, packing, forwarding, transportation to site,
insurance (during transit, storage and erection), storage, erection, supervision, site
testing and commissioning of 36 KV outdoor type vacuum circuit breakers at
various 33/11 kV substations.
1.1.2. The scope of supply shall also include necessary special tools and plants required
for erection, maintenance and necessary spares, required for normal operation and
maintenance of the circuit breakers for a period of five years.
1.1.3. The circuit breakers should be complete in all respects with insulators, bimetallic
connectors, interruptingchamber, operating
mechanisms
control
cabinet, interlocks,
auxiliary
switches indicating
devices,
supporting structures, accessories, etc., described
herein and briefly listed in the schedule of requirements. The spares/attachments
which are necessary for the smooth functioning of the equipment and specifically
are not mentioned here shall be assumed to be included the scope of supply.
1.2
STANDARDS
1.2.1. The circuit breaker shall conform in all respects to the requirements of latest issue
of IS/IEC specifications except for modifications specified herein.he
equipment manufactured according to any other authoritative standards which
ensure an equal or better quality than the provision of IS/IEC specifications shall
also be acceptable. The salient point of difference between the proposed standard
and provision of these specifications shall be clearly brought out in the tender. A
copy of English version of such specifications shall be enclosed with the tender.
1.2.2. The list of standards mentioned in this specification and to which the circuit
conform is given below:
S.
N.
IS
IEC
1.
IS 13118
IEC-56
Desc
ripti
on Breakers
High Voltage A.C. Circuit
2.
IS 2099
IEC-137
3.
IS 12729
IEC-694
4.
IEC-815
5.
IS-4379
6.
IS-3072
7.
IS 9135
8.
IEC 60
9.
IEC-17A
Study Group
Dec.1981
Sealing of interrupters/breakers
IEC227
10.
IS-1554
11.
IS-5
12.
1.3
IEC 529
13.
IS 996
IEC 34
AC motors
14.
IS 2629,
2633
ISO 1460
SERVICE CONDITONS
a)
b)
The above supply voltage may vary as indicated below and all devices shall be suitable for
continuous operation over the entire range of voltages
1.4
i)
AC Supply
Voltage + 10%/-15%
Frequency 5%
Combined voltage and frequency +10% to -15%
ii)
DC Supply
-15% to + 10%
The performance of breakers shall be adequately proven by type tests for the
designed rating at internationally reputed independent testing station.
ii)
iii)
iv)
v)
vi)
The breaker shall be totally restrike free under all duty conditions and shall be
capable of performing the duties without opening resistor. The details of any
device incorporated to limit or control the rate of rise of restriking voltage across
the circuit breaker contacts shall be stated. The complete data for the phase factor,
amplitude factor, etc., for rate of rise of re-striking voltage shall be furnished in the
tender.
vii)
The breaker shall be suitable for three phase auto reclosing operation.
viii)
ground level
even
with the
TEMPERATURE RISE
The maximum temperature attained by any part of the equipment when in service at site
and under continuous full load conditions and exposed to the direct rays of the sun shall
not exceed the permissible limits fixed by IEC. When the standards specify the limits of
temperature rise these shall not be exceeded when corrected for the difference between
ambient temperature specified in the approved specification.
The limits of temperature rise shall also be corrected for altitude as per IEC and stated in
the bid.
1.6
1.7
functions efficiently.
i)
To provide means where the circuit breaker can be closed rapidly, without
hesitation at all currents from zero to rated making current capacity.
ii)
To hold the circuit breaker in closed position till the tripping signal is
received.
iii)
iv)
Tripping/Closing Coils
The circuit breakers shall be provided with two trip coils and one closing coil per
breaker. First trip coil shall be utilized for tripping the breaker on main protection
fault detection. Second trip coil shall be used to trip the breaker when first trip coil
fails to trip the breaker and backup protection comes into operation and shall also
be used to trip the breaker on command. The trip coils shall be suitable for
preclosing and after closing trip circuit supervision. All the breakers shall
have provision for independent electrical operation of trip coils from local as well
as remote through local/remote selector switch. The breaker shall be provided with
suitable protection device against discrepancies in the operation of individual pole.
b)
The trip free mechanism shall permit the circuit breaker to be tripped by the
protective relay even if it is under the process of closing. An anti- pumping
device to prevent the circuit breaker from reclosing after an automatic opening
shall be provided to avoid the breaker from pumping i.e., anti pumping relay should
interrupt the closing coil circuit.
c)
Controls
The circuit breaker shall be controlled by a control switch located in the control
room. The control arrangement shall be such as to disconnect the remote control
circuits of the breaker, when it is under test. Local/remote selector switch shall be
provided for all breakers for selection of Local control/remote control.
Provision shall be made for local manual, closing, tripping and spring charging
controls.
Necessary equipments for local controls shall be housed
in the circuit breaker cabinet of weather-proof construction.
Each circuit breaker shall have a mechanical open/closed and spring charge
indicator Lamps for indicating, close, open and spring charged position of the
breaker shall also be provided.
Mechanical indicator, to show the `open and `close position of the breaker
shall be provided in a position where it will be visible to a man standing on ground
with mechanism housing open. An operation counter, visible from the ground even
with the mechanism housing closed, shall be provided. Electrical tripping of the
breaker shall be performed by shunt trip coils.
Closing coil shall operate correctly at all value of supply voltage between
85% and 110% of the rated voltage.Shunt trip coils shall operate correctly
under all operating conditions of circuit breaker upto the rated breaking capacity
and at all values of supply voltage between 85% and 110% of rated voltage.
Bearings which require grease shall be equipped with pressure type fillings.
Bearing pins, bolts, nuts and other parts shall be adequately pinned or locked to
prevent loosening or changing adjustment with repeated operation of the circuit
breaker.It shall be possible to trip the circuit breaker even in the event of failure
of power supply.
Operating mechanism and all accessories shall be enclosed in control cabinet.
A common marshalling box for the three poles of the breaker shall be provided,
along with supply of tubing, cables from individual pole operating boxes to the
common marshalling box, local.
1.7.1. SPRING OPERTED MECHANISM
The operating mechanism shall have all the necessary auxiliaries, apparatus for operation
and supervision, like motor starter with thermal overload release, one closing coil, two trip
coils, push button for local electrical operation, local/remote control selector switch, push
button for direct mechanical tripping, auxiliary switches, antipuming contactors, operation
counter, socket for inspection, lamp and heater with switch.
In
addition
mechanical interlocking system for interlocking with associated isolators shall be
provided. Spring charging motor shall be standard single phase universal motor suitable
for 220 volts supply.
i)
Operating voltages for closing/tripping coils shall be 110 Volts DC or 30 Volts
DC or 240 Volts AC supply. The dc voltage as available at the substation shall be used. If
dc supply is not available at the substation, then 240 V AC will be used for circuit
breaker tripping/closing controls. The CB shall be of Series Trip type requiring no DC
supply. The closing coil for Series Trip type CB shall be operating on 240 Volts AC supply.
ii)
Operating voltages for heater elements shall be 240V AC 50 HZ. Other features
of the spring operated mechanism shall be as follows.
a)
The spring operating mechanism shall have adequate energy stored in the
operating to close and latch the circuit breaker against the rated making current
and also to provide the required energy for tripping mechanism in case the
tripping energy is derived from the operating mechanism.
a) Enclosure
The enclosure shall be made out of cold rolled steel plates not less than 3 mm thick
and of light section structural steel. It should be weather proof as well as dust and
vermin proof. The enclosure shall have degree of protection IP55 as per IS 13947. The
cabinet shall have full width and full length hinged doors mounted on the front that swing
fully open. The doors shall be provided with latches to securely hold it with the cabinet.
Doors shall be of sturdy construction, with
resilient material covering, fully perimeterically contacting the cabinet frame to provide
dust protection and prevent metal to metal contact except at the latch points. Filtered
ventilation, shall be provided along with the rigid supports for control and other
equipment. Mounting cabinet members and equipment shall not restrict easy access to
terminal blocks for terminating and testing external connection or to equipment for
maintenance.
All screws and bolts used for assembling and mounting wire and cable termination,
supports, devices and other equipment shall be provided with lock washers or other locking
devices. All metal parts shall be clean and free of weld splatter, rust and mill scale prior to
application of double coat of zinc chromate primer which should be followed by an under
coat to serve as base and binder for the finishing coat. The exterior of the cubicle shall be
painted matty grey to shade No.692 of IS-5 or shade No.631 and interior to white shade.
Sufficient quantity of paints shall also be supplied along with the cubicle to restore
at site any damage during transportation. The mounting structure shall be galvanized
and shall be as per IS-802-II-1978.
b) Heaters
Suitable space heaters shall be mounted in the cabinet to prevent condensation. Heaters
shall be controlled by thermostat. ON/OFF MCB shall be provided. Heaters shall be
suitable for 240 V AC supply voltage.
c) Lighting
One 20 watts fluorescent tube fixture and lamp holder working on 240 V 50 c/s AC
supply shall be provided in each switchgear control cubicle section and shall be located to
provide adequate interior lighting of the cubicle. A single-pole door operated 20 Amp.
`T rated lighting switch shall be provided for each cubicle. One duplex 220 volt
convenience outlet shall be provided inside each door or pair of doors inside each cubicle.
The lighting and convenient outlet circuits shall be completely wired in conduit and
terminated on cubicle terminal blocks.
d) Wiring and Cabling
1.
1.8
2.
All the control circuit and secondary wiring shall be wired completely and brought
out preferably to a vertical terminal block ready for external connections in
the control cabinet. The control wire shall not be of cross- section less than 2.5
mm2 copper.
3.
All spare auxiliary contacts of the circuit breaker shall be supplied wired upto
terminal block. Each terminal in terminal block shall be suitable for at least 2 x
2.5 mm copper conductor.
4.
At least 20 number spare terminals shall be provided over and above the number
required.
5.
All wiring termination on terminal blocks shall be made through lugs. For current
and DC supply circuits disconnecting stud type terminal blocks will be
provided. For other control circuits, non-disconnecting snap on type terminal
blocks shall be provided.
6.
All wires shall be identified with non-metallic sleeve or tube type markers at each
terminations.
7.
e)
Grounding
A ground bus of copper bar not less than 6 mm by 25 mm shall be provided along the
inside of the front or rear of the each cubicle and equipment rack. The ground bus shall be
bolted to the frame of each panel in such a way as to make good electrical contact with
each panel or section. Earth terminals at two ends of the cabinet shall be provided for
connection of the ground bus to the station earth mat.
ACCESSORIES
Each circuit breaker assembly shall be supplied with the following accessories. i)
Line and earthing terminals and terminal connectors.
ii)
Bimetalic terminal connectors.
iii)
Control housing with:
a) One auxiliary switch with adequate number of auxiliary contacts, but not less than
20 nos. (10 No + 10 NC) for each breaker.
b) Operation counter
c) Position indicator (Close/Open/Spring Charged)
d) Necessary cable glands e)
MCB as required
f) Manual trip device and local test push buttons
g) Terminal blocks and wiring for all control equipment and accessories
h) Adequate number of heaters for continuous operation to prevent moisture
SUPPORTING STRUCTURE
The circuit breakers shall be supplied complete with hot dip galvanized steel supporting
structures, foundation and fixing bolts, etc. The structure shall be made of steel MS angle
section conforming to IS 226. The galvanizing shall be as per IS.
The mounting of
the breaker shall be such as to ensure the safety of the operating staff and should
conform to Indian Electricity Rules, 1956. Minimum ground clearance of live part from
ground level shall be 3700 mm.
The bidder shall submit detailed design calculations and detailed drawings in respect of
supporting structures suitable for the equipment offered. The tenders shall specify the
loads which shall be transmitted to the equipment foundation under most adverse operating
conditions of the breaker.
All material for making connections between the circuit breaker and its control shall also
be included in the scope of supply. Facility to earth the circuit breaker structure at two
points shall be provided.
1.10
SURFACE FINISH
1.10.1. All interiors and exteriors of control cubicles and other metal parts shall be
thoroughly cleaned to remove all rust, scales, corrosion, greases or other adhering foreign
matter.
1.10.2. All metal surfaces exposed to atmosphere shall be phosphated as per IS 6005 and there
after given two primer coats of zinc chromate and then two coats of epoxy paint with
epoxy base thinner. All metal parts not accessible for painting shall be made of corrosion
resisting material. All machine finished or bright surfaces shall be coated with a suitable
preventive compound and suitably wrapped on otherwise protected. All paints shall be
carefully selected to withstand tropical heat and extremes of weather within the limits
specified. The paint shall not scale off or wrinkle or be removed by abrasion due to normal
handling.
All external paintings shall be as per shade No.631 of IS:5.
1.10.3. All ferrous hardware, exposed to atmosphere, shall be hot dip galvanized.
1.11
GALVANISING
1.11.1. All ferrous parts including all sizes of nuts, bolts, plain and spring washers, support
channels, structures, shall be hot dip galvanized conforming to latest version of IS:2629 or
any other equivalent authoritative standard.
1.12
CABLE TERMINATION
Suitable cable glands for terminating the multicore cable shall be provided at the bottom of
the control cabinet.
1.13
1.13.1.
Each circuit breaker connected with incoming and outgoing feeders shall be provided
with bolted type bi-directional bimetallic terminal connectors suitable for ACSR
conductor mentioned in `Technical Parameter clause 1.26.1.
1.13.2.
Each circuit breaker pole and control cabinet shall be provided with two
grounding terminals and clamps for receiving ground connections.
1.14
INTERLOCKS
Necessary interlocks to prevent closing or opening of the breaker under low pressure of the
contact spring and devices for initiating alarm shall be provided. Provision shall also be
made to enable electrical interlocking with the isolators associated with the breaker to
prevent opening or closing of the isolators. The detailed interlocking scheme based upon
single line diagram of the substation shall be supplied with the write-up. General
Requirement of interlock shall be as given below:
1.
Isolators should not be operated unless the associated circuit breaker is in open
position.
2.
Line isolator shall close only when the corresponding circuit breaker and earthing
switch of the corresponding line are open. Both electrical and mechanical
3.
The circuit breaker shall close only after all isolators associated with it have
been locked in closed position. Both electrical and Mechanical (casted type)
interlock shall be provided for this.
2.
One bus bar selector isolator of any bay excepting the bus coupler bay shall
close only when,
a)
The circuit breaker of corresponding bay is open and locked. b) The
other bus isolator of that bay is open.
When one bus isolator of any bay excepting the bus coupler bay is closed.
The other shall close only when the bus coupler circuit breaker and both the bus
isolators are closed.
3.
1.15
Bus isolator of bus coupler bay shall operate only when the bus coupler breaker
is open
EARTHING SYSTEM
50x6 GI flat earthing connections shall be included in the scope of supply. The system
shall comprise of the leads between the circuit breaker and station mat and the
interconnection between phases where necessary. All switchgear enclosures should be
bolted metal to metal and should carry the full earth return current. Connection between
phases at the earthing points shall be dimensioned for carrying full earth return current.
1.16
1.17
1.17.1. Within 30 days after the award of the contract, the contractor shall supply six sets of
drawings which will describe the equipment in details, for the approval of Purchaser. All
the drawings and manuals should be in English Language and dimensions and weights
shall be in MKS units.
Following drawings and documents for each item are to be supplied as part of the contract.
a)
General outline drawings, showing dimensions, front and side elevations and plan
of the circuit breaker and its local control panel.
b)
c)
d)
f)
1.18
TESTS
ROUTINE TESTS
Routine Tests as per IEC-56 shall be carried out on each breaker in presence of purchasers
representative at the manufacturers expenses at his works except, where agreed to
otherwise. All test reports should be submitted and should be got approved from the
Purchaser before despatch of the equipment.
1.20
2)
3)
4)
1.21
NAME PLATE
1.21.1. Equipment should be provided with name plate giving full details of manufacture,
capacities and other details as specified in the relevant IS.
1.22
TECHNICAL PARAMETERS
1.22.1.
36 KV CIRCUIT BREAKERS
S.
NO.
DESCRIPTION
VALUES
i)
36 KV
ii)
50
iii)
iv)
Vacuum
v)
1250 Amps
vi)
Number of poles
vii)
Installation
Outdoor type
viii)
Temperature rise
ix)
a) Interrupting capacity at 36 KV
25 KA
As
per
IEC
56
(Ref.Page51 21 of IEC)
x)
62.5 KA
xi)
1.5
xii)
25 KA
xiii)
3 Seconds
xiv)
< 80 ms
xv)
< 150 ms
xvi)
Mounting
xvii)
400
&
xviii)
xix)
xxi)
xxiii)
xxiv)
xxv)
xxvi)
xxvii)
xxviii)
2820
150
900
As per IEC-56
RRRV
Characteristics
For short line faults
:
:
Rated operating
Surge
Impedence
Peak
Factor K=1.6 A
KV/ms=0.214
Z(ohms) = 450
a) duty cycle
b) Auto reclosing
:
:
0-0.3Second-CO-3
Suitable
for three phase
Minutes-CO
Auto reclosing duty
170 KV
70 KV
b)
Standard values
recovery
c) Operating mechanism
of
transient
d)
Power available for operating
mechanism
S.
NO.
DESCRIPTION
:
:
25% of rated
capacity
As oper IEC-56
breaking
Spring
operated,
Anti
pumping and Trip free
Three
phase 415 Volts 50
mechanism
C/S or single phase 50 C/S
VALUES
240 volts
xxix)
c) Permissible frequency
xxx)
xxxi)
Number of coils
xxxii)
1)
2)
POST INSULATOR
1.0
1.1
Post Insulators are required to provide rigid supports for bus bars part of
Isolators, AB Switches and other equipments/conductors in the sub-station.
1.2
Standard: Except where they conflict with the specific requirement of this
specification, the post insulators, the post insulators shall comply with the IS :
2544-1973, IS : 5350 Part-II 1969(latest) amendments.
1.3.0
1.3.1
Mechanical Strength: The Post Insulators shall be suitable for the minimum
failing loads specified as under:
Sl.
No
Highest
System
voltage
Failing Loads(Min.)
Bending(N)
12 KV
5000
200
15000
30000
36 KV
4500
680
30000
40000
1.3.2
1.3.2
2.0
Highest
Normal and
System Sl.No
moderately
Total
voltage
polluted
atmosphere
(total)
12 KV
230 mm
380 mm
36 KV
580 mm
840 mm
Protected
420 mm
Atmospheric Conditions:The material offered shall be suitable for operation under the climatic conditions
indicated below:
a)
b)
c)
d)
43C
40C
60C
100%
e)
f)
g)
h)
i)
j)
k)
50 days
20
1750 mm
1270 mm
32C
75 Kg/m2
3.0 Reference atmospheric conditions at which Post Insulator or Post Insulator units
characteristics shall be expressed for the purpose of comparison shall be as given
below :
200 C
Ambient temperature
Barometric Pressure
Absolute humidity
3.1 Test for the purpose of this standard shall preferably be carried out under conditions
of temperature and humidity specified in IS : 196- 1966(revised) i.e. a temperature of
2720 C and relative humidity of 652 % and at the prevailing atmospheric pressure.
when this is not possible test m ay be carried out under conditions naturally obtaining
at the time of test. The barometric pressure, air temp. and humidity shall be recorded
for the purpose of correction. Correction of test voltage for atmospheric conditions is
given in Appendix-A of IS: 2544 1973.
3.2 General Requirements :
3.2.1 The porcelain shall be sound and free defects, thoroughly vitrified and smoothly
glazed.
3.2.2 Unless otherwise specified the glaze shall be brown in colour. The glaze shall cover
all the expose porcelain part of the insulator except those area which serve as
support or required to be left un-glazed.
3.2.3 Precaution shall be taken during design and manufacture to avoid the following :
a)
b)
Stress concentration due to direct engagement of the porcelain with the metal
fittings.
c)
d)
3.2.4
Cement used in the construction of the post insulator shall not cause fracture by
expansion or loosening by contraction and proper care shall be taken to locate the
individual parts correctly during cementing. Further, the cement shall not give rise to
chemical reaction with metal fittings and its thickness shall be as uniform as possible.
Page 2 of 5
3.2.5
All ferrous metal parts except those of stainless steel, shall be hot dip
galvanized and the uniformity of zinc coating shall satisfy the requirements of IS :
2633 1964. The parts shall be galvanized after mechanising . The finished
galvanized surface shall be smooth.
3.2.6
The threads of the tapped holes in the post insulators metal fittings shall be cut
after giving anti- corrosion protection and shall be protected against rest by greasing
of other similar means. All other threads shall be cut before giving anti-corrosion
protection. The tapped holes shall be suitable for bolts with threads having anti corrosion protection and shall confirm to IS : 4218(Part-I to VI). The effective length
of thread shall not be less than the nominal diameter of the bolt.
3.2.7
The post insulator unit shall be assembled in a suitable jig to ensure the correct
positioning of the top and bottom metal fitting relative to one another. The faces of
the metal fittings shall be parallel and at right angles to the axis of the insulator and
the corresponding holes in the top and bottom metal fittings shall be in a vertical plan
containing the axis of insulator.
4.0
Classification
The standard insulator levels of the post insulator or post insulator unit shall be as under ::
Highest
system
voltage
Visible
discharge
test
Dry
one
minute
power
frequency
withstand
test.
Wet
one
minute
power
frequency
withstand
test.
Power
frequency
puncture
withstand
test.
12 KV 9 KV(rms)
(rms)
35 KV(rms)
35 KV(rms)
KV
36 KV 27 KV(rms)
(rms)
75 KV(rms)
75 KV(rms)
KV
Page 3 of 5
Impulse
voltage
withstand
test.
5.2
In this standard ,power frequency voltage are expressed as peak values divided by 2.
The impulse voltage are expressed as peak values.
5.3 The withstand and flashover voltage are referred to the atmospheric condition.
6.0
6.1
Tests:
The insulators shall comply with the following constitute the type tests :
a) Visual examination.
b) Verification of dimensions.
c) Visible discharge test.
d) Impulse voltage withstand test.
e) Dry power frequency voltage withstand test.
f) Wet power frequency voltage withstand test.
g) Temperature cycle tests.
f) Mechanical strength tests.
g) Puncture test.
h) Porosity test.
i) Galvanising test.
Type test certificates for the tests carried out on prototype of same specifications shall
be enclosed with the tender.
be subjected to the following acceptance test in the order indicated below :
6.2
Acceptance test : The test samples after having withstood routine test shall be
subjected to the at least following acceptance test in the order indicated below :
a) Verification of dimensions.
b) Temperature cycle tests.
c) Mechanical strength tests.
d) Puncture test.
e) Porosity test.
f) Galvanising test.
6.3
Routine tests: following shall must be covered as routine tests on each post insulator
or post insulator unit.
a) Visual examination as per Cl. No.- 9.12 of IS : 2544/1973
Page 4 of 5
Marking
7.1
Each post insulator shall be legibly and indelibly marked to show the following.
a)
Name or trade mark of the manufacturer.
b)
Month of year of manufacture.
c)
Country of manufacture.
7.1.1 Marking on porcelain shall be printed and shall be applied before firing.
7.2
Post insulator or post insulator units may also be mark with I.S.I. certification mark.
8.
Packing
All post insulators shall be pack in wooden crates suitable for easy but rough handling
and acceptable for rail, transport. Where more than one insulator is packed in a create wooden
separators shall be fixed between the insulators to keep individual insulator in position without
movement within the crate.
Page 5 of 5
SCOPE
1.1
1.2
5 MVA
2.
No. of Phases
3.
Type of Installation
Outdoor
4.
Frequency
50 Hz
5.
Cooling medium
Insulating Oil
6.
Rated voltage
a) High voltage winding
b) Low voltage winding
33kV
11kV
36kV
12kV
8.
9.
Range of tapings
10.
On LV Side only
11 a
12.
13.
14.
16.
17.
Vector group
7.
15.
33kV
70
Dyn 11
-1-
11kV
28
18.
Type of cooling
ONAN
19.
Neutral earthing
20.
21
One no
One No.
22
Current Density
23
Flux Density
50 0C
b)
55 0C
The rise in temperature of top oil and winding given above shall be reduced as per clause
3.2 & 3.3 of IS 2026 (Part-I) in case of increase in Ambient above 50 oC and an increase in
altitude above 1000 m.
1.3
PERFORMANCE
The performance of the transformer shall be measured on the following aspects.
i)
ii)
-2-
iii)
1.4
1.5
DRAWINGS/DOCUMENTS
Detailed overall general outline drawing showing front and side elevations and plan of
the transformer and all accessories including radiators and external features with details
of dimensions, spacing of wheels in either direction of motion, net weights and shipping
weights, crane lift for un-tanking, bushing lifting height, clearances between HV and LV
terminals and ground, quantity of insulating oil etc.
ii)
Foundation plan showing loading on each wheel and jacking points with respect to centre
line of transformer.
iii)
GA drawings/details of bushing.
iv)
v)
vi)
vii)
viii)
ix)
x)
xi)
xii)
xiii)
xiv)
xv)
1.6
MISCELLANEOUS
i)
Padlocks alongwith duplicate keys as asked for various valves, marshalling box
etc., shall be supplied by the contractor, wherever locking arrangement is
provided.
ii)
1.7
Foundation rails, bolts, clamps for fixing rail, wheel locking devices of
Transformer shall be supplied by the Contractor.
ALTITUDE FACTOR
If the equipment is to be installed in altitude above 1000 meter, necessary correction
factors as given in the Indian Standard for oil temperature rise, insulation level etc. shall
be applied to the Standard Technical Parameters given above.
1.8
NAME PLATE
Transformer rating plate shall contain the information as given in clause 15 of IS-2026
(Part-I). The details on rating plate shall be finalised during the detailed engineering.
2.0
2.1
2.2
The equipment, materials and service covered by this specification shall conform to the
latest applicable provision of the following standards:
-4-
IS:5
IS:335
IS:1271
Power Transformer
IS:2071
IS:2099
IS:13947
IS:3347
:
:
IS: 3637
IS:3639
IS: 5561
IS: 6600
IS: 6005
IS: 10028
C.B.I.P. Publication
If the standard is not quoted for any item, it shall be presumed that the latest
version of the relevant Indian Standard shall be applicable to that item.
The equipment complying other internationally accepted standards, may also be
considered if they ensure performance superior to the Indian Standards. If the standard is
of language other than English, an English translation shall be provided
3.0
3.1
-5-
stresses which may impair suitability of the various parts for the work which they have
to perform.
3.2
3.3
Pipes and pipe fittings, screws, studs, nuts and bolts used for external connections shall
be as per the relevant standards.
Nuts, bolts and pins used inside the transformers and tap changer compartments shall be
provided with lock washers or locknuts.
3.4
3.5
Exposed parts shall not have pockets where water can collect.
3.6
Internal design of transformer shall ensure that air is not trapped in any location.
3.7
Material in contact with oil shall not react with oil or to contribute to the formation of
acid in oil. Surface in contact with oil shall not be galvanized or cadmium plated.
3.8
Labels, indelibly marked, shall be provided for all identifiable accessories like switches
etc. All label plates shall be of in-corrodible material.
3.9
All internal connections and fastenings shall be capable of operating under overloads
and over-excitation, allowed as per specified standards without injury.
3.10
3.11
3.12
Schematic Drawing of the wiring, including external cables shall be put under the
prospane sheet on the inside door of the transformer marshalling box.
4.0
4.1
-6-
4.2
Surface Preparation for radiatorAll internal and external surfaces of radiator shall be thoroughly cleaned either by
chemical cleaning or by blast with sand or shot or grit in accordance with ISO 8501 Part
1 to make the surface free from visible oil, grease & dirt, mill scale, rust, paint coatings
and foreign matter. Suitable chemical should be used for chemical cleaning, if required.
The air that is used for blasting should be dry and free from oil. After adequate surface
cleaning, the first coat of primer paint/varnish should be applied not later than 3-4 hours
after preparation of surface to avoid oxidation.
4.3
Painting- external & internal surfacesPainting shall be carried out in closed and dust free area. The external surface shall be
coated with suitable layers of paint and to form an impermeable layer so that air and
water cannot reach the substrate. The paint selected shall be stable in outdoor condition
such as rain, sunlight, pollution etc. Paint used for primer, under coat and top or finish
coat should be from the same manufacturer and compatible to each other. In case in the
rare event, paint used for primer, under coat and finish coat are not from the same
manufacturer the compatibility test of the paint from different source shall be carried out.
Painting shall be applied as per the recommendation of the paint manufacturer. The
number of coats shall be such that the minimum dry film thickness (DFT) specified is
achieved. The DFT of painted surface shall be checked with a measuring gauge to ensure
specified DFT. Complete painting scheme for the transformer is tabulated below:
4.4
SURFA
CE
PREPA
RATIO
N
Tank, pipes, etc. Blast
cleaning
(External
Sa2
surfaces)
PRIMER
COAT
INTERMEDI
ATE
UNDERCOA
T
FINISH
COAT
Radiator
and Chemica
-7-
--
TOTAL
DFT
COLOUR
SHADE
Min
m
Min
m
30 Glossy white
for paint
Min
110m
--
Matching
shade of tank/
different
shade
aesthetically
matching to
tank
--
pipes (Internal l
cleaning
surfaces)
if
required
4.5
low viscosity
varnish,
flushing with
transformer
oil.
4.5.1. Surface Preparation for all Transformer Control cabinets/Marshalling Boxes shall be
carried out confirming to following Indian standard in dust free area:
i)
IS: 3618: Degreasing by solvent wiping: Phosphate Treatment of Iron &Steel for
Protection against corrosion.
ii)
IS: 6005: Code of Practice for phosphating of Iron & Steel.
4.5.2. Chemicals: Suitable chemicals should be used and concentration of chemicals /weight of
Phosphate coating should be checked regularly as per recommendation of the chemical
manufacturer and applicable IS.
4.5.3. Inspection: The surface for application of paint should be dry, free from oil, dirt, acid &
loose adhering powder and reasonably smooth in finish without uncovered areas, rusty
surfaces and roughness.
4.6
Painting- Control cabinets/Marshalling Boxes -Enamel paint shall be used with total paint
thickness as minimum 80 microns.
5.0
DETAILED DESCRIPTION
5.1
Tank
5.1.1. The Transformer tank and cover shall be fabricated from high grade low carbon plate
5.1.2.
5.1.3.
5.1.4.
5.1.5.
5.1.6.
steel of tested quality of adequate thickness. The tank and the cover shall be of welded
construction. All welds shall be stress relieved. Stiffener shall be provided for general
rigidity. Tank surface shall be designed to prevent retention of water.
Tank shall be designed to permit lifting by crane or jacks of the complete transformer
assembly filled with oil. Suitable lugs and bosses shall be provided for this purpose.
All beams, flanges, lifting lugs, braces and permanent parts attached to the tank, shall be
welded and where practicable, they shall be double welded.
The main tank body of the transformer, excluding tap changing compartments and
radiators, shall be capable of withstanding pressure of 760 mm of Hg.
All bolted connections to the tank shall be fitted with suitable oil-tight gaskets which
shall give satisfactory service under the operating conditions for complete life of the
transformer. Special attention shall be given to the methods of making the hot oil-tight
joints between the tank and the cover as also between the tank cover and the bushings and
all outlets to ensure that the joint can be remade satisfactorily and with ease, with the help
of semi-skilled labour. Where compressible gaskets are used, steps shall be provided to
prevent over-compression.
Suitable guides shall be provided for positioning the various parts during assembly or
dismantling. Adequate space shall be provided between the cores and windings and the
bottom of the tank for collection of any sediment.
-8-
5.2
Tank Cover
5.2.1. The transformer top shall be provided with a detachable tank cover with bolted flanged
gasket joint. Lifting lugs shall be provided for removing the cover. The surface of the
cover shall be suitably sloped so that it does not retain rain water.
5.2.2. Inspection hole(s) with welded flange(s) and bolted cover(s) shall be provided on the tank
cover. The inspection hole(s) shall be of sufficient size to afford easy access to the lower
ends of the bushings, terminals etc.
5.2.3. Pockets shall be provided for bulbs of OTI & WTI. Air and Oil tightness shall be ensured
for the same.
5.2.4. The bolted openings shall be fitted with weather proof hot oil resisyant neoprene gasket
for complete tightness.
5.3
UNDER CARRIAGE
5.3.1. The transformer tank shall be supported on steel structure with detachable plain rollers
completely filled with oil. Suitable channels for movement of roller with transformer
shall be spaced
accordingly. Rollers wheels shall be provided with suitable rollers
bearings, which will resist rust and corrosion and shall be equipped with fittings for
lubrication. It shall be possible to swivel the wheels in two directions, at right angle to or
parallel to the main axis of the transformers.
5.3.2. Jacking pads shall be provided on the transformer. It shall be possible to change the
direction of the wheels through 90 degree when the transformer is lifted on jacks to
permit movement of the transformer both in longitudinal and transverse directions.
5.4
CORE
5.4.1. Stage level inspection for core construction shall be carried out by the owner.
5.4.2. The core shall be constructed either from high grade, non-aging Cold Rolled Grain
Oriented (CRGO) silicon steel laminations conforming to grade M4 or better. The
maximum flux density in any part of the cores and yoke at normal voltage and frequency
shall be such that the flux density with + 12.5 % voltage variation from rated voltage or
frequency variation of -5% shall not exceed 1.9 Tesla. The bidder shall provide
saturation curve of the core material proposed to be used.
5.4.3. The bidder should offer the core for inspection and approval by the purchaser during the
manufacturing stage. Bidders call notice for the purpose should be accompanied with the
following documents as applicable as a proof towards use of prime core material:
a) Invoice of the supplier
b) Mills test certificate
c) Packing list
-9-
d) Bill of lading
e) Bill of entry certificate to customs
Core material shall be directly procured either from the manufacturer or through their
accredited marketing organization of repute and not through any agent.
5.4.4. The laminations shall be free of all burrs and sharp projections. Each sheet shall have an
insulating coating resistant to mechanical pressure and the action of hot oil.
5.4.5. The insulation structure for the core to bolts and core to clamp plates, shall be such as to
withstand 2000 V AC voltage for one minute.
5.4.6. The completed core and coil shall be so assembled that the axis and the plane of the outer
surface of the core assembly shall not deviate from the vertical plane by more than 25
mm.
5.4.7. All steel sections used for supporting the core shall be thoroughly shot or sand blasted,
after cutting, drilling, welding and before painting.
5.4.8. The finally assembled core with all the clamping structures shall be free
from
deformation and shall not vibrate during operation.
5.4.9. The core clamping structure shall be designed to minimize eddy current loss.
5.4.10. The framework and clamping arrangements shall be securely earthed.
5.4.11. The core shall be carefully assembled and rigidly clamped to ensure adequate mechanical
strength.
5.4.12. The design of magnetic circuit shall be such as to avoid static discharges, development of
short circuit paths within itself or to the earthed clamping structure and production of flux
component at right angle to the plane of the lamination, which may cause local heating.
The supporting framework of the cores shall be so designed as to avoid the presence of
pockets, which would prevent complete emptying of the tank through the drain valve or
cause trapping of air during filling.
5.4.13. The construction is to be of `core type. The core shall be provided with lugs suitable for
lifting the complete core and coil assembly. The core and coil assembly shall be so fixed
in the tank that shifting will not occur during transport or short circuits and the assembly
shall withstand these with ease.
5.5
INTERNAL EARTHING
5.5.1. All internal non alive metal parts of the transformer, with the exception of individual
laminations, core bolts and their individual clamping plates shall be earthed by
connecting to tank by copper strip.
5.5.2. The magnetic circuit shall be connected to the clamping structure at one point only and
this shall be brought out of the top cover of the transformer tank through a suitably rated
insulator. A disconnecting link shall be provided on transformer tank to facilitate
disconnections from ground for IR measurement purpose.
5.5.3. Coil clamping rings of metal at earth potential shall be connected to the adjacent core
clamping structure on the same side as the main earth connections.
5.6
WINDING
5.6.1.
- 10 -
5.6.2.
All low voltage windings for use in the circular coil concentric winding shall be
wound on a preformed insulating cylinder for mechanical protection of the winding
in handling and placing around the core.
5.6.3.
Winding shall not contain sharp bends which might damage the insulation or produce
high dielectric stresses. No strip conductor wound on edge shall have width
exceeding six times the thickness.
5.6.4.
Materials used in the insulation and assembly of the windings shall be insoluble, non
catalytic and chemically inactive in the hot transformer oil and shall not soften or the
otherwise affected under the operating conditions.
5.6.5.
Varnish application on coil windings may be given only for mechanical protection
and not for improvement in dielectric properties. In no case varnish or other adhesive
be used which will seal the coil and prevent evacuation of air and moisture and
impregnation by oil.
5.6.6.
5.6.7.
Permanent current carrying joints in the windings and leads shall be welded or
brazed. Clamping bolts for current carrying parts inside oil shall be made of oil
resistant material which shall not be affected by acidity in the oil steel bolts, if used,
shall be suitably treated.
5.6.8.
Terminals of all windings shall be brought out of the tank through bushings for
external connections. The leads used shall be rigidly supported and guide tubes shall
be provided where practicable.
5.6.9.
The completed core and coil assembly shall be dried in vacuum at not more than
0.5mm of mercury absolute pressure and shall be immediately impregnated with oil
after the drying process to ensure the elimination of air and moisture within the
insulation.
5.6.10.
The winding shall be so designed that all coil assemblies of identical voltage ratings
shall be interchangeable and field repairs to the winding can be made readily without
special equipment. The coils shall have high dielectric strength.
Coils shall be made of continuous smooth high grade electrolytic copper conductor,
shaped and braced to provide for expansion and contraction due to temperature
changes.
Adequate barriers shall be provided between coils and core and between high and
low voltage coil. End turns shall have additional protection against abnormal line
disturbances.
The insulation of winding shall be designed to withstand voltage stress arising from
surge in transmission lines due to atmospheric or transient conditions caused by
switching etc.
Tappings shall not be brought out from inside the coil or from intermediate turns and
shall be so arranged as to preserve as far as possible magnetic balance of the
transformer at all voltage ratios.
5.6.11.
5.6.12.
5.6.13.
5.6.14.
- 11 -
5.6.15.
5.6.16.
5.7
INSULATING OIL
5.7.1. The insulating oil shall conform to IS: 335. No inhibitors shall be used in the oil.
5.7.2. The quantity of oil required for the first filling of the transformer and its full specification
shall be stated in the bid. The transformer shall be supplied filled with oil above winding
level and rest of the oil supplied in non-returnable drums.
5.7.3. The design and materials used in the construction of the transformer shall be such as to
reduce the risk of the development of acidity in the oil.
5.7.4. The contractor shall warrant that oil furnished is in accordance with the following
specifications.
S. No
1
2
3
Characteristic
Appearance
Requirement
The oil shall be clear &
transparent & free from
suspended
matter
or
Sediment
Electric strength Break Less than 72.5 kV
Down (voltage) Min.
Water content Max:
Less than 25 ppm
Method of Test
A representative sample of oil
shall be examined in a 100
mm thick layer at ambient
temp.
IS: 6792
IS: 2362
5.8
VALVES
5.8.1. Valves shall be of forged carbon steel or Gun metal upto 50 mm. They shall be of full
way type with screwed ends and shall be opened by turning counter clockwise when
facing the hand wheel. There shall be no oil leakage when the valves are in closed
position.
5.8.2. Each valve shall be provided with an indicator to show the open and closed positions and
shall be provided with facility for padlocking in either open or closed position. All
screwed valves shall be furnished with pipe plugs for protection. Padlocks with duplicate
keys shall be supplied alongwith the valves.
5.8.3. All valves except screwed valves shall be provided with flanges having
machined
faced drilled to suit the applicable requirements. Oil tight blanking plates shall be
provided for each connection for use when any radiator is detached and for all valves
- 12 -
opening to atmosphere. If any special radiator valve tools are required, the Contractor
shall supply the same.
5.8.4. Each transformer shall be provided with following valves on the tank:
a)
b)
c)
d)
e)
Filter valves shall be suitable for applying vacuum as specified in the specifications.
5.9
ACCESSORIES
ii)
Stress due to expansion and contraction in any part of the bushing shall not lead
to deterioration or loosening of cemented joint.
iii)
The creepage distance shall be not less than 25 mm/kv and protected creepage
distance shall be not less than 50% of total.
iv)
v)
Arcing horns are to be provided with adjustable horn gap except the neutral
bushing.
vi)
vii)
Bushing shall be so located on the transformers that full flashover strength will
be utilized. Minimum clearances as required for the BIL shall be realized
between live parts and live parts and live parts to earthed structures.
viii)
All applicable routine and type tests certificates of the bushings shall be
furnished for approval.
ix)
x)
- 13 -
xi)
Each bushing shall be so coordinated with the transformer insulation that all
flashover will occur outside the tank.
(ii)
i)
Oil Conservator
(a)
The conservator shall have adequate capacity between highest and lowest visible
levels to meet the requirement of expansion of the total cold oil volume in the
transformer and cooling equipment.
(b)
The conservator shall be bolted into position so that it can be removed for
cleaning purposes.
(c)
The conservator shall be fitted with magnetic oil level gauge with low level
electrically insulated alarm contact.
(d)
It shall be provided with oil filling hole with cap on top and a drain valve at the
bottom.
(iii)
Buchholz Relay
A double float type Buchholz relay shall be provided. Any gas evolved in the
transformer shall collect in this relay. The relay shall be provided with a test cock
suitable for a flexible pipe connection for checking its operation. A copper tube shall be
connected from the gas collector to a valve located about 1200 mm above ground level to
facilitate gas sampling with the transformer in service. The device shall be provided with
two electrically independent potential free contacts, one for alarm on gas accumulation
and the other for tripping on sudden rise of pressure.
(iv)
Temperature Indicator
(a)
(b)
- 14 -
A device for measuring the hot spot temperature of the winding shall be
provided. It shall comprise the following.
i)
ii)
iii)
iv)
v)
5.9.3.
The conservator shall be fitted with a dehydrating silica gel filter breather. It shall
be so designed that,
i)
ii)
iii)
iv)
5.10
MARSHALLING BOX
i)
Sheet steel (not less than 2 mm thick), weather, vermin and dust proof
marshalling box fitted with required glands, locks, glass door, terminal Board,
water-tight hinged and padlocked door of a suitable construction shall be
provided with each transformer to accommodate temperature indicators, terminal
blocks etc. The box shall have sloping roof and the interior and exterior painting
shall be in accordance with the specification. Padlock alongwith duplicate keys
shall be supplied for marshalling box. The degree of protection shall be IP-55.
ii)
The schematic diagram of the circuitry inside the marshalling box be prepared
and fixed inside the door under a prospone sheet.
iii)
Temperature indicators
Space for accommodating Control & Protection equipment in future for
the cooling fan (for ONAF type cooling, may be provided in future))
Terminal blocks and gland plates for incoming and outgoing cables.
All the above equipment except (c) shall be mounted on panels and back of panel
wiring shall be used for inter-connection. The temperature indicators shall be so
- 15 -
mounted that the dials are not more than 1600 mm from the ground level and the
door (s) of the compartment(s) shall be provided with glazed window of adequate
size.
The transformer shall be erected on a plinth which shall be 2.5 feet above ground
level.
5.11
i)
To prevent internal condensation, a metal clad space heater with thermostat shall
be provided. The heater shall be controlled by a MCB of suitable rating mounted
in the box. An 11 W CFL shall be provided for illumination with door operated
switch.
ii)
All incoming cables shall enter the kiosk from the bottom and the gland plate
shall not be less than 450 mm from the base of the box. The gland plate and
associated compartment shall be sealed in suitable manner to prevent the ingress
of moisture.
iii)
The control connection, wiring etc. shall be as per Clause 5.13 of this
specification.
(i)
(ii)
The Transformer with off-load tap changing gear shall have taps ranging from
+5% to 10% in 6 equal steps of 2.5% each on HV winding for voltage
variation.
The tap changing switch shall be located in a convenience position at one side of
the tank so that it can be operated from ground level. The switch handle shall be
provided with locking arrangement along with a position indication.
(iii)
5.12
FITTINGS
The following fittings shall be provided on the transformers:
i)
ii)
iii)
iv)
v)
vi)
vii)
viii)
Conservator with isolating valves, oil filling hole with cap and drain valve.
Magnetic type oil level gauge (150 mm dia.) with low oil level alarm contacts.
Prismatic/toughened glass oil level gauge.
Silica gel breather with oil seal and connecting pipe complete with first fill of
activated silica gel.
A double float type Buchholz relay with isolating valve, bleeding pipe and a
testing cock. The relay shall be provided with shut off valve on the conservator
side as well as on the tank side.
Pressure relief devices (including pressure relief valve) and necessary air
equalizer connection between this and the conservator with necessary trip
contacts.
Air release plugs in the top cover.
Inspection covers, access holes with bolted covers for access and inspection of
inner ends of bushing, core/coil assembly etc.
- 16 -
ix)
x)
xi)
xii)
xiii)
xiv)
xv)
xvi)
xvii)
xviii)
xix)
xx)
xxi)
xxii)
xxiii)
xxiv)
xxv)
xxvi)
Note: (i)
(ii)
5.13
i)
Normally no fuses shall be used anywhere. Instead of fuses MCBs (both in AC & DC
circuits) shall be used. Only in cases where a MCB cannot replace a fuse due to system
requirements, a HRC fuse can be accepted.
ii)
All wiring connections, terminal boards, fuses, MCBs and links shall be suitable for
tropical atmosphere. Any wiring liable to be in contact with oil shall have oil resisting
insulation and the bare ends of stranded wire shall be sweated together to prevent seepage
of oil along the wire.
- 17 -
iii)
iv)
v)
Panel connections shall be neatly and squarely fixed to the panel. All instruments and
panel wiring shall be run in PVC. All wiring to a panel shall be taken from suitable
terminal boards.
When 400 volt connections are taken through junction boxes or marshalling boxes, they
shall be adequately screened and 400 volts Danger Notice must be affixed to the outside
of the junction boxes or marshalling box. Proper colour code for Red, Yellow, Blue
phases wires shall be followed. All circuits, in which the voltage exceeds 125 volts, shall
be kept physically separated from the remaining wiring. The function of each circuit shall
be marked on the associated terminal boards.
All box wiring shall be in accordance with relevant IS. All wiring shall be of stranded
single core copper (48 strands) of 1100 Volt grade and size as under:
CT circuits 2x2.5 sq.mm.
AC/DC Power circuit 1x2.5 sq.mm.
All other circuit - 1x2.5 sq.mm.
vi)
vii)
viii)
ix)
x)
xi)
xii)
xiii)
xiv)
xv)
xvi)
xvii)
xviii)
All wires on panels and all multi-core cables shall have ferrules, for easy identifications,
which bear the same number at both ends, as indicated in the relevant drawing.
The same ferrule number shall not be used on wires in different circuits on the same
panels.
Ferrules shall be of white insulating material and shall be provided with glossy finish to
prevent the adhesion of dirt. They shall be clearly and durably marked in black and shall
not be affected by dampness or oil.
Stranded wires shall be terminated with tinned terminals, claw washers or crimped
tubular lugs. Separate washers shall be suited to the size of the wire terminated. Wiring
shall, in general, be accommodated on the sides of the box and the wires for each circuit
shall be separately grouped. Back of panel wiring shall be arranged so that access to the
connecting items of relays and other apparatus is not impeded.
Where apparatus is mounted on panels, all metal cases shall be separately earthed by
means of stranded (48 No.) copper wire or strip having a cross section of not less than 2.5
sq. mm. Where strip is used, the joints shall be sweated.
The wiring diagram for marshalling box shall preferably be drawn as viewed from the
back and shall show the terminal boards arranged as in services.
Terminal blocks shall be 1100 volts 10 Amp grade moulded material complete with stud
type brass terminal, washers, nuts and identification strips.
Terminal block rows should be spaced adequately not less than 100 mm apart to permit
convenient access to external cables and terminations.
Terminal blocks shall be placed with respect to the cable gland (at a minimum distance of
200 mm) as to permit satisfactory arrangement of multicore cable tails.
Terminal blocks shall have separate pairs of terminals for incoming and outgoing wires.
Insulating barriers shall be provided between adjacent connections. The height of the
barriers and the spacing between terminals shall be such as to give adequate protection
while allowing easy access to terminals. The terminals shall be adequately protected with
insulating dust proof covers. No live metal shall be exposed at the back of the terminal
boards.
All interconnecting wiring, as per the final approved scheme between accessories of
transformer and marshalling box is included in the scope of this specification and shall be
done by the Transformer supplier.
The schematic diagram shall be drawn and fixed under a transparent prospane sheet on
the inner side of the marshalling box cover.
All marking of terminals shall follow IS 11953
- 18 -
5.14
6.0
(ii)
(iii)
The Contractor shall draw up and carry out a comprehensive inspection and
testing programme during manufacture of the transformer duly approved by the
purchaser.
The contractor shall carry out type tests, acceptance test and routine tests on the
transformers.
The pre-shipment checks shall also be carried out by the contractor.
(iv)
6.1
ii)
a)
b)
c)
d)
Core
a)
iii)
b)
c)
d)
e)
f)
High voltage DC test (2 kV for one minute) between core and clamps.
Insulating Material
- 19 -
iv)
a)
b)
c)
Winding
a)
b)
Visual and dimensional checks on conductor for scratches, dent mark etc.
c)
d)
e)
f)
Check and ensure that physical condition of all materials taken for
windings is satisfactory and free of dust.
g)
v)
vi)
vii)
b)
c)
d)
b)
Oil
All standard tests in accordance with IS: 335 shall be carried out on Transformer
oil sample before filling in the transformer.
(ix)
Buchholz relay
b)
- 20 -
6.2
c)
d)
e)
Bushings
f)
Marshalling box
g)
h)
i)
FACTORY TESTS
i)
All standards routine tests in accordance IS: 2026 with dielectric tests as per
latest amendments shall be carried out.
ii)
iii)
Following additional routine tests shall also be carried out on each transformer:
Magnetic Circuit Test
Each core shall be tested for 1 minute at 2000 Volt AC.
(2)
(3)
(4)
(5)
(6)
(7)
(vi)
(vii)
(viii)
(ix)
(x)
(xi)
(xii)
Load losses.
No load losses and no load current.
Absorption index i.e. insulation resistance for 15 seconds and 60 seconds
(R60/R15) and polarization index i.e. Insulation Resistance for 10 minutes and
one minute (R10 mt/R1 mt).
Induced over voltage withstand test.
Phase relation, polarity, angular displacement and phase sequence test
Separate source voltage withstand test (applied potential).
Measurement of Zero sequence impedance.
b)
The tank and oil filled radiators shall be tested for oil tightness completely filled
with air or oil of viscosity not greater than that of insulating oil conforming to IS:
335 at the ambient temperature and applying a pressure equal to the normal
pressure plus 35 KN/m2 measured at the base of the tank. The pressure shall be
maintained for a period of not less than 12 hours for oil and one hour for air and
during that time no leak shall occur.
Pressure Test
Where required by the Purchaser, one transformer tank of each size together with
its radiator, conservator vessel and other fittings shall be subjected to a pressure
corresponding to twice the normal head of oil or to the normal pressure plus 35
KN/m2 whichever is lower, measured at the base of the tank and maintained for
one hour.
c)
Vacuum Test
One transformer tank of each size shall be subjected to the vacuum pressure of
760 mm of mercury. The permanent deflection of flat plates
after the vacuum has been released shall not exceed the value specified in
C.B.I.P. Manual on Transformers (Revised 1999).
6.4
Check for proper provision of bracing to arrest the movement of core and
winding assembly inside the tank.
6.5
- 22 -
i)
Check and record condition of each package visible parts of the transformers etc
for any damage.
ii)
Check completed transformer against approved outline drawing, provision for all
fittings, finish level etc.
iii)
ii)
iii)
Test on oil samples taken from main tank top and bottom and cooling system. Samples
should be taken only after the oil has been allowed to settle for 24 hours.
Check the whole assembly for tightness, general appearance etc.
iv)
v)
Load losses
(KW)
34.0
These losses are maximum allowable and there would not be any positive
tolerance. However, the manufacturer can offer losses less than above.
- 23 -
7.2
CAPITALISATION OF LOSSES
For total cost evaluation, the capitalized cost of losses will be taken into account as per
the following:
Capitalised cost of Losses = Rs.A x WI + Rs. B x Wc
Where :
The no load loss in KW at the rated voltage and frequency and the load loss in KW at
rated voltage, rated frequency, rated output and at 75 degree centigrade shall be quoted
and these figures shall be guaranteed.
7.3
REJECTION
The Purchaser may reject any transformer if during tests or service any of the following
conditions arise:
i)
8.0
SPARE PARTS
In case the manufacturer goes out of production of spare parts, then he shall make
available the drawings of spare parts and specification of materials at no extra cost to the
Purchaser to fabricate or procure spare parts from other sources.
8.1
INSTRUCTIONS MANUAL
Eight sets of the instruction manuals shall be supplied at least four (4) weeks before the
actual dispatch of equipment. The manuals shall be in bound volumes and shall contain
all the drawings and information required for erection, operation and maintenance of the
transformer. The manuals shall include amongst others, the following particulars :
a)
b)
c)
Detailed views of the core and winding assembly, winding connections and
tapings, tap changer construction etc. These drawings are required for carrying
out overhauling operation at site.
d)
e)
f)
- 24 -
All fittings and accessories, which may not be specifically mentioned in the
specification but which are necessary for the satisfactory operation of the plant,
shall be deemed to be included in the specification and shall be furnished by the
contractor without extra charges. The equipment shall be complete in all details,
whether such details are mentioned in the specification or not, without any
financial liability to the Purchaser under any circumstances.
ii)
All deviations from this specification shall be separately listed under the requisite
schedules, in the absence of which it will be presumed that all the provisions of
the specification are complied with by the bidder.
8.3
9.0 COMMISSIONING
The equipment shall be commissioned as per CBIP manual, IS 10028 and
manufacturers recommendations.
10.0
TRANSFORMER OIL
The Transformer shall be supplied complete with first filling of oil and 10 % extra.
- 25 -
AC Distribution Board
1.1
GENERAL
This specification covers the design, engineering, manufacture, shop testing,
inspection before dispatch, packing, forwarding, transportation to site, insurance
(during transit, storage and erection), storage, erection, supervision, site testing
and commissioning of indoor AC Distribution board for catering power supply to
33kV and 11kV equipment, illumination, battery charger and other auxiliary loads
of the sub-station. Incoming power supply to the board will be provided from
63KVA, 11/0.433 kV outdoor station transformer .
1.2
STANDARDS
CONSTRUCTIONAL FEATURE
Panels shall be completely metal enclosed and shall be dust, moisture and vermin
proof and fully compartmentalized. The enclosure shall provide a degree of
protection not less than IP-52 (for indoor) in accordance with IS: 13947. It should
be free standing, floor mounting type and smooth finished, made of cold rolled
sheet steel of thickness not less than 3 mm for weight bearing members of the
panels such as base frame, front sheet and door frames, and 2.0mm for sides,
door, top and bottom portions. There shall be sufficient reinforcement to provide
level transportation and installation. Design, materials selection and workmanship
shall be such as to result in neat appearance, inside and outside with no welds
rivets or bolt head apparent from outside, with all exterior surfaces tune and
smooth. The colour of the finishing paint shall be light grey in accordance with
shade no.692 of IS: 5 or in matching colour of other existing Panels. There shall
be space heater with thermostat, illumination lamp and one 3-pin, 15 Amp. Power
point with socket in the panel. For further requirement/detail of equipment &
component to be in the part of ACDB, which are not covered here, are with
station lighting specification.
The cable entries shall be from bottom. Gland Plates and electroplated brass cable
glands shall be provided. Cable clamping arrangements shall be provided.
The board shall be mounted on a base frame made of 75x50x6 mm ISMC painted
black. It shall be grouted to the floor. The board can also be wall mounted with
suitable mounting arrangements.
Page 1 of 3
1.4
PAINTING
1.41
All sheet steel work shall be phosphated in accordance with the IS:6005 "Code of
Practice for Phosphating Iron and Steel".
1.42
Rust, scale, oil, grease, dirt and swarf shall be removed by 7 tank process.
1.43
After phosphating, thorough rinsing shall be carried out with clean water followed
by final rinsing with dilute dichromate solution and oven drying.
1.44
The phosphate coating shall be sealed with application of two coats of ready
mixed, stoved type zinc chromate primer. The first coat may be "flash dried"
while the second coat shall be stoved.
1.45
After application of the primer, two coats of finishing synthetic enamel paint shall
be applied, each coat followed by stoving. The second finishing coat shall be
applied after inspection of first coat of painting. The exterior colour of paint shall
be of a slightly different shade to enable inspection of the painting. The final coat
should present a hard glass finish.
1.46
1.47
In case the bidder proposes to follow any other established painting procedure like
electrostatic painting or powder coating, the procedure shall be submitted for
BSEB's review and approval.
1.5
TECHNICAL DETAIL
Incomer will be from 415 volt 3-phase, 4 wire, 200A MCCB of 10kA interrupting
capacity and 10 kA short time rating for 1 sec. The board shall have isolated bus
bar chamber for main bus bar at top, running throughout the length of the board
and TPN vertical busbar chambers for power supply to outgoing feeders. The bus
bar and connecting links etc. shall be of electrolytic aluminum. All nuts and bolts
shall be electro galvanized.
General feeder arrangement will be as follows but actual number of incomer and
outgoing feeder will be mentioned in BPS.
Incomer:
protection.
1no. 200 Amp TPN MCCB with Over Current and Short Circuit
Outgoing: 4No. 63 Amp. TPN MCCB and 2 Nos. 32Amp TPN MCCB of 10 kA
interrupting capacity and 10 kA short time rating for 1 sec. These will be provided
with Over Current and Short Circuit protection.
Metering module:
i)
ii)
Page 2 of 3
1.6
EARTHING
One Earth bars of Aluminium shall be provided near the base. The earth bar shall
be connected to two earth terminals. The earth terminals shall be connected to
station earth.
Page 3 of 3
ACSR CONDUCTOR
1.0
1.1
1.1.1
1.1.2
1.2
1.2.1
1.2.2
1.2.3
1.2.4
1.3
1.3.1
WORKMANSHIP
All the aluminium and steel strands shall be smooth, uniform and
free from all imperfections, such as spills and splits, die marks,
scratches, abrasions, etc., after drawing and also after stranding.
The finished conductor shall be smooth, compact, uniform and free
from all imperfections including kinks (protrusion of wires), scuff
marks, dents, pressmarks, cut marks, wire cross over, over riding,
looseness (wire being dislocated by finger/hand pressure and/or
unusual bangle noise on tapping), material inclusions, white rust,
powder formation or black spot (on account of reaction with trapped
rain water etc.), dirt, grit etc.
The steel strands shall be hot dip galvanized and shall have a
minimum zinc coating as specified in Table-I. The zinc coating shall
be smooth, continuous, of uniform thickness, free from
imperfections. The steel wire rods shall be of such quality and
purity that, when drawn to the size of the strands specified and
coated with zinc, the finished strands and the individual wires shall
be of uniform quality and have the same properties and
characteristics as required in the specification.
The steel strands shall be preformed and post formed in order to
prevent spreading of strands in the event of cutting of composite
core wire. Care shall be taken to avoid, damages to galvanization
during pre-forming and post-forming operation.
JOINTS IN WIRES
ALUMINIUM/AL-ALLOY WIRES
i.
ii.
1.3.2
STEEL WIRES
There shall be no joint of any kind in the finished wire entering into
the manufacture of the strand. There shall also be no strand joints or
strand splices in any length of the completed stranded steel core of
the conductor.
1 of 22
1.4
STRANDING
In all constructions, the successive layers shall be stranded in
opposite directions. The wires in each layer shall be evenly and
closely stranded round the underlying wire or wires. The outer most
layers of wires shall have a right hand lay. the ratio of the different
layers shall be within the limits given in Table-I.
1.5
TOLERANCES
The manufacturing tolerances in diameter of individual steel and
aluminium strand shall be as per table-I
1.6
1.6.1
MATERIALS
ALUMINIUM
The aluminium strands shall be hard drawn from electrolytic
aluminium rods of EC grade having purity not less than 99.5% and a
copper content not exceeding 0.04%. They shall have the same
properties and characteristics as prescribed in IEC: 889-latest
amendment.
1.6.2
STEEL
The steel wire
rods produced
or the electric
shall conform
composition:
S.No.
Element
% Composition
Carbon
0.50 to 0.85
Manganese
0.50 to 1.10
Phosphorous
Sulphur
Silicon
0.10 to 0.35
The Steel wire strands shall have the same properties and
characteristics as prescribed for regular strength steel wire in IEC:
888-Latest amendment.
1.6.3
ZINC
2 of 22
The zinc used for galvanizing shall be electrolytic High Grade Zinc of
99.95% purity. It shall conform to and satisfy all the requirements of
IS: 209-1979.
1.7
1.7.1
1.7.2
1.7.3
STANDARD LENGTH
The standard length of the conductor shall be 2000 meters.
Contractor shall indicate the standard length of the conductor to be
offered by them. A tolerance of + 5% on the standard length offered
by the Bidder shall be permitted. All lengths outside this limit of
tolerance shall be treated as random lengths.
Random lengths will be accepted provided no length is less than
70% of the standard length and the total quantity of such random
lengths shall not be more than 10% of the total quantity ordered.
Bidder shall also indicate the maximum single length, above the
standard length, he can manufacture in the guaranteed technical
particulars of offer. This is required for special stretches like river
crossing etc. The Owner reserves the right to place orders for the
above lengths on the same terms and conditions applicable for the
standard lengths during the pendency of the Contract.
1.8
1.8.1
TYPE TESTS
The following tests shall be conducted once on a sample/samples of
each type of conductor (ACSR) from each manufacturing facility:
i.
)
)
)
ii.
1.8.2
DC resistance test on
stranded conductor
Annexure-A
)
)
ACCEPTANCE TESTS
i.
)
)
)
ii.
3 of 22
Annexure - A
iii.
Dimensional check on
)
steel and aluminium/Al-alloy strands )
)
iv.
Annexure - A
)
v.
)
)
vi.
)
)
)
vii.
viii.
ix.
DC resistance test on
Aluminium strands
Procedure qualification
test on welded joint of
x.
Aluminium strands
IS : 398
)
)
)
)
Annexure-A
Note: All the above tests except (j) shall be carried out on aluminium
and steel strands after stranding only.
1.8.3
ROUTINE TEST
4 of 22
1.8.4
i.
ii.
iii.
iv.
)
)
ii.
iii.
Chemical analysis of
)
Aluminium used for
making Aluminium strands
)
)
)
Annexure-A
1.9
TESTING EXPENSES
1.9.1
The testing charges for the type tests specified shall be included in
the quoted unit price of conductor.
1.9.2
1.9.3
5 of 22
the sample selected from the already manufactured lot at his own
expenses. In case a fresh lot is manufactured for testing, then the
lot already manufactured shall be rejected.
1.9.4
The entire cost of testing for the acceptance and routine tests and
tests during manufacture specified herein shall be treated as
included in the quoted unit price of conductor, except for the
expenses of the inspector/Owner's representative.
1.9.5
In case of failure in any type test, if repeat type tests are required to
be conducted, then all the expenses for deputation of
Inspector/Owner's representative shall be deducted from the
contract price. Also if on receipt of the Contractor's notice of testing,
the Owner's representative does not find 'the material or testing
facilities' to be ready for testing the expenses incurred by the Owner
for re-deputation shall be deducted from contract price.
1.10
ADDITIONAL TESTS
1.10.1
The Owner reserves the right of having at his own expenses any
other test(s) of reasonable nature carried out at Contractors
premises, at site or in any other place in addition to the aforesaid
type, acceptance and routine tests to satisfy himself that the
materials comply with the Specifications.
1.10.2
The Owner also reserves the right to conduct all the tests mentioned
in this specification at his own expense on the samples drawn from
the site at Contractors premises or at any other test centre. In case
of evidence of non-compliance, it shall be binding on the part of
Contractor to prove the compliance of the items to the technical
specifications by repeat tests, or correction of deficiencies, or
replacement of defective items all without any extra cost to the
Owner.
1.11
1.11.1
The Contractor shall offer material for selection of samples for type
testing only after getting Quality Assurance Plan approved from
Owners Quality Assurance Deptt. The sample shall be
6 of 22
1.11.3
1.12
1.12.1
TEST REPORTS
Copies of type test reports shall be furnished in at least six copies
along with one original. One copy will be returned duly certified by
the Owner only after which the commercial production of the
material shall start.
1.12.2
1.12.3
1.13
INSPECTION
1.13.1
1.13.2
1.13.3
7 of 22
is waived off by the Owner in writing. In the latter case also, the
conductor shall be despatched only after satisfactory testing for all
tests specified herein have been completed.
1.13.4
1.14
TEST FACILITIES
1.14.1
ii.
iii.
1.15
PACKING
1.15.1
8 of 22
1.15.2
The drums shall be suitable for wheel mounting and for letting off the
conductor under a minimum controlled tension of the order of 5 KN.
1.15.3
1.15.4
The Contractor may offer more than one length of the conductor in a
single drum.
1.15.5
1.15.6
1.15.7
The wooden battens used for making the barrel of the conductor
shall be of segmental type. These shall be nailed to the barrel
supports with at least two nails. The battens shall be closely butted
and shall provide a round barrel with smooth external surface. The
edges of the battens shall be rounded or chamfered to avoid
damage to the conductor.
1.15.8
Barrel studs shall be used for the construction of drums. The flanges
shall be holed and the barrel supports slotted to receive them. The
barrel studs shall be threaded over a length on either end, sufficient
to accommodate washers, spindle plates and nuts for fixing flanges
at the required spacing.
1.15.9
Normally, the nuts on the studs shall stand protruded of the flanges.
All the nails used on the inner surface of the flanges and the drum
9 of 22
The inner cheek of the flanges and drum barrel surface shall be
painted with a bitumen based paint.
1.15.11
1.15.12
1.15.13
1.15.14
The nuts on the barrel studs shall be tack welded on the one side in
order to fully secure them. On the second end, a spring washer shall
be used.
1.15.15
A steel collar shall be used to secure all barrel studs. This collar
shall be located between the washers and the steal drum and
secured to the central steel plate by welding.
1.15.16
10 of 22
1.15.17
The conductor ends shall be properly sealed and secured with the
help of U-nail on the side of one of the flanges to avoid loosening of
the conductor layers during transit and handling.
1.15.18
1.16
MARKING
Each drum shall have the following information stenciled on it in
indelible ink along with other essential data :
i.
ii.
iii.
iv.
v.
vi.
vii.
viii.
ix.
x.
xi.
11 of 22
xii.
xiii.
1.17
The Owner reserves the right to verity the length of conductor after
unreeling at least Two (2) percent of the drums in a lot offered for
inspection.
STANDARDS
1.18
1.18.1
1.18.2
Sl.
Title
No.
International
Standards
1.
IS : 209-Latest
amendment
BS:3436- Latest
amendment
2.
IS : 398- Latest
amendment
Specification
for,
Aluminium
conductors
for
Overhead
Transmission Purposes
IEC:1089- Latest
amendment
1
BS:215Latest
amendment
3.
IS:398Latest
amendment
BS-215Latest
amendment
IEC:1089- Latest
Part-II
12 of 22
amendment
4.
IS : 1778- Latest
amendment
Reels and
Conductors
Bare
BS:1559- Latest
amendment
5.
IS : 1521- Latest
amendment
6.
IS : 2629- Latest
amendment
7.
IS : 2633- Latest
amendment
8.
IS : 4826- Latest
amendment
9.
IS : 6745- Latest
amendment
Methods of Determination of
Weight of Zinc Coating of Zinc
Coated Iron and Steel Articles.
BS:433Latest
amendment ISO
1460 Latest
amendment
10.
IS : 9997- Latest
amendment
11.
IS : 1841- Latest
amendment
EC Grade Aluminium
produced by rolling
12.
IS : 5484-1978
13.
Drums
13 of 22
for
Rods
wires
for
14.
15.
IS:398 (Part-IV)
Aluminium
conductor
Alloy
14 of 22
stranded
ANNEXURE-A
1
1.1.
1.2.
1.3.
15 of 22
1.4.
1.5.
1.6.
1.7.
1.8.
PROCEDURE QUALIFICATION
ALUMINIUM STRANDS
TEST
ON
WELDED
16 of 22
1.9.
1.10.
GALVANISING TEST
The test procedure shall be as specified in IEC : 888. The material shall
conform to the requirements of this Specification. The adherence of zinc
shall be checked by wrapping around a mandrel four times the diameter
of steel wire.
1.11.
1.12.
1.13.
17 of 22
18 of 22
Table-1
Details of parameters of ACSR conductor
S.N.
Parameter
Wolf
DOG
Rabbit
Weasel
Squirrel
30/2.59
6/4.72
6/3.35
6/2.59
6/2.11
7/2.59
1/1.57
1/3.35
1/2.59
1/2.11
158.10
105
52.88
31.61
20.98
194.90
118.5
61.7
36.88
24.48
Overall diameter mm
18.13
14.15
10.05
7.77
6.33
726
394
214
128
85
19 of 22
S.N.
Parameter
Wolf
DOG
Rabbit
Weasel
Squirrel
0.1871
0.2792
0.5524
0.9289
1.394
67.34
32.41
18.25
11.12
7.61
Right hand
Right hand
Right hand
Right hand
Right hand
80
75
79
79
79
19.8x10-6
19.8x10-6
19.1x10-6
19.1x10-6
19.1x10-6
10
11
12
0.89
2.78
1.43
0.89
0.63
0.85
2.64
1.36
0.85
0.60
1.650
3.265
5.49
8.237
20 of 22
S.N.
Parameter
Wolf
DOG
Rabbit
Weasel
Squirrel
Weight (kg/km)
14.24
47.30
23.82
14.24
9.45
Diameter
Nominal
4.72
3.35
2.59
2.11
ii
Maximum
4.77
3.38
2.62
2.13
iii
Minimum
4.67
3.32
2.56
2.09
13
6.92
2.7
11.58
6.92
4.60
6.57
2.57
11
6.57
4.37
Weight (kg/km)
15.10
68.75
41.09
27.27
190
250
230
210
Galvanising
ii
230
2 of one
2 of one
minute and 1 minute and 1
21 of 22
2 of one minute
and 1 of half
2 of one
minute and 1
2 of one
minute and
S.N.
Parameter
standard preece test (Nos.)
iii
Diameter
Wolf
DOG
of half
minute
Rabbit
of half minute
minute
Weasel
Squirrel
of half minute
1 of half
minute
16
16
16
16
Nominal
1.57
3.35
2.59
2.11
ii
Maximum
1.60
3.42
2.64
2.15
iii
Minimum
1.54
3.28
2.54
2.07
14
Lay Ratio
Aluminium wire
Max
Min
Max
Min
Max
Min
Max
Min
Max
Min
16
10
14
10
14
10
14
10
14
10
14
10
Steel wire
28
13
28
13
22 of 22
ACSR CONDUCTOR
1.0
1.1
1.1.1
1.1.2
1.2
1.2.1
1.2.2
1.2.3
1.2.4
1.3
1.3.1
ALUMINIUM/AL-ALLOY WIRES
i.
During stranding, no aluminium wire welds shall be made for the purpose of
achieving the required conductor length.
ii.
No joints shall be permitted in any layer of finished conductor
1.3.2
STEEL WIRES
There shall be no joint of any kind in the finished wire entering into the
manufacture of the strand. There shall also be no strand joints or strand splices in
any length of the completed stranded steel core of the conductor.
STRANDING
In all constructions, the successive layers shall be stranded in opposite directions.
The wires in each layer shall be evenly and closely stranded round the underlying
wire or wires. The outer most layers of wires shall have a right hand lay. the ratio
of the different layers shall be within the limits given in Table-I.
1.4
1.5
TOLERANCES
The manufacturing tolerances in diameter of individual steel and aluminium
strand shall be as per table-I
1 OF 17
1.6
MATERIALS
1.6.1
ALUMINIUM
The aluminium strands shall be hard drawn from electrolytic aluminium rods of
EC grade having purity not less than 99.5% and a copper content not exceeding
0.04%. They shall have the same properties and characteristics as prescribed in
IEC: 889-latest amendment.
STEEL
The steel wire strands shall be drawn from high carbon steel wire rods produced
by either the acid or the basic open-hearth process, or the electric furnace process,
or the basic oxygen process and shall conform to the following requirements as to
the chemical composition:
1.6.2
1.6.3
1.7
1.7.1
1.7.2
1.7.3
S.No.
Element
% Composition
1
Carbon
0.50 to 0.85
2
Manganese
0.50 to 1.10
3
Phosphorous
Not more than 0.035
4
Sulphur
Not more than 0.045
5
Silicon
0.10 to 0.35
The Steel wire strands shall have the same properties and characteristics as
prescribed for regular strength steel wire in IEC: 888-Latest amendment.
ZINC
The zinc used for galvanizing shall be electrolytic High Grade Zinc of 99.95%
purity. It shall conform to and satisfy all the requirements of IS: 209-1979.
STANDARD LENGTH
The standard length of the conductor shall be 2000 meters. Contractor shall
indicate the standard length of the conductor to be offered by them. A tolerance of
+ 5% on the standard length offered by the Bidder shall be permitted. All lengths
outside this limit of tolerance shall be treated as random lengths.
Random lengths will be accepted provided no length is less than 70% of the
standard length and the total quantity of such random lengths shall not be more
than 10% of the total quantity ordered.
Bidder shall also indicate the maximum single length, above the standard length,
he can manufacture in the guaranteed technical particulars of offer. This is
required for special stretches like river crossing etc. The Owner reserves the right
to place orders for the above lengths on the same terms and conditions applicable
for the standard lengths during the pendency of the Contract.
1.8
1.8.1
TYPE TESTS
The following tests shall be conducted once on a sample/samples of each type of
conductor (ACSR) from each manufacturing facility:
i.
ii.
DC resistance test on
)
)
Annexure-A
2 OF 17
stranded conductor
1.8.2
ACCEPTANCE TESTS
i.
ii.
iii.
Dimensional check on
)
steel and aluminium/Al-alloy strands )
iv.
v.
vi.
)
)
Annexure - A
)
)
)
)
Annexure - A
)
)
)
)
)
vii.
viii.
DC resistance test on
Aluminium strands
ix.
x.
IS : 398
)
)
)
Procedure qualification )
test on welded joint of
Aluminium strands
)
)
Annexure-A
Note: All the above tests except (j) shall be carried out on aluminium and steel
strands after stranding only.
1.8.3
1.8.4
ROUTINE TEST
i.
ii.
iii.
iv.
)
)
3 OF 17
)
ii.
iii.
Chemical analysis of )
Aluminium used for
making Aluminium strands
Chemical analysis of steel
used for making steel strands
)
)
)
Annexure-A
)
)
1.9
TESTING EXPENSES
1.9.1
The testing charges for the type tests specified shall be included in the quoted
unit price of conductor.
1.9.2
Contractor shall indicate the laboratories in which they propose to conduct the
type tests. They shall ensure that adequate facilities are available in the
laboratories and the tests can be completed in these laboratories within the time
schedule guaranteed by them.
1.9.3
In case of failure in any type test, the Contractor is either required to manufacture
fresh sample lot and repeat all the tests successfully once or repeat that particular
type test three times successfully on the sample selected from the already
manufactured lot at his own expenses. In case a fresh lot is manufactured for
testing, then the lot already manufactured shall be rejected.
1.9.4
The entire cost of testing for the acceptance and routine tests and tests during
manufacture specified herein shall be treated as included in the quoted unit price
of conductor, except for the expenses of the inspector/Owner's representative.
1.9.5
In case of failure in any type test, if repeat type tests are required to be conducted,
then all the expenses for deputation of Inspector/Owner's representative shall be
deducted from the contract price. Also if on receipt of the Contractor's notice of
testing, the Owner's representative does not find 'the material or testing facilities'
to be ready for testing the expenses incurred by the Owner for re-deputation shall
be deducted from contract price.
1.10
ADDITIONAL TESTS
1.10.1
The Owner reserves the right of having at his own expenses any other test(s) of
reasonable nature carried out at Contractors premises, at site or in any other place
in addition to the aforesaid type, acceptance and routine tests to satisfy himself
that the materials comply with the Specifications.
1.10.2
The Owner also reserves the right to conduct all the tests mentioned in this
specification at his own expense on the samples drawn from the site at
Contractors premises or at any other test centre. In case of evidence of noncompliance, it shall be binding on the part of Contractor to prove the compliance
of the items to the technical specifications by repeat tests, or correction of
deficiencies, or replacement of defective items all without any extra cost to the
Owner.
4 OF 17
1.11
1.11.1
The Contractor shall offer material for selection of samples for type testing only
after getting Quality Assurance Plan approved from Owners Quality Assurance
Deptt. The sample shall be manufactured strictly in accordance with the Quality
Assurance Plan approved by Owner.
1.11.2
The Contractor shall offer at least three drums for selection of sample required for
conducting all the type tests.
1.11.3
The Contractor is required to carry out all the acceptance tests successfully in
presence of Owners representative before sample selection.
1.12
1.12.1
TEST REPORTS
Copies of type test reports shall be furnished in at least six copies along with one
original. One copy will be returned duly certified by the Owner only after which
the commercial production of the material shall start.
1.12.2
Record of routine test reports shall be maintained by the Supplier at his works for
periodic inspection by the Owners representative.
1.12.3
1.13
INSPECTION
1.13.1
The Owners representative shall at all times be entitled to have access to the
works and all places of manufacture, where conductor shall be manufactured and
representative shall have full facilities for unrestricted inspection of the
Contractors works, raw materials and process of manufacture for conducting
necessary tests as detailed herein.
1.13.2
The Contractor shall keep the Owner informed in advance of the time of starting
and of the progress of manufacture of conductor in its various stages so that
arrangements can be made for inspection.
1.13.3
No material shall be dispatched from its point of manufacture before it has been
satisfactorily inspected and tested, unless the inspection is waived off by the
Owner in writing. In the latter case also, the conductor shall be despatched only
after satisfactory testing for all tests specified herein have been completed.
1.13.4
The acceptance of any quantity of material shall in no way relieve the Contractor
of any of his responsibilities for meeting all requirements of the Specification, and
shall not prevent subsequent rejection if such material is later found to be
defective.
1.14
TEST FACILITIES
1.14.1
The following additional test facilities shall be available at the Contractors works:
5 OF 17
i.
ii.
iii.
1.15
PACKING
1.15.1
The conductor shall be supplied in strong, wooden drums provided with lagging of
adequate strength, constructed to protect the conductor against any damage and
displacement during transit, storage and subsequent handling and stringing
operations in the field. The Contractor shall be responsible for any loss or damage
during transportation handling and storage due to improper packing. The drums
shall generally conform to IS:1778-Latest amendment, except as otherwise
specified hereinafter.
1.15.2
The drums shall be suitable for wheel mounting and for letting off the conductor
under a minimum controlled tension of the order of 5 KN.
1.15.3
The Contractor should submit their proposed drum drawings along with the bid.
1.15.4
The Contractor may offer more than one length of the conductor in a single drum.
1.15.5
All wooden components shall be manufactured out of seasoned soft wood free
from defects that may materially weaken the component parts of the drums.
Preservative treatment shall be applied to the entire drum with preservatives of a
quality, which is not harmful to the conductor.
1.15.6
The flanges shall be of two ply construction with 64 mm thickness with each ply
at right angles to the adjacent ply and nailed together. The nails shall be driven
from the inside face flange, punched and then clenched on the outer face. Flange
boards shall not be less than the nominal thickness by more than 2mm. There
shall not be less than 2 nails per board in each circle. Where a slot is cut in the
flange to receive the inner end of the conductor the entrance shall be in line with
the periphery of the barrel.
1.15.7
The wooden battens used for making the barrel of the conductor shall be of
segmental type. These shall be nailed to the barrel supports with at least two nails.
The battens shall be closely butted and shall provide a round barrel with smooth
external surface. The edges of the battens shall be rounded or chamfered to avoid
damage to the conductor.
6 OF 17
1.15.8
Barrel studs shall be used for the construction of drums. The flanges shall be holed
and the barrel supports slotted to receive them. The barrel studs shall be threaded
over a length on either end, sufficient to accommodate washers, spindle plates and
nuts for fixing flanges at the required spacing.
1.15.9
Normally, the nuts on the studs shall stand protruded of the flanges. All the nails
used on the inner surface of the flanges and the drum barrel shall be counter sunk.
The ends of barrel shall generally be flushed with the top of the nuts.
1.15.10
The inner cheek of the flanges and drum barrel surface shall be painted with a
bitumen based paint.
1.15.11
1.15.12
1.15.13
Each batten shall be securely nailed across grains as far as possible to the flange,
edges with at least 2 nails per end. The length of the nails shall not be less than
twice the thickness of the battens. The nails shall not protrude above the general
surface and shall not have exposed sharp, edges or allow the battens to be released
due to corrosion.
1.15.14
The nuts on the barrel studs shall be tack welded on the one side in order to fully
secure them. On the second end, a spring washer shall be used.
1.15.15
A steel collar shall be used to secure all barrel studs. This collar shall be located
between the washers and the steal drum and secured to the central steel plate by
welding.
1.15.16
Outside the protective lagging, there shall be minimum of two binder consisting of
hoop iron/ galvanised steel wire. Each protective lagging shall have two recesses
to accommodate the binders.
1.15.17
The conductor ends shall be properly sealed and secured with the help of U-nail
on the side of one of the flanges to avoid loosening of the conductor layers during
transit and handling.
1.15.18
7 OF 17
1.16
MARKING
Each drum shall have the following information stenciled on it in indelible ink
along with other essential data :
i.
ii.
iii.
iv.
v.
vi.
vii.
viii.
ix.
x.
xi.
xii.
xiii.
1.17
1.18
STANDARDS
1.18.1
1.18.2
8 OF 17
Sl.
No.
1.
Indian Standard
Title
International
Standards
BS:3436- Latest
amendment
IS
:
209-Latest
amendment
2.
IS : 398amendment
Latest
Specification
for,
Aluminium
conductors for Overhead Transmission
Purposes
IEC:1089- Latest
amendment
1
BS:215Latest
amendment
3.
IS:398amendment
Part-II
Latest
BS-215Latest
amendment
IEC:1089- Latest
amendment
4.
IS : 1778- Latest
amendment
BS:1559- Latest
amendment
5.
IS : 1521amendment
IS : 2629amendment
IS : 2633amendment
IS : 4826amendment
Latest
Latest
6.
7.
8.
Latest
Latest
9.
IS : 6745- Latest
amendment
10.
IS : 9997- Latest
amendment
IS : 1841- Latest
amendment
IS : 5484-1978
11.
12.
IEC : 888amendment
BS:443amendment
BS:433amendment
1460
amendment
IEC 104amendment
Latest
Latest
Latest
ISO
Latest
Latest
13.
14.
wire
9 OF 17
for
15.
IS:398 (Part-IV)
10 OF 17
ANNEXURE-A
1
1.1.
1.2.
1.3.
1.4.
1.5.
1.6.
1.7.
11 OF 17
The lay-ratios of various layers shall be checked to ensure that they conform to the
requirements of this Specification.
1.8.
1.9.
1.10.
GALVANISING TEST
The test procedure shall be as specified in IEC : 888. The material shall conform to the
requirements of this Specification. The adherence of zinc shall be checked by wrapping
around a mandrel four times the diameter of steel wire.
1.11.
1.12.
1.13.
1.14.
12 OF 17
13 OF 17
SECTION 3, CHAPTER 16
ACSR Conductor
S.N
.
Parameter
Table-1
Details of parameters of ACSR conductor
DOG
Raccon
Rabbit
Weasel
Squirrel
6/4.72
6/4.09
6/3.35
6/2.59
6/2.11
7/1.57
1/4.09
1/3.35
1/2.59
1/2.11
105
78.83
52.88
31.61
20.98
118.5
91.97
61.7
36.88
24.48
Overall diameter mm
14.15
12.27
10.05
7.77
6.33
394
319
214
128
85
14 OF 17
SECTION 3, CHAPTER 16
ACSR Conductor
S.N
.
Parameter
DOG
Raccon
Rabbit
Weasel
Squirrel
0.2792
0.3712
0.5524
0.9289
1.394
32.41
26.91
18.25
11.12
7.61
Right hand
Right hand
Right hand
Right hand
Right hand
75
79
79
79
79
19.8x10-6
19.1x10-6
19.1x10-6
19.1x10-6
19.1x10-6
10
11
12
2.78
2.08
1.43
0.89
0.63
2.64
1.98
1.36
0.85
0.60
1.650
2.194
3.265
5.49
8.237
Weight (kg/km)
47.30
35.51
23.82
14.24
9.45
15 OF 17
SECTION 3, CHAPTER 16
ACSR Conductor
S.N
.
Parameter
DOG
Raccon
Rabbit
Weasel
Squirrel
Diameter
Nominal
4.72
4.09
3.35
2.59
2.11
ii
Maximum
4.77
4.13
3.38
2.62
2.13
iii
Minimum
4.67
4.05
3.32
2.56
2.09
13
2.7
17.27
11.58
6.92
4.60
2.57
16.4
11
6.57
4.37
Weight (kg/km)
15.10
102.48
68.75
41.09
27.27
275
250
230
210
Galvanising
190
ii
2 of one minute
and 1 of half
minute
2 of one minute
and 1 of half
minute
16 OF 17
2 of one minute
and 1 of half
minute
2 of one
minute and 1
of half
minute
SECTION 3, CHAPTER 16
ACSR Conductor
S.N
.
Parameter
DOG
Raccon
Rabbit
Weasel
Squirrel
iii
16
16
16
16
16
Nominal
1.57
4.09
3.35
2.59
2.11
ii
Maximum
1.60
4.17
3.42
2.64
2.15
iii
Minimum
1.54
4.01
3.28
2.54
2.07
14
Lay Ratio
Aluminium wire
Steel wire
Max
14
28
Min
10
13
Max
14
-
17 OF 17
Min
10
-
Max
14
-
Min
10
-
Max
14
-
Min
10
-
Max
14
-
Min
10
-
1.1
1.2
The contractor shall submit the drawings and get the owners approval before
proceeding.
2.0
STANDARDS
Except where modified by this specification, battery and battery charger and the
equipment mounted therein shall be designed, manufactured and tested in accordance
with latest editions of the following standards.
IEC:896
IS:1652
IEC:76
IEC:146
IEC:529
IEC:255
IEC: 337
IEC: 227
IEC:947-1
IS:2026
IS:3136
IS:13947
IS:3231
IS:8686
IS:6875
IS:1554
IS:13947-1
IEC:947-2
IEC:947-3
IEC:947-4
IEC:439
IS: 13947-2
IS: 13947-3
IS: 13947-4
IS:8623
IS:1901
IS:13703
IS:1300
IS:11353
IEC:269
IEC:800
IS:3043
IS:6005
3.0
DC SUPPLY SYSTEM
The proposed 30 volt DC supply system shall consist of the battery and battery charger.
The battery charger, battery and load shall be normally connected in parallel and work
as a system.
Under parallel operating conditions, the battery shall float between the charger and load
with the transformer-cum-rectifier unit of the float charger supplying the required DC
load as well as maintaining the battery in fully charged condition. The battery shall act
as a back up source of power or contributing to total current during load peaks if it
exceeds the rated output of the transformer-cum-rectifier unit. Should the charger fail
due to loss of its AC supply or for other reasons, the battery shall immediately take
over feeding the load and shall continue to do so until the charger has been restored to
Page 1 of 10
service. Thus the charger and battery shall supply the load current either separately or
simultaneously as circumstances dictate.
In the event of battery being discharged, the boost charger shall be capable of recharging it at the ten hours rate. On completion of re-charge operation, the charger shall
revert to float charging. The charger shall have the additional facility of being able to
boost charge the battery at a constant voltage above that of the float charge level, under
manual supervision. The change from float charge operation to boost charging and vice
versa shall be effected by means of a float/boost charge selection switch.
Automatic charging of the battery shall be carried out in accordance with the (IU)
characteristic. The battery shall be charged with a constant current the magnitude of
which shall be the maximum output rating of the charger less the current being drawn
by the load (I characteristics). As soon as the battery terminal voltage rises to the float
voltage the charger shall switch to constant voltage operation (U characteristics). Boost
charging of a battery shall also be carried out in accordance with the (U) characteristics.
The facility to boost charge shall enable the constant voltage, at which the change from
I to U characteristic takes place, to be set at a higher level than the float charge voltage.
The setting of the constant current portion of the characteristic shall be adjustable at
least over the range of fifty percent of the rated output current to maximum rating of the
chargers. The constant voltage portions of the characteristics shall be pre-set at 2.30
volt per cell for the trickle charging. For boost charging the characteristics of the
constant voltage portion shall be pre set at 2.70 volt per cell. The settings shall be
adjustable.
4.0
BATTERY
4.1
The 30V DC Batteries shall be stationary Lead-Acid type consisting of 15 cells with
tubular positive plates. Tubular type batteries shall be Normal Discharge type. These
Batteries shall be suitable for a long life under continuous float operations at 2.15 to
2.25 volts per cell, and occasional discharges. The capacity shall be 100 Ampere Hours
at 10 hour discharge rate. The 30 V DC system is - ve earth system.
4.2
Cell Terminals: All cell terminals shall have adequate current carrying capacity and
shall be of lead alloy or lead alloy reinforced with copper core inserts. Cell terminal
posts shall be equipped with connection bolts having acid resisting bolts and nuts.
4.3
Container: Containers shall be made of glass or hard rubber or suitable plastic material
or glass fibre reinforced plastics or lead lined wood. Containers shall be robust, heat
resistant, leak proof, non-absorbent, acid resistant and free from flaws. Glass containers
shall be transparent. Electrolyte level lines shall be marked on container in case of
transparent containers. Float type level indicator shall be provided in case of opaque
containers. The marking for the electrolyte level should be for the upper, normal and
lower limits. The material of level indicator shall be acid-proof and oxidation proof.
4.4
Vent Plugs: Vent plugs shall be provided in cells. They shall be of anti-splash type,
having more than one exit hole and shall allow the gases to escape freely but shall
prevent acid from coming out. Suitable arrestors shall be provided to prevent spilling of
electrolyte.
4.5
Plates : The plates shall be designed for maximum durability during all service
conditions including high rate of discharge and rapid fluctuations of load. The
construction of plates shall conform to latest revisions of IS : 1651 or IS:1652 as
Page 2 of 10
Sediment Space: Sufficient sediment space shall be provided so that cells will not have
to be cleaned out during normal life.
4.7
Cell Insulator: Each cell shall be separately supported on porcelain or hard rubber
insulators fixed on to the racks with adequate clearance between adjacent cells.
4.8
Electrolyte: The electrolyte shall be prepared from battery grade sulphuric acid
conforming to IS:226 and distilled water conforming to IS:1069. The cells shall be
shipped dry and uncharged. The electrolyte for initial filling shall be furnished
separately. A minimum of 10% extra electrolyte shall be supplied after completion of
initial charging.
4.9
4.10
Serial Number
4.11
Battery Racks
Battery cells are to be mounted on Teak wood racks to be supplied by the contractor. It
should be made of straight grain hardwood, free from knots. It should be painted with
Page 3 of 10
acid proof paint. Racks shall have free access to the floor beneath making cleaning
possible. There shall be three rows of five cells each.
5.0
TESTS
5.1
Batteries shall conform to all type tests as per the latest issue of IS: 1651 or IS: 1652
(whichever is applicable depending on type of Battery being offered).
5.2
All Acceptance tests as required by the relevant Indian Standards shall be carried out at
site after completion of installation. The capacity tests shall be carried out for 10 hr.
discharge rating. The Contractor shall arrange for all necessary equipment, including
the variable resistor, tools, tackles and instruments. If a Battery fails to meet the
guaranteed requirements the OWNER shall have the option of asking the contractor to
replace the same with appropriate batteries at no extra cost and without affecting the
commissioning schedule of the employer.
5.3
If successful Contractor has not manufactured & commissioned the specified cell size,
they must manufacture & test the prototype in advance and obtain Employers approval
for the same.
5.4
Following type tests shall be carried out on each type of cells in the presence of
Employers representative, if desired by the OWNER:
i. Capacity tests
ii. Watt hour and AH efficiency tests
6.0
ACCESSORIES
6.1
The following information shall be given on the instruction cards supplied with the
Battery:
6.2
a)
Manufacturers instruction for filling and initial charging of the Battery together
with starting and finishing charging rate.
b)
Maintenance instructions.
c)
d)
A complete Set of all the accessories and devices for maintenance of Batteries shall
be supplied along with each set of battery bank, as under:.
i)
ii)
iii)
2 Nos. of Hydrometers.
2 sets of Hydrometer syringes suitable for the vent holes in different cells.
2 Nos. of thermometers for measuring electrolyte temperature.
iv)
Page 4 of 10
v)
2 Nos. of Wall mounting type holders made of teak wood for hydrometer and
thermometer.
vi)
7.0
ix)
1 Set of spanners
x)
BATTERY CHARGER
The Battery Chargers as well as the automatic regulators shall be of static type. The
battery charger shall be capable of continuous operation at the rated load in float
charging mode. The chargers shall also be capable of Boost charging the associated
DC Battery at the desired rate.
7.1
The Battery Charger shall be provided with facility for both automatic and manual
control of output voltage and current. A selector switch shall be provided for selecting
the mode of output voltage/current control, whether automatic or manual. When on
automatic control mode during Float charging, the Charger output voltage shall remain
within +1% of the set value, for AC input voltage variation of +10%, frequency
variation of +5%, a combined voltage and frequency variation of +10%, and a DC load
variation from zero to full load.
7.2
The battery charger shall have constant voltage characteristics throughout the range
(from zero to full load) at the floating value of the voltage so as to keep the battery
fully charged but without harmful overcharge.
7.3
The charger shall have load limiters having drooping characteristic, which shall cause,
when the voltage control is in automatic mode, a gradual lowering of the output
voltage when the DC load current exceeds the Load limiter setting of the Charger.
The Load-limiter characteristics shall be such that any sustained overload or short
circuit in DC System shall not damage the Charger, nor shall it cause blowing of any
of the Charger fuses. The Charger shall not trip on overload or external short circuit.
7.4
Uniform and step less adjustments of voltage setting (in both manual and automatic
modes) shall be provided on the front of the Charger panel covering the entire float
charging output range specified. Stepless adjustments of the Load-limiter setting shall
also be possible from 80% to 100% of the rated output current for Charging mode.
7.5
It shall be possible to adjust the Boost charging current continuously over a range of 50
to 100% of the rated output current for Boost charging mode.
7.6
Page 5 of 10
7.7
The Charger manufacturer may offer an arrangement in which the voltage setting
device for Float charging mode is also used as output voltage limit setting device for
Boost charging mode and the Load-limiter of Float charging mode is used as current
setting device in boost charging mode.
7.8
Suitable filter circuits shall be provided in all the chargers to limit the ripple content
(Peak to Peak) in the output voltage to 1%, irrespective of the DC load level, when
they are not connected to a Battery.
7.9
The continuous rating of the charger shall be 20 Amps but the contractor shall compute
the total load and if it is necessary, supply charger of higher rating.
8.0
MCCB
The Battery Charger shall have 1 No. MCCB on the input side to receive cables from
one source. It shall be of P2 duty and suitable for continuous duty. MCCBs should have
auxiliary contacts for annunciation/hooter on input AC supply failure..
Rectifier Assembly
The rectifier assembly complying with IS:3136 shall be fully controlled bridge type and
shall be designed to meet the duty as required by the respective Charger. The rectifier
shall be provided with heat sink having their own heat dissipation arrangements with
natural air-cooling. Necessary surge protection devices and rectifier type fast acting
HRC fuses shall be provided in each arm of the rectifier connections.
10.0
INSTRUMENTS
One AC voltmeter and one AC ammeter alongwith selector switches shall be provided
for all chargers. One DC voltmeter and DC ammeter (with shunt) shall be provided for
all Chargers. The instruments shall be flush type, dust proof and moisture resistant.
The instruments shall have easily accessible means for zero adjustment. The
instruments shall be of 1.5 accuracy classes complying with IS:1248.
11.0
Page 6 of 10
switches shall be suitable for their continuous load. Alternatively, MCCBs of suitable
ratings shall also acceptable in place of Air Break Switch.
12.0 FUSES
All fuses shall be HRC cartridge type. Fuses shall be mounted on mounted material fuse
carriers, which are in turn mounted on fuse bases. The Contractor depending on the
circuit requirement shall choose fuse rating. All fuses in the chargers shall be monitored.
Fuse failure annunciation shall be provided on the failure of any fuse.
13.0 BLOCKING DIODE
Blocking diode shall be provided in the positive pole of the output circuit of each
charger to prevent current flow from the DC Battery into the Charger.
14.0 ANNUNCIATION SYSTEM
Audio-visual indications through bright LEDs shall be provided in all Chargers for the
following abnormalities:
a) AC power failure
b) Rectifier/chargers fuse blown.
c) Over voltage across the battery when boost charging.
d) Abnormal voltage (High/Low)
e) Earth leakage
f) Any other annunciation if required.
Potential free NO Contacts of above abnormal conditions shall also be provided for
common remote indication CHARGER TROUBLE in Employers Control Board.
Indication for charger in float mode and boost mode through indication lamps shall be
provided for chargers. A potential free contact for float/boost mode shall be provided
for external interlocks.
15.0
Page 7 of 10
properly earthed. The degree of protection of Charger enclosure shall be at least IP-42
as per IS: 13947.
16.1 All indicating instruments, control switches and indicating lamps shall be mounted on
the front side of the Charger.
16.2
Each Charger shall be furnished completely wired upto power cable lugs and terminal
blocks and ready for external connections. The control wiring shall be carried out with
PVC insulated, 1.5 sq.mm. stranded copper wires. Control terminals shall be suitable
for connecting two wires, with 2.5 sq.mm stranded copper conductors. All terminals
shall be numbered for ease of connections and identification. Each wire shall bear a
ferrule or tag on each end for identification. At least 20% spare terminals shall be
provided for control circuits.
16.3
The insulation of all circuits, except the low voltage electronic circuits shall withstand
test voltage of 2 KV AC for one minute. An air clearance of at least ten (10) mm shall
be maintained throughout for such circuits, right up to the terminal lugs. Whenever this
clearance is not available, the live parts shall be insulated or shrouded.
17.0
PAINTING
All sheet steel work shall be pretreated, in 7 tanks process, in accordance with IS: 6005.
Degreasing shall be done by alkaline cleaning. Rust and scale shall be removed by
pickling with acid. After pickling, the parts shall be washed in running water. Then
these shall be rinsed in slightly alkaline hot water and dried. The phosphate coating
shall be `Class-C as specified in IS:6005. Welding shall not be done after
phosphating. The phosphated surfaces shall be rinsed and passivated prior to
application of stoved zinc chromate primer coating. After primer application, two coats
of finishing synthetic enamel paint of shade-692 (smoke grey) of IS:5 shall be applied,
unless required otherwise by the Employer. The inside of the chargers shall be glossy
white. Each coat of finishing synthetic enamel paint shall be properly stoved. The
paint thickness shall not be less than fifty (50) microns.
18.0
TESTS
18.1
Battery chargers including the components shall conform to all type tests as per
relevant Indian Standard. Performance test on the Chargers as per Specification shall
also be carried out on each Charger as per specification. Rectifier transformer shall
conform to all type tests specified in IS: 4540 and short circuit test as per IS: 2026.
Following type tests shall be carried out for compliance of specification requirements:
i)
ii)
iii)
iv)
v)
vi)
Page 8 of 10
18.2 The Contractor may be required to demonstrate to the Owner that the Chargers conform
to the specification particularly regarding continuous rating, ripple free output, voltage
regulation and load limiting characteristic, before dispatch as well as after installation
at site. At site the following tests shall be carried out:
i)
ii)
18.3
If a Charger fails to meet the specified requirements, the Contractor shall replace the
same with appropriate Charger without affecting the commissioning schedule of the
Sub-station, and without any extra cost to the owner.
18.4
The Contractor shall present for inspection, the type and routine test certificates for the
following components whenever required by the OWNER.
(i)
(ii)
(iii)
(iv)
(v)
(vi)
(vii)
(viii)
(ix)
(x)
(xi)
(xii)
Switches.
Relays/MCCBs
Instruments.
DC fuses.
SCR.
Diodes.
Condensers.
Potentiometers.
Semiconductor
Annunciator.
Control wiring
Push buttons for contactors.
Outgoing: 6 no. outgoing feeders points with HRC Cartridge Fuse of suitable rating
Page 9 of 10
Metering module: The Metring module shall consist of voltmeter (1 no.), Ammeter (1
no), indication lamps (1no) for supply indication. They are to be mounted in-comer
panel.
The size of the bus and rating of fuses/MCCB shall be proposed by the contractor for
owners approval during detailed engineering.
20.0 EARTHING
Two earthing terminals shall be provided complete with nuts and washers near the base
for connecting to station earthing system by 30x6 mm GI flats.
Page 10 of 10
Page 1 of 1
Simplex Panel
The Control and Relay Panel Boards shall consist of Simplex panel, vertical independent, floor mounted
with equipment mounted on front and having wiring access from rear. In case of panel having width
more than 800mm, double leaf-doors shall be provided. Doors shall have handles with built-in locking
facility.
2.1
CONSTRUCTIONAL FEATURES
2.1.1
It is the responsibility of the Contractor to ensure that the equipment specified and such unspecified
complementary equipment required for completeness of the protective/control schemes be properly
accommodated in the panels without congestion. However, the width of panels that are being offered to
be placed in existing switchyard control rooms, should be in conformity with the space availability in
the control room.
2.1.2
Panels shall be completely sheet metal clad and shall be dust, moisture and vermin proof. The enclosure
shall provide a degree of protection not less than IP-4X in accordance with IS: 13947.
2.1.3
Panels shall be free standing, floor mounting type and shall comprise structural frames completely
enclosed with specially selected smooth finished, cold rolled sheet steel of thickness not less than 3 mm
for weight bearing members of the panels such as base frame, front sheet and door frames, and 2.0mm
for sides, door, top and bottom portions. There shall be sufficient reinforcement to provide level
transportation and installation.
2.4
All doors, removable covers and panels shall be gasketed all around with neoprene gaskets. Ventilating
louvers to be if provided shall have screens and filters. The screens shall be made of either brass or GI
wire mesh.
2.5
Design, materials selection and workmanship shall be such as to result in neat appearance, inside and
outside with no welds, rivets or bolt head apparent from outside, with all exterior surfaces tune and
smooth.
2.6
Panels shall have base frame with smooth bearing surface, which shall be fixed on the embedded
foundation channels/insert plates. Anti vibration strips made of shock absorbing materials that shall be
supplied by the contractor, shall be placed between panel and base frame.
2.7
Cable entries to the panels shall be from the bottom. Cable gland plate fitted on the bottom of the panel
shall be connected to earthing of the panel/station through a flexible braided copper conductor rigidly.
The gland shall confirm to IS 12943.
3.0
MOUNTING
3.1
All equipment on and in panels shall be mounted and completely wired to the terminal blocks ready for
external connections. The equipment on front of panel shall be mounted flush. No equipment shall be
mounted on the doors.
3.2
Equipment shall be mounted such that removal and replacement can be accomplished individually
without interruption of service to adjacent devices and are readily accessible without use of special tools.
Terminal marking on the equipment shall be clearly visible.
3.3
Contractor shall carry out cut out, mounting and wiring of the items supplied by others, which are to be
mounted in his panel in accordance with the corresponding equipment manufacturer's drawings. Cut
outs if any, provided for future mounting of equipment shall be properly blanked off with blanking plate.
3.4
The centre lines of switches, push buttons and indicating lamps shall be not less than 750mm from the
bottom of the panel. The centre lines of relays, meters and recorders shall be not less than 450mm from
the bottom of the panel
3.5
The centre lines of switches, push buttons and indicating lamps shall be matched to give a neat and
uniform appearance. Like wise the top lines of all meters, relays and recorders etc. shall be matched.
Page 1 of 10
4.0
4.1
Panels shall be supplied complete with interconnecting wiring provided between all electrical devices
mounted and wired in the panels and between the devices and terminal blocks for the devices to be
connected to equipment outside the panels. When panels are arranged to be located adjacent to each
other all inter panel wiring and connections between the panels shall be furnished and the wiring shall be
carried out internally
4.2
All wiring shall be carried out with 1100V grade, single core, stranded FRLS tinned copper conductor
wires with PVC insulation conforming to IS 1554. The minimum size of the multi-stranded copper
conductor used for internal wiring shall be as follows:
All circuits except current transformer circuits and voltage transformer circuits meant for
energy metering and AC & DC power circuit- one no 2.5 sq. mm. per lead.
All current transformer circuits two nos. 2.5 sq. mm. per lead.
Voltage transformer circuit (for energy meters): Two 2.5 sq.mm. per lead.
4.3
All internal wiring shall be securely supported, neatly arranged, readily accessible and connected to
equipment terminals and terminal blocks. Wiring gutters and troughs shall be used for this purpose.
4.4
Auxiliary bus wiring for AC and DC supplies, voltage transformer circuits, annunciation circuits and other
common services shall be provided near the top of the panels running throughout the entire length of the
panels.
4.5
Wire termination shall be made with solderless crimping type and tinned copper lugs, which firmly grip
the conductor. Insulated sleeves shall be provided at all the wire terminations. Engraved core
identification plastic ferrules marked to correspond with panel wiring diagram shall be fitted at both ends
of each wire. Ferrules shall fit tightly on the wire and shall not fall off when the wire is disconnected from
terminal blocks. All wires directly connected to trip circuit of breaker or device shall be distinguished by
the addition of red coloured unlettered ferrule.
4.6
Longitudinal troughs extending throughout the full length of the panel shall be preferred for inter panel
wiring. Inter-connections to adjacent panel shall be brought out to a separate set of terminal blocks located
near the slots of holes meant for taking the inter-connecting wires.
4.7
Contractor shall be solely responsible for the completeness and correctness of the internal wiring and for
the proper functioning of the connected equipments
5.0
TERMINAL BLOCKS
5.1
All internal wiring to be connected to external equipment shall terminate on terminal blocks. Terminal
blocks shall be 1100 V grade and have 10 Amps continuous rating, moulded piece, complete with
insulated barriers, stud type brass terminals, washers, nuts, lock nuts and identification strips. Markings
on the terminal blocks shall be on marking strips and shall correspond to wire number and terminal
numbers on the wiring diagrams. All terminal blocks shall have shrouding with transparent unbreakable
material. All Marking shall confirm to IS 11353.
5.2
Disconnecting type terminal blocks for voltage transformer secondary leads shall be provided. Current
transformer secondary leads shall be provided with short circuiting and earthing facilities. These leads
should have testing facilities.
5.3
At least 20% spare terminals shall be provided on each panel and these spare terminals shall be
uniformly distributed on all terminal blocks.
5.4
Unless otherwise specified, terminal blocks shall be suitable for connecting the following conductors of
external cable on each side
All CT & PT circuits: minimum of two of 2.5mm Sq. copper.
AC/DC Power Supply Circuits: One of 4mm Sq. Copper.
All other circuits: minimum of one of 2.5mm Sq. Copper.
5.5
There shall be a minimum clearance of 250mm between the first row of terminal blocks and the
associated cable gland plate or panel side wall. Also the clearance between two rows of terminal blocks
edges shall be minimum of 150mm.
Page 2 of 10
5.6
Arrangement of the terminal block assemblies and the wiring channel within the enclosure shall be such
that a row of terminal blocks is run in parallel and close proximity along each side of the wiring-duct to
provide for convenient attachment of internal panel wiring. The side of the terminal block opposite the
wiring duct shall be reserved for the external cable connections. All adjacent terminal blocks shall also
share this field wiring corridor. All wiring shall be provided with adequate support inside the panels to
hold them firmly and to enable free and flexible termination without causing strain on terminals.
5.7
All necessary cable terminating accessories such as gland plates, supporting clamps & brackets, wiring
troughs and gutters etc. for external cables shall be included in the scope of supply.
6.0
PAINTING
6.1
All sheet steel work shall be phosphated in accordance with the IS:6005
Phosphating Iron and Steel".
6.2
Rust, scale, oil, grease, dirt and swarf shall be removed by 7 tank process.
6.3
After phosphating, thorough rinsing shall be carried out with clean water
with dilute dichromate solution and oven drying.
6.4
The phosphate coating shall be sealed with application of two coats of ready mixed, stoved type zinc
chromate primer. The first coat may be "flash dried" while the second coat shall be stoved.
6.5
After application of the primer, two coats of finishing synthetic enamel paint shall be applied, each coat
followed by stoving. The second finishing coat shall be applied after inspection of first coat of painting.
The exterior colour of paint shall be of a slightly different shade to enable inspection of the painting.
The final coat should present a hard glass finish.
6.6
A small quantity of finished paint shall be supplied for minor touching up required at site after
installation of the panels.
6.7
In case the bidder proposes to follow any other established painting procedure like electrostatic painting
or powder coating, the procedure shall be submitted for 's review and approval.
7.0
MIMIC DIAGRAM
7.1
Coloured mimic diagram and symbols showing the exact representation of the system shall be provided
in the front of control panels.
7.2
Mimic diagram shall be made preferably of anodised aluminium or plastic of approved fast colour
material, which shall be screwed on to the panel and can be easily cleaned. Painted overlaid mimic is
also acceptable. The mimic bus shall be 2 mm thick. The width of the mimic bus shall be 10mm for
bus bars and 7 mm for other connections.
7.3
Mimic bus colour will be decided by the BSPHCLand shall be furnished to the successful Bidder during
Engineering.
7.4
When semaphore indicators are used for equipment position they shall be so mounted in the mimic that
the equipment close position shall complete the continuity of mimic.
7.5
Indicating lamp, one for each phase, for each bus shall be provided on the mimic to indicate bus charged
condition.
Page 3 of 10
8.0
8.1
All equipment mounted on front and rear side as well as equipment mounted inside the panels shall be
provided with individual name plates with equipment designation engraved. Also on the top of each
panel on front as well as rear side, large and bold name plates shall be provided for circuit/feeder
designation.
8.2
All front mounted equipment shall also be provided at the rear with individual name plates engraved
with tag numbers corresponding to the one shown in the panel internal wiring to facilitate easy tracing of
the wiring.
8.3
Each instrument and meter shall be prominently marked with the quantity measured e.g. KVA, MW, etc.
All relays and other devices shall be clearly marked with manufacturer's name, manufacturer's type,
serial number and electrical rating data.
8.4
Name Plates shall be made of non-rusting metal or 3 ply lamicoid. Nameplates shall be black with
white engraving lettering.
8.5
All the panels shall be provided with nameplate mounted inside the panel bearing LOA No & Date,
Name of the Substation & feeder and reference drawing number.
9.0
MISCELLANEOUS ACCESSORIES
9.1
Plug Point:
A 240V, Single phase 50Hz, 15Amp AC socket with 15 Amps standard Indian plug, shall be provided in
the interior of each cubicle with ON-OFF switch.
9.2
Interior Lighting:
Each panel shall be provided with a 20 W fluorescent lighting fixture rated for 240 Volts, single phase,
50 Hz supply for the interior illumination of the panel controlled by the respective panel door switch.
9.3
9.4
Space Heater:
Each panel shall be provided with a space heater rated for 240V, single phase, 50 Hz AC supply for the
internal heating of the panel to prevent condensation of moisture. The heater shall be complete with
thermostat controlled and a switch unit.
10.0
EARTHING
10.1
All panels shall be equipped with an earth bus securely fixed. The material and the sizes of the bus bar
shall be at least 25 X 6 sq.mm perforated copper strip with threaded holes at a gap of 50mm with a
provision of bolts and nuts for connection with cable armours and mounted equipment etc for effective
earthing suitable connectors for this purpose shall be provided. When several panels are mounted
adjoining each other, the earth bus shall be made continuous and necessary connectors and clamps for
this purpose shall be included in the scope of supply of Contractor. Provision shall be made for
extending the earth bus bars to future adjoining panels on either side.
10.2
All metallic cases of relays, instruments and other panel mounted equipment including gland plate, shall
be connected to the earth bus by copper wires of size not less than 2.5 sq. mm. The colour code of
earthing wires shall be green.
Page 4 of 10
10.3
Looping of earth connections which would result in loss of earth connection to other devices when the
loop is broken, shall not be permitted. However, looping of earth connections between equipment to
provide alternative paths to earth bus shall be provided.
10.4
VT and CT secondary neutral or common lead shall be earthed at one place only at the terminal blocks
where they enter the panel. Such earthing shall be made through links so that earthing may be removed
from one group without disturbing continuity of earthing system for other groups.
10.5
The earth bar shall be terminated into two earthling terminals of adequate size with nuts and washer for
connecting to the station earthing sytem.
11.0
INDICATING INSTRUMENTS
All instruments and meters shall be enclosed in dust proof, moisture resistant, black finished cases and
shall be suitable for tropical use. Frequency meters shall be provided with individual transducers and
these shall be calibrated along with transducers to read directly the primary quantities. They shall be
accurately adjusted and calibrated at works and shall have means of calibration check and adjustment at
site.
11.1.1
Unless otherwise specified, all electrical indicating instruments shall have circular 240 degree scale and
with a dial of 96mm x 96mm. They shall be suitable for flush mounting.
11.1.2
Instruments dial shall be with white circular scale and black pointer and with black numerals and
lettering. The dial shall be free from warping, fading, and decolouring. The dial shall also be free from
parallax error.
11.1.1.3
Instruments shall conform to IS:1248 and shall have accuracy class of 1.0 or better. The design of the
scales shall be such as to have resolution suitable for the application. The marking of centre zero Watt
/Var meters shall be IMPORT (on left) and EXPORT (on right) to indicate the direction of
active/reactive power flow towards or away from the substation bus bars respectively.
11.1.4
Digital frequency meters shall be of class: 0.5 and shall have digital display of 5 and 4 digits
respectively, with display size, not less than 25mm (height).
11.2
TRANSDUCERS
11.2.1
Transducers (for use with Indicating Instruments) shall in general conform to IEC: 688-1
11.2.2
The energy meter capability shall be used for measurement of active power, reactive power, voltage,
current and frequency in three phase four wire unbalanced system.
11.2.3
One 33 kV C&R panel shall be installed for each incomer of 33 kV (Line incomer and 33 kV side of
transformer). Each panel shall consist of energy meter, protection schemes, indication and control etc.
One 11kV C&R panel shall be provided for each 11kV outdoor type VCB for incomer and feeder.
11.2.4
Voltage signal (440 Volt ac L-L) for voltmeter, PF meter, frequency meter, KW meter etc to be provided
in the C&R panel and shall be tapped from the respective PTs through a separate / independent copper
cable.
11.3
ENERGY METER
Contractor shall provide Static TVM energy meter as per the technical specification covered in the
chapter of technical specification of TVM energy meter
11.4
ANNUNCIATION SYSTEM
11.4.1
Alarm annunciation system shall be provided in the control board by means of visual and audible alarm.
The annunciation equipment shall be suitable for operation on the voltages specified in this
specification.
511.4.2
The visual annunciation shall be provided by annunciation facia windows mounted flush on the top of
the control panels.
11.4.3
The annunciator facia shall be provided with translucent plastic window for alarm point with
approximate size of 35mm x 50mm. The facia plates shall be engraved in black lettering with respective
inscriptions. Alarm inscriptions shall be engraved on each window in not more than three lines and size
of the lettering shall not be less than 5 mm.
Page 5 of 10
11.4.4
Each annunciation window shall be provided with two white lamps in parallel to provide safety against
lamp failure. Long life lamps shall be used. The transparency of cover plates and wattage of the lamps
provided in the facia windows shall be adequate to ensure clear visibility of the inscriptions in the
control room having high illumination intensity (350 Lux), from the location of the operator's desk.
11.4.5
All Trip facia shall have red colour and all Non-trip facia shall have white colour.
11.4.6
The annunciation system shall work in co-ordination with the existing annunciation system (hooter or
bell) in the substation for R&M scheme. If the same is not provided, hooter shall be supplied for above
purpose.
11.4.7
Alarm condition
Normal
Open
Off
OFF
Abnormal
Close
Flashing
ON
Accept
pressed
Close
Steady on Steady on
OFF
Fault contact
push
Reset
push
pressed
button
Visual Annunciation
Open
button
Lamp test
is
Audible
Annunciation
Hooter)
(by
OFF
Close
On
OFF
Open
Off
OFF
Open
Steady On
OFF
Open
Flashing
ON
Alarm test
11.4.8
Audible annunciation for the failure of DC supply to the annunciation system shall be provided and this
annunciation shall operate on 240 Volts AC supply. On failure of the DC to the annunciation system for
more than 2 or 3 seconds. (adjustable setting), a bell shall sound. A separate push button shall be
provided for the cancellation of this audible alarm alone but the facia window shall remain steadily
lighted till the DC supply to annunciation system is restored.
11.4.9
A separate voltage check relay shall be provided to monitor the failure of supply (240V AC). If the
failure of supply exists for more than 2 to 3 seconds. this relay shall initiate visual and audible
annunciation. This annunciation shall operate on DC and buzzer shall sound.
11.4.10
The total number of windows shall be 16 and the matter for engraving shall be indicated to the
contractor in due course.
11.5
SWITCHES
11.5.1
Control and instrument switches shall be rotary operated type with escutcheon plates clearly marked to
show operating position and circuit designation plates and suitable for flush mounting with only switch
front plate and operating handle projecting out.
11.5.2
The selection of operating handles for the different types of switches shall be as follows :
Breaker
control switches
Selector switches
Instrument switches
Page 6 of 10
11.5.3
The control switch of breaker shall be of spring return to neutral type. The switch shall have spring
return from close and trip positions to "after close" and "after trip" positions respectively. It shall be
necessary to press the switch before turning to close or command position.
11.5.4
11.5.5
The contacts of all switches shall preferably open and close with snap action to minimise arcing.
Contacts of switches shall be spring assisted and contact faces shall be with rivets of pure silver or silver
alloy. Springs shall not be used as current carrying parts
11.5.6
Continuous
supply,
11.6
INDICATING LAMPS
11.6.1
Indicating lamps shall be of multiple LED, panel mounting type with rear terminal connections. Lamps
shall have translucent lamp covers to diffuse lights coloured red, green, amber, clear white or blue as
specified. The lamp cover shall be preferably of screwed type, unbreakable and moulded from heat
resisting material.
11.6.2
Lamps and its parts shall be interchangeable and easily replaceable from the front of the panel.
11.6.3
The indicating lamps shall withstand 120% of rated voltage on a continuous basis.
11.7
SEMAPHORE INDICATORS
11.7.1
Position indicators of "SEMAPHORE" type shall be provided as part of the mimic diagrams on panels
for indicating the position of circuit breakers, isolating/earthing switches etc. The indicator shall be
suitable for semi-flush mounting with only the front disc projecting out and with terminal connection
from the rear. Their strips shall be of the same colour as the associated mimic.
11.7.2
Position indicator shall be suitable for DC Voltage as specified. When the supervised object is in the
closed position, the pointer of the indicator shall take up a position in line with the mimic busbars, and at
right angles to them when the object is in the open position. When the supply failure to the indicator
occurs, the pointer shall take up an intermediate position to indicate the supply failure.
11.7.3
11.7.4
The position indicators shall withstand 120 percent of rated voltage on a continuous basis.
12.0
RELAYS
12.1
All relays shall conform to the requirements of IS: 3231 or IEC-60255 or other applicable standards.
Relay shall be suitable for flush or semi-flush mounting on the front with connections from the rear.
Relays could be either electromechanical or electronics.
12.2
All protective relays shall be in draw out type in modular cases with proper testing facilities in the form
of blocks. Necessary test plugs shall be supplied loose and shall be included in Contractor's scope of
supply.
12.3
AC Voltage operated relays shall be suitable for 110 Volts VT secondary and current operated relays for
5 amp CT secondary. All DC operated relays and timers shall be designed for the DC voltage specified,
and shall operate satisfactorily between 80 percent and 110 percent of rated voltage. All relays shall
have adequate thermal capacity for continuous operation.
12.4
The protective relays shall be suitable for efficient and reliable operation of the protection scheme
described in the specification. Necessary auxiliary relays, timers, lockout relay etc. required for the
complete protection schemes described in the specification shall be provided. All protective relays shall
be provided with at least two pairs of potential free isolated output contacts. Auxiliary relays and timers
shall have pairs of contacts as required to complete the scheme. Contacts shall be silver faced with
Page 7 of 10
spring action. Relay case shall have adequate number of terminals for making potential free external
connections.
12.5
All protective relays, auxiliary relays and timers shall be provided with hand reset type contacts. They
shall also be provided with hand reset type external operation indicators with suitable inscription to be
informed in due course of time.
12.6
No control relay which shall trip the power circuit breaker when the relay is de-energised shall be
employed in the circuits.
12.7
Provision shall be made for easy isolation of trip circuits of each relay for the purpose of testing and
maintenance.
12.9
All protective relays and alarm relays shall be provided with one extra isolated pair of contacts wired to
terminals.
12.10.
The setting ranges of the relays offered, if different from the ones specified shall also be acceptable if
they meet the functional requirements.
12.11
Any alternative or additional protections or relays considered necessary for providing complete
effective and reliable protection should also be offered separately. The acceptance of this alternative/
additional equipment shall lie with the BSPHCL.
12.12
All relays shall have capability to withstand test voltage of 2 kV rms for one minute.
12.13
All relays and their drawings shall have phase indications as R-Red, Y-yellow, and B-blue
12.14
PROTECTIONS:
A)
Two over current(IDMT characteristic with a definite minimum time of 3.0 seconds at
10 times setting and have a variable setting range of 50-200% of rated current) and one
earth fault relay. Contractor may offer a composite unit also having these features as
separate elements.
II.
One auxiliary relay which shall receive inputs from all transformer protections and send
command to trip coil of the circuit breaker through master trip relay.
III.
B)
C)
12.15
33 kV line panels.
I.
Two over current (IDMT characteristic with a definite minimum time of 3.0 seconds at
10 times setting and have a variable setting range of 50-200% of rated current) and one
earth fault relay. The 33 kV lines are envisaged to operate in a synchronous ring having
feed at multiple points.
II.
There shall be high speed master trip hand reset lock out relay which shall receive inputs
from above relay and send command to trip coil of the circuit breaker directly.
Two over current(IDMT characteristic with a definite minimum time of 3.0 seconds at
10 times setting and have a variable setting range of 50-200% of rated current) and one
earth fault relay. The 33 kV lines are envisaged to operate in a synchronous ring having
feed at multiple points.
II.
There shall be high speed master trip hand reset lock out relay which shall receive inputs
from above relay and send command to trip coil of the circuit breaker directly.
SUPERVISION RELAY
Following supervision relay shall be provided having adequate contacts for providing alarm.
(a)
(b)
DC supply supervision
Page 8 of 10
(c)
AC supply supervision
13.0
TYPE TESTS
13.1
b)
High frequency disturbance test as per IEC 60255-4 (Appendix -E) -Class III (not
applicable for electromechanical relays)
c)
Fast transient test as per IEC 1000-4, Level III (not applicable for electromechanical
relays)
d)
Dynamic
e)
f)
g)
13.2
Steady state & Dynamic characteristics tests on the relays (current differential protection relays), as type
test, shall be carried out based on general guide lines specified in CIGRE Committee 34 report on
simulator/network analyser/PTL.
14.0
Sl.
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Description of Relays
QUANTITY
Ammeter
1
with selector switch
0
Wattmeter
Pistol
1
grip CB control switch
3
Red indicating lamp for indicating close position
of CB
Red indicating lamp for indicating close position
of Isolator
Red indicating lamp for indicating close position
of Earth switch
Green indicating lamp for indicating open
position of CB
Green indicating lamp for indicating open
position of Isolator
Green indicating lamp for indicating open
position of Earth switch
Yellow indicating lamp for auto trip
Blue indicating lamp for spring charging
Annunciation
1
windows
with
associated
annunciation
5
relay
Push
1 buttons for Alarm accept/Reset/Lamp test
4
Mimic
1
to represent SLD with Seamaphore
indication
6
Voltmeter
9
with selector switch
Cut
1 out mounting and wiring for WTI and
selector
7
switch
TRANSFORMER
PANEL
1
BUS
COUPLER
-
FEEDER PANEL
1
1
1
1
1
1 no for each
Isolator
1 no for each Earth
switch
1
1 no for each
Isolator
1 no for each
Earth switch
1
1 no for each
Isolator
1 no for each Earth
switch
1
1 no for each
Isolator
1 no for each Earth
switch
1
1
1
1 no for each
Isolator
1 no for each
Earth switch
1
1
1
1 no for each
Isolator
1 no for each Earth
switch
1
1
1
1 LOT
1 LOT
1 LOT
1
1 LOT
Page 9 of 10
Sl.
No.
17
18
19
20
21
22
23
24
25
26
27
28
29
Description of Relays
QUANTITY
Energy
8
meter TVM
Trip
4 Circuit supervision relays
DC
1 supply supervision relay
8
AC
1 supply supervision relay
8
Flag
1 relays, aux relays, timers trip relays etc as
per
9 scheme requirement
Bus frequency meter(Digital)
Bus Healthy indication lamps
Auxiliary relay for Buchholz
21O/C 1 E/F realy
.
Static,
5
instantaneous 3 phase PT Fuse Failure
Relays. Rated Voltage-110VAC
Master
6
Trip Relays suitable for operation at 110
VDC with sufficient number and configuration
of contacts.
Auxiliary
7
Relays for Anti-pumping, Density
switch, Contact multiplier etc. as may be
required.
Power
1
Factor meter (Digital)
1
TRANSFORMER
PANEL
1
1
BUS
COUPLER
1
1
FEEDER PANEL
1
1
1
1 set
1 set
1 set
1
3
1
1
1 LOT
1 LOT
1 LOT
Note :
1
For transformer feeders, all equipments of control panel shall be provided separately for HV
and LV sides.
The above list of equipments mentioned for control panel is generally applicable unless it is
defined elsewhere and in case of bay extension in existing substations, necessary equipments
for matching the existing control panel shall be supplied
3.
Each line /HV side of transformer/LV side of transformer /TBC shall be considered as one
feeder for above purpose.
Page 10 of 10
1.
1.
2.
APPLICABLE STANDARDS
S
N
1
IS 2705(I-IV)
IS 2165
IS 2099
4
5
IS 3347
IS 2071
6
7
IS 335
IS 13947(Part I)
3.
IS
Indian electricity
Rules 1956/ CEA
regulations, 2010
IEC
IEC 185, IEC
44(4)
IEC 815
Item
Current transformers
Insulation coordination: Part 1
Phase to earth insulation coordination
Bushings
voltages
principles for
andalternating
rules
above 1 000 Volts
Dimensions for Porcelain Transformer
Methods
Bushings of High Voltage Testing
New insulating oils
Glossary of terms relating to metal
containers
Indian electricity Rules 1956/ CEA
regulations, 2010
Guide for the selection of insulators in
respect of polluted condition
AMBIENT CONDITIONS
The CT supplied against this specification shall be suitable for satisfactory
continuous operation under the tropical conditions mentioned in General
Technical Requirement.
4.
TECHNICAL PARAMETERS OF CT
a)
Type
b)
c)
d)
e)
Type of mounting
Rated primary current
Rated Continuous capacity
Rated short time withstand
Requirement for secondary Winding
f)
Rated short time withstand
Current for 3 sec (KA rms)
g)
Rated dynamic withstand Current
(KA rms)
h)
Max temp rise
i)
Minimum creepage distance of
porcelain housing (mm) of highest
system voltage
j)
One minute power frequency
Withstand voltage between
Secondary terminal & earth
i)
Detail of Secondary Cores
Current ratio
Accuracy class
Burden (VA)
Instrument security Factor
3 kV
Metering/ Protn.
1200-600-300/ 1-1-1 A
0.5/ 5P10
30 / 30
5/ 5
Note: The ratings indicated for instrument transformer are tentative only
and the contractor should verify this and supply equipment to meet the
requirements.
5.
PORCELAIN HOUSING
It shall be single piece of homogeneous, vitreous porcelain of high
mechanical & dielectric strength. It will be glazed with uniform Brown or
Dark brown colour with smooth surface finish. The clear height of
porcelain housing shall be at least 430 mm.
The contractor shall clearly detail in his bid the details of attaching the
metallic flange to porcelain, pressure release valve and also how primary
& secondary terminals shall be brought out.
6.
CORE
Core shall be made of high grade non aging, cold rolled grain oriented steel of
low hysterisis loss and permeability to ensure specified accuracy at normal and
over voltage. The flux density shall be limited so that there is no saturation
during service. The internal security factor should be low enough not to damage
the instrument in the event of short circuit or over voltage
7.
WINDING
PRIMARY WINDING:
It shall be made of double paper insulated high conductivity rigid copper
wire. The primary winding current density shall not exceed the limit of 1.6
Amp per sq. mm for normal rating. The insulation shall be free from
composition likely to flow, ooze or collapse in oil.
The design current density for short circuit current as well as conductivity
of metal used for primary winding shall be as per IS 2705. The calculation
for the selection of winding cross section shall be furnished by contractor.
The primary terminal shall be of standard size of 30 mm dia x 80 mm
length of heavily tinned (min. thickness 15 micron) electrolytic copper of
99.99 % conductivity.
SECONDARY WINDING:
It shall be made of insulated copper wire of electrolytic grade. Type of
insulation used shall be described in the offer. For multi ration design, the
multi ratio will be achieved by reconnection of the primary winding or
secondary winding. The excitation current of the CT shall be as low as
possible. The contractor shall furnish the magnetization curves for all the
cores.
The terminal box shall be dust free & vermin proof. The size of the terminal
box shall be big enough to enable easy access and working space with the
use of normal tools.
The secondary terminals studs shall be provided with at least 3 nuts and
two plain washers, these shall be made of brass. Duly nickeld. The min.
stud outer dia shall be 6 mm & length 15 mm. The min spacing between
the centers of the adjacent studs shall be 1.5 time the outer dia of the
stud.
8.
POLARITY
The polarity shall be marked on each CT at the secondary terminals in the
terminal box.
9.
10.
INSULATION OIL
The first filling of oil in CT shall be in contractors scope. The oil shall be
as per IS 335.The ensure the prevention of oil, the contractor will give
the details supported by drawings:
1.
2.
3.
11.
12.
EARTHING
Two earthing terminals shall be provided on the metallic tank of size 16
mm dia & 30 mm length each with one plain washer & one nut for
connection to the station earth mat
13.
14.
TESTING
The following test shall be conducted on CT
1.
2.
Polarity test
a.
b.
1.
3.1
Scope
The specification covers the design, manufacture, testing at
manufacturers works and supply of 33 KV Current Transformers complete
with all accessories and spares required for their satisfactory operation
for various PSS , as detailed in the schedule of requirements enclosed.
3.2
Standards
The Current Transformers shall conform in all respects to IEC-186 & IS:
2705 part-I,II,III & IV (amended up to date) except where specified
otherwise. The equipment meeting any other authoritative standard which
ensures equal or better quality than the standard mentioned above shall
also be acceptable. Where the equipment offered conforms to any other
standard the salient features of difference between the standards adopted and
specified shall be clearly brought out in the tender.
3.3.
Ratings
33 KV Current Transformers
1 Normal System Voltage (KV)
33
2 Highest System Voltage (KV)
36
3 Earthing
Effective
4 1 min. Power Frequency with stand Voltage (KV)
5 Impulse with stand Voltage (KVp)
6 Short time Current Rating (KA/1 sec)
Detail of Secondary Cores
7
Current ratio
Accuracy class
Burden (VA)
70
170
25
Metering/ Protn./ Diff
Protection
800-400-200/1-1-1 (3 core)
0.5/ 5P10
20VA/20 VA/20VA
3.4
General
3.4.1
3.4.2
3.4.3
The transformer shall be sealed to climate breathing and shall prevent air
and moisture from entering the tank. These shall be provided with oil
level gauge and shall be equipped with pressure releasing device capable of
releasing abnormal pressure without damage to metal or porcelain housing.
3.5
Windings
3.5.1
3.5.2
The current transformer core to be used for O/C and E/F protection
shall be of 5P class. The core shall be designed for minimum saturation
factor of 10 for the highest setting. The magnetizing curves for the core
shall be furnished with the tender.
3.5.3
The current transformer core to be used for distance, differential and bus
bar protection shall be of Ps class.
3.5.4.
3.5.5
3.6
Temperature Rise
3.6.1
3.7
Bushings
3.7.1
when operated at rated voltage .In general the bushings shall conform to the
latest issue of IS 2099 or equivalent.
3.7.2
3.8
Insulation Oil
3.8.1
The quantity of insulating oil for first filling and complete specification for
insulating oil shall be stated in the tender. The oil shall conform to the latest
requirement of Indian Standard 335
3.9
Type of Mounting
The Current Transformers shall be suitable for mounting on steel structures.
The necessary flanges, nuts, bolts, etc for Current Transformers shall be
supplied and these shall be galvanized.
3.10
3.11
Terminal Connectors
Terminal connectors shall be suitable for 0.4 ACSR Conductor. Suitable
terminal connector for earth connection shall also be supplied size of
Terminal connectors however shall be confirmed at the time of approval of
drawing.
3.12
Tests
3.12.1 Each Current Transformer shall be subjected to all tests as specified in
IS 2705, in presence of the purchasers representative.
3.12.2 Report of the following type tests as stipulated in IS 2705 shall
be supplied
a)
Short time current test
b)
Temperature rise test
c)
Impulse voltage test
d)
Instrument security current test (for measuring CTs)
e)
Composite error test (direct test) for protective CTs. All the test
report shall be submitted and got approved by the purchaser before dispatch of
the equipment.
3.13
3.13.1
The tenderer shall submit with the tender the following drawings to
enable the purchaser to assess the suitability of the equipment.
a)
c)
e)
3.13.2
These drawings shall show sufficiently over all dimensions clearance and
space requirements of all apparatus to be furnished to enable the
purchaser to determine the design and layout of the installation.
3.13.3
Soon after the award of the contract the manufacturer shall submit the
drawing duly describing the equipment in detail for approval.
The following drawings are to be supplied as part f the contract:a)
b)
c)
d)
e)
f)
3.13.4
3.15
Completeness of Equipment
Any fitting accessories or apparatus which may not have been specifically
mentioned in this specification but are usual or necessary in the equipment
for satisfactory functioning shall be deemed to be included in the contract
and shall be supplied without any extra cost. All plant and equipment shall
be complete in all details whether such details are mentioned in the
specification or not.
3.16
Galvanization
All the ferrous parts including nuts bolts etc shall be hot dip galvanized as
per IS 2629-1966 (As amended up to date).
3.17
3.18
Guarantee
The equipment along with all accessories shall be guaranteed for a period of
18 months from the date of supply or 12 months from the date of
commissioning which ever is earlier. If any defect develops or is noted
during this period in any part of the equipment and accessories, the supplier
shall replace or repair the same to the satisfaction of the purchaser
expeditiously free of cost to the purchaser.
SECTION 3, CHAPTER 7
INSTRUMENT TRANSFORMERS
2.
1.
SCOPE
The scope of this specification covers design, manufacturing, testing, supply,
transportation, insurance (transit & storage), erection site testing &
commissioning of 12kV Current Transformer suitable for outdoor service. Any
parts not specifically mentioned in this specification but otherwise required
for proper functioning of the equipment should be included by the bidder in the
offer.
2.
APPLICABLE STANDARDS
S
N
1
IS 2705(I-IV)
IS 2165
IS 2099
4
5
IS 3347
IS 2071
6
7
IS 335
IS 13947(Part I)
3.
IS
IEC
IEC 185, IEC
44(4)
Item
Current transformers
Insulation coordination: Part 1 Phase to
earth insulation coordination principles
Bushings
and rules for alternating voltages above 1
000 Volts
Dimensions for Porcelain Transformer
Bushings of High Voltage Testing
Methods
New insulating oils
Glossary of terms relating to metal
containers
Indian electricity Rules 1956/ CEA
regulations, 2010
Indian electricity
Rules 1956/ CEA
regulations, 2010
IEC 815
AMBIENT CONDITIONS
The CT supplied against this specification shall be suitable for satisfactory
continuous operation under the tropical conditions mentioned in General
Technical Requirement.
SECTION 3, CHAPTER 7
INSTRUMENT TRANSFORMERS
4.
TECHNICAL PARAMETERS OF CT
a)
Type
b)
c)
d)
e)
Type of mounting
Rated primary current
Rated Continuous capacity
Rated short time withstand
Requirement for secondary Winding
f)
Rated short time withstand Current
for 3 sec (KA rms)
g)
Rated dynamic withstand Current
(KA rms)
h)
Max temp rise
i)
Minimum creepage distance of
porcelain housing (mm) of highest
system voltage
j)
One minute power frequency
Withstand voltage between Secondary
terminal & earth
i)
Detail of Secondary Cores
Current ratio
Accuracy class
Burden (VA)
Instrument security Factor
3 kV
Metering/ Protn.
600-300-150/ 5-5 A
0.5/ 5P10
30 / 30
5/ 5
Note: The ratings indicated for instrument transformer are tentative only and the
contractor should verify this and supply equipment to meet the requirements.
5.
PORCELAIN HOUSING
It shall be single piece of homogeneous, vitreous porcelain of high mechanical &
dielectric strength. It will be glazed with uniform Brown or Dark brown colour
with smooth surface finish. The clear height of porcelain housing shall be at
least 430 mm.
The contractor shall clearly detail in his bid the details of attaching the
metallic flange to porcelain, pressure release valve and also how primary
& secondary terminals shall be brought out.
6.
CORE
SECTION 3, CHAPTER 7
INSTRUMENT TRANSFORMERS
Core shall be made of high grade non aging, cold rolled grain oriented steel of low
hysterisis loss and permeability to ensure specified accuracy at normal and over
voltage. The flux density shall be limited so that there is no saturation during service.
The internal security factor should be low enough not to damage the instrument in the
event of short circuit or over voltage
7.
WINDING
PRIMARY WINDING:
It shall be made of double paper insulated high conductivity rigid copper wire.
The primary winding current density shall not exceed the limit of 1.6
Amp per sq. mm for normal rating. The insulation shall be free from composition
likely to flow, ooze or collapse in oil.
The design current density for short circuit current as well as conductivity of
metal used for primary winding shall be as per IS 2705. The calculation for the
selection of winding cross section shall be furnished by contractor.
The primary terminal shall be of standard size of 30 mm dia x 80 mm length of
heavily tinned (min. thickness 15 micron) electrolytic copper of
99.99 % conductivity.
SECONDARY WINDING:
It shall be made of insulated copper wire of electrolytic grade. Type of insulation
used shall be described in the offer. For multi ration design, the multi ratio will
be achieved by reconnection of the primary winding or secondary winding. The
excitation current of the CT shall be as low as possible. The contractor shall
furnish the magnetization curves for all the cores.
The terminal box shall be dust free & vermin proof. The size of the terminal box
shall be big enough to enable easy access and working space with the use of
normal tools.
The secondary terminals studs shall be provided with at least 3 nuts and two
plain washers, these shall be made of brass. Duly nickeld. The min. stud outer
dia shall be 6 mm & length 15 mm. The min spacing between the centers of
the adjacent studs shall be 1.5 time the outer dia of the stud.
8.
POLARITY
SECTION 3, CHAPTER 7
INSTRUMENT TRANSFORMERS
9.
10.
INSULATION OIL
The first filling of oil in CT shall be in contractors scope. The oil shall be
as per IS 335.The ensure the prevention of oil, the contractor will give the
details supported by drawings:
1.
2.
3.
11.
SECTION 3, CHAPTER 7
INSTRUMENT TRANSFORMERS
EARTHING
Two earthing terminals shall be provided on the metallic tank of size 16 mm dia
& 30 mm length each with one plain washer & one nut for
connection to the station earth mat
13.
14.
TESTING
The following test shall be conducted on CT
1.
2.
Polarity test
a.
b.
SECTION 3, CHAPTER 7
INSTRUMENT TRANSFORMERS
3.
1.0
2.0
APPLICABLE STANDARDS
Sl.
No.
IS
IS 3156
IS 2099
3
4
IS 3347
IS 335
5
6
IS 13947(Part I)
Indian electricity Rules
1956/ CEA regulations,
2010
3.0
IEC
IEC 186
Item
Voltage transformers
Bushings for alternating
voltages above 1 000 Volts
Dimensions for Porcelain
New
insulating
oils
Transformer
Bushings
Glossary of terms relating to
Indian
electricity Rules 1956/
metal containers
CEA regulations, 2010
IEC 815
AMBIENT CONDITIONS
The PT supplied against this specification shall be suitable for
satisfactory continuous operation under the tropical conditions mentioned in
General Technical Requirement.
4.0
TECHNICAL PARAMETERS OF PT
SECTION 3, CHAPTER 7
INSTRUMENT TRANSFORMERS
a)
Rated primary Voltage
b)
Type
transformer
c)
36 kV
12 KV
Single phase potential
33/0.11
d)
Rated voltage factor continuous
e)
O ne minute power freq.
Withstand voltage for
1.2 continuous
11/0.11
1.2
Primary Terminals
70 kV (rms) - 28 k V (rms)
Secondary winding
3 kV (rms) - 3 kV (rms)
f)
Application
Metering
Accuracy
0.5
Burden (VA)
200
h)
sec
Metering
0.5
200
PORCELAIN HOUSING
It shall be single piece of homogeneous, vitreous porcelain of high mechanical &
dielectric strength. It will be glazed with uniform Brown or Dark brown colour
with smooth surface finish. The clear height of porcelain housing shall be at least
430 mm for 33kV /11 KV class PT.
The contractor shall clearly detail in his bid the details of attaching the metallic
flange to porcelain, pressure release valve and also how primary
SECTION 3, CHAPTER 7
INSTRUMENT TRANSFORMERS
7.0
CORE
Core shall be made of high grade non aging, cold rolled grain oriented steel of
low hysterisis loss and permeability to ensure specified accuracy at normal and
over voltage. The flux density shall be limited so that there is no saturation during
service. The internal security factor should be low enough not to damage the
instrument in the event of short circuit or over voltage
WINDING Primary
Winding:
It shall be made of double paper insulated electrolytic copper wire. The neutral end
of the winding shall be brought outside for earthing. The insulation shall be free
from composition likely to flow, ooze or collapse in oil.
The primary terminal shall be of standard size of 30 mm dia x 80 mm length of
heavily tinned (min. thickness 15 micron) electrolytic copper of
99.99 % conductivity.
Secondary Winding:
It shall be made of insulated copper wire of electrolytic grade. The terminal
box shall be dust free & vermin proof.
The secondary terminals studs shall be provided with at least 3 nuts and two plain
washers, these shall be made of brass duly nickeld. The min. stud outer dia shall
be 10 mm & length 15 mm. The min spacing between the centers of the adjacent
studs shall be 1.5 times the outer dia of the stud.
Polarity:
The polarity shall be marked on each PT at the secondary terminals in the terminal
box. There shall be MCB of suitable rating at secondary terminals.
8.0
SECTION 3, CHAPTER 7
INSTRUMENT TRANSFORMERS
epoxy paint externally after cleaning and application of primer. The inner surface
shall be painted with oil resistance white enamel paint.
All ferrous hardwares, exposed to atmosphere shall be hot dipped galvanized.
9.0
INSULATION OIL
The first filling of oil in PT shall be in Contractors scope. The oil shall be as per
IS 335.To ensure the prevention of oil, the contractor will give the details
supported by drawings:
1.
2.
3.
Any nut & bolt and screw used for fixation of the interfacing porcelain bushing for
taking out the terminals shall be provided on flanges clamped to the bushings &
not on the porcelain directly.
If gasket joints are used, Nitrite Butyl Rubber gasket shall be used. The grooves
shall be machined with adequate space for accommodating gasket under pressure.
The PT shall be vacuum filled with oil after processing. It will be hermatically
sealed to eliminate breathing and to prevent air & moisture from entering the
tank. The sealing methods/arrangement shall be described by the contractor &
be approved by the owner.
10.0
11.0
EARTHING
Two earthing terminals shall be provided on the metallic tank of size 16 mm dia &
30 mm length each with one plain washer & one nut for connection to the station
earth mat.
SECTION 3, CHAPTER 7
INSTRUMENT TRANSFORMERS
12.0
13.0
TERMINAL BOX
A dust, vermin and weatherproof terminal box shall be provided at the lower end
of the voltage transformer for terminating the secondary windings. The box shall
have bolted cover plate complete with gasket. The terminal box shall have terminal
blocks, cable gland plate and cable glands with shrouds suitable for 6x2.5
sq.mm. PVC insulated and armoured control cable as per IEC:277 or IS 1554.
The terminal blocks shall have covering of moulded insulation material
complete with brass studs, washers nuts and lock nuts suitable for
termination
of 2x2.5 sq.mm.
wires. The termination shall be made by crimping lugs or bare wire with insulating
sleeves at ends.
The inside of the terminal box shall be accessible through a removable bolted
cover. The secondary taps shall be adequately reinforced to withstand normal
handling without damage. Suitable cable glands, supporting strip and clamps shall
be provided to support and accommodate control cables
The secondary terminal shall be provided with isolating and earthing
arrangements at the terminal block to be provided in the terminal box.
Temperature rise of the winding over the ambient shall be limited to 55oC The
terminal box enclosure shall have protection as per class IP55 of
IEC:529 or IS 13947.
14.0
SECTION 3, CHAPTER 7
INSTRUMENT TRANSFORMERS
15.0
TESTING
The following routine test shall be conducted on PT
16.0
1.
Insulation Resistance
2.
3.
Polarity Test
4.
Marking
Rating plates shall be as per IS 3156
17.0
ACCESSORIES
The fitting and accessories to be provided with each of the voltage
transformers shall include the following.
a.
Terminal Box
b.
c.
e.
f.
SECTION 3, CHAPTER 7
INSTRUMENT TRANSFORMERS
h.
i.
j.
GENERAL
The provisions of this section of specification shall only be applicable to the extent of
scope of works indicated in Bid Proposal Sheet (BPS). The intent of specification
covers the following:
Design, engineering, and construction of all civil works at sub-station. All civil works
shall also satisfy the general technical requirements specified in other Sections of this
Specification and as detailed below. They shall be designed to the required service
conditions/loads as specified elsewhere in this Specification or implied as per National/
International Standards.
All civil works shall be carried out as per applicable Indian Laws, Standards and Codes.
All materials shall be of best quality conforming to relevant Indian Standards and
Codes.
The Contractor shall furnish all design, drawings, labour, tools, equipment, materials,
temporary works, constructional plant and machinery, fuel supply, transportation and
all other incidental items not shown or specified but as may be required for complete
performance of the Works in accordance with approved drawings, specifications and
direction of Employer.
The work shall be carried out according to the design/drawings to be developed by the
Contractor and approved by the owner based on Tender Drawings Supplied to the
Contractor by the Owner. For all buildings, structures, foundations etc. necessary
layout and details shall be developed by the Contractor keeping in view the functional
requirement of the substation facilities and providing enough space and access for
operation, use and maintenance based on the input provided by the Owner. Certain
minimum requirements are indicated in this specification for guidance purposes only.
In case of R&M of existing substations, Contactor shall visit site to ascertain the
amount of repair and strengthening of structures and foundations, dismantling and new
construction of structures and foundations works are to be done before quoting.
Contractor must furnish the design and drawings in support of the activities mentioned
above that are to be carried out in the R&M of existing substation site.
However, the Contractor shall quote according to the complete requirements.
2.0
GEOTECHNICAL INVESTIGATION
2.1
Page 1 of 30
2.2
The Contractor should visit the site to ascertain the soil parameters before submitting
the bid. The topography is uneven steeply sloping at few places requiring cutting and
filling operations including slope stability and protection measures (if slopes
encountered). Any variation in soil data shall not constitute a valid reason for any
additional cost & shall not affect the terms & condition of the Contract. Tests must be
conducted under all the critical locations i.e. Control Room Building. Tower locations,
transformer etc.
3.0
SCOPE OF WORK
This specification covers all the work required for detailed soil investigation and
preparation of a detailed report. The work shall include mobilisation of necessary
equipment, providing necessary engineering supervision and technical personnel,
skilled and unskilled labour etc. as required to carry out field investigation as well as,
laboratory investigation, analysis and interpretation of data and results, preparation of
detailed Geo-technical report including specific recommendations for the type of
foundations and the allowable safe bearing capacity for different sizes of foundations at
different founding strata for the various structures of the substation. The Contractor
shall make his own arrangement for locating the co-ordinates and various test positions
in field as per the information supplied to him and also for determining the reduced
level of these locations with respect to the benchmark indicated by the Owner.
All the work shall be carried out as per latest edition of the corresponding Indian
Standard Codes.
3.1
Bore Holes
Drilling of bore holes of 150 mm dia. in accordance with the provisions of IS: 1892, to
10 m depth or to refusal which ever occur earlier (by refusal it shall mean that a
standard penetration blow count (N) of 100 is recorded for 30 cm penetration). For a
new substation, minimum two bore holes shall be done to find out the geological
profile of the area. If any unconformity encountered then more bore holes shall be
drilled with the approval of Engineer-in-charge for the new projects. However in case
deep pile foundations are envisaged the depths have to be regulated as per codel
provisions. In cases where rock is encountered, coring in one borehole per bay shall be
carried out to 1.5 M in bedrock and continuous core recovery is achieved.
Performing Standard Penetration Tests at approximately 1.5 m interval in the borehole
starting from 1.5 m below ground level onwards and at every change of stratum. The
disturbed samples from the standard penetrometer shall also be collected for necessary
tests.
Collecting undisturbed samples of 100/75 mm diameter 450 mm long from the
boreholes at intervals of 2.5 m and every change of stratum starting from 1.0 m below
ground level onwards in clayey strata.
The depth of Water table shall be recorded in each borehole.
All samples, both disturbed and undisturbed, shall be identified properly with the
borehole number and depth from which they have been taken.
Page 2 of 30
The sample shall be sealed at both ends of the sampling tubes with wax immediately
after the sampling and shall be packed properly and transported to the Contractors
laboratory without any damage or loss.
The logging of the boreholes shall be compiled immediately after the boring is
completed and a copy of the bole log shall be handed over to the Engineer-in-charge.
3.2
3.3
3.4
Water Sample
Representative samples of ground water shall be taken when ground water is first
encountered before the addition of water to aid drilling of boreholes. The samples shall
be of sufficient quantity for chemical analysis to be carried out and shall be stored in
airtight containers.
3.5
3.6
Laboratory Test
1.
The laboratory tests shall be carried out progressively during the field work
after sufficient number of samples have reached the laboratory in order that the
test results of the initial bore holes can be made use of in planning the later
stages of the field investigation and quantum of laboratory tests.
Page 3 of 30
2.
3.7
a)
b)
c)
d)
e)
h)
f)
g)
h)
3.7.1 The Contractor shall submit the detailed report in two (2) copies wherein information
regarding the geological detail of the site, summarised observations and test data, bore
logs, and conclusions and recommendations on the type of foundations with supporting
calculations for the recommendations. Initially the report shall be submitted by the
Contractor in draft form and after the draft report is approved, the final report in two (2)
copies shall be submitted. The test data shall bear the signatures of the Investigation
Agency, Vendor and also site representative of BSPHCL.
3.7.2. The report shall include but not limited to the following:
a)
A plan showing the locations of the exploration work i.e. bore holes, dynamic
cone penetration tests etc.
b)
Bore Logs: Bore logs of each bore holes clearly identifying the stratification and
the type of soil stratum with depth. The values of Standard Penetration Test
(SPT) at the depths where the tests were conducted on the samples collected at
various depths shall be clearly shown against that particular stratum.
Test results of field and laboratory tests shall be summarised strata wise as well
in combined tabular form. All relevant graphs, charts tables, diagrams and
photographs, if any, shall be submitted along with report. Sample illustrative
reference calculations for settlement, bearing capacity, pile capacity shall be
enclosed.
Page 4 of 30
3.10
4.0
Recommendations: The report should contain specific recommendations for the type
of foundation for the various structures envisaged at site. The Contractor shall acquaint
himself about the type of structures and their functions from the Owner. The
observations and recommendations shall include but not limited to the following:
a)
b)
c)
Allowable bearing pressure on the soil at various depths for different sizes of
the foundations based on shear strength and settlement characteristics of soil
with supporting calculations. Minimum factor of safety for calculating net safe
bearing capacity shall be taken as 3.0 (three). Recommendation of liquefaction
characteristics of soil shall be provided.
d)
e)
Comments on the Chemical nature of soil and ground water with due regard to
deleterious effects of the same on concrete and steel and recommendations for
protective measures.
f)
g)
SITE PREPARATION
The contractor shall be responsible for proper leveling of switchyard site as per layout
and levels of switchyard finalised during detailed engineering stage. The Contractor at
his own cost shall make the layout and levels of all structure etc from the general grids
of the plot and benchmarks set by the Contractor and approved by the Owner. The
Contractor shall give all help in instruments, materials and personnel to the Owner for
checking the detailed layout and shall be solely responsible for the correctness of the
layout and levels. Site leveling shall be in the scope of the contractor. Bidder may
decide the level of the sites. However, the level shall be such that it is 300 mm higher
than the highest flood level (HFL) of the site.
Page 5 of 30
Whenever for bay extension works the existing substation are to be modified or
strengthen, contractor should keep the R.L of extension part of the sub-station same as
EL of existing sub-station so that FFL shall be same for both and all the necessary
arrangements are to be carried out in this regard by the contractor.
5.0
SCOPE OF WORKS
This clause covers the design and execution of the work for site preparation, such as
clearing of the site, the supply and compaction of fill material, slope protection by
stone pitching/retaining walls depending on the site location/condition, excavation and
compaction of backfill for foundation, road construction, drainage, trenches and final
topping by brick soling/stone filling.
5.1
5.2
General
1)
The Contractor shall develop the site area to meet the requirement of the
intended purpose. The site preparation shall conform to the requirements of
relevant sections of this specification or as per stipulations of standard
specifications. Contractor shall also carry out necessary protection of slope of
switchyard area and approach road.
2)
If fill material is required, the fill material shall be suitable for the above
requirement. The fill shall be such a material and the site so designed as to
prevent the erosion by wind and water of material from its final compacted
position or the in-site position of undisturbed soil.
3)
4)
Backfill material around foundations or other works shall be suitable for the
purpose for which it is used and compacted to the density described under
Compaction. Excavated material not suitable or not required for backfill shall be
disposed off in area's as directed by owner upto a maximum lead of 1 km.
Excavation and backfill for foundations shall be in accordance with the relevant
code.
2.
Whenever water table is met during the excavation, it shall be dewatered and
water table shall be maintained below the bottom of the excavation level during
excavation, concreting and backfilling.
3.
4.
5.3
5.4
5.
6.
The pitching shall be designed and provided for slope protection as per
approved drawings. The stone used shall be sound, hard, durable and fairly
regular in shape. Stones subjected to marked deterioration by water or weather
shall not be used. Suitable measures shall be provided to prevent erosion by
seepage of water. Largest stone procurable shall be used as approved by owner
for the work. Random rubble masonry (1:6) retaining walls shall be provided
wherever required as per site condition.
Compaction
1.
The density to which fill materials shall be compacted shall be as per relevant IS
and as per direction of Owner. All compacted sand filling shall be confined as
far as practicable. Backfilled earth shall be compacted to minimum 95% of the
Standard Proctors density at OMC. The sub grade for the roads and
embankment filling shall be compacted to minimum 95% of the Standard
Proctors density at OMC. Cohesion less material sub grade shall be compacted
to 70% relative density (minimum).
2.
3.
6.0
6.1
The Contractor shall furnish all labour, equipment and materials required for complete
performance of the work in accordance with the drawings specification and direction of
the Owner.
Brick soling/stone filling shall be done in the areas of the switchyard wherever
equipments and or structures are to be provided under present scope of work covering
entire fencing area.
Prevailing practice of stone filling or brick soling are to be adopted for the bay extension
works of existing substations. Contractor shall verify the existing practice prevailing at
site before quoting.
7.0
7.1
GENERAL REQUIREMENT
The material required for site surfacing shall be free from all types of organic materials
and shall be of standard quality, and as approved by the Owner.
The material to be used for brick soling /site surfacing shall be over burnet bricks of
regular size. Laying of brick in such away that depth of laying become half brick thick
and joints shall be filled with sand.
The material to be used for stone filling/ site surfacing shall be uncrushed/ crushed/
broken stone of 20 mm nominal size (upgraded single size) conforming to table 2 of IS:
383- 1970. Hardness, flakiness shall be as required for wearing courses are given
below.
(a) Sieve analysis limits/Gradation
Sieve size
% passing by weight
40mm
20mm
10mm
4.75mm
100
85-100
0-20
0-5
(b) Hardness
Abrasion value (IS: 2386 part-IV) not more than 40%
Impact value (IS: 2386 part-IV) not more than 30%
(c) Flakiness Index
As per (IS: 2386 part-IV) and maximum value is 25.
7.2
After all the structures/equipments are erected and antiweed treatment is complete, the
surface of the switchyard area shall be maintained, rolled/compacted to the lines and
grades as decided by Engineer-in-Charge. De-weeding including removal of roots shall
be done before rolling is commenced. Engineer-in-Charge shall decide final formation
level so as to ensure that the site appears uniform devoid of undulations. The final
formation level shall however be very close to the formation level indicated in the
drawing using half-ton roller with suitable water sprinkling arrangement to form a
smooth and compact surface.
7.3
passes and water sprinkling to form a minimum 50 mm layer on the finished ground
level of the specified switchyard area excluding roads, drains, cable trench and tower
and equipment foundations as indicated in the drawing.
7.4
Over the base layer of site surfacing material, a final surface course of minimum 50
mm thickness of 20 mm nominal size (single size ungraded) broken stone as specified
above shall be spread and compacted by light roller using half tones steel roller (width
30" and 24" dia meter) with water sprinkling as directed by the Engineer-in-Charge.
The water shall be sprinkled in such a way that bulking does not take place.
7.5
7.6
Before taking up stone filling/brick soling, antiweed treatment shall be applied in the
switchyard area wherever stone filling/brick soling is to be done, and the area shall be
thoroughly de-weeded including removal of roots. The recommendation of local
agriculture or horticulture department shall be sought wherever feasible while choosing
the type of chemical to be used. Nevertheless the effectiveness of the chemical shall be
demonstrated by the Contractor in a test area of 10M x 10M (approx.) and monitored
over a period of two to three weeks by the Engineer-in-Charge. The final approval shall
be given by Engineer-in-Charge and final approval given based in the results.
7.7
8.0
SITE DRAINAGE
1.
2.
Adequate site drainage system shall be provided by the Contractor in new and
existing substation. In case of bay extension of existing substation, drainage
layout shall be prepared by the contractor in such away that it should satisfy the
technical parameters stated below while designing the drainage system so that
flow of water of the existing part of substation remain uninterrupted and the
same should be approved by the owner. The technical parameters stated below
also to be taken into account while designing the drainage system for new
substation as well.
The Contractor shall obtain rainfall data and design the storm water drainage
system, (culverts, ditches, drains etc.) to accommodate run off due to the most
intense rainfall that is likely to occur over the catchment area in one hour period
on an average of once in ten years. The surface of the site shall be sloped to
prevent the ponding of water.
.
The maximum velocity for pipe drains and open drains shall be limited to
2.4m/sec and 1.8m/sec respectively. However, minimum non-silting velocity of
0.6m/sec shall be ensured. Longitudinal bed slope shall not be milder than 1 in
1000.
Page 9 of 30
3.
9.0
For design of RCC pipes for drains and culverts, IS: 456 and IS: 783 shall be
followed.
4.
The Contractor shall ensure that water drains are away from the site area and
shall prevent damage to adjacent property by this water. Adequate protection
shall be given to site surfaces, roads, ditches, culverts, etc. to prevent erosion of
material by water.
5.
The drainage system shall be adequate without the use of cable/pipe trenches.
(Pipe drains shall be provided in areas of switchyard where movement of crane
will be necessary in operating phase of the substation).
6.
For pipe drains, concrete pipe of class NP2 shall be used. However, for road
crossings etc. higher strength pipe of class NP3 shall be provided. For rail
crossings, pipes conforming to railway loading standards or at least NP4 class
shall be provided. Manholes shall be provided at every 30m interval, at
connection points and at every change of alignment.
7.
8.
9.
Invert of the drainage system shall be decided in such a way that the water can
easily be discharged above the High Flood Level (HFL) outside substation
boundary at suitable location upto a maximum 50M beyond boundary wall of
substation or actual whichever occurs earlier and approved by Owner.
Contractor should provide Pumps for drainage of water (if required).
10.
11.
The main approach road including modification of existing road to meet the site
conditions, roads for access to equipment and buildings with in substations
(including bay extension in existing substations) are in the scope of bidder.
Layout of the roads shall be based on General detail & Arrangement drawing
for the substation. If extra road is required for functional point of view, which
has not been mentioned in the layout drawing, Contractor should provide the
same with out extra cost to the owner.
Page 10 of 30
10.0
2.
3.
4.
Adequate provision shall be made for road drainage. Protection of cut and
embankment slopes of roads as per slope stability requirement shall be made.
5.
All the culverts and its allied structure (required for road/rail, drain trench
crossings etc.) shall be designed for class A loading as per IRC standard / IS
code and should be checked for loading.
6.
All roads shall be designed for class C of traffic as per IRC-37 Guide-lines for
the design of flexible pavements.
TRANSFORMER FOUNDATION
The Contractor shall provide a road system integrated with the transformer foundation
to enable installation and the replacement of any failed unit by the spare unit located at
the site. This system shall enable the removal of any failed unit from its foundation to
the nearest road. If trench/drain crossings are required then suitable R.C.C. culverts
shall be provided in accordance with I.R.C. Code/relevant IS.
If existing/failed transformer is required to be replaced by new one in augmentation/bay
extension works of existing substations then the foundation supporting that equipment
shall be strengthen by modifying the foundation itself or the foundation shall be
dismantle and recast new foundation as suited by contractor. However, contractor must
furnish the design calculation incorporating all those changes so that safety of the
structure and foundation remain adequate.
Similarly all types of equipment foundations with /without supporting structures shall
be treated in similar manner as stated for transformer foundations.
Contractor must access the amount of work involve for augmentation/bay extension of
existing substations while quoting.
General
Fire protection walls shall be provided in accordance with Tariff Advisory Committee
(TAC) recommendations.
12.2
Application criteria
A firewall shall be erected between the transformers to protect each one from the
effects of fire on another as per TAC guidelines.
Also, if the free distance between the transformer, and auxiliary services transformers is
less.
Page 11 of 30
12.3
Fire resistance
The firewall shall have a minimum fire resistance of 3 hours. The partitions, which are
made to reduce the noise level, shall have the same fire resistance where the partitions
are also used as firewalls. The walls of the building, which are used as firewalls, shall
also have a minimum fire resistance of 3 hours.
The firewall shall be designed in order to protect against the effect of radiant heat and
flying debris from an adjacent fire.
12.6 Materials
The firewall may be made of reinforced concrete (M-20 grade), as per the system
requirements. Materials used must conform to the standards of the National Fire
Prevention Association & TAC norms.
13.0 CABLE & PIPE TRENCHES
1.
The cable trenches and precast removable RCC cover (with lifting arrangement)
shall be constructed using RCC of M20 grade for new substation whereas for
bay extension of existing substation size and material of cable trenches shall be
same as the existing one and precast removable RCC cover (with lifting
arrangement) shall be constructed using RCC of M20 grade. Cable trenches
must be designed for the design criteria stated below, whether it is of concrete
or brick for both new substations and bay extension works in existing
substations.
2.
The cable trench walls shall be designed for the following loads.
Page 12 of 30
(i)
(ii)
3.
Dead load of 100 kg/m length of cable support + 75 Kg on one tier at the
end.
Triangular earth pressure + uniform surcharge pressure of 1T/m2.
Cable trench covers shall be designed for self-weight of top slab + concentrated
load of 200 kg at centre of span on each panel.
4.
Cable trench crossing the road/rails shall be designed for class A. Loading of
IRC/relevant IS Code and should be checked for transformer loading.
5.
6.
7.
All metal parts inside the trench shall be connected to the earthing system.
8.
9.
Trench wall shall not foul with the foundation. Suitable clear gap shall be
provided.
10.
The trench bed shall have a slope of 1/500 along the run & 1/250 perpendicular
to the run.
11.
All the construction joints of cable trenches i.e. between base slab to base slab
and the junction of vertical wall to base slab as well as from vertical wall to wall
and all the expansion joints shall be provided with approved quality PVC water
stops of approx. 230 x 5 mm size for those sections where the ground water
table is expected to rise above the junction of base slab and vertical wall of
cable trenches.
12.
Cable trenches shall be blocked at the ends if required with brick masonry in
cement sand mortar 1:6 and plaster with 12mm thick 1:6 cement sand mortar.
13.
Cable trench contains cable trey that shall be supported on ISA. The size and
spacing of angle section shall be as per design criteria mentioned above.
However minimum internal dimension of cable trench is 750mm wide and 600
mm in depth.
14.0
14.1
General
1. Work covered under this Clause of the Specification comprises the design and
construction of foundations and other RCC constructions for switchyard structures,
Page 13 of 30
equipment supports, trenches, drains, jacking pad, control cubicles, bus supports,
transformer, marshalling kiosks, auxiliary equipments & systems, buildings, tanks,
boundary wall or for any other equipment or service and any other foundation
required to complete the work. This clause is as well applicable to the other RCC
constructions.
However, for the augmentation/bay extension works of existing substation, type of
RCC structures and foundations etc. shall be similar to one already existing at the
existing substation and for which design shall be furnished in support of safety of
those RCC structures and foundations etc. Contractor must access the amount of
work involved for the construction of switchyard structures, equipment supports,
trenches, drains, jacking pad, control cubicles, bus supports, transformer,
marshalling kiosks, auxiliary equipments & systems, buildings, tanks, boundary
wall or for any other equipment or service and any other foundation required to
complete the work for the existing substations.
2.
Concrete shall conform to the requirements mentioned in IS: 456 and all the
tests shall be conducted as per relevant Indian Standard Codes as mentioned in
Standard field quality plan appended with the specification
A minimum grade for PCC and RCC shall be used for all structural/loadbearing members as per latest IS 456.
3.
If the site is sloppy, the foundation height will be adjusted to maintain the exact
level of the top of structures to compensate such slopes.
4.
5.
Minimum 75mm thick lean concrete shall be provided below all underground
structures, foundations, trenches etc. to provide a base for construction.
6.
Concrete made with Portland slag cement shall be carefully cured and special
importance shall be given during the placing of concrete and removal of
shuttering.
7.
The design and detailing of foundations shall be done based on the approved
soil data and sub-soil conditions as well as for all possible critical loads and the
combinations thereof. The Spread footings foundation or pile foundation as may
be required based on soil/sub-soil conditions and superimposed loads shall be
provided.
8.
14.2
Design
1.
Foundations shall be of reinforced cement concrete for new substation but for
the augmentation / bay extension works of existing substation it could be of
RCC/ PCC / MASONRY depending on type of structures and materials used for
the similar type of structures in those bay extension works of existing
substation. Design requirement shall be fulfilled by the contractor and furnished
for approval for both new substation and existing substation (for bay extension
works) as specified in the scope of work. The design and construction of RCC/
PCC / Masonry structures shall be carried out as per IS: 456 and relevant IS
code/CBIP manual/NBC etc and minimum grade of concrete shall be as per
relevant IS code. Higher grade of concrete than specified above may be used at
the discretion of Contractor without any additional financial implication to the
Owner.
2.
Limit state method of design shall be adopted unless specified otherwise in the
specification.
3.
For detailing of reinforcement IS: 2502 and SP: 34 shall be followed. Cold
twisted deformed bars (Fe=415 N/mm2) conforming to IS: 1786 shall be used
as reinforcement. However, in specific areas, mild steel (Grade I) conforming to
IS: 432 can also be used. Two layers of reinforcement (on inner and outer face)
shall be provided for wall & slab sections having thickness more than 150 mm.
Clear cover to reinforcement towards the earth face shall be minimum 40 mm.
4.
RCC water retaining structures like storage tanks, etc. shall be designed as
uncracked section in accordance with IS: 3370 (Part I to IV) by working stress
method. However, water channels shall be designed as cracked section with
limited steel stresses as per IS: 3370 (Part I to IV) by working stress method.
5.
The procedure used for the design of the foundations shall be the most critical
loading combination of the steel structure and or equipment and/or
superstructure and other conditions, which produces the maximum stresses in
the foundation or the foundation component and as per the relevant IS Codes of
foundation design. Detailed design calculations shall be submitted by the bidder
showing complete details of piles/pile groups or isolated /combined footings
proposed to be used.
6.
Design shall consider any sub-soil water pressure that may be encountered
following relevant standard strictly.
7.
8.
RCC columns /pedestals shall be provided with rigid connection at the base.
9.
All sub-structures shall be checked for sliding and overturning stability during
both construction and operating conditions for various combinations of loads.
Factors of safety for these cases shall be taken as mentioned in relevant IS
Page 15 of 30
Earth pressure for all underground structures shall be calculated using coefficient of earth pressure at rest, co-efficient of active or passive earth pressure
(whichever is applicable).
11.
In addition to earth pressure and ground water pressure etc., a surcharge load of
2T/Sq.m shall also be considered for the design of all underground structures
including channels, sumps, tanks, trenches, substructure of any underground
hollow enclosure etc., for the vehicular traffic in the vicinity of the structure.
12.
Following conditions shall be considered for the design of water tank in pumps
house, channels, sumps, trenches and other underground structures:
a)
Full water pressure from inside and no earth pressure & ground water
pressure & surcharge pressure from outside (application only to structures,
which are liable to be filled up with water or any other liquid).
b)
Full earth pressure, surcharge pressure and ground water pressure from
outside and no water pressure from inside.
c)
Design shall also be checked against buoyancy due to the ground water
during construction and maintenance stages. Minimum factor of safety of
1.5 against buoyancy shall be ensured ignoring the superimposed loadings.
13.
The foundations shall be proportioned so that the estimated total and differential
movements of the foundations are not greater than the movements that the
structure or equipment is desinged to accommodate.
14.
15. The tower and equipment foundations shall be checked for a factor of safety of 2.0
for normal condition and 1.5 for short circuit condition against sliding, overturning
and pullout.
14.3
Only approved admixtures shall be used in the concrete for the Works. When
more than one admixture is to be used, each admixture shall be batched in its
own batch and added to the mixing water separately before discharging into the
mixer. Admixtures shall be delivered in suitably labeled containers to enable
identification.
2.
Admixtures in concrete shall conform to IS: 9103. The water proofing cement
additives shall conform to IS: 2645. Owner shall approve concrete Admixtures/
Additives.
Page 16 of 30
15.0
3.
The Contractor may propose and the Owner may approve the use of a waterreducing set-retarding admixture in some of the concrete. The use of such an
admixture will not be approved to overcome problems associated with
inadequate concrete plant capacity or improperly planned placing operations
and shall only be approved as an aid to overcoming unusual circumstances and
placing conditions.
4.
5.
The Gate frame shall be made of medium duty MS pipe conforming to relevant
IS with welded joints.
2.
The gates shall be fabricated with welded joints to achieve rigid connections.
The gate frames shall be painted with one coat of approved steel primmer and
two coats of synthetic enamel paint.
3.
Gates shall be fitted with approved quality iron hinges, latch and latch catch.
Latch and latch catch shall be suitable for attachment and operation of pad lock
from either side of gates. Hinges shall permit gates to swing through 180 degree
back against fence.
4.
Gates shall be fitted with galvanized chain hook or gate hold back to hold gates
open. Double gates shall be fitted with centre rest and drop bolt to secure gates
in closed position.
5.
Gates shall be installed in locations shown on drawings. Next to the main gate, a
men gate (1.25 m wide, Single leaf) shall also be provided.
6.
Bottom of gates shall be set approximately 40mm above ground surface and
necessary guiding mechanism shall be fitted.
7.
The contractor shall design and construct boundary wall around substation area
as per requirements. The boundary wall shall be of height 2.0 M and shall be
made of brick wall in cement sand mortar 1:6.The thickness of wall depends on
the design calculation produced by contractor and approved by owner. The
boundary wall shall be plastered on both external and internal faces with cement
sand plaster 1:6 of thickness 18 mm and 12 mm respectively. An additional
barbed Y-shaped arm of MS angle 50x50x6 with 3-rows (6nos) barbed wire A4IS: 278. Expansion joints shall be provided as per codal requirements. MS
grating shall be provided at required locations for drainage purposes. Top and
bottom side of MS grating shall be supported on concrete block or beam. The
boundary wall shall be painted with minimum two coats of colour wash over a
base coat of white wash with lime. The steel work shall be given two coats of
synthetic enamel paint of approved make over one coat of primer. A tentative
drawing is enclosed for guidance purpose.
Page 17 of 30
8.
16.0
16.1
General
The scope for new control room building includes the design, engineering and
construction including anti-termite treatment, plinth protection, DPC of Building
including sanitary, water supply with Boring, provision of Motor, water tank and other
necessary sanitary installations, electrification, false ceiling etc. of control room
building. The buildings shall be of RCC framed structure of concrete of M20 grade
(Min.). Following design criteria shall be adopted for design purposes for new
substation.
If any extension of the Control Room building is required in augmentation / bay
extension works of existing substation then extension part shall be compatible to
existing one structurally and architecturally but following design criteria shall be
adopted for design purposes for R&M of existing substation.
16.2
16.2.1 Design
a)
2.
3.
4.
5.
For a life expectancy of structure, systems and components not less than
that of the equipment, which is contained in the building, provided
regular maintenance is carried out.
6.
7.
8.
With, wherever required, fire retarding materials for walls, ceilings and
doors, which would prevent supporting or spreading of fire.
9.
b)
c)
d)
e)
All cable vaults shall be located above ground levels i.e. cable vaults
shall not be provided as basements in the buildings.
f)
g)
Page 19 of 30
Super-imposed loads in different areas shall include live loads, minor equipment
loads, cable trays, small pipe racks/hangers and erection, operation and maintenance
loads. Equipment loads shall constitute, if applicable, all load of equipments to be
supported on the building frame.
For crane loads an impact factor of 30% and lateral crane surge of 10% (lifted weight
+ trolley) shall be considered in the analysis of frame according to provisions of IS:
875. The horizontal surge shall be 5% of the static wheel load.
The wind loads shall be computed as per IS 875, Seismic Coefficient method shall be
used for the seismic analysis as per IS 1893 with importance factor 1.5.
For temperature loading, the total temperature variation shall be considered as 2/3 of
the average maximum annual variation in temperature. The average maximum annual
variation in temperature for the purpose shall be taken as the difference between the
mean of the daily minimum temperature during the coldest month of the year and
mean of daily maximum temperature during the hottest month of the year. The
structure shall be designed to withstand stresses due to 50% of the total temperature
variation.
Wind and Seismic forces shall not be considered to act simultaneously.
Floors/slabs shall be designed to carry loads imposed by equipment, cables piping
travel of maintenance trucks and equipment and other loads associated with building.
Floors shall be designed for live loads as per relevant IS. Cable and piping loads shall
also be considered additionally for floors where these loads are expected.
In addition, beams shall be designed for any incidental point loads to be applied at any
point along the beams. The floor loads shall be subject to Owners approval.
For consideration of loads on structures, IS: 875 shall strictly adhere to. Any other
load coming in the structure, not mentioned in IS 875 shall be calculated as per
relevant IS code and NBC.
16.2.3 Submission
The following information shall be submitted for review and approval to the Owner:
1.
Design criteria shall comprise the codes and standards used, applicable climatic
data including wind loads, earthquake factors maximum and minimum
temperatures applicable to the building locations, assumptions of dead and live
loads, including equipment loads, impact factors, safety factors and other
relevant information.
2.
3.
4.
5.
6.
7.
A door & window schedule showing door types and locations, door lock sets
and latch sets and other door hardware.
Flooring
Flooring in various rooms of control room building shall be as for detailed schedules
given in Table 1
16.2.6 Walls
Control room buildings shall be of framed superstructure. All walls shall be non-load
bearing walls. Min. thickness of external walls shall be 230 mm (one brick) with 1:6
cement sand mortar.
16.2.7
Plastering
All internal walls shall have minimum 12mm and 15 mm thick 1:6 cement sand
plaster on either side of wall. The ceiling shall have 6mm thick 1:4 cement sand
plaster.
16.2.8
Finishing
All external surfaces shall have 18 mm cement plaster in two coats, under layer 12
mm thick cement plaster 1:5 and finished with a top layer 6 mm thick cement plaster
1:6 (DSR 13.19) with water proofing compound. The paint shall be antifungal quality
of reputed brand suitable for masonry surfaces for high rainfall zone. White cement
primer shall be used as per manufacturers recommendation.
Page 21 of 30
Sl.No.
1.
2.
3.
4.
Location
Control Room,
Relay Room
Sub-station
Incharge, Office,
corridor, staff
room.
Battery room
Toilet
Flooring &
Skirting
150mm high
Precast
Terrazo tiles
(DSR02,
item no.
11.29A.2 &
11.31.2
Precast
Terrazo tiles
(DSR02,
item no.
11.29A.2 &
11.31.2
Acid and
Alkali
Resistant tiles.
DSR02
11.36 C. 1 &
11.36 C.1.1
Ceramic
glazed tiles in
flooring
DSR02
11.74
Wall Internal
Ceiling
White
Wash
(DSR02
13.70.1)
Dado of acid
resistant tile 1.2 M
high & Paint above
1.2 M to ceiling.
DSR02 11.36 C.
2.1, 11.36C.2 &
13.96.1
Acid
resistant
Paint.
DSR02
13.96.1
Doors, Windows,
Ventilators
White
Wash
(DSR02
13.70.1)
White
Wash
(DSR02
13.70.1)
5.
Terrazo tiles
(DSR02 11.29A.2 &
11.31.20
Oil bound
distemper,
DSR02 - 13.40A
& 13.77
White
Wash
(DSR02
13.70.1)
Note : DSR item references (DSR-2002) to be read with CPWD specifications are only for
material and workmanship guidance of the Contractors.
Page 22 of 30
16.2.9
Roof
Roof of the C.R. Building shall consist of Cast-in-situ RCC slab treated with a water
proofing system which shall be an integral cement based treatment conforming to
CPWD specification (item no. 25.8 of DSR 1997). The water proofing treatment shall
be of following operations:
(a) Applying and grouting a slurry coat of neat cement using 2.75 kg/m 2 of cement
admixed with proprietary water proofing compounds conforming to IS: 2645 over
the RCC slab including cleaning the surface before treatment.
(b) Laying cement concrete using broken bricks/brick bats 25mm to 100mm size with
50% of cement mortar 1:5 (1 cement: 5 coarse sand) admixed with proprietary
water proofing compound conforming to IS: 2645 over 20mm thick layer of
cement mortar of min 1:5 (Cement: 5 coarse sand) admixed with proprietary water
proofing compound conforming to IS: 2645 to required slope and treating similarly
the adjoining walls upto 300mm height including rounding of junctions of walls
and slabs.
(c) After two days of proper curing applying a second coat of cement slurry admixed
with proprietary water proofing compound conforming to IS: 2645.
(d) Finishing the surface with 20mm thick joint less cement mortar of mix 1:4 (1
cement: 4 course sand) admixed with proprietary water proofing compound
conforming to IS: 2645 and finally finishing the surface with trowel with neat
cement slurry and making of 300 x 300 mm square.
(e) The whole terrace so finished shall be flooded with water for a minimum period of
two weeks for curing and for final test. All above operations to be done in order
and as directed and specified by the Engineer-in-charge.
With average thickness of 120 mm and minimum thickness at khurra at 65 mm.
16.2.10
Glazing
Minimum thickness of glazing shall be 5.5 mm. as per IS: 2835 Sun film shall be
provided for all windows/doors of AC rooms if any.
16.2.11
All plumbing and sanitation shall be executed to comply with the requirements
of the appropriate byelaws, rules and regulations of the Local Authority having
jurisdiction over such matters. The Contractor shall arrange for all necessary
Page 23 of 30
(iii)
Galvanized MS pipe of medium class conforming to IS: 1239 shall be used for
internal & external piping work for potable water supply.
(iv)
Sand CI pipes with lead joints conforming to IS: 1729 shall be used for sanitary
works above ground level.
(v)
(c)
(d)
(e)
(f)
(vi)
(vii)
All sanitary fixtures and fittings shall be of approved quality and type
manufactured by well known manufacturers. All items brought to site must bear
identification marks of the type of the Manufacturer.
(viii)
Soil, waste and drain pipes, for underground works shall be stoneware for areas
not subject to traffic load. Heavy-duty cast iron pipes shall be used otherwise.
(ix)
17.0
17.1
Dense concrete with controlled water cement ratio as per IS-code shall be used for all
underground concrete structures such as pump-house, tanks, water retaining structures,
cable and pipe trenches etc. for achieving water-tightness.
17.2
All joints including construction and expansion joints for the water retaining structures
shall be made water tight by using PVC ribbed water stops with central bulb.
However, kicker type (externally placed) PVC water stops shall be used for the base
Page 24 of 30
slab and in other areas where it is required to facilitate concreting. The minimum
thickness of PVC water stops shall be 5 mm and minimum width shall be 230 mm.
17.3
All steel sections and fabricated structures that are required to be transported on sea
shall be provided with anti corrosive paint to take care of sea worthiness.
17.4
All mild steel parts used in the water retaining structures shall be hot-double dip
galvanised. The minimum coating of the zinc shall be 750 gm/sq. m. for galvanised
structures and shall comply with IS: 2629 and IS: 2633. Galvanizing shall be checked
and tested in accordance with IS: 2633.The galvanizing shall be followed by the
application of an etching primer and dipping in black bitumen in accordance with BS:
3416.
17.5
A screed concrete layer not less than 100 mm thick and of grade not weaker than M10
conforming to IS: 456-1978 shall be provided below all water retaining structures. A
sliding layer of bitumen paper or craft paper shall be provided over the screed layer to
destroy the bond between the screed and the base slab concrete of the water retaining
structures.
17.6
Bricks having minimum 75kg/cm2 compressive strength can only be used for masonry
work. Contractor shall ascertain himself at site regarding the availability of bricks of
minimum 75kg/cm2 compressive strength before submitting his offer.
17.7
Doors and windows on external walls of the buildings (other than areas provided, with
insulated metal claddings) shall be provided with RCC sunshade over the openings
with 300 mm projection on either side of the openings. Projection of sunshade from
the wall shall be minimum 450 mm over window openings and 750 mm over door
openings.
17.8
17.9
Angles 45x45x5 mm (minimum) with lugs shall be provided for edge protection all
round cut outs/openings in floor slab, edges of drains supporting grating covers, edges
of RCC cable/pipe trenches supporting covers, edges of manholes supporting covers,
supporting edges of manhole precast cover and any other place where breakage of
corners of concrete is expected.
17.10
Anti termite chemical treatment shall be given to column pits, wall trenches,
foundations of buildings, filling below the floors etc. as per IS: 6313 and other
relevant Indian Standards.
17.11
All rungs for ladder shall also be galvanised as per IS: 277 medium classes.
17.12
For all civil works covered under this specification, nominal mix by volume batching
as per CPWD specification is intended. The relationship of grade of concrete and
ratio of ingredients shall be as below:
-----------------------------------------------------------------------------------------Sl.No.
Mix
Cement
Page 25 of 30
Sand
Coarse aggregate of
20 mm down grade
as per IS 383
-----------------------------------------------------------------------------------------1.
M 10
1
3
6
2.
M 15
3.
M 20
1.5
The details given in tender drawings shall be considered along with details available
in this section of the specification while deciding various components of the building.
17.14
18.0
INTERFACING
The proper coordination & execution of all interfacing civil works activities like fixing
of conduits in roofs/walls/floors, fixing of foundation bolts, fixing of lighting fixtures,
fixing of supports/embedment, provision of cutouts etc. shall be the sole responsibility
of the Contractor. He shall plan all such activities in advance and execute in such a
manner that interfacing activities do not become bottlenecks and dismantling,
breakage etc. is reduced to minimum.
19.0
WATER SUPPLY
(i)
(ii)
The contractor shall carry out all the plumbing/erection works required for
supply of water in control room building; the water supply shall include the
boring, provision of Motor, water tank and other necessary sanitary
installations.
(iii)
The details of tanks, pipes, fittings, fixtures etc for water supply are given
elsewhere in the specification under respective sections.
(iv)
A scheme shall be prepared by the contractor indicating the layout and details of
water supply which shall be got approved by the Owner before actual start of
work including all other incidental items not shown or specified but as may be
required for complete performance of the works.
(v)
Bore wells and pumps for water supply are in the scope of contractor meeting
the day-to-day requirement of the water supply.
If the water is supplied by Municipal Corporation then bore well for water
supply purposes is not required to be carried out by contractor. Contractor shall
also make necessary arrangement /formalities to receive water connection from
corporation.
(vi)
Page 26 of 30
20.0
SEWERAGE SYSTEM
(i)
(ii) The Contractor shall construct septic tank and soak pit suitable for 5 users if
outside of Municipal Corporation zone. Otherwise, all necessary arrangement for the
disposal of sewerage to the Municipal Corporations end shall be arranged by the
contractor at his own cost for regularizing the disposal activity.
(iii)
21.0
STATUTORY RULES
21.1
Contractor shall comply with all the applicable statutory rules pertaining to factories
act (as applicable for the State). Fire Safety Rules of Tariff Advisory Committee,
Water Act for pollution control etc.
21.2
Provisions for fire proof doors, no. of staircases, fire separation wall, plastering on
structural members (in fire prone areas) etc. shall be made according to the
recommendations of Tariff Advisory Committee.
21.3
Statutory clearance and norms of State Pollution Control Board shall be followed as
per Water Act for effluent quality from plant.
21.4
Requirement of sulphate resistant cement (SRC) for sub structural works shall be
decided in accordance with the Indian Standards based on the findings of the detailed
soil investigation to be carried out by the Bidder.
21.5
Foundation system adopted by Bidder shall ensure that relative settlement and other
criteria shall be as per provision in IS: 1904 and other Indian Standards.
21.6
All water retaining structures designed as uncracked section shall also be tested for
water tightness at full water level in accordance with clause no. 10 of IS: 3370 (Part-I).
21.7
21.8
All underground concrete structures like basements, pumps houses, water retaining
structures etc. shall have plasticizer cum water proofing cement additive conforming
to IS: 9103. In addition, limit on permeability as given in IS: 2645 shall also be met
with. The concrete surface of these structures in contact with earth shall also be
provided with two coat of bituminous painting for water/damp proofing. In case of
water leakage in the above structures, Injection Method shall be applied for repairing
the leakage.
All building/construction materials shall conform to the best quality specified in
CPWD specifications if not otherwise mentioned in this specification.
21.9
21.10 All tests as required in the standard field quality plans have to be carried out.
22.1 General
Fencing of the distribution transformer shall be designed for the most critical loading
combination taking care of wind force, stability, tension on wires, minimum
requirements as per this clause and relevant IS recommendations.
22.2
22.3
Size of mesh
75 mm
2.
3.15 mm dia
3.
2000 mm
4.
medium
5.
21.3.2 Posts
Angle Section
Intermediate
: L 50 x 50 x 6
Straining posts
: L 65 x 65 x 6
Stay post
: L 50 x 50 x 6
1. All structural steel shall conform to IS: 2062 and shall be painted with a coat of
approved steel primer and two coats of synthetic enamel paint.
2. The Chain Link fabric shall be fixed to the post at the top and bottom of the fence by
welding/fixing 50 mm MS flat all through its length.
3. Fencing top shall be either of galvanised barbed wire or tape. Barbed wire shall
conform to IS: 278.
4. The barbed wire may consist of not more than two splices per reel. The barbed wire
shall be formed by twisting two line wires, one containing the barbs. The barbed wire
shall be designated as A-4 IS: 278 and shall be galvanized.
Page 28 of 30
5. Above chain link, 3-rows (6 nos) of barbed tape/wire shall be provided in each arm of
the Y shaped barbed arm at top.
6. With barbed tape/wire above the chain link fence, the total fence height shall be
minimum 2000 mm above finished gravel level.
7. Barbed tape/wire arms shall be same as intermediate and straining post.
8. Tension wire: single strand, high tensile, galvanised steel wire, 4 mm diameter.
9. Fittings and hardware: cast aluminum alloy or galvanized steel, malleable or ductile
cast iron turnbuckles to be drop forged.
10. For every 50 reels or part there of samples of the barbed wire/tape and the individual
line wires shall be put to tensile test and in case of failure to conform to the tensile
properties given below, two additional tests of each kind shall be made on the samples
cut from other reels.
11. GI chain link mesh shall be as per IS: 2721. Mesh size 75 mm and nominal wire size
shall be 3.15 mm diameter.
Tensile properties
Tensile strength of line wire
40 to 60Kgs/Sq.mm
375Kgs.
On the results of these additional tests, the whole or portion of the barbed
wire/tape shall be accepted or discarded by the Purchaser, as the case may be.
22.4
INSTALLATION
1.
Contractor shall submit the fencing drawing Fence shall be installed along lines
shown on approved drawings.
2.
3.
4.
5.
6.
All corner post will have two-stay post and every tenth post will have a
transverse stay post.
7.
Posts shall be set in 1:2:4 plain cement concrete Blocks of minimum dimension
400 mm x 400 mm x 1000 mm deep Concrete work shall conform to relevant
Page 29 of 30
clause. Post shall be braced and held in plumb position and true alignment and
elevation until concrete has set.
8.
Fence fabric shall not be installed until concrete has cured a minimum of 7
days.
9.
Bottom and top of the fence fabric shall be fixed with MS flats of 50 mm x
6mm (min).
10.
Fence fabric shall be laid out with barbed edge on top, stretched tightly and
shall be fastened to intermediate, post gate and straining post with 50 x 6 flats.
11.
Fabric shall be secured to tension wires with tie wires at 400 mm intervals. Tie
wires shall be given not less than two twists.
12.
13.
14.
Barbed tape shall be attached to barbed wire arms with approved metal clips.
15.
Toe wall of one Brick/Random Rubble masonry, with notches over 75 mm thick
PCC (1:4:8) shall be provided below all fencing and shall be minimum 200 mm
above and 200 mm below finished ground level. All exposed surfaces of brick
toe wall shall be provided with 1:6 cement sand plaster and coated with two
coats of colour wash with a base coat of white wash with lime. Rubble masonry
toe wall shall be with raised & cut pointing and 50 mm PCC (1:2:4) band
coping.
Page 30 of 30
1.
7.1.0. SCOPE
7.1.1.
horizontal/vertical
7.1.3. Isolators shall be supplied with Earth Switch as and where specified.
7.2.0. GENERAL
7.2.1. The Isolators and accessories shall conform in general to IS 9921 (or IEC:
62271-102) except to the extent explicitly modified in specification.
7.2.2. All isolating switches and earthing switches shall have rotating blades and
pressure releasing contacts. All isolating and earth switches shall op erate through
90 angle from closed position to fully open position.
7.2.3. Complete isolator with all the necessary items for successful operation shall be
supplied including but not limited to the following:
(i). Isolator assembled with complete base frame, linkages, operating mechanism,
control cabinet, interlocks etc.
(ii). All necessary parts to provide a complete and operable isolator installation,
control parts and other devices whether specifically called for herein or not.
(iii). The isolator shall be designed for use in the geographic and meteorological
conditions as given in Section 1.
7.3.0. DUTY REQUIREMENTS
7.3.1. Isolators and earth switches shall be capable of withstanding the dynamic and
thermal effects of the maximum possible short circuit current of the systems in their
closed position. They shall be constructed such that they do not open under influence
of short circuit current.
7.3.2. The earth switches, wherever provided, shall be constructionally interlocked so
that the earth switches can be operated only when the isolator is open and vice
Page | 1
Page | 2
a) All metal parts shall be of non-rusting and non-corroding material. All current
carrying parts shall be made from high conductivity electrolytic
copper/aluminium. Bolts, screws and pins shall be provided with lock washers.
Keys or equivalent locking facilities if provided on current carrying parts, shall
be made of copper silicon alloy or stainless steel or equivalent. The bolts or
pins used in current carrying parts shall be made of non-corroding material. All
ferrous castings except current carrying parts shall be made of malleable cast
iron or cast-steel. No grey iron shall be used in the manufacture of any part of
the isolator.
b) The live parts shall be designed to eliminate sharp joints, edges and other
corona producing surfaces, where this is impracticable adequate corona
shield shall be provided..
c) Isolators and earthing switches including their operating parts shall be such that
they cannot be dislodged from their open or closed positions by short circuit
forces, gravity, wind pressure, vibrations, shocks, or accidental touching of the
connecting rods of the operating mechanism.
d) The switch shall be designed such that no lubrication of any part is required
except at very infrequent intervals i.e. after every 1000 operations or after 5
years whichever is earlier.
7.4.4. Insulators:
a) The insulator shall conform to IS: 2544 and/or IEC-60168. The insulators shall
have a minimum cantilever strength of 400 Kgs. for 33/11 kV insulators
respectively.
b) Pressure due to the contact shall not be transferred to the insulators after the
main blades are fully closed.
7.4.5. Base:
Each isolator shall be provided with a complete galvanised steel base provided with
holes and designed for mounting on a supporting structure.
7.5.0. EARTHING SWITCHES
7.5.1. Where earthing switches are specified
operating mechanism and auxiliary contacts.
these
shall
include
the
complete
7.5.2. The earthing switches shall form an integral part of the isolator and shall be mounted
on the base frame of the isolator.
7.5.3. The earthing switches shall be constructionally interlocked with the isolator so
that the earthing switches can be operated only when the isolator is open and
vice ve rsa. The constructional interlocks shall be built in construction of isolator
and shall be in addition to the electrical interlocks.
Page | 3
Each earth switch shall be provided with flexible copper/aluminum braids for
connection to earth terminal. These braids shall have the same short time current
carrying capacity as the earth blade. The transfer of fault current through swivel
connection will not be accept ed.
7.5.5. The frame of each isolator and earthing switches shall be provided with two reliable
earth terminals for connection to the earth mat.
7.5.6. Isolator design shall be such as to permit addition of earth switches at a future
date. It should be possible to interchange position of earth switch to either side.
7.5.7. The earth switch should be able to carry the same fault current as the main blades of
the Isolators and shall withstand dynamic stresses.
7.6.0. OPERATING MECHANISM
7.6.1. The bidder shall offer manual operated Isolators and earth switches..
7.6.2. Control cabinet/operating mechanism box shall be made of aluminum sheet of
adequate thickness (minimum 3 mm).
7.6.3. Gear should be of forged material suitably chosen to avoid bending/jamming on
operation after a prolonged period of non-operation. Also all gear and connected
material should be so chosen/surface treated to avoid rusting.
7.7.0. OPERATION
7.7.1. The main Isolator and earth switches shall be gang operated.
7.7.2.
The design shall be such as to provide maximum reliability under all service
conditions. All operating linkages carrying mechanical loads shall be designed for
negligible deflection. The length of inter insulator and interpole operating rods shall
be capable of adjustments, by means of screw thread which can be locked with a
lock nut after an adjustment has been made. The isolator and earth switches shall be
provided with over center device in operating mechanism to prevent accidental
opening by wind, vibration, short circuit forces or movement of the support structures.
7.7.3. Each isolator and earth switch shall be provided with a manual operating handle
enabling one man to open or close the isolator with ease in one movement while
standing at ground level. Detachable type manual operating handle shall be provided.
Suitable provision shall be made inside the operating mechanism box for parking
the detached handles. The provision of manual operation shall be located at a
height of 1000 mm from the base of isolator support structure.
7.7.4. The isolator shall be provided with positive continuous control throughout the entire
cycle of operation. The operating pipes and rods shall be sufficiently rigid to maintain
Page | 4
positive control under the most adverse conditions and when operated in tension or
compression for isolator closing. They shall also be capable of withstanding all torsional
and bending stresses due to operation of the isolator. Wherever supported the
operating rods shall be provided with bearings on either ends. The operating rods/
pipes shall be provided with suitable universal couplings to account for any angular
misalignment.
7.7.5. All rotating parts shall be provided with grease packed roller or ball bearings in
sealed housings designed to prevent the ingress of moisture, dirt or other foreign
matter. Bearings pressure shall be kept low to ensure long life and ease of operation.
Locking pins wherever used shall be rustproof.
7.7.6. Signaling of closed position shall not take place unless it is certain that the
movable contacts, have reached a position in which rated normal current, peak
withstand current and short time withstand current can be carried safely. Signaling of
open position shall not take place unless movable contacts have reached a position
such that clearance between contacts is atleast 80% of the isolating distance.
7.7.7. The position of movable contact system (main blades) of each of the Isolators and
earthing switches shall be indicated by a mechanical indicator at the lower end of the
vertical rod of shaft for the Isolators and earthing switch. The indicator shall be of
metal and shall be visible from operating level.
7.7.8. The contractor shall furnish the following details along with quality norms, during
detailed engineering stage.
(i) Current transfer arrangement from main blades of isolator along with
millivolt drop immediately across transfer point.
(ii)
Dielectric test (impulse and one minute) power frequency withstands voltage.
Page | 5
Page | 6
SL No.
1
2
3
Type of Isolator
5
6
7
8
10
11
Isolators class
Technical Particulars
33 kV
33
36
50
800
25
11kV
11
12
50
Double Break,
center pole
rotating
800
25
170
195
75
85
70
80
28
32
900
400
Double Break,
center pole rotating
Page | 7
As per relevant IS
Specification of LTDB
1.0 Box Specification
1.1 The LT Distribution Box (LTDB) of adequate size not less than 850 mm x 650 mm shall
be provided with suitable mounting arrangements for fixing on DSS struture.
1.2 The LTDB will be made of MS Sheet of thickness 18 SWG for LTDB and 16 SWG for
Gland Plate and powder coating of 40-45 microns of Siemens grey shade after surface
pre-treatment. Pad locking bracket and common key lock (inside) will be provided with
insulated handle on front door.
1.3 LTDB shall conform to IP-55 degree of arrangement except for three opening, two for
transformer bushing and one key hole.
1.4 FSS may be embossed on the front cover of the LTDB and name plate to be provided on
LTDB.
1.5 Adequate size of fixed Glass window to be provided on the LTDB for taking the reading
of energy meter installed inside the LTDB.
1.6 Suitable arrangement shall be provided for installation of the following
equipments/materials inside LTDB.
(i)
MCCB
Capacity as per DT rating.
(ii)
Energy Meter
(iii)
CTs
(iv)
Copper Bus Bars Separate for incoming & outgoing
1.7 Suitable arrangement shall be made on the front cover of LTDB such that MCCB can be
operated without opening the LTDB Cover.
2.0 Bus Bar Specification
3.0
4.0
5.0
6.0
Separate Bus bars for incoming line from DT and for outgoing line from LTDB shall be
provided.
Copper Bus Bars of following size may be provided.
Cu Bus Bars for phase & Neutral - 25mmx4mm - 8 Nos.
Other materials to be provided are as follows :(i)
Body earth terminals M 8x40 - 2Nos
(ii)
MCCB 63A, 25kA,
Fixed TP - 1 No.
(iii)
DMC insulator for Bus bar support - 3 Nos. per Bus bar.
CANOPY
A Canopy is to be provided with slanting roof to protect from rain water.
Danger Plate to be provided on LTDB.
Drawings indicating all the above may be got approved by BSPHCL.
Page 1 of 1
GENERAL
1.1
2.0
2.1
For design of steel structures loads such as dead loads, live loads, wind loads
etc. shall be based on IS: 875,Parts I to V.
2.2
For materials and permissible stresses IS: 802,Part-I, Section-2 for angle section
and for other types (like ISMB, ISLC T-section etc.) IS: 800 shall be followed
in general. However, additional requirements given in following paragraphs
shall be also considered.
2.3
Other members
Page 1 of 6
Redundant members
2.4
Maximum slenderness ratios for leg members, other stressed members and
redundant members for compression force shall be as per IS-802 for angle
sections otherwise IS: 800 shall be adopted for ISMB, ISLC, etc.
2.5
Minimum distance from hole center to edge shall be 1.5 x bolt diameter.
Minimum distance between center to center of holes shall be 2.5-x bolt
diameter.
The minimum bolt diameter shall be 12 mm. and welding shall be as per
IS:
816.
2.6
2.7
Step Bolts
In order to facilitate inspection and maintenance, the structures shall be
provided with climbing devices. Each tower shall be provided with step bolts
not less than 16mm diameter & 175mm long spaced not more than 450mm
apart, staggered on faces on one leg extending from about 0.5 meters above
ground level to the top of the tower. The step bolt shall conform to IS: 10238.
Ladders on towers with lighting appliances shall be provided with safety guards.
2.8
Design Criteria
a) All structures shall be designed for the worst combination of dead loads,
superimpose equipment load, live loads, wind loads as per code IS: 875,
seismic forces as per code IS: 1893 (latest), Importance factor of 1.5, loads
due to deviation of conductor, load due to unbalanced tension in conductor,
torsional load due to unbalanced vertical and horizontal forces, erection
loads, short circuit forces. Short circuit forces shall be calculated
considering a fault level of 25.0 kA. IEC-865 may be followed for
evaluation of short circuit forces.
b)
Switchyard gantry structures shall be designed for the two conditions i.e.
normal condition and short circuit condition. In both conditions the
design of all structures shall be based on the assumption that stringing is
done only on one side i.e. all the three (phase) conductors broken on the
other side.
Factor of safety of 2.0 under normal conditions and 1.5 under short
circuit condition shall be considered on all external loads for the design
of switchyard structures which are of lattice i.e. type using angle section.
c)
Vertical load of half the span of conductors/string and the earth wires on
either side of the beam shall be taken into account for the purpose of
design. Weight of man with tools shall be considered as 80 kgs. for the
design of structures.
d)
The distance between terminal gantry and dead end tower shall be taken
as 150 metres. The design of these terminal gantries shall also be
checked considering +/- 15 deg deviation of conductor in both vertical
Page 2 of 6
f)
All support used for supporting equipments shall be designed for the
worst combination of dead loads, erection load, Wind load / seismic
forces, short circuit forces and operating forces acting on the equipment
and associated bus bars as per IS: 806. The material specification shall
be as per IS: 1161 read in conjunction with IS: 806.
g)
Foundation bolts shall be designed for the loads for which the structures
are designed.
3.0
3.1
The Contractor shall furnish design, drawing and BOMs and shop
manufacturing drawings for every member to the Purchaser after award of the
Contract. However, Contractor shall have to prepare and submit any other
drawings, bill of materials (BOM) additionally required during design and
construction stage which the Purchaser feels necessary. In case Purchaser feels
that any design drawing, BOM are to be modified even after its approval,
Contractor shall modify the designs & drawings and resubmit the design
drawing, BOM as required in the specification.
3.2
3.3
The fabrication work shall start only after the final approval to the Fabrication
drawing is accorded by the Purchaser. The design drawing should indicate not
only profile, but section, numbers and sizes of bolts and details of typical joints.
3.4
Such approval shall, however, not relieve the Contractor of his responsibility for
the safety of the structure and good connections and any loss or damage
occurring due to defective fabrication, design or workmanship shall be borne by
the Contractor.
4.0
4.1
The fabrication and erection works shall be carried out generally in accordance
with IS 802. A reference however may be made to IS 800 in case of nonstipulation of some particular provision in IS 802. All materials shall be
completely shop fabricated and finished with proper connection material and
erection marks for ready assembly in the field.
Page 3 of 6
5.0
PROTO-ASSEMBLY
i)
The component parts shall be assembled in such a manner that they are
neither twisted nor otherwise. In order to minimize distortion in member
the component parts shall be positioned by using clamps, clips, dogs,
jigs and other suitable means and fasteners (bolts and welds) shall be
placed in a balanced pattern. If the individual components are to be bolted, paralleled and tapered drifts shall be used to align the part so that the
bolts can be accurately positioned.
ii)
6.0
BOLTING
i)
ii)
iii)
Every bolt shall be provided with a washer under the nut so that no part
of the threaded portion of the bolt is within the thickness of the parts
bolted together.
All steel items, bolts, nuts and washers shall be hot dip galvanised.
2.0% extra nuts and bolts shall be supplied for erection.
7.0
WELDING
2.7
The work shall be done as per approved fabrication drawings which clearly
indicate various details of joints to be welded, type of weld, length and size of
weld. A symbol for welding on erection and shop drawings shall be according
to IS: 813. Efforts shall be made to reduce site welding so as to avoid improper
joints due to constructional difficulties. Welding shall be done as per IS: 816.
8.0
FOUNDATION BOLTS
8.1
Foundation bolts for the towers and equipment supporting structures and
elsewhere shall be embedded in first stage concrete while the foundation is cast.
The Contractor shall ensure the proper alignment of these bolts to match the
holes in the base plate.
8.2
The Contractor shall be responsible for the correct alignment and leveling of all
steel work on site to ensure that the towers/structures are plumb.
8.3
All foundation bolts for steel structures, pipe structures are to be supplied by the
Contractor.
Page 4 of 6
8.4
All foundation bolts shall be fully galvanised so as to achieve 0.61 kg. per Sq.m.
of Zinc Coating as per specifications.
8.5
All foundation bolts shall conform to IS 5624 but the material, however shall be
MS conforming to IS: 2062.
9.0
STABILITY OF STRUCTURE
The Supplier shall be responsible for the stability of the structure at all stages of
its erection at site and shall take all necessary measures by the additions of
temporary bracings and guying to ensure adequate resistance to wind and also to
loads due to erection equipment and their operations.
10.0
GROUTING
The method of grouting the column bases shall be subject to approval of
Purchaser and shall be such as to ensure a complete uniformity of contact over
the whole area of the steel base. The Contractor will be fully responsible for the
grouting operations. Grouting shall be done only after the erection and
alignment have been checked and approved by the purchaser.
11.0
GALVANISING
11.1
All structural steel works and pipe supports shall be galvanised after fabrication.
11.2
11.3
12.0
TOUCH-UP PAINTING
The touch up primers and paints shall consist of Red Oxide / Zinc chromate
conforming to the requirements of IS: 2074 with a pigment to be specified by
the Purchaser.
13.0
14.0
TEST CERTIFICATE
Copies of all test certificates relating to material procured by the Contractor for
the works shall be forwarded to the Purchaser.
15.0
ERECTION
Page 5 of 6
The Contractor should arrange on his own all plant and equipment, welding set,
tools and tackles, scaffolding, trestles equipments and all other accessories and
ancillaries required for carrying out erection without causing any stresses in the
members which may cause deformation and permanent damage.
16.0
SAFETY PRECAUTIONS
The Contractor shall strictly follow at all stages of fabrication, transportation
and erection of steel structures, raw materials and other tools and tackles, the
stipulations contained in Indian Standard Code for Safety during erection of
structural steel work-IS: 7205.
17.0
18.0
All tests mentioned in standard field quality plans have to be carried out and
conformity of materials and workmanship shall be ascertained.
Page 6 of 6
LIGHTING SYSTEM
1.0
SCOPE
The scope of work comprises of design, engineering, testing, supply, installation, site testing
and commissioning of various lighting fixtures complete with lamps, supports and
accessories, ceiling fans complete with regulators & accessories, lighting panels, lighting
poles complete with distribution boxes, galvanized rigid steel conduits, lighting wires, G.I.
Earth wire, receptacles, switchboards, switches, junction boxes, pull out boxes complete with
accessories.
1.1
All lighting fixtures shall be mounted on the structures and control room buildings and Main
Gate etc.. No tubular lighting poles shall be used for this purpose.
2.0
SYSTEM DESCRIPTION
The lighting system shall comprise of the following:
2.1
AC Normal Lighting
AC lights will be connected to AC lighting panels. All the lights connected to the AC lighting system in different areas will be connected to the main lighting distribution boards to be
supplied.
2.2
2.3
A few DC emergency lighting fixtures operated on the DC system will be provided in the
strategic locations including control room, battery room etc. These lights will be normally
'OFF' and will be switched 'ON' automatically when under voltage occurs in the AC main
lighting distribution board. All DC emergency lighting shall be designed for 30 Volt DC
system.
2.4
The Contractor shall install the following under AC normal lighting system for both new
substations and existing substations under R&M:
a) Fluorescent industrial tube lights each having tube light 2 x 36 Watts with reflectors of
make Philips/Crompton/Bajaj as per following details:
i)
b) In the Switchyard, main gate substation boundaries etc. total eight nos. High pressure
Sodium Vapour lamps of 250 W each (outdoor use) with all fittings and fixtures shall be
installed.
4 nos. on lighting poles and 4 nos. at the locations as directed by the Engineer inCharge
c) One number 18 exhaust fan with louvers shutter shall be provided in the battery room.
d) Four numbers 1400 mm sweep ceiling fan with electronic regulator shall be provided in
control room.
The exact locations of the above fixtures shall be decided during detailed engineering.
2.5
Page 1 of 11
2.6
A single line diagram and a detailed drawings showing the lighting layout of these areas shall
be prepared by the Contractor and submitted for approval. The above layout drawings will
include disposition and location of lighting fixtures, receptacles, switchboards, ceiling fan
points, etc. The conduit layout for substation buildings, cable schedule for substation yard
etc. for wiring of this equipment shall also be prepared by the Contractor.
2.7
Each cable and conduit run shall be tagged with number that appears in the cable and conduit
schedules. Cables and conduits shall be tagged at their entrance and/or exit from any piece of
equipment, junction or pull box, floor opening etc. Each cable core shall be properly ferruled
at both ends with high quality PVC ferrules.
2.8
The tag shall be made up of aluminium with the number punched on it and securely attached
to the cable by not less than two turns of 10 SWG G.I. wire. Cable tags shall be rectangular in
shape for power cables and circular shape for control cables.
2.9
Location of cables laid directly under ground shall be indicated clearly by cable marker made
of galvanized iron plate embedded in concrete block. The location of under ground cable
joints if any, shall be clearly indicated with cable marker with an additional inscription "cable
joint".
3.0
DESCRIPTION OF ITEMS
The Contractor shall supply and install the following equipment and accessories in
accordance with the specification.
3.1
Lighting Panels
433V AC lighting panel shall have 433V, 63A, 3 phase 4 wire incomer bus of electrolytic
aluminium, TP MCB with neutral link and 20A, MCB as outgoing feeders with the following
details. These panels are without lighting transformers.
S. No.
Type
Description
ACP-I
Indoor
ACP-2
Outdoor
ACP-3
Note: The number of outgoing feeders indicated above are indicative only and to be supplied
as per requirement on approval of purchaser. A composite panel
(combination of
ACP-2 & ACP-3) or only ACP-2 may be accepted during post award engineering if they are
found suitable and suffice the requirement.
3.2
Receptacles
Number
1
3
1
Page 2 of 11
3.3
Switch Boards
Decorative type switch-board with switches & receptacle as stated above.
3.4
3.5
3.6
3.7
4.0
4.1
General
All lighting fixtures and accessories shall be designed for continuous operation under
atmospheric conditions existing at site, without reduction in the life or without any
deterioration of materials, internal wiring.
4.2
Temperature Rise
All lighting fixtures and accessories shall be designed to have a low temperature rise
according to the relevant Indian Standards. The design ambient temperature shall be taken as
50 deg.C.
4.3
Supply Voltage
Lighting fixtures and accessories meant for 240V A.C. operation shall be suitable for
operation on 240V A.C. 50Hz, supply voltage variation of 10%, frequency variation of
5% and combined voltage and frequency variation of 10%.
Lighting fixture and accessories meant for 30V DC operation shall be suitable for operation
on 30V DC with variation between 90% to 110% rated voltage.
4.4
Lighting Fixtures
The lighting fixtures shall be Phillips or Bajaj or Crompton Greaves make only. The different
types of lighting fixtures are as indicated in clause 12.6 of this Section.
4.5
All fixtures shall be designed for minimum glare. The finish of the fixtures shall be such that
no bright spots are produced either by direct light source or by reflection.
All lighting fixtures shall be complete with fluorescent tubes / high pressure sodium vapour
lamps as specified and shall be suitably wired up.
All fluorescent lamp fixture shall be complete with all accessories like ballasts, power factor
improvement capacitors, lamps, starters, holders etc.
Sodium vapour lamp fixtures shall be complete with ignitor, ballasts, lamps and holders.
Each lighting fixture shall be provided with an earthing terminal suitable for connection to 16
SWG GI earthing conductors.
All light reflecting surfaces shall have optimum light reflecting co-efficient such as to ensure
the overall light output as specified by the manufacturer.
Height of fixtures should be such that it is easy to replace the lamps with normal ladder/stool.
In case the ceiling height is very high, the fixtures may be placed on the walls for ground
lighting or suspended on steel tubes..
4.6
4.7
4.8
4.9
4.10
4.11
5.0
ACCESSORIES
5.1
Reflectors
The reflectors shall be manufactured from anodised aluminium as applicable of not less than
22 SWG thickness. They shall be securely fixed to the fitting.
5.2
Page 3 of 11
5.3
(a)Lamp holders/starter holders for fluorescent tubes shall be of the spring loaded, low
contact resistance, bi-pin rotor type, resistant to wear and suitable for operation at the
specified temperature, without deterioration in insulation value, contact resistance. They shall
hold the lamp/starter in position under normal condition of shock and vibration.
(b)Lamp holders for HPSV lamps shall be of screwed type, manufactured in accordance with
relevant standard and designed to give long and satisfactory service.
Ballasts
a)The Ballasts shall be designed, manufactured and supplied in accordance with relevant
standard and function satisfactorily under site condition specified. The ballasts shall be
designed to have a long service life and low power loss.
b)Ballasts shall be mounted using self locking anti-vibration fixing and shall be easy to
remove without dismantling the fixtures. They shall be totally enclosed units.
c)The ballasts shall be of the inductive, heavy duty type, filled with thermosetting insulating
moisture repellent polyester compound filled under vacuum. The ballast wiring shall be of
copper wire. They shall be free from hum. Ballasts which produce humming sound shall be
replaced free of cost by the Contractor. Ballasts for high pressure HPSV lamps shall be
provided with suitable tapping to set the voltage within the range specified. End connections
and taps shall be brought out in a suitable terminal block, rigidly fixed to the ballast
enclosure.
d)Separate ballast for each lamp shall be provided in case of multi-lamp fixtures.
5.4
Starters
Starters shall have bimetal electrodes and high mechanical strength. Starters shall be
replaceable without disturbing the reflector or lamps and without the use of any tool. Starters
shall have brass contacts and radio interference suppressing capacitor.
5.5
Capacitors
a)The capacitors shall have a constant value of capacitance and shall be connected across the
supply of individual lamp circuits.
b)The capacitors shall be suitable for operation at supply voltage as specified and shall have a
value of capacitance so as to correct the power factors of its corresponding lamp circuit to the
extent of 0.98 lag.
c)The capacitors shall be hermetically sealed in a metal enclosure.
5.6
5.6.1
5.6.2
5.6.3
Lamps
The fluorescent lamps shall be 'Day-light-colour' type unless otherwise specified and shall
also be provided with features to avoid blackening of lamps ends. The Contractor should
clearly state these features in the bid.
High pressure sodium vapour lamps shall be colour corrected type with caps.
Flexible conduits if required, for any fixture shall be deemed to be included in Contractors
scope.
6.0
RECEPTACLES
a)All receptacles shall be of cast steel/aluminum, heavy duty type, suitable for fixing on
wall/column and complete with individual switch.
7.0
Page 4 of 11
(c)Switch boards/boxes shall have conduit knock outs on both the sides and bottom..
Adequate provision shall be made for ventilation of these boxes.
(d)Flush type receptacles provided shall be so located that only the plug project outside.
(e)Switches shall be of piano key type having quick make and quick-break
complete with position indicator and shall conform to relevant Indian Standard.
mechanism
(f) All the components housed in the switchboard shall be wired to an outgoing terminal
block by 2.5 sq.mm. stranded copper wire The terminal block shall be adequately rated
(g)The exact number of switches including regulator for fans and layout of the same in the
switchboard shall be to suit the requirement during installation.
8.0
8.1
8.3
The conduits shall conform to IS:9537. All conduits shall be seemed by welding, shall be of
heavy gauge and shall be hot dip galvanized.
Flexible conduits wherever required shall be made with bright, cold rolled annealed and
electro-galvanized mild steel strips.
All conduits accessories shall conform to relevant IS and shall be hot dip galvanized.
9.0
JUNCTION BOXES
9.1
9.2
The junction boxes shall be suitable for mounting on walls, columns, lighting poles,
structures etc..
Junction boxes shall be of square/rectangular type of 1.6 mm sheet steel with minimum 6 mm
thick pressure die cast aluminum material LM-6 and shall have bolted cover with good
quality gasket lining.
9.3
9.4
The junction boxes shall be complete with conduit knockouts/threaded nuts and provided
with terminal strips .The junction boxes shall be suitable for termination of conduit/glands of
dia 20 mm, 25 mm, 32 mm, 40 mm on all sides. The junction boxes shall be provided with 4
way terminals suitable for two numbers 10 sq. mm. wire & for street lighting/switchyard
lighting suitable for 2 numbers 4C x 16 Sq.mm Al. cable.
The junction boxes shall have the following indelible markings
(i)
Circuit Nos. on the top.
(ii)
Circuit Nos. with ferrules (inside) as per drawings.
(iii)
DANGER sign in case of 433 volt junction box.
8.2
9.5
9.6
The outdoor junction boxes shall be weather proof type with gaskets conforming to IP-55 as
per IS:13947 (Part-I). The conduit connections shall also be properly sealed to prevent entry
of water. The indoor junction boxes shall conform to IP-52.
10.0
TERMINAL BLOCKS
Each terminal shall be suitable for terminating upto 2 Nos. 10 sq.mm. stranded Aluminum
Conductors without any damage to the conductors or any looseness of connections. Terminal
strips provided in street - lighting poles shall be suitable for terminating upto 2 nos. 4C x 16
sq. mm PVC insulated aluminum cables.
11.0
11.1
11.2
11.3
Page 5 of 11
11.4
11.5
The pull out boxes shall be completed with conduit knock outs/threaded hubs and provided at
approximately 3 meters intervals in a conduit run.
The pull out boxes used outdoor shall be weather proof type with gaskets conforming to IP55 as per IS:13947 (Part-I).
12.0
12.1
12.2
12.2.0
Constructional Features
Panels shall be sheet steel enclosed and shall be dust, weather and vermin proof. Sheet steel
used shall be of thickness not less than 2.00 mm (cold rolled) or 2.5 mm (hot rolled)
smoothly finished, leveled and free from flaws. Stiffners shall be provided wherever
necessary.
All outdoor panels and panels located in damp atmosphere shall have degree of protection not
less than IP-55 as per IS:13947 / (Part-I). All indoor panels shall have degree of protection
not less than IP-52 as per IS:13947 (Part-I).
The panels shall be of single front construction, front hinged and front connected, suitable for
either floor mounting on channels, sills or on walls/columns by suitable M.S. brackets.
Panels shall have a dead front assembly provided with hinged door(s) with padlocking
arrangement with single key supplied in duplicate.
All doors, removable covers and plates shall be gasketed all around with neoprene gaskets.
The panels shall be suitable for cable/conduit entry from the top and bottom. Suitable
removable cable gland-plate shall be provided on the top and bottom of panels. Necessary
number of double compression cable gland shall be supplied, fitted on to this gland plate.
The glands shall be screwed type and made of tinned brass.
The panels shall be so constructed as to permit free access to connection of terminals and
easy replacement of parts.
Each panel shall have a caution notice fixed on it.
Each panel shall be provided with a circuit directory plate (of anodized aluminium with the
inscriptions indelibly etched on the plate) which is fitted on the inside of the door.
Each lighting panel shall be provided with one no. ON indicating lamp for each phase
alongwith fuses.
12.2.1
12.2.2
12.2.3
12.2.4
12.2.5
12.2.6
12.2.7
12.2.8
12.2.9
12.3
12.4
12.5
12.6
12.7
shall be provided with the three element, positive acting, ambient temperature compensated
time lagged, hand reset type thermal overload relay with adjustable settings to suit the rated
current. Hand reset button shall be flush with the front of the cabinet and suitable for
resetting with starter compartment door closed. The contractor shall check the adequacy of
the Contactors rating wire with respect to lighting load.
Lighting Fixtures
S.No.
Type
Description
FC
SC
FI
SFI
IB
FF
FL
Labels
a)The lighting panels shall be provided on the front with panel designation labels on a 3 mm
thick plastic plate of approved type. The letter shall be black engraved on white back ground.
Page 7 of 11
b)All incoming and outgoing circuits shall be provided with labels. Labels shall be made of
non-rusting metal or 3 ply lamicold. Labels shall have white letters on black or dark blue
background.
12.8
Earthing Terminals
12.8.1
Panels shall be provided with two separate and distinct earthing terminals suitable to receive
the earthing conductors of size 50x6 G.S. Flat.
12.9
Testing
All lighting panels shall have to be tested for the following items and test certificates shall be
furnished for the same:
(i) Wiring continuity test
(ii) High voltage (2.5 KV for 1 minute) and insulation resistance test
(iii) Operational test
(iv) Degree of protection
(v) Heat run test
13.
Not Used
14.
14.1
The contractor shall supply and install 1400 mm sweep ceiling fans complete with electronic
regulator and switch, suspension rod, canopy and accessories.
14.2
The contractor shall supply and install the switch and electronic regulator.
14.3
Winding of the fans and regulators shall be insulated with Class-E insulating material.
Winding shall be of copper wire.
14.4
14.5
15.
LIGHTING WIRES
15.1
The wiring used for lighting shall be 1100 V grade, PVC insulated cables of reputed
manufacturers.
15.2
The conductor sizes for wires used for point wiring beyond lighting panels shall be single
core 2.5 sq.mm, 4 sq.mm and 6 sq.mm stranded copper wire of 1100V grade flexible PVC
insulated cords, unsheathed, conforming to IS:694.
15.3
The wires used for connection of a lighting fixture from a nearest junction box or for loop-in
loop-out connection between two fluorescent fixtures shall be single core copper stranded
conductor, with nominal conductor cross sectional areas of 2.5 sq. mm.
The wiring from ACDB to lighting panel shall be with 4x25 sq.mm. aluminium core 1100
volt grade cable.
15.4
15.5
Page 8 of 11
The wiring for outdoor steel tubular poles shall be done by 2x10 sq.mm. PVC armoured
aluminium core cable, 1100 V grade conforming to IS 1554. They shall run from LT ACDB
to an outdoor lighting panel and then to the junction boxes of the poles in trenches and laid
direct in ground.
15.7
15.7.1
All sheet steel work shall be phosphated in accordance with the procedure in IS:6005 'Code
of Practice for Phosphating Iron and Steel'.
Rust and scale shall be removed by pickling with dilute acid followed by washing with
running water, rinsing with slightly alkaline hot water and drying.
After phosphating through rinsing shall be carried out with clean water, followed by final
rinsing with diluted dichromate solution and oven drying.
The phosphate coating shall be sealed by the application of two coats of ready mixed stoving
type metal primer (comprising of red oxide and Zinc chromate in a synthetic medium). The
first coat may be 'flash dried' while the second coat shall be stoved.
After application of the primer, two coats of finishing synthetic enamel paint shall be applied
with each coat followed by stoving. The second finishing coat for the external of panels shall
be applied after completion of tests.
Both outside and inside of lighting panel, sheet metal fabricated junction boxes etc. and
outside of lighting fixtures shall be finished in light gray (IS-5 shade 631). Inside of lighting
fixtures, boxes and boards shall be finished in white.
Each coat of primer and finishing paint shall be of slightly different shade so as to enable
inspection of the painting.
The final finished thickness of paint film on steel shall not be less than 100 microns and shall
not be more than 150 microns.
Finished painted appearance on equipment shall present an aesthetically pleasing appearance,
free from dents and uneven surfaces.
15.7.2
15.7.3
15.7.4
15.7.5
15.7.6
15.7.7
15.7.8
15.7.9
16.0
17.0
LIGHTING SYSTEM INSTALLATION WORKS
17.1
General
17.1.1
In accordance with the specified installation instructions as shown on manufacturers
drawings or as directed by Owner, Contractor shall unload, erect, install, test and put into
commercial use all the electrical equipment included in the contract. Equipment shall be
installed in a neat, workmanship manner so that it is level, plumb square and properly aligned
and oriented. Tolerances shall be as established in manufacturers drawing or as stipulated by
Owner.
17.1.2
All apparatus, connections and cabling shall be designed so as to minimise risk of fire or any
damage which will be caused in the event of fire.
17.2
17.2.1
Conduit System
Contractor shall supply, store and install conduits required for the lighting installation as
specified. All accessories/fittings required for making the installation complete, including but
not limited to pull out boxes (as specified in specification.ordinary and inspection tees and
elbow, checknuts, male and female bushings (brass or galvanised steel), caps, square headed
make plugs, nipples, gland sealing fittings, pull boxes, conduits terminal boxes, glands,
gaskets and box covers, saddle terminal boxes, and all steel supporting work shall be supplied
by the Contractor. The conduit fittings shall be of the same material as conduits.
Page 9 of 11
17.2.2
17.2.3
17.2.4
17.2.5
17.2.6
17.2.7
17.2.8
17.2.9
17.2.10
17.2.11
17.2.12
17.3
17.3.1
17.3.2
17.3.3
17.3.4
17.3.5
17.3.6
17.3.7
17.3.8
17.3.9
17.3.10
17.4
17.4.1
17.4.2
17.5
17.5.1
17.5.2
All unarmoured cables shall run within the conduits from lighting panels to lighting fixtures,
receptacles. etc.
Size of conduit shall be suitably selected by the Contractor.
Conduit support shall be provided at an interval of 750 mm for horizontal runs and 1000 mm
for vertical runs.
Conduit supports shall be clamped on the approved type spacer plates or brackets by saddles
or U-bolts. The spacer plates or brackets in turn, shall be securely fixed to the building steel
by welding and to concrete or brick work by grouting or by nylon rawl plugs. Wooden plug
inserted in the masonary or concrete for conduit support is not acceptable.
Where conduits are alongwith cable trays they shall be clamped to supporting steel at an
interval of 600 mm.
For directly embedding in soil, the conduits shall be coated with an asphalt-base compound.
Concrete pier or anchor shall be provided wherever necessary to support the conduit rigidly
and to hold it in place.
For long conduit run, pull boxes shall be provided at suitable intervals to facilitate wiring.
Conduit shall be securely fastened to junction boxes or cabinets, each with a lock nut inside
and outside the box.
Conduits joints and connections shall be made through water-tight and rust proof by
application of a thread compound which insulates the joints. White lead is suitable for
application on embedded conduit and red lead for exposed conduit.
The entire metallic conduit system, whether embedded or exposed, shall be electrically
continuous and thoroughly grounded. Where slip joints are used, suitable bounding shall be
provided around the joint to ensure a continuous ground circuit.
Conduits and fittings shall be properly protected during construction period against
mechanical injury. Conduit ends shall be plugged or capped to prevent entry of foreign
material.
Wiring
Wiring shall be generally carried out by PVC wires in conduits. All wires in a conduit shall
be drawn simultaneously. No subsequent drawings of wires is permissible.
Wires shall not be pulled through more than two equivalent 90 deg. bends in a single conduit
run. Where required, suitable junction boxes shall be used.
Wiring shall be spliced only at junction boxes with approved type terminal strip.
For lighting fixtures, connection shall be teed off through suitable round conduit or junction
box, so that the connection can be attended without taking down the fixture.
For vertical run of wires in conduit, wires shall be suitably supported by means of
wooden/hard rubber plugs at each pull/junction box.
Maximum two wires can be terminated to each way of terminal connections.
Separate neutral wires are to be provided for each circuit.
AC and DC wiring should not run through the same conduit.
Outdoor wiring shall be by armoured cable laid in trenches or directly in ground.
Wiring from LT ACDB to lighting panels shall be laid in trenches.
Lighting Panels
The lighting panels shall be erected at the locations to be finalised during detailed
engineering.
Suitable foundations/supporting structures for all outdoor type lighting panels and necessary
supporting structures for indoor lighting panels shall be provided by the Contractor.
Foundation & civil works
Foundation for street lighting poles and panel foundation and transformer foundation shall be
done by the Contractor. The rates for these civil works shall be included in the erection rates
of respective items.
All final adjustment of foundation levels, chipping and dressing of foundation surfaces,
setting and grouting of anchor bolts, sills, inserts and flastening devices shall be carried out
by the Contractor including minor modification of civil works as may be required for
erection.
Page 10 of 11
17.5.3
Any cutting of masonary/concrete work, which is necessary shall be done by the Contractor
at his own cost and shall be made good to match the original work.
Page 11 of 11
PSC Poles
PSC poles shall be of solid rectangular type with an overall length of
8.0 M & 9.0M suitable for use in 11 KV overhead power lines, LT
power lines and double pole structures associated with the lines and
for 11/0.4 KV substations. The poles shall be designed for the
working load of 200/400 Kg.
2.0
Applicable Standards
Except when they conflict with specific requirements in this
Specification, the PSC poles shall comply with the relevant
provisions made in the following Indian Standards or the latest
versions thereof.
3.0
a)
b)
c)
Terminology
For the purpose of this specification, following definitions shall
apply:-
3.1
3.2
Load Factor
The ratio of ultimate transverse load to the transverse load at first
crack.
3.3
Transverse
The direction of the line bisecting the angle contained by the
conductor at the pole. In the case of a straight run, this will be normal
to the run of the line.
Page 1 of 11
3.4
3.5
Working Load
The maximum load in the transverse direction, that is ever likely to
occur, including the wind pressure on the pole. This load is assumed
to act at a point 600mm below the top with the butt end of the pole
planted to the required depth as intended in the design.
3.6
Ultimate Failure
The condition existing when the pole ceases to sustain a load
increment owing to either crushing of concrete, or snapping of the
prestressing tendon or permanent stretching of the steel in any part of
the pole.
3.7
4.0
Application
4.1
8.0 M Poles
These poles shall be used for 11KV & L.T. lines and in double pole
structures of Distribution Transformers in wind pressure zones of 50
kg/M2, 75 kg/M2 and 100 kg/M2 in accordance with REC
Construction Standards no. A-5 & B-6.
4.2
5.0
Material
5.1
Cement
The cement used in the manufacture of prestressed concrete poles shall
be ordinary or rapid hardening Portland cement conforming to IS: 269 -
Page 2 of 11
Aggregates
Aggregates used for the manufacture of pre-stressed concrete poles shall
confirm to IS : 383 (Specification for coarse and fine aggregates from
natural sources for concrete). The nominal maximum size of aggregates
shall in no case exceed 12 mm .
5.3
Water
Water should be free from chlorides, sulphates, other salts and organic
matter. Potable water will be generally suitable.
5.4
Admixture
Admixture should not contain Calcium Chloride or other chlorides and
salts which are likely to promote corrosion of pre-stressing steel. The
admixture shall conform to IS 9103.
5.5
Pre-Stressing Steel
The pre-stressing steel wires including those used as untensioned wires
should conform to IS: 1785 (Part-I) (Specification for plain hard-drawn
steel wire for prestressed concrete, Part-I cold drawn stress relieved
wire), IS: 1785 (Part-II) (Specification for plain hard-drawn steel wire) or
IS:6003 (Specification for indented wire for prestressed concrete). The
type designs given in the annexure are for plain wires of 4 mm diameter
with a guaranteed ultimate strength of 175 kg/mm2 and for plain wires of
5 mm diameter with a guaranteed ultimate strength of 160 kg/mm2.
All prestressing steel shall be free from splits, harmful scratches, surface
flaws, rough, aged and imperfect edges and other defects likely to impair
its use in prestressed concrete.
5.6
Concrete Mix
The concrete mix shall be designed to the requirements laid down for
controlled concrete (also called design mix concrete) in IS : 1343 1980 (Code of practice for prestressed concrete) and IS : 456 - 1978
(Code of practice for plain and reinforced concrete), subject to the
following special conditions;
a)
b)
Page 3 of 11
6.0
c)
The mix should contain at least 380 Kg. of cement per cubic
meter of concrete.
d)
Design Requirements
The poles shall be designed for the following requirements:
a)
b)
c)
The factor of safety for all poles 9.0 Mts. and above shall not be
less than 2.0 and for 8.0 M poles, the factor of safety shall not be
less than 2.5.
d)
e)
f)
g)
h)
i)
j)
The concrete strength at transfer shall not be less than half, the
28 days strength ensured in the design, i.e. 400 x 0.5 =
200kg/cm2.
6.1
6.2
Manufacture
6.2.1
6.2.2
6.3
Cover
The cover of concrete measured from the outside of pre-stressing
tendon shall be normally 20 mm.
6.4
6.5
Compacting
Concrete shall be compacted by spinning, vibrating, shocking or other
suitable mechanical means. Hand compaction shall not be permitted.
6.6
Curing
The concrete shall be covered with a layer of sacking, canvass,
hessian or similar absorbent material and kept constantly wet up to
the time when the strength of concrete is at least equal to the
minimum strength of concrete at transfer of prestress. Thereafter, the
pole may be removed from the mould and watered at intervals to
prevent surface cracking of the unit, the interval should depend on the
atmospheric humidity and temperature.
The prestressing wires shall be de-tensioned only after the concrete
has attained the specified strength at transfer (i.e. 200 or 210 kg/cm2,
Page 5 of 11
6.8
7.0
should be carried out in such a way that the erection loads are applied
so as to cause moment with respect to the major axis, i.e. the rope
used for hoisting the pole should be parallel to the broader face of the
pole.
8.0
Earthing
8.1
8.2
9.0
Tests
9.1
9.1.1
Poles made from ordinary Portland cement shall be tested only on the
completion of 28 days and poles made from rapid hardening cement
only on the completion of 14 days, after the day of manufacture.
9.1.2
9.1.3
The pole shall be rigidly supported at the butt end for a distance equal
to the agreed depth of planting
9.1.4
Load shall be applied at a point 600 mm from the top of the pole and
shall be steadily and gradually increased to the design value of the
transverse load at first crack. The deflection at this load shall be
measured.
9.1.5
9.1.6
Page 7 of 11
The pole shall be deemed not to have passed the test if the observed
ultimate transverse load is less than the design ultimate transverse
load.
9.2
Measurement of Cover
9.2.1
After completion of the transverse strength test, the sample pole shall
be taken and checked for cover. The cover of the pole shall be
measured at 3 points, one within 1.8 meter from the butt end of the
pole, the second within 0.6 meters from the top and the third at an
intermediate point and the mean value compared with the specified
value.
9.2.2
The mean value of the measured cover should not differ by more than
(+) 1 mm from the specified cover. The individual values should not
differ by more than (+) 3 mm from the specified value.
9.2.3
10.0
10.1
Scale of Sampling
10.1.1
Lot: In any batch, all poles of the same class and same dimensions
shall be grouped together to constitute a lot.
10.1.1
Sub-lot: If the number of poles in a lot exceed 500, the lot shall be
divided into a suitable number of sub lots such that the number of
poles in any sub-lot shall not exceed 500.
Page 8 of 11
The acceptance or
Dimensional Requirement
Sample Size
No. of poles
for transverse
Permissible No. strength test
of
defective
samples
Upto 100
10
101 to 200
15
201 to 300
20
301 to 500
30
10.2
Number of Tests
10.2.1
All the poles as selected in 10.1.3 shall be tested for overall length,
cross-section and uprightness. The tolerance shall be (+) 15 mm on
overall length (+), 3 mm on cross sectional dimensions and 0.5 per
cent on uprightness.
10.2.1
10.3
10.3.1
Page 9 of 11
10.3.2
10.3.3
All the poles tested for transverse strength test shall satisfy the
requirements of the test. If one or more poles fail, twice the number
of poles originally tested shall be selected from those already selected
and subjected to the test. If there is no failure among these poles, the
lot or the sub-lot shall be considered to have satisfied the
requirements of this test.
11.0
Marking
The following marking should be given of the poles during its casting
at 3 meters height from bottom:Sr. no.
Particulars
FEEDER SEGREGATION
Name of agency
.
12.0
Drawings
12.1
12.2
12.3
12.4
Page 11 of 11
1.0.1
1.0.1.1
Stranded Aluminium conductor PVC insulated armoured cables shall be used for
main power supply purpose from LT Aux. Transformers to ACDB, between
distribution boards and for various other applications in switchyard area and control
room except for control/protection purposes.
1.0.1.2
1.0.1.3
Sizing of power cables shall be done keeping in view the continuous current,
voltage drop & short-circuit consideration of the system. Relevant calculations shall
be submitted by the contractor during detailed engineering for purchasers
approval.
1.0.1.4
1.0.1.5
1.0.1.6
At least one (1) core shall be kept as spare in each copper control cable of
4C, 5C or 7C size whereas minimum no. of spare cores shall be two (2)
for control cables of 10 core or higher size.
For control cabling, including CT/VT circuits, 2.5 sq.mm. size copper cables shall
be used per connection. However, if required from voltage drop/VA burden
consideration additional cores shall be used. Further for potential circuits of energy
meters separate connections by 2 cores of 2.5sq.mm. size shall be provided.
2.0
TECHNICAL REQUIREMENTS
2.0.1
General
2.0.1.1
2.0.1.2
The cables shall be suitable for laying in racks, ducts, trenches, conduits and
underground-buried installation with uncontrolled back fill and chances of flooding
by water.
The XLPE insulated cables shall be capable of withstanding a conductor
temperature of 250C during a short circuit without any damage. The PVC
insulated cables shall be capable of withstanding a conductor temperature of 160C
during a short circuit.
Page 1 of 3
2.0.1.3
The Aluminium / Copper wires used for manufacturing the cables shall be
electrolytic grade and true circular in shape before stranding and shall be uniformly
good quality, free from defects. All aluminium used in the cables shall be of H2
grade.
2.0.1.4
The fillers and inner sheath shall be of non-hygroscopic, fire retardant material,
shall be softer than insulation and outer sheath shall be suitable for the operating
temperature of the cable.
Progressive sequential marking of the length of cable in meters at every one metre
shall be provided on the outer sheath of all cables.
2.0.1.5
2.0.1.6
Strip wire armouring following method (a) mentioned in the relevant ISS shall not
be accepted for any of the cables. For control cables only round wire armouring
shall be used.
2.0.1.7
The cables shall have outer sheath of a material with an oxygen index of not less
than 29 and a temperature index of not less than 250C.
2.0.1.8
All the cables shall pass fire resistance test as per IS: 1554 (Part-I)
2.0.1.9
The normal current rating of all PVC insulated cables shall be as per IS: 3961.
Repaired cables shall not be accepted.
2.0.1.10 Allowable tolerance on the overall diameter of the cables shall be plus or minus 2
mm.
3.0
3.0.1
4.0
4.0.1
The PVC (70C) insulated 1100V grade power cables shall be of FR type, C1
category, conforming to IS: 1554 (Part-I) and its amendments, read along with this
specification and shall be suitable for a steady conductor temperature of 70C. The
conductor shall be stranded aluminium. The Insulation shall be extruded PVC to
type-A of IS: 5831. A distinct inner sheath shall be provided in all multicore
cables. For multicore armoured cables, the inner sheath shall be of extruded PVC.
The outer sheath shall be extruded PVC to Type ST-1 of IS: 5831 for all cables.
5.0.
5.0.1
The 1100 grade control cables shall be of FR type C1 category conforming to IS:
1554 (Part-1) and its amendments, read along with this specification. The
Page 2 of 3
conductor shall be stranded copper. The insulation shall be extruded PVC to type A
of IS: 5831. A distinct inner sheath shall be provided in all cables whether armored
or not. The outer sheath shall be extruded PVC to type ST-1 of IS: 5831 and shall
be gray in colour except where specifically advised by the Employer to be black.
5.0.2
Cores shall be identified as per IS: 1554 (Part-1) for the cables upto five (5) cores
and for cables with more than five (5) cores the identification of cores shall be done
by printing legible Hindu Arabic Numerals on all cores as per clause 10.3 of IS
1554 (Part-1).
6.0.
CABLE DRUMS
6.0.1
6.0.2
Standard lengths for each size of power and control cables shall be 500/1000
meters. The cable length per drum shall be subject to a tolerance of plus or minus
5% of the standard drum length. In case, the total requirement is less than 500
meters, non-standard drum length shall also be acceptable.
6.0.3
A layer of waterproof paper shall be applied to the surface of the drums and over
the outer most cable layer.
6.0.4
A clear space of at least 40 mm shall be left between the cables and the lagging.
6.0.5
Each drum shall carry the manufacturer's name, the purchaser's name, address and
contract number and type, size and length of the cable, net and gross weight
stencilled on both sides of drum. A tag containing the same information shall be
attached to the leading end of the cable. An arrow and suitable accompanying
wording shall be marked on one end of the reel indicating the direction in which it
should be rolled.
Packing shall be sturdy and adequate to protect the cables, from any injury due to
mishandling or other conditions encountered during transportation, handling and
storage. Both cable ends shall be sealed with PVC/Rubber caps so as to eliminate
ingress of water during transportation and erection.
6.0.6
7
7.0.1
TESTS
All cables shall conform to all type, routine and acceptance tests listed in the
relevant IS.
7.0.2
All power cables of sizes 240 sqmm and above shall meet the requirements of the
following additional tests and type tests may be conducted to prove their
capabilities.
8.0
Page 3 of 3