Professional Documents
Culture Documents
CS notes:
1. The CENELEC National Committees are invited to comment on this draft Guide by
1999-05-31 and/or to indicate their preference for the future publication of this
document as a CENELEC Report or a European Specification.
2.
1. Foreword
2. APPLICATION OF THE CENELEC STANDARD
2.1
Introduction
2.2
Scope of standard
2.4.
Groups of Voltage Characteristics
2.4.1
Definite Values
2.4.2
Indicative Values
2.5
Voltage Terminology
3. Description of main voltage characteristics
3.1
Power frequency ***
3.2
Magnitude of the supply voltage
3.3
Supply voltage variations
3.4
Rapid voltage changes
3.4.1
Magnitude of rapid voltage changes
3.4.2
Flicker severity
3.5
Supply Voltage Dips
3.6
Short and long interruptions of the supply voltage
3.7
Temporary (power frequency) overvoltages between live conductors and earth
3.8
Transient overvoltages between live conductors and earth
3.9
Supply voltage unbalance
3.10 Harmonic voltage
3.11 Interharmonic voltage
3.12 Mains signalling voltage on the supply voltage
4. Small private generation
5. REFERENCES
3
4
4
4
8
8
9
10
11
11
11
11
12
12
12
12
16
17
19
22
22
23
23
25
26
1.
FOREWORD
General
This guide has been prepared by BTTF-68-6 based on an application guide written
by the UNIPEDE Group of Experts NORMCOMP: Electricity Product
Characteristics and Electromagnetic Compatibility.
The aim of this guide is to give explanations, background and complementary
information related to EN 50160 Voltage characteristics of electricity supplied by
public distribution systems.
By its very nature, a standard has to be concise and cannot give a comprehensi ve
background of the subject being dealt with. It was accordingly decided to prepare a
guide providing additional information and clarification of the standard.
Background of the definition of supply voltage characteristcs
From the very beginning of their association, the Member States of the European
Communities decided to create a wide economic area without barriers to internal
trade.
For this purpose a number of directives have been issued by the Commission of the
European Community (EC), to remove the differences in the legislation of the
Member States, which could affect the free exchange of goods and services.
One such directive is the Directive 85/374 on Product Liability [1]. This states, in
Article 2 that product includes electricity for the purpose of the directive. Conse quently, it was considered necessary to define the essential characteristics of the
electricity supply.
2.1
Introduction
Electricity distribution systems are developed taking into account the problem of
providing adequate conditions for the operation of user equipment and, at the same
time, avoiding unnecessary increases of the cost of the electricity supply.
The standard takes this into account.
2.2
Scope of standard
Condition:
Illustrative examples:
Sabotage, vandalism
Industrial action
Force majeure
major accidents
Exceptional weather conditions are for example conditions where the severity
exceeds the legally required design conditions of the network equipment. Another
example would be conditions under which the repair and maintenance work of the
supply utility is restricted due to extreme weather conditions in severity or duration
(long lasting blizzards, flood situations, landslides, extreme wind conditions etc.).
The standard also does not apply if the supplier is prevented from carrying out
necessary alterations to the supply system, by government or other public autho rities or by lack of public consent.
An example of a condition in which application of the standard is temporarily not
applicable, is that a part of the supply system is out of operation, due either to a
fault of large impact or to the need to carry out maintenance or construction work.
Under these circumstances, if supply can be maintained to all or as many custo mers
as possible, even at the expense of some deterioration of one or more of the
voltage characteristics, this is generally accepted to be preferable to an outright
interruption.
Because the public distribution networks are the unintended carriers of electromagnetic disturbances emitted by equipment within the customers installations, it is
necessary that such emissions have to be subject to appropriate limits. These limits
are either specified in relevant product standards or prescribed for particular
installations by the public authorithies or the electricity supplier.
Compliance with these limits by the customers installations and equipment is a
necessary precondition to keep the voltage characteristics within the given values of
EN 50160. The same principle applies to all connections to the supply system,
including private generation embedded in it.
The standard allows for its requirements to be superseded by terms of a contract
between a customer and the electricity supplier. In this case the values of voltage
characteristics are matter of mutual agreement between customer and supplier.
Such contract is most likely to arise for customers with relatively large electricity
demand, supplied from the MV network. It may also arise in sparsely populated or
difficult terrain, such as mountain regions where supply costs are high. In such an
area a customer may be willing to accept a supply at lower costs which does not
entirely comply with EN 50160. Where an agreement is made in a contract which
supersedes the standard the customer should consider its effect on his installation
and equipment.
EN 50160 is not an EMC standard. It does not give compatibility levels or emission
limits. Moreover the standard does not have the function of specifying the
requirements for electrical equipment. Its sole function is to give values for the main
voltage characteristics of electricity supplied by LV and MV public networks. That
means EN 50160 is a product standard giving the voltage characteristics which can
be expected at the supply terminals.This standard does not describe the average
situation in the public supply networks but the maximum values or variations of
the voltage characteristics under normal operating conditions which can be
expected by the customer at any place of the network.
2.3 Definitions
The definition 1.3.2 supplier needs clarification in the context of the open market
for energy. The place where electricity is generated may be distant from the
consumer. The quality of the supply voltage is influenced by the electricity supply
system or systems through which the electricity is delivered to the supply terminals.
This standard was prepared on basis of a bilateral contract between the owner of
the electricity supply system and one customer. In this case the supplier provides
the described voltage characteristics. In other cases application of EN 50160 will
depend on the contractual arrangements or legal requirements.
A rapid voltage change is a fast decrease or increase of the r.m.s. value of the
supplied voltage caused by rapid load changes or switching. If a rapid voltage
change is caused by the inrush current of a motor, the rapid voltage change starts
with a step reduction followed by a ramped recovery ending at a voltage value less
than that existing before switching (FIG. 1).
Error!Vnculo no vlido.
A rapid voltage change is defined as the time function of change of the r.m.s voltage
evaluated step-wise over successive half-periods between zero-crossings between
periods when the voltage is in a steady-state condition for at least 1 second.
The voltage during a rapid voltage change must not drop below a level of 0.9*U c, as
it would otherwise be considered a voltage dip.
2.4.
b)
2.4.1
Definite Values
For some characteristics it is feasible to set limits which can be complied with for
most of the time, however, there still remains the possiblity of relatively rare
excursions beyond these limits.
The essential randomness of the factors involved precludes declaring any bounds
within which there could be a reasonable expectation that such excursions could be
contained.
The following table gives the characteristics for which definite limits have been
specified. Interharmonics have been included even if no indications have been
given. As stated, limits will be established once additional experience enables this
to do.
Generally an observation period of one week is chosen because it is the shortest
intervall to get representative and reproducable measurement results.
Limits are set with a view to compliance for a percentage of the observation time, e.
g. 95 % of the observations in any period of one week. For the reason stated above,
no limit is set for the remainder of the time. However, experience shows that in
practice the frequency with which excursions outside the 95 % limits occur
decreases very rapidly with the magnitude of such excursions. An indication of 100
% values which might be expected are given in chapter 3 of this guide.***
Compliance with
stated limits
Observation
period
frequency ***
100 %
99,5 %
year
100 %
95 %
week
day
95 %
week
95 %
week
95 %
week
interharmonic voltages
mains-borne signalling voltages
***
to be defined
99 %
to be defined
day
The given values are based on the assumtion that the amendments
prAB and prAC will have a positive voting.
An exception is made in case of supply voltage and power frequency: Here limits
are given for compliance over a 100 % of time, in addition to 95 % and 99,5 %
limits.
A special case is rapid voltage changes, for which allowance is given for a few
occurrences per day exceeding the limit.
2.4.2
Indicative Values
The remaining characteristics of the voltage are, by their nature, so unpredic table
and so variable from place to place and from time to time, that it is only possible to
set indicative values, which are intended to provide users with information on the
range of magnitude which can be expected.
- voltage dips
- short interruptions
- long interruptions
temporary
and
overvoltages
transient
2.5
Voltage Terminology
- supply voltage
- nominal voltage Un
- declared voltage Uc
The nominal or declared voltages are used in the EN as reference value for the
evaluation of some of the voltage characteristics and must be interpreted as
interchangeable, as appropriate, in the rest of the present document.
3.
3.1
The EN states that the nominal value of the frequency is 50 Hz. Taking into account
the fact that the frequency in a supply system depends on the interaction between
generators and load and that the range of variation is smaller the higher the ratio
between generation capacity and load fluctuations, a distinction is made between
power supply systems with synchronous interconnection to adjacent systems and
weaker isolated systems as those which typically exist in islands.
In case of fault operation, parts of an interconnected system may become isolated.
Under some circumstances frequency is needed to be used for load control. For
these reasons a frequency variation +4%/-6% is defined.
In practical terms the statistical assessment requires definition of a basic measurement, which could be carried out by determining the mean value of frequency over
successive fixed time intervals of 10 seconds.
Compliance with the limits given will than be assessed over an observation period
of one week, including Saturday and Sunday, by a statistical analysis carried out
over the sequence of 10 seconds measurements.
***
3.2
3.3
Under normal operating conditions load changes cause variations of the average
supply voltage, which are in general compensated by automatic voltage regula tion,
within a period of a few tens of seconds.
The stated range of variation of the r.m.s. magnitude of the supply voltage,
Pestka : versorgungsqualitt : arbeitskreise : bt68-6 : application guide : oktober 98
3.4
Error!Vnculo no vlido.
Table 1 summarises the results obtained in the survey. Each cell of the table
represents a combination of the results from all locations and gives the number
of events belonging to the corresponding classes of depth and duration, which
may be expected to occur per year with a probability of 95 % of not being
exceeded. It should be noted that, according to the criterion stated before, data
on the lowest row are to be considered as interruptions and not as voltage
dips.
Table 1
UNIPEDE survey on the characteristics of voltage dips: frequency of occurrence per annum and per location with a 95
% probability of not being exceeded
Depth
(% of nominal
voltage)
Duration
(ms)
(ms)
(s)
(s)
(s)
(s)
from
to less
than
10 <
100
100 <
500
0.5 < 1
1<3
3 < 20
20 < 60
10
30*
111
68
12
30
60
13
38
60
99
12
20
99
100
12
16
In a future survey UNIPEDE DISDIP has decided to split this class into
two classes: 10 - 15 and 15 - 30
The value of each cell of table 1 has been calculated from the values for each
location. As each cell is therefore calculated independent from the others, the
95 % value of each cell may concern a different choice of locations. This
means that the sum of values over all cells per row or per column do not give
the precise 95 % values of the whole survey for example per depth or per
duration. The real 95 % values per depth or per duration or per depth and
duration are normally lower than the corresponding sum which can be
calculated from the rows or columns of the table 1. (This text needs to be
confirmed by BTTF 68-6 !!!)
This classification takes into account the characteristics of protection and auto matic reclosing systems in use in supply networks.
On medium voltage overhead networks it is common practice to perform a fast
automatic reclosing after the initial tripping of a line circuit breaker on a fault.
The delay for the fast reclosing is in general between 300 ms and 500 ms and
in most cases less than 1 second.
In case of a successful auto reclose operation which clears the fault, the users
supplied by the line are affected by a voltage dip, with a duration equal to the
operating time of the circuit breaker and the time delay of the protective relay
of about 100 up to 500 ms followed by an interruption until the circuit breaker
auto-recloses. In urban areas a time delay of 1 s is not unnormal.
The other lines connected to the same busbar of the line where the fault
occurs experience a voltage dip with a duration equal to the operating time of
the circuit breaker and whose depth depends on the distance of fault location
from the substation busbar.
If, on reclosing, the fault is still present, another voltage dip will occur on the
faulted line and on the other lines supplied by the same busbars and the circuit
breaker will trip again.
The users supplied by the line will accordingly experience another short
interruption followed by restoration of supply or a final tripping of the circuit
breaker, depending on whether the fault has cleared spontaneously or persists.
Pestka : versorgungsqualitt : arbeitskreise : bt68-6 : application guide : oktober 98
In this latter case, the supply will be interrupted until the fault is localised and
the line section is isolated for inspection and repair. If an alternative source of
supply is provident, manual or if available automatic switching of the
alternative supply is performed. For the automatic switching the delay is
commonly ranging between 30 seconds and 3 minutes.
It must be stressed that these techniques are applied in order to provide the
best possible continuity of supply, and to minimise the number of users
affected by the long interruption caused by a permanent fault. As a
consequence the users connected to the healthy lines may be affected by a
few additional voltage dips.
As far as faults on the low voltage networks are concerned, the probability that
a fault clears spontaneously when the voltage is switched off is very low, so
auto-reclosing is not needed.
Low voltage users are therefore affected by the events on the medium voltage
network to which their supply lines are connected and to those occurring on
their specific and adjacent low voltage circuits.
The protection and supply restoration schemes have been considered an intrinsic feature of normal operation of a supply system and this explains why
the duration of short interruptions has been increased to three minutes, instead
of keeping the duration of one minute, as in the EMC standards.
3.7
Temporary overvoltages mainly occur at power frequency and can last from
several cycles up to hours or days depending on specific situations.
3.7.1 LV distribution systems
The majority of LV public distribution systems are operated with a solidly
grounded neutral, therefore limited temporary overvoltages are experienced;
these overvoltages can arise as a consequence of faults and switching on of
power factor improvement capacitors.
The magnitude is generally limited at 1.5 kV rms for up to 5 seconds.
3.7.2 MV distribution systems
Events originating temporary overvoltages on the MV networks are mainly of
two types:
-
open conductors
transference of transient overvoltages from MV to the LV of the transformers by electromagnetic coupling (generally: amplitude: up to 1 kV,
waveform: oscillatory with frequency in the range a fraction to a few ten
kHz)
3.8.1.2
induction of the nearby lightning strikes along LV lines conductors (ge nerally: amplitude: up to 20 kV, waveform: unidirectional, some times
unidirectional oscillatory, high energy levels)
resistive coupling that due to lightning ground currents flows in the common ground impedance paths and in a partially common ground
resistance gives surges (amplitude generally up to 6 - 10 kV,
unidirectional or sometimes unidirectional oscillatory waveform, high
energy levels)
3.8.1.3
3.8.2.1
3.8.2.3
Harmonic voltage
Harmonic values are specified only up to order 25, for the practical reason that
for higher orders the values are generally so small as to be impractical to
measure and because of the difficulty of giving values which would be relevant
to all networks.
For medium voltage networks the same values of harmonics are given as in
low voltage systems even if the expected values normally are less than 80 %
of the values in low voltage systems. This was done because of the higher risk
of resonance effects, diversity of loads and the sometimes nearly arithmetic
superposition of harmonics with the same phase angle in medium voltage
systems especially for the low order harmonics.
EN 50160 declares that in case of network resonances higher values of an
individual harmonic may occur. Normally those resonance effects are more
severe in MV networks than in LV networks. The highest resonances occur
under low load conditions. The value of a low order individual harmonic due to
network resonance is roughly up to factor 2 higher than the value in the same
network without resonance effect.
3.11
Interharmonic voltage
100 Hz to 900 Hz: The values are taken of the so-called Meister-curve
which defines the maximum permissible ripple control voltages in LVnetworks. It consists of a horizontal part for the low frequency range with
a maximum level of 20 V and a following decrease starting at 500 Hz,
according to the function 10 000/f (f in Hz). The Meister-curve is
contained also in ENV 61000-2-2, 1993 [7]
Levels are equall for LV and MV in the range from 100 Hz to 9 kHz; for
frequencies above 9 kHz the MV-part of EN 50160 does not give levels
because of lack of experience and with respect to possible future
developments.
When energy is supplied to the public networks from small private generators,
it is important to keep the level of disturbances under control.
In this context private generation is in the same position as any customers
installation and therefore have to comply with the related emission standards
and contractual limits on power produced.
Such compliance is therefore also a condition for the applicability of EN 50160.
5.
REFERENCES
[ 1]
[ 2]
[ 3]
[ 4]
IEC Publ. 38 (6th edition), 1983: IEC standard voltages / HD 472SI, November 1988 Nominal Voltages for Low Voltage Public Electricity Supply
Systems, amendment 1-1994
[ 5]
UNIPEDE Report 91 en 50.02: Voltage Dips and Short Interruptions in Electricity Supply Systems
[ 6]
IEC Publ. 1000-2-1, 1990: Electromagnetic compatibility (EMC). Part 2: Environment, Section 1: Description of the environment - Electromagnetic
environments for low frequency conducted disturbances and signalling in
public power supply systems
[7]
[8]