prEN 50160:2008

Foreword
This European Standard was prepared by the Working Group 1, Physical characteristics of
electrical energy of the Technical Committee CENELEC TC 8X, System aspects of electrical
energy supply. It is submitted to the formal vote.
This European Standard will supersede EN 50160:2006.
The following dates are proposed:

latest date by which the existence of the EN


has to be announced at national level

(doa)

dor + 6 months

latest date by which the EN has to be implemented


at national level by publication of an identical
national standard or by endorsement

(dop)

dor + 12 months

latest date by which the national standards conflicting


with the EN have to be withdrawn

(dow)

dor + 36 months
(to be confirmed or
modified when voting)

__________

prEN 50160:2008

Contents
1

Scope and object .......................................................................................................................... 4


1.1 Scope ................................................................................................................................... 4
1.2 Object................................................................................................................................... 4
2 Normative references ................................................................................................................... 5
3 Definitions ...................................................................................................................................... 6
4 Low-voltage supply characteristics............................................................................................ 11
4.1 General .............................................................................................................................. 11
4.2 Continuous phenomena ................................................................................................... 11
4.2.1 Power frequency ..................................................................................................... 11
4.2.2 Supply voltage variations........................................................................................ 11
4.2.2.1 Requirements........................................................................................................ 11
4.2.3 Rapid voltage changes ........................................................................................... 12
4.2.4 Supply voltage unbalance ...................................................................................... 12
4.2.5 Harmonic voltage .................................................................................................... 12
4.2.6 Interharmonic voltage ............................................................................................. 13
4.2.7 Mains signalling voltage on the supply voltage .................................................... 13
4.3 Voltage events................................................................................................................... 14
4.3.1 Interruptions of the supply voltage......................................................................... 14
4.3.2 Supply voltage dips/swells ..................................................................................... 14
4.3.3 Transient overvoltages between live conductors and earth ................................ 16
5 Medium-voltage supply characteristics..................................................................................... 17
5.1 General .............................................................................................................................. 17
5.2 Continuous phenomena ................................................................................................... 17
5.2.1 Power frequency ..................................................................................................... 17
5.2.2 Supply voltage variations........................................................................................ 17
5.2.2.1 Requirements........................................................................................................ 17
5.2.3 Rapid voltage changes ........................................................................................... 18
5.2.4 Supply voltage unbalance ...................................................................................... 18
5.2.5 Harmonic voltage .................................................................................................... 18
5.2.6 Interharmonic voltage ............................................................................................. 19
5.2.7 Mains signalling voltage on the supply voltage .................................................... 19
5.3 Voltage events................................................................................................................... 20
5.3.1 Interruptions of the supply voltage......................................................................... 20
5.3.2 Supply voltage dips/swells ..................................................................................... 20
5.3.3 Transient overvoltages between live conductors and earth ................................ 22
6 High-voltage supply characteristics........................................................................................... 23
6.1 General .............................................................................................................................. 23
6.2 Continuous phenomena ................................................................................................... 23
6.2.1 Power frequency ..................................................................................................... 23
6.2.2 Supply voltage variations........................................................................................ 23
6.2.3 Rapid voltage changes ........................................................................................... 23
6.2.4 Supply voltage unbalance ...................................................................................... 24
6.2.5 Harmonic voltage .................................................................................................... 24
6.2.6 Interharmonic voltage ............................................................................................. 25
6.2.7 Mains signalling voltage on the supply voltage .................................................... 25
6.3 Voltage events................................................................................................................... 25
6.3.1 Interruptions of the supply voltage......................................................................... 25
6.3.2 Supply voltage dips/swells ..................................................................................... 25
6.3.3 Transient overvoltages between live conductors and earth ................................ 27
Annex A (informative) Special nature of electricity........................................................................ 28
Annex B (informative) Indicative values for voltage events and single rapid voltage
changes ............................................................................................................................................... 30
Bibliography ........................................................................................................................................ 33

Eliminato: 23
Formattato: Evidenziato

Eliminato: 23
Eliminato: 23
Eliminato: 23
Eliminato: 23
Eliminato: 23
Eliminato: 24
Eliminato: 24
Eliminato: 25
Eliminato: 25
Eliminato: 25
Eliminato: 25
Eliminato: 25
Eliminato: 27

prEN 50160:2008

Scope and object

1.1 Scope
This European Standard defines, describes and specifies the main characteristics of the voltage
at a network user's supply terminals in public low voltage, medium and high voltage electricity
distribution networks under normal operating conditions. This standard describes the limits or
values within which the voltage characteristics can be expected to remain over the whole of the
public distribution network and does not describe the average situation usually experienced by
an individual network user.
NOTE For the definitions of low, medium and high voltage see 3.1 to 3.3.

The European Standard does not apply under abnormal operating conditions including the
following:
a temporary supply arrangement to keep the network users supplied during condition arising
as a result of a fault, maintenance and construction work or to minimize the extent and
duration of a loss of supply;
in case of non-compliance of a network user's installation or equipment with the relevant
standards or with the technical requirements for connection, established either by the public
authorities or the network operator including the limits for the emission of conducted
disturbances;
NOTE A network users installation may include load as well as generation.

in exceptional situations, in particular,


exceptional weather conditions and other natural disasters,
third party interference,
acts by public authorities,
industrial actions (subject to legal requirements),
force majeure,
power shortages resulting from external events.
The voltage characteristics given in this standard are not intended to be used as
electromagnetic compatibility (EMC) levels or user emission limits for conducted disturbances in
public distribution networks.
The voltage characteristics given in this standard are not intended to be used to specify
requirements in equipment product standards and in installation standards.
NOTE The performance of equipment might be impaired if it is subjected to supply conditions which are not
specified in the equipment product standard.

This standard may be superseded in total or in part by the terms of a contract between the
individual network user and the network operator.
Measurement methods to be applied in this standard are described in EN 61000-4-30.
1.2 Object
The object of this European Standard is to define and describe the characteristics of the supply
voltage concerning
frequency,
magnitude,
wave form,

prEN 50160:2008

symmetry of the line voltages.


These characteristics are subject to variations during the normal operation of a supply system
due to changes of load, disturbances generated by certain equipment and the occurrence of
faults which are mainly caused by external events.
The characteristics vary in a manner which is random in time, with reference to any specific
supply terminal, and random in location, with reference to any given instant of time. Because of
these variations, the levels of the characteristics can be expected to be exceeded on a small
number of occasions.
Some of the phenomena affecting the voltage are particularly unpredictable, which make it very
difficult to give useful definite values for the corresponding characteristics. The values given in
this standard for such phenomena, e.g. voltage dips and voltage interruptions, shall be
interpreted accordingly.
2

Normative references

The following referenced documents are indispensable for the application of this document. For
dated references, only the edition cited applies. For undated references, the latest edition of the
referenced document (including any amendments) applies.
IEC 60038
+ A1
+ A2

1983
1994
1997

IEC 60050-161

IEC standard voltages

International Electrotechnical Vocabulary - Chapter 161:


Electromagnetic compatibility

IEC/TR 61000-2-8

2002

Electromagnetic compatibility (EMC) Part 2-8: Environment


Voltage dips and short interruptions on public electric power
supply systems with statistical measurement results

IEC 60364-4-44
+ A1

2001
2003

Electrical installations of buildings Part 4-44: Protection for


safety - Protection against voltage disturbances and
electromagnetic disturbances

IEC 60364-5-53
+ A1

2001
2002

Electrical installations of buildings Part 5-53: Selection and


erection of electrical equipment - Isolation, switching and
control

IEC 61000-3-7

1996

Electromagnetic compatibility (EMC) Part 3-7: Limits


Assessment of emission limits for HV and MV fluctuating loads

EN 60664-1

2003

Insulation coordination for equipment within low-voltage


systems Part 1: Principles, requirements and tests
(IEC 60664-1:1992 + A1:2000 + A2:2002)

EN 61000-3-3

1995

Electromagnetic compatibility (EMC) Part 3-3: Limits Limitation of voltage changes, voltage fluctuations and flicker
in public low-voltage supply systems, for equipment with rated
current <= 16 A per phase and not subject to conditional
connection (IEC 61000-3-3:1994)

EN 61000-4-30

2003

Electromagnetic compatibility (EMC) Part 4-30: Testing and


measurement techniques Power quality measurement
methods (IEC 61000-4-30:2003)

prEN 50160:2008

Definitions

For the purposes of this document, the following terms and definitions apply.
NOTE

References and compliance with IEV as far as possible - will be checked.

3.1
low voltage (LV)
voltage whose nominal r.m.s. value is Un 1 kV.
3.2
medium voltage (MV)
voltage whose declared r.m.s. value is 1 kV < UC 35 kV.
NOTE According to the existing network structures, in some countries the boundary between MV and HV can be
different.

3.3
high voltage (HV)
voltage whose declared r.m.s. value is 35 kV < UC 150 kV.
NOTE According to the existing network structures, in some countries the boundary between MV and HV can be
different.

3.4
network user
party being supplied by or supplying to an electricity supply network.
NOTE In several countries, the term network user includes network operators connected to a supply network with
the same or higher voltage level.

3.5
network operator
party responsible for operating, ensuring the maintenance of and, if necessary, developing the
supply network in a given area and, for ensuring the long term ability of the network to meet
reasonable demands for the electricity supply.
3.6
normal operating condition
for a supply network, condition of meeting load and generation demands, system switching and
clearing faults by automatic system protection excluding the abnormal operating conditions
listed in 1.1.
3.7
supply terminal
point in a public supply network designated as such and contractually fixed, at which electrical
energy is exchanged between contractual partners.
NOTE

This point can differ from, for example, the electricity metering point or the point of common coupling.

prEN 50160:2008

3.8
supply voltage
r.m.s. value of the voltage at a given time at the supply terminal, measured over a given
interval.
3.9
nominal voltage (Un)
voltage by which a supply network is designated or identified and to which certain
operating characteristics are referred.
3.10
declared supply voltage (Uc)
the declared supply voltage Uc is normally the nominal voltage Un of the supply network. If by
agreement between the network operator and the network user a voltage different from the
nominal voltage is applied to the terminal, then this voltage is the declared supply voltage U c.
3.11
frequency of the supply voltage
repetition rate of the fundamental wave of the supply voltage measured over a given interval of
time.
3.12
conducted disturbance
electromagnetic phenomenon propagated along the line conductors of a supply network. In
some cases an electromagnetic phenomenon is propagated across transformer windings and
hence between networks of different voltage levels. These disturbances may degrade the
performance of a device, equipment or system or they may cause damage.
3.13
voltage variation
increase or decrease of voltage normally due to load variations.
3.14
rapid voltage change
a single rapid variation of the r.m.s. value of a voltage between two consecutive levels which
are sustained for definite but unspecified durations (for more information see EN 61000-3-3).
3.15
voltage fluctuation
series of voltage changes or a cyclic variation of the voltage envelope.
[IEV 161-08-05]
3.16
flicker
impression of unsteadiness of visual sensation induced by a light stimulus whose luminance or
spectral distribution fluctuates with time.
[IEV 161-08-13]

prEN 50160:2008

NOTE Voltage fluctuation cause changes of the luminance of lamps which can create the visual phenomenon called
flicker. Above a certain threshold flicker becomes annoying. The annoyance grows very rapidly with the amplitude of
the fluctuation. At certain repetition rates even very small amplitudes can be annoying.

3.17
flicker severity
intensity of flicker annoyance defined by the UIE-IEC flicker measuring method and evaluated
by the following quantities:
short term severity (Pst ) measured over a period of ten minutes;
long term severity (Plt) calculated from a sequence of 12 Pst-values over a two hour
interval, according to the following expression:

Plt = 3

12

i =1

Psti
12

3.18
supply interruption
condition in which the voltage at the supply terminals is lower than 5 % of the reference voltage.
A supply interruption can be classified as

prearranged, when network users are informed in advance, to allow the execution of
scheduled works on the distribution network, or

accidental, caused by permanent or transient faults, mostly related to external events,


equipment failures or interference. An accidental interruption is classified as:
a long interruption (longer than three minutes);
a short interruption (up to and including three minutes).

NOTE 1 Normally, interruptions are being caused by the operation of switches or protecting devices.
NOTE 2 The effect of a prearranged interruption can be minimized by the network users by taking appropriate
measures.
NOTE 3 Accidental supply interruptions are unpredictable, largely random events
NOTE 4 For polyphase systems, an interruption happens when the voltage falls below 5 % of the reference voltage
on all phases (otherwise, it is a dip).
NOTE 5 In some countries, the term Very Short Interruptions (VSI) or transitory interruptions are used to classify
interruptions with duration shorter than 1 to 5 seconds. Such interruptions are related to automatic reclosing device
operation..

3.19
voltage dip
a temporary reduction of the voltage at a point in the electrical supply system below a specified
start threshold. For the purpose of this standard, the dip start threshold is equal to 90 % of the
reference voltage).
NOTE 1 Typically, a dip is associated with the occurrence and termination of a short circuit or other extreme current
increase on the system or installations connected to it.
NOTE 2 For the purpose of this standard, a voltage dip is a two dimensional electromagnetic disturbance, the level
of which is determined by both voltage and time (duration).

3.20
reference voltage (for voltage dips and swells evaluation)
a value specified as the base on which residual voltage, thresholds and other values are
expressed in per unit or percentage terms
NOTE For the purpose of this standard, the reference voltage is the nominal or declared voltage of the supply
system.

3.21

prEN 50160:2008

voltage dip start threshold


an r.m.s. value of the voltage on an electricity supply system specified for the purpose of
defining the start of a voltage dip.
3.22
voltage dip end threshold
an r.m.s. value of the voltage on an electricity supply system specified for the purpose of
defining the end of a voltage dip.
3.23
voltage dip duration
the time between the instant at which the voltage at a particular point of an electricity supply
system falls below the start threshold and the instant at which it rises to the end threshold. For
the purpose of the standard, the duration of a voltage dip is from 20 ms up to and including 1
min.
NOTE For polyphase events a dip begins when the voltage of at least one phase falls below the dip start threshold
and ends when the voltage on all phases is equal to or above the dip end threshold.

3.24
voltage dip residual voltage
the minimum value of r.m.s. voltage recorded during a voltage dip.
NOTE

For the purpose of this standard, the residual voltage is expressed as a percentage of the reference voltage.

3.25
voltage swell (temporary power frequency overvoltage)
a temporary increase of the voltage at a point in the electrical supply system above a specified
start threshold. For the purpose of this standard, the swell start threshold is equal to the 110 %
of the reference voltage (see CLC/TR 50422, Clause 3 for more information).
NOTE 1 For the purpose of this standard, a voltage swell is a two dimensional electromagnetic disturbance, the
level of which is determined by both voltage and time (duration).
NOTE 2 Voltage swells may appear between live conductors or between live conductors and earth. Depending on
the neutral arrangement, faults to ground may also give rise to overvoltages between healthy phases and neutral.

3.26
voltage swell start threshold
an r.m.s. value of the voltage on an electricity supply system specified for the purpose of
defining the start of a voltage swell.
3.27
voltage swell end threshold
an r.m.s. value of the voltage on an electricity supply system specified for the purpose of
defining the end of a voltage swell.
3.28
voltage swell duration
the time between the instant at which the voltage at a particular point of an electricity supply
system exceeds the start threshold and the instant at which it falls below the end threshold.
For the purpose of this standard, the duration of a voltage swell is from 20 ms up to and
including 1 min.
3.29
transient overvoltage

prEN 50160:2008

10

short duration oscillatory or non-oscillatory overvoltage usually highly damped and with a
duration of a few milliseconds or less.
[IEV 604-03-13 modified]
NOTE: Transient overvoltages are usually caused by lightning, switching or operation of fuses. The rise time of a
transient overvoltage can vary from less than a microsecond up to a few milliseconds.

3.30
harmonic voltage
sinusoidal voltage with a frequency equal to an integer multiple of the fundamental frequency of
the supply voltage. Harmonic voltages can be evaluated
individually by their relative amplitude (Uh) related to the fundamental voltage U1, where h is
the order of the harmonic,
globally, for example by the total harmonic distortion factor THD, calculated using the
following expression:

THD =

40

(u )
h= 2

NOTE: Harmonics of the supply voltage are caused mainly by network users' non-linear loads connected to all
voltage levels of the supply network. Harmonic currents flowing through the network impedance give rise to harmonic
voltages. Harmonic currents and network impedances and thus the harmonic voltages at the supply terminals vary in
time.

3.31
interharmonic voltage
sinusoidal voltage with a frequency between the harmonics, i.e. the frequency is not an integer
multiple of the fundamental.
NOTE Interharmonic voltages at closely adjacent frequencies can appear at the same time forming a wide band
spectrum.

3.32
voltage unbalance
condition in a polyphase system in which the r.m.s. values of the line-to-line voltages
(fundamental component), or the phase angles between consecutive line voltages, are not all
equal. The degree of the inequality is usually expressed as the ratios of the negative and zero
sequence components to the positive sequence component.
[IEV 161-08-09 modified]
NOTE In this European Standard, voltage unbalance is considered in relation to three-phase
negative phase sequence only.

systems

and

3.33
mains signalling voltage
signal superimposed on the supply voltage for the purpose of transmission of information in the
public supply network and to network users' premises. Three types of signals in the public
supply network can be classified:

ripple control signals: superimposed sinusoidal voltage signals in the range of 110 Hz to
3 000 Hz;

power-line-carrier signals: superimposed sinusoidal voltage signals in the range between


3 kHz to 148,5 kHz;

mains marking signals: superimposed short time alterations (transients) at selected points
of the voltage waveform.

11

prEN 50160:2008

Low-voltage supply characteristics

4.1 General
The present paragraph describes the voltage characteristics of electricity supplied by low
voltage public networks. In the following, a distinction is made between:
continuous phenomena, i.e. small deviations from the nominal value that occur continuously
over time. Such phenomena are mainly due to load pattern, changes of load or nonlinear
loads.
voltage events, sudden and significant deviations from normal or desired wave shape.
Voltage events are typically due to unpredictable events (e.g., faults) or to external causes
(e.g., weather, third party actions).
For continuous phenomena, limits are specified1 2; on the other side, for voltage events, only
indicative values can be given (see annex B).
The standard nominal voltage U n for public low voltage is U n = 230 V, either between phase and
neutral, or between phases.
for four-wire three phase systems:
Un = 230 V between phase and neutral;
for three-wire three phase systems:
Un = 230 V between phases.
NOTE In low voltage systems declared and nominal voltage are equal.

4.2 Continuous phenomena


4.2.1

Power frequency

The nominal frequency of the supply voltage shall be 50 Hz. Under normal operating conditions
the mean value of the fundamental frequency measured over 10 s shall be within a range of:
for systems with synchronous connection to an interconnected system:
50 Hz 1 %
(i.e. 49,5 Hz... 50,5 Hz)
during 99,5 % of a year;
50 Hz + 4 % / - 6 %
(i.e. 47 Hz... 52 Hz)
during 100 % of the time;
for systems with no synchronous connection to an interconnected system
(e.g. supply systems on certain islands):
50 Hz 2 %
(i.e. 49 Hz... 51 Hz)
during 95 % of a week;
50 Hz 15 %
(i.e. 42,5 Hz... 57,5 Hz)
during 100 % of the time.
4.2.2

Supply voltage variations

4.2.2.1 Requirements
Under normal operating conditions, voltage variations should not exceed 10 % of the nominal
voltage Un.
In cases of electricity supplies in networks not interconnected to transmission systems or for
special remote customers, voltage variations should not exceed +10% / -15% of Un. Network
users should be informed of the conditions.
NOTE 1. The actual power consumption required by individual network users is not fully predictable, in terms of
amount and of contemporary demand. As a consequence, networks are generally designed on a probabilistic basis.
1
2

For single rapid voltage changes, only indicative values are given for the time being.
For some specific parameters, in some national regulations stricter limits may exist.

prEN 50160:2008

12

If, following a complaint, measurements carried out by the network operator according to 4.2.2.2 indicate that the
magnitude of the supply voltage departs beyond Un+/-10% causing negative consequences for the network user, the
network operator should take remedial action in collaboration with the network user(s) depending on a risk
assessment. The sharing of complaint management and problem mitigation costs between the involved parties is
outside the scope of EN 50160. Temporarily, for the time needed to solve the problem, voltage variations should be
within the range +10% / -15% of Un , unless otherwise agreed with the network users.
NOTE 2 In accordance with relevant product and installation standards and application of IEC 60038, network users
appliances are typically designed to tolerate supply voltages of 10 % around the nominal system voltage, which is
sufficient to cover an overwhelming majority of supply conditions. It is generally not technically nor economically
viable to give all appliances the ability to handle wider voltage variations at supply terminals.
NOTE 3 Identification of what is a special remote customer can vary between countries, taking into account different
characteristics of national electric systems as, for instance, limitation of power on the supply terminal and/or power
factor limits.

4.2.2.2 Test method


When voltage measurements are required, they will be done in accordance with 5.2 of EN
61000-4-30 with a measurement period of at least one week.
Under normal operating conditions excluding the periods with interruptions the following limits
apply:

4.2.3

100% of all 10 min mean r.m.s. values of the supply voltage shall be below the upper
limit of + 10% given in 4.2.2.1 and
At least 99% of the 10 min mean r.m.s. values of the supply voltage shall be above the
lower limit of -10% given in 4.2.2.1 and with not more than two consecutive 10 min mean
r.m.s. values below the lower limit of 10%.
Rapid voltage changes

4.2.3.1 Single rapid voltage change


Rapid voltage changes of the supply voltage are mainly caused either by load changes in the
network users' installations or by switching in the system.
The voltage during a rapid voltage change must not exceed the voltage dip and/or the voltage
swell threshold, as it would otherwise be considered as a voltage dip or swell.
Some indicative values can be found in Annex B.
4.2.3.2 Flicker severity
Under normal operating conditions, in any period of one week the long term flicker severity
caused by voltage fluctuation should be P lt 1 for 95 % of the time.
NOTE Reaction to flicker is subjective and can vary depending on the perceived cause of the flicker and the period
over which it persists. In some cases P lt = 1 gives rise to annoyance, whereas in other cases higher levels of P lt are
found without annoyance.

4.2.4

Supply voltage unbalance

Under normal operating conditions, during each period of one week, 95 % of the 10 min mean
r.m.s. values of the negative phase sequence component (fundamental) of the supply voltage
shall be within the range 0 % to 2 % of the positive phase sequence component (fundamental).
In some areas with partly single phase or two phase connected network users' installations,
unbalances up to about 3 % at three-phase supply terminals occur.
NOTE In this European Standard only values for the negative sequence component are given because this
component is the relevant one for the possible interference of appliances connected to the system.

4.2.5

Harmonic voltage

13

prEN 50160:2008

Under normal operating conditions, during each period of one week, 95 % of the 10 min mean
r.m.s. values of each individual harmonic voltage shall be less than or equal to the value given
in Table 1. Resonances may cause higher voltages for an individual harmonic.
Moreover, the THD of the supply voltage (including all harmonics up to the order 40) shall be
less than or equal to 8 %.
NOTE The limitation to order 40 is conventional.

Table 1 - Values of individual harmonic voltages at the supply terminals


for orders up to 25 given in percent of the fundamental voltage U1
Odd harmonics
Not multiples of 3

Multiples of 3

Even harmonics

Order
h

Relative
voltage (Un)

Order
h

Relative
voltage (Un)

Order
h

Relative
voltage (Un)

6,0 %

5,0 %

2,0 %

5,0 %

1,5 %

1,0 %

11

3,5 %

15

0,5 %

6 24

0,5 %

13

3,0 %

21

0,5 %

17

2,0 %

19

1,5 %

23

1,5 %

25

1,5 %

NOTE No values are given for harmonics of order higher than 25, as they are usually small, but largely unpredictable due to
resonance effects.

4.2.6

Interharmonic voltage

The level of interharmonics is increasing due to the development of frequency converters and
similar control equipment. Levels are under consideration, pending more experience.
In certain cases interharmonics, even at low levels, give rise to flicker (see 4.2.3.2), or cause
interference in ripple control systems.
4.2.7

Mains signalling voltage on the supply voltage

In some countries the public distribution networks may be used by the public supplier for the
transmission of signals. Over 99 % of a day the 3 s mean of signal voltages shall be less than or
equal to the values given in Figure 1.

prEN 50160:2008

14

Voltage level in percent

Frequency in kHz

Figure 1 - Voltage levels of signal frequencies in percent of Un used


in public LV distribution networks
NOTE Power line carrier signalling with frequencies in the range from 95 kHz to 148,5 kHz may be used in network
users' installations. Though the use of the public system for the transmission of signals between network users is not
allowed, voltages of these frequencies up to 1,4 V r.m.s. in the public LV distribution network have to be taken into
account. Because of the possibility of mutual influences of neighbouring signalling installations the network user may
need to apply protection or appropriate immunity for his signalling installation against this influence.

4.3 Voltage events


4.3.1

Interruptions of the supply voltage

Interruptions are, by their nature, very unpredictable and variable from place to place and from
time to time. For the time being, it is not possible to give fully representative statistical results of
measurements of interruptions frequency covering the whole of European networks. A
reference for actual values recorded in the European networks concerning interruptions is given
in Annex B.
4.3.2

Supply voltage dips/swells

Voltage dips are typically originated by faults occurring in the public network or in the network
users installations.
Voltage swells are typically originated by switching operations, load disconnections etc.
Both phenomena are unpredictable and largely random. The annual frequency varies greatly
depending on the type of supply system and on the point of observation. Moreover, the
distribution over the year can be very irregular.
4.3.2.1 Voltage dip/swell measurement and detection
Voltage dips/swells shall be measured and detected according to EN 61000-4-30, using as
reference the nominal supply voltage for LV networks. The voltage dips/swells characteristics of
interest for this standard are residual voltage (maximum r.m.s. voltage for swells) and duration1.
On LV networks, for four-wire three phase systems, the line to neutral voltages shall be
considered; for three-wire three phase systems the line to line voltages shall be considered; in
case of a single phase connection, the supply voltage (line to line or line to neutral, according to
the customer connection) shall be considered.
1

In this standard, values are expressed in percentage terms of the reference voltage.

15

prEN 50160:2008

Conventionally, the dip threshold is equal to 90 % of the nominal voltage; the threshold for
swells is equal to the 110 % of the nominal voltage. The hysteresis is typically 2 %; reference
rules for hysteresis are given in clause 5.4.2.1 of EN 61000-4-30.
Note: For polyphase measurements, it is recommended that the number of phases affected by each event are
detected and stored.

4.3.2.2 Voltage dips evaluation


Voltage dips shall be evaluated according to EN 61000-4-30. Post treatment aimed at dips
evaluation depends on the intended purpose.
Typically, on LV networks:
if a three-phase system is considered, polyphase aggregation shall be applied;
polyphase aggregation consists in defining an equivalent event characterized by a
single duration and a single residual voltage;
time aggregation shall be applied; time aggregation consists in defining an
equivalent event in case of multiple successive events; the method used for multiple
events aggregation can be set according to the final use of data; some reference
rules are given in IEC TR 61000-2-8.
4.3.2.3 Voltage dips classification
For statistical purposes dips shall be classified according to the following table. The figures to
be put in the cells refer to the number of equivalent events (as defined in the previous
paragraph) 1.
Table 2: classification of dips according to residual voltage and duration
Residual voltage
u [%]

90>u>=80
80>u>=70
70>u>=40
40>u>=5
5 >u

Duration t [ms]
20 t 200

200 < t 500

CELL A1
CELL B1
CELL C1
CELL D1
CELL X1

CELL A2
CELL B2
CELL C2
CELL D2
CELL X2

500 < t 1000 1000 < t 5000


CELL A3
CELL B3
CELL C3
CELL D3
CELL X3

CELL A4
CELL B4
CELL C4
CELL D4
CELL X4

5000 < t
60000
CELL A5
CELL B5
CELL C5
CELL D5
CELL X5

Voltage dips are, by their nature, very unpredictable and variable from place to place and from
time to time. For the time being, it is not possible to give fully representative statistical results of
measurements of voltage dips frequency covering the whole of European networks. A reference
for actual values recorded in the European networks concerning dips is given in Annex B.
It should be noted that, due to the measurement method adopted, measurement uncertainty
affecting the results has to be taken into account: this is particularly relevant for shorter events.
Measurement uncertainty is addressed in EN 61000-4-30.
Dips duration depends generally on the protection strategy adopted on the network, that may
differ from network to network, depending on network structure and on neutral grounding. As a
consequence, typical durations are not necessarily matching the boundaries of columns of table
2.
4.3.2.4 Voltage swells evaluation
1

This table reflects the polyphase network performance. Further information is needed to consider events affecting
an individual single-phase voltage in three-phase systems. To calculate the latter, a different evaluation method has
to be applied.

prEN 50160:2008

16

Voltage swells shall be evaluated according to EN 61000-4-30. Post treatment aimed at swells
evaluation depends on the intended purpose.
Typically, on LV networks:
if a three phase system is considered, polyphase aggregation shall be applied;
polyphase aggregation consists in defining an equivalent event characterized by a
single duration and a single maximum r.m.s. voltage;
time aggregation shall be applied; time aggregation consists in defining an
equivalent event in case of multiple successive events; the method used for multiple
events aggregation can be set according to the final use of data; some reference
rules are given in IEC TR 61000-2-8.
4.3.2.5 Voltage swells classification
Swells shall be classified according to the following table. The figures to be put in the cells refer
to the number of equivalent events (as defined in the previous paragraph) 1.
Table 3: classification of swells according to maximum voltage and duration
Swell voltage u [%]
u>=120
120>u>=110

20 t 500
CELL S1
CELL T1

Duration t [ms]
500 < t 5000
CELL S2
CELL T2

5000 < t 60000


CELL S3
CELL T3

A voltage swell generally happens in case of switching operations and load disconnections.
Note 1 Faults in the public distribution network, or in a network user's installation, typically give rise to temporary
power frequency overvoltages between live conductors and earth; such overvoltages disappear when the fault is
cleared. Some indicative values are given in Annex B.
Note 2 For the classification of swells between live conductors and earth, reference can be made to EN 60364-4-442.

4.3.3

Transient overvoltages between live conductors and earth

Transient overvoltages at the supply terminals are generally caused by lightning (induced
overvoltage) or by switching in the system.
NOTE 1 The rise time can cover a wide range from milliseconds down to much less than a microsecond. However,
for physical reasons transients of longer durations usually have much lower amplitudes. Therefore, the coincidence of
high amplitudes and a long rise time is extremely unlikely.
NOTE 2 The energy content of a transient overvoltage varies considerably according to the origin. An induced
overvoltage due to lightning generally has a higher amplitude but lower energy content than an overvoltage caused
by switching, because of the generally longer duration of such switching overvoltages.
NOTE 3 LV Installations and end users appliances are designed in accordance with standard EN 60664-1, to
withstand transient overvoltages in an overwhelming majority of situations. Where necessary, according to
IEC 60364-4-44, surge protective devices should be selected, according to IEC 60364-5-53, to take account of the
actual situations. This is assumed to cover the induced over-voltages due to both lightning and switching.
1

This table reflects the polyphase network performance. Further information is needed to
consider events affecting an individual single phase voltage in three-phase systems. To
calculate the latter, a different evaluation method has to be applied.

17

prEN 50160:2008

Medium-voltage supply characteristics

5.1 General
Network users with demands exceeding the capacity of the low voltage network are generally
supplied at declared voltages above 1 kV. This standard applies to such electricity supplies at
declared voltages up to and included 35 kV.
NOTE Network users may be supplied at such voltages also to satisfy special requirements or to mitigate conducted
disturbances emitted by their equipment.

The present paragraph describes the voltage characteristics of electricity supplied by medium
voltage public networks. In the following, a distinction is made between:
voltage variations, i.e. small deviations from the nominal value that occur continuously over
time. Voltage variations are mainly due to load pattern, changes of load or nonlinear loads.
voltage events, sudden and significant deviations from normal or desired wave shape.
Voltage events are typically due to unpredictable events (e.g., faults) or to external causes
(e.g., weather, third party actions).
For voltage variations, definite limits are given 1, 2; on the other side, for voltage events, only
indicative values can be given (see annex B).
The magnitude of voltage is given by the declared voltage Uc.
5.2 Continuous phenomena
5.2.1

Power frequency

The nominal frequency of the supply voltage shall be 50 Hz. Under normal operating conditions
the mean value of the fundamental frequency measured over 10 s shall be within a range of:
for systems with synchronous connection to an interconnected system:
50 Hz 1 %
(i.e. 49,5 Hz... 50,5 Hz)
during 99,5 % of a year;
50 Hz + 4 % / - 6 %
(i.e. 47 Hz... 52 Hz)
during 100 % of the time,
for systems with no synchronous connection to an interconnected system
(e.g. supply systems on certain islands):
50 Hz 2 %
(i.e. 49 Hz... 51 Hz)
during 95 % of a week;
50 Hz 15 %
(i.e. 42,5 Hz... 57,5 Hz)
during 100 % of the time.
5.2.2

Supply voltage variations

5.2.2.1 Requirements
Under normal operating conditions, voltage variations should not exceed 10 % of the declared
voltage Uc .
In cases of electricity supplies in networks not interconnected to transmission systems or for
special remote customers, voltage variations should not exceed +10% / -15% of Uc. Network
users should be informed of the conditions.
NOTE 1. The actual power consumption required by individual network users is not fully predictable, in terms of
amount and of contemporary demand. As a consequence, networks are generally designed on a probabilistic basis.
If, following a complaint, measurements carried out by the network operator according to 5.2.2.2 indicate that the
magnitude of the supply voltage departs beyond Uc+/-10%, causing negative consequences for the network user, the
Network operators should take remedial action in collaboration with the network user(s) depending on a risk
1
2

For single rapid voltage changes, only indicative values are given.
For some specific parameter, in single countries stricter limits can be found.

prEN 50160:2008

18

assessment. The sharing of complaint management and problem mitigation costs between the involved parties is
outside the scope of EN 50160. Temporarily, for the time needed to solve the problem, voltage variations should be
within the range +10% / -15% of Uc , unless otherwise agreed with the network users.
NOTE 2 Identification of what is a special remote customer can vary between countries, taking into account different
characteristics of national electric systems as, for instance, limitation of power on the supply terminal and/or power
factor limits.

5.2.2.2 Test method


When voltage measurements are required, they will be done in accordance with 5.2 of EN
61000-4-30 with a measurement period of at least one week
Under normal operating conditions excluding the periods with interruptions the following limits
apply:

5.2.3

100% of all 10 min mean r.m.s. values of the supply voltage shall be below the upper
limit of + 10% given in 5.2.2.1 and
At least 99% of the 10 min mean r.m.s. values of the supply voltage shall be above the
lower limit of -10% given in 5.2.2.1 and with not more than two consecutive 10 min mean
r.m.s. values below the lower limit of 10%.
Rapid voltage changes

5.2.3.1 Single rapid voltage change


Rapid voltage changes of the supply voltage are mainly caused either by load changes in the
network users' installations or by switching in the system.
The voltage during a rapid voltage change must not exceed the voltage dip and/or the voltage
swell threshold, as it would otherwise be considered as a voltage dip or swell.
Some indicative values can be found in Annex B.
5.2.3.2 Flicker severity
Under normal operating conditions, in any period of one week the long term flicker severity
caused by voltage fluctuation should be P lt 1 for 95 % of the time.
This value was chosen on the assumption that the transfer coefficient between MV and LV
system is unity. In practice the transfer coefficients between MV levels and LV levels can be
less than 1.
In case of complaints, MV limit shall be chosen in such a way that in LV the Plt values do not
exceed 1, according to the stages described in IEC 61000-3-7.
5.2.4

Supply voltage unbalance

Under normal operating conditions, during each period of one week, 95 % of the 10 min mean
r.m.s. values of the negative phase sequence component of the supply voltage shall be within
the range 0 % to 2 % of the positive phase sequence component. In some areas unbalances up
to 3 % occur.
NOTE In this European Standard only values for the negative sequence component are given because this
component is the relevant one for the possible interference of appliances connected to the system.

5.2.5

Harmonic voltage

Under normal operating conditions, during each period of one week, 95 % of 10 min mean
r.m.s. values of each individual harmonic voltage shall be less than or equal to the value given
in Table 4. Resonances may cause higher voltages for an individual harmonic.

19

prEN 50160:2008

Moreover, the THD of the supply voltage (including all harmonics up to the order 40) shall be
less than or equal to 8 %.
NOTE The limitation to order 40 is conventional.

Table 4 - Values of individual harmonic voltages at the supply terminals


for orders up to 25 given in percent of the fundamental voltage U1
Odd harmonics
Not multiples of 3

Even harmonics
Multiples of 3

Order
h

Relative
voltage (Uc)

Order
h

6,0 %

5,0 %

11

Relative
voltage (Uc)

Order
h

Relative
voltage (Uc)

5,0 % a

2,0 %

1,5 %

1,0 %

3,5 %

15

0,5 %

6 24

0,5 %

13

3,0 %

21

0,5 %

17

2,0 %

19

1,5 %

23

1,5 %

25

1,5 %

Depending on the network design the value for the third harmonic order can be substantially lower.

NOTE No values are given for harmonics of order higher than 25, as they are usually small, but largely unpredictable due to
resonance effects.

5.2.6

Interharmonic voltage

The level of interharmonics is increasing due to the development of frequency converters and
similar control equipment. Levels are under consideration, pending more experience.
In certain cases interharmonics, even at low levels, give rise to flicker (see 5.4.2), or cause
interference in ripple control system.
5.2.7

Mains signalling voltage on the supply voltage

In some countries the public distribution networks may be used by the public supplier for the
transmission of signals. Over 99 % of a day the 3 s mean of the signal voltages shall be less or
equal to the values given in Figure 2.
NOTE It is assumed that network users do not use the public MV network for signalling purposes.

prEN 50160:2008

20

Voltage level in percent

Frequency in kHz

Figure 2 - Voltage levels of signal frequencies in percent of Uc


used in public MV distribution networks
5.3 Voltage events
5.3.1

Interruptions of the supply voltage

Interruptions are, by their nature, very unpredictable and variable from place to place and from
time to time. For the time being, it is not possible to give fully representative statistical results of
measurements of interruptions frequency covering the whole of European networks. A
reference for actual values recorded in the European networks concerning interruptions is given
in Annex B.
5.3.2

Supply voltage dips/swells

Voltage dips are typically originated by faults occurring in the public network or in the network
users installations.
Voltage swells are typically originated by switching operations, load disconnections etc.
Both phenomena are unpredictable and largely random. The annual frequency varies greatly
depending on the type of supply system and on the point of observation. Moreover, the
distribution over the year can be very irregular.
5.3.2.1 Voltage dip/swell measurement and detection
Voltage dips/swells shall be measured and detected according to EN 61000-4-30, using as
reference the declared supply voltage for MV networks. The voltage dips/swells characteristics
of interest for this standard are residual voltage (maximum r.m.s. voltage for swells) and
duration1.
Typically, on MV networks, the line to line voltages shall be considered.
Conventionally, the dip threshold is equal to 90 % of the nominal voltage; the threshold for
swells is equal to the 110 % of the nominal voltage. The hysteresis is typically 2 %; reference
rules for hysteresis are given in clause 5.4.2.1 of EN 61000-4-30.
Note: For polyphase measurements, it is recommended that the number of phases affected by
each event are detected and stored.
1

In this standard, values are expressed in percentage terms of the reference voltage.

21

prEN 50160:2008

5.3.2.2 Voltage dips evaluation


Voltage dips shall be evaluated according to EN 61000-4-30. Post treatment aimed at dips
evaluation depends on the intended purpose.
Typically, on MV networks:
polyphase aggregation is applied; polyphase aggregation consists in defining an
equivalent event characterized by a single duration and a single residual voltage;
time aggregation consists in defining an equivalent event in case of multiple
successive events; the method used for multiple events aggregation can be set
according to the final use of data; some reference rules are given in IEC TR 610002-8.
5.3.2.3 Voltage dips classification
For statistical purposes dips shall be classified according to the following table. The figures to
be put in the cells refer to the number of equivalent events (as defined in the previous
paragraph) 1.
Table 5: classification of dips according to residual voltage and duration
Residual voltage
u [%]

90>u>=80
80>u>=70
70>u>=40
40>u>=5
5 >u

Duration t [ms]
20 t 200

200 < t 500

CELL A1
CELL B1
CELL C1
CELL D1
CELL X1

CELL A2
CELL B2
CELL C2
CELL D2
CELL X2

500 < t 1000 1000 < t 5000


CELL A3
CELL B3
CELL C3
CELL D3
CELL X3

CELL A4
CELL B4
CELL C4
CELL D4
CELL X4

5000 < t
60000
CELL A5
CELL B5
CELL C5
CELL D5
CELL X5

Voltage dips are, by their nature, very unpredictable and variable from place to place and from
time to time. For the time being, it is not possible to give fully representative statistical results of
measurements of voltage dips frequency covering the whole of European networks. A reference
for actual values recorded in the European networks concerning dips is given in Annex B.
It should be noted that, due to the measurement method adopted, measurement uncertainty
affecting the results has to be taken into account: this is particularly relevant for shorter events.
Measurement uncertainty is addressed in EN 61000-4-30.
Dips duration depends generally on the protection strategy adopted on the network, that may
differ from network to network, depending on network structure and on neutral grounding. As a
consequence, typical durations are not necessarily matching the boundaries of columns of table
5.
5.3.2.4 Voltage swells evaluation
Voltage swells shall be evaluated according to EN 61000-4-30. Post treatment aimed at swells
evaluation depends on the intended purpose.
Typically, on MV networks:
polyphase aggregation shall be applied; polyphase aggregation consists in defining
an equivalent event characterized by a single duration and a single maximum r.m.s.
voltage;
time aggregation shall be applied; time aggregation consists in defining an
equivalent event in case of multiple successive events; the method used for multiple
events aggregation can be set according to the final use of data; some reference
rules are given in IEC TR 61000-2-8.
1

This table reflects the polyphase network performance. Further information is needed to consider events affecting
an individual single-phase voltage in three-phase systems. To calculate the latter, a different evaluation method has
to be applied.

prEN 50160:2008

22

5.3.2.5 Voltage swells classification


Swells shall be classified according to the following table. The figures to be put in the cells refer
to the number of equivalent events (as defined in the previous paragraph) 1.
Table 6: classification of swells according to maximum voltage and duration
Swell voltage u [%]
u>120
120>u>=110

20 t 500
CELL S1
CELL T1

Duration t [ms]
500 < t 5000
CELL S2
CELL T2

5000 < t 60000


CELL S3
CELL T3

A voltage swell generally happens in case of switching operations and load disconnections.
Faults in the public distribution network, or in a network user's installation, give rise to temporary
power frequency overvoltages between live conductors and earth; such overvoltages disappear
when the fault is cleared. Some indicative values are given in Annex B.
5.3.3

Transient overvoltages between live conductors and earth

Transient overvoltages in MV supply systems are caused by switching or, directly or by


induction, by lightning. Switching overvoltages generally are lower in amplitude than lightning
overvoltages, but they can have a shorter rise time and/or longer duration.
NOTE The network users' insulation coordination scheme should be compatible with that adopted by the supplier.
1

This table reflects the polyphase network performance. Further information is needed to
consider events affecting an individual single phase voltage in three-phase systems. To
calculate the latter, a different evaluation method has to be applied.

23

prEN 50160:2008

High-voltage supply characteristics

6.1 General
Network users with demands exceeding the capacity of the medium voltage network are
generally supplied at declared voltages above 35 kV. This standard applies to such electricity
supplies at declared voltages up to and included 150 kV.
NOTE Network users may be supplied at such voltages also to satisfy special requirements or to mitigate conducted
disturbances emitted by their equipment.

The present paragraph describes the voltage characteristics of electricity supplied by medium
voltage public networks. In the following, a distinction is made between:
voltage variations, i.e. small deviations from the nominal value that occur continuously over
time. Voltage variations are mainly due to load pattern, changes of load or nonlinear loads.
voltage events, sudden and significant deviations from normal or desired wave shape.
Voltage events are typically due to unpredictable events (e.g., faults) or to external causes
(e.g., weather, third party actions).
For voltage variations, definite limits are given1,2; on the other side, for voltage events, only
indicative values can be given (see annex B).
The magnitude of voltage is given by the declared voltage Uc.
6.2 Continuous phenomena
6.2.1

Power frequency

The nominal frequency of the supply voltage shall be 50 Hz. Under normal operating conditions
the mean value of the fundamental frequency measured over 10 s shall be within a range of:
for systems with synchronous connection to an interconnected system:
50 Hz 1 %
(i.e. 49,5 Hz... 50,5 Hz)
during 99,5 % of a year;
50 Hz + 4 % / - 6 %
(i.e. 47 Hz... 52 Hz)
during 100 % of the time,
for systems with no synchronous connection to an interconnected system
(e.g. supply systems on certain islands):
50 Hz 2 %
(i.e. 49 Hz... 51 Hz)
during 95 % of a week;
50 Hz 15 %
(i.e. 42,5 Hz... 57,5 Hz)
during 100 % of the time.
6.2.2

Supply voltage variations

As the number of customers supplied directly from HV networks are limited and normally
subject to individual contracts, no limits for supply voltage variations are given in this standard.
Existing product standards for HV equipment should be considered.
6.2.3

Rapid voltage changes

6.2.3.1 Single rapid voltage change


1
2

For single rapid voltage changes, only indicative values are given.
For some specific parameter, in single countries stricter limits can be found.

prEN 50160:2008

24

Rapid voltage changes of the supply voltage are mainly caused either by load changes in the
network users' installations or by switching in the system.
The voltage during a rapid voltage change must not exceed the voltage dip and/or the voltage
swell threshold, as it would otherwise be considered as a voltage dip or swell.
Formattato: Evidenziato

6.2.3.2 Flicker severity


Under normal operating conditions, in any period of one week the long term flicker severity
caused by voltage fluctuation should be P lt 1 for 95 % of the time.
This value was chosen on the assumption that the transfer coefficient between HV and LV
system is unity. In practice the transfer coefficients between HV levels and LV levels can be
less than 1.
In case of complaints, HV limit shall be chosen in such a way that in LV the Pl t values do not
exceed 1, according to the stages described in IEC 61000-3-7.
6.2.4

Supply voltage unbalance

Under normal operating conditions, during each period of one week, 95 % of the 10 min mean
r.m.s. values of the negative phase sequence component of the supply voltage shall be within
the range 0 % to 2 % of the positive phase sequence component. In some areas unbalances up
to 3 % occur.
NOTE In this European Standard only values for the negative sequence component are given because this
component is the relevant one for the possible interference of appliances connected to the system.

6.2.5

Harmonic voltage

Under normal operating conditions, during each period of one week, 95 % of 10 min mean
r.m.s. values of each individual harmonic voltage shall be less than or equal to the value given
in Table 7. Resonances may cause higher voltages for an individual harmonic.
Moreover, the THD of the supply voltage (including all harmonics up to the order 40) shall be
less than or equal to 5 %.
Limits for harmonic higher than 13 do not apply for HV meshed networks exceeding 90 kV
(included) of nominal voltage.
NOTE The limitation to order 40 is conventional. The measurement of higher order harmonics is not reliable; further
information is given in Annex A 2 of EN 61000-4-30.

Table 7 - Values of individual harmonic voltages at the supply terminals


for orders up to 25 given in percent of the fundamental voltage U1
Odd harmonics
Not multiples of 3
Multiples of 3
Order
Relative
Order
Relative
h
voltage
h
voltage
5
4%
3
3%
7
3%
9
1,3 %
11
2%
15
0,5 %
13
1,8 %
21
0,5 %
17
1,5 %
19
1,3 %
23
1%
25
0,9 %

Even harmonics
Order
h
2
4
6 .. 24

Relative
voltage
1,9 %
1%
0,5 %

25

prEN 50160:2008

Depending on the network design the value for the third harmonic order can be substantially lower.

NOTE No values are given for harmonics of order higher than 25, as they are usually small, but largely unpredictable due to
resonance effects.

6.2.6

Interharmonic voltage

Due to the low resonance frequency of the HV network, no values are given for interharmonic
voltage.
NOTE: Due to the very low resonant frequency in HV grid (200 500 Hz) caused by high capacities and
inductances, interharmonics are of minor relevance in HV networks.

6.2.7

Mains signalling voltage on the supply voltage

Due to the low resonance frequency of the HV network, no values are given for mains signalling
voltage.
6.3 Voltage events
6.3.1

Interruptions of the supply voltage

Interruptions are, by their nature, very unpredictable and variable from place to place and from
time to time. For the time being, it is not possible to give fully representative statistical results of
measurements of interruptions frequency covering the whole of European networks. A
reference for actual values recorded in the European networks concerning interruptions is given
in Annex B.
6.3.2 Supply voltage dips/swells
Voltage dips are typically originated by faults occurring in the public network or in the network
users installations.
Voltage swells are typically originated by switching operations, load disconnections etc.
Both phenomena are unpredictable and largely random. The annual frequency varies greatly
depending on the type of supply system and on the point of observation. Moreover, the
distribution over the year can be very irregular.

6.3.2.1

Voltage dip/swell measurement and detection


Voltage dips/swells shall be measured and detected according to EN 61000-4-30, using as
reference the declared supply voltage for HV networks. The voltage dips/swells characteristics
of interest for this standard are residual voltage (maximum r.m.s. voltage for swells) and
duration1.
Typically, on HV networks, the line to line voltages shall be considered.
Conventionally, the dip threshold is equal to 90 % of the reference voltage; the threshold for
swells is equal to the 110 % of the nominal voltage. The hysteresis is typically 2 %; reference
rules for hysteresis are given in clause 5.4.2.1 of EN 61000-4-30.
Note: For polyphase measurements, it is recommended that the number of phases affected by each event are
detected and stored.

6.3.2.2 Voltage dips evaluation


Voltage dips shall be evaluated according to EN 61000-4-30. Post treatment aimed at dips
evaluation depends on the intended purpose.
Typically, on HV networks:
1

In this standard, values are expressed in percentage terms of the reference voltage.

prEN 50160:2008

26

polyphase aggregation is applied; polyphase aggregation consists in defining an


equivalent event characterized by a single duration and a single residual voltage;
time aggregation consists in defining an equivalent event in case of multiple
successive events; the method used for multiple events aggregation can be set
according to the final use of data; some reference rules are given in IEC TR 610002-8.

6.3.2.3 Voltage dips classification


For statistical purposes dips shall be classified according to the following table. The figures to
be put in the cells refer to the number of equivalent events (as defined in the previous
paragraph) 1.
Table 8: classification of dips according to residual voltage and duration
Residual voltage
u [%]

90>u>=80
80>u>=70
70>u>=40
40>u>=5
5 >u

Duration t [ms]
20 t 200

200 < t 500

CELL A1
CELL B1
CELL C1
CELL D1
CELL X1

CELL A2
CELL B2
CELL C2
CELL D2
CELL X2

500 < t 1000 1000 < t 5000


CELL A3
CELL B3
CELL C3
CELL D3
CELL X3

CELL A4
CELL B4
CELL C4
CELL D4
CELL X4

5000 < t
60000
CELL A5
CELL B5
CELL C5
CELL D5
CELL X5

Voltage dips are, by their nature, very unpredictable and variable from place to place and from
time to time. For the time being, it is not possible to give fully representative statistical results of
measurements of voltage dips frequency covering the whole of European networks.
It should be noted that, due to the measurement method adopted, measurement uncertainty
affecting the results has to be taken into account: this is particularly relevant for shorter events.
Measurement uncertainty is addressed in EN 61000-4-30.
Dips duration depends generally on the protection strategy adopted on the network, that may
differ from network to network, depending on network structure and on neutral grounding. As a
consequence, typical durations are not necessarily matching the boundaries of columns of table
8.
6.3.2.4 Voltage swells evaluation
Voltage swells shall be evaluated according to EN 61000-4-30. Post treatment aimed at swells
evaluation depends on the intended purpose.
Typically, on HV networks:
polyphase aggregation shall be applied; polyphase aggregation consists in defining
an equivalent event characterized by a single duration and a single maximum rms
voltage;
time aggregation shall be applied; time aggregation consists in defining an
equivalent event in case of multiple successive events; the method used for multiple
events aggregation can be set according to the final use of data; some reference
rules are given in IEC TR 61000-2-8.
6.3.2.5 Voltage swells classification

This table reflects the polyphase network performance. Further information is needed to consider events affecting
an individual single-phase voltage in three-phase systems. To calculate the latter, a different evaluation method has
to be applied.

27

prEN 50160:2008

Swells shall be classified according to the following table. The figures to be put in the cells refer
to the number of equivalent events (as defined in the previous paragraph) 1.
Table 9: classification of swells according to maximum voltage and duration
Swell voltage u [%]
u>120
120>u>=110

20 t 500
CELL S1
CELL T1

Duration t [ms]
500 < t 5000
CELL S2
CELL T2

5000 < t 60000


CELL S3
CELL T3

A voltage swell generally happens in case of switching operations and load disconnections.
Faults in the public distribution network, or in a network user's installation, give rise to temporary
power frequency overvoltages between live conductors and earth; such overvoltages disappear
when the fault is cleared.
Generally, temporary power frequency overvoltages in HV do not cause any network users
concern as normally any load is connected via transformers with different types of neutral
grounding.
6.3.3

Transient overvoltages between live conductors and earth

Transient overvoltages in HV supply systems are caused by switching or, directly or by


induction, by lightning. Switching overvoltages generally are lower in amplitude than lightning
overvoltages, but they may have a shorter rise time and/or longer duration.
NOTE The network users' insulation coordination scheme must be compatible with that adopted by the supplier.

This table reflects the polyphase network performance. Further information is needed to consider events affecting
an individual single phase voltage in three -phase systems. To calculate the latter, a different evaluation method has
to be applied.

prEN 50160:2008

28

Annex A
(informative)
Special nature of electricity
Electricity is an energy form which is particularly versatile and adaptable. It is utilised by being
converted into several other forms of energy: heat, light, mechanical energy, and the many
electromagnetic, electronic, acoustic and visual forms which are the bases of modern
telecommunications, information technology and entertainment.
Electricity as delivered to the network users has several characteristics which are variable and
which affect its usefulness to the network user. This standard describes characteristics of
electricity in terms of the alternating voltage. With respect to the use of electricity it is desirable
that the supply voltage would alternate at a constant frequency, with a perfect sine wave and a
constant magnitude. In practice, there are many factors which cause departures from this. In
contrast to normal products, application is one of the main factors which influence the variation
of "characteristics".
The flow of energy to the network user's appliances gives rise to electric currents which are
more or less proportional to the magnitudes of the network users' demands. As these currents
flow through the conductors of the supply system, they give rise to voltage drops. The
magnitude of the supply voltage for an individual network user at any instant is a function of the
cumulative voltage drops on all the components of the system through which that network user
is supplied, and is determined both by the individual demand and by the simultaneous demands
of other network users. Since each network user's demand is constantly varying, and there is a
further variation in the degree of coincidence between the demands of several network users,
the supply voltage is also variable. For this reason, this standard deals with the voltage
characteristics in statistical or probabilistic terms. It is in the economic interests of the network
user that the standard of supply should relate to normally expected conditions rather than to
rare contingencies, such as an unusual degree of coincidence between the demands of several
appliances or several network users.
Electricity reaches the network user through a system of generation, transmission and
distribution equipment. Each component of the system is subject to damage or failure due to the
electrical, mechanical and chemical stresses which arise from several causes, including
extremes of weather, the ordinary processes of wear and deterioration with age, and
interference by human activities, birds, animals, etc. Such damage can affect or even interrupt
the supply to one or to many network users.
To keep the frequency constant requires the amount of running generation capacity to be
matched instant by instant to the simultaneous combined demand. Because both the generation
capacity and the demand are liable to change in discrete amounts, especially in the event of
faults on the generation, transmission or distribution networks, there is always a risk of a
mismatch, resulting in an increase or decrease of the frequency. This risk is reduced, however,
by connecting many systems into one large interconnected system, the generation capacity of
which is very great relative to the changes which are likely to occur.
There are several other characteristics that may have a disturbing or damaging effect on
network users' equipment, or even on the network users. Some of these disturbing
characteristics arise from unavoidable transient events in the supply system itself, resulting from
faults or switching, or caused by atmospheric phenomena (lightning). Others, however, are the
result of various uses of electricity which directly alter the waveform of the voltage, impose a
particular pattern on its magnitude, or superimpose signalling voltages. Coincidentally with the
modem proliferation of equipment which has these effects, there is also an increase in the
equipment which is susceptible to the disturbances.

29

prEN 50160:2008

This European Standard defines where possible the variations of the characteristics normally to
be expected. In other cases the standard provides the best possible indication of what, in
quantitative terms, is to be expected.
Since there is a considerable diversity in the structures of the distribution networks in different
areas, arising from differences in load density, population dispersion, local topography, etc.
many network users will experience considerably smaller variations of the voltage
characteristics than the values given in this standard.
It is a particular feature of electricity that, in respect of some of its characteristics, its quality is
affected by the user rather than by the producer or supplier. In these cases the network user is
an essential partner, with the supplier, in the effort to maintain the quality of electricity.
It should be noted that this question is addressed directly by other standards, already published
or in preparation: Emission standards govern the levels of electromagnetic disturbances which
network users' equipment may be allowed to generate. Immunity standards set down
disturbance levels which the equipment should be capable of tolerating without undue damage
or loss of function. A third set of standards, for electromagnetic compatibility levels, has the
function of enabling coordination and coherence of the emission and immunity standards, with
the overall objective of achieving electromagnetic compatibility.
Although this standard has obvious links with compatibility levels, it is important to note that it
relates to voltage characteristics of electricity. It is not a standard for compatibility levels. It
should be especially noted that the performance of equipment might be impaired, if the
equipment is subjected to supply conditions more severe than specified in their product
standard.

prEN 50160:2008

30

Annex B
(informative)
Indicative values for voltage events and single rapid voltage changes

The present Annex B is aimed at providing the reader with some information about indicative
values currently available at a European level for some of the events defined and described in
the standard. Some information is also given about the way of using values given in the
standard, and about the way of collecting data of further measurement campaigns, in order to
allow for comparisons between different systems and to have homogeneous data at a European
level.
As many monitoring systems are in place in some countries, further information is available at a
national level.
At a national level, more precise figures can be found; furthermore, some regulations may exist.
B.1

Long interruptions of the supply voltage

Under normal operating conditions the annual frequency of voltage interruptions longer than
three minutes varies substantially between areas. This is due to, among others, differences in
system layout (e.g cable systems versus overhead line systems), environmental and climatic
conditions etc. To get information about what can be expected, the local network operator
should be consulted. In different countries national interruption statistics exist giving indicative
values. The CEER Benchmarking Reports on Quality Supply give some statistics for a certain
number of European countries and a review of applicable regulatory standards for long
interruptions.
Rules for aggregating events should be considered when comparing statistical values for long
interruptions.
B.2

Short interruptions of the supply voltage

The duration of most of the short interruptions may be less than some seconds. Indicative
values, intended to provide readers with information on the range of magnitude which can be
expected, can be found in IEC TR 61000-2-8 (UNIPEDE statistics).
When comparing statistical values for short interruptions, the following issues should be
considered:
rules for aggregating events,
the possible inclusion of Very Short Interruptions (VSI) or transitory interruptions.
In some documents short interruptions are considered as having durations not exceeding one
minute. Sometimes control schemes are applied which need operating times of up to three
minutes in order to avoid long voltage interruptions.
B.3

Voltage dips and swells

The swells treated in this paragraph are between live conductors.


Use of Table 2, 5 and 8
As detailed in product standards, voltage dips and swells, according to their severity, can impair
the operation of equipment.
Classes 2 and 3 are defined in EN 61000-4-11 and in EN 61000-4-34.
Although the cells of the table 2,5 and 8 are not exactly coincident with the test levels table, it
can be expected that equipment tested according to the relevant product standard should cope
with voltage dips as indicated in the cells:

A1, B1, A2, B2 for class 2;

31

prEN 50160:2008

A1, B1, C1, A2, B2, A3, A4 for class 3.

Compatibility levels for industrial power networks are defined in EN 61000-2-4.


Table 2, 5 and 8 data can help the user to identify the expected performance of the network; in
order to assess the probable behaviour of the equipment connected, its immunity has to be
considered in accordance with such data.
The specification of immunity requirements (including tests specifications and performance
criteria) is the responsibility of the product committees. Generic EMC standards (EN 61000-6-1
and 61000-6-2) apply to products operating in a particular environment for which no dedicated
product family /product EMC standards exist. Nevertheless, and for information only, the
performance criteria are reported in the following.
Performance criteria
Performance criterion A: The apparatus shall continue to operate as intended during and after
the test. No degradation of performance or loss of function is allowed below a performance level
specified by the manufacturer, when the apparatus is used as intended. The performance level
may be replaced by a permissible loss of performance. If the minimum performance level or the
permissible performance loss is not specified by the manufacturer, either of these may be
derived from the product description and documentation and what the user may reasonably
expect from the apparatus if used as intended.
Performance criterion B: The apparatus shall continue to operate as intended after the test. No
degradation of performance or loss of function is allowed below a performance level specified
by the manufacturer, when the apparatus is used as intended.
The performance level may be replaced by a permissible loss of performance. During the test,
degradation of performance is however allowed. No change of actual operating state or stored
data is allowed.
If the minimum performance level or the permissible performance loss is not specified by the
manufacturer, either of these may be derived from the product description and documentation
and what the user may reasonably expect from the apparatus if used as intended.
Performance criterion C: Temporary loss of function is allowed, provided the function is selfrecoverable or can be restored by the operation of the controls."
Currently available indicative values
The vast majority of voltage dips has a duration less than 1 s and a residual voltage above 40
%. However, voltage dips with smaller residual voltage and longer duration can occur
infrequently. In some areas voltage dips with residual voltage between 90 % and 85 % of Uc can
occur very frequently as a result of the switching of loads in network users' installations.
Indicative values, which are intended to provide readers with information on the range of
magnitude which can be expected, can be found in IEC TR 61000-2-8 (UNIPEDE statistics).
Methods for reporting measurement campaigns
The data relevant to voltage dips/swells should be presented according to the following
guidelines.
The data collected should be homogeneous in terms of voltage levels. Within the same voltage
level, distinction should be made between networks with prevailing underground cables or aerial
lines. To cover all seasonal effects, the observation time should be one year.
The data should be collected in tables like 4 and 5; the following data shall be reported:
average dips/swells incidence per bus per year;
90 or 95% dips/swells incidence per bus per year;
maximum dips/swells incidence per bus per year.
B.4
Swells (temporary power frequency overvoltages) between live conductors
and earth

prEN 50160:2008

32

For low voltage systems, under certain circumstances, a fault occurring upstream of a
transformer may produce temporary overvoltages on the LV side for the time during which the
fault current flows. Such overvoltages will generally not exceed 1,5 kV r.m.s.
For medium voltage systems, the expected value of such an overvoltage depends on the type
of earthing of the system. In systems with a solidly or impedance earthed neutral the
overvoltage shall generally not exceed 1,7 U c. In isolated or resonant earthed systems the
overvoltage shall generally not exceed 2,0 Uc. The type of earthing will be indicated by the
distributor.
Indicative values about overvoltages on distribution networks can be found in IEC TR 61000-214. More information for LV systems can be found in IEC TR 62066.
B.5 Magnitude of rapid voltage changes
For low voltage, under normal operating conditions, rapid voltage changes generally do not
exceed 5 % Un, but changes of up to 10 % Un with a short duration might occur some times per
day in some circumstances.
For medium voltage, under normal operating conditions, rapid voltage changes generally do not
exceed 4 % Uc, but changes of up to 6 % Uc with a short duration might occur some times per
day in some circumstances.
These indicative values apply to the phenomenon of rapid voltage changes as defined in 3.14.
At a national level, additional values may be available, but in some cases they are referred to
another definition of rapid voltage change (Umax, see EN 61000-3-3 clause 3.3 and fig. 2).
In general, the frequency and magnitude of rapid voltage changes are related to the load
variation by the users and to the short-circuit power level of the network.

33

prEN 50160:2008

Bibliography
IEC TR 61000-2- 2006
14

Electromagnetic compatibility Part 2-14: Environment


Overvoltages on public electricity distribution networks

IEC TR 62066

2002

Surge overvoltages and surge protection in low voltage a.c.


power systems - General basic information

EN 50065-1

2001

Signalling on low-voltage electrical installations in the


frequency range 3 kHz to 148,5 kHz Part 1: General
requirements, frequency bands and electromagnetic
disturbances

CLC/TR 50422

2003

Guide for the application of the European Standard EN 50160

EN 61000-2-2

2002

Electromagnetic compatibility Part 2-2: Environment Compatibility levels for low-frequency conducted disturbances
and signalling in public low-voltage power supply systems
(IEC 61000-2-2:2002)

EN 61000-2-4

1997

Electromagnetic compatibility Part 2-4: Environment Compatibility levels in industrial plants for low-frequency
conducted disturbances

EN 61000-4-15
+ A1

1998
2003

Electromagnetic compatibility (EMC) Part 4-15 Testing and


measurement techniques Flickermeter - Functional and
design specifications (IEC 61000-4-15:1997 + A1:2003)

EN 61000-6-1

2002

Electromagnetic compatibility Part 6-1: Generic standards Immunity for residential, commercial and light-industrial
environments

EN 61000-6-2

2000

Electromagnetic compatibility Part 6-2: Generic standards Immunity for industrial environments

UNIPEDE 91
en 50.02
CEER

Voltage dips and short interruptions in public medium voltage


electricity supply systems
2001
2003
2005

Benchmarking Report on Quality of Electricity Supply - Freely


available at http://www.ceer-eu.org