net Contents 11/1


Moeller HPL0211-2007/2008

Switch-Disconnector IN from 630 A to 6300 A


IZM circuit-breakers

Circuit-Breaker IZM from 630 A to 6300 A,


IN switch-disconnectors Circuit-breakers,
switch-disconnectors
from 630 to 6300 A
up to 6300 A

Page Page Page

Technical overview Ordering Engineering

Modern protection technology covering the IZM circuit-breakers 11/2 Switch-disconnectors, 3- and 4 pole 11/22 Control circuit plug terminal 11/45
rated current range from 630 A to 6300 A. IN switch-disconnectors 11/3
assignment plan
Increasing the rated operational 11/24 Ordering
Electronic releases for circuit-breakers voltage to 1000 V AC
This overview will assist you to efficiently use 11/4
Electronic overcurrent releases 11/25
Locking devices 11/46

the Moeller concept for the open circuit-breaker System overview


Test units, rated current module 11/25
Locking arrangements 11/47

IZM. It shows you a whole range of available Circuit-breakers 11/6 Earth-fault protection 11/26
Withdrawable units 11/48

options and the system involved for function Description Accessories for electronic overcurrent 11/26
Ordering, withdrawable units

enhancements. releases
Withdrawable unit 11/48
Basic unit Circuit-breaker, switch-disconnector 11/8 Description
- Switching capacity 440 V AC, Fixed mounting conversion kit for 11/49
Ordering withdrawable units
Icu = Ics from 50 to 100 kA Components for communication 11/29
- 3- or 4 pole Position signalling switch 11/49
IZM1 circuit-breakers, 3 pole … Ordering
- Electronic release for system
Shutters 11/49
protection, selective protection, … For system protection (A) 11/10
universal protection and digital Parameter definition systems 11/31 Arcing chamber cover 11/49
… For selective protection (V) 11/10
High availability release with graphic display
Communication and measuring 11/32 Coding system 11/49
- Withdrawable units - Rated current In from 630 to 6300 A … For universal protection (U) 11/10 function
Part no.: +IZM...-XAV... - Rated voltage Ue 1000 V Ordering
… With digital release (D) 11/10 Expansion modules 11/34
Page 11/48 Part no.: +IZM...-...-X1000V
Page 11/10 IZM2 circuit-breakers, 3 pole … Auxiliary contact 11/36 Connection systems for fixed 11/50
- Arcing chamber covers mounting
Part no.: +IZM...-XKLA...-AV … For system protection (A) 11/12 Motor operator 11/38
Page 11/49 Connection system for withdrawable 11/52
… For selective protection (V) 11/12 Closing release, trip block 11/40 unit
… For universal protection (U) 11/12 Electrically ON, Emergency-Stop, 11/44 Engineering
… With digital release (D) 11/12 brackets, door seals

IZM3 circuit-breakers, 3 pole … Selectivity tables 415 V AC 11/54

… For selective protection (V) 11/14 Tripping characteristics 11/61


Technical data
Measurement, signalling, … For universal protection (U) 11/14
communication … With digital release (D) 11/14 Permissible continuous current 11/65
- Communication module IZM1 circuit-breakers, 4 pole … Circuit-breakers 11/66
Part no. +IZM-COM-DP,
Page 11/32 … For system protection (A) 11/16 Switch-disconnector 11/72
- Measuring module … For selective protection (V) 11/16 Control unit 11/76
Part no.: +IZM-XMH, … For universal protection (U) 11/16 Auxiliary contact 11/76
Page 11/32
… With digital release (D) 11/16 Voltage release 11/77
- Display for universal circuit-breaker, Comprehensive fixed Operate with comfort
Part no. +IZM-XAM, mounted accessories - Motor drives IZM2 circuit-breakers, 4 pole … Motor operator 11/77
Page 11/26 - Main circuit terminals Part no.: +IZM-XM... … For system protection (A) 11/18 Current consumption 11/78
- Operations counter (V = vertical, F = front, A = flange) Page 11/38
… For selective protection (V) 11/18 Safety clearances 11/78
Page 11/38 Part no.: +IZM...-XAT...V(F, A)... - Parameter definition systems
Page 11/50 Part no.: IZM-XEM-...PG... … For universal protection (U) 11/18 Dimensions
- Position signalling switches
For withdrawable unit - Auxiliary springloaded terminals Page 11/31 … With digital release (D) 11/18
Part no.: +IZM-XHIAV... Part no.: +IZM-XKLZ... - Shunt releases, Part no. +IZM-XA… External dimensions, door cut-out 11/80
IZM3 circuit-breakers, 4 pole …
Page 11/49 Page 11/38 Page 11/40 Fixed mounting and optional 11/81
- Auxiliary contacts … For selective protection (V) 11/20 connection terminals, 3 and 4-pole
- Door sealing frames, external - Closing releases
(Trip-indicating, Availability signal, actuation, IP40 Part no.: +IZM-XE... … For universal protection (U) 11/20 Withdrawable units and optional 11/83
Spring charge state, Part no.: IZM-XRT Page 11/40 connection terminals, 3 and 4-pole
… With digital release (D) 11/20
Voltage release state) Page 11/44
- Undervoltage releases Fixed mounted, 3 and 4 pole 11/85
Part no.: +IZM-XHI... - Protective cover, transparent, IP55 Part no.: +IZM-XU...
Page 11/36 Part no.: IZM-XDT Optional connection terminals 11/86
Page 11/42
- Expansion modules Page 11/44 Measuring transformers, voltage 11/91
Part no.: IZM-XEM-... releases
Page 11/34
11/2 Technical overview
Circuit-breaker
IZM Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Circuit-breaker Basic Normal switching capacity High switching capacity (H)


with main switch and isolating characteristics switching capacity (B) (N)
(in combination with the “interlock in OFF” facility)
from 630 … 6300 A

Rated ultimate short-circuit breaking capacity Icu at rated operational voltage Ue


from 630 A to 6300 A

Rated current n = 440 V 690 V 440 V 690 V 440 V 690 V 1000 V


rated uninterrupted current Iu

cu = cs cu = cs cu = cs cu = cs cu = cs cu = cs cu = cs
A kA kA kA kA kA kA

IZM

IZM…1(-4)-…
50 42 65 50

a
a

IZM…2(-4)-…

a
a

IZM…3(-4)-…

IZM … … … … …

Switching capacity
see above B
see above N
see above H

Frame size
630 … 1600 A 1
800 … 3200 A 2
4000 … 6300 A 3
Poles
3 pole ()
4 pole -4
Electronic releases
page 11/6
Standard release A
Selective-operating release V

Universal release U
Digital release D

Rated current in A
Frame size 1 630…1600
Frame size 2 800…3200
Frame size 3 4000…6300
Technical overview 11/3
Switch-disconnectors IN
IN

Circuit-breakers, switch-disconnectors
Switch-disconnectors Basic Normal High
with main switch and isolating characteristics (in switching capacity (B) switching capacity (N) switching capacity (H)
combination with the “interlock in OFF” facility)
from 630 … 6300 A

Rated ultimate short-circuit making capacity

from 630 A to 6300 A


cm
rated short-time withstand current cw t = 1 s
Rated current n =
rated uninterrupted current u

cm cw cm cw cm cw
A kA kA kA kA kA kA

IN

IN…1(-4)-…
630 … 1600 105 42 143 50

page 11/22

IN…2(-4)-…
800 … 3200 121 55 176 65 220 80

page 11/22

INH3(-4)-…
4000 … 5000 220 80
6300 220 100

page 11/23
11/4 Feature overview
Electronic releases for circuit-breakers
IZM Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

IZM …-A… IZM …-V… IZM …-U… IZM …-D… IZM …-D… +
IZM-XZMR
System protection Selectively- Universal Digital release Digital release
630 … 3200 A opening circuit- protection 630 … 6300 A exclusively featur-
breakers 630 … 6300 A ing external param-
630 … 6300 A eterization access
from 630 A to 6300 A

630 … 6300 A

Basic protective functions


Overload protection Ir L K K K K K
Adjustable delay time tr … … K K K
Short-time delayed short-circuit protection Isd S … K K K K
Non-delayed short-circuit protection Ii I K K2) K K K
Neutral conductor protection N … k K K K
Earth-fault protection G … k k k k
Additional functions
N conductor protection can be … k K K K
Short time delayed short-circuit protection can be … … K K K
activated/deactivated
Non-delayed short-circuit protection can be … … K K K
activated/deactivated
Thermal memory can be activated/deactivated … … K K K
Load monitoring … … K K K
Leading “L” trip signal, 200 ms … … K K K
Short-time delayed short-circuit protection I2t can be … … K K K
selected
Overload protection can be set to I4t … … K K K

Overload protection can be activated/deactivated … … … K K


N conductor protection adjustable … … K K K
Earth-fault protection convertible to I2t … … K K K

Earth fault alarm … … k k k


Selectable parameter sets … … … K K
Zone-selective interlocking … … k k k
Parametric programming and visualization
Parametric programming via rotary coding switch K K K … …
Parametric programming via communication … … … K K
(absolute values)
Parametric programming via communication … … … K …
Remote parameter definition of the basic functions … … … K K
Remote parameter definition of additional functions … … K K K
Setting using parameter assignment module Comm … … … K K
IZM-XEM-PG or PROFIBUS-DP1)
Menu-assisted setting directly on release1) Menu … … … K …
Alphanumeric LCD (4-line display) … … k … …
Graphic LCD … … … K …
Other
Connection feature for an external 24 V DC power … … K K K
supply

Notes 1)Step size for setting Menu/Comm or Comm K standard


Setting range Step width k optional
0…1 0.1
1 … 100 1
100 … 500 5
500 … 1000 10
1000 … 1600 50
1600 … 10 000 100
10 000 … max. 1000
2) Fixed at Ii f 20 x In, max. 50 kA
Technical overview 11/5
Electronic releases for circuit-breakers
http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM…

Circuit-breakers, switch-disconnectors
IZM …-A… IZM …-V… IZM …-U… IZM …-D… IZM …-D… +
IZM-XZMR
System protection Selectively- Universal Digital release Digital release
630 … 3200 A opening circuit- protection 630 … 6300 A exclusively featur-
breakers 630 … 6300 A ing external param-
630 … 6300 A eterization access

from 630 A to 6300 A


630 … 6300 A

Measuring function
“harmonic” measuring function … … k k k
Communication
Internal system bus … … K K K
PROFIBUS-DP communication … … k k K
Communication using Ethernet … … k k k
LED display features
Release active K K K K K
Alarm 100 % Ir K K K K K
Control unit error message K K K K K
Overload trip L … K K K K
Short-time delayed short-circuit trip S … K K K K

Non-delayed short-circuit trip I … K K K K


Neutral conductor trip N … K1) K K K

Earth-fault protection trip G … K1) K2) K2) K2)


Earth-fault protection alarm G … … K3) K3) K2)
Trip by extended protective function … … K K K
Communication … … K K K
Signals via signalling switch with external
system bus modules (relay)
Overload warning 100 % Ir … … K K K
Load shedding, load pick-up … … K K K
Leading overload signal 100 ms … … K K K

Temperature alarm … … K K K
Phase imbalance … … K K K
Overload trip L … … K K K
Short-time delayed short-circuit trip S … … K K K
Non-delayed short-circuit trip I … … K K K
Neutral conductor trip N … … K K K

Earth-fault protection trip G … … K2) K2) K


Earth-fault protection alarm G … … K3) K3) K
Auxiliary relay … … K K K
Control unit error message … … K K K

Notes 1) (only possible with option +IZM-XT) K standard


2) (only possible with option (+)IZMU-XT) k optional
3) (only possible with option (+)IZMD-XT(A))
11/6 System overview
Circuit-breakers
IZM Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

5 5
5 5
5 7
from 630 A to 6300 A

2
3
4

8
8

17

16

15

0 169 5 9
10
14
11
11
11

11

13 12
System overview 11/7
Circiut-breakers
http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM

Circuit-breakers, switch-disconnectors
Base units Add-on functions Mounting accessories

Circuit-breakers IZM 1 Position signalling switch 4 Terminations 5

from 630 A to 6300 A


Rated current from 630 … 6300 A Module for withdrawable unit Horizontal connection (standard)
4-stage switching capacity Module 1 Vertical connection
4 release types for different protection • Connected position: 1 changeover con- Front connection (single hole fitting,
and indication functions tact double hole fitting)
• Test position: 1 changeover contact
3 and 4-pole versions • Disconnected position: 1 changeover Flanged connection (on withdrawable
a page 11/10 contact units)
Module 2 a page 11/50
• Connected position: 3 changeover con-
tacts Replacing the switch by insertion and 6
• Test position: 2 changeover contacts withdrawal
Communication • Disconnected position: 1 changeover
contact 3 positions, lockable
• Connected position
a page 11/49
• Test position
• Disconnected position
Communication module 3 Control circuit plugs 7 Indication of the positions by position
Screw terminals Spring-loaded terminals signalling switch
for PROFIBUS-DP
a page 11/38 Arcing chamber cover for reduction of the
a page 11/32 safety clearance
Shutter for automatic locking of the input
Auxiliary contacts 8 and output contacts within the withdra-
External expansion modules 2
a page 11/35 Normal auxiliary contacts with 2 N/C and wable unit, lockable
2 N/O contacts (standard) Replacing the switch by insertion and
2 N/C contacts and 2 N/O contacts addi- withdrawal
Electronic releases 11 tionally possible a page 11/48
Standard protection functions Ready-to-close auxiliary contacts
Optional protection functions Trip indication Door seal 14
Additional functions Spring energy store status signal For door mounting, degree of protection
Parametric programming and visualiza- Voltage release status signal IP40
tion
a page 11/37 Protective cover to IP55
Measuring functions
a page 11/44
Communication
Motor operator 9
a page 11/24
Automatic charging of the stored energy
mechanism for ON and OFF operations
Parameter assignment module 12 Motor cut-off switch
a page 11/31 a page 11/38

Earth-fault protection module 13 Operations counter 10


Earth-fault alarm module a page 11/38
a page 11/26
Rated current modules 15
Rating plug
a page 11/25

Emergency-Stop mushroom actuator 16


a page 11/44

Voltage release 17
Closing release
Shunt release
Undervoltage release
• Non-delayed
• Off-delayed
a page 11/40
11/8 Description
Circuit-breakers, switch-disconnectors
IZM, IN Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors
from 630 A to 6300 A

IZM circuit-breakers Standard version

The IZM from Moeller embodies a concept for open circuit-breakers that exceeds the IZM circuit-breaker has the following standard equipment:
standard throughout the world. Based on state-of-the-art system engineering, the- • Electronic overcurrent releases
se switches open up a new dimension in the rated current range from • Rated current module (with the exception of IZM…-A…)
630 to 6300 A. They excel not only for their performance, but also for their functio- • Mechanical ON and mechanical OFF switch
nality, especially in their communications capabilities and their ease of handling • Manual drive for charging the spring-operated stored energy mechanism
and installation. • Switch position indication 0 / I
A comprehensive operator manual is supplied with each device. • Ready indication OK
• Charge state display
Applications • Auxiliary circuit switch 2 M + 2 B
• Horizontal main terminals on rear with fixed mounted and with withdrawable
units up to 5000 A and on rear with vertical main terminals at 6300 A
Coupler switches: Beside the IZM circuit-breakers, IN switch-disconnectors are avai- • With 4-pole switches the 4th pole (N) is fitted on the left and can be loaded to
lable. These are used, for example, as coupler switches between different power 100 %
supplies. • Display of the contact erosion of the main contacts
Main switches: You can use both IN switch-disconnectors and IZM circuit-breakers • Auxiliary current plug system with screw terminals. The switch is always equip-
as mains isolating switches. When fitted with a lockable handle, all IZM circuit-bre- ped with the required number of auxiliary current plugs.
akers (and IN switch-disconnectors) fulfil the main switch and isolating characteris- • Mechanically tripped display of the overcurrent release system
tics according to IEC/EN 60204-1. Depending on the type of apparatus to be • Mechanical reclosing lockout after trip
protected, the tasks of the circuit-breakers can be split into four main applications: • Operation manual in English
• System protection Additional with withdrawable units:
• Motor protection • Main contacts: Laminated contacts on the back plate of the withdrawable unit,
• Transformer protection contact pin on basic unit
• Generator protection. • Position display with operating console of the plug-in switch
These key applications make different demands on the switches, which are met with • Captive crank handle for switch movement with withdrawable system
a range of control units. • Withdrawable unit with guide rails for simple handling
Switches with closing release are suitable for synchronization tasks. • Locking facility for switch movement in the withdrawable unit
• The switch cannot be moved in the withdrawable unit in the on state
Safety and reliability • Rated current coding between the withdrawable unit and the switch.

Numerous locking features are provided or can be fitted by the user, on the one Design
hand to protect the switch and system from unauthorised switching, and on the
other for the protection of maintenance and operating personnel. The compact design of the circuit-breakers provides optimum utilization of the avai-
Further safety features are: lable space, allowing control panels to be equipped more efficiently. The IZM for a
• Power feed from top or bottom as required rated current up to 6300 A, for example, can be installed in am 800 mm wide control
• Standard locking facility for the withdrawable unit when the switch is removed panel field. Switches with a rated current of 1600 A need only a 400 mm field.
• Standard locking facility for the switch in withdrawable unit to prevent removal
• High degree of protection with IP 55 terminal cover
• Standard with mechanical closing lockout after overload or short-circuit release Operating panel
• The operating panel cannot be removed when the switch is operational
• Delivery including all auxiliary circuit connectors corresponding to built-in fea- The operating panel is designed to ensure that it can protrude through a cut-out in
tures including coding device to prevent mix-up of plug-connectors with fixed the door and that all operation elements and displays can be accessed when the
mounted breakers control panel door is closed. The operating panels of all switches (fixed mounted/
• Devices with +IZM-XCOM-DP communication interfacing feature temperature withdrawable, 3/4-pole) are identical. The operating panel provides IP20 degree of
sensors on the built-in microswitch detection units (XBSS) and on the commu- protection.
nication module.
Description 11/9
Circuit-breakers, switch-disconnectors
http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM, IN

Circuit-breakers, switch-disconnectors
Current range Selection criteria for IZM circuit-breakers

The new open circuit-breaker IZM covers the entire range from 800 A … 6300 A Fundamental criteria for the selection of circuit-breakers:
with just two frame sizes. The compact frame size IZM1 extends the rated current • Max. short-circuit at the point of installation of circuit-breaker Ik max: this value
range downwards to 630 A. If required, the range can be extended to 250 A by ex- determines the short-circuit breaking capacity or the short-circuit current car-
changing the rating plug. And all this with a setting range of 0.4 … 1 x In. rying capacity of the circuit-breaker. It is compared with the value Icu, Ics, Icw of
the switch and mainly determines the size of the switch a technical data.

from 630 A to 6300 A


Dimensions • Rated current In which should flow through the respective branch circuit: this
value may not be greater than the maximum switch rated current of the circuit-
breaker. The rated current is defined with the IZM with the rated current module
The IZM devices have the same height and depth across their entire current range. (exception: overcurrent release for system protection XZMA).
Only their device varies depending on the number of poles and the frame size. • Ambient temperature of the circuit-breaker: this is generally the internal control
panel temperature. Observe the derating table with increased ambient tempe-
Connection by rature a Technical data.
• Circuit-breaker type: fixed mounted or withdrawable, 3 or 4-pole.
As standard, IZM circuit-breakers are fitted with horizontal connections. Optionally, • Minimum short-circuit current, which flows through the switchgear: The release
the following connections are possible: vertical connections, connections that are must recognize this value as a short-circuit and may react with a trip.
accessible from the front and flanged connections. • Protection functions of the circuit-breaker: This is determined by the selection
of the respective overcurrent release.
Control units
Documentation
The IZM features microprocessor-controlled control units as standard. Five different
control units are available for selection and thus offer optimum protection for your Operating manual AWB1230-1407D/GB, part no. 232792
system: From simple system protection with overload and short-circuit release ex-
tending to a digital circuit-breaker with graphic display and the option of setting up Approvals
time-discriminating networks.
Approved circuit-breakers IZM can be found under “Approvals for world markets”.
Control circuit connections

The built-in auxiliary switches are connected to the male connector on the switch.
Irrespective of the mounting type, the customer connects the auxiliary power circuits
to the control circuit plugs at the top of the circuit-breaker. The standard terminals
are screw-type; spring-loaded terminals are optional.
ON fixed mounting units, the control circuit plugs are fitted directly to the plug con-
nectors on the switch and are coded against accidental reversal.
To allow withdrawable units to be moved, a sliding contact module is fitted between
switch and mounting. The sliding contact module allows a secure connection of the
control circuit cable connectors in the “connected” and “test” positions of the
switch.

Modular design

Because components are installed from the front, retrofitting accessories is especial-
ly quick and easy. This allows you to respond flexibly to changing requirements
within your system.

Communication-capability

With their communication-capability, the IZM circuit-breakers open up new possibi-


lities in power distribution. Providing and transmitting all important operational in-
formation, they increase system transparency and shorten the response times to
states such as overcurrent, phase asymmetry and overvoltage. A rapid intervention
in a process can, for example, prevent downtimes and help to schedule maintenance
activities and therefore boost plant availability.
Internal system bus
The IZM universal and digital circuit-breakers contain an internal system bus as
standard, which connects all intelligent components of the circuit-breaker.
Through the communications interface, the information from the intelligent compo-
nents can then be transmitted through PROFIBUS-DP, for example with the IZM-
XCOM communication module.
Expansion modules for the internal system bus:
External add-on modules can be connected to the IZM circuit-breakers through the
internal system bus without extensive additional wiring. Digital input modules and
digital and analog output modules are available for this purpose. A further module
implements reduced-time selectivity control between IZM circuit-breakers.
11/10 Ordering Ordering 11/11
Circuit-breakers, 3-pole Circuit-breakers, 3-pole
IZM...1 Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM...1
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Rating data Setting range Basic switching capacity (B) Normal switching capacity (N)

Rated current = rated Overload Short-circuit releases Icu = Ics = 50kA at 415 V 50/60 Hz Icu = Ics = 65kA at 415 V 50/60 Hz
uninterrupted current releases
Delayed Non-delayed Part no. Price Std. pack Part no. Price Std. pack Notes
from 630 A to 6300 A

from 630 A to 6300 A


In = Iu Ir Isd Ii Article no. see price list Article no. see price list

A A A A
I I

IZM…1-…
Circuit-breakers for distribution circuit protection (A)
630 315 – 630 1260 … 5040 IZMB1-A630 1 off IZMN1-A630 1 off • Adjustable overload release Ir = 0.5 – 1 x In
229889 229894 • Delay time tr = 10s at 6 x Ir
800 400 – 800 1600 … 6400 IZMB1-A800 IZMN1-A800 • Adjustable non-delayed short-circuit release Ii = 2 – 8 x In
229890 229895
1000 500 – 1000 2000 … 8000 IZMB1-A1000 IZMN1-A1000
229891 229896
1250 625 – 1250 2500 … 10000 IZMB1-A1250 IZMN1-A1250
229892 229898
1600 800 – 1600 3200 … 12800 IZMB1-A1600 IZMN1-A1600
229893 229899
Circuit-breaker for selective operation (V) and motor protection
630 252 – 630 788 … 7560 12600 IZMB1-V630 1 off IZMN1-V630 1 off • Adjustable overload release Ir = 0.4 – 1 x In
229900 229905 • Delay time tr = 10s at 6 x Ir
800 320 – 800 1000 … 9600 16000 IZMB1-V800 IZMN1-V800 • Adjustable delayed short-circuit release Isd = 1.25 – 12 x In
229901 229906 • Delay time tsd = 0, 20 (motor protection), 100, 200, 300, 400 ms
• Non-delayed short-circuit release Ii f 20 x In
1000 400 – 1000 1250 … 12000 20000 IZMB1-V1000 IZMN1-V1000
229902 229907
1250 500 – 1250 1563 … 15000 25000 IZMB1-V1250 IZMN1-V1250
229903 229908
1600 640 – 1600 2000 … 19200 32000 IZMB1-V1600 IZMN1-V1600
229904 229909
Circuit-breaker for universal protection (U) and motor protection
630 252 – 630 788 … 7560 945 … 7560, OFF IZMB1-U630 1 off IZMN1-U630 1 off • Adjustable overload release Ir = 0.4 – 1 x In
229913 229918 • Delay time tr = 2 – 30 s when set to J at 6 x Ir, tr = 1, 2, 3, 4, 5 s when set to I4t
800 320 – 800 1000 … 9600 1200 – 9600 , OFF IZMB1-U800 IZMN1-U800 • Adjustable N conductor protection In = 0.5 x In, 1 x In, OFF (external transducer required for N conductor)
229914 229919 • Adjustable delayed short-circuit release Isd = 1.25 – 12 x In
• Delay time tsd = OFF, 20 (motor protection), 100, 200, 300, 400 ms
1000 400 – 1000 1250 … 12000 1500 – 12000 , OFF IZMB1-U1000 IZMN1-U1000 • Adjustable non-delayed short-circuit release Ii = 1.5 – 12 x In; further settings: max. 0.8 x Ics, OFF: Ics = Icw
229915 229920
1250 500 – 1250 1563 … 15000 1875 … 15000, OFF IZMB1-U1250 IZMN1-U1250
229916 229921
1600 640 – 1600 2000 … 19200 2400 – 19200 , OFF IZMB1-U1600 IZMN1-U1600
229917 229922
Digital circuit-breaker (D) incl. graphic display
630 252 – 630 1.25 x In – 0.8 x Icw 1.5 x In – 0.8 x Ics IZMB1-D630 1 off IZMN1-D630 1 off • Adjustable overload release Ir = 0.4 – 1 x In
229923 229933 • Delay time tr = 2 – 30 s when set to J, tr = 1, 2, 3, 4, 5 s with setting to I4t
800 320 – 800 IZMB1-D800 IZMN1-D800 • Adjustable N conductor In = 0.5 – 2 x In, (external transducer required for N conductor).
229927 229934 • Adjustable delayed short-circuit release Isd = 1.25 x In – 0.8 x Icw, with max. setting of 0.8 x Icw the setting of the
delay time tsd is only permissible to max. 400 ms, Icw, see Technical data
1000 400 – 1000 IZMB1-D1000 IZMN1-D1000 • Delay time tsd = OFF, 80 – 4000 ms
229930 229935 • Observe adjustable non-delayed short-circuit release Ii = 1.5 x In – 0.8 x Ics, OFF: Ics = Icw!
1250 500 – 1250 IZMB1-D1250 IZMN1-D1250 • External 24 V DC power supply required (description a “Components for communication”).
229931 229936
1600 640 – 1600 IZMB1-D1600 IZMN1-D1600
229932 229937

Notes rated current reduction: a Accessories “Rated current module”


11/12 Ordering Ordering 11/13
Circuit-breakers, 3-pole Circuit-breakers, 3-pole
IZM...2 Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM...2
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Rating data Basic switching capacity (B) Normal switching capacity (N) High switching capacity (H)

Rated current = rated Setting range Icu = Ics = 55kA at 415 V 50/60 Hz Icu = Ics = 80kA at 415 V 50/60 Hz Icu = Ics = 100kA at 415 V 50/60 Hz
uninterrupted current
Overload Short-circuit releases
releases
from 630 A to 6300 A

from 630 A to 6300 A


Delayed Non-delayed Part no. Price Std. pack Part no. Price Std. pack Part no. Price Std. pack Notes
In = Iu Ir Isd Ii Article no. see price list Article no. see price list Article no. see price list

A A A
A I I

IZM…2-…
Circuit-breakers for distribution circuit protection (A)
800 400 – 800 1600 … 6400 IZMB2-A800 1 off IZMN2-A800 1 off IZMH2-A800 1 off • Adjustable overload release Ir = 0.5 – 1 x In
225530 225534 225545 • Delay time tr = 10s at 6 x Ir
1000 500 – 1000 2000 … 8000 IZMB2-A1000 IZMN2-A1000 IZMH2-A1000 • Adjustable non-delayed short-circuit release Ii = 2 – 8 x In
225531 225535 225546
1250 625 – 1250 2500 … 10000 IZMB2-A1250 IZMN2-A1250 IZMH2-A1250
225532 225536 225547
1600 800 – 1600 3200 … 12800 IZMB2-A1600 IZMN2-A1600 IZMH2-A1600
225533 225537 225548
2000 1000 – 2000 4000 … 16000 IZMB2-A2000 IZMN2-A2000 IZMH2-A2000
229979 225538 225549
2500 1250 – 2500 5000 … 20000 IZMB2-A2500 IZMN2-A2500 IZMH2-A2500
229980 225539 225550
3200 1600 – 3200 6400 … 25600 IZMB2-A3200 IZMN2-A3200 IZMH2-A3200
229982 225540 225551
Circuit-breaker for selective operation (V) and motor protection
800 320 – 800 1000 … 9600 16000 IZMB2-V800 1 off IZMN2-V800 1 off IZMH2-V800 1 off • Adjustable overload release Ir = 0.4 – 1 x In
229995 230004 230014 • Delay time tr = 10 s at 6 x Ir
1000 400 – 1000 1250 … 12000 20000 IZMB2-V1000 IZMN2-V1000 IZMH2-V1000 • Adjustable delayed short-circuit release Isd = 1.25 – 12 x In
229996 230007 230016 • Delay time tsd = 0, 20 (motor protection), 100, 200, 300, 400 ms
• Non-delayed short-circuit release Ii f 20 x In, max. 50 kA
1250 500 – 1250 1563 … 15000 25000 IZMB2-V1250 IZMN2-V1250 IZMH2-V1250
229997 230008 230017
1600 640 – 1600 2000 … 19200 32000 IZMB2-V1600 IZMN2-V1600 IZMH2-V1600
229998 230009 230018
2000 800 – 2000 2500 … 24000 40000 IZMB2-V2000 IZMN2-V2000 IZMH2-V2000
229999 230010 230027
2500 1000 – 2500 3125 … 30000 50000 IZMB2-V2500 IZMN2-V2500 IZMH2-V2500
230001 230011 230028
3200 1280 – 3200 4000 … 38400 50000 IZMB2-V3200 IZMN2-V3200 IZMH2-V3200
230003 230012 230029
Circuit-breaker for universal protection (U) and motor protection
800 320 – 800 1000 … 9600 1.5 – 12 x In, OFF IZMB2-U800 1 off IZMN2-U800 1 off IZMH2-U800 1 off • Adjustable overload release Ir = 0.4 – 1 x In
225556 225560 225572 • Delay time tr = 2 – 30 s when set to J with 6 x Ir, tr = 1, 2, 3,
1000 400 – 1000 1250 … 12000 1.5 – 12 x In, OFF IZMB2-U1000 IZMN2-U1000 IZMH2-U1000 4, 5 s with setting to I4 t
225557 225561 225573 • Adjustable N conductor IN = 0.5 x In, 1 x In, (external
transducer required for N conductor)
1250 500 – 1250 1563 … 15000 1.5 – 12 x In, OFF IZMB2-U1250 IZMN2-U1250 IZMH2-U1250 • Adjustable delayed short-circuit release Isd = 1.25 – 12 x In
225558 225562 225574 • Delay time tsd = OFF, 20 (motor protection), 100, 200, 300, 400
1600 640 – 1600 2000 … 19200 1.5 – 12 x In, OFF IZMB2-U1600 IZMN2-U1600 IZMH2-U1600 ms
225559 225564 225575 • Adjustable non-delayed short-circuit release Ii = 1.5 – 12 x In,
note further setting values: max. = 0.8 x Ics, OFF: Ics = Icw
2000 800 – 2000 2500 … 24000 1.5 – 12 x In, OFF IZMB2-U2000 IZMN2-U2000 IZMH2-U2000
230069 225565 225576
2500 1000 – 2500 3125 … 30000 1.5 – 12 x In, OFF IZMB2-U2500 IZMN2-U2500 IZMH2-U2500
230070 225566 225577
3200 1280 – 3200 4000 … 38400 1.5 – 12 x In, OFF IZMB2-U3200 IZMN2-U3200 IZMH2-U3200
230071 225567 225578
Digital circuit-breaker (D) incl. graphic display
800 320 – 800 1.25 x In – 0.8 x Icw 1.5 x In – 0.8 x Ics IZMB2-D800 1 off IZMN2-D800 1 off IZMH2-D800 1 off • Adjustable overload release Ir = 0.4 – 1 x In
230083 230090 230097 • Delay time tr = 2 – 30 s when set to J, tr = 1, 2, 3, 4, 5 s with
1000 400 – 1000 1.25 x In – 0.8 x Icw 1.5 x In – 0.8 x Ics IZMB2-D1000 IZMN2-D1000 IZMH2-D1000 setting to I4t
230084 230091 230098 • Adjustable N conductor IN = 0.5 – 2 x In, (external transducer
required for N conductor)
1250 500 – 1250 1.25 x In – 0.8 x Icw 1.5 x In – 0.8 x Ics IZMB2-D1250 IZMN2-D1250 IZMH2-D1250 • Adjustable delayed short-circuit release
230085 230092 230099 Isd = 1.25 x In – 0.8 x Icw, with max. setting of 0.8 x Icw the
1600 640 – 1600 1.25 x In – 0.8 x Icw 1.5 x In – 0.8 x Ics IZMB2-D1600 IZMN2-D1600 IZMH2-D1600 setting of the delay time tsd is only permissible to max. 400 ms,
230086 230093 230100 Icw a Technical data
• Delay time tsd = OFF, 80 – 4000 ms
2000 800 – 2000 1.25 x In – 0.8 x Icw 1.5 x In – 0.8 x Ics IZMB2-D2000 IZMN2-D2000 IZMH2-D2000
• Observe adjustable non-delayed short-circuit release
230087 230094 230101
Ii = 1.5 x In – 0.8 x Ics, OFF: Ics = Icw!
2500 1000 – 2500 1.25 x In – 0.8 x Icw 1.5 x In – 0.8 x Ics IZMB2-D2500 IZMN2-D2500 IZMH2-D2500 • External 24 V DC power supply required (description a
230088 230095 230102 “Components for communication”).
3200 1280 – 3200 1.25 x In – 0.8 x Icw 1.5 x In – 0.8 x Ics IZMB2-D3200 IZMN2-D3200 IZMH2-D3200
230089 230096 230103

Notes rated current reduction: a Accessories “Rated current module”


11/14 Ordering Ordering 11/15
Circuit-breakers, 3-pole Circuit-breakers, 3-pole
IZM...2, IZM...3 Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM...2, IZM...3
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Rating data
Rated current = rated Setting range High switching capacity (H)
uninterrupted current

Overload releases Short-circuit releases Icu = Ics = 100 kA at 415 V 50/60 Hz


from 630 A to 6300 A

from 630 A to 6300 A


Delayed Non-delayed Part no. Price Std. pack Notes
Article no. see price list

In = Iu Ir Isd Ii
A A A A
I I

IZM…3-…
Circuit-breaker for selective operation (V) and motor protection
4000 1600 – 4000 5000 … 48000 50000 IZMH3-V4000 1 off • Adjustable overload release Ir = 0.4 – 1 x In
230051 • Delay time tr = 10 s at 6 x Ir
5000 2000 – 5000 6250 – 60000 IZMH3-V5000 • Adjustable delayed short-circuit release Isd = 1.25 – 12 x In
230053 • Delay time tsd = 0, 20 (motor protection), 100, 200, 300, 400 ms
• Non-delayed short-circuit release Ii f 20 x In, max. 50 kA
6300 2520 – 6300 7875 – 75600 IZMH3-V6300 1)
232158

Circuit-breaker for universal protection (U) and motor protection


4000 1600 – 4000 5000 … 48000 1.5 – 12 x In, OFF IZMH3-U4000 1 off • Adjustable overload release Ir = 0.4 – 1 x In
225580 • Delay time tr = 2 – 30 s when set to J with 6 x Ir, tr = 1, 2, 3, 4, 5 s with setting to I4 t
5000 2000 – 5000 6250 … 60000 IZMH3-U5000 • Adjustable N conductor IN = 0.5 x In, 1 x In, (external transducer required for N conductor)
225581 • Adjustable delayed short-circuit release Isd = 1.25 – 12 x In
• Delay time tsd = OFF, 20 (motor protection), 100, 200, 300, 400 ms
6300 2520 – 6300 7875 … 75600 IZMH3-U6300 1) • Adjustable non-delayed short-circuit release Ii = 1.5 – 12 x In, note further setting values: max. = 0.8 x Ics,
232159 OFF: Ics = Icw

Digital circuit-breaker (D) incl. graphic display


4000 1600 – 4000 1.25 x In – 0.8 x Icw 1.5 x In – 0.8 x Ics IZMH3-D4000 1 off • Adjustable overload release Ir = 0.4 – 1 x In
230104 • Delay time tr = 2 – 30 s when set to J, tr = 1, 2, 3, 4, 5 s with setting to I4t
5000 2000 – 5000 IZMH3-D5000 • Adjustable N conductor IN = 0.5 – 2 x In, (external transducer required for N conductor)
230105 • Adjustable delayed short-circuit release Isd = 1.25 x In – 0.8 x Icw, with max. setting of 0.8 x Icw the setting of
the delay time tsd is only permissible to max. 400 ms, Icw a Technical data
6300 2520 – 6300 IZMH3-D6300 1) • Delay time tsd = OFF, 80 – 4000 ms
232160 • Observe adjustable non-delayed short-circuit release Ii = 1.5 x In – 0.8 x Ics, OFF: Ics = Icw!
• External 24 V DC power supply required (description a “Components for communication”).

Notes rated current reduction: a Accessories “Rated current module”


Only vertical version of main terminals possible
11/16 Ordering Ordering 11/17
Circuit-breakers, 4-pole Circuit-breakers, 4-pole
IZM...1 Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM...1
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Rating data
Rated current = rated Setting range Basic switching capacity (B) Normal switching capacity (N)
uninterrupted current Overload Short-circuit releases Icu = Ics = 50kA at 415 V 50/60 Hz Icu = Ics = 65 kA at 415 V 50/60 Hz
releases
Delayed Non-delayed Part no. Price Std. pack Part no. Price Std. pack Notes
from 630 A to 6300 A

from 630 A to 6300 A


In = Iu Ir Isd Ii Article no. see price list Article no. see price list

A A A A
I I

IZM...1-4...
Circuit-breakers for distribution circuit protection (A)
630 315 – 630 1260 … 5040 IZMB1-4-A630 1 off IZMN1-4-A630 1 off • Adjustable overload release Ir = 0.5 – 1 x In
229938 229943 • Delay time tr = 10 s at 6 x Ir
800 400 – 800 1600 … 6400 IZMB1-4-A800 IZMN1-4-A800 • Adjustable non-delayed short-circuit release Ii = 2 – 8 x In
229939 229944 • without overload protection in the 4th pole, therefore not suitable for IT networks
1000 500 – 1000 2000 … 8000 IZMB1-4-A1000 IZMN1-4-A1000
229940 229945
1250 625 – 1250 2500 … 10000 IZMB1-4-A1250 IZMN1-4-A1250
229941 229946
1600 800 – 1600 3200 … 12800 IZMB1-4-A1600 IZMN1-4-A1600
229942 229947
Circuit-breaker for selective operation (V) and motor protection
630 252 – 630 788 … 7560 12600 IZMB1-4-V630 1 off IZMN1-4-V630 1 off • Adjustable overload release Ir = 0.4 – 1 x In
229948 229953 • Delay time tr = 10 s at 6 x Ir
800 320 – 800 1000 … 9600 16000 IZMB1-4-V800 IZMN1-4-V800 • Adjustable delayed short-circuit release Isd = 1.25 – 12 x In
229949 229954 • Delay time tsd = 0, 20 (motor protection), 100, 200, 300, 400 ms
• Non-delayed short-circuit release Ii f 20 x In
1000 400 – 1000 1250 … 12000 20000 IZMB1-4-V1000 IZMN1-4-V1000 • without overload protection in the 4th pole, therefore not suitable for IT networks
229950 229955 • (optional with overload protection in the 4th pole: +IZM-XT additionally necessary)
1250 500 – 1250 1563 … 15000 25000 IZMB1-4-V1250 IZMN1-4-V1250
229951 229956
1600 640 – 1600 2000 … 19200 32000 IZMB1-4-V1600 IZMN1-4-V1600
229952 229957
Circuit-breaker for universal protection (U) and motor protection
630 252 – 630 788 … 7560 945 7560, OFF IZMB1-4-U630 1 off IZMN1-4-U630 1 off • Adjustable overload release Ir = 0.4 – 1 x In
229958 229963 • Delay time tr = 2 – 30 s when set to J with 6 It = 1, 2, 3, 4, 5 I4ts with setting to
800 320 – 800 1000 … 9600 1200 9600, OFF IZMB1-4-U800 IZMN1-4-U800 • Adjustable delayed short-circuit release Isd = 1.25 – 12 x In
229959 229964 • Delay time tsd = OFF, 20 (motor protection), 100, 200, 300, 400 ms
• Adjustable non-delayed short-circuit release Ii = 1.5 – 12 x In, note further setting values: max. = 0.8 x Ics,
1000 400 – 1000 1250 … 12000 1500 12000, OFF IZMB1-4-U1000 IZMN1-4-U1000 OFF: Ics = Icw!
229960 229965 • With overload protection on the 4th pole, can be set to OFF, 100 or 50 % Ir
1250 500 – 1250 1563 … 15000 1875 15000, OFF IZMB1-4-U1250 IZMN1-4-U1250
229961 229966
1600 640 – 1600 2000 … 19200 2400 19200, OFF IZMB1-4-U1600 IZMN1-4-U1600
229962 229967
Digital circuit-breaker (D) incl. graphic display
630 252 – 630 1.25 x In – 0.8 x Icw 1.5 x In – 0.8 x Ics IZMB1-4-D630 1 off IZMN1-4-D630 1 off • Adjustable overload release Ir = 0.4 … 1 x In
229968 229973 • Delay time tr = 2 … 30 s when set to J, tr = 1, 2, 3, 4, 5 s with setting to I4t
800 320 – 800 IZMB1-4-D800 IZMN1-4-D800 • Adjustable delayed short-circuit release Isd = 1.25 x In … 0.8 x Icw, with max setting of 0.8 x Icw the setting
229969 229975 of the delay time tsd is only permissible to 400 ms, Icw a Technical data
• Delay time tsd = OFF, 80 … 4000 ms
1000 400 – 1000 IZMB1-4-D1000 IZMN1-4-D1000 • Observe adjustable non-delayed short-circuit release Ii = 1.5 x In … 0.8 x Ics, OFF: Ics = Icw!
229970 229976 • With overload protection on the 4th pole, can be set to OFF, 100 % or 50 % Ir
1250 500 – 1250 IZMB1-4-D1250 IZMN1-4-D1250 • External 24 V DC power supply required (description a “components for communication”)
229971 229977
1600 640 – 1600 IZMB1-4-D1600 IZMN1-4-D1600
229972 229978

Notes 1) rated current reduction: a Accessories “Rated current module”


11/18 Ordering Ordering 11/19
Circuit-breakers, 4-pole Circuit-breakers, 4-pole
IZM...2 Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM...2
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Rating data Setting range Basic switching capacity (B) Normal switching capacity (N) High switching capacity (H)

Rated current = rated Overload releases Short-circuit releases Icu = Ics = 55kA at 415 V 50/60 Hz Icu = Ics = 80kA at 415 V 50/60 Hz Icu = Ics = 100kA at 415 V 50/60
uninterrupted current Hz
Delayed Non-delayed Part no. Price Part no. Price Part no. Price Std. pack Notes
from 630 A to 6300 A

from 630 A to 6300 A


In = Iu Ir Isd Ii Article no. see price list Article no. see price list Article no. see price list
A A A A
I I

IZM...2-4...
Circuit-breakers for distribution circuit protection (A)
800 400 – 800 1600 … 6400 IZMB2-4-A800 IZMN2-4-A800 IZMH2-4-A800 1 off • Adjustable overload release Ir = 0.5 – 1 x In
225583 225587 225598 • Delay time tr = 10 s at 6 x Ir
1000 500 – 1000 2000 … 8000 IZMB2-4-A1000 IZMN2-4-A1000 IZMH2-4-A1000 • Adjustable non-delayed short-circuit release Ii = 2 – 8 x In
225584 225588 225599 • without overload release in the 4th pole, therefore not suitable for IT networks
1250 625 – 1250 2500 … 10000 IZMB2-4-A1250 IZMN2-4-A1250 IZMH2-4-A1250
225585 225589 225600
1600 800 – 1600 3200 … 12800 IZMB2-4-A1600 IZMN2-4-A1600 IZMH2-4-A1600
225586 225590 225601
2000 1000 – 2000 4000 … 16000 IZMB2-4-A2000 IZMN2-4-A2000 IZMH2-4-A2000
230118 225591 225602
2500 1250 – 2500 5000 … 20000 IZMB2-4-A2500 IZMN2-4-A2500 IZMH2-4-A2500
230119 225592 225603
3200 1600 – 3200 6400 … 25600 IZMB2-4-A3200 IZMN2-4-A3200 IZMH2-4-A3200
230120 225593 225604
Circuit-breaker for selective operation (V) and motor protection
800 320 – 800 1000 … 9600 16000 IZMB2-4-V800 IZMN2-4-V800 IZMH2-4-V800 1 off • Adjustable overload release Ir = 0.4 – 1 x In
230147 230154 230162 • Delay time tr = 10 s at 6 x Ir
1000 400 – 1000 1250 … 12000 20000 IZMB2-4-V1000 IZMN2-4-V1000 IZMH2-4-V1000 • Adjustable delayed short-circuit release Isd = 1.25 – 12 x In
230148 230156 230163 • Delay time tsd = 0, 20 (motor protection), 100, 200, 300, 400 ms
• Non-delayed short-circuit release Ii f 20 x In, max. 50 kA
1250 500 – 1250 1563 … 15000 25000 IZMB2-4-V1250 IZMN2-4-V1250 IZMH2-4-V1250 • without overload release in the 4th pole, therefore not suitable for IT networks
230149 230157 230180 • (optional with overload protection in the 4th pole: +IZM-XT additionally
1600 640 – 1600 2000 … 19200 32000 IZMB2-4-V1600 IZMN2-4-V1600 IZMH2-4-V1600 necessary)
230150 230158 230181
2000 800 – 2000 2500 … 24000 40000 IZMB2-4-V2000 IZMN2-4-V2000 IZMH2-4-V2000
230151 230159 230182
2500 1000 – 2500 3125 … 30000 50000 IZMB2-4-V2500 IZMN2-4-V2500 IZMH2-4-V2500
230152 230160 230183
3200 1280 – 3200 4000 … 38400 50000 IZMB2-4-V3200 IZMN2-4-V3200 IZMH2-4-V3200
230153 230161 230184
Circuit-breaker for universal protection (U) and motor protection
800 320 – 800 1000 … 9600 1.5 – 12 x In, OFF IZMB2-4-U800 IZMN2-4-U800 IZMH2-4-U800 1 off • Adjustable overload release Ir = 0.4 – 1 x In
225609 225613 225624 • Delay time tr = 2 – 30 s when set to J at 6 x Ir, tr = 1, 2, 3, 4, 5 s when set to I4t
1000 400 – 1000 1250 … 12000 IZMB2-4-U1000 IZMN2-4-U1000 IZMH2-4-U1000 • Adjustable delayed short-circuit release Isd = 1.25 – 12 x In
225610 225614 225625 • Delay time tsd = OFF, 20 (motor protection), 100, 200, 300, 400 ms
• Adjustable non-delayed short-circuit release Ii = 1.5 – 12 x In; further settings:
1250 500 – 1250 1563 … 15000 IZMB2-4-U1250 IZMN2-4-U1250 IZMH2-4-U1250 max. 0.8 x Ics, OFF: Ics = Icw
225611 225615 225626 • with overload protection in 4th pole, can be set to OFF, 100 % or 50 % Ir
1600 640 – 1600 2000 … 19200 IZMB2-4-U1600 IZMN2-4-U1600 IZMH2-4-U1600
225612 225616 225627
2000 800 – 2000 2500 … 24000 IZMB2-4-U2000 IZMN2-4-U2000 IZMH2-4-U2000
230198 225617 225628
2500 1000 – 2500 3125 … 30000 IZMB2-4-U2500 IZMN2-4-U2500 IZMH2-4-U2500
230199 225618 225629
3200 1280 – 3200 4000 … 38400 IZMB2-4-U3200 IZMN2-4-U3200 IZMH2-4-U3200
230200 225619 225630
Digital circuit-breaker (D) incl. graphic display
800 320 – 800 1.25 x In – 0.8 x Icw 1.5 x In – 0.8 x Ics IZMB2-4-D800 IZMN2-4-D800 IZMH2-4-D800 1 off • Adjustable overload release Ir = 0.4 – 1 x In
230212 230219 230226 • Delay time tr = 2 – 30 s when set to J, tr = 1, 2, 3, 4, 5 s with setting to I4t
1000 400 – 1000 IZMB2-4-D1000 IZMN2-4-D1000 IZMH2-4-D1000 • Adjustable delayed short-circuit release Isd = 1.25 x In – 0.8 x Icw, with max.
230213 230220 230227 setting of 0.8 x Icw the setting of the delay time tsd is only permissible to max.
400 ms, Icw a Technical data
1250 500 – 1250 IZMB2-4-D1250 IZMN2-4-D1250 IZMH2-4-D1250 • Delay time tsd = OFF, 80 – 4000 ms
230214 230221 230228 • Observe adjustable non-delayed short-circuit release Ii = 1.5 x In – 0.8 x Ics,
1600 640 – 1600 IZMB2-4-D1600 IZMN2-4-D1600 IZMH2-4-D1600 OFF: Ics = Icw!
230215 230222 230229 • With overload protection on the 4th pole, can be set to OFF, 100 or 50 % Ir
• External 24 V DC power supply required (description a “Components for
2000 800 – 2000 IZMB2-4-D2000 IZMN2-4-D2000 IZMH2-4-D2000
communication”).
230216 230223 230230
2500 1000 – 2500 IZMB2-4-D2500 IZMN2-4-D2500 IZMH2-4-D2500
230217 230224 230231
3200 1280 – 3200 IZMB2-4-D3200 IZMN2-4-D3200 IZMH2-4-D3200
230218 230225 230232

Notes 1) rated current reduction: a Accessories “Rated current module”


11/20 Ordering Ordering 11/21
Circuit-breakers, 4-pole Circuit-breakers, 4-pole
IZM...2, IZM...3 Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM...2, IZM...3
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Rating data

Rated current = rated Setting range High switching capacity (H) Std. pack Notes
uninterrupted current
Overload releases Short-circuit releases Icu = Ics = 100 kA at 415 V 50/60 Hz
from 630 A to 6300 A

from 630 A to 6300 A


Delayed Non-delayed Part no. Price
In = Iu Ir Isd Ii Article no. see price list
A A A A
I I

IZM...3-4...
Circuit-breaker for selective operation (V) and motor protection
4000 1600 – 4000 5000 … 48000 50000 IZMH3-4-V4000 1 off • Adjustable overload release Ir = 0.4 – 1 x In
230185 • Delay time tr = 10 s at 6 x Ir
5000 2000 – 5000 6250 – 50000 IZMH3-4-V5000 • Adjustable delayed short-circuit release Isd = 1.25 – 12 x In
230186 • Delay time tsd = 0, 20 (motor protection), 100, 200, 300, 400 ms
• Non-delayed short-circuit release Ii f 20 x In, max. 50 kA
6300 2520 – 6300 7875 – 50000 IZMH3-4-V6300 1) • without overload release in the 4th pole, therefore not suitable for IT networks
232161 • (optional with overload protection in the 4th pole: +IZM-XT additionally necessary)

Circuit-breaker for universal protection (U) and motor protection


4000 1600 – 4000 5000 … 48000 1.5 – 12 x In, OFF IZMH3-4-U4000 1 off • Adjustable overload release Ir = 0.4 – 1 x In
225632 • Delay time tr = 2 – 30 s when set to J at 6 x Ir, tr = 1, 2, 3, 4, 5 s when set to I4t
5000 2000 – 5000 6250 … 60000 IZMH3-4-U5000 • Adjustable delayed short-circuit release Isd = 1.25 – 12 x In
225633 • Delay time tsd = OFF, 20 (motor protection), 100, 200, 300, 400 ms
• Adjustable non-delayed short-circuit release Ii = 1.5 – 12 x In; further settings:
6300 2520 – 6300 7875 … 75600 IZMH3-4-U6300 1) max. 0.8 x Ics, OFF: Ics = Icw
232162 • with overload protection in 4th pole, can be set to OFF, 100 % or 50 % Ir

Digital circuit-breaker (D) incl. graphic display


4000 1600 – 4000 1.25 x In – 0.8 x Icw 1.5 x In – 0.8 x Ics IZMH3-4-D4000 1 off • Adjustable overload release Ir = 0.4 – 1 x In
230233 • Delay time tr = 2 – 30 s when set to J, tr = 1, 2, 3, 4, 5 s with setting to I4t
5000 2000 – 5000 IZMH3-4-D5000 • Adjustable delayed short-circuit release Isd = 1.25 x In – 0.8 x Icw, with max. setting of 0.8
230234 x Icw the setting of the delay time tsd is only permissible to max. 400 ms, Icw a Technical
data
6300 2520 – 6300 IZMH3-4-D6300 1) • Delay time tsd = OFF, 80 – 4000 ms
232163 • Observe adjustable non-delayed short-circuit release Ii = 1.5 x In – 0.8 x Ics, OFF: Ics = Icw!
• With overload protection on the 4th pole, can be set to OFF, 100 or 50 % Ir
• External 24 V DC power supply required (description a “Components for
communication”).

Notes rated current reduction: a Accessories “Rated current module”


Only vertical version of main terminals possible
11/22 Ordering Ordering 11/23
Switch-disconnectors, 3 and 4 pole Switch-disconnectors, 3 and 4 pole
IN...1, IN...2, IN...3 Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net Moeller HPL0211-2007/2008 IN...1, IN...2, IN...3
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Rated current = rated Rated short-circuit Rated short-time Basic switching capacity (B) Normal switching capacity (N) High switching capacity (H)
uninterrupted current making capacity withstand current

t=1s Part no. Price Part no. Price Part no. Price Std. pack Notes
In = Iu Icm Icw Article no. see price list Article no. see price list Article no. see price list
from 630 A to 6300 A

from 630 A to 6300 A


A kA kA

IN switch-disconnectors
IN...1-... 3 pole 630 105 42 INB1-630 INN1-630 1 off The INB1(-4)-... switch-disconnector has the same construction as
230261 230274 the IZMB1(-4)-... circuit-breaker, however, without electronic trip
800 INB1-800 INN1-800 control. In this manner, it is possible to equip the IN series switch
230269 230276 with the same accessory equipment as a comparable IZM circuit-
breaker.
1000 INB1-1000 INN1-1000 The INN1(-4)-... switch-disconnector has the same construction as
230270 230277 the IZMN1(-4)-... circuit-breaker, however, without electronic trip
1250 INB1-1250 INN1-1250 control. In this manner, it is possible to equip the IN series switch
230272 230278 with the same accessory equipment as a comparable IZM circuit-
breaker.
1600 INB1-1600 INN1-1600
230273 230279
4 pole 630 143 50 INB1-4-630 INN1-4-630
230281 230291
800 INB1-4-800 INN1-4-800
230283 230293
1000 INB1-4-1000 INN1-4-1000
230285 230294
1250 INB1-4-1250 INN1-4-1250
230287 230296
1600 INB1-4-1600 INN1-4-1600
230288 230297
IN...2-... 3 pole 800 121 55 INB2-800 INN2-800 INH2-800 1 off The INB2(-4)-... switch-disconnector has the same construction as
230300 230308 230315 the IZMB2(-4)-... circuit-breaker, however, without electronic trip
1000 INB2-1000 INN2-1000 INH2-1000 control. In this manner, it is possible to equip the IN series switch
230302 230309 230316 with the same accessory equipment as a comparable IZM circuit-
breaker.
1250 INB2-1250 INN2-1250 INH2-1250 The INN2(-4)-... switch-disconnector has the same construction as
230303 230310 230317 the IZMN2(-4)-... circuit-breaker, however, without electronic trip
1600 INB2-1600 INN2-1600 INH2-1600 control. In this manner, it is possible to equip the IN series switch
230304 230311 230318 with the same accessory equipment as a comparable IZM circuit-
breaker.
2000 INB2-2000 INN2-2000 INH2-2000
The INH2(-4)-... switch-disconnector has the same construction as
230305 230312 230319
the IZMH2(-4)-... circuit-breaker, however, without electronic trip
2500 INB2-2500 INN2-2500 INH2-2500 control. In this manner, it is possible to equip the IN series switch
230306 230313 230320 with the same accessory equipment as a comparable IZM circuit-
3200 INB2-3200 INN2-3200 INH2-3200 breaker.
230307 230314 230321
4 pole 800 176 65 INB2-4-800 INN2-4-800 INH2-4-800
230325 230332 230339
1000 INB2-4-1000 INN2-4-1000 INH2-4-1000
230326 230333 230340
1250 INB2-4-1250 INN2-4-1250 INH2-4-1250
230327 230334 230341
1600 INB2-4-1600 INN2-4-1600 INH2-4-1600
230328 230335 230342
2000 INB2-4-2000 INN2-4-2000 INH2-4-2000
230329 230336 230343
2500 INB2-4-2500 INN2-4-2500 INH2-4-2500
230330 230337 230344
3200 INB2-4-3200 INN2-4-3200 INH2-4-3200
230331 230338 230345
IN...3-... 3 pole 4000 220 80 INH3-4000 1 off
230322
5000 80 INH3-5000
230323
6300 100 INH3-63001)
232164
4 pole 4000 80 INH3-4-4000
230346
5000 80 INH3-4-5000
230347
6300 100 INH3-4-63001)
232165

Notes rated current reduction: a Accessories “Rated current module”


1) Only vertical version of main terminals possible
11/24 Ordering
Increasing the rated operational voltage to 1000 V AC
IZM2, IZM3, IZM-XZM... Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Pole For use with Rated Type suffix Price Std. pack Notes
basic unit operational Order number for see price list
current orders with basic unit
Ie
from 630 A to 6300 A

Increasing the rated operational voltage


to 1000 V AC
3-pole IZMH2-... Up to 2000 A +IZM2-20-X1000V 1 off A rated operational voltage of 1000 V AC is possible only for
INH2-... 257038 INH2-... and INH3-... switch-disconnectors and for IZMH2-... and
Up to 2500 A +IZM2-25-X1000V IZMH3-... circuit-breakers with high switching capacity.
257039 Observe reduced values in the technical specifications.
Up to 3200 A +IZM2-32-X1000V
257040
IZMH3-... Up to 4000 A +IZM3-40-X1000V
INH3-... 257041
Up to 5000 A +IZM3-50-X1000V
257042
Up to 6300 A +IZM3-63-X1000V
257043
4-pole IZMH2-4-... Up to 2000 A +IZM2-204-X1000V
INH2-4-... 257044
Up to 2500 A +IZM2-254-X1000V
257045
Up to 3200 A +IZM2-324-X1000V
257046
IZMH3-4-... Up to 4000 A +IZM3-404-X1000V
INH3-4-... 257047
Up to 5000 A +IZM3-504-X1000V
257048
Up to 6300 A +IZM3-634-X1000V
257049

Part no. Price Std. pack Notes


Article no. see price list

Electronic overcurrent releases


System protection IZM-XZMA 1 off Order separately for spare part requirement. State the part no. of
259210 the circuit-breaker with the order! Order internal wiring
Selectively-opening circuit-breakers IZM-XZMV separately is required: IZM-XZM-VLIS(-VLEW). Trip release (incl.
259211 rated current module IZM-XRP…) must be ordered separately.
Control circuit plug X8 is required for the release IZM-XZMU(…),
Selectively-opening circuit-breakers with IZM-XZMV-XT IZM-XZMR(…) and IZM-XZMD(…). If not already available order
earth-fault protection and neutral 281344 control circuit plug IZM-XKL-…
conductor protection a Terminal assignment, page 11/5
Universal IZM-XZMU Trip accessories (incl. rating plug IZM-XRP…), please order
259213 separately.
A rating plug is not included in the equipment supplied and must
Universal with “harmonic” measuring IZM-XZMU-MH
be ordered separately with an upgrade of the IZM-XZMA to
function 281346
IZMU(R, D).
Remote IZM-XZMR1) Upgrading of a switch-disconnector by Moeller Field
259214 Service is possible.
Remote with “harmonic” measuring IZM-XZMR-MH1)
function 281348
Digital IZM-XZMD
259215
Digital with “harmonic” measuring IZM-XZMD-MH
function 281410

Notes 1) The
difference to part no. suffix +IZM-XZMR a page 11/27 is that these part numbers do not include the
communication interface IZM-XCOM-DP.
Ordering 11/25
Electronic overcurrent release and additional functions
http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM...-X…

Circuit-breakers, switch-disconnectors
Part no. Price Std. pack Notes Notes
Article no. see price list

Internal wiring for retrofitting purposes


Required with upgrade from release XZMA(V) to

from 630 A to 6300 A


release XZMU(R)(D)
IZM-XZM-VLIS 1 off With release upgrade, the With release upgrade from 4-
281411 necessary “internal system bus” pole IZM with XZMA(V) to
wiring between the release and XZMV(U)(R)(D) with neutral
X8, if communication functions or conductor or. earth-fault
an external 24 V DC supply are to protection, an additional
be used. external measurement
X8: 1 – 4 transducer IZM…-WX… is
used a page 11/27

IZM-XZM-VLEW 1 off Additional wiring required


281412 between release and X8: 9-12 with
a release upgrade
Hand-held test unit
For checking that the overcurrent release, IZM-XPH 1 off With mains cable
energy transformer, current transformer and 226018 Mains voltages: 220 – 240 V
F5 tripping magnet are functioning correctly; or 110 – 125 V, 50/60 Hz
suitable for all overcurrent releases from 07/ possible.
02

Hand held test unit


IZM-XTEST 1 off
107328

can be Rated current = rated Part no. suffix Price Part no. Price Std. pack Notes
exchanged uninterrupted current Order number for see Order number see price
orders with basic price list for separate list
In = Iu unit orders

Rated current module/rating plug


for modification of the release rated current In

IZM...-1(-4)-... 250 +IZM-XRP250 IZM-XRP250 1 off Not for use with IZM...-A...
IZM...-2(-4)-... 230675 230622 circuit-breakers for system
IZM...-1(-4)-... 315 +IZM-XRP315 IZM-XRP315 protection
IZM...-2(-4)-... 230676 230623 The upper limit of the rated
uninterrupted current Iu of
IZM...-1(-4)-... 400 +IZM-XRP400 IZM-XRP400 the circuit-breaker cannot be
IZM...-2(-4)-... 230677 230624 exceeded.
IZM...-1(-4)-... 500 +IZM-XRP500 IZM-XRP500 IZM circuit-breaker supplied
IZM...-2(-4)-... 230678 230625 as standard with rating plug
(corresponding to the In of
IZM...-1(-4)-... 630 +IZM-XRP630 IZM-XRP630
the circuit-breaker).
IZM...-2(-4)-... 230679 230626
The rating plg is exchanged if
IZM...-1(-4)-... 800 +IZM-XRP800 IZM-XRP800 the circuit-breaker is ordered
IZM...-2(-4)-... 230681 230628 with +IZM-XRP….
IZM...-1(-4)-... 1000 +IZM-XRP1000 IZM-XRP1000
IZM...-2(-4)-... 230682 230629
IZM...-1(-4)-... 1250 +IZM-XRP1250 IZM-XRP1250
IZM...-2(-4)-... 230683 230630
IZM...-3(-4)-...
IZM...-1(-4)-... 1600 +IZM-XRP1600 IZM-XRP1600
IZM...-2(-4)-... 230684 230631
IZM...-3(-4)-...
IZM...-2(-4)-... 2000 +IZM-XRP2000 IZM-XRP2000
IZM...-3(-4)-... 230685 230632
IZM...-2(-4)-... 2500 +IZM-XRP2500 IZM-XRP2500
IZM...-3(-4)-... 230686 230633
IZM...-2(-4)-... 3200 +IZM-XRP3200 IZM-XRP3200
IZM...-3(-4)-... 230687 230634
IZM...-3(-4)-... 4000 +IZM-XRP4000 IZM-XRP4000
230688 230635
IZM...-3(-4)-... 5000 +IZM-XRP5000 IZM-XRP5000
230689 230636
IZM...-3(-4)-... 6300 +IZM-XRP6300 IZM-XRP6300
230690 230637
11/26 Ordering
Electronic overcurrent release and additional functions
IZM...-X… Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Part no. Price Std. pack Part no. Price Std. pack Notes
suffix see price Order see price
Order number list number for list
for orders with separate
basic unit orders
from 630 A to 6300 A

Earth-fault
protection with
selectively-
operating IZM...-V...
circuit-breakers

Earth-fault +IZM-XT 1 off Settings: With 3-pole circuit-


protection (and 230830 • tg: 0.1 – 0.5 s breakers, an external
N-conductor • Ig: (IZM...1-... and IZM...2- transducer for the N
protection with ...): 100, 300, 600, 900, conductor is required for
4-pole circuit- 1200 A summation current
breakers) • Ig: (IZM...3-...): 400, 600, formation.
800, 1000, 1200 A

IZM…-U… earth-
fault protection for
IZM universal
circuit-breaker

Earth-fault +IZMU-XT 1 off IZMU-XT 1 off Settings: With 3-pole circuit-


protection 225661 230426 • tg: 0.1 – 0.5 s breakers, an external
(alarm and trip • Ig: (IZM...1-... and IZM...2- transducer for the N
release) ...): 100, 300, 600, 900, conductor is required for
1200 A summation current
• Ig: (IZM...3-...): 400, 600, formation.
800, 1000, 1200 A
Through an external
transducer, the earth-fault
current in the transformer’s
star point can alternatively be
measured. Commercially
available current transformers
1200 A/1 A with an apparent
power of Pn = 15 VA can be
used. Measuring principle
changeover on earth-fault
protection module.

Display for universal


circuit-breaker

4-line +IZM-XAM 1 off IZM-XAM 1 off Display of:


230430 232188 • Currents IL1, IL2, IL3, IN, Ig, maintenance information, trip
cause and phase.
In conjunction with measuring function IZM-XZM…-MH
display of:
• U, P, c, W, f (total harmonic distortion and peak
factor).
If ordered separately a control circuit plug IZM-XKL-… is
necessary for connection. Order if required, a Terminal
assignment, page 11/5.
For full functionality an external 24 V DC supply is
required (description a „Components for
communication“).
Without an external power supply the data of the trip are
not saved. The phase currents and the set parameters can
however be read under the following conditions:
• The load on the main conductors is > 80 A (applies for
frame size 1 and 2).
• The load on the main conductors is > 200 A (applies for
frame size 3).
Ordering 11/27
Electronic overcurrent release and additional functions
http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM...-X…

Circuit-breakers, switch-disconnectors
Part no. suffix Price Std. pack Part no. Price Std. pack Notes
Order number see price Order number see price
for orders with list for separate list
basic unit orders

from 630 A to 6300 A


Earth-fault protection for IZM
with digital release IZM...-
R(D)...(+IZM-XZMR)
With 3-pole circuit-breakers, an
external transducer for the N
conductor is required for
summation current formation.

Earth-fault protection +IZMD-XT 1 off IZMD-XT 1 off Settings:


(alarm and trip release) 230431 230432 • tg: 0.1 – 0.5 s
• IZM...1(2)-...: 1000 – 1200 A
• IZM...3-...: 400 – 1200 A
Through an external transducer, the
earth-fault current in the transformer’s
star point can alternatively be measured.
Commercially available current
transformers 1200 A/1 A with an
apparent power of Pn = 15 VA can be
used.
Menu-driven measuring principle
changeover with cursor keys.
Release variants exclusively
with external
parameterisation access
for IZM with IZM...-D... +IZM-XZMR External 24 V DC power supply required.
digital release 263471 This option is not available with the
contained in scope of digital circuit-breaker’s graphic display
delivery: communications and has no possibility for local operation.
interface +IZM-XCOM-DP For applications with special safety
requirements, which can be
parameterized only through external
access.
This ordering position contains the
communication interface required for
remote parameterization (+IZM-XCOM-
DP).

For use with Part no. Price Std. pack Notes


Article no. see price
list

N conductor protection with solely single pole load in IT networks


– +IZM-XIT 1 off Only possible with 4 pole circuit-breaker
101529 with IZM-XZMV-XT or IZM-XZMU(R,
D)…
EMV filter
Suppressor for dampening common-mode interference (e.g. in IT grids, caused
by frequency inverters)
– +IZM-XEMV 1 off Dampening (asymmetric) in the range
101531 from 40 kHz to 10 MHz > 40dB

IZM-XEMV – IZM-XEMV 1
101530
CT for N conductor and earth-fault protection

Ring-type transformer (Rogowski convertor)


IZM…1-… IZM...-V... IZM1-XW 1 off With 3-pole circuit-breakers, an external
IZM...-U... 230439 transducer for the N conductor is
IZM…2-… IZM...-D... IZM2-XW required for the earth-fault protection
230440 (for vectorial summation).
An auxiliary plug IZM-XKL... is required
IZM…3-… IZM3-XW for connection, order if necessary.
230441 a Terminal assignment, page 11/5
Transformers with copper connection
IZM…1-… IZM...-V... IZM1-XWC 1 off
IZM...-U... 230442
IZM…2-… IZM...-D... IZM2-XWC
230443
IZM…3-… IZM3-XWC
230444
11/28 Ordering
Electronic overcurrent release and additional functions
IZM-X… Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Rated control voltage Part no. suffix Price Std. pack Part no. Price Std. pack Notes
Order number for orders see price Order number see price
Us with basic unit list for separate list
orders
V

Accessories for electronic


from 630 A to 6300 A

overcurrent releases

Cover for setting buttons

Suitable for IZM...A(V)(U) +IZM-XHB 1 off IZM-XHB 1 off Sealable cover for setting
control units and for IZM...D- 230638 230639 buttons,
...+IZM-XZMR (without with lockable cover for reset
graphic display) button (with key)

Suitable for IZM...D control +IZM-XHBG 1 off IZM-XHBG 1 off


unit with graphic display 232190 232191
(without IZM-XZMR option)

Automatic reset of the


mechanical reclosing lockout
+IZM-XOW 1 off • No Reset required after
230783 overcurrent trip
• Tripped indicator (red pin)
and IZM-XHIA remain as
continuous signal
• Switch can be immediately
switched on again
• Permissible only if a
mechanical manual reset is
not essential

Remote reset
24 DV +IZM-XFR24DC 1 off Switch is immediately ready for
230725 operation again after the
DC 125 +IZM-XFR120AC/125DC Remote Reset command (on
AC 120 230727 condition that the spring-
operated stored-energy
250 DC +IZM-XFR230AC/250DC mechanism is charged
220 – 240 AC, 50/60 Hz 230728 automatically by a motor
operator).
IZM-XFR... includes the IZM-
XOW-function:
• Automatic reset of the
mechanical reclosing
lockout
• Resetting the trip indication
(red pin and IZM-XHIA are
reset)
X8 control circuit plug
required. If not available, order
the IZM-XKL-… control circuit
plug with the order.
a Terminal assignment,
page 11/5
Description 11/29
Components for communications
http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM

Circuit-breakers, switch-disconnectors
that case, a standard commercial 24 V DC mains adapter with 5.5 mm jack (plus on
the insider) and a load carrying capacity of 500 mA can be used. The mains adapter
must meet the SELV regulations.
a b
Communication module

from 630 A to 6300 A


The IZM-XCOM-DP communication module enables connection of the IZM circuit-
g c breaker to the PROFIBUS-DP. A PROFIBUS master can communicate with the IZM
via the DP and DPV1 protocols for monitoring purposes.
Maintenance information received on time (e.g. via the operating time/hours or via
the wear and usage of the main contacts) enables the user to prevent system stand-
stills. With threshold violation signals, users can take preventative measures before
f it comes to a trip. For later analysis with the IZM-XEM-PG parameter assignment
module, the relevant data generated when a trip takes place is saved in the device
(for example tripping current with date and time).
Because the communication module is attached to the frame of the circuit-breaker,
the built-in temperature sensor measures the temperature inside the control panel.
The switch position is transmitted to PROFIBUS through three microswitches in the
underside of the communication module (operating, test or isolated position).
All microswitches that record information about the state of the circuit-breaker are
e d installed on or connected to the breaker status sensor (BSS module) for signalling
internal switching states. The module provides this digital information (ON, OFF,
status of the spring energy store, availability, voltage release) on the built-in system
bus. A further temperature sensor determines the temperature in the circuit-breaker.
This reading is also made available through a bus line.

Internal system bus

The internal system bus used in the circuit-breakers with communication features al-
a PROFIBUS-DP lows various external expansion modules to be connected to the data exchange pro-
b Internal system bus cess.
c External expansion modules (max. 8 modules) The available modules include digital output modules, an analog output module, a
d Parameter definition of the IZM without additional software digital input module and the ZSI module for reduced-time selectivity control. The di-
e Parameter assignment module IZM-XEM-PG(E) gital output modules with relay outputs are available in a user-programmable ver-
f IZM-XMH measuring module sion and a version programmable with a rotary coding switch.
g Communication module IZM-XCOM-DP The power for the external expansion module is provided by the internal system bus.
Moeller IZM...-U... and IZM...-D... circuit-breakers are open circuit-breakers with
communication features. Extremely space-efficient, they provide all important
switch information. “harmonic” measuring function
• The circuit-breakers can be parameterized via the local interface of the XZMD(R) [x263A]With the data and functions provided by the measuring function, the power
overcurrent release. All device-specific data can be shown. distribution can be analysed in detail. With the setpoint functions of the measuring
• Built-in circuit-breaker bus for communication between IZM and release, measu- functions, users can signal or record specific events in the network. In addition, ex-
ring function, switchgear signals, remote monitoring, tripping and parameteriza- tended protective functions can be implemented, providing additional tripping con-
tion ditions that are not covered by the overcurrent release.
• Connection of external module to the internal system bus, for example for moni- The "harmonic" measuring function determines currents, voltages, ratings, power
toring (also when subsequently upgrading without additional wiring). factors, energy values , frequencies, harmonic distortion, form factors and peak fac-
• Simple connection to PROFIBUS-DP with communication module for IZM with tors.
universal and digital circuit-breakers The measuring function provides two additional, independent curve form memories
• The IZM circuit-breakers can be incorporated in wide-area communication soluti- and a frequency analysis up to the 29th harmonic (fast Fourier transformation, or
ons based on PROFIBUS-DP. Within the system, the circuit-breakers can be para- FFT), which can be used for a harmonic compensation.
meterized with a programmable logic controller (PLC). All available data can be
read.
• Switching, controlling and data transfer through central PC
• Data acquisition and power management through measuring function

Control voltage supply

The basic functions of the electronic overcurrent release do not require auxiliary po-
wer. With the “Universal” and “Digital” release it is possible to use additional func-
tions which necessitate a data exchange via the internal system bus. These devices
are fitted with the internal system bus as standard. For data communications, an ex-
ternal 24 V DC power supply is required, which must fulfil the following conditions:
• Primary switched-mode power supply unit
• 24 V DC, G 3 %
• Rated output current: 5 A per circuit-breaker with the greatest possible number
of external expansion modules.
For example, you can use the Moeller switched-mode power supply unit SN4-050-
BI7, Article no. 200034.
Connection to control circuit connections X8:3 and X8:4 or to one of the expansion
modules. The various components are then supplied with power through the inter-
nal system bus connection.

Additional functions through the use of:


• Communication module
• Expansion modules
• Measuring module
• 4-line display or graphic display
• Parameter assignment module

With the 4-line display, the phase currents and the set parameters can be viewed
without an external power supply, as soon as the load exceeds 80 A (at IZM...1(2)...)
or 200 A (with IZM...3...) on the main circuit.

If the parameter assignment module is used in Offline mode (i.e. without connection
to an electronic release), it can not be supplied through the internal system bus. In
11/30 Description
Components for communications
IZM Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

ZSI module

Where full selectivity at low delay times is an issue even if the circuit-breakers are
arranged in hierarchical groups, the ZSI modules have the solution. They are used to
connect the circuit-breakers with each other.
If a short-circuit occurs, each circuit-breaker through which short-circuit current
from 630 A to 6300 A

flows determines whether the adjacent circuit-breaker on the next lower level is also
affected. This allows the exact location of the short-circuit to be identified and only
the circuit-breaker immediately upstream of the fault location is tripped.
With the microprocessor-controlled “delayed selectivity control”, the tripping delay
of these upstream circuit-breakers can be reduced to up to 50 ms.

Digital output module with rotary coding switch

This module can output 6 binary data units concerning the switching state (trip cau-
ses and warnings) of external switching devices (e.g. lamps, horns, klaxons) or for
switching off further system components (e.g. frequency inverters).
Various versions of digital output modules are available, both with and without a
rotary coding switch. Modules with a rotary coding switch allow selection between
two signal blocks, each with six defined assignments, and an additional response
delay.
The digital output modules are available as versions with opto-coupler outputs (N/
O contact, 150 mA) or with relay outputs (changeover contacts up to 10 A). Up to
two modules of this type can be connected to an IZM.

Digital output module, configurable

For high-performance solutions, the configurable output module is available. With


this unit, any event on the internal system bus can be switched directly on one of six
available outputs or three of these outputs can be assigned with up to six events
(“OR” operation). The module can be configured with the IZM-XEM-PG or IZM-
XEM-PGE parameter assignment module (with Ethernet interface).
As for the output modules with rotary coding switch, a relay version are available.
Only one module of this type can be used per IZM. Parameter assignment module

The IZM-XEM-PG parameter assignment module with integrated webserver allows


Analog output module access to all device information for analysis or parameterization purposes. The pa-
rameter assignment module is connected to the local interface of the overcurrent re-
The analog output module can be used in conjunction with the measuring function lease and, acting as a Web server, makes the data available through the Hypertext
to output the following measured values of the circuit-breaker to analog indication Transfer Protocol (HTTP). With this interface, any PC – desktop, notebook or palm-
devices in the control panel door: top – with a Web browser with Java 2 Virtual Machine can become a user interface.
• IL1, IL2, IL3, IN or The required HTTP files are included as standard.
• UL12, UL23, UL31, UL1N or No additional software needs to be installed. The data is displayed in a clear tree
• PL1, PL2, PL3, Sges or structure for quick access. With the parameter assignment module, the switch para-
• c1, c2, c3, DI% or meters can not only be changed, but also saved for later transmission to identical
• favg, ULLavg, Pges, cavg circuit-breakers.
Four interfaces (4 … 20 mA/0 … 10 V) are available for this purpose. The measured Depending on the equipment level of the IZM circuit-breaker, the following values
values for output are selected with a rotary coding switch. The use of the analog can be displayed: current, voltage, power, energy, c, frequency and harmonics
output module removes the need for additional transducers and their conventional as well as temperature.
installation and wiring in the main circuit. Up to two modules of this type can be All status information for the circuit-breaker, warning and trip indications, threshold
connected to an IZM. violations – each with date and time of occurrence, maintenance and statistical in-
formation (to reduce or prevent system downtimes).
Digital input module The parameter assignment module is fitted with a magnet on its back, which makes
it ideally suited as a portable “online” parameterization and diagnostics tool. Alter-
With the digital input module, six additional binary signals (24 V DC) can be connec- natively, the parameter assignment module can be used to create and modify para-
ted to the system. Alternatively, a changeover between two parameter sets (e.g. for meter sets offline on a notebook. A printing function allows all processes and
motoric and regenerative operation) can be implemented quickly and easily. settings to be documented on paper.
Ordering 11/31
Communication and measurement
http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM-XEM-…

Circuit-breakers, switch-disconnectors
Description Part no. Price Std. pack Notes
Order number for see price
separate orders list

Parameter definition systems

from 630 A to 6300 A


Suitable for IZM...-U... and IZM...-D...

Parameter • Parameterization, operation, monitoring and IZM-XEM-PG 1 off System requirement of the input/
assignment diagnostics of the IZM circuit-breaker via the local 230759 output module is a standard
module interface. browser with Java 2 Virtual
• Includes the connection cable to the IZM circuit-breaker Machine (e.g. Internet Explorer,
and null modem cable to the PC/Laptop, runs under V5.5 or higher or Netscape
Internet Explorer with JAVA2 VM 1.4.0-01. Navigator, V6.2 or higher).
Parameter • Parameterization, operation, monitoring and IZM-XEM-PGE 1 off Once the parameter assignment
assignment diagnostics of the IZM circuit-breaker via the local 230782 module has been connected to the
module with interface. circuit-breaker, the browser can
Ethernet interface • Includes the connection cable to the IZM circuit-breaker access the web pages of the
and null modem cable to the PC/Laptop, runs under parameter assignment module
Internet Explorer with JAVA2 VM 1.4.0-01. and the data from the circuit-
• With integrated Ethernet interface for connection to breakers.
Ethernet/Internet/Intranet.
Connection cable For IZM-XEM-PGE parameter assignment and operating IZM-XEM-VLPGE-X8 1 off Connection cable for connecting
to the X8 terminal device 281413 the IZM-XEM-PGE to the X8
terminal strip.
For permanent use on a circuit-
breaker, which does not feature
the IZM-XCOM-DP
communication modules or
expansion modules.

Notes

a b

g c

e d

a PROFIBUS-DP
b Internal system bus
c External expansion modules
d Parameter definition of the IZM without additional software
e Parameter assignment module IZM-XEM-PG(E)
f Metering module IZM-XMH
g Communication module IZM-XCOM-DP

To use the communications interface, an external 24 V DC power supply must be connected to terminals X8.3 and X8.4.
The various components are then supplied with power through the internal system bus connection (included as standard).
11/32 Ordering Ordering 11/33
Communication and measurement Communication and measurement
IZM-X... Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM-X...
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Description Part no. suffix Price Std. pack Part no. Price Std. pack Notes Notes
Order number for see price list Order number for see price list
orders with basic unit separate orders

Communication modules
from 630 A to 6300 A

from 630 A to 6300 A


Suitable for IZM...-U... and IZM...-D...
PROFIBUS-DP communication PROFIBUS-DP communication connection including +IZM-XCOM-DP 1 off IZM-XCOM-DP 1 off With use of the communication modules, the External 24 V DC power supply is required.
interface connection cable and BSS module (Breaker Status Sensor) for 230751 230833 installation feature for the IZM-XHIA, -XHIF, -XHIS Description a „Components for communication“
bus side signalling of internal switching states. and -XHIS1 auxiliary contacts is not applicable. The part no. (+)IZM-XCOM-DP already includes the Breaker-
With integrated temperature sensor and micro switches for The respective signals are detected internally via Status-Sensor IZM-XBSS.
position signalling (for switches in withdrawable units). the Breaker-Status-Sensor and can be accessed The communication interface (+)IZM-XCOM-DP already
with the parameter assignment module, via includes the Breaker-Status-Sensor and an actuation module
expansion modules or via the PROFIBUS. which are attached to the base unit. When separately
ordering the base unit and the withdrawable unit, the
Separate communication module Required with spare part requirement or if the communication IZM-XCO-DP 1 off With use of the communication modules, the required order options are to be assigned to the basic unit.
without BSS module interfacing without Breaker-Status-Sensor is to be 257028 installation feature for the IZM-XHIA, -XHIF, -XHIS The +IZM-XBSS plus type is only required however if the
implemented. and -XHIS1 auxiliary contacts is not applicable. internal signals are required, without any further
The respective signals are only available in communication interfacing.
conjunction with a BSS module via The IZM-XBSS single type is only intended for spare part
communication. requirement.
The IZM-XBSS Breaker-Status-Sensor IZM-XBSS is installed in
Separate Breaker-Status-Sensor Required with spare part requirement or if the Breaker-Status- +IZM-XBSS 1 off IZM-XBSS 1 off With use of the BSS modules, the installation the base unit.
(BSS module) Sensor without communication interfacing is to be 259201 259202 feature for the IZM-XHIA, -XHIF, -XHIS and -XHIS1
implemented. auxiliary contacts is not applicable.
Serves for signalling internal switching states on the internal The respective signals are detected internally via
system bus: the Breaker-Status-Sensor and can be accessed
Main contact ON/OFF, trip indication, spring-charge state with the parameter assignment module or with
signals, ready-to-close indication, voltage trip state external expansion modules.
With integrated temperature sensor.

Measurement modules
Suitable for IZM...-U... and IZM...-D...
“harmonic” measurement The "harmonic" measuring function allow the I, U, P, c, +IZM-XMH 1 off IZM-XMH 1 off Configuration of the measuring function (setting of External 24 V DC power supply required (description
function W, fand also distortion factor, peak factor and form factor. 230437 230835 the energy flow direction, transformer primary and a “Components for communications”).
Also two independant waveform memories (for current and secondary voltage and connection type): Part no. IZM-XMH can only be order on request.
voltage) and a frequency analysis up to 29th harmonic. • For IZM with digital circuit-breaker (IZM...-D...):
An external 3-phase voltage transformer is required for the menu assisted via graphic display
measuring function. • For IZM with universal circuit-breaker (IZM...-
U...): IZM-XEM-PG(E) parameter assignment
module required

Voltage transformer (3-phase)

380 … 690 V/100 V Required for measuring function IZM-XW380-690AC 1 off 1 voltage transformer can supply up to 6 circuit-breakers with
101526 the measurement function “harmonic.
11/34 Ordering Ordering 11/35
Communication and measurement Communication and measurement
IZM-XEM-... Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM-XEM-...
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Description Part no. suffix Price Std. pack Part no. Price Std. pack Notes Notes
Order number for see price list Order number for see price list
orders with basic unit separate orders

Expansion module
from 630 A to 6300 A

from 630 A to 6300 A


Suitable for IZM...-U... and IZM...-D...

Digital output module relay Six digital outputs, time delay adjustable from 0 to 2 s. IZM-XEM-6DO-R 1 off Max. summation current, 6 channels: For connection with further modules a prefabricated connection cable
Outputs optionally assigned with 230753 AC-12, 250 V: 10 A is included with each expansion module. The length of the connection
• Signal from overload release, delayed/non-delayed short-circuit release, DC-12, 24 V: 10 A cable is 0.2 m.
earth fault alarm/trip and neutral conductor trip or DC-12, 250 V: 250 mA For connection to the switch the longer, prefabricated connection
• early make (100 ms) signal from instantaneous overload warning, release cable IZM-XEM-VL1(VL2)(VLM-X8) is required (not supplied).
electronics fault, load shedding, load pick-up, temperature alarm, current When the internal switch condition is to be read, a Breaker-Status-
phase asymmetry Sensor IZM-XBSS is necessary.
External 24 V DC power supply required (description a
Digital output module relay, Six digital outputs, programmable with the parameter assignment module IZM-XEM-6PDO-R 1 off Max. summation current, 6 channels: “Components for communication”).
freely programmable or via PROFIBUS-DP with additional software (on request) 230755 AC-12, 250 V: 10 A For use without a communication module, an IZM-XKL(Z)(-AV)
DC-12, 24 V: 10 A control circuit plug at position X8 is required. Order separately if
DC-12, 250 V: 250 mA required.
Dimensions W x H x D: 70 x 86 x 95 mm
Analog output module Four analog outputs, 4 – 20 mA or 0 – 10 V IZM-XEM-4AO 1 off Installation on 35 mm mounting rail
Outputs optionally assigned with phase currents, phase voltages, effective 230757
and apparent power, frequency, power factor

Digital input module Six digital inputs (24 V DC) IZM-XEM-6DI 1 off
Transmission of additional information to PROFIBUS-DP 230758
Zone-selective interlocking Optimization of time selectivity IZM-XEM-ZSI 1 off Between the setting marks Isd and Ii of the
230752 short-circuit protection, the time
selectivity can be optimized:
• The delay is reduced on all IZM
hierarchical levels to a total of 50 ms.
• One module is required per circuit-
breaker.

Connecting cables
For connecting the expansion modules to the built-in system bus
M 0.2 IZM with communication module IZM-XCOM-DP IZM-XEM-VL05 1 off
230848
1m IZM-XEM-VL1 1 off
230850
2m IZM-XEM-VL2 1 off
230852
M2 IZM without communication module IZM-XCOM-DP IZM-XEM-VLM-X8 1 off
Connection to X8 281414
Documentation
“IZM – communication solutions” manual AWB1230-1465 1 off
263470
Operating instructions IZM/IN
German +AWB1230-1407D 1 off AWB1230-1407D 1 off Each circuit-breaker is delivered with an operating instruction in
101540 101533 English.
English AWB1230-1407GB 1 off When necessary a german operating manual must be seperately
101532 ordered (GB-Version will be exchanged for the D-Version).
The operating manual is also available as download via Internet.
11/36 Ordering Ordering 11/37
Auxiliary contacts Auxiliary contacts
IZM-XHI… Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM-XHI…
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Rated control voltage Part no. suffix Price Std. pack Part no. Price Std. pack Notes Notes
Order number for see price list Order number for see price list
Us orders with basic unit separate orders
V
from 630 A to 6300 A

from 630 A to 6300 A


Auxiliary contacts

Standard auxiliary contacts


Additional 2 make contacts and 2 break contacts +IZM-XHI22 1 off IZM-XHI22 1 off XHI indicates the position of the main contacts.
230605 230606 Depending on the selected combination the same terminal assignment applies for N/O contact
and N/C contact, see terminal assignment
Additional 3 make contacts and 1 break contact +IZM-XHI31 1 off Up to 8 switching contacts or standard auxiliary contacts can be used simultaneously
256920 Standard on IZM, do not order separately
Four additional make contacts +IZM-XHI40 1 off • IZM-XHI standard auxiliary contact with 2 N/O contacts and 2 N/C contacts.
256921 The standard terminals are screw-type; spring-loaded terminals are optional.
When ordered separately and additional control circuit cable connection may need to be fitted.
2 make contacts IZM-XHI20 1 off a Terminal assignment, page 11/5
256922
1 make contact and 1 break contact IZM-XHI11 1 off
256923
Trip-indicating auxiliary
contacts 1 C/O +IZM-XHIA 1 off IZM-XHIA 1off Optionally, signals trip caused by the overcurrent release: overload, short-circuit and earth-
263476 263475 fault tripping.
1 changeover contact IZM-XHIA-M 1 off ON remote switching through shunt release or undervoltage release, the IZM (unlike the NZM
Necessary for IZM circuit-breakers with metal 101527 switch-disconnectors) does not go into its tripped position.
system carrier (07/2005) When the circuit-breaker is fitted with the communication interfacing IZM-XCOM-DP or IZM-
XBSS, the connection XHIA to X7 is not required. The signal can be accessed via the
communication interface.
The standard terminals are screw-type; spring-loaded terminals are optional.

Availability signal
1 make contact +IZM-XHIB 1 off IZM-XHIB 1 off Availability is also signalled locally by the OK indication and means:
225680 225876 • Mechanical reclosing lockout reset (red reset pin)
• Spring energy store tensioned
• Undervoltage release excited
• Shunt release not excited
• Electrical interlock in the plant control cancelled
• Mechanical interlock ineffective
• Locking devices not activated
The standard terminals are screw-type; spring-loaded terminals are optional.

Spring energy store status


signal 1 make contact +IZM-XHIF 1 off IZM-XHIF 1 off “Spring-operated stored energy mechanism charged” is one of several preconditions for
256925 256924 availability.
The standard terminals are screw-type; spring-loaded terminals are optional.
On circuit-breaker featuring communication connection IZM-XCOM-DP or IZM-XBSS the
terminal slot for XHIF on X7 is not required. The signal of the XHIS can be read via the
communication.
If ordered separately a control circuit plug IZM-XKL-… is necessary for connection. Order if
required.
a Terminal assignment, page 11/5

Voltage release status


signal 1 N/O for the 1st shunt release or for the 2nd +IZM-XHIS 1 off IZM-XHIS 1 off XHIS and XHIS1 are Signals whether the shunt release/undervoltage release is excited/de-energised. XHIS and
voltage release (+IZM-XA1..., IZM-XE/A..., 230713 230714 of identical design XHIS1 are of identical design. When ordering separately, always choose XHIS. Up to two
(+)IZM-XU(V)...) XHIS(1) auxiliary switches can be used.
On circuit-breaker featuring communication connection IZM-XCOM-DP or IZM-XBSS the
1 N/O contact for the 2nd voltage release (+IZM- +IZM-XHIS1 1 off XHIS and XHIS1 are terminal slots for XHIS and XHIS1 on X7 are not required. The signal of the XHIS can be read
XA1…, IZM-XE/A…, (+)IZM-XU(V)…) 256926 of identical design via the communication.
The standard terminals are screw-type; spring-loaded terminals are optional.
If ordered separately a control circuit plug IZM-XKL-… is necessary for connection. Order if
required.
a Terminal assignment, page 11/5
11/38 Ordering Ordering 11/39
Motor operator Motor operator
IZM-XM…, IZM-XKL-... Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM-XM…, IZM-XKL-…
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Rated control Part no. suffix Price Std. pack Part no. Price Std. pack Notes Notes
voltage Order number for orders see price Order number for see price list
with basic unit list separate orders
Us
from 630 A to 6300 A

from 630 A to 6300 A


V

Motor operator
24 – 30 DC +IZM-XM24-DC 1 off IZM-XM24-DC 1 off Automatic charging of the spring-operated stored energy mechanism
230538 230539 Standard: customer connection as screw terminals
48 – 60 DC +IZM-XM48-60DC 1 off IZM-XM48-60DC 1 off If ordered separately a control circuit plug IZM-XKL-… is necessary for connection.
230540 230541 Order if required.
a Terminal assignment, page 11/5
110 – 125 DC +IZM-XM110AC/DC 1 off IZM-XM110AC/DC 1 off For remote operator and additional closing release and shunt release or undervoltage
110 – 127 AC 230542 230543 release is required.
220 – 250 DC +IZM-XM230AC/220DC 1 off IZM-XM230AC/220DC 1 off
208 – 240 AC 230544 230545
Motor cut-off switch
Thumb-grip handle +IZM-XMS 1 off IZM-XMS 1 off Can not be combined
230717 230718 with electrical ON,
Only for switches
with motor-operator

Operations counter
Mechanical, 5-position +IZM-XSZ 1 off IZM-XSZ 1 off Only possible with The operations counter can be used only in combination with the motor operator.
230729 259216 motor-operator
0 169 5

Control circuit connections

Spring-loaded fixed mounting +IZM-XKLZ 1 off Standard: customer connection as screw terminals
256914 Each switch is equipped with the required number of auxiliary connections to match the
Spring-loaded terminals, withdrawable modules +IZM-XKLZ-AV 1 off installed accessories. On fixed mounted breakers these are protected against incorrect
256915 insertion with a coding pin.
When accessories are being fitted, the auxiliary connections may need to be
supplemented.
a Terminal assignment, page 11/5
Individual parts for replacement or retrofitting
Screw-type manual connector IZM-XKL-HS 1 off See also AWB1230-1407 (06/05)
256919 Wiper contact, withdrawable
Spring-loaded manual connector IZM-XKL-HZ 1 off b c
256918
Plug connector IZM-XKL-ML 1 off
259207
Sliding contact module (optional) IZM-XKL-SK 1 off Wiper contact, IZM-XKL-HS IZM-XKL-HZ
for combination with IZM-XKL-H… 259208 withdrawable
a d
Blanking block IZM-XKL-B 1 off
256917
Coding set for 4 hand connectors, fixed mounting IZM-XKL-C 1off Prevents reversal of
256916 control circuit plugs,
for example during
maintenance. IZM-XKL-SS IZM-XKL-SK

e
Wiping contact module with screw terminals IZM-XKL-SS 1 off
101523

IZM-XKL-ML
a Standard: with screw terminals
b Optional: screw-type terminal connection
c Optional: Spring-loaded terminals
d Option: please order positions b or c separately.
e Plug on basic device

Adapter - plug connector


For 1000 V switch IZM-XKL-AML-1000V 1 off One off required per
263472 control circuit
connector (only for
subsequent ordering
of accessories).
11/40 Ordering Ordering 11/41
Closing release, trip block Closing release, trip block
IZM-XE… , IZM-XA… Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM-XE… , IZM-XA…
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Rated control voltage Part no. suffix Price Std. pack Part no. Price Std. pack Notes Notes
Order number for orders with see price list Order number for separate see price list
Us basic unit orders
V
from 630 A to 6300 A

from 630 A to 6300 A


Closing releases

Closing release
100 % duty factor
24 DC – +IZM-XE24DC 1 off IZM-XE/A24DC 1 off Closing releases and shunt releases have the same construction. A closing release is necessary for remote-ON.
230564 230565 The function is determined by the position where they are Remote-OFF must be implemented by the shunt release or the undervoltage release.
DC – 30 +IZM-XEDC IZM-XE/A30DC installed. In addition to the closing release it is possible to install:
230566 230567 • up to two shunt releases or
• a shunt release and an undervoltage release
DC – 48 +IZM-XE48DC IZM-XE/A48DC
230568 230569
DC – 60 +IZM-XE60DC IZM-XE/A60DC
230570 230571
110 DC +IZM-XE110AC/DC IZM-XE/A110AC/DC
110 AC, 50/60 Hz 230572 230573
220 DC +IZM-XE230AC/220DC IZM-XE/A230AC/220DC
230 AC, 50/60 Hz 230574 230575
Over-excited closing release
Retrieval time: 25 ms
5 % duty factor
24 DC – +IZM-XE24DC05 1 off IZM-XE/A24DC05 1 off Not suitable for uninterrupted operation.
230576 230577 With cut-off switch (internal auxiliary switch).
DC – 48 +IZM-XE48DC05 IZM-XE/A48DC05
230578 230579
110 – 125 DC +IZM-XE110AC/DC05 IZM-XE/A110AC/DC05
110 – 127 AC, 50/60 Hz 230580 230581
220 – 250 DC +IZM-XE230AC/DC05 IZM-XE/A230AC/DC05
208 – 240 AC, 50/60 Hz 230582 230583
Shunt releases

First shunt release


100 % duty factor
24 DC – +IZM-XA24DC 1 off For separate order, select part no. IZM-XE/A... For Remote ON, a closing release is required.
230546 Closing releases and shunt releases have the same construction. Remote OFF must be implemented with shunt releases or undervoltage releases.
DC – 30 +IZM-XA30DC The function is determined by the position where it is installed. The following can be fitted in addition to the closing release:
230548 • Up to two shunt releases or
• one shunt release and one undervoltage release
48 DC – +IZM-XA48DC Capacitor store on request.
230550
DC – 60 +IZM-XA60DC
230552
110 DC +IZM-XA110AC/DC
110 AC, 50/60 Hz 230554
220 DC +IZM-XA230AC/220DC
230 AC, 50/60 Hz 230556
11/42 Ordering Ordering 11/43
Closing release, trip block Closing release, trip block
IZM-XA… , IZM-XE… , IZM-XU… Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM-XA… , IZM-XE… , IZM-XU…
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Rated control voltage Part no. suffix Price Std. pack Part no. Price Std. pack Notes Notes
Order number for orders with see price list Order number for separate see price list
Us basic unit orders
V
from 630 A to 6300 A

from 630 A to 6300 A


Shunt releases

Second shunt releases


100 % duty factor
24 DC – +IZM-XA1(24DC) 1 off IZM-XE/A24DC 1 off For separate order, select part no. IZM-XE/A... For Remote ON, a closing release is required.
230760 230565 Closing releases and shunt releases have the same construction. Remote OFF must be implemented with shunt releases or undervoltage releases.
DC – 30 +IZM-XA1(30DC) IZM-XE/A30DC The function is determined by the position where it is installed. The following can be fitted in addition to the closing release:
230762 230567 A control circuit plug IZM-XKL-... is required for the connection • Up to two shunt releases or
when ordered separately. Order separately if required. • one shunt release and one undervoltage release
DC – 48 +IZM-XA1(48DC) IZM-XE/A48DC a Terminal assignment, page 11/5 Capacitor store on request.
230764 230569
DC – 60 +IZM-XA1(60DC) IZM-XE/A60DC
230766 230571
110 DC +IZM-XA1(110AC/DC) IZM-XE/A110AC/DC
110 AC, 50/60 Hz 230768 230573
220 DC +IZM-XA1(230AC/220DC) IZM-XE/A230AC/220DC
230 AC, 50/60 Hz 230770 230575
Undervoltage releases

Short-time delay (200 ms) possible with


jumper
24 DC – +IZM-XU24DC 1 off IZM-XU24DC 1 off A control circuit plug IZM-XKL-… is required for the connection A closing release is necessary for remote-ON.
230584 230585 when ordered separately. Order separately if required. Remote-OFF must be implemented by the shunt release or the undervoltage release.
DC – 30 +IZM-XU30DC IZM-XU30DC a Terminal assignment, page 11/5 In addition to the closing release it is possible to install:
230586 230587 • up to two shunt releases or
• a shunt release and an undervoltage release
48 DC – +IZM-XU48DC IZM-XU48DC
230588 230589
60 DC +IZM-XU60DC IZM-XU60DC
101525 101524
110 – 125 DC +IZM-XU127AC/125DC IZM-XU127AC/125DC
110 – 127 AC, 50/60 Hz 230591 230592
220 – 250 DC +IZM-XU240AC/250DC IZM-XU240AC/250DC
208 – 240 AC, 50/60 Hz 230593 230594
380 – 415 AC, 50/60 Hz +IZM-XU415AC IZM-XU415AC
230595 230596
Delayed
delay time 0.2 – 3.2 s
DC – 48 +IZM-XUV48DC 1 off IZM-XUV48DC 1 off With second input for non-delayed release.
230597 230598 A control circuit plug IZM-XKL-… is required for the connection
110 – 125 DC +IZM-XUV127AC/125DC IZM-XUV127AC/125DC when ordered separately. Order separately if required.
110 – 127 AC, 50/60 Hz 230599 230600 a Terminal assignment, page 11/5
220 – 250 DC +IZM-XUV240AC/250DC IZM-XUV240AC/250DC
208 – 240 AC, 50/60 Hz 230601 230602
380 – 415 AC, 50/60 Hz +IZM-XUV415AC IZM-XUV415AC
230603 230604
11/44 Ordering
Electrically ON, emergency-stop, brackets, door seals
IZM…-X... Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Part no. suffix Price Part no. Price Std. pack Notes
Order number for see price list Order see price list
orders with basic number for
unit separate
orders
from 630 A to 6300 A

Electrical ON
Can not be combined with motor cut-off switch,
Can not be combined with communication module,
Can be used only in combination with closing release,
If required, order cover for mechanical ON (IZM-
XVD...) separately

Push-button with sealable +IZM-XEE-TP IZM-XEE-TP 1 off If ordered separately a control


shroud 230721 230722 circuit plug is necessary for
Safety lock, Make: CES +IZM-XEE-C IZM-XEE-C 1 off connection. Order if required
230723 230724 a Terminal assignment,
page 11/5
Order cover for mechanical
ON (IZM-XVD…) separately,
if required.

Emergency-Stop actuator
+IZM-XPV IZM-XPV 1 off mushroom actuator instead of
230646 230647 the mechanical OFF-actuator

Part no. Price Std. pack Notes


Article no. see price list

Mounting brackets for fixed mounted circuit-


breakers
IZM1/2-XTW 1 off 1 pair, wall mounting for:
230731 • IZM...1-...
• IZM...2-...
• IN...1-...
• IN...2-...

Door seal
IZM-XRT 1 off For door cut-out with degree of protection IP40, cover of the
230730 door cut-out

Protective cover
IZM-XDT 1 off Degree of protection IP55, transparent,
230750 Can not be combined with door sealing frame.
Shroud removable or can be opened to left or right.
Engineering 11/45
Control circuit plug terminal assignment plan
http://catalog.moeller.net Moeller HPL0211-2007/2008

Circuit-breakers, switch-disconnectors
Control circuit plug IZM-XKL(-AV) for customer connection (a page 11/38)
Control circuit plugs X8, X7, X6, X5 are identical Internal Terminals External

X8: optional control circuit plug


X8

from 630 A to 6300 A


(Connections X8:1 to X8:8 only with IZM…- L/L+
U… and IZM…-D…) XFR remote reset 14 Us
13 N/L-
aelectronic G-converter S2 12 e.g. converter transformer star
overload release point or summation current
G-converter S1 11 transformer 1200 A/1 A
IZM-XW(C) N-converter S2 10
Jumper if no N-converter
IZM-XW(C) N-converter S1 9
External voltage transformer star 8 L1
External voltage transformer L3 7 L2
External voltage transformer L2 a L3
6
External voltage transformer L1 5 N
0 V DC 4 24 V DC external power
24 V DC 3 supply
Internal system bus + 2
Internal system bus … 1
Terminating resistor,
(120 O) no external system
X7: optional control circuit plug bus module
X7

Internal
External
Not available with IZM-XCOM- 14
DP communication function.
The communications XHIA tripped signalling switch 13

IN Enable
module is at position 12 IZM-XCOM-DP

DPWrite Free
1
X7. XHIF spring-operated stored energy 11

2
mechanism state signal 10
L/L+ Us

3
9
XEE electrically “ON”
8

Free
– +
7

5
6
XHIS signalling switch on first voltage release

Close
– +
5

7
4

XE
3

Open
– +
XHIS signalling switch on second voltage release 2

OUT
1
XU
XA,
X6: standard control circuit plug X6
XE/A first shunt release 14 L/L+ Us
13 N/L-
12
XHI standard auxiliary switch: S1 "N/O"
11
10
XHI standard auxiliary switch: S1 "N/C"
9
XE/A closing release 8 N/L- Us
7 L/L+
6
XHIB “ready to close” auxiliary switch
5
4
XHI standard auxiliary switch: S2 "N/O"
3

XHI standard auxiliary switch: S2 "N/C" 2


1

X5: optional control circuit plug


X5
14 Emergency-stop or jumper
Only XUV “non-delayed trip”
13
12 L/L+ Us
XA1, XU, XUV second voltage release
11 N/L-
10
Standard auxiliary contact XHI11/XHI22/XHI31: S3“NO”, XHI40: S7 "N/O"
9
8
Standard auxiliary contact XHI11/XHI22/XHI31: S3“NC”, XHI40: S7 "N/O"
7
6
Standard auxiliary contact XHI22: S4“NO”, XHI31/XHI40: S8 "N/O"
5
4
Standard auxiliary contact XHI22: S4“NC”, XHI31/XHI40: S8 "N/O"
3
a b L/L+
Motor operators M 2 Us
XMS optional motor cut-off switch 1 N/L-
a black-white
b brown
11/46 Ordering
Locking devices
IZM-XV... Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Part no. suffix Price Part no. Price Std. Notes


Order number for see price list Order number see price list pack
orders with basic for separate
unit orders
from 630 A to 6300 A

ON and OFF key locking facility

Locking set with two covers for padlocks or +IZM-XVD IZM-XVD 1 off Prevents local switching.
seal, two covers for tool operation and two 230642 230645 Electrical remote operation is still
lock barrel holders possible.
Can be locked with a 6 to 8 mm
padlock.
Padlock and barrel lock are not
supplied.

Locking set as before, but with a CES safety IZM-XVD-CES 1 off Prevents local switching.
lock 256975 Electrical remote operation is still
possible.

Locking device, locking in OFF1)

With CES safety lock +IZM-XVDM IZM-XVDM 1 off Locking in OFF position fulfils
230640 230643 isolator conditions

With Ronis safety lock +IZM-XVDM-R IZM-XVDM-R Locking in OFF position fulfils
263860 263861 isolator conditions

Castell mounting kit +IZM-XVDME-C IZM-XVDME-C Locking in OFF position fulfils


230641 230644 isolator conditions.
The lock is not included as
standard.

Locking shackle, for up to four 6 mm padlocks, +IZM-XVDMV IZM-XVDMV Locking in OFF position fulfils
lockable 230778 230779 isolator conditions.
Padlocks are not included as
standard.

Locking in OFF position, independently of +IZM-XVZ-AV IZM-XVZ-AV Locking in OFF position fulfils
switch, only for withdrawable modules (CES 263436 256986 isolator conditions.
lock in control panel door)

Locking as previously with additional Ronis +IZM-XVZ-R-AV IZM-XVZ-R-AV Cannot be combined with (+)IZM-
safety lock 263438 263437 XVK-AV and IZM-XVV.
Locking device to prevent movement of
the circuit-breaker in the withdrawable
unit
Prevents movement of the switch in the
withdrawable unit
Locking of the crank handle to prevent +IZM-XVK-AV IZM-XVK-AV 1 off Can not be combined with
movement (lock beside the crank handle); 230648 230649 (+)IZM-XV-AV and IZM-XVV.
make: CES
Lock to prevent movement out of the +IZM-XV-AV IZM-XV-AV
disconnected position (lock in the control 230650 230651
panel door); make: CES
Locking as previously with additional Ronis +IZM-XV-R-AV IZM-XV-R-AV
safety lock 263463 263464
Operator lever locking facility

Hand lever can be locked with a padlock. IZM-XVS 1 off Prevents manual charging of the
256987 spring energy store.
The padlock is not included as
standard.

Notes 1) Formechanical interlock with (+) IZM-XVDM… there is simultaneously an electrical interlock, i.e. closing release has
no effect.
Ordering 11/47
Locking devices
http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM-XV..., IZM-XMV...

Circuit-breakers, switch-disconnectors
Part no. suffix Price Part no. Price Std. pack Notes
Order number for see price Order number for see price
orders with basic list separate orders list
unit

from 630 A to 6300 A


Door interlock
For fixed mounting, effective when +IZM-XVT IZM-XVT 1 off Interlock can be overridden with tool
switch in ON position 230652 230653
For withdrawable units, effective in +IZM-XVT-AV IZM-XVT-AV 1 off Interlock can be overridden with tool
connected position 230654 230655
Locking arrangement
Locking arrangement for open control
panel utilization prevention

+IZM-XVV IZM-XVV 1 off Can not be combined with (+)IZM-


230660 230661 XVK-AV and IZM-XV-AVV.
Mechanical interlock
Mechanical interlock with Bowden
cables for 2 or 3 IZM/IN switches (side-
by-side or above each other)

Assembly kit for one fixed +IZM-XMV IZM-XMV 1 off Order an assembly kit with each switch
mounting switch, with 2 m 230662 232168
Bowden cables
Assembly kit for one withdrawable +IZM-XMV-AV IZM-XMV-AV Order an assembly kit with each switch
switch, with 2 m Bowden cables 230663 232169 For IZM(IN)...3-..., one additional
adapter set required per switch:
(+)IZM3-XMVAS-AV

Adapter set, required from +IZM3-XMVAS- IZM3-XMVAS-AV For withdrawable IZM(IN)...3-..., one
withdrawable units of frame size 3 AV 263474 additional adapter set required per
263473 switch:
2 m Bowden cables IZM-XMVB200 For triple interlocks, additional
232176 Bowden cables may, depending on the
3 m Bowden cables IZM-XMVB300 application, be required (see operating
232177 manual AWB1230-1407D/GB, section
18).
4.5 m Bowden cables IZM-XMVB450
232178
6 m Bowden cables IZM-XMVB600
232179
Individual components for
replacement or when ordering
withdrawable unit and switch for AV
separately
Individual components for replacement
purposes or with separate order of
withdrawable unit and switch for
withdrawable unit.
Intermediate shaft with coupling IZM-XMVAD 1 off Installation on the switch for
232175 withdrawable unit.
(IZM-XMV-AV) = (IZM-XMVAD) +
(IZM-XMVAD-AV)
Mechanical locking module for IZM-XMVAD-AV 1 off For fitting to the withdrawable unit.
withdrawable unit, with 2 m 259206 (IZM-XMV-AV) = (IZM-XMVAD) +
Bowden cables (IZM-XMVAD-AV)
11/48 Ordering
Withdrawable units
IZM... -XAV... Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Pole For use with Rated Part no. suffix Price Part no. Price Std. Notes
current = Order number for see price Order number see price pack
rated orders with basic list for separate list
uninterrupt unit orders
ed current
from 630 A to 6300 A

In = Iu
A

Withdrawable unit

3- IZM...1-... 630 +IZM1-XAV10 IZM1-XAV10 1 off Standard: Horizontal connections; versions a


pole IN...1-... 800 230733 230734 Connections for withdrawable unit.
1000 A rated operational voltage of 1000 V is possible
IZM...1-... 1250 +IZM1-XAV16 IZM1-XAV16 only when ordering together with the basic unit
IN...1-... 1600 230735 230736 for 1000 V.
When ordering separately, note:
IZM...2-... 800 +IZM2-XAV20 IZM2-XAV20 • Withdrawable units already contain four control
IN...2-... 1000 225772 225978 circuit plugs (X5 – X8) with screw-type
1250 terminals.
1600 • Can be combined only with basic units that
2000 have been prepared for withdrawable units
2500 +IZM2-XAV25 IZM2-XAV25 (basic unit +IZM-XAVE or with IZM...-XUS...-AV
225773 225979 conversion kit)
3200 +IZM2-XAV32 IZM2-XAV32
225774 225980
IZM...3-... 4000 +IZM3-XAV40 IZM3-XAV40
IN...3-... 230737 230738
5000 +IZM3-XAV50 IZM3-XAV50
230739 230740
6300 +IZM3-XAV63 IZM3-XAV63
225776 225982
4- IZM...1-4-... 1000 +IZM1-XAV104 IZM1-XAV104
pole IN...1-4-... 230742 230743
IZM...1-4-... 1600 +IZM1-XAV164 IZM1-XAV164
IN...1-4-... 230744 230745
IZM...2-4-... 2000 +IZM2-XAV204 IZM2-XAV204
IN...2-4-... 225779 225985
2500 +IZM2-XAV254 IZM2-XAV254
225780 225986
3200 +IZM2-XAV324 IZM2-XAV324
225781 225987
IZM...3-4-... 4000 +IZM3-XAV404 IZM3-XAV404
IN...3-4-... 230746 230747
5000 +IZM3-XAV504 IZM3-XAV504
230748 230749
6300 +IZM3-XAV634 IZM3-XAV634 6300 A device: connections always vertical.
257006 257001 A rated operational voltage of 1000 V is possible
only when ordering together with the basic unit
for 1000 V.
When ordering separately, note:
• Withdrawable units already contain four control
circuit plugs (X5 – X8) with screw-type
terminals.
• Can be combined only with basic units that
have been prepared for withdrawable units
(basic unit +IZM-XAVE or with IZM...-XUS...-AV
conversion kit)
Replacement switch
For withdrawable unit
– – +IZM-XAVE 1 off Type suffix for basic unit for use in withdrawable
225784 unit
• For replacements or
• when ordering basic unit and withdrawable
unit separately
The basic unit is factory-modified (cranks, control
sliders, side panels) to allow its insertion in the
respective withdrawable unit.
Ordering 11/49
Withdrawable units
http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM...-XUS…, IZM-X…

Circuit-breakers, switch-disconnectors
Pole For use with Part no. suffix Price Part no. Price Std. pack Notes
Order number for see price Order number for see price
orders with basic unit list separate orders list

Conversion kit

from 630 A to 6300 A


Fixed mounted in withdrawable unit
3-pole IZM...1-... IZM1-XUS-AV 1 off Retrospectively converting
IN...1-... 256950 fixed mounting switches
IZM...2-... IZM2-XUS-AV (cranks, control sliders,
IN...2-... 256951 side panels) to allow the
switch to be used in the
IZM...3-... IZM3-XUS-AV respective withdrawable
IN...3-... 256952 unit.
4-pole IZM...1-4-... IZM1-XUS4-AV
IN...1-4-... 256955
IZM...2-4-... IZM2-XUS4-AV
IN...2-4-... 256957
IZM...3-4-... IZM3-XUS4-AV
IN...3-4-... 256959
Position signalling switches
For withdrawable unit

Module 1 – +IZM-XHIAV1 IZM-XHIAV1 1 off Position signal


230708 232166 Connected position: 1
changeover contact
Test position: 1
changeover contact
Disconnected position: 1
changeover contact
Module 2 – +IZM-XHIAV2 IZM-XHIAV2 1 off Position signal
230709 232167 Connected position: 3
changeover contacts
Test position: 2
changeover contacts
Disconnected position: 1
changeover contact
Shutters

3-pole IZM...1-... +IZM1-XIKL IZM1-XIKL 1 off Standard: Lockable with


IN...1-... 230664 230665 padlocks
IZM...2-... +IZM2-XIKL IZM2-XIKL
IN...2-... 225808 226007
IZM...3-... +IZM3-XIKL IZM3-XIKL
IN...3-... 225810 226009
4-pole IZM...1-4-... +IZM1-XIKL4 IZM1-XIKL4
IN...1-4-... 230666 230667
IZM...2-4-... +IZM2-XIKL4 IZM2-XIKL4
IN...2-4-... 225809 226008
IZM...3-4-... +IZM3-XIKL4 IZM3-XIKL4
IN...3-4-... 225811 226010
Arcing chamber cover
For withdrawable unit F 690 V
3-pole IZM...1-... +IZM1-XLKA-AV IZM1-XLKA-AV 1 off
IN...1-... 230696 230697
IZM...2-... +IZM2-XLKA-AV IZM2-XLKA-AV
IN...2-... 230698 230699
IZM...3-... +IZM3-XLKA-AV IZM3-XLKA-AV
IN...3-... 230700 230701
4-pole IZM...1-4-... +IZM1-XLKA4-AV IZM1-XLKA4-AV
IN...1-4-... 230702 230703
IZM...2-4-... +IZM2-XLKA4-AV IZM2-XLKA4-AV
IN...2-4-... 230704 230705
IZM...3-4-... +IZM3-XLKA4-AV IZM3-XLKA4-AV
IN...3-4-... 230706 230707
Coding system
for equipment dependent coding
– IZM-XCE 1 36 coding variants
225999
11/50 Ordering Ordering 11/51
Connection systems for fixed mounting Connection systems for fixed mounting
IZM...-XAT... Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM...-XAT...
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
For use with Rated current = rated Type suffix Std. pack Type Std. pack Notes Notes
uninterrupted current Order number for orders with Order number for separate
In = Iu basic unit orders
A

Connection type for fixed mounted unit, individual connectors


from 630 A to 6300 A

from 630 A to 6300 A


Vertical connection
IZM...1(-4)-... 1000 +IZM1-XATV10 1 off IZM1-XATV10 1 off For the 3-pole circuit-breakers,
IN...1(-4)-... 257013 257009 6 connections are to be
IZM...1(-4)-... 1600 +IZM1-XATV16 IZM1-XATV16 (+)IZM1-XATV16 consists of 2 x (+)IZM1-XATV10 ordered and for the 4-pole
IN...1(-4)-... 230450 230451 circuit-breakers, 8 connections
are to be ordered
IZM...2(-4)-... 2500 +IZM2-XATV25 IZM2-XATV25
IN...2(-4)-... 230877 230878
IZM...2(-4)-... 3200 +IZM2-XATV32 IZM2-XATV32 (+)IZM2-XATV32 consists of 2 x (+)IZM2-XATV25
IN...2(-4)-... 230452 230453
IZM...3(-4)-... 5000 +IZM3-XATV50 IZM3-XATV50 (+)IZM3-XATV50 has the same design as the vertical connection
IN...3(-4)-... 230454 230455 supplied as standard with the 6300 A (fixed mounting) devices.

Front connection top (single-hole fitting)


When front connections are used, a partition between busbar and arcing space must be fitted on the
system side.
IZM...1(-4)-... 1000 +IZM1-XAT1F10-O 1 off IZM1-XAT1F10-O 1 off For the 3-pole circuit-breakers,
IN...1(-4)-... 230456 230457 3 connections are to be
IZM...1(-4)-... 1600 +IZM1-XAT1F16-O IZM1-XAT1F16-O ordered and for the 4-pole
IN...1(-4)-... 230458 230459 circuit-breakers, 4 connections
are to be ordered
IZM...2(-4)-... 2000 +IZM2-XAT1F20-O IZM2-XAT1F20-O
IN...2(-4)-... 230460 230461
IZM...2(-4)-... 2500 +IZM2-XAT1F25-O IZM2-XAT1F25-O
IN...2(-4)-... 230462 230463
IZM...2(-4)-... 3200 +IZM2-XAT1F32-O IZM2-XAT1F32-O
IN...2(-4)-... 230464 230465
IZM...3(-4)-... 4000 +IZM3-XAT1F40-O IZM3-XAT1F40-O
IN...3(-4)-... 230466 230467
Front connection bottom (single-hole fitting)
IZM...1(-4)-... 1000 +IZM1-XAT1F10-U 1 off IZM1-XAT1F10-U 1 off For the 3-pole circuit-breakers,
IN...1(-4)-... 230468 230469 3 connections are to be
IZM...1(-4)-... 1600 +IZM1-XAT1F16-U IZM1-XAT1F16-U ordered and for the 4-pole
IN...1(-4)-... 230470 230471 circuit-breakers, 4 connections
are to be ordered
IZM...2(-4)-... 2000 +IZM2-XAT1F20-U IZM2-XAT1F20-U
IN...2(-4)-... 230472 230473
IZM...2(-4)-... 2500 +IZM2-XAT1F25-U IZM2-XAT1F25-U
IN...2(-4)-... 230474 230475
IZM...2(-4)-... 3200 +IZM2-XAT1F32-U IZM2-XAT1F32-U
IN...2(-4)-... 230476 230477
IZM...3(-4)-... 4000 +IZM3-XAT1F40-U IZM3-XAT1F40-U
IN...3(-4)-... 230478 230479
Front connection, top (double-hole fitting according to DIN 43673)
When front connections are used, a partition between busbar and arcing space must be fitted on the
system side.
IZM...1(-4)-... 1000 +IZM1-XATF10-O 1 off IZM1-XATF10-O 1 off For the 3-pole circuit-breakers,
IN...1(-4)-... 230480 230481 3 connections are to be
IZM...1(-4)-... 1600 +IZM1-XATF16-O IZM1-XATF16-O ordered and for the 4-pole
IN...1(-4)-... 230482 230483 circuit-breakers, 4 connections
are to be ordered
IZM...2(-4)-... 2000 +IZM2-XATF20-O IZM2-XATF20-O
IN...2(-4)-... 230484 230485
IZM...2(-4)-... 2500 +IZM2-XATF25-O IZM2-XATF25-O
IN...2(-4)-... 230486 230487
IZM...2(-4)-... 3200 +IZM2-XATF32-O IZM2-XATF32-O
IN...2(-4)-... 225819 226022
IZM...3(-4)-... 4000 +IZM3-XATF40-O IZM3-XATF40-O
IN...3(-4)-... 230488 230489
Front connection bottom (double-hole fitting according to DIN 43673)
IZM...1(-4)-... 1000 +IZM1-XATF10-U 1 off IZM1-XATF10-U 1 off For the 3-pole circuit-breakers,
IN...1(-4)-... 230490 230491 3 connections are to be
IZM...1(-4)-... 1600 +IZM1-XATF16-U IZM1-XATF16-U ordered and for the 4-pole
IN...1(-4)-... 230492 230493 circuit-breakers, 4 connections
are to be ordered
IZM...2(-4)-... 2000 +IZM2-XATF20-U IZM2-XATF20-U
IN...2(-4)-... 230494 230495
IZM...2(-4)-... 2500 +IZM2-XATF25-U IZM2-XATF25-U
IN...2(-4)-... 230496 230497
IZM...2(-4)-... 3200 +IZM2-XATF32-U IZM2-XATF32-U
IN...2(-4)-... 225820 226023
IZM...3(-4)-... 4000 +IZM3-XATF40-U IZM3-XATF40-U
IN...3(-4)-... 230498 230499
11/52 Ordering Ordering 11/53
Connection system for withdrawable unit Connection system for withdrawable unit
IZM...-XAT... Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM...-XAT...
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
Pole For use with Rated current = rated Part no. suffix Std. pack Part no. Std. pack Notes
uninterrupted current Order number for orders with basic unit Order number for separate
In = Iu orders
A

Connection type for withdrawable unit, individual connectors


from 630 A to 6300 A

from 630 A to 6300 A


Vertical connection
IZM...1(-4)-... 1000 +IZM1-XATV10-AV 1 off IZM1-XATV10-AV 1 off For the 3-pole circuit-breakers, 6 connections are to be ordered and for the 4-pole circuit-breakers,
IN...1(-4)-... 230500 230501 8 connections are to be ordered
IZM...1(-4)-... 1600 +IZM1-XATV16-AV IZM1-XATV16-AV
IN...1(-4)-... 230502 230503
IZM...2(-4)-... 2000 +IZM2-XATV20-AV IZM2-XATV20-AV
IN...2(-4)-... 230504 230505
IZM...2(-4)-... 2500 +IZM2-XATV25-AV IZM2-XATV25-AV
IN...2(-4)-... 230506 230507
IZM...2(-4)-... 3200 +IZM2-XATV32-AV IZM2-XATV32-AV
IN...2(-4)-... 230508 230509
IZM...3(-4)-... 5000 +IZM3-XATV50-AV IZM3-XATV50-AV
IN...3(-4)-... 230510 230511
Front connection (single-hole fitting)
IZM...1(-4)-... 1000 +IZM1-XAT1F10-AV 1 off IZM1-XAT1F10-AV 1 off For the 3-pole switches order six connections and for the 4-pole switches order eight connections.
IN...1(-4)-... 230514 230515 When ordering front connectors for withdrawable units separately, additional insulators are
IZM...1(-4)-... 1600 +IZM1-XAT1F16-AV IZM1-XAT1F16-AV required, which must be ordered separately.
IN...1(-4)-... 230516 230517 When ordering with the basic unit (type suffix), the insulators are included as standard.
IZM...2(-4)-... 2000 +IZM2-XAT1F20-AV IZM2-XAT1F20-AV
IN...2(-4)-... 230518 230519
IZM...2(-4)-... 2500 +IZM2-XAT1F25-AV IZM2-XAT1F25-AV
IN...2(-4)-... 230520 230521
IZM...2(-4)-... 3200 +IZM2-XAT1F32-AV IZM2-XAT1F32-AV
IN...2(-4)-... 230522 230523
IZM...3(-4)-... 4000 +IZM3-XAT1F40-AV IZM3-XAT1F40-AV
IN...3(-4)-... 230524 230525
Front connection (double-hole fitting according to DIN 43673)
IZM...1(-4)-... 1000 +IZM1-XATF10-AV 1 off IZM1-XATF10-AV 1 off For the 3-pole switches order six connections and for the 4-pole switches order eight connections.
IN...1(-4)-... 230526 230527 When ordering front connectors for withdrawable units separately, additional insulators are
IZM...1(-4)-... 1600 +IZM1-XATF16-AV IZM1-XATF16-AV required, which must be ordered separately.
IN...1(-4)-... 230528 230529 When ordering with the basic unit (type suffix), the insulators are included as standard.
IZM...2(-4)-... 2000 +IZM2-XATF20-AV IZM2-XATF20-AV
IN...2(-4)-... 230530 230531
IZM...2(-4)-... 2500 +IZM2-XATF25-AV IZM2-XATF25-AV
IN...2(-4)-... 230532 230533
IZM...2(-4)-... 3200 +IZM2-XATF32-AV IZM2-XATF32-AV
IN...2(-4)-... 230534 230535
IZM...3(-4)-... 4000 +IZM3-XATF40-AV IZM3-XATF40-AV
IN...3(-4)-... 230536 230537
Insulator for front connections
3-pole IZM...1-... – IZM1-XATFS 1 off For withdrawable units, the insulators for installing the front connections are required.
IN...1-... 256927 When ordering the front connections separately, you must order one insulator for each connection
IZM...2-... – IZM2-XATFS side (incoming and outgoing side).
IN...2-... 256928
IZM...3-... – IZM3-XATFS
IN...3-... 256930
4-pole IZM...1-4-... – IZM1-XATFS4
IN...1-4-... 256938
IZM...2-4-... – IZM2-XATFS4
IN...2-4-... 256940
IZM...3-4-... – IZM3-XATFS4
IN...3-4-... 256942
Flange connection
IZM...1(-4)-... 1000 +IZM1-XATA10-AV 1 off IZM1-XATA10-AV 1 off For the 3-pole circuit-breakers, 6 connections are to be ordered and for the 4-pole circuit-breakers,
IN...1(-4)-... 230817 230818 8 connections are to be ordered
IZM...1(-4)-... 1600 +IZM1-XATA16-AV IZM1-XATA16-AV
IN...1(-4)-... 230819 230820
IZM...2(-4)-... 2000 +IZM2-XATA20-AV IZM2-XATA20-AV
IN...2(-4)-... 230821 230822
IZM...2(-4)-... 2500 +IZM2-XATA25-AV IZM2-XATA25-AV
IN...2(-4)-... 230823 230824
IZM...2(-4)-... 3200 +IZM2-XATA32-AV IZM2-XATA32-AV
IN...2(-4)-... 230825 230826
IZM...3(-4)-... 4000 +IZM3-XATA40-AV IZM3-XATA40-AV
IN...3(-4)-... 230827 230828
11/54 Engineering
415 V AC selectivity table
IZM...1-A..., IZM...1-V... Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Selectivity Selection:
1
between circuit-breakers enables separate shut-down of faulty Provided that the short-circuit current does not exceed those
system sections. Selectivity (discrimination) exists between incom- values specified (Icceff in kA). These details represent the
2 3 4
ing breaker 1 and outgoing breaker 2 if, only outgoing breaker 2 limits of selectivity. Both circuit-breakers will switch off with
In : Rated current trips at position 2 during a short-circuit. System sections 3 and 4 higher short-circuit currents.
continue to be operational. On IZM circuit-breakers with V, U, D releases, the delay time
Iu : Rated uninterrupted current tsd must be at least 100 ms longer than the delay time of the
from 630 A to 6300 A

next downstream levels (2, 3, 4).


Ii: Setting: non-delayed short-circuit
releases

Part no. IZM…1-A… IZM…1-V…


incoming circuit-breakers with standard trip release (A) incoming circuit-breakers with selectively-operating release (V)
In = Iu [A] 630 800 1000 1250 1600 630 800 1000 1250 1600
Ii [A] 5040 6400 8000 10000 12800 12600 16000 20000 25000 32000
Icu[kA] 50 65 50 65 50 65 50 65 50 65 50 65 50 65 50 65 50 65 50 65

Outgoing circuit- Prospective short-circuit current (kA)


breaker
Iu [A] Icu[kA] B N B N B N B N B N B N B N B N B N B N
NZM...1-A... 40 25(50) 5 5 6 6 8 8 12 12 16 16 16 16 T(35) T(35) T T T T T T
50 25(50) 5 5 6 6 8 8 12 12 16 16 16 16 T(35) T(35) T T T T T T
63 25(50) 5 5 6 6 8 8 12 12 16 16 16 16 T(35) T(35) T T T T T T
80 25(50) 5 5 6 6 8 8 12 12 16 16 16 16 T(35) T(35) T T T T T T
100 25(50) 5 5 6 6 8 8 12 12 16 16 16 16 T(35) T(35) T T T T T T
125 25(50) 5 5 6 6 8 8 12 12 16 16 16 16 T(35) T(35) T T T T T T
NZM...2-A... 40 100(150) 5 5 6 6 8 8 12 12 20 20 20 20 40 40 T T T T T T
50 100(150) 5 5 6 6 8 8 12 12 20 20 20 20 40 40 T T T T T T
63 100(150) 5 5 6 6 8 8 12 12 20 20 20 20 40 40 T T T T T T
80 100(150) 5 5 6 6 8 8 12 12 20 20 20 20 40 40 T T T T T T
100 100(150) 5 5 6 6 8 8 12 12 20 20 20 20 40 40 T T T T T T
125 25...150 5 5 6 6 8 8 12 12 20 20 20 20 T(40) T(40) T T T T T T
160 25...150 5 5 6 6 8 8 12 12 20 20 20 20 T(40) T(40) T T T T T T
200 25...150 5 5 6 6 8 8 12 12 20 20 20 20 T(40) T(40) T T T T T T
250 25...150 5 5 6 6 8 8 12 12 20 20 20 20 T(40) T(40) T T T T T T
NZM...1-M... 40 25(50) 5 5 6 6 8 8 12 12 16 16 16 16 T(35) T(35) T T T T T T
50 25(50) 5 5 6 6 8 8 12 12 16 16 16 16 T(35) T(35) T T T T T T
63 25(50) 5 5 6 6 8 8 12 12 16 16 16 16 T(35) T(35) T T T T T T
80 25(50) 5 5 6 6 8 8 12 12 16 16 16 16 T(35) T(35) T T T T T T
NZM...2-M 125 25...150 5 5 6 6 8 8 12 12 20 20 20 20 T(40) T(40) T T T T T T
160 25...150 5 5 6 6 8 8 12 12 20 20 20 20 T(40) T(40) T T T T T T
200 25...150 5 5 6 6 8 8 12 12 20 20 20 20 T(40) T(40) T T T T T T
NZM...2-VE... 100 50...150 5 5 6 6 8 8 12 12 20 20 20 20 16 16 T T T T T T
160 50...150 5 5 6 6 8 8 12 12 20 20 20 20 16 16 T T T T T T
250 50...150 5 5 6 6 8 8 12 12 20 20 20 20 16 16 T T T T T T
NZM...3-...E... 250 50...150 5 5 6 6 8 8 12 12 12 12 12 12 16 16 20 20 30 30 T T
400 50...150 5 5 6 6 8 8 12 12 12 12 12 12 16 16 20 20 30 30 T T
630 50...150 5 5 6 6 8 8 12 12 12 12 12 12 16 16 20 20 30 30 T T
NZM...4-...E... 630 50...100 5 5 6 6 8 8 12 12 12 12 12 12 16 16 20 20 30 30 32 32
800 50...100 5 5 6 6 8 8 12 12 12 12 12 12 16 16 20 20 30 30 32 32
1000 50...100 5 5 6 6 8 8 12 12 12 12 12 12 16 16 20 20 30 30 32 32
1250 50...100 5 5 6 6 8 8 12 12 12 12 12 12 16 16 20 20 30 30 32 32
1600 50...100 5 5 6 6 8 8 12 12 12 12 12 12 16 16 20 20 30 30 32 32

Notes T: Full selectivity


Engineering 11/55
415 V AC selectivity table
http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM...1-U..., IZM...1-D...

Circuit-breakers, switch-disconnectors
Selectivity Selection:
1
between circuit-breakers enables separate shut-down of faulty Provided that the short-circuit current does not exceed those
system sections. Selectivity (discrimination) exists between incom- values specified (Icceff in kA). These details represent the
2 3 4
ing breaker 1 and outgoing breaker 2 if, only outgoing breaker 2 limits of selectivity. Both circuit-breakers will switch off with
In : Rated current trips at position 2 during a short-circuit. System sections 3 and 4 higher short-circuit currents.
continue to be operational. On IZM circuit-breakers with V, U, D releases, the delay time
Iu : Rated uninterrupted current tsd must be at least 100 ms longer than the delay time of the

from 630 A to 6300 A


next downstream levels (2, 3, 4).
Ii: Setting: non-delayed short-circuit
releases

Part no. IZM…1-U… IZM…1-D…


Incoming circuit-breaker with universal trip-release (U) incoming circuit-breaker with digital trip-relaese (D)
In = Iu [A] 630 800 1000 1250 1600 630 800 1000 1250 1600
Ii [kA] 40 52 40 52 40 52 40 52 40 52 40 52 40 52 40 52 40 52 40 52
Icu[kA] 50 65 50 65 50 65 50 65 50 65 50 65 50 65 50 65 50 65 50 65
OFF/ON OFF/ON OFF/ON OFF/ON OFF/ON
Outgoing circuit- Prospective short-circuit current (kA)
breaker
Iu [A] Icu[kA] B N B N B N B N B N B N B N B N B N B N
NZM...1-A... 40 25(50) T T T T T T T T T T T T T T T T T T T T
50 25(50) T T T T T T T T T T T T T T T T T T T T
63 25(50) T T T T T T T T T T T T T T T T T T T T
80 25(50) T T T T T T T T T T T T T T T T T T T T
100 25(50) T T T T T T T T T T T T T T T T T T T T
125 25(50) T T T T T T T T T T T T T T T T T T T T
NZM...2-A... 40 100(150) T T T T T T T T T T T T T T T T T T T T
50 100(150) T T T T T T T T T T T T T T T T T T T T
63 100(150) T T T T T T T T T T T T T T T T T T T T
80 100(150) T T T T T T T T T T T T T T T T T T T T
100 100(150) T T T T T T T T T T T T T T T T T T T T
125 25...100 T T T T T T T T T T T T T T T T T T T T
160 25...100 T T T T T T T T T T T T T T T T T T T T
200 25...100 T T T T T T T T T T T T T T T T T T T T
250 25...100 T T T T T T T T T T T T T T T T T T T T
NZM...1-M... 40 25(50) T T T T T T T T T T T T T T T T T T T T
50 25(50) T T T T T T T T T T T T T T T T T T T T
63 25(50) T T T T T T T T T T T T T T T T T T T T
80 25(50) T T T T T T T T T T T T T T T T T T T T
100 25(50) T T T T T T T T T T T T T T T T T T T T
NZM...2-M... 125 25...150 T T T T T T T T T T T T T T T T T T T T
160 25...150 T T T T T T T T T T T T T T T T T T T T
200 25...150 T T T T T T T T T T T T T T T T T T T T
NZM...2-VE... 100 50...150 T T T T T T T T T T T T T T T T T T T T
160 50...150 T T T T T T T T T T T T T T T T T T T T
250 50...150 T T T T T T T T T T T T T T T T T T T T
NZM...3-...E... 250 50...150 T T T T T T T T T T T T T T T T T T T T
400 50...150 T T T T T T T T T T T T T T T T T T T T
630 50...150 T T T T T T T T T T T T T T T T T T T T
NZM...4-...E... 630 50(100) T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52
800 50(100) T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52
1000 50(100) T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52
1250 50(100) T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52
1600 50(100) T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52 T/40 T/52

Notes T: Full selectivity


11/56 Engineering
415 V AC selectivity table
IZM...2-A... Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Selectivity Selection:
1
between circuit-breakers enables separate shut-down of faulty Provided that the short-circuit current does not exceed those
system sections. Selectivity (discrimination) exists between incom- values specified (Icceff in kA). These details represent the
2 3 4
ing breaker 1 and outgoing breaker 2 if, only outgoing breaker 2 limits of selectivity. Both circuit-breakers will switch off with
In : Rated current trips at position 2 during a short-circuit. System sections 3 and 4 higher short-circuit currents.
continue to be operational.
Iu : Rated uninterrupted current
from 630 A to 6300 A

Ii: Setting: non-delayed short-circuit


releases

Part no. IZM…2-A…


incoming circuit-breaker with standard trip-releaes (A) Ii = 8 x In
In = Iu [A] 800 1000 1250 1600 2000 2500 3200
Ii [A] 6400 8000 10000 12800 16000 20000 25600
Icu[kA] 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100
Outgoing circuit-breaker Prospective short-circuit current (kA)

Iu [A] Icu[kA] B N H B N H B N H B N H B N H B N H B N H
NZM...1-A... 40 25(50) 6 6 6 8 8 8 10 10 10 16 16 16 T(25) T(25) T(25) T(42) T(42) T(42) T T T
50 25(50) 6 6 6 8 8 8 10 10 10 16 16 16 T(25) T(25) T(25) T(42) T(42) T(42) T T T
63 25(50) 6 6 6 8 8 8 10 10 10 16 16 16 T(25) T(25) T(25) T(42) T(42) T(42) T T T
80 25(50) 6 6 6 8 8 8 10 10 10 16 16 16 T(25) T(25) T(25) T(42) T(42) T(42) T T T
100 25(50) 6 6 6 8 8 8 10 10 10 16 16 16 T(25) T(25) T(25) T(42) T(42) T(42) T T T
125 25(50) 6 6 6 8 8 8 10 10 10 16 16 16 T(25) T(25) T(25) T(42) T(42) T(42) T T T
NZM...2-A... 40 100(150) 6 6 6 8 8 8 10 10 10 20 20 20 30 30 30 55 65 65 T T T
50 100(150) 6 6 6 8 8 8 10 10 10 20 20 20 30 30 30 55 65 65 T T T
63 100(150) 6 6 6 8 8 8 10 10 10 20 20 20 30 30 30 55 65 65 T T T
80 100(150) 6 6 6 8 8 8 10 10 10 20 20 20 30 30 30 55 65 65 T T T
100 100(150) 6 6 6 8 8 8 10 10 10 20 20 20 30 30 30 55 65 65 T T T
125 25...150 6 6 6 8 8 8 10 10 10 20 20 20 T(30) T(30) T(30) T(55) T(65) T(65) T T T
160 25...150 6 6 6 8 8 8 10 10 10 20 20 20 T(30) T(30) T(30) T(55) T(65) T(65) T T T
200 25...150 6 6 6 8 8 8 10 10 10 20 20 20 T(30) T(30) T(30) T(55) T(65) T(65) T T T
250 25...150 6 6 6 8 8 8 10 10 10 20 20 20 T(30) T(30) T(30) T(55) T(65) T(65) T T T
NZM...1-M... 40 25(50) 6 6 6 8 8 8 10 10 10 16 16 16 T(25) T(25) T(25) T(42) T(42) T(42) T T T
50 25(50) 6 6 6 8 8 8 10 10 10 16 16 16 T(25) T(25) T(25) T(42) T(42) T(42) T T T
63 25(50) 6 6 6 8 8 8 10 10 10 16 16 16 T(25) T(25) T(25) T(42) T(42) T(42) T T T
80 25(50) 6 6 6 8 8 8 10 10 10 16 16 16 T(25) T(25) T(25) T(42) T(42) T(42) T T T
100 25(50) 6 6 6 8 8 8 10 10 10 16 16 16 T(25) T(25) T(25) T(42) T(42) T(42) T T T
NZM...2-M... 125 25...150 6 6 6 8 8 8 10 10 10 20 20 20 T(30) T(30) T(30) T(55) T(65) T(65) T T T
160 25...150 6 6 6 8 8 8 10 10 10 20 20 20 T(30) T(30) T(30) T(55) T(65) T(65) T T T
200 25...150 6 6 6 8 8 8 10 10 10 20 20 20 T(30) T(30) T(30) T(55) T(65) T(65) T T T
NZM...2-VE... 100 50...150 6 6 6 8 8 8 10 10 10 20 20 20 30 30 30 T(55) T(65) T(65) T T T
160 50...150 6 6 6 8 8 8 10 10 10 20 20 20 30 30 30 T(55) T(65) T(65) T T T
250 50...150 6 6 6 8 8 8 10 10 10 20 20 20 30 30 30 T(55) T(65) T(65) T T T
NZM...3-E... 250 50...150 6 6 6 8 8 8 10 10 10 12 12 12 16 16 16 20 20 20 30 30 30
400 50...150 6 6 6 8 8 8 10 10 10 12 12 12 16 16 16 20 20 20 30 30 30
630 50...150 6 6 6 8 8 8 10 10 10 12 12 12 16 16 16 20 20 20 30 30 30
NZM...4-...E... 630 50(100) 6 6 6 8 8 8 10 10 10 12 12 12 16 16 16 20 20 20 25 25 25
800 50(100) 6 6 6 8 8 8 10 10 10 12 12 12 16 16 16 20 20 20 25 25 25
1000 50(100) 6 6 6 8 8 8 10 10 10 12 12 12 16 16 16 20 20 20 25 25 25
1250 50(100) 6 6 6 8 8 8 10 10 10 12 12 12 16 16 16 20 20 20 25 25 25
1600 50(100) 6 6 6 8 8 8 10 10 10 12 12 12 16 16 16 20 20 20 25 25 25

Notes T: Full selectivity


Engineering 11/57
415 V AC selectivity table
http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM...2-V..., IZM…3…-V

Circuit-breakers, switch-disconnectors
Selectivity Selection:
1
between circuit-breakers enables separate shut-down of faulty Provided that the short-circuit current does not exceed those
system sections. Selectivity (discrimination) exists between incom- values specified (Icc eff in kA). These details represent the lim-
2 3 4
ing breaker 1 and outgoing breaker 2 if, only outgoing breaker 2 its of selectivity. Both circuit-breakers will switch off with
In : Rated current trips at position 2 during a short-circuit. System sections 3 and 4 higher short-circuit currents. On IZM circuit-breakers with V,
continue to be operational. U, D releases, the delay time tsd must be at least 100 ms
Iu : Rated uninterrupted current longer than the delay time of the next downstream levels (2,

from 630 A to 6300 A


3, 4).
Ii: Setting: non-delayed short-circuit
releases

Part no. IZM…2(3)-V…


incoming circuit-breaker with selectively-operating trip-release (V) Iimax = 50 kA
In = Iu [A] 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
Ii [A] 16000 20000 25000 32000 40000 50000 50000 50000
Icu[kA] 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 100 100 100
Outgoing cir- Prospective short-circuit current (kA)
cuit-breaker
Iu [A] Icu[kA] B N H B N H B N H B N H B N H B N H B N H B N H
NZM...1-A...
40 25(50) T(35) T(35) T(35) T T T T T T T T T T T T T T T T T T T T T
50 25(50) T(35) T(35) T(35) T T T T T T T T T T T T T T T T T T T T T
63 25(50) T(35) T(35) T(35) T T T T T T T T T T T T T T T T T T T T T
80 25(50) T(35) T(35) T(35) T T T T T T T T T T T T T T T T T T T T T
100 25(50) T(35) T(35) T(35) T T T T T T T T T T T T T T T T T T T T T
125 25(50) T(35) T(35) T(35) T T T T T T T T T T T T T T T T T T T T T
NZM...2-A
40 100(150) 40 40 40 T T T T T T T T T T T T T T T T T T T T T
50 100(150) 40 40 40 T T T T T T T T T T T T T T T T T T T T T
63 100(150) 40 40 40 T T T T T T T T T T T T T T T T T T T T T
80 100(150) 40 40 40 T T T T T T T T T T T T T T T T T T T T T
100 100(150) 40 40 40 T T T T T T T T T T T T T T T T T T T T T
125 25...150 T(40) T(40) T(40) T T T T T T T T T T T T T T T T T T T T T
160 25...150 T(40) T(40) T(40) T T T T T T T T T T T T T T T T T T T T T
200 25...150 T(40) T(40) T(40) T T T T T T T T T T T T T T T T T T T T T
250 25...150 T(40) T(40) T(40) T T T T T T T T T T T T T T T T T T T T T
NZM...1-M...
40 25(50) T(35) T(35) T(35) T T T T T T T T T T T T T T T T T T T T T
50 25(50) T(35) T(35) T(35) T T T T T T T T T T T T T T T T T T T T T
63 25(50) T(35) T(35) T(35) T T T T T T T T T T T T T T T T T T T T T
80 25(50) T(35) T(35) T(35) T T T T T T T T T T T T T T T T T T T T T
100 25(50) T(35) T(35) T(35) T T T T T T T T T T T T T T T T T T T T T
NZM...2-M
125 25...150 T(40) T(40) T(40) T T T T T T T T T T T T T T T T T T T T T
160 25...150 T(40) T(40) T(40) T T T T T T T T T T T T T T T T T T T T T
200 25...150 T(40) T(40) T(40) T T T T T T T T T T T T T T T T T T T T T
NZM...2-E
100 50...150 16 16 16 T T T T T T T T T T T T T T T T T T T T T
160 50...150 16 16 16 T T T T T T T T T T T T T T T T T T T T T
250 50...150 16 16 16 T T T T T T T T T T T T T T T T T T T T T
NZM...3-...E...
250 50...150 16 16 16 20 20 20 30 30 30 T T T T T T T T T T T T T T T
400 50...150 16 16 16 20 20 20 30 30 30 T T T T T T T T T T T T T T T
630 50...150 16 16 16 20 20 20 30 30 30 T T T T T T T T T T T T T T T
NZM...4-...E
630 50...100 16 16 16 20 20 20 30 30 30 32 32 32 40 40 40 T(50) T(50) T(50) T(50) T(50) T(50) T(50) T(50) T(50)
800 50...100 16 16 16 20 20 20 30 30 30 32 32 32 40 40 40 T(50) T(50) T(50) T(50) T(50) T(50) T(50) T(50) T(50)
1000 50...100 16 16 16 20 20 20 30 30 30 32 32 32 40 40 40 T(50) T(50) T(50) T(50) T(50) T(50) T(50) T(50) T(50)
1250 50...100 16 16 16 20 20 20 30 30 30 32 32 32 40 40 40 T(50) T(50) T(50) T(50) T(50) T(50) T(50) T(50) T(50)
1600 50...100 16 16 16 20 20 20 30 30 30 32 32 32 40 40 40 T(50) T(50) T(50) T(50) T(50) T(50) T(50) T(50) T(50)

Notes T: Full selectivity


11/58 Engineering
415 V AC selectivity table
IZM...2-U..., IZM…3-U… Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Selectivity Selection:
1
between circuit-breakers enables separate shut-down of faulty Provided that the short-circuit current does not exceed those
system sections. Selectivity (discrimination) exists between incom- values specified (Icc eff in kA). These details represent the lim-
2 3 4
ing breaker 1 and outgoing breaker 2 if, only outgoing breaker 2 its of selectivity. Both circuit-breakers will switch off with
In : Rated current trips at position 2 during a short-circuit. System sections 3 and 4 higher short-circuit currents. On IZM circuit-breakers with V,
continue to be operational. U, D releases, the delay time tsd must be at least 100 ms
Iu : Rated uninterrupted current longer than the delay time of the next downstream levels (2,
from 630 A to 6300 A

3, 4).
Ii: Setting: non-delayed short-circuit
releases

Part no. IZM…2(3)-U…


incoming circuit-breaker with universal trip-release (U) Ii = 0.8 x Icu(= 0.8 x Ics)
In = Iu [A] 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
Ii [kA] 44 64 80 44 64 80 44 64 80 44 64 80 44 64 80 44 64 80 44 64 80 80
Icu[kA] 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 100 100 100
Outgoing cir- Prospective short-circuit current (kA)
cuit-breaker
Iu [A] Icu[kA] B N H B N H B N H B N H B N H B N H B N H B N H
OFF/ON OFF/ON OFF/ON OFF/ON OFF/ON OFF/ON OFF/ON OFF/ON
NZM...1-A...
40 25(25) T T T T T T T T T T T T T T T T T T T T T T T T
50 25(50) T T T T T T T T T T T T T T T T T T T T T T T T
63 25(50) T T T T T T T T T T T T T T T T T T T T T T T T
80 25(50) T T T T T T T T T T T T T T T T T T T T T T T T
100 25(50) T T T T T T T T T T T T T T T T T T T T T T T T
125 25(50) T T T T T T T T T T T T T T T T T T T T T T T T
NZM...2-A
40 100(150) T T T T T T T T T T T T T T T T T T T T T T T T
50 100(150) T T T T T T T T T T T T T T T T T T T T T T T T
63 100(150) T T T T T T T T T T T T T T T T T T T T T T T T
80 100(150) T T T T T T T T T T T T T T T T T T T T T T T T
100 100(150) T T T T T T T T T T T T T T T T T T T T T T T T
125 25...150 T T T T T T T T T T T T T T T T T T T T T T T T
160 25...150 T T T T T T T T T T T T T T T T T T T T T T T T
200 25...150 T T T T T T T T T T T T T T T T T T T T T T T T
250 25...150 T T T T T T T T T T T T T T T T T T T T T T T T
NZM...1-M
40 25(50) T T T T T T T T T T T T T T T T T T T T T T T T
50 25(50) T T T T T T T T T T T T T T T T T T T T T T T T
63 25(50) T T T T T T T T T T T T T T T T T T T T T T T T
80 25(50) T T T T T T T T T T T T T T T T T T T T T T T T
100 25(50) T T T T T T T T T T T T T T T T T T T T T T T T
NZM...2-M
125 25...150 T T T T T T T T T T T T T T T T T T T T T T T T
160 25...150 T T T T T T T T T T T T T T T T T T T T T T T T
250 25...150 T T T T T T T T T T T T T T T T T T T T T T T T
NZM...2-E
100 50...150 T T T T T T T T T T T T T T T T T T T T T T T T
160 50...150 T T T T T T T T T T T T T T T T T T T T T T T T
250 50...150 T T T T T T T T T T T T T T T T T T T T T T T T
NZM...3-...E...
250 50...150 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) T(80) T(80) T(80)
400 50...150 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) T(80) T(80) T(80)
630 50...150 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) T(80) T(80) T(80)
NZM...4-...E
630 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) T(80) T(80) T(80)
800 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) T(80) T(80) T(80)
1000 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) T(80) T(80) T(80)
1250 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) T(80) T(80) T(80)
1600 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) T(80) T(80) T(80)

Notes T: Full selectivity


Engineering 11/59
415 V AC selectivity table
http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM...2-D...

Circuit-breakers, switch-disconnectors
Selectivity Selection:
1
between circuit-breakers enables separate shut-down of faulty Provided that the short-circuit current does not exceed those
system sections. Selectivity (discrimination) exists between incom- values specified (Icc eff in kA). These details represent the lim-
2 3 4
ing breaker 1 and outgoing breaker 2 if, only outgoing breaker 2 its of selectivity. Both circuit-breakers will switch off with
In : Rated current trips at position 2 during a short-circuit. System sections 3 and 4 higher short-circuit currents. On IZM circuit-breakers with V,
continue to be operational. U, D releases, the delay time tsd must be at least 100 ms
Iu : Rated uninterrupted current longer than the delay time of the next downstream levels (2,

from 630 A to 6300 A


3, 4).
Ii: Setting: non-delayed short-circuit
releases

Part no. IZM…2-D…


incoming circuit-breake with digital trip-release (D) Ii = 0.8 x Icu = 0.8 x Ics
In = Iu [A] 800 1000 1250 1600
Ii [A] 44000 64000 80000 44000 64000 80000 44000 64000 80000 44000 64000 80000
Icu[kA] 55 80 100 55 80 100 55 80 100 55 80 100
Outgoing circuit-breaker Prospective short-circuit current (kA)

Iu [A] Icu[kA] B N H B N H B N H B N H
NZM...1-A... 40 25(50) T T T T T T T T T T T T
50 25(50) T T T T T T T T T T T T
63 25(50) T T T T T T T T T T T T
80 25(50) T T T T T T T T T T T T
100 25(50) T T T T T T T T T T T T
125 25(50) T T T T T T T T T T T T
NZM...2-A 40 100(150) T T T T T T T T T T T T
50 100(150) T T T T T T T T T T T T
63 100(150) T T T T T T T T T T T T
80 100(150) T T T T T T T T T T T T
100 100(150) T T T T T T T T T T T T
125 25...150 T T T T T T T T T T T T
160 25...150 T T T T T T T T T T T T
200 25...150
250 25...150 T T T T T T T T T T T T
NZM...1-M... 40 25(50) T T T T T T T T T T T T
50 25(50) T T T T T T T T T T T T
63 25(50) T T T T T T T T T T T T
80 25(50) T T T T T T T T T T T T
100 25(50) T T T T T T T T T T T T
NZM...2-M 125 25...150 T T T T T T T T T T T T
160 25...150 T T T T T T T T T T T T
200 25...150 T T T T T T T T T T T T
NZM...2-E 100 50...150 T T T T T T T T T T T T
160 50...150 T T T T T T T T T T T T
250 50...150 T T T T T T T T T T T T
NZM...3-...E... 250 50...150 T T T T T T T T T T T T
400 50...150 T T T T T T T T T T T T
630 50...150 T T T T T T T T T T T T
NZM4-...E 630 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80)
800 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80)
1000 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80)
1250 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80)
1600 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80)

Notes T: Full selectivity


11/60 Engineering
415 V AC selectivity table
IZM...2-D..., IZM…3-D… Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Selectivity Selection:
1
between circuit-breakers enables separate shut-down of faulty Provided that the short-circuit current does not exceed those
system sections. Selectivity (discrimination) exists between incom- values specified (Icc eff in kA). These details represent the lim-
2 3 4
ing breaker 1 and outgoing breaker 2 if, only outgoing breaker 2 its of selectivity. Both circuit-breakers will switch off with
In : Rated current trips at position 2 during a short-circuit. System sections 3 and 4 higher short-circuit currents. On IZM circuit-breakers with V,
continue to be operational. U, D releases, the delay time tsd must be at least 100 ms
Iu : Rated uninterrupted current longer than the delay time of the next downstream levels (2,
from 630 A to 6300 A

3, 4).
Ii: Setting: non-delayed short-circuit
releases

Part no. IZM…2(3)-D…


incoming circuit-breaker with digital trip-release (D) Ii = 0.8 x Icu = 0.8 x Ics
In = Iu [A] 2000 2500 3200 4000 5000 6300
Ii [A] 44000 64000 80000 44000 64000 80000 44000 64000 80000 80000 80000 80000
Icu [kA] 55 80 100 55 80 100 55 80 100 100 100 100
Outgoing circuit-breaker Prospective short-circuit current (kA)

Iu [A] Icu[kA] B N H B N H B N H B N H
NZM...1-A... 40 25(50) T T T T T T T T T T T T
50 25(50) T T T T T T T T T T T T
63 25(50) T T T T T T T T T T T T
80 25(50) T T T T T T T T T T T T
100 25(50) T T T T T T T T T T T T
125 25(50) T T T T T T T T T T T T
NZM...2-A 40 100(150) T T T T T T T T T T T T
50 100(150) T T T T T T T T T T T T
63 100(150) T T T T T T T T T T T T
80 100(150) T T T T T T T T T T T T
100 100(150) T T T T T T T T T T T T
125 25...150 T T T T T T T T T T T T
160 25...150 T T T T T T T T T T T T
200 25...150 T T T T T T T T T T T T
250 25...150 T T T T T T T T T T T T
NZM...1-M... 40 25(50) T T T T T T T T T T T T
50 25(50) T T T T T T T T T T T T
63 25(50) T T T T T T T T T T T T
80 25(50) T T T T T T T T T T T T
100 25(50) T T T T T T T T T T T T
NZM...2-M... 125 25...150 T T T T T T T T T T T T
160 25...150 T T T T T T T T T T T T
250 25...150 T T T T T T T T T T T T
NZM....2-E 100 50...150 T T T T T T T T T T T T
160 50...150 T T T T T T T T T T T T
250 50...150 T T T T T T T T T T T T
NZM...3-...E... 250 50...150 T T T T T T T T T T T T
400 50...150 T T T T T T T T T T T T
630 50...150 T T T T T T T T T T T T
NZM...4-...E 630 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) T(80) T(80) T(80)
800 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) T(80) T(80) T(80)
1000 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) T(80) T(80) T(80)
1250 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) T(80) T(80) T(80)
1600 50(100) 45 T(64) T(80) 45 T(64) T(80) 45 T(64) T(80) T(80) T(80) T(80)

Notes T: Full selectivity


Engineering 11/61
Tripping characteristics for circuit-breakers
http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM…-A…, IZM…-V…

Circuit-breakers, switch-disconnectors
Release for protection of systems
L-, I-trip
10000 The following characteristics each demonstrate the largest and smallest setting
in the respective protective area. In order to receive the complete tripping
Ir min. Ir max. characteristic, the respective characteristic sections have been brought together.
t [s]

1000 0.5 – 1.0 x In

from 630 A to 6300 A


The characteristic curves indicate the behaviour of the overcurrent release when
it has been activated by one of the currents flowing before the trip. If the
overcurrent trip occurs directly after switch on and if the overcurrent release is
not activated for this reason, the opening delay may extend by up to ms
100 depending on the level of the overcurrent. In order to determine the total
opening delay of the switch, about 15 ms are to be added to the shown opening
delays for the duration of the arc.
10
The curves shown apply for an ambient temperature on the switch of –
5 … +55 °C. The release can be operated at ambient temperatures from –
Ii min. Ii max. 20 … +70 °C (with LCD display up to 55 °C). An extended tolerance band range
1 can apply with these temperatures.
2 – 8 x In
Tolerances with the setting currents
0.1 L: trip between 1.05 and 1.2 x Ir
S: –0% +20%
I: –0% +20%
0.01
0.1 1 10 100 G: –0% +20%
I / In Tolerances with the trip times
L: –20% +0%
S: –0 ms +60 ms
I: < 50 ms
G: –0 ms +60 ms

L = current dependent delayed overload release


Release for selectively-opening circuit-breakers S = short-time delayed short-circuit release
I = non-delayed short-circuit release
L-, S, I-trip N = neutral pole overload release
N trip with option + IZM-XT G = earth-fault release
G trip with option + IZM-XT
Earth-fault release
A) IZM…1-…: 100 … 1200 A
IZM…2-…: 100 … 1200 A
IZM…3-…: 400 … 1200 A
10000

Ir min. Ir max.
t [s]

0.4 – 1.0 I
1000 x In N

100

10

Isd min. Isd max.


1 1.25 – 12 x In
tsd max.
0.1 – 0.4 s
0.1 tsd min.

Ii Ii f 20 x ln
max. 50 kA
0.01
0.1 1 10 100
I / In
11/62 Engineering
Tripping characteristics for circuit-breakers
IZM…-V…,IZM…-U…, IZM…-D… Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Earth-fault release
G trip with option + IZM-XT
10000 The following characteristics each demonstrate the largest and smallest setting
in the respective protective area. In order to receive the complete tripping
characteristic, the respective characteristic sections have been brought together.
t [s]

1000
from 630 A to 6300 A

The characteristic curves indicate the behaviour of the overcurrent release when
it has been activated by one of the currents flowing before the trip. If the
overcurrent trip occurs directly after switch on and if the overcurrent release is
not activated for this reason, the opening delay may extend by up to ms
100
depending on the level of the overcurrent. In order to determine the total opening
delay of the switch, about 15 ms are to be added to the shown opening delays
Ig min. Ig max. for the duration of the arc.
10
The curves shown apply for an ambient temperature on the switch of –
5 … +55 °C. The release can be operated at ambient temperatures from –
100 – 1200 A1) 20 … +70 °C (with LCD display up to 55 °C). An extended tolerance band range
1 can apply with these temperatures.
tg max.
0.1 – 0.5 s Tolerances with the setting currents
0.1 tg min.
L: trip between 1.05 and 1.2 x Ir
S: –0% +20%
I: –0% +20%
0.01
0.1 1000 10000 100000 G: –0% +20%
I [A]
Tolerances with the trip times
A) IZM…1-…: 100 … 1200 A
IZM…2-…: 100 … 1200 A L: –20% +0%
IZM…3-…: 400 … 1200 A S: –0 ms +60 ms
I: < 50 ms
Release for universal protection
IZM...-U... G: –0 ms +60 ms
IZM...-D...
L-trip L = current dependent delayed overload release
10000 S = short-time delayed short-circuit release
I4t = const. I = non-delayed short-circuit release
Ir N = neutral pole overload release
G = earth-fault release
t [s]

0.4 – 1.0
1000 x In

100 I2t = const.

10 tr
2 – 30 s

0.1

0.01
0.1 1 10 100
I / In
Engineering 11/63
Tripping characteristics
http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM...-U..., IZM...-D...

Circuit-breakers, switch-disconnectors
Release for universal protection

S-trip

10000 The following characteristics each demonstrate the largest and smallest setting
in the respective protective area. In order to receive the complete tripping
characteristic, the respective characteristic sections have been brought together.

from 630 A to 6300 A


t [s]

1000 The characteristic curves indicate the behaviour of the overcurrent release when
Isd it has been activated by one of the currents flowing before the trip. If the
overcurrent trip occurs directly after switch on and if the overcurrent release is
1.25 – 12 x In not activated for this reason, the opening delay may extend by up to ms
100 depending on the level of the overcurrent. In order to determine the total opening
delay of the switch, about 15 ms are to be added to the shown opening delays
I2tsd = const. for the duration of the arc.
10
The curves shown apply for an ambient temperature on the switch of –
I2tsd = const. 5 … +55 °C. The release can be operated at ambient temperatures from –
0.1 – 0.4 s 20 … +70 °C (with LCD display up to 55 °C). An extended tolerance band range
1 can apply with these temperatures.

tsd = const.
Tolerances with the setting currents
0.1 L: trip between 1.05 and 1.2 x Ir
0.02 – 0.4 s
S: –0% +20%
I: –0% +20%
0.01
0.1 1 10 100 G: –0% +20%
I / In Tolerances with the trip times
L: –20% +0%
S: –0 ms +60 ms
I: < 50 ms
G: –0 ms +60 ms

The characteristic curves apply for a circuit-breaker IZMH2…, 440 V with earth-
fault protection module

Release for universal protection


IZM...-U...
IZM...-D...

I-trip

10000
t [s]

1000

100

10

1
Ii
1.5 x In – 0.8 x Ics
0.1

0.01
0.1 1 10 100
I / In kA
11/64 Engineering
Tripping characteristics
IZM...-D..., IZM...-U... Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Earth-fault release
IZM...-U...
IZM...-D...
G trip with option (+)IZMU-XT(A)

10000 The following characteristics each demonstrate the largest and smallest setting in
from 630 A to 6300 A

the respective protective area. In order to receive the complete tripping


characteristic, the respective characteristic sections have been brought together.
t [s]

1000
The characteristic curves indicate the behaviour of the overcurrent release when it
has been activated by one of the currents flowing before the trip. If the overcurrent
trip occurs directly after switch on and if the overcurrent release is not activated
100 for this reason, the opening delay may extend by up to ms depending on the level
of the overcurrent. In order to determine the total opening delay of the switch,
about 15 ms are to be added to the shown opening delays for the duration of the
Ig arc.
10
I2t = const. The curves shown apply for an ambient temperature on the switch of –
5 … +55 °C. The release can be operated at ambient temperatures from –
1 100 – 1200 A1) 20 … +70 °C (with LCD display up to 55 °C). An extended tolerance band range
can apply with these temperatures.
tg
0.1 0.1 – 0.5 s Tolerances with the setting currents
L: trip between 1.05 and 1.2 x Ir
S: –0% +20%
0.01 I: –0% +20%
0.1 1000 10000 100000 G: –0% +20%
I [A]
Tolerances with the trip times
L: –20% +0%
S: –0 ms +60 ms
I: < 50 ms
G: –0 ms +60 ms

A) IZM…1-…: 100 … 1200 A


IZM…2-…: 100 … 1200 A
IZM…3-…: 400 … 1200 A
The characteristic curves apply for a circuit-breaker IZMH2…, 440 V with earth-fault
protection module

Digital release IZM...-D...


S-trip L = current dependent delayed overload release
S = short-time delayed short-circuit release
10000 I = non-delayed short-circuit release
N = neutral pole overload release
G = earth-fault release
t [s]

1000
Isd

100 1.25 x In – 0.8 x Icw

10

1 I2tsd = const.
tsd = const. 0.1 – 0.4 s
0.1 0.02 – 4 s

0.01
0.1 1 10 1
I / In I / Icw
The characteristic curves apply for a circuit-breaker IZMH2…, 440 V with earth-fault
protection module
L-, I-, G-trip, see universal circuit-breaker
Technical Data 11/65
Permissible continuous current
http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM..., IN...

Circuit-breakers, switch-disconnectors
Permissible continuous current
In dependence on the ambient temperature with horizontal or vertical connection
Part no. Version Ambient temperature

Up to 55 °C 60 °C 70 °C

from 630 A to 6300 A


IZM(IN)…1(-4)-
IZM…1(-4)-…630 Fixed mounted 630 630 630
IN…1(-4)-630 Withdrawable units 630 630 630
IZM…1(-4)-…800 Fixed mounted 800 800 800
IN…1(-4)-800 Withdrawable units 800 800 800
IZM…1(-4)-…1000 Fixed mounted 1000 1000 1000
IN…1(-4)-1000 Withdrawable units 1000 1000 910 (1000)
IZM…1(-4)-…1250 Fixed mounted 1250 1250 1250
IN…1(-4)-1250 Withdrawable units 1250 1250 1140 (1210)
IZM…1(-4)-…1600 Fixed mounted 1600 1600 1500 (1600)
IN…1(-4)-1600 Withdrawable units 1600 1600 1390 (1490)

IZM(IN)…2(-4)-…
IZM…2(-4)-…800 Fixed mounted 800 800 800
IN…2(-4)-800 Withdrawable units 800 800 800
IZM…2(-4)-…1000 Fixed mounted 1000 1000 1000
IN…2(-4)-1000 Withdrawable units 1000 1000 1000
IZM…2(-4)-…1250 Fixed mounted 1250 1250 1250
IN…2(-4)-1250 Withdrawable units 1250 1250 1250
IZM…2(-4)-…1600 Fixed mounted 1600 1600 1600
IN…2(-4)-1600 Withdrawable units 1600 1600 1520 (1600)
IZM…2(-4)-…2000 Fixed mounted 2000 2000 2000
IN…2(-4)-2000 Withdrawable units 2000 2000 2000
IZM…2(-4)-…2500 Fixed mounted 2500 2500 2350 (2360)
IN…2(-4)-2500 Withdrawable units 2500 2500 2220 (2280)
IZM…2(-4)-…3200 Fixed mounted 3200 3150 2910 (2940)
IN…2(-4)-3200 Withdrawable units 3200 3070 2790 (2870)

IZM(IN)…3(-4)-…
IZM…3(-4)-…4000 Fixed mounted 4000 4000 4000
IN…3(-4)-4000 Withdrawable units 4000 4000 4000
IZM…3(-4)-…5000 Fixed mounted 5000 5000 5000 (4860)
IN…3(-4)-5000 Withdrawable units 5000 5000 5000 (4730)
IZM…3(-4)-…6300 Fixed mounted 6300 A (40 °C) 6150 5910 (5970) 5610 (5670)
IN…3(-4)-6300 Withdrawable units 6300 A 5920 5810 (5900) 5400 (5500)
(40 °C)

Notes Figure in brackets: copper busbar painted black, partly with reduced, recommended terminal capacities
11/66 Technical Data Technical Data 11/67
Circuit-breakers Circuit-breakers
IZM...1 Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM...1
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
IZM…1(-4)-…630 IZM…1(-4)-…800 IZM…1(-4)-…1000 IZM…1(-4)-…1250 IZM…1(-4)-…1600 Notes
B N B N B N B N B N

General 1) Time for mechanical unlatching until the contacts separate +


Standards IEC/EN 60947 IEC/EN 60947 statistical average value of the arc fault time.
from 630 A to 6300 A

from 630 A to 6300 A


2) Time from mechanical unlatching until tne main contacts close.
Climatic proofing IEC/EN 60947-2-30 IEC/EN 60947-2-30 3) Time from application of the voltage until closing of the main
Ambient temperature Storage °C -40 – 70 (device with LCD-display up to 55 °C) -40 – 70 (device with LCD-display up to 55 °C) contacts. Closing delay with overexcited closing release (5 % DF):
50 ms.
Open °C -25 – 70 (device with LCD-display up to 55 °C) -25 – 70 (device with LCD-display up to 55 °C) 4) Time from application of voltage to contact separation +
statististical average value of the arc.
5) Maintenance means: exchange main contacts and arcing
Mounting position 30˚ 30˚ 30˚ 30˚ 30˚ 30˚ 30˚ 30˚
chambers

Utilization category B B B B B B B B B B
Protection type IP20, IP41 with door frame seals, IP55 with protective cover IP20, IP41 with door frame seals, IP55 with protective cover

Direction of incoming supply as required as required


Main conducting paths
Rated current = rated uninterrupted current In = Iu A 630 630 800 800 1000 1000 1250 1250 1600 1600
Rated impulse withstand voltage Uimp V AC 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000
Rated operational voltage Ue V AC 690 690 690 690 690 690 690 690 690 690
Use in IT electrical power networks up to U = 440 AC IIT kA 23 23 23 23 23 23 23 23 23 23
Use in IT power networks up to U = 690 V IIT kA IZM…-4-A(V)… without overload protection on the 4th. pole are IZM…-4-A(V)… without overload protection on the 4th. pole are not suitable for IT grids.
only for 1000 V variants not suitable for IT grids.
Overvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3
Rated insulation voltage Ui V 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Switching capacity
Rated short-circuit making capacity up to 440 V 50/60 Hz Icm kA 105 143 105 143 105 143 105 143 105 143
up to 690 V 50/60 Hz Icm kA 88 105 88 105 88 105 88 105 88 105
up to 1000 V 50/60 Hz Icm kA – – – – – – – – – –
Rated short-time withstand current 50/60 Hz t = 0.5 s Icw kA 42 65 42 65 42 65 42 65 42 65
t=1s Icw kA 42 50 42 50 42 50 42 50 42 50
t=2s Icw kA 29 35 29 35 29 35 29 35 29 35
t=3s Icw kA 24 29 24 29 24 29 24 29 24 29
t=4s Icw kA 21 25 21 25 21 25 21 25 21 25
Rated short-circuit breaking capacity Icn
IEC/EN 60947 operating sequence Icu O- up to 440 V 50/60 Hz Icu kA 50 65 50 65 50 65 50 65 50 65
t-CO up to 690 V 50/60 Hz Icu kA 42 50 42 50 42 50 42 50 42 50
up to 1000 V 50/60 Hz Icu kA – – – – – – – – – –
IEC/EN 60947 operating sequence Ics O-t- up to 440 V 50/60 Hz Ics kA 50 65 50 65 50 65 50 65 50 65
CO-t-CO up to 690 V 50/60 Hz Ics kA 42 50 42 50 42 50 42 50 42 50
up to 1000 V 50/60 Hz Ics kA – – – – – – – – – –
Operating Total opening delay1) ms 38 38 38 38 38 38 38 38 38 38
delays Closing delay2) ms 35 35 35 35 35 35 35 35 35 35
Closing delay electrical (via closing release)3) ms 80 80 80 80 80 80 80 80 80 80
Opening delay electrical ( via shunt release / undervoltage release)4) ms 73 73 73 73 73 73 73 73 73 73

Opening delay via trip electronics (non-delayed short-circuit release) ms 50 50 50 50 50 50 50 50 50 50

Lifespan mechanical, without maintenance Operations 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000
mechanical, with maintenance5) Operations 20000 20000 20000 20000 20000 20000 20000 20000 20000 20000
electrical, without maintenance Operations 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000

electrical, with maintenance5) Operations 20000 20000 20000 20000 20000 20000 20000 20000 20000 20000
1000 V version Operations – – – – – – – – – –
Maximum operating frequency 690 V version Operations/h 60 60 60 60 60 60 60 60 60 60
1000 V version Operations/h – – – – – – – – – –
Heat dissipation at rated current In with 3- Fixed mounting W 100 100 100 100 100 100 105 105 150 150
phase symmetrical load Withdrawable units W 195 195 195 195 195 195 205 205 350 350
Weight
Fixed mounting 3-pole kg 43 43 43 43 43 43 43 43 43 43
4-pole kg 50 50 50 50 50 50 50 50 50 50
Withdrawable units 3-pole kg 70 70 70 70 70 70 70 70 70 70
4-pole kg 84 84 84 84 84 84 84 84 84 84
Terminal capacities
Copper bar Fixed mounting blank mm 1 x 40 x 10 1 x 40 x 10 1 x 50 x 10 1 x 50 x 10 1 x 60 x 10 1 x 60 x 10 2 x 40 x 10 2 x 40 x 10 2 x 50 x 10 2 x 50 x 10
Black mm 1 x 40 x 10 1 x 40 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 1 x 60 x 10 2 x 40 x 10 2 x 40 x 10 2 x 50 x 10 2 x 50 x 10
Withdrawable units blank mm 1 x 40 x 10 1 x 40 x 10 1 x 50 x 10 1 x 50 x 10 1 x 60 x 10 1 x 60 x 10 2 x 40 x 10 2 x 40 x 10 2 x 50 x 10 2 x 50 x 10
Black mm 1 x 40 x 10 1 x 40 x 10 1 x 50 x 10 1 x 50 x 10 1 x 60 x 10 1 x 60 x 10 2 x 40 x 10 2 x 40 x 10 2 x 50 x 10 2 x 50 x 10
11/68 Technical Data Technical Data 11/69
Circuit-breakers Circuit-breakers
IZM...2 Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM...2, IZM...3
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
IZM…2(-4)-… IZM…3(-4)-…
IZM…2(-4)-…800 IZM…2(-4)-…1000 IZM…2(-4)-…1250 IZM…2(-4)-…1600 IZM…2(-4)-…2000 IZM…2(-4)-…2500 IZM…2(-4)-…3200 4000 5000 6300
B N H B N H B N H B N H B N H B N H B N H H H H
from 630 A to 6300 A

from 630 A to 6300 A


General
Standards IEC/EN 60947 IEC/EN 60947
Climatic proofing IEC/EN 60947-2-30 IEC/EN 60947-2-30
Ambient temperature
Storage °C -40 – 70 (device with LCD-display up to 55 °C) -40 – 70 (device with LCD-display up to 55 °C)
Open °C -25 – 70 (device with LCD-display up to 55 °C) -25 – 70 (device with LCD-display up to 55 °C)
Mounting position 30˚ 30˚ 30˚ 30˚

30˚ 30˚ 30˚ 30˚

Utilization category B B
Protection type IP20, IP41 with door frame seals, IP55 with protective cover IP20, IP41 with door frame seals, IP55 with protective cover
Direction of incoming supply as required as required
Main conducting paths
Rated current = rated uninterrupted current In = Iu A 800 800 800 1000 1000 1000 1250 1250 1250 1600 1600 1600 2000 2000 2000 2500 2500 2500 3200 3200 3200 4000 5000 6300

Rated impulse withstand voltage Uimp V AC 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000
Rated operational voltage Ue V AC 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

Use in IT electrical power networks up to U = IIT kA 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50


Use in IT power networks up to U = 690 V kA – – 50 – – 50 – – 50 – – 50 – – 50 – – 50 – – 50 50 50 50
only for 1000 V variants1)
Overvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3
Rated insulation voltage Ui V 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

Switching capacity
Rated short-circuit making capacity
up to 440 V 50/60 Hz Icm kA 121 176 220 121 176 220 121 176 220 121 176 220 121 176 220 121 176 220 121 176 220 220 220 220
up to 690 V 50/60 Hz Icm kA 105 165 187 105 165 187 105 165 187 105 165 187 105 165 187 105 165 187 105 165 187 187 187 187
up to 1000 V 50/60 Hz Icm kA – – 95 – – 95 – – 95 – – 95 – – 95 – – 95 – – 95 105 105 105
Rated short-time withstand current 50/60 Hz
t = 0.5 s Icw kA 55 80 85 55 80 85 55 80 85 55 80 85 55 80 85 55 80 85 55 80 85 85 85 100
t=1s Icw kA 55 65 80 55 65 80 55 65 80 55 65 80 55 65 80 55 65 80 55 65 80 80 80 100
t=2s Icw kA 39 46 50 39 46 50 39 46 50 39 46 50 39 46 50 39 46 50 39 46 56 56 56 70
t=3s Icw kA 32 37 40 32 37 40 32 37 40 32 37 40 32 37 40 32 37 40 32 37 50 46 46 57
t=4s Icw kA 27 32 32 27 32 32 27 32 32 27 32 32 27 32 32 27 32 32 27 32 40 40 40 50
Rated short-circuit breaking capacity Icn
IEC/EN 60947 operating sequence Icu O-t-
up to 440 V 50/60 Hz Icu kA 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 100 100 100
up to 690 V 50/60 Hz Icu kA 50 75 85 50 75 85 50 75 85 50 75 85 50 75 85 50 75 85 50 75 85 85 85 85
up to 1000 V 50/60 Hz Icu kA – – 45 – – 45 – – 45 – – 45 – – 45 – – 45 – – 45 50 50 50
IEC/EN 60947 operating sequence Ics O-t-
up to 440 V 50/60 Hz Ics kA 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 55 80 100 100 100 100
up to 690 V 50/60 Hz Ics kA 50 75 85 50 75 85 50 75 85 50 75 85 50 75 85 50 75 85 50 75 85 85 85 85
up to 1000 V 50/60 Hz Ics kA – – 45 – – 45 – – 45 – – 45 – – 45 – – 45 – – 45 50 50 50

Switching capacity 1) IZM…-4-A(V)… without overload protection on the 4th. pole are not suitable for IT grids.
11/70 Technical Data
Circuit-breakers
IZM...2 Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

IZM…2(-4)-…
IZM…2(-4)-…800 IZM…2(-4)-…1000 IZM…2(-4)-…1250
IZMB2- IZMN2- IZMH2- IZMB2- IZMN2- IZMH2- IZMB2- IZMN2- IZMH2-
…-800 …-800 …-800 …- …- …- …- …- …-
1000 1000 1000 1250 1250 1250
from 630 A to 6300 A

Operating delays
Total opening delay1) ms 73
Closing delay2) ms 100
Closing delay electrical (via closing ms 100
release)3)
Opening delay electrical ( via shunt ms 73
release / undervoltage release)4)

Opening delay via trip electronics ms 50


(non-delayed short-circuit release)
5)

Lifespan
mechanical, without maintenance Operations 10000 10000 10000 10000 10000 10000 10000 10000 10000
mechanical, with maintenance Operations 15000 15000 15000 15000 15000 15000 15000 15000 15000
electrical, without maintenance Operations 7500 7500 7500 7500 7500 7500 7500 7500 7500

electrical, with maintenance Operations 15000 15000 15000 15000 15000 15000 15000 15000 15000
1000 V version Operations > 1000 > 1000 > 1000 > 1000 > 1000 > 1000 > 1000 > 1000 > 1000
Maximum operating frequency
690 V version Operations/h 60 60 60 60 60 60 60 60 60
1000 V version Operations/h – – 20 – – 20 – – 20
Heat dissipation at rated current In
with 3-phase symmetrical load

Fixed mounting W 40 40 40 45 45 45 80 80 80
Withdrawable units W 85 85 85 95 95 95 165 165 165
Weight
Fixed mounting
3-pole kg 56 56 56 56 56 56 56 56 56
4-pole kg 67 67 67 67 67 67 67 67 67
Withdrawable units
3-pole kg 91 91 91 91 91 91 91 91 91
4-pole kg 109 109 109 109 109 109 109 109 109
Terminal capacities
Copper bar
Fixed mounting
blank mm 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10

Black mm 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10

Withdrawable units
blank mm 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10

Black mm 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10

Notes 1) Time for mechanical unlatching until the contacts separate + statistical average value of the arc
fault time.
2) Time from mechanical unlatching until tne main contacts close.
3) Time from application of the voltage until closing of the main contacts. Closing delay with over-
excited closing release (5 % DF): 50 ms.
4) Time from application of voltage to contact separation + statististical average value of the arc.
5) Exception release for &#x200C;protection of systems (XZMA): 85 ms.
6) Maintenance means: exchange main contacts and arcing chambers
Technical Data 11/71
Circuit-breakers
http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM...2, IZM...3

Circuit-breakers, switch-disconnectors
IZM…3(-4)-…
IZM…2(-4)-…1600 IZM…2(-4)-…2000 IZM…2(-4)-…2500 IZM…2(-4)-…3200 4000 5000 6300
IZMB2- IZMN2- IZMH2- IZMB2- IZMN2- IZMH2- IZMB2- IZMN2- IZMH2- IZMB2- IZMN2- IZMH2- IZMH3- IZMH3- IZMH3-
…- …- …- …- …- …- …- …- …- …- …- …- …- …- …-
1600 1600 1600 2000 2000 2000 2500 2500 2500 3200 3200 3200 4000 5000 6300

from 630 A to 6300 A


73
100
100

73

50

10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 5000 5000 5000

15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 10000 10000 10000

7500 7500 7500 7500 7500 7500 7500 7500 7500 4000 4000 4000 2000 2000 2000

15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 10000 10000 10000

> 1000 > 1000 > 1000 > 1000 > 1000 > 1000 > 1000 > 1000 > 1000 > 1000 > 1000 > 1000 > 1000 > 1000 > 1000

60 60 60 60 60 60 60 60 60 60 60 60 60 60 60
– – 20 – – 20 – – 20 – – 20 20 20 20

85 85 85 180 180 180 270 270 270 410 410 410 520 630 900
175 175 175 320 320 320 520 520 520 710 710 710 810 1050 1600

56 56 56 56 56 56 59 59 59 64 64 64 82 82 90
67 67 67 67 67 67 71 71 71 77 77 77 99 99 108

91 91 91 91 91 91 102 102 102 113 113 113 148 148 166


109 109 109 109 109 109 123 123 123 136 136 136 190 190 227

2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10 4 x 100 5 x 100 6 x 120


x 10 x 10 x 10
2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10 4 x 100 4 x 120 6 x 120
x 10 x 10 x 10

2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10 4 x 100 5 x 100 6 x 120


x 10 x 10 x 10
2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10 4 x 100 4 x 120 6 x 120
x 10 x 10 x 10
11/72 Technical Data
Switch-disconnectors
IN...1 Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

IN…1(-4)-630 IN…1(-4)-800 IN…1(-4)-1000 IN…1(-4)-1250 IN…1(-4)-1600


INB1- INN1- INB1- INN1- INB1- INN1- INB1- INN1- INB1- INN1-
…- …- …- …- …- …- …- …- …- …-
630 630 800 800 1000 1000 1250 1250 1600 1600

General
from 630 A to 6300 A

Standards IEC/EN 60947


VDE 0660
Climatic proofing IEC/EN 60947-2-30
Ambient temperature
Storage °C -40/70
Open °C -25/70
Mounting position 30˚ 30˚ 30˚ 30˚

Utilization category B
Protection type IP20, IP40 with door sealing frame, IP55 with protective cover
Direction of incoming supply as required
Main conducting paths
Rated current = rated uninterrupted current In = Iu A 630 630 800 800 1000 1000 1250 1250 1600 1600

Rated impulse withstand voltage Uimp V AC 12000


Rated operational voltage Ue V AC 690
Overvoltage category/pollution degree III/3
Rated insulation voltage Ui V 1000

Switching capacity
Rated short-circuit making capacity
up to 440 V 50/60 Hz Icm kA 105 143 105 143 105 143 105 143 105 143
up to 690 V 50/60 Hz Icm kA 88 105 88 105 88 105 88 105 88 105
up to 1000 V 50/60 Hz Icm kA –
Rated short-time withstand current 50/60 Hz
t = 0.5 s Icw kA 42 65 42 65 42 65 42 65 42 65
t=1s Icw kA 42 50 42 50 42 50 42 50 42 50
t=2s Icw kA 29 35 29 35 29 35 29 35 29 35
t=3s Icw kA 24 29 24 29 24 29 24 29 24 29
t=4s Icw kA 21 25 21 25 21 25 21 25 21 25
Operating delays
Total opening delay1) ms 73
Closing delay2) ms 80
Closing delay electrical (via closing ms 80
release)3)
Opening delay electrical ( via shunt ms 73
release / undervoltage release)4)

Lifespan
mechanical, without maintenance Operations 10000
mechanical, with maintenance5) Operations 20000
electrical, without maintenance Operations 10000
electrical, with maintenance5) Operations 20000
1000 V version Operations –
Maximum operating frequency
690 V version Operations/h 60
1000 V version Operations/h –
Heat dissipation at rated current In with 3-
phase symmetrical load
Fixed mounting W 100 105 170
Withdrawable units W 195 205 350

Notas 1) Time for mechanical unlatching until contact separation + statistical average value of the arc fault quench time.
2) Time for mechanical untlaching until closing of the main contacts.
3) Time from application of the voltage until closing of the main contacts. Closing delay with overexcited closing release (5 % DF): 50 ms.
4) Time from application of voltage to contact separation + statististical average value of the arc.
5) Maintenance means: exchange main contacts and arcing chambers
Technical Data 11/73
Switch-disconnectors
http://catalog.moeller.net Moeller HPL0211-2007/2008 IN...1, IN...2, IN...3

Circuit-breakers, switch-disconnectors
IN…1(-4)-630 IN…1(-4)-800 IN…1(-4)-1000 IN…1(-4)-1250 IN…1(-4)-1600

Weight
Fixed mounting 3-pole kg 43 43 43 43 43
4-pole kg 50 50 50 50 50
Withdrawable units 3-pole kg 70 70 70 70 70

from 630 A to 6300 A


4-pole kg 84 84 84 84 84
Terminal capacities
Copper bar
Fixed mounting
blank mm 1 x 40 x 10 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10
Black mm 1 x 40 x 10 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10
Withdrawable units
blank mm 1 x 40 x 10 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10
Black mm 1 x 40 x 10 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10

IN…2(-4)-800 IN…2(-4)- IN…2(-4)- IN…2(-4)- IN…2(-4)- IN…2(-4)- IN…2(-4)-

Weight
Fixed mounting
3-pole kg 56 56 56 56 56 59 64
4-pole kg 67 67 67 67 67 71 77
Withdrawable units
3-pole kg 91 91 91 91 91 102 113
4-pole kg 109 109 109 109 109 123 136
Terminal capacities
Copper bar
Fixed mounting
blank mm 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10
Black mm 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10

Withdrawable units
blank mm 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10
Black mm 1 x 50 x 10 1 x 60 x 10 2 x 40 x 10 2 x 50 x 10 3 x 50 x 10 2 x 100 x 10 3 x 100 x 10

IN…3(-4)-4000 IN…3(-4)-5000 IN…3(-4)-6300

Weight
Fixed mounting
3-pole kg 82 82 90
4-pole kg 99 99 108
Withdrawable units
3-pole kg 148 148 166
4-pole kg 190 190 227
Terminal capacities
Copper bar
Fixed mounting
blank mm 4 x 100 x 10 5 x 100 x 10 6 x 120 x 10
Black mm 4 x 100 x 10 4 x 120 x 10 6 x 120 x 10
Withdrawable units
blank mm 4 x 100 x 10 6 x 100 x 10 6 x 120 x 10
Black mm 4 x 100 x 10 4 x 120 x 10 6 x 120 x 10
11/74 Technical Data Technical Data 11/75
Switch-disconnectors Switch-disconnectors
IN...2 Moeller HPL0211-2007/2008 http://catalog.moeller.net http://catalog.moeller.net Moeller HPL0211-2007/2008 IN...2, IN...3
Circuit-breakers, switch-disconnectors

Circuit-breakers, switch-disconnectors
IN…2(-4)-800 IN…2(-4)-1000 IN…2(-4)-1250 IN…2(-4)-1600 IN…2(-4)-2000 IN…2(-4)-2500 IN…2(-4)-3200 IN…3(-4)- IN…3(-4)- IN…3(-4)-
4000 5000 6300
INB2- INN2- INH2- INB2- INN2- INH2- INB2- INN2- INH2- INB2- INN2- INH2- INB2- INN2- INH2- INB2- INN2- INH2- INB2- INN2- INH2- INH3-…- INH3-…- INH3-…-
…-800 …-800 …-800 …- …- …- …- …- …- …- …- …- …- …- …- …- …- …- …- …- …- 4000 5000 6300
1000 1000 1000 1250 1250 1250 1600 1600 1600 2000 2000 2000 2500 2500 2500 3200 3200 3200
from 630 A to 6300 A

from 630 A to 6300 A


General
Standards IEC/EN 60947VDE 0660 IEC/EN 60947VDE 0660
Climatic proofing IEC/EN 60947-2-30 IEC/EN 60947-2-30
Ambient temperature
Storage °C -40/70 -40/70
Open °C -25/70 -25/70
Mounting position 30˚ 30˚ 30˚ 30˚ 30˚ 30˚ 30˚ 30˚

Utilization category B B
Protection type IP20, IP40 with door sealing frame, IP55 with protective cover IP20, IP40 with door sealing frame, IP55 with protective cover
Direction of incoming supply as required as required
Main conducting paths
Rated current = rated uninterrupted current In = Iu A 800 800 800 1000 1000 1000 1250 1250 1250 1600 1600 1600 2000 2000 2000 2500 2500 2500 3200 3200 3200 4000 5000 6300
Rated impulse withstand voltage Uimp V AC 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000 12000
Rated operational voltage Ue V AC 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690 690
1000 1000 1000 1000 1000 1000 1000 1000 1000
Overvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3
Rated insulation voltage Ui V 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Switching capacity
Rated short-circuit making capacity
up to 440 V 50/60 Hz Icm kA 121 176 220 121 176 220 121 176 220 121 176 220 121 176 220 121 176 220 121 176 220 220 220 220
up to 690 V 50/60 Hz Icm kA 105 165 187 105 165 187 105 165 187 105 165 187 105 165 187 105 165 187 105 165 187 187 187 187
up to 1000 V 50/60 Hz Icm kA – – 95 – – 95 – – 95 – – 95 – – 95 – – 95 – – 95 105 105 105
Rated short-time withstand current 50/60 Hz
t = 0.5 s Icw kA 55 80 85 55 80 85 55 80 85 55 80 85 55 85 85 55 80 85 55 80 85 85 85 100
t=1s Icw kA 55 65 80 55 65 80 55 65 80 55 65 80 55 65 80 55 65 80 55 65 80 80 80 100
t=2s Icw kA 39 46 50 39 46 50 39 46 50 39 46 50 39 46 50 39 46 50 39 46 56 56 56 70
t=3s Icw kA 32 37 40 32 37 40 32 37 40 32 37 40 32 37 40 32 37 40 32 37 50 50 46 57
t=4s Icw kA 27 32 32 27 32 32 27 32 32 27 32 32 27 32 32 27 32 32 27 32 40 40 40 50
Operating delays
Total opening delay1) ms 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34 34
Closing delay2) ms 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
Closing delay electrical (via closing release)3) ms 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80

Opening delay electrical ( via shunt release / ms 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73 73


undervoltage release)4)
Lifespan
mechanical, without maintenance Operations 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 5000 5000 5000
mechanical, with maintenance5) Operations 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 10000 10000 10000
electrical, without maintenance Operations 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 7500 4000 4000 4000 2000 2000 2000
electrical, with maintenance5) Operations 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 15000 10000 10000 10000
1000 V version Operations – – 1000 – – 1000 – – 1000 – – 1000 – – 1000 – – 1000 – – 1000 1000 1000 1000
Maximum operating frequency
690 V version Operations/h 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60
1000 V version Operations/h – – 20 – – 20 – – 20 – – 20 – – 20 – – 20 – – 20 20 20 20
Heat dissipation at rated current In with 3-phase
symmetrical load
Fixed mounting W 40 40 40 40 40 40 80 80 80 85 85 85 180 180 180 270 270 270 410 410 410 520 630 900
Withdrawable units W 95 95 95 95 95 95 165 165 165 175 175 175 320 320 320 520 520 520 710 710 710 810 1050 1600

Notes Switching capacity in N pole = 60 %


1) Time for mechanical unlatching until contact separation + statistical average value of the arc fault quench time.
2) Time for mechanical untlaching until closing of the main contacts.
3) Time from application of the voltage until closing of the main contacts. Closing delay with overexcited closing release (5 % DF): 50 ms.
4) Time from application of voltage to contact separation + statististical average value of the arc.
5) Maintenance means: exchange main contacts and arcing chambers
11/76 Technical Data
Control unit
IZM-... Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

IZM…-A… IZM…-V… IZM…-U… IZM…-D…


(XZMA) IZM…1/2… IZM…3… ZM…1/2… IZM…3… IZM…1/2… IZM…3…

Control units
from 630 A to 6300 A

Overload protection L
Setting range Ir A 0.5 – 1.0 x In 0.4 – 1.0 x In 0.4 – 1.0 x In 0.4 – 1.0 x In 0.4 – 1.0 x In 0.4 – 1.0 x In 0.4 – 1.0 x In
Delay time with
6 x Ir tr s 10 10 10 – – – –
6 x Ir with time delay setting tr s 2 – 30 2 – 30 2 – 30 2 – 30
to overcome current peaks to
J
6 x Ir with time delay to tr s 1…5 1…5 1…5 1…5
overcome current peaks set to
I4 t
Phase-failure sensitivity only with tsd = 20 (motor only with tsd = 20 (motor ON/OFF via Menu/Comm
protection) ms protection) ms
Thermal memory can be switched on/off ON/OFF via Menu/Comm

Tolerance Protective function to IEC/EN 60947 Protective function conform to IEC/EN 60947,
current display F 5 %
measurement function basic values F 1 %
measurement function derived values F 3 %
ZSI function with option “IZM-XEM-ZSI” with option “IZM-XEM-ZSI”
Short-time delayed short-circuit protection

Setting range Isd A 1.25 – 12 x In 1.25 – 12 x In 1.25 x In – 0.8 x Icw (max. 0.8
x Icw)
Delay time tsd ms 0, 20 (motor protection), 100, 20 (motor protection), 100, 20, 100, 200, 300, 400, 500,
200, 300, 400 200, 300, 400, OFF 1000, 2000, 3000, 4000, OFF
Jsd with 12 x In tsd ms 100, 200, 300, 400, OFF 100, 200, 300, 400, OFF
Non-delayed short-circuit protection I
Can be de-activated OFF2) OFF2) OFF via Menu/ OFF via Menu/
Comm2) Comm2)

Adjustment range Ii A 2 – 8 x In f 20 x In (max. 50 kA) 1.5 x In … 0.8 x Ics (max. 0.8 1.5 x In … 0.8 x Ics (max. 0.8
tolerance: g 0 … + 20% x Ics), OFF: Ics = Icw (0.5 s) x Ics), OFF: Ics = Icw (0.5 s)
N-conductor protection N
Setting range 0 %, 100 % of In, can be 0 %, 50 %, 100 % of In, can be Via menu/COMM 50 % to 200
switched on/off with slide switched on/off with slide % of In
switch switch
Earth-fault protection G
Option for fixed mounting Module can be retrofitted Module can be retrofitted

Setting range of the response Ig A OFF, 100, OFF, 400, OFF, 100, OFF, 400, 100–1200 400–1200
current Ig for the trip 300, 600, 600, 800, 300, 600, 600, 800,
900, 1200 1000, 1200 900, 1200 1000, 1200
Setting range of the response Ig A 100, 300, 400, 600, 100–1200 400–1200
current Ig for the alarm 600, 900, 800, 1000,
1200 1200
Delay time tg ms 100, 200, 300, 400, 500 100, 200, 300, 400, 500 100, 200, 300, 400, 500
Delay time with I2t tg ms 100, 200, 300, 400, 500 100, 200, 300, 400, 500
Tripping function can be switched on/off can be switched on/off ON/OFF via Menu/Comm

Alarm function – – – – ON/OFF via Menu/Comm

ZSI function with option “IZM-XEM-ZSI” with option “IZM-XEM-ZSI”


Acquisition of earth-fault current – Yes Yes yes, can be selected yes, can be selected
through summation current
transformation with built-in or
external transducer for the N
conductor

Acquisition of earth-fault current – – – yes, can be selected yes, can be selected


through external transducer for
the protective conductor

Notes 1) Control unit XZMR receives a plus option “+IZM-XZMR”. All settings only possible via communication interfaces (via Comm),
i.e. a) with parameter assignment module IZM-XEM-PG(E) or b) via PROFIBUS.
2) IZM…-4-A(V)… without overload protection on the 4th. pole are not suitable for IT grids.
Technical Data 11/77
Auxiliary contacts
http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM-XHI...

Circuit-breakers, switch-disconnectors
IZM-XHI... standard IZM-XHIB ready to IZM-XHIA trip- Position signalling
auxiliary contact switch on message indicating auxiliary switch IZM-XHIAV...
contact

Auxiliary contacts

from 630 A to 6300 A


Rated insulation voltage
AC Ui V AC 500 – – 440
DC Ui V DC 500 – – 250

Rated operational voltage Ue V AC/DC 500 220 230 440


V AC/DC 220 220 220 250

Rated impulse withstand voltage Uimp kV 4 – – 4

Short-circuit protection

max. fuse A gL 10 2 6 8
Fuseless Type FAZ-C10 – – FAZ-C6

Rated breaking capacity


AC12
24 230 V A 10 – – –
110 … 127 V A 10 0.14 – 13
220/230 V A 10 0.1 6 13
400 V A 10 – – –
500 V A 10 – – –
AC-15
24 230 V A 4 – – –
110/127 V A 4 – – 5
220/230 V A 4 – – 4
400 V A 3 – – 3
440 V A – – – 3
500 V A 2 – – –
DC12
24 V A 10 0.2 6 13
30 V I A – – – 10
48 V A 8 – – 2.5
110 V A 3.5 – 0.4 0.8
220 V A 1 0.1 0.2 0.6
DC-13
24 V A 8 – – 3
48 V A 4 – – –
100 V A 1.2 – – –
220/250 V A 0.4 – – 0.1
400 V A – – – –
DC – -
24 V A 10 – – –
48 V A 4 – – –
110 V A 1.2 – – –
220 V A 0.4 – – –
Terminal capacities
Flexible without ferrule mm2 2 x (0.5 – 2.5) 2 x (0.5 – 2.5) 2 x (0.5 – 2.5) 2 x (0.5 – 2.5)

Flexible with ferrule mm2 2 x (0.5 – 1.5) 2 x (0.5 – 1.5) 2 x (0.5 – 1.5) 2 x (0.5 – 1.5)

Notes Terminal capacity:


Standard spring-loaded terminal
11/78 Technical Data
Voltage release, motor operator
IZM-X... Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Voltage releases
Closing release +IZM-XA(1) shunt Undervoltage
+IZM-XE/A, IZM-XE/ release release IZM-XU(V)
A
100 % duty factor 5 % duty factor 100 % duty factor delayed t =....etc non-delayed and t =
200 ms
from 630 A to 6300 A

Voltage releases
Rated control voltage

AC 50/60 Hz Us V 110, 230 110 … 127, 208 … 110, 230 110 … 127, 208 … 110 … 127, 208 … 240,
240 240, 380 … 415 380 … 415
DC Us V 24, 30, 48, 60, 110, 24, 48, 110 … 125, 24, 30, 48, 60, 110, 48, 110 … 125, 220 24, 30, 48, 60, 110 …
220 220 … 250 220 … 250 125, 220 … 250
Power consumption
AC, 50/60 Hz VA 15 15 15 5 (pick-up 200) 5 (pick-up 200)
DC W 15 15 15 5 (pick-up 200) 5 (pick-up 200)
Circuit-breaker response ms 80 50 73 80 non-delayed, 80 non-delayed,
time otherwise according otherwise according to
to delay time delay time

Minimum command time ms 60 25 60 – –

Operating range
Drop-out voltage x Us 0.35 – 0.7 0.35 – 0.7
Pick-up voltage x Us 0.85 – 1.1 0.85 – 1.1 0.85 – 1.1 0.85 – 1.1 0.85 – 1.1
Enhanced battery operation
range
Pick-up voltage x Us 0.7 – 1.26 0.7 – 1.26 0.7 – 1.26 0.85 – 1.26 0.85 – 1.26
Short-circuit protection

DIAZED fuses 1 A TDz (slow) 1 A TDz (slow) 1 A TDz (slow) 1 A TDz (slow) 1 A TDz (slow)
(utilization category gL)
Miniature circuit- W 1 A600 1 A600 1 A600 1 A600 1 A600
breaker with
characteristic C
Terminal capacities
Flexible without ferrule mm2 2 x (0.5 – 2.5) 2 x (0.5 – 2.5) 2 x (0.5 – 2.5) 2 x (0.5 – 2.5) 2 x (0.5 – 2.5)

Flexible with ferrule mm2 2 x (0.5 – 1.5) 2 x (0.5 – 1.5) 2 x (0.5 – 1.5) 2 x (0.5 – 1.5) 2 x (0.5 – 1.5)

Notes Terminal capacity:


Standard spring-loaded terminal
Rated power undervoltage release:
AC pickup power 200 VA or DC 200 W

IZM-XM24-30DC IZM-XM48-60DC IZM-XM110AC/DC IZM-XM230AC/


220DC

Motor operators
Rated control voltage
AC 50/60 Hz Us V 110 … 125 208 … 250
DC Us V 24 … 30 48 … 60 110 … 127 220 … 225
Operating range x Us V 0.85 – 1.1 0.85 – 1.1 0.85 – 1.1 0.85 – 1.1
Extended operating range for battery operation 24 V x Us V 0.7 – 1.26 0.7 – 1.26 0.7 – 1.26 0.7 – 1.26
to 220 V DC
Necessary time requirement for charging of the s 10 10 10 10
spring-operated stored energy mechanism with 1 x
Starting current A 19.3 (24 V DC) 7.6 (48 V DC) 8.8 (110 V AC) 3.9 (220 V AC)
24.5 (30 V DC) 11.6 (60 V DC) 7 (110 V DC) 2.6 (220 V DC)
Power consumption
AC 50/60 Hz VA 110 110 110 110
DC W 110 110 110 110
Short-circuit protection
DIAZED fuses (utilization category gL) 2 A TDz (slow) 2 A TDz (slow) 2 A TDz (slow) 2 A TDz (slow)
Miniature circuit-breaker with characteristic W 2A 2A 1 A600 1 A600
C
Terminal capacities
Flexible without ferrule mm2 2 x (0.5 – 2.5) 2 x (0.5 – 2.5) 2 x (0.5 – 2.5) 2 x (0.5 – 2.5)
Flexible with ferrule mm2 2 x (0.5 – 1.5) 2 x (0.5 – 1.5) 2 x (0.5 – 1.5) 2 x (0.5 – 1.5)
Notes Terminal capacity:
Standard spring-loaded terminal
Technical data 11/79
Current consumption, safety clearances
http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM..., IN...

Circuit-breakers, switch-disconnectors
Maximum continuous cur- Max. starting current Part no.
rent
I
mA A

Current consumption for the communication module

from 630 A to 6300 A


Trip XZMU 120 2 IZM-XZMU
Trip XZMR 120 2 IZM-XZMR
Trip XZMD 170 2 IZM-XZMD
Measuring function XMH 120 0.12 +IZM-XMH
Breaker Status Sensor XBSS 40 0.11 +IZM-XBSS
Communication module XCOM-DP 125 0.28 +IZM-XCOM-DP
ZSI module 50 0.125 IZM-XEM-ZSI
Digital output module with rotary coding switch, relay outputs 180 0.125 IZM-XEM-6DO-R
Digital output module, configurable, relay outputs 180 0.125 IZM-XEM-6PDO-R
Analog output module 110 0.8 IZM-XEM-4AO
Digital input module 30 0.125 IZM-XEM-6DI
PG (E) parameter assignment module 250 0.35 IZM-XEM-PG

Safety clearance to live parts IZM...1-..., IN...1-... IZM...2-..., IN...2-... IZM...3-..., IN...3-...
Rated operational voltage V AC 440 690 440 690 1000 440 690 1000

Fixed mounted
above control circuit plug mm 150 300 250 600 430 75 500 430
Side (each) mm 20 50 50 100 100 20 100 100
Rear mm 20 125 20 140 125 20 125 125
Withdrawable units
without arc chute cover
above control circuit plug mm 150 300 250 600 350 50 500 350
Side (each) mm 20 50 50 100 100 20 100 100
Rear mm 14 14 14 30 14 14 14 14
with arc chute cover
above control circuit plug mm 14 14 14 14 – 14 14 –
Side (each) mm 100 100 50 225 – 50 200 –
Rear mm 14 14 14 14 – 14 14 –

Safety clearance to earthed parts IZM...1-..., IN...1-... IZM...2-..., IN...2-... IZM...3-..., IN...3-...
Rated operational voltage V AC 440 690 440 690 1000 440 690 1000

Fixed mounted
above control circuit plug mm 751) 751) 751) 751) 180 751) 751) 180
Side (each) mm 0 0 0 0 0 0 0 0
Rear mm 0 0 0 0 0 0 0 0
Withdrawable units
without arc chute cover
above control circuit plug mm 501) 501) 501) 501) 100 501) 501) 100
Side (each) mm 0 0 0 0 0 0 0 0
Rear mm 0 0 0 0 0 0 0 0
with arc chute cover
above control circuit plug mm 0 0 0 0 0 0 –
Side (each) mm 02) 02) 02) 02) 02) 02) –
Rear mm 0 0 0 0 0 0 –

Notes 1) Value for plates, 0 mm for supports and grills


2) 40 mm (IZM...2-..., IN...2-... 70 mm) for plates, that cover side apertures in the drawer area. All safety clearances above the switch relate
to the upper edge of the control circuit plug - not to the upper edge of the arcing chamber! See dimensional drawings.
11/80 Dimensions
External dimensions, door cut-out
IZM..., IN... Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Circuit-breakers Switch-disconnectors

Fxed mounting Withdrawable units


a b c1) a b c1)
IZM…1-…, IN…1-… 320 434 357 320 460 471
from 630 A to 6300 A

IZM…2-…, IN…2-… 460 434 357 460 460 471

b
IZM…3-…, IN…3-… 704 434 357 704 460 471
IZM…1-4…, IN…1-4… 410 434 357 410 460 471
IZM…2-4…, IN…2-4… 590 434 357 590 460 471
IZM…3-4…, IN…3-4… 914 434 357 914 460 471
a c

1) including dimensions for horizontal connection.


Height “b” up to the control circuit plug upper edge as screw termination for circuit-
breaker/switch-disconnector with UeF690 V. Deviations for Ue=1000 V see detail
drawings.

Door cut-out for operating panel Door cut-out with edge protection
When door seal is used Cut-out after mounting the edge protection
314 295
300
120 40

o 5.5 c

340
R5 R5
185
140

240
o 5.5 b
350
140

175

180

40 120

o 5.5
65
11.5

a 12 d
21
40

a Mounting area
b Centre of IZM/IN operating panel
c 8 mounting holes for door seal
d 3 mounting holes for door interlock
Dimensions 11/81
Fixed mounting and optional terminations, 3 and 4 pole
http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM…1-…, IN…1-…, IZM1-XAT…

Circuit-breakers, switch-disconnectors
Standard version for horizontal connection Optional terminations
Front connection (single
hole fitting)
IZM1-XAT1F...
i o 13.5 k
60.5

from 630 A to 6300 A


a h
33.5

35
e d
c

451

421
6

541.5
275

327.5
439.5
434

11
c 47
k

35
26
123.5

82 55 55 55 55

76
60 90 90 90

270 15 20 Front connection (double-hole IZM1-XATF...


300 10 5.5 fitting) according to DIN 43673
130 k

40
390 o 13.5
150 45

80
f
210 106

541
90 90 90 60 230 127
6
55
c

421
o 13.5
35

34
k k

80
g

40
c c 47
4xo9 82

14
55 55 55 55
60 90 90 90

139 58 Vertical connection IZM1-XATV...


320
35
410
k
c
60

o 13.5
30
a

267.5

c
127.5

b
275

60 90 90 90
113.5
150
a

128.5

60 90 90 90

Rated current Iu a b c a Mounting area for removal of the arcing chambers


c Grooves (4 mm wide, 5 mm deep) for supporting phase isolation plates in the system
up to 1000 A 10 10 10 d Control circuit plug with screw terminals
1250 – 1600 A 15 15 15 e Control circuit plug with spring-loaded terminal
f Dimension for internal area of closed switchgear system door
g Attachment points for circuit-breaker mounting in the system
h Interlock in OFF (optional accessories)
i Key operation (optional accessories)
k Connection area
When front connections are used, a partition between the busbar and arcing space must be fitted on the system side
11/82 Dimensions
Withdrawable mounting and optional terminations, 3 and 4 pole
IZM…1-…, IN…1-…, IZM1-XAT Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Standard version for horizontal connection Optional terminations


Front connection (single IZM1-XAT1F...-AV
hole fitting)
382.5 o 13.5 k
367.5
e d
from 630 A to 6300 A

35
mn
o

373
c

403
6

327.5
275

35
465.5

c
460

o14
k

26
123.5

j 55 55 55 55

11
76
40 c 62.5
15 90 90 90
j j 169.5
31
20

13 30 27 220 45
210 55 42 58
f Front connection (double-hole IZM1-XATF...-AV
fitting) according to DIN 43673
270 88.5
300 121.5 o 13.5 k
320 140.5

40
80
493
55 55 55 55 6
o 13.5

373
k
38

14
34

80

40
62.5
k
c 169.5 55 55 55 55
15 90 90 90

Vertical connection IZM1-XATV...-AV


139 68
38
270 25 k
320
60

410
30

c
267.5

350
127.5

260
o 13.5
c

150 b

165 15 90 90 90
a

Flanged connection IZM1-XATA...-AV


o M12
287
275

33
150
a

59
69

j
26

15 j c
282.5
59

55 90 90 90
142.5

55 55 55 55
14 15 90 90 90
121

Rated current Iu a b c c Grooves (4 mm wide, 5 mm deep) for supporting phase isolation plates in the system
d Control circuit plug with screw terminals
up to 1000 A 10 10 10 e Control circuit plug with spring-loaded terminal
1250 – 1600 A 15 15 15 f Dimension for internal area of closed switchgear system door
j Fixing holes, o 10 mm
k Connection area
m IZM in connected position
n IZM in test position
o IZM in disconnected position
When front connections are used, a partition between the busbar and arcing space must be fitted on the system side
Dimensions 11/83
Withdrawable mounting and optional terminations, 3 and 4 pole
http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM…2-…, IN…2-…, IZM2-XAT

Circuit-breakers, switch-disconnectors
Standard version for horizontal connection Optional terminations
Front connection (single hole IZM2-XAT1F...
fitting)
a o 13.5 k

from 630 A to 6300 A


35
e d

421
451
6
c

541.5
275
c

327.5
451.5
435.5
434

11

35
26
47 40 k
123.5

90 90

76
c 90 90
82 90 130 130 130
10 20
Front connection (double-hole fitting) according to DIN 43673
270 85 5.5
o 13.5 k

40
440 45

80
570 130

150
f
210 106 c
130 130 130 90 127
230

421
6

541
90 30
30

34
35

80
k

40
k

14
c 47 40
o 13.5
g g 82 90 90 90 90
4xo9
90 130 130 130

Vertical connection
35
139 128
30

k
30

460
c
590
o 13.5
290

98
134.5

c 113.5 b
a

128.5 90 130 130 130


275
a
150

90 130 130 130

a Mounting area for removal of the arcing chambers


Rated current Iu a b c At Ue = 1000 V 175 mm is required, in order to remove the arcing chamber.
up to 2000 A 10 10 10 c Grooves (4 mm wide, 5 mm deep) for supporting phase isolation plates in the system
d Control circuit plug with screw terminals
2500 A 15 15 20
e Control circuit plug with spring-loaded terminal
3200 A 30 30 20 f Dimension for internal area of closed switchgear system door
g Attachment points for circuit-breaker mounting in the system
k Connection area
l Circuit-breaker upper edge - 1000 V AC version only
When front connections are used, a partition between the busbar and arcing space must be fitted on the
system side
11/84 Dimensions
Withdrawable mounting and optional terminations, 3 and 4 pole
IZM…2-…, IN…2-…, IZM2-XAT Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Standard version for horizontal connection Optional terminations


Front connection (single holle IZM2-XAT1F...-AV
fitting)
382.5 o 13.5 k
367.5
from 630 A to 6300 A

40.5

35
c
l m n
d 6

373
e

403
o

35
26
11
275

k
465.5

62.5 40
460

327.5
517
c 45
o14
169.5 90 90 90 90
j
123.5

55 130 130 130

76
Front connection (double-hole IZM2-XATF...-AV
40

j 270 40
j 27 220 45 fitting) according to DIN 43673
f
350 55 42 58
o 13.5 k

40
480 88.5

80
121.5
31
20

140.5 c
30 30

373
6

493
38

o 13.5
k

80

40
14
k
34

c 62.5 40
169.5 45
90 90 90 90
55 130 130 130

Vertical connection IZM2-XATV...-AV


139 138
38
270 95
30
30

460
590 c
k
290

100

530
135

400

157
172 b
55 45 130 130 130
a

Flanged connection IZM2-XATA...-AV


287
275
a

o M12
150

33
69

j
59

j
90 90 90 90
282.5
26

55 45 130 130 130 c


59
142.5

121
90 40
45 130 130 130

At Ue = 1000 V 175 mm is required, in order to remove the arcing chamber.


Rated current Iu a b c c Grooves (4 mm wide, 5 mm deep) for supporting phase isolation plates in the system
up to 2000 A 10 10 10 d Control circuit plug with screw terminals
e Control circuit plug with spring-loaded terminal
2500 A 15 15 20
f Dimension for internal area of closed switchgear system door
3200 A 30 30 20 j Fixing holes, o 10 mm
k Connection area
l Circuit-breaker upper edge - 1000 V AC version only
m IZM in connected position
n IZM in test position
o IZM in disconnected position
When front connections are used, a partition between the busbar and arcing space must be fitted on the
system side
Dimensions 11/85
Fixed mounted, 3 and 4 pole
http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM…3-…, IN…3-…

Circuit-breakers, switch-disconnectors
Standard version horizontal connection F 6300 A

a
l

from 630 A to 6300 A


ed

30
541.5
c

327.5
275

451.5
439
434

275
150
123.5

30

76
270 205 12 20
680 5.5
890 130

35 150 45 f
210 106
210 210 210 130
230 127
30 160 15
35

g o 13.5 g
4xo9

139 248
704
914

130 210 210 210 130

a Mounting area for removal of the arcing chambers


At Ue = 1000 V 175 mm is required, in order to remove the arcing chamber.
c Grooves (4 mm wide, 5 mm deep) for supporting phase isolation plates in the system
d Control circuit plug with screw terminals
e Control circuit plug with spring-loaded terminal
f Dimension for internal area of closed switchgear system door
g Attachment points for circuit-breaker mounting in the system
k Connection area
l Circuit-breaker upper edge - 1000 V AC version only
When front connections are used, a partition between the busbar and arcing space must be fitted on the system side
11/86 Dimensions
Optional terminations
IZM3-XAT… Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Optional terminations

Front connection (single hole fitting) IZM3-XATF... F 4000 A


o 13.5 k
from 630 A to 6300 A

35
c

421
451

35
26
k
11

20 50 50
47 160 160 160 160
82 130 210 210 210

Front connection (double hole fitting) IZM3-XATF... F 4000 A


k

40
o 13.5

80
c
541

421
6
34

80

k
40
14

47 50 50
20 160 160 160 160
82 130 210 210 210

Vertical connection IZM3-XATV... F 5000 A


k
30
15

c
o 13.5
330.5

120
94.5

107 10
40 20
142 85 210 210 210
162
Dimensions 11/87
Optional terminations
http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM…3-…, IN…3-…

Circuit-breakers, switch-disconnectors
Standard version horizontal connection F 5000 A

382.5
367.5
40.5

from 630 A to 6300 A


e d l m n
o

30

327.5
c

517
275

460
461

466.5

275

30
o14

150
123.5
j

76
j j

20
40
31
270 160 57 27 220 45
f
590 42 58
800 88.5
121.5
140.5
30 30
38

o 13.5
k

139 260
270 217
704
914

840
630
287
69

160 160 160 160

57 85 210 210 210

c Grooves (4 mm wide, 5 mm deep) for supporting phase isolation plates in the system
Rated current Iu a b d Control circuit plug with screw terminals
4000 A 40 210 e Control circuit plug with spring-loaded terminal
5000 A 40 210 f Dimension for internal area of closed switchgear system door
j Fixing holes, o 10 mm
6300 A 5 245 k Connection area
l Circuit-breaker upper edge - 1000 V AC version only
m IZM in connected position
n IZM in test position
o IZM in disconnected position
When front connections are used, a partition between the busbar and arcing space must be fitted on
the system side
11/88 Dimensions
Optional terminations
IZM3-XAT… Moeller HPL0211-2007/2008 http://catalog.moeller.net
Circuit-breakers, switch-disconnectors

Optional terminations

Front connection (single holle fitting) IZM3-XAT1F...-AV F 4000 A


o 13.5 k
from 630 A to 6300 A

35
403

373
6

k
11

35
26
20 62.5 50 50
169.5 160 160 160 160
85 210 210 210
590
57 800

Front connection (double hole fitting) IZM3-XATF...-AV F 4000 A


k

40
o 13.5

80
493

6 373
80

40
14
34

20 62.5 50 50 k
169.5 160 160 160 160
85 210 210 210
590
57 800

Vertical connection IZM3-XATV...-AV F 6300 A


38

k
30

o 13.5
330.5

124.5
94.5

24 10
177 20
197 a b b 210
57 590
704
800
914

Flanged connection IZM3-XATA...-AV F 4000 A


o M12
26
59

282.5
59
142.5
33

5 30
121 160 160 160 160
57 85 210 210 210
590
704
800
914
Dimensions 11/89
Measuring transformers, voltage releases
http://catalog.moeller.net Moeller HPL0211-2007/2008 IZM1, IZM2, IZM3

Circuit-breakers, switch-disconnectors
Measurement transformer for N-conductor protection and earth-fault
protection
IZM1-XW...
o 13.5

8.9
40 22
81
97
44

from 630 A to 6300 A


130

170
91

68
24

51

36
60
70

55 15 83

83 41
97

IZM2-XW...
o 13.5
44

115
131
54
65.5
130
91

68

170
24

51

88
95
90 3 x 10
113
30 30 50.5
119
119 131

IZM3-XW...
o 13.5 161
44

130
91

68

170
24

51

107
123
45

31
3

30 30 30 3 x 10 160
160 52 184
184 123

Voltage transformers
for IZM with measuring function
for mounting on 35 mm top-hat rail
125 g1

260 g3 87 g2