Circuit-Breaker Switchgear Type NXAIR,

NXAIR M and NXAIR P, up to 24 kV, Air-Insulated


Medium-Voltage Switchgear

Catalog HA 25.71 2010

Answers for energy.


R-HA25-338 tif
Application
Industry

R-HA25-340.tif

Application R-HA25-339.tif

Public power
supply system

NXAIR switchgear
R-HA25-341.tif

Application
Industry

2 Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010
Contents

Circuit-Breaker Application Page

Switchgear Types
Typical uses, classication
4
5

Type NXAIR, NXAIR M Requirements


Customer benets and features 6

and NXAIR P, up to Technical data


Electrical data, dimensions 7 to 9
24 kV, Air-Insulated Room planning 10

Product range
Medium-Voltage Switchgear NXAIR 11 and 12
NXAIR M 13 and 14
Catalog HA 25.71 2010 NXAIR P 15 and 16

Invalid: Catalog HA 25.71 2007 Design


Basic panel design,
operation, compartments 17 to 20

Components
Vacuum circuit-breaker 21
Other switching devices 22
Current transformers, post insulators 23
Low-voltage equipment 24

Standards
Standards, specications, guidelines 25 and 26

The products and systems described in this catalog are


manufactured and sold according to a certied quality
and environmental management system (acc. to ISO 9001
and ISO 14001).
(DQS Certicate Reg. No. DQS 003473 QM UM).
The certicate is accepted in all IQNet countries.

Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010 3
Application
Types

R-HA25-344 tif

NXAIR P panel
Maximum values
17.5 kV / 50 kA / 4000 A
R-HA25-343 tif

NXAIR M panel
R-HA25-342 tif

Maximum values
24 kV / 25 kA / 2500 A

NXAIR panel
Maximum values
17.5 kV / 31.5 kA / 2500 A

4 Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010
Application
Typical uses Classication

Circuit-breaker switchgear NXAIR, NXAIR M and NXAIR P is NXAIR, NXAIR M and NXAIR P switchgear corresponds to
factory-assembled, type-tested, metal-enclosed and metal-clad the following classications according to IEC 62271-200 or
switchgear for indoor installation according to IEC 62271-200 / VDE 0671-200.
VDE 0671-200 (former IEC 60298 / VDE 0670-6).

Loss of service continuity category and partition class Loss of service continuity category and partition class
Loss of service continuity category: LSC 2B (metal-clad) Loss of service continuity LSC 2B (metal-clad)
Partition class: PM (metallic partition) category
Internal arc classication: IAC A FLR, Partition class PM (metallic partition)
Isc 50 kA, t = 1 s Accessibility to compartments
arc duration Busbar compartment Tool-based
Switching device Interlock-controlled
NXAIR, NXAIR M and NXAIR P circuit-breaker switchgear is used
compartment
in transformer and switching substations, mainly at the primary Connection compartment Interlock-controlled or tool-based
distribution level, e.g.:
Internal arc classications
The following internal arc
Application classications are fullled:
Public power supply IAC A FLR, Isc, t
Power supply companies. IAC = Internal arc classication
A = 300 mm distance of indicators
Application for test (installation in closed
Industry electrical service location)
Power stations F = Front arrangement of indicators
Cement industry for test
Automobile industry L = Lateral arrangement of indicators
Iron and steel works for test
Rolling mills R = Rear arrangement of indicators
Mining industry for test
Textile, paper and food industries Isc = Test current for NXAIR up to 31.5 kA
Chemical industry = Test current for NXAIR M up to 25 kA
Petroleum industry = Test current for NXAIR P up to 50 kA
Pipeline installations t = Arc duration 1 s, optionally 0.1 s
Offshore installations In this way, NXAIR, NXAIR M
Electrochemical plants and NXAIR P switchgear is suit-
Petrochemical plants able for unrestricted application
Shipbuilding industry (wall or free-standing arrange-
Diesel power plants ment) in electrical service
Emergency power supply installations locations up to the maximum
Lignite open-cast mines short-circuit ratings.
Traction power supply systems.

Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010 5
Requirements
Customer benets and features

Customer benets Features


Peace of mind As insulating medium, air is always available; it requires no monitoring
For power supply companies Factory-assembled, type-tested switchgear according to IEC 62271-200 or VDE 0671-200
and industrial plants, the Platform concept introduced worldwide, centrally controlled development, local manufacture
platform concept of the NXAIR
Use of standardized block-type current transformers (NXAIR) or bushing-type current transformers
family introduced at all produc-
(NXAIR M, NXAIR P)
tion locations has very concrete
advantages: Use of standard components available worldwide
Smooth operation, exemplary More than 400,000 air-insulated switchgear panels of Siemens in operation worldwide
availability and optimal safety.
Use of maintenance-free vacuum circuit-breakers or contactors
Type testing of the vacuum circuit-breaker and the make-proof earthing switch in the panel
Pressure-resistant partitions
Flexibility regarding the low-voltage equipment (removable compartment, plug-in wires)
Quality assurance in accordance with DIN EN ISO 9001

Saves lives All operations with high-voltage door closed


All switchgear types of the Metallic enclosure, earthed shutters and partitions
NXAIR family are approved Internal arc classied switchgear according to IAC A FLR; front, lateral and rear accessibility; for all short-circuit
with internal arc classica- currents and an arc duration of 1 s, optionally 0.1 s
tion IAC A FLR, loss of service
Loss of service continuity category LSC 2B (separate partitions for busbar, connection and switching device
continuity category LSC 2B and
compartments)
partition class PM. This makes
them suitable for universal Partition class PM (metal-clad in pressure-resistant design)
installation, meeting the high- Unambiguous position indicators and control elements on the high-voltage door
est requirements regarding
Use of vacuum circuit-breakers or contactors
personal safety.
Standard degree of protection IP3XD
Positively driven shutters
Logical mechanical interlocking system

Increases productivity Loss of service continuity category: LSC 2B (separate partitions for the busbar, connection and switching
Properties such as modular device compartment)
design, type tests of the circuit- Partition class PM
breaker in the switchgear, Positively driven shutters
connement of an internal arc
Use of standardized block-type current transformers (NXAIR) or bushing-type current transformers
to the respective compartment,
(NXAIR M, NXAIR P)
and thus maximum operational
reliability, contribute to uninter- Cable testing without isolating the busbar
rupted operation and a remark- Functions such as establishment of the isolating distance, as well as feeder and busbar earthing, can be
able increase of productivity. completely controlled from remote
Connement of an internal arc to the respective compartment
Use of maintenance-free vacuum circuit-breakers or contactors
Control cables in metallic wiring ducts

Saves money Use of maintenance-free vacuum circuit-breakers or contactors


The compact design of the NXAIR Maintenance intervals of the switchgear > 10 years
family pays twice for owners due Interruption of operation reduced to a minimum by logical mechanical interlocking system
to the use of the new SION circuit-
Minimized space requirements (reduced building investments) due to compact design and exible cable
breaker series. On the one hand,
connection options
building costs can be reduced in
this way, and on the other hand,
the maintenance-free circuit-
breakers and the modular design
enable continuous operation with-
out expensive shutdown times.

Preserves the environment As insulating medium, air is absolutely neutral to the environment
Air used as insulating medium, Local production presence in all regions, minimized energy consumption (CO2) regarding transport
local production locations with Service life > 35 years optimizes the energy balance additionally
short transportation ways and
The materials used are fully recyclable without special knowledge
times, as well as a service life
> 35 years, optimize the total
energy balance.

6 Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010
Technical data
NXAIR electrical data and dimensions

Rated values Dimensions in mm


Rated Width B Circuit-breaker panel
voltage kV 7.2 12 17.5 1000 A 600
frequency Hz 50 / 60 50 / 60 50 / 60 2500 A 800/1000
short-duration power-frequency kV 20 1) 28 1) 38 Contactor panel
withstand voltage 400 A 435
(phase-to-phase, phase-to-earth) Disconnecting panel
lightning impulse kV 60 75 95 2500 A 800/1000
withstand voltage Bus sectionalizer
(phase-to-phase, phase-to-earth) 2500 A 2 x 800/1000
short-circuit breaking max. kA 31.5 31.5 31.5 Metering panel 800
current Busbar connection panel
short-time withstand max. kA 31.5 31.5 31.5 2500 A 800
current, 3 s Height H1 With standard low-voltage compart- 2300
short-circuit making current 2) max. kA 80 / 82 80 / 82 80 / 82 ment, natural ventilation
peak withstand current 2) max. kA 80 / 82 80 / 82 80 / 82 H2 With high low-voltage compartment 2350
normal current of busbar max. A 2500 2500 2500 or additional compartment for
busbar components
normal current of feeders:
Circuit-breaker panel max. A 2500 2500 2500 Depth T Single busbar, all panel types 1350
Contactor panel 3) max. A 400 400 (except contactor panel)
Disconnecting panel max. A 2500 2500 2500 Contactor panel 1400
Bus sectionalizer max. A 2500 2500 2500
Busbar connection panel max. A 2500 2500 2500

H2
H1
HA25-2686f eps

B T

1) 32 kV or 42 kV optional for GOST standard


2) Values for 50 Hz: 80 kA
60 Hz: 82 kA
3) Current values dependent on HV HRC fuses, for GOST
standard max. 32 kV short-duration power-frequency
withstand voltage.
Lightning impulse withstand voltage across open con-
tact gap of contactor: 40 kV at 7.2 kV, 60 kV at 12 kV.

Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010 7
Technical data
NXAIR M electrical data and dimensions

Rated values Dimensions in mm


Rated Width B Circuit-breaker panel
voltage kV 24 2000 A 800
frequency Hz 50 2500 A 1000
short-duration power-frequency kV 50 Disconnecting panel
withstand voltage 2000 A 800
(phase-to-phase, phase-to-earth) 2500 A 1000
lightning impulse withstand voltage kV 125 Bus sectionalizer
(phase-to-phase, phase-to-earth) 1250 A 2 x 800
1600 A, 2000 A, 2500 A 2 x 1000
short-circuit breaking current max. kA 25
Metering panel 800
short-time withstand current, 3 s max. kA 25
Height H1 With standard low-voltage 2200
short-circuit making current max. kA 63
compartment
peak withstand current max. kA 63
H2 With high low-voltage compartment 2550
normal current of busbar max. A 2500
H3 Standard panel or standard panel 2655
normal current of feeders:
with natural ventilation
Circuit-breaker panel max. A 2500
H4 With additional compartment 2770
Disconnecting panel max. A 2500
for busbar components
Bus sectionalizer max. A 2500
Depth T Single busbar 1554

H4
H3
H2
H1
HA25-2687g eps

B T

8 Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010
Technical data
NXAIR P electrical data and dimensions

Rated values Dimensions in mm


Rated Width B Circuit-breaker panel
voltage kV 7.2 12 17.5 2000 A 800
frequency Hz 50 / 60 50 / 60 50 / 60 > 2000 A 1000
short-duration power-frequency kV 20 1) 28 1) 38 Contactor panel 400 A 400
withstand voltage Disconnecting panel
(phase-to-phase, phase-to-earth) 2000 A 800
lightning impulse kV 60 75 95 > 2000 A 1000
withstand voltage Bus sectionalizer
(phase-to-phase, phase-to-earth) 2000 A 2 x 800
short-circuit breaking max. kA 50 50 50 > 2000 A 2 x 1000
current Metering panel 800
short-time withstand max. kA 50 50 50 Height H1 With standard low-voltage compart- 2225
current, 3 s ment ( 3150 A)
short-circuit max. kA 125 / 130 125 / 130 125 / 130 H2 With high low-voltage compartment 2485
making current 2) H3 With top-mounted pressure relief duct 2550
peak withstand current 2) max. kA 125 / 130 125 / 130 125 / 130 as standard
normal current of busbar max. A 4000 4000 4000 H4 With forced ventilation (4000 A) 2710
normal current of feeders: Depth T Single busbar (except contactor panel) 1635
Circuit-breaker panel max. A 4000 4000 4000 Contactor panel 1650
Contactor panel max. A 400 3) 400 3) Double busbar in back-to-back ar- 3320
Disconnecting panel max. A 4000 4000 4000 rangement (except contactor panel)
Bus sectionalizer max. A 4000 4000 4000

H4
H3
H2
H1
HA25-2688f eps

B T

1) 32 kV or 42 kV optional for GOST standard


2) Values for 50 Hz: 125 kA, 60 Hz: 130 kA,
make-proof earthing switch for 17.5 kV up to 100 kA
3) Dependent on rated current of HV HRC fuses used; dielectric
strength of contactor panel: 20 kV short-duration power-frequency
withstand voltage phase-to-phase, phase-to-earth, open contact
gap, or 60 kV lightning impulse withstand voltage phase-to-phase,
phase-to-earth, 40 kV open contact gap of the contactor.

Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010 9
Technical data
Room planning

NXAIR

1501)
HA25-2689e eps
Single-row arrangement (plan view)
for single-busbar switchgear
Dimensions B (width) and T (depth) see table on page 7 B B

T
For back-to-back and face-to-face arrangement, the room dimen-
sions apply accordingly to those for single-row arrangement.
For back-to-back arrangement, a 1200-mm wide control aisle is 35 35

1250
required on the left or on the right of the switchgear. 150 150
Room height 2) 2500 mm

NXAIR M

150
Single-row arrangement (plan view) HA25-2690e eps

for single-busbar switchgear


Dimensions B (width) and T (depth) see table on page 8 B B

T
For back-to-back and face-to-face arrangement, the room dimen-
sions apply accordingly to those for single-row arrangement.
For back-to-back arrangement, a 1200-mm wide control aisle is 35 35
150 150

1350
required on the left or on the right of the switchgear.
Room height 3000 mm

NXAIR P

110
HA25-2691f eps

Single-row arrangement (plan view)


for single-busbar switchgear
Dimensions B (width) and T (depth) see table on page 9 B B
T

For back-to-back and face-to-face arrangement, the room dimen-


sions apply accordingly to those for single-row arrangement.
For back-to-back arrangement, a 1200-mm wide control aisle is
required on the left or on the right of the switchgear. 32 32
100 100
1450

Room height 2800 mm

1) 100 mm to contactor panel


2) Room height dependent on short-circuit current
and pressure relief system.

10 Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010
Product range
NXAIR panels

Circuit-breaker panel Disconnecting panel


Current transformer

Voltage transformer

Withdrawable volt-
age transformers
with primary fuses

Make-proof
earthing switch

and/or and/or and/or and/or


Capacitive voltage
detecting system

or or and/or or

Cable sealing ends 1)


max. 4 x 500 mm2
and/or and/or and/or and/or per phase

and/or or
Bar feeder
HA25-2659d eps

or and/or
Withdrawable circuit-
breaker, optionally
manual or motor op-
HA25-2658e eps

and/or erating mechanism

HA25-2701 eps
Withdrawable
Contactor panel Metering panel contactor with
HV HRC fuses

Withdrawable con-
tactor with control
transformer and
HV HRC fuses

or
Withdrawable
disconnector link
with manual operat-
and/or or ing mechanism

or
HA25-2661f eps

and/or and/or
HV HRC fuse

For other compo-


HA25-2669b eps

and/or nents in the busbar


and connection 1) The details refer to Withdrawable
compartments, conventional single- metering unit with
see page 20. core sealing ends. withdrawable volt-
age transformers

Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010 11
Product range
NXAIR panels

Bus sectionalizer (mirror-image installation also possible)


Current transformer

Voltage transformer

Make-proof
earthing switch

Withdraw- Bus riser


Capacitive voltage
able panel panel
detecting system

1) 1) 1)

and/or and/or and/or and/or


Cable sealing ends 1)
max. 4 x 500 mm2
2) 2)
per phase
or and/or and/or or

2)
Bar feeder
HA25-2662e eps

and/or and/or

Withdrawable circuit-
breaker, optionally
manual or motor op-
erating mechanism

HA25-2701 eps
Busbar connection panel
Withdrawable
disconnector link
with manual operat-
ing mechanism

Withdrawable volt-
age transformers
with primary fuses

Withdrawable volt-
age transformers
and/or or or

and/or and/or

and/or
For other components in the busbar and connection
compartments, see page 20.
HA25-2700c eps

or 1) Current transformers only possible in combination


with withdrawable disconnector link.
2) In case of withdrawable metering unit, voltage
transformers and earthing switches on the busbar
are not possible.
3) The details refer to conventional single-core sealing
ends.

12 Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010
Product range
NXAIR M panels

Circuit-breaker panel Disconnecting panel


Current transformer

Voltage transformer

Make-proof
earthing switch

Capacitive voltage
detecting system

and/or and/or and/or and/or


Cable sealing ends 1)
max. 4 x 500 mm2
per phase
and/or or and/or or

Bar feeder
and/or and/or and/or and/or

or or Withdrawable circuit-
breaker, optionally
manual or motor op-
erating mechanism
HA25-2664d eps

HA25-2665d eps

and/or and/or

HA25-2701 eps
Withdrawable
disconnector link
with manual operat-
Metering panel ing mechanism

HV HRC fuse

Withdrawable
metering unit with
withdrawable volt-
age transformers

or

or
HA25-2666f eps

and/or

For other components in the busbar and connection


compartments, see page 20.

1) The details refer to conventional single-core sealing


ends.

Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010 13
Product range
NXAIR M panels

Bus sectionalizer (mirror-image installation also possible)


Current transformer

Voltage transformer

Make-proof
earthing switch

Withdraw- Bus riser


Capacitive voltage
able panel panel
detecting system

1) 1) 1)

and/or and/or and/or or and/or


Withdrawable
2) 2) circuit-breaker,
optionally manual
or and/or and/or or
or motor operating
mechanism
2)

HA25-2701 eps
HA25-2670f eps

and/or and/or

Withdrawable
disconnector link,
optionally manual
or motor operating
mechanism

Withdrawable volt-
age transformers

Withdrawable volt-
age transformers
with primary fuses

For other components in the busbar and connection


compartments, see page 20.

1) Current transformers only possible in combination


with withdrawable disconnector link.
2) In case of withdrawable metering unit, voltage
transformers and earthing switches on the busbar
are not possible.

14 Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010
Product range
NXAIR P panels

Circuit-breaker panel Disconnecting panel


Current transformer

Voltage transformer

Make-proof
earthing switch

Capacitive voltage
detecting system

and/or and/or and/or and/or


Cable sealing ends 1)
max. 6 x 500 mm2
per phase
and/or and/or

and/or and/or Bar feeder

or or
Withdrawable
circuit-breaker,
optionally manual
HA25-2673c eps
HA25-2672c eps

and/or and/or or motor operating


mechanism

Withdrawable dis-
Contactor panel Metering panel connector link with
manual operating
mechanism

HA25-2701 eps
Withdrawable
contactor with
HV HRC fuses

Withdrawable con-
tactor with control
HA25-2676b eps

and/or or transformer and HV


HRC fuses
or

and/or

Withdrawable
metering unit, with-
HA25-2675b eps

and/or drawable voltage


transformers with
For other components in the busbar and connection primary fuses
compartments, see page 20.

1) The details refer to conventional single-core sealing


ends.

Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010 15
Product range
NXAIR P panels

Bus sectionalizer (mirror-image installation also possible)


Current transformer

Voltage transformer

Make-proof
earthing switch

Withdraw- Bus riser


able panel panel Busbar riser for
bar connection

and/or and/or or Capacitive voltage


detecting system

HA25-2701 eps
HA25-2679e eps

and/or

Withdrawable
circuit-breaker,
optionally manual
or motor operating
mechanism

Withdrawable
metering unit, with-
drawable voltage
transformers

Withdrawable
metering unit, with-
For other components in the busbar and connection drawable voltage
compartments, see page 20. transformers with
primary fuses

Double-busbar switchgear Back-to-back arrangement


Double-busbar switchgear consists of panels from the single- Panels from the single-busbar product range (circuit-breaker
busbar product range. panel, disconnecting panel, bus sectionalizer and metering
It can be designed as follows: panel)
Face-to-face arrangement The two switchgear rows are interconnected by means of bars
Back-to-back arrangement. inside the panels
Bus coupler consisting of:
Face-to-face arrangement Circuit-breaker panel
Panels from the single-busbar product range (circuit-breaker Disconnecting panel.
panel, disconnecting panel, bus sectionalizer and metering
panel)
The two switchgear rows are interconnected by means of
cables or bars beneath the panels
Bus coupler consisting of:
Circuit-breaker panel
Disconnecting panel.

16 Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010
Design
NXAIR panel design, operation

Operation at the panel


Basic panel design (example)
Features
Integrated mimic diagram
Recognition of the respec-
tive switch positions, circuit-

HA25-2611g eps
breaker CLOSED / OPEN,
disconnected position, 13
earthing switch CLOSED /
OPEN, on the integrated 1 E
mimic diagram 2 B A
Unambiguous assignment
of actuating openings and 3
14
control elements to the 20
corresponding position 4
15 21
indicators 5
All switching operations 6 D
always with high-voltage 16 22
7
door closed
8 23
Ergonomically favorable
height for all control and 9 17
24
indicator elements 10
Option: Verication of safe 11 18
isolation from supply for
12
feeder or busbar by means
of the capacitive voltage 19 C
detecting system with panel
front closed.
Interlocks
Interlocking conditions
specied according to
IEC 62271-200 / VDE 0671- 1 Door of low-voltage compartment 12 Mechanical position indicator for
200 are fullled 2 Protection device withdrawable part
Feeder earthing switch 3 Option: Capacitive voltage detecting 13 Pressure relief duct
can only be operated with system for feeder and busbar 14 Busbars
switching device in discon- 4 High-voltage door 15 Bushing-type insulator
nected position 5 Mimic diagram 16 Block-type current transformer
Switching device can only 6 CLOSE-OPEN actuating openings for 17 Voltage transformer
be racked on the movable the circuit-breaker, opening for spring 18 Cable connection for max. 4 cables
part with the associated charging per phase
switching device in OPEN 7 Inspection window to recognize the 19 Make-proof earthing switch
position and with earthing CLOSED-OPEN indicator of the circuit- 20 Low-voltage connection, plug-in type
switch OPEN breaker, closing spring charged indicator,
21 Operating and interlocking unit for
Switching device can only operations counter
circuit-breaker
be operated in interlocked 8 Handle for opening the high-voltage door
22 Vacuum interrupters
disconnected or service 9 Actuating opening for racking the switch-
23 Contact system
position. ing device
24 Operating and interlocking unit for rack-
10 Mechanical position indicator for feeder
Beyond the specications ing the circuit-breaker and for earthing,
earthing switch
of the standards manual or optionally motor operation
11 Actuating opening for feeder earthing
Coding prevents insertion
switch, manual or optionally motor
of switching devices with a
operation
lower rated normal current
into panels with a higher
rated normal current
Interlocking between the
A Switching device compartment
high-voltage door and the
B Busbar compartment
position of the withdraw- C Connection compartment
able part D Withdrawable circuit-breaker
Option: Electromagnetic E Low-voltage compartment
interlocks, mechanical
key interlocking systems,
padlocks.

Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010 17
Design
NXAIR M panel design, operation

Operation at the panel


Basic panel design (example)
Features
Integrated mimic diagram
Recognition of the respec-
tive switch positions, circuit-
breaker CLOSED / OPEN,
13
disconnected position,

HA25-2641g eps
earthing switch CLOSED /
OPEN, on the integrated
1
mimic diagram B
Unambiguous assignment E
2
of actuating openings and
control elements to the A
3
corresponding position 14
indicators
4
All switching operations 20
always with high-voltage 5 15
door closed 21
6
Ergonomically favorable
height for all control and 7 22
16
indicator elements D
8 23
Option: Verication of safe
isolation from supply for 9
17
feeder or busbar by means 10
of the capacitive voltage 24
detecting system with panel 11
18
front closed. 12 C
Interlocks
Interlocking conditions 19
specied according to
IEC 62271-200 / VDE 0671-
200 are fullled
Feeder earthing switch
can only be operated with
switching device in discon- 1 Door of low-voltage compartment 11 Actuating opening for feeder earthing
nected position 2 Protection device switch, manual or optionally motor
Switching device can only 3 Option: Capacitive voltage detecting operation
be racked on the movable system for feeder and busbar 12 Mechanical position indicator for
part with the associated 4 High-voltage door withdrawable part
switching device in OPEN 5 Locking device / knob for high-voltage 13 Pressure relief duct
position and with earthing door 14 Busbars
switch OPEN 6 Mimic diagram 15 Bushing-type insulator
Switching device can only 7 CLOSE-OPEN actuating openings for 16 Bushing-type current transformer
be operated in interlocked the circuit-breaker, opening for spring 17 Voltage transformer
disconnected or service charging 18 Cable connection for max. 4 cables
position. 8 Inspection window to recognize the per phase
CLOSED-OPEN indicator of the circuit- 19 Make-proof earthing switch
Beyond the specications
breaker, closing spring charged indicator, 20 Low-voltage connection, plug-in type
of the standards
operations counter
Coding prevents insertion 21 Operating and interlocking unit for
9 Actuating opening for racking the switch- circuit-breaker
of switching devices with a
ing device
lower rated normal current 22 Vacuum interrupters
10 Mechanical position indicator for feeder
into panels with a higher 23 Contact system
earthing switch
rated normal current 24 Operating and interlocking unit for rack-
Interlocking between the ing the circuit-breaker and for earthing,
A Switching device compartment
high-voltage door and the manual or optionally motor operation
B Busbar compartment
position of the withdraw- C Connection compartment
able part D Withdrawable circuit-breaker
Option: Electromagnetic E Low-voltage compartment
interlocks, padlocks.

18 Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010
Design
NXAIR P panel design, operation

Operation at the panel


Basic panel design (example)
Features
Integrated mimic diagram
Recognition of the respec-
tive switch positions, circuit- 13
breaker CLOSED / OPEN,

HA25-2681g eps
disconnected position,
earthing switch CLOSED /
OPEN, on the integrated 1
14 E
mimic diagram
2
Unambiguous assignment
of actuating openings and 3 A
control elements to the 4
corresponding position 15
5 19
indicators
6 B
All switching operations
always with high-voltage 7 20
door closed 16
Ergonomically favorable 8 21
height for all control and C D
indicator elements 9
Option: Verication of safe 17 22
isolation from supply for 10
feeder or busbar by means
of the capacitive voltage 11
detecting system with panel 23
18
front closed. 12
Interlocks
Interlocking conditions
specied according to
Circuit-breaker panel 3150 A panel with natural ventilation
IEC 62271-200 / VDE 0671-
200 are fullled
Feeder earthing switch
can only be operated with
switching device in discon- 1 Door of low-voltage compartment 11 Mechanical position indicator and actuat-
nected position 2 Protection device ing opening for the make-proof earth-
Switching device can only 3 Option: Capacitive voltage detecting ing switch, manual or optionally motor
be racked on the movable system for feeder and busbar operation
part with the associated 4 High-voltage door 12 Ventilation duct up to 2500 A
switching device in OPEN 5 Mechanical lifting mechanism for opening 13 Pressure relief duct
position and with earthing the high-voltage door 14 Busbars
switch OPEN 6 Locking device for high-voltage door 15 Bushing-type insulator
Switching device can only 7 Mimic diagram 16 Bushing-type current transformer
be operated in interlocked 8 Closing spring charged indicator, position 17 Make-proof earthing switch
disconnected or service indicator for the switching device, and 18 Cable connection for max. 6 cables
position. operations counter per phase
Beyond the specications 9 CLOSE-OPEN actuating openings for 19 Operating and interlocking unit for
of the standards the circuit-breaker racking and operating the withdrawable
10 Mechanical position indicator and actuat- circuit-breaker
Coding prevents insertion
of switching devices with a ing opening for the withdrawable part, 20 Contact system
manual or optionally motor operation 21 Vacuum interrupters
lower rated normal current
into panels with a higher 22 Low-voltage connection, automatically
rated normal current coupling
Interlocking between the 23 Option: Truck
A Switching device compartment
high-voltage door and the
B Busbar compartment
position of the withdraw- C Connection compartment
able part D Withdrawable circuit-breaker
Option: Electromagnetic E Low-voltage compartment
interlocks, padlocks.

Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010 19
Design
NXAIR NXAIR M NXAIR P panels

Switching device compartment Connection compartment


Enclosure made of sendzimir-galvanized sheet steel Enclosure made of sendzimir-galvanized sheet steel
Pressure relief upwards Pressure relief upwards through rear pressure relief duct
Panel front powder-coated with epoxy resin For NXAIR and NXAIR M:
Standard color RAL 7035 Pressure-resistant partitions between switching device and
Separate shutter mechanism for opening and closing the busbar compartment
busbar compartment Shutters can be opened and locked separately
connection compartment Earthing busbar
High-voltage door pressure-resistant in the event of internal Option: Installation of bushing-type insulators or block-type
arcs in the panel current transformers in NXAIR, or bushing-type current trans-
For NXAIR and NXAIR M: formers in NXAIR M, NXAIR P
Pressure-resistant partitions to connection and busbar Option: Coupling electrode for capacitive voltage detecting
compartments system
Lateral metallic wiring duct for laying the control cables Option: Pressure-resistant oor cover
Low-voltage plug connector for connection of control cables Connection from front/bottom, or from rear/bottom, or from
between primary part and secondary part; automatically rear/top
coupling in NXAIR P Suitable for connection of:
Switching device compartment for the different panel Single-core XLPE cables up to 4 x 500 mm2 for NXAIR and
versions with withdrawable devices: NXAIR M, or 6 x 500 mm2 for NXAIR P
Vacuum circuit-breaker Three-core cables 3 x 240 mm2 per panel
Vacuum contactor Flat copper bars with bushings in a oor cover or fully-insu-
Withdrawable disconnector link lated bars including oor cover
Withdrawable metering unit Installation of voltage transformers
Endurance classes for: Cast-resin insulated
Circuit-breaker: E2, M2, C2 3 x 1-pole
Isolating distance (withdrawable part): M0 Fixed-mounted, without primary fuses
manually or partly motor-operated for withdrawable circuit- Or withdrawable with primary fuses in a separate compart-
breaker and disconnector link ment, with bushings and shutters to the connection compart-
Vacuum contactor 1,000,000 x IN. ment
Make-proof earthing switch
Busbar compartment With manual operating mechanism, optionally motor operat-
Enclosure made of sendzimir-galvanized sheet steel ing mechanism
Pressure relief upwards In addition to the standard interlock: Earthing switch option-
Option: Transverse partition from panel to panel for ally lockable or electromagnetically interlocked against the
NXAIR and NXAIR M withdrawable switching device
Standard: Transverse partition from panel to panel for Endurance class for earthing switch: M0, E1
NXAIR P Surge arrester or surge limiter
Busbars made of at copper, bolted from panel to panel: Surge arrester for protecting the switchgear against external
For NXAIR P, coated with epoxy resin powder overvoltages
Option: Insulated Surge limiter for protecting consumers against switching
For NXAIR and NXAIR M: overvoltages while operating motors with starting currents
Pressure-resistant partitions between connection and switch- 600 A.
ing device compartment, pressure-resistant rear wall
Shutters can be opened and locked separately
Bushing-type insulators for supporting the busbars and for
accommodating the upper xed contacts for the switching
device
Option: Max. three bushing-type current transformers
Option: Coupling electrode for capacitive voltage detecting
system.
Additional compartments (option) for busbar components
in NXAIR and NXAIR M, see also product range
Pressure-resistant compartment above the busbar compart-
ment within the pressure relief duct
Separate pressure relief of the additional compartment
upwards via pressure relief aps
Options: Possibility of installing the following components
(but not for panels with natural ventilation, see also product
range):
Voltage transformers
Make-proof earthing switch (endurance class: M0, E1),
manual or optionally motor operation.

20 Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010
Components
Vacuum circuit-breaker

Features
According to IEC 62271-100, for NXAIR for NXAIR M for NXAIR P
VDE 0671-100
Suitable for all switching duties
Circuit-breaker always with 1
motor operating mechanism,
manual operation always pos-
2 1
sible 11

R-HA25-314b tif
Racking the circuit-breaker with 2
manual operating mechanism, 3 12
optionally with motor operat-
4
ing mechanism
5
64-pole low-voltage plug con- 3 6
nector between circuit-breaker 7
4
and xed part (automatically 8
5
coupling in NXAIR P) 7
Maintenance-free operating 6
8 13
mechanisms under normal 9 9
climatic conditions and for the 13
10 10
max. permissible number of 14

R-HA25-315a eps
11
operating cycles
Contact arms generally with 12
silver-plated round contacts.

1 Low-voltage plug connector, 64-pole 1 ON pushbutton


2 Primary contacts 2 Hand crank coupling for the spring energy
3 OFF pushbutton store
4 Position indicator for circuit-breaker 3 OFF pushbutton
5 ON pushbutton 4 Indicator for closing spring of spring energy
6 Spring charged indicator store charged
7 Hand crank coupling for the spring energy 5 Position indicator
store 6 Operations counter
8 Operations counter 7 Position indicator for disconnected or service
9 Actuating opening for the racking mechanism position
10 Position indicator for earthing switch 8 Actuating opening for racking
11 Actuating opening for earthing switch 9 Position indicator for earthing switch
12 Position indicator for withdrawable part 10 Actuating opening for earthing
in disconnected or service position 11 Pole columns with moving contacts
13 Locking/unlocking the withdrawable part 12 Operating unit
13 Interlocking unit
14 Truck (option)

Electrical data for NXAIR NXAIR M NXAIR P


Rated operating voltage up to 17.5 kV 24 kV up to 17.5 kV
Rated short-circuit breaking current up to 31.5 kA up to 25 kA up to 50 kA
Rated short-time withstand current up to 31.5 kA / 3 s up to 25 kA / 3 s up to 50 kA / 3 s
Rated short-circuit making current up to 80 / 82 kA up to 63 kA up to 125 / 130 kA
Rated peak withstand current up to 80 / 82 kA up to 63 kA up to 125 / 130 kA
Rated normal current up to 2500 A up to 2500 A up to 4000 A
Endurance class E2, M2, C2 E2, M2, C2 E2, M2, C2

Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010 21
Components
Other switching devices

Vacuum contactor
Features for NXAIR for NXAIR P
According to IEC 60470,
VDE 0670-501
Suitable for operating consum-
ers with high switching rates

R-HA25-346 eps
R-HA25-345 eps
Short-circuit protection via up
to 2 HV HRC fuses connected
in parallel
Voltage supply of contactor
coil via primary-fused control
transformer or via external
power supply
Optional latching module for
the contactor
Racking the contactor via Withdrawable contactor Withdrawable contactor
manual operating mechanism 3TL6, HV HRC fuses and, 3TL6/8, HV HRC fuses and,
if applicable, control trans- if applicable, control trans-
64-pole low-voltage plug con-
former former
nector between contactor and
xed part
Maintenance-free operating Electrical data for 3TL6 in NXAIR 3TL6 in NXAIR P
mechanisms under normal Rated operating voltage up to 12 kV up to 12 kV
climatic conditions and for the Rated short-time withstand current 1) up to 8 kA up to 8 kA
max. permissible number of Rated normal current 2) 400 A 400 A
operating cycles
Number of mechanical operating cycles 1,000,000 3,000,000
Contact arms generally with of the contactor
silver-plated round contacts. Number of mechanical operating cycles 1,000,000 1,000,000
of the interrupters
Number of electrical operating cycles 500,000 or 1,000,000 1,000,000
of the contactor IN

1) Can be used in switchgear with short-time withstand currents up to 50 kA due to the current
limitation provided by HV HRC fuses.
2) Depending on the HV HRC fuses installed.

22 Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010
Components
Current transformers and post insulators

Features
According to IEC 60044-1, Current transformers
VDE 0414-1
Cast-resin insulated
for NXAIR for NXAIR M for NXAIR P
Block-type current transformer
principle, standardized, avail-
able worldwide
Bushing-type current trans-
former principle, standardized;
integrated functions: current
measurement, bushing and R-HA25-347 eps

R-HA25-317 eps

R-HA25-318 eps
support
Optionally with coupling
electrode for capacitive voltage
detecting system
Secondary multiratio possible
Current transformer certiable. Block-type current Bushing-type current Bushing-type current
transformer up to 2500 A transformer up to 2500 A transformer up to 4000 A

1 2 3 4 1 2 3 4

3 HA25-2684 eps

HA25-2685 eps
4
HA25-2702 eps

6
7

8
5 6 7 8 5 6 7 8

Section Section Section

1 Partition between switch- 4 Coupling electrode


ing device and connection 5 Fixed contact
compartment 6 Core with secondary winding
2 Cup bushing 7 Primary conductor
3 Mounting plate 8 Primary connection

Bushing-type insulators

for NXAIR for NXAIR M for NXAIR P


R-HA25-348 eps

R-HA25-320 eps

R-HA25-321 eps

(example)

Electrical data for NXAIR NXAIR M NXAIR P


Rated operating voltage up to 17.5 kV 24 kV up to 17.5 kV
Rated short-time withstand current up to 31.5 kA / up to 25 kA / up to 50 kA /
1 or 3 s 1 or 3 s 1 or 3 s
Rated peak withstand current up to 80 / 82 kA up to 63 kA up to 125 / 130 kA
Rated normal current up to 2500 A up to 2500 A up to 4000 A
Max. number of secondary cores for 3 3 3
instrument transformers

Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010 23
Components
Low-voltage equipment

Low-voltage compartment
Features
Low-voltage compartment for
accommodation of all protec-
tion, control, measuring and
metering equipment
Partitioned safe-to-touch off
the high-voltage part
Low-voltage compartment can
be removed, as all bus wires
and control cables are plugged
in
Option: Test sockets for capaci-
tive voltage detecting system
at the feeders or the busbar

R-HA25-292a eps
Option: Higher low-voltage
compartment
Option: Separation wall from
panel to panel
Low-voltage cables are exible
and protected by metal covers Low-voltage compartment with
Connection of withdrawable built-in equipment (example)
part and panel wiring to low-
voltage compartment via 10-
pole, coded plug connectors
Bus wires are pluggable from
panel to panel.

R-HA25-305a eps

Door of low-voltage
compartment (example)

24 Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010
Standards
Standards, specications, guidelines

Type of service location Table Dielectric strength


The switchgear can be used as indoor installation according Rated voltage (r.m.s. value) kV 7.2 12 15 17.5 24
to IEC 61936 (Power installations exceeding AC 1 kV) and
Rated short-duration power-frequency withstand voltage (r.m.s. value)
VDE 0101
Between phases and to earth kV 20 28 35 38 50
Outside lockable electrical service locations at places which
Across isolating distances kV 23 32 39 45 60
are not accessible to the public. Enclosures of switchgear can
only be removed with tools Rated lightning impulse withstand voltage (peak value)
In lockable electrical service locations. A lockable electrical Between phases and to earth kV 60 75 95 95 125
service location is a place outdoors or indoors that is reserved Across isolating distances kV 70 85 105 110 145
exclusively for housing electrical equipment and which is
kept under lock and key. Access is restricted to authorized Altitude correction factor K a
personnel and persons who have been properly instructed in
Ka
electrical engineering. Untrained or unskilled persons may
For site altitudes 1.50

HA40-2037c en eps
only enter under the supervision of authorized personnel or m=1
above 1000 m,

Altitude correction factor


properly instructed persons.
the altitude cor- 1.40
rection factor Ka
Dielectric strength
is recommended, 1.30
The dielectric strength is veried by testing the switch-
depending on
gear with rated values of short-duration power-frequency the site altitude
withstand voltage and lightning impulse withstand voltage 1.20
above sea level.
according to IEC 62271-1 / VDE 0671-1 (see table Dielectric
strength). 1.10
The rated values are referred to sea level and to normal
atmospheric conditions (1013 hPa, 20 C, 11 g/m3 humidity 1.00
according to IEC 60071 and VDE 0111). 1,000 1,500 2,000 2,500 3,000 3,500 4,000
The dielectric strength decreases with increasing altitude. Site altitude in m above sea level
For site altitudes above 1000 m (above sea level) the stan-
dards do not provide any guidelines for the insulation rating,
but leave this to the scope of special agreements. Rated short-dur. power-freq. withstand volt. to be selected for site altitudes > 1000 m
Site altitude
Rated short-duration power-frequency withstand voltage up to 1000 m Ka
The dielectric strength of air insulation decreases with
increasing altitude due to low air density. This reduction is Rated lightning impulse withstand voltage to be selected for site altitudes > 1000 m
permitted up to a site altitude of 1000 m according to IEC Rated lightning impulse withstand voltage up to 1000 m Ka
and VDE.
For site altitudes above 1000 m, a higher insulation level
must be selected. It results from the multiplication of the Example:
rated insulation level for 0 to 1000 m with the altitude cor- 3000 m site altitude above sea level
rection factor K a. 17.5 kV switchgear rated voltage
95 kV rated lightning impulse withstand voltage
Standards Rated lightning impulse withstand voltage to be selected =
The switchgear complies with the relevant standards and speci- 95 kV 1.28 = 122 kV
cations applicable at the time of type tests.
Result: According to the above table, a switchgear for a rated voltage of
In accordance with the harmonization agreement reached by
24 kV with a rated lightning impulse withstand voltage of 125 kV is to be
the countries of the European Union, their national specica-
selected.
tions conform to the IEC standard.

Overview of standards (December 2009)


IEC standard VDE standard EN standard
Switchgear NXAIR, NXAIR M, NXAIR P IEC 62271-1 VDE 0671-1 EN 62 271-1
IEC 62271-200 VDE 0671-200 EN 62 271-200
Devices Circuit-breakers IEC 62271-100 VDE 0671-100 EN 62 271-100
Vacuum contactors IEC 60470 VDE 0670-501 EN 60 470
Disconnectors and earthing switches IEC 62271-102 VDE 0671-102 EN 62 271-102
Switch-disconnectors IEC 60265-1 VDE 0670-301 EN 60 265-1
Switch-disconnector/fuse combination IEC 62271-105 VDE 0671-105 EN 62 271-105
HV HRC fuses IEC 60282 VDE 0670-4 EN 60 282
Voltage detecting systems IEC 61243-5 VDE 0682-415 EN 61 243-5
Degree of protection IEC 60529 VDE 0470-1 EN 60 529
Insulation IEC 60071 VDE 0111 EN 60 071
Instrument Current transformers IEC 60044-1 VDE 0414-1 EN 60 044-1
transformers Voltage transformers IEC 60044-2 VDE 0414-2 EN 60 044-2
Installation, erection IEC 61936-1 VDE 0101

Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010 25
Standards
Standards, specications, guidelines

Current carrying capacity Aseismic capacity


According to IEC 62271-1 / VDE 0671-1 and IEC 62271-200 / NXAIR, NXAIR P switchgear is tested in accordance with interna-
VDE 0671-200, the rated normal current refers to the follow- tionally accepted requirements.
ing ambient air temperatures:
Maximum of 24-hour mean + 35 C Internal arc classication
Maximum + 40 C Protection of operating personnel by means of tests for veri-
The rated normal current of the panels and busbars depends fying the internal arc classication
on the ambient air temperature outside the enclosure. Internal arcing tests must be performed in accordance with
IEC 62271-200 / VDE 0671-200
Protection against solid foreign objects, The switchgear complies with all criteria specied in the a.m.
electric shock and water standards (page 25) for the basic version up to 50 kA
NXAIR, NXAIR M and NXAIR P switchgear fullls according to NXAIR, NXAIR M und NXAIR P comply with the internal arc
the standards classication: IAC A FLR up to 50 kA, 1 s.
IEC 62271-200 This provides maximum personal safety of switchgear acces-
IEC 60529 sible from all sides
VDE 0470-1 Denition of criteria:
VDE 0671-200 Criterion 1
the following degrees of protection: Correctly secured doors and covers do not open,
Switchgear panel NXAIR NXAIR M NXAIR P limited deformations are accepted
Degree of protection for the IP3XD IP3XD IP3XD Criterion 2
enclosure, optionally IP4X, IP4X No fragmentation of the enclosure, no projection
IP50, IP51 IP50, IP51 of small parts above 60 g
Degree of protection for the IP3XD IP3XD IP3XD Criterion 3
enclosure, with ventilation IP4X IP4X No holes in accessible sides up to a height of 2 m
Degree of protection for the IP2X IP2X IP2X Criterion 4
partitions No ignition of indicators due to hot gases
Criterion 5
Climate and environmental inuences The enclosure remains connected to its earthing point
The switchgear may be used, subject to possible additional Beyond the specications of the above-mentioned standards,
measures, under the following environmental inuences: NXAIR switchgear up to 31.5 kA and/or NXAIR M switchgear
Natural foreign materials up to 25 kA are designed with connement of internal arcs to
Chemically active pollutants the respective compartment, which means that in the event
Small animals of an internal fault (arc) in a particular compartment, the
effects of this fault arc are limited to that compartment:
and the climate classes:
No burn-through of partitions to adjacent compartments
3K3
No burn-through of separation walls to adjacent switchgear
3K6
panels
3K8H.
Pressure resistance to adjacent compartments and switchgear
The climate classes are dened according to IEC 60721-3-3. panels
The connement of the internal arc to the respective com-
partment prevents:
Re-ignition of an internal arc on live parts in adjacent com-
partments
Impermissible deformation of partitions.

Terms
Make-proof earthing switches are earthing switches with
short-circuit making capacity according to
IEC 62271-102 and
VDE 0671-102 / EN 62 271-102.

26 Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010
Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P, up to 24 kV, Air-Insulated Siemens HA 25.71 2010 27
Published by and copyright 2010:
Siemens AG
Energy Sector
Freyeslebenstrae 1
91058 Erlangen, Germany

Siemens AG
Energy Sector
Power Distribution Division
Medium Voltage
Postfach 3240
91050 Erlangen, Germany
www.siemens.com/medium-voltage-switchgear

For more information, please contact our


Customer Support Center.
Phone: +49 180 / 524 70 00
Fax: +49 180 / 524 24 71
(Charges depending on provider)
E-mail: support.energy@siemens.com

KG 1209 28 En
6101/20874

All rights reserved.


If not stated otherwise on the individual pages of this
catalog, we reserve the right to include modifications,
especially regarding the stated values, dimensions and weights.
Drawings are not binding.
All product designations used are trademarks or product
names of Siemens AG or other suppliers.
If not stated otherwise, all dimensions in this
catalog are given in mm.

Subject to change without prior notice.


The information in this document contains general
descriptions of the technical options available, which
may not apply in all cases. The required technical
options should therefore be specified in the contract.

www.siemens.com/energy