1TL0001

THREE-PHASE ASYNCHRONOUS MOTOR


INSTRUCTIONS


Siemens Standard Motors Ltd.

1
1 General
1TL0001
1TL0001 motor is a totally enclosed self cooling induction motor for general purpose.
1TL0001 FS080-355 0.55-315kW IP54IP55

1TL0001 motor FS080~355, rating power 0.55-315kW, Protection class IP54. Option IP55.
GB18613-2012
3
1TL0001 motors comply with GB18613-2012Minimum allowable values of energy efficiency and
the energy efficiency grades for small and medium three-phase asynchronous motors. Energy
efficiency grade of the motors are grade 3, and the value of energy efficiency are shown on rating
plate.
1TL0001 ,:
,.:

1TL0001 motor is suitable for driving machines which have no special requirement, such as
machine tools, pumps, blowers, mining machines, agricultural machines etc. As the series of motor
has good starting characteristics, it is also suitable for machines which need high starting torque such
as compressors, mixers, miller etc.

2 Technical condition
(1) : 200660V , Rated voltage: 200660V.
(2) : 50Hz60Hz , Rated frequency: 50Hz, Option 60Hz.
(3) S1Rating: S1 (continuous).
(4) Y connection: or Y.
(5) 155(F
Insulation class: 155(F) class .
(6) 40 1000 Ambient temperature: up to 40.
Altitude above sea level up to 1,000 meters.

2
3 Motor type designation

Foot note:
1) 1)
90 Other voltages with voltage code 90 and the
corresponding option code
2) 2)
FS 080 -112 Only for FS 080 -112
3) 3)
H03 For correct position of condensation drainage holes,
B3 needed order with right specified type of construction
4) 4)
For protective cover with canopy needed option code
H00 H00
3
5) 5)
IM B3 As standard, the type of construction IM B3 is stamped
on the rating plate
6) 6)
IM B35 As standard, the type of construction IM B35 is stamped
on the rating plate
7) 7)
IM B5 As standard, the type of construction IM B5 is stamped
on the rating plate
8) 8)
IM B14 As standard, the type of construction IM B14 is stamped
on the rating plate
9) 9)
160 ~ 355 Only applicable for FS160~355
10) 10)
200 ~ 355 Only applicable for FS200~355

4 Configuration type
:
B3
B5
B35
There are three basic configuration type arrangements for series 1TL0 motor:
B3: Have frame feet but no flange.
B5: Have flange but no frame feet.
B35: Have frame feet and flange on end shield.
1 Table1

Foot note:

1) H00
1) At outdoor application the using of protective cover
(option code H00) is recommended;

2) 2) At out door application the protection of shaft


again jet-water is recommended.

4
5 Preparation of installation
5.1

Before unpacking, check up to ensure that the package is not damaged. After unpacking,
remove dust from the motor surface and rust-preventive coating from shaft extension end.
5.2
Check, whether the data on the nameplate are correct.
5.3

Check, if there is any damage or deformation during transportation. The fasteners should all be
fixed. The rotor should not rub against the stator, when it is turned by hand.
5.4 500 1 ,,
120
Check winding insulation resistance with 500 volts ohmmeter. The measured value should not be
lower than 1M, otherwise the stator winding has to be dried with temperature lower than 120.

6 Installation

All work must be carried out by a skilled worker. Before starting any work,
be sure to isolate the machine from the main and auxiliary power supply as
applicable. Mains must be secured against accidental switch on.

6.1 4 2 30 4
,

Motor can be transmitted through coupling, reduction gear or belt. But it is not suitable for
transmitted through belt of 2 pole motors above 4kW and 4 pole motors above 30 kW. The
transmission range of V- belt may be enlarged with using a small belt pulley. Extension shaft on NDE
(not drive end) is allowed to use the power output from the next smaller frame size.
6.2

With belt drive, the centre line of the motor shaft should be paralleled with centre line of the load
shaft, centre line of the belt should be perpendicular to the centre line of the shaft. With coupling drive,
the centre line of the motor should coincide with centre line of the load shaft.
6.3
For vertical installed motor, additional axial load is not allowed by belt pulley (or its equivalent).

5
7 Operation
7.1
The motor should be grounded properly. The terminal box should have grounding mark.
7.2 6
There are six terminals on the terminal board. The identifications are as follows:
2 Table2
Phase sequence A B C
Head of phase winding U1 V1 W1
Tail of phase winding U2 V2 W2

7.3 , Y

According to the nameplate, the connection of stator winding should be delta or star. When phase
sequence A.B.C of the power supply is accord with winding sequence U1, V1, W1, motor turn
direction is clockwise as viewed from the shaft extension end. With any of the two phase of the power
line changed, the motor turns in the opposition direction.

7.4
The motor should has a winding protecting device and a short-circuit protection device. According
to the current given by the name -plate, reset the relays for protecting device.

7.5 Winding protection


1TL0001:(15)
1TL0001 motors have different types of electrical protection available as an option:
PTC (145)(155)
PTC - used for temperature alarming (145C) or tr ipping function (155C)
PT100
PT100 - used for monitoring temperature of bearing or stator windings.

6
3 Table3


PTC 2PTC PT100 2PT100 Option
Option code Q5A
code Q02

2 PT100
U V W
155

155

145
PTC

PTC

PTC
resistance thermo-
U V W
meter for bearing
Heater
U1 U2 V1 V2 W1 W2 DE NDE

1HE1

1HE2
2TP1
2TP2
2TP1
2TP2
1TP1
1TP2

10R1

10R2

11R1

11R2
1R1
1R2
2R1
2R2
3R1
3R2
1R1
1R2
2R1
2R2
3R1
3R2
4R1
4R2
5R1
5R2
6R1
6R2
Foot note:
2PT1002TP12TP2 by usage of 2 PTC, terminal 2TP1 and 2TP2 are used
1TP11TP2 for tripping, 1TP1 and 1TP2 are used for alarming.

8 Maintenance
8.1 ,
Motors should be installed where atmosphere is relatively clean, dry, well ventilated.
8.2

If the winding protecting device or short circuit protecting device comes to function continually,
evaluation must be made to determine whether the motor is over- loaded or the protecting value is set
too low. Only after the trouble is eliminated the motor is allowed to resume operation.
8.3 5000

1/2 2 2/3 4.6.8



Correct lubrication must be maintained during operation. Normally, bearing grease should be
replace or replenish every 5000 hours of operation (for closed bearings, not change is necessary
during their bearing-life). Bearing grease should be replaced when its lubricant deteriorates or when
excessive heat of bearing occurs. Before fresh grease is use, bearing and oil slot of bearing cover
should be removed the dirty grease and cleaned with gasoline, then filled with lubricant ,grease up to
a half volume ( for 2 pole motors) or 2/3 volume ( for 4, 6 and 8 pole motors ) of the bearing inner
space.
8.4

When the bearing is on the wear limit, motor vibration and noise will go up noticeably. Inspect
bearing radial clearance and replace the bearing if the gap has reached the following values:
4 Table4
Bearing I.D (mm) 20-30 35-50 55-80 85-120
Max. Play allowed (mm) 0.10 0.15 0.20 0.30
8.5

7

When dismantle the motor to draw-out the rotor, it can be draw-out from either side of the motor
frame usually. It is more convenient to draw out the rotor from fan side. Carefully handling is
imperative in order not to damage the stator winding.

9 Storage and Transportation


9.1
Avoid any tilt or up side down during storage and transportation.
9.2
The motor must be in a dry space where no sudden change of air temperature.
9.3
Do not stack too high to damage the packages underneath.


The service coverage of Beide motor just restricts Chinese Mainland.

The company product service by after service room answer.

110
5
0514-85718143
0514-85718148
: 211417

Siemens Standard Motors Ltd.


No.110 West street, Qingshan Town, Yizheng City, Jiangsu. Prov.
Tel 0514-85718143
Fax0514-85718148
Zip211417