Treated Water Tank

Project- Page
Client- Design By
Date

DESCRIPTION Value Unit


Length of tank (L) 2.2 m
Width of tank (B) 2.2
Depth of water in tank (h) 2 m
Free board (fb) 0.5 m
Total heighht of water to be assumed for design (H) 2.5 m
Specific gravity of water (G) 1
Corrosion allowance @ inside surface (Ci) 1.5 mm
Corrosion allowance @ outside surface (Ce) 1.5 mm
Permissibel stress in bending tension (t) 165 N/mm2
Joint efficiency assumed 85 %
Joint efficiency factor (E) 0.85
Shell nominal thickness (Tnom) 6 mm
Permissible variation under specified thickness (Tol) 0.25 mm
L/B ratio of tank 1
We shall be providing tie at four levels in tank. Horizontal moment according coefficient of horizontal
moment mentioned in IS 3370 part IV
coef. My mom =Mywa
3

At height 3/4H from bottom 0.036 5.63 kNm/m


At height 1/2H from bottom 0.036 5.63 kNm/m
At height 1/4H from bottom 0.025 3.91 kNm/m
At top 0.019 2.97 kNm/m

UNDER INTERNAL PRESSURE


Z reqd Provided sect.
At height 3/4H from bottom 17.04545 ISMC 75
At height 1/2H from bottom 17.04545 ISMC 75
At height 1/4H from bottom 11.83712 ISMC 75
At top 8.996212 ISMC 75
Assuming plate as continuously supported over channels, moment in plate = wl /10
2

2.50m

25N/mm^2
Max. pressure at bottom = 25kN/m2 0.976563 kNm
Thickness required for above moment 5.959141 mm
Total thickness to be provided incl. corrosion allowance 8.959141 mm
Povide 10mm thk tank plate at bottom
Max. pressure at center = 25kN/m2 0.488281 kNm
Thickness required for above moment 4.213749 mm
Total thickness to be provided incl. corrosion allowance 7.213749 mm
Povide 8 mm thk plate at top
1
SRS
###

ovided sect.