Allied Consultants Ltd. DESIGN CALCULATION xx xx
1. Input Data:
2. Assumptions:
The pressure difference between stairwell
and building at stairwell bottom : 12.4 Pa
5. Calculations:
Abo Flow area between the building and outside per floor = 0.132 m2
Asb Flow area between stairwell and the building per floor = 0.031 m2
Project No. Date
Allied Consultants Ltd. DESIGN CALCULATION xx xx
In this system, an exterior stairwell door opens automatically uopn system activation. In addition, the lower
two floors will be considered opened, while the others doors will be considered closed.
(= 11326 cfm)
automatically uopn system activation. In addition, the lower
Wall Tightness - Area ratio
Construction element Tight Av. Loose V. Loose
1 2 3 4
Exterior building walls 0.00007 0.00021 0.00042 0.0013
Stairwell walls 0.000014 0.00011 0.00035
Elevator shaft walls 0.00018 0.00084 0.0018
Floors 0.000052