Power Plus

Power Plus Box


Stand alone, cascade and in-box applications
for commercial heating solutions

compliant
Beretta,
the professional
of the Plant Room
Thanks to Power Plus/BOX
systems, Beretta has become
the professional of your plant
room. The high reliability
of products, the availability
of a comprehensive line of
specific accessories, the ease
of mounting and the maximum
flexibility, make Beretta Power
Plus/BOX systems the best
solution both for large domestic
properties and commercial
buildings, like hotels, schools,
office-buildings, factories, sports
centers, etc. They are suitable
both for new buildings and as a
replacement of old boiler systems
and offer the highest efficiency
at any time, combined with the
maximum peace of mind, thanks
to their modularity.
The availability of two
different heat exchangers with
combustions of 50 kW (Hs)
and 128 kW (Hs), in different
combinations, offer a number of
practical boiler variants and even
more cascade configurations, all
available as natural gas or LPG.
Power Plus/BOX
Discover in this catalogue all models
and configurations offered by Beretta
Power Plus/BOX product range. You
will be surprised by the modularity
and flexibility of the solutions that
cover all installation needs in
commercial and light commercial
fields.
Beretta has developed also a
complete line of components and
accessories, listed at the end of this
guide, enabling to compose also
tailor-made applications. By choosing
all Beretta components, that
harmonize perfectly with each other,
your Power Plus/BOX system will
ensure the maximum comfort and
savings that are provided only by a
unique specialized manufacturer.
Contents

500-series_______________________________________________________________________ 7
Focus on Technology ______________________________________________________________________ 7
CASCADE and stand alone Applications ___________________________________________________ 13
Power Plus_____________________________________________________________________________ 18
Stand-alone wall-hung or free-standing configurations__________________________________________________ 20
Linear wall-hung or free-standing configurations______________________________________________________ 22
Back-to-back free-standing configurations_________________________________________________________ 28
Flue guidance ___________________________________________________________________________ 34
Examples of installations____________________________________________________________________ 38
Pre-assembled BOX______________________________________________________________________ 47
Flue and installation guidance _________________________________________________________________ 51
Stand alone up to 128 kW (outdoor or indoor) _______________________________________________________ 54
Cascade (outdoor - indoor)___________________________________________________________________ 56
Examples of installations____________________________________________________________________ 58

1000-series_____________________________________________________________________ 63
Focus on technology______________________________________________________________________ 63
Pre-assembled BOX______________________________________________________________________ 67
Flue and installation guidance _________________________________________________________________ 71
Cascade (indoor) _________________________________________________________________________ 74
Cascade (outdoor)________________________________________________________________________ 76
Stand alone (indoor and outdoor) _______________________________________________________________ 78
Hydraulic separator details ___________________________________________________________________ 80
Flue guidance: flue gas outlet and combustion air intake ________________________________________________ 82
Examples of installations____________________________________________________________________ 84

Complementary items ________________________________________________________ 91


SP - Inspectable plate heat exchanger ________________________________________________________ 92
Commercial cylinders and buffer tanks________________________________________________________ 94

Accessories________________________________________________________________ 97
Specific for 500-series CASCADE ___________________________________________________________ 98
Specific for 500-series BOX _______________________________________________________________ 102
Specific for 1000-series BOX______________________________________________________________ 105
Common to all configurations ______________________________________________________________ 107
Indoor flue options______________________________________________________________________ 109
Outdoor flue options_____________________________________________________________________ 118
Chimney system________________________________________________________________________ 122

6
500-series
500-series
Focus on Technology

7
Power Plus

The structure: Power Plus and Power Plus BOX


Power Plus, according to the output, consists of one (50 kW) or two
(100 kW) boiler units, connected to the water and gas system in parallel.
Each unit consists of the following main components:
Power Plus structure
Pre-mix combustion group, consisting of a modulating gas valve
integrated with a high total head fan.
This system guarantees a constant calibrated gas and air mix, ensuring
the highest efficiency under any running conditions.

High-efficiency 50 kW heat exchanger unit consisting of a continuous


bi-metal corrugated helical tube (copper on water side and AISI 316
stainless steel on flue sides) inside a cover. The micro-flame burner is
located in the upper part of the heat exchanger with single spark ignition.

The Master / Slave control system is located behind the front panel. It is
made of a Master board that manages one or more Slave boards (according
to the number of Slave boilers of the installation).
The Master board, beside allowing the cascade installation of more Slave
boilers, can manage:
a high temperature circuit;
a low temperature circuit;
a DHW tank, the temperature control function and the remote control panel.

Power Plus BOX structure

The board, which is located inside the box, can manage:


a high temperature circuit;
a low temperature circuit;
a DHW tank, the temperature control function.
It can be also linked to the remote control panel.

Pre-mix combustion group, consisting of a modulating gas valve


integrated with a high total head fan.
This system guarantees a constant calibrated gas and air mix, ensuring
the highest efficiency under any running conditions.

High-efficiency 50 kW heat exchanger unit consisting of a continuous


bi-metal corrugated helical tube (copper on water side and AISI 316
stainless steel on flue sides) inside a cover. The micro-flame burner is
located in the upper part of the heat exchanger with single spark ignition.

8
500-series
The technology: Condensing heat exchanger
The Power Plus condensing heat exchanger has a high exchange surface and an excellent corrosion resistance.
It has a cylindrical shape and it is made of the following components:
micro-flame burner;
stainless steel covering AISI 316L;
continuous bi-metallic corrugated helical tube (copper alloy on the water side and stainless steel on the flue side), which is coiled up inside the cover;
refractory brick, which keeps the heat inside the combustion chamber and forces the flue gases over the heat exchanger surfaces, optimising the
thermal heat exchange performance.
plastic header on the flue outlet with a probe for the continuous control of the flues temperature.

Flow pipe
Fan
Single spark ignition and
flame control electrode
Gas valve

Burner
Air inlet pipe

Refractory brick

Heat exchanger

Flue discharge pipe

Condensate discharge pipe Return pipe

Condensing heat exchanger section of the continuous


bi-metallic corrugated helical tube, coiled up inside a cover:
copper alloy on the water side and stainless steel on the
flue side

9
Power Plus

Condensing boilers and radiator plants... the Power Plus strength!


During the years, the diffused thought is that condensing boilers allow The distinctive element of our condensing boiler is the low T water-
to save on fuel only with low temperature systems (underfloor heating). flues, that is the capacity to exhaust flues at a temperature of only 3C
This may be true for many condensing boilers on the market... higher than the heating plant water returning to the boiler; other
BUT NOT FOR THE POWER PLUS! condensing boilers have a T water-flues of even 25C.

Condensing boilers Power Plus condensing boilers

T
T
Underfloor
systems

Dew temperature
Dew temperature
55C
55C
Flues Flues
TEMPERATURE TEMPERATURE
40C = 40C =
35C T return + 20C 35C T return + 3C

Burner Plant return Burner Plant return


- - - -
Plant flow Flues exhaust Plant flow Flues exhaust

In low temperature systems (ex. 40C/35C), the other In low temperature systems (ex. 40C/35C), the
condensing boilers also manage to evacuate flues at Power Plus condensing boilers manage to evacuate flues
a temperature sufficiently low (approx. 50C - 55C) at a temperature of only 3C higher than the return
to be able to work in condensing conditions with high (approx. 38C) and work in full condensing conditions
efficiency. with very high efficiency.

Condensing boilers Power Plus condensing boilers

T
T

Radiator
systems
70C
70C
Flues
Flues
Dew temperature TEMPERATURE
TEMPERATURE
Dew temperature 55C =
55C =
T return + 3C
50C
T return + 20C 50C

Burner Plant return Burner Plant return


- - - -
Plant flow Flues exhaust Plant flow Flues exhaust
In high temperature systems (ex. 70C/50C), most In high temperature systems (ex. 70C/50C), the
condensing boilers on the market evacuate flues at a Power Plus condensing boilers evacuate flues at an
temperature higher than that of the nat gas flues dew, even lower temperature than that of the nat gas flues
in fact working as traditional boilers and therefore with dew, still working as condensing boilers with high
low efficiency. The cause is the high water-flues T efficiency. The point of strength is in the low water-flues
(even up to 25C). delta T (3C) which brings us to evacuate the flues at
53C, with a return of 50C!

10
500-series
Low Energy shunt pump and differential pressure switch
According to the new ErP Directive, for the Power Plus range it is These componets ensure maximum savings and meanwhile the
available the new Low Energy shunt pump. Also the Power Plus BOX highest reliability.
range is equipped with Low Energy shunt pumps and in addition a In the event of a fault or maintenance on one unit, the other units are
differential pressure switch on each unit. still able to operate.

Residual head of the Power Plus


LOW ENERGY shunt pump
H[m]
10

0
0 1 2 3 4 5 Q [m 3/h]

Perfect combination with renewable systems

Power Plus and Power Plus BOX can be perfectly matched with Beretta renewable systems

11
International Markets

Product Catalogue

M O LTO
DI UN TE M OS TATO.

Thanks to the flexibility of the Power Plus/BOX


range, it is possible to integrate the boilers with
solar systems and heat pumps.
Refer to the system diagrams and to the
solutions proposed on the
Beretta International Product Catalogue.

12
500-series CAASCADE and STAND ALONE
500-series
CASCADE and stand alone
Applications

13
Power Plus
The efficiency of our condensing technology
500-series CAASCADE and STAND ALONE
Beretta Power Plus is a condensing pre-mixed air blown modulating wall-hung boiler, designed for cascade and stand-alone installation.

It is available in four versions:


50 M and 100 M (Master models, of 50 and 100 kW respectively), working both as stand-alone boiler and in cascade application with Slave
versions;
100 M DEP (Master model, of 77,3 kW), working both as stand-alone boiler and in cascade application with Slave versions;
100 S (Slave model, of 100 kW), especially designed to work in cascade application (up to 400 kW) managed by a Master versions.

Power Plus range achieved an Efficiency


according to European Directive EEC 92/42
Gas Directive EEC 90/396
Low voltage Directive EEC 89/336
Electromagnetic compatibility Directive EEC 73/23

The range
MASTER models SLAVE models
Power Plus 50 M
Master model, output from 15 (Hi) to 50 kW
(Hs), consists of one heat exchanger unit and
can work both as stand alone and in cascade
applications with Slave models.

Power Plus 100 M DEP Power Plus 100 S


Master model, output from 15 (Hi) to 77,3 kW Slave model, output from 15 (Hi) to 100 kW
(Hs), consists of two heat exchanger units and (Hs), consists of two heat exchanger units and
can work both as stand alone and in cascade can work only in cascade applications
applications with Slave models. managed by a Master model.

Power Plus 100 M


Master model, output from 15 (Hi) to 100 kW
(Hs), consists of two heat exchanger units and
can work both as stand alone and in cascade
applications with Slave models.

Characteristics and advantages at a glance


Possibility to combine Power Plus boilers in thus ensuring the installer a quick controlled pre-mix burner and the micro-
pre-set cascade systems up to 400 kW, connection to any type of heating and hot flame burner combination, allowing Power
making them suitable for a wide variety of water storage system as it simultaneously Plus to achieve Class 5 of the UNI EN 483
installations, from office buildings and controls three different circuits, each standard (best European category in
sports centres to schools and hotels. operating at a different temperature. ecological terms).
A cascade installation that offers system Power Plus units are designed to provide Water drain built-in as standard in the boiler
options to meet the space requirements of water to 3 different circuits at different for each heating unit.
the customer, who can choose among wall temperatures either supplied as direct take Built-in temperature control and external
hung, linear free-standing and back-to- offs or via a header system utilizing controls probe as standard.
back free-standing configurations. as required. With this in mind suggested Automatic burner ignition sequence
Excellent performance combined with low usage are DHW, High Temperature reversal.
running costs, thanks to Beretta (heating) and Low Temperature (under-floor Anti-legionnaires disease function (only
condensing technology with pre-mix heating). It is possible to add up to 8 zones available with room-control kit).
combustion. with the use of specific accessories. Frost-protection system.
These heating units boast latest generation Modulating and modular power regulation.
electronic control, modularity and versatility, Minimum polluting emissions, thanks to the

15
Power Plus

Ten reasons why a Power Plus cascade system is the logical choice
The Beretta Power Plus has been specifically designed for cascade applications. Thanks to its modularity and intelligent features, it can be
considered the best solution for light commercial applications, both in the new buildings and as replacement of old, less efficient boiler systems.

Maximum efficiency at any time Maximum use of space


The efficiency of a Power Plus cascade system is significantly higher The cascade system of Power Plus range is designed to provide a
than a traditional single boiler installation with the same output. In fact, space-saving and versatile solution for large domestic properties or
by automatically controlling the number of boilers in operation, the light commercial buildings. The compact dimensions of Power Plus
system can optimise the heat supply according to demand at any (1000x600x380 mm) enable for instance a 400 kW free standing back-
particular time. For instance in spring and autumn, when the heat to-back cascade to fit in less than 1,30 m!
request is lower, or in buildings like hotels and restaurants, where the
heat request is not constant, the system can switch individual boilers Maximum flexibility
on and off, ensuring maximum efficiency. Power Plus cascade installation can be tailored to meet the space
requirements of the customer, as there are three different possibilities of
Maximum peace of mind composing the cascade: wall hung installation, free-standing side-by-
Power Plus cascade system is more reliable than a traditional individual side installation and free-standing back-to-back installation. Moreover,
boiler installation. As each boiler of the cascade can be individually thanks to the modularity of the system, the total output can be
serviced and maintained, in the event of a fault or maintenance on one accurately sized to meet the space and energy requirements of the
boiler, the other boilers of the cascade are still able to operate without building.
a total loss of heating.
Maximum ease of installation
Maximum savings Power Plus cascade design allows an extremely easy installation. Each
The high efficiency of the cascade system, courtesy of the intelligent single boiler can be transported separately and its compact dimensions
condensing technology of the boilers allow you to save so much energy fit through most doorways. The cascade can be assembled in the
in daily use that the costs of the heating system are recovered in a few boiler room, which is useful in new-build and refurbished plant-rooms.
years. In addition, reduced installation time and quick servicing result in The installer simply has to set up the framework, mount and connect
precious savings for the end user. the boiler and all other parts together and the system is installed by a
quick and simple process.
Maximum commitment to the environment
Power Plus range achieved Class 5 of the UNI EN 483 standard (best Maximum range of modulation
European category in ecological terms), thanks to condensing Power Plus M (master model) contains a board that can manage up to
combustion with controlled pre-mix burner and micro-flame burner 60 slaves in cascade up to a maximum 3 MW of power, with a
combination. A Power Plus cascade system can also control modulation down to only 16 kW. To configure multi-boiler cascades
automatically the number of boilers in operation according to heat over 400 kW, all components of the cascade must be accurately sized
demand, saving energy and reducing polluting emissions. and selected with the help of a specialised design engineer.

Maximum reliability Maximum ease of servicing


Beretta has carefully selected an extensive range of high quality Power Plus range is designed so that all components can be easily
components and accessories to configure Power Plus cascades up to serviced and maintened from the front. Moreover, each boiler of the
400 kW, as per the detailed configuration proposals contained in this cascade can be individually serviced and maintained, while the other
guide. By choosing Beretta complete Power Plus systems, you ensure boilers of the cascade are still able to operate.
that all the components of your cascade work in harmony with one
another, flow volumes are balanced and hydraulic performance is
optimized, so that you obtain maximum reliability and saving from your
heating system.

16
500-series CAASCADE and STAND ALONE
One frame, three different installation solutions
Beretta has developed a clever frame for the cascade (or stand-alone) Trouble-free installation, compact design and competitive price make
installation of Power Plus. this frame the most clever solution to install your Power Plus with or
According to the space requirements of the customer, the same frame without the need of a wall.
allows three different possibilities of installation: The robustness of the frame (made in painted, zinc-coated steel)
wall-hung, completes the profile of this versatile product.
linear free-standing,
back-to-back free-standing installation.

linear back-to-back
wall-hung or free-standing installation free-standing installation

Beretta ready-made configurations


Beretta offers you in the following pages a wide choice of configurations of Power Plus series, among which you can
choose the one that best meets your requirements.
According to the preferred installation solution and the power you need, Beretta suggests:
8 linear wall-hung or free-standing configurations (from 50 to 400 kW)
6 back-to-back free-standing cascade configurations (from 150 to 400 kW)
Every configuration is described by a diagram, with a key related to the different components of the configuration.

17
Power Plus

Minimum polluting emissions: class 5 (UNI EN 483).


Pre-mix burner: low NOx emissions class 5 (UNI EN 483).
Built-in thermoregulation with external probe supplied as
standard.
Possibility to combine Power Plus boilers in cascade
systems in wall-hung or free-standing installations.
Modulating and modular power regulation.
Automatic burner ignition sequence reversal.
Simultaneous control of three different circuits, each operating
at different temperatures (DHW tank, high-temperature, low-
temperature).
Automatic summer/winter reversal.
Anti-legionnaires disease function (only available with remote
control kit).
Availability of a wide range of accessories for complete cascade
configurations.
Can be converted to LPG with LPG kit (supplied as standard).

Open flue/Room-sealed through special kit


DIMENSIONS ENERGY CLASS
INPUT INPUT
CODE GAS MODEL HWD
(kW) Hs (kW) Hi
(mm)
HEATING ONLY BOILERS

20019155 NG POWER PLUS 50 M * 1.000 600 380 50 45

20019201 NG POWER PLUS 100 M DEP ** 1.000 600 380 77,3 69,7 -

20019200 NG POWER PLUS 100 M *** 1.000 600 380 100 90 -

20019309 NG POWER PLUS 100 S *** 1.000 600 380 100 90 -

* The 50 kW model consists of one heat-exchanger unit.


** The 100 kW DEP model consists of two depowered heat-exchanger units.
*** The 100 kW models consist of two heat-exchanger units.
1000

380 M R gas M R gas


600

= NEW (new codes are contained inthe green rectangle)

18
500-series CAASCADE and STAND ALONE
KEY: M Master model
S Slave model
DEP Depowered heat exchanger model

Power Plus Power Plus Power Plus Power Plus


SPECIFICATIONS
50 M 100 M DEP 100 M 100 S
Fuel G20 - G25 - G2.350 - G27 - G30 - G31
Appliance Category II2ELwLs3B/P - II2H3+ - I2E(S)B
Type of Appliance B23 - B53 - C13x - C33x - C43x - C53x - C63 - C63x - C83
Seasonal space heating energy efficiency class (ErP) A - - -
Heat input ref. Hs (min-max) G20 kW 16,3 - 50,0 16,3 - 77,3 16,3 - 100,0 16,3 - 100,0
Heat input ref. Hi (min-max) G20 kW 15,0 - 45,0 15 - 69,6 15,0 - 90,0 15,0 - 90,0
Useful heat output (80/60C) (min-max) kW 14,8 - 44,2 14,8 - 68,5 14,8 - 88,3 14,8 - 88,3
Useful heat output (50/30C) (min-max) kW 16,3 - 48,5 16,3 - 75,3 16,3 - 96,8 16,3 - 96,8
Useful efficiency ref. Hi (80-60C) % 98,2 98,4 98,2 98,2
Useful efficiency ref. Hi (50-30C) % 107,7 108,2 107,7 107,7
Useful efficiency at ref. Hi 30% (80 - 60C) % 98,7
Useful efficiency at ref. Hi 30% (50 - 30C) % 108,7
Losses through the chimney with the burner operating % 1,3
Losses through the chimney with the burner off % 0,1
Losses through the casing (Tm = 70C) % 0,5
Flue gas temperature C Return temperature 5C
CO2 at minimum - maximum G20 % 9,0 - 9,0
CO2 at minimum - maximum G30 - G31 % 10,4 - 10,4
CO without air at minimum - maximum less than mg/kWh 11-91
NOx Class 5
Air flow rate G20 Nm3/h 58,78 88,84 117,56 117,56
Air flow rate G30 - G31 Nm3/h 58,59 90,58 117,18 117,18
Flue gas flow rate G20 Nm3/h 71,04 114,52 142,08 142,08
Flue gas flow rate G30 - G31 Nm /h 3
71,76 110,94 143,52 143,52
Flue mass gas flow rate (max - min) G20 gr/s 20,57 - 6,60 31,08 - 6,60 41,14 - 6,60 41,14 - 6,60
Flue mass gas flow rate (max - min) G30 - G31 gr/s 20,52 - 6,85 31,73 - 6,85 41,04 - 6,85 41,04 - 6,85
at min. heat output Pa 50 50 50 50
Residual head of boiler fan without pipes
at max. heat output Pa 560 420 560 560
at min. heat output Pa 40 40 40 40
Residual head of boiler fan downstream from clapet*
at max. heat output Pa 490 370 490 490
Minimum operating pressure, central heating bar 0,5
Maximum operating pressure, central heating bar 6
Maximum admissible temperature C 90
Range of boiler water temperature settings (3C) C 20 - 80
Water content l 5 10 10 10
Power supply V-Hz 230 - 50
Power consumption: only Gas Boiler W 80 154 160 160
Power consumption: Gas Boiler + Low Energy Pump (ErP compliant) W 165 324 330 330
Power consumption: only Low Energy Pump (ErP compliant) W 85 170 170 170
Power consumption: Gas Boiler + Pump (non ErP compliant) W 230 - 460 460
Power consumption: only Pump (non ErP compliant) W 150 - 300 300
Index of protection IP X0D
Quantity of condensate kg/h 7,2 11,2 14,4 14,4
Noise level at min - max heat output** dBA 48,2 - 57,1 49,0 - 58,0 49,0 - 58,9 49,0 - 58,9
Gas capacity (min - max) G20 Sm3/h 1,52 - 4,76 1,52 - 7,37 1,52 - 9,52 1,52 - 9,52
Gas capacity (min - max) G30 kg/h 1,16 - 3,64 1,16 - 5,48 1,16 - 7,28 1,16 - 7,28
Gas capacity (min - max) G31 kg/h 1,14 - 3,57 1,14 - 5,41 1,14 - 7,14 1,14 - 7,14
Dry weight kg 60 90 90 90
(*) Measurements obtained using the clapet with which the boiler was homologated.
(**) Measurements taken at 1m from the appliance, at a height of 1,5m with background noise of 36,5 dBA.

19
Power Plus

Stand-alone configuration - 50 kW (wall-hung or free-standing)

23

22 125

1
24

11

13
18

5
16

17

19

This scheme has only an indication purpose

diagram diagram
code description qty code description qty
ref. ref.
BOILERS 18 20017271 Hydraulic header/separator 100 kW 1
1 20019155 Power Plus 50 M 1 17 20017270* I.N.A.I.L. connection pipes kit - 100 kW 1
USER INTERFACE 13 20009475* I.N.A.I.L. safety kit (400 kW max.) 1
24 1102379** Remote control 1 16 20009486** Gas safety cut-off valve (115 kW max.) 1
HYDRAULIC COMPONENTS and SAFETY DEVICES SUPPORTS for LINEAR WALL-HUNG or FREE-STANDING MOUNTING

Hydraulic manifold kit 100 kW for Power Plus rig with 11 20009472 Power Plus rig (front mounting) 1
19 20017226 1
blank end-flange FLUES

LOW ENERGY pump kit (front) 23 4030311 Flues collector kit 125 for 50 kW 1
5 20075526*** 1
for Power Plus rig (ErP compliant) 22 20062337 Condensate drain kit 125 with end cap 1

* I.N.A.I.L. optional component (I.N.A.I.L. = Italian safety certification Institute).


** OPTIONAL component.
*** Pump kit (front), non-ERP compliant, is available, as an alternative option, only for EXTRA-EC countries. See section ACCESSORIES.

note: the whole range of components, accessories and flues for Power Plus applications is listed in this guide in the section ACCESSORIES

20
500-series CAASCADE and STAND ALONE
Stand-alone configuration - 100 kW (wall-hung or free-standing)

21

22 125

2 24

13
11
18

5
16

17
19

This scheme has only an indication purpose

diagram diagram
code description qty code description qty
ref. ref.
BOILERS 18 20017271 Hydraulic header/separator 100 kW 1
2 20019200 Power Plus 100 M 1 17 20017270* I.N.A.I.L. connection pipes kit - 100 kW 1
USER INTERFACE 13 20009475* I.N.A.I.L. safety kit (400 kW max.) 1
24 1102379** Remote control 1 16 20009486** Gas safety cut-off valve (115 kW max.) 1
HYDRAULIC COMPONENTS and SAFETY DEVICES SUPPORTS for LINEAR WALL-HUNG or FREE-STANDING MOUNTING

Hydraulic manifold kit 100 kW for Power Plus rig with 11 20009472 Power Plus rig (front mounting) 1
19 20017226 1
blank end-flange FLUES

LOW ENERGY pump kit (front) 21 4030312 Flues collector kit 125 for 100 kW 1
5 20075526*** 2
for Power Plus rig (ErP compliant) 22 20062337 Condensate drain kit 125 with end cap 1

* I.N.A.I.L. optional component (I.N.A.I.L. = Italian safety certification Institute).


** OPTIONAL component.
*** Pump kit (front), non-ERP compliant, is available, as an alternative option, only for EXTRA-EC countries. See section ACCESSORIES.

note: the whole range of components, accessories and flues for Power Plus applications is listed in this guide in the section ACCESSORIES

21
Power Plus

Linear cascade configuration - 150 kW (wall-hung or free-standing)

21 23

125 125
22

3 1 24

POWER POWER 8
PLUS 100 S PLUS 50 M 13
11

7
10
14
4

This scheme has only an indication purpose

diagram diagram
code description qty code description qty
ref. ref.
BOILERS 8 20009466 Hydraulic header/separator (150-200 kW) 1
1 20019155 Power Plus 50 M 1 10 20009471 Hydraulic manifold (150 - 400 kW) 1
3 20019309 Power Plus 100 S 1 13 20009475* I.N.A.I.L. safety kit (400 kW max.) 1
USER INTERFACE 14 20009482** Gas safety cut-off valve (230 kW max.) 1
24 1102379** Remote control 1 SUPPORTS for LINEAR WALL-HUNG or FREE-STANDING MOUNTING
HYDRAULIC COMPONENTS and SAFETY DEVICES 11 20009472 Power Plus rig (front mounting) 2
4 20009439 Hydraulic manifold kit up to 400 kW for Power Plus rig 2 FLUES
7 20009444 Blank end-flange kit for hydraulic manifold 1 21 4030312 Flues collector kit 125 for 100 kW 1

LOW ENERGY pump kit (front) 22 20062337 Condensate drain kit 125 with end cap 1
5 20075526*** 3
for Power Plus rig (ErP compliant) 23 4030311 Flues collector kit 125 for 50 kW 1

* I.N.A.I.L. optional component (I.N.A.I.L. = Italian safety certification Institute).


** OPTIONAL component.
*** Pump kit (front), non-ERP compliant, is available, as an alternative option, only for EXTRA-EC countries. See section ACCESSORIES.

note: the whole range of components, accessories and flues for Power Plus applications is listed in this guide in the section ACCESSORIES

22
500-series CAASCADE and STAND ALONE
Linear cascade configuration - 200 kW (wall-hung or free-standing)

21

22 125 125

3 2 24

11 8
POWER POWER 13
PLUS 100 S PLUS 100 M

7
10
14
4

This scheme has only an indication purpose

diagram diagram
code description qty code description qty
ref. ref.
BOILERS 8 20009466 Hydraulic header/separator (150-200 kW) 1
2 20019200 Power Plus 100 M 1 7 20009444 Blank end-flange kit for hydraulic manifold 1
3 20019309 Power Plus 100 S 1 10 20009471 Hydraulic manifold (150 - 400 kW) 1
USER INTERFACE 13 20009475* I.N.A.I.L. safety kit (400 kW max.) 1
24 1102379** Remote control 1 14 20009482** Gas safety cut-off valve (230 kW max.) 1
HYDRAULIC COMPONENTS and SAFETY DEVICES SUPPORTS for LINEAR WALL-HUNG or FREE-STANDING MOUNTING

Hydraulic manifold kit up to 400 kW 11 20009472 Power Plus rig (front mounting) 2
4 20009439 2
for Power Plus rig FLUES

LOW ENERGY pump kit (front) 21 4030312 Flues collector kit 125 for 100 kW 2
5 20075526*** 4
for Power Plus rig (ErP compliant) 22 20062337 Condensate drain kit 125 with end cap 1

* I.N.A.I.L. optional component (I.N.A.I.L. = Italian safety certification Institute).


** OPTIONAL component.
*** Pump kit (front), non-ERP compliant, is available, as an alternative option, only for EXTRA-EC countries. See section ACCESSORIES.

note: the whole range of components, accessories and flues for Power Plus applications is listed in this guide in the section ACCESSORIES

23
Power Plus

Linear cascade configuration - 250 kW (wall-hung or free-standing)

21 23

22 125 125 125

3 1 24

11 9
POWER
PLUS 50 M
13

5 7

10
4 15

This scheme has only an indication purpose

diagram diagram
code description qty code description qty
ref. ref.
BOILERS 9 20009467 Hydraulic header/separator (250-460 kW) 1
1 20019155 Power Plus 50 M 1 10 20009471 Hydraulic manifold (150 - 400 kW) 1
3 20019309 Power Plus 100 S 2 13 20009475* I.N.A.I.L. safety kit (400 kW max.) 1
USER INTERFACE 15 20009483** Gas safety cut-off valve (580 kW max.) 1
24 1102379** Remote control 1 SUPPORTS for LINEAR WALL-HUNG or FREE-STANDING MOUNTING
HYDRAULIC COMPONENTS and SAFETY DEVICES 11 20009472 Power Plus rig (front mounting) 3
4 20009439 Hydraulic manifold kit up to 400 kW for Power Plus rig 3 FLUES
7 20009444 Blank end-flange kit for hydraulic manifold 1 21 4030312 Flues collector kit 125 for 100 kW 2

LOW ENERGY pump kit (front) 22 20062337 Condensate drain kit 125 with end cap 1
5 20075526*** 5
for Power Plus rig (ErP compliant) 23 4030311 Flues collector kit 125 for 50 kW 1

* I.N.A.I.L. optional component (I.N.A.I.L. = Italian safety certification Institute).


** OPTIONAL component.
*** Pump kit (front), non-ERP compliant, is available, as an alternative option, only for EXTRA-EC countries. See section ACCESSORIES.

note: the whole range of components, accessories and flues for Power Plus applications is listed in this guide in the section ACCESSORIES

24
500-series CAASCADE and STAND ALONE
Linear cascade configuration - 300 kW (wall-hung or free-standing)

21

125 125
125
22

3 2 24

9
POWER
PLUS 100 S
POWER
PLUS 100 S
POWER
PLUS 100 M 13

11

7
5

10
4 15

This scheme has only an indication purpose

diagram diagram
code description qty code description qty
ref. ref.
BOILERS 7 20009444 Blank end-flange kit for hydraulic manifold 1
2 20019200 Power Plus 100 M 1 9 20009467 Hydraulic header/separator (250-460 kW) 1
3 20019309 Power Plus 100 S 2 10 20009471 Hydraulic manifold (150 - 400 kW) 1
USER INTERFACE 13 20009475* I.N.A.I.L. safety kit (400 kW max.) 1
24 1102379** Remote control 1 15 20009483** Gas safety cut-off valve (580 kW max.) 1
HYDRAULIC COMPONENTS and SAFETY DEVICES SUPPORTS for LINEAR WALL-HUNG or FREE-STANDING MOUNTING

Hydraulic manifold kit up to 400 kW 11 20009472 Power Plus rig (front mounting) 3
4 20009439 3
for Power Plus rig FLUES

LOW ENERGY pump kit (front) 21 4030312 Flues collector kit 125 for 100 kW 3
5 20075526*** 6
for Power Plus rig (ErP compliant) 22 20062337 Condensate drain kit 125 with end cap 1

* I.N.A.I.L. optional component (I.N.A.I.L. = Italian safety certification Institute).


** OPTIONAL component.
*** Pump kit (front), non-ERP compliant, is available, as an alternative option, only for EXTRA-EC countries. See section ACCESSORIES.

note: the whole range of components, accessories and flues for Power Plus applications is listed in this guide in the section ACCESSORIES

25
Power Plus

Linear cascade configuration - 350 kW (wall-hung or free-standing)

22 21 23

125
125 125
125
24

3 1

13 9
POWER POWER POWER POWER
PLUS 100 S PLUS 100 S PLUS 100 S PLUS 50 M

11

5 7

15
10

This scheme has only an indication purpose

diagram diagram
code description qty code description qty
ref. ref.
BOILERS 9 20009467 Hydraulic header/separator (250-460 kW) 1
1 20019155 Power Plus 50 M 1 10 20009471 Hydraulic manifold (150 - 400 kW) 1
3 20019309 Power Plus 100 S 3 13 20009475* I.N.A.I.L. safety kit (400 kW max.) 1
USER INTERFACE 15 20009483** Gas safety cut-off valve (580 kW max.) 1
24 1102379** Remote control 1 SUPPORTS for LINEAR WALL-HUNG or FREE-STANDING MOUNTING
HYDRAULIC COMPONENTS and SAFETY DEVICES 11 20009472 Power Plus rig (front mounting) 4
4 20009439 Hydraulic manifold kit up to 400 kW for Power Plus rig 4 FLUES
7 20009444 Blank end-flange kit for hydraulic manifold 1 21 4030312 Flues collector kit 125 for 100 kW 3

LOW ENERGY pump kit (front) 22 20062337 Condensate drain kit 125 with end cap 1
5 20075526*** 7
for Power Plus rig (ErP compliant) 23 4030311 Flues collector kit 125 for 50 kW 1

* I.N.A.I.L. optional component (I.N.A.I.L. = Italian safety certification Institute).


** OPTIONAL component.
*** Pump kit (front), non-ERP compliant, is available, as an alternative option, only for EXTRA-EC countries. See section ACCESSORIES.

note: the whole range of components, accessories and flues for Power Plus applications is listed in this guide in the section ACCESSORIES

26
500-series CAASCADE and STAND ALONE
Linear cascade configuration - 400 kW (wall-hung or free-standing)

22 21

24
125 125
125 125

3 2
9
POWER POWER POWER 13
11 PLUS 100 S PLUS 100 S PLUS 100 S
POWER
PLUS 100 M

5 7

10
4 15

This scheme has only an indication purpose

diagram diagram
code description qty code description qty
ref. ref.
BOILERS 7 20009444 Blank end-flange kit for hydraulic manifold 1
2 20019200 Power Plus 100 M 1 9 20009467 Hydraulic header/separator (250-460 kW) 1
3 20019309 Power Plus 100 S 3 10 20009471 Hydraulic manifold (150 - 400 kW) 1
USER INTERFACE 13 20009475* I.N.A.I.L. safety kit (400 kW max) 1
24 1102379** Remote control 1 15 20009483** Gas safety cut-off valve (580 kW max) 1
HYDRAULIC COMPONENTS and SAFETY DEVICES SUPPORTS for LINEAR WALL-HUNG or FREE-STANDING MOUNTING

Hydraulic manifold kit up to 400 kW 11 20009472 Power Plus rig (front mounting) 4
4 20009439 4
for Power Plus rig FLUES

LOW ENERGY pump kit (front) 21 4030312 Flues collector kit 125 for 100 kW 4
5 20075526*** 8
for Power Plus rig (ErP compliant) 22 20062337 Condensate drain kit 125 with end cap 1

* I.N.A.I.L. optional component (I.N.A.I.L. = Italian safety certification Institute).


** OPTIONAL component.
*** Pump kit (front), non-ERP compliant, is available, as an alternative option, only for EXTRA-EC countries. See section ACCESSORIES.

note: the whole range of components, accessories and flues for Power Plus applications is listed in this guide in the section ACCESSORIES

27
Power Plus

Back-to-back free-standing cascade configuration - 150 kW

23 20

125 160
22

1 24 3

13 8
POWER
PLUS 50 M POWER
PLUS 50 M
11

5 7
6
14
10

4
12

This scheme has only an indication purpose

diagram diagram
code description qty code description qty
ref. ref.
BOILERS SUPPORTS for BACK-TO-BACK FREE-STANDING MOUNTING
160
1
125
20019155 Power Plus 50 M 1 11 20009472 Power Plus rig (front mounting) 1
3 20019309 Power Plus 100 S 1 12 20009474 Rear mounting kit for Power Plus free-standing rig 1
USER INTERFACE FLUES
24 1102379** Remote control 1 20 20017306 Flues collector kit for frontal/rear installation 1
HYDRAULIC
POWER COMPONENTS and SAFETY DEVICES 21 4030312 Flues collector kit 125 for 100 kW 1
PLUS 50 M POWER
PLUS 50 M
4 20009439 Hydraulic manifold kit up to 400 kW for Power Plus rig 1 22 20062337 Condensate drain kit 125 with end cap 2
7 20009444 Blank end-flange kit for hydraulic manifold 1 23 4030311 Flues collector kit 125 for 50 kW 1

LOW ENERGY pump kit (front)


5 20075526*** 1
for Power Plus rig (ErP compliant) 21
LOW ENERGY pump kit (rear)
6 20075527*** 2
for Power Plus rig (ErP compliant) 125

8 20009466 Hydraulic header/separator (150-200 kW) 1


10 20009471 Hydraulic manifold (150 - 400 kW) 1
20
13 20009475* I.N.A.I.L. safety kit (400 kW max.) 1
22
14 20009482** Gas safety cut-off valve (230 kW max.) 1
125 160

* I.N.A.I.L. optional component (I.N.A.I.L. = Italian safety certification Institute).


** OPTIONAL component.
*** Pump kits (front and rear), non-ERP compliant, are available, as an alternative option, 23 Flueing layout
only for EXTRA-EC countries. See section ACCESSORIES.

note: the whole range of components, accessories and flues for Power Plus applications is listed in this guide in the section ACCESSORIES

28
500-series CAASCADE and STAND ALONE
Back-to-back free-standing cascade configuration - 200 kW

21 20

160
125
22

2 24 3

13 8
POWER POWER POWER
PLUS 100 M PLUS 100 S PLUS 100 M
11

5 7
6
14
10
4
12

This scheme has only an indication purpose

diagram diagram
code description qty code description qty
ref. ref.
BOILERS SUPPORTS for BACK-TO-BACK FREE-STANDING MOUNTING
2 20019200 Power Plus 100 M
160 1 11 20009472 Power Plus rig (front mounting) 1
125
3 20019309 Power Plus 100 S 1 12 20009474 Rear mounting kit for Power Plus free-standing rig 1
USER INTERFACE FLUES
24 1102379** Remote control 1 20 20017306 Flues collector kit for frontal/rear installation 1
HYDRAULIC COMPONENTS and SAFETY DEVICES 21 4030312 Flues collector kit 125 for 100 kW 2
4
POWER 20009439 Hydraulic manifold kit up to 400 kW forPOWER
Power Plus rig POWER
1 22 20062337 Condensate drain kit 125 with end cap 2
PLUS 100 M PLUS 100 S PLUS 100 M

7 20009444 Blank end-flange kit for hydraulic manifold 1

LOW ENERGY pump kit (front)


5 20075526*** 2
for Power Plus rig (ErP compliant) 21
LOW ENERGY pump kit (rear)
6 20075527*** 2
for Power Plus rig (ErP compliant)
125

8 20009466 Hydraulic header/separator (150-200 kW) 1


10 20009471 Hydraulic manifold (150 - 400 kW) 1
13 20009475* I.N.A.I.L. safety kit (400 kW max.) 1 20
22
14 20009482** Gas safety cut-off valve (230 kW max.) 1
125 160
* I.N.A.I.L. optional component (I.N.A.I.L. = Italian safety certification Institute).
** OPTIONAL component.
*** Pump kits (front and rear), non-ERP compliant, are available, as an alternative option, Flueing layout
only for EXTRA-EC countries. See section ACCESSORIES.

note: the whole range of components, accessories and flues for Power Plus applications is listed in this guide in the section ACCESSORIES

29
Power Plus

Back-to-back free-standing cascade configuration - 250 kW

21 23 20

125 160
22 125

3 1 24

13 9
POWER POWER POWER POWER
PLUS 100 S PLUS 50 M PLUS 100 S PLUS 50 M

11
POWER
PLUS 100 S

5 7

6
15
10
4
12

This scheme has only an indication purpose

diagram diagram
code description qty code description qty
ref. ref.
BOILERS SUPPORTS for BACK-TO-BACK FREE-STANDING MOUNTING
1 20019155 Power Plus 50 M 1 11 20009472 Power Plus rig (front mounting) 2
3 20019309 Power Plus 100 S 2 12 20009474 Rear mounting kit for Power Plus free-standing rig 2
125 160
125
USER INTERFACE FLUES
24 1102379** Remote control 1 20 20017306 Flues collector kit for frontal/rear installation 1
HYDRAULIC COMPONENTS and SAFETY DEVICES 21 4030312 Flues collector kit 125 for 100 kW 2
4 20009439 Hydraulic manifold kit up to 400 kW for Power Plus rig 2 22 20062337 Condensate drain kit 125 with end cap 2
POWER POWER POWER POWER
PLUS 100 S
7 20009444
PLUS 50 M Blank end-flange kit for hydraulic manifold
PLUS 100 S PLUS 50 M 1 23 4030311 Flues collector kit 125 for 50 kW 1

LOW ENERGY pump kit (front) POWER

5 20075526*** PLUS 100 S


3
for Power Plus rig (ErP compliant) 21
LOW ENERGY pump kit (rear)
5 20075527*** 2
for Power Plus rig (ErP compliant)
125

9 20009467 Hydraulic header/separator (250-460 kW) 1


20
10 20009471 Hydraulic manifold (150 - 400 kW) 1
13 20009475* I.N.A.I.L. safety kit (400 kW max.) 1
15 20009483** Gas safety cut-off valve (580 kW max.) 1 125 125 160

* I.N.A.I.L. optional component (I.N.A.I.L. = Italian safety certification Institute).


** OPTIONAL component.
*** Pump kits (front and rear), non-ERP compliant, are available, as an alternative option, 22 23 Flueing layout
only for EXTRA-EC countries. See section ACCESSORIES.

note: the whole range of components, accessories and flues for Power Plus applications is listed in this guide in the section ACCESSORIES

30
500-series CAASCADE and STAND ALONE
Back-to-back free-standing cascade configuration - 300 kW

21 20

22 125 160
125

24
3 2
13 9

POWER POWER POWER POWER


11 PLUS 100 S PLUS 100 M PLUS 100 S PLUS 100 M

POWER
PLUS 100 S

5 7
6
15
10
4 12

This scheme has only an indication purpose

diagram diagram
code description qty code description qty
ref. ref.
BOILERS SUPPORTS for BACK-TO-BACK FREE-STANDING MOUNTING
2 20019200 Power Plus 100 M 1 11 20009472 Power Plus rig (front mounting) 2
3 20019309 Power Plus 100 S 2 12 20009474 Rear mounting kit for Power Plus free-standing rig 2
125 160
125
USER INTERFACE FLUES
24 1102379** Remote control 1 20 20017306 Flues collector kit for frontal/rear installation 1
HYDRAULIC COMPONENTS and SAFETY DEVICES 21 4030312 Flues collector kit 125 for 100 kW 3
4 20009439 Hydraulic manifold kit up to 400 kW for Power Plus rig 2 22 20062337 Condensate drain kit 125 with end cap 2
POWER POWER POWER POWER
PLUS 100 S
7 20009444
PLUS 100 M
Blank end-flange kit for hydraulic manifold
PLUS 100 S PLUS 100 M 1
POWER
LOW ENERGY pump kit (front) PLUS 100 S

5 20075526*** 4
for Power Plus rig (ErP compliant) 21
LOW ENERGY pump kit (rear)
6 20075527*** 2
for Power Plus rig (ErP compliant)
125

9 20009467 Hydraulic header/separator (250-460 kW) 1


20
10 20009471 Hydraulic manifold (150 - 400 kW) 1
13 20009475* I.N.A.I.L. safety kit (400 kW max.) 1
15 20009483** Gas safety cut-off valve (580 kW max.) 1 125 125 160

* I.N.A.I.L. optional component (I.N.A.I.L. = Italian safety certification Institute).


** OPTIONAL component.
*** Pump kits (front and rear), non-ERP compliant, are available, as an alternative option, 22 Flueing layout
only for EXTRA-EC countries. See section ACCESSORIES.

note: the whole range of complonents, accessories and flues for Power Plus applications is listed in this guide in the section ACCESSORIES

31
Power Plus

Back-to-back free-standing cascade configuration - 350 kW

21 23 20

160
22 125 125

24
3 1

13 9
POWER POWER POWER POWER
PLUS 100 S PLUS 50 M PLUS 100 S PLUS 50 M

11
POWER POWER
PLUS 100 S PLUS 100 S

5 7
6 15
10
4
12

This scheme has only an indication purpose

diagram diagram
code description qty code description qty
ref. ref.
BOILERS SUPPORTS for BACK-TO-BACK FREE-STANDING MOUNTING
1 20019155 Power Plus 50 M 1 11 20009472 Power Plus rig (front mounting) 2
3 20019309
125
Power
160Plus 100 S 3 12 20009474 Rear mounting kit for Power Plus free-standing rig 2
125
USER INTERFACE FLUES
24 1102379** Remote control 1 20 20017306 Flues collector kit for frontal/rear installation 1
HYDRAULIC COMPONENTS and SAFETY DEVICES 21 4030312 Flues collector kit 125 for 100 kW 3

POWER
4 20009439 Hydraulic manifold kit up to 400 kWPOWER
for Power Plus rig
POWER
2 22 20062337 Condensate drain kit 125 with end cap 2
POWER
LUS 100 S PLUS 50 M PLUS 100 S PLUS 50 M
7 20009444 Blank end-flange kit for hydraulic manifold 1 23 4030311 Flues collector kit 125 for 50 kW 1
POWER POWER
LOW ENERGY pump kit (front) PLUS 100 S PLUS 100 S
5 20075526*** 3
for Power Plus rig (ErP compliant) 22 21
LOW ENERGY pump kit (rear)
6 20075527*** 4
for Power Plus rig (ErP compliant) 125 125

9 20009467 Hydraulic header/separator (250-460 kW) 1 20


10 20009471 Hydraulic manifold (150 - 400 kW) 1
13 20009475* I.N.A.I.L. safety kit (400 kW max.) 1
15 20009483** Gas safety cut-off valve (580 kW max.) 1 125 125 160

* I.N.A.I.L. optional component (I.N.A.I.L. = Italian safety certification Institute).


** OPTIONAL component.
*** Pump kits (front and rear), non-ERP compliant, are available, as an alternative option, 23 Flueing layout
only for EXTRA-EC countries. See section ACCESSORIES.

note: the whole range of components, accessories and flues for Power Plus applications is listed in this guide in the section ACCESSORIES

32
500-series CAASCADE and STAND ALONE
Back-to-back free-standing cascade configuration - 400 kW

21 20

125 160
22 125

24
3 2

POWER
PLUS 100 S
POWER
PLUS 100 M
13 9 POWER
PLUS 100 S
POWER
PLUS 100 M

11 POWER POWER
PLUS 100 S PLUS 100 S

5 7
6 15
10
4
12

This scheme has only an indication purpose

diagram diagram
code description qty code description qty
ref. ref.
BOILERS SUPPORTS for BACK-TO-BACK FREE-STANDING MOUNTING
2 20019200 Power Plus 100 M 1 11 20009472 Power Plus rig (front mounting) 2
3 20019309 Power Plus 100 S 3 12 20009474 Rear mounting kit for Power Plus free-standing rig 2
160
125 USER INTERFACE
125 FLUES
24 1102379** Remote control 1 20 20017306 Flues collector kit for frontal/rear installation 1
HYDRAULIC COMPONENTS and SAFETY DEVICES 21 4030312 Flues collector kit 125 for 100 kW 4
4 20009439 Hydraulic manifold kit up to 400 kW for Power Plus rig 2 22 20062337 Condensate drain kit 125 with end cap 2
POWER POWER
PLUS 100 S 7 20009444
PLUS 100 M Blank end-flange kit for hydraulic manifold
POWER
PLUS 100 S
POWER
PLUS 100 M 1

LOW ENERGY pump kit (front)


5 20075526*** POWER POWER
PLUS 100 S 4
for Power Plus rig (ErP compliant) PLUS 100 S

22 21
LOW ENERGY pump kit (rear)
6 20075527*** 4
for Power Plus rig (ErP compliant)
125 125
9 20009467 Hydraulic header/separator (250-460 kW) 1 20
10 20009471 Hydraulic manifold (150 - 400 kW) 1
13 20009475* I.N.A.I.L. safety kit (400 kW max.) 1
15 20009483** Gas safety cut-off valve (580 kW max.) 1
125 125 160
* I.N.A.I.L. optional component (I.N.A.I.L. = Italian safety certification Institute).
** OPTIONAL component.
*** Pump kits (front and rear), non-ERP compliant, are available, as an alternative option, Flueing layout
only for EXTRA-EC countries. See section ACCESSORIES.

note: the whole range of components, accessories and flues for Power Plus applications is listed in this guide in the section ACCESSORIES

33
Power Plus

Flue guidance: dimensions inside the plant-room


125 and 160, Stand-alone configuration

125 Linear, wall hung and free standing configuration

160 Linear, wall hung and free standing configuration

34
500-series CAASCADE and STAND ALONE
125 Back-to-back up to 200 kW configuration

125 Back-to-back up to 400 kW configuration

Lateral views

35
Power Plus

Flue guidance: flue gas outlet and combustion air intake


Air intake and vent pipe sizes
The high-head fan of Power Plus gives a residual head of 560 Pa in This enables long flue pipes lenghts using reduced diameter flue pipe,
the point B, that becomes 380 Pa in the point A. as detailed in the table below.

b Measurements obtained using the pipes with which the boiler was homologated, downstream from the flue gas manifold (from point A on).

Maximum length of pipe (m)


with with with with
TOTAL installed power (kW)
50 mm * 125 mm 160 mm 200 mm
50 30 55 60 100
100 - 55 60 100
150 - 55 60 100
200 - 55 60 100
250 - 35 55 100
300 - 30 50 100
350 - 25 50 100
400 - 20 50 80
450 - - 40 60
500 - - 30 50
550 - - 30 40
600 - - 25 35
650 - - - 30
700 - - - 30
750 - - - 30
800 - - - 30

Equivalent length for other elements of pipe (m)


with with with with
Type of element
50 mm * 125 mm 160 mm 200 mm
45 bend 1 1,2 1,7 1,7
87 bend 3 5 7,5 7,5
T joint 3 4 7,5 7,5
* The same measures apply to 80 mm pipe

36
500-series CAASCADE and STAND ALONE
Preparing the condensate drain
The condensate produced by the boiler during normal operation must
be drained at atmospheric pressure and must conform to any current i3
i
standards and law applicable.
b Install a neutraliser where required by law.
b Specific pipes for condensing boilers must be used.
For installation, follow the instructions provided with the kit.
Drain trap along the drain pipe:
If the vertical or horizontal section of the drain pipe needs to be
extended by more than 4 metres, a drain trap must be installed at the Minimum
foot of the pipe. The useful height of the drain trap must be at least 300 distance
metres. The discharge of the drain trap must then be connected to the 300 mm
sewerage system.
The condensate produced by the boiler during normal operation must
be drained at atmospheric pressure and must confirm to any current
standards and applicable legislation

Minimum
distance i>3%
10 mm Mains
Condense collector sewers
(at atmospheric pressure)

Example of Hs 50 kW with 1 x 50 mm Example of Hs 100 kW with 2 x 50 mm Example of Hs 150 kW with 3 x 50 mm

Modello 50 M Model 100 M Models 50 M + 100 S


Model 100 M DEP

Minimum dimensions of the compartment


Minimum dimensions of the compartment for the passage of two flues, diameter 50 mm Minimum dimensions of the compartment
for the passage of one flue, diameter 50 mm for the passage of three flues, diameter 50 mm
Circle Rectangular
compartment compartment Square Rectangular
Circle Square compartment compartment
compartment compartment
20 50 20 50 20 230 mm
160 mm 160 mm
20 50 20
20 50 20

71 mm 63 mm
90 mm
90 mm

20 20

20 50 20 50 20 50 20
50mm 50mm 20 50 20 50 20
160 mm
20 50 20 50 20

37
Power Plus
Examples of installations - Configuration with loop pump and valves on the heating units

38
500-series CAASCADE and STAND ALONE
Examples of installations - Multiple C.H. zones with individual pumps and D.H.W. tank

39
Power Plus Cascade
Examples of installations - Multiple C.H. zones, solar integration for D.H.W. production
and swimming pool

40
500-series CAASCADE and STAND ALONE
Examples of installations - Multiple C.H. zones, solar integration for D.H.W. production

41
Power Plus Cascade

Examples of installations - Multiple C.H. zones, solar integration for D.H.W. production

42
500-series CAASCADE and STAND ALONE
Examples of installations - D.H.W. production in case of typical commercial systems.
Integrated solution with high efficiency cascade heat generator and solar thermal

43
Power Plus Cascade

Examples of installations - Centralized plant room with back-to-back system

44
500-series CAASCADE and STAND ALONE
Examples of installations - Solution for Multiple Dwellings:
Centralized solar thermal system and individual D.H.W. production with understations

45
46
500-series BOX
500-series
Pre-assembled BOX

47
Power Plus BOX
The efficiency of our condensing technology
Beretta Power Plus Box is a pre-assembled box based on the 500-series thermal group: condensing, pre-mixed, air blown and modulating
combustion system.

Available for INDOOR and OUTDOOR installations.

Power Plus Box range achieved an Efficiency


according to European Directive EEC 92/42
Gas Directive EEC 90/396
Low voltage Directive EEC 89/336
Electromagnetic compatibility Directive EEC 73/23

The range
STAND ALONE models models for CASCADE

500-series BOX
POWER PLUS LE 85 SYS POWER PLUS BOX 150 POWER PLUS BOX 100 SE
Module consisting of 2 heat generators for Module consisting of 3 heat generators for Module consisting of 2 heat generators for
heating and DHW production systems. heating and DHW production systems. Heat heating and DHW production systems and
Heat input from 14,4 to 76,7 kW. input from 15 to 135 kW. including safety devices and hydraulic
separator. Heat input from 14,4 to 76,7 kW.
POWER PLUS LE HI 115 SYS POWER PLUS BOX 200
Module consisting of 3 heat generators for Module consisting of 4 heat generators for
heating and DHW production systems. heating and DHW production systems. Heat
Heat input from 14,4 to 115 kW. input from 15 to 180 kW.

LE HI 115 SYS BOX 200 BOX 100 SE

Characteristics and advantages at a glance


Possibility to combine Power Plus BOX water storage system as it simultaneously flame burner combination, allowing Power
(500-series) in cascade to reach up to 3 controls three different circuits, each Plus BOX to achieve Class 5 of the UNI EN
MW of total power. operating at a different temperature. 483 standard (best European category in
All the BOX are already assembled and Power Plus BOX units are designed to ecological terms).
tested in our factories. provide water to 3 different circuits at Water drain built-in as standard in the boiler
In-line and back-to-back cascade different temperatures either supplied as for each heating unit.
installation of multiple Box units is possible. direct take offs or via a header system Built-in temperature control and external
Compact in-line solution. utilizing controls as required. With this probe as standard.
All the BOX units have, already fitted and in mind suggested usage are DHW, Can work with water-glycole mixture up to
connected, water and gas manifolds, flue High Temperature (heating) and Low 50%.
exhaust duct (with anti-return clapet on Temperature (under-floor heating). It is Automatic burner ignition sequence rever-
each unit) and condensate drain. possible to add up to further 8 zones with sal.
These units boast latest generation the use of specific accessories. Anti-legionnaires disease function (only
electronic control, modularity and Modulating and modular power regulation. available with room-control kit).
versatility, thus ensuring the installer a quick Minimum polluting emissions, thanks to the Frost-protection system.
connection to any type of heating and hot controlled pre-mix burner and the micro-

49
Power Plus BOX

Ten reasons why a Power Plus BOX system is the logical choice
Beretta Power Plus BOX, thanks to its modularity and intelligent features, can be considered the best solution for light commercial applications,
both in the new buildings and as replacement of old floor standing boilers. More than one box can be connected in cascade (except SIS models)
so to obtain extremely high powers.

Maximum efficiency at any time Maximum use of space


The efficiency of a Power Plus BOX is significantly higher than a The in-BOX cascade system of Power Plus BOX range is designed
traditional single boiler installation with the same output. In fact, by to provide a space-saving and versatile solution for large domestic
automatically controlling the number of boilers in operation, the system properties or light commercial buildings.
can optimise the heat supply according to demand at any particular
time. For instance in spring and autumn, when the heat request is
lower, or in buildings like hotels and restaurants, where the heat request Maximum flexibility
is not constant, the system can switch individual boilers on and off, Power Plus BOX is suitable both for indoor and outdoor installations
ensuring the maximum efficiency. thanks to its zync-coated, painted box.

Maximum peace of mind Maximum ease of installation


Power Plus BOX is more reliable than a traditional individual boiler The combustion groups come already assembled in the BOX, together
installation. As each combustion unit of the BOX can be individually with the water, gas, condensate and flue manifolds. Everything is pre-
serviced and maintained, in the event of a fault or maintenance on one tested in the factory. The SIS models have also the hydraulic separator
combustion unit, the other boilers of the cascade are still able to operate fitted and connected in the same box of the combustion groups.
without a total loss of heating. The integrated flue collector contributes to keeping the total height of
the cascade to compact dimentions.

Maximum savings
High efficiency of the in-BOX cascade and top condensing technology Maximum reliability
of the boilers allow you to save so much energy in daily use that the All the components are assembled and tested in our factories, thus
costs of the heating system are recovered in a few years. In addition, granting the maximum levels of quality.
reduced installation time and quick servicing result in precious savings The multi-combustion configuration of most of the Power Plus BOX
for the end user. guarantees that the end user benefits of continuity of service at any
time.
The extensive range of accessories carefully selected by Beretta helps
Maximum ease of servicing the designer/installer, covering the needs of most of the installations.
Power Plus BOX range is designed so that all components can be easily
serviced and maintened from the front. Moreover, each boiler of the
cascade can be individually serviced and maintained, while the other Maximum commitment to the environment
boilers of the cascade are still able to operate. Power Plus BOX range achieved Class 5 of the UNI EN 483 standard
(best European category in ecological terms), thanks to condensing
combustion with controlled pre-mix burner and micro-flame burner
Maximum range of modulation combination.
Up to 60 combustion units can be cascaded, so as to reach up to 3 MW A Power Plus BOX can also control automatically the number of boilers
of power, with a modulation down to only 16 kW. in operation according to heat demand, saving energy and reducing
polluting emissions.

50
Flue and installation guidance
Power Plus Box flue exhaust
The following guidance refers to the flue options of the Beretta Power
Plus Box 500-series (except SIS models).
Local regulations apply and must be referred to.

Flue drain for INDOOR and OUTDOOR installations


The Beretta Power Plus BOX, suitable for indoor and outdoor of the cascade. As a general rule, it is recomended not to go over 800
applications, are pre-assembled with the 160 mm flue pipe (in PPtl), kW Hs (flue side). Over this value it is suggested to built the exhaust
inside the box. In the zync-coated, painted box are two female 160 mm flue chimney and get into a larger diameter duct (e.g. 200mm). The
outlets, on each side, through which it is possible to discharge the flues necessary connections (flue + condensate) are provided in a specific kit
directly to terminal flue chimney, or connecting to other heat generators (see relevant section).

500-series BOX
2 x 160 mm
with one plug

Beretta Power Plus BOX cascade


example of cascade installation of 600 kW

BOX 200 BOX 200 BOX 200 Hydraulic Separator

51
Power Plus BOX

Flue and installation guidance

BOX structure
Integrated flue
Given the extremely low flue temperatures, it is possible to use duct 160mm
plastic (PP) flue ducts.
Power Plus BOX integrates not only the 160mm flues duct, but
also the clapet valves necessary to prevent the back-flow of the
combustion products in those thermal groups that are off. Clapet valves

Gas manifold

Flow manifold

Return manifold

Installation tips

PP pipe
Example of a cascade application with the condensate drain and initial flue connections. 160mm
The condensate drain kit is compulsory whenever the vertical pipe length is over 4 m.

PP 90 bend
160mm

PP condensate drain
kit 160mm

Example of a 200 kW single-box application, for indoor installation with the direct management of three circuits. Please refer to the
relevant section of this document for a complete overview of all the available accessories.

52
Example of a single-box 200 kW installation with inverse return.

500-series BOX
Example of a cascade installation of a total of 600 kW with direct return.

Remote control
Each cascade can be monitored and fully controlled from remote,
thanks to several devices (remote control, MOD BUS, etc.).The remote
control allows a maximum distance of 100 m and it gives the possibility
of setting the timings for the ON/OFF, the weekly programming of the
circuit and the anti-legionnaires disease prevention function.

53
Power Plus BOX - stand alone

Floor-standing, modular condensing boilers complete


with hydraulic collectors and hydraulic header/separator,
gas collectors, flues collectors in plastic with clapet and
condensate drain kit.
Suitable only for stand-alone application.
Stainless steel BOX with IPx4D protection and insulation,
specifically designed for OUTDOOR installation.
It can be installed INDOOR as well.
Efficiency according to European Directive EEC 92/42.
Minimum polluting emissions: class 5 (UNI EN 483).
Climatic curves on board.
Flue temperature of only max 3C above the return water
temperature.
Maximum ease of installation.
All models are provided with a Low Energy main pump and
a two-ways valve for each heat exchanger.
Possibility to integrate the secondary pumps inside the BOX (as
optional accessory, see in the section ACCESSORIES).

BOX for OUTDOOR / INDOOR installation


DIMENSIONS
INPUT INPUT
CODE GAS MODEL HWD
(kW) Hs (kW) Hi
(mm)

20107448 NG POWER PLUS LE 85 SYS 1.5301.250650 85 77

20107449 NG POWER PLUS LE HI 115 SYS 1.5301.250650 128 115

note: The whole range of components, accessories and flues for Power Plus BOX 500-series is listed in this guide in the section ACCESSORIES.

POWER PLUS LE 85 SYS POWER PLUS LE HI 115 SYS

1 1

2 2
3 3

54
D L

R 150
G
H

1041
SC

500-series BOX
433

104

DESCRIPTION POWER PLUS LE 85 SYS POWER PLUS LE HI 115 SYS

Boiler type B23, B53


Heat input (Hs) kW 85,2 127,8
Heat input (Hi) kW 76,7 115
Nominal heat output (80-60C) kW 75,3 112,9
Nominal heat output (50-30C) kW 82,5 123,8
Minimum heat input (Hs) kW 16 16
Minimum heat input (Hi) kW 14,4 14,4
Efficiency according European
Directive EEC 92/42

Efficiency at nominal output (80-60C) (HI) % 98,2
Efficiency at nominal output (50-30C) (HI) % 107,7
Efficiency at partial load 30% (80-60C) (HI) % 98,7
Efficiency at partial load 30% (50-30C) (HI) % 108,7
Emissions
NOx class 5
CO d.a.f. min-max less than mg/kWh 10/80
Flue gas temperature C T return + MAX 2,5 C
Central heating
Maximum pressure bar 6
Adjustable CH water temperature range C 20/80
Max condensate production l/h 11,1 16,6
Electrical
Power supply V-Hz 230-50
Maximum power consumption W 310 359
Dimensions, weight, gas
Boiler dimensions (H x L x D) mm 1530 x 1250 x 650
Net weight (empty) kg 180 220
Water content l 10 15
Gas category II2H3+
Available gas versions NG/LPG
G (Gas manifolds) 2
M/R (flow and Return manifolds) 2 / 2
SC (Condensate manifolds) mm 50
(Flue header outlet) mm 125

55
Power Plus BOX - cascade

Floor-standing, modular condensing boilers complete with


hydraulic collectors, gas collectors, flues collectors in PPtl
with clapet (non-return valve), condensate drain kit and
embedded Low Energy shunt pumps.
Zync coated steel BOX specifically painted both for OUTDOOR
and INDOOR installation, with ventilation air intake.
Efficiency according to European Directive
EEC 92/42.
Minimum polluting emissions: class 5 (UNI EN 483).
Climatic curves on board.
Possibility to cascade more than one appliance to reach up
to 3.000 kW.
Index of electrical protection IPX4D
Electronic cascade control on board.
LPG gas conversion kit on board.

BOX for OUTDOOR / INDOOR installation


DIMENSIONS
INPUT INPUT
CODE GAS MODEL HWD
(kW) Hs (kW) Hi
(mm)
ONLY HEATING

20071998 NG POWER PLUS BOX 150 (1) 1.5301.250650 150 135

20071999 NG POWER PLUS BOX 200 (1) 1.5301.250650 200 180

20072002 NG POWER PLUS BOX 100 SE (2) 1.5301.250650 100 90

(1) Power Plus BOX boilers are equipped with the blind flanges kit for 500-series (code 20075887) and with the Power Plus junction kit for cascade
(code 20074998) for cascade installation. See the section ACCESSORIES
(2) The thermal module Power Plus BOX SE is complete with hydraulic separator, safety-devices up to 300kW, and safety gas cut-off valve and can be installed in
stand-alone or in cascade applications with one Power Plus BOX 150 or one Power Plus BOX 200. In case of stand-alone application it is possible to buy the
blind flanges kit for 500-series (code 20075887). See the section ACCESSORIES

POWER PLUS BOX 150 POWER PLUS BOX 200 POWER PLUS BOX 100 SE
Error

Error
RESET

RESET
On

On

5.5
bar

56
BOX 100 SE BOX 150/200 BOX 150/200/100 SE

650 660 1250 1250


795
G1 G1
F
M1 171
F
M1 M1
170
450

M2 G
M2 M2
1483

1530
1490
G

1357
1370

1300

195
300

1224
M
R2 R2
M
M R2 M
810

SC

775
220

R1 SC
R1 R1

477
460

R
R R R

260
261

142

500-series BOX
354 296 95
295
650

Power Plus BOX Power Plus BOX Power Plus BOX


DESCRIPTION
150 200 100 SE
Gas - G20 - G30 - G31
Gas category - II2H3+
Boiler type - B23 - B53
Heat input ref. Hs (min-max) kW 16,0 - 150,0 16,0 - 200,0 16,0 - 100,0
Heat input ref. Hi (min-max) kW 14,4 - 134,9 14,4 -179,8 14,4 - 89,9
Nominal heat output (80-60C) (max) kW 132,5 176,6 88,3
Nominal heat output (50-30C) (max) kW 145,3 193,6 96,8
Minimum heat input (Hs) kW 16 16 16
Minimum heat input (Hi) kW 14,4 14,4 14,4
Efficiency according European Directive EEC 92/42 -
Efficiency at nominal output (80-60C) (Hi) % 98,2 98,2 98,2
Efficiency at nominal output (50-30C) (Hi) % 107,7 107,7 107,7
Efficiency at nominal output (60-40C) (Hi) % 106,1 106,1 106,1
Efficiency at partial load 30% (80-60C) (Hi) % 98,7 98,7 98,7
Efficiency at partial load 30% (50-30C) (Hi) % 108,7 108,7 108,7
Efficiency at partial load 30% (60-40C) (Hi) % 106,6 106,6 106,6
Gas Rates
Gas capacity (min - max) G20 Sm3/h 1,5 - 13,8 1,5 - 18,4 1,5 - 9,2
Gas capacity (min - max) G30 kg/h 1 - 9,8 1 - 13,1 1 - 6,5
Gas capacity (min - max) G31 kg/h 1 - 9,7 1 - 12,9 1 - 6.4
Emissions
CO2 at minimum - maximum % 9,0 (G20) - 10,4 (G30-G31)
CO d.a.f. less than (min-max) mg/kWh 11 - 91
Flue gas temperature C T return + MAX 2,5 C
NOx Class 5
Central Heating
Working Pressure (min-max) bar 0,5 - 6
Adjustable CH water temperature range C 20 - 80
Water content l 15 20 70
Max condensate production l/h 20,7 27,6 13,8
Electrical
Power supply V-Hz 230-50 230-50 230-50
Maximum power consumption W 495 660 330
Index of electrical protection IP IPX4D
Dimensions, Weight and Gas
Boiler dimensions (H x W x D) mm 1530 x 1250 x 650
Dry weight kg 310 340 200
Available gas versions - NG / LPG NG / LPG NG / LPG
G (Gas manifolds) 3 DN 80 - PN 6 3 DN 80 - PN 6 3 DN 80 - PN 6
G1 (Gas manifolds) - - 2 (threaded)
M/R (Flow and Return flanged manifolds) 5 DN 125 - PN 6 5 DN 125 - PN 6 5 DN 125 - PN 6
M1/M2/R1/R2 (Flow and Return flanged manifolds) 3 DN 80 - PN 6 3 DN 80 - PN 6 3 DN 80 - PN 6
SC (Condensate manifold) mm 50 50 50
F (Flue header Outlet) mm 160 160 160

57
Power Plus BOX

Example of outdoor installation - Multiple C.H. zones with individual pumps


and D.H.W. tank

58
Example of indoor installation - Multiple C.H. zones, solar integration for D.H.W.
production and swimming pool

500-series BOX

59
Power Plus BOX

Example of installation - Centralized system with 500-series Power Plus BOX

60
Example of OUTDOOR installation - Multiple C.H. zones, solar integration for D.H.W.
production and swimming pool

500-series BOX

61
62
1000-series

1000-series
Focus on Technology

63
Power Plus BOX

The structure of the 1000-series


The aim of the 1000-series is that to enhance the output options of Power Plus BOX, increasing the Power density, i.e. the power for each square
centimetre occupied by the heat unit and, as a consequence, by the Box. This is obtained coupling the patented Cuprosteel corrugated helical tube
with a more traditional pipe.

The technology: heat exchanger


While the 500-series heat exchanger is a single coil of the well-known
Cuprosteel, the 1000-series one has two pipes working in parallel, in
the section before the refractory brick.
The outer pipe is the corrugated Cuprosteel, the inner one is pentagonal
and smooth.
The two pipes are hydraulically connected by means of the upper and
lower caps of the heat exchanger assembly, that thus work as a real
hydraulic manifold.

Technical features of each combustion group:


Fan connection
(air/gas mixture inlet)

Flow pipe
Upper heat exchanger header

Burner
Heat exchanger (pentagonal pipe)

Refractory brick
Heat exchanger
(bi-metallic corrugated pipe)

Lower heat exchanger header


Return pipe

Flue and condensate discharge pipe

64
Heat exchanger operation
The air and gas mixture is pushed (A) through the burner, where the
low-NOx combustion process happens (B). The flues so produced
flow through the double-coil of the exchanger, where they heat the A
circulating water (C). In the course of the heat exchanger, condence is
produced (D) and drained out of the combustion engine. An automatic E
air vent purges the air that is in the circulating water (E).

Technical features
C
Power of 128 kW on Hs (115 kW on Hi).
Modulation from 26 to 128 kW with a flat curve of CO2 (9%).
Efficiency: 108,6% at full load, 109% at 0,3 Pn (water temperatures
50C-30C).
Temperature difference between flue and return water: less than
10C.
CO level at Pn: less than 130 mg/kWh. At minimum: less than 23
mg/kWh.
NOx class: 5.
Ebm fan NRG137 low energy series with integrated venturi and high
residual head.
Heat exchanger with wet head: flow manifold, air vent, working D

1000-series
sensors (flow + return), max temperature sensor.
Includes the gas valve and the differential pressure switch.

The structure of the 1000-series

The location of the master board depends


on the models: onboard on 1001 models
and detached for the other models

Totally pre-mixed micro-flame jet burner

Power of 128 kW on Hs (115 kW on Hi)


on each heat exchanger unit

1002-1003-1004 INT/EXT 1001 INT/EXT


for cascade installation only for stand-alone installation

65
Power Plus Box

Efficiency vs. Return Water Temperature


The Power Plus BOX incorporates an extremely efficient heat engine; this results in an extremely low return temperature / flue exhaust gas
temperature (temperature differential); as can be seen in the graph below, the Power Plus BOX achieves a minimum efficiency of 99% at a return
temperature of 60C, that can rise to over 108% depending on the return water temperature. Whats really impressive is that the efficiency begins
to exceed 100% once the return water temperature drops below the dew point.

Hi Efficiency vs. ReturnHiwater


Rendimento vs. Ttemperature of 1000-series
ritorno acqua of Power
Corolla serie 1000Plus Box
Rendimento
Hi Efficiency
Hiat
a 30% Rendimento
Hi Efficiency
Hiat
a 100%
100%

110,0%

108,0%

106,0%

104,0%

102,0%

100,0%

98 0%
98,0%
30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64

Note: From the above diagram it is easy to identify the range of return water temperature where the boiler works in condensing or
non-condensing modes

Rendimento
Hi Efficiency vs. ReturnHiwater
vs. Ttemperature
ritorno acqua Corolla serie
of 1000-series 1000Plus Box
of Power
Rendimento
Hi EfficiencyHi
ata30%
30% Rendimento
Hi Efficiency Hi
at a100%
100%

110,0%

108,0%

106,0%

104,0%

102,0% If return water temperature is


> 52-54 C the boiler works
in NON condensing mode
100,0%
if return water temperature is
< 52- 54 C the boiler works
in condensing mode
98 0%
98,0%
30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64

max T for efficiency > 100% Hi

66
1000-series
Pre-assembled BOX

1000-series BOX

67
Power Plus
Power PlusBOX
BOX(1000-series)
The efficiency of our condensing technology
The efficiency of our condensing technology
Beretta Power Plus BOX is a pre-assembled box based on the 1000-series thermal group: condensing, pre-mixed, air blown and modulating
combustion system.
Available for INDOOR and OUTDOOR installations.
Power Plus BOX range achieved an Efficiency
according to European Directive EEC 92/42
Gas Directive EEC 90/396
Low voltage Directive EEC 89/336
Electromagnetic compatibility Directive EEC 73/23

The range
models for CASCADE STAND ALONE models

POWER PLUS BOX 1002 P INT POWER PLUS BOX 1002 P EXT POWER PLUS BOX 1001 INT
Module made of 2 heat exchanger unit, with Module made of 2 heat exchanger unit, with a Module made of 1 heat exchanger unit, with
a modulating power input from 23 to 230 kW modulating power input from 23 to 230 kW a modulating power input from 23 to 115
(Hi), and equipped with climatic regulation (Hi), and equipped with climatic regulation and kW (Hi), and equipped with climatic
and RS485 connection, for indoor installation. RS485 connection, for outdoor installation. regulation and RS485 connection.
POWER PLUS BOX 1003 P INT POWER PLUS BOX 1003 P EXT Embedded hydraulic separator, for stand
Module made of 3 heat exchanger unit, with Module made of 3 heat exchanger unit, with a alone indoor installation.
a modulating power input from 23 to 345 kW modulating power input from 23 to 345 kW
(Hi), and equipped with climatic regulation and POWER PLUS BOX 1001 EXT
(Hi), and equipped with climatic regulation
RS485 connection, for outdoor installation. Module made of 1 heat exchanger unit, with
and RS485 connection, for indoor installation.
a modulating power input from 23 to 115
POWER PLUS BOX 1004 P INT POWER PLUS BOX 1004 P EXT kW (Hi), and equipped with climatic
Module made of 4 heat exchanger unit, with Module made of 4 heat exchanger unit, with a regulation and RS485 connection.
a modulating power input from 23 to 460 kW modulating power input from 23 to 460 kW Embedded hydraulic separator, for stand
(Hi), and equipped with climatic regulation (Hi), and equipped with climatic regulation and
alone outoor installation.
and RS485 connection, for indoor installation. RS485 connection, for outdoor installation.

1004 P INT 1004 P EXT 1001 EXT

1000-series BOX
Characteristics and advantages at a glance
Possibility to combine Power Plus BOX connection to any type of heating and hot Minimum polluting emissions, thanks to the
(1000-series) in cascade to reach up to 6,9 water storage system as it simultaneously controlled pre-mix burner and the micro-
MW (Hi) of total power. controls three different circuits, each flame burner combination, allowing Power
All the BOX unit are already assembled and operating at different temperatures. Plus to achieve Class 5 of the UNI EN
tested in our factories. Power Plus BOX units are designed to 483 standard (best European category in
High power in compact dimensions provide water to 3 different circuits at ecological terms).
In-line and back-to-back cascade different temperatures either supplied as Water drain built-in as standard in the boiler
installation of multiple BOX units is possible. direct take offs or via a header system for each heating unit.
Compact in-line solution. utilizing controls as required. With this Can work with water-glycole mixture up to
All the BOX units have, already fitted and in mind suggested usage are DHW, 50%.
connected, water and gas manifolds, High Temperature (heating) and Low Automatic burner ignition sequence
flue exhaust connections 110 mm and Temperature (under-floor heating). It is reversal.
condensate drain. possible to add up to further 8 zones with Anti-legionnaires disease function
These units boast latest generation the use of specific accessories. (only available with room-control kit).
electronic control, modularity and Modulating and modular power regulation. Frost-protection system.
versatility, thus ensuring the installer a quick

69
Power Plus BOX

Ten reasons why a Power Plus BOX system is the logical choice
Beretta Power Plus Box, thanks to its modularity and intelligent features, can be considered the best solution for any commercial application from
the smallest to the largest, both in the new buildings and as replacement of old floor standing boilers. More than one box can be connected in
cascade so to obtain extremely higt power.

Maximum efficiency at any time Maximum commitment to the environment


The efficiency of a Power Plus BOX is significantly higher than a Power Plus range achieved Class 5 of the UNI EN 483 standard
traditional single boiler installation with the same output. In fact, by (best European category in ecological terms), thanks to condensing
automatically controlling the number of boilers in operation, the system combustion with controlled pre-mix burner and micro-flame burner
can optimise the heat supply according to demand at any particular combination. A Power Plus Box can also control automatically the
time. For instance in spring and autumn, when the heat request is lower, number of boilers in operation according to heat demand, saving
or in buildings like hotels and restaurants, where the heat request is not energy and reducing polluting emissions.
constant, the system can switch individual boilers on and off, ensuring
the maximum efficiency.
Maximum savings
High efficiency of the in-Box cascade and top condensing technology
Maximum peace of mind of the boilers allow you to save so much energy in daily use that the
Power Plus BOX is more reliable than a traditional individual boiler costs of the heating system are recovered in a few years. In addition,
installation. As each combustion unit of the box can be individually reduced installation time and quick servicing result in precious savings
serviced and maintained, in the event of a fault or maintenance on one for the end user.
combustion unit, the other boilers of the cascade are still able to operate
without a total loss of heating.
Maximum use of space
The in-BOX cascade system of Power Plus BOX range is designed
Maximum ease of installation to provide a space-saving and versatile solution for large domestic
The combustion groups come already assembled in the BOX, together properties or commercial buildings.
with the water, gas, condensate and flue manifolds. Everything is pre-
tested in the factory. The integrated flue collector contributes to keeping
the total height of the cascade to compact dimensions. Maximum reliability
All the components are assembled and tested in our factories, thus
ensuring the maximum levels of quality.
Maximum ease of servicing The multi-combustion configuration of the Power Plus BOX guarantees
Power Plus range is designed so that all components can be easily that the end user is ensured continuity of service at any time.
serviced and maintened from the front. Moreover, each boiler of the The extensive range of accessories carefully selected by Beretta helps
cascade can be individually serviced and maintained, while the other the designer/installer, covering the needs of most of the installations.
boilers of the cascade are still able to operate.

Maximum range of modulation


Maximum flexibility Up to 60 combustion units can be cascaded, so as to reach up to 6,9
Power Plus BOX allows installation INDOOR and OUTDOOR, choosing MW of power (Hi), with a modulation down to only 23 kW.
the model with the standard painted- or stainless- steel case.

70
Flue and installation guidance
The following guidance refers to the flue options of the Beretta Power Plus Box 1000-series. Local regulations apply and must be referred to.

Flue drain for INDOOR installation


The Boxes of 1000-series do not contain any manifold to collect the 200 mm provided as an accessory (refer to the relevant section).
flues. Each combstion engine has instead an individual outlet 110 Please note that for the two-engines box, it is necessary to purchase
mm, to which is possible to connect the collector (in plastic, with clapet), two single-inlet collectors.

900

1000-series BOX

71
Power Plus BOX

Flue and installation guidance


Remote control Compact in-line solution
Each cascade can be monitored and fully controlled from remote, The installation as a whole benefits from high outputs from a compact
thanks to several devices (remote control, MOD BUS, etc.).The remote design. In the example, an installation with eight engines, for a total of
control allows a maximum distance of 100 m and it gives the possibility around 1MW (Hs).
of setting the timings for the ON/OFF, the weekly programming of the
circuit and the anti-legionnaires disease prevention function.

Master PCB
The master PCB (to be purchased separately) manages all the to perform a variety of functions ranging from simple monitoring
combustion groups and it is the core of the net of intelligent devices of the main parameters to the system configuretion of the device
that can be added (additional zones PCB, remote control, etc...). depending on the type of plant which is located downstream of it.
It is delivered together with a set of blind flanges and the outdoor The control panel was designed to enable the user to enter the
sensor to complete the installation. various user modes; each one of these has a set of corresponding
The master PCB of the Power Plus BOX is located in the external functions, activated by pressing a button or combination of two
cabinet. buttons pressed together. Furthermore, each button has a specific
It is possible to operate on the master contro.l panel opening the function depending on the selected user mode.
cover with the plexiglass window. The various buttons on it allow you
500

200 405
72
Hydraulic circuit

CF CF CF
SC SC SC

CL CL CL CL CL CL CL CL CL

CG
CG CG
VE VG
TB
VE VG VE VG VEVG VEVG VE
VG
TB VE VG VE VG TB VEVG
TB TB TB TB TB TB
SA SM SA SM SA SM SA SM SASM SA SM SA SM SA SM SA SM
V V V V V V V V V

PM PM PM PM PM PM PM PM PM
SR SR SR SR SR SR SR SR SR
CM CM CM
CP CP CP CP CP CP CP
CP CP

VI VI VI VI VI VI VI VI VI
CR CR CR

Power Plus Box 1002 P INT Power Plus Box 1003 P INT Power Plus Box 1004 P INT

Key Features Key Features

Optional and external to the thermal


CF Flue collector SC Condensate drain kit
condensing unit 200mm in PPtl
Optional and external to the thermal unit Minimum pressure switch
CL Clapet no-return flues valve PM
110mm - > 110mm in PPtl (differential)
VG Motorized gas valve
SR Return NTC probe NTC type, 10 kOhm
VE Venturi pre-mixing device Allows the total pre-mixing
Max power 80 W - modulating 1200-3600 Included in the thermal unit - fixed low 5000
V Fan CP Pump for single thermal unit
rpm l/h and 4,5 m H2O for single unit, ref. T 21C
SM Flow NTC probe NTC type, 10 kOhm VI Stop valve 3/4 included as standard
Max T lockout: 90C +/- 5C CG Gas pipe 3 flanged pipe PN6, included as standard
TB Lockout thermostat
Max T manual reset: 80C +/- 5C
CM Flow collector 5 flanged pipe PN6, included as standard

1000-series BOX
SA Air vent Jolly type, 3/8connection CR Return collector 5 flanged pipe PN6, included as standard
365
1590
1590

900 1700 750

1250 2260

73
Power Plus BOX - cascade

Floor-standing, modular condensing boilers complete with 5


hydraulic collectors, 3 gas collector, flue outlets 110mm and
condensate drain kit.
Painted steel BOX for indoor installations with ventilation air
intake.
Efficiency according to European Directive EEC 92/42.
Minimum polluting emissions: class 5 (UNI EN 483).
Climatic curves available with Master Control (accessory).
Possibility to cascade up to 60 combustion units.
Electronic cascade control managed by Master Control.
Flue temperature of only around 8C above the return water
temperature.
P ower Plus Box is provided with Low Energy shunt pumps.
Non-return valve (clapet) built-in.

BOX for INDOOR installation


DIMENSIONS
INPUT INPUT
CODE GAS MODEL HWD
(kW) Hs (kW) Hi
(mm)
WITH LOW ENERGY SHUNT PUMPS

20107464 NG POWER PLUS BOX 1002 P INT 1.590900750 256 230

20107472 NG POWER PLUS BOX 1003 P INT 1.5901.700750 384 345

20107478 NG POWER PLUS BOX 1004 P INT 1.5901.700750 511 460

note: The whole range of components, accessories and flues for Power Plus BOX 1000-series is listed in this guide in the section ACCESSORIES

Electronic control for cascade management

CODE DESCRIPTION

Master board (manages the thermal modules cascade;


20067837*
contains blind flanges kit and external probe)

* It is necessary to order a master board for the whole cascade system.

74
Power Plus Box 1002 Power Plus Box 1003 - Power Plus Box 1004

1 2
365

365
1590
1590

1550

1590

850
750 900 750 1700 390 516
908
1250 2260

POWER PLUS POWER PLUS POWER PLUS


specifications
BOX 1002 P INT BOX 1003 P INT BOX 1004 P INT
Boiler type B23, B53, B53P, C13, C33, C53, C63
CE Homologation Number 0085CL0333
Number of burners 2 (x128 kW) 3 (x128 kW) 4 (x128 kW)
Dimension and Connections
HxLxD mm 1590x900x750 1590x1700x750
Empty weight kg 270 380 450
Content of water l 77 123 149
Water manifold 5
Gas manifold 3
Flue manifold mm 110
Condensate drain mm 50
Power and Efficiency
Heat input ref. HHV (min - max) kW 25,5 - 255,6 25,5 - 383,4 25,5 - 511,2

1000-series BOX
Heat input ref. NHV (min - max) kW 23 - 230 23 - 345 23 - 460
Useful heat output (80/60C) kW 226,8 340,2 453,6
Useful heat output (50/30C) kW 249,8 374,7 499,6
Useful heat output (60/40C) kW 239,6 359,4 479,2
Condensate production per hour at 100% (50 - 30C) - gas G20 kg/h 34,4 51,6 68,8
Useful efficiency ref. NHV (80C/60C) % 98,6 98,6 98,6
Useful efficiency ref. NHV (50C/30C) % 108,6 108,6 108,6
Useful efficiency ref. NHV Tm=50C (60/40C) % 104,2 104,2 104,2
Useful efficiency at 30% ref. NHV (80C/60C) % 99,2 99,2 99,2
Useful efficiency at 30% ref. NHV (50C/30C) % 109 109 109
Useful efficiency at 30% ref. NHV Tm=50C (60 40C) % 105 105 105
Losses through the casing (Tm=70) % 0,1 0,1 0,1
Efficiency Class 92/42 CEE
Consumption and electrical power
Gas Category II2H3+
Gas Consumption (G20) (min / rated) m3/h 2,43 / 24,3 2,43 / 36,5 2,43 / 48,7
Power supply 230V - 50Hz
Maximum electrical consumption (boiler + Low Energy pump) W 580 870 1160
Maximum electrical consumption (only boiler) W 300 450 600
Combustion data
Max exhaust residual manometric head for each unit Pa 500
CO (0% di O2) (min / max) mg/kWh 23 /130
NOx class 5
Heating circuit
Heating temperature regulation (min / max) C 20 / 80
Water operating pressure (max / min) bar (kPa) 6 / 0,5 (600/50)
Max manometric head at nominal flow of 5500 l/h Pa [m c.a.] 1500 [1,5]

75
Power Plus BOX - cascade

Floor-standing, modular condensing boilers complete with 5


hydraulic collectors flow and return, 3 gas collector, flue outlets
110mm and condensate drain kit.
Stainless-steel BOX for outdoor installations with ventilation air
intake.
Efficiency according to European Directive EEC 92/42.
Minimum polluting emissions: class 5 (UNI EN 483).
Climatic curves available with Master Control (accessory).
Possibility to cascade up to 60 combustion units.
Electronic cascade control managed by Master Control.
Flue temperature of only around 8C above the return water
temperature.
Power Plus Box is provided with Low Energy shunt pumps.
Non-return valve (clapet) built-in.

BOX for OUTDOOR installation


DIMENSIONS
INPUT INPUT
CODE GAS MODEL HWD
(kW) Hs (kW) Hi
(mm)
WITH LOW ENERGY SHUNT PUMPS

20107469 NG POWER PLUS BOX 1002 P EXT 1.637900750 256 230

20107477 NG POWER PLUS BOX 1003 P EXT 1.6371.710750 384 345

20107479 NG POWER PLUS BOX 1004 P EXT 1.6371.710750 511 460

note: The whole range of components, accessories and flues for Power Plus BOX 1000-series is listed in this guide in the section ACCESSORIES

Electronic control for cascade management

CODE DESCRIPTION

Master board (manages the thermal modules cascade;


20067837*
contains blind flanges kit and external probe)

* It is necessary to order a master board for the whole cascade system.

76
Power Plus BOX 1002 Power Plus BOX 1003 - Power Plus BOX 1004
1637

310 850
100

898 750
190 908

POWER PLUS POWER PLUS POWER PLUS


specifications
BOX 1002 P EXT BOX 1003 P EXT BOX 1004 P EXT
Boiler type B23, B53, B53P, C13, C33, C53, C63
CE Homologation Number 0085CL0333
Number of burners 2 (x128 kW) 3 (x128 kW) 4 (x128 kW)
Dimension and Connections
HxLxD mm 1637x900x750 1637x1710x750
Empty weight kg 270 380 450
Content of water l 77 123 149
Water manifold 5
Gas manifold 3
Flue manifold mm 110
Condensate drain mm 50
Power and Efficiency
Heat input ref. HHV (min - max) kW 25,5 - 255,6 25,5 - 383,4 25,5 - 511,2

1000-series BOX
Heat input ref. NHV (min - max) kW 23 - 230 23 - 345 23 - 460
Useful heat output (80/60C) kW 226,8 340,2 453,6
Useful heat output (50/30C) kW 249,8 374,7 499,6
Useful heat output (60/40C) kW 239,6 359,4 479,2
Condensate production per hour at 100% (50 - 30C) - gas G20 kg/h 34,4 51,6 68,8
Useful efficiency ref. NHV (80C/60C) % 98,6 98,6 98,6
Useful efficiency ref. NHV (50C/30C) % 108,6 108,6 108,6
Useful efficiency ref. NHV Tm=50C (60/40C) % 104,2 104,2 104,2
Useful efficiency at 30% ref. NHV (80C/60C) % 99,2 99,2 99,2
Useful efficiency at 30% ref. NHV (50C/30C) % 109 109 109
Useful efficiency at 30% ref. NHV Tm=50C (60 40C) % 105 105 105
Losses through the casing (Tm=70) % 0,1 0,1 0,1
Efficiency Class 92/42 CEE
Consumption and electrical power
Gas Category II2H3+
Gas consumption (G20) (min / rated) m3/h 2,43 / 24,3 2,43 / 36,5 2,43 / 48,7
Power supply 230V - 50Hz
Maximum electrical consumption (boiler + Low Energy pump) W 580 870 1160
Maximum electrical consumption (only boiler) W 300 450 600
Combustion data
Max exhaust residual manometric head for each unit Pa 500
CO (0% di O2) (min / max) mg/kWh 23 / 130
NOx Class 5
Heating circuit
Heating temperature regulation (min / max) C 20 / 80
Water operating pressure (max / min) bar (kPa) 6 / 0,5 (600/50)
Max manometric head at nominal flow of 5500 l/h Pa [m c.a.] 1500 [1,5]

77
Power Plus BOX - stand alone

Stand-alone floor standing condensing boiler 115 kW with pre-


assembled hydronic header and multi-zones kit.
Painted steel BOX for indoor installations with ventilation air intake.
Stainless-steel BOX for outdoor installations with sloping top cover
and ventilation air intake.
Efficiency according to European Directive EEC 92/42,
ensuring low running costs.
Minimum polluting emissions: class 5 (UNI EN 483).
Compact dimensions.
Ready for installation.
Power Plus Box 1001 is a floor-standing condensing boiler available in
the following models:
- Power Plus Box 1001 INT (for indoor installation, painted box).
- Power Plus Box 1001 EXT (specific for outdoor installation,
stainless steel box).
This compact boiler is ready for installation and consists of:
boiler unit, Low Energy A-Class modulating pump, hydraulic
separator, I.N.A.I.L.* hydraulic manifold with safety devices and
flues collector.
Heat-generator also includes: system drain tap, exchangers drain tap,
gas tap, condensate drain collector, safety valve, air vent, external
probe, high and low temperature probes, domestic water probe and
LPG conversion kit.
High flexibility of installation: possibility of managing one direct zone,
one mixed zone and a DHW tank through the electronic board of the
OUTDOOR INDOOR master boiler. Specific accessories are available to control more mixed
(EXT) (INT) zones.
* I.N.A.I.L. = Italian safety certification Institute

Dedicated BOX for OUTDOOR and INDOOR installation


DIMENSIONS
INPUT INPUT
CODE GAS MODEL HWD
(kW) Hs (kW) Hi
(mm)

WITH LOW ENERGY SHUNT PUMPS

20067835 NG POWER PLUS BOX 1001 INT (115 all inside) 1.590900750 128 115

20067836 NG POWER PLUS BOX 1001 EXT (115 all inside) 1.640900750 128 115

Note: The Power Plus BOX 1001 INT/EXT comes with an embedded hydraulic separator up to 150 kW.
The whole range of components, accessories and flues for Power Plus BOX 1000-series is listed in this guide in the section ACCESSORIES

78
Power Plus BOX 1001 INT (115 all inside) Power Plus BOX 1001 EXT (115 all inside)

355 139 355 139

35

140 180 110110


35 69
140 180 110110

69

256
256

506

1637
506

1590

290
290

140
140

290
290

387
387

154

93
154

100
93

100
898 750 344 125 898 750
344 125
410
410
482
482

POWER PLUS BOX 1001 INT


SPECIFICATIONS
POWER PLUS BOX 1001 EXT
Boiler type B23, B53, B53p
CE Homologation Number 0085CL0333
Dimension and Connections
HxLxD (Power Plus BOX 1001 INT) mm 1590x898x750
HxLxD (Power Plus BOX 1001 EXT) mm 1637x898x750
Empty weight kg 140
Content of water l 32
Water manifold 2
Gas manifold 1
Flue manifold mm 110
Condensate drain mm 50
Power and Efficiency
Heat input ref. HHV (min / max) kW 25,5 / 127,8

1000-series BOX
Heat input ref. NHV (min / max) kW 23 / 115
Useful heat output (80/60C) kW 113,4
Useful heat output (50/30C) kW 124,9
Useful heat output (60/40C) kW 119,8
Condensate production per hour at 100% (50/ 30C) - gas G20 kg/h 17,2
Useful efficiency ref. NHV (80/60C) % 98,6
Useful efficiency ref. NHV (50/30C) % 108,6
Useful efficiency ref. NHV Tm=50C (60/40C) % 104,2
Useful efficiency at 30% ref. NHV (80/60C) % 99,2
Useful efficiency at 30% ref. NHV (50/30C) % 109
Useful efficiency at 30% ref. NHV Tm=50C (60 / 40C) % 105
Losses through the casing (Tm=70) % 0,1
Efficiency Class 92/42 CEE
Consumption and electrical power
Gas Category II2H3+
Gas consumption (G20) (min / rated) m3/h 2,43 / 12,2
Power supply 230V - 50Hz
Maximum electrical comsumption kW 0,25
Index of electrical protection IPX4D (for STAINLESS STEEL version only)
Combustion data
Max exhaust residual manometric head for each unit Pa 800
CO (0% di O2) (min / max) mg/kWh 23 / 130
NOx class 5
Heating circuit
Heating temperature regulation (min / max) C 20 / 80
Water operating pressure (min / max) bar (kPa) 6 / 0,5 (600/50)
Max manometric head at nominal flow of 5500 l/h Pa [m c.a.] 1500 [1,5]

79
Power Plus BOX (1000-series)

Hydraulic separator details


Hydraulic separator connections
FLOW 5
Nr. 2 FLANGES DN 125 PN6

connection
bend ( trimmed )

connection

connection
connection

connection

connection connection

tolerance

RETURN 5 Nr. 2 FLANGES DN125 PN6

tolerances 1 mm

80
Hydraulic separator

external

connection Fe 1 - H35

Nr. 4 FLANGES DN 125 PN6

master leak

connection Fe 1 - H35

tolerance 1 mm

1000-series BOX
1162
312

750 890

81
Power Plus BOX (1000-series)

Flue guidance: flue gas outlet and combustion air intake


Air intake and vent pipe sizes
If you decide to bring together in one manifold the discharges of each For cascade installations where there are more than two machines,
unit, the diameter of the pipe to be used for one or two units POWER the diameter of the exhaust manifold must be properly sized, or simply
PLUS BOX INT-EXT series connected in series is 200 mm (see the connect up to two POWER PLUS BOX INT-EXT using multiple lines
following table ). 200 mm separated.

Maximum Pipe Length (m)


Installed power with 110 with 160 with 200
(kW) (mm) (mm) (mm)
115 50 60 -
230 - 60 -
345 - 60 -
460 - 40 60
575 - 25 60
690 - - 60
805 - - 55
920 - - 40
1035 - - 35
1150 - - 25
1150 - - 25

Exhaust flue
The chimney should be as straight as possible, sealed and isolated. b Where collectors are used to evacuate the smoke, the presence
Should not have occlusions or narrowing. of non-return valves within each unit stops the products of
combustion of the active units entering the boiler room by means
b The overall potential of thermal groups POWER PLUS BOX INT- of the closed unit intake ducts.
EXT series is more than 35 kW, so they can be installed only in
rooms that have venting opening to the outside. In the event of installation with air intake from the premises (both in
the heating unit and externally) avoid obstructing the passage of air
b The POWER PLUS BOX INT-EXT series generators must under the metal cupboard.
be connected to a exhaust pipe system in flame retardant To bring together in one manifold the discharges of each unit, the
polypropylene (PP) or suitable materials according to UNI EN 483 diameter of the pipe to be used for one or two units POWER PLUS
and associated standards. BOX INT-EXT series connected in series is 200 mm.
For cascade installations where there are more than two machines the
DO NOT for any reason use piping not specifically designed for diameter of the exhaust manifold must be properly sizing, or simply
this specific scope as the condensing action could cause rapid connect up to two POWER PLUS BOX INT-EXT using multiple lines
degradation. 200 mm separated.

82
Condensate outlet
The condensate water produced by POWER PLUS BOX INT-EXT a Furthermore, should the vertical part of the flue exhaust duct have to be
normal running conditions is evacuated into a special manifold. prolonged by more than 4 metres the condensate drain-trap will have to
be placed at the foot of the piping. The working height of the drain-trap
Drainage must be done at atmospheric pressure, i.e. by dripping into a must be at least 30 cm. The drain-trap outlet must then be connected
connected drain-trap, as follows: up to the sewerage mains.
install a drip at the condensate drainage manifold;
connect the drip to the sewerage mains by a drain-trap; b The condensate drain must be connected to the sewerage
be ready to use a neutralizer where required. mains in such way as to prevent it from being frozen under any
circumstances.
There is generally no need to take any special precautions for draining
condensate. b Always install a condensate drain in the exhaust flue duct at no
We advise using plastic (PP) piping for building the condensate drainage. more than 1 m from the boiler.

DO NOT for any reason use pipes in copper or in any other material
not specifically used for this particular scope, as the condensing
action could cause rapid degradation.

i 3 i 3
i i

(*)
(*)

(*) minimum
distance
(*) minimum 300 mm

1000-series BOX
distance
300 mm

minimum minimum
i > 3% distance i > 3%
distance Civil drain
Civil drain 10 mm
10 mm Condensate collector
Condensate collector (at atmospheric pressure)
(at atmospheric pressure)
(*) Fill the siphons with water.
(*) Fill the siphons with water.

83
Power Plus Box

Example of INDOOR installation - Typical plant room with multi temperature zones

84
Example of INDOOR installation - Multiple C.H. zones, solar integration for D.H.W.
production

1000-series BOX
Hydraulic separator

85
Power Plus Box

Example of INDOOR installation - Multiple C.H. zones with individual pumps and D.H.W.
tank

86
Example of INDOOR installation - Multiple C.H. zones, solar integration for D.H.W.
production

1000-series BOX

87
Power Plus Box

Example of OUTDOOR installation - Multiple C.H. zones with individual pumps and
D.H.W. tank

88
Example of INDOOR installation - High efficiency condensing gas fired boiler in
combination with solar thermal system for D.H.W. preparation (load profile hotel/condominium)

1000-series BOX

89
International Markets

Product Catalogue

M O LTO
DI UN TE M OS TATO.

Thanks to the flexibility of the Power Plus/BOX


range, it is possible to integrate the boilers with
solar systems and heat pumps.
Refer to the system diagrams and to the
solutions proposed on the
Beretta International Product Catalogue.

90
Complementary items

complementary items

91
SP - Inspectable plate heat exchangers

Inspectable plate heat-exchanger in stainless-steel AISI 316 L


Gaskets in NBR
Screw fittings in AISI 316
Max working temperature 110C
Max pressure 10 bar

Plate heat exchangers DN 65

CODE MODEL PLATES no. DN MIX (%) * WEIGHT (kg)

20014230 SP 04A - 19 N 19 DN 65 100 122

20014218 SP 04A - 23 N 23 DN 65 100 124

20014225 SP 04X - 23 N 23 DN 65 45 126

20014219 SP 04A - 27 N 27 DN 65 100 126

20014239 SP 04X - 29 N 29 DN 65 40 100

20014238 SP 04X - 33 N 33 DN 65 35 130

20014235 SP 04A - 35 N 35 DN 65 100 131

20014234 SP 04X - 41 N 41 DN 65 35 135

20014232 SP 04A - 47 N 47 DN 65 100 142

20014236 SP 04X - 55 N 55 DN 65 35 147

20014231 SP 04A - 59 N 59 DN 65 100 150

20014241 SP 04X - 67 N 67 DN 65 90 155

20014233 SP 04X - 71 N 71 DN 65 25 157

20014228 SP 04X - 79 N 79 DN 65 85 177

20014221 SP 04X - 93 N 93 DN 65 20 186

* % mix of high-efficiency plates

= NEW (new codes are contained in the green rectangle)

92
Dimensions - SP heat exchangers
L P
H W D
DESCRIPTION
mm mm mm

PLATE HEAT EXCHANGERS IN AISI 316 L, WITH NBR GASKETS


SP 04 - 19 to 71 N 820 310 638

H SP 04 - 79 to 93 N 820 310 1138

SELECTION TABLE Condensing boilers / high temperature installations

Installation output Thermal software

POWER PLUS OUT LOSSES


CODE MODEL FLUID IN (C)
CONFIGURATION (C) (kPa)

100 - 115 20014230 SP04A-19N primary H2O 80 60 15

150 20014230 SP04A-19N secondary H2O 50 70 20

200 20014225 SP04A-23N

250 20014235 SP04A-35N

300 20014235 SP04A-35N

350 20014232 SP04A-47N

400 20014232 SP04A-47N

450 20014231 SP04A-59N

500 20014231 SP04A-59N

550 20014241 SP04X-67N

600 20014228 SP04X-79N

SELECTION TABLE Condensing boilers / low temperature installations complementary items

Installation output Thermal software

POWER PLUS OUT LOSSES


CODE MODEL FLUID IN (C)
CONFIGURATION (C) (kPa)

100 - 115 20014225 SP04X-23N primary H2O 60 40 15

150 20014239 SP04X-29N secondary H2O 60 30 15

200 20014238 SP04X-33N

250 20014234 SP04X-41N

300 20014236 SP04X-55N

350 20014233 SP04X-71N

400 20014233 SP04X-71N

450 20014221 SP04X-93N

500 20014221 SP04X-93N

93
Commercial cylinders and buffer tanks
IMMERSION HEATERS Compatible with all cylinders

CODE MODEL OUTPUT SIZE

4383270 Single-phase immersion heater kit 1,5 kW 1,5


4383271 Single-phase immersion heater kit 2,2 kW 1,5
4383272 Single-phase immersion heater kit 3,0 kW 1,5
20079908 Single-phase immersion heater kit 6,0 kW 1,5
20020707 Three-phase immersion heater kit 3,8 kW 1,5

IDRA DS and IDRA N DS - twin coil steel cylinders


Maximum working temperature 99C.
Twin coil heat exchanger.
Double magnesium anode included IDRA

Dimensions Capacity
CODE MODEL (H x )
(litres)
mm
20001226 IDRA DS 430 1630 x 755 441
20001227 IDRA DS 550 1980 x 755 550
20009144 IDRA DS 750 1870 x 1000 716
20009145 IDRA DS 1000 2195 x 1000 875
20052790 IDRA N DS 1500 2185 x 1200 1390
20052791 IDRA N DS 2000 2470 x 1300 1950

IDRA PLUS DS - cylinder and accessories


Maximum working temperature 99C
Three flanges
Double magnesium anode included

Dimensions Capacity
CODE MODEL (H x )
(litres)
mm
20052796 IDRA PLUS DS 3000 2730 x 1450 2959

Dimensions WATER
CODE MODEL (H x ) CONTENT
mm (litres)

20055205 Tin coated copper coil kit 2.63m2 -53kW 580 x 200 1.74
4383089 Tin coated copper coil kit 4.54m -91kW
2
750 x 200 3.56
4383087 Tin coated copper coil kit 6.34m2 -127kW 980 x 200 5.1

IDRA MS - single coil cylinder


Single coil heat exchanger
Sacrificial magnesium anode included
Enameled (double layer) steel solar cylinder

Dimensions Capacity
CODE MODEL (H x )
(litres)
mm
20015340 IDRA MS 550 1980x755 556

94
HYBRID STOR - triple coil buffer tank
Triple coil buffer tank
Ideal for heating and DHW production
DHW coil in AISI 316L stainless steel

Dimensions Capacity
CODE MODEL (H x )
(litres)
mm
20051862 HYBRID STOR 430 1650 x 810 431
20051863 HYBRID STOR 550 2000 x 810 544
20051864 HYBRID STOR 750 1855 x 1000 762
20051866 HYBRID STOR 1000 2180 x 1000 928

STOR M and STOR - buffer tanks


Designed for forced circulation solar systems to supplement the heating system.
Not suitable for DHW storage. Production of DHW through an additional heat exchanger
module. (Ask Beretta Pre Sales for advice)
Eight fittings for the use of different types of heat generators optimising stratification.
STOR M models are supplied with heat exchange solar coil and insulation as standard.
Additional heat exchange solar coils can be installed via a standard flange on STOR models.
Insulation is delivered separately from the STOR models.
Dimensions Capacity
CODE MODEL (H x )
(litres)
mm
20055207 STOR 300M with coil 1635 x 700 270
20055208 STOR 500M with coil 1775 x 850 476
20001406 STOR 1000M with coil 2190 x 990 920
20001407 STOR 1500M with coil 2165 x 1200 1410
20001408 STOR 2000 2480 x 1300 2010
20001409 STOR 3000 2720 x 1450 2959
20001410 STOR 5000 2870 x 1800 5055

Dimensions Capacity
CODE MODEL (H x )
(litres)
mm
20055205* Tin coated copper coil kit 2,63m2 -53kW 580 x 200 1.74
4383089* Tin coated copper coil kit 4,54m -91kW2 750 x 200 3.56
4383087* Tin coated copper coil kit 6,34m2 -127kW 980 x 200 5.1
* Only to be used with STOR 2000, 3000 and 5000 buffer tanks.
complementary items

STOR H - hot/cold water storage tank


Ideal for use with heat pumps, solar thermal and biomass boilers.
Integrates into systems where a Beretta boiler works as the auxiliary heat generator.
Possibility to integrate an immersion heater.

Dimensions Capacity
CODE MODEL (H x )
(litres)
mm
20056180 STOR H 200 1395 x 550 203
20056181 STOR H 300 1560 x 600 277
20056182 STOR H 400 1540 x 700 390
20056183 STOR H 500 1840 x 700 473

95
96
Accessories
Beretta components and accessories
for tailor-made installation solutions
The complete line of components and accessories developed by Beretta, hereafter
listed and shown, in addition to the configurations proposed in this guide, allow you
to compose also tailor-made Power Plus and Power Plus BOX applications.
By choosing all Beretta components, that harmonize perfectly with each other,
your Power Plus system will ensure the maximum comfort and savings that are
provided only by a unique specialized supplier.
accessories

97
Specific for 500-series CASCADE

code description

HYDRAULIC COMPONENTS and SAFETY DEVICES

20017226 Hydraulic manifold kit 100 kW for Power Plus rig with blank end flange

20009439 Hydraulic manifold kit up to 400 kW for Power Plus rig

20009444 Blank end-flange kit for hydraulic manifold (400 kW)

20009442 Pump kit (front) for Power Plus rig (Non ErP compliant)

20075526 LOW ENERGY pump kit (front) for Power Plus rig (ErP compliant)

20009443 Pump kit (rear) for Power Plus rig (Non ErP compliant)

20075527 LOW ENERGY pump kit (rear) for Power Plus rig (ErP compliant)

20072821 LOW ENERGY pump kit for secondary circuit

20017270 I.N.A.I.L.* safety connection pipes kit - 100 kW

* I.N.A.I.L. = Italian safety certification Institute - Beretta highly recommends safety devices also in countries where they are not compulsory.

98
Specific for 500-series CASCADE

code description

HYDRAULIC COMPONENTS and SAFETY DEVICES

20017271 Hydraulic header/separator 100 kW

20009466 Hydraulic header/separator (150 - 200 kW)

20009467 Hydraulic header/separator (250 - 460 kW)

20009471 Hydraulic manifold (150 - 400 kW)

I.N.A.I.L.* safety kit (400 kW max.)

it contains: temperature gauge


20009475
pressure gauge
pressure switch
connection plug with valve

20009486 Gas safety cut-off valve (115 kW max.)

20009482 Gas safety cut-off valve (230 kW max.)

20009483 Gas safety cut-off valve (580 kW max.)

20041367 Two-ways valve kit (only front mounting)

HYDRAULIC COMPONENTS and SAFETY DEVICES

10029891 Connections kit for injection pump


accessories

* I.N.A.I.L. = Italian safety certification Institute - Beretta highly recommends safety devices also in countries where they are not compulsory.

99
Specific for 500-series CASCADE

code description

ROOM-SEALED KITS

1102439 Air connection kit to Power Plus 50 kW

1102449 Air connection kit to Power Plus 100 kW

20064739 Conveyor (if you need this accessory please contact Pre Sales for advice)

FLUE HEADERS
4030311 Flues collector kit 125 for 50 kW

4030019 Flues collector kit 160 for 50 kW

20062323 Flues collector kit 200 for 50 kW

4030312 Flues collector kit 125 for 100 kW

4030037 Flues collector kit 160 for 100 kW

20062312 Flues collector kit 200 for 100 kW

20062337 Condensate drain kit 125 with end cap

20062338 Condensate drain kit 160 with end cap

20062340 Condensate drain kit 200 with end cap

20062332 End cap 125

20062333 End cap 160

20062335 End cap 200

100
Specific for 500-series CASCADE

code description

SPECIFIC ACCESSORIES FOR SPECIAL CASCADE SYSTEMS

20010996 Hydraulic header/separator (LLH) up to 720 kW for indoor installation

Primary loop pump <270 kW for P.P. Hs 300 kW (with connections and
20021898
electronic injection pump type VegA RMDA 50-80)

Primary loop pump <450 kW for P.P. Hs 500 kW (with connections and
20021900
electronic injection pump type VegA RMDA 80-90)

SUPPORTS for LINEAR WALL-HUNG or FREE STANDING MOUNTING

20009472 Power Plus rig (front mounting)

20018456 Supports hydraulic manifold kit (without rig) from 150 kW

SUPPORT for BACK-TO-BACK MOUNTING

20009474* Rear mounting kit for Power Plus free-standing rig


accessories

* This component is recommended also for linear free-standing cascade installations to provide extra stability where needed.

101
Specific for 500-series BOX

code description

COMMON ACCESSORIES FOR POWER PLUS BOX (all versions except SIS models)

50
Power Plus juntion Kit for Cascade
20074998
(common to all the Boxes, except SIS) 160

20011004 Gas anti-vibration kit (1 pcs)

20011003 Water anti-vibration kit (2 pcs)

20011165 Gas shutting valve (VIC) 11/4 with flange up to 300 kW

20011167 Gas shutting valve (VIC) 11/2 with flange up to 540 kW

20011169 Gas shutting valve (VIC) 2 with flange up to 720 kW

Primary loop pump <270 kW for P.P. Hs 300 kW (with connections and
20021898
electronic injection pump type VegA RMDA 50-80)

Primary loop pump <450 kW for P.P. Hs 500 kW (with connections and
20021900
electronic injection pump type VegA RMDA 80-90)

I.N.A.I.L.* safety kit (400 kW max.)

it contains: temperature gauge


20009475
pressure gauge
pressure switch
connection plug with valve

* I.N.A.I.L. = Italian safety certification Institute - Beretta highly recommends safety devices also in countries where they are not compulsory.

102
Specific for 500-series BOX

code description

SPECIFIC ACCESSORIES FOR SIS MODELS


E

D
C A

20069664 Low temperature kit SIS B

20069666 High temperature kit SIS


C

20069667 Tank kit SIS C

20011175 System connections kit (2 pcs)

20074999 Plugs kit (2 pcs)

SPECIFIC ACCESSORIES FOR OUTDOOR INSTALLATIONS (for all versions of BOX except SIS models)
20071951 Hydraulic separator for BOX EXT MAX 200 kW with fitting pipes (right)

20071949 Hydraulic separator for BOX EXT MAX 400 kW with fitting pipes (right)

20071942 Hydraulic separator for BOX EXT MAX 600 kW with fitting pipes (right)

20071950 Hydraulic separator for BOX EXT MAX 200 kW with fitting pipes (left)

20071943 Hydraulic separator for BOX EXT MAX 400 kW with fitting pipes (left)

20071940 Hydraulic separator for BOX EXT MAX 600 kW with fitting pipes (left)
accessories

103
Specific for 500-series BOX

code description

SPECIFIC ACCESSORIES FOR OUTDOOR INSTALLATIONS (for all versions of BOX except SIS models)

20010062 Hydraulic separator for BOX EXT MAX 720KW with fitting pipes (right)

20010065 Hydraulic separator for BOX EXT MAX 720KW with fitting pipes (left)

20071791 Painted BOX - empty

SPECIFIC ACCESSORIES FOR INDOOR INSTALLATIONS (for all versions of BOX except SIS models)
20075000 Hydraulic separator for BOX INT MAX 200 kW with fitting pipes (right)

20073125 Hydraulic separator for BOX INT MAX 400 kW with fitting pipes (right)

20073304 Hydraulic separator for BOX INT MAX 600 kW with fitting pipes (right)

20075001 Hydraulic separator for BOX INT MAX 200 kW with fitting pipes (left)

20073126 Hydraulic separator for BOX INT MAX 400 kW with fitting pipes (left)

20073305 Hydraulic separator for BOX INT MAX 600 kW with fitting pipes (left)

20010996 Hydraulic separator for BOX INT MAX 720KW with fitting pipes (right - left)

104
Specific for 1000-series BOX - INT

code description

SPECIFIC FOR 1000-SERIES BOX INT

20076316 Extension kit 110 with inspection

20069767 Flues collector 4x110 - 1x200

20069769 Flues collector 3x110 - 1x200

20069771 Flues collector 1x110 - 1x200 (for 2-engines box purchase 2)

20062340 Condensate drain kit 200 with end cap

20069073 Hydraulic separator INT 100 640 kW


20069075 Hydraulic manifold connection to low header and safety devices - right

20069074 Hydraulic separator INT MAX 1024 kW (suitable up to 10 engines)


20069075 Hydraulic manifold connection to low header and safety devices - right

20069073 Hydraulic separator INT 100 640 kW


20069072 Hydraulic manifold connection to low header and safety devices - left

20069074 Hydraulic separator INT MAX 1024 kW (suitable up to 10 engines)


20069072 Hydraulic manifold connection to low header and safety devices - left
accessories

105
Specific for 1000-series BOX - EXT

code description

SPECIFIC FOR 1000-SERIES BOX EXT

20060817 terminal chimney (stainless steel)

20060819 Kit extention 110 mm, 500 mm (stainless steel)

20060820 Kit extention 110 mm, 1000 mm (stainless steel)

20060821 90 bend 110 mm (stainless steel)

20060827 Hydraulic separator in BOX up to 640 kW - right

20060829 Hydraulic separator in BOX up to 1150 kW - right

20060828 Hydraulic separator in BOX up to 640 kW - left

20060830 Hydraulic separator in BOX up to 1150 kW - left

106
Common to all configurations

code description

COMMON FOR 1000-SERIES BOX INT and EXT


I.N.A.I.L.* safety kit

it contains: temperature gauge


20061644
pressure gauge
pressure switch
connection plug with valve

20061638 Valve kit up to 580 kW

20061640 Valve kit up to 1150 kW

20067019 EMPTY BOX L= 900 mm (1 door)

20067020 EMPTY BOX L= 1700 mm (2 door)

XKIT1460E Isolating valve for single heat exchanger

COMPLEMENTARY ITEMS

20011126 Condensate neutralizer N2 - up to 320 kW

20011132 Condensate neutralizer N3 - up to 1250 kW

20011135 Condensate neutralizer HN2 (with pump) - up to 320 kW

20011162 Condensate neutralizer HN3 (with pump) - up to 1250 kW

1102579 Blind flange 3 UNI 60/91 PN6 80 mm

1102589 Flange 3 UNI 2276-67 PN6 80 mm


accessories

20063062 Hydraulic gasket 3 80 mm

* I.N.A.I.L. = Italian safety certification Institute - Beretta highly recommends safety devices also in countries where they are not compulsory.

107
Common to all configurations

code description

COMPLEMENTARY ITEMS

20063060 Blind flange 5 UNI 60/91 PN6 125 mm

20063061 Flange 5 UNI 2276-67 PN6 125 mm

20063063 Hydraulic gasket 5 125 mm

x1 x1

20075887 Blind flanges kit for 500-series x 20


x2 x2

20063064 Bolt and nut

1102379 Remote control kit Power Plus

20046946 Interface kit for PC

1102869 Low temperature kit

20016110 Zone master kit

20073129 Mod-Bus interface (cables includes)

1103059 Probe kit for DHW tank

108
Indoor flue options

code description

FLUE SYSTEMS 50 (only for 500-series)

20021607 Extension 50, 250 mm (white PPS)

20021608 Extension 50, 500 mm (white PPS)

20021609 Extension 50, 1000 mm (white PPS)

20031842 Condensate drain kit 50 (white PPS)

20031841 45 bend 50 (white PPS)

20031840 90 bend 50 (white PPS)

20027815 Non-return flue valve kit 50/80 (PPtl)

FLUE SYSTEMS 60 (only for 500-series)

20046016 Extension 60, 640 mm (black PPS)

20046015 87 Bend 60 (black PPS)

20046028 Air intake/flue drain kit 60 (black PPS)

UV protected
accessories

109
Indoor flue options

code description

FLUE SYSTEMS 125 (only for 500-series)

Flues collector kit for frontal/rear installation


20017306
(PPtl, for cascade back-to-back)

20037413 Extension 125, 500 mm (PPtl)

20037415 Extension 125, 1000 mm (PPtl)

20037416 Extension 125, 2000 mm (PPtl)

20037424 Inspection extension 125 (PPtl)

20062337 Condensate drain kit 125 with end cap

20062371 Condensate drain pipe 125 (PPtl)

20062443 Siphon Long John (PPtl)

20062357 30 bend kit 125 (PPtl)

20037396 45 bend kit 125 (PPtl)

20037405 90 bend kit 125 (PPtl)

20062362 Inspection bend 125

20027816 Chimney kit 125

20037431 Chimney cover 125 (PP & stainless steel)

110
Indoor flue options

code description

20037429 Chimney support 125 (PPtl, EPDM, MET)

FLUE SYSTEMS 125 (only for 500-series)

20062376 T-connection 125 with condensate drain (PPtl)

20063418 T-connection kit 125 with condensate drain and chimney support

20062409 Eccentric adapter 125/110

20062411 Concentric adapter 125/110

20062381 Wall feeder 125/185 (stainless steel)

20062419 Wall cover 125 (stainless steel)

20062420 Wall cover 125 (white EPDM)

20062439 Grid 125 (stainless steel)

20037426 Pipe spacers kit 125 (plastic), 5 pcs.

20062440 Spacers 125 (met white)

20062398 Tool 125


accessories

20062441 Assembly lubricant, 5 pcs

111
Indoor flue options

code description

FLUE SYSTEMS 160 (only for 500-series)

20060940 Extension 160, 500 mm (PPtl)

20060941 Extension 160, 1000 mm (PPtl)

20060942 Extension 160, 2000 mm (PPtl)

20060945 Inspection extension 160 (PPtl)

20062338 Condensate drain kit 160 with end cap

20062447 Condensate drain pipe 160

20062445 30 bend kit 160 (PPtl)

20032646 45 bend kit 160 (PPtl)

20032644 90 bend kit 160 (PPtl)

20062446 Inspection bend 160

20032653 Chimney kit 160

20060953 Chimney cover 160 (stainless steel)

20062703 Chimney support kit 160

112
Indoor flue options

code description

FLUE SYSTEMS 160 (only for 500-series)

20062448 T-connection 160 with condensate drain

20063419 T-connection kit 160 with condensate drain and chimney support

20062511 Eccentric adapter 160-125

20060950 Concentric adapter 160-125

20062449 Wall feeder 160/225 (stainless steel)

20062512 Wall cover 160 (stainless steel)

20062513 Grid 160 (stainless steel)

20060948 Pipe spacers kit 160 (plastic), 5 pcs.

20062444 Pipe spacers kit 160 (stainless steel)

20062510 Tool 160


accessories

113
Indoor flue options

code description

FLUE SYSTEMS 200

20062527 Extension 200, 500 mm

20062530 Extension 200, 1000 mm

20062532 Extension 200, 2000 mm

20062534 Inspection extension 200

20062340 Condensate drain kit 200 with end cap

20062537 Condensate drain pipe 200

20062539 30 bend kit 200

20062542 45 bend kit 200

20062543 87 bend kit 200

20062545 Inspection bend 200

20062547 Chimney cover 200 (stainless steel)

20062548 Chimney support kit 200

20062550 T-connection 200 with condensate drain

20063420 T-connection kit 200 with condensate drain and chimney support

114
Indoor flue options

code description

FLUE SYSTEMS 200

20062566 Eccentric adapter 200-160

20062567 Concentric adapter 200-160

20062556 Wall feeder 200 (stainless steel)

20062574 Wall cover 200 (stainless steel)

20062575 Grid 200 (stainless steel)

20062564 Pipe spacers 200 (stainless steel)

20062563 Tool 200

accessories

115
Indoor flue options

code description

FLUE SYSTEMS 250

20062576 Extension 250, 500 mm

20062577 Extension 250, 1000 mm

20062578 Extension 250, 2000 mm

20062591 Inspection pipe 250

20062592 Condensate drain pipe 250

20062593 30 bend kit 250

20062594 45 bend kit 250

20062595 87 bend kit 250

20062598 Inspection bend 250

20062599 Chimney cover 250 (stainless steel)

20062600 Chimney support kit 250

20062601 T-connection 250 with condensate drain

20063421 T-connection kit 250 with condensate drain and chimney support

116
Indoor flue options

code description

FLUE SYSTEMS 250

20062606 Eccentric adapter 250-160

20062607 Concentric adapter 250-200

20062602 Wall feeder 250 (stainless steel)

20062635 Wall cover 250 (stainless steel)

20062636 Grid 250 (stainless steel)

20062605 Pipe spacers 250 (stainless steel)

20062604 Tool 250

accessories

117
Outdoor flue options

code description

FLUE SYSTEMS 125 (PP) - 185 (stainless steel)

20062637 Extension 125-185, 250 mm (stainless steel)

20062638 Extension 125-185, 500 mm (stainless steel)

20062639 Extension 125-185, 1000 mm (stainless steel)

20062641 Inspection pipe 125-185 (PP-stainless steel)

20062644 30 bend kit 125-185 (PP-stainless steel)

20062646 45 bend kit 125-185 (PP-stainless steel)

20062648 90 bend kit 125-185 (PP-stainless steel)

20062650 125-185 pipe for terminal (PP-stainless steel)

20062651 125-185 terminal (PP-stainless steel)

20062649 Chimney support kit 125-185 (PP-stainless steel)

20062654 Wall cover 185 (stainless steel)

20062653 External chimney spacers 185 (stainless steel)

118
Outdoor flue options

code description

FLUE SYSTEMS 160 (PP) - 225 (stainless steel)

20062655 Extension 160-225, 500 mm (PP-stainless steel)

20062656 Extension 160-225, 1000 mm (PP-stainless steel)

20062657 Inspection pipe 160-225 (PP-stainless steel)

20062658 30 bend kit 160-225 (PP-stainless steel)

20062659 45 bend kit 160-225 (PP-stainless steel)

20062660 87 bend kit 160-225 (PP-stainless steel)

20062662 160-225 pipe for terminal (PP-stainless steel)

20062663 160-225 terminal (PP-stainless steel)

20062661 Chimney support kit 160-225 (PP-stainless steel)

20062449 Wall feeder 160-225 (stainless steel)

20062665 Wall cover 225 (stainless steel)

20062513 Grid 160 (stainless steel)


accessories

20062664 External chimney spacers 225 (stainless steel)

119
Outdoor flue options

code description

FLUE SYSTEMS 200 (PP) - 300 (stainless steel)

20062666 Extension 200-300, 500 mm (PP-stainless steel)

20062667 Extension 200-300, 1000 mm (PP-stainless steel)

20062668 Inspection pipe 200-300 (PP-stainless steel)

20062669 30 bend kit 200-300 (PP-stainless steel)

20062670 45 bend kit 200-300 (PP-stainless steel)

20062671 87 bend kit 200-300 (PP-stainless steel)

20062673 200-300 pipe for terminal (PP-stainless steel)

20062674 200-300 terminal (PP-stainless steel)

20062672 Chimney support kit 200-300 (PP-stainless steel)

20062675 Wall cover 300 (stainless steel)

120
Outdoor flue options

code description

FLUE SYSTEMS 250 (PP) - 350 (stainless steel)

20062676 Extension 250-350, 500 mm (PP-stainless steel)

20062677 Extension 250-350, 1000 mm (PP-stainless steel)

20062688 Inspection pipe 250-350 (PP-stainless steel)

20062689 45 bend kit 250-350 (PP-stainless steel)

87 bend kit 250-350 (PP-stainless steel)


-
(to be done by means of 2x45 bends code 20062689)

20062691 250-350 pipe for terminal (PP-stainless steel)

20062692 250-350 terminal (stainless steel)

20062690 Chimney support kit 250-350 (PP-stainless steel)

20062693 Wall cover 350 (stainless steel)


accessories

121
Chimney system

Roof chimney terminal parts

Typical installation variants with


Beretta indoor and outdoor flue systems

122
123
accessories
5002_01 en 02/16

Trading Address:
Via Risorgimento, 23/A
23900 LECCO - Italy
Tel. +39 0341 277111
Fax +39 0341 277263
info@berettaboilers.com
www.berettaboilers.com

In order to improve its products, Beretta


reserves the right to modify the characteristics
and information contained in this catalogue at any
time and without prior notice.
This catalogue, therefore, cannot be considered as
contractually binding on third parties.