Subject: Amendments of my PEE TER entitled POWER SYSTEM


DESIGN OF 3-82 MW CFB POWER PLANT OF CEDC

Dear Sirs:

I am submitting herewith the amendments of my PEE TER at


reference pages 60, 62, 63, 140, and 141 as compliance to the
requirement for passing the Professional Electrical Engineering
Licensure Examination hoping for your favourable considerations
and approval.

Respectfully yours,

Nestor A. Diamada
Registered E lectrical Engineer
PRC Reg. No. 31537

POWER SYSTEM DESIGN OF 3-82 MW CFB POWER PLANT OF CEDC


ADDENDUM (PAGE 63)

source: IEEE C37-013 (courtesy from AREVA)

NAMEPLATE DATA: GENERATOR CIRCUIT BREAKER


BRAND: AREVA
MODEL: FKG2S
RATED MAXIMUM VOLTAGE: 17.5 kV
RATE FREQUENCY: 60 Hz
RATED CONTINUOUS CURRENT: 6000 A
RATED FULL-WAVE IMPULSE WITHSTAND VOLTAGE: PEAK 110 kV
RATED SHORT-CIRCUIT DUTY CYCLE: CO-30min-CO
RATED SHORT-CIRCUIT CURRENT, SYMMETRICAL: 72 kA
DC COMPONENT OF THE RATED SHORT-CIRCUIT CURRENT:75%
CLOSE, LATCH AND CARRY CURRENT: PEAK 173 kA
SHORT-TIME CURRENT: 63 kA 3s
ASSIGNED OUT-OF-PHASE SWITCHING CURRENT: 31.5 kA
RATED INTERRUPTING TIME: 83ms
SF6 GAS ABSOLUTE PRESSURE: 850 kPa
(RELATIVE PRESSURE AT 20C, 1013 hPa): 750 kPa
MASS OF SF6 GAS: 9 kg
TOTAL MASS OF CIRCUIT BREAKER: 3120 kg

POWER SYSTEM DESIGN OF 3-82 MW CFB POWER PLANT OF CEDC


ADDENDUM (PAGE 60)

source: IEC 52271-100 (courtesy from

ABB)

NAMEPLATE DATA: MAIN MEDIUM VOLTAGE

CIRCUIT

BREAKER
BRAND: FUJI
MODEL: HS4006X-40Mf-NZ
RATED VOLTAGE: 7.2 kV
RATED NORMAL CURRENT: 4000 A
RATED LIGHTNING IMPULSE WITHSTAND VOLTAGE: 60 kV
RATED SHORT-CIRCUIT BREAKING CURRENT: 40 kA
RATED FREQUENCY: 50/60 Hz
RATED DURATION OF SHORT-CIRCUIT: 40 kA 1 s
RATED SUPPLY VOLTAGE OF CLOSING DEVICE: 110 V DC
RATED SUPPLY VOLTAGE OF OPENING DEVICE: 110 V DC
RATED SUPPLY VOLTAGE OF OPERATING MOTOR: 110 V DC
RATED OPERATING SEQUENCE: O-3M-CO-3M-CO
TOTAL WEIGHT: 400 kg

ADDENDUM (PAGE 62)

source: IEC 52271-100 (courtesy from ABB)

POWER SYSTEM DESIGN OF 3-82 MW CFB POWER PLANT OF CEDC


NAMEPLATE DATA: MEDIUM VOLTAGE

CIRCUIT

BREAKER
BRAND: ABB
MODEL: VD4 1212-40
RATED VOLTAGE: 12 kV
RATED FREQUENCY: 60 Hz
POWER FREQUENCY WITHSTAND VOLTAGE: 42 kV
LIGHTNING IMPULSE WITHSTAND VOLTAGE: 75 Kv
NORMAL CURRENT: 1250 A
SHORT-CIRCUIT BREAKING CURRENT: 40 kA
SHORT-TIME WITHSTAND CURRENT: 40 kA 1 s
SHORT-CURRENT MAKING CURRENT: 100 kA
OPERATION SEQUENCE: O-0.3s-CO-3min-CO
AUXILLARY VOLTAGE: AC/DC 110 V
MOTOR VOLTAGE: AC/DC 110 V
MASS WEIGHT: 132 kg

ADDENDUM (PAGE 140)

POWER SYSTEM DESIGN OF 3-82 MW CFB POWER PLANT OF CEDC


ADDENDUM (PAGE 141)

POWER SYSTEM DESIGN OF 3-82 MW CFB POWER PLANT OF CEDC