QUICK CHECK. At a minim um, confirm ation of the governing Design Operating
Rating; show the factored components of the rating factor equation. A more
comprehensive check is recom mended, especially when results significantly differ
from the original Design Load increased to the Operating Level.
The Design Operating Rating is governed by shear at transfer point of Beam 10.
Total Servic e Dead Load Shear V DL := V sw + V noncomp + V deck + V diaph + V comp = 13.9 kip
Service Shear Due to Live & Im pact: V LI := 46.5 kip SHEAR AND MOMENT ENVELOPE : Span : 1,
Beam : 10, SERVICE I
V r - 1.25 V DL
Operating Rating: RF := = 1.549
1.35 V LI