TheworddemanditselfsaysthemeaningofDemandFactor.Theratioofthemaximumcoincident
demandofasystem,orpartofasystem,tothetotalconnectedloadofthesystem.
Forexample,anoversizedmotor20Kwdrivesaconstant15KwloadwheneveritisON.Themotor
demandfactoristhen15/20=0.75=75%.
DemandFactorisexpressasapercentage(%)orinaratio(lessthan1).
DemandFactorisalwayschangewiththetimetotimeorhourstohoursofuseanditwillnot
constant.
Theconnectedloadisalwaysknownsoitwillbeeasytocalculatethemaximumdemandifthe
demandfactorforacertainsupplyisknownatdierenttimeintervalsandseasons.
Thelowerthedemandfactor,thelesssystemcapacityrequiredtoservetheconnectedload.
1 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
(1)AResidenceConsumerhas10NosLampof400WbutatthesametimeItispossiblethatonly9
NosofBulbsareusedatthesametime.HereTotalConnectedloadis1040=400W.Consumer
maximumdemandis940=360W.DemandFactoofthisLoad=360/400=0.9or90%.
(2)OneConsumerhave10lightsat60KweachinKitchen,theloadis60Kwx10=600KW.Thiswill
betrueonlyifAlllightsareTurnsONthesametime(Demandfactor=100%or1)
ForthisConsumeritisobservedthatonlyhalfofthelightsbeingturnedONatatimesowecansay
thatthedemandfactoris0.5(50%).Theestimatedload=600KwX0.5=300Kw.
FeederconductorsshouldhavesucientAmpereCapacitytocarrytheload. TheAmpereCapacity
doesnotalwaysbeequaltothetotalofallloadsonconnectedbranchcircuits.
Thisfactormustbeappliedtoeachindividualload,withparticularattentiontoelectricmotors,which
areveryrarelyoperatedatfullload.
AsperNationalElectricalCode(NEC)demandfactormaybeappliedtothetotalload.Thedemand
factorpermitsafeederampearcitytobelessthan100percentofallthebranchcircuitloads
connectedtoit.
DemandfactorcanbeappliedtocalculatethesizeofthesubmainwhichisfeedingaSubpanelora
fixedloadlikeamotoretc.Ifthepanelhavetotalloadof250kVA,consideringaDemandfactorof
0.8,wecansizethefeedercablefor250x0.8=200kVA.
Demandfactorsforbuildingstypicallyrangebetween50and80%oftheconnectedload.
Inanindustrialinstallationthisfactormaybeestimatedonanaverageat0.75formotors.
Forincandescentlightingloads,thefactoralwaysequals1.
TextBookofDesignofElect.InstallationJain
ElectricalLoad DemandFactor
1NoofMotor 1
Upto10NosofMotor 0.75
Upto20NosofMotor 0.65
Upto30NosofMotor 0.6
2 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
Upto40NosofMotor 0.5
Upto50NosofMotor 0.4
TextBookofDesignofElect.InstallationJain
Utility DemandFactor
Oce,School 0.4
Hospital 0.5
AirPort,Bank,Shops, 0.6
Restaurant,Factory, 0.7
WorkShop,Factory(24Hr 0.8
Shift)
ArcFurnace 0.9
Compressor 0.5
Handtools 0.4
InductanceFurnace 0.8
SaudiElectricityCompanyDistributionStandard
3 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
Utility DemandFactor
Residential 0.6
Commercial 0.7
Flats 0.7
Hotel 0.75
Mall 0.7
Restaurant 0.7
Oce 0.7
School 0.8
CommonAreainbuilding 0.8
PublicFacility 0.75
StreetLight 0.9
IndoorParking 0.8
OutdoorParking 0.9
Park/Garden 0.8
Hospital 0.8
Workshops 0.6
WareHouse 0.7
Farms 0.9
FuelStation 0.7
Factories 0.9
4 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
TextBookofPrincipalofPowerSystemV.K.Mehta
Utility DemandFactor
ResidenceLoad(<0.25KW) 1
ResidenceLoad(<0.5KW) 0.6
ResidenceLoad(>0.1KW) 0.5
Restaurant 0.7
Theatre 0.6
Hotel 0.5
School 0.55
SmallIndustry 0.6
Store 0.7
MotorLoad(upto10HP) 0.75
MotorLoad(10HPto20HP) 0.65
MotorLoad(20HPto100HP) 0.55
MotorLoad(Above100HP) 0.50
DiversityFactorisratioofthesumoftheindividualmaximumdemandsofthevarioussubcircuitofa
5 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
systemtothemaximumdemandofthewholesystem.
DiversityFactor=Installedload/Runningload.
DiversityFactorisalways>1becausesumofindividualmax.Demands>Max.Demand.
Inotherterms,DiversityFactor(0to100%)isafractionofTotalLoadthatisparticularitem
contributedtopeakdemand.70%diversitymeansthatthedeviceoperatesatitsnominalor
maximumloadlevel70%ofthetimethatitisconnectedandturnedON.
Itisexpressedasapercentage(%)oraratiomorethan1.
Ifweusediversityvaluein%thanitshouldbemultiplywithLoadandifweuseinnumerical
value(>1)thanitshouldbedividedwithLoad.
DiversityoccursinanoperatingsystembecauseallloadsconnectedtotheSystemarenotoperating
simultaneouslyorarenotsimultaneouslyoperatingattheirmaximumrating.Thediversityfactor
showsthatthewholeelectricalloaddoesnotequalthesumofitspartsduetothistime
Interdependence(i.e.diverseness).
Ingeneraltermswecansaythatdiversityfactorreferstothepercentoftimeavailablethata
machine.70%diversitymeansthatthedeviceoperatesatitsnominalormaximumloadlevel70%of
thetimethatitisconnectedandturnedON.
ConsidertwoFeederswiththesamemaximumdemandbutthatoccuratdierentintervalsoftime.
Whensuppliedbythesamefeeder,thedemandonsuchislessthesumofthetwodemands.In
electricaldesign,thisconditionisknownasdiversity.
Diversityfactorisanextendedversionofdemandfactor.Itdealswithmaximumdemandofdierent
unitsatatime/Maximumdemandoftheentiresystem.
Greaterthediversityfactor,lesseristhecostofgenerationofpower.
Manydesignersprefertouseunityasthediversityfactorincalculationsforplanningconservatism
becauseofplantloadgrowthuncertainties.Localexperiencecanjustifyusingadiversityfactor
largerthanunity,andsmallerserviceentranceconductorsandtransformerrequirementschosen
accordingly.
Thediversityfactorforallotherinstallationswillbedierent,andwouldbebaseduponalocal
evaluationoftheloadstobeappliedatdierentmomentsintime.Assumingittobe1.0may,on
someoccasions,resultinasupplyfeederandequipmentratingthatisratherlargerthanthelocal
installationwarrants,andanoverinvestmentincableandequipmenttohandletheratedload
current.Itisbettertoevaluatethepatternofusageoftheloadsandcalculateanacceptablediversity
factorforeachparticularcase.
6 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
OneMainFeederhavetwoSubfeeder(SubFeederAandSubFeederB),SubFeederAhave
demandatatimeis35KWandSubFeederBhavedemandsatatimeis42KW,butthemaximum
demandofMainFeederis70KW.
TotalindividualMaximumDemand=35+42=77KW.
MaximumDemandofwholeSystem=70KW
SoDiversityfactorofTheSystem=77/70=1.1
Diversityfactorcanshootupabove1.
TheDiversityFactorisappliedtoeachgroupofloads(e.g.beingsuppliedfromadistributionor
subdistributionboard).
Diversityfactoriscommonlyusedforacompleteacoordinationstudyforasystem.Thisdiversity
factorisusedtoestimatetheloadofaparticularnodeinthesystem.
DiversityfactorcanbeusedtoestimatethetotalloadrequiredforafacilityortosizetheTransformer
Diversityfactorshavebeendevelopedformainfeederssupplyinganumberoffeeders,andtypically
1.2to1.3forResidenceConsumerand1.1to1.2forCommercialLoad.1.50to2.00forpowerand
lightingloads.
Note:Reciprocaloftheaboveratio(willbemorethan1)alsoisusedinsomeothercountries.
Diversityfactorismostlyusedfordistributionfeedersizeandtransformeraswellastodeterminethe
maximumpeakloadanddiversityfactorisalwaysbasedonknowingtheprocess.Youhaveto
understandwhatwillbeonoroatagiventimefordierentbuildingsandthiswillsizethefeeder.
Notefortypicalbuildingsdiversityfactorisalwaysone.Youhavetoestimateorhaveadatarecords
tocreate24hoursloadgraphandyoucandeterminethemaximumdemandloadfornodethenyou
caneasilydeterminethefeederandtransformersize.
Thediversityfactorofafeederwouldbethesumofthemaximumdemandsoftheindividual
consumersdividedbythemaximumdemandofthefeeder.Inthesamemanner,itispossibleto
computethediversityfactoronasubstation,atransmissionlineorawholeutilitysystem.
Theresidentialloadhasthehighestdiversityfactor.Industrialloadshavelowdiversityfactors
usuallyof1.4,streetlightpracticallyunityandotherloadsvarybetweentheselimits.
(StandardHandbookforElectricalEngineersbyFinkandBeaty)
7 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
Numberofcircuits DiversityFactorin%(ks)
Assembliesentirelytested2and3 90%
4and5 80%
6to9 70%
10andmore 60%
Assembliespartiallytestedineverycase 100%
choose
CircuitsFunction DiversityFactorin%(ks)
8 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
Lighting 90%
Heatingandairconditioning 80%
Socketoutlets 70%
Liftsandcateringhoist
Forthemostpowerfulmotor 100%
Forthesecondmostpowerfulmotor 75%
Forallmotors 80%
Apartment DiversityFactorin%(ks)
2To4 1
5To19 0.78
10To14 0.63
15To19 0.53
20To24 0.49
25To29 0.46
30To34 0.44
35To39 0.42
40To40 0.41
9 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
50ToAbove 0.40
TextBookofPrincipalofPowerSystemV.K.Mehta
TheratiooftheActualLoadofequipmenttoFullloadofequipment.
ItistheratioofactualkilowattHoursusedinagivenperiod,dividedbythetotalpossiblekilowatt
hoursthatcouldhavebeenusedinthesameperiodatthepeakKWlevel.
LoadFactor=(energy(kWhpermonth))/(peakdemand(kW)xhours/month)
InothertermsLoadfactorisdefinedastheratioofAverageloadtomaximumdemandduringa
givenperiod.
LoadFactor=AverageLoad/MaximumDemandduringgivenTimePeriod
LoadFactorisalwayslessthan1becausemaximumdemandisalwaysmorethanaveragedemand.
10 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
LoadFactorcanbecalculatedforasingleday,foramonthorforayear.
Loadfactorinothertermsofeciency.
Itisusedfordeterminingtheoverallcostperunitgenerated.
HighertheloadfactorisGOODanditwillmoreOutputofPlan,lesserthecostperunitwhich
meansanelectricitygeneratorcansellmoreelectricityatahighersparkspread,Fixedcostsare
spreadovermorekWhofoutput.ApowerplantmaybehighlyecientatHighloadfactors.
LowloadfactorisaBED.Alowloadfactorwilluseelectricityinecientlyrelativetowhatwecould
beifwewerecontrollingourpeakdemand.Apowerplantmaybelessecientatlowloadfactors.
Foralmostconstantloads,theloadfactorisclosetounity.
ForVaryingLoadFactorisclosedZero.
LoadFactorisameasureoftheeectiveutilizationoftheloadanddistributionequipment,i.e.
higherloadfactormeansbetterutilizationofthetransformer,lineorcable.
Ahighloadfactormeanspowerusageisrelativelyconstant.Lowloadfactorshowsthatoccasionally
ahighdemandisset.Toservicethatpeak,capacityissittingidleforlongperiods,therebyimposing
highercostsonthesystem.Electricalratesaredesignedsothatcustomerswithhighloadfactorare
chargedlessoverallperkWh.
Sometimesutilitycompanieswillencourageindustrialcustomerstoimprovetheirloadfactors.
Loadfactoristermthatdoesnotappearonyourutilitybill,butdoesaectelectricitycosts.Load
factorindicateshowecientlythecustomerisusingpeakdemand.
Calculation:
Motorof20hpdrivesaconstant15hploadwheneveritison.
Themotorloadfactoristhen15/20=75%.
IntroductiontoPowerRequirementforBuildingJ.PaulGuyer,
11 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
Electricalandelectronicslaboratory 2030 37
12 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
Thereciprocalofdiversityfactoriscoincidencefactor
Thecoincidencefactoristheratioofthemaximumdemandofasystem,orpartunderconsideration,
tothesumoftheindividualmaximumdemandsofthesubdivisions
Expressedasapercentage(%)oraratiolessthan1.
UsuallyConfidenceFactorwilldecreaseasthenumberofconnectedcustomersincreases.
Thefactorksisappliedtoeachgroupofloads(e.g.distributionorsubdistributionboard).
Thedeterminationofthesefactorsistheresponsibilityofthedesigner,sinceitrequiresadetailed
knowledgeoftheinstallationandtheconditionsinwhichtheindividualcircuitsaretobeexploited.
Forthisreason,itisnotpossibletogiveprecisevaluesforgeneralapplication.
13 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
Themaximumdemandofaninstallationisthemaximumrateofconsumptionexpressedinamperes,
kWorkVA.Itisgenerallytakenastheaveragerateofconsumptionoveraperiodoftime.Example
the15minutemaximumkWdemandfortheweekwas150kW.Maximumdemanddoesnotinclude
motorstartingcurrentsorothertransienteects.Faultcurrentsandoverloadcurrentsarealso
excluded.MaximumdemandinKWisrelevantonlyformetering/taripurposes.
Maximumdemand(oftenreferredtoasMD)isthelargestcurrentnormallycarriedbycircuits,
switchesandprotectivedevices.Itdoesnotincludethelevelsofcurrentflowingunderoverloador
shortcircuitconditions.
MaximumDemandisagreatestofalldemandsthatoccurduringaspecifictime
Themajordisadvantageofallocatingloadusingthediversityfactorsisthatmostutilitieswillnothave
atableofdiversityfactorsandsometimeitisnotviabletodetermineaccurateDiversityFactor.In
thissituationMaximumDemandisveryhelpfultocalculatesizeofFeederorTC.
ThekVAratingofalldistributiontransformersisalwaysknownforafeeder.Themeteredreadings
canbetakentoeachtransformerbaseduponthetransformerrating.Anallocationfactor(AF)can
becalculate.
AllocationFactor=MeteredDemand(KVA)/TotalKVA.
EquipmentDemand=AFxTotalKVAofEquipments
Calculation:
ActualLoadingorSizeofTC1andTC2.
(https://electricalnotes.files.wordpress.com/2011/10/11.jpg)
TotalLoadonTC1=10+11+12+08=41KW.
MaximumDiversityDemandofTC1=41/1.1=37.3KW.
TotalLoadonTC2=4+3+12+02=21KW.
MaximumDiversityDemandofTC2=21/1.2=17.5KW.
TotalLoad=37.3+17.5=54.8KW.
AllocatingFactor(AF)=M.D/TotalLoad
AllocatingFactor(AF)=0.27.
ActualLoadonTC1=0.2737.3=1.20KW.
14 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
ActualLoadonTC2=0.2717.5=4.8KW.
AssessmentofmaximumdemandisveryeasyforResistiveLoad,Forexample,themaximum
demandofa240Vsinglephase8kWshowerheatercanbecalculatedbydividingthepower(8kW)
bythevoltage(240V)togiveacurrentof33.3A.Thiscalculationassumesapowerfactorofunity,
whichisareasonableassumptionforsuchapurelyresistiveload.
LightingcircuitsposeaspecialproblemwhendeterminingMD.Dischargelampsareparticularly
diculttoassess,andcurrentcannotbecalculatedsimplybydividinglamppowerbysupply
voltage.ThereasonsforthisareControlgearlossesresultinadditionalcurrent,thepowerfactoris
usuallylessthanunitysocurrentisgreater,andChokesandothercontrolgearusuallydistortthe
waveformofthecurrentsothatitcontainsharmonicswhichareadditionaltothefundamental
supplycurrent.
Solongasthepowerfactorofadischargelightingcircuitisnotlessthan0.85,thecurrentdemandfor
thecircuitcanbecalculatedfrom:
current(A)=(lamppower x1.8)/supplyvoltage(V)
Forexample,thesteadystatecurrentdemandofa240Vcircuitsupplyingten65Wfluorescent
lampswouldbe:I=10X65X1.8A/240=4.88A
Switchesforcircuitsfeedingdischargelampsmustberatedattwicethecurrenttheyarerequiredto
carry,unlesstheyhavebeenspeciallyconstructedtowithstandtheseverearcingresultingfromthe
switchingofsuchinductiveandcapacitiveloads.
ThereisgenerallyconfusionbetweenDemandfactorandDiversityfactor.Demandfactorsshould
beideallyappliedtoindividualloadsanddiversityfactortoagroupofloads.
Whenyoutalkaboutdiversity,therearenaturallymorethanoneormanyloadsinvolved.
Demandfactorcanbeappliedtocalculatethesizeofthesubmain,whichisfeedingaSubpanelora
fixedloadlikeamotoretc,individualLoad.
DemandfactorsaremoreconservativeandareusedbyNECforserviceandfeedersizing.
IftheSubpanelhavetotalloadis250kVA,consideringaDemandfactorof0.8,wecansizethe
feedercablefor250x0.8=200kVA.
TheDiversityFactorisappliedtoeachgroupofloads(e.g.beingsuppliedfromadistributionor
subdistributionboard),sizetheTransformer.
Demandfactorsanddiversityfactorsareusedindesign.Forexample,thesumoftheconnected
loadssuppliedbyafeederismultipliedbythedemandfactortodeterminetheloadforwhichthe
feedermustbesized.Thisloadistermedthemaximumdemandofthefeeder.Thesumofthe
maximumdemandloadsforanumberofsubfeedersdividedbythediversityfactorforthesub
feederswillgivethemaximumdemandloadtobesuppliedbythefeederfromwhichthesubfeeders
arederived.
15 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
Theestimatedelectricaldemandforallfeedersserveddirectlyfromtheserviceentranceiscalculated
bymultiplyingthetotalconnectedloadsbytheirdemandfactorsandthenaddingallofthese
together.Thissumisdividedbythediversityfactor(frequentlyassumedtobeunity)tocalculate
theserviceentrancedemandwhichisusedtodetermineampacityrequirementsfortheservice
entranceconductors.
WhenusedDiversityandDemandFactorinanelectricaldesignitshouldbeappliedasfollows,the
sumoftheconnectedloadssuppliedbyafeedercircuitcanbemultipliedbythedemandfactorto
determinetheloadusedtosizethecomponentsofthesystem.
Thesumofthemaximumdemandloadsfortwoormorefeedersisdividedbythediversityfactorfor
thefeederstoderivethemaximumdemandload.
Example1:CalculateSizeofTransformerhavingfollowingdetails:
(https://electricalnotes.files.wordpress.com/2011/10/2.jpg)
FeederBreaker1DemandLoad=FeederBreaker1xDemandFactor.
FeederBreaker1DemandLoad=20000.7=1400KVA
FeederBreaker2DemandLoad=FeederBreaker2xDemandFactor.
FeederBreaker2DemandLoad=15000.6=900KVA
FeederBreaker3DemandLoad=FeederBreaker3xDemandFactor.
FeederBreaker2DemandLoad=10000.5=500KVA
TotalFeederBreakerDemand=1400+900+500=2800KVA
TransformerDemandLoad=TotalFeederBreakerDemand/DiversityFactor.
TransformerDemandLoad=2800/1.1=2545KVA
IfweCalculatedTotalLoadonTransformerwithoutanyDemand&
Diversity=2000+1500+1000=4500KVA.
16 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
ButafterCalculatingDemand&DiversityFactorTotalLoadonTransformer=2545KVA
Example2:CalculateSizeofMainFeederofMainTransformerhavingfollowingDetails:
(https://electricalnotes.files.wordpress.com/2011/10/3.jpg)
SumofMaximumDemandofCustomeronTC1=10KWx0.65=6.5KW
SumofMaximumDemandofCustomeronTC2=20KWx0.75=15KW
SumofMaximumDemandofCustomeronTC3=30KWx0.65=19.5KW
AsDiversityofConsumerConnectedonTC1is1.5so,
MaximumDemandonTC1=6.5KW/1.5=4KW.
AsDiversityofConsumerConnectedonTC2is1.1so,
MaximumDemandonTC2=15KW/1.1=14KW
AsDiversityofConsumerConnectedonTC3is1.5so,
MaximumDemandonTC3=19.5KW/1.5=13KW.
IndividualMaximumDemandonMainTransformer=04+14+13=31KW.
MaximumDemandonMainFeeder=04+14+13/1.3=24KW
Loadfactoranddiversityfactorplayanimportantpartinthecostofthesupplyofelectrical
energy.Higherthevaluesofloadfactoranddiversityfactors,lowerwillbetheoverallcostperunit
generated.
Thecapitalcostofthepowerstationdependsuponthecapacityofthepowerstation.Lowerthe
maximumdemandofthepowerstation,theloweristhecapacityrequiredandthereforeloweristhe
capitalcostoftheplant.Withagivennumberofconsumersthehigherthediversityfactoroftheir
loads,thesmallerwillbethecapacityoftheplantrequiredandconsequentlythefixedchargesdue
tocapitalinvestmentwillbemuchreduced.
Similarlyhigherloadfactormeansmoreaverageloadormorenumberofunitsgeneratedforagiven
maximumdemandandthereforeoverallcostperunitofelectricalenergygeneratedisreduceddue
todistributionofstandingchargeswhichareproportionaltomaximumdemandandindependentof
17 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
numberofunitsgenerated.
Thusthesuppliersshouldalwaystrytoimprovetheloadfactoraswellasdiversityfactorbyinducing
theconsumerstousetheelectricalenergyduringopeakhoursandtheymaybechargedatlower
ratesforsuchschemes.
Advertisements
FiledunderUncategorized
AboutJignesh.Parmar
JigneshParmarhascompletedM.Tech(PowerSystemControl),B.E(Electrical)fromGujaratUniversity.
Hehasmorethan13yearsexperienceinPowerTransmissionPowerDistributionElectricalenergy
theftdetectionElectricalMaintenanceElectricalProjects(PlanningDesigningcoordinationExecution).
HeisPresentlyassociatewithoneoftheleadingbusinessgroupasaDeputyManagerat
Ahmedabad,India.HeisFreelancerProgrammerofAdvanceExcelanddesignusefulExcelSheetsof
ElectricalEngineeringasperIS,NEC,IEC,IEEEcodes.HeistechnicalAuthorforElectricalMirrorand
ElectricalIndiaMagazines.HeisTechnicalBloggerandFamiliarwithEnglish,Hindi,Gujarati,French
languages.HewantstoSharehisexperience&knowledgeandhelptechnicalenthusiaststofind
suitablesolutionsandupdatingthemselvesonvariousEngineeringTopics.
1.Manish says:
October31,2011at4:14pm
Thankyouverymuchforsuchagoodanddetailedarticle.
Yourblogpostsarealwaysquitegood!
Reply
2.Dieter says:
November9,2011at10:55am
AsajuniorE&IEngineer,Iherewiththankyouforyourkindnessofsharingyourknowledge.
Ilookforewardtomoreofyourwork.
18 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
Reply
S.SAMBATH says:
November29,2011at1:36pm
Sir,
TheinformationsareveryusefullikemeasElectricityBoardEngineer.ThankuandIexpect
more.
s.sambath
Reply
zaheerkhattak says:
May30,2012at7:15am
dearsir,thanksalotbothofuiamelectricalengineerandimworkinginconsultancyfirmin
pakistan
imostlydesignhighriseocialandresidentialbuilding.iwanttoshareandgainsome
importantknowledgeaboutdesigningforAllofuandeveryonehowhelpme.
thanks
Zaheerkhattak
shazconsultantPeshawarPakistan
availableonFacebook
3.chemie says:
November30,2011at6:21am
mefrommalaysiauaregreatsir..thanksalot
Reply
4.Md.Samiuddin says:
December7,2011at8:58am
DearMr.JigneshParmar,
Thedetailsprovidedbyareveryuseful.Excellent!
Ineedasmallhelp.IamanIndian,nativeofAndhraPradesh.Iamamechanicalengineer,handling
anewprojectinJeddah,SaudiArabia.
Thedetailsinthepowersummaryreportare:
ConnectedPowerUsage=1290KWH
Aftermultiplyingbypowerfactorsandmaximumutilizationfactorsindividuallytoeachequipment
thesumis=535KWH.
Example:Craneconnectedpower=95kwh;powerfactor=0.6;Max.Utlzn.Factor=0.75gives
95kwhX0.6X0.75=42.75kwh
Now,IfIwantbuythegenerators(OR)toaskforelectricitydept.whatpowershouldIask?Willit
be1290KWHor535KWH?Pleaseclarifyandexplainmetoimprovemyawaenessinthisperticular
topicbecausealwaysIcomeacrosswithsuchincidents.
Pleasereplytometomyemail:(or)
Thanksforyoursupportinadvance.
BestRegard
19 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
Md.Samiuddin
Plantmanager
MIMCo.,
Jeddah
KSA
Reply
5.MansourA, says:
January15,2012at7:08pm
ThankuverymuchMr.Parmar,Ireallygetuseandunderstandthesefactorswhichwereconfused
tome.Ihavesetthissiteinfavouritieslookingforewardtoreadyourgoodactivities.
Reply
6.francisazumah says:
February18,2012at2:49pm
amverygreatfulfortheexplanatorynotes,isaywelldonebutneedsmoreofthat.thankyou
Reply
7.Rahman says:
February27,2012at11:49am
veryusefullinkthankyou
Reply
8.opeyemi says:
March17,2012at6:32am
Greatanswer,itreallymeetmydemand
Reply
9.ranx says:
March23,2012at6:57pm
Thankforyourkindness,yourexplanationveryusefulandveryunderstadbletous.
Reply
10.ranx says:
March23,2012at6:58pm
Thanksforthesharingofyourknowledgethissveryusefultomydesign
Reply
11.anam says:
April25,2012at1:03pm
canihavethedefinitionofgrowthfactor?
Reply
12.goldwincs says:
June18,2012at2:42pm
greatpost!canyouexplainaboutpeakdiversityfactor?
Reply
13.ahmednazmi says:
July19,2012at9:05am
20 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
whatthedierencebetweendiversityfactoranddiversityfactor(ks)andwhereiwilluse:diversity
factor,diversityfactor(ks)anddemandfactor
Reply
14.daniel says:
August8,2012at5:45pm
great,pleasedomorepostanddetailedexplanation
Reply
15.mynameisokekhianstanley. says:
August16,2012at2:34pm
Thankyouforyourknowledge.Thiswillbeofhelpinmyfieldwork.
Reply
16.kwame says:
August16,2012at2:57pm
Thanksverymuch,Iamreallyenlightenedalot.
Reply
17.JoseAntonioMartins says:
September28,2012at6:06pm
DearMr.JigneshParmar,
Thedetailsprovidedaboutthisissueareveryuseful.
Wouldyoumindinformingmeabouttheoriginofthetable:DiversityFactorforanapartment
block?
Pleaseanswermebyemail.
Thanksforyoursupportinadvance.
Reply
JoseAntonioMartins says:
December19,2012at8:21pm
IhavealreadyfoundthereferredtableintheFrenchStandardNFC14100(2008):Lowvoltage
mainsinstallations.
Pleaseconsiderthecorrections:
whereis40To40shouldbe40to49
whereis50ToAbove,ks=0.40shouldbe50toAbove,ks=0.38.
Reply
18.dhananjayPrasad says:
October12,2012at2:18am
Thankyousir
Reply
19.salmanp says:
November7,2012at8:16am
thankusir
21 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
Reply
20.tiger says:
November19,2012at11:05am
Verygoodarticle,butthesecalculationderivedfromwhichCodeorstandard???speciallytable
(DemandFactor&LoadFactoraccordingtoTypeofIndustries),becausethesevaluesisvariedand
dependonthepracticewise
Reply
Jignesh.Parmar says:
November19,2012at2:35pm
Yes.Agreewithyou.ThisisjustreferenceValue.ThisValuevaryaccordingtoitsusers
Profile.
Wecannotpredicttheactualvaluebutthistablevaluehelpfulustocalculatemorerealistic
assumption.
IgotthisTablefromoneBookorManual.IfitismorevaluableforYouthanIwilldefiantly
conveyitsReferenceSource.
Reply
tigerman says:
November20,2012at7:48am
Manythanksforyourreply,andihopetosendtomethisreferenceorbookitwillbeakind
fromyou
Samer says:
January2,2013at9:10am
Canyoupleaseprovidemewiththereferencesource?Itisveryimportanttome.
Thankyouforthegreatarticle.
Regards.
21.RonChatterji says:
December5,2012at1:26pm
IamfromUS.MynameisRon.Iwanttotalkwithyouonsomething.Pleasetellmewhatphone#I
cancallandtime.Iwillcallyouaftergettingyour3
Reply
Jignesh.Parmar says:
December5,2012at2:20pm
IamavailableonEmail.
MyEmailIdisjiguparmar@yahoo.com
Reply
Mohammed says:
February24,2013at4:16pm
DearJignesh,ineedthereferencesofyourdiversity,demandandcoincidencefactrostables.
aretheyasperanyinternational/nationalcodes.Yourkindreplywillbnehelfulinstudyinga
project.
M.A.Bari
Shakil says:
22 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
July6,2013at2:49am
Jignesh.Parmar,Ineedyourhelp.IamfmBangladesh.Iamalsoaelectricalengineer.Isawthat
youhavemostexperienceinpowersector.In15thjuly,aBangladeshipowergeneration
companycallainterview.Iamalsoacandidateforthatinterview.Sirpleasegivesome
materialsandtellmehowcanigotthatjob.Iliketoinformyouthat,Ihavenoexperienceto
workanypowerplant.Iamafresherelectricalengineer
22.RonChatterji says:
December5,2012at1:27pm
Ineedyourphone#andthetime/date
Reply
23.minhaz says:
December23,2012at5:00am
exellent
Reply
24.saad says:
December23,2012at9:31am
thanksdear
Reply
25.MarkJasonAcopioObordo says:
January17,2013at2:08pm
thanks!!nowiknow.:)
Reply
26.colinchallinger says:
February5,2013at9:59am
HiIhaveanappartmentblockwith12flatstocostandtheyareallelectrilyheatedtoalpotdivesity
equals22.4Kva
refto(ks)willthisfactorstillapplytotheincomingmain?
Reply
27.PercyMakhuvha says:
February28,2013at8:28am
ThankyouverymuchknowIamhappy
Reply
28.AllanSanjose says:
March18,2013at12:32am
Yourfirststatementregardingdemandfactorisalwayslessthanone.
ifyourdemandfactoris100%thatisequaltoone.
Philippines
Reply
Jignesh.Parmar says:
March18,2013at2:25pm
PleasecarefullyReadDefinitionFirst!!!
23 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
DemandFactor=Maximumdemandofasystem/Totalconnectedloadonthesystem.
YourmaxdemandnevergoesbeyondconnectedloadsoD.Fisalwayslessthan1.
Hopethisclarificationmayclearyourdough.
Reply
29.Rahul says:
March21,2013at5:22pm
Dearsir,
Icameacrossanotherformulalike
Maximumnormalrunningplantload=100%sumofallcontinuouslyoperatingloads+30%sumof
allintermittentloads.
Where100%and30%areconsideredasthediversityfactorsofcontinuousandintermittentloads
respectively
Sirdoyouknowwhichindustryisthisformulacommonlyused.canyouexplainthisformula..
Ihopeyouwillreplytomyquestion
Reply
30.KhwajaSalim says:
April3,2013at9:36am
ThankYouMr.JigneshParmar.Itisveryusefulindesigningofelectricalinstalltion.
Reply
31.John says:
May11,2013at2:52pm
DearSir,Iwouldliketolearnaboutthereferenceforthisinfo.Thankyouverymuchforyourkind
help.
Reply
32.avtarsingh says:
May27,2013at10:44am
Dearsir,oneconfusionisthatifmyconectedloadis450kwandconsumptionis307kwhthenwhat
theratingofincommingtransformerpleasetellmebrief.
Reply
33.Bala says:
September22,2013at5:56am
ThankYouMr.JigneshParmar.
Reply
34.pritchitroda says:
October3,2013at6:04pm
veryusefullthingsuhavegiven,thanks,
Reply
35.saad says:
November2,2013at8:04am
24 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
thankyouverymuch.
Reply
36.atest says:
November12,2013at7:52am
thisisatest
Reply
37.aki says:
November25,2013at8:17am
thankuuu
Reply
38.haseebullha says:
November25,2013at12:51pm
niceandsimpleinformationthanksforyoureort
Reply
39.irdanraybodiongan says:
January17,2014at8:44am
whatisthedemandfactorandloadfactorfordraftingroom?
Reply
40.AlbertoGasmen says:
February24,2014at8:21pm
Basically,thesedatafortheDEMANDandDIVERSITYfactorsareexcellentinfoforafast
estimationofPOWERSUPPLY,CABLE/WIRESIZES,manythanks
Reply
41.souvik says:
March22,2014at8:56am
thanksforthearticle..ithelpedme.thanks
Reply
42.SPSarathy says:
March23,2014at12:46pm
Youreortislaudable.Westandtogainwithyoursharinginasimpleway.
Reply
43.ashokchaudhary says:
September7,2014at6:00am
thanksforusefulAndapplicablekno
wlge
Reply
44.HarishKumarJohri says:
September8,2014at5:10am
ThankyouMr.Jignesh!NiceexplanationsoftheseElectricityfactorsinoneArticle.
HarishKumarJohri,L&TFaridabad.
Reply
25 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
45.Rafiq says:
September21,2014at5:55pm
Thanksforthisnote,hopefullycaniknowwhatisyourreferenceforthisImgladto
knowthanksinadvance
Reply
46.Godfrey says:
November15,2014at8:45am
Amappreciationforthisprovisionoftheinfomatiomaboutdiversityfactorbcauseitsalwaysdicult
tofindreliablenotesforthistopic.
Reply
47.DaramolaDele says:
November23,2014at7:00am
yourarticleisalwaysedifyingmystudies.MayGodBlessyoumoreandmore
Reply
48.DaramolaDele says:
November24,2014at10:06am
howcangetthispaper
Reply
49.MahmoudElghazaly says:
December29,2014at11:14am
thankyouverymuchforsuchvaluableinformations
Reply
50.Rajesh says:
January19,2015at12:12pm
Verysimpleexplanationandreallyvaluable.
Thisisanantibioticformyknowledge
Reply
51.zak says:
March2,2015at12:57pm
dearJignesh
ihaveasmallquestionregardingthetransformers.
ineedtoknowaccordingtoNECwhatisthepercentagetobeloadedforthecapacityofa
transformer.
Asapracticewealwaysconsider80%oftotalkvaofatransformer.
ex.ifwehave1600kvat/rthenwecanuse1600*80%=1280kva.
wecanuseonly1280kvainsteadof1600kva.supooseyourtotalloadis1400kvathenyouhavetogo
tohighersizethatis2000kva.
Reply
52.usman says:
April2,2015at7:12am
niceeortformakingitunderstandabletonontechnicalalso..
26 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
Reply
53.RAJNISHKUMAR says:
April22,2015at9:30am
Sir,thanksforprovidingusefulinformationasithelpsinpreparationofamie
Reply
54.monacodelpasao says:
June16,2015at5:38am
greatnotesbutalotofspellingmistakes
Reply
55.avnishkumar says:
July6,2015at9:41am
iamplantengineer(electrcial).disconceptalwayswerusing,soundestandtheLF,DFetc..
Reply
56.thongraty says:
August4,2015at8:46am
Dearsir,
Actuallysir,CouldyoupleasemoredetailformeaboutwhatistheKuandWhatistheKscosistill
confusewithwhatyoushowedabove.
Bestregard,
Reply
57.8463838172 says:
August22,2015at2:55pm
siriamelectricalengg.studentiwanttowriteresearchpaperonruralelectricitysocouldyouhelp
me
Reply
58.sourabhvishwakarma says:
November9,2015at7:37am
thankyouforthisinformationbutihaveanQuestion:ifihave2000kwconnectedloadthanhow
muchkvatransformerweshoulduseeitherhigherfrom2000kworbelow.accordingtoyour
calculationitgiveverylowcapacitycapacityoftransformer.pleasereply.
Reply
59.kimdongmin says:
December15,2015at1:46am
Thankyouforsharingyourknowledge!!
Reply
60.Nandakumar.R says:
December30,2015at1:33pm
DearMr.Jignesh.Parmar
Thankyouforyourideaandimplementationofsharingyourexperience&knowledgeandhelp
technicalenthusiaststolearnmore.
GREATTHINKING;GREATJOB!
27 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
Reply
61. says:
February7,2016at9:34am
+32.thanksverygoodsite,thankforhelp
Reply
62.ChandrakantGhan says:
February12,2016at9:07am
ChandrakantGhan:
DearMr.Parmar,AveryusefularticleandclearsmanydoubtsaboutthefactorsinElectrical
isntalltion.
Thanksforsucharticle.
Regards
Reply
63.sunny says:
May12,2016at5:52am
whatisthecapacityoftransformerfor33000sqfeetareaplssuggested
Reply
64.AboderinSulaiman says:
June1,2016at3:33pm
DearMrParmar
WearecurrentlyworkingonaprojectforLagosStateMinistryofHousingatotalof53blocks.Each
blockisafourfloorscomprisesof8Nos1bedroomflat(2nosperfloor)onawingand8Nos2
bedroomflat(2Nosperfloor)ontheotherwing.Thetotalloadforeachblockis478.4KWandforall
the53blocks,thetotalloadwas25,355.2KWi.e25.355MW.
SelectingTransformersfortheEstate:
Adiversityfactorof0.8(1.25)wasapplyforeachblockandaloadfactorof0.3wasusedforthe
entireestate,enblock
ThetotalutilityfactorappliedfortheentireEstateis0.8multiplyby0.3=0.24
TotalestimatedloadforselectionofTransformeris25.355MWX0.24=6.085MW
Applyingpowerfactorof0.8,estimatedloadinKVA=7,606KVA
NumberofTransformerrequired(AssumedeachselectedTransformerisof(500KVA)=
7,606/500No=15.2say16Noof500KVAwillberequiredfortheEstate.
IneedyouradviceandIwanttoknowifthereisaRegulationthatconfirmtheaboveapplication
factorforfinalload(Estimated)asdoneabove.
IwanttoknowifIamontherighttrackconsideringyourdefinitionofdiversityfactor,loadfactor
etc.
Baseontheabovecalculationwhatisthesizeofthemaininjectionsubstationthatwillsupplythe
28 of 29 2/20/2017 6:39 PM
Demand Factor-Diversity Factor-Utilization Factor-Load Factor | Electric... https://electricalnotes.wordpress.com/2011/10/31/demand-factor-diversit...
entireestate.Thankyou.
ThankyouasIexpecttohearfromyousoonest.
Reply
65.DeepakM.R. says:
July28,2016at6:38am
ThanksalotSir.Theseinformationwereveryuseful.
Reply
66.venkat says:
August26,2016at11:51pm
IliketoreadyouranswersiwouldliketoSizeofGeneratorformynewPlant.Pladvicehowto
arrivecorrectsizeofDGset.similarly,ifiwanttodosamefromrunningplant,plspecifythesame
also..thanks..venkat
Reply