Professional Documents
Culture Documents
Customizedtrippingcurve
PE0
Defined point by point using the SFT2841 setting and operating software tool, this
curve may be used to solve all special cases involving protection coordination or
revamping.
3
Customized tripping curve set using SFT2841 software.
IECcurves
Equation Curvetype Coefficient values
k a b
Standard inverse / A 0.14 0.02 2.97
k T
t d( I) = ---------------------- --- Very inverse / B 13.5 1.50
--I--- 1 b
a
Long time inverse / B 0 13.33
Is
Extremely inverse / C 0 0.808
Ultra inverse 315.2 2.5
RIcurve
Equation: 1 T
td ( I ) = -------------------------------------------------------- -------------------
I 1 3 ,1706
0 ,339 0,236 -----
Is
IEEEcurves
Equation Curvetype Coefficient values
A B p b
Moderately inverse 0.010 0.023 0.02 0.241
A T Very inverse 3.922 0.098 0.138
td ( I ) = ------------------------ + B ---
I p b Extremely inverse 5.64 0.0243 0.081
-Is
---
1
IEEEcurves
Equation Curvetype Coefficient values
A B C D E b
Inverse 0.208 0.863 0.800 -0.418 0.195 0.297
B D E T Very inverse 0.090 0.795 0.100 -1.288 7.958 0.165
td ( I ) = A + -------------------- + ----------------------- + ----------------------- x -----
---I- C ---I-- C
2
---I-- C b
3 Extremely inverse 0.004 0.638 0.620 1.787 0.246 0.092
Is Is Is
0
2CDC021004S0014
2CDC021046S0014
The miniature circuit breaker SU 200 M Features
High performance MCB with 10 kA interrupting capacity
is ABBs solution for UL 489 branch acc. to UL 489 / CSA 22.2 No. 5 and 15 kA breaking
circuit protection up to 480 Y/277 V AC capacity acc. to IEC/EN 60947-2
and 96 V DC. This circuit breaker is Certified up to In = 40 A at 480 Y/277 V AC acc. to
UL 489 / CSA 22.2 No. 5
an all-round device for AC and DC Certified for AC and DC use acc. to UL and CSA
applications for universal use in North 40 C reference temperature acc. to UL and CSA
American and global markets due to Current limiting acc. to UL 489
Clear contact position indication in red/green (real CPI)
its approvals acc. to the international
standards UL, CSA and IEC. Moreover, Standards and approvals
SU 200 M is fully compatible with Standards
System pro M compact UL 489 UL 489
accessories. CSA 22.2 No. 5
IEC/EN 60947-2
Approvals
UL 489 US
CSA 22.2 No. 5 CA
VDE DE
CCC CN
Miniature Circuit Breaker SU 200 M
Technical data
General Data
Standards UL 489, CSA 22.2 No. 5, IEC/EN 60947-2
Poles 1P, 2P, 3P, 4P
Tripping characteristics C, K, Z
Rated current In 0.2 - 63 A
Rated frequency f 50 / 60 Hz, DC (0 Hz)
Rated insulation voltage Ui acc. to IEC/EN 60664-1 250 V AC (phase to ground), 440 V AC (phase to phase)
Overvoltage category III
Pollution degree 3
IEC/EN 60947-2
Rated operational voltage Ue 1P: 230 V AC; 2P, 3P, 4P: 400 V AC
Max. power frequency recovery voltage Umax AC 1P: 253 V AC; 2P, 3P, 4P: 440 V AC
Min. operating voltage 12 V AC, 12 V DC
Rated ultimate short-circuit breaking capacity Icu 15 kA
Rated service short-circuit breaking capacity Ics 40 A: 11.25 kA
> 40 A: 7.5 kA
Rated impulse withstand voltage Uimp (1.2/50s) 4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m)
Dielectric test voltage 2 kV (50 / 60Hz, 1 min.)
Reference temperature for tripping characteristics 30 C
Electrical endurance In < 30 A: 20,000 ops (AC), In 30 A: 10,000 ops. (AC);
1 cycle (2 s - ON, 13 s - OFF, In 32 A), 1 cyle (2 s - ON, 28 s - OFF, In > 32 A)
UL / CSA
Rated voltage AC 1P: 277 V AC up to 40 A for C, Z char.,
AC 277 V AC up to 35 A for K char., 240 V AC
AC 2P, 3P, 4P: 480 Y / 277 V AC up to 40 A for C, Z char.,
AC 480 Y / 277 V AC up to 35 A for K char., 240 V AC
DC 1P: 48 V DC; 2P: 96 V DC (2p in series)
Rated interrupting capacity acc. to UL 1077
Short-circuit current rating acc. to UL 489 10 kA
Application
Reference temperature for tripping characteristics 40 C
Electrical endurance 6,000 ops (AC), 6,000 ops. (DC); 1 cycle (1 s - ON, 9 s - OFF)
Mechanical data
Housing Insulation group II, RAL 7035
Toggle Insulation group II, black, sealable
Contact position indication Real CPI (green OFF / red ON)
Protection degree acc. to DIN EN 60529 IP20*, IP40 in enclosure with cover
Mechanical endurance 20,000 ops.
Shock resistance acc. to IEC/EN 60068-2-27 25 g - 2 shocks - 13 ms
Vibration resistance acc. to IEC/EN 60068-2-6 5g - 20 cycles at 51505 Hz with load 0.8 In
Environmental conditions (damp heat cyclic) acc. to IEC/EN 60068-2-30 28 cycles with 55C/90-96% and 25C/95-100%
Ambient temperature -25 +55C
Storage temperature -40 ... +70 C
Installation
Terminal Failsafe bi-directional cylinder-lift terminal
Cross-section of conductors (top/bottom) solid, stranded: 35 mm / 35 mm
flexible: 25 mm 2 / 25 mm2
18 4 AWG
Cross-section of busbars (top/bottom) 10 mm / 10 mm
18 8 AWG
Torque 2.8 Nm
AWG 18-16: 13.3 in-lbs.
AWG 14-10: 17.7 in-lbs.
AWG 8-4: 39.8 in-lbs.
Screwdriver No. 2 Pozidrive
Mounting On DIN rail 35 mm acc. to EN 60715 by fast clip
Mounting position any
Supply optional
Dimensions and weight
Mounting dimensions acc. to DIN 43880 Mounting dimension 3
Pole dimensions (H x D x W) 111 x 69 x 17.5 mm
Pole weight approx. 125 g
Combination with auxiliary elements
Auxiliary contact Yes
Signal contact Yes
Shunt trip Yes
*
Also fulfilling the requirements acc. to the protection degree IPXXB
2 - 2CDC002177D0202
Miniature Circuit Breaker SU 200 M
Tripping characteristics
Tripping characteristics
Acc. to Tripping Rated Thermal release 1)
Electromagnetic release 2)
characte- current
ristics
Currents: Tripping Range of Tripping time
conventional conventional time instantaneous
non-tripping tripping tripping
current current
In I1 I2
IEC/EN 60947-2 C 0.5 to 63 A 1.05 I n >1h 5 In > 0.2 s
1.3 In <1h 3)
10 In < 0.2 s
K 0.2 to 63 A 1.05 I n >1h 10 In > 0.2 s
1.3 In <1h 3)
14 In < 0.2 s
Z 0.5 to 63 A 1.05 I n >1h 2 In > 0.2 s
1.3 In <1h 3)
3 In < 0.2 s
1)
The thermal releases are calibrated to a nominal reference ambient temperature of 30 C.
In the case of higher ambient temperatures, the current values fall by approx. 6 % for each 10 K temperature rise.
2)
The indicated tripping values of electromagnetic tripping devices apply to a frequency of 50/60 Hz. The thermal release operates independent of frequency.
3)
As from operating temperature (after I1 > 1h)
2CDC022004F0214
2CDC022005F0214
2CDC002177D0202 - 3
Miniature Circuit Breaker SU 200 M Derating
Deviating ambient temperature
The rated value of the current of a miniature circuit breaker of following table shows derating factors for ambient temperature
SU 200 M series refers to a reference ambient temperature of from -40 C to 70 C for the characteristics C, K, Z.
30 C acc. to IEC/EN 60947-2 and 40 acc. to UL/CSA. The
4 - 2CDC002177D0202
Miniature Circuit Breaker SU 200 M Derating
Internal resistance and power loss
2CDC002177D0202 - 5
Miniature Circuit Breaker SU 200 M
Current limiting I peak and I2t values acc. to UL 489
A kA kA 2S
SU203M-K0.2 480Y/277 10000 0.45-0.5 3 0.026 0.008
SU203M-K7 480Y/277 4095 0.45-0.5 3 2.3 11.9
SU203M-K7 480Y/277 7500 0.45-0.5 3 3.4 16.7
SU203M-K7 480Y/277 10000 0.45-0.5 3 4.6 19.0
SU203M-K20 480Y/277 4095 0.45-0.5 3 2.9 18.1
SU203M-K20 480Y/277 7500 0.45-0.5 3 4.3 28.1
SU203M-K20 480Y/277 10000 0.45-0.5 3 6.4 34.6
SU203M-K35 480Y/277 4095 0.45-0.5 3 3.4 27.9
SU203M-K35 480Y/277 7500 0.45-0.5 3 4.7 33.1
SU203M-K35 480Y/277 10000 0.45-0.5 3 9.0 72.0
SU203M-C40 480Y/277 4095 0.45-0.5 3 3.4 22.8
SU203M-C40 480Y/277 7500 0.45-0.5 3 5.1 42.5
SU203M-C40 480Y/277 10000 0.45-0.5 3 9.3 74.6
SU201M-K0.2 277 10000 0.45-0.5 1 0.7 0.092
SU201M-K7 277 4095 0.45-0.5 1 2.5 10.5
SU201M-K7 277 7500 0.45-0.5 1 3.4 16.9
SU201M-K7 277 10000 0.45-0.5 1 3.4 14.5
SU201M-K20 277 4095 0.45-0.5 1 2.8 14.7
SU201M-K20 277 7500 0.45-0.5 1 4.1 23.5
SU201M-K20 277 10000 0.45-0.5 1 4.7 32.5
SU201M-K35 277 4095 0.45-0.5 1 3.0 19.8
SU201M-K35 277 7500 0.45-0.5 1 4.7 36.5
SU201M-K35 277 10000 0.45-0.5 1 4.4 22.1
SU201M-C40 277 4095 0.45-0.5 1 3.6 22.9
SU201M-C40 277 7500 0.45-0.5 1 5.3 52.6
SU201M-C40 277 10000 0.45-0.5 1 5.9 44.9
SU203M-K63 240 4095 0.45-0.5 3 3.6 19.9
SU203M-K63 240 7500 0.45-0.5 3 5.1 33.0
SU203M-K63 240 10000 0.45-0.5 3 6.3 43.3
SU201M-K63 240 4095 0.45-0.5 1 3.9 33.8
SU201M-K63 240 7500 0.45-0.5 1 5.2 43.8
SU201M-K63 240 10000 0.45-0.5 1 6.5 61.8
6 - 2CDC002177D0202
Miniature Circuit Breaker SU 200 M
Accessories and dimensional drawing
Accessory overview
SU 200 M
Dimensional drawing
2CDC022007F0014
2CDC002177D0202 - 7
Miniature Circuit Breaker SU 200 M
Ordering data characteristic C
8 - 2CDC002177D0202
Miniature Circuit Breaker SU 200 M
Ordering data characteristic C
2CDC002177D0202 - 9
Miniature Circuit Breaker SU 200 M
Ordering data characteristic K
10 - 2CDC002177D0202
Miniature Circuit Breaker SU 200 M
Ordering data characteristic K
2CDC002177D0202 - 11
Miniature Circuit Breaker SU 200 M
Ordering data characteristic Z
12 - 2CDC002177D0202
Miniature Circuit Breaker SU 200 M
Ordering data characteristic Z
2CDC002177D0202 - 13
Contact us
You can find the address of your We reserve all rights in this document and in
local sales organization on the the subject matter and illustrations contained
ABB home page therein. Any reproduction, disclosure to third
http://www.abb.com/contacts parties or utilization of its contents in whole
-> Low Voltage Products and Systems or in parts is forbidden without prior written