SUPPLY OF PLCC TERMINAL WITH

ETL-41 SYSTEM

GUJARAT ENERGY TRANSMISSION CORPORATION


LTD.
SARADAR PATEL VIDYUT BHAVAN,
RACE COURSE, BARODA 390 007.

TECHNICAL SPECIFICATIONS

FOR

PLCC TERMINAL WITH ETL-41 SYSTEM

GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012

Page 1 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM

(A) SPECIAL INSTRUCTIONS TO BIDDER

Please read following instructions carefully before submitting your bid.

1. All the drawings, i.e. elevation, side view, plan, cross sectional
view etc., in AutoCAD format and manuals in PDF format, for
offered item shall be submitted. Also the hard copies as per
specification shall be submitted.

2. The bidder shall submit Quality Assurance Plan for manufacturing


process and Field Quality Plan with the technical bid.

3. The bidder shall have to submit all the required type test reports for
the offered item. In case of non-submission of the type test reports
with the offer, the bid shall be liable to be rejected.

4. The bidder must fill up all the point of GTP for offered item/s.
Instead of indicating refer drawing, or as per IS/IEC, the exact
value/s must be filled in.

5. All the points other than GTP, which are asked to confirm in
technical specifications must be submitted separately with the bid.

6. The bidder is required to impart training in view of manufacture,


assembly, erection, operation and maintenance for offered item, at
his works, to the person/s identified by GETCO, in the event of an
order, free of cost. The cost of logistics will be bear by GETCO.

7. Please note that the evaluation will be carried out on the strength of
content of bid only. No further correspondence will be made.

8. The bidder shall bring out all the technical deviation/s only at the
specified annexure.
9. The bidder should indicate manufacturing capacity by submitting latest
updated certificate of a Chartered Engineer (CE).

Page 2 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM

(B) QUALIFYING REQUIREMENT DATA


(For Supply)

Bidder to satisfy all the following requirements.

1) The bidder shall be Original Equipment Manufacturer


(OEM). The offered equipment have to be designed,
manufactured and tested as per relevant IS/IEC with latest
amendments.

2) The minimum requirement of manufacturing capacity of


offered type, size and rating of equipment shall be 7 times
tender / bid quantity. The bidder should indicate
manufacturing capacity by submitting latest updated
certificate of a Chartered Engineer (CE).

3) Equipment proposed shall be of similar or higher rating and


in service for a minimum period of THREE (3) years and
satisfactory performance certificate in respect of this is to be
available and submitted.

4) The bidder should clearly indicate the quantity and Single


Value Contract executed during last FIVE (5) years, for the
offered equipment. Bidder should have executed one single
contract during last five years for the quantity equivalent to
tender / bid.
The details are to be submitted in following format,

Sr. ITEMS ORDER ITEMS ORDER FULLY STATUS, IF REMARK


No SUPPLIED REFERENCE QUANTITY EXECUTED ORDER UNDER
TO No. & DATE YES/NO EXECUTION

5) Equipment offered shall have Type Test Certificates from


accredited laboratory (accredited based on ISO/IEC Guide
25 / 17025 or EN 45001 by the National accredition body of
the country where laboratory is located), as per IEC / IS /
technical specifications not older than FIVE (5) years and
shall have validity till expiry of validity of technical bid.

Page 3 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM

(I) GENERAL :

Indoor PLCC Equipments are required for important 400KV,


220KV and 132KV Sub/station for Speech, Data Transmission,
Protection and Teleprinter Links.

(II) GENERAL REQUIREMENT :

The equipments shall be of latest components, technology and


highly reliable. The equipments offered must have been type
tested.

(III) SCOPE OF SUPPLY :

PLCC TERMINAL WITH Single or DUAL 19 RACK OF


ETL-41 SYSTEM as per schedule of requirement, 4 Wire
Telephone, Dummy Load Print for testing of ETL-41 SYSTEM on
Loop, 75 Ohm Cylindrical Balance Load, 4 Nos. of UHF
Connector (UHF Gland), Emergency test tone calling jack handset,
industrial good quality single phase A.C exhaust fan for cooling of
carrier terminal under operation, Operating instruction manual,
Programming & tuning procedure manual etc., all are included in
scope of supply. The Carrier equipment shall be supplied with
fully wired complete in all respect with all interconnections
between equipments wherever necessary and terminal blocks
required for termination of external wiring or to provide
interconnection between equipments to be integrated along with
steel channels with fixing nut/screws. The internal co-axial
loop with UHF gland of sufficient length for HF signal
connectivity between two racks of ETL-41 system in
case of panel with dual rack shall also be provided. The
equipment shall be of latest design with motherboard construction.
You will have to impart free training of ETL version carrier
equipments to at least 3 to 4 telecom engineers of G.E.T.C.O to get
acquainted with the technology for our new incumbents.

(IV) SPECIFICATION :

The equipments to be supplied under this specification shall


function satisfactorily under tropical, hot, humid, salty and
chemically polluted climatic condition with adverse temperature

Page 4 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM

condition. The equipment shall be manufactured and tested as per


latest national or international standard (IS, IEC, CCITT, CIGRE,
etc.) whichever is better. This will be clearly brought out by the
bidder. The equipments offered shall confirm to, but not limited to
following standards.

(1) IEC 495 - Single sideband Power Line Carrier Terminals.

(2) IEC 834-1/1988 - Performance & Testing of teleprotection


(Part-I) equipments of Power system - Narrow band
Command system.
(3) IEC 68-2-3/1969 - Environmental Testing Part-2 Tests section-3
Test Ca: Damp heat steady state.

In addition to the above, the carrier terminal shall be manufactured


and supplied detailed as under:

(IV)(A) CARRIER TERMINAL EQUIPMENT :

It will be multipurpose equipment to transmit and receive speech,


data, protection, tele-operation, telemetry, and facsimile signals. It
will be manufactured and supplied as per following details.

The "Carrier Cabinet" shall be multipurpose cubicle suitable to


accommodate carrier equipment, electronic group selector,
protection coupler, modems for data transmission, DC to DC
convertor and band pass filters etc.

All the equipments details as above shall fit into different tiers of
the "Swinging Frame" fitted inside the above cubicle, swinging
frame shall be of 14 SWG sheet steel.

All the equipments fitted in above swinging frame shall be fully


wired. It should be possible to test the equipment from front side
and erect the cubicle side-by-side or back-to-back.

The cubicle shall be made from 16 SWG sheet steel. It will have
rounded corners with front door and lock. It will be designed for
efficient cooling with an exhaust fan at the top inside the cabinet, to
take away the heat generated within the terminal. Normally the
cable entry shall be from the bottom, however, suitable provision

Page 5 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM

shall be made for cable entry from top, which shall be covered by
blanking plate at the time of supply. Visual indication shall be
provided in front of the terminal at the top for indication of failure
of carrier terminal i.e. Transmitter, Receiver or Power supply.
There shall be provision for audio indication also. Suitable labels
for identification of indication shall be provided.

The cubicle shall be provided with foundation holes for fixing the
same on foundation. Air inlet shall be provided at bottom and Air
Outlet with exhaust fan at the top. Any opening shall be provided
with wire mesh for vermin proofing. The cubicle shall be
completely dust proof and vermin proof.

The cubicle shall go through seven-tank phosphating process and


shall be coated with two coats of red oxide primer followed by
synthetic enamel.

2 Nos. vertical C-Channels with slotted angles and sufficient no.


of horizontal channels with holes shall be provided inside the
cubicle at backside for wiring purpose suitable for system
capacity of twin 19 rack of ETL-41.

The cubicle size shall generally match with existing cubicle and
shall be of size 1960mm X 670 mm X 420 mm (Height x Width x
Depth). It shall be provided with standard 19" tiers to house the
modules.

Three ways HF co-axial clamp with terminal shall be provided


inside the cubicle at rear side.

One 8 way electrical connector, a three-pin plug with fuse shall be


provided for 250 V AC 3 Phase 50 C/S supply. The cubicle shall
be fully wired. Arrangement for internal lighting shall be provided
using 15-Watt fluorescent tube of Philips make.

The equipment shall be supplied with arrangement suitable


to operate either on 48V DC or 220V DC supply as per
requirement provided in SCHEDULE OF REQUIREMENT
OF respective tender with voltage variation from - 15% to +
20% and ripple of < 2 % maximum.

Page 6 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM

The carrier power supply module shall be provided with a circuit


breaker, which shall automatically trip due to over voltage to
carrier equipment and/or over modulation. The circuit breaker
shall be provided in front of power supply module so that it is
easily accessible. This circuit breaker shall be provided with a
facility to switch on and to switch off the same mechanically by
hand, by pressing and releasing a push button switch. A fuse shall
also be provided in series of this circuit breaker, which shall
operate in case of failure of the circuit breaker.

Amplitude Modulation, single side band, 40W (which can be


programmed for 20w/10w/5w, if required) peak envelope power at
co-axial output including pilot and if any other carrier signal shall
be provided. HF range shall be 40 kHz to 500 kHz. The
equipments are meant for multipurpose application like speech,
data, teleprinter and control command facility. The requirement of
IS 9528 and IEC 663 shall be fulfilled for accurate transmission of
control command, data and TP signals.

A central frequency synthesizer, whose basic frequency is obtained


from a crystal-controlled oscillator with very high frequency
stability, shall generate the necessary frequencies required in
carrier terminal. Thus a synthesized version carrier set shall be
preferable.

Carrier terminal shall be multipurpose, fully transistorized IC


version with modular construction and mother board technique,
fully programmable i.e. pilot frequency, audio freq. & carrier freq.
with synchronizer and highly efficient for adjacent channel
working to overcome frequency congestion problem.

It will be suitable for 2-Wire services and Hand set/Emergency call


telephone, which can be used for "Audio Test", shall be provided
with necessary circuitry etc., together with handset.

The transmitter shall be provided with 3 teleoperational input


minimum (in addition to speech and protection input), which shall
be fully decoupled and adjustable for level setting. Preferably
inputs shall be through disconnectible links to avoid use of
soldering irons for soldering and desoldering of wires from
terminal block. Minimum separate tunable teleoperational output

Page 7 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM

shall be provided, for the normal 600-Ohm termination.

Suitable facility for transit connection of teleoperational channel


shall be provided. Additional outputs may be provided for this
purpose.

The "Signal Boosting" facility shall be provided for important


signals like "Protection of Tele-operational signals". The speech is
disconnected and entire output is available for protection signals.
The bidder shall describe the arrangement provided.

A built in "PLC EQUALIZER" shall be provided to overcome


effect of amplitude distortion due to mismatch etc. Equalization
facility for auxiliary carrier shall be described in details.

A supervision module with necessary circuitry shall be provided to


monitor Transmitter, Receiver and Power supply. Both the
collective alarm and individual alarm shall be provided. Audio and
Visual indication shall be preferable. The indication for squelch
operation is necessary. Suitable potential free contact shall be
provided for external alarms. The bidder shall describe in detail
indications, internal alarm and external alarms provided.

A module with built-in meter and oscillator with selector switch


shall be provided with necessary circuitry to test and commission
the PLC link without the help of an external signal for ease of
inspection and testing. A cylindrical dummy load, dummy load
print for testing shall be in the scope of supply. It shall be possible
to test the equipment locally by a dummy load. It is preferable that
equipment is provided with facility to test transmitter and receiver
locally by connecting them back-to-back. Any extra optional print
required for such type of test shall be in the scope of supply. Built-
in AGC test for HF level variation of + 14 dB/-26 dB may be
necessary. The local testing facility provided shall be described in
detail by all bidders. The 4 Wire express telephone instruments
shall also be in the scope of supply. The bidder shall have to
provide training to four personals of GETCO on all the equipments
covered under this specification free of cost at their works.

All the test points with standard values, indications etc. shall be
provided in front of the cabinet and shall be easily accessible.

Page 8 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM

All the bidders should furnish full technical particulars of their


equipment as indicated in Schedule-"A" attached.

The carrier terminal shall have a 4 kHz bandwidth so that it is


compatible with UHF/Microwave equipment. Speech shall use
bandwidth up to 2 kHz. The rest of the band shall be utilized for
teleoperational channels. The bidder shall indicate possible
number of teleoperational channels with speed. The pilot
frequency shall be above 3600 Hz and should be programmable.

The bidder shall indicate Frequency Spacing required between


Transmit and Receive bands for parallel working of a number of
Carrier Terminals on a Common Line. This will be indicated in
Schedule-A attached.

Low Power consumption shall be desired feature to maintain


healthy communication during system disturbance.

The equipment shall be suitable for co-axial cable having


impedance of 75/125-Ohm unbalanced or 150-Ohm balance. This
should be programmable.

Carrier Terminal shall be provided with 4-wire jack; dummy load


module, and 75/125-Ohm load in loose.

Carrier Terminal shall have in built Digital Transit Filter with


programmable frequency and also in built Compressor and
Expander for improving the S/N ratio.

The equipment must have gone through all environmental and field
tests and shall work satisfactorily under hot, humid and polluted
climate. It should have worked for at least five years successfully
in Electricity Boards. It shall work satisfactorily up to 55 C. It
shall satisfy a storage temperature of 70 C. The Temperature
criteria shall be shown by laboratory test by using hot chamber
during inspection.

The equipment shall be provided with a nameplate in front of


cabinet indicating make, serial no., Transmit and Receive

Page 9 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM

frequency and station Direction. The module layout and station


direction and Transmit-Receive Frequency shall be indicated
behind the door.

Bidder shall indicate guaranteed values for carrier terminal offered


by him. This shall be indicated in Schedule-A attached.

The bidder may quote different models being manufactured by


them, which are equivalent to or better than the specified.

(IV)(B)

(1) Any deviation shall only be indicated in Schedule-A/1


attached with this specification.
(2) The GETCO reserves right to increase or decrease the
quantity at the time of placing the order.
(3) The GETCO reserve right either to accept or reject
any of the offers without assigning the reason.

(V) CONFIGURATION:

The Configuration of 40 Watt Single Channels, Fully


Programmable Carrier Equipment Type ETL-41 shall have
following different cards/prints.

B5LA : Power Supply Unit


N3NL : Test Meter
E5LA or E5LB: Tx-Filter (Detail of model will be
decided later on & based on Tx/Rx frequencies).
P3LA : RF Hybrid
B4LA : 48V DC/DC Converter
O4LA + E1LA : Tele Control Interface
O4LC : 2/4 Wire PAX Interface
P4LA : Pilot and Supervision
P4LB : AF Converter
P4LC : IF Converter
P4LD : Rx RF Converter
P4LF : Tx RF Converter
P4LG : Carrier Generator
P1LA : RF Amplifier

Page 10 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM

P3LK : Dummy Load Print


Any other card/print required for proper working of
carrier terminal.

(VI) TYPE TESTS:

Valid type test reports not older than 5 Years and shall be valid
up to expiry of validity of offer for following tests along with
all test results sheets & reference documents shall be submitted
with the offer with List of Type Tests in Performa- X given here
under.

Performa X:

Sr. Test Description of Applicable Test report Remarks


No. Equipment test conducted Standard/ No. & Name
Clause of test
laboratory
1. 2 3 4 5 6

1. Voltage variation test


2. Carrier frequency range & band
3. Frequency Accuracy
4. Transmit/receive frequency Difference
5. Automatic gain control
6. Harmonic Distortion
7. Selectivity
8. Nominal impedance, return loss and tapping loss
9. Balance to Ground
10. Limiter action
11. Spurious emission
12. Carrier frequency levels
13. Attenuation Distortion
14. Noise Generated within Terminals
15. Near end/Far end Cross Talk
16. Group Delay Distortion
17. Conducted noise
18. Telephone Signaling Channel Distortion
19. Speech Levels

Page 11 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM

20. Voltage withstand test and Insulation test


21. Teleprotection interface
22. Input and Output level
23. Speech band
24. Frequency band above speech band
25. EMI/EMC tests
26. Conducted emission
27. Radiated emission
28. Radiated Susceptibility Amplitude modulated
29. Electrostatic Discharge
30. Electrical Fast Transient (EFT)
31. High Frequency Disturbance test
32. Storage test
33. Dry Heat test
34. Cold test
35. Damp heat test
36. Impulse withstand
37. Power Supply variations

(VII) DRAWINGS:

Following Drawings shall be submitted with the offer.

1. Module Layout For ETL 41 : Unit Arrangement


2. Cabinet Layout For ETL 41
3. Wiring Diagram For ETL 41 (DC Supply & Alarm)

The list of drawings that require to be submitted for


approval on receipt of A/T from GETCO is as under.

1. Module Layout for ETL-41


2. Cabinet Layout for ETL-41 (Single or Dual 19 rack)
3. Cabinet wiring diagram (Single or Dual 19 rack)
4. Cabinet General Dimensional Drawing
5. External termination for ETL-41 (Single or Dual rack)
6. List of accessories

Page 12 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM

S C H E D U L E "A"
SCHEDULE OF GENERAL TECHNICAL DATA AND
GUARANTEED TECHNICAL PERTICULARS
( TO BE FURNISHED BY THE BIDDER FOR CARRIER TERMINAL)
Sr. SYSTEM PARTICULAR TECHNICAL
No. PARTICULAR OF
BIDDER'S EQUIPMENT
1. Name of OEM
2. Type/Model
3. Operating Mode
4. HF Band
5. Nominal Bandwidth
6. Send / Receive Band
7. Permissible line attenuation
8. Frequency spacing for parallel
Working on a common line
9. HF System Impedance
10. Carrier Frequency Stability
11. Useful AF Bandwidth
12. Frequency Response
13. Linearity
14. Non - Linear Distortion
15. Near and Far End Crosstalk
16. Crosstalk Attenuation (Double channel)
17. Group delay
18. Basic Noise
19. Audio Frequency difference
Transmit to receive
20. Supervision alarms
21. Alarm Outputs
22. Ambient Conditions:
(a) For guaranteed data
(b) For reliable operation
(c) Storage

Page 13 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM

S C H E D U L E "A"
SCHEDULE OF GENERAL TECHNICAL DATA AND
GUARANTEED TECHNICAL PERTICULARS
( TO BE FURNISHED BY THE BIDDER FOR CARRIER TERMINAL)
Sr. SYSTEM PARTICULAR TECHNICAL
No. PARTICULAR OF
BIDDER'S EQUIPMENT
23. Transmitter Data
(a) HF Output Power
(b) Harmonic and Spurious Signal
Attenuation
(c) Pilot channel with Programmable
range of Frequency
(d) Speech Input: 2 Wire
4 Wire
(e) Limiter Characteristics
(f) Suppression of unwanted Side bands.
24. Telephone Criteria
(a) Signaling
(b) Transit / Terminal Switching (V)
(c) Hybrid Switching (GA)
(d) 4 - Wire remote / emergency Call
telephone
25. Teleoperation Signals:
(A) Teleoperation I/P's
(a) Number & type of I/P
(b) Number of I/P with
Boosting Facility.
(c) Nominal I/P level.
(d) I/P level range
(e) Balance referred to
ground
(f) Return loss
(g) Minimum level for
maximum RF output
power.
(h) Boosting criteria.

Page 14 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM

S C H E D U L E "A"
SCHEDULE OF GENERAL TECHNICAL DATA AND
GUARANTEED TECHNICAL PERTICULARS
( TO BE FURNISHED BY THE BIDDER FOR CARRIER TERMINAL)
Sr. SYSTEM PARTICULAR TECHNICAL
No. PARTICULAR OF
BIDDER'S EQUIPMENT
(B) Teleoperation O/P's
(a) Number & type of O/P's
(b) Nominal O/P level
(c) O/P level range
(d) Maximum O/P level (PEP)
(e) Balance referred to ground
(f) Return loss
Whether teleoperation I/P's & O/P's
expandable by inserting additional interface
module.
Whether provision is made for Programmable
Digital transit Filter, which allow to pass
required Band & frequencies of Teleoperation
Signal.
26. Receiver Data
(a) HF Sensitivity at coax input and at
Relative system impedance (speech) :
Carrier Frequency
(b) Selectivity :
From 4 kHz Carrier Band
(c) Image rejection
(d) IF rejection
(e) Automatic gain control:
AF Output Level
Time constant for 10 dB level
variation
(f) Hunting characteristics :
Synchronizing channel bandwidth
With loss of synch. signal
(auxiliary carrier)
Synchronization time with
loss of signal for 1 second:
Describe the method of
synchronization

Page 15 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM

S C H E D U L E "A"
SCHEDULE OF GENERAL TECHNICAL DATA AND
GUARANTEED TECHNICAL PERTICULARS
( TO BE FURNISHED BY THE BIDDER FOR CARRIER TERMINAL)
Sr. SYSTEM PARTICULAR TECHNICAL
No. PARTICULAR OF
BIDDER'S EQUIPMENT
(g) Frequency response equalization
(h) Describe the method of Equalization
(i) Speech outputs:
2 wire
4 wire
Symmetry against ground
return loss
DC source resistance
(j) Signaling criteria :
(k) Pulse distortion :
(l) Squelch :
27. POWER SUPPLIES
(a) Mains
(b) Consumption
(c) Battery
(d) Consumption
(e) Reflected noise
28. TEST EQUIPMENT
(A) Test Tone generator : Test Tone
(B) Audio Tests :
(a) Band width
(b) Level range
(c) Input impedance
(d) Dummy load / test loop
(Whether print required for loop test is
provided)
(C) Any other test equipments required.
29. Insulation test and EMC:
(A) Unbalanced Carrier I/O
(a) impulse voltage test
(b) HF interference test
(c) Fast electrical transients/bursts

Page 16 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM

S C H E D U L E "A"
SCHEDULE OF GENERAL TECHNICAL DATA AND
GUARANTEED TECHNICAL PERTICULARS
( TO BE FURNISHED BY THE BIDDER FOR CARRIER TERMINAL)
Sr. SYSTEM PARTICULAR TECHNICAL
No. PARTICULAR OF
BIDDER'S EQUIPMENT
(B) Balanced Carrier I/O
(a) Voltage withstand
(b) Insulation resistance
(c) Impulse voltage test
(d) HF interference test
(e) Fast electrical transients/burst
FREQUENCY SPACING required for
operation of carrier Terminal on a common
line:
(a) Transmitting Band to Own
Receiving Band :
(b) Transmitting Band to neighboring
Transmitting Band :
(c) Transmitting Band to neighboring
Receiving Band :
(d) Receiving Band to neighboring
Receiving Band :

Page 17 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM

S C H E D U L E ' A/1
(To be filled in and signed by the Tenderer)

Schedule of deviations from Technical Specifications for ____________.

We / I have carefully gone through the Technical Specification and


we / I have satisfied ourselves / myself and hereby confirm that our / my
offer strictly confirm to the requirements of the Technical Specification
except for the deviations given below :

Sr.No. Description Stipulations Deviation Remarks


in Offered
specification

___________________________________________________________
Signature :

Name of Authorized signatory of the company :

Name of the tendering Company

Date :
Place:

Page 18 of 19
GETCO/E/TS-PLCC 03402/R1, Dt: 28.09.2012
SUPPLY OF PLCC TERMINAL WITH
ETL-41 SYSTEM

SCHEDULE OF REQUIREMENTS OF CARRIER


TERMINAL EQUIPMENT

Sr.No. Description Unit Quantity


1. 40Watt Single Channel, Fully Programmable No.
Carrier Equipment Type ETL-41 of ABB Make
suitable to operate on 48V DC and with 4-
Wire table telephone for ETL, Dummy Load Print
P3LK, 75 Ohm Cylindrical Load and 4 Nos. of
UHF Gland , Emergency jack handset as per
technical Specification.
2. 40Watt Single Channel, Fully No.
Programmable Carrier Equipment Type
ETL-41 of ABB Make suitable to operate
on 220V DC and with 4-Wire table
telephone for ETL, Dummy Load Print
P3LK, 75 Ohm Cylindrical Load and 4 Nos.
of UHF Gland , Emergency jack handset
as per technical Specification.
3. Carrier Terminal Equipment with Dual 19 No.
rack of 40Watt Single Channel, Fully
Programmable Carrier Equipment Type
ETL-41 of ABB Make suitable to operate
on 48V DC and with 4-Wire table
telephone for ETL, Dummy Load Print
P3LK, 75 Ohm Cylindrical Load and 4 Nos.
of UHF Gland , Emergency jack handset
as per technical Specification.
4. Carrier Terminal Equipment with Dual 19 No.
rack of 40Watt Single Channel, Fully
Programmable Carrier Equipment Type
ETL-41 of ABB Make suitable to operate
on 220V DC and with 4-Wire table
telephone for ETL, Dummy Load Print
P3LK, 75 Ohm Cylindrical Load and 4 Nos.
of UHF Gland , Emergency jack handset
as per technical Specification.

Page 19 of 19