Professional Documents
Culture Documents
Multi-line 2
4921240306A
Standard functions
kW sharing
Voltage gen./busbar (27/59)
kvar sharing
Frequency gen./busbar (81)
Engine control Load dependent start/stop
Configurable start/stop sequence Type B only
Run coil or stop coil Relay output at high load
Relay output at low load
Start/stop command
Remote (auto - digital input) Engine communication
Local (semi - display) Type B only
Automatic (time dependent) J1939 (see engine list, page 2)
MDEC (MTU)
DEIF A/S
Data sheet BGC-L Controller
Application BGC-L variants
The BGC-L is a microprocessor-based control unit Two variants of the BGC-L exist, type A and type B.
containing all necessary functions for protection of a
gen-set and control of the generator breaker. It contains Type A is the basic version giving the required
all necessary 3-phase measuring circuits and all values functionality for synchronising and load sharing with
and alarms are presented on the LCD display. governor and AVR control.
The BGC-L is a compact all-in-one unit designed for Type B is a unit with increased functionality of
island mode applications, i.e. stand-alone or load protections, start/stop functionality and engine
sharing with other gen-sets. communication.
Standard
Principle diagram
+ -
DEIF supplies a complete range of current transformers (MAK range of CTs), power supplies (DCP range),
meters (DQ range) and transducers (TAS range) that are suitable for use with our range of generator
controls and protection relays - please see www.deif.com for full details.
Accuracy: Class 1.0, to IEC 688 Load sharing lines: -50+5V DC,
impedance 23.5k
Operating temp.: -25-70C
Analogue outputs: 0(4)-20mA
Galvanic separation: Between AC voltage, AC current Galvanically separated
and other I/Os: 3250V AC, Active output (internal supply)
50Hz, 1 min. Load max. 500
Panel cutout:
H x W = 87 x 208
Display size:
H x W = 129 x 248
207
248
129
86
1154500136
148
158
Order specifications