You are on page 1of 1

NOTES:

1. FOR GENERAL NOTES, SYMBOLS AND DETAILS SEE DRAWING


A10-K-2207 A10-A-PID-VA-449162-001 THRU A10-A-PID-VA-449165-003.
2. LPN PURGE CONNECTION TO BE AS CLOSE TO HRSG AS PRACTICAL.
STATIC MIXER 3. LPN PURGE CONNECTION TO BE AS CLOSE TO PV BYPASS BRANCH AS
PRACTICAL.
SIZE (DIA x T-T): x 4. MIN DISTANCE BETWEEN TWO BOLCK VALVE IS 1000MM
DP: 14 barg /FV

PB02-FGS-002 Fuel gas system for HRSG(A10-U-2201) DT: 125 C


OP: 4.5 barg
OT: 45 C
MOC: CS
00A
00A

TRIM:
INSULATION: HC

A10
H HOLDS: 00A
TI
2591
151. ALL CONTROL VALVE SIZE HOLD, WAITING VENDOR INFORMATION.

FF
A10

TT
A10

PI H 00A
2591 2591 A10-2"-LPF-22023-1CC2H2
7110 A10-718590-206
NI (34 C) 0 mm
RTD VENT TO LP FLARE
A10 A10 FF
TE PT 00A
2591 2591
NOTE 2 00A

3/4"
00A 00A
I A10-3"-ROG-22002-1CC1P
7107 A10-718589-206 LEGEND
ET (94 C) 40 mm
MIX GAS TO FUEL GAS PIPING MATERIAL INSTRUMENT DEFINITION & SYMBOLS SAES-J-004
SPECIFICATION SAES-L-105
00A KNOCK-OUT DRUM AC/AFO -AIR TO CLOSE/ VE -VIBRATION ELEMENT
A10-D-2235 AIR FAILURE OPEN VS -VIBRATION SWITCH
AC/AFS -AIR TO CLOSE/AIR VT -VIBRATION TRANSMITTER
PROCESS LINE
FAILURE STEADY XL -PILOT LIGHT
INSTRUMENT AO/AFC -AIR TO OPEN/ (NOT FOR MOTOR)
AIR LINE AIR FAILURE CLOSE XS -LIMIT SWITCH
AO/AFS -AIR TO OPEN/AIR ZV -SAFETY SHUTDOWN VALVE
INSTRUMENT
FAILURE STEADY
ELECTRICAL LINE DATA LOGGER POINT
AOV -AIR OPERATED VALVE
F-FLOW P-PRESS.

INPUTS
AT -ANALYZER TRANSMITTER
UC
A10
H L-LEVEL T-TEMP.
DT -DENSITY TRANSMITTER

THIS DRAWING AND THE INFORMATION CONTAINED HEREIN ARE THE SOLE PROPERTY OF SAUDI ARAMCO. NO REPRODUCTION IN FULL, OR IN PART, SHALL BE OBTAINED FROM THIS DRAWING WITHOUT THE WRITTEN CONSENT OF SAUDI ARAMCO.
X-MISC. A-ALARM
REDUCER ESD -EMER. SHUTDOWN SYSTEM
2591 LOCAL PANEL
L FC - FLOW CONTROLLER
MOUNTED INSTR.
SPECTACLE FV -FLOW CONTROL VALVE
PLATE-OPEN FCV -FLOW CONTROL VALVE
BOARD MOUNTED
(SELF-ACTUATED) INSTRUMENT
SPECTACLE FE -FLOW ELEMENT
PLATE-CLOSED FG -FLOW SIGHT GLASS
R/G
STATUS LIGHTS
GATE VALVE FHV -FLOW MANUAL CONT. VALVE XL R=RED, G=GREEN
FHTD -FLOW MANUAL TRANSDUCER PILOT LIGHT (DO NOT
GLOBE VALVE FIC -FLOW INDICATOR CONTROLLER USE FOR MOTOR STATUS)
CHECK VALVE FM -FLOW METER
RO -RESTRICTION ORIFICE MOTOR STATUS
PILOT LIGHT
PLUG VALVE FQI -FLOW TOTALIZER INDICATOR
FR -FLOW RECORDER
BALL VALVE ML LOCAL MOUNTED
FT -FLOW TRANSMITTER INSTRUMENT
DOUBLE DISC FY -FLOW RELAY
GATE VALVE HIC -HAND INDICATOR CONTROLLER
MOUNTED BEHIND
ANGLE VALVE HS -HAND SWITCH LOCAL PANEL
LA -LEVEL ALARM
00A -LEVEL CONTROL VALVE
LV
PRESS.RELIEF VALVE RACK MOUNTED
LCV -LEVEL CONTROL VALVE (OR BACK OF PANEL)
A10-2"-LPF-22025-1CC2H2 (SELF-ACTUATED)
7111 A10-718590-206
NI (34 C) 0 mm LG -LEVEL GAUGE GLASS ELECTRICAL
-LEVEL INDICATOR CONTROLLER SUPPLY REQUIRED
TO LP FLARE VACUUMRELIEF VALVE LIC
LI -LEVEL INDICATOR
1CC2H2
LR -LEVEL RECORDER INSTRUMENT
1CC1P -LEVEL SWITCH AIR SUPPLY REQUIRED
M MOTOR OPERATED LS
A10 A10 FF LT -LEVEL TRANSMITTER
VALVE H
00A PC PT LTD -LEVEL TRANSDUCER HIGH LOW
ML -MOTOR STATUS LIGHT L
FF 2590 2590 -MOTOR OPERATED VALVE
NOTE 4 P MOV
A10
PISTON OPERATED NA -ANNUNCIATOR TWO PEN RECORDER
PV VALVE PB -PUSHBUTTON
00A
00A 2590 PC -PRESSURE CONTROLLER FF
00A

3/4"
CONTROL VALVE PV -PRESS. CONTROL VALVE FOUNDATION
PCV -PRESS. CONTROL VALVE FIELDBUS INSTRUMENT
A10-3"-ROG-22001-1CC1P NOTE 3 (SELF ACTUATED)
7460 A10-718768-206
NI (50 C) 0 mm I
A10-K-2207 P
BALL TYPE PDC -PRESS. DIFF. CONTROLLER DISTRIBUTED CONTROL/SHARED
A10-K-2207 CONTROL VALVE PDI -PRESS. DIFF. INDICATOR DISPLAY SYMBOLS
OFF GAS FROM BATTERY 3/4" D AO/AFC 3/4" D WITH POSITIONER PDIC -PRESSURE DIFFERENTIAL
(DCS) DISTRIBUTED CONTROL
LIMIT 00A 3/4" D 3/4" D S INDICATOR CONTROLLER SYSTEM, OPERATOR ACCESSIBLE
SOLENOID VALVE PDIS -PRESSURE DIFFERENTIAL IN CONTROL ROOM
00A
3" x 2" INDICATOR SWITCH (DCS) DISTRIBUTED CONTROL
PDT -PRESS. DIFF. TRANSMITTER
VALVE NORMALLY SYSTEM, OPERATOR INACCESSIBLE
00A A10
CLOSED
PDTD -PRESS. DIFF. TRANSDUCER IN CONTROL ROOM
PI PG -PRESSURE GAGE
PI (DCS) DISTRIBUTED CONTROL
-PRESSURE INDICATOR
2598 PIC -PRESS. INDICATOR CONTROLLER
SYSTEM, OPERATOR INACCESSIBLE
IN FIELD
PR -PRESSURE RECORDER
00A PS -PRESSURE SWITCH
3/4" PT -PRESSURE TRANSMITTER DISTRIBUTED CONTROL
A10-2"-LPN-22016-1CC1P INTERCONNECTING LOGIC
PX -PRESSURE POINT
A10-718594-202 7112
NI (45 C) 0 mm PY -PRESS. COMPUTATION MOD. CONTROLLER WITH BINARY
00A LPN PURGE PZV -PRESSURE RELIEF VALVE OR SEQUENTIAL FUNCTIONS

A10-2"-LPN-22017-1CC1P
3/4" D RTD -RESIST. TEMP. DETECTOR
(PLC) PROGRAMMABLE LOGIC
SI -SPEED INDICATOR
CONTROLLER, NORMALLY
SS -SPEED SWITCH INACCESSIBLE OR BEHIND THE
TC -TEMP. CONTROLLER PANEL DEVICE OR FUNCTIONS
TV -TEMP. CONTROL VALVE (PLC) PROGRAMMABLE LOGIC
TCV -TEMP. CONTROL VALVE CONTROLLER FUNCTION,
(SELF-ACTUATED) CAN BE NORMALLY
TE -TEMP. ELEMENT DISPLAYED ON CRT
TSO -TIGHT SHUT OFF TG -THERMOMETER LOCAL DCS OR AUXILIARY
S.C. - SAMPLE CONN. THS -TEMP. HAND SWITCH DCS LOCATION NORMALLY
00A TI -TEMP. INDICATOR ACCESSIBLE TO OPERATOR
S -DRAIN TO
TR -TEMP. RECORDER
PRESSURE SEWER
A10-2"-LPF-22026-1CC2H2 TS -TEMP. SWITCH
(PLC) PROGRAMMABLE LOGIC
7113 A10-718590-206 CONTROLLER I/O POINT
OWS -OILY WATER SEWER TT -TEMP. TRANSMITTER NORMALLY INACCESSIBLE
NI (34 C) 0 mm D -DRAIN TTD -TEMP. TRANSDUCER BY OPERATOR
TO LP FLARE V -VENT TW -THERMOWELL
00A
REFERENCE DRAWINGS
00A
LETTER IDENTIFICATION OF LINES AE-036204

A10 A10
FF PIPING SYMBOLS AB-036227
PC PT EQUIPMENT SYMBOLS AB-036305
2589 2589 INSTRUMENT SYMBOLS AC-036950
PIPING LAYOUT INDEX
1CC2H2
00A 1CC2P PLOT PLAN

SP A10
FF PROCESS FLOW DIAGRAM
PV NOTE 4 HYDROSTATIC TEST DIAGRAM
2237
3/4"

00A 2589 00A DRAWING CONTROL FOR J.O.


I INSTRUMENT INSTALLATION SCHEDULES
A10-3"-FGH-22001-1CC2P NOTE 3 I
7108 A10-718589-206
ET (94 C) 40 mm
3/4" D 3/4" D
Jazan - \A10\A10\VA-718589-204.pid - 9/29/2015 9:59:52 AM - [JE07]

HP FUEL GAS FROM AO/AFC


00A
BATTERY LIMIT 3/4" D 3/4" D
00A 00A

REVISION VALIDATION
THIS REVISION NO. 00A IS COVERED, FOR ALL APPROVAL AND CERTIFICATION
REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:
10-01525-0004-XXX

DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER


(DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)
ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE
HL.ZENG B.ANDERS
09/25/15 09/25/15

REV.NO. DATE REVISION DESCRIPTION


00A 09/25/15 ISSUED FOR CONSTRUCTION

JOB ORDER/EWO NO.


THIS REVISION IS NOT TO BE USED FOR
10-01525-0004 CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY


DRAWING TYPE
PIPING & INSTRUMENTATION DIAGRAM PID
BLOCK #2 OFF GAS & FUEL GAS MIX-TURE
POWER GENERATION UNIT
JAZAN SAUDI ARABIA
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

A10 A VA-718589 204 00A


Saudi Aramco 5994 ENG. (09/03)

RESTRICTED SMART CADD-05