RVK & RVS


the new controller
generation ABB Jumet
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

INTRODUCCION
El presente tema describe las instrucciones de:
INSTALACION, OPERACION Y CONTROL de
los reguladores automticos de energa reactiva
ABB JUMET RSS RVK.
Adems se tratar lo siguiente :
- Puesta en marcha rpida.
- Carcateristicas avanzadas.
- Pruebas y localizacin de averas.
- Especificaciones tcnicas.
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

1
17/04/2013

1 2 3 4 5 6

AUTO V RMS COS

MAN A RMS OUTPUT

PRINT KVA DELAY

SET KVAR SEQUENCE

PLOT THD V TEMP RS 232


LOG THD A SETUP LOCK

MODE DISPLAY NEXT

RVS 6 POWER FACTOR CONTROLLER

Standard models
Types :
RVK or RVS
Number of outputs :
6 or 12
Current inputs :
5 A or 1 A
Voltage :
400 V or 230 V or 120 V

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

2
17/04/2013

Controller back-side

Identification of model (label on left side):


- ABB article number 20.050.82220
- Controller serial number 13492 40622
- Type RVK 12
- Current input 5A
- Voltage range 220-240 V
- Network frequency 50-60 Hz

Voltage range

3
17/04/2013

12 outputs

LOCK Switch
SET Switch

RVS

Alarm Relay

RVS
Fan Relay

4
17/04/2013

RVS

Temperature Input
Plot Output
RS232 Communication
night cos contact

1 2 3 4 5 6 7 8 9 10 11 12

AUTO V RMS COS

MAN A RMS OUTPUT

PRINT KVA DELAY

SET KVAR SEQUENCE

PLOT THD V TEMP RS 232

LOG THD A SETUP LOCK

MODE DISPLAY NEXT

RVS 12 POWER FACTOR CONTROLLER

5
17/04/2013

1 2 3 4 5 6 RVS 6

AUTO V RMS COS

MAN A RMS OUTPUT

PRINT KVA DELAY

SET KVAR SEQUENCE

PLOT THD V TEMP RS 232


LOG THD A SETUP LOCK

MODE DISPLAY NEXT

RVS 6 POWER FACTOR CONTROLLER

1 2 3 4 5 6 7 8 9 10 11 12 RVK 12

AUTO V RMS COS

MAN A RMS OUTPUT

PRINT KVA DELAY

SET KVAR SEQUENCE

SETUP LOCK

MODE DISPLAY NEXT

RVK 12 POWER FACTOR CONTROLLER

6
17/04/2013

1 2 3 4 5 6 7 8 9 10 11 12

AUTO V RMS COS

MAN A RMS OUTPUT RVS


PRINT KVA DELAY

only for RVS


SET KVAR SEQUENCE

PLOT THD V TEMP RS 232


LOG THD A SETUP LOCK
only for RVS

MODE DISPLAY NEXT

RVS 12 POWER FACTOR CONTROLLER

Mode choice while pushing on


1 2 3 4 5 6 7 8 9 10 11 12
MODE switch :
- AUTO: Automatic regulation
- MAN: Manual mode
- PRINT: Printer setting mode
AUTO V RMS
- SET:
COS
Parameters setting mode
MAN A RMS
- PLOT:
OUTPUT
Plot setting mode
PRINT KVA
- LOG:
DELAY
Data storage mode
SET KVAR SEQUENCE

PLOT THD V TEMP RS 232


LOG THD A SETUP LOCK

MODE MODE Menus


DISPLAY NEXT

RVS 12 POWER FACTOR CONTROLLER

7
17/04/2013

Choice of parameter to PLUS and MINUS switches to


display with DISPLAY 1 2 3 4 5(sub-)parameters
modify 6 7 8 9 10 11 12
switch:
NEXT switch to walk through
- Voltage all sub-parameters
- Current
- Apparent power AUTO V RMS COS
- Reactive power MAN A RMS OUTPUT
- THD(U) PRINT KVA DELAY
- THD(I) SET KVAR SEQUENCE
- Power factor PLOT THD V TEMP RS 232
- Temperature LOG THD A SETUP LOCK

DISPLAY Menu
MODE DISPLAY NEXT

RVS 12 POWER FACTOR CONTROLLER

1 2 3 4 5 6 7 8 9 10 11 12

LEDs indication :
- Switched on steps
COS
- switching demand AUTO
+/- V RMS

MAN A RMS OUTPUT


- Fan Relay status
PRINT KVA DELAY
- Alarm contact
SET KVAR SEQUENCE
(Alarm Relay status)
- RS232 Connection PLOT
status THD V TEMP RS 232
LOG THD A SETUP LOCK
- Locked front plate status

MODE DISPLAY NEXT

RVS 12 POWER FACTOR CONTROLLER

8
17/04/2013

Measurements
1 2 3 4 5 6 7 8 9 and
10 11 12 Parameters

NEXT
AUTO V RMS COS Voltage
MAN A RMS OUTPUT
- RMS Voltage measurement
PRINT KVA DELAY

SET KVAR
- Voltage
SEQUENCE
transformer ratio
PLOT THD V
- Maximum
TEMP
voltage
RS 232
threshold
LOG THD A
(start
SETUP
a LOG-storage/disconnection)
LOCK
- Minimum voltage threshold
(quick disconnection)
MODE DISPLAY NEXT
- Nominal voltage

RVS 12 POWER FACTOR CONTROLLER


DISPLAY

Measurements
1 2 3 4 5 6 7 8 9 and
10 11 12 Parameters
NEXT

AUTO V RMS COS Current


MAN A RMS OUTPUT
- RMS Current measurement
PRINT KVA DELAY

SET KVAR
- CT ratio
SEQUENCE

PLOT THD V
- Maximum
TEMP
current
RS 232
LOG-threshold
LOG THD A
- Reactive
SETUP
current
LOCK
measurement
- C/k value introduced / calculated
MODE DISPLAY NEXT

RVS 12 POWER FACTOR CONTROLLER


DISPLAY

9
17/04/2013

Measurements
1 2 3 4 5 6 7 8 9 and
10 11 12 Parameters

AUTO V RMS COS

Apparent power

NEXT
MAN A RMS OUTPUT

PRINT KVA DELAY

SET
- kVA measurement
KVAR SEQUENCE

PLOT
- LOG-threshold Smax
THD V TEMP RS 232
LOG THD A SETUP LOCK

MODE DISPLAY NEXT

RVS 12 POWER FACTOR CONTROLLER


DISPLAY

Measurements
1 2 3 4 5 6 7 8 9 and
10 11 12 Parameters

Reactive power
NEXT

AUTO V RMS COS

MAN A RMS OUTPUT


- kvar measurement
PRINT KVA DELAY

SET KVAR
- LOG-threshold
SEQUENCE
Qmax
PLOT THD V
- kvar
TEMP
for one RSstep
232
(related to C/k)
LOG THD A
- Missing
SETUP
kvar measurement
LOCK
*)
- Missing steps measurement *)
- Number of switched steps
MODE DISPLAY NEXT
*) related to the minimum-cos
RVS 12 POWER FACTOR CONTROLLER
DISPLAY

10
17/04/2013

Measurements
1 2 3 4 5 6 7 8 9 and
10 11 12 Parameters

AUTO V RMS COS

MAN A RMS OUTPUT

PRINT KVA DELAY

NEXT
SET KVAR
Voltage total harmonic
SEQUENCE

PLOT THD V TEMP


distortion
RS 232
LOG THD A SETUP THD(U)
LOCK

- THD (U) measurement


MODE DISPLAY NEXT
- LOG-threshold THD(U)max

RVS 12 POWER FACTOR CONTROLLER


DISPLAY

Measurements
1 2 3 4 5 6 7 8 9 and
10 11 12 Parameters

AUTO V RMS COS

MAN A RMS OUTPUT

PRINT KVA DELAY


Voltage total harmonic
NEXT

SET KVAR SEQUENCE

PLOT THD V TEMP


distortion
RS 232
LOG THD A SETUP THD(I)
LOCK

- THD (I) measurement


MODE DISPLAY NEXT
- LOG-threshold THD(I)max

RVS 12 POWER FACTOR CONTROLLER


DISPLAY

11
17/04/2013

Measurements
1 2 3and
4 5 6 Parameters
7 8 9 10 11 12

Power factor ( cos

NEXT
AUTO V RMS COS

MAN A RMS OUTPUT


- Power factor measurement
PRINT KVA DELAY

- Controller referenceSETcos KVAR SEQUENCE

- Controller night reference


PLOT V
cosTHD TEMP RS 232

- Minimum-cos (Tarification)
LOG THD A SETUP LOCK

Alarm activation, LOG-storage


MODE DISPLAY NEXT

RVS 12 POWER FACTOR CONTROLLER


DISPLAY

Measurements
1 2 3and
4 5 6 Parameters
7 8 9 10 11 12

Output
NEXT

AUTO V RMS COS

MAN A RMS OUTPUT


- Number of active outputs
PRINT KVA DELAY
- Individual output deactivation
SET KVAR SEQUENCE

PLOT THD V TEMP RS 232


LOG THD A SETUP LOCK

MODE DISPLAY NEXT

RVS 12 POWER FACTOR CONTROLLER


DISPLAY

12
17/04/2013

Measurements
1 2 3and
4 5 6 Parameters
7 8 9 10 11 12

Delay

NEXT
AUTO V RMS COS

MAN A RMS OUTPUT


- Switch on delay PRINT KVA DELAY
- Switch off delay SET KVAR SEQUENCE
- Starting reset delayPLOT THD V TEMP RS 232
- Alarm delay 1 Second
LOG THD A SETUP LOCK

- Alarm reset delay to


- Printing period MODE 120 Minutes DISPLAY NEXT

RVS 12 POWER FACTOR CONTROLLER


DISPLAY

Measurements
1 2 3and
4 5 6 Parameters
7 8 9 10 11 12

Sequence
NEXT

AUTO V RMS COS

MAN A RMS OUTPUT


- Type of sequence PRINT KVA DELAY
- Linear / Circular SET KVAR SEQUENCE
- Progressive / DirectPLOT
switchingTHD V TEMP RS 232
- Normal / Integral measurement
LOG THD A SETUP LOCK

- 1-phase / 3-phase Connection


- Phase correctionMODE DISPLAY NEXT

RVS 12 POWER FACTOR CONTROLLER


DISPLAY

13
17/04/2013

Measurements
1 2 3and
4 5 6 Parameters
7 8 9 10 11 12

1:1:1:1:1: ... :1
1:2:2:2:2: ... :2
Sequence

NEXT
AUTO
1:2:4:4:4:
V RMS
...
COS :4

MAN
Circular or 1:2:4:8:8:
A RMS OUTPUT
... :8
- Type of sequence Linear
PRINT KVA DELAY
- Linear / Circular SET 1:1:2:2:2:
KVAR ... :2
SEQUENCE
- Progressive / DirectPLOT
switchingTHD V
1:1:2:4:4: ...
- Normal / Integral measurement
LOG
:4
TEMP RS 232

THD A SETUP LOCK

- 1-phase / 3-phase Connection1:1:2:4:8: ... :8


- Phase correctionMODE DISPLAY NEXT

RVS 12 POWER FACTOR CONTROLLER


DISPLAY

Measurements
1 2 3and
4 5 6 Parameters
7 8 9 10 11 12

Temperature
NEXT

AUTO V RMS COS

MAN A RMS OUTPUT


- Temperature measurement
PRINT KVA DELAY
- Units C / F SET KVAR SEQUENCE
- Calibration : V / K PLOT THD V TEMP RS 232
- Calibration : Offset LOG THD A SETUP LOCK

- Reference T for fan activation


- Maximum T (disconnection
MODE / DISPLAY NEXT
LOG-Threshold Tmax)
RVS 12 POWER FACTOR CONTROLLER
DISPLAY

14
17/04/2013

Measurements
1 2 3and
4 5 6 Parameters
7 8 9 10 11 12

SETUP

NEXT
AUTO V RMS COS

MAN A RMS OUTPUT

(easy start procedure)


PRINT KVA DELAY

SET KVAR SEQUENCE


- Voltage transformer ratio
PLOT THD V TEMP RS 232
- Current transformerLOG
ratio THD A SETUP LOCK
- Reference cos
- Automatic Ct correction (+ & -)
MODE
- Automatic C/k procedure (+ & -)DISPLAY NEXT

RVS 12 POWER FACTOR CONTROLLER


DISPLAY

AUTO

Printer output MAN

PRINT

No required connection SET

PLOT

Infrared communication LOG

(HP-Printer)
MODE
Free selection of print function
Choice of individual measurements
and printing period
Number of steps when changed
Report of controller settings
Report of Log-datas stored
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

15
17/04/2013

Plot output
Control of a measured value
Choice of 1 Parameter
Quick measurement device
AUTO

MAN

PRINT
Oscilloscope SET

XT-recorder PLOT

LOG

Measurement device
(Ex. Voltmeter) MODE

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

LOG-data storage
Threshold programming (SET)
AUTO

MAN

Free Parameter choice PRINT

SET

Free Threshold choice PLOT

LOG

Stored data
Maximum measured value MODE

Cumulated storage period


Stored data display (LOG)
Retrieve all stored data

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

16
17/04/2013

Temperature measurement
Activation of fan relay
Programmable threshold
Disconnection by over-temperature
Log-storage
Stop regulation until temperature
becomes normal
SEQUENCE

TEMP RS 232

SETUP LOCK

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

Protection capability
Disconnection with under-voltage
avoid brief power outage destruction
Disconnection with over-voltage
avoid over-voltage damages
Disconnection by over-temperature
avoid hot-points damages

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

17
17/04/2013

Alarm Function
optimal operation
Free choice of a particular cos
Minimum-cos related to tarification
(Alarm activation when the minimum
cos can not be reached.)
possibility of programming delays
for alarm activation DELAY

SEQUENCE
for alarm reset TEMP RS 232

SETUP LOCK

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

1:1:2: ...- Sequence


optimal operation
right number of steps
complete modules
alternate switching of both smaller
steps DELAY

Mini - Circular SEQUENCE

switching TEMP

SETUP
RS 232

LOCK

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

18
17/04/2013

Direct switching
few intermediate switchings
goes right to the target
bigger steps are switched first
rapid regulation
switching-on with 12s delays
switching-off in one shot
DELAY

SEQUENCE

TEMP RS 232

SETUP LOCK

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

Integral control
Reach the target cos
Compensation of average demand
Regulation even with demand
cancellation
Sharp variations doesnt alterate
precise regulation
Frequent variations DELAY

doesnt influence SEQUENCE

TEMP RS 232
great amount of steps SETUP LOCK

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

19
17/04/2013

Phase correction
Avoid connection problems
Transformer can be installed in a
preferred phase DELAY

SEQUENCE
Wrong connections TEMP RS 232

Mixed measurements SETUP LOCK

No special controller needed


No special phase configuration
needed (for example for voltage)
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

RS232 Connection DELAY

SEQUENCE

RVSlink Software TEMP RS 232

SETUP LOCK

The RS232 connection and the


RVS-Link ABB-Software allows the
communication between the Controller
and a Computer.
This gives then many additional
possibilities related to the use of the
Controller as a measuring device .

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

20
17/04/2013

RS232 Connection DELAY

SEQUENCE

RVSlink Software TEMP RS 232

SETUP LOCK

Display, modify and store all


programming parameters
Display and store all measurements
Display the LOG-data
Controller setup by Computer
Example

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

RS232-Connection DELAY

SEQUENCE

Software RVS-Link TEMP RS 232

SETUP LOCK

Quick programming utilities


Long time measurements with
graphical tools
Instantaneous measurements
(Oscillogramme) with harmonic
analysis
Example
...
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

21
17/04/2013

RVC : the user-friendly PF Controller

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

User friendly interface

LCD
Display

Key pad

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

22
17/04/2013

LCD icons

Alarm Linked to
contact one output
relay

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

LCD icons

Overtemperature Linked
to one
output
relay

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

23
17/04/2013

LCD icons

Inductive /
Capacitive
PF

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

LCD icons

Active outputs Indicates a


demand for
switching on/off
a capacitor step

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

24
17/04/2013

Key pad buttons

Parameters
and values
Automatic / adjustment
Manual mode

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

Easy commissioning
Autoadaptation to
phase rotation
CT terminals
Automatic recognition
number of outputs
switching sequence

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

25
17/04/2013

Auto set up

Phase C/k
shift

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

Auto set up

Switching
delay time

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

26
17/04/2013

Auto set up

Number
Switching of outputs
sequence

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

Easy programming

MODE
- +

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

27
17/04/2013

Highly efficient switching strategy


Integral, direct and circular
Reduce n of switching
Avoid intermediary switching
longer life of capacitors & contactors
Cos phi control with rapidly varying loads.
Reliable
Insensitive to the presence of harmonics
Suitable for hot environment
Max. ambient temperature rating of 70C
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

Range Programmable
RVC-3 3 outputs
RVC-6 6 outputs
RVC-8 8 outputs
RVC-10 10 outputs
RVC-12 12 outputs

Range
230V (220V to 240V)
voltage 400V (380V to 440V)
50Hz / 60Hz (automatic adjustment)
REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

28
17/04/2013

RVC : the user-friendly PF Controller


Unique design

easy commissioning
easy programming
complete auto set-up

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

THEN YOU ABB

REGULADORES AUTOMATICOS DE ENERGIA REACTIVA ING. HUBER MURILLO MANRIQUE

29