ELECTRICAL GENERAL NOTES ELECTRICAL ABBREVIATIONS CABLE REFERENCING LINE 4


QIBLA

1. DO NOT SCALE FROM LAYOUT DRAWINGS. WORK ACCORDING TO ARCHITECTURAL A kWH KILO WATT HOUR TAG OPTIONS
DRAWINGS OR ELECTRICAL DETAILS UNLESS OTHERWISE INDICATED. A/AMP AMPERE
SINGLE CABLE
a.c ABOVE COUNTER L REFERENCE ON SINGLE X EQUIPMENT TYPE SMDB, MCC, MCP, LDP, PDP
2. ALL DIMENSIONS ARE IN MILLIMETRES & LEVELS IN METRES UNLESS NOTED OTHERWISE.
ALL DIMENSIONS TO BE VERIFIED ON SITE & APPROVED BY THE ENGINEER. AC ALTERNATING CURRENT LAN LOCAL AREA NETWORK LINE DIAGRAMS (SLD) CABLE No. ON SCHEMATIC DIAGRAM TYPE OF SUPPLY N (NORMAL SUPPLY), E (ESSENTIAL), U (UPS), C (CBS)
ACB AIR CIRCUIT BREAKER LCM LIGHTING CONTROL MODULE X = A1, A2, A3, etc.
3. ALL THE DRAWING SHOULD BE READ IN CONJUNCTION WITH OTHER RELEVANT ACC ACCESS CONTROL LCP LIGHTING CONTROL PANEL
LEVEL BL (BASEMENT LEVEL) ML (MEZZANINE LEVEL)
ARCHITECTURAL, PROJECT WIDE ARCHITECTURAL STANDARD DETAILS, STRUCTURAL, AD AUTO DOOR LDP LIGHTING DISTRIBUTION PANEL GL (GROUND LEVEL) UL (UNDER PLATFORM LEVEL)
Millimetres

MECHANICAL, ELECTRICAL & CIVIL DRAWINGS & ALL RELEVANT SECTIONS OF THE ER ADDR. ADDRESSABLE L/L LOW LEVEL
SPECIFICATION AND SUPPLEMENTARY GUIDE SPECIFICATION PRODUCED BY DJV. AF AMPERE FRAME LMS LIGHTING MANAGEMENT SYSTEM CL (CONCOURSE LEVEL) LINE 1
4. WALL / SLAB CONSTRUCTION, ETC. SHOWN IN PROJECT WIDE - ELECTRICAL DETAILS AFFL ABOVE FINISHED FLOOR LEVEL LPF LIFT PRESSURIZATION FAN MULTIPLE CABLES AT A1, A2, A3, A4 PL (PLATFORM LEVEL)
AFL AUTOFLUSH LSOH LOW SMOKE ZERO HALOGEN SAME LOCATION ON LINE 6

100
DRAWINGS ARE INDICATIVE ONLY.REFER TO RELEVANT ARCHITECTURAL DRAWINGS AND CAN BE PREFIXED IF
DETAILS FOR REQUIRED INFORMATION. AHU AIR HANDLING UNIT LTG LIGHTING REQUIRED
UNIQUE NUMBER 1, 2, 3, ..... LINE 2
AM ADDRESSABLE MODULE LV LOW VOLTAGE PLAN OR ON CABLE TYPE OF SUPPLY (TO SUIT PARTICULAR BUILDING/DESIGN)
5. ALL EQUIPMENT LAYOUTS ARE PROVISIONAL. FINAL LAYOUTS SHALL BE DETERMINED BY
THE CONTRACTOR FROM THE CONSTRUCTION/SHOP DRAWINGS & AFTER COORDINATION
AR AUTORINSE L&P LIGHTING & POWER CONTAINMENT
AS AUTOTRANSFORMER STARTER NOTE: IN LARGE COMPLEX BUILDINGS WHERE GREATER DEFINITION IS REQUIRED, 'XX' CAN LINE 4
WITH OTHER TRADES. AT AMPERE TRIP M BE ENHANCED TO PROVIDE MORE DETAILS.
6. CONTRACTOR SHALL PROVIDE THE MATCHING PLUG IN FOR ALL SPECIAL OUTLETS. ATR AUXILIARY TRANSFORMER M MOTOR LINE 5
LINE 3
ATS AUTOMATIC TRANSFER SWITCH
CABLE CONTAINMENT LABELLING
10

7. LAMPS SHALL BE FURNISHED & INSTALLED IN ALL LIGHTING FIXTURES. MA MILLIAMPERE EXAMPLE: SMDB-4E2-CL-1N EXAMPLE: MCC-4E2-CL-1N
AV AUDIO VISUAL MCB MINIATURE CIRCUIT BREAKER
8. CONDUIT, LIGHTING PANELS, LIGHTING FIXTURES, RECEPTACLES & OTHER ITEMS SHALL MCC MOTOR CONTROL CENTRE LINE 2
EXAMPLE: SMDB-4E2-CL-1E EXAMPLE: MCP-4E2-CL-1E
0

BE LOCATED AS SHOWN ON THE DRAWINGS. B MCCB MOLDED CASE CIRCUIT BREAKER FIELD 2 LINE 6
BB BUS BAR MCP MOTOR CONTROL PANEL (TYPE OF SERVICE)
9. FOR EXACT LOCATION OF AIR-CONDITIONING & OTHER MECHANICAL EQUIPMENT, SEE EXAMPLE: SMDB-4E2-CL-1C
MECHANICAL & PLUMBING DRAWINGS. BD BUS DUCT MCPr MOTOR CIRCUIT PROTECTOR
BL BASEMENT LEVEL MCS MOLDED CASE SWITCH CABLE CONTAINMENT CCB No.- - -
10. FOR EXACT LOCATION OF RECESSED LIGHTING FIXTURES, SEE ARCHITECTURAL BLDG. BUILDING MD MAXIMUM DEMAND BANK No. (WHERE CT 600 LV LINE 5
REFLECTED CEILING PLANS. BMS BUILDING MANAGEMENT SYSTEM MDB MAIN DISTRIBUTION BOARD REQUIRED) FOR CROSS TYPE OF SERVICE /
BOH BACK OF HOUSE MFACP MAIN FIRE ALARM CONTROL REFERENCING TO CABLE A1, A2, A3 EQUIPMENT (SEE
11. EXACT METHOD OF JOINING CABLE TRAYS, CABLE LADDER & CABLE TRUNKING SHALL BE
BOT BOTTOM OF TRAY PANEL CONTAINMENT SIZING TABLE BELOW)
IN ACCORDANCE WITH THE RESPECTIVE MANUFACTURER'S RECOMMENDATION USING

100
MOD MOTORIZED OPERATING DAMPER SHEETS LINE 3
PROPRIETARY COMPONENTS. BUILDING REFERENCE
12. THE DIMENSION OF ELECTRICAL PANELS SHALL BE AS PER APPROVED
C MPEB MAIN POTENTIAL EQUALIZATION
FIELD 1 (REFER TABLE 1)
CAV CONSTANT AIR VOLUME BUS BAR
FABRICATOR/SUPPLIER SHOP DRAWINGS. (TYPE / SIZE) PLAN OR SECTION DETAIL
CBS CENTRAL BATTERY SYSTEM MSD MOTORIZED SMOKE DAMPER LEVEL (SEE TABLE
LINE 1
13. MAIN POWER SUPPLIES TO LOW CURRENT EQUIPMENT SHOULD BE OVER VOLTAGE & CCT CIRCUIT MSFD MOTORISED SMOKE & FIRE BELOW)
CABLE REFERENCE Nos.
TRANSIENT PROTECTED. CCTV
CD
CLOSED CIRCUIT TELEVISION
CABLE DUCT MV
DAMPER
MEDIUM VOLTAGE
ON THIS CONTAINMENT UNIQUE NUMBER KEY PLAN
14. THE LAYOUT DRAWINGS DO NOT SHOW ALL THE SYSTEMS, ITEMS OR ACCESSORIES (SAME AS CABLE
CHU AIR COOLED WATER CHILLER REFERENCING) TYPE OF SUPPLY
COVERED UNDER THE SCOPE OF ELECTRICAL WORKS TO BE EXECUTED.
CL CONCOURSE LEVEL N FOR DISTRIBUTION PANEL NOTES:
15. ALL SWITCHES, SOCKET OUTLETS, ETC. SHALL BE INSTALLED WITH THEIR REQUIRED N.T.S. NOT TO SCALE
CLD CABLE LADDER BOARDS VDP-WW-XX-YZ 1. FOR PROJECT WIDE LEGENDS & SYMBOLS REFER TO DRAWING
PLATES. CN CONDUIT N/C NORMALLY CLOSED FIELD TAG OPTIONS NO. M3-DJV-EDR-EEL00-PWD-GEN-1370101.
16. GROUND FAULT PROTECTION(GFCI) SHALL BE PROVIDED FOR OUTLETS WITHIN 0-180CM CP CONTROL PANEL N/O NORMALLY OPEN
N NEON FIELD 1 TYPE/SIZE CABLE CONTAINMENT TYPE TAG OPTIONS
OF A SINK EDGE AND OTHER WET LOCATIONS. CPC CIRCUIT PROTECTIVE
CONDUCTOR NS NORMAL SUPPLY CT CABLE TRAY
17. ALL MANUAL FIRE ALARM STATIONS SHALL BE MOUNTED AT 1100mm ABOVE F.F.L. TYPE OF SERVICE L (LIGHTING), P (POWER)
CS CONTROL SUBSTATION FOR NA NON AUTO TR CABLE TRUNKING
18. WHEREVER ELECTRICAL SERVICES ARE CROSSING A FIRE ZONE/COMPARTMENT, THE EMERGENCY LIGHT FIXTURE CLD CABLE LADDER TYPE OF SUPPLY N (NORMAL SUPPLY), E (ESSENTIAL), U (UPS), C (CBS)
CONTRACTOR SHALL PROVIDE ADEQUATE FIRE BARRIERS. CT CABLE TRAY P CN CONDUIT LEVEL BL (BASEMENT LEVEL) ML (MEZZANINE LEVEL)
Cu COPPER P NUMBER OF POLES
19. ALL LIGHTING DISTRIBUTION & POWER PANEL BOARDS ARE TO BE INSTALLED WITH TOP BD BUS DUCT GL (GROUND LEVEL) UL (UNDER PLATFORM LEVEL)
ENDS AT 1800mm F.F.L. UNLESS OTHERWISE INDICATED. PC PHOTOCELL
D PCS PULL CORD SWITCH CL (CONCOURSE LEVEL) RL (ROOF LEVEL) AB
20. FOR EXACT LOCATION OF MECHANICAL EQUIPMENT, REFER TO MECHANICAL DRAWINGS. DC DIRECT CURRENT PDP POWER DISTRIBUTION PANEL CABLE CONTAINMENT ANNOTATION FORMATS
21. THE CONTRACTOR SHALL COORDINATE ALL WORKS WITH OTHER TRADES & SERVICES & DF DIVERSITY FACTOR PEB POTENTIAL EQUALIZATION BUS CT 600 600mm WIDE CABLE TRAY PL (PLATFORM LEVEL)
INCORPORATE ALL THEIR EXACT & FINAL REQUIREMENTS. DOL DIRECT ON LINE STARTER BAR UNIQUE NUMBER 1, 2, 3, .....
CLD 600 600mm WIDE CABLE LADDER
DP DISTRIBUTION PANEL BOARD PFCR POWER FACTOR CORRECTION
22. SCHEMATIC DIAGRAMS REFLECT THE GENERAL CONCEPTS OF THE REQUIRED SYSTEM(S). DWP DOMESTIC WATER PUMP RELAY TR 100x100 INDICATES 1-no. TRUNKING 100x100 TYPE OF SUPPLY (TO SUIT PARTICULAR BUILDING/DESIGN)
SCHEMATIC DIAGRAM SHALL BE APPLICABLE FOR ALL TYPES OF STATIONS. CONTRACTOR PL PLATFORM LEVEL IN SIZE
IS TO VERIFY THE DESIGN ACCORDING TO FINAL STATION LAYOUT. NOTE: IN LARGE COMPLEX BUILDINGS WHERE GREATER DEFINITION IS REQUIRED, 'XX' CAN
E PLC PROGRAMMABLE LOGIC 2 x TR 100x100 INDICATES 2-nos. TRUNKING 100x100
CONTROLLER BE ENHANCED TO PROVIDE MORE DETAILS.
23. ALL EQUIPMENT RATINGS SHOWN ON DRAWINGS ARE PROVISIONAL. CONTRACTOR IS TO E&M ELECTRICAL & MECHANICAL IN SIZE
VERIFY THE FINAL RATING/CAPACITY OF EQUIPMENT ACCORDING TO THE APPROVED INTERLOCK PMU POWER MONITORING UNIT
PS POWER SUPPLY TR 100x100(2C) INDICATES 100x100 TRUNKING
MANUFACTURER. EB ELECTRONIC BALLAST EXAMPLE: LDP-4E2-CL-1N EXAMPLE: LDP-4E2-CL-1C
PSU POWER SUPPLY UNIT HAVING 2 COMPARTMENTS
ECC EARTH CONDUCTOR CABLE
24. ALL CABLE TRAYS THAT RUN HORIZONTALLY SHALL BE COORDINATED WITH ALL OTHER PV PHOTOVOLTAIC
SERVICES (e.g. L.C CABLE TRAYS, HVAC DUCTS, PIPES, ETC.) WHICH RUN AT SAME
EF EXHAUST OR EXTRACT FAN EXAMPLE: PDP-4E2-CL-1E
ELCB EARTH LEAKAGE CIRCUIT PFR POWER FAILURE RELAY NOTES: ALL CABLE CONTAINMENT SIZES INDICATED
LOCATION.
PROTECTION ARE IN MILLIMETRES (mm) UNLESS
25. SEGREGATED RACEWAYS SHALL BE PROVIDED FOR EMERGENCY (LIFE SAFETY) ELV EXTRA LOW VOLTAGE R OTHERWISE DESCRIBED. TYPE OF EQUIPMENT
FEEDERS/CIRCUITS. EM EMERGENCY RAD RADIAL CABLE TRAY PERFORATED MINIMUM 45mm (SEE TABLE BELOW)
EP EMERGENCY PUSHBUTTON RCD RESIDUAL CURRENT DEVICE DEEP.
26. ALL CABLE TRAYS & LADDERS ARE TO BE SIZED CONSIDERING 30% ADDITIONAL SPACE
EPO ELECTRIC POWER OFF REF REFERENCE BUILDING REFERENCE
FOR FUTURE INSTALLATIONS. CABLE LADDER SIDE CHANNEL MINIMUM
ESS ESSENTIAL SUPPLY RM ROOM (REFER TABLE 1)
27. AS AGREED WITH GDCD, ALL ELEVATORS ARE REQUIRED TO BE CLASSIFIED AS FIRE 127x32mm.
EWH ELECTRIC WATER HEATER RMU RING MAIN UNIT
FIGHTING ELEVATORS AND SHALL BE SUPPLIED BY EMERGENCY GENERATORS. LEVEL (SEE TABLE
EX EXPLOSION PROOF FIELD 2 TYPE OF SERVICE ABBREV. SUB-SYSTEMS
BELOW)
28. ALL FIRE SUPPRESSION SYSTEMS SHALL BE INTERFACED TO FIRE ALARM SYSTEM. SIG&COMMS COMMUNICATIONS (CO)
F S UNIQUE NUMBER
29. FAULT ISOLATOR MODULES SHALL BE USED EVERY 10 ADDRESSABLE DEVICES MAXIMUM SYSTEMS (SYS)
F.F.L. FINISHED FLOOR LEVEL SC SHORT CIRCUIT LEVEL
& BETWEEN FLOORS & ZONES. SCADA SUPERVISORY CONTROL & DATA ELV FIRE ALARM (FA)
F/A FROM ABOVE
30. VISIBLE APPLIANCES CD LEVEL SHALL BE SET AS PER NFPA 72 CODE REQUIREMENTS. F/B FROM BELOW ACQUISITION ICT
FOR CENTRAL BATTERY
Folder Name: \\wsatkins.com\ProjectMEI\AEDXA\5127225-Riyadh Metro\Standard Details\Project Wide Legends & Symbols And Standard Details

FAA FIRE ALARM ANNUNCIATOR SCM SUBSTATION CONTROL MODULE LV LOW VOLTAGE (LV) SYSTEM & UPS SYSTEM WW-XX-YY-ZZ Internal Ref. Internal Rev.
31. CONSIDER SPARE CAPACITY PER LOOP & FACP ACCORDING TO SPECIFICATION & N/A N/A
FACP FIRE ALARM CONTROL PANEL SD STAR DELTA STARTER
MANUFACTURER REQUIREMENTS. EM LIGHTING
FAHU FRESH AIR HANDLING UNIT SF SUPPLY FAN TAG OPTIONS
32. ALL CABLE TRAY/LADDER ACCESSORIES SHALL BE FACTORY FABRICATED. FCU FAN COIL UNIT SIG&COMMS SIGNALLING & COMMUNICATIONS ESSENTIAL SERVICES
FLR FLOOR SL FIRE ALARM SUB LOOP UPS SERVICES EQUIPMENT TYPE CBS, UPS
33. FLEXIBLE CONDUITS SHALL BE LIQUID TIGHT METAL CONDUIT. (TO LIGHT FIXTURES,
FOH FRONT OF HOUSE SMDB SUB MAIN DISTRIBUTION LV BUSDUCT
JUNCTION BOXES, SOCKETS, FIRE ALARM DEVICES AND ETC).
BOARD AB
LEVEL BL (BASEMENT LEVEL) ML (MEZZANINE LEVEL)
FR FIRE RATED LIGHTING, SMALL POWER
34. ALL FIRE ALARM DETECTORS AND MANUAL CALL POINTS ARE WITH INBUILT ADDRESSABLE FS FLOW SWITCH SPD SURGE PROTECTIVE DEVICE
OUTLET
GL (GROUND LEVEL) UL (UNDER PLATFORM LEVEL)
MODULE. FSCP FIRE SYSTEM CONTROL PANEL SPF STAIRCASE PRESSURIZATION FAN
FWP FIRE WATER PUMP SPN SINGLE PHASE NEUTRAL TRUNKING CL (CONCOURSE LEVEL)
35. ALL CONTROL GEARS FOR INDOOR LIGHTING SHALL CONTAIN HARMONIC COMPLIANCE
AND PF IMPROVEMENT NOT LESS THAN 0.95. FWT FIRE WATER TANK SS SOFT STARTER DC (DIRECT CURRENT) PL (PLATFORM LEVEL)
SUP SUMP PUMP MV (MEDIUM VOLTAGE)
36. FIRE ALARM CABLES SHALL BE FIRE RATED, NON POWER LIMITED CIRCUITS SHALL BE SWA STEEL WIRED ARMOURED UNIQUE NUMBER 1, 2, 3, .....
G
SYS SYSTEM
G GROUND NOTE: IN LARGE COMPLEX BUILDINGS WHERE GREATER DEFINITION IS REQUIRED, 'XX' CAN
- LOW VOLTAGE : 1.5SQ.mm MIN. GAP
GEN
GRAPHIC ANNUNCIATOR PANEL
GENERATOR T SWITCHBOARD / EQUIPMENT TAGGING BE ENHANCED TO PROVIDE MORE DETAILS.
-LINE VOLTAGE : 2.5SQ.mm MIN.
GFCI GROUND FAULT CIRCUIT T/A TO ABOVE
FOR MAIN DISTRIBUTION EXAMPLE: CBS-4E2-CL-01 EXAMPLE: UPS-4E2-CL-01 AB 22:09:16 DRAFT FINAL DESIGN SUBMISSION BR DPC KW
POWER LIMITED CIRCUITS SHALL BE FPL, FPLR, FPLP, AS RECOMMENDED BY INTERRUPTER T/B TO BELOW
MANUFACTURER. GI GALVANIZED IRON TCL TOTAL CONNECTED LOAD BOARD AA 20:09:15 DRAFT FINAL DESIGN SUBMISSION BR DPC KW
GL GROUND LEVEL TDL TOTAL DEMAND LOAD EQUIPMENT TYPE
CABLES ARE TO BE MICC (OR) SILICON RUBBER INSULATED, WITH OVERALL PVC SHEATH
TPN THREE PHASE NEUTRAL BUILDING REFERENCE Rev. Date Description By Chk'd App'd
BONDING TO COATED ALUMINUM FOIL (OR) OTHER EQUAL AND APPROVED.
H TR CABLE TRUNKING (REFER TABLE 1) TABLE 1 Drawing Status
H.C HANDLING CAPACITY TTR TRACTION TRANSFORMER
HD
H/L
HAND DRYER
HIGH LEVEL
TVF
TVSS
TUNNEL VENTILATION FAN
TRANSIENT VOLTAGE SURGE
LEVEL (SEE
UPPER-RIGHT TABLE)
TAG
4E2, 4C2, etc. STATION REFERENCE
BUILDING REFERENCE
DRAFT FINAL DESIGN
HP HORSE POWER SUPPRESSION CLIENT
AB UNIQUE NUMBER ES EMERGENCY SHAFT
HVAC HEATING-VENTILATION-AIR TYP TYPICAL
CONDITIONING TMCS TUNNEL MONITORING CONTROL SOURCE OF SUPPLY PS PUMPING SHAFT
SYSTEM
U EXAMPLE: MDB-4E2-BL-1N MDB-WW-XX-YZ VS VENTILATION SHAFT
I PROJECT CONTRACTOR

IDMT INVERSE DEFINITE MINIMUM TIME UPS UNINTERRUPTIBLE POWER CS COMBINED SHAFT
SUPPLY
IFU INTERFACE UNIT NOTE: N - NORMAL POWER SUPPLY EQUIPMENT TYPE (SEE PSS
User name: Guintu, Victor Date:22 September 2016 17:33:00

PACKAGE SUBSTATION
IP INGRESS PROTECTION UPPER-RIGHT TABLE)
ITPS INTERMEDIATE TRACTION POWER V E - ESSENTIAL POWER SUPPLY Project Title
BUILDING REFERENCE
IWP
SUBSTATION
IRRIGATION WATER PUMP
V
VCB
VOLTS
VACUUM CIRCUIT BREAKER (REFER TABLE 1) RIYADH METRO
J
VD
VFD
VOLTAGE DROP
VARIABLE FREQUENCY DRIVE
LEVEL (SEE
UPPER-RIGHT TABLE)
Package 3 (Lines 4, 5 & 6)
JB JUNCTION BOX VT VOLTAGE TRANSFORMER
FOR DOWNSTREAM SUBMAIN UNIQUE NUMBER Drawing Title

K W DISTRIBUTION BOARDS, TYPE OF SUPPLY PROJECT WIDE - ELECTRICAL


kVA KILO VOLT AMPERE WH WATER HEATER MOTOR CONTROL CENTRES GENERAL NOTES & ABBREVIATIONS
kW KILO WATT WP WEATHERPROOF VDB-WW-XX-YZ
& MOTOR CONTROL PANELS
X
XLPE CROSS LINKED POLYETHYLENE Scale Designed Drawn Checked Approved
NTS BR VCG DPC KW
1P ONE POLE
Original Size Date Date Date Date
2P TWO POLE
3P THREE POLE A1 10:02:15 10:02:15 10:02:15 10:02:15
4P FOUR POLE Drawing Number Revision

AB
Copyright C ADA (2016) Filename: M3-DJV-EDR-EEL00-PWD-GEN-1370201.dwg
Author: ATKINS-DUBAI, UAE