Professional Documents
Culture Documents
Contents
8.1 Standard Thee Phase Transformer Connections ................................
....................................... 2
8.1.1 Star connection.......................................................
............................................................ 3
8.1.2 Delta connection .....................................................
........................................................... 5
8.1.3 Three phase power ....................................................
......................................................... 6
8.1.4 Three phase transformation............................................
.................................................... 7
8.1.5 Standard three phase transformer connections .........................
....................................... 14
8.2 Thee Phase Transformer Construction.........................................
........................................... 15
8.5 Open-Delta connection (V-V Connection or V connection) .....................
............................. 28
8.5.1 Voltage relations in open delta connection ...........................
........................................... 28
8.5.2 kVA delivered by an open delta connection ............................
........................................ 31
8.5.3 Applications of open delta system ....................................
............................................... 33
8.6 Three- phase to two-phase conversion (Scott connection) ....................
................................. 35
8.6.1 Basic Theory of Scott Connection .....................................
.............................................. 35
8.6.2 Voltage Relations in Scott Connection ................................
............................................ 39
8.6.3 Position of the Neutral Point on Primary .............................
............................................ 40
8.6.4 Current Relations in Scott Connection ................................
............................................ 41
8.7 Three phase to multi-phase transformer connections .........................
.................................... 48
8.7.1 3-phase to 6-phase conversion ........................................
................................................. 48
8.7.2 3-phase to 12-phase conversion ...........................................
................................................ 60
Chapter 8
Three phase systems are used for transmission of electric power at optimum cost
where the total
power is divided between three conductors. These three lines are commonly design
ated as R-Y-B
or A-B-C or U-V-W with an optional neutral line.
In most power generating stations, three phase AC generators are used for genera
tion of electric
power. Power is transmitted from the generating station by three phase overh
ead transmission
lines. Three phase transformers are therefore necessary to bring up the voltage
(step up) before
transmission and to step down the voltage at the receiving station for distribut
ion.
A three-phase balanced system is characterized by three voltages and currents, e
ach individually
being pure sinusoidal signals under ideal conditions. RMS values of th
ese three sinusoidal
0
signals are same, but they are displaced from each other in phase by 120 in a b
alanced system.
For such a balanced supply system, summation of the three signals at every ins
tant is zero as
shown in Figure 8.1.
V V V V V V V V V V V V
(8.2)
AB A B A N B N A N B N
AN BN
----------------------- Page 4-----------------------
The line voltage V can thus be represented in the phasor diagram as
the phasor summation of
AB
V and V reversed.
AN BN
VBN
1200
N
600
VCN VAN
-VBN
VAB
Then, the line current, say at node A in Figure 8.4, can be expressed following
KCL as:
I A I AB I CA I AB I CA
(8.7)
The line current I can thus be represented in the phasor diagram as
the phasor summation of
A
I and I reversed.
AB CA
----------------------- Page 6-----------------------
I I
AB CA
1200
600
I
A
-ICA
IBC
Figure 8.5 Phasor diagram of balanced delta connected system of currents
From the phasor diagram, magnitude of the line current can be determined as:
2 2 0
I I I 2 I I cos60
A CA AB CA AB
2 2 1
I I 2 I I
ph ph ph ph 2
2 2 2
I I I
ph ph ph
2
3I
ph
3I ph (8.8
)
For a balanced three phase system, the other line currents can also be derived i
n the same manner
as:
I A I B I C 3I ph (8.9)
The line currents in a balanced delta connected system are thus related to the p
hase currents as:
I L 3I ph (8.1
0)
For a balanced system, if the line voltages are denoted as V and voltages acro
ss each of the three
L
phase windings are denoted by the quantity V , the
n they are basically same as indicated in
ph
Figure 8.4 such that:
V V (8.1
1)
L ph
If the same load is connected to a delta connected system, the total three phas
e power is given
by:
P 3 V I cos
ph ph
I
L
3 V cos
L
3
3V I cos (8.13)
L L
The equivalence between (8.12) and (8.13) indicates that irrespective of the typ
e of connection,
star or delta, the power delivered (or consumed) remains same for a given three
system. Power is
generally expressed in terms of the line voltage and line currents since it is c
onvenient to connect
voltmeter and ammeter in the line that are external to the device, rather than
in the phase coils
which are often inaccessible.
(a)
B
300
VBC VBN VAB
b
N
c
VCN VAN
a
C A
VCA
(b) (c
)
Figure 8.7 (a) Star connected HV side connected to 3 phase supply, while LV is s
till unconnected
(b) Line and phase voltages applied to HV side (c) Phase voltages in
duced in unconnected
secondary LV coils a, b, and c.
The line and phase voltages prevailing in the HV side is shown in Figure 8.7(b).
With the phase
voltage magnitudes being 400 V (rated HV voltage), the line voltages are 400 3=693
V. Note
that both the three phase voltages and the three line voltages maintain phase
displacements of
0
120 from each other.
Due to transformer action, voltages induced in the secondary LV coils a, b, and
c, respectively,
bear the same relation to each other as the phase voltages of primary HV side. M
agnitude of each
of the phase voltages on LV side is 200 V as per the turns ratio, and their phas
or relationships,
when unconnected, is shown in Figure 8.7(c). Different possibilities for interc
onnection of the
secondary LV coils will now be investigated.
Star connected LV with dotted terminals as output
----------------------- Page 9-----------------------
Figure 8.8(a) shows a connection where the secondary LV windings are star conne
cted with the
un-dotted terminals are joined together to a common point (n) and the
dotted terminals are
connected to external lines a, b, and c. As per the phasor relations of Figure 8
.7(c), the phase and
line voltages of the star connected secondary LV is shown in Figure 8.8 (b). Lin
e voltage across
any two LV terminals is obtained as phasor combination of two corresponding ph
ase voltages.
Thus, the voltage between lines a and b is the phasor summation of phase voltage
s between a1-n
and n-b1. In LV side also, the line voltage is 3 times phase voltage, i.e. 200 3 = 3
46 V.
A
a
A 1 A2 a2
a1
A
a
VCA B VAB B1 B B2 N n b2
b b1 Vab b Vca
VBC C
c Vbc
C1 C2 c2
c1
C
c
(a)
b
300
Vbc Vbn Vab
n
Vcn Van
c a
Vca
(b)
Figure 8.8 (a) LV side star connected with un-dotted terminals joined together t
o common point
(b) Line and phase voltages available at LV side
Compare the LV phasors in Figure 8.8(b) with the HV phasors in Figure 8.7(b). Fo
r the type of
connection made in Figure 8.8(a), there is no phase displacement between the lin
e voltages of the
secondaries and line voltages of the corresponding primaries. Same is true for t
he phase voltages
of primaries and secondaries. The two phasor diagrams of Figure 8.8(b) and Figur
e 8.7(b) look
exactly similar, the only difference being in magnitude of the voltages due to t
urns ratio of the
transformer.
Star connected LV with dotted terminals as the common junction point
Figure 8.9(a) shows a connection where the secondary LV windings are star connec
ted with the
dotted terminals are joined together to a common point (n) and the u
n-dotted terminals are
connected to external lines a, b, and c. The HV star connection however, remains
same as before.
Connecting the instantaneous positive terminals to the common point n, rather th
an to the lines,
0
produces 180 reversal of the secondary LV phase voltages with respect to Figu
re 8.7(c). The
0
line voltage will thus also be reversed by 180 as shown in Figure 8.9 (b).
(a)
Vca
a c
Van Vcn
n
Vab Vbn
300 Vbc
b
(b)
Figure 8.9 (a) LV side star connected with dotted terminals joined together to c
ommon point (b)
Line and phase voltages available at LV side
While magnitudes of all phase and line voltages are the same in Figures 8.8(b) a
nd 8.9(b), they
0
are 180 out of phase with respect to each other. When operating individually, t
hese two different
connections can be used with equal effectiveness, but they can never be connect
ed in parallel.
Doing so will produce an immediate short circuit and large circulating current a
mong the parallel
connected secondary LV windings.
Star connected LV with one coil reversed with respect to polarity
The two LV star connections demonstrated in Figures 8.8 and 8.9 are individually
correct and
can be used individually, if one does not attempt to connect these two in paral
lel. However, if
accidentally one makes a wrong connection by reversing any one of the LV coils w
ith respect to
polarity, then the line voltages get disturbed, even if the phase vol
tage magnitudes remain
undisturbed. This is demonstrated in Figure 8.10(a) where the coil b
on LV side has been
reversed as compared to Figure 8.8(a). The HV connection howev
er, remains same as
previously.
A
a
A 1 A2 a2
a1
A
a
VCA B VAB B1 B B2 N n b1
b b2 Vab b Vca
VBC C
c Vbc
C1 C2 c2
c1
C
c
(a)
----------------------- Page 11-----------------------
n
Vcn
Van
Vca
c
a
600 Vbn
Vbc Vab
b
(b)
Figure 8.10 (a) LV side star connected with coil b reversed (b) Line and phase v
oltages available
at LV side
As observed in Figure 8.10(b), reversal of coil b in the secondary LV side distu
rbs the relative
displacement between the three phase voltages and also the three line voltages.
Though the phase
voltages still remain 200 V, the line voltage magnitudes get disturbed. The two
line voltages Vab,
and Vbc reduce to 200 V each (equal to phase voltage), while the third line volt
age Vca is 200 3
= 346 V. The three secondary LV line voltages are thus neither equal in magnitud
e, nor displaced
0
from each other by 120 .
When used independently, such connection will not give satisfactory ope
ration of the load
connected to the secondary LV side due to unbalanced line voltages available. In
addition, if this
transformer is paralleled with any one of Figures 8.8 and 8.9, large circulating
current among the
LV coils will flow due to large differences in respective line voltages across t
he three terminals.
Delta connected LV with correct polarity
With the primary HV coils connected as star as before, the three sec
ondary LV coils can be
connected in delta. For correct delta connection it is required that
coil ends of opposite
instantaneous polarity are connected together to form a closed loop as shown in
Figure 8.11(a).
A
a
A 1 A2 a2
a1
A
a
VAB B B2 b2
b Vab
VCA B B1 N
b1 b Vca
VBC C
c Vbc
C1 C2 c2
c1
C
c
(a)
B
b
Vab
300
VBC VBN VAB
Vbc
a
N
VCN VAN Vca
C VCA A c
(a)
b
Vab
Vbc
a
Vca
V =0
R
c
(b)
Figure 8.12 Use of voltmeter to check correct delta connection in secondary LV (
a) connection
diagram for checking V = 0 (b) Secondary LV phasor diagram for cor
rect delta connection
R
resulting in V = 0.
R
(a)
B
b
300
Vbc
VBC VBN VAB
N c
Vab
VCN VAN
Vca
C A
a
VCA
(b)
(c)
Figure 8.13 (a) HV side star connected, LV side delta connected, both
with proper regard to
polarity (b) Line and phase voltages applied to primary HV star side (c) Line an
d phase voltages
available at secondary LV delta side
Reversing the terminals of LV coils to be connected as delta with regard to thei
r instantaneous
polarities produces makes the secondary LV phase voltages re-orient as shown in
Figure 8.13(c).
When operating individually, both these two different delta connections shown in
Figures 8.11
and 8.13 are correct and can be used with equal effectiveness, but they can neve
r be connected in
parallel . Doing so will produce an immediate short circuit and large circulatin
g current among
the parallel connected secondary LV windings.
Delta connected LV with incorrect polarity
The mandatory requirement for correct delta connection is that
coil ends of opposite
instantaneous polarity are to be connected together to form a closed loop as was
earlier shown in
Figures 8.11 to 8.13. However, if accidentally one of the LV coils of the transf
ormer is reversed,
high circulating currents will flow in the transformer secondary LV de
lta connection causing
severe damage. Let us consider the case when the coil c of LV is accidentally r
eversed making
the delta connection as shown in Figure 8.14(a). The primary HV connection howev
er, remains
connected correctly as star as before. The corresponding LV phasor diagram in Fi
gure 8.14(b)
shows that the resultant of three LV phase voltages is not zero, as would have
been for a properly
connected closed delta loop. Such an erroneous connection will cause large shor
t circuit current
to flow in the secondary LV delta once the loop is closed. It is t
hus recommended that a
----------------------- Page 14-----------------------
voltmeter be used as earlier to check this resultant voltage before c
losing the delta. In such a
case, Vab will read 200 V, Vbc will read 3200 = 364 V and Vca will read 2200 = 400
V. The
moment the voltmeter is removed and attempt is made to close the delta by connec
ting a1 and c1
together, we are actually shorting two terminals which are at a poten
tial difference of 400V.
Such a wrong delta connection will thus not only make the line voltages totally
unbalanced in the
secondary LV delta side, but will damage the transformer due to flow
of large short circuit
current. Effect of such severe short circuit on the secondary will also get refl
ected on the primary
side as well causing primary voltages to get unbalanced as well unles
s the supply is not
sufficiently stiff.
A a
A 1 A2 a2 a1
A
a
VAB B B2 VR b2 b V
ab
VCA B B1 N b1
b Vca
VBC C c V
bc
C1 C2 c2 c1
C
c
(a)
b
Vab
h
p a
V V
3 b
=
c
b
V
Vc
h
p
V
2
=
c R
V
=
a
c
V
(b)
Figure 8.14 (a) HV side correctly star connected, LV side delta conne
cted, but with improper
polarity (b) Line and phase voltages of wrongly connected secondary LV delta sid
e
Foregoing discussions in this section have enumerated the importance of
checking the correct
instantaneous polarity markings on the coils to be interconnected in three phase
transformers.
8.1.5 Standard three phase transformer connections
As discussed previously, both the HV and LV coils of a three phase
transformer may be
connected as star or delta as per the requirement. Accordingly, the s
tandard connections
available for three phase transformers are star-delta, delta-star, delta-delta,
or star-star. Whether
the connection type to be used for a given application is star or delta depends
on factors such as
the operating voltage level, insulation, load to be connected, and har
monic suppression.
Remember that for a delta connection, line voltages are equal to the phase volta
ges and for a star
1
connection, phase voltages are times line voltages. Consider the sc
hematic diagram of a part
3
of a power system shown in Figure 8.15. The generator voltage of 25 kV is first
stepped up to a
higher voltage level of 132 kV by the generator transformer T1. Power is transmi
tted at 132 kV
----------------------- Page 15-----------------------
before being stepped down by the transformer T2 to a voltage level o
f 11 kV for primary
distribution. A third transformer T3 is used to step down the voltage
further to 415 V to
distribute the power at low voltage to consumers. All the three trans
formers shown in the
diagram are three phase transformers that are used to transfer the po
wer at different voltage
levels.
25 kV 132 kV 132 kV
11 kV
G
T1 T2
T3
Consumer
25 kV 25/ 132 kV 132/
11 kV 11/0.4 15 kV
the middle is , whereas flux in the left and right vertical sections are only
. In the top most
2
and bottom most horizontal sections, the flux is also only .
In the two horizontal sections at the
2
3
middle, the flux is as explained in the phasor diagram of Figure 8.17 (
b).
2
----------------------- Page 18-----------------------
R R
2 2
R
Y Y
2 2
Y
R
3
2
B B
R
2
2
2
Y
2
H
V
Y B B
Y
2
2
Y
B
(a)
(b)
Figure 8.17 (a) Three phase shell type construction (b) Phasor diagram to calcul
ate resultant flux
in two horizontal sections at the middle when the two fluxes are subtractive
Such non-uniform distribution of flux makes core construction extremely difficu
lt. In order to
have uniform flux density in all sections of the core, different sections need t
o be of different
cross sections; that not only increases cost of manufacture, also makes it diffi
cult to assemble
laminations of different sizes. If the entire core is made of same cross section
, then some part of
the core will get saturated due to excessive flux density and some other part wi
ll remain under-
utilized due to low flux density.
To avoid this situation, a simple solution can be achieved by reversing the wind
ing direction of
the middle coil, i.e. the coils of Y phase. This can be done by interchanging th
e terminals of Y
phase. This makes the flux of phase Y to reverse its direction as shown in Figur
e 8.18(a). In the
two horizontal sections at the middle, the flux coming from opposite directions
are now additive
so the resultant flux there is as explained in the phasor diagram of Figu
re 8.18 (b).
2
----------------------- Page 19-----------------------
R R
2 2
R
Y Y
2 2
Y
R
B
B
2
2
R
2
H
V
2
Y B
B
Y
2
2
Y
B
(a)
(b)
Figure 8.18 (a) Three phase shell type construction with middle phase
terminals reversed (b)
Phasor diagram to calculate resultant flux in two horizontal sections at the mid
dle when the two
fluxes are additive
This makes flux in all the sections equal ( ), except for the vertical m
iddle section where it is
2
. The core construction is much easier and less costly since cross section in mo
st part of the core
can now be made equal without causing saturation.
Though overall size of the core is more in shell type construction a
s compared to core type
construction, one great advantage of the shell type is that since the
three magnetic paths are
mostly independent (quasi-independent), in case of fault in any one of the phase
coils, the other
two coils can still be used to supply the load without hampering the magnetic fl
ux. One such
condition is the open delta mode of operation, as will be discussed in detail in
later sections,
where the transformer will be found to be able to deliver up to 58% of its ratin
g even with one of
the phases getting opened. This is not possible in core type construction, since
the resultant flux
in the core is influenced by all the three phase fluxes in every part of the cor
e. Thus, a fault in
any of the winding will disturb the flux distribution throughout the
entire core causing the
transformer to fail to operate satisfactorily.
----------------------- Page 20-----------------------
At this point we are ready to compare the relative merits and demerits of whethe
r to use three
single phase transformers connected in a bank, or to use a single three phase tr
ansformer.
A single three phase transformer is big and heavy as compared to any of t
he single phase
transformers. And thus a big three phase unit is more difficult to han
dle, transport and
install. Specially installation in places where space is a constraint,
such as in mines; it is
thus recommended to use bank of three single phase transformer
s that are easier to
transport individually rather than a single big three phase unit.
Single three phase unit is more difficult and costly to repair or even f
or maintenance than
single phase units. In case of fault in any one of the units of the ba
nk, it can be taken out
of service for maintenance without disturbing the other two. But for a
single three phase
transformer, the entire unit need to be taken out of service, entire oi
l to be drained out,
entire heavy core with coils need to be de-tanked before attempting any
repair job.
It is obviously less costly to keep one standby (spare) when three single
phase units are
used in a bank, rather than a single three phase unit. In case of fault
in any one of the
three single phase transformers, only the faulty unit needs to be repla
ced by the spare one
and service can be restored quickly. On the other hand, if a
single three phase unit is
used, then even for a minor fault, the total unit needs to be taken ou
t and replaced by a
similar big unit.
When three separate single phase units used in a bank are conn
ected in delta, it is
possible to supply de-rated three phase supply in open delta mo
de when one single
phase unit becomes faulty. In open-delta mode, the faulty unit
is simply removed and
continuity of three phase supply is maintained by operating th
e remaining two healthy
units in open delta mode delivering up to 58% of the original power ca
pacity till the
faulty unit is replaced. This facility is often not possible when a sin
gle three phase unit is
used where all the magnetic circuits are interlinked, thus fau
lt in any of the three
windings will affect the other two phase thereby preventing satisfactor
y operation of the
whole transformer.
In spite of these disadvantages, the common practice is to use single three
phase unit rather
than a bank of three single phase units due to the following reasons:
The great advantage of using a single three phase unit rather than t
hree separate single
phase units is in terms of large saving in core material. Whereas
as three single phase
transformers will require three independent cores, having a
t least six limbs, a core
type three phase transformer will require only three limbs . This
is possible because in
a single three phase unit, the same iron is being utilized by all
the three phases for
flow of flux, which is not possible in three single phase units wh
ere the flux paths are
obviously independent as the transformers are physically separate.
A three phase unit
used for the same purpose roughly requires only one third
of the core material
required if three single phase units are connected in a bank.
Reduced core material obviously reduces the cost of iron in a single
three phase units
in comparison to three single phase units connected in a bank.
When the interconnections between windings of different phases are d
one internally,
which is commonly the case, a single three phase unit wi
ll require only three
terminals to be brought out of the transformer tank to b
e connected to power lines
both in HV and LV sides. Thus three HV bushings and thr
ee LV bushings are
----------------------- Page 21-----------------------
sufficient when a single three phase unit is used. On the other ha
nd, when three single
phase units are to be connected in a bank, there is no
provision for internal
connections, and all connections for star or delta whatever the ca
se may be, must be
done externally. Thus from each of the three single phase units f
our terminals (two
HV and two LV) need to be brought out of the tank and then to be
interconnected
externally. Thus a bank of three single phase units will require a
t least 12 bushings
which obviously increase the cost.
Since the entire three phase assembly is compact in size, the size o
f tank and amount
of oil required is less if a single three phase unit is used in pl
ace of three separate
single phase units. This also saves overall cost.
Additionally, three separate single phase units will require three ti
mes more number
of accessories such as breather, conservator, Buchholzs relay, valv
es, indicators etc.
as compared to a single three phase unit.
A three phase transformer is thus cheaper (by approximately 15%) tha
n when a bank
of three single phase transformers are used for the same purpose.
A single three phase unit is more efficient than three single phase u
nits since the core
losses are less in former due to shorter magnetic path and less vo
lume of iron being
used in core.
The space required for installing three single phase units is genera
lly more since they
need to be physically separated from each other to enhance safety a
nd cooling. On the
other hand, the overall floor space necessary to install
a single three phase unit is
comparatively less.
Example 8.2: Three single phase 50 kVA, 2300/230 V, 50 Hz transformers are conn
ected to
form a three phase star-delta transformer. The equivalent impedance of each tran
sformer
referred to HV side is (1.2 + j1.6) . The three phase transformer thus formed sup
plies a
----------------------- Page 24-----------------------
three-phase load of 120 kVA at 230 V with 0.85 power factor (lag).
Determine voltage
regulation of the transformer.
3
120 10
With the connected load, secondary line current I
301.23 A
2L
3 230
301.23
Secondary phase current I 2ph
173.92 A
3
2300
Ratio of turns per phase = a 10
230
The impedance of (1.2 + j1.6) when referred to LV side is:
Z 1.2 j 1.6
e
Z 0.012 j 0.16 R jX
e 2 2 e e
a 10
Given, load power factor, cos 0.85
1 0
cos 0.85 31.79
Thus, the secondary load current per phase can be represented as: I 2ph
173.92 31.790
Taking the no-load secondary voltage of 230 V as reference, the secondary voltag
e at full load
is given by:
V E I R jX
2 2 2 e e
230 173.92 31.790 0.012 j 0.016
226.76 0.320 V
E V 230 226.76
% Regulation = 2 2 100% 100% 1.43%
V 226.76
2
3
100 10
Power per phase
3 100
Rated current per phase in delta connected primary
Voltage per phas
e 11000 33
Rated Primary voltage per phase 11000
Base impedance 3630
Rated Primary current per phase100
33
Note that per unit impedance of a transformer remain unaffected whether it is re
ferred to primary
or the secondary.
3
100 10
Power per phase
3
Full load LV winding current per phase I 2
144A
Voltage per phase
400
3
400
Voltage per phase 3
LV winding base impedance = 1.6 ohm
Current per phase 144
LV winding impedance = Per unit impedance base impedance
4.5
= 1.6 0.072 ohm
100
When LV is short circuited, the LV winding voltage is entirely consum
ed in the internal
impedance of the winding.
Thus, to circulate half the full load current i.e. 144/2 = 72 A current, the req
uired LV voltage is
720.072 = 5.18 V
HV voltage per phase 11000
Now, per phase turns ratio a 47.63
LV voltage per phase 400
3
Hence, corresponding voltage to be applied to the HV side is 47.635.18 = 246.7 V
Ans
Load
c2
A 1 C2
a1 c Ic
C
IC
Figure 8.80 Open delta (V-V) connection of transformers
Let the primary supply line to line voltages are VAB, VBC and VCA as applied t
o the three input
terminals A, B, and C. These three line voltages form a balanced set of three-ph
ase voltage being
0
displaced by 120 with respect to each other. Arbitrarily considering the phase
sequence A-B-C,
these three voltages can be represented as following taking V
as the reference phasor:
AB
V V 00
AB P
0
V V 120
BC P
----------------------- Page 29-----------------------
0
V V 120
CA P
Where, V is the magnitude of primary line voltage.
P
The primary voltage phasor diagram is shown in Figure 8.81. A three phase balan
ced voltage
0
(each of same magnitude and displaced from each other by 120 ) is applied at the
three terminals
A, B, and C.
VAB
A B
VCA VBC
C
Figure 8.81 Three phase balanced supply line voltage phasors
Voltages induced in the two healthy secondary coils are available between the ou
tput terminals
a-b, and c-a. Let these voltages be denoted by Vab, and Vca. Magnitudes of these
two secondary
voltages are determined by the per-phase turns ratio:
V V V Primary turns per phase
AB CA P Turns ratio a
Remember that the primary and secondary coils of the same phase are put one the
same limb and
are linked by the same mutual flux. Thus the primary and secondary voltages of s
ame phase coils
do not have any phase angle difference between them. Thus, since the primary vol
tages on AB
0
0
and CA phases are represented by V V 0 , and V
V 120 , so the two
AB P
CA P
corresponding secondary line voltages can be denoted as:
V V 0 0 V V
0 0
V AB P 0 V 0 , and V CA P 120 V
ab S ca
S
a a a a
Though there is no winding between the terminals b and c in the secondary side (
coil c1-c2 is
absent), but there exists a potential difference between the terminals b and c.
Let this voltage be
denoted by Vbc :
V V V
bc b c
or, V V V V V
bc b a c a
----------------------- Page 30-----------------------
or, V V V V V
bc a b c a
or, V V V
bc ab ca
or, V V V
bc ab ca
0 0
or, V V 0 V 120
bc S S
0 0 0 0
or, V V cos0 j sin 0 cos120 j sin 120
bc S
1
or, V V 1 j 0.866
bc S
2
1
V V j 0.866
or, bc S
2
1
V V j 0.866
or, bc S
2
0 0
or, V V cos 120 j sin 120
bc S
0
or, V V 120
bc S
Thus, across the three secondary terminals we get three line voltages given by:
0 0 0
V V 0 , V V 120 , and V V 120
ab S ca S bc S
It is interesting to note that these three secondary line voltages form a triad
of three balanced
0
voltages of equal magnitude and displaced from each other by 120 . Thus, with t
wo transformers
only, it is possible to obtain a three phase balanced set of voltage
s in the secondary with no
difficulty in supplying a three phase load.
Phasor diagram of the secondary side line voltages are shown in Figure 8.82(a).
The line voltage
Vbc is represented by dotted line to indicate that the corresponding coil is act
ually absent.
Vab
a b
Vca Vbc
c
Figure 8.82 Three phase balanced secondary line voltage phasors
Power (VA) rating of the three phase healthy delta connected transformer bank i
s:
P 3V I 3V 3I 3V I (8
.14)
healthy L L ph ph ph ph
Now, with open delta connection, the line voltages still remain same as that acr
oss each of the
phase coils (i.e V V ) for all the three voltages Vab, Vbc
, and Vca. For a balanced load
L ph
connected between the three lines of secondary, since the three phases of the lo
ad receive same
0
voltage (at 120 with respect to each other), the three line currents must also
be balanced (same
0
magnitude, but displaced from each other by 120 ). However, the line currents in
lines b and c (I
b
and I ) should not be more than the rated currents in the corresponding phase co
ils, i.e. I = I =
c
L1 b
I = I , I = I = I = I . The third line current I =
I must be equal to (I + I ) for satisfying
ba ph L2 c ac ph L3
a b c
KCL at node a.
Thus,
0 0
I I I I 0 I 120
a b c ph ph
The three secondary line currents are thus seen to form a balanced set of three-
phase currents
0
with same magnitude (= Iph) and displaced from each other by 120 .
It is thus seen that without overloading any of the two remaining coils, the lin
e currents can no
longer be more than the currents flowing through individual phase coil
s, i.e. I L I ph for the
secondary line currents.
Thus, power (VA) delivered to the load by the open delta connected transformer b
ank is:
P 3V I 3V I (8.15)
open L L ph ph
----------------------- Page 32-----------------------
Hence, when one out of the three transformers in a delta-delta bank fails, it is
still possible to
supply a three phase load, but with a reduced capacity of 57.7%.
[It means that when one of the three transformers in a healthy three-phase delta
connection
gets damaged, then with open delta mode it is still possible to supp
ly balanced three phase
powe r but the load current must be reduced to 57.7% of its original value. Othe
rwise the two
healthy coils will get over loaded by 1/0.577 = 1.732 times, i.e. 73.2% more].
Thus, without exceeding the ratings of the two remaining healthy tran
sformers, the capacity
available under open-delta mode is less than the total available capa
city of the two healthy
transformers. Each of the two healthy transformers have power (VA) ratings of V
I , so the
ph ph
total installed capacity is 2V I , whereas the open delta
connection can only provide a
ph ph
capacity of 3V I .
ph ph
The ratio of actual open delta capacity and the total available (or installed)
capacity is expressed
by the term utilization factor (UF) or rating factor for open delta connection:
Thus, each transformer shares 57.7% of the total VA, and not 50% of the total V
A as anticipated.
It is now understood that an open delta connection can still be used to supply
a three phase load,
but with reduced capacity. If by any means, the same load stay connected to the
system, then the
share of load to be supplied by the healthy transformers gets increased drastic
ally and both the
two healthy transformers get overloaded. This increased amount of load can be ca
lculated as:
[Note that in a healthy three phase system, each of the three transformers take
1/3rd (33.3%) of
the total load.]
Thus, each of the two healthy transformers will get overloaded by 73.
2% if the same load is
continued to be supplied even after one of the three transformers in the three-p
hase delta-delta
bank has failed.
The other difference that can be observed is in values of the power
factor of the two healthy
transformers in comparison to the load power factor when open delta connection i
s being used. It
can be shown that if the load power factor angle is , then one of two transforme
rs in the open
0
0
delta configuration operates at a power factor of cos(30 + ) while the other o
perates at cos(30
- ).
Solution:
With healthy / connection:
Secondary load = 150 kW, at VLS = 440 V and 0.8 pf lagging.
----------------------- Page 34-----------------------
3
P 3V I cos 150 10 3 440 I 0.8
healthy LS LS LS
Thus, secondary line current I LS 246A
Given primary line voltage VLP = 11000 V
V
440
Thus, primary line current can be calculated as I LP LS I LS
246 9.84A
V
11000
LP
Since both the primary and secondary windings are connected in delta, current in
each phase, i.e
1
current in each winding will be times the corresponding line cur
rents.
3
246
Thus, current in secondary phase windings = I phS 142A
3
9.84
And, current in primary phase windings = I phP 5.68A
3
With V-V connection:
The secondary load is maintained at 150 kW, at VLS = 440 V and 0.8 pf lagging.
3
150 10
Thus, secondary line current I LS 246 A
3 440 0.8
Since in open delta mode, the secondary line current is equal to the
phase current, now the
current in secondary phase windings become IphS = 246 A (as compared
to 142 A in /
connection).
And, primary phase current = I phP Secondary phase cur
rent x transformation ratio
440
246 9.84 A (as compared to 5.68 A in / connection)
11000
To find out the power shared by each of two healthy transformers, re
member that in V-V
connection, if the load power factor angle is , then one of two transformers oper
ates at a power
0 0
factor of cos(30 + ) while the other operates at cos(30 - ).
For load power factor of 0.8, = cos-10.8 = 36.870
st
0 0
Thus, power delivered by 1 transformer P = 440x246xcos(30 + 36.87 ) = 42.52
kW
1
nd
0 0
And, power delivered by 2 transformer P = 440x246xcos(30 - 36.87
) = 107.47 kW
2
50%
86.6%
(a) (b)
A
d
a
VL o
L
86.6%
e
d Teaser e
i d
s i
e s
s e
a s
h a
p h
e- VL B p-
e o
r w
h
T T
d
a
o
VL 50% L
Main
C
(a)
I =I
A 1T A
A
I2T
a
V1T V2T Phase 1
Load
VL 86.6%
d
Teaser
VL
I =I 50%
B 1M D
B C
B
b c
I2M
V =V V2M
L 1M
Main
Phase 2 Load
IC
C
(b)
Figure 8.84 Schematic diagrams for Scott connection
For a balanced three-phase input voltage source,
----------------------- Page 37-----------------------
V V V V
(8.19)
AB BC CA L
Let us take VBC as the reference voltage, and draw it along the hor
izontal axis, so that the
primary voltage phasor diagram is as shown in Figure 8.85.
VAB
1200
1200
VBC
1200
VCA
Figure 8.85 Primary voltages phasor diagram
The three line voltages can be represented as:
V V 00
BC L
0
V V 120
CA L
0
V V 120
AB L
Now, V V V
AB AD DB
or, V V V
AD AB DB
Since, V V , the expression for teaser transformer primary winding volt
age can be written
BD DB
as:
V V V V
(8.21)
1T AD AB BD
----------------------- Page 38-----------------------
0 1 0
V 120 V 0
L L
2
0 0 0 0
V cos120 j sin120 0.5V cos0 j sin 0
L L
V j 0.866V
AD L
0.866V 900
(8.22)
L
3 0
V 90
L
2
Comparing (8.22) with (8.20), we see that the voltage across teaser transformer
primary V is
AD
0.866 times (i.e. 86.6%) the voltage across the main transformer primary, and al
so that the teaser
V 0
transformer primary voltage leads the main transformer primary voltage
BC by 90 . Voltage
rating of the teaser transformer primary winding is thus only 86.6% o
f that of the main
transformer.
These two primary voltages across the main and the teaser transformers, V
and V , are now
BC AD
included in the primary voltage phasor diagram as shown in Figure 8.86.
VAB VAD
V V V
AD AB BD
900
VBD VBC
VCA
VAD
r Vad
e
s
a r
e e
T 900 s
a 900
e
T
Main VBC Main V
bc
(a) (b)
Figure 8.87 Main and Teaser transformer voltage phasors (a) primary (b) secondar
y
Since the phase angle between the two secondary voltages of main and teaser tran
sformer i.e. Vbc
0
and Vad is 90 , the two voltages Vbc and Vad produce a set of two-phase system
. Thus, a three-
phase system has been converted to a two-phase system. In a reverse
manner, a two-phase
system can be converted to a three-phase system. If a two-phase volta
ge is applied at the
terminals a-d and b-c, the voltages at terminals A-B-C will produce a three-phas
e system.
Thus, in order to keep same value of voltage per turn in both the two transforme
r, the number of
turns in the teaser transformer primary (T1T) must be 86.6% of that
in the main transformer
primary (T1M). That is why a tap is taken out from 86.6% of the pr
imary turns on the teaser
transformer to be connected to the mid-point of the main transformer as shown in
Figure 8.84.
Thus, T 0.866T
(8.23)
1T 1M
T T
2T 2M
V T
or, 2T 2T
(8.26)
V T
2M 2M
Thus, secondary voltages V2T and V2M of the two transformers can be
made equal if the two
transformers have same number of turns in their secondaries, i.e. if T2T = T2M .
Thus, we can get a
0
perfectly balanced set of two-phase voltages at the output, of equal magnitude
and at 90
phase difference with respect to each other.
Two exactly identical transformers with tappings at 50% and 86.6% on their prima
ry windings
and equal number turns in their secondary windings can thus be used
for Scott connection
purpose. For the transformer being used as the main, the 50% tap position is to
be used, and the
transformer being used as the teaser, its 86.6% tap position is to be used.
8.6.3 Position of the Neutral Point on Primary
When the three-phase supply on primary side is from a 4-wire system,
then it is necessary to
provide a proper position for the neutral point on the Scott connected transform
er. The neutral
point N is provided on the teaser transformer as shown in Figure 8.88 at a prope
r position such
that:
V
Phase voltage: V L
AN
3
3
From (8.22), since V V , we must have:
AD L
2
3V V V
V V V L L L
ND AD AN
2 3 2 3
----------------------- Page 41-----------------------
A
A
N
VL 86.6%
Teaser
VL
D 50%
B
VL Main
C
When two identical transformers are used for the Scott connection, if T (= T
) is the primary
1 1M
number turns in main transformer, then number of turns used in the primary win
ding of teaser
transformer is T = 0.866T .
1T 1
Let, both main and teaser transformers have same number of turns T
(= T =T ) in their
2 2M 2T
secondaries.
Neglecting no-load current, the primary and secondary winding MMFs must be balan
ced in the
teaser transformer, such that:
Primary MMF = Secondary MMF
I 0.866T I T
A 1 2T 2
1 T
2
I I
A 2T
0.866 T
1
T
2
or, I A 1.155 I 2T
T
1
T
If the turns ratio per phase is designated as 1 a , then:
T
2
I
I A 1.155 2T
(8.28)
a
If the primary and secondary windings of the main transformer are made with same
number of
turns, i.e. if it is an 1:1 transformer, then a = 1, leading to the relation:
I A 1.155 I 2T
(8.29)
In order to establish such MMF balance equation for the main transformer it is n
ecessary to note
that the current directions in sections BD and CD of the main winding primary a
re opposite to
each other (refer Figure 8.84(b)).
Primary MMF = Secondary MMF
I T I T I T
(8.30)
B BD C CD 2M 2
Since D is at 50% tap position of the main transformer primary winding, it divid
es the total turns
1
equally. So, T T T
BD CD 1
2
T T
From (8.30), I 1 I 1 I T
B C 2M 2
2 2
T
or, I I 1 I T
B C 2M 2
2
T
or, I B I C 2 I 2M 2
T
1
----------------------- Page 43-----------------------
I
or, I B I C 2 2M
(8.31)
a
If a = 1, i.e. the main transformer primary and secondary turns are equal, then:
I B I C 2I 2M
(8.32)
For a 3-wire system, KCL at D (Figure 8.84(b)) gives:
I I I 0
A B C
I C I A I B
(8.33)
From (8.31) and (8.33):
I
2M
I I I 2
B A B
a
I
2M
or, 2I B I A 2
a
I
2M
or, 2I B I A 2
a
1 I
or, I B I A 2M
(8.34)
2 a
If a = 1, i.e. the main transformer primary and secondary turns are equal, then:
1
I B I A I 2M
(8.35)
2
Now from (8.33) and (8.34):
I I I
C A B
1 I
2M
or, I C I A I A
2 a
1 I
2M
or, I C I A
2 a
1 I
or, I C I A 2M
(8.36)
2 a
If a = 1, i.e. the main transformer primary and secondary turns are equal, then:
1
I C I A I 2M
(8.37)
2
----------------------- Page 44-----------------------
Example: Resistive loads of 5 and 10 are connected respectively across the teaser
and main
transformer secondaries of a Scott connected transformer arrangement, fed from a
3-phase, 230
V supply mains. If the main transformer primary to secondary turns ratio is 2, t
hen determine the
supply line currents. Neglect the magnetizing current and internal impedance dro
ps.
Solution:
Given supply voltage is V = 230 V.
L
Teaser transformer primary voltage V = 0.8
66 V
AD
L
= 0
.866230 = 199.18 V
And, Main transformer primary voltage V = V
= 230V
BC
L
T
Turns ratio of main transformer: a 1 2 .
T
2
V 230
Main transformer secondary voltage Vbc = V2M =
BC 115V
a 2
0.866T T
Turns ratio of teaser transformer 1 0.866 1 0.86
6 2 1.732
T T
2 2
V 199.18
Teaser transformer secondary voltage Vad = V2T =
AD 115V
1.732 1.732
I
A A
A
I2T
a
V2T
ZL1
VL 86.6%
d
Teaser
VL
IB D 50%
B C
B
b c
I2M
V2M
VL Main
ZL2
IC
C
V
115
Load current in teaser transformer secondary I 2T 2T
23 A
Z
5
L
1
V
115
Load current in main transformer secondary I 2M 2M
11.5A
Z
10
L
2
Since only resistive loads are connected, current and voltage are in
the same phase in the
secondary sides of both the teaser as well as the main transformer.
The secondary phasor
diagram is:
----------------------- Page 45-----------------------
Vad=V2T
I2T = 23 A
I2M = 11.5 A
Vbc=V2M
I
23
Teaser primary current: I A 1.155 2T 1.155
13.28A. This current is in the same
a
2
direction as the teaser secondary current, i.e. vertically upwards with
respect to the phasor
diagram.
1 I
To find out I B from the relation I B I A 2M ,
we need to construct the phasor diagram
2 a
involving I A and I 2M .
I
A From the phasor diagram,
1 2 I 2
M 2
I I
B A
2
a
2 2
I2M or, I 13.28 11.5
B
a I2M 2
2
or, I B 8.784A
-I
A
2 IB
1 I
To find out I C from the relation I C I A 2M ,
we need to construct the phasor diagram
2 a
involving I A and I 2M .
I
A
2 2
13.28 11.5
or, I B
2 2
or, I B 8.784A
Example: A set of Scott connected transformers is supplying two single phase loa
ds at 100 V.
Load across teaser secondary is 350 kW at unity power factor, and th
e load across main
secondary is 250 kW at 0.8 power factor lagging. For input three-phase line volt
age of 6600 V,
calculate primary line currents. Neglect magnetizing current and leakage impedan
ce drops.
Solution:
3
350 10
Load current in teaser transformer secondary I 2T 3
500A at unity pf
100 1
i.e. I 3500A , in
the same direction as V
2T
ad
3
250 10
Load current in main transformer secondary I 2M 3
125A at 0.8 pf (lag)
100 0.8
i.e.
1 0
I 3125 cos
0.8 3125 36.9
2M
0
i.e. lagging V b
y 36.9 .
bc
Vad = 100 V
Thus, the secondary sid
e voltage and current phasor
diagram can be drawn as:
0
I2T = 3500 0 A
T
V 6600
Turns ratio a 1 1
66
T
V 100
2
2
I
A
0 0 0
In the phasor diagram, B
90 36.9 53.1
From the phasor diagram
,
2 2
1 I 2M
I 2M 1
I I 2
I cos
B A
A B
2 a
a 2
2
2
36.90 61.25 3125
3125 61.25 0
or, I B
cos53.1
2 66
66 2
B I2M
a or, I B 70.15A
-I
A
2 I
2M
IB
1 I
To find out I C from the relation I C I A 2M , we
need to construct the phasor diagram
2 a
involving I A and I 2M .
I
A
In the phasor dia
gram,
0
0 0 0
180 (90
36.9 ) 126.9
C
I2M
a
From the phasor
diagram,
2
2
C 1 I 2M
I 2M 1
I I
2 I cos
C A
A C
IC 36.90 2 a
a 2
or,
2
2
61.25 312
5 3125 61.25 0
I
2 cos126.9
-I C
A I2M 2 6
6 66 2
2
or, I C 37.9 A
Thus, the supply line currents are: I = 61.25 A, I = 70.15 A, and I = 37.9
A
A B
C
Figure 8.89 3-phase rectifier (a) schematic arrangement, (b) 3-phase AC input,
(c) rectified DC
output showing ripples
Transformers for 3-phase to 6-phase conversion or even 3-phase to 12-phase conve
rsion are thus
widely used for such applications. More number of phases in the input AC side
also reduces
harmonics in the alternating current.
(a)
(b)
Figure 8.91 (a) Primary coils (b) secondary coils
As indicated in Figure 8.90, while making 3-phase connection delta connection in
primary, A1-
B2, B1-C2, and C1-A2 are connected together and the three terminals A2, B2, C2 a
re taken out
of transformer where the 3-phase input AC is given. On the secondary
side, a1, b1, c1 are
connected together as the first secondary star with neutral point marked as n1.
The reverse star in
----------------------- Page 50-----------------------
secondary is made by connecting a4, b4, c4 together as the second neutral point
n2. The six free
terminals a2, b2, c2, and a3, b3, c3 are connected to the 6-phase load terminals
as shown in Fig.
2. Winding diagram of the primary delta side is shown in Figure 8.92(a) while th
ose for the first
secondary star and the second secondary reverse star are shown in Fig
ure 8.92(b) and (c)
respectively.
(a)
(b)
(c)
Figure 8.92 Winding connection diagram of delta double-star connection, (a) pri
mary delta (b)
secondary star (c) secondary reverse star
In the phasor diagram, the primary side voltage phasors A1A2, B1B2 and C1C2 are
drawn as
0
shown in Figure 8.93(a). As usual for three phase system, these are the phasors
displaced 120
from each other. Similarly in the secondary side voltage phasors a1a2, b1b2 and
c1c2 are drawn
as the first secondary star in Figure 8.93(b). The second secondary s
tar (reversed star) with
phasors a3a4, b3b4, and c3c4 are shown in Figure 8.93(c). Observe that a1a2 & a3
a4 are parallel
to A1A2; b1b2 & b3b4 are parallel to B1B2; and c1c2 & c3c4 are parallel to C1C2.
Phasor diagram can be easily drawn based on the winding connection diagram of F
igure 8.92
simply by replacing the winding coils with arrow headed straight lines (phasors)
.
----------------------- Page 51-----------------------
(a) (b)
(c)
Figure 8.93 Phasor diagram of delta double-star connection, (a) primary delta (b
) secondary star
(c) secondary reverse star
The six secondary terminals a2, c3, b2, a3, c2, b3 are connected to the 6-phase
load terminals 1,
2, 3, 4, 5, and 6 respectively as shown in Figure 8.90. If the two secondary neu
trals n1, and n2
are joined together to form the single neutral point n, then a true 6-phase volt
age is obtained at
0
the six secondary terminals. In this way, six equal voltages with 60
phase displacement with
respect to each other can be obtained. In the case of six phase rectifier, the n
eutral point formed
by the coils serves as the neutral point of the DC supply from the rectifier. It
is interesting to note
that in case of such a double-star connection, the secondary line to line volta
ges (between two
consecutive line terminals) are same as the individual secondary phase (line to
neutral) voltages.
Winding connection and phasor diagram, of the complete 6-phase winding is shown
in Figure
8.94(a) and (b) respectively.
(a)
(b)
Figure 8.94 Six phase secondary double star connection (a) winding con
nection (b) phasor
diagram
To mark the six output terminals, start from a2 in Fig. 6 and mark it as 1. Then
move cyclically
clockwise to mark c3 as 2, b2 as 3, a3 as 4, c2 as 5 and finally b3 as 6.
----------------------- Page 52-----------------------
It is worth noting here that the primary can also be connected as star, but delt
a connection in
primary is generally preferred because of the triple frequency harmonics of volt
ages which are
introduced in star-star connection.
2. Six phase Star Connection
In six-phase star connection, either three single phase transformers, or even a
single unit of three
phase transformer can be used to convert 3-phase signal to 6-phase. In the three
secondary coils,
there must be provision for center taps. The primary can be either connected as
star or delta. Six
phase signals are obtained from the six secondary terminals with the
three center taps being
joined together as the neutral as shown in schematic diagram of Figure 8.95.
Figure 8.95 Schematic diagram of 3-phase to 6-phase conversion by six phase star
connection
Winding connection and phasor diagrams are shown in Figure 8.96 and Figure 8.97
respectively.
Note that in this case, it is not necessary to have two separate secondary coil
s on each phase,
only a tap point at 50% position is sufficient.
(a)
(b)
Figure 8.96 Winding connection for six-phase star connection with neutr
al (a) primary (b)
secondary
----------------------- Page 53-----------------------
(a)
(b)
Figure 8.97 Phasor diagram for six-phase star connection with neutral (a) primar
y (b) secondary
The six secondary terminals a2, c1, b2, a1, c2, b1 are connected to the 6-phase
load terminals 1,
2, 3, 4, 5, and 6 respectively as shown in Figure 8.95. In this case also the li
ne to line voltages
between secondary terminals (say a1-b2) are same as the line to neutral voltages
(say a1-n).
3. Diametrical Connection
In this type of connection for converting 3-phase to 6-phase, it is not necessar
y to have center tap
points on the secondary coils. However, due to absence of the neutral in the sec
ondary, the six
phase output can be used for rectifiers. In this connection also, the primary c
an be connected in
either star or delta, but as usual delta is preferred in order to s
uppress harmonics. The six
secondary outputs are obtained from the six secondary terminals as sho
wn in the schematic
diagram of Figure 8.98. When there is no need for the secondary neut
ral, such a diametrical
connection is often the cheapest.
(a)
(b)
Figure 8.99 Winding connection for six-phase diametrical connection (a) primary
(b) secondary
(a)
(b)
Figure 8.100 Phasor diagram for six-phase diametrical connection (a) primary (b)
secondary
0
To achieve proper phasor relationships among the six output voltages (
60 apart), the six
secondary terminals a2, c1, b2, a1, c2, b1 need to be connected to the six load
terminals 1, 2, 3,
4, 5, and 6 respectively as shown in Figure 8.98. In this case, however, the lin
e to line voltages
between secondary terminals (say a1-b2) are half of the voltage across each seco
ndary phase coil
(say a1-a2).
4. Double delta connection
In this type of connection also, three identical single phase transfor
mers are used, each
transformer having one primary and two equal sections of secondary win
dings. The six half
sections of the secondary windings are used to make two deltas. One delta is mad
e by normal
connection, i.e. start of phase a (a1) connected to finish of phase b (b2), then
start of phase b (b1)
connected to finish of phase c(c2) and finally, start of phase c (c1) connected
to finish of phase a
(a2). The other set of terminals a3a4, b3b4, and c3c4 are also connected to form
a delta, but in an
opposite manner, i.e. finish of phase a (a4) connected to start of phase b (b3)
, finish of phase b
(b4) connected to start of phase c (c3), finish of phase c (c4) connected to sta
rt of phase a (a3).
Note that since no neutral is available on the double-delta six phase secondary,
this connection is
----------------------- Page 55-----------------------
not suitable for rectifier circuits. Six output terminals are taken out from the
three terminals of
the two deltas as shown in the schematic diagram of Figure 8.101. One set of th
ree outputs are
taken from a2, b2, and c2; and the three remaining secondary terminals are taken
out from a3,
b3, and c3.
(a)
(b)
Figure 8.102 (a) Primary coils (b) secondary coils
The primary may be connected for star or delta. Since the two deltas in the seco
ndary provide
closed path for the third harmonic current to be arrested, the primary winding f
or this scheme can
be connected in star. Let the terminals A1, B1, and C1 of primary are connected
as the star point
----------------------- Page 56-----------------------
and three phase supply is given to terminals A2, B2, and C2. Winding connection
diagrams are
shown in Figure 8.103. In the first delta on the secondary side, shown in Figur
e 8.103(b), the
outputs are taken from terminals a2, b2, and c2. In the second secondary delta,
the three output
terminals are taken out from a3, b3, and c3 as shown in Figure 8.103(c).
(a)
(b) (c)
Figure 8.103 Winding scheme for double delta connection (a) primary star (b), (c
) two secondary
deltas
Phasor diagram of the two secondary deltas when overlapped over each other can b
e shown to
take the form as shown in Figure 8.104. Note that the two individual
deltas are electrically
isolated from each other, and get interconnected only through the output 6-phase
load.
Figure 8.104 Double delta connection phasor diagram for obtaining 6-phase voltag
e
The six-phase voltages are available at the six output terminals a2, c3, b2, a3,
c2, and b3 which
are connected to the six load terminals 1, 2, 3, 4, 5, and 6 respectively as sho
wn in Figure 8.101.
0
Phasor relationships (60 apart) between the individual voltages in the 6-phase
secondary can be
understood by considering the six terminal voltages with respect to the virtual
neutral (common
centroid of the two delta triangles) of the deltas as shown in Figure 8.105.
----------------------- Page 57-----------------------
Consider the equilateral triangle a2-n-c3, where all the three sides ar
e of equal length
a2n=nc3=c3a2=V .
L
0
In the right angled triangle a2-p-c3, the base a2p=V cos30 = 0.866 V .
L
L
Note that the point p bisects the line a1a2. Thus, a1a2 = 2xa2p = 2x0.866V = 1.7
32V
L L
Thus, voltage across the half secondary coils is 1.732 ( 3) times the line to line
voltage.
Note that a1a4 = a1n+na4 = a2n+nc3 = 2x a2c3 = 2V
L
Thus, voltage across the full secondary coil in one phase is 2 times the line to
line voltage.
Figure 8.107 Winding diagram of ring connection for 3-phase to 6-phase conversio
n
Figure 8.108 Phasor diagram of ring connection for 3-phase to 6-phase conversion
While connecting the six secondary coils in ring form, care should be taken that
the terminals a1,
0
b1, c1 are 120 apart with proper phase sequence (i.e. b1 lagging a1 and so on)
. Also, extreme
ends of the same phase, i.e. a1-a4, b1-b4, and c1-c4 must be diametrically oppos
ite to each other.
These can be confirmed from either Figure 8.107 or Figure 8.108. How the six te
rminals of the
ring are going to be connected to the load is determined by passing clockwise st
arting from any
one terminal and sequentially putting the numbers. As noted from Figure 8.108, i
f c1b3 terminal
is to be connected to terminal number 1 of the load, then moving clockwise, the
a2b4 is to be
connected to terminal number 2 of the six phase load and so on. Thus, as shown i
n the schematic
diagram, the six output terminals c1, b4, a1, c4, b1, and a4 are connected to te
rminal 1, 2, 3, 4, 5,
and 6 of the six phase load respectively as shown in Figure 8.106.
The clue is to draw either the winding diagram (Figure 8.107) or the phasor di
agram (Figure
8.108) based on the coil orientations (Figure 8.102); identify how the six sec
ondary coils are to
be interconnected and accordingly join them to complete the schematic diagram
of Figure
8.106.
----------------------- Page 60-----------------------
8.7.2 3-phase to 12-phase conversion
Though ripple contents in the rectified output will be less when 12
phases are used, the
connections become more complicated and costly. Thus use of 12-phase A
C for rectification
purpose is restricted to large installations only. In a 12-phase AC signal, the
voltages are of the
0 0
same magnitude, but are displaced from each other by 360 /12 = 30 .
The basic connection principle for converting 3-phase to 12-phase is however sim
ple. First it is
necessary to convert 3-phase signal to 6-phase, and then connect two
such 6-phase signal
properly to obtain the 12-phase output. There are various schemes, out of which
only some will
be discussed in detail in this section.
1. Double-star pair connection (or star-delta/double star connection)
In this scheme, two three phase transformers are used. In both of them, the seco
ndary coils have
center taps. The first transformer primary is connected in delta, while its seco
ndary is connected
as double-star to produce a 6-phase signal (refer Figure 8.95 to Figu
re 8.97). The second
transformer primary is connected in star, while its secondary is once again conn
ected as double-
star to produce another 6-phase signal. The two primaries are connected together
to the same 3-
phase supply system. The two secondaries together now can produce a 1
2-phase signal. The
scheme is shown by the block diagram of Figure 8.109.
Figure 8.110 Schematic diagram of 3-phase to 6-phase conversion by six phase sta
r connection
Phasor diagrams of the primary delta and secondary 6-phase double star
are shown in Figure
8.111(a) and (b) respectively. Considering a supply phase sequence of
A-B-C, the respective
positions of primary delta phasors are assumed to be oriented in the positions a
s shown in Figure
8.111(a). Note the positions of corresponding phasors in the secondary
side. The secondary
phasors n1-a2 and n1-a1 are drawn parallel to the corresponding primary phasor A
1-A2, since
the primary and secondary coils of same phase are always put on the
same limb. In similar
manner, the primary and secondary phasors of B phase are also drawn parallel to
each other and
so are the phasors for C phase.
(a)
(b)
Figure 8.111 Phasor diagram of delta/double-star connection (a) primary (b) seco
ndary
Connection scheme for transformer 2 for which the primary is connected as star a
nd secondary
as double star is shown in Figure 8.112.
----------------------- Page 62-----------------------
Figure 8.112 Schematic diagram of 3-phase to 6-phase conversion by six phase sta
r connection
Phasor diagrams of the primary star and secondary 6-phase double star
are shown in Figure
8.113(a) and (b) respectively. For the same phase sequence A-B-C, the primary st
ar phasors are
oriented as shown in Figure 8.113(a). Note the positions of corresponding phasor
s in the double-
star connected secondary side. The secondary phasors n2-a2 and n2-a1 are once agai
n drawn
parallel to the corresponding primary phasor A1-A2 , since the primary and seconda
ry coils of
same phase are always put on the same limb. In similar manner, the
primary and secondary
phasors of B phase are also drawn parallel to each other and so are the phasors
for C phase.
(a)
(b)
Figure 8.113 Phasor diagram of star/double-star connection (a) primary (b) secon
dary
Considering a supply phase sequence of A-B-C, the respective positions of primar
y star phasors
will be oriented in the positions as shown in Figure 8.113(a). Compar
e the positions of the
terminals A2, B2, and C2 of the primary star of transformer 2 in Figur
e 8.111(a) with the
corresponding terminals A2, B2, and C2 of the primary delta of Transf
ormer 1 in Figure
8.113(a). Since the corresponding primary line terminals of both the t
wo transformers are
connected to the same 3-phase supply lines, the positions of A2, B2, and C2 will be
same as
A2, B2, and C2 respectively. The situation can be visualized more effectively w
ith Figure 8.114
where the two primary phasor diagrams, delta for transformer 1, and star for tra
nsformer 2 are
assumed to be superimposed one over the other.
----------------------- Page 63-----------------------
(a)
(b)
Figure 8.117 Phasor diagram of star/double-delta connection (a) primary (b) seco
ndary
Phasor diagram of the primary delta of transformer 2 and the two sec
ondary deltas when
overlapped over each other are shown in Figure 8.118 (a) and Figure 8.118(b) re
spectively. In
this case also, note that a1-a2, and a3-a4 phasors in secondary deltas are p
arallel with A1-A2
phasor of primary. Similar orientations of the phasors are also valid for other
two phases.
(a)
(b)
Figure 8.118 Phasor diagram of delta/double-delta connection (a) primary (b) sec
ondary
Comparing the primary phasors of Figure 8.117(a) and Figure 8.118(a), it is seen
that position of
the terminals A2 and A2 are exactly the same, even though one is star connected a
nd the other is
delta connected. Similarly, positions of B2 and B2 are same, and positions of C2
and C2 are
also same. This is because both the two primaries are supplied from the same 3-p
hase source as
shown in Figure 8.116. Thus, while the two primary phasors can be assumed to be
overlapping
with each other with output terminals A2, B2, and C2 of transformer 1 matching p
erfectly with
the terminals A2, B2, and C2 respectively of transformer 2, then the two secondary
double-
deltas could also be made to overlap as shown in Figure 8.119. The
double delta of Figure
8.117(b) has been redrawn with dotted line so as to enhance visual appearance of
the double-
delta pair in Figure 8.119. The virtual neutral point n is also marked in Figure
8.119.