You are on page 1of 4

F3-data via VFx-module Peak level for the adjustment in PowerSys

FSK-Channel ACN nom. level No. of FSK channels Menu: Configuration/Services/Service x


50 Bd NB 0.9 -23.5
100 Bd NB 1.1 -21.5 set input and output level to ...
200 Bd NB 1.6 -18.5
50 Bd 1.0 -22.5
100 Bd 1.4 -19.5 The input resp. output level of the Vfx port
200 Bd 2.0 -16.5 has to be adjusted to this peak level. If
600 Bd 2.8 -13.5 several VFx ports are used for data
1200 Bd 4.0 -10.5 transmission, the peak level has to be
2400 Bd 5.7 -7.5 calculated and adjusted for each port
separate.
Bandwidth data band
If the number of FSK channels is
not known, please enter here the
bandwidth of the data band in Hz
Transmission of protection signals
(ext. SWT 3000) in the data band
No

Adjusted with Configuration/Services/Service x

ACN to be adjusted in PowerSys


Menu: Adjustments/Tx-Levelling/Service x F3 data
0.0 via VFx
set ACN for this service to ... #NAME?

In case of feeding external modems via the


VFx ports the calculated ACN for the data
channels has to be entered in this form. If
several VFx ports are used for data
transmission, the ACN has to be calculated
and adjusted for each port separate.The
corresponding Tx levels CSP are calculated
from the system.
corresponding Tx levels CSP are calculated
from the system.

You might also like