You are on page 1of 12

SWT 3000 Equipment Manual

Chapter 7: The Alarm Modules ALRS and ALR

Function of the ALRS 3

Jumper settings ALRS 5

Pin assignment ALRS 6

Function of the ALR 7

Jumper settings ALR 9

Pin assignment ALR 10


ALRS and ALR Module SWT 3000 Equipment Manual

Table of Contents:

The ALRS module---------------------------------------------------------------------------------------------------------------------- 3


Function of the ALRS-------------------------------------------------------------------------------------------------------------- 3
Input and outputs------------------------------------------------------------------------------------------------------------------- 3
Operating the signaling relay ---------------------------------------------------------------------------------------------------- 3
Binary input clock synchronization: -------------------------------------------------------------------------------------------- 3
Supply voltages-------------------------------------------------------------------------------------------------------------------- 4
Jumper settings -------------------------------------------------------------------------------------------------------------------- 5
Pin assignment X1 of the ALRS ------------------------------------------------------------------------------------------------ 6
The ALR module ----------------------------------------------------------------------------------------------------------------------- 7
Block diagram --------------------------------------------------------------------------------------------------------------------- 7
Binary inputs-------------------------------------------------------------------------------------------------------------------- 8
Relay outputs ------------------------------------------------------------------------------------------------------------------- 8
Visual Indication --------------------------------------------------------------------------------------------------------------- 8
Test switch S1 ------------------------------------------------------------------------------------------------------------------ 8
ALR jumper settings----------------------------------------------------------------------------------------------------------- 9
Pin assignment X1 of the ALR -------------------------------------------------------------------------------------------------10
Index: --------------------------------------------------------------------------------------------------------------------------------11
Appendix: ---------------------------------------------------------------------------------------------------------------------------12
List of figures ---------------------------------------------------------------------------------------------------------------------12
List of tables ----------------------------------------------------------------------------------------------------------------------12

Page - 2 Edition p3_3_2x 08/09 SIEMENS AG 2008


SWT 3000 Equipment Manual ALRS and ALR Module

The ALRS module

Function of the ALRS


The alarm module ALRS is the interface between the alarm and signaling point circuits of the user
and the PU3 on the SWT 3000 unit. The ALRS is installed on a European standard-sized card to
the slide-in unit in an ES902 frame.

Input and outputs


The module has 3 relay outputs and 1 binary input.
Outputs:
c General alarm (GALR)
d Pre- alarm (NDALR)
e Receiver alarm (EALR)

Operating the signaling relay

The signaling relay is operated by the PU3 module at active low level, i.e. an alarm is applied
when the input level is 0V. The relay contacts are in the normal position (i.e. released) in the event
of an alarm so that the alarm is triggered even in the event of power failure.
Only 2 connections are brought out from the signaling relay. Using links it is possible to choose
between make and break contacts. The break contact is the default setting supplied.

X1 X1
K1
C15 + 12V X4 X5 X6
GALR

A32

GALR

C30

K2
C14 + 12V X7 X8 X9
NDALR

A28

NDALR

A25

K3
C13 + 12V X10 X11 X12
EALR

A21

EALR

C23

GALR General alarm


NDALR Pre- alarm
EALR Receive alarm

Figure 1: Block diagram of the alarm relay activation and selection of the signaling contacts

Binary input clock synchronization:

SIEMENS AG 2008 Edition p3_3_2x 08/09 Page - 3


ALRS and ALR Module SWT 3000 Equipment Manual

A1

A14 SYNC
SYNC X3 1
2
3 C3

Figure 2: Block diagram of the binary input

The binary input is also active low. Electrical isolation is provided by means of optocouplers. The
operating point is between about 15V (0-15V Off state, 20-250V On) and about 54V (0_50V
Off state, 60-250V On state) settable by a link.

Supply voltages

The ALRS module needs the following supply voltages:


+12V
+5V
In the SWT 3000 unit the power supply is generally interrupted by an inhibit line when a module is
pulled. The ALRS does not have an Inhibit line so that the equipment can also be operated for test
purposes with the module pulled.

Page - 4 Edition p3_3_2x 08/09 SIEMENS AG 2008


SWT 3000 Equipment Manual ALRS and ALR Module

Jumper settings

V7 R17
1
N1 R16
U2 X3 V8
X2 V4 R8
V3
1 R7
U1
N2
K1 K2 K3 X1

X6 X5 X4 X9 X8 X7 X12 X11 X10

Figure 3: Position of the jumper on the ALRS

Table 1: Selection of the operating point for the ALRS input


Input Input voltage 15 V 250V Input voltage 54V 250V
Clock synchronization Link X3 1-2 Link X3 2-3
Table 2: Selection of the relay contacts of the ALRS outputs
Alarm relay Designation Break contact (NC) Make contact (NO)
K1 General alarm X4 - X5 X5 - X6
K2 Pre- alarm X7 - X8 X8 - X9
K3 Receiver alarm X10 - X11 X11 - X12

SIEMENS AG 2008 Edition p3_3_2x 08/09 Page - 5


ALRS and ALR Module SWT 3000 Equipment Manual

Pin assignment X1 of the ALRS


Table 3: Pin assignment of the ALRS module

PIN Signalname PIN Signalname PIN Signalname


A1 Usync Input a B1 C1
A2 B2 C2
A3 B3 C3 Usync Input b
A4 B4 C4
A5 B5 C5
A6 B6 C6
A7 B7 C7
A8 B8 C8
A9 B9 C9
A10 B10 C10
A11 B11 C11
A12 GNDS B12 GNDS C12 GNDS
A13 B13 C13 ALA1_OUT_L
A14 Usync to PU3 B14 C14 ALA2_OUT_L
A15 B15 C15 ALA3_OUT_L
A16 P5V B16 P5V C16 P5V
A17 GND B17 GND C17 GND
A18 P12V B18 P12V C18 P12V
A19 B19 C19
A20 B20 C20
A21 ALA1_A (RX_Alarm) B21 C21
A22 B22 C22
A23 B23 C23 ALA1_B (RXALR)
A24 B24 C24
A25 ALA2_B (NU_Alarm) B25 C25
A26 B26 C26
A27 B27 C27
A28 ALA2_A (NU_Alarm) B28 C28
A29 B29 C29
A30 B30 C30 ALA3_B (Gen. Alarm)
A31 B31 C31
A32 ALA3_A (Gen. Alarm) B32 C32

Input/output signals

Page - 6 Edition p3_3_2x 08/09 SIEMENS AG 2008


SWT 3000 Equipment Manual ALRS and ALR Module

The ALR module


The ALR module provides as well 3 alarm relays like the ALRS module. The difference to the
ALRS module is in the two binary inputs. The input voltage is adjustable to 24V, 48/60V, 110V
resp. 250V DC. The binary input 1 is used for the clock synchronization of the iSWT. Either an ex-
ternal synch. pulse is connected or the input is alternatively configurable as an input for entering
IRIG-B signals. Additionally the ALR module provides a LED for visual indication of the state for
each binary input and for each alarm output. The LED are visible after removal of the front panel.
For more details refer to chapter 4 commissioning.

Block diagram

X16 X17
24V
IRIG-B 12V
H6
+5V
IRIG-B-Test (S1/4)
5V +12V

250V

i n t e r f a c e s
BI1_A X14 X15
A1
110V
BI1
i n t e r f a c e s

BI1_IN_L
(USYNC) BI1_B 48/60V
C3 H5
BI1-Test (S1/2)
24V

250V
BI2_A
A5
BI2 BI2_B
110V
BI2_IN_L
A8 48/60V
BI2-Test (S1/1) H4
24V

K1
X7
A21 ALA1_A X6

ALA1 X5
ALA1_OUT_L
(EALR)
ALA1_B H3

s y s t e m
C23
u s e r

K2
X10
ALA2_A
A28 X9
ALA2 X8
ALA2_OUT_L
(SALR/NDALR)
H2
ALA2_B
A25

K3
X13
A32 ALA3_A X12

ALA3 X11
(GENALR) ALA3_OUT_L
ALA3_B H1
C30

ALR_INFO.vsd/Sheet-1
2008-03-14/DOE

Figure 4: ALR Block diagram

SIEMENS AG 2008 Edition p3_3_2x 08/09 Page - 7


ALRS and ALR Module SWT 3000 Equipment Manual

Binary inputs

The module ALR provides two electrically isolated inputs BI1 and BI2 with selectable input voltage
levels. As the circuits for the binary inputs comprise rectification, differential DC input signals of ei-
ther polarity can be connected. The output signals of the circuits have TTL level. Binary input BI1 is
alternatively configurable as an input for entering IRIG-B signals.

Relay outputs

The alarm module comprises as well three alarm outputs, switched by relay (K1 K3). The three
relays provide change over contacts. In the standard setup the break contacts (NC) are used.

BI1/USYNC BI1/USYNC
X17 X16
IRIG B
5 6
X2 9 7 5 3 1 X14 X15
X18 3 4 FAST 10 8 6 4 2
5 31 1 2 SLOW

250V
Park

24V

110V
48/60V
H6 IRIG-B X3
6 42
5V
12V
24V

BI2
5 6
H5 BI1 X19 3 4 FAST BI2
1 2 SLOW 9 7531
X4 10 8 6 4 2

250V
Park

24V

110V
48/60V
H4 BI2

1 Test BI2
S1 Test BI1
n.u.
Test IRIG-B ALA1
X7 X6 X5
K1
H3 ALA1 ALA2
X10 X8
H2 ALA2 K2
X9
ALA3
H1 ALA3 X12
K3

X13 X11

Figure 5: Display and setting elements on the ALR module

Visual Indication

The module ALR provides a LED for visual indication of the state for each binary input and for
each alarm output. They are visible after removal of the front panel. The significations are shown in
the table below:
Table 4: ALR indication
LED Indication
H6 IRIG-B Input energized
H5 Binary Input 1 energized
H4 Binary input 2 energized
H3 Alarm output 1 activated
H2 Alarm output 2 activated
H1 Alarm output 3 activated

Test switch S1

For test purposes the module ALR provides a switch for each of the binary input circuits and for
the IRIG-B circuit. Closing a switch sets the output of the assigned circuit to the active state.
Table 5: Functions of the ALR test switch
Switch Function
S1.1 Binary Input 2 test
S1.2 Binary input 1 test
S1.3 n.u.
S1.4 IRIG-B test

Page - 8 Edition p3_3_2x 08/09 SIEMENS AG 2008


SWT 3000 Equipment Manual ALRS and ALR Module

ALR jumper settings

The function of the ALR jumpers is shown in the table below.


Table 6: Setting options for the ALR module
Jumpers
X2 X3 X4 X5 X13 X14 X17
Binary Input 1

250V X2 7 / 8 *) open --- --- X14 X15 *)


110V X2 1 / 2 open --- --- X14 X15
48V / X2 3 / 4 open --- --- X14 X15
60V
24V X2 5 / 6 open --- --- X14 X15
fast X18 / 3 4
Input behaviour
slow X18 / 1 - 2
IRIG-B

24V open X3 1 / 2 --- --- X16 X17


12V open X3 3 / 4 --- --- X16 X17
5V open X3 5 / 6 --- --- X16 X17
Binary Input 2
*)
250V --- --- X4 7 / 8 --- ---
110V --- --- X4 1 / 2 --- ---
48V / --- --- X4 3 / 4 --- ---
60V
24V --- --- X4 5 / 6 --- ---
fast X19 / 3 4
Input behaviour
slow X19 / 1 - 2
Alarm Output 1 Relay K1

NC --- --- --- X5 X6 *) ---


NO --- --- --- X6 X7 ---
Alarm Output 2 Relay K2

NC --- --- --- X8 X9 *) ---


NO --- --- --- X9 X10 ---
Alarm Output 3 Relay K3

NC --- --- --- X11 X12 *) ---


NO --- --- --- X12 X13 ---
NC Break contact
NO Make contact
*) Default setting

SIEMENS AG 2008 Edition p3_3_2x 08/09 Page - 9


ALRS and ALR Module SWT 3000 Equipment Manual

Pin assignment X1 of the ALR


Table 7: Pin assignment of the ALR

PIN Signalname PIN Signalname PIN Signalname


A1 BI1_A B1 C1
A2 B2 C2
A3 B3 C3 BI1_B
A4 B4 C4
A5 BI2_A B5 C5
A6 B6 C6
A7 B7 C7
A8 BI2_B B8 C8
A9 B9 C9
A10 B10 C10
A11 B11 C11
A12 FGND B12 FGND C12 FGND
A13 B13 C13 ALA1_OUT_L
A14 BI1_IN_L B14 C14 ALA2_OUT_L
A15 BI2_IN_L B15 C15 ALA3_OUT_L
A16 P5V B16 P5V C16 P5V
A17 GND B17 GND C17 GND
A18 P12V B18 P12V C18 P12V
A19 B19 C19
A20 B20 C20
A21 ALA1_A B21 C21
A22 B22 C22
A23 B23 C23 ALA1_B
A24 B24 C24
A25 ALA2_B B25 C25
A26 B26 C26
A27 B27 C27
A28 ALA2_A B28 C28
A29 B29 C29
A30 B30 C30 ALA3_B
A31 B31 C31
A32 ALA3_A B32 C32

Page - 10 Edition p3_3_2x 08/09 SIEMENS AG 2008


SWT 3000 Equipment Manual ALRS and ALR Module

Index:

E O

EALR 3 Operating point 4


Outputs 3
G
P
GALR 3
General alarm 3 Pin assignment
ALR 10
ALRS 6
J Pre- alarm 3
Jumper settings
ALR 9 R
ALRS 5
Receiver alarm 3
Relay contacts 3
N

NDALR 3 S

Signaling relay 3
Supply voltages 4

SIEMENS AG 2008 Edition p3_3_2x 08/09 Page - 11


ALRS and ALR Module SWT 3000 Equipment Manual

Appendix:

List of figures
Figure 1: Block diagram of the alarm relay activation and selection of the signaling contacts ------------------------ 3
Figure 2: Block diagram of the binary input ---------------------------------------------------------------------------------- 4
Figure 3: Position of the jumper on the ALRS--------------------------------------------------------------------------------- 5
Figure 4: ALR Block diagram --------------------------------------------------------------------------------------------------- 7
Figure 5: Display and setting elements on the ALR module ----------------------------------------------------------------- 8

List of tables
Table 1: Selection of the operating point for the ALRS input ----------------------------------------------------------------- 5
Table 2: Selection of the relay contacts of the ALRS outputs ----------------------------------------------------------------- 5
Table 3: Pin assignment of the ALRS module ----------------------------------------------------------------------------------- 6
Table 4: ALR indication------------------------------------------------------------------------------------------------------------ 8
Table 5: Functions of the ALR test switch --------------------------------------------------------------------------------------- 8
Table 6: Setting options for the ALR module ------------------------------------------------------------------------------------ 9
Table 7: Pin assignment of the ALR ---------------------------------------------------------------------------------------------10

Page - 12 Edition p3_3_2x 08/09 SIEMENS AG 2008

You might also like