0 PIPE SIZING CALCULATION

Water Demand per day

Time Taken to fill Storage Tanks


Q = volumetric flow rate
v = flow velocity (m/s)
n=
Pipe size required - ( ( Q x 4 )/ ( v x ))

Proposed Pipe size (internal diameter )

5.0 CALCULATION OF HEAD LOSSES

5.1 Head Loss due to Height Differences


Total Head Loss, z

5.2 Head Loss due to Lenght of Pipe


Length of Pipe from 'meter position' to the Storage tank
(Type of Pipe used is HDPE )
HAZEN WILLIAMS FORMULA
hf = 10.67x Q1.85/C1.85x d4.87
where:

hf = head loss in meters (water) over the length of pipe


L = length of pipe in meters

Q = volumetric flow rate, m3/s (cubic meters per second)


C = pipe roughness coefficient
d = inside pipe diameter, m (meters)

SPAN Table B.7 : Hazen-William Coefficient C for Various


Pipe Materials
Type Of Pipe Hazen-William Coefficient, C
Ductile Iron (cement lined) 100
Steel (cement lined) 100
HDPE/ ABS/ GRP/uPVC 120

Therefore , head loss hf

5.3 Head Loss due to Connections, Bends and Tees


Ks per Nos
Coefficient for Various Pipe Fittings no
90o tee in line 0.4 1
90o tee branch 1.5 0
90o bend 0.5 6
gate valve 0.25 4
Total

Head loss due velocity, hv

5.4 Total Head Loss

Total Head Loss z + hf + hv

Note: Pressure required should be 19.50m


420180.732 litres/day
420.18 m3/day
8.00 hours
0.0145896088 m3/sec
1.0 m/sec

0.136 m
136.27 mm

150 mm
ok !

11.39 m

98.40 m

98.40 m

0.0145896088
m3/sec
120
0.15 m

0.00627 m
Ks

0.4
0
3
1
4.4

Ks v2 / 2g

0.22 m

11.62 m
6.0 DESIGN OF RECTICUATION SYSTEM TAKING INTO FIRE FLOW

Design Flow

Peak Flow = 2.5 x Average Flow


Hydrant Flow = Average Flow + Fire Flow

AVERAGE FLOW + FIRE FLOW

Fire Fighting

For fire fighting the fire flow is taken as 300 gpm or 0.0225 m3/sec.
The design flow adopted in this case is average flow + fire flow
Average flow is 0.015 m3/sec

FRICTION HEAD LOSS CALCULATION USING HAZEN-WILLIAM EQUATION

Friction Loss

The friction loss in pipies shall be calculated using Hazen William Formula

hf = (10.67*L*Q^1.85)/C^1.85*d^4.87)

HYDRANT
LENGTH DIAMETER d
PIPE No. C FLOW
L (m) (m)
Q ( m3/s )
1 to 2 to 3 103.32 0.18 120 0.0240

Totol Head loss due to Fire Flow

Pressure available tapping point 8.28


Pressure available at Hydrant point after losses is 7.610
HEAD-LOSS
(m)

0.670

0.670

m
m OK!
Water Demand Calculation

BASED ON SPAN
GUIDELINES
Area (m2)

Ground Floor 262


First Floor 262
Second Floor 262
Total (Required)
Total (Provided)
Estimated Water Demand Total Water Demand
Rate
(Liters)
1000 liters/100 m 2 2620
1000 liters/100 m2 1522
1000 liters/100 m2 1522
equired) 5664
rovided) 6000 (1585gall)