Conductor Resistance, Reactance, Impedance

2 2
Average Characteristics of Application Notes Z X R
600 V Conductors Resistance and reactance are For busway impedance data, see
i
phase-to-neutral values, based on Tab 21 of this catalog
Ohms per 1000 ft (305 m)
60 Hz AC, three-phase, four-wire For PF (power factor) values less ii
The tables below are average charac- distribution, in ohms per 100 ft than 1.0, the effective impedance Ze
teristics based on data from IEEE (30 m) of circuit length (not total is calculated from
Standard 141-1993. Values from
different sources vary because of
conductor lengths) Z e R PF X sin (arc cos PF) 1
Based upon conductivity of 100% for
operating temperatures, wire For copper cable data, resistance
copper, 61% for aluminum
stranding, insulation materials based on tinned copper at 60 Hz;
and thicknesses, overall diameters, Based on conductor temperatures
600 V and 5 kV nonshielded cable
2
random lay of multiple conductors of 75 C. Reactance values will
based on varnished cambric insula-
in conduit, conductor spacing, and have negligible variation with
tion; 5 kV shielded and 15 kV cable 3
other divergences in materials, test temperature. Resistance of both
based on neoprene insulation
conditions and calculation methods. copper and aluminum conductors
will be approximately 5% lower For aluminum cable data, cable is
These tables are for 600 V 5 kV and
15 kV conductors, at an average at 60 C or 5% higher at 90 C. cross-linked polyethylene insulated 4
temperature of 75 C. Other parame- Data shown in tables may be
ters are listed in the notes. For used without significant error
medium voltage cables, differences between 60 and 90 C 5
among manufacturers are consider- For interlocked armored cable,
ably greater because of the wider vari- use magnetic conduit data for
ations in insulation materials and steel armor and non-magnetic
6
thicknesses, shielding, jacketing, over- conduit data for aluminum armor
all diameters, and the like. Therefore, 7
data for medium voltage cables should
be obtained from the manufacturer
of the cable to be used. 8
Table 1.5-17. 60 Hz Impedance Data for Three-Phase Copper Cable Circuits, in Approximate Ohms per 1000 ft (305 m) at 75 C (a) Three Single Conductors
Wire Size, In Magnetic Duct In Non-Magnetic Duct
9
AWG or 600 V and 5 kV Non-Shielded 5 kV Shielded and 15 kV 600 V and 5 kV Non-Shielded 5 kV Shielded and 15 kV
kcmil
R X Z R X Z R X Z R X Z
10
8 0.811 0.0754 0.814 0.811 0.0860 0.816 0.811 0.0603 0.813 0.811 0.0688 0.814
8 (solid) 0.786 0.0754 0.790 0.786 0.0860 0.791 0.786 0.0603 0.788 0.786 0.0688 0.789
6 0.510 0.0685 0.515 0.510 0.0796 0.516 0.510 0.0548 0.513 0.510 0.0636 0.514 11
6 (solid) 0.496 0.0685 0.501 0.496 0.0796 0.502 0.496 0.0548 0.499 0.496 0.0636 0.500
4 0.321 0.0632 0.327 0.321 0.0742 0.329 0.321 0.0506 0.325 0.321 0.0594 0.326
4 (solid)
2
0.312
0.202
0.0632
0.0585
0.318
0.210
0.312
0.202
0.0742
0.0685
0.321
0.214
0.312
0.202
0.0506
0.0467
0.316
0.207
0.312
0.202
0.0594
0.0547
0.318
0.209
12
1 0.160 0.0570 0.170 0.160 0.0675 0.174 0.160 0.0456 0.166 0.160 0.0540 0.169
1/0 0.128 0.0540 0.139 0.128 0.0635 0.143 0.127
2/0 0.102 0.0533 0.115 0.103 0.0630 0.121 0.101
0.0432
0.0426
0.134
0.110
0.128
0.102
0.0507
0.0504
0.138
0.114
13
3/0 0.0805 0.0519 0.0958 0.0814 0.0605 0.101 0.0766 0.0415 0.0871 0.0805 0.0484 0.0939
4/0 0.0640 0.0497 0.0810 0.0650 0.0583 0.0929 0.0633 0.0398 0.0748 0.0640 0.0466 0.0792
250 0.0552 0.0495 0.0742 0.0557 0.0570 0.0797 0.0541 0.0396 0.0670 0.0547 0.0456 0.0712 14
300 0.0464 0.0493 0.0677 0.0473 0.0564 0.0736 0.0451 0.0394 0.0599 0.0460 0.0451 0.0644
350 0.0378 0.0491 0.0617 0.0386 0.0562 0.0681 0.0368 0.0393 0.0536 0.0375 0.0450 0.0586
400 0.0356 0.0490 0.0606 0.0362 0.0548 0.0657 0.0342 0.0392 0.0520 0.0348 0.0438 0.0559 15
450 0.0322 0.0480 0.0578 0.0328 0.0538 0.0630 0.0304 0.0384 0.0490 0.0312 0.0430 0.0531
500 0.0294 0.0466 0.0551 0.0300 0.0526 0.0505 0.0276 0.0373 0.0464 0.0284 0.0421 0.0508
600
750
0.0257
0.0216
0.0463
0.0495
0.0530
0.0495
0.0264
0.0223
0.0516
0.0497
0.0580
0.0545
0.0237
0.0194
0.0371
0.0356
0.0440
0.0405
0.0246
0.0203
0.0412
0.0396
0.0479
0.0445
16
Note: More tables on Page 1.5-16.
17

18

19

20

21

CA08104001E For more information, visit: www.eaton.com/consultants


1.5-16 Power Distribution Systems
Reference Data April 2016
Sheet 01 110
Conductor Resistance, Reactance, Impedance

Table 1.5-18. 60 Hz Impedance Data for Three-Phase Copper Cable Circuits, in Approximate Ohms per 1000 ft (305 m) at 75 C (b) Three Conductor Cable
i Wire Size, In Magnetic Duct and Steel Interlocked Armor In Non-Magnetic Duct and Aluminum Interlocked Armor
AWG or 600 V and 5 kV Non-Shielded 5 kV Shielded and 15 kV 600 V and 5 kV Non-Shielded 5 kV Shielded and 15 kV
kcmil
ii R X Z R X Z R X Z R X Z

8 0.811 0.0577 0.813 0.811 0.0658 0.814 0.811 0.0503 0.812 0.811 0.0574 0.813
8 (solid) 0.786 0.0577 0.788 0.786 0.0658 0.789 0.786 0.0503 0.787 0.786 0.0574 0.788
1 6
6 (solid)
0.510
0.496
0.0525
0.0525
0.513
0.499
0.510
0.496
0.0610
0.0610
0.514
0.500
0.510
0.496
0.0457
0.0457
0.512
0.498
0.510
0.496
0.0531
0.0531
0.513
0.499
4 0.321 0.0483 0.325 0.321 0.0568 0.326 0.321 0.0422 0.324 0.321 0.0495 0.325
2 4 (solid)
2
0.312
0.202
0.0483
0.0448
0.316
0.207
0.312
0.202
0.0508
0.0524
0.317
0.209
0.312
0.202
0.0422
0.0390
0.315
0.206
0.312
0.202
0.0495
0.0457
0.316
0.207
1 0.160 0.0436 0.166 0.160 0.0516 0.168 0.160 0.0380 0.164 0.160 0.0450 0.166
1/0 0.128 0.0414 0.135 0.128 0.0486 0.137 0.127 0.0360 0.132 0.128 0.0423 0.135
3 2/0 0.102 0.0407 0.110 0.103 0.0482 0.114 0.101 0.0355 0.107 0.102 0.0420 0.110
3/0 0.0805 0.0397 0.0898 0.0814 0.0463 0.0936 0.0766 0.0346 0.0841 0.0805 0.0403 0.090
4/0 0.0640 0.0381 0.0745 0.0650 0.0446 0.0788 0.0633 0.0332 0.0715 0.0640 0.0389 0.0749
4 250 0.0552 0.0379 0.0670 0.0557 0.0436 0.0707 0.0541 0.0330 0.0634 0.0547 0.0380 0.0666
300 0.0464 0.0377 0.0598 0.0473 0.0431 0.0640 0.0451 0.0329 0.0559 0.0460 0.0376 0.0596
350 0.0378 0.0373 0.0539 0.0386 0.0427 0.0576 0.0368 0.0328 0.0492 0.0375 0.0375 0.0530
5 400 0.0356 0.0371 0.0514 0.0362 0.0415 0.0551 0.0342 0.0327 0.0475 0.0348 0.0366 0.0505
450 0.0322 0.0361 0.0484 0.0328 0.0404 0.0520 0.0304 0.0320 0.0441 0.0312 0.0359 0.0476
500 0.0294 0.0349 0.0456 0.0300 0.0394 0.0495 0.0276 0.0311 0.0416 0.0284 0.0351 0.0453
600 0.0257 0.0343 0.0429 0.0264 0.0382 0.0464 0.0237 0.0309 0.0389 0.0246 0.0344 0.0422
6 750 0.0216 0.0326 0.0391 0.0223 0.0364 0.0427 0.0197 0.0297 0.0355 0.0203 0.0332 0.0389

Table 1.5-19. 60 Hz Impedance Data for Three-Phase Aluminum Cable Circuits, in Approximate Ohms per 1000 Ft (305 m) at 90 C (a) Three Single Conductors
7 Wire Size, In Magnetic Duct In Non-Magnetic Duct
AWG or 600 V and 5 kV Non-Shielded 5 kV Shielded and 15 kV 600 V and 5 kV Non-Shielded 5 kV Shielded and 15 kV
kcmil
8 R X Z R X Z R X Z R X Z

6 0.847 0.053 0.849 0.847 0.042 0.848


4 0.532 0.050 0.534 0.532 0.068 0.536 0.532 0.040 0.534 0.532 0.054 0.535
9 2 0.335 0.046 0.338 0.335 0.063 0.341 0.335 0.037 0.337 0.335 0.050 0.339
1 0.265 0.048 0.269 0.265 0.059 0.271 0.265 0.035 0.267 0.265 0.047 0.269
1/0 0.210 0.043 0.214 0.210 0.056 0.217 0.210 0.034 0.213 0.210 0.045 0.215
10 2/0
3/0
0.167
0.133
0.041
0.040
0.172
0.139
0.167
0.132
0.055
0.053
0.176
0.142
0.167
0.133
0.033
0.037
0.170
0.137
0.167
0.132
0.044
0.042
0.173
0.139
4/0 0.106 0.039 0.113 0.105 0.051 0.117 0.105 0.031 0.109 0.105 0.041 0.113

11 250
300
0.0896
0.0750
0.0384
0.0375
0.0975
0.0839
0.0892
0.0746
0.0495
0.0479
0.102
0.0887
0.0894
0.0746
0.0307
0.0300
0.0945
0.0804
0.0891
0.0744
0.0396
0.0383
0.0975
0.0837
350 0.0644 0.0369 0.0742 0.0640 0.0468 0.0793 0.0640 0.0245 0.0705 0.0638 0.0374 0.0740
400 0.0568 0.0364 0.0675 0.0563 0.0459 0.0726 0.0563 0.0291 0.0634 0.0560 0.0367 0.0700
12 500 0.0459 0.0355 0.0580 0.0453 0.0444 0.0634 0.0453 0.0284 0.0535 0.0450 0.0355 0.0573
600 0.0388 0.0359 0.0529 0.0381 0.0431 0.0575 0.0381 0.0287 0.0477 0.0377 0.0345 0.0511
700 0.0338 0.0350 0.0487 0.0332 0.0423 0.0538 0.0330 0.0280 0.0433 0.0326 0.0338 0.0470
13 750 0.0318 0.0341 0.0466 0.0310 0.0419 0.0521 0.0309 0.0273 0.0412 0.0304 0.0335 0.0452
1000 0.0252 0.0341 0.0424 0.0243 0.0414 0.0480 0.0239 0.0273 0.0363 0.0234 0.0331 0.0405

14 Table 1.5-20. 60 Hz Impedance Data for Three-Phase Aluminum Cable Circuits, in Approximate Ohms per 1000 ft (30 m) at 90 C (b) Three Conductor Cable
Wire Size, In Magnetic Duct and Steel Interlocked Armor In Non-Magnetic Duct and Aluminum Interlocked Armor
AWG or 600 V and 5 kV Non-Shielded 5 kV Shielded and 15 kV 600 V and 5 kV Non-Shielded 5 kV Shielded and 15 kV
15 kcmil
R X Z R X Z R X Z R X Z

6 0.847 0.053 0.849 0.847 0.042 0.848



16 4
2
0.532
0.335
0.050
0.046
0.534
0.338

0.335 0.056

0.340
0.532
0.335
0.040
0.037
0.534
0.337

0.335

0.045

0.338
1 0.265 0.048 0.269 0.265 0.053 0.270 0.265 0.035 0.267 0.265 0.042 0.268
1/0 0.210 0.043 0.214 0.210 0.050 0.216 0.210 0.034 0.213 0.210 0.040 0.214
17 2/0 0.167 0.041 0.172 0.167 0.049 0.174 0.167 0.033 0.170 0.167 0.039 0.171
3/0 0.133 0.040 0.139 0.133 0.048 0.141 0.133 0.037 0.137 0.132 0.038 0.138
4/0 0.106 0.039 0.113 0.105 0.045 0.114 0.105 0.031 0.109 0.105 0.036 0.111
18 250 0.0896 0.0384 0.0975 0.0895 0.0436 0.100 0.0894 0.0307 0.0945 0.0893 0.0349 0.0959
300 0.0750 0.0375 0.0839 0.0748 0.0424 0.0860 0.0746 0.0300 0.0804 0.0745 0.0340 0.0819
350 0.0644 0.0369 0.0742 0.0643 0.0418 0.0767 0.0640 0.0245 0.0705 0.0640 0.0334 0.0722
19 400
500
0.0568
0.0459
0.0364
0.0355
0.0675
0.0580
0.0564
0.0457
0.0411 0.0700 0.0563 0.0291 0.0634 0.0561 0.0329 0.0650
0.0399 0.0607 0.0453 0.0284 0.0535 0.0452 0.0319 0.0553
600 0.0388 0.0359 0.0529 0.0386 0.0390 0.0549 0.0381 0.0287 0.0477 0.0380 0.0312 0.0492
700 0.0338 0.0350 0.0487 0.0335 0.0381 0.0507 0.0330 0.0280 0.0433 0.0328 0.0305 0.0448
20 750 0.0318 0.0341 0.0466 0.0315 0.0379 0.0493 0.0309 0.0273 0.0412 0.0307 0.0303 0.0431
1000 0.0252 0.0341 0.0424 0.0248 0.0368 0.0444 0.0239 0.0273 0.0363 0.0237 0.0294 0.0378

21

For more information, visit: www.eaton.com/consultants CA08104001E