Professional Documents
Culture Documents
3. Chapter 3 - Operation
3.1 General
Ideally a generator would operate with few load cycles and always within the parameters
recommended by the equipment designers. Since these ideal conditions are neither possible nor
practical, it is worthwhile to consider the affects on generator reliability and length of life of
common operating practices, i.e., load cycling, start-stops, temperature control, over-loading, off-
line turning gear, off-line stationary, cleanliness and contamination, unbalanced armature load
current.
In addition, mis-operation and malfunction will have a determining influence, e.g., cooling water
leaks, oil entry, loss of cooling, synchronizing errors, sudden short circuit events, loss of
lubrication, over-speed, loss of excitation, over-fluxing incidents, auxiliary system failures, alarm
failure or misinterpretation.
These affects on reliability and length of life from normal operation, mis-operation and
malfunction will be considered below.
Armature bar groundwall and internal insulation mechanical deterioration and migration
Field turn insulation and slot liner mechanical deterioration and migration.
3-1
Maughan Engineering Consultants
Alignment between generator and turbine will also be affected and can result in high vibration
problems.
3.2.4 Over-loading
Because over-loading even by modest amounts substantially influences reliability and life,
designers continue to emphasize the importance of operating within specified design limits. In
particular, the reactive capability curve limits should be maintained (Figure 3-1). Differential
expansions of armature bars and field copper will increase, with accompanying increased
mechanical deterioration rates. Also, over-temperature conditions will tend to exist and will
impact life of insulating materials.
3.2.5 Start/Stops
In addition to temperature cycling, start/stop operation mechanically cycles all components of the
field. This includes wedges, collectors, retaining rings, fan rings, and field forging. Shrink fit
locations are also cycled. Non-body mounted retaining rings go through a heavy flexing of the
field copper at the inboard end of the rings. Generally speaking, generators do not like shutdowns.
3-2
Maughan Engineering Consultants
Low-speed turning gear operation allows field coils and blocking to continually shift with
rotation. This is the root cause of the copper dust phenomenon. Otherwise, low speed turning
gear should not affect reliability if bearing lubrication is maintained properly.
3-3
Maughan Engineering Consultants
System faults and synchronizing errors are accompanied by high torque on the field, which is
transferred into the turbine. In the process, the couplings may slip, bolts may be deformed, shafts
broken, and the turbine severely damaged.
Fortunately because of the high reliability of isolated phase buss, close-in faults are rare on large
machines. Also short circuit is most likely to occur due to flashover near peak armature voltage;
this will limit current to about one-half the theoretical maximum obtained if a short circuit were to
occur at the instant of zero armature voltage on the AC voltage cycle. Because force is a function
of the square of current, force would be limited to one-forth of theoretical maximum. But even so,
the forces can be very high, on the order of 100 times normal operational force.
3-4
Maughan Engineering Consultants
to the power grid whatever power the turbine is producing. If allowed to persist, severe and
destructive damage may occur to the field in a matter of moments.
Reclosure of the field will cause the generator to pull back in step as the field builds back up over
a period of a few seconds. This will place some additional duty of the armature winding; however,
this may be preferable to a continuation of asynchronous operation if the steam valves cannot be
closed and the machine shut down.
Under non-synchronized conditions, excess field current will cause magnetic circuit saturation.
Exciters are capable of output of more than 3 times the necessary field current for rated no-load
stator voltage. A field current value of 1.5 times no-load field current will give about 1.20 times
rated armature voltage. On an unsynchronized generator, this field current will cause significant
stator magnetic circuit saturation. This, in turn, will drive significant flux beyond the outside
diameter of the core, and will also increase duty from core end leakage flux. If the condition is
prolonged, core iron damage can be expected. Values of field current for varying load conditions
are provided by manufacturers on the V-curve, Figure 3-4.
The condition of maximum exciter current output to an unsynchronized generator can be expected
to destroy the stator core, probably in a matter of several seconds, Figure 3-5. Core iron burning
will be particularly severe at the core ends and at the keybars. Tooth burning is likely to cause
stator-winding failure, with additional core burning and contamination damage.
3-5
Maughan Engineering Consultants
Several redundancies are incorporated into lubrication oil systems, but failures of this type still
periodically occur. Furthermore, the severe vibration is likely to fracture bearing oil supply lines.
Due to the several back-ups provided to assure lubricating oil supply to the bearings under all
conditions, the system will tend to pump the oil tank dry into the resulting fire.
Extensive equipment and plant damage can be expected in the event of complete loss of
lubrication oil.
3-6
Maughan Engineering Consultants
If the field uses 18/5 retaining ring material, a slow persistent leak can cause stress-corrosion
catastrophic fracture of a ring in a period of only a few months.
3.2.17 Overspeed
Excessive overspeed can destroy a turbine-generator, Figure 3-7. Even if fracture does not occur,
components may yield and stretch to a point where replacement is required.
3-7
Maughan Engineering Consultants
brush holders. At least one design is available which is essentially a drop-in replacement, and the
retrofit can be accomplished at modest cost during a one-day outage.
The preventative maintenance check list, below, can be used as a guide in reviewing plant
collector inspection/maintenance practices to assure that optimum collector maintenance is being
accomplished.
Daily Inspections:
Inspect for sparking between brush and rings.
Listen for brush chatter.
On brush holders without constant pressure springs, check that pressure is still within
acceptable range.
Look for loose, frayed, or blue pigtails.
Check for dust or oil.
Look for short brushes.
Check for any instability or increase in indicated field temperature recorder readings.
Watch for any changes from previous conditions.
Any abnormalities should be immediately reported to responsible plant maintenance
and/or management personnel.
Weekly Inspections:
On brush holders without constant pressure springs, adjust brush-spring pressures so they
are all within proper range.
Remove a brush at random, and examine its wear face for evidence of pitting, edge
chipping, grooving, or threading.
Check all brushes for hang-up in the brush holder.
Examine brush springs and pigtail connections.
Spot-check for vibration, and record and plot the levels on long-term chart.
Observe brushes and pig-tails with infrared scope.
Observe collector rings with stroboscope.
Replace worn and/or deficient brushes, removing one brush (or magazine) at a time.
Note the appearance of collector ring surfaces and of the brush films on the rings for any
change from normal.
Inspect air filters. Replace or clean as necessary.
Conditions should be recorded and timely correction of deficiencies should be
accomplished.
3.2.19 Auxiliaries
The pumping units, valves, and piping associated with the auxiliaries tend to be a source of
constant minor maintenance. However, the auxiliaries generally are not a major problem if given
proper on-going maintenance.
Alarm conditions, such as high levels and low pressures, should be immediately addressed since if
left unattended may lead to a serious forced outage. Conditions of particular concern include low
oil pressures, high gas flow from the stator cooling water or hydrogen seal systems, and liquid
accumulation in the detectors.
3-8
Maughan Engineering Consultants
3.2.20 Alarms
Instrumentation monitoring the status of the generator from the control room is limited in
quantity, with few backups, sometimes ambiguous information, and infrequent alarm conditions.
As a result, misinterpretation, misunderstanding or procrastination in response to alarm conditions
occasionally occurs, with serious consequences.
For example, failure to respond to one or two RTDs or TCs reading high temperature on a liquid
cooled stator winding can result in winding double-failure to ground with extensive arc damage.
Core monitor alarm may be false or indicative of beginning stages of fatal burning of insulation.
Sudden increase in vibration may be minor or the beginning stages of catastrophic failure. High
cooling gas temperature may be a bad sensor or a generator in the process of severe overheating.
A field ground alarm may be of little consequence or preliminary stages of forging burning or a
double ground problem.
Most power plants now incorporate a Distributed Control System (DCS). Correct response(s) to
each of the various generator alarms should be programmed into the DCS.
3-9