Professional Documents
Culture Documents
4-1. Introduction:
In this chapter it is required to plan the distribution system of the residential
area. The planning of this area starts from inside the individual flats of the
buildings.
The various types of loads in the house like lighting, normal sockets (N.S),
power sockets (P.S) and load break switches (L.B.S) are estimated according
to the standard forms. The feeding circuits are defined and the main wiring
c.s.a. are calculated.
The mains wiring is generally built using insulated copper cables. The
choice of conductor material is a compromise among electrical properties,
mechanical properties, and price. From the start, copper has been the
material of choice for household branch circuits.
The ratings of the sub-circuits' miniature circuit breakers (M.C.B) and the
main circuit breaker of the flat or the villa as well as energy meter are
selected.
Any house that has been properly wired will have a circuit breaker panel
used to shut circuits off in case they draw too much current. It is the current
capacity of circuit breaker (in amperes) that determines how much current a
circuit can supply. In case of an overload or a short-circuit on that circuit, the
breaker trips and automatically shuts off power to that circuit. Ground fault
circuit breakers offer protection against more than just overloads.
After the load of the flat is being calculated, the diversified estimation of the
total load of the building is made. The buildings are fed from distribution boxes
via cables of suitable sizes, forming a part of the low voltage distribution
network. The distribution boxes are fed from 11 KV/380 V distribution
transformers, preferably in loops, to secure the continuity of supply to the
distribution boxes and hence to the buildings.
40
Chapter -4- Building Wiring Calculations
Light is the prime factor in the human life as all activities of human beings
ultimately depend upon the light. Where there is no natural light, use of
artificial is made. Lighting increases production and reduce accidents.
Candela
International unit (SI) of luminous intensity; term evolved from considering a
standard candle, similar to a plumber's candle, as the basis of evaluating the
intensity of other light describe the relative intensity of a source .
Illuminance (E)
The quantity of light (measured in foot-candles, Lux, etc) at a point on a
surface.
Lumen
The international unit of luminous flux or quantity of light.
Luminaire
A complete lighting unit consisting of a lamp (or lamps) together with the parts
designed to distribute the light, position and protect the lamps, and connect
them to the power supply. This is sometimes referred to as a "fixture".
41
Chapter -4- Building Wiring Calculations
Lamp efficiency
It is the amount of output lumen per watt.
Lux (lumen/m2)
SI (international system) unit of illumination. One lumen uniformly distributed
over an area of one square meter.
Mounting Height
Distance from the bottom of the fixture to either the floor or work
plane, depending on usage.
42
Chapter -4- Building Wiring Calculations
It is a factor that depends on the dimension of the room. It equals the ratio
between the product of length (L) and breadth (W) of the room to the product
of the mounting height (H) and the summation of the length and breadth of
that room.
L *W
K=
H * (L + W )
Generally K varies from 0.6 to 5.0
A- Types of lamps:
The lighting design process in its most basic form entails identifying a task
and then providing a light source that will provide proper quantity and quality
of light for the task. The fixture protects the light source, connects it to the
power source and distributes its light.
I-Incandescent Lamps:
Incandescent light sources are the cheapest light sources.
.
Do not require a ballast
It is based on the fact that current is passed through a filament, which
heats until it glows
Less efficacious light source
Shorter service life than other light sources in most cases
Filament is sensitive to vibrations
Bulb can get very hot during operation
Must be properly shielded because incandescent lamps can produce
direct glare as a point source
Require proper line voltage as line voltage variations can severely
affect light output and service life
43
Chapter -4- Building Wiring Calculations
ii-Fluorescent Lamps:
These lamps rely on the gaseous discharge method.
Require a ballast
Low surface brightness compared to point sources
More efficacious compared to incandescent
Ambient temperatures and convection currents can affect light output
and life
Options for starting methods and lamp current loadings
Requires compatibility with ballast
Low temperatures can affect starting unless"cold weather" ballast is
specified.
44
Chapter -4- Building Wiring Calculations
B- Lighting Schemes:
i- Direct Lighting
In this type of lighting the light from the source falls directly on the object or
the surface to be illuminated.
45
Chapter -4- Building Wiring Calculations
iv-Semi-Indirect Lighting
Like the pervious type except that 75% of the light is directed upwards and
25% of it reaches the working plane.
illumenace * area
Installed wattage =
U .F * M .F * efficiency
Common figures of M.F and U.F are 0.8 and 0.4 respectively
Approximate equation to calculate the required wattage for certain area and
illumination are given by:
N.B The recommended lux in every place is given in table 1 in the appendix of
this chapter.
46
Chapter -4- Building Wiring Calculations
They have different ratings, which can be used such as 3 Amp., 5A,10A the
ratings of 3A,5A, can be used for bedrooms, entrance, balcony, which
requires low electrical sets as T.V, radio and small electric fans...etc. In
general we are going to use only the 5A sockets in all the rooms since this is
more practical.
Sometimes we need some sockets to be used for special purposes like: full
automatic washing cloth machines, air conditions, water heaters, dish
washers, electric ovens and toasters. Such sockets are called power sockets
and they require higher current rating and taking into consideration the
starting period which increases the delivered current to a value higher than
normal operation.
To estimate the socket load for certain domestic units the following are to be
considered:
1- Generally there are 2-5 sockets in the room.
2- Generally there are 5-8 normal sockets on a line.
3- Referring to the IEC standard specification, the ratings of sockets are:
*M.C.B. rating for normal socket = 10 A
*M.C.B. rating for power sockets = 16 A. or 26 A.
4- Calculate the normal socket loads on a line is according to the
formula:
Socket load on a line = 100% of largest normal socket rating on the
line + (20% to 40%) of ratings of other normal sockets.
5- Each power socket has its own line.
6- Total socket load is given by the formula:
Total socket load = 100% of largest M.C.B. Rating of sockets + (20%
to 40%) of Rating of other M.C.B.
47
Chapter -4- Building Wiring Calculations
The riser is cable, which passes upward in each building for transmitting the
electric power from the coffree of the building to each unit of this building, in
other words, it starts from the fuse at the bottom of the house to the highest
flat.
Riser may be one cable or double cable depending on the height of the
house, the number of flats and on the load of each flat.
48
Chapter -4- Building Wiring Calculations
49
Chapter -4- Building Wiring Calculations
Villa Required Total no. required Unit per No. of No. of Total no.
building building
Villa C 10 % 400 50 1 1 1 50
Villa E 10 % 400 50 1 1 1 50
50
Chapter -4- Building Wiring Calculations
Living 660+160+160
3 5.083.00 150 I 457.20 480 2.18
room W
Bedroom3
6 (main 4.263.38 150 I 431.96 4100 W 400 1.82
bedroom)
7 Bathroom 1.923.5 100 F 45.70 140 W 40 0.30
Shaving
50 I 67.20 240 W 80 0.36
mirror
L1 = 4.7 Amps
The M.C.B used =10 Amps
The Copper wire used is of c.s.a 2 mm2
51
Chapter -4- Building Wiring Calculations
Circuit (2): L2
This circuit containing loads of rooms 4,5,6,7 and 8
L2 = 0.66 actual currents of the rooms in the circuit)
= 0.66 (0.114+1.212+1.82+0.303+0.364+0.91)
= 3.118 Amps.
And for safety and good design; we take a safety factor of 1.6
L2 = 5.0 Amps
The M.C.B used =10 Amps
The Copper wire used is of c.s.a 2 mm2
B- Sockets calculations:
- Since the area of the flat is less than 90 m2 and the flat is of youth
housing we don't expect to have any power sockets in this flat.
- The following loads are expected in the flat:
>> Bedroom1:
This is the kids' room, we expect the use of 1 fan of 200 W.
>> Bedroom 2:
We expect the use of 1 cassette of 40 W.
>>Living room:
We expect 1 TV set of 65 W and 1 fan of 200 W
>>Balcony
Since this balcony is very small and accompanied to the main
bedroom so no need for sockets in it.
>> Kitchen
We expect the use of a fridge of 160 w and a kitchen machine of 600 w.
>> Bathroom
We expect the use of a normal washing machine of 400 w and a shaving
machine of 150 w.
>>Hall
We expect the use of any appliance not more than 3 A.
>> Balcony
This is the main balcony and we may use a cassette in it.
52
Chapter -4- Building Wiring Calculations
Room
1 2 3 4 5 6 7 8 9
No.
Room Living
Bedrrom1 Bedroom2 balcony kitchen Bedroom3 bathroom Hall balcony
Function room
No. of
1 1 2 --------- 2 2 2 1 1
N.S
53
Chapter -4- Building Wiring Calculations
D- Riser Calculations:
Flat KVA = 2.75 KVA after diversity for 15 flats.
13.75 x 1000
Phase current = = 62.5 Amps
220
For safety considerations, the riser is loaded with 70%of its ampacity.
1.5x 746
a- Water Pump = 1.5 HP, 0.85 p.f. KVA of the pump = = 1.32
0.85
KVA.
54
Chapter -4- Building Wiring Calculations
Shaving
50 I 51.87 225 W 50 0.23
mirror
Bedroom1
3 (main 3.53.63 150 I 381.15 4100 W 400 1.82
bedroom)
Bedroom2
4 (kids' 3.353.62 150 F 123.70 340 W 120 0.91
bedroom)
L1 = 5 Amps
The M.C.B used =10 Amps
The Copper wire used is of c.s.a 2 mm2
55
Chapter -4- Building Wiring Calculations
Circuit ( 2 ): L2
This circuit containing loads of rooms 3, 4, 5 and 6
L2 = 0.66 actual currents of the rooms in the circuit)
= 0.66 (1.82+0.91+0.27+1.86)
= 3.21 Amps.
And for safety and good design; we take a safety factor of 1.52
L2 = 4.88 Amps
The M.C.B used =10 Amps
The Copper wire used is of c.s.a 2 mm2
B- Sockets calculations:
- Since the area of the flat is less than 90 m2 and the flat is of youth
housing we don't expect to have any power sockets in this flat.
- The following loads are expected in the flat:
>> Kitchen:
We expect the use of a fridge of 160 w and a kitchen machine of 600 w.
>> Bathroom
We expect the use of a normal washing machine of 400 w.
>> Bedroom 2:
This is the kids' room. We expect the use of a fan of 200w.
>>Living room:
We expect 1 TV set of 65 W and 1 fan of 200 W
>>Hall
We expect the use of any appliance like a vacuum cleaner of 800w.
56
Chapter -4- Building Wiring Calculations
Room
1 2 3 4 5 6 7 8
No.
Room Bedroom Bedroom Living Dinning
Kitchen Bathroom Balcony Hall
Function 1 2 room room
No. of
2 1 2 1 1 2 1 2
N.S
57
Chapter -4- Building Wiring Calculations
D- Riser Calculations:
Flat KVA = 3.02 KVA after diversity for 10 flats.
10.06 x 1000
Phase current = = 45.71 Amps
220
For safety considerations, the riser is loaded with 70%of its ampacity.
1.5x 746
a- Water Pump = 1.5 HP, 0.85 p.f. KVA of the pump = = 1.32
0.85
KVA.
And since phases R and S have only 3 flats on each while phase T has 4
flats, thus to cause relative balance between phases then we feed the
auxiliary loads from either phase R or S.
58
Chapter -4- Building Wiring Calculations
L1
This circuit containing loads of areas 1, 2, 8, 10 and 11
L1 = 0.66 actual currents of the rooms in the circuit)
= 0.66 (1.82+0.3+0.36+0.11+0.27+0.45)
= 2.1846 Amps.
And for safety and good design; we take a safety factor of 1.6
L1 = 3.5 Amps
The M.C.B used =10 Amps
The Copper wire used is of c.s.a 3 mm2
59
Chapter -4- Building Wiring Calculations
L2
L2 = 4.1296 Amps
The M.C.B used =10 Amps
The Copper wire used is of c.s.a 3 mm2
L3
This circuit containing loads of areas 4, 5 and 6
L3 = 0.66 actual currents of the rooms in the circuit)
= 0.66 (2.18+2.18+0.27)
= 3.06 Amps.
And for safety and good design; we take a safety factor of 1.6
L3 = 4.9 Amps
The M.C.B used =10 Amps
The Copper wire used is of c.s.a 3 mm2
B- Sockets calculations:
- Normal Socket Lines:
The following loads are expected in each area.
>> Kitchen:
We expect the use of a fridge of 160 w, a kitchen machine of 600 w and
deep freezer of 160 w.
>> Bathroom
We expect the use of a hair dryer of 600w or a shaving machine of 150w.
>>Living room:
We expect a TV set of 65 W, a video of 30w and a cassette of 40w.
>>Salon:
We expect the use of a T.V of 65w and a sound system of 800w
60
Chapter -4- Building Wiring Calculations
>>Hall 1:
Since the hall is long we use at least two normal sockets one at each end.
Room No. 1 2 3 4 5 6 7 8 9
Room Living Dinning
Kitchen Bathroom Salon Balcony Balcony Balcony Hall1
Function room room
No. of N.S 3 1 3 2 2 1 1 1 2
NS1
This circuit contains the loads of rooms 1, 2 and 8.
NS1 = largest rating socket in ampere + ( the rest sockets ratings in ampere
of the rooms in the circuit)diversity factor
= 5+0.2 4 5 = 9 A
NS2
This circuit contains the loads of rooms 3, 7 and 9.
NS2 = largest rating socket in ampere + ( the rest sockets ratings in ampere
of the rooms in the circuit) diversity factor
= 5+0.2 5 5 = 10 A
NS3
This circuit contains the loads of rooms 4, 5 and 6..
NS3 = largest rating socket in ampere + ( the rest sockets ratings in ampere
of the rooms in the circuit) diversity factor
= 5+0.2 4 5 = 9 A
61
Chapter -4- Building Wiring Calculations
62
Chapter -4- Building Wiring Calculations
For phase S:
Total Socket Load = largest rating M.C.B in amperes + ( the rest M.C.B
ratings in amperes) diversity factor.
= PS3+0.2 NS2
= 28.2 Amps
Total Lighting Load = L2 = 4.13 Amps
Total Load of phase S for the 1st floor = Total Socket Load + Total Lighting
Load
= 32.33 Amps
For phase T:
Total Socket Load = largest rating M.C.B in amperes + ( the rest M.C.B
ratings in amperes) diversity factor.
= PS4+0.2 NS3
= 27.0 Amps
Total Lighting Load = L3 = 4.9 Amps
Total Load of phase T for the 1st floor = Total Socket Load + Total Lighting
Load
= 31.9 Amps
63
Chapter -4- Building Wiring Calculations
L4
This circuit containing loads of areas 12, 13, 19 and 20.
L4 = 0.66 actual currents of the rooms in the circuit)
= 0.66 (0.91+0.3+0.36+0.11+0.91)
= 1.71 Amps.
And for safety and good design; we take a safety factor of 1.6
L4 = 2.74 Amps
The M.C.B used =6 Amps
The Copper wire used is of c.s.a 3 mm2
64
Chapter -4- Building Wiring Calculations
L5
This circuit containing loads of areas 14 and 18.
L5 = 0.66 actual currents of the rooms in the circuit)
= 0.66 (2.36+0.27)
= 1.73 Amps.
And for safety and good design; we take a safety factor of 1.6
L5 = 2.78 Amps
The M.C.B used =6 Amps
The Copper wire used is of c.s.a 3 mm2
L6
This circuit containing loads of areas 15, 16 and 17.
L6 = 0.66 actual currents of the rooms in the circuit)
= 0.66 (1.82+1.21+0.27)
= 2.2 Amps.
And for safety and good design; we take a safety factor of 1.6
L6 = 3.48 Amps
The M.C.B used =6 Amps
The Copper wire used is of c.s.a 3 mm2
B- Sockets calculations:
- Normal Socket Lines:
The following loads are expected in each area.
>> Kitchenette:
We expect the use of a small fridge of 80 w and a toaster of 800w
>> Bathroom
We expect the use of a hair dryer of 600w or a shaving machine of 150w
and an air blower of 200w
>> Bedroom2:
We expect the use of a cassette of 40w and an iron of 1000w.
>>Bedroom3:
We expect the use of a T.V of 65w and a fan of 800w
>>Balcony of bedroom3
We expect the use of a cassette of 40w
>>Balcony of bedroom1
We expect the use of any appliance of not more than 3A
65
Chapter -4- Building Wiring Calculations
>>Hall 2:
Like we did in hall1, we use at least two normal sockets one at each end.
Room No. 1 2 3 4 5 6 7 8 9
Room Kitchen Bedro Bedroo Bedro
Bathroom Balcony Balcony Balcony Hall2
Function ette om1 m2 om3
No. of N.S 2 2 3 2 2 1 1 1 2
NS4
This circuit contains the loads of rooms 12, 13 and 19.
NS4 = largest rating socket in ampere + ( the rest sockets ratings in ampere
of the rooms in the circuit)diversity factor
= 5+0.2 4 5 = 9 A
NS5
This circuit contains the loads of rooms 14, 18 and 20.
NS5 = largest rating socket in ampere + ( the rest sockets ratings in ampere
of the rooms in the circuit) diversity factor
= 5+0.2 5 5 = 10 A
66
Chapter -4- Building Wiring Calculations
NS6
This circuit contains the loads of rooms 15, 16 and 17.
NS6 = largest rating socket in ampere + ( the rest sockets ratings in ampere
of the rooms in the circuit) diversity factor
= 5+0.2 4 5 = 9 A
67
Chapter -4- Building Wiring Calculations
Remark: in the 1st floor, load of phase R> load of phase S> load of phase T;
thus in the 2nd floor we care that the opposite happens to cause a balance on
the phase as a whole.
Calculations of phases current:
For phase R:
Total Socket Load = largest rating M.C.B in amperes + ( the rest M.C.B
ratings in amperes) diversity factor.
= PS5+0.2 NS4
= 27 Amps
Total Lighting Load = L4 = 2.74 Amps
Total Load of phase R for the 2nd floor = Total Socket Load + Total Lighting
Load
= 29.74 Amps.
For phase S:
Total Socket Load = largest rating M.C.B in amperes + ( the rest M.C.B
ratings in amperes) diversity factor.
= PS6+0.2 NS6
= 27 Amps
Total Lighting Load = L5 = 2.78 Amps
Total Load of phase S for the 2nd floor = Total Socket Load + Total Lighting
Load
= 29.78 Amps
For phase T:
Total Socket Load = largest rating M.C.B in amperes + ( the rest M.C.B
ratings in amperes) diversity factor.
= PS7+0.2 NS5
= 28. Amps
Total Lighting Load = L6 = 3.48 Amps
Total Load of phase T for the 2nd floor = Total Socket Load + Total Lighting
Load
= 31.9 Amps
The incoming M.C.B. of the 2nd floor panel board 40A (3p)
68
Chapter -4- Building Wiring Calculations
E- Riser Calculations:
Villa KVA without the garden lighting is 41 KVA.
13.67 x 1000
Phase current = = 62.12 Amps
220
For safety considerations, the riser is loaded with 70%of its ampacity.
the riser used is 3x50 + 25 mm2 Cu & the resistance per phase
is 0.836x10-3 V/m.
69
Chapter -4- Building Wiring Calculations
Dinning
4 55 150 I 750 1060 W+2160 W 720 3.27
room
L1
This circuit containing loads of areas 1, 3 and 11
L1 = 0.66 actual currents of the rooms in the circuit)
= 0.66 (2.73+3.27+0.55)
= 4.323 Amps.
And for safety and good design; we take a safety factor of 1.2
L1 = 5.1876 Amps
The M.C.B used =10 Amps
The Copper wire used is of c.s.a 3 mm2
70
Chapter -4- Building Wiring Calculations
L2
This circuit containing loads of areas 2, 5, 7 and 8
L2 = 0.66 actual currents of the rooms in the circuit)
= 0.66 (1.82+3.82+0.303+0.23+0.45)
= 4.37 Amps.
And for safety and good design; we take a safety factor of 1.2
L2 = 5.244 Amps
The M.C.B used =10 Amps
The Copper wire used is of c.s.a 3 mm2
L3
This circuit containing loads of areas 4, 6, 9 and 10
L3 = 0.66 actual currents of the rooms in the circuit)
= 0.66 (3.27+2.42+0.189+0.55)
= 3.06 Amps.
And for safety and good design; we take a safety factor of 1.2
L3 = 5.088 Amps
The M.C.B used =10 Amps
The Copper wire used is of c.s.a 3 mm2
B- Sockets calculations:
- Normal Socket Lines:
The following loads are expected in each area.
>> Bedroom2:
We expect the use of a cassette of 40w and an iron of 1000w.
>>Salon:
We expect the use of a T.V of 65w, a video of 30w and a sound system of
800w.
>>Hall 1:
Since the area is big (6.5 6m2) thus we must spread at least two or three
sockets in this area so that the user can use the required appliance
71
Chapter -4- Building Wiring Calculations
>> Bathroom
We expect the use of a hair dryer of 600w or a shaving machine of 150w
>>Hall 2:
We expect the use of any appliance of 3A.
>> W.C
We expect the use of a hair dryer of 600w or a shaving machine of 150w
>> Hall3:
We expect the use of any appliance of 3A.
>> Hall4
We expect the use of any appliance of 3A.
Room
1 2 3 4 5 6 7 8 9 10 11
No.
Bedroom bedroom Dinning Hall Hall Hall Hall
Room salon kitchen bathroom W.C
1 2 room 1 2 3 4
No. of
3 2 3 2 3 3 1 1 1 1 1
N.S
NS1
This circuit contains the loads of rooms 1, 3 and 11
NS1 = largest rating socket in ampere + ( the rest sockets ratings in ampere
of the rooms in the circuit)diversity factor
= 5+0.2 6 5 = 11 A
72
Chapter -4- Building Wiring Calculations
NS2
This circuit contains the loads of rooms 2, 5, 7 and 8 .
NS2 = largest rating socket in ampere + ( the rest sockets ratings in ampere
of the rooms in the circuit) diversity factor
= 5+0.2 6 5 = 11 A
NS3
This circuit contains the loads of rooms 4, 6, 9 and 10.
NS3 = largest rating socket in ampere + ( the rest sockets ratings in ampere
of the rooms in the circuit) diversity factor
= 5+0.2 6 5 = 11 A
73
Chapter -4- Building Wiring Calculations
For phase S:
Total Socket Load = largest rating M.C.B in amperes + ( the rest M.C.B
ratings in amperes) diversity factor.
= PS2+0.2 NS2
= 28.2 Amps
Total Lighting Load = L2 = 5.244 Amps
Total Load of phase S for the 1st floor = Total Socket Load + Total Lighting
Load
74
Chapter -4- Building Wiring Calculations
= 33.44 Amps
For phase T:
Total Socket Load = largest rating M.C.B in amperes + ( the rest M.C.B
ratings in amperes) diversity factor.
= PS5+0.2 (NS3 + PS4)
= 30.2 Amps
Total Lighting Load = L3 = 5.088 Amps
Total Load of phase T for the 1st floor = Total Socket Load + Total Lighting
Load
= 35.288 Amps
Let the garden lighting be 1.5 KVA. It will be connected to the phase R since it
is the least loaded phase.
Total KVA of the building = 22.5 + 1.5 = 24 KVA.
E- Riser Calculations:
Villa KVA without the garden lighting is 22.5 KVA.
7.5 x 1000
Phase current = = 34.1 Amps
220
For safety considerations, the riser is loaded with 70%of its ampacity.
75
Chapter -4- Building Wiring Calculations
The load and the number of each building type are summarized in the
following table:
76