You are on page 1of 16

MostWidelyAcceptedandTrusted

ICCESReport
ESR2818
ICCES|(800)4236587|(562)6990543|www.icces.org Reissued12/2016
000 Thisreportissubjecttorenewal12/2017.


DIVISION:030000CONCRETE
SECTION:031600CONCRETEANCHORS

DIVISION:050000METALS
SECTION:050519POSTINSTALLEDCONCRETEANCHORS

REPORTHOLDER:

DEWALT

701EASTJOPPAROAD

TOWSON,MARYLAND21286



EVALUATIONSUBJECT:


POWERSTUD+SD1EXPANSIONANCHORSFORCRACKEDANDUNCRACKED
CONCRETE(DEWALT/POWERS)

LookforthetrustedmarksofConformity!

2014RecipientofPrestigiousWesternStatesSeismicPolicyCouncil
(WSSPC)AwardinExcellence ASubsidiaryof

ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not
specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a
recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any product covered by the report.

Copyright2016ICCEvaluationService,LLC.Allrightsreserved.
ICC-ES Evaluation Report ESR-2818
Reissued December 2016
This report is subject to renewal December 2017.

www.icc-es.org | (800) 423-6587 | (562) 699-0543 A Subsidiary of the International Code Council

DIVISION: 03 00 00CONCRETE
Section: 03 16 00Concrete Anchors Properties evaluated:
DIVISION: 05 00 00METALS Structural
Section: 05 05 19Post-Installed Concrete Anchors
2.0 USES
REPORT HOLDER: The Power-Stud+ SD1 expansion anchors are used to
resist static, wind and seismic tension and shear loads in
DEWALT
cracked and uncracked normal-weight concrete and
701 EAST JOPPA ROAD
lightweight concrete having a specified compressive
TOWSON, MARYLAND 21286
strength, fc, of 2,500 psi to 8,500 psi (17.2 MPa to
(800) 524-3244
58.6 MPa).
www.dewalt.com
3 1
engineering@powers.com The /8-inch- and /2-inch-diameter (9.5 mm and 12.7 mm)
anchors may be installed in the topside of cracked and
ADDITIONAL LISTEES: uncracked normal-weight or sand-lightweight concrete-
filled steel deck having a specified compressive strength,
POWERS FASTENERS fc, of 2,500 psi to 8,500 psi (17.2 MPa to 58.6 MPa).
701 EAST JOPPA ROAD
TOWSON, MARYLAND 21286 The 3/8-inch- to 3/4-inch-diameter (9.5 mm to 19.1 mm)
(800) 524-3244 anchors may be installed in the soffit of cracked and
www.powers.com uncracked [1/4-inch (6.4 mm) uncracked only] normal-
engineering@powers.com weight or sand-lightweight concrete-filled steel deck having
a minimum specified compressive strength, fc, of 3,000 psi
COOPER B-LINE (20.7 MPa).
509 WEST MONROE STREET
HIGHLAND, ILLINOIS 62249 The anchors comply with Section 1901.3 of the 2015
blineus@cooperindustries.com IBC, Section 1909 of the 2012 IBC and Section 1912 of
the 2009 and 2006 IBC. The anchors are alternatives to
L. H. DOTTIE COMPANY cast-in-place anchors described in Section 1908 of the
6131 SOUTH GARFIELD AVENUE 2012 IBC and Section 1911 of the 2009 IBC. The anchors
COMMERCE, CALIFORNIA 90040 may also be used where an engineered design is
lane@lhdottie.com submitted in accordance with Section R301.1.3 of the IRC.
Installation instructions and information are set forth in
THE HILLMAN GROUP
Section 4.3, Table 1 and Figures 1 3, 4, 5A and 5B.
10590 HAMILTON AVENUE
CINCINNATI, OHIO 45231 3.0 DESCRIPTION
info@hillmangroup.com
3.1 Power-Stud+ SD1:
Power-Stud+ SD1 expansion anchors are torque-
EVALUATION SUBJECT:
controlled, mechanical expansion anchors comprised of an
anchor body, expansion wedge (clip), washer and hex
POWER-STUD+ SD1 EXPANSION ANCHORS FOR
nut. Product names corresponding to report holder and
CRACKED AND UNCRACKED CONCRETE (DEWALT /
additional listees are presented in Table A of this report.
POWERS)
1 3 1 5
Available diameters are /4 inch, /8 inch, /2 inch, /8 inch,
3 7 1
1.0 EVALUATION SCOPE /4 inch, /8 inch, 1 inch, and 1 /4 inch (6.4 mm, 9.5 mm,
12.7 mm, 15.9 mm, 19.1 mm, 22.0 mm, 25.4 mm and
Compliance with the following codes:
31.8 mm). The anchor body and expansion clip are
2015, 2012 and 2009 International Building Code (IBC) manufactured from medium carbon steel complying
with requirements set forth in the approved quality
2015, 2012 and 2009 International Residential Code documentation, and have minimum 0.0002-inch-thick
(IRC) (5 m) zinc plating in accordance with ASTM B633, SC1,

ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed
as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any product covered by the report.
1000

Copyright 2016 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 13
ESR-2818 | Most Widely Accepted and Trusted Page 2 of 13

Type III. The washers comply with ASTM F844. The hex 4.1.3 Requirements for Static Concrete Breakout
nuts comply with ASTM A563, Grade A. The Power-Stud+ Strength in Tension, Ncb or Ncbg: The nominal concrete
SD1 expansion anchor is illustrated in Figure 2. breakout strength of a single anchor or a group of anchors
in tension, Ncb and Ncbg, respectively must be calculated in
The anchor body is comprised of a high-strength
accordance with ACI 318-14 17.4.2 or ACI 318-11 D.5.2,
threaded rod at one end and a tapered mandrel at the
as applicable, with modifications as described in this
other end. The tapered mandrel is enclosed by a three-
section. The basic concrete breakout strength in tension,
section expansion clip that freely moves around the
Nb, must be calculated in accordance with ACI 318-14
mandrel. The expansion clip movement is restrained by the
17.4.2.2 or ACI 318-11 D.5.2.2, as applicable, using the
mandrel taper and by a collar. The anchors are installed in
values of hef and kcr as given in Table 2 of this report. The
a predrilled hole with a hammer. When torque is applied to
nominal concrete breakout strength in tension in regions
the nut of the installed anchor on the threaded end of the
where analysis indicates no cracking in accordance with
anchor body, the mandrel at the opposite end of the
ACI 318-14 17.4.2.6 or ACI 318-11 D.5.2.6, as applicable,
anchor is drawn into the expansion clip, forcing it outward
must be calculated with the value of kuncr as given in Table
into the sides of the predrilled hole in the base material.
2 and with c,N = 1.0.
3.2 Concrete:
For anchors installed in the soffit of sand-lightweight or
Normal-weight and lightweight concrete must comply with normal-weight concrete-filled steel deck floor and roof
Sections 1903 and 1905 of the IBC as applicable. assemblies, as shown in Figure 5A and Figure 5B,
3.3 Steel Deck Panels: calculation of the concrete breakout strength in accordance
with ACI 318-14 17.4.2 or ACI 318-11 D.5.2, as applicable,
Steel deck panels must comply with the configuration in is not required.
Figure 4, Figure 5A and Figure 5B and have a minimum
base steel thickness of 0.035 inch (0.889 mm) [No. 20 4.1.4 Requirements for Static Pullout Strength in
gage]. Steel must comply with ASTM A653/A653M SS Tension, Npn: The nominal pullout strength of a single
Grade 33, and have a minimum yield strength of 33 ksi anchor in accordance with ACI 318-14 17.4.3 or ACI
(228 MPa). 318-11 D.5.3, as applicable, in cracked and uncracked
concrete, Np,cr and Np,uncr, respectively, is given in Table 2.
4.0 DESIGN AND INSTALLATION In lieu of ACI 318-14 17.4.3.6 or ACI 318-11 D.5.3.6, as
4.1 Strength Design: applicable, c,P = 1.0 for all design cases. The nominal
pullout strength in cracked concrete may be adjusted by
4.1.1 General: Design strength of anchors complying with calculations according to Eq-1:
the 2015 IBC, as well as Section R301.3 of the 2015 IRC
0.5
must be determined in accordance with ACI 318-14 Npn, = Np,cr (lb, psi)
Chapter 17 and this report. 2,500
(Eq-1)
Design strength of anchors complying with the 2012 IBC,
0.5
as well as Section R301.1.3 of the 2012 IRC, must be
determined in accordance with ACI 318-11 Appendix D Npn, = Np,cr (N,MPa)
17.2
and this report.
where fc is the specified concrete compressive strength.
Design strength of anchors complying with the 2009 IBC,
In regions where analysis indicates no cracking in
as well as Section R301.1.3 of the 2009 IRC, must be
accordance with ACI 318-14 17.4.3.6 or ACI 318-11
determined in accordance with ACI 318-08 Appendix D
D.5.3.6, as applicable, the nominal pullout strength in
and this report.
tension can be adjusted by calculations according to Eq-2:
Design examples according to the 2015 IBC and 2012 0.5
IBC are given in Figures 7, 8 and 9 of this report. Npn, = Np,uncr (lb, psi) (Eq-2)
2,500
Design parameters provided in Tables 1, 2, and 3 and
0.5
references to ACI 318 are based on the 2015 IBC (ACI
Npn, = Np,uncr (N,MPa)
318-14) and on the 2012 IBC (ACI 318-11) unless noted 17.2
otherwise in Sections 4.1.1 through 4.1.12 of this report. where fc is the specified concrete compressive strength.
The strength design of anchors must comply with ACI
318-14 17.3.1 or ACI 318-11 D.4.1, as applicable, except Where values for Np,cr or Np,uncr are not provided in Table
as required in ACI 318-14 17.2.3 or ACI 318-11 D.3.3, as 2 of this report, the pullout strength in tension need not be
applicable. Strength reduction factors, , as given in ACI evaluated.
318-14 17.3.3 or ACI 318-11 D.4.3, as applicable, and The nominal pullout strength in tension for anchors
noted in Tables 2 and 3 of this report, must be used for installed in the soffit of sand-lightweight or normal weight
load combinations calculated in accordance with Section concrete-filled steel deck floor and roof assemblies, as
1605.2 of the IBC and ACI 318-14 Section 5.3 or ACI shown in Figure 5A and Figure 5B, is provided in Table 2.
318-11, Section 9.2, as applicable. Strength reduction In accordance with ACI 318-14 17.4.3.2 or ACI 318-11
factors, , described in ACI 318-11 D.4.4, must be D.5.3.2, as applicable, the nominal pullout strength in
used for load combinations calculated in accordance with cracked concrete must be calculated according to Eq-1,
ACI 318-11 Appendix C. Strength reduction factors, , whereby the value of Np,deck,cr must be substituted for Np,cr
corresponding to ductile steel elements are appropriate. and the value of 3,000 psi (20.7 MPa) must be substituted
4.1.2 Requirements for Static Steel Strength in for the value of 2,500 psi (17.2 MPa) in the denominator. In
Tension, Nsa: The nominal static steel strength of a single regions where analysis indicates no cracking in
anchor in tension, Nsa, calculated in accordance with ACI accordance with ACI 318-14 17.4.3.6 or ACI 318-11
318-14 17.4.1.2 or ACI 318-11 D.5.1.2, as applicable, is D.5.3.6, as applicable, the nominal strength in uncracked
given in Table 2 of this report. Strength reduction factors, concrete must be calculated according to Eq-2, whereby
the value of Np,deck,uncr must be substituted for Np,uncr and
, corresponding to ductile steel elements may be used.
the value of 3,000 psi (20.7 MPa) must be substituted for
ESR-2818 | Most Widely Accepted and Trusted Page 3 of 13

the value of 2,500 psi (17.2 MPa) in the denominator. The anchors comply with ACI 318-14 2.3 or ACI 318
(-11, -08) D.1, as applicable, as ductile steel elements and
4.1.5 Requirements for Static Steel Strength in Shear,
must be designed in accordance with ACI 318-14 17.2.3.4,
Vsa: The nominal steel strength in shear, Vsa, of a single
17.2.3.5, 17.2.3.6 or 17.2.3.7; ACI 318-11 D.3.3.4, D.3.3.5,
anchor in accordance with ACI 318-14 17.5.1.2 or ACI
D.3.3.6 or D.3.3.7; ACI 318-08 D.3.3.4, D.3.3.5 or D.3.3.6;
318-11 D.6.1.2, as applicable, is given in Table 3 of this
as applicable. Strength reduction factors,, are given
report and must be used in lieu of the values derived by
in Tables 2 and 3 of this report. The 1/4-inch-diameter
calculation from ACI 318-14 Eq. 17.5.1.2b or ACI 318-11
(6.4 mm) anchors must be limited to installation in
Eq. D-29. The strength reduction factor,, corresponding to
structures assigned to IBC Seismic Design Categories A
a ductile steel element must be used for all anchors, as 3 1
and B only. The /8-inch-diameter (9.5 mm), /2-inch-
described in Table 3 of this report.
diameter (12.7 mm), 5/8-inch-diameter (15.9 mm), 3/4-inch-
7
The shear strength Vsa,deck of anchors installed in the diameter (19.1 mm), /8-inch-diameter (22.2 mm), 1-inch-
soffit of sand-lightweight or normal-weight concrete on diameter (25.4 mm) and 11/4-inch-diameter (31.8 mm)
steel deck floor and roof assemblies, as shown in Figure anchors may be installed in structures assigned to IBC
5A and Figure 5B, is given in Table 3 of this report in Seismic Design Categories A to F.
lieu of the values derived by calculation from ACI 318-14 4.1.8.2 Seismic Tension: The nominal steel strength and
17.5.1.2b or ACI 318-11 Eq. D-29, as applicable. nominal concrete breakout strength for anchors in tension
4.1.6 Requirements for Static Concrete Breakout must be calculated in accordance with ACI 318-14 17.4.1
Strength in Shear, Vcb or Vcbg: The nominal concrete and 17.4.2 or ACI 318-11 D.5.1 and D.5.2, respectively, as
breakout strength of a single anchor or group of anchors in applicable, as described in Sections 4.1.2 and 4.1.3 of
shear, Vcb or Vcbg, respectively, must be calculated in this report. In accordance with ACI 318-14 17.4.3.2 or ACI
accordance with ACI 318-14 17.5.2 or ACI 318-11 D.6.2, 318-11 D.5.3.2, as applicable, the appropriate value for
as applicable, with modifications as described in this pullout strength in tension for seismic loads, Np,eq,
section. The basic concrete breakout strength in shear, Vb, described in Table 2 must be used in lieu of Np. Np,eq may
must be calculated in accordance with ACI 318-14 17.5.2.2 be adjusted by calculations for concrete compressive
or ACI 318-11 D.6.2.2, as applicable, using the values of e strength in accordance with Eq-1 of this report.
and da given in Table 3 of this report. For anchors installed in the soffit of sand-lightweight or
For anchors installed in the topside of concrete-filled normal-weight concrete-filled steel deck floor and roof
steel deck assemblies, the nominal concrete breakout assemblies, the nominal pullout strength in tension for
strength of a single anchor or group of anchors in shear, seismic loads, Np,deck,eq, is provided in Table 2 and must be
Vcb or Vcbg, respectively, must be calculated in accordance used in lieu of Np,cr. Np,deck,eq may be adjusted by
with ACI 318-14 17.5.2.1 or ACI 318-11 D.6.2.1, as calculations for concrete compressive strength in
applicable, using the actual member topping thickness, accordance with Eq-1 of this report where the value of
hmin,deck, in the determination of AVc. Minimum member 3,000 psi (20.7 MPa) must be substituted for the value of
topping thickness for anchors in the topside of concrete- 2,500 psi (17.2 MPa) in the denominator.
filled steel deck assemblies is given in Table 1 of this Where values for Np,eq or Np,deck,eq, are not provided in
report. Table 2 of this report, the pullout strength in tension for
For anchors installed in the soffit of sand-lightweight or seismic loads does not govern and need not be evaluated.
normal-weight concrete-filled steel deck floor and roof 4.1.8.3 Seismic Shear: The nominal concrete breakout
assemblies, as shown in Figure 5A and Figure 5B, strength and concrete pryout strength for anchors in shear
calculation of the concrete breakout strength in accordance must be calculated according to ACI 318-14 17.5.2 and
with ACI 318-14 17.5.2 or ACI 318-11 D.6.2, as applicable, 17.5.3 or ACI 318-11 D.6.2 and D.6.3, respectively, as
is not required. applicable, as described in Sections 4.1.6 and 4.1.7. In
4.1.7 Requirements for Static Concrete Pryout accordance with ACI 318-14 17.5.1.2 or ACI 318-11
Strength in Shear, Vcp or Vcpg: The nominal concrete D.6.1.2, as applicable, the appropriate value for nominal
pryout strength of a single anchor or group of anchors in steel strength in shear for seismic loads, Vsa,eq, described
shear, Vcp or Vcpg, respectively, must be calculated in in Table 3 must be used in lieu of Vsa.
accordance with ACI 318-14 17.5.3 or ACI 318-11 D.6.3, For anchors installed in the soffit of sand-lightweight or
as applicable, modified by using the value of kcp provided normal-weight concrete-filled steel deck floor and roof
in Table 3 and the value of Ncb or Ncbg as calculated in assemblies, as shown in Figure 5A and Figure 5B, the
Section 4.1.3 of this report. appropriate value for nominal steel strength in shear for
For anchors installed in the soffit of sand-lightweight or seismic loads, Vsa,deck,eq, described in Table 3 must be
normal-weight concrete-filled steel deck floor and roof used in lieu of Vsa.
assemblies, as shown in Figure 5A and Figure 5B, 4.1.9 Requirements for Interaction of Tensile and
calculation of the concrete pryout strength in accordance Shear Forces: Anchors or groups of anchors that are
with ACI 318-14 17.5.3 or ACI 318-11 D.6.3, as applicable, subject to the effects of combined axial (tensile) and shear
is not required. forces must be designed in accordance with ACI 318-14
4.1.8 Requirements for Seismic Design: 17.6 or ACI 318-11 D.7, as applicable.

4.1.8.1 General: For load combinations including seismic 4.1.10 Requirements for Critical Edge Distance: In
loads, the design must be performed in accordance with applications where c < cac and supplemental reinforcement
ACI 318-14 17.2.3 or ACI 318-11 D.3.3, as applicable. to control splitting of the concrete is not present, the
Modifications to ACI 318-14 17.2.3 shall be applied under concrete breakout strength in tension for uncracked
Section 1905.1.8 of the 2015 IBC. For the 2012 IBC, concrete, calculated according to ACI 318-14 17.4.2 or ACI
Section 1905.1.9 must be omitted. Modifications to ACI 318-11 D.5.2, as applicable, must be further multiplied by
318-08, D.3.3 shall be applied under Section 1908.1.9 of the factor cp,N given by Eq-3:
the 2009 IBC. cp,N =
c
(Eq-3)
cac
ESR-2818 | Most Widely Accepted and Trusted Page 4 of 13

where the factor cp,N need not be taken as less than


1.5hef
. Section 1908.1.9, and Section 4.1 of
cac this report, as applicable (lbf or N).
For all other cases, cp,N = 1.0. In lieu of using ACI 318-14
17.7.6 or ACI 318-11 D.8.6, as applicable, values of cac = Conversion factor calculated as a
must comply with Table 1 of this report. weighted average of the load factors
for the controlling load combination. In
4.1.11 Requirements for Minimum Member Thickness, addition, must include all applicable
Minimum Anchor Spacing and Minimum Edge factors to account for nonductile
Distance: In lieu of ACI 318-14 17.7.1 and 17.7.3; or ACI failure modes and required over-
318-11 D.8.1 and D.8.3, respectively, as applicable, values strength.
of cmin and smin must comply with Table 1. In lieu of ACI
318-14 17.7.5 or ACI 318-11 D.8.5, as applicable, The requirements for member thickness, edge distance
minimum member thicknesses, hmin or hmin,deck, must and spacing, described in this report, must apply. An
comply with Table 1. Additional combinations of minimum example of allowable stress design values for illustrative
member thickness, hmin, and spacing, smin, may be derived purposes is shown in Table 4 and Figures 7, 8 and 9.
by linear interpolation between the given boundary values 4.2.2 Interaction of Tensile and Shear Forces: The
as described in Figure 6. interaction must be calculated and consistent with ACI
For anchors installed in the topside of concrete-filled 318-14 17.6 or ACI 318 (-11 and, -08) D.7 as follows:
steel deck assemblies, the anchors must be installed in For shear loads Vapplied 0.2Vallowable,ASD, the full
accordance with Table 1 and Figure 4 of this report. allowable load in tension shall be permitted.
For anchors installed through the soffit of steel deck For tension loads Tapplied 0.2Tallowable,ASD, the full
assemblies, the anchors must be installed in accordance allowable load in shear shall be permitted.
with Figure 5A and Figure 5B and must have an axial
spacing along the flute equal to the greater of 3hef or 1.5 For all other cases Eq-6 applies:
times the flute width.
+ 1.2 (Eq-6)
Tallowable,ASD Vallowable,ASD

4.1.12 Lightweight Concrete: For the use of anchors in 4.3 Installation:


lightweight concrete, the modification factor a equal to Installation parameters are provided in Table 1 and Figures
0.8 is applied to all values of f c affecting Nn and Vn. 1, 3, 4, 5A and 5B of this report. Anchor locations must
comply with this report and the plans and specifications
For ACI 318-14 (2015 IBC), ACI 318-11 (2012 IBC) and approved by the code official. The Power-Stud+ SD1
ACI 318-08 (2009 IBC), shall be determined in expansion anchors must be installed in accordance with
accordance with the corresponding version of ACI 318. the manufacturer's published installation instructions and
this report. Anchors must be installed in holes drilled into
For anchors installed in the soffit of sand-lightweight the concrete using carbide-tipped masonry drill bits
concrete-filled steel deck and floor and roof assemblies, complying with ANSI B212.15-1994. The nominal drill bit
further reduction of the pullout values provided in this diameter must be equal to that of the anchor. The
report is not required. minimum drilled hole depth is given in Table 1, Figure 4,
4.2 Allowable Stress Design (ASD): Figure 5A and Figure 5B. Prior to anchor installation, the
dust and debris must be removed from the predrilled hole
4.2.1 General: Where design values for use with using a hand pump, compressed air or vacuum. The
allowable stress design (working stress design) load anchor must be hammered into the predrilled hole until the
combinations in accordance with Section 1605.3 of the IBC proper nominal embedment depth is achieved. The nut
are required these are calculated using Eq-4 and Eq-5 as must be tightened against the washer until the torque
follows: values specified in Table 1 are achieved.
Nn
Tallowable,ASD = (Eq-4) For installation in the topside of concrete-filled steel deck

assemblies, installations must comply with Figure 4.
Vn
Vallowable,ASD = (Eq-5) For installation in the soffit of concrete on steel deck

assemblies, the hole diameter in the steel deck must be no
where: more than 1/8-inch (3.2 mm) larger than the diameter of the
Tallowable,ASD = Allowable tension load (lbf or kN) hole in the concrete. Member thickness and edge distance
restrictions for installations into the soffit of concrete on
Vallowable,ASD = Allowable shear load (lbf or kN) steel deck assemblies must comply with Figure 5A and
Nn = Lowest design strength of an anchor Figure 5B.
or anchor group in tension as 4.4 Special Inspection:
determined in accordance with ACI
Periodic special inspection is required in accordance with
318-14 Chapter 17 and 2015 Section
Section 1705.1.1 and Table 1705.3 of the 2015 IBC and
1905.1.8, ACI 318-11 Appendix D,
2012 IBC, Section 1704.15 and Table 1704.4 of the 2009
ACI 318-08 Appendix D and 2009 IBC
IBC, as applicable. The special inspector must make
Section 1908.1.9, and Section 4.1 of
periodic inspections during anchor installation to verify
this report, as applicable (lbf or N).
anchor type, anchor dimensions, concrete type, concrete
Vn = Lowest design strength of an anchor compressive strength, drill bit type, hole dimensions, hole
or anchor group in shear as cleaning procedure, concrete member thickness, anchor
determined in accordance with ACI embedment, anchor spacing, edge distances, tightening
318-14 Chapter and 2015 IBC Section torque and adherence to the manufacturers printed
1905.1.8, ACI 318-11 Appendix D, installation instructions. The special inspector must be
ACI 318-08 Appendix D and 2009 IBC present as often as required in accordance with the
ESR-2818 | Most Widely Accepted and Trusted Page 5 of 13
1
statement of special inspection. 5.13 The /4-inch-diameter (6.4 mm) anchors may be used
5.0 CONDITIONS OF USE to resist short-term loading due to wind forces, and for
seismic load combinations limited to structures
The Power-Stud+ SD1 expansion anchors described in assigned to Seismic Design Categories A and B,
this report comply with, or are suitable alternatives to what under the IBC, subject to the conditions of this report.
is specified in, those codes listed in Section 1.0 of this The 3/8-inch- to 11/4-inch-diameter (9.5 mm to
report, subject to the following conditions: 31.8 mm) anchors may be used to resist short-term
5.1 The anchors must be installed in accordance with the loading due to wind or seismic forces in structures
manufacturers published installation instructions and assigned to Seismic Design Categories A through F,
this report. In case of conflict, this report governs. under the IBC, subject to the conditions of this report.
5.2 Anchor sizes, dimensions, and minimum embedment 5.14 Where not otherwise prohibited in the code, Power-
depths are as set forth in this report. Stud+ SD1 expansion anchors are permitted for use
5.3 The 1/4-inch (6.4 mm) anchors must be installed in with fire-resistance-rated construction provided that at
uncracked normal-weight or lightweight concrete; least one of the following conditions is fulfilled:
3
/8-inch to 11/4-inch anchors (9.5 mm to 31.8 mm) The anchors are used to resist wind or seismic
must be installed in cracked or uncracked normal- forces only.
weight or lightweight concrete having a specified
Anchors that support a fire-resistance-rated
compressive strength, fc, of 2,500 psi to 8,500 psi
envelope or a fire-resistance-rated membrane are
(17.2 MPa to 58.6 MPa).
protected by approved fire-resistance-rated
5.4 The 3/8-inch and 1/2-inch (9.5 mm to 12.7 mm) anchors materials, or have been evaluated for resistance to
must be installed in the topside of cracked and fire exposure in accordance with recognized
uncracked normal-weight or sand-lightweight standards.
concrete-filled steel deck having a specified
Anchors are used to support nonstructural
compressive strength, fc, of 2,500 psi to 8,500 psi
elements.
(17.2 MPa to 58.6 MPa).
3 3 5.15 Use of carbon steel anchors is limited to dry, interior
5.5 The /8-inch to /4-inch anchors (9.5 mm and 19.1 mm)
locations.
must be installed in the soffit of cracked and
uncracked normal-weight or sand-lightweight 5.16 Special inspection must be provided in accordance
concrete-filled steel deck having a minimum specified with Section 4.4 of this report.
compressive strength, fc, of 3,000 psi (20.7 MPa). 5.17 Anchors are manufactured under an approved quality
5.6 The values of fc used for calculation purposes must control program with inspections by ICC-ES.
not exceed 8,000 psi (55.2 MPa). 6.0 EVIDENCE SUBMITTED
5.7 Strength design values must be established in Data in accordance with the ICC-ES Acceptance Criteria
accordance with Section 4.1 of this report. for Mechanical Anchors in Concrete Elements (AC193),
5.8 Allowable stress design values must be established in dated October 2015, which incorporates requirements in
accordance with Section 4.2 of this report. ACI 355.2-07 / ACI 355.2-04, for use in cracked and
5.9 Anchor spacing(s) and edge distance(s), as well uncracked concrete; including optional service-condition
as minimum member thickness, must comply with Test 18 and Test 19 (AC193, Annex 1, Table 4.2) for
Table 1, Figure 4, Figure 5A and Figure 5B of this seismic tension and shear; and quality control
report, unless otherwise noted. documentation.
5.10 Prior to installation, calculations and details 7.0 IDENTIFICATION
demonstrating compliance with this report must be The Power-Stud+ SD1 expansion anchors are identified by
submitted to the code official. The calculations and dimensional characteristics and packaging. A length letter
details must be prepared by a registered design code is stamped on each anchor on the exposed threaded
professional where required by the statutes of the stud end which is visible after installation. Table C
jurisdiction in which the project is to be constructed. summarizes the length code identification system. A plus
5.11 Since an ICC-ES acceptance criteria for evaluating sign + is also marked with the number 1 on all anchors
data to determine the performance of anchors with the exception of the 1/4-inch-diameter (6.4 mm)
subjected to fatigue or shock loading is unavailable at anchors. Packages are identified with the product name,
this time, the use of these anchors under such type and size, the company name as set forth in Table A of
conditions is beyond the scope of this report. this report, and the evaluation report number (ESR-2818).
1
5.12 Anchors [except /4-inch-diameter (6.4 mm)] may be
installed in regions of concrete where cracking has
occurred or where analysis indicates cracking may
occur (ft > fr), subject to the conditions of this report.

TABLE ACROSS REFERENCE OF PRODUCT NAMES TO COMPANY NAMES

COMPANY NAME PRODUCT NAME


DEWALT Power-Stud+ SD1
Powers Fasteners Power-Stud+ SD1
Cooper B-Line Cooper B-Linda Wedge Anchor
L.H. Dottie Co. Dottie Wedge SD1
The Hillman Group Hillman Power-Stud+ SD1
ESR-2818 | Most Widely Accepted and Trusted Page 6 of 13
1
TABLE 1POWER-STUD+ SD1 ANCHOR INSTALLATION SPECIFICATIONS IN CONCRETE
Nominal Anchor Diameter
Anchor Property/Setting 1 3 1 5 3 7
Information
Notation Units /4 /8 /2 /8 /4 /8 1 11/4
inch inch inch inch inch inch inch inch
in. 0.250 0.375 0.500 0.625 0.750 0.875 1.000 1.250
Anchor diameter da (do)7
(mm) (6.4) (9.5) (12.7) (15.9) (19.1) (22.2) (25.4) (31.8)
5 7 9 11 13
Minimum diameter of hole clearance in. /16 /16 /16 /16 /16 1 11/8 13/8
dh
in fixture
(mm) (7.5) (11.1) (14.3) (17.5) (20.6) (25.4) (28.6) (34.9)
1 3 1 5 3 7
/4 /8 /2 /8 /4 /8 1 11/4
Nominal drill bit diameter dbit in.
ANSI ANSI ANSI ANSI ANSI ANSI ANSI ANSI
in. 13 / 4 23/8 21/2 33/4 33/8 45/8 4 55/8 41/2 51/2 61/2
Nominal embedment depth hnom
(mm) (44) (60) (64) (95) (86) (117) (102) (143) (114) (140) (165)
in. 1.50 2.00 2.00 3.25 2.75 4.00 3.125 4.75 3.50 4.375 5.375
Effective embedment depth hef
(mm) (38) (51) (51) (83) (70) (102) (79) (114) (89) (111) (137)
in. 17 / 8 21/2 23/4 4 33/4 5 41/4 57/8 47/8 57/8 71/4
Minimum hole depth hhole
mm (48) (64) (70) (102) (95) (127) (108) (149) (124) (149) (184)
in. 21 / 4 3 33/4 41/2 41/2 6 51/2 7 8 9 9
Minimum overall anchor length2 anch
mm (57) (76) (95) (114) (114) (152) (140) (178) (203) (229) (229)
ft.-lbf. 4 20 40 80 110 175 225 375
Installation torque6 Tinst
(N-m) (5) (27) (54) (108) (149) (237) (305) (508)
7 9 3 15
Torque wrench/socket size - in. /16 /16 /4 /16 11/8 15/16 11/2 17/8
7 21 7 35 41 3 55
Nut height - in. /32 /64 /16 /64 /64 /4 /64 11/16
Anchors Installed in Concrete Construction
in. 31 / 4 33/4 4 4 6 6 7 6 10 10 10 12
Minimum member thickness hmin
(mm) (83) (95) (102) (102) (152) (152) (178) (152) (254) (254) (254) (305)
in. 13 / 4 6 23/4 21/4 6 31/4 4 23/4 6 51/2 41/4 5 6 7 8 8
Minimum edge distance cmin
(mm) (44) (152) (70) (57) (152) (95) (102) (70) (152) (140) (108) (127) (152) (178) (203) (203)
in. 21 / 4 31/2 9 33/4 41/2 10 5 6 6 11 41/4 6 61/2 61/2 8 8
Minimum spacing distance smin
(mm) (57) (89) (229) (95) (114) (254) (127) (152) (152) (270) (108) (152) (165) (165) (203) (203)

Critical edge distance in. 31 / 2 61/2 8 8 6 10 11 16 111/2 12 20


cac
(uncracked concrete only)
(mm) (89) (165) (203) (203) (152) (254) (279) (406) (292) (305) (508)

Anchors Installed in the Topside of Concrete-filled Steel Deck Assemblies3,4


in. 31/4 31/4 31/4
Minimum member topping thickness hmin,deck
(mm) (83) (95) (95)
in. 13/4 23/4 41/2
See Note 3

See Note 3

See Note 3

See Note 3

See Note 3

See Note 3
Minimum edge distance cmin,deck,top
(mm) (44) (70) (114)
in. 21/4 4 61/2
Minimum spacing distance smin,deck,top
(mm) (57) (102) (165)
Critical edge distance in. 31/2 61/2 6
cac,deck,top
(uncracked concrete only) (mm) (89) (165) (152)

Anchors Installed Through the Soffit of Steel Deck Assemblies into Concrete5

Minimum member topping thickness in. 31/4 31/4 31/4 31/4


hmin,deck
Not Applicable

Not Applicable

Not Applicable
(see detail in Figure 5A) (mm) (95) (95) (95) (95)
Minimum edge distance, lower flute in. 11 / 4 11/4 11/4 11/4
cmin
(see detail in Figure 5A) (mm) (32) (32) (32) (32)
Minimum axial spacing distance in. 63 / 4 63/4 93/4 81/4 12 93/8 141/4
Not Applicable

smin
along flute (see detail in Figure 5A) (mm) (171) (171) (248) (210) (305) (238) (362)
Minimum member topping thickness in. 21 / 4 21/4
hmin,deck
(see detail in Figure 5B) (mm) (57) (57)
Not Applicable

Not Applicable

Not Applicable

Not Applicable

Not Applicable

3 3
Minimum edge distance, lower flute in. /4 /4
cmin
(see detail in Figure 5B) (mm) (19) (19)
in. 6 6 93 / 4
Minimum axial spacing distance
smin
along flute (see detail in Figure 5B)
(mm) (152) (152) (248)
For SI: 1 inch = 25.4 mm, 1 ft-lbf = 1.356 N-m.
1
The information presented in this table is to be used in conjunction with the design criteria of ACI 318-14 Chapter 17 or ACI 318-11 Appendix D, as applicable.
2
The listed minimum overall anchor length is based on anchor sizes commercially available at the time of publication compared with the requirements to achieve the
minimum nominal embedment depth, nut height and washer thickness, and consideration of a possible fixture attachment.
3
The 1/4-inch-diameter (6.4 mm) anchors may be installed in the topside of uncracked concrete-filled steel deck assemblies where concrete thickness above the upper
flute meets the minimum member thicknesses specified in this table. The 3/8 -inch (9.5 mm) through 11/4 -inch-diameter (31.8 mm) anchors may be installed in the topside
of cracked and uncracked concrete-filled steel deck assemblies where concrete thickness above the upper flute meets the minimum member thicknesses specified in this
table under Anchors Installed in Concrete Construction.
4
For installations in the topside of concrete-filled steel deck assemblies, see the installation detail in Figure 4.
5
For installations through the soffit of steel deck assemblies into concrete, see the installation details in Figures 5A and 5B. In accordance with the figures, anchors shall
have an axial spacing along the flute equal to the greater of 3hef or 1.5 times the flute width.
6
For installation of 5/8-inch-diameter anchors through the soffit of the steel deck into concrete, the installation torque is 50 ft.-lbf. For installation of 3/4-inch-diameter
anchors through the soffit of the steel deck into concrete, installation torque is 80 ft.-lbf.
7
The notation in brackets is for the 2006 IBC.
ESR-2818 | Most Widely Accepted and Trusted Page 7 of 13

FIGURE 1POWER-STUD+ SD1 ANCHOR DETAIL FIGURE 2POWER-STUD+ SD1


Before (Left Picture) and After (Right Picture) Application of Installation Torque ANCHOR ASSEMBLY

1.) Using the 2.) Remove 3.) Position the 4.) Tighten the
proper drill bit dust and washer on the anchor with a
size, drill a hole debris from anchor and torque wrench by
into the base the hole using thread on the nut. applying the
material to the a hand pump, If installing required installation
required depth. compressed through a fixture, torque, Tinst. (See
The tolerances air or a drive the anchor Table1. Note: The
of the drill bit vacuum to through the threaded stud will
used should remove loose fixture into the draw up during the
meet the particles left hole. Be sure the tightening of the
requirements of from drilling. anchor is driven nut; the expansion
ANSI Standard to the minimum clip (wedge)
B212.15. required remains in original
embedment position.)
depth, hnom.

FIGURE 3POWER-STUD+ SD1 INSTALLATION INSTRUCTIONS

TABLE CPOWER-STUD+ SD1 ANCHOR LENGTH CODE IDENTIFICATION SYSTEM


Length ID marking on
A B C D E F G H I J K L M N O P Q R S T
threaded stud head
1 1 1 1 1 1 1 1 1
Overall anchor From 1 /2 2 2 /2 3 3 /2 4 4 /2 5 5 /2 6 6 /2 7 7 /2 8 8 /2 9 9 /2 10 11 12
length, anch, Up to but 1 1 1 1 1 1 1 1
(inches) 2 2 /2 3 3 /2 4 4 /2 5 5 /2 6 6 /2 7 7 /2 8 8 /2 9 9 /2 10 11 12 13
not including
For SI: 1 inch = 25.4 mm.

1
Anchors may be
placed in the
topside of steel deck
profiles in
accordance with
Figure 4 provided
the minimum
member topping
thickness, minimum
spacing distance
and minimum edge
distance are
satisfied as given in
Table 1 of this
report.

FIGURE 4POWER-STUD+ SD1 INSTALLATION DETAIL FOR ANCHORS IN THE TOPSIDE OF CONCRETE-FILLED
1
STEEL DECK FLOOR AND ROOF ASSEMBLIES (SEE DIMENSIONAL PROFILE REQUIREMENTS)
ESR-2818 | Most Widely Accepted and Trusted Page 8 of 13

FIGURE 5APOWER-STUD+ SD1 INSTALLATION DETAIL FOR ANCHORS IN THE SOFFIT OF CONCRETE OVER
1
STEEL DECK FLOOR AND ROOF ASSEMBLIES (SEE DIMENSIONAL PROFILE REQUIREMENTS)
1
Anchors may be placed in the upper flute or lower flute of the steel deck profiles in accordance with Figure 5A provided the minimum hole clearance is satisfied.
Anchors in the lower flute of Figure 5A profiles may be installed with a maximum 1-inch offset in either direction from the center of the flute. The offset distance
may be increased proportionally for profiles with lower flute widths greater than those shown provided the minimum lower flute edge distance is also satisfied. In
addition, the anchors must have an axial spacing along the flute equal to the greater of 3hef or 1.5 times the flute width.

FIGURE 5BPOWER-STUD+ SD1 INSTALLATION DETAIL FOR ANCHORS IN THE SOFFIT OF CONCRETE OVER
1,2
STEEL DECK FLOOR AND ROOF ASSEMBLIES (SEE DIMENSIONAL PROFILE REQUIREMENTS)
1
Anchors may be placed in the lower flute of the steel deck profiles in accordance with Figure 5B provided the minimum hole clearance is satisfied. Anchors in the
lower flute of Figure 5B profiles may be installed with a maximum 1/8-inch offset in either direction from the center of the flute. The offset distance may be increased
proportionally for profiles with lower flute widths greater than those shown provided the minimum lower flute edge distance is also satisfied. In addition, the anchors
must have an axial spacing along the flute equal to the greater of 3hef or 1.5 times the flute width.
2
Anchors may be placed in the upper flute of the steel deck profiles in accordance with Figure 5B provided the concrete thickness above the upper flute is
minimum 31/4-inch and a minimum hole clearance of 3/4-inch is satisfied.

1
FIGURE 6INTERPOLATION OF MINIMUM EDGE DISTANCE AND ANCHOR SPACING
1
This interpolation applies to the cases when two sets of minimum edge distances, cmin, and minimum spacing distances, smin, are given in Table 1 for a given
anchor diameter under the same effective embedment depth, hef, and corresponding minimum member thickness, hmin.
ESR-2818 | Most Widely Accepted and Trusted Page 9 of 13

TABLE 2TENSION DESIGN INFORMATION FOR POWER-STUD+ SD1 ANCHOR IN CONCRETE


1,2
(For use with load combinations taken from ACI 318-14 Section 5.3 or ACI 318 -11 Section 9.2)
Nominal Anchor Diameter
Design Characteristic Notation Units 1 3 1 5 3 7
/4 inch /8 inch /2 inch /8 inch /4 inch /8 inch 1 inch 11/4 inch
Anchor category 1, 2 or 3 - 1 1 1 1 1 1 1 1
4
STEEL STRENGTH IN TENSION
ksi 88.0 88.0 80.0 80.0 64.0 58.0 58.0 58.0
Minimum specified yield strength (neck) fya
(N/mm2) (606) (606) (551) (551) (441) (400) (400) (400)
Minimum specified ultimate tensile strength ksi 110.0 110.0 100.0 100.0 80.0 75.0 75.0 75.0
futa12
(neck) (N/mm2) (758) (758) (689) (689) (552) (517) (517) (517)
in2 0.0220 0.0531 0.1018 0.1626 0.2376 0.327 0.4300 0.762
Effective tensile stress area (neck) Ase,N
(mm2) (14.2) (34.3) (65.7) (104.9) (150.9) (207.5) (273.1) (484)
lb 2,255 5,455 9,080 14,465 19,000 24,500 32,250 56,200
Steel strength in tension4 Nsa
(kN) (10.0) (24.3) (40.4) (64.3) (84.5) (109.0) (143.5) (250)
Reduction factor for steel strength 3
- 0.75
8
CONCRETE BREAKOUT STRENGTH IN TENSION
in. 1.50 2.00 2.00 3.25 2.75 4.00 3.125 4.75 3.50 4.375 5.375
Effective embedment depth hef
(mm) (38) (51) (51) (83) (70) (102) (79) (114) (89) (111) (137)
Effectiveness factor for uncracked concrete kuncr - 24 24 24 24 24 24 24 24 27
Not
Effectiveness factor for cracked concrete kcr - 17 17 17 21 17 21 24 24
Applicable
Modification factor for cracked and uncracked
c,N - 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
concrete5
Critical edge distance (uncracked concrete in.
cac See Table 1
only) (mm)
3
Reduction factor for concrete breakout strength - 0.65 (Condition B)
PULLOUT STRENGTH IN TENSION (NON SEISMIC-APPLICATIONS)8,9

Characteristic pullout strength, uncracked lb See 2,865 3,220 5,530 See See See See See See
Np,uncr
concrete (2,500 psi)6 (kN) note 7 (12.8) (14.3) (24.6) note 7 note 7 note 7 note 7 note 7 note 7
Characteristic pullout strength, cracked lb Not 2,035 See 2,505 See 4,450 See See See 11,350
Np,cr
concrete (2,500 psi)6 (kN) Applicable (9.1) note 7 (11.2) note 7 (19.8) note 7 note 7 note 7 (50.5)
Reduction factor for pullout strength3 - 0.65 (Condition B)

PULLOUT STRENGTH IN TENSION FOR SEISMIC APPLICATIONS8,9


Characteristic pullout strength, seismic lb Not 2,035 See 2,505 See 4,450 See See See 11,350
Np,eq
(2,500 psi)6,10 (kN) Applicable (9.1) note 7 (11.1) note 7 (19.8) note 7 note 7 note 7 (50.5)
Reduction factor for pullout strength, seismic3 - 0.65 (Condition B)
PULLOUT STRENGTH IN TENSION FOR ANCHORS INSTALLED THROUGH THE SOFFIT OF
SAND-LIGHTWEIGHT AND NORMAL-WEIGHT CONCRETE OVER STEEL DECK
Characteristic pullout strength, uncracked lb 1,940 3,205 2,795 3,230
Np,deck,uncr
concrete over steel deck(Figure 5A)6,11 (kN) (8.6) (14.2) (12.4) (14.4)
Characteristic pullout strength, cracked lb 1,375 2,390 1,980 2,825
Np,deck,cr
concrete over steel deck(Figure 5A)6,11 (kN) (6.1) (10.6) (8.8) (12.4)
Not Applicable

Not Applicable

Not Applicable

Not Applicable
Characteristic pullout strength, cracked lb 1,375 2,390 1,980 2,825
N
concrete over steel deck, seismic (Figure 5A)6,11 p,deck,eq (kN) (6.1) (10.6) (8.8) (12.4)
Characteristic pullout strength, uncracked lb 1,665 1,900
Not Applicable

Np,deck,uncr
concrete over steel deck (Figure 5B)6,11 (kN) (7.4) (8.5)
Applicable

Characteristic pullout strength, cracked lb 1,180 1,420


Not

Np,deck,cr
concrete over steel deck (Figure 5B)6,11 (kN) (5.2) (6.3)
Characteristic pullout strength, cracked lb 1,180 1,420
N
concrete over steel deck, seismic (Figure 5B)6,11 p,deck,eq (kN) (5.2) (6.3)
Reduction factor for pullout strength, steel deck3 - 0.65 (Condition B)
For SI: 1 inch = 25.4 mm; 1 ksi = 6.894 N/mm2; 1 lbf = 0.0044 kN.
1
The data in this table is intended to be used with the design provisions of ACI 318-14 Chapter 17 or ACI 318 -11 Appendix D, as applicable; for anchors resisting seismic
load combinations the additional requirements of ACI 318-14 17.2.3 or ACI 318-11 D.3.3, as applicable, must apply.
2
Installation must comply with published instructions and details.
3
All values of apply to the load combinations of IBC Section 1605.2, ACI 318-14 Section 5.3 or ACI 318-11 Section 9.2, as applicable. If the load combinations of ACI 318-
11 Appendix C are used, then the appropriate value of must be determined in accordance with ACI 318-11 D4.4. For reinforcement that meets ACI 318-14 Chapter 17 or
ACI 318-11 Appendix D requirements for Condition A, see ACI 318-14 17.3.3(c) or ACI 318-11 D.4.3(c), as applicable, for the appropriate factor when the load
combinations of IBC Section 1605.2, ACI 318-14 Section 5.3 or ACI 318-11 Section 9.2, as applicable, are used.
4
The Power-Stud+ SD1 is considered a ductile steel element as defined by ACI 318-14 2.3 or ACI 318-11 D.1, as applicable. Tabulated values for steel strength in tension
are based on test results per ACI 355.2 and must be used for design.
5
For all design cases use c,N = 1.0. The appropriate effectiveness factor for cracked concrete (kcr) or uncracked concrete (kuncr) must be used.
6
For all design cases use c,P = 1.0. For the calculation of Npn, see Section 4.1.4 of this report.
7
Pullout strength does not control design of indicated anchors. Do not calculate pullout strength for indicated anchor size and embedment.
8
Anchors are permitted to be used in lightweight concrete in accordance with Section 4.1.12 of this report.
9
For anchors in the topside of concrete-filled steel deck assemblies, see Figure 4.
10
Tabulated values for characteristic pullout strength in tension are for seismic applications and based on test results in accordance with ACI 355.2, Section 9.5.
11
Values for Np,deck are for sand-lightweight concrete (f'c, min = 3,000 psi) and additional lightweight concrete reduction factors need not be applied. In addition, evaluation for
the concrete breakout capacity in accordance with ACI 318-14 17.4.2 or ACI 318-11 D.5.2, as applicable, is not required for anchors installed in the deck soffit (flute).
ESR-2818 | Most Widely Accepted and Trusted Page 10 of 13

TABLE 3SHEAR DESIGN INFORMATION FOR POWER-STUD+ SD1 ANCHOR IN CONCRETE


1,2
(For use with load combinations taken from ACI 318-14 Section 5.3 or ACI 318-11, Section 9.2)
Nominal Anchor Diameter
Design Characteristic Notation Units 1 3 1 5 3 7 11/4
/4 inch /8 inch /2 inch /8 inch /4 inch /8 inch 1 inch
inch
Anchor category 1, 2 or 3 - 1 1 1 1 1 1 1 1
STEEL STRENGTH IN SHEAR4
ksi 70.0 80.0 70.4 70.4 64.0 58.0 58.0 58.0
Minimum specified yield strength (threads) fya
(N/mm2) (482) (552) (485) (485) (441) (400) (400) (400)
ksi 88.0 100.0 88.0 88.0 80.0 75.0 75.0 75.0
Minimum specified ultimate strength (threads) futa11
(N/mm2) (606) (689) (607) (607) (552) (517) (517) (517)
in2 0.0318 0.0775 0.1419 0.2260 0.3345 0.462 0.6060 0.969
Effective tensile stress area (threads) Ase,V
(mm2) (20.5) (50.0) (91.5) (145.8) (212.4) (293.4) (384.8) (615)
lb 925 2,990 4,620 9,030 10,640 11,655 8,820 10,935 17,750
Steel strength in shear5 Vsa11
(kN) (4.1) (13.3) (20.6) (40.2) (47.3) (54.8) (39.2) (48.6) (79.0)
Reduction factor for steel strength3 - 0.65
6,7
CONCRETE BREAKOUT STRENGTH IN SHEAR
Load bearing length of anchor 11 in. 1.50 2.00 2.00 3.25 2.75 4.00 3.125 4.75 3.50 4.375 5.375
e
(hef or 8do, whichever is less) (mm) (38) (51) (51) (83) (70) (102) (79) (114) (88.9) (111) (137)
in. 0.250 0.375 0.500 0.625 0.750 0.875 1.000 1.25
Nominal anchor diameter da [do]12
(mm) (6.4) (9.5) (12.7) (15.9) (19.1) (22.2) (25.4) (31.8)
3
Reduction factor for concrete breakout - 0.70 (Condition B)

PRYOUT STRENGTH IN SHEAR6,7

Coefficient for pryout strength


kcp - 1.0 1.0 1.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
(1.0 for hef < 2.5 in., 2.0 for hef 2.5 in.)
in. 1.50 2.00
2.75 4.00 3.125 2.00 3.25 4.75 3.50 4.375 5.375
Effective embedment hef
(mm) (38) (51)
(70) (102) (79) (51) (83) (114) (88.9) (111) (137)
Reduction factor for pryout strength3 - 0.70 (Condition B)
STEEL STRENGTH IN SHEAR FOR SEISMIC APPLICATIONS
lb Not 2,440 3,960 6,000 8,580 9,635 8,820 9,845 17,750
Steel strength in shear, seismic8 Vsa,eq11
(kN) Applicable (10.9) (17.6) (26.7) (38.2) (42.9) (39.2) (43.8) (79.0)
Reduction factor for steel strength in shear for
- 0.65
seismic3
STEEL STRENGTH IN SHEAR FOR ANCHORS INSTALLED THROUGH THE SOFFIT OF
SAND-LIGHTWEIGHT AND NORMAL-WEIGHT CONCRETE OVER STEEL DECK9,10
Steel strength in shear, concrete over steel deck lb 2,120 2,290 3,710 5,505
Vsa,deck
(Figure 5A)9 (kN) (9.4) (10.2) (16.5) (24.5)
Not Applicable

Not Applicable

Not Applicable

Not Applicable
Steel strength in shear, concrete over steel deck, lb 2,120 2,290 3,710 4,570
Vsa,deck,eq
seismic (Figure 5A)9 (kN) (9.4) (10.2) (16.5) (20.3)

Steel strength in shear, concrete over steel deck lb 2,120 2,785


Applicable

Applicable
Vsa,deck
(Figure 5B)9 (kN) (9.4) (12.4)
Not

Not

Steel strength in shear, concrete over steel deck, lb 2,120 2,785


Vsa,deck,eq
seismic (Figure 5B)9 (kN) (9.4) (12.4)
Reduction factor for steel strength in shear, steel
- 0.65
deck3
2
For SI: 1 inch = 25.4 mm; 1 ksi = 6.894 N/mm ; 1 lbf = 0.0044 kN.
1
The data in this table is intended to be used with the design provisions of ACI 318-14 Chapter 17 or ACI 318-11 Appendix D, as applicable; for anchors resisting
seismic load combinations the additional requirements of ACI 318-14 17.2.3 or ACI 318-11 D.3.3, as applicable, must apply.
2
Installation must comply with published instructions and details.
3
All values of were determined from the load combinations of IBC Section 1605.2, ACI 318-14 Section 5.3 or ACI 318-11 Section 9.2. If the load combinations of ACI
318-11 Appendix C are used, then the appropriate value of must be determined in accordance with ACI 318-11 D.4.4. For reinforcement that meets ACI 318-14
Chapter 17 or ACI 318-11 Appendix D requirements for Condition A, see ACI 318-14 17.3.3(c) or ACI 318-11 D.4.3(c), as applicable, for the appropriate factor when
the load combinations of IBC Section 1605.2, ACI 318-14 Section 5.3 or ACI 318-11 Section 9.2, as applicable, are used.
4
The Power-Stud+ SD1 is considered a ductile steel element as defined by ACI 318-14 2.3 or ACI 318-11 D.1, as applicable.
5
Tabulated values for steel strength in shear must be used for design. These tabulated values are lower than calculated results using equation D-20 in ACI 318-08.
6
Anchors are permitted to be used in lightweight concrete in accordance with Section 4.1.12 of this report.
7
For anchors in the topside of concrete-filled steel deck assemblies, see Figure 4.
8
Tabulated values for steel strength in shear are for seismic applications and based on test results in accordance with ACI 355.2, Section 9.6.
9
Tabulated values for Vsa,deck and Vsa,deck,eq are for sand-lightweight concrete (f'c, min = 3,000 psi); additional lightweight concrete reduction factors need not be applied. In
addition, evaluation for the concrete breakout capacity in accordance with ACI 318-14 17.5.2 or ACI 318-11 D.6.2, as applicable, and the pryout capacity in accordance
with ACI 318-14 17.5.3 or ACI 318-11 D.6.3, as applicable, are not required for anchors installed in the deck soffit (flute).
10
Shear loads for anchors installed through steel deck into concrete may be applied in any direction.
ESR-2818 | Most Widely Accepted and Trusted Page 11 of 13
1,2,3,4,5,6,7,8,9
TABLE 4EXAMPLE ALLOWABLE STRESS DESIGN VALUES FOR ILLUSTRATIVE PURPOSES

Anchor Diameter Nominal Embedment Depth Effective Embedment Allowable Tension Load
(inches) (inches) (inches) (pounds)
1 3
/4 1 /4 1.50 970
3 3
/8 2 /8 2.00 1,260
1
1 2 /2 2.00 1,415
/2 3
3 /4 3.25 2,425
3
5 3 /8 2.75 2,405
/8 5
4 /8 4.00 4,215
3 4 3.125 2,910
/4 5
5 /8 4.75 5,455
7 1
/8 4 /2 3.50 3,450
1
1 5 /2 4.375 4,820
1 1
1 /4 6 /2 5.375 7,385

For SI: 1 inch = 25.4 mm, 1 lbf = 4.45 N.


1
Single anchor with static tension load only.
2
Concrete determined to remain uncracked for the life of the anchorage.
3
Load combinations are taken from ACI 318-14 Section 5.3 or ACI 318-11 Section 9.2, as applicable (no seismic loading).
4
30% dead load and 70% live load, controlling load combination 1.2D + 1.6L.
5
Calculation of weighted average for conversion factor = 1.2(0.3) + 1.6(0.7) = 1.48.
6
f'c = 2,500 psi (normal weight concrete).
7
ca1 = ca2 cac.
8
h hmin.
9
Values are for Condition B where supplementary reinforcement in accordance with ACI 318-14 17.3.3 or ACI 318-11 D.4.3, as applicable, is not provided.

Given: Calculate the factored resistance strength, , and the allowable stress design value,
Tallowable,ASD, for a 3/8-inch-diameter Power-Stud+ SD1 anchor assuming the given conditions in
Table 4.

318-14 318-11
Calculation in accordance with ACI 318-14, ACI 318-11 Appendix D and this report: Report Ref.
Ref. Ref.
Step 1. Calculate steel strength of a single anchor in tension:
17.4.1.2 D.5.1.2 Table 2
0.75 5,455 4,091 .
Step 2. Calculate concrete breakout strength of a single anchor in tension:

, , ,

.
17.4.2.1 D.5.2.1 Table 2
.
24 1.0 2,500 2.0 3,394 .
36.0
0.65 1.0 1.0 1.0 3,394 2,206 .
36.0
Step 3. Calculate pullout strength of a single anchor:
,
, , 17.4.3.2 D.5.3.2 Table 2
2,500
.
0.65 2,865 1.0 1.0 1,862 .
Step 4. Determine controlling factored resistance strength in tension:
17.3.1.1 D.4.1.1 -
min , , 1,862 .
Step 5. Calculate allowable stress design conversion factor for loading condition:
Controlling load combination: 1.2D + 1.6L 5.3 9.2 -
= 1.2(30%) + 1.6(70%) = 1.48
Step 6. Calculate the converted allowable stress design value:
, - - Section 4.2
, , .
.

FIGURE 7EXAMPLE STRENGTH DESIGN CALCULATION INCLUDING ASD CONVERSION FOR ILLUSTRATIVE PURPOSES
ESR-2818 | Most Widely Accepted and Trusted Page 12 of 13

Given:
1
Two /2PowerStud+SD1anchors
Concretecompressivestrength:
(fc)=4,000psi
Nosupplementalreinforcement:
(ConditionBperACI3181417.3.3c
orACI31811D.4.3c)
Assumecrackedconcrete,noseismic,
noloadingeccentricityandarigid
plate
1

ha=4.0in.
hef=2.0in.
sa=4.5in.
ca1=ca,min=6.0in.
ca21.5ca1
Calculatethefactoredresistancedesignstrengthintensionandequivalentallowablestressdesignloadfortheconfiguration.
31811 Report
CalculationinaccordancewithACI31814,ACI31811andthisreport: 31814Ref.
Ref. Ref.
Step1.Verifyminimummemberthickness,spacingandedgedistance:
ha=4.0in.hmin=4.0in.OK
17.7 D.8 Table1
sa=4.5in.smin=4.5in.OK
ca,min=6.0in.cmin=6.0in.OK
Step2.Calculatesteelstrengthofanchorgroupintension:Nsag=nNsa=29,080lbs.=18,160lbs. 4.1.2
17.4.1.2 D.5.1.2
Calculatesteelcapacity:Nsag=0.7518,160lbs.=13,620lbs. Table2
Step3.Calculateconcretebreakoutstrengthofanchorgroupintension:
17.4.2.1(b) D.5.2.1(b) 4.1.3
, , , ,

Step3a.CalculateANcoandANc
2 2 2
ANco=9hef =9(2.0) =36.0in. 17.4.2.1(b) D.5.2.1(b) Table1
Anc=(3.0hef)(3.0hef+sa)=(3.02.0)((3.02.0)+4.5)=63.0in.2 ANc=63.0in.2
Step3b.Calculateec,N= 1.0;eN=0ec,N=1.0
17.4.2.4 D.5.2.4
,
Step3c.Calculateed,N=1.0ifca,min1.5hef;ed,N=0.7 0.3 ifca,min<1.5hef
. 17.4.2.5 D.5.2.5 Table1
ca,min=6.0in.1.5hef=3.0in.ed,N=1.0
Step3d.Calculatec,N=1.0 17.4.2.6 D.5.2.6 Table2
Step3e.Calculatecp,N=1.0(crackedconcrete) 17.4.2.7 D.5.2.7
.
Step3f.CalculateNb= =17 1.0 4,000 2.0 . =3,041lbs. 17.4.2.2 D.5.2.2 Table2
Step3g.Calculateconcretebreakoutstrengthofanchorgroupintension:
Ncbg=(63.0/36.0)1.01.01.01.03,041=5,321lbs. 17.4.2.1(b) D.5.2.1(b) 4.1.3
Calculateconcretebreakoutcapacity=Ncbg=0.655,321=3,459lbs.
Step4.Calculatenominalpulloutstrengthofasingleanchorintension: 4.1.4
17.4.3.1 D.5.3.1
Npn=c,PNpn,fc Table2
4.1.10
Step4a.Calculatec,P=1.0(crackedconcrete) 17.4.3.6 D.5.3.6
Table2
.
Step4b.CalculateNpn,fc=Np,cr =perTable2ofthereport,pulloutdoesnotcontrol; 4.1.4
17.4.3.2 D.5.3.2
Donotcalculatepulloutcapacity Table2
Step5.Determinecontrollingresistancestrengthoftheanchorgroupintension:
17.3.1.1 D.4.1.1 4.1.1
Nn=min , , n =Ncbg=3,459lbs.
Step6. Calculateallowablestressdesignconversionfactorforloadingcondition:
Assumecontrollingloadcombination:1.2D+1.6L;50%DeadLoad,50%LiveLoad 5.3 9.2 4.2.1
=1.2(50%)+1.6(50%)=1.40
Step7. Calculateallowablestressdesignvalue:
, 5.3 9.2 4.2.1
, . =2,470lbs.

FIGURE 8EXAMPLE STRENGTH DESIGN CALCULATION FOR TENSION CAPACITY


ESR-2818 | Most Widely Accepted and Trusted Page 13 of 13

Given:
1
Two /2PowerStud+SD1anchors
Concretecompressivestrength:
(fc)=4,000psi
Nosupplementalreinforcement:
(ConditionBperACI3181417.3.3(c)
orACI31811D.4.3(c)
Assumecrackedconcrete,noseismic,
noloadingeccentricityandarigid
plate
1
ha=4.0in.
hef=2.0in.
sa=4.5in.

ca1=ca,min=6.0in.
ca21.5ca1
Calculatethefactoredresistancedesignstrengthinshearandequivalentallowablestressdesignloadfortheconfiguration.
31814Ref. 31811 Report
CalculationinaccordancewithACI31814,ACI31811andthisreport:
Ref. Ref.
Step1.Verifyminimummemberthickness,spacingandedgedistance:
ha=4.0in.hmin=4.0in.OK
17.7 D.8 Table1
sa=4.5in.smin=4.5in.OK
ca,min=6.0in.cmin=6.0in.OK
Step2.Calculatesteelstrengthofanchorgroupinshear:Vsag =nVsa =2 4,620 lbs.=9,240 lbs. 4.1.5
17.5.1.2 D.6.1.2
Calculatesteelcapacity:Vsag=0.659,240lbs.=6,006lbs. Table3
Step3.Calculateconcretebreakoutstrengthofanchorgroupinshear:
17.5.2.1(b) D.6.2.1(b) 4.1.6
, , , ,

Step3a.CalculateAVcoandAVc
AVco=4.5(ca1)2=4.5(6.0)2=162.0in.2 17.5.2.1 D.6.2.1 Table1
AVc=(ha)(3ca1+sa)=(4.0)((36.0)+4.5)=90.0in.2
Step3b.Calculateec,V= 1.0;eV=0ec,V=1.0 17.5.2.5 D.6.2.5

Step3c.Calculateed,V=1.0ifca21.5ca1;ed,V=0.7 0.3 ifca2<1.5ca1


. 17.5.2.6 D.6.2.6 Table1
ca21.5ca1ed,V=1.0
Step3d.Calculatec,V=1.0(crackedconcrete,nosupplementaloredgereinforcement) 17.5.2.7 D.6.2.7
.
Step3e.Calculateh,V= ;formemberswhereha<1.5ca1
17.5.2.8 D.6.2.8
.
ha=4.0<1.5ca1=9.0h,V= .
=1.5
. . .
Step3f.CalculateVb= 7 .
=7 .
0.5 1.0 4000 6.0 .

17.5.2.2 D.6.2.2 Table2
=6,071lbs.
Step3g.Calculateconcretebreakoutstrengthofanchorgroupinshear:
Vcbg=(90.0/162.0)1.01.01.01.56,071=5,059lbs. 17.5.2.1(b) D.6.2.1(b) 4.1.6
Calculateconcretebreakoutcapacity=Vcbg=0.704,641=3,542lbs.
Step4.Calculatenominalpryoutstrengthofananchorgroupinshear:
4.1.7
Vcpg = kcpNcbg =1.05,321lbs=5,321lbs. 17.5.3.1(b) D.6.3.1(b)
Table3
Calculatepryoutcapacity:Vcpg=0.705,321lbs.=3,724lbs.
Step5.Determinecontrollingresistancestrengthinshear:
17.3.1.1 D.4.1.1 4.1.1
Vn=min , , =Vcbg=3,542lbs.
Step6. Calculateallowablestressdesignconversionfactorforloadingcondition:
Assumecontrollingloadcombination:1.2D+1.6L;50%DeadLoad,50%LiveLoad 5.3 9.2 4.2.1
=1.2(30%)+1.6(70%)=1.40
Step7. Calculateallowablestressdesignvalue:
, 5.3 9.2 4.2.1
, .
=2,530lbs.

FIGURE 9EXAMPLE STRENGTH DESIGN CALCULATION FOR SHEAR CAPACITY


ESR-2818 | Most
E M Widely Acc
cepted and Tru
usted Pag
ge 14 of 14

Givven:
Two o1/2PowerStu ud+SD1anchorss
Con ncretecompresssivestrength:
(fc)=4,000psi
Nosupplementalre einforcement:
(CoonditionBperAC CI3181417.3.3 3(c)
orAACI31811D.4.3 3(c)
Assumecrackedconcrete,noseism mic,
noloadingeccentricityandarigid
platte
1
ha==4.0in.
hef==2.0in.
sa==4.5in.

ca1==ca,min=6.0in.
ca21.5ca1
Calculatethefactorredresistancede esignstrengthinnshearandequuivalentallowab
blestressdesignnloadforthecoonfiguration.
31814R Ref. 31811 Report
CalcculationinaccordancewithACI31814,ACI31 1811andthisreeport:
Ref. Ref.
Step1.Verifyminim mummemberth hickness,spacinggandedgedistaance:
OK
ha=4.0in..hmin=4.0in.
17.77 D.8 Table1
OK
sa=4.5in.smin=4.5in.
ca,min=6.0in.cmin=6.0in
n.OK
Step2.Calculatestteelstrengthofaanchorgroupinshear:Vsag =nVsa =2 4,620 lbbs.=9,240 lbs. 4.1.5
17.5.11.2 D.6.1.22
Calculatessteelcapacity:Vsag=0.659,24 40lbs.=6,006lb
bs. Table3
Step3.Calculateco
oncretebreakou
utstrengthofanchorgroupinsh
hear:
17.5.2.11(b) D.6.2.1(b
b) 4.1.6
, , , ,

Step3a.CalculateA AVcoandAVc
AVco=4.5((ca1)2=4.5(6.0
0)2=162.0in.2 17.5.22.1 D.6.2.11 Table1
0)((36.0)+4.5)=90.0in.2
AVc=(ha)(3ca1+sa)=(4.0
Step3b.Calculate
ec,V= 1.0;eV=0
ec,V=1.0 17.5.22.5 D.6.2.55

Step3c.Calculate
ed,V=1.0ifca21.5c
0.7
a1;ed,V=0 0.3 ifca2<1.5ca1
. 17.5.22.6 D.6.2.66 Table1
ca21.5ca1ed,V=1.0
Step3d.Calculatec,V=1.0(cracke
edconcrete,nosupplementalo
oredgereinforceement) 17.5.22.7 D.6.2.77
.
Step3e.Calculate
h,V= ;fformemberswh
hereha<1.5ca1
17.5.22.8 D.6.2.88
.
ha=4.0<
<1.5ca1=9.0
h,V= .
=1.5
. . .
Vb= 7
Step3f.CalculateV .
=7 .
0.5 1.0 40 00 6.0 .

17.5.22.2 D.6.2.22 Table2
=6,071lbss.
Step3g.Calculatecconcretebreako outstrengthofanchorgroupinsshear:
Vcbg=(90.0
0/162.0)1.01.0
1 1.01.56,071=5,059lbs. 17.5.2.11(b) D.6.2.1(b
b) 4.1.6
Calculatecconcretebreakoutcapacity=Vcbg=0.704,641 1=3,542lbs.
Step4.Calculatenoominalpryoutsttrengthofananchorgroupinsh hear:
4.1.7
Vcpg = kcpNcbg =1.05,321lbs=5,321lbs. 17.5.3.11(b) D.6.3.1(b
b)
Table3
Calculateppryoutcapacity:Vcpg=0.705,,321lbs.=3,7244lbs.
Step5.Determinecontrollingresistancestrengthinshear:
17.3.11.1 D.4.1.1 4.1.1
Vn=min , , =Vcbg=3,542lbs.
Step6. Calculateallowablestressd designconversio onfactorforload
dingcondition:
Assumeco ontrollingloadcoombination:1.2D DeadLoad,50%LLiveLoad
D+1.6L;50%D 5.3 9.2 4.2.1
=1.2(30%%)+1.6(70%)=1.40
Step7. Calculateallowablestressd designvalue:
, 5.3 9.2 4.2.1
, =2,530lbs.
.
FIGUR
RE 9EXAMPLE
E STRENGTH DESIGN CALCUL
LATION FOR SH
HEAR CAPACIT
TY
ICC-ES Evaluation Report ESR-2818 FBC Supplement
Reissued December 2016
This report is subject to renewal December 2017.

www.icc-es.org | (800) 423-6587 | (562) 699-0543 A Subsidiary of the International Code Council

DIVISION: 03 00 00CONCRETE
Section: 03 16 00Concrete Anchors

DIVISION: 05 00 00METALS
Section: 05 05 19Post-Installed Concrete Anchors

REPORT HOLDER:

DEWALT
701 EAST JOPPA ROAD
TOWSON, MARYLAND 21286
(800) 524-3244
www.dewalt.com
engineering@powers.com

EVALUATION SUBJECT:

POWER-STUD+ SD1 EXPANSION ANCHORS FOR CRACKED AND UNCRACKED CONCRETE

1.0 REPORT PURPOSE AND SCOPE


Purpose:
The purpose of this evaluation report supplement is to indicate that the Powers Power-Stud+ SD1 Expansion Anchors in
1 3 1
uncracked concrete only [ /4 inch (6.4 mm)] and in cracked and uncracked concrete [ /8 inch to 1 /4 inches (9.5 mm to
31.8 mm)], recognized in ICC-ES master evaluation report ESR-2818, have also been evaluated for compliance with the
codes noted below.
Applicable code editions:
2014 and 2010 Florida Building CodeBuilding
2014 and 2010 Florida Building CodeResidential
2.0 CONCLUSIONS
The Powers Power-Stud+ SD1 Expansion Anchors in uncracked concrete only [1/4 inch (6.4 mm)] and in cracked and
uncracked concrete [3/8 inch to 11/4 inches (9.5 mm to 31.8 mm)], described in master evaluation report ESR-2818, comply
with the 2014 and 2010 Florida Building CodeBuilding and the 2014 and 2010 Florida Building CodeResidential, when

designed and installed in accordance with the 2012 International Building Code provisions noted in the master report, and
under the following conditions:
Design wind loads must be based on Section 1609 of the 2014 and 2010 Florida Building CodeBuilding or Section
R301.2.1.1 of the 2014 and 2010 Florida Building CodeResidential, as applicable.
Load combinations must be in accordance with Section 1605.2 or Section 1605.3 of the 2014 and 2010 Florida Building
CodeBuilding, as applicable.
Use of the Powers Power-Stud+ SD1 Expansion Anchors in uncracked concrete only [1/4 inch (6.4 mm)] and in cracked
3 1
and uncracked concrete [ /8 inch to 1 /4 inches (9.5 mm to 31.8 mm)], for compliance with the High-Velocity Hurricane Zone
Provisions of the 2014 and 2010 Florida Building CodeBuilding and the 2014 and 2010 Florida Building Code
Residential, has not been evaluated, and is outside the scope of this supplement.
For products falling under Florida Rule 9N-3, verification that the report holders quality assurance program is audited by a
quality-assurance entity approved by the Florida Building Commission for the type of inspections being conducted is the
responsibility of an approved validation entity (or the code official when the report holder does not possess an approval by
the Commission).
This supplement expires concurrently with the master report reissued December 2016.

ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed
as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as
to any finding or other matter in this report, or as to any product covered by the report.
1000

Copyright 2016 ICC Evaluation Service, LLC. All rights reserved. Page 1 of 1

You might also like