You are on page 1of 9

MANUAL

Operating Instructions

M700-225/40
480V 60Hz

NEG Micon A/S


Alsvej 21
DK-8900 Randers

English (WP3000)
Index ?

General 1
How to use this manual Page 4 1.1

Safety instructions 5 1.2

How a wind turbine operates 6 1.3

Principal data 7 1.4

Operating and inspection 2


Automatic operation Page 9 2.1

Control panel and display 9 2.2

Emergency stop 9 2.3

Manual yaw 10 2.4

Disrupt power supply 10 2.5

Generator 10 2.6

Wind vane 10 2.7

Twisting of cable 11 2.8

Inspection 11 2.9

3
Electronic Control and Information Displays
Status display Page 12 3.1

Access Rights 13 3.1.1

Exsample 14 3.2

Grid menu 24 3.3

Parameters 25 3.4

NEG Micon M700-225/40 Manual 2


M700-225kw-480v-60hz.P65

Rev. 1998.01.29 OKK


Index ?

Error List Menu Page 26 3.5

Error Count Menu 26 3.6

Event List Menu 27 3.7

Access List Menu 27 3.8

Error Code List 28 3.9

Service and Maintenance 4

Service intervals Page 32 4.1

Service plan 33 4.2

Lubrication 39 4.3

Bolt tightening checklist 40 4.4

Technical Specifications 5

Mechanical construction Page 42 5.1

Electrical construction 43 5.2

Electronic controls 43 5.3

Safety equipment 44 5.4

Abnormal Operating Conditions 6

"Runaway", fire and lightning strike Page 45 6.1

NEG Micon M700-225/40 Manual 3


M700-225kw-480v-60hz.P65

Rev. 1998.01.29 OKK


General 1

How to use this manual 1.1

These user instructions are for the use of turbine


owners who carry out the inspection of their
turbine(s) themselves.

Described within are the procedures necessary


to operate the turbine on a day-to-day basis.
NEG Micon A/S
As will be seen within these instructions, there
will be occasions when it is necessary to contact Alsvej 21
NEG Micon's Service Department, which is DK-8900 Randers
always ready to provide help and assistance.

Such instances are marked thus:  +45 87 10 50 00


Fax +45 87 10 50 01

Operating or repairing the windturbine under


circumstances other than those covered in this
manual may only occur with the prior knowledge
and permission of NEG Micon A/S.

Failure to comply can lead to


invalidation of the guarantee on
damaged components.

Note relevant information here:

The guarantee covering individual components is Address of windturbine


described in full in the Purchase Agreement.

In addition to the inspection procedures that can


be carried out by the windturbine owner, a full
service -inspection must be made within the
guarantee period in accordance with approved
NEG Micon guidelines.

See chapter 4, Maintenance.

It is advisable to carefully read these instructions,


as there may be some points you wish clarified.
In which case you are welcome to contact NEG
Micon A/S.

NEG Micon M700-225/40 Manual 4


M700-225kw-480v-60hz.P65

Rev. 1998.01.29 OKK


General 1

Safety instructions 1.2

NEG Micon turbines are constructed with the


highest regard for safety - both of the turbine itself
and its surroundings.
- if the turbine wings are iced over,
When inside, or in the vicinity of the turbine, there stop the turbine until the ice is remo-
are certain basic safety rules that must always ved
be observed.

When inside the turbine:

- beware of ice falling from the tur-


- there must be at least two people bine, wear a safety helmet
present

- stop the turbine and


disconnect the power - always keep the turbine locked
against intruders

- always use safety belts when


ascending and descending
ABNORMAL OPERATING
CONDITIONS
See chapter 6

- wear a safety helmet

- remember to close all platform


trapdoors

NEG Micon M700-225/40 Manual 5


M700-225kw-480v-60hz.P65

Rev. 1998.01.29 OKK


General 1

How a wind turbine operates 1.3

WIND BECOMES ELECTRICITY

Windpower is clean energy.

As soon as the speed of the wind exceeds approx. 3m/


sec., the turbine wings (A) begin to rotate. Power is transfer-
red via the main shaft (B) to the gear box (C), where the
number of revolutions are increased to suit the genera-
tor's capacity(D). The wind vane (E), ensures via the yaw
mechanism (F) that the turbine module is always
positioned to derive the maximum benefit from the wind's
direction. All the turbine's functions can be controlled and
at any time checked via the central computer's control
panel (G), which together with NEG Micon's well-proven
and sturdy mechanism, guarantees reliable production
and minimal maintenance year after year.

For detailed technical data, see the following pages


and chapter 5, Technical Specifications.

NEG Micon M700-225/40 Manual 6


M700-225kw-480v-60hz.P65

Rev. 1998.01.29 OKK


General 1

Principal data 1.4

NM225/30

ROTOR DIAMETER () 29.8 m


SWEPT AREA 697 m2
HUB HEIGHT (NH) 30 / 36 m
GENERATOR OUTPUT 225/40 kW
ROTOR REVOLUTIONS 38 / 25 rpm
OUTPUT REGULATION Stall

BLADES:(POS. 2)
TOTAL 3 pcs.
CONSTRUCTION LM
TYPE LM 13.4
BRAKE Centrifugal sensor

TOWER (POS . 3)
TYPE 24-edged conical tower
HEIGHT 28.7/34.7 m
SURFACE TREATMENT Painted

WEIGHT
ROTOR 4.7 t
NACELLE (POS. 1) 12 t
TOWER 14 / 18 t

NEG Micon M700-225/40 Manual 7


M700-225kw-480v-60hz.P65

Rev. 1998.01.29 OKK


General 1

Principal data 1.4

1. Blade hub
2. Main bearing,
with flexible
suspension
3. Main shaft
4. "Park" brake
5. Yaw ring
6. Yaw gear
7. Yaw brake
8. Gear, flexible
suspension
9. Gear
10. Disc brake
11. Brake Hydr.
12. Flexible coupling
14 15
13. Generator
14. Wind vane
15. Anemometer

1. Control panel 1234567890123


1234567890123
2. Ladder 1234567890123
1234567890123
1234567890123
3. Entrance 1234567890123
1

NEG Micon M700-225/40 Manual 8


M700-225kw-480v-60hz.P65

Rev. 1998.01.29 OKK


Operation and inspection 2

Automatic operation 2.1 2.2

The wind turbine is equipped with a computer which


monitors the running of the turbine, making it un-
necessary to operate the turbine manually.
Should a fault occur with the turbine or the elec-
tricity grid, the turbine will stop, and the nature of
the fault can be seen on the control panel

See chapter 3, Status Displays

Individual faults and their remedies are described


under "Fault Description".

See chapter 3.5

After certain types of fault have occurred, the


windturbine will restart automatically once the cen-
tral computer has checked the turbine and the
2.3
electricity grid.

NEG Micon M700-225/40 Manual 9


M700-225kw-480v-60hz.P65

Rev. 1998.01.29 OKK