Professional Documents
Culture Documents
Author
Florian Fink | florian.fink@omicron.at
Date
March 18, 2015
Application Area
Auto-reclose
Keywords
RelaySimTest, System Testing
Version
v1.0
Document ID
ANS_15003_ENU
Abstract
Due to the increasing complexity of our electrical power systems, the need for highly selective protection is
increasingly being fulfilled by the use of multifunctional relays. Most of these multifunctional relays provide
an auto-reclose function. To test this protection function thoroughly, an application oriented approach is
strongly advisable.
This application note describes how this could be done in an easy and comfortable way using the OMICRON
RelaySimTest software. To perform an application oriented test, a fault scenario is calculated based on the
simulation of the power system network. Within one simulation step voltages and currents for different
locations can be calculated to test the important coordination of the auto-reclose functions over multiple
relays. RelaySimTest offers the possibility to inject the signals through several distributed and time
synchronized CMC test sets.
OMICRON Page 1 of 22
General information
OMICRON electronics GmbH including all international branch offices is henceforth referred to as
OMICRON.
The product information, specifications, and technical data embodied in this application note represent the
technical status at the time of writing and are subject to change without prior notice.
We have done our best to ensure that the information given in this application note is useful, accurate and
entirely reliable. However, OMICRON does not assume responsibility for any inaccuracies which may be
present.
OMICRON translates this application note from the source language English into a number of other
languages. Any translation of this document is done for local requirements, and in the event of a dispute
between the English and a non-English version, the English version of this note shall govern.
All rights including translation reserved. Reproduction of any kind, for example, photocopying, microfilming,
optical character recognition and/or storage in electronic data processing systems, requires the explicit
consent of OMICRON. Reprinting, wholly or partly, is not permitted.
OMICRON 2015. All rights reserved. This application note is a publication of OMICRON.
DANGER
Death or severe injury caused by high voltage or current if the respective
protective measures are not complied.
Carefully read and understand the content of this application note as well as
the manuals of the involved systems before starting its practical application.
Please contact OMICRON before you continue the process if you do not
understand the safety instructions, operating instructions, or parts of it.
Follow each instruction mentioned there especially the safety instructions
since this is the only way to avoid danger that can occur when working at
high voltage or high current systems.
Furthermore, only use the involved equipment according to its intended
purpose to guarantee a safe operation.
Existing national safety standards for accident prevention and
environmental protection may supplement the equipments manual.
Only experienced and competent professionals that are trained for working in high voltage or high current
environments may perform this application note. Additional the following qualifications are required:
Authorized to work in environments of energy generation, transmission or distribution and familiar
with the approved operating practices in such environments.
Familiar with the five safety rules.
Good knowledge of CMC test sets.
Before you get started with this application note, read the Getting started manual [1] of RelaySimTest.
Please make sure that you also have a good knowledge about the CMC test system.
The application note describes how an auto-reclose function could be tested using the Iterative Closed Loop
function of RelaySimTest. Therefore it shows the following content:
1. Automatic reclose function (general information)
2. Defining the System under Test
3. Defining test cases
4. Overview about the hardware test setup
5. Defining the Test sets configuration
The application note does not describe parameter tests. To test the protection thoroughly such tests are
also recommended.
Statistics show that about 85% of the arc faults on overhead lines extinguish after the protection tripped and
are cleared when re-energizing the line again. The reclosing is performed by an automatic reclose function.
As the possibility of clearing an arc fault does not exists on other equipment, the automatic recloser function
is only permitted on overhead lines. It must not be used in any other case. If the protected object consists of
a mixture of overhead lines and other equipment (e.g. overhead line in block with a transformer or an
overhead line combined with cable), it must be ensured that reclosing can only be performed in the event of
a fault on the overhead line. If the circuit breaker poles can be operated individually, a single-pole automatic
reclosing is usually initiated in the case of single-phase faults and a 3-pole automatic reclose in the case of
phase-to-phase faults. If the fault still exists after reclosure (arc not extinguished or metallic short-circuit), the
protection issues a final trip. In some systems several reclosing attempts are performed. Also it is possible to
initiate the auto reclose function by an external protection device (e.g. a backup protection).
In order to make the reclosing successful, the fault must be cleared at all line ends simultaneously with a
sufficient pause time to de-energize as fast as possible [2].
The following figure shows a line with its protection system that is used as example. The system under test
could be an overcurrent, distance or differential protection. The recloser functionality is mostly the same.
This is an example to illustrate a realistic scheme.
When a fault occurs on the line both relays are configured to trip instantaneously and perform an auto
reclose after two cycles.
Line Data
50 Hz
A Solidly grounded system B
110 kV
CB A 600 A
3-pole 32,5 km CB B
trip time = 50 ms R = 0.193 /km same as CB A
close time = 100 ms X = 0.4 /km
RN/R = 0.6
XN/X = 0.6
CT A CT B
Trip 110 V 600 A / 1 A 600 A / 1 A Trip 110 V
Relay Relay
A B
Figure 2: Example protected line (CT: current transformer, transformer CB: circuit breaker)
1
1
2
1
3
1
The network simulation on the PC transfers transient signals to the test set. Especially when test sets are
deployed over different substations the test set cannot react to external events from the relay in real time
(closed loop). To simulate the real-time behaviour, the transient playback is repeated multiple times. In such
a scheme, the relay reaction in the current iteration is assumed to be the same as the relay reaction
detected in the previous iteration. As long as there are relay reactions, the injection keeps running iteratively
similar to a closed-loop approach.
This test is valid based on the assumption that the relay reactions are consistent in every iteration. The relay
reaction in the binary traces should fall within the time tolerance set for the circuit breaker function of the
previous run. Otherwise, the shot is assigned the error status "inconsistent reaction of relay" and the
injection stops [1].
1. Enable
2. Tolerance
3. Pause
This chapter describes test scenarios that fit to the application. The following chapters describe the test
cases in detail. Because each protection scheme is very individual these test cases are just examples for
tests. They should explain testing methods with RelaySimTest in general.
1. Auto-reclose, two cycles, unsuccessful
2. Auto-reclose, two cycles, successful
3. Auto-reclose, one cycle, successful
Sometimes the behaviour of the protection system depends on the prefault condition. For example, it might
be different if there is a load current during the prefault state. However, for this example, this distinction is
not considered.
Initial simulation:
a. Fault appears after 300 ms > Fault current present
b. Relays trip
a
1
b
1
When the fault current persists, the relay wont trigger a reclose cycle. Therefore RelaySimTest integrates
the opening of the CBs in the simulation when the relays trip. The fault current disappear after the CB
operation time.
First iteration:
a. Fault appears after 300 ms > Fault current raised
b. Relays trip
c. CBs open > Fault current disappears
d. Reclose command triggered
c
1
d
1
Figure 7: Auto reclose First Iteration
Second iteration:
a. Fault appears after 300 ms > Fault current raised
b. Relays trip
c. CBs open > Fault current disappears
d. Reclose command triggered
e. CBs close > Fault current reappears
f. Relays trip
e
1
f
1
The second trip of the CBs will be integrated in the third iteration.
Third iteration:
a. Fault appears after 300 ms > Fault current raised
b. Relays trip
c. CBs open > Fault current disappears
d. Reclose command triggered
e. CBs close > Fault current reappears
f. Relays trip
g. CBs open > Fault current disappears
h. Reclose command triggered
g
1
h
1
Figure 9: Auto reclose Third iteration
i
1
j
1
Fifth iteration:
a. Fault appears after 300 ms > Fault current raised
b. Relays trip
c. CBs open > Fault current disappears
d. Reclose command triggered
e. CBs close > Fault current reappears
f. Relays trip
g. CBs open > Fault current disappears
h. Reclose command triggered
i. CBs close > Fault current reappears
j. Relays trip
k. CBs opens > Fault current disappear
l. No close command will follow
k
1
l
1
Figure 11: Auto reclose Fifth iteration
The measurement for the dead time is done from the breaker trip commands until the close commands rise.
For the second cycle the second signals of the trip and close commands are used.
With a right click on the fault at the single line diagram we can add a fault event.
When the fault event is selected you can adjust the timing of the event. We select a time in the second cycle
for the deactivation of the fault. In the first test case we have seen, that the dead time runs between 1100 ms
and 1700 ms. Therefore we choose for the fault deactivation event a setting of 1500 ms.
Fault event:
Deactivate Fault
The measurement and the assessment for the dead time is done like in test step 1.
It is also possible to perform an end to end test for an auto-reclose function. Therefore synchronized
injection of test currents is necessary. The synchronization ensures that both test sets the local and the
remote one start the test at the same time. This is very important since any inaccuracy can result in an
unexpected relay behavior. For this reason RelaySimTest supports the use of CMGPS 588 an antenna-
integrated GPS controlled time reference to synchronize the starting point of a CMC test process. Each end
needs its own CMGPS 588. It delivers a time signal using PTP (Precision Time Protocol). For more
information about PTP see [3].
Especially after tests with high currents it is sometime necessary to interrupt the test sequence with the Stop
button. This ensures breaks between the tests to avoid too much stress for the relays.
Figure 24: Execute selected and Execute all button for a certain test case (top figure) and in the Test Manager menu (bottom figure)